Baldor Portable Generator GLC10 User Manual

GLC Generator  
(Gaseous Liquid Cooled)  
GLC10, 15, 20, 25 30, 40, 45, 60, 65, 100 and 105  
Installation & Operating Manual  
2/08  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table of Contents  
Section 1  
Product Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Safety Notice . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Responsibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
IMPORTANT SAFETY INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Caution Statements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Section 2  
1-1  
1-1  
1-1  
1-2  
1-6  
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Limited Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Installation Guidelines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Site Planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Room Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Room Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Foundation Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Level Of Attenuation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
System Placement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Multi-Engine Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Exhaust Manifold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Exhaust Gas Restriction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
2-1  
2-1  
2-3  
2-3  
2-3  
2-4  
2-5  
2-9  
2-9  
2-9  
2-9  
2-9  
2-9  
Exhaust Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10  
Rain Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10  
Transfer Switch . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11  
Battery Starting System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12  
Battery Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12  
Battery Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12  
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13  
Battery Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13  
Section 3  
Receiving & Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
3-1  
3-1  
3-1  
3-1  
3-3  
3-3  
3-4  
3-6  
3-6  
3-9  
Receiving & Inspection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Lifting the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Physical Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Secure the Generator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Engine Cooling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Hot Exhaust Gasses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Fuel Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Electrical Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Battery Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-12  
Recommended Engine Oil and Battery Type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13  
Post Installation Checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3-13  
MN2408  
Table of Contents i  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4  
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Digital Engine Controller Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Set points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
4-1  
4-1  
4-4  
4-5  
4-6  
4-6  
Operator Control Panel (MICROPROCESSOR Engine Controller Only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-13  
Operating Procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14  
Manual Start/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14  
Automatic Start/Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-14  
Automatic Fault Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15  
Automatic Mains Failure (AMF) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-15  
Standard Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-17  
Output Contacts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-20  
Display Modes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21  
Operating Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21  
Fault Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-21  
Timer Countdown . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-22  
Generator AC Metering . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-23  
Engine Parameter Display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24  
Program Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-24  
Main Menu Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-25  
Analog Fault Menu Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-26  
Digital Fault Menu Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27  
Calibration Menu Loop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27  
Voltage Sensing Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27  
Voltage Calibration Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-27  
Current Sensing Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28  
Battery Voltage Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-28  
Engine Temperature & Oil Pressure Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-29  
Section 5  
Troubleshooting and Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
5-1  
5-1  
5-2  
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Problems and Solutions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  
Appendix A  
Options & Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1  
Battery Charger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1  
Battery Heaters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3  
Engine Block Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-5  
Silencers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-6  
Fuel Strainers & Fuel Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-7  
E-Stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-8  
Remote Annuciators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-9  
Radiator Duct Flange . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-10  
Enclosures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-11  
Appendix B  
Series GLC Parts & Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1  
GLC Circuit Breaker & Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-1  
GLC Wire Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2  
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-2  
Start-up Inspection Form . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . B-25  
ii Table of Contents  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 1  
Product Safety Information  
Safety Notice  
Be sure that you are completely familiar with the safe operation of this equipment. This  
equipment may be connected to other machines that have rotating parts or parts that are  
controlled by this equipment. Improper use can cause serious or fatal injury. Always  
disconnect all electrical loads before starting the generator.  
Installation and repair procedures require specialized skills with electrical generating equipment  
and liquid cooled engine systems. Any person that installs or repairs this generator must have  
these specialized skills to ensure that this generating unit is safe to operate. Contact Baldor  
service department for repairs or any questions you may have about the safe installation and  
operation of this system.  
The precaution statements are general guidelines for the safe use and operation of this  
generator. It is not practical to list all unsafe conditions. Therefore, if you use a procedure that is  
not recommended in this manual you must determine if it is safe for the operator and all  
personnel in the proximity to the generator and connected loads. If there is any question of the  
safety of a procedure please contact Baldor before starting the generator.  
This equipment contains high voltages. Electrical shock can cause serious or fatal injury. Only  
qualified personnel should attempt the start-up procedure or troubleshoot this equipment.  
This equipment may be connected to other machines that have rotating parts or parts that are  
driven by this equipment. Improper use can cause serious or fatal injury. Only qualified  
personnel should attempt the start-up procedure or troubleshoot this equipment.  
-
System documentation must be available to anyone that operates this equipment at all  
times.  
-
-
Keep non‐qualified personnel at a safe distance from this equipment.  
Only qualified personnel familiar with the safe installation, operation and maintenance  
of this device should attempt start‐up or operating procedures.  
-
-
Always stop engine before making or removing any connections.  
Always stop engine and allow it to cool before refueling.  
Responsibility When your generator is delivered, it becomes the responsibility of the owner/operator of the  
generator set to prevent unsafe conditions and operation of the equipment. Some  
responsibilities include (but are not limited to) the following:  
1. It is the responsibility of the owner/operator of this generator to ensure that this  
equipment is correctly and safely installed.  
2. It is the responsibility of the owner/operator of this generator to ensure that this  
equipment, when installed fully complies with all federal, state and local codes.  
3. It is the responsibility of the owner/operator of this generator to ensure that any person  
operating this equipment has been properly trained.  
4. It is the responsibility of the owner/operator of this generator to ensure that any person  
operating this equipment has access to all manuals and information required for the  
safe use and operation of this equipment.  
5. It is the responsibility of the owner/operator of this generator to ensure that it is properly  
maintained and safety inspected at regular scheduled intervals.  
6. It is the responsibility of the owner/operator of this generator to ensure that any person  
who has not been trained on the safe use of this equipment does not have access to  
this equipment.  
Read This Manual Thoroughly  
If you do not understand any concept, any procedure, any safety warning statement, any safety  
caution statement or any portion of this manual, contact Baldor or your nearest authorized Baldor  
representative. We are happy to make sure you understand the information in this manual so  
that you can safely enjoy the full use of this generator.  
MN2408  
Product Safety Information 1‐1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Symbols  
This symbol is shown throughout the manual to indicate a connection to ground reference point.  
Indicates a potentially hazardous situation which, if not avoided, could result in injury or death.  
Indicates a potentially hazardous situation which, if not avoided, could result in injury or death.  
