Carrier Furnace 58CTA CTX User Manual

58CTA/CTX  
2 --- St a g e De l u x e  
In d u c e d --- Com b u st i on  
4---Way Multipoise Furnace  
Installation, Start---up, Operating and  
Service and Maintenance  
Instructions Series 130/D  
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . 2  
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
CODES AND STANDARDS . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Safety . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
General Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Combustion and Ventilation Air . . . . . . . . . . . . . . . . . . . . . . 5  
Duct Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Acoustical Lining and Fibrous Glass Duct . . . . . . . . . . . . . . . 5  
Gas Piping and Gas Pipe Pressure Testing . . . . . . . . . . . . . . . 5  
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
ama  
ISO 9001:2000  
CERTIFIED  
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS  
PROCEDURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
REGISTERED  
LOCATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6  
AIR FOR COMBUSTION AND VENTILATION . . . . . . . . . 8  
INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
UPFLOW INSTALLATION . . . . . . . . . . . . . . . . . . . . . . 10  
DOWNFLOW INSTALLATION . . . . . . . . . . . . . . . . . . . 11  
HORIZONTAL INSTALLATION . . . . . . . . . . . . . . . . . . 11  
FILTER ARRANGEMENT . . . . . . . . . . . . . . . . . . . . . . . 15  
AIR DUCTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15  
GAS PIPING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17  
ELECTRICAL CONNECTIONS . . . . . . . . . . . . . . . . . . 21  
VENTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
START--UP, ADJUSTMENT, AND SAFETY CHECK . . . . . 34  
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
Start--Up Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
Check Safety Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
Checklist . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40  
SERVICE AND MAINTENANCE PROCEDURES . . . . . 45  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45  
Care and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 46  
Sequence of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53  
NOTE: Read the entire instruction manual before starting the  
installation.  
Portions of the text and tables are reprinted from NFPA 54/ANSI  
Z223.1--2006E, with permission of National Fire Protection  
Association, Quincy, MA 02269 and American Gas Association,  
Washington DC 20001. This reprinted material is not the  
complete and official position of the NFPA or ANSI on the  
referenced subject, which is represented only by the standard in  
its entirety.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 1 – Dimensions  
F
FILTER  
MEDIA  
CABINET  
IN (mm)  
A
D
E
FLUE  
COLLAR*  
IN (mm)  
C.L. TOP AND  
BOTTOM FLUE  
COLLAR  
SHIP WT  
LB (KG)  
CABINET  
WIDTH  
IN (mm)  
SUPPLY---AIR  
WIDTH  
RETURN---AIR  
WIDTH  
FURNACE SIZE  
IN (mm)  
IN (mm)  
IN (mm)  
045---08/024045  
045---12/036045  
070---08/024070  
070---12/036070  
070---16/048070  
090---14/042090  
090---16/048090  
090---20/060090  
110---12/036110  
110---16/048110  
110---22/066110  
135---16/048135  
135---22/066135  
155---20/060155  
14---3/16 (360)  
14---3/16 (360)  
14---3/16 (360)  
14---3/16 (360)  
17---1/2 (445)  
17---1/2 (445)  
21 (533)  
21 (533)  
17---1/2 (445)  
21 (533)  
12---9/16 (319)  
12---9/16 (319)  
12---9/16 (319)  
12---9/16 (319)  
15---7/8 (403)  
15---7/8 (403)  
19---3/8 (492)  
19---3/8 (492)  
15---7/8 (403)  
19---3/8 (492)  
19---3/8 (492)  
19---3/8 (492)  
22---7/8 (581)  
22---7/8 (581)  
12---11/16 (322)  
12---11/16 (322)  
12---11/16 (322)  
12---11/16 (322)  
16 (406)  
9---5/16 (237)  
9---5/16 (237)  
9---5/16 (237)  
9---5/16 (237)  
11---9/16 (294)  
11---9/16 (294)  
13---5/16 (338)  
13---5/16 (338)  
11---9/16 (294)  
13---5/16 (338)  
13---5/16 (338)  
13---5/16 (338)  
15---1/16 (383)  
15---1/16 (383)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
4 (102)  
104 (47)  
107 (48)  
111 (50)  
115 (52)  
126 (57)  
127 (58)  
140 (64)  
146 (66)  
135 (61)  
146 (66)  
152 (69)  
149 (68)  
163 (74)  
170 (77)  
16 (406)  
16 (406)  
16 (406)  
16 (406)  
16 (406)  
16 (406)  
20 (508)  
20 (508)  
16 (406)  
20 (508)  
20 (508)  
20 (508)  
24 (610)  
24 (610)  
16 (406)  
19---1/2 (495)  
19---1/2 (495)  
16 (406)  
19---1/2 (495)  
19---1/2 (495)  
19---1/2 (495)  
23 (584)  
21 (533)  
21 (533)  
24---1/2 (622)  
24---1/2 (622)  
23 (584)  
* 5---in. or 6---in. (127 or 152 mm) vent connector may be required in some cases.  
{ 135 and 155 size furnaces require 5---in. (127 mm) or larger vents. Use a 4 to 5 or 4 to 6---in. (102 to 127 or 102 to 152 mm) vent adapter between furnace and  
vent connector.  
product and property damage. NOTE is used to highlight  
suggestions which will result in enhanced installation, reliability,  
or operation.  
11. See Fig. 2 for required clearances to combustible construc-  
tion.  
12. Maintain a 1--in. (25 mm) clearance from combustible ma-  
terials to supply air ductwork for a distance of 36 inches  
(914 mm) horizontally from the furnace. See NFPA 90B  
or local code for further requirements.  
1. Use only with type of gas approved for this furnace. Refer  
to the furnace rating plate 2. Install this furnace only in a  
2. Install this furnace only in a location and position as spe-  
cified in the “Location” section of these instructions.  
13. These furnaces SHALL NOT be installed directly on car-  
peting, tile, or any other combustible material other than  
wood flooring. In downflow installations, factory access-  
ory floor base MUST be used when installed on combust-  
ible materials and wood flooring. Special base is not re-  
quired when this furnace is installed on manufacturer’s  
Coil Assembly Part No. CAR, CAP, CNRV, CNPV or  
when Coil Box Part No. KCAKC is used. See Fig. 2 for  
clearance to combustible construction information.  
3. Provide adequate combustion and ventilation air to the  
furnace space as specified in “Air for Combustion and  
Ventilation” section.  
4. Combustion products must be discharged outdoors. Con-  
nect this furnace to an approved vent system only, as spe-  
cified in the “Venting” section of these instructions.  
5. Never test for gas leaks with an open flame. Use a com-  
mercially available soap solution made specifically for the  
detection of leaks to check all connections, as specified in  
the “Gas Piping” section.  
INTRODUCTION  
The Series 130/D 4--way multipoise Category I fan--assisted  
furnace is CSA (formerly A.G.A.. and C.G.A.) design--certified.  
A Category I fan--assisted furnace is an appliance equipped with  
an integral mechanical means to either draw or force products of  
combustion through the combustion chamber and/or heat  
exchanger. The furnace is factory--shipped for use with natural  
gas. This furnace is not approved for installation in mobile  
homes, recreational vehicles, or outdoors.  
6. Always install furnace to operate within the furnace’s in-  
tended temperature--rise range with a duct system which  
has an external static pressure within the allowable range,  
as specified in the “Start--Up, Adjustments, and Safety  
Check” section. See furnace rating plate.  
7. When a furnace is installed so that supply ducts carry air  
circulated by the furnace to areas outside the space con-  
taining the furnace, the return air shall also be handled by  
duct(s) sealed to the furnace casing and terminating out-  
side the space containing the furnace. See “Air Ducts” sec-  
tion.  
8. A gas--fired furnace for installation in a residential garage  
must be installed as specified in the warning box in the  
“Location” section.  
These furnaces shall not be installed directly on carpeting, tile, or  
any other combustible material other than wood flooring. For  
downflow installations, a factory accessory floor base must be  
used when installed on combustible materials and wood flooring.  
This special base is not required when this furnace is installed on  
the manufacturer’s coil assembly, or when the manufacturer’s coil  
box is used. See Fig. 2 for clearance to combustible material  
information.  
9. The furnace may be used for construction heat provided  
that the furnace installation and operation complies with  
the first CAUTION in the LOCATION section of these in-  
structions.  
10. These Multipoise Gas--Fired Furnaces are CSA (formerly  
A.G.A. and C.G.A.) design--certified for use with natural  
and propane gases (see furnace rating plate) and for install-  
ation in alcoves, attics, basements, closets, utility rooms,  
crawlspaces, and garages. The furnace is factory--shipped  
for use with natural gas. A CSA (A.G.A. and C.G.A.) lis-  
ted accessory gas conversion kit is required to convert fur-  
nace for use with propane gas.  
This furnace is designed for minimum continuous return--air  
temperature of 60_F (16_C) db or intermittent operation down to  
55_F (13_C) db such as when used with a night setback  
thermostat. Return--air temperature must not exceed 80_F (27_C)  
db. Failure to follow these return--air temperature limits may  
affect reliability of heat exchangers, motors, and controls. (See  
Fig. 3.)  
For accessory installation details, refer to the applicable  
instruction literature.  
NOTE: Remove all shipping brackets and materials before  
operating the furnace.  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
A08471  
Fig. 2 -- Clearances to Combustibles  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
90B as tested by UL Standard 181 for Class I Rigid Air Ducts  
80 / 27 C  
Step 6 — Gas Piping and Gas Pipe Pressure Testing  
S
US: NFPA 54 / ANSI Z223.1--2006; chapters 5, 6, 7, and 8 and  
National Plumbing Codes  
S
CANADA: CAN/CSA--B149.1--05 Parts 4, 5, and 6 and  
Appendices A, B, E and H.  
Step 7 — Electrical Connections  
S
US: National Electrical Code (NEC) ANSI/NFPA 70--2008  
S
CANADA: Canadian Electrical Code CSA C22.1  
Step 8 — Venting  
60 / 16 C  
S
US: NFGC; NFPA 54 / ANSI Z223.1--2006 chapters 12 and 13  
S
CANADA: CAN/CSA--B149.1--05 Part 8 and Appendix C  
ELECTROSTATIC DISCHARGE (ESD)  
PRECAUTIONS PROCEDURE  
A06745  
Fig. 3 -- Return Air Temperature  
!
CAUTION  
CODES AND STANDARDS  
FURNACE RELIABILITY HAZARD  
Follow all national and local codes and standards in addition  
to these instructions. The installation must comply with  
regulations of the serving gas supplier, local building, heating,  
plumbing, and other codes. In absence of local codes, the  
installation must comply with the national codes listed below and  
all authorities having jurisdiction.  
Improper installation or service of furnace may cause  
premature furnace component failure.  
Electrostatic discharge can affect electronic components.  
Follow the Electrostatic Discharge Precautions Procedure  
listed below during furnace installation and servicing to  
protect the furnace electronic control. Precautions will  
prevent electrostatic discharges from personnel and hand  
tools which are held during the procedure. These  
precautions will help to avoid exposing the control to  
electrostatic discharge by putting the furnace, the control,  
and the person at the same electrostatic potential.  
In the United States and Canada, follow all codes and standards  
for the following:  
Step 1 — Safety  
S
US: National Fuel Gas Code (NFGC) NFPA 54--2006/ANSI  
Z223.1--2006 and the Installation Standards, Warm Air Heating  
and Air Conditioning Systems ANSI/NFPA 90B  
S
CANADA: CSA B149.1--05 National Standard of Canada  
1. Disconnect all power to the furnace. Multiple disconnects  
may be required. DO NOT TOUCH THE CONTROL OR  
ANY WIRE CONNECTED TO THE CONTROL PRIOR  
Natural  
Gas  
and  
Propane  
Installation  
Code  
(CAN/CSA--B149.1--05)  
TO  
DISCHARGING  
YOUR  
BODY’S  
Step 2 — General Installation  
ELECTROSTATIC CHARGE TO GROUND.  
S
US: Current edition of the NFGC and the NFPA 90B. For  
copies, contact the National Fire Protection Association Inc.,  
only the NFGC, contact the American Gas Association, 400 N.  
Capitol Street, N.W., Washington DC 20001 (www.AGA.org.)  
2. Firmly touch the clean, unpainted, metal surface of the fur-  
nace chassis which is close to the control. Tools held in a  
person’s hand during grounding will be satisfactorily dis-  
charged.  
3. After touching the chassis, you may proceed to service the  
control or connecting wires as long as you do nothing to  
recharge your body with static electricity (for example;  
DO NOT move or shuffle your feet, do not touch un-  
grounded objects, etc.).  
S
CANADA: CAN/CSA--B149.1--05. For a copy, contact  
Standard Sales, CSA International, 178 Rexdale Boulevard,  
Etobicoke (Toronto), Ontario, M9W 1R3 Canada Step  
Step 3 — Combustion and Ventilation Air  
S
US: Section 9.3 of the NFGC, NFPA 54/ ANSI Z223.1--2006  
Air for Combustion and Ventilation  
4. If you touch ungrounded objects (and recharge your body  
with static electricity), firmly touch a clean, unpainted  
metal surface of the furnace again before touching control  
or wires.  
S
CANADA: Part 8 of CAN/CSA--B149.1--05, Venting Systems  
and Air Supply for Appliances  
5. Use this procedure for installed and uninstalled (ungroun-  
ded) furnaces.  
Step 4 — Duct Systems  
S
US and CANADA: Air Conditioning Contractors Association  
(ACCA) Manual D, Sheet Metal and Air Conditioning  
Contractors National Association (SMACNA), or American  
Society of Heating, Refrigeration, and Air Conditioning  
Engineers (ASHRAE) 2001 Fundamentals Handbook Chapter  
34 or 2000 HVAC Systems and Equipment Handbook Chapters  
9 and 16.  
6. Before removing a new control from its container, dis-  
charge your body’s electrostatic charge to ground to pro-  
tect the control from damage. If the control is to be in-  
stalled in a furnace, follow items 1 through 4 before  
bringing the control or yourself in contact with the fur-  
nace. Put all used and new controls into containers before  
touching ungrounded objects.  
Step 5 — Acoustical Lining and Fibrous Glass Duct  
7. An ESD service kit (available from commercial sources)  
may also be used to prevent ESD damage.  
S
US and CANADA: current edition of SMACNA and NFPA  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
THE BLOWER IS  
LOCATED BELOW THE  
BURNER SECTION, AND  
CONDITIONED AIR IS  
DISCHARGED UPWARD.  
THE BLOWER IS LOCATED  
TO THE RIGHT OF THE  
BURNER SECTION, AND  
AIR CONDITIONED AIR IS  
DISCHARGED TO THE LEFT.  
THE BLOWER IS  
THE BLOWER IS  
LOCATED ABOVE THE  
BURNER SECTION, AND  
CONDITIONED AIR IS  
DISCHARGED DOWNWARD  
LOCATED TO THE LEFT  
OF THE BURNER SECTION,  
AND CONDITIONED AIR IS  
DISCHARGED TO THE RIGHT.  
A02097  
Fig. 4 -- Multipoise Orientations  
The following types of furnace installations may require  
OUTDOOR AIR for combustion due to chemical exposures:  
LOCATION  
GENERAL  
S
S
S
S
S
Commercial buildings  
Buildings with indoor pools  
Laundry rooms  
This multipoise furnace is shipped in packaged configuration.  
Some assembly and modifications are required when used in any  
of the four applications shown in Fig. 4.  
Hobby or craft rooms, and  
Chemical storage areas  
NOTE:  
For high--altitude installations, the high--altitude  
conversion kit MUST be installed at or above 5500 ft. (1676 M)  
above sea level. Obtain high--altitude conversion kit from your  
area authorized distributor.  
If air is exposed to the following substances, it should not be used  
for combustion air, and outdoor air may be required for  
combustion:  
This furnace must:  
S
S
S
S
be installed so the electrical components are protected from  
water.  
S
S
S
S
S
S
S
S
S
S
S
S
Permanent wave solutions  
Chlorinated waxes and cleaners  
Chlorine based swimming pool chemicals  
Water softening chemicals  
not be installed directly on any combustible material other than  
wood flooring (refer to SAFETY CONSIDERATIONS).  
be located close to the chimney or vent and attached to an air  
distribution system. Refer to Air Ducts section.  
De--icing salts or chemicals  
Carbon tetrachloride  
be provided ample space for servicing and cleaning. Always  
comply with minimum fire protection clearances shown on the  
furnace clearance to combustible construction label.  
Halogen type refrigerants  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
!
WARNING  
CARBON MONOXIDE POISONING AND UNIT  
DAMAGE HAZARD  
Cements and glues  
Antistatic fabric softeners for clothes dryers  
S
Masonry acid washing materials  
Failure to follow this warning could result in personal  
injury or death, and furnace damage.  
All fuel--burning equipment must be supplied with air for fuel  
combustion. Sufficient air must be provided to avoid negative  
pressure in the equipment room or space. A positive seal must be  
made between the furnace cabinet and the return--air duct to  
prevent pulling air from the burner area and from draft safeguard  
opening.  
Corrosive or contaminated air may cause failure of parts  
containing flue gas, which could leak into the living space.  
Air for combustion must not be contaminated by halogen  
compounds, which include fluoride, chloride, bromide, and  
iodide. These elements can corrode heat exchangers and  
shorten furnace life. Air contaminants are found in aerosol  
sprays, detergents, bleaches, cleaning solvents, salts, air  
fresheners, and other household products. Do not install  
furnace in a corrosive or contaminated atmosphere. Make  
sure all combustion and circulating air requirements are met,  
in addition to all local codes and ordinances.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
!
WARNING  
FIRE, INJURY OR DEATH HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
When the furnace is installed in a residential garage, the  
burners and ignition sources must be located at least 18  
inches (457 mm) above the floor. The furnace must be  
located or protected to avoid damage by vehicles. When the  
furnace is installed in a public garage, airplane hangar, or  
other building having a hazardous atmosphere, the furnace  
must be installed in accordance with the NFGC or  
CAN/CSA--B149.1--05. (See Fig. 5.)  
A02054  
Fig. 6 -- Prohibit Installation on Back  
!
CAUTION  
PROPERTY DAMAGE HAZARD  
Improper use or installation of this furnace may cause  
premature component failure. This gas furnace may be used  
for construction heat provided that:  
--The furnace is permanently installed with all electrical  
wiring, piping, venting and ducting installed according to  
these installation instructions. A return air duct is provided,  
sealed to the furnace casing, and terminated outside the  
space containing the furnace. This prevents a negative  
pressure condition as created by the circulating air blower,  
causing a flame roll--out and/or drawing combustion  
products into the structure.  
18-IN. (457.2 mm)  
MINIMUM TO BURNERS  
--The furnace is controlled by a thermostat. It may not be  
”hot wired” to provide heat continuously to the structure  
without thermostatic control.  
A93044  
Fig. 5 -- Installation in a Garage  
--Clean outside air is provided for combustion. This is to  
minimize the corrosive effects of adhesives, sealers and  
other construction materials. It also prevents the  
entrainment of drywall dust into combustion air, which can  
cause fouling and plugging of furnace components.  
--The temperature of the return air to the furnace is  
maintained between 55_F (13_C) and 80_F (27_C), with  
no evening setback or shutdown. The use of the furnace  
while the structure is under construction is deemed to be  
intermittent operation per our installation instructions.  
--The air temperature rise is within the rated rise range on  
the furnace rating plate, and the gas input rate has been set  
to the nameplate value.  
!
WARNING  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
Do not install the furnace on its back or hang furnace with  
control compartment facing downward. Safety control  
operation will be adversely affected. Never connect  
return--air ducts to the back of the furnace. (See Fig. 6.)  
--The filters used to clean the circulating air during the  
construction process must be either changed or thoroughly  
cleaned prior to occupancy.  
--The furnace, ductwork and filters are cleaned as necessary  
to remove drywall dust and construction debris from all  
HVAC system components after construction is completed.  
--Verify proper furnace operating conditions including  
ignition, gas input rate, air temperature rise, and venting  
according to these installation instructions.  
LOCATION RELATIVE TO COOLING EQUIPMENT  
The cooling coil must be installed parallel with, or on the  
downstream side of the unit to avoid condensation in the heat  
exchangers. When installed parallel with the furnace, dampers or  
other flow control must prevent chilled air from entering the  
furnace. If the dampers are manually operated, they must be  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
equipped with means to prevent operation of either unit unless  
the damper is in the full--heat or full--cool position.  
The requirements for combustion and ventilation air depend upon  
whether or not the furnace is located in a space having a volume  
of at least 50 cubic feet per 1,000 Btuh input rating for all gas  
appliances installed in the space.  
AIR FOR COMBUSTION AND  
VENTILATION  
Provisions for adequate combustion, ventilation, and dilution air  
must be provided in accordance with:  
U.S. installations: Section 9.3 of the NFPA 54 /A ANSI  
Z223.1--2006, Air for Combustion and Ventilation, and  
applicable provisions of the local building codes.  
S
Spaces having less than 50 cubic feet per 1,000 Btuh require the  
Outdoor Combustion Air Method.  
S
Spaces having at least 50 cubic feet per 1,000 Btuh may use the  
Indoor Combustion Air, Standard or Known Air Infiltration  
Method.  
Outdoor Combustion Air Method  
1. Provide the space with sufficient air for proper combus-  
tion, ventilation, and dilution of flue gases using perman-  
ent horizontal or vertical duct(s) or opening(s) directly  
communicating with the outdoors or spaces that freely  
communicate with the outdoors.  
Canadian installations: Part 8 of the CAN/CSA--B149.1--05,  
Venting Systems and Air Supply for Appliances and all  
authorities having jurisdiction.  
!
CAUTION  
2. Fig. 7 illustrates how to provide TWO OUTDOOR  
OPENINGS, one inlet and one outlet combustion and  
ventilation air opening, to the outdoors.  
FURNACE CORROSION HAZARD  
Failure to follow this caution may result in furnace damage.  
a. One opening MUST commence within 12 in. (300 mm)  
of the ceiling and the second opening MUST commence  
within 12 in. (300 mm) of the floor.  
Air for combustion must not be contaminated by halogen  
compounds, which include fluoride, chloride, bromide, and  
iodide. These elements can corrode heat exchangers and  
shorten furnace life. Air contaminants are found in aerosol  
sprays, detergents, bleaches, cleaning solvents, salts, air  
fresheners, and other household products.  
b. Size openings and ducts per Fig. 7 and Table 2.  
2
c. TWOHORIZONTALDUCTSrequire1 --in of freearea  
2
per 2,000 Btuh (1,100 mm /kW) of combined input for  
all gas appliances in the space per Fig. 7 and Table 2.  
d. TWO OPENINGS OR VERTICAL DUCTS require 1  
2
2
-- i n of free area per 4,000 Btuh (550 mm /kW) for com-  
bined input of all gas appliances in the space per Fig. 7  
and Table 2.  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
3. ONE OUTDOOR OPENING requires:  
a. One square inch of free area per 3,000 Btuh (734  
mm /kW) for combined input of all gas appliances in the  
space per Table 2 and  
b. Not less than the sum of the areas of all vent connectors  
in the space.  
