Carrier Refrigerator 48TCA04 A12 User Manual

48TCA04---A12  
Nominal 3 to 10 Tons  
With Puron® (R---410A) Refrigerant  
Service and Maintenance Instructions  
TABLE OF CONTENTS  
SAFETY CONSIDERATIONS  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1  
UNIT ARRANGEMENT AND ACCESS . . . . . . . . . . . 2  
SUPPLY FAN (BLOWER) SECTION . . . . . . . . . . . . . . 4  
COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
PURONR (R-410A) REFRIGERANT . . . . . . . . . . . . . . 8  
COOLING CHARGING CHARTS . . . . . . . . . . . . . . . . . 9  
CONVENIENCE OUTLETS . . . . . . . . . . . . . . . . . . . . 14  
SMOKE DETECTORS . . . . . . . . . . . . . . . . . . . . . . . . . 15  
PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . . 22  
GAS HEATING SYSTEM . . . . . . . . . . . . . . . . . . . . . . 22  
PREMIERLINKT CONTROL . . . . . . . . . . . . . . . . . . . 34  
RTU-MP CONTROL SYSTEM . . . . . . . . . . . . . . . . . . 42  
ECONOMI$ER SYSTEMS . . . . . . . . . . . . . . . . . . . . . . 55  
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . 63  
PRE-START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66  
START-UP, GENERAL . . . . . . . . . . . . . . . . . . . . . . . . 66  
START-UP, PREMIERLINKT CONTROL . . . . . . . . 68  
START-UP, RTU-MP CONTROL . . . . . . . . . . . . . . . . 68  
OPERATING SEQUENCES . . . . . . . . . . . . . . . . . . . . . 71  
FASTENER TORQUE VALUES . . . . . . . . . . . . . . . . . 81  
APPENDIX I. MODEL NUMBER SIGNIFICANCE . 82  
APPENDIX II. PHYSICAL DATA . . . . . . . . . . . . . . . . 83  
APPENDIX III. FAN PERFORMANCE . . . . . . . . . . . 87  
APPENDIX IV. ELECTRICAL DATA . . . . . . . . . . . . . 99  
APPENDIX V. WIRING DIAGRAM LIST . . . . . . . . 104  
Installation and servicing of air-conditioning equipment  
can be hazardous due to system pressure and electrical  
components. Only trained and qualified service personnel  
should install, repair, or service air-conditioning  
equipment. Untrained personnel can perform the basic  
maintenance functions of replacing filters. Trained service  
personnel should perform all other operations.  
When working on air-conditioning equipment, observe  
precautions in the literature, tags and labels attached to  
the unit, and other safety precautions that may apply.  
Follow all safety codes. Wear safety glasses and work  
gloves. Use quenching cloth for unbrazing operations.  
Have fire extinguishers available for all brazing  
operations.  
Follow all safety codes. Wear safety glasses and work  
gloves. Use quenching cloth for brazing operations. Have  
fire extinguisher available. Read these instructions  
thoroughly and follow all warnings or cautions attached to  
the unit. Consult local building codes and National  
Electrical Code (NEC) for special requirements.  
Recognize safety information. This is the safety-alert  
symbol  
. When you see this symbol on the unit and in  
instructions or manuals, be alert to the potential for  
personal injury.  
Understand the signal words DANGER, WARNING, and  
CAUTION. These words are used with the safety-alert  
symbol. DANGER identifies the most serious hazards  
which will result in severe personal injury or death.  
WARNING signifies a hazard which could result in  
personal injury or death. CAUTION is used to identify  
unsafe practices which may result in minor personal  
injury or product and property damage. NOTE is used to  
highlight suggestions which will result in enhanced  
installation, reliability, or operation.  
APPENDIX VI. MOTORMASTER SENSOR  
LOCATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105  
UNIT START-UP CHECKLIST . . . . . . . . . . . . . . . . . 107  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Quarterly Inspection (and 30 days after initial start)  
S Return air filter replacement  
To remove the filters:  
1. Grasp the bottom flange of the upper panel.  
S Outdoor hood inlet filters cleaned  
S Belt tension checked  
2. Lift up and swing the bottom out until the panel dis-  
engages and pulls out.  
3. Reach inside and extract the filters from the filter  
rack.  
4. Replace these filters as required with similar replace-  
ment filters of same size.  
S Belt condition checked  
S Pulley alignment checked  
S Fan shaft bearing locking collar tightness checked  
S Condenser coil cleanliness checked  
S Condensate drain checked  
To re-install the access panel:  
1. Slide the top of the panel up under the unit top panel.  
2. Slide the bottom into the side channels.  
Seasonal Maintenance  
These items should be checked at the beginning of each  
season (or more often if local conditions and usage  
patterns dictate):  
3. Push the bottom flange down until it contacts the top  
of the lower panel (or economizer top).  
IMPORTANT: DO NOT OPERATE THE UNIT  
WITHOUT THESE FILTERS!  
Air Conditioning  
Outside Air Hood  
S Condenser fan motor mounting bolts tightness  
S Compressor mounting bolts  
S Condenser fan blade positioning  
S Control box cleanliness and wiring condition  
S Wire terminal tightness  
Outside air hood inlet screens are permanent  
aluminum-mesh type filters. Check these for cleanliness.  
Remove the screens when cleaning is required. Clean by  
washing with hot low-pressure water and soft detergent  
and replace all screens before restarting the unit. Observe  
the flow direction arrows on the side of each filter frame.  
S Refrigerant charge level  
S Evaporator coil cleaning  
Economizer Inlet Air Screen  
S Evaporator blower motor amperage  
Heating  
This air screen is retained by spring clips under the top  
edge of the hood. (See Fig. 3.)  
S Heat exchanger flue passageways cleanliness  
S Gas burner condition  
17 1/4”  
S Gas manifold pressure  
S Heating temperature rise  
Economizer or Outside Air Damper  
S Inlet filters condition  
DIVIDER  
S Check damper travel (economizer)  
S Check gear and dampers for debris and dirt  
Air Filters and Screens  
OUTSIDE  
AIR  
HOOD  
Each unit is equipped with return air filters. If the unit has  
an economizer, it will also have an outside air screen. If a  
manual outside air damper is added, an inlet air screen  
will also be present.  
CLEANABLE  
ALUMINUM  
FILTER  
FILTER  
BAROMETRIC  
RELIEF  
Each of these filters and screens will need to be  
periodically replaced or cleaned.  
FILTER  
CLIP  
C06027  
Return Air Filters  
Fig. 3 - Filter Installation  
Return air filters are disposable fiberglass media type.  
Access to the filters is through the small lift-out panel  
located on the rear side of the unit, above the  
evaporator/return air access panel. (See Fig. 1.)  
To remove the filter, open the spring clips. Re-install the  
filter by placing the frame in its track, then closing the  
spring clips.  
Manual Outside Air Hood Screen  
This inlet screen is secured by a retainer angle across the  
top edge of the hood. (See Fig. 4.)  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
inside surfaces. Check belt tension by using a spring-force  
tool (such as Browning’s Part Number “Belt Tension  
Checker” or equivalent tool); tension should be 6-lbs at a  
5/8-in. deflection when measured at the centerline of the  
belt span. This point is at the center of the belt when  
measuring the distance between the motor shaft and the  
blower shaft.  
NOTE: Without the spring-tension tool, place a straight  
edge across the belt surface at the pulleys, then deflect the  
belt at mid-span using one finger to a 1/2-in. deflection.  
Adjust belt tension by loosening the motor mounting plate  
front bolts and rear bolt and sliding the plate toward the  
fan (to reduce tension) or away from fan (to increase  
tension). Ensure the blower shaft and the motor shaft are  
parallel to each other (pulleys aligned). Tighten all bolts  
when finished.  
C07156  
Fig. 4 - Screens Installed on Outdoor-Air Hood  
(Sizes 7-1/2 to 12-1/2 Tons Shown)  
To remove the screen, loosen the screws in the top retainer  
and slip the retainer up until the filter can be removed.  
Re-install by placing the frame in its track, rotating the  
retainer back down and tighten all screws.  
To replace the belt:  
1. Use a belt with same section type or similar size. Do  
not substitute a “FHP” type belt. When installing the  
new belt, do not use a tool (screwdriver or pry-bar) to  
force the belt over the pulley flanges, this will stress  
the belt and cause a reduction in belt life.  
SUPPLY FAN (BLOWER) SECTION  
2. Loosen the motor mounting plate front bolts and rear  
bolts.  
3. Push the motor and its mounting plate towards the  
blower housing as close as possible to reduce the cen-  
ter distance between fan shaft and motor shaft.  
4. Remove the belt by gently lifting the old belt over  
one of the pulleys.  
5. Install the new belt by gently sliding the belt over  
both pulleys and then sliding the motor and plate  
away from the fan housing until proper tension is  
achieved.  
6. Check the alignment of the pulleys, adjust if neces-  
sary.  
7. Tighten all bolts.  
8. Check the tension after a few hours of runtime and  
re-adjust as required.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could cause personal  
injury or death.  
Before performing service or maintenance operations  
on the fan system, shut off all unit power and tag-out  
the unit disconnect switch. Do not reach into the fan  
section with power still applied to unit.  
Supply Fan (Belt--Drive)  
The supply fan system consists of a forward-curved  
centrifugal blower wheel on a solid shaft with two  
concentric type bearings, one on each side of the blower  
housing. A fixed-pitch driven pulley is attached to the fan  
shaft and an adjustable-pitch driver pulley is on the  
motor. The pulleys are connected using a “V” type belt.  
(See Fig. 5.)  
Adjustable-Pitch Pulley on Motor  
The motor pulley is an adjustable-pitch type that allows a  
servicer to implement changes in the fan wheel speed to  
match as-installed ductwork systems. The pulley consists  
of a fixed flange side that faces the motor (secured to the  
motor shaft) and a movable flange side that can be rotated  
around the fixed flange side that increases or reduces the  
pitch diameter of this driver pulley. (See Fig. 6.)  
As the pitch diameter is changed by adjusting the position  
of the movable flange, the centerline on this pulley shifts  
laterally (along the motor shaft). This creates  
a
requirement for a realignment of the pulleys after any  
adjustment of the movable flange. Also reset the belt  
tension after each realignment.  
C07087  
Check the condition of the motor pulley for signs of wear.  
Glazing of the belt contact surfaces and erosion on these  
surfaces are signs of improper belt tension and/or belt  
slippage. Pulley replacement may be necessary.  
Fig. 5 - Belt Drive Motor Mounting  
Belt  
Check the belt condition and tension quarterly. Inspect the  
belt for signs of cracking, fraying or glazing along the  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
To change fan speed:  
Motor  
1. Shut off unit power supply.  
2. Loosen belt by loosening fan motor mounting nuts.  
(See Fig. 5.)  
When replacing the motor, also replace the external-tooth  
lock washer (star washer) under the motor mounting base;  
this is part of the motor grounding system. Ensure the  
teeth on the lock washer are in contact with the motor’s  
painted base. Tighten motor mounting bolts to 120 +/- 12  
in-lbs.  
3. Loosen movable pulley flange setscrew. (See Fig. 6.)  
4. Screw movable flange toward fixed flange to increase  
speed and away from fixed flange to decrease speed.  
Increasing fan speed increases load on motor. Do not  
exceed maximum speed specified.  
5. Set movable flange at nearest keyway of pulley hub  
and tighten setscrew to torque specifications.  
Changing fan wheel speed by changing pulleys: The  
horsepower rating of the belt is primarily dictated by the  
pitch diameter of the smaller pulley in the drive system  
(typically the motor pulley in these units). Do not install a  
replacement motor pulley with a smaller pitch diameter  
than provided on the original factory pulley. Change fan  
wheel speed by changing the fan pulley (larger pitch  
diameter to reduce wheel speed, smaller pitch diameter to  
increase wheel speed) or select a new system (both  
pulleys and matching belt(s)).  
To align fan and motor pulleys:  
1. Loosen fan pulley setscrews.  
2. Slide fan pulley along fan shaft. Make angular align-  
ment by loosening motor from mounting.  
3. Tighten fan pulley setscrews and motor mounting  
bolts to torque specifications.  
4. Recheck belt tension.  
Before changing pulleys to increase fan wheel speed,  
check the fan performance at the target speed and airflow  
rate to determine new motor loading (bhp). Use the fan  
performance tables or use the Packaged Rooftop Builder  
software program. Confirm that the motor in this unit is  
capable of operating at the new operating condition. Fan  
shaft loading increases dramatically as wheel speed is  
increased.  
To reduce vibration, replace the motor’s adjustable pitch  
pulley with a fixed pitch pulley (after the final airflow  
balance adjustment). This will reduce the amount of  
vibration generated by the motor/belt-drive system.  
COOLING  
C07075  
!
WARNING  
Fig. 6 - Supply-Fan Pulley Adjustment  
UNIT OPERATION AND SAFETY HAZARD  
Bearings  
Failure to follow this warning could cause personal  
injury, death and/or equipment damage.  
This fan system uses bearings featuring concentric split  
locking collars. The collars are tightened through a cap  
screw bridging the split portion of the collar. The cap  
screw has a Torx T25 socket head. To tighten the locking  
collar: Hold the locking collar tightly against the inner  
race of the bearing and torque the cap screw to 65-70  
in-lb (7.4-7.9 Nm). See Fig. 7.  
This system uses PuronR refrigerant which has  
higher pressures than R-22 and other refrigerants. No  
other refrigerant may be used in this system. Gauge  
set, hoses, and recovery system must be designed to  
handle Puron refrigerant. If unsure about equipment,  
consult the equipment manufacturer.  
Condenser Coil  
The condenser coil is fabricated with round tube copper  
hairpins and plate fins of various materials and/or coatings  
(see Model Number Format in the Appendix to identify  
the materials provided in this unit). The coil may be  
one-row or composite-type two-row. Composite two-row  
coils are two single-row coils fabricated with a single  
return bend end tubesheet.  
Condenser Coil Maintenance and Cleaning  
Recommendation  
Routine cleaning of coil surfaces is essential to maintain  
proper operation of the unit. Elimination of contamination  
and removal of harmful residues will greatly increase the  
C08121  
Fig. 7 - Tightening Locking Collar  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
life of the coil and extend the life of the unit. The  
following maintenance and cleaning procedures are  
recommended as part of the routine maintenance activities  
to extend the life of the coil.  
Two-Row Coils  
                                                                                                                  
Clean coil as follows:  
1. Turn off unit power, tag disconnect.  
2. Remove top panel screws on condenser end of unit.  
Remove Surface Loaded Fibers  
3. Remove condenser coil corner post. See Fig. 8. To  
hold top panel open, place coil corner post between  
top panel and center post. See Fig. 9.  
Surface loaded fibers or dirt should be removed with a  
vacuum cleaner. If a vacuum cleaner is not available, a  
soft non-metallic bristle brush may be used. In either  
case, the tool should be applied in the direction of the fins.  
Coil surfaces can be easily damaged (fin edges can be  
easily bent over and damage to the coating of a protected  
coil) if the tool is applied across the fins.  
NOTE: Use of a water stream, such as a garden hose,  
against a surface loaded coil will drive the fibers and dirt  
into the coil. This will make cleaning efforts more  
difficult. Surface loaded fibers must be completely  
removed prior to using low velocity clean water rinse.  
Periodic Clean Water Rinse  
A periodic clean water rinse is very beneficial for coils  
that are applied in coastal or industrial environments.  
However, it is very important that the water rinse is made  
with a very low velocity water stream to avoid damaging  
the fin edges. Monthly cleaning as described below is  
recommended.  
C08205  
Fig. 8 - Cleaning Condenser Coil  
Routine Cleaning of Coil Surfaces  
Periodic cleaning with TotalineR environmentally sound  
coil cleaner is essential to extend the life of coils. This  
cleaner is available from Carrier Replacement  
Components Division as part number P902-0301 for a one  
gallon container, and part number P902-0305 for a 5  
gallon container. It is recommended that all coils,  
including standard aluminum, pre-coated, copper/copper  
or E-coated coils be cleaned with the Totaline  
environmentally sound coil cleaner as described below.  
Coil cleaning should be part of the unit’s regularly  
scheduled maintenance procedures to ensure long life of  
the coil. Failure to clean the coils may result in reduced  
durability in the environment.  
C08206  
Fig. 9 - Propping Up Top Panel  
4. Remove screws securing coil to compressor plate and  
compressor access panel.  
5. Remove fastener holding coil sections together at re-  
turn end of condenser coil. Carefully separate the out-  
er coil section 3 to 4 in. from the inner coil section.  
See Fig. 10.  
Avoid use of:  
S coil brighteners  
S acid cleaning prior to painting  
S high pressure washers  
S poor quality water for cleaning  
Totaline environmentally sound coil cleaner is  
nonflammable, hypo allergenic, non bacterial, and a  
USDA accepted biodegradable agent that will not harm  
the coil or surrounding components such as electrical  
wiring, painted metal surfaces, or insulation. Use of  
non-recommended coil cleaners is strongly discouraged  
since coil and unit durability could be affected.  
One-Row Coil  
Wash coil with commercial coil cleaner. It is not  
necessary to remove top panel.  
C08207  
Fig. 10 - Separating Coil Sections  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Use a water hose or other suitable equipment to flush  
down between the 2 coil sections to remove dirt and  
debris. Clean the outer surfaces with a stiff brush in  
the normal manner.  
Avoid spraying in horizontal pattern to minimize po-  
tential for fin damage.  
7. Ensure cleaner thoroughly penetrates deep into finned  
areas.  
7. Secure inner and outer coil rows together with a  
field-supplied fastener.  
8. Interior and exterior finned areas must be thoroughly  
cleaned.  
8. Reposition the outer coil section and remove the coil  
corner post from between the top panel and center  
post. Reinstall the coil corner post and replace all  
screws.  
9. Finned surfaces should remain wet with cleaning  
solution for 10 minutes.  
10. Ensure surfaces are not allowed to dry before rinsing.  
Reapplying cleaner as needed to ensure 10-minute  
saturation is achieved.  
11. Thoroughly rinse all surfaces with low velocity clean  
water using downward rinsing motion of water spray  
nozzle. Protect fins from damage from the spray  
nozzle.  
Totaline Environmentally Sound Coil Cleaner  
Application Equipment  
S 2-1/2 gallon garden sprayer  
S Water rinse with low velocity spray nozzle  
Evaporator Coil  
!
CAUTION  
Cleaning the Evaporator Coil  
UNIT DAMAGE HAZARD  
1. Turn unit power off. Install lockout tag. Remove  
evaporator coil access panel.  
2. If economizer or two-position damper is installed, re-  
move economizer by disconnecting Molex plug and  
removing mounting screws.  
Failure to follow this caution may result in accelerated  
corrosion of unit parts.  
Harsh chemicals, household bleach or acid or basic  
cleaners should not be used to clean outdoor or indoor  
coils of any kind. These cleaners can be very difficult  
to rinse out of the coil and can accelerate corrosion at  
the fin/tube interface where dissimilar materials are in  
contact. If there is dirt below the surface of the coil,  
use the Totaline environmentally sound coil cleaner.  
3. Slide filters out of unit.  
4. Clean coil using a commercial coil cleaner or dish-  
washer detergent in a pressurized spray canister. Wash  
both sides of coil and flush with clean water. For best  
results, back-flush toward return-air section to re-  
move foreign material. Flush condensate pan after  
completion.  
!
CAUTION  
5. Reinstall economizer and filters.  
6. Reconnect wiring.  
UNIT DAMAGE HAZARD  
Failure to follow this caution may result in reduced  
unit performance or unit shutdown.  
7. Replace access panels.  
Evaporator Coil Metering Devices  
High velocity water from a pressure washer, garden  
hose, or compressed air should never be used to  
clean a coil. The force of the water or air jet will  
bend the fin edges and increase airside pressure drop.  
The metering devices are multiple fixed-bore devices  
(Acutrolt) swedged into the horizontal outlet tubes from  
the liquid header, located at the entrance to each  
evaporator coil circuit path. These are non-adjustable.  
Service requires replacing the entire liquid header  
assembly.  
Totaline Environmentally Sound Coil Cleaner  
Application Instructions  
To check for possible blockage of one or more of these  
metering devices, disconnect the supply fan contactor  
(IFC) coil, then start the compressor and observe the  
frosting pattern on the face of the evaporator coil. A frost  
pattern should develop uniformly across the face of the  
coil starting at each horizontal header tube. Failure to  
develop frost at an outlet tube can indicate a plugged or a  
missing orifice.  
1. Proper eye protection such as safety glasses is recom-  
mended during mixing and application.  
2. Remove all surface loaded fibers and dirt with a vacu-  
um cleaner as described above.  
3. Thoroughly wet finned surfaces with clean water and  
a low velocity garden hose, being careful not to bend  
fins.  
4. Mix Totaline environmentally sound coil cleaner in a  
2-1/2 gallon garden sprayer according to the instruc-  
tions included with the cleaner. The optimum solution  
temperature is 100_F.  
Refrigerant System Pressure Access Ports  
There are two access ports in the system - on the suction  
tube near the compressor and on the discharge tube near  
the compressor. These are brass fittings with black plastic  
caps. The hose connection fittings are standard 1/4 SAE  
male flare couplings.  
NOTE: Do NOT USE water in excess of 130_F, as the  
enzymatic activity will be destroyed.  
5. Thoroughly apply Totaline environmentally sound  
coil cleaner solution to all coil surfaces including  
finned area, tube sheets and coil headers.  
6. Hold garden sprayer nozzle close to finned areas and  
apply cleaner with a vertical, up-and-down motion.  
The brass fittings are two-piece High Flow valves, with a  
receptacle base brazed to the tubing and an integral  
spring-closed check valve core screwed into the base.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
(See Fig. 11.) This check valve is permanently assembled  
into this core body and cannot be serviced separately;  
replace the entire core body if necessary. Service tools are  
available from RCD that allow the replacement of the  
check valve core without having to recover the entire  
system refrigerant charge. Apply compressor refrigerant  
oil to the check valve core’s bottom o-ring. Install the  
fitting body with 96 +/ -10 in-lbs of torque; do not  
overtighten.  
Refrigerant Charge  
Amount of refrigerant charge is listed on the unit’s  
nameplate. Refer to Carrier GTAC2-5 Charging,  
Recovery, Recycling and Reclamation training manual  
and the following procedures.  
Unit panels must be in place when unit is operating during  
the charging procedure.  
No Charge  
PURONR (R--410A) REFRIGERANT  
Use standard evacuating techniques. After evacuating  
system, weigh in the specified amount of refrigerant.  
This unit is designed for use with Puron (R-410A)  
refrigerant. Do not use any other refrigerant in this  
system.  
Low-Charge Cooling  
Using Cooling Charging Charts, Fig. 12, vary refrigerant  
until the conditions of the appropriate chart are met. Note  
the charging charts are different from type normally used.  
Charts are based on charging the units to the correct  
superheat for the various operating conditions. Accurate  
pressure gauge and temperature sensing device are  
required. Connect the pressure gauge to the service port  
on the suction line. Mount the temperature sensing device  
on the suction line and insulate it so that outdoor ambient  
temperature does not affect the reading. Indoor-air cfm  
must be within the normal operating range of the unit.  
Puron (R-410A) refrigerant is provided in pink (rose)  
colored cylinders. These cylinders are available with and  
without dip tubes; cylinders with dip tubes will have a  
label indicating this feature. For a cylinder with a dip  
tube, place the cylinder in the upright position (access  
valve at the top) when removing liquid refrigerant for  
charging. For a cylinder without a dip tube, invert the  
cylinder (access valve on the bottom) when removing  
liquid refrigerant.  
Because Puron (R-410A) refrigerant is a blend, it is  
strongly recommended that refrigerant always be removed  
from the cylinder as a liquid. Admit liquid refrigerant into  
the system in the discharge line. If adding refrigerant into  
the suction line, use a commercial metering/expansion  
device at the gauge manifold; remove liquid from the  
cylinder, pass it through the metering device at the gauge  
set and then pass it into the suction line as a vapor. Do not  
remove Puron (R-410A) refrigerant from the cylinder as a  
vapor.  
To Use Cooling Charging Charts  
Take the outdoor ambient temperature and read the  
suction pressure gauge. Refer to chart to determine what  
suction temperature should be. If suction temperature is  
high, add refrigerant. If suction temperature is low,  
carefully recover some of the charge. Recheck the suction  
pressure as charge is adjusted.  
SEAT  
CORE  
(Part No. EC39EZ067)  
1/2-20 UNF RH  
0.596  
45o  
30o  
WASHER  
O-RING  
DEPRESSOR PER ARI 720  
+.01/-.035  
FROM FACE OF BODY  
1/2" HEX  
.47  
5/8” HEX  
7/16-20 UNF RH  
This surface provides a metal to metal seal when  
torqued into the seat. Appropriate handling is  
required to not scratch or dent the surface.  
C08453  
Fig. 11 - CoreMax Access Port Assembly  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOMINAL TONS  
REFERENCE  
SIZE DESIGNATION  
EXAMPLE:  
A04  
A05  
A06  
A07  
A08  
A09  
A12  
3
4
5
Model 48TC*A04  
Outdoor Temperature . . . . . . . . . . . . . . . . . . 85_F (29_C)  
Suction Pressure . . . . . . . . . . . . . . . . . 140 psig (965 kPa)  
Suction Temperature should be . . . . . . . . . . 60_F (16_C)  
6
7.5  
8.5  
10  
COOLING CHARGING CHARTS  
C08203  
Fig. 12 - Cooling Charging Charts  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING CHARGING CHARTS (cont.)  
C08204  
C08228  
Fig. 12 (cont.) - Cooling Charging Charts  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING CHARGING CHARTS (cont.)  
C08229  
C08437  
Fig. 12 (cont.) - Cooling Charging Charts  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
COOLING CHARGING CHARTS (cont.)  
C08438  
C08439  
Fig. 12 (cont.) - Cooling Charging Charts  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1 – Cooling Service Analysis  
PROBLEM  
CAUSE  
REMEDY  
Power failure.  
Fuse blown or circuit breaker tripped.  
Call power company.  
Replace fuse or reset circuit breaker.  
Defective thermostat, contactor, transformer,  
or control relay.  
Insufficient line voltage.  
Incorrect or faulty wiring.  
Thermostat setting too high.  
Replace component.  
Compressor and Condenser  
Fan Will Not Start.  
Determine cause and correct.  
Check wiring diagram and rewire correctly.  
Lower thermostat setting below room temperature.  
Faulty wiring or loose connections in  
compressor circuit.  
Compressor motor burned out, seized, or  
internal overload open.  
Defective run/start capacitor, overload, start  
relay.  
Check wiring and repair or replace.  
Determine cause. Replace compressor.  
Determine cause and replace.  
Compressor Will Not Start But  
Condenser Fan Runs.  
Replace fuse or reset circuit breaker. Determine  
cause.  
Recover refrigerant, evacuate system, and recharge  
to nameplate.  
One leg of three---phase power dead.  
Refrigerant overcharge or undercharge.  
Defective compressor.  
Insufficient line voltage.  
Blocked condenser.  
Defective run/start capacitor, overload, or start  
relay.  
Replace and determine cause.  
Determine cause and correct.  
Determine cause and correct.  
Compressor Cycles (other  
than normally satisfying ther-  
mostat).  
Determine cause and replace.  
Defective thermostat.  
Replace thermostat.  
Faulty condenser---fan motor or capacitor.  
Restriction in refrigerant system.  
Dirty air filter.  
Replace.  
Locate restriction and remove.  
Replace filter.  
Unit undersized for load.  
Thermostat set too low.  
Low refrigerant charge.  
Leaking valves in compressor.  
Air in system.  
Decrease load or increase unit size.  
Reset thermostat.  
Locate leak; repair and recharge.  
Replace compressor.  
Recover refrigerant, evacuate system, and recharge.  
Clean coil or remove restriction.  
Replace filter.  
Compressor Operates  
Continuously.  
Condenser coil dirty or restricted.  
Dirty air filter.  
Dirty condenser coil.  
Clean coil.  
Refrigerant overcharged.  
Air in system.  
Recover excess refrigerant.  
Recover refrigerant, evacuate system, and recharge.  
Determine cause and correct.  
Check for leaks; repair and recharge.  
Replace compressor.  
Remove restriction.  
Check for source and eliminate.  
Replace compressor.  
Excessive Head Pressure.  
Condenser air restricted or air short---cycling.  
Low refrigerant charge.  
Compressor valves leaking.  
Restriction in liquid tube.  
High head load.  
Compressor valves leaking.  
Refrigerant overcharged.  
Dirty air filter.  
Head Pressure Too Low.  
Excessive Suction Pressure.  
Recover excess refrigerant.  
Replace filter.  
Low refrigerant charge.  
Metering device or low side restricted.  
Check for leaks; repair and recharge.  
Remove source of restriction.  
Suction Pressure Too Low.  
Increase air quantity. Check filter and replace if  
necessary.  
Insufficient evaporator airflow.  
Temperature too low in conditioned area.  
Reset thermostat.  
Outdoor ambient below 25˚F.  
Install low---ambient kit.  
Evaporator Fan Will Not Shut  
Off.  
Time off delay not finished.  
Wa it f o r 3 0 --- se co n d o f f d e la y.  
Compressor Makes Excessive  
Noise.  
Compressor rotating in wrong direction.  
Reverse the 3---phase power leads.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Remove condenser-fan assembly (grille, motor, and  
fan).  
3. Loosen fan hub setscrews.  
4. Adjust fan height as shown in Fig. 13.  
5. Tighten setscrews.  
Compressor  
Lubrication  
The compressor is charged with the correct amount of oil  
at the factory.  
6. Replace condenser-fan assembly.  
!
CAUTION  
UNIT DAMAGE HAZARD  
Failure to follow this caution may result in damage to  
components.  
Conduit  
The compressor is in a PuronR refrigerant system and  
uses a polyolester (POE) oil. This oil is extremely  
hygroscopic, meaning it absorbs water readily. POE  
oils can absorb 15 times as much water as other oils  
designed for HCFC and CFC refrigerants. Avoid  
exposure of the oil to the atmosphere.  
0.14 in + 0.0 / -0.03  
C08448  
Fig. 13 - Condenser Fan Adjustment  
Troubleshooting Cooling System  
Replacing Compressor  
Refer to Table 1 for additional troubleshooting topics.  
The compressor used with Puron refrigerant contains a  
POE oil. This oil has a high affinity for moisture. Do not  
remove the compressor’s tube plugs until ready to insert  
the unit suction and discharge tube ends.  
CONVENIENCE OUTLETS  
!
WARNING  
Compressor mounting bolt torque is 65-75 ft-lbs.  
ELECTRICAL OPERATION HAZARD  
Compressor Rotation  
Failure to follow this warning could result in personal  
injury or death.  
On 3-phase units with scroll compressors, it is important  
to be certain compressor is rotating in the proper  
direction. To determine whether or not compressor is  
rotating in the proper direction:  
Units with convenience outlet circuits may use  
multiple disconnects. Check convenience outlet for  
power status before opening unit for service. Locate  
its disconnect switch, if appropriate, and open it.  
Tag-out this switch, if necessary.  
1. Connect service gauges to suction and discharge pres-  
sure fittings.  
2. Energize the compressor.  
3. The suction pressure should drop and the discharge  
pressure should rise, as is normal on any start-up.  
NOTE: If the suction pressure does not drop and the  
discharge pressure does not rise to normal levels:  
4. Note that the evaporator fan is probably also rotating  
in the wrong direction.  
5. Turn off power to the unit.  
6. Reverse any two of the unit power leads.  
7. Reapply power to the compressor.  
Two types of convenience outlets are offered on 48TC  
models: Non-powered and unit-powered. Both types  
provide  
a
125-volt  
GFCI  
(ground-fault  
circuit-interrupter) duplex receptacle rated at 15-A  
behind a hinged waterproof access cover, located on the  
end panel of the unit. See Fig. 14.  
Pwd-CO Transformer  
Conv Outlet  
GFCI  
Pwd-CO  
Fuse  
The suction and discharge pressure levels should now  
move to their normal start-up levels.  
Switch  
NOTE: When the compressor is rotating in the wrong  
direction, the unit makes an elevated level of noise and  
does not provide cooling.  
Filter Drier  
Replace whenever refrigerant system is exposed to  
atmosphere. Only use factory specified liquid-line filter  
driers with working pressures no less than 650 psig. Do  
not install a suction-line filter drier in liquid line. A  
liquid-line filter drier designed for use with Puron  
refrigerant is required on every unit.  
C08128  
Fig. 14 - Convenience Outlet Location  
Non-powered type: This type requires the field  
installation of a general-purpose 125-volt 15-A circuit  
powered from a source elsewhere in the building. Observe  
national and local codes when selecting wire size, fuse or  
Condenser--Fan Adjustment  
1. Shut off unit power supply. Install lockout tag.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
breaker requirements and disconnect switch size and  
location. Route 125-v power supply conductors into the  
bottom of the utility box containing the duplex receptacle.  
lamps, etc; it is not intended to provide 15-amps loading  
                                                                                                                                                                         
for continuous duty loads (such as electric heaters for  
overnight use). Observe a 50% limit on circuit loading  
above 8-amps (i.e., limit loads exceeding 8-amps to 30  
minutes of operation every hour).  
Unit-powered type: A unit-mounted transformer is  
factory-installed to stepdown the main power supply  
voltage to the unit to 115-v at the duplex receptacle. This  
option also includes a manual switch with fuse, located in  
a utility box and mounted on a bracket behind the  
convenience outlet; access is through the unit’s control  
box access panel. See Fig. 14.  
Maintenance: Periodically test the GFCI receptacle by  
pressing the TEST button on the face of the receptacle.  
This should cause the internal circuit of the receptacle to  
trip and open the receptacle. Check for proper grounding  
wires and power line phasing if the GFCI receptacle does  
not trip as required. Press the RESET button to clear the  
tripped condition.  
The primary leads to the convenience outlet transformer  
are not factory-connected. Selection of primary power  
source is a customer-option. If local codes permit, the  
transformer primary leads can be connected at the  
Fuse on powered type: The factory fuse is a Bussman  
“Fusetron” T-15, non-renewable screw-in (Edison base)  
type plug fuse.  
line-side terminals on  
a
unit-mounted non-fused  
disconnect or HACR breaker switch; this will provide  
service power to the unit when the unit disconnect switch  
or HACR switch is open. Other connection methods will  
result in the convenience outlet circuit being de-energized  
when the unit disconnect or HACR switch is open. See  
Fig. 15.  
Using unit-mounted convenience outlets: Units with  
unit-mounted convenience outlet circuits will often  
require that two disconnects be opened to de-energize all  
power to the unit. Treat all units as electrically energized  
until the convenience outlet power is also checked and  
de-energization is confirmed. Observe National Electrical  
Code Article 210, Branch Circuits, for use of convenience  
outlets.  
SMOKE DETECTORS  
Smoke detectors are available as factory-installed options  
on 48TC models. Smoke detectors may be specified for  
Supply Air only or for Return Air without or with  
economizer or in combination of Supply Air and Return  
Air. Return Air smoke detectors are arranged for vertical  
return configurations only. All components necessary for  
operation are factory-provided and mounted. The unit is  
factory-configured for immediate smoke detector  
shutdown operation; additional wiring or modifications to  
unit terminal board may be necessary to complete the unit  
and smoke detector configuration to meet project  
requirements.  
CO8283  
System  
Fig. 15 - Powered Convenience Outlet Wiring  
The smoke detector system consists of a four-wire  
controller and one or two sensors. Its primary function is  
to shut down the rooftop unit in order to prevent smoke  
from circulating throughout the building. It is not to be  
used as a life saving device.  
UNIT  
VOLTAGE  
CONNECT  
AS  
PRIMARY  
CONNECTIONS  
TRANSFORMER  
TERMINALS  
208,  
230  
L1: RED +YEL  
L2: BLU + GRA  
L1: RED  
Splice BLU + YEL  
L2: GRA  
H1 + H3  
H2 + H4  
H1  
H2 + H3  
H4  
240  
480  
600  
Controller  
460  
575  
The controller (see Fig. 16) includes a controller housing,  
a printed circuit board, and a clear plastic cover. The  
controller can be connected to one or two compatible duct  
smoke sensors. The clear plastic cover is secured to the  
housing with a single captive screw for easy access to the  
wiring terminals. The controller has three LEDs (for  
Power, Trouble and Alarm) and a manual test/reset button  
(on the cover face).  
L1: RED  
L2: GRA  
H1  
H2  
Duty Cycle: The unit-powered convenience outlet has a  
duty cycle limitation. The transformer is intended to  
provide power on an intermittent basis for service tools,  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Duct smoke sensor  
Exhaust gasket  
Duct smoke sensor  
controller  
Exhaust tube  
Conduit nuts  
(supplied by installer)  
Sensor housing  
and electronics  
See  
Detail A  
Conduit support plate  
Terminal block cover  
Cover gasket  
(ordering option)  
Intake  
gasket  
Controller housing  
and electronics  
Cover gasket  
(ordering option)  
Controller cover  
Conduit couplings  
(supplied by installer)  
TSD-CO2  
(ordering option)  
Sensor cover  
Plug  
Fastener  
(2X)  
Sampling tube  
(ordered separately)  
Coupling  
Detail A  
Trouble  
Alarm  
Power  
Test/reset  
switch  
Magnetic  
test/reset  
switch  
C08208  
Fig. 16 - Controller Assembly  
Alarm  
Trouble  
Power  
Dirty  
C08209  
Sensor  
Fig. 17 - Smoke Detector Sensor  
The sensor (see Fig. 17) includes a plastic housing, a  
printed circuit board, a clear plastic cover, a sampling  
tube inlet and an exhaust tube. The sampling tube (when  
used) and exhaust tube are attached during installation.  
The sampling tube varies in length depending on the size  
of the rooftop unit. The clear plastic cover permits visual  
inspections without having to disassemble the sensor. The  
cover attaches to the sensor housing using four captive  
screws and forms an airtight chamber around the sensing  
electronics. Each sensor includes a harness with an RJ45  
terminal for connecting to the controller. Each sensor has  
four LEDs (for Power, Trouble, Alarm and Dirty) and a  
manual test/reset button (on the left-side of the housing).  
For installations using two sensors, the duct smoke  
detector does not differentiate which sensor signals an  
alarm or trouble condition.  
Smoke Detector Locations  
Supply Air — The Supply Air smoke detector sensor is  
located to the left of the unit’s indoor (supply) fan. See  
Fig. 18. Access is through the fan access panel. There is  
no sampling tube used at this location. The sampling tube  
inlet extends through the side plate of the fan housing  
(into a high pressure area). The controller is located on a  
bracket to the right of the return filter, accessed through  
the lift-off filter panel.  
Air is introduced to the duct smoke detector sensor’s  
sensing chamber through a sampling tube that extends into  
the HVAC duct and is directed back into the ventilation  
system through a (shorter) exhaust tube. The difference in  
air pressure between the two tubes pulls the sampled air  
through the sensing chamber. When a sufficient amount of  
smoke is detected in the sensing chamber, the sensor  
signals an alarm state and the controller automatically  
takes the appropriate action to shut down fans and  
blowers, change over air handling systems, notify the fire  
alarm control panel, etc.  
Smoke Detector Sensor  
The sensor uses a process called differential sensing to  
prevent gradual environmental changes from triggering  
false alarms. A rapid change in environmental conditions,  
such as smoke from a fire, causes the sensor to signal an  
alarm state but dust and debris accumulated over time  
does not.  
C08245  
Fig. 18 - Typical Supply Air Smoke Detector Sensor  
Location  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Return Air without Economizer — The sampling tube is  
located across the return air opening on the unit basepan.  
See Fig. 19. The holes in the sampling tube face  
downward, into the return air stream. The sampling tube is  
connected via tubing to the return air sensor that is  
mounted on a bracket high on the partition between return  
filter and controller location. (This sensor is shipped in a  
flat-mounting location. Installation requires that this  
sensor be relocated to its operating location and the tubing  
to the sampling tube be connected. See installation steps  
below.)  
Completing Installation of Return Air Smoke  
Sensor:  
Screws  
Flexible  
Exhaust Tubes  
Return Air Detector module  
(shipping position shown)*  
Sample Tube  
C08126  
Fig. 21 - Return Air Detector Shipping Position  
Controller module  
1. Unscrew the two screws holding the Return Air  
Sensor detector plate. See Fig. 21. Save the screws.  
2. Remove the Return Air Sensor and its detector plate.  
3. Rotate the detector plate so the sensor is facing out-  
wards and the sampling tube connection is on the bot-  
tom. See Fig. 22.  
4. Screw the sensor and detector plate into its operating  
position using screws from Step 1. Make sure the  
sampling tube connection is on the bottom and the ex-  
haust tube is on the top. See Fig. 22.  
5. Connect the flexible tube on the sampling inlet to the  
sampling tube on the basepan.  
Return Air Detector Sampling Tube  
*RA detector must be moved from shipping position to operating position by installer  
C07307  
Fig. 19 - Typical Return Air Detector Location  
Return Air with Economizer — The sampling tube is  
inserted through the side plates of the economizer  
housing, placing it across the return air opening on the  
unit basepan. See Fig. 20. The holes in the sampling tube  
face downward, into the return air stream. The sampling  
tube is connected via tubing to the return air sensor that is  
mounted on a bracket high on the partition between return  
filter and controller location. (This sensor is shipped in a  
flat-mounting location. Installation requires that this  
sensor be relocated to its operating location and the tubing  
to the sampling tube be connected. See installation steps  
below.)  
6. For units with an economizer, the sampling tube is in-  
tegrated into the economizer housing but the connec-  
tion of the flexible tubing to the sampling tube is the  
same.  
C08127  
Fig. 22 - Return Air Sensor Operating Position  
FIOP Smoke Detector Wiring and Response  
All units: FIOP smoke detector is configured to  
automatically shut down all unit operations when smoke  
condition is detected. See Fig. 23, Smoke Detector  
Wiring.  
Return Air  
Sampling Tube  
C08129  
Highlight A: JMP 3 is factory-cut, transferring unit  
control to smoke detector.  
Fig. 20 - Return Air Sampling Tube Location  
Highlight B: Smoke detector NC contact set will open on  
smoke alarm condition, de-energizing the ORN  
conductor.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B
D
C
F
E
A
C08246  
Fig. 23 - Typical Smoke Detector System Wiring  
Highlight C: 24-v power signal via ORN lead is removed  
at Smoke Detector input on LCTB; all unit operations  
cease immediately.  
Sensor and Controller Tests  
Sensor Alarm Test  
The sensor alarm test checks a sensor’s ability to signal an  
alarm state. This test requires that you use a field provided  
SD-MAG test magnet.  
PremierLink and RTU-MP Controls: Unit operating  
functions (fan, cooling and heating) are terminated as  
described above. In addition:  
!
CAUTION  
Highlight D: On smoke alarm condition, the smoke  
detector NO Alarm contact will close, supplying 24-v  
power to GRA conductor.  
OPERATIONAL TEST HAZARD  
Failure to follow this caution may result in personnel  
and authority concern.  
Highlight E: GRA lead at Smoke Alarm input on LCTB  
provides 24-v signal to FIOP DDC control.  
This test places the duct detector into the alarm state.  
Unless part of the test, disconnect all auxiliary  
equipment from the controller before performing the  
test. If the duct detector is connected to a fire alarm  
system, notify the proper authorities before  
performing the test.  
