CpC CommerCial
3- to 6-ton paCkaged
Cooling CapaCity:
35,000 — 71,000 BtU/h
air Conditioners
13 seer / 11.3 eer
single-phase & three-phase
Standard Features
• R-410A chlorine-free refrigerant
• High-efficiency scroll compressor
• Copper tube/aluminum fin coils
• High- and low-pressure switches
• Contactor with lugs
• High-capacity, steel-cased filter dryer
• Heater kits with single-point entry
• 24-volt terminal strip
• Convertible
• Easy to service
• Built-in filter rack with standard 2” filters
• Bottom utility entry
• AHRI Certified; ETL Listed
Cabinet Features
Contents
• Heavy-gauge, galvanized-steel cabinet with
UV-resistant powder-paint finish
• Full Perimeter Rail
Nomenclature....................................................................2
Product Specifications .......................................................3
Heat Kit Electrical Data .....................................................9
Airflow Data .....................................................................12
Expanded Cooling Data ...................................................18
Dimensions ......................................................................26
Wiring Diagrams .............................................................30
Accessories .......................................................................36
com.
SS-CPC36-72
6/11
Supersedes 4/11
Download from Www.Somanuals.com. All Manuals Search And Download.
prodUCt speCifiCations
prodUCt speCifiCations — CpC036 B models
CPC036
XXX1DXXX
CPC036
XXX3DXXX
CPC036
XXX3BXXX
CPC036
XXX4BXXX
CPC036
XXX7BXXX
Cooling Capacity
Total BTU/h
34,600
25,600
13 / 11.3
78
34,600
25,600
13 / 11.3
78
34,600
25,600
13 / 11.3
78
34,600
25,600
13 / 11.3
78
34,600
25,600
13 / 11.3
78
Sensible BTU/h
SEER / EER
Decibels
ARI Reference #s
4385050
4385051
4385051
4385052
4397604
Evaporator Motor / Coil
Motor Type
Direct Drive
1,200
Direct Drive
1,200
Belt Drive
Belt Drive
1,200
---
Belt Drive
1,200
---
Indoor Nominal CFM
Motor Speed Tap (Cooling)
Indoor motor FLA (Cooling)
Horsepower - RPM
1,200
Low Speed
2.50
Low Speed
2.50
---
3.8
1.9
2.3
⅓ - 890
0.068
⅓ - 890
0.068
1.0 - 1725
1.0 - 1725
0.068
1.5 - 1725
0.068
Piston Size (Cooling)
Filter Size (Qty)
0.068
(1) 24" x 24" x 2"
¾"
(1) 24" x 24" x 2"
¾"
(1) 24" x 24" x 2"
(1) 24" x 24" x 2"
(1) 24" x 24" x 2"
Drain Size (NPT)
¾"
83
¾"
83
¾"
125
R-410A Refrigerant Charge (oz.)
Evaporator Coil Face Area (ſt²)
Rows Deep/ Fins per Inch
Evaporator Fan
83
83
5.4
5.4
5.4
5.4
5.4
3 / 16
3 / 16
3 / 16
3 / 16
3 / 16
Standard Direct Drive (D x W) HP
Standard Belt Drive (D x W) HP
High-Staꢀc Belt Drive (D x W) HP
# of Wheels (D x W)
Motor Sheave
(10" X 9") ½
(10" X 9") ½
---
---
---
---
---
---
---
---
---
---
---
---
---
(11" X 10") 1
(11" X 10") 1½
1 (11" x 10")
1VL40 X ⅝
(11" X 10") 1
(11" X 10") 1½
1 (11" x 10")
1VL40 X ⅝
(11" X 10") 1½
(11" X 10") 1½
1 (11" x 10")
1VL40 X ⅝
Blower Sheave / Belt
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
AK69 x 1 / AX55
AK69 x 1 / AX55
AK69 x 1 / AX55
1
1
1
1
1
¼ / 1,090
22 / 4
3,800
17.0
¼ / 1,090
22 / 4
3,800
17.0
¼ / 1,090
22 / 4
3,800
17.0
¼ - 890
22 / 4
3,800
17.0
¼ - 1,075
22 / 4
3,800
13.0
Fan Diameter/ # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
Rows Deep/ Fins per Inch
Compressor
1 / 24
1 / 24
1 / 24
1 / 24
2 / 16
Quanꢀty / Type
1 / Scroll
Single
1 / Scroll
Single
1 / Scroll
Single
1 / Scroll
Single
1 / Scroll
Single
Stage
Compressor RLA / LRA
Electrical Data
16.7 / 79.0
10.5 / 73.0
10.5 / 73.0
5.8 / 38.0
3.8 / 36.5
Voltage-Phase-Frequency
Indoor Blower HP / FLA
Outdoor Fan HP / FLA
Total Unit Amps
208/230-1-60
⅓ / 2.5
¼ / 1.4
20.57
25
208/230-3-60
⅓ / 2.5
¼ / 1.4
14.35
17
208/230-3-60
1 / 3.8
¼ / 1.4
15.65
18
460-3-60
1 / 1.9
¼ / 0.8
8.47
575-3-60
1.5 / 2.3
0.60
6.68
8
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Power Supply Conduit Hole
Low Voltage Conduit Hole
Operating Weight (lbs)
Ship Weight (lbs)
10
40
25
25
15
15
1.125"
½"
1.125"
½"
1.125"
½"
1.125"
½"
1.125"
½"
500
500
500
500
500
525
525
525
525
525
¹ Wire size should be determined in accordance with Naꢀonal Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
3
prodUCt speCifiCations
prodUCt speCifiCations — CpC048 B models
CPC048
XXX1DXXX
CPC048
XXX3DXXX
CPC048
XXX3BXXX
CPC048
XXX4BXXX
CPC048
XXX7BXXX
Cooling Capacity
Total BTU/h
45,500
35,000
45,500
35,000
45,500
35,000
45,500
35,000
45,500
35,000
Sensible BTU/h
SEER / EER
13.0 / 11.3
78
13.0 / 11.3
78
13.0 / 11.3
78
13.0 / 11.3
78
13.0 / 11.3
78
Decibels
ARI Reference #s
4385053
4385054
4385054
4385055
4397605
Evaporator Motor / Coil
Motor Type
Direct Drive
1,600
Direct Drive
1,600
Belt Drive
Belt Drive
Belt Drive
Indoor Nominal CFM
Motor Speed Tap (Cooling)
Indoor Motor FLA (Cooling)
Horsepower - RPM
Piston Size (Cooling)
Filter Size (Qty)
1,600
1,600
1,600
Medium
2.87
Medium
2.87
--
--
--
3.8
1.0 - 1,725
0.076
1.9
1.0 - 1,725
0.076
2.3
1.5 - 1,725
0.076
½ -1,000
0.076
½ -1,000
0.076
(4) 14" x 20" x 2"
¾"
(4) 14" x 20" x 2"
¾"
(4) 14" x 20" x 2"
¾"
(4) 14" x 20" x 2"
¾"
(4) 14" x 20" x 2"
¾"
Drain Size (NPT)
R-410A Refrigerant Charge (oz.)
Evaporator Coil Face Area (ſt²)
Rows Deep / Fins per Inch
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave
103
103
103
103
105
7.0
7.0
7.0
7.0
7.0
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
---
---
---
---
---
---
1 (11" x 10")
VL44 X 5/8
1 (11" x 10")
VL44 X 5/8
AK66 X 1
1 (11" x 10")
VL44 X 5/8
AK66 X 1
Blower Sheave / Belt
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
Fan Diameter / # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
AK66 x 1 / AX55
1
¼ - 1,090
22 / 4
3,800
17
1
¼ - 1,090
22 / 4
3,800
17
1
¼ - 1,090
22 / 4
3,800
17
1
¼ - 1,090
22 / 4
3,800
17
1
¼ - 1,075
22 / 4
3,800
17
Rows Deep / Fins per Inch
Compressor
1 / 24
1 / 24
1 / 24
1 / 24
1 / 24
Quanꢀty / Stage
1 / Single
Scroll
1 / Single
Scroll
1 / Single
Scroll
1 / Single
Scroll
1 / Single
Scroll
Type
Compressor RLA / LRA
Electrical Data
20 / 109
13.1/ 83.1
13.1/ 83.1
6.1/ 41
4.4/ 33
Voltage-Phase-Frequency
Outdoor Fan FLA
208/230-1-60
208/230-3-60
208/230-3-60
460-3-60
0.80
8.8
575-3-60
0.60
7.3
1.40
24.1
29
1.40
17.4
21
1.40
18.3
22
Total Unit Amps
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Power Supply Conduit Hole
Low-Voltage Conduit Hole
Operating Weight (lbs)
Ship Weight (lbs)
10
8
45
30
30
15
15
1.125"
½"
1.125"
½"
1.125"
½"
1.125"
½"
1.125"
½"
535
560
535
560
535
560
535
535
560
560
¹ Wire size should be determined in accordance with Naꢀonal Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
4
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
prodUCt speCifiCations — CpC060 B models
CPC060
XXX1DXXX
CPC060
XXX3DXXX
CPC060
XXX3BXXX
CPC060
XXX4BXXX
CPC060
XXX7BXXX
Cooling Capacity
Total BTU/h
59,500
43,200
13 / 11.3
78
59,500
43,200
13 / 11.3
78
59,500
43,200
13 / 11.3
78
59,500
43,200
13 / 11.3
78
59,500
43,200
13 / 11.3
78
Sensible BTU/h
SEER / EER
Decibels
ARI Reference #s
4385056
4385057
4385057
4385058
4397606
Evaporator Motor / Coil
Motor Type
Direct
2,000
Direct
2,000
Belt
2,000
Belt
Belt
Indoor Nominal CFM
Expansion Device
2,000
Piston
0.086
2,000
Piston
0.082
Piston
Piston
Piston
Piston Size (Cooling)
Filter Size (")
0.086
0.086
0.086
(4) 14 x 20 x 2
¾"
(4) 14 x 20 x 2
¾"
(4) 14 x 20 x 2
¾"
(4) 14 x 20 x 2
(4) 14 x 20 x 2
Drain Size (NPT)
¾"
162
¾"
162
R-410A Refrigerant Charge (oz.)
