50TCA04---A07
Nominal 3 to 6 Tons
With Puron® (R410A) Refrigerant
Service and Maintenance Instructions
TABLE OF CONTENTS
SAFETY CONSIDERATIONS
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . 1
UNIT ARRANGEMENT AND ACCESS . . . . . . . . . . . 2
SUPPLY FAN (BLOWER) SECTION . . . . . . . . . . . . . . 3
COOLING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
PURONR (R-410A) REFRIGERANT . . . . . . . . . . . . . . 7
COOLING CHARGING CHARTS . . . . . . . . . . . . . . . . . 9
CONVENIENCE OUTLETS . . . . . . . . . . . . . . . . . . . . 13
SMOKE DETECTORS . . . . . . . . . . . . . . . . . . . . . . . . . 13
DETECTOR CLEANING . . . . . . . . . . . . . . . . . . . . . . . 18
INDICATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . 20
PROTECTIVE DEVICES . . . . . . . . . . . . . . . . . . . . . . . 20
ELECTRIC HEATERS . . . . . . . . . . . . . . . . . . . . . . . . . 21
PREMIERLINKT CONTROL . . . . . . . . . . . . . . . . . . . 23
ECONOMIZER SYSTEMS . . . . . . . . . . . . . . . . . . . . . 32
FASTENER TORQUE VALUES . . . . . . . . . . . . . . . . . 50
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . 50
APPENDIX I. MODEL NUMBER SIGNIFICANCE . 52
APPENDIX II. PHYSICAL DATA . . . . . . . . . . . . . . . . 53
APPENDIX III. FAN PERFORMANCE . . . . . . . . . . . 54
APPENDIX IV. ELECTRICAL DATA . . . . . . . . . . . . . 63
APPENDIX V. WIRING DIAGRAM LIST . . . . . . . . . 69
Installation and servicing of air-conditioning equipment
can be hazardous due to system pressure and electrical
components. Only trained and qualified service personnel
should install, repair, or service air-conditioning
equipment. Untrained personnel can perform the basic
maintenance functions of replacing filters. Trained service
personnel should perform all other operations.
When working on air-conditioning equipment, observe
precautions in the literature, tags and labels attached to
the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for unbrazing operations.
Have fire extinguishers available for all brazing
operations.
Follow all safety codes. Wear safety glasses and work
gloves. Use quenching cloth for brazing operations. Have
fire extinguisher available. Read these instructions
thoroughly and follow all warnings or cautions attached to
the unit. Consult local building codes and National
Electrical Code (NEC) for special requirements.
Recognize safety information. This is the safety-alert
symbol
. When you see this symbol on the unit and in
instructions or manuals, be alert to the potential for
personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety-alert
symbol. DANGER identifies the most serious hazards
which will result in severe personal injury or death.
WARNING signifies a hazard which could result in
personal injury or death. CAUTION is used to identify
unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced
installation, reliability, or operation.
APPENDIX VI. MOTORMASTER SENSOR
LOCATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70
UNIT START-UP CHECKLIST . . . . . . . . . . . . . . . . . . 73
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit. Electrical
shock and rotating equipment could cause injury.
Download from Www.Somanuals.com. All Manuals Search And Download.
located on the rear side of the unit, above the
evaporator/return air access panel. (See Fig. 1.)
To remove the filters:
1. Grasp the bottom flange of the upper panel.
2. Lift up and swing the bottom out until the panel dis-
engages and pulls out.
3. Reach inside and extract the filters from the filter
rack.
4. Replace these filters as required with similar replace-
ment filters of same size.
To re-install the access panel:
C07156
1. Slide the top of the panel up under the unit top panel.
2. Slide the bottom into the side channels.
Fig. 4 - Screens Installed on Outdoor-Air Hood
(Sizes 7-1/2 to 12-1/2 Tons Shown)
3. Push the bottom flange down until it contacts the top
of the lower panel (or economizer top).
IMPORTANT: DO NOT OPERATE THE UNIT
To remove the screen, loosen the screws in the top retainer
and slip the retainer up until the filter can be removed.
Re-install by placing the frame in its track, rotating the
retainer back down and tighten all screws.
WITHOUT THESE FILTERS!
Outside Air Hood
Outside air hood inlet screens are permanent
aluminum-mesh type filters. Check these for cleanliness.
Remove the screens when cleaning is required. Clean by
washing with hot low-pressure water and soft detergent
and replace all screens before restarting the unit. Observe
the flow direction arrows on the side of each filter frame.
Economizer Inlet Air Screen
This air screen is retained by spring clips under the top
edge of the hood. (See Fig. 3.)
17 1/4”
C07087
Fig. 5 - Belt Drive Motor Mounting
SUPPLY FAN (BLOWER) SECTION
DIVIDER
!
WARNING
OUTSIDE
AIR
ELECTRICAL SHOCK HAZARD
HOOD
Failure to follow this warning could cause personal
injury or death.
CLEANABLE
ALUMINUM
FILTER
FILTER
Before performing service or maintenance operations
on the fan system, shut off all unit power and tag-out
the unit disconnect switch. Do not reach into the fan
section with power still applied to unit.
BAROMETRIC
RELIEF
FILTER
CLIP
C06027
Supply Fan (Belt--Drive)
Fig. 3 - Filter Installation
The supply fan system consists of a forward-curved
centrifugal blower wheel on a solid shaft with two
concentric type bearings, one on each side of the blower
housing. A fixed-pitch driven pulley is attached to the fan
shaft and an adjustable-pitch driver pulley is on the
motor. The pulleys are connected using a “V” type belt.
(See Fig. 5.)
To remove the filter, open the spring clips. Re-install the
filter by placing the frame in its track, then closing the
spring clips.
Manual Outside Air Hood Screen
This inlet screen is secured by a retainer angle across the
top edge of the hood. (See Fig. 4.)
Belt
Check the belt condition and tension quarterly. Inspect the
belt for signs of cracking, fraying or glazing along the
3
Download from Www.Somanuals.com. All Manuals Search And Download.
inside surfaces. Check belt tension by using a spring-force
tool (such as Browning’s Part Number “Belt Tension
Checker” or equivalent tool); tension should be 6-lbs at a
5/8-in. deflection when measured at the centerline of the
belt span. This point is at the center of the belt when
measuring the distance between the motor shaft and the
blower shaft.
To change fan speed:
1. Shut off unit power supply.
2. Loosen belt by loosening fan motor mounting nuts.
(See Fig. 5.)
3. Loosen movable pulley flange setscrew. (See Fig. 6.)
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified.
5. Set movable flange at nearest keyway of pulley hub
and tighten setscrew to torque specifications.
NOTE: Without the spring-tension tool, place a straight
edge across the belt surface at the pulleys, then deflect the
belt at mid-span using one finger to a 1/2-in. deflection.
Adjust belt tension by loosening the motor mounting plate
front bolts and rear bolt and sliding the plate toward the
fan (to reduce tension) or away from fan (to increase
tension). Ensure the blower shaft and the motor shaft are
parallel to each other (pulleys aligned). Tighten all bolts
when finished.
To align fan and motor pulleys:
1. Loosen fan pulley setscrews.
2. Slide fan pulley along fan shaft. Make angular align-
ment by loosening motor from mounting.
3. Tighten fan pulley setscrews and motor mounting
bolts to torque specifications.
4. Recheck belt tension.
To replace the belt:
1. Use a belt with same section type or similar size. Do
not substitute a “FHP” type belt. When installing the
new belt, do not use a tool (screwdriver or pry-bar) to
force the belt over the pulley flanges, this will stress
the belt and cause a reduction in belt life.
2. Loosen the motor mounting plate front bolts and rear
bolts.
3. Push the motor and its mounting plate towards the
blower housing as close as possible to reduce the cen-
ter distance between fan shaft and motor shaft.
4. Remove the belt by gently lifting the old belt over
one of the pulleys.
5. Install the new belt by gently sliding the belt over
both pulleys and then sliding the motor and plate
away from the fan housing until proper tension is
achieved.
C07075
Fig. 6 - Supply-Fan Pulley Adjustment
6. Check the alignment of the pulleys, adjust if neces-
sary.
Bearings
7. Tighten all bolts.
8. Check the tension after a few hours of runtime and
re-adjust as required.
This fan system uses bearings featuring concentric split
locking collars. The collars are tightened through a cap
screw bridging the split portion of the collar. The cap
screw has a Torx T25 socket head. To tighten the locking
collar: Hold the locking collar tightly against the inner
race of the bearing and torque the cap screw to 65-70
in-lb (7.4-7.9 Nm). See Fig. 7.
Adjustable-Pitch Pulley on Motor
The motor pulley is an adjustable-pitch type that allows a
servicer to implement changes in the fan wheel speed to
match as-installed ductwork systems. The pulley consists
of a fixed flange side that faces the motor (secured to the
motor shaft) and a movable flange side that can be rotated
around the fixed flange side that increases or reduces the
pitch diameter of this driver pulley. (See Fig. 6.)
As the pitch diameter is changed by adjusting the position
of the movable flange, the centerline on this pulley shifts
laterally (along the motor shaft). This creates
a
requirement for a realignment of the pulleys after any
adjustment of the movable flange. Also reset the belt
tension after each realignment.
Check the condition of the motor pulley for signs of wear.
Glazing of the belt contact surfaces and erosion on these
surfaces are signs of improper belt tension and/or belt
slippage. Pulley replacement may be necessary.
C08121
Fig. 7 - Tightening Locking Collar
4
Download from Www.Somanuals.com. All Manuals Search And Download.
Motor
life of the coil and extend the life of the unit. The
following maintenance and cleaning procedures are
recommended as part of the routine maintenance activities
to extend the life of the coil.
When replacing the motor, also replace the external-tooth
lock washer (star washer) under the motor mounting base;
this is part of the motor grounding system. Ensure the
teeth on the lock washer are in contact with the motor’s
painted base. Tighten motor mounting bolts to 120 +/- 12
in-lbs.
Remove Surface Loaded Fibers
Surface loaded fibers or dirt should be removed with a
vacuum cleaner. If a vacuum cleaner is not available, a
soft non-metallic bristle brush may be used. In either
case, the tool should be applied in the direction of the fins.
Coil surfaces can be easily damaged (fin edges can be
easily bent over and damage to the coating of a protected
coil) if the tool is applied across the fins.
Changing fan wheel speed by changing pulleys: The
horsepower rating of the belt is primarily dictated by the
pitch diameter of the smaller pulley in the drive system
(typically the motor pulley in these units). Do not install a
replacement motor pulley with a smaller pitch diameter
than provided on the original factory pulley. Change fan
wheel speed by changing the fan pulley (larger pitch
diameter to reduce wheel speed, smaller pitch diameter to
increase wheel speed) or select a new system (both
pulleys and matching belt(s)).
NOTE: Use of a water stream, such as a garden hose,
against a surface loaded coil will drive the fibers and dirt
into the coil. This will make cleaning efforts more
difficult. Surface loaded fibers must be completely
removed prior to using low velocity clean water rinse.
Before changing pulleys to increase fan wheel speed,
check the fan performance at the target speed and airflow
rate to determine new motor loading (bhp). Use the fan
performance tables or use the Packaged Rooftop Builder
software program. Confirm that the motor in this unit is
capable of operating at the new operating condition. Fan
shaft loading increases dramatically as wheel speed is
increased.
Periodic Clean Water Rinse
A periodic clean water rinse is very beneficial for coils
that are applied in coastal or industrial environments.
However, it is very important that the water rinse is made
with a very low velocity water stream to avoid damaging
the fin edges. Monthly cleaning as described below is
recommended.
Routine Cleaning of Coil Surfaces
To reduce vibration, replace the motor’s adjustable pitch
pulley with a fixed pitch pulley (after the final airflow
balance adjustment). This will reduce the amount of
vibration generated by the motor/belt-drive system.
Periodic cleaning with TotalineR environmentally sound
coil cleaner is essential to extend the life of coils. This
cleaner is available from Carrier Replacement
Components Division as part number P902-0301 for a one
gallon container, and part number P902-0305 for a 5
gallon container. It is recommended that all coils,
including standard aluminum, pre-coated, copper/copper
or E-coated coils be cleaned with the Totaline
environmentally sound coil cleaner as described below.
Coil cleaning should be part of the unit’s regularly
scheduled maintenance procedures to ensure long life of
the coil. Failure to clean the coils may result in reduced
durability in the environment.
COOLING
!
WARNING
UNIT OPERATION AND SAFETY HAZARD
Failure to follow this warning could cause personal
injury, death and/or equipment damage.
This system uses PuronR refrigerant which has
higher pressures than R-22 and other refrigerants. No
other refrigerant may be used in this system. Gauge
set, hoses, and recovery system must be designed to
handle Puron refrigerant. If unsure about equipment,
consult the equipment manufacturer.
Avoid use of:
S coil brighteners
S acid cleaning prior to painting
S high pressure washers
S poor quality water for cleaning
Condenser Coil
The condenser coil is fabricated with round tube copper
hairpins and plate fins of various materials and/or coatings
(see Model Number Format in the Appendix to identify
the materials provided in this unit). The coil may be
one-row or composite-type two-row. Composite two-row
coils are two single-row coils fabricated with a single
return bend end tubesheet.
Totaline environmentally sound coil cleaner is
nonflammable, hypo allergenic, non bacterial, and a
USDA accepted biodegradable agent that will not harm
the coil or surrounding components such as electrical
wiring, painted metal surfaces, or insulation. Use of
non-recommended coil cleaners is strongly discouraged
since coil and unit durability could be affected.
Condenser Coil Maintenance and Cleaning
Recommendation
One-Row Coil
Wash coil with commercial coil cleaner. It is not
necessary to remove top panel.
Routine cleaning of coil surfaces is essential to maintain
proper operation of the unit. Elimination of contamination
and removal of harmful residues will greatly increase the
5
Download from Www.Somanuals.com. All Manuals Search And Download.
Two-Row Coils
6. Use a water hose or other suitable equipment to flush
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in
the normal manner.
Clean coil as follows:
1. Turn off unit power, tag disconnect.
2. Remove top panel screws on condenser end of unit.
7. Secure inner and outer coil rows together with a
field-supplied fastener.
8. Reposition the outer coil section and remove the coil
corner post from between the top panel and center
post. Reinstall the coil corner post and replace all
screws.
3. Remove condenser coil corner post. See Fig. 8. To
hold top panel open, place coil corner post between
top panel and center post. See Fig. 9.
Totaline Environmentally Sound Coil Cleaner
Application Equipment
S 2-1/2 gallon garden sprayer
S Water rinse with low velocity spray nozzle
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in accelerated
corrosion of unit parts.
C08205
Fig. 8 - Cleaning Condenser Coil
Harsh chemicals, household bleach or acid or basic
cleaners should not be used to clean outdoor or indoor
coils of any kind. These cleaners can be very difficult
to rinse out of the coil and can accelerate corrosion at
the fin/tube interface where dissimilar materials are in
contact. If there is dirt below the surface of the coil,
use the Totaline environmentally sound coil cleaner.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in reduced
unit performance or unit shutdown.
C08206
Fig. 9 - Propping Up Top Panel
High velocity water from a pressure washer, garden
hose, or compressed air should never be used to
clean a coil. The force of the water or air jet will
bend the fin edges and increase airside pressure drop.
4. Remove screws securing coil to compressor plate and
compressor access panel.
5. Remove fastener holding coil sections together at re-
turn end of condenser coil. Carefully separate the out-
er coil section 3 to 4 in. from the inner coil section.
See Fig. 10.
Totaline Environmentally Sound Coil Cleaner
Application Instructions
1. Proper eye protection such as safety glasses is recom-
mended during mixing and application.
2. Remove all surface loaded fibers and dirt with a vacu-
um
cleaner as described above.
3. Thoroughly wet finned surfaces with clean water and
a low velocity garden hose, being careful not to bend
fins.
4. Mix Totaline environmentally sound coil cleaner in a
2-1/2 gallon garden sprayer according to the instruc-
tions included with the cleaner. The optimum solution
temperature is 100_F.
NOTE: Do NOT USE water in excess of 130_F, as the
enzymatic activity will be destroyed.
C08207
Fig. 10 - Separating Coil Sections
5. Thoroughly apply Totaline environmentally sound
coil cleaner solution to all coil surfaces including
finned area, tube sheets and coil headers.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
6. Hold garden sprayer nozzle close to finned areas and
apply cleaner with a vertical, up-and-down motion.
Avoid spraying in horizontal pattern to minimize po-
tential for fin damage.
7. Ensure cleaner thoroughly penetrates deep into finned
areas.
8. Interior and exterior finned areas must be thoroughly
cleaned.
9. Finned surfaces should remain wet with cleaning
solution for 10 minutes.
10. Ensure surfaces are not allowed to dry before rinsing.
Reapplying cleaner as needed to ensure 10-minute
saturation is achieved.
11. Thoroughly rinse all surfaces with low velocity clean
water using downward rinsing motion of water spray
nozzle. Protect fins from damage from the spray
nozzle.
The brass fittings are two-piece High Flow valves, with a
receptacle base brazed to the tubing and an integral
spring-closed check valve core screwed into the base.
(See Fig. 11.) This check valve is permanently assembled
into this core body and cannot be serviced separately;
replace the entire core body if necessary. Service tools are
available from RCD that allow the replacement of the
check valve core without having to recover the entire
system refrigerant charge. Apply compressor refrigerant
oil to the check valve core’s bottom o-ring. Install the
fitting body with 96 +/ -10 in-lbs of torque; do not
overtighten.
PURONR (R--410A) REFRIGERANT
This unit is designed for use with Puron (R-410A)
refrigerant. Do not use any other refrigerant in this
system.
Evaporator Coil
Puron (R-410A) is provided in pink (rose) colored
cylinders. These cylinders are available with and without
dip tubes; cylinders with dip tubes will have a label
indicating this feature. For a cylinder with a dip tube,
place the cylinder in the upright position (access valve at
the top) when removing liquid refrigerant for charging.
For a cylinder without a dip tube, invert the cylinder
(access valve on the bottom) when removing liquid
refrigerant.
Cleaning the Evaporator Coil
1. Turn unit power off. Install lockout tag. Remove
evaporator coil access panel.
2. If economizer or two-position damper is installed, re-
move economizer by disconnecting Molex plug and
removing mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dish-
washer detergent in a pressurized spray canister. Wash
both sides of coil and flush with clean water. For best
results, back-flush toward return-air section to re-
move foreign material. Flush condensate pan after
completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
Because Puron (R-410A) is a blend, it is strongly
recommended that refrigerant always be removed from
the cylinder as a liquid. Admit liquid refrigerant into the
system in the discharge line. If adding refrigerant into the
suction line, use a commercial metering/expansion device
at the gauge manifold; remove liquid from the cylinder,
pass it through the metering device at the gauge set and
then pass it into the suction line as a vapor. Do not remove
Puron (R-410A) from the cylinder as a vapor.
Evaporator Coil Metering Devices
Refrigerant Charge
The metering devices are multiple fixed-bore devices
(Acutrolt) wedged into the horizontal outlet tubes from
the liquid header, located at the entrance to each
evaporator coil circuit path. These are non-adjustable.
Service requires replacing the entire liquid header
assembly.
Amount of refrigerant charge is listed on the unit’s
nameplate. Refer to Carrier GTAC2-5 Charging,
Recovery, Recycling and Reclamation training manual
and the following procedures.
Unit panels must be in place when unit is operating during
the charging procedure.
To check for possible blockage of one or more of these
metering devices, disconnect the supply fan contactor
(IFC) coil, then start the compressor and observe the
frosting pattern on the face of the evaporator coil. A frost
pattern should develop uniformly across the face of the
coil starting at each horizontal header tube. Failure to
develop frost at an outlet tube can indicate a plugged or a
missing orifice.
No Charge
Use standard evacuating techniques. After evacuating
system, weigh in the specified amount of refrigerant.
Low-Charge Cooling
Using Cooling Charging Charts, Fig. 12, vary refrigerant
until the conditions of the appropriate chart are met. Note
the charging charts are different from type normally used.
Charts are based on charging the units to the correct
superheat for the various operating conditions. Accurate
pressure gauge and temperature sensing device are
required. Connect the pressure gauge to the service port
on the suction line. Mount the temperature sensing device
on the suction line and insulate it so that outdoor ambient
temperature does not affect the reading. Indoor-air cfm
must be within the normal operating range of the unit.
Refrigerant System Pressure Access Ports
There are two access ports in the system - on the suction
tube near the compressor and on the discharge tube near
the compressor. These are brass fittings with black plastic
caps. The hose connection fittings are standard 1/4 SAE
Male Flare couplings.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
To Use Cooling Charging Charts
EXAMPLE:
Model 50TC*A06
Take the outdoor ambient temperature and read the
suction pressure gauge. Refer to chart to determine what
suction temperature should be. If suction temperature is
high, add refrigerant. If suction temperature is low,
carefully recover some of the charge. Recheck the suction
pressure as charge is adjusted.
Outdoor Temperature . . . . . . . . . . . . . . . . . . 85_F (29_C)
Suction Pressure . . . . . . . . . . . . . . . . . 130 psig (896 kPa)
Suction Temperature should be . . . . . . . . . 63_F (17.2_C)
1/2-20 UNF RH
0.596
45o
30o
DEPRESSOR PER ARI 720
+.01/-.035
FROM FACE OF BODY
WASHER
O-RING
1/2" HEX
.47
5/8” HEX
7/16-20 UNF RH
This surface provides a metal to metal seal when
torqued into the seat. Appropriate handling is
required to not scratch or dent the surface.
SEAT
CORE
C07150
Fig. 11 - CoreMax Access Port Assembly
8
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING CHARGING CHARTS
C08203
C08204
Fig. 12 - Cooling Charging Charts
9
Download from Www.Somanuals.com. All Manuals Search And Download.
COOLING CHARGING CHARTS (cont)
C08228
C08229
Fig. 12 - Cooling Charging Charts (cont.)
10
Download from Www.Somanuals.com. All Manuals Search And Download.
The suction and discharge pressure levels should now
move to their normal start-up levels.
Compressor
Lubrication
NOTE: When the compressor is rotating in the wrong
direction, the unit makes an elevated level of noise and
does not provide cooling.
The compressor is charged with the correct amount of oil
at the factory.
Filter Drier
!
CAUTION
Replace whenever refrigerant system is exposed to
atmosphere. Only use factory specified liquid-line filter
driers with working pressures no less than 650 psig. Do
not install a suction-line filter drier in liquid line. A
liquid-line filter drier designed for use with Puron
refrigerant is required on every unit.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to
components.
The compressor is in a PuronR refrigerant system and
uses a polyolester (POE) oil. This oil is extremely
hygroscopic, meaning it absorbs water readily. POE
oils can absorb 15 times as much water as other oils
designed for HCFC and CFC refrigerants. Avoid
exposure of the oil to the atmosphere.
Condenser--Fan Location
See Fig. 13.
1. Shut off unit power supply. Install lockout tag.
2. Remove condenser-fan assembly (grille, motor, and
fan).
Replacing Compressor
3. Loosen fan hub setscrews.
4. Adjust fan height as shown in Fig. 13.
5. Tighten setscrews.
The compressor used with Puron refrigerant contains a
POE oil. This oil has a high affinity for moisture. Do not
remove the compressor’s tube plugs until ready to insert
the unit suction and discharge tube ends.
6. Replace condenser-fan assembly.
Compressor mounting bolt torque is 65-75 ft-lbs.
Compressor Rotation
On 3-phase units with scroll compressors, it is important
to be certain compressor is rotating in the proper
direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect service gauges to suction and discharge pres-
sure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
NOTE: If the suction pressure does not drop and the
discharge pressure does not rise to normal levels:
4. Note that the evaporator fan is probably also rotating
in the wrong direction.
5. Turn off power to the unit.
C07091
Fig. 13 - Condenser Fan Adjustment
(except with Motormaster)
6. Reverse any two of the unit power leads.
7. Reapply power to the compressor.
Troubleshooting Cooling System
Refer to Table 1 for additional troubleshooting topics.
11
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 1 – Cooling Service Analysis
PROBLEM
CAUSE
REMEDY
Power failure.
Fuse blown or circuit breaker tripped.
Call power company.
Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer,
or control relay.
Insufficient line voltage.
Incorrect or faulty wiring.
Thermostat setting too high.
Replace component.
Compressor and Condenser
Fan Will Not Start.
Determine cause and correct.
Check wiring diagram and rewire correctly.
Lower thermostat setting below room temperature.
Faulty wiring or loose connections in compres-
sor circuit.
Compressor motor burned out, seized, or
internal overload open.
Defective run/start capacitor, overload, start
relay.
Check wiring and repair or replace.
Determine cause. Replace compressor.
Determine cause and replace.
Compressor Will Not Start But
Condenser Fan Runs.
Replace fuse or reset circuit breaker. Determine
cause.
Recover refrigerant, evacuate system, and recharge
to nameplate.
One leg of three---phase power dead.
Refrigerant overcharge or undercharge.
Defective compressor.
Insufficient line voltage.
Blocked condenser.
Defective run/start capacitor, overload, or start
relay.
Replace and determine cause.
Determine cause and correct.
Determine cause and correct.
Compressor Cycles (other
than normally satisfying ther-
mostat).
Determine cause and replace.
Defective thermostat.
Replace thermostat.
Faulty condenser---fan motor or capacitor.
Restriction in refrigerant system.
Dirty air filter.
Replace.
Locate restriction and remove.
Replace filter.
Unit undersized for load.
Thermostat set too low.
Low refrigerant charge.
Leaking valves in compressor.
Air in system.
Decrease load or increase unit size.
Reset thermostat.
Locate leak; repair and recharge.
Replace compressor.
Recover refrigerant, evacuate system, and recharge.
Clean coil or remove restriction.
Replace filter.
Compressor Operates
Continuously.
Condenser coil dirty or restricted.
Dirty air filter.
Dirty condenser coil.
Clean coil.
Refrigerant overcharged.
Air in system.
Recover excess refrigerant.
Recover refrigerant, evacuate system, and recharge.
Determine cause and correct.
