Carrier Air Conditioner 37HS User Manual

37HS  
ModulineAir Terminals  
Application Data  
Page  
CONTENTS  
VAV HEATING AND COOLING WITH  
SYSTEM-POWERED CHANGEOVER  
VAV HEATING  
Page  
INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2  
BUILDING LOAD CALCULATION . . . . . . . . . . 2-23  
System-Powered Controls With  
Electric Interface . . . . . . . . . . . . . . . . . . . . . . . . . 64  
VAV COOLING WITH ELECTRIC WARM-UP  
VAV HEATING AND COOLING WITH  
ELECTRIC CHANGEOVER  
VAV COOLING WITH ELECTRIC HEAT  
INTERLOCK  
System-Powered Controls With  
Pneumatic Interface . . . . . . . . . . . . . . . . . . . . . . 69  
• PNEUMATIC SEQUENCED HEATING/  
COOLING (HOT WATER)  
VAV COOLING WITH PNEUMATIC  
WARM-UP OR FIRE SAFETY SWITCH  
Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
• LOAD CONSIDERATIONS  
2
• DESIGN PROCEDURE  
Heating . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20  
• OVERHEAD AIR HEATING  
TERMINAL SELECTION AND LAYOUT . . . . . 23-41  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23  
Step 1 — Determine Air Volume (Cfm)  
Per Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24  
Step 2 — Lay Out Terminals . . . . . . . . . . . . . . . 25  
Step 3 — Consider Unit Combinations  
and Run-Out Duct . . . . . . . . . . . . . . . . . . . . . . . . 27  
Step 4 — Determine Controller Location . . . . 37  
Final Layout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41  
AIRFLOW ADJUSTMENT . . . . . . . . . . . . . . . . . . 71,72  
Maximum Airflow (Cfm) Adjustment . . . . . . . . 71  
Minimum Airflow (Cfm) Adjustment . . . . . . . . . 71  
Variation in Maximum Airflow . . . . . . . . . . . . . . 72  
THE MODULINE VALVE . . . . . . . . . . . . . . . . . . . 41-44  
The Moduline Control Concept . . . . . . . . . . . . . 41  
• HIGH AND LOW PRESSURE  
AIR DISTRIBUTION . . . . . . . . . . . . . . . . . . . . . . . . 73  
Throw for Standard Diffusers . . . . . . . . . . . . . . . 82  
• BELLOWS PRESSURE  
• UNIT AIRFLOW DELIVERY  
INTRODUCTION  
CONTROL APPLICATIONS . . . . . . . . . . . . . . . . 44-50  
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44  
System-Powered Controls . . . . . . . . . . . . . . . . . 44  
• COMPONENTS OF THE SYSTEM-  
POWERED CONTROL SYSTEM  
The Modulineair terminal (Fig. 1) is a truly flexible unit  
for the control and distribution of conditioned air to the oc-  
cupied space. Available in 3 airflow sizes for single or mul-  
tiple terminal installation, it is adaptable to a variety of  
• SYSTEM-POWERED APPLICATIONS  
Constant Volume (CV) Cooling  
CV Heating  
Variable Air Volume (VAV) Cooling  
VAV Cooling With Warm-Up  
VAV Heating and Cooling With Changeover  
VAV Heating  
• SYSTEM-POWERED CONTROLS WITH  
ELECTRIC INTERFACE  
VAV Cooling With Electric Warm-Up  
VAV Heating and Cooling With Electric Changeover  
VAV Cooling With Electric Heat Interlock  
• SYSTEM-POWERED CONTROLS WITH  
PNEUMATIC INTERFACE  
Pneumatic Sequenced Cooling/Heating (Hot Water)  
VAV Cooling With Pneumatic Warm-Up  
VAV Cooling With Fire Safety  
Night Set Back Heating  
VAV Cooling/Separate System Heating  
CONTROL SELECTION . . . . . . . . . . . . . . . . . . . 50-54  
Control Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Control Packages . . . . . . . . . . . . . . . . . . . . . . . . . 50  
CONTROL OPERATING SEQUENCES . . . . . . 55-71  
System-Powered Controls . . . . . . . . . . . . . . . . . 55  
• CV COOLING  
• CV HEATING  
VAV COOLING  
VAV COOLING WITH WARM-UP  
Fig. 1 — Moduline Air Terminal  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 3  
PC 201  
Catalog No. 513-741  
Printed in U.S.A.  
Form 37HS-1XA  
Pg 1  
6-91  
Replaces: New  
Tab 6a  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Oversizing — Oversizing of variable volume systems re-  
sults in unused equipment capacity and worse performance  
at part load, not in increased system airflow. The actual sys-  
tem operation will reflect the actual system load, not the de-  
sign load. If conservative data, safety factors, or provision  
for future loads are included in the design estimate, the ac-  
tual system airflow will not be increased. The equipment will  
be capable of handling an increased load should it ever ex-  
ist, but will automatically throttle back to handle only the  
actual load at that moment.  
It is recommended that safety factors not be included in  
load calculations; they are not included in the following method.  
Air Motion, Ventilation and Odor Dilution — Air motion,  
ventilation, and odor dilution deserve special attention in the  
design of a VAV system. The designer must visualize the  
correct system operating condition in order to evaluate the  
adequacy of these items at either full or part-load cooling  
conditions, or during the heating season.  
Room air motion is determined by the supply air quantity  
and the diffuser induction ratio. The minimum room air ve-  
locity is higher if building humidity and temperature are higher.  
The design cfm at peak cooling load in any zone should be  
not less than the minimum shown below:  
Fig. 3 — Estimating Block Load  
DESIRED  
ROOM TEMPERATURE  
(F)  
DESIGN CFM  
AT PEAK COOLING  
(cfm/sq ft)  
78  
75  
0.7  
0.4  
These minimums are based on using the Carrier Modu-  
line diffuser, which has very high performance; competitive  
diffusers require a higher cfm/sq ft.  
The outside air cfm requirement at maximum design con-  
ditions may be determined by local building code. If the out-  
side air cfm to the central air handler is adequate to maintain  
a low overall building odor level, the odor level in a par-  
ticular space will depend upon the odors generated locally in  
that space and the supply airflow to that space. A space with  
high odor generation (a conference room with much smok-  
ing) should be provided with a separate exhaust system to  
increase the air flow through the space for odor dilution. The  
only way to increase the VAV airflow to that space would be  
to add reheat to increase the room sensible heat, which is  
unacceptable from an energy conservation standpoint.  
Fig. 4 — Floor Plan of Typical Zones  
for Single-Story Office Building  
LOAD CONSIDERATIONS  
Lighting — Even though lighting loads (Watts/sq ft) are con-  
siderably lower in today’s buildings, the lighting is by far  
the largest load component.  
It is necessary, therefore, to pay close attention to getting  
an accurate estimate of the lighting requirements.  
In estimating the lighting load, special consideration should  
be given to evaluating storage effect and the performance of  
return air ceiling plenums. Both of these items reduce the  
peak room load from lights and delay the time at which the  
stored heat becomes a load on the central equipment.  
The following odor dilution cfm (either VAV supply or  
supplemental exhaust cfm) is usually adequate:  
Private or General Office — 0.25 cfm/sq ft  
Major Conference Room — 1.0 cfm/sq ft  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
1. Using the E20-II Block Load Program, select Cincinnati  
for its weather data. The WEATHER PARAMETERS print-  
out shown on pages 5 and 6 shows the weather data used  
for the load estimating calculations.  
Supply Air Temperature — In systems using draw-thru air  
handling units and high induction Carrier Modulinetermi-  
nal units, the acceptable range of supply air temperatures at  
the terminals is from 50 to 54 F. The cooling coil ADP (Ap-  
paratus Dew Point) will be from 3 to 5° F lower than the  
supply air temperature, due to allowance for coil bypass, fan  
heat and duct gain.  
The system installed cost for ductwork, central air han-  
dler, and VAV terminals will be greater if the air quantity is  
higher because of the designer’s choice of a higher supply  
air temperature. The increased fan air quantity will result in  
higher fan operating cost, which may be offset by the lower  
cost of operating the refrigeration system at a higher suction  
temperature. The higher coil surface temperature (ADP) of  
the system will result in a higher building humidity, which  
will be less comfortable and require greater ventilation air.  
2. The next step is to gather data on the building, including  
dimensions, construction materials used, internal load pat-  
terns (such as lighting levels) and the building orienta-  
tion. For our example, we have divided the building into  
nine zones. The actual building has ten zones on its north  
exposure, but we’ve grouped them all into a single zone  
because zones on the same exposure tend to have similar  
load patterns. Similarly, the ten south exposure zones have  
been grouped into a single zone, and the four east and  
west zones have been combined into single east and west  
zones respectively.  
Pages 7-15 contain the ZONE DESCRIPTION printouts  
for each of the nine zones.  
An unduly low choice of supply air temperature may  
result in unacceptably low room air motion in interior zones  
with low lighting levels, and in unnecessarily low  
humidity.  
The same supply air temperature must be used for the zone  
load and block load estimates.  
3. The final input step is to select an initial set of system  
design data, including the cooling and heating set points,  
the supply air temperature (or supply airflow rate, if that  
is known) and the fan static pressure. This system design  
data will, of course, be directly influenced by the actual  
central station equipment, be it packaged or applied.  
Load Calculating Methods — The cooling load estimates can  
be made very accurately and quickly using the Carrier E20-II  
Block Load program.  
Because of the computer’s speed, it is not necessary to  
compromise the design procedure to obtain the most accu-  
rate result. The optimum design procedure listed here as-  
sumes the use of the E20-II program, and may require ‘‘short  
cuts’’ when using manual methods.  
While the E-20 program is the most convenient and rapid  
method of load calculation, other methods will also provide  
the required results. In particular, Carrier multi-room load  
estimating form E-5056 is available for this purpose.  
Page 16 shows the HVAC SYSTEM DATA printout which  
lists the system design data we’ve selected for this  
example.  
Load Calculations — With the input data from Step 1, the  
Block Load Program calculates the building loads for each  
month of the year to find the largest load on the building’s  
air conditioning system. Typically, this will occur during the  
middle or late afternoon hours in July or August. The  
SYSTEM SIZING SUMMARY printout shown on pages 17  
and 18 provides both the cooling and heating equipment siz-  
ing data. At the same time, it provides the maximum cooling  
load, maximum heating load and design airflow rate for each  
zone in the building. Notice that each zone may peak at a  
month and hour different from that at which the HVAC sys-  
tem peaks. The detailed system load report is shown on  
page 19.  
DESIGN PROCEDURE (with example)  
Data Collection — Our example uses Cincinnati, Ohio as a  
representative city. The building is a one-story office build-  
ing with 11,250 sq ft. The building layout is shown in  
Fig. 4 on page 3.  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
ModulineSelection (Analysis of Data) — The printout shown below presents an analysis of the preceding data.  
Separate Duct Heating — A simple type of overhead air heat-  
ing system for use with a Moduline cooling system consists  
of a series of ceiling outlets, placed around the perimeter of  
the building close to the outside wall, which blow warm air  
outward and/or downward to floor level. The outlets are con-  
nected by a simple duct system to an electric (or hot water)  
heating-only fan coil unit located above the ceiling. (See  
Fig. 5.) A minimum of one fan coil unit per exposure is used  
for each story of the building. The fan coil unit draws air  
from the ceiling plenum and distributes it to the building pe-  
rimeter by means of a separate duct system. This type of  
heating system operates at constant volume.  
The separate duct heating approach allows heat to blanket  
the outside wall, eliminating the transmission of heat through  
the outside wall and permits the Moduline cooling units to  
be located in the best arrangement for cooling distribution.  
Control interlock between separate system heating and Modu-  
line cooling is outlined in the Control Applications section,  
on page 44.  
Heating — Heat must be provided in a building to offset  
losses through the perimeter walls, windows, and roof. In  
the interior spaces the heat gain from lights and people will  
in many cases be enough to cause a cooling load even in  
winter.  
The two most commonly used heating systems are these:  
• Baseboard  
• Overhead air  
Baseboard has been used historically in the North because  
it is effective in overcoming the downdraft from windows,  
particularly with the large single pane windows used in the  
past.  
Now, with improvements in the building thermal enve-  
lope due to better materials and construction methods, over-  
head air heating is a viable and attractive alternative.  
Overhead air heating, when properly applied, can handle  
all requirements except the severe cases in which the wall U  
values and temperature differences are large.  
The 35BD heating slot boot diffuser (Fig. 6) is specifi-  
cally designed for this heating approach and will provide ex-  
cellent distribution of the hot air necessary to offset the load.  
Overhead air heating is the method which will be con-  
sidered for these procedures.  
OVERHEAD AIR HEATING — Two basic forms of over-  
head heating are used with Moduline cooling systems:  
• Separate duct heating  
• Changeover Moduline heating/cooling  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 5 — Separate Duct Heating System  
Performance Heating — Downblow Slot  
NOMINAL  
LENGTH (ft)  
2
4
Placement  
(in.)  
Placement  
(in.)  