Precaution Statements Used In This Manual  
There are three classifications of precautionary statements used in this manual. The most critical  
is a WARNING statement, then the Caution statement and the least critical is the Note  
statement. The usage of each statement is as follows:  
WARNING: Indicates a potentially hazardous situation which, if not avoided, could result in injury or  
death.  
Caution: Indicates a potentially hazardous situation which, if not avoided, could result in damage to  
property.  
Note:  
Additional information that is not critical to the installation or operation.  
IMPORTANT SAFETY INSTRUCTIONS  
SAVE THESE INSTRUCTIONS - This manual contains important instructions for the generator that  
should be followed during installation, operation and maintenance of the generator and battery (batteries).  
For ease of reading, the Warning statements are divided into four categories: Operation, Burn, Installation,  
and Maintenance.  
Operation  
WARNING: Never operate this generator in a manner other than as described in this manual. Operation  
in any manner not described in this manual should be considered unsafe and should not be  
attempted. Never start the engine unless you have first verified that the installation and  
operation of the generator are as described in this manual.  
WARNING: Be sure that you are completely familiar with the safe operation of this equipment. This  
equipment may be connected to other machines that have rotating parts or parts that are  
controlled by this equipment. Improper use can cause serious or fatal injury.  
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never  
breath exhaust fumes produced by a running engine. Only run the engine outdoors where  
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and  
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon  
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or  
incoherence. If you or anyone else experiences these symptoms, get out into fresh air  
immediately. Stop the engine and do not restart the engine until it has been inspected and if  
necessary repaired or reinstalled in a well ventilated area.  
WARNING: Hot exhaust gasses must never be directed toward anything that may catch fire or explode.  
WARNING: This generator must not be used on or near any forest covered, brush covered, or grass  
covered land unless the engine's exhaust system is equipped with a spark arrestor. The  
spark arrestor must be maintained in effective working order by the operator.  
WARNING: Some parts of this generator rotate during operation. Rotating parts can present extreme  
danger if clothing or body extremities are caught by the rotating part and can cause serious  
or fatal injury. Never touch a part of the generator until the engine has been stopped and all  
rotating parts are completely stopped. Also, disconnect the spark plug wires and battery  
connection to prevent accidental engine rotation during servicing.  
WARNING: Never move a generator set that is running. Loads should be connected and position secure  
before starting the engine. Hazards are caused by moving a generator set that is running.  
Continued on next page.  
1‐2 Product Safety Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operation Warning Statements Continued  
WARNING: Never connect or disconnect loads during operation. Always connect load circuits before  
starting the engine and use external branch disconnects etc. to switch loads On/Off.  
WARNING: Be sure that you understand how to stop the engine quickly in case of an emergency situation.  
Become familiar with the controls and safety systems provided with this generator set.  
WARNING: Always wear safety glasses with side shields and hearing protection when working near the  
generator.  
WARNING: Improper operation may cause violent motion of connected equipment. Be certain that  
unexpected movement will not cause injury to personnel or damage to equipment.  
WARNING: Never operate the generator set indoors or in a poorly ventilated area such as a tunnel or cave.  
Exhaust fumes are extremely dangerous to all personnel that are in or in contact with that area.  
WARNING: Never permit anyone to operate the generator without proper instructions. Be sure to keep a  
copy of this manual with the generator so that all users can be properly informed of its safe  
operation.  
WARNING: Never allow children or pets to be in the area where the generator is running. The generator  
and the equipment being powered by the generator may cause injury or death.  
WARNING: Never operate the generator unless all guards, covers, shields and other safety items are  
properly installed.  
WARNING: Do not put hands, feet, tools clothing or other objects near rotating parts such as drive shaft,  
pulley, belt etc. Rotating parts cause extremely dangerous situations because they can catch  
loose clothing or extremities and cause serious or fatal injury.  
WARNING: When operating this generator remain alert at all times. Never operate machinery when  
physically or mentally fatigued, or while under the influence of alcohol, drugs or medication.  
WARNING: Never operate the engine when the air cleaner is removed. An engine backfire can cause  
serious burns.  
WARNING: Never “jump start” a generator to start the engine. If the battery charge is insufficient to start  
the engine, charge or replace the battery and try to restart. Jump starting a battery can cause  
the battery to explode and cause severe injury or death to anyone in the area.  
WARNING: High voltage is present whenever engine is running. Electrical shock can cause serious or  
fatal injury. Never operate electrical equipment while standing in water, on wet ground or with  
wet hands, feet or shoes or while barefoot.  
WARNING: High voltage is present whenever the engine is running. Electrical shock can cause serious  
or fatal injury. Always stop engine before connecting or disconnecting power cords or  
external devices.  
WARNING: Do not smoke near generator during operation or when close to fuel source. LPG and natural  
gas fuels are flammable and can cause fire, explosions, injury or death.  
WARNING: Keep generator at least three feet away from buildings and other structures.  
WARNING: Keep generator away from flammable or hazardous materials (trash, rags, lubricants,  
explosives, paints etc.) and grass or leaf build up.  
WARNING: Keep a fire extinguisher near the generator while generator is in use. An extinguisher rated  
“ABC” by the National Fire Protection Association is appropriate.  
Burn  
WARNING: Parts of this generator are extremely hot during and after operation. To prevent severe burns,  
do not touch any part of the generator until you have first determined if the part is hot. Wear  
protective clothing and after use allow sufficient time for parts to cool before touching any  
part of the generator.  
WARNING: Do not touch the hot exhaust parts or the high voltage spark plug or coil terminals of the  
engine. Although spark plug voltages are not normally lethal, a sudden involuntary jerk of the  
hand or body part caused by contact with high voltage or a hot surface can result in injury to  
yourself or others.  
WARNING: Engine coolant is under pressure and is near the boiling point of water when engine is hot.  
Do not open the coolant system until the engine has completely cooled. Hot coolant can  
cause severe burns and other injuries. When engine is cool, coolant level can be checked.  
Continued on next page.  
MN2408  
Product Safety Information 1‐3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warning Statements Continued  
Installation  
WARNING: Installation and servicing of batteries is to be performed or supervised by personnel  
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away  
from batteries.  
