Greenheck Fan Humidifier HRE 20 User Manual

PART #461248  
READ AND SAVE THESE INSTRUCTIONS  
HEAT RECOVERY UNIT  
WITH EVAPORATIVE COOLING  
®
Models:  
HRE-20, 45, 55, & 90  
INSTALLATION, OPERATION AND MAINTENANCE MANUAL  
**WARNING**  
DISCONNECT AND SECURE TO THE "OFF" POSITION ALL ELECTRICAL POWER TO THE UNITS  
PRIOR TO INSPECTION OR SERVICING. FAILURE TO COMPLY WITH THIS SAFETY PRECAUTION  
COULD RESULT IN SERIOUS INJURY OR DEATH.  
**IMPORTANT**  
ALL FACTORY PROVIDED LIFTING LUGS MUST BE USED WHEN LIFTING THE UNITS. FAILURE TO  
COMPLY WITH THIS SAFETY PRECAUTION COULD RESULT IN PROPERTY DAMAGE, SERIOUS  
INJURY OR DEATH.  
Indirect Evaporative Cooler  
(Exhaust/Scavenger Airstream)  
Direct Evaporative Cooler  
(Outdoor/Supply Airstream)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION  
The system design and installation should follow  
accepted industry practice, such as described in the  
ASHRAE Handbook.  
Adequate space should be left around the unit for  
piping coils and drains, filter replacement, and  
maintenance. Sufficient space should be provided on  
the side of the unit for routine service and component  
removal should that become necessary.  
Lift using lifting  
lugs and  
See pages 6 and 7 for more detail on appropriate  
clearances.  
spreader bar  
LIFTING  
Units must be lifted as it ships from the factory. All  
units are equipped with lifting lugs. THE USE OF ALL  
LIFTING LUGS IS MANDATORY WHEN LIFTING.  
Lifting should only be done with all access doors  
closed to avoid damaging the unit. To prevent  
damage to the unit cabinetry, use spreader bars.  
Spreader bars must be in position to stop cables from  
rubbing the frame or panels. Before hoisting into  
position, test lift to insure stability and balance. Avoid  
twisting or uneven lifting of the unit. Never lift units by  
weatherhoods.  
FIGURE 1  
UNIT WEIGHTS (dry weights)  
Unit Size Approx. Weight (lbs)  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
1500  
2300  
3000  
5000  
V
RECOMMENDED ROOF OPENING  
Model  
U
V
EXHAUST  
INLET  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
46  
54  
65  
85  
37  
39  
47  
49  
U
SUPPLY  
OUTLET  
All dimensions shown are in inches.  
FIGURE 2  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROOF CURB MOUNTING  
1. Factory Supplied Roof Curbs  
Roof curbs are Model GKD, which are shipped in a  
knockdown kit and require field assembly (by  
others). Assembly instructions are included with  
the curb.  
2. Cut Roof Opening and Locate Curb  
Layout the unit roof opening such that the supply  
discharge & exhaust inlet of the unit will line up  
with the corresponding ductwork (refer to  
Recommended Roof Openings on page 3). Be  
sure to allow for the recommended service  
clearances. Keep the supply inlet of the unit away  
from any other exhaust fans.  
3. Install Curb  
Locate curb over roof opening and fasten in place.  
Check that the diagonal dimensions are within  
1/8 inch of each other and adjust as necessary.  
Shim as required to level. Lower unit onto curb by  
following the LIFTING instructions on page 3 of  
this manual. Note,  
roof curbs fit inside  
the unit base.  
Curb Outside Dimensions  
Model  
L
W
4. Install Duct Work  
Installation of all  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
93  
51  
L
100.5  
112.75  
60.63  
71.5  
W
ducts should be  
done in accordance  
with SMACNA and  
AMCA guidelines.  
125.75 90.75  
FIGURE 3  
All dimensions shown are in inches.  
DUCT WORK CONNECTIONS  
Examples of good and poor fan-to-duct connections are shown below (See FIGURE 4). Airflow out of the fan  
should be directed straight or curve the same direction as the fan wheel rotates. Poor duct installation will result  
in low airflow and other system effects.  
n
o
i
t
n
o
i
t
Length of Straight Duct  
a
t
a
t
o
o
R
R
GOOD  
POOR  
FIGURE 4  
SUPPLY WEATHERHOOD  
Supply weatherhood will be factory mounted.  
EXHAUST WEATHERHOOD  
The exhaust weatherhood is shipped separately as a kit with its own instructions.  
EXHAUST DAMPERS  
Backdraft dampers for exhaust discharge are mounted in the unit. Motorized dampers are shipped loose (inside  
HRE) and must be field installed.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION (continued)  
ELECTRICAL CONNECTIONS  
The electrical supply must be compatible with that shown on the nameplate: voltage, phase, and amperage  
capacity. The electrical supply line must be properly fused and conform to local and national electrical codes.  
All internal electrical components are pre-wired at the factory. Field electrical connections only need to be made  
inside the unit to the main disconnect (See FIGURE 5, Item #1) and the 24 volt control circuit (See FIGURE 5,  
Item #7). A door interlocking safety disconnect is provided as standard feature.  
Note: Standard factory installed electric post heaters have their own disconnect separate from the unit  
disconnect. Thus, electric post heaters require a separate power connection.  
IMPORTANT:  
Use minimum 14 ga. wire for 24 volt control power.  
Control wire resistance should not exceed 0.75 ohms (approximately 285 feet total length for  
14 ga. wire; 455 feet total length for 12 ga. wire). If wire resistance exceeds 0.75 ohms, an  
industrial-style, plug-in relay should be added to the unit control center and wired in place of  
the remote switch (between terminal blocks 2 and 3 on the control strip — See FIGURE 5,  
Item #7). The relay must be rated for at least 5 amps and have a 24 Vac coil. Failure to  
comply with these guidelines may cause motor starters to “chatter” or not pull in which can  
cause contactor failures and/or motor failures.  