TYPE  
DIFFUSER  
Cfm  
Cfm  
Min  
Max  
Min  
Max  
Heating Slot  
Boot Diffuser  
20-70  
12  
24  
25-120  
12  
24  
NOTES:  
1. Minimum and maximum show distance diffuser should be lo-  
cated from perimeter wall in inches.  
2. For optimum performance of the diffuser, the air temperature should  
be held between 90 and 115 F.  
Fig. 6 — 35BD Heating Slot Boot Diffuser  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The Moduline location for heating and cooling requires  
the unit to be a specific distance from the outside wall in  
order to produce satisfactory distribution of the hot air. The  
recommended location is shown in Fig. 8.  
Changeover ModulineHeating/Cooling — Both hot air and  
cold air distribution are possible with a Moduline system.  
The Moduline unit uses a director diffuser which, sensing  
the duct temperature of the supply air, directs the air towards  
or away from the perimeter wall. (Fig. 7.)  
HEATING  
COOLING  
With cold air in the duct, the discharge is two-way blow — both into  
the room and towards the wall.  
With hot air in the duct, all discharge air is directed towards the  
perimeter wall to offset the transmission.  
Fig. 7 — Director Diffuser  
DISTANCE TO OUTSIDE WALL ‘‘L’’  
Minimum  
Maximum  
M − H  
2
L =  
Where:  
2.5 Ft  
M = Max Throw  
for Heating  
One-Way Blow  
H = Ceiling Height  
Fig. 8 — Recommended Location for Changeover ModulineHeating/Cooling  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Additional Guidelines for Heating — In addition to down-  
blow slot boot diffusers and Moduline director diffusers, round  
nozzles spaced along the perimeter wall will also provide  
satisfactory overhead heating distribution. Some guidance for  
outlet use are shown in Tables 1 and 2.  
TERMINAL SELECTION  
AND LAYOUT  
Introduction — Selecting the terminals and making a  
layout is one of the most important steps in the design pro-  
cess. This is where you use your knowledge to lay out the  
job at a low cost and still give your client a satisfactory job.  
There are 4 items which must be considered when select-  
ing an air terminal:  
Moduline heating and cooling is less flexible than sepa-  
rate duct system heating with Moduline cooling because:  
• Moduline heating/cooling is a changeover system requir-  
ing complete replacement of the cooling duct supply air  
with heated air, making zone control difficult.  
• air volume (Cfm) per terminal — a function of 1) the de-  
sired sound level in the space, and 2) cost  
• layout — a function of 1) the proper room air motion and  
2) physical spacing  
• unit combinations and run-out duct  
• controller location  
• Moduline location is a compromise between obtaining out-  
side wall coverage with hot air and good cooling  
distribution.  
Thus, separate duct heating can provide heat for a given  
exposure without materially affecting the building cooling  
system. The heating outlets and Moduline terminals can be  
located in the most efficient air distribution places of the con-  
ditioned space.  
Definitions — Following are definitions of terms used  
when discussing the layout of a Moduline system.  
Moduline units are arranged as single units or as units in  
an air series.  
SINGLE UNIT — A single unit is connected to the supply  
duct and supplies conditioned air to a space or part of a space.  
Fig. 9.  
Table 1 — Optimum Outlet Discharge  
AIR SERIES — Units in air series are connected unit-to-  
unit or with interconnecting ductwork and the supply air for  
all units enters the first unit in the series. Fig. 10.  
DIFFUSER SLOTS  
VELOCITY (Fpm)  
TEMPERATURE (F)  
Downblow slots  
Round nozzles  
One-way blow slots  
Director Diffusers  
500 to 1250  
900 to 1800  
600 to 2200  
800 to 2200  
90 to 115  
90 to 125  
80 to 105  
90 to 105  
MASTER UNIT — A Moduline unit with controller, alone  
or in air series, is a master unit. Fig. 11.  
SLAVE UNIT — A unit in air series, controlled by another  
unit (master unit) is a slave unit. Fig. 11.  
CONTROLS — System-powered controls are installed at the  
jobsite and consist of the components shown below:  
Table 2 — Location Guidelines  
MINIMUM  
MAXIMUM  
DISTANCE (ft)*  
Constant Volume — Filter and volume controller.  
DIFFUSER STYLE  
DISTANCE (ft)*  
Variable Volume, Diffuser Thermostat — Filter, volume con-  
troller, thermostat with aspirator.  
Variable Volume, Wall Thermostat — Filter, volume con-  
troller, wall thermostat.  
Round Nozzles and  
Downblow Slots  
1.0  
2.0  
One-Way Blow Slots  
Director Diffusers  
0.5  
2.5  
L†  
L†  
*Feet away from outside wall.  
†See Fig. 8.  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 9 — Single ModulineUnit Connected to  
Supply Duct  
Fig. 12 — Control Block  
Fig. 10 — Moduline Units in Air Series  
Fig. 13 — Control End of Unit  
Step 1 — Determine Air Volume (Cfm) Per Ter-  
minal — Before you can start making a layout, you must  
know the required air volumes (cfm).  
Use the cfm per zone you obtained from the cooling load  
calculation and, using Table 3, Recommended Maximum Cfm  
Per Terminal, decide on the number of terminals you will  
need in each zone.  
Fig. 11 — Master Unit and Slave Units  
Cost dictates that the fewest number of Moduline units be  
used consistent with good design. The maximum cfm per  
unit that can be used (to keep the total number of units down)  
is mainly a function of maximum acceptable sound level.  
Perimeter zones with glass in the east, west, and south  
building zones have peaks of rather short duration (i.e. loads  
vary widely during the course of the day and year). There-  
fore, a higher sound level can be tolerated for these short  
peaks.  
CONTROL END — The control end of a Modulineunit is  
the end containing a control block at the end plate of the  
valve section of the unit. (Fig. 12.) The end of the unit op-  
posite the control end contains a blank block. The control  
end of the Moduline unit is at the longer of the diffuser pro-  
jections from the plenum. In Fig. 13, the longer projection,  
B, is the control end.  
The filter, volume controller, and diffuser-mounted ther-  
mostat are applied to the control end of a master unit.  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
As a result, slightly higher maximum cfm per unit is al-  
lowed as compared to interior zones or the north perimeter,  
which have relatively constant loads.  
The maximum cfm per unit also is affected by the desired  
sound level in the room and the type of use of the space.  
Most jobs use a 2- x 4-ft grid T-Bar ceiling with 2- x 4-ft  
or 2- x 2 ft tiles.  
The first consideration in making a layout is to place the  
terminals as economically as possible in the grid, which means  
locating the terminals perpendicular to the main tees.  
For example, an executive office uses low sound levels  
but the furnishings generally absorb more sound so the al-  
lowable cfm/unit is only slightly lower than other types of  
rooms.  
Main tees (the ones with hangers) are 4 ft on center (nor-  
mally) and the cross tees are spaced 2 ft apart between the  
mains to make up a 2- x 4-ft T-bar grid. Additional trim tees  
may be used to divide the ceiling into a 2- x 2-ft grid.  
The Moduline units use mounting brackets and hang from  
(run perpendicular to) the main tees. While the units can be  
installed anywhere between mains, the most common loca-  
tion is on the center line of the cross tee (replaces the cross  
tee). The next most common location is half way between  
cross tees. See Fig. 15.  
While less desirable, the units can be run parallel to the  
main tees. Unless absolutely necessary the units should not  
replace the main tee because this means the main tee must  
be cut. A location halfway between the mains is common  
and in this case additional hangers are required to the upper  
plenum of the unit or to the cross tee near the unit.  
Table 3 — Recommended Maximum Cfm  
Per Terminal  
MODULINE UNITS  
37HS1  
37HS2  
37HS4  
TYPE OF  
SPACE USE  
East  
West  
and  
East  
West  
and  
East  
West  
and  
Interior  
and  
North  
Interior  
and  
North  
Interior  
and  
North  
South  
South  
South  
General  
Office  
110  
100  
90  
95  
90  
80  
75  
220  
200  
180  
170  
190  
180  
160  
150  
400  
330  
300  
280  
350  
300  
270  
250  
With  
Carpet  
Private  
Office  
With  
Tile  
Special units are available for many other types of  
ceilings.  
Executive  
Office  
85  
Step 2 — Lay Out Terminals  
LOCATE UNITS IN T-BAR GRID — In making a layout,  
begin with a plan view of the ceiling. Normally, the ceiling  
grid and the lighting is done first and the diffuser plan must  
fit the layout.  
The center of the room is the ideal location, but where  
that space has been reserved for lighting, the Moduline dif-  
fuser has enough flexibility to provide good distribution when  
not centered in the room.  
For a two-way blow diffuser, anywhere from the 14 point  
1
to the 4 point (wall to wall) is usually suitable. Outside of  
the 14 points, a one-way blow diffuser may be needed. Use  
two-way blow diffuser wherever possible and one-way blow  
only when really necessary. (See Fig. 14.)  
Fig. 15 — Terminal Location  
Fig. 14 — Diffuser Locations for  
Preferred 2-Way or One-Way Blow  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EVALUATE THE THROW OF MODULINEUNITS IN  
POSSIBLE LOCATIONS — Check minimum throw for  
2-way blow diffuser near walls and all one-way blow  
diffusers.  
Table 4 — Air Throw Data —  
1-Way and 2-Way Blow, 2-Slot Diffusers  
OPTIMUM AIR THROW (ft)  
37HS1 UNIT  
AIRFLOW  
(Cfm)  
1-Way Blow  
2-Way Blow  
Exceeding maximum throw is almost never a problem. A  
2-way blow unit covers 50 ft at nominal cfm.  
Min  
Max  
Min  
Max  
40  
50  
2.0  
4.0  
7.0  
9.0  
2.0  
3.0  
3.5  
4.0  
4.5  
5.0  
6.0  
7.0  
5.0  
6.0  
60  
7.5  
12.0  
15.0  
18.0  
20.0  
22.0  
24.0  
7.5  
In perimeter rooms, if 2-way blow units are off center,  
favor the exterior wall if possible.  
70  
8.0  
9.0  
10.0  
11.0  
12.0  
9.0  
80  
10.5  
11.5  
13.0  
15.0  
90  
Generally, one-way blow diffusers should blow away from  
the nearest wall.  
100  
110  
Air throw data in Tables 4 and 5 for the Modulineair  
terminals provides the suggested minimum and maximum  
coverages the units can handle in a typical installation while  
maintaining the desired room conditions.  
OPTIMUM AIR THROW (ft)  
1-Way Blow 2-Way Blow  
37HS2 UNIT  
AIRFLOW  
(Cfm)  
Min  
Max  
Min  
Max  
80  
100  
120  
140  
160  
180  
200  
220  
2.0  
4.0  
7.0  
9.0  
2.0  
3.0  
3.5  
4.0  
4.5  
5.0  
6.0  
7.0  
5.0  
6.0  
7.5  
12.0  
15.0  
18.0  
20.0  
22.0  
24.0  
7.5  
The optimum air throw values given in the table are dis-  
tances from the unit centerline to the outside wall or nearest  
obstruction (wall, light fixture, or opposing air stream).  
8.0  
9.0  
10.0  
11.0  
12.0  
9.0  
10.5  
11.5  
13.0  
15.0  
When given a choice, always put diffusers in line with each  
other, not blowing at each other. If diffusers must be placed  
so they are blowing at each other, the minimum throw must  
be checked. Do not put units closer together than minimum  
allows. Down-drafts caused by going below minimum will  
bother room occupants. (Fig. 16)  
OPTIMUM AIR THROW (ft)  
1-Way Blow 2-Way Blow  
37HS4 UNIT  
AIRFLOW  
(Cfm)  
Min  
Max  
Min  
Max  
160  
200  
250  
300  
350  
400  
440  
8.5  
10.0  
11.0  
12.0  
14.0  
15.0  
17.0  
16.0  
20.0  
21.0  
22.0  
23.0  
25.0  
29.0  
5.0  
6.0  
7.0  
10.0  
13.0  
17.0  
19.0  
21.0  
24.0  
7.0  
Modulineunits can be placed fairly close to a wall or  
partition. This is because the down-draft follows the wall  
(stays close to the wall) and doesn’t bother the room occu-  
pant. If furniture is placed against the wall near a Moduline  
unit, it causes the air to be deflected causing drafts. The prob-  
lem can often be solved by moving the furniture 6 in. or so  
away from the wall.  
