Generac Power Systems Portable Generator 004373 6 User Manual |
Owner’s Manual
Liquid-cooled, Prepackaged
Standby Generators
Models: 004373-6
(40 kW/Single-phase w/
200 Amp Transfer
Switch)
004626-5
(40 kW/Single-phase w/
200 Amp Transfer
Switch California
Emissions)
Not intended for use in critical life support applications.
!
!
ONLY QUALIFIED ELECTRICIANS OR CONTRACTORS SHOULD ATTEMPT
INSTALLATION!!
DEADLY EXHAUST FUMES. OUTDOOR INSTALLATION ONLY!
This manual should remain with the unit.
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of Contents
Guardian Liquid-cooled 40 kW Generator
Introduction ........................Inside Front Cover
Read This Manual Thoroughly ............................IFC
Contents..............................................................IFC
Operation and Maintenance ................................IFC
How to Obtain Service ........................................IFC
Authorized Dealer Locator Number ........................IFC
Section 3 – Operation ....................................12
3.1 Control Console Components ......................12
3.2 Using the Auto/Off/Manual Switch................12
3.3 Automatic Transfer Operation ....................13
3.4 Sequence of Automatic Operation................13
3.5 Engine Heater ................................................13
3.6 Weekly Exercise Cycle..................................14
Safety Rules ........................................................2
Section 1 – General Information ..................4
Section 4 – Maintenance ..............................14
4.1 Checking the Engine Oil Level......................14
4.2 Changing the Engine Oil and Filter ..............15
4.3 Changing the Engine Air Cleaner ................15
4.4 Spark Plugs ................................................16
4.5 Battery Maintenance ....................................16
4.6 Cooling System ............................................16
1.1 Unpacking/Inspection ....................................4
1.2 The Generator................................................4
1.3 Generator AC Connection Systems ................4
1.4 Prepackaged Transfer Switch ........................4
1.5 Automatic System Operation ........................4
1.6 Main Circuit Breaker ....................................5
1.7 Engine Protective Devices ..............................5
1.8 Specifications ................................................5
4.7 Overload Protection for
Engine DC Electrical System ......................17
1.9 Fuel Requirements and
4.8 DC Fuse ......................................................17
4.9 Engine Coolant ............................................17
4.10 Miscellaneous Maintenance..........................17
4.11 Out of Service Procedure ............................18
4.12 Service Schedule..........................................19
Recommendations..........................................6
1.10 Engine Oil Recommendations........................7
1.11 Coolant ..........................................................7
1.12 Emission Control System ..............................7
Section 2 – Installation ....................................8
2.1 Basic Standby Electric System ......................8
Section 5 – Troubleshooting ........................20
5.1 Troubleshooting Guide ................................20
2.2 Emergency Circuit Isolation Method..............9
2.3 Total Circuit Isolation Method........................9
2.4 Grounding the Generator ..............................9
2.5 Generator AC Neutral Connections................9
2.6 Transfer Switch Start Signal Connections ....9
2.7 Battery Installation ......................................10
2.8 Preparation Before Start-up ........................11
Section 6 – Installation Diagram ................21
Section 7 – Electrical Data ............................22
Section 8 – Exploded Views and
Parts Lists....................................30
Section 9 – Notes ............................................58
Section 10 – Warranty ....................................60
®
Generac Power Systems, Inc.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
IMPORTANT SAFETY INSTRUCTIONS
Guardian Liquid-cooled 40 kW Generator
SAVE THESE INSTRUCTIONS – The manufacturer suggests that these rules for safe
operation be copied and posted in potential hazard areas. Safety should be stressed to all
operators and potential operators of this equipment.
!
!
!
!
SAVE THESE INSTRUCTIONS – This manual contains important instructions that should be
followed during installation and maintenance of the generator and batteries.
!
!
!
GENERAL HAZARDS
!
WARNING:
The engine exhaust from this product
contains chemicals known to the state
of California to cause cancer, birth
defects or other reproductive harm.
• For safety reasons, Generac recommends that the
installation, initial start-up and maintenance of this
equipment is carried out by a Generac/Guardian
Authorized Dealer.
• Installation, operation, servicing and repair of this
(and related) equipment must always comply with
applicable codes, standards, laws and regulations.
Adhere strictly to local, state and national electrical
and building codes. Comply with regulations the
Occupational Safety and Health Administration
(OSHA) has established. Also, ensure that the gener-
ator is installed, operated and serviced in accordance
with the manufacturer’s instructions and recommen-
dations. Following installation, do not do anything
that might render the unit unsafe or in noncompli-
ance with the aforementioned codes, standards, laws
and regulations.
!
!
WARNING:
This product contains or emits chemicals
known to the state of California to cause
cancer, birth defects or other reproductive harm.
Study these SAFETY RULES carefully before installing,
operating or servicing this equipment. Become familiar
with this Owner’s Manual and with the unit. The gen-
erator can operate safely, efficiently and reliably only if
it is properly installed, operated and maintained. Many
accidents are caused by failing to follow simple and fun-
damental rules or precautions.
• The engine exhaust fumes contain carbon monoxide,
which can be DEADLY. This dangerous gas, if
breathed in sufficient concentrations, can cause
unconsciousness or even death. For that reason, ade-
quate ventilation must be provided. Exhaust gases
must be piped safely away from any building or
enclosure that houses the generator to an area where
people, animals, etc., will not be harmed. This
exhaust system must be installed properly, in strict
compliance with applicable codes and standards.
• Keep hands, feet, clothing, etc., away from drive belts,
fans, and other moving or hot parts. Never remove
any drive belt or fan guard while the unit is operating.
• Adequate, unobstructed flow of cooling and ventilating
air is critical in any room or building housing the gen-
erator to prevent buildup of explosive gases and to
ensure correct generator operation. Do not alter the
installation or permit even partial blockage of ventila-
tion provisions, as this can seriously affect safe oper-
ation of the generator.
Generac cannot possibly anticipate every possible
circumstance that might involve a hazard. The warn-
ings in this manual, and on tags and decals
affixed to the unit are, therefore, not all-inclusive. If
using a procedure, work method or operating technique
Generac does not specifically recommend, satisfy your-
self that it is safe for others. Also make sure the proce-
dure, work method or operating technique chosen does
not render the generator unsafe.
DANGER
Despite the safe design of this generator,
operating this equipment imprudently, neglecting
!
its maintenance or being careless can cause possi-
ble injury or death. Permit only responsible and
capable persons to operate or maintain this
equipment.
Potentially lethal voltages are generated by these
machines. Ensure all steps are taken to render the
machine safe before attempting to work on the
generator.
• Keep the area around the generator clean and unclut-
tered. Remove any materials that could become haz-
ardous.
• When working on this equipment, remain alert at all
times. Never work on the equipment when physically
or mentally fatigued.
Parts of the generator are rotating and/or hot
during operation. Exercise care near running gen-
!
erators.
®
2
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Important Safety Instructions
Guardian Liquid-cooled 40 kW Generator
• Inspect the generator regularly, and promptly repair • Generators installed with an automatically transfer
or replace all worn, damaged or defective parts using
only factory-approved parts.
• Before performing any maintenance on the generator,
disconnect its battery cables to prevent accidental
start-up. Disconnect the cable from the battery post
indicated by a NEGATIVE, NEG or (–) first.
Reconnect that cable last.
• Never use the generator or any of its parts as a step.
Stepping on the unit can stress and break parts, and
may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
switch will crank and start automatically when NOR-
MAL (UTILITY) source voltage is removed or is below
an acceptable preset level. To prevent such automat-
ic start-up and possible injury to personnel, disable
the generator’s automatic start circuit (battery cables,
etc.) before working on or around the unit. Then,
place a “Do Not Operate” tag on the generator control
panel and on the transfer switch.
• In case of accident caused by electric shock, immedi-
ately shut down the source of electrical power. If this
is not possible, attempt to free the victim from the
live conductor. AVOID DIRECT CONTACT WITH THE
VICTIM. Use a nonconducting implement, such as a
dry rope or board, to free the victim from the live
conductor. If the victim is unconscious, apply first aid
and get immediate medical help.
• Never wear jewelry when working on this equipment.
Jewelry can conduct electricity resulting in electric
shock, or may get caught in moving components
causing injury.
ELECTRICAL HAZARDS
• All generators covered by this manual produce dan-
gerous electrical voltages and can cause fatal electri-
cal shock. Utility power delivers extremely high and
dangerous voltages to the transfer switch as does the
standby generator when it is in operation. Avoid con-
tact with bare wires, terminals, connections, etc.,
while the unit is running. Ensure all appropriate cov-
ers, guards and barriers are in place before operating
the generator. If work must be done around an oper-
ating unit, stand on an insulated, dry surface to
reduce shock hazard.
• Do not handle any kind of electrical device while
standing in water, while barefoot, or while hands or
feet are wet. DANGEROUS ELECTRICAL SHOCK
MAY RESULT.
• If people must stand on metal or concrete while
installing, operating, servicing, adjusting or repairing
this equipment, place insulative mats over a dry
wooden platform. Work on the equipment only while
standing on such insulative mats.
FIRE HAZARDS
• Keep a fire extinguisher near the generator at all
times. DO NOT use any carbon tetra-chloride type
extinguisher. Its fumes are toxic, and the liquid can
deteriorate wiring insulation. Keep the extinguisher
properly charged and be familiar with its use. If there
are any questions pertaining to fire extinguishers,
consult the local fire department.
EXPLOSION HAZARDS
• The National Electrical Code (NEC) requires the
frame and external electrically conductive parts of the
generator to be connected to an approved earth
ground and/or grounding rods. This grounding will
help prevent dangerous electrical shock that might be
caused by a ground fault condition in the generator
set or by static electricity. Never disconnect the
ground wire.
• Properly ventilate any room or building housing the
generator to prevent build-up of explosive gas.
• Do not smoke around the generator. Wipe up any fuel
or oil spills immediately. Ensure that no combustible
materials are left in the generator compartment, or
on or near the generator, as FIRE or EXPLOSION
may result. Keep the area surrounding the generator
clean and free from debris.
• Wire gauge sizes of electrical wiring, cables and cord
sets must be adequate to handle the maximum elec- • Generac generator sets may operate using one of sev-
trical current (ampacity) to which they will be sub-
eral types of fuels. All fuel types are potentially FLAM-
MABLE and/or EXPLOSIVE and should be handled
with care. Comply with all laws regulating the storage
and handling of fuels. Inspect the unit’s fuel system
frequently and correct any leaks immediately. Fuel
supply lines must be properly installed, purged and
leak tested according to applicable fuel-gas codes
before placing this equipment into service.
jected to.
• Before installing or servicing this (and related) equip-
ment, make sure that all power voltage supplies are
positively turned off at their source. Failure to do so will
result in hazardous and possibly fatal electrical shock.
• Connecting this unit to an electrical system normally
supplied by an electric utility shall be by means of a
transfer switch so as to isolate the generator electric
system from the utility electric system while in oper-
ation. Failure to isolate the two electric system power
sources from each other by such means will result in
damage to the generator and may also result in injury
or death to utility power workers due to backfeed of
electrical energy.
• Diesel fuels are highly FLAMMABLE. Gaseous fluids
such as natural gas and liquid propane (LP) gas are
extremely EXPLOSIVE. Natural gas is lighter than air,
and LP gas is heavier than air; install leak detectors
accordingly.
®
Generac Power Systems, Inc.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1 — General Information
Guardian Liquid-cooled 40 kW Generator
the two windings are connected in series, a 240VAC, 60-
Hertz output results. Typically, the two “hot” leads in the
circuit are Wires 11 and 44. The neutral leads are the
junction of Wires 22 and 33.
1.1 UNPACKING/INSPECTION
After unpacking, carefully inspect the contents for dam-
age.
• This standby generator set has been factory installed
in an all-weather, metal enclosure that is intended
exclusively for outdoor installation.
Figure 1.1 – Single-phase
Generator AC Connection System
If this generator is used to power electrical load
circuits normally powered by a utility power
source, code requires to install a transfer switch.
The transfer switch must effectively isolate the
electrical system from the utility distribution sys-
tem when the generator is operating (NEC 701).
Failure to isolate an electrical system by such
means will result in damage to the generator and
also may result in injury or death to utility power
workers due to backfeed of electrical energy.
Neutral Block
If any loss or damage is noted at time of delivery, have
the person(s) making the delivery note all damage on
the freight bill or affix his or her signature under the
consignor's memo of loss or damage.
1.4 PREPACKAGED TRANSFER SWITCH
The transfer switch shipped with this generator is rated
200 amps maximum at 120/240VAC single-phase. The
enclosure of the transfer switch is NEMA 3R. This type
of enclosure is intended for outdoor use but it can be
mounted indoors. It also protects enclosed parts from
windblown dust and water. The enclosure is sealed for
dust, rain or sleet and is ice resistant.
If there is loss or damage after delivery, separate the
damaged materials and contact the carrier for claim
procedures.
“Concealed damage” is understood to mean damage to
the contents of a package that is not in evidence at the
time of delivery, but is discovered later.
Follow these rules:
• Install the transfer switch on a firm, sturdy support-
ing structure.
1.1.1 LIFTING THE GENERATOR
• To prevent switch distortion, level the switch if nec-
essary. This can be done by placing washers between
the switch enclosure and mounting surface.
• Never install the switch where any corrosive sub-
stance might drop onto the enclosure.
• Where practical, protect the switch against excessive
moisture, dust, dirt, lint, and construction grit.
Always prevent corrosive vapors from coming in con-
tact with enclosure.
‹
When lifting or hoisting equipment is used, be
careful not to touch overhead power lines.
The generator’s weight of more than 2,000
pounds requires proper tools and equipment, and
qualified personnel to be used in all phases of
handling and unpacking.
!
1.5 AUTOMATIC SYSTEM OPERATION
When this generator, along with its transfer switch, has
been installed and interconnected, a circuit board in the
generator panel continuously monitors utility power
source voltage. Should that voltage drop below a preset
value, and remain at such a low state for a preset amount
of time, the generator cranks and starts. After the gener-
ator starts, the transfer switch transfers load circuits so
the generator can power them.
1.2 THE GENERATOR
This liquid-cooled, Guardian generator set is designed
to supply electrical power to operate critical electrical
loads during utility power failure. Use this generator as
a source of electrical power for the operation of 120
and/or 240VAC, single-phase loads.
1.3 GENERATOR AC
When utility source voltage has been restored, the
switch transfers back to the utility source voltage, and
the generator then shuts down after a brief cool-down
time.
CONNECTION SYSTEMS
Figure 1.1 represents a single-phase, four-wire genera-
tor AC connection system. The stator assembly in this
system consists of a pair of stationary windings with
two leads brought out of each winding. Each single
winding can supply a 120VAC, 60-Hertz output. When
®
4
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1 — General Information
Guardian Liquid-cooled 40 kW Generator
1.7.3 LOW COOLANT LEVEL SWITCH
‹
1.6 MAIN CIRCUIT BREAKER
The generator’s main circuit breaker is included with the
unit as shipped from the factory. The breaker for each
unit is described as follows:
Should the engine coolant level drop below the level of the
high coolant temperature switch, it is possible for the
engine to overheat without automatic shut down. To pre-
vent such overheating without automatic shut down, the
engine has a low coolant level sensor. If the engine coolant
drops too low, the engine automatically shuts down
(Figure 1.2).
