				OPERATION   
					REAR PANEL (continued)   
					Switch On   
					Back-up   
					Protection Socket   
					Surge Protection   
					Socket   
					With the UPS plugged in, press and hold the on/off/test button for   
					more than three seconds until the "ON LINE" LED lights up to   
					switch the UPS on. The UPS will perform self-testing each time it   
					is switched on. Note: The UPS maintains a battery charge when in   
					the off position.   
					AC   
					Inlet   
					Switch Off   
					Press and hold the on/off/test button for more than three seconds   
					until the "ON LINE" or "ON BATTERY" LED goes off.   
					FOR MODELS   
					F6C350zSER-SB   
					F6C500zSER-SB   
					F6C650zSER-SB   
					Self-Test   
					Use the self-test to verify both the operation of the UPS and the   
					condition of the battery. In normal utility power, push the   
					on/off/test button less than two seconds and the UPS performs   
					a self-test function. During the self-test, the UPS operates in   
					“BACKUP” mode.   
					RJ11/RJ45   
					Circuit   
					Breaker   
					Communication   
					Port   
					Surge Protector   
					AC-Input Power Cord   
					Connect to the AC utility.   
					Note   
					During the self-test, the UPS briefly operates “ON BATTERY”   
					mode (the “REPLACE BATTERY” LED comes on). If the UPS   
					passes the self-test, it returns to “ON LINE” operation. The   
					“REPLACE BATTERY” LED goes off and the “ON LINE” LED goes   
					on steady. If the UPS fails the self-test, it immediately returns to   
					on-line operation and flashes the “REPLACE BATTERY” LED. The   
					loads are not affected. Recharge the battery overnight and   
					perform the self-test again. If the “REPLACE BATTERY” LED is still   
					on, the battery will need to be replaced; go to belkin.com.   
					AC Input Breaker (Circuit Breaker)   
					USER MANUAL   
					The circuit breaker button will stick out if an overload condition   
					forces the UPS to disconnect itself from utility power. If the button   
					sticks out, disconnect nonessential equipment.   
					Battery Back-up Sockets   
					Data-sensitive equipment such as a computer, monitor, and   
					external drive should be powered by these sockets. Battery power   
					is automatically provided in case of a power outage. Power (utility   
					or battery) is not supplied to these sockets when the UPS is   
					switched off. (Do not plug surge protectors, power strips, or laser   
					printers into the battery back-up sockets.)   
					Silence   
					In "BACK-UP" mode, push the on/off/test button less than three   
					seconds to silence the audible alarm. (The function is void when   
					under condition of "LOW BATTERY".)   
					One Surge-Protected Socket   
					Equipment such as a printer, fax machine, scanner, or a desk lamp   
					should be powered by this socket. This socket does not provide   
					power during a power outage. This socket is always on (when   
					utility power is available) and is not controlled by the front   
					panel switch.   
					INTRODUCTION   
					Have you ever noticed your lights dim or flicker when you turn   
					on your dishwasher or air conditioner? This common occurrence   
					is attributed to an under-voltage of power, also know as a   
					brownout.   
					A brownout is a period of insufficient power-line voltage. It is   
					the most common power problem, accounting for 80% of all   
					power disturbances.   
					Effects: A brownout can deprive a computer of the power it   
					needs to function, causing unwanted damage to your   
					computer–such as frozen keyboards and hard drive crashes.   
					Such problems will cause you to incur computer repairs, lost   
					data, and downtime.   
					Solution: A Belkin Uninterruptible Power Supply (UPS) unit   
					protects against surges, spikes, swells, line-noise, brownouts,   
					and blackouts! A surge protector can only protect your computer   
					from over-voltages due to irregular power!   
					Printer   
					CONNECTING EQUIPMENT   
					Computer   
					Connect the Loads   
					Plug the loads into the output connectors on the rear of the UPS.   
					To use the UPS as a master on/off switch, make sure all of the   
					loads are switched on.   