TYPICAL CONTROL CENTER COMPONENTS  
1. Main Disconnect  
2. Motor Starter — Exhaust/Scavenger  
Air Fan  
3. Motor Starter — Outdoor Air Fan  
4. Motor Contactor — Energy Wheel  
5. Control Power Transformer  
(24 VAC Secondary)  
6. Energy Wheel Motor Transformer  
(230 VAC Secondary)  
(for HRE-20 & HRE-45 units with  
primary voltage greater than 230 Vac)  
7. 24 VAC Terminal strip  
1
8
5
6
8. Fuses for the control circuit, wheel  
drive transformer, and blower  
motors.  
7
4
Control Center  
O
f
f
On  
3
2
Main  
Disconnect  
Intake  
Hood  
FIGURE 5  
Exhaust  
Hood  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE CLEARANCES / ACCESS PANEL LOCATIONS for Model HRE  
HRE-20, 45, 55, and 90 units require minimum clearances for access on all sides for routine maintenance. Filter  
replacement, drain pan inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and  
belt adjustment, are examples of routine maintenance that must be performed. Blower and motor assemblies,  
energy recovery wheel cassette, coil and filter sections are always provided with a service door or panel for  
proper component access. Clearances for component removal may be greater than the service clearances,  
refer to FIGURES 6 and 7 below for these dimensions.  
Clearances for service and component removal on HRE-20 and HRE-45  
36 in.  
Exhaust  
Hood  
Access Panel  
Electrical Box  
36 in.  
Indirect  
Evap  
Section  
0 in.  
Exhaust Air  
Intake  
Clearance without  
IG Heater  
52 in.  
Clearance with  
IG Heater  
Direct  
Evap  
Section  
Access Panel  
*48 in. **64 in.  
TOP VIEW  
*Clearance for energy wheel removal on HRE-20.  
**Clearance for energy wheel removal on HRE-45.  
FIGURE 6  
Clearances for service on HRE-55 and HRE-90  
42 in.  
Exhaust  
Hood  
Access Panel  
Electrical Box  
42 in.  
Indirect  
Evap  
Section  
0 in.  
Exhaust Air  
Intake  
Clearance without  
IG Heater  
52 in.  
Clearance with  
IG Heater  
Direct  
Evap  
Section  
Access Panel  
42 in.  
TOP VIEW  
FIGURE 7  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Evaporative Cooling Modules  
Indirect Evaporative Cooler  
(Exhaust/Scavenger Airstream)  
It is important to mount the heat recovery unit level to  
ensure proper operation and water drainage. Piping  
should be of adequate size to provide sufficient  
supply of water to meet the maximum demand of the  
evaporative coolers.  
Evap Module Start-Up  
1. After the energy recovery unit is set in place, run  
the overflow and drain lines to the exterior fittings  
on the evaporative cooler (drain & overflow  
connections at unit are 34-inch female pipe thread).  
The supply line can be attached at the  
downstream side of the evaporative cooler. A  
manual shut off valve should be mounted in the  
supply line near the unit for servicing purposes.  
Also, a trap should be installed in the drain line to  
prevent sewer gas from being drawn into the unit  
(see Figure 8).  
Direct Evaporative Cooler  
(Outdoor/Supply Airstream)  
2. The cooler will be prewired by the factory.  
6. After the media break-in period, the water flow  
rate over the media needs to be checked. The  
pumps should provide enough water to saturate  
the media in 1-3 minutes. If adequate flow rate is  
not achieved, consult with the factory.  
3. Check to make sure that the pump filter is around  
the pump inlet.  
4. Turn the water on and allow the pan to fill up with  
water. The float should be adjusted to provide 2  
inches of water depth in the sump.  
7. The water bleed-off rate will now need to be  
adjusted. This measurement is 3 to 6 percent of  
the media flow rate. The recommended flow rate is  
112 to 2 GPM per  
5. Saturate the media without any airflow through the  
unit. A jumper wire is required on the terminal strip  
to provide power to the evaporative cooler pump  
(see the wiring diagram for the proper location).  
This saturation process will break-in the media and  
minimize the odors associated with the media. The  
media’s break-in period should be no less than 20  
minutes. When the process is complete, remove  
the jumper wires in the control center.  
Unit Size Media Pad Top Area  
square foot of  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
1.5 ft2  
2 ft2  
2.5 ft2  
3.3 ft2  
media pad top area  
(see table at right).  
After the unit has  
been installed and  
running for two  
weeks the unit should be checked for mineral  
deposits. If there are deposits, the bleed-off rate  
needs to be increased. Some areas of the country  
have water with greater amounts of dissolved  
minerals requiring a higher bleed-off rate.  
Note: Evaporative media may foam for a short  
period following the initial start-up. Leave  
the bleed-off valve fully open until the  
foaming stops.  
8. Verify that both airflow and system static pressure  
are in agreement with the specifications. If these  
conditions are met, check for water carry over  
from the discharge side of the media. If carry over  
is observed, check the distribution header for  
holes or tears and the  
Side of HRE Unit  
Drain Line  
Evaporative  
Cooling  
water standoff tube for  
blockage.  
Overflow  
Media  
Sump  
Trap  
9. After all final  
Manual  
Shutoff  
Valve  
adjustments are made,  
remove the jumper  
wires and replace all  
Drain  
Line  
Roof Curb  
access panels. The  
unit is now ready for  
operation.  
Roof Line  
Manual Shutoff Valve  
Supply Line  
FIGURE 8  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
WATER CONTROL OPTIONS FOR EVAPORATIVE COOLING  
Auto Drain and Fill with Freeze Protection  
This system will automatically drain the sump tank and fill it with fresh water at the field adjustable intervals,  
typically once every 24 hours. This flushes mineral build-up and debris from the tank to promote low  
maintenance and increase media pad life. In addition, the system will protect the evaporative cooler from  
freezing by draining the sump tank and supply line when the outside temperatures fall below the set point of the  
outside air sensor. Typically, this is set at 45º to 50º F. The auto drain and fill control box should be installed in  
an area that is shaded from direct sunlight so the outside air sensor probe will detect an accurate air  
temperature.  
Plumbing (see FIGURE 9)  
1. Run water supply line to the unit and install Water Supply Solenoid Valve (A) in this line as close to the water  
source as possible.  
2. Install Drain Solenoid Valve (B) in the supply line as indicated below. From the outlet on the drain valve, run line  
to a suitable drain location.  
