Greenheck Fan Smoke Alarm FSD 211 User Manual

model Fsd-211  
Combination FIRe smOKe dAmPeRs  
APPLICATION  
Model FSD-211 is a combination fire smoke damper with 3V style  
blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and  
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire  
smoke situations. Model FSD-211 may be installed vertically (with  
blades running horizontal) or horizontally and is rated for airflow and  
leakage in either direction.  
Steel 3-V Blades  
UL 555S Leakage Class I  
UL555 112 Hour Fire Resistance Rating  
Model FSD-211 meets the requirements for fire  
dampers, smoke dampers and combination fire  
smoke dampers established by:  
RATINgs  
UL 555 Fire Resistance Rating  
National Fire Protection Association  
Fire Rating:  
112 Hours  
NFPA Standards 80, 90A, 92A, 92B, 101 & 105  
IBC International Building Codes  
ICBO uniform Building Codes  
CsFm California state Fire marshal  
Fire Damper Listing (#3225-0981:103)  
Leakage (Smoke) Damper Listing (#3230-0981:104)  
New York City (MEA listing #260-91-M)  
Dynamic Closure Rating: Actual ratings are size dependent  
Maximum Velocity:  
Maximum Pressure:  
2000 fpm (10.2 m/s)  
4 in. wg (1 kPa)  
Maximum Temperature: 350ºF (177°C) -- Depending on  
actuator  
UL 555S Leakage Rating  
Leakage Class:  
I
Operational Rating:  
Maximum Velocity:  
Maximum Pressure:  
Actual ratings are actuator dependent  
2000 fpm (10.2 m/s)  
4 in. wg (1 kPa)  
“uL CLAssIFIed (see complete marking on  
product)”  
“uL CLAssIFIed to Canadian safety standards  
(see complete marking on product)”  
Standard 555 & 555S (Listing #R13317)  
Maximum Temperature: 350ºF (177°C) - Depending on  
actuator  
sTANdARd CONsTRuCTION  
Frame:  
5 in. x 1 in. (127mm x 25mm)  
galvanized steel hat channel with  
reinforced corners. A low profile head  
and sill are used on sizes less than  
17 in. (432mm) high to maximize free  
area and performance.  
Greenheck Fan Corporation certifies that the  
model FSD-211 shown herein is licensed to bear  
the AMCA Seal. The ratings shown are based on  
tests and procedures performed in accordance  
with AMCA Publication 511 and comply with  
the requirements of the AMCA Certified Ratings  
Programs. The AMCA Certified Ratings Seal  
applies to air performance ratings only.  
Blades:  
16 ga. (1.5mm) galvanized steel,  
reinforced with 3 longitudinal  
structurally designed vee’s.  
Extruded silicone rubber blade seals  
Flexible stainless steel jamb seals  
Concealed in jamb.  
R
Seals:  
Jamb Seals:  
Linkage:  
Closure Device:  
Axles:  
Bearings:  
UL listed 165°F (74°C) RRL  
12 in. (13mm) dia. plated steel  
Bronze sleeve type  
W*  
sIze LImITATIONs:  
Minimum Size:  
8 in. W x 6 in. H (203mm W x 152mm H)  
Single Section: 32 in. W x 50 in. H  
(813mm W x 1270mm H)  
36 in. W x 48 in. H  
Maximum Size:  
(914mm x 1219mm)  
Multiple Section:  
RH  
Horizontal: 144 in. W x 96 in. H  
(3658mm W x 2438mm H)  
Vertical: 128 in. W x 100 in. H  
(3251mm W x 2540mm H)  
H*  
OPTIONAL FeATuRes:  
• RRL/OCI (Open closed indication switches)  
• Electric or pneumatic actuators  
• POC retaining angles  
• Smoke detectors  
• Momentary switch  
LH  
• Pneumatic Relief Valve (PRV)  
• Security bars  
*W&H dimensions furnished approximately ¼in. (6mm) undersize.  