Premier-Link: This signal is conveyed to PremierLink  
FIOP’s TB1 at terminal TB1-6 (BLU lead). This signal  
initiates the FSD sequence by the PremierLink control.  
FSD status is reported to connected CCN network.  
RTU-MP: The 24-v signal is conveyed to RTU-MP’s  
J1-10 input terminal. This signal initiates the FSD  
sequence by the RTU-MP control. FSD status is reported  
to connected BAS network.  
Sensor Alarm Test Procedure  
1. Hold the test magnet where indicated on the side of  
the sensor housing for seven seconds.  
2. Verify that the sensor’s Alarm LED turns on.  
3. Reset the sensor by holding the test magnet against  
the sensor housing for two seconds.  
Using Remote Logic: Five conductors are provided for  
field use (see Highlight F) for additional annunciation  
functions.  
4. Verify that the sensor’s Alarm LED turns off.  
Additional Application Data — Refer to Catalog No.  
HKRNKA-1XA for discussions on additional control  
features of these smoke detectors including multiple unit  
coordination. See Fig. 23.  
Controller Alarm Test  
The controller alarm test checks the controller’s ability to  
initiate and indicate an alarm state.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 – Dirty LED Test  
!
CAUTION  
FLASHES  
DESCRIPTION  
0---25% dirty. (Typical of a newly installed detector)  
25---50% dirty  
1
2
3
4
OPERATIONAL TEST HAZARD  
Failure to follow this caution may result in personnel  
and authority concern.  
51---75% dirty  
76---99% dirty  
This test places the duct detector into the alarm state.  
Disconnect all auxiliary equipment from the controller  
before performing the test. If the duct detector is  
connected to a fire alarm system, notify the proper  
authorities before performing the test.  
Dirty Sensor Test Procedure  
1. Hold the test magnet where indicated on the side of  
the sensor housing for two seconds.  
2. Verify that the sensor’s Dirty LED flashes.  
Controller Alarm Test Procedure  
!
1. Press the controller’s test/reset switch for seven  
seconds.  
2. Verify that the controller’s Alarm LED turns on.  
CAUTION  
OPERATIONAL TEST HAZARD  
Failure to follow this caution may result in personnel  
and authority concern.  
3. Reset the sensor by pressing the test/reset switch for  
two seconds.  
Changing the dirty sensor test operation will put the  
detector into the alarm state and activate all automatic  
alarm responses. Before changing dirty sensor test  
operation, disconnect all auxiliary equipment from the  
controller and notify the proper authorities if  
connected to a fire alarm system.  
4. Verify that the controller’s Alarm LED turns off.  
Dirty Controller Test  
The dirty controller test checks the controller’s ability to  
initiate a dirty sensor test and indicate its results.  
!
CAUTION  
Changing the Dirt Sensor Test  
By default, sensor dirty test results are indicated by:  
S The sensor’s Dirty LED flashing.  
S The controller’s Trouble LED flashing.  
OPERATIONAL TEST HAZARD  
Failure to follow this caution may result in personnel  
and authority concern.  
S The controller’s supervision relay contacts toggle.  
The operation of a sensor’s dirty test can be changed so  
that the controller’s supervision relay is not used to  
indicate test results. When two detectors are connected to  
a controller, sensor dirty test operation on both sensors  
must be configured to operate in the same manner.  
Pressing the controller’s test/reset switch for longer  
than seven seconds will put the duct detector into the  
alarm state and activate all automatic alarm responses.  
Dirty Controller Test Procedure  
1. Press the controller’s test/reset switch for two  
seconds.  
To Configure the Dirty Sensor Test Operation  
1. Hold the test magnet where indicated on the side of  
the sensor housing until the sensor’s Alarm LED turns  
on and its Dirty LED flashes twice (approximately 60  
seconds).  
2. Reset the sensor by removing the test magnet then  
holding it against the sensor housing again until the  
sensor’s Alarm LED turns off (approximately 2  
seconds).  
2. Verify that the controller’s Trouble LED flashes.  
Dirty Sensor Test  
The dirty sensor test provides an indication of the sensor’s  
ability to compensate for gradual environmental changes.  
A sensor that can no longer compensate for environmental  
changes is considered 100% dirty and requires cleaning or  
replacing. You must use a field provided SD-MAG test  
magnet to initiate a sensor dirty test. The sensor’s Dirty  
LED indicates the results of the dirty test as shown in  
Table 2.  
Remote Station Test  
The remote station alarm test checks a test/reset station’s  
ability to initiate and indicate an alarm state.  
!
CAUTION  
!
CAUTION  
OPERATIONAL TEST HAZARD  
OPERATIONAL TEST HAZARD  
Failure to follow this caution may result in personnel  
and authority concern.  
Failure to follow this caution may result in personnel  
and authority concern.  
Holding the test magnet against the sensor housing for  
more than seven seconds will put the duct detector  
into the alarm state and activate all automatic alarm  
responses.  
This test places the duct detector into the alarm state.  
Unless part of the test, disconnect all auxiliary  
equipment from the controller before performing the  
test. If the duct detector is connected to a fire alarm  
system, notify the proper authorities before  
performing the test.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SD-TRK4 Remote Alarm Test Procedure  
Dirty Sensor Test Using an SD-TRK4  
1. Turn the key switch to the RESET/TEST position for  
seven seconds.  
1. Turn the key switch to the RESET/TEST position for  
two seconds.  
2. Verify that the test/reset station’s Alarm LED turns  
on.  
2. Verify that the test/reset station’s Trouble LED  
flashes.  
3. Reset the sensor by turning the key switch to the  
RESET/TEST position for two seconds.  
4. Verify that the test/reset station’s Alarm LED turns  
off.  
Detector Cleaning  
Cleaning the Smoke Detector  
Clean the duct smoke sensor when the Dirty LED is  
flashing continuously or sooner if conditions warrant.  
Remote Test/Reset Station Dirty Sensor Test  
The test/reset station dirty sensor test checks the test/reset  
station’s ability to initiate a sensor dirty test and indicate  
the results. It must be wired to the controller as shown in  
Fig. 24 and configured to operate the controller’s  
supervision relay. For more information, see “Changing  
sensor dirty test operation.”  
!
CAUTION  
OPERATIONAL TEST HAZARD  
Failure to follow this caution may result in personnel  
and authority concern.  
If the smoke detector is connected to a fire alarm  
system, first notify the proper authorities that the  
detector is undergoing maintenance then disable the  
relevant circuit to avoid generating a false alarm.  
12  
Smoke Detector Controller  
1
TB3  
1
Auxiliary  
equipment  
1. Disconnect power from the duct detector then remove  
the sensor’s cover. (See Fig. 25.)  
+
2
3
14  
HVAC duct  
Sampling  
tube  
SD-TRK4  
Trouble  
Supervision relay  
contacts [3]  
Sensor  
housing  
13  
19  
5
4
1
3
Power  
18 Vdc (  
+)  
Wire must be  
Alarm  
Optic  
plate  
Airflow  
added by installer  
15  
2
Reset/Test  
Retainer  
clip  
18 Vdc (  
)  
2
20  
Optic  
housing  
C08247  
Fig. 24 - Remote Test/Reset Station Connections  
C07305  
Fig. 25 - Sensor Cleaning Diagram  
!
2. Using a vacuum cleaner, clean compressed air, or a  
soft bristle brush, remove loose dirt and debris from  
inside the sensor housing and cover.  
CAUTION  
OPERATIONAL TEST HAZARD  
Use isopropyl alcohol and a lint-free cloth to remove  
dirt and other contaminants from the gasket on the  
sensor’s cover.  
Failure to follow this caution may result in personnel  
and authority concern.  
If the test/reset station’s key switch is left in the  
RESET/TEST position for longer than seven seconds,  
the detector will automatically go into the alarm state  
and activate all automatic alarm responses.  
3. Squeeze the retainer clips on both sides of the optic  
housing then lift the housing away from the printed  
circuit board.  
4. Gently remove dirt and debris from around the optic  
plate and inside the optic housing.  
5. Replace the optic housing and sensor cover.  
6. Connect power to the duct detector then perform a  
sensor alarm test.  
!
CAUTION  
OPERATIONAL TEST HAZARD  
Failure to follow this caution may result in personnel  
and authority concern.  
INDICATORS  
Normal State  
Holding the test magnet to the target area for longer  
than seven seconds will put the detector into the alarm  
state and activate all automatic alarm responses.  
The smoke detector operates in the normal state in the  
absence of any trouble conditions and when its sensing  
chamber is free of smoke. In the normal state, the Power  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LED on both the sensor and the controller are on and all  
other LEDs are off.  
NOTE: All troubles are latched by the duct smoke  
detector. The trouble condition must be cleared and then  
the duct smoke detector must be reset in order to restore it  
to the normal state.  
Alarm State  
The smoke detector enters the alarm state when the  
amount of smoke particulate in the sensor’s sensing  
chamber exceeds the alarm threshold value. (See Table 3.)  
Upon entering the alarm state:  
S The sensor’s Alarm LED and the controller’s Alarm LED  
turn on.  
Resetting Alarm and Trouble Condition Trips:  
Manual reset is required to restore smoke detector systems  
to Normal operation. For installations using two sensors,  
the duct smoke detector does not differentiate which  
sensor signals an alarm or trouble condition. Check each  
sensor for Alarm or Trouble status (indicated by LED).  
Clear the condition that has generated the trip at this  
sensor. Then reset the sensor by pressing and holding the  
reset button (on the side) for 2 seconds. Verify that the  
sensor’s Alarm and Trouble LEDs are now off. At the  
controller, clear its Alarm or Trouble state by pressing and  
holding the manual reset button (on the front cover) for 2  
seconds. Verify that the controller’s Alarm and Trouble  
LEDs are now off. Replace all panels.  
S The contacts on the controller’s two auxiliary relays  
switch positions.  
S The contacts on the controller’s alarm initiation relay  
close.  
S The controller’s remote alarm LED output is activated  
(turned on).  
S The controller’s high impedance multiple fan shutdown  
control line is pulled to ground Trouble state.  
The SuperDuct duct smoke detector enters the trouble  
state under the following conditions:  
S A sensor’s cover is removed and 20 minutes pass before  
Troubleshooting  
Controller’s Trouble LED is On  
1. Check the Trouble LED on each sensor connected to  
the controller. If a sensor’s Trouble LED is on, de-  
termine the cause and make the necessary repairs.  
2. Check the wiring between the sensor and the control-  
ler. If wiring is loose or missing, repair or replace as  
required.  
it is properly secured.  
S A sensor’s environmental compensation limit is reached  
(100% dirty).  
S A wiring fault between a sensor and the controller is  
detected.  
An internal sensor fault is detected upon entering the  
trouble state:  
S The contacts on the controller’s supervisory relay switch  
Controller’s Trouble LED is Flashing  
1. One or both of the sensors is 100% dirty.  
2. Determine which Dirty LED is flashing then clean  
that sensor assembly as described in the detector  
cleaning section.  
positions. (See Fig. 26.)  
S If a sensor trouble, the sensor’s Trouble LED the  
controller’s Trouble LED turn on.  
Sensor’s Trouble LED is On  
S If 100% dirty, the sensor’s Dirty LED turns on and the  
controller’s Trouble LED flashes continuously.  
1. Check the sensor’s Dirty LED. If it is flashing, the  
sensor is dirty and must be cleaned.  
2. Check the sensor’s cover. If it is loose or missing, se-  
cure the cover to the sensor housing.  
S If a wiring fault between a sensor and the controller, the  
controller’s Trouble LED turns on but not the sensor’s.  
3. Replace sensor assembly.  
Trouble  
Sensor’s Power LED is Off  
Alarm  
Power  
1. Check the controller’s Power LED. If it is off, de-  
termine why the controller does not have power and  
make the necessary repairs.  
2. Check the wiring between the sensor and the control-  
ler. If wiring is loose or missing, repair or replace as  
required.  
Test/reset  
switch  
C07298  
Fig. 26 - Controller Assembly  
Table 3 – Detector Indicators  
CONTROL OR INDICATOR  
DESCRIPTION  
Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in  
the normal state.  
Magnetic test/reset switch  
Alarm LED  
Trouble LED  
Indicates the sensor is in the alarm state.  
Indicates the sensor is in the trouble state.  
Indicates the amount of environmental compensation used by the sensor  
(flashing continuously = 100%)  
Dirty LED  
Power LED  
Indicates the sensor is energized.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Controller’s Power LED is Off  
The standard supply fan motor is equipped with internal  
overcurrent and overtemperature protection. Protection  
devices reset automatically.  
1. Make sure the circuit supplying power to the control-  
ler is operational. If not, make sure JP2 and JP3 are  
set correctly on the controller before applying power.  
2. Verify that power is applied to the controller’s supply  
input terminals. If power is not present, replace or re-  
pair wiring as required.  
The High Static option supply fan motor is equipped with  
a pilot-circuit Thermix combination overtemperature/  
overcurrent protection device. This device resets  
automatically. Do not bypass this switch to correct  
trouble. Determine the cause and correct it.  
Remote Test/Reset Station’s Trouble LED Does Not  
flash When Performing a Dirty Test, But the Control-  
ler’s Trouble LED Does  
Condenser Fan Motor Protection  
The condenser fan motor is internally protected against  
overtemperature.  
1. Verify that the remote test/station is wired as shown  
in Fig. 24. Repair or replace loose or missing wiring.  
Relief Device  
2. Configure the sensor dirty test to activate the control-  
ler’s supervision relay. See “Changing sensor dirty  
test operation.”  
A soft solder joint at the suction service access port  
provides pressure relief under abnormal temperature and  
pressure conditions (i.e., fire in building). Protect this  
joint during brazing operations near this joint.  
Sensor’s Trouble LED is On, But the Controller’s  
Trouble LED is OFF  
Remove JP1 on the controller.  
Control Circuit, 24--V  
The control circuit is protected against overcurrent  
conditions by a circuit breaker mounted on control  
transformer TRAN. Reset is manual.  
PROTECTIVE DEVICES  
Compressor Protection  
Overcurrent  
GAS HEATING SYSTEM  
General  
The compressor has internal linebreak motor protection.  
Overtemperature  
The heat exchanger system consists of a gas valve feeding  
multiple inshot burners off a manifold. The burners fire  
into matching primary tubes. The primary tubes discharge  
into combustion plenum where gas flow converges into  
secondary tubes. The secondary tubes exit into the  
induced draft fan wheel inlet. The induced fan wheel  
discharges into a flue passage and flue gases exit out a  
flue hood on the side of the unit. The induced draft fan  
motor includes a Hall Effect sensor circuit that confirms  
adequate wheel speed via the Integrated Gas Control  
(IGC) board. Safety switches include a Rollout Switch (at  
the top of the burner compartment) and a limit switch  
(mounted through the fan deck, over the tubes). (See Fig.  
27 and Fig. 28.)  
The compressor has an internal protector to protect it  
against excessively high discharge gas temperatures.  
High Pressure Switch  
The system is provided with a high pressure switch  
mounted on the discharge line. The switch is  
stem-mounted and brazed into the discharge tube. Trip  
setting is 630 psig +/- 10 psig (4344 +/- 69 kPa) when  
hot. Reset is automatic at 505 psig (3482 kPa).  
Low Pressure Switch  
The system is protected against a loss of charge and low  
evaporator coil loading condition by a low pressure switch  
located on the suction line near the compressor. The  
switch is stem-mounted. Trip setting is 54 psig +/- 5 psig  
(372 +/- 34 kPa). Reset is automatic at 117 +/- 5 psig  
(807 +/- 34 kPa).  
INDUCED-  
DRAFT  
MOTOR  
ROLLOUT  
SWITCH  
MOUNTING  
PLATE  
Evaporator Freeze Protection  
The system is protected against evaporator coil frosting  
and low temperature conditions by a temperature switch  
mounted on the evaporator coil hairpin. Trip setting is  
30_F +/- 5_F (-1_C +/- 3_C). Reset is automatic at 45_F  
(7_C).  
BURNER  
SECTION  
FLUE  
EXHAUST  
VESTIBULE  
PLATE  
INDUCED-  
DRAFT  
MOTOR  
BLOWER  
HOUSING  
MANIFOLD  
PRESSURE  
TAP  
GAS  
VALVE  
Supply (Indoor) Fan Motor Protection  
Disconnect and lockout power when servicing fan motor.  
C06152  
Fig. 27 - Burner Section Details  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 – Liquid Propane Supply Line Pressure Ranges  
Limit Switch  
and Shield  
UNIT MODEL  
48TCD,E,F  
48TCS,R,T  
UNIT SIZE  
MIN  
11.0 in. wg  
(2740 Pa)  
MAX  
13.0 in. wg  
(3240 Pa)  
All  
All  
48TCL,M,N  
NA  
NA  
Manifold pressure for LP fuel use must be adjusted to  
specified range. Follow instructions in the accessory kit to  
make initial readjustment.  
Table 7 – Liquid Propane Manifold Pressure Ranges  
UNIT MODEL  
UNIT SIZE  
HIGH FIRE  
LOW FIRE  
48TCD,S  
48TCE,R  
48TCF,T  
C08284  
10.0 in. wg  
(2490 Pa)  
5.0 in. wg  
(1245 Pa){  
All  
Fig. 28 - Limit Switch Location  
48TCL,  
48TCM,  
48TCN  
Fuel Types and Pressures  
All  
NA  
NA  
Natural Gas — The 48TC unit is factory-equipped for use  
with Natural Gas fuel at elevation under 2000 ft (610 m).  
See section Orifice Replacement for information in  
modifying this unit for installation at elevations above  
2000 ft (610 m).  
NA: Not Available  
{ 3 Phase models only  
Supply Pressure Switch — The LP conversion kit includes  
a supply low pressure switch. The switch contacts (from  
terminal C to terminal NO) will open the gas valve power  
whenever the supply line pressure drops below the  
setpoint. See Fig. 29 and Fig. 30. If the low pressure  
remains open for 15 minutes during a call for heat, the  
IGC circuit will initiate a Ignition Fault (5 flashes)  
lockout. Reset of the low pressure switch is automatic on  
rise in supply line pressure. Reset of the IGC requires a  
recycle of unit power after the low pressure switch has  
closed.  
Gas line pressure entering the unit’s main gas valve must  
be within specified ranges. Adjust unit gas regulator valve  
as required or consult local gas utility.  
Table 4 – Natural Gas Supply Line Pressure Ranges  
UNIT MODEL  
UNIT SIZE  
MIN  
4.0 in. wg  
(996 Pa)  
MAX  
13.0 in. wg  
(3240 Pa)  
48TC  
All  
Manifold pressure is factory-adjusted for NG fuel use.  
Adjust as required to obtain best flame characteristic.  
Table 5 – Natural Gas Manifold Pressure Ranges  
UNIT  
MODEL  
UNIT  
SIZE  
HIGH  
FIRE  
LOW  
FIRE  
RANGE  
48TCD,S  
48TCE,R  
48TCF,T  
3.5 in. wg 1.7 in. wg 2.0---5.0 in. wg (Hi)  
All  
All  
(872 Pa) (423 Pa){  
(498---1245 Pa)  
48TCL  
48TCM  
48TCN  
3.5 in. wg  
NA  
2.0---5.0 in. wg (Hi)  
(498---1245 Pa)  
(872 Pa)  
NA: Not Available  
{ 3 Phase models only  
C08238  
Fig. 29 - LP Low Pressure Switch (Installed)  
Liquid Propane — Accessory packages are available for  
field-installation that will convert the 48TC unit (except  
low NOx model) to operate with Liquid Propane (LP)  
fuels. These kits include new orifice spuds, new springs  
for gas valves and a supply line low pressure switch. See  
section on Orifice Replacement for details on orifice size  
selections.  
LP LPS  
IGC  
BRN  
BRN  
C
NO  
J2-11  
C
MGV  
IGC  
GRA  
Low NOx models include specially-sized orifices and use  
of different flue flow limits and tube baffles. Because of  
these extra features, conversion of these models to LP is  
not recommended.  
J2-12  
TSTAT  
W2  
PNK  
C08285  
Fig. 30 - LP Supply Line Low Pressure Switch Wiring  
Fuel line pressure entering unit gas valve must remain  
within specified range.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
This switch also prevents operation when the propane tank  
level is low which can result in gas with a high  
concentration of impurities, additives, and residues that  
have settled to the bottom of the tank. Operation under  
these conditions can cause harm to the heat exchanger  
system. Contact your fuel supplier if this condition is  
suspected.  
season, inspect blower wheel bi  
proper cleaning frequency.  
                                                                                                                                                            
-monthly to determine  
To access burner section, slide the sliding burner partition  
out of the unit.  
To inspect blower wheel, shine a flashlight into draft hood  
opening. If cleaning is required, remove motor and wheel  
as follows:  
Flue Gas Passageways  
1. Slide burner access panel out.  
2. Remove the 7 screws that attach induced-draft motor  
housing to vestibule plate. (See Fig. 31.)  
3. The blower wheel can be cleaned at this point. If ad-  
ditional cleaning is required, continue with Steps 4  
and 5.  
4. To remove blower from the motor shaft, remove 2  
setscrews.  
5. To remove motor, remove the 4 screws that hold the  
motor to mounting plate. Remove the motor cooling  
fan by removing one setscrew. Then remove nuts that  
hold motor to mounting plate.  
To inspect the flue collector box and upper areas of the  
heat exchanger:  
1. Remove the combustion blower wheel and motor as-  
sembly according to directions in Combustion-Air  
Blower section. See Fig. 31.  
2. Remove the flue cover to inspect the heat exchanger.  
3. Clean all surfaces as required using a wire brush.  
Combustion--Air Blower  
Clean periodically to assure proper airflow and heating  
efficiency. Inspect blower wheel every fall and  
periodically during heating season. For the first heating  
6. To reinstall, reverse the procedure outlined above.  
Regulator  
Gasket  
Heater Tube  
Assembly  
Seal Strips, Sponge Rubber  
Regulator  
Baffle Assembly  
(Low NOx only)  
Retainer  
Support  
Insulation  
Assembly  
Wind Cap Assembly  
(shown inverted,  
as shipped)  
Flue Baffle  
(Low NOx only)  
Inducer Fan-Motor  
Assembly  
Burner Assembly  
C08227  
Fig. 31 - Heat Exchanger Assembly  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Slide the burner tray out of the unit (Fig. 33).  
9. To reinstall, reverse the procedure outlined above.  
Cleaning and Adjustment  
Burners and Igniters  
!
CAUTION  
1. Remove burner rack from unit as described in Re-  
moval and Replacement of Gas Train section, above.  
EQUIPMENT DAMAGE HAZARD  
Failure to follow this caution may result in  
equipment damage.  
2. Inspect burners; if dirty, remove burners from rack.  
(Mark each burner to identify its position before re-  
moving from the rack.)  
3. Use a soft brush to clean burners and cross-over port  
as required.  
When working on gas train, do not hit or plug  
orifice spuds.  
Main Burners  
4. Adjust spark gap. (See Fig. 35 and Fig. 36.)  
5. If factory orifice has been removed, check that each  
orifice is tight at its threads into the manifold pipe  
and that orifice projection does not exceed maximum  
valve. See Fig. 32  
6. Reinstall burners on rack in the same locations as  
factory-installed. (The outside crossover flame re-  
gions of the outermost burners are pinched off to pre-  
vent excessive gas flow from the side of the burner  
assembly. If the pinched crossovers are installed  
between two burners, the flame will not ignite prop-  
erly.)  
To access burners, remove burner access panel and slide  
out burner partition. At the beginning of each heating  
season, inspect for deterioration or blockage due to  
corrosion or other causes. Observe the main burner flames  
and adjust, if necessary.  
Orifice projection — Refer to Fig. 32 for maximum  
projection dimension for orifice face to manifold tube.  
Orifice  
INTEGRATED GAS UNIT  
CONTROLLER (IGC)  
1.00-in  
(25.4 mm)  
RACEWAY  
Manifold  
Pipe  
C08211  
Fig. 32 - Orifice Projection  
Removal and Replacement of Gas Train  
See Fig. 27, Fig. 31 and Fig. 33.  
1. Shut off manual gas valve.  
2. Shut off power to unit.  
HOLE IN END PANEL (HIDDEN)  
3. Slide out burner partition.  
C08454  
4. Disconnect gas piping at unit gas valve.  
Fig. 34 - Unit Control Box/IGC Location  
5. Remove wires connected to gas valve. Mark each  
wire.  
7. Reinstall burner rack as described in Removal and  
Replacement of Gas Train section, above.  
Gas Valve — All three-phase models (except Low NOx)  
are equipped with 2-stage gas valves. Single-phase  
models and all Low NOx models are equipped with  
single-stage gas valves. See Fig. 37 for locations of  
adjustment screws and features on the gas valves.  
To adjust gas valve pressure settings:  
IMPORTANT: Leak check all gas connections including  
the main service connection, gas valve, gas spuds, and  
manifold pipe plug. All leaks must be repaired before  
firing unit.  
C06153  
Fig. 33 - Burner Tray Details  
Check Unit Operation and Make Necessary Adjust-  
ments  
6. Remove igniter wires and sensor wires at the Integ-  
rated Gas Unit Controller (IGC). (See Fig. 34.)  
7. Remove the 2 screws that attach the burner rack to  
the vestibule plate (Fig. 31).  
NOTE: Gas supply pressure at gas valve inlet must be  
within specified ranges for fuel type and unit size. See  
Table 4 and Table 5.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Remove manifold pressure tap plug from manifold  
and connect pressure gauge or manometer. (See Fig.  
33.)  
10. Turn off unit, remove pressure manometer and re-  
place the 1/8 in. pipe fitting on the gas manifold. (See  
Fig. 32.)  
2. Turn on electrical supply.  
Limit Switch  
3. Turn on unit main gas valve.  
Remove blower access panel. Limit switch is located on  
the fan deck. See Fig. 28.  
4. Set room thermostat to call for heat. If unit has two-  
stage gas valve, verify high-stage heat operation be-  
fore attempting to adjust manifold pressure.  
Burner Ignition  
5. When main burners ignite, check all fittings, mani-  
fold, and orifices for leaks.  
6. Adjust high-stage pressure to specified setting by  
turning the plastic adjustment screw clockwise to in-  
crease pressure, counter-clockwise to decrease pres-  
sure.  
7. For Two-Stage Gas Valves set room thermostat to  
call for low-stage heat. Adjust low-stage pressure to  
specified setting.  
Unit is equipped with a direct spark ignition 100% lockout  
system. Integrated Gas Unit Controller (IGC) is located in  
the control box. See Fig. 34. The IGC contains a  
self-diagnostic LED (light-emitting diode). A single LED  
(see Fig. 38) on the IGC provides a visual display of  
operational or sequential problems when the power supply  
is uninterrupted. When a break in power occurs, the IGC  
will be reset (resulting in a loss of fault history) and the  
indoor (evaporator) fan ON/OFF times will be reset. The  
LED error code can be observed through the viewport.  
During servicing refer to the label on the control box  
cover or Table 8 for an explanation of LED error code  
descriptions.  
8. Replace regulator cover screw(s) when finished.  
9. With burner access panel removed, observe unit heat-  
ing operation in both high stage and low stage opera-  
tion if so equipped. Observe burner flames to see if  
they are blue in appearance, and that the flames are  
approximately the same for each burner.  
If lockout occurs, unit may be reset by interrupting power  
supply to unit for at least 5 seconds.  
LOW HEAT  
72,000 BTUH INPUT AND 60,000 BTUH INPUT  
MEDIUM AND HIGH HEAT  
115,000 BTUH INPUT,  
150,000 BTUH INPUT,  
90,000BTUH INPUT AND  
120,000 BTUH INPUT  
C06154  
Fig. 35 - Spark Adjustment (04-07)  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
125,000/90,000 BTUH INPUT  
180,000/120,000 BTUH INPUT  
240,000/180,000 BTUH INPUT  
250,000/200,000 BTUH INPUT  
C08447  
Fig. 36 - Spark Adjustment (08-12)  
Table 8 – LED Error Code Description*  
IMPORTANT: Refer to Troubleshooting Table 13 and  
Table 14 for additional information.  
ERROR CODE  
LED INDICATION  
Orifice Replacement  
DESCRIPTION  
ON  
Normal Operation  
This unit uses orifice type LH32RFnnn (where nnn  
indicates orifice reference size). When replacing unit  
orifices, order the necessary parts via Carrier RCD. See  
Table 10 for available orifice sizes. See Table 11 and  
Table 12 for orifice sizes for Natural Gas and LP fuel  
usage at various elevations above sea level.  
OFF  
Hardware Failure  
1 Flash{  
2 Flashes  
3 Flashes  
4 Flashes  
5 Flashes  
6 Flashes  
7 Flashes  
8 Flashes  
9 Flashes  
Evaporator Fan On/Off Delay Modified  
Limit Switch Fault  
Flame Sense Fault  
4 Consecutive Limit Switch Faults  
Ignition Lockout Fault  
Induced---Draft Motor Fault  
Rollout Switch Fault  
Check that each replacement orifice is tight at its threads  
into the manifold pipe and that orifice projection does not  
exceed maximum value. See Fig. 32.  
Internal Control Fault  
Software Lockout  
LEGEND  
LED --- L ig h t E m it t in g D i o d e  
* . A 3---second pause exists between LED error code flashes. If  
more than one error code exists, all applicable codes will be  
displayed in numerical sequence.  
{
Indicates a code that is not an error. The unit will continue to  
operate when this code is displayed.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2 Stage  
Single Stage  
C08210  
Fig. 37 - Gas Valves  
Red LED-Status  
C08452  
Fig. 38 - Integrated Gas Control (IGC) Board  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 – IGC Connections  
CONNECTION  
PIN NUMBER  
TERMINAL LABEL  
POINT DESCRIPTION  
SENSOR LOCATION  
TYPE OF I/O  
INPUTS  
RT, C  
SS  
Input power from TRAN 1  
Speed sensor  
control box  
gas section  
gas section  
LCTB  
24 VAC  
analog input  
switch input  
24 VAC  
J1, 1-3  
FS, T1  
W
Flame sensor  
Heat stage 1  
J2, 2  
RS  
Rollout switch  
gas section  
fan section  
switch input  
switch input  
switch input  
J2, 5-6  
J2, 7-8  
J2, 9-10  
LS  
Limit switch  
CS  
Centrifugal switch (not used)  
OUTPUTS  
L1, CM  
IFO  
Induced draft combustion motor  
Indoor fan  
gas section  
control box  
gas section  
line VAC  
relay  
J2, 1  
GV  
Gas valve (heat stage 1)  
relay  
J2, 11-12  
Table 10 – Orifice Sizes  
ORIFICE  
CARRIER  
DRILL  
DRILL SIZE  
PART NUMBER  
DIA. (in.)  
0.1285  
0.1250  
0.1200  
0.1160  
0.1130  
0.1110  
0.1100  
0.1065  
0.1040  
0.1015  
0.0995  
0.0980  
0.0960  
0.0935  
0.0890  
0.0860  
0.0820  
0.0810  
0.0785  
0.0760  
0.0730  
0.0700  
0.0670  
0.0635  
0.0595  
0.0550  
0.0520  
0.0465  
0.0430  
0.0420  
#30  
1/8  
LH32RF129  
LH32RF125  
LH32RF120  
LH32RF116  
LH32RF113  
LH32RF111  
LH32RF110  
LH32RF105  
LH32RF104  
LH32RF102  
LH32RF103  
LH32RF098  
LH32RF096  
LH32RF094  
LH32RF089  
LH32RF086  
LH32RF082  
LH32RF080  
LH32RF079  
LH32RF076  
LH32RF073  
LH32RF070  
LH32RF067  
LH32RF065  
LH32RF060  
LH32RF055  
LH32RF052  
LH32RF047  
LH32RF043  
LH32RF042  
#31  
#32  
#33  
#34  
#35  
#36  
#37  
#38  
#39  
#40  
#41  
#42  
#43  
#44  
#45  
#46  
#47  
#48  
#49  
#50  
#51  
#52  
#53  
#54  
#55  
#56  
#57  
#58  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 11 – Altitude Compensation* (A04-A07)  
72,000 BTUH  
Nominal  
115,000 BTUH  
Nominal  
150,000 BTUH  
Nominal  
ELEVATION  
ft (m)  
NG  
LP  
NG  
LP  
NG  
Orifice Size  
†30  
LP  
Orifice Size  
Orifice Size  
Orifice Size  
Orifice Size  
Orifice Size  
1
4
1
3
3
0 --- 2000 (610)  
2000 (610)  
3000 (914)  
33  
51  
33  
35  
35  
36  
36  
37  
38  
39  
50  
51  
51  
51  
51  
52  
52  
52  
46  
1
4
1
4
3
35  
51  
†30  
47  
47  
48  
48  
48  
49  
49  
50  
50  
51  
51  
52  
1
4
1
4
1
3
35  
52  
31  
31  
31  
31  
32  
33  
34  
35  
1
4
1
4
1
3
4000 (1219)  
5000 (1524)  
6000 (1829)  
7000 (2134)  
8000 (2438)  
9000 (2743)  
10000 (3048)  
11000 (3353)  
12000 (3658)  
13000 (3962)  
14000 (4267)  
36  
52  
1
4
1
4
1
3
36  
52  
2
4
2
4
1
3
37  
52  
2
4
2
4
1
3
38  
53  
2
4
2
4
1
3
39  
53  
4
4
1
3
†40  
†41  
†42  
†43  
†43  
53  
†40  
†41  
†42  
†43  
†43  
53  
53  
53  
54  
54  
55  
4
4
1
3
54  
4
4
1
4
54  
36  
37  
38  
4
4
2
4
54  
4
4
2
4
55  
2
2
4
4
44  
†56  
44  
†40  
53  
Table 11 (cont.) - Altitude Compensation* (A08-A12)  
125,000  
BTUH Nominal  
250,000  
180,000, 224,000  
BTUH Nominal  
BTUH Nominal  
ELEVATION  
ft (m)  
NG Orifice  
LP Orifice  
NG Orifice  
LP Orifice  
NG Orifice  
LP Orifice  
Size  
Size  
Size  
†30  
†30  
Size  
46  
47  
47  
48  
48  
48  
49  
49  
50  
50  
51  
51  
52  
Size  
Size  
1
3
3
1
3
0 --- 2000 (610)  
2000 (610)  
3000 (914)  
31  
32  
32  
33  
33  
34  
35  
36  
49  
50  
50  
50  
51  
51  
51  
52  
31  
48  
49  
49  
49  
50  
50  
50  
51  
1
3
3
1
3
32  
1
3
1
3
1
3
31  
31  
31  
31  
32  
33  
34  
35  
32  
1
3
1
3
1
3
4000 (1219)  
5000 (1524)  
6000 (1829)  
7000 (2134)  
8000 (2438)  
9000 (2743)  
10000 (3048)  
11000 (3353)  
12000 (3658)  
13000 (3962)  
14000 (4267)  
33  
1
4
1
3
1
3
33  
1
4
1
3
1
3
34  
1
4
1
3
1
3
35  
1
4
1
3
1
4
36  
2
4
1
3
2
4
37  
38  
39  
52  
52  
53  
37  
51  
52  
52  
2
4
1
3
2
4
38  
2
4
1
4
2
4
36  
37  
38  
39  
4
2
4
4
†41  
†42  
†43  
53  
54  
54  
†41  
†42  
†43  
53  
53  
54  
4
2
4
4
4
4
4
†40  
53  
LEGEND  
NG = Natural Gas  
LP = Liquid Propane  
1 = CRLPELEV001A00  
2 = CRLPELEV002A00  
3 = CRLPELEV003A00  
4 = CRLPELEV004A00  
*
As the height above sea level increases, there is less oxygen  
per cubic ft. of air. Therefore, heat input rate should be reduced  
at higher altitudes.  
{
Not included in kit. May be purchased separately through  
dealer.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 12 – Altitude Compensation* (A04-A06) - Low NOx Units  
60,000, 90,000  
120,000  
BTUH Nominal  
ELEVATION  
ft (m)  
BTUH Nominal  
NG Orifice Size  
LP Orifice Size  
NG Orifice Size  
LP Orifice Size  
2
4
1
1
1
1
1
1
1
2
2
3
0 --- 2000 (610)  
2000 (610)  
3000 (914)  
38  
39  
53  
32  
33  
34  
35  
35  
36  
36  
37  
38  
50  
2
4
4
54  
51  
4
4
†40  
†41  
†41  
†42  
†42  
†43  
†43  
54  
51  
4
4
4000 (1219)  
5000 (1524)  
6000 (1829)  
7000 (2134)  
8000 (2438)  
9000 (2743)  
10000 (3048)  
11000 (3353)  
12000 (3658)  
13000 (3962)  
14000 (4267)  
54  
51  
4
4
54  
51  
4
4
54  
52  
4
4
54  
52  
4
4
55  
52  
4
4
55  
53  
2
4
4
44  
55  
†40  
†41  
†42  
†43  
†43  
53  
2
4
4
44  
55  
53  
2
4
45  
†56  
†56  
†56  
54  
3
4
47  
54  
3
4
48  
55  
LEGEND  
NG = Natural Gas  
LP = Liquid Propane  
1 = CRLPELEV001A00  
*
As the height above sea level increases, there is less oxygen  
per cubic ft. of air. Therefore, heat input rate should be reduced  
at higher altitudes.  
Not included in kit. May be purchased separately through  
dealer.  
2 = CRLPELEV002A00  
3 = CRLPELEV003A00  
4 = CRLPELEV004A00  
{
Minimum heating entering air temperature  
heating is initiated using low entering air temperatures  
with insufficient heating temperature rise.  
When operating on first stage heating, the minimum  
temperature of air entering the dimpled heat exchanger is  
50_F continuous and 45_F intermittent for standard heat  
exchangers and 40_F continuous and 35_F intermittent for  
stainless steel heat exchangers. To operate at lower  
mixed-air temperatures, a field-supplied outdoor-air  
thermostat must be used to initiate both stages of heat  
when the temperature is below the minimum required  
temperature to ensure full fire operation. Wire the  
outdoor-air thermostat OALT (part no. HH22AG106) in  
series with the second stage gas valve. See Fig. 39. Set the  
outdoor-air thermostat at 35_F for stainless steel heat  
exchangers or 45_F for standard heat exchangers. This  
temperature setting will bring on the second stage of heat  
whenever the ambient temperature is below the thermostat  
setpoint. Indoor comfort may be compromised when  
Thermostat  
TH1  
LCTB  
W1  
OALT  
TH2  
W2  
C08442  
Fig. 39 - OATL Connections  
Troubleshooting Heating System  
Refer to Table 13 and Table 14 for additional  
troubleshooting topics.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13 – Heating Service Analysis  
PROBLEM  
CAUSE  
REMEDY  
Check flame ignition and sensor electrode positioning.  
Adjust as needed.  
Misaligned spark electrodes.  
Check gas line for air, purge as necessary. After purging  
gas line of air, allow gas to dissipate for at least 5 minutes  
before attempting to relight unit.  
No gas at main burners.  
Check gas valve.  
Water in gas line.  
No power to furnace.  
Drain water and install drip leg to trap water.  
Check power supply, fuses, wiring, and circuit breaker.  
Burners Will Not Ignite.  
No 24 v power supply to control  
circuit.  
Check transformer. Transformers with internal overcurrent  
protection require a cool down period before resetting.  
Miswired or loose connections.  
Check all wiring and wire nut connections.  
Burned---out heat anticipator in  
thermostat.  
Replace thermostat.  
Broken thermostat wires.  
Dirty air filter.  
Run continuity check. Replace wires, if necessary.  
Clean or replace filter as necessary.  
Check gas pressure at manifold. Clock gas meter for input.  
If too low, increase manifold pressure, or replace with  
correct orifices.  
Gas input to unit too low.  
Unit undersized for application.  
Restricted airflow.  
Replace with proper unit or add additional unit.  
Clean filter, replace filter, or remove any restrictions.  
Use high speed tap, increase fan speed, or install optional  
blower, as suitable for individual units.  
Inadequate Heating.  
Blower speed too low.  
Check rotation of blower, thermostat heat anticipator  
settings, and temperature rise of unit. Adjust as needed.  
Adjust minimum position.  
Limit switch cycles main burners.  
Too much outdoor air.  
Check economizer operation.  
Check all screws around flue outlets and burner  
compartment. Tighten as necessary.  
Cracked heat exchanger.  
Overfired unit — reduce input, change orifices, or adjust  
gas line or manifold pressure.  
Check vent for restriction. Clean as necessary.  
Check orifice to burner alignment.  
Incomplete combustion (lack of  
combustion air) results in:  
Aldehyde odors, CO, sooting  
flame, or floating flame.  
Poor Flame  
Characteristics.  
Burners Will Not Turn  
Off.  
Unit is locked into Heating mode  
for a one minute minimum.  
Wait until mandatory one---minute time period has elapsed  
or reset power to unit.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 14 – IGC Board LED Alarm Codes  
LED  
FLASH  
CODE  
ACTION TAKEN BY  
RESET METHOD  
CONTROL  
DESCRIPTION  
PROBABLE CAUSE  
On  
Normal Operation  
Loss of power to the IGC. Check 5 amp  
fuse on IGC, power to unit, 24V circuit  
breaker, transformer, and wiring to the  
IGC.  
Off  
Hardware Failure  
Limit Switch Fault  
No gas heating.  
High temperature limit switch is open.  
Check the operation of the indoor (evapo-  
rator) fan motor.  
Ensure that the supply-air temperature  
rise is within the range on the unit name-  
plate. Check wiring and limit switch opera-  
tion.  
Gas valve and igniter  
Off.  
Indoor fan and inducer  
On.  
2
Limit switch closed,  
or heat call (W) Off.  
Flashes  
Flame sense normal. The IGC sensed a flame when the gas  
Power reset for LED valve should be closed. Check wiring,  
3
Indoor fan and inducer  
On.  
Flame Sense Fault  
Flashes  
reset.  
flame sensor, and gas valve operation.  
Heat call (W) Off.  
Power reset for LED  
reset.  
4
Four Consecutive Limit  
4 consecutive limit switch faults within a  
single call for heat. See Limit Switch Fault.  
No gas heating.  
Flashes Switch Fault  
Unit unsuccessfully attempted ignition for  
15 minutes. Check igniter and flame sen-  
sor electrode spacing, gaps, etc. Check  
Heat call (W) Off.  
5
Ignition Fault  
Flashes  
No gas heating.  
Power reset for LED flame sense and igniter wiring. Check gas  
reset.  
valve operation and gas supply. Check  
gas valve connections to IGC terminals.  
BRN lead must be on Pin 11.  
Inducer sense On when heat call Off, or  
inducer sense Off when heat call On.  
Check wiring, voltage, and operation of  
IGC motor. Check speed sensor wiring to  
IGC.  
If heat off: no gas  
heating.  
If heat on: gas valve  
Off and inducer On.  
Inducer sense nor-  
mal, or heat call (W)  
Off.  
6
Induced Draft Motor  
Flashes Fault  
Gas valve and igniter  
Rollout switch has opened. Check gas  
valve operation. Check induced-draft  
blower wheel is properly secured to motor  
shaft.  
7
Off.  
Rollout Switch Lockout  
Power reset.  
Power reset.  
Indoor fan and inducer  
On.  
Flashes  
IGC has sensed internal hardware or soft-  
ware error. If fault is not cleared by reset-  
ting 24 v power, replace the IGC.  