Model Number
0043736
Circuit Breaker Rating
200-amp breaker
0046265
200-amp breaker
1.7 ENGINE PROTECTIVE DEVICES
1.7.4 OVERSPEED SHUTDOWN
‹
The engine has several safety switches that cause
it to automatically shut down under the following condi-
tions: low oil pressure, high coolant temperature, low
coolant level, engine overspeed and overcrank.
The control module assembly (CMA) circuit board on
liquid-cooled units receives AC frequency (rpm) signals
directly from the stator AC power windings. Should AC
frequency exceed approximately 72 Hertz, circuit board
action will automatically shut down the engine.
1.7.1 LOW OIL PRESSURE SWITCH
‹
This switch is normally closed (N.C.) but is held open by
engine oil pressure during engine running. Should oper-
ating oil pressure drop below approximately 10 psi (68
kPa), the switch contacts close, and the engine shuts down
automatically (Figure 1.2).
1.7.5 OVERCRANK SHUTDOWN
‹
After 90 seconds of crank-rest cycles (about seven sec-
onds cranking/seven seconds at rest), this function ends
cranking if the engine fails to start in that 90-second
span.
Figure 1.2 – Engine Protective Devices
1.7.6 DC FUSE
‹
This fuse is located on the front panel of the control sys-
tem. It protects the panel wiring and components from
damaging overload. Always remove this fuse before
commencing work on the generator. The unit will not
start or crank if the fuse is blown. Replace the fuse with
one of the same size, type, and rating. Generac uses an
AGC fuse rated at 15 amps.
1.8 SPECIFICATIONS
1.8.1 GENERATOR
◆
Models ..............................................0043736, 0046265
Rated Maximum Continuous
AC Power Output (kW)*..................................................40
Rated Voltage (volts) ................................................120/240
Rated Maximum Continuous
Current at 240 Volts, Single-phase (amps)................................167
Number of Rotor Poles ........................................................4
Driven Speed of Rotor (rpm) ........................................1,800
Type of Stator ........................................................Four-wire
Rotor Excitation System..................................Direct Excited
Brush-type System
Stator Insulation ....................................................Class “H”
Rotor Insulation ......................................................Class “F”
*Rated power of generator is subject to and limited by such factors as ambient tempera-
ture, altitude, engine condition and other factors. Engine power will decrease about 3.5
percent for each 1,000 feet above sea level; and also will decrease an additional 1 percent
for each 6° C (10° F) above 15.5° C (60° F) ambient. Maximum output power of the gener-
ator is limited by maximum engine power.
1.7.2 HIGH COOLANT TEMPERATURE SWITCH
‹
This normally open (N.O.) thermostatic switch has a
sensing tip that is immersed in captive coolant. Should
the coolant temperature exceed approximately 121° C
(250° F), the switch contacts close, which causes the
engine to shut down automatically (Figure 1.2).
®
Generac Power Systems, Inc.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1 — General Information
Guardian Liquid-cooled 40 kW Generator
1.8.2 GENERATOR AND LOAD COMPATIBILITY
The generator must be fully compatible with the rated
voltage, number of phases and frequency of the con-
nected electrical loads. The generator, connected elec- type of system uses the vapors formed above the liquid
trical devices, or both, can be damaged if voltage, num-
ber of phases and frequency are not compatible.
‹
1.9 FUEL REQUIREMENTS
AND RECOMMENDATIONS
With LP gas, use only the vapor withdrawal system. This
fuel in the storage tank.
Recommended fuels should have a Btu content of at
least 1,000 Btus per cubic foot for natural gas, or at
least 2,520 Btus per cubic foot for LP gas. Ask the fuel
supplier for the Btu content of the fuel.
NOTE:
This manual assumes that the standby generator has
been properly selected, installed and interconnected
by a competent, qualified electrician or installation
contractor. Once the installation is complete, do
nothing that may result in noncompatibility between
the generator and connected electrical loads.
Fuel pressure for both natural gas and liquid propane
setups should be 11 inches to 14 inches of water column
(0.6 psi) at all load ranges.
Gaseous fuels such as natural gas and liquid
propane (LP) gas are highly explosive. Even the
slightest spark can ignite such fuels and cause an
explosion. No leakage of fuel is permitted. Natural
gas, which is lighter than air, tends to collect in
high areas; LP gas is heavier than air and tends to
settle in low areas – install leak detectors accord-
ingly.
1.8.3 ENGINE
‹
Make ............................................................General Motors
Displacement ......................................4.3 liters (262 cu. in.)
Cylinder Arrangement ......................................................V-6
Valve Arrangement ......................................Overhead Valves
Firing Order ........................................................1-6-5-4-3-2
Number of Main Bearings....................................................4
Compression Ratio....................................................9.4-to-1
No. of Teeth on Flywheel..................................................168
Ignition System......................................................Electronic
Ignition Timing at 1,800 rpm ....................40 degrees BTDC
Rated Horsepower at 1,800 rpm ......................................67
Spark Plug Gap ....................................0.045 inch (1.1 mm)
Recommended Spark Plugs ............AC 41-932 or equivalent
Oil Pressure............................................................30-50 psi
Crankcase Oil Capacity ....................4.5 U.S. quarts (4.25 L)
Recommended Engine Oil..................................SAE 15W-40
Type of Cooling System ............Pressurized, closed recovery
Cooling Fan ........................................................Pusher Type
Cooling System Capacity ....................4.5 U.S. gallons (17 L)
Recommended Coolant........................Use a 50-50 mixture of
ethylene glycol and
1.9.1 CONVERSION TO LP GAS VAPOR
The generator is shipped from the factory configured for
using natural gas as fuel. To convert the fuel system to LP
gas, proceed as follows (Figure 1.3).
‹
1. Remove end cap from the pressure reducer valve.
2. Turn the tension screw counterclockwise until all ten-
sion is removed from the inner spring.
3. Install and tighten the end cap.
4. Invert the pressure reducer valve. In other words, turn
it upside down (end cap facing downward).
5. Purge and leak test the entire fuel system according to
gaseous fuel codes. NO LEAKS can appear at any point
in the system.
deionized water.
Fuel Consumption
Figure 1.3 – Conversion to LP Gas Vapor
Natural Gas ..............................................................720 cfh
LP Gas ..........................................................288 cfh/7.9gph
®
6
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 1 — General Information
Guardian Liquid-cooled 40 kW Generator
1.10 ENGINE OIL RECOMMENDATIONS
The unit has been filled with 15W-40 engine oil at the
factory. Use a high-quality detergent oil classified “For
Service CC, SD, SE or SF.” Detergent oils keep the
engine cleaner and reduce carbon deposits. Use oil hav-
ing the following SAE viscosity rating, based on the
ambient temperature range anticipated before the next
oil change:
1.12 EMISSIONS CONTROL SYSTEM
(MODEL 0046265)
This model is equipped with an active exhaust emis-
sions control system to comply with certain California
air district regulations for natural gas emergency gener-
ating sets, including the South Coast Air Quality
Management District. DO NOT tamper with or disable
any part of this system, including the exhaust catalyst,
carburetor, oxygen sensor, air-fuel ratio controller, sole-
noid valve and gas regulator. These items are not sub-
ject to periodic maintenance or adjustment.
Temperature
Above 80º F (27º C)
Oil Grade(Recommended)
SAE 30W or 15W-40
SAE 20W-20 or 15W-40
SAE 10W or 15W-40
32º to 80º F (-1º C to 27º C)
Below 32º F (0º C)
This model is of a size (greater than 50 brake horse-
power) that may require a review by air permitting
authorities prior to installation and operation. Consult
the local air management district for details and spe-
cific requirements.
Any attempt to crank or start the engine before it
has been properly serviced with the recommended
oil may result in an engine failure.
!
Figure 1.4 - Emissions Control System
1.11 COOLANT
Use a mixture of half low silicate, ethylene glycol base
antifreeze and half deionized water. Use only deionized
water and only low silicate antifreeze. If desired, add a
high quality rust inhibitor to the recommended coolant
mixture. When adding coolant, always add the recom-
mended 50-50 mixture.
DANGER
Do not remove the radiator pressure cap while
the engine is hot or serious burns from boiling
liquid or steam could result.
!
1.12.1 AIR FUEL RATIO CONTROLLER
‹
Ethylene glycol base antifreeze is poisonous. Do
not use mouth to siphon coolant from the radia-
tor, recovery bottle or any container. Wash
hands thoroughly after handling. Never store
used antifreeze in an open container because
animals are attracted to the smell and taste of
antifreeze even though it is poisonous to them.
The air fuel ratio controller is an advanced micro-
processor designed to work with a three-way catalyst
and a feedback (rich bias) carburetor to provide close-
loop fuel management. Its digital adaptive control is
able to compensate for variations in fuel mixtures and
engine tunes. It is time based activated. (For example, it
will activate after 45 seconds from receiving the power
signal.) The part number for the air fuel ratio controller
is 0D4221.
!
Do not use any chromate base rust inhibitor
with ethylene glycol base antifreeze, or chromi-
um hydroxide (“green slime”) will form and
!
cause overheating. Engines that have been oper-
ated with a chromate base rust inhibitor must
be chemically cleaned before adding ethylene
glycol base antifreeze. Using any high silicate
antifreeze boosters or additives also will cause
overheating. Generac also recommends that any
soluble oil inhibitor NOT be used for this equip-
ment.
Principle of Operation: The oxygen sensor, installed
on the exhaust pipe, between the engine and the cat-
alytic muffler (closer to the engine), continuously moni-
tors the exhaust gas composition. A feedback signal is
sent from the oxygen sensor to the air fuel ratio con-
troller, which controls the fuel system to maintain the
optimal, stoichiometric air fuel ratio. The air fuel mix-
ture to the engine is controlled by biasing the
diaphragm in the fuel regulator using vacuum (from the
carburetor). This vacuum signal is directed to the fuel
regulator via the control valve. The air fuel ratio con-
troller determines the amount of vacuum signal sent to
the fuel regulator. The more vacuum sent to the regula-
tor, the more restricted the fuel flow will be, therefore
the leaner the air fuel mixture.
®
Generac Power Systems, Inc.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2 — Installation
Guardian Liquid-cooled 40 kW Generator
STANDBY GENERATOR INSTALLATION
DANGER
Connecting this generator to an electrical system normally supplied by an electric utility shall be by
means of a transfer switch (such as the Generac “Pre-packaged” type transfer switch), so as to isolate
the electric system from the utility distribution system when the generator is operating. Failure to
isolate the electric system by these means will result in damage to the generator and may also result
in injury or death to utility workers due to backfeed of electrical energy.
OTHER PUBLISHED STANDARDS
◆
In addition to NFPA standards, the following informa-
tion pertaining to the installation and use of standby
electric systems is available:
If an open bottom is used, the engine-generator is
to be installed over non-combustible materials
and should be located such that combustible
materials are not capable of accumulating under
the generator set.
• Article X, NATIONAL BUILDING CODE, available
from the American Insurance Association, 85 John
Street, New York, N.Y. 10038.
• AGRICULTURAL WIRING HANDBOOK, obtainable
from the Food and Energy Council, 909 University
Avenue, Columbia, MO, 65201.
• ASAE EP-364.2, INSTALLATION AND MAINTE-
NANCE OF FARM STANDBY ELECTRIC POWER,
available from the American Society of Agricultural
Engineers, 2950 Niles Road, St. Joseph, MI 49085.
• A52.1, AMERICAN NATIONAL STANDARD FOR
CHIMNEYS, FIREPLACES AND VENTING SYS-
TEMS, available from the American National
Standard Institute, 1430 Broadway, New York, N.Y.
10018.
Only qualified, competent installation contractors or
electricians thoroughly familiar with applicable codes,
standards and regulations should install this standby
electric power system. The installation must comply
strictly with all codes, standards and regulations per-
taining to the installation.
This genset must be installed on a level surface. The
base frame must be level within 1/2 inch all around.
After the system has been installed, do nothing that
might render the installation in noncompliance with
such codes, standards and regulations.
NOTE:
For more information about the installation of a stand-
by system, order Engine-Generator Standby Electric
Power Systems Installer’s Guide and Reference
Manual (part #046622) from a Generac Authorized
Service Dealer.
• NEC HANDBOOK available from the National Fire
Protection Association, 1 Batterymarch Park,
PO Box 9146, Quincy, MA 02269-9959.
2.1 BASIC STANDBY ELECTRIC SYSTEM
Figure 2.1 shows a schematic diagram of a basic stand-
by electric system. Both the UTILITY power supply and
the STANDBY (EMERGENCY) output are connected to
an approved transfer switch. The transfer switch is
required by electrical code and serves the following
functions:
NFPA STANDARDS
◆
The following published standards booklets pertaining
to standby electric systems are available form the
National Fire Protection Association (NFPA),
Batterymarch Park, Quincy, MA 02269:
• Permits the LOAD circuits to be connected to only one
power supply at a time.
• Prevents electrical backfeed between STANDBY
• NFPA No. 37, STATIONARY COMBUSTION ENGINES
AND GAS TURBINES.
power and the UTILITY power circuits.
Notice that both the STANDBY and the UTILITY power
supplies to the transfer switch are protected against
overload by a main line circuit breaker.
• NFPA No. 76A, ESSENTIAL ELECTRICAL SYSTEMS
FOR HEALTH CARE FACILITIES.
• NFPA No. 220, STANDARD TYPES OF BUILDING
CONSTRUCTION
NOTE:
• NFPA No. 68, GUIDE FOR EXPLOSION VENTING
• NFPA No. 70, NATIONAL ELECTRICAL CODE.
• NFPA No. 30, FLAMMABLE AND COMBUSTIBLE
LIQUIDS CODE.
Generac recommends the use of a Generac Power
Systems “pre-packaged” type transfer switch (Part
No. 0E5782) in conjunction with this generator.
• NFPA No. 10, INSTALLATION, MAINTENANCE AND
USE OF PORTABLE FIRE EXTINGUISHERS.
®
8
Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2 — Installation
Guardian Liquid-cooled 40 kW Generator
Figure 2.1 – Basic Standby Electric System
DANGER
Do not connect the ground wire to any pipe that
carries a flammable or explosive substance – FIRE
or an EXPLOSION may result.
Proper grounding helps protect personnel against electri-
cal shock in the event of a ground fault condition in the
generator or in connected electrical devices. In addition,
grounding helps dissipate static electricity that often
builds up in ungrounded devices.
Figure 2.2 – Generator Grounding Lug (typical)
2.2 EMERGENCY CIRCUIT ISOLATION
METHOD
This method prevents overloading the generator by
keeping electrical loads below the wattage/amperage
capacity of the generator. If the generator is powering
only critical loads, within its wattage/amperage capacity,
during utility power outages, consider using the emer-
gency circuit isolation method.
Critical electrical loads are grouped together and wired
into a separate “Emergency Distribution Panel.” Load
circuits powered by that panel are within the
wattage/amperage capacity of the generator set. When
this method is used, it is difficult to overload the gener-
2.5 GENERATOR AC NEUTRAL
CONNECTIONS
ator. The transfer switch must meet the following Generac uses an UNGROUNDED AC neutral. Grounding
requirements:
is recommended only at the main service entrance.
• It must have an ampere rating equal to or greater
than the total amperage rating of the emergency dis-
tribution panel circuit.
2.6 TRANSFER SWITCH START SIGNAL
CONNECTIONS
• It must be installed between the building’s main distri-
‹
2.6.1 PRE-PACKAGED TYPE SWITCH
bution panel and the emergency distribution panel.
