model Fsd-211
Combination FIRe smOKe dAmPeRs
APPLICATION
Model FSD-211 is a combination fire smoke damper with 3V style
blades. The FSD-211 has been qualified to 2000 fpm (10.2 m/s) and
4 in. wg (1 kPa) for operation and dynamic closure in emergency fire
smoke situations. Model FSD-211 may be installed vertically (with
blades running horizontal) or horizontally and is rated for airflow and
leakage in either direction.
Steel 3-V Blades
UL 555S Leakage Class I
UL555 11⁄2 Hour Fire Resistance Rating
Model FSD-211 meets the requirements for fire
dampers, smoke dampers and combination fire
smoke dampers established by:
RATINgs
UL 555 Fire Resistance Rating
National Fire Protection Association
Fire Rating:
11⁄2 Hours
NFPA Standards 80, 90A, 92A, 92B, 101 & 105
IBC International Building Codes
ICBO uniform Building Codes
CsFm California state Fire marshal
Fire Damper Listing (#3225-0981:103)
Leakage (Smoke) Damper Listing (#3230-0981:104)
New York City (MEA listing #260-91-M)
Dynamic Closure Rating: Actual ratings are size dependent
Maximum Velocity:
Maximum Pressure:
2000 fpm (10.2 m/s)
4 in. wg (1 kPa)
Maximum Temperature: 350ºF (177°C) -- Depending on
actuator
UL 555S Leakage Rating
Leakage Class:
I
Operational Rating:
Maximum Velocity:
Maximum Pressure:
Actual ratings are actuator dependent
2000 fpm (10.2 m/s)
4 in. wg (1 kPa)
“uL CLAssIFIed (see complete marking on
product)”
“uL CLAssIFIed to Canadian safety standards
(see complete marking on product)”
Standard 555 & 555S (Listing #R13317)
Maximum Temperature: 350ºF (177°C) - Depending on
actuator
sTANdARd CONsTRuCTION
Frame:
5 in. x 1 in. (127mm x 25mm)
galvanized steel hat channel with
reinforced corners. A low profile head
and sill are used on sizes less than
17 in. (432mm) high to maximize free
area and performance.
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with
the requirements of the AMCA Certified Ratings
Programs. The AMCA Certified Ratings Seal
applies to air performance ratings only.
Blades:
16 ga. (1.5mm) galvanized steel,
reinforced with 3 longitudinal
structurally designed vee’s.
Extruded silicone rubber blade seals
Flexible stainless steel jamb seals
Concealed in jamb.
R
Seals:
Jamb Seals:
Linkage:
Closure Device:
Axles:
Bearings:
UL listed 165°F (74°C) RRL
1⁄2 in. (13mm) dia. plated steel
Bronze sleeve type
W*
sIze LImITATIONs:
Minimum Size:
8 in. W x 6 in. H (203mm W x 152mm H)
Single Section: 32 in. W x 50 in. H
(813mm W x 1270mm H)
36 in. W x 48 in. H
Maximum Size:
(914mm x 1219mm)
Multiple Section:
RH
Horizontal: 144 in. W x 96 in. H
(3658mm W x 2438mm H)
Vertical: 128 in. W x 100 in. H
(3251mm W x 2540mm H)
H*
OPTIONAL FeATuRes:
• RRL/OCI (Open closed indication switches)
• Electric or pneumatic actuators
• POC retaining angles
• Smoke detectors
• Momentary switch
LH
• Pneumatic Relief Valve (PRV)
• Security bars
*W&H dimensions furnished approximately ¼in. (6mm) undersize.
(Add sleeve thickness for overall sleeved damper dimension)
Right hand drive is shown. Left hand drive is available upon request.
• TOR (remote override of 165ºF (74°C) or 212ºF (100°C) closure
allows damper to perform smoke management functions during a
fire emergency)
• 165ºF (74°C), 212°F (100°C), 250ºF (121°C), and 350ºF (177°C)
RRL's available.
Installation installations available at www.greenheck.com
• Sealed transitions and sleeves
Download from Www.Somanuals.com. All Manuals Search And Download.
AmCA 5.2 Pressure drop
Fsd-211
5D
Figure 5.2
ꢀ
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Velocity (fpm)
Velocity (fpm)
Velocity (fpm)
Velocity (fpm)
Velocity (fpm)
500
1000
1500
2000
2500
3000
3500
0.04
0.14
0.31
0.55
0.86
1.24
1.69
500
1000
1500
2000
2500
3000
3500
0.02
0.07
0.16
0.29
0.45
0.65
0.89
500
0.01
0.04
0.09
0.16
0.25
0.36
0.49
500
0.01
0.06
0.13
0.23
0.36
0.52
0.70
500
0.03
0.10
0.23
0.41
0.63
0.91
1.24
1000
1500
2000
2500
3000
3500
1000
1500
2000
2500
3000
3500
1000
1500
2000
2500
3000
3500
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to
air performance ratings only.