8
Internal Control Lockout No gas heating.  
Flashes  
9
Temporary Software  
1 hour auto reset, or Electrical interference is disrupting the  
power reset. IGC software.  
No gas heating.  
Flashes Lockout  
LEGEND  
IGC --- Integrated Gas Unit Control  
LED --- L ig h t --- E m it t in g D i o d e  
NOTES:  
1. There is a 3---second pause between alarm code displays.  
2. If more than one alarm code exists, all applicable alarm codes will be displayed in numerical sequence.  
3. Alarm codes on the IGC will be lost if power to the unit is interrupted.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C08199  
Fig. 40 - PremierLink Controller  
Supply Air Temperature (SAT) Sensor  
On  
PREMIERLINKT CONTROL  
FIOP-equipped 48TC unit, the unit is supplied with a  
supply-air temperature (SAT) sensor (33ZCSENSAT).  
This sensor is a tubular probe type, approx 6-inches (12.7  
mm) in length. It is a nominal 10-k ohm thermistor. See  
Table 15 for temperature-resistance characteristic.  
The PremierLink controller (see Fig. 40) is compatible  
with Carrier Comfort Networkr (CCN) devices. This  
control is designed to allow users the access and ability to  
change factory-defined settings, thus expanding the  
function of the standard unit control board. CCN service  
access tools include System Pilot (TM), Touch Pilot (TM)  
and Service Tool. (Standard tier display tools Navigatort  
and Scrolling Marquee are not suitable for use with latest  
PremierLink controller (Version 2.x).)  
The SAT is factory-wired. The SAT probe is wire-tied to  
the supply-air opening (on the horizontal opening end) in  
its shipping position. Remove the sensor for installation.  
Re-position the sensor in the flange of the supply-air  
opening or in the supply air duct (as required by local  
codes). Drill or punch a 1/2-in. hole in the flange or duct.  
Use two field-supplied, self-drilling screws to secure the  
sensor probe in a horizontal orientation. See Fig. 41.  
The PremierLink control is factory-mounted in the 48TC  
unit’s main control box to the left of the LCTB. Factory  
wiring is completed through harnesses connected to the  
LCTB thermostat. Field connections are made at a  
16-pole terminal block (TB1) located on the bottom shelf  
of the unit control box in front of the PremierLink  
controller The factory-installed PremierLink control  
includes the supply-air temperature (SAT) sensor. The  
outdoor air temperature (OAT) sensor is included in the  
FIOP/accessory EconoMi$er 2 package.  
Refer to Fig. 40 for PremierLink connection locations.  
NOTE:  
Refer to Form 33CS-58SI for complete  
PremierLink configuration, operating sequences and  
troubleshooting information. Have a copy of this manual  
available at unit start-up.  
ROOF  
CURB  
SUPPLY AIR  
TEMPERATURE  
SENSOR  
SUPPLY AIR  
RETURN AIR  
The PremierLink controller requires the use of a Carrier  
electronic thermostat or a CCN connection for time  
broadcast to initiate its internal timeclock. This is  
necessary for broadcast of time of day functions  
(occupied/unoccupied).  
C08200  
Fig. 41 - Typical Mounting Location for Supply Air  
Temperature (SAT) Sensor on Small Rooftop Units  
NOTE: PremierLink controller is shipped in Sensor  
mode. To be used with a thermostat, the PremierLink  
controller must be configured to Thermostat mode. Refer  
to PremierLink Configuration instructions for Operating  
Mode.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 – Thermistor Resistance vs Temperature  
Values for Space Temperature Sensor, Supply Air  
Temperature Sensor, and Outdoor Air Temperature  
Sensor  
Field connections — Field connections for accessory  
sensor and input devices are made at the 16-pole terminal  
block (TB1) located on the control box bottom shelf in  
front of the PremierLink control. Some input devices also  
require a 24-vac signal source; connect at LCTB terminal  
R at “THERMOSTAT” connection strip for this signal  
source. See connections figures on following pages for  
field connection locations (and for continued connections  
at the PremierLink board inputs).  
TEMP  
(C)  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
--- 40  
--- 35  
--- 30  
--- 25  
--- 20  
--- 15  
--- 10  
--- 5  
0
5
10  
15  
20  
--- 40  
--- 31  
--- 22  
--- 13  
--- 4  
5
14  
23  
32  
41  
335,651  
242,195  
176,683  
130,243  
96,974  
72,895  
55,298  
42,315  
32,651  
25,395  
19,903  
15,714  
12,494  
10,000  
8,056  
Table 17 provides a summary of field connections for  
units equipped with Space Sensor. Table 18 provides a  
summary of field connections for units equipped with  
Space Thermostat.  
Space Sensors  
-
The PremierLink controller is  
factory-shipped configured for Space Sensor Mode. A  
Carrier T-55 or T-56 space sensor must be used. T-55  
space temperature sensor provides a signal of space  
temperature to the PremierLink control T-56 provides  
same space temperature signal plus it allows for  
adjustment of space temperature setpoints from the face of  
the sensor by the occupants. See Table 15 for temperature  
versus resistance characteristic on the space sensors.  
50  
59  
68  
77  
25  
30  
86  
35  
95  
6,530  
Connect T-55 - See Fig. 43 for typical T-55 internal  
connections. Connect the T-55 SEN terminals to TB1  
terminals 1 and 3 (see Fig. 44).  
40  
45  
50  
55  
60  
65  
70  
104  
113  
122  
131  
140  
149  
158  
5,325  
4,367  
3,601  
2,985  
2,487  
2,082  
1,752  
1
2
4
5
6
3
NOTE: The sensor must be mounted in the discharge  
airstream downstream of the cooling coil and any heating  
devices. Be sure the probe tip does not come in contact  
with any of the unit’s heater surfaces.  
RED(+)  
WHT(GND)  
CCN COM  
BLK(-)  
SEN  
SW1  
BRN (GND)  
BLU (SPT)  
SENSOR WIRING  
Outdoor Air Temperature (OAT) Sensor — The OAT is  
factory-mounted in the EconoMi$er  
2
(FIOP or  
accessory). It is a nominal 10k ohm thermistor attached to  
an eyelet mounting ring. See Table 15 for  
temperature-resistance characteristic.  
EconoMi$er 2 — The PremierLink control is used with  
EconoMi$er 2 (option or accessory) for outdoor air  
management. The damper position is controlled directly  
by the PremierLink control; EconoMi$er 2 has no internal  
logic device.  
C08201  
Fig. 43 - T-55 Space Temperature Sensor Wiring  
TB1  
1
PL  
Outdoor air management functions can be enhanced with  
field-installation of these accessory control devices:  
SEN  
SEN  
J6-7  
Enthalpy control (outdoor air or differential sensors)  
Space CO2 sensor  
J6-6  
3
C08212  
Outdoor air CO2 sensor  
Fig. 44 - PremierLink T-55 Sensor  
Refer to Table 16 for accessory part numbers.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 16 – PremierLink Sensor Usage  
OUTDOOR AIR  
TEMPERATURE  
SENSOR  
RETURN AIR  
TEMPERATURE  
SENSOR  
OUTDOOR AIR  
ENTHALPY SENSOR  
RETURN AIR  
ENTHALPY SENSOR  
APPLICATION  
Differential Dry Bulb  
Temperature with  
PremierLink  
(PremierLink requires  
4---20 mA Actuator)  
Single Enthalpy with  
PremierLink  
(PremierLink requires  
4 --- 20m A A ctuator)  
Differential Enthalpy  
with PremierLink  
(PremierLink requires  
4 --- 20m A A ctuator)  
R eq uired ---  
33ZCT55SPT  
or equivalent  
I ncluded ---  
---  
---  
---  
CRTEMPSN001A00  
R eq uires ---  
HH57AC077  
or equivalent  
I ncluded ---  
Not Used  
---  
---  
R eq uires ---  
HH57AC077  
or equivalent  
Requires ---  
HH57AC078  
or equivalent  
I ncluded ---  
Not Used  
NOTES:  
CO Sensors (Optional):  
2
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.  
33ZCASPCO2 --- Aspirator box used for duct---mounted CO room sensor.  
2
33ZCT55CO2 --- Space temperature and CO room sensor with override.  
2
33ZCT56CO2 --- Space temperature and CO room sensor with override and setpoint.  
2
Table 17 – Space Sensor Mode  
TB1 TERMINAL  
FIELD CONNECTION  
T55---SEN/T56---SEN  
RMTOCC  
T55---SEN/T56---SEN  
CMPSAFE  
INPUT SIGNAL  
1
2
3
4
5
6
7
Analog (10k thermistor)  
Discrete, 24VAC  
Analog (10k thermistor)  
Discrete, 24VAC  
Analog (10k thermistor)  
Discrete, 24VAC  
Analog, 24VDC  
T56---SET  
FSD  
LOOP---PWR  
8
9
SPS  
IAQ---SEN  
FILTER  
Discrete, 24VAC  
Analog, 4---20mA  
Discrete, 24VAC  
Analog, 4---20mA  
Digital, , 5VDC  
Analog, 4---20mA  
Digital, 5VDC  
10  
11  
12  
13  
14  
15  
16  
I A Q --- CO M /O A Q --- CO M /R H --- CO M  
CCN + (RED)  
O A Q --- S E N /R H --- S E N  
CCN Gnd (WHT)  
AUX OUT(Power Exhaust)  
CCN --- (BLK)  
(Output)Discrete 24VAC  
Digital, 5VDC  
LEGEND:  
T55  
--- Space Temperature Sensor  
--- Space Temperature Sensor  
F S D  
IAQ  
--- F ir e S h u t d o w n  
--- Indoor Air Quality (CO )  
T56  
2
CCN  
--- Carrier Comfort Network (communication bus)  
OAQ  
--- Outdoor Air Quality (CO )  
2
CMPSAFE  
FILTER  
--- Compressor Safety  
--- Dirty Filter Switch  
RH  
SFS  
--- Relative Humidity  
--- Supply Fan Status  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 18 – Thermostat Mode  
TB1 TERMINAL  
FIELD CONNECTION  
INPUT SIGNAL  
Analog (10k thermistor)  
Discrete, 24VAC  
1
2
RAT SEN  
G
3
4
RAT SEN  
Y1  
Analog (10k thermistor)  
Discrete, 24VAC  
5
6
7
8
Y2  
LOOP---PWR  
W1  
I A Q --- S E N  
Discrete, 24VAC  
Analog, 24VDC  
Discrete, 24VAC  
A nalog, 4 --- 20m A  
Discrete, 24VAC  
A nalog, 4 --- 20m A  
Digital, 5VDC  
9
10  
11  
12  
13  
14  
15  
16  
W2  
I A Q --- CO M /O A Q --- CO M /R H --- CO M  
CCN + (RED)  
O A Q --- S E N /R H --- S E N  
CCN Gnd (WHT)  
AUX OUT (Power Exhaust)  
CCN --- (BLK)  
A nalog, 4 --- 20m A  
Digital, 5VDC  
(Output) Discrete 24VAC  
Digital, 5VDC  
LEGEND:  
CCN  
---  
---  
---  
---  
---  
Carrier Comfort Network (communication bus)  
T h e r m o st a t Fa n  
RH  
W1  
W2  
Y1  
---  
---  
---  
---  
---  
Relative Humidity  
G
Thermostat Heat Stage 1  
Thermostat Heat Stage 2  
Thermostat Cool Stage 1  
Thermostat Cool Stage 2  
IAQ  
OAQ  
RAT  
Indoor Air Quality (CO )  
2
Outdoor Air Quality (CO )  
2
Return Air Temperature  
Y2  
Connect T-56  
-
See Fig. 45 for T-56 internal  
Connect Thermostat — A 7-wire thermostat connection  
requires a 24-v power source and a common connection.  
Use the R and C terminals on the LCTB’s THERMOSTAT  
connection strip for these. Connect the thermostat’s Y1,  
Y2, W1, W2 and G terminals to PremierLink TB1 as  
shown in Fig. 47.  
connections. Install a jumper between SEN and SET  
terminals as illustrated. Connect T-56 terminals to TB1  
terminals 1, 3 and 5 (see Fig. 46).  
LCTB  
SPACE  
THERMOSTAT  
THERMOSTAT  
1
2
4
5
6
3
RED(+)  
R
TB1  
2
R
WHT(GND)  
CCN COM  
BLK(-)  
PL  
J4-12  
SET  
SEN  
G
Y1  
Y2  
W1  
W2  
C
SW1  
BLK  
(T56)  
BRN (GND)  
BLU (SPT)  
SENSOR WIRING  
J4-10  
J4-8  
J4-6  
4
6
JUMPER  
TERMINALS  
AS SHOWN  
8
J4-4  
10  
C
LCTB  
THERMOSTAT  
Cool  
Warm  
C08202  
C08119  
Fig. 45 - T-56 Internal Connections  
Fig. 47 - Space Thermostat Connections  
TB1  
1
PL  
If the 48TC unit has an economizer system and  
free-cooling operation is required, a sensor representing  
Return Air Temperature must also be connected  
(field-supplied and installed). This sensor may be a T-55  
Space Sensor (see Fig. 43) installed in the space or in the  
return duct, or it may be sensor PNO 33ZCSENSAT,  
installed in the return duct. Connect this sensor to TB1-1  
and TB1-3 per Fig. 44. Temperature-resistance  
characteristic is found in Table 15.  
SEN  
SEN  
J6-7  
PL  
TB1  
3
J6-6  
Jumper  
SET  
SET  
J6-5  
5
C08213  
Fig. 46 - PremierLink T-56 Sensor  
Configure the unit for Thermostat Mode — Connect to the  
CCN bus using a CCN service tool and navigate to  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PremierLink Configuration screen for Operating Mode.  
Default setting is Sensor Mode (value 1). Change the  
value to 0 to reconfigure the controller for Thermostat  
Mode.  
return air sensor is wired to the enthalpy controller  
(HH57AC077). See Fig. 49.  
ENTHALPY CONTROLLER  
(OUTDOOR  
AIR  
ENTHALPY  
SENSOR)  
S
+
RED  
BRN  
When the PremierLink is configured for Thermostat  
Mode, these functions are not available: Fire Shutdown  
(FSD), Remote Occupied (RMTOCC), Compressor Safety  
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure  
Switch (FILTER).  
B
TR  
SO  
TR1  
BLK  
RED  
C
D
A
+
S
+
(RETURN AIR  
ENTHALPY  
SENSOR)  
+
3
1
SR  
2
GRAY/ORN  
GRAY/RED  
Economizer controls —  
WIRE HARNESS  
IN UNIT  
LED  
Outdoor Air Enthalpy Control (PNO HH57AC077) -  
NOTES:  
1. Remove factory-installed jumper across SR and + before connecting  
wires from return air sensor.  
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3  
close on low outdoor air enthalpy relative to indoor air enthalpy.  
3. Remove sensor mounted on back of control and locate in outside air-  
stream.  
The enthalpy control (HH57AC077) is available as a  
field-installed accessory to be used with the EconoMi$er2  
damper system. The outdoor air enthalpy sensor is part of  
the enthalpy control. (The separate field-installed  
accessory return air enthalpy sensor (HH57AC078) is  
required for differential enthalpy control. See below.)  
C06019  
Fig. 49 - Outside and Return Air Enthalpy Sensor  
Wiring  
Locate the enthalpy control in the economizer hood.  
Locate two GRA leads in the factory harness and connect  
these leads to enthalpy control sensors 2 and 3. See Fig.  
48. Connect the enthalpy control power input terminals to  
economizer actuator power leads RED (connect to TR)  
and BLK (connect to TR1).  
To wire the return air enthalpy sensor, perform the  
following:  
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable  
to connect the return air enthalpy sensor to the enthal-  
py controller.  
2. At the enthalpy control remove the factory-installed  
resistor from the (SR) and (+) terminals.  
LCTB  
ECON  
Enthalpy  
Switch  
3. Connect the field-supplied RED wire to (+) spade  
connector on the return air enthalpy sensor and the  
(SR+) terminal on the enthalpy controller. Connect  
the BLK wire to (S) spade connector on the return air  
enthalpy sensor and the (SR) terminal on the enthalpy  
controller.  
6
7
2
3
GRA  
GRA  
NOTE: The enthalpy control must be set to the “D”  
setting for differential enthalpy control to work properly.  
Factory Wiring Harness  
C08218  
The enthalpy control receives the indoor and return  
enthalpy from the outdoor and return air enthalpy sensors  
Fig. 48 - Enthalpy Switch (HH57AC077) Connections  
and provides  
a
dry contact switch input to the  
The outdoor enthalpy changeover setpoint is set at the  
enthalpy controller.  
PremierLink controller. A closed contact indicates that  
outside air is preferred to the return air. An open contact  
indicates that the economizer should remain at minimum  
position.  
The enthalpy control receives the outdoor air enthalpy  
from the outdoor air enthalpy sensor and provides a dry  
contact switch input to the PremierLink controller. A  
closed contact indicates that outside air is preferred to the  
return air. An open contact indicates that the economizer  
should remain at minimum position.  
Indoor Air Quality (CO2 sensor) — The indoor air quality  
sensor accessory monitors space carbon dioxide (CO2)  
levels. This information is used to monitor IAQ levels.  
Several types of sensors are available, for wall mounting  
in the space or in return duct, with and without LCD  
display, and in combination with space temperature  
sensors. Sensors use infrared technology to measure the  
levels of CO2 present in the space air.  
Differential Enthalpy Control — Differential enthalpy  
control is provided by sensing and comparing the outside  
air and return air enthalpy conditions. Install the outdoor  
air enthalpy control as described above. Add and install a  
return air enthalpy sensor.  
The CO2 sensors are all factory set for a range of 0 to  
2000 ppm and a linear mA output of 4 to 20. Refer to the  
instructions supplied with the CO2 sensor for electrical  
Return Air Enthalpy Sensor — Mount the return-air  
enthalpy sensor (HH57AC078) in the return-air duct. The  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
requirements and terminal locations. See Fig. 50 for  
typical CO2 sensor wiring schematic.  
Refer to Form 33CS-58SI, PremierLink Installation,  
Start-up, and Configuration Instructions, for detailed  
configuration information  
                                                                                                                                             
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus  
weatherproof enclosure) — The outdoor air CO2 sensor is  
designed to monitor carbon dioxide (CO2) levels in the  
outside ventilation air and interface with the ventilation  
damper in an HVAC system. The OAQ sensor is packaged  
with an outdoor cover. See Fig. 52. The outdoor air CO2  
sensor must be located in the economizer outside air hood.  
+ 0-10VDC  
-
SIG COM (J4-6)  
4-20mA (J4-5)  
+
ALARM  
NC  
COM RELAY  
}
NO CONTACTS  
24 VAC  
OR  
24 VDC  
H G  
+
-
2 1  
5 4 3 2 1  
8 7 6  
C07134  
Fig. 50 - Indoor/Outdoor Air Quality (CO2) Sensor  
(33ZCSENCO2) - Typical Wiring Diagram  
COVER REMOVED  
SIDE VIEW  
To accurately monitor the quality of the air in the  
conditioned air space, locate the sensor near a return-air  
grille (if present) so it senses the concentration of CO2  
leaving the space. The sensor should be mounted in a  
location to avoid direct breath contact.  
C07135  
Fig. 52 - Outdoor Air Quality Sensor Cover  
Wiring the Outdoor Air CO2 Sensor — A dedicated power  
supply is required for this sensor. A two-wire cable is  
required to wire the dedicated power supply for the sensor.  
The two wires should be connected to the power supply  
and terminals 1 and 2.  
Do not mount the IAQ sensor in drafty areas such as near  
supply ducts, open windows, fans, or over heat sources.  
Allow at least 3 ft (0.9 m) between the sensor and any  
corner. Avoid mounting the sensor where it is influenced  
by the supply air; the sensor gives inaccurate readings if  
the supply air is blown directly onto the sensor or if the  
supply air does not have a chance to mix with the room air  
before it is drawn into the return airstream.  
To connect the sensor to the control, identify the positive  
(4 to 20 mA) and ground (SIG COM) terminals on the  
OAQ sensor. See Fig. 50. Connect the 4 to 20 mA  
terminal to 48TC’s terminal TB1-11. Connect the SIG  
COM terminal to 48TC’s terminal TB1-13. See Fig. 53.  
Wiring the Indoor Air Quality Sensor —  
OAQ Sensor/RH Sensor  
For each sensor, use two 2-conductor 18 AWG (American  
Wire Gage) twisted-pair cables (unshielded) to connect  
the separate isolated 24 vac power source to the sensor  
and to connect the sensor to the control board terminals.  
TB1  
13  
PL  
J5-2  
SEN  
TB1  
11  
COM  
J5-3  
24 VAC  
To connect the sensor to the control, identify the positive  
(4 to 20 mA) and ground (SIG COM) terminals on the  
sensor. See Fig. 50. Connect the 4-20 mA terminal to  
terminal TB1-9 and connect the SIG COM terminal to  
terminal TB1-7. See Fig. 51.  
C08275  
Fig. 53 - Outdoor CO2 Sensor Connections  
Refer to Form 33CS-58SI, PremierLink Installation,  
Start-up, and Configuration Instructions, for detailed  
configuration information.  
IAQ Sensor  
TB1  
9
PL  
J5-5  
SEN  
Smoke Detector/Fire Shutdown (FSD) — This function is  
available only when PremierLink is configured for  
(Space) Sensor Mode. The unit is factory-wired for  
PremierLink FSD operation when PremierLink is  
factory-installed.  
TB1  
7
COM  
J5-6  
24 VAC  
C08274  
Fig. 51 - Indoor CO2 Sensor (33ZCSENCO2)  
Connections  
On 48TC units equipped with factory-installed Smoke  
Detector(s), the smoke detector controller implements the  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fan (Pressure) Switch (NO, close on rise in pressure)  
unit shutdown through its NC contact set connected to the  
unit’s LCTB input. The FSD function is initiated via the  
smoke detector’s Alarm NO contact set. The PremierLink  
communicates the smoke detector’s tripped status to the  
CCN building control. See Fig. 23 for unit smoke detector  
wiring.  
LCTB  
Thermostat  
R
TB1  
8
PL  
J4-6  
Alarm state is reset when the smoke detector alarm  
condition is cleared and reset at the smoke detector in the  
unit.  
C08118  
Fig. 55 - PremierLink Wiring Fan Pressure Switch  
Connection  
Filter Status Switch — This function is available only  
when PremierLink is configured for (Space) Sensor Mode.  
Remote Occupied Switch — The PremierLink control  
permits a remote timeclock to override the control’s  
on-board occupancy schedule and place the unit into  
Occupied mode. This function may also provide a “Door  
Switch” time delay function that will terminate cooling  
and heating functions after a 2-20 minute delay.  
PremierLink control can monitor return filter status in two  
ways: By monitoring a field-supplied/installed filter  
pressure switch or via supply fan runtime hours.  
Using switch input: Install the dirty filter pressure switch  
according to switch manufacturer’s instructions, to  
measure pressure drop across the unit’s return filters.  
Connect one side of the switch’s NO contact set to  
LCTB’s THERMOSTAT-R terminal. Connect the other  
side of the NO contact set to TB1-10. Setpoint for Dirty  
Filter is set at the switch. See Fig. 54.  
Connect one side of the NO contact set on the timeclock  
to LCTB’s THERMOSTAT-R terminal. Connect the other  
side of the timeclock contact to the unit’s TB1-2 terminal.  
LCTB  
Remote Occupied  
Thermostat  
R
Filter Switch (NO, close on rising pressure (high drop))  
Time Clock  
TB1  
2
PL  
J4-12  
LCTB  
Thermostat  
C08214  
R
Fig. 56 - PremierLink Wiring Remote Occupied  
TB1  
10  
PL  
J4-4  
Refer to Form 33CS-58SI for additional information on  
configuring the PremierLink control for Door Switch  
timer function.  
C08216  
Fig. 54 - PremierLink Filter Switch Connection  
Power Exhaust (output) - Connect the accessory Power  
Exhaust contactor coils(s) per Fig. 57.  
When the filter switch’s NO contact set closes as filter  
pressure drop increases (indicating dirt-laden filters), the  
input signal to PremierLink causes the filter status point to  
read “DIRTY”.  
Power Exhaust  
TB1  
PL  
15  
J8-3  
PEC  
TAN  
LCTB  
THERMOSTAT  
C
Using Filter Timer Hours: Refer to Form 33CS-58SI for  
instructions on using the PremierLink Configuration  
screens and on unit alarm sequence.  
GRA  
C08120  
Supply Fan Status Switch — The PremierLink control can  
Fig. 57 - PremierLink Power Exhaust Output  
Connection  
monitor  
supply  
fan  
operation  
through  
a
field-supplied/installed differential pressure switch. This  
sequence will prevent (or interrupt) operation of unit  
cooling, heating and economizer functions until the  
pressure switch contacts are closed indicating proper  
supply fan operation.  
Space Relative Humidity Sensor — The RH sensor is not  
used with 48TC models at this time.  
CCN Communication Bus — The PremierLink controller  
connects to the bus in a daisy chain arrangement.  
Negative pins on each component must be connected to  
respective negative pins, and likewise, positive pins on  
each component must be connected to respective positive  
pins. The controller signal pins must be wired to the signal  
ground pins. Wiring connections for CCN must be made  
at the 3-pin plug.  
Install the differential pressure switch in the supply fan  
section according to switch manufacturer’s instructions.  
Arrange the switch contact to be open on no flow and to  
close as pressure rises indicating fan operation.  
Connect one side of the switch’s NO contact set to  
LCTB’s THERMOSTAT-R terminal. Connect the other  
side of the NO contact set to TB1-8. Setpoint for Supply  
Fan Status is set at the switch. See Fig. 55.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RTU-MP CONTROL SYSTEM  
                                                                                                            
At any baud (9600, 19200, 38400 baud), the number of  
controllers is limited to 239 devices maximum. Bus length  
may not exceed 4000 ft, with no more than 60 total  
devices on any 1000-ft section. Optically isolated RS-485  
repeaters are required every 1000 ft.  
Connect the CCN (+) lead (typically RED) to the unit s  
TB1-12 terminal. Connect the CCN (ground) lead  
(typically WHT) to the unit’s TB1-14 terminal. Connect  
the CCN (-) lead (typically BLK) to the unit’s TB1-16  
terminal. See Fig. 58.  
NOTE: Carrier device default is 9600 band.  
CCN Bus  
TB1  
12  
COMMUNICATION BUS WIRE SPECIFICATIONS —  
The CCN Communication Bus wiring is field-supplied  
and field-installed. It consists of shielded 3-conductor  
cable with drain (ground) wire. The cable selected must  
be identical to the CCN Communication Bus wire used for  
the entire network.  
PL  
J2-1  
+ (RED)  
TB1  
14  
GND (WHT)  
J2-2  
TB1  
16  
– (BLK)  
J2-3  
See Table 19 for recommended cable.  
C08276  
Fig. 58 - PremierLink CCN Bus Connections  
Table 19 – Recommended Cables  
MANUFACTURER  
Alpha  
CABLE PART NO.  
2413 or 5463  
A22503  
American  
Belden  
Columbia  
The RTU-MP controller, see Fig. 59, provides expanded  
stand-alone operation of the HVAC system plus  
connection and control through communication with  
several Building Automation Systems (BAS) through  
popular third-party network systems. The available  
network systems are BACnet MP/TP, Modbus and  
Johnson J2. Communication with LonWorks is also  
possible by adding an accessory interface card to the  
RTU-MP. Selection of the communication protocol and  
baud rate are made at on-board DIP switches.  
8772  
02525  
NOTE: Conductors and drain wire must be at least 20  
AWG, stranded, and tinned copper. Individual conductors  
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or  
polyethylene. An aluminum/polyester 100% foil shield  
and an outer jacket of PVC, PVC/nylon, chrome vinyl, or  
Teflon with a minimum operating temperature range of  
-20 C to 60 C is required. Do not run communication wire  
in the same conduit as or next to any AC voltage wiring.  
Carrier’s diagnostic display tools BACviewer6 Handheld  
and Virtual BACview (loaded on a portable PC) must be  
used with the RTU-MP controller. Connection to the  
RTU-MP board is at the J12 access port, see Fig. 59.  
The communication bus shields must be tied together at  
each system element. If the communication bus is entirely  
within one building, the resulting continuous shield must  
be connected to ground at only one single point. If the  
communication bus cable exits from one building and  
enters another building, the shields must be connected to  
the grounds at a lightning suppressor in each building (one  
point only).  
The RTU-MP control is factory-mounted in the 48TC  
unit’s main control box, to the left of the LCTB. See Fig.  
60. Factory wiring is completed through harnesses  
connected to the LCTB. Field connections for RTU-MP  
sensors will be made at the Phoenix connectors on the  
RTU-MP board. The factory-installed RTU-MP control  
includes the supply-air temperature (SAT) sensor. The  
outdoor air temperature (OAT) sensor is included in the  
FIOP/accessory EconoMi$er 2 package.  
Connecting CCN bus:  
NOTE: When connecting the communication bus cable,  
a
color code system for the entire network is  
recommended to simplify installation and checkout. See  
Table 20 for the recommended color code.  
Refer to Table 21, RTU-MP Controller Inputs and Outputs  
for locations of all connections to the RTU-MP board.  
Table 20 – Color Code Recommendations  
CCN BUS WIRE  
COLOR  
CCN PLUG PIN  
NUMBER  
SIGNAL TYPE  
+
Ground  
---  
Red  
White  
Black  
1
2
3
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C07129  
Fig. 59 - RTU-MP Multi-Protocol Control Board  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
44  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 21 – RTU-MP Controller Inputs and Outputs  
BACnet OBJECT  
TYPE OF I/O  
NAME  
CONNECTION PIN  
NUMBERS  
POINT NAME  
INPUTS  
Space Temperature Sensor  
Supply Air Temperature  
Local Outside Air Temperature Sensor  
Space Temperature Offset Pot  
Indoor Air Quality  
Outdoor Air Quality  
Safety Chain Feedback  
Compressor Safety  
sptsens  
sat  
oatsens  
sptopot  
iaq  
oaq  
safety  
compstat  
firedown  
enthalpy  
humstat  
AI (10K Thermistor)  
AI (10K Thermistor)  
AI (10K Thermistor)  
AI (100K Potentiometer)  
A I (4 --- 20 m a)  
J 20 --- 1, 2  
J 2 --- 1, 2  
J 2 --- 3, 4  
J 20 --- 3  
J 4 --- 2, 3  
J 4 --- 5, 6  
J 1 --- 9  
A I (4 --- 20 m a)  
DI (24 VAC)  
DI (24 VAC)  
DI (24 VAC)  
DI (24 VAC)  
DI (24 VAC)  
J 1 --- 2  
Fire Shutdown  
Enthalpy Switch  
Humidistat Input Status  
J 1 --- 10  
J 2 --- 6, 7  
J 5 --- 7, 8  
CONFIGURABLE INPUTS*  
Space Relative Humidity  
Outside Air Relative Humidity  
Supply Fan Status  
Filter Status  
Remote Occupancy Input  
sprh  
oarh  
fanstat  
filtstat  
remocc  
OUTPUTS  
econocmd  
A I (4 --- 20 m a)  
A I (4 --- 20 m a)  
DI (24 VAC)  
DI (24 VAC)  
DI (24 VAC)  
J4---2,3 or J4---5,6  
J 5 --- 1, 2 or J 5 --- 3, 4 or  
J5 5,6 or J5---7,8  
Economizer Commanded Position  
Supply Fan Relay State  
4 --- 20m a  
J 2 --- 5  
J 1 --- 4  
J 1 --- 8  
J 1 --- 7  
J 1 --- 6  
J 1 --- 5  
J 11 --- 3  
J 11 --- 7, 8  
sf  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC , 1A)  
DO Relay (24VAC, 1A)  
Compressor 1 Relay State  
Compressor 2 Relay State  
Heat Stage 1 Relay State  
Heat Stage 2 Relay State  
Power Exhaust Relay State  
Dehumidification Relay State  
comp_1  
comp_2  
heat_1  
heat_2  
aux_2  
humizer  
LEGEND  
AI --- A n a lo g In p u t  
AO --- A n a lo g O u t p u t  
DI --- D iscr e t e In p u t  
DO --- Discrete Output  
*
These inputs (if installed) take the place of the default input on the specific channel according to schematic.  
Pa r a lle l p in s J 5 --- 1 = J 2 --- 6 , J 5 --- 3 = J 1 --- 1 0 , J 5 --- 5 = J 1 --- 2 a r e u se d f o r f ie ld --- in st a lla t io n .  
Refer to the input configuration and accessory sections for more detail.  
NOTE: Refer to Form 48-50H-T-2T for complete  
configuration of RTU-MP, operating sequences and  
troubleshooting information. Refer to RTU-MP 3rd Party  
Integration Guide for details on configuration and  
troubleshooting of connected networks. Have a copy of  
these manuals available at unit start-up.  
Use two field-supplied, self-drilling screws to secure the  
sensor probe in a horizontal orientation. See Fig. 41.  
Outdoor Air Temperature (OAT) Sensor - The OAT is  
factory-mounted in the EconoMi$er  
2
(FIOP or  
accessory). It is a nominal 10k ohm thermistor attached to  
an eyelet mounting ring. See Table 15 for  
temperature-resistance characteristic.  
The RTU-MP controller requires the use of a Carrier  
space sensor. A standard thermostat cannot be used with  
the RTU-MP system.  
EconoMi$er 2 - The RTU-MP control is used with  
EconoMi$er2 (option or accessory) for outdoor air  
management. The damper position is controlled directly  
by the RTU-MP control; EconoMi$er 2 has no internal  
logic device.  
Supply Air Temperature (SAT) Sensor  
-
On  
FIOP-equipped 48TC unit, the unit is supplied with a  
supply-air temperature (SAT) sensor (33ZCSENSAT).  
This sensor is a tubular probe type, approx 6-inches (12.7  
mm) in length. It is a nominal 10-k ohm thermistor. See  
Table 15 for temperature-resistance characteristic.  
Outdoor air management functions can be enhanced with  
field-installation of these accessory control devices:  
Enthalpy control (outdoor air or differential sensors)  
Space CO2 sensor  
Outdoor air CO2 sensor  
The SAT is factory-wired. The SAT probe is wire-tied to  
the supply-air opening (on the horizontal opening end) in  
its shipping position. Remove the sensor for installation.  
Re-position the sensor in the flange of the supply-air  
opening or in the supply air duct (as required by local  
codes). Drill or punch a 1/2-in. hole in the flange or duct.  
Field Connections - Field connections for accessory  
sensors and input devices are made the RTU-MP, at plugs  
J1, J2, J4, J5, J11 and J20. All field control wiring that  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
connects to the RTU-MP must be routed through the  
raceway built into the corner post as shown in Fig. 34.  
The raceway provides the UL required clearance between  
high- and low-voltage wiring. Pass the control wires  
through the hole provided in the corner post, then feed the  
wires thorough the raceway to the RTU-MP. Connect to  
the wires to the removable Phoenix connectors and then  
reconnect the connectors to the board.  
terminal (BRN) to J20  
or BLK) to J20-3.  
                                                                                                                                           
-2. Connect the SET terminal (STO  
BRN (COM)  
BLK (STO)  
BLU (SPT)  
SENSOR  
WIRING  
Space Temperature (SPT) Sensors  
OR  
SET SEN  
A field-supplied Carrier space temperature sensor is  
required with the RTU-MP to monitor space temperature.  
There are 3 sensors available for this application:  
OPB COM- PWR+  
S 33ZCT55SPT, space temperature sensor with override  
button  
S 33ZCT56SPT, space temperature sensor with override  
button and setpoint adjustment  
POWER  
WIRING  
24 VAC  
NOTE: Must use a separate isolated transformer.  
S 33ZCT59SPT, space temperature sensor with LCD  
(liquid crystal display) screen, override button, and  
setpoint adjustment  
Use 20 gauge wire to connect the sensor to the controller.  
The wire is suitable for distances of up to 500 ft. Use a  
three-conductor shielded cable for the sensor and setpoint  
adjustment connections. If the setpoint adjustment  
(slidebar) is not required, then an unshielded, 18 or 20  
gauge, two-conductor, twisted pair cable may be used.  
C07132  
Fig. 63 - Space Temperature Sensor Typical Wiring  
(33ZCT59SPT)  
Economizer controls —  
Connect T-55 - See Fig. 43 for typical T-55 internal  
connections. Connect the T-55 SEN terminals to  
RTU-MP J20-1 and J20-2. See Fig. 61.  
Outdoor Air Enthalpy Control (PNO HH57AC077) -  
The enthalpy control (HH57AC077) is available as a  
field-installed accessory to be used with the EconoMi$er2  
damper system. The outdoor air enthalpy sensor is part of  
the enthalpy control. (The separate field-installed  
accessory return air enthalpy sensor (HH57AC078) is  
required for differential enthalpy control. See below.)  
J20-1  
SEN  
J20-2  
SEN  
Locate the enthalpy control in the economizer hood.  
Locate two GRA leads in the factory harness and connect  
these leads to enthalpy control sensors 2 and 3. See Fig.  
48. Connect the enthalpy control power input terminals to  
economizer actuator power leads RED (connect to TR)  
and BLK (connect to TR1).  
C08460  
Fig. 61 - RTU-MP T-55 Sensor Connections  
Connect T-56 See Fig. 45 for T-56 internal  
-
connections. Install a jumper between SEN and SET  
terminals as illustrated. Connect T-56 terminals to  
RTU-MP J20-1, J20-2 and J20-3 per Fig. 62.  
The outdoor enthalpy changeover setpoint is set at the  
enthalpy controller.  
SEN  
J20-1  
The enthalpy control receives the outdoor air enthalpy  
from the outdoor air enthalpy sensor and provides a dry  
contact switch input to the RTU-MP controller. A closed  
contact indicates that outside air is preferred to the return  
air. An open contact indicates that the economizer should  
remain at minimum position.  
SEN  
J20-2  
Jumper  
SET  
SET  
Differential Enthalpy Control — Differential enthalpy  
control is provided by sensing and comparing the outside  
air and return air enthalpy conditions. Install the outdoor  
air enthalpy control as described above. Add and install a  
return air enthalpy sensor.  
J20-3  
C08461  
Fig. 62 - RTU-MP T-56 Sensor Connections  
Connect T-59 - The T-59 space sensor requires a  
separate, isolated power supply of 24 VAC. See Fig. 61  
for internal connections at the T-59. Connect the SEN  
terminal (BLU) to RTU-MP J20-1. Connect the COM  
Return Air Enthalpy Sensor — Mount the return-air  
enthalpy sensor (HH57AC078) in the return-air duct. The  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
return air sensor is wired to the enthalpy controller  
(HH57AC077). See Fig. 49.  
To connect the sensor to the control, identify the positive  
(4 to 20 mA) and ground (SIG COM) terminals on the  
sensor. See Fig. 50. Connect the 4-20 mA terminal to  
terminal TB1-9 and connect the SIG COM terminal to  
terminal TB1-7. See Fig. 64.  
To wire the return air enthalpy sensor, perform the  
following:  
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable  
to connect the return air enthalpy sensor to the enthal-  
py controller.  
2. At the enthalpy control remove the factory-installed  
resistor from the (SR) and (+) terminals.  
IAQ Sensor  
J4-2  
SEN  
COM  
J4-3  
3. Connect the field-supplied RED wire to (+) spade  
connector on the return air enthalpy sensor and the  
(SR+) terminal on the enthalpy controller. Connect  
the BLK wire to (S) spade connector on the return air  
enthalpy sensor and the (SR) terminal on the enthalpy  
controller.  
24 VAC  
C08462  
Fig. 64 - RTU-MP / Indoor CO2 Sensor  
(33ZCSENCO2) Connections  
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus  
weatherproof enclosure) — The outdoor air CO2 sensor is  
designed to monitor carbon dioxide (CO2) levels in the  
outside ventilation air and interface with the ventilation  
damper in an HVAC system. The OAQ sensor is packaged  
with an outdoor cover. See Fig. 52. The outdoor air CO2  
sensor must be located in the economizer outside air hood.  
NOTE: The enthalpy control must be set to the “D”  
setting for differential enthalpy control to work properly.  
The enthalpy control receives the indoor and return  
enthalpy from the outdoor and return air enthalpy sensors  
and provides a dry contact switch input to the RTU-MP  
controller. A closed contact indicates that outside air is  
preferred to the return air. An open contact indicates that  
the economizer should remain at minimum position.  
Wiring the Outdoor Air CO2 Sensor — A dedicated power  
supply is required for this sensor. A two-wire cable is  
required to wire the dedicated power supply for the sensor.  
The two wires should be connected to the power supply  
and terminals 1 and 2.  
Indoor Air Quality (CO2 sensor) — The indoor air quality  
sensor accessory monitors space carbon dioxide (CO2)  
levels. This information is used to monitor IAQ levels.  
Several types of sensors are available, for wall mounting  
in the space or in return duct, with and without LCD  
display, and in combination with space temperature  
sensors. Sensors use infrared technology to measure the  
levels of CO2 present in the space air.  
To connect the sensor to the control, identify the positive  
(4 to 20 mA) and ground (SIG COM) terminals on the  
OAQ sensor. See Fig. 50. Connect the 4 to 20 mA  
terminal to 48TC’s terminal TB1-11. Connect the SIG  
COM terminal to 48TC’s terminal TB1-13. See Fig. 65.  
The CO2 sensors are all factory set for a range of 0 to  
2000 ppm and a linear mA output of 4 to 20. Refer to the  
instructions supplied with the CO2 sensor for electrical  
requirements and terminal locations. See Fig. 50 for  
typical CO2 sensor wiring schematic.  
OAQ Sensor/RH Sensor  
J4-5  
J4-6  
SEN  
To accurately monitor the quality of the air in the  
conditioned air space, locate the sensor near a return-air  
grille (if present) so it senses the concentration of CO2  
leaving the space. The sensor should be mounted in a  
location to avoid direct breath contact.  
COM  
24 VAC  
C08463  
Fig. 65 - RTU-MP / Outdoor CO2 Sensor  
(33ZCSENCO2) Connections  
Do not mount the IAQ sensor in drafty areas such as near  
supply ducts, open windows, fans, or over heat sources.  
Allow at least 3 ft (0.9 m) between the sensor and any  
corner. Avoid mounting the sensor where it is influenced  
by the supply air; the sensor gives inaccurate readings if  
the supply air is blown directly onto the sensor or if the  
supply air does not have a chance to mix with the room air  
before it is drawn into the return airstream.  
On 48TC units equipped with factory-installed Smoke  
Detector(s), the smoke detector controller implements the  
unit shutdown through its NC contact set connected to the  
unit’s LCTB input. The FSD function is initiated via the  
smoke detector’s Alarm NO contact set. The PremierLink  
communicates the smoke detector’s tripped status to the  
CCN building control. See Fig. 23 for unit smoke detector  
wiring.  
Wiring the Indoor Air Quality Sensor —  
The  
Fire  
Shutdown  
Switch  
configuration,  
identifies the  
For each sensor, use two 2-conductor 18 AWG (American  
Wire Gage) twisted-pair cables (unshielded) to connect  
the separate isolated 24 vac power source to the sensor  
and to connect the sensor to the control board terminals.  
MENUConfigInputsinput 5,  
normally open status of this input when there is no fire  
alarm.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Alarm state is reset when the smoke detector alarm  
condition is cleared and reset at the smoke detector in the  
unit.  
