Part #462888
Modular Small Cabinet Fan
®
Installation, Operation and Maintenance Manual
Please read and save these instructions. Read carefully before attempting to assemble, install, operate or maintain the
product described. Protect yourself and others by observing all safety information. Failure to comply with instructions
could result in personal injury and/or property damage! Retain instructions for future reference.
Model MSCF-BI
Model MSCF-FC
General Safety Information
Only qualified personnel should install this unit.
Personnel should have a clear understanding of these
instructions and should be aware of general safety
precautions. Improper installation can result in electric
shock, possible injury due to coming in contact with
moving parts, as well as other potential hazards.
Other considerations may be required if high winds
or seismic activity are present. If more information
is needed, contact a licensed professional engineer
before moving forward.
2. The rotation of the wheel is critical. It must be
free to rotate without striking or rubbing any
stationary objects.
3. Motor must be securely and adequately
grounded.
4. Do not spin fan wheel faster than the maximum
cataloged fan rpm. Adjustments to fan speed
significantly affects motor load. If the fan RPM is
changed, the motor current should be checked
to make sure it is not exceeding the motor
nameplate amps.
5. Do not allow the power cable to kink or come
in contact with oil, grease, hot surfaces,
or chemicals. Replace cord immediately if
damaged.
1. Follow all local electrical and safety codes, as
well as the National Electrical Code (NEC), the
National Fire Protection Agency (NFPA), where
applicable. Follow the Canadian Electric Code
(CEC) in Canada.
6. Verify that the power source is compatible with
the equipment.
DANGER
7. Never open blower access doors while the fan is
running.
Always disconnect power before working on or
near a unit. Lock and tag the disconnect switch or
breaker to prevent accidental power up.
CAUTION
When servicing the unit, motor may be hot enough
to cause pain or injury. Allow motor to cool before
servicing.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
1
®
Table of Contents
Installation
Installation
Unit Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
Mounting / Hanging Instructions . . . . . . . . . . . . . 4
Mounting Dimensions. . . . . . . . . . . . . . . . . . . . . . 5
Dimensions / Weights. . . . . . . . . . . . . . . . . . . . . . 6
Filter Sizes / Quantity . . . . . . . . . . . . . . . . . . . . . . 6
Coil Dimensions . . . . . . . . . . . . . . . . . . . . . . . . .7-9
Start-Up
Electric Heater. . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Operation
Electric Heater. . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Maintenance
Fan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Drain Pan. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Reference
Start-Up Documentation. . . . . . . . . . . . . . . . . . . 17
Maintenance Log . . . . . . . . . . . . . . . . . . . . . .18-19
Warranty . . . . . . . . . . . . . . . . . . . . . . . . .Backcover
System Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . 10
Troubleshooting
Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Motor Overamps . . . . . . . . . . . . . . . . . . . . . . . . . 10
Insufficient / Too Much Airflow. . . . . . . . . . . . . . 10
Excessive Noise or Vibration . . . . . . . . . . . . . . . 10
Start-Up
Coil Module . . . . . . . . . . . . . . . . . . . . . . . . . . .12-13
Drain Pan / Drain Trap . . . . . . . . . . . . . . . . . . . . 13
Unit Layout
Airflow
4
7
2
8
8
8
8
8
6
8
5
3
9
1
1. Fan and Cabinet Section
6. Mixing Box Section
7. Lifting Lugs
2. Cooling Section
• Chilled Water
• DX Coils
Four (4) lifting lugs for each section
8. Side Access Panels
3. Heating Section
• Hot Water
Right and left access to each section
(image shows panels removed)
• Steam Coils
9. 7/8-inch knockout is provided for the
recommended electrical wiring penetration or
disconnect switch.
4. Filter Section
Filter may be mounted in Mixing Box Section
5. Plenum Section
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
3
®
Mounting Instructions
Hanging Instructions
Greenheck’s Modular Small Cabinet Fan (MSCF)
should be lifted by the factory supplied lifting lugs
(see Figure 1) or frame rails and a spreader bar
(see Figure 2) to prevent damage from occurring to
the equipment. Avoid twisting or uneven lifting of
equipment. Do not lift equipment by coil connections
or headers. The unit must remain upright during lifting.
All access doors and panels must be closed during
lifting to avoid damage.
The MSCF should be hung by the factory supplied
lifting lugs or field supplied frame rails as shown
respectively in Figures 3 and 4. The number of
hanging brackets used will be determined by the
number of fan modules.
Spreader Bar
Figure 3
Lifting lugs
Figure 1
Figure 4
Spreader Bar
External Mounting Isolation
The MSCF is available with external neoprene or
spring isolation options. When external isolation is
selected, a bridge bracket will be provided to reduce
installation time (see Figure 5).
