CPC CommerCial
7½- to 12½-ton three-phase
paCkaged air Conditioners
Cooling CapaCity: 90,000 — 118,000 BtU/h
up to 11.5 EER
Standard Features
• R-410A chlorine-free refrigerant
• High-efficiency scroll compressor
• Copper tube / aluminum fin coils
• Contactor with lugs
• High- and low-pressure switches
• High-capacity, steel-cased filter dryer
• Heater kits with single-point entry
• 24-volt terminal strip
• Convertible
• Easy to service
• Built-in filter rack with standard 2”filters
• Bottom utility entry
• AHRI Certified; ETL Listed
Contents
Nomenclature..................................................................................................2
Product Specifications................................................................................3
Airflow Data.......................................................................................................7
Heat Kit Electrical Data ...........................................................................11
Expanded Cooling Data..........................................................................16
Dimensions.....................................................................................................26
Wiring Diagrams .........................................................................................30
Accessories......................................................................................................34
Cabinet Features
• Heavy-gauge, galvanized-steel cabinet with
UV-resistant powder-paint finish
• Full Perimeter Rail
SS-CPC90-150
6/11
Supersedes 3/11
Download from Www.Somanuals.com. All Manuals Search And Download.
prodUCt speCifiCations
prodUCt speCifiCations — 7½ tons
A Models
B Models
CPC090
XXX3BXXX
CPC090
XXX4BXXX
CPC090
XXX3BXXX
CPC090
XXX4BXXX
CPC090
XXX7BXXX
Cooling Capacity
Total BTU/h
90,000
65,700
90,000
65,700
90,000
64,000
90,000
64,000
90,000
64,000
Sensible BTU/h
EER / IEER
11.5 / 11.5
82.0
11.5 / 11.5
82.0
11.5 / 11.5
82.0
11.5 / 11.5
82.0
11.5 / 11.5
82.0
Decibels
AHRI Reference #s
3000986
3000986
3620223
3620223
3620223
Evaporator Motor / Coil
Motor Type
Belt Drive
3,000
Belt Drive
3,000
Belt Drive
3,000
Belt Drive
3,000
Belt Drive
3,000
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower / RPM
Piston Size (Cooling)
Filter Size (Qty)
7.8
3.9
5.0
2.5
2.3
2.0 / 1725
0.076
2.0 / 1725
0.076
1.5 / 1745
0.078
1.5 / 1745
0.078
1.5 / 1725
0.078
(4) 16”x24”x2”
¾”
(4) 16”x24”x2”
¾”
(4) 16”x20”x2”
¾”
(4) 16”x20”x2”
¾”
(4) 16”x20”x2”
¾”
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1 & #2
Evaporator Coil Face Area (ſt²)
Rows Deep / Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave / Blower Sheave
Belt
215 oz.
10.2
215 oz.
10.2
175 oz.
8.9
175 oz.
8.9
175 oz.
8.9
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
1 (15” x 12”)
VL40 / AK74
AX51
1 (15” x 12”)
VL40 / AK74
AX51
1 (15” x 12”)
VL40 / AK74
AX51
1 (15” x 12”)
VL40 / AK74
AX51
1 (15” x 12”)
VL40 / AK74
AX51
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
2
2
2
2
2
¼ - 1090
22 / 4
7,600
32.4
¼ - 890
22 / 4
7,600
32.4
¼ - 1075
22 / 4
7,600
26.5
¼ - 890
22 / 4
7,600
26.5
¼ - 1,075
22 / 4
7,600
26.5
Rows Deep / Fins per Inch
Compressor
2 / 20
2 / 20
2 / 22
2 / 22
2 / 22
Quanꢀty / Type
2 / Scroll
1
2 / Scroll
1
2 / Scroll
1
2 / Scroll
1
2 / Scroll
1
Stage
Electrical Data
Voltage-Phase-Frequency
Quanꢀty of Compressors
Compressor RLA / LRA
Max External Staꢀc
Outdoor Fan HP / RLA
Total Unit Amps
208/230-3-60
460-3-60
2
208/230-3-60
460-3-60
2
575-3-60
2
2
13.1 / 83.1
1.5”
2
13.1 / 83.1
1.0”
6.1 / 41.0
1.5”
6.1 / 41.0
1.0”
4.4 / 33.0
1.0”
(2) ¼ / 1.4
36.9
(2) ¼ / 0.8
17.7
(2) ¼ / 1.4
34.0
(2) ¼ / 0.8
16.3
(2) ¼ / 0.6
12.3
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
40
19
37.3
17.8
13.4
50
25
50
20
15
Locaꢀng
Dimple
Locaꢀng
Dimple
Locaꢀng
Dimple
Locaꢀng
Dimple
Locaꢀng
Dimple
1110
1150
1110
1150
975
975
975
1000
1000
1000
¹ Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
3
prodUCt speCifiCations
prodUCt speCifiCations — 8½ tons
CPC102
XXX3BXXX
CPC102
XXX4BXXX
CPC102
XXX7BXXX
Cooling Capacity
Total, BTU/h
102,000
70,380
102,000
70,380
102,000
70,380
Sensible BTU/h
EER / IEER
11.3 / 11.2
83
11.3 / 11.2
83
11.3 / 11.2
83
Decibels
ARI Reference #s
3620220
3620220
3620220
Evapoartor Motor / Coil
Motor Type
Belt Drive
3,400
Belt Drive
3,400
Belt Drive
3,400
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
7.8
3.9
2.3
1725
1725
1725
Piston Size (Cooling)
Filter Size (Qty)
0.08
0.08
0.08
(4) 16” x 20” x 2”
3/4"
(4) 16” x 20” x 2”
3/4"
(4) 16” x 20” x 2”
3/4"
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1 & #2
Evaporator Coil Face Area (ſt2)
Rows Deep / Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave / Blower Sheave
Belt
180 oz.