WARNING: Disconnect the battery's ground terminal before working in the vicinity of the battery or  
battery wires. Contact with the battery can result in electrical shock when a tool accidently  
touches the positive battery terminal or wire. The risk of such shock is reduced when the  
ground lead is removed during installation and maintenance.  
WARNING: An open bottom stationary engine generator set must be installed over noncombustible  
materials and shall be located such that it prevents combustible materials from accumulating  
under the generator set.  
WARNING: Installation and repair procedures requires specialized skills with electrical generating  
equipment and small engine systems. Any person that installs or performs repairs must have  
these specialized skills to ensure that the generator set is safe to operate. Contact Baldor for  
installation or repairs.  
WARNING: Be sure all wiring complies with the National Electrical Code (NEC) and all regional and local  
codes or CE Compliance. Improper wiring may cause a hazardous condition and exposure to  
electrical hazards can cause serious injury or death.  
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power  
before you ensure that grounds are connected. Electrical shock can cause serious or fatal  
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be  
connected to an approved earth ground. Local codes may also require proper grounding of  
generator systems.  
WARNING: Place protective covers over all rotating parts such as drive shaft, pulley, belt etc. Rotating  
parts cause extremely dangerous situations because they can catch loose clothing or  
extremities and cause serious or fatal injury.  
WARNING: Unauthorized modification of a generator set may make the unit unsafe for operation or may  
impair the operation of the unit. Never start a generator set that has been modified or  
tampered with. Be sure that all covers and guards are properly installed and that the unit is  
safe before starting the engine. If you are unsure, contact Baldor before starting the engine.  
WARNING: When moving the generator, use reasonable caution. Be careful where you place fingers and  
toes to prevent injury “Pinch Points”. Never try to lift a generator without a hoist or lift means  
because they are heavy and bodily injury may result.  
Warning: Never connect this generator to the electrical system of any building unless a licensed  
electrician has installed an approved transfer switch. The national electrical code (NEC)  
requires that connection of a generator to any electrical circuit normally powered by means of  
an electric utility must be connected by means of approved transfer switch equipment to  
isolate the electrical circuit from the utility distribution system when the generator is  
operating. Failure to isolate the electrical circuits by such means may result in injury or death  
to utility power workers due to backfeed of electrical energy onto the utility lines.  
WARNING: Circuit overload protection must be provided in accordance with the National Electrical Code  
and local regulations.  
WARNING: Check Ground Fault Circuit Interrupt (GFCI) receptacles monthly by using the “Test” and  
“Reset” buttons.  
WARNING: Only a professional experienced technician should install a fuel supply system. LPG and  
natural gas fuels are flammable and can cause fire, explosions, injury or death. Fuel supply  
lines should be kept away from sharp objects to prevent rupture. Comply with all NFPA  
regulations and local codes for shut-off valves, regulators, fuel line type, connectors etc.  
WARNING: Have electrical circuits and wiring installed and checked by licensed electrician or qualified  
technician. Electrical shock can cause serious or fatal injury.  
WARNING: Incorrect installation of this generator set could result in property damage, injury or death.  
Connection of the generator to its fuel source must be done by a qualified professional  
technician or contractor.  
WARNING: An open bottom stationary engine generator set must be installed over noncombustible  
materials and shall be located such that it prevents combustible materials from accumulating  
under the generator set.  
Continued on next page.  
1‐4 Product Safety Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warning Statements Continued  
Battery Safety  
WARNING: Installation and servicing of batteries is to be performed or supervised by personnel  
knowledgeable of batteries and the required precautions. Keep unauthorized personnel away  
from batteries.  
WARNING: Do not dispose of battery or batteries in a fire. The battery is capable of exploding. If the  
battery explodes, electrolyte solution will be released in all directions. Battery electrolyte  
solution is caustic and can cause severe burns and blindness. If electrolyte contacts skin or  
eyes, immediately flush the area with water and seek medical attention quickly.  
WARNING: Do not mutilate the battery . The battery contains electrolyte solution which is caustic and  
can cause severe burns and blindness. If electrolyte contacts skin or eyes, immediately flush  
the area with water and seek medical attention quickly.  
WARNING: A battery presents a risk of electrical shock hazard and high short circuit current. The  
following precautions are to be followed when working on batteries:  
1. Remove watches, rings, necklaces and all other metal objects.  
2. Use tools with insulated handles.  
WARNING: The battery electrolyte is a dilute sulfuric acid that is harmful to the skin and eyes. It is  
electrically conductive and corrosive. The following precautions are to be followed when  
working on batteries:  
1. Wear full eye protection (safety glasses or goggles) and protective clothing.  
2. Where electrolyte contacts the skin, flush the area immediately with water and wash it  
off using soap and water.  
3. Where electrolyte contacts the eyes, immediately flush the eye thoroughly with water  
and seek medical attention quickly.  
4. Spilled electrolyte is to be washed down with an acid neutralizing agent. A common  
practice is to use a solution of one pound (500 grams) bicarbonate of soda to one  
gallon (four liters) of water. The bicarbonate solution is to be added until evidence of  
reaction (foaming) has ceased. The resulting liquid is to be flushed with water and the  
area dried.  
WARNING: A battery presents a risk of fire because they generate hydrogen gas. Hydrogen gas is  
extremely explosive. Never jump start a battery, smoke in the area around the battery or  
cause any spark to occur in the area around the battery. The following precautions are to be  
followed when working on batteries:  
1. Do not smoke when near batteries.  
2. Do not cause flame or spark in battery area.  
3. Discharge static electricity from body before touching batteries by first touching a  
grounded metal surface.  
Continued on next page.  
MN2408  
Product Safety Information 1‐5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Warning Statements Continued  
Maintenance  
WARNING: Before cleaning, inspecting, repairing or performing any maintenance to the generator set,  
always be sure the engine has stopped and that all rotating parts have also stopped. After  
stopping, certain components are still extremely hot so be careful not to get burned. Before  
servicing the generator set, be sure to disconnect the spark plug wires and the battery  
terminals to prevent accidental engine rotation or starting.  
WARNING: Engine coolant is under pressure and is near the boiling point of water when engine is hot.  
Do not open the coolant system until the engine has completely cooled. Hot coolant can  
cause severe burns and other injuries. When engine is cool, coolant level can be checked.  