(Add sleeve thickness for overall sleeved damper dimension)  
Right hand drive is shown. Left hand drive is available upon request.  
• TOR (remote override of 165ºF (74°C) or 212ºF (100°C) closure  
allows damper to perform smoke management functions during a  
fire emergency)  
• 165ºF (74°C), 212°F (100°C), 250ºF (121°C), and 350ºF (177°C)  
RRL's available.  
Installation installations available at www.greenheck.com  
• Sealed transitions and sleeves  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AmCA 5.2 Pressure drop  
Fsd-211  
5D  
Figure 5.2  
12 in. x 12 in. (305mm x 305mm)  
Pressure Drop  
24 in. x 24 in. (610mm x 610mm)  
Pressure Drop  
36 in. x 36 in. (914mm x 914mm)  
Pressure Drop  
12 in. x 48 in. (305mm x 1219mm)  
Pressure Drop  
48 in. x 12 in. (1219mm x 305mm)  
Pressure Drop  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
Velocity (fpm)  
Velocity (fpm)  
Velocity (fpm)  
(in. wg)  
(in. wg)  
(in. wg)  
(in. wg)  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.04  
0.14  
0.31  
0.55  
0.86  
1.24  
1.69  
2.20  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.02  
0.07  
0.16  
0.29  
0.45  
0.65  
0.89  
1.16  
500  
0.01  
0.04  
0.09  
0.16  
0.25  
0.36  
0.49  
0.64  
500  
0.01  
0.06  
0.13  
0.23  
0.36  
0.52  
0.70  
0.92  
500  
0.03  
0.10  
0.23  
0.41  
0.63  
0.91  
1.24  
1.62  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
Greenheck Fan Corporation certifies that the  
model FSD-211 shown herein is licensed to bear  
the AMCA Seal. The ratings shown are based on  
tests and procedures performed in accordance  
with AMCA Publication 511 and comply with the  
requirements of the AMCA Certified Ratings Pro-  
grams. The AMCA Certified Ratings Seal applies to  
air performance ratings only.  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
AmCA 5.3 Pressure drop  
Fsd-211  
5D  
6D  
Figure 5.3  
12 in. x 12 in. (305mm x 305mm)  
Pressure Drop  
24 in. x 24 in. (610mm x 610mm)  
Pressure Drop  
36 in. x 36 in. (914mm x 914mm)  
Pressure Drop  
12 in. x 48 in. (305mm x 1219mm)  
Pressure Drop  
48 in. x 12 in. (1219mm x 305mm)  
Pressure Drop  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.02  
0.09  
0.20  
0.36  
0.56  
0.81  
1.10  
1.44  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.01  
0.04  
0.09  
0.16  
0.25  
0.35  
0.48  
0.63  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.01  
0.03  
0.06  
0.11  
0.17  
0.24  
0.33  
0.42  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.01  
0.04  
0.10  
0.17  
0.27  
0.39  
0.53  
0.70  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.02  
0.07  
0.16  
0.29  
0.45  
0.64  
0.88  
1.14  
Greenheck Fan Corporation certifies that the  
model FSD-211 shown herein is licensed to bear  
the AMCA Seal. The ratings shown are based on  
tests and procedures performed in accordance  
with AMCA Publication 511 and comply with the  
requirements of the AMCA Certified Ratings Pro-  
grams. The AMCA Certified Ratings Seal applies to  
air performance ratings only.  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
AmCA 5.5 Pressure drop  
Fsd-211  
12 in. x 12 in. (305mm x 305mm)  
24 in. x 24 in. (610mm x 610mm)  
36 in. x 36 in. (914mm x 914mm)  
12 in. x 48 in. (305mm x 1219mm)  
48 in. x 12 in. (1219mm x 305mm)  
Pressure Drop  
Pressure Drop  
Pressure Drop  
Pressure Drop  
Pressure Drop  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
Velocity (fpm)  
(in. wg)  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.04  
0.17  
0.38  
0.67  
1.04  
1.50  
2.05  
2.67  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.06  
0.22  
0.50  
0.89  
1.39  
2.00  
2.72  
3.55  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.03  
0.14  
0.31  
0.54  
0.85  
1.22  
1.66  
2.17  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.03  
0.12  
0.26  
0.46  
0.73  
1.05  
1.42  
1.86  
500  
1000  
1500  
2000  
2500  
3000  
3500  
4000  
0.03  
0.13  
0.30  
0.53  
0.83  
1.19  
1.62  
2.11  
Greenheck Fan Corporation certifies that the  
model FSD-211 shown herein is licensed to bear  
the AMCA Seal. The ratings shown are based on  
tests and procedures performed in accordance  
with AMCA Publication 511 and comply with the  
requirements of the AMCA Certified Ratings Pro-  
grams. The AMCA Certified Ratings Seal applies to  
air performance ratings only.  
