Carrier Air Conditioner PC 111 User Manual

48FK,JK034-104  
48FM078-104  
50FK,FY,JK,JY034-104  
50FM,FS078-104  
Variable-Air Volume Rooftop Units  
Controls Operation,  
and Troubleshooting  
CONTENTS  
Page  
Page  
Control From Remote Building Management  
SAFETY CONSIDERATIONS. . . . . . . . . . . . . . . . . . . . . . 2  
System (BMS). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19  
GENERAL. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13  
Rooftop Information. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
VAV Control System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Processor Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3  
• P1 — SUPPLY-AIR SET POINT  
• OCCUPIED/UNOCCUPIED  
• NIGHT SETBACK CONTROL  
• UNIT SUPPLY AIR SET POINT ADJUSTMENT  
• DEMAND UNIT (1-STAGE OR 2-STAGE)  
• SUPPLY DUCT PRESSURE SET POINT ADJUSTMENT  
• EXTERNAL ALARM SIGNAL  
• P2 — ECONOMIZER POSITION  
• P3 — RESET LIMIT  
• REMOTE ECONOMIZER CONTROL  
Smoke Control Modes. . . . . . . . . . . . . . . . . . . . . . . . . . . 21  
• FIRE SHUTDOWN MODE  
• P4 — DEMAND LIMIT  
• P5 — ECONOMIZER MINIMUM POSITION  
• P6 WARM-UP SET POINT  
• PRESSURIZATION MODE  
• P7 — SASP RESET TEMPERATURE  
• EVACUATION MODE  
• PROCESSOR BOARD OUTPUTS  
• CONFIGURATION HEADER AND DIP SWITCH  
ASSEMBLY  
Relay Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Display Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
Thermistors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5  
• T1 — SUPPLY-AIR TEMPERATURE THERMISTOR  
• T2 — RETURN-AIR TEMPERATURE THERMISTOR  
• T3 — SATURATED CONDENSING TEMPERATURE,  
CIRCUIT 1  
• SMOKE PURGE MODE  
• INSTALLATION  
• CONFIGURATION  
• OPERATING SEQUENCE  
Air Pressure Tubing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
• INLET GUIDE VANES  
• SUPPLY FAN VARIABLE FREQUENCY DRIVE  
• MODULATING POWER EXHAUST  
START-UP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-31  
Initial Check. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25  
Configuration Header . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
DIP Switches. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26  
Adjusting Set Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Potentiometers. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27  
Supply Fan Control with IGV Option . . . . . . . . . . . . 28  
Supply Fan Control with VFD Option . . . . . . . . . . . . 28  
Modulating Power Exhaust Option or  
Accessory) (48FK,JK and 50FK,JK Units) . . . . . 30  
High Capacity Power Exhaust  
(48FM and 50FM,FS Units) . . . . . . . . . . . . . . . . . . . . 30  
START UNIT. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31-34  
Quick Test Program. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31  
• T4 — SATURATED CONDENSING TEMPERATURE,  
CIRCUIT 2  
• T10 — RESET TEMPERATURE  
Compressor Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
• CONTROL RELAY (CR)  
Accessory Board. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7  
• P3 — RESET LIMIT  
• P5 — ECONOMIZER MINIMUM POSITION  
• P6 — MORNING WARM-UP TEMPERATURE  
Single-Step Demand Unit. . . . . . . . . . . . . . . . . . . . . . . . . 7  
Demand Limit Control Module (DLCM) . . . . . . . . . . . 7  
Economizer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10  
• ENTHALPY CONTROL  
• DIFFERENTIAL ENTHALPY  
OPERATING INFORMATION. . . . . . . . . . . . . . . . . . 34-44  
Digital Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34  
• CODES 0 THROUGH 8, CAPACITY STEPS  
• CODES 20 THROUGH 30 AND 88, OPERATIONAL  
STATUS  
Supply Fan Variable Frequency Drive (VFD). . . . . 12  
High Capacity Modulating Power  
Exhaust Variable Frequency Drive . . . . . . . . . . . . 12  
Temperature Reset. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
CONTROLS INSTALLATION. . . . . . . . . . . . . . . . . . 13-25  
Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13  
• NIGHT SETBACK THERMOSTAT  
• SPACE TEMPERATURE RESET ACCESSORY  
(50DJ900021)  
• CODES 51 THROUGH 87, DIAGNOSTIC  
INFORMATION  
Operating Sequence . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35  
• SIZE 034, 038 AND 048-088 UNITS  
• SIZE 044 UNITS  
• SIZE 104 UNITS  
Space Temperature Reset . . . . . . . . . . . . . . . . . . . . . . 13  
• INSTALLATION  
Head Pressure Control . . . . . . . . . . . . . . . . . . . . . . . . . . 36  
Supply Fan Control with IGV . . . . . . . . . . . . . . . . . . . . 38  
Supply Fan Control with VFD. . . . . . . . . . . . . . . . . . . . 38  
Modulating Power Exhaust (48FK,JK and  
50FK,JK Units Option or Accessory). . . . . . . . . . 38  
High Capacity Modulating Power Exhaust  
(48FM and 50FM,FS Units) . . . . . . . . . . . . . . . . . . . . 38  
Unit Staging. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38  
• CONFIGURATION  
• OPERATING SEQUENCE  
Demand Limit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18  
• SINGLE-STEP DEMAND LIMIT  
• TWO-STEP DEMAND LIMIT  
• INSTALLATION  
• CONFIGURATION  
• OPERATING SEQUENCE  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 534-763 Printed in U.S.A. Form 48/50F,J-3T Pg 1 3-00 Replaces: 48/50F,J-1T  
Book 1  
1
Tab 1a 1b  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The VAV control system monitors and controls the follow-  
ing functions of the rooftop unit:  
Several status switches are also monitored. These switches  
are connected to the processor at pin terminal connector J2. See  
Fig. 3 and Table 2.  
In addition to the unit status switch inputs, the processor  
board also accepts inputs from several potentiometers. These  
potentiometers control various operational characteristics of  
the system. Inputs are received by the processor through pin  
terminal connector J3. See Fig. 4.  
supply-air temperature (unit capacity)  
morning warm-up or electric heat (if equipped)  
head pressure control, fan cycling  
economizer position  
diagnostic display  
unit check-out (quick test)  
supply air temperature reset (if equipped)  
demand limiting (if equipped)  
Table 1 — Pin Terminal Connector J1  
Thermistor Inputs  
Processor Board — The processor board, shown in  
Fig. 1, contains the logic and the necessary hardware to drive  
the outputs and the display board. The processor board is en-  
closed by a sheet metal cover and a heater. The heater is con-  
trolled by a thermostat to keep the processor temperature above  
32 F (0° C). All electrical connections are made to the proces-  
sor board through wire and ribbon cables.  
CONNECTOR J1  
TERMINAL NO.  
TEMPERATURE  
INPUT  
Reset Temperature*  
Saturated Condensing  
Temp., Circuit 2  
Saturated Condensing  
Temp., Circuit 1  
UNIT SIZE  
034-104  
1,2  
T10  
14,15  
T4  
16,17  
T3  
Several temperature inputs are connected to the processor.  
There are either 4 or 5 thermistors (depending on the field-  
installed accessories) which input temperature data into the  
processor through pin terminal connector J1. See Table 1 and  
Fig. 2.  
18,19  
20,21  
Return-Air Temperature  
Supply-AirTemperature  
T2  
T1  
LEGEND  
T — Thermistor  
*If equipped with accessory temperature reset package.  
NOTE: Terminal numbers 3-13 are not used on these units.  
LEGEND  
DIP  
EPPOM — Erasable, Programmable Read-Only Memory  
EXV — Electronic Expansion Valve  
Dual In-Line Package  
*EPROM HT204485-1-XX where “XX” is the current revision  
number.  
NOTE: Processor Board is positioned in unit with J3 and J10  
connections at the bottom.  
Do not remove label covering EPROM. Removal causes pro-  
gram to be erased.  
Fig. 1 — Processor Board  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND  
CR  
EC  
Control Relay  
Enthalpy Control  
LEGEND  
LPS — Low-Pressure Switch  
T
Thermistor  
Field Wiring  
Accessory  
Fig. 3 — Pin Terminal Connector J2  
Status Switch Inputs  
Fig. 2 — Pin Terminal Connector J1  
Thermistor Inputs  
Table 2 — Pin Terminal Connector J2  
Status Switch Inputs  
CONNECTOR J2  
TERMINAL NO.  
UNIT SIZE  
034-104  
STATUS SWITCH  
Oil Pressure,  
Circuit 2  
Oil Pressure,  
Circuit 1  
Loss of Charge,  
Circuit 2  
1,2  
Jumpered  
Jumpered  
LPS2  
3,4  
7,8  
Loss of Charge,  
Circuit 1  
9,10  
LPS1  
Economizer  
Changeover  
Compressor Fault  
Signal  
Compressor Fault  
Signal  
13,14  
15,20  
15,24  
LEGEND  
EC  
CR2  
CR1  
LEGEND  
IN  
Input  
Factory Wiring  
Field Wiring  
Accessory  
CR — Control Relay  
P
Potentiometer  
Return  
EC — Enthalpy Control  
RNT  
SW  
LPS — Low-Pressure Switch  
Switch  
NOTE: Terminal numbers 5, 6, 11, 12, 16-19, and 21-23 are not used  
on these units.  
Fig. 4 — Pin Terminal Connector J3  
Potentiometer Inputs  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
All of the potentiometers must be set before the unit is start-  
ed in order for the unit to function properly. See Start Up, Po-  
tentiometers section on page 27 for information on establishing  
set points. Each of the potentiometers has a valid range that is  
used by the control. The valid range is defined as the potenti-  
ometer’s resistance value that the control will not consider to  
be in error. This is usually between 10% and 90% of the poten-  
tiometer’s total resistance. The control has been programmed  
to accept an operational range for the potentiometer, which  
may not be the same as the valid range.  
CONFIGURATION HEADER AND DIP SWITCH ASSEM-  
BLY — The processor board is programmed to control a vari-  
ety of air conditioning units. To tailor the processor to the par-  
ticular unit being controlled, 2 devices are used. One is the  
configuration header, and the other is the DIP switch assembly.  
The configuration header (part no. 30GB660001) is a series  
of 8 small wires that are broken or unbroken in a pattern to in-  
dicate several unique characteristics of the unit. The configura-  
tion header is factory set and should not be changed. Changing  
the factory setting may cause the unit to malfunction.  
The DIP switches configure the unit for several field-in-  
stalled options, as well as for several other options that may be  
unique to the unit. The DIP switches are located under a plastic  
enclosure which must be removed for access. The switches can  
be field adjusted, but must be adjusted only when the unit con-  
trol circuit breaker is off.  
The potentiometer locations and functions are as follows:  
P1 — SUPPLY-AIR SET POINT — This potentiometer is  
located on the display board. The supply-air set point is the  
cooling mode control temperature which the VAV control sys-  
tem will attempt to maintain at Thermistor T1 by control of  
economizer position and/or cycling unloaders and compres-  
sors.  
P2 — ECONOMIZER POSITION — Economizer feedback  
potentiometer is located on the economizer motor. The micro-  
processor is programmed to indicate an alarm if the travel dur-  
ing initialization is less than 10% of the total potentiometer’s  
resistance. An alarm condition will also be signaled if the  
potentiometer fails during operation, indicating that the  
damper blades are stuck. If either situation occurs, the proces-  
sor will try to drive the economizer dampers closed.  
P3 — RESET LIMIT — This potentiometer is located on the  
accessory board (provided standard from the factory) in the  
unit main control box and establishes the maximum amount of  
reset that can be applied to the supply-air set point (P1). Reset  
is limited by the P1 default of 70 F. This potentiometer is used  
only when accessory, field-installed temperature reset is used.  
If temperature reset is used, DIP (dual, in-line package) switch  
2 must be in the ON position.  
P4 — DEMAND LIMIT — This potentiometer is located near  
TRAN4 in the unit control box. The demand limit potentiome-  
ter is used only if accessory, field-installed demand limit is  
used, and if DIP switch 5 is in the ON position. For single-step  
demand limit, a field-installed 5 to 20 Kohm potentiometer and  
switch must be used.  
P5 — ECONOMIZER MINIMUM POSITION — This  
potentiometer is on the accessory board (provided standard  
from the factory) located in the unit main control box. This  
potentiometer specifies the minimum opening position for the  
optional economizer. If a fault condition is detected by the pro-  
cessor, an alarm condition will be signaled and the economizer  
dampers will close.  
P6 — WARM-UP SET POINT — This potentiometer is on  
the accessory board (provided standard from the factory)  
located in the unit main control box. This potentiometer estab-  
lishes the set point temperature for the Morning Warm-Up  
function. When the temperature is reached, Morning Warm-Up  
is terminated and VAV operation begins. DIP switch 4 must be  
in the ON position if morning warm-up heat is to be used.  
Relay Board — The relay board is used to control 24-v  
and 115-v loads. See Fig. 5. The relay board is connected to the  
processor board by a ribbon cable at pin J9. Electrical connec-  
tions to the relay board are made through pins J5 (115 v) and J6  
(24 v). The relay board has eight 24-v relays and five 115-v re-  
lays. See Table 3.  
Display Board — The display board is located in the  
main unit control box and is connected to the J10 port of the  
processor board through a ribbon cable. The display board con-  
tains the supply-air set point potentiometer P1; a 2-digit, LED  
display; and the display button (see Fig. 6). The LED display is  
used to convey the operating information and operational error  
codes.  
Thermistors — The processor uses up to 5 thermistors to  
sense the temperatures at various points in the system. See Ta-  
ble 1 and Fig. 7-14. All the thermistors have identical tempera-  
ture versus resistance and voltage drop characteristics, and are  
monitored by the processor for a short or open circuit. The val-  
id range for a thermistor is 362,640 to 219 ohms. Thermistor  
details and locations are as follows:  
T1 — SUPPLY-AIR TEMPERATURE THERMISTOR —  
This thermistor is located in the unit supply fan discharge. It  
provides information for the processor to stage the number of  
capacity steps required to maintain a desired supply-air tem-  
perature.  
T2 — RETURN-AIR TEMPERATURE THERMISTOR —  
This thermistor is located in the mixed-air portion of the unit  
cabinet. The thermistor’s primary function is to provide morn-  
ing warm-up information. This sensor will also provide differ-  
ential information for the processor during cooling operation  
(such as the rate of change for a capacity step).  
T3 — SATURATED CONDENSING TEMPERATURE,  
CIRCUIT 1 — This thermistor is located on the condenser coil  
return bend. See Fig. 13 and 14. It controls the staging of the  
unit condenser fans based on the condensing temperature of  
the refrigerant at the designated position on the condenser coil.  
P7 — SASP (SUPPLY AIR SET POINT) RESET TEMPER-  
ATURE — This 10 Kohm potentiometer is used only if the  
accessory, field-installed temperature reset package is installed.  
This potentiometer determines the temperature at which reset  
will begin. It is located on the accessory temperature reset  
board. DIP switch 2 must be in the ON position to enable  
SASP reset.  
PROCESSOR BOARD OUTPUTS — The processor board  
also controls outputs through the relay board. The relay board  
plugs into the processor board using a ribbon cable.  
T4 — SATURATED CONDENSING TEMPERATURE,  
CIRCUIT 2 — This thermistor is located on the condenser coil  
return bend. See Fig. 13 and 14. It controls the staging of the  
unit condenser fans based on the condensing temperature of  
the refrigerant at the designated position on the condenser coil.  
T10 — RESET TEMPERATURE — This thermistor is used  
only if the accessory temperature reset package is used. It pro-  
vides occupied space temperature information to the processor,  
which determines whether or not reset is required. The ther-  
mistor is remotely mounted outside the unit in the conditioned  
space.  
In addition, the processor board controls the display board. The  
display board is connected to the processor board by a ribbon  
cable, and has an LED (light-emitting diode) display showing  
the status of the unit and diagnostic information.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 3 — Output Pin and Terminal Assignments  
OUTPUT PIN-  
TERMINAL  
NAME  
RATING  
DEVICE  
CR1  
Stage 1  
J6-1  
J6-2  
Compressor Relay (K1)*  
Stage 2  
U2**  
Compressor Relay (K2)*  
Stage 3  
J6-3  
J6-4  
J6-5  
U1  
Not Used  
CR2  
Compressor Relay (K3)*  
Compressor Relay (K4)†  
Stage 5  
Compressor Relay (K5)†  
24 vac  
Stage 6  
Compressor Relay (K6)†  
J6-6  
Not Used  
J6-7  
J6-8  
J5-1  
J5-2  
Economizer Open Relay (K7)  
Economizer Close Relay (K8)  
Supply Fan Relay (K9)  
EOR  
ECR  
IFC  
Morning Warm-Up Relay (K10)  
HIR  
Stage 1 Condenser  
Fan Relay (K11)  
J5-3  
OFC2/OFC3††  
115 vac  
Stage 2 Condenser  
Fan Relay (K12)  
External Alarm Relay (K13)  
J5-4  
J5-5  
OFC4||  
ALM  
LEGEND  
*Circuit 1.  
†Circuit 2.  
ALM — Alarm  
**U2 is not used on 044 units.  
CR — Control Relay  
††OFC2 on 034-048 units; OFC3 on 054-104 units.  
ECR — Economizer Close Relay  
EOR — Economizer Open Relay  
HIR — Heat Interlock Relay  
||Used on 054-104 units only.  
IFC — Indoor (Evaporator) Fan Contactor  
OFC — Outdoor (Condenser) Fan Contactor  
U
Unloader  
LEGEND  
CR — Control Relay  
J
K
Terminal Pin Connectors  
Relay  
Fig. 5 — Relay Board  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
P1 SUPPLY AIR  
SET POINT  
POTENTIMETER  
TWO-DIGIT  
DISPLAY  
DISPLAY  
BUTTON  
P3 — RESET LIMIT — The processor board is programmed  
for occupied space temperature reset. In order for reset to  
work, the accessory temperature reset board must be used.  
Potentiometer P3 is the maximum set point temperature to  
which the supply air can be reset.  
P5 — ECONOMIZER MINIMUM POSITION — This  
potentiometer controls the set point for the minimum position  
of the economizer.  
P6 — MORNING WARM-UP TEMPERATURE — This  
potentiometer controls the morning warm-up temperature set  
point.  
Single-Step Demand Limit — The single step de-  
mand limit provides a means to limit the capacity of the VAV  
unit using an external switch. Single step demand limit will  
limit the compressor displacement based on the ratio of the  
wiper arm to the full scale resistance. The exact percentage of  
capacity reduction differs depending on the number of capacity  
steps.  
A 3-wire, 5 to 20 Kohm, field-supplied potentiometer (P4)  
is required for this option. The potentiometer should be wired  
to the processor J3 connections. In order to control the demand  
limit, the wiper arm of the potentiometer should be switched  
open and closed based on the demand limit requirement. The  
control switch is also field-supplied and installed.  
If the wiper arm wire is open, all capacity stages can be  
used. When the wiper arm wire is closed, the capacity is re-  
duced by the amount set on potentiometer P4.  
Fig. 6 — Display/Set Point Board  
Compressor Operation  
CONTROL RELAY (CR) — This relay provides information  
to the processor about compressor operation (one control relay  
per compressor). The relay controls and protects the compres-  
sor and also controls the crankcase heater.  
Demand Limit Control Module (DLCM) — The  
DLCM provides a 2-step demand limit control using an exter-  
nal switch. The first step is between 50% and 100% of the  
maximum compressor displacement. See Fig. 16. The second  
step is between 0% and 49% of the maximum compressor dis-  
placement. The exact percentage differs depending on the  
number of capacity steps.  
Two adjustable potentiometers are used to set the 2 demand  
limit points. Potentiometer P1 is used to set a demand limit  
between 50% and 100% of the unit capacity. Potentiometer P2  
is used to set a demand limit between 0% and 49% of unit  
capacity.  
If no power is supplied to the demand limit control module,  
all capacity stages can be used. When power is supplied to ter-  
minal IN1 only, the first step of the demand limit control is en-  
ergized and the capacity is reduced by the amount set on poten-  
tiometer P1. When power is supplied to terminal IN2 only, or  
to both IN1 and IN2, the capacity is reduced by the amount set  
on potentiometer P2.  
A control signal to check the safety statuses and to start the  
compressor is sent from the relay board. This signal travels  
through all of the safeties: the high-pressure switch, and the in-  
ternal protector (where used) and on to the control relay coil.  
Once the control relay coil has been energized, the control re-  
lay completes a feedback circuit for the processor, informs the  
processor of the status of the compressor safeties, energizes the  
compressor contactor coil, and deenergizes the crankcase heat-  
ers. A fault will be detected by the processor if the control relay  
opens during operation or startup. The processor will lock the  
compressor or the circuit off by deenergizing the appropriate  
relay(s) on the relay board and energizing an alarm signal.  
Accessory Board — The accessory board is standard  
(factory supplied) in the VAV rooftop units. See Fig. 15. This  
board is located in the control box of each unit. Each board has  
a prewired connector supplied with it to connect directly to the  
processor board. It has 3 potentiometers: P3, P5, and P6.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
GAS SECTION  
(48FK,JK ONLY)  
HORIZONTAL SUPPLY SECTION  
(50FY,JY ONLY) AND EXTENDED  
PLENUM SECTION (50FKX,FKY,JKX,JKY)  
Fig. 7 — Thermistor T1 Location, 48FK,JK, 50FY,JY and 50FKX,FKY,JKX,JKY 034-048 Units  
FAN DISCHARGE/ELECTRIC HEAT SECTION  
Fig. 8 — Thermistor T1 Location, 50FK,JK034-048 Units  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
HORIZONTAL SUPPLY SECTION (50FS,FY,JY)  
AND EXTENDED  
PLENUM SECTION (50FKX,FKY,FMX,FMY,JKX,JKY)  
GAS SECTION  
(48FK,FM,JK)  
Fig. 9 — Thermistor T1 Location, 48FK,FM,JK, 50JY and  
50JKX,JKY 054-074 Units and 50FKX,FKY,FMX,FMY and 50FS,FY054-104 Units  
FAN DISCHARGE/ELECTRIC HEAT SECTION  
Fig. 10 — Thermistor T1 Location, 50FK,JK054-074 Units  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
BAG  
FILTERS  
STANDARD  
FILTERS  
Fig. 11 — Thermistor T2 Location, Size 034-048 Units  
Fig. 13 — Thermistor T3 and T4 Locations,  
Size 034-048 Units  
ENTHALPY CONTROL  
48FK,JK and 50FK,FY,JK,JY Units — Outside air enthalpy  
control is standard with the factory-installed economizer op-  
tion. Enthalpy is sensed by a controller located behind the end  
outside air hood. The control can be accessed by removing the  
upper hood filter. See Fig. 17.  
48FM and 50FM,FS Units — The control is located on the  
metal upright between the two economizer hoods, on the right  
hand side of the unit, and can be accessed by removing the fil-  
ter on either economizer hood.  
DIFFERENTIAL ENTHALPY — Added efficiencies in econ-  
omizer control can be gained by installing a differential en-  
thalpy sensor in the return air duct. When differential enthalpy  
control is installed, the economizer control will use the air  
stream with lower enthalpy (outside air or return air) to provide  
for lower compressor operating costs during integrated econo-  
mizer cycle operation. The differential enthalpy sensor is  
installed in the return-air duct.  
BAG FILTERS  
(054-074 Only)  
STANDARD FILTERS AND  
PLEATED FILTERS  
Fig. 12 — Thermistor T2 Location, Size 034-048 Units  
Economizer — Economizer control is used to control the  
outside and return air dampers of the unit, to satisfy space cool-  
ing demand using all outside air (when permitted), and to satis-  
fy cooling in conjunction with compressor operation (when  
conditions permit). During Occupied periods without cooling  
demand, the outside-air dampers will be at the user-configured  
Minimum Damper Position (at P5 on accessory board). During  
Unoccupied periods, the outside-air dampers will be closed.  
The economizer is a standard feature on 48FM and  
50FM,FS units and is available as a factory-installed option on  
48FK,JK and 50FK,FY,JK,JY units.  
The user can install an accessory differential enthalpy sen-  
sor to enhance economizer control. Refer to the installation  
section for field wiring of the sensor.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
054 UNITS  
064, 074, 078 UNITS  
088, 104 UNITS  
Fig. 14 — Thermistor T3 and T4 Locations, Size 054-104 Units  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The unit is supplied with a pressure transducer capable of  
measuring from 0.0 to 5.0 in. wg. The pressure transducer will  
send a 4 to 20 mA signal to the VFD to modulate the speed of  
the indoor fan motor to precisely control the fan to the desired  
static pressure set point. The VFD is factory set at 2.5 in. wg  
duct static pressure. Refer to the Operating Sequence section  
for more information on the VFD.  