WARNING: Before servicing the generator set, be sure to disconnect the spark plug wires and the battery  
terminals to prevent accidental engine rotation or starting.  
WARNING: Inspect all wiring frequently and replace any damaged, broken or frayed wiring or wires with  
damaged insulation immediately. Electrical shock can cause serious or fatal injury.  
WARNING: Disconnect all electrical wires and load devices from generator power outlets before servicing  
the generator. Electrical shock can cause serious or fatal injury. Always treat electrical  
circuits as if they are energized.  
WARNING: Check all fuel supply piping, and their connections monthly for fuel leaks. LPG and natural  
gas fuels are flammable and can cause fire, explosions, injury or death. If a leak is found,  
replace only with approved pipe or components.  
Caution Statements  
Caution: Avoid installing the generator set beside heat generating equipment, or directly below water  
or steam pipes or in the vicinity of corrosive substances or vapors, metal particles and dust.  
Heat can cause engine problems to develop and unwanted substances can cause rust or  
generator failure over time.  
Caution: Do not apply high voltage to windings (do not start the generator) in a moisture-saturated  
condition. Moisture can cause insulation breakdown, making it necessary to return the  
generator for repair.  
Caution: Use only original equipment or authorized replacement parts. Using the correct parts will  
assure continued safe operation as designed.  
Caution: Do not support the generator from the top of the frame or enclosure.  
Caution: Do not tamper with or change the engine speed. Engine speed is factory set to produce the  
correct voltage and output frequency.  
Caution: Never operate the engine without a muffler. The engine is designed to have the correct  
exhaust components installed and operating without these components can present a fire  
hazard, cause excessive exhaust gases and cause damage to engine. Inspect muffler  
periodically and replace if necessary.  
Caution: The Programmable Output Contacts selection must agree with the external control wiring  
prior to energizing the controller. Failure to do so may cause severe equipment damage.  
1‐6 Product Safety Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 2  
General Information  
Thank you for purchasing your Baldor Generator Set. This manual contains information you need to safely and  
efficiently install and operate your generator set. During the preparation of this manual every effort was made to  
ensure the accuracy of its contents. This manual describes only very basic engine information. A separate owner's  
manual for the engine is supplied with this unit for your use. Please refer to the engine manual for information  
relative to engine operation, maintenance, recommendations and additional safety warnings.  
Copyright Baldor © 2008. All rights reserved.  
This manual is copyrighted and all rights are reserved. This document may not, in whole or in part, be copied or  
reproduced in any form without the prior written consent of Baldor Electric Company, Inc.  
Baldor Generators have earned the reputation of being high quality and dependable. We take pride in this fact and  
continue to keep our quality standards high on our list of priorities. We are also constantly researching new  
technological ideas to determine if they could be used to make our generator sets even better.  
Baldor makes no representations or warranties with respect to the contents hereof and specifically disclaims any  
implied warranties of fitness for any particular purpose. The information in this document is subject to change  
without notice. Baldor assumes no responsibility for any errors that may appear in this document.  
Limited Warranty  
Baldor will replace or repair free of charge any part or parts of the generator of their manufacture that are defective in  
workmanship and materials for a period of time as set forth in the Warranty Period chart below. All Baldor products  
requiring warranty service shall be transported or shipped freight pre-paid to a Baldor Generator repair facility.  
Notification of the defect or problem, a description of the manner in which the Baldor generator is used, and the name,  
address and telephone number of the customer requiring warranty service must be included. Baldor is not responsible for  
removal and shipment of the Baldor product to the service center or for the reinstallation of the Baldor product upon its  
return to the customer, or any incidental or consequential damages resulting from the defect, removal, reinstallation,  
shipment or otherwise. Problems with Baldor products can be due to improper maintenance, faulty installation,  
non-Baldor additions or modifications, or other problems not due to defects in Baldor workmanship or materials. If a  
Baldor Generator repair facility determines that the problem with a Baldor product is not due to defects in Baldor  
workmanship or materials, then the customer will be responsible for the cost of any necessary repairs. Genset engines  
are covered under the engine manufacturers warranty. Proper engine maintenance is required. Any request for engine  
warranty or repair should be made directly with the engine manufacturers warranty center. See engine manufacturers  
data for applicable engine warranty periods and location of repair centers. This Limited Warranty and Service Policy  
represents Baldor's sole and exclusive warranty obligation with respect to Baldor products. Baldor's liability to a customer  
or any other person shall not exceed Baldor's sales price of the applicable Baldor product. BALDOR DISCLAIMS ALL  
OTHER EXPRESSED AND IMPLIED WARRANTIES INCLUDING THE IMPLIED WARRANTIES OF FITNESS FOR A  
PARTICULAR PURPOSE AND MERCHANTABILITY.  
Warranty Period  
Generator Series  
Portable Products (Premier, Powerchief,  
DG Series)  
Labor*  
1 Year  
Parts  
3 Years  
Towable Products (TS)  
POW'R LITE Light Towers  
1 Year or 3,000 Hours  
1 Year or 3,000 Hours  
3 Years or 3,000 Hours  
3 Years or 3,000 Hours  
Light Fixture, Lamps and Ballasts are excluded from  
any warranty coverage  
3 Years or 1,000 Hours  
3600 RPM Standby Systems  
(Some AE Models)  
1 Year or 1,000 Hours  
1 Year or 3,000 Hours  
1800 RPM Standby Systems  
(Some AE Models, DLC, GLC)  
Industrial Standby Systems  
Industrial Prime Power Systems  
International  
3 Years or 3,000 Hours  
1 Year or 1,000 Hours  
1 Year or 1,000 Hours  
1 Year or 1,000 Hours  
2 Years or 1,000 Hours  
1 Year or 1,000 Hours  
1 Year or 1,000 Hours  
*For products covered under labor coverage, travel expenses will be allowed up to 7 hours straight labor or 300 miles,  
whichever occurs first, and only applies to permanently wired and mounted products (AE, DLC, GLC, IDLC).  
You must save the purchase receipt. Proof of purchase, date, serial number and model number will be required for all  
portable and Towable products to qualify for any warranty consideration.  
A start-up inspection form/warranty registration must be completed in its entirety and submitted to Baldor Generators  
within 30 days of start-up to qualify for any warranty consideration, excluding: Portables, Towables and Light Towers.  
