Generac Power Systems Portable Generator UL 2200 User Manual

Standby Power Rating  
70 kW 60 Hz  
Liquid Cooled Gas Engine Generator Sets  
Whisper-Test™  
Low Speed Exercise  
61 dB(A) at 23 feet  
GENERAC 6.8L ENGINE  
Naturally Aspirated  
Gaseous Fueled  
UL 2200 Listed  
Transfer Switch is sold separately  
STANDARD EQUIPMENT  
UV/Ozone resistant hoses  
Watertight state of the art electrical connectors  
Mainline circuit breaker  
Oil drain extension to frame rail  
Radiator drain extension  
All input connections in one single area  
High coolant temperature shutdown  
Low oil pressure shutdown  
Low coolant level automatic shutdown  
Low fuel pressure  
Battery charge alternator  
Overspeed automatic shutdown  
Adjustable cranking timer  
Adjustable exercise timer  
Oil drain extension  
Cool flow radiator  
2 Amp static battery charger  
Battery, battery rack and battery cables  
Fan and belt guards  
Isochronous governor  
Flex fuel line pigtail  
Closed coolant recovery system  
FEATURES  
Watertight electrical connectors  
Rodent proof construction  
Innovative design and fully prototype tested  
UL 2200 Listed  
High efficiency, low distortion Generac designed alternator  
Vibration isolated from mounting base  
Matching Generac transfer switches engineered and tested  
to work as a system  
All components easily accessible for maintenance  
Electrostatically applied powder paint  
Built-in kW, kVAR and power factor meters  
Solid state frequency compensated voltage regulator  
Dynamic and static battery charger  
Sound attenuated acoustically designed enclosure  
Whisper-Test™ for low noise level exercise  
Acoustically designed engine cooling system  
High flow low noise factory engineered exhaust system  
State of the art digital control system with H-100 microprocessor  
control panel  
COMMERCIAL SERIES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COMMERCIAL 70 kW  
OPERATING DATA  
KW RATING  
COMMERCIAL SERIES  
COMMERCIAL 70 kW  
70  
ENGINE SIZE  
6.8 Liter V-10  
GENERATOR OUTPUT VOLTAGE/KW - 60 Hz  
120/240V, single phase, 1.0 pf  
120/208V, 3-phase, 0.8 pf  
120/240V, 3-phase, 0.8 pf  
277/480V, 3-phase, 0.8 pf  
KW  
AMP  
CB Size  
70 LP / 68 NG  
70 LP / 68 NG  
70 LP / 68 NG  
70 LP / 68 NG  
291.6 LP / 283.3 NG  
243.1 LP / 236.2 NG  
210.7 LP / 204.7 NG  
105.3 LP / 102.4 NG  
300  
300  
250  
125  
GENERATOR LOCKED ROTOR KVA  
AVAILABLE @ VOLTAGE DIP OF 35%  
Single phase or 208V & 240V 3-phase  
480V 3-phase  
145  
160  
ENGINE FUEL CONSUMPTION (Natural Gas) (Propane)  
Natural Gas  
(ft /hr.)  
110  
260  
499  
696  
1020  
Propane  
3
(gal/hr.)  
1.20  
2.85  
5.46  
7.62  
cu ft/hr  
Exercise cycle  
44.2  
104.9  
200.9  
280.4  
411  
25% of rated load  
50% of rated load  
75% of rated load  
100% of rated load  
11.17  
ENGINE COOLING  
Air flow (inlet air including alternator and combustion air)  
System coolant capacity  
Heat rejection to coolant  
Max. operating air temp. on radiator  
Max. ambient temperature  
3
ft /min.  
5200  
4.5  
287,000  
60 (150)  
50 (140)  
US gal.  
BTU/hr.  
°C (°F)  
°C (°F)  
COMBUSTION AIR REQUIREMENTS  
Flow at rated power 60 Hz  
cfm  
205  
SOUND EMISSIONS IN DBA  
db(A) @ 23 feet in exercise mode  
db(A) @ 23 feet at normal operating load  
61  
65  
EXHAUST  
Exhaust flow at rated output 60 Hz  
Exhaust temp. at muffler outlet  
cfm  
°F  
557  
890  
ENGINE PARAMETERS  
Rated synchronous RPM  
HP at rated KW  
60 Hz  
60 Hz  
1800  
110.7  
POWER ADJUSTMENT FOR AMBIENT CONDITIONS  
Temperature Deration  
3% for every 10 °C above - °C  
1.65% for every 10 °F above - °F  
25  
77  
Altitude Deration  
1% for every 100 m above - m  
3% for every 1000 ft. above - ft.  
183  
600  
RATING: All three phases units are rated at 0.8 power factor. All single phase units are rated at 1.0 power factor. STANDBY RATING: Standby ratings apply to installations served by a reliable utility  
source. The standby rating is applicable to varying loads for the duration of a power outage. There is no overload capability for this rating. Ratings are in accordance with ISO-3046-1. Design and  
specifications are subject to change without notice. Maximum wattage and current are subject to and limited by such factors as fuel Btu content, ambient temperature, altitude, engine power  
and condition, etc.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTERCONNECTIONS  
COMMERCIAL 70 kW  
KW  
70  
70  
70  
70  
VOLTS  
120/240 1  
120/208 3  
120/240 3  
277/480 3  
CB AMPS  
300  
LUG SIZE  
ø
ø
ø
ø
1-600 mcm to 2 - 250 mcm-2- 1/0  
1-600 mcm to 2 - 250 mcm-2- 1/0  
1-600 mcm to 2 - 250 mcm-2- 1/0  
300 mc to #6  
300  
250  
125  
INSTALLATION LAYOUT  
COMMERCIAL SERIES  
Note:  
Door access from  
both sides.  
UNIT WEIGHT: Steel 2185 lbs., Aluminum 2040 lbs.  
GENERAC® POWER SYSTEMS, INC. • P.O. BOX 297 • WHITEWATER, WI 53190  
www.guardiangenerators.com  
Bulletin 0174670SBY / Printed in USA 06.07, 08.07  
Download from Www.Somanuals.com. All Manuals Search And Download.  
© 2007 Generac Power Systems, Inc. All rights reserved. All specifications are subject to change without notice.  

Eclipse Fujitsu Ten Car Stereo System CD8061 User Manual
Euro Pro Mixer KM550E User Manual
Fender Guitar PS 210 User Manual
Fender Musical Instrument Amplifier 400 User Manual
Frontier Labs Computer Monitor Lite Pro User Manual
Fujitsu Camcorder CG 301 User Manual
Fundex Games Games Chicken Coop User Manual
Garmin GPS Receiver 190 01492 00 0B User Manual
GE Indoor Furnishings 45602 User Manual
GE Indoor Furnishings G85 User Manual