The VFD has been programmed and wired at the factory for  
this application. No further adjustments (except for Duct Static  
Pressure Set Point) should be necessary at start-up. Factory  
jumper wire configurations are shown in the Supply Fan Con-  
trol with VFD Option section on page 28.  
A separate service manual for the factory-installed VFD is  
supplied with each unit. Refer to the VFD manual for more in-  
formation on the VFD controls.  
LEGEND  
High Capacity Modulating Power Exhaust  
Variable Frequency Drive (48FM and 50FM,FS  
Units Only) — The power exhaust VFD (PE VFD) is used  
to modulate the power exhaust fan motor no. 1 and stage the  
power exhaust fan motor no. 2 in order to maintain building  
static pressure. The PE VFD is located at the return air end of  
the unit of the opposite side from the auxiliary control box and  
can be accessed by opening the access door.  
The unit is supplied with a pressure transducer capable of  
measuring from –0.5 to +0.5 in. wg. The pressure transducer  
will send a 4 to 20 mA signal to the PE VFD to modulate the  
speed of the power exhaust motor no. 1 and also stage on/off  
the power exhaust motor no. 2 to precisely maintain the desired  
building pressure set point. The PE VFD is factory set at  
0 in. wg. Refer to Operating Sequence section for more infor-  
mation on the PE VFD.  
ECON — Economizer  
MIN  
P
Minimum  
Potentiometer  
VAV — Variable-Air  
Volume  
Fig. 15 — Accessory Relay Board  
(Standard; Factory Supplied)  
The PE VFD has been programmed and wired at the factory  
for this application. No further adjustments (except for Build-  
ing Pressure Set Point) should be necessary at start-up. Factory  
jumper wire configurations are shown in the Power Exhaust  
Variable Frequency Drive section in the Troubleshooting sec-  
tion on page 55.  
LEGEND  
IC  
IN  
P
Integrated Circuit  
Input  
Potentiometer  
RTN — Return  
Fig. 16 — Two-Step Demand Limit Module  
Fig. 18 — Variable Frequency Drive,  
Sizes 034-048 and 078-104  
Fig. 17 — Enthalpy Sensor Location  
(48FK,JK and 50FK,FY,JK,JY Units Only)  
Supply Fan Variable Frequency Drive  
(VFD) — The optional VFD is used to modulate supply fan  
airflow to maintain duct static pressure on VAV applications.  
The VFD is located in the supply fan section (see Fig. 18 and  
19), and can be accessed by opening the fan section access  
door.  
Fig. 19 — Variable Frequency Drive, Sizes 054-074  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A separate service manual for the factory installed PE VFD  
is supplied with each unit. Refer to PE VFD manual for more  
information on the PE VFD.  
control box. When unit goes into Heating mode, interlock relay  
is energized providing switch closure or opening (depending  
on how field power source is set up) to open the room termi-  
nals. Field connections for interlock relays are terminals 3 and  
4 (for normally open contacts) and terminals 3 and 7 (for nor-  
mally closed contacts) on terminal block 3 (sizes 034-048) or  
terminal block 4 (sizes 054-104). See Fig. 24. Note that a field-  
supplied power source is required.  
There are no required 115-volt field wiring connections,  
therefore no provisions have been made in the unit for running  
115-volt wiring. If any of the field-installed options requiring  
115-volt connections are desired, the unit must be modified in  
the field for 115-volt wiring.  
NIGHT SETBACK THERMOSTAT — Wire field-supplied  
thermostat (suitable for 24-v circuit) between terminals 1 and 2  
on terminal block 3 (sizes 034-048) or terminal block 4  
(sizes 054-104). This thermostat is used to bypass the time-  
clock occupied/unoccupied switch and is used to operate unit  
during unoccupied times at more economical temperatures.  
(See Fig. 23.)  
SPACE TEMPERATURE RESET ACCESSORY (50DJ900021)  
— Consists of a thermistor (T10) and a reset board with a potenti-  
ometer (P7) that is used to set space temperature at which reset  
starts. Mount reset board in unit control box or other convenient  
place. Wire thermistor in series with P7 and connect to terminals  
12 and 15 on terminal block 3 (sizes 034-048) or terminal block 4  
(sizes 054-104) in unit control box. If there is a long run to condi-  
tioned space, it is necessary to splice additional wire to thermistor.  
The reset board has 2 pressure connectors for field wiring. (See  
Fig. 25.)  
Temperature Reset — Accessory temperature reset al-  
lows the unit to automatically adjust (‘‘reset’’) the supply-air  
temperature set point to a higher value once most of the space  
cooling load has been met. When the space conditions are sat-  
isfied, the VAV terminals will close to the minimum position.  
All VAV units will sense the decrease in actual supply-air tem-  
perature and the unit controls respond by reducing capacity  
stages to maintain user-established supply-air set point temper-  
ature. When VAV units are also equipped with optional supply  
duct pressure controls (either inlet guide vanes [IGV] or vari-  
able frequency drive package), the unit also senses an increase  
in duct static pressure and responds by closing IGV dampers or  
slowing fan wheel speed to maintain user-configured set points  
for supply duct pressure. Allowing the supply-air temperature  
to be reset to a higher value maintains air circulation in the  
space without costly overcooling.  
The accessory package is required for temperature reset.  
The accessory includes:  
thermistor T10, to monitor space temperature  
reset temperature potentiometer P7, to establish start  
temperature for reset operation  
reset limit potentiometer P3, to establish maximum level  
of modified supply-air temperature  
More than one space sensor may be used if an average  
space temperature is desired for initiating temperature reset.  
Refer to installation section for sensor part number and wiring  
schematic.  
Space Temperature Reset  
INSTALLATION — Install the accessory temperature reset  
package in accordance with instructions provided with the  
accessory kit.  
Mount the reset board in the unit control box (or other suit-  
able location) per instructions.  
Locate the thermistor T10 in a suitable location in the occu-  
pied space per instructions.  
Temperature reset will start when space temperature (at  
T10) drops to the set point at P7. When Temperature Reset  
is active, the LED (light-emitting diode) display will show  
code 21 . Automatic adjustment of supply-air temperature set  
point will end when modified SASP equals reset limit set point  
at P3. (See formula for automatic modification of SASP in  
Controls Installation, Space Temperature Reset section on this  
page.)  
Wire T10 to the reset board and to the unit control terminal  
block per Fig. 25. Wire the other terminal on the reset board to  
the unit control terminal block per Fig. 25.  
If multiple sensors are required to average the space temper-  
ature, see Fig. 26. Use only Carrier Part Number HH79NZ014  
sensor, in arrangements of 4 or 9 sensors, with total wiring not  
to exceed 1000 ft.  
CONTROLS INSTALLATION  
The VAV units may be used in applications with additional  
control features, options, or accessories. Refer to the appropri-  
ate accessory installation instructions for more information on  
installing that accessory. Unit control box component arrange-  
ment is shown in Fig. 20-22. Control options and accessories  
available for VAV units are:  
To enable reset function, change DIP (dual in-line package)  
switch 2 to position ON. (Disconnect control power before  
changing DIP switch positions; reconnect power after all  
changes have been made.)  
CONFIGURATION — Set points for reset operation are  
established at potentiometers P7 and P3 (on the reset board).  
Potentiometer P7 — Reset temperature set point (temperature  
at which reset function will start). Maximum of 80 F, mini-  
mum 0° F. Set below normal room cooling set point level to  
sense overcooling in the occupied space.  
NOTE: It is difficult to accurately set the P7 potentiometer to  
the desired set point. Use the procedure below.  
smoke control modes  
differential enthalpy sensor  
electric heaters (sizes 034-074 only)  
modulating power exhaust  
Motormaster® I control  
space temperature reset  
night setback thermostat (field-supplied)  
single step demand limit  
two-step demand limit  
inlet guide vanes  
variable frequency drive  
variable frequency drive remote display kit  
Control Wiring — A switch or timeclock (field supplied)  
must be wired in to control when unit will go into and out of  
Occupied mode. Connect switch or timeclock between termi-  
nals 1 and 2 on terminal block 3 (sizes 034-048) or terminal  
block 4 (sizes 054-104) in unit control box. See Fig. 23. The  
circuit potential is 24 v.  
Variable air volume units equipped with warm-up heat re-  
quire that room terminals be controlled to go fully open when  
unit goes into the Heating mode. Heating interlock relay (HIR)  
is provided for this function. The relay is located in the unit  
Proper setting of the P7 potentiometer may be made on a re-  
sistance basis. The microprocessor initiates reset when it de-  
tects a resistance of the thermistor plus the potentiometer of  
13,084 ohm. The potentiometer set point may be calculated us-  
ing the following formula:  
P7R = 13,084 – T10R  
Where:  
P7R = the desired set point of the P7 potentiometer in ohms  
T10R = the resistance of the T10 thermistor for the desired  
set point  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 20 — Unit Control Box Arrangement, Sizes 034-048  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
034-048: TB3  
054-104: TB4  
034-048: TB3  
054-104: TB4  
OPERATING SEQUENCE — If space temperature is above  
reset set point (T10 > P7), no reset will occur.  
If space temperature is equal to or less that reset set point  
(T10 < P7), the LED will display 20 and reset will begin.  
1
2
Control will automatically adjust leaving air temperature by  
the following formula:  
OCCUPIED/UNOCCUPIED  
SWITCH  
MSP = SP + [(P3 - SP) / 3] x (P7 – T10)  
where:  
MSP = Modified Leaving-Air Set Point  
SP = Supply-Air Set Point  
NIGHT SETBACK THERMOSTAT  
P3 = Maximum Supply-Air Temperature (reset limit)  
P7 = Reset Initiation Temperature (reset set point)  
T10 = Actual Space Temperature  
NOTES:  
1. Occ/Unocc switch closes when occupied.  
2. Night setback thermostat closes when in night setback heating.  
3
= Ratio for reset (F) (fixed parameter)  
Fig. 23 — Occupied/Unoccupied Switch with  
Night Setback Thermostat  
Table 4 — Thermistor Resistance and Voltage  
Drop Characteristics  
TEMP  
(F)  
RESISTANCE  
(Ohms)  
VOLTAGE  
DROP (v)  
034-048: TB3  
054-104: TB4  
31.0  
32.0  
33.0  
34.0  
35.0  
36.0  
37.0  
38.0  
39.0  
40.0  
41.0  
42.0  
43.0  
44.0  
45.0  
46.0  
47.0  
48.0  
49.0  
50.0  
51.0  
52.0  
53.0  
54.0  
55.0  
56.0  
57.0  
58.0  
59.0  
60.0  
61.0  
62.0  
63.0  
64.0  
65.0  
66.0  
67.0  
68.0  
69.0  
70.0  
71.0  
72.0  
73.0  
74.0  
75.0  
76.0  
77.0  
78.0  
79.0  
80.0  
16813.8  
16345.7  
15892.2  
15452.7  
15026.7  
14613.9  
14213.6  
13825.5  
13449.2  
13084.2  
12730.1  
12386.6  
12053.3  
11730.0  
11416.1  
11111.5  
10815.8  
10528.7  
10250.0  
9979.3  
9716.5  
9461.3  
9213.4  
8972.6  
8738.6  
8511.4  
8290.6  
8076.1  
7867.7  
7665.1  
7468.3  
7277.1  
7091.2  
6910.6  
6735.1  
6564.4  
6398.6  
6237.5  
6080.8  
5928.6  
5780.6  
5636.8  
5497.0  
5361.2  
5229.1  
5100.8  
4976.0  
4854.8  
4736.9  
4622.4  
3.582  
3.553  
3.523  
3.494  
3.464  
3.434  
3.404  
3.373  
3.343  
3.312  
3.281  
3.250  
3.219  
3.187  
3.156  
3.124  
3.093  
3.061  
3.029  
2.997  
2.965  
2.933  
2.901  
2.869  
2.837  
2.805  
2.772  
2.740  
2.708  
2.676  
2.644  
2.612  
2.581  
2.549  
2.517  
2.486  
2.454  
2.423  
2.391  
2.360  
2.329  
2.299  
2.268  
2.237  
2.207  
2.177  
2.147  
2.117  
2.088  
2.058  
FIELD  
SUPPLIED  
3
4
7
V
POWER  
SOURCE  
4
6
5
N.O.  
N.C.  
SIGNAL  
TO ROOM  
TERMINALS  
Fig. 24 — Heat Interlock Relay  
034-048: TB3  
054-104: TB4  
T10  
12  
RESET  
BOARD  
P7  
15  
Fig. 25 — Accessory Reset Board  
EXAMPLE:  
T10 desired set point is 70 F.  
T10R from Table 4 for 70 F is 5929 ohms.  
P7R = 13,084 – 5929  
P7R = 7155 ohms  
Using an ohmmeter, set the P7 potentiometer to 7155 ohms  
to achieve a reset initiation set point of 70 F.  
Potentiometer P3 — Reset limit set point (maximum tempera-  
ture value for modified supply air set point). Maximum of 70 F,  
minimum 40 F. Set between leaving air set point (P1) and 70 F  
(maximum range permitted by control).  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RED  
BLK  
RED  
BLK  
SIZES 034-048  
TB3  
RED  
RED  
BLK  
RED  
BLK  
12  
15  
BLK  
TO ACCESSORY SPACE  
TEMPERATURE RESET  
CONTROL BOARD  
SIZES 054-104  
TB4  
12  
15  
SENSOR 1  
SENSOR 2  
SENSOR 3  
SENSOR 4  
SPACE TEMPERATURE RESET 4 SENSOR AVERAGING APPLICATION  
SIZES 034-048  
TB3  
12  
RED  
BLK  
RED  
BLK  
RED  
BLK  
15  
TO ACCESSORY SPACE  
TEMPERATURE RESET  
CONTROL BOARD  
SENSOR 1  
SENSOR 3  
SENSOR 2  
SIZES 054-104  
TB4  
12  
RED  
BLK  
RED  
BLK  
15  
SENSOR 4  
SENSOR 5  
SENSOR 6  
RED  
BLK  
RED  
BLK  
NOTE: Sensor part number is HH79NZ014.  
SENSOR 7  
SENSOR 8  
SENSOR 9  
SPACE TEMPERATURE RESET 9 SENSOR AVERAGING APPLICATION  
Fig. 26 — Space Temperature Sensor Averaging  
Demand Limit — The demand limit function provides a  
means to limit the cooling capacity of the VAV unit using an  
external discrete switch function. When enabled by the closure  
of the external switch, the control will limit the available com-  
pressor staging capacity according to user set points established  
at demand limit potentiometer(s).  
Control Module kit plus installation of 2 field-supplied control  
switches (SPST-NO each). This accessory control provides for  
a first step reduction of 50% to 100% of the maximum com-  
pressor staging; the second step provides for reduction  
between 0% and 49%. The exact percentage of capacity reduc-  
tion differs depending on the number of capacity steps.  
The unit controls support two types of demand limit: single-  
step and 2-step control.  
When demand limit is active, the LED display will show  
code 22 .  
SINGLE-STEP DEMAND LIMIT — This function will limit  
the total compressor staging based on the ratio of the set point  
potentiometer’s wiper arm position to the full scale resistance  
of the potentiometer. The exact percentage of capacity reduc-  
tion differs depending on the number of capacity steps.  
A field-supplied potentiometer and control switch are re-  
quired for this function. See installation section for specifica-  
tion on potentiometer and field wiring.  
INSTALLATION  
Single-Step Demand Limit — A 3-wire 5 to 20 K-ohm poten-  
tiometer must be field-supplied and installed. A single-  
pole normally open switch is also required (field-supplied  
and -installed). Locate the potentiometer (designated P4) and  
the switch in a suitable location (external from the unit or in the  
unit control box).  
TWO-STEP DEMAND LIMIT — Two-step demand limit is  
provided with the installation of the accessory Demand Limit  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect the potentiometer end terminals to terminals 8  
and 9 on control terminal block TB3 (sizes 034-048) or TB4  
(sizes 054-104) (see Fig 27). Connect the switch terminals to  
the potentiometer wiper arm terminal and to terminal 10 on  
TB3 or TB4.  
034-048: TB3  
054-104: TB4  
8
To enable demand limit function, change DIP switch 5 to  
position ON. (Disconnect control power before changing DIP  
switch positions. Reconnect power after all changes have been  
made.)  
5-20K  
POTENTIOMETER  
(P4)  
9
Set the potentiometer P4 to desired capacity reduction value.  
Two-Step Demand Limit — Install the demand limit control  
module (DLCM) according to the installation instructions pro-  
vided with the accessory. Disconnect existing leads at connec-  
tor J3 on the processor board (see instructions) and connect the  
plug from the DLCM harness to connector J3.  
10  
SWITCH  
Fig. 27 — Single-Step Demand Limit  
Connect the field input control power wires (from the exter-  
nal control relays) at the terminal strips marked IN1, RTN1,  
IN2 and RTN2 (see Fig. 28 and 29).  
To enable demand limit function, change DIP switch 5 to  
position ON. (Disconnect control power before hanging DIP  
switch positions. Reconnect power after all changes have been  
made.)  
Set the potentiometers DLCM-P1 and DLCM-P2 to desired  
capacity reduction values.  
Check the operation of demand limit function by using the  
Quick Test procedures.  
CONFIGURATION  
Fig. 28 — Two-Step Demand Limit Module  
Single-Step Demand Limit — Field-installed potentiometer  
P4 establishes capacity reduction value for demand limit opera-  
tion. Set this potentiometer between 0% and 100%. The exact  
percentage of capacity reduction differs depending on the num-  
ber of capacity steps.  
Two-Step Demand Limit — Potentiometer P1 and P2 (locat-  
ed on the accessory demand limit control module) establish the  
capacity reduction values for each step of demand limit. Set po-  
tentiometer DLCM-P1 between 50% and 100%. Set potenti-  
ometer DLCM-P2 between 0% and 49%. The exact percentage  
of capacity reduction differs depending on the number of ca-  
pacity steps.  
NOTES:  
1. Demand limit switches are field supplied and wired.  
2. Demand limit control module terminal blocks will accept up to  
12-gage wire.  
OPERATING SEQUENCE  
Single-Step Demand Limit — If the field control switch to  
the wiper arm terminal is open, all capacity stages will be avail-  
able (no demand limit in effect). When the field control switch  
is closed, the compressor cooling capacity is reduced by the  
amount set on potentiometer P4.  
3.  
is field wiring.  
Fig. 29 — 115-Volt Field Wiring to Accessory  
2-Step Demand Limit Control Module  
Control From Remote Building Management  
System (BMS) — The unit control system is not a com-  
municating control system, and it cannot be accessed directly  
by a DDC (Direct Digital Control) control system (or by a  
BACnet communication system). However, it is possible to  
control some functions of these units via 4 to 20 mA or 2 to  
10 vdc signals and discrete inputs (relay contact closures).  
When demand limit is in effect, the LED display will show  
code 22 . If a potentiometer setting or input is out of range, the  
control will terminate the demand limit function and show  
code 84 at the display LED.  
Two-Step Demand Limit — If the field control switches are  
both open (no power supplied to the Demand Limit Control  
Module), all capacity stages will be available (no demand limit  
in effect). When control power is supplied to terminal IN1 only  
(field switch SW1 closes), the first step of the demand limit is  
energized and the compressor cooling capacity is reduced by  
the amount set on potentiometer DLCM-P1. When control  
power is supplied to terminal IN2 (field switch SW2 closes),  
the second step of the demand limit is energized and compres-  
sor cooling capacity is reduced by the amount set on potenti-  
ometer DLCM-P2.  
Functions that can be managed from or accessed from an  
external control system include:  
Occupied/Unoccupied Status  
Night Setback Control  
Unit Supply Air Set Point Adjustment  
Demand Limit (1-stage or 2-stage)  
Supply Duct Pressure Set Point Adjustment  
External Alarm Signal  
Remote control of the economizer cycle on these units is not  
recommended. Refer to the Operating Sequence section on  
page 35 for a discussion on the economizer cycle operation.  
When demand limit is in effect, the LED display will show  
code 22 . If a potentiometer setting or input is out of range, the  
control will terminate the demand limit function and show  
code 84 at the display LED.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OCCUPIED/UNOCCUPIED — The unit control system will  
initiate normal occupied mode functions (including Morning  
Warm-up, Economizer Minimum Position, and Cooling Cycle)  
whenever a contact closure is made that emulates the normal  
timeclock contacts. See Fig. 23. (‘‘Occupied/Unoccupied  
Switch’’). The contact closure from the BMS must be an iso-  
lated contact set, normally open, and suitable for 24 volts AC  
pilot duty.  
Configuration — Configure as follows:  
1. Set DIP switch no. 2 to ON.  
2. Adjust manual potentiometer to 12.6 to 12.8 k-ohm.  
3. Configure transducer for job site input signal from BMS.  
4. Adjust Potentiometer (P3) on the rooftop to MAXIMUM  
SASP value (typically 65 to 70 F). The maximum P3 SASP  
control limit is 70 F.  
NIGHT SETBACK CONTROL — Night setback control is  
used to control the space to a set point level that is typically  
lower than during normal occupied periods (Heating Only  
mode). Some applications also require a limitation on the max-  
imum space temperature during unoccupied periods (Cooling  
mode). Both modes are possible by closing the same contacts  
used in the Occupied/Unoccupied control, or by installing a  
dedicated contact set in parallel with the Occupied/ Unoccu-  
pied control contacts, and using the BMS space temperature  
sensing system and its logic to determine when to initiate unit  
operation.  
Operation — Unit will initiate SASP Reset (adjust configured  
SASP upward) when the sum of the resistance (fixed resistance  
+ potentiometer + transducer) exceeds 13.1 k-ohm. Once reset  
is initiated, full range of reset (P3 setting minus configured  
SASP) will be reached with 500-ohm increase in transducer re-  
sistance (TR).  
During Reset mode operation, Code 21 will appear on unit  
display board.  
Formula:  
MSP = SASP +  
Once the unit operation has been initiated by the BMS con-  
tact closure, the unit operates in its normal occupied mode  
manner, initiating morning warm-up if needed (as sensed by re-  
turn air temperature to the unit) or cooling (controlling to cur-  
rent SASP value). The Night Setback Control contacts will in-  
terrupt normal unit operation when the BMS senses that space  
temperatures have returned to unoccupied set point levels, and  
the unit will shut down normally.  
(P3 — SASP)  
(3)  
(0.6 F)  
(100 ohm)  
X
X (TR [email protected])  
[
]
MSP: Modified SASP (SASP plus Reset)  
TR: Resistance at transducer  
[email protected]: TR required to reach 13.1 k-ohm start level  
DEMAND LIMIT (1-STAGE OR 2-STAGE) — Both of the  
Demand Limit functions on the units rely on external switches  
to initiate the reset functions. Contact closures by the BMS can  
be used in place of these switches. Contacts must be isolated  
and suitable for 115-vac pilot duty operation.  
For Single-Step Demand Limit, emulate function of switch  
SW with contact closure controlled by the BMS. Set potenti-  
ometer P4 manually at the unit control box. Alternatively, po-  
tentiometer P4 might also be emulated by a variable resistance  
transducer, with the BMS now able to adjust the amount of de-  
mand limit.  
For 2-Step Demand Limit, install the accessory Demand  
Limit Control Module (DLCM) according the instructions on  
page 18. Replace switch functions Switch 1 and Switch 2 with  
contact closures controlled by the BMS (see Fig. 29).  
Follow unit control configuration instructions in the De-  
mand Limit section on page 18.  
The contact closure from the BMS must be an isolated con-  
tact set, normally open, suitable for 24 volts AC pilot duty.  
NOTE: If the rooftop unit is equipped with a VFD and night  
setback cooling operation is intended, the fan system must be  
controlled to permit FULL SUPPLY FAN AIR DELIVERY  
during unoccupied cooling operation. This is most conve-  
niently attained by replicating the HIR relay function of the  
rooftop unit. An HIR control sequence will force all room ter-  
minals to their minimum heating CFM position, thus assuring  
adequate airflow through the rooftop unit during night setback  
cooling operation. During night setback cooling operation, the  
return-air temperature (RAT) will be well above normal levels.  
The higher RAT means that the air temperature leaving the  
evaporator coil will also be well above normal levels. This sit-  
uation is interpreted by the unit control system as a demand for  
additional cooling stages. The unit control responds to this  
demand by bringing on more stages, until typically all stages  
are active. If the VFD is not working in-step with the refrigera-  
tion system demand, it is possible to produce low suction pres-  
sures and local frosting on the evaporator coil during the night  
setback cooling operation.  
