Greenheck Fan Gas Heater DGX User Manual

Modular Make-Up Air Unit  
Model DGX  
• Direct Gas-Fired Heating  
• Evaporative • Chilled Water • DX Cooling  
March  
2007  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODULE SELECTION OPTIONS  
Module 1  
INTAKE  
Module 2  
FILTER  
Module 3  
COOLING  
Module 4  
HEATING  
Module 5  
DISCHARGE  
None  
None  
None  
requires  
Module 2, Option 2  
Direct Gas Furnace  
100% Outdoor Air  
Downblast  
Discharge  
Birdscreen Weatherhood  
requires  
V-Bank Filters  
Pleated or  
Aluminum Mesh  
*Cooling Coil – CW, DX  
(standard capacity)  
Direct Gas Furnace  
Recirculation - requires  
Module 2, Option 3  
Horizontal  
Discharge  
Module 2, Option 2  
Filtered  
Weatherhood  
80/20 Filtered  
Recirculation  
*Cooling Coil – CW, DX  
(high capacity)  
Direct Gas Furnace  
Variable Air Volume  
Upblast  
Discharge  
*Chilled water or direct expansion (DX) cooling is available with the model DGX. The cooling section  
includes the cooling coil, sloped stainless steel drain pan and insulated double wall construction.  
Drain and coil connections are stubbed through the wall for convenience.  
For proper coil sizing, use Greenheck CAPS selection software or contact your local representative.  
Four row and six row chilled water or DX coils are available with airflow capacity up to 11,000 cfm.  
Louvered  
Cooling coil sections are installed upstream of the fan section for a draw through arrangement and  
provide a streamlined transition to adjacent DGX sections. DX coils require remote condensing units.  
Weatherhood  
Module 2 is not available with the Evaporative Cooler section (Module 1, Option 6)  
Cooling Coil modules (Module 3, Option 2 & 3) are not available with Recirculation (Module 2,  
Option 3)  
Optional intake dampers available on Cooling Coil section (Module 3, Option 2 & 3)  
Module 1, Option 3, 4 & 5 are not available on Housing 35 and larger  
Thru-Wall  
The evaporative cooling section includes a galvanized steel housing with a louvered intake, 2 inch  
aluminum mesh filters and a stainless steel evaporative cooling module. The evaporative cooling  
media has a depth of 12 inches for 90% cooling effectiveness.  
The entire section mounts directly to the front of the DGX unit, eliminating transition or ductwork  
by others. Drain and overflow are conveniently tapped through the side of the cooling section. The  
supply line connection is field located where convenient. Freeze protection, automatic drain & fill, and  
water economizer (Water Wizard) options are also available.  
Airflow capacity for evaporative cooling is up to 46,000 cfm. The evaporative cooling section for the  
housing 32 and larger ship separately.  
Evaporative  
Cooling  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
VARIABLE MAKE-UP AIR OPTIONS  
Variable Volume  
The variable volume option is recommended when a  
building’s exhaust volume will vary. The make-up air  
volume will track with the exhaust volume, providing  
only the necessary amount of make-up air.  
• 2 speed motor controlled manually with a remote  
switch.  
Burner By-Pass Damper  
The Variable Volume option includes a patented  
burner by-pass damper, which maintains the pressure  
drop across the burner as air volumes change. This  
assures that complete and proper combustion occurs.  
The by-pass damper is self-adjusting, designed for  
minimal maintenance, and requires no controls.  
The variable volume option saves energy by reducing  
both fan power and gas consumption whenever make-  
up air requirements are less than the maximum.  
Airflow Control Strategies  
Greenheck offers four methods of controlling the  
make-up air volume. All four vary the fan speed for  
maximum energy savings.  
• Variable Frequency Drive controlled by building  
pressure.  
• Variable Frequency Drive controlled manually with a  
remote potentiometer.  
Outside Air  
• Variable frequency drive controlled by a 2-10 VDC  
or 4-20 mA signal.  
Supply Air  
Recirculation  
The recirculation option is recommended when the  
ventilation equipment provides the primary source of  
heating for the space.  
• Modulating actuator controlled manually with a  
remote potentiometer.  