Connect the six signal wires from the automatic trans-
fer switch to the engine generator control, which is
located on the upper right side and inside the lower
control panel. Match wires 23, 194, N1, N2, T1 and T2
in the transfer switch to the corresponding wires on the
terminal strip in the lower panel. The conductors for
these wires should be in a separate conduit from the
main AC output wires.
2.3 TOTAL CIRCUIT ISOLATION METHOD
When a generator capable of powering all electrical
loads in the circuit is to be installed, use the “Total
Circuit Isolation Method.” It is possible for the genera-
tor to be overloaded when this isolation method is
employed. The following apply to the transfer switch in
this type of system.
• Ampere rating of the transfer switch must be equal to
or greater than the ampere rating of the normal
incoming utility service.
‹
2.6.2 “GTS” Type Engineered Switch
Connect the two-wire start signal from the automatic
transfer switch to the automatic start connection, which is
located in the right hand corner inside the lower panel.
Match wires 178 and 183 in the transfer switch to 178
and 183 on the terminal strip in the control panel. The
conductors for the two-wire start circuit must be in their
own conduit.
• The transfer switch must be installed between the
utility service disconnect circuit breaker and the
building distribution panel.
2.4 GROUNDING THE GENERATOR
The National Electrical Code requires the frame and
external electrically conductive parts of this equipment
to be properly connected to an approved earth ground
and/or grounding rods. For that purpose, a GROUND
LUG (Figure 2.2) is provided on the generator mounting
base. Consult a qualified electrician for grounding
requirements in the area. Grounding procedures must
meet local regulations.
NOTE:
When using a GTS switch, it is necessary to connect
a 240V AC supply to N1 and N2 terminals
of the generator to provide for battery charging.
Wires T1, T2, 23 and 194 should not be
connected.
®
Generac Power Systems, Inc.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2 — Installation
Guardian Liquid-cooled 40 kW Generator
‹
2.7.1 VENTED BATTERIES
2.7 BATTERY INSTALLATION
DANGER
Standby generators installed with automatic trans-
fer switches will crank and start automatically
when NORMAL (UTILITY) source voltage is
removed or is below an acceptable preset level. To
prevent such automatic start-up and possible
injury to personnel, do not connect battery cables
until the NORMAL source voltage at the transfer
switch is correct and the system is ready to be
placed into operation.
The electrolyte is a dilute sulfuric acid that is
harmful to the skin and eyes. It is electrically con-
ductive and corrosive. The following procedures
are to be observed:
!
!
• Wear full eye protection and protective clothing,
• Where electrolyte contacts the skin, wash it off
immediately with water,
• Where electrolyte contacts the eyes, flush thoroughly
and immediately with water and seek medical atten-
tion, and
• Spilled electrolyte is to be washed down with an acid-
neutralizing agent. A common practice is to use a
solution of one pound (500 grams) bicarbonate of
soda to one gallon (4 liters) of water. The bicarbonate
of soda solution is to be added until the evidence of
reaction (foaming) has ceased. The resulting liquid is
to be flushed with water and the area dried.
Storage batteries give off explosive hydrogen gas.
This gas can form an explosive mixture around
the battery for several hours after charging. The
slightest spark can ignite the gas and cause an
explosion. Such an explosion can shatter the bat-
tery and cause blindness or other injury. Any area
that houses a storage battery must be properly
ventilated. Do not allow smoking, open flame,
sparks or any spark producing tools or equipment
near the battery.
Lead acid batteries present a risk of fire because
they generate hydrogen gas. The following proce-
dures are to be followed:
Battery electrolyte fluid is an extremely caustic
sulfuric acid solution that can cause severe burns.
Do not permit fluid to contact eyes, skin, clothing,
painted surfaces, etc. Wear protective goggles,
protective clothing and gloves when handling a
battery. If fluid is spilled, flush the affected area
immediately with clear water.
!
• DO NOT SMOKE when near batteries,
• DO NOT cause flame or spark in battery area, and
• Discharge static electricity from body before touching
batteries by first touching a grounded metal surface.
Servicing of batteries is to be performed or supervised
by personnel knowledgeable of batteries and the
required precautions. Keep unauthorized personnel
away from batteries.
Do not dispose of the battery in a fire. The
battery is capable of exploding.
For recommended batteries, see Section 4.5, “Battery
Maintenance”. All batteries must be at 100 percent state-
of-charge before they are installed on the generator.
Do not open or mutilate the battery. Released
electrolyte can be toxic and harmful to the skin
and eyes.
!
When using maintenance-free batteries, it is not neces-
sary to check the specific gravity or electrolyte level.
Have these procedures performed at the intervals spec-
ified in Section 4, “Maintenance.” A negative ground sys-
tem is used. Battery connections are shown on the
wiring diagrams. Make sure all batteries are correctly
connected and terminals are tight. Observe battery
polarity when connecting batteries to the generator set.
The battery represents a risk of high short circuit
current. When working on the battery, always
remove watches, rings or other metal objects, and
only use tools that have insulated handles.
NOTE:
Damage will result if the battery connections are
reversed.
®
10 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 2 — Installation
Guardian Liquid-cooled 40 kW Generator
‹
2.8.5 BELT TENSION
2.8 PREPARATION BEFORE START-UP
The instructions in this section assume that the standby
generator has been properly installed, serviced, tested,
adjusted and otherwise prepared for use by a competent,
qualified installation contractor. Be sure to read the
“Safety Rules” on Pages 2 and 3, as well as all other safe-
ty information in this manual, before attempting to oper-
ate this (and related) equipment.
Check the engine fan belt tension and condition prior to
placing the unit into service and at recommended
intervals. Belt tension is correct when a force of approx-
imately 22 pounds (10 kg), applied midway between
pulleys, deflects the belt about 3/8- to 5/8-inch (10 to 16
mm).
‹
2.8.6 ELECTRICAL SYSTEM
‹
2.8.1 PRIOR TO INITIAL START-UP
Make sure the generator is properly connected to an
approved earth ground and/or ground rod.
Make sure the generator battery is fully charged, proper-
ly installed and interconnected, and ready for use.
Prior to initially starting the generator, it must be
properly prepared for use. Any attempt to crank
or start the engine before it has been properly
serviced with the recommended types and quanti-
ties of engine fluids (oil, coolant, fuel, etc.) may
result in an engine failure.
!
Check to ensure that there are no loose electrical con-
nections. Restrain any loose wires to keep them clear of
any moving generator set components.
‹
2.8.7 RODENT PROTECTION
Before starting the generator for the first time, the
installer must complete the following procedures. For
follow-up maintenance information and/or service inter-
vals, please refer to Section 4, “Maintenance.”
Make sure the four 3-inch diameter cap plugs (part #
0A8785) are properly installed in the tie-down holes in
the side rails of the unit’s base frame (Figure 2.3). The
cap plugs are shipped in a plastic bag located in the
lower connection box. These plugs are needed to pre-
vent rodents from accessing the interior of the genera-
tor set. On acoustic units, cap plugs also are needed to
stay within noise specification limits.
‹
2.8.2 FUEL SYSTEM
Make sure the fuel supply system to the generator (a)
delivers the correct fuel at the correct pressure and (b)
is properly purged and leak tested according
to code. No fuel leakage is permitted. See Section 1.8,
“Specifications”, for more information.
Figure 2.3 - Base Frame Cap Plugs
‹
2.8.3 GENERATOR SET LUBRICATION
Check the engine crankcase oil level before operating
and add oil to the proper level – the dipstick “FULL”
mark. Never operate the engine with the oil level below
the dipstick “ADD” mark. See Section 1.8,
“Specifications” and Section 1.10, “Engine Oil
Recommendations”.
NOTE:
This engine is shipped from the manufacturer with
SAE 15W-40 oil. This oil should be changed after 30
hours of operation.
‹
2.8.4 ENGINE COOLANT
Have the engine cooling system properly filled with the
recommended coolant mixture. Check the system for
leaks and other problems. See Section 1.8,
“Specifications” and Section 1.11, “Coolant”.
®
Generac Power Systems, Inc. 11
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3 — Operation
Guardian Liquid-cooled 40 kW Generator
3.1.5 HOURMETER
‹
3.1 CONTROL CONSOLE COMPONENTS
The components of a liquid-cooled generator control
console (Figure 3.1) are as follows:
This indicates the time the engine-generator has operat-
ed, in hours and tenths of hours. Use the hourmeter
along with the periodic maintenance schedule for the
generator set.
Figure 3.1 – Control Console
3.1.6 AUTO/OFF/MANUAL SWITCH
‹
See Section 3.2.
3.1.7 FAULT INDICATOR LAMP
‹
This lamp goes ON when one or more of the following
engine faults occurs and when engine shuts down.
• Low oil pressure
• High coolant temperature
15
• Low coolant level • Overcrank
• Overspeed
3.1.8 15-AMP FUSE
‹
This fuse protects the control console’s DC control cir-
cuit against electrical overload. If the fuse has melted
open because of an overload, engine cranking and start-
up cannot occur. Replace the fuse with an identical AGC
15-amp replacement fuse.
3.1.1 AC VOLTMETER
‹
The voltmeter displays generator AC output voltage dur-
ing operation. Voltage is regulated by a solid-state volt-
age regulator and is proportional to AC frequency. Refer
to the unit’s DATA PLATE for rated AC voltage.
3.1.9 7.5 AMP INLINE FUSE (NOT SHOWN)
‹
This inline fuse is connected in the 15A line that runs
between the AUTO/OFF/MANUAL switch and position
10 of the 076009A PCB. This fuse protects the start,
fuel, field boost, and transfer outputs from the PCB and
will open if there is excessive current draw on any one
of these outputs.
3.1.2 AC AMMETER
‹
This indicates current draw of connected electrical
loads during operation. DO NOT EXCEED THE UNIT’S
RATED MAXIMUM CONTINUOUS CURRENT. Refer to
the unit DATA PLATE.
3.1.10 VOLTAGE-PHASE SELECTOR SWITCH
This switch permits selection between either line-to-line
or line-to-neutral voltage and amperage readings on the
console AC voltmeter and AC ammeter.
‹
3.1.3 AC FREQUENCY METER
‹
This indicates generator AC output frequency in Hertz
(cycles per second). Frequency is proportional to engine
speed. Units with a four-pole rotor, supply 60 Hertz at
1,800 rpm. The frequency reading with no electrical
loads connected (no-load condition) should be between
60-62 Hertz.
3.1.11 SET EXERCISE TIME SWITCH
This switch allows to program the generator to start and
exercise automatically. (See Section 3.6)
‹
3.1.4 DC VOLTMETER
‹
3.2 USING THE AUTO/OFF/MANUAL
SWITCH
The generator is equipped with a belt-driven DC alter-
nator, which maintains battery state of charge when the
engine operates. The control module assembly (CMA)
also incorporates a trickle charge circuit that maintains
battery state of charge during nonoperating periods.
Battery voltage should read approximately12.5 to 14.5
volts DC. A low battery voltage indicates the battery is
discharging.
3.2.1 “AUTO” POSITION
‹
Selecting this switch position activates fully automatic
system operation. It also allows the unit to start and
exercise the engine every seven days with the setting of
the exercise timer.
®
12 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 3 — Operation
Guardian Liquid-cooled 40 kW Generator
Upon restoration of utility source voltage above a preset
level, generator circuit board action signals the transfer
switch to transfer loads back to that power supply. After
retransfer, the engine is signalled to shut down.
3.2.2 “OFF” POSITION
This switch position shuts down the engine. This posi-
tion also prevents operation.
‹
The actual sequence of operation is controlled by
sensors and timers on a control logic circuit board, as
follows:
3.2.3 “MANUAL” POSITION
Set the switch to MANUAL to crank and start the engine.
Transfer to standby power will not automatically occur
unless there is a utility failure.
‹
A.Utility Voltage Dropout Sensor
• This sensor monitors utility source voltage.
• If utility source voltage drops below about 60 per-
cent of the nominal supply voltage, the sensor ener-
gizes a 15-second timer.
• Once the timer has expired, the engine will crank
and start.
With the switch set to AUTO, the engine may
crank and start at any time without warning.
!
Such automatic starting normally occurs when
utility power source voltage drops below a preset
level or during the normal exercise cycle. To pre-
vent possible injury that might be caused by such
sudden starts, always set the switch to OFF and
remove the fuse before working on or around the
generator or transfer switch. Then, place a “Do
Not Operate” tag on the generator panel and on
the transfer switch.
B.Engine Warm-up Time Delay
• This mechanism lets the engine warm up for about
10 seconds before the load is transferred to the
engine-generator output.
C.Standby Voltage Sensor
• This sensor monitors generator AC output voltage.
When the voltage has reached 50 percent of the
nominal rated voltage, transfer to standby can
occur.
D.Utility Voltage Pickup Sensor
3.3 AUTOMATIC TRANSFER OPERATION
• This sensor monitors utility power supply voltage.
When that voltage is restored above 80 percent of
the nominal source voltage, a retransfer time delay
starts timing.
To select automatic operation, do the following:
1. Make sure the transfer switch main contacts are set
to their UTILITY position, i.e., loads connected to
the utility power source.
2. Be sure that normal utility power source voltage is
available to transfer switch terminal lugs N1 and N2.
3. Set the generator’s AUTO/OFF/MANUAL switch to
AUTO.
E.Retransfer Time Delay
• This timer runs for about 15 seconds.
• At end of a 15-second delay, circuit board action de-
energizes transfer relay in the transfer switch.
• Retransfer to utility power source then occurs.
F. Engine Cool-down Timer
• When the load is transferred back to utility power
source, the engine cool-down timer starts timing.
• The timer will run for about one minute, and the
generator will then shut down.
4. Set the generator’s main circuit breaker to its ON
(or closed) position.
With the preceding steps complete, the generator will
start automatically when utility source voltage drops
below a preset level. After the unit starts, loads are
transferred to the standby power source. Refer to
“Sequence of Automatic Operation.”
3.5 ENGINE HEATER
This Generac standby generator comes equipped with a
block heater (Figure 3.2, page 14) that is similar to the
block heaters used in automotive applications. The
block heater must be connected to a customer supplied
120V AC circuit.
3.4 SEQUENCE OF AUTOMATIC
OPERATION
The generator’s control panel houses a control logic cir-
cuit board. This board constantly monitors utility
power source voltage. Should that voltage drop below a
preset level, circuit board action will signal the engine to
crank and start. After the engine starts, the circuit
board signals the transfer switch to activate and connect
load circuits to the standby power supply (load terminal
lugs T1/T2 connect to terminal lugs E1/E2).
®
Generac Power Systems, Inc. 13
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Maintenance
Guardian Liquid-cooled 40 kW Generator
NOTE:
Figure 3.2 – Engine Block Heater
If the battery terminals are disconnected or the con-
trol panel fuse is removed, the exercise timer needs
to be reset for automatic exercise operation.
OUTLET
Figure 3.3 – “Set Exercise” Switch on Control Panel
INLET
Refer to applicable wiring diagram(s) and electrical
schematic(s) at the back of this manual for wiring con-
nections.
3.6 WEEKLY EXERCISE CYCLE
4.1 CHECKING THE ENGINE OIL LEVEL
For oil capacities, see “Specifications,” Section 1.8. For
engine oil recommendations, see Section 4.2.1. To
check the engine oil level, proceed as follows (Figure
4.1):
The generator will start and exercise once every seven
days. During this weekly exercise, the unit runs for
approximately 20 minutes and shuts down. Transfer of
loads to generator output does not occur during the
exercise unless power is lost during the exercise period.
