NOTIFIER NCA2/NFS2-3030 DESCRIPTION
The NCA2/NFS2-3030 Serial driver allows the FieldServer to record data from Notifier NCA2 or NFS2-3030 panels
over RS-232 as per NFS2-3030/NCA-2 EIA-232 Protocol & Data Formats 53219 Rev A 1/3/2008. There is no active
polling by this driver; the communications are one-way through the panel's printer or CRT port. The FieldServer
acts as a Client; receives messages and records the status of a Panel. The panel MUST output messages in160
characters ASCII format in English.
This driver is not capable of emulating a Notifier NCA2 or NFS2-3030 panel.
The NCA2 controls all the devices (e.g. 3030, 640 panels) connected on the Notifier network. Each Fire Alarm
Panel on Network is considered as a Node. 240 Nodes can exist on one network. NFS2-3030 can exist on a
network or be self-standing.
NCA2 interacts with other Fire Alarm Panels, records the status of the panels and sends the events to printer and
CRT ports. FieldServer captures these events in text form, parses and stores them in Data Arrays. These Data
Arrays can be monitored by third party tools. Since the FieldServer does not actively poll for data, the accuracy
and timeliness of the stored data is limited to the frequency of update messages that the Notifier Fire Panel issues.
If a networked panel does not send the 'CLEARED' message for latched points via the NCA2 it is not possible to
detect cleared points unless a system reset is done. It is possible to configure the FieldServer to clear on reset
Please note that the FieldServer can be configured with a large number of points. The point limits purchased with
the FieldServer prevent the entire database from being accessed in any one application. It is therefore strongly
advisable to ensure that only the point addresses of interest are configured, and that the FieldServer is purchased
with the correct point count.
The types of Notifier messages supported by this driver are summarized in Section 4.1. A detailed table presented
in Appendix A.1 shows each type of NCA2/NFS2-3030 message the FieldServer recognizes and the effect that it has
on the status of the points in the Data Array.
Max Nodes Supported
FieldServer Mode Nodes Comments
Client
Server
0
1
This Driver cannot be used as a Client.
Each FieldServer port can connect to only 1 Notifier panel port
2
DRIVER SCOPE OF SUPPLY
2.1 Supplied by FieldServer Technologies for this driver
FieldServer Technologies PART # Description
FS-8917-16
FS-8700-130
Pigtail cable for RJ45 Port
Driver Manual.
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 4 of 22
3
HARDWARE CONNECTIONS
The FieldServer is connected to the Notifier NCA2/NFS2-3030 Fire Panel as shown in the following connection
drawing.
Configure the Notifier Panel according to manufacturer’s instructions.
RJ45
Notifier NCA2/NFS2-3030
Rx (Brown)
Com (Blue/White)
Tx (Orange/White)
Connection to TB5 Printer
Port.
Printer
CRT
TB5
PTX PRX REF CTX CRX REF
FieldServer Part #
8917-16
Pigtail for RJ45
Port
Connect to one of the RS-232
Ports on the FieldServer
8
1
FieldServer
P1
Connector Pinouts
Function Receive
Pin CRX
Function Receive
Pin PRX
Function Transmit
Pin
Reference Transmit
REF CTX
Reference Transmit
TB5 CRT
TB5 Printer
REF
Com
4
PTX
Receive
1
RJ-45
8
Wire Color
Orange/white Blue/white Brown
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 5 of 22
3.1 Hardware Connection Tips / Hints
•
The FieldServer should preferably be connected to the TB5 Printer port. It is theoretically possible to
connect to the TB5 CRT port, but this has not been fully tested.
•
The Panel’s port must be enabled and set to 80 Columns Not Supervised.
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 6 of 22
4
CONFIGURING THE FIELDSERVER AS A NOTIFIER NCA2/NFS2-3030 CLIENT
For a detailed discussion on FieldServer configuration, please refer to the FieldServer Configuration Manual. The
information that follows describes how to expand upon the factory defaults provided in the configuration files
included with the FieldServer (See “.csv” sample files provided with the FieldServer).
This section documents and describes the parameters necessary for configuring the FieldServer to receive
information from a Notifier Panel.
4.1 Panel Status - Memory Mapping
The primary purpose of this driver is to record the status of devices connected to the Notifier panel by interpreting
the text messages sent to the printer or CRT port. Not all messages will be interpreted, as many messages do not
directly pertain to device status, or are not currently supported. The following subset of event messages is
recognized:
Active Events:
FIRE ALARM
SECURITY ALARM (LIFE)
LIFE CRITICAL ALARM
MEDICAL EMERGENCY
SECURITY ALARM
CRITICAL PROCESS
SUPERVISORY
TROUBLE/ FAULT
DISABLED
PREALARM
ACTIVE
ON/ OFF
This Driver divides the memory into various types. Each location in each memory type is assigned an address. It is
therefore possible to map an address to a particular offset in a Data Array and make it accessible for reading by
other connected devices. The address structure is provided in Table 1.
Most of these addresses will only contain binary information to represent an active or inactive state.
Where multiple troubles are associated with a single device the addressed register corresponding to that device
will be incremented as a counter for each trouble message and decremented when a trouble is cleared. These
addresses should preferably be stored in SINT16 format in the Data Array.
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 7 of 22
Parameter
Addresses
For each SLC loop per Node
Memory Type : Detector ; Module
Fire Alarm
1 – 159
Security Life
Life Critical
Medical Emergency
Security Alarm
Critical Process
Supervisory
Disabled
Prealarm
Active
ON/OFF
160 – 318
319 – 477
478 – 636
637 – 795
796 – 954
955 - 1113
1114 – 1272
1273 – 1431
1432 – 1590
1591 – 1749
Memory Type : Detector_Trouble; Module_Trouble
Troubles/Faults
1 – 159
Parameter
Addresses
For each Node
Memory Type : Node_Trouble
Troubles/Faults
1 – 508
Memory Type : Panel
Panel (Maximum12 Boards and 8 Panel circuits per Board )
Hardware address
Board 1 panel 1
Board 1 panel 2
Board 2 panel 1
-----
memory address
1
2
9
-----
Board 12 panel 8
)
96
Fire Alarm
1 – 96
Security Life
Life Critical
Medical Emergency
Security Alarm
Critical Process
Supervisory
Disabled
Prealarm
Active
ON/OFF
97 - 192
193 - 288
289 - 384
385 - 480
481 - 576
577 - 672
673 - 768
769 - 864
865 - 960
961 - 1056
Memory Type : Panel_Trouble
Troubles/Faults
1–96
Memory Type : Bell_Trouble
Troubles/Faults
1-4
Table 1 – Memory Mapping Address Structure.