3. Run an unobstructed drain line from the sump overflow to the drain as shown below.  
4. Install Sump Drain Solenoid Valve (C) in the drain line from the sump as indicated below. From the outlet on  
this drain valve, run a line to a suitable drain location.  
Note: Water Supply Solenoid Valve  
(A) is not the same as the  
Drain Solenoid valves (B) and  
(C). Make sure to use the  
Side of HRE Unit  
proper valve for each location.  
Check your local code  
Sump Drain Pipe  
requirements for proper  
installation of this type of  
system. Additional drain and  
supply plumbing may be  
needed to meet your local  
code.  
Evaporative  
Cooling  
Media  
Sump Overflow Pipe  
Sump  
Caution: All solenoid valves A, B,  
and C must be installed below the  
roof to protect the supply water line  
from freezing. If these valves cannot  
be installed below the roof, an  
Roof Curb  
Roof Line  
Sump Drain  
Solenoid  
Valve (C)  
alternate method must be used to  
protect these lines from freezing.  
Water Supply  
Solenoid Valve (A)  
Drain  
Solenoid  
Valve (B)  
Supply Line  
Trap  
Drain  
Line  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
TROUBLE SHOOTING FOR EVAPORATIVE MODULE  
Symptom  
Solution  
Insufficient water  
A. Check water level in base pan. The level should be at 2 inches.  
B. Check the pump filter at the inlet. Clean the filter if clogged or dirty.  
C. If pump is not operating, check wiring for loose connections and proper  
voltage.  
volume or recirculation  
pump not operating  
Irregular water  
distribution on cooling  
media  
Water distribution header, orifices or media partially blocked or plugged.  
Remove evaporative cooler from unit.  
Disassemble and clean distribution header, orifices and media.  
A. Check water flow across the face of the media. Irregular water distribution  
must be corrected (see above)  
Scale and mineral  
deposit formation on  
face of media  
B. Increase water flow rate. Media is self cleaning with flow rate of 112 to 2  
gpm per square foot of media top area. Generally this flow rate prevents  
dissolved solvents from collecting on the media. To prevent further trouble,  
flush and clean the system more frequently.  
C. If this condition persists, chemicals may need to be added. Water pH  
should be maintained between 6 and 8.  
A. Irregular water distribution on face of media (see above).  
B. Average face velocity exceeds 650 fpm. Decrease fan rpm and airflow.  
C. Localized face velocities exceeding 650 fpm. Air filters or media face area  
is partially blocked. Clean or replace air filters and media.  
D. Check the overflow for blockage.  
Water Carry-Over  
A. Irregular water distribution over face of media (see above).  
B. Check for uniform air flow.  
Inadequate cooling  
C. Check outside wet-bulb temperature. High wet-bulb temperatures can  
decrease performance.  
D. Check water flow rate over media. Flow rate should be 112 to 2 gpm per  
square foot of media top area.  
A. Check the water bleed off rate and make sure that it is not excessive.  
B. Check water level in base pan. The level should be at 2 inches.  
Excessive water  
discharge into drain  
Pad installed backwards. To get the  
performance from the cooling pads,  
they must be installed properly. The  
pads are manufactured with 15/45  
degree flute angles. The pads must  
always be installed with the steeper  
flute angle sloping down toward the  
entering air side. See figure on right.  
Poor performance after  
cooling pad  
replacement  
45°  
Entering Air  
Leaving Air  
15°  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
EVAPORATIVE COOLING MAINTENANCE  
Regularly scheduled maintenance is the key to peak  
performance, minimized cost, and extended life of the  
evaporative cooler. The following is a checklist of  
Continuous operation in this manner may cause  
serious damage and void the warranty.  
items that need to be looked at on a regular basis.  
7. At the end of each cooling season the  
evaporative cooler should be thoroughly cleaned.  
A dispersant and biocide (consult water  
1. The media should be checked for mineral and  
foreign material deposits that have built up. If  
these items are left on the media, the life and  
performance of the unit will be greatly reduced.  
Also, there are risks of water carry over when this  
type of condition exists. When signs of mineral  
build-up are noticed, you should increase the  
bleed off rate. If this does not solve the problem,  
chemicals may need to be added to the water.  
The evaporative pads tend to be self cleaning.  
Depending on water quality and system  
treatment consultant for suitable materials and  
dosage levels) should be recirculated for 12 to 24  
hours prior to performing the following steps:  
a) Disconnect power to unit.  
b) Shut off all water to the unit  
c) Open evaporative cooling section door  
d) Flush distribution headers and media for 20  
minutes  
e) Turn off pumps and drain all water distribution  
piping, headers, etc.  
maintenance, the useful life of the pads should  
be 3 to 5 years.  
f) Dry media completely by running blowers.  
g) Brush media as described in Paragraph 2 and  
perform steps d and e again.  
h) Clean all remaining components (i.e. sump,  
pump, etc.) of any mineral deposits or foreign  
materials  
2. The media should be periodically brushed lightly  
with a soft bristle brush in an up and down  
motion (never brush side-to-side) while flushing  
with water. This will also aid in reducing the  
amount of foreign material build-up.  
i) Replace all worn or non-functioning parts  
j) Reassemble the cooling unit.  
k) Close cooling section door.  
3. The water should be shut off and all the lines  
drained when the temperature drops below 50°F.  
l) Turn the main disconnect 'ON', leaving the  
cooling switch in the 'OFF' position.  
4. When the evaporative cooler is going to be used  
for the first time each season, it is recommended  
that the media be flushed with clean water for a  
period of 2 minutes (see Evap Module Start-Up  
on page 7).  
8. If the evaporative cooler will be turned off during  
the cooling season for an extended period of  
time, it is recommended that the media be dried  
out. This can be accomplished by allowing the  
blowers to continue to run for 1-2 hours. Doing  
so, will prevent organic build-up on the media  
and subsequent odors getting into the space.  
5. At the beginning of each cooling season, the  
upright recirculating pump should have the shaft  
oiled and spun to eliminate the potential of  
seizing and pump burn out.  
9. Media should be permitted to dry once per week  
by allowing the blowers to run for 1-2 hours.  