R
Download from Www.Somanuals.com. All Manuals Search And Download.
AmCA 5.3 Pressure drop
Fsd-211
5D
6D
Figure 5.3
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
Velocity (fpm)
(in. wg)
500
1000
1500
2000
2500
3000
3500
0.02
0.09
0.20
0.36
0.56
0.81
1.10
500
1000
1500
2000
2500
3000
3500
0.01
0.04
0.09
0.16
0.25
0.35
0.48
500
1000
1500
2000
2500
3000
3500
0.01
0.03
0.06
0.11
0.17
0.24
0.33
500
1000
1500
2000
2500
3000
3500
0.01
0.04
0.10
0.17
0.27
0.39
0.53
500
1000
1500
2000
2500
3000
3500
0.02
0.07
0.16
0.29
0.45
0.64
0.88
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to
air performance ratings only.
R
Download from Www.Somanuals.com. All Manuals Search And Download.
AmCA 5.5 Pressure drop
Fsd-211
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Pressure Drop
Velocity (fpm)
Velocity (fpm)
Velocity (fpm)
Velocity (fpm)
Velocity (fpm)
500
1000
1500
2000
2500
3000
3500
0.04
0.17
0.38
0.67
1.04
1.50
2.05
500
1000
1500
2000
2500
3000
3500
0.06
0.22
0.50
0.89
1.39
2.00
2.72
500
1000
1500
2000
2500
3000
3500
0.03
0.14
0.31
0.54
0.85
1.22
1.66
500
1000
1500
2000
2500
3000
3500
0.03
0.12
0.26
0.46
0.73
1.05
1.42
500
1000
1500
2000
2500
3000
3500
0.03
0.13
0.30
0.53
0.83
1.19
1.62
Greenheck Fan Corporation certifies that the
model FSD-211 shown herein is licensed to bear
the AMCA Seal. The ratings shown are based on
tests and procedures performed in accordance
with AMCA Publication 511 and comply with the
requirements of the AMCA Certified Ratings Pro-
grams. The AMCA Certified Ratings Seal applies to
air performance ratings only.
R
Download from Www.Somanuals.com. All Manuals Search And Download.
Application data
damper sleeve dimensional data
The drawings below and corresponding table show the position of the FSD-211 damper when mounted in a factory sleeve.
The standard mounting locations provide enough space for the mounting of actuators, controls and allow space for
installation of retaining angles and duct connections.
The standard location of a damper mounted in a factory sleeve ("A" dimension) is shown below. The damper can be
positioned at other locations within a range of 6 in. (152mm) to 12 in. (305mm) for the "A" dimension.
11/2 in.
max.
"A" Dimension
in. (mm)
Standard
7 3/16 (183)
12 (305)
Maximum
12 (305)
12 (305)
All Dampers*
33/4
in.
When H is 11 in. (279mm) or
less with OCI, RRL, or TOR
*With the exception of dampers 10 in. high (254mm) or less.
NOTE: Entire damper frame is not required to be installed within the
wall. The damper blades, when closed should be contained within
the wall.
6 in.
RH
Varies
53/8 in.
LH
Right hand drive is shown
Left hand drive available upon request
A
5 in.
Sleeve Length
Actuators and Accessories
space envelopes
Externally mounted actuators always require space outside
of the damper sleeve. The “S” dimension illustrates the
clearance required for various available actuators.
T*
S
On dampers less than 18 in. (457mm) high, actuators
may also require clearances above and/or below the
sleeve. “B” and “T” dimensions are worst case clearance
requirements for some dampers less than 18 in. (457mm)
high. All damper sizes under 18 in. (457mm) high do not
require these worst case clearances. If space availability
above or below the damper sleeve is limited, each damper
size should be individually evaluated.
B*
B*
T*
Actuator Type/Model
S
With
With
RRL, RRL/OCI, or TOR RRL, RRL/OCI, or TOR
120 Volt AC
ML-4XXX Series Honeywell
MS-4XXX Series Honeywell
MS-4120 Series Honeywell
5¼ in. (133mm)
6 in. (152mm)
6 in. (152mm)
¾ in.(19mm)
3/8 in. (10mm)
3/8 in. (10mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
24 Volt AC
ML-8XXX Series Honeywell
MS-8XXX Series Honeywell
MS-8120 Series Honeywell
5¼ in. (133mm)
6 in. (152mm)
6 in. (152mm)
¾ in.(19mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
6 in. (152mm)
Pneumatic (25 psi min.)