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 8 of 22
4.2 Data Arrays/Descriptors
The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable
the FieldServer for Notifier NCA2/NFS2-3030 communications, the driver independent FieldServer buffers need to
be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side
Nodes” section, and the required data from Notifier Panels needs to be mapped in the “Client Side Map
Descriptors” section. Details on how to do this can be found below.
Note that in the tables, * indicates an optional parameter, with the bold legal value being the default.
Section Title
Data_Arrays
Column Title
Function
Legal Values
Up to 15 alphanumeric
characters
Data_Array_Name
Provide name for Data Array
Provide data format. Each Data Array can only take on one
format.
Data_Array_Format
Bit, Sint16, Float1
Number of Data Objects. Must be larger than the data
Data_Array_Length storage area required by the Map Descriptors for the data 1-10,000
being placed in this array.
Example 1
// Data Arrays
Data_Arrays
Data_Array_Name ,Data_Format ,Data_Array_Length
DA_SYS_N2
DA_N2L01D
,SINT16
,BIT
,SINT16
,BIT
,SINT16
,BIT
,SINT16
,SINT16
,508
,1749
,159
,1749
,159
,1056
,96
DA_N2L01D_T
DA_N2L01M
DA_N2L01M_T
DA_N2_PANEL
DA_N2_PANEL_T
DA_N2_BELL_T
,4
1
Sint16 is recommended over Float, as Float is memory expensive format
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 9 of 22
4.3 Client Side Connection Descriptions
Section Title
Connections
Column
Function
Title
Legal Values
P1-P82
Specify which port the device is connected to the
Port
FieldServer
Protocol
Specify protocol used
nfs2-nca; nca2; nfs2-3030
CRT Port
4800; 9600; 19200; 38400; 57600; (Vendor
limitation)
Baud*
Specify baud rate
Printer Port
9600 (Vendor limitation)
None (Vendor limitation)
8 (Vendor limitation)
1 (Vendor limitation)
Parity*
Data_Bits*
Stop_Bits*
Specify parity
Specify data bits
Specify stop bits
Example
// Client Side Connections
Connections
Port ,Protocol ,Baud ,Stop_Bits ,Parity
P8
,nfs2-nca ,9600 ,1
,None
4.4 Client Side Node Descriptors
Section Title
Nodes
Column Title
Node_Name
Function
Provide name for Node
Legal Values
Up to 32 alphanumeric characters
Station address of any physical Node on 1-240. Set unique Id for standalone Notifer-
Node_ID
Protocol
Port
network
3030 Panel
Specify protocol used
Specify which port the device is connected
to the FieldServer
nfs2-nca or nca2 ; nfs2-3030
P1-P8
Example
// Client Side Nodes
Nodes
Node_Name ,Node_ID ,Protocol ,Port
Panel_1
,2
,nfs2-nca ,P8
2 Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available
on specific hardware.
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 10 of 22
4.5 Client Side Map Descriptors
4.5.1 FieldServer Related Map Descriptor Parameters
Column Title
Function
Legal Values
Up to 32 alphanumeric characters
Name of Data Array where data is to be One of the Data Array names from “Data
Map_Descriptor_Name Name of this Map Descriptor
Data_Array_Name
stored in the FieldServer
Array” section above
Any integer value
0 - one less than Data Array length
Passive
Data_Array_Offset
Function
Starting location in Data Array
Function of Map Descriptor
4.5.2 Driver Related Map Descriptor Parameters
Column Title
Node_Name
Function
Legal Values
One of the Node names specified in
“Client Node Descriptor” above
Detector
Name of Node to fetch data from
Module
Detector_Trouble
Module_Trouble
Panel
Data_Type
Specify memory area type
Panel_Trouble
Bell_Trouble
Node_Trouble
As per Data_type
Detector
Module
1-1749
Detector_Trouble
Module_Trouble
1-159 for point troubles
Panel
Address
Starting address of block
1-1056 for Panel circuits
Panel_Trouble
1-96 for Panel troubles
Bell_Trouble
1-4 for Bell circuits
Node_Trouble
1-509 for Node troubles
Same as address value
Length
Length of Map Descriptor
Specify whether driver should clear Node(s)
Clear_on_Reset*
memory area upon receipt of “SYSTEM RESET” No, Yes
message from Panel.
Specify whether driver should clear Node(s)
Clear_on_Normal* memory area upon receipt of “SYSTEM NORMAL” Yes ,No
message from Panel.
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 11 of 22
4.5.3 Map Descriptor Example: Standard example
This shows the standard Map Descriptor setup for one Node with 1 loop and all 159 modules and 159 detectors installed. This Node also has all boards, panel
and bell circuits
//
// Client Side Map Descriptor
// Define Map Descriptors to capture just required data
//
// Node 2
//
Map_Descriptors
Map_Descriptor_Name
//
,Data_Array_Name ,Data_Array_Offset ,Function ,Node_Name ,Loop ,Data_Type
,Address ,Length
// Capture Node Events
SMD_N2_Troubles
SMD_N2_PANEL
SMD_N2_PANEL_T
SMD_N2_BELL_T
,DA_SYS_N2
,0
,0
,0
,0
,Passive
,Passive
,Passive
,Passive
,NODE2
,NODE2
,NODE2
,NODE2
,-
,-
,-
,-
,Node_Trouble
,Panel
,Panel_Trouble
,Bell_Trouble
,1
,1
,1
,1
,508
,1056
,96
,DA_N2_PANEL
,DA_N2_PANEL_T
,DA_N2_BELL_T
,4
// Capture Loop 1 events
SMD_N2L01D
SMD_N2L01D_T
SMD_N2L01M
,DA_N2L01D
,0
,0
,0
,0
,Passive
,Passive
,Passive
,Passive
,NODE2
,NODE2
,NODE2
,NODE2
,1
,1
,1
,1
,Detector
,Detector_Trouble ,1
,Module
,Module_Trouble
,1
,1749
,159
,1749
,159
,DA_N2L01D_T
,DA_N2L01M
,DA_N2L01M_T
,1
,1
SMD_N2L01M_T
All Map Descriptors are
Passive; waiting for a message
from the Notifier panel.