Check for leaks; repair and recharge.
Replace compressor.
Remove restriction.
Check for source and eliminate.
Replace compressor.
Excessive Head Pressure.
Condenser air restricted or air short---cycling.
Low refrigerant charge.
Compressor valves leaking.
Restriction in liquid tube.
High head load.
Compressor valves leaking.
Refrigerant overcharged.
Dirty air filter.
Head Pressure Too Low.
Excessive Suction Pressure.
Recover excess refrigerant.
Replace filter.
Low refrigerant charge.
Metering device or low side restricted.
Check for leaks; repair and recharge.
Remove source of restriction.
Suction Pressure Too Low.
Increase air quantity. Check filter and replace if
necessary.
Insufficient evaporator airflow.
Temperature too low in conditioned area.
Reset thermostat.
Outdoor ambient below 25˚F.
Install low---ambient kit.
Evaporator Fan Will Not Shut
Off.
Time off delay not finished.
Wa it f o r 3 0 --- se co n d o f f d e la y.
Compressor Makes Excessive
Noise.
Compressor rotating in wrong direction.
Reverse the 3---phase power leads.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
or HACR switch is open. Other connection methods will
result in the convenience outlet circuit being de-energized
when the unit disconnect or HACR switch is open. See
Fig. 15.
CONVENIENCE OUTLETS
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
Units with convenience outlet circuits may use
multiple disconnects. Check convenience outlet for
power status before opening unit for service. Locate
its disconnect switch, if appropriate, and open it.
Tag-out this switch, if necessary.
Two types of convenience outlets are offered on 50TC
models: Non-powered and unit-powered. Both types
provide
a
125-volt
GFCI
(ground-fault
circuit-interrupter) duplex receptacle rated at 15-A
behind a hinged waterproof access cover, located on the
end panel of the unit. See Fig. 14.
Pwd-CO Transformer
CO8283
Conv Outlet
GFCI
Fig. 15 - Powered Convenience Outlet Wiring
Duty Cycle: The unit-powered convenience outlet has a
duty cycle limitation. The transformer is intended to
provide power on an intermittent basis for service tools,
lamps, etc; it is not intended to provide 15-amps loading
for continuous duty loads (such as electric heaters for
overnight use). Observe a 50% limit on circuit loading
above 8-amps (i.e., limit loads exceeding 8-amps to 30
minutes of operation every hour).
Pwd-CO
Fuse
Switch
Maintenance: Periodically test the GFCI receptacle by
pressing the TEST button on the face of the receptacle.
This should cause the internal circuit of the receptacle to
trip and open the receptacle. Check for proper grounding
wires and power line phasing if the GFCI receptacle does
not trip as required. Press the RESET button to clear the
tripped condition.
C08128
Fig. 14 - Convenience Outlet Location
Non-powered type: This type requires the field
installation of a general-purpose 125-volt 15-A circuit
powered from a source elsewhere in the building. Observe
national and local codes when selecting wire size, fuse or
breaker requirements and disconnect switch size and
location. Route 125-v power supply conductors into the
bottom of the utility box containing the duplex receptacle.
Fuse on powered type: The factory fuse is a Bussman
“Fusetron” T-15, non-renewable screw-in (Edison base)
type plug fuse.
Using unit-mounted convenience outlets: Units with
unit-mounted convenience outlet circuits will often
require that two disconnects be opened to de-energize all
power to the unit. Treat all units as electrically energized
until the convenience outlet power is also checked and
de-energization is confirmed. Observe National Electrical
Code Article 210, Branch Circuits, for use of convenience
outlets.
Unit-powered type: A unit-mounted transformer is
factory-installed to stepdown the main power supply
voltage to the unit to 115-v at the duplex receptacle. This
option also includes a manual switch with fuse, located in
a utility box and mounted on a bracket behind the
convenience outlet; access is through the unit’s control
box access panel. See Fig. 14.
SMOKE DETECTORS
The primary leads to the convenience outlet transformer
are not factory-connected. Selection of primary power
source is a customer-option. If local codes permit, the
transformer primary leads can be connected at the
Smoke detectors are available as factory-installed options
on 50TC models. Smoke detectors may be specified for
Supply Air only or for Return Air without or with
economizer or in combination of Supply Air and Return
Air. Return Air smoke detectors are arranged for vertical
return configurations only. All components necessary for
line-side terminals on
a
unit-mounted non-fused
disconnect or HACR breaker switch; this will provide
service power to the unit when the unit disconnect switch
13
Download from Www.Somanuals.com. All Manuals Search And Download.
operation are factory-provided and mounted. The unit is
factory-configured for immediate smoke detector
shutdown operation; additional wiring or modifications to
unit terminal board may be necessary to complete the unit
and smoke detector configuration to meet project
requirements.
inspections without having to disassemble the sensor. The
cover attaches to the sensor housing using four captive
screws and forms an airtight chamber around the sensing
electronics. Each sensor includes a harness with an RJ45
terminal for connecting to the controller. Each sensor has
four LEDs (for Power, Trouble, Alarm and Dirty) and a
manual test/reset button (on the left-side of the housing).
System
The smoke detector system consists of a four-wire
controller and one or two sensors. Its primary function is
to shut down the rooftop unit in order to prevent smoke
from circulating throughout the building. It is not to be
used as a life saving device.
Duct smoke sensor
Exhaust tube
Controller
The controller (see Fig. 16) includes a controller housing,
a printed circuit board, and a clear plastic cover. The
controller can be connected to one or two compatible duct
smoke sensors. The clear plastic cover is secured to the
housing with a single captive screw for easy access to the
wiring terminals. The controller has three LEDs (for
Power, Trouble and Alarm) and a manual test/reset button
(on the cover face).
Exhaust gasket
Sensor housing
and electronics
See
Detail A
Intake
gasket
Cover gasket
(ordering option)
TSD-CO2
(ordering option)
Sensor cover
Plug
Sampling tube
(ordered separately)
Coupling
Detail A
Duct smoke sensor
controller
Conduit nuts
(supplied by installer)
Magnetic
test/reset
switch
Conduit support plate
Terminal block cover
Alarm
Trouble
Power
Dirty
Controller housing
and electronics
Cover gasket
(ordering option)
C08209
Controller cover
Conduit couplings
(supplied by installer)
Fig. 17 - Smoke Detector Sensor
Fastener
(2X)
Air is introduced to the duct smoke detector sensor’s
sensing chamber through a sampling tube that extends into
the HVAC duct and is directed back into the ventilation
system through a (shorter) exhaust tube. The difference in
air pressure between the two tubes pulls the sampled air
through the sensing chamber. When a sufficient amount of
smoke is detected in the sensing chamber, the sensor
signals an alarm state and the controller automatically
takes the appropriate action to shut down fans and
blowers, change over air handling systems, notify the fire
alarm control panel, etc.
Trouble
Alarm
Power
Test/reset
switch
C08208
Fig. 16 - Controller Assembly
The sensor uses a process called differential sensing to
prevent gradual environmental changes from triggering
false alarms. A rapid change in environmental conditions,
such as smoke from a fire, causes the sensor to signal an
alarm state but dust and debris accumulated over time
does not.
Sensor
The sensor (see Fig. 17) includes a plastic housing, a
printed circuit board, a clear plastic cover, a sampling
tube inlet and an exhaust tube. The sampling tube (when
used) and exhaust tube are attached during installation.
The sampling tube varies in length depending on the size
of the rooftop unit. The clear plastic cover permits visual
14
Download from Www.Somanuals.com. All Manuals Search And Download.
For installations using two sensors, the duct smoke
detector does not differentiate which sensor signals an
alarm or trouble condition.
Return Air with Economizer — The sampling tube is
inserted through the side plates of the economizer
housing, placing it across the return air opening on the
unit basepan. See Fig. 20. The holes in the sampling tube
face downward, into the return air stream. The sampling
tube is connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat-mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See installation steps
below.)
Smoke Detector Locations
Supply Air — The Supply Air smoke detector sensor is
located to the left of the unit’s indoor (supply) fan. See
Fig. 18. Access is through the fan access panel. There is
no sampling tube used at this location. The sampling tube
inlet extends through the side plate of the fan housing
(into a high pressure area). The controller is located on a
bracket to the right of the return filter, accessed through
the lift-off filter panel.
Smoke Detector Sensor
Return Air
Sampling Tube
C08245
Fig. 18 - Typical Supply Air Smoke Detector Sensor
Location
C08129
Fig. 20 - Return Air Sampling Tube Location
Return Air without Economizer — The sampling tube is
located across the return air opening on the unit basepan.
See Fig. 19. The holes in the sampling tube face
downward, into the return air stream. The sampling tube is
connected via tubing to the return air sensor that is
mounted on a bracket high on the partition between return
filter and controller location. (This sensor is shipped in a
flat-mounting location. Installation requires that this
sensor be relocated to its operating location and the tubing
to the sampling tube be connected. See installation steps
below.)
Completing Installation of Return Air Smoke
Sensor:
Screws
Flexible
Exhaust Tubes
Return Air Detector module
(shipping position shown)*
Sample Tube
Controller module
C08126
Fig. 21 - Return Air Detector Shipping Position
1. Unscrew the two screws holding the Return Air
Sensor detector plate. See Fig 21. Save the screws.
2. Remove the Return Air Sensor and its detector plate.
3. Rotate the detector plate so the sensor is facing out-
wards and the sampling tube connection is on the bot-
tom. See Fig 22.
4. Screw the sensor and detector plate into its operating
position using screws from Step 1. Make sure the
sampling tube connection is on the bottom and the ex-
haust tube is on the top. See Fig 22.
5. Connect the flexible tube on the sampling inlet to the
sampling tube on the basepan.
Return Air Detector Sampling Tube
*RA detector must be moved from shipping position to operating position by installer
C07307
Fig. 19 - Typical Return Air Detector Location
15
Download from Www.Somanuals.com. All Manuals Search And Download.
6. For units with an economizer, the sampling tube is in-
tegrated into the economizer housing but the connec-
tion of the flexible tubing to the sampling tube is the
same.
Highlight B: Smoke detector NC contact set will open on
smoke alarm condition, de-energizing the ORN
conductor.
Highlight C: 24-v power signal via ORN lead is removed
at Smoke Detector input on LCTB; all unit operations
cease immediately.
PremierLink Control: Unit operating functions (fan,
cooling and heating) are terminated as described above. In
addition:
Highlight D: On smoke alarm condition, the smoke
detector NO Alarm contact will close, supplying 24-v
power to GRA conductor.
Highlight E: GRA lead at Smoke Alarm input on LCTB
provides 24-v signal. This signal is conveyed to
PremierLink FIOP’s TB1 at terminal TB1-6 (BLU lead).
This signal initiates the FSD sequence by the PremierLink
control.
C08127
Fig. 22 - Return Air Sensor Operating Position
FIOP Smoke Detector Wiring and Response
Using Remote Logic: Five conductors are provided for
field use (see Highlight F) for additional annunciation
functions.
All units: FIOP smoke detector is configured to
automatically shut down all unit operations when smoke
condition is detected. See Fig. 23, Smoke Detector
Wiring.
Additional Application Data — Refer to Catalog No.
HKRNKA-1XA for discussions on additional control
features of these smoke detectors including multiple unit
coordination. See Fig. 23.
Highlight A: JMP 3 is factory-cut, transferring unit
control to smoke detector.
B
D
C
F
E
A
C08246
Fig. 23 - Typical Smoke Detector System Wiring
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Sensor and Controller Tests
Sensor Alarm Test
The sensor alarm test checks a sensor’s ability to signal an
alarm state. This test requires that you use a field provided
SD-MAG test magnet.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
Pressing the controller’s test/reset switch for longer
than seven seconds will put the duct detector into the
alarm state and activate all automatic alarm responses.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
Dirty Controller Test Procedure
1. Press the controller’s test/reset switch for two
seconds.
2. Verify that the controller’s Trouble LED flashes.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system, notify the proper authorities before
performing the test.
Dirty Sensor Test
The dirty sensor test provides an indication of the sensor’s
ability to compensate for gradual environmental changes.
A sensor that can no longer compensate for environmental
changes is considered 100% dirty and requires cleaning or
replacing. You must use a field provided SD-MAG test
magnet to initiate a sensor dirty test. The sensor’s Dirty
LED indicates the results of the dirty test as shown in
Table 2.
Sensor Alarm Test Procedure
1. Hold the test magnet where indicated on the side of
the sensor housing for seven seconds.
2. Verify that the sensor’s Alarm LED turns on.
3. Reset the sensor by holding the test magnet against
the sensor housing for two seconds.
!
4. Verify that the sensor’s Alarm LED turns off.
CAUTION
OPERATIONAL TEST HAZARD
Controller Alarm Test
The controller alarm test checks the controller’s ability to
initiate and indicate an alarm state.
Failure to follow this caution may result in personnel
and authority concern.
Holding the test magnet against the sensor housing for
more than seven seconds will put the duct detector
into the alarm state and activate all automatic alarm
responses.
!
CAUTION
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
Table 2 – Dirty LED Test
FLASHES
DESCRIPTION
0---25% dirty. (Typical of a newly installed detector)
25---50% dirty
This test places the duct detector into the alarm state.
Disconnect all auxiliary equipment from the controller
before performing the test. If the duct detector is
connected to a fire alarm system, notify the proper
authorities before performing the test.
1
2
3
4
51---75% dirty
76---99% dirty
Controller Alarm Test Procedure
Dirty Sensor Test Procedure
1. Press the controller’s test/reset switch for seven
seconds.
1. Hold the test magnet where indicated on the side of
the sensor housing for two seconds.
2. Verify that the controller’s Alarm LED turns on.
2. Verify that the sensor’s Dirty LED flashes.
3. Reset the sensor by pressing the test/reset switch for
two seconds.
4. Verify that the controller’s Alarm LED turns off.
!
CAUTION
OPERATIONAL TEST HAZARD
Dirty Controller Test
The dirty controller test checks the controller’s ability to
initiate a dirty sensor test and indicate its results.
Failure to follow this caution may result in personnel
and authority concern.
Changing the dirty sensor test operation will put the
detector into the alarm state and activate all automatic
alarm responses. Before changing dirty sensor test
operation, disconnect all auxiliary equipment from the
controller and notify the proper authorities if
connected to a fire alarm system.
17
Download from Www.Somanuals.com. All Manuals Search And Download.
Changing the Dirt Sensor Test
By default, sensor dirty test results are indicated by:
S The sensor’s Dirty LED flashing.
12
1
Smoke Detector Controller
TB3
1
S The controller’s Trouble LED flashing.
S The controller’s supervision relay contacts toggle.
−
+
Auxiliary
equipment
2
The operation of a sensor’s dirty test can be changed so
that the controller’s supervision relay is not used to
indicate test results. When two detectors are connected to
a controller, sensor dirty test operation on both sensors
must be configured to operate in the same manner.
3
14
SD-TRK4
Supervision relay
contacts [3]
Trouble
5
13
19
Power
4
18 Vdc (
+)
To Configure the Dirty Sensor Test Operation
1. Hold the test magnet where indicated on the side of
the sensor housing until the sensor’s Alarm LED turns
on and its Dirty LED flashes twice (approximately 60
seconds).
Wire must be
added by installer
Alarm
1
15
2
Reset/Test
3
2. Reset the sensor by removing the test magnet then
holding it against the sensor housing again until the
sensor’s Alarm LED turns off (approximately 2
seconds).
18 Vdc (
−
)
2
20
C08247
Fig. 24 - Remote Test/Reset Station Connections
Remote Station Test
The remote station alarm test checks a test/reset station’s
ability to initiate and indicate an alarm state.
!
CAUTION
OPERATIONAL TEST HAZARD
!
CAUTION
Failure to follow this caution may result in personnel
and authority concern.
OPERATIONAL TEST HAZARD
Failure to follow this caution may result in personnel
and authority concern.
If the test/reset station’s key switch is left in the
RESET/TEST position for longer than seven seconds,
the detector will automatically go into the alarm state
and activate all automatic alarm responses.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary
equipment from the controller before performing the
test. If the duct detector is connected to a fire alarm
system, notify the proper authorities before
performing the test.
!
CAUTION
OPERATIONAL TEST HAZARD
SD-TRK4 Remote Alarm Test Procedure
Failure to follow this caution may result in personnel
and authority concern.
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns
on.
Holding the test magnet to the target area for longer
than seven seconds will put the detector into the alarm
state and activate all automatic alarm responses.
3. Reset the sensor by turning the key switch to the
RESET/TEST position for two seconds.
Dirty Sensor Test Using an SD-TRK4
4. Verify that the test/reset station’s Alarm LED turns
off.
1. Turn the key switch to the RESET/TEST position for
two seconds.
Remote Test/Reset Station Dirty Sensor Test
2. Verify that the test/reset station’s Trouble LED
flashes.
The test/reset station dirty sensor test checks the test/reset
station’s ability to initiate a sensor dirty test and indicate
the results. It must be wired to the controller as shown in
Fig. 24 and configured to operate the controller’s
supervision relay. For more information, see “Changing
sensor dirty test operation.”
DETECTOR CLEANING
Cleaning the Smoke Detector
Clean the duct smoke sensor when the Dirty LED is
flashing continuously or sooner if conditions warrant.
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 3 – Detector Indicators
CONTROL OR INDICATOR
DESCRIPTION
Magnetic test/reset switch
Resets the sensor when it is in the alarm or trouble state. Activates or tests the sensor when it is in
the normal state.
Alarm LED
Trouble LED
Dirty LED
Indicates the sensor is in the alarm state.
Indicates the sensor is in the trouble state.
Indicates the amount of environmental compensation used by the sensor
(flashing continuously = 100%)
Power LED
Indicates the sensor is energized.
INDICATORS
!
CAUTION
Normal State
OPERATIONAL TEST HAZARD
The smoke detector operates in the normal state in the
absence of any trouble conditions and when its sensing
chamber is free of smoke. In the normal state, the Power
LED on both the sensor and the controller are on and all
other LEDs are off.
Failure to follow this caution may result in personnel
and authority concern.
If the smoke detector is connected to a fire alarm
system, first notify the proper authorities that the
detector is undergoing maintenance then disable the
relevant circuit to avoid generating a false alarm.
Alarm State
The smoke detector enters the alarm state when the
amount of smoke particulate in the sensor’s sensing
chamber exceeds the alarm threshold value. (See Table 3.)
Upon entering the alarm state:
1. Disconnect power from the duct detector then remove
the sensor’s cover. (See Fig. 25.)
2. Using a vacuum cleaner, clean compressed air, or a
soft bristle brush, remove loose dirt and debris from
inside the sensor housing and cover.
S The sensor’s Alarm LED and the controller’s Alarm LED
turn on.
Use isopropyl alcohol and a lint-free cloth to remove
dirt and other contaminants from the gasket on the
sensor’s cover.
S The contacts on the controller’s two auxiliary relays
switch positions.
S The contacts on the controller’s alarm initiation relay
close.
3. Squeeze the retainer clips on both sides of the optic
housing then lift the housing away from the printed
circuit board.
4. Gently remove dirt and debris from around the optic
plate and inside the optic housing.
5. Replace the optic housing and sensor cover.
6. Connect power to the duct detector then perform a
sensor alarm test.
S The controller’s remote alarm LED output is activated
(turned on).
S The controller’s high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
The SuperDuct duct smoke detector enters the trouble
state under the following conditions:
S A sensor’s cover is removed and 20 minutes pass before
it is properly secured.
HVAC duct
Sampling
tube
Sensor
housing
S A sensor’s environmental compensation limit is reached
(100% dirty).
S A wiring fault between a sensor and the controller is
detected.
Optic
plate
Airflow
An internal sensor fault is detected upon entering the
trouble state:
Retainer
clip
Optic
housing
S The contacts on the controller’s supervisory relay switch
positions. (See Fig. 26.)
S If a sensor trouble, the sensor’s Trouble LED the
C07305
Fig. 25 - Sensor Cleaning Diagram
controller’s Trouble LED turn on.
S If 100% dirty, the sensor’s Dirty LED turns on and the
controller’s Trouble LED flashes continuously.
19
Download from Www.Somanuals.com. All Manuals Search And Download.
S If a wiring fault between a sensor and the controller, the
controller’s Trouble LED turns on but not the sensor’s.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.
Controller’s Power LED is Off
Trouble
1. Make sure the circuit supplying power to the control-
ler is operational. If not, make sure JP2 and JP3 are
set correctly on the controller before applying power.
Alarm
Power
2. Verify that power is applied to the controller’s supply
input terminals. If power is not present, replace or re-
pair wiring as required.
Test/reset
switch
Remote Test/Reset Station’s Trouble LED Does
Not flash When Performing a Dirty Test, But the
Controller’s Trouble LED Does
C07298
Fig. 26 - Controller Assembly
1. Verify that the remote test/station is wired as shown
in Fig. 23. Repair or replace loose or missing wiring.
2. Configure the sensor dirty test to activate the control-
ler’s supervision relay. See “Changing sensor dirty
test operation.”
NOTE: All troubles are latched by the duct smoke
detector. The trouble condition must be cleared and then
the duct smoke detector must be reset in order to restore it
to the normal state.
Resetting Alarm and Trouble Condition Trips:
Sensor’s Trouble LED is On, But the Controller’s
Trouble LED is OFF
Remove JP1 on the controller.
Manual reset is required to restore smoke detector systems
to Normal operation. For installations using two sensors,
the duct smoke detector does not differentiate which
sensor signals an alarm or trouble condition. Check each
sensor for Alarm or Trouble status (indicated by LED).
Clear the condition that has generated the trip at this
sensor. Then reset the sensor by pressing and holding the
reset button (on the side) for 2 seconds. Verify that the
sensor’s Alarm and Trouble LEDs are now off. At the
controller, clear its Alarm or Trouble state by pressing and
holding the manual reset button (on the front cover) for 2
seconds. Verify that the controller’s Alarm and Trouble
LEDs are now off. Replace all panels.
PROTECTIVE DEVICES
Compressor Protection
Overcurrent
The compressor has internal linebreak motor protection.
Overtemperature
The compressor has an internal protector to protect it
against excessively high discharge gas temperatures.
High Pressure Switch
TROUBLESHOOTING
The system is provided with a high pressure switch
mounted on the discharge line. The switch is
stem-mounted and brazed into the discharge tube. Trip
setting is 630 psig +/- 10 psig (4344 +/- 69 kPa) when
hot. Reset is automatic at 505 psig (3482 kPa).
Controller’s Trouble LED is On
1. Check the Trouble LED on each sensor connected to
the controller. If a sensor’s Trouble LED is on, de-
termine the cause and make the necessary repairs.
2. Check the wiring between the sensor and the control-
ler. If wiring is loose or missing, repair or replace as
required.
Low Pressure Switch
The system is protected against a loss of charge and low
evaporator coil loading condition by a low pressure switch
located on the suction line near the compressor. The
switch is stem-mounted. Trip setting is 54 psig +/- 5 psig
(372 +/- 34 kPa). Reset is automatic at 117 +/- 5 psig
(807 +/- 34 kPa).
Controller’s Trouble LED is Flashing
1. One or both of the sensors is 100% dirty.
2. Determine which Dirty LED is flashing then clean
that sensor assembly as described in the detector
cleaning section.
Evaporator Freeze Protection
Sensor’s Trouble LED is On
1. Check the sensor’s Dirty LED. If it is flashing, the
sensor is dirty and must be cleaned.
2. Check the sensor’s cover. If it is loose or missing, se-
cure the cover to the sensor housing.
The system is protected against evaporator coil frosting
and low temperature conditions by a temperature switch
mounted on the evaporator coil hairpin. Trip setting is
30_F +/- 5_F (-1_C +/- 3_C). Reset is automatic at 45_F
(7_C).
3. Replace sensor assembly.
Supply (Indoor) Fan Motor Protection
Sensor’s Power LED is Off
Disconnect and lockout power when servicing fan motor.
1. Check the controller’s Power LED. If it is off, de-
termine why the controller does not have power and
make the necessary repairs.
The standard supply fan motor is equipped with internal
overcurrent and overtemperature protection. Protection
devices reset automatically.
20
Download from Www.Somanuals.com. All Manuals Search And Download.
DISCONNECT EMT OR RIGID CONDUIT SINGLE
CENTER MANUAL RESET
The High Static option supply fan motor is equipped with
pilot-circuit Thermix combination
overtemperature/overcurrent protection device. This
device resets automatically. Do not bypass this switch to
correct trouble. Determine the cause and correct it.
MOUNTING
LOCATION
(FIELD-SUPPLIED)
POINT BOX POST
LIMIT SWITCH
a
HEATER
COVERS
Condenser Fan Motor Protection
The condenser fan motor is internally protected against
overtemperature.
Relief Device
SINGLE POINT
A soft solder joint at the suction service access port
provides pressure relief under abnormal temperature and
pressure conditions (i.e., fire in building). Protect this
joint during brazing operations near this joint.
MAIN
BRACKET AND BOX
HEATER
MODULE
HEATER
MODULE
HEATER
CONTROL CONDUIT
MOUNTING
SCREW
MOUNTING
BOX
DRIP BOOT
(LOCATION 1) (LOCATION 2) BRACKET
CONTROL WIRE TERMINAL BLOCK
C08134
Fig. 28 - Typical Component Location
Control Circuit, 24--V
The control circuit is protected against overcurrent
conditions by a circuit breaker mounted on control
transformer TRAN. Reset is manual.
ELECTRIC HEATERS
50TC units may be equipped with field-installed
accessory electric heaters. The heaters are modular in
design, with heater frames holding open coil resistance
wires strung through ceramic insulators, line-break limit
switches and a control contactor. One or two heater
modules may be used in a unit.
TRACK
Heater modules are installed in the compartment below
the indoor (supply) fan outlet. Access is through the
indoor access panel. Heater modules slide into the
compartment on tracks along the bottom of the heater
opening. See Figs 27 - 29.
FLANGE
DISCONNECT MOUNTING
LOCATION
C08135
Fig. 29 - Typical Module Installation
Not all available heater modules may be used in every
unit. Use only those heater modules that are UL listed for
use in a specific size unit. Refer to the label on the unit
cabinet re approved heaters.