Power Exhaust (output)  
Connect the accessory Power Exhaust contactor coil(s) per  
Fig. 66.  
Connecting Discrete Inputs  
Filter Status  
Power Exhaust  
The filter status accessory is a field-installed accessory.  
This accessory detects plugged filters. When installing  
this accessory, the unit must be configured for filter status  
by setting MENUConfigInputsinput 3, 5, 8, or 9  
to Filter Status and normally open (N/O) or normally  
closed (N/C). Input 8 or 9 is recommended for easy of  
installation. Refer to Fig. 59 and Fig. 60 for wire  
terminations at J5.  
J11-3  
PEC  
TAN  
LCTB  
THERMOSTAT  
C
GRA  
C08464  
Fig. 66 - RTU-MP Power Exhaust Connections  
Space Relative Humidity Sensor - The RH sensor is not  
used with 48TC models at this time.  
Fan Status  
The fan status accessory is a field-installed accessory.  
This accessory detects when the indoor fan is blowing air.  
When installing this accessory, the unit must be  
Communication Wiring -- Protocols  
General  
configured  
for  
fan  
status  
by  
setting  
Protocols are the communication languages spoken by  
control devices. The main purpose of a protocol is to  
communicate information in the most efficient method  
possible. Different protocols exist to provide different  
kinds of information for different applications. In the BAS  
application, many different protocols are used, depending  
on manufacturer. Protocols do not change the function of  
a controller; just make the front end user different.  
The RTU-MP can be set to communicate on four different  
protocols: BACnet, Modbus, N2, and LonWorks. Switch 3  
(SW3) on the board is used to set protocol and baud rate.  
Switches 1 and 2 (SW1 and SW2) are used to set the  
board’s network address. See Fig 67 for the switch setting  
per protocol. The 3rd party connection to the RTU-MP is  
through plug J19. Refer to the RTU-MP 3rd Party  
Integration Guide for more detailed information on  
protocols, 3rd party wiring, and networking.  
MENUConfigInputsinput 3, 5, 8, or 9 to Fan  
Status and normally open (N/O) or normally closed (N/C).  
Input 8 or 9 is recommended for easy of installation. Refer  
to Fig. 59 and Fig. 60 for wire terminations at J5.  
Remote Occupancy  
The remote occupancy accessory is a field-installed  
accessory. This accessory overrides the unoccupied mode  
and puts the unit in occupied mode. When installing this  
accessory, the unit must be configured for remote  
occupancy by setting MENUConfigInputsinput 3,  
5, 8, or 9 to Remote Occupancy and normally open (N/O)  
or normally closed (N/C).  
Also set MENUSchedulesoccupancy source to DI  
on/off. Input 8 or 9 is recommended for easy of  
installation. Refer to Fig. 59 and Table 21 for wire  
terminations at J5.  
NOTE: Power must be cycled after changing the SW1-3  
switch settings.  
SW3 Protocol Selection  
DS6 DS5  
OFF OFF  
PROTOCOL  
BACnet MS/TP  
(Master)  
DS8  
DS7  
DS4  
DS3  
DS2  
DS1  
Unused  
OFF  
ON  
OFF  
Select Baud Select Baud  
Modbus  
(Slave)  
Unused  
OFF  
OFF  
ON  
ON  
OFF  
Select Baud Select Baud  
N2  
Unused  
Unused  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
(Slave)  
LonWorks  
OFF  
NOTE:  
DS = Dip Switch  
BACnet MS/TP SW3 example shown  
Baud Rate Selections  
BAUD RATE  
9600  
DS2  
OFF  
ON  
OFF  
ON  
DS1  
OFF  
OFF  
ON  
19,200  
38,400  
76,800  
ON  
C07166  
Fig. 67 - RTU-MP SW3 Dip Switch Settings  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BACnet MS/TP  
Local Access  
6
BACnet Master Slave/Token Passing (MS/TP) is used for  
BACview Handheld  
communicating BACnet over  
a
sub-network of  
The BACview6 is a keypad/display interface used to  
connect to the RTU-MP to access the control information,  
read sensor values, and test the RTU, see Fig. 68. This is  
an accessory interface that does not come with the MP  
controller and can only be used at the unit. Connect the  
BACview6 to the RTU-MP’s J12 local access port. There  
are 2 password protected levels in the display (User and  
Admin). The user password is defaulted to 0000 but can  
be changed. The Admin password is 1111 and cannot be  
changed. There is a 10 minute auto logout if a screen is  
left idle. See Form 48-50H-T-2T, Appendix A for  
navigation and screen content.  
BACnet-only controllers. This is the default Carrier  
communications protocol. Each RTU-MP module acts as  
an MS/TP Master. The speed of an MS/TP network can  
range from 9600 to 76.8K baud. Physical Addresses can  
be set from 01 to 99.  
Modbus  
The RTU-MP module can speak the Modicon Modbus  
RTU Protocol as described in the Modicon Modbus  
Protocol Reference Guide, PI-MBUS-300 Rev. J. The  
speed of a Modbus network can range from 9600 to 76.8K  
baud. Physical Addresses can be set from 01 to 99.  
Virtual BACview  
Johnson N2  
Virtual BACview is a freeware computer program that  
functions as the BACview6 Handheld. The USB Link  
interface (USB-L) is required to connect a computer to  
the RTU-MP board. The link cable connects a USB port  
to the J12 local access port. This program functions and  
operates identical to the handheld.  
N2 is not a standard protocol, but one that was created by  
Johnson Controls, Inc. that has been made open and  
available to the public. The speed of N2 network is  
limited to only 9600 baud. Physical Addresses can be set  
from 01 to 99.  
LonWorks  
RTU--MP Troubleshooting  
Communication LEDs  
LonWorks is an open protocol that requires the use of  
Echelon’s Neuron microprocessor to encode and decode  
the LonWorks packets. In order to reduce the cost of  
adding that hardware on every module, a separate  
LonWorks Option Card (LON-OC) was designed to  
connect to the RTU-MP.  
The LEDs indicate if the controller is speaking to the  
devices on the network. The LEDs should reflect  
communication traffic based on the baud rate set. The  
higher the baud rate the more solid the LEDs will appear.  
This accessory card is needed for LonWorks and has to be  
ordered and connected using the ribbon cable to plug J15.  
The RTU-MP’s baud rate must be set to 38.4k to  
communicate with the LON-OC. The address switches  
(SW1 & SW2) are not used with LonWorks.  
C07170  
Fig. 68 - BACview6 Handheld Connections  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 22 – LEDs  
The LEDs on the RTU-MP show the status of certain functions  
If this LED is on...  
Status is...  
Power  
Rx  
Tx  
The RTU MP has power  
The RTU MP is receiving data from the network segment  
The RTU MP is transmitting data over the network segment  
The digital output is active  
DO#  
The Run and Error LEDs indicate control module and network status  
If Run LED shows...  
2 flashes per second  
And Error LED shows...  
Off  
Status is...  
Normal  
2 flashes,  
Five minute auto---restart delay after sys-  
tem error  
Control module has just been  
formatted  
Two or more devices on this network  
have the same ARC156 network address  
Exec halted after frequent system errors  
or control programs halted  
Exec start---up aborted, Boot is running  
Firmware transfer in progress, Boot is  
running  
2 flashes per second  
2 flashes per second  
2 flashes per second  
alternating with Run LED  
3 flashes,  
then off  
4 flashes,  
then pause  
2 flashes per second  
5 flashes per second  
5 flashes per second  
On  
On  
Off  
7 flashes per second, alternating with  
Run LED  
14 flashes per second,  
alternating with Run LED  
Ten second recovery period after brown-  
out  
7 flashes per second  
14 flashes per second  
Brownout  
Failure. Try the following solutions:  
S
S
S
S
Turn the RTU---MP off, then on.  
Form at the R TU --- M P.  
Download memory to the RTU---MP.  
Replace the RTU---MP.  
On  
On  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 23 – Troubleshooting Alarms  
BACnet  
OBJECT  
NAME  
ACTION TAKEN BY  
CONTROL  
RESET  
METHOD  
POINT NAME  
Safety Chain Alarm  
Fire Shutdown Alarm  
PROBABLE CAUSE  
Alarm Generated  
Immediate  
safety_chain  
fire_alarm  
spt_alarm  
sat_alarm  
Automatic  
Automatic  
Automatic  
Automatic  
Over load Indoor Fan or Electric Heater overheat.  
Shutdown  
Alarm Generated  
Immediate  
Shutdown  
Alarm Generated  
Immediate  
Shutdown  
Alarm Generated  
Immediate  
Shutdown  
Smoke detected by smoke detector or configura-  
tion incorrect  
Space Temp Sensor  
Failure  
Faulty, shorted, or open thermistor caused by  
wiring error or loose connection.  
Faulty, shorted, or open thermistor caused by  
wiring error or loose connection.  
SAT Sensor Alarm  
The space temperature has risen above the cool  
setpoint by more than the desired amount.  
The space temperature has dropped below the  
heat setpoint by more than the desired amount.  
SAT is greater then 160 degrees for more than 5  
minutes.  
High Space Temp Alarm  
Low Space Temp Alarm  
High Supply Air Temp  
Low Supply Air Temp  
spt_hi  
spt_lo  
sat_hi  
sat_lo  
Alarm Generated  
Alarm Generated  
Alarm Generated  
Alarm Generated  
Automatic  
Automatic  
Automatic  
Automatic  
The supply air temperature is below 35_F for  
more than 5 minutes.  
Alarm Generated  
Immediately  
Tripped Circuit Breaker, Broken belt, Bad indoor  
fan motor, Configuration incorrect, Bad fan status  
switch.  
Supply Fan Failed to  
Start  
sf_fail  
Automatic  
Automatic  
disable Operation  
Alarm Generated  
Ramp down  
Supply Fan in Hand  
sf_hand  
Bad Fan Status Switch, Configuration incorrect.  
Operations  
Compressor Safety  
Alarm  
dx_compstat  
slide_alarm  
Alarm Generated  
Automatic  
Automatic  
Compressor would not start.  
Alarm Generated  
Offset set to zero  
STO sensor is open or shorted for more then 5  
seconds.  
Setpoint Slider Alarm  
Automatic/  
reset timer  
when config-  
ured with or  
without  
Dirty Filter, supply fan run time exceeded, filter  
switch configuration wrong.  
Dirty Filter Alarm  
filter  
Alarm Generated  
switch  
Alarm Generated  
Disable misconfi-  
gured switch  
More than one binary input is configured for the  
same purpose. More then one discrete input is  
configured to provide the same function.  
Switch Configuration  
Alarm  
Configure  
correctly  
sw_cfg_alarm  
an_cfg_alarm  
oat_alarm  
functions  
Alarm Generated  
Disable 4 selectable  
analog inputs  
Alarm Generated  
Economizer and Low  
ambient DX cooling  
lockout disabled.  
Alarm Generated  
Dehumidification  
disabled  
Misconfigured Analog In-  
put  
Configure  
correctly  
More then one analog input is configured to pro-  
vide the same function.  
Faulty, shorted, or open thermistor caused by  
wiring error or loose connection.  
OAT Sensor Alarm  
Automatic  
Sensor reading is out of range. Bad sensor, bad  
wiring, or sensor configured incorrectly.  
Space RH Sensor Alarm  
sprh_alarm  
oarh_alarm  
Automatic  
Automatic  
Outdoor RH Sensor  
Alarm  
Sensor reading is out of range. Bad sensor, bad  
wiring, or sensor configured incorrectly.  
IRH is greater then 70% for more then 10 min-  
utes.  
Alarm Generated  
High Space Humidity  
Low Space Humidity  
sprh_hi  
sprh_lo  
Alarm Generated  
Automatic  
Automatic  
Alarm Generated  
Alarm Generated  
Disables IAQ  
Operation Econo-  
mizer moves to mini-  
mum position  
IRH is less then 35% for more then 10 minutes.  
Sensor reading is out of range. Bad sensor, bad  
wiring, or sensor configured incorrectly.  
IAQ Sensor Alarm  
iaq_alarm  
Automatic  
Alarm Generated Set  
Sensor reading is out of range. Bad sensor, bad  
wiring, or sensor configured incorrectly.  
OAQ Sensor Alarm  
oaq_alarm  
co2_hi  
Automatic  
Automatic  
OAQ to 400  
High Carbon Dioxide  
Level  
Supply Fan Runtime  
Alarm  
Compressor 1 Runtime  
Alarm  
Compressor 2 Runtime  
Alarm  
Alarm Generated  
Alarm Generated  
Alarm Generated  
Alarm Generated  
CO2 reading is above 1200ppm.  
clear the  
timer  
clear the  
timer  
clear the  
timer  
sf_rntm  
Supply fan run time exceeded user defined limit.  
Compressor run time limit is exceeded.  
Compressor run time limit is exceeded.  
dx1_rntm  
dx2_rntm  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Misconfigured Analog Input  
Alarms  
This occurs if more than one analog input (inputs 1 & 2)  
is configured for the same sensor. When this happens the  
two inputs will be disabled as inputs. This alarm will  
automatically be cleared when configuration is corrected.  
An example of this would be: Input 1 = IAQ Sensor, input  
2 = IAQ Sensor; the alarm would be active, unit would  
run, but the IAQ Sensor (inputs 1 & 2) will be interpreted  
as “No Function.”  
Alarms can be checked through the network and/or the  
local access. All the alarms are listed in Table 23 with  
name, object name, action taken by control, reset method,  
and probable cause. There are help screens for each alarm  
on the local access display and listed in Form  
48-50H-T-2T, Appendix A: Help Screens. Some alarms  
are explained in detail below.  
Safety Chain Alarm  
Third Party Networking  
This alarm occurs immediately if the supply-fan internal  
overload trips or if an electric-heat limit switch trips. The  
Unit Status will be Shutdown and the System Mode will  
be Disable. When this happens LCTB (R terminal) will  
not have 24 VAC, but the RTU-MP board will still be  
powered. All unit operations stop immediately and will  
not restart until the alarm automatically clears. There are  
no configurations for this alarm; it is all based on internal  
wiring. This alarm will never occur if Fire Shutdown  
Alarm is active.  
Third  
party  
communication  
and  
networking  
troubleshooting should be done by or with assistance from  
the front end 3rd party technician. A Module Status  
Report (Modstat) can be run from the BACview6, see  
Table 24 to perform. This lists information about the  
board status and networking state. For basic  
troubleshooting, see Table 25. Refer to the RTU-MP 3rd  
Party Integration Guide for additional information.  
BACnet MS/TP  
Fire Shutdown Alarm  
1. Verify that the BAS and controller are both set to  
speak the BACnet MS/TP protocol. The protocol of  
the controller is set via SW3 (switches 3, 4, 5, and 6).  
The protocol can also be verified by getting a Modstat  
of the controller through the BACview. Hit the “FN”  
key and the ’.’ key at the same time to pull up a  
Modstat. Scroll to the bottom of the page and there is  
a section entitled “Network Communications.” The  
active protocol and baud rate will be shown in this  
section.  
2. Verify that the BAS and controller are set for the  
same baud rate. The baud rate of the controller is set  
via SW3 (switches 1 and 2). The baud rate can also  
be verified via the BACview by obtaining a Modstat.  
(See Fig. 67.)  
3. Verify that the BAS is configured to speak 2-wire  
EIA-485 to the controller. The BAS may have to con-  
figure jumper or DIP switches on their end.  
4. Verify that the BAS and the controller have the same  
communication settings (8 data bits, No Parity, and 1  
stop bit).  
5. Verify that the controller has a unique MAC address  
on the MS/TP bus. The controller’s MS/TP MAC ad-  
dress is set by its rotary address switches.  
6. Verify proper wiring between the BAS and the con-  
troller.  
7. Verify that the BAS is reading or writing to the proper  
BACnet objects in the controller. Download the latest  
points list for the controller to verify.  
8. Verify that the BAS is sending his requests to the  
proper MS/TP MAC address of our controller.  
This alarm occurs immediately when the smoke detector  
senses smoke. The Unit Status will be Shutdown and the  
System Mode will be Disable. All unit operations stop  
immediately and will not restart until the alarm  
automatically clears. If there is not a smoke detector  
installed or the smoke detector did not trip, check input  
configurations.  
Space Temp Sensor Failure  
This alarm occurs if the space sensor wired to the  
RTU-MP is disconnected or shorted for more then 10  
seconds. When this occurs the Unit Status will be  
Shutdown and the System Mode will be Run. Sensor,  
sensor connections, wiring, board connection, and  
configurations should be checked for faults or errors.  
Alarm will reset automatically when cause is fixed.  
SAT Sensor Alarm  
This alarm occurs immediately when the supply air  
temperature sensor wired to the RTU-MP is disconnected  
or shorted. When this occurs the Unit Status will be  
Shutdown and the System Mode will be Run. Sensor,  
sensor connections, wiring, board connection, and  
configurations should be checked for faults or errors.  
Alarm will reset automatically when cause is fixed.  
Switch Configuration Alarm  
This occurs if more than one binary input (inputs 3, 5, 8,  
and 9) is configured for the same function. When this  
happens the two inputs (or more) configured wrong will  
be disabled as an inputs. This alarm will automatically be  
cleared when configuration is corrected.  
An example of this would be: Input 3 = Compressor  
Safety, input 5 = Fan Status, input 8 = Fan Status, and  
input 9 = Humidistat; the alarm would be active, unit  
would run, compressor safety and humidistat would  
function normally, and Fan Status (inputs 5 & 8) will be  
interpreted as “No Function.”  
9. Present the BAS company with a copy of our control-  
ler’s BACnet PICS so that they know which BACnet  
commands are supported. See below.  
10. In certain situations, it may be necessary to tweak the  
MS/TP Protocol timing settings through the BAC-  
view6. There are two settings that may be tweaked:  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S Max Masters: Defines the highest MS/TP Master MAC  
address on this MS/TP network. For example, if there are  
3 master nodes on an MS/TP network, and their MAC  
addresses are 1, 8, and 16, then Max Masters would be set  
to 16 (since this is the highest MS/TP MAC address on  
the network). This property optimizes MS/TP network  
communications by preventing token passes and “poll for  
master” requests to non-existent Master nodes (i.e., in  
                                                                                                                                                 
the above example, MAC address 16 would know to pass  
the token back to MAC address 1 instead of counting up  
to MAC address 127). Each MS/TP master node on the  
network must have their Max Masters set to this same  
value. The default is 127.  
Device Instance: 0160001  
1 PRGs loaded. 1 PRGs running.  
Module status:  
Firmware sections validated in flash memory  
============================================  
Boot16-H  
- v2.06:001 Jun 19 2007  
- v2.09:050 Jun 26 2007  
RTU-MP DRIVER  
Reset counters:  
11 Power failures  
0 Brownouts  
18 Commanded warm boots  
22 Commanded cold boots  
0 System errors  
0 Watchdog timeouts  
System error message history:  
Warning message history:  
Type Specific  
Information message history:  
POWERUP: BACnet reinitialize warmstart  
Menu file not found.  
06/29/07 10:49:40  
06/29/07 10:48:35  
ARC156 reconfigurations during the last hour (cleared upon reset):  
Total ....................... 0  
Initiated by this node ...... 0  
Core board hardware:  
Type=147, board=34, manufactured on 05/14/2007, S/N 21A740188N  
RAM: 1024 kBytes;  
FLASH: 1024 kBytes, type = 3  
Base board hardware:  
Type=147, board=71, manufactured on 05/14/2007, S/N RMP750037N  
Largest free heap space = 65536.  
Database size = 742082 , used = 352162, free = 389920.  
Raw physical switches: 0x01280000  
Module Communications:  
Network Protocol=BACnet MSTP Master  
Network Baud Rate=9600 bps  
C07195  
Fig. 69 - Module Status Report (Modstat) Example  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 24 – Manufacture Date  
When troubleshooting, you may need to know a control module’s manufacture date  
Obtain the manufacture date from  
a...  
Notes  
6
Module status report (modstat)  
To obtain a modstat with BACview :  
1. Press Function (FN) key and hold.  
2. Then press period (.)  
3. Release both buttons.  
The report shows the date under Main board hardware.  
Sticker on the back of the main control The serial numbers are unique and contain embedded information:  
module board  
”Serial No: RMPYMxxxxN”  
(Bar Coded & Typed Number)  
“RMP”  
“YM”  
---  
---  
These first three digits are unique to RTU---MP and are used as an identifier.  
These two digits identify the last digit of the year and month (in hex, A=10/Oct)  
of manufacture. ”74” would represent a date of manufacture of ”April 2007”.  
These four digits represent the sequential number of units produced for a given  
product for the mentioned manufacturing time period.  
This final digit represents the decade and toggles between ”N” and ”M” every  
ten years.  
xxxx”  
---  
---  
“N”  
Table 25 – Basic Protocol Troubleshooting  
Problem  
No communication with 3rd  
party vendor  
Possible cause  
Incorrect settings on SW1, SW2 and SW3  
Corrective action  
Verify and correct switch settings. Cycle  
power to RTU---MP after changing switch  
settings.  
RS485 Port has no voltage output  
(check with RTU---MP disconnected from RS485 commu-  
nication bus)  
Verify RTU---MP has correct power supply  
Possible bad driver on board.  
Bacnet @ 9600/19.2K --- .01 to .045vdc  
Check RS485 bus for external before re-  
connecting to the bus  
Bacnet @ 38.4K --- .06 to .09vdc  
Bacnet @ 76.8K --- .1vdc  
Voltage, shorts or grounding  
before reconnecting to the bus  
Modbus @ 9600 --- 76.8K --- .124vdc  
N2 @ 9600 --- .124vdc  
Verify devices are daisy chained and repeaters and bias  
terminators are correctly installed  
Check 3rd party vendor RS485 commu-  
nication wiring guidelines and trouble-  
shooting procedures  
S MaxInfo Frames: This property defines the maximum  
number of responses that will be sent when our controller  
gets the token. A valid number is any positive integer.  
The default is 10 and should be ideal for the majority of  
applications. In cases where the controller is the target of  
many requests, this number could be increased as high as  
100 or 200.  
NOTE: MS/TP networks can be comprised of both  
Master and Slave nodes. Valid MAC addresses for Master  
nodes are 0 - 127 and valid addresses for Slave nodes are  
0 - 254.  
Modbus  
1. Verify that the BAS and controller are both set to  
speak the Modbus RTU protocol. The protocol of the  
controller is set via SW3 (switches 3, 4, 5, and 6).  
The protocol can also be verified by getting a Modstat  
of the controller through the BACview. Hit the ”FN”  
key and the ’.’ key at the same time to pull up a  
Modstat. Scroll to the bottom of the page and there is  
a section entitled “Network Communications.” The  
active protocol and baud rate will be shown in this  
section.  
NOTE: See RTU-MP 3rd Party Integration Guide (or  
alternatively Form 48-50H-T-1T Appendix) for Protocol  
Maps.  
2. Verify that the BAS and controller are set for the  
same baud rate. The baud rate of the controller is set  
via SW3 (switches 1 and 2). The baud rate can also  
be verified via the BACview by obtaining a Modstat  
(see above).  
3. Verify that the BAS is configured to speak 2-wire  
EIA-485 to the controller. The BAS may have to con-  
figure jumper or DIP switches on their end.  
4. Verify that the BAS and the controller have the same  
communication settings (8 data bits, No Parity, and 1  
stop bit).  
5. Verify that the controller has a unique Modbus slave  
address. The controller’s Modbus slave address is set  
by its rotary address switches.  
Table 26 – Modbus Exception Codes that May be  
Returned From This Controller  
CODE  
NAME  
MEANING  
The Modbus function code used  
in the query is not supported by  
the controller.  
01  
Illegal Function  
The register address used in the  
query is not supported by the  
controller.  
02  
04  
Illegal Data Address  
Slave Device Failure  
The Modbus Master has at-  
tempted to write to a non---exist-  
ent register or a read---only regis-  
ter in the controller.  
6. Verify that the BAS is using the proper Modbus func-  
tion codes to access data from our controller. Sup-  
ported function codes are shown above.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7. Verify proper wiring between the BAS and the con-  
troller.  
8. Verify that the BAS is reading or writing to the proper  
Modbus register numbers on the controller. Download  
the latest points list for the controller to verify.  
9. Verify that the BAS is sending his requests to the  
proper slave address of our controller.  
NOTE: See RTU-MP 3rd Party Integration Guide (or  
alternatively Form 48-50H-T-1T, Appendix) for Modbus  
Protocol Conformance Statement.  
ECONOMIZER SYSTEMS  
The 48TC units may be equipped with a factory-installed  
or accessory (field-installed) economizer system. Two  
types are available: with  
(EconoMi$er IV) and without  
a
logic control system  
control system  
a
(EconoMi$er2, for use with external control systems such  
as PremierLink). See Fig. 70 and Fig. 71 for component  
locations on each type. See Fig. 72 and Fig. 73 for  
economizer section wiring diagrams.  
Both EconoMi$ers use direct-drive damper actuators.  
N2  
ECONOMI$ER IV  
CONTROLLER  
1. Verify that the BAS and controller are both set to  
speak the N2 protocol. The protocol of the controller  
is set via SW3 (switches 3, 4, 5, and 6). The protocol  
can also be verified by getting a Modstat of the con-  
troller through the BACview. Hit the “FN” key and  
the ’.’ key at the same time to pull up a Modstat.  
Scroll to the bottom of the page and there is a section  
entitled ”Network Communications.” The active pro-  
tocol and baud rate will be shown in this section.  
OUTSIDE AIR  
WIRING  
TEMPERATURE SENSOR  
HARNESS  
LOW AMBIENT  
SENSOR  
ACTUATOR  
2. Verify that the BAS and controller are set for 9600  
baud. The baud rate of the controller is set via SW3  
(switches 1 and 2). The baud rate can also be verified  
via the BACview by obtaining a Modstat (see above).  
3. Verify that the BAS is configured to speak 2-wire  
EIA-485 to the controller. The BAS may have to con-  
figure jumper or DIP switches on their end.  
C06021  
Fig. 70 - EconoMi$er IV Component Locations  
OUTDOOR  
AIR HOOD  
4. Verify that the BAS and the controller have the same  
communication settings (8 data bits, No Parity, and 1  
stop bit).  
ECONOMI$ER2  
HOOD  
PLUG  
SHIPPING  
BRACKET  
5. Verify that the controller has a unique N2 slave ad-  
dress on the N2 bus. The controller’s N2 slave ad-  
dress is set by its rotary address switches.  
6. Verify proper wiring between the BAS and the con-  
troller.  
7. Verify that the BAS is reading or writing to the proper  
network point addresses on the controller. Download  
the latest points list for the controller to verify.  
GEAR DRIVEN  
BAROMETRIC  
DAMPER  
RELIEF  
DAMPER  
C06022  
Fig. 71 - EconoMi$er2 Component Locations  
8. Verify that the BAS is sending his requests to the  
proper slave address of our controller.  
NOTE: See RTU-MP 3rd Party Integration Guide (or  
alternatively Form 48-50H-T-1T Appendix) for N2  
Protocol Conformance Statement.  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FOR OCCUPANCY CONTROL  
REPLACE JUMPER WITH  
FIELD-SUPPLIED TIME CLOCK  
8
7
Potentiometer Defaults Settings:  
LEGEND  
NOTES:  
Power Exhaust Middle  
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential  
DCV— Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
Minimum Pos.  
DCV Max.  
DCV Set  
Fully Closed  
enthalpy or dry bulb.  
Middle  
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power  
supply, it cannot have the secondary of the transformer grounded.  
3. For field-installed remote minimum position POT, remove black wire jumper  
between P and P1 and set control minimum position POT to the minimum  
position.  
LA — Low Ambient Lockout Device  
OAT — Outdoor-Air Temperature  
POTPotentiometer  
Middle  
C Setting  
Enthalpy  
RAT — Return-Air Temperature  
C06028  
Fig. 72 - EconoMi$er IV Wiring  
BLACK  
BLUE  
4
3
TRANSFORMER  
GROUND  
5
2
500 OHM  
RESISTOR  
8
VIOLET  
PINK  
6
NOTE 1  
7
RUN  
OAT SENSOR  
RED  
24 VAC  
1
NOTE 3  
10  
11  
9
50HJ540573  
ACTUATOR  
ASSEMBLY  
4-20 mA  
WHITE  
DIRECT DRIVE  
ACTUATOR  
TO J9 ON  
PremierLink  
BOARD  
4-20mA SIGNAL  
12  
ECONOMISER2 PLUG  
NOTES:  
1. Switch on actuator must be in run position for economizer to operate.  
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen  
sor or HH57A077 enthalpy sensor.  
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.  
C08310  
Fig. 73 - EconoMi$er2 with 4 to 20 mA Control Wiring  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 27 – EconoMi$er IV Input/Output Logic  
INPUTS  
OUTPUTS  
N Terminal†  
Enthalpy*  
Compressor  
Demand Control  
Ventilation (DCV)  
Y1 Y2  
Occupied  
Unoccupied  
Closed  
Stage Stage  
Outdoor  
Return  
Low  
1
2
Damper  
On On  
On Off  
Off Off  
On  
On  
Off  
On  
Off  
Off  
High  
(Free Cooling LED  
Off)  
Minimum position  
Below set  
(DCV LED Off)  
Modulating** (between  
min. position and full-  
open)  
Modulating** (be-  
tween closed and  
full-open)  
On On  
On  
Off  
Low  
(Free Cooling LED  
On)  
High  
On Off  
Off Off  
On On  
Off  
Off  
On  
Off  
Off  
On  
Minimum position  
Closed  
Modulating†† (be-  
tween closed and  
DCV  
High  
(Free Cooling LED  
Off)  
Modulating†† (between  
min. position and DCV  
maximum)  
On Off  
Off Off  
On On  
On Off  
Off Off  
On  
Off  
Off  
Off  
Low  
Above set  
(DCV LED On)  
maximum)  
On  
Off  
Off  
Off  
Off  
Off  
Low  
(Free Cooling LED  
On)  
High  
Modulating***  
Modulating†††  
*
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.  
Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).  
** Modulation is based on the supply-air sensor signal.  
†† Modulation is based on the DCV signal.  
*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV)  
or fully open (supply-air signal).  
††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully  
open (supply-air signal).  
C06053  
Fig. 74 - EconoMi$er IV Functional View  
EconoMi$er IV Standard Sensors  
EconoMi$er IV  
Outdoor Air Temperature (OAT) Sensor  
Table 27 provides a summary of EconoMi$er IV.  
Troubleshooting instructions are enclosed.  
The outdoor air temperature sensor (HH57AC074) is a 10  
to 20 mA device used to measure the outdoor-air  
temperature. The outdoor-air temperature is used to  
determine when the EconoMi$er IV can be used for free  
cooling. The sensor is factory-installed on the  
EconoMi$er IV in the outdoor airstream. (See Fig. 75.)  
The operating range of temperature measurement is 40_ to  
100_F (4_ to 38_C). See Fig. 77.  
A functional view of the EconoMi$er is shown in Fig. 74.  
Typical settings, sensor ranges, and jumper positions are  
also shown. An EconoMi$er IV simulator program is  
available from Carrier to help with EconoMi$er IV  
training and troubleshooting.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Supply Air Temperature (SAT) Sensor  
and D. See Fig. 77 for the corresponding temperature  
changeover values.  
The supply air temperature sensor is a 3 K thermistor  
located at the inlet of the indoor fan. (See Fig. 75.) This  
sensor is factory installed. The operating range of  
temperature measurement is 0° to 158_F (-18_ to 70_C).  
See Table 15 for sensor temperature/resistance values.  
SUPPLY AIR  
TEMPERATURE  
SENSOR  
MOUNTING  
LOCATION  
SUPPLY AIR  
TEMPERATURE  
SENSOR  
C06033  
C06034  
Fig. 76 - EconoMi$er IV Controller Potentiometer  
and LED Locations  
Fig. 75 - Supply Air Sensor Location  
The temperature sensor looks like an eyelet terminal with  
wires running to it. The sensor is located in the “crimp  
end” and is sealed from moisture.  
19  
LED ON  
18  
Outdoor Air Lockout Sensor  
D
17  
The EconoMi$er IV is equipped with an ambient  
temperature lockout switch located in the outdoor  
airstream which is used to lock out the compressors below  
a 42_F (6_C) ambient temperature. (See Fig. 70.)  
LED ON  
LED OFF  
16  
15  
14  
C
LED ON  
LED OFF  
B
13  
12  
EconoMi$er IV Control Modes  
LED ON  
LED OFF  
A
11  
10  
9
IMPORTANT: The optional EconoMi$er2 does not  
include a controller. The EconoMi$er2 is operated by a 4  
to 20 mA signal from an existing field-supplied controller  
(such as PremierLinkcontrol). See Fig. 72 for wiring  
information.  
LED OFF  
85 90  
95  
100  
50  
55 60  
70 75  
DEGREES FAHRENHEIT  
40 45  
65  
80  
C06035  
Determine the EconoMi$er IV control mode before set up  
of the control. Some modes of operation may require  
different sensors. (See Table 22.) The EconoMi$er IV is  
supplied from the factory with a supply-air temperature  
sensor and an outdoor- air temperature sensor. This allows  
for operation of the EconoMi$er IV with outdoor air dry  
bulb changeover control. Additional accessories can be  
added to allow for different types of changeover control  
and operation of the EconoMi$er IV and unit.  
Fig. 77 - Outside Air Temperature Changeover  
Setpoints  
30  
25  
20  
15  
10  
5
Outdoor Dry Bulb Changeover  
The standard controller is shipped from the factory  
configured for outdoor dry bulb changeover control. The  
outdoor air and supply air temperature sensors are  
included as standard. For this control mode, the outdoor  
temperature is compared to an adjustable setpoint selected  
on the control. If the outdoor-air temperature is above the  
setpoint, the EconoMi$er IV will adjust the outside air  
dampers to minimum position. If the outdoor-air  
temperature is below the setpoint, the position of the  
outside air dampers will be controlled to provided free  
cooling using outdoor air. When in this mode, the LED  
next to the free cooling setpoint potentiometer will be on.  
The changeover temperature setpoint is controlled by the  
free cooling setpoint potentiometer located on the control.  
(See Fig. 76.) The scale on the potentiometer is A, B, C,  
0
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50  
STATIC PRESSURE (in. wg)  
C06031  
Fig. 78 - Outdoor-Air Damper Leakage  
Differential Dry Bulb Control  
For differential dry bulb control the standard outdoor dry  
bulb sensor is used in conjunction with an additional  
accessory  
dry  
bulb  
sensor  
(part  
number  
CRTEMPSN002A00). The accessory sensor must be  
mounted in the return airstream. (See Fig. 79.) Wiring is  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
provided in the EconoMi$er IV wiring harness. (See Fig.  
70.)  
In this mode of operation, the outdoor-air temperature is  
compared to the return-air temperature and the lower  
temperature airstream is used for cooling. When using this  
mode of changeover control, turn the enthalpy setpoint  
potentiometer fully clockwise to the D setting. (See Fig.  
76.)  
ECONOMI$ERIV  
CONTROLLER  
ECONOMI$ERIV  
Outdoor Enthalpy Changeover  
For enthalpy control, accessory enthalpy sensor (part  
number HH57AC078) is required. Replace the standard  
outdoor dry bulb temperature sensor with the accessory  
enthalpy sensor in the same mounting location. (See Fig.  
79.) When the outdoor air enthalpy rises above the  
outdoor enthalpy changeover setpoint, the outdoor-air  
damper moves to its minimum position. The outdoor  
enthalpy changeover setpoint is set with the outdoor  
enthalpy setpoint potentiometer on the EconoMi$er IV  
controller. The setpoints are A, B, C, and D. (See Fig. 80.)  
The factory-installed 620-ohm jumper must be in place  
across terminals SR and SR+ on the EconoMi$er IV  
controller.  
GROMMET  
RETURN AIR  
SENSOR  
RETURN DUCT  
(FIELD-PROVIDED)  
C07085  
Fig. 79 - Return Air Temperature or Enthalpy Sensor  
Mounting Location  
85  
90  
95 100 105 110  
(29) (32) (35) (38) (41) (43)  
CONTROL CONTROL POINT  
CURVE  
APPROX. deg. F (deg. C)  
AT 50% RH  
80  
(27)  
A
B
C
D
73 (23)  
70 (21)  
67 (19)  
63 (17)  
75  
(24)  
70  
(21)  
65  
(18)  
0
6
60  
(16)  
A
55  
(13)  
B
50  
(10)  
C
45  
(7)  
D
40  
(4)  
35  
(2)  
A
B
C
D
HIGH LIMIT  
CURVE  
35  
(2)  
40  
45  
50  
55  
60  
65  
70  
75  
80  
85  
90  
95 100 105 110  
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)  
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)  
C06037  
Fig. 80 - Enthalpy Changeover Setpoints  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CO SENSOR MAX RANGE SETTING  
2
TR1  
EXH  
Set  
10V  
TR  
6000  
5000  
4000  
3000  
2000  
1000  
0
N1  
N
2V  
EXH  
24  
Va c  
HOT  
24 Vac  
COM  
P1  
T1  
P
T
Min  
Pos  
800 ppm  
900 ppm  
1000 ppm  
1100 ppm  
_
+
Open  
DCV  
Max  
10V  
1
2
5
2V  
AQ1  
AQ  
SO+  
SO  
SR+  
SR  
DCV  
DCV  
Set  
10V  
4
3
2
3
4
5
6
7
8
2V  
DAMPER VOLTAGE FOR MAX VENTILATION RATE  
Free  
Cool  
EF1  
EF  
C06039  
C
D
B
Fig. 82 - CO2 Sensor Maximum Range Settings  
A
If a separate field-supplied transformer is used to power  
the IAQ sensor, the sensor must not be grounded or the  
EconoMi$er IV control board will be damaged.  
When using demand ventilation, the minimum damper  
position represents the minimum ventilation position for  
C06038  
Fig. 81 - EconoMi$er IV Control  
Differential Enthalpy Control  
For differential enthalpy control, the EconoMi$er IV  
controller uses two enthalpy sensors (HH57AC078 and  
CRENTDIF004A00), one in the outside air and one in the  
return air duct. The EconoMi$er IV controller compares  
the outdoor air enthalpy to the return air enthalpy to  
determine EconoMi$er IV use. The controller selects the  
lower enthalpy air (return or outdoor) for cooling. For  
example, when the outdoor air has a lower enthalpy than  
the return air, the EconoMi$er IV opens to bring in  
outdoor air for free cooling.  
Replace the standard outside air dry bulb temperature  
sensor with the accessory enthalpy sensor in the same  
mounting location. (See Fig. 70.) Mount the return air  
enthalpy sensor in the return air duct. (See Fig. 79.)  
Wiring is provided in the EconoMi$er IV wiring harness.  
(See Fig. 70.) The outdoor enthalpy changeover setpoint is  
set with the outdoor enthalpy setpoint potentiometer on  
the EconoMi$er IV controller. When using this mode of  
changeover control, turn the enthalpy setpoint  
potentiometer fully clockwise to the D setting.  
VOC (volatile  
organic  
compounds) ventilation  
requirements. The maximum demand ventilation position  
is used for fully occupied ventilation.  
When demand ventilation control is not being used, the  
minimum position potentiometer should be used to set the  
occupied ventilation position. The maximum demand  
ventilation position should be turned fully clockwise.  
Exhaust Setpoint Adjustment  
The exhaust setpoint will determine when the exhaust fan  
runs based on damper position (if accessory power  
exhaust is installed). The setpoint is modified with the  
Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig.  
76.) The setpoint represents the damper position above  
which the exhaust fans will be turned on. When there is a  
call for exhaust, the EconoMi$er IV controller provides a  
45 ± 15 second delay before exhaust fan activation to  
allow the dampers to open. This delay allows the damper  
to reach the appropriate position to avoid unnecessary fan  
overload.  
Indoor Air Quality (IAQ) Sensor Input  
Minimum Position Control  
The IAQ input can be used for demand control ventilation  
control based on the level of CO2 measured in the space  
or return air duct.  
Mount the accessory IAQ sensor according to  
manufacturer specifications. The IAQ sensor should be  
wired to the AQ and AQ1 terminals of the controller.  
Adjust the DCV potentiometers to correspond to the DCV  
voltage output of the indoor air quality sensor at the  
user-determined setpoint. (See Fig. 82.)  
There is a minimum damper position potentiometer on the  
EconoMi$er IV controller. (See Fig. 76.) The minimum  
damper position maintains the minimum airflow into the  
building during the occupied period.  
When using demand ventilation, the minimum damper  
position represents the minimum ventilation position for  
VOC  
(volatile  
organic  
compound)  
ventilation  
requirements. The maximum demand ventilation position  
is used for fully occupied ventilation.  
When demand ventilation control is not being used, the  
minimum position potentiometer should be used to set the  
occupied ventilation position. The maximum demand  
ventilation position should be turned fully clockwise.  
Adjust the minimum position potentiometer to allow the  
minimum amount of outdoor air, as required by local  
codes, to enter the building. Make minimum position  
adjustments with at least 10_F temperature difference  
between the outdoor and return-air temperatures.  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To determine the minimum position setting, perform the  
following procedure:  
timeclock function in place of the jumper between TR and  
N. When the timeclock contacts are closed, the  
EconoMi$er IV control will be in occupied mode. When  
the timeclock contacts are open (removing the 24-v signal  
from terminal N), the EconoMi$er IV will be in  
unoccupied mode.  
1. Calculate the appropriate mixed air temperature  
using the following formula:  
OA  
100  
RA  
100  
+ (TR x  
(TO x  
)
) =TM  
Demand Control Ventilation (DCV)  
When using the EconoMi$er IV for demand controlled  
ventilation, there are some equipment selection criteria  
which should be considered. When selecting the heat  
capacity and cool capacity of the equipment, the  
maximum ventilation rate must be evaluated for design  
conditions. The maximum damper position must be  
calculated to provide the desired fresh air.  
Typically the maximum ventilation rate will be about 5 to  
10% more than the typical cfm required per person, using  
normal outside air design criteria.  
TO = Outdoor-Air Temperature  
OA = Percent of Outdoor Air  
TR = Return-Air Temperature  
RA = Percent of Return Air  
TM = Mixed-Air Temperature  
As an example, if local codes require 10% outdoor  
air during occupied conditions, outdoor-air  
temperature is 60_F, and return-air temperature is  
75_F.  
(60 x .10) + (75 x .90) = 73.5_F  
2. Disconnect the supply air sensor from terminals T  
and T1.  
3. Ensure that the factory-installed jumper is in place  
across terminals P and P1. If remote damper  
positioning is being used, make sure that the  
terminals are wired according to Fig. 59 and that the  
minimum position potentiometer is turned fully  
clockwise.  
A proportional anticipatory strategy should be taken with  
the following conditions: a zone with a large area, varied  
occupancy, and equipment that cannot exceed the required  
ventilation rate at design conditions. Exceeding the  
required ventilation rate means the equipment can  
condition air at a maximum ventilation rate that is greater  
than the required ventilation rate for maximum  
occupancy. A proportional-anticipatory strategy will cause  
the fresh air supplied to increase as the room CO2 level  
increases even though the CO2 setpoint has not been  
reached. By the time the CO2 level reaches the setpoint,  
the damper will be at maximum ventilation and should  
maintain the setpoint.  