Identify the Loop id for
which this Map Descriptor
will store data
Specify Data
Type
Specify range,
starting address
and length
Select the array
for data storage
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 13 of 22
Appendix A. Advanced Topics
Appendix A.1. Notifier NCA2/NFS2-3030 Message Types Recognized
Event Keyword
FIRE ALARM
Clearing Event
CLEARED
ALARM
Notes
FIRE
states: {1,0}
SECURITY
ALARM (LIFE)
CLEARED SECURITY states: {1,0}
ALARM (LIFE)
LIFE
CRITICAL CLEARED
LIFE states: {1,0}
ALARM
CRITICAL ALARM
MEDICAL
EMERGENCY
SECURITY
ALARM
CLEARED MEDICAL states: {1,0}
EMERGENCY
CLEARED SECURITY states: {1,0}
ALARM
CRITICAL
PROCESS
states: {1,0}
CRITICAL PROCESS
CLEARED
SUPERVISORY
CLEARED
TROUBLE/ FAULT
CLEARED
DISABLED
states: {1,0}
SUPERVISORY
TROUBLE/
FAULT
States: [counter}
states: {1,0}
DISABLED
CLEARED
states: {1,0}
PREALARM
PREALARM
CLEARED ACTIVE
OFF
ACTIVE
ON/ OFF
states: {1,0}
states: {1,0}
Resets all addresses in all memory areas but only if data is previously set
by driver and is not yet cleared by “Cleared” message and is configured
to Clear_on_Normal. By default Clear_on_Normal is “yes”.
Resets all addresses in all memory areas for a given Node but only if
data is previously set by driver and is not yet cleared by “Cleared”
message and is configured to Clear_on_Reset. By default
Clear_on_Reset is ‘no’.
SYSTEM
NORMAL
SYSTEM RESET
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 14 of 22
Appendix A.2. System Trouble Messages
The following table lists the system troubles theoretically recognized by this driver – only a selection have been
tested.
System Trouble
Address
1
2
3
4
5
6
7
8
System Trouble
STYLE 4 SHORT A L6
STYLE 4 SHORT B L6
STYLE 4 SHORT A L7
STYLE 4 SHORT B L7
STYLE 4 SHORT A L8
STYLE 4 SHORT B L8
STYLE 4 SHORT A L9
STYLE 4 SHORT B L9
STYLE 4 SHORT A L10
STYLE 4 SHORT B L10
GENERAL PS FAULT
INSTALLATION ERROR OR CPU/AVPS-24 FAULT
INSTALLATION ERROR OR CPU/AVPS-24 FAULT
INSTALLATION ERROR OR CPU/AVPS-24 FAULT
EARTH FAULT DETECTED IN WIRING OR SYSTE
EARTH FAULT DETECTED IN WIRING OR SYSTE
EARTH FAULT DETECTED IN WIRING OR SYSTE
COMM FAULT LOOP INTERFACE BOARD 1
COMM FAULT LOOP INTERFACE BOARD 2
COMM FAULT LOOP INTERFACE BOARD 3
COMM FAULT LOOP INTERFACE BOARD 4
COMM FAULT LOOP INTERFACE BOARD 5
COMM FAULT LOOP INTERFACE BOARD 6
COMM FAULT LOOP INTERFACE BOARD 7
COMM FAULT LOOP INTERFACE BOARD 8
COMM FAULT LOOP INTERFACE BOARD 9
COMM FAULT LOOP INTERFACE BOARD 10
CATASTROPHIC ISIB COMMUNICATIONS FAULT
MEMORY PATTERN FAULT. SERVICE REQUIRED
CATASTROPHIC CPU BOARD COMM FAULT
Address
255
256
257
258
259
260
261
262
263
264
265
266
267
268
269
270
271
272
273
274
275
276
277
278
279
280
281
282
283
284
GROUND FAULT LOOP 1
GROUND FAULT LOOP 2
GROUND FAULT LOOP 3
GROUND FAULT LOOP 4
GROUND FAULT LOOP 5
GROUND FAULT LOOP 6
GROUND FAULT LOOP 7
GROUND FAULT LOOP 8
GROUND FAULT LOOP 9
GROUND FAULT LOOP 10
GROUND FAULT PORT A
GROUND FAULT PORT B
GROUND FAULT
STYLE 6 NEG LOOP 1
STYLE 6 NEG LOOP 2
STYLE 6 NEG LOOP 3
STYLE 6 NEG LOOP 4
STYLE 6 NEG LOOP 5
STYLE 6 NEG LOOP 6
STYLE 6 NEG LOOP 7
STYLE 6 NEG LOOP 8
STYLE 6 NEG LOOP 9
STYLE 6 NEG LOOP 10
STYLE 6 POS LOOP 1
STYLE 6 POS LOOP 2
STYLE 6 POS LOOP 3
STYLE 6 POS LOOP 4
STYLE 6 POS LOOP 5
STYLE 6 POS LOOP 6
STYLE 6 POS LOOP 7
STYLE 6 POS LOOP 8
STYLE 6 POS LOOP 9
STYLE 6 POS LOOP 10
STYLE 6 SHORT L1
STYLE 6 SHORT L2
STYLE 6 SHORT L3
STYLE 6 SHORT L4
STYLE 6 SHORT L5
STYLE 6 SHORT L6
STYLE 6 SHORT L7
STYLE 6 SHORT L8
STYLE 6 SHORT L9
STYLE 6 SHORT L10