Face Area (ſt²)
162
162
162
7.8
7.8
7.8
7.8
7.8
Rows Deep/ Fins per Inch
Tube Diameter - Material
Evaporator Fan
4 / 16
4 / 16
4 / 16
4 / 16
4 / 16
5/16 - Copper
5/16 - Copper
5/16 - Copper
5/16 - Copper
5/16 - Copper
Standard Direct Drive (D x W) HP
Standard Belt Drive (D x W) HP
High-Staꢀc Belt Drive (D x W) HP
Belt Drive Evap Fan Data
# of Wheels (D x W)
Motor Sheave
(11" X 10") 1
(11" X 10") 1
---
---
---
---
---
---
---
(11" X 10") 1
(11" X 10") 1½
(11" X 10") 1
(11" X 10") 1½
(11" X 10") 1½
(11" X 10") 1½
---
---
---
---
---
---
1 (11" x 10")
VL44 x ⅝
1 (11" x 10")
VL44 x ⅝
1 (11" x 10")
VL44 x ⅝
Blower Sheave / Belt
Condenser Fan / Coil
Horsepower / RPM
Fan Diameter/ # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
AK61x1 / AX53
AK61x1 / AX53
AK61x1 / AX53
¼ / 1,090
22 / 4
¼ / 1,090
22 / 4
¼ / 1,090
22 / 4
¼ / 1,090
22 / 4
¼ / 1,075
22 / 4
3,800
3,800
3,800
3,800
3,800
17.0
17.0
17.0
17.0
17.0
Rows Deep/ Fins per Inch
Tube Diameter - Material
Compressor
2 / 18
2 / 18
2 / 18
2 / 18
2 / 18
5/16 - Copper
5/16 - Copper
5/16 - Copper
5/16 - Copper
5/16 - Copper
Quanꢀty / Type
1 / Scroll
Single
1 / Scroll
Single
1 / Scroll
Single
1 / Scroll
Single
1 / Scroll
Single
Stage
Compressor RLA / LRA
Electrical Data
26.4 / 134
16 / 110
16 / 110
7.8 / 52
5.7 / 38.9
Voltage-Phase-Frequency
Indoor Blower HP / FLA
Indoor Blower LRA
Outdoor Fan HP / FLA
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon²
Power Supply Conduit Hole
Low-Voltage Conduit Hole
Operating Weight (lbs)
Ship Weight (lbs)
208/230-1-60
1.0 / 7.6
24
208/230-3-60
1.0 / 7.6
----
208/230-3-60
1.0 / 3.8
24
460-3-60
1.0 / 1.9
12
575-3-60
1.5 / 2.3
12
¼ / 1.40
42
¼ / 1.40
29
¼ / 1.40
25
¼ / 0.80
12
¼ / 0.60
10
60 amps
1.125"
½"
45 amps
1.125"
½"
40 amps
1.125"
½"
20 amps
1.125"
½"
15 amps
1.125"
½"
580
580
580
580
580
605
605
605
605
605
¹ Wire size should be determined in accordance with Naꢀonal Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
5
prodUCt speCifiCations
prodUCt speCifiCations — CpC072 B models
CPC072
XXX3BXXX
CPC072
XXX4BXXX
CPC072
XXX7BXXX
Cooling Capacity
Total BTU/h
71,000
48,280
11.2
71,000
48,280
11.2
71,000
48,280
11.2
Sensible BTU/h
EER
Decibels
78.0
78.0
78.0
AHRI Number
3397631
3397631
3397631
Evaporator Motor / Coil
Motor Type
Belt Drive
1 (11" x 10")
2,400
Belt Drive
1 (11" x 10")
2,400
Belt Drive
1 (11" x 10")
2,400
Wheel (D x W)
Indoor Nominal CFM
Indoor motor FLA (Cooling)
Horsepower - RPM
Piston Size (Cooling)
Filter Size (Qty)
5.0
2.5
2.3
1.5-1,725
0.094
1.5-1,725
0.094
1.5-1,725
0.094
(4) 16" x 20" x 2"
¾"
(4) 16" x 20" x 2"
¾"
(4) 16" x 20" x 2"
¾"
Drain Size (NPT)
R-410A Refrigerant Charge Cir #1(oz.)
Evaporator Coil Face Area (ſt²)
Rows Deep/ Fins per Inch
Motor Sheave
213.0
213.0
213.0
8.9
8.9
8.9
4/ 16
4/ 16
4/ 16
VL44 X 7/8
AK59 X 1
AX53
VL44 X 7/8
AK59 X 1
AX53
VL44 X 7/8
AK59 X 1
AX53
Blower Sheave
Belt
Condenser Fan / Coil
Quanꢀty of Condenser Fan Motors
Horsepower - RPM
Fan Diameter/ # Fan Blades
Outdoor Nominal CFM
Face Area (ſt²)
1
⅓ - 1,075
22/ 4
1
⅓ - 1,075
22/ 4
1
⅓ - 1,075
22/ 4
4,300
18.7
4,300
18.7
4,300
18.7
Rows Deep/ Fins per Inch
Compressor
2/ 20
2/ 20
2/ 20
Quanꢀty / Type
1 / Scroll
Single
1 / Scroll
Single
1 / Scroll
Single
Stage
Compressor RLA / LRA ea.
Electrical Data
19/123.0
9.7/62.0
7.4/50.0
Voltage/Phase/ Frequency
Belt-Driven Standard Max Staꢀc
Outdoor Fan FLA ea.
Total Unit Amps
208-230/3/60
460/3/60
1.0
575/3/60
1.0
1.0
1.90
25.9
31
1.20
13.4
16
0.90
10.6
12
Min. Circuit Ampacity¹
Max. Overcurrent Protecꢀon (amps)²
Entrance Power Supply
Entrance Control Voltage
Operating Weight (lbs)
Ship Weight (lbs)
45
25
15
1.125"
½"
1.125”
½"
1.125”
½"
640
665
640
640
665
665
¹ Wire size should be determined in accordance with Naꢀonal Electrical Codes. Extensive wire runs will require larger wire sizes.
May use fuses or HACR-type circuit breakers of the same size as noted.
Note: Always check the S&R plate for electrical data on the unit being installed.