Unit heaters are marked with Heater Model Numbers. But
heaters are ordered as and shipped in cartons marked with
a corresponding heater Sales Package part number. See
Table 4 for correlation between heater Model Number and
Sales Package part number.
NOTE: The value in position 9 of the part number differs
between the sales package part number (value is 1) and a
bare heater model number (value is 0).
INDOOR
UNIT BLOCK-OFF
PANEL
OUTDOOR
ACCESS
PANEL
ACCESS PANEL
C08133
Fig. 27 - Typical Access Panel Location (3-6 Ton)
Table 4 – Heater Model Number
Bare Heater Model
Number
C
C
R
R
H
H
E
E
A
A
T
T
E
E
R
R
0
1
0
0
1
1
A
A
0
0
0
0
Heater Sales Package
PNO
Includes:
Bare Heater
Carton and packing
materials
Installation sheet
21
Download from Www.Somanuals.com. All Manuals Search And Download.
Single Point Boxes and Supplementary Fuses — When
the unit MOCP device value exceeds 60-A, unit-mounted
supplementary fuses are required for each heater circuit.
These fuses are included in accessory Single Point Boxes,
with power distribution and fuse blocks. The single point
box will be installed directly under the unit control box,
just to the left of the partition separating the indoor
section (with electric heaters) from the outdoor section.
The Single Point Box has a hinged access cover. See Fig
30.
copper wire only. Size these conductors based on the
MCA (Minimum Circuit Ampacity) value marked on the
50TC unit’s info plate for the base unit less electric heater
load.
Use
UL-approved
pressure
connectors
(field-supplied) for these splice joints.
CONTROL
BOX
2
1
1
1
2
1
3
3
Line-Break
Limit Switches
BUSHING
2 1
1 1
2 3
SINGLE
POINT BOX
MOUNTING
SCREWS
1 3
ALLIED
MODE
P
A
L
NO
.
OD
ERIAL
NO
.
DRIP BOOT
BRACKET
MOUNTING
SCREWS
ISTED
AIR
NDITIONING
1
3
23
2-
UIP
ACCES
6N
S
34
.
P
/
N
5610-4
REV
POWER
WIRES
2 3
2 1
1 3
1 1
FOAM
BUSHING
LLIED
PA
CORP
.
MDEL
NO.
OD
IAL NO
.
22.2
TED AIR
ITIONING
P ACCESS
1
3
23
2-
36N.
P
/
N
5610-4
REV
C08330
HEATER
RELAYS
Fig. 31 - Typical Location of Heater Limit Switches
(3-phase heater shown)
HEATER
MOUNTING
SCREWS
Low-Voltage Control Connections
—
Pull the
C08136
low-voltage control leads from the heater module(s) -
VIO and BRN (two of each if two modules are installed;
identify for Module #1) - to the 4-pole terminal board
TB4 located on the heater bulkhead to the left of Heater
#1. Connect the VIO lead from Heater #1 to terminal
TB4-1. Connect the VIO lead from Heater #2 to terminal
TB4-2. Connect both BRN leads to terminal TB4-3. See
Fig. 32.
Fig. 30 - Typical Single Point Installation
On 50TC units, all fuses are 60-A. Single point boxes
containing fuses for 208/230-V applications use UL Class
RK5 250-V fuses (Bussman FRNR 60 or Shawmut TR
60R). Single point boxes for 460-V and 575-V
applications use UL Class T 600-V fuses (Bussman JJS
60 or Shawmut A6T 60). (Note that all heaters are
qualified for use with a 60-A fuse, regardless of actual
heater ampacity, so only 60-A fuses are necessary.)
Unit heater applications not requiring supplemental fuses
do not require a Single Point Box. Connect power supply
conductors to heater conductors and field-supplied base
unit power tap leads (see text below re: “Completing
Heater Installation”) below the unit’s main control box
using UL-approved connectors.
LCTB
CONTL
BOARD
2
VIO
ORN
BRN
3
12
Safety Devices — Electric heater applications use a
combination of line-break/auto-reset limit switches and a
pilot-circuit/manual reset limit switch to protect the unit
against over-temperature situations.
BRN
3
VIO
2
ORN
1
TB4
Line-break/auto-reset limit switches are mounted on the
base plate of each heater module. See Fig. 31. These are
accessed through the indoor access panel. Remove the
switch by removing two screws into the base plate and
extracting the existing switch.
Pilot-circuit/manual reset limit switch is located in the
side plate of the indoor (supply) fan housing. See Fig. 28.
VIO
VIO
BRN BRN
Field
Connections
Elec Htr
VIO
BRN
BRN
HR2
HR1
VIO
Completing Heater Installation
HR1: On Heater 1 in Position #1
HR2: On Heater 2 in Position #2 (if installed)
Field Power Connections
—
Field-supplied tap
conductors must be installed between the base unit’s field
power connection lugs and the splice connection between
field power supply conductors and the conductors to the
electric heater(s). Refer to unit wiring schematic. Use
C08331
Fig. 32 - Accessory Electric Heater Control
Connections
22
Download from Www.Somanuals.com. All Manuals Search And Download.
C08199
Fig. 33 - PremierLink Controller
Supply Air Temperature (SAT) Sensor
—
On
PREMIERLINKT CONTROL
FIOP-equipped 50TC unit, the unit is supplied with a
supply-air temperature (SAT) sensor (33ZCSENSAT).
This sensor is a tubular probe type, approx 6-inches (12.7
mm) in length. It is a nominal 10-k ohm thermistor. See
Table 15 for temperature-resistance characteristic.
The PremierLink controller (see Fig. 33) is compatible
with Carrier Comfort Networkr (CCN) devices. This
control is designed to allow users the access and ability to
change factory-defined settings, thus expanding the
function of the standard unit control board. CCN service
access tools include System Pilot (TM), Touch Pilot (TM)
and Service Tool. (Standard tier display tools Navigatort
and Scrolling Marquee are not suitable for use with latest
PremierLink controller (Version 2.x).)
The SAT is factory-wired. The SAT probe is wire-tied to
the supply-air opening (on the horizontal opening end) in
its shipping position. Remove the sensor for installation.
Re-position the sensor in the flange of the supply-air
opening or in the supply air duct (as required by local
codes). Drill or punch a 1/2-in. hole in the flange or duct.
Use two field-supplied, self-drilling screws to secure the
sensor probe in a horizontal orientation. See Fig. 36.
The PremierLink control is factory-mounted in the 50TC
unit’s main control box to the left of the LCTB. Factory
wiring is completed through harnesses connected to the
LVTB. Field connections are made at a 16-pole terminal
block (TB1) located on the bottom shelf of the unit
control box in front of the PremierLink controller The
factory-installed PremierLink control includes the
supply-air temperature (SAT) sensor. The outdoor air
temperature (OAT) sensor is included in the
FIOP/accessory Economizer 2 package.
Refer to Fig. 33 for PremierLink connection locations.
NOTE:
Refer to Form 33CS-58SI for complete
PremierLink configuration, operating sequences and
troubleshooting information. Have a copy of this manual
available at unit start-up.
ROOF
CURB
SUPPLY AIR
TEMPERATURE
SENSOR
SUPPLY AIR
RETURN AIR
The PremierLink controller requires the use of a Carrier
electronic thermostat or a CCN connection for time
broadcast to initiate its internal timeclock. This is
necessary for broadcast of time of day functions
(occupied/unoccupied).
C08200
Fig. 34 - Typical Mounting Location for Supply Air
Temperature (SAT) Sensor on Small Rooftop Units
NOTE: PremierLink controller is shipped in Sensor
mode. To be used with a thermostat, the PremierLink
controller must be configured to Thermostat mode. Refer
to PremierLink Configuration instructions for Operating
Mode.
23
Download from Www.Somanuals.com. All Manuals Search And Download.
24
24
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 5 – Thermistor Resistance vs Temperature
Values for Space Temperature Sensor, Supply Air
Temperature Sensor, and Outdoor Air Temperature
Sensor
Field connections — Field connections for accessory
sensor and input devices are made at the 16-pole terminal
block (TB1) located on the control box bottom shelf in
front of the PremierLink control. Some input devices also
require a 24-vac signal source; connect at LCTB terminal
R at “THERMOSTAT” connection strip for this signal
source. See connections figures on following pages for
field connection locations (and for continued connections
at the PremierLink board inputs).
TEMP
(C)
TEMP
(F)
RESISTANCE
(Ohms)
--- 4 0
--- 3 5
--- 3 0
--- 2 5
--- 2 0
--- 1 5
--- 1 0
--- 5
0
5
10
15
20
--- 4 0
--- 3 1
--- 2 2
--- 1 3
--- 4
5
14
23
32
41
335,651
242,195
176,683
130,243
96,974
72,895
55,298
42,315
32,651
25,395
19,903
15,714
12,494
10,000
8,056
Table 7 provides a summary of field connections for units
equipped with Space Sensor. Table 8 provides a summary
of field connections for units equipped with Space
Thermostat.
Space Sensors
-
The PremierLink controller is
factory-shipped configured for Space Sensor Mode. A
Carrier T-55 or T-56 space sensor must be used. T-55
space temperature sensor provides a signal of space
temperature to the PremierLink control. T-56 provides
same space temperature signal plus it allows for
adjustment of space temperature setpoints from the face of
the sensor by the occupants. See Table 5 for temperature
versus resistance characteristic on the space sensors.
50
59
68
77
25
30
86
35
95
6,530
40
45
50
55
60
65
70
104
113
122
131
140
149
158
5,325
4,367
3,601
2,985
2,487
2,082
1,752
Connect T-55 - See Fig. 36 for typical T-55 internal
connections. Connect the T-55 SEN terminals to TB1
terminals 1 and 3 (see Fig. 37).
NOTE: The sensor must be mounted in the discharge
airstream downstream of the cooling coil and any heating
devices. Be sure the probe tip does not come in contact
with any of the unit’s heater surfaces.
1
2
4
5
6
3
RED(+)
WHT(GND)
CCN COM
BLK(-)
SEN
Outdoor Air Temperature (OAT) Sensor — The OAT is
SW1
factory-mounted in the Economizer
accessory). It is a nominal 10k ohm thermistor attached to
2
(FIOP or
BRN (GND)
BLU (SPT)
SENSOR WIRING
an eyelet mounting ring. See Table
temperature-resistance characteristic.
5
for
Economizer 2 — The PremierLink control is used with
Economizer 2 (option or accessory) for outdoor air
management. The damper position is controlled directly
by the PremierLink control; Economizer 2 has no internal
logic device.
C08201
Fig. 36 - T-55 Space Temperature Sensor Wiring
Outdoor air management functions can be enhanced with
field-installation of these accessory control devices:
TB1
1
PL
Enthalpy control (outdoor air or differential sensors)
Space CO2 sensor
Outdoor air CO2 sensor
SEN
SEN
J6-7
J6-6
3
Refer to Table 6 for accessory part numbers
C08212
Fig. 37 - PremierLink T55 Sensor
25
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 6 – PremierLink Sensor Usage
OUTDOOR AIR
TEMPERATURE
SENSOR
RETURN AIR
TEMPERATURE
SENSOR
OUTDOOR AIR
ENTHALPY SENSOR
RETURN AIR
ENTHALPY SENSOR
APPLICATION
Differential Dry Bulb
Temperature with
PremierLink (PremierLink
r e q u ir e s 4 --- 2 0 m A
Actuator)
Single Enthalpy with
PremierLink (PremierLink
r e q u ir e s 4 --- 2 0 m A
Actuator)
Differential Enthalpy with
PremierLink (PremierLink
r e q u ir e s 4 --- 2 0 m A
Actuator)
R e q u ir e d ---
33ZCT55SPT
or equivalent
In c lu d e d ---
---
---
---
CRTEMPSN001A00
R e q u ir e s ---
HH57AC077
or equivalent
In c lu d e d ---
Not Used
---
---
R e q u ir e s ---
HH57AC077
or equivalent
R e q u ir e s ---
HH57AC078
or equivalent
In c lu d e d ---
Not Used
NOTES:
CO2 Sensors (Optional):
33ZCSENCO2 --- Room sensor (adjustable). Aspirator box is required for duct mounting of the sensor.
33ZCASPC02 --- Aspirator box used for duct---mounted CO2 room sensor.
33ZCT55CO2 --- Space temperature and CO2 room sensor with override.
33ZCT56C02 --- Space temperature and CO2 room sensor with override and setpoint.
26
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 7 – Space Sensor Mode
TB1 TERMINAL
FIELD CONNECTION
T 5 5 --- S E N / T 5 6 --- S E N
RMTOCC
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24VAC
1
2
3
4
T 5 5 --- S E N / T 5 6 --- S E N
CMPSAFE
Analog (10k thermistor)
Discrete, 24VAC
5
6
T 5 6 --- S E T
FSD
Analog (10k thermistor)
Discrete, 24VAC
7
LOOP---PWR
Analog, 24VDC
8
SPS
Discrete, 24VAC
9
IA Q --- S E N
FILTER
A n a lo g , 4 --- 2 0 m A
Discrete, 24VAC
A n a lo g , 4 --- 2 0 m A
Digital, , 5VDC
A n a lo g , 4 --- 2 0 m A
Digital, 5VDC
10
11
12
13
14
15
16
IA Q --- C O M/ O A Q --- C O M/ R H --- C O M
CCN + (RED)
O A Q --- S E N / R H --- S E N
CCN Gnd (WHT)
AUX OUT(Power Exhaust)
CCN --- (BLK)
(Output)Discrete 24VAC
Digital, 5VDC
LEGEND:
T55
--- Space Temperature Sensor
T56
--- Space Temperature Sensor
CCN
--- Carrier Comfort Network (communication bus)
CMPSAFE
FILTER
--- Compressor Safety
--- Dirty Filter Switch
F S D
IAQ
OAQ
--- F ir e S h u t d o w n
--- Indoor Air Quality (CO2)
--- Outdoor Air Quality (CO2)
RH
SFS
--- Relative Humidity
--- Supply Fan Status
Table 8 – Thermostat Mode
TB1 TERMINAL
FIELD CONNECTION
INPUT SIGNAL
Analog (10k thermistor)
Discrete, 24VAC
1
2
RAT SEN
G
3
4
RAT SEN
Y1
Analog (10k thermistor)
Discrete, 24VAC
5
6
7
8
9
10
11
12
13
14
15
16
Y2
LOOP---PWR
W1
IA Q --- S E N
Discrete, 24VAC
Analog, 24VDC
Discrete, 24VAC
A n a lo g , 4 --- 2 0 m A
Discrete, 24VAC
A n a lo g , 4 --- 2 0 m A
Digital, 5VDC
W2
IA Q --- C O M/ O A Q --- C O M/ R H --- C O M
CCN + (RED)
O A Q --- S E N / R H --- S E N
CCN Gnd (WHT)
AUX OUT (Power Exhaust)
CCN --- (BLK)
A n a lo g , 4 --- 2 0 m A
Digital, 5VDC
(Output) Discrete 24VAC
Digital, 5VDC
LEGEND:
CCN
G
---
---
---
---
---
---
---
---
---
---
Carrier Comfort Network (communication bus)
T h e r m o st a t Fa n
Indoor Air Quality (CO2)
Outdoor Air Quality (CO2)
Return Air Temperature
Relative Humidity
Thermostat Heat Stage 1
Thermostat Heat Stage 2
Thermostat Cool Stage 1
Thermostat Cool Stage 2
IAQ
OAQ
RAT
RH
W1
W2
Y1
Y2
27
Download from Www.Somanuals.com. All Manuals Search And Download.
Connect T-56
-
See Fig. 38 for T-56 internal
PremierLink Configuration screen for Operating Mode.
Default setting is Sensor Mode (value 1). Change the
value to 0 to reconfigure the controller for Thermostat
Mode.
connections. Install a jumper between SEN and SET
terminals as illustrated. Connect T-56 terminals to TB1
terminals 1, 3 and 5 (see Fig. 39).
When the PremierLink is configured for Thermostat
Mode, these functions are not available: Fire Shutdown
(FSD), Remote Occupied (RMTOCC), Compressor Safety
(CMPSAFE), Supply Fan Status (SFS), and Filter Pressure
Switch (FILTER).
1
2
4
5
6
3
RED(+)
WHT(GND)
CCN COM
Economizer controls —
BLK(-)
SET
SEN
Outdoor Air Enthalpy Control (PNO HH57AC077) -
SW1
BLK
(T56)
The enthalpy control (HH57AC077) is available as a
field-installed accessory to be used with the EconoMi$er2
damper system. The outdoor air enthalpy sensor is part of
the enthalpy control. (The separate field-installed
accessory return air enthalpy sensor (HH57AC078) is
required for differential enthalpy control. See below.)
BRN (GND)
BLU (SPT)
SENSOR WIRING
JUMPER
TERMINALS
AS SHOWN
Locate the enthalpy control in the economizer hood.
Locate two GRA leads in the factory harness and connect
these leads to enthalpy control sensors 2 and 3. See Fig.
41. Connect the enthalpy control power input terminals to
economizer actuator power leads RED (connect to TR)
and BLK (connect to TR).
Cool
Warm
C08202
Fig. 38 - T-56 Internal Connections
TB1
1
PL
SEN
SEN
J6-7
LCTB
SPACE
PL
TB1
3
THERMOSTAT
THERMOSTAT
J6-6
R
TB1
2
R
Jumper
SET
SET
PL
J4-12
G
Y1
Y2
W1
W2
C
J6-5
5
J4-10
J4-8
J4-6
4
6
C08213
Fig. 39 - PremierLink T56 Sensor
8
Connect Thermostat — A 7-wire thermostat connection
requires a 24-v power source and a common connection.
Use the R and C terminals on the LCTB’s THERMOSTAT
connection strip for these. Connect the thermostat’s Y1,
Y2, W1, W2 and G terminals to PremierLink TB1 as
shown in Fig. 40.
J4-4
10
C
LCTB
THERMOSTAT
C08119
Fig. 40 - Space Thermostat Connections
If the 50TC unit is equipped with factory-installed smoke
detector(s), disconnect the factory BLU lead at TB1-6
(Y2) before connecting the thermostat. Identify the BLU
lead originating at LCTB DDC-1; disconnect at TB1-6
and tape off. Confirm that the second BLU lead at TB1-6
remains connected to PremierLink J4-8.
LCTB
ECON
Enthalpy
Switch
6
2
3
GRA
GRA
If the 50TC unit has an economizer system and
free-cooling operation is required, a sensor representing
Return Air Temperature must also be connected
(field-supplied and installed). This sensor may be a T-55
Space Sensor (see Fig. 36) installed in the space or in the
return duct, or it may be sensor PNO 33ZCSENSAT,
installed in the return duct. Connect this sensor to TB1-1
and TB1-3 per Fig. 37. Temperature-resistance
characteristic is found in Table 5.
7
Factory Wiring Harness
C08218
Fig. 41 - Enthalpy Switch (HH57AC077) Connections
Configure the unit for Thermostat Mode — Connect to the
CCN bus using a CCN service tool and navigate to
The outdoor enthalpy changeover setpoint is set at the
enthalpy controller.
28
Download from Www.Somanuals.com. All Manuals Search And Download.
The enthalpy control receives the outdoor air enthalpy
from the outdoor air enthalpy sensor and provides a dry
contact switch input to the PremierLink controller. A
closed contact indicates that outside air is preferred to the
return air. An open contact indicates that the economizer
should remain at minimum position.
levels. This information is used to monitor IAQ levels.
Several types of sensors are available, for wall mounting
in the space or in return duct, with and without LCD
display, and in combination with space temperature
sensors. Sensors use infrared technology to measure the
levels of CO2 present in the space air.
Differential Enthalpy Control — Differential enthalpy
control is provided by sensing and comparing the outside
air and return air enthalpy conditions. Install the outdoor
air enthalpy control as described above. Add and install a
return air enthalpy sensor.
The CO2 sensors are all factory set for a range of 0 to
2000 ppm and a linear mA output of 4 to 20. Refer to the
instructions supplied with the CO2 sensor for electrical
requirements and terminal locations. See Fig. 43 for
typical CO2 sensor wiring schematic.
Return Air Enthalpy Sensor — Mount the return-air
enthalpy sensor (HH57AC078) in the return-air duct. The
return air sensor is wired to the enthalpy controller
(HH57AC077). See Fig. 42.
ENTHALPY CONTROLLER
(OUTDOOR
AIR
ENTHALPY
SENSOR)
S
+
RED
BRN
B
TR
SO
TR1
BLK
RED
C
D
A
+ 0-10VDC
+
-
SIG COM (J4-6)
4-20mA (J4-5)
+
S
+
(RETURN AIR
ENTHALPY
SENSOR)
+
3
1
SR
2
ALARM
NC
COM RELAY
}
GRAY/ORN
GRAY/RED
NO CONTACTS
WIRE HARNESS
IN UNIT
LED
24 VAC
OR
24 VDC
H G
+
-
2 1
5 4 3 2 1
8 7 6
NOTES:
1. Remove factory-installed jumper across SR and + before connecting
wires from return air sensor.
2. Switches shown in high outdoor air enthalpy state. Terminals 2 and 3
close on low outdoor air enthalpy relative to indoor air enthalpy.
3. Remove sensor mounted on back of control and locate in outside air-
stream.
C06019
C07134
Fig. 42 - Outside and Return Air Enthalpy Sensor
Wiring
Fig. 43 - Indoor/Outdoor Air Quality (CO2) Sensor
(33ZCSENCO2) - Typical Wiring Diagram
To wire the return air enthalpy sensor, perform the
following:
To accurately monitor the quality of the air in the
conditioned air space, locate the sensor near a return-air
grille (if present) so it senses the concentration of CO2
leaving the space. The sensor should be mounted in a
location to avoid direct breath contact.
1. Use a 2-conductor, 18 or 20 AWG, twisted pair cable
to connect the return air enthalpy sensor to the enthal-
py controller.
2. At the enthalpy control remove the factory-installed
resistor from the (SR) and (+) terminals.
Do not mount the IAQ sensor in drafty areas such as near
supply ducts, open windows, fans, or over heat sources.
Allow at least 3 ft (0.9 m) between the sensor and any
corner. Avoid mounting the sensor where it is influenced
by the supply air; the sensor gives inaccurate readings if
the supply air is blown directly onto the sensor or if the
supply air does not have a chance to mix with the room air
before it is drawn into the return airstream.
3. Connect the field-supplied RED wire to (+) spade
connector on the return air enthalpy sensor and the
(SR+) terminal on the enthalpy controller. Connect
the BLK wire to (S) spade connector on the return air
enthalpy sensor and the (SR) terminal on the enthalpy
controller.
NOTE: The enthalpy control must be set to the “D”
setting for differential enthalpy control to work properly.
Wiring the Indoor Air Quality Sensor —
For each sensor, use two 2-conductor 18 AWG (American
Wire Gage) twisted-pair cables (unshielded) to connect
the separate isolated 24 vac power source to the sensor
and to connect the sensor to the control board terminals.
The enthalpy control receives the indoor and return
enthalpy from the outdoor and return air enthalpy sensors
and provides
a
dry contact switch input to the
PremierLink controller. A closed contact indicates that
outside air is preferred to the return air. An open contact
indicates that the economizer should remain at minimum
position.
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
sensor. See Fig. 43. Connect the 4-20 mA terminal to
terminal TB1-9 and connect the SIG COM terminal to
terminal TB1-7. See Fig. 44.
Indoor Air Quality (CO2 sensor) — The indoor air quality
sensor accessory monitors space carbon dioxide (CO2)
29
Download from Www.Somanuals.com. All Manuals Search And Download.
IAQ Sensor
24 VAC
Refer to Form 33CS-58SI, PremierLink Installation,
Start-up, and Configuration Instructions, for detailed
configuration information.
TB1
9
PL
J5-5
SEN
TB1
7
COM
J5-6
Smoke Detector/Fire Shutdown (FSD) — This function is
available only when PremierLink is configured for
(Space) Sensor Mode. The unit is factory-wired for
PremierLink FSD operation when PremierLink is
factory-installed.
C08274
Fig. 44 - Indoor CO2 Sensor (33ZCSENCO2) Connec-
tions
On 50TC units equipped with factory-installed Smoke
Detector(s), the smoke detector controller implements the
unit shutdown through its NC contact set connected to the
unit’s LCTB input. The FSD function is initiated via the
smoke detector’s Alarm NO contact set. The PremierLink
communicates the smoke detector’s tripped status to the
CCN building control. See Fig. 23 for unit smoke detector
wiring.
Refer to Form 33CS-58SI, PremierLink Installation,
Start-up, and Configuration Instructions, for detailed
configuration information
Outdoor Air Quality Sensor (PNO 33ZCSENCO2 plus
weatherproof enclosure) — The outdoor air CO2 sensor is
designed to monitor carbon dioxide (CO2) levels in the
outside ventilation air and interface with the ventilation
damper in an HVAC system. The OAQ sensor is packaged
with an outdoor cover. See Fig. 45. The outdoor air CO2
sensor must be located in the economizer outside air hood.
Alarm state is reset when the smoke detector alarm
condition is cleared and reset at the smoke detector in the
unit.
If the PremierLink mode has been changed to Thermostat,
disconnect the BLU lead (from LCTB DDC-1) at TB1-6
(Y2) and tape off before connecting the thermostat to
TB1.
Filter Status Switch — This function is available only
when PremierLink is configured for (Space) Sensor Mode.
PremierLink control can monitor return filter status in two
ways: By monitoring a field-supplied/installed filter
pressure switch or via supply fan runtime hours.
Using switch input: Install the dirty filter pressure switch
according to switch manufacturer’s instructions, to
measure pressure drop across the unit’s return filters.
Connect one side of the switch’s NO contact set to
LCTB’s THERMOSTAT-R terminal. Connect the other
side of the NO contact set to TB1-10. Setpoint for Dirty
Filter is set at the switch. See Fig. 47.