STYLE 6 RING 1
STYLE 6 ON LOOP 1
STYLE 6 ON LOOP 2
STYLE 6 ON LOOP 3
STYLE 6
ANNUN 1 TROUBLE
ANNUN 2 TROUBLE
ANNUN 3 TROUBLE
ANNUN 4 TROUBLE
ANNUN 5 TROUBLE
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
UPLOAD/DOWNLOAD COMMUNICATIONS FAULT 285
STYLE \6\" WIRING OR LOOP #1 ABNORMAL"
STYLE \4\" WIRING OR LOOP #1 ABNORMAL"
STYLE \6\" WIRING OR LOOP #2 ABNORMAL"
STYLE \4\" WIRING OR LOOP #2 ABNORMAL"
STYLE \6\" WIRING OR LOOP #3 ABNORMAL"
STYLE \4\" WIRING OR LOOP #3 ABNORMAL"
STYLE \6\" WIRING OR LOOP #4 ABNORMAL"
STYLE \4\" WIRING OR LOOP #4 ABNORMAL"
STYLE \6\" WIRING OR LOOP #5 ABNORMAL"
STYLE \4\" WIRING OR LOOP #5 ABNORMAL"
STYLE \6\" WIRING OR LOOP #6 ABNORMAL"
STYLE \4\" WIRING OR LOOP #6 ABNORMAL"
STYLE \6\" WIRING OR LOOP #7 ABNORMAL"
STYLE \4\" WIRING OR LOOP #7 ABNORMAL"
STYLE \6\" WIRING OR LOOP #8 ABNORMAL"
STYLE \4\" WIRING OR LOOP #8 ABNORMAL"
STYLE \6\" WIRING OR LOOP #9 ABNORMAL"
STYLE \4\" WIRING OR LOOP #9 ABNORMAL"
STYLE \6\" WIRING OR LOOP #10 ABNORMAL"
STYLE \4\" WIRING OR LOOP #10 ABNORMAL"
UNPROGRAMMED DEVICE ON LOOP 1
286
287
288
289
290
291
292
293
294
295
296
297
298
299
300
301
302
303
304
305
306
307
UNPROGRAMMED DEVICE ON LOOP 2
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 15 of 22
System Trouble
ANNUN 6 TROUBLE
ANNUN 7 TROUBLE
ANNUN 8 TROUBLE
ANNUN 9 TROUBLE
ANNUN 10 TROUBLE
ANNUN 11 TROUBLE
ANNUN 12 TROUBLE
ANNUN 13 TROUBLE
ANNUN 14 TROUBLE
ANNUN 15 TROUBLE
ANNUN 16 TROUBLE
ANNUN 17 TROUBLE
ANNUN 18 TROUBLE
ANNUN 19 TROUBLE
ANNUN 20 TROUBLE
ANNUN 21 TROUBLE
ANNUN 22 TROUBLE
ANNUN 23 TROUBLE
ANNUN 24 TROUBLE
ANNUN 25 TROUBLE
ANNUN 26 TROUBLE
ANNUN 27 TROUBLE
ANNUN 28 TROUBLE
ANNUN 29 TROUBLE
ANNUN 30 TROUBLE
ANNUN 31 TROUBLE
ANNUN 32 TROUBLE
REMOTE DISPLAY 1 TROUBLE
REMOTE DISPLAY 2 TROUBLE
REMOTE DISPLAY 3 TROUBLE
REMOTE DISPLAY 4 TROUBLE
REMOTE DISPLAY 5 TROUBLE
REMOTE DISPLAY 6 TROUBLE
REMOTE DISPLAY 7 TROUBLE
REMOTE DISPLAY 8 TROUBLE
REMOTE DISPLAY 9 TROUBLE
REMOTE DISPLAY 10 TROUBLE
REMOTE DISPLAY 11 TROUBLE
REMOTE DISPLAY 12 TROUBLE
REMOTE DISPLAY 13 TROUBLE
REMOTE DISPLAY 14 TROUBLE
REMOTE DISPLAY 15 TROUBLE
REMOTE DISPLAY 16 TROUBLE
REMOTE DISPLAY 17 TROUBLE
REMOTE DISPLAY 18 TROUBLE
REMOTE DISPLAY 19 TROUBLE
REMOTE DISPLAY 20 TROUBLE
REMOTE DISPLAY 21 TROUBLE
REMOTE DISPLAY 22 TROUBLE
REMOTE DISPLAY 23 TROUBLE
REMOTE DISPLAY 24 TROUBLE
REMOTE DISPLAY 25 TROUBLE
REMOTE DISPLAY 26 TROUBLE
REMOTE DISPLAY 27 TROUBLE
REMOTE DISPLAY 28 TROUBLE
REMOTE DISPLAY 29 TROUBLE
REMOTE DISPLAY 30 TROUBLE
REMOTE DISPLAY 31 TROUBLE
REMOTE DISPLAY 32 TROUBLE
Address
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
91
92
93
94
95
96
97
98
99
100
101
102
103
104
105
106
107
108
109
110
111
112
System Trouble
Address
308
309
310
311
312
313
314
315
316
317
318
319
320
321
322
323
324
325
326
327
328
329
330
331
332
333
334
335
336
337
338
339
340
341
342
343
344
345
346
347
348
349
350
351
352
353
354
355
356
357
358
359
360
361
362
363
364
365
366
UNPROGRAMMED DEVICE ON LOOP 3
UNPROGRAMMED DEVICE ON LOOP 4
UNPROGRAMMED DEVICE ON LOOP 5
UNPROGRAMMED DEVICE ON LOOP 6
UNPROGRAMMED DEVICE ON LOOP 7
UNPROGRAMMED DEVICE ON LOOP 8
UNPROGRAMMED DEVICE ON LOOP 9
UNPROGRAMMED DEVICE ON LOOP 10
IR ENABLED ON LOOP 1
IR ENABLED ON LOOP 2
IR ENABLED ON LOOP 3
IR ENABLED ON LOOP 4
IR ENABLED ON LOOP 5
IR ENABLED ON LOOP 6
IR ENABLED ON LOOP 7
IR ENABLED ON LOOP 8
IR ENABLED ON LOOP 9
IR ENABLED ON LOOP 10
TX/RX ERROR ABOVE LIMIT ON LOOP 1
TX/RX ERROR ABOVE LIMIT ON LOOP 2
TX/RX ERROR ABOVE LIMIT ON LOOP 3
