Greenheck Fan Electric Heater ERH 20 User Manual

PART #459657  
READ AND SAVE THESE INSTRUCTIONS  
ENERGY RECOVERY UNIT  
with HEATING  
®
Models:  
ERH-20, 45, 55, & 90  
INSTALLATION, OPERATION AND MAINTENANCE MANUAL  
**WARNING**  
DISCONNECT AND SECURE TO THE "OFF"  
Energy Recovery Wheel  
POSITION ALL ELECTRICAL POWER TO THE  
UNITS PRIOR TO INSPECTION OR SERVICING.  
FAILURE TO COMPLY WITH THIS SAFETY  
PRECAUTION COULD RESULT IN SERIOUS  
INJURY OR DEATH.  
**IMPORTANT**  
ALL FACTORY PROVIDED LIFTING LUGS MUST  
BE USED WHEN LIFTING THE UNITS. FAILURE  
TO COMPLY WITH THIS SAFETY PRECAUTION  
COULD RESULT IN PROPERTY DAMAGE,  
SERIOUS INJURY OR DEATH.  
INSTALLATION SUPPLEMENT  
Refer to the following Greenheck installation  
supplement for ERH units supplied with Indirect  
Gas (IG) heating:  
Model PVF, Indirect Gas Fired Furnaces for  
Energy Recovery Units, Part #461006  
Heating Section  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BASIC OPERATION  
The ERH brings in fresh,  
outdoor air and  
Energy  
Recovery  
Wheel  
Exhaust Air  
from building  
removes stale, exhaust  
air. Prior to discharging  
the exhaust air, the  
energy recovery wheel  
transfers energy from  
the exhaust air to the  
outdoor air at an  
Exhaust Air  
discharged outside  
efficiency of 70-80%.  
Simply put, this unit  
preconditions the  
Outdoor Air  
outdoor air to save  
money on heating and  
cooling costs. This  
particular unit also has  
a heater option  
Optional  
Heater  
available after the  
recovery wheel to  
further increase the  
fresh air temperature if  
desired.  
Preconditioned Air sent  
to conditioning system  
INSTALLATION  
Lift using lifting  
lugs and  
spreader bar  
The system design and installation should follow accepted industry  
practice, such as described in the ASHRAE Handbook.  
Adequate space should be left around the unit for piping coils and  
drains, filter replacement, and maintenance. Sufficient space should  
be provided on the side of the unit for routine service and  
component removal should that become necessary.  
See page 6 for more detail on appropriate clearances.  
LIFTING  
Units must be lifted as it ships from the factory. All units are  
equipped with lifting lugs. THE USE OF ALL LIFTING LUGS IS  
MANDATORY WHEN LIFTING. Lifting should only be done with all  
access doors closed to avoid damaging the unit. To prevent damage  
to the unit cabinetry, use spreader bars. Spreader bars must be in  
position to stop cables from rubbing the frame or panels. Before  
hoisting into position, test lift to insure stability and balance. Avoid  
twisting or uneven lifting of the unit. Never lift units by weatherhoods.  
FIGURE 1  
RECOMMENDED ROOF OPENING  
UNIT WEIGHTS (dry weights)  
V
TABLE 2  
TABLE 1  
Unit Size Approx. Weight (lbs)  
Model  
U
V
EXHAUST  
INLET  
ERH-20  
ERH-45  
ERH-55  
ERH-90  
1000  
1800  
2500  
4500  
ERH-20  
ERH-45  
ERH-55  
ERH-90  
46  
54  
65  
85  
37  
39  
47  
49  
U
SUPPLY  
OUTLET  
Dimensions shown are in inches.  
FIGURE 2  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROOF CURB MOUNTING  
1. Factory Supplied Roof Curbs  
Roof curbs are Model GKD, which are shipped in a  
knockdown kit and require field assembly (by  
others). Assembly instructions are included with  
the curb.  
2. Cut Roof Opening and Locate Curb  
Layout the unit roof opening such that the supply  
discharge & exhaust inlet of the unit will line up  
with the corresponding ductwork (refer to  
Recommended Roof Openings on page 3). Be  
sure to allow for the recommended service  
clearances. Keep the supply inlet of the unit away  
from any other exhaust fans.  
3. Install Curb  
Locate curb over roof opening and fasten in place.  
Check that the diagonal dimensions are within  
1/8 inch of each other and adjust as necessary.  
Shim as required to level. Lower unit onto curb by  
following the LIFTING instructions on page 3 of  
this manual. Note,  
TABLE 3  
roof curbs fit inside  
L
the unit base.  
Curb Outside Dimensions  
W
Model  
L
W
4. Install Duct Work  
Installation of all  
FIGURE 3  
ERH-20  
ERH-45  
ERH-55  
ERH-90  
73  
80.75  
94  
51  
ducts should be  
60.63  
71.5  
done in accordance  
with SMACNA and  
AMCA guidelines.  
Roof curb details, including duct  
location dimensions, are available  
on ERH roof curb submittals.  
106.25 90.75  
Dimensions shown are in inches.  
