Eaton Electrical Network Card 34003991EN EB User Manual

www.eaton.com  
Network  
Management Card  
User manual  
Network Management Card – User Manual  
34003991EN/EB  
Page 1/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.1  
4.3.2  
4.4  
Email Notification  
E-mail Message Settings  
CONFIGURATION  
43  
45  
47  
48  
50  
52  
54  
55  
57  
59  
60  
60  
61  
62  
64  
4.4.1  
4.4.2  
4.4.3  
4.4.4  
4.4.5  
4.4.6  
4.4.7  
4.5  
Network settings  
System  
Notified Applications  
Central shutdown configuration  
Access control  
Date and time  
Firmware upload  
ENVIRONMENT SENSOR (OPTION)  
Characteristics  
4.5.1  
4.5.2  
4.5.3  
4.5.4  
Environment Status  
Environment Settings  
Log  
5
SERVER PROTECTION  
65  
5.1  
SET-UP OF THE SHUTDOWN PARAMETERS  
65  
65  
68  
68  
69  
69  
69  
70  
71  
71  
71  
5.1.1  
5.1.2  
5.1.3  
5.2  
Shutdown criteria managed by the Network Management Card  
Controlled outlets  
Protection of a server connected to a controlled outlet  
THE DIFFERENT SERVER AND UPS SHUTDOWN SEQUENCES  
Extended power outage, shutdown initiated by the Shutdown Timer (Shutdown after)  
Extended power outage, shutdown initiated by the "Low battery power" message  
Case of power restoration before the end of the "shutdown duration" counter  
SHUTDOWN MANAGEMENT WITH 2 NMC BOARDS  
5.2.1  
5.2.2  
5.2.3  
5.3  
5.3.1  
5.3.2  
Shutdown Duration  
Settings  
6
CONFIGURATION VIA RS232  
72  
6.1  
CHOICE 1: RESTART / RESET  
73  
73  
73  
74  
74  
75  
76  
6.2  
CHOICE 2: NETWORK CONFIGURATION  
6.2.1  
6.2.2  
6.2.3  
6.3  
Choice 1: Read Network settings  
Choice 2: Modify Network settings  
Choice 3: Set Ethernet speed  
CHOICE 3: LOST PASSWORD / SET LOGIN PASSWORD TO DEFAULT  
CHOICE 4: RETURN TO DEFAULT CONFIGURATION  
6.4  
7
INDUSTRIAL NETWORK MANAGEMENT CARD (INMC OPTION)  
77  
7.1  
PRESENTATION  
77  
77  
77  
78  
79  
79  
80  
86  
90  
7.1.1  
7.1.2  
7.1.3  
7.2  
Overview  
Functions  
Technical characteristics  
INSTALLATION  
7.2.1  
7.2.2  
7.2.3  
7.3  
RS232 link configuration and connection  
RS485 link configuration and connection  
Configuration of the JBUS/MODBUS communication parameters  
ADDITIONAL WEB PAGES  
Network Management Card – User Manual  
34003991EN/EB  
Page 3/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4  
JBUS TABLE  
91  
7.4.1  
7.4.2  
7.4.3  
7.4.4  
7.4.5  
7.4.6  
Data for Pulsar 700 / 1000 / 1500  
Data for Pulsar M 2200 / 3000  
Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT  
Data for Pulsar MX frame 15 / 20  
Sensor data  
91  
93  
95  
97  
102  
105  
Other data  
8
APPENDICES  
106  
8.1  
TABLES OF ALARMS AND EVENTS  
Table of alarms  
106  
106  
109  
111  
112  
112  
115  
8.1.1  
8.1.2  
8.1.3  
8.2  
Table of UPS events  
Table of system alarms  
SNMP OBJECTS  
8.2.1  
8.2.2  
MGE MIB  
Table des TRAPS : (1.3.6.1.4.1.705.1.11)  
9
GLOSSARY  
117  
Network Management Card – User Manual  
34003991EN/EB  
Page 4/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 EATON Network Solution  
1.1 General Presentation  
EATON Network Solution :  
- Provides information on events concerning the supply of power to the computers connected to your computer  
network,  
- Carries out automatic shutdown of computer systems,  
- Monitors and controls all the UPSs connected to the network.  
EATON Network Solution provides 3 main functions:  
- Supervision of the UPSs over the Network : Web browser, Enterprise Power Manager, or SNMP NMS.  
- Protection of the computers (multi-platform) with :  
Network Shutdown Module for MGE Office Protection Systems UPS.  
Netwatch for Powerware UPS.  
- Connexion of the UPS to the Network.  
Network Management Card – User Manual  
34003991EN/EB  
Page 5/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.1.1 Connecting the UPS to the Ethernet network  
This function can be performed through network Cards inserted in the UPS (Network Management Card).  
Also a software "agent" running on a nearby PC that is called the Network Management Proxy can be used.  
The Network Management Card or Proxy:  
- manages communication with the UPS (as well as local protection of the machine on which Proxy is installed)  
- periodically accesses the information concerning the UPS  
- makes this information available to the connected applications (Network Shutdown Modules, Netwatch, Web Browser,  
Network Management Systems, Enterprise Power Manager)  
- sends notifications on certain events.  
Operation may be in standard secure mode (the default mode) or in SSL secure mode (Secure Socket Layer SSL).  
1.1.2 Protection of the computers/servers  
This function is performed by :  
-
-
Network Shutdown Module for MGE Office Protection Systems UPS  
Netwatch for Powerware UPS  
installed on each of the servers to be protected.  
Note that Network Shutdown Module and Netwatch are available on several Operating Systems.  
Both protection applications:  
Continuously waits for information from the Network Management Card/Proxy connected to the UPS.  
Warns administrators and users if AC power fails and proceeds with graceful system shutdown before the end of  
battery backup power is reached.  
Network Management Card – User Manual  
34003991EN/EB  
Page 6/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.1.3 Supervision of the UPSs over the network  
Depending on your needs, you can either use:  
Your Internet browser to monitor each UPS, as Management Proxy and Management Card includes a Web server  
Your company’s standard Network Management System (HP-Openview, CA Unicenter, HP Insight Manager, IBM Tivoli  
Netview)  
To simplify integration of EATON UPSs, you can use one of the Network Management System Kits for MGE devices.  
These kits are available on the Management Pac 2 CD-ROM. (ref 66923)  
The supervisor "Enterprise Power Manager".  
1.1.4 Connection  
Before installing the Network Solution, the UPS must be set up as indicated in the steps below.  
Shut down the computers to be protected by the UPS.  
Connect the UPS to a wall outlet. (For UPSs above 3kVA, please refer to the UPS installation manual).  
Connect the power cord of each computer to an outlet on the UPS. (For UPSs above 3kVA, please refer to the UPS  
installation manual)  
Network Management Card – User Manual  
34003991EN/EB  
Page 7/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.1.4.1 How to connect UPS / agent / network:  
Insert the optional card in the UPS and connect the UPS to the computer network.  
Start the UPS, then the computers.  
1.1.4.2 Setting up the protection:  
Set up the Network Management Card (see user manual).  
Install and configure the protection application on all machines that are to be protected by the UPS :  
-
-
Network Shutdown Module for MGE Office Protections Systems UPS : The software components for each  
platform and the user manuals are on the Solution-Pac-2 CD or available at download.mgeops.com  
Netwatch for Powerware UPS : The software components for each platform and the user manuals are  
available at powerware.com  
1.2 Presentation of the Network Management Card (NMC)  
1.2.1 Compatibility with UPSs  
The Minislot Network Management Card is compatible with the UPS listed into the compatibility list :  
-
-
available at download.mgeops.com for the MGE Office Protection Systems UPS.  
available at powerware.com for the Powerware UPS.  
Network Management Cards acquire information on the operation status of the UPS systems and provide remote  
control of these systems by means of an ETHERNET network from any SNMP administration station or Web browser.  
They also supply alarms to the Network Shutdown Modules to trigger shutdown or other automatic actions for  
protected servers.  
Network Management Card – User Manual  
34003991EN/EB  
Page 8/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Network Management Cards are compatible with the "Enterprise Power Management" supervision system, with the  
MGE Office Protection Systems network protection system and with Powerware Netwatch.  
Network Shutdown Module  
Enterprise Power Manager  
Management-Pac 2  
1.2.2 Direct sending of E-mail  
When a UPS event occurs, the Network Management Card can directly notify up to 4 intranet or extranet addresses  
by e-mail. (see E-mail Notification and E-mail message settings)  
1.2.3 Sending text messages (SMS)  
The card offers the possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is compatible  
with mobile telephone e-mail/SMS transfer systems proposed by ISPs. The format to be used depends on the service  
provider.  
For example, sms.0660256585@votre-login.activmail.net (text messages).  
1.2.4 Compatibility with the Network Management Systems (NMS) – Trap  
sending  
The Network Management Cards are compatible with the major Network Management Systems (IBM Tivoli, CA  
Unicenter, HP Insight Manager). The Management-Pac 2 offering includes the necessary SNMP plug-ins to allow an  
easy integration in the NMS. Events are notified by SNMP trap.  
NMS can subscribe on page “Notified Applications”  
The trap list is given in the appendix.  
1.2.5 Environment Sensor (option)  
The Environment Sensor (66846) solution comprises a box to be connected to the Card Settings port of the  
Network Management Cards.  
Environment Sensor enables measurement of temperature and humidity around the UPS, consideration of external  
alarms via 2 dry contacts and notification of alarms according to pre-programmed thresholds. (see Environmen  
Status and Environment Configuration)  
Network Management Card – User Manual  
34003991EN/EB  
Page 9/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.3 Technical data  
1.3.1 Hardware characteristics  
Dimensions  
Dimensions (L x l x H)  
Weight (gr)  
132 x 66 x 42 mm  
70 g  
Storage  
Storage temperature  
Ambient conditions  
Operating temperature  
Ambient humidity  
ROHS  
-10 °C to 70 °C  
0 °C to 40 °C  
90 % RH max without condensation  
100 % compatible  
1.3.2 EMC Compatibility  
When correctly installed and used in accordance with the manufacturer's instructions, the Network Management Card  
complies with the following standards:  
Safety for ATI: IEC/EN 60950-1 2002  
EMC: EN 61000-6-2 (2002), EN 61000-6-3 (2002). IEC/EN 62040-2 (2002).  
As per European directives:  
Low voltage: 73/23/EEC and 93/68/EEC  
EMC: 89/336/EEC and 93/68/EEC.  
1.3.3 Configuration  
The user can configure the card with one of the following means:  
Web browser  
Local serial link (network parameters)  
BOOTP/DHCP (network parameters).  
Network Management Card – User Manual  
34003991EN/EB  
Page 10/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.3.4 Administration  
Up to 35 workstations(in TCP connected mode) or up to 100(in UDP broadcasted mode) protected by Network  
Shutdown Modules - Central or local configuration.  
Up to 5 browsers connected at the same time (3 in SSL).  
Minimum recommended browser versions: Internet Explorer 6.x / 7.0, Mozilla Firefox 1.5 / 2.0 / 3.0  
E-mail sending configurable according to UPS alarms and transmission of a periodical report.  
Control of UPS on/off switching via the HTML interface.  
Adjustment and control of PowerShare outlets via the HTML interface, sequential starting of the installation and  
optimisation of backup time by shutting down non-priority systems.  
Automatic data and time adjustment via NTP server.  
Protection by encrypted password.  
Protection by secure SSL connection.  
Saving of logs in the non-volatile memory.  
Languages available: English/French/Spanish/German/Italian.  
On-line help in English available for each page.  
Card firmware updated via the network.  
Card Mass settings via the network with the NMC tool.  
1.3.5 Network  
Fast ETHERNET 10/100 Mbits compatibility with auto-negotiation on the RJ45 outlet.  
1.3.5.1 List of ports used  
BootP, DHCP  
HTML  
UDP 68, 67  
TCP 80  
SSL  
TCP 443  
NSM in connected mode  
NSM in broadcasted  
SMTP  
TCP 5000  
UDP 4679 and 4680  
25  
NTP  
123  
161  
162  
SNMP V1  
TRAP SNMP  
1.3.6 Environment sensor  
Temperature measurement from 0 to 70 °C with +/- 1 °C accuracy.  
Measurement of humidity from 0 to 100 % with +/- 6 % accuracy.  
Min / max time-stamped function for temperature and humidity.  
Choice of temperature readings in Celsius or Fahrenheit.  
High and low thresholds, hysteresis and offset adjustable via Web interface.  
Possibility of notification of status changes by e-mail, SMS or SNMP trap.  
Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m).  
Name and status of each configurable contact.  
Network Management Card – User Manual  
34003991EN/EB  
Page 11/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Recording of events and measurements in the card log  
Possibility of shutting down the installation in the event of a threshold being exceeded or on opening / closure of a  
dry contact  
Connection to the card with straight CAT5 RJ45 network cables (maximum card/sensor distance: 20 m)  
Hot installation  
1.3.7 MIB (Management Information Base)  
Compatible with MIB MGE Office Protection Systems V1.7  
The list of objects managed can be found in the appendix  
Network Management Card – User Manual  
34003991EN/EB  
Page 12/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1.3.8 Default parameters  
Function  
Network  
Parameter  
Default value  
166.99.16.16  
255.255.0.0  
0.0.0.0  
Possible value  
IP address  
Network IP address  
Network IP address  
Network IP address  
Active / Deactivated  
Active / Deactivated  
49 characters maximum  
49 characters maximum  
31 characters maximum  
10 to 99999 sec.  
Subnet mask  
Gateway Address  
BOOTP/DHCP  
Firmware Upload  
SMTP server  
Enabled  
Enabled  
smtpserver  
Computer Room Manager  
Computer Room  
60  
System  
UPS Contact  
UPS Location  
History log interval (sec.)  
Environment log interval (sec.) 300  
10 to 99999 sec.  
Default Language  
English  
English / French / Spanish /  
German / Italian  
Manager table  
Access control  
empty  
50 maximum  
User name  
admin  
10 characters maximum  
10 characters maximum  
49 characters maximum  
Non configurable  
Password  
admin  
Community name read  
Trap port  
public  
161  
Date and time  
Date and time adjustment  
Accept automatic update from  
NSM or EPM  
Synchronise with an NTP  
server  
Accept automatic update from  
NSM or EPM  
Synchronise manually  
49 characters maximum  
Non configurable  
NTP server  
Speed  
ntpserver  
9600 baud  
8
Serial link  
Data bits  
Stop bits  
Parity  
Non configurable  
1
Non configurable  
without  
without  
Non configurable  
Flow control  
Non configurable  
Network Management Card – User Manual  
34003991EN/EB  
Page 13/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 Installation  
2.1 Unpacking and check on contents  
The installation kit contents:  
A Network Management Card (66102)  
A serial communication cable for configuration (34003918)  
Installation manual (34003905)  
2.2 Indications  
Network Management Card – User Manual  
34003991EN/EB  
Page 14/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Ethernet port  
LED  
Colour  
Activity  
Description  
Off  
Card not connected to the network.  