3/8-16x3/4 Spinlock Bolt
Two required per assembly
3/4 inch Flat Washer
One per assembly as needed
3/8-16 Spinlock Nut
Two required per assembly
Bridge Bracket
Part No. 711779
Drawing No. 89814
One required per assembly
Frame Rails
(by others)
Hanging Bracket
Part No. 710774
Drawing No. 85537
Hanging Bracket
Part No. 710774
Figure 2
Drawing No. 85537
3/8-16x3/4 Spinlock Bolt
Two required per assembly
HANGING ASSEMBLY
Bridge Bracket
Part No. 711779
Drawing No. 89814
One required per assembly
3.0 inch
3/4 inch Flat Washer
One required per assembly
Figure 5
3/8-16 Spinlock Nut
Two required per assembly
BASE ASSEMBLY
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
4
®
Modular Construction
The MSCF is designed to be modular so it can be
mounted as an assembly or as individual sections
when the appropriate lifting equipment is not
available.
MSCF Mounting Dimensions
K
J
L
F
A
B
C
D
E
G
H
M
Mixing
Box
24 in.
Plenum
12 in.
Plenum
Filter
*Heating
Cooling / Combo
Coil
Fan
Horizontal Hanging
E
A
D
Unit
Size
B
C
F
G
H
J
K
L
M
w/o
w/
Hot Water 4 Row HW
Vertical Sloped
Filter Filter
1 & 2 Row & Steam
15
20
25
30
45
50
65
85
6.75
6.75
6.75
6.75
6.75
6.75
6.75
6.75
18.5 18.5 6.75
18.5 18.5 6.75
6.75
6.75
6.75
6.75
6.75
6.75
6.75
6.75
18.5
18.5
21
6.75
6.75
6.75
6.75
6.75
6.75
6.75
6.75
9.5
9.5
9.5
9.5
9.5
9.5
9.5
9.5
18.5
18.5
18.5
18.5
18.5
18.5
18.5
18.5
19
19
23
26
26
32
36
36
38
38
38
38
50
50
50
62
2.5
2.5
2.5
2.5
2.5
2.5
2.5
2.5
3
3
3
3
3
3
3
3
.5
.5
.5
.5
.5
.5
.5
.5
43
43
43
43
55
55
55
67
21
25
26
26
32
32
18.5 6.75
18.5 6.75
18.5 6.75
18.5 6.75
18.5 6.75
18.5 6.75
25
26
26
28
28
*See CAPS for electric heating dimensions.
All dimensions are in inches.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
5
®
Dimensional Data
G
F
A
B
C
D
E
Mixing
Box
Plenum
Filter
*Heating
Cooling / Combo
Coil
Fan
A
B
C
D
Inlet
Outlet
Unit
Size
Unit
Width
E
F
G
w/o
w/
Hot Water 4 Row HW
1 & 2 Row & Steam
12 in. 24 in. Vertical Sloped
Height Width Height Width
Filter Filter
15
20
25
30
45
50
65
85
11 24.5 12.75 24.5 12.75 24.5
14 24.5 12.75 24.5 12.75 24.5
12.75
12.75
12.75
12.75
12.75
12.75
12.75
12.75
15.5
15.5
15.5
15.5
15.5
15.5
15.5
15.5
24.5 25
24.5 25
24.5 29
11
14
16
38
38
38
9
12
36
36
36
36
48
4
6.5
8
6.75
6.75
8.5
9
16
27 12.75 24.5 12.75
27
31
32
32
38
38
14
18.5 31 12.75 24.5 12.75
18.5 32 12.75 24.5 12.75
24.5 32 18.5 38
24.5 32 18.5 50
16.5
16.5
19
9
9
10
21
26
26
32 12.75 24.5 12.75
38 12.75 24.5 12.75
38 12.75 24.5 12.75
24.5 38
24.5 42
24.5 42
21
26
26
50
50
62
48 10.25 10
24
48
60
12 12.75
24
12
15
*See CAPS for electric heating dimensions.
All dimensions are in inches.
Weights
A
B
C
**D
**E
F (FC)
F (BI)
Unit
Size
w/o
w/
Hot Water 4 Row HW
1 & 2 Row & Steam
Max
Motor
Max
Motor
12 in. 24 in. Vertical Sloped
CW/DX Fan
Total Fan
Total
Filter Filter
15
20
25
30
45
50
65
85
80
95
107
126
31
36
40
45
50
58
75
85
57
68
34
41
45
50
55
64
77
90
61
72
61
72
86
145
171
190
209
234
269
323
350
94
50
50
144
161
190
225
269
353
453
500
-
-
-
101
112
123
138
159
190
196
111
130
150
194
253
328
360
-
-
-
105 140
118 157
132 176
151 202
197 263
226 302
75
80
80
60
168
182
239
279
333
375
60
228
257
339
379
433
475
84
90
88
75
75
94
100
115
150
175
99
75
100
100
100
100
108
141
170
113
136
140
100
125
140
All weights are approximated. Motor weights may very depending on enclosure type and horsepower.
**Weight information for hot water, steam, chilled water and DX coils is wet weight.
*See CAPS for electric heat dimensions.