UNIT SUPPLY AIR SET POINT ADJUSTMENT — The  
minimum Supply Air Set Point (SASP) temperature is estab-  
lished by the setting at Potentiometer P1 on the unit display  
board (see Fig. 6). The control point can also be adjusted  
upward by emulating the function of the accessory Space Tem-  
perature Reset package. The BMS can be used to cause this  
reset by adjusting the resistance value in a variable resistance  
transducer with a 4 to 20 mA or 2 to 10 vdc signal generated  
by the BMS.  
SUPPLY DUCT PRESSURE SET POINT ADJUSTMENT  
— Supply duct pressure set point adjustment from a remote  
BMS is possible when the unit has been equipped with a fac-  
tory-option VFD (variable frequency drive). There are two  
methods available:  
Direct 4 to 20 mA signal  
DDC direct to the VFD  
Direct 4 to 20 mA Signal — During normal unit operation,  
the factory-installed VFD receives a 4 to 20 mA signal from  
the Duct Pressure (DP) transducer which indicates current sup-  
ply duct pressure. The VFD then determines the appropriate  
fan speed (using its internal PID logic feature) and adjusts its  
output to the supply fan motor to suit. It is possible to emulate  
this 4 to 20 mA control signal by the BMS, which will transfer  
control of the VFD to the BMS.  
This emulation requires the following field-supplied parts:  
Variable resistance transducer (Kele RES-1 or equiva-  
lent, range 0 to 1000 ohms)  
Series resistance with potentiometer, suitable for manual  
adjustment to 12.5 to 13.0 k-ohms total resistance  
NOTE: When providing a direct 4 to 20 mA signal to the VFD  
from a BMS with DP logic, disable the PID (proportion inte-  
grated derivative calculation process) feature of the VFD.  
DDC Direct to the VFD — Several accessory interface  
boards are available for the VFDs that permit direct communi-  
cation between the VFD and several BMS communication sys-  
tems. Contact your Carrier representative for information on  
selecting an appropriate accessory interface board and the  
name of the local service office (for sale and installation of the  
accessory boards).  
Field Connections (see Fig. 30) — Connect fixed resistance  
with manual potentiometer and variable resistance transducer  
in series.  
Connect wiring to rooftop unit at:  
Size 034-044: TB3-12 and TB3-15  
Size 054-104: TB4-12 and TB4-15  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
034-048: TB3  
054-104: TB4  
EXTERNAL ALARM SIGNAL — The unit controls provide  
an external alarm status signal via a 115-vac output signal at  
the relay board J5, available at TB2-4 and TB2-5 (common).  
This signal can be forwarded to the BMS by adding a signal  
relay at the alarm output, placing its coil across terminals TB2-  
4 and TB2-5 and using its contacts to control a discrete input to  
the BMS (see Fig. 31).  
TRANSDUCER  
BMS  
P
CONTROL  
R
12  
(4 TO 20 MA  
OR  
2 TO 10 VDC  
SIGNAL)  
15  
The alarm signal output is energized when any of the diag-  
nostic codes is tripped.  
REMOTE ECONOMIZER CONTROL — Economizer con-  
trol is tightly integrated into the unit’s capacity control algo-  
rithms and diagnostic routines. Consequently, control  
modifications that interfere with this standard operating  
sequence are not recommended.  
LEGEND  
P
R
Manual Potentiometer  
Fixed Resistor  
Field Wiring  
Fig. 30 — Remote SASP Wiring  
Economizer position is determined by the unit processor  
board based on current outdoor air enthalpy status and cooling  
capacity demand. The economizer damper actuator is a floating  
point device with an internal brake and spring return. Its posi-  
tion is determined by the sequencing of relays EOR (Econo-  
mizer Open Relay) and ECR (Economizer Close Relay). The  
economizer’s current position is sensed by the processor board  
through position feedback potentiometer P2.  
TB2  
4
TB2  
5
LIGHT  
R
Whenever the economizer position potentiometer signal is  
not consistent with the processor board’s commanded position,  
a fault condition is determined by the processor board and an  
alarm signal is initiated. The processor board also attempts to  
return the economizer damper to its fully closed position dur-  
ing this fault condition by energizing the ECR relay.  
RELAY  
Any attempt to effect an external control of the economizer  
actuator will lead to an alarm condition and an automatic re-  
sponse by the unit control to attempt to close the dampers.  
SIGNAL TO BMS  
Smoke Control Modes — It is common practice to use  
rooftop units for aid in building smoke control in the event of a  
building fire. The available functions include: Fire Shutdown,  
Pressurization, Evacuation, and Smoke Purge. These functions  
are enhanced when multiple rooftop units are used to zone a  
building.  
Implementation of the various Smoke Control modes on  
these units requires the installer to modify the unit wiring to  
add contacts (via either manual switches or relays) that will se-  
lectively interrupt and override standard factory control se-  
quences. See Table 5.  
Smoke control mode Pressurization requires the economiz-  
er function. Evacuation and Smoke Purge modes require both  
economizer and power exhaust functions. Both functions are  
standard features on 48FM and 50FM,FS units. These func-  
tions require factory-installed options, field-installed accesso-  
ries and/or field-supplied exhaust systems on 48FK,JK and  
50FK,FY,JK,JY units. Consult price pages for specific details.  
FIRE SHUTDOWN MODE — Fire Shutdown mode termi-  
nates all unit operation (cooling, heating, supply fan and power  
exhaust). This mode prevents recirculation of contaminated air  
back into the space or the admission into the space of unsuit-  
able outside air.  
LEGEND  
R
Fixed Resistor  
Factory Wiring  
Field Wiring  
Fig. 31 — External Alarm Indication  
running the supply fan (optional inlet guide vanes open  
or optional VFD [variable frequency drive] at normal  
duct static pressure set point)  
shutting off the power exhaust fans (Standard on 48FM  
and 50FM,FS units. Factory-installed option or field-  
installed accessory on 48FK,JK and 50FK,JK units)  
This allows the space to be overpressurized relative to adja-  
cent zones and prevents or slows entry of smoke into this space  
from adjacent zones.  
EVACUATION MODE — Evacuation mode removes smoke  
or undesirable air from interior spaces without reintroducing  
unsuitable air. The economizer and power exhaust are required  
for this function. The economizer and power exhaust are  
standard on 48FM and 50FM,FS units. The economizer is a  
factory-installed option and the power exhaust is a factory-  
installed option or field-installed accessory on 48FK,JK and  
50FK,JK units. Evacuation is accomplished by:  
turning supply fan off  
PRESSURIZATION MODE — Pressurization mode is  
intended to keep smoke out of a zone. The economizer is  
required for this function. The economizer is standard on  
48FM and 50FM,FS units. The economizer is a factory-  
installed option on 48FK,JK and 50FK,FY,JK,JY units. Pres-  
surization is accomplished by:  
opening the economizer  
running the exhaust fans  
opening the exhaust dampers  
opening the economizer  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SMOKE PURGE MODE — Smoke Purge mode removes  
smoke from the interior spaces and replaces it with fresh out-  
side air. The economizer and power exhaust are required for  
this function. The economizer and power exhaust are standard  
on 48FM and 50FM,FS units. The economizer is a factory-  
installed option and the power exhaust is a factory-installed  
option or field-installed accessory on 48FK,JK and 50FK,JK  
units. Smoke purge is accomplished by:  
CONFIGURATION — No set points required for Smoke Con-  
trol modes. Modes are activated by energizing all switches  
appropriate for each Smoke Control mode.  
OPERATING SEQUENCE  
Fire Shutdown — At command from the field switches (see  
Table 5), all unit operation (cooling, heating, supply fan and  
power exhaust) will terminate.  
Pressurization — At command from the field switches for  
Pressurization mode (see Table 5):  
1. Economizer dampers will open.  
2. The HIR function will energize, opening room terminals  
to full-open (heating) positions.  
3. Supply fan will run. (If equipped with IGV: control vanes  
will open. If equipped with VFD: the VFD will control to  
duct static set point or best available with all terminals  
open.)  
turning supply fan on  
opening the economizer  
running the exhaust fans  
opening the exhaust dampers  
INSTALLATION — To enable one or more of the possible  
smoke control modes available with these units, determine the  
switches required for the desired mode(s) from Table 6, field-  
supply and install the appropriate switches and field wire per  
Fig. 32. Switch functions are shown in Table 7.  
4. Power exhaust dampers (if equipped) will close.  
5. Power exhaust fans (if equipped) will turn off.  
Table 5 — Smoke Control Modes  
Evacuation — At command from the field switches for Evacu-  
ation mode (see Table 5):  
1. Supply fan will turn off.  
2. Economizer dampers will open.  
3. Exhaust fans will run at maximum capacity.  
4. Exhaust dampers will open.  
Smoke Purge — At command from the field switches for  
Smoke Purge mode (see Table 5):  
MODE  
FUNCTION  
Fire  
Pressur-  
ization  
Smoke  
Purge*  
On  
Open/On  
Open  
Evacuation*  
Shutdown  
Supply Fan  
IGV/VFD†  
Economizer  
Return Air  
Damper  
Exhaust  
Fans  
Off  
Closed  
On  
Off  
Open  
Open/On  
Open  
Open  
Off  
Closed  
Off  
Closed  
On  
Closed  
On  
1. Economizer dampers will open.  
2. The HIR function will energize, opening room terminals  
to full-open (heating) positions.  
Exhaust  
Damper  
Closed  
Closed  
Open  
Open  
LEGEND  
3. Supply fan will run. (If equipped with IGV: Control vanes  
will open. If equipped with VFD: the VFD will control to  
duct static set point or best available with all terminals  
open.)  
4. Exhaust fans will run at maximum capacity.  
5. Exhaust dampers will open.  
IGV — Inlet Guide Vane  
VAV — Variable Air Volume  
VFD — Variable Frequency Drive  
*Power exhaust function required for this mode.  
Applicable to VAV units with appropriate options.  
Table 6 — Smoke Control Switches Required for Each Mode  
EVACUATION  
(Modulating Power  
Exhaust)  
FIRE  
SHUTDOWN  
SMOKE  
PURGE  
PRESSURIZATION  
SW-1  
SW-2  
SW-1  
SW-2  
SW-4  
SW-5  
SW-6  
SW-1  
SW-2  
SW-3  
SW-5  
SW-6  
SW-7  
SW-8*  
SW-1  
SW-2  
SW-3  
SW-4  
SW-9A/B  
SW-9A/B  
*Not required on 48FM and 50FM,FS units (high capacity power exhaust units).  
NOTE: All switches are shown in as installed(power OFF or deenergized) position. In these  
positions, none of these modes will be activated; normal unit operation is permitted by the base  
unit controls. To initiate any mode, all switches listed under this mode in the table must be ener-  
gized, causing the depicted contact position to change from depicted positions to energized posi-  
tions. Switches may be manually or electrically operated.  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 — Switch Functions  
SWITCH  
NUMBER  
CONFIGURATION  
VOLTAGE  
FUNCTION  
SW-1  
SW-2  
SW-3  
SW-4  
SW-5  
SW-6  
N.C.  
N.C.  
N.O.  
N.O.  
N.C.  
N.O.  
115  
115  
24  
115  
115  
115  
Deenergize 115-v (OFC, Comp, IFC, Electric Heaters)  
Deenergize TRAN7 (Process Board)  
Energize EOR (Open Economizer Outside Air Dampers)  
Energize IFC and CR-3 (IGV/VFD)  
Isolate IFC and PEC for Separate Operation  
Energize PEC (Power Exhaust)  
Open PED at DPS (48FK,JK and 50FK,JK Units) Force Power Exhaust VFD  
to Maximum Speed (48FM and 50FM,FS Units)  
Block Auto-Close at DPS (Due to Low BP)  
SW-7  
SW-8*  
N.O.  
N.C.  
24  
24  
A: N.O.  
B: N.C.  
SW-9A/B  
115 max  
Signal Room Terminals to Open (HIR1)  
*Not required on 48FM and 50FM,FS units (units with high capacity power exhaust).  
LEGEND  
BP — Building Pressure  
DPS — Differential Pressure Switch  
EOR — Economizer Open Relay  
HIR — Heat Interlock Relay  
IFC — Indoor Fan Contactor  
IGV — Inlet Guide Vane  
N.C. — Normally Closed  
N.O. — Normally Open  
PEC — Power Exhaust Contactor  
PED — Power Exhaust Damper  
OFC — Outdoor Fan Contactor  
VFD — Variable Frequency Drive  
INLET GUIDE VANES — The tubing for the duct pressure  
Air Pressure Tubing — Before options such as inlet  
guide vanes (IGV), variable frequency drive (VFD), and/or  
modulating power exhaust can operate properly, the pneumatic  
tubing for pressure sensing must be installed. Use fire-retardant  
plenum tubing (field-supplied). Tubing size depends on type of  
control device (see Table 8 below). Tubing must be run from  
the appropriate sensing location (in the duct or in the building  
space) to the control device location in the unit.  
(DP) control option should sample supply duct pressure about  
2/3 of the way out from the unit in the main trunk duct, at a  
location where a constant duct pressure is desired.  
The inlet guide vanes are controlled by a differential pres-  
sure switch (DPS). On sizes 034-048, the DPS is located in the  
auxiliary control box at the economizer end of the unit (see  
Fig. 33). On sizes 054-104, the DPS is located in the supply fan  
section. See Fig. 34. Use a nominal 3/8-in. plastic tubing.  
SUPPLY FAN VARIABLE FREQUENCY DRIVE — The  
tubing for the duct pressure (DP) control option should sample  
supply duct pressure about 2/3 of the way out from the unit in  
the main trunk duct, at a location where a constant duct pres-  
sure is desired.  
Table 8 — Tubing Size  
NOMINAL TUBE  
OPTION  
UNITS  
ALL  
SIZE (in.)  
3
Inlet Guide Vanes (IGV)  
/
8
The duct pressure is sensed by a pressure transducer. The  
pressure transducer output is directed to the VFD. On 034-048  
units the DP transducer is located in the auxiliary control box.  
On 054-104 units, the DP transducer is located in the supply  
fan section. See Fig. 34. Use a nominal 1/4-in. plastic tubing.  
Supply Fan Variable  
1
ALL  
/
4
Frequency Drive (VFD)  
3
FK,FKX,JK,JKX  
FM,FS  
/
/
8
Modulating Power Exhaust  
1
4
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
054-104 UNITS  
034-048 UNITS  
TB2  
5
SW-1  
TB2  
6
TB2  
13  
SW-1  
TB2  
14  
REMOVE JUMPER  
REMOVE JUMPER  
TB2  
1
SW-2  
TB2  
2
TB2  
7
SW-2  
TB2  
8
REMOVE JUMPER  
REMOVE JUMPER  
SW-3  
SW-4  
TB3  
5
TB3  
1
SW-3  
SW-4  
TB4  
5
TB4  
1
TB2  
9
TB2  
5
TB2  
2
TB2  
13  
TB2  
8
SW-5  
TB2  
9
TB2  
1
SW-5  
TB2  
2
REMOVE JUMPER  
REMOVE JUMPER  
TB2  
8
TB2  
5
SW-6  
TB2  
1
TB2  
13  
SW-6  
SW-9A  
TB3  
4
TB3  
3
SW-9A  
TB4  
4
TB4  
3
HIR  
HIR  
TB4  
7
TB3  
3
SW-9B  
TB3  
7
TB4  
3
SW-9B  
4
4
5
5
REMOVED FROM TB3-7  
REMOVED FROM TB4-7  
48FK, JK AND 50FK, JK034-104 UNITS  
SW-7  
DPS  
NC  
SW-8  
WHT  
C
VIO  
NO  
REMOVED  
FROM C-DPS  
GRA  
48FM, AND 50FM, FS034-104 UNITS  
SW7  
PEVFD  
CC  
PEVFD  
S1  
LEGEND  
DPS  
HIR  
Differential Pressure Switch  
Heat Interlock Relay  
PEVFD — Power Exhaust Variable Frequency Drive  
SW  
TB  
Switch  
Terminal Block  
Fig. 32 — Smoke Control Wiring  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODULATING POWER EXHAUST  
48FK,JK and 50FK, JK Units — The tubing for the building  
pressure control (achieved via the Modulating Power Exhaust  
option/accessory) should sample building pressure in the area  
near the entrance lobby (or other appropriate and sensitive  
location) so that location is controlled as closely to design pres-  
sures as possible.  
A differential pressure switch (DPS) is used to control the  
actuator on the modulating discharge damper in exhaust fan  
no. 1. The building pressure (BP) DPS is located in the auxilia-  
ry control box of the unit. See Fig. 33 and 35. Use a nominal  
3/8-in. plastic tubing.  
For instructions on adjusting BP control set points, refer to  
Start-Up, Modulating Power Exhaust section in this book.  
48FM and 50FM,FS Units — The tubing for the building  
pressure control (achieved through the High Capacity Modu-  
lating Power Exhaust) should sample the building pressure in  
the area near the entrance lobby (or other appropriate and sen-  
sitive location) so that the location is controlled as closely to  
design pressures as possible.  
Fig. 33 — Modulating Power Exhaust and Inlet  
Guide Vane Differential Pressure Switch  
(Sizes 034-048)  
A building pressure transducer (BPT) is used to sense the  
building pressure and supply a 4 to 20 mA signal to the power  
exhaust VFD (PE VFD) which controls the speed of exhaust  
fan motor no. 1 and stages on/off power exhaust fan motor  
no. 2 to maintain the building pressure. The BPT is located in  
the auxiliary control box. Use a nominal 1/4-in. plastic tubing.  
For instructions on adjusting the BP control set point, refer  
to Start-Up, High Capacity Modulating Power Exhaust section  
in this book.  
START-UP  
Initial Check  
IMPORTANT: Do not attempt to start unit, even  
momentarily, until all items on the Controls Start-Up  
Checklist (in installation instructions) and the following  
steps have been completed.  
Fig. 34 — Inlet Guide Vane Differential  
Pressure Switch and Variable Frequency Drive  
(Sizes 054-104)  
1. Verify unit has been installed per the Installation Instruc-  
tions included in the unit installation packet.  
2. Verify that all auxiliary components (sensors, controls,  
etc.) have been installed and wired to the unit control  
boxes per these instructions, the unit Installation Instruc-  
tions, and the unit wiring label diagrams.  
3. Verify that air pressure hoses (static, duct, etc.) are prop-  
erly attached, routed, and free from pinches or crimps that  
may affect proper control operation.  
4. Set any control configurations that are required (field-  
installed accessories, etc.). The unit is factory configured  
for all appropriate factory-installed options with the ap-  
plicable controls programmed to the default values.  
5. Check and adjust unit set points. See Table 9.  
6. Check tightness of all electrical connections.  
Fig. 35 — Modulating Power Exhaust Differential  
Pressure Switch (Sizes 054-104)  
7. Perform quick test (see Quick Test Program section on  
page 31).  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Potentiometer Inputs and Ranges  
CONTROL  
POTENTIOMETER  
DESCRIPTION  
LOCATION  
VALID  
DEFAULT VALUE  
45 F if -22 F < P1 < 45 F  
RANGE  
Supply Air  
Set Point  
Economizer  
Position  
Display  
Board  
Economizer  
Motor  
Accessory  
Board  
P1  
P2*  
P3  
45 to 70 F  
0 to 100%  
0 to 80 F  
70 F if P1 > 70 F OR IF P1 < -22 F  
None (0 if P2 is bad)  
Reset Limit  
None (limited to 70 F maximum)  
None  
Demand Limit,  
Single-Step  
P4†  
Main Control Box  
0 to 100%  
DLCM-P1  
DLCM-P2  
DLCM Board  
DLCM Board  
50 to 100%  
0 to 49%  
None  
None  
Demand Limit,  
2-Step  
Minimum Economizer  
Position  
P5*  
Accessory Board  
Accessory Board  
Reset Board  
0 to 100%  
40 to 80 F  
40 to 100 F  
None  
40 F if 0° F < P6 < 40 F OR IF P6 < 95 F  
OR IF P6 < 0  
80 F if 80 F < P6 < 95 F  
Warm-Up  
Set Point  
P6  
Reset  
Temperature  
P7**  
None  
*Optional factory-installed economizer is required. Potentiometer P2 is not a set point.  
Accessory two-step demand limit module is required (which has 2 potentiometers), or a 5 to 20 k-ohm  
field-supplied potentiometer is required for single-step demand limit.  
**Accessory temperature reset is required.  
NOTE: Potentiometers P1-P6 input data to pin terminal connector J3.  
Potentiometer P7 inputs data to pin terminal connector J1.  
Configuration Header — The configuration header is a  
Table 11 — Configuration Header Jumpers  
series of 8 small wires that are broken (open circuit) or unbro-  
ken (closed circuit) in a pattern to indicate several unique char-  
acteristics of the unit. The configuration header is factory set  
and should not be changed; changing the factory setting may  
cause the unit to malfunction.  
JUMPER  
NUMBER  
FACTORY  
SETTING  
FUNCTION  
Unit Type  
MEANING  
1,2  
3,4,5  
6
I
I
VAV Rooftop Unit  
2 Compressors  
TXV  
Qty Compressors  
Expansion Valve  
Power Frequency  
Not Used  
I
Before start-up, visually check the configuration header  
against the factory setting for the unit size. See Table 10 for  
factory settings. See Table 11 for purpose for each jumper.  
7
8
60 Hz  
I
No Significance  
LEGEND  
Thermostatic Expansion Valve  
Table 10 — Configuration Header and  
DIP Switch Factory Settings  
TXV  
VAV — Variable-Air Volume  
Broken Jumper (open circuit)  
Unbroken Jumper (closed circuit)  
I
UNIT SIZES  
034-038,  
048-088  
UNIT SIZE  
044  
UNIT SIZE  
104  
JUMPER OR  
SWITCH NO.  
Header Switch Header Switch Header Switch  
Position Position Position Position Position Position  
DIP Switches — The DIP switches configure the unit for  
several factory-installed options and field-installed accessories,  
plus factory unloaders. The DIP switches are located under a  
plastic enclosure which must be removed for access. See  
Fig. 1. The switches can be field adjusted. Switches must only  
be adjusted when control power is deenergized. See Table 12  
for DIP switch purposes and Table 10 for factory settings of the  
switch positions.  
1
2
3
4
5
6
7
8
Off  
Off  
Off  
Off  
Off  
Off  
I
I
I
I
I
I
I
On/Off*  
On/Off*  
Off  
On/Off*  
On/Off*  
Off  
On/Off*  
On/Off*  
Off  
I
Off  
I
I
On  
I
I
On  
On  
Off  
Off  
I
Off  
Off  
Off  
LEGEND  
DIP  
Dual, In-Line Package  
Disconnect control power before changing the settings of  
the DIP switches. To disconnect control power, open the  
control circuit breaker.  
Broken Jumper (open circuit)  
I
Unbroken Jumper (closed circuit)  
*Depending on factory-installed options or field-installed accessories.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIP SWITCH NO. 1 — Supply Air Set Point (SASP) Reset  
Type. Factory setting is OFF. Do not change.  
DIP SWITCH NO. 2 — SASP Reset Enabled. Factory setting  
is OFF (no SASP reset enabled). If SASP reset has been  
installed, enable it by changing switch position to ON.  
DIP SWITCH NO. 3 — Economizer option. If economizer  
option has been installed, this switch will be ON. If there is no  
economizer installed, this switch will be OFF. For all 48FM  
and 50FM,FS units, this switch will be ON. Confirm setting  
per Table 10. Change only if in error.  
DIP SWITCH NO. 4 — Morning Warm-Up. For 48FK,FM,JK  
units, this switch will be ON (morning warm-up enabled). For  
50FK,JK units with factory-installed electric heaters, this  
switch will be ON. For all other units, this switch will be OFF.  
If accessory electric heaters are installed (for 50FK,JK 034-  
074 units without plenum option), change this switch to ON.  
Potentiometer inputs and ranges are summarized in Table 9.  
Information on individual set point potentiometers (including  
function, location and range data) are shown below:  
SUPPLY AIR SET POINT (Leaving-Air Temperature) (P1)  
— This potentiometer establishes the set point for cooling  
cycle operation of the VAV unit. The VAV control uses a valid  
control range of 45 to 70 F, and the potentiometer has a valid  
range of –22 to 70 F. If the set point is between –22 and 45 F,  
the control will use a value of 45 F. If the set point is outside  
the valid range (less than –22 F or greater than 70 F), an alarm  
condition will be signaled and a default value of 70 F will be  
used.  
ECONOMIZER MINIMUM POSITION (P5) — This potenti-  
ometer specifies the minimum opening position for the  
optional economizer during running periods. It has both a valid  
range and an operational range of 0 to 100%.  
SASP RESET TEMPERATURE (P7) — This potentiometer  
establishes the space temperature at which the control will ini-  
tiate the reset of the SASP (i.e., the unit control begins to raise  
the base SASP, to prevent overcooling of the space). The  
potentiometer has a valid range of 40 to 100 F. Refer to Space  
Temperature Reset section on page 13 for further discussion of  
SASP Reset operation.  
