MODEL XR200A WIRING DIAGRAM
Refer to the XR200A Installation Guide (LT-0482) for a complete description of wiring connections.
Refer to the XR200 Programming Manual (LT-0196) for complete programming instructions.
CAUTION
Danger of explosion if lithium battery is incorrectly replaced.
Replace only with DMP part number BT-0005 or equivalent
type. When discharged, disposal of used lithium battery is
non- hazardous per USEPA criteria. Disposal according to
local, state, and federal waste regulations.
s
s
DD, MPX
Selection
Form C Relays
J3
Output 1 N/C
Output 1 Com
Output 1 N/O
Output 2 N/C
Output 2 Com
Output 2 N/O
Violet
Gray
Orange
Violet
Gray
J12 J11
Lithium
Battery
Phone Jack Connector
Front Tamper
Tamper Header
J4
AC wiring must be in conduit and exit out the left
side of the enclosure.
Orange
Voltage Outputs
Wiring on terminals
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 9
Output 10
Ground
White/Orange
White/Yellow
White/Green
White/Blue
White/Violet
White/Gray
White
5 through 22 must
exit to the right and
maintain a 1/4"
separation from the
AC and battery
Ground Start Relay
Use Model 305
Rear Tamper
Answering
Machine
Bypass Relay
Use Model 305
K2
K4
positive wiring.
J6
White/Black
Black
Tamper protection
when required for
Model 350A Attack
Resistant Enclosure.
J2
Output Header J2
J2 Output color code for
Model 430 Output Harness
J16
Battery Only Restart CR7
Command
Processor
Reset
K6
1
K7
Relay Output
Use Model 305
Relay Output
Use Model 305
2
Heat detectors,
pull stations, or
any other shorting
devices can be
connected to
Primary Power
16VAC
40 - 100 VA
AC
1
AC
2
+B
-B
4
BELL
5
GND
6
RED
7
YEL
8
GRN
9
BLK
10
SMK
11
GND
12
Z1
13
GND
14
Z2
15
Z3
16
GND
17
Z4
18
Z5
GND
20
Z6
21
Z7
22
GND
23
Z8
24
Z9
+
Z9
26
-
Z10
27
+
Z10
28
-
3
1
9
25
zones 9 and 10.
16 to 18 gauge wire
s
s
Zones 9 and 10 and
Model 715 compatibility
identifier: A
Maximum operating
range:
Maximum AC wire distance
With 16 gauge wire: 70 feet
With 18 guage wire: 40 feet
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
s
Secondary Power Supply
1k
Ω
1k
Ω
1k
Ω
1k
Ω
1k
Ω
1k
Ω
1k
Ω
1k
Ω
1.2 Amps max. charging current.
Use only 12 VDC rechargable
batteries. DMP Model 367.
Replace every 3 to 5 years.
Resistor
DMP Model 309
Resistor
DMP Model 309
8.8 VDC to 14.2 VDC.
3.3k
Ω
3.3k
Ω
Protective
Earth Ground
Auxiliary Power
Total current 1.0 Amps
combined from Terminals
7, 11, 26, & 28.
Bell
Bell
12 VDC nominal
Total current 1.5 Amps max.
s
s
s
s
s
s
= Supervised Circuit
Red
Red
ZONE EXPANDER
Model 715
25mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
Yellow
Green
Keypads
Model 670, 770, and 771
125mA at 8 to 16 VDC.
Black
Model 690
90mA at 8 to 16 VDC.
ZONE EXPANDER
Model 714
ZONE
EXPANDER
Model 711/711E
12mA at
15mAat 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
Model 790 and 791
100mA at 8 to 16 VDC.
s
s
s
s
s
s
DISARM
A R M
s
s
s
s
12 VDC
s
s
s
s
s
s
Model 793
130 mA at 8 to 16 VDC.
3.3k
Ω
3.3k
Ω
3.3k
Ω
3.3k
Ω
s
s
1k
Ω
1k
Ω
1k
Ω
Smoke
1k
Ω
See the XR200A Installation Guide for a
list of approved 2-wire smoke detectors
for zones 9 and 10 and 715 Zone
Expanders.
s
s
Detector
Power
Supervision
Relay
Keyswitch Arming
Can be connected to any loop.
+
Ð
s
s
s
s
1k
Ω
1k
Ω
1k
Ω
s
s
1k
Ω
s
Refer to LT-0164 for a list of approved 4-wire
smoke detectors and power supervision relays.
s
!
1k
Ω
WARNING!
DMP Model 310
Installation to be
performed by
authorized personnel.
In all applications where more than one wire is
under a terminal, the wire must be cut and not
looped around the screw terminal.
ACN 087 480 279
LT-0468 (12/99)
Download from Www.Somanuals.com. All Manuals Search And Download.
|