Filter Sizes and Quantity
Unit
Size
Face
Area
Face
Area
Vertical
Quantity
Sloped
Quantity
12x12
12x24
16x16
16x20
16x20
12x24
24x24
24x24
24x24
24x24
12x24
24x24
1
1
1
1
2
1
1
2
2
4
2
4
15
9x18
2
1.8
2.5
12x12
12x24
14x18
16x16
16x20
16x24
18x24
24x24
12x24
24x24
1
1
2
1
1
2
2
2
1
2
20
25
30
2.5
3.0
3.4
3.4
3.8
5.3
45
50
65
4.8
5.4
7.2
7.2
7.2
14.4
85
8.9
17.8
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
6
®
Coil Dimensions
Hot Water • 1 and 2 Row
Unit
Size
Face
Area
A
B
C
D
E
F
15
20
25
30
45
50
65
85
1.6
2.2
2.7
3.2
4.5
5.2
6.7
8.6
38
38
38
38
50
50
50
62
12.75
12.75
12.75
12.75
12.75
12.75
12.75
12.75
11.0
14.0
16.0
18.5
18.5
21.0
26.0
26.0
3.0
4.5
4.0
4.0
4.0
4.0
4.0
4.0
0.75
0.75
0.88
0.88
0.88
1.13
1.38
1.38
.5
.5
.5
.5
.5
.5
.5
.5
3
E
C
Outlet
Inlet
F
D
All dimensions are in inches.
A
NOTE
6
Fluid enters the coil from the bottom connection
(Inlet) and exits from the top (Outlet).
B
Hot Water • 4 Row
Unit Face
Size Area
A
B
C
D
E
F
G
15
20
25
30
45
50
65
85
1.6
2.2
2.7
3.2
4.5
5.2
6.7
8.6
38 15.50 9.38 3.188 0.750 4.0 11.0
38 15.50 9.38 3.188 0.750 4.5 14.0
38 15.50 9.38 3.188 0.875 4.0 16.0
38 15.50 9.38 3.188 0.875 4.0 18.8
50 15.50 9.38 3.188 1.375 4.0 21.0
50 15.50 9.38 3.188 1.375 4.0 26.0
50 15.50 9.38 3.188 1.375 4.0 26.0
62 12.75 9.38 3.188 1.375 4.0 26.0
G
F
Outlet
All dimensions are in inches.
A
Inlet
NOTE
D
With airflow from left to right, the fluid enters the coil
from the bottom connection (Inlet) and exits from the
top (Outlet). The other two coil connections should
be capped off (Cap).
E
C
B
Steam • 1 and 2 Row
Unit Face
Size Area
A
B
C
D
E
F
G
15
20
25
30
45
50
65
85
1.6
2.2
2.7
3.2
4.5
5.2
6.7
8.6
38 15.50 7.75 3.31 1.5 5.18 11.0
38 15.50 7.75 3.00 1.5 6.50 14.0
38 15.50 7.75 3.31 2.5 7.69 16.0
38 15.50 7.75 3.00 2.5 9.00 18.5
50 15.50 7.75 3.00 2.5 9.00 18.5
50 15.50 7.75 4.31 2.5 10.18 21.0
50 15.50 7.75 3.00 2.5 12.50 26.0
62 15.50 7.75 3.00 2.5 12.50 26.0
G
Inlet
F
All dimensions are in inches.
A
D
Outlet
NOTE
E
C
Steam enters the coil from the center connection
(Inlet) and exits from the bottom (Outlet).
B
Electric Heat • See our Computer Aided Product Selection (CAPS) Software Program for dimensional data.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
7
®
Coil Dimensions - continued
Chilled Water • 4, 6 or 8 Row
3
NOTE
With airflow from left to right, the fluid enters the coil
from the bottom connection (Inlet) and exits from the
top (Outlet). The other two coil connections should
be capped off (cap).
C
1
A
B
Airflow
J
K
Unit Face
Size Area
A
B
C
4 Row 6 Row 8 Row 4 & 6 Row 6 Row
(cap)
3.88
2
15
20
25
30
45
50
65
85
1.6
2.2
2.7
3.2
4.5
5.2
6.7
8.6
38 24.5 11.0
38 24.5 14.0
38 24.5 16.0
38 24.5 18.5
50 24.5 18.5
50 24.5 21.0
50 24.5 26.0
62 24.5 26.0
10
10
10
10
10
10
10
10
12
12
12
12
12
12
12
12
14
14
14
14
14
14
14
14
0.75
0.75
0.88
0.88
0.88
1.38
1.38
1.38
1.38
1.38
1.38
1.38
1.38
1.63
1.63
1.63
Outlet
(cap)
.75
1.5
K
Inlet
3.75
6.5
J
13.25
18.5
All dimensions are in inches.
Direct Expansion (DX) • 4, 6 or 8 Row
(Orifice Code 18/19)
Coil connection made inside housing.
Two inch hole is provided.
NOTE
3
With airflow from left to right, the fluid enters the coil
from the center connection (Inlet) and exits from the
bottom (Outlet). The other coil connections should
be capped off (cap).