6. If the cooling media was removed from the unit,  
check to make sure that is not installed  
backwards. If the media is installed backwards,  
there will be large amounts of water carry over  
downstream of the evaporative cooler.  
10. A flush cycle should be performed weekly for one  
hour with the fans off.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WATER COIL APPLICATION  
RECOMMENDATIONS  
Factory installed heating components are  
mounted down stream of the energy wheel (and  
direct evaporative cooler if supplied) on the  
supply air side of the unit.  
See FIGURE 10 for coil connection location. Coil  
connections are located external to the unit as  
shown. Coil connections that are not external  
have been ordered from the factory with interior  
or exhaust air stream coil connections.  
Water coil  
connections  
FIGURE 10  
1. Piping should be in accordance with accepted  
industry standards. Pipework should be supported  
independently of the coils. Water connections are  
male NPT iron pipe. When installing couplings, do  
not apply undue stress to the connection  
extending through the unit. Use a backup pipe  
wrench to avoid breaking the weld between coil  
connection and header.  
release all of the air from the coil. To maintain heat  
transfer capacity, periodically vent any air in coil.  
4. Water coils are not normally recommended for use  
with entering air temperatures below 40oF;  
however, the energy recovery wheel maintains a  
pre-coil temperature higher than 40oF. No control  
system can be depended on to be 100% safe  
against freeze-up with water coils. Glycol  
solutions or brines are the only safe media for  
operation of water coils with low entering air  
conditions.  
2. Connect the WATER SUPPLY TO THE BOTTOM  
CONNECTION on the air leaving side and the  
WATER RETURN TO THE TOP CONNECTION on  
the air entering side. To insure proper venting, an  
external air vent in the piping is recommended.  
Connecting the supply and/or return in any other  
manner will result in very poor performance. Be  
sure to replace factory installed grommets around  
coil connections if removed for piping. Failure to  
replace grommets will result in water leakage into  
the unit and altered performance.  
CONTINUOUS WATER CIRCULATION THROUGH  
THE COIL AT ALL TIMES IS HIGHLY  
RECOMMENDED.  
5. Pipe sizes for the system must be selected on the  
basis of the head (pressure) available from the  
circulation pump. The velocity should not exceed  
6 feet per second and the friction loss should be  
approximately 3 feet of water column per 100 feet  
of pipe.  
3. The air vent at the uppermost point should be  
temporarily opened during system start-up to  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRIC HEATER APPLICATION/OPERATION  
Factory installed electric heaters can be provided for preheat and/or post-heat (see FIGURE 11). An electric  
preheater warms the outdoor air prior to the energy recovery wheel to prevent frosting on the wheel. An electric  
post-heater warms the air leaving the energy recovery wheel to a user specified discharge temperature. Electric  
heaters are available in 208, 230, or 460 Vac (refer to heater nameplate for voltage).  
Preheaters:  
Preheaters are standard as 2-stage, step control. Step control heaters are designed with  
multiple stages made up of equal increments of heating capability. For example, a 10 kW  
heater with two stages will be composed of two 5-kW stages. Preheaters are single point  
wired at the factory. A temperature sensor (with field adjustable set point) is mounted in the  
outdoor airstream after the preheater to turn the preheater on. See FROST CONTROL  
APPLICATION/OPERATION for typical set points. If the outdoor air temperature falls below the  
set point, the first stage of the preheater will turn on. If the first stage does not satisfy the set  
point, the second stage will also turn on.  
Post-heaters: Post-heaters are standard as 4-stage, step control. Post-heaters are not single point wired  
(see ELECTRICAL CONNECTIONS, page 5). The functionality of a 4-stage heater is the same  
as the 2-stage preheater above, except it has an additional two stages of heat control.  
Post-heaters supplied with Greenheck temperature control package are 3-stage with binary  
control that provides 7 steps of heating. For example, a 35 kW heater with three stages will be  
composed of 5, 10, and 20 kW stages. The stages essentially ‘mix and match’ to provide heat  
output from 5 kW to 35 kW, in 5 kW increments.  
FIGURE 11  
Disconnect  
Post-Heater Control Panel  
The post-heater is not single point  
wired to the HRE control center.  
Separate power must be supplied  
to the post-heater disconnect.  
Access to the post-heater control  
panel is through the exhaust filter  
door. The top portion of the indirect  
evaporative cooling media must be  
removed from the unit along with  
the exhaust filters.  
Electric Preheater  
The preheater is single point  
wired to the HRE control  
center. Access to the  
Electric Post-Heater  
preheater control panel is  
through the supply filter door.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FROST CONTROL APPLICATION/OPERATION  
When outdoor air temperatures are extremely cold, moisture condensation and frosting on the energy recovery  
wheel is possible. Frost control is an optional feature that will prevent wheel frosting. Two options are available:  
1) Timed Exhaust frost control and  
2) Preheat frost control  
Timed exhaust frost control includes a thermostat (with  
Indoor RH @ 70°F  
Frost Threshold Temp  
probe) mounted in the supply air inlet compartment (see  
FIGURE 13, page 14) and a timer (Figure 12) mounted in the  
HRE control center. The thermostat will turn on the timed  
exhaust frost control feature at a predetermined field  
adjustable outdoor air temperature (referred to as the Frost  
Threshold temperature). The typical temperature setting  
20%  
25%  
30%  
2°F  
7°F  
14°F  
TABLE 1  
corresponds to the indoor air relative humidity as shown in TABLE 1.  
Testing (refer to FIGURE 12)  
• Set the Timer Scale for T1 and T2 to 1 minute. Set  
the Timer Settings for T1 and T2 to 1.0. Set the dip  
switch to the down position.  
Turn the temperature sensor up as high as possible.  
The supply blower should cycle on for one minute,  
then turn off for one minute.  
A1  
B1  
15  
0.8 0.6  
1.0 0.4  
0.2  
Dip  
Switch  
0
• After testing, set the Timer Scale as follows: T1 = 10  
minutes, T2 = 1 hour  
T2  
1 MIN T2  
• Set the Timer Settings as follows: T1 = 0.5, T2 =  
0.5. The timer is now set for 5 minutes off and 30  
minutes on.  