COVER REMOVED
SIDE VIEW
C07135
Fig. 45 - Outdoor Air Quality Sensor Cover
Filter Switch (NO, close on rising pressure (high drop))
Wiring the Outdoor Air CO2 Sensor — A dedicated
power supply is required for this sensor. A two-wire cable
is required to wire the dedicated power supply for the
sensor. The two wires should be connected to the power
supply and terminals 1 and 2.
LCTB
Thermostat
R
TB1
10
PL
J4-4
To connect the sensor to the control, identify the positive
(4 to 20 mA) and ground (SIG COM) terminals on the
OAQ sensor. See Fig. 43. Connect the 4 to 20 mA
terminal to 50TC’s terminal TB1-11. Connect the SIG
COM terminal to 50TC’s terminal TB1-13. See Fig. 461.
C08216
Fig. 47 - PremierLink Filter Switch Connection
When the filter switch’s NO contact set closes as filter
pressure drop increases (indicating dirt-laden filters), the
input signal to PremierLink causes the filter status point to
read “DIRTY”.
OAQ Sensor/RH Sensor
TB1
13
PL
J5-2
SEN
TB1
11
COM
J5-3
Using Filter Timer Hours: Refer to Form 33CS-58SI for
instructions on using the PremierLink Configuration
screens and on unit alarm sequence.
24 VAC
C08275
Fig. 46 - Outdoor CO2 Sensor Connections
Supply Fan Status Switch — The PremierLink control can
monitor
supply
fan
operation
through
a
field-supplied/installed differential pressure switch. This
30
Download from Www.Somanuals.com. All Manuals Search And Download.
sequence will prevent (or interrupt) operation of unit
cooling, heating and economizer functions until the
pressure switch contacts are closed indicating proper
supply fan operation.
CCN Communication Bus — The PremierLink controller
connects to the bus in a daisy chain arrangement.
Negative pins on each component must be connected to
respective negative pins, and likewise, positive pins on
each component must be connected to respective positive
pins. The controller signal pins must be wired to the signal
ground pins. Wiring connections for CCN must be made
at the 3-pin plug.
Install the differential pressure switch in the supply fan
section according to switch manufacturer’s instructions.
Arrange the switch contact to be open on no flow and to
close as pressure rises indicating fan operation.
At any baud (9600, 19200, 38400 baud), the number of
controllers is limited to 239 devices maximum. Bus length
may not exceed 4000 ft, with no more than 60 total
devices on any 1000-ft section. Optically isolated RS-485
repeaters are required every 1000 ft.
Connect one side of the switch’s NO contact set to
LCTB’s THERMOSTAT-R terminal. Connect the other
side of the NO contact set to TB1-8. Setpoint for Supply
Fan Status is set at the switch. See Fig. 48
Fan (Pressure) Switch (NO, close on rise in pressure)
NOTE: Carrier device default is 9600 band.
LCTB
Thermostat
COMMUNICATION BUS WIRE SPECIFICATIONS —
The CCN Communication Bus wiring is field-supplied
and field-installed. It consists of shielded 3-conductor
cable with drain (ground) wire. The cable selected must
be identical to the CCN Communication Bus wire used for
the entire network.
R
TB1
8
PL
J4-6
C08118
Fig. 48 - PremierLink Wiring Fan Pressure Switch
Connection
See Table 9 for recommended cable.
Table 9 – Recommended Cables
Remote Occupied Switch — The PremierLink control
permits a remote timeclock to override the control’s
on-board occupancy schedule and place the unit into
Occupied mode. This function may also provide a “Door
Switch” time delay function that will terminate cooling
and heating functions after a 2-20 minute delay.
MANUFACTURER
Alpha
CABLE PART NO.
2413 or 5463
A22503
American
Belden
Columbia
8772
02525
NOTE: Conductors and drain wire must be at least 20
AWG, stranded, and tinned copper. Individual conductors
must be insulated with PVC, PVC/nylon, vinyl, Teflon, or
polyethylene. An aluminum/polyester 100% foil shield
and an outer jacket of PVC, PVC/nylon, chrome vinyl, or
Teflon with a minimum operating temperature range of
-20 C to 60 C is required. Do not run communication wire
in the same conduit as or next to any AC voltage wiring.
Connect one side of the NO contact set on the timeclock
to LCTB’s THERMOSTAT-R terminal. Connect the other
side of the timeclock contact to the unit’s TB1-2 terminal.
LCTB
Remote Occupied
Thermostat
R
Time Clock
TB1
2
PL
J4-12
The communication bus shields must be tied together at
each system element. If the communication bus is entirely
within one building, the resulting continuous shield must
be connected to ground at only one single point. If the
communication bus cable exits from one building and
enters another building, the shields must be connected to
the grounds at a lightning suppressor in each building (one
point only).
C08214
Fig. 49 - PremierLink Wiring Remote Occupied
Refer to Form 33CS-58SI for additional information on
configuring the PremierLink control for Door Switch
timer function.
Power Exhaust (output) - Connect the accessory Power
Exhaust contactor coils(s) per Fig. 50.
Connecting CCN bus:
NOTE: When connecting the communication bus cable,
Power Exhaust
TB1
PL
a
color code system for the entire network is
recommended to simplify installation and checkout. See
Table 10 for the recommended color code.
15
J8-3
PEC
TAN
LCTB
THERMOSTAT
C
Table 10 – Color Code Recommendations
GRA
CCN BUS WIRE
COLOR
CCN PLUG PIN
NUMBER
C08120
SIGNAL TYPE
Fig. 50 - PremierLink Power Exhaust Output
Connection
+
Ground
---
Red
White
Black
1
2
3
Space Relative Humidity Sensor — The RH sensor is not
used with 50TC models at this time.
Connect the CCN (+) lead (typically RED) to the unit’s
TB1-12 terminal. Connect the CCN (ground) lead
31
Download from Www.Somanuals.com. All Manuals Search And Download.
ECONOMI$ER IV
CONTROLLER
(typically WHT) to the unit’s TB1-14 terminal. Connect
the CCN (-) lead (typically BLK) to the unit’s TB1-16
terminal. See Fig. 51.
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
WIRING
HARNESS
CCN Bus
ACTUATOR
TB1
12
PL
J2-1
+ (RED)
TB1
14
GND (WHT)
J2-2
TB1
16
– (BLK)
J2-3
C08276
C06021
Fig. 51 - PremierLink CCN Bus Connections
Fig. 52 - EconoMi$er IV Component Locations
OUTDOOR
AIR HOOD
ECONOMIZER SYSTEMS
The 50TC units may be equipped with a factory-installed
or accessory (field-installed) economizer system. Two
ECONOMI$ER2
HOOD
PLUG
SHIPPING
BRACKET
types are available: with
a
logic control system
control system
(EconoMi$er IV) and without
a
(EconoMi$er2, for use with external control systems such
as PremierLink). See Fig. 52 and 53 for component
locations on each type. See Fig. 54 and 55 for economizer
section wiring diagrams.
GEAR DRIVEN
DAMPER
BAROMETRIC
RELIEF
DAMPER
Both economizers use direct-drive damper actuators.
C06022
Fig. 53 - EconoMi$er2 Component Locations
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK
8
7
Potentiometer Defaults Settings:
LEGEND
NOTES:
Power Exhaust Middle
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
Minimum Pos.
DCV Max.
DCV Set
Fully Closed
enthalpy or dry bulb.
Middle
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT— Potentiometer
Middle
C Setting
Enthalpy
RAT — Return-Air Temperature
C06028
Fig. 54 - EconoMi$er IV Wiring
32
Download from Www.Somanuals.com. All Manuals Search And Download.
BLACK
BLUE
4
3
TRANSFORMER
GROUND
5
2
500 OHM
RESISTOR
8
VIOLET
PINK
6
NOTE 1
NOTE 3
7
RUN
OAT SENSOR
RED
24 VAC
1
10
11
9
50HJ540573
ACTUATOR
ASSEMBLY
4-20 mA
WHITE
DIRECT DRIVE
ACTUATOR
TO J9 ON
PremierLink
BOARD
4-20mA SIGNAL
12
ECONOMISER2 PLUG
NOTES:
1. Switch on actuator must be in run position for economizer to operate.
2. PremierLink™ control requires that the standard 50HJ540569 outside-air sensor be replaced by either the CROASENR001A00 dry bulb sen
sor or HH57A077 enthalpy sensor.
3. 50HJ540573 actuator consists of the 50HJ540567 actuator and a harness with 500-ohm resistor.
C08310
Fig. 55 - EconoMi$er2 with 4 to 20 mA Control Wiring
Table 11 – EconoMi$er IV Input/Output Logic
INPUTS
Enthalpy*
OUTPUTS
N Terminal†
Occupied
Compressor
Demand Control
Ventilation (DCV)
Y1 Y2
Unoccupied
Closed
Stage Stage
Outdoor
Return
Low
1
2
Damper
On On
On Off
Off Off
On On
On Off
Off Off
On On
On Off
Off Off
On On
On Off
Off Off
On
On
Off
On
Off
Off
On
On
Off
On
Off
Off
On
Off
Off
Off
Off
Off
On
Off
Off
Off
Off
Off
High
Minimum position
(Free Cooling LED Off)
Below set
(DCV LED Off)
Modulating** (between min. Modulating** (between
Low
position and full-open)
Minimum position
closed and full-open)
Closed
High
Low
High
(Free Cooling LED On)
Modulating†† (between min. Modulating†† (between
High
position and DCV
maximum)
closed and DCV
maximum)
(Free Cooling LED Off)
Above set
(DCV LED On)
Low
Modulating***
Modulating†††
(Free Cooling LED On)
*
†
For single enthalpy control, the module compares outdoor enthalpy to the ABCD setpoint.
Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
** Modulation is based on the supply-air sensor signal.
†† Modulation is based on the DCV signal.
*** Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV)
or fully open (supply-air signal).
††† Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully
open (supply-air signal).
33
Download from Www.Somanuals.com. All Manuals Search And Download.
C06053
Fig. 56 - EconoMi$er IV Functional View
The temperature sensor looks like an eyelet terminal with
wires running to it. The sensor is located in the “crimp
end” and is sealed from moisture.
EconoMi$er IV
Table 11 provides a summary of Economizer IV.
Troubleshooting instructions are enclosed.
Outdoor Air Lockout Sensor
A functional view of the EconoMi$er is shown in 56.
Typical settings, sensor ranges, and jumper positions are
also shown. An EconoMi$er IV simulator program is
available from Carrier to help with EconoMi$er IV
training and troubleshooting.
The EconoMi$er IV is equipped with an ambient
temperature lockout switch located in the outdoor
airstream which is used to lock out the compressors below
a 42_F (6_C) ambient temperature. (See Fig. 52.)
EconoMi$er IV Control Modes
EconoMi$er IV Standard Sensors
IMPORTANT: The optional EconoMi$er2 does not include
a controller. The EconoMi$er2 is operated by a 4 to 20
mA signal from an existing field-supplied controller (such
as PremierLink™ control). See Fig. 54 for wiring
information.
Determine the EconoMi$er IV control mode before set up
of the control. Some modes of operation may require
different sensors. (See Table 12.) The EconoMi$er IV is
supplied from the factory with a supply-air temperature
sensor and an outdoor- air temperature sensor. This allows
for operation of the EconoMi$er IV with outdoor air dry
bulb changeover control. Additional accessories can be
added to allow for different types of changeover control
and operation of the EconoMi$er IV and unit.
Outdoor Air Temperature (OAT) Sensor
The outdoor air temperature sensor (HH57AC074) is a 10
to 20 mA device used to measure the outdoor-air
temperature. The outdoor-air temperature is used to
determine when the EconoMi$er IV can be used for free
cooling. The sensor is factory-installed on the
EconoMi$er IV in the outdoor airstream. (See Fig. 55.)
The operating range of temperature measurement is 40_ to
100_F (4_ to 38_C). See Fig. 55.
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3 K thermistor
located at the inlet of the indoor fan. (See Fig. 57.) This
sensor is factory installed. The operating range of
temperature measurement is 0° to 158_F (-18_ to 70_C).
See Table 5 for sensor temperature/resistance values.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory
configured for outdoor dry bulb changeover control. The
outdoor air and supply air temperature sensors are
included as standard. For this control mode, the outdoor
temperature is compared to an adjustable setpoint selected
on the control. If the outdoor-air temperature is above the
setpoint, the EconoMi$er IV will adjust the outside air
dampers to minimum position. If the outdoor-air
temperature is below the setpoint, the position of the
outside air dampers will be controlled to provided free
cooling using outdoor air. When in this mode, the LED
next to the free cooling setpoint potentiometer will be on.
The changeover temperature setpoint is controlled by the
free cooling setpoint potentiometer located on the control.
(See Fig. 58.) The scale on the potentiometer is A, B, C,
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
C06033
Fig. 57 - Supply Air Sensor Location
34
Download from Www.Somanuals.com. All Manuals Search And Download.
and D. See Fig. 59 for the corresponding temperature
changeover values.
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry
bulb sensor is used in conjunction with an additional
accessory
dry
bulb
sensor
(part
number
CRTEMPSN002A00). The accessory sensor must be
mounted in the return airstream. (See Fig. 61.) Wiring is
provided in the EconoMi$er IV wiring harness. (See Fig.
52.)
ECONOMI$ERIV
CONTROLLER
ECONOMI$ERIV
GROMMET
C06034
Fig. 58 - EconoMi$er IV Controller Potentiometer
and LED Locations
RETURN AIR
SENSOR
19
LED ON
18
D
17
RETURN DUCT
LED ON
LED OFF
16
15
14
(FIELD-PROVIDED)
C
C07085
Fig. 61 - Return Air Temperature or Enthalpy Sensor
Mounting Location
LED ON
LED OFF
B
13
12
LED ON
LED OFF
A
11
10
9
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower
temperature airstream is used for cooling. When using this
mode of changeover control, turn the enthalpy setpoint
potentiometer fully clockwise to the D setting. (See Fig.
58.)
LED OFF
85 90
95
100
50
55 60
70 75
DEGREES FAHRENHEIT
40 45
65
80
C06035
Fig. 59 - Outside Air Temperature Changeover
Setpoints
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part
number HH57AC078) is required. Replace the standard
outdoor dry bulb temperature sensor with the accessory
enthalpy sensor in the same mounting location. (See 56.)
When the outdoor air enthalpy rises above the outdoor
enthalpy changeover setpoint, the outdoor-air damper
moves to its minimum position. The outdoor enthalpy
changeover setpoint is set with the outdoor enthalpy
setpoint potentiometer on the EconoMi$er IV controller.
The setpoints are A, B, C, and D. (See Fig. 62.) The
factory-installed 620-ohm jumper must be in place across
terminals SR and SR+ on the EconoMi$er IV controller.
(See Fig. 52 and 63.)
30
25
20
15
10
5
0
0.13 0.20 0.22 0.25 0.30 0.35 0.40 0.45 0.50
STATIC PRESSURE (in. wg)
C06031
Fig. 60 - Outdoor-Air Damper Leakage
35
Download from Www.Somanuals.com. All Manuals Search And Download.
85
90
95 100 105 110
(29) (32) (35) (38) (41) (43)
CONTROL CONTROL POINT
CURVE
APPROX. deg. F (deg. C)
AT 50% RH
80
(27)
A
B
C
D
73 (23)
70 (21)
67 (19)
63 (17)
75
(24)
70
(21)
65
(18)
0
6
60
(16)
A
55
(13)
B
50
(10)
C
45
(7)
D
40
(4)
35
(2)
A
B
C
D
HIGH LIMIT
CURVE
35
(2)
40
45
50
55
60
65
70
75
80
85
90
95 100 105 110
(4) (7) (10) (13) (16) (18) (21) (24) (27) (29) (32) (35) (38) (41) (43)
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
C06037
Fig. 62 - Enthalpy Changeover Setpoints
the outdoor air enthalpy to the return air enthalpy to
determine EconoMi$er IV use. The controller selects the
lower enthalpy air (return or outdoor) for cooling. For
example, when the outdoor air has a lower enthalpy than
the return air, the EconoMi$er IV opens to bring in
outdoor air for free cooling.
Replace the standard outside air dry bulb temperature
sensor with the accessory enthalpy sensor in the same
mounting location. (See Fig. 52.) Mount the return air
enthalpy sensor in the return air duct. (See Fig. 61.)
Wiring is provided in the EconoMi$er IV wiring harness.
(See Fig. 52.) The outdoor enthalpy changeover setpoint is
set with the outdoor enthalpy setpoint potentiometer on
the EconoMi$er IV controller. When using this mode of
changeover control, turn the enthalpy setpoint
potentiometer fully clockwise to the D setting.
TR1
EXH
Set
10V
TR
N1
N
2V
EXH
24
Va c
HOT
24 Vac
COM
P1
T1
P
T
Min
Pos
_
+
Open
DCV
Max
10V
1
2
5
2V
AQ1
AQ
SO+
SO
SR+
SR
DCV
DCV
Set
10V
4
3
2V
Free
Cool
EF1
EF
C
D
B
A
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation
control based on the level of CO2 measured in the space
or return air duct.
Mount the accessory IAQ sensor according to
manufacturer specifications. The IAQ sensor should be
wired to the AQ and AQ1 terminals of the controller.
Adjust the DCV potentiometers to correspond to the DCV
voltage output of the indoor air quality sensor at the
user-determined setpoint. (See Fig. 64.)
C06038
Fig. 63 - EonoMi$er IV Control
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV
controller uses two enthalpy sensors (HH57AC078 and
CRENTDIF004A00), one in the outside air and one in the
return air duct. The EconoMi$er IV controller compares
36
Download from Www.Somanuals.com. All Manuals Search And Download.
CO SENSOR MAX RANGE SETTING
2
To determine the minimum position setting, perform the
following procedure:
6000
5000
4000
3000
2000
1000
0
1. Calculate the appropriate mixed air temperature
using the following formula:
OA
100
RA
100
800 ppm
900 ppm
1000 ppm
1100 ppm
+ (TR x
(TO x
)
) =TM
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
T
M = Mixed-Air Temperature
2
3
4
5
6
7
8
DAMPER VOLTAGE FOR MAX VENTILATION RATE
As an example, if local codes require 10% outdoor
air during occupied conditions, outdoor-air
temperature is 60_ F, and return-air temperature is
75_F.
C06039
Fig. 64 - CO2 Sensor Maximum Range Settings
If a separate field-supplied transformer is used to power
the IAQ sensor, the sensor must not be grounded or the
EconoMi$er IV control board will be damaged.
(60 x .10) + (75 x .90) = 73.5_F
2. Disconnect the supply air sensor from terminals T
and T1.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for
3. Ensure that the factory-installed jumper is in place
across terminals P and P1. If remote damper
positioning is being used, make sure that the
terminals are wired according to Fig. 52 and that the
minimum position potentiometer is turned fully
clockwise.
VOC (volatile
organic
compounds) ventilation
requirements. The maximum demand ventilation position
is used for fully occupied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand
ventilation position should be turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully
adjust
the
minimum
position
potentiometer until the measured mixed air
temperature matches the calculated value.
Exhaust Setpoint Adjustment
The exhaust setpoint will determine when the exhaust fan
runs based on damper position (if accessory power
exhaust is installed). The setpoint is modified with the
Exhaust Fan Setpoint (EXH SET) potentiometer. (See Fig.
58.) The setpoint represents the damper position above
which the exhaust fans will be turned on. When there is a
call for exhaust, the EconoMi$er IV controller provides a
45 ± 15 second delay before exhaust fan activation to
allow the dampers to open. This delay allows the damper
to reach the appropriate position to avoid unnecessary fan
overload.
6. Reconnect the supply air sensor to terminals T and
T1.
Remote control of the EconoMi$er IV damper is desirable
when requiring additional temporary ventilation. If a
field-supplied remote potentiometer (Honeywell part
number S963B1128) is wired to the EconoMi$er IV
controller, the minimum position of the damper can be
controlled from a remote location.
To control the minimum damper position remotely,
remove the factory-installed jumper on the P and P1
terminals on the EconoMi$er IV controller. Wire the
field-supplied potentiometer to the P and P1 terminals on
the EconoMi$er IV controller. (See Fig. 63.)
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. (See Fig. 58.) The minimum
damper position maintains the minimum airflow into the
building during the occupied period.
When using demand ventilation, the minimum damper
position represents the minimum ventilation position for
Damper Movement
Damper movement from full open to full closed (or vice
versa) takes 21/2 minutes.
Thermostats
VOC
(volatile
organic
compound)
ventilation
The EconoMi$er IV control works with conventional
thermostats that have a Y1 (cool stage 1), Y2 (cool stage
2), W1 (heat stage 1), W2 (heat stage 2), and G (fan). The
EconoMi$er IV control does not support space
temperature sensors. Connections are made at the
thermostat terminal connection board located in the main
control box.
requirements. The maximum demand ventilation position
is used for fully occupied ventilation.
When demand ventilation control is not being used, the
minimum position potentiometer should be used to set the
occupied ventilation position. The maximum demand
ventilation position should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local
codes, to enter the building. Make minimum position
adjustments with at least 10_F temperature difference
between the outdoor and return-air temperatures.
Occupancy Control
The factory default configuration for the EconoMi$er IV
control is occupied mode. Occupied status is provided by
the black jumper from terminal TR to terminal N. When
unoccupied mode is desired, install a field-supplied
37
Download from Www.Somanuals.com. All Manuals Search And Download.
timeclock function in place of the jumper between TR and
N. (See Fig. 52.) When the timeclock contacts are closed,
the EconoMi$er IV control will be in occupied mode.
When the timeclock contacts are open (removing the 24-v
signal from terminal N), the EconoMi$er IV will be in
unoccupied mode.
graph with the left side of the chart to determine that the
range configuration for the CO2 sensor should be 1800
ppm. The EconoMi$er IV controller will output the 6.7
volts from the CO2 sensor to the actuator when the CO2
concentration in the space is at 1100 ppm. The DCV
setpoint may be left at 2 volts since the CO2 sensor
voltage will be ignored by the EconoMi$er IV controller
until it rises above the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been
determined, set the maximum damper demand control
ventilation potentiometer to this position. Do not set to the
maximum position as this can result in over-ventilation to
the space and potential high humidity levels.
Demand Control Ventilation (DCV)
When using the EconoMi$er IV for demand controlled
ventilation, there are some equipment selection criteria
which should be considered. When selecting the heat
capacity and cool capacity of the equipment, the
maximum ventilation rate must be evaluated for design
conditions. The maximum damper position must be
calculated to provide the desired fresh air.
Typically the maximum ventilation rate will be about 5 to
10% more than the typical cfm required per person, using
normal outside air design criteria.
A proportional anticipatory strategy should be taken with
the following conditions: a zone with a large area, varied
occupancy, and equipment that cannot exceed the required
ventilation rate at design conditions. Exceeding the
required ventilation rate means the equipment can
condition air at a maximum ventilation rate that is greater
than the required ventilation rate for maximum
occupancy. A proportional-anticipatory strategy will cause
the fresh air supplied to increase as the room CO2 level
increases even though the CO2 setpoint has not been
reached. By the time the CO2 level reaches the setpoint,
the damper will be at maximum ventilation and should
maintain the setpoint.
In order to have the CO2 sensor control the economizer
damper in this manner, first determine the damper voltage
output for minimum or base ventilation. Base ventilation
is the ventilation required to remove contaminants during
unoccupied periods. The following equation may be used
to determine the percent of outside air entering the
building for a given damper position. For best results there
should be at least a 10 degree difference in outside and
return-air temperatures.
CO2 Sensor Configuration
The CO2 sensor has preset standard voltage settings that
can be selected anytime after the sensor is powered up.
(See Table 12.)
Use setting 1 or 2 for Carrier equipment. (See Table 12.)
1. Press Clear and Mode buttons. Hold at least 5
seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
Table 12 – EconoMi$er IV Sensor Usage
ECONOMI$ER IV WITH OUTDOOR AIR
DRY BULB SENSOR
Accessories Required
APPLICATION
None. The outdoor air dry bulb sensor
Outdoor Air
Dry Bulb
is factory installed.
Differential
Dry Bulb
CRTEMPSN002A00*
Single Enthalpy
HH57AC078
HH57AC078
Differential
Enthalpy
and
CRENTDIF004A00*
CO for DCV
2
Control using a
Wall-Mounted
33ZCSENCO2
CO Sensor
2
CO for DCV
2
33ZCSENCO2†
O
R
Control using a
Duct-Mounted
and
CRCBDIOX005A00††
33ZCASPCO2**
CO Sensor
2
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used
on many different base units. As such, these kits may contain parts
that will not be needed for installation.
OA
100
RA
100
+ (TR x
(TO x
)
) =TM
† 33ZCSENCO2 is an accessory CO sensor.
2
** 33ZCASPCO2 is an accessory aspirator box required for duct-
mounted applications.
†† CRCBDIOX005A00 is an accessory that contains both
33ZCSENCO2 and 33ZCASPCO2 accessories.
TO = Outdoor-Air Temperature
OA = Percent of Outdoor Air
TR = Return-Air Temperature
RA = Percent of Return Air
3. Use the Up/Down button to select the preset
number. (See Table 12.)
4. Press Enter to lock in the selection.
T
M = Mixed-Air Temperature
Once base ventilation has been determined, set the
minimum damper position potentiometer to the correct
position.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO2 sensor can be changed
anytime after the sensor is energized. Follow the steps
below to change the non-standard settings:
The same equation can be used to determine the occupied
or maximum ventilation rate to the building. For example,
an output of 3.6 volts to the actuator provides a base
ventilation rate of 5% and an output of 6.7 volts provides
the maximum ventilation rate of 20% (or base plus 15 cfm
per person). Use Fig. 64 to determine the maximum
setting of the CO2 sensor. For example, an 1100 ppm
setpoint relates to a 15 cfm per person design. Use the
1100 ppm curve on Fig. 64 to find the point when the CO2
sensor output will be 6.7 volts. Line up the point on the
1. Press Clear and Mode buttons. Hold at least 5
seconds until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD
menu and press Enter.
4. Use the Up/Down button to toggle through each of
the nine variables, starting with Altitude, until the
desired setting is reached.