C
1
A
B
Airflow
L
M
N
P
Unit Face
Size Area
A
B
C
4 & 6
Row
(cap)
4 Row 6 Row 8 Row All
All
8 Row
3.88
P
15
20
25
30
45
50
65
85
1.6
2.2
2.7
3.2
4.5
5.2
6.7
8.6
38 24.5 11.0 8.75 10.75 12.75 5.25 0.63 0.63 1.38
38 24.5 14.0 8.75 10.75 12.75 7.00 0.63 0.63 1.38
38 24.5 16.0 8.75 10.75 12.75 8.00 0.88 1.38 1.38
38 24.5 18.5 8.75 10.75 12.75 9.00 0.88 1.38 1.38
50 24.5 18.5 8.75 10.75 12.75 9.00 0.88 1.38 1.38
50 24.5 21.0 8.75 10.75 12.75 10.25 0.88 1.38 1.63
50 24.5 26.0 8.75 10.75 12.75 13.00 1.13 1.38 1.63
62 24.5 26.0 8.75 10.75 12.75 13.00 1.13 1.38 1.63
Inlet
Outlet
N
M
2
3.75
1.5
6.5
L
13.25
18.5
All dimensions are in inches.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
8
®
Coil Dimensions - continued
Direct Expansion (DXI) • 4, 6 or 8 Row
Dual Circuit with 50/50 Face Interlaced Construction
Coil connection made inside housing.
Two inch hole is provided.
NOTE
The first suction header on the entering air side
of the coil is circuited to the top distributor. With
airflow from left to right, the fluid enters the coil
from the center connection (Inlet) and exits from the
bottom (Outlet). The other connections should be
capped off (cap).
3
C
1
Airflow
A
B
(cap) (cap)
Inlet 1
D
E
Unit Face
Size Area
A
B
C
F
G
6 & 8
Row
4 Row
4 Row 6 Row 8 Row
Inlet 2
F
Outlet 2
3.75
G
30
45
50
65
85
3.2
4.5
5.2
6.7
8.6
38 24.5 18.5 9.25 11.0 7.88 8.50
50 24.5 18.5 9.25 11.0 7.88 8.50
8.5
8.5
7.00 12.0
7.00 12.5
Outlet 1
50 24.5 21.0 9.25 11.0 7.50 8.50 8.75 7.75 13.5
50 24.5 26.0 9.25 11.0 8.12 8.75 8.75 9.50 17.0
62 24.5 26.0 9.25 11.0 8.12 8.75 8.75 9.50 17.0
6.5
1.5
2
E
D
13.25
18.5
All dimensions are in inches.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
9
®
any two supply power connections will reverse the
direction of rotation.
System Start-Up
For proper unit function and safety, follow everything
in this start-up procedure in the order presented.
This is to be done after the electrical connections are
complete.
To reverse the rotation, turn the power off and use the
following procedure:
•
For single phase units, rewire the motor per the
instructions on the motor.
PRE-START CHECK LIST
1. Disconnect and lock-out all power switches to fan.
•
For three phase units, interchange any two
power leads. This can be done at the motor
starter.
2. Check all fasteners, set screws and locking
collars on the fan, bearings, drive, motor base and
accessories for tightness.
3. Check for Vibration
Check for unusual noise, vibration or overheating of
bearings. Excessive vibration may be experienced
during initial start-up. Left unchecked, excessive
vibration can cause a multitude of problems, including
structural and/or component failure. Many conditions
can be discovered by careful observation. If the
problem is wheel unbalance, in-place balancing can
be done providing there is access to the fan wheel.
Generally, fan vibration and noise is transmitted
to other parts of the building by the ductwork. To
eliminate this undesirable effect, Greenheck has
used a heavy canvas connection between the scroll
and the discharge of the fan. If noise is an issue, we
recommend using heavy canvas connections on the
inlet of the fan. Refer to the Troubleshooting section of
this manual if a problem develops.
3. Rotate the fan wheel by hand and assure no parts
are rubbing.
4. Check the V-belt drive for proper alignment and
tension.
Unit Size
25 - 50
G
1/4 inch
3/8 inch
65 - 85
G
Wheel Overlap Dimensions
SPECIAL TOOLS REQUIRED
4. Air Volume Check and Measurement
Along with the building balance, the unit’s air volume
(cfm) should be measured and compared with its
rated air volume. This unit is flexible for varying air
volume, but the actual air volume should be known for
making final adjustments. The most accurate way to
measure the air volume is by using the pitot traverse
method in the ductwork away from the blower. Other
methods can be used, but should be proven and
accurate. To adjust the air volume, change the fan rpm
or the system losses. See Troubleshooting section in
this guide.
• Voltage Meter
• Tachometer
• Amperage Meter
1. Check Voltage
Before starting the unit, compare the supplied voltage
with the unit’s nameplate voltage and the motor
voltage. Units are not provided with thermal overload
protection unless a control center has been ordered
with the unit or the motor has been selected with
thermal overload protection.
2. Check Blower Rotation
5. Measure Motor Voltage, Amperage
A common problem is wheel rotation in the wrong
direction. For centrifugal fans, incorrect wheel rotation
will provide poor air performance, motor overloading
and possible burnout. Rotation should be checked
while the fan is coasting to a stop. Proper wheel
rotation is shown.
and Fan RPM
All access doors must be installed. Measure and
record the input voltage and motor amperage(s).
To measure the fan RPM, the blower door will need to
be removed. Minimize measurement time because the
motor may over amp with the door removed.
Compare measured amps to the motor nameplate
full load amps and correct if over amping. See the
Troubleshooting section in this guide.