DUCT WORK CONNECTIONS  
Examples of good and poor fan-to-duct connections are shown below (See FIGURE 4). Airflow out of the fan  
should be directed straight or curve the same direction as the fan wheel rotates. Poor duct installation will result  
in low airflow and other system effects.  
n
o
i
t
n
o
i
t
Length of Straight Duct  
a
t
a
t
o
o
R
R
GOOD  
POOR  
FIGURE 4  
Recommended Discharge  
Duct Size and Length  
TABLE 4  
ERH  
Blower  
Size  
Straight  
Duct  
Length  
ERH  
Model  
Duct  
Size  
20  
45  
55  
90  
10  
12  
15  
18  
14 x 14  
20 x 20  
28 x 28  
32 x 32  
40  
48  
60  
72  
Dimensions shown are in inches.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
INSTALLATION (continued)  
WEATHERHOODS  
Supply weatherhood will be factory mounted. The exhaust weatherhood is shipped separately as a kit with its  
own instructions.  
EXHAUST DAMPERS  
Backdraft dampers for exhaust discharge are mounted in the unit. Motorized dampers are shipped loose (inside  
ERH) and must be field installed.  
ELECTRICAL CONNECTIONS  
The electrical supply must be compatible with that shown on the nameplate: voltage, phase, and amperage  
capacity. The electrical supply line must be properly fused and conform to local and national electrical codes.  
All internal electrical components are pre-wired at the factory. Field electrical connections only need to be made  
inside the unit to the main disconnect (See FIGURE 5, Item #1) and the 24 volt control circuit (See FIGURE 5,  
Item #7). A door interlocking safety disconnect is provided as standard feature.  
Note: Standard factory installed electric post heaters have their own disconnect separate from the unit  
disconnect. Thus, electric post heaters require a separate power connection.  
IMPORTANT:  
Use minimum 14 ga. wire for 24 volt control power.  
Control wire resistance should not exceed 0.75 ohms (approximately 285 feet total length for  
14 ga. wire; 455 feet total length for 12 ga. wire). If wire resistance exceeds 0.75 ohms, an  
industrial-style, plug-in relay should be added to the unit control center and wired in place of  
the remote switch (between terminal blocks 2 and 3 on the control strip — See FIGURE 5,  
Item #7). The relay must be rated for at least 5 amps and have a 24 Vac coil. Failure to  
comply with these guidelines may cause motor starters to “chatter” or not pull in which can  
cause contactor failures and/or motor failures.  
TYPICAL CONTROL CENTER COMPONENTS  
1. Main Disconnect  
2. Motor Starter — Exhaust/Scavenger  
Air Fan  
3. Motor Starter — Outdoor Air Fan  
4. Motor Contactor — Energy Wheel  
5. Control Power Transformer  
(24 VAC Secondary)  
6. Energy Wheel Motor Transformer  
(230 VAC Secondary)  
(for ERH-20 & ERH-45 units with  
primary voltage greater than 230 Vac)  
7. 24 VAC Terminal strip  
1
8
5
6
8. Fuses for the control circuit, wheel  
drive transformer, and blower  
motors.  
7
4
Control Center  
O
f
f
On  
3
2
Main  
Disconnect  
Intake  
Hood  
FIGURE 5  
Exhaust  
Hood  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE CLEARANCES / ACCESS PANEL LOCATIONS for Model ERH  
ERH-20, 45, 55, and 90 units require minimum clearances for access on all sides for routine maintenance. Filter  
replacement, drain pan inspection and cleaning, energy wheel cassette inspection, fan bearing lubrication and  
belt adjustment, are examples of routine maintenance that must be performed. Blower and motor assemblies,  
energy recovery wheel cassette, coil and filter sections are always provided with a service door or panel for  
proper component access. Clearances for component removal may be greater than the service clearances,  
refer to FIGURES 6 and 7 below for these dimensions.  
Clearances for service and component removal on ERH-20 and ERH-45  
36 in.  
Exhaust  
Hood  
Access Panel  
Electrical Box  
36 in.  
0 in.  
Exhaust Air  
Intake  
Clearance without  
IG Heater  
52 in.  
Clearance with  
IG Heater  
Access Panel  
*48 in. **64 in.  
TOP VIEW  
*Clearance for energy wheel removal on ERH-20.  
**Clearance for energy wheel removal on ERH-45.  
FIGURE 6  
Clearances for service on ERH-55 and ERH-90  
42 in.  
Exhaust  
Hood  
Access Panel  
Electrical Box  
42 in.  
0 in.  
Exhaust Air  
Intake  
Clearance without  
IG Heater  
52 in.  
Clearance with  
IG Heater  
Access Panel  
42 in.  
TOP VIEW  
FIGURE 7  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
WATER COIL LOCATION AND CONNECTION  
A hot water coil can be factory installed in the coil section of the ERH. The coil section is downstream of the  
energy wheel on the supply air side of the unit. Coil connections are external to the unit as shown below. Coil  
connections not external have been ordered from the factory with internal or exhaust air stream connections.  
FIGURE 9  
FIGURE 10  
TABLE 5  
Model  
ERH-90 Coil  
Connections  
A
B
C
D
D
ERH-20  
15  
33 34  
39 14  
48 14  
54 14  
41 14  
46 34  
46 34  
50 12  
1 12 NPT  
1 12 NPT  
2 NPT  
ERH-45L 17 12  
ERH-45H 17 12  
Top  
Coil  
3034  
ERH-55  
ERH-90  
17 12  
2 NPT  
1 12 NPT  
17 12 See Note 5 62 14  
Note 1: Dimensions shown are for 1-row coil.  