8.9
180 oz.
8.9
180 oz.
8.9
4 / 16
4 / 16
4 / 16
1 (15" x 12")
VL40 / AK74
AX51
1 (15" x 12")
VL40 / AK74
AX51
1 (15" x 12")
VL40 / AK74
AX51
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
2
1/4" - 1,090
22 / 4
2
2
1/4" - 1,075
22 / 4
1/4" - 890
22 / 4
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ſt2)
7,600
7,600
7,600
13.25
13.25
13.25
Rows Deep / Fins per Inch
Compressor
2 / 22
2 / 22
2 / 22
Quanꢀty / Type
2 / Scroll
1
2 / Scroll
1
2 / Scroll
1
Stage
Electrical Data / Static
Voltage / Phase / Frequency
Quanꢀty of Compressors
Compressor RLA / LRA ea.
Standard Max Staꢀc
Outdoor Fan FLA ea.
Total Unit Amps
230 / 3 / 60
460 / 3 / 60
575 / 3 / 60
2
14.5 / 98
1"
2
6.3 / 55
1
2
6.0 / 41
1
1.4
0.8
0.6
39.6
43.2
50
18.1
19.7
25
15.5
17
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
20
Locaꢀng
Dimple
Locaꢀng
Dimple
Locaꢀng
Dimple
975
975
975
1000
1000
1000
¹
²
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
prodUCt speCifiCations — 10 tons
CPC120
XXX3BXXX
CPC120
XXX4BXXX
CPC120
XXX7BXXX
Cooling Capacity
Total BTU/h
118,000
87,300
118,000
87,300
118,000
87,300
Sensible BTU/h
EER / IEER
11.5 / 11.2
83.0
11.5 / 11.2
83.0
11.5 / 11.2
83.0
Decibels
ARI Reference #s
3023833
3023833
3023833
Evaporator Motor / Coil
Motor Type
Belt Drive
4,000
Belt Drive
4,000
Belt Drive
4,000
Indoor Nominal CFM
Indoor motor FLA (Cooling)
Horsepower - RPM
7.8
3.9
2.7
2.0/1725
0.086
2.0/1725
0.086
2.0/1725
0.086
Piston Size (Cooling)
Filter Size (Qty)
(4) 16” x 24” x 2”
¾”
(4) 16” x 24” x 2”
¾”
(4) 16” x 24” x 2”
¾”
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1 & #2
Evaporator Coil Face Area (ſt²)
Rows Deep / Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave / Blower Sheave
Belt
220 oz.
10.2
220 oz.
10.2
220 oz.
10.2
4 / 14
4 / 14
4 / 14
(1) 15” x 15”
VL40 / AK74
AX51
(1) 15” x 15”
VL40 / AK74
AX51
(1) 15” x 15”
VL40 / AK74
AX51
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
2
⅓ - 1,075
22 / 3
2
⅓ - 1,075
22 / 3
2
⅓ - 1,075
22 / 3
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
7,200
7,200
7,200
32.4
32.4
32.4
Rows Deep - Fins per Inch
Compressor
2/2 rows - 22 fpi
2/2 rows - 22 fpi
2/2 rows - 22 fpi
Quanꢀty / Type
2 / Scroll
1
2 / Scroll
1
2 / Scroll
1
Stage
Electrical Data
Voltage/Phase/ Frequency
Quanꢀty of Compressors
Compressor RLA / LRA ea.
Standard Max Staꢀc
Outdoor Fan RLA ea.
Total Unit Amps
208-230/3/60
460/3/60
2
575/3/60
2
2
16/110.0
2.0”
7.8/52.0
2.0”
1.20
22
5.7/38.9
2.0”
0.89
16
2.40
45
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
49
24
17
60.0
30
20
Locaꢀng
Dimple
Locaꢀng
Dimple
Locaꢀng
Dimple
1135
1175
1135
1175
1135
1175
¹
²
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
5
prodUCt speCifiCations
prodUCt speCifiCations — 12½ tons
CPC150XXX
3BXXX
CPC150XXX
4BXXX
CPC150XXX
7BXXX
Cooling Capacity
Total, BTU/h
146,000
102,200
11.0 / 11.2
83
146,000
102,200
11.0 / 11.2
83
146,000
102,200
11.0 / 11.2
83
Sensible BTU/h
EER / IPLV
Decibels
ARI Reference #s
3542680
3542680
3542680
Evapoartor Motor / Coil
Motor Type
Belt Drive
5,000
Belt Drive
5,000
Belt Drive
5,000
Indoor Nominal CFM
Indoor Motor FLA (Cooling)
Horsepower - RPM
Piston Size (Cooling)
Filter Size
9.4
4.7
4.2
3.0 - 1,725
0.096
3.0 - 1,725
0.096
3.0 - 1,725
0.096
(4) 20" x 25" x 2"
¾"
(4) 20" x 25" x 2"
¾"
(4) 20" x 25" x 2"
¾"
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1 & #2
Evaporator Coil Face Area (ſt2)
Rows Deep / Fins per Inch
Condenser Fan / Coil
Quanꢀty of condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ſt2)
285 oz.