8.0  
9.0  
10.0  
13.0  
Table 5 — Air Throw Data —  
2-Way and 1-Way Director, 3-Slot Diffusers  
OPTIMUM AIR THROW (ft)  
37HS1 UNIT  
Heating  
Cooling  
AIRFLOW  
(Cfm)  
1-Way Blow  
2-Way Blow  
Min  
Max  
Min  
Max  
40  
50  
2.0  
4.0  
7.0  
9.0  
2.0  
3.0  
3.5  
4.0  
4.5  
5.0  
6.0  
7.0  
5.0  
6.0  
60  
7.5  
12.0  
15.0  
18.0  
20.0  
22.0  
24.0  
7.5  
70  
8.0  
9.0  
10.0  
11.0  
12.0  
9.0  
80  
10.5  
11.5  
13.0  
15.0  
90  
100  
110  
OPTIMUM AIR THROW (ft)  
Heating Cooling  
1-Way Blow 2-Way Blow  
37HS2 UNIT  
AIRFLOW  
(Cfm)  
Min  
Max  
Min  
Max  
80  
100  
120  
140  
160  
180  
200  
220  
2.0  
4.0  
7.0  
9.0  
2.0  
3.0  
3.5  
4.0  
4.5  
5.0  
6.0  
7.0  
5.0  
6.0  
7.5  
12.0  
15.0  
18.0  
20.0  
22.0  
24.0  
7.5  
8.0  
9.0  
10.0  
11.0  
12.0  
9.0  
10.5  
11.5  
13.0  
15.0  
OPTIMUM AIR THROW (ft)  
Heating Cooling  
1-Way Blow 2-Way Blow  
37HS4 UNIT  
AIRFLOW  
(Cfm)  
Fig. 16 — Locate Units to Prevent Down-Drafts  
Min  
Max  
Min  
Max  
160  
200  
250  
300  
350  
400  
440  
8.5  
10.0  
11.0  
12.0  
14.0  
15.0  
17.0  
16.0  
20.0  
21.0  
22.0  
23.0  
25.0  
29.0  
5.0  
6.0  
7.0  
10.0  
13.0  
17.0  
19.0  
21.0  
24.0  
7.0  
8.0  
9.0  
10.0  
13.0  
NOTES:  
1. Minimum air throw refers to the distance from the diffuser where the air ve-  
locity is 150 fpm. In maximum air throw, this velocity has dropped to 50 rpm.  
2. Data is based on an area with a 9-ft ceiling. For higher ceilings, values may  
be reduced by one foot for each foot of height increase. For specific instal-  
lations, minimum values can be reduced if properly qualified. Values are  
dependent on cfm only and are not affected by duct pressure.  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
STAGGER SPACING — A frequently used layout method  
is to stagger the units. This arrangement gives good cover-  
age, solves the problem of drafts when units blow at each  
other, and is low cost. It also gives good flexibility for future  
partition changes. (Fig. 17.)  
Step 3 — Consider Unit Combinations And Run-  
Out Duct — When the preliminary office layout is com-  
plete, the trunk or main duct can be laid on the floor plan.  
We are now ready for positioning the units in the space ac-  
cording to the load calculations and the design of the run-out  
ducts.  
The zone load calculation provides the cfm requirements  
for each space. Using those requirements and the ceiling lay-  
out, the unit location and run-out can be determined. Figure  
19 shows a single Moduline unit located on the grid line in  
the approximate center of the space. Figure 20 shows mul-  
tiple units in an air series located in similar fashion.  
RECOMMENDED UNIT COMBINATIONS — Tables 6-8  
list the recommended combinations of Moduline terminals.  
Each model (size) of Moduline terminal is shown in com-  
binations of 2, 3, 4 and 5 plenum sizes. To illustrate the use  
of the tables, consider the 37HS2 for a space requiring 550  
cfm. Three units in air series will provide the capacity. (Note  
that 550 cfm is below the max cfm limit of 660 shown in  
Table 7.) Six combinations of 37HS2 units are available; all  
will produce a good installation. However, some factors in-  
fluence the choice:  
If it is desirable to have common plenum sizes throughout  
the space, the choice will be three 9 x 9-in. plenums.  
Fig. 17 — Staggered Units  
The lowest inlet velocities will result in the least variance  
of discharge cfm among the 3 units on one control.  
If this is a consideration, the choice would be three 11 x 11-  
in. plenums.  
MAXIMUM UNIT SPACING — Interior zones use less air,  
as low as 0.4 to 0.6 cfm per sq ft. Using the large capacity  
37HS4 unit at 250 to 350 cfm each may cause units to be too  
widely separated. This results in poor coverage and poor air  
distribution.  
The lowest cost choice would be 9- x 9-in., 9- x 9-in., and  
7- x 7-inches.  
A good solution is to use a larger number of lower ca-  
pacity 37HS2 units at 150 to 190 cfm each.  
The maximum distance between units parallel to each other  
(blowing at each other) can and should be fairly great, 25 to  
45 ft. (See Tables 4 and 5.) But the maximum distance be-  
tween the ends of the units in the same row must be more  
limited for good coverage.  
If the requirement of the space is for maximum cfm from  
the unit combination, one of the larger plenum combinations  
would be favored.  
Conversely, a conservative design with small cfm per unit  
can use the smaller plenum sizes.  
The unit will effectively cover a strip whose width is 3 to  
4 times the unit’s length. A 4-ft unit would therefore cover  
an area whose width is 12 to 16 ft (maximum). See  
Fig. 18.  
The selection of plenum sizes will not affect the sound  
level of the space; there is no measurable difference in the  
recommended plenum combinations.  
The high induction ratio of the Modulinediffuser keeps  
total room air motion up to acceptable levels when the cfm  
per sq ft is low.  
NOTE: The listing of recommended air series combinations  
does not indicate that one controller will always handle the  
combination; in some cases, a second controller may be re-  
quired. Refer to Determine Controller Location section,  
page 37.  
Table 9 provides an overall limitation on cfm in the inlet  
collar of units in air series.  
Fig. 18 — Unit Spacing  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 19 — Run-Out Duct for Single ModulineUnit  
Fig. 20 — Run-Out Duct for Moduline Units in Air Series  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 — 37HS1 Units in Air Series  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 6 — 37HS1 Units in Air Series (cont)  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 — 37HS2 Units in Air Series  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 7 — 37HS2 Units in Air Series (cont)  
Table 8 — 37HS4 Units in Air Series  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 8 — 37HS4 Units in Air Series (cont)  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 9 — Maximum Cfm Through the Inlet Collar  
of a Single Unit or of Units in Air Series  
In general, units in an air series should not be of mixed  
sizes (cfm capacities). If units of different capacities are used,  
a controller must be applied for each size unit. For example,  
an application for 800 cfm using different capacity units, as  
shown in Fig. 21, is acceptable only with multiple controls.  
This arrangement, although not preferred, can be used if care  
is taken to use the necessary controllers. In this case, 3 con-  
trollers are required. However, the best installation for an  
800 cfm (nominal cfm total) would be one in which all the  
units are the same size. (Fig. 22.) In this case, a single con-  
troller can be used in the space.  
INLET  
PLENUM  
SIZE  
(in.)  
MAXIMUM TOTAL  
AIRFLOW  
COLLAR  
DIAM  
MODEL  
(Cfm)  
(in.)  
5 x 7  
7 x 7  
4
6
110  
400  
37HS1  
9 x 9  
8
800  
11 x 11  
7 x 7  
10  
6
1100  
400  
37HS2  
37HS4  
9 x 9  
8
800  
11 x 11  
9 x 9  
10  
8
1100  
800  
11 x 11  
13 x 13  
10  
12  
1100  
1600  
Fig. 21 — Air Series of Units with Different Capacities  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 22 — Air Series of Units of the Same Size and Capacity  
FLEX DUCT IN AIR SERIES — Flexible duct is often used  
minimum static pressure for multiple units is equal to 0.75  
in. wg. Three lengths of flex duct at 4.5 ft equal 13.5 ft.  
From Table 11, read with 8-in. duct diam, P is equal to  
0.16 in. wg for each 10 ft. of flex duct. Therefore, for  
13.5 ft, P is equal to 0.16 + 0.06 in. wg. The total P  
downstream of run-out duct is equal to 0.75 + 0.22  
= 0.97 in. wg.  
in air series to connect Modulineunits. In calculating pres-  
sure requirements for units in air series, use the following  
guidelines:  
1. For close-coupled units (either continuous diffuser or units  
in adjoining ceiling modules) where the flexible duct used  
is 6 to 8 in. in length, add 0.1 in. wg to unit requirement  
for minimum static pressure at control unit (Table 10).  
3. Flexible duct, unsupported, tends to sag; this deflection  
increases the pressure drop. Whenever possible, support  
the duct with wire between connections. Sagging will in-  
crease the P as much as 0.06 in. wg in a 10-ft length;  
therefore rigid duct is recommended for lengths greater  
than 5.5 ft.  
4. The use of flexible duct in air series run-out when 90 de-  
gree turns are required will also add P. Table 12 pro-  
vides the additional pressure drop.  
For example, consider three 37HS2 units in air series, in  
adjoining modules, with 200 cfm per unit (Fig. 23). The  
minimum static pressure for multiple units is equal to 0.75  
in. wg (from Table 10). Adding 0.1 in. wg for flexible  
duct, the total pressure downstream of run-out duct equals  
0.85 in. wg.  
2. For units in air series with extended flexible duct lengths,  
add P from Table 11.  
For example, refer to Fig. 25. The ‘‘straight’’ line P is  
equal to 0.97 in. wg. If a bend is added to the run-out, the  
total pressure drop becomes:  
For example, consider four 37HS2 units in air series,  
200 cfm per unit (Fig. 24). The units are in alternate  
series modules; 8-in. duct; 9- x 9-in. plenum. The  
0.97 + 0.16 = 1.13 in. wg.  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 10 — Minimum Static Pressure at Control  
(Master) Unit — Units with System-Powered  
Controls and Standard Diffusers  
Table 11 — Additional P for  
Extended Lengths of Flexible Duct  
FLEX  
DUCT  
DIAM  
(in.)  
TOTAL  
CFM  
ADDITIONAL  
P PER  
10 FT FLEX DUCT  
(in. wg)  
37HS1  
37HS2  
37HS4  
IN AIR  
SERIES  
PLENUM SIZE (in.)  
AIRFLOW  
(Cfm)  
7 x 7  
9 x 9  
11 x 11  
7 x 7  
9 x 9  
9 x 9  
6
8
400  
800  
0.2  
5 x 7  
11 x 11  
13 x 13  
0.16  
0.1  
11 x 11  
10  
12  
1100  
1600  
Minimum Static Pressure (in. wg)  
0.07  
40  
50  
60  
70  
0.75  
0.75  
0.75  
N/A  
N/A  
N/A  
80  
90  
100  
0.75  
0.75  
110  
0.90  
N/A  
0.90  
N/A  
0.75  
0.75  
N/A  
N/A  
Table 12 — Additional P for  
Flexible Duct with 90-Degree Bend  
120  
140  
160  
180  
200  
FLEX  
DUCT  
DIAM  
(in.)  
TOTAL  
CFM  
IN AIR  
SERIES  
RADIUS  
OF  
BEND  
(in.)  
ADDITIONAL P  
FOR 90° BEND  
IN FLEXIBLE DUCT  
(in. wg)  
N/A  
N/A  
N/A  
N/A  
0.75  
0.90  
0.75  
0.75  
220  
6
8
400  
800  
18  
24  
30  
36  
0.26  
0.16  
0.08  
0.04  
240  
280  
320  
360  
400  
N/A  
N/A  
N/A  
N/A  
N/A  
N/A  
0.75  
0.90  
10  
12  
1100  
1600  
440  
N/A — Not Applicable  
NOTE: Maximum inlet pressure — 3.0 in. wg.  
C — Controller  
Fig. 23 — Three 37HS2 ModulineUnits in Adjoining Modules  
Fig. 24 — Four 37HS2 Moduline Units in Alternate Series Modules  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 25 — Flexible Duct Used with 90-Degree Bend  
GUIDELINES FOR CONTROLLER LOCATION  
Step 4 — Determine Controller Location — The  
final step in the terminal selection and layout process is to  
decide where the controllers will be placed.  
1. A master unit is mounted in the ceiling so that the air  
intake is on the end of the unit opposite the end with the  
control block and controller. (Fig. 26.)  
2. A slave unit can receive air from either end of the unit.  
Either end can be the inlet, assuming the inlet collar is  
the same size as the connecting unit. At the same time, it  
is good practice to place the ‘‘control’’ end of a slave unit  
downstream as shown in Fig. 26. Should the slave unit be  
later converted to a master unit, the unit would be in its  
correct configuration for control installation.  
The temperature control zones in the building will be de-  
termined by the final partition layout. Before the final par-  
tition layout has been determined, you must install enough  
controllers to meet job requirement; the controllers can then  
be relocated when the tenant layout is finished.  
One of the main features of Moduline controls is that con-  
troller locations can be changed quickly and easily at any  
time.  
3. The volume controller for a single unit should be located  
on the end of the unit opposite the inlet end. (Fig. 27.)  
Another main feature of Moduline controls is that more  
than one unit can be controlled from a single thermostat. In  
large interior zones the ‘‘master’’ unit (the one with the ther-  
mostat) can be hooked up with control tubing to control sev-  
eral ‘‘slaves’’. Table 13 shows the maximum number of units  
that can be controlled by one controller.  
Table 13 — Maximum Number of Units in an  
Air Series on One Controller  
PLENUM  
SIZE (in.)  