MN2408  
General Information 2‐1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
2‐2 General Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Important  
Be sure you are completely familiar with all Safety Instructions detailed in Section 1 of this  
manual. Do not proceed if you are unsure of any detail. Contact your Baldor Distributor, they are  
experienced and are happy to assist you and to answer your questions.  
Installation Guidelines  
The procedures presented in this manual are suggestions and it is the responsibility of the  
Owner/Operator to arrange for these procedures to be performed by licensed contractors  
according to all applicable codes including local codes for your Municipality/City/County and  
State. In addition to these suggestions, before installing your generator you should obtain the  
most up to date copies of the following documents from the National Electrical Code and other  
authorities:  
S
S
National Electric Code, Articles 230, 250, 445, 517, 700.  
National Fire Protection Association  
No. 30 - Storage, Handling and Use of Flammable Liquids.  
No. 37 - Stationary Combustion Engines and Gas Turbines.  
No. 99 - Essential Electrical Systems for Health Care Facilities.  
No. 101 - Life Safety Code No. Systems.  
No. 110 - 1985 Emergency and Standby Power Systems.  
S
S
NEMA MG1  
Local Codes applicable to Genset Installation. See your local building inspector.  
NFPA (National Fire Protection Association (617) 770-3000 (includes NEC)  
1 Batterymarch Park, Quincy, MA 02169-7471 USA  
NEMA (National Electrical Manufacturers Association) (703) 841-3200  
1300 N. 17th Street, Suite 1847, Rosslyn, VA, 22209 USA  
Site Planning  
Room Size  
Open frame generators must be protected from the environment while having good ventilation  
and cooling. Here are some considerations for planning a generator room or enclosure:  
S
S
Never use the Genset room for storage as well.  
The room must be large enough to contain the genset and all the accessories, such as  
batteries and their charging system, transfer switch and other controls, and elements of  
the cooling and fuel systems.  
S
S
S
S
A minimum of 2 feet (preferably 4 feet), must be allowed on the two sides of the engine  
for service access.  
On the generator end of the engine, allow a space equal to the length of the generator  
(generator length only, not the entire genset).  
At the front of the engine, 4 feet of clearance is preferable. Allow clearance between  
hot parts of the system (exhaust) and structural members of the building.  
Certain safety and building codes may require the genset room not to be used to house  
any other mechanical or electrical equipment.  
MN2408  
General Information 2‐3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Room Location Often a separate building located on the site away from the main building is the most simple and  
cost effective. Major considerations when housing the genset in a separate building are:  
S
S
S
S
Maintain the building at a satisfactory temperature year round (to meet applicable  
codes).  
Assure the genset is not located so far from the emergency loads that reliability is  
compromised.  
The floor's load carrying capacity must be checked and must exceed the weight of the  
genset and its associated equipment.  
Engine Cooling System  
A genset with an engine mounted radiator is the least costly to install; however, the  
room must be located in a place where sufficient radiator cooling air can be brought  
into and exhausted from the room.  
S
S
Exhaust System  
The exhaust system must minimize exhaust restriction. Exhaust restriction must be  
limited to 3 in. Hg (76 mm Hg) maximum, to ensure proper engine operation. The  
exhaust system should be as short and have as few bends as possible.  
Room Air  
If the genset is cooled with an engine mounted radiator, and sufficient air is brought into  
and exhausted from the room to satisfy the radiator cooling requirements and the  
combustion air requirements, the room will not overheat when the genset is running.  
If a remote mounted radiator or a heat exchanger is used, and adequate air is  
circulated through the room to keep it at a reasonable temperature, there will be  
adequate air for combustion.  
S
S
Fuel Tanks (Diesel Only)  
Locate the fuel storage tank as near the genset as possible. This will minimize the cost  
of fuel system installation and will maximize fuel system reliability.  
Controls and Transfer Switch  
Locate the control switch gear as close to the emergency loads and the genset as  
practical. This will minimize the chances that a failure of the power line to the  
emergency load will go undetected. In locating the switchgear, accessibility for service  
and maintenance must be considered.  
S
Genset Noise  
Internal combustion engines produce noise, so the room should be located away from  
occupied buildings. In addition the genset room can be treated to reduce noise  
transmission. In locating the genset room, both engine, fan and exhaust noise must be  
considered.  
If noise within the genset room, or noise transmitted to the surrounding parts of the  
building are a concern, then the room must be made large enough to allow for  
installation of noise attenuating walls and noise absorbing walls.  
Light weight concrete blocks filled with sand or special “sound block” concrete blocks  
are commonly used. Noise attenuating, tight fitting windows and doors also help reduce  
noise transmission to the rest of the building.  
A double-walled room should be considered. Vibration isolators under the genset rails  
will also reduce the transmission of noise through the floor.  
S
Code Requirements  
Building and safety codes deal with engine location. These requirements are  
concerned with fire rated walls, a location that minimizes the possibility of damage to  
the genset and interruption of the emergency system due to storms, foods, fire,  
vandalism, etc.  
Codes often deal with the need to maintain certain temperatures in the genset room  
and with fuel system location. The most important codes in the USA are the National  
Fire Protection Association Code Numbers 99 and 110, but local codes must also be  
observed.  
2‐4 General Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Foundation Design  
WARNING: An open bottom stationary engine generator set must be installed over noncombustible  
materials and shall be located such that it prevents combustible materials from accumulating  
under the generator set.  
Foundation Checklist  
A. Evaluate if a separate, isolated foundation is required for the application.  
B. Observe local codes on soil bearing capacity freezing and thawing.  
C. Design the separate foundation for the genset and specify the appropriate concrete mix.  
D. Determine if the application requires vibration isolators and if so, order as a factory option.  
The foundation must be strong enough to support the weight of the genset and its associated  
equipment, must prevent any deflection of the genset base and absorb vibration produced by the  
rotating and reciprocating masses.  
Setting The Genset On An Existing Concrete Floor Slab  
S
S
S
S
S
If an existing floor is used, the floor slab must be strong enough to carry 1.50 times the  
genset wet weight (including coolant and oil) to accommodate dynamic loads.  
The actual mounting arrangement (ie., surface area in contact with the floor) will  
determine the compressive strength required.  