Note 2: All dimensions are in inches (measured  
to center of coil connections).  
B
634  
Note 3: NPT - National Pipe Thread.  
Note 4: ‘A’ dimension assumes a 12 in. curb.  
Note 5: The ERH-90 uses a dual coil (stacked  
on top of each other). Refer to FIGURE  
10 for the ‘B’ dimension.  
Bottom  
Coil  
3034  
C
A
WATER COIL APPLICATION  
RECOMMENDATIONS  
Factory installed heating components are mounted  
down stream of the energy wheel on the supply air side  
of the unit.  
DX coil liquid  
connection  
access door  
See FIGURE 8 & 9 for coil connection location. Coil  
connections are located external to the unit as shown.  
Coil connections that are not external have been ordered  
from the factory with interior or exhaust air stream coil  
connections.  
Water coil  
connections  
1. Piping should be in accordance with accepted  
industry standards. Pipework should be supported  
independently of the coils. Water connections are  
male NPT iron pipe. When installing couplings, do  
not apply undue stress to the connection  
extending through the unit. Use a backup pipe  
wrench to avoid breaking the weld between coil  
connection and header.  
FIGURE 8  
4. Water coils are not normally recommended for use  
with entering air temperatures below 40oF;  
however, the energy recovery wheel maintains a  
pre-coil temperature higher than 40oF. No control  
system can be depended on to be 100% safe  
against freeze-up with water coils. Glycol  
solutions or brines are the only safe media for  
operation of water coils with low entering air  
conditions.  
2. Connect the WATER SUPPLY TO THE BOTTOM  
CONNECTION on the air leaving side and the  
WATER RETURN TO THE TOP CONNECTION on  
the air entering side. To insure proper venting, an  
external air vent in the piping is recommended.  
Connecting the supply and/or return in any other  
manner will result in very poor performance. Be  
sure to replace factory installed grommets around  
coil connections if removed for piping. Failure to  
replace grommets will result in water leakage into  
the unit and altered performance.  
CONTINUOUS WATER CIRCULATION THROUGH  
THE COIL AT ALL TIMES IS HIGHLY  
RECOMMENDED.  
5. Pipe sizes for the system must be selected on the  
basis of the head (pressure) available from the  
circulation pump. The velocity should not exceed  
6 feet per second and the friction loss should be  
approximately 3 feet of water column per 100 feet  
of pipe.  
3. The air vent at the uppermost point should be  
temporarily opened during system start-up to  
release all of the air from the coil. To maintain heat  
transfer capacity, periodically vent any air in coil.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRIC HEATER APPLICATION/OPERATION  
Factory installed electric heaters can be provided for preheat and/or post-heat (see FIGURE 11). An electric  
preheater warms the outdoor air prior to the energy recovery wheel to prevent frosting on the wheel. An electric  
post-heater warms the air leaving the energy recovery wheel to a user specified discharge temperature. Electric  
heaters are available in 208, 230, or 460 Vac (refer to heater nameplate for voltage).  
Preheaters:  
Preheaters are standard as 2-stage, step control. Step control heaters are designed with  
multiple stages made up of equal increments of heating capability. For example, a 10 kW  
heater with two stages will be composed of two 5-kW stages. Preheaters are single point  
wired at the factory. A temperature sensor (with field adjustable set point) is mounted in the  
outdoor airstream after the preheater to turn the preheater on. See FROST CONTROL  
APPLICATION/OPERATION for typical set points. If the outdoor air temperature falls below the  
set point, the first stage of the preheater will turn on. If the first stage does not satisfy the set  
point, the second stage will also turn on.  
Post-heaters: Post-heaters are standard as 4-stage, step control. Post-heaters are not single point wired  
(see ELECTRICAL CONNECTIONS, page 5). The functionality of a 4-stage heater is the same  
as the 2-stage preheater above, except it has an additional two stages of heat control.  
Post-heaters supplied with Greenheck temperature control package are 3-stage with binary  
control that provides 7 steps of heating. For example, a 35 kW heater with three stages will be  
composed of 5, 10, and 20 kW stages. The stages essentially ‘mix and match’ to provide heat  
output from 5 kW to 35 kW, in 5 kW increments.  
FIGURE 11  
Electric Post-Heater  
The post-heater is not single  
point wired to the ERH control  
center (requires separate  
power). The post-heater and the  
ERH each have their own  
disconnect located in the UNIT  
control center.  
If required, access to the post-  
heater control panel is through  
the exhaust filter door.  
Electric Preheater  
The preheater is single point wired to the ERH control  
center (does not require separate power). Access to the  
preheater control panel is through the supply filter door.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
FROST CONTROL APPLICATION/OPERATION  
When outdoor air temperatures are extremely cold, moisture condensation and frosting on the energy recovery  
wheel is possible. Frost control is an optional feature that will prevent wheel frosting. Two options are available:  
1) Timed Exhaust frost control and  
2) Preheat frost control  
Timed exhaust frost control includes a thermostat (with  
probe) mounted in the supply air inlet compartment (see  
FIGURE 13, page 10) and a timer (Figure 12) mounted in the  
ERH control center. The thermostat will turn on the timed  
exhaust frost control feature at a predetermined field  
adjustable outdoor air temperature (referred to as the Frost  
Threshold temperature). The typical temperature setting  
TABLE 6  
Indoor RH @ 70°F  
Frost Threshold Temp  
20%  
30%  
40%  
-10°F  
-5°F  
0°F  
corresponds to the indoor air relative humidity as shown in TABLE 6.  