In order to have the CO2 sensor control the economizer  
damper in this manner, first determine the damper voltage  
output for minimum or base ventilation. Base ventilation  
is the ventilation required to remove contaminants during  
unoccupied periods. The following equation may be used  
to determine the percent of outside air entering the  
building for a given damper position. For best results there  
should be at least a 10 degree difference in outside and  
return-air temperatures.  
4. Connect 24 vac across terminals TR and TR1.  
5. Carefully  
adjust  
the  
minimum  
position  
potentiometer until the measured mixed air  
temperature matches the calculated value.  
6. Reconnect the supply air sensor to terminals T and  
T1.  
Remote control of the EconoMi$er IV damper is desirable  
when requiring additional temporary ventilation. If a  
field-supplied remote potentiometer (Honeywell part  
number S963B1128) is wired to the EconoMi$er IV  
controller, the minimum position of the damper can be  
controlled from a remote location.  
To control the minimum damper position remotely,  
remove the factory-installed jumper on the P and P1  
terminals on the EconoMi$er IV controller. Wire the  
field-supplied potentiometer to the P and P1 terminals on  
the EconoMi$er IV controller. (See Fig. 81.)  
OA  
100  
RA  
100  
+ (TR x  
(TO x  
)
) =TM  
TO = Outdoor-Air Temperature  
OA = Percent of Outdoor Air  
TR = Return-Air Temperature  
RA = Percent of Return Air  
Damper Movement  
Damper movement from full open to full closed (or vice  
versa) takes 21/2 minutes.  
T
M = Mixed-Air Temperature  
Thermostats  
Once base ventilation has been determined, set the  
minimum damper position potentiometer to the correct  
position.  
The EconoMi$er IV control works with conventional  
thermostats that have a Y1 (cool stage 1), Y2 (cool stage  
2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The  
EconoMi$er IV control does not support space  
temperature sensors. Connections are made at the  
thermostat terminal connection board located in the main  
control box.  
The same equation can be used to determine the occupied  
or maximum ventilation rate to the building. For example,  
an output of 3.6 volts to the actuator provides a base  
ventilation rate of 5% and an output of 6.7 volts provides  
the maximum ventilation rate of 20% (or base plus 15 cfm  
per person). Use Fig. 82 to determine the maximum  
setting of the CO2 sensor. For example, an 1100 ppm  
setpoint relates to a 15 cfm per person design. Use the  
1100 ppm curve on Fig. 82 to find the point when the CO2  
sensor output will be 6.7 volts. Line up the point on the  
Occupancy Control  
The factory default configuration for the EconoMi$er IV  
control is occupied mode. Occupied status is provided by  
the black jumper from terminal TR to terminal N. When  
unoccupied mode is desired, install a field-supplied  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
graph with the left side of the chart to determine that the  
range configuration for the CO2 sensor should be 1800  
ppm. The EconoMi$er IV controller will output the 6.7  
volts from the CO2 sensor to the actuator when the CO2  
concentration in the space is at 1100 ppm. The DCV  
setpoint may be left at 2 volts since the CO2 sensor  
voltage will be ignored by the EconoMi$er IV controller  
until it rises above the 3.6 volt setting of the minimum  
position potentiometer.  
Once the fully occupied damper position has been  
determined, set the maximum damper demand control  
ventilation potentiometer to this position. Do not set to the  
maximum position as this can result in over-ventilation to  
the space and potential high humidity levels.  
4. Use the Up/Down button to toggle through each of  
the nine variables, starting with Altitude, until the  
desired setting is reached.  
5. Press Mode to move through the variables.  
6. Press Enter to lock in the selection, then press Mode  
to continue to the next variable.  
Dehumidification of Fresh Air with DCV (Demand  
Controlled Ventilation) Control  
If normal rooftop heating and cooling operation is not  
adequate for the outdoor humidity level, an energy  
recovery unit and/or a dehumidification option should be  
considered.  
EconoMi$er IV Preparation  
CO2 Sensor Configuration  
This procedure is used to prepare the EconoMi$er IV for  
troubleshooting. No troubleshooting or testing is done by  
performing the following procedure.  
The CO2 sensor has preset standard voltage settings that  
can be selected anytime after the sensor is powered up.  
(See Table 28.)  
NOTE: This procedure requires a 9-v battery, 1.2  
kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are  
not supplied with the EconoMi$er IV.  
IMPORTANT: Be sure to record the positions of all  
potentiometers before starting troubleshooting.  
Use setting 1 or 2 for Carrier equipment. (See Table 28.)  
1. Press Clear and Mode buttons. Hold at least 5  
seconds until the sensor enters the Edit mode.  
2. Press Mode twice. The STDSET Menu will appear.  
1. Disconnect power at TR and TR1. All LEDs should  
be off. Exhaust fan contacts should be open.  
2. Disconnect device at P and P1.  
3. Jumper P to P1.  
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm  
resistor across T and T1.  
5. Jumper TR to 1.  
6. Jumper TR to N.  
7. If connected, remove sensor from terminals SO and +.  
Connect 1.2 kilo-ohm 4074EJM checkout resistor  
across terminals SO and +.  
8. Put 620-ohm resistor across terminals SR and +.  
9. Set minimum position, DCV setpoint, and exhaust po-  
tentiometers fully CCW (counterclockwise).  
Table 28 – EconoMi$er IV Sensor Usage  
ECONOMI$ER IV WITH OUTDOOR AIR DRY  
BULB SENSOR  
Accessories Required  
None. The outdoor air dry bulb sensor is  
factory installed.  
APPLICATION  
Outdoor Air  
Dry Bulb  
Differential  
CRTEMPSN002A00*  
HH57AC078  
Dry Bulb  
Single Enthalpy  
Differential  
Enthalpy  
HH57AC078 and CRENTDIF004A00*  
CO for DCV  
2
Control using a  
Wall-Mounted  
CO Sensor  
33ZCSENCO2  
2
2
CO for DCV  
33ZCSENCO2† and  
33ZCASPCO2**  
O
R
Control using a  
Duct-Mounted  
CRCBDIOX005A00††  
CO Sensor  
10. Set DCV maximum position potentiometer fully CW  
(clockwise).  
11. Set enthalpy potentiometer to D.  
12. Apply power (24 vac) to terminals TR and TR1.  
Differential Enthalpy  
2
*
CRENTDIF004A00 and CRTEMPSN002A00 accessories are  
used on many different base units. As such, these kits may  
contain parts that will not be needed for installation.  
33ZCSENCO2 is an accessory CO sensor.  
2
** 33ZCASPCO2 is an accessory aspirator box required for duct-  
mounted applications.  
†† CRCBDIOX005A00 is an accessory that contains both  
33ZCSENCO2 and 33ZCASPCO2 accessories.  
To check differential enthalpy:  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
2. Place 620-ohm resistor across SO and +.  
3. Place 1.2 kilo-ohm resistor across SR and +. The  
Free Cool LED should be lit.  
4. Remove 620-ohm resistor across SO and +. The Free  
Cool LED should turn off.  
3. Use the Up/Down button to select the preset  
number. (See Table 28.)  
4. Press Enter to lock in the selection.  
5. Press Mode to exit and resume normal operation.  
The custom settings of the CO2 sensor can be changed  
anytime after the sensor is energized. Follow the steps  
below to change the non-standard settings:  
5. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
1. Press Clear and Mode buttons. Hold at least 5  
seconds until the sensor enters the Edit mode.  
2. Press Mode twice. The STDSET Menu will appear.  
3. Use the Up/Down button to toggle to the NONSTD  
menu and press Enter.  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Single Enthalpy  
5. Turn the Minimum Position potentiometer to mid-  
point. The actuator should drive to between 20 and  
80% open.  
6. Turn the Minimum Position Potentiometer fully CW.  
The actuator should drive fully open.  
7. Remove the jumper from TR and N. The actuator  
should drive fully closed.  
8. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
To check single enthalpy:  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
2. Set the enthalpy potentiometer to A (fully CCW). The  
Free Cool LED should be lit.  
3. Set the enthalpy potentiometer to D (fully CW). The  
Free Cool LED should turn off.  
4. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
Supply-Air Sensor Input  
To check supply-air sensor input:  
DCV (Demand Controlled Ventilation) and Power  
Exhaust  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
2. Set the Enthalpy potentiometer to A. The Free Cool  
LED turns on. The actuator should drive to between  
20 and 80% open.  
To check DCV and Power Exhaust:  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
2. Ensure terminals AQ and AQ1 are open. The LED for  
both DCV and Exhaust should be off. The actuator  
should be fully closed.  
3. Connect a 9-v battery to AQ (positive node) and AQ1  
(negative node). The LED for both DCV and Exhaust  
should turn on. The actuator should drive to between  
90 and 95% open.  
4. Turn the Exhaust potentiometer CW until the Exhaust  
LED turns off. The LED should turn off when the po-  
tentiometer is approximately 90%. The actuator  
should remain in position.  
3. Remove the 5.6 kilo-ohm resistor and jumper T to  
T1. The actuator should drive fully open.  
4. Remove the jumper across T and T1. The actuator  
should drive fully closed.  
5. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
EconoMi$er IV Troubleshooting Completion  
This procedure is used to return the EconoMi$er IV to  
operation. No troubleshooting or testing is done by  
performing the following procedure.  
5. Turn the DCV setpoint potentiometer CW until the  
DCV LED turns off. The DCV LED should turn off  
when the potentiometer is approximately 9-v. The ac-  
tuator should drive fully closed.  
6. Turn the DCV and Exhaust potentiometers CCW until  
the Exhaust LED turns on. The exhaust contacts will  
close 30 to 120 seconds after the Exhaust LED turns  
on.  
1. Disconnect power at TR and TR1.  
2. Set enthalpy potentiometer to previous setting.  
3. Set DCV maximum position potentiometer to previ-  
ous setting.  
4. Set minimum position, DCV setpoint, and exhaust po-  
tentiometers to previous settings.  
5. Remove 620-ohm resistor from terminals SR and +.  
6. Remove 1.2 kilo-ohm checkout resistor from termin-  
als SO and +. If used, reconnect sensor from termin-  
als SO and +.  
7. Remove jumper from TR to N.  
8. Remove jumper from TR to 1.  
7. Return EconoMi$er IV settings and wiring to normal  
after completing troubleshooting.  
DCV Minimum and Maximum Position  
To check the DCV minimum and maximum position:  
1. Make sure EconoMi$er IV preparation procedure has  
been performed.  
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon-  
nect wires at T and T1.  
2. Connect a 9-v battery to AQ (positive node) and AQ1  
(negative node). The DCV LED should turn on. The  
actuator should drive to between 90 and 95% open.  
3. Turn the DCV Maximum Position potentiometer to  
midpoint. The actuator should drive to between 20  
and 80% open.  
10. Remove jumper from P to P1. Reconnect device at P  
and P1.  
11. Apply power (24 vac) to terminals TR and TR1.  
WIRING DIAGRAMS  
See Fig. 83 and Fig. 84 for typical wiring diagrams.  
4. Turn the DCV Maximum Position potentiometer to  
fully CCW. The actuator should drive fully closed.  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
C08308  
Fig. 83 - 48TC Typical Unit Wiring Diagram - Power (A06, 208/230-3-60)  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Verify the following conditions:  
PRE--START--UP  
a. Make sure that condenser-fan blade are correctly  
positioned in fan orifice. See Condenser-Fan  
Adjustment section for more details.  
b. Make sure that air filter(s) is in place.  
c. Make sure that condensate drain trap is filled  
with water to ensure proper drainage.  
!
WARNING  
PERSONAL INJURY HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
1. Follow recognized safety practices and wear pro-  
tective goggles when checking or servicing refri-  
gerant system.  
2. Do not operate compressor or provide any electric  
power to unit unless compressor terminal cover is  
in place and secured.  
3. Do not remove compressor terminal cover until  
all electrical sources are disconnected.  
d. Make sure that all tools and miscellaneous loose  
parts have been removed.  
START--UP, GENERAL  
Unit Preparation  
Make sure that unit has been installed in accordance with  
installation instructions and applicable codes.  
Gas Piping  
4. Relieve all pressure from system before touching  
or disturbing anything inside terminal box if refri-  
gerant leak is suspected around compressor ter-  
minals.  
5. Never attempt to repair soldered connection while  
refrigerant system is under pressure.  
6. Do not use torch to remove any component. Sys-  
tem contains oil and refrigerant under pressure.  
To remove a component, wear protective goggles  
and proceed as follows:  
Check gas piping for leaks.  
!
WARNING  
UNIT OPERATION AND SAFETY HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Disconnect gas piping from unit when leak testing at  
pressure greater than 1/2 psig. Pressures greater than  
1/2 psig will cause gas valve damage resulting in  
hazardous condition. If gas valve is subjected to  
pressure greater than 1/2 psig, it must be replaced  
before use. When pressure testing field-supplied gas  
piping at pressures of 1/2 psig or less, a unit connected  
to such piping must be isolated by manually closing  
the gas valve.  
a. Shut off electrical power and then gas to unit.  
b. Recover refrigerant to relieve all pressure from  
system using both high-pressure and low  
pressure ports.  
c. Cut component connection tubing with tubing  
cutter and remove component from unit.  
d. Carefully unsweat remaining tubing stubs  
when necessary. Oil can ignite when exposed  
to torch flame.  
Return--Air Filters  
Make sure correct filters are installed in unit (see  
Appendix II - Physical Data). Do not operate unit without  
return-air filters.  
Proceed as follows to inspect and prepare the unit for  
initial start-up:  
1. Remove all access panels.  
Outdoor--Air Inlet Screens  
2. Read and follow instructions on all WARNING,  
CAUTION, and INFORMATION labels attached to,  
or shipped with, unit.  
Outdoor-air inlet screen must be in place before operating  
unit.  
3. Make the following inspections:  
Compressor Mounting  
a. Inspect for shipping and handling damages such  
as broken lines, loose parts, or disconnected  
wires, etc.  
Compressors are internally spring mounted. Do not loosen  
or remove compressor hold down bolts.  
Internal Wiring  
b. Inspect for oil at all refrigerant tubing connec-  
tions and on unit base. Detecting oil generally  
indicates a refrigerant leak. Leak-test all refri-  
gerant tubing connections using electronic leak  
detector, halide torch, or liquid-soap solution.  
Check all electrical connections in unit control boxes.  
Tighten as required.  
Refrigerant Service Ports  
c. Inspect all field-wiring and factory-wiring con-  
nections. Be sure that connections are completed  
and tight. Be sure that wires are not in contact  
with refrigerant tubing or sharp edges.  
Each unit system has two 1/4” SAE flare (with check  
valves) service ports: one on the suction line, and one on  
the compressor discharge line. Be sure that caps on the  
ports are tight.  
d. Inspect coil fins. If damaged during shipping and  
handling, carefully straighten fins with a fin  
comb.  
Compressor Rotation  
On 3-phase units with scroll compressors, it is important  
to be certain compressor is rotating in the proper  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
direction. To determine whether or not compressor is  
rotating in the proper direction:  
3. Set system switch selector at HEAT position and fan  
switch at AUTO. or ON position. Set heating temper-  
ature lever above room temperature.  
1. Connect service gauges to suction and discharge pres-  
sure fittings.  
4. The induced-draft motor will start.  
5. After a call for heating, the main burners should light  
within 5 seconds. If the burner does not light, then  
there is a 22-second delay before another 5-second  
try. If the burner still does not light, the time delay is  
repeated. If the burner does not light within 15  
minutes, there is a lockout. To reset the control, break  
the 24 v power to W1.  
6. The evaporator-fan motor will turn on 45 seconds  
after burner ignition.  
7. The evaporator-fan motor will turn off in 45 seconds  
after the thermostat temperature is satisfied.  
2. Energize the compressor.  
3. The suction pressure should drop and the discharge  
pressure should rise, as is normal on any start-up.  
If the suction pressure does not drop and the discharge  
pressure does not rise to normal levels:  
4. Note that the evaporator fan is probably also rotating  
in the wrong direction.  
5. Turn off power to the unit and install lockout tag.  
6. Reverse any two of the unit power leads.  
7. Re-energize to the compressor. Check pressures.  
8. Adjust airflow to obtain a temperature rise within the  
range specified on the unit nameplate.  
The suction and discharge pressure levels should now  
move to their normal start-up levels.  
NOTE: The default value for the evaporator-fan motor  
on/off delay is 45 seconds. The Integrated Gas Unit  
Controller (IGC) modifies this value when abnormal limit  
switch cycles occur. Based upon unit operating conditions,  
the on delay can be reduced to 0 seconds and the off delay  
can be extended to 180 seconds. When one flash of the  
LED is observed, the evaporator-fan on/off delay has  
been modified.  
NOTE: When the compressor is rotating in the wrong  
direction, the unit will make an elevated level of noise  
and will not provide cooling.  
Cooling  
Set space thermostat to OFF position. To start unit, turn on  
main power supply. Set system selector switch at COOL  
position and fan switch at AUTO. position. Adjust  
If the limit switch trips at the start of the heating cycle  
during the evaporator on delay, the time period of the on  
delay for the next cycle will be 5 seconds less than the  
time at which the switch tripped. (Example: If the limit  
switch trips at 30 seconds, the evaporator-fan on delay for  
the next cycle will occur at 25 seconds.) To prevent  
short-cycling, a 5-second reduction will only occur if a  
minimum of 10 minutes has elapsed since the last call for  
heating.  
thermostat to  
Compressor starts on closure of contactor.  
a
setting below room temperature.  
Check unit charge. Refer to Refrigerant Charge section.  
Reset thermostat at a position above room temperature.  
Compressor will shut off. Evaporator fan will shut off  
after a 30-second delay.  
To shut off unit, set system selector switch at OFF  
position. Resetting thermostat at a position above room  
temperature shuts unit off temporarily until space  
temperature exceeds thermostat setting.  
The evaporator-fan off delay can also be modified. Once  
the call for heating has ended, there is a 10-minute period  
during which the modification can occur. If the limit  
switch trips during this period, the evaporator-fan off  
delay will increase by 15 seconds. A maximum of 9 trips  
can occur, extending the evaporator-fan off delay to 180  
seconds.  
Main Burners  
Main burners are factory set and should require no  
adjustment.  
To check ignition of main burners and heating controls,  
move thermostat setpoint above room temperature and  
verify that the burners light and evaporator fan is  
energized. Check heating effect, then lower the thermostat  
setting below the room temperature and verify that the  
burners and evaporator fan turn off.  
To restore the original default value, reset the power to the  
unit.  
To shut off unit, set system selector switch at OFF  
position. Resetting heating selector lever below room  
temperature will temporarily shut unit off until space  
temperature falls below thermostat setting.  
Refer to Tables 11 and 12 for the correct orifice to use at  
high altitudes.  
Ventilation (Continuous Fan)  
Heating  
Set fan and system selector switches at ON and OFF  
positions, respectively. Evaporator fan operates  
continuously to provide constant air circulation. When the  
evaporator-fan selector switch is turned to the OFF  
position, there is a 30-second delay before the fan turns  
off.  
1. Purge gas supply line of air by opening union ahead  
of the gas valve. If gas odor is detected, tighten union  
and wait 5 minutes before proceeding.  
2. Turn on electrical supply and manual gas valve.  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START  
                                                                                                              
-UP, RTU-MP CONTROL  
                                                                                                                             
subsequent resets to factory defaults if the switch is left at  
position 1.  
START--UP, PREMIERLINK CONTROLS  
To cause a reset of the non-volatile memory (to factory  
defaults), turn the controller power off if it is on, move the  
switch from position 1 to position 0, and then apply power  
to the controller for a minimum of 5 seconds. At this  
point, no action occurs, but the controller is now ready for  
the memory to reset. Remove power to the controller  
again and move the switch from position 0 to position 1.  
This time, when power is applied, the memory will reset  
to factory defaults. The controller address will return to  
bus 0 element 31, indicating that memory reset occurred.  
!
WARNING  
ELECTRICAL OPERATION HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
The unit must be electrically grounded in accordance  
with local codes and NEC ANSI/NFPA 70 (American  
National Standards Institute/National Fire Protection  
Association.)  
Refer to Installation Instruction 33CS-58SI for full  
discussion on configuring the PremierLink control system.  
Use the Carrier network communication software to start  
up and configure the PremierLink controller.  
Changes can be made using the ComfortWORKSr  
software, ComfortVIEWt software, Network Service  
Tool, System Pilott device, or Touch Pilott device. The  
System Pilot and Touch Pilot are portable interface  
devices that allow the user to change system set-up and  
setpoints from a zone sensor or terminal control module.  
During start-up, the Carrier software can also be used to  
verify communication with PremierLink controller.  
Field Service Test, explained below, will assist in proper  
start-up. Configuration of unit parameters, scheduling  
options, and operation are also discussed in this section.  
Field Service Test  
The Field Service Test function can be used to verify  
proper operation of compressors, heating stages, indoor  
NOTE: All set-up and setpoint configurations are factory  
set and field-adjustable.  
fan,  
power  
exhaust  
fans,  
economizer,  
and  
dehumidification. Use of Field Service Test is  
recommended at initial system start up and during  
troubleshooting. See Form 48-50H-T-2T, Appendix A for  
Field Service Test Mode table.  
Field Service Test mode has the following changes from  
normal operation:  
For specific operating instructions, refer to the literature  
provided with user interface software.  
Perform System Check--Out  
1. Check correctness and tightness of all power and  
communication connections.  
2. At the unit, check fan and system controls for proper  
operation.  
3. At the unit, check electrical system and connections  
of any optional electric reheat coil.  
S Outdoor air temperature limits for cooling circuits,  
economizer, and heating are ignored.  
S Normal compressor time guards and other staging delays  
are ignored.  
S The status of Alarms (except Fire and Safety chain) is  
ignored but all alerts and alarms are still broadcasted on  
the network.  
Field Service Test can be turned ON/OFF at the unit  
display or from the network. Once turned ON, other  
entries may be made with the display or through the  
network. To turn Field Service Test on, change the value  
of Test Mode to ON, to turn Field Service Test off, change  
the value of Test Mode to OFF.  
4. Check to be sure the area around the unit is clear of  
construction dirt and debris.  
5. Check that final filters are installed in the unit. Dust  
and debris can adversely affect system operation.  
6. Verify that the PremierLink controls are properly con-  
nected to the CCN bus.  
Initial Operation and Test  
Perform the following procedure:  
NOTE: Service Test mode is password protected when  
accessing from the display. Depending on the unit model,  
factory-installed options, and field-installed accessories,  
some of the Field Service Test functions may not apply.  
The independent outputs (IndpOutputs) submenu is used  
to change output status for the supply fan, economizer,  
and Power Exhaust. These independent outputs can  
operate simultaneously with other Field Service Test  
modes. All outputs return to normal operation when Field  
Service Test is turned off.  
The Cooling submenu is used to change output status for  
the individual compressors and the dehumidification relay.  
Compressor starts are not staggered. The fans and heating  
service test outputs are reset to OFF for the cooling  
service test. Indoor fans and outdoor fans are controlled  
1. Apply 24 vac power to the control.  
2. Connect the service tool to the phone jack service  
port of the controller.  
3. Using the Service Tool, upload the controller from  
address 0, 31 at 9600 baud rate. The address may be  
set at this time. Make sure that Service Tool is con-  
nected to only one unit when changing the address.  
Memory Reset  
DIP switch 4 causes an E-squared memory reset to  
factory defaults after the switch has been moved from  
position 0 to position 1 and the power has been restored.  
To enable the feature again, the switch must be put back  
to the 0 position and power must be restored; this prevents  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
normally to maintain proper unit operation. All normal  
cooling alarms and alerts are functional.  
Factory Default = 0 hr  
NOTE: Setting this configuration timer to 0, disables the  
NOTE: Circuit A is always operated with Circuit B due  
to outdoor fan control on Circuit A. Always test Circuit A  
first, and leave it on to test other Circuits.  
The Heating submenu is used to change output status for  
the individual heat stages, gas or electric. The fans and  
cooling service test outputs are reset to OFF for the  
heating service test. All normal heating alarms and alerts  
are functional.  
alarm.  
Compressor2 Service Hours  
This refers to the timer set for the Compressor 2 Runtime  
Alarm. After the number of hours set on this point is  
exceeded the corresponding alarm will be generated, and  
must be manually cleared on the alarm rest screen after  
the maintenance has been completed. The timer will then  
begin counting its runtime again for the next maintenance  
interval  
Configuration  
Factory Default = 0 hr  
NOTE: Setting this configuration timer to 0, disables the  
The RTU-MP controller configuration points affect the  
unit operation and/or control. Review and understand the  
meaning and purpose of each configuration point before  
changing it from the factory default value. The submenus  
containing configuration points are as follows: Unit,  
Cooling, Heating, Inputs, Economizer, IAQ, Clock-Set,  
and User Password (USERPW). Each configuration point  
is described below under its according submenu. See  
Form 48-50H-T-2T, Appendix for display tables.  
alarm.  
Cooling  
Number of Compressor Stages  
This refers to the number of mechanical cooling stages  
available on a specific unit. Set this point to “One Stage”  
if there is one compressor in the specific unit, set to “Two  
Stage” if there are two compressors in the unit, and set to  
“None” if economizer cooling ONLY is desired.  
Unit  
Start Delay  
Factory Default = One Stage for 1 compressor units  
Two Stage for 2 compressor units  
This refers to the time delay the unit will wait after power  
up before it pursues any specific operation.  
Cooling/Econ SAT Low Setpt  
Factory Default = 5 sec  
Range = 0-600 sec  
The supply air temperature must remain above this value  
to allow cooling with the economizer and/or compressors.  
There is 5_F plus and minus deadband to this point. If the  
SAT falls below this value during cooling, all compressors  
will be staged off. The economizer will start to ramp  
down to minimum position when the SAT = this  
configuration +5_F.  
Filter Service Hours  
This refers to the timer set for the Dirty Filter Alarm.  
After the number of runtime hours set on this point is  
exceeded the corresponding alarm will be generated, and  
must be manually cleared on the alarm reset screen after  
the maintenance has been completed. The timer will then  
begin counting its runtime again for the next maintenance  
interval.  
Factory Default = 600 hr  
NOTE: Setting this configuration timer to 0, disables the  
alarm.  
Factory Default = 50_F  
Range = 45-75_F  
Cooling Lockout Temp  
This defines the minimum outdoor air temperature that  
cooling mode can be enabled and run. If the OAT falls  
below this threshold during cooling, then compressor  
cooling will not be allowed.  
Supply Fan Service Hours  
This refers to the timer set for the Supply Fan Runtime  
Alarm. After the number of runtime hours set on this point  
is exceeded the corresponding alarm will be generated,  
and must be manually cleared on the alarm reset screen  
after the maintenance has been completed. The timer will  
then begin counting its runtime again for the next  
maintenance interval.  
Factory Default = 0 hr  
NOTE: Setting this configuration timer to 0, disables the  
alarm.  
Factory Default = 45_F  
Range = 0-65_F  
Heating  
Heating SAT High Setpt  
The supply air temperature must remain below this value  
to allow heating. There is 5_F plus and minus deadband to  
this point. If the SAT rises above this value during heating  
the heat stages will begin to decrease until the SAT has  
dropped below this value.  
Factory Default = 120_F  
Range = 95-150_F  
Compressor1 Service Hours  
This refers to the timer set for the Compressor 1 Runtime  
Alarm. After the number of runtime hours set on this point  
is exceeded the corresponding alarm will be generated,  
and must be manually cleared on the alarm reset screen  
after the maintenance has been completed. The timer will  
then begin counting its runtime again for the next  
maintenance interval.  
Heating Lockout Temp  
This defines the maximum outdoor air temperature that  
heating mode can be enabled and run. If the OAT rises  
above this threshold during heating, then heating will not  
be allowed.  
Factory Default = 65_F  
Range = 49-95_F  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Inputs  
Input 1 Function  
NOTE: For installation of inputs and field installed  
accessories, refer to the appropriate sections.  
This input is an analog input and can be configured to be  
one of five different inputs: No Sensor, IAQ Sensor, OAQ  
Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 1  
is wired to pin J4-5.  
Input 3  
This input is a discrete input and can be configured to be  
one of five different inputs: No Function, Compressor  
Safety, Fan Status, Filter Status, or Remote Occupancy.  
This input can also be configured to be either Normally  
Open (N/O) or Normally Closed (N/C). Input 3 is factory  
wired to pin J1-2. Field accessories get wired to its  
parallel pin J5-5. Do not connect inputs to both locations,  
one function per input.  
Factory Default = No Sensor  
Input 2 Function  
This input is an analog input and can be configured to be  
one of five different inputs: No Sensor, IAQ Sensor, OAQ  
Sensor, Space RH Sensor, or Outdoor RH Sensor. Input 2  
is wired to pin J4-2.  
Factory Default = No Sensor  
Factory Default = Compressor Safety and N/O  
Setpoint Slider Range  
NOTE: Compressor Safety input comes from the CLO  
board. J1-2 is always factory wired to TB1-8 (X) terminal  
on the unit. If the unit has a CLO board, do not configure  
input 3 for anything but Compressor Safety.  
This sets the slider range of the space sensor (with this  
built in function). The slider is used to offset the current  
control setpoint.  
Factory Default = 5 n_F  
Range = 0-15 n_F  
Input 5  
This input is a discrete input and can be configured to be  
one of five different inputs: No Function, Fire Shutdown,  
Fan Status, Filter Status, or Remote Occupancy. This  
input can also be configured to be either Normally Open  
(N/O) or Normally Closed (N/C). Input 5 is factory wired  
to pin J1-10. Field accessories get wired to its parallel pin  
J5-3. Do not connect inputs to both locations, one  
function per input.  
T55/56 Override Duration  
This sets the occupancy override duration when the  
override button is pushed on the space sensor.  
Factory Default = 1 hr  
Range = 0-24 hr  
IAQ Low Reference @ 4mA  
This is used when an IAQ sensor is installed on Input 1 or  
2. This value is displayed and used when 4mA is seen at  
the input.  
Factory Default = Fire Shutdown and N/C  
NOTE: Fire Shutdown input comes from TB4-7. J1-10  
is always factory wired to TB4-7. Only change input 5s  
function if absolutely needed.  
Factory Default = 0 PPM  
Range = 0-400 PPM  
Input 8  
IAQ High Reference @ 20mA  
This input is a discrete input and can be configured to be  
one of five different inputs: No Function, Enthalpy  
Switch, Fan Status, Filter Status, or Remote Occupancy.  
This input can also be configured to be either Normally  
Open (N/O) or Normally Closed (N/C). Input 8 is factory  
wired to pin J2-6. Field accessories get wired to its  
parallel pin J5-1. Do not connect inputs to both locations,  
one function per input.  
This is used when an IAQ sensor is installed on Input 1 or  
2. This value is displayed and used when 20mA is seen at  
the input.  
Factory Default = 2000 PPM  
Range = 0-5000 PPM  
NOTE: IAQ low Reference @ 4mA and IAQ High  
Reference @ 20mA are used to set the linear curve of mA  
vs. PPM.  
Factory Default = No Function and N/O  
OAQ Low Reference @ 4mA  
Input 9  
This is used when an OAQ sensor is installed on Input 1  
or 2. This value is displayed and used when 4mA is seen  
at the input.  
This input is a discrete input and can be configured to be  
one of five different inputs: No Function, Humidistat, Fan  
Status, Filter Status, or Remote Occupancy. This input can  
also be configured to be either Normally Open (N/O) or  
Normally Closed (N/C). Input 9 is factory and field wired  
to pin J5-7. Do not connect inputs to both locations, one  
function per input.  
Factory Default = 0 PPM  
Range = 0-400 PPM  
OAQ High Reference @ 20mA  
This is used when an OAQ sensor is installed on Input 1  
or 2. This value is displayed and used when 20mA is seen  
at the input.  
Factory Default = Humidistat and N/O  
Space Sensor Type  
Factory Default = 2000 PPM  
Range = 0-5000 PPM  
NOTE: OAQ low Reference @ 4mA and OAQ High  
Reference @ 20mA are used to set the linear curve of mA  
vs. PPM.  
This tells the controller what type of space sensor is  
installed to run the unit. The three types that can be used  
are the T55 space sensor, the T56 space sensor, or the RS  
space sensor.  
Factory Default = T55 Type  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Economizer  
USERPW  
This submenu screen allows you to change the user  
password to a four number password of choice. The User  
password change screen is only accessible with the  
Administrator Password (1111). The ADMIN password  
will always override the user password.  
Economizer Exists  
This point tells the controller if there is an economizer  
installed on the unit.  
Factory Default = NO if no economizer  
YES if there is an economizer installed  
Economizer Minimum Position  
OPERATING SEQUENCES  
This defines the lowest economizer position when the  
indoor fan is running and the building is occupied.  
Base Unit Controls  
Factory Default = 20%  
Range = 0-100 %  
Cooling, Units Without Economizer  
When thermostat calls for cooling, terminals G and Y1 are  
energized. The indoor-fan contactor (IFC) and  
compressor contactor are energized and indoor-fan motor,  
compressor, and outdoor fan starts. The outdoor fan motor  
runs continuously while unit is cooling.  
Economizer High OAT Lockout  
If the outdoor air temperature rises above this value,  
economizer cooling will be disabled and dampers will  
return and stay at minimum position.  
Factory Default = 75_F  
Range = 55-80_F  
Heating, Units Without Economizer  
When the thermostat calls for heating, terminal W1 is  
energized. To prevent thermostat short-cycling, the unit is  
locked into the Heating mode for at least 1 minute when  
W1 is energized. The induced-draft motor is energized  
and the burner ignition sequence begins. The indoor  
(evaporator) fan motor (IFM) is energized 45 seconds  
after a flame is ignited. On units equipped for two stages  
of heat, when additional heat is needed, W2 is energized  
and the high-fire solenoid on the main gas valve (MGV)  
is energized. When the thermostat is satisfied and W1 is  
deenergized, the IFM stops after a 45-second time off  
delay.  
Power Exhaust Setpt  
When the economizer damper position opens above this  
point the power exhaust operation will begin. When the  
damper position falls 10% below the setpoint, the power  
exhaust will shutdown.  
Factory Default = 50%  
Range = 20-90 %  
NOTE: This point is only used when Continuous Occ  
Exhaust = NO  
Continuous Occ Exhaust  
This point tells the controller when to run the power  
exhaust if equipped on the unit. If set to YES, the power  
exhaust will be on all the time when in occupied mode  
and will be off when in unoccupied mode. If set to NO the  
power exhaust will be controlled by the Power Exhaust  
Setpoint.  
Cooling, Unit With EconoMi$er IV  
For Occupied mode operation of EconoMi$er IV, there  
must be a 24-v signal at terminals TR and N (provided  
through PL6-3 from the unit’s IFC coil). Removing the  
signal at N places the EconoMi$er IV control in  
Unoccupied mode.  
Factory Default = NO  
IAQ  
During Occupied mode operation, indoor fan operation  
will be accompanied by economizer dampers moving to  
Minimum Position setpoint for ventilation. If indoor fan is  
off, dampers will close. During Unoccupied mode  
operation, dampers will remain closed unless a Cooling  
(by free cooling) or DCV demand is received.  
Max Differential CO2 Setpt  
If the difference between indoor an outdoor air quality  
becomes greater then this value the damper position will  
stay at the IAQ Greatest Min Dmpr Pos. configuration  
point  
Factory Default = 650 PPM  
Range = 300-950 PPM  
Integrated EconoMi$er IV operation on 48TC single  
compressor model requires a 2-stage thermostat (Y1 and  
Y2 switches).  
IAQ Greatest Min Dmpr Pos.  
This is the greatest minimum position the economizer will  
open to while trying to control the indoor air quality, CO2  
differential.  
When free cooling using outside air is not available, the  
unit cooling sequence will be controlled directly by the  
space thermostat as described above as Cooling, Without  
Economizer. Outside air damper position will be closed or  
Minimum Position as determined by occupancy mode and  
fan signal.  
Factory Default = 50% open  
Range = 10-60% open  
Clockset  
This submenu screen allows you to set the date and time  
manually. The Daylight Savings Time (DST) can also be  
changed here. The date and time is automatically set when  
ever software is downloaded. The clock is a 24 hour clock  
and not am/pm. The time should be verified (and maybe  
changed) according to unit location and time zone.  
When free cooling is available as determined by the  
appropriate changeover command (dry bulb, outdoor  
enthalpy, differential dry bulb or differential enthalpy), a  
call for cooling (Y1 closes at the thermostat) will cause  
the economizer control to modulate the dampers open and  
closed to maintain the unit supply air temperature at 50 to  
55_F. Compressor will not run.  
Factory Default = Eastern Standard Time  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
During free cooling operation, a supply air temperature  
(SAT) above 50_F will cause the dampers to modulate  
between Minimum Position setpoint and 100% open. With  
SAT from 50_F to 45_F, the dampers will maintain at the  
Minimum Position setting. With SAT below 45_F, the  
outside air dampers will be closed. When SAT rises to  
48_F, the dampers will re-open to Minimum Position  
setting.  
suitable for economizer cooling when an economizer  
damper is available. A valid OAT, SPT (CCN space  
temperature) and SAT (supply air temperature) sensor  
MUST be installed for proper economizer operation. It  
recommended that an outdoor or differential enthalpy  
sensor also be installed. If one is not present, then a  
jumper is needed on the ENTH input on J4, which will  
indicate that the enthalpy will always be low. Economizer  
operation will be based only on outdoor air dry bulb  
temperature. The conditions are suitable when: enthalpy is  
low, OAT is less than OATL High Lockout for TSTAT,  
and OAT is less than OATMAX, the high setpoint for free  
cooling. The default for OATL is 65_F. The default for  
OATMAX is 75_F.  
Should 100% outside air not be capable of satisfying the  
space temperature, space temperature will rise until Y2 is  
closed. The economizer control will call for compressor  
operation. Dampers will modulate to maintain SAT at 50  
to 55_F concurrent with compressor operation. The Low  
Ambient Lockout Thermostat will block compressor  
operation with economizer operation below 42_F outside  
air temperature.  
When all of the above conditions are satisfied and all the  
required sensors are installed, the PremierLink controller  
will use the economizer for cooling. One of three different  
control routines will be used depending on the  
temperature of the outside air. The routines use a PID loop  
to control the SAT to a supply air setpoint (SASP) based  
on the error from setpoint (SASPSAT). The SASP is  
determined by the routine.  
When space temperature demand is satisfied (thermostat  
Y1 opens), the dampers will return to Minimum Damper  
position if indoor fan is running or fully closed if fan is  
off.  
If accessory power exhaust is installed, the power exhaust  
fan motors will be energized by the economizer control as  
the dampers open above the PE-On setpoint and will be  
de-energized as the dampers close below the PE-On  
setpoint.  
If an economizer is not available or the conditions are not  
met for the following economizer routines below, the  
compressors 1 and 2 will be cycled based on Y1 and Y2  
inputs respectively.  
Damper movement from full closed to full open (or vice  
versa) will take between 1-1/2 and 2-1/2 minutes.  
Any time the compressors are running, the PremierLink  
controller will lock out the compressors if the SAT  
becomes too low. These user configurable settings are  
found in the SERVICE configuration table:  
Heating With EconoMi$er IV  
During Occupied mode operation, indoor fan operation  
will be accompanied by economizer dampers moving to  
Minimum Position setpoint for ventilation. If indoor fan is  
off, dampers will close. During Unoccupied mode  
operation, dampers will remain closed unless a DCV  
demand is received.  
Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F)  
(default is 55_F)  
Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F)  
(default is 50_F)  
After a compressor is locked out, it may be started again  
after a normal time-guard period and the supply-air  
temperature has increased at least 8_F above the lockout  
setpoint.  
When the room temperature calls for heat (W1 closes), the  
heating controls are energized as described in Heating,  
Unit Without Economizer above.  
PremierLink Control  
Routine No. 1: If the OAT DXLOCK (OAT DX lockout  
temperature) and DX Cooling Lockout is enabled when  
Y1 input is energized, the economizer will be modulated  
to maintain SAT at the Supply Air Setpoint (SASP) =  
SATLO1 + 3_F (Supply Air Low Temp lockout for  
compressor 1). When Y2 is energized, the economizer  
will be modulated to control to a lower SASP = SATLO2  
+ 3_F (Supply Air Low Temp lockout for compressor no.  
2). Mechanical cooling is locked out and will not be  
energized.  
THERMOSTAT MODE — If the PremierLink controller  
is configured for Thermostat mode (TSTAT), it will  
control only to the thermostat inputs on J4. These inputs  
can be overridden through CCN communication via the  
CV_TSTAT points display table. When in this mode, the  
fire safety shutdown (FSD) input cannot be used, so any  
fire/life safety shutdown must be physically wired to  
disable the 24 vac control circuit to the unit.  
Indoor Fan — The indoor fan output will be energized  
whenever there is 24 vac present on the G input. The  
indoor fan will be turned on without any delay and the  
economizer damper will open to its minimum position if  
the unit has a damper connected to the controller. This  
will also occur if the PremierLink controller has been  
configured for electric heat or heat pump operation.  
Routine No. 2: If DXLOCK (or DX Cooling Lockout is  
disabled) < OAT 68_F when Y1 input is energized, the  
economizer will be modulated to maintain SAT at SASP =  
SATLO1 + 3_F. If the SAT > SASP + 5_F and the  
economizer position > 85% then the economizer will  
close the to minimum position for three minutes or until  
the SAT > 68_F. The economizer integrator will then be  
reset and begin modulating to maintain the SASP after  
stage one has been energized for 90 seconds.  
Cooling — For cooling operation, there must be 24 vac  
present on G. When G is active, the PremierLink  
controller will then determine if outdoor conditions are  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When Y2 is energized, the economizer will be modulated  
to control to a lower supply air setpoint SASP= SATLO2  
+ 3_F If the SAT > SASP + 5_F it will close the  
economizer to minimum position for 3 minutes, reset the  
integrator for the economizer, then start modulating the  
economizer to maintain the SASP after the stage two has  
been on for 90 seconds. This provides protection for the  
compressor against flooded starts and allow refrigerant  
flow to stabilize before modulating the economizer again.  
By using return air across the evaporator coil just after the  
compressor has started allows for increased refrigerant  
flow rates providing better oil return of any oil washed out  
during compressor start-up.  
minimum position (MDP) and the greatest value becomes  
the final minimum damper position (IQMP). If the  
calculated IAQ Minimum Position is greater than the IAQ  
maximum damper position (IAQMAXP) decision in the  
SERVICE configuration table, then it will be clamped to  
IAQMAXP value.  
If IAQ is configured for low priority, the positioning of  
the economizer damper can be overridden by comfort  
requirements. If the SAT < SASP -8_F and both stages of  
heat are on for more then 4 minutes or the SAT > SASP +  
5_F and both stages of cooling on for more then 4 minutes  
then the IAQ minimum damper position will become 0  
and the IQMP = MDP. IAQ mode will resume when the  
SAT > SASP -8_F in heating or the SAT < SASP + 5_F in  
cooling.  
Routine No. 3: If the OAT > 68_F and the enthalpy is low  
and the OAT < SPT then the economizer will open to  
100% and compressors 1 and 2 will be cycled based on  
Y1 and Y2 inputs respectively. If any of these conditions  
are not met the economizer will go to minimum position.  
If the PremierLink controller is configured for 1 stage of  
heat and cool or is only using a single stage thermostat  
input, this function will not work as it requires the both  
Y1 and Y2 or W1 and W2 inputs to be active. In this  
application, it is recommended that the user configure  
IAQ priority for high.  