Timer  
Scale  
1 MIN T1  
0.8 0.6  
1.0 0.4  
0.2  
0
Preheat frost control (see FIGURE 11, page 12) includes a  
thermostat (with probe) and an electric heater located in the  
supply air inlet compartment and an air pressure switch in the  
supply air outlet compartment. The thermostat should be set  
according to the Frost Threshold temperatures shown in TABLE 1.  
When the outdoor air temperature reaches the thermostat setting,  
the electric preheater will turn on and warm the air entering the energy  
wheel.  
T1  
16  
18  
A2  
FIGURE 12  
Testing  
Turn the thermostat as high as it will go. The heater should turn on.  
• If it doesn’t, either put the supply side doors on or temporarily jumper the  
air pressure switch to avoid nuisance tripping of the pressure switch.  
Remember to remove the jumper.  
DIRTY FILTER SWITCH SETUP  
This unit may be equipped with a dirty filter switch that functions on differential air pressures to close a relay  
when the unit filters are clogged and need cleaning. This switch has not been set at the factory due to external  
system losses that will affect the switch. This switch will need minor field adjustments after the unit has been  
installed with all ductwork complete. The dirty filter switch is mounted in the exhaust inlet compartment next to  
the electrical control center.  
To adjust the switch the unit must be running with all of the access doors in place, except for the compartment  
where the switch is located (exhaust inlet compartment). Remove the switch cover plate. The adjusting screw is  
located on the top of the switch. Open the filter compartment and place a sheet of plastic or cardboard over  
50% of the filter media. Replace the filter compartment door. Check to see if there is power at the alert signal  
leads (refer to electrical diagram). If there is no power, turn the adjustment screw on the dirty filter gage  
clockwise until you have power. Open the filter compartment and remove the obstructing material. Replace the  
door and check to make sure that you do not have power at the alert signal leads. The unit is now ready for  
operation.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ECONOMIZER APPLICATION/OPERATION  
The energy recovery wheel may be de-energized for the purpose of providing economizer (free cooling)  
operation. This can be achieved with a signal from a Temperature or Enthalpy sensor mounted in the supply air  
inlet compartment (see FIGURE 13). This Primary sensor will de-energize the energy wheel when the outdoor air  
temperature (factory default is 65°F) or enthalpy (factory default is the ‘D’ setting) is below the field adjustable  
set point. An additional Override temperature sensor is also furnished in the supply air inlet compartment to  
deactivate economizer mode (see FIGURE 13). The Override (with field adjustable set point) is set at some  
temperature lower than the Primary sensor (factory default is 50°F). Effectively, the two sensors create a  
deadband where the energy recovery wheel will not operate and free cooling from outside can be brought into  
the building unconditioned.  
Testing (terminals referenced below are in the unit control center — see FIGURE 5, Item #7)  
Temperature sensor with Override  
Turn both Temperature and Override  
thermostats down as low as they go.  
The wheel should be rotating.  
FIGURE 13  
Turn the Temperature sensor up as  
high as it goes, and keep the Override  
sensor as low as it will go. The wheel  
should stop rotating.  
Turn both sensors as high as they will  
Enthalpy Sensor  
(Primary Sensor)  
go. The wheel should start rotating.  
• Set the Temperature sensor to the  
desired temperature for economizer  
Timed Exhaust  
Override  
Frost Control  
operation to begin. Set the Override  
sensor to the desired temperature for  
economizer operation to end (factory  
default is 65°F and 50°F, respectively).  
Probes  
Enthalpy sensor with Override  
• A factory-installed 620 ohm resistor is  
connected across terminals SR and +.  
The Override sensor should be turned  
down below current temperature in unit. Turn the unit on; LED on the sensor should be off. Check  
continuity across 2 and 3, there should not be continuity. There should be continuity between  
terminals 1 and 2.  
• Disconnect the 620 ohm resistor from terminals SR and +. LED should turn on. There should be  
continuity between terminals 2 and 3. There should not be continuity between terminals 1 and 2.  
Turn the Override sensor above current temperature in unit. There should be continuity between  
terminals 3 and 6. Set the Override sensor to the desired temperature for economizer operation to end  
(factory default is 50°F).  
• Reconnect the factory-installed jumper.  
AUTO DRY CYCLE  
The HRE may be supplied with a timer to delay turning off the unit to allow the evaporative cooler media pads  
to dry. The blowers continue to run for a user designated time (factory default is 1.5 hours) following a signal to  
turn the HRE unit off. The timer is located in the unit control center and can be adjusted from 15 minutes to 3  
hours. This option is designed to prevent bacteria/mold growth on the pads. Refer to diagram in unit control  
center for wiring.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START UP CHECKS  
**WARNING**  
DO NOT OPERATE ENERGY RECOVERY VENTILATOR WITHOUT THE FILTERS AND BIRDSCREENS INSTALLED.  
THEY PREVENT THE ENTRY OF FOREIGN OBJECTS SUCH AS LEAVES, BIRDS, ETC.  
DO NOT REMOVE ACCESS PANELS OR OTHER UNIT COMPONENTS WHILE STANDING ON A LADDER OR OTHER  
UNSTEADY BASE. ACCESS PANELS AND UNIT COMPONENTS ARE HEAVY AND SERIOUS INJURY MAY OCCUR.  
CAUTION: See **WARNING** on page 1 and above  
For proper unit function and safety, follow everything in this start-up procedure in the order presented. This to  
be done after the electrical and gas connections are complete.  
Pre-Start Check List  
1. Disconnect and lock-out all power switches to fan.  
2. Check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and  
accessories for tightness.  
3. Rotate the fan wheel by hand and assure no parts are rubbing.  
4. Check the V-belt drive for proper alignment and tension.  
Special Tools Required  
• Voltage meter  
• Incline manometer or equivalent  
Tachometer  
• Thermometer  
• Amperage meter  
GENERAL  
Check all fasteners and set screws for tightness. This is especially important  
for bearings and fan wheels. Also, if dampers are not motorized, check that  
they open and close without binding.  
n
o
i
t
Airflow  
a
t
o
R
FAN WHEEL ROTATION  
Hand rotate the blower to ensure that the wheel is not rubbing against the  
scroll. If the blower is rotating in the wrong direction, the unit will move some  
air but not perform properly.  