1. Remove the dipstick and wipe it dry with a
clean cloth.
2. Install the dipstick cap; then, remove it again. The
oil level should be at the dipstick “Full” mark. If nec-
essary, add oil to the “Full” mark only. DO NOT FILL
ABOVE THE “FULL” MARK.
To select the day of the week and time of day for exer-
cising, proceed as follows:
• Set the AUTO/OFF/MANUAL switch to OFF.
• Set generator’s main circuit breaker to its OFF (or
open) position.
• Locate the rocker switch on the control panel identi-
fied with the words “Set Exercise Time” (Figure 3.3).
• Push “Set Exercise Time” switch to the ON position
for 20 to 30 seconds and then release. The switch will
spring back into its original position when released.
• Wait 30 seconds before setting the AUTO/OFF/
MANUAL switch to the AUTO position.
3. Install the dipstick.
Figure 4.1 – Oil Dipstick and Fill
OIL DIPSTICK
OIL FILL CAP
NOTE:
The unit will exercise 20 minutes before it is set.
Example: Set – Noon; Exercise – 11:40 a.m.
If you switch the AUTO/OFF/MANUAL switch is
switched too soon, the engine may start. If
!
engine does start, it will shut down automatically
in about two (2) minutes.
• Set the generator’s main circuit breaker to its ON (or
closed) position.
• The generator is now programmed to start and exer-
cise every seven days thereafter, on the day and at the
time of day the switch was activated.
Never operate the engine with the oil level below
the “Add” mark on the dipstick. Doing this could
damage the engine.
• Place a sign on the generator’s control panel and on
the transfer switch that indicates the day and time
the generator will be exercising.
!
®
14 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Maintenance
Guardian Liquid-cooled 40 kW Generator
5. Apply a light coating of clean engine oil to the seal
of new oil filter. Install the filter and tighten by
hand only. DO NOT OVERTIGHTEN.
6. Remove the oil fill cap (Figure 4.1). Add the recom-
mended oil (see Section 4.2.1). DO NOT FILL
ABOVE THE DIPSTICK “FULL” MARK. Crankcase
oil capacity is 4.5 U.S. quarts (4.25 L).
4.2 CHANGING THE ENGINE OIL AND
FILTER
4.2.1 ENGINE OIL RECOMMENDATIONS
‹
Use oil of API Service Class SG, SH or SJ. The
recommended oil grade for the engine is
SAE 15W-40.
NOTE:
After refilling the crankcase with oil, always
check the oil level on the dipstick. Never
operate the engine with the oil level below the
“Add” mark on the dipstick. Doing this could
damage the engine.
The unit is supplied with “break-in” oil. See the
“Service Schedule,” Section 4.12, for the first
required oil change.
!
7. Start the engine and check for oil leaks.
8. Check the oil level after checking for leaks to
ensure that the oil is filled to the proper level.
Any attempt to crank or start the engine before
it has been properly serviced with the recom-
mended oil may result in an engine failure.
!
4.3 CHANGING THE ENGINE AIR
4.2.2 OIL AND FILTER CHANGE PROCEDURE
To change the oil and filter, proceed as follows:
‹
CLEANER
To replace the engine air cleaner, (Generac part num-
ber 0A4637), remove the air cleaner cover and
replace the air filter making sure it is positioned
properly before reattaching the cover. (See Figure
4.3).
Refer to the “Service Schedule,” (Section 4.12) for
engine oil and filter change frequencies.
Drain the oil while the engine is still warm from run-
ning. This means, warm up the engine, shut it down
and drain it immediately as follows:
Figure 4.3 – Engine Air Cleaner
1. Remove the oil drain hose from its retaining clip,
located on the generator base frame.
2. Loosen and remove the oil drain hose cap, located
on the base frame end of the hose. Drain the oil
completely into a suitable container.
Air Cleaner
3. When all of the oil has drained, install and tighten
the oil drain hose cap.
4. Turn the oil filter (Generac part number
0A37970001, Figure 4.2) counterclockwise and
remove it. Properly dispose of the old filter.
Figure 4.2 – Oil Filter
OIL FILTER
See the “Service Schedule,” Section 4.12, for recom-
mended air cleaner maintenance.
OIL DRAIN HOSE
TO BASE
®
Generac Power Systems, Inc. 15
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Maintenance
Guardian Liquid-cooled 40 kW Generator
Storage batteries give off explosive hydrogen gas.
This gas can form an explosive mixture around
the battery for several hours after charging. The
slightest spark can ignite the gas and cause an
explosion. Such an explosion can shatter the bat-
tery and cause blindness or other injury. Any area
that houses a storage battery must be properly
ventilated. Do not allow smoking, open flame,
sparks or any spark producing tools or equipment
near the battery.
4.4 SPARK PLUGS
!
Reset the spark plug gap or replace the spark plugs as
necessary. See Section 4.12.
1. Clean the area around the base of the spark plugs to
keep dirt and debris out of the engine. Clean the
plugs by scraping using a wire brush. Do not “blast”
the spark plugs to clean.
2. Remove the spark plugs and check the condition.
Replace the spark plugs if worn or if reuse is ques-
tionable. See the “Service Schedule,” Section 4.12, for
recommended inspection.
Battery electrolyte fluid is an extremely caustic
sulfuric acid solution that can cause severe burns.
Do not permit fluid to contact eyes, skin, clothing,
painted surfaces, etc. Wear protective goggles,
protective clothing and gloves when handling a
battery. If fluid is spilled, flush the affected area
immediately with clear water.
!
3. Check the spark plug gap using a feeler gauge.
Adjust the gap to 0.045 inch (1.1 mm) by carefully
bending the ground electrode (Figure 4.4).
Figure 4.4 – Setting the Spark Plug Gap
0.045 inch (1.1 mm)
Do not dispose of the battery in a fire. The bat-
tery is capable of exploding.
Do not open or mutilate the battery. Released
electrolyte can be toxic and harmful to the skin
and eyes.
!
The battery represents a risk of high short circuit
current. When working on the battery, always
remove watches, rings or other metal objects, and
only use tools that have insulated handles.
4.5 BATTERY MAINTENANCE
The battery should be inspected per the “Service
Schedule,” Section 4.12. The following procedure
should be followed for inspection:
‹
4.5.1 BATTERY REPLACEMENT
Generac uses a Group 27F vented type battery that has
600 CCA @ 0º F. Generac’s part number is 058665.
1. Inspect the battery posts and cables for tightness
and corrosion. Tighten and clean as necessary.
2. Check the battery fluid level of unsealed batteries
and, if necessary, fill with DISTILLED WATER
ONLY. DO NOT USE TAP WATER IN BATTERIES.
3. Have the state of charge and condition checked.
This should be done with an automotive-type bat-
tery hydrometer or load test.
NOTE:
The BCI number should be located directly on the
battery.
4.6 COOLING SYSTEM
Air intake and outlet openings in the generator compart-
ment must be open and unobstructed for continued prop-
er operation. This includes such obstructions as high
grass, weeds, brush, leaves and snow.
DANGER
Standby generators installed with automatic
transfer switches will crank and start automatical-
ly when NORMAL (UTILITY) source voltage is
removed or is below an acceptable preset level. To
prevent such automatic start-up and possible
injury to personnel, do not connect battery cables
until the NORMAL source voltage at the transfer
switch is correct and the system is ready to be
placed into operation.
Without sufficient cooling and ventilating air flow, the
engine/generator quickly overheats, which causes it to
shut down.
The exhaust system of this product gets extremely
hot and remains hot after shutdown. High grass,
weeds, brush, leaves, etc. must remain clear of the
exhaust. Such materials may ignite and burn from
the heat of the exhaust system.
®
16 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Maintenance
Guardian Liquid-cooled 40 kW Generator
4.7 OVERLOAD PROTECTION FOR
4.10 MISCELLANEOUS MAINTENANCE
ENGINE DC ELECTRICAL SYSTEM
Engine cranking, start-up and running are controlled by
a solid-state engine controller circuit board. Battery
voltage is delivered to that circuit board via a 15-amp
fuse. These overcurrent protection devices will open if
the circuit is overloaded.
4.10.1 CLEANING THE GENERATOR
‹
Keep the generator as clean and as dry as possible. Dirt
and moisture that accumulate on internal generator
windings have an adverse effect on insulation resist-
ance.
Periodically, clean the generator’s exterior surfaces. A
soft brush may be used to loosen caked on dirt. Use a
vacuum system or dry, low pressure air to remove any
accumulations of dirt. The generator is housed inside
an all-weather enclosure; clean the enclosure with a
soft, damp cloth or sponge and water.
If a circuit breaker opens or a fuse element melts,
find the cause of the overload before resetting the
circuit breaker or replacing the fuse.
Once each year, have the generator cleaned and inspect-
ed by a Generac/Guardian Authorized Dealer. Service
technicians will use dry, low pressure air to clean inter-
nal windings. Parts inside the control console should be
cleaned and inspected at this time as well.
4.8 DC FUSE
The generator panel’s 15-amp AGC fuse (Figure 4.4) pro-
tects the DC control circuit against overload. The fuse is
wired in series with the battery output lead to the panel.
If the fuse element has melted open, cranking or starting
the engine cannot occur. Replace the fuse using only an
identical 15-amp AGC replacement.
Finally, have the insulation resistance of stator and
rotor windings checked. If insulation resistances are
excessively low, the generator may require drying.
Figure 4.4 – Location of 15-amp Fuse
4.10.2 RODENT PROTECTION
‹
The intrusion of rodents into the generator set can
cause a wide range of problems, from failure of the unit
to start, to personal injury and, in extreme circum-
stances, short circuit or fire. Although the unit was
designed to limit this problem, further precautions can
be taken by the owner to help minimize both the chance
of rodent entry and the extent of any damage. The fol-
lowing inspection should be performed.
1. The base frame of the unit contains an optional fuel
inlet location and four lifting holes that are capped
at the factory. These caps are sometimes removed
for transportation during installation but always
should be replaced afterwards. Check that they are
secured in place. The same applies for any access
ports in the roof of the enclosure. If any of these
caps are missing, contact a Generac/Guardian
Authorized Dealer.
2. Inside the generator set, the chance of rodent entry
into the control panel is greatly reduced by the
inclusion of adjustable wire connectors. Check that
the wire connector screws are tight, closing off any
gap between the access holes and the wires.
15
4.9 ENGINE COOLANT
Check the coolant level in the coolant recovery bottle.
• Add the recommended coolant mixture as necessary,
see Section 1.10.
• Periodically remove the radiator pressure cap to make
sure the coolant recovery system is functioning
properly. Coolant should be at the bottom of the radia-
tor filler neck. If the coolant level is low, inspect the
gasket in the radiator pressure cap. Replace the cap, if
necessary. To have the pressure cap tested, contact a
Generac/Guardian Authorized Dealer. Inspect the cool-
ing system and coolant recovery system for leaks.
®
Generac Power Systems, Inc. 17
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Maintenance
Guardian Liquid-cooled 40 kW Generator
‹
4.11.2 RETURN TO SERVICE
4.11 OUT OF SERVICE PROCEDURE
To return the unit to service after storage, proceed
as follows:
‹
4.11.1 REMOVAL FROM SERVICE
If the generator cannot exercise every seven days, and it
is to be out of service longer than 90 days, prepare the
generator for storage as follows:
1. Verify that UTILITY power is turned off to the trans-
fer switch and that the AUTO/OFF/MANUAL switch
is set to OFF.
2. Check the tag on the engine for oil viscosity and
classification. Verify that the correct recommended
oil is used in engine, see Section 4.2.1. If necessary,
drain and refill with the proper oil.
3. Check the battery. Fill all cells to the proper level
with distilled water. DO NOT USE TAP WATER IN
THE BATTERY. Remove the battery before charging.
Recharge the battery to 100 percent state of charge,
or, if defective, replace the battery with a 12-volt DC
Group 27F battery rated for 90 amp hours (part #
058665).
1. Start the engine and let it warm up.
2. Close the fuel shutoff valve in the fuel supply line
and allow the unit to shut down.
3. Once the unit has shut down, it will signal a fault on
the control panel.
4. Set the AUTO/OFF/MANUAL switch to OFF and turn
off the UTILITY power to the transfer switch.
5. While the engine is still warm from running, drain
the oil completely. Refill the crankcase with SAE
15W-40 oil having API Service Class SG, SH or SJ.
6. Attach a tag to the engine indicating the viscosity
and classification of the oil in the crankcase.
7. Remove the spark plug(s) and spray fogging agent
into the spark plug(s) threaded openings. Reinstall
and tighten the spark plug(s).
4. Clean and wipe the entire generator.
5. Reconnect the battery. Observe battery polarity.
Damage may occur if the battery is connected incor-
rectly.
6. Open the fuel shutoff valve.
8. Remove the battery and store it in a cool, dry room
on a wooden board. Never store the battery on any
concrete or earthen floor.
7. Start the unit by moving the AUTO/OFF/MANUAL
switch to MANUAL. Allow the unit to warm up thor-
oughly.
9. Clean and wipe the entire generator.
8. Stop the unit and set the AUTO/OFF/MANUAL
switch to AUTO.
9. Turn on the UTILITY power to the transfer switch.
10. The generator is now ready for service.
®
18 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 4 — Maintenance
Guardian Liquid-cooled 40 kW Generator
4.12 SERVICE SCHEDULE
ATTENTION: It is recommended that all service work
be performed by the nearest Generac/Guardian Authorized Dealer.
SYSTEM/COMPONENT
PROCEDURE
FREQUENCY
X = Action
Inspect
Change
Clean
W = Weekly
M = Monthly
Y = Yearly
R = Replace/Adjust as Needed
* = Notify Dealer
if Repair is Needed.
H = Hours
FUEL
Fuel lines and connections*
LUBRICATION
Oil level
X
X
EVERY 3 M
M
Oil
X
X
FIRST 30 H,
EVERY 150 H / 6 M
Oil filter
FIRST 9 H,
EVERY 150 H / 6 M
Oil line leakage*
COOLING
Engine cooling system*
Coolant
Enclosure louvers
EXHAUST
X
X
X
100 H
M
Y
W
X
X
X
Exhaust system
Retorque Exhaust Manifold*
X
X
EVERY 3 M
FIRST 100 H AND
EVERY 800 H
BATTERY
Charge and condition
FAN BELT
Tension and condition*
ENGINE
X
X
R
R
EVERY 3 M
EVERY 3 M
Retorque cylinder head*
X
X
FIRST 100 H AND
EVERY 800 H
FIRST 100 H AND
EVERY 800 H
Retorque intake manifold*
Starter motor*
DC alternator*
Air cleaner*
Compression*
Valve clearance*
Governor*
Safety devices*
Spark plugs
Ignition system*
GENERAL
X
X
X
X
X
X
X
X
X
R
R
R
EVERY 500 H
EVERY 500 H AND Y
EVERY 500 H
EVERY 800 H
EVERY 800 H
Y
R
R
R
R
R
EVERY 6 M
500 H AND Y
EVERY 3 M
Overall condition
Exercise system
COMPLETE TUNE-UP*
X
X
M
W
Y
TO BE COMPLETED BY A GENERAC/
GUARDIAN AUTHORIZED DEALER
®
Generac Power Systems, Inc. 19
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 5 — Troubleshooting
Guardian Liquid-cooled 40 kW Generator
5.1 TROUBLESHOOTING GUIDE
PROBLEM
The engine will not crank.