					Caution   
					Never connect a laser printer or scanner to the back-up sockets of   
					a UPS with other computer equipment. A laser printer or scanner   
					periodically draws significantly more power when in use than when   
					idle. This may overload the UPS.   
					Cash   
					Register   
					Lamp   
					CONNECTING THE   
					TELEPHONE/FAX/MODEM/DSL LINES   
					PRESENTATION   
					IMPORTANT SAFETY INSTRUCTIONS   
					Connect a single telephone/fax/modem/DSL line into the surge-   
					protected sockets on the back of the UPS. The RJ11 modular   
					sockets accept standard single-line telephone connections. This   
					connection will require another length of telephone cable   
					(supplied).   
					Please Read This Manual!   
					STEADY LIGHT   
					LED   
					MEANING   
					BLINKING   
					Thank you for purchasing the Belkin Uninterruptible Power   
					Supply (UPS). It will provide you with the best protection for   
					your connected equipment.   
					Utility is normal.   
					GREEN   
					ON LINE/   
					ON BATTERY   
					Utility is abnormal, supplies power to outlets   
					from battery source.   
					Please Save This Manual!   
					Note! This connection is optional but highly suggested as   
					phone/fax/modem/DSL lines often carry dangerous surges and   
					spikes. The UPS works properly without a phone/fax/modem   
					/DSL connection.   
					It includes important instructions for the safe use of this UPS   
					and for obtaining factory service should the proper operation of   
					the UPS come into question.   
					Battery capacity is low. The UPS will start   
					shutdown. The unit sounds an audible alarm.   
					LOW BATTERY/   
					Please Save or Recycle the Packaging Materials!   
					YELLOW   
					1. The LED flashes eight seconds. It means the   
					UPS is in the self-checking mode.   
					REPLACE   
					BATTERY   
					Caution! The telephone/fax/modem/DSL protection feature could   
					be rendered inoperable if improperly installed.   
					The UPS shipping materials were designed with great care to   
					provide protection from transportation-related damage. These   
					materials are invaluable if you ever have to return the UPS for   
					service. Damage sustained during transit is not covered under   
					the warranty.   
					Federal Communications Commission Interference Statement   
					This equipment has been tested and found to comply with the   
					limits for a Class B digital device, pursuant to Part 15 of the FCC   
					Rules. These limits are designed to provide reasonable   
					protection against harmful interference in a residential   
					installation. This equipment generates, uses, and can radiate   
					radio frequency energy and, if not installed and used in   
					accordance with the instructions, may cause harmful   
					interference to radio communications. To assure continued   
					compliance, use only shielded interface cables when connecting   
					to computer or peripheral devices. Any changes or modifications   
					not expressly approved by the party responsible for compliance   
					could void the user’s authority to operate this equipment.   
					2. The LED flashes more than 10 seconds.   
					It means the battery is bad or the charger   
					is at fault.   
					Make sure that the telephone line from the wall is plugged   
					into the connector marked "IN", and the device to be   
					protected (telephone/fax/modem) is plugged into the   
					connector marked "OUT".   
					There is a problem with the UPS. The LED   
					will be lit continuosly and the unit will   
					sound an audible alarm for 10 seconds.   
					FAULT/   
					RED   
					OVERLOAD   
					Battery ouput is drawing more power than   
					the UPS can provide.   
					INSTALLATION   
					Note   
					Before the installation, please inspect the UPS upon   
					receipt. Make sure that everything inside the package is   
					not damaged.   
					ALARM   
					Back-up (Slow Alarm)   
					Connect to Utility   
					Connect the AC inlet to utility power via the power cord.   
					Charge the Battery   
					For best results, charge the battery for six hours prior to   
					initial use. The UPS charges its battery whenever it is connected to   
					the utility power.   
					When in "BACK-UP" mode, the GREEN LED illuminates and the   
					UPS sounds an audible alarm. The alarm stops when the UPS   
					returns to LINE NORMAL operation.   