TX/RX ERROR ABOVE LIMIT ON LOOP 4
TX/RX ERROR ABOVE LIMIT ON LOOP 5
TX/RX ERROR ABOVE LIMIT ON LOOP 6
TX/RX ERROR ABOVE LIMIT ON LOOP 7
TX/RX ERROR ABOVE LIMIT ON LOOP 8
TX/RX ERROR ABOVE LIMIT ON LOOP 9
TX/RX ERROR ABOVE LIMIT ON LOOP 10
TOO MANY DEVICES ON LOOP 1
TOO MANY DEVICES ON LOOP 2
TOO MANY DEVICES ON LOOP 3
TOO MANY DEVICES ON LOOP 4
TOO MANY DEVICES ON LOOP 5
TOO MANY DEVICES ON LOOP 6
TOO MANY DEVICES ON LOOP 7
TOO MANY DEVICES ON LOOP 8
TOO MANY DEVICES ON LOOP 9
TOO MANY DEVICES ON LOOP 10
MISMATCHED LOOP TYPE ON LOOP 1
MISMATCHED LOOP TYPE ON LOOP 2
MISMATCHED LOOP TYPE ON LOOP 3
MISMATCHED LOOP TYPE ON LOOP 4
MISMATCHED LOOP TYPE ON LOOP 5
MISMATCHED LOOP TYPE ON LOOP 6
MISMATCHED LOOP TYPE ON LOOP 7
MISMATCHED LOOP TYPE ON LOOP 8
MISMATCHED LOOP TYPE ON LOOP 9
MISMATCHED LOOP TYPE ON LOOP 10
MAPPING IN PROGRESS LOOP 1
MAPPING IN PROGRESS LOOP 2
MAPPING IN PROGRESS LOOP 3
MAPPING IN PROGRESS LOOP 4
MAPPING IN PROGRESS LOOP 5
MAPPING IN PROGRESS LOOP 6
MAPPING IN PROGRESS LOOP 7
MAPPING IN PROGRESS LOOP 8
MAPPING IN PROGRESS LOOP 9
MAPPING IN PROGRESS LOOP 10
LIB #1 SCB RECEIVE ERROR
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 16 of 22
System Trouble
Address
System Trouble
LIB #2 SCB RECEIVE ERROR
LIB #3 SCB RECEIVE ERROR
LIB #4 SCB RECEIVE ERROR
LIB #5 SCB RECEIVE ERROR
LIB #6 SCB RECEIVE ERROR
LIB #7 SCB RECEIVE ERROR
LIB #8 SCB RECEIVE ERROR
Address
367
368
369
370
371
372
373
374
375
376
377
378
379
380
381
382
383
384
385
386
387
388
389
390
391
392
393
394
395
396
397
398
399
400
401
402
403
404
405
406
407
408
409
410
411
ANALOG OUTPUT 1 TROUBLE
ANALOG OUTPUT 2 TROUBLE
ANALOG OUTPUT 3 TROUBLE
ANALOG OUTPUT 4 TROUBLE
AUXILIARY TROUBLE
UDACT TROUBLE
AVPS. TROUBLE
MASTER BOX TROUBLE
AUXIN TROUBLE
DIGIN TROUBLE
FFT TROUBLE
REMOTE MIC TROUBLE
LOCAL MIC TROUBLE
LOCAL PHONE TROUBLE
POWER SUPPLY TROUBLE
FIM TROUBLE - FIELD INTERFACE MODULE
LIM TROUBLE - LOOP INTERFACE MODULE
NIM TROUBLE - NETWORK INTERFACE MODULE 130
SYSTEM TROUBLE DEFAULT MESSAGE
TROUBLE
ANNUN 1 NO ANSWER
ANNUN 2 NO ANSWER
113
114
115
116
117
118
119
120
121
122
123
124
125
126
127
128
129
LIB #9 SCB RECEIVE ERROR
LIB #10 SCB RECEIVE ERROR
LIB #1 SCB ACKNOWLEDGE ERROR
LIB #2 SCB ACKNOWLEDGE ERROR
LIB #4 SCB ACKNOWLEDGE ERROR
LIB #5 SCB ACKNOWLEDGE ERROR
LIB #6 SCB ACKNOWLEDGE ERROR
LIB #7 ACKNOWLEDGE ERROR
LIB #8 SCB ACKNOWLEDGE ERROR
LIB #9 SCB ACKNOWLEDGE ERROR
LIB #10 SCB ACKNOWLEDGE ERROR
LIB #1 NIB COMMUNICATION ERROR
LIB #2 NIB COMMUNICATION ERROR
LIB #3 NIB COMMUNICATION ERROR
LIB #4 NIB COMMUNICATION ERROR
LIB #5 NIB COMMUNICATION ERROR
LIB #6 NIB COMMUNICATION ERROR
LIB #7 NIB COMMUNICATION ERROR
LIB #8 NIB COMMUNICATION ERROR
LIB #9 COMMUNICATION ERROR
LIB #10 NIB COMMUNICATION ERROR
LIB #1 NIB M/S PROGRAMMING ERROR
LIB #2 NIB M/S PROGRAMMING ERROR
LIB #3 NIB M/S PROGRAMMING ERROR
LIB #4 NIB M/S PROGRAMMING ERROR
LIB #5 NIB M/S PROGRAMMING ERROR
LIB #6 NIB M/S PROGRAMMING ERROR
LIB #7 NIB M/S PROGRAMMING ERROR
LIB #8 NIB M/S PROGRAMMING ERROR
LIB #9 NIB M/S PROGRAMMING ERROR
LIB #10 NIB M/S PROGRAMMING ERROR
INTERNAL RAM ERROR
131
132
133
134
135
136
137
138
139
140
141
142
143
144
145
146
147
148
149
150
151
152
153
154
155
156
157
158
159
160
161
162
163
164
165
166
167
168
169
170
171
ANNUN 3 NO ANSWER
ANNUN 4 NO ANSWER
ANNUN 5 NO ANSWER
ANNUN 6 NO ANSWER
ANNUN 7 NO ANSWER
ANNUN 8 NO ANSWER
ANNUN 9 NO ANSWER
ANNUN 10 NO ANSWER
ANNUN 11 NO ANSWER
ANNUN 12 NO ANSWER
ANNUN 13 NO ANSWER
ANNUN 14 NO ANSWER