ACT  
Green  
Card connected to the network but  
without activity  
On  
Port is active in receiving /  
transmission  
Flashing  
Off  
On  
Port operating at 10Mbits/s.  
Port operating at 100Mbits/s.  
100M  
Orange  
Service port  
LED  
Colour  
Activity  
Description  
Off  
Card startup in progress.  
UPS  
Green  
Communication with UPS in  
progress  
On  
Data  
Normal operation.  
Flashing  
Communication with the UPS is  
operational  
Off  
On  
Configuration menu is active  
Normal operation. Configuration  
menu is deactived  
RS232  
Orange  
Flashing  
Communication with the  
Environment Sensor (option).  
2.3 Installation in the UPS  
The Network Management Card (66102) can be "hot" installed in all UPSs of the MGE Office Protection Systems or  
Powerware range equipped with a Minislot without having to shut it down.  
Remove the protective plastic cover from the Minislot  
Note the card's MAC address prior to insertion  
Insert and tighten the card's retaining screws  
Connect the ETHERNET cable  
Wait 2 min. the card is completely operational when the green UPS Data LED flashes continuously  
Network Management Card – User Manual  
34003991EN/EB  
Page 15/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4 Sensor installation (option)  
The Environment sensor is available as an option on the Network Management Card and is available from MGE Office  
Protection Systems (reference 66846).  
The sensor allows remote monitoring of the UPS's environment through regular measurements: temperature, humidity,  
status of two external contacts. It also enables notification of alarms (e-mail, trap SNMP) according to pre-programmed  
thresholds.  
It is connected to the Service port (Settings/Sensor) directly on the Network Management Card with a standard  
Ethernet cable (20 meters maximum).  
Recognition is automatic. Supervision and configuration are performed via a menu that can be accessed directly from  
the home page.  
Network Management Card – User Manual  
34003991EN/EB  
Page 16/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3 Configuration  
3.1 Configure IP parameters  
Once the card has started:  
Connect one end of the cable (34003918) to the Service port.  
If the environment sensor was previously connected, the card must be restarted in order to access the configuration  
menu.  
Connect the other end of the cable to the COM port (IOIOI) of a PC.  
Launch a HyperTerminal™ type emulator with the following configuration:  
Speed: 9600  
Data bits: 8  
Parity: none  
Stop bits: 1  
Flow control: none  
"Locally reproduce the characters entered" option: deactivated.  
Enter admin. The main menu is displayed:  
-----------------------------------------------------------------------------  
EATON  
NETWORK MANAGEMENT CARD  
-----------------------------------------------------------------------------  
1 : Reset  
2 : Network configuration  
3 : Set Login Password to Default  
4 : Return to Default Configuration  
0 : Exit  
-----------------------------------------------------------------------------  
Network Management Card – User Manual  
34003991EN/EB  
Page 17/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.1 Your network is equipped with a DHCP server  
The card is configured by default with this service activated.  
The card automatically collects IP parameters.  
To know the IP parameters, type 2, the next menu is displayed:  
-----------------------------------------------------------------------------  
Network settings  
-----------------------------------------------------------------------------  
1 : Read Network settings  
2 : Modify Network settings  
3 : Set Ethernet speed  
0 : Exit  
-----------------------------------------------------------------------------  
Then type 1. The menu is displayed:  
Network configuration :  
MAC address : 00:20:85:FD:1C:07  
Mode : Static IP  
IP address : 166.99.21.94  
Subnet mask : 255.255.248.0  
Gateway 166.99.17.1  
Note the IP address.  
To exit, enter 0 then 0. The card is operational.  
Note: As long as the card is not connected to the network, it continuously attempts to make connection. Once the  
connection has been established, the operational mode presented in the table above becomes effective.  
Network Management Card – User Manual  
34003991EN/EB  
Page 18/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.1.2 Your network is not equipped with a DHCP server  
In the main menu enter 2, then 2 again. The menu is displayed:  
Follow the instructions and enter the static IP parameters.  
At the end of the menu, wait for the "Done" message to be displayed indicating that the IP parameters have been  
saved.  
-----------------------------------------------------------------------------  
Network settings  
-----------------------------------------------------------------------------  
1 : Read Network settings  
2 : Modify Network settings  
3 : Set Ethernet speed  
0 : Exit  
-----------------------------------------------------------------------------  
For each of the following questions, you can press <Return> to select the value  
shown in braces, or you can enter a new value.  
Should this target obtain IP settings from the network?[N] N  
Static IP address [166.99.21.94]? 166.99.21.21  
Static IP address is 166.99.21.21  
Subnet Mask IP address [255.255.248.0]? 255.255.255.0  
Subnet Mask IP address is 255.255.255.0  
Gateway address IP address [166.99.17.1]? 166.99.17.1  
Gateway address IP address is 166.99.17.1  
Wait during your new configuration is saved ...  
Reset the card to take into account the new configuration.  
Return to the main menu and enter 1 then 2.  
The card restarts with the new IP parameters.  
3.2 Test after configuration  
To check that the Network Management Card is operational after installation and configuration.  
From a station connected to the same subnet as the card, open a web browser and enter the IP address of the card in  
the address field  
Check the display of the home page.  
Network Management Card – User Manual  
34003991EN/EB  
Page 19/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4 Supervision and administration by browser  
On a computer equipped with a Web browser (Internet Explorer, FireFox or Netscape recommended), enter the  
address initialised previously in the Installation chapter (e.g. http://166.99.16.16.)  
The "UPS properties" home page is displayed.  
4.1 Optimising the performance of your browser  
To view status changes on the UPS in real time, the browser must be configured so that it automatically refreshes  
all the objects on the current page.  
Example on IE 6: Tools / Internet Options / General / Parameters menu, tick Every time this page is visited and  
validate.  
Network Management Card – User Manual  
34003991EN/EB  
Page 20/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2 UPS  
4.2.1 UPS properties page  
This page is automatically refreshed every 10 seconds.  
From this page, access to the main UPS information is available thanks to the combo box (see screen copy below).  
The different choices are the following ones:  
“UPS Status”: (chosen by default) this page gives instant access to the essential information about your UPS.  
“UPS Alarms”: to view the list of current alarms.  
“UPS Modules”: (available on modular UPS) to view general information on each modules.  
“About your UPS”: provides information on the UPS and the card, in particular, the model range and software  
version.  
These different pages are detailed in the following chapters.  
Network Management Card – User Manual  
34003991EN/EB  
Page 21/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.1.1 "UPS" zone: general information on the UPS.  
Indication of the picture and generic name of the UPS range  
Computer room: Customised name of your system.  
You can change this name on the "System" page.  
UPS status icon :  
The various icons showing the status of the UPS are:  
Normal operation  
Alarm present. This icon links directly to the  
alarm page.  
Loss of communication with the UPS  
Animated synoptic: An animated synoptic gives a global overview of the UPS current operating mode.  
This synoptic is available on all On-Line UPS.  
The synoptic drawing depends on the UPS topology. The different drawings are described in the table below.  
UPS with automatic bypass  
UPS with automatic and manual bypass  
Network Management Card – User Manual  
34003991EN/EB  
Page 22/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS without automatic bypass  
Note: In case of loss of communication with the UPS, all the elements of the synoptic are grey.  
The various elements of the synoptic are the following ones:  
AC Normal Input :  
In tolerances  
Out of tolerances  
AC Normal Flow :  
AC to DC converter powered by AC Normal  
AC to DC converter not powered by AC  
Normal  
AC to DC Converter:  
Powered  
Not powered  
Internal failure  
Network Management Card – User Manual  
34003991EN/EB  
Page 23/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery :  
Remaining capacity > 50%  
Remaining capacity < 50%  
Battery to be checked (battery test result)  
Battery Output Flow :  
DC to AC converter powered by battery  
DC to AC converter not powered by  
battery  
DC to AC Converter Input flow :  
Energy flow  
present  
No energy flow  
DC to AC Converter :  
Powered  
Not powered  
Internal failure  
DC to AC Converter Output :  
Energy flow  
present  
No energy flow  
AC Bypass Input :  
In tolerances  
Out of tolerances  
Network Management Card – User Manual  
34003991EN/EB  
Page 24/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AC Automatic Bypass Flow :  
Energy flow  
present  
No energy flow  
AC Automatic Bypass Status :  
Powered  
Not powered  
Internal failure  
AC Manual Bypass Flow :  
Energy flow  
present  
No energy flow  
AC Manual Bypass Status :  
Open  
Closed  
AC Output Flow :  
Energy flow  
present  
No energy flow  
AC Output :  
Load protected  
Load not  
protected  
Network Management Card – User Manual  
34003991EN/EB  
Page 25/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS measurements :  
Boxes showing measurements appear when synoptic elements are hovered by the pointer. See example below.  
These measurements are available for AC to DC converter, Battery, DC to AC converter and automatic bypass.  
The measurements available in these boxes depend on the UPS range.  
Network Management Card – User Manual  
34003991EN/EB  
Page 26/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.1.2 "UPS status" zone: Essential information  
"Active sources": (available on parallel or modular UPS)  
x UPS + y UPS redundant :  
x indicates the minimal number of UPS necessary to power the load,  
y indicates the number of UPS in redundancy.  
An alarm can be generated if the number of UPS in redundancy is less than a configurable threshold. See UPS  
modules section.  
"Power source": indicates whether the power comes from the utility or from the UPS battery  
"Output load level": indicates the power percentage used at UPS output  
"Output": indicates if the different UPS outputs are protected.  
"Master": indicates if the UPS main output is protected  
"Group1 and Group2": indicates if the controlled outlets (if available) are powered.  
The various icons showing the status of the UPS outputs are:  
Outlet powered  
(green outlet)  
Outlet not powered or not  
(red outlet)  
protected  
Battery Information :  
"Battery load level": remaining battery charge (in percent).  
The information is completed with the two following labels:  
“Charging” : if the utility power is present and the battery charge is in progress  
“Discharging”: if the UPS operates on battery.  
“Fault”: if the battery is faulty.  
"Remaining backup time": Estimation of the battery's maximum backup time remaining before UPS shutdown  
"Battery status": Result of the last automatic battery test carried out by the UPS  
Possible values are:  
– OK: the test was completed correctly  
– NOK: the battery needs to be checked  
– Deactivated: the automatic battery test is not validated on the UPS  
Network Management Card – User Manual  
34003991EN/EB  
Page 27/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.1.3 Viewing the modules  
Click on "UPS Modules" scroll list to view the information about the UPS modules.  
Active sources:  
x UPS + y UPS redundant :  
x indicates the minimal number of UPS necessary to power the load,  
y indicates the number of UPS in redundancy.  
The addition of these 2 values is the total number of available UPS.  
The "Minimum redundant UPS modules to trigger alarm can be configured from this page. The button Save makes  
the card setting the parameter into the UPS. A warning message informs the user about the consequences of this  
parameters modification.  
The redundancy lost can generate Email notification (if set in the email notification page) and SNMP trap. It can  
also be used by NSM for server protection criteria.  
The Module Nr gives the location of the module in the UPS.  
Network Management Card – User Manual  
34003991EN/EB  
Page 28/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Status can take the next forms:  
or when the module is working properly with no alarm.  
when the module has at least one alarm (level Warning) active.  
when the module has at least one alarm (level Critical) active.  
when the module has a communication fault.  
When the module is working properly with no alarms, the icon is not reactive, otherwise it is reactive and clicking on it  
makes the page Alarm Table appear.  
"Output load level": Value of the percentage of load at module output  
"Battery load level": Percentage of charge available in the battery module  
Network Management Card – User Manual  
34003991EN/EB  
Page 29/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.1.4 Viewing the alarms  
Click on "Alarm Table" scroll list to view the list of current alarms. The table of managed alarms is included in the  
appendix.  
The level of the alarms appears like below:  
Critical  
Warning  
Unknown  
Alarm table for standard UPS  
Network Management Card – User Manual  
34003991EN/EB  
Page 30/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarm table for modular UPS  
Network Management Card – User Manual  
34003991EN/EB  
Page 31/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.1.5 Viewing the “About your UPS” window  
Click on "About your UPS" scroll list to view the information about the UPS and the card.  
Network Management Card – User Manual  
34003991EN/EB  
Page 32/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.2 On-line help  
On-line contextual help in English is available at the top of each page by clicking on the Help link, which is always  
located on the top right corner. The navigation menu of the on-line help is identical to that of the card's pages.  
The Help page always opens a new window.  
Network Management Card – User Manual  
34003991EN/EB  
Page 33/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.3 UPS control  
Click on the "UPS Control" section in the menu  
The parameters of this menu can only be modified after entering the "Login" and "Password". The following screen is  
proposed automatically:  
The default login and password are: admin/admin  
Each field accepts up to 10 characters max.  
After the login and password are entered, they remain active for 5 minutes.  
If the browser is closed, they will have to be re-entered.  
An error in either field results in systematic rejection of the requested action (save, page access, card reboot…). After  
three unsuccessful attempts, the browser must be rebooted.  
These two fields do not travel "decoded" on the IT network. They are encrypted with an MD5 type algorithm, ensuring  
total confidentiality.  
In the event of password loss, the user can return to the default values via the maintenance menu.  
Network Management Card – User Manual  
34003991EN/EB  
Page 34/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UPS configuration may prevent the shutdown and restart commands from being properly run. Read the UPS user  
manual for more information.  
This page enables triggering of startup and shutdown sequences for the UPS main output and controlled outlets.  
The status of each output is displayed by a symbol associated with the Off label (red symbol) or On (green  
symbol).  
The shutdown sequences take into account the time required for the registered servers to shut down without  
losing data (see shutdown parameters).  
The main outlet has priority over the controlled outlets. Shutdown of the main outlet causes the controlled outlets  
to shut down. Controlled outlets can only be started if the master outlet is on.  
The Check column proposes six different commands, and a command is only actually started after clicking on  
'Execute':  
"Safe power down": A sequence to switch off output power is launched immediately. The systems supplied are shut  
down correctly while the shutdown sequence is running, then the output is cut.  
"Safe power down & reboot": A sequence to switch off then restore output power is launched immediately. The  
powered systems are shut down correctly during the shutdown sequence, then the output is switched off.  
Finally, the restart sequence is launched at the end of the time delay specified in the "Toggle duration" parameter. The  
output status is updated.  
Network Management Card – User Manual  
34003991EN/EB  
Page 35/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
"Immediate On": A sequence to switch on output power is launched immediately. The output is re-powered and the  
systems supplied start up correctly.  
"Delayed, safe power down": This is the same switch off sequence as for the "Safe power down" command, but  
postponed by the number of seconds programmed in the "Off Delay" parameter.  
"Delayed, safe power down & reboot": This is the same switch off then on sequence as for the "Safe power down &  
reboot" command, but postponed by the number of seconds programmed in the "Off Delay" parameter.  
"Delayed On": This is the same switch on sequence as for the "Immediate On" command, but postponed by the  
number of seconds programmed in the "On Delay" parameter.  
The Save button saves the Off Delay, Toggle duration and On Delay parameters on the card.  