					Low Battery (Rapid Alarm)   
					In "BACK-UP" mode, when the battery energy runs low, the UPS   
					beeps rapidly until the UPS shuts down from a depleted battery or   
					returns to LINE NORMAL operation.   
					FRONT PANEL   
					Press the button longer than three seconds to turn the UPS on   
					or off. Press the button less than three seconds to activate the   
					UPS self-testing or to silence the backup alarm.   
					Overload (Continuous Alarm)   
					When the UPS is overloaded (the connected loads exceed the   
					maximum rated capacity) the UPS emits a continuous alarm to   
					warn of an overload condition. Disconnect nonessential equipment   
					from the UPS to eliminate the overload.   
					Fault (10 Seconds Continuously)   
					Fault/Overload   
					Low Battery/Replace Battery   
					When the output is shorted, the UPS emits a 10-second alarm.   
					Disconnect the equipment from the UPS prior to checking   
					the equipment.   
					COMMUNICATION INTERFACE   
					Belkin Sentry Bulldog Shutdown Management Software and   
					RS-232 cable can be used with this UPS. If used, connect the   
					interface cable to the computer interface port on the rear panel of   
					the UPS, and then connect to the serial port on your PC.   
					REAR PANEL   
					Interface Port   
					The communication port provides the following features:   
					1) Monitors charger status   
					2) Monitors UPS status   
					3) Monitors battery status and condition   
					4) Monitors the utility status   
					5) Provides power-switch function for power saving   
					Provides an RS-232 port to relay the signal to support DOS,   
					Windows®, and other operating systems.   
					Phone/Fax/Modem/DSL or Network Protection   
					Telephone/fax/modem lines are surge protected and provide   
					complete safety for Internet connection. One input and one output   
					allow two devices to be protected (i.e. modem and fax).   
					On Line/On Battery   
					On/Off/Test   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				BELKIN COMPONENTS USER LICENSE AGREEMENT   
					SOFTWARE OPTIONS   
					STORAGE   
					LICENSE: You have the non-exclusive right to use the software.   
					You are not permitted to copy, modify or transfer the software or   
					documentation. You may not decompile, disassemble or   
					otherwise reverse engineer, break down, analyze or modify the   
					software.   
					Belkin Sentry Bulldog Shutdown Management Software   
					Belkin Sentry Bulldog Shutdown Management Software receives   
					communication through the RS-232 interface port to perform   
					monitoring functions, and also provide an orderly shutdown of the   
					computer in the event of a power failure. Moreover, Belkin Sentry   
					Bulldog Shutdown Management Software displays all of the   
					diagnostic symptoms on screen, such as voltage level, frequency,   
					battery level, etc. The software is available for Windows® 95,   
					Windows® 98, Windows NT® V4 or higher, Windows® 2000,   
					Windows® Me, Unix®, and Novell® 3.X and above.   
					Storage Conditions   
					Store the UPS covered and upright in a cool, dry location,   
					with its battery fully charged. Before storing, charge the UPS   
					for at least four hours. Disconnect any cables connected to   
					the computer interface port to avoid unnecessary drainage of   
					the battery.   
					USE AND RESTRICTIONS: You are permitted to make backup   
					copies of all the software disks for archival purposes only. You   
					must reproduce the proprietary notice set forth on the disks and   
					affix them to all backup copies. You are not permitted to use   
					these programs in connection with a computer service, or to use   
					the backup copies other than as a replacement for the original   
					copy.   
					Extended Storage   
					During extended storage in environments where the ambient   
					temperature is 15˚ C to 30˚ C, charge the UPS battery every   
					six months.   
					Interface Kits   
					During extended storage in   
					environments where the   
					ambient temperature is   
					30˚ C to 45˚ C, charge   
					the UPS battery every three   
					months. Note:   
					Each interface kit includes a special interface cable which is   
					required to convert status signals from the UPS into signals that   
					the individual operation system can recognize. The interface cable   
					must be connected to the (RS-232) serial port on the UPS. The   
					other side of the interface cable can be connected to the DB9   
					serial port on your PC. For other installation instructions and   
					features, please refer to the READ.ME file.   