CAUSE
CORRECTION
1. Replace fuse.
2. Tighten, clean or replace
as necessary.
1. Fuse blown
2. Loose, corroded or defective
battery cables
3. Defective starter contactor
4. Defective starter motor
5. Dead Battery
3. *
4. *
5. Charge or replace battery.
The engine cranks but
will not start.
1. Out of fuel
1. Replenish fuel.
2. *
3. *
2. Defective fuel solenoid (FS)
3. Open #14 wire from
engine control board
4. Defective spark plug(s)
5. Dirty/Blocked air filter
4. Clean, re-gap or replace plug(s).
5. Clean or replace as required.
The engine starts hard
and runs rough.
1. Air cleaner
1. Check, clean or replace air cleaner.
plugged or damaged
2. Defective spark plug(s)
3. Dirty/Blocked air filter
2. Clean, re-gap or replace plug(s).
3. Clean or replace as required.
The engine starts, but then
shuts down.
1. Engine oil level low
2. Defective low oil
pressure switch
1. Check oil and add oil as needed.
2. *
3. Defective high temperature
switch
4. Defective control board
5. Low coolant level
3. *
4. *
5. Check coolant level, repair leaks
and refill.
The AUTO/OFF/MANUAL switch
is set to OFF, but the engine
continues to run.
1. Defective switch
2. Defective control board
1. *
2. *
There is no AC output from
the generator.
1. Generator main line circuit
breaker open
2. Generator internal failure
1. Reset circuit breaker
to ON (or closed).
2. *
There is no transfer to
STANDBY after UTILITY
source failure.
1. Generator main line circuit
breaker open
2. Defective transfer switch coil
3. Defective transfer relay
4. Transfer relay circuit open
5. Defective control logic board
1. Reset circuit breaker
to ON (or closed).
2. *
3. *
4. *
5. *
*Contact the nearest Generac/Guardian Authorized Dealer for assistance.
®
20 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6 — Installation Diagram
Guardian Liquid-cooled 40 kW Generator
Drawing No. 0E7015
®
Generac Power Systems, Inc. 21
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Electrical Data
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator
Electrical Schematic (Stepper Motor) – Drawing No. 0A5858
P/N 98647
BLUE
GCB - GOVERNOR CONTROL BOARD
HZ - FREQUENCY METER
®
22 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 6 — Electrical Data
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator
Wiring Diagram — Pre-pack Panel (4.3L) – Drawing No. 0D4992-A
7
5
5
5
7
5
5
5
2 5
K
L A
7
8
9
10
11
12
R
T U A T
V E R N
R
®
Generac Power Systems, Inc. 23
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Electrical Data
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator
Electrical Schematic — Pre-pack Panel (4.3L) – Drawing No. 0D4993-A
W
E L L
E
R A N
E L L
W
W N R
L A
K
R E T H ) N N E
I N E ( E N
P )
R
T
N N E
W E R L P A N E L (
®
24 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Electrical Data
Guardian Liquid-cooled 40 kW Generator
Wiring Diagram/Schematic – Lower Panel – Drawing No. 0D5997
P )
R
T
N N E
L P A N N E T L R (
®
Generac Power Systems, Inc. 25
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Electrical Data
(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators
Wiring Diagram - Control Panel - Drawing No. 0D6974
7
5
7
5
5
2 5
K
L A
H I E L D P U
-
+
T -
T +
-
7
+
®
26 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Electrical Data
(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators
Electrical Schematic - Control Panel - Drawing No. 0D6975
W
E L L
H I E L D P U
-
+
T -
T +
R E T H ) N N E
I N E ( E N
P )
R
T
N N E
W E R L P A N E L (
®
Generac Power Systems, Inc. 27
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Electrical Data
Guardian Liquid-cooled 40 kW Generators
Wiring Diagram - Drawing No. 0E2966
1
2
3
4
5
6
7
8
9
161
160
56
0
85
85
0
161
160
GND
0
85
85
85
GND
OS
85
0
79
14
14
13
10
11
12
GND
0
56
13
16
16
13
0
13
13
GND
(+)
(-)
LEGEND:
ACT: ACTUATOR ELECTRONIC GOVERNOR
ALT: DC ALTERNATOR
BAT: BATTERY
CC:
CONTROL CONTACTOR
EC1: ENGINE CONNECTOR 1(BLACK)
EH:
FS:
ENGINE HEATER
FUEL SOLENOID
GND: GROUND
COOLANT HIGH TEMP. SWITCH
IC:
ID:
IGNITION COIL
IGNITION DISTRIBUTOR
LOW OIL PRESSURE SWITCH
MP1: MAGNETIC PICKUP 1
SM: STARTER
WLS: WATER LEVEL SENSOR
ONLY USED ON EMISSIONS MODELS
®
28 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Electrical Data
Guardian Liquid-cooled 40 kW Generators
Wiring Diagram - Drawing No. 0E2967
161
160
1
2
0
56
0
85
3
4
5
85
HCT
85
85
6
7
8
9
0
0
79
0
0
14
14
13
10
11
12
14
(-)
) +
RED
IC
13
13
16
LEGEND:
ACT: ACTUATOR ELECTRONIC GOVERNOR
ALT: DC ALTERNATOR
CC:
CONTROL CONTACTOR
EC1: ENGINE CONNECTOR 1(BLACK)
EH:
FS:
ENGINE HEATER
FUEL SOLENOID
HCT COOLANT HIGH TEMP. SWITCH
IC:
IGNITION COIL
IGNITION DISTRIBUTOR
LOS: LOW
MP1: MAGNETIC PICKUP 1
SC
STARTER CONTACTOR
SM: STARTER
WLS: WATER LEVEL SENSOR
ONLY USED ON EMISSIONS MODELS
®
Generac Power Systems, Inc. 29
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Mounting Base - Drawing No. 0E6976-A
28
BLACK
9
26
19
11
10
12
18
38
37
4
RED
39
8
7
36
29
TO STARTER
SOLENOID
15
6
18
20
15
1
To Oil Drain
On Oil Pan.
19
23
11
10
16
17
13
34
25
25
33
32
16
3
3
31
30
25
®
30 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 7 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Mounting Base - Drawing No. 0E6976-A
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
0E6900
038804T
055414
0A4084
022129
045771
022237
029745
023152
043107
022145
027482
055597
052251
052257
052252
052259
052860
0536210098
052251A
044118
057823
057448
024310
0D4239D
038805H
022131
025507
061902
022413
022473
022097
022127
0A4010
052858
058665
059473
049820
075763
1
1
1
REF.
2
2
7
6
1
2
2
3
4
2
4
4
4
4
1
2
1
2
1
1
1
1
1
1
1
1
1
1
1
2
MTG BASE 4.3L D/D PRE-PACK
CABLE BATT RED #1 X 31.00
LUG SLDLSS #2-#8 X 17/64 CU
MOUNT ENGINE (R&L)
WASHER LOCK M8-5/16
NUT HEX M8-1.25 G8 YEL CHR
WASHER LOCK 3/8
SCREW HHC 3/8-16 X 1 G5
SCREW HHC 3/8-16 X 3/4 G5
SCREW HHC M8-1.25 X 25 G8.8
WASHER FLAT 5/16 ZINC
WASHER SHAKEPROOF EXT 5/16 STL
SCREW HHC M12-1.75 X 85 G8.8
DAMPENER VIBRATION 40 BLUE
SPACER .49 X .62 X 1.87 PWDR/ZINC
DAMPENER VIBRATION
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
WASHER FLAT M12
NUT LOCKING M12-1.75
ASSEMBLY GROUNDWIRE 10"/3/8
DAMPENER VIBRATION 50 WHITE
BARBED STRAIGHT 1/2 NPT X 5/8
CLAMP HOSE #10 .56 - 1.06
HOSE 5/8 ID TYPE 3 SINGLE (11"LG)
PLUG STD PIPE 1/2 STEEL SQ HD
KIT VARMIT GUARD 4.3L PRE-PACK
CABLE BATT BLK #1 X 23.00
WASHER FLAT 3/8-M10 ZINC
WASHER SHAKEPROOF EXT 7/16 STL
HOLD DOWN BATTERY
SCREW HHC 1/4-20 X 1 G5
WASHER FLAT 1/4 ZINC
WASHER LOCK M6-1/4
NUT HEX 1/4-20 STEEL
SCREW HHC M8-1.25 X 60 G8.8 FT
NUT LOCK FL M8-1.25
2
1
1
2
BATT 12VDC 90-AH 27F
HOLD DOWN BATTERY
NUT LOCK HEX M8-1.25 NYL INSRT
BOOT BATTERY CABLE
1
®
Generac Power Systems, Inc. 31
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Compartment - Drawing No. 0D8992-A
®
32 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Compartment - Drawing No. 0D8992-A
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4 *
5
6
7
8
9
0C3594
0E3257
0A3359
022769
10
4
40
5
5
1
1
1
1
2
4
2
1
1
5
20
5
20
20
5
1
1
1
1
1
28
1
72
2
2
1
1
ASSEMBLY M6 HINGE
SCREW TH-FRM M6 W/CAP SHKPRF W
SCREW BHSC M6-1.0 X 16 SS
WASHER SHAKEPROOF INT #10
DOOR SMALL STD. WELD
CORNER POST LH REAR
CORNER POST RH REAR
CORNER POST LH FRONT
CORNER POST RH FRONT
REAR BRACE TOP & BOTTOM
BRACE SIDE TOP AND BOTTOM
SIDE SUPPORT
ROOF ONE-PC WELD ALUMINUM
FRONT BRACE TOP
PLATE STRIKER
SCREW PPHM M4-0.7 X 12 SS
PADDLE HANDLE LOCK
NUT LOCK HEX M4-0.7 SS NYL INS
WASHER FLAT #8 SS
0C2522 (A)
0C2527 (A)
0C2528 (A)
0C2535 (A)
0C2536 (A)
0C2547 (A)
0F1255 (A)
0C2555 (A)
0C2560A
0D7904 (A)
0C2633
10
11
12
13
15
16
17
18
19
20
21
22
23
24
25
26
27 **
28
29
30
31
32
33
34
35
36
39
42
43
44
0C6749
060069
0C6748
080490
087233
RIVET POP 3/16 X 1/4
DUCT FRONT LH
DUCT FRONT RH
DUCT BOTTOM
0C4065 (A)
0C4064 (A)
0C4066 (A)
0C4067 (A)
0C4117A
077992
0C2634A
0C2454
022129
042907
022473
022097
022127
DUCT FRONT PANEL
DUCT FRONT TOP RH ALUMINUM
NUT HEX LOCK M6-1.0 SS NY INS
ASSEMBLY COVER ACCESS
SCREW TH-FRM M6-1 X 16 N WA Z/JS
WASHER LOCK M8-5/16
SCREW HHC M8-1.25 X 16 G8.8
WASHER FLAT M6-1/4 ZINC
WASHER LOCK M6-1/4
NUT HEX 1/4-20 STEEL
GASKET DOOR RUBBER
SCREW SHOULDER
COVER EXHAUST HOLE
FASTENER RATCHET
STRIP SEALANT 1/8 X 1
WASHER FLAT 5/16 ZINC
1
0A9881
0C3393
0C3400 (A)
0C3397
066760
49.1 FT.
2
1
4
39-3/8"
2
022145
OPTIONAL COMPARTMENT MATERIALS:
ALL P/N'S WITH AN "A" SUFFIX INDICATE ALUMINUM MATERIAL OPTION.
* ONE PER PADDLE HANDLE
** ALUMINUM ENCLOSURE NOTE: ALL ENCLOSURE PANELS THAT FASTEN TO THE BASE FRAME MUST BE SECURED USING ITEM 2 & 29 THREAD
FORMING FASTENER AND ITEM 27 LOCK NUT. LOCK NUT IS TO BE INSTALLED AFTER THREAD FORMING FASTENER HAS PENETRATED THROUGH
EXTRUSIONS IN ENCLOSURE PANELS. ALL ROOF PANELS ARE TO BE SECURED IN THE SAME MANNER.
®
Generac Power Systems, Inc. 33
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator
Control Panel 4.3L – Drawing No. 0D4995-F
®
34 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generator
Control Panel 4.3L – Drawing No. 0D4995-F
ITEM PART NO. QTY.
DESCRIPTION
ITEM PART NO. QTY.
DESCRIPTION
1
2
3
0D5488
0D1521A
0D1522
1
1
2
PANEL BTM & BACK CONTROL
PANEL
CONTROL PANEL, FRONT W/ SILK
SCREEN
PANEL,SIDE COVER CONTROL
PANEL
ASSY VOLTAGE REGULATOR 60HZ
WASHER LOCK HDPDEUTSCH
NUT, HDP DEUTSCH
CIRCT BRK 7 X 1 ETA 46-500-P
RES WW LUG 10R 10% 25W
COVER CON PNL TOP (NOT SHOWN)
HEATSINK
WASHER STEP NYLON .20
RECTIFIER MSC 12A 600V 1N1206R
WASHER MICA .203
NUT HEX #10-32 STEEL
WASHER SHAKEPROOF EXT #10
STL
WASHER FLAT #10 ZINC
PP LOGIC ASM 50/60HZ
PCB SUPPORT SNAP-IN 1/4"
GROMMET 3/4 X 5/32 X 5/16
SWITCH ROCKER DPST 125V SPD
SWITCH TOG DPDT 15/10 SP
HOLDER FUSE
32
33
34
35
36
37
39
41
42
43
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62*
63*
64
65
070042
081988
0C1229
098647
0A3968
048766
083264
057335
076061
029333
040479
022507
022127
022097
033121
022152
036902
022155
022985
036918
022264
038150
022471
022188
036908
0C2428
0C2323
0D5324
0A9611
074908
0E3783
1
1
1
REF.
1
REF
1
REF
1
6
4
4
4
FREQUENCY METER 240V 55-65HZ
DECAL EXERCISE INFO
DECAL CUST CONN BOX
ASSY L.C. ELECT GOV
CAPACITOR FILTER ASY
BLOCK TERM 20A 2 X 6 X 1100V
TFMR ASM,CMA 240/12V
BLOCK TERM 20A 20 X 6 X 1100V
DECAL, TERM. STRIP
TIE WRAP 7.4" X .19" NATL UL
VIB MNT 1.0 X 1.0 X 1/4-20
SCREW HHC 1/4-20 X 1/2 G5
NUT HEX 1/4-20 STEEL
WASHER LOCK M6-1/4
SCREW HHC #10-32 X 1/2
WASHER LOCK #10
SCREW PPHM #6-32 X 1/2
WASHER LOCK #6
WASHER FLAT #6 ZINC
SCREW PPHM #8-32 X 1/2
WASHER LOCK M4
WASHER FLAT #8 ZINC
NUT HEX #8-32 STEEL
NUT HEX #6-32 STEEL
SCREW PPHM #6-32 X 1-1/4
SCREW PHTT #6-32 X 1/2 ZYC
SCREW PHTT #6-32 X 5/8 ZYC
FUSE & HOLDER LITTEL 7.5A
FUSE 7.5AXBK/AGC7.5NX W/22670
SCREW HHTT M5-0.8 X 10 BP
DECAL, WARNING REMOVE FUSE
4
5
6
8
9
10
12
13
14
15
16
17
067680
0C8243
0C8244
048467
057907
064008
055444
030468
049939
070370
022158
023762
1
1
1
1
1
1
1
1
1
1
1
1
4
14
14
4
6
6
4
4
4
4
6
2
4
4
REF.