Failure to follow this warning could result in personal  
injury or death.  
2
The operation of exhaust fans, kitchen ventilation fans,  
clothes dryers, attic exhaust fans or fireplaces could create a  
NEGATIVE PRESSURE CONDITION at the furnace.  
Make--up air MUST be provided for the ventilation devices,  
in addition to that required by the furnace. Refer to Carbon  
Monoxide Poisoning Hazard warning in venting section of  
these instructions to determine if an adequate amount of  
make--up air is available.  
Table 2 – Minimum Free Area Required for Each Combustion Air opening of Duct to Outdoors  
TWO HORIZONTAL DUCTS  
(1 SQ. IN./2,000 BTUH) (1,100 SQ. MM/KW)  
SINGLE DUCT OR OPENING  
(1 SQ. IN./3,000 BTUH) (734 SQ. MM/KW)  
TWO OPENINGS OR VERTICAL DUCTS  
(1 SQ. IN./4,000 BTUH) (550 SQ. MM/KW)  
FURNACE  
INPUT  
(BTUH)  
Free Area of Opening  
and Duct  
Sq. In. (Sq. mm)  
Round Duct  
Dia.  
In. (mm)  
Free Area of Opening  
and Duct  
Sq. In. (Sq. mm)  
Round Duct  
Dia.  
In. (mm)  
Free Area of Opening  
and Duct  
Sq. In. (Sq. mm)  
Round Duct  
Dia.  
In. (mm)  
44,000  
66,000  
88,000  
110,000  
132,000  
154,000  
22 (14194)  
33 (21290)  
44 (28387)  
55 (35484)  
66 (42580)  
77 (49677)  
6 (152)  
7 (178)  
8 (203)  
9 (229)  
10 (254)  
10 (254)  
14.7 (9484)  
22 (14193)  
29.3 (18903)  
36.7 (23677)  
44 (28387)  
5 (127)  
6 (152)  
7 (178)  
7 (178)  
8 (203)  
9 (229)  
11 (7096)  
16.5 (10645)  
22 (14193)  
27.5 (17742)  
33 (21290)  
38.5 (24839)  
4 (102)  
5 (127)  
6 (152)  
6 (152)  
7 (178)  
8 (203)  
51.3 (33096)  
EXAMPLES: Determining Free Area  
FURNACE  
WATER HEATER  
TOTAL INPUT  
110,000  
66,000  
88,000  
+
+
+
30,000  
40,000  
30,000  
=
=
=
(140,000 divided by 4,000)  
(106,000 divided by 3,000)  
(118,000 divided by 2,000)  
=
=
=
35.0 Sq. In. for each two Vertical Ducts or Openings  
35.3 Sq. In. for a Single Duct or Opening  
59.0 Sq. In. for each of two Horizontal Ducts  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
1 SQ IN.  
PER 4000  
BTUH*  
CIRCULATING AIR  
DUCTS  
VENT THROUGH ROOF  
DUCTS  
TO  
OUTDOORS  
12" MAX(305mm)  
(305mm)  
12MAX  
D
12″  
(305mm)  
MAX  
1 SQ IN.  
PER 2000  
BTUH*  
VENT  
1 SQ IN.  
B
THROUGH  
ROOF  
F
PER 1000  
BTUH* IN DOOR  
OR WALL  
1 SQ IN.  
PER  
4000  
BTUH*  
UNCONFINED  
SPACE  
INTERIOR  
HEATED  
SPACE  
DUCTS  
TO  
OUTDOORS  
6" MIN (152mm)  
(FRONT)Ü  
1 SQ IN.  
1 SQ IN.  
PER  
PER 1000  
BTUH* IN DOOR  
OR WALL  
4000  
BTUH*  
1 SQ IN.  
PER 2000  
BTUH*  
E
G
A
12" MAX  
12″  
MAX  
(305mm)  
(305mm)  
(305mm)  
12MAX  
C
12MAX  
(305mm)  
CIRCULATING AIR DUCTS  
CIRCULATING AIR DUCTS  
DUCT  
TO  
OUTDOORS  
1 SQ IN.  
PER 4000  
BTUH*  
* Minimum opening size is 100 sq in. (64516 sq. mm) with minimum  
dimensions of 3 in. (76 mm)  
† Minimum of 3 in. (76 mm) when type-B1 vent is used.  
*Minimum dimensions of 3---in. (76 mm).  
Note: Use any of the following combinations of openings:  
A & B C & D D & E F & G  
A03175  
A03174  
Fig. 8 -- Air for Combustion, Ventilation, and Dilution from  
Indoors  
Fig. 7 -- Air for Combustion, Ventilation, and Dilution for  
Outdoors  
The Standard Method:  
The opening shall commence within 12 in. (300 mm) of the  
ceiling. Appliances in the space shall have clearances of at least 1  
in. (25 mm) from the sides and back and 6 in. (150 mm) from the  
front. The opening shall directly communicate with the outdoors  
or shall communicate through a vertical or horizontal duct to the  
outdoors or spaces (crawl or attic) that freely communicate with  
the outdoors.  
1. The space has no less volume than 50 cubic feet per 1,000  
Btuh of the maximum input ratings for all gas appliances  
installed in the space and  
2. The air infiltration rate is not known to be less than 0.40  
air changes per hour (ACH).  
The Known Air Infiltration Rate Method shall be used, if the  
infiltration rate is known to be:  
Indoor Combustion AirE NFPA & AGA Standard and  
Known--Air--Infiltration Rate Methods  
1. Less than 0.40 ACH and  
2. Equal to or greater than 0.10 ACH  
Indoor air is permitted for combustion, ventilation, and dilution,  
if the Standard or Known--Air--Infiltration Method is used.  
Infiltration rates greater than 0.60 ACH shall not be used. The  
minimum required volume of the space varies with the number of  
ACH and shall be determined per Table 3 or Equations 1 and 2.  
Determine the minimum required volume for each appliance in  
the space and add the volumes together to get the total minimum  
required volume for the space.  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in death and/or  
personal injury.  
Many homes require air to be supplied from outdoors for  
furnace combustion, ventilation, and dilution of flue gases.  
The furnace combustion air supply must be provided in  
accordance with this instruction manual.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 – Minimum Space Volumes for 100% Combustion, Ventilation, and Dilution from Indoors  
OTHER THAN FAN---ASSISTED TOTAL  
(1,000s BTUH GAS INPUT RATE)  
FAN---ASSISTED TOTAL  
(1,000s BTUH GAS INPUT RATE)  
ACH  
30  
40  
50  
44  
66  
88  
110  
132  
154  
Space Volume (ft.3)  
0.60  
0.50  
0.40  
0.30  
0.20  
0.10  
0.00  
1,050  
1,260  
1,575  
2,100  
3,150  
6,300  
NP  
1,400  
1,680  
2,100  
2,800  
4,200  
8,400  
NP  
1,750  
2,100  
2,625  
3,500  
5,250  
10,500  
NP  
1,100  
1,320  
1,650  
2,200  
3,300  
6,600  
NP  
1,650  
2,200  
2,640  
3,300  
4,400  
6,600  
13,200  
NP  
2,750  
3,300  
4,125  
5,500  
8,250  
16,500  
NP  
3,300  
3,960  
4,950  
6,600  
9,900  
19,800  
NP  
3,850  
4,620  
5,775  
7,700  
11,550  
23,100  
NP  
1,980  
2,475  
3,300  
4,950  
9,900  
NP  
NP = Not Permitted  
Table 3--Minimum Space Volumes were determined by using  
the following equations from the National Fuel Gas Code ANSI  
Z223.1--2006/NFPA 54--2006, 9.3.2.2:  
However, in buildings with unusually tight construction,  
additional air MUST be provided using the methods de-  
scribed in the Outdoor Combustion Air Method section.  
Unusually tight construction is defined as Construction  
with:  
1. For other than fan--assisted appliances, such as a draft  
hood--equipped water heater:  
a. Walls and ceilings exposed to the outdoors have a con-  
tinuous, sealed vapor barrier. Openings are gasketed or  
sealed and  
21ft3  
I other  
ACH 1000 Btu/hr  
Volume  
=
Other  
b. Doors and openable windows are weatherstripped and  
c. Other openings are caulked or sealed. These include  
joints around window and door frames, between sole  
plates and floors, between wall--ceiling joints, between  
wall panels, at penetrations for plumbing, electrical and  
gas lines, etc.  
A04002  
2. For fan--assisted appliances such as this furnace:  
15ft3  
I fan  
Volume  
=
Combination of Indoor and Outdoor Air  
Fan  
ACH 1000 Btu/hr  
1. Indoor openings shall comply with the Indoor Combus-  
tion Air Method below and,  
A04003  
If:  
I
2. Outdoor openings shall be located as required in the Out-  
door Combustion Air Method mentioned previously and,  
3. Outdoor openings shall be sized as follows:  
=
=
=
combined input of all other than fan--assisted  
appliances in Btuh/hr  
combined input of all fan--assisted appliances in  
other  
I
fan  
a. Calculate the Ratio of all Indoor Space volume divided  
by required volume for Indoor Combustion Air Meth-  
od below.  
Btuh/hr  
ACH  
air changes per hour (ACH shall not exceed 0.60.)  
b. Outdoor opening size reduction Factor is 1 minus the  
Ratio in a. above.  
c. Minimum size of Outdoor openings shall be the size re-  
quired in Outdoor Combustion AirMethod abovemul-  
tiplied by reduction Factor in b. above. The minimum  
dimension of air openings shall be not less than 3 in. (80  
mm).  
The following requirements apply to the Standard Method and  
to the Known Air Infiltration Rate Method.  
1. Adjoining rooms can be considered part of a space if:  
a. There are no closeable doors between rooms.  
b. Combining spaces on same floor level. Each opening  
2
shall have free area of at least 1 in. /1,000 Btuh (2,000  
2
mm /kW) of the total input rating of all gas appliances  
INSTALLATION  
UPFLOW INSTALLATION  
2
2
in the space, but not less than 100 in. (0.06 m ). One  
opening shall commence within 12 in. (300 mm) of the  
ceiling and the second opening shall commence within  
12 in. (300 mm) of the floor. The minimum dimension  
of air openings shall be at least 3 in. (80 mm). (See Fig.  
8.)  
Bottom Return Air Inlet  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. Remove and discard this panel when  
bottom return air is used. To remove bottom closure panel,  
perform the following:  
c. Combining space on different floor levels. The volumes  
of spaces on different floor levels shall be considered as  
communicating spaces if connected by one or more per-  
manent openings in doors or floors having free area of  
1. Tilt or raise furnace and remove 2 screws holding bottom  
filler panel. (See Fig. 9.)  
2. Rotate bottom filler panel downward to release holding  
tabs.  
2
2
at least 2 in. /1,000 Btuh (4,400 mm /kW) of total input  
rating of all gas appliances.  
3. Remove bottom closure panel.  
4. Reinstall bottom filler panel and screws.  
Side Return Air Inlet  
2. An attic or crawlspace may be considered a space that  
freely communicates with the outdoors provided there are  
adequate permanent ventilation openings directly to out-  
doors having free area of at least 1--in.2/4,000 Btuh of  
total input rating for all gas appliances in the space.  
3. In spaces that use the Indoor Combustion Air Method, in-  
filtration should be adequate to provide air for combus-  
tion, permanent ventilation and dilution of flue gases.  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. This panel MUST be in place when  
only side return air is used.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: Side return--air openings can be used in UPFLOW and  
most HORIZONTAL configurations. Do not use side return--air  
openings in DOWNFLOW configuration.  
DOWNFLOW INSTALLATION  
NOTE: For downflow applications, this furnace is approved for  
use on combustible flooring when any one of the following 3  
accessories are used:  
S
S
S
Special Base, KGASB  
Cased Coil Assembly Part No. CNPV, CNRV, CAP, and CAR  
Coil Box Part No. KCAKC  
1. Determine application being installed from Table 4.  
2. Construct hole in floor per Table 4 and Fig. 11.  
3. Construct plenum to dimensions specified in Table 4 and  
Fig. 11.  
4. If downflow subbase, KGASB is used, install as shown in  
Fig. 12. If Coil Assembly Part No. CNPV, CNRV, CAP,  
CAR or Coil Box Part No. KCAKC is used, install as  
shown in Fig. 13.  
NOTE: It is recommended that the perforated supply--air duct  
flanges be completely folded over or removed from furnace when  
installing the furnace on a factory--supplied cased coil or coil box.  
To remove the supply--air duct flange, use wide duct pliers or  
hand seamers to bend flange back and forth until it breaks off. Be  
careful of sharp edges. (See Fig. 14.)  
A02098  
Fig. 9 -- Removing Bottom Closure Panel  
Leveling Legs (If Desired)  
In upflow position with side return inlet(s), leveling legs may be  
used. (See Fig. 10.) Install field--supplied, 5/16 x 1--1/2 in. (8 x  
38 mm) (max) corrosion--resistant machine bolts, washers and  
nuts.  
NOTE: Bottom closure must be used when leveling legs are  
used. It may be necessary to remove and reinstall bottom closure  
panel to install leveling legs. To remove bottom closure panel, see  
item 1 in Bottom Return Air Inlet section in Step 1 above.  
Bottom Return Air Inlet  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. Remove and discard this panel when  
bottom return air is used. To remove bottom closure panel,  
perform the following:  
1. Tilt or raise furnace and remove 2 screws holding bottom  
filler panel. (See Fig. 9.)  
2. Rotate bottom filler panel downward to release holding  
tabs.  
3. Remove bottom closure panel.  
4. Reinstall bottom filler panel and screws.  
HORIZONTAL INSTALLATION  
To install leveling legs:  
1. Position furnace on its back. Locate and drill a hole in  
each bottom corner of furnace. (See Fig. 10.)  
2. For each leg, install nut on bolt and then install bolt and  
nut in hole. (Install flat washer if desired.)  
The furnace can be installed horizontally in an attic or crawl space  
on either the left--hand (LH) or right--hand (RH) side. The furnace  
can be hung from floor joists, rafters or trusses or installed on a  
non--combustible platform, blocks, bricks or pad.  
3. Install another nut on other side of furnace base. (Install  
flat washer if desired.)  
4. Adjust outside nut to provide desired height, and tighten  
inside nut to secure arrangement.  
5. Reinstall bottom closure panel if removed.  
!
WARNING  
5/  
16  
(8mm)  
FIRE, EXPLOSION, AND CARBON MONOXIDE  
POISONING HAZARD  
(8mm)  
5/  
16″  
Failure to follow this warning could result in personal  
injury, death, or property damage.  
1 3/4  
Do not install the furnace on its back or hang furnace with  
control compartment facing downward. Safety control  
operation will be adversely affected. Never connect  
return--air ducts to the back of the furnace.  
(44mm)  
1 3/4  
(44mm)  
Suspended Furnace Support  
The furnace may be supported under each end with threaded rod,  
angle iron or metal plumber’s strap as shown. (See Fig. 15 and  
16.) Secure angle iron to bottom of furnace as shown.  
Heavy--gauge sheet metal straps (plumber’s straps) may be used  
to suspend the furnace from each bottom corner. To prevent  
screws from pulling out, use 2 #8 x 3/4--in. (19 mm) screw into  
the side and 2 #8 x 3/4--in. (19 mm) screw in the bottom of the  
furnace casing for each strap. (See Fig. 15 and 16.)  
If the screws are attached to ONLY the furnace sides and not the  
bottom, the straps must be vertical against the furnace sides and  
not pull away from the furnace sides, so that the strap attachment  
screws are not in tension (are loaded in shear) for reliable support.  
(8mm)  
5/16″  
(8mm)  
5/  
16″  
(44mm)1 3/  
1 3/  
4″  
4
(44mm)  
A89014  
Fig. 10 -- Leveling Legs  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Platform Furnace Support  
FURNACE  
(OR COIL CASING  
WHEN USED)  
Construct working platform at location where all required furnace  
clearances are met. (See Fig. 2 and 17.) For furnaces with 1--in.  
(25 mm) clearance requirement on side, set furnace on  
non--combustible blocks, bricks or angle iron. For crawlspace  
installations, if the furnace is not suspended from the floor joists,  
the ground underneath furnace must be level and the furnace set  
on blocks or bricks.  
COMBUSTIBLE  
FLOORING  
Roll--Out Protection  
Provide a minimum 17--3/4--in. x 22--in. (451 x 559 mm) piece of  
sheet metal for flame roll--out protection in front of burner area  
for furnaces closer than 12 inches (305 mm) above the  
combustible deck or suspended furnaces closer than 12 inches  
(305 mm) to joists. The sheet metal MUST extend underneath the  
furnace casing by 1 in. (25 mm) with the door removed.  
The bottom closure panel on furnaces of widths 17--1/2 in. (445  
mm) and larger may be used for flame roll--out protection when  
bottom of furnace is used for return air connection. See Fig. 17  
for proper orientation of roll--out shield.  
DOWNFLOW  
SUBBASE  
SHEET METAL  
PLENUM  
FLOOR  
OPENING  
Bottom Return Air Inlet  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. Remove and discard this panel when  
bottom return air is used. To remove bottom closure panel,  
perform the following:  
1. Tilt or raise furnace and remove 2 screws holding bottom  
filler panel. (See Fig. 9.)  
2. Rotate bottom filler panel downward to release holding  
tabs.  
A96285  
Fig. 12 -- Furnace, Plenum, and Subbase installed on a  
Combustible Floor  
3. Remove bottom closure panel.  
4. Reinstall bottom filler panel and screws.  
Side Return Air Inlet  
FURNACE  
APPROVED  
COIL ASSEMBLY  
OR  
These furnaces are shipped with bottom closure panel installed in  
bottom return--air opening. This panel MUST be in place when  
side return air inlet(s) are used without a bottom return air inlet.  
COIL BOX  
COMBUSTIBLE  
FLOORING  
SHEET METAL  
PLENUM  
A
PLENUM  
OPENING  
FLOOR  
OPENING  
B
D
FLOOR  
OPENING  
C
A08556  
Fig. 13 -- Furnace, Plenum, and Coil Assembly or Coil Box  
Installed on a Combustible Floor  
A96283  
Fig. 11 -- Floor and Plenum Opening Dimensions  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4 – Opening dimensions -- In. (mm)  
PLENUM OPENING  
FURNACE  
CASING  
WIDTH  
FLOOR OPENING  
APPLICATION  
A
B
C
D
Upflow Applications on Combustible or Noncombustible Floor-  
ing (KGASB subbase not required)  
12---11/16  
(322)  
21---5/8  
(549)  
19  
(483)  
19  
(483)  
13---5/16  
(338)  
22---1/4  
(565)  
Downflow Applications on Noncombustible Flooring (KGASB  
subbase not required)  
12---9/16  
(319)  
13---3/16  
(335)  
19---5/8  
(498)  
14–3/16  
(376)  
Downflow applications on combustible flooring (KGASB sub-  
base required)  
11---13/16  
(284)  
13---7/16  
(341)  
20---5/8  
(600)  
Downflow Applications on Combustible Flooring with CNPV,  
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box  
(KGASB subbase not required)  
12---5/16  
(319)  
19  
13---5/16  
(338)  
20  
(483)  
(508)  
Upflow Applications on Combustible or Noncombustible Floor-  
ing (KGASB subbase not required)  
16  
(406)  
21---5/8  
(549)  
19  
(483)  
19  
(483)  
16---5/8  
(422)  
22---1/4  
(565)  
Downflow Applications on Noncombustible Flooring (KGASB  
subbase not required)  
15---7/8  
(403)  
16---1/2  
(419)  
19---5/8  
(498)  
17–1/2  
(445)  
Downflow applications on combustible flooring (KGASB sub-  
base required)  
15---1/8  
(384)  
16---3/4  
(425)  
20---5/8  
(600)  
Downflow Applications on Combustible Flooring with CNPV,  
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box  
(KGASB subbase not required)  
15---1/2  
(394)  
19  
16---1/2  
(419)  
20  
(483)  
(508)  
Upflow Applications on Combustible or Noncombustible Floor-  
ing (KGASB subbase not required)  
19---1/2  
(495)  
21---5/8  
(549)  
19  
(483)  
19  
(483)  
20---1/8  
(511)  
20  
(508)  
20---1/4  
(514)  
22---1/4  
(565)  
Downflow Applications on Noncombustible Flooring (KGASB  
subbase not required)  
19---3/8  
(492)  
19---5/8  
(498)  
21  
(533)  
Downflow applications on combustible flooring (KGASB sub-  
base required)  
18---5/8  
(473)  
20---5/8  
(600)  
Downflow Applications on Combustible Flooring with CNPV,  
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box  
(KGASB subbase not required)  
19  
19  
20  
20  
(483)  
(483)  
(508)  
(508)  
Upflow Applications on Combustible or Noncombustible Floor-  
ing (KGASB subbase not required)  
23  
(584)  
21---1/8  
(537)  
19  
(483)  
19  
(483)  
23---5/8  
(600)  
22---1/4  
(565)  
Downflow Applications on Noncombustible Flooring (KGASB  
subbase not required)  
22---7/8  
(581)  
23---1/2  
(597)  
19---5/8  
(498)  
24---1/2  
(622)  
Downflow applications on Combustible flooring (KGASB sub-  
base required)  
22---1/8  
(562)  
23---3/4  
(603)  
20---5/8  
(600)  
Downflow Applications on Combustible Flooring with CNPV,  
CNRV, CAR, or CAP Coil Assembly or KCAKC coil box  
(KGASB subbase not required)  
22---1/2  
(572)  
19  
(483)  
23---1/2  
(597)  
20  
(508)  
W
DOWNFLOW  
UPFLO  
HORIZONTAL  
90û  
90û  
YES  
YES  
YES  
YES  
YES  
YES  
120û  
MIN  
120û  
MIN  
120û  
MIN  
NOT  
NOT  
NOT  
RECOMMENDED  
RECOMMENDED  
RECOMMENDED  
A02329  
Fig. 14 -- Duct Flanges  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1
/
4" (6 mm) THREADED ROD  
4 REQ.  
OUTER DOOR  
ASSEMBLY  
SECURE ANGLE  
IRON TO BOTTOM  
OF FURNACE WITH  
3 #8 x 3  
/4" (19 mm) SCREWS  
TYPICAL FOR 2 SUPPORTS  
8” (203 mm) MIN FOR  
DOOR REMOVAL  
1" (25 mm) SQUARE, 11  
/4  
" x 11 " x 1  
/
4
/4  
"
(32 x 32 x 6 mm) ANGLE IRON  
OR UNI-STRUT MAY BE USED  
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS  
REQ. PER ROD  
A02345  
Fig. 15 -- Horizontal Unit Suspension  
METHOD 2  
USE (4) #8 x 3/4 (19 mm) SHEET  
METAL SCREWS FOR EACH  
STRAP. THE STRAPS  
SHOULD BE VERTICAL  
AGAINST THE FURNACE  
SIDES AND NOT PULL AWAY  
FROM THE FURNACE  
SIDES.  