38
Download from Www.Somanuals.com. All Manuals Search And Download.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode
to continue to the next variable.
3. Set the enthalpy potentiometer to D (fully CW). The
Free Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Dehumidification of Fresh Air with DCV (Demand
Controlled Ventilation) Control
DCV (Demand Controlled Ventilation) and Power
Exhaust
If normal rooftop heating and cooling operation is not
adequate for the outdoor humidity level, an energy
recovery unit and/or a dehumidification option should be
considered.
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator
should be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between
90 and 95% open.
EconoMi$er IV Preparation
This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2
kilo-ohm resistor, and a 5.6 kilo-ohm resistor which are
not supplied with the EconoMi$er IV.
4. Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the po-
tentiometer is approximately 90%. The actuator
should remain in position.
5. Turn the DCV setpoint potentiometer CW until the
DCV LED turns off. The DCV LED should turn off
when the potentiometer is approximately 9-v. The ac-
tuator should drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until
the Exhaust LED turns on. The exhaust contacts will
close 30 to 120 seconds after the Exhaust LED turns
on.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
IMPORTANT: Be sure to record the positions of all
potentiometers before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should
be off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm
resistor across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals SO and +.
Connect 1.2 kilo-ohm 4074EJM checkout resistor
across terminals SO and +.
8. Put 620-ohm resistor across terminals SR and +.
DCV Minimum and Maximum Position
9. Set minimum position, DCV setpoint, and exhaust po-
tentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential Enthalpy
To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20
and 80% open.
4. Turn the DCV Maximum Position potentiometer to
fully CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to mid-
point. The actuator should drive to between 20 and
80% open.
6. Turn the Minimum Position Potentiometer fully CW.
The actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator
should drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has
been performed.
2. Place 620-ohm resistor across SO and +.
3. Place 1.2 kilo-ohm resistor across SR and +. The
Free Cool LED should be lit.
4. Remove 620-ohm resistor across SO and +. The Free
Cool LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Single Enthalpy
To check single enthalpy:
Supply-Air Sensor Input
1. Make sure EconoMi$er IV preparation procedure has
been performed.
To check supply-air sensor input:
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
1. Make sure EconoMi$er IV preparation procedure has
been performed.
39
Download from Www.Somanuals.com. All Manuals Search And Download.
2. Set the Enthalpy potentiometer to A. The Free Cool
LED turns on. The actuator should drive to between
20 and 80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to
T1. The actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator
should drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
PRE--START--UP
!
WARNING
PERSONAL INJURY HAZARD
Failure to follow this warning could result in personal
injury or death.
1. Follow recognized safety practices and wear pro-
tective goggles when checking or servicing refri-
gerant system.
EconoMi$er IV Troubleshooting Completion
This procedure is used to return the EconoMi$er IV to
operation. No troubleshooting or testing is done by
performing the following procedure.
2. Do not operate compressor or provide any electric
power to unit unless compressor terminal cover is
in place and secured.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Do not remove compressor terminal cover until
all electrical sources are disconnected.
4. Relieve all pressure from system before touching
or disturbing anything inside terminal box if refri-
gerant leak is suspected around compressor ter-
minals.
5. Never attempt to repair soldered connection while
refrigerant system is under pressure.
6. Do not use torch to remove any component. Sys-
tem contains oil and refrigerant under pressure.
To remove a component, wear protective goggles
and proceed as follows:
3. Set DCV maximum position potentiometer to previ-
ous setting.
4. Set minimum position, DCV setpoint, and exhaust po-
tentiometers to previous settings.
5. Remove 620-ohm resistor from terminals SR and +.
6. Remove 1.2 kilo-ohm checkout resistor from termin-
als SO and +. If used, reconnect sensor from termin-
als SO and +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Recon-
nect wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P
and P1.
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from
system using both high-pressure and low
pressure ports.
c. Cut component connection tubing with tubing
cutter and remove component from unit.
11. Apply power (24 vac) to terminals TR and TR1.
d. Carefully unsweat remaining tubing stubs
when necessary. Oil can ignite when exposed
to torch flame.
WIRING DIAGRAMS
See Fig. 65-66 for typical wiring diagrams.
Proceed as follows to inspect and prepare the unit for
initial start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to,
or shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such
as broken lines, loose parts, or disconnected
wires, etc.
b. Inspect for oil at all refrigerant tubing connec-
tions and on unit base. Detecting oil generally
indicates a refrigerant leak. Leak-test all refri-
gerant tubing connections using electronic leak
detector, halide torch, or liquid-soap solution.
c. Inspect all field-wiring and factory-wiring con-
nections. Be sure that connections are completed
and tight. Be sure that wires are not in contact
with refrigerant tubing or sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin
comb.
40
Download from Www.Somanuals.com. All Manuals Search And Download.
4. Verify the following conditions:
NOTE: When the compressor is rotating in the wrong
direction, the unit will make an elevated level of noise
and will not provide cooling.
a. Make sure that condenser-fan blade are correctly
positioned in fan orifice. See Condenser-Fan
Adjustment section on page 11 for more details.
b. Make sure that air filter(s) is in place.
c. Make sure that condensate drain trap is filled
with water to ensure proper drainage.
Cooling
Set space thermostat to OFF position. To start unit, turn on
main power supply. Set system selector switch at COOL
position and fan switch at AUTO. position. Adjust
d. Make sure that all tools and miscellaneous loose
parts have been removed.
thermostat to
a
setting below room temperature.
Compressor starts on closure of contactor.
Check unit charge. Refer to Refrigerant Charge section on
page 7.
START--UP, GENERAL
Unit Preparation
Reset thermostat at a position above room temperature.
Compressor will shut off. Evaporator fan will shut off
after a 30-second delay.
Make sure that unit has been installed in accordance with
installation instructions and applicable codes.
TO SHUT OFF UNIT
Return--Air Filters
Set system selector switch at OFF position. Resetting
thermostat at a position above room temperature shuts
unit off temporarily until space temperature exceeds
thermostat setting.
Make sure correct filters are installed in unit (see
Appendix II - Physical Data). Do not operate unit without
return-air filters.
Outdoor--Air Inlet Screens
Heating
Outdoor-air inlet screen must be in place before operating
unit.
To start unit, turn on main power supply.
Compressor Mounting
Set system selector switch at HEAT position and set
thermostat at a setting above room temperature. Set fan at
AUTO position.
Compressors are internally spring mounted. Do not loosen
or remove compressor hold down bolts.
First stage of thermostat energizes the first-stage electric
heater elements; second stage energizes second-stage
electric heater elements, if installed. Check heating effects
at air supply grille(s).
Internal Wiring
Check all electrical connections in unit control boxes.
Tighten as required.
Refrigerant Service Ports
If electric heaters do not energize, reset limit switch
(located on evaporator-fan scroll) by pressing button
located between terminals on the switch.
Each unit system has two 1/4” SAE flare (with check
valves) service ports: one on the suction line, and one on
the compressor discharge line. Be sure that caps on the
ports are tight.
TO SHUT OFF UNIT - Set system selector switch at OFF
position. Resetting thermostat at a position below room
temperature temporarily shuts unit off until space
temperature falls below thermostat setting.
Compressor Rotation
On 3-phase units with scroll compressors, it is important
to be certain compressor is rotating in the proper
direction. To determine whether or not compressor is
rotating in the proper direction:
Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF
positions, respectively. Evaporator fan operates
continuously to provide constant air circulation.
1. Connect service gauges to suction and discharge pres-
sure fittings.
START--UP, PREMIERLINK CONTROLS
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
!
WARNING
If the suction pressure does not drop and the discharge
pressure does not rise to normal levels:
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal
injury or death.
1. Note that the evaporator fan is probably also rotating
in the wrong direction.
The unit must be electrically grounded in accordance
with local codes and NEC ANSI/NFPA 70 (American
National Standards Institute/National Fire Protection
Association.)
2. Turn off power to the unit and install lockout tag.
3. Reverse any two of the unit power leads.
4. Re-energize to the compressor. Check pressures.
The suction and discharge pressure levels should now
move to their normal start-up levels.
41
Download from Www.Somanuals.com. All Manuals Search And Download.
Use the Carrier network communication software to start
up and configure the PremierLink controller.
Refer to Installation Instruction 33CS-58SI for full
discussion on configuring the PremierLink control system.
Operating Sequence, Base Unit Controls
Changes can be made using the ComfortWORKSr
software, ComfortVIEWt software, Network Service
Tool, System Pilott device, or Touch Pilott device. The
System Pilot and Touch Pilot are portable interface
devices that allow the user to change system set-up and
setpoints from a zone sensor or terminal control module.
During start-up, the Carrier software can also be used to
verify communication with Premier-Link controller.
COOLING, UNITS WITHOUT ECONOMIZER — When
thermostat calls for cooling, terminals G and Y1 are
energized. The indoor-fan contactor (IFC) and
compressor contactor are energized and indoor-fan motor,
compressor, and outdoor fan starts. The outdoor fan motor
runs continuously while unit is cooling.
HEATING, UNITS WITHOUT ECONOMIZER — When
the thermostat calls for heating, terminal W1 will be
energized with 24v. The IFC and heater contactor no. 1
(HC1) are energized.
NOTE: All set-up and setpoint configurations are factory
set and field-adjustable.
For specific operating instructions, refer to the literature
provided with user interface software.
COOLING, UNITS WITH ECONOMI$ER IV — When
free cooling is not available, the compressors will be
controlled by the zone thermostat. When free cooling is
available, the outdoor-air damper is modulated by the
EconoMi$er IV control to provide a 50 to 55_F supply-air
temperature into the zone. As the supply-air temperature
fluctuates above 55 or below 50_F, the dampers will be
modulated (open or close) to bring the supply- air
temperature back within the setpoint limits.
Perform System Check--Out
1. Check correctness and tightness of all power and
communication connections.
2. At the unit, check fan and system controls for proper
operation.
3. At the unit, check electrical system and connections
of any accessory electric heater.
4. Check to be sure the area around the unit is clear of
construction dirt and debris.
5. Check that final filters are installed in the unit. Dust
and debris can adversely affect system operation.
6. Verify that the PremierLink controls are properly con-
nected to the CCN bus.
Integrated EconoMi$er IV operation on single stage units
requires a 2-stage thermostat (Y1 and Y2).
For EconoMi$er IV operation, there must be a thermostat
call for the fan (G). This will move the damper to its
minimum position during the occupied mode.
Initial Operation and Test
If the increase in cooling capacity causes the supply-air
temperature to drop below 45_F, then the outdoor-air
damper position will be fully closed. If the supply-air
temperature continues to fall, the outdoor-air damper will
close. Control returns to normal once the supply-air
temperature rises above 48_F. If optional power exhaust is
installed, as the outdoor-air damper opens and closes, the
power exhaust fans will be energized and deenergized.
Perform the following procedure:
1. Apply 24 vac power to the control.
2. Connect the service tool to the phone jack service
port of the controller.
3. Using the Service Tool, upload the controller from
address 0, 31 at 9600 baud rate. The address may be
set at this time. Make sure that Service Tool is con-
nected to only one unit when changing the address.
If field-installed accessory CO2 sensors are connected to
the EconoMi$er IV control,
a
demand controlled
Memory Reset
ventilation strategy will begin to operate. As the CO2
level in the zone increases above the CO2 setpoint, the
minimum position of the damper will be increased
proportionally. As the CO2 level decreases because of the
increase in fresh air, the outdoor-air damper will be
proportionally closed. Damper position will follow the
higher demand condition from DCV mode or free cooling
mode.
DIP switch 4 causes an E-squared memory reset to
factory defaults after the switch has been moved from
position 0 to position 1 and the power has been restored.
To enable the feature again, the switch must be put back
to the 0 position and power must be restored; this prevents
subsequent resets to factory defaults if the switch is left at
position 1.
To cause a reset of the non-volatile memory (to factory
defaults), turn the controller power off if it is on, move the
switch from position 1 to position 0, and then apply power
to the controller for a minimum of 5 seconds. At this
point, no action occurs, but the controller is now ready for
the memory to reset. Remove power to the controller
again and move the switch from position 0 to position 1.
This time, when power is applied, the memory will reset
to factory defaults. The controller address will return to
bus 0 element 31, indicating that memory reset occurred.
Damper movement from full closed to full open (or vice
versa) will take between 1-1/2 and 2-1/2 minutes.
If free cooling can be used as determined from the
appropriate changeover command (switch, dry bulb,
enthalpy curve, differential dry bulb, or differential
enthalpy), a call for cooling (Y1 closes at the thermostat)
will cause the control to modulate the dampers open to
maintain the supply air temperature setpoint at 50 to 55_F.
As the supply-air temperature drops below the setpoint
range of 50 to 55_F, the control will modulate the
42
Download from Www.Somanuals.com. All Manuals Search And Download.
outdoor-air dampers closed to maintain the proper
supply-air temperature.
compressors 1 and 2 will be cycled based on Y1 and Y2
inputs respectively.
HEATING, UNITS WITH ECONOMI$ER IV — When
the room temperature calls for heat, the heating controls
are energized as described in the Heating, Units Without
Economizer section.
Any time the compressors are running, the PremierLink
controller will lock out the compressors if the SAT
becomes too low. These user configurable settings are
found in the SERVICE configuration table:
ECONOMIZER IN OCCUPIED MODE
—
The
Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F)
(default is 55_F)
economizer logic will be energized when the unit IFC is
energized. The economizer damper will open to the
minimum position setting and remain open until the IFC is
de-energized.
Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F)
(default is 50_F)
After a compressor is locked out, it may be started again
after a normal time-guard period and the supply-air
temperature has increased at least 8_F above the lockout
setpoint.
ECONOMIZER IN UNOCCUPIED MODE — The
economizer damper will remain closed during Unoccupied
Mode periods.
Operating Sequence, PremierLink Control
Routine No. 1: If the OAT ≤ DXLOCK (OAT DX lockout
temperature) and DX Cooling Lockout is enabled when
Y1 input is energized, the economizer will be modulated
to maintain SAT at the Supply Air Setpoint (SASP) =
SATLO1 + 3_F (Supply Air Low Temp lockout for
compressor 1). When Y2 is energized, the economizer
will be modulated to control to a lower SASP = SATLO2
+ 3_F (Supply Air Low Temp lockout for compressor no.
2). Mechanical cooling is locked out and will not be
energized.
THERMOSTAT MODE — If the PremierLink controller
is configured for Thermostat mode (TSTAT), it will
control only to the thermostat inputs on J4. These inputs
can be overridden through CCN communication via the
CV_TSTAT points display table. When in this mode, the
fire safety shutdown (FSD) input cannot be used, so any
fire/life safety shutdown must be physically wired to
disable the 24 vac control circuit to the unit.
Indoor Fan — The indoor fan output will be energized
whenever there is 24 vac present on the G input. The
indoor fan will be turned on without any delay and the
economizer damper will open to its minimum position if
the unit has a damper connected to the controller. This
will also occur if the Premier-Link controller has been
configured for electric heat or heat pump operation.
Routine No. 2: If DXLOCK (or DX Cooling Lockout is
disabled) < OAT ≤ 68_F when Y1 input is energized, the
economizer will be modulated to maintain SAT at SASP =
SATLO1 + 3_F. If the SAT > SASP + 5_F and the
economizer position > 85% then the economizer will
close the to minimum position for three minutes or until
the SAT > 68_F. The economizer integrator will then be
reset and begin modulating to maintain the SASP after
stage one has been energized for 90 seconds.
Cooling — For cooling operation, there must be 24 vac
present on G. When G is active, the PremierLink
controller will then determine if outdoor conditions are
suitable for economizer cooling when an economizer
damper is available. A valid OAT, SPT (CCN space
temperature) and SAT (supply air temperature) sensor
MUST be installed for proper economizer operation. It
recommended that an outdoor or differential enthalpy
sensor also be installed. If one is not present, then a
jumper is needed on the ENTH input on J4, which will
indicate that the enthalpy will always be low. Economizer
operation will be based only on outdoor air dry bulb
temperature. The conditions are suitable when: enthalpy is
low, OAT is less than OATL High Lockout for TSTAT,
and OAT is less than OATMAX, the high setpoint for free
cooling. The default for OATL is 65_F. The default for
OATMAX is 75_F.
When Y2 is energized, the economizer will be modulated
to control to a lower supply air setpoint SASP= SATLO2
+ 3_F If the SAT > SASP + 5_F it will close the
economizer to minimum position for 3 minutes, reset the
integrator for the economizer, then start modulating the
economizer to maintain the SASP after the stage two has
been on for 90 seconds. This provides protection for the
compressor against flooded starts and allow refrigerant
flow to stabilize before modulating the economizer again.
By using return air across the evaporator coil just after the
compressor has started allows for increased refrigerant
flow rates providing better oil return of any oil washed out
during compressor start-up.
Routine No. 3: If the OAT > 68_F and the enthalpy is low
and the OAT <SPT then the economizer will open to
100% and compressors 1 and 2 will be cycled based on
Y1 and Y2 inputs respectively. If any of these conditions
are not met the economizer will go to minimum position.
When all of the above conditions are satisfied and all the
required sensors are installed, the PremierLink controller
will use the economizer for cooling. One of three different
control routines will be used depending on the
temperature of the outside air. The routines use a PID loop
to control the SAT to a supply air setpoint (SASP) based
on the error from setpoint (SASPSAT). The SASP is
determined by the routine.
If there is no call for heating or cooling, the economizer,
if available, will maintain the SASP at 70_F.
Heating — For gas or electric heat, HS1 and HS2 outputs
will follow W1 and W2 inputs respectively. The fan will
also be turned on if it is configured for electric heat.
If an economizer is not available or the conditions are not
met for the following economizer routines below, the
43
Download from Www.Somanuals.com. All Manuals Search And Download.
Heating may also be energized when an IAQ sensor
installed and has overridden the minimum economizer
damper position. If the OAT < 55_F and an IAQ sensor is
installed and the IAQ minimum position > minimum
damper position causing the SAT to decrease below the
SPT - 10_F, then the heat stages will be cycled to temper
the SAT to maintain a temperature between the SPT and
the SPT + 10_F.
heat stages to maintain the SAT between the SPT and the
SPT + 10_F.
CCN SENSOR MODE — When the PremierLink
controller is configured for CCN control, it will control
the compressor, economizer and heating outputs based its
own space temperature input and setpoints or those
received from Linkage. An optional CO2 IAQ sensor
mounted in the space or received through communications
can also influence the economizer and heating outputs.
The PremierLink controller does not have a hardware
clock so it must have another device on the CCN
communication bus broadcasting time. The controller will
maintain its own time once it has received time as long as
it has power and will send a request for time once a
minute until it receives time when it has lost power and
power is restored. The controller will control to
unoccupied setpoints until it has received a valid time.
The controller must have valid time in order to perform
any broadcast function, follow an occupancy schedule,
perform IAQ pre-occupancy purge and many other
functions as well. The following sections describe the
operation for the functions of the PremierLink controller.
Auxiliary Relay configured for Exhaust Fan — If the
Auxiliary Relay is configured for exhaust fan (AUXOUT
= 1) in the CONFIG configuration table and Continuous
Power Exhaust (MODPE) is enable in the SERVICE
configuration table then the output (HS3) will be
energized whenever the G input is on. If the MODPE is
disabled then output will be energized based on the Power
Exhaust Setpoint (PES) in the SETPOINT table.
Indoor Air Quality — If the optional indoor air quality
(IAQI) sensor is installed, the PremierLink controller will
maintain indoor air quality within the space at the
user-configured differential setpoint (IAQD) in the
CONFIG configuration table. The setpoint is the
difference between the IAQI and an optional outdoor air
quality sensor (OAQ). If the OAQ is not present then a
fixed value of 400 ppm is used. The actual space IAQ
setpoint (IAQS) is calculated as follows:
Indoor Fan — The indoor fan will be turned on whenever
any one of the following conditions are met:
S If the PremierLink controller is in the occupied mode and
ASHRAE 90.1 Supply Fan is configured for Yes in the
CONFIG table. This will be determined by its own
internal occupancy schedule if it is programmed to
follow its local schedule or broadcast its local schedule as
a global schedule, or following a global schedule
broadcast by another device.
IAQS = IAQD + OAQ (OAQ = 400 ppm if not present)
As air quality within the space changes, the minimum
position of the economizer damper will be changed also
thus allowing more or less outdoor air into the space
depending on the relationship of the IAQI to the IAQS.
The IAQ algorithm runs every 30 seconds and calculates
IAQ minimum position value using a PID loop on the
IAQI deviation from the IAQS. The IAQ minimum
position is then compared against the user configured
minimum position (MDP) and the greatest value becomes
the final minimum damper position (IQMP). If the
calculated IAQ Minimum Position is greater than the IAQ
maximum damper position (IAQMAXP) decision in the
SERVICE configuration table, then it will be clamped to
IAQMAXP value.
S If PremierLink controller is in the occupied mode and
ASHRAE 90.1 Supply Fan is configured for No and there
is a heat or cool demand (fan auto mode)
S If the PremierLink controller is in the occupied mode and
ASHRAE 90.1 Supply Fan is configured for Yes when
Linkage is active and the Linkage Coordinator device is
sending an occupied mode flag
If IAQ is configured for low priority, the positioning of
the economizer damper can be overridden by comfort
requirements. If the SAT < SASP -8_F and both stages of
heat are on for more then 4 minutes or the SAT > SASP +
5_F and both stages of cooling on for more then 4 minutes
then the IAQ minimum damper position will become 0
and the IQMP = MDP. IAQ mode will resume when the
SAT > SASP -8_F in heating or the SAT < SASP + 5_F in
cooling. If the Premier-
S When Temperature Compensated Start is active
S When Free Cool is active
S When Pre-Occupancy Purge is active
S Whenever there is a demand for cooling or heating in the
unoccupied mode
S Whenever the Remote Contact input is configured for
Remote Contact (RC_DC=1 in SERVICE table) and it is
closed or the point is forced Closed via communications
in the STATUS01 points display table (remote contact
closed = occupied, remote contact open = unoccupied)
Link controller is configured for 1 stage of heat and cool
or is only using a single stage thermostat input, this
function will not work as it requires the both Y1 and Y2
or W1 and W2 inputs to be active. In this application, it is
recommended that the user configure IAQ priority for
high.
S Whenever the H3_EX_RV point is configured for
Dehumidification (AUXOUT=5 in CONFIG table) and it
is in the unoccupied mode and the indoor RH exceeds the
unoccupied humidity setpoint
If IAQ is configured for high priority and the OAT < 55_F
and the SAT < (SPT -10_F), the algorithm will enable the
44
Download from Www.Somanuals.com. All Manuals Search And Download.
S Whenever the Supply Fan Relay point is forced On in the
STATUS01 points display table
a demand for cooling. An internal 5 to 10-minute
user-programmable time guard between modes prevents
rapid cycling between modes when used in a single zone
application. The Time Guard is lowered to 3 minutes
when Linkage is active to allow the 3Vt linkage
coordinator to have better control of the Premier-Link
controller when used as the air source for the 3V control
system.
The fan will also continue to run as long as compressors
are on when transitioning from occupied to unoccupied
with the exception of Fire Shutdown mode. If the Fire
Shutdown input point is closed or forced in the
STATUS01 points display table, the fan will be shutdown
immediately regardless of the occupancy state or demand.
Table 13 indicates the number of stages available. The
staging algorithm looks at the number of stages available
based the number of cool stages configured in the
SERVICE configuration table. The algorithm will skip the
economizer if it is not available and turn on a compressor.
The PremierLink controller has an optional Supply Fan
Status input to provide proof of airflow. If this is enabled,
the point will look for a contact closure whenever the
Supply Fan Relay is on. If the input is not enabled, then it
will always be the same state as the Supply Fan Relay.
The cooling, economizer and heating routines will use this
input point for fan status.
Table 13 – Available Cooling Stages
NUMBER OF
STAGES
1
0
2
3
(ECONOMIZER*)
Cooling — The compressors are controlled by the Cooling
Control Loop that is used to calculate the desired SAT
needed to satisfy the space. It will compare the SPT to the
Occupied Cool Setpoint (OCSP) + the T56 slider offset
(STO) when occupied and the Unoccupied Cool Setpoint
(UCSP + Unoccupied Cooling Deadband) if unoccupied
to calculate a Cooling Submaster Reference (CCSR) that
is then used by the staging algorithm (Cooling submaster
loop) to calculate the required number of cooling stages.
The economizer, if available, will be used as the first
stage of cooling in addition to the compressors. This loop
runs every minute. The following conditions must be met
in order for this algorithm to run:
Compressor 1
Compressor 2
Off
Off
Off
Off
On
Off
On
On
*
If conditions are suitable for economizer operation.
Any time the compressors are running, the PremierLink
controller will lockout the compressors if the SAT
becomes too low. These user configurable settings are
found in the SERVICE configuration table:
Compressor 1 Lockout at SAT < SATLO1 (50 to 65_F)
(default is 55_F)
Compressor 2 Lockout at SAT < SATLO2 (45 to 55_F)
(default is 50_F)
S indoor fan has been ON for at least 30 seconds
After a compressor is locked out, it may be started again
after a normal time-guard period and the supply air
temperature has increased at least 8_F above the lockout
setpoint.
S heat mode is not active and the time guard between
modes equals zero.
S mode is occupied or the Temperature Compensated Start
Dehumidification — The PremierLink controller will
provide occupied and unoccupied dehumidification
control when AUXOUT = 5 in the CONFIG table and is
installed on HVAC units that are equipped with additional
controls and accessories to accomplish this function. This
function also requires a space relative humidity sensor be
installed on the OAQ/IRH input.
or Cool mode is active
S SPT reading is available and > (OCSP + STO)
S If mode is unoccupied and the SPT > (UCSP +
Unoccupied Cooling Deadband). The indoor fan will be
turned on by the staging algorithm.