Security: The administrator must click on Save and enter his/her login/password to save modifications or run  
commands. The default login and password by default are: admin/admin  
Network Management Card – User Manual  
34003991EN/EB  
Page 36/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.4 UPS weekly schedule programming  
Click on the "Weekly schedule" section of the menu.  
UPS configuration may prevent the shutdown and restart commands from being properly run. Read the UPS user  
manual for more information.  
The weekly schedule enables the administrator to optimise power consumption or program a reboot of the protected  
equipment at a set time.  
In a shutdown sequence, the Network Shutdown Modules connected to the card are informed and ensure that each  
machine is shut down correctly before the UPS output is switched off. Up to 7 UPS shutdown sequences can be  
programmed in one week, with a minimum shutdown delay of 30 minutes.  
The On / Off sequences are valid only if the card's time has been properly set.  
Security: The administrator clicks on "Save" and enters his/her login / password to save any edits. The login and  
password by default are: admin/admin  
Network Management Card – User Manual  
34003991EN/EB  
Page 37/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.5 Shutdown parameters  
This page enables viewing and configuration of UPS operating parameters in battery mode and for power restoration.  
Click on the "Shutdown parameters" section in the menu to see the list of parameters.  
When you tick the Show advanced parameters option, extra parameters are displayed. These parameters enable, in  
particular, adjustment of certain thresholds related to the percentage of remaining battery charge level.  
The Output column enables each outlet to be named (maximum 20 characters).  
Note  
As priority is given to the main outlet, the card cannot supply the controlled outlets when main outlet power is off.  
Network Management Card – User Manual  
34003991EN/EB  
Page 38/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
For the main outlet ("Master" by default)  
The first shutdown criteria initiates the restart of the shutdown sequence.  
If remaining time is under (0 to 99999 seconds, 180 by default) is the minimum remaining backup time from which  
the shutdown sequence is launched.  
If battery capacity is under (0 to 100%); this value cannot be less than that of the UPS and is the minimum  
remaining battery capacity level from which the shutdown sequence is launched.  
Shutdown after (0 to 99999 minutes, not validated by default) is the operating time in minutes left for users after a  
switch to backup before starting the shutdown sequence.  
Shutdown duration (120 seconds by default) is the time required for complete shutdown of systems when a switch  
to backup time is long enough to trigger the shutdown sequences. It is calculated automatically at the maximum of  
Shutdown duration of subscribed clients but can be modified in the Advanced mode.  
If battery capacity exceeds Minimum battery level to reach before restarting the UPS after utility restoration  
.
Important: Certain UPSs do not support this option  
For the controlled outlets ("group 1 or group 2" by default)  
The page enables programming of operation time and level in backup mode to manage outlet load shedding in the  
event of electric power failure:  
Switch Off after (from 0 to 99999, 65535 by default) defines the time during which the outlet is supplied starting  
from the moment of utility failure. Caution, this time includes the outlet shutdown duration.  
Switch Off if battery capacity under (0 by default) is an extra condition for outlet shutdown that can trigger the  
shutdown sequence before the shutdown duration runs out.  
Shutdown duration is the time required for complete shutdown of the systems supplied by the outlet when an  
outlet shutdown sequence is launched.  
It is calculated automatically using the maximum shutdown durations of notified applications on the outlets.  
Switch On after (from 0 to 99999, default 65535) is the period between main output startup and startup of the  
relevant programmable outlet, therefore outlet startup can be delayed in relation to the main output.  
Important: Certain UPSs do not support this option  
Security: The administrator has to click on Save and enter his/her login/password to save any modifications. The login  
and password by default are: admin/admin  
Network Management Card – User Manual  
34003991EN/EB  
Page 39/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.6 Measurements  
Click on "Measurements" in the menu  
The next window shows the measurements for a mono phases UPS.  
The following measurements are saved and time-stamped (env. 430):  
"AC Normal : Voltage": Value of the utility voltage supplying the UPS  
"AC Normal : Frequency": Value of the utility frequency supplying the UPS  
"AC Output : Voltage": Value of the output voltage of your UPS  
"AC Output : Frequency": Value of the output frequency of your UPS  
"AC Output : Power (kVA)": Value of the output power of your UPS  
"AC Output : Load level (%)": Value of the percentage of load at UPS output  
"Battery : Capacity (%)": Percentage of charge available in the battery  
"Battery : Remaining time (mn)": Estimation of the remaining backup time  
The save frequency of these values is defined in the "System" page (60 seconds by default). Approximately 435  
time-stamps are stored permanently on the card. The oldest time-stamps are automatically deleted.  
"Save Log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type  
spreadsheets)  
"Clear Log" enables deletion of all records. Enter the login/password to validate this action.  
Network Management Card – User Manual  
34003991EN/EB  
Page 40/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.7 Event log  
Click on "Event Log". in the menu  
"Save log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type  
spreadsheets)  
"Clear log" enables deletion of all records. The administrator must enter his/her login / password to validate this  
action.  
The card can save 435 events. The table of managed alarms is included in the appendix.  
Network Management Card – User Manual  
34003991EN/EB  
Page 41/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.2.8 System log  
Click on "System log". in the menu  
"Save log" enables all saved values to be opened or saved in CSV format. (compatible with Excel type  
spreadsheets)  
"Clear log" enables deletion of all records. The administrator must enter his/her login / password to validate this  
action.  
The card can save 435 events. The table of managed alarms is included in the appendix.  
Network Management Card – User Manual  
34003991EN/EB  
Page 42/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3 Notification  
4.3.1 Email Notification  
The card offers the possibility of redirecting UPS alarms to an e-mail server. The format of these e-mails is  
compatible with mobile telephone transfer systems using text messages (SMS).  
Network Management Card – User Manual  
34003991EN/EB  
Page 43/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Recipient List:  
On the left side of this page, up to four recipients can be configured to receive e-mails from the card. Each  
addressee has its own trigger events, selected from the right side of the page, for which an e-mail is sent. The  
card’s log indicates e-mail transmission errors.  
Each recipient is configured with the following parameters:  
Recipient: (Field is limited to 99 characters) this is the e-mail address of the person or department to  
receive the e-mail.  
The default value is recipientx@domain.com  
Attached files: The files selected (Measurements, Event log, System log, Environment  
measurements) are enclosed with each e-mail sent. The files are sent in CSV format  
Periodic report: In addition to the e-mails sent when events occur, a periodic e-mail containing the 3  
log files can be sent to the recipient every x days at the time specified by the user.  
To configure the first transmission, specify the day, time and frequency of the next transmission in  
the "next report" box. After this date, the page will show the date and time of the next transmission.  
Data are sent in CSV format.  
Save: Saves any modifications.  
Test enables an e-mail to be sent to the recipient immediately. This is one way of checking e-mail transmission,  
particularly access to the SMTP server configured in "Network" settings. A transmission report is added to the  
system log.  
The event label in the subject and text of the message is replaced with a test label.  
If the user makes any modifications to the page, they must be saved before using the "Test" function.  
Notified events:  
The right side of the page shows the events that can be notified.  
By default, only the main events of battery operation and a few UPS alarms are accessible. All the events appear if  
the Show/Hide Events option is actuated.  
By default, two events are selected for notification. The user can modify this pre-selection by ticking other events  
or can, on the contrary, restore the initial configuration by clicking Set Default.  
Email Message Settings: access to the message configuration page  
Network Settings: enables the name of the SMTP server to be entered. See page  
Security: The administrator has to click on Save and enter his/her login/password to save any modifications. The  
default  
login and password are: admin/admin  
Network Management Card – User Manual  
34003991EN/EB  
Page 44/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.3.2 E-mail Message Settings  
This page enables customisation of the content of the messages received by recipients of e-mails sent by the card.  
Customisation is common to the four recipients that can be notified (see E-mail notification).  
Sender  
(59 characters maximum) identifies the source of the message. The default value is ups@domain.com.  
This field is free. However, depending on the type of SMTP server configuration, it is possible that the server  
checks that the domain name contained in the Sender address exists, and even that the user in the Sender address  
belongs to this domain.  
Subject  
enables the user to specify the subject of the e-mail to be sent. By entering some free text and selecting from  
several optional fields, if desired, the message subject is built:  
- UPS name recalls the name of the UPS; it may or may not be selected.  
- UPS location recalls the geographic location of the UPS (see System Settings); it may or may not be selected.  
- Event message identifies the event generating the e-mail; it may or may not be selected.  
Message text is a free zone long of 255 characters maximum.  
Network Management Card – User Manual  
34003991EN/EB  
Page 45/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The body of the e-mail sent is composed of:  
- Message text, which is free text.  
- The date and time of the event, as saved in the log.  
- URL of the card, enabling a direct link with the card to be established.  
- Attachments, as configured for the e-mail recipients .- duplication of the subject, as configured.  
Network Management Card – User Manual  
34003991EN/EB  
Page 46/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4 Configuration  
The parameters of this menu can only be modified after entering the "Login" and "Password". The following screen is  
proposed automatically:  
The default login and password are : admin/admin  
Each field accepts up to 10 characters max.  
After the login and password are entered, they remain active for 5 minutes.  
If the browser is closed, they will have to be re-entered.  
An error in either field results in systematic rejection of the requested action (save, page access, card reboot…). After  
three unsuccessful attempts, the browser must be rebooted.  
These two fields do not travel "decoded" on the IT network. They are encrypted with an MD5 type algorithm, ensuring  
total confidentiality.  
In the event of password loss, the user can return to the default values via the maintenance menu.  
Network Management Card – User Manual  
34003991EN/EB  
Page 47/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.1 Network settings  
Click on "Network" in the menu.  
This menu enables the administrator to configure the network parameters of the card and authorisation of the remote  
upgrade of the embedded system.  
IP Address: The IP address of the card (e.g.: 166.99.22.252).  
Subnet Mask: The mask of the sub-network of your network (e.g.: 255.255.255.0).  
Gateway Address: Indicate the IP address of the gateway to access the stations located outside the card’s subnet  
(e.g.: 166.99.17.1).  
Hostname must be suited to the card. This is the first part of the fully qualified domain name, used by the DNS.  
As the card does not support NetBIOS protocol, the hostname will only be sent to DNS if the DHCP server sends it  
the hostname with the new IP address. This mechanism is described in the update of the DNS protocol RFC 2136  
Domain Name is the domain to which the card belongs. This is the part of the fully qualified domain name that  
follows the hostname and is used by the DNS. The default value of the two parameters comprising the fully  
qualified domain name: ups.domain.com  
BOOTP/DHCP: Authorises (choose "Enabled") configuration of network parameters with your BootP/DHCP server  
when the card is booted.  
Mode of card operation with server: After each startup, the card makes 5 attempts to recover the network  
parameters. If no response is received from the server, the card boots with the last saved parameters from the  
previous start. These parameters are those shown on the page.  
The default value for this parameter is "Enable"  
Note 1:  
Network Management Card – User Manual  
34003991EN/EB  
Page 48/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the hostname is not used, the IP address supplied by the DHCP server must be fixed to maintain connection with the  
clients installed on the stations to be protected.  
Note 2:  
During the first connection, if the DHCP query is not successful, the NMC starts with the following IP configuration:  
IP address:166.99.16.16  
Subnet mask: 255.255.255.0  
Gateway Address: 0.0.0.0  
Firmware Upload: Authorise (chose "Enabled") remote updating of the card's embedded software.  
The default value for this parameter is "Enabled".  
Primary DNS Server: contains the IP address of the main DNS server ensuring conversion of the domain name to IP  
address.  
Secondary DNS Server: contains the IP address of the secondary DNS server ensuring conversion of the domain  
name to IP address if the primary DNS server is not available.  
SMTP Server: contains the name or IP address of the local server with which the card connects to send e-mails.  
It may be filled in either as host + domain name (DNS resolution), or directly with the IP address.  
The default value is smtpserver. The card uses the standard port (25) for sending e-mails.  
Important note:  
The card must be rebooted after any changes to these parameters.. See "System" page  
Security: The administrator has to click on Save and enter his/her login/password to save any modifications.  
Network Management Card – User Manual  
34003991EN/EB  
Page 49/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.2 System  
Click on "System" in the menu.  
This menu enables the customisation of the information on the UPS properties pages.  
UPS Contact: This text field is limited to 49 characters. Enter the name of the person responsible for UPS  
administration at IT network level and/or electrical maintenance. This field does not appear on any other Web page.  
By default, its value is "Computer Room Manager".  
UPS Location: Enter a description (limited to 31 characters) of the location of the UPS in your installation (e.g.  
Computer room E1-C066). This text is displayed in the home page. By default, its value is "Computer Room".  
Default Language: Enables initialisation of the browser language at card connection.  
Choice of one of the available languages: English, French, German, Spanish, Italian changes the language of the  
html interface pages (reboot the browser after modification).  
History log interval: [from 5 to 99999 sec., 60 by default]. Measurement save period.  
Environment log interval: [from 60 to 99999 sec., 300 by default]. Temperature and humidity measurement save  
period. Reset Communication button: performs a remote reboot of the card without modifying the configuration.  
This action is compulsory for consideration of any changes made on the "Network Settings" page. Security of this  
operation is ensured by requesting Login and Password.  
Network Management Card – User Manual  
34003991EN/EB  
Page 50/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Factory Reset button: enables restoration of the default configuration of all the card’s parameters. TCP/IP  
parameters: IP address, subnet mask, gateway and BootP/DHCP value are maintained if the "Keep TCP/IP  
parameters" option is selected. Security of this operation is ensured by requesting Login and Password. The  
default login and password are : admin/admin  
Network Management Card – User Manual  
34003991EN/EB  
Page 51/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.3 Notified Applications  
Click on "Notified Applications" in the menu.  
Security: The administrator has to enter his/her login/password in order to view this information.  
This menu enables:  
The addition of the supervision stations receiving traps and configuration of the trap type.  
To list all the Notified Applications and the main parameters.  
To test the operation of notified applications  
by simulating power loss  
by sending a real shutdown sequence.  
Up to 100 destinations can be managed by the card :  
35 in TCP connected mode or  
100 in UDP not connected mode or  
mixed mode: 20 connected and 50 not connected.  
Important note: It is not necessary to add the Network Shutdown Modules protecting your servers in this list. These  
modules subscribe and unsubscribe themselves automatically.  
Select an entry in the list to modify the values in the edit zone at the bottom of the page. The table displays the  
following information:  
The All button: Allows the following information to be displayed.  
Nr is the index where the application is stored into the table.  
Hostname or Address IP: By priority, the hostname of the computer is displayed when the IP address can be  
converted into a hostname by a DNS server or if the application has been entered as a hostname.  
Application Name : Gived by the application at subscription time.  
Output: number of the UPS output from which the client is powered.  
Configuration: shows where the parameters of the Network Shutdown Module come from: Local (coming from the  
Network Management Card – User Manual  
34003991EN/EB  
Page 52/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
application) or Central (coming from the card).  
The Central shutdown configuration is available by clicking on the Configuration link.  