R
Download from Www.Somanuals.com. All Manuals Search And Download.  
Application data  
damper sleeve dimensional data  
The drawings below and corresponding table show the position of the FSD-211 damper when mounted in a factory sleeve.  
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for  
installation of retaining angles and duct connections.  
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be  
positioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.  
11/2 in.  
max.  
"A" Dimension  
in. (mm)  
Standard  
7 3/16 (183)  
12 (305)  
Maximum  
12 (305)  
12 (305)  
All Dampers*  
33/4  
in.  
When H is 11 in. (279mm) or  
less with OCI, RRL, or TOR  
*With the exception of dampers 10 in. high (254mm) or less.  
NOTE: Entire damper frame is not required to be installed within the  
wall. The damper blades, when closed should be contained within  
the wall.  
6 in.  
RH  
Varies  
53/8 in.  
LH  
Right hand drive is shown  
Left hand drive available upon request  
A
5 in.  
Sleeve Length  
Actuators and Accessories  
space envelopes  
Externally mounted actuators always require space outside  
of the damper sleeve. The “S” dimension illustrates the  
clearance required for various available actuators.  
T*  
S
On dampers less than 18 in. (457mm) high, actuators  
may also require clearances above and/or below the  
sleeve. “B” and “T” dimensions are worst case clearance  
requirements for some dampers less than 18 in. (457mm)  
high. All damper sizes under 18 in. (457mm) high do not  
require these worst case clearances. If space availability  
above or below the damper sleeve is limited, each damper  
size should be individually evaluated.  
B*  
B*  
T*  
Actuator Type/Model  
S
With  
With  
RRL, RRL/OCI, or TOR RRL, RRL/OCI, or TOR  
120 Volt AC  
ML-4XXX Series Honeywell  
MS-4XXX Series Honeywell  
MS-4120 Series Honeywell  
5¼ in. (133mm)  
6 in. (152mm)  
6 in. (152mm)  
¾ in.(19mm)  
3/8 in. (10mm)  
3/8 in. (10mm)  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
24 Volt AC  
ML-8XXX Series Honeywell  
MS-8XXX Series Honeywell  
MS-8120 Series Honeywell  
5¼ in. (133mm)  
6 in. (152mm)  
6 in. (152mm)  
¾ in.(19mm)  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
6 in. (152mm)  
Pneumatic (25 psi min.)  
331-4551 Powers  
331-2976 Powers  
MK2-7121 Invensys  
1 in. (25mm)  
2 3/8 in. (60mm)  
3 3/4 in. (95mm)  
6¼ in. (159mm)  
12 1/8 in. (308mm)  
16½ in. (419mm)  
6½ in. (165mm)  
9¼ in. (235mm)  
10 in. (254mm)  
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .  
Download from Www.Somanuals.com. All Manuals Search And Download.  
damper sizing Information  
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size.  
The following figures show maximum damper section size and assembly configurations for multi-section dampers.  
Double Section  
Single Section  
50 in.  
(1270mm)  
(
50 in.  
(1270mm)  
32 in. (813mm)  
64 in. (1626mm)  
32 in. (813mm)  
When a fire/smoke damper is being used in conjunction with round or oval ductwork, the  
FSD-211 can be supplied in a factory sleeve with round or oval transitions on both ends  
of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show  
overall damper size.  