²
6
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 3 tons
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW &
BTU at 240V
Recommended
Airflow Range
CPC036***1D***
EHK1-10
25
40
48 / 55
70 / 81
17
50 / 60
80 / 90
25
10
15
1250-1350 CFM
1400-1440 CFM
EHK1-15
CPC036***3D***
EHK3-10
29 / 33
42 / 48
18
30 / 35
45 / 50
25
10
15
1250-1350 CFM
1400-1440 CFM
EHK3-15
CPC036***3B***
EHK3-10
30 / 33
43 / 48
35 / 35
45 / 50
10
15
1250-1350 CFM
1400-1440 CFM
EHK3-15
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW &
BTU at 480V
Recommended
Airflow Range
CPC036***4B***
EHK4-10
10
17
25
15
20
25
10
15
1250-1350 CFM
1400-1440 CFM
EHK4-15
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW &
BTU at 575V
Recommended
Airflow Range
CPC036***7B***
EHK7-10
8
15
22
15
20
25
10
15
1250-1350 CFM
1400-1440 CFM
EHK7-15
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon device
kw CorreCtion faCtor
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
1
230
220
210
208
Correction Factor
0.93
0.82
0.78
0.76
Mulꢀply rated kW by correcꢀon factor to get actual kW
kW Correction Factor for 480V Units
Minimum Airflow for Electric Heat
Actual Voltage
460
440
430
0.8
Minimum CFM
Heater Size
Correction Factor
0.92
0.84
A Models
1,250
B Models
For other voltage use voltage2 / 4802
10 kW
15 kW
1,250
1,250
kW Correction Factor for 575V Units
1,400
Supply Voltage
560
550
540
Correction Factor
0.95
0.91
0.88
Mulꢀply rated kW by correcꢀon factor to get actual kW
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
7
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 4 tons
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW &
BTU at 240V
Recommended
Airflow Range
CPC048***1D***
EHK1-10
29
45
48 / 56
71 / 82
84 / 97
21
50 / 60
80 / 90
90 / 100
30
10
15
18
1400-1800 CFM
1575-1800 CFM
1575-1800 CFM
EHK1-15
EHK1-18
CPC048***3D***
EHK3-10
29 / 34
42 / 49
50 / 58
22
35 / 35
45 / 50
60 / 60
30
10
15
18
1400-1800 CFM
1575-1800 CFM
1575-1800 CFM
EHK3-15
EHK3-18
CPC048***3B***
EHK3-10
30 / 35
43 / 50
51 / 59
35 / 35
45 / 50
60 / 60
10
15
18
1400-1800 CFM
1575-1800 CFM
1575-1800 CFM
EHK3-15
EHK3-18
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW &
BTU at 480V
Recommended
Airflow Range
CPC048***4B***
EHK4-10
10
17
25
29
15
20
25
30
10
15
18
1400-1800 CFM
1575-1800 CFM
1575-1800 CFM
EHK4-15
EHK4-18
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps) Actual kW & BTU Recommended
at 575V
at 575V
Airflow Range
CPC048***7B***
EHK7-10
8
15
20
25
30
15
22
25
10
15
18
1400-1800 CFM
1575-1800 CFM
1575-1800 CFM
EHK7-15
EHK7-18
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon device
kw CorreCtion faCtor
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
Correction Factor
240
1
230
0.93
220
0.82
210
0.78
208
0.76
Mulꢀply rated kW by correcꢀon factor to get actual kW
kW Correction Factor for 480V Units
Actual Voltage
Correction Factor
460
0.92
440
0.84
430
0.8
Minimum Airflow for Electric Heat
Minimum CFM
Heater Size
For other voltage use voltage² / 480²
A Models
B Models
1,300
10 kW
15 kW
18 kW
1,400
1,575
1,575
kW Correction Factor for 575V Units
1,400
Supply Voltage
Correction Factor
560
0.95
550
0.91
540
0.88
1,400
Mulꢀply rated kW by correcꢀon factor to get actual kW.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 5 tons
Model and
Heat Kit Usage
MCA¹ at
208 / 240V
MOP² (amps)
at 208 / 240V
Actual kW &
BTU at 240V
Recommended
Airflow Range
Speed Tap
CPC060***1D***
EHK1-10
42
60
60 / 70
80 / 90
100 / 120
45
53 / 62
76 / 88
99 / 114
29
10
15
20
1750-2250 CFM
1750-2250 CFM
1850-2250 CFM
T3, T4, T5
T3, T4, T5
T5
EHK1-15
EHK1-20
CPC060***3D***
EHK3-10
34 / 40
47 / 55
60 / 70
25
35 / 45
50 / 60
70 / 70
40
10
15
20
1750-2250 CFM
1750-2250 CFM
1850-2250 CFM
T3, T4, T5
EHK3-15
T3, T4, T5
EHK3-20
T5
---
---
---
---
CPC060***3B***
EHK3-10
30 / 35
43 / 50
56 / 65
35 / 40
45 / 50
60 / 70
10
15
20
1750 - 2250 CFM
1750 - 2250 CFM
1850 - 2250 CFM
EHK3-15
EHK3-20
Model and
Heat Kit Usage
MCA¹
at 480V
MOP² (amps)
at 480V
Actual kW &
BTU at 480V
Recommended
Airflow Range
CPC060***4B***
EHK4-10
12
19
25
35
20
20
25
35
10
15
20
1750 - 2250 CFM
1750 - 2250 CFM
1850 - 2250 CFM
EHK4-15
EHK4-20
Model and
Heat Kit Usage
MCA¹
at 575V
MOP² (amps)
at 575V
Actual kW &
BTU at 575V
Recommended
Airflow Range
CPC060***7B***
EHK7-10
10
15
22
28
34
15
20
25
30
35
10
15
20
25
1750-2250 CFM
1750-2250 CFM
1850-2250 CFM
---
EHK7-15
EHK7-20
EHK7-25
¹
²
Minimum Circuit Ampacity
Maximum Overcurrent Protecꢀon Device
kw CorreCtion faCtor
kW Correction Factor for 1- & 3-Phase Units
Supply Voltage
240
1
230
220
210
208
0.76
Correction Factor
0.93
0.82
0.78
kW Correction Factor for 480V Units
Actual Voltage
460
440
430
0.8
Minimum Airflow for Electric Heat
Correction Factor
0.92
0.84
Minimum CFM
Heater Size
For other voltage use voltage² / 480²
A Models
1,750
B Models
1,700
10
15
20
kW Correction Factor for 575V Units
1,750
1,700
Supply Voltage
560
550
540
1,850
1,880
Correction Factor
0.95
0.91
0.88
Mulꢀply rated kW by correcꢀon factor to get actual kW
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
9
prodUCt speCifiCations
heat kit eleCtriCal data (Blower only, heat mode) — 6 tons
Model and
Heat Kit Usage
MCA¹ @
208 / 240V
MOP² (amps)
@ 208 / 240V
Actual kW &
BTU @ 240V
Recommended
Airflow Range
CPC072XXX3BXXX
EHK3-10
31
36
51
66
81
45
45
60
70
90
10
15
20
25
2,100 - 2,700 CFM
2,100 - 2,700 CFM
2,100 - 2,700 CFM
2,100 - 2,700 CFM
EHK3-15
EHK3-20
EHK3-25
Model and
Heat Kit Usage
MCA¹
@ 480V
MOP² (amps)
@ 480V
Actual kW &
BTU @ 480V
Recommended
Airflow Range
CPC072XXX4BXXX
EHK4-10
16
18
26
33
41
25
25
30
35
45
10
15
20
25
2,100 - 2,700 CFM
2,100 - 2,700 CFM
2,100 - 2,700 CFM
2,100 - 2,700 CFM
EHK4-15
EHK4-20
EHK4-25
Model and
Heat Kit Usage
MCA¹
@ 575V
MOP² (amps)
@ 575V
Actual kW &
BTU @ 575V
Recommended
Airflow Range
CPC072XXX7BXXX
EHK7-10
13
15
22
28
34
15
20
25
30
35
10
15
20
25
2,100 - 2,700 CFM
2,100 - 2,700 CFM
2,100 - 2,700 CFM
2,100 - 2,700 CFM
EHK7-15
EHK7-20
EHK7-25
¹
Minimum Circuit Ampacity
²
Maximum Overcurrent Protecꢀon Device
Note: All heaters have single-point entry kit
kW Correction Factor for 3-Phase Units
Supply Voltage
240
1
230
220
210
Correcꢀon Factor
0.92
0.84
0.77
kW Correction Factor for 480V Units
Actual Voltage
460
440
430
0.8
Minimum Airflow for Electric Heat
Correcꢀon Factor
0.92
0.84
Heater Size
Minimum CFM
2,100
For other voltage use voltage² / 480²
10
15
20
25
2,100
kW Correction Factor for 575V Units
2,100
Supply Voltage
560
550
540
2,100
Correcꢀon Factor
0.95
0.91
0.88
Mulꢀply rated kW by correcꢀon factor to get actual kW.
10
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
airflow data — CpC036
direCt drive — horizontal
direCt drive — down shot
Speed
Tap
Speed
Tap
CFM
Static
Amps
Watts
RPM
CFM
Static
Amps
Watts
RPM
1296
1245
1174
1103
1013
1502
1449
1396
1335
1273
1153
996
0.1
0.2
0.3
0.4
0.5
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.2
0.3
0.4
0.5
0.6
0.7
0.8
1.67
1.60
1.56
1.52
1.46
2.10
2.06
2.02
1.97
1.91
1.83
1.71
2.36
2.31
2.26
2.17
2.09
2.02
1.90
356
334
325
316
300
456
444
432
418
404
380
346
506
496
486
458
441
424
390
764
830
861
891
935
836
864
891
916
940
973
1017
940
960
979
1006
1023
1039
1067
1287
1233
1176
1107
1044
965
0.1
0.2
0.3
0.4
0.5
0.6
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.3
0.4
0.5
0.6
0.7
0.8
1.66
1.63
1.59
1.55
1.51
1.45
2.08
2.03
1.96
1.90
1.84
1.78
1.70
2.31
2.25
2.16
2.09
2.02
1.90
350
342
332
320
312
296
446
432
414
396
386
368
344
490
476
454
438
418
386
770
815
858
891
924
957
866
885
918
945
971
990
1023
962
984
1006
1025
1039
1067
Low
Low
Med
High
1476
1421
1334
1255
1180
1085
964
Med
1516
1454
1392
1273
1183
1092
920
1455
1367
1277
1180
1080
922
High
Notes:
•
Assumes dry coil with filter in place
•
SCFM correcꢀon for wet coil = 4%
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
11
prodUCt speCifiCations
airflow data — CpC036 (Cont.)