REF.
1
18
19
20
21
22
23
24
25
26
27
28
29
30
31
023897
076009A
040213
027744
082573
076020
032300
022676
064009
061945
076037
070081
070043
070045
15
1
4
1
1
1
1
1
1
1
1
1
1
1
FUSE 15A X AGC15
LIGHT 12VDC .02A LED RED PILOT
SWITCH SELECTOR 6A AMP/V
VOLTMETER DC 8-18V
HOURMETER
VOLTMETER AC 0-300
AMMETER AC 0-200
1
* PART OF CONTROL PANEL WIRE HARNESS
®
Generac Power Systems, Inc. 35
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generator
Control Panel – Drawing No. 0D6978-C
®
36 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generator
Control Panel – Drawing No. 0D6978-C
ITEM PART NO. QTY.
DESCRIPTION
ITEM PART NO. QTY.
DESCRIPTION
1
2
0D7397
0D1521A
1
1
PNL BTM & BACK CNTL PNL 04626
CONTROL PANEL FRONT W/ SILK
SCREEN
PANEL SIDE COVER CONTROL
PANEL
ASSY VOLTAGE REGULATOR 60HZ
WASHER LOCK HDP DEUTSCH
NUT, HDP DEUTSCH
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55
56
57
58
59
60
61
62*
63*
64
65
081988
0C1229
0D3440
0A3968
048766
0A1441B
083264
0A1441C
057335
076061
029333
040479
022507
022127
022097
033121
022152
036902
022155
022985
036918
022264
038150
022471
022188
0C2428
0C2323
0A2284
0C1127
0D5324
0A9611
074908
0E3783
1
1
1
1
REF
1
1
1
REF
1
6
4
4
4
4
14
14
4
6
8
8
8
8
8
6
8
4
4
1
4
1
4
DECAL EXERCISE INFO
DECAL CUST CONN BOX
CONTROLLER, B-C #DPG-2103
CAPACITOR FILTER ASY
BLOCK TERM 20A 2 X 6 X 1100V
COVER PLATE AVR
TFMR ASM,CMA 240/12V
COVER PLATE EGOV
BLOCK TERM 20A 20 X 6 X 1100V
DECAL TERM. STRIP
TIE WRAP 7.4" X .19" NATL UL
VIB MNT 1.0 X 1.0 X 1/4-20
SCREW HHC 1/4-20 X 1/2 G5
NUT HEX 1/4-20 STEEL
WASHER LOCK M6-1/4
SCREW HHC #10-32 X 1/2
WASHER LOCK #10
3
0D1522
1
4
5
6
7
8
067680
0C8243
0C8244
0A6321
048467
057907
064008
0E3550
055444
030468
049939
070370
022158
023762
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PANEL LEFT SIDE E
CIRCT BRK 7 X 1 ETA 46-500-P
RES WW LUG 10R 10% 25W
COVER CON PNL TOP (NOT SHOWN)
CHASSIS, UNIVERSAL
9
10
11
12
13
14
15
16
17
HEATSINK
WASHER STEP NYLON .20
RECTIFIER MSC 12A 600V 1N1206R
WASHER MICA .203
NUT HEX #10-32 STEEL
WASHER SHAKEPROOF EXT #10
STL
WASHER FLAT #10 ZINC
PP LOGIC ASM 50/60HZ
PCB SUPPORT SNAP-IN 1/4"
GROMMET 3/4 X 5/32 X 5/16
SWITCH ROCKER DPST 125V SPD
SWITCH TOG DPDT 15/10 SP
HOLDER FUSE
SCREW PPHM #6-32 X 1/2
WASHER LOCK #6
WASHER FLAT #6 ZINC
SCREW PPHM #8-32 X 1/2
WASHER LOCK M4
WASHER FLAT #8 ZINC
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
023897
076009A
040213
0A3394
082573
076020
032300
022676
064009
061945
076037
070081
070043
070045
070042
15
1
4
1
1
1
1
1
1
1
1
1
1
1
1
NUT HEX #8-32 STEEL
NUT HEX #6-32 STEEL
SCREW PHTT #6-32 X 1/2 ZYC
SCREW PHTT #6-32 X 5/8 ZYC
SCREW SWAGE 8-32 X 1/2 Z/YC
DECAL AVR COVER
FUSE & HOLDER LITTEL 7.5A
FUSE 7.5AXBK/AGC7.5NX W/22670
SCREW HHTT M5-0.8 X 10 BP
DECAL, WARNING REMOVE FUSE
FUSE 15A X AGC15
LIGHT 12VDC .02A LED RED PILOT
SWITCH SELECTOR 6A AMP/V
VOLTMETER DC 8-18V
HOURMETER
VOLTMETER AC 0-300
1
AMMETER AC 0-200
FREQUENCY METER 240V 55-65HZ
* PART OF CONTROL PANEL WIRE HARNESS
®
Generac Power Systems, Inc. 37
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Connection Box – Drawing No. 0E6892-A
®
38 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Connection Box – Drawing No. 0E6892-A
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
0E6353
0D5489
0E6427
023484N
0E6454
056739
0C2454
051715
0D3388
058710
0D5492
(048766)
022985
0E6689
022264
052813
039253
022145
0D5840
022129
045771
022287
022473
022097
022127
0E4458
0E5586
0E5587
022237
022241
081320
048527
0D5464B
057073
0C2266
1
1
1
2
1
1
2
2
1
2
1
REF.
2
1
2
2
4
6
1
5
5
28
36
34
6
1
1
1
4
2
2
2
1
2
4
LOWER PANEL 15
COVER LOWER CONNECTION BOX
PLATE GLAND
BUSHING SNAP SB-2.5-31
BRACKET NEUTRAL
RELAY SOLENOID 12VDC PNL MNT
SCREW THF M6-1X16 N WA Z/JS
NUT HEX M4-0.7 G8 YEL CHR
DECAL REMOTE START CONNECTION
TRANSFORMER 200A TO 5A 5VA
HARNESS LOWER PANEL 4.3L GRDN
BLOCK TERM 20A 2 X 6 X 1100V
WASHER FLAT #6 ZINC
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
COVER LOWER
WASHER LOCK M4
SCREW HHC M4-0.7 X 20 G8.8
SCREW HHC M8-1.25 X 20 G8.8
WASHER FLAT 5/16 ZINC
DECAL CUSTOMER CONNECTN FOR TS
WASHER LOCK M8-5/16
NUT HEX M8-1.25 G8 YEL CHR
SCREW HHC 1/4-20 X 3/4 G5
WASHER FLAT 1/4 ZINC
WASHER LOCK M6-1/4
NUT HEX 1/4-20 STEEL
CB 0200A 240V 2P S QJ22B200HL
PLATE CB MOUNT S (QJ 2P) 390S
COVER TERMINALS S (QJ 2P)
WASHER LOCK 3/8
NUT HEX 3/8-16 STEEL
SCREW SHC 1/4-20 X 4.5 G8.8 NZ
SCREW SHC 3/8-16 X 3/4 G5
NEUTRAL BLOCK 390/200-400A
JUNCTION BLOCK 3/8-16
SCREW PHTT M5-0.8 X 16 ZYC
®
Generac Power Systems, Inc. 39
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Generator – Drawing No. 0E6891
®
40 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Generator – Drawing No. 0E6891
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
051768
051769
0A8240
039253
022129
082130D
0C4286
0A2601
0A2602
0A1138
021941
020808A
052624
070892
0A5580
0A1633
020729A
022131
022237
022511
068113
0E6353
043123
051779
046852
022145
039287
071641
071639
0A2110
022473
022746
031980
083549
0A4089
7
7
2
6
7
1
1
1
1
1
1
1
1
1
4
4
1
12
11
11
1
1
4
4
1
1
4
1
1
2
8
1
2
1
1
SCREW HHC M12-1.75 X 25 G8.8
WASHER LOCK M12
FLEX PLATE SAE10
SCREW HHC M8-1.25 X 20 G8.8
WASHER LOCK M8-5/16
ASSEMBLY MAG PICKUP 72"
ASSEMBLY FAN W/PRESS DISC 10.75 X 3
SCREW HHC M16-2.0 X 45 G8.8
WASHER FLAT .688 ID X 3.25 OD
KEY SQ 3/8 X 2-1/2 STEEL
COUPLER 390 SAE
ROTOR 390 40 1P DIRECT
BEARING BALL 6212 SEALED
SLIP RING -MACHINED-
SCREW HHC M14-2.0 X 140 G8.8
WASHER 390 SAE ALT.
STATOR 390 40 AD2 SAE
WASHER FLAT 3/8-M10 ZINC
WASHER LOCK 3/8
SCREW HHC 3/8-16 X 1-1/4 G5
CARRIER REAR BEARING 15"
LOWER PANEL 15
6
7
8 *
9 *
10 *
11 *
12
13 *
14 *
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
WASHER LOCK M14
NUT HEX M14-2.0 G8 YEL CHR
SCREW HHTT #10-32 X 1/4 CZ
WASHER FLAT 5/16 ZINC
SCREW HHC M8-1.25 X 45 G8.8 FT
BRUSH HOLDER ASSEMBLY
HOLDER BRUSH SUPPORT
SCREW SWAGE 1/4-20 X 1/2 Z/YC
WASHER FLAT 1/4 ZINC
SCREW HHC 3/8-16 X 1-3/4 G5
TIE WRAP UL 14.6 X .14 NATL
SLEEVE RUBBER
ASSEMBLY SCROLL 390 SAE
KIT 0A4089 PARTS
36
37
38
39
40
41
42
43
0A2491
0A2497
0A2496
056326
022097
045757
047411
0A2110
2
2
2
SHROUD ALTERNATOR SHEET METAL
SCREEN SHROUD SAE
BRACKET TENSIONER SAE SCROLL
TRIM VINYL BLACK 1/8 GP
WASHER LOCK M6-1/4
SCREW HHC M6-1.0 X 25 G8.8
SCREW HHC M6-1.0 X 16 G8.8
SCREW SWAGE 1/4-20 X 1/2 Z/YC
8.4 FT
6
2
4
12
* ROTOR REPLACEMENT PARTS
®
Generac Power Systems, Inc. 41
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Engine – Drawing No. 0D6980-D
®
42 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Engine – Drawing No. 0D6980-D
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
6
0A9046
0A9118A
070022
0A6021
059056A
0A9050
022237
045772
049226
051716
0A4244
0A4215
0A4231
059057
0A2440
026568
099729A
061012
069939
035606
0A4930B
0A4084
029745
044101
023152
022131
058030
0A4085
0A3928
0C7947A
057794
0A4277
022241
057795A
048191
032303
0A3852
098239
0E0561
0D2244M
075885
0C7947B
1
1
1
6
1
2
17
1
1
1
1
1
1
10"
2
2
1
1
1
1
1
1
3
2
2
2
2
1
1
2
2
1
4
1
2
6
3
1
1
1
1
2
ENGINE 4.3L GM
FLYWHL 4.3L GM SAE
WASHER STAR M12 EXT
SCREW HHC 7/16-20 X 1 G8
STARTER 5.7L/7.4L GM
8
9
BOLT STARTER 4.3L
WASHER LOCK 3/8
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
NUT HEX M10-1.5 G8 YEL CHR
WASHER LOCK M5
NUT HEX M5-0.8 G8 YEL CHR
CONNECTOR COIL TO DISTRIBUTOR
DIP STICK 4.3L GM
TUBE DIP STICK 4.3L
HOSE 3/4 ID SAE-30R2
GASKET THERMOSET
SCREW HHC 3/8-16 X 2-3/4 G5
HOUSING THERM IMPREX
PLUG STD PIPE 1/8 SOCKET HEAD
HOUSING THERMOSTAT/WATER INLET
SENSOR HI COOLANT SHUTDOWN
HEAT SHIELD RIGHT
MOUNT ENGINE
SCREW HHC 3/8-16 X 1 G5
BRACKET SUPPORT SPARK PLUG WIRE
SCREW HHC 3/8-16 X 3/4 G5
WASHER FLAT 3/8-M10 ZINC
RETAINER PLUG WIRES
GASKET EXHAUST MANIFOLD
MANIFOLD RIGHT EXHAUST
U BOLT 3/8-16 2.5" I.D.
RETAINER SPARK PLUG WIRES
WIRES SPARK PLUG 4.3L
NUT HEX 3/8-16 STEEL
BARBED EL 90 3/4 PLASTIC
PIN DOWEL M10 X 24
SCREW HHC 3/8-16 X 3-1/2 G5
PLATE FLEX GM
CASTING ADAPTOR
ASSY WATER LEVEL SENSOR
ASSY MAGPICKUP (3/8-24 MALE) (MODEL 004626 0NLY)
THERMOSTAT 195 DEG
SADDLE 2 1/2"
*
*
0D6979
0A4308
1
1
40KW GUARDIAN WIRE HARNESS (NOT SHOWN FOR MOD. 004626-0)
HARNESS 4.3L STD WIRE (NOT SHOWN FOR MOD. 004373-1)
®
Generac Power Systems, Inc. 43
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Engine – Drawing No. 0A4304-N
®
44 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Engine – Drawing No. 0A4304-N
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
0A9046
0A4084
0A4239
0A4240
0A5640
0A5640A
0A5639
0D3293A
077996
057823
035579
037065
022302
0A8584
052644
0A4278A
0A4930A
0A4085
0A3927
0C7947A
0A1232
0A7801B
021928
0C6239
0A4241
0C2885
0A5737C
022131
077456
044117
057823
057448
022129
022142
048614
022237
029745
042633
033819
022241
0A5768
046526
049814
0C3756
045772
0A37970172
052259
055934D
0A37970001
0A1646
056739
0C7947B
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
8
1
1
1
1
8
4
4
12
4
3
1
4
1
5
2
1
2
8
1
1
1
1
1
2
ENGINE 4.3L GM
MOUNT ENGINE (R & L)
PULLEY CRANKSHAFT
PULLEY WATER PUMP
SPACER FAN 50MM 4.3L (35KW UNITS ONLY)
SPACER FAN 62MM (45KW UNITS ONLY)
FAN 17" REVRS ROT (35KW UNITS ONLY)
FAN COOLING 22" DIA REVRS ROT (45KW UNITS ONLY)
CAP HOSE
CLAMP HOSE #10 .56 - 1.06
BUSHING REDUCER 1/4 TO 1/8
SCREW HHC 7/16-20 X 2-1/4 G5
WASHER LOCK 7/16
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
SWITCH OIL PRESSURE
SPACER .5 X 1.5 X .25 STL/ZINC
BELT SERPENTNE 72.5"
HEAT SHIELD LEFT
GASKET EXHAUST MANIFOLD
MANIFOLD LEFT EXHAUST
U BOLT 3/8-16 2.5" I.D.
DC ALTERNATOR ASSEMBLY
PULLEY PLOY-V 82 OD.