14.7
285 oz.
14.7
285 oz.
14.7
4 / 15
4 / 15
4 / 15
2
⅓ - 1,075
22/3
2
⅓ - 1,075
22/3
2
⅓ - 1,075
22/3
7,200
7,200
7,200
35.3
35.3
35.3
Rows Deep / Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave / Blower Sheave
Belt
2/3 rows 15 fpi
2/3 rows 15 fpi
2/3 rows 15 fpi
(1) 15" x 15"
VL40 / AK66
AX49
(1) 15" x 15"
VL40 / AK66
AX49
(1) 15" x 15"
VL40 / AK66
AX49
Compressor
Quanꢀty / Type
1 / Scroll
Single
1 / Scroll
Single
1 / Scroll
Single
Stage
Compressor RLA / LRA ea.
Electrical Data / Static
Voltage / Phase / Frequency
Outdoor Fan FLA ea.
Total Unit Amps
Min. Circuit Ampacity1
Max. Overcurrent Protecꢀon (amps)2
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
22.4 / 149
10.6 / 75
7.7 / 54
208-230/3/60
460/3/60
575/3/60
0.9
2.4
59
65
80
1.2
28
31
40
21.4
23
30
Locaꢀng
Dimple
Locaꢀng
Dimple
Locaꢀng
Dimple
1275
1300
1275
1300
1275
1300
¹
²
Wire size should be determined in accordance with National Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
airflow data — 7½ tons
Standard Belt Drive — Down Shot
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1
0.3
0.5
0.7
0.9
1.1
3617 704
1.15 3179 704
0.94 2606 710
0.75
1.07 3293 653
0.88 2757 656
0.71
0.84
0.66
3541 749
1.23 3049 754
1.01 2474 754
0.82
3447 798
1.33 2950 798
1.11 2408 804
3400 848
1.41 2871 848
1.23
3303 890
2838 897
High-Static Belt Drive — Down Shot (for A Models only)
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.9
1.1
1.3
1.5
1.7
1.9
2.1
3401 909
1.51
1.3
3428 965
3012 971
1.71 2943 915
3471 1015
1.9
1.5
2423 920
1.12
DO NOT
OPERATE
3722 1063 2.25 3041 1023 1.67 2503 976
3359 1075 2.04 2540 1031 1.5
3381 1119 2.22 2890 1080 1.78
1.31
3089 1129 2.04
Standard Belt Drive — Horizontal
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1
0.3
0.5
0.7
0.9
1.1
3625 701
1.11 3177 703
0.94 2608 709
0.73
1.08 3309 660
0.88 2796 663
0.68 2225 665
0.86
0.68
0.53
3815 797
1.52 3405 803
1.29 2968 805
1.44 3468 747
1.23 3053 753
1.02 2423 758
0.8
3780 841
3327 847
3687 885
3236 891
2713 896
1.6
1.39 2850 852
1.17
1.1
2352 807
High-Static Belt Drive — Horizontal (for A Models only)
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.9
1.1
1.3
1.5
1.7
1.9
2.1
3447 902
1.65 3006 908
1.44
1.54
1.31
3398 956
3486 1008 1.87 2960 962
DO NOT
OPERATE
3514 1057 2.07 2949 1019 1.62
3388 1103 2.18 3036 1069 1.84
2959 1114 2.0
2527 1124 1.86
Notes :
Assume dry coil with filter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
7
prodUCt speCifiCations
airflow data — 8½ tons
Standard Belt Drive — Down Shot
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1
0.3
0.5
0.7
0.9
1.1
3467 701
1.12 3029 701
0.91 2456 707
1.04 3143 650
0.85 2607 653
0.68
0.81
0.63
3391 746
1.20 2899 751
0.98
3297 795
1.30 2800 795
1.08
3250 845
1.38 2721 845
1.20
3153 887
2688 894
High-Static Belt-Drive — Down Shot
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.9
1.1
1.3
1.5
1.7
1.9
2.1
3251 906
1.68 2793 912
1.47
1.48
1.27
3278 962
3321 1012 1.87 2862 968
3572 1060 2.22 2891 1020 1.64
3209 1072 2.01
3231 1116 2.19 2740 1077 1.75
3256 1156 2.31 2939 1126 2.01
Standard Belt Drive — Horizontal
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.1
0.3
0.5
0.7
0.9
1.1
3475 698
1.08 3027 700
0.91 2458 706
1.05 3159 657
0.85 2646 660
0.65
0.83
0.65
3665 794
1.49 3255 800
1.26 2818 802
1.07
1.41 3318 744
3630 838
1.57 3177 844
1.36 2700 849
1.14
1.2
2903 750
3537 882
3086 888
2563 893
0.99
High-Static Belt-Drive — Horizontal
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.9
1.1
1.3
1.5
1.7
1.9
3297 899
1.62 2856 905
1.41
1.51
1.28
3248 953
3336 1005 1.84 2810 959
3364 1054 2.04 2799 1016 1.59
3238 1100 2.15 2886 1066 1.81
3188 1146 2.23 2809 1111 1.97
Notes :
Assume dry coil with filter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
airflow data — 10 tons
Standard Belt-Drive — Down Shot
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.2
0.4
0.6
0.8
1
4632 781
1.85 4183 783
1.63 3717 786
1.41
1.76 4203 742
1.54 3733 748
1.31
1.41 3927 691
1.23 3512 693
1.17 3510 658
1
0.9
4488 825
2.02 4066 830
1.77 3622 835
1.55
4442 880
4001 885
3603 890
1.2
High-Static Belt-Drive — Down Shot
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.8
1
4435 940
2.22 4078 886
2.05 3539 892
1.71
1.82
1.52
4462 997
2.47 4103 945
1.2
1.4
1.6
1.8
2
4513 1054 2.75 4127 1003 2.26 3568 950
4126 1064 2.52 3597 1008 1.92
4438 1116 2.97 3759 1069 2.25
3956 1124 2.55
4050 1179 3.05 3473 1132 2.32
Standard Belt-Drive — Horizontal
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.2
0.4
0.6
0.8
1
4562 736