Testing (refer to FIGURE 12)  
• Set the Timer Scale for T1 and T2 to 1 minute. Set  
the Timer Settings for T1 and T2 to 1.0. Set the dip  
switch to the down position.  
Turn the temperature sensor up as high as possible.  
The supply blower should cycle on for one minute,  
then turn off for one minute.  
A1  
B1  
15  
0.8 0.6  
1.0 0.4  
0.2  
Dip  
Switch  
0
• After testing, set the Timer Scale as follows: T1 = 10  
minutes, T2 = 1 hour  
T2  
1 MIN T2  
• Set the Timer Settings as follows: T1 = 0.5, T2 =  
0.5. The timer is now set for 5 minutes off and 30  
minutes on.  
Timer  
Scale  
1 MIN T1  
0.8 0.6  
1.0 0.4  
0.2  
0
Preheat frost control (see FIGURE 11, page 8) includes a  
thermostat (with probe) and an electric heater located in the  
supply air inlet compartment and an air pressure switch in the  
supply air outlet compartment. The thermostat should be set  
according to the Frost Threshold temperatures shown in TABLE 6.  
When the outdoor air temperature reaches the thermostat setting,  
the electric preheater will turn on and warm the air entering the energy  
wheel.  
T1  
16  
18  
A2  
FIGURE 12  
Testing  
Turn the thermostat as high as it will go. The heater should turn on.  
• If it doesn’t, either put the supply side doors on or temporarily jumper the  
air pressure switch to avoid nuisance tripping of the pressure switch.  
Remember to remove the jumper.  
DIRTY FILTER SWITCH SETUP  
This unit may be equipped with a dirty filter switch that functions on differential air pressures to close a relay  
when the unit filters are clogged and need cleaning. This switch has not been set at the factory due to external  
system losses that will affect the switch. This switch will need minor field adjustments after the unit has been  
installed with all ductwork complete. The dirty filter switch is mounted in the exhaust inlet compartment next to  
the electrical control center.  
To adjust the switch the unit must be running with all of the access doors in place, except for the compartment  
where the switch is located (exhaust inlet compartment). Remove the switch cover plate. The adjusting screw is  
located on the top of the switch. Open the filter compartment and place a sheet of plastic or cardboard over  
50% of the filter media. Replace the filter compartment door. Check to see if there is power at the alert signal  
leads (refer to electrical diagram). If there is no power, turn the adjustment screw on the dirty filter gage  
clockwise until you have power. Open the filter compartment and remove the obstructing material. Replace the  
door and check to make sure that you do not have power at the alert signal leads. The unit is now ready for  
operation.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
ECONOMIZER APPLICATION/OPERATION  
The energy recovery wheel may be de-energized for the purpose of providing economizer (free cooling)  
operation. This can be achieved with a signal from a Temperature or Enthalpy sensor mounted in the supply air  
inlet compartment (see FIGURE 13). This Primary sensor will de-energize the energy wheel when the outdoor air  
temperature (factory default is 65°F) or enthalpy (factory default is the ‘D’ setting) is below the field adjustable  
set point. An additional Override temperature sensor is also furnished in the supply air inlet compartment to  
deactivate economizer mode (see FIGURE 13). The Override (with field adjustable set point) is set at some  
temperature lower than the Primary sensor (factory default is 50°F). Effectively, the two sensors create a  
deadband where the energy recovery wheel will not operate and free cooling from outside can be brought into  
the building unconditioned.  
Testing (terminals referenced below are in the unit control center — see FIGURE 5, Item #7)  
Temperature sensor with Override  
Turn both Temperature and Override  
thermostats down as low as they go.  
The wheel should be rotating.  
FIGURE 13  
Turn the Temperature sensor up as  
high as it goes, and keep the Override  
sensor as low as it will go. The wheel  
should stop rotating.  
Turn both sensors as high as they will  
Enthalpy Sensor  
(Primary Sensor)  
go. The wheel should start rotating.  
• Set the Temperature sensor to the  
desired temperature for economizer  
Timed Exhaust  
Override  
Frost Control  
operation to begin. Set the Override  
sensor to the desired temperature for  
economizer operation to end (factory  
default is 65°F and 50°F, respectively).  
Probes  
Enthalpy sensor with Override  
• A factory-installed 620 ohm resistor is  
connected across terminals SR and +.  
The Override sensor should be turned  
down below current temperature in unit. Turn the unit on; LED on the sensor should be off. Check  
continuity across terminals 2 and 3, there should not be continuity. There should be continuity  
between terminals 1 and 2.  
• Disconnect the 620 ohm resistor from terminals SR and +. LED should turn on. There should be  
continuity between terminals 2 and 3. There should not be continuity between terminals 1 and 2.  
Turn the Override sensor above current temperature in unit. There should be continuity between  
terminals 3 and 6. Set the Override sensor to the desired temperature for economizer operation to end  
(factory default is 50°F).  