ANNUN 15 NO ANSWER
ANNUN 16 NO ANSWER
ANNUN 17 NO ANSWER
ANNUN 18 NO ANSWER
ANNUN 19 NO ANSWER
ANNUN 20 NO ANSWER
ANNUN 21 NO ANSWER
ANNUN 22 NO ANSWER
ANNUN 23 NO ANSWER
ANNUN 24 NO ANSWER
ANNUN 25 NO ANSWER
ANNUN 26 NO ANSWER
ANNUN 27 NO ANSWER
ANNUN 28 NO ANSWER
ANNUN 29 NO ANSWER
ANNUN 30 NO ANSWER
ANNUN 31 NO ANSWER
ANNUN 32 NO ANSWER
REMOTE DISPLAY 1 NO ANSWER
REMOTE DISPLAY 2 NO ANSWER
REMOTE DISPLAY 3 NO ANSWER
REMOTE DISPLAY 4 NO ANSWER
REMOTE DISPLAY 5 NO ANSWER
REMOTE DISPLAY 6 NO ANSWER
REMOTE DISPLAY 7 NO ANSWER
EXTERNAL RAM ERROR
CPU EXTERNAL RAM TEST ERROR
CATASTROPHIC CUP NONVOLATILE RAM
DIB EXTERNAL RAM TEST ERROR
CATASTROPHIC DIA NONVOLATILE RAM
EPROM ERROR
PRINTER SUPERVISORY PATH IS INTERRUPTED
PRINTER SUPERVISORY
PRINTER COVER OPEN
412
413
414
415
416
417
418
419
420
421
422
423
424
425
PRINTER PAPER OUT
PRINTER BUFFER FULL OR OUT OF PAPER
AUX PRINTER BUFFER FULL OR OUT OF PAPER
PRINTER OFF LINE
PRINT QUEUE FULL
FACP PRINT BUFFER FULL
CORRUPT LOGIC EQUAT
PROGRAM CORRUPTED
DATABASE CORRUPTED
AUDIO LIBRARY CORRUPTED
LCD80 SUPERVISORY
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 17 of 22
System Trouble
Address
System Trouble
TERM SUPERVISORY
CRT SUPERVISORY
TERMINAL SUPERVISORY PATH IS INTERRUPTE
NVRAM BATTERY TROUBLE
NCM PIEZO BATTERY FAILURE
BATTERY(S) NOT CONNECTED OR DEFECTIVE
BATTERY CHARGER DETACHED
BATTERY
TM4 DISABLED
UP/DOWN LOAD IN PROGRESS _ ACS DISABLED
NO DEV INST ON L1
ADV WALK TEST
PROG MODE ACTIVATED
LOADING..NO SERVICE
BASIC WALK TEST
NFPA 24HR REMINDER
OPTION MODULE
DRILL ACTIVATED
MAN EVAC RECEIVED
MANUAL MODE ENTERED
POWER SUPPLY CABLE NOT CONNECTED
NETWORK INCOMPATIBLE
Address
426
427
REMOTE DISPLAY 8 NO ANSWER
REMOTE DISPLAY 9 NO ANSWER
REMOTE DISPLAY 10 NO ANSWER
REMOTE DISPLAY 11 NO ANSWER
REMOTE DISPLAY 12 NO ANSWER
REMOTE DISPLAY 13 NO ANSWER
REMOTE DISPLAY 14 NO ANSWER
REMOTE DISPLAY 15 NO ANSWER
REMOTE DISPLAY 16 NO ANSWER
REMOTE DISPLAY 17 NO ANSWER
REMOTE DISPLAY 18 NO ANSWER
REMOTE DISPLAY 19 NO ANSWER
REMOTE DISPLAY 20 NO ANSWER
REMOTE DISPLAY 21 NO ANSWER
REMOTE DISPLAY 22 NO ANSWER
REMOTE DISPLAY 23 NO ANSWER
REMOTE DISPLAY 24 NO ANSWER
REMOTE DISPLAY 25 NO ANSWER
REMOTE DISPLAY 26 NO ANSWER
REMOTE DISPLAY 27 NO ANSWER
REMOTE DISPLAY 28 NO ANSWER
REMOTE DISPLAY 29 NO ANSWER
REMOTE DISPLAY 30 NO ANSWER
REMOTE DISPLAY 31 NO ANSWER
REMOTE DISPLAY 32 NO ANSWER
UDACT NO ANSWER
172
173
174
175
176
177
178
179
180
181
182
183
184
185
186
187
188
189
190
191
192
193
194
195
196
197
198
199
200
201
202
203
204
205
206
207
208
209
210
211
212
213
214
215
216
217
218
219
220
221
222
223
224
225
226
227
228
229
230
428
429
430
431
432
433
434
435
436
437
438
439
440
441
442
443
444
445
446
447
448
449
450
451
452
453
454
455
456
457
458
459
460
461
462
463
464
465
466
467
468
469
470
471
472
473
474
475
476
477
478
479
480
481
482
483
484
SYSTEM INITIALIZATION
LINK PROTECTOR PRIMARY STATUS
LINK PROTECTOR SECONDARY STATUS
LINK PROTECTOR PRIMARY NOT PRESENT
EVENT BUFFER 80% FULL
EBI STATUS
SOFTWARE MISMATCH
NO POWER SUPPLY INST
TEST PROGRAM UPDATE
HISTORY 80% FULL
FLASH IMAGE ERROR
AMPLIFIER LIMIT
AMPLIFIER SUPERVISION
DAA ADDRESS CONFLICT
DEVICE SERVICING REQUIRED
DATABASE INCOMPATIBLE
AUDIO LIBRARY INCOMPATIBLE
DAA DOWNLOAD IN PROGRESS
PHONE CHANNEL LIMIT EXCEEDED
CPU EXECUTIVE ROUTINE RE-ENTERED
CPU RECEIVE QUE OVERFLOW
CPU DATA MESSAGE RECEIVED ERROR
CPU LEVEL QUE FULL
CPU CODE MEMORY CHECKSUM ERROR
CPU MESSAGE TRANSMITTED ERROR
AVPS-24 PROBLEM
DATABASE INCOMPLETE PLEASE REDOWNLOAD