Backward
Inclined
Forward
Curved
Proper Wheel Rotation
When connecting a 3-phase motor, there is a 50%
chance that the fan will run backwards. Changing
Model MSCF Modular Small Cabinet Fan
10
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Troubleshooting
NOTE
Before taking any corrective action, ensure unit is incapable of operation during repairs.
Symptom
Possible Cause
Corrective Action
Blown fuse or open circuit breaker
Broken fan belt
Replace fuse or reset circuit breaker and check amps
Replace
Blower fails to
operate
Defective motor or capacitor
Motor starter overloaded
Airflow too high
Replace
Reset starter and check amps
Check airflow and adjust drives if needed
Static pressures are higher or lower
than design
If higher, ductwork should be improved
If lower, fan RPMs should be lower
Blower rotation is incorrect
Motor voltage incorrect
Check rotation and correct
Motor overamps
Check motor nameplate and supplied voltage
See specifications and catalog for fan curves to determine
if horsepower is sufficient
Motor horsepower too low
Shorted windings in motor
Replace motor
Mixing box damper not fully open
Adjust damper linkage or replace damper motor
Improve ductwork to eliminate losses using good duct
practices
System static pressure too high
Blower speed too low
Mixing box dampers closed
Dirty or clogged filters
Leaks in ductwork
Check for correct drives and RPMs with catalog data
Open and adjust
Clean or replace
Repair
Insufficient airflow
Elbows, or other obstructions may
restrict fan outlet
Correct or improve ductwork
Belt slippage
Adjust belt tension
Correct as shown in System Start-Up section, Step #2,
page 10
Unit running backwards
Excessive dirt buildup on wheels
Blower fan speed too high
Filter(s) not in place
Clean wheel
Check for correct fan RPM
Install filters
Too much airflow
Insufficient static pressure
(airflow resistance)
Induce static pressure into system ductwork
Center wheel
Wheel improperly aligned and rubbing on
housing
Loose wheel on shaft
Loose motor or blower sheave
Belts too loose
Tighten wheel setscrew
Tighten sheave setscrew
Adjust belt tension after 24 hours of operation
Loosen to maintain 3/8 inch deflection per ft. of span
between sheaves
Belts too tight
Worn belt
Replace
Excessive noise or
vibration
Motor base or blower loose
Worn bearings
Tighten mountings bolts
Replace
Bearing and drive alignment
Motor out of balance
Realign
Replace
Unbalanced wheel caused by excessive
dirt and grease buildup
Replace or rebalance
Sheaves eccentric or out-of-balance
Accumulation of material on wheel
Foreign objects in wheel or housing
Replace or rebalance
Clean wheel and housing
Remove objects. Check for damage or unbalance.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
11
®
3. When connecting suction and liquid connections,
make sure the coil is free from all foreign material.
Make sure all joints are tight and free of leakage.
Start-Up of Coil Module
Hot Water and Chilled Water
4. Greenheck does not supply compressor or
condensing units, for further instruction on DX coil
installation and operation contact your compressor
and/or condenser manufacturer.
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Water pipes are copper
with sweat connections. USE WET TOWEL TO
AVOID BURNING COIL CONNECTION GROMMETS.
When installing coupling, do not apply undue
stress to the connection extending through the
unit. Use a back-up pipe wrench to avoid breaking
the weld between coil connection and header.
DXI coils have dual connections and should be used
with two compressors.
WARNING
Standard unit insulation of 1.5 lbs. density has an
insulation R-value of 3.7.
2. Connect the water supply to the bottom
connection on the air-leaving side and the water
return to the top connection on the air-entering
side. The extra bottom connection can be used for
an auxiliary manual drain connection, and the extra
top connection may be used for an automatic air
vent, or the extra connections can be capped. To
ensure proper venting, an external air vent in the
piping is recommended. Connecting the supply
and/or return in any other manner will result in very
poor performance. CAP UNUSED CONNECTIONS.
For applications where the unit discharge
temperatures are below 55°F and the unit is installed
in a warm, humid environment, additional insulation
may need to be applied to the exterior of the unit to
prevent condensation.
Steam Coils
Application Recommendations
Satisfactory operation and
service life are best
ensured when coils
are installed with
proper piping,
trap and support
arrangement.
3. The air vent at the uppermost point should be
temporarily opened during system start-up to
release all of the air from the coil. To maintain heat
transfer capacity, periodically vent any air in coil.
Vent to be located behind connections side access
door.
The following
4. Water coils are not normally recommended for
use with entering air temperatures below 40°F.
No control system can be depended on to be
100% safe against freeze-up with water coils.
Glycol solutions or brines are the only safe media
for operation of water coils with low entering air
conditions.
notes and
drawing are
recommended
for the coil unit
installation and
operation.
General
Strainer
WARNING
1. Provide
Float & Thermostat Trap
Gate Valve
separate
supports and
hangers for the
unit and the piping.
Check Valve
Control Valve
Vacuum Breaker
Continuous water circulation through the coil at all
times is highly recommended.
Modulating Two-Position
Steam Coil Piping
5. Pipe sizes for the system must be selected on the
basis of the head (pressure) available from the
circulation pump. Piping should be in accordance
with accepted industry standards.