• Reconnect the factory-installed jumper.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START UP CHECKS  
**WARNING**  
DO NOT OPERATE ENERGY RECOVERY VENTILATOR WITHOUT THE FILTERS AND BIRDSCREENS INSTALLED.  
THEY PREVENT THE ENTRY OF FOREIGN OBJECTS SUCH AS LEAVES, BIRDS, ETC.  
DO NOT REMOVE ACCESS PANELS OR OTHER UNIT COMPONENTS WHILE STANDING ON A LADDER OR OTHER  
UNSTEADY BASE. ACCESS PANELS AND UNIT COMPONENTS ARE HEAVY AND SERIOUS INJURY MAY OCCUR.  
CAUTION: See **WARNING** on page 1 and above  
For proper unit function and safety, follow everything in this start-up procedure in the order presented. This to  
be done after the electrical and gas connections are complete.  
Pre-Start Check List  
1. Disconnect and lock-out all power switches to fan.  
2. Check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and  
accessories for tightness.  
3. Rotate the fan wheel by hand and assure no parts are rubbing.  
4. Check the V-belt drive for proper alignment and tension.  
Special Tools Required  
• Voltage meter  
• Incline manometer or equivalent  
Tachometer  
• Thermometer  
• Amperage meter  
GENERAL  
Check all fasteners and set screws for tightness. This is especially important  
for bearings and fan wheels. Also, if dampers are not motorized, check that  
they open and close without binding.  
n
o
i
t
Airflow  
a
t
o
R
FAN WHEEL ROTATION  
Hand rotate the blower to ensure that the wheel is not rubbing against the  
scroll. If the blower is rotating in the wrong direction, the unit will move some  
air but not perform properly.  
FIGURE 14  
To check the rotation, open the blower access panels, which are labeled either  
supply or exhaust, and run the blower momentarily to determine the rotation.  
Rotation should be in the same direction as airflow at the outlet (See FIGURES  
14 & 15). Check for unusual noise, vibration or overheating of bearings. Refer to  
the “Trouble Shooting” section of this manual if a problem develops.  
To reverse the rotation, turn the power off and use the following procedure:  
• For single phase units, rewire the motor per the instructions on the  
motor.  
FIGURE 15  
• For three phase units, interchange any two power leads. (this can be  
done at the motor starter).  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Check pulleys and belts for proper alignment to avoid unnecessary  
belt wear, noise, vibration and power loss. Motor and drive shafts  
must be parallel and pulleys in line (see FIGURE 16).  
FAN RPM  
The adjustable motor pulley is preset at the factory to the  
customer specified RPM. Fan speed can be increased or  
decreased by adjusting the pitch diameter of the motor pulley.  
Multi-groove variable pitch pulleys must be adjusted an equal  
number of turns open or closed. Any increase in fan speed  
represents a substantial increase in load on the motor. Always  
check the motor amperage reading and compare it to the  
amperage rating shown on the motor nameplate when changing  
fan RPM. Access these components through the labeled access  
panels.  
WRONG  
WRONG  
All access doors must be installed except the control center door.  
To measure the fan rpm, the blower door will need to be removed.  
Minimize measurement time because the motor may overamp with  
the door removed. Do not operate units with access doors/panels  
open or without proper ductwork in place as the motors will  
overload.  
WRONG  
CORRECT  
FIGURE 16  
ENERGY RECOVERY WHEEL  
CAUTION: See **WARNING** on page 1 and 11  
For the ERH-20 and ERH-45, open the access door marked  
"Energy Wheel Cassette Access". UNPLUG the wheel drive  
motor and remove the metal spacer. Then pull the cassette  
out halfway as seen in FIGURE 17.  
Note: For the ERH-55 and ERH-90, the energy recovery  
wheel does not slide out due to its size and weight. There is  
ample room inside the unit to perform energy recovery wheel  
servicing.  
Turn the energy recovery wheel by hand to verify free  
operation. Check that the air seals, located around the  
outside of the wheel and across the center (both sides of  
wheel), are secure and in good condition. Replace cassette  
into unit, plug in wheel drive, replace access door and apply  
power. Observe that the standard and high flow wheel  
rotates freely at about 60 RPM.  
FIGURE 17  
If wheel does not rotate or rotates too slowly, remove the  
cassette (following the instruction on page 16). Air seals, which are too tight, will prevent proper rotation of the  
energy recovery wheel. Recheck the air seals for tightness. Air seal clearance may be checked by placing a  
sheet of paper, to act as a feeler gauge, against the wheel face. To adjust the air seals, loosen all eight seal  
retaining screws. These screws are located on the bearing support that spans the length of the cassette  
through the wheel center. Tighten the screws so the air seals tug slightly on the sheet of paper.  
COILS  
Leak test thermal system to insure tight connections.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE MAINTENANCE  
CAUTION: See **WARNING** on Page 1 and 11  
Once the unit has been put into operation, a periodic maintenance program should be set up to preserve the  
reliability and performance. Items to be included in this program are:  
• BELTS  
• MOTORS  
• WHEEL AND FASTENERS  
• VIBRATION  
• FILTER MAINTENANCE  
• COIL MAINTENANCE  
• ENERGY WHEEL CASSETTE  
FAN BELTS  
Belt Span  
Belts tend to stretch after a period of time. They should be  
periodically checked for tension and wear. When replacing  
belts, use the same type as supplied with the unit.  