• Modulating actuator controlled by a 2-10 VDC or  
4-20 mA signal.  
Up to 80% of the air from the space can be  
recirculated and filtered and then combined with a  
minimum of 20% outdoor air for a continuous source  
of fresh air. Only outdoor air is used for combustion to  
eliminate the possibility of contaminants from the  
recirculated air crossing over the burner.  
• Two position actuator controlled manually with a  
remote switch/time clock.  
20%  
Airflow Control Strategies  
Greenheck offers four methods of controlling the ratio  
of recirculated air to outdoor air via motorized  
dampers.  
80-0%  
Outside Air  
(100-20%)  
Supply Air  
Recirculated Air  
(0-80%)  
• Modulating actuator controlled by building pressure.  
Temperature Control  
There are three temperature control  
options for heat: 1) Discharge Control, 2)  
Space Control, and 3) DDC Interface  
Control. Cooling controls are by others.  
Room Control  
Specify this option when the DGX has the primary  
responsibility for controlling the room temperature. A  
manually adjusted room thermostat provides feedback  
to the unit controls, which vary the discharge  
temperature in order to maintain desired room set  
point.  
Discharge Control  
A factory installed modulating system  
controls the gas valve to provide the  
desired temperature based on a sensor  
at the fan discharge. A room override  
option is available to boost the discharge  
temperature when the space is too cool.  
DDC Interface Control  
Allows for an external signal (0-10 VDC or 4-20 mA)  
from the building management system to modulate  
the burner output to satisfy monitored conditions.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION OPTIONS  
Roof Mounted Installation  
Model DGX is available for stand alone installations as shown below. Downblast (Arrangement DB), upblast  
(Arrangement UB), or horizontal (Arrangement HZ) discharge may be specified.  
Horizontal Discharge - Arrangement HZ  
Upblast Discharge - Arrangement UB  
The Greenheck combination package  
simplifies installation and reduces field labor  
costs. The pre-engineered design ensures that  
the supply fan, exhaust fan, curb, and  
combination extension components interface  
properly for kitchen ventilation applications.  
Equally important, Greenheck combination  
packages are specifically designed to comply  
with NFPA 96.  
Combination Package - Arrangement DBC  
NFPA 96 states:  
• Exhaust duct must terminate at least 24  
inches above the roof deck  
• Fan discharge must be at least 40 inches  
above the roof deck  
• Air intake shall have a horizontal separation  
of 10 feet from the exhaust discharge  
Note: Consult local codes and the authority  
having jurisdiction if there are questions  
concerning the use of this product.  
The combination curb extension  
is the component that pulls the  
Combination Package together,  
providing a factory engineered  
interface between the roof curb  
and the fans. It is also designed  
to satisfy NFPA 96 requirements  
- above the roof line - for  
kitchen hood exhaust.  
Thru-Wall Installation  
Model DGX (Housing 12, 22, & 32 only) is available with a pre-engineered thru-wall installation option, which is  
ideal when a roof penetration is not desirable.  
Factory options that facilitate easy installation  
and ensure problem-free operation:  
Weatherhood: A full down turn design with  
generous intake area to minimize intake velocity  
and moisture entrainment.  
Thru-Wall Sleeve: Sleeve provides attachment  
interface between weatherhood and burner  
section. Accommodates walls up to 15 inches in  
depth.  
Filter Section: Aluminum mesh media filters  
outdoor air and strips fine mist from the air. A  
drain pan weeps moisture out the front of the  
wall sleeve.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
Remote Control Panels  
A wide variety of remote control panels are available. Specify the desired combination of switches, thermostats,  
temperature selectors and indicator lights. A terminal strip at the unit control center and remote panel simplify  
field control wiring.  
Kitchen style remote panels  
Basic remote control panel with  
feature toggle switches and a  
thermostat for room temperature  
stainless steel face plate for  
control option.  
flush mounting to a wall. The  
junction box is also included.  
Accessories  
Special Coatings  
Spring Vibration Isolation  
Spring blower vibration isolators are available in lieu of  
neoprene isolators.  