4200 736
1.58 4253 691
1.41 3735 691
1.18
1.29 3893 642
1.06 3322 648
1
4497 780
1.81 4221 784
1.68 3677 785
1.34
1.7
0.83
4467 824
2.06 4170 830
1.81 3498 835
1.49
1.55 3689 741
1.29
4564 873
4129 875
3558 879
1.2
High-Static Belt-Drive — Horizontal
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP
0.8
1
4602 884
2.44 4180 885
2.12 3642 896
1.8
2.13
1.89
1.58
4749 940
4251 945
3744 951
1.2
1.4
1.6
1.8
2
DO NOT
OPERATE
4443 1001
2.5
4587 1056 2.82 3971 1006 2.17
4760 1105 3.23 4071 1061 2.43 3342 1012 1.86
4364 1114 2.91 3579 1067 2.05
Notes :
Assume dry coil with filter in place; CFM correction for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applications that exceed the above could
require a larger motor. Minimum rated SCFM is 350 per ton.
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
9
prodUCt speCifiCations
airflow data — 12½ tons
Standard Belt Drive --- Down Shot
Turns Open
ESP
(" W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
5378
4750
4488
4019
BHP
2.35
1.97
1.81
1.55
CFM
4967
4583
4258
BHP
1.92
1.71
1.54
CFM
4710
4319
BHP
1.59
1.40
CFM
4512
4030
BHP
1.33
1.13
0.2
0.4
0.6
0.8
1.0
5514
5204
4830
4497
2.92
2.69
2.42
2.19
5349
4919
4649
4264
2.56
2.27
2.09
1.86
High-Static Belt Drive --- Down Shot
Turns Open
ESP
(" W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
5978
5656
5459
4844
4404
BHP
3.87
3.58
3.40
2.88
2.54
CFM
5691
5376
4950
4525
BHP
3.38
3.12
2.79
2.45
CFM
5324
4933
4441
BHP
2.81
2.52
2.18
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
5947
5708
5245
4894
4495
4142
4.16
3.93
3.48
3.17
2.83
2.55
5776
5465
5145
4805
4429
4.64
4.30
3.97
3.63
3.27
5510
5199
4871
4565
4233
4.07
3.74
3.41
3.13
2.85
Standard Belt Drive --- Horizontal
Turns Open
ESP
(" W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
5570
4902
4603
4393
BHP
2.27
1.88
1.72
1.61
CFM
4935
4637
4341
BHP
1.70
1.55
1.41
CFM
4584
4178
BHP
1.36
1.19
0.2
0.4
0.6
0.8
1.0
1.2
5871
5610
5391
5078
4521
3.20
3.00
2.83
2.59
2.20
5639
5358
5010
4676
4226
2.77
2.57
2.33
2.11
1.83
5307
5051
4799
4448
2.31
2.15
2.00
1.79
High-Static Belt Drive --- Horizontal
Turns Open
ESP
(" W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
5858
5502
5110
4793
4382
BHP
3.51
3.20
2.88
2.64
2.34
CFM
5538
5282
4869
4598
BHP
2.97
2.78
2.47
2.28
0.8
1.0
1.2
1.4
1.6
1.8
2.0
2.2
5894
5570
5312
4945
4504
3.85
3.55
3.33
3.01
2.66
5780
5501
5257
5020
4601
4222
4.04
3.77
3.54
3.32
2.96
2.65
5900
5514
5315
4906
4541
4.49
4.08
3.88
3.49
3.15
5860
5615
5529
4938
4.76
4.49
4.40
3.78
Notes
•
•
•
Assume dry coil with filter in place; CFM correcꢀon for wet coil = 3%
Any adjustment made to the blower should not cause the motor to draw more than the motor rated RLA. Applicaꢀon
that exceed the above could require a larger motor. Minimum rated SCFM is 350 per ton.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 7½ tons (a modles)
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC090XXX3BXXX
EHK3-16
40
50
48 / 55
87 / 100
121 / 139
50 / 60
90 / 100
125 / 150
15
30
43
3000 - 3375 CFM
3000 - 3375 CFM
3000 - 3375 CFM
EHK3-30
EHK3-45
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPC090XXX4BXXX
EHK4-16
19
27
50
70
25
30
50
70
15
30
43
3000 - 3375 CFM
3000 - 3375 CFM
3000 - 3375 CFM
EHK4-30
EHK4-45
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
CPC090XXX7BXXX
EHK7-16
14
22
41
57
15
25
45
60
15
30
43
---
---
---
EHK7-30
EHK7-45
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon device
kw CorreCtion faCtors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
1
230
220
210
208
Correction Factor
0.93
0.82
0.78
0.76
kW Correction Factor (for 480V Units)
Supply Voltage
460
440
430
0.8
Correction Factor
0.92
0.84
minimUm airflow for eleCtriC heat
For other voltage, use voltage² / 480²
Heater Size (kW)
Minimum CFM
3,000
15
30
43
kW Correction Factor (for 575V Units)
3,000
Supply Voltage
560
550
540
3,000
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
11
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 7½ tons (B modles)
Model and
Heat Kit Usage
MCA¹
at 240V
MOP² (amps)
at 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC090XXX3BXXX
EHK3-16
37
51
50
60
15
30
43
3000 - 3375 CFM
3000 - 3375 CFM
3000 - 3375 CFM
EHK3-30
97
100
150
EHK3-45
136
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPC090XXX4BXXX
EHK4-16
18
26
48
68
20
30
50
70
15
30
43
3000 - 3375 CFM
3000 - 3375 CFM
3000 - 3375 CFM
EHK4-30
EHK4-45
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Recommended
Airflow Range
CPC090XXX7BXXX
EHK7-16
13
22
41
57
15
25
45
60
15
30
43
