Dynacord Marine Battery DEM 316 Batterie MODULE 24V 38 Ah User Manual

ELA-MODULE-SYSTEM  
OWNER’S MANUAL  
DEM 316 Batterie-MODULE 24 V / 38 Ah  
DEM 317 Batterie-MODULE 24 V / 65 Ah  
Features of the battery modules  
19 “ drawer-type chassis with 3 HU, 4 HU and 2x4 HU  
Rated voltage 24 V  
Energy storage  
completely maintenance-free, universal-location lead batteries with grid plates and fixed electrolyte,  
suitable for cycle operation, continuous battery power supply and trickle charge.  
Exhaustive discharge protection relay controlled by DEM 313 charger  
Charging input and battery outputs via AMP flat pin terminals 6.3 x 0.8 mm  
charging input and all battery outputs fused.  
Temperature tracking of charging voltage at standby charge depending on the battery temperature  
with integrated temperature sensor.  
Batteries with VdS-registration and UL recognition.  
The technical specifications comply with the requirements issued by the “Leistungsgemeinschaft  
Beschallungstechnik”, pertaining to the professional association for audio and video technology in  
the ZVEI.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Emergency power supply of alarm devices  
Alarm devices require 2 independent energy sources, both of which must be able to power the alarm  
device alone. One of the energy sources must be the general mains supply or a similar network in non-stop  
operation. The other must be part of the apparatus (e.g. a battery) or an equivalent network fused  
separately. If the mains power supply is interrupted, the second source of energy must guarantee constant  
non-stop operation automatically and without interruption. If the energy source belonging to the alarm  
device consists of a battery, the user must ensure that the batteries used are suitable for stationary and  
floating operation. The power supply for alarm devices must not be used to supply other apparatus or  
parts. However, electrical equipment which serves to pass on messages may also be powered by the  
said source. An automatic charging device is required to charge and maintain the battery. It must be able  
to charge a battery which is discharged to its discharge voltage up to 80% max. of its rated capacity within  
24 hours. The battery capacity must be sufficient to guarantee the fixed alarm duration at the end of the  
stored energy time. When selecting new batteries, the user should make sure that their capacity is  
sufficient to compensate the capacity loss due to natural ageing of the batteries during the prescribed  
service life.  
2. Commissioning the battery module  
2.1 Battery module DEM 316/DEM 317  
The following points must be observed:  
The battery may only be connected to the charging apparatus without load (i.e. all types of  
consumers must be disconnected) and when the mains is switched OFF.  
The battery must be charged directly after discharging. The battery must not be left uncharged. It  
becomes impossible to maintain a charge if the battery is left uncharged for any length of time.  
Please ensure that the temperature inside the rack is always within the admissible temperature  
range specified in the data sheet.  
2.2 Battery module DEM 317 A and DEM 317 B  
The following points must be observed:  
The insulated screw terminals on the rear side of the battery module DEM 317 are directly  
connected to the battery poles and are live.  
Before removing the insulating caps, all the connections of the battery modules DEM 317A and  
DEM 317B are to be disconnected.  
When connecting the cables, the insulating caps on the battery poles should never be removed at  
the same time because this could cause a short. After the cables have been connected they should  
be replaced immediately.  
The cables between the battery modules DEM 317A and DEM 317B connect the pole B+ with B+,  
M with M and B- with B-. When connecting the cables, the lock washer is to be mounted between  
the cable lug and the nut to secure the screw.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.3 Fusing the inputs and outputs  
The batteries have individually fused outputs for the load connections. Thus all plus and minus lines are  
protected against excess currect and short. Different line cross-sections for consumers with low and high  
current can be connected to a battery at the same time, providing that the fuse values of their individual  
outputs are chosen accordingly. The maximum value of the fuses must not, however, exceed 20 A.  
The total amount of the currents of all the output fuses in a fuse block must not exceed 50 A.  
If the fuse values are changed, the current values printed on the units above the fuse switch are to be  
covered with the enclosed sticky labels. The fuse values for the appropriate plus and minus outputs must  
always be the same.  