FIGURE 14  
To check the rotation, open the blower access panels, which are labeled either  
supply or exhaust, and run the blower momentarily to determine the rotation.  
Rotation should be in the same direction as airflow at the outlet (See FIGURES  
14 & 15). Check for unusual noise, vibration or overheating of bearings. Refer to  
the “Trouble Shooting” section of this manual if a problem develops.  
To reverse the rotation, turn the power off and use the following procedure:  
• For single phase units, rewire the motor per the instructions on the  
motor.  
FIGURE 15  
• For three phase units, interchange any two power leads. (this can be  
done at the motor starter).  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check pulleys and belts for proper alignment to avoid unnecessary  
belt wear, noise, vibration and power loss. Motor and drive shafts  
must be parallel and pulleys in line (see FIGURE 16).  
FAN RPM  
The adjustable motor pulley is preset at the factory to the  
customer specified RPM. Fan speed can be increased or  
decreased by adjusting the pitch diameter of the motor pulley.  
Multi-groove variable pitch pulleys must be adjusted an equal  
number of turns open or closed. Any increase in fan speed  
represents a substantial increase in load on the motor. Always  
check the motor amperage reading and compare it to the  
amperage rating shown on the motor nameplate when changing  
fan RPM. Access these components through the labeled access  
panels.  
WRONG  
WRONG  
All access doors must be installed except the control center door.  
To measure the fan rpm, the blower door will need to be removed.  
Minimize measurement time because the motor may overamp with  
the door removed. Do not operate units with access doors/panels  
open or without proper ductwork in place as the motors will  
overload.  
WRONG  
CORRECT  
FIGURE 16  
ENERGY RECOVERY WHEEL  
CAUTION: See **WARNING** on page 1 and 15  
For the HRE-20 and HRE-45, open the access door marked  
"Energy Wheel Cassette Access". UNPLUG the wheel drive  
motor and remove the metal spacer. Then pull the cassette  
out halfway as seen in FIGURE 17.  
Note: For the HRE-55 and HRE-90, the energy recovery  
wheel does not slide out due to its size and weight. There is  
ample room inside the unit to perform energy recovery wheel  
servicing.  
Turn the energy recovery wheel by hand to verify free  
operation. Check that the air seals, located around the  
outside of the wheel and across the center (both sides of  
wheel), are secure and in good condition. Replace cassette  
into unit, plug in wheel drive, replace access door and apply  
power. Observe that the standard and high flow wheel  
rotates freely at about 60 RPM.  
FIGURE 17  
If wheel does not rotate or rotates too slowly, remove the  
cassette (following the instruction on page 20). Air seals, which are too tight, will prevent proper rotation of the  
energy recovery wheel. Recheck the air seals for tightness. Air seal clearance may be checked by placing a  
sheet of paper, to act as a feeler gauge, against the wheel face. To adjust the air seals, loosen all eight seal  
retaining screws. These screws are located on the bearing support that spans the length of the cassette  
through the wheel center. Tighten the screws so the air seals tug slightly on the sheet of paper.  
COILS  
Leak test thermal system to insure tight connections.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE MAINTENANCE  
CAUTION: See **WARNING** on Page 1 and 15  
Once the unit has been put into operation, a periodic maintenance program should be set up to preserve the  
reliability and performance. Items to be included in this program are:  
• BELTS  
• MOTORS  
• WHEEL AND FASTENERS  
• VIBRATION  
• FILTER MAINTENANCE  
• COIL MAINTENANCE  
• ENERGY WHEEL CASSETTE  
FAN BELTS  
Belt Span  
Belts tend to stretch after a period of time. They should be  
periodically checked for tension and wear. When replacing  
belts, use the same type as supplied with the unit.  
Replacement of belts should be accomplished by loosening  
the motor slide plate so the belts may be removed by hand.  
Do not force belts on or off as this may cause breakage of  
cords and lead to premature belt failure.  
Belt tension should be adjusted to allow 1/64 in. of belt  
deflection per 1 in. of belt span. For example, a 16 in. belt  
span should have 16/64 in. or 1/4 in. of deflection with  
moderate thumb pressure at mid-point between the pulleys  
(FIGURE 18).  
Belt Span  
Deflection =  
64  
FIGURE 18  
MOTORS  
Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be  
limited to exterior surfaces only. Removing dust and grease build-up on the motor housing assures proper  
motor cooling. Use caution and do not allow water or solvents to enter the motor or bearings. Under no  
circumstances should motors or bearings be sprayed with steam, water or solvents.  
Greasing of motors is intended only when fittings are provided. Many fractional horsepower motors are  
permanently lubricated for life and require no further lubrication. Motors supplied with grease fittings should  
be greased in accordance with the manufacturer’s recommendations.  
WHEEL AND FASTENERS  
Wheels require very little attention when moving clean air. Occasionally oil and dust may accumulate on the  
wheel causing imbalance. When this occurs the wheel and housing should be cleaned to assure smooth and  
safe operation. Inspect fan impeller and housing for fatigue, corrosion or wear.  
Routinely check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and  
accessories for tightness. A proper maintenance program will help preserve the performance and reliability  
designed into the fan.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VIBRATION  
Excessive vibration maybe experienced during initial start-up. Left unchecked, excessive vibration can cause a  
multitude of problems, including structural and/or component failure. The most common sources of vibration  
are listed below.  
Many of these conditions can be discovered by careful observation.  
1. Wheel Unbalance  
Refer to the troubleshooting section of this manual for corrective actions.  
2. Drive Pulley Misalignment  
If observation cannot locate the source of vibration, a qualified  
technician using vibration analysis equipment should be consulted. If the  
problem is wheel unbalance, in-place balancing can be done providing  
there is access to the fan wheel.  
3. Incorrect Belt Tension  
4. Bearing Misalignment  
5. Mechanical Looseness  
6. Faulty Belts  
7. Drive Component Unbalance  
8. Poor Inlet/Outlet Conditions  
9. Foundation Stiffness  
Generally, fan vibration and noise are transmitted to other parts of the  
building by the ductwork. To eliminate this undesirable effect, the use of  
heavy canvas connectors is recommended.  