NUMBER OF UNITS ON ONE CONTROLLER  
MODEL FIRST UNIT  
IN AIR  
Units in Air Series  
Single  
Unit  
2
3
4
5
SERIES*  
5 x 7†  
X
X
X
X
X
X
X
X
X
X
X
X
X
X
7 x 7  
37HS1  
9 x 9  
X
X
X
11 x 11  
7 x 7  
X
X
X
X
X
X
X
37HS2  
37HS4  
9 x 9  
11 x 11  
9 x 9  
X
X
X
X
X
X
11 x 11  
13 x 13  
X
X
X
*See Tables 6-8 for recommended combinations of units in air series.  
†The 37HS1 unit with 5 x 7 size plenum is available with blank end only; mul-  
tiple units of this size would not be used on one control.  
Fig. 26 — Air Intake on Master Unit  
NOTE: The conditions stated in Table 9 must be included in evaluations for  
selecting the number of units in an air series.  
37  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4. The controller for units in an air series should be located  
as shown in Fig. 28.  
5. Volume controllers for units in an air series must be con-  
nected from master to slave units in the same air series;  
they must not be connected to units in a different air  
series from that of the master unit. See examples shown  
in Fig. 29 and 30.  
C — Controller  
6. To connect slave units with control tubing, use the end  
bellows fittings only; do not attempt to use the 0.25 molded  
connection on the filter. See Fig. 31 for examples of con-  
trol tubing connections.  
Fig. 27 — Location of Volume Controller  
on Single Unit  
C — Controller  
Fig. 28 — Location of Volume Controller on Units in an Air Series  
38  
Download from Www.Somanuals.com. All Manuals Search And Download.  
EXAMPLES OF GUIDELINE USE — Figure 29 shows an incorrect application. Figure 30 shows the corrected layout.  
An incorrect application:  
1. Room A & B units are on the same controller but on different duct  
air series.  
2. Room B calls for half the cfm as in units in room A — not feasible  
because there is only one controller.  
3. Units in room C are on different duct runs with one control — not  
correct.  
4. Units in room D are fine for one control, but controller should be  
on second unit in air series.  
Fig. 29 — Incorrect Layout of ModulineUnits with Controls  
39  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The corrected layout:  
1. Room A has its own controller.  
2. Room B has its own controller.  
3. Room C has a correct air series for one control.  
4. Room D has the controller in the proper location.  
Fig. 30 — Corrected Layout  
Fig. 31 — Control Tubing Connection  
40  
Download from Www.Somanuals.com. All Manuals Search And Download.  
• the control tube layout for connecting the master unit (with  
thermostat) to all its slaves  
Final Layout — After these 4 steps are complete, you  
are ready to make a final layout.  
• the cfm for the master unit (all slaves will be the same cfm  
and need not be indicated)  
The final layout should show not only the number and lo-  
cation of the Moduline units, but also:  
• the model number of the unit to be used  
• the round duct size connected to the unit  
• the controller location  
THE MODULINEVALVE  
Figure 32 shows the Moduline terminal in cross section  
with the valve in three positions — shutoff, partially open  
and fully open. The valve opening varies with the pressure  
of the bellows and the pressure of the plenum.  
Figure 33 shows the internal components of the Moduline  
unit.  
Figure 34 shows the comparison of operating character-  
istics between Carrier’s new Moduline unit (the 37HS) and  
the previous design.  
The Moduline Control Concept — The 37HS Modu-  
line system-powered control concept is based on using the  
building’s primary air supply as a source of energy. The dis-  
tribution duct pressure provides energy to operate the con-  
trols that modulate the flow of air through the unit. The heart  
of this system is a bellows-operated unit air valve, which is  
positioned by varying the pressure of the air in the bellows  
relative to the supply air pressure in the duct. As the pres-  
sure in the bellows approaches the pressure in the supply  
duct, the unit air valve opening is reduced, finally closing  
completely when the pressures are equal.  
41  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT SHUTOFF — BELLOWS FULLY INFLATED  
UNIT MODULATING — BELLOWS PARTIALLY INFLATED  
UNIT FULL CAPACITY — BELLOWS DEFLATED  
Fig. 32 — Bellows and Unit Air Valve Arrangement  
42  
Download from Www.Somanuals.com. All Manuals Search And Download.  
HIGH AND LOW PRESSURE — As primary air flows from  
the unit plenum to the unit air valve and from there to the  
conditioned space, it passes through a slotted plate called  
the distribution baffle. The resistance of the baffle tends to  
‘‘even out’’ the airflow through the unit. The baffle also cre-  
ates a pressure differential which forms the basis of the sens-  
ing side of the unit control.  
Static pressure from above the baffle is called the high  
pressure; static pressure below the baffle is the low pressure.  
Figure 35 shows the pick-up tubes for the high and low pres-  
sures, the differential pressure across the distribution baffle.  
Fig. 33 — Cross Section of 37HS Moduline  
Air Terminal  
Fig. 34 — Bellows Comparison  
43  
Download from Www.Somanuals.com. All Manuals Search And Download.  
delivers maximum flow, as determined by the existing ple-  
num pressure. Units normally operate between these ex-  
tremes. In constant volume applications, the bellows pres-  
sure is automatically adjusted in proportion to the plenum  
pressure, providing a constant pre-set flow within the oper-  
ating limits of the unit. In variable air volume op-  
eration, the bellows pressure is further modulated to reduce  
flow below the preset level as load requirements are satis-  
fied. After passing through the valve, the primary air flows  
down through the diffuser and out to the conditioned space.  
CONTROL APPLICATIONS  
Introduction — The Modulineterminal is offered with  
a variety of cooling and heating control options which adapt  
to many building applications. In this section, the various  
control applications are described and the functions they in-  
clude are identified. Each application has a function number  
which corresponds to the function number shown in  
Tables 14 and 15 in the Control Selection section, page 50.  
Table 14 describes the functions; Table 15 shows the control  
packages required for each function. The part numbers shown  
are found on the Moduline air terminal price pages.  
Detailed operating sequences for each control application  
are found beginning on page 55.  
System-Powered Controls  
COMPONENTS OF THE SYSTEM-POWERED CON-  
TROL SYSTEM — The 37HS system-powered control con-  
sists of a set of custom design and manufacturer’s compo-  
nents which provide airflow and temperature regulation of a  
Moduline air terminal. These devices are interchangeable,  
field-installed components which plug into the Moduline unit  
without the use of tools.  
Figure 36 shows the basic components: Control block (part  
of the unit); filter/manifold; volume controller; and thermo-  
stat. Figure 37 demonstrates the control air paths in a sec-  
tional view of the control system. Note that the high pres-  
sure and low pressure pick-ups of the unit are connected through  
the control block to the filter and from there to the volume  
controller and thermostat.  
Fig. 35 — High and Low Pressure Pick-Up Tubes  
BELLOWS PRESSURE — As the airflow through the unit  
changes, the high and low pressures vary proportionately.  
Comparing these 2 pressures, the unit volume controller pro-  
vides a bellows pressure which in turn inflates the unit air  
valve. Bellows pressure varies from near zero at full flow to  
plenum or duct pressure at shutoff.  
UNIT AIRFLOW DELIVERY — The relationship between  
the bellows pressure and the plenum pressure determines the  
unit air valve position, which controls unit airflow delivery.  
When the pressures become nearly equal, the valve closes  
and the unit shuts off. Conversely, as the bellows pressure  
approaches zero, the valve opens completely and the unit  
Figure 38 shows the control filter/manifold; Fig. 39, the  
airflow volume controller; Fig. 40, the diffuser thermostat  
with aspirator; and Fig. 41, the wall thermostat and alternate  
to diffuser mounting.  
44  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 36 — 37HS Control Components  
Fig. 37 — Basic 37HS Control Operation  
45  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Both CV and VAV control packages include a plastic baffle  
which is installed over the vertical leg of the center diffuser  
and blocks the unused portion of the diffuser slots. See  
Fig. 42. On VAV units, this prevents stray air currents from  
influencing thermostat operation.  
Other control components used in extended system-  
powered electric and pneumatic control schemes are de-  
scribed in the control applications which follow.  
50  
70  
90  
Fig. 41 — Wall-Mounted Thermostat  
Fig. 38 — 37HS Control Filter/Manifold  
S
O
CFM  
120  
Fig. 39 — 37HS Airflow Volume Controller  
Fig. 42 — Diffuser Baffle Assembly  
Fig. 40 — Unit-Mounted (Diffuser) Thermostat  
46  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEM-POWERED APPLICATIONS  
VAV Cooling With Warm-Up — (Function 4.) During an ex-  
tended off period (overnight or during a holiday), the space  
temperature will often be lowered. It is necessary to provide  
heated air, temporarily, to reestablish comfortable tempera-  
tures when occupancy resumes. Since the cooling thermo-  
stats are satisfied at the reduced temperature, the units will  
be shut off and the system will not be able to deliver warm  
air. It is necessary, therefore, to provide a means of tempo-  
rarily overriding the cooling thermostat. System-powered  
warm-up is achieved by adding a warm-up switch to the VAV  
cooling control arrangement (Fig. 45). The warm-up switch,  
located inside the unit plenum, closes when it senses that  
warm air is being supplied to the unit. This causes the bel-  
lows to bleed, opening the unit. This condition is maintained  
until cool air is returned to the system and the warm-up switch,  
sensing cool supply air, returns control to the thermostat.  
Where all Moduline units on a main duct-run are pro-  
vided with thermostats for variable air volume control, it is  
often difficult to get warm air to the end units on a run; with  
the units in shutoff there is no significant flow which will  
trigger the warm-up switch. Solutions to this situation are  
found on page 58 in the Control Operating Sequences, VAV  
Cooling with Warm-Up section.  
Constant Volume (CV) Cooling — (Function No. 1.) This is  
the most basic operating configuration. The control arrange-  
ment consists of the volume controller and the filter. The unit  
maintains a steady flow of primary air at the quantity set on  
the volume controller over a range of supply pressures. Fig-  
ure 43 shows constant volume controls mounted on the Modu-  
lineunit.  
CV Heating (Function No. 1.) Constant volume heating con-  
trols are the same as for CV cooling.  
Variable Air Volume (VAV) Cooling — (Function No. 2 and  
3.) The addition of a cooling thermostat to the constant vol-  
ume controls allows the unit to vary the flow of primary air.  
The unit will provide just enough airflow to satisfy the ther-  
mostat setting at existing load conditions, up to the maxi-  
mum flow set on the volume controller. The cooling thermo-  
stat is direct acting (DA); thus the branch pressure output  
from the thermostat increases as the space temperature in-  
creases. Both diffuser-mounted and wall-mounted variations  
are available. Figure 44 shows the system-powered VAV con-  
trols (with diffuser thermostat) mounted on the unit.  
Fig. 43 — Constant Volume Control  
Arrangement  
Fig. 45 — VAV Control Arrangement for  
System-Powered Warm-Up  
Fig. 44 — Variable Air Volume Control  
Arrangement  
47  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SYSTEM-POWERED CONTROLS WITH ELECTRIC  
INTERFACE  
VAV Heating and Cooling With Changeover — (Function  
5.) A VAV control arrangement for cooling/heating includes  
a wall-mounted cooling/heating thermostat and provision to  
change the thermostat from cooling to heating configuration  
and back again. Figure 46 shows the control arrangement  
with Modulinecontrol for heating and cooling. The wall  
thermostat is shown in Fig. 47. The system-powered heating  
and cooling changeover uses an assembly consisting of 2  
temperature-operated pneumatic switches located inside the  
unit plenum and installed in-line between a cooling/heating  
thermostat and the volume controller. These switches se-  
quence the thermostat between the cooling and heating modes,  
depending upon the temperature of the primary air supply.  
VAV Cooling With Electric Warm-Up — (Function 6.) Elec-  
tric warm-up uses an electric changeover valve to perform  
the same function as system-powered warm-up; that is, to  
provide heated air to reestablish comfortable temperatures  
when occupancy resumes after an extended unoccupied pe-  
riod. Since the cooling thermostats are satisfied at the re-  
duced temperature, the units will be shut off and the system  
will not be able to deliver warm air. It is necessary, there-  
fore, to provide a means of temporarily overriding the cool-  
ing thermostat.  
The changeover control is an electrically operated, re-  
motely controlled 3-way solenoid valve. The normally closed  
port of the valve is capped. The valve usually is wired to  
activate automatically with the supplemental heating switch;  
however, it can also be manually activated. This option may  
be used with either a unit-mounted or wall-mounted ther-  
mostat. See Fig. 49.  
VAV Heating — (Function 9.) Variable air volume heating  
controls are the same as for VAV cooling except that only a  
wall-mounted heating thermostat is offered (Fig. 48). The  
heating thermostat is reverse acting (RA); thus the output  
pressure decreases as the space temperature increases.  
VAV Heating and Cooling With Electric Changeover — (Func-  
tion 7.) A VAV control arrangement for cooling/heating in-  
cludes a wall-mounted cooling/heating thermostat (Fig. 47)  
and provision to change the thermostat from a cooling to  
heating configuration and back again. System-powered cooling/  
heating with electric changeover uses a 3-way electric so-  
lenoid valve to switch control between the cooling and heat-  
ing functions of a cooling/heating wall-mounted thermostat.  
It is installed in-line between the volume controller of a CV  
cooling control package and the thermostat. The valve may  
be activated separately or interlocked with an electric heat-  
ing system. See Fig. 50.  