3000 - 3375 CFM
3000 - 3375 CFM
3000 - 3375 CFM
EHK7-30
EHK7-45
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon device
kw CorreCtion faCtors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
1
230
220
210
208
Correction Factor
0.93
0.82
0.78
0.76
kW Correction Factor (for 480V Units)
Supply Voltage
460
440
430
0.8
Correction Factor
0.92
0.84
minimUm airflow for eleCtriC heat
For other voltage, use voltage² / 480²
Heater Size (kW)
Minimum CFM
3,000
kW Correction Factor (for 575V Units)
15
30
43
Supply Voltage
560
550
540
3,000
Correction Factor
0.95
0.91
0.88
3,000
Multiply rated kW by correction factor to get actual kW.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 8½ tons
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
CPC102XXX3BXXX
EHK3-16
43
55
50
60
15
30
43
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
EHK3-30
100
139
100
150
EHK3-45
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
CPC102XXX4BXXX
EHK4-16
20
27
50
70
25
30
50
70
15
30
43
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
EHK4-30
EHK4-45
Recommended
Airflow Range
(Downshot)
Recommended
Airflow Range
(Horizontal)
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
CPC102XXX7BXXX
EHK7-16
17
22
41
57
20
25
45
60
15
30
43
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
3400 - 3825 CFM
EHK7-30
EHK7-45
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon device
^ - EHK Heater Kits above require a three-phase power supply
kw CorreCtion faCtors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
1
230
220
210
208
Correction Factor
0.93
0.82
0.78
0.76
kW Correction Factor (for 480V Units)
Supply Voltage
460
440
430
0.8
Correction Factor
0.92
0.84
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
13
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 10 tons
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC120XXX3BXXX
49
60
EHK3-16
EHK3-30
EHK3-45
48 / 55
87 / 100
121 / 139
50 / 60
90 / 100
125 / 150
15
30
43
3500 - 4500 CFM
3500 - 4500 CFM
4000 - 4500 CFM
Model and
Heat Kit Usage
MCA¹
at 208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC120XXX3HXXX
EHK3-16
50
60
49 / 57
88 / 102
122 / 141
50 / 60
90 / 110
125 / 150
15
30
43
3500 - 4500 CFM
3500 - 4500 CFM
4000 - 4500 CFM
EHK3-30
EHK3-45
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW
at 480V
Recommended
Airflow Range
CPC120XXX4BXXX
EHK4-16
24
27
50
70
30
30
50
70
15
30
43
3500 - 4500 CFM
3500 - 4500 CFM
4000 - 4500 CFM
EHK4-30
EHK4-45
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW
at 575V
Model and
Heat Kit Usage
Recommended
Airflow Range
CPC0120XXX7BXXX
EHK7-16
17
22
41
57
20
25
45
60
15
30
43
3500 - 4500 CFM
3500 - 4500 CFM
4000 - 4500 CFM
EHK7-30
EHK7-45
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon device
kw CorreCtion faCtor
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
1
230
220
210
0.78
208
Correcꢀon Factor
0.93
0.82
0.76
kW Correction Factor for 480V Units
minimUm airflow for eleCtriC heat
Actual Voltage
460
440
430
0.8
Correcꢀon Factor
0.92
0.84
Min. CFM
Heater Size (kW)
Min. CFM
Horizontal
For other voltage use voltage² / 480²
Down-shot
15
30
43
4,000
4,000
4,000
4,000
4,000
4,000
kW Correction Factor for 575V Units
Supply Voltage
560
550
540
Correcꢀon Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW
14
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 12½ tons
Model and
Heat Kit Usage
MCA1 at
208 / 240V
MOP2 (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC150***3B***
65
65
80
80
EHK3-16
EHK3-30
EHK3-45
15
30
43
4000 - 5600
4300 - 5600
4500 - 5600
102
141
110
150
Model and
Heat Kit Usage
MCA1 at
208 / 240V
MOP2 (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC150***4B***
31
31
51
71
40
40
60
80
EHK4-16
EHK4-30
EHK4-45
15
30
43
4000 - 5600
4300 - 5600
4500 - 5600
Model and
Heat Kit Usage
MCA1 at
208 / 240V
MOP2 (amps)
at 208 / 240V
Actual kW
at 240V
Recommended
Airflow Range
CPC150***7B***
23
24
43
59
30
30
45
60
EHK7-16
EHK7-30
EHK7-45
15
30
43
4000 - 5600
4300 - 5600
4500 - 5600
¹
²
Minimum Circuit Ampacity (standard drive)
Maximum Overcurrent Protecꢀon device (standard drive)
kw CorreCtion faCtors
kW Correction Factor (for 1- & 3-Phase Units)
Supply Voltage
240
1
230
220
210
208
0.76
Correction Factor
0.93
0.82
0.78
kW Correction Factor (for 480V Units)
Supply Voltage
460
440
430
0.8
Correction Factor
0.92
0.84
For other voltage, use voltage² / 480²
kW Correction Factor (for 575V Units)
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Multiply rated kW by correction factor to get actual kW.