EXTERNAL FILTER MAINTENANCE  
Aluminum mesh 2 in. filters are located in the  
supply weatherhood (if the weatherhood option  
was purchased). Filters should be checked and  
cleaned on a regular basis for best efficiency. The  
frequency of cleaning depends upon the  
cleanliness of the incoming air.  
FIGURE 19  
To remove these filters, remove bottom bolt in the  
access door on the side of the weatherhood. Slide  
the access door up and then pull out. Then, slide  
the filters out (see FIGURE 19).  
Clean filters by rinsing with a mild detergent in  
warm water. After the filters are dry, an adhesive  
spray available at most filter distributors may be  
applied to increase filter efficiency.  
TABLE 2  
Internal  
Quantity  
Filter Size  
Model  
INTERNAL FILTER MAINTENANCE  
Opening the access doors labeled as “Filter  
Access” provides access to the pleated 30%  
filters (if the filter option was purchased). These  
filters should be checked regularly, cleaned or  
replaced as needed. See TABLE 2 for pleated filter  
size and quantity for each unit.  
HRE-20  
HRE-45  
HRE-55  
HRE-90  
20 x 20  
20 x 25  
16 x 25  
20 x 20  
2
3
6
8
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WATER COIL MAINTENANCE  
CAUTION: See **WARNING** on Page 1 and 15  
FILTERS  
Filters upstream of the coil should be checked regularly. If the filters are dirty, they should be cleaned or  
replaced. It is important that the coils stay clean to maintain desired airflow. See page 18 for more information  
on filter maintenance.  
COIL MAINTENANCE  
1. Coils must be clean to obtain maximum performance. Check once a year under normal operating  
conditions and, if dirty, brush or vacuum clean. Soiled fins reduce the capacity of the coil, demand more  
energy from the fan, and create an environment for odor and bacteria to grow and spread through the  
conditioned zone. High pressure water (700 Psi or less) may be used to clean coils with fin thickness over  
0.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the fins  
will withstand the spray pressure.  
For coils with fragile fins or high fin density, foaming chemical sprays and washes are available. Many coil  
cleaners contain harsh chemicals, so they must be used with caution by qualified personnel only. Care  
must be taken not to damage the coils, including fins, while cleaning.  
CAUTION: Fin edges are sharp.  
**WARNING**  
BIOLOGICAL HAZARD. MAY CAUSE DISEASE. CLEANING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE ENERGY RECOVERY WHEEL MAINTENANCE  
CAUTION: See **WARNING** on Page 1 and 15  
MAINTENANCE OF THE ENERGY RECOVERY WHEEL  
Annual inspection of the energy recovery wheel is recommended. Units ventilating smoking lounges and other  
non-clean air spaces should have energy recovery wheel inspections more often based upon need. Inspections  
for smoke ventilation applications are recommended bimonthly to quarterly until a regular schedule can be  
established.  
ACCESSING ENERGY RECOVERY WHEEL  
For the HRE-20 and HRE-45, open the access door marked "Energy Wheel Cassette Access" (FIGURE 20).  
UNPLUG the wheel drive motor and remove the metal spacer. Then pull the cassette out halfway (FIGURE 21).  
The energy recovery wheel cassettes for model HRE-55 and HRE-90 do not slide out due to their size and  
weight. Service to these energy wheel cassettes can be done through the Filter and Electrical Control Box  
access doors, or by entering the unit through the Exhaust Blower access door.  
**WARNING: Disconnect power to the unit before performing any type of service.**  
FIGURE 20  
FIGURE 21  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMOVING THE ENERGY RECOVERY WHEEL SEGMENTS  
Model HRE-20, 45, 55, & 90  
Bracket Segment Retainer  
Steel retainers are located on the  
inside of the wheel rim (FIGURE 22).  
Push the retainer toward center of  
wheel, then lift up and away to  
Lift Away  
From Segment  
release segments (FIGURE 23).  
Catch-  
Segment Retainer  
Inside of Wheel Rim  
Spoke  
Push Toward Center  
FIGURE 22  
IMPORTANT! PLACE RETAINERS BACK IN THE ORIGINAL  
POSITION BEFORE ROTATING THE ENERGY  
RECOVERY WHEEL. OTHERWISE DAMAGE TO  
RETAINER WILL OCCUR.  
FIGURE 23  
CLEANING ENERGY RECOVERY WHEEL SEGMENTS  
If the wheel appears excessively dirty, it should be cleaned to ensure maximum operating efficiency. Only  
excessive buildup of foreign material needs to be removed. DISCOLORATION AND STAINING OF ENERGY  
RECOVERY WHEEL DOES NOT AFFECT ITS PERFORMANCE.  
Thoroughly spray wheel matrix with household cleaner such as Fantastic or equivalent. Gently rinse with warm  
water and using a soft brush remove any heavier accumulation. A detergent/water solution can also be used.  
Avoid aggressive organic solvents, such as acetone. The energy recovery wheel segments can be soaked in the  
above solution overnight for stubborn dirt or accumulation.  
After cleaning is complete, shake the excess water from the wheel or segments. Dry wheel or segments before  
placing them back into the cassette. Place wheel or segments back into cassette by reversing removal  
procedures.  
** DO NOT CLEAN ENERGY RECOVERY WHEEL SEGMENTS WITH WATER IN EXCESS OF 140°F  
** DO NOT DRY ENERGY RECOVERY WHEEL SEGMENTS IN AIR IN EXCESS OF 140°F.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
7
11  
8
3
6
1
5
2
9
12  
7
4
10  
Model HRE  
(shown with indirect evaporative cooler,  
optional direct evaporative cooler, and  
indirect gas heater)  
1. Supply blower  
8. Electrical control box (standard features)  
- Single point power  
- Forward curved fan  
- Adjustable motor mount for belt tensioning  
- Adjustable sheaves for speed control  
- Disconnect interlocked with access door  
- Motor starters for the supply blower, exhaust  
blower and energy wheel motors.  