Fig. 46 — System-Powered Changeover  
Switch Arrangement with Heating/Cooling  
Wall Thermostat  
90  
70  
50  
Fig. 49 — VAV Control Arrangement  
for Electric Warm-Up  
50  
70  
90  
Fig. 47 — Cooling/Heating Wall Thermostat  
50  
70  
90  
90  
70  
50  
Fig. 50 — VAV Control Arrangement  
for Electric Changeover  
Fig. 48 — Wall-Mounted Heating Thermostat  
48  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VAV Cooling With Electric Heat Interlock — (Function 8.)  
In cases where VAV cooling terminals are used in conjunc-  
tion with a separate heating system, such as perimeter heat-  
ing, it is necessary to prevent the heating equipment from  
turning on before the cooling system turns off. The addition  
of a differential pressure switch to the unit controls makes  
this possible. When the switch detects that control pressures  
are approaching a shutoff condition (cooling load satisfied),  
it closes a set of contacts. This allows the heating system to  
operate as the heating thermostat dictates. See Fig. 51.  
VAV Cooling With Fire Safety — (Functions 11 and 12.) Code  
requirements may specify that air distribution terminals be  
open or closed during a fire. For example, in tower construc-  
tion there may be a requirement that if a fire begins on one  
floor the terminals on the ‘‘fire floor’’ must be shut off to  
prevent the addition of oxygen to the fire; terminals on the  
floors above and below the fire floor must be wide open to  
ventilate the space. These actions must occur regardless of  
the space temperature and the position of the individual duct-  
powered thermostats (unit mounted or wall mounted). This  
application is effectively the same as the pneumatic warm-up  
previously described. In this case, the pneumatic switch is  
remotely operated by the fire master control to open the ad-  
jacent floor units. Air supply to units on the ‘‘fire floor’’ is  
interrupted by the use of duct fire-dampers.  
Fig. 51 — VAV Control Arrangement with  
Electric Heat Interlock  
50  
70  
90  
SYSTEM-POWERED CONTROLS WITH PNEUMATIC IN-  
TERFACE — The Moduline unit is designed as a stand-  
alone, reactive air terminal in which the only source of en-  
ergy for control purposes is the distribution air itself. There  
are applications where separate system energy affords ad-  
ditional control functions not possible with system power.  
This section covers the use of 20 psi pneumatic energy and  
standard and custom pneumatic devices for the application  
of Moduline terminals in a conditioning system.  
Fig. 52 — Pilot Valve for Pneumatic Sequenced  
Cooling/Heating (Hot Water)  
Pneumatic Sequenced Cooling/Heating (Hot Water) — (Func-  
tion 10.) A 37HS VAV cooling system can be sequenced with  
a hot water heating system through the use of a pilot valve  
and a single proportional pneumatic thermostat (one-pipe or  
2-pipe). See Fig. 52. By properly matching the operating pres-  
sure ranges of the pilot valve and the field-supplied hot wa-  
ter heat valve, the system can be configured to automatically  
change over from cooling to heating and back again based  
on the thermostat branch line pressure. The cooling and heat-  
ing functions can be separated by a deadband or they can be  
overlapped, depending upon pressure ranges selected. The  
system may be designed to use either of the following  
combinations:  
• pilot valve (NO), hot water valve (NO) and thermostat (DA,  
one- or 2-pipe)  
• pilot valve (NC), hot water valve (NC), and thermostat (RA,  
one- or 2-pipe)  
Fig. 53 — VAV Control Arrangement with  
Pneumatic Warm-Up Switch  
VAV Cooling With Pneumatic Warm-Up — (Functions 11  
and 12.) Pneumatic warm-up is accomplished by using a re-  
motely operated pneumatic switch in place of the system-  
powered warm-up switch. The pneumatic switch is installed  
in-line between the volume controller and the thermostat (unit  
mounted or wall mounted) and must be closed during  
warm-up. It may be either normally open or normally closed,  
but must match the pneumatic line pressure available. See  
Fig. 53.  
49  
Download from Www.Somanuals.com. All Manuals Search And Download.  
NOTE: The following applications require the control pack-  
ages shown for Function 10, plus field-supplied thermostats  
as described below.  
Control Packages — In order to obtain a desired set  
of control functions with Moduline air terminals, the correct  
combination of control packages is required. Table 15 shows  
the control packages that must be installed on a master unit  
in order to achieve each function. The control package num-  
bers correspond to the numbers on the 37HS Price Pages.  
Night Set Back Heating — In the interest of energy conser-  
vation, it may be desirable to raise a system’s cooling set  
point during unoccupied time periods, whether they occur at  
night or on weekends, holidays or other occasions. This ap-  
plication requires a field-supplied dual set point DA pneu-  
matic thermostat operating on a switched-main pressure supply.  
The air supply must have 2 pressure levels available. A nor-  
mally open pilot valve, controlled by the dual thermostat, is  
also required. The thermostat set point is determined by the  
supply pressure selected.  
VAV Cooling/Separate System Heating AModulinecool-  
ing system may be interlocked with a separate hot water heat-  
ing system and controlled by a common thermostat. This ap-  
plication requires a field-supplied switched-main pressure  
supply, a field-supplied dual set point DA/RA pneumatic ther-  
mostat, a pneumatic switching relay, a pilot valve, and a pneu-  
matic hot water valve. The summer mode (cooling) or the  
winter mode (heating) is selected by switching the pneu-  
matic supply system pressure between high or low pressure  
ranges. The pneumatic thermostat operates in either the cool-  
ing mode (DA) or the heating mode (RA) depending on the  
supply pressure provided. The pneumatic switching relay re-  
sponds to the pressure level by selecting either the pilot valve  
and the Moduline cooling system or the hot water valve and  
the hot water heating system, to match the thermostat mode.  
Table 14 — Control Index  
FUNCTION  
FUNCTION DESCRIPTION  
NO.  
1
2
3
Cooling or Heating Only, Constant Volume  
Cooling Only, Variable Volume, Diffuser Thermostat  
Cooling Only, Variable Volume, Wall Thermostat  
VAV Cooling with System-Powered Warm-Up,  
Wall Thermostat  
4
5
6
7
VAV Cooling/Heating, System-Powered Changeover,  
Wall Thermostat  
VAV Cooling with Electric Warm-Up, Wall Thermostat  
or Diffuser Thermostat  
VAV Cooling/Heating, Electric Changeover,  
Wall Thermostat or Diffuser Thermostat  
8
9
VAV Cooling with Electric Heat Interlock  
Heating Only, Variable Volume, Wall Thermostat  
VAV Cooling with Pneumatic Sequenced Heating (Hot Water)  
and Pneumatic Thermostat*  
10  
11  
12  
VAV Cooling with Pneumatic Warm-Up or Fire Safety Switch,  
Wall Thermostat  
VAV Cooling with Pneumatic Warm-Up or Fire Safety Switch,  
Diffuser Thermostat  
*For night set back heating, a field-supplied dual set point DA thermostat must  
be used with the control packages and components shown in Table 15. For  
VAV cooling/separate system heating, a field-supplied dual set point DA/RA  
thermostat must be used with the control packages and components shown  
in Table 15.  
CONTROL SELECTION  
Control Index — Table 14 summarizes the control func-  
tions available with 37HS Moduline air terminals. These func-  
tions are described in detail in the preceding Control Appli-  
cations section.  
50  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 — 37HS Control Combinations  
CONTROL  
PACKAGES  
REQUIRED  
NO.  
FUNCTION  
MODEL  
CONNECTION ARRANGEMENT  
SYSTEM POWERED  
37HS1  
37HS2  
37HS4  
37HS900003  
37HS900003  
37HS900003  
CONSTANT VOLUME  
COOLING  
1
SYSTEM POWERED  
37HS1  
37HS2  
37HS4  
37HS900001  
37HS900002  
37HS900004  
VARIABLE VOLUME  
COOLING  
DIFFUSER  
THERMOSTAT  
2
SYSTEM POWERED  
37HS900003  
37CM901012  
37HS1  
37HS2  
37HS4  
VARIABLE VOLUME  
COOLING  
37HS900003  
37CM901012  
WALL THERMOSTAT  
37HS900003  
37CM901012  
3
51  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 — 37HS Control Combinations (cont)  
CONTROL  
PACKAGES  
REQUIRED  
NO.  
FUNCTION  
MODEL  
CONNECTION ARRANGEMENT  
SYSTEM POWERED  
37HS900003  
37CM900152  
37CM901012  
37HS1  
37HS2  
37HS4  
VARIABLE VOLUME  
COOLING  
37HS900003  
37CM900152  
37CM901012  
SYSTEM POWERED  
WARM-UP  
WALL THERMOSTAT*  
37HS900003  
37CM900152  
37CM901012  
4
SYSTEM POWERED  
37HS900003  
37CM900192  
37CM900992  
37HS1  
37HS2  
37HS4  
VARIABLE VOLUME  
HEATING & COOLING  
37HS900003  
37CM900192  
37CM900992  
SYSTEM POWERED  
CHANGEOVER  
WALL THERMOSTAT  
37HS900003  
37CM900192  
37CM900992  
5
SYSTEM POWERED  
37HS900003  
37CM900792†  
37CM901012  
37HS1  
37HS2  
37HS4  
VARIABLE VOLUME  
COOLING  
37HS900003  
37CM900792†  
37CM901012  
ELECTRIC WARM-UP  
WALL THERMOSTAT*  
37HS900003  
37CM900792†  
37CM901012  
6
*To use a diffuser thermostat in place of the wall thermostat, replace constant volume package 37HS900003 and wall thermostat 37CM901012  
with variable volume package 37HS900001 (37HS1), 37HS900002 (37HS2) or 37HS900004 (37HS4).  
†Package 37CM900792 is 24 v; other voltages available.  
52  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 — 37HS Control Combinations (cont)  
CONTROL  
NO.  
FUNCTION  
MODEL  
37HS1  
37HS2  
37HS4  
PACKAGES  
REQUIRED  
CONNECTION ARRANGEMENT  
SYSTEM POWERED  
37HS900003  
37CM900792†  
37CM900992  
VARIABLE VOLUME  
HEATING & COOLING  
37HS900003  
37CM900792†  
37CM900992  
ELECTRIC CHANGEOVER  
WALL THERMOSTAT  
37HS900003  
37CM900792†  
37CM900992  
7
SYSTEM POWERED  
37HS900001  
37CM900922  
37HS1  
37HS2  
37HS4  
VARIABLE VOLUME  
COOLING  
37HS900002  
37CM900922  
DIFFUSER THERMOSTAT**  
37HS900004  
37CM900922  
ELECTRIC  
INTERLOCK TO FAN COIL  
OR BASEBOARD HEATING  
8
SYSTEM POWERED  
37HS900003  
37CM901002  
37HS1  
37HS2  
37HS4  
VARIABLE VOLUME  
HEATING  
37HS900003  
37CM901002  
WALL THERMOSTAT  
37HS900003  
37CM901002  
9
†Package 37CM900792 is 24 v; other voltages available.  
**To use a wall thermostat in place of the diffuser thermostat, replace variable volume packages 37HS900001 (37HS1), 37HS900002 (37HS2) or  
37HS900004 (37HS4) with constant volume package 37HS900003 and add wall thermostat 37CM901012.  
53  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 15 — 37HS Control Combinations (cont)  
CONTROL  
PACKAGES  
REQUIRED  
NO.  
FUNCTION  
MODEL  
CONNECTION ARRANGEMENT  
SYSTEM POWERED  
37HS900003  
37CM900972 (NO)  
with  
VARIABLE VOLUME  
COOLING  
37HS1  
37HS2  
37HS4  
37HS900007 (DA)  
PNEUMATIC  
PILOT VALVE FOR  
HEATING/COOLING  
SEQUENCE  
37CM900982 (NC)  
with  
37HS900008 (RA)  
37HS900003  
PNEUMATIC  
WALL  
THERMOSTAT††  
37CM900972 (NO)  
with  
37HS900007 (DA)  
10  
37CM900982 (NC)  
with  
37HS900008 (RA)  
37HS900003  
37CM900972 (NO)  
with  
37HS900007 (DA)  
37CM900982 (NC)  
with  
37HS900008 (RA)  
SYSTEM POWERED  
37HS900003  
37CM901012  
37HS900017  
37HS1  
37HS2  
37HS4  
VARIABLE VOLUME  
COOLING  
37HS900003  
37CM901012  
37HS900017  
WALL THERMOSTAT  
PNEUMATIC  
WARM-UP/FIRE  
SWITCH  
37HS900003  
37CM901012  
37HS900017  
11  
SYSTEM POWERED  
37HS900001  
37HS900017  
37HS1  
37HS2  
37HS4  
VARIABLE VOLUME  
COOLING  
37HS900002  
37HS900017  
DIFFUSER  
THERMOSTAT  
37HS900004  
37HS900017  
PNEUMATIC  
WARM-UP/FIRE  
SWITCH  
12  
††For night set back heating, a field-supplied dual set point DA ther-  
mostat must be substituted for thermostat packages shown. For  
VAV Modulinecooling/separate system heating, a field-supplied  
dual set point DA/RA thermostat must be substituted for thermo-  
stat packages shown.  