2. Be certain that adequate piping flexibility is
provided. Stresses resulting from expansion of
closely coupled piping and coil arrangement can
cause serious damage.
6. For chilled water coils, the condensate drain
pipe should be sized adequately to ensure the
condensate drains properly. See Drain Pan Traps
section and related drawing.
3. Standard steam coils are pitched in the casings
when installed for horizontal airflow. The casing
must be level after the unit is installed for proper
condensate drainage. If condensate is not
removed, the coil will suffer from water hammering
and will have a shortened life. On vertical airflow
applications, the coils must be pitched when
installed.
Direct Expansion (DX) Coils
1. Piping should be in accordance with accepted
industry standards. Pipework should be supported
independently of the coils. Undue stress should not
be applied at the connection to coil headers.
4. Do not reduce pipe size at the coil return
connection. Carry return connection size through
the dirt pocket, making the reduction at the branch
leading to the trap.
2. The condensate drain pipe should be sized
adequately to ensure the condensate drains
properly. See Drain Pan Traps and related drawing.
Model MSCF Modular Small Cabinet Fan
12
®
Download from Www.Somanuals.com. All Manuals Search And Download.
General - continued
Drain Pan / Drain Trap
5. It is recommended that vacuum breakers be
installed on all applications to prevent retaining
condensate in the coil. Generally, the vacuum
breaker is to be connected between the coil inlet
and the return main. The vacuum breaker should
be open to the atmosphere and the trap design
should allow venting of large quantities of air.
Drain lines and traps should be run full size from the
drain pan connection. Drain pans should have drain
lines and traps to permit the condensate from the
coils to drain freely. On all units with drain pans, the
trap depth and the distance between the trap outlet
and the drain pan outlet should be twice the static
pressure (P) in the drain pan section under normal
operation to assure the trap remains sealed.
6. Do not attempt to lift condensate when using
modulating or on-off control.
7. Do not reduce the pipe size leaving the coil.
Traps
1. Size traps in accordance with the manufacturer’s
recommendations. Be certain that the required
pressure differential will always be available. DO
NOT UNDERSIZE.
2P = minimum
2P = minimum
2. Float and thermostatic or bucket traps are
recommended for low pressure steam. On high
pressure systems, bucket traps are normally
recommended. The thermostatic traps should be
used only for air venting.
Drain Pan / Drain Trap
3. Bucket traps are recommended for use with on-off
control only.
4. Locate traps at least 12 inches below the coil
return connection.
Controls
1. On high pressure installations, a two-position
steam valve with a face and bypass arrangement is
preferred where modulating control is required.
2. Modulating valves must be sized properly. DO NOT
UNDERSIZE.
Freezing Conditions (entering air below 35°F)
1. 5 PSI steam must be supplied to the coil at all times.
2. Modulating valves are not recommended. Control
should be by means of face and bypass dampers.
3. Provision should always be made to thoroughly
mix fresh air and return air before it enters the
coil on return air units. Also, temperature control
elements must be properly located to obtain true
air mixture temperatures.
4. As additional protection against freeze-up, the trap
should be installed sufficiently—far below the coil
to provide an adequate hydrostatic head to ensure
removal of condensate during an interruption in the
steam pressure. Estimate 3 feet for each 1 PSI of
trap differential required.
5. On start-up, admit steam to coil ten minutes before
admitting outdoor air.
6. Provision must be made to close fresh air dampers
if steam supply pressure falls below minimum
specified.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
13
®
Sizing of Supply Conductors
Installation of Electric Heater
(optional)
The required minimum size of supply conductors
is marked at the field wiring terminals within the
heater control box or reference the Supply Wire Size
table included in this section. The wire gauges are
calculated for 125% of the heater line current as
required by the National Electric Code, Article 424-3(b)
based on conductor insulation rated for 75°C (167°F).
WARNING
Electrical Shock Hazard! Disconnect all power
sources before doing any work on the unit.
General:
Supply Wire Size
The requirements and practices described below
are based on the National Electric Code (NEC) and
The Space Heating Standard of the Underwriters
Laboratories Inc. (UL). Although UL requirements
are uniform throughout the country, local electrical
codes may deviate from the National Electrical Code.
Therefore, local inspection authorities should be
consulted regarding local requirements.
(Not more than six conductors in Single Conduit1)
Max. Heater
Max. Heater
AWG or
MCM
AWG or
MCM
Line Current2
Line Current2
Copper3
Copper3
14
12
10
8
12
0000
250
300
350
400
500
600
700
750
800
900
1000
184
16
204
24
228
Electrical Wiring Instructions:
36
248
1. Use the wiring diagram supplied with the heater
as a guide in correlating field wiring with the
heater internal wiring.
2. All field wiring to the heater must meet the
requirements of the National Electric Code and
any other applicable local or state codes.
3. Wiring to the heater must be rated for 75°C
(167°F) minimum.
4. If heater does not have a built-in disconnect
switch or main circuit breaker, install a remote
disconnect (furnished by others) in accordance
with the National Electric Code, Article 424-65.