Replacement of belts should be accomplished by loosening  
the motor slide plate so the belts may be removed by hand.  
Do not force belts on or off as this may cause breakage of  
cords and lead to premature belt failure.  
Belt tension should be adjusted to allow 1/64 in. of belt  
deflection per 1 in. of belt span. For example, a 16 in. belt  
span should have 16/64 in. or 1/4 in. of deflection with  
moderate thumb pressure at mid-point between the pulleys  
(FIGURE 18).  
Belt Span  
Deflection =  
64  
FIGURE 18  
MOTORS  
Motor maintenance is generally limited to cleaning and lubrication (where applicable). Cleaning should be  
limited to exterior surfaces only. Removing dust and grease build-up on the motor housing assures proper  
motor cooling. Use caution and do not allow water or solvents to enter the motor or bearings. Under no  
circumstances should motors or bearings be sprayed with steam, water or solvents.  
Greasing of motors is intended only when fittings are provided. Many fractional horsepower motors are  
permanently lubricated for life and require no further lubrication. Motors supplied with grease fittings should  
be greased in accordance with the manufacturer’s recommendations.  
WHEEL AND FASTENERS  
Wheels require very little attention when moving clean air. Occasionally oil and dust may accumulate on the  
wheel causing imbalance. When this occurs the wheel and housing should be cleaned to assure smooth and  
safe operation. Inspect fan impeller and housing for fatigue, corrosion or wear.  
Routinely check all fasteners, set screws and locking collars on the fan, bearings, drive, motor base and  
accessories for tightness. A proper maintenance program will help preserve the performance and reliability  
designed into the fan.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VIBRATION  
Excessive vibration maybe experienced during initial start-up. Left unchecked, excessive vibration can cause a  
multitude of problems, including structural and/or component failure. The most common sources of vibration  
are listed below.  
Many of these conditions can be discovered by careful observation.  
1. Wheel Unbalance  
Refer to the troubleshooting section of this manual for corrective actions.  
2. Drive Pulley Misalignment  
If observation cannot locate the source of vibration, a qualified  
technician using vibration analysis equipment should be consulted. If the  
problem is wheel unbalance, in-place balancing can be done providing  
there is access to the fan wheel.  
3. Incorrect Belt Tension  
4. Bearing Misalignment  
5. Mechanical Looseness  
6. Faulty Belts  
7. Drive Component Unbalance  
8. Poor Inlet/Outlet Conditions  
9. Foundation Stiffness  
Generally, fan vibration and noise are transmitted to other parts of the  
building by the ductwork. To eliminate this undesirable effect, the use of  
heavy canvas connectors is recommended.  
EXTERNAL FILTER MAINTENANCE  
Aluminum mesh 2 in. filters are located in the  
supply weatherhood (if the weatherhood option  
was purchased). Filters should be checked and  
cleaned on a regular basis for best efficiency. The  
frequency of cleaning depends upon the  
cleanliness of the incoming air.  
FIGURE 19  
To remove these filters, remove bottom bolt in the  
access door on the side of the weatherhood. Slide  
the access door up and then pull out. Then, slide  
the filters out (see FIGURE 19).  
Clean filters by rinsing with a mild detergent in  
warm water. After the filters are dry, an adhesive  
spray available at most filter distributors may be  
applied to increase filter efficiency.  
TABLE 7  
Internal  
Quantity  
Filter Size  
Model  
INTERNAL FILTER MAINTENANCE  
Opening the access doors labeled as “Filter  
Access” provides access to the pleated 30%  
filters (if the filter option was purchased). These  
filters should be checked regularly, cleaned or  
replaced as needed. See TABLE 7 for pleated filter  
size and quantity for each unit.  
ERH-20  
ERH-45  
ERH-55  
ERH-90  
20 x 20  
20 x 25  
16 x 25  
20 x 20  
2
3
6
8
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WATER COIL MAINTENANCE  
CAUTION: See **WARNING** on Page 1 and 11  
FILTERS  
Filters upstream of the coil should be checked regularly. If the filters are dirty, they should be cleaned or  
replaced. It is important that the coils stay clean to maintain desired airflow. See page 14 for more information  
on filter maintenance.  
COIL MAINTENANCE  
1. Coils must be clean to obtain maximum performance. Check once a year under normal operating  
conditions and, if dirty, brush or vacuum clean. Soiled fins reduce the capacity of the coil, demand more  
energy from the fan, and create an environment for odor and bacteria to grow and spread through the  
conditioned zone. High pressure water (700 Psi or less) may be used to clean coils with fin thickness over  
0.0095 inches thick. TEST THE SPRAY PRESSURE over a small corner of the coil to determine if the fins  
will withstand the spray pressure.  
For coils with fragile fins or high fin density, foaming chemical sprays and washes are available. Many coil  
cleaners contain harsh chemicals, so they must be used with caution by qualified personnel only. Care  
must be taken not to damage the coils, including fins, while cleaning.  
CAUTION: Fin edges are sharp.  
