Carrier Heat Pump 50PTH User Manual

AQUAZONE™  
50PTH, PTV, PTD026-072  
Two-Stage Water Source Heat Pumps  
with PURON® Refrigerant (R-410A)  
Installation, Start-Up, and Service Instructions  
Page  
CONTENTS  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33-38  
Operating Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33  
Scroll Compressor Rotation. . . . . . . . . . . . . . . . . . . . . 34  
Unit Start-Up Cooling Mode . . . . . . . . . . . . . . . . . . . . . 34  
Unit Start-Up Heating Mode . . . . . . . . . . . . . . . . . . . . . 34  
Unit Start-Up with WSHP Open Controls . . . . . . . . 36  
Flow Regulation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Flushing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Antifreeze . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37  
Cooling Tower/Boiler Systems . . . . . . . . . . . . . . . . . . 38  
Ground Coupled, Closed Loop and Plateframe  
Heat Exchanger Well Systems . . . . . . . . . . . . . . . . 38  
OPERATION. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38-42  
Power Up Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39  
Units with Aquazone™ Complete C Control . . . . . 39  
Units with Aquazone Deluxe D Control . . . . . . . . . . 39  
Units with WSHP Open Multiple Protocol. . . . . . . . 39  
Page  
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . .1,2  
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-29  
Step 1 — Check Jobsite. . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Step 2 — Check Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
• STORAGE  
• PROTECTION  
• INSPECT UNIT  
Step 3 — Locate Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
• FIELD CONVERSION OF DISCHARGE AIR  
Step 4 — Mount the Unit . . . . . . . . . . . . . . . . . . . . . . . . . 9  
• HORIZONTAL UNIT  
• VERTICAL UNITS  
Step 5 — Check Duct System . . . . . . . . . . . . . . . . . . . . 9  
• SOUND ATTENUATION  
• EXISTING DUCT SYSTEM  
COMPLETE C AND DELUXE D BOARD  
Step 6 — Install Condensate Drain . . . . . . . . . . . . . . . 9  
• HORIZONTAL UNIT  
SYSTEM TEST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42,43  
Test Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42  
WSHP Open Test Mode. . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Retry Mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43  
Aquazone Deluxe D Control LED Indicators . . . . . 43  
• VERTICAL UNITS  
• VENTING  
Step 7 — Pipe Connections . . . . . . . . . . . . . . . . . . . . . 10  
WATER LOOP APPLICATIONS  
• GROUND-WATER APPLICATIONS  
• GROUND-LOOP APPLICATIONS  
• INSTALLATION OF SUPPLY AND RETURN HOSE  
KIT  
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .44,45  
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Water Coil. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Condensate Drain Pans . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Refrigerant System. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Compressor. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Fan Motors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Condensate Drain Cleaning . . . . . . . . . . . . . . . . . . . . . 44  
Air Coil Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Condenser Cleaning . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
Checking System Charge . . . . . . . . . . . . . . . . . . . . . . . 45  
Refrigerant Charging. . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Air Coil Fan Motor Removal . . . . . . . . . . . . . . . . . . . . . 45  
Replacing the WSHP Open Controller’s  
Step 8 — Wire Field Power Supply . . . . . . . . . . . . . . 12  
• POWER CONNECTION  
• SUPPLY VOLTAGE  
• 208-VOLT OPERATION  
• 460-VOLT OPERATION  
• WSHP OPEN WIRING  
Step 9 — Wire Field Controls. . . . . . . . . . . . . . . . . . . . 25  
• THERMOSTAT CONNECTIONS  
WATER FREEZE PROTECTION  
• AIR COIL FREEZE PROTECTION  
• ACCESSORY CONNECTIONS  
WATER SOLENOID VALVES  
Step 10 — Operate ECM Interface Board . . . . . . . . 27  
• STANDALONE — NO DDC CONTROLS  
• WSHP OPEN CONTROLS  
Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . 45-53  
Thermistor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Control Sensors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
WSHP Open Controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Thermostatic Expansion Valves . . . . . . . . . . . . . . . . . . 46  
Stopped or Malfunctioned ECM Motor. . . . . . . . . . . . 50  
Moisture Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51  
PRE-START-UP. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .29,30  
System Checkout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29  
FIELD SELECTABLE INPUTS. . . . . . . . . . . . . . . . . 30-33  
Complete C Control Jumper Settings. . . . . . . . . . . . 30  
Deluxe D Control Jumper Settings . . . . . . . . . . . . . . 30  
Complete C Control DIP Switches. . . . . . . . . . . . . . . 30  
Deluxe D Control DIP Switches. . . . . . . . . . . . . . . . . . 30  
Units with Modulating Hot Water Reheat  
(HWR) Option. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
• STANDALONE — NO DDC CONTROLS  
• WSHP OPEN CONTROLS  
APPENDIX A — WSHP OPEN SCREEN  
CONFIGURATION . . . . . . . . . . . . . . . . . . . . . . . . . . 54-59  
50PTH,PTV,PTD START-UP  
CHECKLIST . . . . . . . . . . . . . . . . . . . . . . . . . . CL-1, CL-2  
IMPORTANT: Read the entire instruction manual before  
starting installation.  
SAFETY CONSIDERATIONS  
Installation and servicing of air-conditioning equipment can  
be hazardous due to system pressure and electrical  
• HWR APPLICATION CONSIDERATIONS  
• HWR COMPONENT FUNCTIONS  
Deluxe D Control Accessory  
Relay Configurations. . . . . . . . . . . . . . . . . . . . . . . . . 32  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53500079-01 Printed in U.S.A. Form 50PT-4SI Pg 1 7-10 Replaces: 50PT-3SI  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. Provide an unobstructed path to the unit within the closet  
or mechanical room. Space should be sufficient to allow  
removal of unit if necessary.  
9. Provide ready access to water valves and fittings, and  
screwdriver access to unit side panels, discharge collar,  
and all electrical connections.  
10. Where access to side panels is limited, pre-removal of the  
control box side mounting screws may be necessary for  
future servicing.  
INSPECT UNIT — To prepare the unit for installation, com-  
plete the procedures listed below:  
1. Compare the electrical data on the unit nameplate with  
ordering and shipping information to verify that the  
correct unit has been shipped.  
2. Do not remove the packaging until the unit is ready for  
installation.  
3. Verify that the unit’s refrigerant tubing is free of kinks or  
dents, and that it does not touch other unit components.  
STORAGE — If the equipment is not needed immediately at  
the jobsite, it should be left in its shipping carton and stored in a  
clean, dry area of the building or in a warehouse. Units must be  
stored in an upright position at all times. If carton stacking is  
necessary, stack units a maximum of 3 high. Do not remove  
any equipment from its shipping package until it is needed for  
installation.  
PROTECTION — Once the units are properly positioned on  
the jobsite, cover them with either a shipping carton, vinyl film,  
or an equivalent protective covering. Cap open ends of pipes  
stored on the jobsite. This precaution is especially important in  
areas where painting, plastering, or spraying of fireproof mate-  
rial, etc. is not yet complete. Foreign material that accumulates  
within the units can prevent proper start-up and necessitate  
costly clean-up operations.  
4. Inspect all electrical connections. Be sure connections are  
clean and tight at their terminations.  
5. Loosen compressor bolts until the compressor rides freely  
on springs. Remove shipping restraints.  
1
6. Remove the four / in. shipping bolts from compressor  
4
support plate (two bolts on each side) to maximize vibra-  
tion and sound alternation.  
CAUTION  
Failure to remove shipping brackets from spring-mounted  
compressors will cause excessive noise and could cause  
component failure due to added vibration.  
7. Remove any blower support cardboard from inlet of the  
blower.  
8. Locate and verify any accessory kit located in compressor  
and/or blower section.  
9. Remove any access panel screws that may be difficult to  
remove once unit is installed.  
Before installing any of the system components, be sure to  
examine each pipe, fitting, and valve, and remove any dirt or  
foreign material found in or on these components.  
CAUTION  
DO NOT store or install units in corrosive environments or  
in locations subject to temperature or humidity extremes  
(e.g., attics, garages, rooftops, etc.). Corrosive conditions  
and high temperature or humidity can significantly reduce  
performance, reliability, and service life. Always move  
units in an upright position. Tilting units on their sides may  
cause equipment damage.  
Table 1 — Physical Data — 50PTH, PTV, PTD026-072 Units  
UNIT 50PTH, PTV, PTD  
COMPRESSOR (1 each)  
FACTORY CHARGE R-410A (oz)  
026  
038  
049  
Two-Stage, Scroll  
81  
064  
072  
58  
78  
144  
156  
ECM FAN MOTOR AND BLOWER  
Fan Motor Type  
VAR  
1
VAR  
1
VAR  
1
11x10  
VAR  
1
11x10  
VAR  
1
11x10  
Fan Motor (Hp)  
/
/
2
2
Blower Wheel Size (D x W) (in.)  
9 x 7  
11 x 10  
COAXIAL COIL VOLUME (gal.)  
WATER CONNECTION SIZE (FPT) (in.)  
HWG CONNECTION SIZE (FPT) (in.)  
.76  
3
.92  
3
1.24  
1.56  
1.56  
/
/
/
/
1
1
1
1
1
1
4
2
4
2
1
1
/
2
/
/
2
2
VERTICAL  
Air Coil  
Dimensions (H x W) (in.)  
Filter Standard — 1-in. Throwaway  
(Qty — Size) (in.)  
Weight (lb)  
28 x 20  
28 x 25  
32 x 25  
36 x 25  
36 x 25  
1 — 16 x 30  
1 — 20 x 30  
1 — 16 x 30  
1 — 20 x 30  
1 — 28 x 24  
1 — 28 x 30  
2 — 16 x 30  
Operating  
Packaged  
266  
276  
327  
337  
416  
426  
443  
453  
443  
453  
HORIZONTAL  
Air Coil  
Dimensions (H x W) (in.)  
Filter Standard — 1-in. Throwaway  
(Qty — Size) (in.)  
Weight (lb)  
18 x 31  
20 x 25  
20 x 40  
20 x 45  
20 x 45  
1 — 12 x 20  
1 — 20 x 24  
1 — 18 x 20  
1 — 20 x 24  
2 — 18 x 18  
2 — 20 x 24  
2 — 20 x 24  
Operating  
Packaged  
266  
276  
327  
337  
416  
426  
443  
453  
443  
453  
LEGEND  
ECM  
HWG — Hot Water Generator  
VAR Variable Speed  
Electronically Commutated Motor  
NOTE: All units have spring compressor mountings, TXV (thermostatic expan-  
1
3
sion valve) expansion devices, and  
/
2
and / -in. electrical knockouts.  
4
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
ASP  
BSP  
CAP  
CSP  
FPT  
Alternate Service Panel  
Blower Service Panel  
Control Access Panel  
Compressor Service Panel  
Female Pipe Thread  
2
Service  
CSP  
Front  
2
Service Access  
HWG — Hot Water Generator  
HWR Hot Water Reheat  
Access  
Front  
2
Service Access  
Left Return  
Power Supply  
3/4” Knockout  
2
Service Access  
Right Return  
1/2”  
Knockout  
1.6”  
CSP  
ASP  
3.25”  
3.25”  
Low Voltage  
1/2” Knockout  
L
G
K
F
E
CAP  
J
H
H
Left  
Discharge  
Right  
Discharge  
D
A
Condensate  
3/4” FPT  
Condensate  
3/4” FPT  
Back  
Discharge  
Back  
Discharge  
P
R
Size  
P
Q
BSP  
Blower  
Outlet  
BSP  
O
Q
Y
Z
C
C
Blower  
Outlet  
O
, 072  
R
A
A
X
Y Configuration - Left Return/Back Discharge  
P Configuration - Right Return/Back Discharge - Air Coil Opening  
P
M
O
N
P
Blower  
Outlet  
BSP  
Left  
View  
ASP  
CSP  
BSP  
Right  
View  
Blower  
Outlet  
O
N
Front  
M
W Configuration - Left Return/Right Discharge - Air Coil Opening  
N Configuration - Right Return/Left Discharge - Air Coil Opening  
Air Coil  
1.1”  
V
Air Coil  
S
U
S
Right  
View  
CSP  
ASP  
T
T
C
C
Front  
Front  
B
B
W Configuration - Left Return/Right Discharge - Air Coil Opening  
N Configuration - Right Return/Left Discharge - Air Coil Opening  
WATER  
CONNEC-  
TIONS (in.)  
- UNITS  
DISCHARGE CONNECTIONS (in.) RETURN CONNECTION  
OVERALL CABINET  
WATER CONNECTIONS (in.)  
(in.)  
ELECTRICAL  
KNOCKOUTS (in.)  
DUCT FLANGE INSTALLED  
USING AIR COIL  
OPENING (in.)  
(0.10 in.)  
WITH HWR  
50PTH  
UNIT  
J
2
K
2
L
4
1
1
3
1
2
3
F
4
5
1
2
/ -in. / -in. / -in.  
Loop  
Water  
FPT  
HWG  
FPT  
(in.)  
M
O
P
Q
S
T
Cond Cond Cond  
A
B
C
(LH  
rtn)  
N
Supply Supply (RH  
Height Width rtn)  
R
Return Return  
Width Height  
U
V
Width Depth Height  
G
H
D
In  
E
Out  
Low  
Ext Power  
Loop Loop  
in D out E  
(in.)  
HWG HWG Cond-  
Voltage Pump Supply  
In  
Out ensate  
3
1
026  
038  
049  
22.4  
25.4  
25.4  
62.2  
71.2  
76.2  
81.2  
19.3  
21.3  
21.3  
21.3  
2.1 10.0 13.9 16.9  
3.4 10.8 14.6 18.9  
3.4 10.8 15.6 18.9  
3.4 10.8 15.6 18.9  
3.5  
3.4  
3.4  
3.4  
/
/
/
2.1 10.0  
3.6  
6.1  
6.1  
6.1  
6.1  
8.6  
8.6  
8.6  
8.6  
3.6 2.0 12.5  
3.1 1.2 19.0  
3.1 1.2 19.0  
3.1 1.2 19.0  
15.5 3.6 2.0 33.8  
17.5 3.1 1.0 34.8  
17.5 3.1 1.0 39.8  
17.5 3.1 1.0 44.8  
16.2 2.3 1.5  
18.2 3.1 1.5  
18.2 3.1 1.5  
18.2 3.1 1.5  
4
2
2
2
2
3
1
/
5.96 13.13 3.4  
5.96 13.13 3.6  
5.96 13.13 3.6  
4
1
1
1
/
1
064,072 25.4  
/
NOTES:  
1. Condensate connection is stainless steel  
AIRFLOW CONFIGURATION  
3
/
in. female pipe thread (FPT).  
4
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without  
CODE  
RETURN  
Right  
Right  
Left  
DISCHARGE  
Left  
additional support.  
N
P
3. Discharge flange is factory-installed.  
4. Hanger kit is factory-installed.  
5. Shaded areas are recommended service areas, not required.  
6. Discharge can be modified in field. Return cannot be modified.  
Back  
W
Y
Right  
Left  
Back  
Fig. 1 — 50PTH026-072 Dimensional Data  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
3/8” threaded rods  
(by others)  
FilterAccess  
Return Air  
(Ductwork  
not shown)  
Thermostat  
Wiring  
Field-supplied transition to  
minimize pressure loss  
Balancing Valve (field-  
installed accessory)  
Power Wiring  
Stainless steel  
braid hose  
Supply Air  
with integral  
“J” swivel  
Low Pressure Drop Water  
Control Valve (optional)  
(field-installed accessory)  
Unit Power  
Building  
Loop  
Flexible  
Connection  
Insulated supply duct with  
at least one 90 degree elbow  
to reduce air noise  
Unit Power  
Disconnect  
(by others)  
Water Out  
Water In  
Field-Supplied  
Electric Heat  
(if applicable)  
(field-supplied)  
Ball Valve with optional  
Unit Hanger  
integral P/Tplug (typical for supply  
(field-installed  
accessory)  
(factory-  
Aux Electric  
and return piping) (field-installed accessory)  
supplied)  
Heat Disconnect  
3/8” Threaded  
Rod (by others)  
Vibration Isolator  
(white-compressor end  
and red-blower end)  
Washer  
(by others)  
Double Hex Nuts  
(by others)  
Integral hanger support-  
pre-attached in factory  
UNIT HANGER ISOLATION DETAIL  
Fig. 2 — Typical Installation — 50PTH Unit  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
Field-Installed  
ASP  
BSP  
CAP  
CSP  
FPT  
HV  
Alternate Service Panel  
Blower Service Panel  
Control Access Panel  
Compressor Service Panel  
Female Pipe Thread  
High Voltage  
Discharge Flange  
(shipped loose inside  
blower section)  
Access Panels  
Filter Bracket  
HWG — Hot Water Generator  
HWR  
LV  
Hot Water Reheat  
Low Voltage  
Air Coil  
B
P
N
P
ASP  
ASP  
N
BSP  
CAP  
O
A
O
Q
2ʼ Service Access  
CSP  
M
Air Coil Side  
Air Coil Side  
K - Configuration - Right Return  
/Top Discharge  
J - Configuration - Left Return  
/Top Discharge  
(Top View)  
(Top View)  
2ʼ Service Access  
Isometric View  
S
R
S
R
1.00”  
U
C
U
Air Coil  
Air Coil  
T
T
1.68”  
C
Condensate  
Power Supply  
3/4” FPT  
3/4”  
HV Knockout  
CAP  
1.63”  
1/2”  
Knockout  
1.18”  
CSP  
Low Voltage  
1/2”  
ASP  
G
LV Knockout  
F
E
CSP  
L
K
Back  
Back  
Front  
Front  
J
H
D
K - Configuration - Right Return -  
Air Coil Opening  
J - Configuration - Left Return -  
Air Coil Opening  
Front View  
(Right Side View)  
(Left Side View)  
WATER  
CONNEC-  
DISCHARGE CONNECTIONS (in.)  
DUCT FLANGE INSTALLED  
(0.10 in.)  
RETURN CONNECTION  
USING AIR COIL OPENING  
(in.)  
OVERALL CABINET  
(in.)  
ELECTRICAL  
KNOCKOUTS (in.)  
WATER CONNECTIONS (in.)  
TIONS (in.)  
- UNITS  
WITH HWR  
50PTV  
UNIT  
J
K
L
1
1
3
1
2
3
F
4
5
1
2
/ -in.  
2
/ -in.  
2
/ -in.  
4
Loop  
Water  
FPT  
HWG  
FPT  
(in.)  
M
O
P
Q
S
T
Cond Cond Cond  
A
B
C
(LH  
rtn)  
N
Supply Supply (RH  
Width Depth rtn)  
R
Return Return  
Depth Height  
U
Width Depth Height  
G
H
D
In  
E
Out  
Low  
Ext  
Power  
Loop Loop  
in D out E  
(in.)  
HWG HWG Cond-  
Voltage Pump Supply  
In  
Out ensate  
3
1
026  
038  
049  
22.4  
25.4  
25.4  
25.4  
25.6  
30.6  
30.6  
30.6  
48.5  
50.5  
54.5  
58.5  
2.1  
3.4  
3.4  
3.4  
10.0 13.9 16.9  
10.8 15.6 18.9  
10.8 15.6 18.9  
10.8 15.6 18.9  
7.8  
7.8  
7.8  
7.8  
/
/
/
2
2.1 10.0  
5.96 13.13  
5.96 13.13  
5.96 13.13  
3.6  
3.6  
3.6  
3.6  
6.1  
6.1  
6.1  
6.1  
8.6  
8.6  
8.6  
8.6  
7.2  
6.4  
6.4  
6.4  
5.8  
6.3  
6.3  
6.3  
14.0  
18.0  
18.0  
18.0  
14.0  
18.0  
18.0  
18.0  
4.9 2.2  
5.3 2.2  
5.3 2.2  
5.3 2.2  
21.1  
26.1  
26.1  
26.1  
27.2  
27.2  
31.2  
35.2  
1.0  
1.0  
1.0  
1.0  
4
3
1
1
1
/
4
2
1
1
/
2
064,  
072  
/
2
NOTES:  
AIRFLOW CONFIGURATION  
3
1. Condensate connection is stainless steel  
/
in. female pipe thread (FPT).  
4
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without  
additional support.  
3. Discharge flange is field-installed.  
4. Shaded areas are recommended service areas, not required.  
CODE  
RETURN  
Left  
DISCHARGE  
J
Top  
Top  
K
Right  
Fig. 3 — 50PTV Dimensional Data  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
ASP  
BSP  
CAP  
CSP  
FPT  
Alternate Service Panel  
Blower Service Panel  
Control Access Panel  
Compressor Service Panel  
Female Pipe Thread  
HWG — Hot Water Generator  
HWR  
Hot Water Reheat  
WATER  
CONNEC-  
TIONS (in.)  
DISCHARGE CONNECTIONS (in.)  
DUCT FLANGE INSTALLED  
(0.10 in.)  
OVERALL CABINET  
(in.)  
ELECTRICAL  
KNOCKOUTS (in.)  
RETURN CONNECTION (in.)  
USING AIR COIL OPENING  
WATER CONNECTIONS (in.)  
- UNITS  
WITH HWR  
50PTD  
UNIT  
J
2
Cond  
K
L
4
Cond  
1
1
3
/ -in.  
1
2
3
F
4
5
1
2
/ -in.  
/ -in.  
2
Loop  
HWG  
M
O
P
Q
S
T
Cond  
A
B
C
Water  
FPT  
FPT  
(in.)  
(LH  
rtn)  
N
Supply Supply (RH  
Width Depth rtn)  
R
Return Return  
Depth Height  
U
Width Depth Height  
G
H
D
E
Low  
Ext  
Power  
Loop Loop  
in D out E  
(in.)  
HWG HWG Cond-  
In Out  
Voltage Pump Supply  
In  
Out ensate  
3
1
026  
038  
049  
22.4  
25.4  
25.4  
25.6  
30.6  
30.6  
30.6  
52.5  
54.5  
58.5  
62.5  
2.1 10.0 13.9 16.9  
3.4 10.8 15.6 18.9  
3.4 10.8 15.6 18.9  
3.4 10.8 15.6 18.9  
3.6  
3.6  
3.6  
3.6  
/
/
2.1 10.0  
5.96 13.13  
5.96 13.13  
5.96 13.13  
3.6  
3.6  
3.6  
3.6  
6.1  
6.1  
6.1  
6.1  
8.6  
8.6  
8.6  
8.6  
6.7 8.4  
7.2 9.0  
7.2 9.0  
7.2 9.0  
10.1  
13.4  
13.4  
13.4  
9.1  
12.9  
12.9  
12.9  
10.8 2.2  
10.4 2.2  
10.4 2.2  
10.4 2.2  
21.1  
26.1  
26.1  
26.1  
27.2  
27.2  
31.4  
35.2  
1.0  
1.0  
1.0  
1.0  
4
4
2
2
2
2
3
1
/
/
1
1
1
/
1
064,072 25.4  
/
NOTES:  
AIRFLOW CONFIGURATION  
3
1. Condensate connection is stainless steel  
/
4
in. female pipe thread (FPT).  
2. Unit shipped with top and bottom filter rack and is not suitable for duct connection without  
additional support.  
3. Downflow unit does not have discharge flange, and is rated for zero clearance installation.  
4. Shaded areas are recommended service areas, not required.  
CODE  
RETURN  
Left  
DISCHARGE  
J
Bottom  
Bottom  
K
Right  
Fig. 4 — 50PTD Dimensional Data  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Provide adequate clearance for filter replacement and  
drain pan cleaning. Do not block filter access with pip-  
ing, conduit or other materials. Refer to Fig. 1, 3, and 4  
for dimensional data.  
• Provide access for fan and fan motor maintenance and  
for servicing the compressor and coils without removing  
the unit.  
• Provide an unobstructed path to the unit within the closet  
or mechanical room. Space should be sufficient to allow  
removal of the unit, if necessary.  
• In limited side access installations, pre-removal of the  
control box side mounting screws will allow control box  
removal for future servicing.  
Supply Air  
Building  
Loop  
Flexible  
Connection  
Water  
Out  
Water  
In  
Balancing Valve  
(field-installed  
accessory)  
Stainless steel  
braid hose  
with integral  
“J” swivel  
(field-installed  
accessory)  
Low Pressure  
Drop Water  
Control Valve  
(optional)  
Power  
• Provide access to water valves and fittings and screw-  
driver access to the unit side panels, discharge collar and  
all electrical connections.  
Thermostat  
Wiring  
(field-installed  
accessory)  
Ball Valve with optional  
NOTE: Correct placement of the horizontal unit can play an  
important part in minimizing sound problems. Since duct-  
work is normally applied to these units, the unit can be  
placed so that the principal sound emission is outside the oc-  
cupied space in sound-critical applications. A fire damper  
may be required by the local code if a fire wall is penetrated.  
integral P/T plug  
Compressor  
Access Panel  
(typical for supply and  
return piping) (field-Installed  
accessory)  
NOTE: Ball valve with integral pressure temperature plug recommended.  
Fig. 5 — Typical Vertical Installation — 50PTV Unit  
FIELD CONVERSION OF DISCHARGE AIR — The dis-  
charge air of the 50PTH horizontal units can be converted  
between side and back discharge in the field. The conversion  
process is the same for right and left return configurations. See  
Fig. 7 and 8.  
NOTE: It is not possible to convert return air between left or  
right return models in the field due to refrigerant piping  
changes.  
Building  
Loop  
Flexible  
Connection  
Water  
Out  
Water  
In  
Stainless  
steel  
braid hose  
with  
Balancing Valve  
(field-installed  
accessory)  
integral ”J”  
swivel(field-  
installed  
accessory)  
Water  
Connection End  
Low Pressure  
Drop Water  
Control Valve  
(optional)  
Return Air  
Power  
Thermostat  
(field-installed  
accessory)  
Wiring  
Supply  
Duct  
Compressor  
Ball Valve with  
optional integral  
Access Panel  
Flexible  
P/T plug (typical for  
supply and return  
piping)(field-installed  
accessory)  
Connection  
Side Discharge  
Water  
Connection End  
Supply Air  
NOTE: Ball valve with integral pressure temperature plug recommended.  
Return Air  
Drain  
Fig. 6 — Typical Downflow Installation —  
50PTD Unit  
Step 3 — Locate Unit — The following guidelines  
should be considered when choosing a location for a WSHP:  
• Units are for indoor use only.  
Back Discharge  
Discharge Air  
• Locate in areas where ambient temperatures are between  
39 F and 102 F and relative humidity is no greater than  
75%.  
• Provide sufficient space for water, electrical and duct  
connections.  
• Locate unit in an area that allows easy access and removal  
of filter and access panels.  
• Allow enough space for service personnel to perform  
maintenance.  
Fig. 7 — Conversion Right Return,  
Side Discharge to Back Discharge  
Preparation — The unit should be on the ground in a well lit  
area. Hung units should be taken down to ground level before  
converting.  
Side to Back Discharge Conversion  
1. Remove screws to free the top and discharge panels. Set  
screws aside for later use. See Fig. 8.  
• Return air must be able to freely enter the space if unit needs  
to be installed in a confined area such as a closet.  
2. Remove the access panel and set aside.  
• Install the unit on a piece of rubber, neoprene or other  
mounting pad material for sound isolation. The pad  
3. Lift the discharge panel from side of unit and rotate it to  
back using care not to damage blower wiring.  
4. Check blower wire routing and connections for undue  
tension or contact with sheet metal edges. Re-route if  
necessary.  
3
1
should be at least / in. [10 mm] to / in. [13 mm] in  
8
2
thickness. Extend the pad beyond all four edges of the  
unit.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. Check refrigerant tubing for contact with other compo-  
nents. Adjust if necessary.  