DIP SWITCH NO. 5 — Demand Limit. Factory setting is OFF  
(demand limit not enabled). If Demand Limit (single-step or  
2-step accessory) has been installed, change this switch to ON.  
DIP SWITCHES NO. 6 AND NO. 7 — Unloader Configu-  
ration. These are factory set to match unit size. Confirm set-  
tings per Table 12. Change only if in error.  
Table 12 — DIP Switches  
RESET LIMIT (P3) — Used in conjunction with P7 potenti-  
ometer, this potentiometer establishes the maximum tempera-  
ture for the modified SASP value during the Reset function.  
This potentiometer has a valid range of 0° to 80 F.  
DEMAND LIMIT, SINGLE-STEP (P4) — This potentiome-  
ter establishes the maximum amount of compressor capacity  
permitted by the unit control when single-step demand limit  
operation is implemented (by closing contact set to potentiom-  
eter wiper arm). This potentiometer is field-supplied and  
-installed and will be located in the main control box. The  
valid range is 0% to 100%, which is also the operational range.  
SWITCH  
NO.  
SWITCH  
POSITION*  
FUNCTION  
MEANING  
Reset  
Mode  
Space or Outdoor-Air Reset  
(DO NOT CHANGE)  
1
2
3
4
5
Off  
Reset  
Select  
On  
Off  
Reset Used  
Reset Not Used  
On  
Off  
Enable Economizer  
Disable Economizer†  
Economizer  
Morning  
Warm-Up  
On  
Off  
Enable Morning Warm-Up**  
Disable Morning Warm-Up**  
Demand  
Limit  
On  
Off  
Enable Demand Limit  
Disable Demand Limit  
If the wiper arm is open, all capacity stages can be used.  
When the wiper arm is closed, the capacity is reduced by the  
amount set on potentiometer P4.  
Off, Off  
On, Off  
Off, On  
No Unloaders  
1 Unloader  
6,7  
8
Unloaders  
Not Used  
2 Unloaders  
Off  
No Significance  
DEMAND LIMIT, 2-STEP — The accessory 2-step demand  
limit control is a 2-potentiometer system. The demand limit  
control board (DLCM) accessory board is field-installed in the  
main control box; the 2 control potentiometers are located on  
the DLCM. Potentiometer DLCM-P1 establishes the maxi-  
mum amount of compressor capacity available when SW1 is  
closed and has a valid range is 50% to 100%. Potentiometer  
DLCM-P2 establishes the maximum amount of compressor  
capacity available when SW2 is closed and has a valid range is  
0% to 49%.  
If no power is supplied to the DLCM, all capacity stages  
can be used. When power is supplied to terminal IN1 only, the  
first step of demand limit control is energized and the capacity  
is reduced by the amount set on potentiometer P1. When power  
is supplied to IN2 (or IN1 and IN2), the capacity is reduced by  
the amount set on potentiometer P2.  
MORNING WARM-UP (P6) — This potentiometer estab-  
lishes the set point temperature for the Morning Warm-Up  
function. This is the temperature at which the morning warm-  
up sequence is terminated and VAV cooling operation begins.  
The valid control range is 0° to 95 F, but the control is pro-  
grammed to accept a range of 40 to 80 F. If the set point is  
between 0° and 40 F, the control will use a value of 40 F. If the  
set point is between 80 and 95 F, the control will use a value of  
80 F. If the set point is outside the valid range (less than 0° F or  
greater than 95 F, an alarm condition will be signaled and a  
default value of 40 F will be used.  
LEGEND  
Dual, In-Line Package  
DIP  
*Control circuit breaker must be off before changing the setting of the DIP  
switch.  
No economizer.  
**And/or electric heat (50FK,JK034-074 units without plenum only).  
Adjusting Set Points — Set points for unit operation  
are established via potentiometer settings. Set points for Supply  
Fan controls are set at the VFD keypad (if installed) or at the  
IGV differential pressure switch (DPS1) (if IGV option in-  
stalled). Set points for modulating power exhaust (option or ac-  
cessory) are set at the differential pressure switch (DPS2).  
Set points for high capacity modulating power exhaust  
(48FM and 50FM,FS units) are set at the power exhaust VFD  
keypad.  
Potentiometers — All of the set point potentiometers  
must be set before the unit is started in order for the unit to  
function properly. Each of the potentiometers has a valid range  
that is used by the control. The valid range is defined as the po-  
tentiometer’s resistance value that the control will not consider  
to be in error. This is usually between 10% and 90% of the po-  
tentiometer’s total resistance. The control has been pro-  
grammed to accept an operational range for the potentiometer,  
which may not be the same as the valid range.  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Supply Fan Control with IGV Option — The inlet  
guide vane option will modulate the supply fan airflow in order  
to maintain the static pressure in the supply duct. The set point  
for duct static pressure is established at the differential pressure  
switch for the IGV control.  
SIZE 034-048 UNITS — The inlet guide vane differential  
pressure switch is located in the auxiliary control box mounted  
in the corner under the side air hood that is next to the access  
door marked FILTER SECTION. To gain access to this control  
box, remove the auxiliary control box cover. When replacing  
cover, be sure to properly secure it in order to prevent water  
from being drawn into the unit. See Fig. 36 and 37.  
SIZE 054-104 UNITS — The inlet guide vane differential  
pressure witch is mounted on an upright located behind the  
supply-fan motor. See Fig. 36-38.  
The IGV differential pressure switch has an adjustable set  
point range of 1.1 to 3.5 in. wg. and a factory setting of  
1.9 in. wg.  
*The inlet guide vane differential pressure switch for the 034-048  
units is located in the back of the unit in the auxiliary control box. Its  
location is not shown in this figure.  
To adjust set point, turn set point adjusting screw (see  
Fig. 39) clockwise to decrease set point and counterclockwise  
to increase set point. This switch also has an adjustable null  
span. The null span is the pressure change that can be made  
without contacts opening or closing. It is adjustable from  
0.06 in. wg to 0.17 in. wg when set point is at minimum posi-  
tion (1.1 in. wg) and 0.11 in. wg to 0.31 in. wg when set point is  
at maximum position (3.5 in. wg). To adjust null span, turn a  
null adjusting screw (Fig. 39) clockwise to decrease span and  
counterclockwise to increase span. All switches leave factory  
with null span set at maximum position. The smaller the null  
span, the closer the pressure will be maintained to desired set  
point.  
Fig. 36 — Inlet Guide Vane Motor,  
50FK,JK034-074 Units  
Supply Fan Control with VFD Option — The VFD  
option will modulate Supply Fan motor (and thus wheel) speed  
to maintain the static pressure in the ductwork. Set point for the  
VFD option is set at the VFD, using the display keyboard on  
the front of the VFD enclosure. See Fig. 40.  
NOTE: The VFD will always provide the proper phase  
sequence to the supply-fan motor. The supply-fan motor oper-  
ates in proper rotation regardless of the phase sequence to the  
unit. If, upon start-up, the outdoor fans operate backwards but  
the supply fan operates in the correct direction, reverse any two  
leads to the main terminal block. All fans will then operate in  
the correct direction.  
*The inlet guide vane differential pressure switch for the 034-048  
units is located in the back of the unit in the auxiliary control box. Its  
location is not shown in this figure.  
Fig. 37 — Inlet Guide Vane Motor, 48FK,JK, 50FJ,JY,  
and 50FJX,FJY,FKX,FKY034-074 Units  
The supply duct pressure transducer has a range of 0.0 to  
5.0 in. wg. Its output is a 4 to 20 mA signal, scaled to this  
range. The VFD translates this 4 to 20 mA input signal to rep-  
resent a frequency value over the control range of 0 to 60 Hz.  
The factory default set point is 30 Hz, representing a supply  
duct pressure of 2.5 in. wg.  
Factory-installed optional VFD is located near the supply  
fan and motor. During any service work or programming at  
the VFD, operation of the fan and motor is not desirable  
and may be dangerous. Either disable the unit supply fan  
(following instructions below) or install the accessory VFD  
remote display accessory.  
Fig. 38 — Inlet Guide Vane Motor,  
Size 078-104 Units  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DISABLE SUPPLY FAN MOTOR — To disable the supply  
fan motor and change programming of VFD set point:  
CAPACITOR  
1. Turn off Indoor Fan Circuit Breaker (IFCB). This will re-  
move power to the VFD.  
NULL  
ADJUSTMENT  
COM  
N.C.  
N.O.  
Ensure the “CHARGE” lamp on the VFD is unlit. This  
may take up to 4 minutes. The “CHARGE” lamp indicates  
that the main capacitors in the VFD are charged. Internal  
components of the VFD should not be touched until the  
“CHARGE” lamp is completely out. Electrical shock can  
cause injury or death.  
SET  
2. Wait for the VFD display to go blank and remove VFD  
cover without touching any interior components.  
POINT  
ADJUSTMENT  
3. Ensure that the charge indicator lamp is out which indi-  
cates that the VFD is discharged. The lamp is located on  
the upper right hand corner of the terminal block. If still  
lit, wait until lamp goes completely out. This may take  
several minutes.  
4. Remove jumper from terminals ST-CC (see Fig. 41) and  
replace VFD cover.  
5. Turn on IFCB.  
6. The drive output will now be disabled but the program-  
ming can be changed.  
SET  
POINT  
INDICATOR  
LEGEND  
COM Common  
N.C. Normally Closed  
N.O. Normally Open  
Fig. 39 Differential Pressure Switch for Inlet  
Guide Vane and Static Pressure Control Option  
and Modulating Power Exhaust Option  
7. Change VFD set point according to Table 14 shown  
on page 30.  
HZ  
8. Once the program changes are completed, turn off IFCB.  
PERCENT  
SECONDS  
KW/AMPS/VOLTS  
9. Wait for the VFD display to go blank and remove VFD  
cover without touching any interior components.  
10. Ensure that the charge indicator lamp is out which indi-  
cates that the VFD is discharged. The lamp is located on  
the upper right hand corner of the terminal block. If still  
lit, wait until lamp goes completely out. This may take  
several minutes.  
SETUP  
PROGRAM  
RUN  
MONITOR  
11. Replace jumper to terminals ST-CC.  
12. Replace VFD cover.  
13. Turn on IFCB to enable the drive.  
STOP  
READ  
For additional information on the VFD (including basic  
troubleshooting, factory jumper arrangements, and Carrier fac-  
tory defaults programming), refer to Troubleshooting, Supply  
Fan Variable Frequency Drive section (page 52).  
WRITE  
RESET  
LOCAL/REMOTE  
MANUAL/AUTO  
IMPORTANT: The Carrier factory default values for the  
VFD may be different than the default values of the  
manufacturer. Refer to the Service section when check-  
ing default values.  
SPEED CTRL  
RUN MODE  
Fig. 40 Variable Frequency Drive Keypad  
P24 RES RR  
F
R
S1 S2 S3 S4 RCH P24 LOW LOW  
CC RX PP IV FP FLC FLB FLA  
DETERMINE VFD SET POINT — The unit of measure for  
the Duct Pressure set point at the VFD is output frequency  
(Hz), corresponding to the desired DP set point (DPSP) in  
inches of water gage (in. wg). To convert desired DPSP into  
the VFD set point, refer to Table 13. Locate the pressure value  
in the table closest to the desired DPSP for this installation  
and use the corresponding VFD set point (Hz) value. If neces-  
sary, interpolation between duct static pressure values is  
permissible.  
ST  
FM AM CC  
REMOVE  
JUMPER  
Fig. 41 Jumper Removal to Disable Motor  
ADJUST VFD SET POINT — To adjust the VFD set point,  
the VFD must be powered; however, since it is located near the  
supply fan and motor, operation of the fan and motor is not  
desirable. Either disable the Supply Fan or install the accessory  
VFD remote display accessory.  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 13 VFD Set Point (Frequency Command) for Duct Pressure  
PRESSURE  
(in. wg)  
CONTROL SIGNAL  
(mA)  
PRESSURE  
(in. wg)  
VFD SET POINT  
(Hz)  
CONTROL SIGNAL  
(mA)  
VFD SET POINT (Hz)  
0.00  
0.25  
0.50  
0.75  
1.00  
1.25  
1.50  
1.75  
0
3
6
4.0  
4.8  
5.6  
6.4  
7.2  
8.0  
8.8  
9.6  
2.00  
2.25  
2.50  
2.75  
3.00  
3.25  
3.50  
24  
27  
30  
33  
36  
39  
42  
10.4  
11.2  
12.0  
12.8  
13.6  
14.4  
15.2  
9
12  
15  
18  
21  
Table 14 Changing the VFD Set Point (Frequency Command)*  
KEY OPERATION  
LED MESSAGE  
EXPLANATION  
Standard Monitor Mode (output frequency). If drive is disabled, display  
will read OFF. If enabled, display will show current output frequency  
XX.X or OFF  
↓↑  
60.0  
45.0 (flashing)  
Pressing arrow key once will display the current frequency set point  
Pressing up/down arrow keys changes the desired set point  
When the Read/Write key is pressed, the parameter name (FC) and the new value (45.0)  
FC and 45.0 (flashing) will alternately flash to indicate that the new value has been stored. After 2 cycles, the display will  
return to the standard monitor mode.  
READ  
WRITE  
Standard Monitor Mode (output frequency). If drive is disabled, display  
will read OFF. If enabled, display will show current output frequency  
XX.X or OFF  
*Choose set point from Table 13 according to desired duct pressure or Table 15 according to desired building pressure.  
power exhaust fan motor no. 2 to maintain the building pres-  
Modulating Power Exhaust (Option or Acces-  
sory) (48FK,JK and 50FK,JK Units) The Mod-  
ulating Power Exhaust system will maintain space pressure by  
modulating power exhaust fan no. 1 and staging power exhaust  
fan no. 2. Building pressure set point is established at the mod-  
ulating power exhaust differential pressure switch (DPS).  
sure. The set point for the building pressure control is set at the  
power exhaust VFD using the keyboard on the front of the  
power exhaust VFD enclosure. See Fig. 40.  
NOTE: The VFD will always provide the proper phase  
sequences to the power exhaust fan motor.  
SIZE 034-048 UNITS — The modulating power exhaust dif-  
ferential pressure switch is located in the auxiliary control box  
mounted in the corner next to the power exhaust motor door.  
To gain access to this control box, remove the auxiliary control  
box cover. When replacing cover, be sure to properly secure it  
in order to prevent water from being drawn into the unit. See  
Fig. 33.  
SIZE 054-104 UNITS — The modulating power exhaust dif-  
ferential pressure switch is mounted below the auxiliary con-  
trol box next to the access door labeled FILTER SECTION.  
See Fig. 35.  
DIFFERENTIAL PRESSURE SWITCH — The modulating  
power exhaust DPS has a set point range of 0.5 in. wg to  
–0.5 in. wg. Factory setting is +0.1 in. wg. To adjust set point,  
turn set point adjusting screw (see Fig. 39) clockwise to  
decrease set point and counterclockwise to increase set point.  
This switch also has an adjustable null span. The null span is  
the pressure change that can be made without contacts opening  
or closing. It is adjustable from 0.06 in. wg to 0.14 in. wg when  
set point is at minimum position (–0.5 in. wg) and 0.07 in. wg  
to 0.14 in. wg when set point is at maximum position  
(+0.5 in. wg). To adjust null span, turn null adjusting screw  
(Fig. 39) clockwise to decrease span and counterclockwise to  
increase span. All switches leave factory with null span set at  
maximum position. The smaller the null span, the closer the  
pressure will be maintained to desired set point.  
The exhaust fan motor operates in proper rotation regardless  
of the phase sequence to the unit. If, upon start-up, the outdoor  
fans operate backwards but the exhaust fan operates in the cor-  
rect direction, reverse any two leads on the main terminal  
block. All fans will then operates in the correct direction.  
The building pressure transducer has a range of –0.5 to  
+0.5 in. wg. The output is a 4 to 20 mA signal, scaled to this  
range. The VFD translates the 4 to 20 mA signal to represent a  
frequency value over the control range of 0 to 60 Hz. See  
Table 15. The set point for duct pressure control is established  
at the power exhaust VFD keypad in terms of Hz. The factory  
default set point is 30 Hz, representing a building pressure of  
0.0 in. wg.  
DETERMINE POWER EXHAUST VFD SET POINT —  
The unit of measure for the building pressure set point (BPSP)  
at the power exhaust VFD is output frequency (Hz), represent-  
ing the desired BPSP (in. wg). To convert the desired BPSP  
into the power exhaust VFD set point, refer to Table 15. Locate  
the pressure value in the table closet to the desired BPSP for  
the application and use the corresponding set point (Hz) value.  
If necessary, interpolation between duct static pressure values  
is permissible.  
ADJUST PE VFD SET POINT — To adjust the PE VFD set  
point, the PE VFD must be powered. Since it is located in the  
indoor section of the unit, use caution to ensure that the service  
access door is blocked open and will not close suddenly.  
High Capacity Power Exhaust (48FM and  
50FM,FS Units) The power exhaust VFD will modu-  
late the power exhaust fan motor no. 1 speed and stage (on/off)  
Change PE VFD set point according to Table 14.  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 PE VFD Set Point (Frequency  
display board will be energized. This indicates that control sys-  
tem is ready to run quick test program.  
Command) for Building Pressure  
VFD  
SET POINT  
(Hz)  
CONTROL  
SIGNAL  
(mA)  
VFD  
SET POINT  
(Hz)  
CONTROL  
SIGNAL  
(mA)  
IMPORTANT: Do not allow unit control circuit to  
remain energized with 20 showing on display for more  
than 2 minutes. If display button is not pressed within  
this time period, control will attempt to start unit.  
PRESSURE  
(in. wg)  
PRESSURE  
(in. wg)  
0.50  
0.45  
0.40  
0.35  
0.30  
0.25  
0.20  
0.15  
0.10  
0.05  
0.0  
3.0  
4.00  
4.80  
5.60  
6.40  
7.20  
8.00  
8.80  
9.60  
10.40  
11.20  
0.00  
0.05  
0.10  
0.15  
0.20  
0.25  
0.30  
0.35  
0.40  
0.45  
0.50  
30.0  
33.0  
36.0  
39.0  
42.0  
45.0  
48.0  
51.0  
54.0  
57.0  
60.0  
12.00  
12.80  
13.60  
14.40  
15.20  
16.00  
16.80  
17.60  
18.40  
19.20  
20.00  
6.0  
9.0  
For each step of the 33-step program, display button must  
be pressed twice. On first press, step number is displayed;  
second press initiates required action and appropriate code is  
displayed.  
NOTE: The step number is a numeral followed by a decimal  
point (a 2-digit number has a decimal point after each  
numeral). The action code number is one or 2 digits with no  
decimal point(s).  
12.0  
15.0  
18.0  
21.0  
24.0  
27.0  
IMPORTANT: Once quick test is initiated, display but-  
ton must be pressed at least once every 10 minutes for  
control to remain in Quick Test mode. If button is not  
pressed within this time, control will attempt to start the  
unit.  
START UNIT  
To start unit:  
To recheck any step in quick test program, control must be  
recycled by turning unit control switch off for a few seconds,  
and then turning it back on again. Restart quick test program as  
described above and proceed through quick test steps. Press  
display button twice for each step until step to be rechecked is  
reached.  
1. Close the unit-mounted ON/OFF switch (located in the  
main control box).  
2. Close the field-supplied and -installed timeclock (or con-  
trol) switch (contacts located at Terminals 1 and 2 (TB3  
for 034-048, TB4 for 054-104).  
The quick test program is divided into 3 sections as de-  
scribed below and shown in Tables 16-18.  
1. Quick Test Steps 1.-1.3. — Unit Configuration and  
Switch Check  
IMPORTANT: The field-supplied and installed switch  
(or timeclock) MUST BE CLOSED to put unit in  
Occupied mode. Unit WILL NOT START until this is  
accomplished.  
The microprocessor in unit control system is pro-  
grammed by 2 switch assemblies located on processor  
board (Fig. 1). The configuration header is factory set and  
cannot be changed in the field. The DIP switch assembly  
contains 8 microswitches that must be set in accordance  
with the various options selected by the customer. All  
DIP switches should be checked and set to proper posi-  
tion for options selected prior to the quick test. See Con-  
figuration of Header and DIP Switch Assembly section  
on page 5 for factory switch settings. The DIP switch  
functions and display codes are shown in Table 16.  
3. Initialization mode begins (see Operating Information  
section on page 34 for complete description of sequences  
and display codes).  
4. Run Quick Test. If the display button is pressed during  
the initialization mode period, the unit will run its self-  
diagnostic routine. When this is in effect, an 88 will ap-  
pear in the display screen. Refer to Quick Test Program  
section below, for instructions on completing the Quick  
Test program.  
Quick Test Program Turn on power to unit.  
2. Quick Test Steps 1.4.-2.3. — Thermistor and Set Point  
Potentiometer Check  
IMPORTANT: The field-supplied switch (or timeclock)  
must be closed to put unit into the occupied mode.  
In these steps, the microprocessor checks resistance val-  
ues of all sensors and set point potentiometers to ensure  
that they are functional, connected properly, and set with-  
in proper range for unit configuration.  
Nominal resistance values for all sensors range from  
363,000 to 219 ohms in accordance with Table 19. Nor-  
mal display code for good sensors and potentiometers  
is 1. A display code of 0 indicates a faulty potentiometer,  
thermistor or wiring. A 0 display also indicates that op-  
tion is not being used.  
The quick test program utilizes the 2-digit LED display (see  
Fig. 6) on the set point board to show status of all input and  
output signals to microprocessor. Display action and quick test  
procedures are described below.  
The quick test program is a 33-step program that provides a  
means of checking all input and output signals of controls prior  
to unit start-up. This check ensures that all control options,  
thermistors, and control switches are in proper working order.  
When unit control circuit is switched to Occupied mode, a  
20 will appear on the display. Immediately press display button  
once. An 88 will appear on the display and alarm light on  
Table 17 shows thermistor and set point potentiometer  
functions and quick test display codes.  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 16 Quick Test, Unit Configuration and Switch Check  
QUICK  
TEST  
NORMAL  
DESCRIPTION  
Type Unit Air-Cooled VAV  
CONTROL SWITCH  
Configuration Header  
DISPLAY  
STEP NO.  
1.  
2.  
01  
2
No. of Compressors  
Configuration Header  
DIP Switch No. 6 and 7  
No. of Unloaders  
(034,038,048-088)  
3.  
2
1
(044, 104)  
4.  
5.  
60  
60-Hertz Power  
Configuration Header  
DIP Switch No. 2  
0 No Reset (Switch Off)  
1 Reset On (Switch On)  
0 or 1  
0 No Economizer (Switch Off)  
1 Economizer On (Switch On)  
DIP Switch No. 3  
DIP Switch No. 4  
DIP Switch No. 5  
6.  
7.  
0 or 1  
0 or 1  
0 No Warm-Up (Switch Off)  
1 Warm-Up Used (Switch On)  
0 Demand Limit Not Used  
(Switch Off)  
1 Demand Limit Used  
(Switch On)  
8.  
0 or 1  
0 Enthalpy Switch Open  
1 Enthalpy Switch Closed  
EC  
9.  
0 or 1  
1.0.  
1.1.  
1.2.  
1.3.  
1
1
1
1
1 Low-Pressure Switch Closed  
1 Low-Pressure Switch Closed  
No Circuit 1 Oil Pressure Switch  
No Circuit 2 Oil Pressure Switch  
Low-Pressure Switch 1  
Low-Pressure Switch 2  
None*  
None*  
LEGEND  
DIP Dual, In-Line Package  
EC Enthalpy Control  
VAV Variable Air Volume  
*Units are not equipped with oil pressure switches.  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 17 Quick Test, Thermistor and Potentiometer Check  
QUICK  
TEST  
STEP NO.  
NORMAL  
DISPLAY  
THERMISTOR OR  
POTENTIOMETER*  
DESCRIPTION  
1 Thermistor OK  
Supply Air  
1.4.  
1.5.  
1.6.  
1.7.  
1
1
1
1
0 Thermistor Faulty  
Thermistor (T1)  
1 Thermistor OK  
0 Thermistor Faulty  
1 Thermistor OK  
0 Thermistor Faulty  
1 Thermistor OK  
0 Thermistor Faulty  
Return Air  
Thermistor (T2)  
Circuit 1 Condenser Thermistor  
(T3)  
Circuit 2 Condenser Thermistor  
(T4)  
1 Thermistor or Potentiometer OK  
0 Thermistor or Potentiometer Faulty or  
Option not used  
Accessory Space Temperature Thermistor (T10)  
or Accessory Reset Potentiometer (P7)  
1.8.  