If any outputs are not used, the fuses are to be removed and and fuse values above the fuse switches  
are to be covered over with the enclosed blank sticky labels.  
The output secured with 3 A is intended for connection of the control module DEM 207.  
The cross-sections of the lines connected must be correctly dimensioned for the fuse value  
selected. Please note that lines laid in cable channels have a lower permissible current loading due to  
lower heat dissipation.  
The following are guidelines for bundled lines  
Number of lines  
Reduction factor  
2 to 5  
6 to 15  
16 to 30  
0.8  
0.7  
0.5  
Current consumption at Ebat = 24 V  
Module type  
Standby  
-10 dB wert  
rated power  
rated power  
Fuse value  
DEM 287 power amp. 125 W  
DEM 288 power amp. 250 W  
DEM 289 power amp. 400 W  
with NRS 90 144  
10 mA  
10 mA  
10 mA  
2.5 A  
3.5 A  
7 A  
5.7 A  
10.6 A  
19.7 A  
7.5 A  
10 A  
20 A  
Table I Fuse values of the battery outputs for connection of power amplifiers  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table II shows the maximum currents which can be drawn from the batteries. These must not be exceeded.  
This gives the maximum number of power amplifiers which can be powered by the batteries.  
I max  
in A  
max. number of power amplifiers*  
Battery  
type  
DEM 287  
DEM 288  
DEM 289  
DEM 316  
DEM 317  
100  
150  
17  
25  
9
13  
5
7
Table II Maximum currents and number of power amplifiers  
* The number of power amplifiers which can be directly connected to the battery drawers can be lower  
than the values specified in Table II (see number of outputs, section 8, specifications). The values specified  
in the Table only refer to the connection of one amplifier type to one battery type. As long as the maximum  
current drawn is observed, however, various types of amplifier can be supplied by one type of battery.  
Circuit diagram of the battery connection to the charging device.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2.4. BATTERY CONTROL connection  
The battery drawers are equipped with a exhaustive discharge protection which is controlled by the  
monitoring module in the charging device DEM 313. The monitoring circuit checks whether the battery’s  
discharge voltage has been reached when the batteries are discharged. If the battery voltage is less than  
19.5 V, measured at the battery poles, the consumers are disconnected from the battery and the battery  
is thus reliably protected from exhaustive discharge.  
Note!  
If the 15-pole plug connector BATTERY CONTROL has not been correctly connected with  
the charging device, or if the battery voltage is lower than the discharge voltage, the battery  
outputs are not live  
The connection of the temperature sensor for the temperature tracking of the battery voltage takes place  
via contact 5 (+temp) and contact 6 (-temp) of the 15-pole plug connector BATTERY CONTROL to the  
charging device DEM 313. If the connection is faulty, the temperature tracking does not work and the  
battery will not charged. (Also see the operating instructions for the charging device).  
In the case of the battery module DEM 317, the temperature sensor is located in the module DEM 317A.  
2.5 Connection for battery charging  
Connection of the charging device to the battery takes place via the flat pin connector CHARGE  
CURRENT. The plus pole of the charging device is to be connected to the plus pole of the battery, and  
the minus pole of the charging device is to be connected to the minus pole of the battery. (Please also  
see the operating instructions of the charging devices).  
3. Notes for the user  
3.1 Use of the battery is to be avoided in the following locations.  
areas exposed to direct sunlight  
areas with excessive radioactivity, infrared radiation or ultra-violet radiation  
areas with organic solvent vapours, dust, salt or corrosive gases  
areas with abnormal vibration.  
3.2 Regulations for battery use  
Do not throw batteries into the fire. Do not place batteries in the proximity of fires.  
Do not short battery poles.  
Do not tamper with or open batteries.  
If the battery has been damaged and diluted sulphuric acid comes into contact with skin or clothing,  
rinse immediately with plenty of water. If diluted sulphuric acid gets into the eyes, consult a doctor  
immediately.  