standard Belt drive — horizontal
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
1658
1339
949
BHP
0.35
0.28
0.19
CFM
1489
1129
BHP
0.28
0.21
0.2
0.4
0.6
0.8
1.0
1.2
1560
1196
828
0.36
0.27
0.18
1682
1354
994
0.47
0.38
0.28
1436
1096
756
0.36
0.28
0.19
1581
1266
923
0.50
0.39
0.28
high-statiC Belt drive — horizontal
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
1742
1357
1011
BHP
CFM
1431
1078
BHP
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.50
0.36
0.27
1626
1315
976
0.52
0.42
0.31
0.39
0.28
1611
1299
959
0.56
0.46
0.35
1605
1281
981
0.62
0.51
0.41
1605
1281
981
0.68
0.57
0.47
standard Belt drive — down shot
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
1424
1073
619
BHP
CFM
1239
779
BHP
0.2
0.4
0.6
0.8
1.0
1.2
0.30
0.22
0.12
0.23
0.14
1520
1192
864
0.39
0.30
0.22
1292
944
0.29
0.21
1439
1101
729
0.40
0.31
0.21
1350
1028
675
0.42
0.31
0.20
high-statiC Belt drive — down shot
Turns Open
ESP
(“ W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
1692
1397
1078
BHP
0.54
0.44
0.34
CFM
1449
1107
794
BHP
CFM
1173
854
BHP
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.41
0.29
0.21
1678
1381
1062
0.58
0.49
0.39
0.31
0.22
1681
1362
1066
789
0.65
0.54
0.44
0.34
1681
1362
1066
789
0.71
0.60
0.50
0.40
12
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
airflow data —CpC048
standard direCt drive — horizontal
standard direCt drive — down shot
Speed
Tap
Speed
Tap
CFM
Static
Amps
Watts
RPM
CFM
Static
Amps
Watts
RPM
1622
1558
1494
1410
1326
1861
1733
1639
1564
1434
1320
1156
1984
1883
1770
1656
1540
1415
0.1
0.2
0.3
0.4
0.5
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.1
0.2
0.3
0.4
0.5
0.6
2.54
2.43
2.32
2.21
2.10
3.11
2.78
2.64
2.51
2.35
2.25
2.08
3.34
3.18
3.03
2.87
2.76
2.62
539
517
495
471
447
670
606
568
542
508
482
446
734
694
654
620
590
558
809
852
1602
1538
1474
1390
1306
1805
1704
1625
1549
1437
1301
1158
1971
1828
1744
1628
1510
1402
0.1
0.2
0.3
0.4
0.5
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.1
0.2
0.3
0.4
0.5
0.6
2.48
2.37
2.26
2.15
2.04
2.84
2.71
2.59
2.47
2.38
2.23
2.09
3.22
3.03
2.94
2.80
2.69
2.57
528
506
484
460
436
620
590
558
540
516
480
444
706
664
632
606
582
552
835
878
895
Low
921
Low
924
950
953
979
886
935
918
967
960
990
984
Med
1012
1030
1050
1072
968
Med
1017
1039
1067
949
977
998
1001
1027
1044
1061
1017
1034
1050
1067
High
High
Notes:
•
Assumes dry coil with filter in place
•
SCFM correcꢀon for wet coil = 4%
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
13
prodUCt speCifiCations
airflow data —CpC048 (Cont.)
standard Belt drive — horizontal
0 Turns
CFM
1 Turn
CFM
2 Turns
CFM
3 Turns
4 Turns
CFM
5 Turns
CFM
ESP
(" W.C.)
BHP
BHP
BHP
CFM
BHP
BHP
0.52
0.40
0.26
BHP
0.40
0.26
0.2
0.4
0.6
0.8
1.0
1.2
1943
1566
1136
1714
1270
2187
1761
1335
0.72
0.56
0.40
1876
1444
0.55
0.40
2044
1704
1275
0.72
0.59
0.36
1947
1598
1208
0.74
0.60
0.45
high-statiC Belt drive — horizontal
0 Turns
1 Turn
2 Turns
CFM
3 Turns
4 Turns
BHP
0.72
5 Turns
BHP
0.54
0.40
ESP
(" W.C.)
CFM
BHP
CFM
BHP
BHP
CFM
BHP
CFM
2056
1662
1270
CFM
1721
1328
0.6
0.8
1.0
1.2
1.4
1.6
1.8
1996
1603
1210
0.77
0.61
0.44
0.57
0.43
1924
1559
1195
0.79
0.64
0.49
1952
1543
1180
0.88
0.70
0.54
1888
1557
1192
0.92
0.77
0.60
standard Belt drive — down shot
0 Turns
1 Turn
2 Turns
CFM
3 Turns
4 Turns
BHP
5 Turns
BHP
ESP
(" W.C.)
CFM
BHP
CFM
BHP
BHP
CFM
2129
1701
1326
BHP
0.64
0.49
0.36
CFM
1795
1433
1025
CFM
1550
1163
0.2
0.4
0.6
0.8
1.0
1.2
0.47
0.36
0.22
0.35
0.22
1994
1606
1216
0.65
0.50
0.36
1905
1565
1137
0.67
0.54
0.32
1808
1473
1103
0.69
0.55
0.41
high-statiC Belt drive — down shot
0 Turns
1 Turn
2 Turns
CFM
3 Turns
4 Turns
5 Turns
ESP
(" W.C.)
CFM
BHP
CFM
BHP
BHP
CFM
2194
1832
1472
1111
BHP
0.85
0.70
0.55
0.40
CFM
1886
1526
1166
BHP
CFM
1580
1219
BHP
0.6
0.8
1.0
1.2
1.4
1.6
1.8
0.66
0.49
0.37
2113
1776
1440
1104
0.86
0.73
0.59
0.46
0.52
0.39
2182
1780
1421
1095
0.98
0.80
0.64
0.50
2053
1759
1442
1095
1.00
0.86
0.72
0.56
14
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
airflow data — CpC060
standard direCt drive motor — horizontal
standard direCt drive motor — down shot
Speed
Tap
Speed
Tap
CFM
Static
Amps
Watts
RPM
CFM
Static
Amps
Watts
RPM
1355
1281
1235
1168
1118
1049
982
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.57
1.66
1.76
1.81
1.94
2.03
2.10
2.14
2.25
2.04
2.17
2.25
2.35
2.42
2.52
2.62
2.73
2.77
4.13
4.25
4.37
4.48
4.61
4.73
4.86
4.91
5.03
4.76
4.91
5.02
5.14
5.27
5.41
5.47
5.60
5.70
5.44
5.55
5.68
5.80
5.93
6.01
6.12
6.22
6.10
174
182
196
202
218
232
240
246
260
234
250
260
276
282
296
316
326
336
516
536
552
568
586
604
622
630
648
608
628
640
660
678
696
704
724
736
710
726
742
766
782
788
808
822
804
599
651
693
726
775
819
858
885
927
660
704
742
781
809
849
891
935
957
825
852
885
913
950
973
1012
1028
1067
863
896
924
951
979
1012
1034
1067
1089
904
934
958
990
1017
1039
1060
1094
1111
1334
1286
1212
1144
1077
1039
953
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1.65
1.75
1.83
1.94
1.99
2.10
2.17
2.27
2.30
2.12
2.24
2.31
2.44
2.54
2.59
2.72
2.77
2.90
4.27
4.39
4.60
4.68
4.79
4.87
4.99
5.06
5.19
4.95
5.07
5.19
5.28
5.40
5.49
5.58
5.70
5.69
5.70
5.80
5.90
6.07
6.12
6.21
6.30
6.27
6.13
180
192
202
216
222
238
248
258
266
240
254
264
282
296
304
322
328
344
540
558
576
588
608
620
640
650
668
634
652
670
682
698
720
732
742
740
742
748
768
786
804
816
820
816
790
627
665
715
759
792
830
874
913
940
682
720
759
803
836
874
913
946
984
869
896
929
957
989
1012
1050
1072
1105
913
940
962
990
T1
T2
T3
T4
T5
T1
T2
T3
T4
T5
922
871
904
825
1544
1490
1427
1370
1319
1274
1210
1137
1106
2099
2068
2029
1971
1911
1876
1821
1792
1740
2233
2168
2125
2070
2050
1980
1954
1893
1852
2322
2294
2254
2201
2147
2117
2081
2017
1932
1512
1469
1397
1333
1285
1221
1173
1118
1049
2053
2014
1999
1947
1897
1857
1763
1741
1669
2137
2093
2095
2026
1980
1961
1914
1845
1766
2299
2233
2217
2157
2131
2060
2015
1940
1862
1018
1039
1072
1100
1127
942
969
990
1018
1045
1073
1095
1111
1128
Notes
Assumes dry coil with filter in place; SCFM correcꢀon for wet coil = 4%
Five-ton models are shipped from the factory with speed tap set on T4.
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
15
prodUCt speCifiCations
airflow data — CpC060 (Cont.)
standard Belt drive — horizontal
Turns Open
ESP
(" W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
2420
2133
1806
BHP
0.79
0.67
0.55
CFM
2198
1874
BHP
0.64
0.52
0.2
0.4
0.6
0.8
1.0
1.2
2605
2300
1975
1628
1.02
0.88
0.73
0.57
2358
2026
1670
0.84
0.70
0.54
2526
2252
1943
1582
1.06
0.93
0.78
0.61
2529
2233
1907
1.15
0.99
0.83
high-statiC Belt drive — horizontal
Turns Open
ESP
(" W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
2323
2009
1666
BHP
0.92
0.77
0.60
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2315
1992
1646
1.00
0.84
0.66
2308
1992
1648
1.09
0.92
0.72
2338
2025
1684
1.21
1.02
0.82
2359
2056
1722
1.32
1.13
0.92
2404
2088
1.45
1.24
standard Belt drive — down shot
Turns Open
ESP
(" W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
2579
2318
2045
1760
BHP
1.01
0.89
0.77
0.63
CFM
2368
2089
1797
BHP
0.85
0.73
0.60
CFM
2175
1906
1604
BHP
0.69
0.59
0.47
CFM
1961
1666
BHP
0.55
0.44
0.2
0.4
0.6
0.8
1.0
1.2
2513
2276
2017
1730
1.05
0.94
0.82
0.68
2514
2261
1989
1695
1.14
1.01
0.87
0.72
high-statiC Belt drive — down shot
Turns Open
ESP
(" W.C.)
0
1
2
3
4
5
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
2331
2059
1774
BHP
1.01
0.87
0.72
CFM
2072
1791
BHP
0.80
0.66
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2324
2058
1776
1.10
0.95
0.79
2350
2086
1805
1.21
1.06
0.89
2367
2111
1835
1.33
1.17
0.99
2404
2136
1868
1.45
1.28
1.10
16
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
airflow data — CpC072
standard Belt drive — horizontal
0 Turns
1 Turn
1 Turn
1 Turn
2 Turns
3 Turns
4 Turns
BHP
5 Turns
ESP (In W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
2784
2620
2398
2142
1883
BHP
1.30
1.19
1.06
0.91
0.78
CFM
2582
2342
2103
1816
CFM
2411
2105
1902
BHP
0.79
0.66
0.57
0.2
0.4
0.6
0.8
1
0.83
0.72
0.62
0.51
2814
2583
2370
2098
1.34
1.19
1.07
0.92
2665
2492
2275
1996
1.34
1.22
1.09
0.92
2689
2438
2250
1.38
1.22
1.10
1.2
standard Belt drive — down shot
0 Turns
2 Turns
3 Turns
4 Turns
5 Turns
ESP (In W.C.)