331-4551 Powers
331-2976 Powers
MK2-7121 Invensys
1 in. (25mm)
2 3/8 in. (60mm)
3 3/4 in. (95mm)
6¼ in. (159mm)
12 1/8 in. (308mm)
16½ in. (419mm)
6½ in. (165mm)
9¼ in. (235mm)
10 in. (254mm)
* For dampers 18 in. (457mm) or more in height these dimensions are 0 in. .
Download from Www.Somanuals.com. All Manuals Search And Download.
damper sizing Information
Dampers larger than maximum single section size are supplied as a factory assembly of two or more sections of equal size.
The following figures show maximum damper section size and assembly configurations for multi-section dampers.
Double Section
Single Section
50 in.
(1270mm)
(
50 in.
(1270mm)
32 in. (813mm)
64 in. (1626mm)
32 in. (813mm)
When a fire/smoke damper is being used in conjunction with round or oval ductwork, the
FSD-211 can be supplied in a factory sleeve with round or oval transitions on both ends
of the sleeve. Dampers should be ordered to the duct dimensions. Drawings below show
overall damper size.
Transitioned damper
dimensions
D*+
2 in. (51mm) +T
s
W*+ 2 in. (51mm)+T
s
W*+ 2 in. (51mm)+T
s
D*+ 2 in. (51mm)+T
s
H*+ 2 in. (51mm)+T
H*+ 2 in. (51mm)+T
s
s
H*
H*
21/8in.
21/8in.
(54mm)
21/8in.
(54mm)
(54mm)
*
W
W*
D*
16 in. (406mm)
Min.
16 in. (406mm)
Min.
16 in. (406mm)
Min.
TYPE R
TYPE O
TYPE C
These dimensions are furnished approximately 1/4 in.
*
(6mm) undersize, except round and oval dimensions which
are approximately 1/8 in. (3mm) undersize.
T
= (2)(Sleeve Thickness)
s
specifications
Combination Fire Smoke Dampers meeting the following
reinforced corners. Bearings shall be sintered bronze sleeve type
rotating in extruded holes in the damper frame. Blade edge seals
shall be silicone rubber designed to inflate and provide a tighter seal
against leakage as pressure on either side of the damper increases.
Jamb seals shall be stainless steel compression type. Blades shall be
completely symmetrical relative to their axle pivot point, presenting
identical resistance to airflow in either direction or pressure on either
side of the damper.
specifications shall be furnished and installed where shown on
plans and/or as described in schedules. Dampers shall meet the
requirements of NFPA 80, 90A, 92A, 92B, 101 & 105 and further shall
be tested, rated and labeled in accordance with the latest edition
of UL Standards 555 and 555S. Dampers shall have a UL555 fire
rating of 1½ hours and be of low leakage design qualified to UL 555S
Leakage Class I.
Each damper/actuator combination shall have a UL555S elevated
temperature rating of 250°F (121°C) minimum and shall be
The Damper Manufacturer's submittal data shall certify all air
performance pressure drop data is licensed in accordance with the
AMCA Certified Ratings Program for Test Figures 5.2, 5.3, and 5.5.
Damper air performance data shall be developed in accordance with
the latest edition of AMCA Standard 500-D. Dampers shall be labeled
with the AMCA Air Performance Seal.
operational and dynamic rated to operate at maximum design air
flow at its installed location. Each damper shall be supplied with an
appropriate actuator installed by the damper manufacturer at the
time of damper fabrication. Damper actuator shall be (specifier select
one of the following) electric type for 120 (24 or 230) volt operation or
pneumatic type for 25 psi minimum (30 psi maximum) operation.
Damper must be rated for mounting vertically (with blades running
horizontal) or horizontally and be UL 555S rated for leakage and
airflow in either direction through the damper. Each damper shall be
supplied with a 165°F (74°C) RRL. The basis of design is Greenheck
Model FSD-211.
Damper blades shall be 16 ga. (1.5mm) galvanized steel 3V type with
three longitudinal grooves for reinforcement. Damper frame shall
be galvanized steel formed into a structural hat channel shape with
Copyright ©2006 Greenheck Fan Corporation
FSD-211 Rev 3 June 2006