BRACKET ALT. SUPPORT
BRACKET MOUNTING WELD ASSEMBLY
PULLEY GROOVED IDLER
PULLEY TENSIONER
SPACER DC ALTERNATOR 34MM
WASHER FLAT 3/8-M10 ZINC
ADAPTOR M12-1.75 3/8 NPT
BARBED STRAIGHT 3/8 NPT X 5/8
CLAMP HOSE #10 .56 - 1.06
HOSE 5/8 ID TYPE 3 SINGLE (12")
WASHER LOCK M8-5/16
SCREW HHC 5/16-18 X 3/4 G5 (45KW)
SCREW HHC 5/16-24 X 3/4 G5
WASHER LOCK 3/8
SCREW HHC 3/8-16 X 1 G5
SCREW HHC 3/8-24 X 1 G5
SCREW HHC 3/8-16 X 4 G5
NUT HEX 3/8-16 STEEL
WASHER FLAT HEAVY DUTY
WASHER LOCK M10
SCREW HHC M10-1.5 X 25 G8.8
BOLT TENSIONER PULLEY
NUT HEX M10-1.5 G8 YEL CHR
SPARK PLUG
WASHER FLAT M12
CLAMP VINYL 1.06 X .406 Z
FILTER OIL
WASHER FLAT M16
RELAY SOLENOID 12VDC PNL MNT (NOT SHOWN)
SADDLE 2 1/2"
®
Generac Power Systems, Inc. 45
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
4.3L Radiator – Drawing No. 0D7992-E
®
46 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
4.3L Radiator – Drawing No. 0D7992-E
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
0D7825A
0D8251
0D8252
024655
022097
022473
0D7174
0D7174A
0D7870
035685
047290
040173
036865
029032
052250
058443
029745
022237
022131
0D7850
076749
0D7975
090388
048031C
0C4341
0A6984
0D7942
0D7943
022413
022097
022473
0D7924
024655
022097
022473
090283
1
1
1
4
4
4
1
1
1
4
1
2
1
1
3
10
4
4
4
1
1
1
1
1
2
1
1
1
8
8
8
1
4
4
4
1
RADIATOR COPPER BRASS
FAN GUARD BOTTOM
FAN GUARD TOP
SCREW HHTT 1/4-20 X 1 CZ
WASHER LOCK M6-1/4
WASHER FLAT 1/4 ZINC
VENTURI 4.3L 22" FAN
VENTURI 4.3L 17" FAN
9
10
11
12
14
15
16
17
18
19
20
21
22
23
24
27
29
30 *
31 *
32 *
33 *
34 *
35 *
36 **
37 **
38 **
39 **
40
RADIATOR HOSE LOWER
CLAMP HOSE #28 1.32 - 2.25
HOSE 3/8 ID SINGLE BRAID
CLAMP HOSE #5.5 .62 - .62
DRAINCOCK
HOSE 9/32 ID (64" LG)
TAPE FOAM 1 X 1 (29" LG)
SCREW CRIMPTITE 1/4-20 X 5/8
SCREW HHC 3/8-16 X 1 G5
WASHER LOCK 3/8
WASHER FLAT 3/8-M10 ZINC
RADIATOR HOSE UPPER
BOTTLE COOLANT RECOVERY
WATER BOTTLE BRACKET
SCREW HHTT M6-1.0 X 12 YC
CLAMP HOSE BAND 1/4
SUPPORT RADIATOR A GRP
BRACKET AIR DUCT TOP/BOT
SUPPORT AIR DUCT RH SIDE
SUPPORT AIR DUCT LH SIDE
SCREW HHC 1/4-20 X 1 G5
WASHER LOCK M6-1/4
WASHER FLAT 1/4 ZINC
SCREEN FRONT
SCREW HHTT 1/4-20 X 1 CZ
WASHER LOCK M6-1/4
WASHER FLAT 1/4 ZINC
CAP RADIATOR 13 PSI-FOR SERVICE ONLY
* OPTIONAL WITH KIT 0D7948
** OPTIONAL WITH KIT 0D7947
®
Generac Power Systems, Inc. 47
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators
4.3L Exhaust – Drawing No. 0E0704-A
1
21
20
24
21
20
24
23
19
19
6
19
22
19
19
19
8
9
19
3
19
5
13
18
14
7
18
16
15
14
11
4
13
15
13
10
TO
COMPARTMENT
FRONT
TO ENGINE
15
TO ENGINE
12
14
5
4
18
10
ITEM PART NO. QTY.
DESCRIPTION
ITEM PART NO. QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
059902A
0C9641
0C9650
0C4114A
0C4126
0D5787
0A5215B
0E0699
0E0698
0C4170
0C4305
0C2454
1
1
1
2
2
1
2
1
1
2
1
2
CAP RAIN 2.50 / 2.69
13
14
15
16
18
19
20
21
22
23
24
0C3433A
022129
022145
0C9748
042907
080762
022237
022241
0E0701
0E0700
022131
4
12
12
1
12
6
12
12
1
CLAMP BAND 2.5"
TUBE STRAIGHT 'A' GROUP
MUFFLER 2-1/2" INLET/OUTLET
CLAMP BAND MUFFLER 6.5"
BRACKET MUFFLER MOUNTING
TUBE ELBOW 90 DEG 2.5"
PIPE FLEX 2.5"
TUBE, CROSS OVER
TUBE, 90 ELBOW
BRACKET EXHAUST SHIELD
SHIELD A-GRP HEAT
SCREW TH-FRM M6-1 X 16 N WA
Z/JS
WASHER LOCK M8-5/16
WASHER FLAT 5/16 ZINC
PLUG M18-1.5
SCREW HHC M8-1.25 X 16 G8.8
BOLT U 3/8-16 X 2.62
WASHER LOCK 3/8
NUT HEX 3/8-16 STEEL
SHIELD, CROSSOVER HEAT
SHIELD, EXHAUST HEAT
WASHER FLAT 3/8-M10 ZINC
10
11
12
1
8
®
48 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
4.3L Air Cleaner – Drawing No. 0E0712-A
1
2
3
4
7
5
8
6
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
037561
0A4632A
0A4637
0A4632B
062522
022127
057796
057795A
1
1
1
1
1
1
1
1
NUT WING 1/4-20 NYLK
PLATE AIR CLEANER TOP
FILTER AIR 11.5" CA326
PLATE,AIR CLEANR BOT
STUD TH 1/4-20 X 3 G2 ZNC FULL
NUT HEX 1/4-20 STEEL
GROMMET
BARBED EL 90 3/4 PLASTIC
®
Generac Power Systems, Inc. 49
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators
4.3L Nat. Gas Fuel System – Drawing No. 0E7011-B
®
50 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators
4.3L Nat. Gas Fuel System – Drawing No. 0E7011-B
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
065907
026812
028238
0C7598
026490
026577
055944
028237
0E0521
022259
022145
022129
030795
025655
022132
051778
028641
057824
057422
043123
051779
082508
050279
026915
055934P
0A5737C
0D1509
061258
0A7631
029745
022237
052865
033212
0A4120
064945
044074
0A4121
047290
036409
022097
0A5763
1
3
2
1
2
2
1
2
1
4
6
6
2
1
2
2
2
2
1
2
2
REF
1
3
1
REF
1
1
1
2
2
1
2
1
1
SUPPORT SOLENOID NAT GAS
ELBOW 90D 3/4 NPT
BOLT U 5/16-18 X 1.50
ASSY NATURAL GAS SOLENOID
NIPPLE PIPE 3/4 NPT X 2
BUSHING REDUCER 1 TO 3/4
REGULATOR NAT GAS LPG VAPOR
SADDLE 1-3/8
SUPPORT REGULATOR
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26**
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
NUT HEX 5/16-18 STEEL
WASHER FLAT 5/16 ZINC
WASHER LOCK M8-5/16
SCREW HHC 5/16-18 X 1 G5
PLUG STD PIPE 3/4 STEEL SQ HD
WASHER FLAT 9/16 ZINC
SCREW HHC M14-2.0 X 25 G8.8
NIPPLE TOE 3/4 NPT X 2
CLAMP HOSE #16 .87 - 1.50
HOSE 1IN ID LP GAS (42" LG)
WASHER LOCK M14
NUT HEX M14-2 G8 YEL CHR
BALL JOINT PLA .25-28
DECAL FUEL INLET NG
NIPPLE CLOSE 3/4 X 1.375
CLAMP VINYL 1.62 X .486 Z
SPACER D.C. ALT. (29MM LONG) (NOT SHOWN)
DECAL INLET PRESSURE
GASKET AIR CLEANER
CARB. REWORK 4.3L
SCREW HHC 3/8-16 X 1 G5
WASHER LOCK 3/8
GASKET CARBURETOR
SCREW HHC 5/16-18 X 1-1/4 G5
ADAPTOR CARBURETOR W/INLET
GASKET CARBURETOR ADAPTOR
BARBED STR 1/8NPT X 3/8
VALVE PCV
HOSE 3/8 ID SINGLE BRAID (10")
NUT HEX 1/4-28 STEEL
WASHER LOCK M6-1/4
1
1
1
1
1
1
ARM THROTTLE-REWORK
**NOT SHOWN
®
Generac Power Systems, Inc. 51
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators
4.3L Nat. Gas Fuel System – Drawing No. 0E7013-B
®
52 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators
4.3L Nat. Gas Fuel System – Drawing No. 0E7013-B
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
065907
026812
022259
0C7598
026490
026577
0D2758
0E0521
028237
028238
022145
022129
030795
025655
022132
051778
028641
057824
057422
043123
051779
0C7820
050279
026915
055934P
0A5737C
0D1509
061258
0C7650A
029745
022237
0C7059
033212
0A4120
064945
044074
0A4121
047290
0C7060
0D3485
022152
0C7908
0A6613
064090
1
3
4
1
2
2
1
1
2
2
6
6
2
1
2
2
2
2
1
2
2
1
1
3
1
REF
1
1
1
2
2
1
4
1
1
1
1
1
1
1
4
4
1
4
SUPPORT SOLENOID NAT GAS
ELBOW 90D 3/4NPT
NUT HEX 5/16-18 STEEL
ASSY NATURAL GAS SOLENOID
NIPPLE PIPE 3/4 NPT X 2
BUSHING REDUCER 1 TO 3/4
REGULATOR N/G (R600S)
SUPPORT REGULATOR
SADDLE 1-3/8
BOLT U 5/16-18 X 1.50
WASHER FLAT 5/16 ZINC
WASHER LOCK M8-5/16
SCREW HHC 5/16-18 X 1 G5
PLUG STD PIPE 3/4 STEEL SQ HD
WASHER FLAT 9/16 ZINC
SCREW HHC M14-2.0 X 25 G8.8
NIPPLE TOE 3/4 NPT X 2
CLAMP HOSE #16 .87 - 1.50
HOSE 1IN ID LP GAS (44" LG)
WASHER LOCK M14
NUT HEX M14-2 G8 YEL CHR
MACHINING, CARBURETOR ADAPTOR
DECAL FUEL INLET LPG
NIPPLE CLOSE 3/4 X 1.375
CLAMP VINYL 1.62 X .486 Z
SPACER, D.C. ALT. (29MM LONG)
DECAL INLET PRESSURE
GASKET AIR CLEANER
MIXER (EMISSIONS) NATURAL GAS
SCREW HHC 3/8-16 X 1 G5
WASHER LOCK 3/8
GASKET GOVERNOR THROTTLE BODY
SCREW HHC 5/16-18 X 1-1/4 G5
ADAPTOR CARBURETOR W/INLET
GASKET CARBURETOR ADAPTOR
BARBED STR 1/8NPT X 3/8
VALVE PCV
HOSE 3/8 ID SINGLE BRAID (10")
GASKET CARBURETOR ADAPTOR
ASSY THROTTLE PF42 WIRE CONN
WASHER LOCK #10
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26 **
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
SCREW SHC #10-32 X 5/8 G8.8 NZ
GASKET CARB IMPCO 225
SCREW PHM SEMS #12-24 X 5/8 EX
** NOT SHOWN
®
Generac Power Systems, Inc. 53
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators
Exhaust – Drawing No. 0E1347-A
®
54 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0046262, 0046263 & 0046264) Guardian Liquid-cooled 40 kW Generators
Exhaust – Drawing No. 0E1347-A
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
6
7
8
9
059902A
0C9641
0D4208
0D5061
0C4126
0D5787
0A5215B
0E0699
0E0698
0C4170
0C4305
0C2454
0C3433A
022129
022145
045771
042907
080762
022237
022241
0E0701
0E0700
077879
0D4221
0D4512
043116
022471
022264
038150
036918
049811
022097
049813
0D8780
022131
1
1
1
4
2
1
2
1
1
2
1
2
4
16
20
4
16
6
12
12
1
1
1
1
1
2
5
5
8
5
2
2
2
1
8
CAP RAIN 2.50 / 2.69
TUBE STRAIGHT 'A' GROUP
MUFFLER CATALYST 4.3L
MOUNTING BAND A-GRP CATALYST
BRACKET MUFFLER MOUNTING
TUBE ELBOW 90 DEG 2.5"
PIPE FLEX 2.5"
TUBE, CROSS OVER
TUBE, 90 ELBOW
BRACKET EXHAUST SHIELD
SHIELD A-GRP HEAT
SCREW TH-FRM M6-1 X 16 N WA Z/JS
CLAMP BAND 2.5"
10
11
12
13
14
15
16
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
WASHER LOCK M8-5/16
WASHER FLAT 5/16 ZINC
NUT HEX M8-1.25 G8 YEL CHR
SCREW HHC M8-1.25 X 16 G8.8
BOLT U 3/8-16 X 2.62
WASHER LOCK 3/8
NUT HEX 3/8-16 STEEL
SHIELD, CROSSOVER HEAT
SHIELD, EXHAUST HEAT
HOSE VACUUM 5/32 (36"LG)
KIT AIR/FUEL RATIO CONTROLLER
BRACKET AIR/FUEL CONTROLLER
SCREW HHC M6-1.0 X 12 G8.8
NUT HEX #8-32 STEEL
WASHER LOCK #8-M4
WASHER FLAT #8 ZINC
SCREW PPHM #8-32 X 1/2
WASHER FLAT M6
WASHER LOCK M6-1/4
NUT HEX M6 X 1.0 G8 YEL CHR
DECAL IMPORTANT EXHAUST EMISSION INFO
WASHER FLAT 3/8-M10 ZINC
*NOTE: COMPONENT INSTALLED AT WAUKESHA FACILITY
®
Generac Power Systems, Inc. 55
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
(Model No. 0043733, 0043734 & 0043735) Guardian Liquid-cooled 40 kW Generators
Electronic Governor – Drawing No. 0A2615-F
ITEM
PART NO.
QTY.