S OAT > DXLOCK or OAT DX Lockout is disabled
When in the occupied mode and the indoor relative
humidity is greater then the Occupied High Humidity
setpoint, then the H3_EX_RV output point will be
energized. When in the unoccupied mode and indoor
relative humidity is greater then the Unoccupied High
Humidity setpoint, then the H3_EX_RV output point and
supply fan output will be energized. There is a fixed 5%
hysteresis that the indoor relative humidity must drop
below the active setpoint to end the dehumidification
mode and deenergize the H3_EX_RV output. If the
PremierLink controller is in the unoccupied mode, then
the fan relay will deenergize if there is no other mode
requiring to the fan to be on. This function will not
energize mechanical cooling as a result of the indoor
relative humidity exceeding either setpoint.
If all of the above conditions are met, the CCSR will be
calculated, otherwise it is set to its maximum value and
DX stages is set to 0. If only the last condition is not true
and an economizer is available, it will be used to cool the
space.
The submaster loop uses the CCSR compared to the actual
SAT to determine the required number of capacity stages
to satisfy the load. There is a programmable minimum
internal time delay of 3 to 5 minutes on and 2 to 5 minutes
off for the compressors to prevent short cycling. There is
also a 3-minute time delay before bringing on the second
stage compressor. If the PremierLink controller is
configured for Heat Pump and AUXOUT is configured for
Reversing Valve Cool, the H3_EX_RV output will
energize 2 seconds after the first compressor is energized
and stay energized until there is a demand for heat. If
AUXOUT is configured for Reversing Valve Heat, then
the H3_EX_RV contact will be deenergized when there is
A high humidity alarm will be generated if the indoor
relative humidity exceeds the high humidity setpoint by
the amount configured in the Control Humidity Hysteresis
in the ALARMS table for 20 minutes. The alarm will
45
Download from Www.Somanuals.com. All Manuals Search And Download.
return to normal when the indoor relative humidity drops
3% below the active humidity setpoint.
into account the cooling effect that has just been turned on
and not return to the value require before the cooling was
added. This will prevent the economizer from causing
premature off cycles of compressors while maintaining the
low SAT temperature setpoint for the number of stages
active. In addition to preventing compressor short cycling,
by using return air across the evaporator coil just after the
compressor has started allows for increased refrigerant
flow rates providing for better oil return of any oil washed
out during compressor start-up.
Economizer — The economizer dampers are used to
provide free cooling and indoor air quality if optional
CO2 sensor is installed and when the outside conditions
are suitable. Temperature control is accomplished by
controlling the SAT to a certain level determined by the
Economizer PID Loop by calculating a submaster
reference (ECONSR) value. This algorithm will calculate
the submaster reference temperature (ECONSR) based on
OAT and enthalpy conditions and cooling requirements.
The ECONSR value is then passed to the Economizer
Submaster Loop, which will modulate dampers to
maintain SAT at ECONSR level.
If the OAT > 68_F and OAT < SPT and the number of DX
stages requested is > 0 by the staging algorithm, then
ECONSR is set to its minimum value 48_F and the
damper will go to 100% open.
The following conditions are required to determine if
economizer cooling is possible:
If the Auxiliary Relay is configured for exhaust fan
(AUXOUT = 1) in the CONFIG configuration table and
Continuous Power Exhaust (MODPE) is Enable in the
SERVICE configuration table, then the AUXO output
(HS3) will be energized whenever the PremierLink
controller is in the occupied mode. If the MODPE is
disabled then AUXO output will be energized based on
the Power Exhaust Setpoint (PES) in the SETPOINT
table.
S Indoor fan has been on for at least 30 seconds
S Enthalpy is low
S SAT reading is available
S OAT reading is available
S SPT reading is available
Heating — The heat stages are controlled by the Heating
Control Loop, which is used to calculate the desired SAT
needed to satisfy the space. It will compare the SPT to the
Occupied Heat Setpoint (OHSP) + the T56 slider offset
(STO) when occupied and the Unoccupied Heat Setpoint
(UHSP - Unoccupied Heating Deadband) if unoccupied to
calculate a Staged Heat Submaster Reference (SHSR).
The heat staging algorithm compares the SHSR to the
actual SAT to calculate the required number of heating
stages to satisfy the load. This loop runs every 40 seconds.
The following conditions must be met in order for this
algorithm to run:
S OAT ≤ SPT
S OAT < OATMAX (OATMAX default is 75_F)
S Economizer position is NOT forced
If any of the above conditions are not met, the ECONSR
will be set to its MAX limit of 120_F and the damper will
go to its configured minimum position. The minimum
damper position can be overridden by the IAQ routine
described later in this section.
The calculation for ECONSR is as follows:
ECONSR = PID function on (setpoint - SPT), where:
S Indoor fan has been ON for at least 30 seconds.
setpoint = ((OCSP+STO) + (OHSP+STO))/2 when
NTLO (Unoccupied Free Cool OAT Lockout) < OAT <
68_F
S Cool mode is not active and the time guard between
modes equals zero.
setpoint = (OCSP+STO) - 1 when OAT ≤ NTLO
setpoint = (OHSP+STO) + 1 when OAT ≥ 68_F
S Mode is occupied or the Temperature Compensated Start
or Heat mode is active.
The actual damper position (ECONPOS) is the result of
the following calculation. Values represented in the right
side of the equation can be found in the SERVICE
configuration table descriptions in this manual. Note that
that the OAT is taken into consideration to avoid large
changes in damper position when the OAT is cold:
S SPT reading is available and < (OHSP + STO).
S If it is unoccupied and the SPT < (UHSP - Unoccupied
Heating Deadband). The indoor fan will be turn on by the
staging algorithm.
When all of the above conditions are met, the SHSR is
calculated and up to 3 stages of heat will turned on and off
to satisfy to maintain the SAT = SHSR. If any of the
above conditions are not met, the SHSR is set to its
minimum value of 35_F.
ECONPOS = SubGain x (ECONSR-SAT) + CTRVAL
where SubGain = (OAT - TEMPBAND) / (ESG + 1)
If the OAT < DXLOCK (DX Cool Lockout setpoint) then
the damper will be modulated to maintain the SAT at the
ECONSR value.
The Staged Heat Submaster Reference (SHSR) is
calculated as follows:
If the OAT is between DXLOCK and 68_F (DXLOCK <
OAT < 68_F) and additional cooling is required, the
economizer will close the to minimum position for three
minutes, the economizer integrator will then be reset to 0
and begin modulating to maintain the SASP after the stage
has been energized for about 90 seconds. This will allow
the economizer to calculate a new ECONSR that takes
SHSR = Heating PID function on (error) where error =
(OHSP + STO) - Space Temperature
The Maximum SHSR is determined by the SATHI
configuration. If the supply-air temperature exceeds the
SATHI configuration value, then the heat stages will turn
46
Download from Www.Somanuals.com. All Manuals Search And Download.
off. Heat staging will resume after a delay to allow the
supply-air temperature to drop below the SATHI value.
configuration table. The setpoint is the difference between
the IAQI and an optional outdoor air quality sensor
(OAQ). If the OAQ is not present then a fixed value of
400 ppm is used. The actual space IAQ setpoint (IAQS) is
calculated as follows:
The maximum number of stages available is dependent on
the type of heat and the number of stages programmed in
the CONFIG and SERVICE configuration tables. Staging
will occur as follows for gas electric units, Carrier heat
pumps with a defrost board, or cooling units with electric
heat:
IAQS = IAQD + OAQ (OAQ = 400 ppm if not present)
As air quality within the space changes, the minimum
position of the economizer damper will be changed also
thus allowing more or less outdoor air into the space
depending on the relationship of the IAQI to the IAQS.
The IAQ algorithm runs every 30 seconds and calculates
IAQ minimum position value using a PID loop on the
IAQI deviation from the IAQS. The IAQ minimum
position is then compared against the user configured
minimum position (MDP) and the greatest value becomes
the final minimum damper position (IQMP). If the
calculated IAQ minimum position is greater than the IAQ
maximum damper position (IAQMAXP) decision in the
SERVICE configuration table, then it will be clamped to
IAQMAXP value.
For Heating PID STAGES = 2
HEAT STAGES = 1 (50% capacity) - energize HS1.
HEAT STAGES = 2 (100% capacity) - energize HS2.
For Heating PID STAGES = 3 and AUXOUT = HS3
HEAT STAGES = 1 (33% capacity if) - energize HS1
HEAT STAGES = 2 (66% capacity) - energize HS2
HEAT STAGES = 3 (100% capacity) - energize HS3
Staging will occur as follows For heat pump units with
AUXOUT configured as reversing valve:
For Heating PID STAGES = 2 and AUXOUT = Reversing
Valve Heat (the H3_EX_RV output will stay energized
until there is a cool demand) HEAT STAGES = 1 (50%
capacity) shall energize CMP1, CMP2, RVS.
If IAQ is configured for low priority, the positioning of
the economizer damper can be overridden by comfort
requirements. If the SPT > OCSP + 2.5 or the SPT <
OHSP - 2.5 then IAQ minimum position becomes 0 and
the IQMP = MDP. The IAQ mode will resume when the
SPT ≤ OCSP + 1.0 and SPT ≥ OHSP - 1.0.
HEAT STAGES = 2 (100% capacity) shall energize HS1
and HS2.
Heating PID STAGES = 3 and AUXOUT = Reversing
Valve Heat (the H3_EX_RV output will stay energized
until there is a cool demand)
If IAQ is configured for high priority and the OAT < 55_F
and the SAT < (SPT - 10_F), the algorithm will enable the
heat stages to maintain the SAT between the SPT and the
SPT + 10_F.
HEAT STAGES = 1 (33% capacity if) shall energize
CMP1, CMP2, RVS
IAQ Pre-Occupancy Purge — This function is designed to
purge the space of airborne contaminants that may have
accumulated 2 hours prior to the beginning of the next
occupied period. The maximum damper position that will
be used is temperature compensated for cold whether
conditions and can be pre-empted by Temperature
Compensated Start function. For pre-occupancy to occur,
the following conditions must be met:
HEAT STAGES = 2 (66% capacity) shall energize HS1
HEAT STAGES = 3 (100% capacity) shall energize HS2
If AUXOUT is configured for Reversing Valve Cool, then
the H3_EX_RV contact will be deenergized when there is
a demand for heating. The heat stages will be cycled to
temper the SAT so that it will be between the SPT and the
SPT + 10_F (SPT < SAT < (SPT + 10_F)) if:
S IAQ Pre -Occupancy Purge option is enabled in the
CONFIG configuration table
S the number of heat stages calculated is zero
S the OAT < 55_F
S Unit is in the unoccupied state
S Current Time is valid
S an IAQ sensor is installed
S Next Occupied Time is valid
S the IAQ Minimum Damper Position > minimum damper
position
S Time is within 2 hours of next Occupied period
S and the SAT < SPT -10_F.
S Time is within Purge Duration (user-defined 5 to 60
minutes in the CONFIG configuration table)
There is also a SAT tempering routine that will act as SAT
low limit safety to prevent the SAT from becoming too
cold should the economizer fail to close. One stage of
heating will be energized if it is not in the Cooling or Free
Cooling mode and the OAT is below 55_F and the SAT is
below 40_F. It will deenergize when the SAT > (SPT +
10_F).
S OAT Reading is available
If all of the above conditions are met, the economizer
damper IQMP is temporarily overridden by the
pre-occupancy damper position (PURGEMP). The
PURGEMP will be set to one of the following conditions
based on atmospheric conditions and the space
temperature:
Indoor Air Quality — If the optional indoor air quality
(IAQI) sensor is installed, the PremierLink controller will
maintain indoor air quality within the space at the user
configured differential setpoint (IAQD) in the CONFIG
S If the OAT ≥ NTLO (Unoccupied OAT Lockout
Temperature) and OAT < 65_F and OAT is less than or
47
Download from Www.Somanuals.com. All Manuals Search And Download.
equal to OCSP and Enthalpy = Low then PURGEMP =
100%.
S Unit is in unoccupied state
S Next occupied time is valid
S Current time of day is valid
S If the OAT < NTLO then PURGEMP = LTMP (Low
Temperature Minimum Position - defaults to 10%)
S Valid space temperature reading is available (from sensor
S If the OAT > 65_F or (OAT ≥ NTLO and OAT > OCSP)
or Enthalpy = High then PURGEMP = HTMP (High
Temperature Minimum Position defaults to 35%).
or linkage thermostat)
S Cool Start Bias (KCOOL) and Heat Bias Start (KHEAT)
> 0 in the CONFIG configuration table
The LTMP and HTMP are user adjustable values from 0
to 100% in the SETPOINT table. Whenever PURGEMP
The SBT is calculated by one of the following formulas
depending on temperature demand:
results in
a
number greater than 0%, the IAQ
If SPT > OCSP then SBT = (SPT - OCSP) * KCOOL
If SPT < OHSP then SPT = (OHSP - SPT) * KHEAT.
pre-occupancy purge mode will be enabled turning on the
Indoor Fan Relay and setting the economizer IQMP to the
PURGEMP value. When IAQ pre-occupancy mode is not
active PURGEMP = 0%.
The calculated start bias time can range from 0 to 255
minutes. When SBT is greater than 0 the function will
subtract the SBT from the next occupied time to calculate
a new start time. When a new start time is reached, the
Temperature Compensated Start mode is started. This
mode energizes the fan and the unit will operate as though
it is in occupied state. Once set, Temperature
Compensated Start mode will stay on until the unit returns
to occupied state. If either Unoccupied Free Cool or IAQ
Pre-Occupancy mode is active when Temperature
Compensated Start begins, their mode will end.
Unoccupied Free Cooling — Unoccupied free cool
function will start the indoor fan during unoccupied times
in order to cool the space with outside air. This function is
performed to delay the need for mechanical cooling when
the system enters the occupied period. Depending on how
Unoccupied Free Cooling is configured, unoccupied mode
can occur at any time in the unoccupied time period or 2
to 6 hours prior to the next occupied time. Once the space
has been sufficiently cooled during this cycle, the fan will
be stopped. In order to perform unoccupied free cooling
all of the following conditions must be met:
Door Switch — The Door Switch function is designed to
disable mechanical heating and cooling outputs when the
REMOCC contact input is closed (in the ON state) after a
programmed time delay. The fan will continue to operate
based on the current mode and the ASHRAE 90.1 Supply
Fan setting. The delay is programmable from 2 to 20
minutes by setting the Remote Cont/Door Switch decision
in the SERVICE table to a value equal to the number of
minutes desired. When the contact is open (in the OFF
state), the PremierLink controller will resume normal
temperature control.
S NTEN option is enabled in the CONFIG configuration
table
S Unit is in unoccupied state
S Current time of day is valid
S Temperature Compensated Start mode is not active
S COOL mode is not active
S HEAT mode is not active
S SPT reading is available
This application is designed for use in schools or other
public places where a door switch can be installed to
monitor the opening of a door for an extended period of
time. The controller will disable mechanical cooling and
heating when the door is open for a programmed amount
of time.
S OAT reading is available
S Enthalpy is low
S OAT > NTLO (with 1_F hysteresis) and < Max Free Cool
setpoint
This function can also be used to monitor a high
condensate level switch when installed on a water source
heat pump to disable mechanic cooling in case of a
plugged evaporator condensate pan drain.
If any of the above conditions are not met, Unoccupied
Free Cool mode will be stopped, otherwise, the mode will
be controlled as follows:
Linkage — The Linkage function in the PremierLink
controller is available for applications using a Linkage
thermostat or the 3V control system. If using the Linkage
thermostat, both the PremierLink controller and the stat
must be on the same CCN bus. When used as the air
source for a 3V control system, the PremierLink controller
is not required to be on the same CCN bus but it is
recommended. Linkage will be active when it is initiated
from the Linkage thermostat or the 3V Linkage
Coordinator through CCN communications and requires
no configuration. Only one device can be linked to the
PremierLink controller.
The NTFC setpoint (NTSP) is determined as NTSP =
(OCSP + OHSP) / 2
The Unoccupied Free Cool mode will be started when:
SPT > (NTSP + 2_F) and SPT > (OAT + 8_F)
The Unoccupied Free Cool mode will be stopped when:
SPT < NTSP or SPT < (OAT + 3_F)
Temperature Compensated Start — This function will run
when the controller is in unoccupied state and will
calculate early start bias time (SBT) based on space
temperature deviation from occupied setpoints in minutes
per degree. The following conditions will be met for the
function to run:
48
Download from Www.Somanuals.com. All Manuals Search And Download.
Once Linkage is active, the PremierLink controller’s own
SPT, temperature setpoints, and occupancy are ignored
and the controller will use the information provided by the
remote linkage device. The following information will be
received from the remote linked device and can be viewed
in the maintenance display table:
For more information on how the PremierLink controller
is used in conjunction with the Carrier 3V control system,
contact your CCN controls representative.
IMPORTANT: The PremierLink controller should not be
used as a linked air source in a ComfortIDt VAV system.
The ComfortID VAV system will NOT function correctly
when applied with a PremierLink controller as the air
source, resulting in poor comfort control and possible
equipment malfunction.
NOTE: The PremierLink controller can be used as an air
source in a 3V Pressure Independent (PI) System (a 3V
Linkage Coordinator with ComfortID PI Zone
Controllers), but it should not be used as an air source
with ComfortID controllers unless a 3V zone controller is
used as the Linkage Coordinator. Contact your Carrier
CCN controls representative for assistance.
S Supervisory Element
S Supervisory Bus
S Supervisory Block
S Average Occupied Heat Setpoint
S Average Occupied Cool Setpoint
S Average Unoccupied Heat Setpoint
S Average Unoccupied Cool Setpoint
S Average Zone Temp
Demand Limit — If the demand limit option is enabled,
the control will receive and accept Redline Alert and
Loadshed commands from the CCN loadshed controller.
When a redline alert is received, the control will set the
maximum stage of capacity equal to the stage of capacity
that the unit is operating at when the redline alert was
initiated.
S Average Occupied Zone Temp
S Occupancy Status
In return, the PremierLink controller will provide its SAT
and operating mode to the linked device.
It will convert its operating modes to Linkage modes. See
Table 14.
When loadshed command is received the control will
reduce capacity as shown in Table 15.
Table 14 – Linkage Modes
Table 15 – Loadshed Command — Gas and Electric
Heat Units
ROOFTOP MODE
Demand Limit
Heat
Cool or Free Cooling
IAQ Control
Temp. Compensated
Start Heat
Temp. Compensated
Start Cool
IAQ Purge
Occupied (Indoor Fan
ON)
Unoccupied Free Cool
Fire Shutdown
Factory/Field Test
Off
VALUE
N/A
3
4
N/A
LINKAGE MODE
N/A
Heating
Cooling
N/A
CURRENT CAPACITY
CMP1
NEW CAPACITY
DX Cooling OFF
CMP1
CMP1+CMP2
HS1
2
Wa r m --- u p
Heat OFF
HS1+HS2 (+HS3)
HS1
4
6
4
Cooling
Pressurization
Cooling
The controller will have a maximum demand limit timer
of 1 hour that prevents the unit from staying in load shed
or redline alert longer than 1 hour in the event the
controller loses communication with the network load
shed module. Should the maximum demand limit timer
expire prior to receiving the loadshed device command
from CCN, the control will stop demand limit mode and
return to normal operation.
5
7
1
1
Unoccupied Free Cooling
Evac
Off
Off
The PremierLink controller will generate a Linkage
Communication Failure alarm if a failure occurs for 5
consecutive minutes once a Linkage has previously been
established. It will then revert back to its own SPT,
setpoints and occupancy schedule for control. For this
reason, Carrier strongly recommends that an SPT be
installed in the space on open plenum systems or in the
return air duct of ducted return air systems to provide
FASTENER TORQUE VALUES
See Table 16 for torque values.
continued
backup
operation.
When
Linkage
communication is restored, the controller will generate a
return to normal.
49
Download from Www.Somanuals.com. All Manuals Search And Download.
Table 16 – Torque Values
Supply fan motor mounting
Supply fan motor adjustment plate
Motor pulley setscrew
1 2 0 +/ --- 1 2 in --- lb s
1 2 0 +/ --- 1 2 in --- lb s
7 2 +/ --- 5 in --- lb s
7 2 +/ --- 5 in --- lb s
7 2 +/ --- 5 in --- lb s
6 5 --- 7 0 in --- lb s
6 5 --- 7 5 in --- lb s
2 0 +/ --- 2 in --- lb s
8 4 +/ --- 1 2 in --- lb s
Fan pulley setscrew
Blower wheel hub setscrew
Bearing locking collar setscrew
Compressor mounting bolts
Condenser fan motor mounting bolts
Condenser fan hub setscrew
C08393
Fig. 65 - 50TC Typical Unit Wiring diagram - Power (A06)
50
Download from Www.Somanuals.com. All Manuals Search And Download.
51
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX I. MODEL NUMBER SIGNIFICANCE
Model Number Nomenclature
1
2
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17 18
5
0
T
C --
A
0
6
A
0
A
5
A
0
A
0
A
0
____
____
____
Unit Heat Type
50 = Elec heat pkg rooftop
Brand / Packaging
0 = Standard
1 = LTL
Tier / Model
TC = Entry tier (with Puron)
Electrical Options
A = None
Heat Size
--- = N o h e a t
C = N o n --- f u se d d isc
D = Thru the base
F = Non---fused & thru the base
Refrig. System Options
A = Standard refrigeration system
D = 2 comp. upgrade
Service Options
0 = None
1 = Unpowered convenience outlet
2 = Powered convenience outlet
Cooling Tons
04 = 3 Ton
05 = 4 Ton
06 = 5 Ton
07 = 6 Ton
Intake / Exhaust Options
A = None
B = Temp econo w/ baro relief
F = Enthalpy econo w/ baro relief
K = 2 pos damper w/ baro relief
Base Unit Controls
Sensor Options
0 = Electromechanical
A = None
1 = PremierLink DDC controller
2 = Open protocol DDC controller
B = RA smoke detector
C = SA smoke detector
D = RA & SA smoke detector
Design Rev
E = CO sensor
2
Factory assigned
F = RA smoke detector & CO
2
G = SA smoke detector & CO
Voltage
2
H = RA & SA smoke detector & CO
1 = 575/3/60
3 = 208---230/1/60
5 = 208---230/3/60
6 = 460/3/60
2
Indoor Fan Options
1 = Standard static option
2 = Medium static option
3 = High static option
Coil Options (Outdoor Coil --- Indoor Coil)
A = Al/Cu --- Al/Cu
B = P r e co a t A l/ C u --- A l/ C u
C = E co a t A l/ C u --- A l/ C u
D = E coat Al/Cu --- E coat Al/Cu
E = Cu/Cu --- Al/Cu
F = Cu/Cu --- Cu/Cu
Serial Number Format
POSITION NUMBER
1
2
3
4
5
6
7
8
9
10
TYPICAL
1
2
0
8
G
1
2
3
4
6
POSITION
1---2
DESIGNATES
Week of manufacture (fiscal calendar
Year of manufacture (“08” = 2008)
3---4
5
Manufacturing location (G = ETP, Texas, USA)
Sequential number
6---10
52
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX II. PHYSICAL DATA
3 -- 6 TONS
Physical Data (Cooling)
50TC**04
50TC**05
50TC**06
50TC**07
Refrigeration System
# Circuits / # Comp. / Type
Puron (R---410a) charge A/B (lbs)
Oil A/B (oz)
1 / 1 / Scroll
5.6
1 / 1 / Scroll
8.5
1 / 1 / Scroll
10.7
1 / 1 / Scroll
14.1
25
42
42
56
Metering Device
High---press. Trip / Reset (psig)
Low---press. Trip / Reset (psig)
Acutrol
630 / 505
54 / 117
Acutrol
630 / 505
54 / 117
Acutrol
630 / 505
54 / 117
Acutrol
630 / 505
54 / 117
Evap. Coil
Material
Coil type
Cu / Al
3/8” RTPF
2 / 15
Cu / Al
3/8” RTPF
2 / 15
Cu / Al
3/8” RTPF
4 / 15
Cu / Al
3/8” RTPF
4 / 15
Rows / FPI
2
Total Face Area (ft )
5.5
5.5
5.5
7.3
Condensate Drain Conn. Size
3/4”
3/4”
3/4”
3/4”
Evap. Fan and Motor
1 / Belt
1.2
560---854
48
1 / Centrifugal
10 x 10
1 / Belt
1.2
770---1175
48
1 / Centrifugal
10 x 10
---
---
---
---
---
---
Motor Qty / Drive Type
Max BHP
1 / Belt
1.2
560---854
48
1 / Centrifugal
10 x 10
RPM Range
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
Motor Qty / Drive Type
Max BHP
1 / Belt
1.2
560---854
48
1 / Centrifugal
10 x 10
1 / Belt
1.2
560---854
48
1 / Centrifugal
10 x 10
1 / Belt
1.2
770---1175
48
1 / Centrifugal
10 x 10
1 / Belt
2.4
1073---1457
56
1 / Centrifugal
10 x 10
RPM Range
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
Motor Qty / Drive Type
Max BHP
1 / Belt
1.2
770---1175
48
1 / Centrifugal
10 x 10
1 / Belt
1.2
770---1175
56
1 / Centrifugal
10 x 10
1 / Belt
1.5
1035---1466
56
1 / Centrifugal
10 x 10
---
---
---
---
---
---
RPM Range
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
Motor Qty / Drive Type
Max BHP
1 / Belt
1.2
1 / Belt
1.2
1 / Belt
2.4
1 / Belt
2.9
RPM Range
770---1175
48
1 / Centrifugal
10 x 10
770---1175
48
1 / Centrifugal
10 x 10
1035---1466
56
1 / Centrifugal
10 x 10
1173---1788
56
1 / Centrifugal
10 x 10
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
Motor Qty / Drive Type
Max BHP
1 / Belt
2.4
1 / Belt
2.4
1 / Belt
2.9
1 / Belt
3.7
RPM Range
1035---1466
56
1 / Centrifugal
10 x 10
1035---1466
56
1 / Centrifugal
10 x 10
1303---1687
56
1 / Centrifugal
10 x 10
1474---1788
56
1 / Centrifugal
10 x 10
Motor Frame Size
Fan Qty / Type
Fan Diameter (in)
Cond. Coil
Material
Coil type
Cu / Al
3/8” RTPF
1 / 17
Cu / Al
3/8” RTPF
2 / 17
Cu / Al
3/8” RTPF
2 / 17
Cu / Al
3/8” RTPF
2 / 17
Rows / FPI
2
Total Face Area (ft )
14.6
12.6
16.5
21.3
Cond. fan / motor
Filters
Qty / Motor Drive Type
Motor HP / RPM
1/ Direct
1/4 / 1100
22
1/ Direct
1/4 / 1100
22
1/ Direct
1/4 / 1100
22
1/ Direct
1/4 / 1100
22
Fan diameter (in)
RA Filter # / Size (in)
OA inlet screen # / Size (in)
2 / 16 x 25 x 2
1 / 20 x 24 x 1
2 / 16 x 25 x 2
1 / 20 x 24 x 1
2 / 16 x 25 x 2
1 / 20 x 24 x 1
4 / 16 x 16 x 2
1 / 20 x 24 x 1
53
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE
General Fan Performance Notes:
1. Interpolation is permissible. Do not extrapolate.
2. External static pressure is the static pressure difference between the return duct and the supply duct plus the static
pressure caused by any FIOPs or accessories.