6. Reinstall top panel using screws set aside in Step 1.  
NOTE: Location for some screws at bottom of discharge  
panel may have to be changed.  
7. Manually spin fan wheel to check for obstructions.  
Adjust for any obstruction found.  
8. Replace access panel.  
Remove Screws  
Water  
Connection End  
Return Air  
Fig. 9 — 50PTV Units Mounted With  
Vibration Absorption Pad  
Side Discharge  
Water  
Connection End  
Step 5 — Check Duct System — Size the duct sys-  
tem to handle the design airflow quietly.  
Rotate  
Return Air  
NOTE: Depending on the unit, the fan wheel may have a ship-  
ping support installed at the factory. This must be removed  
before operating unit.  
SOUND ATTENUATION — To eliminate the transfer of  
vibration to the duct system, a flexible connector is recom-  
mended for both discharge and return air duct connections on  
metal duct systems. The supply and return plenums should in-  
clude internal duct liner of fiberglass or be made of duct board  
construction to maximize sound attenuation of the blower.  
Installing the WSHP unit to uninsulated ductwork in an uncon-  
ditioned space is not recommended since it will sweat and  
adversely affect the unit’s performance.  
Move to Side  
Replace Screws  
Water  
Connection End  
To reduce air noise, at least one 90-degree elbow could be  
included in the supply and return air ducts, provided system  
performance is not adversely impacted. The blower speed can  
also be changed in the field to reduce air noise or excessive air-  
flow, provided system performance is not adversely impacted.  
Return Air  
Drain  
EXISTING DUCT SYSTEM — If the unit is connected to  
existing ductwork, consider the following:  
Verify that the existing ducts have the proper capacity to  
handle the unit airflow. If the ductwork is too small, install  
larger ductwork.  
Discharge Air  
Back Discharge  
Fig. 8 — Conversion Left Return,  
Side Discharge to Back Discharge  
• Check existing ductwork for leaks and repair as necessary.  
NOTE: Local codes may require ventilation air to enter the  
space for proper indoor air quality. Hard-duct ventilation  
may be required for the ventilating air supply. If hard  
ducted ventilation is not required, be sure that a proper air  
path is provided for ventilation air to unit to meet ventila-  
tion requirement of the space.  
Back to Side Discharge Conversion — Follow instructions  
above for Side to Back Discharge Conversion, noting the  
panels would be reversed.  
Step 4 — Mount the Unit  
HORIZONTAL UNIT (50PTH) — Horizontal units should  
be mounted using the factory-installed hangers. Proper attach-  
ment of hanging rods to building structure is critical for safety.  
See Fig. 1. Rod attachments must be able to support the weight  
of the unit. See Table 1 for unit operating weights.  
VERTICAL UNITS (50PTV,PTD) — Vertical and downflow  
units are available in left or right return air configurations. See  
Fig. 3 and 4. Mount the unit (except 50PTD) on a vibration  
absorption pad slightly larger than the entire base to minimize  
vibration transmission. It is not necessary to mount the unit on  
the floor. See Fig. 9.  
Step 6 — Install Condensate Drain  
HORIZONTAL UNIT (50PTH) — Slope the unit toward the  
1
drain at / in. See Fig. 10. If it is not possible to meet the re-  
4
quired pitch, install a condensate at the unit to pump conden-  
sate to building drain.  
Horizontal units are not internally trapped, therefore an ex-  
ternal trap is necessary. Install each unit with its own individual  
trap and means to flush or blow out the condensate drain line.  
Do not install units with a common trap or vent. See Fig. 11 for  
typical condensate connections.  
NOTE: Never use a pipe size smaller than the connection.  
NOTE: Some codes require the use of a secondary drain pan  
under vertical units. Check local codes for more information.  
VERTICAL UNITS (50PTV,PTD) — Each unit uses a con-  
densate hose inside all cabinets as a trapping loop, therefore an  
external trap is not necessary. See Fig. 12.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Each unit must be installed with its own individual vent and  
means to flush or blow out the condensate drain line. Do not in-  
stall units with a common trap or vent.  
• Be sure to support the line where anticipated sagging from  
the condensate or when “double trapping” may occur.  
• If condensate pump is present on unit, be sure drain connec-  
tions have a check valve to prevent back flow of condensate  
into other units.  
Step 7 — Pipe Connections — Depending on the  
application, there are 3 types of WSHP piping systems to  
choose from: water loop, ground-water and ground loop. Refer  
to Piping Section of Carrier System Design Manual for addi-  
tional information.  
1/4Pitch for  
Drainage  
All WSHP units use low temperature soldered female pipe  
thread fittings for water connections to prevent annealing and  
out-of-round leak problems which are typically associated with  
high temperature brazed connections. Refer to Table 1 for con-  
nection sizes. When making piping connections, consider the  
following:  
• Use a backup wrench when making screw connections to  
unit to prevent internal damage to piping.  
Pitch Toward  
Drain  
• Insulation may be required on piping to avoid condensation  
in the case where fluid in loop piping operates at tempera-  
tures below dew point of adjacent air.  
Drain Connection  
Fig. 10 — Horizontal Unit Pitch  
• Piping systems that contain steel pipes or fittings may be  
subject to galvanic corrosion. Dielectric fittings may be  
used to isolate the steel parts of the system to avoid galvanic  
corrosion.  
WATER LOOP APPLICATIONS — Water loop applications  
usually include a number of units plumbed to a common pip-  
ing system. Maintenance to any of these units can introduce air  
into the piping system. Therefore, air elimination equipment  
comprises a major portion of the mechanical room plumbing.  
The flow rate is usually set between 2.25 and 3.5 gpm per  
ton of cooling capacity. For proper maintenance and servicing,  
pressure-temperature (P/T) ports are necessary for temperature  
and flow verification.  
Cooling tower/boiler systems typically utilize a common  
loop maintained at 60 to 95 F. The use of a closed circuit evap-  
orative cooling tower with a secondary heat exchange between  
the tower and the water loop is recommended. If an open type  
cooling tower is used continuously, chemical treatment and fil-  
tering will be necessary.  
NOTE: Trap should be deep enough to offset maximum unit static  
difference. A 4-in. trap is recommended.  
In addition to complying with any applicable codes, consid-  
er the following for system piping:  
Fig. 11 — Trap Condensate Drain  
• Piping systems using water temperatures below 50 F  
3/4Copper FPT/PVC  
3/4PVC  
1
require / -in. closed cell insulation on all piping surfaces to  
2
Vent  
eliminate condensation.  
1/2”  
• Avoid all plastic to metal threaded fittings due to the poten-  
1/4per foot  
slope to drain  
tial to leak. Use a flange fitted substitute.  
• Teflon tape thread sealant is recommended to minimize  
internal fouling of the heat exchanger.  
• Use backup wrench. Do not overtighten connections.  
• Route piping to avoid service access areas to unit.  
• Flush the piping system prior to operation to remove dirt  
and foreign materials from the system.  
1/2”  
Water  
Connections  
Alternate  
Condensate  
Location  
GROUND-WATER APPLICATIONS — Typical ground-  
water piping is shown in Fig. 13. In addition to complying  
with any applicable codes, consider the following for sys-  
tem piping:  
NOTE: Unit does not need to be sloped toward drain.  
• Install shut-off valves for servicing.  
Fig. 12 — Vertical Condensate Connection  
• Install pressure-temperature plugs to measure flow and  
temperature.  
VENTING — Install a vent in the condensate line of any  
application that may allow dirt or air to collect in the line. Con-  
sider the following:  
• Connect boiler drains and other valves using a “T” connec-  
tor to allow acid flushing for the heat exchanger.  
• Do not overtighten connections.  
• Route piping to avoid service access areas to unit.  
• Use PVC SCH80 or copper piping material.  
• Always install a vent where an application requires a long  
horizontal run.  
• Always install a vent where large units are working against  
higher external static pressure and to allow proper drainage  
for multiple units connected to the same condensate main.  
NOTE: PVC SCH40 should not be used due to system high  
pressure and temperature extremes.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Water  
Flow  
Control  
Regulator  
(field-installed  
accessory)  
Valve  
Pressure  
Tank  
(field-installed  
accessory)  
Water Out  
Water In  
From Pump  
Shut-Off  
Valve (field-installed accessory)  
Strainer (field-installed accessory)  
(16 to 20 mesh recommended for  
filter sediment)  
Boiler  
Drains  
(field-installed)  
Fig. 13 — Typical Ground-Water Piping Installation  
Water Supply and Quantity — Check water supply. Water  
supply should be plentiful and of good quality. See Table 2 for  
water quality guidelines.  
5. Refer to Table 3. Do not exceed the minimum bend radius  
for the hose selected. Exceeding the minimum bend radi-  
us may cause the hose to collapse, which reduces water  
flow rate. Install an angle adapter to avoid sharp bends  
in the hose when the radius falls below the required  
minimum.  
IMPORTANT: Failure to comply with the above required  
water quality and quantity limitations and the closed-  
system application design requirements may cause damage  
to the tube-in-tube heat exchanger. This damage is not the  
responsibility of the manufacturer.  
NOTE: Piping must comply with all applicable codes.  
Insulation is not required on loop water piping except where  
the piping runs through unheated areas or outside the building  
or when the loop water temperature is below the minimum ex-  
pected dew point of the pipe ambient. Insulation is required if  
loop water temperature drops below the dew point.  
In all applications, the quality of the water circulated  
through the heat exchanger must fall within the ranges listed in  
the Water Quality Guidelines table. Consult a local water treat-  
ment firm, independent testing facility, or local water authority  
for specific recommendations to maintain water quality within  
the published limits.  
GROUND-LOOP APPLICATIONS — Temperatures between  
25 and 110 F and a cooling capacity of 2.25 to 3 gpm of flow  
per ton is recommended. In addition to complying with any  
applicable codes, consider the following for system piping:  
CAUTION  
Do not bend or kink supply lines or hoses.  
Pipe joint compound is not necessary when Teflon threaded  
tape is pre-applied to hose assemblies or when flared-end  
connections are used. If pipe joint compound is preferred, use  
compound only in small amounts on the male pipe threads of  
the fitting adapters. Prevent sealant from reaching the flared  
surfaces of the joint.  
NOTE: When anti-freeze is used in the loop, assure that it is  
compatible with Teflon tape or pipe joint compound employed.  
Maximum allowable torque for brass fittings is 30 ft-lb. If a  
torque wrench is not available, tighten finger-tight plus one  
quarter turn. Tighten steel fittings as necessary.  
Optional pressure-rated hose assemblies designed specifi-  
cally for use with Carrier units are available. Similar hoses can  
be obtained from alternate suppliers. Supply and return hoses  
are fitted with swivel-joint fittings at one end to prevent kink-  
ing during installation.  
• Limit piping materials to only polyethylene fusion in the  
buried sections of the loop.  
• Do not use galvanized or steel fittings at any time due to  
corrosion.  
Avoid all plastic to metal threaded fittings due to the poten-  
tial to leak. Use a flange fitted substitute.  
• Do not overtighten connections.  
• Route piping to avoid service access areas to unit.  
• Use pressure-temperature (P/T) plugs to measure flow of  
pressure drop.  
INSTALLATION OF SUPPLY AND RETURN HOSE  
KIT — Follow these piping guidelines.  
1. Install a drain valve at the base of each supply and return  
riser to facilitate system flushing.  
CAUTION  
2. Install shutoff/balancing valves and unions at each unit to  
permit unit removal for servicing.  
3. Place strainers at the inlet of each system circulating  
pump.  
Backup wrench is required when tightening water connec-  
tions to prevent water line damage.  
4. Select the proper hose length to allow slack between con-  
nection points. Hoses may vary in length by +2% to –4%  
under pressure.  
Refer to Fig. 14 for an illustration of a supply/return hose  
kit. Male adapters secure hose assemblies to the unit and risers.  
Install hose assemblies properly and check them regularly to  
avoid system failure and reduced service life.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 2 — Water Quality Guidelines  
HX  
MATERIAL*  
CONDITION  
CLOSED RECIRCULATING†  
OPEN LOOP AND RECIRCULATING WELL**  
Scaling Potential — Primary Measurement  
Above the given limits, scaling is likely to occur. Scaling indexes should be calculated using the limits below.  
pH/Calcium  
Hardness Method  
All  
N/A  
pH < 7.5 and Ca Hardness, <100 ppm  
Index Limits for Probable Scaling Situations (Operation outside these limits is not recommended.)  
Scaling indexes should be calculated at 150 F for direct use and HWG applications, and at 90 F for indirect HX use. A monitoring plan should be  
implemented.  
Ryznar Stability Index  
6.0 - 7.5  
If >7.5 minimize steel pipe use.  
–0.5 to +0.5  
All  
N/A  
Langelier Saturation Index  
All  
N/A  
If <–0.5 minimize steel pipe use.  
Based upon 150 F HWG and direct well, 85 F indirect well HX.  
Iron Fouling  
2+  
Iron Fe (Ferrous)  
<0.2 ppm (Ferrous)  
All  
All  
N/A  
N/A  
(Bacterial Iron Potential)  
2+  
If Fe (ferrous) >0.2 ppm with pH 6 - 8, O <5 ppm check for iron bacteria.  
2
Iron Fouling  
<0.5 ppm of Oxygen  
Above this level deposition will occur.  
Corrosion Prevention††  
pH  
6 - 8.5  
Minimize steel pipe below 7 and no open tanks with pH <8.  
<0.5 ppm  
6 - 8.5  
All  
All  
Monitor/treat as needed.  
Hydrogen Sulfide (H S)  
2
At H S>0.2 ppm, avoid use of copper and cupronickel piping or HXs.  
2
N/A  
N/A  
Rotten egg smell appears at 0.5 ppm level.  
Copper alloy (bronze or brass) cast components are okay to <0.5 ppm.  
Ammonia Ion as Hydroxide,  
Chloride, Nitrate and Sulfate  
Compounds  
<0.5 ppm  
All  
Maximum Chloride Levels  
Maximum allowable at maximum water temperature.  
50 F (10 C)  
75 F (24 C)  
100 F (38 C)  
Copper  
Cupronickel  
304 SS  
N/A  
N/A  
N/A  
N/A  
N/A  
<20 ppm  
<150 ppm  
<400 ppm  
<1000 ppm  
>1000 ppm  
NR  
NR  
NR  
NR  
<250 ppm  
<550 ppm  
>550 ppm  
<150 ppm  
<375 ppm  
>375 ppm  
316 SS  
Titanium  
Erosion and Clogging  
Particulate Size and Erosion  
<10 ppm of particles and a  
maximum velocity of 6 fps.  
Filtered for maximum  
800 micron size.  
<10 ppm (<1 ppm “sandfreefor reinjection) of particles and a maximum velocity  
of 6 fps. Filtered for maximum 800 micron size. Any particulate that is not  
removed can potentially clog components.  
All  
All  
Brackish  
Use cupronickel heat exchanger when concentrations of calcium or sodium chlo-  
ride are greater than 125 ppm are present. (Seawater is approximately 25,000  
ppm.)  
N/A  
LEGEND  
††If the concentration of these corrosives exceeds the maximum allowable  
level, then the potential for serious corrosion problems exists.  
Sulfides in the water quickly oxidize when exposed to air, requiring that no  
agitation occur as the sample is taken. Unless tested immediately at the  
site, the sample will require stabilization with a few drops of one Molar zinc  
acetate solution, allowing accurate sulfide determination up to 24 hours  
after sampling. A low pH and high alkalinity cause system problems, even  
when both values are within ranges shown. The term pH refers to the acid-  
ity, basicity, or neutrality of the water supply. Below 7.0, the water is consid-  
ered to be acidic. Above 7.0, water is considered to be basic. Neutral water  
contains a pH of 7.0.  
HWG — Hot Water Generator  
HX  
Heat Exchanger  
N/A  
Design Limits Not Applicable Considering Recirculating  
Potable Water  
NR  
SS  
Application Not Recommended  
Stainless Steel  
*Heat exchanger materials considered are copper, cupronickel, 304 SS  
(stainless steel), 316 SS, titanium.  
†Closed recirculating system is identified by a closed pressurized piping  
system.  
To convert ppm to grains per gallon, divide by 17. Hardness in mg/l is  
equivalent to ppm.  
**Recirculating open wells should observe the open recirculating design  
considerations.  
Step 8 — Wire Field Power Supply  
WARNING  
Table 3 — Metal Hose Minimum Bend Radii  
HOSE DIAMETER (in.)  
MINIMUM BEND RADII (in.)  
1
1
/
/
2 /  
4
2
2
3
4
To avoid possible injury or death due to electrical shock,  
open the power supply disconnect switch and secure it in  
an open position during installation.  
1
1
5 /  
2
Swivel  
Brass  
Fitting  
Brass  
Fitting  
Rib Crimped  
CAUTION  
Use only copper conductors for field-installed electrical  
wiring. Unit terminals are not designed to accept other  
types of conductors.  
Length  
(2 ft Length Standard)  
MPT  
Fig. 14 — Supply/Return Hose Kit  
All field-installed wiring, including the electrical ground,  
MUST comply with the National Electrical Code (NEC) as  
well as applicable local codes. In addition, all field wiring must  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
conform to the Class II temperature limitations described in the  
NEC.  
452 + 464 + 455  
3
Average Voltage =  
=
Refer to unit wiring diagrams Fig. 15-24 for a schematic of  
the field connections, which must be made by the installing (or  
electrical) contractor. For Deluxe D with WSHP Open controls  
3-phase units and Complete C with Open controls single-phase  
and 3-phase units contact Application Engineering. Refer to  
Table 4 for fuse sizes.  
1371  
3
= 457  
Determine maximum deviation from average voltage:  
(AB) 457 – 452 = 5 v  
(BC) 464 – 457 = 7 v  
(AC) 457 – 455 = 2 v  
Consult the unit wiring diagram located on the inside of the  
compressor access panel to ensure proper electrical hookup.  
The installing (or electrical) contractor must make the field  
connections when using field-supplied disconnect.  
Maximum deviation is 7 v.  
Operating voltage must be the same voltage and phase as  
shown in electrical data shown in Table 4.  
Make all final electrical connections with a length of flexi-  
ble conduit to minimize vibration and sound transmission to  
the building.  
Determine percent voltage imbalance.  
7
% Voltage Imbalance = 100 x  
457  
= 1.53%  
POWER CONNECTION — Make line voltage connection  
by connecting the incoming line voltage wires to the line  
side of the compressor contactor terminal as shown in  
Fig. 25. See Table 4 for amperage ratings to provide correct  
wire and maximum overcurrent protection sizing.  
SUPPLY VOLTAGE — Operating voltage to unit must be  
within voltage range indicated on unit nameplate.  
On 3-phase units, voltages under load between phases must  
be balanced within 2%. Use the following formula to deter-  
mine the percentage voltage imbalance:  
This amount of phase imbalance is satisfactory as it is  
below the maximum allowable 2%.  
Operation on improper line voltage or excessive phase  
imbalance constitutes abuse and may cause damage to electri-  
cal components.  
NOTE: If more than 2% voltage imbalance is present, contact  
your local electric utility.  
208-VOLT OPERATION — All 208-230 volt units are factory  
wired for 208 volts. The transformers may be switched to  
230-volt operation by switching the red (208 volt) wire with  
the orange (230 volt) wire at the L1 terminal.  
% Voltage Imbalance  
max voltage deviation from average voltage  
460-VOLT OPERATION — Units using 460-v and an ECM  
(electronically commutated motor) fan motor, modulating  
HWR, and/or internal secondary pump will require a neutral  
wire from the supply side in order to feed accessory with  
265-v.  
= 100 x  
average voltage  
Example: Supply voltage is 460-3-60.  
AB = 452 volts  
BC = 464 volts  
AC = 455 volts  
Table 4 — 50PTH,PTV,PTD Electrical Data  
COMPRESSOR  
UNITS WITH HWR  
50PTH,  
PTV, PTD  
UNITS  
FAN  
MOTOR  
FLA  
MIN  
MAX  
FUSE/  
HACR  
VOLTAGE  
MIN/MAX  
TOTAL  
REHEAT TOTAL  
MIN  
MAX  
V-PH-Hz*  
CIRCUIT  
AMPS  
UNIT FLA  
RLA  
LRA  
PUMP  
UNIT  
CIRCUIT FUSE/  
FLA  
FLA  
AMP  
18.0  
26.0  
19.1  
10.4  
34.6  
24.9  
16.0  
40.1  
30.1  
19.2  
42.1  
HACR  
25  
40  
30  
15  
50  
35  
20  
60  
026  
038  
208/230-1-60  
208/230-1-60  
208/230-3-60  
460-3-60  
208/230-1-60  
208/230-3-60  
460-3-60  
208/230-1-60  
208/230-3-60  
460-3-60  
197/254  
197/254  
197/254  
414/506  
197/254  
197/254  
414/506  
197/254  
197/254  
414/506  
197/254  
10.3  
16.7  
11.2  
4.5  
52.0  
82.0  
58.0  
4.3  
4.3  
4.3  
4.1  
7.0  
7.0  
6.9  
7.0  
7.0  
6.9  
7.0  
14.6  
21.0  
15.5  
8.6  
28.2  
20.5  
13.3  
32.6  
24.6  
15.9  
34.2  
17.2  
25.2  
18.3  
9.7  
33.5  
23.9  
14.9  
39.0  
29.0  
18.2  
41.0  
25  
40  
25  
15  
50  
35  
20  
60  
45  
25  
60  
0.8  
0.8  
0.8  
15.4  
21.8  
16.3  
9.3  
29.0  
0.7  
21.2  
13.5  
6.4  
96.0  
88.0  
41.0  
1.07  
1.07  
1.07  
1.07  
1.07  
1.07  
1.07  
29.3  
21.6  
14.4  
33.7  
25.7  
17.7  
35.3  
049  
25.6  
17.6  
9.0  
118.0  
123.0  
62.0  
064  
072  
45  
25  
60  
208/230-1-60  
27.2  
150.0  
LEGEND  
FLA — Full Load Amps  
*The 460-v units using an ECM (electronically commutated motor) fan  
motor, modulating HWR, and/or an internal secondary pump will require  
a neutral wire from the supply side in order to feed the accessory with  
265-v.  
HACR — Heating, Air Conditioning and Refrigeration  
LRA — Locked Rotor Amps  
RLA — Rated Load Amps  
HWR — Hot Water Reheat  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G
Y
R
G
G
G
G
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G
Y
R
G
G
G
G
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G
Y
R
G
G
G
G
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G
Y
R
G
G
G
G
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G
Y
R
G
G
G
G
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
G
Y
R
G
G
G
G
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8363  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8364  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8570  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8571  
D B  
8
7
6
4
5 3  
1
2
1
D
L E  
1
2
4
3
1
2
G n d  
n e R t +  
N
E E G R  
E I T W H  
B L A C K  
R E  
t - R n e  
V
+ 1 2  
D
To WSHP Controller  
Rnet Terminals (J13)  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAPACITOR  
COMPLETE C CONTROL  
COMPRESSOR CONTACTOR  
LINE  
L O A D  
ECM CONTROL  
BOARD  
TRANSFORMER  
Fig. 25 — 50PTH,PTV,PTD Typical Single-Phase Line Voltage Power Connection  
WSHP OPEN WIRING — The WSHP Open controller will Table 6 — SPT Sensors  
be factory mounted to the unit control panel and wired to the  
Complete C or Deluxe D control board, however, the system  
wiring will need to be completed utilizing WSHP Open con-  
troller wiring diagrams and the Third Party Integration (TPI)  
Guide. Factory installation includes harness, LWT (leaving  
water temperature), supply air, and condensate sensor.  
PART  
SENSOR  
FEATURES  
NUMBER  
SPT  
Standard  
• Local access port  
• No operator control  
SPS  
• Slide potentiometer to adjust set point  
• Manual on button to override schedule  
• LED to show occupied status  
• Local access port  
SPT Plus  
SPT Pro  
SPPL  
SPP  
• LCD display  
WARNING  
• Manual on button to override schedule  
• Warmer and cooler buttons to adjust set point  
• Info button to cycle through zone and outside  
air temperatures, set points, and local override  
time  
Disconnect all power to the unit before performing mainte-  
nance or service. Unit may automatically start if power is  
not disconnected. Failure to follow this warning could  
cause personal injury, death, and/or equipment damage.  
• Local access port  
• LCD display  
• Manual on button to override schedule  
• Warmer and cooler buttons to adjust set point  
• Info button to cycle through zone and outside  
air temperatures, set points, and local override  
time  
Wiring Sensors to Inputs — Sensors can be wired to the  
WSHP Open controller’s inputs. See Table 5.  
All field control wiring that connects to the WSHP Open con-  
troller must be routed through the raceway built into the corner  
post. The raceway provides the UL required clearance between  
high and low-voltage wiring.  
SPT Pro  
Plus  
SPPF  
• Local access port  
• Fan speed*  
*The SPT Pro Plus fan speed adjustment has no effect in this application.  
Wire SPT sensors to the WSHP Open controller’s Rnet  
port. An Rnetbus can consist of any of the following combina-  
tions of devices wired in a daisy-chain configuration:  
1. Pass control wires through the hole provided in the corner  
post.  
• 1 SPT Plus, SPT Pro, or SPT Pro Plus sensor  
• 1 to 4 SPT Standard sensors  
2. Feed the wires through the raceway to the WSHP Open  
controller.  
3. Connect the wires to the removable Phoenix connectors.  
4. Reconnect the connectors to the board.  
Field-Supplied Sensor Hardware — The WSHP Open con-  
troller is configurable with the following field-supplied sen-  
sors. See Table 5.  
• 1 to 4 SPT Standard sensors and 1 SPT Plus, SPT Pro, or  
SPT Pro Plus sensor  
6
• Any of the above combinations, plus up to 2 BACview  
Handheld but no more than 6 total devices  
NOTE: If the Rnetbus has multiple SPT Standard sensors, each  
sensor must be given a unique address on the Rnetbus. See the  
Carrier Open Sensor Installation Guide.  
Use the specified type of wire and cable for maximum signal  
integrity. See Table 7.  
Table 5 — Field-Supplied Sensors for  
WSHP Open Controller  
SENSOR  
NOTES  
Space Temperature Sensor  
(SPT)  
Field Installed (Must be used with  
WSHP Open controller.)  
Table 7 — Rnet Wiring Specifications  
RNET WIRING SPECIFICATIONS  
Outdoor Air  
Network Sensor  
Temperature Sensor  
4 conductor, unshielded, CMP,  
Description  
plenum rated cable  
Indoor Air Quality Sensor  
(Separate Sensor)  
Required only for demand  
control ventilation.  
Conductor  
Maximum Length  
18 AWG  
500 ft  
Space Relative  
Humidity Sensor  
Separate Sensor  
Jacket: white  
Wiring: black, white, green, red  
Recommended Coloring  
6
NOTE: BACview Handheld or Virtual BACview can be used as the user  
interface.  
UL Temperature  
Voltage  
32 to 167 F  
For specific details about sensors, refer to the literature sup-  
plied with the sensor.  
300-vac, power limited  
UL: NEC CL2P, or better  
Listing  
Wiring a SPT Sensor — A WSHP Open controller is connect-  
ed to a wall-mounted space temperature (SPT) sensor to moni-  
tor room temperature using a Molex plug.  
The WSHP Open system offers the following SPT sensors.  
See Table 6.  
LEGEND  
AWG — American Wire Gage  
CMP — Communications Plenum Cable  
NEC — National Electrical Code  
UL  
Underwriters Laboratories  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
To wire the SPT sensor to the controller:  
Wiring a Relative Humidity (RH) Sensor — The RH sensor  
is used for zone humidity control (dehumidification) if the  
WSHP unit has a dehumidification device. If not, the sensor  
only monitors humidity.  