CFM
BHP
CFM
BHP
CFM
2771
2573
2360
2111
1840
BHP
CFM
2567
2382
2119
1868
BHP
1.05
0.95
0.81
0.69
CFM
2421
2186
1934
BHP
0.88
0.77
0.65
CFM
2220
1980
BHP
0.71
0.61
0.2
0.4
0.6
0.8
1
1.27
1.15
1.02
0.89
0.75
2753
2548
2331
2078
1.38
1.24
1.11
0.96
2655
2470
2296
2040
1.42
1.30
1.18
1.02
1.2
high-statiC Belt drive — horizontal
0 Turns
2 Turns
3 Turns
4 Turns
5 Turns
ESP (In W.C.)
CFM
BHP
CFM
BHP
CFM
BHP
CFM
BHP
CFM
2746
2494
2255
1996
BHP
1.38
1.21
1.06
0.91
CFM
2515
2261
1994
BHP
1.12
0.97
0.83
0.6
0.8
1
2721
2500
2252
2037
1.47
1.32
1.15
1.02
2689
2473
2286
1997
1.56
1.40
1.27
1.08
1.2
1.4
1.6
1.8
2
2752
2487
2308
2014
1.74
1.53
1.40
1.19
2802
2553
2355
2055
1.88
1.67
1.51
1.29
high-statiC Belt drive — down shot
0 Turns
1 Turn
2 Turns
BHP
3 Turns
4 Turns
5 Turns
ESP (In W.C.)
CFM
BHP
CFM
BHP
CFM
2793
2696
2445
2310
2032
CFM
2603
2369
2196
1932
BHP
1.39
1.23
1.12
0.96
CFM
2450
2236
1968
BHP
1.18
1.05
0.90
CFM
2270
1987
BHP
0.97
0.82
0.6
0.8
1
1.64
1.57
1.38
1.29
1.11
2903
1.87
1.69
1.57
1.40
1.19
2776
2599
2424
2172
1953
1.86
1.71
1.57
1.38
1.22
2682.5
2539
2305
2017
1.2
1.4
1.6
1.8
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
17
prodUCt speCifiCations
expanded Cooling data — CpC036
18
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
expanded Cooling data — CpC036 (Cont.)
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
19
prodUCt speCifiCations
expanded Cooling data — CpC048
20
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
expanded Cooling data — CpC048 (Cont.)
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
21
prodUCt speCifiCations
expanded Cooling data — CpC060
22
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
expanded Cooling data — CpC060 (Cont.)
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
23
prodUCt speCifiCations
expanded Cooling data — CpC072
24
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
expanded Cooling data — CpC072 (Cont.)
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
25
prodUCt speCifiCations
dimensions
47¹/₂”
73¹/₄”
3 to 5 Tons: 38¹³/₁₆”
”
6 Tons: 42¹³/₁₆”
74¹/₁₆”
48³/₁₆”
11”
4⁷/₈”
/
7³/₈”
/
17”
19⁷/₁₆”
RETURN
25”
SUPPLY
12”
RETURN
DRAIN
THRU CURB
LOCATION
EMBOSS
FOR
THRU THE
BASE
”
5⁷/₈”
UTILITIES
6 1/4”
SUPPLY
27³/₈”
Horizontal Discharge
4 1/2”
4¹/₂”
8³/₁₆”
7¹/₂”
47¹/₂”
BOTTOM VIEW OF UNIT
Verꢀcal Discharge
26
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
Unit ClearanCes
Maintain an adequate clearance around the unit for safety, service,
maintenance, and proper unit operation. Leave a total clearance
of 75” on the main control panel side of the unit for possible
removal of fan shaft, coil, electric heat, and gas furnace.
Leave a clearance of 48” on all other sides of the unit for
possible compressor removal or service access, and
to ensure proper ventilation and condenser
airflow. Do not install the unit
Beneath any obstruction. Install
the unit away from all building
exhausts to inhibit ingestion of
exhaust air into the unit’s fresh-air
intake.
eleCtriCal entranCe loCations
High-Voltage Entrance
(Remove Plug)
12⅜”
30¼”
Low-Voltage Entrance
3½” Dia.
Power Thru
the Curb
47½”
7½”
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
27
prodUCt speCifiCations
roof CUrB installation — rigging
Provisions for forks have been included in the unit base frame. No other fork
locations are approved.
• Unit must be lifted by the four lifting holes located at the base frame
corners.
• Lifting cables should be attached to the unit with shackles.
• The distance between the crane hook and the top of the unit must not
be less than 60”.
• Two spreader bars must span over the unit to prevent damage to the
cabinet by the lift cables. Spreader bars must be of sufficient length
so that cables do not come in contact with the unit during transport.
Remove wood struts mounted beneath unit base frame before set-
ting unit on roof curb. These struts are intended to protect unit base
frame from fork lift damage. To remove the struts, extract the sheet
metal retainers and pull the struts through the base of the unit.
Refer to rigging label on the unit.
Important: If using bottom discharge with roof curb, duct-work should be
attached to the curb prior to installing the unit. Duct-work dimensions are
shown in Roof Curb Installation Instructions Manual.
Refer to the Roof Curb Installation Instructions for proper curb installation.
Curbing must be installed in compliance with the National Roofing Contractors Association Manual.
Lower unit carefully onto roof mounting curb. While rigging the unit, the center of gravity will cause the condenser end to be lower
than the supply air end.
Bring condenser end of unit into alignment with the curb. With condenser end of the unit resting on curb member and using curb as
a fulcrum, lower opposite end of the unit until entire unit is seated on the curb. When a rectangular cantilever curb is used, take care
to center the unit. Check for proper alignment and orientation of supply and return openings with duct.
To assist in determining rigging requirements, unit weights are shown below.
Corner & Center-of-gravity loCations
3-Ton
4-Ton
5-Ton
6-Ton
Unit Weights
Weights Weights Weights Weights
Corner Weight (A)
Corner Weight (B)
Corner Weight (C)
Corner Weight (D)
Unit Shipping Weight
Unit Operaꢀng Weight
115
150
105
130
525
500
120
150
105
135
540
515
130
160
115
150
580
555
150
190
130
170
665
640
Return
Evaporator Coil
30”
Condenser
Coil
Supply
Note: Weights are calculated without accessories installed.
Compressor
37”
28
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
roof CUrB installation (Cont.)
Curb installations must comply with local codes and should follow the established guidelines of the National Roofing Contractors
Association.
Proper unit installation requires that the roof curb be firmly and permanently attached to the roof structure. Check for adequate
fastening method prior to setting the unit on the curb.
Full perimeter roof curbs are available from the factory and are shipped unassembled. The installing contractor is responsible for
field assembly, squaring, leveling, and mounting on the roof structure. All required hardware necessary for the assembly of the sheet
metal curb is included in the curb accessory package.
• Determine sufficient structural support before locating and mounting the curb and package unit.
• Duct-work must be constructed using industry guidelines. The duct-work must be placed into the roof curb before mounting the
package unit. Our full perimeter curbs include duct connection frames to be assembled with the curb. Cantilevered-type curbs
are not available from the factory.
• Contractor furnishes curb insulation, cant strips, flashing, and general roofing material.
• Support curbs on parallel sides with roof members. To prevent damage to the unit, the roof members cannot penetrate supply
and return duct openings.
Note: The unit and curb accessories are designed to allow Down Shot duct installation before unit placement. Duct installation after
unit placement is not recommended.
See the manual shipped with the roof curb for assembly and installation instructions.
3-d view for Ba models
Insulated
Panels
70¾
40¼
14 x 20
Supply Opening
14
31⅝ x 14
Return Opening
15/6
¾
14
1⅜
top view for Ba models
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
29
prodUCt speCifiCations
wiring diagram — CpC036/48*1d (single phase, direCt driVe)
PU
RD
BK
BK
RD
BL
BL
BR
1
C
2
208
3
240
RD
BK
2
0
8
-
2
4
0
GR
TR
G
R
BL
EBTDR
24V
BL
RD
NO
PB
K1
K1
BL
XFMR-R
XFMR-C
T2
T1
L2
L1
COM
RD
PK
BL
RD
SEE
NOTE #2
M1
C
BK
NC
M2
BK
/
1
/
BR
SPEED
UP
BK
C
BK
S2
S1
TB1
BK
6
0
YL/PK
SMOKE/FIRE DETECTOR
REPLACES JUMPER
GND
YL
BL
OR
PLF 2
GR
3
6
5
4
2
1
RD
YL
1
BK
PU
BK
3
YL
BL
BR
2
PU
GR
RD
C
T
BIR
PU
YL
Y1
WH
H
E
R
M
O
S
T
Y/Y2
R
G
W1
W2
O
PU
RD
GR
WH
BR
OR
PU
3
6
5
4
9
8
7
H
F
RCCF
2
1
BR
BL
BL
BL
C
A
T
TB1
YL
++
PLF 1
BK
BK
BK
RD
RD
BR
RD
CONTROL
BOX
EM
3 SPEED
YL
BL
BL/PK
BC
PU
BK
BR
YL/PK
T3
T2 T1
PU
PU
EM
3 SPEED
ALTERNATE
MOTOR
6-WIRES
BR
BL
CM
RD
PU
HPS
COMP
BK
LPS
BC
SEE TABLE 1
FACTORY WIRING
L1
L2
LINE VOLTAGE
LOW VOLTAGE
SUPPLY VOLTAGE
208-240/1/60
OPTIONAL
HIGH VOLTAGE
COMPONENT LEGEND
FIELD WIRING
BC
BIR
C
CM
COMP
EM
GND
HPS
LPS
PLF
RCCF
BLOWER CAPACITOR
BLOWER INTERLOCK RELAY
CONTACTOR
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
EQUPIMENT GROUND
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
FEMALE PLUG / CONNECTOR
RUN CAPACITOR FOR
CONDENSER FAN
C
T2
HIGH VOLTAGE
LOW VOLTAGE
R
C
T1
C
WIRE CODE
S
BK BLACK
BL BLUE
COMP
BR BROWN
GR GREEN
OR ORANGE
C
RCCF
H
F
PK PINK
PU PURPLE
RD RED
CM
WH WHITE
YL YELLOW
TB1
TR
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP
THERMOSTAT
FIELD WIRING
NOTES:
EM
BR
EBTDR
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST
105°C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE
M1 OR M2 WIRE TO COM TERMINAL ON EBTDR
AND PLACE WIRE REVMOVED FROM COM ON
EMPTY M1 OR M2 TERMINAL.