METHOD 1  
FOLD ALL STRAPS UNDER  
FURNACE AND SECURE WTH  
(4) #8 x 3/4 (19 mm) SHEET METAL SCREWS  
(2 SCREWS IN SIDE AND 2 SCREWS  
IN BOTTOM).  
A03176  
Fig. 16 -- Horizontal Suspension with Straps  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LINE CONTACT ONLY PERMISSIBLE BETWEEN  
LINES FORMED BY INTERSECTIONS OF  
THE TOP AND TWO SIDES OF THE FURNACE  
JACKET AND BUILDING JOISTS,  
STUDS, OR FRAMING.  
17 3/4  
4 3/4  
(451mm)OVERALL  
(121mm) UNDER DOOR  
1(25mm) UNDER FURNACE  
GAS  
ENTRY  
TYPE-B  
VENT  
EXTEND OUT 12(305mm)  
FROM FACE OF DOOR  
2mm)  
(15  
*
IN  
M
6
30-IN. (762mm)  
MIN WORK AREA  
* WHEN USED WITH  
SINGLE WALL VENT  
CONNECTIONS  
17 3/4  
(451mm)  
SHEET  
METAL  
22  
EQUIPMENT MANUAL  
SHUT-OFF GAS VALVE  
SEDIMENT  
TRAP  
UNION  
A03177  
Fig. 17 -- Typical Attic Installation  
Not all horizontal furnaces are approved for side return air  
connections. (See Fig. 20.)  
FILTER ARRANGEMENT  
Secure ductwork with proper fasteners for type of ductwork used.  
Seal supply-- and return--duct connections to furnace with code  
approved tape or duct sealer.  
NOTE: Flexible connections should be used between ductwork  
and furnace to prevent transmission of vibration.  
!
WARNING  
Ductwork passing through unconditioned space should be  
insulated to enhance system performance. When air conditioning  
is used, a vapor barrier is recommended.  
Maintain a 1--in. (25 mm) clearance from combustible materials  
to supply air ductwork for a distance of 36 in. (914 mm)  
horizontally from the furnace. See NFPA 90B or local code for  
further requirements.  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal  
injury, or death.  
Never operate a furnace without a filter or with filter access  
door removed.  
Ductwork Acoustical Treatment  
There are no provisions for an internal filter rack in these  
furnaces. An external filter rack is required.  
NOTE: Metal duct systems that do not have a 90_ elbow and 10  
ft. (3 M) of main duct to the first branch take--off may require  
internal acoustical lining. As an alternative, fibrous ductwork may  
be used if constructed and installed in accordance with the latest  
edition of SMACNA construction standard on fibrous glass  
ducts. Both acoustical lining and fibrous ductwork shall comply  
with NFPA 90B as tested by UL Standard 181 for Class 1 Rigid  
air ducts.  
This furnace is shipped with a factory--supplied Media Filter  
Cabinet. The Media Filter Cabinet uses either a factory--supplied  
standard 3/4--in. (19 mm) filter or 4--in. (102 mm) wide Media  
Filter which can be purchased separately.  
Refer to the instructions supplied with Media Cabinet for  
assembly and installation options.  
AIR DUCTS  
Supply Air Connections  
General Requirements  
For a furnace not equipped with a cooling coil, the outlet duct  
shall be provided with a removable access panel. This opening  
shall be accessible when the furnace is installed and shall be of  
such a size that the heat exchanger can be viewed for possible  
openings using light assistance or a probe can be inserted for  
sampling the air stream. The cover attachment shall prevent leaks.  
The duct system should be designed and sized according to  
accepted national standards such as those published by: Air  
Conditioning Contractors Association (ACCA), Sheet Metal and  
Air Conditioning Contractors National Association (SMACNA)  
or American Society of Heating, Refrigerating and Air  
Conditioning Engineers (ASHRAE) or consult The Air Systems  
Design Guidelines reference tables available from your local  
distributor. The duct system should be sized to handle the  
required system design CFM at the design external static pressure.  
The furnace airflow rates are provided in Table 5--Air Delivery  
CFM (With Filter).  
When a furnace is installed so that the supply ducts carry air  
circulated by the furnace to areas outside the space containing the  
furnace, the return air shall also be handled by duct(s) sealed to  
the furnace casing and terminating outside the space containing  
the furnace.  
Upflow and Horizontal Furnaces  
Connect supply--air duct to flanges on furnace supply--air outlet.  
Bend flange upward to 90_ with wide duct pliers. (See Fig. 14.)  
The supply--air duct must be connected to ONLY the furnace  
supply--outlet--air duct flanges or air conditioning coil casing  
(when used). DO NOT cut main furnace casing side to attach  
supply air duct, humidifier, or other accessories. All accessories  
MUST be connected to duct external to furnace main casing.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 – Air Delivery -- CFM (With Filter)*  
EXTERNAL STATIC PRESSURE (IN. WC)  
FURNACE  
SIZE  
RETURN---AIR  
INLET  
SPEED  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
1120  
1075  
1020  
960  
895  
750  
650  
555  
1175  
1090  
985  
895  
745  
815  
680  
585  
495  
1085  
1015  
920  
835  
700  
720  
600  
505  
405  
980  
930  
835  
765  
635  
605  
500  
400  
305  
860  
830  
740  
685  
555  
455  
345  
235  
--- ---  
725  
700  
620  
570  
445  
340  
195  
--- ---  
045---08 /  
024045  
Bottom or  
Side(s)  
930  
890  
850  
805  
820  
725  
1465  
1295  
1150  
1030  
860  
785  
690  
1400  
1260  
1120  
1010  
835  
750  
655  
700  
605  
--- ---  
High  
1325  
1210  
1085  
980  
1250  
1155  
1040  
945  
560  
545  
510  
345  
260  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
045---12/  
036045  
Bottom or  
Side(s)  
810  
780  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
1140  
915  
1105  
885  
1055  
855  
1010  
825  
955  
785  
655  
550  
1240  
1085  
965  
845  
670  
885  
725  
600  
475  
1170  
1030  
925  
815  
640  
815  
655  
510  
415  
1090  
970  
875  
770  
600  
715  
530  
420  
340  
1000  
890  
800  
700  
540  
545  
420  
325  
245  
890  
785  
700  
605  
460  
390  
280  
--- ---  
070---081 /  
024070  
Bottom or  
Side(s)  
795  
770  
740  
700  
690  
665  
630  
590  
--- ---  
High  
1440  
1180  
1015  
885  
1400  
1165  
1020  
885  
1355  
1150  
1010  
880  
1300  
1125  
990  
865  
690  
745  
645  
560  
475  
345  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
070---12/  
036070  
Bottom or  
Side(s)  
695  
700  
700  
High  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
1840  
1610  
1460  
1260  
1065  
1790  
1575  
1430  
1240  
1040  
1730  
1535  
1400  
1215  
1015  
1670  
1485  
1360  
1180  
985  
1605  
1435  
1315  
1145  
955  
1530  
1370  
1260  
110  
1450  
1305  
1205  
1040  
875  
1370  
1230  
1130  
985  
1275  
1145  
1055  
915  
1170  
1055  
965  
070---16/  
048070  
Bottom or  
Side(s)  
835  
915  
825  
765  
695  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
1650  
1515  
1385  
1205  
2060  
1710  
1470  
1260  
1030  
1600  
1485  
1360  
1180  
2000  
1695  
1475  
1365  
1025  
1535  
1440  
1320  
1160  
1930  
1665  
1450  
1245  
1020  
1465  
1380  
1260  
1120  
1835  
1585  
1390  
1225  
990  
1385  
1300  
1195  
1065  
1755  
1480  
1335  
1165  
940  
1285  
1220  
1120  
1005  
1620  
1390  
1230  
1090  
890  
1175  
1115  
1025  
925  
1055  
990  
895  
830  
710  
630  
1115  
955  
855  
750  
615  
645  
600  
565  
510  
910  
775  
690  
600  
500  
090---14/  
042090  
Bottom or  
Side(s)  
915  
810  
1490  
1245  
1120  
995  
1315  
1110  
1005  
880  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
090---16/  
048090  
Bottom or  
Side(s)  
810  
720  
High  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
2380  
2185  
1905  
1595  
1340  
2295  
2115  
1865  
1565  
1310  
2205  
2045  
1815  
1530  
1280  
2105  
1960  
1740  
1485  
1225  
2005  
1875  
1670  
1430  
1170  
1900  
1770  
1590  
1355  
1120  
1775  
1655  
1490  
1275  
1040  
1650  
1535  
1390  
1160  
955  
1510  
1400  
1245  
1055  
850  
1335  
1240  
1110  
920  
Bottom Only  
750  
High  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
2485  
2175  
1845  
1540  
1280  
2415  
2130  
1815  
1515  
1250  
2330  
2070  
1770  
1475  
1220  
2230  
2000  
1720  
1435  
1190  
2135  
1930  
1655  
1385  
115  
2030  
1840  
1580  
1335  
1105  
1920  
1740  
1500  
1270  
1035  
1790  
1620  
1395  
1175  
945  
1645  
1495  
1270  
1045  
845  
1485  
1345  
1090  
915  
090---20/  
060090  
Both Side or 1  
Side & Bottom  
745  
High  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
2420  
2160  
1850  
1530  
1290  
2345  
2110  
1815  
1490  
1250  
2265  
2045  
1765  
1455  
1220  
2165  
1960  
1710  
1420  
1190  
2070  
1885  
1635  
1375  
115  
1960  
1790  
1560  
1320  
1110  
1850  
1695  
1480  
1250  
1040  
1720  
1570  
1380  
1160  
950  
1570  
1445  
1250  
1055  
835  
1420  
1305  
1110  
905  
1Side Only  
740  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
1625  
1510  
1360  
1195  
2055  
1750  
1545  
1300  
1050  
1575  
1470  
1335  
1180  
1990  
1725  
1525  
1290  
1045  
1515  
1415  
1295  
1155  
1910  
1670  
1490  
1275  
1015  
1445  
1355  
1250  
1115  
1815  
1605  
1445  
1235  
975  
1355  
1285  
1180  
1065  
1695  
1515  
1355  
1165  
935  
1260  
1185  
1100  
980  
1575  
1400  
1260  
1085  
880  
1165  
1070  
985  
990  
890  
785  
725  
670  
605  
1090  
975  
880  
750  
610  
595  
530  
475  
410  
910  
785  
750  
620  
515  
110---12/  
036110  
Bottom or  
Side(s)  
810  
860  
740  
High  
1425  
1255  
1135  
1005  
815  
1230  
1120  
1020  
895  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
110---16/  
048110  
Bottom or  
Side(s)  
715  
High  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
2530  
2225  
1895  
1565  
1320  
2460  
2190  
1885  
1555  
1295  
2380  
2135  
1865  
1535  
1265  
2285  
2075  
1820  
1505  
1235  
2200  
1995  
1770  
1465  
1205  
2085  
1910  
1700  
1410  
1160  
1970  
1805  
1610  
1350  
1105  
1835  
1695  
1520  
1265  
1035  
1695  
1565  
1410  
1175  
950  
1545  
1430  
1290  
1050  
870  
Bottom Only  
Bottom Sides or  
1 Side & Bottom  
High  
Me d --- H i g h  
--- ---  
2205  
--- ---  
2175  
2415  
2120  
2330  
2065  
2235  
1975  
2125  
1900  
1995  
1790  
1860  
1685  
1735  
1580  
1605  
1460  
110---22/  
066110  
High  
Me d --- H i g h  
Medium  
Me d --- L o w  
Low  
2485  
2155  
1830  
1520  
1275  
2430  
2135  
1830  
1505  
1260  
2360  
2100  
1810  
1490  
1240  
2270  
2040  
1780  
1470  
1210  
2175  
1970  
1730  
1430  
1180  
2070  
1885  
1665  
1385  
1135  
1950  
1790  
1595  
1330  
1090  
1825  
1680  
1505  
1250  
1025  
1685  
1560  
1395  
1165  
930  
1535  
1420  
1275  
1055  
840  
1Side Only  
*A filter is required for each return---air inlet. Airflow performance included 3/4---in. (19 mm) washable filter media such as contained in factory ---authorized ac-  
cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.  
--- --- Indicates unstable operating conditions.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 5 -- Air Delivery -- CFM (With Filter)* (Cont.)  
EXTERNAL STATIC PRESSURE (IN. WC)  
FURNACE  
SIZE  
RETURN---AIR  
INLET  
SPEED  
0.1  
0.2  
0.3  
0.4  
0.5  
0.6  
0.7  
0.8  
0.9  
1.0  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
2090  
1790  
1545  
1325  
2010  
1755  
1525  
1320  
1930  
1705  
1500  
1295  
1835  
1640  
1450  
1265  
1710  
1550  
1380  
1210  
1590  
1465  
1315  
1150  
1470  
1360  
1215  
995  
1335  
1210  
1005  
865  
1025  
945  
855  
745  
835  
785  
670  
540  
Bottom  
or  
Side(s)  
135---16/  
048135  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
2485  
2195  
1880  
1640  
2400  
2150  
1850  
1635  
2310  
2090  
1820  
1615  
2215  
2000  
1780  
1585  
2110  
1920  
1715  
1530  
2000  
1825  
1635  
1465  
1880  
1720  
1540  
1370  
1725  
1565  
1415  
1255  
1535  
1405  
1290  
1150  
1355  
1255  
1160  
1040  
Bottom  
Only  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
--- ---  
--- ---  
2385  
2060  
1820  
1615  
2305  
2010  
1780  
1585  
2195  
1945  
1715  
1530  
2085  
1865  
1635  
1465  
1960  
1765  
1540  
1370  
1825  
1660  
1415  
1255  
1670  
1515  
1290  
1150  
1465  
1325  
1160  
1040  
Bottom Sides  
or  
1 Side & Bottom  
135---22/  
066135  
2180  
1880  
1640  
2145  
1850  
1635  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
High  
Me d --- H i g h  
Me d --- L o w  
Low  
2320  
2125  
1845  
1640  
2465  
2115  
1800  
1570  
2250  
2065  
1825  
1620  
2430  
2105  
1790  
1565  
2155  
1995  
1765  
1580  
2375  
2075  
1770  
1550  
2055  
1910  
1710  
1540  
2305  
2030  
1735  
1525  
1970  
1815  
1650  
1485  
2230  
1980  
1695  
1495  
1855  
1710  
1570  
1410  
2110  
1910  
1640  
1445  
1725  
1610  
1475  
1330  
2000  
1830  
1570  
1370  
1600  
1490  
1370  
1220  
1865  
1725  
1465  
1270  
1450  
1340  
1240  
1080  
1725  
1590  
1345  
1175  
1280  
1175  
1100  
960  
1545  
1425  
1225  
1070  
1 Side Only  
Bottom Only  
155---20/  
060155  
Both Sides Or 1  
Side & Bottom  
High  
Me d --- H i g h  
--- ---  
2155  
--- ---  
2135  
2375  
2095  
2285  
2040  
2200  
1975  
2105  
1895  
1995  
1790  
1870  
1685  
1730  
1550  
1570  
1400  
High  
Me d --- H i g h  
--- ---  
2140  
--- ---  
2095  
2260  
2040  
2180  
1975  
2085  
1890  
1975  
1810  
1865  
1705  
1740  
1595  
1605  
1480  
1455  
1325  
1 Side Only  
*A filter is required for each return---air inlet. Airflow performance included 3/4---in. (19 mm) washable filter media such as contained in factory ---authorized ac-  
cessory filter rack. To determine airflow performance without this filter, assume an additional 0.1 in. wc available external static pressure.  
--- --- Indicates unstable operating conditions.  
NOTE: For horizontal applications, the top--most flange may be  
bent past 90_ to allow the evaporator coil to hang on the flange  
temporarily while the remaining attachment and sealing of the  
coil are performed.  
20.) Not all horizontal furnaces are approved for side return air  
connections. (See Fig. 20.)  
GAS PIPING  
Downflow Furnaces  
!
WARNING  
Connect supply--air duct to supply--air outlet on furnace. Bend  
flange inward past 90_ with wide duct pliers. (See Fig. 14.) The  
supply--air duct must be connected to ONLY the furnace  
supplyoutlet or air conditioning coil casing (when used). When  
installed on combustible material, supply--air duct must be  
connected to ONLY the accessory subbase, KGASB0201ALL, or  
a factory approved air conditioning coil casing. DO NOT cut  
main furnace casing to attach supply side air duct, humidifier, or  
other accessories. All accessories MUST be connected to duct  
external to furnace casing.  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
Never purge a gas line into a combustion chamber. Never  
test for gas leaks with an open flame. Use a commercially  
available soap solution made specifically for the detection  
of leaks to check all connections.  
Return Air Connections  
!
WARNING  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
Failure to follow this warning could cause personal injury,  
death and/or property damage.  
Use proper length of pipe to avoid stress on gas control  
manifold and a gas leak.  
Never connect return--air ducts to the back of the furnace.  
Follow instructions below.  
Downflow Furnaces  
!
WARNING  
The return--air duct must be connected to return--air opening  
(bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides  
(left or right). Side opening is permitted for only upflow and most  
horizontal furnaces. Bypass humidifier connections should be  
made at ductwork or coil casing sides exterior to furnace. (See  
Fig. 19.)  
FIRE OR EXPLOSION HAZARD  
Failure to protect gas valve inlet from water and debris  
could result in death, personal injury and/or property  
damage.  
Gas valve inlet and/or inlet pipe must remain capped until  
gas supply line is permanently installed to protect the valve  
from moisture and debris. Also, install a sediment trap in the  
gas supply piping at the inlet to the gas valve.  
Upflow and Horizontal Furnaces  
The return--air duct must be connected to bottom, sides (left or  
right), or a combination of bottom and side(s) of main furnace  
casing as shown in Fig. 1. Bypass humidifier may be attached  
into unused return air side of the furnace casing. (See Fig. 18 and  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A02075  
Fig. 18 -- Upflow Return Air Configurations and Restrictions  
A02163  
Fig. 19 -- Downflow Return Air Configurations and Restrictions  
A02162  
Fig. 20 -- Horizontal Return Air Configurations and Restrictions  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Gas piping must be installed in accordance with national and  
local codes. Refer to current edition of NFGC in the U.S. and the  
CAN/CSA--B149.1--05 in Canada.  
supply connection to furnace and downstream of manual  
equipment shutoff valve.  
NOTE: The furnace gas control valve inlet pressure tap  
connection is suitable to use as test gauge connection providing  
test pressure DOES NOT exceed maximum 0.5 psig (14--in. wc)  
stated on gas control valve. (See Fig. 53.) Some installations  
require gas entry on right side of furnace (as viewed in upflow).  
(See Fig. 21.)  
Table 6 – Maximum Capacity of Pipe  
NOMINAL  
IRON PIPE  
SIZE  
LENGTH OF PIPE --- FT. (M)  
INTERNAL  
DIA.  
IN. (MM)  
10  
20  
30  
40  
50  
(3.0)  
(6.0)  
(9.1)  
(12.1)  
(15.2)  
IN. (MM)  
0.622  
(158)  
1/2 (12.7)  
3/4 (19.0)  
1( 25.4)  
175  
360  
120  
250  
97  
200  
375  
770  
1180  
82  
73  
0.824  
(20.9)  
170  
320  
660  
990  
151  
285  
580  
900  
1.049  
(26.6)  
680  
465  
1-1/4  
(31.8)  
1-1/2  
(38.1)  
1.380  
(35.0)  
1400  
2100  
950  
1.610  
(40.9)  
1460  
2(51mm)  
* Cubic ft. of natural gas per hr for gas pressures of 0.5 psig (14---in. wc)  
or less and a pressure drop of 0.5---in. wc (based on a 0.60 specific  
gravity gas). Ref: Table 6.2 ANSI Z223---2006/NFPA 54---2006.  
Street Elbow  
Installations must be made in accordance with all authorities  
having jurisdiction. If possible, the gas supply line should be a  
separate line running directly from meter to furnace.  
A08551  
Fig. 21 -- Burner and Manifold  
NOTE: In the state of Massachusetts:  
Install a sediment trap in riser leading to furnace as shown in Fig.  
22. Connect a capped nipple into lower end of tee. Capped nipple  
should extend below level of furnace gas controls. Place a ground  
joint union between furnace gas control valve manifold and  
exterior manual equipment gas shutoff valve.  
1. Gas supply connections MUST be performed by a li-  
censed plumber or gas fitter.  
2. When flexible connectors are used, the maximum length  
shall not exceed 36 inches (915 mm).  
3. When lever handle type manual equipment shutoff valves  
are used, they shall be T--handle valves.  
GAS  
SUPPLY  
4. The use of copper tubing for gas piping is NOT approved  
by the state of Massachusetts.  
MANUAL  
SHUTOFF  
VALVE  
Refer to Table 6 for recommended gas pipe sizing. Risers must be  
used to connect to furnace and to meter. Support all gas piping  
with appropriate straps, hangers, etc. Use a minimum of 1 hanger  
every 6 ft. (1.8 M). Joint compound (pipe dope) should be  
applied sparingly and only to male threads of joints. Pipe dope  
must be resistant to the action of propane gas.  
(REQUIRED)  
SEDIMENT  
TRAP  
UNION  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
If local codes allow the use of a flexible gas appliance  
connector, always use a new listed connector. Do not use a  
connector which has previously served another gas  
appliance. Black iron pipe shall be installed at the furnace  
gas control valve and extend a minimum of 2 in. (51 mm)  
outside the furnace.  
A02035  
Fig. 22 -- Typical Gas Pipe Arrangement  
!
CAUTION  
FURNACE DAMAGE HAZARD  
Failure to follow this caution may result in furnace damage.  
Connect gas pipe to furnace using a backup wrench to  
avoid damaging gas controls and burner misalignment.  
An accessible manual equipment shutoff valve MUST be  
installed external to furnace casing and within 6 ft. of furnace. A  
1/8--in. (3 mm) NPT plugged tapping, accessible for test gauge  
connection, MUST be installed immediately upstream of gas  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD 24-VOLT WIRING  
FIELD 115-, 208/230-, 460-VOLT WIRING  
FACTORY 24-VOLT WIRING  
FACTORY 115-VOLT WIRING  
NOTE 2  
1-STAGE  
THERMOSTAT  
TERMINALS  
W
C
Y
R
G
FIVE  
WIRE  
FIELD-SUPPLIED  
FUSED DISCONNECT  
THREE-WIRE  
HEATING-  
ONLY  
208/230- OR  
460-VOLT  
THREE  
PHASE  
W2  
BLK  
BLK  
COM  
W/W1  
WHT  
WHT  
208/230-  
VOLT  
SINGLE  
PHASE  
GND  
NOTE 1  
Y/Y2  
115-VOLT FIELD- JUNCTION  
SUPPLIED  
FUSED  
BOX  
R
G
GND  
CONTROL  
BOX  
CONDENSING  
UNIT  
DISCONNECT  
24-VOLT  
TERMINAL  
BLOCK  
NOTES: 1. Connect Y/Y2-terminal as shown for proper operation.  
2. Some thermostats require a "C" terminal connection as shown.  
3. If any of the original wire, as supplied, must be replaced, use  
same type or equivalent wire.  