1
1 Potentiometer OK  
Supply-Air Set Point  
Potentiometer (P1)  
Accessory Reset Limit  
Potentiometer (P3)  
Accessory Demand Limit  
Potentiometer (P4)  
1.9.  
2.0.  
2.1.  
1
1
1
0 Potentiometer Faulty  
1 Potentiometer OK  
0 Potentiometer Faulty or Option not used  
1 Potentiometer OK  
0 Potentiometer Faulty or Option not used  
1 Potentiometer OK  
Minimum Position  
Economizer  
2.2.  
2.3.  
1
1
0 Potentiometer Faulty or Option not used  
Potentiometer (P5)  
1 Potentiometer OK  
0 Potentiometer Faulty or Option not used  
Warm-Up Set Point  
Potentiometer (P6)  
*Potentiometer P2 is not listed since it is not part of the quick test. If on unit start-up a Code 83 is displayed, check potentiometer P2.  
Table 18 Quick Test, Output Relay Check  
QUICK  
NORMAL  
DISPLAY  
TEST  
DESCRIPTION  
RELAY NUMBER  
STEP NO.  
2.4.  
2.5.  
2.6.  
2.7.  
2.8.  
2.9.  
3.0.  
3.1.  
3.2.  
3.3.  
1
1 Open Economizer or Open Relay if no Economizer  
1 Close Economizer or Close Relay if no Economizer  
1 Energize Fan Relay and Heat Relay  
Energize Stage 1 Condenser Fan(s)  
Energize Stage 2 Condenser Fan(s)  
Energize Compressor 1†  
K7  
1
K8  
1
K9* and K10  
1
K11  
K12  
K1  
1
0 then 1 then 0  
0
Energize Unloader 2; Not Used (044, 104)  
Energize Unloader 1  
K2  
0
K3  
0 then 1 then 0  
0
Energize Compressor 2†  
K5  
Not Used  
K6  
LEGEND  
CR Control Relay  
*K9 (fan relay) will remain on for duration of quick test.  
Compressor will be energized for 10 seconds. Zero indicates open CR; 1 indicates closed CR.  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 19 Sensor Resistance Values  
enthalpy is good. As long as the outdoor-air enthalpy is accept-  
able, no mechanical cooling will take place until the economiz-  
er dampers are fully open. The rest of the steps and the opera-  
tional sequence vary due to the number of compressors and un-  
loaders. Refer to Operating Sequence section on page 35 for  
the unit stages of operation.  
CODES 20 THROUGH 30 AND 88, OPERATIONAL STA-  
TUS — These codes indicate special operational modes, such  
as initialization, morning warm-up, temperature reset, demand  
limit, or an internal failure of the board. Codes 23-25 and  
27-29 are not used on these units.  
Initialization — When the control is turned on, the display  
shows a 20 for approximately 2 minutes to indicate that the  
control is in the initialization mode. During this time, the econ-  
omizer dampers open and close to determine the resistance  
range of the economizer position potentiometer (P2) for full  
economizer operation. The processor loads the necessary con-  
stants for proper unit operation and checks the thermistors and  
other potentiometers for their values and validity. After the ini-  
tialization period, the display screen goes blank until the dis-  
play button is pressed. If the display button is pressed during  
the 2-minute initialization period, the control goes into the  
Quick Test mode.  
Temperature Reset — If the unit is equipped with the accesso-  
ry temperature reset package, and DIP switch 2 is in the ON  
position, the unit will reset the supply-air temperature to a cal-  
culated value when necessary. When this condition is in effect,  
a 21 will appear in the display.  
TEMP RESISTANCE TEMP RESISTANCE TEMP RESISTANCE  
(F)  
(Ohms)  
(F)  
(Ohms)  
(F)  
(Ohms)  
60  
55  
50  
45  
40  
35  
30  
25  
20  
15  
10  
5  
362,640  
297,140  
245,245  
202,841  
168,250  
139,960  
116,820  
98,420  
82,665  
69,685  
58,915  
50,284  
42,765  
36,475  
31,216  
26,786  
23,164  
19,978  
17,276  
14,980  
13,085  
45  
50  
11,396  
9,950  
8,709  
7,642  
6,749  
5,944  
5,249  
4,644  
4,134  
3,671  
3,265  
2,913  
2,600  
2,336  
2,092  
1,879  
1,689  
1,527  
1,377  
1,244  
1,126  
150  
155  
160  
165  
170  
175  
180  
185  
190  
195  
200  
205  
210  
215  
220  
225  
230  
235  
240  
1,020  
929  
844  
768  
699  
640  
585  
535  
490  
449  
414  
380  
350  
323  
299  
276  
255  
236  
219  
55  
60  
65  
70  
75  
80  
85  
90  
95  
100  
105  
110  
115  
120  
125  
130  
135  
140  
145  
0
5
10  
15  
20  
25  
30  
35  
40  
3. Quick Test Steps 2.4.-3.3. — Output Relay Check  
These quick test steps allow microprocessor to check out-  
put signals from relay boards in unit control system. In  
addition, operation of all the condenser fans, compres-  
sors, and economizer (if equipped) are checked at each  
step.  
Normal display for Steps 2.4. through 2.8. is 1. In Steps  
2.9. through 3.2., each compressor and unloader is started  
and allowed to run for approximately 10 seconds. At  
startup, a 0 will appear on the display followed by a  
1 (Steps 2.9. and 3.2.) in a few seconds. Steps 3.0. and  
3.1. will always be 0 since there are unloaders, and Step  
3.3. will always be zero since it is not used.  
At end of the 10-second time period, a 0 will return to the  
display board indicating that test step has been success-  
fully completed (Steps 2.9. and 3.2.). The 1 indicates that  
was tested.  
Fan and compressor operating sequence for quick test  
Steps 2.4. through 3.3. are shown in Table 18.  
Demand Limit — If the unit is equipped with the accessory  
demand limit control module or the field-supplied, single-step  
demand limit potentiometer, and DIP switch 5 is in the ON  
position, the unit will limit the capacity stages to a predeter-  
mined value. When this condition is in effect, a 22 will appear  
in the display.  
Morning Warm-Up — If the morning warm-up heat routine is  
enabled using DIP switch 4, and conditions of the occupied  
space warrant, the unit will begin the morning warm-up rou-  
tine. When this condition is in effect, a 26 will appear in the  
display.  
If the quick test steps do not operate as described above, a  
defect exists in one or more of the following: relay being test-  
ed, electronic control, or unit wiring. Determine problem and  
correct.  
Internal Failure — If the unit detects an internal fault (such as  
a time measurement failure), or detects an incorrect voltage on  
an input channel, a 30 will be displayed, and the unit will shut  
down.  
Quick Test — If the display button is pressed during the ini-  
tialization period of the processor, the unit will run its self-diag-  
nostic routine. When this is in effect, an 88 will appear in the  
display screen.  
CODES 51 THROUGH 87, DIAGNOSTIC INFORMATION  
— These codes indicate diagnostic information when there is a  
unit problem such as a faulty thermistor, potentiometer, or  
compressor fault. Refer to Diagnostic Codes section on  
page 45 for more details. Codes 53, 54, 57, 58, 61, 62, 65-69,  
73, 74, and 77-80 are not used on these units.  
Under normal operation, only the stage number is displayed  
when the display button is pressed. If a status or overload code  
is displayed, the display will rotate every 2 seconds and will  
display up to 3 codes. Overload information takes priority over  
all other codes. The codes are stored in the microprocessor as  
long as the board remains energized.  
OPERATING INFORMATION  
Digital Display The VAV control system uses a 2-digit  
LED display located on the display board to display operation-  
al information and diagnostic codes.  
CODES 0 THROUGH 8, CAPACITY STEPS — These codes  
indicate the number of cooling stages active at the time the dis-  
play button is pressed. The highest code indicated on the dis-  
play will be 6 for the 034,038 and 048-088 units, 4 for the 044  
units, and 8 for the 104 units.  
Capacity steps are directly related to pin terminal connector  
J6 output. At step zero, the unit has no mechanical cooling on,  
and the economizer may or may not be operating (depending  
on the outdoor air conditions). Once a cooling load is detected  
(T1 thermistor reads above the supply-air set point), the econo-  
mizer will begin modulating to meet the load if the outdoor  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Compressors, unloaders, and condenser fans will be cycled  
to maintain a supply-air temperature 2° F below the potentiom-  
eter P1 set point once the mechanical cooling stages begin.  
Each unit’s cycling is slightly different, and is based on the  
number of compressors and unloaders. The operational loading  
sequence of compressors is as follows:  
During the start-up of the lead compressor for each circuit,  
the low-pressure switch will be bypassed for 120 seconds to  
prevent nuisance trips of the low-pressure switch. After start-  
up, a low-pressure trip will be ignored for 30 seconds by the  
processor.  
SIZE 034,038 AND 048-088 UNITS — These units have 2  
compressors and 2 unloaders on compressor 1. See Fig. 42 and  
43 for compressor and condenser-fan motor locations. The  
operating sequence is as follows:  
Stage 1 Relays K1, K2, and K3 are energized. Compressor  
no. 1 starts with both unloaders energized. Compres-  
sor no. 1 runs at 1/3 capacity. The crankcase heater for  
this compressor has been deenergized, and the first  
stage of condenser fans have been energized. Out-  
door (condenser) fan motor no. 1 (OFM1) has started  
on all units.  
Operating Sequence The sequence presented be-  
low assumes that the unit is equipped with heat for morning  
warm-up and an economizer. If these items are not enabled  
with the appropriate DIP switches, the processor bypasses  
these subroutines. This sequence is also based on an EPROM  
(erasable, programmable, read-only memory) processor chip  
with the identification ‘HT204485-1-XX,’ where ‘XX’ is re-  
placed by a 2-digit number representing the current software  
version. See Fig. 1 for EPROM chip location.  
When power is applied to the occupied mode relay (OMR)  
through the closure of either a field-installed timeclock or a  
field-installed switch in the occupied space, the unit will begin  
its initialization mode.  
A 20 will appear in the display screen, and the initialization  
period will last approximately 2 minutes. During this time, the  
economizer dampers open and close to determine the resis-  
tance range for full economizer operation of the economizer  
position potentiometer (P2). The processor loads the necessary  
constants for unit operation, and also checks the thermistors  
and other potentiometers for their values and validity. After the  
initialization period, the screen goes blank until the display but-  
ton is pressed.  
Stage 2 Relays K1 and K3 are energized. Compressor no. 1 is  
running with unloader 1 (U1) energized. The com-  
pressor is now operating at 2/3 capacity.  
Stage 3 Relay K1 is energized. Compressor no. 1 is fully  
loaded.  
Use caution during this time (after initialization when the  
screen is blank), because the unit supply and return fans  
could start at any time. Personal injury could result from  
contact with rotating fans.  
Stage 4 Relays K1, K2, K3, and K5 are energized. Compres-  
1
sor no. 1 is running at /3 capacity, and compressor  
Once the initialization period is complete, the supply fan be-  
gins operation. While the fan is operating, the economizer  
dampers are closed and return air from the building is being  
circulated. After 2 minutes, the processor checks the resistance  
value of thermistor T2. If T2 temperature sensed is 5° F or  
more below the set point of the morning warm-up potentiome-  
ter (P6), the unit will begin the morning warm-up routine, and  
a 26 will be displayed.  
no. 2 is running at full capacity. The crankcase heater  
for compressor no. 2 has been deenergized.  
Stage 5 Relays K1, K3, and K5 are energized. Compressor  
no. 1 is running at 2/3 capacity, and compressor no. 2  
is running at full capacity.  
Stage 6 Relays K1 and K5 are energized. Both compressors  
are running fully loaded.  
Size 034 and 038 units have 2 condenser fans, one of which  
is controlled by the microprocessor. The OFM1 is energized  
with compressor no. 1. The OFM2 is controlled by the proces-  
sor and is cycled based on input from circuit thermistor T3 or  
T4.  
Size 048 units have one fan that can be controlled by the  
processor. The other 2 are controlled by the compressors. The  
OFM1 is energized by compressor no. 1, and OFM3 is ener-  
gized by compressor no. 2. The OFM2 is cycled by the proces-  
sor based on input from either circuit (thermistors T3 and T4).  
Unit heat will be energized through the heat interlock relay  
(HIR), and all of the occupied space air terminals will open.  
The unit will continue heating the space until the return-air  
temperature is within 2° F of set point. The unit will then shut  
off the heat and continue to circulate air. The unit will cycle in  
and out of the Heating mode until the return-air temperature  
reaches the morning warm-up set point (P6). Once morning  
warm-up has been terminated, the unit cannot return to morn-  
ing warm-up until the unit is powered down and restarted. This  
action signals a return to the Occupied mode.  
NOTE: Occupied heat is NOT AVAILABLE on these units.  
On size 054,064 units, the first 2 condenser fans energize  
with the compressors; compressor no. 1 controls OFM1, and  
compressor no. 2 controls OFM2. The OFM3 and OFM4 are  
staged by the microprocessor based on the condensing temper-  
ature input from thermistor T3 or T4.  
On size 074-078 units, the first 3 condenser fans energize  
with the compressors; compressor no. 1 controls OFM1, and  
compressor no. 2 controls OFM2 and OFM3. The OFM4 and  
OFM5 are staged by the microprocessor based on condensing  
temperature input from either circuit’s T3 or T4 thermistor.  
On Size 088 units, the first 4 condenser fans energize with  
the compressors; compressor no. 1 controls OFM1 and OFM3,  
and compressor no. 2 controls OFM2 and OFM4. The OFM5  
and OFM6 are staged by the microprocessor based on  
condensing temperature input from either circuit’s T3 or T4  
thermistor.  
Once out of the morning warm-up routine, the unit will be-  
gin its cooling routine based on the supply-air set point (P1). At  
step zero, the unit has no mechanical cooling on, and the econ-  
omizer may or may not be operational. The economizer will  
move to the minimum position determined by potentiometer  
P5 if no cooling load is detected. Once a cooling load is detect-  
ed by thermistor T1 sensing a temperature higher than the cool-  
ing demand set point (P1), the economizer will begin modulat-  
ing to meet the load if the outdoor enthalpy is good. The pro-  
cessor will attempt to maintain a supply-air temperature of P1  
± 2° F by modulating the economizer dampers.  
No mechanical cooling will take place until the economizer  
dampers are fully open (if the outdoor-air enthalpy permits). If  
the economizer is unable to meet the cooling demand, then me-  
chanical cooling is used in conjunction with the economizer. If  
the economizer is unable to meet the load due to unacceptable  
outdoor-air enthalpy, the dampers will return to the minimum  
position as determined by P5.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SIZE 044 UNITS — These units have 2 compressors and 1  
unloader on compressor no. 1. See Fig. 42 for compressor and  
condenser fan motor locations. The unit operating sequence is  
as follows:  
Stage 5 Relays K1, K3, K5, and K5 are energized. Compres-  
2
sor no. 1 runs at /3 capacity and compressors no. 2  
and no. 4 are running at full capacity. The crankcase  
heater on compressor no. 4 is deenergized. Fans  
OFM1, OFM2, OFM3, and OFM4 are operating.  
Stage 1 Relays K1 and K3 are energized. Compressor no. 1  
starts with the unloader energized. Compressor no. 1  
Stage 6 Relays K1, K5, and K6 are energized. Compressors  
no. 1, no. 2, and no. 4 are running fully loaded.  
1
is running at /2 capacity. The crankcase heater on  
compressor no. 1 has been deenergized, and the first  
stage condenser fan has been energized. Outdoor  
(condenser) fan motor no. 1 (OFM1) has started.  
Stage 7 Relays K1, K2, K3, K5, and K6 are energized. Com-  
pressor no. 1 runs at 2/3 capacity and compressors no.  
2, no. 3, and no. 4 are running at full capacity. Fans  
OFM1, OFM2, OFM3, and OFM4 are operating.  
Crankcase heater for compressor no. 3 is deener-  
gized.  
Stage 8 Relays K1, K2, K5, and K6 are energized. Compres-  
sors no. 1, no. 2, no. 3, and no. 4 are running fully  
loaded.  
On size 104 units, the first 4 condenser fans energize with  
the compressors; circuit no. 1 compressors control OFM1 and  
OFM3, and circuit no. 2 compressors control OFM2 and  
OFM4. The OFM5 and OFM6 are staged by the microproces-  
sor based on condensing temperature input from either circuit’s  
T3 or T4 thermistor.  
Stage 2 Relay K1 is energized. Compressor no. 1 is fully  
loaded.  
Stage 3 Relays K1, K3, and K5 are energized. Compressor  
no. 1 is running at 1/2 capacity, and compressor no. 2  
is running at full capacity. The crankcase heater for  
compressor no. 2 is deenergized. The second stage  
condenser fan has been energized. Both OFM1 and  
OFM3 are operating.  
Stage 4 Relays K1 and K5 are energized. Both compressors  
are running fully loaded.  
Size 044 units have one fan that can be controlled by the  
processor. The other 2 are controlled by the compressors. The  
OFM1 is energized by compressor no. 1, and OFM3 is ener-  
gized by compressor no. 2. The OFM2 is cycled by the proces-  
sor based on input from either circuit (thermistors T3 and T4).  
SIZE 104 UNITS — These units have 4 compressors and 1  
unloader on compressor no. 1. See Fig. 43 for compressor and  
condenser fan motor locations. The unit operating sequence is  
as follows:  
Stage 1 Relays K1 and K3 are energized. Compressor no. 1  
starts with unloader energized. Compressor no. 1 runs  
at 2/3 capacity. The crankcase heater for this compres-  
sor has been deenergized, and first stage of condenser  
fans has been energized. Outdoor (condenser) fan  
motor no. 1 (OFM1) and outdoor fan motor no. 3  
(OFM3) have started.  
Head Pressure Control All units have as standard a  
basic head pressure control function which allows the units to  
operate in cooling down to 45 F. If cooling is required at out-  
door ambient temperatures lower than 45 F, refer to accessory  
head pressure control literature for details.  
Head pressure control is handled by the processor. The pro-  
cessor attempts to maintain the head pressure by cycling the  
condenser-fan motors. No condenser fans will be running with-  
out a call for mechanical cooling. Thermistors T3 and T4 pro-  
vide the condensing temperature information to the processor.  
These VAV rooftop units have dual refrigeration circuits, and  
the higher circuit temperature will govern unit operation. If the  
condensing temperature is above 133 F (236 psig), a condenser  
fan stage will be added. If the condensing temperature is 78 F  
(142 psig) or less, the number of condenser fans operating will  
be decreased. After each fan stage, the processor will wait one  
minute for the head pressures to stabilize before changing  
again, unless thermistor T3 or T4 senses a temperature greater  
than 125 F (278 psig), in which case all condenser fans are  
started.  
Stage 2 Relay K1 is energized. Compressor no. 1 is fully  
loaded.  
Stage 3 Relays K1, K3, and K5 are energized. Compressor  
no. 1 runs at 2/3 capacity and compressor no. 2 is run-  
ning at full capacity. The crankcase heater for com-  
pressor no. 2 is deenergized. The first stage of  
condenser fans on circuit 2 has been energized. Fans  
OFM1, OFM2, OFM3, and OFM4 are operating.  
During start-up, if the outdoor ambient is above 70 F (as  
sensed by thermistor T3 or T4), the first-stage, processor-  
controlled fans are turned on to prevent excessive discharge  
pressures.  
Stage 4 Relays K1 and K5 are energized. Both compressors  
no. 1 and no. 2 are running fully loaded.  
044 AND 048 UNITS  
034 AND 038 UNITS  
LEGEND  
OFM  
Outdoor (Condenser) Fan Motor  
Fig. 42 Component Arrangement, 034-048 Units  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
054, 064 UNITS  
054-088 UNITS  
074, 078 UNITS  
088, 104 UNITS  
104 UNITS  
Fig. 43 Component Arrangement, 054-104 Units  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
As the economizer actuator opens past 17% open, auxiliary  
switch DMS1 closes, energizing fan contactor PEC1. Fan mo-  
tor no. 1 starts and runs.  
Capacity of fan no. 1 is controlled by the position of the out-  
let damper. As building pressure increases above set point,  
the DPS will close its contact and drive the power exhaust  
damper motor (PEDM) open until set point is achieved. DPS  
then opens its control contacts and PEDM maintains current  
position.  
When space demand moves PEDM to 90% of full-open po-  
sition, auxiliary switch PEDMS closes, energizing fan contac-  
tor PEC2. Fan motor no. 2 starts and runs. Increased exhaust  
airflow will lower space pressure, causing DPS to drive PEDM  
back towards its closed position, until the set point is achieved.  
If space pressure decreases until PEDM position is reduced  
to 10% of open position, PEDMS will open, deenergizing fan  
contactor PEC2 and shutting off fan no. 2.  
Supply Fan Control with IGV In most VAV units,  
the supply fan static pressure is controlled by inlet guide vanes.  
The inlet guide vanes operate independently from the micro-  
processor. The supply static pressure is controlled by a differ-  
ential pressure switch.  
For example, assume that set point on supply fan differen-  
tial switch is 1.9 in. wg. If pressure in supply duct goes above  
1.9 in. wg, switch will make to the normally open contact and  
energize inlet guide vane motor to drive inlet guide vanes to a  
more closed position, thus reducing airflow and lowering duct  
pressure. Once set point pressure is reached, switch will open  
and deenergize inlet guide vane motor. If pressure in supply  
duct is below 1.9 in. wg, the switch will make to the normally  
closed contact and energize inlet guide vane motor to drive in-  
let guide vane to a more open position; increasing airflow and  
raising duct pressure. Once again, once desired pressure has  
been reached, switch will open and deenergize inlet guide vane  
motor. How far above or below the set point setting the switch  
goes before energizing depends on setting of null span (null  
span is pressure change that can be made without contacts  
opening or closing). If null span is at maximum position, pres-  
sure will vary from 0.17 in. wg to 0.31 in. wg depending on set  
point (if set point is at minimum setting, null span will be  
0.17 in. wg, while if it is at maximum position, the null span  
will be 0.31 in. wg) before switch acts. If null span is adjusted  
to a minimum setting, duct pressure will vary from 0.06 in. wg  
to 0.11 in. wg (again depending on switch set point) before  
switch acts. Setting null span to minimum position will result  
in a smaller pressure fluctuation than if it is set at maximum  
position.  
High Capacity Modulating Power Exhaust  
(48FM and 50 FM,FS Units) The high-capacity  
modulating power exhaust assembly consists of two parallel  
and independent belt-drive large diameter forward curve fans.  
The fans, motors, and drives are located in a cabinet extension  
(not over the return air opening of the unit), in a plenum be-  
neath the outside air intake plenum. The fans discharge hori-  
zontally out the back of the unit through individual barometric  
backdraft dampers with hoods. Operation is interlocked with  
economizer operation. Space pressure is monitored by a  
factory-installed differential pressure transducer. See Fig. 48  
for component locations and sheet metal details.  
The high-capacity modulating power exhaust is also avail-  
able on horizontal 50FS units. Return duct opening is located  
on the left-hand side of the unit; exhaust air exits the unit out  
the back.  
Control of the high-capacity modulating power exhaust sys-  
tem is accomplished via a combination modulated capacity  
fan/staged fan. Modulation is provided by a variable frequency  
drive controlling the direct output to fan no. 1 and controlling  
the ON/OFF status of fan no. 2.  
Fan no. 1 is equipped with a Variable Frequency Drive,  
matched to the motor size. VFD output is determined by the  
VFD’s internal PID logic in response to actual space pressure  
as monitored by the Building Pressure (BP) transducer. Set  
point for BP control is established at the PE VFD. Available set  
point range is –0.50 to +0.50 in. wg. Building Pressure is  
sensed by a pick-up (field-supplied and -installed) located in  
the occupied space and connected to the BP transducer by  
1/4-in. tubing (field-supplied and -installed).  
Supply Fan Control with VFD When equipped  
with the VFD option, the supply fan static pressure is con-  
trolled by modulating the fan wheel speed. The VFD operates  
independently from the microprocessor. A duct pressure trans-  
ducer monitors duct static pressure. The transducer output (4 to  
20 mA) is directed into the VFD. The VFD adjusts supply fan  
motor speed (which changes wheel speed) as measured duct  
pressure varies from set point as established at the VFD. The  
VFD will modulate fan speed until the duct pressure set point is  
achieved.  
NOTE: The VFD will always provide the proper phase  
sequence to the supply fan motor. This motor will operate in  
proper rotation regardless of the phase sequence to the unit. If,  
upon start-up, the outdoor fans operate backwards but the  
indoor fan operates in the correct direction, reverse any two  
leads to the main terminal block. All fans will then operate in  
the correct direction.  
Operation of the modulating power exhaust is a combina-  
tion modulating/staged control, with fan no. 1 providing modu-  
lating control from 0 to 50% of total exhaust capability, and fan  
no. 2 being staged On/Off (for a step of 50% of total exhaust  
capability) according to VFD output level on fan no. 1.  