6
52
268
4
68
304
3
80
336
2
92
368
1
104
120
140
160
380
0
392
00
000
416
436
1
2
For 7-24 conductors in raceway or cable, reduce allowable
heater line currents to 87½% of those shown above.
Calculation of Line Currents (amps):
Based on 30°C. (86°F) ambient temperature, for higher
ambient temperature see National Electric Code table
310-16 and 310-18 Note 13.
watts
Single Phase Current =
volts
3
Based on 80% of ratings in the National Electric Code
table 310-16 for 75°C insulation.
EXAMPLE: 5 kW, 208 volt
5000 watts
= 24 amps
208 volts
Effect of Low Voltage on Wattage and
British Thermal Unit (BTU)
watts
Three Phase Current =
volts x 1.73
The heating elements may be used on voltages
lower than the design voltage of the heater, however,
the wattage and BTU output will be reduced to the
percentages listed in the table below.
EXAMPLE: 14.4 kW, 208 volt
14400 watts
208 volts x 1.73
14400
360
=
= 40 amps
De-rated Wattage for Low Voltage
% of
% of
Heater Line
Heater Heater Line
Heater
Voltage Voltage Wattage Voltage Voltage Wattage
and BTU
and BTU
460
440
265
254
230
220
208
200
92
84
92
84
92
84
75
69
200
190
115
110
92
83
92
84
480
277
208
120
240
Model MSCF Modular Small Cabinet Fan
14
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Sequence of Operation - Electric
Heater
1. Electric heaters are divided in to equally sized
steps. For example, a 60 kW heater with 3 steps
will have 20 kW per step. The thermostat and
step controller will control these steps.
2. 120 Volt power from the control center (when
supplied) or by others with out a control center,
is delivered to the electric heater for the step
controller. This power must be interlocked with
the supply fan, so when the fan is off, the heater
control power is off.
3. A step control with the thermostat set to
70ºF the heater will be off with a temperature
sensing above 70ºF. As the temperature varies
the steps turn on and off to hold the setpoint
discharge temperature. The colder the discharge
temperature becomes the more steps the
controller will energize.
4. With a step controller, in addition to the fan
interlock mentioned in Step 2, the heater has an
airflow switch to prove that airflow is established
before energizing the steps. The heater also
has an automatic resetting highlimit switch and
manual resetting highlimit switch set above the
automatic switch to protect from overheating.
5. For more detailed information on your specific
controller, please review the controller spec
sheet supplied with the heater.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
15
®
Every Three (3) Months
Fan Maintenance
Filters - The filter in the unit should be inspected
at least every three (3) months. Depending on the
environment, filters could require changing or cleaning
more or less often. The filters can be slid out of the
coil connection side of the unit.
Greenheck recommends these procedures to ensure
trouble-free operation of this unit. It is especially
important to maintain heater units for clean and
efficient operation. Most unit failures can be attributed
to poor setup or poor maintenance.
If washable filters are installed, they can be washed in
warm soapy water. An adhesive spray can be applied
to increase filter efficiency.
A record of maintenance performed on this unit
should be kept. This information will provide essential
information if problems are encountered. A section at
the back of this manual is provided for recording the
unit’s maintenance history.
If disposable filters are installed, check by holding up
to a light source. If light cannot pass through the filter,
it should be replaced. Replacement filters should be
of the same manufacturer and size. When reinstalling
filters, be sure to install with the airflow in the correct
direction indicated on the filter.
CAUTION
When performing any maintenance on this unit,
be certain the power is disconnected and cannot
be accidentally turned on. The control center
disconnect can be locked in the off position.
Yearly
Bearings — Most bearings are permanently
lubricated and require no further lubrication under
normal use. Normal use being considered -20ºF to
120ºF and in a relatively clean environment. Some
bearings are re-lubricatable and will need to be re-
greased depending on fan use. Check your bearings
for grease fittings to find out what type of bearing
you have. If your fan is not being operated under
normal use, bearings should be checked monthly for
lubrication.
Two Weeks after Start-Up
Belts - Belts tend to stretch after a period of
time. They should be
periodically checked
for wear and tightness.
Approximately 3/8 inch
of deflection per ft.
Belt Span
64
Deflection =
Belt Span
of span between
Motors — Motor maintenance is generally limited to
cleaning and lubrication (where applicable). Cleaning
should be limited to the exterior surfaces only.
Removing dust and grease buildup on motor housing
assures proper motor cooling. Greasing of motors
is intended only when grease fittings are provided.
Many fractional motors are permanently lubricated
and require no further lubrication. Motors supplied
with grease fittings should be greased in accordance
with manufacturer’s recommendations. When motor
temperature does not exceed 104ºF (40ºC), the grease
should be replaced after 2000 hours of running time
as a general rule.
sheaves is standard for
belt tightness. When
replacing belts, use the
same type as supplied
with the unit. Matched
belts should always be
NOTE: For motors of 1 hp or less a
smaller sliding base bracket
is used to attach to blower.
used on units with multi-groove pulleys.
If adjustments are made, it is very important to check
the pulleys for proper alignment. Misaligned pulleys
lead to excessive belt wear, vibration, noise and
power loss.