FURNACE  
A95236  
Fig. 23 -- Field Wiring Diagram  
A 1/8--in. (3 mm) NPT plugged tapping, accessible for test gauge  
connection, MUST be installed immediately upstream of gas  
supply connection to furnace and downstream of manual  
equipment shutoff valve.  
!
WARNING  
ELECTRICAL SHOCK AND FIRE HAZARD  
Piping should be pressure and leak tested in accordance with  
NFGC in the United States or CAN/CSA--B149.1--05 in Canada,  
local, and national plumbing and gas codes before the furnace has  
been connected. After all connections have been made, purge  
lines and check for leakage at furnace prior to operating furnace.  
If pressure exceeds 0.5 psig (14--in. wc), gas supply pipe must be  
disconnected from furnace and capped before and during supply  
pipe pressure test. If test pressure is equal to or less than 0.5 psig  
(14--in. wc), turn off electric shutoff switch located on furnace gas  
control valve and accessible manual equipment shutoff valve  
before and during supply pipe pressure test. After all connections  
have been made, purge lines and check for leakage at furnace  
prior to operating furnace.  
Failure to follow this warning could result in personal  
injury, death, or property damage.  
The cabinet MUST have an uninterrupted or unbroken  
ground according to NEC ANSI/NFPA 70--2008 and  
Canadian Electrical Code CSA C22.1 or local codes to  
minimize personal injury if an electrical fault should occur.  
This may consist of electrical wire, conduit approved for  
electrical ground or a listed, grounded power cord (where  
permitted by local code) when installed in accordance with  
existing electrical codes. Refer to the power cord  
manufacturer’s ratings for proper wire gauge. Do not use  
gas piping as an electrical ground.  
The gas supply pressure shall be within the maximum and  
minimum inlet supply pressures marked on the rating plate with  
the furnace burners ON and OFF.  
!
CAUTION  
ELECTRICAL CONNECTIONS  
FURNACE MAY NOT OPERATE HAZARD  
!
WARNING  
Failure to follow this caution may result in intermittent  
furnace operation.  
ELECTRICAL SHOCK HAZARD  
Furnace control must be grounded for proper operation or  
else control will lock out. Control must remain grounded  
through green/yellow wire routed to gas valve and manifold  
bracket screw.  
Failure to follow this warning could result in personal  
injury or death.  
Blower access panel door switch opens 115--v power to  
control. No component operation can occur. Do not bypass  
or close switch with panel removed.  
115--V WIRING  
Verify that the voltage, frequency, and phase correspond to that  
specified on unit rating plate. Also, check to be sure that service  
provided by utility is sufficient to handle load imposed by this  
equipment. Refer to rating plate or Table 7 for equipment  
electrical specifications.  
See Fig. 23 for field wiring diagram showing typical field 115--v  
wiring. Check all factory and field electrical connections for  
tightness.  
Field--supplied wiring shall conform with the limitations of 63_F  
(33_C) rise.  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 – Electrical Data  
MAXIMUM  
WIRE  
MAXIMUM  
OPERATING VOLTAGE  
RANGE  
V O LT S ---  
H E R T Z ---  
PHASE  
MAX  
UNIT  
MINIMUM  
WIRE  
FUSE OR  
FURNACE  
UNIT  
L E N G T H ---  
FT. (M)‡  
49 (14.9)  
38 (11.5)  
51 (15.5)  
37 (11.2)  
27 (8.2)  
CKT BKR  
AMPS†  
15  
SIZE  
AMPACITY#  
AMPS  
GAUGE  
MAX*  
MIN.*  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
1 1 5 --- 6 0 --- 1  
127  
127  
127  
127  
127  
127  
127  
127  
127  
127  
127  
127  
127  
127  
104  
104  
104  
104  
104  
104  
104  
104  
104  
104  
104  
104  
104  
104  
5.3  
7.1  
5.2  
7.3  
10.1  
8.2  
9.9  
12.9  
8.2  
10.1  
13.7  
10.2  
14.5  
15.0  
045---08/024045  
045---12/036045  
070---08/024070  
070---12/036070  
070---16/048070  
090---14/042090  
090---16/048090  
090---20/060090  
110---12/036110  
110---16/048110  
110---22/066110  
135---16/048135  
135---22/066135  
155---20/060155  
7.42  
9.67  
7.22  
14  
14  
14  
14  
14  
14  
14  
12  
14  
14  
12  
14  
12  
12  
15  
15  
15  
15  
15  
15  
20  
15  
15  
20  
15  
20  
9.90  
13.42  
10.84  
13.0  
16.70  
10.76  
13.19  
17.60  
13.28  
18.61  
19.34  
34 (10.3)  
28 (8.5)  
34 (10.3)  
34 (10.3)  
28 (8.5)  
32 (9.7)  
27 (8.2)  
30 (9.1)  
29 (8.8)  
20  
* Permissible limits of the voltage range at which the unit operates satisfactorily.  
# Unit ampacity = 125% of largest operating component’s full load amps plus 100% of all other potential operating components (EAC, humidifier,  
etc.) full load amps.  
{ Time---delay type is recommended.  
} Length shown is as measured 1 way along wire path between unit and service panel for maximum 2% voltage drop.  
U.S. Installations: Make all electrical connections in accordance  
with National Electrical Code (NEC) ANSI/NFPA 70--2008 and  
any local codes or ordinances that might apply.  
4. Fasten J--Box to casing with the two screws removed in  
Step 1.  
5. Route J--Box wires within furnace away from sharp edges,  
rotating parts, and hot surfaces.  
Canadian Installations: Make all electrical connections in  
accordance with Canadian Electrical Code CSA C22.1 or  
authorities having jurisdiction.  
!
WARNING  
FIRE HAZARD  
TWO  
Failure to follow this warning could result in personal  
injury, death, or property damage.  
Do not connect aluminum wire between disconnect switch  
and furnace. Use only copper wire.  
Use a separate branch electrical circuit with a properly sized fuse  
or circuit breaker for this furnace. See Table 7 for wire size and  
fuse specifications. A readily accessible means of electrical  
disconnect must be located within sight of the furnace.  
NOTE: Proper polarity must be maintained for 115--v wiring. If  
polarity is incorrect, control LED status indicator light will flash  
rapidly and furnace will NOT operate.  
A02099  
Fig. 24 -- Relocating J--Box  
J--BOX RELOCATION  
ELECTRICAL CONNECTION TO J--BOX  
NOTE: If factory location of J--Box is acceptable, go to next  
section (ELECTRICAL CONNECTION TO J--BOX).  
Field--Supplied Electrical Box on Furnace J--Box Bracket. See  
Fig. 26.  
NOTE: On 14” wide casing models, the J--Box shall not be  
relocated to other side of furnace casing when the vent pipe is  
routed within the casing.  
1. Remove cover from furnace J--Box.  
2. Attach electrical box to furnace J--Box bracket with at least  
two field--supplied screws through holes in electrical box  
into holes in bracket. Use blunt--nose screws that will not  
pierce wire insulation.  
1. Remove and save two screws holding J--Box. (See Fig.  
24.)  
NOTE: The J--Box cover need not be removed from the J--Box  
in order to move the J--Box. Do NOT remove green ground  
screw inside J--Box. The ground screw is not threaded into the  
casing flange and can be lifted out of the clearance hole in casing  
while swinging the front edge of the J--box outboard of the  
casing.  
3. Route furnace power wires through holes in electrical box  
and J--Box bracket, and make field--wire connections in  
electrical box. Use best practices (NEC in U.S. and CSA  
C22.1 in Canada) for wire bushings, strain relief, etc.  
4. Route and secure field ground wire to green ground screw  
on J--Box bracket.  
2. Cut wire tie on loop in furnace wires attached to J--Box.  
3. Move J--Box to desired location.  
5. Connect line voltage leads as shown in Fig. 23.  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. Reinstall cover to J--Box. Do not pinch wires between  
cover and bracket.  
Electrical Box on Furnace Casing Side. See Fig. 25.  
11. Secure field ground wire to J--Box green ground screw.  
12. Complete electrical box wiring and installation. Connect  
line voltage leads as shown in Fig. 23. Use best practices  
(NEC in U.S. and CSA C22.1 in Canada) for wire bush-  
ings, strain relief, etc.  
13. Reinstall cover to J--Box. Do not pinch wires between  
cover and bracket.  
!
WARNING  
FIRE OR ELECTRICAL SHOCK HAZARD  
POWER CORD INSTALLATION IN FURNACE J--BOX  
Failure to follow this warning could result in personal  
injury, death, or property damage.  
NOTE: Power cords must be able to handle the electrical  
requirements listed in Table 7. Refer to power cord  
manufacturer’s listings.  
If field--supplied manual disconnect switch is to be mounted  
on furnace casing side, select a location where a drill or  
fastener cannot damage electrical or gas components.  
1. Remove cover from J--Box.  
2. Route listed power cord through 7/8--inch (22 mm) dia-  
meter hole in J--Box.  
3. Secure power cord to J--Box bracket with a strain relief  
bushing or a connector approved for the type of cord used.  
4. Secure field ground wire to green ground screw on J--Box  
bracket.  
5. Connect line voltage leads as shown in Fig. 23.  
6. Reinstall cover to J--Box. Do not pinch wires between  
cover and bracket.  
BX. CABLE INSTALLATION IN FURNACE J--BOX  
1. Remove cover from J--Box.  
2. Route BX cable into 7/8--inch (22 mm) diameter hole in  
J--Box.  
3. Secure BX cable to J--Box bracket with connectors ap-  
proved for the type of cable used.  
4. Secure field ground wire to green ground screw on J--Box  
bracket.  
5. Connect line voltage leads as shown in Fig. 23.  
6. Reinstall cover to J--Box. Do not pinch wires between  
cover and bracket.  
24--V WIRING  
Make field 24--v connections at the 24--v terminal strip. (See Fig.  
33.) Connect terminal Y/Y2 as shown in Fig. 26--32 for proper  
cooling operation. Use only AWG No. 18, color--coded, copper  
thermostat wire.  
A03221  
The 24--v circuit contains an automotive--type, 3--amp. fuse  
located on the control. Any direct shorts during installation,  
service, or maintenance could cause this fuse to blow. If fuse  
replacement is required, use ONLY a 3--amp. fuse of identical  
size.  
Fig. 25 -- Field--Supplied Electrical Box on Furnace Casing  
1. Select and remove a hole knockout in the casing where the  
electrical box is to be installed.  
NOTE: Check that duct on side of furnace will not interfere with  
installed electrical box.  
2. Remove the desired electrical box hole knockout and posi-  
tion the hole in the electrical box over the hole in the fur-  
nace casing.  
3. Fasten the electrical box to casing by driving two field--  
supplied screws from inside electrical box into casing  
steel.  
4. Remove and save two screws holding J--Box. (See Fig.  
24.)  
5. Pull furnace power wires out of 1/2--inch (12 mm) diamet-  
er hole in J--Box. Do not loosen wires from strain--relief  
wire--tie on outside of J--Box.  
6. Route furnace power wires through holes in casing and  
electrical box and into electrical box.  
7. Pull field power wires into electrical box.  
8. Remove cover from furnace J--Box.  
9. Route field ground wire through holes in electrical box  
and casing, and into furnace J--Box.  
10. Reattach furnace J--Box to furnace casing with screws re-  
moved in Step 4.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
See notes 2, 5, 8, 10, 11 and 12  
on the page following these figures  
See notes 1, 2, 3, 4, 6, 8, 9, 10, 12, 13 and 15  
on the page following these figures  
A03179  
A03178  
Fig. 26 -- Two--Stage Furnace with Two--Speed Air  
Conditioner  
Fig. 28 -- Two--Stage Furnace with Two--Speed Heat Pump  
(Dual Fuel)  
See notes 1, 2, 4, 11, 14, 15, and 16  
on the page following these figures  
See notes 1, 2, 4, 6, 7, 9, 10, 11, and 15  
on the page following these figures  
A03180  
A03181  
Fig. 27 -- Two--Stage Furnace with Single--Speed Heat Pump  
(Dual Fuel)  
Fig. 29 -- Dual Fuel Thermostat with Two--Stage Furnace  
and Single--Speed Heat Pump  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
See notes 2, 11, and 12 on the  
page following these figures  
See notes 1, 2, 3, 4, 12, 13, 14, 15, and 17  
on the page following these figures  
A03182  
A03183  
Fig. 30 -- Dual Fuel Thermostat with Two--Stage Furnace  
and Two--Speed Heat Pump  
Fig. 31 -- Two--Stage Thermostat with Two--Stage Furnace  
and Two--Speed Air Conditioner  
See notes 1 and 2 on the page  
following these figures  
A03184  
Fig. 32 -- Single--Stage Thermostat with Two--Stage Furnace and Two--Speed Air Conditioner  
NOTES: For Figu r es 26 --- 32  
1. Heat pump MUST have a high pressure switch for dual fuel applications.  
2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure.  
3. Outdoor Air Temperature Sensor must be attached in all dual fuel applications.  
4. Dip switch No. 1 on Thermidistat should be set in OFF position for air conditioner installations. This is factory default.  
5. Dip switch No. 1 on Thermidistat should be set in ON position for heat pump installations.  
6. Dip switch No. 2 on Thermidistat should be set in OFF position for single---speed compressor operation. This is factory default.  
7. Dip switch No. 2 on Thermidistat should be set in ON position for two---speed compressor operation.  
8. Configuration Option No. 10 “Dual Fuel Selection” must be turned ON in all dual fuel applications.  
9. NO connection should be made to the furnace HUM terminal when using a Thermidistat.  
10. Optional connection: If wire is connected, dip switch SW1---2 on furnace control should be set in ON position to allow Thermidistat/Thermostat to control  
furnace staging.  
11. Optional connection: If wire is connected, ACRDJ jumper on furnace control should be removed to allow Thermidistat/Thermostat to control outdoor unit  
staging.  
12. When using both a two---stage furnace and a two---stage heat pump, the furnace must control its own high---stage heating operation via furnace control  
algorithm.  
13. The RVS Sensing terminal “Lshould not be connected. This is internally used to sense defrost operation.  
14. DO NOT SELECT the “FURNACE INTERFACE” or “BALANCE POINT” option on the two---speed heat pump control board. This is controlled internally by  
the Thermidistat/Dual Fuel Thermostat.  
15. Dip switch D on Dual Fuel Thermostat should be set in OFF position for single---speed compressor operation. This is factory default.  
16. Dip switch D on Dual Fuel Thermostat should be set in ON position for two---speed compressor operation.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ACCESSORIES  
NOTE: DO NOT connect furnace control HUM terminal to  
HUM (humidifier) terminal on Thermidistat, Zone Controller or  
similar device. See Thermidistatt, Zone Controller, thermostat,  
or controller manufacturer’s instructions for proper connection.  
1. Electronic Air Cleaner (EAC)  
Connect an accessory Electronic Air Cleaner (if used) us-  
ing 1/4--in female quick connect terminals to the two male  
1/4--in quick--connect terminals on the control board  
marked EAC--1 and EAC--2. The terminals are rated for  
115VAC, 1.0 amps maximum and are energized during  
blower motor operation. (See Fig. 33.)  
VENTING  
The furnace shall be connected to a listed factory built chimney  
or vent or a clay--tile lined masonry or concrete chimney. Venting  
into an unlined masonry chimney or concrete chimney is  
prohibited. When an existing Category I furnace is removed or  
replaced, the original venting system may no longer be sized to  
properly vent the attached appliances. An improperly sized  
Category I venting system could cause the formation of  
condensate in the furnace and vent, leakage of condensate and  
combustion products, and spillage of combustion products into  
the living space.  
2. Humidifier (HUM)  
Connect an accessory 24 VAC, 0.5 amp. maximum hu-  
midifier (if used) to the 1/4--in male quick--connect HUM  
terminal and COM--24V screw terminal on the control  
board thermostat strip. The HUM terminal is energized  
when gas valve relay (GVR) is energized. (See Fig. 33.)  
NOTE: A field--supplied, 115--v controlled relay connected to  
EAC terminals may be added if humidifier operation is desired  
during blower operation.  
SETUP SWITCHES  
LOW-HEAT ONLY AND  
BLOWER OFF-DELAY  
TWINNING AND/OR  
COMPONENT TEST  
TERMINAL  
ACRDJ - AIR CONDITIONING  
RELAY DISABLE JUMPER  
LHT  
OFF  
DLY  
24-V-THERMOSTAT  
TERMINALS  
TEST/TWIN  
TRANSFORMER 24-VAC  
HUM  
CONNECTIONS  
0.5-AMP024 VAC  
HUMIDIFIER TERMINAL  
(24-VAC 0.5 AMP MAX.)  
FUSE 3-AMP  
AT  
PL1 - LOW VOLTAGE MAIN  
HARNESS CONNECTOR  
S
SEC-1  
SEC-2  
U
D
3-AMP FUSE  
S
E
C
L
O
E
D
LED OPERATION &  
DIAGNOSTIC LIGHT  
EAC-2  
NEUTRAL-L2  
PL3  
BLW  
BHI/LOR  
115-VAC (L2) NEUTRAL  
CONNECTIONS  
BHT/CLR  
BLWR  
HI HEAT  
LO HEAT  
COOL  
SPARE-2  
1-AMP@115 VAC  
EAC-1  
SPARE-1  
PR-1  
HSI HI LO  
SPARE-1  
SPARE-2  
PL2 - HOT SURFACE  
IGNITER & INDUCER  
MOTOR CONNECTOR  
115-VAC (L1) LINE  
VOLTAGE CONNECTION  
COOL  
BLOWER SPEED  
SELECTION TERMINALS  
EAC-1 TERMINAL  
(115-VAC 1.0 AMP MAX.)  
A02017  
Fig. 33 -- Furnace Control--PSC Blower Motor  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CAN/CSA--B149.1--05, local building codes, and furnace and  
vent manufacturers’ instructions.  
The following information and warning must be considered in  
addition to the requirements defined in the NFGC or the  
CAN/CSA--B149.1--05.  
!
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
!
Failure to follow the steps outlined below for each  
appliance connected to the venting system being placed into  
operation could result in carbon monoxide poisoning or  
death. The following steps shall be followed for each  
appliance connected to the venting system being placed into  
operation, while all other appliances connected to the  
venting system are not in operation:  
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Do not bypass the draft safeguard switch, as an unsafe  
condition could exist which must be corrected.  
1. Seal any unused openings in venting system.  
2. Inspect the venting system for proper size and  
horizontal pitch, as required in the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54 or the CSA B149.1, Natural Gas  
and Propane Installation Code and these instructions.  
Determine that there is no blockage or restriction, leakage,  
corrosion and other deficiencies, which could cause an  
unsafe condition.  
3. As far as practical, close all building doors and windows  
and all doors between the space in which the appliance(s)  
connected to the venting system are located and other  
spaces of the building.  
1. If a vent (common or dedicated) becomes blocked, the fur-  
nace will be shut off by the draft safeguard switch located  
on the vent elbow.  
2. Two--stage furnaces require Type B vent connectors out-  
side the casing in all configurations. Single wall vent con-  
nector may be used inside the furnace casing with the  
transition to Type B vent outside the furnace casing. Size  
the connector so that the FAN--Min vent connector capa-  
city is equal to or lower than the low fire rate of the fur-  
nace and the FAN--Max vent connector capacity is equal  
to or higher than the furnace high fire rate.  
4. Close fireplace dampers.  
5. Turn on clothes dryers and any appliance not connected  
to the venting system. Turn on any exhaust fans, such as  
range hoods and bathroom exhausts, so they are operating  
at maximum speed. Do not operate a summer exhaust fan.  
6. Follow the lighting instructions. Place the appliance  
being inspected into operation. Adjust the thermostat so  
appliance is operating continuously.  
7. Test for spillage from draft hood equipped appliances at  
the draft hood relief opening after 5 minutes of main burner  
operation. Use the flame of a match or candle.  
8. If improper venting is observed during any of the above  
tests, the venting system must be corrected in accordance  
with the National Fuel Gas Code, ANSI Z223.1/NFPA 54  
and/or CSA B149.1, Natural Gas and Propane Installation  
Code.  
9. After it has been determined that each appliance  
connected to the venting system properly vents when tested  
as outlined above, return doors, windows, exhaust fans,  
fireplace dampers and any other gas--fired burning  
appliance to their previous conditions of use.  
3. Do not vent this Category I furnace into a single wall ded-  
icated or common vent. The dedicated or common vent is  
considered to be the vertical portion of the vent system  
that terminates outdoors.  
4. Vent connectors serving Category I furnaces shall not be  
connected into any portion of a mechanical draft system  
operating under positive pressure.  
5. In the US: Do not vent this appliance with any solid fuel  
burning appliance. In Canada: Check with the authority  
having jurisdiction for approval on use with solid fuel  
burning appliance.  
6. Category I furnaces must be vented vertically or nearly  
vertically unless equipped with a listed mechanical venter.  
See the SIDEWALL VENTING section.  
7. Do not vent this appliance into an unlined masonry chim-  
ney. Refer to Chimney Inspection Chart, Fig. 34.  
MASONRY CHIMNEY REQUIREMENTS  
NOTE: These furnaces are CSA design--certified for use in  
exterior tile--lined masonry chimneys with a factory accessory  
Chimney Adapter Kit. Refer to the furnace rating plate for correct  
kit usage. The Chimney Adapter Kits are for use with ONLY  
furnaces having a Chimney Adapter Kit number marked on the  
furnace rating plate.  
Vent system or vent connectors may need to be resized. Vent  
systems or vent connectors must be sized to approach minimum  
size as determined using appropriate table found in the NFGC or  
CAN/CSA--B149.1--05.  
If a clay tile--lined masonry chimney is being used and it is  
exposed to the outdoors below the roof line, relining might be  
required. Chimneys shall conform to the Standard for Chimneys,  
Fireplaces, Vents, and Solid Fuel Burning Appliances  
ANSI/NFPA 211--2006 in the United States and to a Provincial or  
Territorial Building Code in Canada (in its absence, the National  
Building Code of Canada) and must be in good condition.  
GENERAL VENTING REQUIREMENTS  
Follow all safety codes for proper vent sizing and installation  
requirements, including local building codes, the National Fuel  
Gas Code ANSI Z223.1--2006/NFPA 54--2006 (NFGC), Parts 12  
and 13 in the United States or the National Standard of Canada,  
Natural Gas and Propane Installation Code CSA--B149.1--05  
(CAN/CSA--B149.1--05), Section 8 and Appendix C in Canada,  
the local building codes, and furnace and vent manufacturers’  
instructions.  
U.S.A.--Refer to Sections 13.1.8 and 13.2.20 of the NFPA 54 /  
ANSI Z223.1--2006 or the authority having jurisdiction to  
determine whether relining is required. If relining is required, use  
a properly sized listed metal liner, Type--B vent, or a listed  
alternative venting design.  