1. Partially cut , then bend and pull off the outer jacket of  
the Rnet cable(s), being careful not to nick the inner  
insulation.  
NOTE: Do not use a relative humidity sensor and CO sensor  
1
2
2. Strip about / in. of the inner insulation from each wire.  
4
on the same zone controller if both sensors are powered off the  
board. If sensors are externally powered, both sensors may be  
used on the same zone controller.  
See Fig. 26.  
OUTER JACKET  
If the cable used to wire the RH sensor to the controller will  
be less than 100 ft, an unshielded 22 AWG (American Wire  
Gage) cable should be used. If the cable will be greater than  
100 ft, a shield 22 AWG cable should be used. The cable  
should have a maximum length of 500 ft.  
To wire the RH sensor to the controller:  
1. Strip the outer jacket from the cable for at least 4 inches.  
a50-8443  
.25 IN.  
INNER INSULATION  
Fig. 26 — Rnet Cable Wire  
3. Wire each terminal on the sensor to the same terminal on  
the controller. See Fig. 15-24. Table 8 shows the recom-  
mended Rnet wiring scheme.  
1
2. Strip / in. of insulation from each wire.  
4
3. Wire the sensor to the controller.  
Table 8 — Rnet Wiring  
Step 9 — Wire Field Controls  
THERMOSTAT CONNECTIONS — The thermostat  
should be wired directly to the ECM control board. See  
Fig. 27.  
WIRE  
Red  
Black  
White  
Green  
TERMINAL  
+12-v  
.Rnet  
Rnet+  
Gnd  
WATER FREEZE PROTECTION — The Aquazone™ con-  
trol allows the field selection of source fluid freeze protection  
points through jumpers. The factory setting of jumper JW3  
(FP1) is set for water at 30 F. In earth loop applications, jumper  
JW3 should be clipped to change the setting to 10 F when  
using antifreeze in colder earth loop applications. See Fig. 28.  
NOTE: The extended range option should be selected  
with water temperatures below 60 F to prevent internal  
condensation.  
NOTE: The wire should be connected to the terminal shown.  
Wiring a Supply Air Temperature (SAT) Sensor  
SAT sensor is required for reheat applications.  
If the cable used to wire the SAT sensor to the controller  
will be less than 100 ft, an unshielded 22 AWG (American  
Wire Gage) cable should be used. If the cable will be greater  
than 100 ft, a shield 22 AWG cable should be used. The cable  
should have a maximum length of 500 ft.  
To wire the SAT sensor to the controller:  
1. Wire the sensor to the controller. See Fig. 15-24.  
2. Verify that the Enable SAT jumper is on.  
The  
AIR COIL FREEZE PROTECTION — The air coil freeze  
protection jumper JW2 (FP2) is factory set for 30 F and should  
not need adjusting.  
3. Verify that the Enable SAT and Remote jumper is in the  
left position.  
ACCESSORY CONNECTIONS — Terminal A on the control  
is provided to control accessory devices such as water valves,  
electronic air cleaners, humidifiers, etc. This signal operates  
with the compressor terminal. See Fig. 29. Refer to the specific  
unit wiring schematic for details.  
NOTE: The A terminal should only be used with 24-volt  
signals — not line voltage signals.  
WATER SOLENOID VALVES — An external solenoid  
valve(s) should be used on ground water installations to shut  
off flow to the unit when the compressor is not operating. A  
slow closing valve may be required to help reduce water  
hammer. Figure 29 shows typical wiring for a 24-vac external  
solenoid valve. Figures 30 and 31 illustrate typical slow closing  
water control valve wiring for Taco 500 Series and Taco ESP  
Series valves. Slow closing valves take approximately 60 sec.  
to open (very little water will flow before 45 sec.). Once fully  
open, an end switch allows the compressor to be energized (on-  
ly on valves with end switches). Only relay or triac based elec-  
tronic thermostats should be used with slow closing valves.  
When wired as shown, the slow closing valve will operate  
properly with the following notations:  
Wiring an Indoor Air Quality (IAQ) Sensor  
An IAQ  
sensor monitors CO levels. The WSHP Open controller uses  
2
this information to adjust the outside-air dampers to provide  
proper ventilation. An IAQ sensor can be wall-mounted or  
mounted in a return air duct. (Duct installation requires an aspi-  
rator box assembly.)  
The sensor has a range of 0 to 2000 ppm and a linear 4 to  
20 mA output. This is converted to 1 to 5 vdc by a 250-ohm,  
1
/ watt, 2% tolerance resistor connected across the zone con-  
4
troller’s IAQ input terminals.  
NOTE: Do not use a relative humidity sensor and CO sensor  
2
on the same zone controller if both sensors are powered off the  
board. If sensors are externally powered, both sensors may be  
used on the same zone controller.  
If the cable used to wire the IAQ sensor to the controller  
will be less than 100 ft, an unshielded 22 AWG (American  
Wire Gage) cable should be used. If the cable will be greater  
than 100 ft, a shield 22 AWG cable should be used. The cable  
should have a maximum length of 500 ft.  
To wire the IAQ sensor to the controller:  
1. Wire the sensor to the controller. See Fig. 15-24.  
1. The valve will remain open during a unit lockout.  
2. The valve will draw approximately 25 to 35 VA through  
the “Y” signal of the thermostat.  
1
2. Install a field-supplied 250-ohm, / watt, 2% tolerance  
4
IMPORTANT: Connecting a water solenoid valve can  
overheat the anticipators of electromechanical thermo-  
stats. Only use relay based electronic thermostats.  
resistor across the controller’s RH/IAQ and Gnd  
terminals.  
3. Verify the the RH/IAQ jumper is set to 0 to 5 vdc.  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAPACITOR  
COMPLETE C CONTROL  
COMPRESSOR CONTACTOR  
a50-8141  
LINE  
A D  
L O  
J1  
S1  
W
O
CFM  
SW1  
TRANSFORMER  
SW2  
SW3  
SW4  
SW5  
SW6  
SW7  
SW8  
SW9  
Y2  
Y1  
G
ON  
OFF  
DEHUM  
TB1  
R
C
Y2 Y1  
G
O
W
C
R
DH AL1  
A
A
AL1  
THERMOSTAT CONNECTION  
Fig. 27 — Low Voltage Field Wiring  
a50-7764tf  
a50-8441  
2
AMV  
TACO VALVE  
3
1
HEATER SWITCH  
AQUAZONE CONTROL (Complete C Shown)  
THERMOSTAT  
Fig. 28 — Typical Aquazone™ Control Board  
Jumper Locations  
Fig. 30 — AMV Valve Wiring  
TERMINAL STRIP P2  
C
TYPICAL  
WATER  
VALVE  
24 VAC  
A
a50-8442  
Fig. 31 — Taco SBV Valve Wiring  
Fig. 29 — Typical Accessory Wiring  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Dehumidification Mode — The dehumidification mode  
setting provides field selection of humidity control. When op-  
erating in the normal mode, the cooling airflow settings are de-  
termined by the cooling tap setting in Table 12.  
Step 10 — Operate ECM Interface Board  
STANDALONE — NO DDC CONTROLS — The ECM  
fan is controlled by an interface board that converts thermostat  
inputs and field selectable cfm settings to signals used by the  
ECM (electronically commutated motor) controller. See  
Fig. 32.  
Table 12 — Dehumidificaton Mode Settings  
DIP SWITCH  
TAP SETTING  
NOTE: Power must be off to the unit for at least three seconds  
before the ECM will recognize a speed change. The motor will  
recognize a change in the CFM Adjust or Dehumidification  
mode settings while the unit is powered.  
SW9  
NORM  
ON  
Dehumid  
OFF  
When dehumidification is enabled, there is a reduction in  
airflow in cooling to increase the moisture removal of the heat  
pump. The Dehumidification mode can be enabled in two  
ways:  
There are four different airflow settings from lowest airflow  
rate (speed tap 1) to the highest airflow rate (speed tap 4).  
Tables 9-13 indicate settings for the ECM interface board, fol-  
lowed by detailed information for each setting.  
1. Constant Dehumidification mode: When the Dehumidifi-  
cation mode is selected via DIP switch, the ECM will  
operate with a multiplier applied to the cooling CFM  
settings (approximately 20 to 25% lower airflow). Any  
time the unit is running in the Cooling mode, it will oper-  
ate at the lower airflow to improve latent capacity. The  
“DEHUM” LED will be illuminated at all times. Heating  
airflow is not affected.  
CAUTION  
When the disconnect switch is closed, high voltage is pres-  
ent in some areas of the electrical panel. Exercise caution  
when working with energized equipment.  
Cooling — The cooling setting determines the cooling (nor-  
mal) cfm for all units with ECM motor. Cooling (normal) set-  
ting is used when the unit is not in Dehumidification mode. Tap  
1 is the lowest cfm setting, while tap 4 is the highest cfm set-  
ting. To avoid air coil freeze-up, tap 1 may not be used if the  
Dehumidification mode is selected. See Table 9.  
NOTE: Do not select Dehumidification mode if cooling  
setting is tap 1.  
2. Automatic (humidistat-controlled) Dehumidification  
mode: When the Dehumidification mode is selected  
via DIP switch AND a humidistat is connected to termi-  
nal DH, the cooling airflow will only be reduced when  
the humidistat senses that additional dehumidification is  
required. The DH terminal is reverse logic. Therefore,  
a humidistat (not dehumidistat) is required. The  
“DEHUM” LED will be illuminated only when the hu-  
midistat is calling for Dehumidification mode. Heat-  
Table 9 — Cooling Settings  
DIP SWITCH  
TAP SETTING  
SW1  
ON  
ON  
OFF  
OFF  
SW2  
ON  
OFF  
ON  
1
2
3
4
ing  
airflow is not affected.  
NOTE: Do not select Dehumidification mode if cooling  
setting is tap 1.  
OFF  
Heating — The heating setting determines the heating cfm  
for 50PTH,PTV,PTD units. Tap 1 is the lowest cfm setting,  
while tap 4 is the highest cfm setting. See Table 10.  
1/4" SPADE  
CONNECTIONS  
TO COMPLETE C OR  
DELUXE D BOARD  
THERMOSTAT  
INPUT LEDS  
Table 10 — Heating Settings  
G
G
G
G
R
DIP SWITCH  
TAP SETTING  
SW3  
ON  
ON  
OFF  
OFF  
SW4  
ON  
OFF  
ON  
1
2
3
4
CFM COUNTER  
THERMOSTAT  
CONNECTIONS  
1 FLASH PER 100 CFM  
Y
OFF  
ECM MOTOR  
LOW VOLTAGE  
CONNECTOR  
CFM Adjust — The CFM Adjust setting allows four selec-  
tions. The NORM setting is the factory default position. The +  
or – settings adjust the airflow by ±15%. The + or – settings are  
used to “fine tune” airflow adjustments. The TEST setting runs  
the ECM at 70% torque, which causes the motor to operate  
like a standard PSC motor, and disables the cfm counter. See  
Table 11.  
G
DEHUMIDIFICATION  
LED  
Table 11 — CFM Adjust Settings  
FAN SPEED SELECTION DIP SWITCH  
DIP SWITCH  
TAP SETTING  
Fig. 32 — ECM Interface Board Physical Layout  
SW7  
ON  
ON  
OFF  
OFF  
SW8  
ON  
OFF  
ON  
TEST  
+
NORM  
OFF  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13 — Blower Performance Data  
FAN  
MOTOR  
(hp)  
COOLING MODE (cfm)  
Stage 1 Stage 2 Fan  
DEHUMIDIFICATION MODE (cfm)  
HEATING MODE (cfm)  
50PT  
MAX ESP  
TAP  
SETTING  
UNIT SIZE (in. wg)  
Stage 1  
Stage 2  
Fan  
Stage 1  
Stage 2  
Fan  
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
810  
725  
620  
950  
850  
730  
475  
425  
370  
300  
700  
630  
540  
450  
870  
780  
670  
560  
1020  
920  
790  
660  
1050  
980  
910  
850  
630  
560  
490  
870  
780  
670  
1140  
1020  
870  
1300  
1160  
1000  
740  
660  
570  
1090  
980  
840  
1350  
1210  
1040  
1600  
1430  
1230  
475  
425  
370  
700  
630  
540  
870  
780  
670  
1020  
920  
790  
920  
825  
710  
1060  
950  
820  
475  
425  
370  
300  
700  
630  
540  
450  
870  
780  
670  
560  
1020  
920  
790  
660  
1050  
980  
910  
850  
1
026  
038  
049  
064  
072  
0.50  
0.50  
0.75  
0.75  
0.75  
/
/
2
520  
610  
600  
690  
1120  
1000  
860  
1400  
1250  
1080  
900  
1120  
1000  
860  
1400  
1250  
1080  
900  
1
2
730  
730  
1460  
1300  
1120  
940  
1670  
1500  
1280  
1080  
1620  
1500  
1400  
1320  
1730  
1550  
1330  
1120  
2050  
1825  
1580  
1320  
2190  
1950  
1830  
1700  
1560  
1400  
1200  
1010  
1860  
1650  
1430  
1200  
1690  
1600  
1400  
1240  
1850  
1650  
1430  
1200  
2280  
2050  
1750  
1470  
2230  
2100  
1850  
1620  
1
1
1
1270  
1170  
1100  
1650  
1520  
1420  
1050  
980  
910  
WSHP OPEN CONTROLS — The ECM fan is controlled by  
an interface board that converts the fan speed outputs from the  
WSHP Open control board to the signal used by the ECM mo-  
tor (see Fig 35). The indicator LEDs allow the service techni-  
cian to view the airflow mode that the WSHP Open control is  
commanding. The table below indicates the illuminated LEDs  
for each fan mode.  
Table 14A). The fan speed and airflow is independent from the  
compressor capacity control. During Fan Only operation, the  
fan will operate at the Fan Only airflow value specified in the  
table for the appropriate tap setting. Once either cooling or  
heating is required and the compressor is energized, the fan  
will increase the minimum airflow across the coil to the value  
defined by the low fan selection. Coil freeze protection and ex-  
cessive discharge air temperature protection are integral parts  
of the WSHP Open controller function so the fan airflow can  
increase to medium or high airflow as required and indepen-  
dent of compressor capacity to prevent excessively hot or cold  
supply air temperature and coil freeze-up. The selection of the  
high fan airflow setting is independent of the other fan airflow  
settings and is defined in Table 14B. The high airflow must be  
chosen so that it is equal to or greater than the medium fan air-  
flow. Therefore the tap setting for high fan (SW5 and SW6)  
MUST equal or exceed the tap chosen for the SW3 and SW4.  
ECM INDICATORS LEDs  
SPEED  
Fan Only  
Low Fan  
Med Fan  
High Fan  
G
G + Y1  
G + Y1 + Y2  
G + Y1 +W  
NOTE: Power must be off to the unit for at least three seconds  
before the ECM will recognize a speed change. The motor will  
recognize a change in the CFM Adjust setting (SW7 and SW8)  
while the unit is powered.  
Dehumidification — When Dehumidification is used, the fan  
operates at the airflow setting defined by the Medium Fan air-  
flow setting and the tap position of SW3 and SW4.  
CFM Adjust — The CFM Adjust setting allows the balancer  
to fine tune the actual airflow. SW7 and SW8 are used to set  
the CFM Adjustment if necessary. The NORM setting is the  
factory default. The (+) or (-) settings provide the ability to ad-  
just the airflow by either +15% or -15% as needed. A test posi-  
tion is also provided but should not be used (see Table 11).  
The WSHP Open controller provides four different airflow  
settings which can be set between the lowest airflow (tap 1) to  
the highest airflow (tap 4). The lowest three airflow settings  
(Fan Only, Low, and Medium) are set using SW3 and SW 4  
while the highest airflow (High) is set independently using  
SW5 and SW6. This provides the ability to better adjust the fan  
performance of the unit to meet the required load conditions.  
Cooling and Heating — The SW3 and SW4 DIP switch set-  
tings determine the fan airflow (cfm) to be used during normal  
Fan Only, Cooling, Heating, and Dehumidification modes (see  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 14A — WSHP Open — Fan Only / Low Fan and Med Fan Airflow  
50PT UNIT MAX FAN MOTOR  
SW 3  
(SW 1)  
SW 4  
(SW 2)  
COOLING AND  
HEATING LOW FAN  
COOLING AND  
HEATING MED FAN  
TAP SETTING  
FAN ONLY  
SIZE  
ESP  
HP  
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
OFF  
OFF  
ON  
OFF  
ON  
475  
425  
370  
300  
700  
630  
540  
450  
870  
780  
670  
560  
1020  
920  
780  
660  
1050  
980  
910  
850  
920  
825  
1050  
950  
26  
0.5  
0.5  
OFF  
ON  
OFF  
ON  
710  
600  
1120  
1000  
860  
820  
690  
1400  
1250  
1080  
900  
1850  
1650  
1430  
1200  
2280  
2040  
1750  
1470  
2230  
2100  
1850  
1620  
ON  
OFF  
OFF  
ON  
38  
49  
64  
72  
0.5  
0.5  
1
OFF  
ON  
OFF  
ON  
ON  
730  
OFF  
OFF  
ON  
1560  
1400  
1200  
1010  
1860  
1650  
1430  
1200  
1600  
1600  
1400  
1240  
0.75  
0.75  
0.75  
OFF  
ON  
OFF  
ON  
ON  
OFF  
OFF  
ON  
1
OFF  
ON  
OFF  
ON  
OFF  
ON  
ON  
OFF  
OFF  
ON  
1
ON  
NOTE: Factory default setting shown bold.  
IMPORTANT: The tap setting for high fan MUST equal or exceed the  
tap setting for fan only/low/med fan  
Table 14B — WSHP Open — High Fan Airflow  
50PT UNIT SIZE MAX ESP  
FAN MOTOR HP  
TAP SETTING  
SW 5  
OFF  
OFF  
ON  
SW 6  
OFF  
ON  
COOLING AND HEATING HIGH FAN  
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
4
3
2
1
1060  
950  
26  
38  
49  
64  
72  
0.5  
0.5  
0.5  
0.5  
1
OFF  
ON  
820  
690  
ON  
OFF  
OFF  
ON  
OFF  
ON  
1400  
1350  
1350  
1350  
1850  
1660  
1430  
1350  
2280  
2050  
1750  
1470  
2230  
2100  
1870  
1670  
OFF  
ON  
ON  
OFF  
OFF  
ON  
OFF  
ON  
0.75  
0.75  
0.75  
OFF  
ON  
ON  
OFF  
OFF  
ON  
OFF  
ON  
1
OFF  
ON  
ON  
OFF  
OFF  
ON  
OFF  
ON  
1
OFF  
ON  
ON  
NOTE: Factory default setting shown bold.  
IMPORTANT: The tap setting for high fan MUST equal or exceed the  
tap setting for fan only/low/med fan  
5. Air is purged from closed loop system.  
6. System is balanced as required. Monitor if necessary.  
7. Isolation valves are open.  
PRE-START-UP  
8. Water control valves or loop pumps are wired.  
9. Condensate line is open and correctly pitched.  
10. Transformer switched to lower voltage tap if necessary.  
11. Blower rotates freely — shipping support is removed.  
12. Blower speed is on correct setting.  
13. Air filter is clean and in position.  
14. Service/access panels are in place.  
15. Return-air temperature is between 40 to 80 F heating and  
50 to 110 F cooling.  
System Checkout — When the installation is complete,  
follow the system checkout procedure outlined below before  
starting up the system. Be sure:  
1. Voltage is within the utilization range specifications of the  
unit compressor and fan motor and voltage is balanced  
for 3-phase units.  
2. Fuses, breakers and wire are correct size.  
3. Low voltage wiring is complete.  
4. Piping and system flushing is complete.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16. Air coil is clean.  
17. Control field-selected settings are correct.  
AIR COIL — To obtain maximum performance, clean the air  
coil before starting the unit. A 10% solution of dishwasher  
detergent and water is recommended for both sides of the coil.  
Rinse thoroughly with water.  
NOTE: The alarm relay will not cycle during Test mode if  
switch is set to OFF, stage 2.  
SWITCH 3 — Not used.  
DDC OUTPUT AT EH2 — Switch 4 provides a selection for  
Direct Digital Control (DDC) operation. If set to DDC output  
at EH2, the EH2 terminal will continuously output the last  
fault code of the controller. If the control is set to EH2 Normal,  
then EH2 will operate as standard electric heat output. Set the  
switch to ON to set the EH2 to normal. Set the switch to OFF  
to set the DDC output at EH2.  
FACTORY SETTING — Switch 5 is set to ON. Do not  
change the switch to OFF unless instructed to do so by the  
factory.  
FIELD SELECTABLE INPUTS  
Jumpers and DIP (dual in-line package) switches on the  
control board are used to customize unit operation and can be  
configured in the field.  
IMPORTANT: Jumpers and DIP switches should only  
be clipped when power to control board has been turned  
off.  
Deluxe D Control DIP Switches — The Deluxe D  
control has 2 DIP (dual in-line package) switch banks. Each  
bank has 8 switches and is labeled either S1 or S2 on the cir-  
cuit board. See Fig. 16, 18, 20, 22, and 23.  
DIP SWITCH BANK 1 (S1) — This set of switches offers  
the following options for Deluxe D control configuration:  
Performance Monitor (PM) — The PM is a unique feature  
that monitors water temperature and will display a warning  
when heat pump is beyond typical operating range. Set switch 1  
to enable or disable performance monitor. To enable the PM, set  
the switch to ON. To disable the PM, set the switch to OFF.  
Compressor Relay Staging Operation — Switch 2 will en-  
able or disable compressor relay staging operation. The com-  
pressor relay can be set to turn on with stage 1 or stage 2 call  
from the thermostat. This setting is used with dual stage units  
(units with 2 compressors and 2 Deluxe D controls) or in mas-  
ter/slave applications. In master/slave applications, each com-  
pressor and fan will stage according to its switch 2 setting. If  
switch is set to stage 2, the compressor will have a 3-second  
delay before energizing during stage 2 demand.  
Complete C Control Jumper Settings  
WATER COIL FREEZE PROTECTION (FP1) LIMIT  
SETTING — Select jumper 3 (JW3-FP1 Low Temp) to  
choose FP1 limit of either 30 F or 10 F. To select 30 F as the  
limit, DO NOT clip the jumper. To select 10 F as the limit, clip  
the jumper.  
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-  
TING — Select jumper 2 (JW2-FP2 Low Temp) to choose  
FP2 limit of either 30 F or 10 F. To select 30 F as the limit, DO  
NOT clip the jumper. To select 10 F as the limit, clip the  
jumper.  
ALARM RELAY SETTING — Select jumper 1 (JW1-AL2  
Dry) to either connect alarm relay terminal (AL2) to 24 vac (R)  
or to remain as a dry contact (no connection). To connect AL2  
to R, DO NOT clip the jumper. To set as dry contact, clip the  
jumper.  
Deluxe D Control Jumper Settings  
NOTE: If DIP switch is set for stage 2, the alarm relay will not  
cycle during Test mode.  
WATER COIL FREEZE PROTECTION (FP1) LIMIT  
SETTING — Select jumper 3 (JW3-FP1 Low Temp) to  
choose FP1 limit of either 30 F or 10 F. To select 30 F as the  
limit, DO NOT clip the jumper. To select 10 F as the limit, clip  
the jumper.  
AIR COIL FREEZE PROTECTION (FP2) LIMIT SET-  
TING — Select jumper 2 (JW2-FP2 Low Temp) to choose  
FP2 limit of either 30 F or 10 F. To select 30 F as the limit, DO  
NOT clip the jumper. To select 10 F as the limit, clip the  
jumper.  
ALARM RELAY SETTING — Select jumper 4 (JW4-AL2  
Dry) to either connect alarm relay terminal (AL2) to 24 vac (R)  
or to remain as a dry contact (no connection). To connect AL2  
to R, DO NOT clip the jumper. To set as dry contact, clip the  
jumper.  
Heating/Cooling Thermostat Type — Switch 3 provides se-  
lection of thermostat type. Heat pump or heat/cool thermostats  
can be selected. Select OFF for heat/cool thermostats. When in  
heat/cool mode, Y1 is used for cooling stage 1, Y2 is used for  
cooling stage 2, W1 is used for heating stage 1 and O/W2 is  
used for heating stage 2. Select ON for heat pump thermostats.  
In heat pump mode, Y1 used is for compressor stage 1, Y2 is  
used for compressor stage 2, W1 is used for heating stage 3 or  
emergency heat, and O/W2 is used for reversing valve (heating  
or cooling) depending upon switch 4 setting.  
O/B Thermostat Type — Switch 4 provides selection for heat  
pump O/B thermostats. O is cooling output. B is heating out-  
put. Select ON for thermostats with O output. Select OFF for  
thermostats with B output.  
LOW PRESSURE SETTING — The Deluxe D control can  
be configured for Low Pressure Setting (LP). Select jumper 1  
(JW1-LP Norm Open) for choosing between low pressure  
input normally opened or closed. To configure for normally  
closed operation, DO NOT clip the jumper. To configure for  
normally open operation, clip the jumper.  
Dehumidification Fan Mode — Switch 5 provides selection  
of normal or dehumidification fan mode. Select OFF for  
dehumidification mode. The fan speed relay will remain OFF  
during cooling stage 2. Select ON for normal mode. The fan  
speed relay will turn on during cooling stage 2 in normal mode.  
Output — Switch 6 provides selection for DDC operation. If  
set to DDC output at EH2, the EH2 terminal will continuously  
output the last fault code of the controller. If the control is set to  
EH2 normal, then the EH2 will operate as standard electric  
heat output. Set the switch to ON to set the EH2 to normal. Set  
the switch to OFF to set the DDC output at EH2.  
Boilerless Operation — Switch 7 provides selection of boil-  
erless operation and works in conjunction with switch 8. In  
boilerless operation mode, only the compressor is used for  
heating when FP1 is above the boilerless changeover tempera-  
ture set by switch 8 below. Select ON for normal operation or  
select OFF for boilerless operation.  
Complete C Control DIP Switches The Com-  
plete C control has 1 DIP (dual in-line package) switch bank  
with five switches labeled SW1. See Fig. 15, 17 , 19, and 21.  
PERFORMANCE MONITOR (PM) — The PM is a unique  
feature that monitors water temperature and will display a warn-  
ing when heat pump is beyond typical operating range. Refer to  
Control Operation section for detailed information. DIP switch  
1 will enable or disable this feature. To enable the PM, set the  
switch to ON. To disable the PM, set the switch to OFF.  
STAGE 2 — DIP switch 2 will enable or disable compressor  
delay. Set DIP switch to OFF for stage 2 in which the compres-  
sor will have a 3-second delay before energizing.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Boilerless Changeover Temperature — Switch 8 on S1  
provides selection of boilerless changeover temperature set  
point. Select OFF for set point of 50 F or select ON for set  
point of 40 F.  
If switch 8 is set for 50 F, then the compressor will be used  
for heating as long as the FP1 is above 50 F. The compressor  
will not be used for heating when the FP1 is below 50 F and the  
compressor will operates in emergency heat mode, staging on  
EH1 and EH2 to provide heat. If a thermal switch is being used  
instead of the FP1 thermistor, only the compressor will be used  
for heating mode when the FP1 terminals are closed. If the FP1  
terminals are open, the compressor is not used and the control  
goes into emergency heat mode.  
DIP SWITCH BANK 2 (S2) — This set of DIP switches is  
used to configure accessory relay options. See Fig. 16, 18, 20,  
22, and 23.  
Switches 1 to 3 — These DIP switches provide selection of  
Accessory 1 relay options. See Table 15A for DIP switch  
combinations.  
pump. The reversing valve ("O" signal) is energized in cool-  
ing, along with the compressor contactor(s) and blower relay.  
In the heating mode, the reversing valve is deenergized.  