The genset should be securely fastened to the floor slab with expansion anchors that fit  
the mounting holes shown on the genset installation diagram.  
For installations not expected to be permanent, elastomer pad with non-slip surface  
placed between the base and the floor will also prevent movement.  
Any floor/slab surface should be as flat as possible to prevent sub-base deflection.  
Vibration Isolators  
S
Mounting to the pad, will result in overall reduced motion on other parts of the genset.  
The trade-off is that slightly more vibration is transmitted to the structure.  
S
A more common practice when mounting to a concrete pad is to use vibration isolators.  
The two most common types of vibration isolators are steel spring and elastomer pad.  
The primary purpose of vibration isolators is to reduce the noise and vibration which  
would be transmitted from the genset to the foundation or supporting structure.  
S
A simple and effective method of mounting and applying pad type isolators is to place  
non-skidding type isolation pads directly between the sub-base and floor.  
The number of pads required will be determined by the load bearing capability of the  
pads and the genset's weight.  
Figure 2‐1 Typical Installation of Spring Type Isolator  
MN2408  
General Information 2‐5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
S
Steel spring isolators are a very effective and commonly used. Steel spring isolators  
are typically 95-98% efficient (reduces the transmitted vibration 95-98%) while a pad  
type can be 75-88% efficient. Spring isolators also level the genset sub-base in the  
event the foundation pad is not perfectly level.  
Spring steel isolators offer the highest level of vibration isolation, however higher levels  
of vibration (although not detrimental) may be seen on some areas of the genset when  
mounted on steel springs, due to the (almost) total isolation from the foundation. The  
base of most steel spring isolators contains a non-skid pad. The base should be  
isolator manufacturer.  
A common practice is to pour a concrete pad directly on top of the floor slab and to  
mount the genset on this pad. The purpose of the pad is to facilitate cleaning around  
the genset and to provide a more level base. When using this method, floor strength  
must support the pad and the genset. The pad should be at least 6in (150mm) thick  
and extend beyond the genset in all directions 12in (300mm).  
Weight Of The Genset  
The dry weight of the entire genset is shown on the Generator Set Specification Sheet. The wet  
except in critical situations.  
Figure 2‐2 Approximate Weight vs. kW Output  
2‐6 General Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Designing An Isolated Foundation  
If the genset cannot be mounted directly on a floor slab, or if it is desirable to isolate it from the  
floor slab, then a separate foundation slab must be designed.  
A massive concrete foundation is not required. Outside dimensions of the foundation should  
exceed the outside genset dimensions by 12in (300mm).  
For single genset installation, the foundation weight should be a minimum of 1.50 times the  
genset wet weight.  
For multiple genset installation, the foundation weight should be a minimum of 2.0 times the  
genset wet weight.  
foundation and generator set. The soil load bearing capacity under the foundation must equal or  
exceed the load from the foundation and genset. If it does not, then a footing, as shown in Figure  
Figure 2‐3 Calculate Soil Bearing Load (SBL) Capacity  
Figure 2‐4 Typical Footing on Foundation in Soil With Low Soil Load Bearing Capacity  
MN2408  
General Information 2‐7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table 2‐1 Approximate Load Bearing Capacities of Various Soil Types  
Safe Bearing Capacity  
Soil Type  
lb per ft2  
50,000 - 200,000  
20,000 - 30,000  
16,000 - 20,000  
10,000 - 20,000  
10,000 - 12,000  
8,000 - 10,000  
8,000 - 10,000  
8,000 - 10,000  
6,000 - 8,000  
4,000 - 8,000  
2,000 - 4,000  
2,000  
kilo Pascals  
Hard Rock - Granite etc.  
Medium Rock - Shale etc.  
Hardpan  
2,395 - 9,576  
958 - 1,436  
766 - 958  
479 - 958  
479 - 575  
383 - 479  
383 - 479  
383 - 479  
287 - 383  
192 - 383  
96 - 192  
Soft Rock  
Compacted Sand and Gravel  
Hard Clay  
Gravel and Coarse Sand  
Loose, Medium and Coarse Sand  
Compacted Fine Sand  
Medium Clay  
Loose Fine Sand  
Soft Clay  
96  
bearing capacity of the soil under the foundation is not known.  
Caution: Check the local building codes for load bearing capacity requirements.  
Caution: If the soil is subject to freezing and thawing, the foundation must be extended below the frost  
line. Check the local building codes.  
S
S
Reinforce the foundation with No. 8 gauge steel wire mesh placed horizontally on  
6in (150mm) centers. As an alternative, use No. 6 re-bars on 12in (300mm) centers  
horizontally. Minimum cover over the bars should be 3in (76mm).  
Suggested concrete mixture by volume is 1 part cement, 2 parts sand, and 3 parts  
aggregate. Maximum slump of 4in (100mm) and a 28-day compressive strength of  
3000 psi (20,600 kPa).  
S
S
The size of the bolts holding the sub-base to the foundation should be sized to fit the  
mounting holes shown on the Installation Diagram.  
Three-inch (76mm) iron pipe sleeves should be placed around the bolts in the  
foundation to allow for any mislocation of the bolts after the foundation hardens. “J” or  
“L” type bolts are recommended for the foundation bolts.  
S
After the foundation is cured and the genset is located, the sleeves are filled with grout.  
Figure 2‐5 Typical Foundation Installation  
2‐8 General Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Exhaust System  
Exhaust Checklist  
A. Exhaust outlets are not located upwind or near any building air intakes.  
B. Flexible piping section is used at engine exhaust outlet.  
C. Exhaust piping material is adequate for expected service.  
D. Exhaust piping sizing is adequate to prevent back pressure.  
E. Exhaust piping components are insulated as necessary to prevent operator burns and reduce  
pipe radiant heat losses.  
F. Pipe sleeves or fire proof materials are used where exhaust pipe passes through building  
materials as per local and state codes.  
G. Exhaust pipe includes rain cap or is horizontal.  
The purpose of the exhaust system is to safely discharge the engine combustion products into  
the atmosphere outside the building. A silencer should be installed in the exhaust system to  
reduce noise levels. Compliance with local noise codes is always required.  