These furnaces are design--certified as Category I furnaces in  
accordance with ANSI Z21.47--2006/CSA 2.3--2006 and operate  
with a non--positive vent static pressure to minimize the potential  
for vent gas leakage. Category I furnaces operate with a flue loss  
not less than 17% to minimize the potential for condensation in  
the venting system. These furnaces are approved for common  
venting and multi--story venting with other fan assisted or draft  
hood equipped appliances in accordance with the NFCG or the  
NOTE: See the NFPA 54 / ANSI Z223.1--2006, 13.1.8 and  
13.2.20 regarding alternative venting design and the exception,  
which cover installations such as the Chimney Adapter Kits  
KGACA02014FC and KGACA02015FC, which are listed for  
use with these furnaces.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CHIMNEY INSPECTION CHART  
For additional requirements refer to the National Fuel Gas Code NFPA 54/ANSI Z223.1 and ANSI/NFPA 211  
Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances in the U.S.A. or to the Canadian  
installation Code CSA-B149.1 in Canada.  
Crown  
Rebuild  
crown.  
condition:  
Missing mortar  
or brick?  
Yes  
No  
Is chimney  
property lined with  
clay tile liner?  
No  
Yes  
Repair  
Is  
Reline  
No  
liner or top seal  
or reline chimney as  
necessary.  
liner and top  
seal in good  
condition?  
Repair  
Yes  
Debris  
Mortar  
or tile  
debris?  
in cleanout?  
Yes  
Yes  
Remove mortar  
and tile debris  
Mortar, tile, metal vent,  
fuel oil residue?  
No  
Remove metal vent  
or liner.  
No  
Clay  
Yes  
tile misalignment,  
missing sections,  
gaps?  
Consult  
Part B of  
Not Suitable  
chimney adapter venting  
instructions for  
application  
No  
No  
suitability.  
Is chimney  
lined with properly  
sized, listed liner or  
Type-B vent?  
Line chimney with property  
sized, listed flexible metal  
liner or Type-B vent per  
NFGC or NSCNGPIC Vent  
Sizing Tables and liner or  
vent manufacturer’s  
Condensate  
drainage at bottom  
of chimney?  
Suitable  
Yes  
Yes  
Install chimney  
adapter per  
instructions.  
No  
Installation instructions.  
Not Suitable  
Consult  
Yes  
Chimney  
exposed to  
outdoors below  
roof line?  
Part C of  
chimney adapter venting  
instructions for  
application  
Is chimney  
to be dedicated to  
a single  
No  
Suitable  
Yes  
furnace?  
suitability  
Install chimney  
adapter per  
instructions.  
No  
Chimney is  
acceptable for use.  
A03206  
Fig. 34 -- Chimney Inspection Chart  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Chimney Adapter Kit is a listed alternative venting system  
for these furnaces. See the kit instructions for complete details.  
Table 9 – Minimum Allowable Input Rating of Space--Heat-  
ing Appliance in Thousands of BTUH per Hour  
Canada (and U.S.A.)--This furnace is permitted to be vented into  
a clay tile--lined masonry chimney that is exposed to the outdoors  
below the roof line, provided:  
INTERNAL AREA OF CHIMNEY  
SQ. IN. (SQ. MM)  
VENT HEIGHT  
1. Vent connector is Type--B double--wall, and  
(FT)  
12  
(7741)  
19  
28  
38  
2. This furnace is common vented with at least 1 draft hood--  
equipped appliance, and  
3. The combined appliance input rating is less than the max-  
imum capacity given in Table 8, and  
(12258) (18064) (24516)  
Local 99% Winter Design  
Temperature: 17 to 26_F ( --- 8 t o --- 3 _C)  
6 (1.8)  
8 (2.4)  
0
55  
74  
99  
141  
154  
169  
212  
258  
362  
4. The input rating of each space heating appliance is greater  
than the minimum input rating given in Table 9 for the  
local 99% Winter Design Temperature. Chimneys having  
52  
111  
125  
167  
212  
NR  
10 (3.0)  
15 (4.6)  
20 (6.1)  
30 (9.1)  
NR  
NR  
NR  
NR  
90  
2
2)  
NR  
NR  
NR  
internal areas greater than 38 in (24516 mm require fur-  
nace input ratings greater than the input ratings of these  
furnaces. See footnote at bottom of Table 9, and  
5. The authority having jurisdiction approves.  
Local 99% Winter Design  
Temperature: 5 to 16_F * ( --- 1 5 t o --- 9 _C)  
If all of these conditions cannot be met, an alternative venting  
design shall be used, such as the listed chimney adapter kit with a  
furnace listed for use with the kit, a listed chimney--lining system,  
or a Type--B common vent.  
Inspections before the sale and at the time of installation will  
determine the acceptability of the chimney or the need for repair  
and/or (re)lining. Refer to Fig. 34 to perform a chimney  
inspection. If the inspection of a previously used tile--lined  
chimney:  
6 (1.8)  
8 (2.4)  
NR  
NR  
NR  
NR  
NR  
NR  
78  
94  
121  
135  
149  
193  
NR  
166  
182  
198  
247  
293  
377  
10 (3.0)  
15 (4.6)  
20 (6.1)  
30 (9.1)  
111  
NR  
NR  
NR  
NR  
Local 99% Winter Design  
Temperature: ---10 to 4_F * ( --- 2 3 t o --- 1 6 _C)  
a. Shows signs of vent gas condensation, the chimney  
should be relined in accordance with local codes and the  
authority having jurisdiction. The chimney should be re-  
lined with a listed metal liner, Type--B vent, or a listed  
chimney adapter kit shall be usedto reducecondensation.  
If a condensate drain is required by local code, refer to  
the NFPA 54 / ANSI Z223.1--2006, Section 12.10 for ad-  
ditional information on condensate drains.  
6 (1.8)  
8 (2.4)  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
NR  
145  
159  
175  
NR  
NR  
NR  
196  
213  
231  
283  
333  
NR  
10 (3.0)  
15 (4.6)  
20 (6.1)  
30 (9.1)  
Local 99% Winter Design  
b. Indicates the chimney exceeds the maximum permissible  
size in the tables, the chimney should be rebuilt or relined  
to conform to the requirements of the equipment being  
installed and the authority having jurisdiction.  
Temperature: ---11_F ( --- 2 4 _C) or lower  
Not recommended for any vent configuration.  
*The 99.6% heating db temperatures found in the 1997 or 2001 ASHRAE  
Fundamentals Handbook, Climatic Design Information chapter, Table 1A  
(United States) and 2A (Canada) or the 2005 ASHRAE Fundamentals  
handbook, Climatic Design Information chapter, and the CD---ROM in-  
cluded with the 2005 ASHRAE Fundamentals Handbook.  
A chimney without a clay tile liner, which is otherwise in good  
condition, shall be rebuilt to conform to ANSI/NFPA 211 or be  
lined with a UL listed (ULC listed in Canada) metal liner or UL  
listed Type--B vent. Relining with a listed metal liner or Type--B  
vent is considered to be a vent--in--a--chase.  
APPLIANCE APPLICATION REQUIREMENTS  
Appliance operation has a significant impact on the performance  
of the venting system. If the appliances are sized, installed,  
adjusted, and operated properly, the venting system and/or the  
appliances should not suffer from condensation and corrosion.  
The venting system and all appliances shall be installed in  
accordance with applicable listings, standards, and codes.  
If a metal liner or Type--B vent is used to line a chimney, no other  
appliance shall be vented into the annular space between the  
chimney and the metal liner.  
Exterior Masonry Chimney FAN + NAT  
Installations with Type--B Double--Wall Vent  
Connectors ENFPA & AGA  
The furnace should be sized to provide 100% of the design  
heating load requirement plus any margin that occurs because of  
furnace model size capacity increments. Heating load estimates  
can be made using approved methods available from Air  
Conditioning Contractors of America (Manual J); American  
Society of Heating, Refrigerating, and Air--Conditioning  
Engineers; or other approved engineering methods. Excessive  
over--sizing of the furnace could cause the furnace and/or vent to  
fail prematurely. When a metal vent or metal liner is used, the  
vent must be in good condition and be installed in accordance  
with the vent manufacturer’s instructions.  
Table 8 – Combined Appliance Maximum Input Rating in  
Thousands of BTUH per Hour  
INTERNAL AREA OF CHIMNEY  
SQ. IN. (SQ. MM)  
VENT HEIGHT  
FT. (M)  
12  
19  
(12258)  
28  
(18064)  
38  
(24516)  
(7741)  
6 (1.8)  
8 (2.4)  
10 (3.)  
15 (4.5)  
20 (6.0)  
30 (9.1)  
74  
80  
84  
NR  
NR  
NR  
119  
130  
138  
152  
NR  
178  
193  
207  
233  
250  
NR  
257  
279  
299  
334  
368  
404  
To prevent condensation in the furnace and vent system, the  
following precautions must be observed:  
NR  
1. The return--air temperature must be at least 60_F (15_C)  
db except for brief periods of time during warm--up from  
setback at no lower than 55_F (13_C) db or during initial  
start--up from a standby condition.  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2. Adjust the gas input rate per the installation instructions.  
Low gas input rate causes low vent gas temperatures, caus-  
ing condensation and corrosion in the furnace and/or vent-  
ing system. Derating is permitted only for altitudes above  
2000 ft  
3. Adjust the air temperature rise to the midpoint of the rise  
range or slightly above. Low air temperature rise can cause  
low vent gas temperature and potential for condensation  
problems.  
4. Set the thermostat heat anticipator or cycle rate to reduce  
short cycling.  
Air for combustion must not be contaminated by halogen  
compounds which include chlorides, fluorides, bromides, and  
iodides. These compounds are found in many common home  
products such as detergent, paint, glue, aerosol spray, bleach,  
cleaning solvent, salt, and air freshener, and can cause corrosion  
of furnaces and vents. Avoid using such products in the  
combustion--air supply. Furnace use during construction of the  
building could cause the furnace to be exposed to halogen  
compounds, causing premature failure of the furnace or venting  
system due to corrosion.  
SEE NOTES: 1,2,4,7,8,9  
on the page following  
these figures  
Vent dampers on any appliance connected to the common vent  
can cause condensation and corrosion in the venting system. Do  
not use vent dampers on appliances common vented with this  
furnace.  
A03208  
Fig. 35 -- Upflow Application--Vent Elbow Up  
ADDITIONAL VENTING REQUIREMENTS  
A 4 in. (102 mm) round vent elbow is supplied with the furnace.  
A 5 in. or 6 in. (127 or 152 mm) vent connector may be required  
for some model furnaces. A field--supplied 4 in. to 5 in. (102 to  
127 mm) or 4 in. to 6 in. (102 mm to 152 mm) sheet metal  
increaser fitting is required when 5 in. or 6 in. (127 or 152 mm)  
vent connector is used. See Fig. 35--47 Venting Orientation for  
approved vent configurations.  
See Venting Notes after Fig. 47.  
SEE NOTES: 1,2,3,4,7,8,9  
on the pages following  
these figures  
A03209  
Fig. 36 -- Upflow Application--Vent Elbow Right  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEE NOTES:1,2,3,4,5,7,8,9  
on the page following  
these figures  
SEE NOTES: 1,2,4,5,6,7,8,9,10  
on the page following these figures  
A03210  
A03207  
Fig. 37 -- Downflow Application--Vent Elbow Up then Left  
Fig. 39 -- Downflow Application--Vent Elbow Left then Up  
SEE NOTES: 1,2,4,5,7,8,9  
on the page following  
these figures  
SEE NOTES:1,2,3,4,5,7,8,9  
on the page following  
these figures.  
A03211  
A03212  
Fig. 38 -- Downflow Application--Vent Elbow Up  
Fig. 40 -- Downflow Application--Vent Elbow Up then Right  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEE NOTES: 1,2,4,5,7,8,9 on the page  
following these figures  
SEE NOTES: 1,2,4,7,8,9 on the page  
following these figures  
A03213  
A03215  
Fig. 41 -- Horizontal Left Application -- Vent Elbow Left  
Fig. 44 -- Horizontal Left Application -- Vent Elbow Up  
SEE NOTES: 1,2,4,5,7,8,9 on the page  
following these figures  
SEE NOTES: 1,2,4,5,7,8,9 on the page  
following these figures  
A03214  
A03216  
Fig. 42 -- Horizontal Left Application -- Vent Elbow Right  
then Up  
Fig. 45 -- Horizontal Left Application -- Vent Elbow Right  
SEE NOTES: 1,2,4,7,8,9 on the page  
following these figures  
SEE NOTES: 1,2,4,5,7,8,9 on the page  
following these figures  
A03218  
A03219  
Fig. 43 -- Horizontal Right Application -- Vent Elbow Right  
Fig. 46 -- Horizontal Right Application -- Vent Elbow Left  
then Up  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SEE NOTES: 1,2,4,5,7,8,9  
A02068  
Fig. 47 -- Horizontal Right Application--Vent Elbow Left  
NOTES: Venting Notes for Fig. 35---47  
1. For common vent, vent connector sizing and vent material: United States--- ---use the NFGC Canada--- ---use the CAN/CSA---B149.1---05  
2. Immediately increase to 5---in. or 6---in. (127 or 152 mm) vent connector outside furnace casing when 5---in. (127 mm) vent connector is required, refer to  
Note 1 above.  
3. Side outlet vent for upflow and downflow installations must use Type B vent immediately after exiting the furnace, except when KGAVG0101DFG, Downflow  
Vent Guard Kit, is used in the downflow position.  
4. Type---B vent where required, refer to Note 1 above.  
5. Four---in. (102 mm) single---wall (26 ga. min.) vent must be used inside furnace casing and when the KGAVG0101DFG Downflow Vent Guard Kit is used  
external to the furnace.  
6. Accessory Downflow Vent Guard Kit, KGAVG0101DFG required in downflow installations with lower vent configuration.  
7. Chimney Adapter Kit may be required for exterior masonry chimney applications. Refer to Chimney Adapter Kit, KGACA02014FC or KGACA02015FC, for  
sizing and complete application details.  
8. Secure vent connector to furnace elbow with (2) corrosion---resistant sheet metal screws, spaced approximately 180_ apart.  
9. Secure all other single wall vent connector joints with (3) corrosion resistant screws spaced approximately 120_ apart. Secure Type---B vent connectors per  
vent connector manufacturer’s recommendations.  
10. The total height of the vent and connector shall be at least seven feet (2 M) for the 154,000 Btuh gas input rate model when installed in a downflow applica-  
tion with furnace elbow turned to left side with the connector elbow outside furnace casing pointing upward. (See Fig. 40.)  
Caution!! For the following applications, use the minimum vertical heights as specified below.  
For all other applications, follow exclusively the National Fuel Gas Code  
MINIMUM VENT  
DIAMETER  
MINIMUM VERTICAL  
VENT HEIGHT  
FT. (M)**  
FURNACE  
ORIENTATION  
VENT  
ORIENTATION  
FURNACE  
INPUT(BTUH/HR)  
IN. (mm)*  
154,000  
132,000  
110,000(036/---12 only)  
Vent elbow left, then  
up Fig. 39  
Downflow  
5 (127)  
12 (3.6)  
Vent elbow right,  
then up Fig. 42  
Vent Elbow up Fig.  
43  
Vent elbow right Fig.  
44  
Vent elbow up then  
left Fig. 37  
154,000  
132,000  
154,000  
132,000  
Horizontal Left  
Horizontal Left  
Horizontal Left  
Downflow  
5 (127)  
5 (127)  
5 (127)  
5 (127)  
5 (127)  
7 (.65)  
7 (.65)  
7 (.65)  
10 (3.0)  
10 (3.0)  
154,000  
110,000 (036/---12 only)  
110,000 (036/---12 only)  
Vent elbow up, then  
right Fig. 40  
Downflow  
*4 in. (102 mm) inside casing or vent guard  
**Including 4 in. (102 mm) vent section(s)  
NOTE: All vent configurations must also meet National Fuel Gas Code venting requirements NFGC.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A04127  
Fig. 48 -- Using Tin Snips to Cut Tie Points  
For the rectangular J--box knockout, use tin snips along the door  
edge and use a sharp blow with a hammer to remove the  
knockout. Remove any burrs and sharp edges.  
!
CAUTION  
For the knockouts in the other locations on the door (top and  
sides), tin snips can also be used along the door edges; however,  
the preferred method is to use a hammer and screwdriver to strike  
a sharp blow (See Fig. 51.) directly to the knockout tie points or  
use a hammer in the upper left corner of the desired knockout.  
(See Fig. 52.) Remove any burrs and sharp edges.  
CUT HAZARD  
Failure to follow this caution may result in personal injury.  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing, safety glasses and  
gloves when handling parts and servicing furnaces.  
NOTE: If a knockout does not come out after two sharp blows,  
pull and snip as needed to remove the knockout. Additional  
blows may cause damage to the door.  
NOTE: Vent connector length for connector sizing starts at  
furnace vent elbow. The 4--in. (102 mm) vent elbow is shipped  
for upflow configuration and may be rotated for other positions.  
Remove the 3 screws that secure vent elbow to furnace, rotate  
furnace vent elbow to position desired, re--install screws. The  
factory--supplied vent elbow does NOT count as part of the  
number of vent connector elbows.  
The vent connector can exit the door through one of 5 locations  
on the door.  
1. Attach the single wall vent connector to the furnace vent  
elbow, and fasten the vent connector to the vent elbow  
with at least two field--supplied, corrosion--resistant, sheet  
metal screws located 180_ apart.  
NOTE: An accessory flue extension KGAFE0112UPH is  
available to extend from the furnace elbow to outside the furnace  
casing. If flue extension is used, fasten the flue extension to the  
vent elbow with at least two field--supplied, corrosion--resistant,  
sheet metal screws located 180_ apart. Fasten the vent connector  
to the flue extension with at least two field--supplied, corrosion  
resistant sheet metal screws located 180_ apart.  
2. Vent the furnace with the appropriate connector as shown  
in Fig. 35--47.  
3. Orient the door to determine the correct location of the  
door knockout to be removed.  
4. Remove the correct U--shaped knockout in door.  
NOTE: A number of techniques can be used to remove these  
knockouts as seen in Fig. 48 through 52. The knockout in the  
bottom of the door is unique due to its flanging and is more easily  
removed by first cutting the two tie points at the edge of the door,  
using aviation--type tin snips. (See Fig. 48.) A sharp blow to the  
rounded end of the knockout (See Fig. 49.) will separate more tie  
points and allow the knockout to be pulled loose. (See Fig. 50.)  
Remove all burrs any sharp edges.  
A04128  
Fig. 49 -- Rounded End of Knockout  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
An accessory Vent Guard Kit, KGAVG0101DFG is REQUIRED  
for downflow applications for use where the vent exits through  
the lower portion of the furnace casing door. Refer to the Vent  
Guard Kit Instructions for complete details.  
The horizontal portion of the venting system shall slope upwards  
not less than 1/4--in. per linear ft. (6 mm/.3 M) from the furnace  
to the vent and shall be rigidly supported every 5 ft. (1.5 M) or  
less with metal hangers or straps to ensure there is no movement  
after installation.  
SIDEWALL VENTING  
This furnace is not approved for direct sidewall horizontal  
venting.  
In the U.S.: Per section 10.3.4 of the NFPA 54 / ANSI  
Z223.1--2006, any listed mechanical venter may be used, when  
approved by the authority having jurisdiction.  
In Canada: Per section 8.24.2 of the CAN/CSA--B149.1--05,  
any listed mechanical venter may be used, when approved by the  
authority having jurisdiction.  
A04129  
Fig. 50 -- Knockout Pulled Loose  
Select the listed mechanical venter to match the Btuh input of the  
furnace being vented. Follow all manufacturer’s installation  
requirements for venting and termination included with the listed  
mechanical venter.  
START--UP, ADJUSTMENT, AND SAFETY  
CHECK  
Step 1 — General  
!
WARNING  
FIRE HAZARD  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
This furnace is equipped with manual reset limit switches in  
the gas control area. The switches open and shut off power  
to the gas valve if a flame roll--out or overheating condition  
occurs in the gas control area. DO NOT bypass the  
switches. Correct problem before resetting the switches.  
A04130  
Fig. 51 -- Hammer and Screwdriver Used for Knockout  
1. Maintain 115--v wiring and ground. Improper polarity will  
result in rapid flashing LED and no furnace operation.  
2. Make thermostat wire connections at the 24--v terminal  
block on the furnace control. Failure to make proper con-  
nections will result in improper operation. (See Fig. 23.)  
3. Gas supply pressure to the furnace must be greater than  
4.5--in. wc (0.16 psig ) but not exceed 14--in. wc (0.5  
psig).  
!
CAUTION  
CUT HAZARD  
Failure to follow this caution may result in personal injury.  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing, safety glasses and  
gloves when handling parts and servicing furnaces.  
A04131  
Fig. 52 -- Remove Knockout with Hammer  
!
CAUTION  
4. Check all manual--reset switches for continuity.  
5. Install blower compartment door. Door must be in place to  
operate furnace.  
BURN HAZARD  
Failure to follow this caution may cause personal injury.  
6. Setup switch descriptions The 2 stage furnace has DIP  
switches used to select thermostat staging and blower off  
delay timings. For switch locations on Furnace control  
board, See Fig. 33 and 57.  
Hot vent pipe is within reach of small children when  
installed in downflow position.  
See the following instruction.  
7. Setup switch descriptions -- See Table 10.  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 – 2--Stage Furnace Setup Switch Description  
SETUP  
SWITCH NO.  
SWITCH  
NAME  
NORMAL  
POSITION  
DESCRIPTION  
OF USE  
When OFF, allows 2---stage operation with a single stage thermostat.  
Turn ON when using 2 stage thermostat to allow Low Heat opera---  
tion when R to W/W1 closes and High Heat operation when R to  
W/W1 and W2 close.  
SW --- 1  
Adaptive Heat Mode  
OFF  
Control blower OFF delay time. Used in conjunction with SW---3.  
See Table 14.  
SW --- 2  
SW --- 3  
Blower OFF delay  
Blower OFF delay  
ON or OFF  
ON or OFF  
Control blower OFF delay time. Used in conjunction with SW---2.  
See Table 14.  
5. Verify furnace shut down by lowering thermostat setting  
below room temperature.  
Step 2 — Start-Up Procedures  
6. Verify furnace restarts by raising thermostat setting above  
room temperature.  
!
WARNING  
Step 3 — Adjustments  
FIRE AND EXPLOSION HAZARD  
Failure to follow this warning could cause personal injury,  
death and/or property damage.  
!
WARNING  
Never test for gas leaks with an open flame. Use a  
commercially available soap solution made specifically for  
the detection of leaks to check all connections.  
FIRE HAZARD  
Failure to follow this warning could result in injury, death  
and/or property damage.  
DO NOT bottom out gas valve regulator adjusting screw.  
This can result in unregulated manifold pressure and result  
in excess over--fire and heat exchanger failures.  
1. Purge gas lines after all connections have been made.  
2. Check gas lines for leaks.  
!
WARNING  
!
ELECTRICAL SHOCK HAZARD  
CAUTION  
Failure to follow this warning could result in personal  
injury, or death.  
FURNACE DAMAGE HAZARD  
Failure to follow this caution may result in reduced furnace  
life.  
Blower access door switch opens 115--v power to control.  
No component operation can occur unless switch is closed.  
Caution must be taken when manually closing this switch  
for service purposes.  