Shutdown duration: the shutdown duration necessary to properly shutdown the computer.  
Shutdown after: the time available to the user from the power failure until the launch of the shutoff sequence of the  
UPS and equipment This parameter is optional.  
Many actions are available on this page:  
Remove: Depending on the kind of application, the selected ones will definitively disappear from the table as SNMP  
applications, or they will disappear and automatically re-subscribe as Network Shutdown Module applications.  
Utility failure Test: Two alarms, 'Utility failure' and 'Utility restored' spaced 60 seconds apart, will be sent to the  
applications selected, making sure that the applications can be reached over the network.  
Shutdown Test: This test simulates a UPS on battery operation. It enables an easy check to see if the server  
protection works correctly.  
- No intervention on the UPS is required.  
- The applications selected will process the simultaneous alarms and perform an actual shutdown sequence.  
WARNING!  
- This test will generate a REAL shutdown sequence of the selected servers on which the Network Shutdown Module  
application is running.  
Add NMS: allows an SNMP trap receiver to be added such as a Network Management System.  
Modify NMS: allows an SNMP trap receiver to be modified.  
Both buttons open a new window where it is possible to enter the Application name, the Hostname or IP Address, the  
Trap community and the severity.  
The default severity value is 1 – Warning  
Network Management Card – User Manual  
34003991EN/EB  
Page 53/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.4 Central shutdown configuration  
Click on "Notified Applications" in the menu, then "Configuration".  
This page is used to define either the "shutdown" or the "notification" settings used by the Network Shutdown  
Modules that connect to Network Management Card. These settings are used by the Network Shutdown Modules if  
they are in central-configuration mode or if their configuration is not valid.  
Shutdown duration: the shutdown duration necessary to properly shutdown the computer.  
Shutdown after: the time available to the user from the power failure until the launch of the shutoff sequence of the  
UPS and equipment. This parameter is optional. Uncheck the box if you wish not to use this parameter.  
Broadcast : Sends network notifications to the Administrators and Users groups on events declared in the server  
hosting the NSM  
If you wish to set up a new configuration for the Network Shutdown Modules already set to "central-configuration  
mode", proceed as indicated below:  
Change the Network Shutdown Module parameters in the "Notified Applications" page.  
Click the "Save" button.  
In this page, select the NSMs for which you want to apply the new configuration.  
Press the "Remove" button.  
The NSMs selected will disconnect then reconnect and use the new configuration.  
Network Management Card – User Manual  
34003991EN/EB  
Page 54/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.5 Access control  
Click on "Access Control" in the menu.  
To access this page, the login and password are systematically requested if they have not already been entered.  
This menu enables configuration of the different parameters enabling secure access to the card via a browser or  
SNMP.  
Login: This text field is limited to 10 characters - Enables secure access and modification of pages. Default value  
"admin"  
Change / Confirm password: This text field is limited to 10 characters - Enables secure access to Configuration  
menu pages. Default value "admin"  
Current Community Read name: Indicates the SNMP community name used for read operations  
Change Community Read-Only: This text field is limited to 49 characters - Enables the SNMP community name  
used for read operations to be changed  
Security mode: manages the various authentication methods for page access  
Authentication for configuration: Only the configuration pages are protected by login / password  
Full authentication: All pages are protected by login / password  
SSL and full authentication: All pages are protected by login / password and are only accessible in SSL  
Network Management Card – User Manual  
34003991EN/EB  
Page 55/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SSL Access: When selected, access to the Web interface is made in secure mode (https).  
Connections with Network Shutdown Modules stay in standard mode (secure TCP)  
SSL Security Implementation:  
SSL  
version 3.0  
version 1.0  
TLS_RSA_WITH_512_MD5  
RSA  
TLS  
Method  
Auth  
Key Exchange  
Encryption  
Digest  
RSA  
RC4_512  
MD5  
Changes take effect after a card reboot  
Network Management Card – User Manual  
34003991EN/EB  
Page 56/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.6 Date and time  
Click on "Date and Time" in the menu.  
This menu enables initialisation of the date and time of the card in three different ways.  
The date format is always of year/month/day type  
Set manually: Enables initialisation of the date and time of the card, with the values entered in the Date and Time  
fields. This update is made after clicking on the "Save" button.  
Maximum drift is +/- 2 min./month  
Accept automatic update from NSM or EPM: Enables initialisation of the date and time of the card, with the values  
provide by the Network Shutdown Modules or the Enterprise Power Management.  
Network Management Card – User Manual  
34003991EN/EB  
Page 57/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Synchronize with NTP server: Enables connection with a time server, either available on the company’s internal  
network or on the Web. This server communicates GMT time. The IP address or hostname of the time server must  
be entered, and the time zone of your geographic area must then be selected from the list. Connection is made with  
the server and the date and time are set after clicking on the "Save" button. Time is updated every five hours, thus  
preventing any drift in the time. After two attempts, if the NTP server is not accessible, the card shifts to manual  
mode.  
The card uses the NTP protocol (UDP 123 port). The "firewall" must be set to transmit queries outside the intranet.  
No error message is generated if the time server contact fails.  
Note 1:  
The even the card is used in a UPS supporting time-stamping, the card's time is automatically synchronized with that  
of the UPS.  
Note 2:  
After start-up, if the card is in manual mode or if no NTP server was reached, the card initializes at 01/01/1970  
Network Management Card – User Manual  
34003991EN/EB  
Page 58/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.4.7 Firmware upload  
Click on "Firmware Upload" in the menu.  
This menu enables a new firmware version to be uploaded  
To upload a new version of the card's firmware, select the file to be loaded using the "Browse…" button and click  
Upload.  
Do not interrupt the operation before the card displays the following screen:  
Network Management Card – User Manual  
34003991EN/EB  
Page 59/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5 Environment Sensor (option)  
The environment sensor (66846) is an option that enables temperature and humidity to be measured, and indication of  
the position of two external contacts. It is connected with a standard network cable to the Card Settings port of the  
Network Management Card.  
The card automatically detects sensor presence. The main menu then displays an additional section "Environment"  
with the following elements:  
Status  
Configuration  
Log  
Important note: To switch the serial port to the configuration mode, just disconnect the cable and reset the card.  
4.5.1 Characteristics  
Temperature measurement from 0 to 70 °C with +/- 1° C accuracy  
Measurement of humidity from 0 to 100% with +/- 6% accuracy  
Min / max time-stamped function for temperature and humidity  
Choice of temperature readings in Celsius or Fahrenheit  
High and low thresholds, hysteresis and offset adjustable via Web interface  
Possibility of notification of status changes by e-mail, SMS or SNMP trap  
Position detection of 2 dry contacts (maximum sensor/contact distance: 20 m)  
Name and status of each configurable contact  
Recording of events and measurements in the card log  
Possibility of shutting down the installation safely if one of the thresholds is exceeded or dry contact status  
change  
Connection to the Network Management Card by CAT5 straight RJ45 network cables (maximum card/sensor  
distance: 20m)  
Network Management Card – User Manual  
34003991EN/EB  
Page 60/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.2 Environment Status  
For both measurements, a graduated gauge proposes the following functions:  
The cursor indicates the current value.  
Two red zones to the left and right represent the high and low thresholds that can be set on the Environment Settings  
page.  
When the measured value enters one of these zones, an alarm can be notified (see Notification parameter in the  
Environment Settings page).  
Time-stamped minimum and maximum temperatures show the extreme values recorded since the last Reset Min/Max,  
a thin dotted line shows their positions on the gauge.  
Min and Max can be forced at any time to the current value by clicking on the Reset Min/Max button.  
Calibrate: The sensor is factory-calibrated, but the user can apply an offset to adjust the measurement.  
Input #1 and Input #2 show the position of the two contacts acquired by the sensor.  
The position is displayed with the parameters entered in the Environment Settings page.  
The last status change of each contact is time-stamped.  
The Internet browser updates this page every 10 seconds  
Network Management Card – User Manual  
34003991EN/EB  
Page 61/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.3 Environment Settings  
The environment sensor measures temperature, humidity and gives the status of the 2 contacts (used for door, alarms  
or generator unit).  
The temperature and humidity thresholds can be adjusted and can trigger notification and correct shutdown of the  
protected system.  
The Sensor name is the function name given to the sensor, usually it enables location of the sensor.  
Temperature: Choose the temperature unit (°C or °F) from the selection box.  
High threshold: if this value is exceeded, a notification if enabled. The default value is 40 °C / 104 °F.  
Low threshold: If this value is exceeded, a notification if enabled. The default value is 5 °C / 41 °F .  
Hysteresis must be set to prevent multiple notifications if temperature fluctuates around a threshold.  
The default value is 2 °C / -3.6 °F.  
The high alarm disappears when the value drops below the High threshold - Hysteresis value  
The low alarm disappears when the value returns above the Low threshold + Hysteresis value  
Humidity  
High threshold: If this value is exceeded, a notification is sent if this is validated. The default value is 90%.  
Low threshold: If this value is exceeded, a notification is sent if this is validated. The default value is 5%.  
Hysteresis must be set to prevent multiple notifications if humidity fluctuates around a threshold. The default value is  
5%.  
The high alarm disappears when the value drops below the High threshold - Hysteresis value  
Network Management Card – User Manual  
34003991EN/EB  
Page 62/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The low alarm disappears when the value returns above the Low threshold + Hysteresis value  
Input #1 and Input #2: Enter an identifier corresponding to the acquired contact (e.g.: rack door, air conditioning,  
generator unit, etc.). Max. length is 28 characters.  
when closed and when open: are the names associated to the two contact positions. (e.g.: "open" and "closed" for a  
door, "On" and "Off" for a generator).  
Each status change triggers a notification if enabled.  
When the Notification box is enabled, the following functions are activated for each event selected:  
display in the list of current alarms  
Consideration in the UPS log  
SNMP trap generation  
notification by e-mail (if the Environment sensor notification option is enabled in the e-mail notification page)  
The list of messages is given in the appendix  
System shutdown can be triggered for each notification if this option is enabled. If notification is disabled, the  
Shutdown option cannot be used.  
Export settings to file: Enables exportation ("Download" button) and saving of card configuration information.  
Import settings from file: Enables selection of a configuration file ("Browse" button) and uploading ("Upload" button)  
of card configuration information.  
Security: The user must be identified to access this page.  
Network Management Card – User Manual  
34003991EN/EB  
Page 63/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4.5.4 Log  
The two environment sensor measurements: Temperature and Humidity are recorded at an interval defined by the  
Environment log interval in the System settings page.  
By default, this period is 300 seconds.  
Each measurement is dated and stored in the log of the UPS’s communication card.  
The size of log files is limited by a time indexing system.  
The user can Save the log on his/her workstation at any time, in a CSV format file.  
The user can also Clear the files contained in the card to reset the log.  
Network Management Card – User Manual  
34003991EN/EB  
Page 64/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5 Server protection  
5.1 Set-up of the shutdown parameters  
The protection application : Network Shutdown Module or Netwatch, on protected server boot, subscribes itself  
automatically to notified applications list and sends its essential data:  
IP Address or hostname of the server on which it is installed: So that the card can inform it of power events.  
Time required to shutdown the server (Shutdown Duration, configurable in the "Set-up" menu of each NSM): The  
card takes into account the longest shutdown time of all the Network Shutdown Modules subscribed (This is the  
Shutdown duration of the Shutdown parameters) page to manage UPS shutdowns without affecting any of  
Shutdown Modules connected.  
During normal operation, the protection application periodically checks its connection with the card.  
In case of a major power event, the card sends information to the protection application which reacts according to the  
situation. (shutdown order, programmed actions, messages to the administrator and to users via the network)  
When the server shuts down, the protection application unsubscribes itself from the notified applications.  
5.1.1 Shutdown criteria managed by the Network Management Card  
During an extended power failure, three criteria may cause the server shutdown procedure to be initiated. If several  
criteria are selected, (See page Shutdown parameters), the first criterion encountered will launch the shutdown  
procedure.  
At the end of the shutdown procedure, when all servers have been shut down, the UPS may shut down to avoid  
unnecessary discharge of its batteries, depending on its configuration.  
Network Management Card – User Manual  
34003991EN/EB  
Page 65/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Utility failure  
UPS Shut off  
Start of the shutdown sequence  
Shutdown after :  
Battery  
capacity  
Delay before  
shutdown  
100%  
Remaining autonomy  
If remaining time under  
Shutdown if  
remainig  
Shutdown duration  
capacity under  
t
0%  
Card parameters  
UPS parameters  
5.1.1.1 Backup time before initiating the shutdown procedure  
(Shutdown After – Shutdown Timer)  
When the UPS switches to battery, the Network Management Card starts the Shutdown Timer countdown and launches  
the system shutdown procedure at the end of the countdown.  
This value must be chosen so that users have time to complete their tasks and disconnect, without exceeding battery  
backup time.  
Note 1:  
The Network Shutdown Module can also manage its own Shutdown Timer (configurable in the Shutdown Module"set-  
up" menu of each Network Shutdown Module) launched when the UPS switches to battery.  
Note that if this criterion is selected to initiate system shutdown, automatic system reboot when power is restored is  
not guaranteed (e.g. power restoration if only this system was shut down).  
5.1.1.2 Initiating the shutdown procedure when the battery level is lower than:  
(If Capacity under)  
When the card detects that the remaining backup time percentage is less than the configured level, the shutdown  
sequence is started.  
By default, this value is set at 20%.  
Note:  
The UPS already manages an equivalent parameter for the end of backup pre-alarm.  
The card does not accept values less than that programmed in the UPS.  
Check the UPS documentation.  
Network Management Card – User Manual  
34003991EN/EB  
Page 66/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.1.1.3 Shutdown when backup time is less than  
When the Network Management Card detects that the percentage of backup time remaining is less than the value set,  
the shutdown sequence is started.  
5.1.1.4 Shutdown duration  
Duration (in seconds) required for the system protected by the protection application to shut down.  
The protection application transmit their own "Shutdown duration" to the Network Management Card.  
Based on these values (maximum Shutdown duration of all subscribed customer systems) that the card will send to  
the delayed shutdown order to the UPS.  
Network Management Card – User Manual  
34003991EN/EB  
Page 67/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.1.2 Controlled outlets  
Certain UPS models are equipped with controlled outlets (generally 2) which are always dependant on the UPS's main  
outlet.  
Shutdown of the main outlet systematically causes shutdown of the programmable outlets.  
The following notations are used to identify these outlets:  
Main outlet:  
Main  
Controlled outlet 1  
Controlled outlet 2  
1
2
Start shutdown main  
output  
Start shutdown  
outlet 1  
Utility failure  
Utility restore  
Utility  
Main output  
Shutdown duration  
main output  
Outlet 1  
Shutdown  
duration outlet  
1
Shutdown duration 1  
NSM 1 on main  
output  
Shutdown  
duration 2  
NSM 2 on outlet 1  
Shutdown after:  
Shutdown duration 3  
NSM 3 on main  
output  
5.1.3 Protection of a server connected to a controlled outlet  
Network Shutdown Modules (NSM) starting with version 3.0 are compatible with the controlled outlets.  