Transitioned damper  
dimensions  
D*+  
2 in. (51mm) +T  
s
W*+ 2 in. (51mm)+T  
s
W*+ 2 in. (51mm)+T  
s
D*+ 2 in. (51mm)+T  
s
H*+ 2 in. (51mm)+T  
H*+ 2 in. (51mm)+T  
s
s
H*  
H*  
21/8in.  
21/8in.  
(54mm)  
21/8in.  
(54mm)  
(54mm)  
*
W
W*  
D*  
16 in. (406mm)  
Min.  
16 in. (406mm)  
Min.  
16 in. (406mm)  
Min.  
TYPE R  
TYPE O  
TYPE C  
These dimensions are furnished approximately 1/4 in.  
*
(6mm) undersize, except round and oval dimensions which  
are approximately 1/8 in. (3mm) undersize.  
T
= (2)(Sleeve Thickness)  
s
specifications  
Combination Fire Smoke Dampers meeting the following  
reinforced corners. Bearings shall be sintered bronze sleeve type  
rotating in extruded holes in the damper frame. Blade edge seals  
shall be silicone rubber designed to inflate and provide a tighter seal  
against leakage as pressure on either side of the damper increases.  
Jamb seals shall be stainless steel compression type. Blades shall be  
completely symmetrical relative to their axle pivot point, presenting  
identical resistance to airflow in either direction or pressure on either  
side of the damper.  
specifications shall be furnished and installed where shown on  
plans and/or as described in schedules. Dampers shall meet the  
requirements of NFPA 80, 90A, 92A, 92B, 101 & 105 and further shall  
be tested, rated and labeled in accordance with the latest edition  
of UL Standards 555 and 555S. Dampers shall have a UL555 fire  
rating of 1½ hours and be of low leakage design qualified to UL 555S  
Leakage Class I.  
Each damper/actuator combination shall have a UL555S elevated  
temperature rating of 250°F (121°C) minimum and shall be  
The Damper Manufacturer's submittal data shall certify all air  
performance pressure drop data is licensed in accordance with the  
AMCA Certified Ratings Program for Test Figures 5.2, 5.3, and 5.5.  
Damper air performance data shall be developed in accordance with  
the latest edition of AMCA Standard 500-D. Dampers shall be labeled  
with the AMCA Air Performance Seal.  
operational and dynamic rated to operate at maximum design air  
flow at its installed location. Each damper shall be supplied with an  
appropriate actuator installed by the damper manufacturer at the  
time of damper fabrication. Damper actuator shall be (specifier select  
one of the following) electric type for 120 (24 or 230) volt operation or  
pneumatic type for 25 psi minimum (30 psi maximum) operation.  
Damper must be rated for mounting vertically (with blades running  
horizontal) or horizontally and be UL 555S rated for leakage and  
airflow in either direction through the damper. Each damper shall be  
supplied with a 165°F (74°C) RRL. The basis of design is Greenheck  
Model FSD-211.  
Damper blades shall be 16 ga. (1.5mm) galvanized steel 3V type with  
three longitudinal grooves for reinforcement. Damper frame shall  
be galvanized steel formed into a structural hat channel shape with  
Copyright ©2006 Greenheck Fan Corporation  
FSD-211 Rev 3 June 2006  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Grizzly Switch T24101 User Manual
Haier Refrigerator BCF27 User Manual
Hand Held Products PDAs Smartphones 7400 User Manual
Havis Shields Personal Computer C TCB 4 User Manual
Hayter Mowers Lawn Mower 422V User Manual
Honeywell Weather Radio 08060 TH106 TL6061 69 2024 User Manual
Hotpoint Cooktop CH60GTCF User Manual
Hotpoint Microwave Oven DY46 BD42 BD32 User Manual
HP Hewlett Packard Switch 212M User Manual
Husqvarna Chainsaw 340 EPA II User Manual