NO ECONOMIZER
W
G
WH
GR
RD
W
G
R
208-240V
SEE NOTE 3
24V
R
3
1
Y1
Y/Y2
YL
BL
OR
Y2
C
TR
3. FOR 208 VOLT TRANSFORMER OPERATION
MOVE BLACK WIRES FROM TERMINAL
C
O
O
3
TO TERMINAL 2 ON TRANSFORMER.
TB1
STAT
TB1
4. USE COPPER CONDUCTORS ONLY ++ USE N.E.C.
CLASS 2 WIRE
WITH ECONOMIZER OPTION
5. ECONOMIZER PLUG LOCATED IN THE RETURN
AIR COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO ECONOMIZER
ACCESSORY.
BR
W
G
WH
GR
RD
W
G
R
7
8
9
4
R
5
6
6. DIAGRAM SHOWS FACTORY SPEED TAP SETTINGS.
Y1
YL
Y
Y/Y2
C
LPS
C
TABLE 1
TABLE 2
PLF
BL
C
SPEED TAPS
ALTERNATE MOTOR WIRING
COLOR TERMINATION
OR
O
O
STAT
LOW
MED
HIGH
RD
BL
BK
TB1
RD
BK
BL
COM (EBTDR)
M1 (EBTDR)
M2 (EBTDR)
PLF2
HPS
2 STAGE COOLING
6
3
5
2
4
1
W
G
WH
GR
RD
YL
W
G
PU
PIN 1 (24V XFMR)
R
R
R
Y/
Y2
Y1
Y/Y2
C
Y1
G
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
R
O
R
W2 W1
Y1
G
C
PK
BL
Y2
C
SEE NOTE 5
XFMR
C
THERMOSTAT
TB1
OR
O
O
EBTDR
208-240/1/60 0140L00504 REV A
STAT
TB1
30
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
wiring diagram — CpC036/48*3d (three phase, direCt driVe)
PU
BK
RD
BK
BL
BL
BR
1
C
2
208
3
240
RD
BK
2
0
8
-
2
4
0
PB
GR
TR
G
R
BL
EBTDR
24V
BL
RD
T3
T2
L3
L2
YL
RD
NO
K1
K1
BL
XFMR-R
XFMR-C
COM
PK
BL
RD
SEE
C
BK
NOTE #2
NC
M2
BK
BK
T1
L1
/
3
/
BR
S2
SPEED
UP
M1
C
BK
S1
BK
6
0
YL/PK
SMOKE/FIRE DETECTOR
REPLACES JUMPER
TB1
GND
YL
BL
OR
PLF 2
GR
3
6
5
4
2
1
RD
YL
1
BK
PU
BK
3
YL
BL
BR
2
PU
GR
RD
C
BIR
T
PU
YL
Y1
WH
H
E
R
M
O
S
T
Y/Y2
R
G
W1
W2
O
PU
RD
GR
WH
BR
OR
PU
3
6
5
4
9
8
7
FC
F
2
1
BR
BL
BL
BL
C
A
T
TB1
++
PLF 1
BK
BK
BK
RD
RD
BR
RD
CONTROL
BOX
EM
3 SPEED
YL
BL
BL/PK
BC
PU
BK
BR
YL/PK
T3
T2 T1
PU
PU
EM
3 SPEED
ALTERNATE
MOTOR
6-WIRES
BR
BL
CM
RD
PU
HPS
COMP
BK
LPS
BC
SEE TABLE 1
FACTORY WIRING
L3
L1
L2
LINE VOLTAGE
LOW VOLTAGE
SUPPLY VOLTAGE
208-240/3/60
OPTIONAL
HIGH VOLTAGE
COMPONENT LEGEND
FIELD WIRING
BC
BIR
C
CM
COMP
EM
GND
HPS
LPS
PLF
FC
TB1
TR
BLOWER CAPACITOR
BLOWER INTERLOCK RELAY
CONTACTOR
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
EQUPIMENT GROUND
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
FEMALE PLUG / CONNECTOR
FAN CAPACITOR
C
T2
HIGH VOLTAGE
LOW VOLTAGE
T2
C
T1
T1
C
T3
WIRE CODE
T3
BK BLACK
BL BLUE
COMP
BR BROWN
GR GREEN
OR ORANGE
C
F
PK PINK
RCCF
PU PURPLE
RD RED
CM
WH WHITE
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
YL YELLOW
BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP
THERMOSTAT
FIELD WIRING
NOTES:
EM
BR
EBTDR
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST
105°C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE
M1 OR M2 WIRE TO COM TERMINAL ON EBTDR
AND PLACE WIRE REVMOVED FROM COM ON
EMPTY M1 OR M2 TERMINAL.
NO ECONOMIZER
W
G
WH
GR
RD
W
G
R
208-240V
SEE NOTE 3
R
3
1
Y1
Y/Y2
YL
BL
OR
Y2
C
TR
3. FOR 208 VOLT TRANSFORMER OPERATION
MOVE BLACK WIRES FROM TERMINAL
C
O
24V
O
3
TO TERMINAL 2 ON TRANSFORMER.
TB1
STAT
TB1
4. USE COPPER CONDUCTORS ONLY ++ USE N.E.C.
CLASS 2 WIRE
WITH ECONOMIZER OPTION
5. ECONOMIZER PLUG LOCATED IN THE RETURN
AIR COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO ECONOMIZER
ACCESSORY.
BR
W
G
WH
GR
RD
W
G
R
7
8
9
4
R
5
6
6. DIAGRAM SHOWS FACTORY SPEED TAP SETTINGS.
Y1
YL
Y
Y/Y2
C
LPS
C
TABLE 1
TABLE 2
PLF
BL
C
SPEED TAPS
ALTERNATE MOTOR WIRING
COLOR TERMINATION
OR
O
O
STAT
LOW
MED
HIGH
RD
BL
BK
TB1
RD
BK
BL
COM (EBTDR)
M1 (EBTDR)
M2 (EBTDR)
PLF2
HPS
2 STAGE COOLING
6
3
5
2
4
1
W
G
WH
GR
RD
YL
W
G
PU
PIN 1 (24V XFMR)
R
R
R
Y/
Y2
Y1
Y1
G
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
R
O
R
W2 W1
Y1
G
C
PK
BL
Y/Y2
C
Y2
C
SEE NOTE 5
XFMR
C
THERMOSTAT
TB1
OR
O
O
EBTDR
208-240/3/60 0140L00505 REV A
STAT
TB1
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
31
prodUCt speCifiCations
wiring diagram — CpC036-72*3B (three phase, Belt driVe)
2
0
8
-
RD
SMOKE/FIRE DETECTOR
REPLACES JUMPER
BK
BK
BK
TB1
BL
RD
RD
BL
BR
2
3
1
2
4
0
-
RD
GR
240
460
575
RD
208
S2
S1
PK
C
T3
T2
RD
L3
L2
BR
TR
G
R
EBTDR
24V
RD
YL
BL
4
6
0
-
NO
COM
NC
K1
C
BL
BL
XFMR-R
XFMR-C
GR
PU
BK
BK
T1
L1
K1
RD
SEE
NOTE #2
C
5
7
5
/
3
/
NOTE #2
SPEED
UP
RD
M1 M2
BK
YL/PK
OR
GND
YL
PLF 2
OR
GR
6
0
3
2
1
6
5
4
BL
BK
YL
BL
YL
BL
PU
BR
RD
C
LVJB
PU
T
H
E
R
M
O
S
T
WH
Y1
PU
YL
Y/Y2
R
L2
T2
L3
T3
L1
T1
RD
GR
WH
BR
BL
RD
GR
3
2
1
6
9
GR
G
F
C
W1
W2
C
RCCF
5
4
8
7
BR
PU
A
T
BC
OR
O
++
TB1
PLF 1
BL
OR
RD
BK
YL
BK
YL/PK
CONTROL
BOX
RD
PU
BK
BL/PK
BR
T3 T1
T2
LPS
EM
CM
COMP
HPS
FACTORY WIRING
L1
L3
COMPONENT LEGEND
L2
LINE VOLTAGE
LOW VOLTAGE
SUPPLY VOLTAGE
208-240/3/60
BC
C
CM
BLOWER CONTACTOR
CONTACTOR
CONDENSER MOTOR
OPTIONAL
HIGH VOLTAGE
CMR
COMP
DC
DFT
ECON
EBTD
EMR
R
CONDENSER MOTOR RELAY
COMPRESSOR
DEFROST CONTROL
DEFROST THERMOSTAT
ECONOMIZER
ELECTRONIC BLOWER TIME DELAY
EVAPORATOR MOTOR RELAY
RELAY
EVAPORATOR MOTOR
FAN CAPACITOR
EQUPIMENT GROUND
HIGH PRESSURE SWITCH
HIGH VOLTAGE DEFROST RELAY
LOW PRESSURE SWITCH
LOW VOLTAGE DEFROST RELAY
LOW VOLTAGE JUNCTION BOX
POWER DISTRUBTION BLOCK
FEMALE PLUG / CONNECTOR
REVERSING VAVLE COIL
RUN CAPACITOR FOR
FIELD WIRING
C
T2
HIGH VOLTAGE
LOW VOLTAGE
T2
C
T1
COMP
T3
T1
WIRE CODE
C
T3
BK BLACK
BL BLUE
BR BROWN
C
GR GREEN
RCCF
OR ORANGE
PK PINK
EM
FC
F
PU PURPLE
CM
GND
HPS
HVDR
LPS
LVDR
LVJB
PB
PLF
RVC
RCCF
RD RED
WH WHITE
YL YELLOW
BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP
BC
BC
THERMOSTAT
FIELD WIRING
BC
NO ECONOMIZER
EM
COMPRESSOR AND FAN
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
W
G
WH
GR
RD
W
G
R
TB1
TR
208-240V
R
1
3
Y1
YL
BL
OR
Y
C
Y/Y2
C
TB1
TR
O
O
24V
G
EBTDR
STAT
TB1
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)
USE COPPER CONDUCTOR ONLY.