After connecting the server electrically to one of the controlled outlets, the NSM must be informed of the outlet number  
to which it is connected.  
Refer to the documentation of the NSM available on the internet site www.mgeops.com section “Downloads – Software  
Download.  
5.1.3.1 Load shedding or sequential shutdown  
It is possible to optimise backup time by shutting down non-priority equipment or sequencing the shutdown of several  
devices.  
Two shutdown criteria are possible:  
Shutdown of outlets after a set battery back-up time (After)  
Shutdown of outlets at a given battery discharge level (if battery capacity under)  
It is possible to specify values for both criteria. The first criterion reached will initiate server shutdown.  
Network Management Card – User Manual  
34003991EN/EB  
Page 68/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.1.3.2 Sequential startup  
It is possible to delay outlet power-on to reduce inrush currents on startup or to sequence the startup of several  
devices.  
Controlled outlet startup after a given time is based on startup of the main outlet.  
5.2 The different server and UPS shutdown sequences  
5.2.1 Extended power outage, shutdown initiated by the Shutdown Timer  
(Shutdown after)  
During battery backup time, the Shutdown Timer of the Network Management Card is reached: After a user-defined  
backup time period (Shutdown parameters page), the shutdown of all servers is initiated, followed by the UPS  
shutdown (depending on its configuration). The UPS restarts when utility power is restored (depending on its  
configuration)  
Shutdown duration: Maximum value of shutdown times of protection application subscribed to the card. This value is  
updated each time a client subscribes/ unsubscribes.  
Start shutdown main  
Start shutdown  
Utility failure  
Utility restore  
output  
output 1  
Utility  
Main output  
Shutdown duration  
main output  
Shutdown after:  
NSM 1 on main  
output  
Shutdown after 1:  
Output 1  
Shutdown  
duration output 1  
NSM 2 on output 1  
5.2.2 Extended power outage, shutdown initiated by the "Low battery power"  
message  
When the "Low battery power" criterion is displayed, the UPS is shut off after taking into account the shutdown  
duration of the servers.  
"Low battery power": The message appears if either of the two following criteria is checked:  
- Low Battery Level  
- Low Battery Delay  
Network Management Card – User Manual  
34003991EN/EB  
Page 69/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start shutdown main  
output  
Start shutdown  
output 1  
Utility failure  
Utility restore  
Utility  
Shutdown duration  
Main output  
Battery capacity  
under:  
NSM 1 on main  
output  
Shutdown  
duration output 1  
Output 1  
Battery capacity  
under: (output 1)  
NSM 2 on output 1  
5.2.3 Case of power restoration before the end of the "shutdown duration"  
counter  
If power is restored before the end of the Shutdown Duration, the UPS is shut off after the Shutdown Duration for a  
time equal to the forced reboot delay (10 seconds)  
Start shutdown main  
Start shutdown  
Utility failure  
Utility restore  
output  
output 1  
Utility  
Shutdown  
duration  
Forced Reboot  
Main output  
Battery capacity under  
:
NSM 1 on main  
output  
Shutdown  
duration output 1  
Output 1  
Battery capacity  
under: (output 1)  
NSM 2 on output 1  
Network Management Card – User Manual  
34003991EN/EB  
Page 70/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5.3 Shutdown management with 2 NMC boards  
Certain UPS can have 2 NMC boards in order to:  
Increase the number of protected servers,  
Protect 2 groups of server connected to different networks physically separated.  
5.3.1 Shutdown Duration  
As described in the 5.1.1.4 paragraph, The protection application transmit their own "Shutdown duration" to the  
Network Management Card. Based on these values (maximum Shutdown duration of all subscribed customer systems)  
that the card will send to the delayed shutdown order to the UPS.  
If the UPS have two NMC cards, the maximum shutdown duration of the two groups of protected systems will be used  
for the delayed shutdown order.  
Example: If the subscribed customers of the first NMC card have a maximum Shutdown duration of 60s and the ones  
of the second NMC card of 120s, the servers shutdown will be launched 120s before the UPS shutoff..  
5.3.2 Settings  
Set-up shutdown parameters to the same values on the 2 cards is highly recommended (for the main output and the  
controlled outlets).  
If the settings are not the same, the first criteria reached on one the 2 cards will launch the secure shutdown of all  
servers  
Please, note that in any case the shutdown of the protected servers will be executed safely.  
Network Management Card – User Manual  
34003991EN/EB  
Page 71/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6 Configuration via RS232  
Use the cord supplied with the card.  
Connect the card to a computer equipped with a hyperterminal type emulator. The serial link must be set at 9600  
baud, 8 bits, no parity, 1 stop bit, and without flow control.  
Check that UPS power is on.  
Enter the admin password (not modifiable).  
The menu is in English only.  
-----------------------------------------------------------------------------  
EATON  
NETWORK MANAGEMENT CARD  
-----------------------------------------------------------------------------  
1 : Reset  
2 : Network configuration  
3 : Set Login Password to Default  
4 : Return to Default Configuration  
0 : Exit  
-----------------------------------------------------------------------------  
Network Management Card – User Manual  
34003991EN/EB  
Page 72/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.1 Choice 1: Restart / Reset  
Use this function to restart the card; two choices are possible  
1 : Hardware Reset: Equivalent to a restart of the electrical power supply.  
2 : Restart application: Restarts only the application part.  
-----------------------------------------------------------------------------  
Reset  
-----------------------------------------------------------------------------  
1 : Hardware Reset  
2 : Restart application  
0 : Exit  
-----------------------------------------------------------------------------  
6.2 Choice 2: Network Configuration  
Use this function to access network settings.  
-----------------------------------------------------------------------------  
Network settings  
-----------------------------------------------------------------------------  
1 : Read Network settings  
2 : Modify Network settings  
3 : Set Ethernet speed  
0 : Exit  
-----------------------------------------------------------------------------  
6.2.1 Choice 1: Read Network settings  
Enables reading of the card's routine settings  
Network configuration :  
MAC address : 00:20:85:FD:1C:07  
Mode : Static IP  
IP address : 166.99.18.129  
Subnet mask : 255.255.248.0  
Gateway : 166.99.17.1  
Network Management Card – User Manual  
34003991EN/EB  
Page 73/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.2.2 Choice 2: Modify Network settings  
Enables the modification of network parameters  
For each of the following questions, you can press <Return> to select the value  
shown in braces, or you can enter a new value.  
Should this target obtain IP settings from the network?[N]  
Static IP address [166.99.18.129]?  
Subnet Mask IP address [255.255.248.0]?  
Gateway address IP address [166.99.17.1]?  
Wait during your new configuration is saved ...  
Reset the card to take into account the new configuration.  
In DHCP mode, the card can receive the following parameters according to the DHCP server settings  
IP address  
Subnet Mask  
Gateway address  
Primary DNS server  
Secondary DNS server  
The card must be restarted in order for the new parameters to be taken into account.  
6.2.3 Choice 3: Set Ethernet speed  
Enables the modification of the network speed  
Set the Ethernet speed : [1 : Automatic, 2 : 10 MBit]  
1
New Ethernet speed : Automatic  
Wait during the new setting is saved ...  
Reset the card to take into account the new configuration.  
The card must be restarted in order for the new parameters to be taken into account.  
Network Management Card – User Manual  
34003991EN/EB  
Page 74/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.3 Choice 3: Lost password / Set Login Password to Default  
In the even the login or password is lost, choice 3 enables the return to the default password:  
-----------------------------------------------------------------------------  
EATON  
NETWORK MANAGEMENT CARD  
-----------------------------------------------------------------------------  
1 : Reset  
2 : Network configuration  
3 : Set Login Password to Default  
4 : Return to Default Configuration  
0 : Exit  
-----------------------------------------------------------------------------  
Wait during Login Password return to default ...  
Wait for the confirmation message.  
Login Password are succefully been set.  
The card is now accessible via the Web with the password admin.  
The card must be restarted in order for the new parameters to be taken into account.  
Network Management Card – User Manual  
34003991EN/EB  
Page 75/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6.4 Choice 4: Return to Default Configuration  
Enables restoration of the default configuration of all the card’s parameters  
-----------------------------------------------------------------------------  
EATON  
NETWORK MANAGEMENT CARD  
-----------------------------------------------------------------------------  
1 : Reset  
2 : Network configuration  
3 : Set Login Password to Default  
4 : Return to Default Configuration  
0 : Exit  
-----------------------------------------------------------------------------  
Wait during configuration returns to default ...  
Wait for the confirmation message.  
Configuration has been set to default one.  
You must Reset the card.  
The card must be restarted in order for the new parameters to be taken into account.  
Network Management Card – User Manual  
34003991EN/EB  
Page 76/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7 Industrial Network Management Card (INMC option)  
7.1 Presentation  
7.1.1 Overview  
7.1.2 Functions  
The Industrial Network Management Card (INMC) provides the same functions than the NMC card described in the  
previous section of this document.  
The adding function consists to provide UPS (Uninterruptible Power Supply) data (states and measures) to be sent a  
computer system.  
The JBUS hexadecimal (MODBUS RTU) communication protocol is used in slave mode. The system provides a  
communication channel with an RS485 or RS232 interface.  
Note:  
2 wires or 4 wires RS485 link are available.  
Warning:  
RS232 and RS485 communication ports cannot be used together.  
JBUS/MODBUS communication is operational 2 minutes after the startup of the card.  
Network Management Card – User Manual  
34003991EN/EB  
Page 77/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.1.3 Technical characteristics  
Functions  
Parameters  
Default values  
- 9600 bauds  
- without parity  
- Slave nr 1  
Possible values  
JBUS/MODBUS  
communication  
- Baud rate  
- 1200, 2400, 4800, 9600  
- Without parity, even parity  
- 1 to FF (hexadecimal)  
- Rx on pin 1  
- Parity  
- Slave number  
- Link connection in  
transmit  
RS232 link  
- Rx on pin 1  
- Tx on pin 3  
- Tx on pin 3  
data (Tx) or receive data  
(Rx)  
RS485 link  
- Termination  
- No termination  
- With or without (2 or 4  
wires)  
Network Management Card – User Manual  
34003991EN/EB  
Page 78/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2 Installation  
7.2.1 RS232 link configuration and connection  
Set the SA2 switches like below:  
The next figure shows the details of the connection in RS232 mode:  
Network Management Card – User Manual  
34003991EN/EB  
Page 79/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2.2 RS485 link configuration and connection  
7.2.2.1 RS485 connection  
The EIA RS485 link, 2 wires or 4 wires, must be polarized at a unique point of the link and must be adapted at both  
ends for a good working.  
Normally, the master of the network sets the polarity of the line. The INMC card is a slave equipment and don’t have  
polarisation resistor.  
The two ends of the line must be terminated. Allow for 1 or 2 terminators to avoid mismatching the line when any  
equipment at the end of the line is disconnected.  
The next figure gives the detail of the RS485 connector and the internals drivers:  
Pin number  
Function  
1
2
3
4
5
R- : Receiver - (input)  
R+ : Receiver + (input)  
T- : Transmitter - (output)  
T+ : Transmitter + (output)  
0 V  
Important notes:  
Use twisted pair cable (cable specification 0.3mm2 and capacitance 42pF/m)  
The transmission range will increase if a cable with lower capacitance and larger diameter is used.  
Use shielded cable in heavy industrial environments.  
Network Management Card – User Manual  
34003991EN/EB  
Page 80/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The settings of the RS485 link are made through the SA1 switches:  
SA1 description:  
1: reserved  
2: reserved  
3: link termination between T- to R- (2 wires configuration) if set to ON  
4: connection T- to R- (2 wires configuration) if set to ON  
5: connection T+ to R+ (2 wires configuration) if set to ON  
6: reserved  
7: reserved  
8: link termination between R+ and R- if set to ON  
Network Management Card – User Manual  
34003991EN/EB  
Page 81/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2.2.2 RS485 link configuration for 2 wires connexion  
Set the SA2 switches like below to set the RS485 mode:  
Set the SA1 switches to select the two wires configuration with no termination:  
Network Management Card – User Manual  
34003991EN/EB  
Page 82/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Set the SA1 switches to select the two wires configuration with termination:  
The next figure gives a typical bus structure in the two wires configuration:  
Network Management Card – User Manual  
34003991EN/EB  
Page 83/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2.2.3 RS485 link configuration for 4 wires connexion  
Set the SA2 switches like below:  
Set the SA1 switches to select the four wires configuration with no termination:  
Network Management Card – User Manual  
34003991EN/EB  
Page 84/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Set the SA1 switches to select the four wires configuration with termination:  
The next figure gives a typical bus structure in the four wires configuration:  
Network Management Card – User Manual  
34003991EN/EB  
Page 85/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2.3 Configuration of the JBUS/MODBUS communication parameters  
Connect the RS232 link  
to a terminal  
(Microsoft Hyper  
Use the cord supplied with the card.  
Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600  
baud,  
8 bits, no parity, 1 stop bit, and without flow control.  
Check that UPS power is on.  
Enter the admin password (not modifiable).  
Network Management Card – User Manual  
34003991EN/EB  
Page 86/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The next menu appears:  
-----------------------------------------------------------------------------  
EATON  
NETWORK MANAGEMENT CARD  
-----------------------------------------------------------------------------  
1 : Reset  
2 : Network configuration  
3 : Set Login Password to Default  
4 : Return to Default Configuration  
5 : Jbus configuration  
6 : Sensor configuration  
0 : Exit  
-----------------------------------------------------------------------------  
Type 5 and return to display the JBUS configuration menu.  
The next menu appears:  
-----------------------------------------------------------------------------  
Jbus settings  
-----------------------------------------------------------------------------  
1 : Display Jbus settings  
2 : Modify Jbus settings  
3 : Display Jbus diagnostics  
4 : Reset Jbus diagnostics  
5 : Return to Jbus Default Configuration  
6 : Display Jbus frames  
0 : Exit  
-----------------------------------------------------------------------------  
7.2.3.1 Choice 1: Display Jbus settings  
Enables reading of the card's Jbus settings  
Jbus configuration :  
Slave number : 7  
Speed : 9600 bds  
Data : 8 bits  
stop bit : 1  
Parity : None  
7.2.3.2 Choice 2: Modify Jbus settings  
Enables the modification of Jbus settings.  
Network Management Card – User Manual  
34003991EN/EB  
Page 87/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Setting Jbus configuration :  
Set Slave number : 0x7  
Set the Baud Rate [1: 38400, 2: 19200, 3: 9600, 4: 4800, 5: 2400, 6: 1200] :3  
Set data format [1: 8 bits, 2: 7 bits] :1  
Set stop bit [1: 1 bits, 2: 2 bits] :1  
Set Parity [1: None, 2: Even, 3: Odd] :1  
Wait during the new setting is saved ...  
TLS/ Slave JBUS initialized  
The Jbus configuration is now updated.  
7.2.3.3 Choice 3: Display Jbus diagnostics  
Enables reading of the Jbus diagnostics.  