DESCRIPTION
1
2
3
4
5
098290
0A3439
098958A
021888
082508
036409
043146
098941A
098942A
098225
022097
064526
029333A
074031
051716
049226
076040
098647
036409
0C2184
1
1
1
1
2
2
3
2
2
4
4
1
1
-
2
2
2
1
2
1
ASSEMBLY MOTOR STEPPER
BRACKET GOVERNOR MOUNTING
CONNECTOR INTERFACE ASSEMBLY
LEVER STEPPER MOTOR
BALL JOINT 1/4-28
NUT HEX 1/4-28 STEEL
SCREW HHC M6-1.0 X 10 G8.8
HOUSING GOVERNOR CONNECT
COVER CONN HOUSING
SCREW FHM #2 X 5/8 SELF TAP
WASHER LOCK M6-1/4
SCREW TAP HWH #6-25 X 3/8 ZINC
TIE WRAP 7.4" X .19" BLACK UL
NEOPRENE LIQUID COATING (NOT SHOWN)
NUT HEX M5-0.8 G8 YEL CHR
WASHER LOCK M5
9
11
12
13
14
15
16
17
18
19
20
21
22
23
24
SCREW PPHM M5-0.8 X 16
ASSEMBLY L.C. ELECTRONIC GOVERNOR
NUT HEX 1/4-28 STEEL
STUD THR 1/4-28 X 3-1/2 G2 ZINC
®
56 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 8 — Exploded Views and Parts Lists
Guardian Liquid-cooled 40 kW Generators
Engine Coolant Heater – Drawing No. 0E2352-A
TO THERMOSTAT
HOUSING
TO ENGINE
BLOCK
**16
**7
1
2
**6
3
4
4
**5
8
**6
9
2
10
11
9
12
8
12
13
ITEM
PART NO. QTY. DESCRIPTION
ITEM
PART NO. QTY. DESCRIPTION
1
2
3
4
5
0C4905
057822
077043E
050967
0A6283
1
2
1
1
1
BARBED EL 45 FITTING
CLAMP HOSE #8 .53-1.00
CONDUIT FLEX 1" BLACK (15"LG)
HOSE 5/8 ID RIA 250F (46"LG)
HOSE PREFORMED BLOCK
HEATER
CLAMP HOSE #8 .53-1.00
BARBED EL 45 3/8NPT X 5/8OD
SCREW HHC M6-1.0 X 20 G8.8
WASHER FLAT 1/4-M6 ZINC
HEATER ENG 1000W 120V
HEATER BLOCK 1000W 240V
11
12
13
14
084427
022097
049813
055934D
1
4
2
1
BRACKET HEATER W/WELDNUTS
WASHER LOCK M6-1/4
NUT HEX M6 X 1.0 G8 YEL CHR
CLAMP VINYL 1.06 X .406 Z (NOT
SHOWN)
CONDUIT FLEX .38 ID (42"LG) (NOT
SHOWN) (USED ON HEATER
CORD)
15
16
077043A
062303
1
1
6
7
8
9
10
057822
0C4905
042568
022473
084918A
*084918B
2
1
4
4
1
1
ADAPTOR 1/4" NPT TO 3/8" NPT
*USED ON 50HZ VOLTAGE GENERATORS ONLY.
**USED ON NATURAL GAS & L/P VAPOR UNITS ONLY.
®
Generac Power Systems, Inc. 57
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 9 – Notes
Guardian Liquid-cooled 40 kW Generators
®
58 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 9 – Notes
Guardian Liquid-cooled 40 kW Generators
®
Generac Power Systems, Inc. 59
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 10 – Warranty
Guardian Liquid-cooled 40 kW Generators
CALIFORNIA EMISSION CONTROL WARRANTY STATEMENT
YOUR WARRANTY RIGHTS AND OBLIGATIONS
The California Air Resources Board (CARB) and Generac Power Systems, Inc. (Generac) are pleased to explain the Emission
Control System Warranty on your new engine.* In California, new utility, and lawn and garden equipment engines must be
designed, built and equipped to meet the state’s stringent anti-smog standards. Generac will warrant the emission control
system on your engine for the periods of time listed below provided there has been no abuse, neglect, unapproved modifi-
cation or improper maintenance of your engine.
Your emission control system may include parts such as the carburetor, ignition system and exhaust system. Generac will
repair your engine at no cost to you for diagnosis, replacement parts and labor, should a warrantable condition occur.
MANUFACTURER’S EMISSION CONTROL SYSTEM WARRANTY COVERAGE:
Emissions control systems on 1995 and later model year engines are warranted for two years as hereinafter noted. If, dur-
ing such warranty period, any emission-related component or system on your engine is found to be defective in materials or
workmanship, repairs or replacement will be performed by a Generac Authorized Warranty Service Facility.
PURCHASER’S/OWNER’S WARRANTY RESPONSIBILITIES:
As the engine purchaser/owner, you are responsible for the completion of all required maintenance as listed in your factory
supplied Owner’s Manual. For warranty purposes, Generac recommends that you retain all receipts covering maintenance
on your engine. However, Generac cannot deny warranty solely due to the lack of receipts or for your failure to ensure the
completion of all scheduled maintenance.
As the engine purchaser/owner, you should, however, be aware that Generac may deny any and/or all warranty coverage or
responsibility if your engine, or a part/component thereof, has failed due to abuse, neglect , improper maintenance or unap-
proved modifications, or the use of counterfeit and/or “grey market” parts not made, supplied or approved by Generac.
You are responsible for presenting your engine to a Generac Authorized Warranty Service Facility as soon as a prob-
lem occurs. The warranty repairs should be completed in a reasonable amount of time, not to exceed 30 days.
Warranty service can be arranged by contacting either your selling dealer or a Generac Authorized Warranty Service Facility.
To locate the Generac Authorized Warranty Service Facility nearest you, call our toll-free number:
1-800-333-1322
IMPORTANT NOTE: This warranty statement explains your rights and obligations under the Emission Control System
Warranty (ECS Warranty), which is provided to you by Generac pursuant to California law. See also the “Generac Limited
Warranties for Generac Power Systems, Inc.,” which is enclosed herewith on a separate sheet, also provided to you by
Generac. The ECS Warranty applies only to the emission control system of your new engine. If there is any conflict in terms
between the ECS Warranty and the Generac Warranty, the ECS Warranty shall apply except in circumstances where the
Generac Warranty may provide a longer warranty period. Both the ECS Warranty and the Generac Warranty describe impor-
tant rights and obligations with respect to your new engine.
Warranty service can be performed only by a Generac Authorized Warranty Service Facility. When requesting warranty serv-
ice, evidence must be presented showing the date of the sale to the original purchaser/owner.
If you have any questions regarding your warranty rights and responsibilities, you should contact Generac at the fol-
lowing address:
ATTENTION WARRANTY DEPARTMENT
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297
WHITEWATER, WI 53190
Part 1
®
60 Generac Power Systems, Inc.
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 10 – Warranty
Guardian Liquid-cooled 40 kW Generators
EMISSION CONTROL SYSTEM WARRANTY
Emission Control System Warranty (ECS Warranty) for 1995 and later model year engines:
(a) Applicability: This warranty shall apply to 1995 and later model year engines. The ECS Warranty Period shall begin on
the date the new engine or equipment is purchased by/delivered to its original, end-use purchaser/owner and shall con-
tinue for 24 consecutive months thereafter.
(b) General Emissions Warranty Coverage: Generac warrants to the original, end-use purchaser/owner of the new engine or
equipment and to each subsequent purchaser/owner that each of its engines is ...
(1) Designed, built and equipped so as to conform with all applicable regulations adopted by the CARB pursuant to its
authority, and
(2) Free from defects in materials and workmanship which, at any time during the ECS Warranty Period, may cause a war-
ranted emissions-related part to fail to be identical in all material respects to the part as described in the engine man-
ufacturer’s application for certification.
(c) The ECS Warranty only pertains to emissions-related parts on your engine, as follows:
(1) Any warranted, emissions-related parts that are not scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the ECS Warranty Period. If any such part fails during the ECS Warranty Period, it shall
be repaired or replaced by Generac according to Subsection (4) below. Any such part repaired or replaced under the
ECS Warranty shall be warranted for the remainder of the ECS Warranty Period.
(2) Any warranted, emissions-related part that is scheduled only for regular inspection as specified in the Owner’s Manual
shall be warranted for the ECS Warranty Period. A statement in such written instructions to the effect of “repair or
replace as necessary” shall not reduce the ECS Warranty Period. Any such part repaired or replaced under the ECS
Warranty shall be warranted for the remainder of the ECS Warranty Period.
(3) Any warranted, emissions-related part that is scheduled for replacement as required maintenance in the Owner’s
Manual shall be warranted for the period of time prior to the first scheduled replacement point for that part. If the part
fails prior to the first scheduled replacement, the part shall be repaired or replaced by Generac according to Subsection
(4) below. Any such emissions-related part repaired or replaced under the ECS Warranty shall be warranted for the
remainder of the ECS Warranty Period prior to the first scheduled replacement point for such emissions-related part.
(4) Repair or replacement of any warranted, emissions-related part under this ECS Warranty shall be performed at no
charge to the owner at a Generac Authorized Warranty Service Facility.
(5) When the engine is inspected by a Generac Authorized Warranty Service Facility, the owner shall not be held responsi-
ble for diagnostic costs if the repair is deemed warrantable.
(6) Generac shall be liable for damages to other original engine components or approved modifications proximately caused
by a failure under warranty of any emission-related part covered by the ECS Warranty.
(7) Throughout the ECS Warranty Period, Generac shall maintain a supply of warranted emission-related parts sufficient
to meet the expected demand for such emission-related parts.
(8) Any Generac authorized and approved emission-related replacement part may be used in the performance of any ECS
Warranty maintenance or repairs and will be provided without charge to the owner. Such use shall not reduce Generac
ECS Warranty obligations.
(9) Unapproved, add-on, modified, counterfeit and/or “grey market” parts may not be used to modify or repair a Generac
engine. Such use voids this ECS Warranty and shall be sufficient grounds for disallowing an ECS Warranty claim.
Generac shall not be held liable hereunder for failures of any warranted parts of a Generac engine caused by the use of
such an unapproved, add-on, modified, counterfeit and/or “grey market” part.
EMISSION RELATED PARTS INCLUDE THE FOLLOWING:
1) Fuel Metering System:
3) Ignition System including:
a) Spark plug
b) Ignition module
1.2) LPG/Natural Gas carburetion assembly and its internal
components.
a) Fuel controller (if so equipped)
4) Catalytic Muffler Assembly (if so equipped) including:
a) Muffler gasket
b) Exhaust manifold
b) Mixer and its gaskets (if so equipped)
c) Carburetor and its gaskets (if so equipped)
d) Primary gas regulator (if so equipped)
e) LP liquid vaporizer (if so equipped)
5) Crankcase Breather Assembly including:
a) Breather connection tube
2) Air Induction System including:
a) Intake pipe/manifold
b) Air cleaner
*Generac engine types covered by this warranty statement include the following:
1) Prepackaged Standby Generator
2) Auxiliary Power Unit (APU) Generator
3) Standby Generator
Part 2
®
Generac Power Systems, Inc. 61
Download from Www.Somanuals.com. All Manuals Search And Download.
Section 10 – Warranty
Guardian Liquid-cooled 40 kW Generators
®
GENERAC POWER SYSTEMS "TWO YEAR" LIMITED WARRANTY FOR GUARDIAN
"PREPACKAGED EMERGENCY AUTOMATIC STANDBY GENERATORS"
For a period of two years from the date of original sale, Generac Power Systems, Inc. (Generac) warrants that its Guardian generator
will be free from defects in material and workmanship for the items and period set forth below. Generac will, at its option, repair or replace
any part which, upon examination, inspection and testing by Generac or a Guardian Authorized Warranty Service Dealer, is found to be
defective. Any equipment that the purchaser/owner claims to be defective must be examined by the nearest Guardian Authorized
Warranty Service Dealer. All transportation costs under the warranty, including return to the factory, are to be borne and prepaid by the
purchaser/owner. This warranty applies only to Generac Guardian prepackaged emergency automatic standby generators sold and
rated for use in "Standby" applications.
WARRANTY SCHEDULE
YEARS ONE and TWO - 100% (one hundred percent) transferable coverage on Labor and Part(s) listed (proof of purchase and main-
tenance is required):
Engine - All Components
Alternator - All Components
Transfer System - All Components
Steel enclosures are warranted against rusting for the first year of ownership only. Damage caused after receipt of generator is the
responsibility of the owner and is not covered by this warranty. Nicks, scrapes, dents or scratches to the painted enclosure should be
repaired promptly by the owner.
All warranty expense allowances are subject to the conditions defined in Guardian's Warranty Policies, Procedures and Flat Rate
Manual.
THIS WARRANTY SHALL NOT APPLY TO THE FOLLOWING:
• Guardian generators that utilize non-Guardian/Generac replacement parts.
• Guardian generators utilizing non-Guardian/Generac automatic transfer switches.
• Repairs or diagnostics performed by individuals other than Guardian/Generac authorized dealers not authorized in writing by
Generac Power Systems.
• Any Guardian generators used as rental or trailer mounted applications.
• Units used for prime power in place of existing utility power where utility power is present or in place of utility power where utility
power service does not normally exist.
• Costs of normal maintenance, adjustments, installation and start-up.
• Steel enclosures that are rusting due to the improper installation, location in a harsh or saltwater environment or scratched where
integrity of paint applied is compromised.
• Failures caused by any contaminated fuels, oils, coolants or lack of proper fluid amounts.
• Failures due, but not limited, to normal wear and tear, accident, misuse, abuse, negligence or improper installation. As with all
mechanical devices, the Generac engines need periodic part(s) service and replacement to perform well. This warranty will not
cover repair when normal use has exhausted the life of a part(s) or engine.
• Failures caused by any external cause or act of God, such as collision, theft, vandalism, riot or wars, nuclear holocaust, fire,
freezing, lightning, earthquake, windstorm, hail, volcanic eruption, water or flood, tornado or hurricane.
• Damage related to rodent and/or insect infestation.
• Products that are modified or altered in a manner not authorized by Generac in writing.
• Any incidental, consequential or indirect damages caused by defects in materials or workmanship, or any delay in repair or
replacement of the defective part(s).
• Failure due to misapplication.
• Telephone, cellular phone, facsimile, internet access or other communication expenses.
• Living or travel expenses of person(s) performing service, except as specifically included within the terms of a specific unit warranty
period.
• Expenses related to "customer instruction" or troubleshooting where no manufacturing defect is found.
• Rental equipment used while warranty repairs are being performed.
• Costs incurred for equipment used for removal and/or reinstallation of generator, (i.e.; cranes, hoists, lifts, etc.)
• Overnight freight costs for replacement part(s).
• Overtime labor.
• Starting batteries, fuses, light bulbs and engine fluids.
THIS WARRANTY IS IN PLACE OF ALL OTHER WARRANTIES, EXPRESSED OR IMPLIED. SPECIFICALLY, GENERAC MAKES
NO OTHER WARRANTIES AS TO THE MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE. Some states do not
allow limitations on how long an implied warranty lasts, so the above limitation may not apply to you.
GENERAC'S ONLY LIABILITY SHALL BE THE REPAIR OR REPLACEMENT OF PART(S) AS STATED ABOVE. IN NO EVENT
SHALL GENERAC BE LIABLE FOR ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES, EVEN IF SUCH DAMAGES ARE A
DIRECT RESULT OF GENERAC'S NEGLIGENCE. Some states do not allow the exclusion or limitation of incidental or consequential
damages, so the above limitation may not apply to you.
This warranty gives you specific legal rights. You also have other rights from state to state.
®
GENERAC POWER SYSTEMS, INC.
P.O. BOX 297 • WHITEWATER, WI 53190
Revision (02/01/05)
Part No. 0E7018
Revision D (06/02/05)
Printed in U.S.A.
Download from Www.Somanuals.com. All Manuals Search And Download.
|
Easton Sports Bicycle Accessories BearTrap User Manual
Fellowes Chipper T440C User Manual
FieldServer Computer Drive FS 8700 87 User Manual
Fiesta Gas Grill ESD45055 BC347 User Manual
Fisher Price Model Vehicle X5855 User Manual
Ford Car Stereo System 95 5025 User Manual
FujiFilm Camcorder BL01619 603 User Manual
Garland Cooktop GIU 18 User Manual
GE Portable Generator GEK 45404F User Manual
Giant Router LP122A 3100 User Manual