LEGEND  
Direct Acting  
Normally Closed  
DA  
NC  
NO  
RA  
Normally Open  
Reverse Acting  
54  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The control valve is positioned by 2 diaphragms, one in  
the low pressure chamber and one in the high pressure cham-  
ber, and an adjustable spring. Pressure above the low pres-  
sure diaphragm tends to open the control valve while the  
high pressure diaphragm tends to hold it closed. The spring  
tension balances these forces as the pressures vary and de-  
termines the valve position. Rotating the adjusting dial on  
the volume controller changes the spring tension and pro-  
vides a means of establishing a flow set point.  
CONTROL OPERATING SEQUENCES  
System-Powered Controls  
CV COOLING — See Fig. 54. Air from above the distri-  
bution baffle (high pressure) enters the filter through the up-  
per port of the control block, while the lower port receives  
air from below the baffle (low pressure). These air streams  
pass through separate filter chambers where particulate con-  
taminants are removed.  
The bellows pressure determined by the action of the con-  
trol valve is communicated to the bellows. As the plenum  
pressure changes, the control bellows valve is constantly re-  
set to maintain a corresponding bellows pressure. The bel-  
lows pressure chamber of the volume controller feeds air back  
through the middle port and chamber of the filter (also called  
a bellows pressure chamber), to the bellows connection on  
the unit end panel, and into the bellows. The bellows pres-  
sure re-sets the bellows on the unit air valve to provide a  
constant airflow through the unit at the value selected on the  
volume controller dial.  
The low pressure air stream enters the low pressure cham-  
ber of the volume controller from the top port of the filter,  
while the bottom port of the filter feeds the high pressure  
stream into the controller’s high pressure chamber.  
Air from the high pressure chamber feeds into the bellows  
pressure chamber of the controller through the fixed orifice.  
Pressure in the bellows chamber of the volume controller is  
determined by the relationship between the entering flow re-  
sistance of the fixed orifice and the leaving flow resistance  
of the control valve variable orifice.  
As the control valve opens, its resistance decreases and  
relatively more air is allowed to bleed, lowering the pressure  
in the bellows chamber. As the control valve closes, the ef-  
fect is reversed, increasing the bellows pressure. This is the  
principle of control by matched orifices.  
CV HEATING — Control arrangements and operation are  
the same for CV heating as for CV cooling. The controls and  
their operation are not affected by the temperature of the sup-  
ply air.  
Fig. 54 — Constant Volume Controls — Controller Bleeding, Unit Supplying Air  
55  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VAV COOLING — In VAV operation, the filter and volume  
controller perform the same functions as in CV operation.  
The unit-mounted thermostat modifies control operation as  
described below.  
raising the pressure in the low pressure chamber of the con-  
troller. As the low pressure rises, it gradually overcomes  
the high pressure and opens the bellows pressure-chamber  
bleed valve, lowering the bellows pressure proportionally.  
This allows the unit damper to open and gradually increase  
the flow of conditioned primary air into the space. See  
Fig. 56.  
This process continues until the flow of primary air is suf-  
ficient to offset the load, or until the flow level set point of  
the volume controller is reached (Fig. 57). At this point, the  
thermostat bleed is closed and the unit is actually operating  
in CV configuration. As the load is reduced, the process is  
reversed and the unit flow decreases proportionally until the  
unit is shut off when the thermostat is satisfied (bleed fully  
open) (Fig. 58). In this manner, the unit normally delivers  
only the actual amount of primary air needed to offset the  
existing load.  
Refer to Fig. 55. The air enters the low pressure chamber  
of the volume controller through a fixed orifice. The low pres-  
sure chamber is connected through a stub fitting and tube to  
the unit-mounted thermostat. The thermostat senses room tem-  
perature, closes its port as the temperature rises, and opens  
it as the temperature falls. This makes it possible to control  
the pressure in the low pressure chamber in response to the  
space temperature. With normal space temperatures, and the  
thermostat satisfied, the low pressure chamber valve is open  
to the atmosphere through the thermostat. The rate at which  
the valve bleeds air from the low pressure chamber is high  
in relation to the rate at which air enters through the orifice,  
and the pressure decreases in relation to the high pressure.  
The high pressure force is stronger than the low pressure  
force and the bleed valve of the bellows pressure chamber of  
the controller is held closed. Since no air escapes, the bel-  
lows pressure becomes equal to the high pressure in the ple-  
num and the unit damper is closed, shutting off the unit.  
When the wall-mounted DA thermostat is used in place of  
the unit-mounted thermostat, variable air volume control op-  
eration is the same as described above for the unit-mounted  
thermostat. The only difference is that the wall-mounted ther-  
mostat does not include the aspiration feature.  
As the room load increases, the space temperature in-  
creases. The thermostat senses this change and starts to close,  
Fig. 55 — Variable Volume Controls Schematic  
56  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 56 — Variable Volume Controls — Minimum Flow: Thermostat Partially Open,  
Controller Partially Open, Unit Delivering Minimum Flow  
Fig. 57 — Variable Volume Controls — Full Cooling, Thermostat Closed, Controller Bleeding,  
Unit Supplying Air  
57  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 58 — Variable Volume Controls — Thermostat Open,  
Controller Shut Off, Unit Shut Off  
VAV COOLING WITH WARM-UP — Including the warm-  
condition will continue as long as air in the duct system re-  
mains at a temperature higher than approximately 80 F. As  
the supply air returns to normal cooling temperatures, the  
switch opens and control is returned to the cooling thermo-  
stat. See Fig. 60.  
fup switch in the volume controller/thermostat circuit al-  
lows the unit to deliver air when there is warm air in the duct  
system, even though the cooling thermostat is satisfied by  
cool space temperature.  
The warm-up switch is actually a temperature controlled  
pneumatic valve which is normally open at primary air sup-  
ply temperatures below approximately 64 F. It is installed  
in-line between the volume controller and the thermostat.  
When warm primary air is supplied to restore comfort con-  
ditions in the space after an extended shutdown, the warm-up  
switch reacts by closing (Fig. 59). This removes the ther-  
mostat from the control circuit and prevents air from bleed-  
ing from the low pressure chamber of the volume controller.  
This condition simulates a thermostat calling for maximum  
primary-air delivery. The unit is now, in effect, a CV unit  
and operates at the set point of the volume controller. This  
Because the units are shut off, it may be difficult to es-  
tablish the flow of warm air to initiate warm-up. One method  
of overcoming this problem is to install one or more CV units  
near the end of the duct run. Where possible, a constant vol-  
ume unit is located in space not continuously occupied such  
as halls, aisles, or storage rooms. It can also be helpful in an  
area benefiting from continuous circulation. By locating such  
a unit at the end of a duct run, the heated air for morning  
warm-up is assured of reaching the VAV units. See Fig. 61.  
58  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 59 — Cooling with Warm-Up — Morning, Hot Air in Duct, Warm-Up Switch Closed,  
Controller Bleeding, Unit Heating  
Fig. 60 — Cooling with Warm-Up — Nighttime Condition, Room Cool, Thermostat Open,  
Bleeding, Warm-Up Open, Controller Shut Off, Unit Shut Off  
59  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 61 — Location of CV Unit for Warm-Up Application  
VAV HEATING AND COOLING WITH SYSTEM-  
making control air available to each valve. The valve for the  
DA cooling thermostat is normally open as long as there is  
cool supply air in the plenum (Fig. 62). The other valve is  
normally open when warm air is being supplied, matching  
the RA heating thermostat (Fig. 63). Each valve is con-  
nected to the corresponding thermostat by a separate tube.  
In the cooling mode (Fig. 64), the cooling valve is open,  
activating the cooling thermostat, while the heating thermo-  
stat is isolated by the closed heating valve. On changeover  
from cooling to heating, the cooling valve closes and the  
heating valve opens, shifting control to the heating thermo-  
stat (Fig. 65).  
POWERED CHANGEOVER — This application uses a CV  
control package along with a wall-mounted thermostat pack-  
age (cooling/heating) and a system-powered changeover con-  
trol package. The cooling thermostat is direct acting (DA)  
while the heating thermostat is reverse acting (RA).  
Operation is very similar to system-powered warm-up. The  
changeover switch assembly is field installed in the unit ple-  
num and is piped in-line between the volume controller and  
the thermostat. It consists of 2 thermally operated pneumatic  
valves, one for each thermostat. The tube from the volume  
controller is connected by a ‘T’ into the valve assembly,  
60  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 62 — Heating/Cooling Unit — Cooling, Cold Air in Duct, Changeover in Cooling,  
Thermostat Open, Controller Shut Off, Unit Shut Off  
Fig. 63 — Heating/Cooling Unit — Heating, Hot Air in Duct, Changeover in Heating,  
Thermostat Open, Controller Shut Off, Unit Shut Off  
61  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 64 — Heating/Cooling Unit — Cooling, Cold Air in Duct, Changeover in Cooling,  
Thermostat Closed, Controller Bleeding, Unit Cooling  
Fig. 65 — Heating/Cooling Unit — Heating, Hot Air in Duct, Changeover in Heating,  
Thermostat Closed, Controller Bleeding, Unit Heating  
62  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VAV HEATING — It is suggested that the following section  
be reviewed before reading this section: VAV Cooling,  
page 56.  
Combining a diffuser-mounted constant volume control pack-  
age with a wall-mounted thermostat package (heating only)  
allows the use of Modulineunits in VAV heating  
applications.  
The operation of the heating only thermostat is opposite  
to that of the cooling only thermostat in that the heating only  
thermostat is reverse acting (RA) instead of direct acting (DA).  
The thermostat’s bleed valve is open when the room tem-  
perature is above set point. It bleeds air from the low  
pressure chamber of the volume controller, lowering its pres-  
sure, and allowing the relatively stronger pressure of the air  
in the controller’s high pressure chamber to hold closed the  
bleed from the controller’s bellows pressure chamber. The  
bellows pressure becomes equal to the high pressure in the  
unit plenum, closing the unit damper and shutting off the  
unit discharge. See Fig. 66.  
As the room temperature falls, the thermostat bleed closes  
proportionally. This raises the pressure of the air in the low  
pressure chamber of the controller, forcing the bellows pres-  
sure chamber bleed open and lowering the bellows pressure  
proportionally. The damper opens and the unit delivers air to  
meet the existing demand in the conditioned space.  
See Fig. 67.  
Fig. 66 — Variable Volume Controls — Thermostat Open, Controller Shut Off, Unit Shut Off  
63  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 67 — Variable Volume Controls — Minimum Flow: Thermostat Partially Open,  
Controller Partially Open, Unit Delivering Minimum Flow  
be connected to the warm-up terminal of the central station  
System-Powered Controls with Electric  
Interface  
unit, if such is provided. Thus, when heated air be-  
gins to flow in the distribution duct, the bellows is bled down  
by the action of the electric warm-up valve and heated air  
can flow into the conditioned space (Fig. 68).  
VAV COOLING WITH ELECTRIC WARM-UP — Another  
approach to warm-up is the addition of an electric warm-up  
valve; the operating principle is the same as system powered  
warm-up. A building with its conditioning system shut down  
during unoccupied hours must be brought close to operating  
temperature before the occupants arrive. Heated air supplied  
to the space from a central unit can quickly restore operating  
conditions. But because the VAV thermostat has closed the  
unit, the result of the lack of load, the system powered con-  
trol needs to be overcome.  
An electric warm-up valve located on the Moduline unit  
between the volume controller and the thermostat is wired to  
the primary air source machine room. The valve can be  
activated by a simple manual or timer switch or it can  
In the cooling mode (Fig. 69), air flows freely between  
the volume controller and the thermostat and control func-  
tion is not affected. When warm-up is activated, the nor-  
mally open port closes and the control circuit is closed after  
the volume controller. As with system powered warm-up,  
this causes the pressure to rise in the low pressure chamber  
of the volume controller and opens the valve that bleeds air  
from the bellows pressure chamber. The increased bleed rate  
lowers the bellows pressure, opening the unit damper, and  
allowing the flow of primary air to increase up to the con-  
stant volume set point of the volume controller.  
64  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 68 — Cooling with Warm-Up — Morning, Hot Air in Duct, Warm-Up Switch Closed,  
Controller Bleeding, Unit Heating  
Fig. 69 — Cooling with Warm-Up — Nighttime Condition, Room Cool, Thermostat Open,  
Bleeding, Warm-Up Open, Controller Shut Off, Unit Shut Off  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VAV HEATING AND COOLING WITH ELECTRIC  
CHANGEOVER — This application uses a CV control pack-  
age along with a wall-mounted thermostat package (cooling/  
heating) and an electric changeover package. The change-  
over valve permits control of the unit to be switched between  
the cooling and heating sides of a cooling/heating thermo-  
stat. It is field-installed in-line between the volume control-  
ler and the thermostat.  
controller and the cooling side of the thermostat. Because  
the NC port is closed, the heating side of the thermostat is  
locked out of the system. Upon changeover to heating, the  
solenoid valve is energized. The NO port closes and the NC  
port is opened, and the control circuit switches to the heat-  
ing side of the thermostat. Typically, the solenoid valve is  
wired to activate automatically when the heating system is  
turned on, although it may be operated by a simple on/off  
switch.  