					TERM: This license is effective upon acceptance by opening this   
					envelope or in any other way using the enclosed software, which   
					will constitute your acceptance of, and agreement to, this   
					Agreement, and is effective until terminated. The limited license   
					in this Agreement will be automatically terminated if you fail to   
					comply with any of the terms and conditions in this Agreement.   
					You agree that upon such termination you will immediately   
					destroy all programs and documentation, including all copies   
					made or obtained by you.   
					Caution: Use only factory supplied or UPS monitoring cable!   
					TECHNICAL SPECIFICATIONS   
					TROUBLESHOOTING   
					F6C350z   
					SER-SB   
					F6C500z   
					SER-SB   
					F6C650z   
					SER-SB   
					MODEL   
					RATED   
					CAPACITY   
					350VA/   
					190W   
					500VA/   
					300W   
					650VA/   
					360W   
					PROBLEM   
					POSSIBLE CAUSE   
					SOLUTION   
					UPS cannot   
					turn on.   
					UPS does not turn on properly. Press switch and hold longer   
					than three seconds.   
					RATED   
					VOLTAGE   
					INPUT   
					196-264VAC   
					Single Phase 50Hz   
					Simulated Sine Wave   
					50Hz   
					(No alarm, No Battery inside the UPS is bad. Replace with the same   
					LED lights) type of battery from belkin.com.   
					PHASE   
					FREQUENCY   
					LIMITED WARRANTY: Except for the limited replacement   
					warranty with respect to the disks expressly stated in the next   
					paragraph, THE PRODUCT, SOFTWARE, PROGRAM,   
					DOCUMENTATION, AND ANY RELATED INFORMATION, GOODS   
					OR SERVICES ARE PROVIDED "AS IS" WITH NO WARRANTY OR   
					REPRESENTATION OF ANY KIND WHATSOEVER. BELKIN   
					HEREBY DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR   
					IMPLIED, INCLUDING BUT NOT LIMITED TO THE IMPLIED   
					WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A   
					PARTICULAR PURPOSE.   
					UPS fault.   
					Call for service if the above   
					actions do not solve your   
					problems.   
					VOLTAGE   
					OUTPUT   
					BATTERY   
					FREQUENCY   
					UPS always at Power cord is loose.   
					Replace the power cord.   
					battery mode.   
					F6C350   
					Up to 15min   
					F6C500   
					Up to 20min   
					F6C650   
					Up to 25min   
					AC breaker is burned out   
					or tripped.   
					Replace or reset the breaker.   
					BACK-UP TIME   
					RECHARGE   
					TIME   
					AC utility voltage is too high,   
					too low, or blacked out.   
					Normal condition.   
					6 Hours to 90%   
					0~40°C   
					TEMPERATURE   
					HUMIDITY   
					Back-up time   
					too short.   
					Battery inside the UPS   
					is not fully charged.   
					Recharge the battery for   
					at least six hours.   
					ENVIRONMENT   
					10 ~ 90%   
					UPS is overloaded.   
					Remove some un-critical loads.   
					Replace battery at belkin.com.   
					Contact service personnel.   
					The entire risk of the use, results and performance of the   
					software, program and documentation is borne by you. Should   
					any or all of the product, software, program, documentation, or   
					related information, goods or services be defective, misused,   
					unsuitable or cause or give rise to any harm or liability   
					whatsoever, you, not Belkin or its associates, dealers or agents,   
					assume the entire liability, cost of repair, correction or any   
					payment or other remedy whatsoever. Furthermore, no warranty   
					or guarantee is made regarding the use or results of the product,   
					software, program, documentation, or any related information,   
					goods or services in terms of correctness, accuracy, reliability,   
					timeliness or otherwise. You use and rely on the program at your   
					own risk. The following is the only and exclusive warranty and   
					remedy of any kind: Belkin does warrant that the program disks   
					are free from physical defects in materials and workmanship   
					under normal use for a period of one (1) year from the date of   
					purchase, as evidenced by a copy of the sales receipt. Return the   
					defective disk or documentation with your receipt directly to   
					Belkin for a replacement.   