Almost any thermostat will activate the heat pump in heating  
or cooling modes. The Deluxe D microprocessor board, which  
is standard with the HWR option, will accept either heat pump  
(Y,O) thermostats or non-heat pump (Y,W) thermostats.  
The reheat mode requires either a separate humidistat/  
dehumidistat or a thermostat that has an integrated dehumidifi-  
cation function for activation. The Deluxe D board is config-  
ured to work with either a humidistat or dehumidistat input to  
terminal “H” (DIP switch settings for the Deluxe D board are  
shown in Table 16). Upon receiving an “H” input, the Deluxe  
D board will activate the cooling mode and engage reheat.  
Table 16 — Humidistat/Dehumidistat Logic and  
Deluxe D DIP Switch Settings  
Reheat  
Reheat  
Sensor  
2.1 2.2 2.3  
Off Off Off  
Logic  
(ON) - H (OFF) - H  
Humidistat  
Reverse  
0 VAC  
24 VAC  
0 VAC  
Switches 4 to 6 — These DIP switches provide selection of  
Accessory 2 relay options. See Table 15B for DIP switch  
combinations.  
Dehumidistat Off On Off Standard 24 VAC  
Table 17 shows the relationship between thermostat input  
signals and unit operation. There are four operational inputs for  
single-stage units and six operational inputs for dual-stage  
units:  
Table 15A — DIP Switch Block S2 —  
Accessory 1 Relay Options  
• Fan Only  
DIP SWITCH POSITION  
ACCESSORY 1  
RELAY OPTIONS  
• Cooling Stage 1  
• Cooling Stage 2  
• Heating Stage 1  
• Heating Stage 2  
• Reheat Mode  
WSHP OPEN CONTROLS — A heat pump equipped with  
the hot water reheat option and the WSHP Open controller,  
operates in three modes: Cooling, Heating and Dehumidifica-  
tion. Cooling and Heating modes follow the standard water  
source heat pump operation with the reversing valve control-  
ling the operating mode (Heating or Cooling) and the compres-  
sor.  
1
2
3
Cycle with Fan  
Digital NSB  
Water Valve — Slow Opening  
OAD  
Reheat — Humidistat  
Reheat — Dehumidistat  
On  
Off  
On  
On  
Off  
Off  
On  
On  
Off  
On  
Off  
On  
On  
On  
On  
Off  
Off  
Off  
LEGEND  
NSB — Night Setback  
OAD — Outside Air Damper  
NOTE: All other DIP switch combinations are invalid.  
Table 15B — DIP Switch Block S2 —  
Accessory 2 Relay Options  
The hot water reheat option uses the Deluxe D board and  
the optional humidity sensor to provide dehumidification oper-  
ation that is separate from the standard heating or cooling cy-  
cle. The Dehumidification mode is active when the value of the  
humidity sensor exceeds the appropriate (occupied or unoccu-  
pied) humidity setpoint in the WSHP Open controller. When  
this occurs, the WSHP Open controller outputs a signal to the  
H terminal of the Deluxe D board which starts dehumidifica-  
tion with hot water reheat. The WSHP Open controller also  
sets the fan to operate at the airflow defined by the medium fan  
speed and the tap setting of SW3 and SW4. Dehumidification  
is ONLY active when neither cooling nor heating is required  
and the humidity sensor value exceeds the humidity setpoint.  
Also, both the HWR option and the Optional RH sensor must  
be set to Enable in the WSHP Open control for dehumidifica-  
tion.  
HWR APPLICATION CONSIDERATIONS — Unlike  
most hot gas reheat options, the HWR option will operate  
over a wide range of entering-water temperatures (EWTs).  
Special flow regulation (water regulating valve) is not  
required for low EWT conditions. However, below 55 F,  
supply-air temperatures cannot be maintained at 72 F  
because the cooling capacity exceeds the reheat coil capac-  
ity at low water temperatures. Below 55 F, essentially all  
water is diverted to the reheat coil (no heat of rejection to  
the building loop). Although the HWR option will work fine  
with low EWTs, overcooling of the space may result with  
well water systems or, on rare occasions, with ground loop  
(geothermal) systems (NOTE: Extended range units are  
required for well water and ground loop systems). Since  
dehumidification is generally only required in cooling, most  
DIP SWITCH POSITION  
ACCESSORY 2  
RELAY OPTIONS  
4
5
6
Cycle with Compressor  
Digital NSB  
Water Valve — Slow Opening  
OAD  
On  
Off  
On  
On  
On  
On  
Off  
On  
On  
On  
On  
Off  
LEGEND  
NSB — Night Setback  
OAD — Outside Air Damper  
NOTE: All other switch combinations are invalid.  
Auto Dehumidification Mode or High Fan Mode — Switch 7  
provides selection of auto dehumidification fan mode or high  
fan mode. In auto dehumidification fan mode, the fan speed  
relay will remain off during cooling stage 2 if terminal H is  
active. In high fan mode, the fan enable and fan speed relays will  
turn on when terminal H is active. Set the switch to ON for auto  
dehumidification fan mode or to OFF for high fan mode.  
Factory Setting — Switch 8 is set to ON. Do not change the  
switch to OFF unless instructed to do so by the factory.  
Units with Modulating Hot Water Reheat  
(HWR) Option  
STANDALONE — NO DDC CONTROLS — A heat  
pump equipped with hot water reheat (HWR) can operate in  
three modes: cooling, cooling with reheat, and heating. The  
cooling and heating modes are like any other water source heat  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ground loop systems will not experience overcooling of the  
supply-air temperature. If overcooling of the space is a con-  
cern (e.g., computer room well water application), auxiliary  
heating may be required to maintain space temperature  
when the unit is operating in the dehumidification mode.  
Water source heat pumps with HWR should not be used as  
makeup air units. These applications should use equipment  
specifically designed for makeup air.  
CYCLE WITH FAN — In this configuration, the accessory  
relay 1 will be ON any time the Fan Enable relay is on.  
CYCLE WITH COMPRESSOR — In this configuration, the  
accessory relay 2 will be ON any time the Compressor relay is  
on.  
DIGITAL NIGHT SET BACK (NSB) — In this configura-  
tion, the relay will be ON if the NSB input is connected to  
ground C.  
HWR COMPONENT FUNCTIONS — The proportional  
controller operates on 24 VAC power supply and automatically  
adjusts the water valve based on the supply-air sensor. The  
supply-air sensor senses supply-air temperature at the blower  
inlet, providing the input signal necessary for the proportional  
control to drive the motorized valve during the reheat mode of  
operation. The motorized valve is a proportional actuator/three-  
way valve combination used to divert the condenser water  
from the coax to the hydronic reheat coil during the reheat  
mode of operation. The proportional controller sends a signal  
to the motorized valve based on the supply-air temperature  
reading from the supply air sensor.  
The loop pump circulates condenser water through the hy-  
dronic reheat coil during the reheat mode of operation (refer to  
Fig. 33). In this application, the loop pump is only energized  
during the reheat mode of operation. The hydronic coil is uti-  
lized during the reheat mode of operation to reheat the air to the  
set point of the proportional controller. Condenser water is di-  
verted by the motorized valve and pumped through the hydron-  
ic coil by the loop pump in proportion to the control set point.  
The amount of reheating is dependent on the set point and how  
far from the set point the supply air temperature is. The factory  
set point is 70 to 75 F, generally considered "neutral" air.  
NOTE: If there are no relays configured for digital NSB, then  
the NSB and override (OVR) inputs are automatically config-  
ured for mechanical operation.  
MECHANICAL NIGHT SET BACK — When NSB input is  
connected to ground C, all thermostat inputs are ignored. A  
thermostat set back heating call will then be connected to the  
OVR input. If OVR input becomes active, then the Deluxe D  
control will enter night low limit (NLL) staged heating mode.  
The NLL staged heating mode will then provide heating dur-  
ing the NSB period.  
WATER VALVE (SLOW OPENING) — If relay is configured  
for Water Valve (slow opening), the relay will start 60 seconds  
prior to starting compressor relay.  
OUTSIDE AIR DAMPER (OAD) — If relay is configured for  
OAD, the relay will normally be ON any time the Fan Enable  
relay is energized. The relay will not start for 30 minutes fol-  
lowing a return to normal mode from NSB, when NSB is no  
longer connected to ground C. After 30 minutes, the relay will  
start if the Fan Enable is set to ON.  
CAUTION  
To avoid equipment damage, DO NOT leave system filled  
in a building without heat during the winter unless anti-  
freeze is added to system water. Condenser coils never  
fully drain by themselves and will freeze unless winterized  
with antifreeze.  
Deluxe D Control Accessory Relay Configura-  
tions — The following accessory relay settings are applica-  
ble for Deluxe D control:  
Table 17 — HWR Operating Modes  
INPUT  
Y1  
Off  
Off  
On  
On  
On  
Off  
On  
OUTPUT  
MODE  
O
On/Off  
On/Off  
On  
On  
On  
On/Off  
Off  
Off  
G
Y2*  
Off  
Off  
Off  
On  
On/Off  
Off  
Off  
On  
On/Off  
H
O
On/Off  
On/Off  
On  
On  
On  
On  
Off  
Off  
Off  
G
Y1  
Off  
Off  
On  
On  
On  
On  
On  
On  
On  
Y2*  
Off  
Off  
Off  
On  
On/Off  
On  
Off  
On  
On/Off  
Reheat  
Off  
Off  
Off  
Off  
Off  
On  
Off  
Off  
No Demand  
Fan Only  
Off  
On  
On  
On  
On  
Off  
On  
On  
On  
Off  
Off  
Off  
Off  
On  
On  
Off  
Off  
On  
Off  
On  
On  
On  
On  
On  
On  
On  
On  
Cooling Stage 1  
Cooling Stage 2  
Cooling and Dehumidistat  
Dehumidistat Only  
Heating Stage 1  
Heating Stage 2  
Heating and Dehumidistat**  
On  
On  
Off  
Off  
*Not applicable for single stage units; Full load operation for dual capacity  
**Deluxe D is programmed to ignore the H demand when the unit is in heating  
units.  
mode.  
†Cooling input takes priority over dehumidify input.  
NOTE: On/Off is either on or off.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Water Out  
(To Water Loop)  
a50-8145  
Refrigerant In  
(Cooling)  
Mixing Valve  
Water In  
(From Water Loop)  
Internal Pump  
COAX  
Refrigerant Out  
(Cooling)  
Leaving  
Air  
Entering Air  
Reheat  
Coil  
NOTE: All components shown are  
internal to the heat pump unit.  
Evaporator Coil  
Fig. 33 — HWR Schematic  
3. Balance airflow at registers.  
START-UP  
4. Adjust all valves to the full open position and turn on the  
line power to all heat pump units.  
5. Operate unit in the cooling cycle first, then the heating  
cycle. Refer to Table 18 for unit operating limits. Al-  
low 15 minutes between cooling and heating tests for  
pressure to equalize.  
NOTE: Two factors determine the operating limits of a unit:  
entering-air temperature and water temperature. Whenever any  
of these factors are at a minimum or maximum level, the other  
two factors must be at a normal level to ensure proper unit  
operation. See Table 18.  
Use the procedure outlined below to initiate proper unit  
start-up.  
NOTE: This equipment is designed for indoor installation only.  
Operating Limits  
ENVIRONMENT — This equipment is designed for indoor  
installation ONLY. Extreme variations in temperature, humidi-  
ty and corrosive water or air will adversely affect the unit per-  
formance, reliability and service life.  
POWER SUPPLY — A voltage variation of ± 10% of name-  
plate utilization voltage is acceptable.  
UNIT STARTING CONDITIONS — Units start and operate  
in an ambient temperature of 45 F with entering-air tempera-  
ture at 50 F, entering-water temperature at 60 F and with both  
air and water at the flow rates used.  
NOTE: These operating limits are not normal or continuous  
operating conditions. Assume that such a start-up is for the  
purpose of bringing the building space up to occupancy tem-  
perature. See Table 18 for operating limits.  
Table 18 — Operating Limits —  
50PTH, PTV, PTD Units  
AIR LIMITS  
Min. Ambient Air  
Rated Ambient Air  
Max. Ambient Air  
Min. Entering Air  
Rated Entering Air db/wb  
Max. Entering Air db/wb  
WATER LIMITS  
COOLING (F)  
HEATING (F)  
45  
80  
100  
50  
80/67  
110/83  
40  
70  
85  
40  
70  
80  
Min. Entering Water  
Normal Entering Water  
Max. Entering Water  
LEGEND  
30  
50-110  
120  
20  
30-70  
90  
WARNING  
When the disconnect switch is closed, high voltage is pres-  
ent in some areas of the electrical panel. Exercise caution  
when working with the energized equipment.  
db  
Dry Bulb  
Wet Bulb  
wb  
NOTE: Value in heating column is dry bulb only. Any wet bulb reading is  
acceptable.  
1. Restore power to system.  
2. Turn thermostat fan position to ON. Blower should start.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. Check the temperature of both supply and discharge  
water. Compare to Tables 20-23. If temperature is within  
range, proceed. If temperature is outside the range, check  
the cooling refrigerant pressures in Tables 20-23.  
5. Check air temperature drop across the coil when com-  
pressor is operating. Air temperature drop should be  
between 15 and 25 F.  
Scroll Compressor Rotation — It is important to be  
certain compressor is rotating in the proper direction. To  
determine whether or not compressor is rotating in the proper  
direction:  
1. Connect service gages to suction and discharge pressure  
fittings.  
2. Energize the compressor.  
3. The suction pressure should drop and the discharge  
Unit Start-Up Heating Mode  
pressure should rise, as is normal on any start-up.  
NOTE: Operate the unit in heating cycle after checking the  
cooling cycle. Allow 5 minutes between tests for the pressure  
or reversing valve to equalize.  
If the suction pressure does not drop and the discharge  
pressure does not rise to normal levels:  
1. Turn off power to the unit. Install disconnect tag.  
2. Reverse any two of the unit power leads.  
3. Reapply power to the unit and verify pressures are correct.  
The suction and discharge pressure levels should now move  
to their normal start-up levels.  
When the compressor is rotating in the wrong direction, the  
unit makes more noise and does not provide cooling.  
After a few minutes of reverse operation, the scroll com-  
pressor internal overload protection will open, thus activating  
the unit lockout. This requires a manual reset. To reset, turn the  
thermostat on and then off.  
1. Turn thermostat to lowest setting and set thermostat  
switch to HEAT position.  
2. Slowly turn the thermostat to a higher temperature until  
the compressor activates.  
3. Check for warm air delivery at the unit grille within a few  
minutes after the unit has begun to operate.  
4. Check the temperature of both supply and discharge  
water. Compare to Tables 20-23. If temperature is within  
range, proceed. If temperature is outside the range, check  
the heating refrigerant pressures in Tables 20-23.  
5. Once the unit has begun to run, check for warm air deliv-  
ery at the unit grille.  
6. Check air temperature rise across the coil when compres-  
sor is operating. Air temperature rise should be between  
20 and 30 F after 15 minutes at load.  
NOTE: There is a 5-minute time delay before the compressor  
will start.  
Unit Start-Up Cooling Mode  
1. Adjust the unit thermostat to the warmest position.  
Slowly reduce the thermostat position until the compres-  
sor activates.  
2. Check for cool air delivery at unit grille a few minutes  
after the unit has begun to operate.  
3. Verify that the compressor is on and that the water flow  
rate is correct by measuring pressure drop through the  
heat exchanger using P/T plugs. See Table 19. Check the  
elevation and cleanliness of the condensate lines; any  
dripping could be a sign of a blocked line. Be sure the  
condensate trap includes a water seal.  
7. Check for vibration, noise and water leaks.  
Table 19 — Water Temperature Change  
Through Heat Exchanger  
COOLING  
RISE (F)  
HEATING  
DROP (F)  
WATER FLOW RATE (GPM)  
Min  
Max  
Min  
Max  
For Closed Loop: Ground Source or  
Cooling/Boiler Systems at 3 gpm/ton  
9
12  
4
8
For Open Loop: Ground Water Systems at  
1.5 gpm/ton  
20  
26  
10  
17  
Table 20 — Typical 50PTH,PTV,PTD026 Unit Operating Pressures and Temperatures  
FULL LOAD COOLING WITHOUT HWG ACTIVE  
Water  
FULL LOAD HEATING WITHOUT HWG ACTIVE  
Water  
ENTERING  
WATER  
TEMP (F)  
(EWT)  
WATER  
FLOW  
(Gpm/Ton)  
Air  
Temp  
Drop (F)  
DB  
Air  
Suction Discharge Super-  
Sub-  
cooling  
(F)  
Suction Discharge Super-  
Sub-  
cooling  
(F)  
Temp  
Rise  
(F)  
Temp  
Drop  
(F)  
Temp  
Rise (F)  
DB  
Pressure Pressure  
heat  
(F)  
Pressure Pressure  
heat  
(F)  
(psig)  
(psig)  
(psig)  
(psig)  
1.5  
2.25  
3
1.5  
2.25  
3
118-128  
118-128  
118-128  
128-138  
128-138  
128-138  
159-179  
146-166  
132-152  
186-206  
172-192  
158-178  
25-30  
25-30  
25-30  
18-23  
18-23  
18-23  
9-14  
7-12  
7-12  
8-13  
6-11  
6-11  
16.7-18.7  
12.3-14.3  
7.9- 9.9  
16.3-18.3  
12.1-14.1  
7.8- 9.8  
19-25  
20-26  
20-26  
19-25  
20-26  
20-26  
73- 83  
75- 85  
78- 88  
102-112  
106-116  
110-120  
273-293  
275-295  
277-297  
302-322  
303-323  
305-325  
6-11  
6-11  
6-11  
8-12  
8-12  
8-12  
3- 8  
3- 8  
3- 8  
6-11  
6-11  
6-11  
5.9- 7.9  
4.2- 6.2  
2.7- 4.7  
8.9-10.9  
6.7- 8.7  
4.5- 6.5  
16-22  
17-23  
18-24  
22-28  
23-29  
23-29  
30  
50  
1.5  
2.25  
3
136-146  
136-146  
136-146  
281-301  
267-287  
253-273  
7-12  
7-12  
7-12  
7-12  
5-10  
4- 9  
15.7-17.7  
11.6-13.6  
7.6- 9.6  
19-25  
19-25  
19-25  
128-138  
134-144  
141-151  
330-350  
332-352  
334-354  
10-15  
10-15  
10-15  
8-13  
8-13  
8-13  
11.3-13.3  
8.5-10.5  
5.8- 7.8  
27-34  
28-35  
28-35  
70  
1.5  
2.25  
3
139-149  
139-149  
139-149  
368-388  
354-374  
340-360  
6-11  
6-11  
6-11  
7-12  
5-10  
5-10  
14.9-16.9  
11.0-13.0  
7.2- 9.2  
18-24  
18-24  
18-24  
162-172  
166-176  
171-181  
367-387  
372-392  
377-397  
14-19  
15-20  
17-22  
10-15  
10-15  
10-15  
14.4-16.4  
10.8-12.8  
7.1- 9.1  
33-41  
34-42  
34-42  
90  
1.5  
2.25  
3
143-153  
143-153  
143-153  
465-485  
450-470  
433-453  
6-11  
6-11  
6-11  
7-12  
5-10  
5-10  
13.9-15.9  
10.2-12.2  
6.5- 8.5  
17-23  
17-23  
17-23  
110  
LEGEND  
DB  
HWG — Hot Water Generator  
No heating operation in this temperature range  
Dry Bulb  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 21 — Typical 50PTH,PTV,PTD038 Unit Operating Pressures and Temperatures  
FULL LOAD COOLING WITHOUT HWG ACTIVE  
Water  
FULL LOAD HEATING WITHOUT HWG ACTIVE  
Water  
ENTERING  
WATER  
TEMP (F)  
(EWT)  
WATER  
FLOW  
(Gpm/Ton)  
Air  
Temp  
Drop (F)  
DB  
Air  
Temp  
Rise (F)  
DB  
Suction Discharge Super-  
Sub-  
cooling  
(F)  
Suction Discharge Super-  
Sub-  
cooling  
(F)  
Temp  
Rise  
(F)  
Temp  
Drop  
(F)  
Pressure Pressure  
heat  
(F)  
Pressure Pressure  
heat  
(F)  
(psig)  
(psig)  
(psig)  
(psig)  
1.5  
2.25  
3
1.5  
2.25  
3
120-130  
119-129  
119-129  
129-139  
128-138  
128-138  
156-176  
148-168  
138-158  
225-245  
211-231  
197-217  
25-30  
25-30  
25-30  
15-20  
15-20  
15-20  
9-14  
8-13  
8-13  
10-15  
9-14  
9-14  
22.1-24.1  
16.8-18.8  
10.5-12.5  
21.9-23.9  
16.1-18.1  
10.3-12.3  
18-24  
19-25  
19-25  
18-24  
19-25  
19-25  
69- 79  
73- 83  
76- 86  
96-106  
100-110  
105-115  
293-313  
297-317  
300-320  
322-342  
326-346  
331-351  
7-12  
7-12  
7-12  
10-15  
10-15  
10-15  
14-19  
14-19  
14-19  
17-22  
17-22  
17-22  
8.9-10.9  
6.7- 8.7  
4.5- 6.5  
12.2-14.2  
9.3-11.3  
6.4- 8.4  
17-23  
18-24  
19-25  
23-29  
24-30  
24-30  
30  
50  
1.5  
2.25  
3
136-146  
135-145  
135-145  
302-322  
283-303  
265-285  
9-14  
9-14  
9-14  
13-18  
12-17  
12-17  
21.5-23.5  
15.8-17.8  
10.0-12.0  
18-24  
19-25  
19-25  
123-133  
129-139  
135-145  
352-372  
358-378  
364-384  
11-16  
11-16  
11-16  
19-24  
19-24  
19-24  
15-17  
11.6-13.6  
8.2-10.2  
28-35  
29-36  
30-37  
70  
1.5  
2.25  
3
140-150  
140-150  
140-150  
390-410  
369-389  
349-369  
7-12  
8-13  
8-13  
13-18  
8-13  
8-13  
20.5-22.5  
14.9-16.9  
9.3-11.3  
17-23  
17-23  
17-23  
157-167  
169-179  
181-191  
390-410  
399-419  
408-428  
13-18  
18-23  
21-23  
36-44  
37-45  
39-47  
90  
13-18 16.5-21.5 15.5-17.5  
14-19  
15-20  
10.5-12.5  
1.5  
2.25  
3
145-155  
145-155  
145-155  
488-508  
467-487  
447-467  
7-12  
8-13  
8-13  
13-18  
8-13  
8-13  
19.0-21.0  
14.0-16.0  
9.0-11.0  
17-23  
17-23  
17-23  
110  
LEGEND  
DB  
HWG — Hot Water Generator  
No heating operation in this temperature range  
Dry Bulb  
Table 22 — Typical 50PTH,PTV,PTD049 Unit Operating Pressures and Temperatures  
FULL LOAD COOLING WITHOUT HWG ACTIVE  
Water  
FULL LOAD HEATING WITHOUT HWG ACTIVE  
Water  
ENTERING  
WATER  
FLOW  
(Gpm/Ton)  
Air  
Temp  
Drop (F)  
DB  
Air  
Temp  
Rise (F)  
DB  
WATER  
TEMP (F)  
(EWT)  
Suction Discharge Super-  
Sub-  
cooling  
(F)  
Suction Discharge Super-  
Sub-  
cooling  
(F)  
Temp  
Rise  
(F)  
Temp  
Drop  
(F)  
Pressure Pressure  
heat  
(F)  
Pressure Pressure  
heat  
(F)  
(psig)  
(psig)  
(psig)  
(psig)  
1.5  
2.25  
3
1.5  
2.25  
3
112-122  
111-121  
111-121  
125-135  
123-133  
122-132  
187-207  
167-187  
147-167  
242-262  
224-244  
205-225  
22-27  
22-27  
23-28  
13-18  
13-18  
14-19  
14-19  
12-17  
11-16  
10-15  
9-14  
7-12  
20.7-22.7  
15.5-17.5  
10.2-12.2  
20.9-22.9  
15.6-17.6  
10.2-12.2  
18-24  
18-24  
18-24  
19-25  
19-25  
19-25  
66- 76  
69- 79  
72- 82  
93-103  
98-108  
103-113  
286-306  
289-309  
292-312  
314-334  
320-340  
326-346  
7-12  
7-12  
7-12  
8-13  
8-13  
8-13  
8-13  
9-14  
9-14  
10-15  
10-15  
10-15  
8-10  
6- 8  
4- 6  
11.5-13.5  
8.7-10.7  
5.9- 7.9  
18-24  
19-25  
19-25  
23-29  
24-30  
25-31  
30  
50  
1.5  
2.25  
3
133-143  
132-142  
131-141  
310-330  
290-310  
270-290  
8-13  
8-13  
9-14  
8-13  
7-12  
5-10  
20.5-22.5  
15.2-17.2  
9.9-11.9  
19-25  
19-25  
19-25  
123-133  
130-140  
137-147  
344-364  
354-374  
361-381  
9-14  
9-14  
9-14  
9-14  
9-14  
9-14  
15-17  
11.5-13.5  
7.9- 9.9  
28-35  
29-36  
30-37  
70  
1.5  
2.25  
3
138-148  
137-147  
136-146  
396-416  
374-394  
352-372  
7-12  
7-12  
7-12  
7-12  
6-11  
4- 9  
19.2-21.2  
14.3-16.3  
9.3-11.3  
18-24  
18-24  
18-24  
165-175  
175-185  
185-195  
390-410  
401-421  
413-433  
13-18  
15-20  
17-22  
8-13  
8-13  
8-13  
19.6-21.6  
15-17  
10.3-12.3  
37-45  
38-46  
39-47  
90  
1.5  
2.25  
3
144-154  
143-153  
142-152  
497-517  
472-492  
447-467  
7-12  
7-12  
7-12  
5-10  
4- 9  
3- 8  
18.0-20.0  
13.3-15.3  
8.5-10.5  
17-23  
17-23  
17-23  
110  
LEGEND  
DB  
HWG — Hot Water Generator  
No heating operation in this temperature range  
Dry Bulb  
Table 23 — Typical 50PTH,PTV,PTD064,072 Unit Operating Pressures and Temperatures  
FULL LOAD COOLING WITHOUT HWG ACTIVE  
Water  
FULL LOAD HEATING WITHOUT HWG ACTIVE  
Water  
ENTERING  
WATER  
FLOW  
(Gpm/Ton)  
Air  
Temp  
Drop (F)  
DB  
Air  
Temp  
Rise (F)  
DB  
WATER  
TEMP (F)  
(EWT)  
Suction Discharge Super-  
Sub-  
cooling  
(F)  
Suction Discharge Super-  
Sub-  
cooling  
(F)  
Temp  
Rise  
(F)  
Temp  
Drop  
(F)  
Pressure Pressure  
heat  
(F)  
Pressure Pressure  
heat  
(F)  
(psig)  
(psig)  
(psig)  
(psig)  
1.5  
2.25  
3
1.5  
2.25  
3
117-127  
116-126  
115-125  
128-138  
126-136  
125-135  
170-190  
143-163  
135-155  
238-258  
222-242  
205-225  
27-32  
28-33  
29-34  
16-21  
21-26  
26-31  
15-20  
13-18  
12-17  
14-19  
13-18  
12-17  
18.2-20.2  
12.6-14.6  
7.0- 9.0  
20.5-22.5  
14.9-16.9  
9.2-11.2  
17-23  
17-23  
17-23  
21-27  
21-27  
21-27  
66- 76  
69- 79  
72- 82  
90-100  
95-105  
99-109  
282-302  
285-305  
289-309  
310-330  
313-333  
316-336  
10-16  
10-16  
10-16  
11-17  
11-17  
11-17  
9-14  
9-14  
8-10  
6- 8  
4- 6  
11.3-13.3  
8.5-10.5  
5.7- 7.7  
19-25  
19-25  
20-26  
24-30  
25-31  
26-32  
30  
50  
10-15  
12-17  
12-17  
12-17  
1.5  
2.25  
3
135-145  
134-144  
133-143  
315-335  
296-316  
276-296  
10-15  
12-17  
15-20  
14-19  
13-18  
11-16  
21.0-23.0  
15.5-17.5  
10.0-12.0  
22-28  
22-28  
22-28  
115-125  
120-130  
126-136  
337-357  
341-361  
345-365  
12-18  
12-18  
12-18  
14-19  
14-19  
15-20  
14-16  
10.6-12.6  
7.3- 9.3  
28-35  
29-36  
30-37  
70  
1.5  
2.25  
3
139-149  
138-148  
138-148  
408-428  
386-406  
364-384  
10-15  
10-15  
10-15  
15-20  
13-18  
11-16  
20.1-22.1  
14.8-16.8  
9.5-11.5  
21-27  
21-27  
21-27  
157-167  
161-171  
166-176  
390-410  
394-414  
398-418  
15-20  
15-20  
15-20  
14-19  
14-19  
15-20  
18.2-20.2  
13.9-15.9  
9.6-11.6  
37-45  
38-46  
39-47  
90  
1.5  
2.25  
3
144-154  
143-153  
142-152  
515-535  
493-513  
469-489  
8-13  
8-13  
8-13  
14-19  
13-18  
12-17  
19.0-21.0  
14.0-16.0  
9.0-11.0  
20-26  
20-26  
20-26  
110  
LEGEND  
DB  
HWG — Hot Water Generator  
No heating operation in this temperature range  
Dry Bulb  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b. To program the beginning and end dates, scroll  
down to the beginning month and press the enter  
key. The softkeys (INCR and DECR) will activate  
to increment the month in either direction, Jan,  
Feb, March, etc.  
c. Use number keys to select the day of month and  
year.  