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
15
prodUCt speCifiCations
expanded Cooling data — 7½ tons (a models)
16
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
expanded Cooling data — 7½ tons (a models Cont.)
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
17
prodUCt speCifiCations
expanded Cooling data — 7½ tons (B models)
18
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
expanded Cooling data — 7½ tons (B models Cont.)
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
19
prodUCt speCifiCations
expanded Cooling data — 8½ tons
20
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
expanded Cooling data — 8½ tons (Cont.)
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
21
prodUCt speCifiCations
expanded Cooling data — 10 tons
22
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
expanded Cooling data — 10 tons (Cont.)
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
23
prodUCt speCifiCations
expanded Cooling data — 12½ tons
24
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
expanded Cooling data — 12½ tons (Cont.)
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
25
Product SPecificationS
dimenSionS
L
H
Dimensions
Model
Size
H
L
7½ to 10 Tons
12½ Tons
52⅞”
58⅞”
99⅛”
99⅛”
61¾”
12⅝”
5⅞”
5
28⅜”
7⅜”
7 3/8”
RETURN
36⅜”
13⅞”
”
SUPPLY
6½”
RETURN
6¼”
Horizontal Discharge
5
5⅜”
SUPPL
Y
7½”
7
Vertical Discharge (Bottom of Unit)
26
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
Product SPecificationS
unit clearanceS
Maintain an adequate clearance around the unit for safety, service, maintenance,
and proper unit operation. Leave a total clearance of 75”on the main control
panel side of the unit for possible removal of fan shaft, coil, electric heat, and
gas furnace. Leave a clearance of 48”on all other sides of the unit for possible
compressor removal or service access, and to ensure proper ventilation
and condenser airflow. Do not install the unit beneath any obstruct-
ion. Install the unit away from all building exhausts to inhibit
ingestion of exhaust air into the unit’s fresh-air intake.
48”
48”
36” Min.
75”
48”
electrical entrance locationS
Dimples Mark Drill Locaꢀons
11⅝”
High-Voltage Entrance
103/16”
Low-Voltage Entrance
3”
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
27
Product SPecificationS
roof curb inStallation — rigging
Provisions for forks have been included in the unit base frame. No other
fork locations are approved.
•
Unit must be lifted by the four lifting holes located at the base
frame corners.
•
•
Lifting cables should be attached to the unit with shackles.
The distance between the crane hook and the top of the unit must
not be less than 60”.
•
Two spreader bars must span over the unit to prevent damage to
the cabinet by the lift cables. Spreader bars must be of sufficient
length so that cables do not come in contact with the unit during
transport. Remove wood struts mounted beneath unit base frame
before setting unit on roof curb. These struts are intended to protect
unit base frame from fork lift damage. To remove the struts, extract
the sheet metal retainers and pull the struts through the base of the
unit. Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, duct-work
should be attached to the curb prior to installing the unit. Duct-work
dimensions are shown in Roof Curb Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions
for proper curb installation. Curbing must be
installed in compliance with the National
Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb.
While rigging the unit, the center of gravity
will cause the condenser end to be lower
than the supply air end.
Return
30”
Evaporator Coil
Compressor 1
Bring condenser end of unit into alignment
with the curb. With condenser end of the
unit resting on curb member and using curb
as a fulcrum, lower opposite end of the unit
until entire unit is seated on the curb. When
a rectangular cantilever curb is used, take
care to center the unit. Check for proper
alignment and orientation of supply and
return openings with duct.
Compressor 2
Supply
49”
Corner & Center-of-Gravity Locations
7½-Ton B Models
& 8½-Ton
Weights (lbs)
7½-Ton A Models
Weights (lbs)
10-Ton
12½-Ton
Unit Weights
Weight A
Weights (lbs) Weights (lbs)
280
280
260
245
240
225
1000
975
285
285
420
335
Weight B
Weight C
280
285
290
Weight D
280
285
230
Shipping Weight
Operaꢀng Weight
1150
1110
1175
1135
1300
1275
To assist in determining rigging requirements, unit weights are shown to the right.