DO NOT re--drill orifices. Improper drilling (burrs, out--of  
round holes, etc.) can cause excessive burner noise and  
misdirection of burner flames. This can result in flame  
impingement of heat exchangers, causing failures. (See Fig.  
49.)  
3. To Begin Component Self--Test:  
Remove blower access door. Disconnect the thermostat R  
lead from furnace control board. Manually close blower  
door switch. Short (jumper) the COM--24v terminal on  
control to the TEST/TWIN 3/16--in. (8 mm) quick--con-  
nect terminal on control until the LED goes out (approx-  
imately 2 sec). Gas valve and humidifier will not be turned  
on. Remove jumper from terminals. (See Fig. 33 and  
Table 10.)  
Furnace gas input rate on rating plate is for installations at  
altitudes up to 2000 ft. (610 M). Furnace input rate must be  
within +/--2% of furnace rating plate input. For altitudes above  
5500 ft. (1676 M), a field--supplied high altitude pressure switch  
is required.  
1. Determine the correct gas input rate.  
In the U.S.:  
NOTE: The furnace control allows all components, except the  
gas valve, to be run for short period of time. This feature helps  
diagnose a system problem in case of a component failure.  
Component test feature will not operate if any thermostat signal is  
present at the control.  
The input rating for altitudes above 2,000 ft. (610 M) must  
be reduced by 4% for each 1,000 ft. (305 M) above sea  
level.  
For installations below 2000 ft. (610 M), refer to the unit  
rating plate.  
For installations above 2000 ft. (610 M), multiply the in-  
put on the rating plate by the derate multiplier in Table 11  
for the correct input rate.  
Refer to service label attached to furnace or See Fig. 56.  
Component test sequence is as follows:  
a. LED will display previous status code 4 times.  
b. Inducer motor starts on high--speed and continues to run  
until Step g of component test sequence.  
EXAMPLE:  
c. Hot surface igniter is energized for 15 sec., then off.  
d. Blower motor operates on LO--HEAT speed for 10 sec.  
e. Blower motor operates on HI--HEAT speed for 10 sec.  
f. Blower motor operates on COOL speed for 10 sec.  
g. Inducer motor goes to low--speed for 10 sec., then stops.  
88,000 BTUH INPUT FURNACE INSTALLED AT 4300 FT. (1310  
M)  
Derate  
Multiplier  
Factor  
0.90  
Furnace Input Rate  
at Installation  
Altitude  
Furnace Input Rate  
at Sea Level  
88,000  
X
X
=
=
79,200  
h. Reconnect R lead to furnace control board, remove tape  
from blower door switch and re--install blower door.  
4. Operate furnace per instruction on inner door.  
In Canada: The input rating must be reduced by 10% for  
altitudes of 2,000 ft. (610 M) to 4,500 ft. (1372 M) above  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
sea level by an authorized Gas Conversion Station or  
Dealer. To determine correct input rate for altitude, see  
example and use 0.90 as derate multiplier factor.  
3. Adjust manifold pressure to obtain low fire input rate. (See  
Fig. 53.)  
a. Turn gas valve ON/OFF switch to OFF.  
2. Determine the correct orifice and manifold pressure adjust-  
ment. All models in all positions except Low NOx models  
in downflow and horizontal positions use Table 15  
(22,000 BTUH per burner).  
b. Remove manifold pressure tap plug from gas valve.  
c. Connect a water column manometer or similar device to  
manifold pressure tap.  
d. Turn gas valve ON/OFF switch to ON.  
Table 11 – Altitude Derate Multiplier for U.S.A.  
ALTITUDE  
FT. (M)  
PERCENT  
OF DERATE  
DERATE MULTIPLIER  
FACTOR*  
0–2000  
0
1.00  
0.90  
0.86  
0.82  
0.78  
0.74  
0.70  
0.66  
0.62  
(0---610)  
2001–3000  
(610---914)  
3001–4000  
(914---1219)  
4001–5000  
(1219---1524)  
5001–6000  
1524---1829)  
6001–7000  
(1829---2134)  
7001–8000  
(2134---2438)  
8001–9000  
(2438---2743)  
9001–10,000  
(2743---3048)  
8–12  
12–16  
16–20  
20–24  
24–28  
28–32  
32–36  
36–40  
* Derate multiplier factors are based on midpoint altitude for altitude  
range.  
Low NOx models in downflow or horizontal positions MUST  
use Table 16 (21,000 BTUH per burner). See input listed on  
rating plate.  
a. Obtain averageyearly gasheat value(at installed altitude)  
from local gas supplier.  
A06667  
Fig. 53 -- Redundant Automatic Gas Control Valve  
b. Obtain average yearly gas specific gravity from local gas  
supplier.  
e. Move setup switch LHT (SW--1) on furnace control to  
ON position to lock furnace in low--heat operation. (See  
Fig. 33 and Table 10.)  
c. Find installation altitude in Table 15 or 16.  
d. Find closest natural gas heat value and specific gravity  
in Table 15 or 16  
f. Manually close blower door switch.  
g. Jumper R and W/W1 thermostat connections on control  
to start furnace. (See Fig. 33.)  
e. Follow heat value and specific gravity lines to point of  
intersection to find orifice size and low--and high--heat  
manifold pressure settings for proper operation.  
h. Remove regulator adjustment cap from low--heat gas  
valve pressure regulators. (See Fig. 53.) Turn low--heat  
adjusting screw (3/16 in. (5 mm) or smaller flat tipped  
screwdriver) counterclockwise (out) to decrease input  
rate or clockwise (in) to increase input rate.  
f. Check and verify burner orifice size in furnace. NEVER  
ASSUME ORIFICE SIZE. ALWAYS CHECK AND  
VERIFY.  
g. Replace orifice with correct size, if required by Table 15  
or 16. Use only factory--supplied orifices. See  
EXAMPLE 2.  
NOTE: DO NOT set low--heat manifold pressure less than  
1.4--in wc or more than 1.7--in. wc for natural gas. If manifold  
pressure is outside this range, change main burner orifices.  
EXAMPLE 2: (0--2000 ft. / 0--610 M altitude)  
For 22,000 Btuh per burner application, use Table 15.  
Heating value = 1000 Btuh/cu ft.  
i. Install low--heat regulator adjustment cap.  
j. Leave manometer or similar device connected and pro-  
ceed to Step 4.  
Specific gravity = 0.62  
NOTE: If orifice hole appears damaged or it is suspected to have  
been re--drilled, check orifice hole with a numbered drill bit of  
correct size. Never re--drill an orifice. A burr--free and squarely  
aligned orifice hole is essential for proper flame characteristics.  
Therefore: Orifice No. 43*  
Manifold pressure: 3.7--in. wc for high--heat  
1.6--in. wc for low--heat  
4. Verify natural gas low--heat input rate by clocking meter.  
* Furnace is shipped with No. 43 orifices. In this example  
all main burner orifices are the correct size and do not need  
to be changed to obtain proper input rate.  
NOTE: Gas valve regulator adjustment caps must be in place for  
proper input to be clocked.  
a. Turn off all other gas appliances and pilots served by the  
meter.  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
b. Run for 3 minutes in low--heat operation.  
5. Set low--heat temperature rise. The furnace must operate  
within the temperature rise ranges specified on the furnace  
rating plate. Do not exceed temperature rise ranges spe-  
cified on unit rating plate for high--and low--heat.  
Determine the temperature rise as follows:  
c. Measure time (in sec) for gas meter to complete 1 revolu-  
tion and note reading. The 2 or 5 cubic feet dial provides  
a more accurate measurement of gas flow.  
NOTE: Blower access door must be installed when taking  
temperature rise reading. Leaving blower access door off will  
result in incorrect temperature measurements.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
Disconnect 115--v electrical power before changing speed  
tap.  
BURNER  
ORIFICE  
a. Verify unit is running in low heat per Step 3. Place ther-  
mometers in return and supply ducts as close to furnace  
as possible. Be sure thermometers do not see radiant heat  
from heat exchangers. Radiant heat affects temperature  
rise readings. This practice is particularly important with  
straight--run ducts.  
A93059  
Fig. 54 -- Orifice Hole  
d. Refer to Table 12 for cubic ft. of gas per hr.  
b. When thermometer readings stabilize, subtract return--air  
temperaturefromsupply--air temperatureto determineair  
temperature rise.  
e. Multiply gas rate cu ft. /hr by heating value (Btuh/cu ft.  
) to obtain input. If clocked rate does not match required  
input from Step 1, increase manifold pressure to increase  
input or decrease manifold pressure to decrease input.  
Repeat steps b through e until correct low heat input is  
achieved. Re--install low--heat regulator seal cap on gas  
valve.  
NOTE: If the temperature rise is outside this range, first check:  
(1.) Gas input for low heat operation.  
(2.) Derate for altitude if applicable.  
(3.) Return and supply ducts for excessive restrictions  
causing static pressures greater than 0.50--in. wc.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 12 – Gas Rate (cu ft. /hr)  
SECONDS  
SECONDS  
SIZE OF TEST DIAL  
SIZE OF TEST DIAL  
FOR 1  
FOR 1  
1 CU FT.  
2 CU FT.  
5 CU FT.  
1 CU FT.  
2 CU FT.  
5 CU FT.  
REVOLUTION  
REVOLUTION  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
37  
38  
39  
40  
41  
42  
43  
44  
45  
46  
47  
48  
49  
360  
327  
300  
277  
257  
240  
225  
212  
200  
189  
180  
171  
164  
157  
150  
144  
138  
133  
129  
124  
120  
116  
113  
109  
106  
103  
100  
97  
720  
655  
600  
555  
514  
480  
450  
424  
400  
379  
360  
343  
327  
313  
300  
288  
277  
267  
257  
248  
240  
232  
225  
218  
212  
206  
200  
195  
189  
185  
180  
176  
172  
167  
164  
160  
157  
153  
150  
147  
1800  
1636  
1500  
1385  
1286  
1200  
1125  
1059  
1000  
947  
900  
857  
818  
783  
750  
720  
692  
667  
643  
621  
600  
581  
563  
545  
529  
514  
500  
486  
474  
462  
450  
439  
429  
419  
409  
400  
391  
383  
375  
367  
50  
72  
71  
69  
68  
67  
65  
64  
63  
62  
61  
60  
58  
56  
54  
53  
51  
50  
48  
47  
46  
45  
44  
43  
42  
41  
40  
39  
38  
38  
37  
36  
35  
35  
34  
33  
33  
32  
31  
30  
144  
141  
138  
136  
133  
131  
129  
126  
124  
122  
120  
116  
112  
109  
106  
103  
100  
97  
360  
355  
346  
340  
333  
327  
321  
316  
310  
305  
300  
290  
281  
273  
265  
257  
250  
243  
237  
231  
225  
220  
214  
209  
205  
200  
196  
192  
188  
184  
180  
178  
173  
170  
167  
164  
161  
155  
150  
51  
52  
53  
54  
55  
56  
57  
58  
59  
60  
62  
64  
66  
68  
70  
72  
74  
76  
95  
78  
92  
80  
90  
82  
88  
84  
86  
86  
84  
88  
82  
90  
80  
92  
78  
94  
76  
95  
96  
75  
92  
98  
74  
90  
100  
102  
104  
106  
108  
110  
112  
116  
120  
72  
88  
71  
86  
69  
84  
68  
82  
67  
80  
65  
78  
64  
76  
62  
75  
60  
73  
c. Adjust air temperature rise by adjusting blower speed. In-  
crease blower speed to reduce temperature rise. Decrease  
blower speed to increase temperature rise. For low heat,  
speed selection can be low (factory setting), med--low, or  
med (5--speed blowers only).  
d. Remove thermostat jumpers and release Blower Access  
Door Switch.  
e. To change motor speed selection for low heat, remove  
blower motor lead from control LO--HEAT terminal.  
(See Fig. 33.) Select desired blower motor speed lead  
from 1 of the other terminals and relocate it to the LO--  
HEAT terminal. (See Table 13 for lead color identifica-  
tion). Reconnect original lead to SPARE terminal.  
a. Remove high fire regulator adjustment cap from gas  
valve pressure regulator.  
b. Manually close blower access door switch.  
c. Jumper R, W/W1 and W2 thermostat connections on  
control to run furnace in high heat. (See Fig. 33.)  
d. d. Turn high--heat adjusting screw (3/16--in. (5 mm) or  
smaller flat tipped screwdriver) counterclockwise (out)  
to decrease input rate or clockwise (in) to increase rate.  
e. Re--install high--fire adjustment caps.  
f. Leave manifold or similar device connected and proceed  
to Step 7.  
NOTE: DO NOT set high--heat manifold pressure less than  
3.2--in. wc or more than 3.8--in. wc for natural gas. If manifold  
pressure is outside this range, change main burner orifices.  
f. Repeat steps a through e.  
7. Verify natural gas high heat input rate by clocking meter.  
NOTE: Gas valve regulator adjustment caps must be in place for  
proper input to be clocked.  
!
CAUTION  
FURNACE OVERHEATING HAZARD  
a. Turn off all other gas appliances and pilots served by the  
meter.  
Failure to follow this caution may result in reduced furnace  
life.  
b. Run for 3 minutes in high--heat operation.  
c. Measure time (in sec) for gas meter to complete 1 revolu-  
tion and note reading.  
Recheck temperature rise. It must be within limits specified  
on the rating plate. Recommended operation is at the  
midpoint of rise range or slightly above.  
d. Refer to Table 12 for cubic ft. of gas per hr.  
e. Multiply gas rate cu ft. /hr by heating value (Btuh/cu ft.)  
to obtain input.  
g. When correct low heat input rate and temperature rise is  
achieved, proceed to Step 6.  
6. Adjust Manifold Pressure to Obtain High Heat Rate  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: Using the 2 cu. ft. or 5 cu. ft. gas meter dial provides  
greater accuracy in verifying gas input rate.  
!
WARNING  
If clocked rate does not match required input from Step 1,  
increase manifold pressure to increase input or decrease manifold  
pressure to decrease input. Repeat steps b through e until correct  
high heat input is achieved. Re--install high--heat regulator seal  
cap on gas valve.  
FIRE HAZARD  
Failure to reinstall manifold pressure tap plug in gas valve  
could result in personal injury, property damage or death.  
Reinstall manifold pressure tap plug in gas valve to prevent  
gas leak.  
8. Set high heat temperature rise.  
Jumper R to W/W1 and W2 to check high--gas--heat tem-  
perature rise. Do not exceed temperature rise ranges spe-  
cified on furnace rating plate for high heat. The furnace  
must operate within the temperature rise ranges specified  
on the furnace rating plate.  
j. Remove thermostat jumper wire from furnace control  
board.  
k. Turn LHT switch OFF.  
Determine the air temperature rise as follows:  
l. Turn gas valve ON/OFF switch to ON.  
m. Proceed to Step 9, “Set Blower Off Delay” before in-  
stalling blower access door.  
NOTE: Blower access door must be installed when taking  
temperature rise reading. Leaving blower access door off will  
result in incorrect temperature measurements.  
a. Verify the furnace is operating in high heat per Step 6.  
Place thermometers in return and supply ducts as close  
to furnace as possible. Be sure thermometers do not see  
radiant heat from heat exchangers. Radiant heat affects  
temperature rise readings.This practiceis particularly im-  
portant with straight--run ducts.  
!
CAUTION  
FURNACE OVERHEATING HAZARD  
Failure to follow this caution may result in reduced furnace  
life.  
b. When thermometer readings stabilize, subtract return--air  
temperaturefromsupply--air temperatureto determineair  
temperature rise.  
Recheck temperature rise. It must be within limits specified  
on the rating plate. Recommended operation is at the  
midpoint of rise range or slightly above.  
NOTE: If the temperature rise is outside this range, first check:  
(1.) Gas input for low--and high--heat operation.  
(2.) Derate for altitude if applicable.  
9. Set Blower Off Delay  
a. Remove Blower Access Door if installed.  
b. Turn Dip switch 2 and 3 ON or OFF for desired blower  
off delay. (See Table 14 and Fig 34.)  
(3.) Return and supply ducts for excessive restrictions  
causing static pressures greater than 0.50--in. wc.  
(4.) Dirty filter.  
10. Set thermostat heat anticipator.  
c. Adjust air temperature rise by adjusting blower speed. In-  
crease blower speed to reduce temperature rise. Decrease  
blower speed to increase temperature rise. For high heat,  
speed selection can be med--high, med (5--speed blowers  
only), or med--low (factory setting).  
a. Mechanical thermostat -- Set thermostat heat anticipator  
to match the amp. draw of the electrical components in  
the R--W/W1 circuit. Accurate amp. draw readings can  
be obtainedat thewires normallyconnected tothermostat  
subbase terminals, R and W. The thermostat anticipator  
should NOT be in the circuit while measuring current.  
!
(1.) Set LHT switch on furnace control board to ON.  
(2.) Remove thermostat from sub--base or from wall.  
WARNING  
ELECTRICAL SHOCK HAZARD  
(3.) Connect an amp. meter as shown in Fig. 55 across  
the R and W subbase terminals or R and W wires at  
wall.  
Failure to follow this warning could result in personal  
injury or death.  
Disconnect 115--v electrical power before changing speed  
tap.  
(4.) Record amp. draw across terminals when furnace is  
in low heat and after blower starts.  
(5.) Set heat anticipator on thermostat per thermostat in-  
structions and install on subbase or wall.  
d. To change motor speed selection for high heat, remove  
blower motor lead from control HI--HEAT terminal. (See  
Fig. 33.) Select desired blower motor speed lead from 1  
of the other terminals and relocate it to the HI--HEAT ter-  
minal. DO NOT use the low--heattap thatwas already set.  
(See Table 13 for lead color identification). Reconnect  
original lead to SPARE terminal.  
(6.) Turn LHT switch OFF.  
(7.) Install blower access door.  
b. Electronic thermostat: Set cycle rate for 3 cycles per hr.  
11. Set airflow CFM for cooling  
Select the desired blower motor speed lead for cooling air-  
flow. See Table 5--Air Delivery--CFM (With Filter). See  
Table 13 for lead color identification.  
e. Repeat steps a thru e.  
f. When correct high heat input rate and temperature rise is  
achieved, turn gas valve ON/OFF switch to OFF.  
Table 13 – Speed Selection  
COLOR  
White  
Black  
Yellow  
Orange†  
Blue  
SPEED  
Common  
High  
Me d --- H ig h  
Med  
AS SHIPPED  
BLW  
g. Release Blower Access Door switch.  
h. Remove manometer or similar device from gas valve.  
COOL  
SPARE  
SPARE  
HI---HEAT  
LO HEAT  
i. Re--install manifold pressure tap plug in gas valve. (See  
Fig 54.)  
Me d --- L o w  
Low*  
Red  
* Continuous---blower speed---as shipped default  
{ Not all models equipped with 5 speed motors  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 14 – 2--Stage Furnace Blower OFF delay Setup Switch  
DESIRED HEATING MODE  
BLOWER OFF DELAY (SEC.)  
SETUP SWITCH  
S W --- 2  
SETUP SWITCH  
S W --- 3  
90  
OFF  
OFF  
ON  
OFF  
ON  
OFF  
ON  
120  
150  
180  
ON  
guard switch did not function properly and correct condi-  
tion.  
f. Remove blockage from furnace vent elbow.  
g. Switch will auto--reset when it cools.  
h. Re--install vent connector.  
THERMOSTAT SUBBASE  
TERMINALS WITH  
THERMOSTAT REMOVED  
(ANITICIPATOR, CLOCK, ETC.,  
MUST BE OUT OF CIRCUIT.)  
HOOK-AROUND  
AMMETER  
NOTE: Should switch remain open longer than 3 minutes,  
furnace control board will lockout the furnace for 3 hours. To  
reset furnace control board, turn thermostat below room  
temperature or from HEAT to OFF and turn 115--v power OFF,  
then back ON.  
R
Y
W
G
3. Check Pressure Switch(es)  
This control proves operation of the draft inducer blower.  
a. Turn off 115--v power to furnace.  
b. Disconnect inducer motor lead wires from wire harness.  
c. Turn on 115--v power to furnace.  
10 TURNS  
d. Set thermostat to “call for heat” and wait 1 minute. When  
pressure switch is functioning properly, hot surface ig-  
niter should NOT glow and control diagnostic light  
flashes a status code 32. If hot surface igniter glows when  
inducer motor is disconnected, shut down furnace imme-  
diately.  
FROM UNIT 24-V  
CONTROL TERMINALS  
0.5 AMPS FOR THERMOSTAT  
ANTICIPATOR SETTING  
5.0 AMPS ON AMMETER  
10 TURNS AROUND JAWS  
=
EXAMPLE:  
e. Determine reason pressure switch did not function prop-  
erly and correct condition.  
f. Turn off 115--v power to furnace.  
A96316  
Fig. 55 -- Amp. Draw Check with Ammeter  
g. Reconnect inducer motor wires, replace outer door, and  
turn on 115--v power.  
Step 4 — Check Safety Controls  
The flame sensor, gas valve, and pressure switch were all checked  
in the Start--up procedure section as part of normal operation.  
h. Blower will run for 90 seconds before beginning the call  
for heat again.  
1. Check Main Limit Switch(es)  
i. Furnace should ignite normally.  
This control shuts off combustion system and energizes  
air--circulating blower motor, if furnace overheats. By us-  
ing this method to check limit control, it can be established  
that limit is functioning properly and will operate if there  
is a restricted return--air supply or motor failure. If limit  
control does not function during this test, cause must be  
determined and corrected.  
Step 5 — Checklist  
1. Put away tools and instruments. Clean up debris.  
2. Verify that switches for LHT and OFF--DELAY are  
blower OFF--DELAY are selected as desired.  
3. Verify that blower and burner access doors are properly in-  
stalled.  
a. Run furnace for at least 5 minutes.  
4. Cycle test furnace with room thermostat.  
b. Gradually block off return air with a piece of cardboard  
or sheet metal until the limit trips.  
5. Check operation of accessories per manufacturer fs in-  
structions.  
c. Unblock return air to permit normal circulation.  
d. Burners will re--light when furnace cools down.  
6. Review User’s Guide with owner.  
7. Attach literature packet to furnace.  
2. Check draft safeguard switch.  
The purpose of this control is to cause the safe shutdown  
of the furnace during certain blocked vent conditions.  
a. Verify vent pipe is cool to the touch.  
b. Disconnect power to furnace and remove vent connector  
from furnace vent elbow.  
c. Restore power to furnace and set room thermostat above  
room temperature.  
d. After normal start--up, allow furnace to operate for 2  
minutes, then block vent elbow in furnace 80% of vent  
area with a piece of flat sheet metal.  
e. Furnace should cycle off within 2 minutes. Ifgas doesnot  
shut off within 2 minutes, determine reason draft safe-  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 – Orifice Size* and Manifold Pressures (In wc) for Gas Input Rate  
A08485  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 -- Orifice Size and Manifold Pressures (In wc) for Gas Input Rate (cont.)  
A08485A  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 16 – Orifice Size* and Manifold Pressures (In wc) for Gas Input Rate  
A08219  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 16 -- Orifice Size* and Manifold Pressures (In wc) for Gas Input Rate (cont.)  