Jbus diagnostics :  
Cpt1 - Bus Message Count:0  
Cpt2 - CRC Error Count :0  
Cpt3 - Slave Exception Error Count:0  
Cpt4 - Slave Message Count:0  
Cpt5 - Slave No Response Count:0  
Cpt6 - Slave NAK Count:0  
Cpt7 - Slave Busy Count:0  
Cpt8 - Bus Caracter Overrun Count:0  
Cpt9 - Slave Correct Response Count:0  
7.2.3.4 Choice 4: Reset Jbus diagnostics  
Reset the Jbus diagnostic counters.  
7.2.3.5 Choice 5: Return to Jbus Default Configuration  
Returns to the Jbus default configuration (0x01, 9600, 8, 1, none)  
Wait during Jbus configuration returns to default ...  
Jbus Configuration has been set to default one.  
Network Management Card – User Manual  
34003991EN/EB  
Page 88/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.2.3.6 Choice 6: Display Jbus frames  
Enables the display of the Jbus frames:  
Recv : 01 01 00 00 00 64 3d e1  
Send : 01 81 02 c1 91  
Recv : 01 03 00 62 00 64 e5 ff  
Send : 01 03 c8 00 00 00 00 00 00 00 00 00 00 00 00 00 ...  
Recv : 01 01 00 00 00 64 3d e1  
Send : 01 81 02 c1 91  
Recv : 01 03 00 62 00 64 e5 ff  
Send : 01 03 c8 00 00 00 00 00 00 00 00 00 00 00 00 00 ...  
Network Management Card – User Manual  
34003991EN/EB  
Page 89/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.3 Additional Web pages  
The INMC card Jbus parameters could be set through the next page:  
Network Management Card – User Manual  
34003991EN/EB  
Page 90/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4 JBUS table  
7.4.1 Data for Pulsar 700 / 1000 / 1500  
7.4.1.1 Status table  
Status description  
Load protected  
Status to 0  
Status to 1  
yes  
Word (hex)  
Bit  
0
no  
40  
40  
40  
40  
40  
40  
40  
40  
40  
40  
40  
40  
42  
44  
44  
46  
49  
UPS coupled  
no  
yes  
1
Unit general alarm  
UPS in backup  
no  
yes  
2
no  
yes  
4
Battery low warning  
Low battery  
no  
yes  
5
no  
yes  
6
Operation on static switch  
Communication fault  
UPS overload  
no  
yes  
7
absent  
no  
present  
yes  
9
A
B
D
E
0
Emergency stop  
absent  
no  
present  
yes  
Battery to be checked  
Device ventilation fault  
Battery present  
no  
yes  
absent  
no  
present  
yes  
Mains 1 voltage out of tolerance  
Mains 1 frequency out of tolerance  
Bypass status  
8
no  
yes  
B
7
no  
yes  
Charger general fault  
no  
yes  
0
not in  
charge  
no  
Battery charge  
in charge  
49  
1 & 3  
Converter fault  
Inverter fault  
yes  
yes  
4A  
4C  
1
1
no  
Network Management Card – User Manual  
34003991EN/EB  
Page 91/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.1.2 Measurements table  
Description of the physical quantity  
Word (hex)  
109  
Unit  
A
I output  
U output  
124  
V
U battery  
12D  
136  
V
Output active power  
Output apparent power  
% output load level  
Power factor (Cos PHI)  
Mains 1 frequency  
Output frequency  
Battery backup time  
Battery charging level  
U mains 1  
W
VA  
%
137  
139  
13D  
13E  
-
Hz  
Hz  
Min  
%
141  
149  
14B  
150  
V
Nominal voltage of battery element  
213  
V
Network Management Card – User Manual  
34003991EN/EB  
Page 92/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.2 Data for Pulsar M 2200 / 3000  
7.4.2.1 Status table  
Status description  
Status to 0  
no  
Status to 1  
yes  
Word (hex)  
40  
Bit  
0
Load protected  
UPS coupled  
no  
yes  
40  
1
Unit general alarm  
no  
yes  
40  
2
UPS in backup  
no  
yes  
40  
4
Battery low warning  
Low battery  
no  
yes  
40  
5
no  
yes  
40  
6
Operation on static switch  
Communication fault  
UPS overload  
no  
yes  
40  
7
absent  
no  
present  
yes  
40  
9
40  
A
B
D
E
6
Emergency stop  
absent  
no  
present  
yes  
40  
Battery to be checked  
Device ventilation fault  
Manual bypass switch (Q3BP)  
Battery present  
40  
no  
yes  
40  
open  
absent  
no  
closed  
present  
yes  
41  
42  
0
Mains 1 voltage out of tolerance  
Mains 1 frequency out of tolerance  
Redundancy lost  
44  
8
no  
yes  
44  
B
7
no  
yes  
45  
Maintenance position  
Mains 2 overload  
no  
yes  
46  
1
no  
yes  
46  
5
Output on bypass  
no  
yes  
46  
7
Mains 2 frequency out of tolerance  
Mains 2 voltage out of tolerance  
Phase M2 out of tolerance  
Charger general fault  
Battery charge  
no  
yes  
46  
9
no  
yes  
46  
A
B
0
no  
yes  
46  
no  
yes  
49  
no  
yes  
49  
1 & 3  
1
Converter fault  
no  
yes  
4A  
4C  
Inverter major fault  
no  
yes  
1
Network Management Card – User Manual  
34003991EN/EB  
Page 93/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.2.2 Measurements table  
Description of the physical quantity  
Word (hex)  
106  
Unit  
A
I mains 2  
I output  
109  
A
U mains 2  
11E  
124  
V
U output  
V
U battery  
12D  
136  
V
Output active power  
Output apparent power  
% output load level  
Power factor x 100  
Mains 1 frequency  
Output frequency  
Battery backup time  
Battery charging level  
U mains 1  
W
VA  
%
137  
139  
13D  
13E  
141  
-
dHz  
dHz  
Min  
%
149  
14B  
150  
V
Nominal voltage of battery element  
213  
V
Network Management Card – User Manual  
34003991EN/EB  
Page 94/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.3 Data for Pulsar MX 4000 / 5000 / 10000 and EX 5 / 7 / 11 RT  
7.4.3.1 Status table  
Status description  
Status to 0  
no  
Status to 1  
yes  
Word (hex)  
40  
Bit  
0
Load protected  
UPS coupled  
no  
yes  
40  
1
Unit general alarm  
no  
yes  
40  
2
UPS in backup  
no  
yes  
40  
4
Battery low warning  
Low battery  
no  
yes  
40  
5
no  
yes  
40  
6
Operation on static switch  
Communication fault  
UPS overload  
no  
yes  
40  
7
absent  
no  
present  
yes  
40  
9
40  
A
B
D
E
6
Emergency stop  
absent  
no  
present  
yes  
40  
Battery to be checked  
Device ventilation fault  
Manual bypass switch (Q3BP)  
UPS in “eco” mode  
Battery present  
40  
no  
yes  
40  
open  
no  
closed  
yes  
41  
41  
7
absent  
no  
present  
yes  
42  
0
Mains 1 voltage out of tolerance  
Mains 1 fuse fault  
44  
8
no  
yes  
44  
9
Mains 1 frequency out of tolerance  
Redundancy lost  
no  
yes  
44  
B
7
no  
yes  
45  
Maintenance position  
Mains 2 overload  
no  
yes  
46  
1
no  
yes  
46  
5
Mains 2 thermal overload  
Output on bypass  
no  
yes  
46  
6
no  
yes  
46  
7
Mains 2 frequency out of tolerance  
Mains 2 voltage out of tolerance  
Phase M2 out of tolerance  
Mains 2 internal fault  
Charger general fault  
Battery charge  
no  
yes  
46  
9
no  
yes  
46  
A
B
2
no  
yes  
46  
absent  
no  
present  
yes  
47  
49  
0
no  
yes  
49  
1 & 3  
1
Converter fault  
no  
yes  
4A  
4C  
4C  
4C  
4C  
4C  
Inverter major fault  
Inverter overload  
no  
yes  
1
no  
yes  
2
Inverter thermal overload  
Inverter limitation  
no  
yes  
3
no  
yes  
4
UPS fuse fault  
absent  
present  
5
Network Management Card – User Manual  
34003991EN/EB  
Page 95/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.3.2 Measurements table  
Description of the physical quantity  
Word (hex)  
100  
Unit  
A
I mains 1  
I mains 2  
106  
A
I output  
109  
A
I battery  
10E  
11E  
124  
A
U mains 2  
V
U output  
V
U battery  
12D  
136  
V
Output active power  
Output apparent power  
% output load level  
Power factor (Cos PHI)  
Mains 1 frequency  
Mains 2 frequency  
Output frequency  
Battery backup time  
Battery charging level  
U mains 1  
W
137  
VA  
%
139  
13D  
13E  
140  
-
dHz  
dHz  
dHz  
Min  
%
141  
149  
14B  
150  
V
Nominal voltage of battery element  
213  
V
Network Management Card – User Manual  
34003991EN/EB  
Page 96/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.4 Data for Pulsar MX frame 15 / 20  
7.4.4.1 Status table  
Status description  
Status to 0  
no  
Status to 1  
yes  
Word (hex)  
40  
Bit  
0
Load protected  
UPS coupled  
no  
yes  
40  
1
Unit general alarm  
no  
yes  
40  
2
UPS in backup  
no  
yes  
40  
4
Battery low warning  
Low battery  
no  
yes  
40  
5
no  
yes  
40  
6
Operation on static switch  
Communication fault  
UPS overload  
no  
yes  
40  
7
absent  
no  
present  
yes  
40  
9
40  
A
B
D
E
6
Emergency stop  
absent  
no  
present  
yes  
40  
Battery to be checked  
Device ventilation fault  
Manual bypass switch (Q3BP)  
Battery present  
40  
no  
yes  
40  
open  
absent  
no  
closed  
present  
yes  
41  
42  
0
Mains 1 voltage out of tolerance  
Mains 1 fuse fault  
44  
8
no  
yes  
44  
9
Mains 1 frequency out of tolerance  
Redundancy lost  
no  
yes  
44  
B
7
no  
yes  
45  
Maintenance position  
Mains 2 overload  
no  
yes  
46  
1
no  
yes  
46  
5
Mains 2 thermal overload  
Output on bypass  
no  
yes  
46  
6
no  
yes  
46  
7
Mains 2 frequency out of tolerance  
Mains 2 voltage out of tolerance  
Phase M2 out of tolerance  
Mains 2 internal fault  
Charger general fault  
Battery charge  
no  
yes  
46  
9
no  
yes  
46  
A
B
2
no  
yes  
46  
absent  
no  
present  
yes  
47  
49  
0
no  
yes  
49  
1 & 3  
1
Inverter major fault  
Inverter overload  
no  
yes  
4C  
4C  
4C  
4C  
4C  
no  
yes  
2
Inverter thermal overload  
Inverter limitation  
no  
yes  
3
no  
yes  
4
UPS fuse fault  
absent  
present  
5
Network Management Card – User Manual  
34003991EN/EB  
Page 97/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.4.2 Modular fault table  
Description du Status  
Status to 0  
Status to 1  
Word  
(hex)  
61  
Bit  
Module 1  
Module 2  
Module 3  
Module 4  
General alarm  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Present  
Present  
Present  
Present  
Present  
Present  
Present  
0
1
2
3
4
5
6
Fan failure  
61  
Internal communication fault  
Inverter thermal overload  
Inverter fault  
61  
61  
61  
Inverter fuse blown  
Load short circuit  
61  
61  
General alarm  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Present  
Present  
Present  
Present  
Present  
Present  
Present  
62  
62  
62  
62  
62  
62  
62  
0
1
2
3
4
5
6
Fan failure  
Internal communication fault  
Inverter thermal overload  
Inverter fault  
Inverter fuse blown  
Load short circuit  
General alarm  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Present  
Present  
Present  
Present  
Present  
Present  
Present  
63  
63  
63  
63  
63  
63  
63  
0
1
2
3
4
5
6
Fan failure  
Internal communication fault  
Inverter thermal overload  
Inverter fault  
Inverter fuse blown  
Load short circuit  
General alarm  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Present  
Present  
Present  
Present  
Present  
Present  
Present  
64  
64  
64  
64  
64  
64  
64  
0
1
2
3
4
5
6
Fan failure  
Internal communication fault  
Inverter thermal overload  
Inverter fault  
Inverter fuse blown  
Load short circuit  
Network Management Card – User Manual  
34003991EN/EB  
Page 98/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description du Status  
Status to 0  
Status to 1  
Word  
(hex)  
65  
Bit  
Module 5  
Module 6  
Module 7  
Module 8  
General alarm  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Present  
Present  
Present  
Present  
Present  
Present  
Present  
0
1
2
3
4
5
6
Fan failure  
65  
Internal communication fault  
Inverter thermal overload  
Inverter fault  
65  
65  
65  
Inverter fuse blown  
Load short circuit  
65  
65  
General alarm  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Present  
Present  
Present  
Present  
Present  
Present  
Present  
66  
66  
66  
66  
66  
66  
66  
0
1
2
3
4
5
6
Fan failure  
Internal communication fault  
Inverter thermal overload  
Inverter fault  
Inverter fuse blown  
Load short circuit  
General alarm  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Present  
Present  
Present  
Present  
Present  
Present  
Present  
67  
67  
67  
67  
67  
67  
67  
0
1
2
3
4
5
6
Fan failure  
Internal communication fault  
Inverter thermal overload  
Inverter fault  
Inverter fuse blown  
Load short circuit  
General alarm  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Absent  
Present  
Present  
Present  
Present  
Present  
Present  
Present  
68  
68  
68  
68  
68  
68  
68  
0
1
2
3
4
5
6
Fan failure  
Internal communication fault  
Inverter thermal overload  
Inverter fault  
Inverter fuse blown  
Load short circuit  
Network Management Card – User Manual  
34003991EN/EB  
Page 99/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.4.3 Measurements table  
Description of the physical quantity  
Word (hex)  
100  
101  
102  
106  
107  
108  
109  
10A  
10B  
10E  
115  
116  
117  
11E  
11F  
120  
121  
122  
123  
124  
125  
126  
127  
128  
129  
12D  
130  
131  
132  
133  
134  
135  
136  
137  
139  
13A  
13B  
13C  
13D  
13E  
140  
141  
149  
14B  
Unit  
A
I1 (I phase 1) mains 1  
I2 (I phase 2) mains 1  
I3 (I phase 3) mains 1  
I1 (I phase 1) mains 2  
I2 (I phase 2) mains 2  
I3 (I phase 3) mains 2  
I1 (I phase 1) output  
I2 (I phase 2) output  
I3 (I phase 3) output  
I battery  
A
A
A
A
A
A
A
A
A
U12 mains 1  
V
U23 mains 1  
V
U31 mains 1  
V
U mains 2 (phase 1)  
U mains 2 (phase 2)  
U mains 2 (phase 3)  
U12 mains 2  
V
V
V
V
U23 mains 2  
V
U31 mains 2  
V
U1N output  
V
U2N output  
V
U3N output  
V
U12 output  
V
U23 output  
V
U31 output  
V
U battery  
V
Output active power (phase 1)  
Output active power (phase 2)  
Output active power (phase 3)  
Output apparent power (phase 1)  
Output apparent power (phase 2)  
Output apparent power (phase 3)  
Output total active power  
Output total apparent power  
% output load level  
Peak factor phase 1 x 100  
Peak factor phase 2 x 100  
Peak factor phase 3 x 100  
Power factor x 100  
Mains 1 frequency  
Mains 2 frequency  
Output frequency  
W
W
W
VA  
VA  
VA  
W
VA  
%
-
-
-
-
dHz  
dHz  
dHz  
Min  
%
Battery backup time  
Battery charging level  
Network Management Card – User Manual  
34003991EN/EB  
Page 100/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Description of the physical quantity  
U mains 1 (phase 1)  
Word (hex)  
150  
Unit  
V
U mains 1 (phase 2)  
151  
V
U mains 1 (phase 3)  
152  
V
Nominal voltage of battery element  
213  
V
Network Management Card – User Manual  
34003991EN/EB  