Unit Start-Up with WSHP Open Controls —  
The WSHP Open is a multi-protocol (default BACnet*) con-  
troller with extensive features, flexible options and powerful  
capabilities. The unit comes from the factory pre-programmed  
and needs minimal set up to function in a BAS (Building  
Automation System) system or provide additional capabilities  
to Carrier's WSHP product line. Most settings on the controller  
have factory defaults set for ease of installation. There are a  
few settings that must be configured in the field and several  
settings that can be adjusted if required by unique job condi-  
tions. Refer to Appendix A — WSHP Open Screen Configura-  
d. Push the OK softkey to finalize the data.  
6. To view configuration settings:  
a. Select the Config softkey.  
6
tion. In order to configure the unit, a BACview display is  
b. Select the Service Config softkey. Scroll through  
the factory settings by using the up and down  
arrow keys. See below for factory settings.  
required. See Fig. 34.  
NOTE: If the WSHP Open control has lost its programming,  
all display pixels will be displayed on the SPT sensor. See the  
WSHP Third Party Integration Guide.  
Only the following settings will need to be  
checked.  
When the unit is OFF, the SPT sensor will indicate OFF.  
When power is applied, the SPT sensor will indicate tempera-  
ture in the space at 78 F.  
• # of Fan Speeds — This should be set to "1" for  
units with PSC motors and set to "3" for units with  
ECM motors.  
• Compressor Stages — This should be set to "1."  
• Factory Dehumidification Reheat Coil — This  
should be set to "none" unless the modulating hot  
water reheat option is supplied in the unit, then set  
to "installed."  
To start-up a unit with WSHP Open controls:  
6
1. To plug in the BACview handheld display into a SPT  
sensor, point the two ears on the connector up and tilt the  
bottom of the plug toward you. Insert the plug up into the  
SPT sensor while pushing the bottom of the plug away  
from you.  
The condenser water limit needs to be verified  
depending on design parameters and application,  
whether geothermal or boiler/tower.  
6
2. BACview should respond with "Establishing Connec-  
tion." The Home screen will then appear on the display  
showing operating mode and space temperature. Press  
any button to continue.  
7. To view unit configuration settings:  
a. Select the Unit Configuration softkey, then select  
Unit.  
See Appendix A — WSHP Open Screen Configuration  
for the hierarchal structure of the WSHP Open controller.  
All functions of the controller can be set from the Home  
screen.  
b. Scroll through the unit settings by using the up and  
down arrow keys. Unit settings include:  
• Fan Mode: Default Continuous  
• Fan Delay:  
3. When the Login is requested, type 1111 and push the OK  
softkey. The Logout will then be displayed to indicate the  
password was accepted.  
• Minimum SAT Cooling: Default 50 F  
• Maximum SAT Heating: Default 110 F  
• Filter Service Alarm: Must be set from 0 to 9999 hr  
4. To set the Clock if it is not already displayed:  
8. To set local schedules:  
a. Select System Settings from the Home screen, then  
press Clockset.  
b. Scroll to hour, minute and second using the arrow  
keys. Use the number keypad to set actual time.  
c. Scroll to day, month and year using arrow keys.  
Use number keypad to set date.  
a. Select the Schedule softkey from the Configuration  
screen, then press enter.  
b. Select Weekly, then press enter (7 schedules  
available).  
c. Select day and press enter.  
d. Press enter again and select ADD or DEL (DECR  
or INCR) set schedule.  
5. To set Daylight Savings Time (DST):  
a. Push the DST softkey. The display will indicate  
02:00:060 which is equal to 2:00AM.  
e. Enter ON/OFF time, then press continue.  
a50-8444  
6
Fig. 34 — BACview Display Interface  
*Sponsored by ASHRAE (American Society of Heating, Refrigerat-  
ing and Air Conditioning Engineers).  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
f. Press OK to apply and save to a particular day of  
the week.  
g. Continue to add the same or different schedule spe-  
cific days of the week.  
the water level in the flush cart tank to drop below the  
pump inlet line in order to prevent air from filling the line.  
3. Maintain a fluid level in the tank above the return tee in  
order to avoid air entering back into the fluid.  
4. Shutting off the return valve that connects into the flush  
cart reservoir will allow 50 psig surges to help purge air  
pockets. This maintains the pump at 50 psig.  
To add exceptions to the schedule:  
i. Press Add softkey.  
ii. Select exception type from following:  
• Date  
5. To purge, keep the pump at 50 psig until maximum  
pumping pressure is reached.  
• Date Range  
6. Open the return valve to send a pressure surge through  
the loop to purge any air pockets in the piping system.  
7. A noticeable drop in fluid level will be seen in the flush  
cart tank. This is the only indication of air in the loop.  
• Week-N-Day  
• Calender Reference  
9. Go back to Home Screen.  
6
10. Remove BACview cable from SPT sensor by reversing  
NOTE: If air is purged from the system while using a  
10 in. PVC flush tank, the level drop will only be 1 to  
2 in. since liquids are incompressible. If the level drops  
more than this, flushing should continue since air is still  
being compressed in the loop. If level is less than 1 to  
2 in., reverse the flow.  
the process in Step 1.  
11. Perform system test.  
Flow Regulation — Flow regulation can be accom-  
plished by two methods. Most water control valves have a flow  
adjustment built into the valve. By measuring the pressure drop  
through the unit heat exchanger, the flow rate can be deter-  
mined. See Table 24. Adjust the water control valve until the  
flow of 1.5 to 2 gpm is achieved. Since the pressure constantly  
varies, two pressure gages may be needed in some  
applications.  
8. Repeat this procedure until all air is purged.  
9. Restore power.  
Antifreeze may be added before, during, or after the flush-  
ing process. However, depending on when it is added in the  
process, it can be wasted. Refer to the Antifreeze section for  
more detail.  
Loop static pressure will fluctuate with the seasons. Pres-  
sures will be higher in the winter months than during the warm-  
er months. This fluctuation is normal and should be considered  
when charging the system initially. Run the unit in either  
heating or cooling for several minutes to condition the loop to a  
homogenous temperature.  
When complete, perform a final flush and pressurize the  
loop to a static pressure of 40 to 50 psig for winter months or  
15 to 20 psig for summer months.  
Table 24 — Coaxial Water Pressure Drop  
WATER TEMPERATURE (F)  
UNIT 50PTH, PTV,  
GPM  
30 F  
50 F  
70 F  
90 F  
PTD  
Pressure Drop (psi)  
4.0  
6.0  
7.0  
8.0  
4.0  
6.0  
8.0  
9.0  
5.5  
1.5  
3.1  
4.1  
5.1  
1.2  
2.6  
4.5  
5.7  
1.1  
2.2  
3.9  
4.5  
0.5  
1.9  
3.9  
4.8  
1.3  
2.6  
3.4  
4.3  
1.0  
2.5  
4.2  
5.2  
0.9  
2.1  
3.6  
4.2  
0.3  
1.8  
3.5  
4.3  
1.1  
2.3  
3.0  
3.8  
0.8  
2.3  
4.0  
4.8  
0.8  
2.0  
3.2  
3.8  
0.2  
1.7  
3.2  
3.9  
1.0  
2.1  
2.7  
3.4  
0.6  
2.1  
3.7  
4.4  
0.7  
1.8  
3.1  
3.5  
0.1  
1.6  
2.9  
3.5  
026  
038  
049  
After pressurization, be sure to remove the plug from the  
end of the loop pump motor(s) to allow trapped air to be  
discharged and to ensure the motor housing has been flooded.  
Be sure the loop flow center provides adequate flow through  
the unit by checking pressure drop across the heat exchanger.  
Compare the results to the data in Table 24.  
8.3  
11.0  
12.0  
7.0  
10.5  
14.0  
15.0  
Antifreeze — In areas where entering loop temperatures  
drop below 40 F or where piping will be routed through areas  
subject to freezing, antifreeze is needed.  
064,072  
Alcohols and glycols are commonly used as antifreeze  
agents. Freeze protection should be maintained to 15 F below  
the lowest expected entering loop temperature. For example, if  
the lowest expected entering loop temperature is 30 F, the  
leaving loop temperature would be 22 to 25 F. Therefore, the  
freeze protection should be at 15 F (30 F – 15 F = 15 F).  
An alternative method is to install a flow control device.  
These devices are typically an orifice of plastic material de-  
signed to allow a specified flow rate that are mounted on the  
outlet of the water control valve. Occasionally these valves  
produce a velocity noise that can be reduced by applying some  
back pressure. To accomplish this, slightly close the leaving  
isolation valve of the well water setup.  
IMPORTANT: All alcohols should be pre-mixed and  
pumped from a reservoir outside of the building or  
introduced under water level to prevent fuming.  
WARNING  
To avoid possible injury or death due to electrical shock,  
open the power supply disconnect switch and secure it in  
an open position before flushing system.  
Calculate the total volume of fluid in the piping system. See  
Table 25. Use the percentage by volume in Table 26 to deter-  
mine the amount of antifreeze to use. Antifreeze concentration  
should be checked from a well-mixed sample using a hydrom-  
eter to measure specific gravity.  
FREEZE PROTECTION SELECTION — The 30 F FP1  
factory setting (water) should be used to avoid freeze damage  
to the unit.  
Flushing — Once the piping is complete, units require final  
purging and loop charging. A flush cart pump of at least 1.5 hp  
is needed to achieve adequate flow velocity in the loop to purge  
air and dirt particles from the loop. Flush the loop in both direc-  
tions with a high volume of water at a high velocity. Follow the  
steps below to properly flush the loop:  
Once antifreeze is selected, the JW3 jumper (FP1) should  
be clipped on the control to select the low temperature (anti-  
freeze 13 F) set point to avoid nuisance faults.  
1. Verify power is off.  
2. Fill loop with water from hose through flush cart before  
using flush cart pump to ensure an even fill. Do not allow  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 25 — Approximate Fluid Volume (gal.)  
per 100 Ft of Pipe  
HEATING STAGE 2 — To enter Stage 2 mode, terminal W is  
active (Y is already active). Also, the G terminal must be  
active or the W terminal is disregarded. The compressor relay  
will remain on and EH1 is immediately turned on. EH2 will  
turn on after 10 minutes of continual stage 2 demand.  
NOTE: EH2 will not turn on (or if on, will turn off) if FP1 tem-  
perature is greater than 45 F and FP2 is greater than 110 F.  
LOCKOUT MODE — The status LED will flash fast in  
Lockout mode and the compressor relay will be turned off  
immediately. Lockout mode can be “soft” reset via the Y input  
or can be “hard” reset via the disconnect. The last fault causing  
the lockout is stored in memory and can be viewed by entering  
test mode.  
PIPE  
DIAMETER (in.)  
VOLUME (gal.)  
Copper  
1
1.25  
1.5  
4.1  
6.4  
9.2  
Rubber Hose  
Polyethylene  
1
3.9  
3
/ IPS SDR11  
2.8  
4.5  
8.0  
10.9  
18.0  
8.3  
10.9  
17.0  
4
1 IPS SDR11  
1
1 / IPS SDR11  
4
1
/ IPS SDR11  
2
2 IPS SDR11  
1
1
1 / IPS SCH40  
4
2
1 / IPS SCH40  
2 IPS SCH40  
LEGEND  
LOCKOUT WITH EMERGENCY HEAT — While in Lock-  
out mode, if W becomes active, then Emergency Heat mode  
will occur.  
IPS  
Internal Pipe Size  
SCH — Schedule  
SDR — Standard Dimensional Ratio  
EMERGENCY HEAT — In Emergency Heat mode, terminal  
W is active while terminal Y is not. Terminal G must be active  
or the W terminal is disregarded. EH1 is immediately turned  
on. EH2 will turn on after 5 minutes of continual emergency  
heat demand.  
NOTE: Volume of heat exchanger is approximately 1.0 gallon.  
Table 26 — Antifreeze Percentages by Volume  
MINIMUM TEMPERATURE FOR  
FREEZE PROTECTION (F)  
ANTIFREEZE  
Methanol (%)  
Units with Aquazone Deluxe D Control  
10  
15  
20  
25  
10  
25  
21  
16  
EXTENDED COMPRESSOR OPERATION MONITOR —  
If the compressor has been on for 4 continuous hours the con-  
trol will automatically turn off the compressor relay and wait  
the short cycle time protection time. All appropriate safeties,  
including the low-pressure switch, will be monitored. If all  
operations are normal and the compressor demand is still pres-  
ent, the control will turn the compressor back on.  
STANDBY/FAN ONLY — The compressor will be off. The  
Fan Enable, Fan Speed, and reversing valve (RV) relays will be  
on if inputs are present. If there is a Fan 1 demand, the Fan  
Enable will immediately turn on. If there is a Fan 2 demand,  
the Fan Enable and Fan Speed will immediately turn on.  
100% USP Food Grade  
38  
29  
30  
25  
22  
20  
15  
14  
Propylene Glycol (%)  
Ethenol  
Cooling Tower/Boiler Systems These systems  
typically use a common loop temperature maintained at 60 to  
95 F. Carrier recommends using a closed circuit evaporative  
cooling tower with a secondary heat exchanger between the  
tower and the water loop. If an open type cooling tower is used  
continuously, chemical treatment and filtering will be necessary.  
Ground Coupled, Closed Loop and Plateframe  
Heat Exchanger Well Systems — These systems al-  
low water temperatures from 30 to 110 F. The external loop  
field is divided up into 2 in. polyethylene supply and return  
lines. Each line has valves connected in such a way that upon  
system start-up, each line can be isolated for flushing using  
only the system pumps. Locate air separation in the piping sys-  
tem prior to the fluid re-entering the loop field.  
NOTE: DIP switch 5 on S1 does not have an effect upon Fan 1  
and Fan 2 outputs.  
HEATING STAGE 1 — In Heating Stage 1 mode, the Fan  
Enable and Compressor relays are turned on immediately.  
Once the demand is removed, the relays are turned off and the  
control reverts to Standby mode. If there is a master/slave or  
dual compressor application, all compressor relays and related  
functions will operate per their associated DIP switch 2 setting  
on S1.  
OPERATION  
Power Up Mode — The unit will not operate until all the  
inputs, terminals and safety controls are checked for normal  
operation.  
NOTE: The compressor will have a 5-minute anti-short cycle  
upon power up.  
HEATING STAGE 2 — In Heating Stage 2 mode, the Fan  
Enable and Compressor relays are remain on. The Fan Speed  
relay is turned on immediately and turned off immediately  
once the demand is removed. The control reverts to Heating  
Stage 1 mode. If there is a master/slave or dual compressor  
application, all compressor relays and related functions will  
operate per their associated DIP switch 2 setting on S1.  
Units with Aquazone™ Complete C Control  
STANDBY — Y and W terminals are not active in Standby  
mode, however the O and G terminals may be active, depend-  
ing on the application. The compressor will be off.  
COOLING — Y and O terminals are active in Cooling mode.  
After power up, the first call to the compressor will initiate a  
5 to 80 second random start delay and a 5-minute anti-short  
cycle protection time delay. After both delays are complete, the  
compressor is energized.  
NOTE: On all subsequent compressor calls the random start  
delay is omitted.  
HEATING STAGE 1 — Terminal Y is active in heating  
stage 1. After power up, the first call to the compressor will  
initiate a 5 to 80 second random start delay and a 5-minute  
anti-short cycle protection time delay. After both delays are  
complete, the compressor is energized.  
HEATING STAGE 3 — In Heating Stage 3 mode, the Fan  
Enable, Fan Speed and Compressor relays remain on. The EH1  
output is turned on immediately. With continuing Heat Stage 3  
demand, EH2 will turn on after 10 minutes. EH1 and EH2 are  
turned off immediately when the Heating Stage 3 demand is re-  
moved. The control reverts to Heating Stage 2 mode.  
The output signal EH2 will be off if FP1 is greater than 45 F  
AND FP2 (when shorted) is greater than 110 F during Heating  
Stage 3 mode. This condition will have a 30-second recogni-  
tion time. Also, during Heating Stage 3 mode, EH1, EH2, Fan  
Enable, and Fan Speed will be ON if G input is not active.  
EMERGENCY HEAT — In Emergency Heat mode, the Fan  
Enable and Fan Speed relays are turned on. The EH1 output is  
turned on immediately. With continuing Emergency Heat de-  
mand, EH2 will turn on after 5 minutes. Fan Enable and Fan  
Speed relays are turned off after a 60-second delay. The control  
reverts to Standby mode.  
NOTE: On all subsequent compressor calls the random start  
delay is omitted.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Output EH1, EH2, Fan Enable, and Fan Speed will be ON if  
the G input is not active during Emergency Heat mode.  
Occupancy Input Contact — The WSHP Open controller has  
the capability to use an external dry contact closure to deter-  
mine the occupancy status of the unit. The Occupancy Sched-  
ules will need to be disabled in order to utilize the occupancy  
contact input.  
COOLING STAGE 1 — In Cooling Stage 1 mode, the Fan  
Enable, compressor and RV relays are turned on immediately.  
If configured as stage 2 (DIP switch set to OFF) then the com-  
pressor and fan will not turn on until there is a stage 2 demand.  
The Fan Enable and compressor relays are turned off immedi-  
ately when the Cooling Stage 1 demand is removed. The con-  
trol reverts to Standby mode. The RV relay remains on until  
there is a heating demand. If there is a master/slave or dual  
compressor application, all compressor relays and related func-  
tions will track with their associated DIP switch 2 on S1.  
COOLING STAGE 2 — In Cooling Stage 2 mode, the Fan  
Enable, compressor and RV relays remain on. The Fan Speed  
relay is turned on immediately and turned off immediately  
once the Cooling Stage 2 demand is removed. The control  
reverts to Cooling Stage 1 mode. If there is a master/slave or  
dual compressor application, all compressor relays and related  
functions will track with their associated DIP switch 2 on S1.  
NIGHT LOW LIMIT (NLL) STAGED HEATING — In NLL  
staged Heating mode, the override (OVR) input becomes ac-  
tive and is recognized as a call for heating and the control will  
immediately go into a Heating Stage 1 mode. With an addition-  
al 30 minutes of NLL demand, the control will go into Heating  
Stage 2 mode. With another additional 30 minutes of NLL  
demand, the control will go into Heating Stage 3 mode.  
NOTE: Scheduling can only be controlled from one source.  
BAS (Building Automation System) On/Off  
A
BAS  
system that supports network scheduling can control the unit  
through a network communication and the BAS scheduling  
function once the Occupancy Schedules have been disabled.  
NOTE: Scheduling can either be controlled via the unit or the  
BAS, but not both.  
INDOOR FAN — The indoor fan will operate in any one of  
three modes depending on the user configuration selected.  
Fan mode can be selected as Auto, Continuous, or Always  
On. In Auto mode, the fan is in intermittent operation during  
both occupied and unoccupied periods. Continuous fan mode  
is intermittent during unoccupied periods and continuous dur-  
ing occupied periods. Always On mode operates the fan con-  
tinuously during both occupied and unoccupied periods. In the  
default mode, Continuous, the fan will be turned on whenever  
any one of the following is true:  
• The unit is in occupied mode as determined by its occu-  
pancy status.  
• There is a demand for cooling or heating in the unoccu-  
pied mode.  
• There is a call for dehumidification (optional).  
When power is reapplied after a power outage, there will be  
a configured time delay of 5 to 600 seconds before starting the  
fan. There are also configured fan delays for Fan On and Fan  
Off. The Fan On delay defines the delay time (0 to 30 seconds;  
default 10) before the fan begins to operate after heating or  
cooling is started while the Fan Off delay defines the delay  
time (0 to 180 seconds; default 45) the fan will continue to op-  
erate after heating or cooling is stopped. The fan will continue  
to run as long as the compressors, heating stages, or the dehu-  
midification relays are on. If the SPT failure alarm or conden-  
sate overflow alarm is active; the fan will be shut down imme-  
diately regardless of occupancy state or demand.  
Automatic Fan Speed Control — The WSHP Open controller  
is capable of controlling up to three fan speeds using the ECM  
(electronically commutated motor). The motor will operate at  
the lowest speed possible to provide quiet and efficient fan op-  
eration with the best latent capability. The motor will increase  
speed if additional cooling or heating is required to obtain the  
desired space temperature set point. The control increases the  
motor's speed as the space temperature rises above the cooling  
or below the heating set point. The amount of space tempera-  
ture increase above or below the set point required to increase  
the fan speed is user configurable in the set point.  
Units with WSHP Open Multiple Protocol —  
The WSHP Open multi-protocol controller will control me-  
chanical cooling, heating and waterside economizer outputs  
based on its own space temperature input and set points. An  
optional CO IAQ (indoor air quality) sensor mounted in the  
2
space can maximize the occupant comfort. The WSHP Open  
controller has its own hardware clock that is automatically set  
when the heat pump software is downloaded to the board. Oc-  
cupancy types are described in the scheduling section below.  
The following sections describe the functionality of the WSHP  
Open multi-protocol controller. All point objects referred to in  
this sequence of operation will be referenced to the objects as  
6
viewed in the BACview handheld user interface.  
SCHEDULING — Scheduling is used to start/stop the unit  
based on a time period to control the space temperature to spec-  
ified occupied heating and cooling set points. The controller is  
defaulted to control by occupied set points all the time, until ei-  
6
ther a time schedule is configured with BACview , Field Assis-  
®
tant, i-Vu Open, or a third party control system to enable/dis-  
able the BAS (Building Automation System) on/off point. The  
local time and date must be set for these functions to operate  
properly. The occupancy source can be changed to one of the  
following:  
Occupancy Schedules — The controller will be occupied 24/7  
until a time schedule has been configured using either Field  
The Low Fan speed range is configured by the width of the  
Yellow (for cooling) and Light Blue (for heating) setpoint  
bands. The fan will operate at low speed as long as the space  
temperature remains within the yellow or light blue band  
range. The Medium Fan speed range is determined by the Or-  
ange and Dark Blue setpoint band. The fan will operate at me-  
dium speed when the space temperature enters this range. If the  
space temperature rises or falls into the red range, the fan will  
operate at High Fan speed.  
6
Assistant, i-Vu Open, BACview or a third party control sys-  
tem to enable/disable the BAS on/off point. The BAS point can  
be disabled by going to Config, then Unit, then Occupancy  
Schedules and changing the point from enable to disable then  
clicking OK.  
NOTE: This point must be enabled in order for the i-Vu Open,  
6
Field Assistant, or BACview control system to assign a time  
schedule to the controller.  
Schedule_schedule — The unit will operate according to the  
schedule configured and stored in the unit. The schedule is  
As the temperature returns toward setpoint, a configurable  
hysteresis is used to prevent the fan from changing speeds er-  
ratically. The default value is 0.5° F (shown above).  
Also, the control will increase the fan speed as the Supply  
Air Temperature approaches the configured Minimum or Max-  
imum SAT limits.  
Fan Speed Control (During Heating) — Whenever heat is re-  
quired and active, the control continuously monitors the sup-  
ply-air temperature to verify it does not rise above the config-  
6
accessible via the BACview Handheld tool, i-Vu Open, or  
Field Assistant control system. The daily schedule consists of a  
start/stop time (standard or 24-hour mode) and seven days of  
the week, starting with Monday and ending on Sunday. To  
enter a daily schedule, navigate to Config, then Sched, then  
6
enter BACview Admin Password (1111), then go to  
schedule_schedule. From here, enter either a Weekly or Excep-  
tion schedule for the unit.  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ured maximum heating SAT limit (110 F default). As the SAT  
approaches this value, the control will increase the fan speed as  
required to ensure the SAT will remain within the limit. This  
feature provides the most quiet and efficient operation by oper-  
ating the fan at the lowest speed possible.  
Fan Speed Control (During Cooling) — Whenever mechani-  
cal cooling is required and active, the control continuously  
monitors the supply-air temperature to verify it does not fall be-  
low the configured minimum cooling SAT limit (50 F default).  
As the SAT approaches this value, the control will increase the  
fan speed as required to ensure the SAT will remain within the  
limit. The fan will operate at lowest speed to maximize latent  
capacity during cooling.  
COOLING — The WSHP Open controller will operate one or  
two stages of compression to maintain the desired cooling set  
point. The compressor outputs are controlled by the PI (propor-  
tional-integral) cooling loop and cooling stages capacity algo-  
rithm. They will be used to calculate the desired number of  
stages needed to satisfy the space by comparing the space tem-  
perature (SPT) to the appropriate cooling set point. The water  
side economizer, if applicable, will be used for first stage cool-  
ing in addition to the compressor(s). The following conditions  
must be true in order for the cooling algorithm to run:  
HEATING — The WSHP Open controller will operate one or  
two stages of compression to maintain the desired heating set  
point. The compressor outputs are controlled by the heating PI  
(proportional-integral) loop and heating stages capacity algo-  
rithm. They will be used to calculate the desired number of  
stages needed to satisfy the space by comparing the space tem-  
perature (SPT) to the appropriate heating set point. The follow-  
ing conditions must be true in order for the heating algorithm to  
run:  
• Heating is set to Enable.  
• Cooling mode is not active and the compressor time  
guard has expired.  
• Condensate overflow input is normal.  
• If occupied, the SPT is less than the occupied heating set  
point.  
• Space temperature reading is valid.  
• If unoccupied, the SPT is less than the unoccupied heat-  
ing set point.  
• OAT (if available) is less than the heating lockout  
temperature.  
If all the above conditions are met, the heating outputs will  
be energized as required, otherwise they will be deenergized. If  
the heating is active and should the SAT approach the maxi-  
mum SAT limit, the fan will be indexed to the next higher  
speed. Should this be insufficient, and the SAT rises further  
reaching the maximum heating SAT limit, the fan will be  
indexed to the maximum speed. If the SAT still continues to  
rise 5F above the maximum limit, all heating stages will be  
disabled.  