A08219A  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ELECTRICAL CONTROLS AND WIRING  
SERVICE AND MAINTENANCE  
PROCEDURES  
!
WARNING  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury or death.  
FIRE, PERSONAL INJURY AND UNIT DAMAGE  
HAZARD  
There may be more than one electrical supply to the  
furnace. Check accessories and cooling unit for additional  
electrical supplies that must be shut off during furnace  
servicing.  
Failure to follow this warning could result in personal injury,  
death and/or property damage.  
The ability to properly perform maintenance on this  
equipment requires certain knowledge, mechanical skills,  
tools, and equipment. If you do not possess these, do not  
attempt to perform any maintenance on this equipment other  
than those procedures recommended in the User’s Manual.  
The electrical ground and polarity for 115--v wiring must be  
properly maintained. Refer to Fig. 23 for field wiring information  
and to Fig. 57 for furnace wiring information.  
NOTE: If the polarity is not correct, the STATUS LED on the  
control will flash rapidly and prevent the furnace from heating.  
The control system also requires an earth ground for proper  
operation of the control and flame--sensing electrode.  
!
WARNING  
ELECTRICAL SHOCK, FIRE OR EXPLOSION  
HAZARD  
The 24--v circuit contains an automotive--type, 3--amp. fuse  
located on the control. (See Fig. 31.) Any shorts of the 24--v  
wiring during installation, service, or maintenance will cause this  
fuse to blow. If fuse replacement is required, use ONLY a 3--amp.  
fuse. The control LED will display status code 24 when fuse  
needs to be replaced.  
Failure to follow this warning could result in personal injury  
or death, or property damage.  
Before servicing, disconnect all electrical power to furnace.  
Verify proper operation after servicing.  
Proper instrumentation is required to service electrical controls.  
The control in this furnace is equipped with a Status Code LED  
(Light--Emitting Diode) to aid in installation, servicing, and  
troubleshooting. It can be viewed through the sight glass in  
blower access door. The furnace control LED is either ON  
continuously, rapid flashing, or a code composed of 2 digits. The  
first digit is the number of short flashes, the second digit is the  
number of long flashes.  
!
CAUTION  
UNIT OPERATION HAZARD  
Failure to follow this caution may result in improper unit  
operation or failure of unit components.  
For an explanation of status codes, refer to service label located  
on blower access door or Fig. 56, and the troubleshooting guide  
which can be obtained from your distributor.  
Label all wires prior to disconnection when servicing  
controls. Wiring errors can cause improper and dangerous  
operation.  
See Fig. 61 for a brief Troubleshooting guide.  
For Controls with an Amber LED  
The stored status codes will NOT be erased from the control  
memory, if 115-- or 24--v power is interrupted. The control will  
store up to five (5) status codes.  
!
CAUTION  
ENVIRONMENTAL HAZARD  
1. To retrieve status codes, proceed with the following:  
Failure to follow this caution may result in environmental  
pollution.  
NOTE: NO thermostat signal may be present at control, and all  
blower--OFF delays must be completed.  
Remove and recycle all components or materials (i.e. oil,  
refrigerant, control board, etc.) before unit final disposal.  
a. Leave 115--v power to furnace turned on.  
b. Remove outer access door.  
c. Look into blower access door sight glass for current LED  
status. Removing blower access door will open blower  
access door switch and terminate 115--v power to control  
so that status code is not displayed.  
Step 1 — Introduction  
GENERAL  
These instructions are written as if the furnace is installed in an  
upflow application. An upflow furnace application is where the  
blower is located below the combustion and controls section of  
the furnace, and conditioned air is discharged upward. Since this  
furnace can be installed in any of the 4 positions shown in Fig. 4,  
you must revise your orientation to component location  
accordingly.  
d. BRIEFLY remove insulated terminal wire from the draft  
safeguard (DSS) switch until LED goes out, then recon-  
nect it.  
NOTE: If wire to DSS is disconnected longer than 4 sec, main  
blower starts, and retrieval request is ignored.  
2. When above items have been completed, the LED flashes  
status code 4 times. Record this status code for further  
troubleshooting. After the LED flashes status code four  
times, BRIEFLY remove wire again from DSS switch un-  
til LED goes out, then reconnect it to retrieve previous  
status code (if available). Repeat as needed for more previ-  
ous status codes or until Code 11 appears.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE  
If status code recall is needed, briefly remove then reconnect one main limit wire to display last stored status code. On RED LED boards do not remove power or blower door before initiating status code recall.  
LED CODE  
STATUS  
CONTINUOUS OFF - Check for 115VAC at L1 and L2, and 24VAC at SEC-1 and SEC-2.  
CONTINUOUS ON - Control has 24VAC power.  
RAPID FLASHING - Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions.  
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.  
32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED - If open longer than  
five minutes, inducer shuts off for 15 minutes before retry. If opens during blower on-delay  
period, blower will come on for the selected blower off-delay. Check for:  
11 NO PREVIOUS CODE - Stored status code is erased automatically after 72 hours.  
On RED LED boards stored status codes can also be erased when power  
(115 VAC or 24 VAC) to control is interrupted.  
- Excessive wind  
- Restricted vent  
- Defective inducer motor  
- Low inducer voltage (115 VAC)  
- Low inlet gas pressure (if LGPS used)  
12 BLOWER ON AFTER POWER UP (115 VAC or 24 VAC) -Blower runs for the  
selected blower off-delay time, if unit is powered up during a call for heat  
(R-W/W1 closed) or (R-W/W1) opens during blower on-delay.  
- Proper vent sizing  
- Defective pressure switch  
- Inadequate combustion air supply  
- Disconnected or obstructed pressure tubing  
13 LIMIT CIRCUIT LOCKOUT - Lockout occurs if a limit, draft safeguard, flame rollout,  
or blocked vent switch (if used) is open longer than 3 minutes.  
33 LIMIT CIRCUIT FAULT - Indicates a limit, draft safeguard, flame rollout, or blocked vent  
switch (if used) is open. Blower will run for 4 minutes or until open switch remakes  
whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open  
less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout  
switch and BVSS require manual reset. Check for: - Dirty filter or restricted duct system  
- Control will auto reset after three hours.  
- Refer to #33.  
14 IGNITION LOCKOUT - Control will auto-reset after three hours. Refer to #34.  
21 GAS HEATING LOCKOUT - Control will NOT auto reset.  
Check for: - Mis-wired gas valve  
- Defective control (valve relay)  
- Defective blower motor or capacitor  
- Defective switch or connections  
- Proper vent sizing  
- Loose blower wheel  
- Restricted vent  
- Excessive wind  
22 ABNORMAL FLAME-PROVING SIGNAL - Flame is proved while gas valve is de-  
energized. Inducer will run until fault is cleared. Check for:  
- Inadequate combustion air supply (Flame Roll-out Switch open).  
- Leaky gas valve  
- Stuck-open gas valve  
34 IGNITION PROVING FAILURE - Control will try three more times before lockout #14 occurs.  
If flame signal lost during blower on-delay period, blower will come on for the selected  
blower off-delay. Check for: - Oxide buildup on flame sensor (clean with fine steel wool)  
- Proper flame sense microamps (.5 microamps D.C. min., 4.0 - 6.0 nominal)  
23 PRESSURE SWITCH DID NOT OPEN Check for: - Obstructed pressure tubing  
- Pressure switch stuck closed  
24 SECONDARY VOLTAGE FUSE IS OPEN Check for: - Short circuit in secondary  
voltage (24VAC) wiring.  
- Manual valve shut-off  
- Control ground continuity  
- Low inlet gas pressure  
- Defective Hot Surface Ignitor  
31 HIGH-HEAT PRESSURE SWITCH OR RELAY DID NOT CLOSE OR REOPENED  
Control relay may be defective, refer to status code #32  
- Gas valve defective or gas valve turned off  
- Inadequate flame carryover or rough ignition  
- Flame sensor must not be grounded  
COMPONENT TEST  
- Green/Yellow wire MUST be connected to furnace sheet metal  
To initiate the component test sequence, shut OFF the room thermostat or disconnect the  
"R" thermostat lead. Briefly short the TEST/TWIN terminal to the "Com 24V" terminal.  
Status LED will flash last status code and then turn ON the inducer motor. The inducer  
motor will start in HIGH speed and remain on HIGH speed until the end of the test then  
shift to LOW speed for 7 to 15 seconds. The hot surface igniter, blower motor LO HEAT  
speed, blower motor HI HEAT speed, and blower motor COOL speed will be turned ON for  
10-15 seconds each. Gas Valve and Humidifier will not be turned on. When the blower is  
turned OFF the inducer will be switched to low-speed for 10 seconds.  
43 LOW-HEAT PRESSURE SWITCH OPEN WHILE HIGH-HEAT PRESSURE SWITCH IS  
CLOSED - Check for:  
- Disconnected or obstructed pressure tubing  
- Low-heat pressure switch stuck open  
- Mis-wired pressure switches  
- Low inlet gas pressure (if LGPS used)  
45 CONTROL CIRCUITRY LOCKOUT Auto-reset after one hour lockout due to;  
- Gas valve relay stuck open  
- Flame sense circuit failure  
- Software check error  
Reset power to clear lockout. Replace control if status code repeats.  
327598-101 REV. C  
A04210  
Fig. 56 -- Service Label  
Step 2 — Care and Maintenance  
!
WARNING  
!
WARNING  
CARBON MONOXIDE POISONING AND FIRE  
HAZARD  
FIRE OR EXPLOSION HAZARD  
Failure to follow this warning could result in personal  
injury, death, and/or property damage.  
Failure to follow this warning could result in personal  
injury, death and/or property damage.  
Never operate unit without a filter or with filter access door  
removed.  
Never store anything on, near, or in contact with the  
furnace, such as:  
1. Spray or aerosol cans, rags, brooms, dust mops,  
vacuum cleaners, or other cleaning tools.  
2. Soap powders, bleaches, waxes or other cleaning  
compounds, plastic or plastic containers, gasoline,  
kerosene, cigarette lighter fluid, dry cleaning fluids,  
or other volatile fluids.  
3. Paint thinners and other painting compounds, paper  
bags, or other paper products. Explosure to these  
materials could lead to corrosion of the heat  
exchanger.  
!
CAUTION  
CUT HAZARD  
Failure to follow this caution may result in personal injury.  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing, safety glasses and  
gloves when handling parts and servicing furnaces.  
The minimum maintenance on this furnace is as follows:  
For continuing high performance and to minimize possible  
furnace failure, periodic maintenance must be performed on this  
furnace. Consult your local dealer about proper frequency of  
maintenance and the availability of a maintenance contract.  
1. Check and clean air filter each month or more frequently if  
required. Replace if torn.  
2. Check blower motor and wheel for cleanliness each heat-  
ing and cooling season. Clean as necessary.  
3. Check electrical connections for tightness and controls for  
proper operation each heating season. Service as neces-  
sary.  
!
WARNING  
ELECTRICAL SHOCK AND FIRE HAZARD  
4. Inspect burner compartment before each heating season  
for rust, corrosion, soot or excessive dust. If necessary,  
have furnace and burner serviced by a qualified service  
agency.  
5. Inspect the vent pipe/vent system before each heating sea-  
son for rust, corrosion, water leakage, sagging pipes or  
broken fittings. Have vent pipes/vent system serviced by a  
qualified service agency.  
Failure to follow this warning could result in personal  
injury, death or property damage.  
Turn off the gas and electrical supplies to the unit before  
performing any maintenance or service. Follow the  
operating instructions on the label attached to the furnace.  
6. Inspect any accessories attached to the furnace such as a  
humidifier or electronic air cleaner. Perform any service or  
maintenance to the accessories as recommended in the ac-  
cessory instructions.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A07125  
Fig. 57 -- Wiring Diagram  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE 17 – FILTER SIZE INFORMATION (IN. / MM)  
FILTER SIZE  
FURNACE CASING WIDTH  
SIDE  
RETURN  
BOTTOM  
RETURN  
FILTER TYPE  
16 x25 x 3/4  
14 x25 x 3/4  
14---1/2 (368)  
17---1/2 (445)  
21 (533)  
Washable*  
Washable*  
Washable*  
Washable*  
(406 x635 x 19)  
(356 x635 x 19)  
16 x25 x 3/4  
(406 x635 x 19)  
16 x25 x 3/4  
(406 x635 x 19)  
16 x25 x 3/4  
(406 x635 x 19)  
16 x25 x 3/4  
(406 x635 x 19)  
20 x25 x 3/4  
(508 x635 x 19)  
24 x25 x 3/4  
(610 x635 x 19)  
24 (610)  
* Recommended  
** Some furnaces may have 2 filters.  
CLEANING AND/OR REPLACING AIR FILTER  
To ensure long life and high efficiency, clean accumulated dirt  
and grease from blower wheel and motor annually.  
The air filter arrangement will vary depending on the application.  
The inducer and blower motors are pre--lubricated and require no  
additional lubrication. These motors can be identified by the  
absence of oil ports on each end of the motor.  
NOTE: If the filter has an airflow direction arrow, the arrow  
must point towards the blower.  
Clean blower motor and wheel as follows:  
1. Turn off electrical supply to furnace.  
!
CAUTION  
2. Loosen the thumbscrew from outer door and remove outer  
door.  
CUT HAZARD  
Failure to follow this caution may result in personal injury.  
3. For downflow or horizontal furnaces having vent pipes  
within the furnace that pass in front of the blower access  
door:  
Sheet metal parts may have sharp edges or burrs. Use care  
and wear appropriate protective clothing, safety glasses and  
gloves when handling parts and servicing furnaces.  
a. Disconnect vent connector from furnace vent elbow.  
b. Disconnect and remove short piece of vent pipe from  
within furnace.  
Media cabinet filter procedures:  
NOTE: Media Cabinet is included with two--stage furnace.  
4. Remove 2 screws from blower access door and remove  
blower access door.  
5. Disconnect blower leads from furnace control. Record  
wire color and location for reassembly. All other factory  
wires can be left connected, but field thermostat connec-  
tions may need to be disconnected depending on their  
length and routing.  
1. Turn off electrical supply to furnace before removing filter  
access door.  
2. Remove filter cabinet door.  
3. Slide filter out of cabinet.  
4. If equipped with permanent, washable 3/4--in. (19 mm) fil-  
ter, clean filter by spraying cold tap water through filter in  
opposite direction of airflow. Rinse filter and let dry. Oil-  
ing or coating of the filter is not recommended. See Table  
17 for size information.  
6. Remove 2 screws holding control box to blower shelf.  
7. Hang control box from front of furnace casing and away  
from blower compartment.  
8. Remove 2 screws holding blower assembly to blower  
deck and slide blower assembly out of furnace.  
9. Clean blower wheel and motor using a vacuum with soft  
brush attachment. Blower wheel blades may be cleaned  
with a small paint or flux brush. Do not remove or disturb  
balance weights (clips) on blower wheel blades.  
5. If equipped with factory--specified disposable media filter,  
replace only with media filter having the same part num-  
ber and size. For expandable replacement media, refer to  
the instructions included with the replacement media. If  
equipped with accessory KGAFR0301ALL external filter  
rack. See Table 17.  
10. Vacuum any loose dust from blower housing, wheel and  
motor.  
6. Slide filter into cabinet.  
7. Replace filter cabinet door.  
11. If a greasy residue is present on blower wheel, remove  
wheel from the blower housing and wash it with an appro-  
priate degreaser. To remove wheel:  
8. Turn on electrical supply to furnace.  
BLOWER MOTOR AND WHEEL  
NOTE: Before disassembly, mark blower mounting arms, motor,  
and blower housing so motor and each arm is positioned at the  
same location during reassembly.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
a. Disconnectcapacitorwires(if equipped)and groundwire  
attached to blower housing.  
Failure to follow this warning could result in personal  
injury or death.  
b. Remove screws securing cutoff plate and remove cutoff  
plate from housing.  
Blower access door switch opens 115--v power to control.  
No component operation can occur unless switch is closed.  
Caution must be taken when manually closing this switch  
for service purposes.  
c. Loosen set screw holding blower wheel on motor shaft  
(160+/--20 in.--lb. when reassembling).  
d. Remove bolts holding motor to blower housing and slide  
motor out of wheel (40+/--10in.--lb. whenreassembling).  
NOTE: The blower wheel should not be dropped or bent as  
balance will be affected.  
e. Remove blower wheel from housing.  
f. Clean wheel and housing.  
The following steps should be performed by a qualified  
service agency.  
12. Reassemble motor and blower by reversing steps 11e,  
through 11a. Be sure to reattach ground wire to the blower  
housing.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13. Verify that blower wheel is centered in blower housing  
and set screw contacts the flat portion of the motor shaft.  
Loosen set screw on blower wheel and reposition if neces-  
sary.  
cycle. Turn outdoor circuit breaker on after completing  
cooling cycle.  
CLEANING HEAT EXCHANGER  
The following steps should be performed by a qualified  
service agency:  
14. Spin the blower wheel by hand to verify that the wheel  
does not rub on the housing.  
NOTE: If the heat exchangers get a heavy accumulation of soot  
and carbon, they should be replaced rather than trying to clean  
them thoroughly. A build--up of soot and carbon indicates that a  
problem exists which needs to be corrected, such as improper  
adjustment of manifold pressure, insufficient or poor quality  
combustion air, incorrect size or damaged manifold orifice(s),  
improper gas, or a restricted heat exchanger. Action must be taken  
to correct the problem.  
15. Reinstall blower assembly in furnace.  
16. Reinstall control box assembly in furnace.  
!
CAUTION  
UNIT DAMAGE HAZARD  
Failure to follow this caution may result in shortened heat  
exchanger life.  
If it becomes necessary to clean the heat exchangers because of  
dust or corrosion, proceed as follows:  
Heating fan speed(s) MUST be adjusted to provide proper  
air temperature rise as specified on the rating plate.  
Recommended operation is at the midpoint of the rise range  
or slightly above. Refer to “SET TEMPERATURE RISE”  
under START--UP, ADJUSTMENT, and SAFETY  
CHECK.  
1. Turn OFF gas and electrical power to furnace.  
2. Remove outer access door.  
3. Disconnect vent connector from furnace vent elbow.  
4. For downflow or horizontal furnace having an internal  
vent pipe, remove internal vent pipe within the casing.  
5. Disconnect wires to the following components. Mark  
wires to aid in reconnection of (be careful when discon-  
necting wires from switches because damage may occur):  
NOTE: Refer to Table 13 for motor speed lead relocation if leads  
were not identified before disconnection.  
17. Reconnect blower leads to furnace control. Refer to fur-  
nace wiring diagram, and connect thermostat leads if pre-  
viously disconnected.  
18. To check blower for proper rotation:  
a. Turn on electrical supply.  
a. Draft safeguard switch.  
b. Inducer motor.  
c. Pressure switches.  
d. Limit overtemperature switch.  
e. Gas valve.  
b. Manually close blower access door switch.  
f. Hot surface igniter.  
g. Flame--sensing electrode  
h. Flame rollout switches.  
NOTE: If thermostat terminals are jumpered at the time blower  
access door switch is closed, blower will run for 90 sec before  
beginning a heating or cooling cycle.  
6. Remove screws that fasten the collector box assembly to  
the cell panel. Be careful not to damage the collector box.  
Inducer assembly and elbow need not be removed from  
collector box.  
c. Perform component self--test as shown at the bottom of  
the SERVICE label, located on the front of blower access  
door.  
d. Verify blower is rotating in the correct direction.  
7. Disconnect gas line from gas manifold.  
19. If furnace is operating properly, RELEASE BLOWER  
ACCESS DOOR SWITCH. Remove any jumpers or re-  
connect any disconnected thermostat leads. Replace  
blower access door.  
8. Remove the 5 screws that attach the burner assembly to  
the cell panel. The gas valve and individual burners need  
not be removed from support assembly. Remove NOx  
baffles if installed.  
NOTE: Be very careful when removing burner assembly to  
avoid breaking igniter. See Fig. 58 and 59 for correct igniter  
location.  
!
WARNING  
ELECTRICAL SHOCK HAZARD  
Failure to follow this warning could result in personal  
injury, or death.  
Blower access door switch opens 115--v power to furnace  
control. No component operation can occur unless switch is  
closed. Exercise caution to avoid electrical shock from  
exposed electrical components when manually closing this  
switch for service purposes.  
20. Downflow or horizontal furnaces with vent pipe through  
furnace only:  
a. Install and connect short piece of vent pipe inside furnace  
to existing vent.  
b. Connect vent connector to vent elbow.  
21. Turn on gas supply and cycle furnace through one com-  
plete heating and cooling cycle. Verify the furnace temper-  
ature rise as shown in Adjustments Section. Adjust tem-  
perature rise as shown in Adjustments Section. If outdoor  
temperature is below 70_F (21_C) turn off circuit breaker  
to outdoor unit before running furnace in the cooling  
A05025  
Fig. 58 -- Igniter Position--Side View  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9. Using field--provided 25--caliber rifle cleaning brush,  
36--in. (914 mm) long 1/4--in. (6 mm) diameter steel  
spring cable, a variable speed, reversible electric drill, and  
vacuum cleaner, clean cells as follows:  
1-7/8  
(47.6 mm)  
a. Remove metal screw fitting from wire brush to allow in-  
sertion into cable.  
b. Insert the twisted wire end of brush into end of spring  
cable, and crimp tight with crimping tool or crimp by  
striking with ball--peen hammer. TIGHTNESS IS VERY  
IMPORTANT.  
NOTE: The materials needed in item 9 can usually be purchased  
at local hardware stores.  
A05026  
Fig. 59 -- Igniter Position--Top View  
(1.) Attach variable--speed, reversible drill to the end of  
spring cable (end opposite brush).  
(2.) Insert brush end of cable into the outlet opening of  
cell and slowly rotate with drill. DO NOT force  
cable. Gradually insert cable into upper pass of cell.  
(See Fig. 60.)  
(3.) Work cable in and out of cell 3 or 4 times to obtain  
sufficient cleaning. DO NOT pull cable with great  
force. Reverse drill and gradually work cable out.  
(4.) Insert brush end of cable in burner inlet opening of  
cell, and proceed to clean 2 lower passes of cell in  
same manner as upper pass.  
(5.) Repeat foregoing procedures until each cell in fur-  
nace has been cleaned.  
A91252  
(6.) Using vacuum cleaner, remove residue from each  
cell.  
Fig. 60 -- Cleaning Heat Exchanger Cell  
(7.) Using vacuum cleaner with soft brush attachment,  
clean burner assembly.  
16. Replace blower access door only, if it was removed.  
17. Set thermostat above room temperature and check furnace  
for proper operation.  
(8.) Clean flame sensor with fine steel wool.  
(9.) Install NOx baffles (if removed.)  
(10.) Reinstall burner assembly. Center burners in cell  
openings.  
18. Verify blower airflow and speed changes between heating  
and cooling.  
10. Remove old sealant from cell panel and collector box  
flange.  
!
WARNING  
FIRE OR EXPLOSION HAZARD  
11. Spray releasing agent on the heat exchanger cell panel  
where collector box assembly contacts cell panel.  