Page 101/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.5 Sensor data  
7.4.5.1 Status table  
Status description  
Input 1 alarm  
Status to 0  
no  
Status to 1  
yes  
Word (hex) Bit  
45  
45  
45  
45  
45  
45  
45  
48  
48  
5
6
4
3
2
1
0
0
1
Input 2 alarm  
no  
yes  
Alarm : humidity too low  
Alarm : humidity too high  
Alarm : temperature too low  
Alarm : temperature too high  
Communication fault  
Input 1  
no  
yes  
no  
yes  
no  
yes  
no  
yes  
no  
yes  
open  
open  
close  
close  
Input 2  
Network Management Card – User Manual  
34003991EN/EB  
Page 102/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.5.2 Measurements table  
Description of the physical quantity  
Word (hex)  
180  
Unit  
Temperature measure  
°C / °F  
°C / °F  
Maximum temperature  
181  
Maximum temperature date (MSB) in Unix timestamp  
Maximum temperature date (LSB) in Unix timestamp  
Minimum temperature (°C)  
182  
183  
184  
°C / °F  
Minimum temperature date (MSB) in Unix timestamp  
Minimum temperature date (LSB) in Unix timestamp  
Humidity measure (%)  
185  
186  
187  
%
%
Maximum humidity (%)  
188  
Maximum humidity date (MSB) in Unix timestamp  
Maximum humidity date (LSB) in Unix timestamp  
Minimum humidity (%)  
189  
190  
18B  
192  
%
Minimum humidity date (MSB) in Unix timestamp  
Minimum humidity date (LSB) in Unix timestamp  
Input 1 changing date (MSB) in Unix timestamp  
Input 1 changing date (LSB) in Unix timestamp  
Input 2 changing date (MSB) in Unix timestamp  
Input 2 changing date (LSB) in Unix timestamp  
193  
194  
195  
196  
197  
Network Management Card – User Manual  
34003991EN/EB  
Page 103/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.5.3 Read of the personalization table  
Description  
Word (hex)  
32C  
32D  
32E  
32F  
Unit  
High threshold temperature (°C)  
Low threshold temperature (°C)  
Temperature hysteresis (°C)  
0
0
0
Offset temperature  
0
High threshold humidity (%)  
330  
0
0
0
0
0
2
7
6
1
3
5
4
0
0
Low threshold humidity (%)  
331  
Humidity hysteresis (%)  
332  
Humidity offset  
333  
Inputs call mask – input 1 close notification  
Inputs call mask – input 2 close notification  
Inputs call mask – low humidity notification  
Inputs call mask – high humidity notification  
Inputs call mask – input 1 open notification  
Inputs call mask – input 2 open notification  
Inputs call mask – low temperature notification  
Inputs call mask – high temperature notification  
Input 1 identification  
334  
334  
334  
334  
334  
334  
334  
334  
336  
Input 2 identification  
33A  
Network Management Card – User Manual  
34003991EN/EB  
Page 104/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7.4.6 Other data  
Information description  
Word (hex)  
1A0  
Example  
Manufacturer name  
« MGE Office Protection  
Systems »  
Product name  
UPS model  
1A8  
1B0  
1B8  
« Pulsar »  
« 700 »  
Serial number  
« AN2E49008 »  
Network Management Card – User Manual  
34003991EN/EB  
Page 105/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8 Appendices  
8.1 Tables of alarms and events  
8.1.1 Table of alarms  
List of time dated alarms  
Alarm on  
Alarm off  
Battery fuse blown  
Battery fuse OK  
No Battery  
Battery present  
Battery temperature fault  
Battery charger fault  
Battery temperature OK  
Battery charger OK  
Battery fault  
Battery OK  
MAX charger voltage fault  
MIN charger voltage fault  
Charger temperature fault  
Rectifier fault  
Charger voltage OK  
Charger voltage OK  
Charger temperature OK  
Rectifier OK  
Chopper fault  
Chopper OK  
Normal AC frequency out of tolerance  
Normal AC fuses blown  
Normal AC module fault  
Normal AC voltage out of tolerance  
Normal AC NOK  
Normal AC frequency OK  
Normal AC fuses OK  
Normal AC module OK  
Normal AC voltage OK  
Normal AC OK  
Site wiring fault  
Site wiring OK  
Bypass AC frequency out of tolerance  
Bypass AC phase out of tolerance  
Bypass AC voltage out of tolerance  
Automatic Bypass fault  
Automatic Bypass overload  
Automatic Bypass overtemperature  
Automatic Bypass thermal overload  
Automatic Bypass switch (Q4S) open  
Normal AC switch (Q1) open  
Battery switch (QF1) open  
Manual Bypass switch (Q3BP) closed  
UPS on manual bypass  
Output switch (Q5N) open  
Single wave load fault  
Bypass AC frequency OK  
Bypass AC phase OK  
Bypass AC voltage OK  
Automatic Bypass OK  
Automatic Bypass load OK  
Automatic Bypass temperature OK  
Automatic Bypass load OK  
Automatic Bypass switch (Q4S) closed  
Normal AC switch (Q1) closed  
Battery switch (QF1) closed  
Manual Bypass switch (Q3BP) open  
Output switch (Q5N) closed  
Load OK  
Negative DC bus too high  
Positive DC bus too high  
Negative DC bus too low  
Positive DC bus too low  
Inverter limitation  
Negative DC bus OK  
Positive DC bus OK  
Negative DC bus OK  
Positive DC bus OK  
Inverter end of limitation  
Input fuses OK  
Inverter fuses blown  
Inverter fault  
Inverter OK  
Network Management Card – User Manual  
34003991EN/EB  
Page 106/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter overload  
Inverter load OK  
Inverter over temperature  
Inverter short circuit  
Inverter temperature OK  
Inverter OK  
Inverter thermal overload  
Load not protected - On Automatic Bypass  
Load short circuit  
Inverter load OK  
Load protected - Return from Bypass  
Load OK  
Load not powered  
Load powered  
Protection Lost  
Protection OK  
Emergency button ON  
Emergency button OFF  
Fan fault  
Fan OK  
Redundancy Lost  
Redundancy OK  
Low battery  
Battery OK  
UPS communication failed  
UPS data base not available  
UPS on battery  
UPS communication restored  
UPS data base OK  
UPS on normal AC  
UPS internal fault  
UPS OK  
UPS overload  
UPS returns to normal load  
UPS temperature OK  
UPS overtemperature  
Imminent UPS shutoff  
UPS OK  
<Sensor name>:  
<Sensor name>:  
Temperature is above high threshold xx °C  
<Sensor name>:  
La température est au dessus du seuil haut xx °C  
<Sensor name>:  
Humidity is above high threshold xx %  
<Sensor name>:  
L'humidité est au dessus du seuil haut xx %  
<Sensor name>:  
Temperature is below low threshold xx °C  
<Sensor name>:  
La température est en dessous du seuil bas xx °C  
<Sensor name>:  
Humidity is below low threshold xx %  
<Sensor name>: <Input #1 label> <when closed label>  
<Sensor name>: <Input #1 label> <when open label>  
<Sensor name>: <Input #2 label> <when closed label>  
<Sensor name>: <Input #2 label> <when open label>  
L'humidité est en dessous du seuil bas xx %  
<Sensor name>: <Input #1 label> <when closed label>  
<Sensor name>: <Input #1 label> <when open label>  
<Sensor name>: <Input #2 label> <when closed label>  
<Sensor name>: <Input #2 label> <when open label>  
Network Management Card – User Manual  
34003991EN/EB  
Page 107/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the UPS is modular UPS, for each module:  
Battery fuse blown  
Battery fuse OK  
No Battery  
Battery present  
Battery temperature fault  
Battery charger fault  
Battery temperature OK  
Battery charger OK  
Battery OK  
Low battery  
Charger temperature fault  
MAX charger voltage fault  
MIN charger voltage fault  
Chopper fault  
Charger temperature OK  
Charger voltage OK  
Charger voltage OK  
Chopper OK  
Normal AC fuses blown  
Normal AC module fault  
Inverter fuses blown  
Normal AC fuses OK  
Normal AC module OK  
Input fuses OK  
Inverter fault  
Inverter OK  
Inverter short circuit  
Inverter OK  
Load short circuit  
Load OK  
Rectifier fuse blown  
Rectifier OK  
Rectifier fault  
Rectifier OK  
DC bus unbalanced  
Load OK  
Emergency button ON  
Load not powered  
Emergency button OFF  
Load powered  
UPS internal fault  
UPS OK  
Battery fault  
Battery OK  
Imminent UPS shutoff  
UPS OK  
Normal AC frequency out of tolerance  
Normal AC voltage out of tolerance  
Normal AC switch (Q1) open  
Site wiring fault  
Normal AC frequency OK  
Normal AC voltage OK  
Normal AC switch (Q1) closed  
Site wiring OK  
Automatic Bypass switch (Q4S) open  
Bypass AC frequency out of tolerance  
Automatic Bypass fault  
Automatic Bypass overload  
Automatic Bypass overtemperature  
Automatic Bypass thermal overload  
Bypass AC phase out of tolerance  
Bypass AC voltage out of tolerance  
Load not protected - On Automatic Bypass  
Battery switch (QF1) open  
Manual Bypass switch (Q3BP) closed  
UPS on manual bypass  
Inverter limitation  
Automatic Bypass switch (Q4S) closed  
Bypass AC frequency OK  
Automatic Bypass OK  
Automatic Bypass load OK  
Automatic Bypass temperature OK  
Automatic Bypass load OK  
Bypass AC phase OK  
Bypass AC voltage OK  
Load protected - Return from Bypass  
Battery switch (QF1) closed  
Manual Bypass switch (Q3BP) open  
Inverter end of limitation  
Inverter load OK  
Inverter overload  
Inverter overtemperature  
Inverter thermal overload  
Negative DC bus too high  
Positive DC bus too high  
Negative DC bus too low  
Inverter temperature OK  
Inverter load OK  
Negative DC bus OK  
Positive DC bus OK  
Negative DC bus OK  
Network Management Card – User Manual  
34003991EN/EB  
Page 108/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Positive DC bus too low  
Output switch (Q5N) open  
Normal AC NOK  
Positive DC bus OK  
Output switch (Q5N) closed  
Normal AC OK  
UPS on battery  
UPS on normal AC  
UPS overload  
UPS returns to normal load  
UPS temperature OK  
Fan OK  
UPS overtemperature  
Fan fault  
UPS communication failed  
UPS communication restored  
8.1.2 Table of UPS events  
List of time dated informations  
Alarm on  
Alarm off  
Battery fuse blown  
Battery fuse OK  
Battery temperature fault  
No Battery  
Battery temperature OK  
Battery present  
Battery charger fault  
Battery charger OK  
Charger temperature fault  
MAX charger voltage fault  
MIN charger voltage fault  
End of Warranty  
Charger temperature OK  
Charger voltage OK  
Charger voltage OK  
LCM message OK  
End of battery life  
LCM message OK  
End of life of the wearing parts  
Outlet 1 open  
LCM message OK  
Outlet 1 closed  
Outlet 2 open  
Outlet 2 closed  
Chopper fault  
Chopper OK  
Normal AC switch (Q1) open  
Normal AC frequency out of tolerance  
Normal AC fuses blown  
Normal AC module fault  
Normal AC voltage out of tolerance  
Site wiring fault  
Normal AC switch (Q1) closed  
Normal AC frequency OK  
Normal AC fuses OK  
Normal AC module OK  
Normal AC voltage OK  
Site wiring OK  
Automatic Bypass switch (Q4S) open  
Bypass AC frequency out of tolerance  
Automatic Bypass fault  
Automatic Bypass overload  
Automatic Bypass overtemperature  
Bypass AC phase out of tolerance  
Automatic Bypass thermal overload  
Load not protected - On Automatic Bypass  
Bypass AC voltage out of tolerance  
Battery switch (QF1) open  
Manual Bypass switch (Q3BP) closed  
UPS on manual bypass  
Inverter limitation  
Automatic Bypass switch (Q4S) closed  
Bypass AC frequency OK  
Automatic Bypass OK  
Automatic Bypass load OK  
Automatic Bypass temperature OK  
Bypass AC phase OK  
Automatic Bypass load OK  
Load protected - Return from Bypass  
Bypass AC voltage OK  
Battery switch (QF1) closed  
Manual Bypass switch (Q3BP) open  
Inverter end of limitation  
Input fuses OK  
Inverter fuses blown  
Network Management Card – User Manual  
34003991EN/EB  
Page 109/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inverter fault  
Inverter OK  
Inverter overload  
Inverter load OK  
Inverter temperature OK  
Inverter OK  
Inverter overtemperature  
Inverter short circuit  
Inverter thermal overload  
Output switch (Q5N) open  
Load short circuit  
Single wave load fault  
Negative DC bus too high  
Positive DC bus too high  
Rectifier fault  
Inverter load OK  
Output switch (Q5N) closed  
Load OK  
Load OK  
Negative DC bus OK  
Positive DC bus OK  
Rectifier OK  
Negative DC bus too low  
Positive DC bus too low  
Protection Lost  
Negative DC bus OK  
Positive DC bus OK  
Protection OK  
Redundancy Lost  
Redundancy OK  
Normal AC OK  
Normal AC NOK  
Low battery  
Battery OK  
UPS communication failed  
UPS data base not available  
UPS on battery  
UPS communication restored  
UPS data base OK  
UPS on normal AC  
Emergency button OFF  
Fan OK  
Emergency button ON  
Fan fault  
Load not powered  
UPS internal fault  
Load powered  
UPS OK  
Battery fault  
Battery OK  
UPS overload  
UPS returns to normal load  
UPS temperature OK  
UPS OK  
UPS overtemperature  
Imminent UPS shutoff  
< Sensor Name> : Temperature is above high threshold <Sensor Name> : Temperature is in normal range  
<xx> (°C) or (°F)  
< Sensor Name> : Humidity is above high threshold <xx> <Sensor Name> : Temperature is in normal range  
(%)  
< Sensor Name> : Temperature is below low threshold  
<xx> °C or (°F)  
<Sensor Name> : Temperature is in normal range  
< Sensor Name> : Humidity is below high threshold <xx> <Sensor Name> : Temperature is in normal range  
(%)  
<Sensor name>: <Input #1 label> <when closed label>  
<Sensor name>: <Input #1 label> <when open label>  
<Sensor name>: <Input #2 label> <when closed label>  
<Sensor name>: <Input #2 label> <when open label>>  
Network Management Card – User Manual  
34003991EN/EB  
Page 110/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.1.3 Table of system alarms  
Network Management Card startup  
Send test mail SUCCESS  
Send test mail ERROR  
Send mail to <recipient> ERROR  
<Sensor name> Communication failure  
<Sensor name> Communication restored  
Firmware upgraded  
Connected NSM list Full, last connection refused  
sendTrap()-> Unable to resolve hostname <hostname>  
SNMP Send Trap # <num> failure to <hostname>  
Time changed by user with yyyy/mm/dd hh:mm:ss  
Time synchronized by NSM or EPM with yyyy/mm/dd hh:mm:ss  
Network Management Card – User Manual  
34003991EN/EB  
Page 111/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.2 SNMP objects  
8.2.1 MGE MIB  
The NMC card implement reduce MGE Office Protection Systems MIB, with the objects bellow managed.  