• Cooling is set to Enable.  
• Heating mode is not active and the compressor time  
guard has expired.  
• Condensate overflow input is normal.  
• If occupied, the SPT is greater than the occupied cooling  
set point.  
• Space temperature reading is valid.  
• If unoccupied, the SPT is greater than the unoccupied  
cooling set point.  
• If economizer cooling is available and active and the  
economizer alone is insufficient to provide enough cool-  
ing.  
• OAT (if available) is greater than the cooling lockout  
temperature.  
During Heating mode, the reversing valve output will be  
held in the heating position (either B or O type as configured)  
even after the compressor is stopped. The valve will not switch  
position until the Cooling mode is required.  
The configuration screens contain the maximum SAT  
parameter as well as heating lockout based on outdoor-air  
temperature (OAT); both can be adjusted to meet various  
specifications.  
If all the above conditions are met, the compressors will be  
energized as required, otherwise they will be deenergized. If  
cooling is active and should the SAT approach the minimum  
SAT limit, the fan will be indexed to the next higher speed.  
Should this be insufficient and if the SAT falls further (equal to  
the minimum SAT limit), the fan will be indexed to the maxi-  
mum speed. If the SAT continues to fall 5F below the mini-  
mum SAT limit, all cooling stages will be disabled.  
During Cooling mode, the reversing valve output will be  
held in the cooling position (either B or O type as configured)  
even after the compressor is stopped. The valve will not switch  
position until the Heating mode is required.  
The configuration screens contain the minimum SAT  
parameter as well as cooling lockout based on outdoor-air  
temperature (OAT) Both can be adjusted to meet various  
specifications.  
There is a 5-minute off time for the compressor as well as a  
5-minute time delay when staging up to allow the SAT to  
achieve a stable temperature before energizing a second stage  
of capacity. Likewise, a 45-second delay is used when staging  
down.  
After a compressor is staged off, it may be restarted again  
after a normal time-guard period of 5 minutes and if the sup-  
ply-air temperature has increased above the minimum supply-  
air temperature limit.  
The WSHP Open controller provides a status input to moni-  
tor the compressor operation. The status is monitored to deter-  
mine if the compressor status matches the commanded state.  
This input is used to determine if a refrigerant safety switch or  
other safety device has tripped and caused the compressor to  
stop operating normally. If this should occur, an alarm will be  
generated to indicate the faulted compressor condition.  
There is a 5-minute off time for the compressor as well as a  
5-minute time delay when staging up to allow the SAT to  
achieve a stable temperature before energizing a second stage  
of capacity. Likewise, a 45-second delay is used when staging  
down.  
After a compressor is staged off, it may be restarted again  
after a normal time-guard period of 5 minutes and if the sup-  
ply-air temperature has fallen below the maximum supply air  
temperature limit.  
The WSHP Open controller provides a status input to moni-  
tor the compressor operation. The status is monitored to deter-  
mine if the compressor status matches the commanded state.  
This input is used to determine if a refrigerant safety switch or  
other safety device has tripped and caused the compressor to  
stop operating normally. If this should occur, an alarm will be  
generated to indicate the faulted compressor condition. Also, if  
auxiliary heat is available (see below), the auxiliary heat will  
operate to replace the reverse cycle heating and maintain the  
space temperature as required.  
AUXILIARY HEAT — The WSHP Open controller can con-  
trol a two-position, modulating water, or steam valve connect-  
ed to a coil on the discharge side of the unit and supplied by a  
boiler or a single-stage ducted electric heater in order to main-  
tain the desired heating set point. Should the compressor capac-  
ity be insufficient or a compressor failure occurs, the auxiliary  
heat will be used. Unless the compressor fails, the auxiliary  
heat will only operate to supplement the heat provided by the  
compressor if the space temperature falls more than one degree  
below the desired heating set point (the amount is configu-  
rable). The heat will be controlled so the SAT will not exceed  
the maximum heating SAT limit.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Auxiliary Modulating Hot Water/Steam Heating Reheat  
— The control can modulate a hot water or steam valve con-  
nected to a coil on the discharge side of the unit and supplied  
by a boiler in order to maintain the desired heating set point  
should the compressor capacity be insufficient or a compressor  
failure occurs. Unless a compressor fault condition exists, the  
valve will only operate to supplement the heat provided by the  
compressor if the space temperature falls more than one degree  
below the desired heating set point. The valve will be con-  
trolled so the SAT will not exceed the maximum heating SAT  
limit.  
Two-Position Hot Water/Steam Heating Reheat The con-  
trol can operate a two-position, NO or NC, hot water or steam  
valve connected to a coil on the discharge side of the unit and  
supplied by a boiler in order to maintain the desired heating set  
point should the compressor capacity be insufficient or a com-  
pressor failure occurs. Unless a compressor fault condition ex-  
ists, the valve will only open to supplement the heat provided  
by the compressor if the space temperature falls more than one  
degree below the desired heating set point. The valve will be  
controlled so the SAT will not exceed the maximum heating  
SAT limit. The heat stage will also be subject to a 2-minute  
minimum OFF time to prevent excessive valve cycling.  
Single Stage Electric Auxiliary Heat — The control can op-  
erate a field-installed single stage of electric heat installed on  
the discharge side of the unit in order to maintain the desired  
heating set point should the compressor capacity be insufficient  
or a compressor failure occurs. Unless a compressor fault con-  
dition exists, the heat stage will only operate to supplement the  
heat provided by the compressor if the space temperature falls  
more than one degree below the desired heating set point. The  
heat stage will be controlled so the SAT will not exceed the  
maximum heating SAT limit. The heat stage will also be sub-  
ject to a 2-minute minimum OFF time to prevent excessive  
cycling.  
units that are equipped with the modulating hot water reheat  
(HWR) option. This function requires an accessory space rela-  
tive humidity sensor. When using a relative humidity sensor to  
control dehumidification during occupied or unoccupied times,  
the dehumidification set points are used accordingly. When the  
indoor relative humidity becomes greater than the dehumidifi-  
cation set point, a dehumidification demand will be acknowl-  
edged. Once acknowledged, the dehumidification output will  
be energized, bringing on the supply fan (medium speed), me-  
chanical cooling, and the integral hot water reheat coil. The  
controls will engage Cooling mode and waste heat from the  
compressor cooling cycle will be returned to the reheat coil si-  
multaneously, meaning that the reversing valve is causing the  
compressor to operate in the Cooling mode. During Cooling  
mode, the unit cools, dehumidifies, and disables the HWR coil;  
however, once the call for cooling has been satisfied and there  
is still a call for dehumidification, the unit will continue to op-  
erate using the reheat mode and HWR coil.  
WATERSIDE ECONOMIZER — The WSHP Open control-  
ler has the capability of providing modulating or two-position  
water economizer operation (for a field-installed economizer  
coil mounted to the entering air side of the unit and connected  
to the condenser water loop) in order to provide free cooling  
(or preheating) when water conditions are optimal. Water econ-  
omizer settings can be accessed through the equipment status  
screen. The following conditions must be true for economizer  
operation:  
• SAT reading is available.  
• LWT reading is available.  
• If occupied, the SPT is greater than the occupied cooling  
set point or less than the occupied heating set point and  
the condenser water is suitable.  
• Space temperature reading is valid.  
• If unoccupied, the SPT is greater than the unoccupied  
cooling set point or less than the unoccupied heating set  
point and the condenser water is suitable.  
INDOOR AIR QUALITY (IAQ) AND DEMAND CON-  
TROLLED VENTILATION (DCV) — If the optional in-  
door air quality sensor is installed, the WSHP Open controller  
can maintain indoor air quality via a modulating OA damper  
providing demand controlled ventilation. The control operates  
the modulating OA damper during occupied periods. The con-  
Modulating Water Economizer Control — The control has  
the capability to modulate a water valve to control condenser  
water flowing through a coil on the entering air side of the unit.  
Cooling — The purpose is to provide an economizer cooling  
function by using the water loop when the entering water loop  
temperature is suitable (at least 5F below space temperature).  
If the water loop conditions are suitable, then the valve will  
modulate open as required to maintain a supply-air temperature  
that meets the load conditions. Should the economizer coil ca-  
pacity alone be insufficient for a period greater than 5 minutes,  
or should a high humidity condition occur, then the compressor  
will also be started to satisfy the load. Should the SAT ap-  
proach the minimum cooling SAT limit, the economizer valve  
will modulate closed during compressor operation.  
Heating — Additionally, the control will modulate the water  
valve should the entering water loop temperature be suitable  
for heating (at least 5F above space temperature) and heat is  
required. The valve will be controlled in a similar manner ex-  
cept to satisfy the heating requirement. Should the economizer  
coil capacity alone be insufficient to satisfy the space load con-  
ditions for more than 5 minutes, then the compressor will be  
started to satisfy the load. Should the SAT approach the maxi-  
mum heating SAT limit, the economizer valve will modulate  
closed during compressor operation.  
trol monitors the CO level and compares it to the configured  
2
set points, adjusting the ventilation rate as required. The control  
provides proportional ventilation to meet the requirements of  
ASHRAE (American Society of Heating, Refrigerating and  
Air Conditioning Engineers) specifications by providing a base  
ventilation rate and then increasing the rate as the CO level in-  
2
creases. The control will begin to proportionally increase venti-  
lation when the CO level rises above the start ventilation set  
2
point and will reach the full ventilation rate when the CO level  
2
is at or above the maximum set point. A user-configurable min-  
imum damper position ensures that proper base ventilation is  
delivered when occupants are not present. The IAQ configura-  
tions can be accessed through the configuration screen. The  
following conditions must be true in order for this algorithm to  
run:  
• Damper control is configured for DCV.  
• The unit is in an occupied mode.  
• The IAQ sensor reading is greater than the DCV start  
control set point.  
The control has four user adjustable set points: DCV start  
control set point, DCV maximum control set point, minimum  
damper position, and DCV maximum damper position.  
Two-Position OA Damper — The control can be configured  
to operate a ventilation damper in a two-position ventilation  
mode to provide the minimum ventilation requirements during  
occupied periods.  
Two-Position Water Economizer Control — The control has  
the capability to control a NO or NC, two-position water valve  
to control condenser water flow through a coil on the entering  
air side of the unit.  
Cooling — The purpose is to provide a cooling economizer  
function directly from the condenser water loop when the en-  
tering water loop temperature is suitable (at least 5F below  
space temperature). If the optional coil is provided and the wa-  
ter loop conditions are suitable, then the valve will open to pro-  
DEHUMIDIFCATION — The WSHP Open controller will  
provide occupied and unoccupied dehumidification only on  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
vide cooling to the space when required. Should the capacity  
be insufficient for a period greater than 5 minutes, or should a  
high humidity condition occur, then the compressor will be  
started to satisfy the load. Should the SAT reach the minimum  
cooling SAT limit, the economizer valve will close during  
compressor operation.  
Heating — Additionally, the economizer control will open the  
water valve should the entering water loop temperature be suit-  
able for heating (at least 5F above space temperature) and  
heat is required. The valve will be controlled in a similar man-  
ner except to satisfy the heating requirement. Should the coil  
capacity be insufficient to satisfy the space load for more than  
5 minutes, then the compressor will be started to satisfy the  
load. Should the SAT reach the maximum heating SAT limit,  
the economizer valve will close during compressor operation.  
Table 27 — Complete C Control Current LED  
Status and Alarm Relay Operations  
LED STATUS  
DESCRIPTION OF OPERATION  
ALARM RELAY  
Normal Mode  
Open  
Cycle  
(closed 5 sec.,  
open 25 sec.)  
On  
Normal Mode with  
PM Warning  
Complete C Control is  
non-functional  
Off  
Open  
Slow Flash  
Fast Flash  
Fault Retry  
Lockout  
Open  
Closed  
Open,  
(Closed after  
15 minutes)  
Slow Flash  
Over/Under Voltage Shutdown  
Flashing Code 1 Test Mode — No fault in memory  
Cycling Code 1  
Test Mode —  
HP Fault in memory  
Flashing Code 2  
Cycling Code 2  
Test Mode —  
DEMAND LIMIT — The WSHP Open controller has the  
ability to accept three levels of demand limit from the network.  
In response to a demand limit, the unit will decrease its heating  
set point and increase its cooling set point to widen the range in  
order to immediately lower the electrical demand. The amount  
of temperature adjustment in response is user adjustable for  
both heating and cooling and for each demand level. The re-  
sponse to a particular demand level may also be set to zero.  
Flashing Code 3  
Cycling Code 3  
Cycling Code 4  
Cycling Code 5  
Cycling Code 6  
LP Fault in memory  
Test Mode —  
FP1 Fault in memory  
Test Mode —  
FP2 Fault in memory  
Test Mode —  
CO Fault in memory  
Test Mode — Over/Under  
shutdown in memory  
Flashing Code 4  
Flashing Code 5  
Flashing Code 6  
Flashing Code 7  
Cycling Code 7  
Cycling Code 8  
Cycling Code 9  
Flashing Code 8  
Flashing Code 9  
Test Mode — PM in memory  
Test Mode — FP1/FP2  
Swapped Fault in memory  
CONDENSER WATER LINKAGE — The control pro-  
vides optimized water loop operation using an universal con-  
troller (UC) open loop controller. Loop pump operation is auto-  
matically controlled by WSHP equipment occupancy sched-  
ules, unoccupied demand and tenant override conditions.  
Positive pump status feedback prevents nuisance fault trips.  
The condenser water linkage operates when a request for con-  
denser water pump operation is sent from each WSHP to the  
loop controller. This request is generated whenever any WSHP  
is scheduled to be occupied, is starting during optimal start (for  
warm-up or pull down prior to occupancy), there is an unoccu-  
pied heating or cooling demand, or a tenant pushbutton over-  
ride. At each WSHP, the water loop temperature and the loop  
pump status is given. The WSHP will NOT start a compressor  
until the loop pumps are running or will shutdown the com-  
pressors should the pumps stop. This prevents the WSHP from  
operating without water flow and thus tripping out on refriger-  
ant pressure, causing a lockout condition. The WSHP Open  
controller control will prevent this from occurring. Also, the  
loop controller can be configured to start the pumps only after a  
configurable number of WSHPs are requesting operation (from  
1-"N"). This can be used to prevent starting the entire loop op-  
eration for only one WSHP. Meanwhile, the WSHPs will not  
operate if the loop pump status is off and therefore the WSHP  
compressor will not run.  
LEGEND  
CO  
FP  
Condensate Overflow  
Freeze Protection  
High Pressure  
Light-Emitting Diode  
Low Pressure  
Performance Monitor  
HP  
LED  
LP  
PM  
NOTES:  
1. Slow flash is 1 flash every 2 seconds.  
2. Fast flash is 2 flashes every 1 second.  
3. EXAMPLE: “Flashing Code 2is represented by 2 fast flashes followed by  
a 10-second pause. This sequence will repeat continually until the fault is  
cleared.  
Table 28 — Complete C Control LED Code and  
Fault Descriptions  
LED  
CODE  
1
FAULT  
DESCRIPTION  
No fault in memory  
There has been no fault since  
the last power-down to power-  
up sequence  
HP switch opens instantly  
LP switch opens for  
30 continuous seconds before  
or during a call (bypassed for  
first 60 seconds)  
FP1 below Temp limit for  
30 continuous seconds  
(bypassed for first 60 seconds of  
operation)  
2
3
High-Pressure Switch  
Low-Pressure Switch  
4
5
Freeze Protection Coax  
— FP1  
COMPLETE C AND DELUXE D BOARD  
SYSTEM TEST  
Freeze Protection Air Coil — FP2 below Temp limit for  
FP2  
30 continuous seconds  
(bypassed for first 60 seconds of  
operation)  
Sense overflow (grounded) for  
30 continuous seconds  
"R" power supply is <19VAC or  
>30VAC  
Performance Monitor Warning  
has occurred.  
Test mode provides the ability to check the control opera-  
tion in a timely manner. The control enters a 20-minute test  
mode by momentarily shorting the test terminals. All time de-  
lays are sped up 15 times. The following operations are com-  
mon to both Complete C and Deluxe D controls.  
6
7
Condensate overflow  
Over/Under Voltage  
(Autoreset) Shutdown  
8
PM Warning  
Test Mode — To enter Test mode, cycle the fan 3 times  
within 60 seconds. The LED will flash a code representing the  
last fault when entering the Test mode. The alarm relay will  
also power on and off during Test mode. See Tables 27 and 28.  
To exit Test mode, short the terminals for 3 seconds or cycle  
the fan 3 times within 60 seconds.  
NOTE: The flashing code and alarm relay cycling code will  
both have the same numerical label. For example, flashing  
code 1 will have an alarm relay cycling code 1. Code 1 indi-  
cates the control has not faulted since the last power off to  
power on sequence.  
9
FP1 and FP2  
FP1 temperature is higher than  
FP2 in heating/test mode, or  
FP2 temperature is higher than  
FP1 in cooling/test mode.  
Thermistors are swapped  
LEGEND  
FP  
Freeze Protection  
High Pressure  
HP  
LED  
LP  
Light-Emitting Diode  
Low Pressure  
PM  
Performance Monitor  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Once tests are complete, set unit test back to disable. Unit will  
automatically reset to disable after 1 hour.  
WSHP Open Test Mode — To enter WSHP Open test  
6
mode, navigate from the BACview home screen to the config-  
uration screen. Choose the service screen and enable unit test.  
The controller will then test the following:  
FAN TEST — Tests all fan speeds, sequences fan from low to  
high, and operates each speed for one minute. Resets to disable  
on completion.  
COMPRESSOR TEST — Tests compressor cooling and  
heating operation. Sequences cooling stage 1 then cooling  
stage 2 followed by heating stage 2 then reduces capacity to  
heating stage 1. Operates for 1 minute per step.  
DEHUMIDIFICATION TEST — Tests dehumidification  
mode. Operates for 2 minutes.  
Retry Mode — In Retry mode, the status LED will start to  
flash slowly to signal that the control is trying to recover from  
an input fault. The control will stage off the outputs and try to  
again satisfy the thermostat used to terminal Y. Once the ther-  
mostat input calls are satisfied, the control will continue normal  
operation.  
NOTE: If 3 consecutive faults occur without satisfying the  
thermostat input call to terminal Y, the control will go into  
lockout mode. The last fault causing the lockout is stored in  
memory and can be viewed by entering Test mode.  
Aquazone™ Deluxe D Control LED Indica-  
tors — There are 3 LED indicators on the Deluxe D control:  
STATUS LED — Status LED indicates the current status or  
mode of the D control. The Status LED light is green.  
TEST LED — Test LED will be activated any time the D  
control is in test mode. The Test LED light is yellow.  
FAULT LED — Fault LED light is red. The fault LED will  
always flash a code representing the last fault in memory. If  
there is no fault in memory, the fault LED will flash code 1 and  
appear as one fast flash alternating with a 10-second pause.  
See Table 29.  
AUXILIARY HEATING TEST — Tests auxiliary heat.  
Sequences fan on and enables heating coil for 1 minute.  
H O ECONOMIZER TEST — Tests entering/returning  
2
water loop economizer operation. Sequences fan and opens  
economizer water valve for one minute.  
OPEN VENT DAMPER 100% TEST — Tests outside air  
(OA) damper operation.  
PREPOSITION OA DAMPER — Prepositions OA damper  
actuator to set proper preload.  
NOTE: The auxiliary heating test, H O economizer test, open  
2
vent damper 100% test, and preposition OA damper features  
will not be visible on the screen unless configured.  
Table 29 — Aquazone Deluxe D Control Current LED Status and Alarm Relay Operations  
STATUS LED  
(Green)  
TEST LED  
(Yellow)  
DESCRIPTION  
Normal Mode  
FAULT LED (Red)  
Flash Last Fault Code in Memory  
Flashing Code 8  
ALARM RELAY  
On  
Off  
Open  
Cycle (closed 5 sec,  
open 25 sec, …)  
Normal Mode with PM  
On  
Off  
Deluxe D Control  
is non-functional  
Off  
Off  
Off  
Open  
Test Mode  
Night Setback  
ESD  
On  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flash Last Fault Code in Memory  
Flashing Code 1  
Cycling Appropriate Code  
Flashing Code 2  
Flashing Code 3  
Flashing Code 4  
On  
Open  
Open  
Open  
Open  
Open  
Invalid T-stat Inputs  
No Fault in Memory  
HP Fault  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Off  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Slow Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Fast Flash  
Flashing Code 2  
Flashing Code 3  
Flashing Code 4  
Flashing Code 5  
Flashing Code 6  
Flashing Code 7  
Flashing Code 2  
Flashing Code 3  
LP Fault  
FP1 Fault  
FP2 Fault  
CO Fault  
Open  
Over/Under Voltage  
HP Lockout  
LP Lockout  
FP1 Lockout  
FP2 Lockout  
CO Lockout  
Open (closed after 15 minutes)  
Closed  
Closed  
Closed  
Closed  
Closed  
Flashing Code 4  
Flashing Code 5  
Flashing Code 6  
LEGEND  
NOTES:  
1. If there is no fault in memory, the Fault LED will flash code 1.  
2. Codes will be displayed with a 10-second Fault LED pause.  
3. Slow flash is 1 flash every 2 seconds.  
CO — Condensate Overflow  
ESD — Emergency Shutdown  
FP — Freeze Protection  
HP — High Pressure  
LP — Low Pressure  
PM — Performance Monitor  
4. Fast flash is 2 flashes every 1 second.  
5. EXAMPLE: “Flashing Code 2is represented by 2 fast flashes  
followed by a 10-second pause. This sequence will repeat con-  
tinually until the fault is cleared.  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE  
Compressor — Conduct annual amperage checks to en-  
sure that amp draw is no more than 10% greater than indicated  
on the serial plate data.  
Perform the procedures outlined below periodically, as  
indicated.  
Fan Motors — All units have lubricated fan motors. Fan  
motors should never be lubricated unless obvious, dry  
operation is suspected. Periodic maintenance oiling is NOT  
recommended as it will result in dirt accumulating in the excess  
oil and cause eventual motor failure. Conduct annual dry oper-  
ation check and amperage check to ensure amp draw is no  
more than 10% greater than indicated on serial plate data.  
WARNING  
To prevent injury or death due to electrical shock or contact  
with moving parts, open unit disconnect switch before ser-  
vicing unit.  
IMPORTANT: When a compressor is removed from this  
unit, system refrigerant circuit oil will remain in the com-  
pressor. To avoid leakage of compressor oil, the refrigerant  
lines of the compressor must be sealed after it is removed.  
Condensate Drain Cleaning — Clean the drain line  
and unit drain pan at the start of each cooling season. Check  
flow by pouring water into drain. Be sure trap is filled to main-  
tain an air seal.  
Air Coil Cleaning — Remove dirt and debris from evap-  
orator coil as required by condition of the coil. Clean coil with  
a stiff brush, vacuum cleaner, or compressed air. Use a fin  
comb of the correct tooth spacing when straightening mashed  
or bent coil fins.  
IMPORTANT: All refrigerant discharged from this unit  
must be recovered without exception. Technicians must fol-  
low industry accepted guidelines and all local, state and fed-  
eral statutes for the recovery and disposal of refrigerants.  
Condenser Cleaning — Water-cooled condensers may  
require cleaning of scale (water deposits) due to improperly  
maintained closed-loop water systems. Sludge build-up may  
need to be cleaned in an open water tower system due to  
induced contaminants.  
IMPORTANT: To avoid the release of refrigerant into the  
atmosphere, the refrigerant circuit of this unit must only be  
serviced by technicians who meet local, state and federal  
proficiency requirements.  
Local water conditions may cause excessive fouling or  
pitting of tubes. Condenser tubes should therefore be cleaned at  
least once a year, or more often if the water is contaminated.  
Filters — Filters must be clean for maximum performance.  
Inspect filters every month under normal operating conditions.  
Replace when necessary.  
Proper water treatment can minimize tube fouling and  
pitting. If such conditions are anticipated, water treatment  
analysis is recommended. Refer to the Carrier System Design  
Manual, Part 5, for general water conditioning information.  
IMPORTANT: Units should never be operated without  
a filter.  
Water Coil — Keep all air out of the water coil. Check  
open loop systems to be sure the well head is not allowing air  
to infiltrate the water line. Always keep lines airtight.  
Inspect heat exchangers regularly, and clean more frequent-  
ly if the unit is located in a “dirty” environment. Keep the heat  
exchanger full of water at all times. Open loop systems should  
have an inverted P trap placed in the discharge line to keep  
water in the heat exchanger during off cycles. Closed loop  
systems must have a minimum of 15 psig during the summer  
and 40 psig during the winter.  
CAUTION  
Follow all safety codes. Wear safety glasses and rubber  
gloves when using inhibited hydrochloric acid solution.  
Observe and follow acid manufacturer’s instructions.  
Clean condensers with an inhibited hydrochloric acid solu-  
tion. The acid can stain hands and clothing, damage concrete,  
and, without inhibitor, damage steel. Cover surroundings to  
guard against splashing. Vapors from vent pipe are not harmful,  
but take care to prevent liquid from being carried over by the  
gases.  
Check P trap frequently for proper operation.  
CAUTION  
Warm solution acts faster, but cold solution is just as effec-  
tive if applied for a longer period.  
To avoid fouled machinery and extensive unit clean-up,  
DO NOT operate units without filters in place. DO NOT  
use equipment as a temporary heat source during  
construction.  
GRAVITY FLOW METHOD — Do not add solution faster  
than vent can exhaust the generated gases.  
When condenser is full, allow solution to remain overnight,  
then drain condenser and flush with clean water. Follow acid  
manufacturer’s instructions. See Fig. 35.  
FORCED CIRCULATION METHOD — Fully open vent  
pipe when filling condenser. The vent may be closed when  
condenser is full and pump is operating. See Fig. 36.  
Regulate flow to condenser with a supply line valve. If  
pump is a nonoverloading type, the valve may be fully closed  
while pump is running.  
Condensate Drain Pans — Check condensate drain  
pans for algae growth twice a year. If algae growth is apparent,  
consult a water treatment specialist for proper chemical treat-  
ment. Applying an algaecide every three months will typically  
eliminate algae problems in most locations.  
Refrigerant System — Verify air and water flow rates  
are at proper levels before servicing. To maintain sealed circuit-  
ry integrity, do not install service gages unless unit operation  
appears abnormal.  
Check to see that unit is within the superheat and subcool-  
ing temperature ranges shown in Tables 20-23. If the unit is not  
within these ranges, recover and reweigh in refrigerant charge.  
For average scale deposit, allow solution to remain in con-  
denser overnight. For heavy scale deposit, allow 24 hours.  
Drain condenser and flush with clean water. Follow acid manu-  
facturer’s instructions.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Refrigerant Charging  
WARNING  
FILL CONDENSER WITH  
CLEANING SOLUTION. DO  
NOT ADD SOLUTION  
MORE RAPIDLY THAN  
VENT CAN EXHAUST  
GASES CAUSED BY  
PAIL  
To prevent personal injury, wear safety glasses and gloves  
when handling refrigerant. Do not overcharge system —  
this can cause compressor flooding.  
FUNNEL  
CHEMICAL ACTION.  
1  
PIPE  
NOTE: Do not vent or depressurize unit refrigerant to atmo-  
sphere. Remove and recover refrigerant following accepted  
practices.  
VENT  
PIPE  
5’ APPROX  
3’ TO 4’  
Air Coil Fan Motor Removal  
CAUTION  
CONDENSER  
Before attempting to remove fan motors or motor mounts,  
place a piece of plywood over evaporator coils to prevent  
coil damage.  
Disconnect motor power wires from motor terminals before  
motor is removed from unit.  