Level Of Attenuation  
In general, manufacturers offer three grades of silencers: industrial, residential, and critical. In  
most cases, these grades are comparable from make to make. However, attenuation curves for  
the silencer should be checked to assure the desired level of silencing is met.  
System Placement  
By this time, the general genset placement within the room or building has been decided. The  
routing of the exhaust system should be as direct as possible to the building exterior.  
WARNING: Never allow the exhaust outlet to be positioned so that the exhaust gases are directed  
towards any openings or air entry routes (doors, windows, vents, etc...) of an occupied  
building. When discharging the hot exhaust gases out of the building do not direct them  
towards anything that could catch fire or explode.  
For aesthetic reasons, consider exhaust placement in relation to the building. Over a period of  
time, exhaust gas carbon deposits will tend to accumulate on any nearby wall or structure.  
Attention must also be given to exhaust noise in selecting placement of the exhaust system.  
Multi-Engine Installations  
Caution: Do not connect multi-engine exhaust systems together. Each engine must have its own  
exhaust system for proper operation.  
Exhaust gases from an operating engine will migrate back through a non-operating engine and  
cause a hydraulic lock. This may interfere with starting of the second engine. The migrating  
gases will also tend to turn the turbos which are not being provided lubrication if the engine is not  
running. The use of check valves in the exhaust system are discouraged due to their tendency  
to “stick”.  
Exhaust Manifold  
There are two exhaust manifold types. Dry type which is standard and the optional water cooled.  
The dry type is simply exposed to the surrounding air and becomes very hot. Shields, insulating  
wraps, or other types of guards can be used to limit operator contact with the hot surfaces. This  
practice is common where engine room size is small, creating cramped conditions.  
Water cooled exhaust manifolds are not available on all engine models. This type manifold has  
passages through which engine coolant is circulated to remove heat from the manifold surface. It  
also will help protect the operator from contact with the hot manifold surface. This will reduce the  
amount of heat that is radiated by the engine to the surrounding air by approximately 20%. In  
addition, this type manifold significantly increases the amount of heat the cooling system must  
dissipate. Marine and Mining Safety Administration (MSA) codes may require water cooled  
manifolds in all genset installations. If you are in doubt on your particular application, consult your  
Baldor Distributor.  
Exhaust Gas Restriction  
The maximum allowable back pressure, or system restriction, is 3 inches of mercury. If this back  
pressure is exceeded, the air-fuel ratio is reduced due to incomplete scavenging of the cylinders,  
fuel economy and power output is reduced, engine life is reduced and exhaust temperatures and  
smoke levels increase. Any restriction of the exhaust gas reduces horsepower. Take every  
precaution to reduce restriction. Proper design and installation will provide safe genset operation.  
It is essential that all engine exhaust systems by designed with the least possible restriction to  
MN2408  
General Information 2‐9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 2‐6 Exhaust System Calculations  
Exhaust Piping  
Caution: The weight of the exhaust system must never be imposed on the turbo-charger outlet.  
Damage to the turbo-charger and other components may result.  
An exhaust system must withstand the vibration and thermal expansion that they are subjected  
to, yet supported well enough to remain independent of the engine.  
The most common method of providing flexibility is with the use of bellows type flexible piping.  
This piping component allows lateral and linear movement of the piping system without  
subjecting fixed components to excessive stress. A minimum of 12 inches of flexible connection  
must be provided at the engine exhaust manifold to allow for thermal expansion and vibration. If  
the engine is to be mounted on spring type vibration isolators, increase the length to 24 inches.  
This component can be specified to be provided by your Baldor distributor. Flexible pipe should  
never be used for pipe bends or to cure misalignment problems.  
Exhaust piping systems may be supported by a wide variety of methods to long as the system  
remains flexible, and capable of withstanding thermal expansion.  
The material most commonly used for straight runs and elbows in exhaust systems is Schedule  
40 black iron. If hanging weight is a problem, other materials may be used. Galvanized piping  
should never be used in exhaust system. Where exhaust piping passes through combustible  
Figure 2‐7 Exhaust Pipe Thimble Installation  
Rain Protection  
Moisture entering the engine through an exhaust system can cause extensive damage. Exhaust  
2‐10 General Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Transfer Switch  
Transfer Switch Checklist  
A. Locate transfer switch in a clean, dry place, near the emergency load.  
B. Provide a circuit breaker between the genset and the transfer switch.  
C. Put a flexible connection between the conduit and genset.  
D. Observe applicable codes in wiring-in the transfer switch and genset.  
The transfer switch connects the genset to the emergency power system. The emergency power  
system may include several gensets and several transfer switches. Typically, the genset is wired  
Figure 2‐8 Typical Emergency power System Installations  
Multiple Gensets can be arranged either in parallel or separately connected to dedicated  
transfer switches for loads that have different levels of priority. A typical multiple genset  
installation is shown for NFPA 110 Level 1 and Level 2 emergency power circuits and a priority  
control to select the appropriate transfer switch.  
Wattmeters should be installed on each genset so load sharing can be checked. The control  
system should include an automatic paralleling control. Paralleling identical gensets is not  
difficult, but paralleling dissimilar sets can cause load sharing problems. When designing an  
installation that includes the paralleling of dissimilar generators, contact your nearby Baldor  
Distributor.  
Transfer Switch Location  
The transfer switch location is important and key considerations are:  
1. Locate the transfer switch as close to the emergency load as practical to avoid  
interruptions of the emergency power system due to natural or man-made disasters, or  
to equipment failures. Consider several small transfer switches instead of one large  
one to increase reliability.  
2. Locate the transfer switch in a clean, dry, well ventilated location, away from excessive  
heat. When the ambient air is above 104 °F (40 °C), fuses and circuit breakers must be  
derated. Allow adequate working space around the transfer switch.  
3. A circuit breaker (or fuses) should be installed in the line between the generator and  
the transfer switch. Baldor Gensets are available with properly sized circuit breaker  
built into the generator control through 1200 amp breakers. The circuit breaker can be  
separately mounted. In the case of very large circuit breakers, a separate floor  
mounted circuit breaker is easier to wire up than a wall mounted breaker.  
4. Install power and control wires in separate solid conduit with flexible sections at the  
genset. The flexible sections prevent vibration from damaging the conduit. All power  
conduits from the genset must contain all three phases.  