Refer to Fig. 70-73. In cooling operation, the NO port of  
the valve opens the control circuit between the volume  
Fig. 70 — Heating/Cooling Unit — Cooling, Cold Air in Duct, Electric Changeover in Cooling,  
Thermostat Open, Controller Shut Off, Unit Shut Off  
66  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 71 — Heating/Cooling Unit — Heating, Hot Air in Duct, Electric Changeover in Heating,  
Thermostat Open, Controller Shut Off, Unit Shut Off  
Fig. 72 — Heating/Cooling Unit — Cooling, Cold Air in Duct, Electric Changeover in Cooling,  
Thermostat Closed, Controller Bleeding, Unit Cooling  
67  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 73 — Heating/Cooling Unit — Heating, Hot Air in Duct, Electric Changeover in Heating,  
Thermostat Closed, Controller Bleeding, Unit Heating  
VAV COOLING WITH ELECTRIC HEAT INTERLOCK —  
A conditioned space may contain a Moduline system for cool-  
ing and a separate heating system such as baseboard electric  
or hot water or an overhead fan coil. The electric interlock  
switch enables the cooling and heating systems to operate as  
the load dictates with overlap.  
The electric interlock switch compares the bellows pres-  
sure with the low pressure, as a practical means of detecting  
the operating level of the unit. When the unit is delivering,  
the bellows pressure is significantly lower than the low pres-  
sure and the electric interlock (differential pressure) switch  
is open, interrupting the power supply to the heating system.  
When the unit is shut off, the pressures are approximately  
equal and the switch closes, allowing the heating system to  
be energized. It is field installed with the low pressure port  
piped to the auxiliary bellows pressure stub of the filter. (See  
Fig. 74.) The high pressure port is connected by a ‘‘T’’ into  
the line between the volume regulator and the thermostat.  
Fig. 74 — Connection for Electric Interlock  
68  
Download from Www.Somanuals.com. All Manuals Search And Download.  
System-Powered Controls with Pneumatic  
Interface  
PNEUMATIC SEQUENCED HEATING/COOLING (HOT  
WATER) — By using a 20 psi pneumatic source, one ther-  
mostat can control both heating and Moduline cooling in the  
conditioned space. The pneumatic circuit is interfaced with  
the system-powered circuit by use of a pilot valve. In cool-  
ing, the Moduline airflow is controlled by the duct-powered  
volume controller just as in all system-powered control. As  
the schematic diagram shows, a DA pneumatic wall ther-  
mostat working through the pilot valve, replacing the system-  
powered thermostat, modulates the pilot valve and thus the  
volume controller low side pressure.  
Figure 75 shows the piping diagram. Figure 76 shows the  
sequence diagram for a direct acting thermostat with a nor-  
mally open pilot valve. With the system shut down and the  
space temperature low, at start-up the thermostat branch pres-  
sure is low, and the normally open water valve (or other heat-  
ing means) is open. As the space temperature rises, the branch  
pressure rises, modulating the water valve to a closed po-  
sition. The pilot valve is normally open, with set point above  
water valve spring rate, thus maintaining a low pressure in  
the low side of the volume controller, closing the bleed valve  
in the controller and raising the bellows pressure to the duct  
pressure level; this results in unit shutoff.  
Fig. 76 — Sequence Diagram — DA Thermostat  
If the space temperature continues to rise, the NO pilot  
valve will modulate toward closed, raising the low side pres-  
sure, opening the bleed, reducing the bellows pressure, and  
opening the Moduline unit air valve. The airflow will rise  
until the volume controller setting is reached.  
Note that the spring rates of the hot water valve and the  
pilot valve must be properly matched to accomplish the ac-  
tion described above.  
A heating/cooling sequence can also be accomplished with  
a reverse acting circuit (Fig. 77 and 78). At start-up, the tem-  
perature is low, the branch pressure is high, and normally  
closed water valve is wide open. As the space temperature  
rises, the branch pressure falls and the water valve closes,  
stopping the heating supply. The pilot valve is NC and thus  
at branch pressures above its setting will open, volume con-  
troller low pressure will be reduced, the bellows pressure  
will rise and the unit will shut off.  
Fig. 77 — Piping Diagram, Heating/Cooling  
Sequence, RA Thermostat  
LEGEND FOR FIG. 75 - 78  
DA  
HW  
M
Direct Acting  
Hot Water  
Main  
NC  
NO  
RA  
Normally Closed  
Normally Open  
Reverse Acting  
Fig. 78 — Sequence Diagram, RA Thermostat  
Fig. 75 — Piping Diagram, Heating/Cooling  
Sequence, DA Thermostat  
69  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VAV COOLING WITH PNEUMATIC WARM-UP OR FIRE  
SAFETY SWITCH — Through the use of a specific pneu-  
matic switch, the functions of pneumatic warm-up and fire  
safety can be added to Modulineinstallations.  
Pneumatic warm-up offers an opportunity to open all Modu-  
line units in an area to allow immediate hot air distribution  
prior to the building occupancy. Through the use of a sepa-  
rate pneumatic signal, the pneumatic warm-up switch, placed  
in-line between the Moduline volume controller and the dif-  
fuser or wall system powered thermostat, closes the low pres-  
sure bleed in the thermostat line (in the same way as the  
system powered warm-up switch). This raises the low side  
pressure, opens the volume controller bleed and lowers the  
bellows pressure, allowing airflow from the Moduline ter-  
minal at the setting of the volume controller.  
The pneumatic warm-up switch can be piped either NO or  
NC. Figure 79 shows an NO arrangement. The switch is non-  
adjustable and preset to close at 8 ± 2.0 psig. Thus a signal  
pressure in excess of 10 psi will cause the switch to close.  
A pneumatic warm-up switch is required for each Moduline  
unit but only one pneumatic signal valve is required for mul-  
tiple Moduline units. Figure 80 shows the basic piping.  
Fig. 79 — Piping Diagram, NO Configuration,  
Pneumatic Warm-Up  
The field-supplied 3-way pneumatic valve is supplied with  
main pressure and is closed in cooling operation. When heat  
for warm-up is required, a signal sent from the heat source  
opens the pneumatic valve, supplying main pressure to the  
Moduline pneumatic warm-up switches. When the heat is  
discontinued, the pneumatic valve opens and the switches  
return to an open configuration.  
Note that the pneumatic warm-up switch is a nonbleed  
device. The pneumatic valve should therefore be a 3-way  
device, arranged to bleed out the pneumatic circuit down-  
stream of the valve when the valve is closed.  
The pneumatic warm-up switch can be arranged as an NC  
device; Fig. 81 gives the piping connections.  
For fire safety, the same switch is added to the Moduline  
control circuit as a normally open fire safety switch as shown  
in Fig. 82A. The fire safety switch on each Moduline ter-  
minal is connected to a pneumatic distribution circuit on each  
floor of the building. A3-way valve is connected to the switches  
and to the fire master control as shown in Fig. 83.  
The operation is identical to the pneumatic warm-up cir-  
cuit. At the onset of a fire, the fire master control opens the  
Moduline units on the non-fire floors by closing the Modu-  
line fire safety switches, raising the controller low side pres-  
sure and bleeding the bellows. The 3-way pneumatic valve  
on each floor supplies pneumatic pressure in excess of the  
set point of 8.0 ± 2 psig. On the fire floor where air is to be  
shut down, the distribution system uses a duct fire-damper  
to stop the air, and the fire safety switch position is not the  
determining factor in the Moduline operation.  
Fig. 80 — Basic Piping for Pneumatic  
Warm-Up Switch  
If a normally closed fire switch is required, see piping dia-  
gram shown in Fig. 82B. In this case, pneumatic pressure is  
maintained on the fire switch when the system fan is acti-  
vated. Loss of pneumatic pressure closes the fire switch, bleed-  
ing the bellows.  
Fig. 81 — Piping Diagram, NC Configuration,  
Pneumatic Warm-Up  
LEGEND FOR FIG. 79 - 83  
HW  
M
NC  
Hot Water  
Main  
Normally Closed  
NO  
S
T
Normally Open  
Switch  
Thermostat  
70  
Download from Www.Somanuals.com. All Manuals Search And Download.  
AIRFLOW ADJUSTMENT  
Each 37HS volume controller is equipped with a maxi-  
mum cfm lever for setting the required unit airflow in the  
field. The lever is located at the bottom of the controller. See  
Fig. 84. The controller has a star wheel located at the top of  
the controller for setting the minimum airflow. The star wheel  
is also shown in Fig. 84.  
Maximum Airflow (Cfm) Adjustment — The 37HS  
maximum airflow adjustment lever is common to all sizes  
and is divided into levels of percent cfm. Table 16 shows the  
unit airflow that will be obtained by each lever setting for  
each unit size.  
Table 16 — Maximum Airflow Settings  
Fig. 82A — NO Configuration for Fire Safety  
UNIT AIRFLOW (CFM)  
37HS2  
LEVER SETTING  
(% CFM)  
37HS1  
37HS4  
120  
100  
80  
120  
100  
80  
240  
200  
160  
80  
480  
400  
320  
160  
40  
40  
The maximum cfm is the unit airflow obtained when the  
thermostat is calling for full cooling in a VAV system; it is  
the design cfm for the space conditioned by the unit or units  
regulated by one controller.  
To set maximum cfm with zero minimum cfm:  
1. Set diffuser or wall thermostat for maximum cooling.  
2. Turn the minimum cfm star wheel counterlockwise until  
the internal stop is reached. Do not attempt to override  
stop. (Minimum cfm has been set at zero, and the unit  
will turn off when required.)  
3. Adjust maximum cfm lever to desired percent cfm.  
Fig. 82B — NC Configuration for Fire Safety  
Minimum Airflow (Cfm) Adjustment — Some ap-  
plications require both a design maximum cfm and a mini-  
mum cfm. The 37HS controller can be set to provide both  
airflow requirements.  
To set maximum and minimum cfm:  
1. Set diffuser or wall thermostat for maximum cooling.  
2. Turn the minimum cfm star wheel counterclockwise un-  
til the internal stop is reached. Do not attempt to override  
stop.  
3. Shut off unit by adjusting thermostat to zero cool-  
ing, or disconnect tube from volume controller to  
thermostat.  
4. Place a standard airflow hood against the outlet of the  
master unit and slowly turn the minimum cfm star wheel  
on the controller clockwise until the desired minimum cfm  
is reached.  
5. Return the thermostat to the desired setting and/or recon-  
nect tube between volume controller and thermostat.  
Fig. 83 — Fire Safety Switch Floor Layout  
6. Adjust maximum cfm lever to desired percent cfm.  
71  
Download from Www.Somanuals.com. All Manuals Search And Download.  
S
O
S
O
OPEN  
MINIMUM CFM  
STAR WHEEL  
%
40  
120  
80  
%
CFM  
40  
120  
100  
80  
MAXIMUM CFM LEVER  
VOLUME CONTROLLER  
Fig. 84 — Minimum and Maximum Airflow Adjustments, 37HS Controller  
Table 17 — Multiple Unit Airflow Variation  
Variation in Maximum Airflow — As explained in  
the Terminal Selection and Layout section, Modulineunits  
in air series can be controlled individually with a volume  
controller at each unit, or with a master/slave combination,  
where one controller is used with multiple units. All  
the units on one controller must be of the same model  
(capacity).  
In master/slave combinations, some variation in maxi-  
mum airflow among the terminals in air series will occur.  
The variation in maximum airflow is a function of the unit  
plenum size, the model, and the number of units in an air  
series on one controller. Table 17 shows the expected varia-  
tion from the unit with the smallest airflow to the unit with  
the largest airflow.  
APPROXIMATE AIRFLOW VARIATION (Cfm)  
LOWEST UNIT TO HIGHEST UNIT IN AIR SERIES*  
PLENUM  
MODEL  
Number of Units in Air Series On  
One Controller  
SIZE (in.)  
2
3
4
5
7 x 7  
9 x 9  
10  
10  
10  
20  
20  
20  
40  
40  
40  
15  
15  
15  
30  
30  
60  
60  
20  
20  
20  
40  
40  
80  
25  
25  
37HS1  
37HS2  
37HS4  
11 x 11  
7 x 7  
9 x 9  
11 x 11  
9 x 9  
11 x 11  
13 x 13  
For single units with controller, the cfm variation from  
the lever setting is ± 10%.  
*Values shown are based on a typical short, straight duct run be-  
tween units. Variation shown may be affected if there are excessive  
duct pressure losses between units.  
NOTE: The variation value shown in Table 17 for a given number of  
units of a certain model size (capacity) is the same for all size ple-  
nums used in an air series of recommended combinations for that  
model size. Thus, 3 units of model size 37HS2, plenum size 9 x 9, will  
have a maximum variation of 30 cfm; 3 units, plenum sizes 9 x 9 (2)  
and 7 x 7 (1) will also have a maximum variation of 30 cfm. A dash  
indicates that the quantity of a particular plenum size is not recom-  
mended in air series for that unit size.  