Greenheck’s Permatector™ coating is available for a  
durable, long lasting finish. Decorative paints are also  
available in a variety of colors to match existing  
building fixtures. Consult your Greenheck  
representative for paint selections.  
Exhaust Fan Starter(s)  
Exhaust fan starters are available factory mounted and  
wired. Exhaust fan starters allow for an electrical  
interlock between the supply and exhaust fan(s).  
Roof Curbs  
Factory provided roof curbs are available to ensure  
compatibility between the make-up air unit and roof  
curb. Standard construction is G90 galvanized steel.  
Dirty Filter Switch  
A dirty filter switch is available to monitor the pressure  
drop across the filter section. If the pressure drop  
across the filters is higher than the field adjustable  
setting, the dirty filter switch trips indicating the need  
to clean or replace the filters.  
Duct Adapter  
Duct adapter is available with factory supplied roof  
curbs. The duct adapter allows for easy alignment of  
the supply duct connection.  
Freeze Protection  
V-Bank Filter Section  
Electronic freeze protection is available to  
automatically shut down the supply fan when the  
discharge temperature is below the adjustable set  
point for an extended amount of time. This prevents  
the unit from discharging non-tempered air into the  
building and freezing pipes and other temperature  
sensitive items.  
V-bank filter sections are available with 2-inch  
washable aluminum mesh or 2-inch 30% efficient  
disposable filters.  
Weatherhood  
Three weatherhoods are available: standard  
weatherhood includes birdscreen, filtered  
weatherhood includes aluminum mesh filters, and  
louvered intake hood includes a drainable blade  
louver at intake with 2-inch aluminum mesh filters.  
Inlet Air Sensor – Heat  
The heating inlet air sensor will automatically turn the  
heat on and off based on the outdoor air temperature.  
Motorized Dampers  
Discharge Diffuser  
Intake or discharge dampers are available to prevent  
backdrafts when the supply fan is not in operation.  
Intake dampers are factory mounted and wired.  
Discharge dampers ship loose for field mounting in the  
supply air duct.  
Discharge diffusers are available as either 3-way for  
horizontal discharge or 4-way for downblast discharge.  
Service Receptacle  
A 115 volt GFCI outlet is mounted externally in a NEMA  
3R box for the convenience of service personnel. A  
separate 115 volt power source is required.  
Fiberglass Insulation  
One inch fiberglass insulation is available to line the  
housing to prevent the formation of condensation and  
to form an acoustical barrier.  
Auxiliary Contacts  
Normally open and normally closed contacts are  
available for supply fan status and supply fan  
interlocks.  
Double Wall Construction  
An interior metal liner is available to isolate the 1-inch  
fiberglass insulation from the airstream.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIR PERFORMANCE  
Blower  
CFM  
TOTAL PRESSURE in inches WG  
Size  
0.75  
1109  
0.26  
1347  
0.59  
1014  
0.45  
1216  
1.1  
912  
0.59  
1097  
1.4  
761  
0.7  
939  
2.1  
681  
1.3  
850  
3.5  
609  
2.1  
736  
4.9  
590  
4.0  
763  
10.9  
605  
8.3  
720  
15.2  
563  
9.8  
643  
15.9  
451  
11.6  
525  
19.6  
-
1.00  
1216  
0.31  
1445  
0.68  
1140  
0.54  
1306  
1.3  
1013  
0.71  
1172  
1.6  
1.25  
1311  
0.35  
1530  
0.75  
1255  
0.63  
1397  
1.4  
1110  
0.08  
1244  
1.7  
1.50  
1399  
0.40  
-
1.75  
-
2.00  
-
-
-
-
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
800  
-
-
-
108  
1,200  
-
1361  
0.73  
1484  
1.6  
1199  
0.10  
1315  
1.9  
1460  
0.84  
1569  
1.7  
-
-
-
1,500  
109  
110  
112  
115  
118  
120  
122  
125  
127  
130  
133  