Failure to follow this warning could result in personal injury,  
death and/or property damage.  
NOTE: A releasing agent such as cooking spray or equivalent  
(must not contain corn or canola oil, aromatic or halogenated  
hydrocarbons or inadequate seal may occur) and RTV sealant  
(G.E. 162, 6702, or Dow--Corning 738) are needed before  
starting installation. DO NOT substitute any other type of RTV  
sealant. G.E. 162 (P771--9003) is available through RCD in 3--oz.  
tubes.  
Never use a match or other open flame to check for gas  
leaks. Use a soap--and--water solution.  
19. Check for gas leaks.  
20. Replace outer access door.  
12. Apply new sealant to flange of collector box and attach to  
cell panel using existing screws, making sure all screws  
are secure.  
13. Reconnect wires to the following components (Use con-  
nection diagram on wiring label, if wires were not marked  
for reconnection locations.):  
Step 3 — Sequence of Operation  
NOTE: Furnace control must be grounded for proper operation  
or control will lockout. Control is grounded through green wire  
connected to gas valve and burner bracket screw. Using the  
schematic diagram in Fig. 57, follow the sequence of operation  
through the different modes. Read and follow the wiring diagram  
very carefully.  
a. Draft safeguard switch.  
b. Inducer motor.  
c. Pressure switches.  
NOTE: If a power interruption occurs during a call for heat  
(W/W1 or W/W1--and--W2), the control run the blower for the  
selected blower off--delay period two seconds after power is  
restored and if the thermostat is still calling for gas heating. The  
LED light will flash code 12 during this period, after which the  
LED will be ON continuous, as long as no faults are detected.  
After this period, the furnace will respond to the thermostat  
normally.  
d. Limit overtemperature switch.  
e. Gas valve.  
f. Hot surface igniter.  
g. Flame--sensing electrode.  
h. Flame rollout switches.  
14. Reinstall internal vent pipe, if applicable.  
15. Reinstall vent connector on furnace vent elbow. Securely  
fasten vent connector to vent elbow with 2 field--supplied,  
corrosion--resistant, sheet metal screws located 180_ apart.  
The blower door must be installed for power to be conducted  
through the blower door interlock switch ILK to the furnace  
control CPU, transformer TRAN, inducer motor IDM, blower  
motor BLWM, hot--surface igniter HSI, and gas valve GV.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Two--Stage Heating (Adaptive mode) with Single--  
Stage Thermostat  
d. Flame--Proving--When the burner flame is proved at the  
flame--proving sensor electrode FSE, the inducer motor  
IDM switches to low--speed unless running at high--  
speed, and the furnace control CPU begins the blower--  
ON delay period and continues tohold thegas valveGV--  
M open. If the burner flame is not proved within two  
seconds, the control CPU will close the gas valve GV--M,  
and the control CPU will repeat the ignition sequence for  
up to three more Trials--For--Ignition before going to Ig-  
nition-- Lockout. Lockout will be reset automatically  
after three hours, by momentarily interrupting 115 vac  
power to the furnace, or by interrupting 24 vac power at  
SEC1 or SEC2 to the furnace control CPU (not at W/W1,  
G, R, etc.). If flame is proved when flame should not be  
present, the furnace control CPU will lock out of Gas--  
Heating mode and operate the inducer motor IDM on  
high speed until flame is no longer proved.  
(See Fig. 23 or 32 for thermostat connections)  
NOTE: The low--heat only switch (LHT) selects either the  
low--heat only operation mode when ON, (see item 2. below) or  
the adaptive heating mode when OFF in response to a call for  
heat. (See Fig. 33.) When the W2 thermostat terminal is energized  
it will always cause high--heat operation when the R to W circuit  
is closed, regardless of the setting of the low--heat only switch.  
This furnace can operate as a two--stage furnace with a  
single--stage thermostat because the furnace control CPU includes  
a programmed adaptive sequence of controlled operation, which  
selects low--heat or high--heat operation. This selection is based  
upon the stored history of the length of previous gas--heating  
periods of the single--stage thermostat.  
The furnace will start up in either low-- or high--heat. If the  
furnace starts up in low--heat, the control CPU determines the  
low--heat on--time (from 0 to 16 minutes) which is permitted  
before switching to high--heat.  
e. Blower--ON Delay--If the burner flame is proven the  
blower--ON delay for low--heat and high--heat are as fol-  
lows:  
If the power is interrupted, the stored history is erased and the  
control CPU will select low--heat for up to 16 minutes and then  
switch to high--heat, as long as the thermostat continues to call for  
heat. Subsequent selection is based on stored history of the  
thermostat cycle times.  
Low--Heat--45 seconds after the gas valve GV--M is en-  
ergized the blower motor (BLWM) is energized at LO  
HEAT speed.  
High--Heat--25 seconds after the gas valve GV--M is en-  
ergized the BLWM is energized at HI HEAT speed. Sim-  
ultaneously, the electronic air cleaner (EAC--1) terminal  
is energized and remains energized as long as the BLWM  
is energized.  
The wall thermostat “calls for heat”, closing the R to W circuit.  
The furnace control performs a self--check, verifies the low--heat  
and high--heat pressure switch contacts LPS and HPS are open,  
and starts the inducer motor IDM in high--speed.  
f. SwitchingfromLow--to High--Heat--Ifthe furnacecon-  
trol CPU switches from low--heat to high--heat, the fur-  
nace control CPU will switch the inducer motor IDM  
speed from low to high. The high--heat pressure switch  
relay HPSR is de--energized to close the NC contact.  
When sufficient pressure is available the high--heat pres-  
sure switch HPS closes, and the high--heat gas valve  
solenoid GV--HI is energized. The blower motor BLWM  
will switch to HI HEAT speed five seconds after the fur-  
nace control CPU switches from low--heat to high--heat.  
a. Inducer Prepurge Period  
(1.) If the furnace control CPU selects low--heat opera-  
tion the inducer motor IDM comes up to speed, the  
low--heat pressure switch LPS closes, and the fur-  
nace control CPU begins a 15--second prepurge  
period. After the low--heatpressure switchre--closes  
thefurnacecontrolCPUwill begina 15--secondpre-  
purge period, and continue to run the inducer motor  
IDM at high--speed.  
g. Switching from High-- to Low--Heat--The furnace con-  
trol CPU will not switch from high--heat to low--heat  
whilethethermostat R--to--Wcircuit isclosed when using  
a single stage thermostat.  
(2.) If the furnace control CPU selects high--heat opera-  
tion, the inducer motor IDM remains running at  
high--speed, and the high--heatpressure switch relay  
HPSR is de--energized to close the NC contact.  
When sufficient pressure is available the high--heat  
pressure switch HPS closes, and the high--heat gas  
valve solenoid GV--HI is energized. The furnace  
control CPU begins a 15--second prepurge period  
after the low--heat pressure switch LPS closes. If the  
high--heat pressure switch HPS fails to close and the  
low--heat pressure switch LPS closes, the furnace  
will operate at low--heat gas flow rate until thehigh--  
heat pressure switch closes for a maximum of 2  
minutes after ignition.  
h. Blower--OFF Delay--When the thermostatis satisfied, the  
R to W circuit is opened, de--energizing the gas valve  
GV--M,stoppinggas flowto theburners, andde--energiz-  
ing the humidifier terminal HUM. The inducer motor  
IDM will remain energized for a 5--second post--purge  
period. The blower motor BLWM and air cleaner termin-  
al EAC--1 will remain energized for 90, 120, 150, or 180  
seconds (depending on selection at blower--OFF delay  
switches). The furnace control CPU is factory--set for a  
120--second blower--OFF delay.  
2. Two--Stage Thermostat and Two--Stage Heating (See Fig.  
31 for thermostat connections)  
b. Igniter Warm--Up--At the end of the prepurge period,  
the (Hot Surface Igniter) HSI is energized for a  
17--second igniter warm--up period.  
NOTE: In this mode the LHT must be ON to select the low--heat  
only operation mode in response to closing the thermostat  
R--to--W1 circuit. Closing the thermostat R--to--W1--and--W2  
circuits always causes high--heat operation, regardless of the  
setting of the low--heat--only switch.  
c. Trial--for--Ignition Sequence--When the igniter warm--  
up period is completed the main gas valve relay contacts  
GVR--1 and --2 close to energize the gas valve solenoid  
GV--M,thegas valveopens, and24 vacpower issupplied  
for a field--installed humidifier at the HUM terminal. The  
gas valve solenoid GV--M permits gas flowto theburners  
where it is ignited by the HSI. Five sec after the GVR  
closes, a 2--sec flame proving period begins. The HSI ig-  
niter will remain energized until the flame issensed orun-  
til the 2--sec flame proving period begins. If the furnace  
control CPU selects high--heat operation, the high--heat  
gas valve solenoid GV--HI is also energized.  
The wall thermostat “calls for heat”, closing the R--to--W1 circuit  
for low--heat or closing the R--to--W1 and--W2 circuits for  
high--heat. The furnace control performs a self--check, verifies the  
low--heat and high--heat pressure switch contacts LPS and HPS  
are open, and starts the inducer motor IDM in high--speed.  
The start up and shut down functions and delays described in  
item 1. above apply to the 2--stage heating mode as well, except  
for switching from low-- to high--Heat and vice versa.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
a. Switching from Low-- to High--Heat--If the thermostat  
R--to-- W1 circuit is closed and the R--to--W2 circuit  
closes, the furnace control CPU will switch the inducer  
motor IDM speed from low to high. The high--heat pres-  
sure switch relay HPSR is de--energized to close the NC  
contact. When sufficient pressure is available the high--  
heat pressure switch HPS closes, and the high--heat gas  
valve solenoid GV--HI is energized. The blower motor  
BLWM will switch to HI HEAT speed five seconds after  
the R--to--W2 circuit closes.  
b. Switching from High-- to Low--Heat--If the thermostat  
R--to--W2circuitopens,andtheR--to--W1 circuitremains  
closed, the furnace control CPU will switch the inducer  
motor IDM speed from high to low. The high--heat pres-  
sure switch relay HPSR is energized to open the NC con-  
tact and de--energize the high--heat gas valve solenoid  
GV--HI. When the inducer motor IDM reduces pressure  
sufficiently, the high--heat pressure switch HPS will  
open. The gas valve solenoid GV--M will remain ener-  
gized as long as the low--heat pressure switch LPS re-  
mains closed. The blower motor BLWM will switch to  
LO HEAT speed five seconds after the R--to--W2 circuit  
opens.  
starts the furnace blower motor BLWM at low--cool speed (same  
speed as LO HEAT).  
If the furnace control CPU switches from low--cooling to  
high--cooling, the furnace control CPU will energize the air  
conditioning relay ACR. When the air conditioning relay ACR is  
energized the R--to--Y1--and--Y2 circuits switch the outdoor unit  
to high--cooling speed, and the R--to--G--and--Y1--and--Y/Y2  
circuits switch the furnace blower motor BLWM to COOL speed.  
NOTE: When transitioning from low--cooling to high--cooling  
the outdoor unit compressor will shut down for 1 minute while  
the BLWM continues to run at low--cool speed (same speed as  
LO--HEAT) until the outdoor unit compressor comes back on at  
high speed.  
The electronic air cleaner terminal EAC--1 is energized with 115  
vac whenever the blower motor BLWM is operating. When the  
thermostat is satisfied, the R--to--G--and--Y circuit are opened.  
The outdoor unit stops, and the furnace blower BLWM and  
electronic air cleaner terminal EAC--1 will remain energized for  
an additional 90 seconds. Jumper Y1 to DHUM to reduce the  
cooling off--delay to 5 seconds. (See Fig. 34.)  
c. Two--Stage Thermostat and Two--Speed Cooling (See  
Fig. 31 for thermostat connections)  
NOTE: The air conditioning relay disable jumper ACRDJ must  
be disconnected to allow thermostat control of the outdoor unit  
staging. (See Fig. 33.)  
3. Cooling Mode--The thermostat “calls for cooling.”  
a. Single--Speed Cooling--  
(See Fig. 27 for thermostat connections)  
The thermostat closes the R--to--G--and--Y1 circuits for  
low--cooling or closes the R--to--G--and--Y1--and--Y2 circuits for  
high--cooling. The R--to--Y1 circuit starts the outdoor unit on  
low--cooling speed, and the R--to--G--and--Y1 circuit starts the  
furnace blower motor BLWM on low--cool speed (same speed as  
LO HEAT). The R--to--Y1--and--Y2 circuits start the outdoor unit  
on high--cooling speed, and the R--to--G--and-- Y/Y2 circuits start  
the furnace blower motor BLWM on COOL speed. The  
electronic air cleaner terminal EAC--1 is energized with 115 vac  
whenever the blower motor BLWM is operating. When the  
The thermostat closes the R--to--G--and--Y circuits. The  
R--to-- Y circuit starts the outdoor unit, and the R--to--  
G--and--Y/Y2 circuits start the furnace blower motor  
BLWM on COOL speed.  
The electronic air cleaner terminal EAC--1 is energized  
with 115 vacwhen theblower motorBLWM isoperating.  
When the thermostat is satisfied, the R--to--G and--Y cir-  
cuits are opened. The outdoor unit will stop, and the fur-  
nace blower motor BLWMwill continueoperating onthe  
COOL speed for an additional 90 seconds. Jumper Y/Y2  
to DHUM to reduce the cooling off--delay to 5 seconds.  
(See Fig. 24.)  
thermostat  
is  
satisfied,  
the  
R--to--G--and--Y1  
or  
R--to--G--and--Y1--and--Y2 circuits are opened. The outdoor unit  
stops, and the furnace blower BLWM and electronic air cleaner  
terminal EAC--1 will remain energized for an additional 90  
seconds. Jumper Y1 to DHUM to reduce the cooling off--delay to  
5 seconds. (See Fig. 33.)  
b. Single--Stage Thermostat and Two--Speed Cooling  
(Adaptive Mode)  
(See Fig. 32 for thermostat connections)  
4. Thermidistat Mode  
This furnace can operate a two--speed cooling unit with  
a single--stage thermostat because the furnace control  
CPU includes a programmed adaptive sequence of con-  
trolled operation, which selects low--cooling or high--  
cooling operation. This selection is based upon the stored  
history of the length of previous cooling period of the  
single--stage thermostat.  
(See Fig. 26 -- 28 for Thermidistat connections) The dehu-  
midification output, DHUM on the Thermidistat should be  
connected to the furnace control thermostat terminal  
DHUM. When there is a dehumidify demand, the DHUM  
input is activated, which means 24 vac signal is removed  
from the DHUM input terminal. In other words, the  
DHUM input logic is reversed. The DHUM input is  
turned ON when no dehumidify demand exists. Once 24  
vac is detected by the furnace control on the DHUM input,  
the furnace control operates in Thermidistat mode. If the  
DHUM input is low for more than 48 hours, the furnace  
control reverts back to non--Thermidistat mode.  
NOTE: The air conditioning relay disable jumper ACRDJ must  
be connected to enable the adaptive cooling mode in response to  
a call for cooling. (See Fig. 33.) When ACRDJ is in place, the  
furnace control CPU can turn on the air conditioning relay ACR  
to energize the Y/Y2 terminal and switch the outdoor unit to  
high--cooling.  
The cooling operation described in item 3. above also ap-  
plies to operation with a Thermidistat. The exceptions are  
listed below:  
The furnace control CPU can start up the cooling unit in either  
low-- or high--cooling. If starting up in low--cooling, the furnace  
control CPU determines the low--cooling on--time (from 0 to 20  
minutes) which is permitted before switching to high--cooling. If  
the power is interrupted, the stored history is erased and the  
furnace control CPU will select low--cooling for up to 20 minutes  
and then energize the air conditioning relay ACR to energize the  
Y/Y2 terminal and switch the outdoor unit to high--cooling, as  
long as the thermostat continues to call for cooling. Subsequent  
selection is based on stored history of the thermostat cycle times.  
The wall thermostat “calls for cooling”, closing the  
R--to--G--and--Y circuits. The R--to--Y1 circuit starts the outdoor  
unit on low--cooling speed, and the R--to--G--and--Y1 circuits  
a. Low cooling -- When the R--to--G--and--Y1 circuit is  
closedandthereisademandfor dehumidification,thefur-  
nace blower motor BLWM will continue running at low--  
cool speed (same speed as LO HEAT).  
b. High cooling --When the R--to--G--and--Y/Y2 circuit is  
closedandthereisademandfor dehumidification,thefur-  
nace blower motor BLWM will drop the blower speed  
from COOL to HI HEAT for a maximum of 10 minutes  
before reverting back to COOL speed. If there is still a  
demand for dehumidification after 20 minutes, the fur-  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
nace control CPU will drop the blower speed back to HI  
HEAT speed. This alternating 10--minute cycle will con-  
tinue as long as there is a call for cooling.  
NOTE: If the blower--off delay is set to the maximum, the  
adjustable continuous--fan feature is locked (i.e., fan speed cannot  
be changed from its current setting).  
c. Cooling off--delay -- When the “call for cooling” is satis-  
fied and there is a demand for dehumidification, the cool-  
ing blower--off delay is decreased from 90 seconds to 5  
seconds.  
6. Heat Pump  
(See Fig. 27 through 30 for thermostat connections)  
When installed with a heat pump, the furnace control auto-  
matically changes the timing sequence to avoid long  
blower off times during demand defrost cycles. When the  
R--to-- W/W1--and--Y1 or R--to--W/W1--and--Y1--and--G  
circuits are energized the furnace control CPU will switch  
to or turn on the blower motor BLWM at low--cool speed  
(same speed as LO HEAT), and begin a low--heat cycle.  
The blower motor BLWM will remain on until the end of  
the prepurge period, then shut off for 24 seconds then  
come back on at LO HEAT speed. When the W/W1 input  
signal disappears, the furnace control begins a normal in-  
ducer post--purge period and the blower remains running  
at LO HEAT speed. If the R--to-- W/W1--and--Y1--and--G  
signals disappear at the same time, the blower motor  
BLWM will remain on for the selected blower-- OFF delay  
period. If the R--to--W/W1--and--Y1 signals disappear,  
leaving the G signal, the blower motor BLWM will remain  
on for the selected blower--OFF delay period then switch  
to continuous--blower speed.  
When the R--to--W/W1--and--Y/Y2, R--to--W/W1--and--  
Y / Y 2 -- a n d -- G , R -- t o -- W / W 1 -- a n d -- Y 1 -- a n d -- Y / Y 2 , o r  
R--to--W/W1--and-- Y1--and--Y/Y2--and--G circuits are en-  
ergized the furnace control CPU will switch to or turn on  
the blower motor BLWM at COOL speed, and begin a  
high--heat cycle. The blower motor BLWM will remain on  
until the end of the prepurge period, then shut off for 24  
seconds then come back on at HI HEAT speed. When the  
W/W1 input signal disappears, the furnace control begins  
a normal inducer post--purge period and the  
5. Continuous Blower Mode  
When the R--to--G circuit is closed by the thermostat, the  
blower motor BLWM will operate on continuous--blower  
speed (can be set to LO HEAT, HI HEAT, or COOL  
speed). Factory default is LO HEAT speed. Terminal  
EAC--1 is energized as long as the blower motor BLWM is  
energized. During a call for heat, the blower BLWM will  
stop during igniter warm--up (17 seconds), ignition (7  
seconds), and blower--ON delay (45 seconds in low--heat,  
and 25 seconds in high--heat), allowing the furnace heat  
exchangers to heat up more quickly, then restarts at the  
end of the blower--ON delay period at LO HEAT or HI  
HEAT speed respectively. The blower motor BLWM will  
revert to continuous--blower speed after the heating cycle  
is completed. In high--heat, the furnace control CPU will  
hold the blower motor BLWM at HI HEAT speed during  
the selected blower--OFF delay period before reverting to  
continuous--blower speed.  
When the thermostat “calls for low--cooling”, the blower  
motor BLWM will switch to operate at low--cool speed  
(same speed as LO HEAT). When the thermostat is satis-  
fied, the blower motor BLWM will operate an additional  
90 seconds on low--cool speed before reverting back to  
continuous--blower speed.  
When the thermostat “calls for high--cooling”, the blower  
motor BLWM will operate at COOL speed. When the  
thermostat is satisfied, the blower motor BLWM will oper-  
ate an additional 90 seconds on COOL speed before re-  
verting back to continuous--blower speed.  
blower switches to COOL speed after a 3 second delay. If  
t h e R -- t o -- W / W 1 -- a n d -- Y / Y 2 -- a n d -- G o r R -- t o -- W / W 1 -- a n d  
--Y1--and-- Y/Y2--and--G signals disappear at the same  
time, the blower motor BLWM will remain on for the se-  
lected blower--OFF delay period. If the R--to--W/W1--  
a n d -- Y / Y 2 o r R -- t o -- W / W 1 -- a n d -- Y 1 -- a n d -- Y / Y 2 s i g n a l s  
disappear, leaving the G signal, the blower motor BLWM  
will remain on for the selected blower-- OFF delay period  
then switch to continuous--blower speed.  
When the R--to--G circuit is opened, the blower motor  
BLWM will continue operating for an additional 5  
seconds, if no other function requires blower motor  
BLWM operation.  
Continuous Blower Speed Selection from Thermostat  
To select different continuous--blower speeds from the  
room thermostat, momentarily turn off the FAN switch or  
push button on the room thermostat for 1--3 seconds after  
the blower motor BLWM is operating. The furnace control  
CPU will shift the continuous--blower speed from the fact-  
ory setting of LO HEAT to HI HEAT speed. Momentarily  
turning off the FAN switch again at the thermostat will  
shift the continuous--blower speed from HI HEAT to  
COOL. Repeating the procedure will shift the continuous--  
blower speed from COOL to LO HEAT speed. The selec-  
tion can be changed as many times as desired and is stored  
in the memory to be automatically used following a power  
interruption.  
Step 4 — Wiring Diagrams  
Refer to wiring diagram, Fig. 57.  
Step 5 — Troubleshooting  
Refer to the service label. (See Fig. 56—Service Label.) The  
Troubleshooting Guide can be a useful tool in isolating furnace  
operation problems. Beginning with the word “Start,” answer  
each question and follow the appropriate arrow to the next item.  
The Guide will help to identify the problem or failed component.  
After replacing any component, verify correct operation  
sequence.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A02107A  
Fig. 61 -- Troubleshooting Guide -- 2--Speed  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A05001  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Printed in U.S.A.  
Edition Date: 11/08  
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231  
Catalog No:58CT---10SI  
Replaces:58CT--9SI  
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Black Decker Convection Oven CTO4400B 01G User Manual
Black Decker Microwave Oven MZ2300P User Manual
Bogen Power Supply PRS 624DA User Manual
Bosch Appliances Ventilation Hood DUH30252UC User Manual
Broan Ventilation Hood 683L User Manual
Cables to Go Network Card 1000TA TPC User Manual
Califone MP3 Player 2395IR User Manual
Cambridge Audio MP3 Docking Station iPod Docking System User Manual
Casio Watch 1949 User Manual
C Crane Humidifier EE 5201A User Manual