Always re-charge a battery after discharging.  
Never use batteries with different capacities, different degree of discharge or a mixture of old and  
new batteries together. The manufacturing dates should be within one month of each other.  
Batteries should be stored at as low a temperature as possible. If batteries are stored at normal  
temperatures, additional charging is necessary once every six months.  
3.3 Storage and additional charging  
During storage the capacity is reduced due to self-discharge. The battery should be stored in a cool, dry  
place.  
If the average monthly temperature is between 20°C and 30°C, one additional charging procedure is  
necessary every 8 months. If the average monthly temperature is less than 20°C, one additional charging  
procedure is necessary every 12 months.  
If a stored battery is used, one charging procedure should always be carried out before use.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3.4 Transport  
If the battery is transported, it should never be exposed to excessive jolting or knocks.  
If a battery is connected to a device during transport, it must be secured well and the current circuit must  
be interuppted.  
3.5 Battery service life  
Generally speaking, the battery service life in standy parallel operation amounts to 3 - 5 years and  
approximately 260 cycles at 100% discharge depth or more in cyclic operation. The actual service life is  
reduced if the appropriate operating conditions are not maintained, (i.e. charging, discharging, working  
temperature and storage).  
We recommend charging the battery at an ambient temperature of between 5°C and 35°C to minimize  
detrimental effects on its service life.  
3.6 Battery recycling  
The batteries are marked with a recycling symbol as illustrated below. At the end of their service life, the  
batteries should be returned to the manufacturer or supplier or taken to a special collection centre so that  
they can be recycled.  
4. Registrations and Standards  
VdS registration  
The batteries have been tested and recognized by the VdS (Verband der Sachversicherer) and  
comply with the following standards:  
DIN 57 510 / VDE 0510 Akkumulatoren und Batterien, ortsfeste Batterien  
DIN 43 534 “Wartungsfreie” verschlossene Akkumulatoren mit festgelegtem Elektrolyt  
DIN 43 539 part 5 Prfungen “wartungsfreie” verschlossene Akkumulatoren mit festgelegtem  
Elektrolyt  
UL approval  
The batteries have received recognition from the Underwriters Laboratories Inc. and have been  
registered under the number MH 15705.  
IATA classification  
The batteries have been cleared by the International Air Transport Association (IATA) for transport  
in aircrafts and have received the classification “leak-proof”.  
5. Testing and inspecting alarm devices  
In order to gurantee that the alarm device is in working condition, qualified personnel must carry out  
inspections and servicing regularly.  
Inspections must be carried out at least once every 3 months at approximately equal intervals to comply  
with DIN VDE 0833 part 1.  
Servicing must be carried out at least once per year, in accordance with the manufacturer’s instructions.  
The annual services may be linked with the quarterly inspections if so desired, meaning that all sections  
of the apparatus are inspected within one year.  
For the battery of an alarm device this means:  
quarterly tests and annual malfunction simulations of the operating duration with the consumers.  
We recommend carrying out the battery capacity test in accordance with DIN 43 539 part 1, whereby the  
battery manufacturer’s instructions are to be observed.  
Please see section 3.2 for instructions on how to treat maintenance-free lead accus.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Explanation of terms:  
Continuous battery power supply  
In this mode, the battery is constantly kept in full charge. It only gives off current if the DC source,  
supplied by the mains, fails.  
Nominal capacity:  
The nominal capacity is the value in ampere-hours for a 20-hour even, uninterrupted discharge  
with I20 up to the discharge voltage of 1.75 V/cell at a temperature of 22°C.  
Capacity:  
The capacity of a battery is the amount of electricity which can be extracted under the conditions  
in question. It depends on the discharge current, the discharge voltage and the temperature.  
Service life  
For batteries in alarm apparatus and emergency announcing systems, the end of a battery’s servive  
life is reached when the capacity is less than 80% of the rated capacity.  
Stored energy time  
This is the time span between recognizing a failure in the mains supply and remedying this  
failure.  