2. USE COPPER CONDUCTORS ONLY
R
C
WITH ECONOMIZER OPTION
W
G
WH
GR
RD
W
G
R
Y
BC
EBTDR
EBTDR
R
R
++ USE N.E.C. CLASS 2 WIRE
Y1
Y/Y2
C
YL
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR
COMPARTMENT, REMOVE MALE PLUG, ATTACH
FEMALE PLUG TO THE ECONOMIZER ACCESSORY.
4. FOR 208 VOLT TRANSFORMER OPERATION MOVE
BL
C
LPS
OR
O
O
STAT
C
BLACK WIRES FROM TERMINAL
ON TRANSFORMER.
3
TO TERMINAL
2
TB1
2 STAGE COOLING
HPS
W
G
WH
GR
RD
YL
W
G
P
L
F
1
4
5
6
6
3
5
2
4
1
R
R
PLF2
G
Y1
Y1
Y2
C
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
PK
BL
Y/Y2
C
Y
Y2
R
W2
O
W1
Y1
C
OR
O
O
TB1
208-240-460-575/3/60 0140L00427 REV. B
SEE NOTE #3
THERMOSTAT
STAT
++
TB1
32
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
wiring diagram — CpC060*1d (single phase, direCt driVe)
RD
SMOKE/FIRE DETECTOR
BK
2
0
8
-
2
4
0
REPLACES JUMPER
RD
TB1
BL
BL
BK
RD
BK
2
208
3
240
1
C
BL
S2
S1
PK
TR
T2
T1
L2
RD
RD
24V
RD
BK
BK
L1
/
1
/
BL
C
YL
6
0
YL/PK
GND
PLF 2
YL
BK
OR
RD
GR
YL
3
2
1
6
5
4
RD
YL
BL
BR
PU
RD
C
LVJB
T
H
E
R
M
O
S
T
PU
Y1
WH
YL
RD
GR
WH
BR
BL
Y/Y2
R
G
W1
W2
C
+O+
YL
WH
GR
WH
PU
GR
3
2
1
6
9
8
7
TB1
RCCF
H
F
1
5
5
4
BR
BL
A
T
OR BR YL
WH PU
OR
TB1
PLF 1
BL
SA (IF USED)
SEE NOTE 4
OR BR YL
WH PU
RD
BK
YL
CONTROL
BOX
1
2
3
4
5
PU
BK
YL/PK
BL/PK
BR
EM
G
T3 T1
T2
C
L
N
GR
CM
HPS
COMP
BK
BL
LPS
RD
FACTORY WIRING
L1
L2
LINE VOLTAGE
LOW VOLTAGE
SUPPLY VOLTAGE
208-240/1/60
OPTIONAL
HIGH VOLTAGE
COMPONENT LEGEND
CONTACTOR
FIELD WIRING
C
CM
C
T2
HIGH VOLTAGE
LOW VOLTAGE
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
EQUPIMENT GROUND
LOW VOLTAGE JUNCTION BOX
FEMALE PLUG / CONNECTOR
RUN CAPACITOR FOR
R
C
T1
COMP
EM
GND
LVJB
PLF
COMP
C
WIRE CODE
S
BK BLACK
BL BLUE
BR BROWN
GR GREEN
OR ORANGE
C
F
RCCF
RCCF
H
COMPRESSOR AND FAN
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
PK PINK
S.A.
TB1
TR
CM
PU PURPLE
RD RED
WH WHITE
IF USED
YL YELLOW
BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP
THERMOSTAT
FIELD WIRING
N
EM
G
L
NO ECONOMIZER
W
G
WH
GR
RD
W
G
R
208-240V
NOTE #3
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)
USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE
WHITE AND YELLOW LEADS FROM "3" AND "4" TO
"4" AND "5". IF BOTH LEADS ARE ENERGIZED, THE
HIGHER SPEED SETTING IS USED.
R
3
1
Y1
YL
BL
OR
Y/Y2
C
Y
C
TR
24V
O
O
TB1
STAT
TB1
WITH ECONOMIZER OPTION
3. FOR 208 VOLT TRANSFORMER OPERATION MOVE
BLACK WIRE FROM TERMINAL 3 TO TERMINAL 2
ON TRANSFORMER.
4. USE COPPER CONDUCTORS ONLY
++ USE N.E.C. CLASS 2 WIRE.
5. ECONOMIZER PLUG LOCATED IN RETURN AIR
COMPARTMENT. REMOVE MALE PLUG AND ATTACH
FEMALE PLUG TO ECONOMIZER ACCESSORY.
W
G
WH
GR
RD
W
G
R
Y
SEE NOTE #2
1
2
3
4
5
EM
C
R
4
Y1
Y/Y2
C
YL
5
6
TB1
LPS
BL
C
PLF
C
OR
O
O
STAT
TB1
2 STAGE COOLING
PLF2
W
G
WH
GR
RD
YL
W
G
HPS
6
3
5
2
4
1
R
R
Y1
Y1
Y2
C
Y
Y2
PK
BL
Y/Y2
C
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
O
C
TB1
W1
G
R
W2
Y1
OR
O
O
THERMOSTAT
208-240/1/60 0140L00426 REV A
STAT
TB1
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
33
prodUCt speCifiCations
wiring diagram — CpC036-72*4B/7B (460V/575V, Belt driVe)
2
0
8
-
RD
SMOKE/FIRE DETECTOR
REPLACES JUMPER
BK
BK
BK
TB1
BL
RD
RD
BL
BR
2
3
1
2
4
0
-
RD
GR
240
460
575
RD
208
S2
S1
PK
C
T3
T2
RD
L3
L2
BR
TR
G
R
EBTDR
24V
RD
YL
BL
4
6
0
-
NO
COM
NC
K1
C
BL
BL
XFMR-R
XFMR-C
GR
PU
BK
BK
T1
L1
K1
RD
SEE
NOTE #2
C
5
7
5
/
3
/
NOTE #2
SPEED
UP
RD
M1 M2
BK
YL/PK
OR
GND
YL
PLF 2
OR
GR
6
0
3
2
1
6
5
4
BL
BK
YL
BL
YL
BL
PU
BR
RD
C
LVJB
PU
T
H
E
R
M
O
S
T
WH
Y1
PU
YL
Y/Y2
R
L2
T2
L3
T3
L1
T1
RD
GR
WH
BR
BL
RD
GR
3
2
1
6
9
GR
G
F
C
W1
W2
C
RCCF
5
4
8
7
BR
PU
A
T
BC
OR
O
++
TB1
PLF 1
BL
OR
RD
BK
YL
BK
YL/PK
CONTROL
BOX
RD
PU
BK
BL/PK
BR
T3 T1
T2
LPS
EM
CM
COMP
HPS
FACTORY WIRING
L1
L3
COMPONENT LEGEND
L2
LINE VOLTAGE
LOW VOLTAGE
SUPPLY VOLTAGE
208-240/3/60
BC
C
CM
BLOWER CONTACTOR
CONTACTOR
CONDENSER MOTOR
OPTIONAL
HIGH VOLTAGE
CMR
COMP
DC
DFT
ECON
EBTD
EMR
R
CONDENSER MOTOR RELAY
COMPRESSOR
DEFROST CONTROL
DEFROST THERMOSTAT
ECONOMIZER
ELECTRONIC BLOWER TIME DELAY
EVAPORATOR MOTOR RELAY
RELAY
EVAPORATOR MOTOR
FAN CAPACITOR
EQUPIMENT GROUND
HIGH PRESSURE SWITCH
HIGH VOLTAGE DEFROST RELAY
LOW PRESSURE SWITCH
LOW VOLTAGE DEFROST RELAY
LOW VOLTAGE JUNCTION BOX
POWER DISTRUBTION BLOCK
FEMALE PLUG / CONNECTOR
REVERSING VAVLE COIL
RUN CAPACITOR FOR
FIELD WIRING
C
T2
HIGH VOLTAGE
LOW VOLTAGE
T2
C
T1
COMP
T3
T1
WIRE CODE
C
T3
BK BLACK
BL BLUE
BR BROWN
C
GR GREEN
RCCF
OR ORANGE
PK PINK
EM
FC
F
PU PURPLE
CM
GND
HPS
HVDR
LPS
LVDR
LVJB
PB
PLF
RVC
RCCF
RD RED
WH WHITE
YL YELLOW
BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP
BC
BC
THERMOSTAT
FIELD WIRING
BC
NO ECONOMIZER
EM
COMPRESSOR AND FAN
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
W
G
WH
GR
RD
W
G
R
TB1
TR
208-240V
R
1
3
Y1
YL
BL
OR
Y
C
Y/Y2
C
TB1
TR
O
O
24V
G
EBTDR
STAT
TB1
NOTES:
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST 105°C)
USE COPPER CONDUCTOR ONLY.