MPS-24 MONITOR CABLE DISCONNECTED
TYPE ID CHANGED. SERVICE REQUIRED
TYPE ID CHANGED. SERVICE REQUIRED
PROG. CHANGE DET. SERVICE REQUIRED
LIVE TEST - SIGNAL P
DIB EXECUTIVE ROUTINE RE-ENTERED
DIB RECEIVE QUE OVERFLOW
DIB DATA MESSAGE RECEIVED ERROR
DIB CODE MEMORY CHECKSUM ERROR
INCOMPATIBLE SOFTWARE OR INVALID CBE
MASTER BOX NO ANSWER
DAA NO ANSWER
NO ANSWER
NETWORK FAILURE
WORKSTATION FAN FAILURE
UPS FAILURE
NCM COMM FAILURE
NODE COMMUNICATIONS FAILURE
POWER SUPPLY COMM FAILURE
LOOP 1-2 COMM FAILURE
LOOP 3-4 COMM FAILURE
LOOP 5-6 COMM FAILURE
LOOP 7-8 COMM FAILURE
LOOP 9-10 COMM FAILURE
DAP PORT A FAILURE
DAP PORT B FAILURE
FIM COMM FAILURE
LIM COMM FAILURE
NIM COMM FAILURE
CATASTROPHIC LCD FAILURE ON DIA
CATASTROPHIC DUART FAILURE ON DIA
ISIB SCB RECEIVE FAILURE
COMMUNICATION LINK FAILURE IN PORT A
COMMUNICATION LINK FAILURE IN PORT B
LAN COMMUNICATIONS FAILURE
FAILURE
NETWORK FAIL PORT A
NETWORK FAIL PORT B
CHARGER FAIL
SELF TEST FAILED
WORKSTATION COMM FAIL
LOOP CONTINUITY TEST FAIL LOOP 1
LOOP CONTINUITY TEST FAIL LOOP 2
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 18 of 22
System Trouble
Address
System Trouble
WALK TEST - FIRE PROTECTION IS LIMITED
REMOTE PROG MODE ACCESSED
Address
485
486
LOOP CONTINUITY TEST FAIL LOOP 3
LOOP CONTINUITY TEST FAIL LOOP 4
LOOP CONTINUITY TEST FAIL LOOP 5
LOOP CONTINUITY TEST FAIL LOOP 6
LOOP CONTINUITY TEST FAIL LOOP 7
LOOP CONTINUITY TEST FAIL LOOP 8
LOOP CONTINUITY TEST FAIL LOOP 9
LOOP CONTINUITY TEST FAIL LOOP 10
AMP FAIL
231
232
233
234
235
236
237
238
239
240
241
242
DIA PROG. CHANGE DET. SERVICE REQUIRED
ISIB DATA MESSAGE RECEIVED ERROR
ISIB EXECUTIVE ROUTINE RE-ENTERED
DIB TO SIB CABLE BAD OR MISSING
UPLOAD/DOWNLOAD MESSAGE RECEIVED
GLOBAL DATABASE MISMATCH
SIB PROG. CHANGE DET. SERVICE REQUIRED
HS-NCM SNIFFER MODE ACTIVE
EXCEEDED CONNECTION LIMIT
NAM CCBE. PROG LOST
MEMORY LOSS
DVC COMM LOSS
A.C. POWER LOSS. BACK UP ACTIVATED
BUZZER OFF-LINE
PANEL DOOR OPEN
OFF NETWORK
INSTALL. ERROR
OR AUDIO/TELEPHON
EXPANDER MODULES
MANUAL CONTROL
CAT. COMM. FAULT
UNKNOWN
487
488
489
490
491
492
493
494
495
496
497
498
499
500
501
502
503
504
505
506
507
508
AC FAIL
SCB ASSEM. COM. VERIFIED FAILED
8255 PORT CHIP CONTROL WORD CHECK FAILE
NETWORK COMMUNICATION LINK FAIL PORT A 243
NETWORK COMMUNICATION LINK FAIL PORT B 244
STYLE 4 SHORT A L1
STYLE 4 SHORT B L1
STYLE 4 SHORT A L2
STYLE 4 SHORT B L2
STYLE 4 SHORT A L3
STYLE 4 SHORT B L3
STYLE 4 SHORT A L4
STYLE 4 SHORT B L4
STYLE 4 SHORT A L5
STYLE 4 SHORT B L5
245
246
247
248
249
250
251
252
253
254
Appendix A.3. Node Status
•
Data for any particular Node is valid while that Node is online and the system is synchronized. Integrity of
data for any Node will be lost if the Node goes offline or if synchronism between the FieldServer and the
NCA2 Panel is lost.
•
•
Node status offline/online (1/0) is stored in the 502nd address. It is important to read the Node status
before reading any information about the Node.
Node status data integrity itself depends upon system synchronization.
Appendix A.4. FieldServer Synchronization
There is currently no method of auto-synchronizing the FieldServer's Data Arrays with the Notifier NCA2/NFS2-
3030 panel because there is no method for polling the panel through the printer or CRT port. Synchronization of
the two devices can be achieved manually pressing the “System Reset” button on the panel while the FieldServer is
connected and running. All current events will be re-sent to the FieldServer..