136  
1648  
1.9  
-
2,400  
2,000  
-
-
1386  
2.1  
-
1455  
2.2  
-
3,000  
853  
0.9  
934  
1.0  
1009  
1.2  
2,600  
-
-
1006  
2.4  
756  
1.5  
1073  
2.6  
822  
1.8  
1137  
2.9  
892  
2.1  
1197  
3.1  
-
1254  
3.3  
-
4,400  
4,000  
-
-
906  
3.9  
668  
2.5  
960  
4.3  
724  
2.8  
1013  
4.7  
777  
3.2  
1062  
5.1  
-
1110  
5.5  
-
6,500  
6,500  
-
-
783  
5.4  
634  
4.5  
795  
11.6  
637  
8.9  
827  
5.9  
678  
5.0  
829  
12.3  
667  
9.6  
872  
6.4  
723  
5.6  
914  
6.9  
765  
6.1  
892  
13.8  
727  
11.1  
821  
18.6  
683  
13.8  
748  
20.4  
554  
17.2  
613  
26.6  
494  
16.8  
542  
28.3  
467  
22.6  
512  
35.8  
482  
36.3  
-
954  
7.4  
803  
6.6  
921  
14.5  
755  
11.9  
845  
19.4  
711  
14.8  
-
9,500  
10,000  
15,000  
15,000  
19,000  
19,000  
23,000  
24,000  
30,000  
26,000  
34,000  
32,000  
40,000  
42,000  
48,000  
861  
13.1  
698  
10.4  
796  
17.8  
655  
12.8  
723  
19.2  
530  
15.8  
593  
24.9  
467  
15.2  
519  
26.4  
446  
21.0  
491  
33.7  
464  
34.1  
500  
46.4  
746  
16.1  
594  
10.7  
671  
16.9  
478  
13.0  
548  
21.4  
412  
12.5  
477  
23.1  
397  
17.5  
448  
29.1  
426  
29.8  
465  
41.5  
771  
17.0  
625  
11.7  
967  
18.0  
504  
14.3  
571  
23.2  
440  
13.9  
499  
24.8  
422  
19.2  
470  
31.5  
445  
32.0  
483  
44.0  
-
578  
18.6  
-
-
520  
18.3  
-
-
454  
21.5  
371  
15.7  
426  
27.1  
405  
27.7  
447  
39.0  
-
488  
24.3  
531  
37.9  
499  
38.5  
-
-
-
Note: The air performance data shown does not include internal static pressure losses due to items such as filters, dampers, and coils. For  
exact air performance data based on specific unit configuration, use the Greenheck CAPS selection program.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
Typical Specifications  
General: Make-up air unit shall be as manufactured by control transformer for 24 VAC circuit,  
Greenheck or approved equal provided all specifications are integral disconnect switch and terminal  
met. Greenheck Model DGX equipment is used as the basis of strip. Contactors, Class 20 adjustable  
design. Performance to be as scheduled on plans. Make-up air overload protection and single phase  
unit shall be ETL listed to ANSI Z83.4 -1999, CSA 3.7 - M99 (for protection shall be standard.  
100% outdoor air) or ANSI Z83.18-2000 (for recirculation).  
Filter Section: Filter section shall be  
Gas Train and Controls: Direct gas-fired system shall have designed such that velocities across  
a draw through design and field adjustable burner baffles. the filters do not exceed 550 feet per  
Gas trains up to 400,000 Btu/hr shall include a direct spark minute. Filters shall be 2-inch washable  
ignition system. Gas trains greater than 400,000 Btu/hr shall aluminum mesh or 2-inch disposable.  
include a pilot ignition system and shall have digital coded  
Weatherhood: Weatherhood shall be  
fault indicator capability. Fault indicator shall provide service  
constructed of G90 galvanized steel  
history by storing codes for the last five faults. Dual safety  
with birdscreen mounted at the intake.  
shutoff valves shall be industrial duty and use 120 VAC control  
Recirculation (optional): Recirculation  
airflow shall be controlled by adjustment  
of return damper position. Input signal  
for return damper shall be from building  
signals. Temperature control shall incorporate a Maxitrol  
electronic modulation control system.  
Unit Casing and Frames: Unit shall be of internal frame type  
construction of galvanized steel. All frames and panels shall  
pressure sensors, potentiometer,  
be G90 galvanized steel. Where top panels are joined there  
external signal, or manual switch.  
shall be a standing seam to insure positive weather protection.  