72  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A variety of diffuser assemblies are available for the Modu-  
line unit. Tables 18 - 20 show the standard diffusers avail-  
able, which can be ordered directly from the price pages.  
Tables 21-23 show the optional diffusers, which can be pro-  
vided by quote control.  
The difference in standard 37HS diffusers and optional 37A  
diffusers is demonstrated in Fig. 87. The slot opening in the  
37HS is larger than that of the 37A, reducing the net pres-  
sure required from the unit and somewhat reducing the throw.  
Note that the dimensions of the diffuser shown in Fig. 87  
are useful when matching units or 35BD boot diffusers in  
the ceiling. Certified dimension drawings are available for  
these diffusers and the other optional diffusers shown in  
Tables 21-23.  
AIR DISTRIBUTION  
Linear slot diffusers are an integral part of the Moduline  
unit. They provide excellent air distribution for the condi-  
tioned space. The diffuser configuration is designed to in-  
duce room air, creating continuous air motion for occupants  
of the room and reasonably consistent temperatures from floor  
to ceiling.  
Figure 85 shows how cool primary air discharged at the  
ceiling line induces room air toward the diffuser. The cool  
air mixes with the room air, creating room air motion and  
raising the temperature of the air descending upon the room  
occupants. Figure 86 provides a typical room air distribution  
pattern for 2-way blow and one-way blow Moduline units.  
The upper number on the distribution pattern is the mixture  
temperature; the lower number is the air velocity in ft/min.  
Fig. 85 — ModulineDiffuser Mixing Room Air and Primary Air  
73  
Download from Www.Somanuals.com. All Manuals Search And Download.  
37HS — 2-W
37HS2 — ONE
Fig. 86 — Typical Room Air Distribution Pattern  
74  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Fig. 87 — Slot Openings in Standard and Optional Diffusers  
75  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 18 — Standard Diffusers for 37HS1  
UNIT  
MODEL  
LENGTH  
(in.)  
CEILING  
TYPE  
DESIGNATION  
CONFIGURATION  
FLOW  
MATERIAL  
MODE  
23  
47  
T-Bar  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
22.92  
46.92  
24  
2-Way  
Alum  
Cooling  
48  
23.38  
47.38  
1174 mm  
1200 mm  
23  
T-Bar  
47  
22.92  
46.92  
24  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
One-Way  
Alum  
Alum  
Steel  
Cooling  
48  
23.38  
47.38  
1174 mm  
1200 mm  
23  
22.92  
24  
T-Bar  
Tegular T-Bar  
Continous T-Bar  
Narrow T-Bar  
Two-Way  
or  
One-Way  
Heating  
Cooling  
37HS1  
HS  
DIRECTOR DIFFUSER  
23.38  
23  
47  
22.92  
46.92  
24  
Plaster, Spline  
2-Way  
Cooling  
48  
23.38  
47.38  
1174 mm  
1200 mm  
23  
REMOVABLE DIFFUSER  
Metric  
47  
22.92  
46.92  
24  
Plaster, Spline  
2-Way  
Alum  
Cooling  
48  
23.38  
47.38  
1174 mm  
1200 mm  
Metric  
REMOVABLE DIFFUSER  
76  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 19 — Standard Diffusers for 37HS2  
UNIT  
MODEL  
LENGTH  
(in.)  
CEILING  
TYPE  
DESIGNATION  
CONFIGURATION  
FLOW  
MATERIAL  
MODE  
47  
59  
T-Bar  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
46.92  
58.92  
48  
2-Way  
Alum  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
One-Way  
Alum  
Alum  
Steel  
Alum  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
2-Way  
or  
One-Way  
Heating  
Cooling  
37HS2  
HS  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
DIRECTOR DIFFUSER  
59  
46.92  
58.92  
48  
Plaster, Spline  
2-Way  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
REMOVABLE DIFFUSER  
Metric  
59  
46.92  
58.92  
48  
Plaster, Spline  
2-Way  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
Metric  
REMOVABLE DIFFUSER  
77  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 20 — Standard Diffusers for 37HS4  
UNIT  
MODEL  
LENGTH  
(in.)  
CEILING  
TYPE  
DESIGNATION  
CONFIGURATION  
FLOW  
MATERIAL  
MODE  
47  
59  
T-Bar  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
46.92  
58.92  
48  
2-Way  
Alum  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
One-Way  
Alum  
Alum  
Steel  
Alum  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
2-Way  
or  
One-Way  
Heating  
Cooling  
37HS4  
HS  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
DIRECTOR DIFFUSER  
59  
46.92  
58.92  
48  
Plaster, Spline  
2-Way  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
REMOVABLE DIFFUSER  
Metric  
59  
46.92  
58.92  
48  
Plaster, Spline  
2-Way  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
REMOVABLE DIFFUSER  
Metric  
78  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 21 — Optional Diffusers for 37HS1  
UNIT  
MODEL  
LENGTH  
(in.)  
CEILING  
TYPE  
DESIGNATION  
CONFIGURATION  
FLOW  
MATERIAL  
MODE  
23  
47  
T-Bar  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
22.92  
46.92  
24  
AG  
2-Way  
Alum  
Cooling  
48  
23.38  
47.38  
1174 mm  
1200 mm  
23  
T-Bar  
47  
22.92  
46.92  
24  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
AG  
One-Way  
Alum  
Cooling  
48  
23.38  
47.38  
1174 mm  
1200 mm  
37HS1  
Metric  
T-Bar  
23  
22.92  
24  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
T-Bar  
2-Way  
or  
One-Way;  
2-Slot  
Heating  
Cooling  
DG  
Alum  
23.38  
23  
22.92  
24  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
2-Way  
or  
One-Way;  
3-Slot  
Heating  
Cooling  
DG  
Alum  
23.38  
79  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 22 — Optional Diffusers for 37HS2  
UNIT  
MODEL  
LENGTH  
(in.)  
CEILING  
TYPE  
DESIGNATION  
CONFIGURATION  
FLOW  
MATERIAL  
MODE  
47  
59  
T-Bar  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
46.92  
58.92  
48  
AG  
2-Way  
Alum  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
T- Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
AG  
DG  
DG  
One-Way  
Alum  
Alum  
Alum  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
37HS2  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
2-Way  
or  
One-Way;  
2-Slot  
Heating  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
DIRECTOR DIFFUSER  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
2-Way  
or  
One-Way;  
3-Slot  
Heating  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
DIRECTOR DIFFUSER  
80  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 23 — Optional Diffusers for 37HS4  
UNIT  
MODEL  
LENGTH  
(in.)  
CEILING  
TYPE  
DESIGNATION  
CONFIGURATION  
FLOW  
MATERIAL  
MODE  
47  
59  
T-Bar  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
46.92  
58.92  
48  
AH  
2-Way  
Alum  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
AH  
DH  
DH  
One-Way  
Alum  
alum  
Alum  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
37HS4  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
2-Way  
or  
One-Way  
Heating  
Cooling  
60  
47.38  
59.38  
1174 mm  
1200 mm  
47  
DIRECTOR DIFFUSER  
T-Bar  
59  
46.92  
58.92  
48  
Tegular T-Bar  
Continuous T-Bar  
Narrow T-Bar  
Metric  
Heating  
Cooling  
2-Way  
60  
47.38  
59.38  
1174 mm  
1200 mm  
DIRECTOR DIFFUSER  
81  
Download from Www.Somanuals.com. All Manuals Search And Download.  
The optimum air throw values given in the table are dis-  
tances from the unit centerline to the outside wall or nearest  
obstruction (wall, light fixture or opposing air stream).  
Throw for Standard Diffusers — Tables 24 and 25  
provide the suggested minimum and maximum coverages  
the Moduline® air terminals can handle in a typical instal-  
lation while maintaining the desired room conditions.  
Table 25 — Air Throw Data —  
2-Way and 1-Way Director, 3-Slot Diffusers  
Table 24 — Air Throw Data —  
1-Way and 2-Way Blow, 2-Slot Diffusers  
OPTIMUM AIR THROW (ft)  
37HS1 UNIT  
OPTIMUM AIR THROW (ft)  
37HS1 UNIT  
Heating  
Cooling  
AIRFLOW  
(Cfm)  
1-Way Blow  
2-Way Blow  
AIRFLOW  
(Cfm)  
1-Way Blow  
2-Way Blow  
Min  
Max  
Min  
Max  
Min  
Max  
Min  
Max  
40  
50  
2.0  
4.0  
7.0  
9.0  
2.0  
3.0  
3.5  
4.0  
4.5  
5.0  
6.0  
7.0  
5.0  
6.0  
40  
50  
2.0  
4.0  
7.0  
9.0  
2.0  
3.0  
3.5  
4.0  
4.5  
5.0  
6.0  
7.0  
5.0  
6.0  
60  
7.5  
12.0  
15.0  
18.0  
20.0  
22.0  
24.0  
7.5  
70  
8.0  
9.0  
10.0  
11.0  
12.0  
9.0  
60  
7.5  
12.0  
15.0  
18.0  
20.0  
22.0  
24.0  
7.5  
80  
10.5  
11.5  
13.0  
15.0  
70  
8.0  
9.0  
10.0  
11.0  
12.0  
9.0  
90  
80  
10.5  
11.5  
13.0  
15.0  
100  
110  
90  
100  
110  
OPTIMUM AIR THROW (ft)  
1-Way Blow 2-Way Blow  
37HS2 UNIT  
AIRFLOW  
(Cfm)  
OPTIMUM AIR THROW (ft)  
Heating Cooling  
1-Way Blow 2-Way Blow  
37HS2 UNIT  
AIRFLOW  
(Cfm)  
Min  
Max  
Min  
Max  
80  
100  
120  
140  
160  
180  
200  
220  
2.0  
4.0  
7.0  
9.0  
2.0  
3.0  
3.5  
4.0  
4.5  
5.0  
6.0  
7.0  
5.0  
6.0  
Min  
Max  
Min  
Max  
7.5  
12.0  
15.0  
18.0  
20.0  
22.0  
24.0  
7.5  
80  
100  
120  
140  
160  
180  
200  
220  
2.0  
4.0  
7.0  
9.0  
2.0  
3.0  
3.5  
4.0  
4.5  
5.0  
6.0  
7.0  
5.0  
6.0  
8.0  
9.0  
10.0  
11.0  
12.0  
9.0  
10.5  
11.5  
13.0  
15.0  
7.5  
12.0  
15.0  
18.0  
20.0  
22.0  
24.0  
7.5  
8.0  
9.0  
10.0  
11.0  
12.0  
9.0  
10.5  
11.5  
13.0  
15.0  
OPTIMUM AIR THROW (ft)  
1-Way Blow 2-Way Blow  
37HS4 UNIT  
AIRFLOW  
(Cfm)  
OPTIMUM AIR THROW (ft)  
Heating Cooling  
1-Way Blow 2-Way Blow  
Min  
Max  
Min  
Max  
37HS4 UNIT  
AIRFLOW  
(Cfm)  
160  
200  
250  
300  
350  
400  
440  
8.5  
10.0  
11.0  
12.0  
14.0  
15.0  
17.0  
16.0  
20.0  
21.0  
22.0  
23.0  
25.0  
29.0  
5.0  
6.0  
7.0  
10.0  
13.0  
17.0  
19.0  
21.0  
24.0  
7.0  
Min  
Max  
Min  
Max  
8.0  
9.0  
10.0  
13.0  
160  
200  
250  
300  
350  
400  
440  
8.5  
10.0  
11.0  
12.0  
14.0  
15.0  
17.0  
16.0  
20.0  
21.0  
22.0  
23.0  
25.0  
29.0  
5.0  
6.0  
7.0  
10.0  
13.0  
17.0  
19.0  
21.0  
24.0  
7.0  
8.0  
9.0  
10.0  
13.0  
NOTES:  
1. Minimum air throw refers to the distance from the diffuser where the air ve-  
locity is 150 fpm. In maximum air throw, this velocity has dropped to 50 fpm.  
2. Data is based on an area with a 9-ft ceiling. For higher ceilings, values may  
be reduced by one foot for each foot of height increase. For specific instal-  
lations, minimum values can be reduced if properly qualified. Values are  
dependent on cfm only and are not affected by duct pressure.  
82  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Copyright 1991 Carrier Corporation  
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.  
Book 3  
PC 201  
Catalog No. 513-741  
Printed in U.S.A.  
Form 37HS-1XA  
Pg 84  
6-91  
Replaces: New  
Tab 6a  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Blackberry Cell Phone 103 User Manual
Black Decker Pressure Washer 598121 00 User Manual
Black Decker Sander 90518305 User Manual
Bolens Lawn Mower 190 041A User Manual
Bosch Appliances Home Security System AEC AEC21 EXT1 User Manual
Bosch Appliances Security Camera DiBos User Manual
Bradford White Corp Water Heater TG 150I NX User Manual
Brinkmann Gas Grill Stainless Steel 4 Burner Gas Grill User Manual
Brother Sewing Machine 882 U70 User Manual
Bush Hog Brush Cutter 3209 Offset User Manual