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 19 of 22
Appendix A.5. Driver Limitations and Exclusions
•
•
Zone information will not be recorded.
To synchronize the FieldServer with the panel, connect the running FieldServer and press the “System
Reset” button on the panel. All current events will be re-sent to the FieldServer.
•
•
•
The port must be enabled on the unit and set to 80 columns with NO supervision
All data related to non-event driven reports will not be recorded by the FieldServer
This driver was written as a subset of NFS2-3030/NCA-2 EIA-232 Protocol & Data Formats 53219 Rev A
1/3/2008. Any changes or additions by Notifier will not be reflected in this driver unless specifically
revised.
•
•
•
This driver will not record information about zone status that is incorporated with point status messages.
There can only be one panel connected to any given FieldServer port.
This driver records data as presented to the printer/CRT port by the Notifier panel, and can only be as
accurate as this data.
•
•
The driver cannot send messages to the Notifier panel.
Driver will clear any data on “System Normal” only if this data is previously set by driver and is not yet
cleared by “Cleared” message and is configured to Clear_on_Normal. By default Clear_on_Normal is
“yes”.
•
Driver will clear any Node data on “System RESET” only if this data is previously set by driver and is not yet
cleared by “Cleared” message and is configured to Clear_on_Reset. By default Clear_on_Reset is “no”.
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 20 of 22
Appendix B. Troubleshooting tips
Appendix B.1. Connection Tips & Hints
•
Communication errors will be experienced if the port is disabled at the panel. Please check the Notifier
Manuals on how to enable the panel port connected to the FieldServer and ensure that it is set to 80
columns NO supervision.
•
If connecting the Panel to one of the FieldServer RS-232 ports causes the FieldServer to reboot, then an
Optical Isolator is required to balance ground potential problems.
Appendix B.2. Networking Tips
•
By default FieldServer does not take any action on receiving a “SYSTEM RESET”. Normally when a Node
initiates “SYSTEM RESET” by pressing the “RESET” button on the Panel, the panel sends an individual
“CLEAR” message for every point, it clears in its memory area. The FieldServer therefore waits for the
“CLEAR” message to clear a specific bit in its memory for a particular Node or for the “SYSTEM NORMAL”
message to clear all bits in its memory for every Node. Use Clear_on_Reset parameter if required.
•
•
It may be advisable to configure the Notifier panel to suppress less important “Supervisory” or “Trouble”
messages which could prevent the generation of “SYSTEM NORMAL” messages. Consult Notifier for this
configuration or recommendation.
Ensure that every Node is working with a printer or HyperTerminal, before calling FieldServer for Support.
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 21 of 22
Appendix C. Error Messages
Most error messages are associated with errors in parsing an incoming message from the Notifier panel. The most
likely cause is a mismatch in expected message format. The driver will flag one of the following error messages
and continue. In most cases the message currently being processed by the driver will also be printed so that any
problems can be easily diagnosed.
Two screens ‘System Errors’ and ‘Driver Messages’ exist for displaying errors.
The System Error Screen displays the error number and the Driver messages screen displays the error number,
description and the message received from the NCA/NCA2 Panel.
In debug mode the System Error screen will also include Driver messages.
The following Error Messages appear upon the ‘System Errors’ Screen
•
•
%d means numeric number
%s means string
Messages number 1, 3, 4 and 5 will be displayed just once if generated after rebooting or power cycling the
FieldServer.
Error
Description
Action
#1 FYI. Incoming data is
being abandoned on The FieldServer got
a
recognized
Port<%d> Node<%u> message on this particular port, Node, To capture this data, add a new Map
Loop<%d>
Data_Type<%s>
Address<%d>
loop, Address_Type and Address but Descriptor with the required parameters.
did not find a defined Map Descriptor.
This driver keeps track of all non-zero
memory locations per Map Descriptor. If the error occurs during installation or
When the track queue is full, the oldest testing, it can be ignored. If the error
offset is overwritten with the latest occurs during field operation, configure the
one. This could be a problem on Map Descriptor with required address
System_Reset and System_Normal ranges only and keep the Map Descriptor
where memory locations get cleared as length smaller than the queue length.
per this queue.
#2 Err. Reset/Normal
queue<%d> full on
MD<%s>
The
FieldServer
received
an If the error occurs continuously, check that
#3 FYI. Event<%s> not
Supported.
unrecognized event or corrupted connection parameters match with panel
message.
port settings.
The FieldServer received
Trouble event not listed under need this new trouble status, contact
Appendix A.2 or a corrupted message.
The FieldServer received a message
a
Node If this error occurs continuously and you
#4 Err. Unknown Node
Trouble <%s>
FieldServer.
that
a
Node either connected or
#5 Err. Unknown OFF
NETWORK Node <%s>
disconnected from the network, but no Call Tech support.
Node number was received - it is likely
that the message was corrupted
Download from Www.Somanuals.com. All Manuals Search And Download.
FS-8700-130 Notifier NCA2/NFS-3030 Manual
Page 22 of 22
Error
Description
Action
A
message was received from an
#6 Err. Unsupported
unsupported device or the address of
the device is not in the correct
format/location.
Point
Address
Call Tech support.
Format<%s>
This occurs due to poor synchronization
between the FieldServer and the Notifier
panel or because a problem existed before
decrement below zero trouble counting number to a number “System Normal” message. Check the
offset<%d> DA<%s>
less than 0.
configuration file to identify the address
and memory area type mapped to this
offset and the Data Array which is causing
the error.
3 All Data Arrays on the FieldServer are initialized to zero on rebooting or starting up. A zero value in the Data Array assumes no problems with
the devices, but if a problem existed before the startup and the device comes out of problem, the FieldServer will attempt to decrease the
number of problems by 1 and this generates the error. Data from the FieldServer should not be considered reliable until the “System Normal”
message has been returned.
Download from Www.Somanuals.com. All Manuals Search And Download.
|