Recirculated air shall not be permitted  
All metal-to-metal surfaces exposed to the weather shall be  
to pass across the burner. Return air  
sealed, requiring no caulking at job site. All components shall  
shall be filtered.  
be easily accessible through removable doors.  
Variable Volume (optional): Volume shall be varied by either  
Insulation: Unit casing to be lined with 1 inch fiberglass  
insulation where specified. Insulation shall be in accordance  
withNFPA90AandtestedtomeetUL181erosionrequirements.  
Double wall shall be provided where specified.  
a 2-speed motor or variable frequency drive. Input signal for fan  
speed shall be from building pressure sensors, potentiometer,  
external signal, or manual switch. A self-adjusting burner  
bypass damper shall maintain a constant air volume across  
Fan Section: Centrifugal fans shall be double width, double the burner to ensure proper gas combustion. Bypass damper  
inlet. Fan and motor shall be mounted on a common base and shall operate automatically without an electronic signal.  
shall be internally isolated. All blower wheels shall be balanced.  
Cooling Coil (optional): Direct expansion (DX) or chilled  
Ground and polished steel fan shafts shall be mounted in  
water coil shall be factory tested and rated in accordance  
permanently lubricated ball bearings or ball bearing pillow  
with ARI 410. Coils shall have copper tubes with permanently  
blocks. Bearings shall be selected for a minimum (L10) life in  
expanded aluminum fins, 12 fpi or less. DX coils shall be  
excess of 100,000 hours at maximum cataloged speeds.  
equipped with distributors to receive expansion valves at the  
Motors and Drives: Motors shall be energy efficient, liquid connections. Drain pans shall extend at least 12 inches  
complying with EPACT standards, for single speed ODP downstream of coil and be sloped to drain connection. Cooling  
and TE enclosures. Motors shall be permanently lubricated, coil shall meet UL 1995 specifications for non-protected coil.  
heavy duty type, matched to the fan load and furnished at the  
Evaporative Cooling Section (optional):  
Evaporative  
specified voltage, phase and enclosure. Drives shall be sized  
for a minimum of 150% of driven horsepower. Pulleys shall  
be cast and have machined surfaces, 15 horse power and less  
shall be supplied with an adjustable drive pulley.  
cooling section shall include a galvanized steel housing with  
louvered intake, 2 inch aluminum mesh filters and a stainless  
steel evaporative cooling module all provided by the make-up  
air unit manufacturer. The louver shall be stationary type with  
Electrical: All internal electrical components shall be prewired drainable blades, and be designed to withstand wind loads of  
for single point power connection with exception of the larger 25 PSF. Evaporative cooling media shall be 12 inches deep,  
evaporative cooling sections. All electrical components shall with a UL 900 class II fire rating for a cooling effectiveness of  
be UL listed, recognized or classified where applicable and 90%. Drain and overflow connections shall be piped through  
wired in compliance with the National Electrical Code. Control the side of the evaporative cooling section.  
center shall include motor starter, control circuit fusing,  
Our Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from the  
purchase date. Any units or parts which prove defective during the warranty period will be replaced at our option when returned  
to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of one year. Should motors  
furnished by Greenheck prove defective during this period, they should be returned to the nearest authorized motor service  
station. Greenheck will not be responsible for any removal or installation costs.  
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications without  
notice.  
Greenheck P.O. Box 410 • Schofield, WI 54476-0410 • Phone (715) 359-6171 • greenheck.com  
Copyright © 2007 Greenheck Fan Corp. • Catalog DGX Rev. 4 March 2007 SP  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Honeywell Air Cleaner F112C User Manual
Hotpoint Cooktop GW38G User Manual
Hotpoint Dishwasher 7840 User Manual
Hotpoint Freezer RZA50 User Manual
Hotpoint Refrigerator FF187ALG User Manual
HP Hewlett Packard Calculator 48gII User Manual
HP Hewlett Packard Calculator HP 42S User Manual
HP Hewlett Packard Landscape Lighting HP 3400B User Manual
Humminbird Switch 531906 1EN_A User Manual
Icom Stereo System IC F111S User Manual