Note: These weights are calculated without accessories installed.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
Product SPecificationS
roof curb inStallation (cont.)
Curb installations must comply with local codes and should follow the
established guidelines of the National Roofing Contractors Association.
Proper unit installation requires that the roof curb be firmly and permanently
attached to the roof structure. Check for adequate fastening method prior to
setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are shipped
unassembled. The installing contractor is responsible for field assembly,
squaring, leveling, and mounting on the roof structure. All required hardware
necessary for the assembly of the sheet metal curb is included in the curb
accessory package.
•
Determine sufficient structural support before locating and mounting the
curb and package unit.
•
Duct-work must be constructed using industry guidelines. The duct-work
must be placed into the roof curb before mounting the package unit. Our
full perimeter curbs include duct connection frames to be assembled with
the curb. Cantilevered-type curbs are not available from the factory.
•
Contractor furnishes curb insulation, cant strips,
flashing, and general roofing material.
3-d View
•
Support curbs on parallel sides with roof members.
To prevent damage to the unit, the roof members
cannot penetrate supply and return duct openings.
92¼
53¼
Note: The unit and curb accessories are designed to
allow vertical duct installation before unit placement.
Duct installation after unit placement is not
recommended.
15 x 31
Supply Opening
14
14 x 38
Return Opening
See the manual shipped with the roof curb for
assembly and installation instructions.
1
¾
14
1
toP View
Power Wiring
Thermostat
Wiring
Power and low-Voltage block locationS
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
29
prodUCt speCifiCations
wiring diagram — CpC090-120 (for models with serial nUmBers 0907 and Below)
30
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
wiring diagram — CpC090-120 (Cont.) (for models with serial nUmBers 0907 and Below)
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
High Voltage: Disconnect all power before servicing or installing this unit. Mulꢀple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
⚠ Warning
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
31
prodUCt speCifiCations
wiring diagram — CpC090-150
OR
SMOKE/FIRE DETECTOR
REPLACES JUMPER
BK
3
240
460
575
OR
BK
TB1
TR
BL
RD
BR
BL
2
208
1
C
RD
RD
T3
T2
YL
RD
L3
L2
BR
GR
S1
S2
G
R
EBTDR
NO
K1
K1
PK
BL
24V
C
RD
XFMR-R
XFMR-C
GR
PU
2
0
8
-
2
4
0
-
4
6
0
-
5
7
5
/
L1
T1
COM
BL
SEE
NOTE #2
BL
C
OR
RD
BK
CC2
NOTE #2 NC
M1 M2
SPEED
UP
PB
YL
P
O
W
E
R
S
U
P
P
L
BK
RD
BL
BL
OR
BK
BL
BK
OR
RD
T3
T2
YL
L3
L2
RD
BR
Y
BK
T1
YL
RD
L2
OR
BK
RCCF2
RD
BK
GND
BK
C
3
/
6
0
C
F
T1
L1
GR
L1
T1
L3
BK
RD
T3 T2
PU
BK
CC1
BR
YL
T3
PU
BR
C
BK
BK
T2 T3
YL
RD
T2 T1 RCCF1
BR
COMP2
CM2
BC
BL
PU
BK
BK
C
F
CM1
COMP1
OR
RD
BK
PU
YL
BK
SEE
NOTE 3
PLF 2
BL
PU
HPS1
LPS1
BK
GR
9
BL
BK
3
2
1
6
5
4
WH
PU
OR
8
7
WH
YL
YL
EM
BK
WH
T
H
E
R
M
O
S
T
PLF 1
Y1
YL
PU
RD
GR
WH
BR
BL
Y/Y2
R
G
W1
W2
C
RD
3
6
5
4
9
RD
PU
2
1
8
7
WH
BR
A
T
O
BL
OR
TB1
++
BL
SEE NOTE 4
YL
HPS2
LPS2
0140L00548 REV B
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
High Voltage: Disconnect all power before servicing or installing this unit. Mulꢀple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
⚠ Warning
32
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
wiring diagram — CpC090-150 (Cont.)