1. Shut off unit main power supply.  
PAIL  
Fig. 35 — Gravity Flow Method  
2. Loosen bolts on mounting bracket so that fan belt can be  
removed.  
3. Loosen and remove the 2 motor mounting bracket bolts  
on left side of bracket.  
Slide motor/bracket assembly to extreme right and lift out  
through space between fan scroll and side frame. Rest motor on  
a high platform such as a step ladder. Do not allow motor to  
hang by its power wires.  
GAS VENT  
PUMP  
PRIMING  
CONN.  
GLOBE  
VALVES  
SUCTION  
SUPPLY  
PUMP  
SUPPORT  
1PIPE  
CONDENSER  
Replacing the WSHP Open Controller’s Bat-  
tery — The WSHP Open controller’s 10-year lithium  
CR2032 battery provides a minimum of 10,000 hours of data  
retention during power outages.  
TANK  
REMOVE WATER  
REGULATING VALVE  
RETURN  
NOTE: Power must be ON to the WSHP Open controller  
when replacing the battery, or the date, time and trend data will  
be lost.  
1. Remove the battery from the controller, making note of  
the battery's polarity.  
FINE MESH  
SCREEN  
Fig. 36 — Forced Circulation Method  
Checking System Charge — Units are shipped with  
full operating charge. If recharging is necessary:  
2. Insert the new battery, matching the battery's polarity  
with the polarity indicated on the WSHP Open controller.  
1. Insert thermometer bulb in insulating rubber sleeve on  
liquid line near filter drier. Use a digital thermometer for  
all temperature measurements. DO NOT use a mercury  
or dial-type thermometer.  
TROUBLESHOOTING  
2. Connect pressure gage to discharge line near compressor.  
3. After unit conditions have stabilized, read head pressure  
on discharge line gage.  
When troubleshooting problems with a WSHP, consider the  
following:  
Thermistor — A thermistor may be required for single-  
phase units where starting the unit is a problem due to low  
voltage. See Fig. 37 for thermistor nominal resistance.  
NOTE: Operate unit a minimum of 15 minutes before  
checking charge.  
4. From standard field-supplied Pressure-Temperature chart  
for R-410A refrigerant, find equivalent saturated con-  
densing temperature.  
5. Read liquid line temperature on thermometer; then  
subtract from saturated condensing temperature. The dif-  
ference equals subcooling temperature.  
Control Sensors — The control system employs 2 nom-  
inal 10,000 ohm thermistors (FP1 and FP2) that are used for  
freeze protection. Be sure FP1 is located in the discharge fluid  
and FP2 is located in the air discharge. See Fig. 38.  
6. Compare the subcooling temperature with the normal  
temperature listed in Tables 20-23. If the measured liquid  
line temperature does not agree with the required liquid  
line temperature, ADD refrigerant to raise the tempera-  
ture or REMOVE refrigerant (using standard practices) to  
lower the temperature (allow a tolerance of ± 3° F).  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
important for the most efficient operation of the unit and for the  
life of the compressor.  
Packaged heat pumps typically use one bi-flow TXV to me-  
ter refrigerant in both modes of operation. When diagnosing  
possible TXV problems it may be helpful to reverse the refrig-  
erant flow to assist with the diagnosis.  
90.0  
80.0  
70.0  
60.0  
50.0  
40.0  
30.0  
20.0  
10.0  
0.0  
Geothermal and water source heat pumps are designed to  
operate through a wide range of entering-water temperatures  
that will have a direct effect on the unit refrigerant oper-  
ating pressures. Therefore, diagnosing TXV problems can be  
difficult.  
TXV FAILURE — The most common failure mode of a TXV  
is when the valve fails while closed. Typically, a TXV uses  
spring pressure to close the valve and an opposing pressure,  
usually from a diaphragm, to open the valve. The amount of  
pressure exerted by the diaphragm will vary, depending on the  
pressure inside of the sensing bulb. As the temperature of and  
pressure within the bulb decreases, the valve will modulate  
closed and restrict the refrigerant flow through the valve. The  
result is less refrigerant in the evaporator and an increase in the  
superheat. As the temperature at the bulb increases the dia-  
phragm pressure will increase, which opens the valve and  
allows more refrigerant flow and a reduction in the superheat.  
0.0  
20.0  
40.0  
60.0  
80.0 100.0 120.0 140.0  
Temperature (degF)  
Fig. 37 — Thermistor Nominal Resistance  
WSHP Open Controller — With the WSHP Open con-  
troller option, the 100 most recent alarms can be viewed using  
6
the BACview alarm status and alarm history.  
To view the alarms:  
If the sensing bulb, connecting capillary, or diaphragm  
assembly are damaged, pressure is lost and the spring will force  
the valve to a closed position. Often, the TXV will not close  
completely so some refrigerant flow will remain, even if inade-  
quate flow for the heat pump to operate.  
1. Navigate to the Alarm Status screen from the Home  
screen using the arrow softkeys. The screen will display  
the current alarm status, either normal or Alarm, and al-  
low for scrolling through the unit’s alarm status.  
2. From the Alarm Status screen, press the Alarm softkey to  
view the 100 most recent alarms which are labeled with  
date and time for easy reference.  
The TXV sensing bulb must be properly located, secured,  
and insulated as it will attempt to control the temperature of the  
line to which it is connected. The sensing bulb must be located  
on a dedicated suction line close to the compressor. On a pack-  
aged heat pump, the bulb may be located almost any place on  
the tube running from the compressor suction inlet to the  
reversing valve. If the bulb is located on a horizontal section, it  
should be placed in the 10:00 or 2:00 position for optimal  
performance.  
NOTE: Active faults can be viewed by scrolling down,  
these faults indicate a possible bad sensor or some condi-  
tion which may not merit an alarm.  
3. To view alarms which have been corrected, scroll down  
through the Alarm screen to Return Top Normal screen.  
NOTE: Alarms are automatically reset once alarm con-  
dition has been corrected.  
See Table 32 for possible alarm cause and solution.  
CAUTION  
Use caution when tightening the strap. The strap must be  
tight enough to hold the bulb securely but caution must be  
taken not to over-tighten the strap, which could dent, bend,  
collapse or otherwise damage the bulb.  
Thermostatic Expansion Valves Thermostat-  
ic expansion valves (TXV) are used as a means of metering the  
refrigerant through the evaporator to achieve a preset superheat  
at the TXV sensing bulb. Correct superheat of the refrigerant is  
AIR  
COIL  
SUCTION  
AIRFLOW  
(°F)  
AIRFLOW  
(°F)  
COMPRESSOR  
THERMISTOR  
EXPANSION  
VALVE  
COAX  
DISCHARGE  
FP2  
FP1  
CONDENSATE  
OVERFLOW  
(CO)  
LIQUID  
LINE  
WATER IN  
WATER OUT  
AIR COIL  
WATER  
COIL  
PROTECTION  
FREEZE  
PROTECTION  
LEGEND  
COAX  
Coaxial Heat Exchanger  
Airflow  
Refrigerant Liquid Line Flow  
Fig. 38 — FP1 and FP2 Thermistor Location  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The bulb must be secured to the pipe using a copper strap.  
The use of heat transfer paste between the bulb and the pipe  
will also help ensure optimum performance.  
Diagnostics—Several tests may be required to determine if  
a TXV has failed. The following tools may be required for  
testing:  
The bulb must also be properly insulated to eliminate any  
influence on valve operation by the surrounding conditions.  
Cork tape is the recommended insulation as it can be molded  
tight to the bulb to prevent air infiltration.  
1. Refrigerant gage manifold compatible with the refriger-  
ant in the system  
2. Digital thermometer, preferably insulated, with wire leads  
that can be connected directly to the tubing  
Causes of TXV Failure — The most common causes of TXV  
failure are:  
3. Refrigerant pressure-temperature chart for the refrigerant  
used  
1. A cracked, broken, or damaged sensing bulb or capillary  
can be caused by excessive vibration of the capillary dur-  
ing shipping or unit operation.  
To determine that a TXV has failed, verify the following:  
• The suction pressure is low and the valve is non-responsive.  
The TXV sensing bulb can be removed from the suction  
line and warmed by holding the bulb in your hand. This  
action should result in an increase in the suction pressure  
while the compressor is operating. The sensing bulb can  
also be chilled by immersion in ice water, which should  
result in a decrease in the suction pressure while the  
compressor is operating. No change in the suction pres-  
sure would indicate a nonresponsive valve.  
If the sensing bulb is damaged or if the capillary is  
cracked or broken, the valve will be considered failed and  
must be replaced. Replacement of the TXV “power head”  
or sensing bulb, capillary, diaphragm assembly is possi-  
ble on some TXVs. The power head assembly screws  
onto most valves, but not all are intended to be replace-  
able. If the assembly is not replaceable, replace the entire  
valve.  
• Simultaneous LOW suction pressure, HIGH refrigerant  
2. Particulate debris within the system can be caused by sev-  
eral sources including contaminated components, tubing,  
and service tools, or improper techniques used during  
brazing operations and component replacement.  
subcooling and HIGH superheat.  
• LOW suction pressure, LOW subcooling and HIGH super-  
heat may indicate an undercharge of refrigerant. HIGH sub-  
cooling and LOW superheat may indicate an overcharge of  
refrigerant. The suction pressure will usually be normal or  
high if there is an overcharge of refrigerant.  
• LOW suction pressure and frosting of the valve and/or  
equalizer line may indicate a failed valve. However, these  
symptoms may also indicate an undercharge of refrigerant.  
Calculate the subcooling and superheat to verify a failed  
valve or refrigerant charge issue.  
Problems associated with particulate debris can be com-  
pounded by refrigerant systems that use POE (polyol es-  
ter oil). POE oil has solvent-like properties that will clean  
the interior surfaces of tubing and components. Particu-  
lates can be released from interior surfaces and may mi-  
grate to the TXV strainer, which can lead to plugging of  
the strainer.  
3. Corrosive debris within the system may happen after a  
failure, such as a compressor burn out, if system was not  
properly cleaned.  
Repair  
WARNING  
4. Noncondensables may be present in the system. Non-  
condensables includes any substance other than the  
refrigerant or oil such as air, nitrogen, or water. Contami-  
nation can be the result of improper service techniques,  
use of contaminated components, and/or improper evacu-  
ation of the system.  
Symptoms — The symptoms of a failed TXV can be varied  
and will include one or more of the following:  
• Low refrigerant suction pressure  
®
Puron refrigerant (R-410A) operates at higher pressure  
than R-22, which is found in other WSHPs. Tools such as  
manifold gages must be rated to withstand the higher pres-  
sures. Failure to use approved tools may result in a failure  
of tools, which can lead to severe damage to the unit, injury  
or death.  
WARNING  
• High refrigerant superheat  
• High refrigerant subcooling  
Most TXVs are designed for a fixed superheat setting and  
are therefore considered non-adjustable. Removal of the  
bottom cap will not provide access for adjustment and can  
lead to damage to the valve or equipment, unintended vent-  
ing of refrigerant, personal injury, or possibly death.  
• TXV and/or low pressure tubing frosting  
• Equalizer line condensing and at a lower temperature than  
the suction line or the equalizer line frosting  
• FP1 faults in the heating mode in combination with any of  
the symptoms listed above  
• FP2 faults in the cooling mode in combination with any of  
the symptoms listed above. Some symptoms can mimic a  
failed TXV but may actually be caused be another problem.  
CAUTION  
Always recover the refrigerant from the system with suit-  
able approved tools, recovery equipment, and practices  
prior to attempting to remove or repair any TXV.  
Before conducting an analysis for a failed TXV the follow-  
ing must be verified:  
• Confirm that there is proper water flow and water tempera-  
ture in the heating mode.  
CAUTION  
• Confirm that there is proper airflow and temperature in the  
Use caution when tightening the strap. The strap must be  
tight enough to hold the bulb securely but caution must be  
taken not to over-tighten the strap, which could dent, bend,  
collapse or otherwise damage the bulb.  
cooling mode.  
• Ensure coaxial water coil is clean on the inside; this applies  
to the heating mode and may require a scale check.  
• Refrigerant may be undercharged. To verify, subcooling and  
superheat calculations may be required.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
IMPORTANT: Repair of any sealed refrigerant system  
requires training in the use of refrigeration tools and proce-  
dures. Repair should only be attempted by a qualified ser-  
vice technician. A universal refrigerant handling certificate  
will be required. Local and/or state license or certificate  
may also be required.  
CAUTION  
®
Puron refrigerant (R-410A) requires the use of synthetic  
lubricant (POE oil). Do not use common tools on systems  
that contain R-22 refrigerants or mineral oil. Contamina-  
tion and failure of this equipment may result.  
See Tables 30-32 for additional troubleshooting  
information.  
IMPORTANT: Due to the hygroscopic nature of the  
POE oil in Puron refrigerant (R-410A) and other envi-  
ronmentally sound refrigerants, any component replace-  
ment must be conducted in a timely manner using  
caution and proper service procedure for these types of  
refrigerants. A complete installation instruction will be  
included with each replacement TXV/filter drier assem-  
bly. It is of critical importance these instructions are  
carefully understood and followed. Failure to follow  
these instructions can result in a system that is contami-  
nated with moisture to the extent that several filter drier  
replacements may be required to properly dry the  
system.  
CAUTION  
Disconnect power from unit before removing or replacing  
connectors, or servicing motor. Wait 5 minutes after dis-  
connecting power before opening motor.  
Table 30 — ECM Troubleshooting  
FAULT  
DESCRIPTION  
SOLUTION  
Motor rocks slightly when  
starting  
Motor will not start  
This is normal start-up for ECM.  
Check power at motor.  
No movement  
Check low voltage (24-vac R to C) at motor.  
Check low voltage connections (G,Y, W, R, C) at motor.  
Check for unseated pins in connectors on motor harness. See Fig. 39.  
Test with a temporary jumper between R and G.  
Check motor for tight shaft.  
Perform motor/control replacement check.  
Run moisture check. See Moisture Check section in Troubleshooting.  
Check for loose or non-compliant motor mount.  
Make sure blower wheel is tight on shaft.  
Motor rocks  
Perform motor/control replacement check.  
Motor oscillates up and down  
while being tested off of blower  
It is normal for motor to oscillate with no load on shaft.  
Motor starts, but runs erratically Varies up and down or intermittent Check line voltage for variation or “sag.”  
Check low voltage connections (G,Y, W, R, C) at motor, unseated pins in motor harness  
connectors. See Fig. 39.  
Check “Bkfor erratic cfm command (in variable speed applications).  
Check system controls, thermostat.  
Perform moisture check. See Moisture Check section in Troubleshooting.  
If removing panel or filter reduces “puffing,reduce restriction or reduce maximum airflow.  
“Huntsor “puffsat high cfm  
(speed)  
Stays at low cfm despite system  
call for cool or heat cfm  
Check low voltage (thermostat) wires and connections.  
Verify fan is not in delay mode. Wait until delay is complete.  
Check to see if “Ris missing/not connected at motor.  
Perform motor/control replacement check.  
Stays at high cfm  
Check to see if “Ris missing/not connected at motor.  
Verify fan is not in delay mode. Wait until delay is complete.  
Perform motor/control replacement check.  
Blower will not shut off  
Noisy blower or cabinet  
Check to see if there is current leakage from controls into G, Y, or W. Check for Triac switched  
thermostat or solid state relay.  
Excessive noise  
Determine if it’s air, cabinet, duct, or motor noise.  
Check for loose blower housing, panels, etc.  
If high static is creating high blower speed, check for air whistling through seams in ducts,  
cabinets, or panels.  
If high static is creating high blower speed, check for cabinet/duct deformaton.  
“Huntsor “puffsat high cfm  
(speed)  
If removing panel or filter reduces “puffing,reduce restriction or reduce maximum airflow.  
Evidence of moisture  
Motor failure or malfunction has  
occurred and moisture is present  
Replace motor and perform moisture check. See Moisture Check section in Troubleshooting.  
Perform moisture check. See Moisture Check section in Troubleshooting.  
Evidence of moisture present  
inside air mover  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a50-8448  
Fig. 39 — ECM Pin Connectors  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Stopped or Malfunctioned ECM Motor — Refer  
to Fig. 40 to determine the possible cause of a stopped or mal-  
functioned ECM motor. Follow the instructions in the boxes.  
a50-8447  
Fig. 40 — ECM Troubleshooting Flow Diagram  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• Check if condensate drain is plugged.  
• Check for low airflow (too much latent capacity).  
• Check for undercharged condition.  
Moisture Check — To perform moisture check:  
• Check that connectors are orientated “down” (or as recom-  
mended by equipment manufacturer).  
• Arrange harnesses with “drip loop” under motor.  
• Check and plug leaks in return ducts, cabinet.  
Table 31 — Good Practices  
DO  
DO NOT  
Check motor, controls wiring, and connections thoroughly before replac- Automatically assume the motor is bad.  
ing motor.  
Orient connectors down so water cannot get in. Install “drip loops.”  
Locate connectors above 7 and 4 o’clock positions.  
Use authorized motor and control model numbers for replacement.  
Replace one motor or control model number with another (unless  
replacement is authorized).  
Keep static pressure to a minimum by:  
Use high pressure drop filters.  
Use restricted returns.  
Using high efficiency, low-static filters.  
Keeping filters clean.  
Designing ductwork for minimum static and maximum comfort.  
Improving ductwork when replacement is necessary.  
Size equipment wisely.  
Oversize system then compensate with low airflow.  
Check orientation before inserting motor connectors.  
Plug in power connector backwards.  
Force plugs.  
Table 32 — WSHP Troubleshooting  
FAULT  
Main Power Problems  
HEATING COOLING  
POSSIBLE CAUSE  
Green Status LED Off  
SOLUTION  
X
X
Check line voltage circuit breaker and disconnect.  
Check for line voltage between L1 and L2 on the contactor.  
Check for 24 vac between R and C on controller.  
Check primary/secondary voltage on transformer.  
Check pump operation or valve operation/setting.  
Check water flow adjust to proper flow rate.  
HP Fault — Code 2  
High Pressure  
X
X
Reduced or no water flow in cooling  
Water temperature out of range in  
cooling  
Bring water temperature within design parameters.  
X
Reduced or no airflow in heating  
Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
Dirty air coil — construction dust etc.  
External static too high. Check blower performance per Tables 9-13.  
X
X
Air temperature out of range in heating Bring return-air temperature within design parameters.  
X
Overcharged with refrigerant  
Check superheat/subcooling vs typical operating condition per  
Tables 20-23.  
X
X
X
X
X
Bad HP switch  
Insufficient charge  
Compressor pump down at start-up  
Check switch continuity and operation. Replace.  
Check for refrigerant leaks.  
Check charge and start-up water flow.  
LP/LOC Fault — Code 3  
Low Pressure/Loss of  
Charge  
FP1 Fault — Code 4  
Water Freeze Protection  
X
Reduced or no water flow in heating Check pump operation or water valve operation/setting.  
Plugged strainer or filter. Clean or replace.  
Check water flow adjust to proper flow rate.  
X
X
Inadequate antifreeze level  
Improper freeze protect setting (30F Clip JW2 jumper for antifreeze (10F) use.  
vs 10F)  
Check antifreeze density with hydrometer.  
X
X
Water temperature out of range  
Bad thermistor  
Reduced or no airflow in cooling  
Bring water temperature within design parameters.  
Check temperature and impedance correlation.  
Check for dirty air filter and clean or replace.  
X
X
FP2 Fault — Code 5  
Air Coil Freeze Protection  
Check fan motor operation and airflow restrictions.  
External static too high. Check blower performance per Tables 9-13.  
X
X
Air temperature out of range  
Too much cold vent air. Bring entering air temperature within design  
parameters.  
Improper freeze protect setting (30F Normal airside applications will require 30 F only.  
vs 10F)  
X
X
X
X
X
X
X
Bad thermistor  
Blocked drain  
Improper trap  
Poor drainage  
Check temperature and impedance correlation.  
Check for blockage and clean drain.  
Check trap dimensions and location ahead of vent.  
Check for piping slope away from unit.  
Check slope of unit toward outlet.  
Condensate Fault —  
Code 6  
Poor venting. Check vent location.  
X
Moisture on sensor  
Check for moisture shorting to air coil.  
LEGEND  
LED — Light-Emitting Diode  
RV  
Reversing Valve  
TXV — Thermostatic Expansion Valve  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 32 — WSHP Troubleshooting (cont)  
FAULT  
Over/Under Voltage —  
Code 7 (Auto Resetting)  
HEATING COOLING  
POSSIBLE CAUSE  
Under voltage  
SOLUTION  
X
X
Check power supply and 24 vac voltage before and during operation.  
Check power supply wire size.  
Check compressor starting.  
Check 24 vac and unit transformer tap for correct power supply voltage.  
Check power supply voltage and 24 vac before and during operation.  
Check 24 vac and unit transformer tap for correct power supply voltage.  
Check for poor airflow or overcharged unit.  
X
X
X
X
Over voltage  
Performance Monitor —  
Code 8  
Heating mode FP2>125F  
Cooling mode FP1>125F OR  
FP2<40F  
Check for poor water flow or airflow.  
FP1 and FP2 Thermistors  
— Code 9  
X
FP1 temperature is higher  
than FP2 temperature.  
Swap FP1 and FP2 thermistors.  
Swap FP1 and FP2 thermistors.  
X
FP2 temperature is higher  
than FP1 temperature.  
No Fault Code Shown  
X
X
X
X
X
X
X
X
No compressor operation  
Compressor overload  
Control board  
See Scroll Compressor Rotation section.  
Check and replace if necessary.  
Reset power and check operation.  
Reverse position of thermistors.  
Swapped Thermistor —  
Code 9  
FP1 and FP2 swapped  
Unit Short Cycles  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Dirty air filter  
Check and clean air filter.  
Unit in 'Test Mode'  
Unit selection  
Reset power or wait 20 minutes for auto exit.  
Unit may be oversized for space. Check sizing for actual load of space.  
Check and replace if necessary.  
Compressor overload  
Thermostat position  
Unit locked out  
Only Fan Runs  
Ensure thermostat set for heating or cooling operation.  
Check for lockout codes. Reset power.  
Compressor overload  
Thermostat wiring  
Check compressor overload. Replace if necessary.  
Check Y and W wiring at heat pump. Jumper Y and R for compressor  
operation in Test mode.  
Only Compressor Runs  
X
X
X
X
Thermostat wiring  
Check G wiring at heat pump. Jumper G and R for fan operation.  
Check Y and W wiring at heat pump. Jumper Y and R for compressor  
operation in test mode.  
X
Fan motor relay  
Jumper G and R for fan operation. Check for line voltage across BR  
contacts.  
Check fan power enable relay operation (if present).  
Check for line voltage at motor. Check capacitor.  
X
X
Fan motor  
Unit Does Not Operate in  
Cooling  
Reversing valve  
Set for cooling demand and check 24 vac on RV coil and at control.  
If RV is stuck, run high pressure up by reducing water flow and while  
operating, engage and disengage RV coil voltage to push valve.  
X
X
X
Thermostat setup  
Thermostat wiring  
Dirty filter  
Check for 'O' RV setup not 'B'.  
Check O wiring at heat pump. Jumper O and R for RV coil 'Click'.  
Replace or clean.  
Insufficient Capacity/  
Not Cooling or Heating  
Properly  
X
X
Reduced or no airflow in heating Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
External static too high. Check blower performance per Tables 9-13.  
X
X
Reduced or no airflow in cooling Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
External static too high. Check blower performance per Tables 9-13.  
X
Leaky ductwork  
Check supply and return air temperatures at the unit and at distant duct  
registers if significantly different, duct leaks are present.  
X
X
X
X
X
Low refrigerant charge  
Restricted metering device  
Defective reversing valve  
Check superheat and subcooling per Tables 20-23.  
Check superheat and subcooling per Tables 20-23. Replace.  
Set for cooling demand and check 24 vac on RV coil and at control.  
If RV is stuck, run high pressure up by reducing water flow and while  
operating, engage and disengage RV coil voltage to push valve.  
X
X
X
X
Thermostat improperly located  
Unit undersized  
Check location and for air drafts behind thermostat.  
Recheck loads and sizing check sensible cooling load and heat pump  
capacity.  
X
X
X
X
Scaling in water heat exchanger Perform condenser cleaning.  
Inlet water too hot or cold Check load, loop sizing, loop backfill, ground moisture.  
LEGEND  
LED — Light-Emitting Diode  
RV  
Reversing Valve  
TXV — Thermostatic Expansion Valve  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 32 — WSHP Troubleshooting (cont)  
FAULT  
HEATING COOLING  
POSSIBLE CAUSE  
SOLUTION  
High Head Pressure  
X
Reduced or no airflow in heating Check for dirty air filter and clean or replace.  
Check fan motor operation and airflow restrictions.  
External static too high. Check blower performance per Tables 9-13.  
Check pump operation or valve operation/setting.  
X
X
Reduced or no water flow in  
cooling  
Check water flow adjust to proper flow rate. See Tables 19 and 24.  
Check load, loop sizing, loop backfill, ground moisture.  
Bring return-air temperature within design parameters.  
Inlet water too hot  
X
Air temperature out of range in  
heating  
X
X
X
X
Scaling in water heat exchanger Perform condenser cleaning.  
X
X
X
X
Unit overcharged  
Check superheat and subcooling. Reweigh in charge.  
Noncondensables in system  
Restricted metering device  
Reduced water flow in heating  
Remove refrigerant, evacuate system and charge unit.  
Check superheat and subcooling per Tables 20-23. Replace.  
Check pump operation or water valve operation/setting.  
Plugged strainer or filter. Clean or replace.  
Low Suction Pressure  
Check water flow adjust to proper flow rate.  
X
Water temperature out of range  
Reduced airflow in cooling  
Bring water temperature within design parameters.  
Check for dirty air filter and clean or replace.  
X
Check fan motor operation and airflow restrictions.  
External static too high. Check blower performance per Tables 9-13.  
X
X
Air temperature out of range  
Too much cold vent air. Bring entering air temperature within design  
parameters.  
X
X
X
Insufficient charge  
Too high airflow  
Poor performance  
Too high airflow  
Unit oversized  
Check for refrigerant leaks.  
Check blower performance per Tables 9-13.  
See “Insufficient Capacity.”  
Low Discharge Air  
Temperature in Heating  
High Humidity  
X
X
Check blower performance per Tables 9-13  
Recheck loads and sizing check sensible cooling load and heat pump  
capacity.  
Low Refrigerant Suction  
Pressure  
X
X
Normal operation  
Check/compare with unit Installation Manual for typical operating temper-  
atures and pressures chart.  
Reduced water flow  
Check pump operation.  
Check strainer or filter.  
Improper flow regulator.  
X
X
Water temperature out of range  
Bring water temperature within proper range.  
Conduct water quality analysis.  
Scaling in water to refrigerant  
heat exchanger  
X
Reduced airflow  
Check for dirty air filter.  
Check for dirty air coil.  
Check fan motor operation.  
External static pressure exceeds fan operating parameters.  
Space temperature too cold.  
X
X
X
Return air temperature below  
minimum  
Excessive fresh air.  
Supply air bypassing to return air Check for leaking ductwork.  
stream (zone systems).  
X
X
X
X
Insufficient refrigerant charge  
Locate and repair leak.  
Improperly located TXV sensing Locate bulb on suction line between reversing valve and compressor.  
bulb  
X
X
Failed or restricted metering  
device  
Failed TXV power head, capillary or sensing bulb.  
Plugged TXV strainer.  
High Refrigerant Superheat  
X
X
X
X
Insufficient refrigerant charge  
Locate and repair leak.  
Improperly located TXV sensing Locate bulb on suction line between reversing valve and compressor.  
bulb  
X
X
Failed or restricted metering  
device  
Failed TXV power head, capillary or sensing bulb.  
Plugged TXV strainer.  