If there is no call for heating or cooling, the economizer,  
if available, will maintain the SASP at 70_F.  
Heating — For gas or electric heat, HS1 and HS2 outputs  
will follow W1 and W2 inputs respectively. The fan will  
also be turned on if it is configured for electric heat.  
If IAQ is configured for high priority and the OAT < 55_F  
and the SAT < (SPT -10_F), the algorithm will enable the  
heat stages to maintain the SAT between the SPT and the  
SPT + 10_F.  
Heating may also be energized when an IAQ sensor  
installed and has overridden the minimum economizer  
damper position. If the OAT < 55_F and an IAQ sensor is  
installed and the IAQ minimum position > minimum  
damper position causing the SAT to decrease below the  
SPT - 10_F, then the heat stages will be cycled to temper  
the SAT to maintain a temperature between the SPT and  
the SPT + 10_F.  
CCN SENSOR MODE — When the PremierLink  
controller is configured for CCN control, it will control  
the compressor, economizer and heating outputs based its  
own space temperature input and setpoints or those  
received from Linkage. An optional CO2 IAQ sensor  
mounted in the space or received through communications  
can also influence the economizer and heating outputs.  
The PremierLink controller does not have a hardware  
clock so it must have another device on the CCN  
communication bus broadcasting time. The controller will  
maintain its own time once it has received time as long as  
it has power and will send a request for time once a  
minute until it receives time when it has lost power and  
power is restored. The controller will control to  
unoccupied setpoints until it has received a valid time.  
The controller must have valid time in order to perform  
any broadcast function, follow an occupancy schedule,  
perform IAQ pre-occupancy purge and many other  
functions as well. The following sections describe the  
operation for the functions of the PremierLink controller.  
Auxiliary Relay configured for Exhaust Fan — If the  
Auxiliary Relay is configured for exhaust fan (AUXOUT  
= 1) in the CONFIG configuration table and Continuous  
Power Exhaust (MODPE) is enable in the SERVICE  
configuration table then the output (HS3) will be  
energized whenever the G input is on. If the MODPE is  
disabled then output will be energized based on the Power  
Exhaust Setpoint (PES) in the SETPOINT table.  
Indoor Air Quality — If the optional indoor air quality  
(IAQI) sensor is installed, the PremierLink controller will  
maintain indoor air quality within the space at the  
user-configured differential setpoint (IAQD) in the  
CONFIG configuration table. The setpoint is the  
difference between the IAQI and an optional outdoor air  
quality sensor (OAQ). If the OAQ is not present then a  
fixed value of 400 ppm is used. The actual space IAQ  
setpoint (IAQS) is calculated as follows:  
Indoor Fan — The indoor fan will be turned on whenever  
any one of the following conditions are met:  
S If the PremierLink controller is in the occupied mode and  
ASHRAE 90.1 Supply Fan is configured for Yes in the  
CONFIG table. This will be determined by its own  
internal occupancy schedule if it is programmed to  
follow its local schedule or broadcast its local schedule as  
a global schedule, or following a global schedule  
broadcast by another device.  
IAQS = IAQD + OAQ (OAQ = 400 ppm if not present)  
As air quality within the space changes, the minimum  
position of the economizer damper will be changed also  
thus allowing more or less outdoor air into the space  
depending on the relationship of the IAQI to the IAQS.  
The IAQ algorithm runs every 30 seconds and calculates  
IAQ minimum position value using a PID loop on the  
IAQI deviation from the IAQS. The IAQ minimum  
position is then compared against the user configured  
S If PremierLink controller is in the occupied mode and  
ASHRAE 90.1 Supply Fan is configured for No and there  
is a heat or cool demand (fan auto mode)  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S If the PremierLink controller is in the occupied mode and  
ASHRAE 90.1 Supply Fan is configured for Yes when  
Linkage is active and the Linkage Coordinator device is  
sending an occupied mode flag  
If all of the above conditions are met, the CCSR will be  
calculated, otherwise it is set to its maximum value and  
DX stages is set to 0. If only the last condition is not true  
and an economizer is available, it will be used to cool the  
space.  
S When Temperature Compensated Start is active  
S When Free Cool is active  
The submaster loop uses the CCSR compared to the actual  
SAT to determine the required number of capacity stages  
to satisfy the load. There is a programmable minimum  
internal time delay of 3 to 5 minutes on and 2 to 5 minutes  
off for the compressors to prevent short cycling. There is  
also a 3-minute time delay before bringing on the second  
stage compressor. If the PremierLink controller is  
configured for Heat Pump and AUXOUT is configured for  
Reversing Valve Cool, the H3_EX_RV output will  
energize 2 seconds after the first compressor is energized  
and stay energized until there is a demand for heat. If  
AUXOUT is configured for Reversing Valve Heat, then  
the H3_EX_RV contact will be deenergized when there is  
a demand for cooling. An internal 5 to 10-minute  
user-programmable time guard between modes prevents  
rapid cycling between modes when used in a single zone  
application. The Time Guard is lowered to 3 minutes  
when Linkage is active to allow the 3Vt linkage  
coordinator to have better control of the PremierLink  
controller when used as the air source for the 3V control  
system.  
S When Pre-Occupancy Purge is active  
S Whenever there is a demand for cooling or heating in the  
unoccupied mode  
S Whenever the Remote Contact input is configured for  
Remote Contact (RC_DC=1 in SERVICE table) and it is  
closed or the point is forced Closed via communications  
in the STATUS01 points display table (remote contact  
closed = occupied, remote contact open = unoccupied)  
S Whenever the H3_EX_RV point is configured for  
Dehumidification (AUXOUT=5 in CONFIG table) and it  
is in the unoccupied mode and the indoor RH exceeds the  
unoccupied humidity setpoint  
S Whenever the Supply Fan Relay point is forced On in the  
STATUS01 points display table  
The fan will also continue to run as long as compressors  
are on when transitioning from occupied to unoccupied  
with the exception of Fire Shutdown mode. If the Fire  
Shutdown input point is closed or forced in the  
STATUS01 points display table, the fan will be shutdown  
immediately regardless of the occupancy state or demand.  
Table 29 indicates the number of stages available. The  
staging algorithm looks at the number of stages available  
based the number of cool stages configured in the  
SERVICE configuration table. The algorithm will skip the  
economizer if it is not available and turn on a compressor.  
The PremierLink controller has an optional Supply Fan  
Status input to provide proof of airflow. If this is enabled,  
the point will look for a contact closure whenever the  
Supply Fan Relay is on. If the input is not enabled, then it  
will always be the same state as the Supply Fan Relay.  
The cooling, economizer and heating routines will use this  
input point for fan status.  
Table 29 – Available Cooling Stages  
NUMBER OF  
STAGES  
1
0
2
3
(ECONOMIZER*)  
Cooling — The compressors are controlled by the Cooling  
Control Loop that is used to calculate the desired SAT  
needed to satisfy the space. It will compare the SPT to the  
Occupied Cool Setpoint (OCSP) + the T56 slider offset  
(STO) when occupied and the Unoccupied Cool Setpoint  
(UCSP + Unoccupied Cooling Deadband) if unoccupied  
to calculate a Cooling Submaster Reference (CCSR) that  
is then used by the staging algorithm (Cooling submaster  
loop) to calculate the required number of cooling stages.  
The economizer, if available, will be used as the first  
stage of cooling in addition to the compressors. This loop  
runs every minute. The following conditions must be met  
in order for this algorithm to run:  
Compressor 1  
Compressor 2  
Off  
Off  
Off  
Off  
On  
Off  
On  
On  
*
If conditions are suitable for economizer operation.  
Any time the compressors are running, the PremierLink  
controller will lockout the compressors if the SAT  
becomes too low. These user configurable settings are  
found in the SERVICE configuration table:  
Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F)  
(default is 55_F)  
Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F)  
(default is 50_F)  
After a compressor is locked out, it may be started again  
after a normal time-guard period and the supply air  
temperature has increased at least 8_F above the lockout  
setpoint.  
S indoor fan has been ON for at least 30 seconds  
S heat mode is not active and the time guard between  
modes equals zero.  
S mode is occupied or the Temperature Compensated Start  
Dehumidification — The PremierLink controller will  
provide occupied and unoccupied dehumidification  
control when AUXOUT = 5 in the CONFIG table and is  
installed on HVAC units that are equipped with additional  
controls and accessories to accomplish this function. This  
function also requires a space relative humidity sensor be  
installed on the OAQ/IRH input.  
or Cool mode is active  
S SPT reading is available and > (OCSP + STO)  
S If mode is unoccupied and the SPT > (UCSP +  
Unoccupied Cooling Deadband). The indoor fan will be  
turned on by the staging algorithm.  
S OAT > DXLOCK or OAT DX Lockout is disabled  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
When in the occupied mode and the indoor relative  
humidity is greater then the Occupied High Humidity  
setpoint, then the H3_EX_RV output point will be  
energized. When in the unoccupied mode and indoor  
relative humidity is greater then the Unoccupied High  
Humidity setpoint, then the H3_EX_RV output point and  
supply fan output will be energized. There is a fixed 5%  
hysteresis that the indoor relative humidity must drop  
below the active setpoint to end the dehumidification  
mode and deenergize the H3_EX_RV output. If the  
PremierLink controller is in the unoccupied mode, then  
the fan relay will deenergize if there is no other mode  
requiring to the fan to be on. This function will not  
energize mechanical cooling as a result of the indoor  
relative humidity exceeding either setpoint.  
The actual damper position (ECONPOS) is the result of  
the following calculation. Values represented in the right  
side of the equation can be found in the SERVICE  
configuration table descriptions in this manual. Note that  
that the OAT is taken into consideration to avoid large  
changes in damper position when the OAT is cold:  
ECONPOS = SubGain x (ECONSR-SAT) + CTRVAL  
where SubGain = (OAT - TEMPBAND) / (ESG + 1)  
If the OAT < DXLOCK (DX Cool Lockout setpoint) then  
the damper will be modulated to maintain the SAT at the  
ECONSR value.  
If the OAT is between DXLOCK and 68_F (DXLOCK <  
OAT < 68_F) and additional cooling is required, the  
economizer will close the to minimum position for three  
minutes, the economizer integrator will then be reset to 0  
and begin modulating to maintain the SASP after the stage  
has been energized for about 90 seconds. This will allow  
the economizer to calculate a new ECONSR that takes  
into account the cooling effect that has just been turned on  
and not return to the value require before the cooling was  
added. This will prevent the economizer from causing  
premature off cycles of compressors while maintaining the  
low SAT temperature setpoint for the number of stages  
active. In addition to preventing compressor short cycling,  
by using return air across the evaporator coil just after the  
compressor has started allows for increased refrigerant  
flow rates providing for better oil return of any oil washed  
out during compressor start-up.  
A high humidity alarm will be generated if the indoor  
relative humidity exceeds the high humidity setpoint by  
the amount configured in the Control Humidity Hysteresis  
in the ALARMS table for 20 minutes. The alarm will  
return to normal when the indoor relative humidity drops  
3% below the active humidity setpoint.  
Economizer — The economizer dampers are used to  
provide free cooling and indoor air quality if optional CO2  
sensor is installed and when the outside conditions are  
suitable. Temperature control is accomplished by  
controlling the SAT to a certain level determined by the  
Economizer PID Loop by calculating a submaster  
reference (ECONSR) value. This algorithm will calculate  
the submaster reference temperature (ECONSR) based on  
OAT and enthalpy conditions and cooling requirements.  
The ECONSR value is then passed to the Economizer  
Submaster Loop, which will modulate dampers to  
maintain SAT at ECONSR level.  
If the OAT > 68_F and OAT < SPT and the number of DX  
stages requested is > 0 by the staging algorithm, then  
ECONSR is set to its minimum value 48_F and the  
damper will go to 100% open.  
The following conditions are required to determine if  
economizer cooling is possible:  
If the Auxiliary Relay is configured for exhaust fan  
(AUXOUT = 1) in the CONFIG configuration table and  
Continuous Power Exhaust (MODPE) is Enable in the  
SERVICE configuration table, then the AUXO output  
(HS3) will be energized whenever the PremierLink  
controller is in the occupied mode. If the MODPE is  
disabled then AUXO output will be energized based on  
the Power Exhaust Setpoint (PES) in the SETPOINT  
table.  
S Indoor fan has been on for at least 30 seconds  
S Enthalpy is low  
S SAT reading is available  
S OAT reading is available  
S SPT reading is available  
S OAT SPT  
Heating — The heat stages are controlled by the Heating  
Control Loop, which is used to calculate the desired SAT  
needed to satisfy the space. It will compare the SPT to the  
Occupied Heat Setpoint (OHSP) + the T56 slider offset  
(STO) when occupied and the Unoccupied Heat Setpoint  
(UHSP - Unoccupied Heating Deadband) if unoccupied to  
calculate a Staged Heat Submaster Reference (SHSR).  
The heat staging algorithm compares the SHSR to the  
actual SAT to calculate the required number of heating  
stages to satisfy the load. This loop runs every 40 seconds.  
The following conditions must be met in order for this  
algorithm to run:  
S OAT < OATMAX (OATMAX default is 75_F)  
S Economizer position is NOT forced  
If any of the above conditions are not met, the ECONSR  
will be set to its MAX limit of 120_F and the damper will  
go to its configured minimum position. The minimum  
damper position can be overridden by the IAQ routine  
described later in this section.  
The calculation for ECONSR is as follows:  
ECONSR = PID function on (setpoint - SPT), where:  
setpoint = ((OCSP+STO) + (OHSP+STO))/2 when  
NTLO (Unoccupied Free Cool OAT Lockout) < OAT <  
68_F  
setpoint = (OCSP+STO) - 1 when OAT NTLO  
setpoint = (OHSP+STO) + 1 when OAT 68_F  
S Indoor fan has been ON for at least 30 seconds.  
S Cool mode is not active and the time guard between  
modes equals zero.  
S Mode is occupied or the Temperature Compensated Start  
or Heat mode is active.  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S SPT reading is available and < (OHSP + STO).  
S an IAQ sensor is installed  
S If it is unoccupied and the SPT < (UHSP - Unoccupied  
Heating Deadband). The indoor fan will be turn on by the  
staging algorithm.  
S the IAQ Minimum Damper Position > minimum damper  
position  
S and the SAT < SPT -10_F.  
When all of the above conditions are met, the SHSR is  
calculated and up to 3 stages of heat will turned on and off  
to satisfy to maintain the SAT = SHSR. If any of the  
above conditions are not met, the SHSR is set to its  
minimum value of 35_F.  
There is also a SAT tempering routine that will act as SAT  
low limit safety to prevent the SAT from becoming too  
cold should the economizer fail to close. One stage of  
heating will be energized if it is not in the Cooling or Free  
Cooling mode and the OAT is below 55_F and the SAT is  
below 40_F. It will deenergize when the SAT > (SPT +  
10_F).  
The Staged Heat Submaster Reference (SHSR) is  
calculated as follows:  
Indoor Air Quality — If the optional indoor air quality  
(IAQI) sensor is installed, the PremierLink controller will  
maintain indoor air quality within the space at the user  
configured differential setpoint (IAQD) in the CONFIG  
configuration table. The setpoint is the difference between  
the IAQI and an optional outdoor air quality sensor  
(OAQ). If the OAQ is not present then a fixed value of  
400 ppm is used. The actual space IAQ setpoint (IAQS) is  
calculated as follows:  
SHSR = Heating PID function on (error) where error =  
(OHSP + STO) - Space Temperature  
The Maximum SHSR is determined by the SATHI  
configuration. If the supply-air temperature exceeds the  
SATHI configuration value, then the heat stages will turn  
off. Heat staging will resume after a delay to allow the  
supply-air temperature to drop below the SATHI value.  
The maximum number of stages available is dependent on  
the type of heat and the number of stages programmed in  
the CONFIG and SERVICE configuration tables. Staging  
will occur as follows for gas electric units, Carrier heat  
pumps with a defrost board, or cooling units with electric  
heat:  
IAQS = IAQD + OAQ (OAQ = 400 ppm if not present)  
As air quality within the space changes, the minimum  
position of the economizer damper will be changed also  
thus allowing more or less outdoor air into the space  
depending on the relationship of the IAQI to the IAQS.  
The IAQ algorithm runs every 30 seconds and calculates  
IAQ minimum position value using a PID loop on the  
IAQI deviation from the IAQS. The IAQ minimum  
position is then compared against the user configured  
minimum position (MDP) and the greatest value becomes  
the final minimum damper position (IQMP). If the  
calculated IAQ minimum position is greater than the IAQ  
maximum damper position (IAQMAXP) decision in the  
SERVICE configuration table, then it will be clamped to  
IAQMAXP value.  
For Heating PID STAGES = 2  
HEAT STAGES = 1 (50% capacity) - energize HS1.  
HEAT STAGES = 2 (100% capacity) - energize HS2.  
For Heating PID STAGES = 3 and AUXOUT = HS3  
HEAT STAGES = 1 (33% capacity if) - energize HS1  
HEAT STAGES = 2 (66% capacity) - energize HS2  
HEAT STAGES = 3 (100% capacity) - energize HS3  
Staging will occur as follows For heat pump units with  
AUXOUT configured as reversing valve:  
If IAQ is configured for low priority, the positioning of  
the economizer damper can be overridden by comfort  
requirements. If the SPT > OCSP + 2.5 or the SPT <  
OHSP - 2.5 then IAQ minimum position becomes 0 and  
the IQMP = MDP. The IAQ mode will resume when the  
SPT OCSP + 1.0 and SPT OHSP - 1.0.  
For Heating PID STAGES = 2 and AUXOUT = Reversing  
Valve Heat (the H3_EX_RV output will stay energized  
until there is a cool demand) HEAT STAGES = 1 (50%  
capacity) shall energize CMP1, CMP2, RVS.  
HEAT STAGES = 2 (100% capacity) shall energize HS1  
and HS2.  
If IAQ is configured for high priority and the OAT < 55_F  
and the SAT < (SPT - 10_F), the algorithm will enable the  
heat stages to maintain the SAT between the SPT and the  
SPT + 10_F.  
Heating PID STAGES = 3 and AUXOUT = Reversing  
Valve Heat (the H3_EX_RV output will stay energized  
until there is a cool demand)  
HEAT STAGES = 1 (33% capacity if) shall energize  
CMP1, CMP2, RVS  
IAQ Pre-Occupancy Purge — This function is designed to  
purge the space of airborne contaminants that may have  
accumulated 2 hours prior to the beginning of the next  
occupied period. The maximum damper position that will  
be used is temperature compensated for cold whether  
conditions and can be pre-empted by Temperature  
Compensated Start function. For pre-occupancy to occur,  
the following conditions must be met:  
HEAT STAGES = 2 (66% capacity) shall energize HS1  
HEAT STAGES = 3 (100% capacity) shall energize HS2  
If AUXOUT is configured for Reversing Valve Cool, then  
the H3_EX_RV contact will be deenergized when there is  
a demand for heating. The heat stages will be cycled to  
temper the SAT so that it will be between the SPT and the  
SPT + 10_F (SPT < SAT < (SPT + 10_F)) if:  
S IAQ Pre -Occupancy Purge option is enabled in the  
CONFIG configuration table  
S Unit is in the unoccupied state  
S Current Time is valid  
S the number of heat stages calculated is zero  
S the OAT < 55_F  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S Next Occupied Time is valid  
SPT > (NTSP + 2_F) and SPT > (OAT + 8_F)  
The Unoccupied Free Cool mode will be stopped when:  
SPT < NTSP or SPT < (OAT + 3_F)  
S Time is within 2 hours of next Occupied period  
S Time is within Purge Duration (user-defined 5 to 60  
minutes in the CONFIG configuration table)  
Temperature Compensated Start — This function will run  
when the controller is in unoccupied state and will  
calculate early start bias time (SBT) based on space  
temperature deviation from occupied setpoints in minutes  
per degree. The following conditions will be met for the  
function to run:  
S OAT Reading is available  
If all of the above conditions are met, the economizer  
damper IQMP is temporarily overridden by the  
pre-occupancy damper position (PURGEMP). The  
PURGEMP will be set to one of the following conditions  
based on atmospheric conditions and the space  
temperature:  
S Unit is in unoccupied state  
S Next occupied time is valid  
S Current time of day is valid  
S If the OAT NTLO (Unoccupied OAT Lockout  
Temperature) and OAT < 65_F and OAT is less than or  
equal to OCSP and Enthalpy = Low then PURGEMP =  
100%.  
S Valid space temperature reading is available (from sensor  
or linkage thermostat)  
S Cool Start Bias (KCOOL) and Heat Bias Start (KHEAT)  
> 0 in the CONFIG configuration table  
S If the OAT < NTLO then PURGEMP = LTMP (Low  
Temperature Minimum Position - defaults to 10%)  
The SBT is calculated by one of the following formulas  
depending on temperature demand:  
S If the OAT > 65_F or (OAT NTLO and OAT > OCSP)  
or Enthalpy = High then PURGEMP = HTMP (High  
Temperature Minimum Position defaults to 35%).  
If SPT > OCSP then SBT = (SPT - OCSP) * KCOOL  
If SPT < OHSP then SPT = (OHSP - SPT) * KHEAT.  
The LTMP and HTMP are user adjustable values from 0  
to 100% in the SETPOINT table. Whenever PURGEMP  
The calculated start bias time can range from 0 to 255  
minutes. When SBT is greater than 0 the function will  
subtract the SBT from the next occupied time to calculate  
a new start time. When a new start time is reached, the  
Temperature Compensated Start mode is started. This  
mode energizes the fan and the unit will operate as though  
it is in occupied state. Once set, Temperature  
Compensated Start mode will stay on until the unit returns  
to occupied state. If either Unoccupied Free Cool or IAQ  
Pre-Occupancy mode is active when Temperature  
Compensated Start begins, their mode will end.  
results in  
a
number greater than 0%, the IAQ  
pre-occupancy purge mode will be enabled turning on the  
Indoor Fan Relay and setting the economizer IQMP to the  
PURGEMP value. When IAQ pre-occupancy mode is not  
active PURGEMP = 0%.  
Unoccupied Free Cooling — Unoccupied free cool  
function will start the indoor fan during unoccupied times  
in order to cool the space with outside air. This function is  
performed to delay the need for mechanical cooling when  
the system enters the occupied period. Depending on how  
Unoccupied Free Cooling is configured, unoccupied mode  
can occur at any time in the unoccupied time period or 2  
to 6 hours prior to the next occupied time. Once the space  
has been sufficiently cooled during this cycle, the fan will  
be stopped. In order to perform unoccupied free cooling  
all of the following conditions must be met:  
Door Switch — The Door Switch function is designed to  
disable mechanical heating and cooling outputs when the  
REMOCC contact input is closed (in the ON state) after a  
programmed time delay. The fan will continue to operate  
based on the current mode and the ASHRAE 90.1 Supply  
Fan setting. The delay is programmable from 2 to 20  
minutes by setting the Remote Cont/Door Switch decision  
in the SERVICE table to a value equal to the number of  
minutes desired. When the contact is open (in the OFF  
state), the PremierLink controller will resume normal  
temperature control.  
S NTEN option is enabled in the CONFIG configuration  
table  
S Unit is in unoccupied state  
S Current time of day is valid  
S Temperature Compensated Start mode is not active  
S COOL mode is not active  
S HEAT mode is not active  
S SPT reading is available  
This application is designed for use in schools or other  
public places where a door switch can be installed to  
monitor the opening of a door for an extended period of  
time. The controller will disable mechanical cooling and  
heating when the door is open for a programmed amount  
of time.  
S OAT reading is available  
S Enthalpy is low  
This function can also be used to monitor a high  
condensate level switch when installed on a water source  
heat pump to disable mechanic cooling in case of a  
plugged evaporator condensate pan drain.  
Linkage — The Linkage function in the PremierLink  
controller is available for applications using a Linkage  
thermostat or the 3V control system. If using the Linkage  
thermostat, both the PremierLink controller and the stat  
must be on the same CCN bus. When used as the air  
S OAT > NTLO (with 1_F hysteresis) and < Max Free Cool  
setpoint  
If any of the above conditions are not met, Unoccupied  
Free Cool mode will be stopped, otherwise, the mode will  
be controlled as follows:  
The NTFC setpoint (NTSP) is determined as NTSP =  
(OCSP + OHSP) / 2  
The Unoccupied Free Cool mode will be started when:  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
source for a 3V control system, the PremierLink controller  
is not required to be on the same CCN bus but it is  
recommended. Linkage will be active when it is initiated  
from the Linkage thermostat or the 3V Linkage  
Coordinator through CCN communications and requires  
no configuration. Only one device can be linked to the  
PremierLink controller.  
For more information on how the PremierLink controller  
is used in conjunction with the Carrier 3V control system,  
contact your CCN controls representative.  
IMPORTANT: The PremierLink controller should not be  
used as a linked air source in a ComfortIDt VAV system.  
The ComfortID VAV system will NOT function correctly  
when applied with a PremierLink controller as the air  
source, resulting in poor comfort control and possible  
equipment malfunction.  
NOTE: The PremierLink controller can be used as an air  
source in a 3V Pressure Independent (PI) System (a 3V  
Linkage Coordinator with ComfortID PI Zone  
Controllers), but it should not be used as an air source  
with ComfortID controllers unless a 3V zone controller is  
used as the Linkage Coordinator. Contact your Carrier  
CCN controls representative for assistance.  
Once Linkage is active, the PremierLink controller’s own  
SPT, temperature setpoints, and occupancy are ignored  
and the controller will use the information provided by the  
remote linkage device. The following information will be  
received from the remote linked device and can be viewed  
in the maintenance display table:  
S Supervisory Element  
S Supervisory Bus  
S Supervisory Block  
Demand Limit — If the demand limit option is enabled,  
the control will receive and accept Redline Alert and  
Loadshed commands from the CCN loadshed controller.  
When a redline alert is received, the control will set the  
maximum stage of capacity equal to the stage of capacity  
that the unit is operating at when the redline alert was  
initiated.  
S Average Occupied Heat Setpoint  
S Average Occupied Cool Setpoint  
S Average Unoccupied Heat Setpoint  
S Average Unoccupied Cool Setpoint  
S Average Zone Temp  
S Average Occupied Zone Temp  
S Occupancy Status  
When loadshed command is received the control will  
reduce capacity as shown in Table 31.  
In return, the PremierLink controller will provide its SAT  
and operating mode to the linked device.  
Table 31 – Loadshed Command — Gas and Electric  
Heat Units  
It will convert its operating modes to Linkage modes. See  
Table 30.  
CURRENT CAPACITY  
CMP1  
NEW CAPACITY  
DX Cooling OFF  
CMP1  
Table 30 – Linkage Modes  
CMP1+CMP2  
HS1  
ROOFTOP MODE  
Demand Limit  
Heat  
VALUE  
N/A  
3
LINKAGE MODE  
N/A  
Heat OFF  
HS1+HS2 (+HS3)  
HS1  
Heating  
Cooling  
N/A  
The controller will have a maximum demand limit timer  
of 1 hour that prevents the unit from staying in load shed  
or redline alert longer than 1 hour in the event the  
controller loses communication with the network load  
shed module. Should the maximum demand limit timer  
expire prior to receiving the loadshed device command  
from CCN, the control will stop demand limit mode and  
return to normal operation.  
Cool or Free Cooling  
IAQ Control  
4
N/A  
Temp. Compensated  
Start Heat  
2
Warm ---up  
Temp. Compensated  
Start Cool  
IAQ Purge  
Occupied  
(Indoor Fan ON)  
4
6
4
Cooling  
Pressurization  
Cooling  
RTU--MP Sequence of Operation  
Unoccupied Free  
Cool  
Unoccupied Free  
Cooling  
The RTU-MP will control the compressor, economizer  
and heating outputs based on its own space temperature  
input and setpoints. An optional CO2 IAQ sensor mounted  
in the space can influence the economizer minimum  
position. The RTU-MP has its own hardware clock that is  
set automatically when the software is installed on the  
board. The RTU-MP’s default is to control to occupied  
setpoints all the time, until a type of occupancy control is  
set. Occupancy types are described in the scheduling  
section. The following sections describe the operation for  
the functions of the RTU-MP. All point objects that are  
referred to in this sequence will be in reference to the  
objects as viewed in BACview6 Handheld.  
5
Fire Shutdown  
Factory/Field Test  
Off  
7
1
1
Evac  
Off  
Off  
The PremierLink controller will generate a Linkage  
Communication Failure alarm if a failure occurs for 5  
consecutive minutes once a Linkage has previously been  
established. It will then revert back to its own SPT,  
setpoints and occupancy schedule for control. For this  
reason, Carrier strongly recommends that an SPT be  
installed in the space on open plenum systems or in the  
return air duct of ducted return air systems to provide  
Scheduling  
continued  
backup  
operation.  
When  
Linkage  
communication is restored, the controller will generate a  
return to normal.  
Scheduling is used to start heating or cooling (become  
occupied) based upon a day of week and a time period and  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
control to the occupied heating or cooling setpoints.  
Scheduling functions are located under occupancy  
determination and the schedule menu accessed by the  
Menu softkey (see Appendix - for menu structure). Your  
local time and date should be set for these functions to  
operate properly. Five scheduling functions are available  
by changing the Occupancy Source to one of the  
following selections:  
BAS On/Off  
The Building Automation System is scheduling the unit  
via an On/Off command to the BAS ON/OFF software  
point. The Building Automation System can be speaking  
BACnet, Modbus, or N2 and is writing to the BAS On/Off  
point in the open protocol point map.  
NOTE:  
If the BAS supports NATIVE BACnet  
scheduling, then set the Occupancy Source to BACnet  
schedule. If the BAS is BACnet but does NOT support  
NATIVE BACnet scheduling, then set the Occupancy  
Source to BAS On/Off.  
Always Occupied (Default Occupancy)  
The unit will run continuously. RTU-MP ships from the  
factory with this setting.  
Local Schedule  
DI On/Off  
The unit will operate according to the schedule configured  
and stored in the unit. The local schedule is made up of  
three hierarchy levels that consist of two Override  
schedules, twelve Holiday and four Daily schedules, and  
are only accessible by the BACview screen (handheld or  
virtual).  
A hard-wired input on the RTU-MP will command the  
unit to start/stop. Inputs 3, 5, 8, and 9 on plug J5 can be  
hard-wired to command the unit to start/stop.  
NOTE: Scheduling can either be controlled via the unit  
or the BAS, but NOT both.  
Indoor Fan  
The Daily schedule is the lowest schedule in the hierarchy  
and is overridden by both the Holiday and Override  
schedule. It consists of a start time, a stop time (both in 24  
hour mode) and the seven days of the week, starting with  
Monday and ending in Sunday. To select a daily schedule  
scroll to the Schedules menu off of the Menu selection.  
Enter the User password and change the Occupancy  
Source to Local Schedule. Scroll down and over to the  
Daily menu and press enter. Choose one of the four Daily  
schedules by pressing the Next softkey and change the  
Use? point from NO to YES by selecting the point and  
pressing the INCR or DECR softkey. Press the OK softkey  
and scroll to the start and stop times. Edit these times  
following the same steps as the Use? point. Finally scroll  
down to the Days: section and highlight the days required  
for the Daily schedule by INCR or DECR softkeys and  
press OK softkey.  
The Holiday schedule is created to override the Daily  
schedule and identify a specific day and month of the year  
to start and stop the unit and change control to the  
unoccupied heating and cooling setpoints. Follow the  
same steps to turn on one of the twelve Holiday schedules  
and start and stop times. Next, select one out of the twelve  
months and one out of the thirty-one days of that month.  
The RTU-MP will now ignore the Daily schedule for the  
specific day and time you selected and follow the Holiday  
Schedule for this period.  
The indoor fan will be turned on whenever any one of the  
following conditions is true:  
S It is in the occupied mode. This will be determined by its  
own internal occupancy schedule.  
S Whenever there is a demand for cooling or heating in the  
unoccupied mode.  
S Whenever the remote occupancy switch is closed during  
DI On/Off schedule type or if occupancy is forced  
occupied by the BAS during BAS On/Off schedule type.  
When transitioning from unoccupied to occupied, there  
will be a configured time delay of 5 to 600 seconds before  
starting the fan. The fan will continue to run as long as  
compressors, heating stages, or the dehumidification  
relays are on when transitioning from occupied to  
unoccupied with the exception of Shutdown mode. If Fire  
Shutdown, safety chain, SAT alarm or SPT alarm are  
active; the fan will be shutdown immediately regardless of  
the occupancy state or demand.  
The RTU-MP has an optional Supply Fan Status input to  
provide proof of airflow. If this is enabled, the point will  
look for a contact closure whenever the Supply Fan Relay  
is on. If it is not enabled then it will always be the same  
state as the Supply Fan Relay. The cooling, economizer,  
heating, dehumidification, CO2 and power exhaust  
routines will use this input point for fan status.  
Cooling  
The Override schedules primary purpose is to provide a  
temporary change in the occupied heating and cooling  
setpoints and force the unit to control to the unoccupied  
heating and cooling setpoints. This would occur on a set  
day in a particular month and last during the start and stop  
time configured. The Override schedule is enabled by  
following the same steps to create the Holiday schedule.  
The compressor outputs are controlled by the Cooling  
Control PID Loop and Cooling Stages Capacity algorithm.  
They will be used to calculate the desired number of  
stages needed to satisfy the space by comparing the Space  
Temperature (SPT) to the Occupied Cool Setpoint plus the  
T56 slider offset when occupied and the Unoccupied Cool  
Setpoint (UCSP) plus the T56 slider offset, if unoccupied.  
The economizer, if available, will be used for cooling in  
addition to the compressors. The following conditions  
must be true in order for this algorithm to run:  
NOTE: Push button override is only available when  
running a local or BACnet Schedule.  
BACnet Schedule  
For use with a Building Automation System that supports  
native BACnet scheduling is scheduling the unit. With the  
Occupancy Source set to BACnet schedule the BAS will  
control the unit through network communication and it’s  
own scheduling function.  
S Indoor Fan has been ON for at least 30 seconds.  
S Heat mode is not active and the time guard between  
modes equals zero.  
S If occupied and the SPT >(occupied cool setpoint plus  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
the T56 slider offset).  
configured for continuous occupied operation, it will be  
energized whenever the controller is in the occupied mode  
and disabled when in the unoccupied mode. If configured  
for damper position control, it will be energized whenever  
the economizer exceeds the power exhaust setpoint and  
disabled when the economizer drops below the setpoint by  
a fixed hysteresis of 10%.  
S Space Temperature reading is available.  
S If it is unoccupied and the SPT > (unoccupied cool  
setpoint plus the T56 slider offset). The indoor fan will be  
turned on by the staging algorithm.  
S If economizer is available and active and economizer  
open > 85% and SAT > (SAT low limit + 5_F) and SPT >  
effective setpoint + 0.5_F.  
Heating  
OR  
The heating outputs are controlled by the Heating Control  
PID Loop and Heating Stages Capacity algorithm. They  
will be used to calculate the desired number of stages  
needed to satisfy the space by comparing the SPT to the  
Occupied Heat Setpoint plus the T56 slider offset when  
occupied and the Unoccupied Heat Setpoint plus the T56  
slider offset if unoccupied. The following conditions must  
be true in order for this algorithm to run:  
Economizer is available, but not active  
OR  
Economizer is not available  
S OAT > DX Lockout temperature.  
If all of the above conditions are met, the compressors  
will be energized as required, otherwise they will be  
de-energized.  
There is a fixed 3-minute minimum on time and a  
5-minute off time for each compressor output and a  
3-minute minimum time delay between staging up or  
down.  
Any time the compressors are running the RTU-MP will  
stage down the compressors if the SAT becomes less than  
the cooling low supply air setpoint.  
After a compressor is staged off, it may be started again  
after a normal time-guard period and the supply air  
temperature has increased above the low supply air  
setpoint.  
S Indoor Fan has been ON for at least 30 seconds.  
S Cool mode is not active and the time guard between  
modes equals zero.  
S If occupied and SPT <(occupied heat setpoint plus T56  
slider offset)  
S SPT reading is available  
S If it is unoccupied and the SPT < (unoccupied heat  
setpoint plus T56 slider offset). The indoor fan will be  
turned on by the staging algorithm.  
S OAT < High OAT lockout temperature.  
If all of the above conditions are met, the heating outputs  
will be energized as required, otherwise they will be  
de-energized. If the SAT begins to exceed the high supply  
air setpoint, a ramping function will cause the Heat Stages  
Capacity algorithm to decrease the number of stages until  
the SAT has dropped below the setpoint.  
There is a fixed one minute minimum on time and a one  
minute off time for each heat output. Heat staging has a 3  
minute stage up and 30 second stage down delay.  
Economizer  
The Economizer dampers are used to provide free cooling  
and Indoor Air Quality, if optional CO2 sensor is installed,  
when the outside conditions are suitable.  
The following conditions must be true for economizer  
operation:  
S Indoor Fan has been on for at least 30 seconds.  
S Enthalpy is Low if the Enthalpy input is enabled.  
S SAT reading is available.  
Indoor Air Quality  
If the optional indoor air quality sensor is installed, the  
RTU-MP will maintain indoor air quality within the space  
at the user configured differential setpoint. The setpoint is  
the difference between the indoor air quality and an  
optional outdoor air quality sensor. If the outdoor air  
quality is not present then a fixed value of 400ppm is  
used. The following conditions must be true in order for  
this algorithm to run:  
S OAT reading is available.  
S SPT reading is available.  
S OAT <= High OAT economizer lockout configuration  
(default = 75).  
S OAT <= SPT  
If any of the mentioned conditions are not true, the  
economizer will be set to its configured minimum  
position. The minimum damper position can be  
overridden by the IAQ routine described later in this  
section.  
If the above conditions are true, the Economizer Control  
Master Loop will calculate a damper position value based  
on the following calculation:  
Damper Position = minimum position + PID (SPT - econ  
setpoint). Econ setpoint is half way between the effective  
cool and heat setpoints. If the SAT drops below the  
cooling low supply air setpoint (+ 5_F), the economizer  
will ramp down to minimum position.  
S The mode is occupied.  
S Indoor Fan has been ON for at least 30 seconds.  
S Indoor Air Quality sensor has a valid reading  
As air quality within the space changes, the minimum  
position of the economizer damper will be changed thus  
allowing more or less outdoor air into the space depending  
on the relationship of the indoor air quality to the  
differential setpoint. If all the above conditions are true,  
the IAQ algorithm will run and calculates an IAQ  
minimum position value using a PID loop. The IAQ  
minimum damper position is then compared against the  
user configured economizer minimum position and the  
greatest value becomes the final minimum damper  
position of the economizer output.  
Power Exhaust  
If RTU-MP is also controlling an exhaust fan, it can be  
enabled based on damper position or by occupancy. If  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
If the calculated IAQ minimum position is greater than  
the IAQ maximum damper position configuration then it  
will be clamped to the configured value.  
heating and cooling setpoints by the configured demand  
limit setpoint value and remain in effect until the BACnet  
demand limit variable receives a 0 value.  
Demand Limit  
FASTENER TORQUE VALUES  
If the RTU-MP receives a level 1 (one degree offset), 2  
(two degree offset), or a 3 (4 degree offset) to the BACnet  
demand limit variable, the controller will expand the  
See Table 32 for torque values.  