					The battery is weak.   
					EN 60950   
					ACA TS001-1997   
					ACA TS002-1997   
					PCT 200   
					Charger fault or other reason.   
					SAFETY   
					SAFETY   
					REGULATION   
					Low Battery.   
					LED blinks   
					more than 10   
					seconds.   
					Battery fault.   
					Charger fault.   
					Contact Belkin.   
					EMC   
					AS/NZS 3260:1993   
					DIMENSION   
					NET WEIGHT   
					7.1"W x 8.7"D x 2.4"H   
					Low Battery.   
					LED blinks   
					Contact Belkin.   
					APPEARANCE   
					2.9 KGS/   
					6.4 LBS   
					3.2 KGS/   
					7 LBS   
					3.2 KGS/   
					7 LBS   
					more than 10   
					seconds with   
					buzzer beeps.   
					All specifications are subject to change without prior notice.   
					BATTERY REPLACEMENT   
					SAFETY   
					EcoPower Service Program   
					In the event that the UPS needs a battery replacement, Belkin   
					offers its EcoPower Service Program. This program offers a   
					battery replacement on your UPS to ensure it is working properly   
					in protecting your connected devices. It also ensures that the   
					battery in the UPS is discarded of properly in an effort to keep our   
					environment clean. All participants in the program will receive a   
					two-year extended product warranty. Please call Belkin   
					Components for detailed information regarding the cost of the   
					program and shipping procedures.   
					CAUTION   
					! 
					• 
					• 
					• 
					Internal battery voltage is 12V DC. Used CSB HC1217W   
					(for 350VA), HC 1221W (for 500, 650VA).   
					UPS with user-replaceable batteries shall contain   
					detailed instruction for battery removal and installation.   
					The unit is intended for installation in a controlled   
					environment (temperature controlled, indoor area free   
					of conductive contaminants).   
					DISCLAIMER: Belkin or its associates will in no event be liable (i)   
					in any amount for lost profits or special, incidental, punitive or   
					consequential damages, or (ii) for any claim or damage of any   
					nature, or under any theory, whatsoever, in any amount in excess   
					of the purchase price you paid for the product. The warranties   
					and remedies here set are exclusive, and in lieu of all others oral   
					or written, express or implied. Some jurisdictions do not allow   
					exclusion or limitation of implied warranties or of liability for   
					incidental damages, so the foregoing limitations or exclusion   
					may not apply to you. This warranty gives you specific legal   
					rights which vary from jurisdiction to jurisdiction. HOWEVER,   
					YOU WAIVE SUCH RIGHTS, EXCEPT AS EXPRESSLY PROVIDED   
					UNDER THE TERMS AND CONDITIONS OF THIS AGREEMENT,   
					TO THE MAXIMUM EXTENT ALLOWED BY LAW.   
					Sealed lead battery. Battery must be recycled.   
					The Old Battery Must Be Recycled   
					Deliver the battery to an appropriate recycling facility or return it   
					to Belkin in the packing carton that came with your new battery.   
					Additional recycling information is provided with your new battery.   
					For Recycling Information   
					Inside the USA Call:   
					(800) Re-Use-Pb (738-7372)   
					Outside the USA Call:   
					1 (800) 244-4415   
					REFER SERVICING TO QUALIFIED SERVICE PERSONNEL OR   
					CONTACT BELKIN COMPONENTS.   
					Pb   
					Pb   
					NONSPILLABLE   
					BELKIN COMPONENTS USER LICENSE AGREEMENT   
					1. Lay down the UPS. Use your   
					thumb to open the battery   
					cover on the bottom of the unit.   
					2. Grasp the tab attached to   
					the battery and slide the   
					battery out.   
					Belkin Components ("Belkin") thanks you for choosing one of our   
					products for your use. This User License Agreement   
					("Agreement") contains the terms and conditions under which   
					limited use of the product is licensed to you.   