High Refrigerant  
Subcooling  
X
X
X
X
Excessive refrigerant charge  
Remove refrigerant as needed.  
Failed or restricted metering  
device  
Failed TXV power head, capillary or sensing bulb.  
Plugged TXV strainer.  
TXV and/or Low Pressure  
Tubing Frosting  
X
X
X
Normal operation  
May occur when entering water temperature is close to minimum.  
Locate and repair leak.  
X
X
Insufficient refrigerant charge  
Failed or restricted metering  
device  
Failed TXV power head, capillary or sensing bulb.  
Plugged TXV strainer.  
Equalizer Line Condensing  
or Frosting  
X
X
Failed or restricted metering  
device  
Failed TXV power head, capillary or sensing bulb.  
Plugged TXV strainer.  
LEGEND  
LED — Light-Emitting Diode  
RV  
Reversing Valve  
TXV — Thermostatic Expansion Valve  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Off, Fan Only, Economize,  
Cooling, Heating, Cont Fan,  
Test, Start Delay, Dehumidify  
Operating Mode  
Displays unit operating mode  
SPT  
SAT  
F
F
Displays SPT  
Displays SAT  
Condenser Leaving  
Temperature  
Displays leaving condenser  
water temperature  
F
Displays entering condenser  
water temperature (Value  
will not update when compressor  
is operating)  
Condenser Entering  
Temperature  
F
Off/Low Speed/  
Medium Speed  
High Speed/On  
Fan  
Displays fan speed status  
Equipment  
Status  
No Password  
Required  
Compressor Capacity  
Damper Position  
0 - 100%  
0 - 100%  
0 - 100%  
Displays compressor capacity  
Displays current damper position  
(Viewable only if Ventilation DMP  
Type = 2 position or DCV)  
H O Economizer  
2
Displays position of economizer valve  
Displays position of auxiliary  
reheat valve (Viewable only if Leaving  
Air Auxiliary Heat Type = 2 position,  
1 stage Elect or Modulating)  
Auxiliary Heat  
0 - 100%  
Displays space RH% (Viewable only if  
Humidity Sensor = Installed)  
Space RH  
0 - 100%  
Displays if dehumidification is active  
(Viewable only if Factory  
Dehumidification Reheat = Installed)  
Dehumidification  
Inactive/Active  
IAQ CO  
0 - 9999 ppm  
Normal/Alarm  
Displays the space CO level  
2
2
Displays current space  
temperature condition  
SPT Alarm Status  
Displays the SPT that  
exceeded the alarm limit (when SPT  
alarm above is in Alarm)  
Alarming SPT  
F
F
Displays the SPT alarm limit that was  
exceeded; causing the alarm condition  
(when SPT alarm above is in Alarm)  
SPT Alarm Limit  
Displays the status of the Rnet  
SPT sensor - ALARM is displayed  
should the sensor fail to communicate  
with the control module  
SPT Sensor Alarm  
Status  
Normal/Alarm  
IAQ Alarm Status  
Normal/Alarm  
Normal/Alarm  
Normal/Alarm  
Normal/Alarm  
Current IAQ/ventilation condition  
Current compressor condition  
Current SAT condition  
Compressor Alarm  
Status  
No Password  
Required  
Alarm Status  
SAT Alarm Status  
Condensate Overflow  
Alarm Status  
Current status of the condensate  
drain (overflow switch)  
Condenser Water Tem-  
perature Alarm Status  
Current status of the  
condenser water  
Normal/Alarm  
Filter Alarm Status  
Normal/Alarm  
Normal/Alarm  
Current filter condition  
Space RH Alarm Status  
Current space RH condition  
Current status of the OAT  
broadcast function  
OAT Alarm Status  
Normal/Alarm  
Normal/Alarm  
Normal/Alarm  
Airside Linkage Status  
Current linkage status if enabled  
Condenser Water  
Linkage  
Current linkage status if enabled  
SAT  
F
Display SAT  
SAT Offset  
X
X
-9.9 - 10.0  
F
F
F
0
0
0
F
F
F
Used to correct sensor reading  
Leaving Condenser  
Water Temperature  
Displays Leaving Condenser  
Water Temperature  
F
Leaving CW Offset  
-9.9 - 10.0  
Used to correct sensor reading  
Sensor  
Calibration  
Admin Password  
level access only  
Rnet Sensor  
Temperature  
F
Displays SPT  
Rnet Offset  
RH  
X
X
-9.9 - 10.0  
%
Used to correct sensor reading  
Displays Space RH value  
RH Sensor Offset  
-15% - 15%  
0 %  
Used to correct sensor reading  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Off, Fan Only,Economize,  
Cooling, Heating, Cont Fan, Test,  
Start Delay, Dehumidify  
Operating Mode  
Displays unit operating mode  
Displays how the fan is configured  
to operate  
Fan Operating Mode  
Occupancy Status  
Auto/Continuous/Always On  
Unoccupied/Occupied  
Displays the current occupancy status  
Always Occupied/Local Schedule/  
BACnet Schedule/BAS Keypad/  
Occupied Contact/Holiday Schedule/  
Override Schedule/Pushbutton  
Override/Unoccupied None  
Displays the origin of the  
occupancy control  
Occupancy Control  
Outside Air  
Displays OAT (Viewable only if OAT  
is a network broadcast)  
F
F
Temperature  
SPT  
Displays SPT  
Normal/Above Limit/Below  
Limit/Sensor Failure  
SPT Status  
Displays the SPT status  
Displays the connection status  
of the Rnet sensor  
SPT Sensor Status  
Condensate Overflow  
Cooling Set Point  
Inactive/Connected  
Normal/Alarm  
Displays the status of the  
condensate overflow  
Displays the actual set point  
being used for cooling control  
F
F
Displays the actual set point  
being used for heating control  
Heating Set Point  
Unit  
Maintenance  
No Password  
required  
Displays the offset values from the Rnet  
user set point adjustment that is being  
applied to the configured set points  
Set Point Adjustment  
F
Auxiliary Heat Control  
Set Point  
Displays the calculated set point being  
used for auxiliary heating control  
F
F
H O Economizer  
2
Control Set Point  
Displays the calculated set point being  
used for economizer control  
Calculated IAQ/  
Ventilation Damper  
position  
Displays the ventilation damper  
position calculated by the DCV control  
%
Active Compressor  
Stages  
Displays the actual number of  
compressor stages operating  
0/1/2  
SAT  
F
Displays SAT  
Used to reset the filter alarm timer after  
the filter has been cleaned or replaced  
Reset Filter Alarm  
X
X
No/Yes  
Displays the state of the condensate  
overflow switch contact  
Overflow Contact  
Closed/Open  
Closed/Open  
Displays the state of the external/  
remote occupancy input switch contact  
Occupancy Contact  
Provides capability to force the  
equipment to operate in an  
occupied or unoccupied mode  
Inactive/Occupied/  
Unoccupied  
BAS/Keypad Override  
OAT Input  
Inactive  
Displays if an OAT value is being  
received from the Network  
N/A / Network  
BACnet  
Keypad Configuration  
Password  
X
X
X
X
X
X
See TPI  
Mapping  
Changes password  
See TPI  
System Settings  
Network  
BACnet Time Master  
Clock Set  
See TPI  
Changes clock/time setting  
Override Schedules  
Pushbutton Override  
Inactive/Active Occupied  
Inactive/Active Occupied  
Inactive/Active Occupied/Active  
Unoccupied  
Keypad Override  
Occupancy  
Maintenance  
No Password  
required  
Used to display the active and  
inactive occupancy control inputs  
Schedules  
Occupancy Contact  
BAS on/off  
Inactive/Active Occupied  
Inactive/Active Occupied  
Inactive/Active Occupied  
Local Occupancy  
Schedules  
X
X
X
X
Disable/Enable  
Disable/Enable  
Disable/Enable  
Disable/Enable  
Enable  
Disable  
Disable  
Disable  
Local Holiday  
Schedules  
User/Admin  
Password level  
access  
Used to define which occupancy inputs  
are used to determine  
Schedule  
Configuration  
Local Override  
Schedules  
occupancy mode.  
BACnet Occupancy  
Schedules  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP OPEN SCREEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
Occupied Heating  
Occupied Cooling  
Unoccupied Heating  
Unoccupied Cooling  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Defines the Occupied  
Heating Set Point  
X
X
X
X
X
X
40 - 90  
55 - 99  
40 - 90  
55 - 99  
F
F
F
F
72  
76  
55  
90  
F
F
F
F
Defines the Occupied  
Cooling Set Point  
Defines the Unoccupied  
Heating Set Point  
Defines the Unoccupied  
Cooling Set Point  
Effective Heating  
Set Point  
Takes into effect bias (maximum  
allowable set point deviation)  
0 - 10  
0 - 10  
F
Effective Cooling  
Set Point  
Takes into effect bias (maximum  
allowable set point deviation)  
F
Uses historical data to calculate  
ramp up time so as to be at set point  
at occupied/unoccupied time  
Optimal Start  
Configuration  
Set Points  
Defines the control set point used  
during occupied periods (Viewable  
only if Humidity Sensor = Installed/  
Determines when to start  
User/Admin  
Password level  
access  
Occupied RH  
Set Point  
X
0 - 100%  
65%  
Dehumidification when occupied)  
Defines the control set point used  
during unoccupied periods  
(Viewable only if Humidity Sensor =  
Installed/Determines when to start  
Dehumidification when unoccupied)  
Unoccupied RH  
Set Point  
X
X
0 - 100%  
90%  
Defines the control set point used to  
start increasing ventilation during  
occupied periods (Viewable only if  
Ventilation DMP Type = DCV)  
DCV CTRL Start  
Set Point  
0 - 9999 ppm  
500 ppm  
Defines the control set point  
used to define where the ventilation  
will reach its maximum limit during  
DCV Max CTRL  
Set Point  
X
0 - 9999 ppm  
1050 ppm occupied periods (Viewable only if  
Ventilation DMP Type = DCV/Used  
to determine DCV ending control  
point)  
Defines the start time for an  
Start Time  
End Time  
Mon  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
00:00 - 23:59  
00:00 - 24:00  
No/Yes  
06:00  
occupied period  
Defines the ending time of an  
18:00  
occupied period  
Determines if this day is included  
Yes  
Configuration  
Schedule  
in this schedule  
Determines if this day is included  
Tue  
No/Yes  
Yes  
in this schedule  
User/Admin  
Password level  
access  
Determines if this day is included  
Wed  
No/Yes  
Yes  
in this schedule  
Determines if this day is included  
Thur  
No/Yes  
Yes  
in this schedule  
Determines if this day is included  
Weekly Schedule  
Fri  
No/Yes  
Yes  
in this schedule  
Determines if this day is included  
Sat  
No/Yes  
No  
in this schedule  
Determines if this day is included  
Sun  
No/Yes  
No  
in this schedule  
Defines the start month of this  
Start Month  
Start Day  
Start Time  
End Month  
End Day  
End Time  
0 - 12  
0
hoilday schedule  
Configuration  
Schedule  
Defines the start day of this holiday  
0 - 31  
0
schedule  
Determines the start time for this  
00:00 - 23:59  
0 - 12  
0:00  
User/Admin  
Password level  
access  
schedule  
Defines the month to end this  
0
hoilday schedule  
Defines the day to end this holiday  
0 - 31  
0
Exception  
Schedules 1 - 12  
schedule  
Determines the time to end this  
00:00 - 24:00  
0:00  
schedule  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Auto= Intermittant operation during both  
occupied and unoccupied periods/  
Continuous = Intermittant during unoccupied  
periods and continuous during occupied  
periods/Always on = fan operates  
continuously during both occupied and  
unoccupied periods  
Auto/Continuous/  
Always On  
Fan Mode  
X
Continuous  
Defines the delay time before the fan begins  
to operate after heating or cooling is started  
Fan On Delay  
Fan Off Delay  
X
X
0 - 30 sec  
10 sec  
45 sec  
Defines the amount of time the fan will  
continue to operate after heating or  
cooling is stopped  
0 - 180 sec  
Provides capability to manually  
disable heating operation  
Heating Enable  
Cooling Enable  
X
X
X
X
Disable/Enable  
Disable/Enable  
Enable  
Enable  
Provides capability to manually  
disable cooling operation  
Minimum SAT in  
Cooling  
Defines the minimum acceptable operating  
temperature for the Supply Air  
40 - 60  
F
50  
F
Configuration  
Maximum SAT in  
Heating  
Defines the maximum acceptable operating  
temperature for the Supply Air  
80 - 140  
F
110  
F
Admin Password  
level access only  
Normally set to 100% if 2 position damper  
type or set to minimum ventilation position if  
damper type = DCV  
Damper Ventilation  
Position  
X
X
0 - 100%  
100%  
Unit  
Configuration  
DCV Maximum Vent  
Position  
Usually set at 100% - Used to limit maximum  
damper opening in DCV mode  
0 - 100%  
100%  
Filter Alarm Timer  
X
X
0 - 9999 hrs  
0 hrs  
Disables Filter Alarm if set to 0  
Pushbutton Override  
Disable/Enable  
Enable  
Enables Override Feature on Rnet sensor  
SPT Sensor Set Point  
Adjustment  
Enables Set Point adjustment capability  
on Rnet Sensor  
X
Disable/Enable  
Enable  
Cooling is locked out when OAT is less than  
configured value and OAT is actively being  
broadcast  
Lockout Cooling if  
OAT <  
X
-65 - 80  
35 - 150  
F
F
-65  
F
F
Heating is locked out when OAT is greater  
than configured value and OAT is actively  
being broadcast  
Lockout Heating if  
OAT >  
X
150  
Power Fail Restart  
Delay  
X
X
X
0 - 600 sec  
60 sec  
Enable  
Delay before equipment starts  
Occupancy Schedules  
Disable/Enable  
Enables unit occupied  
Used to enforce minimum  
set point separation  
Set Point Separation  
2 - 9  
F
4
F
Used to enable test mode. Will automatically  
reset to disable after 1 hour  
Test Mode  
Fan Test  
X
X
Disable/Enable  
Disable/Enable  
Disable  
Disable  
Used to test all fan speeds. Sequences fan  
from low to high and operates each speed for  
1 minute. Resets to disable on completion  
Off/Low Speed/Medium  
Speed/High Speed/On  
Fan Speed  
Displays current fan operation  
Used to test compressor cooling and heating  
operation. Sequences cooling stage 1, then  
stage 2, then heating stage 2 and reduces  
capacity to stage 1. Operates for 1 minute per  
step. Resets to disable on completion.  
Compressor Test  
X
X
Disable/Enable  
Disable  
Disable  
Used to test dehumification mode -  
Operates for 2 minutes. Resets to  
disable on completion.  
Configuration  
Service  
Dehumidification Test  
Testing Compressor  
Disable/Enable  
Inactive/Heating/Cooling/  
Dehumidify/TimeGard  
Wait  
Admin Password  
level access only  
Displays compressor test mode  
Used to test auxiliary heat.  
Sequences fan on and enables  
heating coil for 1 minute. Resets to  
disable on completion  
Aux Heating Test  
X
X
Disable/Enable  
Disable/Enable  
Disable  
Disable  
Test  
Used to test entering/return air water loop  
economizer coil operation. Sequences fan on  
and opens economizer coil water valve for 1  
minute. Resets to disable on completion  
H O Economizer Test  
2
Preposition OA  
Damper  
Used to preposition OA damper  
actuator to set proper preload  
X
X
Disable/Enable  
Disable/Enable  
Disable  
Disable  
Open Vent  
Damper 100%  
Used to test OA damper operation  
Displays SAT  
SAT  
F
F
Displays Leaving Condenser  
Water Temperature  
LCWT  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Used to set number of  
fan motor speeds  
# of Fan Speeds  
X
1,2,3  
3
When set to Fan On, G output is  
energized when ever any fan speed  
is active (required for ECM and Fan  
control board). When set to Fan  
Low, output is only energized for  
Low Speed  
G Output Type  
X
Fan On/Fan Low  
Fan On  
Defines the number of  
stages of compression  
Compressor Stages  
Reversing Valve Type  
X
X
X
X
X
X
X
One Stage/Two Stages  
One Stage  
O type  
None  
Determines reversing valve  
signal output type  
O type output/B type output  
Leaving Air Auxiliary  
Heat Type  
None/2-Position HW/1 Stage  
Electric/Modulating HW  
Determines Auxiliary  
Reheat Coil Type  
Entering Air Water  
Economizer Type  
Determines Entering Air  
Economizer Coil Type  
None/2-Position/Modulating  
Normally Closed/Normally Open  
Normally Closed/Normally Open  
None/2-Position/DCV  
None  
2-Position Water  
Valve Type  
Normally  
Closed  
Determines type of 2-position  
water valve used  
Modulating Water  
Valve Type  
Normally  
Closed  
Determines type of modulating  
water valve used  
Ventilation Damper  
Type  
Determines type of ventilation  
damper control to be used  
None  
0-10 volt  
None  
Used to determine ventilation  
damper output signal range  
(closed - open)  
Damper Actuator Type  
Humidity Sensor  
X
X
X
(0-10 volt)/(2-10 volt)  
None/Installed  
Set to Installed if humidity  
sensor is present  
Configuration  
Admin Password  
level access only  
Set to Installed if factory-installed  
dehumidification reheat coil  
is present  
Factory Dehumidifica-  
tion Reheat Coil  
None/Installed  
None  
Service  
Configuration  
Occupancy  
Input Logic  
Occupied  
Used to determine external occu-  
X
X
X
Occupied Open/Occupied Closed  
5 - 600 seconds  
CLOSED pancy switch contact occupied state  
Condensate Switch  
Alarm Delay  
Delay before equipment alarms on  
10 sec  
high condensate level  
Condensate Switch  
Alarm State  
Alarm  
CLOSED  
Determine Alarm state of  
condensate switch input  
Alarm OPEN/Alarm CLOSED  
Minimum Condenser  
Water Temperature in  
Heating  
Determines the minimum  
acceptable water loop temperature  
to start heating  
X
X
X
X
25 - 60  
F
60  
90  
60  
95  
F
F
F
F
Maximum Condenser  
Water Temperature in  
Heating  
Determines the maximum  
acceptable water loop temperature  
to start heating  
65 - 100  
F
Minimum Condenser  
Water Temperature in  
Cooling  
Determines the minimum  
acceptable water loop temperature  
to start cooling  
30 - 60  
F
Maximum Condenser  
Water Temperature in  
Cooling  
Determines the maximum  
acceptable water loop temperature  
to start cooling  
85 - 120  
F
IAQ sensor  
Minimum output current (mA)  
for IAQ sensor  
X
X
X
X
0 - 5 ma  
4 ma  
20 ma  
minimum input  
IAQ sensor  
maximum input  
Maximum output current (mA) for  
IAQ sensor  
5 - 20 ma  
IAQ sensor  
minimum output  
Corresponding value in ppm for  
minimum output current  
0 - 9999 ppm  
0 - 9999 ppm  
0 ppm  
IAQ sensor  
maximum output  
Corresponding value in ppm for  
maximum output current  
2000 ppm  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
APPENDIX A — WSHP SCREEN OPEN CONFIGURATION (cont)  
PASSWORD  
LEVEL  
SCREEN NAME  
POINT NAME  
EDITABLE  
RANGE  
DEFAULT  
NOTES  
Defines the hysteresis applied above  
the cooling and below the heating set  
points before an alarm condition will  
occur  
SPT Occupied Alarm  
Hysteresis  
X
2 - 20  
F
5
F
Used to calculate the delay time before  
an alarm is generated after the alarm  
condition occurs  
SPT Alarm Delay  
X
0 - 30 min per degree  
10 min  
SPT Unoccupied Low  
Alarm Temperature  
Defines the fixed unoccupied  
ow SPT alarm limit  
X
X
X
X
35 - 90  
F
45  
95  
45  
F
F
F
SPT Unoccupied High  
Alarm Temperature  
Defines the fixed unoccupied  
high SPT alarm limit  
45 - 100  
F
SAT Low SAT  
Alarm Limit  
Defines the fixed minimum  
SAT alarm limit  
15 - 90  
F
SAT High SAT  
Alarm Limit  
Defines the fixed maximum  
SAT alarm limit  
90 - 175  
F
120  
F
Defines the delay time before an alarm  
is generated after the alarm condition  
occurs  
Condensate Overflow  
Alarm Delay  
X
X
X
5 - 600 sec  
45% - 100%  
10 sec  
100%  
5 min  
Space Humidity Occupied  
High Alarm Limit  
Defines the fixed occupied  
high space RH alarm limit  
Used to calculate the delay time before  
an alarm is generated after the alarm  
condition occurs  
Space Humidity Alarm  
Delay  
0 - 30 min per % RH  
Configuration  
Space Humidity Unoccu- Admin Password  
Defines the fixed unnoccupied  
high space RH alarm limit  
X
X
45% - 100%  
0 - 9999 ppm  
100%  
pied High Alarm Limit  
level access only  
Alarm  
Configuration  
IAQ/Ventilation Occupied  
High Alarm Limit  
Defines the fixed occupied high  
space IAQ/Ventilation alarm limit  
1100 ppm  
Used to calculate the delay time before  
0.25 min an alarm is generated after the alarm  
condition occurs  
IAQ/Ventilation  
Alarm Delay  
X
0.1 - 1.0 min per ppm  
Determines if the SPT alarm is  
Ignore  
Rnet Sensor SPT Alarm  
Rnet Sensor SAT Alarm  
X
X
Ignore/Display  
Ignore/Display  
displayed on the local Rnet sensor  
Determines if the SAT alarm is  
Ignore  
displayed on the local Rnet sensor  
Determines if the Compressor Lockout  
Rnet Sensor Compressor  
Lockout Alarm  
X
X
Ignore/Display  
Ignore/Display  
Display  
Display  
alarm is displayed on the local Rnet  
sensor  
Determines if the Condenser Water  
Temperature alarm is displayed on the  
local Rnet sensor  
Rnet Sensor Condenser  
Water Temperature Alarm  
Determines if the Condensate  
Overflow alarm is displayed on the  
local Rnet sensor  
Rnet Sensor Condensate  
Overflow Alarm  
X
X
X
Ignore/Display  
Ignore/Display  
Ignore/Display  
Display  
Display  
Ignore  
Rnet Sensor Dirty  
Filter Alarm  
Determines if the Dirty Filter alarm is  
displayed on the local Rnet sensor  
Determines if the High Space  
RH alarm is displayed on the  
local Rnet sensor  
Rnet Sensor Space  
High Humidity Alarm  
Loop Control Network  
Number  
See TPI  
See TPI  
See TPI  
Configuration  
Linkage  
Loop Control Network  
Address  
Number of Linked Heat  
Pumps  
LEGEND  
BAS — Building Automation System  
DCV — Demand Controlled Ventilation  
IAQ — Indoor Air Quality  
OAT — Outdoor Air Temperature  
RH  
Relative Humidity  
SAT — Supply Air Temperature  
SPT — Space Temperature  
TPI — Third Party Integration  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 2010 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53500079-01  
Printed in U.S.A.  
Form 50PT-4SI  
Pg 62  
7-10  
Replaces: 50PT-3SI  
Download from Www.Somanuals.com. All Manuals Search And Download.  
50PTH,PTV,PTD  
START-UP CHECKLIST  
CUSTOMER:___________________________  
MODEL NO.:___________________________  
JOB NAME: _______________________________________  
SERIAL NO.:____________________  
DATE:_________  
I. PRE-START-UP  
DOES THE UNIT VOLTAGE CORRESPOND WITH THE SUPPLY VOLTAGE AVAILABLE? (Y/N)  
HAVE THE POWER AND CONTROL WIRING CONNECTIONS BEEN MADE AND TERMINALS  
TIGHT? (Y/N)  
HAVE WATER CONNECTIONS BEEN MADE AND IS FLUID AVAILABLE AT HEAT EXCHANGER?  
(Y/N)  
HAS PUMP BEEN TURNED ON AND ARE ISOLATION VALVES OPEN? (Y/N)  
HAS CONDENSATE CONNECTION BEEN MADE AND IS A TRAP INSTALLED? (Y/N)  
IS AN AIR FILTER INSTALLED? (Y/N)  
II. START-UP  
IS FAN OPERATING WHEN COMPRESSOR OPERATES? (Y/N)  
IF 3-PHASE SCROLL COMPRESSOR IS PRESENT, VERIFY PROPER ROTATION PER INSTRUCTIONS.  
(Y/N)  
UNIT VOLTAGE — COOLING OPERATION  
PHASE AB VOLTS  
PHASE BC VOLTS  
(if 3 phase)  
PHASE CA VOLTS  
(if 3 phase)  
PHASE AB AMPS  
PHASE BC AMPS  
(if 3 phase)  
PHASE CA AMPS  
(if 3 phase)  
CONTROL VOLTAGE  
IS CONTROL VOLTAGE ABOVE 21.6 VOLTS? (Y/N)  
.
IF NOT, CHECK FOR PROPER TRANSFORMER CONNECTION.  
TEMPERATURES  
FILL IN THE ANALYSIS CHART ATTACHED.  
COAXIAL HEAT COOLING CYCLE:  
EXCHANGER  
FLUID IN  
F
F
F
F
FLUID OUT  
FLUID OUT  
AIR OUT  
F
PSI  
PSI  
FLOW  
FLOW  
HEATING CYCLE:  
FLUID IN  
F
F
F
AIR COIL  
COOLING CYCLE:  
AIR IN  
HEATING CYCLE:  
AIR IN  
AIR OUT  
CL-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HEATING CYCLE ANALYSIS  
PSI  
°F  
SAT  
AIR  
COIL  
SUCTION  
°F  
°F  
COMPRESSOR  
DISCHARGE  
EXPANSION  
COAX  
VALVE  
°F  
a50-8449  
LIQUID LINE  
°F  
PSI  
°F  
PSI  
FLUID IN  
FLUID OUT  
LOOK UP PRESSURE DROP IN TABLES 20-23  
TO DETERMINE FLOW RATE  
COOLING CYCLE ANALYSIS  
PSI  
°F  
SAT  
AIR  
COIL  
SUCTION  
°F  
°F  
COMPRESSOR  
DISCHARGE  
EXPANSION  
COAX  
VALVE  
°F  
a50-8450  
LIQUID LINE  
°F  
°F  
PSI  
PSI  
FLUID OUT  
FLUID IN  
LOOK UP PRESSURE DROP IN TABLES 20-23  
TO DETERMINE FLOW RATE  
HEAT OF EXTRACTION (ABSORPTION) OR HEAT OF REJECTION =  
FLOW RATE (GPM) x TEMP. DIFF. (DEG. F) x  
FLUID FACTOR* =  
(Btu/hr)  
SUPERHEAT = SUCTION TEMPERATURE – SUCTION SATURATION TEMPERATURE  
(DEG F)  
=
SUBCOOLING = DISCHARGE SATURATION TEMPERATURE – LIQUID LINE TEMPERATURE  
(DEG F)  
=
*Use 500 for water, 485 for antifreeze.  
Copyright 2010 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Catalog No. 04-53500079-01  
Printed in U.S.A.  
Form 50PT-4SI  
Pg CL-2  
7-10  
Replaces: 50PT-3SI  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Beko Washer WMB 81641 LC User Manual
Black Decker Coffeemaker DCM111100B User Manual
Black Decker Sander 90501831 User Manual
Boss Audio Systems Car Stereo System 815ca User Manual
Brinkmann Gas Grill Pro Series 6418 User Manual
Cannon Fishing Equipment DIGI TROLL 5 User Manual
Canon Calculator MP18DII User Manual
Casio Watch 2358 1 User Manual
Chevrolet Automobile 2010 Colorado User Manual
Cisco Systems Network Card WIC 1DSU T1 User Manual