**WARNING**  
BIOLOGICAL HAZARD. MAY CAUSE DISEASE. CLEANING SHOULD BE PERFORMED BY QUALIFIED PERSONNEL.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ROUTINE ENERGY RECOVERY WHEEL MAINTENANCE  
CAUTION: See **WARNING** on Page 1 and 11  
MAINTENANCE OF THE ENERGY RECOVERY WHEEL  
Annual inspection of the energy recovery wheel is recommended. Units ventilating smoking lounges and other  
non-clean air spaces should have energy recovery wheel inspections more often based upon need. Inspections  
for smoke ventilation applications are recommended bimonthly to quarterly until a regular schedule can be  
established.  
ACCESSING ENERGY RECOVERY WHEEL  
For the ERH-20 and ERH-45, open the access door marked "Energy Wheel Cassette Access" (FIGURE 20).  
UNPLUG the wheel drive motor and remove the metal spacer. Then pull the cassette out halfway (FIGURE 21).  
The energy recovery wheel cassettes for model ERH-55 and ERH-90 do not slide out due to their size and  
weight. Service to these energy wheel cassettes can be done through the Filter and Electrical Control Box  
access doors, or by entering the unit through the Exhaust Blower access door.  
**WARNING: Disconnect power to the unit before performing any type of service.**  
FIGURE 20  
FIGURE 21  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REMOVING THE ENERGY RECOVERY WHEEL SEGMENTS  
Model ERH-20, 45, 55, & 90  
Bracket Segment Retainer  
Steel retainers are located on the  
inside of the wheel rim (FIGURE 22).  
Push the retainer toward center of  
wheel, then lift up and away to  
Lift Away  
From Segment  
release segments (FIGURE 23).  
Catch-  
Segment Retainer  
Inside of Wheel Rim  
Spoke  
Push Toward Center  
FIGURE 22  
IMPORTANT! PLACE RETAINERS BACK IN THE ORIGINAL  
POSITION BEFORE ROTATING THE ENERGY  
RECOVERY WHEEL. OTHERWISE DAMAGE TO  
RETAINER WILL OCCUR.  
FIGURE 23  
CLEANING ENERGY RECOVERY WHEEL SEGMENTS  
If the wheel appears excessively dirty, it should be cleaned to ensure maximum operating efficiency. Only  
excessive buildup of foreign material needs to be removed. DISCOLORATION AND STAINING OF ENERGY  
RECOVERY WHEEL DOES NOT AFFECT ITS PERFORMANCE.  
Thoroughly spray wheel matrix with household cleaner such as Fantastic or equivalent. Gently rinse with warm  
water and using a soft brush remove any heavier accumulation. A detergent/water solution can also be used.  
Avoid aggressive organic solvents, such as acetone. The energy recovery wheel segments can be soaked in the  
above solution overnight for stubborn dirt or accumulation.  
After cleaning is complete, shake the excess water from the wheel or segments. Dry wheel or segments before  
placing them back into the cassette. Place wheel or segments back into cassette by reversing removal  
procedures.  
** DO NOT CLEAN ENERGY RECOVERY WHEEL SEGMENTS WITH WATER IN EXCESS OF 140°F  
** DO NOT DRY ENERGY RECOVERY WHEEL SEGMENTS IN AIR IN EXCESS OF 140°F.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS LIST  
7
3
8
6
1
5
2
9
7
4
10  
Model ERH  
(shown with indirect gas heater)  
1. Supply blower  
8. Electrical control box (standard features)  
- Single point power  
- Forward curved fan  
- Adjustable motor mount for belt tensioning  
- Adjustable sheaves for speed control  
- Disconnect interlocked with access door  
- Motor starters for the supply blower, exhaust  
blower and energy wheel motors.  
2. Vibrations isolators (quantity 4 per blower)  
- Neoprene  
- 24 Vac, control circuit with terminal strip  
9. Supply air tempering options  
- Electric heat  
3. Energy recovery wheel cassette  
- Hot water heat  
4. Removable energy recovery wheel segments  
- Indirect gas heat  
5. Optional supply weatherhood with 2 in. aluminum  
mesh filter  
10. Exhaust blower  
- Forward curved fan  
- Adjustable motor mount for belt tensioning  
- Adjustable sheaves for speed control  
6. Optional exhaust weatherhood with birdscreen  
7. Optional supply and exhaust air filter racks with 2  
in. pleated, 30% efficient filters  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble Shooting  
Symptom  
Possible Cause  
Corrective Action  
Blown fuse or open circuit  
breaker.  
Replace fuse or reset circuit breaker and check amps.  
Defective motor or capacitor.  
Motor starter overloaded.  
Electrical.  
Replace  
Blower Fails to  
Operate  
Reset starter and check amps.  
Check for On/Off switches. Check for correct supply voltage.  
Check for broken or loose belts. Tighten loose pulleys.  
Drive.  
Control power (24 Vac) wiring  
run is too long (resistance  
Shorten wiring run to mechanical room or install a relay  
which will turn unit on/off (C/F for relay information).  
should not exceed 0.75 ohms).  
Motor Starters  
“Chatter” or Do  
Not Pull In  
Incoming supply power is  
less than anticipated. Voltage  
supplied to starter coil must  
be within +10% / -15% of  
nominal voltage stated on  
the coil.  
Need to increase supply power or use a special control  
transformer which is sized for the actual supply power.  