Table 32 – Torque Values  
Supply fan motor mounting  
Supply fan motor adjustment plate  
Motor pulley setscrew  
120 + / --- 12 in --- lb s  
120 + / --- 12 in --- lb s  
72+/--- 5 in---lbs  
72+/--- 5 in---lbs  
72+/--- 5 in---lbs  
65 --- 70 in --- lb s  
65 --- 75 in --- lb s  
20 + / --- 2 in --- lb s  
84 + / --- 12 in --- lb s  
Fan pulley setscrew  
Blower wheel hub setscrew  
Bearing locking collar setscrew  
Compressor mounting bolts  
Condenser fan motor mounting bolts  
Condenser fan hub setscrew  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX I. MODEL NUMBER SIGNIFICANCE  
Model Number Nomenclature  
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18  
4
8
T
C D A  
0
4
A
1
A
5
--  
0
A
0
A
0
____  
____  
____  
Unit Heat Type  
48 = Gas heat pkg rooftop  
Brand / Packaging  
0 = Standard  
1 = LTL  
Tier / Model  
TC = Entry tier (with Puron refrigerant)  
Electrical Options  
A = None  
Heat Size  
C = N o n --- f u se d d isc  
D = Thru the base  
F = Non---fused & thru the base  
D = Low heat  
E = Medium heat  
F = High heat  
L = Low NO , low heat  
Service Options  
x
M = Low NO , medium heat  
0 = None  
x
N = Low NO , high heat  
1 = Unpowered convenience outlet  
2 = Powered convenience outlet  
x
S = Stainless steel, low heat  
R = Stainless steel, medium heat  
T = Stainless steel, high heat  
Intake / Exhaust Options  
A = None  
Refrig. System Options  
A = Standard refrigeration system  
B = Temp econo w/ baro relief  
F = Enthalpy econo w/ baro relief  
Base Unit Controls  
0 = Electromechanical  
Cooling Tons  
04 = 3 Ton  
05 = 4 Ton  
06 = 5 Ton  
07 = 6 Ton  
08 = 7.5 Ton  
09 = 8.5 Ton  
12 = 10 Ton  
1 = PremierLink DDC controller  
2 = RTU---MP multi protocol controller  
Design Rev  
Factory assigned  
Sensor Options  
A = None  
Voltage  
B = RA smoke detector  
C = SA smoke detector  
1 = 575/3/60  
3 = 208---230/1/60  
5 = 208---230/3/60  
6 = 460/3/60  
D = RA & SA smoke detector  
1
E = CO sensor  
2
1
F = RA smoke detector & CO  
G = SA smoke detector & CO  
H = RA & SA smoke detector & CO  
2
1
Coil Options (Outdoor Coil --- Indoor Coil)  
A = Al/Cu --- Al/Cu  
2
1
2
B = P r e co a t A l/ C u --- A l/ C u  
C = E co a t A l/ C u --- A l/ C u  
Indoor Fan Options  
D = E coat Al/Cu --- E coat Al/Cu  
E = Cu/Cu --- Al/Cu  
F = Cu/Cu --- Cu/Cu  
M = A l/ C u --- A l/ C u --- L o u v e r e d H a il G u a r d s  
N = P r e co a t A l/ C u --- A l/ C u --- L o u v e r e d H a il G u a r d s  
P = E co a t A l/ C u --- A l/ C u --- L o u v e r e d H a il G u a r d s  
Q = E co a t A l/ C u --- E co a t A l/ C u --- L o u v e r e d H a il G u a r d s  
R = C u / C u --- A l/ C u --- L o u v e r e d H a il G u a r d s  
S = C u / C u --- C u / C u --- L o u v e r e d H a il G u a r d s  
1 = Standard static option  
2 = Medium static option  
3 = High static option  
1
Future availability  
Serial Number Format  
POSITION NUMBER  
1
2
3
4
5
6
7
8
9
10  
TYPICAL  
1
2
0
8
G
1
2
3
4
6
POSITION  
1---2  
DESIGNATES  
Week of manufacture (fiscal calendar  
Year of manufacture (“08” = 2008)  
3---4  
5
Manufacturing location (G = ETP, Texas, USA)  
Sequential number  
6---10  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX II. PHYSICAL DATA  
3 -- 6 TONS  
Physical Data (Cooling)  
48TC*A04  
48TC*A05  
48TC*A06  
48TC*A07  
Refrigeration System  
# Circuits / # Comp. / Type  
Puron (R---410a) charge A/B (lbs)  
Oil A/B (oz)  
1 / 1 / Scroll  
5.6  
1 / 1 / Scroll  
8.5  
1 / 1 / Scroll  
10.7  
1 / 1 / Scroll  
14.1  
25  
42  
42  
56  
Metering Device  
High---press. Trip / Reset (psig)  
Low---press. Trip / Reset (psig)  
Acutrol  
630 / 505  
54 / 117  
Acutrol  
630 / 505  
54 / 117  
Acutrol  
630 / 505  
54 / 117  
Acutrol  
630 / 505  
54 / 117  
Evap. Coil  
Material  
Coil type  
Cu / Al  
3/8” RTPF  
2 / 15  
Cu / Al  
3/8” RTPF  
2 / 15  
Cu / Al  
3/8” RTPF  
4 / 15  
Cu / Al  
3/8” RTPF  
4 / 15  
Rows / FPI  
2
Total Face Area (ft )  
5.5  
5.5  
5.5  
7.3  
Condensate Drain Conn. Size  
3/4”  
3/4”  
3/4”  
3/4”  
Evap. Fan and Motor  
1 / Belt  
1.2  
560---854  
48  
1 / Centrifugal  
10 x 10  
1 / Belt  
1.2  
770---1175  
48  
1 / Centrifugal  
10 x 10  
---  
---  
---  
---  
---  
---  
Motor Qty / Drive Type  
Max BHP  
1 / Belt  
1.2  
560---854  
48  
1 / Centrifugal  
10 x 10  
RPM Range  
Motor Frame Size  
Fan Qty / Type  
Fan Diameter (in)  
Motor Qty / Drive Type  
Max BHP  
1 / Belt  
1.2  
560---854  
48  
1 / Centrifugal  
10 x 10  
1 / Belt  
1.2  
560---854  
48  
1 / Centrifugal  
10 x 10  
1 / Belt  
1.2  
770---1175  
48  
1 / Centrifugal  
10 x 10  
1 / Belt  
2.4  
1073---1457  
56  
1 / Centrifugal  
10 x 10  
RPM Range  
Motor Frame Size  
Fan Qty / Type  
Fan Diameter (in)  
Motor Qty / Drive Type  
Max BHP  
1 / Belt  
1.2  
770---1175  
48  
1 / Centrifugal  
10 x 10  
1 / Belt  
1.2  
770---1175  
56  
1 / Centrifugal  
10 x 10  
1 / Belt  
1.5  
1035---1466  
56  
1 / Centrifugal  
10 x 10  
---  
---  
---  
---  
---  
---  
RPM Range  
Motor Frame Size  
Fan Qty / Type  
Fan Diameter (in)  
Motor Qty / Drive Type  
Max BHP  
1 / Belt  
1.2  
1 / Belt  
1.2  
1 / Belt  
2.4  
1 / Belt  
2.9  
RPM Range  
770---1175  
48  
1 / Centrifugal  
10 x 10  
770---1175  
48  
1 / Centrifugal  
10 x 10  
1035---1466  
56  
1 / Centrifugal  
10 x 10  
1173---1788  
56  
1 / Centrifugal  
10 x 10  
Motor Frame Size  
Fan Qty / Type  
Fan Diameter (in)  
Motor Qty / Drive Type  
Max BHP  
1 / Belt  
2.4  
1 / Belt  
2.4  
1 / Belt  
2.9  
1 / Belt  
3.7  
RPM Range  
1035---1466  
56  
1 / Centrifugal  
10 x 10  
1035---1466  
56  
1 / Centrifugal  
10 x 10  
1303---1687  
56  
1 / Centrifugal  
10 x 10  
1474---1788  
56  
1 / Centrifugal  
10 x 10  
Motor Frame Size  
Fan Qty / Type  
Fan Diameter (in)  
Cond. Coil  
Material  
Coil type  
Cu / Al  
3/8” RTPF  
1 / 17  
Cu / Al  
3/8” RTPF  
2 / 17  
Cu / Al  
3/8” RTPF  
2 / 17  
Cu / Al  
3/8” RTPF  
2 / 17  
Rows / FPI  
2
Total Face Area (ft )  
14.6  
12.6  
16.5  
21.3  
Cond. fan / motor  
Filters  
Qty / Motor Drive Type  
Motor HP / RPM  
1/ Direct  
1/4 / 1100  
22  
1/ Direct  
1/4 / 1100  
22  
1/ Direct  
1/4 / 1100  
22  
1/ Direct  
1/4 / 1100  
22  
Fan diameter (in)  
RA Filter # / Size (in)  
OA inlet screen # / Size (in)  
2 / 16 x 25 x 2  
1 / 20 x 24 x 1  
2 / 16 x 25 x 2  
1 / 20 x 24 x 1  
2 / 16 x 25 x 2  
1 / 20 x 24 x 1  
4 / 16 x 16 x 2  
1 / 20 x 24 x 1  
83  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX II. PHYSICAL DATA (cont.)  
7.5 -- 10 TONS  
Physical Data (Cooling)  
48TC*A08  
48TC*A09  
48TC*A12  
Refrigeration System  
# Circuits / # Comp. / Type  
Puron (R---410a) charge A/B (lbs)  
Oil A/B (oz)  
1 / 1 / Scroll  
13.75  
1 / 1 / Scroll  
15.25  
1 / 1 / Scroll  
20.0  
60  
85  
110  
Metering Device  
High---press. Trip / Reset (psig)  
Low---press. Trip / Reset (psig)  
Acutrol  
630 / 505  
54 / 117  
Acutrol  
630 / 505  
54 / 117  
Acutrol  
630 / 505  
54 / 117  
Evap. Coil  
Material  
Coil type  
Cu / Al  
3/8” RTPF  
3 / 15  
Cu / Al  
3/8” RTPF  
3 / 15  
Cu / Al  
3/8” RTPF  
4 / 15  
Rows / FPI  
2
Total Face Area (ft )  
8.9  
11.1  
11.1  
Condensate Drain Conn. Size  
3/4”  
3/4”  
3/4”  
Evap. Fan and Motor  
1 / Belt  
1.7  
1 / Belt  
2.4  
Motor Qty / Drive Type  
Max BHP  
1 / Belt  
1.7  
RPM Range  
489---747  
56  
1 / Centrifugal  
15 x 15  
518---733  
56  
1 / Centrifugal  
15 x 15  
591---838  
56  
1 / Centrifugal  
15 x 15  
Motor Frame Size  
Fan Qty / Type  
Fan Diameter (in)  
Motor Qty / Drive Type  
Max BHP  
1 / Belt  
2.9  
733---949  
56  
1 / Centrifugal  
15 x 15  
1 / Belt  
2.4  
690---936  
56  
1 / Centrifugal  
15 x 15  
1 / Belt  
3.7  
838---1084  
56  
1 / Centrifugal  
15 x 15  
RPM Range  
Motor Frame Size  
Fan Qty / Type  
Fan Diameter (in)  
Motor Qty / Drive Type  
Max BHP  
1 / Belt  
5.25  
1 / Belt  
3.7  
1 / Belt  
5.25  
RPM Range  
909---1102  
145TY  
1 / Centrifugal  
15 x 15  
838---1084  
56  
1 / Centrifugal  
15 x 15  
1022---1240  
145TY  
1 / Centrifugal  
15 x 15  
Motor Frame Size  
Fan Qty / Type  
Fan Diameter (in)  
Cond. Coil  
Material  
Coil type  
Cu / Al  
3/8” RTPF  
2 / 17  
Cu / Al  
3/8” RTPF  
2 / 17  
Cu / Al  
3/8” RTPF  
2 / 17  
Rows / FPI  
2
Total Face Area (ft )  
20.5  
21.4  
25.1  
Cond. fan / motor  
Filters  
Qty / Motor Drive Type  
Motor HP / RPM  
2 / Direct  
1/4 / 1100  
22  
2 / Direct  
1/4 / 1100  
22  
2 / Direct  
1/4 / 1100  
22  
Fan diameter (in)  
RA Filter # / Size (in)  
OA inlet screen # / Size (in)  
4 / 16 x 20 x 2  
1 / 20 x 24 x 1  
4 / 20 x 20 x 2  
1 / 20 x 24 x 1  
4 / 20 x 20 x 2  
1 / 20 x 24 x 1  
84  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX II. PHYSICAL DATA (cont.)  
3 -- 6 TONS  
Physical Data (Heating)  
48TC**04  
48TC**05  
48TC**06  
48TC**07  
Gas Connection  
# of Gas Valves  
1
1
1
1
Connection size  
Nat. gas supply line press (in. w.g.)/(PSIG)  
LP supply line press (in. w.g.)/(PSIG)  
1/2” NPT  
1/2” NPT  
1/2” NPT  
1/2” NPT  
5 --- 1 3 / 0 . 1 8 --- 0 . 4 7  
11---13 / 0.40---0.47  
5 --- 1 3 / 0 . 1 8 --- 0 . 4 7  
11---13 / 0.40---0.47  
5 --- 1 3 / 0 . 1 8 --- 0 . 4 7  
11---13 / 0.40---0.47  
5 --- 1 3 / 0 . 1 8 --- 0 . 4 7  
11---13 / 0.40---0.47  
Heat Anticipator Setting (Amps)  
1st stage  
0.14  
0.14  
0.14  
0.14  
0.14  
0.14  
0.14  
0.14  
2nd stage  
Natural Gas Heat  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise  
1 / 2  
1 / 2  
1 / 2  
1 / 2  
195 / 115  
25 / 55  
195 / 115  
25 --- 55  
195 / 115  
25 --- 55  
195 / 115  
25 --- 55  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise  
1 or 2 / 3  
195 / 115  
55 / 85  
1 / 3  
1 / 3  
1 / 3  
195 / 115  
35 / 65  
195 / 115  
35 / 65  
195 / 115  
35 / 65  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise  
---  
---  
---  
1 or 2 / 3  
195 / 115  
50 / 80  
1 or 2 / 3  
195 / 115  
50 / 80  
1 or 2 / 3  
195 / 115  
50 / 80  
Liquid Propane Heat  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise  
1 / 2  
1 / 2  
1 / 2  
1 / 2  
195 / 115  
25 / 55  
195 / 115  
25 --- 55  
195 / 115  
25 --- 55  
195 / 115  
25 --- 55  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise  
1 or 2 / 3  
195 / 115  
55 / 85  
1 or 2 / 3  
195 / 115  
35 / 65  
1 or 2 / 3  
195 / 115  
35 / 65  
1 or 2 / 3  
195 / 115  
35 / 65  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise  
---  
---  
---  
1 or 2 / 3  
195 / 115  
50 / 80  
1 or 2 / 3  
195 / 115  
50 / 80  
1 or 2 / 3  
195 / 115  
50 / 80  
Low NO Gas Heat  
x
# of stages / # of burners (total)  
1 / 2  
1 / 2  
1 / 2  
---  
---  
---  
Rollout switch opens / Closes  
Temperature rise  
195 / 115  
20 / 50  
195 / 115  
20 / 50  
195 / 115  
20 / 50  
# of stages / # of burners (total)  
Rollout switch opens / closes  
Temperature rise  
1 / 3  
1 / 3  
1 / 3  
---  
---  
---  
195 / 115  
30 / 60  
195 / 115  
30 / 60  
195 / 115  
30 / 60  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise  
---  
---  
---  
1 / 3  
1 / 3  
---  
---  
---  
195 / 115  
40 / 70  
195 / 115  
40 / 70  
85  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX II. PHYSICAL DATA (cont.)  
7.5 -- 10 TONS  
Physical Data (Heating)  
48TC**04  
48TC**05  
48TC**06  
48TC**07  
Gas Connection  
# of Gas Valves  
1
1
1
1
Nat. gas supply line press (in. w.g.)/(PSIG)  
LP supply line press (in. w.g.)/(PSIG)  
4 --- 1 3 / 0 . 1 8 --- 0 . 4 7  
11---13 / 0.40---0.47  
4 --- 1 3 / 0 . 1 8 --- 0 . 4 7  
11---13 / 0.40---0.47  
4 --- 1 3 / 0 . 1 8 --- 0 . 4 7  
11---13 / 0.40---0.47  
4 --- 1 3 / 0 . 1 8 --- 0 . 4 7  
11---13 / 0.40---0.47  
Heat Anticipator Setting (Amps)  
1st stage  
0.14  
0.14  
0.14  
0.14  
0.14  
0.14  
0.14  
0.14  
2nd stage  
Natural Gas Heat  
Connection size  
1/2” NPT  
1 / 2  
195 / 115  
25 / 55  
1/2” NPT  
1 / 2  
195 / 115  
25 --- 55  
1/2” NPT  
1 / 2  
195 / 115  
25 --- 55  
1/2” NPT  
1 / 2  
195 / 115  
25 --- 55  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise (min/max)  
Connection size  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise (min/max)  
1/2” NPT  
1 or 2 / 3  
195 / 115  
55 / 85  
1/2” NPT  
1 / 3  
195 / 115  
35 / 65  
1/2” NPT  
1 / 3  
195 / 115  
35 / 65  
1/2” NPT  
1 / 3  
195 / 115  
35 / 65  
Connection size  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise (min/max)  
1/2” NPT  
1/2” NPT  
1 or 2 / 3  
195 / 115  
50 / 80  
1/2” NPT  
1 or 2 / 3  
195 / 115  
50 / 80  
1/2” NPT  
1 or 2 / 3  
195 / 115  
50 / 80  
---  
---  
---  
Liquid Propane Heat  
Connection size  
1/2” NPT  
1 / 2  
195 / 115  
25 / 55  
1/2” NPT  
1 / 2  
195 / 115  
25 --- 55  
1/2” NPT  
1 / 2  
195 / 115  
25 --- 55  
1/2” NPT  
1 / 2  
195 / 115  
25 --- 55  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise (min/max)  
Connection size  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise (min/max)  
1/2” NPT  
1 or 2 / 3  
195 / 115  
55 / 85  
1/2” NPT  
1 or 2 / 3  
195 / 115  
35 / 65  
1/2” NPT  
1 or 2 / 3  
195 / 115  
35 / 65  
1/2” NPT  
1 or 2 / 3  
195 / 115  
35 / 65  
Connection size  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise (min/max)  
1/2” NPT  
1/2” NPT  
1 or 2 / 3  
195 / 115  
50 / 80  
1/2” NPT  
1 or 2 / 3  
195 / 115  
50 / 80  
1/2” NPT  
1 or 2 / 3  
195 / 115  
50 / 80  
---  
---  
---  
Low NO Gas Heat  
x
Connection size  
1/2” NPT  
1 / 2  
195 / 115  
20 / 50  
1/2” NPT  
1 / 2  
195 / 115  
20 / 50  
1/2” NPT  
1 / 2  
195 / 115  
20 / 50  
1/2” NPT  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise (min/max)  
---  
---  
---  
Connection size  
# of stages / # of burners (total)  
Rollout switch opens / closes  
Temperature rise (min/max)  
1/2” NPT  
1 / 3  
195 / 115  
30 / 60  
1/2” NPT  
1 / 3  
195 / 115  
30 / 60  
1/2” NPT  
1 / 3  
195 / 115  
30 / 60  
1/2” NPT  
---  
---  
---  
Connection size  
# of stages / # of burners (total)  
Rollout switch opens / Closes  
Temperature rise (min/max)  
1/2” NPT  
1/2” NPT  
1 / 3  
195 / 115  
40 / 70  
1/2” NPT  
1 / 3  
195 / 115  
40 / 70  
1/2” NPT  
---  
---  
---  
---  
---  
---  
86  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE  
General Fan Performance Notes:  
1. Interpolation is permissible. Do not extrapolate.  
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static  
pressure caused by any FIOPs or accessories.  
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories  
may add static pressure losses.  
4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would  
work, Carrier recommended the lower horsepower option.  
5. For information on the electrical properties of Carrier’s motors, please see the Electrical information section of this  
book.  
87  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
48TC**04  
1 Phase  
3 Ton Horizontal Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
F i e l d --- S u p p l i e d D r i v e  
Standard Static Option  
Medium Static Option  
900  
975  
553  
575  
597  
620  
643  
667  
691  
715  
740  
0.14  
0.16  
0.18  
0.21  
0.23  
0.27  
0.30  
0.34  
0.38  
681  
700  
720  
741  
762  
783  
805  
827  
849  
0.22  
0.25  
0.28  
0.31  
0.34  
0.38  
0.42  
0.47  
0.52  
782  
801  
820  
839  
859  
879  
900  
920  
941  
0.32  
0.35  
0.38  
0.42  
0.46  
0.50  
0.55  
0.60  
0.66  
870  
888  
906  
925  
944  
963  
983  
1002  
1023  
0.42  
0.46  
0.49  
0.54  
0.58  
0.63  
0.68  
0.74  
0.80  
948  
965  
983  
1001  
1020  
1038  
1057  
1076  
1096  
0.53  
0.57  
0.61  
0.66  
0.71  
0.76  
0.82  
0.88  
0.95  
1050  
1125  
1200  
1275  
1350  
1425  
1500  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
2
Medium Static Option  
F i e l d --- S u p p l i e d D r i v e  
900  
975  
1019  
1036  
1053  
1071  
1089  
1107  
1126  
1144  
1163  
0.64  
0.69  
0.74  
0.79  
0.84  
0.90  
0.96  
1.03  
1.10  
1084  
1101  
1118  
1135  
1153  
1171  
1189  
1208  
---  
0.76  
0.81  
0.86  
0.92  
0.98  
1.04  
1.11  
1.18  
---  
1146  
1162  
1179  
1196  
1213  
1231  
---  
0.89  
0.94  
1.00  
1.06  
1.12  
1.19  
---  
1203  
1219  
1236  
1253  
---  
---  
---  
---  
---  
1.02  
1.08  
1.14  
1.20  
---  
---  
---  
---  
---  
1258  
1.16  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
1050  
1125  
1200  
1275  
1350  
1425  
1500  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).  
2. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).  
48TC**04  
1 Phase  
3 Ton Vertical Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.4 0.6 0.8  
0.2  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
F i e l d --- S u p p l i e d D r i v e  
Standard Static Option  
Medium Static Option  
900  
975  
567  
591  
615  
641  
666  
693  
719  
746  
773  
0.15  
0.17  
0.20  
0.23  
0.26  
0.29  
0.33  
0.38  
0.42  
688  
710  
732  
755  
778  
802  
826  
850  
875  
0.22  
0.26  
0.29  
0.33  
0.37  
0.41  
0.46  
0.51  
0.57  
786  
807  
828  
849  
871  
893  
916  
939  
963  
0.30  
0.34  
0.38  
0.42  
0.47  
0.53  
0.58  
0.64  
0.70  
871  
891  
911  
931  
952  
974  
995  
1017  
1040  
0.37  
0.42  
0.47  
0.52  
0.57  
0.63  
0.70  
0.76  
0.84  
947  
966  
985  
1005  
1025  
1046  
1067  
1088  
1110  
0.44  
0.49  
0.55  
0.61  
0.67  
0.74  
0.81  
0.89  
0.96  
1050  
1125  
1200  
1275  
1350  
1425  
1500  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
2
Medium Static Option  
F i e l d --- S u p p l i e d D r i v e  
900  
975  
1016  
1034  
1053  
1073  
1093  
1113  
1133  
1154  
1175  
0.51  
0.57  
0.63  
0.70  
0.77  
0.85  
0.92  
1.01  
1.09  
1080  
1098  
1116  
1135  
1155  
1174  
1194  
1215  
---  
0.57  
0.64  
0.71  
0.79  
0.87  
0.95  
1.03  
1.12  
---  
1139  
1157  
1176  
1194  
1213  
1232  
1252  
---  
0.64  
0.72  
0.79  
0.87  
0.96  
1.05  
1.14  
---  
1195  
1213  
1231  
1250  
1268  
1287  
---  
0.71  
0.79  
0.87  
0.96  
1.05  
1.15  
---  
1249  
1266  
1284  
1302  
1321  
---  
---  
---  
---  
0.77  
0.86  
0.95  
1.04  
1.14  
---  
---  
---  
---  
1050  
1125  
1200  
1275  
1350  
1425  
1500  
---  
---  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).  
2. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).  
88  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
48TC**04  
3 Phase  
3 Ton Horizontal Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
F i e l d --- S u p p l i e d D r i v e  
Standard Static Option  
Medium Static Option  
900  
975  
553  
575  
597  
620  
643  
667  
691  
715  
740  
0.14  
0.16  
0.18  
0.21  
0.23  
0.27  
0.30  
0.34  
0.38  
681  
700  
720  
741  
762  
783  
805  
827  
849  
0.22  
0.25  
0.28  
0.31  
0.34  
0.38  
0.42  
0.47  
0.52  
782  
801  
820  
839  
859  
879  
900  
920  
941  
0.32  
0.35  
0.38  
0.42  
0.46  
0.50  
0.55  
0.60  
0.66  
870  
888  
906  
925  
944  
963  
983  
1002  
1023  
0.42  
0.46  
0.49  
0.54  
0.58  
0.63  
0.68  
0.74  
0.80  
948  
965  
983  
1001  
1020  
1038  
1057  
1076  
1096  
0.53  
0.57  
0.61  
0.66  
0.71  
0.76  
0.82  
0.88  
0.95  
1050  
1125  
1200  
1275  
1350  
1425  
1500  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
900  
975  
1019  
1036  
1053  
1071  
1089  
1107  
1126  
1144  
1163  
0.64  
0.69  
0.74  
0.79  
0.84  
0.90  
0.96  
1.03  
1.10  
1084  
1101  
1118  
1135  
1153  
1171  
1189  
1208  
1226  
0.76  
0.81  
0.86  
0.92  
0.98  
1.04  
1.11  
1.18  
1.25  
1146  
1162  
1179  
1196  
1213  
1231  
1249  
1267  
1285  
0.89  
0.94  
1.00  
1.06  
1.12  
1.19  
1.26  
1.34  
1.41  
1203  
1219  
1236  
1253  
1270  
1287  
1305  
1323  
1341  
1.02  
1.08  
1.14  
1.20  
1.27  
1.34  
1.42  
1.50  
1.58  
1258  
1274  
1290  
1307  
1324  
1341  
1358  
1376  
1394  
1.16  
1.22  
1.28  
1.35  
1.42  
1.50  
1.58  
1.66  
1.75  
1050  
1125  
1200  
1275  
1350  
1425  
1500  
NOTE: For more information, see General Fan Performance Notes on page 87.  
1. Recommend using field---supplied drive (part number KR11AG006) and belt (part number KR30AE039)  
48TC**04  
3 Phase  
3 Ton Vertical Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.4 0.6 0.8  
0.2  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
F i e l d --- S u p p l i e d D r i v e  
Standard Static Option  
Medium Static Option  
900  
975  
567  
591  
615  
641  
666  
693  
719  
746  
773  
0.15  
0.17  
0.20  
0.23  
0.26  
0.29  
0.33  
0.38  
0.42  
688  
710  
732  
755  
778  
802  
826  
850  
875  
0.22  
0.26  
0.29  
0.33  
0.37  
0.41  
0.46  
0.51  
0.57  
786  
807  
828  
849  
871  
893  
916  
939  
963  
0.30  
0.34  
0.38  
0.42  
0.47  
0.53  
0.58  
0.64  
0.70  
871  
891  
911  
931  
952  
974  
995  
1017  
1040  
0.37  
0.42  
0.47  
0.52  
0.57  
0.63  
0.70  
0.76  
0.84  
947  
966  
985  
1005  
1025  
1046  
1067  
1088  
1110  
0.44  
0.49  
0.55  
0.61  
0.67  
0.74  
0.81  
0.89  
0.96  
1050  
1125  
1200  
1275  
1350  
1425  
1500  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
900  
975  
1016  
1034  
1053  
1073  
1093  
1113  
1133  
1154  
1175  
0.51  
0.57  
0.63  
0.70  
0.77  
0.85  
0.92  
1.01  
1.09  
1080  
1098  
1116  
1135  
1155  
1174  
1194  
1215  
1235  
0.57  
0.64  
0.71  
0.79  
0.87  
0.95  
1.03  
1.12  
1.22  
1139  
1157  
1176  
1194  
1213  
1232  
1252  
1272  
1292  
0.64  
0.72  
0.79  
0.87  
0.96  
1.05  
1.14  
1.24  
1.34  
1195  
1213  
1231  
1250  
1268  
1287  
1307  
1326  
1346  
0.71  
0.79  
0.87  
0.96  
1.05  
1.15  
1.25  
1.35  
1.46  
1249  
1266  
1284  
1302  
1321  
1339  
1358  
1378  
1397  
0.77  
0.86  
0.95  
1.04  
1.14  
1.25  
1.35  
1.46  
1.58  
1050  
1125  
1200  
1275  
1350  
1425  
1500  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).  
89  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
48TC**05  
1 Phase  
4 Ton Horizontal Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
643  
675  
707  
740  
773  
807  
841  
875  
910  
0.23  
0.28  
0.33  
0.38  
0.45  
0.52  
0.59  
0.68  
0.77  
762  
790  
819  
849  
879  
910  
942  
974  
1006  
0.34  
0.40  
0.45  
0.52  
0.59  
0.67  
0.75  
0.85  
0.95  
859  
886  
913  
941  
970  
0.46  
0.52  
0.58  
0.66  
0.73  
0.82  
0.91  
1.02  
1.13  
944  
969  
996  
1023  
1050  
1078  
1106  
1135  
1165  
0.58  
0.65  
0.72  
0.80  
0.88  
0.98  
1.08  
1.19  
1.31  
1020  
1044  
1070  
1096  
1123  
1150  
1177  
1205  
1234  
0.71  
0.78  
0.86  
0.95  
1.04  
1.14  
1.25  
1.37  
1.49  
999  
1029  
1059  
1090  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
Medium Static Option  
F i e l d --- S u p p l i e d D r i v e  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
1089  
1113  
1138  
1163  
1189  
---  
---  
---  
---  
0.84  
0.92  
1.01  
1.10  
1.20  
---  
---  
---  
---  
1153  
1177  
1201  
---  
---  
---  
---  
---  
---  
0.98  
1.06  
1.15  
---  
---  
---  
---  
---  
---  
1213  
1.12  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).  
48TC**05  
1 Phase  
4 Ton Vertical Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.4 0.6 0.8  
0.2  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
666  
701  
737  
773  
810  
847  
885  
923  
962  
0.26  
0.31  
0.36  
0.42  
0.49  
0.57  
0.66  
0.75  
0.85  
778  
810  
842  
875  
909  
943  
978  
1014  
1049  
0.37  
0.43  
0.49  
0.57  
0.65  
0.73  
0.83  
0.94  
1.05  
871  
901  
931  
963  
994  
1027  
1060  
1093  
1127  
0.47  
0.54  
0.62  
0.70  
0.79  
0.89  
1.00  
1.11  
1.24  
952  
981  
0.57  
0.65  
0.74  
0.84  
0.94  
1.05  
1.16  
1.29  
1.42  
1025  
1053  
1081  
1110  
1140  
1170  
1200  
1231  
1263  
0.67  
0.76  
0.86  
0.96  
1.08  
1.20  
1.32  
1.46  
1.61  
1010  
1040  
1070  
1101  
1133  
1165  
1198  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
Medium Static Option  
F i e l d --- S u p p l i e d D r i v e  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
1093  
1119  
1147  
1175  
---  
---  
---  
---  
---  
0.77  
0.87  
0.98  
1.09  
---  
---  
---  
---  
---  
1155  
1181  
1208  
---  
---  
---  
---  
---  
---  
0.87  
0.98  
1.09  
---  
---  
---  
---  
---  
---  
1213  
1239  
0.96  
1.08  
---  
---  
---  
---  
---  
---  
---  
1268  
1294  
1.05  
1.18  
---  
---  
---  
---  
---  
---  
---  
1321  
1.14  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).  
90  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
48TC**05  
3 Phase  
4 Ton Horizontal Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
643  
675  
707  
740  
773  
807  
841  
875  
910  
0.23  
0.28  
0.33  
0.38  
0.45  
0.52  
0.59  
0.68  
0.77  
762  
790  
819  
849  
879  
910  
942  
974  
1006  
0.34  
0.40  
0.45  
0.52  
0.59  
0.67  
0.75  
0.85  
0.95  
859  
886  
913  
941  
970  
0.46  
0.52  
0.58  
0.66  
0.73  
0.82  
0.91  
1.02  
1.13  
944  
969  
996  
1023  
1050  
1078  
1106  
1135  
1165  
0.58  
0.65  
0.72  
0.80  
0.88  
0.98  
1.08  
1.19  
1.31  
1020  
1044  
1070  
1096  
1123  
1150  
1177  
1205  
1234  
0.71  
0.78  
0.86  
0.95  
1.04  
1.14  
1.25  
1.37  
1.49  
999  
1029  
1059  
1090  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
1089  
1113  
1138  
1163  
1189  
1216  
1242  
1270  
1297  
0.84  
0.92  
1.01  
1.10  
1.20  
1.31  
1.42  
1.55  
1.68  
1153  
1177  
1201  
1226  
1252  
1277  
1303  
1330  
1357  
0.98  
1.06  
1.15  
1.25  
1.36  
1.48  
1.60  
1.73  
1.87  
1213  
1237  
1261  
1285  
1310  
1335  
1361  
1387  
1414  
1.12  
1.21  
1.31  
1.41  
1.53  
1.65  
1.78  
1.92  
2.07  
1270  
1293  
1317  
1341  
1365  
1390  
1415  
1441  
1467  
1.27  
1.36  
1.47  
1.58  
1.70  
1.83  
1.96  
2.11  
2.26  
1324  
1347  
1370  
1394  
1418  
1442  
1467  
1493  
---  
1.42  
1.52  
1.63  
1.75  
1.87  
2.01  
2.15  
2.30  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181) and belt (part no. KR30AE041).  
48TC**05  
3 Phase  
4 Ton Vertical Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.4 0.6 0.8  
0.2  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
666  
701  
737  
773  
810  
847  
885  
923  
962  
0.26  
0.31  
0.36  
0.42  
0.49  
0.57  
0.66  
0.75  
0.85  
778  
810  
842  
875  
909  
943  
978  
1014  
1049  
0.37  
0.43  
0.49  
0.57  
0.65  
0.73  
0.83  
0.94  
1.05  
871  
901  
931  
963  
994  
1027  
1060  
1093  
1127  
0.47  
0.54  
0.62  
0.70  
0.79  
0.89  
1.00  
1.11  
1.24  
952  
981  
0.57  
0.65  
0.74  
0.84  
0.94  
1.05  
1.16  
1.29  
1.42  
1025  
1053  
1081  
1110  
1140  
1170  
1200  
1231  
1263  
0.67  
0.76  
0.86  
0.96  
1.08  
1.20  
1.32  
1.46  
1.61  
1010  
1040  
1070  
1101  
1133  
1165  
1198  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
1200  
1300  
1400  
1500  
1600  
1700  
1800  
1900  
2000  
1093  
1119  
1147  
1175  
1204  
1233  
1262  
1293  
1323  
0.77  
0.87  
0.98  
1.09  
1.21  
1.34  
1.48  
1.63  
1.79  
1155  
1181  
1208  
1235  
1263  
1292  
1321  
1350  
1380  
0.87  
0.98  
1.09  
1.22  
1.35  
1.49  
1.64  
1.79  
1.96  
1213  
1239  
1265  
1292  
1320  
1348  
1376  
1405  
1434  
0.96  
1.08  
1.21  
1.34  
1.48  
1.63  
1.79  
1.96  
2.13  
1268  
1294  
1320  
1346  
1373  
1401  
1428  
1457  
1486  
1.05  
1.18  
1.32  
1.46  
1.61  
1.77  
1.94  
2.12  
2.31  
1321  
1346  
1371  
1397  
1424  
1451  
1479  
1506  
---  
1.14  
1.28  
1.43  
1.58  
1.74  
1.91  
2.09  
2.28  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part no. KR11AZ506), motor pulley (part no. KR11HY181) and belt (part no. KR30AE041).  
91  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
48TC**06  
1 Phase  
5 Ton Horizontal Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1500  
1625  
1750  
1875  
2000  
2125  
2250  
2375  
2500  
800  
849  
899  
950  
1001  
1053  
1106  
1159  
---  
0.39  
0.48  
0.59  
0.70  
0.84  
0.99  
1.16  
1.34  
---  
904  
947  
992  
1038  
1085  
1133  
1182  
1231  
---  
0.49  
0.59  
0.70  
0.82  
0.96  
1.12  
1.29  
1.49  
---  
999  
1038  
1078  
1120  
1163  
1208  
1254  
---  
0.60  
0.70  
0.82  
0.95  
1.09  
1.26  
1.44  
---  
1087  
1122  
1159  
1198  
1238  
1280  
---  
0.72  
0.83  
0.95  
1.08  
1.23  
1.40  
---  
1169  
1201  
1235  
1271  
1309  
---  
---  
---  
---  
0.85  
0.96  
1.08  
1.22  
1.38  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
1500  
1625  
1750  
1875  
2000  
2125  
2250  
2375  
2500  
1247  
1276  
1308  
1342  
---  
---  
---  
---  
---  
0.98  
1.10  
1.22  
1.37  
---  
---  
---  
---  
---  
1320  
1348  
1377  
---  
---  
---  
---  
---  
---  
1.13  
1.24  
1.38  
---  
---  
---  
---  
---  
---  
1390  
1416  
---  
---  
---  
---  
---  
---  
---  
1.28  
1.40  
---  
---  
---  
---  
---  
---  
---  
1457  
---  
---  
---  
---  
---  
---  
---  
---  
1.44  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
48TC**06  
1 Phase  
5 Ton Vertical Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.4 0.6 0.8  
0.2  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1500  
1625  
1750  
1875  
2000  
2125  
2250  
2375  
2500  
848  
897  
947  
997  
1048  
1100  
1152  
1205  
---  
0.42  
0.51  
0.61  
0.72  
0.85  
1.00  
1.16  
1.34  
---  
968  
0.55  
0.65  
0.76  
0.89  
1.03  
1.19  
1.36  
---  
1069  
1111  
1155  
1199  
1244  
1290  
---  
0.68  
0.79  
0.91  
1.05  
1.20  
1.37  
---  
1158  
1198  
1240  
1283  
1326  
---  
---  
---  
---  
0.80  
0.93  
1.06  
1.21  
1.37  
---  
---  
---  
---  
1238  
1277  
1318  
1359  
---  
---  
---  
0.94  
1.07  
1.21  
1.37  
---  
---  
---  
1013  
1059  
1105  
1153  
1201  
1250  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
Medium Static Option  
F i e l d --- S u p p l i e d D r i v e  
1500  
1625  
1750  
1875  
2000  
2125  
2250  
2375  
2500  
1312  
1350  
1390  
---  
---  
---  
---  
---  
---  
1.07  
1.21  
1.36  
---  
---  
---  
---  
---  
---  
1380  
1418  
---  
---  
---  
---  
---  
---  
---  
1.20  
1.35  
---  
---  
---  
---  
---  
---  
---  
1445  
1482  
1.34  
1.50  
---  
---  
---  
---  
---  
---  
---  
1506  
1.48  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied motor pulley (part number KR11HY171) and belt (part number KR30AE039).  
92  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
48TC**06  
3 Phase  
5 Ton Horizontal Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1500  
1625  
1750  
1875  
2000  
2125  
2250  
2375  
2500  
800  
849  
899  
0.39  
0.48  
0.59  
0.70  
0.84  
0.99  
1.16  
1.34  
1.55  
904  
947  
992  
1038  
1085  
1133  
1182  
1231  
1281  
0.49  
0.59  
0.70  
0.82  
0.96  
1.12  
1.29  
1.49  
1.70  
999  
0.60  
0.70  
0.82  
0.95  
1.09  
1.26  
1.44  
1.64  
1.86  
1087  
1122  
1159  
1198  
1238  
1280  
1323  
1367  
1412  
0.72  
0.83  
0.95  
1.08  
1.23  
1.40  
1.59  
1.80  
2.02  
1169  
1201  
1235  
1271  
1309  
1348  
1389  
1430  
1473  
0.85  
0.96  
1.08  
1.22  
1.38  
1.55  
1.74  
1.96  
2.19  
1038  
1078  
1120  
1163  
1208  
1254  
1300  
1348  
950  
1001  
1053  
1106  
1159  
1212  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
1500  
1625  
1750  
1875  
2000  
2125  
2250  
2375  
2500  
1247  
1276  
1308  
1342  
1377  
1414  
1452  
1492  
1533  
0.98  
1.10  
1.22  
1.37  
1.53  
1.71  
1.91  
2.12  
2.36  
1320  
1348  
1377  
1409  
1442  
1477  
1514  
1551  
1591  
1.13  
1.24  
1.38  
1.52  
1.69  
1.87  
2.08  
2.30  
2.54  
1390  
1416  
1444  
1473  
1505  
1538  
1573  
1609  
1647  
1.28  
1.40  
1.53  
1.69  
1.86  
2.04  
2.25  
2.48  
2.73  
1457  
1481  
1507  
1536  
1565  
1597  
1630  
1665  
---  
1.44  
1.56  
1.70  
1.86  
2.03  
2.22  
2.43  
2.66  
---  
1522  
1544  
1569  
1596  
1624  
1654  
1686  
1719  
---  
1.61  
1.73  
1.87  
2.03  
2.21  
2.40  
2.62  
2.85  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number  
KR30AE042).  
48TC**06  
3 Phase  
5 Ton Vertical Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.4 0.6 0.8  
0.2  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1500  
1625  
1750  
1875  
2000  
2125  
2250  
2375  
2500  
848  
897  
947  
0.42  
0.51  
0.61  
0.72  
0.85  
1.00  
1.16  
1.34  
1.54  
968  
0.55  
0.65  
0.76  
0.89  
1.03  
1.19  
1.36  
1.55  
1.76  
1069  
1111  
1155  
1199  
1244  
1290  
1336  
1384  
1431  
0.68  
0.79  
0.91  
1.05  
1.20  
1.37  
1.55  
1.76  
1.98  
1158  
1198  
1240  
1283  
1326  
1370  
1415  
1460  
1506  
0.80  
0.93  
1.06  
1.21  
1.37  
1.55  
1.75  
1.96  
2.20  
1238  
1277  
1318  
1359  
1401  
1444  
1487  
1532  
1576  
0.94  
1.07  
1.21  
1.37  
1.54  
1.73  
1.94  
2.17  
2.41  
1013  
1059  
1105  
1153  
1201  
1250  
1299  
1349  
997  
1048  
1100  
1152  
1205  
1258  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
1500  
1625  
1750  
1875  
2000  
2125  
2250  
2375  
2500  
1312  
1350  
1390  
1430  
1471  
1513  
1555  
1598  
1642  
1.07  
1.21  
1.36  
1.53  
1.72  
1.92  
2.13  
2.37  
2.63  
1380  
1418  
1457  
1496  
1536  
1577  
1619  
1661  
1704  
1.20  
1.35  
1.51  
1.69  
1.89  
2.10  
2.33  
2.57  
2.84  
1445  
1482  
1520  
1559  
1598  
1638  
1679  
1720  
---  
1.34  
1.50  
1.67  
1.86  
2.06  
2.28  
2.52  
2.78  
---  
1506  
1542  
1580  
1618  
1657  
1696  
1736  
---  
1.48  
1.64  
1.83  
2.02  
2.24  
2.47  
2.72  
---  
1564  
1600  
1637  
1675  
1713  
1752  
---  
1.62  
1.79  
1.98  
2.19  
2.41  
2.65  
---  
---  
---  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number  
KR30AE042).  
93  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
48TC**07  
3 Phase  
6 Ton Horizontal Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
F i e l d --- S u p p l i e d D r i v e  
Standard Static Option  
Medium Static Option  
1800  
1950  
2100  
2250  
2400  
2550  
2700  
2850  
3000  
913  
972  
0.64  
0.78  
0.95  
1.14  
1.36  
1.60  
1.87  
2.17  
2.50  
1010  
1065  
1120  
1177  
1234  
1293  
1352  
1412  
1472  
0.80  
0.96  
1.14  
1.34  
1.57  
1.82  
2.10  
2.42  
2.76  
1098  
1148  
1200  
1254  
1308  
1363  
1420  
1477  
1535  
0.98  
1.14  
1.33  
1.55  
1.78  
2.05  
2.34  
2.67  
3.03  
1178  
1226  
1275  
1325  
1377  
1430  
1484  
1539  
1595  
1.16  
1.34  
1.54  
1.76  
2.01  
2.28  
2.59  
2.93  
3.29  
1252  
1298  
1345  
1393  
1443  
1494  
1546  
1599  
1653  
1.35  
1.54  
1.75  
1.98  
2.24  
2.53  
2.84  
3.19  
3.57  
1032  
1093  
1155  
1217  
1280  
1343  
1406  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
1800  
1950  
2100  
2250  
2400  
2550  
2700  
2850  
3000  
1322  
1366  
1411  
1457  
1505  
1554  
1604  
1656  
---  
1.56  
1.75  
1.97  
2.21  
2.48  
2.78  
3.10  
3.46  
---  
1388  
1430  
1473  
1518  
1564  
1612  
1660  
---  
1.77  
1.97  
2.20  
2.45  
2.73  
3.03  
3.37  
---  
1451  
1491  
1533  
1576  
1621  
1667  
1715  
---  
1.98  
2.20  
2.43  
2.69  
2.98  
3.30  
3.64  
---  
1510  
1550  
1590  
1632  
1676  
1721  
---  
2.21  
2.43  
2.67  
2.94  
3.24  
3.57  
---  
1568  
1606  
1645  
1686  
1729  
---  
---  
---  
---  
2.44  
2.67  
2.92  
3.20  
3.51  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part number KR11AZ406), motor pulley (part number KR11HY151) and belt (part number  
KR29AF035).  
48TC**07  
3 Phase  
6 Ton Vertical Supply  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.4 0.6 0.8  
0.2  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
1800  
1950  
2100  
2250  
2400  
2550  
2700  
2850  
3000  
967  
0.63  
0.77  
0.93  
1.11  
1.32  
1.55  
1.80  
2.09  
2.40  
1075  
1132  
1189  
1248  
1308  
1369  
1431  
1493  
1556  
0.80  
0.96  
1.14  
1.33  
1.55  
1.80  
2.07  
2.37  
2.70  
1170  
1223  
1278  
1333  
1390  
1448  
1507  
1566  
1627  
0.97  
1.14  
1.33  
1.55  
1.78  
2.05  
2.33  
2.65  
3.00  
1255  
1306  
1358  
1411  
1466  
1521  
1578  
1636  
1694  
1.13  
1.32  
1.52  
1.75  
2.01  
2.29  
2.59  
2.92  
3.29  
1333  
1382  
1433  
1484  
1537  
1590  
1645  
1701  
1757  
1.28  
1.49  
1.71  
1.96  
2.23  
2.52  
2.84  
3.19  
3.57  
1029  
1091  
1154  
1218  
1283  
1348  
1414  
1479  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
1800  
1950  
2100  
2250  
2400  
2550  
2700  
2850  
3000  
1406  
1454  
1502  
1552  
1603  
1655  
1709  
1763  
---  
1.43  
1.65  
1.89  
2.15  
2.44  
2.75  
3.09  
3.45  
---  
1475  
1521  
1568  
1617  
1666  
1717  
1769  
---  
---  
1.58  
1.82  
2.07  
2.35  
2.65  
2.98  
3.33  
---  
---  
1540  
1585  
1631  
1678  
1727  
1776  
1827  
---  
---  
1.72  
1.98  
2.25  
2.54  
2.86  
3.20  
3.57  
---  
---  
1601  
1645  
1690  
1737  
1784  
1833  
---  
1.87  
2.13  
2.42  
2.73  
3.06  
3.42  
---  
1660  
1703  
1747  
1793  
1839  
1887  
---  
2.00  
2.29  
2.59  
2.92  
3.26  
3.64  
---  
---  
---  
---  
---  
---  
---  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY191) and belt (part number  
KR29AF042).  