L1
L2
L3
COMPONENT LEGEND
FACTORY WIRING
LINE VOLTAGE
LOW VOLTAGE
SUPPLY VOLTAGE
208-240/460/575/3/60
BC
CC
CM
BLOWER CONTACTOR
COMPRESSOR CONTACTOR
CONDENSER MOTOR
OPTIONAL
HIGH VOLTAGE
CMR
COMP
DC
DFT
ECON
EBTD
EMR
R
CONDENSER MOTOR RELAY
COMPRESSOR
DEFROST CONTROL
DEFROST THERMOSTAT
ECONOMIZER
ELECTRONIC BLOWER TIME DELAY
EVAPORATOR MOTOR RELAY
RELAY
EVAPORATOR MOTOR
FAN CAPACITOR
T2
FIELD WIRING
CC1
T2
COMP1
HIGH VOLTAGE
LOW VOLTAGE
CC1
T1
CC1
T3
T3
C
WIRE CODE
RCCF1
EM
FC
BK
BL
BLACK
BLUE
BROWN
GREEN
ORANGE
PINK
PURPLE
RED
WHITE
YELLOW
F
CM1
GND
HPS
HVDR
LPS
LVDR
PB
PLF
RVC
RCCF
EQUPIMENT GROUND
BR
GR
OR
PK
PU
RD
WH
YL
HIGH PRESSURE SWITCH
HIGH VOLTAGE DEFROST RELAY
LOW PRESSURE SWITCH
LOW VOLTAGE DEFROST RELAY
POWER DISTRUBTION BLOCK
FEMALE PLUG / CONNECTOR
REVERSING VAVLE COIL
RUN CAPACITOR FOR
C
RCCF2
F
CM2
YL/PK YELLOW WITH
PINK STRIP
BL/PK BLUE WITH
PINK STRIP
COMPRESSOR AND FAN
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
TB1
TR
T2
CC2
T2
T1 COMP2
CC2
T1
CC2
T3
THERMOSTAT
T3
FIELD WIRING ++
BC
2 STAGE COOLING
BC
NOTES:
W1
G
WH
GR
RD
YL
W1
G
EM
BC
208-240V
OR APPROPRIATE
INPUT VOLTAGE
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)
USE COPPER CONDUCTOR ONLY.
2. USE COPPER CONDUCTORS ONLY
++ USE N.E.C. CLASS 2 WIRE
R
R
Y1
Y/Y2
C
Y1
Y2
C
PK
BL
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR
COMPARTMENT, REMOVE MALE PLUG, ATTACH
FEMALE PLUG TO THE ECONOMIZER ACCESSORY.
4. FOR TWO STAGE OPERATION REMOVE W1 TO W2
WIRE JUMPER.
5. FOR 208V OPERATION MOVE BLACK WIRE FROM
TERMINAL 3 TO TERMINAL 2 ON 240V
TRANSFORMER.
O
OR
BR
O
1
3
TB1
S2
W2
W2
STAT
TB1
S1
TR
24V
G
EBTDR
R
C
BC
R
EBTDR
EBTDR
LPS1
LPS2
CC1
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
PLF1
HPS2 CC2
HPS1
7
4
9
8
7
6
5
4
3
2
1
PLF2
8
9
5
6
SEE NOTE 4
Y/
R
W2
O
W1
Y1
Y2
G
C
TB1
208-240/460/575/3/60 0140L00549 REV. B
THERMOSTAT
++
SEE NOTE 3
Wiring is subject to change. Always
refer to the wiring diagram or the
unit for the most up-to-date wiring.
High Voltage: Disconnect all power before servicing or installing this unit. Mulꢀple power
sources may be present. Failure to do so may cause property damage, personal injury, or death.
⚡
⚠ Warning
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
33
Product SPecificationS
acceSSorieS
Fits
Model Sizes
Item #
Description
14CURB90150
25FD90150
25MFD90150
BRD3672
Roof Curb 14" Tall
25% Manual Fresh Air Damper
7½-12½ tons
7½-12½ tons
7½-12½ tons
7½-12½ tons
10 tons
25% Motorized Fresh Air Damper
Horizontal Barometric Relief Damper (two required)
Concentric Duct Kit
CDK120
CDK150
Concentric Duct Kit
12½ tons
CDK90102
DNBBS90150
DNECONGS90120
DNECONGS150
DNSQRRND90
GHRC-1
Concentric Duct Kit
7½-8½ tons
7½-12½ tons
7½-10 tons
12½ tons
Burglar Bar Sleeves: Includes Supply & Return
Downflow Economizer
Downflow Economizer
Downflow Square-to-Round Adapter 20" Round
Hurricane Restraint Clip
7½ tons
All Models
7½-10 tons
12½ tons
HailGD02
Condenser Coil Hail Guard
HailGD05
Condenser Coil Hail Guard
HSKT090
High-Staꢀc Kit for 7½-ton AA models & 8½-ton AA models (230/460v)
High-Staꢀc Kit for BA models (230/460v)
High-Staꢀc Kit for AA models (230/460v)
High-Staꢀc Kit for AA models (230/460v)
Horizontal Economizer
7½-8½ tons
7½ tons
HSKT090G
HSKT120
10 tons
HSKT150
12½ tons
HZECONGS90150
LAKT02
7½-12½ tons
7½ - 12½ tons
7½ - 12½ tons
7½-12½ tons
7½-12½ tons
Low-Ambient Kit for units with serial number below 0909
Low Ambient Kit for units with serial numbers 0909 and above
Power Exhaust 208/230 Volt
LAKT03
PE901502
PE901504
Power Exhaust 460 Volt
34
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
prodUCt speCifiCations
notes
SS-CPC90-150
Download from Www.Somanuals.com. All Manuals Search And Download.
35
prodUCt speCifiCations
notes
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without
notice or without incurring obligations. © 2011 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC90-150
|
Electro Voice Speaker System DH2T 16 User Manual
Fitness Quest Home Gym 95e User Manual
Franke Consumer Products Oven FHPL 301 1CO User Manual
Fujitsu Switch MB3842 User Manual
Furman Sound Music Pedal SPB 8 8E User Manual
Gamber Johnson Printer 7160 0526 00 User Manual
GE Coffeemaker 106840 User Manual
GE Convection Oven JBP95 User Manual
GE Refrigerator 21 23 25 27 29 User Manual
GE Water Heater GEH50DEED User Manual