As the economizer actuator opens past 17% open, auxiliary  
PEC1. Fan motor no. 1 starts and runs.  
Capacity of fan no. 1 is controlled by the output level from  
the BP VFD. As building pressure increases above set point,  
the VFD logic will increase the output level to fan no. 1 until  
set point is reachieved.  
When space demand moves PE VFD output to 100%  
(60 Hz), VFD internal relay closes, energizing fan contactor  
PEC2. Fan motor no. 2 starts and runs. Increased exhaust air-  
flow will lower space pressure, causing PE VFD to reduce its  
output to fan no. 1 until set point is reachieved.  
Modulating Power Exhaust (48FK,JK and  
50FK,JK Units Option or Accessory) The pow-  
er exhaust assembly consists of two parallel and independent  
belt-drive forward curve fans. The fans, motors, and drives are  
located over the return air opening of the unit, in a plenum be-  
neath the outside air intake plenum. The fans discharge air hor-  
izontally out the back of the unit through individual barometric  
backdraft dampers with hoods. (See Fig. 44 and 45.) Operation  
is interlocked with economizer operation. Sheet metal installa-  
tion is shown in Fig. 46 and 47.  
Fan no. 1 is equipped with a variable position discharge  
damper located in the outlet of the fan housing. This damper is  
controlled by an actuator (PEDM), based on signals from the  
building pressure differential pressure switch (DPS). Available  
range on the DPS is -0.50 to +0.50 in. wg, adjustable. Building  
pressure is sensed by a pick-up (field-supplied and -installed)  
located in the occupied space.  
If space pressure decreases until PE VFD output is reduced  
to 25% of maximum output (15 Hz), VFD internal relay will  
open, deenergizing fan contactor PEC2 and shutting off fan  
no. 2.  
Operation of the modulating power exhaust is a combina-  
tion modulating/staged control, with fan no. 1 providing modu-  
lating control from 0 to 50% of total exhaust capability, and fan  
no. 2 being staged On/Off (for a step of 50% of total exhaust  
capability) according to damper position on fan no. 1.  
Unit Staging Compressor loading and unloading se-  
quences are shown in Table 20.  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 44 Modulating Power Exhaust Component Locations; Sizes 034-048  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 46 Modulating Power Exhaust Return End Sheet Metal Skin Detail; Sizes 034-048  
Fig. 47 Modulating Power Exhaust Return End Sheet Metal Skin Detail; Sizes 054-104  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PE VFD  
ACCESS DOOR  
AUXILIARY  
CONTROL BOX  
LARGE ECONOMIZER  
HOOD LOCATION  
EXHAUST  
AIR  
POWER EXHAUST  
ACCESS DOOR  
SMALL ECONOMIZER  
HOOD LOCATION  
Fig. 48 Modulating Power Exhaust Return End Sheet Metal Skin Detail; 48FM and 50FM,FS Units  
Table 20 Compressor Loading and Unloading Sequences  
SIZE 034 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
U1  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
4
6
8
0
17  
33  
50  
67  
OFF  
OFF  
ON  
ON  
10  
12  
83  
100  
OFF  
SIZE 038 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
U1  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
4
6
6
0
14  
28  
42  
72  
OFF  
OFF  
ON  
ON  
8
10  
86  
100  
OFF  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 20 Compressor Loading and Unloading Sequences (cont)  
SIZE 044 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
Lag Circuit  
Active  
Percent  
Cylinders  
Capacity  
Comp 1  
Comp 2  
U1  
OFF  
ON  
OFF  
ON  
0
1
2
3
4
OFF  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
ON  
0
2
4
6
8
0
25  
50  
75  
100  
OFF  
ON  
SIZE 048 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
U1  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
4
6
6
0
19  
38  
58  
62  
OFF  
OFF  
ON  
ON  
8
10  
81  
100  
OFF  
SIZE 054 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
U1  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
OFF  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
4
6
10  
12  
0
20  
40  
60  
80  
ON  
100  
SIZE 064 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
U1  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
4
6
8
0
17  
33  
50  
67  
OFF  
OFF  
ON  
ON  
10  
12  
83  
100  
OFF  
SIZE 074, 078 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
U1  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
4
6
8
0
14  
29  
43  
71  
OFF  
OFF  
ON  
ON  
10  
12  
86  
100  
OFF  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 20 Compressor Loading and Unloading Sequences (cont)  
SIZE 088 UNITS  
COOLING  
STAGE  
Lead Circuit  
Unloader  
U1  
Lag Circuit  
Active  
Cylinders  
Percent  
Capacity  
Unloader  
U2  
Comp 1  
Comp 2  
0
1
2
3
4
5
6
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
ON  
OFF  
ON  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
ON  
0
2
4
6
8
0
16  
33  
50  
66  
OFF  
OFF  
ON  
ON  
10  
12  
83  
100  
OFF  
SIZE 104 UNITS  
Lag Circuit  
COOLING  
STAGE  
Lead Circuit  
Unloader  
U1  
Active  
Cylinders  
Percent  
Capacity  
Comp 1  
Comp 3  
Comp 2  
Comp 4  
0
1
2
3
4
5
6
7
8
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
ON  
ON  
OFF  
OFF  
OFF  
OFF  
OFF  
ON  
ON  
ON  
ON  
0
4
6
10  
12  
14  
16  
18  
20  
0
20  
30  
50  
60  
70  
80  
90  
100  
OFF  
ON  
Blown fuse in the control power feed.  
Open control circuit fuse.  
TROUBLESHOOTING  
By using the display module, actual operating conditions of  
the unit are displayed while it is running. The Quick Test func-  
tion allows proper operation of compressors, compressor un-  
loaders, fans, and other components to be checked while unit is  
stopped. If an operating fault is detected, an alarm is generated  
and an alarm code(s) is displayed. For checking specific items,  
see Table 21.  
Operation of the unit blocked by the demand limit  
function.  
Unit supply-air temperature (T1) thermistor failure.  
Supply-air fan is not operating.  
High duct static pressure.  
Single Circuit Stoppage If a single circuit stops,  
there are several potential causes:  
Checking Display Codes To view the digital dis-  
play codes, press the button located to the right of the LED dis-  
play/set point board in the control box. See Table 22 for Opera-  
tional Status Codes. See Table 23 for Diagnostic Codes.  
Open contacts in the compressor high-pressure switch.  
Low refrigerant pressure.  
Thermistor failure.  
Unit supply-air temperature thermistor (T1) failure.  
Compressor circuit breaker trip.  
Operation of the circuit blocked by the demand limit  
function.  
Complete Unit Stoppage If the unit is off, there are  
several conditions that can cause this situation to occur:  
Remote ON/OFF circuit in Unoccupied mode.  
Unit ON/OFF switch moved to OFF position.  
Programmed schedule at the timeclock.  
General power failure.  
Table 21 Controls Troubleshooting  
SYMPTOM(S)  
PROBABLE CAUSE(S)  
SOLUTION(S)  
Controls do not seem  
to be operating.  
Remote on-off function may be  
keeping controls off.  
Check status.  
1. Circuit breaker open.  
1. Find cause and reset circuit breaker.  
2. Find cause and reset.  
1. Find cause and reset circuit breaker.  
2. Correct operation.  
Evaporator fan does not run.  
Compressor does not run.  
2. Inverter overload (if equipped).  
1. Circuit breaker is open.  
2. There is no demand for cooling.  
3. The control is locking out cooling operation.  
3. Check rotating display for alarm codes. Resolve  
alarm cause and reset control by changing to  
standby and back to run mode.  
4. Demand Limit in effect.  
Circuit breaker is open.  
4. Check Demand Limit Settings.  
Condenser fans do not  
turn on.  
Cooling demand exists and  
economizer modulates, but  
compression is not operating.  
Find cause and reset circuit breaker  
Correct operation.  
Compression cannot be initiated  
until economizer damper is 90% open.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 22 Operation Status Codes  
CODES 51, 52, 55, 56: COMPRESSOR FAILURE — If con-  
trol relay (CR) opens while compressor should be operating,  
compressor will stop and microprocessor will energize alarm  
light and display a code of 51 , 52 , 55 or 56 (depending on  
compressor) when display button is pushed. The compressor  
will be locked off; to reset, the ON-OFF switch must be turned  
to OFF and then to ON position.  
If lead compressor in a refrigerant circuit is shut down, the  
other compressor in that circuit will also be shut down and  
locked off. Only the error code for the lead compressor will be  
displayed.  
CODE  
MEANING  
0 cooling stages active  
1 cooling stage active  
2 cooling stages active  
3 cooling stages active  
4 cooling stages active  
5 cooling stages active  
6 cooling stages active  
7 cooling stages active  
8 cooling stages active  
0
1
2
3
4
5
6
7
8
Code 51 is for compressor 1, and Code 55 is for compressor  
2. Codes 52 and 56 are used for compressors 3 and 4, respec-  
tively, on size 104 units.  
Initialization mode (Allow 2 minutes  
The microprocessor has also been programmed to indicate a  
compressor failure if CR switch is closed when compressor is  
not supposed to be on.  
20  
for initialization. To initiate Quick Test,  
press the Display button while 20 is displayed.)  
21  
22  
26  
30  
88  
Temperature Reset in effect  
Demand Limit in effect  
If a failure occurs, the following are possible causes:  
High-Pressure Switch Open — The high-pressure switch for  
each compressor is wired in series with 24-v power that ener-  
gizes CR. If high-pressure switch opens during operation, CR  
will stop compressor and this will be detected by microproces-  
sor through the feedback contacts.  
Morning Warm-Up in effect  
Internal failure detected  
Self-diagnostic mode in effect  
Restart Procedure Before attempting to restart the  
machine, check the display for alarm codes to determine the  
cause of the shutdown. If the unit, circuit, or compressor stops  
more than once as a result of a safety device, determine and  
correct the cause before attempting to start the unit again.  
After the cause of the shutdown has been corrected, unit  
restart may be automatic or manual depending upon the fault.  
Internal Thermostat — The internal thermostat in each 06D  
compressor is also wired in series with 24-v power that ener-  
gizes CR. If thermostat fails or switch opens during operation  
of compressor, compressor will shut down and failure is detect-  
ed through feedback contacts (size 034 and 038 only).  
CR Failure — If CR fails with large relay either open or  
closed, microprocessor will detect this, lock compressor off,  
and indicate an error.  
Diagnostic Codes Diagnostic codes are warnings of  
abnormal or fault conditions, and may cause either one circuit  
or the whole unit to shut down. They are assigned code num-  
bers as described below.  
Relay Board Failure — If small 24-v relay on the relay board  
fails, microprocessor will detect this through feedback contacts  
and indicate an error.  
Processor Board Failure — If hardware that monitors feed-  
back switch fails and processor board fails to energize the relay  
board relay to ON position, an error may be indicated.  
Table 23 contains a description of each diagnostic code er-  
ror and possible cause. Manual reset is accomplished by mov-  
ing the ON/OFF Switch to the OFF position, then back to ON.  
The control does not detect compressor circuit breaker  
failures.  
Wiring Problem — A wiring error or a loose wire may cause  
the feedback circuit to be broken.  
The 2-digit LED display is used to display the diagnostic  
codes and the alarm light (located next to display) is energized  
whenever a diagnostic code is tripped. When a problem is  
suspected, always check the display first for diagnostic  
information.  
NOTE: Codes 53, 54, 57, 58, 61, 62, 65-69, 73, 74, and 77-80  
are not used on these units.  
IMPORTANT: The microprocessor memory and the dis-  
play will be cleared if the power to the microprocessor is  
shut off. DO NOT attempt to bypass, short, or modify  
the control circuit or electronic boards in any way to cor-  
rect a problem. This could result in a hazardous operat-  
ing condition.  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 23 Diagnostic Codes  
ACTION TAKEN  
BY CONTROL  
RESET  
DISPLAY  
DESCRIPTION OF FAILURE  
Compressor 1 failure  
Compressor 2 failure  
Compressor 3 failure  
Compressor 4 failure  
PROBABLE CAUSE  
METHOD  
51  
55  
52  
56  
Circuit 1 shut off  
Manual  
Manual  
Manual  
Manual  
High-pressure switch or high dis-  
charge gas thermostat switch  
trip, compressor ground current  
>2.5 amp or compressor board  
relay on when it is not supposed  
to be on. Wiring error between  
electronic control and compres-  
sor protection module.  
Circuit 2 shut off  
Compressor 3 shut off  
Compressor 4 shut off  
59  
60  
Loss-of-charge circuit 1  
Loss-of-charge circuit 2  
Circuit 1 shut off  
Circuit 2 shut off  
Manual  
Manual  
This indicates either a low refrig-  
erant charge, or a loss-of-charge  
switch failure.  
63  
64  
Low oil pressure circuit 1  
Low oil pressure circuit 2  
Circuit 1 shut off  
Circuit 2 shut off  
Manual  
Manual  
Not used; Check jumper on pro-  
cessor board.  
70  
Illegal unit configuration  
Unit will not start  
Manual  
Configuration error (see Note 1).  
71  
72  
75  
Supply-air thermistor failure  
Return-air thermistor failure  
Circuit 1 saturated condensing thermistor  
Circuit 2 saturated condensing thermistor  
Reset temperature thermistor failure  
Unit shut off  
Auto.  
Auto.  
Auto.  
Thermistor or resistor failure, wir-  
ing error, or thermistor or resistor  
not connected to the processor  
board.  
Use default value  
Unit shut off  
Unit shut off  
Stop reset  
76  
Auto.  
81  
Auto.  
82  
83  
84  
85  
86  
87  
Supply-air set point potentiometer failure  
Economizer potentiometer failure  
Use default value  
Close economizer  
Stop reset  
Stop demand limit  
Close economizer  
Use default value  
Auto.  
Auto.  
Auto.  
Auto.  
Auto.  
Auto.  
Potentiometer improperly con-  
nected, potentiometer setting out  
of range, potentiometer failure or  
wiring error.  
Reset limit set point potentiometer failure  
Demand limit potentiometer failure  
Minimum economizer potentiometer failure  
Warm-up set point potentiometer failure  
NOTES:  
1. Illegal unit configuration caused by missing programmable header or both unloader DIP switches on.  
2. All auto. reset failures that cause the unit to stop will restart when the error has been corrected.  
3. All manual reset errors must be reset by turning the control switch off and then back on.  
4. Valid resistance range for the thermistors is 363,000 to 585 ohms.  
5. Codes 53, 54, 57, 58, 61, 62, 65-69, 73, 74, and 77-80 are not used on these units.  
CODES 59 AND 60: LOW-PRESSURE SWITCH — These  
codes are used to indicate a low-pressure switch failure.  
been corrected. If a failure occurs, the following are possible  
causes:  
The processor monitors the low-pressure switch. If the  
switch opens, either by low refrigerant charge, circuit failure,  
or wiring error, the circuit is locked off. Code 59 indicates a  
failure of the lead circuit, and as a result, that circuit will be  
shut down. Code 60 indicates a failure of the lag circuit, and as  
a result, that circuit will be shut down. These codes will only be  
displayed when the display button is pressed. To reset the cir-  
cuit, the ON-OFF switch must be turned to OFF, then ON  
position.  
CODES 63 AND 64: OIL PRESSURE SWITCH — These  
codes are used to indicate an oil pressure switch failure. Since  
the units do not have oil pressure switches, these codes are not  
used. The terminals on the processor board must be jumpered  
together or an error will occur. If these errors occur, check  
jumper between J2-1 and J2-2 for a code 63, or between J2-3  
and J2-4 for a code 64 to be sure jumper is properly connected.  
To reset the circuit, the ON-OFF switch must be turned to OFF  
and then to ON position.  
CODE 70: ILLEGAL UNIT CONFIGURATION — If the  
unit configuration header is not installed and properly config-  
ured, and/or if DIP switches are not properly set, unit will not  
start, and an error code of 70 will be indicated on display board  
when display button is pushed. Check the header and DIP  
switch settings.  
CODES 71 TO 76: THERMISTOR/RESISTOR FAILURE —  
If measured temperature of a thermistor is less than –60 F  
(363,000 ohms) or greater than 180 F (585 ohms), the appro-  
priate sensor error code (Table 23) will be displayed when  
the display button is pushed. The unit will be shut down.  
Thermistor failures will automatically reset once the error has  
Thermistor or Resistor Failure — A shorted or open ther-  
mistor or resistor will cause the failure.  
Wiring Failure — If a wiring error exists that causes a shorted  
or open circuit, this will cause a failure.  
Processor Board Failure — If circuitry on processor board  
fails, this could cause an error.  
The codes are designated as follows:  
Code 71 Supply-Air Thermistor Failure  
Code 72 Return-Air Thermistor Failure  
Code 73 Not used  
Code 74 Not used  
Code 75 Circuit 1 Saturated Condensing Thermistor  
Code 76 Circuit 2 Saturated Condensing Thermistor  
CODE 81: RESET THERMISTOR OR POTENTIOMETER  
FAILURE — This is a unique code since the reset temperature  
potentiometer (P7) is in series with the space temperature ther-  
mistor (T10). If either one of these components fail, reset will  
be terminated. This error will automatically reset once the situ-  
ation is corrected. If an error is detected, the most probable  
cause is one of the following:  
Thermistor Failure — A shorted or open thermistor will  
cause the failure.  
Potentiometer Failure — If the potentiometer is outside  
of the valid range (40 to 90 F), a failure will result.  
Wiring Problem — If the circuit is open, a failure will be  
detected.  
Processor Board Failure — If the processor board fails  
(hardware), an alarm will be detected.  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
CODE 82: SUPPLY-AIR TEMPERATURE SET POINT  
POTENTIOMETER FAILURE — If supply-air set point  
potentiometer (P1 — located on display board) fails, control  
will use a default value. A failure will cause an error code of  
82 to be displayed on display board when display button is  
pushed; alarm light will also be energized. A failure is deter-  
mined by establishing a range of –22 F to 70 F as a valid range.  
Anything outside this range will be treated as a failure. If set-  
ting is outside the –22 F to 70 F range, alarm light will be ener-  
gized and an error code of 82 will be displayed when display  
button is pushed; the control will use a set point of 70 F. If set  
point is between –22 F and 45 F, control will use a set point of  
45 F and no error code will be indicated. If potentiometer  
returns to normal, control will automatically reset.  
CODE 85: DEMAND LIMIT POTENTIOMETER (P4)  
FAILURE — Used only if demand limit is being used. If  
demand limit is used, DIP switch 5 must be in the ON position.  
Two types of demand limit are available: a field-supplied  
and installed single-step control consisting of a 10 Kohm,  
3-wire linear potentiometer and an accessory 2-step control.  
The single-step control has a single potentiometer while 2-step  
control has 2 potentiometers (mounted on the demand limit  
board, see Fig. 28).  
For both types of demand limit, the control uses only 80%  
of the total potentiometer resistance. If resistance of potentiom-  
eter is less than 10% or greater than 90%, alarm light will be  
energized, a diagnostic code of 85 will be displayed when the  
display button is pushed, and demand limit will be terminated.  
If a failure occurs, it is probably due to one of the following:  
Potentiometer Failure — If a potentiometer is shorted or open,  
a failure will occur.  
Incorrect Potentiometer Setting — A potentiometer turned  
fully clockwise or counterclockwise will put potentiometer out  
of range resulting in an error.  
Faulty Wiring — If wiring between the potentiometer and the  
processor board is incorrect, an error will occur.  
DIP Switch 5 — If DIP switch 5 is in the ON position and po-  
tentiometer is not installed, an error will occur.  
CODE 86: MINIMUM POSITION ECONOMIZER POTEN-  
TIOMETER FAILURE — If potentiometer P5 (on accessory  
board) setting is less than 0% or greater than 100%, alarm light  
will be energized, a code of 86 will be displayed when display  
button is pushed and economizer outdoor air dampers will  
move to the fully closed position.  
The potentiometer full-scale resistance is 10 Kohm, but  
when installed in parallel with the other 2 potentiometers on  
the accessory board, measured resistance will be 3.3 Kohm.  
This failure will automatically reset when potentiometer re-  
turns to normal.  
If a failure occurs, one of the following is the probable  
cause:  
DIP Switch 3 — If this switch is in the ON position and the  
accessory board is not installed (accessory board is standard on  
these units, so it should always be on the unit).  
Incorrect Potentiometer Setting — If potentiometer is turned  
fully clockwise or counterclockwise, potentiometer will be out  
of the allowable range, and an error will result.  
Faulty Wiring — If wiring between the potentiometer and the  
processor board is incorrect, an error will occur.  
Potentiometer Failure — If potentiometer is shorted or open,  
potentiometer will be out of range and an error will result.  
NOTE: The full range of the potentiometer is not used for the  
cooling set point range of 45 F to 70 F. The full scale resistance  
of the potentiometer is 10 Kohms.  
If a failure occurs, one of the following is a probable cause:  
Incorrect Potentiometer Setting — A potentiometer turned  
fully clockwise or counterclockwise is outside the valid range  
and will cause a failure.  
Faulty Wiring — If wiring is incorrect between potentiometer  
and processor board or display board, a failure will result.  
Potentiometer Failure — If potentiometer is shorted or open, a  
failure will result.  
CODE 83: ECONOMIZER FEEDBACK POTENTIOME-  
TER FAILURE — If potentiometer on economizer motor (P2)  
fails, control will use a default value of 0% and economizer  
outdoor-air dampers will close. The failure will energize alarm  
light and cause an error code of 83 to be displayed when dis-  
play button is pushed. This potentiometer is a 5 to 15 Kohm  
potentiometer. If potentiometer returns to normal, control will  
automatically reset. If a failure occurs, one of the following is  
the probable cause.  
Faulty Wiring — If the wiring between processor board and  
potentiometer is wrong, this will cause a failure.  
Potentiometer Failure — If potentiometer is shorted or open,  
this will cause a failure.  
Economizer Damper Stuck — The control has been pro-  
grammed to indicate an error if potentiometer travel is less than  
10% of the full range. This would happen if dampers or damp-  
er linkage were hung up and could not move properly.  
CODE 84: RESET LIMIT POTENTIOMETER FAILURE —  
This code is applicable only if reset is being used. If reset is  
being used, DIP switch 2 must be in the ON position. This  
potentiometer (P3) is located on the accessory board. If poten-  
tiometer setting is less than 0° F or greater than 80 F, alarm  
light will be energized, a diagnostic code of 84 will be dis-  
played if display button is pushed, and reset will be terminated.  
The full-scale resistance of potentiometer is 10 Kohms, but  
when installed on the accessory board in parallel with the other  
2 potentiometers, measured resistance will be 3.3 Kohms. This  
failure will automatically reset once potentiometer returns to  
normal. If a failure occurs, one of the following is the probable  
cause:  
DIP Switch Problem — DIP switch 2 is in the ON position  
and the accessory board is not installed (accessory board is  
standard on these units so it should always be on the unit).  
Incorrect Potentiometer Setting — A potentiometer turned  
fully clockwise or counterclockwise is outside the valid range  
and will result in a failure.  
CODE 87: WARM-UP TEMPERATURE SET POINT FAIL-  
URE — Applicable only if morning warm-up is used. Whether  
or not unit is equipped with electric resistance heaters, use of  
the morning warm-up function is recommended if the unit is  
shut down at night or over weekends. In this application, cool-  
ing will remain off and the outdoor-air damper will stay closed  
until heat load from the occupied space elevates return-air tem-  
perature to the warm-up set point. If warm-up function is used,  
DIP switch 4 must be in the ON position. The potentiometer  
(P6) is located on the accessory board. If potentiometer is set at  
less than 0° F or more than 95 F, alarm light will be energized,  
a diagnostic code of 87 will appear on the display when dis-  
play button is pushed, and control will use a default value of  
40 F. If setting is between 0° F and 40 F, control will use a  
value of 40 F but no diagnostic code will be displayed; if set-  
ting is between 80 F and 95 F, control will use a value of 80 F  
but no diagnostic code will be displayed.  
Faulty Wiring — If the wiring between the potentiometer and  
the processor board is incorrect, a failure will result.  
Potentiometer Failure — If potentiometer is shorted or open, a  
failure will occur.  
The potentiometer full-scale resistance is 10 Kohm, but  
when wired in parallel with other potentiometers on the acces-  
sory board, measured resistance is 3.3 Kohm.  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The failure will automatically reset once potentiometer re-  
turns to normal. If a failure occurs, one of the following is the  
probable cause:  
DIP Switch 4 — If this switch is in the ON position and the  
accessory board is not installed (accessory board is standard on  
these units, so it should always be on the unit).  
Incorrect Potentiometer Setting — If potentiometer is turned  
fully clockwise or counterclockwise, potentiometer will be out  
of the allowable range, resulting in an error.  