94  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
48TC**08  
3 PHASE  
7.5 TON HORIZONTAL SUPPLY  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
2250  
2438  
2625  
2813  
3000  
3188  
3375  
3563  
3750  
505  
533  
562  
591  
621  
652  
682  
713  
745  
0.52  
0.62  
0.74  
0.88  
1.03  
1.21  
1.40  
1.61  
1.85  
586  
610  
635  
661  
688  
715  
743  
772  
801  
0.73  
0.85  
0.98  
1.13  
1.29  
1.48  
1.68  
1.91  
2.15  
657  
679  
701  
725  
749  
774  
800  
826  
853  
0.97  
1.09  
1.23  
1.39  
1.57  
1.77  
1.98  
2.22  
2.48  
722  
742  
762  
783  
806  
829  
853  
878  
903  
1.22  
1.36  
1.51  
1.68  
1.87  
2.07  
2.30  
2.55  
2.82  
782  
800  
819  
839  
859  
881  
903  
927  
951  
1.50  
1.65  
1.81  
1.98  
2.18  
2.40  
2.63  
2.89  
3.18  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
2250  
2438  
2625  
2813  
3000  
3188  
3375  
3563  
3750  
838  
854  
872  
890  
910  
930  
951  
973  
996  
1.81  
1.96  
2.12  
2.31  
2.51  
2.74  
2.99  
3.26  
3.55  
891  
906  
922  
940  
958  
977  
997  
1018  
1040  
2.12  
2.28  
2.46  
2.65  
2.86  
3.10  
3.35  
3.63  
3.93  
941  
955  
970  
2.46  
2.63  
2.81  
3.01  
3.23  
3.47  
3.74  
4.02  
4.34  
988  
2.82  
2.99  
3.17  
3.38  
3.61  
3.86  
4.13  
4.43  
4.75  
1033  
1046  
1060  
1074  
1090  
1107  
1124  
1143  
1162  
3.19  
3.37  
3.56  
3.77  
4.01  
4.26  
4.54  
4.85  
5.18  
1001  
1016  
1031  
1048  
1065  
1083  
1103  
1122  
986  
1004  
1022  
1041  
1061  
1082  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).  
48TC**08  
3 PHASE  
7.5 TON VERTICAL SUPPLY  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
2250  
2438  
2625  
2813  
3000  
3188  
3375  
3563  
3750  
513  
541  
570  
600  
629  
660  
690  
721  
752  
0.54  
0.65  
0.77  
0.91  
1.07  
1.25  
1.45  
1.67  
1.91  
595  
620  
645  
672  
699  
726  
754  
783  
812  
0.76  
0.89  
1.02  
1.18  
1.35  
1.54  
1.75  
1.98  
2.24  
665  
688  
712  
736  
761  
787  
813  
840  
867  
1.01  
1.14  
1.29  
1.46  
1.64  
1.85  
2.07  
2.32  
2.59  
728  
750  
772  
794  
818  
842  
867  
892  
918  
1.27  
1.42  
1.58  
1.76  
1.95  
2.17  
2.41  
2.67  
2.95  
786  
806  
827  
848  
871  
894  
917  
941  
966  
1.56  
1.71  
1.88  
2.07  
2.28  
2.51  
2.76  
3.03  
3.32  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
2250  
2438  
2625  
2813  
3000  
3188  
3375  
3563  
3750  
839  
858  
878  
899  
920  
942  
964  
988  
1011  
1.86  
2.02  
2.20  
2.40  
2.62  
2.86  
3.12  
3.41  
3.71  
889  
907  
926  
946  
966  
987  
1009  
1032  
1054  
2.18  
2.35  
2.54  
2.75  
2.98  
3.23  
3.50  
3.80  
4.11  
935  
953  
972  
2.52  
2.70  
2.89  
3.11  
3.35  
3.61  
3.89  
4.20  
4.53  
980  
997  
2.87  
3.06  
3.26  
3.49  
3.74  
4.01  
4.30  
4.61  
4.95  
1022  
1039  
1056  
1074  
1093  
1112  
1132  
1152  
---  
3.23  
3.43  
3.64  
3.88  
4.14  
4.42  
4.72  
5.04  
---  
1015  
1033  
1052  
1072  
1093  
1114  
1135  
991  
1010  
1031  
1052  
1074  
1096  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).  
95  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FAN PERFORMANCE (cont.)  
8.5 TON HORIZONTAL SUPPLY  
48TC**09  
3 PHASE  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
F i e l d --- S u p p l i e d D r i v e  
Standard Static Option  
Medium Static Option  
2550  
2763  
2975  
3188  
3400  
3613  
3825  
4038  
4250  
497  
524  
551  
580  
609  
638  
668  
698  
728  
0.48  
0.58  
0.70  
0.84  
1.00  
1.17  
1.37  
1.59  
1.83  
579  
602  
626  
651  
677  
703  
730  
758  
786  
0.61  
0.72  
0.86  
1.00  
1.17  
1.35  
1.56  
1.79  
2.04  
651  
671  
693  
716  
739  
763  
788  
813  
839  
0.75  
0.87  
1.01  
1.17  
1.35  
1.54  
1.76  
2.00  
2.26  
717  
735  
754  
775  
797  
819  
842  
866  
890  
0.90  
1.03  
1.18  
1.34  
1.53  
1.73  
1.96  
2.20  
2.47  
777  
794  
812  
831  
851  
871  
893  
915  
938  
1.05  
1.19  
1.35  
1.52  
1.71  
1.93  
2.16  
2.42  
2.70  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
2550  
2763  
2975  
3188  
3400  
3613  
3825  
4038  
4250  
833  
849  
865  
883  
902  
921  
941  
963  
984  
1.21  
1.36  
1.52  
1.70  
1.90  
2.13  
2.37  
2.63  
2.92  
886  
900  
916  
933  
950  
969  
988  
1008  
1029  
1.38  
1.53  
1.70  
1.89  
2.10  
2.33  
2.58  
2.86  
3.15  
936  
950  
964  
980  
996  
1014  
1032  
1051  
1071  
1.56  
1.72  
1.89  
2.09  
2.30  
2.54  
2.80  
3.08  
3.39  
984  
996  
1.74  
1.90  
2.09  
2.29  
2.51  
2.76  
3.02  
3.31  
3.63  
1029  
1041  
1054  
1068  
1083  
1099  
1116  
1133  
1152  
1.93  
2.10  
2.29  
2.50  
2.73  
2.98  
3.25  
3.55  
3.87  
1010  
1025  
1041  
1057  
1075  
1093  
1112  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part no. KR11AK012) and belt (part no. KR29AF055).  
2. Recommend using field---supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).  
48TC**09  
3 PHASE  
8.5 TON VERTICAL SUPPLY  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
2550  
2763  
2975  
3188  
3400  
3613  
3825  
4038  
4250  
526  
557  
588  
621  
653  
687  
720  
754  
788  
0.51  
0.62  
0.75  
0.90  
1.06  
1.25  
1.45  
1.69  
1.94  
600  
627  
655  
684  
714  
744  
775  
807  
839  
0.65  
0.77  
0.91  
1.07  
1.25  
1.45  
1.67  
1.91  
2.17  
666  
690  
716  
743  
770  
798  
827  
856  
886  
0.79  
0.92  
1.08  
1.25  
1.44  
1.65  
1.88  
2.13  
2.41  
727  
749  
772  
797  
822  
849  
876  
904  
932  
0.93  
1.08  
1.24  
1.42  
1.62  
1.84  
2.09  
2.35  
2.64  
783  
804  
825  
848  
872  
897  
922  
949  
976  
1.07  
1.23  
1.40  
1.60  
1.81  
2.04  
2.30  
2.57  
2.88  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
2550  
2763  
2975  
3188  
3400  
3613  
3825  
4038  
4250  
836  
855  
875  
897  
919  
943  
967  
992  
1018  
1.20  
1.37  
1.56  
1.77  
1.99  
2.24  
2.51  
2.80  
3.11  
886  
904  
923  
943  
964  
986  
1010  
1034  
1058  
1.34  
1.52  
1.72  
1.94  
2.18  
2.44  
2.71  
3.02  
3.34  
934  
950  
968  
1.48  
1.67  
1.88  
2.11  
2.36  
2.63  
2.92  
3.24  
3.57  
979  
995  
1.61  
1.82  
2.04  
2.29  
2.55  
2.83  
3.13  
3.46  
---  
1022  
1037  
1053  
1071  
1089  
1108  
1129  
1150  
---  
1.74  
1.97  
2.20  
2.46  
2.73  
3.02  
3.34  
3.68  
---  
1012  
1030  
1049  
1069  
1090  
1112  
---  
987  
1007  
1029  
1051  
1074  
1097  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied motor pulley (part no. KR11HY310), fan pulley (part no. KR11AZ002) and belt (part no. KR29AF054).  
96  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FAN PERFORMANCE (cont.)  
10 TON HORIZONTAL SUPPLY  
48TC**12  
3 PHASE  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
1
F i e l d --- S u p p l i e d D r i v e  
Standard Static Option  
Medium Static Option  
3000  
3250  
3500  
3750  
4000  
4250  
4500  
4750  
5000  
579  
613  
648  
683  
719  
756  
792  
830  
867  
0.70  
0.85  
1.03  
1.23  
1.45  
1.71  
1.99  
2.31  
2.66  
660  
690  
721  
753  
786  
819  
853  
888  
923  
0.89  
1.06  
1.25  
1.47  
1.71  
1.98  
2.28  
2.62  
2.98  
732  
760  
788  
817  
848  
879  
910  
943  
976  
1.09  
1.27  
1.48  
1.71  
1.97  
2.26  
2.57  
2.92  
3.30  
799  
823  
850  
877  
905  
934  
964  
995  
1026  
1.29  
1.49  
1.71  
1.96  
2.23  
2.53  
2.87  
3.23  
3.63  
860  
883  
907  
933  
959  
1.50  
1.71  
1.95  
2.21  
2.50  
2.81  
3.16  
3.54  
3.95  
987  
1015  
1044  
1074  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
3000  
3250  
3500  
3750  
4000  
4250  
4500  
4750  
5000  
917  
938  
961  
1.70  
1.93  
2.18  
2.46  
2.76  
3.09  
3.46  
3.85  
4.28  
970  
991  
1.91  
2.16  
2.42  
2.71  
3.03  
3.38  
3.76  
4.16  
4.61  
1021  
1041  
1062  
1083  
1106  
1130  
1155  
1180  
1207  
2.13  
2.38  
2.66  
2.97  
3.30  
3.66  
4.06  
4.48  
4.94  
1070  
1089  
1108  
1129  
1151  
1174  
1198  
1222  
---  
2.34  
2.61  
2.91  
3.23  
3.58  
3.95  
4.36  
4.80  
---  
1117  
1134  
1153  
1173  
1194  
1216  
1239  
1263  
---  
2.56  
2.85  
3.15  
3.49  
3.85  
4.24  
4.66  
5.12  
---  
1013  
1035  
1059  
1084  
1110  
1137  
1164  
985  
1011  
1037  
1064  
1091  
1120  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied fan pulley (part no. KR11AD912) and belt (part no. KR29AF051).  
2. Recommend using field---supplied motor pulley (part no. KR11HY410).  
48TC**12  
3 PHASE  
10 TON VERTICAL SUPPLY  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
0.2  
0.4  
0.6  
0.8  
1.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Standard Static Option  
Medium Static Option  
3000  
3250  
3500  
3750  
4000  
4250  
4500  
4750  
5000  
616  
655  
695  
736  
777  
818  
860  
902  
944  
0.79  
0.96  
1.17  
1.41  
1.68  
1.98  
2.32  
2.69  
3.11  
689  
724  
760  
797  
834  
873  
912  
951  
991  
0.97  
1.16  
1.38  
1.63  
1.91  
2.23  
2.58  
2.97  
3.40  
757  
788  
821  
855  
889  
925  
962  
999  
1037  
1.16  
1.37  
1.60  
1.86  
2.16  
2.49  
2.85  
3.26  
3.70  
821  
849  
879  
910  
942  
1.36  
1.58  
1.83  
2.10  
2.41  
2.75  
3.13  
3.55  
4.00  
882  
907  
934  
963  
1.57  
1.80  
2.06  
2.35  
2.67  
3.02  
3.41  
3.84  
4.31  
993  
976  
1025  
1057  
1091  
1125  
1010  
1046  
1082  
AVAILABLE EXTERNAL STATIC PRESSURE (in. wg)  
1.4 1.6 1.8  
1.2  
2.0  
CFM  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
RPM  
BHP  
Medium Static Option  
High Static Option  
3000  
3250  
3500  
3750  
4000  
4250  
4500  
4750  
5000  
939  
962  
987  
1014  
1042  
1072  
1103  
1135  
1167  
1.79  
2.03  
2.30  
2.60  
2.93  
3.30  
3.70  
4.14  
4.63  
994  
2.01  
2.26  
2.54  
2.86  
3.20  
3.58  
4.00  
4.45  
4.95  
1047  
1066  
1088  
1111  
1136  
1162  
1190  
1219  
---  
2.24  
2.50  
2.80  
3.12  
3.48  
3.87  
4.29  
4.76  
---  
1098  
1115  
1135  
1157  
1180  
1205  
1232  
1259  
---  
2.47  
2.75  
3.05  
3.39  
3.76  
4.16  
4.60  
5.08  
---  
1147  
1163  
1181  
1202  
1224  
1247  
1273  
---  
2.71  
3.00  
3.32  
3.66  
4.04  
4.46  
4.91  
---  
1015  
1038  
1063  
1090  
1118  
1147  
1177  
1209  
---  
---  
NOTE: For more information, see General Fan Performance Notes on page 87.  
Boldface indicates field---supplied drive is required.  
1. Recommend using field---supplied motor pulley (part no. KR11HY410).  
97  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX III. FAN PERFORMANCE (cont.)  
Pulley Adjustment  
MOTOR PULLEY TURNS OPEN  
MOTOR/DRIVE  
UNIT  
COMBO  
0.0  
0.5  
1.0  
1.5  
2.0  
2.5  
3.0  
3.5  
4.0  
4.5  
5.0  
Standard Static  
854  
825  
795  
766  
736  
707  
678  
648  
619  
589  
560  
Medium Static  
High Static  
1175  
---  
1135  
---  
1094  
---  
1054  
---  
1013  
---  
973  
---  
932  
---  
892  
---  
851  
---  
811  
---  
770  
---  
Standard Static  
Medium Static  
High Static  
854  
825  
795  
766  
736  
707  
973  
1251  
707  
973  
---  
678  
932  
1207  
678  
932  
---  
648  
892  
1164  
648  
892  
---  
619  
851  
1121  
619  
851  
---  
589  
811  
1078  
589  
811  
---  
560  
770  
1035  
560  
770  
---  
1175  
1466  
854  
1135  
1423  
825  
1094  
1380  
795  
1054  
1337  
766  
1013  
1294  
736  
Standard Static  
Medium Static  
High Static  
1175  
---  
1135  
---  
1094  
---  
1054  
---  
1013  
---  
Standard Static  
Medium Static  
High Static  
854  
825  
795  
766  
736  
707  
973  
1251  
973  
1251  
---  
678  
932  
1207  
932  
1207  
---  
648  
892  
1164  
892  
1164  
---  
619  
851  
1121  
851  
1121  
---  
589  
811  
1078  
811  
1078  
---  
560  
770  
1035  
770  
1035  
---  
1175  
1466  
1175  
1466  
---  
1135  
1423  
1135  
1423  
---  
1094  
1380  
1094  
1380  
---  
1054  
1337  
1054  
1337  
---  
1013  
1294  
1013  
1294  
---  
Standard Static  
Medium Static  
High Static  
Standard Static  
Medium Static  
High Static  
1175  
1466  
1687  
1457  
1518  
1788  
747  
1135  
1423  
1649  
1419  
1484  
1757  
721  
1094  
1380  
1610  
1380  
1449  
1725  
695  
1054  
1337  
1572  
1342  
1415  
1694  
670  
1013  
1294  
1533  
1303  
1380  
1662  
644  
973  
1251  
1495  
1265  
1346  
1631  
618  
841  
1006  
626  
813  
961  
715  
961  
1131  
932  
1207  
1457  
1227  
1311  
1600  
592  
819  
986  
604  
788  
936  
690  
936  
1109  
892  
1164  
1418  
1188  
1277  
1568  
566  
798  
967  
583  
764  
912  
665  
912  
1087  
851  
1121  
1380  
1150  
1242  
1537  
541  
776  
948  
561  
739  
887  
640  
887  
1066  
811  
1078  
1341  
1111  
1208  
1505  
515  
755  
928  
540  
715  
863  
616  
863  
1044  
770  
1035  
1303  
1073  
1173  
1474  
489  
733  
909  
518  
690  
838  
591  
838  
1022  
Standard Static  
Medium Static  
High Static  
Standard Static  
Medium Static  
High Static  
949  
927  
906  
884  
863  
1102  
733  
1083  
712  
1063  
690  
1044  
669  
1025  
647  
Standard Static  
Medium Static  
High Static  
936  
911  
887  
862  
838  
1084  
838  
1059  
813  
1035  
789  
1010  
764  
986  
Standard Static  
Medium Static  
High Static  
739  
1084  
1240  
1059  
1218  
1035  
1196  
1010  
1175  
986  
1153  
NOTE: Do not adjust pulley further than 5 turns open.  
--- Fa ct o r y se t t in g s  
98  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX IV. ELECTRICAL DATA  
48TC**04  
3 TONS  
VOLTAGE  
RANGE  
COMP (ea)  
RLA LRA  
OFM (ea)  
IFM  
Max  
AMP Draw  
5.1  
V --- P h --- H z  
Max  
WATTS  
325  
FLA  
1.5  
TYPE  
EFF at Full Load  
FLA  
MIN  
MAX  
WATTS  
1000  
1000  
1000  
1000  
1000  
1000  
2120  
1000  
1000  
2120  
1000  
2120  
2120  
1000  
2120  
2120  
Std Static  
Med Static  
Std Static  
Med Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
70%  
70%  
70%  
70%  
70%  
70%  
80%  
70%  
70%  
80%  
70%  
80%  
80%  
71%  
80%  
80%  
4.9  
4.9  
4.9  
4.9  
4.9  
4.9  
5.2  
4.9  
4.9  
5.2  
2.1  
2.6  
2.6  
1.9  
2.0  
2.0  
2 0 8 --- 1 --- 6 0  
2 3 0 --- 1 --- 6 0  
187  
187  
253  
16.6  
16.6  
79  
79  
5.1  
5.1  
5.1  
5.1  
5.1  
5.5  
5.1  
5.1  
5.5  
2.2  
2.7  
2.7  
2.0  
2.1  
2.1  
253  
253  
325  
1.5  
2 0 8 --- 3 --- 6 0  
2 3 0 --- 3 --- 6 0  
4 6 0 --- 3 --- 6 0  
187  
187  
414  
518  
10.4  
10.4  
5.8  
73  
73  
38  
37  
325  
325  
325  
325  
1.5  
1.5  
0.8  
0.6  
253  
506  
5 7 5 --- 3 --- 6 0  
48TC**05  
V --- P h --- H z  
633  
3.8  
4 TONS  
VOLTAGE  
RANGE  
COMP (ea)  
RLA LRA  
OFM (ea)  
IFM  
Max  
AMP Draw  
5.1  
Max  
WATTS  
1000  
1850  
1000  
1850  
1000  
1000  
2120  
1000  
1000  
2120  
1000  
2120  
2120  
1000  
2120  
2120  
WATTS  
325  
FLA  
1.5  
TYPE  
EFF at Full Load  
FLA  
MIN  
MAX  
Std Static  
Med Static  
Std Static  
Med Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
70%  
78%  
70%  
78%  
70%  
70%  
80%  
70%  
70%  
80%  
70%  
80%  
80%  
71%  
80%  
80%  
4.9  
7.0  
4.9  
7.0  
4.9  
4.9  
5.2  
4.9  
4.9  
5.2  
2.1  
2.6  
2.6  
1.9  
2.0  
2.0  
2 0 8 --- 1 --- 6 0  
2 3 0 --- 1 --- 6 0  
187  
187  
253  
21.8  
21.8  
117  
117  
7.4  
5.1  
7.4  
5.1  
5.1  
5.5  
5.1  
5.1  
5.5  
2.2  
2.7  
2.7  
2.0  
2.1  
2.1  
253  
253  
325  
1.5  
2 0 8 --- 3 --- 6 0  
2 3 0 --- 3 --- 6 0  
4 6 0 --- 3 --- 6 0  
5 7 5 --- 3 --- 6 0  
187  
187  
414  
518  
13.7  
13.7  
6.2  
83  
83  
41  
37  
325  
325  
325  
325  
1.5  
1.5  
0.8  
0.6  
253  
506  
633  
4.8  
99  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX IV. ELECTRICAL DATA (cont.)  
48TC**06  
5 TONS  
VOLTAGE  
RANGE  
COMP (ea)  
RLA LRA  
OFM (ea)  
WATTS FLA  
IFM  
V --- P h --- H z  
Max  
WATTS  
1000  
1850  
1000  
1850  
1000  
2120  
2615  
1000  
2120  
2615  
2120  
2615  
2615  
2120  
3775  
3775  
Max  
AMP Draw  
5.1  
TYPE  
EFF at Full Load  
FLA  
MIN  
MAX  
Std Static  
Med Static  
Std Static  
Med Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
70%  
78%  
70%  
78%  
70%  
80%  
81%  
70%  
80%  
81%  
80%  
81%  
81%  
80%  
81%  
81%  
4.9  
7.0  
4.9  
7.0  
4.9  
5.2  
7.5  
4.9  
5.2  
7.5  
2.6  
3.4  
3.4  
2.0  
2.8  
2.8  
2 0 8 --- 1 --- 6 0  
2 3 0 --- 1 --- 6 0  
187  
187  
253  
26.2  
26.2  
134  
134  
325  
325  
1.5  
1.5  
7.4  
5.1  
7.4  
5.1  
5.5  
7.9  
5.1  
5.5  
7.9  
2.7  
3.6  
3.6  
2.1  
2.9  
2.9  
253  
253  
2 0 8 --- 3 --- 6 0  
2 3 0 --- 3 --- 6 0  
4 6 0 --- 3 --- 6 0  
187  
187  
414  
518  
15.6  
15.6  
7.7  
110  
110  
52  
325  
325  
325  
325  
1.5  
1.5  
0.8  
0.6  
253  
506  
5 7 5 --- 3 --- 6 0  
48TC**07  
V --- P h --- H z  
633  
5.8  
39  
6 TONS  
VOLTAGE  
RANGE  
COMP (ea)  
RLA LRA  
OFM (ea)  
WATTS FLA  
IFM  
Max  
AMP Draw  
5.5  
Max  
WATTS  
2120  
2615  
3775  
2120  
2615  
3775  
2120  
2615  
3775  
2120  
3775  
3775  
TYPE  
EFF at Full Load  
FLA  
MIN  
MAX  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
80%  
81%  
81%  
80%  
81%  
81%  
80%  
81%  
81%  
80%  
81%  
81%  
5.2  
7.5  
10.2  
5.2  
7.5  
10.2  
2.6  
3.4  
4.8  
2.0  
2.8  
2.8  
2 0 8 --- 3 --- 6 0  
2 3 0 --- 3 --- 6 0  
4 6 0 --- 3 --- 6 0  
5 7 5 --- 3 --- 6 0  
187  
187  
414  
518  
253  
19.0  
19.0  
9.7  
12  
12  
62  
50  
325  
325  
325  
325  
1.5  
1.5  
0.8  
0.6  
7.9  
10.7  
5.5  
7.9  
10.7  
2.7  
3.6  
5.0  
2.1  
2.9  
253  
506  
633  
7.4  
2.9  
100  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX IV. ELECTRICAL DATA (cont.)  
48TC**08  
7.5 TONS  
COMP (ea)  
OFM (ea)  
WATTS FLA  
IFM  
VOLTAGE  
RANGE  
EFF at  
Full  
Load  
V --- P h --- H z  
Max  
WATTS  
Max  
AMP Draw  
RLA LRA  
TYPE  
FLA  
MIN  
MAX  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
1448  
2278  
4559  
1448  
2278  
4559  
1448  
2278  
4559  
1379  
3775  
1870  
5.5  
7.9  
15.8  
5.5  
7.9  
15.8  
2.7  
3.6  
7.8  
2.5  
2.9  
5.9  
80%  
81%  
81%  
80%  
81%  
81%  
80%  
81%  
81%  
80%  
81%  
81%  
5.2  
7.5  
15.0  
5.2  
7.5  
15.0  
2.6  
3.4  
7.4  
2.4  
2.8  
5.6  
2 0 8 --- 3 --- 6 0  
2 3 0 --- 3 --- 6 0  
4 6 0 --- 3 --- 6 0  
187  
187  
414  
518  
253  
25.0  
25.0  
12.2  
9.0  
164  
164  
100  
78  
325  
325  
325  
325  
1.5  
1.5  
0.8  
0.6  
253  
506  
633  
5 7 5 --- 3 --- 6 0  
48TC**09  
V --- P h --- H z  
8.5 TONS  
VOLTAGE  
RANGE  
COMP (ea)  
RLA LRA  
OFM (ea)  
WATTS FLA  
IFM  
Max  
WATTS  
Max  
AMP Draw  
TYPE  
EFF at Full Load  
FLA  
MIN  
MAX  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
1448  
2120  
2694  
1448  
2120  
2694  
1448  
2120  
2694  
1379  
1390  
3775  
5.5  
5.5  
10.5  
5.5  
5.5  
10.5  
2.7  
2.7  
4.6  
2.5  
2.1  
2.9  
80%  
80%  
80%  
80%  
80%  
80%  
80%  
80%  
80%  
80%  
80%  
81%  
5.2  
5.2  
10.0  
5.2  
5.2  
10.0  
2.6  
2.6  
4.4  
2.4  
2.0  
2.8  
2 0 8 --- 3 --- 6 0  
2 3 0 --- 3 --- 6 0  
4 6 0 --- 3 --- 6 0  
187  
187  
414  
518  
253  
29.5  
29.5  
14.7  
12.2  
195  
195  
95  
325  
325  
325  
325  
1.5  
1.5  
0.8  
0.6  
253  
506  
633  
5 7 5 --- 3 --- 6 0  
48TC**12  
V --- P h --- H z  
80  
10 TONS  
VOLTAGE  
RANGE  
COMP (ea)  
RLA LRA  
OFM (ea)  
WATTS FLA  
IFM  
Max  
WATTS  
Max  
AMP Draw  
TYPE  
EFF at Full Load  
FLA  
MIN  
MAX  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
Std Static  
Med Static  
High Static  
2120  
3775  
4559  
2120  
3775  
4559  
2120  
3775  
4559  
1390  
3775  
1870  
5.5  
10.5  
15.8  
5.5  
10.5  
15.8  
2.7  
4.6  
7.8  
2.1  
2.9  
80%  
81%  
81%  
80%  
81%  
81%  
80%  
81%  
81%  
80%  
81%  
81%  
5.2  
10.0  
15.0  
5.2  
10.0  
15.0  
2.6  
4.4  
7.4  
2.0  
2.8  
2 0 8 --- 3 --- 6 0  
2 3 0 --- 3 --- 6 0  
4 6 0 --- 3 --- 6 0  
5 7 5 --- 3 --- 6 0  
187  
187  
414  
518  
253  
30.1  
30.1  
16.7  
12.2  
225  
225  
114  
80  
325  
325  
325  
325  
1.5  
1.5  
0.8  
0.6  
253  
506  
633  
5.9  
5.6  
101  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX IV. ELECTRICAL DATA (cont.)  
MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.  
NO C.O. or UNPWRD C.O.  
COMBUSTION POWER  
FAN MOTOR EXHAUST  
NO P.E.  
DISC. SIZE  
FLA LRA  
26 95  
w/ P.E. (pwrd fr/ unit)  
NOM.  
V --- P h --- H z  
IFM  
TYPE  
DISC. SIZE  
FLA  
FLA  
MCA  
MOCP  
MCA  
MOCP  
FLA  
29  
29  
22  
22  
22  
11  
11  
12  
9
LRA  
97  
97  
91  
91  
109  
47  
47  
56  
46  
STD  
MED  
STD  
MED  
HIGH  
STD  
27.2  
27.2  
19.4  
19.4  
19.7  
10.2  
10.2  
10.7  
7.3  
40.0  
40.0  
25.0  
25.0  
30.0  
15.0  
15.0  
15.0  
15.0  
15.0  
15.0  
50.0  
50.0  
30.0  
30.0  
30.0  
15.0  
15.0  
15.0  
15.0  
15.0  
15.0  
60.0  
60.0  
30.0  
40.0  
40.0  
20.0  
20.0  
20.0  
15.0  
15.0  
15.0  
45.0  
50.0  
50.0  
25.0  
25.0  
25.0  
15.0  
20.0  
20.0  
29.1  
29.1  
21.3  
21.3  
21.6  
11.2  
11.2  
11.7  
9.2  
45.0  
45.0  
30.0  
30.0  
30.0  
15.0  
15.0  
15.0  
15.0  
15.0  
15.0  
50.0  
50.0  
30.0  
30.0  
30.0  
15.0  
15.0  
15.0  
15.0  
15.0  
15.0  
60.0  
60.0  
40.0  
40.0  
45.0  
20.0  
20.0  
20.0  
15.0  
15.0  
15.0  
50.0  
50.0  
50.0  
25.0  
25.0  
25.0  
20.0  
20.0  
20.0  
208/230---1---60  
208/230---3---60  
0.48  
1.9  
26  
19  
19  
20  
10  
10  
11  
7
95  
89  
89  
107  
46  
46  
0.48  
0.25  
1.9  
1.0  
MED  
HIGH  
STD  
4 6 0 --- 3 --- 6 0  
55  
44  
MED  
HIGH  
STD  
MED  
STD  
MED  
HIGH  
STD  
7.3  
7.4  
7
7
44  
9.2  
9
46  
5 7 5 --- 3 --- 6 0  
0.24  
0.48  
0.48  
1.9  
1.9  
1.9  
50  
9.3  
10  
35  
35  
25  
25  
25  
12  
12  
12  
11  
11  
11  
40  
42  
27  
28  
30  
13  
14  
15  
12  
13  
13  
32  
34  
34  
16  
17  
18  
14  
15  
15  
52  
33.7  
33.7  
23.5  
23.5  
23.8  
10.7  
10.7  
11.2  
8.5  
32  
32  
23  
23  
23  
10  
10  
11  
8
133  
133  
99  
99  
117  
49  
49  
58  
44  
44  
35.6  
35.6  
25.4  
25.4  
25.7  
11.7  
11.7  
12.2  
10.4  
10.4  
10.5  
41.1  
43.2  
27.8  
28.1  
30.4  
13.5  
14.0  
14.8  
11.7  
11.8  
12.6  
32.4  
34.7  
34.7  
16.5  
17.3  
18.3  
13.8  
14.6  
14.6  
135  
135  
101  
101  
119  
50  
50  
59  
46  
46  
208/230---1---60  
208/230---3---60  
MED  
HIGH  
STD  
4 6 0 --- 3 --- 6 0  
0.25  
1.0  
MED  
HIGH  
STD  
MED  
STD  
MED  
HIGH  
STD  
8.5  
8.6  
8
9
5 7 5 --- 3 --- 6 0  
0.24  
0.48  
0.48  
1.9  
1.9  
1.9  
50  
52  
39.2  
41.3  
25.9  
26.2  
28.5  
12.5  
13.0  
13.8  
9.8  
37  
40  
25  
26  
29  
12  
13  
14  
10  
10  
11  
30  
32  
32  
15  
16  
17  
12  
12  
12  
150  
175  
126  
144  
170  
60  
69  
82  
46  
52  
152  
177  
128  
146  
172  
61  
70  
83  
48  
54  
208/230---1---60  
208/230---3---60  
MED  
HIGH  
STD  
MED  
HIGH  
STD  
4 6 0 --- 3 --- 6 0  
5 7 5 --- 3 --- 6 0  
0.25  
0.24  
0.48  
0.25  
0.24  
1.0  
1.9  
1.9  
1.0  
1.9  
9.9  
10.7  
30.5  
32.8  
32.8  
15.5  
16.3  
17.3  
11.9  
12.7  
12.7  
63  
65  
157  
183  
183  
79  
92  
101  
63  
159  
185  
185  
80  
93  
102  
65  
MED  
HIGH  
STD  
MED  
HIGH  
STD  
208/230---3---60  
4 6 0 --- 3 --- 6 0  
MED  
HIGH  
74  
74  
76  
76  
5 7 5 --- 3 --- 6 0  
See notes on next page.  
102  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX IV. ELECTRICAL DATA (cont.)  
MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.  
NO C.O. or UNPWRD C.O.  
NO C.O. or UNPWRD C.O.  
w/ P.E. (pwrd fr/ unit)  
DISC. SIZE  
COMBUSTION  
FAN MOTOR  
FLA  
POWER  
EXHAUST  
FLA  
NO P.E.  
NOM.  
V --- P h --- H z  
IFM  
TYPE  
DISC. SIZE  
MCA  
MOCP  
MCA  
MOCP  
FLA  
38  
41  
49  
19  
20  
24  
14  
15  
18  
43  
43  
49  
22  
22  
24  
18  
18  
19  
44  
50  
55  
24  
26  
30  
18  
19  
22  
LRA  
191  
228  
254  
113  
132  
145  
89  
104  
118  
222  
233  
276  
108  
114  
136  
91  
FLA  
43  
45  
54  
21  
22  
26  
19  
19  
23  
48  
48  
53  
24  
24  
26  
23  
22  
23  
48  
54  
60  
26  
28  
32  
22  
23  
26  
LRA  
195  
232  
258  
115  
134  
147  
93  
108  
122  
226  
237  
280  
110  
116  
138  
95  
STD  
MED  
HIGH  
STD  
MED  
HIGH  
STD  
39.5  
41.8  
49.3  
19.5  
20.3  
24.3  
14.9  
15.3  
18.1  
45.1  
45.1  
49.9  
22.6  
22.6  
24.4  
18.9  
18.5  
19.3  
45.8  
50.6  
55.6  
25.1  
26.9  
29.9  
18.5  
19.3  
22.1  
60  
60  
60  
30  
30  
30  
20  
20  
25  
60  
60  
60  
30  
30  
30  
30  
30  
30  
60  
60  
80  
30  
40  
45  
30  
30  
30  
43.3  
45.6  
53.1  
21.3  
22.1  
26.1  
18.7  
19.1  
21.9  
48.9  
48.9  
53.7  
24.4  
24.4  
26.2  
22.7  
22.3  
23.1  
49.6  
54.4  
59.4  
26.9  
28.7  
31.7  
22.3  
23.1  
25.9  
60  
60  
60  
30  
30  
30  
25  
25  
30  
60  
60  
80  
30  
30  
30  
30  
30  
30  
60  
80  
80  
40  
45  
45  
30  
30  
30  
208/230---3---60  
4 6 0 --- 3 --- 6 0  
0.48  
0.25  
0.24  
0.48  
0.25  
0.24  
0.48  
0.25  
0.24  
3.8  
1.8  
3.8  
3.8  
1.8  
3.8  
3.8  
1.8  
3.8  
MED  
HIGH  
STD  
5 7 5 --- 3 --- 6 0  
MED  
HIGH  
STD  
MED  
HIGH  
STD  
208/230---3---60  
4 6 0 --- 3 --- 6 0  
MED  
HIGH  
STD  
95  
99  
5 7 5 --- 3 --- 6 0  
106  
263  
306  
315  
133  
155  
159  
95  
110  
267  
310  
319  
135  
157  
161  
99  
MED  
HIGH  
STD  
MED  
HIGH  
STD  
208/230---3---60  
4 6 0 --- 3 --- 6 0  
MED  
HIGH  
106  
120  
110  
124  
5 7 5 --- 3 --- 6 0  
1
Example: Supply voltage is 230-3-60  
Fuse or breaker  
LEGEND:  
CO  
DISC  
FLA  
IFM  
LRA  
MCA  
MOCP  
P E  
AB = 224 v  
BC = 231 v  
AC = 226 v  
--- Convenient outlet  
--- Disconnect  
--- Full load amps  
--- Indoor fan motor  
--- Locked rotor amps  
--- Minimum circuit amps  
--- Maximum over current protection  
--- Po w e r e x h a u st  
(224 + 231 + 226)  
681  
3
Average Voltage =  
3
=
UNPWRD CO --- Unpowered convenient outlet  
NOTES:  
=
227  
Determine maximum deviation from average voltage.  
(AB) 227 – 224 = 3 v  
(BC) 231 – 227 = 4 v  
(AC) 227 – 226 = 1 v  
Maximum deviation is 4 v.  
1. In compliance with NEC requirements for multimotor and  
combination load equipment (refer to NEC Articles 430 and  
440), the overcurrent protective device for the unit shall be  
fuse or HACR breaker. Canadian units may be fuse or circuit  
breaker.  
2. Unbalanced 3-Phase Supply Voltage  
Determine percent of voltage imbalance.  
Never operate a motor where a phase imbalance in supply  
voltage is greater than 2%. Use the following formula to de-  
termine the percentage of voltage imbalance.  
4
% Voltage Imbalance  
= 100 x  
= 1.76%  
227  
max voltage deviation from average voltage  
This amount of phase imbalance is satisfactory as it is below the  
maximum allowable 2%.  
% Voltage Imbalance = 100 x  
average voltage  
IMPORTANT: If the supply voltage phase imbalance is more than  
2%, contact your local electric utility company immediately.  
103  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX V. WIRING DIAGRAM LIST  
Wiring Diagrams  
48TC_A  
SIZE  
VOLTAGE  
CONTROL  
POWER  
208/230---1---60  
208/230---3---60  
460---3---60  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500213.04  
48TM500929.05  
48TM500929.05  
48TM500929.05  
48TM500929.05  
48TM500929.05  
48TM500929.05  
48TM500929.05  
48TM500929.05  
48TM500929.05  
48TM500984.03  
48TM500988.04  
48TM500749.07  
48TM500748.06  
48TM500748.06  
48TM500215.06  
48TM500749.07  
48TM500748.06  
48TM500748.06  
48TM500215.06  
48TM500749.07  
48TM500748.06  
48TM500748.06  
48TM500215.06  
48TM500748.06  
48TM500748.06  
48TM500215.06  
48TM500803.05  
48TM500803.05  
48TM500804.05  
48TM500803.05  
48TM500803.05  
48TM500804.05  
48TM500803.05  
48TM500803.05  
48TM500804.05  
A04  
A05  
A06  
575---3---60  
208/230---1---60  
208/230---3---60  
460---3---60  
575---3---60  
208/230---1---60  
208/230---3---60  
460---3---60  
575---3---60  
208/230---3---60  
460---3---60  
575---3---60  
208/230---3---60  
460---3---60  
575---3---60  
208/230---3---60  
460---3---60  
575---3---60  
208/230---3---60  
460---3---60  
575---3---60  
PremierLink*  
RTU---MP*  
A07  
A08  
A09  
A12  
All  
All  
NOTE: Component arrangement on Control; Legend on Power Schematic  
*
PremierLink and RTU---MP control labels overlay a portion of the base unit control label. The base unit label drawing and the control option  
drawing are required to provide a complete unit control diagram.  
104  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX VI. MOTORMASTER SENSOR LOCATIONS  
C08259  
C08261  
Fig. 85 - 48TC*A04 Outdoor Circuiting  
Fig. 87 - 48TC*A07 Outdoor Circuiting  
C08260  
C08262  
Fig. 86 - 48TC*A05/06 Outdoor Circuiting  
Fig. 88 - 48TC*A08 Outdoor Circuiting  
105  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX VI. (cont.) MOTORMASTER SENSOR LOCATIONS  
C08263  
Fig. 89 - 48TC*A09/12 Outdoor Circuiting  
Catalog No: 48TC---2SM  
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231  
Printed in U.S.A.  
Edition Date: 08/08  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
Replaces: 48TC---1SM  
106  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT START-UP CHECKLIST  
I. PRELIMINARY INFORMATION:  
MODEL NO.:  
SERIAL NO: _____________________________________  
TECHNICIAN: ___________________________________  
BUILDING LOCATION:____________________________  
DATE:  
______________  
II. PRE-START-UP (insert check mark in box as each item is completed):  
j
j
j
j
j
j
j
j
j
j
VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS  
VERIFY THAT FLUE HOOD IS INSTALLED  
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS  
CHECK TO ENSURE NO WIRES ARE TOUCHING REFRIGERANT TUBING OR SHARP EDGES  
CHECK GAS PIPING FOR LEAKS  
CHECK THAT RETURN--AIR FILTER IS CLEAN AND IN PLACE  
VERIFY THAT UNIT INSTALLATION IS LEVEL  
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND VERIFY SETSCREW IS TIGHT  
VERIFY PULLEY ALIGNMENT AND BELT TENSION ARE CORRECT  
III. START-UP  
ELECTRICAL  
SUPPLY VOLTAGE  
COMPRESSOR AMPS  
INDOOR FAN AMPS  
L1-L2  
L1  
L2-L3  
L2  
L3-L1  
L2  
L1  
L2  
L2  
TEMPERATURES  
OUTDOOR-AIR TEMPERATURE  
RETURN-AIR TEMPERATURE  
COOLING SUPPLY AIR  
DB  
DB  
DB  
DB  
WB  
WB  
WB  
GAS HEAT SUPPLY AIR  
PRESSURES  
GAS INLET PRESSURE  
IN. WG  
GAS MANIFOLD PRESSURE  
REFRIGERANT SUCTION  
REFRIGERANT DISCHARGE  
IN. WG (LOW FIRE)  
IN. WG (HI FIRE)  
TEMP _F  
PSIG  
PSIG  
TEMP _F  
j
j
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS  
VERIFY THAT 3--PHASE SCROLL COMPRESSOR IS ROTATING IN CORRECT DIRECTION  
Catalog No: 48TC---2SM  
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231  
Printed in U.S.A.  
Edition Date: 08/08  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
Replaces: 48TC---1SM  
107  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Blender BL2350P User Manual
Black Decker Toaster CTO649 User Manual
BMW Automobile 5 User Manual
Boss Audio Systems Car Stereo System BV6450 User Manual
Bowers Wilkins Speaker ASW600 User Manual
Braun Electric Shaver 320S 4 User Manual
Brother Sewing Machine LS 2125 User Manual
Campbell Hausfeld Air Compressor FP260200 User Manual
Can Am Offroad Vehicle DS650 User Manual
Casio Musical Instrument WK 3300 User Manual