2. Vibrations isolators (quantity 4 per blower)  
- Neoprene  
- 24 Vac, control circuit with terminal strip  
9. Supply air tempering options  
- Electric heat  
3. Energy recovery wheel cassette  
- Hot water heat  
4. Removable energy recovery wheel segments  
- Indirect gas heat  
5. Optional supply weatherhood with 2 in. aluminum  
mesh filter  
10. Exhaust blower  
- Forward curved fan  
- Adjustable motor mount for belt tensioning  
- Adjustable sheaves for speed control  
6. Optional exhaust weatherhood with birdscreen  
7. Optional supply and exhaust air filter racks for 2  
in. pleated, 30% efficient filters  
11. Indirect evaporative cooler  
12. Direct evaporative cooler  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble Shooting  
Symptom  
Possible Cause  
Corrective Action  
Blown fuse or open circuit  
breaker.  
Replace fuse or reset circuit breaker and check amps.  
Defective motor or capacitor.  
Motor starter overloaded.  
Electrical.  
Replace  
Blower Fails to  
Operate  
Reset starter and check amps.  
Check for On/Off switches. Check for correct supply voltage.  
Check for broken or loose belts. Tighten loose pulleys.  
Drive.  
Control power (24 Vac) wiring  
run is too long (resistance  
Shorten wiring run to mechanical room or install a relay  
which will turn unit on/off (C/F for relay information).  
should not exceed 0.75 ohms).  
Motor Starters  
“Chatter” or Do  
Not Pull In  
Incoming supply power is  
less than anticipated. Voltage  
supplied to starter coil must  
be within +10% / -15% of  
nominal voltage stated on  
the coil.  
Need to increase supply power or use a special control  
transformer which is sized for the actual supply power.  
Cfm too high.  
Check cfm and adjust drives if needed.  
Static pressures are higher or  
lower than design.  
If higher, ductwork should be improved.  
If lower, fan rpm should be lower.  
Blower rotation is incorrect.  
Motor voltage incorrect.  
Motor horsepower too low.  
Check rotation and reverse if necessary.  
Motor Over Amps  
Check motor nameplate versus supplied voltage.  
See specifications and catalog for fan curves to determine if  
horsepower is sufficient.  
Shorted windings in motor.  
Unit damper not fully open.  
Replace motor.  
Adjust damper linkage or replace damper motor.  
System static pressure too high Improve ductwork to eliminate losses using good duct  
practices.  
Blower speed too low.  
Check for correct drives and rpm with catalog data.  
For 3-phase see Fan Wheel Rotation on page 15.  
Fan wheels are operating  
backwards.  
Low Airflow (cfm)  
Dirty filter or energy wheel.  
Leaks in ductwork.  
Follow cleaning procedures on pages 18 and 21.  
Repair.  
Elbows or other obstructions  
may be obstructing fan outlet.  
Correct or improve ductwork.  
Belt slippage.  
Adjust belt tension.  
Blower fan speed too high.  
Filter(s) not in place.  
Check for correct fan rpm. Decrease fan speed if necessary.  
Install filters.  
High Airflow (cfm)  
Insufficient static pressure (Ps)  
(airflow resistance).  
Induce Ps into system ductwork. Make sure grilles and  
access doors are installed. Decrease fan speed if necessary.  
* Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble Shooting  
Symptom  
Possible Cause  
Corrective Action  
One or Both  
Blowers Turn Off  
Intermittently and  
Back on After  
Blower fan motor overloads are Decrease fan speed.  
tripping and auto-resetting.  
Exhaust Only frost control  
sensors are tripping.  
Adjust frost temperature sensor set point as needed.  
About 2 Minutes  
Air seals are too tight.  
See Energy Recovery Wheel on page 16.  
“Economizer” sensors are  
operating.  
Adjust temperature or enthalpy set points as needed.  
Energy Wheel  
Does NOT Turn  
No power to wheel motor.  
Make sure wheel drive is plugged in. Verify power is  
available.  
Wheel drive belt  
Check for loose or broken belts. Replace belts (consult  
factory).  
Wheel motor overloads are  
tripping, due to rubbing  
between wheel and air seals.  
Recheck air seals, make sure they are not too tight. See  
Energy Recovery Wheel on page 16.  
Energy Wheel  
Runs Intermittently  
Fan wheel rubbing on inlet  
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing  
collars on shaft.  
Bearings.  
Replace defective bearings (s). Lubricate bearings. Tighten  
collars and fasteners.  
Wheel out of balance.  
Replace or rebalance.  
Loose wheel on shaft.  
Tighten wheel setscrew.  
Tighten sheave setscrew.  
Loose motor or blower sheave.  
Belts too loose.  
Belts too tight.  
Adjust belt tension after 24 hours of operation.  
Excessive Noise or  
Vibration  
Loosen to maintain a 3/8 inch deflection per foot of span  
between sheaves.  
Worn belt.  
Replace.  
Motor base or blower loose.  
Build up of material on wheel.  
Bearing and drive misaligned.  
Tighten mounting bolts.  
Clean wheel and housing.  
Realign.  
Noise being transmitted by  
duct.  
Make sure duct work is supported properly. Make sure duct  
work metal thickness is sized for proper stiffness. Check duct  
size at discharge to ensure that air velocities are not too high.  
* Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating.  
Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from  
the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a  
period of five years from the purchase date. Any units or parts which prove defective during the warranty period will be  
replaced at our option when returned to our factory, transportation prepaid.  
Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove  
defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not  
be responsible for any removal or installation costs.  
Due to continuing product development Greenheck has the right to change specifications without notice  
GREENHECK  
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410  
IOM HRE FS  
Rev. 2, July 2002  
PH. 715-359-6171  
®
Copyright © 2002 Greenheck Fan Corp.  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco High Chair PD162122A User Manual
Greenheck Fan Ventilation Hood CFSD Series User Manual
Greenheck Fan Ventilation Hood UL 762 User Manual
Greenway Home Products Water Dispenser VWD8956W User Manual
Grindmaster Coffeemaker 20H User Manual
Haier Microwave Oven AED 2485EG User Manual
Hamilton Beach Blender 70200 User Manual
Heath Zenith Home Safety Product 5408 5410 User Manual
Honeywell Universal Remote PUB1012S User Manual
Humminbird Fish Finder 425 SX User Manual