Faulty Wiring — If the wiring between the potentiometer and  
the processor board is incorrect, an error will occur.  
PROCESSOR BOARD CHECKOUT — Refer to Fig. 49 and  
50 for location of terminal pins and test points.  
Step 1 — Check Transformer Input to the Board — Con-  
nector J4 is used to connect the control transformer to the pro-  
cessor board.  
1. Set the volt-ohmmeter to ac voltage with a range setting  
of approximately 30 v.  
2. Turn control switch to ON position.  
3. Check voltage at following terminals on pin terminal con-  
nector J4:  
TERMINALS  
VOLTAGE (AC)  
Potentiometer Failure — If potentiometer is shorted or open,  
potentiometer will be out of range, resulting in an error.  
1 to 2  
4 to 6  
5 to 6  
5 to 4  
15.3 to 20.9  
16.2 to 22.0  
8.1 to 11.0  
8.1 to 11.0  
Thermistor Troubleshooting The VAV control  
system uses thermistors to measure temperatures of the enter-  
ing and supply air, as well as the saturated condensing tempera-  
tures of the refrigerant circuits. The resistance versus tempera-  
ture and electrical characteristics for all thermistors in the sys-  
tem are identical. To obtain an accurate reading, a high-  
impedance meter (such as a digital meter) must be used.  
Thermistors in the VAV control system have a 5 vdc signal  
applied across them any time the unit control circuit is ener-  
gized. The voltage drop across the thermistor is directly pro-  
portional to the temperature and resistance of the thermistor.  
To determine temperatures at the various thermistor loca-  
tions, disconnect the thermistor from the processor board and  
measure the resistance across the appropriate thermistor using  
a high-quality digital ohmmeter. Use the resistance reading to  
determine the thermistor temperature.  
The microprocessor has been programmed to check the op-  
eration of the thermistors. If the measured temperature is out-  
side of the range of –24 to 225 F or 98,010 to 282 ohms, then it  
will be treated as a sensor failure and a diagnostic code will be  
displayed. See Table 19 for sensor temperatures versus resis-  
tance drop. It is also possible to check the operation of the ther-  
mistors using the quick test routine.  
4. If voltage is not within range, check primary side.  
115-v transformer — 104 to 127 vac  
230-v transformer — 207 to 254 vac  
5. If primary voltage is not correct, check system fuse, trans-  
former, ON-OFF switch, and wiring. If these are okay,  
contact power company.  
6. If primary voltage is correct, but secondary voltage (24 v  
± 10%) is incorrect, replace transformer.  
7. Turn control switch to OFF position.  
Step 2 — Check Processor Board Power Supply  
1. Set meter to approximately 20 vdc.  
2. Turn power to OFF position.  
3. Connect negative lead to TP18.  
4. Turn power switch to ON position and press display but-  
ton to enter Quick Test mode.  
5. Check voltage between TP18 and each of the following  
test pins:  
TEST PIN  
VOLTAGE (DC)  
TP3  
TP4  
TP6  
TP10  
TP14  
TP15  
TP7  
+10  
+12  
+5  
If a thermistor has failed or the wire is damaged, replace the  
complete assembly. Do not attempt to splice the wires or repair  
the assembly.  
+5  
+12  
+12  
5*  
Electronic Controls Checkout The following will  
help determine whether a processor board, a relay board, dis-  
play set point board, accessory board, or 2-step demand limit  
module is faulty.  
*If not using a digital meter, leads must be reversed.  
6. If voltage is incorrect, replace processor board.  
7. Turn power to ON position.  
Step 3 — Check Voltage Tolerance Circuitry  
1. Turn power to OFF position.  
2. Negative test probe on TP18 and system in Quick Test  
mode.  
3. Check voltage TP18 to TP9.  
4. If voltage is greater than 11 vdc, recheck transformer in-  
put voltage.  
5. If transformer is okay, replace processor board.  
6. Turn power to ON position.  
Before checking out any board, do the following:  
1. At initial start-up, enter the Quick Test mode. This test  
will determine if all components are connected and oper-  
ating properly.  
2. If system has been operating and a malfunction occurs,  
check display for diagnostic codes. Use diagnostic chart  
located on inner panel of access door to control box sec-  
tion of unit; this chart will help determine probable cause  
of failure.  
These 2 steps will help determine if a component other than  
a board is at fault or if the problem is external to control circuit.  
Step 4 — Check Processor Reset Line  
1. Turn power to OFF position.  
2. Negative probe on TP18.  
A volt-ohmmeter will be needed to troubleshoot boards. A  
digital meter is preferred but a Simpson 260 or equivalent will  
work.  
3. Check voltage TP18 to TP11.  
4. If voltage is greater than +3 vdc, reset power and recheck.  
5. If voltage is still incorrect, replace processor board.  
6. Turn power to ON position.  
To prevent damage to solid-state electronic components on  
boards, meter probes should only be placed on terminals  
and test points listed in following sections. Do not short the  
electrical components, and use extreme care while working  
on the processor board.  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Step 5 — Check Relay Board Outputs from the Processor  
Board — This step involves checking the output signals from  
relays K1-K3 on the relay board.  
Table 23 on pin terminal connector J9. See Fig. 51 for J9  
details.  
Step 6 — Display Board Connection Checkout  
1. Turn power to OFF position.  
1. Turn power to OFF position.  
2. Connect negative test probe to TP19 (meter still set to  
dc).  
3. Turn switch to ON position and enter Quick Test mode.  
4. Connect positive test probe to terminal 14 on pin terminal  
connector J9, and check voltage from TP19 to terminal  
14 on pin terminal connector J9.  
5. If not 112 ± 1 vdc, replace processor board.  
6. Turn switch to OFF position.  
7. Remove negative test probe from TP19. Connect positive  
test probe to TP15.  
8. Turn switch to ON position and go into Quick Test mode.  
9. Place negative lead on terminals shown in Table 24, and  
check voltage between TP15 and terminals shown in  
2. Disconnect the ribbon cable.  
3. Connect negative lead of meter to TP18.  
4. Turn power to ON position and go into Quick Test mode.  
5. Place the other lead on terminals shown in table below,  
and check voltage at pin terminals on pin terminal con-  
nector J10 (see Fig. 52 for pin terminal connector J10  
details):  
PIN TERMINAL  
VOLTAGE (DC)  
17  
18  
20*  
22*  
24  
5
5
2.5  
2.5  
5
*Voltage reading is dependent on the meters impedance. Readings  
may vary with different meters.  
Fig. 51 Relay Board Pin Terminal Connector (J9)  
LEGEND  
J
Pin Terminal Strip  
TP Test Pin  
Fig. 49 Processor Board Test Points  
Table 24 Voltage Reading  
J6  
J5  
J9 PIN NUMBERS  
QUICK TEST  
STEP NO.  
R9  
C9  
R10  
C10  
R11  
R12  
C12  
R13  
C13  
1
2
3
4
5
6
7
8
9 10 11 12 13  
1.-2.3.  
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
12  
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
12  
12  
12  
12  
12  
2.4.  
2.5.  
2.6.  
2.7.  
2.8.  
2.9.  
3.0.  
3.1.  
3.2.  
3.3.  
C11  
0
0
0
12 0  
0
0
0
0
0
12 0 12  
0
0
0
0
0
12 0  
12 0  
12 0  
12 0  
12 0  
12 0  
12 0  
0
0
0
0
0
0
0
12  
0
0
0
0
0
12 12  
12  
0
0
0
0
0
0
0
0
0
0
12  
12  
12  
12  
12  
CR9  
CR10  
CR11  
CR12  
CR13  
12  
0
0
0
0
0
12 0  
0
0
0
0
0
0
0
0
0 12  
0
0
0
0
0
0
12  
0
0
NOTES:  
1. Pins shown in boldface type will only be energized for 10 seconds.  
All other pins will be energized continuously while at the proper  
quick test step. The control will only stay in the Quick Test routine  
for 10 minutes unless the display button is pressed.  
2. Acceptable range for the voltage reading:  
0 v 0 to 4 v  
C1  
C2  
C3  
C4  
C5  
C6  
C7  
C8  
CR1  
CR2  
CR3  
CR4  
CR5  
C19  
CR6  
CR7  
E3  
CR8  
12 v 11 to 13 v  
3. If any of these voltages are not measured, replace the processor  
board.  
K1  
K2  
K3  
LEGEND  
CR Control Relay  
J
K
Pin Terminal Strip  
Relay  
Fig. 50 Relay Board Test Points  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6. If voltage is not correct, replace processor board.  
Step 7 — Potentiometer Connection Checkout  
1. Turn power to OFF position.  
2. Remove plug connection from pin terminal strip J3.  
3. Connect negative meter lead to terminal 2 of J3.  
4. Turn switch to ON position and go into Quick Test mode.  
Table 25 Pin Terminal Connector J1 Voltages  
PIN  
TERMINAL  
VOLTAGE  
(vdc 0.25 v)  
1
2
0
5
0
5
0
5
0
5
0
5
0
5
0
5
0
5
0
5
6
7
8
9
5. Place the other lead on terminals shown in table below,  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
and check voltage at pin terminals on terminal connector  
J3:  
PIN TERMINAL  
VOLTAGE (DC)  
1*  
3
2.5  
5
6
5
8*  
2.5  
2.5  
5
2.5  
2.5  
10*  
12  
13*  
14*  
*Voltage reading is dependent on the meters impedance. Readings  
Step 9 — Thermistor Input Connector Checkout  
1. Turn power to OFF position.  
2. Disconnect all plugs for pin terminal connector J2 and  
mark them for later replacement.  
3. Connect a negative test lead to test pin TP18.  
4. Turn power to ON position, and enter the Quick Test  
routine.  
5. Place the other lead on terminals shown in Table 26, and  
check the voltages.  
6. If voltages are incorrect (per Table 26), replace processor  
board.  
7. Turn power to OFF position, and replace the plugs re-  
moved in Step 2.  
8. Turn power to ON position.  
may vary with different meters.  
6. If voltage is not correct, replace processor board.  
Step 8 — Thermistor Input Connector Checkout  
1. Turn power to OFF position.  
2. Remove the thermistor connections from pin terminal  
connector J1, and mark them for later replacement.  
3. Connect the negative test lead to test pin TP18.  
4. Turn power to ON position, and enter the Quick Test  
routine.  
5. Place the other lead on terminals shown in Table 25, and  
check the voltages.  
6. If voltages are incorrect (per Table 25), replace processor  
board.  
7. Turn power to OFF position, and replace the thermistor  
connections removed in Step 2.  
8. Turn power to ON position.  
Table 26 Pin Terminal Connector J2 Voltages  
PIN  
TERMINAL  
VOLTAGE  
(vdc 0.25 v)  
1
0
5
0
5
0
5
0
5
0
5
5
5
5
5
5
5
5
5
5
2
3
4
7
8
9
10  
13  
14  
15  
17  
18  
19  
20  
21  
22  
23  
24  
If Steps 1 through 9 have been competed and the unit still  
will not function properly, replace the processor board.  
Fig. 52 Display Board Pin Terminal Connector  
(J10)  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
RELAY BOARD TROUBLESHOOTING — The relay board  
contains 13 electromechanical relays. The small relays are  
24 vac, and the large relays are 115 vac. These relays are con-  
trolled by the processor through the ribbon cable attached to  
the relay board.  
The following procedure can be used to check out the oper-  
ation of the relays. To do this, turn the control ON/OFF switch  
to the OFF position, and remove the wiring connectors con-  
nected to pin terminal connectors J5 and J6. Set the meter for  
resistance. If the contacts do not close at the required quick test  
step, check the relay outputs from the processor board.  
Table 28 Terminal Strip J5 Connector  
Resistance Reading  
J5 PIN NUMBERS  
QUICK TEST  
STEP NO.  
1
2
3
4
5
1. to 2.5.  
2.6  
2.7.  
2.8.  
2.9. to 3.3.  
0
0
0
0
0
0
0
0
0
0
0
0
LEGEND  
Infinity  
Relay Board Checkout (Fig. 5)  
Step 1 — Low-voltage relay resistance check.  
1. Turn switch to OFF position.  
Step 2 — Check the Display LEDs  
1. Enter Quick Test mode.  
2. Remove plug connection from terminal strip J6.  
2. If 88 is not displayed, replace display board.  
3. Set meter to measure resistance. Connect negative test  
lead to both terminals 11 and 12 of J6.  
4. Turn switch to ON position and go into Quick Test mode.  
Step 3 — Check Set Point Potentiometer — Advance the  
display to quick test step 1.9. to determine if this potentiometer  
is set and connected properly.  
Step 4 — Check Display Switch — Press switch. If switch  
does not click, it is faulty and the display will be energized con-  
tinuously. The switch is an integral part of display board and  
cannot be replaced separately.  
ACCESSORY BOARD CHECKOUT — The accessory board  
can be completely checked using quick test steps 2.0., 2.2., and  
2.3. It can also be checked out as follows:  
1. Remove the accessory board connector from the proces-  
sor board and connect an ohmmeter to terminals 3 and 4  
on the connector. Numbers are marked on the connector.  
See Fig. 15.  
2. Set the meter to 10,000 ohms. The resistance value ob-  
tained should be 3,333 ohms. Adjust the potentiometers  
and the resistance value should not change.  
5. Place other meter lead on terminals shown in Table 27  
and check resistances at each quick test step.  
6. If these resistances are not correct and relay board outputs  
from processor board have been checked out, replace re-  
lay board.  
Step 2 — High-voltage relay resistance check.  
1. Turn switch to OFF position.  
2. Remove plug connection from terminal connector J5.  
3. Connect negative test lead to terminal 8.  
4. Check the resistance between terminals 8 and 5 before  
entering Quick Test mode. The resistance should be  
infinity.  
5. Turn switch to ON position and go into Quick Test mode.  
3. Connect the ohmmeter to terminals 3 and 6. As the reset  
limit potentiometer is turned clockwise, resistance should  
increase from 0 to approximately 3,400 ohms.  
4. Connect the ohmmeter to terminals 3 and 5. As the econ-  
omizer minimum position potentiometer is turned clock-  
wise, resistance should increase from 0 to approximately  
3,400 ohms.  
5. Connect the ohmmeter to terminals 3 and 2. As the  
warm-up set point potentiometer is turned clockwise,  
resistance should increase from 0 to approximately  
3,400 ohms.  
If any of the Steps 1 through 5 result in any other ohm read-  
ing, replace the board; it cannot be serviced.  
TWO-STEP DEMAND LIMIT CONTROL MODULE  
(DLCM) TROUBLESHOOTING — If a problem is suspected  
in the DLCM board, use the following test procedure:  
The board can only be checked when it is connected to the  
processor and the processor is energized so that the DLCM is  
supplied with 5 vdc power. The terminals referenced are shown  
in Fig. 16. Potentiometers P1 and P2 refer to the DLCM poten-  
tiometers.  
6. Place other meter lead on terminals shown in Table 28  
and check resistance at each quick test step.  
7. If these resistances are not correct and relay board outputs  
from processor board have been checked per Processor  
Board Checkout section on page 48, replace relay board.  
DISPLAY BOARD CHECKOUT  
Step 1 — Check the Output Voltage from Processor Board  
to the Relay Board — Refer to Step 6 — Display Board Con-  
nection Checkout section on page 49.  
Table 27 Terminal Strip J6 Connection  
Resistance Reading  
J6 PIN NUMBERS  
QUICK TEST  
STEP NO.  
1. to 2.3.  
2.4.  
1
2
3
4
5
6
7
8
0
0
2.5.  
2.6.  
2.7.  
2.8.  
2.9.  
3.0.  
3.1.  
3.2.  
0
0
IMPORTANT: Be careful to avoid damaging the con-  
nector or the processor board when taking the voltage  
readings.  
0
0
0
3.3.  
LEGEND  
Infinity  
NOTE: Pins shown in boldface type will be energized for only  
10 seconds. All other pins will be energized continuously while at the  
proper quick test step. The control will remain in the Quick Test  
mode for only 10 minutes unless the display button is pressed.  
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Test under the following conditions:  
No power to IN1 or IN2  
Terminal 1 to 2 should read 4.5 vdc ±0.1 v  
Terminal 2 to 3 should read 5.0 vdc ±0.1 v  
Power to IN2 or to both IN1 and IN2, and P2 set at 24%  
Terminal 1 to 2 should read 1.5 vdc ± 0.1 v  
LIMIT SWITCHES  
CAPACITOR  
NOTE: Voltage should vary between 0.5 vdc and 2.5 vdc as  
the setting of P2 is varied between 0% and 49%.  
Terminal 2 to 3 should read 5.0 vdc ± 0.1 v  
Power to IN1 only and P1 set at 50%  
Terminal 1 to 2 should read 2.5 vdc ± 0.1 v  
Terminal 2 to 3 should read 5.0 vdc ± 0.1 v  
NOTE: Voltage should vary between 0.5 vdc and 2.5 vdc as  
the setting of P2 is varied between 50% and 100%.  
NOTE: If the voltages listed in these 3 tests are not ob-  
tained during testing, the DLCM board must be replaced.  
3
2
CW  
ECONOMIZER  
MOTOR  
WINDING  
(OPEN)  
CCW  
WINDING  
(CLOSE)  
T1  
T2  
Enthalpy Sensor Checkout To test operation of  
1
BRAKE  
WINDING  
1
enthalpy sensor, see Table 29.  
Table 29 Enthalpy Sensor Checkout  
1
2
3
CW  
EXPECTED RESULT  
AND RESPONSE  
TEST  
Outdoor-air sensor:  
Milliammeter reading should be  
between 3 and 24 mA if sensor  
is operating correctly. If reading  
FEEDBACK  
POTENTIOMETER  
Enthalpy sensor + terminal  
should be connected to +  
terminal on motor. Connect the is 0 mA, the sensor is either  
positive terminal of a DC  
wired backwards or is defective.  
milliammeter to the S terminal  
of the sensor and the negative  
terminal of the meter to SO  
terminal of the enthalpy board.  
BLU  
RED  
YEL  
Indoor-air sensor:  
Milliammeter reading should be  
between 3 and 24 mA if sensor  
is operating correctly. If reading  
Enthalpy sensor + terminal  
should be connected to +  
AUX. SWITCH  
terminal on motor. Connect the is 0 mA, the sensor is either  
LEGEND  
CCW Counterclockwise  
CW Clockwise  
positive terminal of a DC  
wired backwards or is defective.  
milliammeter to the S terminal  
of the sensor and the negative  
terminal of the meter to SR  
terminal of the enthalpy board.  
Fig. 53 Damper Motor Connection Diagram (VAV)  
Economizer Motor All control of the motor (i.e.,  
enthalpy changeover, minimum position control and mixed air  
control) is accomplished from the main unit microprocessor  
through a relay board. Service and installation instructions  
for the unit should be consulted to verify proper operation of  
these controls. The economizer motor may be checked out sep-  
arately. See Fig. 52 for VAV economizer motor connection  
information.  
Supply Fan Variable Frequency Drive  
Factory-installed optional VFD is located near the supply  
fan and motor. During any service work or programming at  
the VFD, operation of the fan and motor is not desirable.  
Either disable the supply fan or install an accessory VFD  
remote display.  
Motor Test  
Apply 24 volt AC power to terminals T1 and T2 of motor.  
Connections to motor terminals 2 and 3 must be disconnected  
NOTE: The VFDs (part no. TOSVERT130-E3) are specially  
modified for use on Carrier equipment. Some specifications  
and control configuration defaults for Carrier applications will  
differ from the VFD manufacturer manual included in the  
packet. See Table 30 for listing of Carrier-specific default  
values.  
A Motor Test  
Jumper 1 to  
replace motor.  
A Expected Result and Response  
Motor drives open; if not, 2 at motor  
B Motor Test  
Jumper 1 to  
3 at motor  
B Expected Result and Response  
Motor drives closed; if not,  
replace motor.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STANDARD TRANSDUCER CONTROL — The VFD mon-  
itors and controls duct pressure (DP) via a differential pressure  
transducer. The pressure transducer is located in the auxiliary  
control box (034-048 units) or in the supply fan compartment  
(see Fig. 34). The pressure transducer’s low pressure reference  
port is connected to the outside of the unit cabinet by a factory-  
installed tubing section. The pressure transducer’s high pres-  
sure reference point must be field-connected to the duct pres-  
sure pick-up (field-supplied and installed in the supply duct).  
P24  
LOW LOW  
RR  
SI S2  
S4  
RCH  
RES  
F
R
S3  
P24  
ST  
RX  
FLB  
FLA  
AM CC CC  
PP  
IV FP  
FM  
FLC  
4-20mA  
The DP transducer monitors the static pressure in the supply  
duct and provides a 4 to 20 mA signal directly to the VFD. (Re-  
fer to Table 13 for transducer output signal [mA] for actual duct  
static pressure.) The internal logic of the VFD compares this  
signal representing actual duct pressure to the user-configured  
DP set point. The VFD automatically adjusts its output to the  
supply fan motor to maintain the desired DP set point. When  
operating with the factory-standard DP transducer, the internal  
PID logic of the VFD is enabled. EXTERNAL SIGNAL  
CONTROL — If the VFD is to be controlled by an external  
control system other than the factory supplied pressure trans-  
ducer, the internal PID logic function of the VFD must be dis-  
abled. To disable the PID control:  
Fig. 54 Supply Fan Variable Frequency Drive  
Terminal Block (Size 034-048 Units)  
RR  
SI S2  
S4  
RCH  
RES  
F
R
S3  
P24  
LOW LOW  
P24  
ST  
RX  
FLB  
FLA  
AM CC CC  
PP  
IV FP  
FM  
FLC  
1. Disconnect and lock out all power to the Carrier rooftop  
unit.  
2. Remove the VFD access cover.  
4-20mA  
Fig. 55 Supply Fan Variable Frequency Drive  
Terminal Block (Size 054-104 Units)  
Ensure the “CHARGE” lamp on the VFD is unlit. This  
may up to 4 minutes. The “CHARGE” lamp indicates that  
the main capacitors in the VFD are charged. Internal com-  
ponents of the VFD should not be touched until the  
“CHARGE” lamp is completely out. Electrical shock can  
cause injury or death.  
VFD OPERATION — When troubleshooting the VFD, check  
first that all required conditions for VFD operation are  
satisfied.  
For the VFD to run, the following conditions must be met at  
the VFD:  
1. Drive enable jumper is installed from terminals CC-ST  
(factory supplied) (see Fig. 54 and 55).  
2. Proper rotation jumper is installed at terminals R-CC (re-  
verse rotation, factory supplied) or terminals F-CC (for-  
ward rotation, factory supplied).  
3. Install a jumper across S2-CC (see Fig. 54 and 55 for  
VFD terminal board connections).  
4. Remove factory-supplied cable attached to IV and CC.  
5. Remove other end of the same cable from the pressure  
sensor.  
6. Connect field supplied speed reference (4 to 20 mA)  
across terminals IV-CC.  
UNIT SIZES  
ROTATION  
JUMPER  
034-048  
054-074  
078-104  
Reverse  
Forward  
Forward  
R-CC  
F-CC  
F-CC  
7. Disable the supply fan motor operation.  
8. Reconnect power to the unit and VFD.  
9. Reprogram the VFD to accept an external reference (in  
the Utility parameters group [Gr.Ut], set parameter item  
Fnod [no.312] = 4).  
3. Emergency stop jumper is installed from terminals  
S4-CC (factory supplied).  
4. A 4 to 20 mA signal is applied across terminals IV-CC  
(from pressure transducer, factory supplied).  
10. Enable supply fan motor and return power to the unit.  
SUPPLY FAN MOTOR OVERLOAD PROTECTION — The  
VFD provides operating overload protection for the supply fan  
motor. The factory has programmed the VFD overload func-  
tion to match the factory-installed motor (motor size and effi-  
ciency). If the supply fan motor is changed from the original  
factory selection, the overload value may need to be changed  
by the service person. Contact your local Carrier representative  
for assistance in determining the proper overload setting.  
5. DIP switch SW1 (located on the VFD’s printed circuit  
control panel) must be set to ‘‘I’’ (indicating usage of a 4  
to 20 mA input signal at terminals ‘‘IV’’).  
6. Speed Control (located on the VFD’s keypad/display) set  
for ‘‘Remote’’ (press the ‘‘Speed Ctrl’’ button until LED  
‘‘Remote’’ is illuminated).  
7. Programmed according to Carrier defaults.  
8. Duct Pressure set point established by user, or use factory  
default (30 Hz indicating 2.50-in. wg) (see Table 13).  