Cfm too high.  
Check cfm and adjust drives if needed.  
Static pressures are higher or  
lower than design.  
If higher, ductwork should be improved.  
If lower, fan rpm should be lower.  
Blower rotation is incorrect.  
Motor voltage incorrect.  
Motor horsepower too low.  
Check rotation and reverse if necessary.  
Motor Over Amps  
Check motor nameplate versus supplied voltage.  
See specifications and catalog for fan curves to determine if  
horsepower is sufficient.  
Shorted windings in motor.  
Unit damper not fully open.  
Replace motor.  
Adjust damper linkage or replace damper motor.  
System static pressure too high Improve ductwork to eliminate losses using good duct  
practices.  
Blower speed too low.  
Check for correct drives and rpm with catalog data.  
For 3-phase see Fan Wheel Rotation on page 11.  
Fan wheels are operating  
backwards.  
Low Airflow (cfm)  
Dirty filter or energy wheel.  
Leaks in ductwork.  
Follow cleaning procedures on pages 14 and 17.  
Repair.  
Elbows or other obstructions  
may be obstructing fan outlet.  
Correct or improve ductwork.  
Belt slippage.  
Adjust belt tension.  
Blower fan speed too high.  
Filter(s) not in place.  
Check for correct fan rpm. Decrease fan speed if necessary.  
Install filters.  
High Airflow (cfm)  
Insufficient static pressure (Ps)  
(airflow resistance).  
Induce Ps into system ductwork. Make sure grilles and  
access doors are installed. Decrease fan speed if necessary.  
* Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Trouble Shooting  
Symptom  
Possible Cause  
Corrective Action  
One or Both  
Blowers Turn Off  
Intermittently and  
Back on After  
Blower fan motor overloads are Decrease fan speed.  
tripping and auto-resetting.  
Exhaust Only frost control  
sensors are tripping.  
Adjust frost temperature sensor set point as needed.  
About 2 Minutes  
Air seals are too tight.  
See Energy Recovery Wheel on page 12  
“Economizer” sensors are  
operating.  
Adjust temperature or enthalpy set points as needed.  
Energy Wheel  
Does NOT Turn  
No power to wheel motor.  
Make sure wheel drive is plugged in. Verify power is  
available.  
Wheel drive belt  
Check for loose or broken belts. Replace belts (consult  
factory).  
Wheel motor overloads are  
tripping, due to rubbing  
between wheel and air seals.  
Recheck air seals, make sure they are not too tight. See  
Energy Recovery Wheel on page 12.  
Energy Wheel  
Runs Intermittently  
Fan wheel rubbing on inlet  
Adjust wheel and/or inlet cone. Tighten wheel hub or bearing  
collars on shaft.  
Bearings.  
Replace defective bearings (s). Lubricate bearings. Tighten  
collars and fasteners.  
Wheel out of balance.  
Replace or rebalance.  
Loose wheel on shaft.  
Tighten wheel setscrew.  
Tighten sheave setscrew.  
Loose motor or blower sheave.  
Belts too loose.  
Belts too tight.  
Adjust belt tension after 24 hours of operation.  
Excessive Noise or  
Vibration  
Loosen to maintain a 3/8 inch deflection per foot of span  
between sheaves.  
Worn belt.  
Replace.  
Motor base or blower loose.  
Build up of material on wheel.  
Bearing and drive misaligned.  
Tighten mounting bolts.  
Clean wheel and housing.  
Realign.  
Noise being transmitted by  
duct.  
Make sure duct work is supported properly. Make sure duct  
work metal thickness is sized for proper stiffness. Check duct  
size at discharge to ensure that air velocities are not too high.  
* Always provide the unit model and serial number when requesting parts or service information. * Always check motor amps and compare to nameplate rating.  
Warranty  
Greenheck warrants this equipment to be free from defects in material and workmanship for a period of one year from  
the purchase date. The energy recovery wheel is warranted to be free from defects in material and workmanship for a  
period of five years from the purchase date. Any units or parts which prove defective during the warranty period will be  
replaced at our option when returned to our factory, transportation prepaid.  
Motors are warranted by the motor manufacturer for a period of one year. Should motors furnished by Greenheck prove  
defective during this period, they should be returned to the nearest authorized motor service station. Greenheck will not  
be responsible for any removal or installation costs.  
Due to continuing product development Greenheck has the right to change specifications without notice  
GREENHECK  
Copyright © 2002 Greenheck Fan Corp.  
IOM ERH FS  
Rev. 1 January 2002  
P.O. BOX 410 SCHOFIELD, WISCONSIN 54476-0410  
PH. 715-359-6171  
®
Download from Www.Somanuals.com. All Manuals Search And Download.  

Graco Cooktop ISPS002AC User Manual
Honeywell Network Card UDC2500 User Manual
HP Hewlett Packard Air Conditioner 3563A User Manual
Hunter Fan Outdoor Ceiling Fan 27186 User Manual
Husqvarna Chainsaw 1151338 95 User Manual
Husqvarna Chainsaw SMB 70 SMB 70 E User Manual
Husqvarna Trimmer 325HS75X User Manual
IBM Computer Monitor 8183 User Manual
IBM Personal Computer 4190 User Manual
Iiyama Computer Monitor B1780SD B1 User Manual