2. USE COPPER CONDUCTORS ONLY
R
C
WITH ECONOMIZER OPTION
W
G
WH
GR
RD
W
G
R
Y
BC
EBTDR
EBTDR
R
R
++ USE N.E.C. CLASS 2 WIRE
Y1
Y/Y2
C
YL
3. ECONOMIZER PLUG LOCATED IN THE RETURN AIR
COMPARTMENT, REMOVE MALE PLUG, ATTACH
FEMALE PLUG TO THE ECONOMIZER ACCESSORY.
4. FOR 208 VOLT TRANSFORMER OPERATION MOVE
BL
C
LPS
OR
O
O
STAT
C
BLACK WIRES FROM TERMINAL
ON TRANSFORMER.
3
TO TERMINAL
2
TB1
2 STAGE COOLING
HPS
W
G
WH
GR
RD
YL
W
G
P
L
F
1
4
5
6
6
3
5
2
4
1
R
R
PLF2
G
Y1
Y1
Y2
C
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
PK
BL
Y/Y2
C
Y
Y2
R
W2
O
W1
Y1
C
OR
O
O
TB1
208-240-460-575/3/60 0140L00427 REV. B
SEE NOTE #3
THERMOSTAT
STAT
++
TB1
34
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
prodUCt speCifiCations
wiring diagram — CpC060*3d (single phase, direCt driVe)
RD
BK
SMOKE/FIRE DETECTOR
BL
BL
RD
RD
REPLACES JUMPER
2
0
8
-
TB1
BK
BK
2
3
1
BL
T3
T2
L3
L2
RD
S2
S1
240
C
208
TR
2
4
0
/
3
/
RD
YL
PK
24V
RD
BK
BK
T1
YL
L1
BL
C
6
0
YL/PK
GND
YL
OR
BK
PLF 2
GR
3
6
5
4
2
1
YL
RD
YL
BL
BR
PU
GR
RD
C
LVJB
T
PU
YL
Y1
GR
WH
H
E
R
M
O
S
T
Y/Y2
R
WH
PU
RD
GR
WH
BR
BL
YL
3
2
1
6
5
4
9
G
F
RCCF
W1
W2
C
WH
TB1
1
8
7
BR
BL
5
O
A
T
OR
BR
PU
OR
WH
YL
YL
TB1
++
BL
PLF 1
BK
BR
OR
WH
PU
YL
BK
CONTROL
BOX
3
4
5
1
2
RD
YL/PK
PU
BK
EM
G
BR
YL
T3 T1
T2
C
L
N
CM
GR
HPS
COMP
BL
BK
LPS
RD
FACTORY WIRING
L3
L1
L2
LINE VOLTAGE
LOW VOLTAGE
SUPPLY VOLTAGE
208-240/1/60
OPTIONAL
HIGH VOLTAGE
COMPONENT LEGEND
CONTACTOR
FIELD WIRING
C
CM
C
T2
HIGH VOLTAGE
LOW VOLTAGE
CONDENSER MOTOR
COMPRESSOR
EVAPORATOR MOTOR
EQUPIMENT GROUND
HIGH PRESSURE SWITCH
LOW PRESSURE SWITCH
T2
T3
C
T1
COMP
EM
GND
HPS
LPS
T1
C
T3
WIRE CODE
BK BLACK
BL BLUE
COMP
C
F
BR BROWN
GR GREEN
OR ORANGE
PK PINK
LVJB
PLF
RCCF
LOW VOLTAGE JUNCTION BOX
FEMALE PLUG / CONNECTOR
RUN CAPACITOR FOR
RCCF
CM
PU PURPLE
RD RED
CONDENSER FAN
TERMINAL BLOCK (24V SIGNAL)
TRANSFORMER
TB1
TR
WH WHITE
YL YELLOW
BL/PK BLUE WITH PINK STRIP
YL/PK YELLOW WITH PINK STRIP
THERMOSTAT
FIELD WIRING
L
N
EM
G
NOTES:
NO ECONOMIZER
W
G
WH
GR
RD
W
G
R
208-240V
SEE NOTE 3
1. REPLACEMENT WIRE MUST BE SAME SIZE AND
TYPE INSULATION AS ORIGINAL (AT LEAST
105°C) USE COPPER CONDUCTOR ONLY.
2. TO CHANGE EVAPORATOR MOTOR SPEED MOVE
WHITE AND YELLOW LEADS FROM "3" AND "4"
TO "4" AND "5". IF BOTH LEADS ARE ENERGIZED,
THE HIGHER SPEED SETTING IS USED.
3. FOR 208 VOLT TRANSFORMER OPERATION
MOVE BLACK WIRES FROM TERMINAL 3 TO
TERMINAL 2 ON TRANSFORMER.
R
3
1
Y1
YL
BL
OR
Y/Y2
C
Y2
C
TR
24V
O
O
TB1
STAT
TB1
WITH ECONOMIZER OPTION
4. USE COPPER CONDUCTORS ONLY ++ USE N.E.C.
CLASS 2 WIRE
5. ECONOMIZER PLUG LOCATED IN THE RETURN
AIR COMPARTMENT. REMOVE MALE PLUG AND
ATTACH FEMALE PLUG TO ECONOMIZER
ACCESSORY.
5
4
3
2
1
N
G
L
W
G
WH
GR
RD
W
G
R
Y
EM
C
R
4
Y1
Y/Y2
C
YL
TB1
5
6
SEE NOTE 2
C
BL
C
LPS
PLF
OR
O
O
STAT
TB1
2 STAGE COOLING
PLF2
HPS
W
G
WH
GR
RD
YL
W
G
6
3
5
2
4
1
R
R
Y1
Y1
Y2
SEE UNIT RATING PLATE FOR TYPE AND SIZE
OF OVER CURRENT PROTECTION
PK
BL
Y/Y2
C
Y/
Y2
O
R
W2 W1
Y1
G
C
TB1
C
SEE NOTE 5
OR
O
O
208-240/3/60 0140L00428 REV B
THERMOSTAT
STAT
TB1
SS-CPC36-72
Download from Www.Somanuals.com. All Manuals Search And Download.
35
prodUCt speCifiCations
aCCessories
Fits
Model Sizes
Item #
Description
14CURB3672B
25FD3672
Roof Curb – 14" Tall
3-6 tons
3-6 tons
3-6 tons
3-6 tons
3 tons
25% Manual Fresh Air Damper
25% Motorized Fresh Air Damper
Horizontal Barometric Relief Damper
Concentric Duct Kit
25MFD3672
BRD3672
CDK36
CDK4872
Concentric Duct Kit
4-6 tons
3-6 tons
3-6 tons
3 tons
DNECONGS3672B
DNECONGS3672B-NR
DNSQRRND36B
DNSQRRND4872B
DNBBS3672B
GHRC-1
Downflow Economizer
Downflow Economizer w/o Barometric Relief
Downflow Square-to-Round Adapter 16" Round
Downflow Square-to-Round Adapter 18" Round
Burglar Bar Sleeves Includes Supply & Return
Hurricane Restraint Clip
4-6 tons
3-6 tons
All Models
3-5 tons
6 tons
HAILGD03
Condenser Coil Hail Guard
Condenser Coil Hail Guard
High-Alꢀtude Kit
HAILGD04
HA-02
All Models
3-5 tons
6 tons
HSKT036B / 048B /0 60B
HSKT072B
High-Staꢀc Kits (230/460v)
High-Staꢀc Kit (230/460v)
HZECONGS3672B
LPM-05
Horizontal Economizer
3-6 tons
3-6 tons
3-6 tons
3-6 tons
LP Conversion Kit
PE36722B
Power Exhaust 208/230v
PE36724B
Power Exhaust 460v
Goodman Manufacturing Company, L.P., reserves the right to discontinue, or change at any time, specifications or designs without notice
or without incurring obligations. © 2011 • Goodman Manufacturing Company, L.P. • Houston, Texas • Printed in the USA.
36
Download from Www.Somanuals.com. All Manuals Search And Download.
SS-CPC36-72
|
Dynex TV Mount DX TVM111 User Manual
Echo Chainsaw X52000020 User Manual
Electro Voice Music Mixer PSX600 User Manual
EVGA Computer Drive 128 P2 KN01 User Manual
Fisher Price Baby Toy B8728 0920 User Manual
FujiFilm Computer Drive DP121 User Manual
FujiFilm Printer DL430 User Manual
GE Air Conditioner ABN12 User Manual
Gemini Musical Instrument CDX O4 User Manual
GE Mouse HO97882 User Manual