Alarm duration  
The alarm duration is the time during which the alarm signal is given off.  
Emergency announcement duration  
This is the time during which announcements are made to clear the building or section of a  
building.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Specifications battery modules  
Batterie-Module  
DEM 316  
24 V  
DEM 317  
24 V  
Nominal voltage  
Discharge voltage at 25°C (1)  
19,5 V  
19,5 V  
Nominal capacity for 20 hr  
38 Ah  
1.9 A  
65 Ah  
Nominal discharge current I20  
3.25 A  
Capacity for 5 hr (2)  
Capacity for 1 hr (3)  
Capacity for 1 C (4)  
33 Ah  
23 Ah  
20 Ah  
55 Ah  
39 Ah  
33 Ah  
Discharge current for 5 hr (2)  
Discharge current for 1 hr (3)  
Discharge current for 1 hr (4)  
6.6 A  
23 A  
38 A  
11 A  
39 A  
65 A  
Max. discharge current  
100 A  
150 A  
Standby current at mains failurel  
200 mA  
300 mA  
Number of outputs  
14  
21  
Innenwiderstand für 7.5 A Ausgang  
ca.50 mOhm  
27.3 V  
ca. 50 mOhm  
27.3 V  
End-of-charge voltage in standby operation at 20 °C  
(Continuous battery power supply)  
Temperature adaption  
Nominal charging current  
Dimensions (W x D)  
Height  
-40 mV/°C  
4 A  
-40 mV/°C  
4 A  
483 mm x 370 mm  
178 mm  
36.1 kg  
2x178 mm  
30.0 kg (A)  
30.5 kg (B)  
Weight approx.  
(1) Discharge voltage at 25°C: 1.75 V/cell x 12 cells = 21.0 V  
(2) Capacity at 5 hours discharge with discharge current for 5 hr  
(3) Capacity at 1 hour discharge with discharge current for 1 hr  
(4) Capacity at discharge with the current in A corresponding with the nominal capacity in Ah  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Block diagram  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEM 316  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEM 317A  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DEM 317B  
Download from Www.Somanuals.com. All Manuals Search And Download.  
GARANTIE  
WARRANTY  
Das Werk leistet Garantie für alle nachweis-  
baren Material- und Fertigungsfehler für die  
Dauer von 36 Monaten ab Verkauf. Garan-  
tieleistungen werden nur dann anerkannt,  
wenn gültige, d.h. vollständig ausgefüllte  
Garantieunterlagen vorliegen. Von der Ga-  
rantie ausgenommen sind alle Schäden,  
die durch falsche oder unsachgemäße Be-  
dienung verursacht werden. Bei Fremdein-  
griffen oder eigenmächtigen Änderungen  
erlischt jeder Garantieanspruch.  
The factory grants warranty covering all ve-  
rifiable material and manufacturing faults for  
a period of 36 months after purchase. War-  
ranty claims will only be upheld if valid, i.e.  
fully completed warranty forms, are submit-  
ted. This warranty shall not cover damage  
caused by incorrect or improper operation.  
Any claim to warranty shall become null and  
void in the event of modifications to the  
equipment being made by third parties or the  
purchaser himself.  
GmbH Hirschberger Ring 45 94315 Straubing Telefon (09421) 706-0 Telefax (09421) 706-265  
Änderungen vorbehalten. Subject to change without prior notice. Printed in Germany 29. 03. 1999 / 347 030  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Conair Telephone CID110 User Manual
Cooper Lighting Indoor Furnishings VRGC User Manual
Craftsman Lawn Mower 24728901 User Manual
Craftsman Outdoor Cart 61024489 User Manual
Curtis Refrigerator FR1007 User Manual
Danby Microwave Oven DMW7700BLDB User Manual
Delta Electronics Power Supply NE Series User Manual
Electra Accessories Cooktop 230W I User Manual
Fisher Price Video Game Console P8898 User Manual
GE Door 19234 User Manual