The entire MIB description is available on www.mgeops.com area “Downloads – Software Download.  
Le chemin d’accès à la MIB MGE est 1.3.6.1.4.1.705.1.  
MIB object  
SNMP Format  
String  
Add.path  
{1,1,0}  
upsmgIdentFamilyName  
upsmgIdentModelName  
upsmgIdentFirmwareVersion  
upsmgIdentSerialNumber  
upsmgConfigLowBatteryTime  
upsmgConfigLowBatteryLevel  
upsmgConfigAutoRestart  
upsmgConfigVARating  
upsmgBatteryRemainingTime  
upsmgBatteryLevel  
String  
{1,2,0}  
String  
{1,4,0}  
String  
{1,7,0}  
seconds  
%
{4,7,0}  
{4,8,0}  
1(yes) 2(no)  
VA  
{4,9,0}  
{4,12,0}  
seconds  
%
{5,1,0}  
{5,2,0}  
upsmgBatteryVoltage  
upsmgBatteryCurrent  
upsmgBatteryFaultBattery  
upsmgBatteryReplacement  
upsmgBatteryLowBattery  
upsmgBatteryChargerFault  
upsmgBatteryLowCondition  
upsmgInputPhaseNum  
mginputVoltage_1  
deciVolts  
deciAmps  
1(yes) 2(no)  
1(yes) 2(no)  
1(yes) 2(no)  
1(yes) 2(no)  
1(yes) 2(no)  
{5,5,0}  
{5,6,0}  
{5,9,0}  
{5,11,0}  
{5,14,0}  
{5,15,0}  
{5,16,0}  
{6,1,0}  
DeciVolts  
DeciVolts  
DeciVolts  
DeciHz  
{6,2,1,2,1,0}  
{6,2,1,2,2,0}  
{6,2,1,2,3,0}  
{6,2,1,3,1,0}  
{6,2,1,3,2,0}  
{6,2,1,3,3,0}  
{6,2,1,4,0}  
{6,2,1,5,0}  
{6,2,1,6,1,0}  
{6,2,1,6,2,0}  
{6,2,1,6,3,0}  
{6,3,0}  
mginputVoltage_2  
mginputVoltage_3  
mginputFrequency_1  
mginputFrequency_2  
mginputFrequency_3  
mginputMinimumVoltage  
mginputMaximumVoltage  
mginputCurrent_1  
DeciHz  
DeciHz  
DeciAmps  
DeciAmps  
DeciAmps  
mginputCurrent_2  
mginputCurrent_3  
upsmgInputBadStatus  
upsmgInputLineFailCause  
upsmgOutputPhaseNum  
mgoutputPhaseIndex_1  
mgoutputPhaseIndex_2  
mgoutputPhaseIndex_3  
mgoutputVoltage_1  
{6,4,0}  
{7,1,0}  
{7,2,1,1,1,0}  
{7,2,1,1,2,0}  
{7,2,1,1,3,0}  
{7,2,1,2,1,0}  
{7,2,1,2,2,0}  
{7,2,1,2,3,0}  
deciVolts  
deciVolts  
deciVolts  
mgoutputVoltage_2  
mgoutputVoltage_3  
Network Management Card – User Manual  
34003991EN/EB  
Page 112/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
mgoutputFrequency_1  
mgoutputFrequency_2  
mgoutputFrequency_3  
mgoutputLoadPerPhase_1  
mgoutputLoadPerPhase_2  
mgoutputLoadPerPhase_3  
mgoutputCurrent_1  
deciHz  
{7,2,1,3,1,0}  
{7,2,1,3,2,0}  
{7,2,1,3,3,0}  
{7,2,1,4,1,0}  
{7,2,1,4,2,0}  
{7,2,1,4,3,0}  
{7,2,1,5,1,0}  
{7,2,1,5,2,0}  
{7,2,1,5,3,0}  
{7,3,0}  
deciHz  
deciHz  
%
%
%
deciAmps  
deciAmps  
deciAmps  
1(yes) 2(no)  
1(yes) 2(no)  
1(yes) 2(no)  
1(yes) 2(no)  
1(yes) 2(no)  
1(yes) 2(no)  
mgoutputCurrent_2  
mgoutputCurrent_3  
upsmgOutputOnBattery  
upsmgOutputOnByPass  
upsmgOutputUtilityOff  
upsmgOutputInverterOff  
upsmgOutputOverLoad  
upsmgOutputOverTemp  
upsmgAgentIpAddress  
upsmgAgentSubnetMask  
upsmgAgentDefGateway  
upsmgAgentType  
{7,4,0}  
{7,7,0}  
{7,9,0}  
{7,10,0}  
{7,11,0}  
{12,1,0}  
{12,2,0}  
{12,3,0}  
{12,6,0}  
upsmgAgentMibVersion  
upsmgAgentFirmwareVersion  
upsmgAgentCommUPS  
{12,11,0}  
{12,12,0}  
{12,13,0}  
1(yes) 2(no)  
Network Management Card – User Manual  
34003991EN/EB  
Page 113/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the Environment Sensor is detected , the following information are managed.  
upsmgEnvironAmbientTemp  
upsmgEnvironAmbientHumidity  
upsmgEnvironmentNum  
0.1 degré  
0.1 %  
{8,1,0}  
{8,2,0}  
{8,6,0}  
upsmgEnvironmentIndex  
{8,7,1,1,1 }  
{8,7,1,2,1}  
{8,7,1,3,1}  
{8,7,1,4,1}  
upsmgEnvironmentComFailure  
upsmgEnvironmentTemperature  
1(yes) 2(no)  
0.1 degré  
upsmgEnvironmentTemperatureLo 1(yes) 2(no)  
w
upsmgEnvironmentTemperatureHi 1(yes) 2(no)  
gh  
{8,7,1,5,1}  
upsmgEnvironmentHumidity  
upsmgEnvironmentHumidityLow  
upsmgEnvironmentHumidityHigh  
upsmgEnvironmentInput1State  
upsmgEnvironmentInput2State  
0.1 %  
{8,7,1,6,1}  
{8,7,1,7,1}  
{8,7,1,8,1}  
{8,7,1,9,1}  
{8,7,1,10,1}  
1(yes) 2(no)  
1(yes) 2(no)  
closed(1), open(2)  
closed(1), open(2)  
Network Management Card – User Manual  
34003991EN/EB  
Page 114/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8.2.2 Table des TRAPS : (1.3.6.1.4.1.705.1.11)  
SNMP traps are sent when alarms appears and desappears.  
Level : 1:informational , 2:major, 3:critical  
MIB TRAP  
Trap #  
Level  
-upsmgBatteryFault  
-upsmgBatteryOK  
Trap 1  
Level 3  
Level 1  
Level 3  
Level 1  
Level 3  
Level 1  
Level 2  
Level 1  
Level 2  
Level 1  
Level 2  
Level 1  
Level 3  
Level 1  
Level 3  
Level 1  
Level 2  
Level 3  
Level 3  
Level 1  
Level 2  
Level 2  
Level 2  
Level 2  
Trap 2  
-upsmgAtLowBattery  
-upsmgFromLowBattery  
-upsmgChargerFault  
-upsmgChargerOK  
Trap 5  
Trap 6  
Trap 7  
Trap 8  
-upsmgOnBattery  
Trap 11  
Trap 12  
Trap 13  
Trap 14  
Trap 17  
Trap 18  
Trap 21  
Trap 22  
Trap 23  
Trap 24  
Trap 29  
Trap 31  
Trap 37  
Trap 38  
Trap 65  
Trap 66  
Trap 67  
Trap 68  
-upsmgReturnFromBattery  
-upsmgOnByPass  
-upsmgReturnFromByPass  
-upsmgUtilityFailure  
-upsmgUtilityRestored  
-upsmgOverLoad  
-upsmgLoadOK  
-upsmgOverTemperature  
-upsmgTemperatureOK  
-upsmgOffToStart  
-upsmgOffInProgress  
-upsmgCommunicationFailure  
-upsmgCommunicationRestored  
-upsmgRedundancyLost  
-upsmgRedundancyOK  
-upsmgProtectionLost  
-upsmgProtectionOK  
If the Environment Sensor is detected , the following information are managed.:  
- upsEnvironmentComFailure  
- upsEnvironmentComOK  
Trap 53  
Trap 54  
Trap 55  
Trap 56  
Trap 57  
Trap 58  
Trap 59  
Trap 60  
Trap 61  
Level 2  
Level 2  
Level 2  
Level 2  
Level 2  
Level 2  
Level 2  
Level 2  
Level 2  
- upsEnvironmentTemperatureLow  
- upsEnvironmentTemperatureHigh  
- upsEnvironmentTemperatureOK  
- upsEnvironmentHumidityLow  
- upsEnvironmentHumidityHigh  
- upsEnvironmentHumidityOK  
- upsEnvironmentInput1Closed  
Network Management Card – User Manual  
34003991EN/EB  
Page 115/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
- upsEnvironmentInput1Open  
- upsEnvironmentInput2Open  
- upsEnvironmentInput2Closed  
Trap 62  
Trap 64  
Trap 63  
Level 2  
Level 2  
Level 2  
The level is used to select traps to be sent to the supervisor. This adjustment is available from the “Notified  
applications” page  
Network Management Card – User Manual  
34003991EN/EB  
Page 116/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9 Glossary  
Bootp:  
Protocol based on UDP used to allocate an IP address corresponding to an Ethernet card during the startup phase.  
Defined by the RCF 951  
Community name:  
Access key to access SNMP agent information  
DHCP Dynamic Host Configuration Protocol  
This IETF protocol enables remote, automatic, self-configuration of the IP addresses of a workstation.  
DNS Domain Name Sevicel  
The DNS protocol ensure correspondence between the name of a machine and its IP address  
E-mail  
Electronic means of transmitting messages and/or files.  
Gateway  
Interconnection equipment between networks with different conventions, to enable communication between them  
HTML  
(HyperText Markup Language) Language used to describe hypertext pages on the web.  
HTTPS : is the secure version of HTTP, the communication protocol of the World Wide Web. It was invented by  
Netscape Communications Corporation to provide authentication and encrypted communication and is used in  
electronic commerce.  
IP  
Internet Protocol. Network layer protocol in the TCP/IP stack offering a no-connection inter-network service . The IP  
protocol offers functions for addressing, service type specification, fragmentation and re-assembling and security.  
Defined in RFC 791.  
MIB MANAGEMENT INFORMATION BASE  
- Group of software commands to control and administrate a device through the network. Each type of device (server,  
hub, PC, UPS, etc.) has its own MIB  
NETWORK MANAGEMENT CARD  
Communication cards to supervise UPS and communicate with Network Shutdown Module to insure power protection  
on servers  
NETWORK MANAGEMENT PROXY  
Communication software installed on a PC connected to the UPS to supervise it and communicate with Network  
Shutdown Module to insure power protection on servers  
Network Management Card – User Manual  
34003991EN/EB  
Page 117/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NMS NETWORK MANAGEMENT STATION (SNMP)  
The dedicated PC or workstation is used on the company’s networks to administrate all devices connected to the  
network. Data are transmitted using the SNMP protocol. Popular NMS systems include HP OpenView, IBM Tivoli, CA  
Unicenter, etc.  
NSM : NETWORK SHUTDOWN MODULE  
Protection software installed on a PC or server to protect it  
NTP Network Time Protocol  
Protocol to position a set of machines on a network at the same time.  
Programmable outlet (controlled outlet):  
Outlet that can be remote-switched on or off. UM-Client components enable management of such outlets.  
REBOOT: To restart a system after an interruption.  
– To perform an obstacle-free “reboot”, it is essential that the system is correctly and carefully shut down beforehand.  
– The reboot is usually automatic if the computer is re-supplied with electricity (from the utility or from the UPS).  
RFC  
Request for Comments. All documents defining internal Internet operation.  
SNMP (SIMPLE NETWORK MANAGEMENT PROTOCOL)  
Protocol used to remote-supervise, administrate and control devices connected to a company network.  
SMTP (SIMPLE MAIL TRANSFER PROTOCOL)  
Enables message transfer between e-mail servers or between the client and its server. It is based on the server’s port  
25. It is described in RFC 821  
SSL (Secure Sockets Layers) is a protocol developed by Netscape Communications Corporation for securing data  
transmission in commercial transactions on the Internet. Using public-key cryptography, SSL provides server  
authentication, data encryption, and data integrity for client/server communications  
Subnet mask:  
Mask of bits used to identify and differentiate the network address and the equipment address in an IP address.  
Normally, the mask is automatically determined by the class of address, which defines in a unique manner the network  
part/equipment part division of the IP address.  
- Class A: internet address: 255.0.0.0.  
- Class B: internet address: 255.255.0.0.  
- Class C: internet address: 255.255.255.0.  
TCP/IP  
Transmission Control Protocol/Internet Protocol. Common name of a series of protocols developed by the DOD in the  
US to help build Internet networks throughout the world.  
Trap (SNMP) : This term describes an event that affects an MIB variable. Traps are sent to the manager, which is  
programmed to perform specific tasks upon reception of the traps.  
Network Management Card – User Manual  
34003991EN/EB  
Page 118/118  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Clarion CD Player DB346MP User Manual
Closet Maid Indoor Furnishings UC2DR User Manual
Cornelius Door Door Latch User Manual
Cub Cadet Automobile M466 User Manual
Cuisinart Blender CB 18 User Manual
Cuisinart Blender CSB 44N User Manual
Dynex Paper Shredder DX OP102971 User Manual
Fisher Paykel Oven OB30 User Manual
Fluke Wireless Office Headset 3458 HFL User Manual
Frigidaire Dishwasher 154889301 User Manual