3. Tabular data accounts for pressure loss due to clean filters, unit casing, and wet coils. Factory options and accessories
may add static pressure losses. Selection software is available, through your salesperson, to help you select the best
motor/drive combination for your application.
4. The Fan Performance tables offer motor/drive recommendations. In cases when two motor/drive combinations would
work, Carrier recommended the lower horsepower option.
5. For information on the electrical properties of Carrier’s motors, please see the Electrical information section of this
book.
6. For more information on the performance limits of Carrier’s motors, see the application data section of this book.
54
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE (cont.)
50TC**04
1 Phase
3 Ton Horizontal Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1
Field Supplied Drive
Standard Static Option
Medium Static Option
900
975
554
575
597
620
643
666
690
714
738
0.14
0.16
0.18
0.21
0.23
0.27
0.30
0.34
0.38
681
701
721
741
762
784
805
827
849
0.22
0.25
0.28
0.31
0.35
0.38
0.42
0.47
0.52
783
801
821
840
860
880
900
921
942
0.32
0.35
0.38
0.42
0.46
0.50
0.55
0.60
0.66
870
888
906
925
944
964
983
1003
1024
0.42
0.45
0.49
0.54
0.58
0.63
0.68
0.74
0.80
947
965
983
1001
1020
1039
1058
1077
1097
0.53
0.57
0.61
0.66
0.71
0.76
0.82
0.88
0.95
1050
1125
1200
1275
1350
1425
1500
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
900
975
1017
1035
1053
1071
1089
1107
1126
1145
1164
0.64
0.68
0.73
0.78
0.84
0.90
0.96
1.03
1.10
1082
1100
1117
1135
1153
1171
1189
1208
---
0.76
0.81
0.86
0.92
0.98
1.04
1.11
1.18
---
1143
1160
1177
1195
1212
1230
---
0.88
0.93
0.99
1.05
1.12
1.19
---
1200
1217
1234
1251
---
---
---
---
---
1.01
1.07
1.13
1.19
---
---
---
---
---
1254
1271
---
---
---
---
---
---
---
1.14
1.20
---
---
---
---
---
---
---
1050
1125
1200
1275
1350
1425
1500
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).
2. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
50TC**04
1 Phase
3 Ton Vertical Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4 0.6 0.8
0.2
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1
Field Supplied Drive
Standard Static Option
Medium Static Option
900
975
566
590
615
640
666
692
719
746
774
0.14
0.17
0.19
0.22
0.25
0.29
0.33
0.37
0.42
690
711
733
755
778
802
825
850
875
0.23
0.26
0.29
0.33
0.36
0.41
0.45
0.50
0.55
791
811
831
851
873
894
916
939
962
0.32
0.36
0.39
0.43
0.48
0.53
0.58
0.63
0.69
879
897
916
936
956
976
997
1019
1041
0.42
0.46
0.50
0.55
0.60
0.65
0.71
0.77
0.83
957
975
993
1012
1031
1051
1071
1091
1112
0.52
0.57
0.62
0.67
0.72
0.78
0.84
0.91
0.98
1050
1125
1200
1275
1350
1425
1500
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
900
975
1029
1046
1064
1082
1100
1119
1139
1159
1179
0.63
0.68
0.73
0.79
0.85
0.91
0.98
1.05
1.13
1095
1112
1129
1147
1165
1183
1202
1221
---
0.75
0.80
0.86
0.92
0.98
1.05
1.12
1.20
---
1157
1174
1190
1208
1225
1243
---
0.86
0.92
0.98
1.05
1.12
1.19
---
1216
1232
1248
1265
---
---
---
---
---
0.99
1.05
1.11
1.18
---
---
---
---
---
1272
1287
---
---
---
---
---
---
---
1.11
1.18
---
---
---
---
---
---
---
1050
1125
1200
1275
1350
1425
1500
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).
2. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
55
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE (cont.)
50TC**04
3 Phase
3 Ton Horizontal Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1
Field Supplied Drive
Standard Static Option
Medium Static Option
900
975
554
575
597
620
643
666
690
714
738
0.14
0.16
0.18
0.21
0.23
0.27
0.30
0.34
0.38
681
701
721
741
762
784
805
827
849
0.22
0.25
0.28
0.31
0.35
0.38
0.42
0.47
0.52
783
801
821
840
860
880
900
921
942
0.32
0.35
0.38
0.42
0.46
0.50
0.55
0.60
0.66
870
888
906
925
944
964
983
1003
1024
0.42
0.45
0.49
0.54
0.58
0.63
0.68
0.74
0.80
947
965
983
1001
1020
1039
1058
1077
1097
0.53
0.57
0.61
0.66
0.71
0.76
0.82
0.88
0.95
1050
1125
1200
1275
1350
1425
1500
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
900
975
1017
1035
1053
1071
1089
1107
1126
1145
1164
0.64
0.68
0.73
0.78
0.84
0.90
0.96
1.03
1.10
1082
1100
1117
1135
1153
1171
1189
1208
1227
0.76
0.81
0.86
0.92
0.98
1.04
1.11
1.18
1.25
1143
1160
1177
1195
1212
1230
1249
1267
1285
0.88
0.93
0.99
1.05
1.12
1.19
1.26
1.33
1.41
1200
1217
1234
1251
1269
1286
1304
1323
1341
1.01
1.07
1.13
1.19
1.26
1.33
1.41
1.49
1.58
1254
1271
1288
1305
1322
1340
1357
1375
1394
1.14
1.20
1.27
1.34
1.41
1.49
1.57
1.66
1.75
1050
1125
1200
1275
1350
1425
1500
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).
50TC**04
3 Phase
3 Ton Vertical Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4 0.6 0.8
0.2
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1
Field Supplied Drive
Standard Static Option
Medium Static Option
900
975
566
590
615
640
666
692
719
746
774
0.14
0.17
0.19
0.22
0.25
0.29
0.33
0.37
0.42
690
711
733
755
778
802
825
850
875
0.23
0.26
0.29
0.33
0.36
0.41
0.45
0.50
0.55
791
811
831
851
873
894
916
939
962
0.32
0.36
0.39
0.43
0.48
0.53
0.58
0.63
0.69
879
897
916
936
956
976
997
1019
1041
0.42
0.46
0.50
0.55
0.60
0.65
0.71
0.77
0.83
957
975
993
1012
1031
1051
1071
1091
1112
0.52
0.57
0.62
0.67
0.72
0.78
0.84
0.91
0.98
1050
1125
1200
1275
1350
1425
1500
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
900
975
1029
1046
1064
1082
1100
1119
1139
1159
1179
0.63
0.68
0.73
0.79
0.85
0.91
0.98
1.05
1.13
1095
1112
1129
1147
1165
1183
1202
1221
1241
0.75
0.80
0.86
0.92
0.98
1.05
1.12
1.20
1.28
1157
1174
1190
1208
1225
1243
1262
1280
1300
0.86
0.92
0.98
1.05
1.12
1.19
1.27
1.35
1.44
1216
1232
1248
1265
1282
1300
1318
1336
1355
0.99
1.05
1.11
1.18
1.26
1.34
1.42
1.51
1.60
1272
1287
1304
1320
1337
1354
1372
1390
1408
1.11
1.18
1.25
1.32
1.40
1.49
1.57
1.66
1.76
1050
1125
1200
1275
1350
1425
1500
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AG006) and belt (part number KR30AE039).
56
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE (cont.)
50TC**05
1 Phase
4 Ton Horizontal Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
1300
1400
1500
1600
1700
1800
1900
2000
643
674
706
738
771
804
837
871
906
0.23
0.28
0.33
0.38
0.44
0.51
0.59
0.67
0.76
762
791
820
849
879
910
941
972
1004
0.35
0.40
0.45
0.52
0.59
0.66
0.75
0.84
0.94
860
887
914
942
971
1000
1029
1059
1089
0.46
0.52
0.59
0.66
0.74
0.82
0.91
1.02
1.12
944
970
997
1024
1051
1079
1107
1136
---
0.58
0.65
0.72
0.80
0.89
0.98
1.08
1.19
---
1020
1045
1071
1097
1124
1151
---
0.71
0.78
0.86
0.95
1.04
1.14
---
---
---
---
---
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1200
1300
1400
1500
1600
1700
1800
1900
2000
1089
1114
1139
1164
1190
---
---
---
---
0.84
0.92
1.01
1.10
1.20
---
---
---
---
1153
1177
1202
---
---
---
---
---
---
0.98
1.06
1.15
---
---
---
---
---
---
1212
1.12
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
50TC**05
1 Phase
4 Ton Vertical Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4 0.6 0.8
0.2
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
1300
1400
1500
1600
1700
1800
1900
2000
666
701
737
774
811
849
887
926
965
0.25
0.30
0.36
0.42
0.49
0.57
0.65
0.75
0.86
778
809
842
875
909
943
978
1014
1050
0.36
0.42
0.48
0.55
0.63
0.72
0.81
0.92
1.03
873
902
932
962
994
1026
1059
1092
---
0.48
0.54
0.61
0.69
0.78
0.87
0.98
1.09
---
956
983
1012
1041
1071
1101
1133
---
0.60
0.67
0.75
0.83
0.93
1.03
1.14
---
1031
1057
1085
1112
1141
1170
---
0.72
0.80
0.89
0.98
1.08
1.19
---
---
---
---
---
---
---
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1126
1152
1179
1206
1235
1264
1293
1324
0.85
0.94
1.03
1.13
1.24
1.36
1.48
1.62
1.77
1165
1189
1215
---
---
---
---
---
---
0.98
1.07
1.17
---
---
---
---
---
---
1225
1.12
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied motor pulley (part number KR11HY161) and belt (part number KR30AE035).
57
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE (cont.)
50TC**05
3 Phase
4 Ton Horizontal Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
1300
1400
1500
1600
1700
1800
1900
2000
643
674
706
738
771
804
837
871
906
0.23
0.28
0.33
0.38
0.44
0.51
0.59
0.67
0.76
762
791
820
849
879
910
941
972
1004
0.35
0.40
0.45
0.52
0.59
0.66
0.75
0.84
0.94
860
887
914
942
971
1000
1029
1059
1089
0.46
0.52
0.59
0.66
0.74
0.82
0.91
1.02
1.12
944
970
997
1024
1051
1079
1107
1136
1165
0.58
0.65
0.72
0.80
0.89
0.98
1.08
1.19
1.31
1020
1045
1071
1097
1124
1151
1178
1206
1234
0.71
0.78
0.86
0.95
1.04
1.14
1.25
1.37
1.49
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
1200
1300
1400
1500
1600
1700
1800
1900
2000
1089
1114
1139
1164
1190
1217
1244
1271
1298
0.84
0.92
1.01
1.10
1.20
1.31
1.42
1.55
1.68
1153
1177
1202
1227
1252
1278
1305
1331
1358
0.98
1.06
1.15
1.25
1.36
1.48
1.60
1.73
1.87
1212
1236
1261
1285
1311
1336
1362
1388
1415
1.12
1.21
1.31
1.41
1.53
1.65
1.78
1.92
2.07
1269
1292
1316
1341
1366
1391
1416
1442
1468
1.26
1.36
1.47
1.58
1.70
1.83
1.97
2.11
2.27
1322
1346
1369
1394
1418
1443
1468
1494
---
1.41
1.52
1.63
1.75
1.87
2.01
2.15
2.31
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY181) and belt (part number
KR30AE041).
50TC**05
3 Phase
4 Ton Vertical Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4 0.6 0.8
0.2
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1200
1300
1400
1500
1600
1700
1800
1900
2000
666
701
737
774
811
849
887
926
965
0.25
0.30
0.36
0.42
0.49
0.57
0.65
0.75
0.86
778
809
842
875
909
943
978
1014
1050
0.36
0.42
0.48
0.55
0.63
0.72
0.81
0.92
1.03
873
902
932
962
994
1026
1059
1092
1127
0.48
0.54
0.61
0.69
0.78
0.87
0.98
1.09
1.21
956
983
0.60
0.67
0.75
0.83
0.93
1.03
1.14
1.26
1.39
1031
1057
1085
1112
1141
1170
1200
1231
1262
0.72
0.80
0.89
0.98
1.08
1.19
1.31
1.44
1.58
1012
1041
1071
1101
1133
1164
1197
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
High Static Option
1200
1300
1400
1500
1600
1700
1800
1900
2000
1100
1126
1152
1179
1206
1235
1264
1293
1324
0.85
0.94
1.03
1.13
1.24
1.36
1.48
1.62
1.77
1165
1189
1215
1241
1268
1295
1323
1352
1381
0.98
1.07
1.17
1.28
1.40
1.52
1.66
1.80
1.96
1225
1249
1274
1300
1326
1352
1380
1408
1436
1.12
1.22
1.32
1.44
1.56
1.69
1.84
1.99
2.15
1282
1306
1330
1355
1381
1407
1434
1461
1489
1.26
1.36
1.48
1.60
1.73
1.87
2.02
2.17
2.34
1337
1360
1384
1408
1433
1459
1485
1512
---
1.40
1.51
1.63
1.76
1.90
2.04
2.20
2.37
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AZ506), motor pulley (part number KR11HY181) and belt (part number
KR30AE041).
58
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE (cont.)
50TC**06
1 Phase
5 Ton Horizontal Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1
Field Supplied Drive
Standard Static Option
1500
1625
1750
1875
2000
2125
2250
2375
2500
724
765
806
849
892
935
980
1024
1069
0.33
0.40
0.48
0.57
0.67
0.79
0.92
1.06
1.22
837
873
909
947
986
1025
1066
1107
1149
0.45
0.53
0.61
0.71
0.82
0.94
1.08
1.23
1.39
937
969
1002
1036
1072
1108
1146
1184
---
0.59
0.67
0.76
0.86
0.98
1.11
1.25
1.41
---
1028
1056
1087
1118
1151
1185
1220
---
0.74
0.83
0.92
1.03
1.15
1.29
1.43
---
1111
1137
1165
1195
1226
1258
---
0.91
1.00
1.10
1.21
1.33
1.47
---
---
---
---
---
---
---
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1625
1750
1875
2000
2125
2250
2375
2500
1188
1213
1239
1267
---
---
---
---
---
1.09
1.18
1.28
1.40
---
---
---
---
---
1261
1284
1309
---
---
---
---
---
---
1.29
1.38
1.49
---
---
---
---
---
---
1330
---
---
---
---
---
---
---
---
1.49
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AZ606) and belt (part number KR30AE037).
50TC**06
1 Phase
5 Ton Vertical Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4 0.6 0.8
0.2
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
1500
1625
1750
1875
2000
2125
2250
2375
2500
790
837
885
934
0.40
0.48
0.58
0.69
0.81
0.95
1.11
1.28
1.48
897
940
983
0.53
0.62
0.73
0.85
0.98
1.13
1.29
1.48
---
991
0.68
0.77
0.89
1.01
1.16
1.31
1.49
---
1075
1112
1150
1189
1229
1270
---
0.83
0.94
1.06
1.19
1.34
1.50
---
1152
1187
1223
1260
---
---
---
---
---
1.00
1.11
1.24
1.38
---
---
---
---
---
1030
1070
1112
1154
1198
1242
---
1027
983
1073
1119
1166
1214
---
1033
1084
1134
1185
---
---
---
---
---
---
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1625
1750
1875
2000
2125
2250
2375
2500
1224
1257
1292
---
---
---
---
---
---
1.18
1.30
1.43
---
---
---
---
---
---
1291
1323
---
1.36
1.49
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
59
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE (cont.)
50TC**06
3 Phase
5 Ton Horizontal Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1
Field Supplied Drive
Standard Static Option
1500
1625
1750
1875
2000
2125
2250
2375
2500
724
765
806
849
892
935
980
1024
1069
0.33
0.40
0.48
0.57
0.67
0.79
0.92
1.06
1.22
837
873
909
947
986
1025
1066
1107
1149
0.45
0.53
0.61
0.71
0.82
0.94
1.08
1.23
1.39
937
969
1002
1036
1072
1108
1146
1184
1223
0.59
0.67
0.76
0.86
0.98
1.11
1.25
1.41
1.58
1028
1056
1087
1118
1151
1185
1220
1256
1293
0.74
0.83
0.92
1.03
1.15
1.29
1.43
1.60
1.77
1111
1137
1165
1195
1226
1258
1291
1325
1360
0.91
1.00
1.10
1.21
1.33
1.47
1.63
1.79
1.98
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1625
1750
1875
2000
2125
2250
2375
2500
1188
1213
1239
1267
1296
1326
1358
1390
1424
1.09
1.18
1.28
1.40
1.53
1.67
1.83
2.00
2.19
1261
1284
1309
1335
1363
1392
1421
1452
1484
1.29
1.38
1.49
1.60
1.74
1.88
2.05
2.22
2.42
1330
1352
1375
1400
1427
1454
1483
1512
1543
1.49
1.59
1.70
1.82
1.95
2.11
2.27
2.45
2.65
1395
1416
1439
1462
1488
1514
1541
1570
1599
1.71
1.81
1.92
2.04
2.18
2.34
2.51
2.69
2.89
1457
1478
1499
1522
1546
1571
1598
1625
1654
1.95
2.04
2.16
2.28
2.42
2.58
2.75
2.94
3.15
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AZ606) and belt (part number KR30AE037).
50TC**06
3 Phase
5 Ton Vertical Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4 0.6 0.8
0.2
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
1500
1625
1750
1875
2000
2125
2250
2375
2500
790
837
885
934
983
1033
1084
1134
1185
0.40
0.48
0.58
0.69
0.81
0.95
1.11
1.28
1.48
897
940
983
1027
1073
1119
1166
1214
1262
0.53
0.62
0.73
0.85
0.98
1.13
1.29
1.48
1.68
991
0.68
0.77
0.89
1.01
1.16
1.31
1.49
1.68
1.89
1075
1112
1150
1189
1229
1270
1312
1355
1399
0.83
0.94
1.06
1.19
1.34
1.50
1.69
1.89
2.10
1152
1187
1223
1260
1299
1338
1379
1420
1462
1.00
1.11
1.24
1.38
1.53
1.71
1.89
2.10
2.33
1030
1070
1112
1154
1198
1242
1287
1333
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Medium Static Option
1500
1625
1750
1875
2000
2125
2250
2375
2500
1224
1257
1292
1327
1364
1402
1441
1481
1522
1.18
1.30
1.43
1.57
1.74
1.92
2.11
2.33
2.56
1291
1323
1356
1391
1427
1463
1501
1539
1579
1.36
1.49
1.63
1.78
1.95
2.13
2.34
2.56
2.80
1354
1385
1418
1451
1486
1521
1558
1595
---
1.56
1.69
1.83
1.99
2.17
2.36
2.57
2.80
---
1414
1445
1476
1509
1542
1577
1612
---
1.77
1.90
2.05
2.21
2.39
2.59
2.81
---
1472
1501
1532
1564
1596
1630
---
1.98
2.12
2.27
2.44
2.63
2.83
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
60
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE (cont.)
50TC**07
3 Phase
6 Ton Horizontal Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.2
0.4
0.6
0.8
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1
Field Supplied Drive
Standard Static Option
1800
1950
2100
2250
2400
2550
2700
2850
3000
822
872
923
0.51
0.62
0.75
0.90
1.06
1.25
1.46
1.69
1.94
927
973
0.66
0.79
0.92
1.08
1.26
1.46
1.67
1.92
2.18
1018
1061
1104
1149
1195
1241
1289
1336
1385
0.82
0.95
1.10
1.27
1.46
1.67
1.90
2.15
2.43
1100
1140
1182
1224
1268
1312
1358
1404
1451
0.98
1.13
1.29
1.46
1.66
1.88
2.12
2.39
2.68
1174
1213
1253
1294
1336
1379
1422
1467
1512
1.15
1.31
1.48
1.66
1.87
2.10
2.35
2.63
2.93
1019
1067
1115
1164
1214
1264
1315
974
1026
1079
1132
1186
1240
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1800
1950
2100
2250
2400
2550
2700
2850
3000
1244
1281
1320
1359
1400
1441
1483
1527
1571
1.33
1.49
1.67
1.87
2.09
2.33
2.59
2.87
3.18
1308
1345
1382
1420
1460
1500
1541
1583
1626
1.51
1.68
1.87
2.08
2.31
2.55
2.83
3.12
3.44
1369
1405
1441
1479
1517
1557
1597
1638
1680
1.70
1.88
2.08
2.29
2.53
2.79
3.07
3.37
3.70
1427
1462
1498
1534
1572
1610
1650
1690
---
1.90
2.09
2.29
2.51
2.76
3.03
3.32
3.63
---
1483
1517
1552
1587
1624
1662
1701
---
2.10
2.30
2.51
2.74
2.99
3.27
3.57
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 543.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AZ406), motor pulley (part number KR11HY151) and belt (part number
KR30AE035).
50TC**07
3 Phase
6 Ton Vertical Supply
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
0.4 0.6 0.8
0.2
1.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
1
Field Supplied Drive
Standard Static Option
1800
1950
2100
2250
2400
2550
2700
2850
3000
907
965
0.63
0.77
0.93
1.11
1.32
1.55
1.81
2.09
2.41
1006
1060
1115
1170
1227
1284
1342
1400
1459
0.80
0.95
1.12
1.32
1.54
1.78
2.06
2.36
2.69
1092
1143
1195
1248
1302
1357
1412
1469
1525
0.97
1.13
1.32
1.53
1.76
2.02
2.31
2.62
2.97
1169
1218
1268
1319
1371
1424
1478
1532
1587
1.14
1.32
1.52
1.74
1.99
2.26
2.56
2.89
3.25
1239
1287
1335
1385
1435
1487
1539
1592
1646
1.32
1.51
1.72
1.96
2.22
2.50
2.82
3.16
3.53
1024
1083
1143
1203
1264
1326
1387
AVAILABLE EXTERNAL STATIC PRESSURE (IN. WG)
1.4 1.6 1.8
1.2
2.0
CFM
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
RPM
BHP
Standard Static Option
Medium Static Option
1800
1950
2100
2250
2400
2550
2700
2850
3000
1304
1350
1398
1446
1496
1546
1597
1648
---
1.51
1.71
1.93
2.18
2.45
2.75
3.07
3.43
---
1365
1410
1457
1504
1552
1601
1651
1702
---
1.69
1.91
2.14
2.40
2.68
2.99
3.33
3.70
---
1422
1467
1512
1559
1606
1654
1703
---
1.88
2.11
2.35
2.62
2.92
3.24
3.59
---
1477
1520
1565
1611
1658
1705
---
2.08
2.31
2.57
2.85
3.16
3.50
---
1528
1572
1616
1661
1707
---
---
---
---
2.28
2.52
2.79
3.09
3.40
---
---
---
---
---
---
---
---
---
---
NOTE: For more information, see General Fan Performance Notes on page 54.
Boldface indicates field---supplied drive is required.
1. Recommend using field---supplied fan pulley (part number KR11AZ406), motor pulley (part number KR11HY151) and belt (part number
KR30AE035).
61
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX III. FAN PERFORMANCE (cont.)
Pulley Adjustment
MOTOR PULLEY TURNS OPEN
MOTOR/DRIVE
UNIT
COMBO
0.0
0.5
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
5.0
Standard Static
854
825
795
766
736
707
678
648
619
589
560
Medium Static
High Static
1175
---
1135
---
1094
---
1054
---
1013
---
973
---
932
---
892
---
851
---
811
---
770
---
Standard Static
Medium Static
High Static
854
825
795
766
736
707
973
1251
707
973
---
678
932
1207
678
932
---
648
892
1164
648
892
---
619
851
1121
619
851
---
589
811
1078
589
811
---
560
770
1035
560
770
---
1175
1466
854
1135
1423
825
1094
1380
795
1054
1337
766
1013
1294
736
Standard Static
Medium Static
High Static
1175
---
1135
---
1094
---
1054
---
1013
---
Standard Static
Medium Static
High Static
854
825
795
766
736
707
973
1251
973
1251
---
678
932
1207
932
1207
---
648
892
1164
892
1164
---
619
851
1121
851
1121
---
589
811
1078
811
1078
---
560
770
1035
770
1035
---
1175
1466
1175
1466
---
1135
1423
1135
1423
---
1094
1380
1094
1380
---
1054
1337
1054
1337
---
1013
1294
1013
1294
---
Standard Static
Medium Static
High Static
Standard Static
Medium Static
High Static
1175
1466
1687
1457
1518
1788
1135
1423
1649
1419
1484
1757
1094
1380
1610
1380
1449
1725
1054
1337
1572
1342
1415
1694
1013
1294
1533
1303
1380
1662
973
1251
1495
1265
1346
1631
932
1207
1457
1227
1311
1600
892
1164
1418
1188
1277
1568
851
1121
1380
1150
1242
1537
811
1078
1341
1111
1208
1505
770
1035
1303
1073
1173
1474
Standard Static
Medium Static
High Static
NOTE: Do not adjust pulley further than 5 turns open.