CORRECT
WRONG
WRONG
WRONG
Wheels — Wheels require very little attention when
moving clean air. Occasionally, oil and dust may
accumulate on the wheel causing imbalance. When
this occurs the wheel and housing should be cleaned
to assure smooth and safe operation. Inspect fan
impeller and housing for fatigue, corrosion or wear.
Belt Alignment
Routinely check all fasteners, set screws and locking
collars on the fan, bearing, drive, motor base and
accessories for tightness.
Replacement of belts can be accomplished by
loosening the motor to the point where the belts
can be removed by hand. Do not force belts on or
off as this may cause breakage of cords leading to
premature belt failure. Belts should be adjusted as
above.
Model MSCF Modular Small Cabinet Fan
16
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Coil Maintenance
Start-Up Documentation
Coils must be clean to obtain maximum performance.
Check once a year under normal operating conditions
and, if dirty, brush or vacuum clean. Soiled fins reduce
the capacity of the coil, demand more energy from the
fan, and create an environment for odor and bacteria
to grow and spread through the conditioned zone.
High pressure water (400 psi or less) may be used to
clean coils with fin thickness over 0.006 inches thick.
Test the spray pressure over a small corner of the
coil to determine if the fins will withstand the spray
pressure.
Job Information
Job Name
_________________________________
Address
_________________________________
City ________________ State ______ Zip ___________
Phone Number _________________________________
Contact Person _________________________________
Start-Up Company Information
Service Oranization _______________________________
Address
City ________________ State ______ Zip ___________
Phone Number
Fax Number
For coils with fragile fins or high fin density, foaming
chemical sprays and washes are available. Many coil
cleaners contain harsh chemicals, so they must be
used with caution by qualified personnel only. Care
must be taken not to damage the coils, including fins,
while cleaning.
_______________________________
_______________________________
_______________________________
_______________________________
Start-Up Date
Start-Up Personnel Name__________________________
CAUTION
Fin edges are sharp.
Nameplate Information
Unit Model Number _______________________________
Volts ________________Hertz ________ Phase _______
Amps _______________Mark _______________________
Fan rpm_____________
Winterizing Coils
Coil freeze-up can be caused by such things as air
stratification and failure of outdoor air dampers and/
or preheat coils. Routine draining of water cooling
coils for winter shutdown cannot be depended upon
as insurance against freeze-up. Severe coil damage
may result. It is recommended that all coils be drained
as thoroughly as possible and then treated in the
following manner.
Unit Serial Number _______________________________
Field Start-Up Documentation
o Check blower rotation
o Check air volume (cfm)
_________ Design
Fill each coil independently with an antifreeze solution
using a small circulating pump and again thoroughly
drain. Check freezing point of antifreeze before
proceeding to next coil. Due to a small amount of
water always remaining in each coil, there will be
diluting effect. The small amount of antifreeze solution
remaining in the coil must always be concentrated
enough to prevent freeze-up.
_________ Actual
o Actual motor voltage
o Actual motor hertz
o Actual motor phase
o Actual motor amps
_________ Volts
_________ Hertz
_________ Phase
_________ Amps
NOTE: Carefully read instructions for mixing antifreeze
solution used. Some products will have a higher
freezing point in their natural state than when mixed
with water.
Drive
o Fan RPM Range
_________ Minimum
_________ Maximum
Drain Pan Maintenance
Drain pans in any air conditioning unit will have
some moisture in them, therefore, algae and other
organisms will grow due to airborne spores and
bacteria. Periodic cleaning is necessary to prevent
this buildup from plugging the drain and causing the
drain pan to overflow. Inspect twice a year to avoid
the possibility of overflow. Also, drain pans should be
kept clean to prevent the spread of disease. Cleaning
should be performed by qualified personnel.
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
17
®
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Model MSCF Modular Small Cabinet Fan
18
®
Download from Www.Somanuals.com. All Manuals Search And Download.
Maintenance Log
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Date __________________ Time _____________ AM/PM
Notes:___________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
_________________________________________________
Model MSCF Modular Small Cabinet Fan
Download from Www.Somanuals.com. All Manuals Search And Download.
19
®
Warranty
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from
the purchase date. Any units or parts which prove defective during the warranty period will be replaced at our option
when returned to our factory, transportation prepaid. Motors are warranted by the motor manufacturer for a period of
one year. Should motors furnished by Greenheck prove defective during this period, they should be returned to the
nearest authorized motor service station. Greenheck will not be responsible for any removal or installation costs.
As a result of our commitment to continuous improvement, Greenheck reserves the right to change specifications
without notice.
Greenheck Catalog IAH Series (MSCF-FC • MSCF-BI •
LFC-C • VFC-FC • VFCD-FC) provides additional information
describing the equipment, fan performance, available
accessories, and specification data.
AMCA Publication 410-96, Safety Practices for Users and
Installers of Industrial and Commercial Fans, provides
additional safety information. This publication can be
®
Phone: (715) 359-6171 • Fax: (715) 355-2399 • E-mail: [email protected] • Website: www.greenheck.com
462888 • MSCF Modular Small Cabinet Fan, Rev. 2, November 2005
Copyright 2005 © Greenheck Fan Corporation
20
Download from Www.Somanuals.com. All Manuals Search And Download.
|