NOTE: Variable frequency drive size is matched to factory-  
installed motor size. Do not increase motor size without also  
changing to equivalent VFD size.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 30 Carrier Default Program Parameter Values (Supply Fan VFD)  
PARAMETER GROUP  
PARAMETER  
ACC1  
DEC1  
UL  
DEFAULT VALUE  
60.0 Sec  
60.0 Sec  
60.0 Hz  
LL  
10.0 Hz*  
Luln  
P3  
1
20%  
F-P3  
P4  
0.0 Hz  
100%  
SEtP  
(Setup)  
F-P4  
tHr1  
StC1  
StL1  
OLN  
tYP  
60 Hz  
See Table 32  
0
110%  
1
5*  
FH  
Pt  
60 Hz  
2
Gr.F  
(Fundamental)  
FbP1  
Fbln  
GP  
1*  
2
.30  
Gl  
2 sec  
GA  
0
80  
10  
1
Gr.Fb  
(Feedback)  
GFS  
P1LL  
PuL  
PuUl  
PuLL  
Fsor  
Sr.n  
SrN1  
10  
10  
60 Hz  
Gr.SF  
(Frequency Settings)  
1* (054-104 only)  
0* (054-104 only)  
Gr.Pn  
(Panel Control)  
Fr  
0*  
1t  
1
1t0  
0
1t1  
1t2  
56  
13  
Gr.St  
(Terminal Selection)  
1t3  
3
1t4  
10  
UuC  
UuCt  
ArSt  
Cnod  
bLSF  
Fnod  
bLPn  
1*  
2
3
1*  
Gr.Pr  
(Protection)  
1* (054-104 only)  
Gr.Ut  
(Utility)  
2*  
1*  
*These settings differ from the Toshiba defaults and are required for Carrier applications.  
NOTE: To restore original factory settings, change tYP to 6 in Setup mode (SEtP). This restores the VFD original factory settings.  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VFD OPERATIONAL STATUS — The VFDs contain ex-  
tensive self-diagnostic functions which are accessed through  
the VFD display panel (located on the front of the VFD or at a  
remote location when the accessory remote display package  
has been installed).  
logic of the power exhaust VFD compares this signal repre-  
senting actual duct pressure to the user-configured BP set  
point. The power exhaust VFD automatically adjusts its output  
to the power exhaust fan motor to maintain the desired BP set  
point. When operating with the factory-standard BP transducer,  
the internal PID logic of the power exhaust VFD is enabled.  
EXTERNAL SIGNAL CONTROL — If the power exhaust  
VFD is to be controlled by an external control system other  
than the factory-supplied pressure transducer, the internal PID  
logic function of the power exhaust VFD must be disabled. To  
disable the PID control:  
1. Disconnect and lock out all power to the Carrier rooftop  
unit.  
If using the VFD display panel, disconnect all power to  
the unit and the VFD before entering unit, or use the  
accessory remote display module. Disable supply fan and  
motor operation before accessing VFD-mounted display  
module.  
When power is first supplied to the VFD, the display auto-  
matically starts with the frequency monitor function of its stan-  
dard monitor mode. In the frequency monitor function, the out-  
put frequency is displayed. Push the S/P/M (Setup/ Program/  
Monitor) key to switch to the Mode Selection menu. Push the  
S/P/M key again to toggle the display back to the standard  
monitor mode.  
From the Mode Selection menu, the service person can  
view all of the monitored status variables, including up to four  
user-selected variables and any trip history in the memory.  
2. Remove the VFD access cover.  
Ensure the “CHARGE” lamp on the VFD is unlit. This  
may up to 4 minutes. The “CHARGE” lamp indicates that  
the main capacitors in the VFD are charged. Internal com-  
ponents of the VFD should not be touched until the  
“CHARGE” lamp is completely out. Electrical shock can  
cause injury or death.  
Refer to the separate VFD Operation Manual for detailed  
instructions on accessing diagnostic information, initiating  
troubleshooting, and clearing any trip history.  
RESTORING FACTORY VFD DEFAULTS — The original  
factory configuration values are saved in the memory of the  
VFD and can be restored by the service person if required.  
There are two types of saved file data: Carrier-factory settings  
(factory programmed settings made to the VFD which apply  
specifically to the unit it is installed on) and standard defaults  
for general Carrier unit use.  
The Carrier-factory settings are maintained as user settings.  
These can be restored by entering the Setup mode (in the  
S/P/M menu) and setting parameter tYP = 6 on the keypad/  
display. This will recall the specific factory defaults for this  
unit.  
3. Install a jumper across S2-CC (see Fig. 56 for power ex-  
haust VFD terminal board connections).  
4. Remove factory-supplied cable attached to IV and CC.  
5. Remove other end of the same cable from the pressure  
sensor.  
6. Connect field-supplied speed reference (4 to 20 mA)  
across terminals IV-P24.  
7. Disable the supply fan motor operation.  
8. Reconnect power to the unit and power exhaust VFD.  
9. Reprogram the power exhaust VFD to accept an external  
reference (in the Utility parameters group [GR.Ut], set  
parameter item Fnod [no.312] = 4).  
10. Enable supply fan motor and return power to the unit.  
Occasionally it may be necessary to restore the VFD de-  
faults to the general Carrier use values. These are stored in an  
OPTION ROM (read-only memory chip). However, some  
variables may need to be manually changed to match the spe-  
cific unit’s factory default settings. To recall the general Carrier  
defaults, enter the Setup mode and set parameter tYP = 3. Re-  
fer to Table 31 for items requiring manual adjustment.  
Table 31 Supply Fan VFD Required  
User Adjusted Defaults  
SIZES  
All  
ITEM  
Motor overload settings (see Table 32)  
1. Check jumper CC-F  
2. Gr.UT/bLSF = 1  
054-104  
3. Gr.SF/Sr.n = 1  
Power Exhaust Variable Frequency Drive  
(48FM and 50FM,FS)  
4. Gr.SF/SrN1 = 0  
5. SEtP/tYP = 5 (Save User Settings)  
NOTE: The VFDs (part no. TOSVERT130-E3) are specially  
modified for use on Carrier equipment. Some specifications  
and control configuration defaults for Carrier applications  
will differ from the VFD manufacturer manual included in the  
packet. See Table 33 for listing of Carrier-specific default  
values.  
Table 32 Supply Fan Motor Overload Settings  
UNIT  
IFM HP  
DESIGNATION  
VOLTAGE  
tHr1  
SETTING  
DESIGNATION  
UNIT 48/50  
AND  
Model No.  
Position 12  
Model No.  
Position 15  
STANDARD TRANSDUCER CONTROL — The VFD  
monitors and controls building pressure (BP) via a differential  
pressure transducer. The pressure transducer is located in the  
auxiliary control box. The pressure transducer’s high-pressure  
reference port is connected to the outside of the unit cabinet by  
a factory-installed tubing section. The pressure transducer’s  
low-pressure reference point must be field-connected to the  
building pressure pick-up (field-supplied and installed in the  
building).  
The BP transducer monitors the static pressure in the occu-  
pied space and provides a 4 to 20 mA signal directly to the  
power exhaust VFD. (Refer to Table 30 for transducer output  
signal [mA] for actual building static pressure.) The internal  
5
5
6
6
6
6
6
And  
And  
And  
And  
And  
And  
And  
N
Q
A
K
Q
Q
T
82.0  
86.0  
80.0  
80.0  
80.0  
80.0  
78.0  
FK,FY,  
JK,JY  
FKX,FKY,  
JKX,JKY  
LEGEND  
IFM Indoor Fan Motor  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
POWER EXHAUST FAN MOTOR NO. 1 OVERLOAD  
PROTECTION — The VFD provides operating overload  
protection for the supply fan motor. The factory has pro-  
grammed the power exhaust VFD overload function to match  
the factory-installed motor (motor size and efficiency). If the  
power exhaust fan motor is changed from the original factory  
selection, the overload value may need to be changed by the  
service person. Contact your local Carrier representative for  
assistance in determining the proper overload setting.  
P24  
LOW LOW  
RR  
SI S2  
S4  
RCH  
RES  
F
R
S3  
P24  
ST  
C
A
RX  
FLB  
FLA  
AM CC CC  
PP  
IV FP  
FM  
FLC  
NOTE: Variable frequency drive size is matched to factory-  
installed motor size. Do not increase motor size without also  
changing to equivalent VFD size.  
4-20mA  
Fig. 56 Variable Frequency Drive Terminal Block  
Table 33 Carrier Power Exhaust VFD Default Program Parameter Values  
PARAMETER GROUP  
PARAMETER  
DEFAULT VALUE  
ACC1  
DEC1  
UL  
60.0 Sec  
60.0 Sec  
59.8 Hz  
LL  
10.0 Hz*  
Luln  
P3  
1
20%  
F-P3  
P4  
0.0 Hz  
98%  
SEtP  
(Setup)  
F-P4  
tHr1  
StC1  
StL1  
OLN  
tYP  
60 Hz  
See Table 35  
0
110%  
1
5*  
FH  
Pt  
60 Hz  
12  
Gr.F  
(Fundamental)  
FbP1  
Fbin  
GP  
Gl  
GA  
1*  
2
.30  
2 sec  
0
Gr.Fb  
(Feedback)  
GFS  
P1LL  
PuL  
PuUl  
PuLL  
80  
10  
1
10  
10  
Gr.SF  
Fsor  
Fr  
60 Hz  
0*  
(Frequency Settings)  
Gr.Pn  
(Panel Control)  
1t  
1t0  
1
0
1t1  
1t2  
1t3  
56  
13  
3
Gr.St  
1t4  
Ot1  
Ot2  
10  
4*  
2*  
5*  
100*  
15*  
1*  
2
(Terminal Selection)  
Ot2d  
Ot2H  
LF  
UuC  
UuCt  
ArSt  
Cnod  
Fnod  
bLPn  
Gr.Pr  
(Protection)  
3
1*  
2*  
1*  
Gr.Ut  
(Utility)  
*These settings differ from the Toshiba defaults and are required for Carrier applications.  
NOTE: To restore original factory settings, change tYP to 6 in SEtup mode (SEtP).  
This restores the VFD original factory settings.  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
POWER EXHAUST VFD OPERATION — When trouble-  
shooting the power exhaust VFD, check first that all required  
conditions for power exhaust VFD operation are satisfied.  
Refer to the separate VFD Operation Manual for detailed  
instructions on accessing diagnostic information, initiating  
troubleshooting, and clearing any trip history.  
For the power exhaust VFD to run, the following conditions  
must be met at the power exhaust VFD:  
1. Drive enable jumper is installed from terminals ST-CC  
(factory supplied) (see Fig. 56).  
2. Proper rotation jumper is installed at terminals R-CC (re-  
verse rotation, factory supplied).  
3. Emergency stop jumper is installed from terminals  
S4-CC (factory supplied).  
RESTORING FACTORY POWER EXHAUST VFD  
DEFAULTS — The original factory configuration values are  
saved in the memory of the power exhaust VFD and can be  
restored by the service person if required. There are two types  
of saved file data: Carrier-factory settings (factory pro-  
grammed settings made to the power exhaust VFD which  
apply specifically to the unit it is installed on) and standard  
defaults for general Carrier unit use.  
The Carrier-factory settings are maintained as user settings.  
These can be restored by entering the Setup mode (in the  
S/P/M menu) and setting parameter tYP = 6 on the keypad/dis-  
play. This will recall the specific factory defaults for this unit.  
Occasionally it may be necessary to restore the power ex-  
haust VFD defaults to the general Carrier use values. These are  
stored in an OPTION ROM (read-only memory chip). Howev-  
er, some variables may need to be manually changed to match  
the specific unit’s factory default settings. To recall the general  
Carrier defaults, enter the Setup mode and set parameter  
tYP = 3. Refer to Tables 34 and 35 for items requiring manual  
adjustment.  
4. A 4 to 20 mA signal is applied across terminals IV-P24  
(from pressure transducer, factory supplied).  
5. DIP switch SW1 (located on the VFD’s printed circuit  
control panel) must be set to “I” (indicating usage of a 4  
to 20 mA input signal at terminals “IV”).  
6. Speed Control (located on the VFD’s keypad/display) set  
for “Remote” (press the “Speed Ctrl” button until LED  
“Remote” is illuminated).  
7. Programmed according to Carrier defaults.  
8. Building Pressure set point established by user, or  
use factory default (30 Hz indicating 0.0 in. wg) (see  
Table 15).  
POWER EXHAUST VFD OPERATIONAL STATUS —  
The power exhaust VFDs contain extensive self-diagnostic  
functions which are accessed through the power exhaust VFD  
display panel (located on the front of the power exhaust VFD  
or at a remote location when the accessory remote display  
package has been installed.)  
Table 34 Power Exhaust VFD Required  
User Adjusted Defaults  
UNIT  
ALL  
ITEM  
Motor Overload Settings (See Table 35)  
Gr.St/Ot1 = 4  
Gr.St/Ot2 = 2  
Gr.St/Ot2d = 5  
Gr.St/Ot2H = 100  
Gr.St/LF = 15  
If using the VFD display panel, disconnect all power to  
the unit and the VFD before entering unit, or use the  
accessory remote display module. Disable supply fan and  
motor operation before accessing VFD-mounted display  
module.  
SEtP/UL = 59.8  
SEtP/P4 = 98  
Table 35 Power Exhaust Motor  
Overload Settings  
When power is first supplied to the power exhaust VFD, the  
display automatically starts with the frequency monitor func-  
tion of its standard monitor mode. In the frequency monitor  
function, the output frequency is displayed. Push the S/P/M  
(Setup/Program/Monitor) key to switch to the Mode Selec-  
tion menu. Push the S/P/M key again to toggle the display  
back to the standard monitor mode.  
From the Mode Selection menu, the service person can  
view all of the monitored status variables, including up to four  
user-selected variables and any trip history in the memory.  
MODEL NUMBER  
POSITION 16  
TOTAL  
HP  
MOTOR HP  
(ea)  
tHr1  
SETTING  
H, T  
J, V  
K, W  
L, X  
M, Y  
20  
30  
40  
50  
60  
10  
15  
20  
25  
30  
97.3  
100.0  
100.0  
93.5  
92.3  
Unit Wiring A typical wiring schematic is shown in  
Fig. 57.  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
LEGEND AND NOTES FOR FIG. 57  
ALM  
C
Alarm  
IGVM Inlet Guide Vanes Motor  
Contactor  
LAT  
LPS  
Leaving-Air Temperature  
Low-Pressure Switch  
CB  
Circuit Breaker  
Control Circuit Breaker  
CCB  
MTR Motor  
COMP Compressor  
MV  
NC  
NO  
Main Valve  
Normally Closed  
Normally Open  
CH  
CR  
Crankcase Heater  
Control Relay  
DPS  
DPT  
EAT  
EC  
Differential Pressure Switch  
Discharge Pressure Transducer  
Enering-Air Temperature  
Enthalpy Control  
OFC Outdoor Fan Contactor  
OFM Outdoor (Condenser) Fan Motor  
OMR Outdoor Motor Relay  
PCB Power Exhaust Circuit Breaker  
PEC Power Exhaust Contactor  
PEDM Power Exhaust Damper Motor  
PEM Power Exhaust Motor  
P, PL Plug  
ECR  
EOR  
Economizer Close Relay  
Economizer Open Relay  
EQUIP Equipment  
FS  
Fan Status Switch  
GND Ground  
RCB Return Fan Circuit Breaker  
RES Resistor  
HIR  
HPS  
HR  
HTR  
IDC  
IDM  
IFC  
Heat Interlock Relay  
High-Pressure Switch  
Heater Relay  
RFC Return Fan Contactror  
RFM Return Fan Motor  
SCT Saturated Condensing Thermistor  
Heater  
Induced Draft Contactor  
Induced Draft Motor  
Indoor (Evaporator) Fan Contactor  
TB  
Terminal Block  
TRAN Transformer  
U
Unloader  
IFCB Indoor Fan Circuit Breaker  
IFM  
IGV  
VFD Variable Frequence Drive  
Field Wiring  
Indoor Fan Motor  
Inlet Guide Vanes  
Factory Wiring  
NOTES:  
1.Connect TRAN1 to  
H4  
H3  
for 460 v units. Connect to  
for 230 v  
units. If 208/230 v units are run with a 208 v power supply con-  
H2  
nect to  
.
2.Connect TRAN2 to BLK lead for 460 v units. Connect to ORN  
lead for 230 v units. If 208/230 v units are run with a 208 v  
power supply connect to RED lead.  
3.Circuit breaker must trip amps are equal to or less than 156%  
FLA (full load amps) for CB1 and CB2. All others are 140%.  
4.If any of the original wire furnished must be replaced, it must  
be replaced with type 90° C wire or its equivalent.  
5.Number(s) indicates the line location of contacts. A bracket  
over (2) numbers signifies single pole double throw contacts.  
An underlined number signifies a normally closed contact.  
Plain numbers (no lines), signify a normally opened contact.  
6.Condenser fan motors are thermally protected.  
7.Three phase motors are protected under primary single phas-  
ing conditions.  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SERVICE TRAINING  
Packaged Service Training programs are an excellent way to increase your knowledge of the equip-  
ment discussed in this manual, including:  
• Unit Familiarization  
• Installation Overview  
• Maintenance  
• Operating Sequence  
A large selection of product, theory, and skills programs are available, using popular video-based for-  
mats and materials. All include video and/or slides, plus companion book.  
Classroom Service Training which includes ‘‘hands-on’’ experience with the products in our labs can  
mean increased confidence that really pays dividends in faster troubleshooting and fewer callbacks.  
Course descriptions and schedules are in our catalog.  
CALL FOR FREE CATALOG 1-800-962-9212  
[ ] Packaged Service Training  
[ ] Classroom Service Training  
Copyright 2000 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
PC 111 Catalog No. 534-763 Printed in U.S.A. Form 48/50F,J-3T Pg 62 3-00 Replaces: 48/50F,J-1T  
Book 1  
1
Tab 1a 1b  
Download from Www.Somanuals.com. All Manuals Search And Download.  
START-UP CHECKLIST  
MODEL NO.: _____________________________________  
SERIAL NO.: ______________________________________  
TECHNICIAN:_____________________________________  
DATE: ___________________________________________  
I. PRE-START-UP:  
VERIFY THAT UNIT IS LEVEL  
VERIFY THAT ALL PACKING MATERIALS HAVE BEEN REMOVED FROM UNIT  
LOOSEN ALL SHIPPING HOLDDOWN BOLTS AND REMOVE SHIPPING BRACKETS PER INSTRUCTIONS  
VERIFY THAT COMPRESSOR SUSPENSION SPRINGS HAVE BEEN LOOSENED PER INSTRUCTIONS  
VERIFY OPENING OF ECONOMIZER HOODS  
VERIFY INSTALLATION OF EXHAUST HOODS  
CONFIRM THAT TUBING FOR SPACE AND SUPPLY DUCT PRESSURES HAS BEEN INSTALLED  
VERIFY THAT CONDENSATE CONNECTION IS INSTALLED PER INSTRUCTIONS  
VERIFY THAT POWER SUPPLY MATCHES UNIT DATA PLATE  
VERIFY THAT ALL ELECTRICAL CONNECTIONS AND TERMINALS ARE TIGHT  
CHECK GAS PIPING FOR LEAKS (48FK,JK ONLY)  
CHECK THAT INDOOR-AIR FILTERS ARE CLEAN AND IN PLACE  
CHECK FAN WHEEL AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE, AND VERIFY SET SCREWS ARE  
TIGHT  
VERIFY THAT FAN SHEAVES ARE ALIGNED AND BELTS ARE PROPERLY TENSIONED  
OPEN SUCTION, DISCHARGE, AND LIQUID LINE SERVICE VALVES  
CHECK COMPRESSOR OIL LEVEL SIGHT GLASS AND VERIFY PROPER LEVEL  
VERIFY THAT CRANKCASE HEATERS HAVE BEEN ENERGIZED FOR 24 HOURS  
CHECK VOLTAGE IMBALANCE  
LINE-TO-LINE VOLTS:  
(AB + AC + BC)/3 = AVERAGE VOLTAGE =  
MAXIMUM DEVIATION FROM AVERAGE VOLTAGE =  
AB  
V
AC  
V
BC  
V
V
V
VOLTAGE IMBALANCE = 100 X (MAX DEVIATION)/(AVERAGE VOLTAGE) =  
%
IF OVER 2% VOLTAGE IMBALANCE, DO NOT ATTEMPT TO START SYSTEM!  
CALL LOCAL POWER COMPANY FOR ASSISTANCE.  
II. PRELIMINARY CHECKLIST ITEMS:  
CONTROL SETTINGS  
DIP SWITCHES SET TO MATCH INSTALLED ACCESSORIES:  
SUPPLY AIR SET POINT RESET (DIP SWITCH NO. 4 ON)  
MORNING WARM-UP (DIP SWITCH NO. 4 ON)  
DEMAND LIMIT (DIP SWITCH NO. 5 ON)  
SUPPLY AIR SET POINT (P1) SET BETWEEN 45 AND 70 F  
ECONOMIZER MINIMUM POSITION (P5) SET PER PLANS  
SUPPLY AIR SET POINT RESET SETTINGS:  
RESET INITIATION TEMPERATURE (P7) (TYPICALLY 68 TO 72 F)  
RESET LIMIT TEMPERATURE (P3) (TYPICALLY 60 TO 70 F)  
MORNING WARM-UP TEMPERATURE (TYPICALLY 50 TO 65 F)  
IGV/VFD DUCT PRESSURE SET POINT PER PLANS  
BUILDING PRESSURE (MODULATING POWER EXHAUST) SET PER PLANS  
DEMAND LIMIT SETTINGS PER PLAN:  
SINGLE STEP DEMAND LIMIT (P4) SET (TYPICALLY 25 TO 50%)  
TWO-STEP DEMAND LIMIT  
DLCM-P1 SET (TYPICALLY 50 TO 75%)  
DLCM-P2 SET (TYPICALLY 0 TO 25%)  
OCCUPIED/UNOCCUPIED SWITCH INSTALLED PER FIG. 23 (CLOSE TO START UNIT)  
CL-1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
III. START-UP  
CHECK EVAPORATOR FAN SPEED AND RECORD.  
CHECK CONDENSER FAN SPEED AND RECORD.  
AFTER AT LEAST 10 MINUTES RUNNING TIME, RECORD THE FOLLOWING MEASUREMENTS:  
COMP A1  
COMP A2  
COMP B1  
COMP B2  
OIL PRESSURE  
SUCTION PRESSURE  
SUCTION LINE TEMP  
DISCHARGE PRESSURE  
DISCHARGE LINE TEMP  
ENTERING CONDENSER AIR TEMP  
LEAVING CONDENSER AIR TEMP  
EVAP ENTERING AIR DB TEMP  
EVAP ENTERING AIR WB TEMP  
EVAP LEAVING AIR DB TEMP  
EVAP LEAVING AIR WB TEMP  
COMPRESSOR AMPS (L1)  
COMPRESSOR AMPS (L2)  
COMPRESSOR AMPS (L3)  
ELECTRICAL  
SUPPLY FAN AMPS  
EXHAUST FAN AMPS  
L2  
ELECTRIC HEAT AMPS L1  
TEMPERATURES  
L3  
(50 SERIES UNITS ONLY)  
OUTDOOR-AIR TEMPERATURE  
RETURN-AIR TEMPERATURE  
COOLING SUPPLY AIR  
PRESSURES  
F
F
F
DB (Dry-Bulb)  
DB  
F WB (Wet-Bulb)  
GAS INLET PRESSURE  
IN. WG (48 SERIES UNITS ONLY)  
GAS MANIFOLD PRESSURE STAGE NO. 1  
UNITS ONLY)  
IN. WG  
STAGE NO. 2  
IN. WG (48 SERIES  
REFRIGERANT SUCTION  
CIRCUIT NO. 1  
PSIG  
PSIG  
CIRCUIT NO. 2  
CIRCUIT NO. 2  
PSIG  
PSIG  
REFRIGERANT DISCHARGE CIRCUIT NO. 1  
VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS IN UNIT INSTALLATION INSTRUCTIONS  
GENERAL  
ECONOMIZER MINIMUM VENT SETTING TO JOB REQUIREMENTS  
IV. NOTES  
Copyright 2000 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book  
Tab  
1
1
PC 111  
Catalog No. 534-763  
Printed in U.S.A.  
Form 48/50F,J-3T  
Pg CL-2  
3-00  
Replaces: 48/50F,J-1T  
1a 1b  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Bernina Sewing Machine 950 Industrial User Manual
Billion Electric Company Network Router 5200S Series User Manual
Black Decker Air Compressor 9527 User Manual
Blue Rhino Gas Grill NPG2301 C User Manual
Bowers Wilkins Speaker CCM 628 User Manual
Brother Sewing Machine 885 V35 V37 User Manual
Cabletron Systems Switch 5500 User Manual
Chevrolet Automobile 1500 User Manual
Chicago Electric Saw 97580 User Manual
Cisco Systems Network Card Cisco 2800 User Manual