--- Factor y settin gs
62
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX IV. ELECTRICAL DATA
50TC**04
3 TONS
VOLTAGE
RANGE
COMP (ea)
RLA LRA
OFM (ea)
IFM
Max
AMP Draw
5.1
V --- P h --- H z
Max
WATTS
325
FLA
1.5
TYPE
EFF at Full Load
FLA
MIN
MAX
WATTS
1000
1000
1000
1000
1000
1000
2120
1000
1000
2120
1000
2120
2120
1000
2120
2120
Std Static
Med Static
Std Static
Med Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
70%
70%
70%
70%
70%
70%
80%
70%
70%
80%
70%
80%
80%
71%
80%
80%
4.9
4.9
4.9
4.9
4.9
4.9
5.2
4.9
4.9
5.2
2.1
2.6
2.6
1.9
2.0
2.0
2 0 8 --- 1 --- 6 0
2 3 0 --- 1 --- 6 0
187
187
253
16.6
16.6
79
79
5.1
5.1
5.1
5.1
5.1
5.5
5.1
5.1
5.5
2.2
2.7
2.7
2.0
2.1
2.1
253
253
325
1.5
2 0 8 --- 3 --- 6 0
2 3 0 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0
187
187
414
518
10.4
10.4
5.8
73
73
38
37
325
325
325
325
1.5
1.5
0.8
0.6
253
506
633
3.8
50TC**05
4 TONS
VOLTAGE
RANGE
COMP (ea)
RLA LRA
OFM (ea)
IFM
V --- P h --- H z
Max
WATTS
1000
1850
1000
1850
1000
1000
2120
1000
1000
2120
1000
2120
2120
1000
2120
2120
Max
AMP Draw
5.1
WATTS
325
FLA
1.5
TYPE
EFF at Full Load
FLA
MIN
MAX
Std Static
Med Static
Std Static
Med Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
70%
78%
70%
78%
70%
70%
80%
70%
70%
80%
70%
80%
80%
71%
80%
80%
4.9
7.0
4.9
7.0
4.9
4.9
5.2
4.9
4.9
5.2
2.1
2.6
2.6
1.9
2.0
2.0
2 0 8 --- 1 --- 6 0
2 3 0 --- 1 --- 6 0
187
187
253
21.8
21.8
117
117
7.4
5.1
7.4
5.1
5.1
5.5
5.1
5.1
5.5
2.2
2.7
2.7
2.0
2.1
2.1
253
253
325
1.5
2 0 8 --- 3 --- 6 0
2 3 0 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0
187
187
414
518
13.7
13.7
6.2
83
83
41
37
325
325
325
325
1.5
1.5
0.8
0.6
253
506
633
4.8
63
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX IV. ELECTRICAL DATA (cont.)
50TC**06
5 TONS
VOLTAGE
RANGE
COMP (ea)
RLA LRA
OFM (ea)
WATTS FLA
IFM
V --- P h --- H z
Max
WATTS
1000
1850
1000
1850
1000
2120
2615
1000
2120
2615
2120
2615
2615
2120
3775
3775
Max
AMP Draw
5.1
TYPE
EFF at Full Load
FLA
MIN
MAX
Std Static
Med Static
Std Static
Med Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
70%
78%
70%
78%
70%
80%
81%
70%
80%
81%
80%
81%
81%
80%
81%
81%
4.9
7.0
4.9
7.0
4.9
5.2
7.5
4.9
5.2
7.5
2.6
3.4
3.4
2.0
2.8
2.8
2 0 8 --- 1 --- 6 0
2 3 0 --- 1 --- 6 0
187
187
253
26.2
26.2
134
134
325
325
1.5
1.5
7.4
5.1
7.4
5.1
5.5
7.9
5.1
5.5
7.9
2.7
3.6
3.6
2.1
2.9
2.9
253
253
2 0 8 --- 3 --- 6 0
2 3 0 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0
187
187
414
518
15.6
15.6
7.7
110
110
52
325
325
325
325
1.5
1.5
0.8
0.6
253
506
633
5.8
39
50TC**07
6 TONS
VOLTAGE
RANGE
COMP (ea)
RLA LRA
OFM (ea)
WATTS FLA
IFM
V --- P h --- H z
Max
WATTS
2120
2615
3775
2120
2615
3775
2120
2615
3775
2120
3775
3775
Max
AMP Draw
5.5
TYPE
EFF at Full Load
FLA
MIN
MAX
Std Static
Med Static
High Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
Std Static
Med Static
High Static
80%
81%
81%
80%
81%
81%
80%
81%
81%
80%
81%
81%
5.2
7.5
10.2
5.2
7.5
10.2
2.6
3.4
4.8
2.0
2.8
2.8
2 0 8 --- 3 --- 6 0
2 3 0 --- 3 --- 6 0
4 6 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0
187
187
414
518
253
19.0
19.0
9.7
12
12
62
50
325
325
325
325
1.5
1.5
0.8
0.6
7.9
10.7
5.5
7.9
10.7
2.7
3.6
5.0
2.1
2.9
253
506
633
7.4
2.9
64
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX IV. ELECTRICAL DATA (cont.)
MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O.
ELECTRIC HEATER
NO C.O. or UNPWR C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
DISC. SIZE
DISC. SIZE
Nom (kW)
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
None
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
9.8/13.0
None
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
9.8/13.0
None
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
None
None
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
None
15.9/18.3
23.5/27.1
31.4/36.3
37.9/43.8
46.9/54.2
None
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
None
27.2
27.2/29.0
35.5/40.0
45.4/51.5
53.5/60.9
64.8/73.9
27.2
27.2/29.0
35.5/40.0
45.4/51.5
53.5/60.9
64.8/73.9
19.4
19.4/19.4
23.1/25.6
28.8/32.3
33.5/37.8
47.9/54.3
19.4
40
40/40
40/45
50/60
60/70
70/80
40
40/40
40/45
50/60
60/70
70/80
25
25/25
25/30
30/35
35/40
50/60
25
26
26/27
33/37
42/47
49/56
60/68
26
26/27
33/37
42/47
49/56
60/68
19
19/19
21/24
26/30
31/35
44/50
19
95
95/95
95/95
95/95
95/95
95/95
95
95/95
95/95
95/95
95/95
95/95
89
89/89
89/89
89/89
89/89
89/89
89
29.1
29.1/31.4
37.9/42.4
47.8/53.9
55.9/63.3
67.1/76.3
29.1
29.1/31.4
37.9/42.4
47.8/53.9
55.9/63.3
67.1/76.3
21.3
21.3/21.8
25.5/28.0
31.1/34.6
35.9/40.1
50.3/56.6
21.3
45
45/45
45/45
50/60
60/70
70/80
45
45/45
45/45
50/60
60/70
70/80
30
30/30
30/30
35/35
40/45
60/60
30
29
29/29
35/39
44/50
51/58
62/70
29
29/29
35/39
44/50
51/58
62/70
22
22/22
23/26
29/32
33/37
46/52
22
97
97/97
97/97
97/97
97/97
97/97
97
97/97
97/97
97/97
97/97
97/97
91
91/91
91/91
91/91
91/91
91/91
91
STD
MED
STD
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
None
3.3/4.4
4.9/6.5
6.5/8.7
7.9/10.5
12.0/16.0
None
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
None
9.2/10.6
13.6/15.6
18.1/20.9
21.9/25.3
33.4/38.5
None
19.4/19.4
23.1/25.6
28.8/32.3
33.5/37.8
47.9/54.3
19.7
19.7/19.8
23.5/26.0
29.1/32.6
33.9/38.1
48.3/54.6
10.2
25/25
25/30
30/35
35/40
50/60
30
30/30
30/30
30/35
35/40
50/60
15
19/19
21/24
26/30
31/35
44/50
20
20/20
22/24
27/30
31/35
44/50
10
89/89
89/89
89/89
89/89
89/89
107
107/107
107/107
107/107
107/107
107/107
46
21.3/21.8
25.5/28.0
31.1/34.6
35.9/40.1
50.3/56.6
21.6
21.6/22.1
25.9/28.4
31.5/35.0
36.3/40.5
50.6/57.0
11.2
30/30
30/30
35/35
40/45
60/60
30
30/30
30/30
35/40
40/45
60/60
15
22/22
23/26
29/32
33/37
46/52
22
22/22
24/26
29/32
33/37
47/52
11
91/91
91/91
91/91
91/91
91/91
109
109/109
109/109
109/109
109/109
109/109
47
MED
HIGH
6.0
7.2
11.6
15
11
46
12.9
15
12
47
STD
MED
HIGH
8.8
11.5
14.0
None
6.0
8.8
11.5
14.0
10.6
13.8
16.8
None
7.2
10.6
13.8
16.8
15.9
19.9
23.6
10.2
11.6
15.9
19.9
23.6
20
20
25
15
15
20
20
25
15
18
22
10
11
15
18
22
46
46
46
46
46
46
46
46
17.1
21.1
24.9
11.2
12.9
17.1
21.1
24.9
20
25
25
15
15
20
25
25
16
19
23
11
12
16
19
23
47
47
47
47
47
47
47
47
None
6.0
8.8
None
7.2
10.6
10.7
12.3
16.5
15
15
20
11
11
15
55
55
55
11.7
13.5
17.8
15
15
20
12
12
16
56
56
56
11.5
13.8
20.5
25
19
55
21.8
25
20
56
14.0
16.8
24.3
25
22
55
25.5
30
23
56
STD
MED
HIGH
None
None
None
None
None
None
7.3
7.3
7.4
15
15
15
7
7
7
44
44
50
9.2
9.2
9.3
15
15
15
9
9
46
46
52
10
65
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX IV. ELECTRICAL DATA (cont)
MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O. (cont)
ELECTRIC HEATER
NO C.O. or UNPWR C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
DISC. SIZE
DISC. SIZE
Nom (kW)
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
None
3.3/4.4
6.5/8.7
9.8/13.0
13.1/17.4
15.8/21.0
None
None
15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
None
33.7
50
32
32/32
42/47
60/68
78/89
93/106
32
133
35.6
50
35
35/35
44/50
62/70
80/91
95/108
35
135
135/135
135/135
135/135
135/135
135/135
135
33.7/33.7
45.4/51.5
64.8/73.9
84.6/96.8
50/50
50/60
70/80
90/100
133/133
133/133
133/133
133/133
35.6/35.6
47.8/53.9
67.1/76.3
87.0/99.1
50/50
50/60
70/80
90/100
STD
100.9/115.5 110/125
133/133 103.3/117.9 110/125
133
33.7
50
35.6
50
3.3/4.4
6.5/8.7
9.8/13.0
13.1/17.4
15.8/21.0
None
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
None
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
None
4.9/6.5
6.5/8.7
12.0/16.0
15.8/21.0
None
15.9/18.3
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
None
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
None
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
None
13.6/15.6
18.1/20.9
33.4/38.5
43.8/50.5
None
33.7/33.7
45.4/51.5
64.8/73.9
84.6/96.8
50/50
50/60
70/80
90/100
32/32
42/47
60/68
78/89
93/106
23
23/24
26/30
44/50
56/64
23
23/24
26/30
44/50
56/64
23
23/24
27/30
44/50
56/64
10
133/133
133/133
133/133
133/133
35.6/35.6
47.8/53.9
67.1/76.3
87.0/99.1
50/50
50/60
70/80
90/100
35/35
44/50
62/70
80/91
95/108
25
25/26
29/32
46/52
58/66
25
25/26
29/32
46/52
58/66
26
26/26
29/32
47/52
59/66
12
135/135
135/135
135/135
135/135
135/135
101
101/101
101/101
101/101
101/101
101
101/101
101/101
101/101
101/101
119
119/119
119/119
119/119
119/119
50
MED
100.9/115.5 110/125
133/133 103.3/117.9 110/125
23.5
23.5/25.6
28.8/32.3
47.9/54.3
60.9/69.3
23.5
23.5/25.6
28.8/32.3
47.9/54.3
60.9/69.3
23.8
23.8/26.0
29.1/32.6
48.3/54.6
61.3/69.6
10.7
30
30/30
30/35
50/60
70/70
30
30/30
30/35
50/60
70/70
30
30/30
30/35
50/60
70/70
15
99
99/99
99/99
99/99
99/99
99
99/99
99/99
99/99
99/99
117
117/117
117/117
117/117
117/117
49
25.4
25.5/28.0
31.1/34.6
50.3/56.6
63.3/71.6
25.4
25.5/28.0
31.1/34.6
50.3/56.6
63.3/71.6
25.7
25.9/28.4
31.5/35.0
50.6/57.0
63.6/72.0
11.7
30
30/30
35/35
60/60
70/80
30
30/30
35/35
60/60
70/80
30
30/30
35/40
60/60
70/80
15
STD
MED
HIGH
STD
6.0
11.5
7.2
13.8
11.6
19.9
15
20
11
18
49
49
12.9
21.1
15
25
12
19
50
50
14.0
16.8
23.6
25
22
49
24.9
25
23
50
23.0
27.7
37.3
40
34
49
38.5
40
35
50
None
None
10.7
15
10
49
11.7
15
12
50
6.0
7.2
11.6
15
11
49
12.9
15
12
50
MED
HIGH
11.5
14.0
23.0
None
6.0
11.5
13.8
16.8
27.7
None
7.2
13.8
19.9
23.6
37.3
11.2
12.3
20.5
20
25
40
15
15
25
18
22
34
11
11
19
49
49
49
58
58
58
21.1
24.9
38.5
12.2
13.5
21.8
25
25
40
15
15
25
19
23
35
12
12
20
50
50
50
59
59
59
14.0
16.8
24.3
25
22
58
25.5
30
23
59
23.0
27.7
37.9
40
35
58
39.1
40
36
59
STD
MED
HIGH
None
None
None
None
None
None
8.5
8.5
8.6
15
15
15
8
8
9
44
44
50
10.4
10.4
10.5
15
15
15
11
11
11
46
46
52
66
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX IV. ELECTRICAL DATA (cont)
MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O. (cont)
ELECTRIC HEATER
NO C.O. or UNPWR C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
DISC. SIZE
DISC. SIZE
Nom (kW)
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
None
4.9/6.5
6.5/8.7
9.8/13.0
13.1/17.4
15.8/21.0
None
4.9/6.5
6.5/8.7
9.8/13.0
13.1/17.4
15.8/21.0
None
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
None
23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
None
23.5/27.1
31.4/36.3
46.9/54.2
62.8/72.5
75.8/87.5
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
39.2
60
37
37/37
42/47
60/68
78/89
93/106
40
40/40
44/50
62/70
80/91
95/109
25
25/25
31/35
44/50
56/64
69/79
26
150
41.1
60
40
40/40
44/50
62/70
80/91
95/108
42
42/42
46/52
64/73
82/94
97/111
27
27/27
33/37
46/52
58/66
71/81
28
152
152/152
152/152
152/152
152/152
152/152
177
177/177
177/177
177/177
177/177
177/177
128
128/128
128/128
128/128
128/128
128/128
146
39.2/40.0
45.4/51.5
64.8/73.9
84.6/96.8
60/60
60/60
70/80
90/100
150/150
150/150
150/150
150/150
41.1/42.4
47.8/53.9
67.1/76.3
87.0/99.1
60/60
60/60
70/80
90/100
STD
MED
STD
100.9/115.5 110/125
150/150 103.3/117.9 110/125
175
175/175
175/175
175/175
175/175
41.3
60
43.2
60
41.3/42.6
48.0/54.1
67.4/76.5
87.3/99.4
60/60
60/60
70/80
90/100
43.2/45.0
50.4/56.5
69.8/78.9
89.6/101.8
60/60
60/60
70/80
90/110
103.5/118.1 110/125
175/175 105.9/120.5 110/125
25.9
25.9/25.9
33.5/37.8
47.9/54.3
60.9/69.3
75.1/85.9
26.2
30
30/30
40/40
50/60
70/70
80/90
40
126
126/126
126/126
126/126
126/126
126/126
144
27.8
27.8/28.0
35.9/40.1
50.3/56.6
63.3/71.6
77.5/88.3
28.1
40
40/40
40/45
60/60
70/80
80/90
40
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
26.2/26.2
33.9/38.1
48.3/54.6
61.3/69.6
75.5/86.3
28.5
28.5/28.9
36.8/41.0
51.1/57.5
64.1/72.5
78.4/89.1
12.5
40/40
40/40
50/60
70/70
80/90
40
40/40
40/45
60/60
70/80
80/90
20
26/26
31/35
44/50
56/64
69/79
28
28/28
34/38
47/53
59/67
72/82
12
144/144
144/144
144/144
144/144
144/144
170
170/170
170/170
170/170
170/170
170/170
60
28.1/28.4
36.3/40.5
50.6/57.0
63.6/72.0
77.9/88.6
30.4
30.4/31.3
39.1/43.4
53.5/59.9
66.5/74.9
80.8/91.5
13.5
40/40
40/45
60/60
70/80
80/90
45
45/45
45/45
60/60
70/80
90/100
20
28/28
33/37
47/52
59/66
72/82
30
30/30
36/40
49/55
61/69
74/84
13
146/146
146/146
146/146
146/146
146/146
172
172/172
172/172
172/172
172/172
172/172
61
MED
HIGH
STD
6.0
11.5
14.0
7.2
13.8
16.8
12.5
19.9
23.6
20
20
25
12
18
22
60
60
60
13.5
21.1
24.9
20
25
25
13
19
23
61
61
61
23.0
27.7
37.3
40
34
60
38.5
40
35
61
25.5
30.7
41.0
45
38
60
42.3
45
39
61
None
None
13
20
13
69
14
20
14
70
6.0
7.2
13.0
20
13
69
14.0
20
14
70
11.5
14.0
23.0
25.5
None
6.0
11.5
14.0
13.8
16.8
27.7
30.7
None
7.2
13.8
16.8
20.5
24.3
37.9
41.6
13.8
13.8
21.5
25.3
25
25
40
45
20
20
25
30
19
22
35
38
14
14
20
23
69
69
69
69
82
82
82
82
21.8
25.5
39.1
42.9
14.8
14.8
22.8
26.5
25
30
40
45
20
20
25
30
20
23
36
39
15
15
21
24
70
70
70
70
83
83
83
83
MED
HIGH
23.0
27.7
38.9
40
36
82
40.1
45
37
83
25.5
30.7
42.6
45
39
82
43.9
45
40
83
STD
MED
HIGH
None
None
None
None
None
None
9.8
9.9
15
15
15
10
10
11
46
52
63
11.7
11.8
12.6
15
15
15
12
12
13
48
54
65
10.7
67
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX IV. ELECTRICAL DATA (cont)
MCA/MOCP DETERMINATION NO C.O. OR UNPWRD C.O. (cont)
ELECTRIC HEATER
NO C.O. or UNPWR C.O.
NO P.E.
w/ P.E. (pwrd fr/unit)
IFM
TYPE
DISC. SIZE
DISC. SIZE
Nom (kW)
FLA
MCA
MOCP
MCA
MOCP
FLA
LRA
FLA
LRA
None
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
4.9/6.5
7.9/10.5
12.0/16.0
15.8/21.0
19.9/26.5
None
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
13.6/15.6
21.9/25.3
33.4/38.5
43.8/50.5
55.2/63.8
None
30.5
30.5/30.5
33.9/38.1
48.3/54.6
61.3/69.6
75.5/86.3
32.8
32.8/32.8
36.8/41.0
51.1/57.5
64.1/72.5
78.4/89.1
32.8
32.8/32.8
36.8/41.0
51.1/57.5
64.1/72.5
78.4/89.1
15.5
45
45/45
45/45
50/60
70/70
80/90
50
50/50
50/50
60/60
70/80
80/90
50
50/50
50/50
60/60
70/80
80/90
25
30
30/30
31/35
44/50
56/64
69/79
32
32/32
34/38
47/53
59/67
72/82
32
32/32
34/38
47/53
59/67
72/82
15
157
157/157
157/157
157/157
157/157
157/157
183
183/183
183/183
183/183
183/183
183/183
183
183/183
183/183
183/183
183/183
183/183
79
32.4
32.4/32.4
36.3/40.5
50.6/57.0
63.6/72.0
77.9/88.6
34.7
34.7/34.7
39.1/43.4
53.5/59.9
66.5/74.9
80.8/91.5
34.7
34.7/34.7
39.1/43.4
53.5/59.9
66.5/74.9
80.8/91.5
16.5
50
50/50
50/50
60/60
70/80
80/90
50
50/50
50/50
60/60
70/80
90/100
50
50/50
50/50
60/60
70/80
90/100
25
32
32/32
33/37
47/52
59/66
72/82
34
34/34
36/40
49/55
61/69
74/84
34
34/34
36/40
49/55
61/69
74/84
16
159
159/159
159/159
159/159
159/159
159/159
185
185/185
185/185
185/185
185/185
185/185
185
185/185
185/185
185/185
185/185
185/185
80
STD
MED
HIGH
STD
6.0
11.5
14.0
7.2
13.8
16.8
15.5
20.5
24.3
25
25
25
15
19
22
79
79
79
16.5
21.8
25.5
25
25
30
16
20
23
80
80
80
23.0
27.7
37.9
40
35
79
39.1
40
36
80
25.5
30.7
41.6
45
38
79
42.9
45
39
80
None
None
16.3
25
16
92
17.3
25
17
93
6.0
7.2
16.3
25
16
92
17.3
25
17
93
11.5
14.0
23.0
25.5
None
6.0
11.5
14.0
13.8
16.8
27.7
30.7
None
7.2
13.8
16.8
21.5
25.3
38.9
42.6
17.3
17.3
22.8
26.5
25
30
40
45
25
25
25
30
20
23
36
39
17
17
21
24
92
92
92
92
101
101
101
101
22.8
26.5
40.1
43.9
18.3
18.3
24.0
27.8
25
30
45
45
25
25
25
30
21
24
37
40
18
18
22
26
93
93
93
93
102
102
102
102
MED
HIGH
23.0
27.7
40.1
45
37
101
41.4
45
38
102
25.5
30.7
43.9
45
40
101
45.1
50
42
102
STD
MED
HIGH
None
None
None
None
None
None
11.9
12.7
12.7
15
20
20
12
12
12
63
74
74
13.8
14.6
14.6
20
20
20
14
15
15
65
76
76
68
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX V. WIRING DIAGRAM LIST
Wiring Diagrams
50TC
DRAWING NUMBER.REV
Size
Voltage
CONTROL
POWER
208/230---1---60
208/230---3---60
460---3---60
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500212.04
48TM500983.02
48TM500211.08
48TM500214.07
48TM500214.07
48TM500214.07
48TM500211.08
48TM500214.07
48TM500214.07
48TM500214.07
48TM500211.08
48TM500214.07
48TM500214.07
48TM500214.07
48TM500214.07
48TM500214.07
48TM500214.07
A04
575---3---60
208/230---1---60
208/230---3---60
460---3---60
A05
A06
575---3---60
208/230---1---60
208/230---3---60
460---3---60
575---3---60
208/230---3---60
460---3---60
A07
All
575---3---60
PremierLink*
NOTE: Component arrangement on Control; Legend on Power Schematic
*
The PremierLink label is an overlay for the Control label for the specific base model. Both labels
(Control and PremierLink) are required to display a complete unit control schematic with PremierLink Option
69
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX VI. MOTORMASTER SENSOR LOCATIONS
C08259
C08261
Fig. 67 - 50TC*A04 Outdoor Circuiting
Fig. 69 - 50TC*A07 Outdoor Circuiting
C08260
C08262
Fig. 68 - 50TC*A05/06 Outdoor Circuiting
Fig. 70 - 50TC*A08 Outdoor Circuiting
70
Download from Www.Somanuals.com. All Manuals Search And Download.
APPENDIX VI. (cont) MOTORMASTER SENSOR LOCATIONS
C08263
Fig. 71 - 50TC*A09/12 Outdoor Circuiting
71
Download from Www.Somanuals.com. All Manuals Search And Download.
Catalog No: 50TC---1SM
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 05/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: NEW
72
Download from Www.Somanuals.com. All Manuals Search And Download.
START-UP CHECKLIST
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:
DATE:
SERIAL NO.:
TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
j
j
j
j
j
j
j
j
j
VERIFY THAT JOBSITE VOLTAGE AGREES WITH VOLTAGE LISTED ON RATING PLATE
VERIFY THAT ALL PACKAGING MATERIALS HAVE BEEN REMOVED FROM UNIT
REMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLATION INSTRUCTIONS
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTALLATION INSTRUCTIONS
CHECK REFRIGERANT PIPING FOR INDICATIONS OF LEAKS; INVESTIGATE AND REPAIR IF NECESSARY
CHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
CHECK THAT RETURN (INDOOR) AIR FILTERS ARE CLEAN AND IN PLACE
VERIFY THAT UNIT INSTALLATION IS LEVEL
CHECK FAN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
j
CHECK TO ENSURE THAT ELECTRICAL WIRING IS NOT IN CONTACT WITH REFRIGERANT LINES
OR SHARP METAL EDGES
j CHECK PULLEY ALIGNMENT AND BELT TENSION PER INSTALLATION INSTRUCTIONS
III. START-UP
ELECTRICAL
SUPPLY VOLTAGE
COMPRESSOR AMPS
INDOOR-FAN AMPS
L1-L2
L1
L1
L2-L3
L2
L2
L3-L1
L3
L3
TEMPERATURES
OUTDOOR-AIR TEMPERATURE
RETURN-AIR TEMPERATURE
COOLING SUPPLY AIR
DB
DB
DB
WB
WB
PRESSURES (Cooling Mode)
F
REFRIGERANT SUCTION
PSIG
PSIG
F
REFRIGERANT DISCHARGE
j
VERIFY THAT 3-PHASE FAN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION.
j
j
VERIFY THAT 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS
GENERAL
j SET ECONOMIZER MINIMUM VENT AND CHANGEOVER SETTINGS TO MATCH JOB REQUIREMENTS
(IF EQUIPPED)
Catalog No: 50TC---1SM
Copyright 2008 Carrier Corp. S 7310 W. Morris St. S Indianapolis, IN 46231
Printed in U.S.A.
Edition Date: 04/08
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
Replaces: NEW
73
Download from Www.Somanuals.com. All Manuals Search And Download.
|