					The license is governed by the laws prevailing in the State of New   
					York, without regard to its conflicts of laws principles.   
					PLEASE READ THIS NOTICE CAREFULLY   
					ACKNOWLEDGMENT: By opening the package on which this   
					Agreement is printed, or through which it is visible, you   
					acknowledge that you have read this Agreement, understand it,   
					and agree that this agreement is the complete and exclusive   
					statement of agreement between yourself and Belkin and   
					supersedes any prior agreements, oral or written, and any other   
					communications relating to the subject matter of this Agreement.   
					DO NOT OPEN THIS ENVELOPE OR USE ANY OF THE SOFTWARE   
					UNTIL YOU HAVE READ AND AGREED TO THIS AGREEMENT. IF   
					YOU OPEN THE ENVELOPE, YOU ARE AGREEING TO THE TERMS   
					AND CONDITIONS SET OUT IN THIS AGREEMENT. IF YOU DO   
					NOT ACCEPT THESE TERMS AND CONDITIONS, YOU MUST   
					RETURN THE ENVELOPE UNOPENED AND WITH THE DISKS   
					INSIDE TO THE PARTY FROM WHOM YOU RECEIVED IT.   
					4. Put the battery cover back   
					and slide it into position.   
					3. Insert the replacement gently   
					into the UPS. Make sure the   
					battery is well connected!   
					MAINTENANCE   
					SEVERABILITY: Any term or provision of this Agreement or any   
					application thereof which may be prohibited or unenforceable by   
					law in a particular jurisdiction shall be interpreted and enforced   
					to the maximum extent allowed in such jurisdiction (which the   
					parties acknowledge could mean severing the provision from this   
					Agreement or, if allowed, enforcing it in a narrower form),   
					without affecting the remainder of this Agreement, or any other   
					application of such term or provision in such jurisdiction, or   
					application of such term or provision in any other jurisdiction.   
					• Normally, the life of a battery is 3-5 years. But extreme operating   
					conditions and environment may shorten its life span.   
					• When the UPS has been unused for some time, the battery   
					inside will discharge slightly. It is recommended to plug the UPS   
					into a wall socket to let the battery begin charging automatically.   
					• When cleaning the plastic case or front panel, use only a soft,   
					dry cloth. If the case or front panel is very dirty, use a neutral,   
					non-abrasive detergent.   
					• Do not use alcohol or ammonia-based solutions.   
					• When moving the UPS, always handle it with care.   
					SCOPE OF USE: In this Agreement, "software" means all machine   
					readable software programs and associated files in this package,   
					all modified versions of and upgrades or improvements to such   
					programs and all copies of such programs and files. You, a single   
					user opening this envelope ("You", "you" or "your"), may use the   
					software on a single central processing unit. You may not rent it,   
					loan it out, or lease it, nor use it on a multi-user system.   
					Belkin Components USA   
					800.223.5546   
					belkin.com/au   
					Belkin Components B.V.   
					Belkin Components   
					501 West Walnut St.   
					Compton • CA • 90220-5221 • USA   
					Tel: 310 898 1100 • Fax: 310 898 1111   
					Belkin Components, Ltd.   
					7 Bowen Cresent • West Gosford •   
					NSW 2250 • Australia   
					Belkin Components, Ltd.   
					Starparc Building • Boeing Avenue 333 •   
					1119 PH Schiphol-Rijk • The Netherlands   
					Tel.+31 (0)20 654 7300 • Fax.+31 (0)20 654 7349   
					Express Business Park • Shipton Way •   
					Rushden • NN10 6GL • United Kingdom   
					Tel:+44 (0)1933 35 2000 • Fax:+44 (0)1933 31 2000   
					Tel:+61 (2)4372 8600 • Fax:+61 (2)4325 4277   
					© 2002 Belkin Components. All rights reserved. All trade names are registered trademarks of respective manufacturers listed. P73579   
					Download from Www.Somanuals.com. All Manuals Search And Download.   
				 |