5. Never install control wires in the same conduit as power conductors.  
MN2408  
General Information 2‐11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6. Conduit, wire, circuit protective device sizes, insulation etc. must conform to applicable  
local and national codes and regulations.  
7. Be certain to seal around conduits that penetrate the walls of the genset room to  
reduce the amount of noise that is transmitted to the surrounding areas of the building  
and maintain site fire code rating.  
Battery Starting System  
This section describes the battery starting system (nominal 12 volt rating of the battery supply)  
for the engine, battery charger, and precautions to take if the ambient temperature is expected to  
be below 70 °F (20°C).  
WARNING: If batteries are not mounted in the battery rack supplied with the genset, protect batteries  
from vibration and do not locate them near a source of flame or spark. A battery presents a  
risk of fire and explosion because they generate hydrogen gas. Hydrogen gas is extremely  
explosive. Never jump start a battery, smoke in the area around the battery or cause any  
spark to occur in the area around the battery.  
Battery Location  
Locate batteries as close as possible to the genset to minimize starting circuit resistance, see  
batteries on a level rack away from dirt and liquids. Allow space for servicing (checking water  
level and level of charge). Cold ambient temperature at the battery location substantially reduces  
the battery output.  
Figure 2‐9 Battery Starting System  
Battery Size  
The ability to start the engine depends upon battery capacity, ambient temperature and coolant  
and oil temperatures. The Engine/Generator Set Data Sheet lists minimum recommended battery  
capacity.  
Battery capacities decrease as ambient temperatures decrease so it is important to specify  
batteries with the appropriate CCA rating at a temperature no higher than the minimum ambient  
temperature for the application.  
2‐12 General Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Battery Charger  
An engine mounted alternator charges the batteries during engine operation. Standby gensets  
should include a solid state battery charger that is connected to utility power so the battery is  
charged continuously while the genset is not running. The battery charger should be connected  
to the utility power emergency circuit. The batteries on prime power gensets are charged by the  
engine mounted alternator, if equipped.  
The output of the battery charger or the belt driven alternator must be connected directly to the  
battery or to the battery terminals on the starter to prevent the electronic governor from acting  
erratically. Make control connections to the genset control using a conduit with a flexible section  
at the genset to avoid damage due to genset vibrations.  
Battery Cables  
The wire size (wire gauge) of the cables connecting the starter to the batteries must be large  
enough to ensure proper voltage at the engine starter motor during cranking. The total cranking  
circuit resistance includes the resistance of the cables from the starting motor to the battery and  
the resistance of all relays, solenoids, switches, and connections. The resistance of various sizes  
cable size, the resistance of each connection can be taken as .00001 ohms and the resistance of  
of a typical cranking circuit resistance calculation.  
Figure 2‐10 Typical Battery Cable Calculations  
MN2408  
General Information 2‐13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
2‐14 General Information  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 3  
Receiving & Installation  
Receiving & Inspection When you receive your generator, there are several things you should do immediately.  
1. Observe the condition of the shipping container and report any damage immediately to  
the commercial carrier that delivered your system.  
2. Verify that the part number of the system you received is the same as the part number  
listed on your purchase order.  
3. If the system is to be stored for several weeks before use, be sure that it is stored in a  
location that conforms to published storage temperature and humidity specifications.  
Lifting the Generator When lift or hoist equipment is used to lift the generator and move it to position, be careful not  
to contact overhead wires or other obstacles. Be sure lift or hoist equipment has appropriate tires  
for the terrain to avoid becoming stuck or tipping over. If the shipping pallet is intact, use a fork lift  
to move the generator. If the shipping pallet has been removed, use two steel pipes through the “Lift  
Point” holes to lift the generator. See Figure 3‐1.  
Figure 3‐1 Generator Lifting  
Height  
To lift the generator, always use spreader bars,  
chains, eyehooks and other hardware that is of  
sufficient strength to lift at least three times the  
Lift  
Point  
weight of the generator.  
Length  
Width  
Lift Point  
Physical Location The mounting location of the system is important. It should be installed in an area that is  
protected from direct harmful gases or liquids, dust, metallic particles, shock and vibration.  
It should be installed in an outdoor location so the exhaust fumes are vented to the atmosphere.  
When the Generator is installed outdoors  
The factory installed enclosure is designed to keep out undesirable weather elements while  
providing cooling and ventilation.  
When the Generator is installed in a building it is essential to provide:  
1. Adequate control and exhausting of the heated air.  
2. An adequate and constant supply of incoming cooling air.  
3. Adequate control and discharge of the engine's hot exhaust gases.  
4. Adequate ventilation of the building when the engine shuts down.  
MN2408  
Receiving & Installation 3‐1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WARNING: An open bottom stationary engine generator set must be installed over noncombustible  
materials and shall be located such that it prevents combustible materials from accumulating  
under the generator set.  
Several other factors should be carefully evaluated when selecting a location for installation:  
1. For effective cooling and maintenance, the system should be mounted on a flat,  
smooth, noncombustible level surface. A concrete pad is ideal and provides a secure  
installation.  
2. Installation should prevent water levels from reaching the generator. Drainage must be  
adequate to keep concrete pad free from standing water.  
3. Installation should prevent obstructions by buildup of leaves, grass, sand, snow, etc. If  
these items pose a problem, consider building a small fence or other break to protect  
the unit from accumulation of debris.  
4. Installation should place the generator as close as possible to the fuel supply and  
transfer switch.  
5. At least twenty-four (24) inches clearance must be provided on all sides for air flow.  
6. Access must be provided to allow the enclosure covers to be opened or removed for  
service and maintenance.  
7. Maximum Ambient temperature is 122°F (50°C).  
Figure 3‐2 Generator Mounting  
Fuel Stub Up  
GLC125 ONLY  
Large Exhaust Area  
For all models with enclosure  
B1  
B
Fuel Stub Up  
Electrical Stub Up  
A3  
A1  
A2  
A2  
F1  
F2  
A
A
Table 3‐2 Mounting Dimensions  
A3  
Generator  
A
A
(Weather.) (Sound)  
A
A1  
A2  
B
B1  
F1  
F2  
(Open)  
60.25  
78.0  
GLC10-25  
GLC30-45  
GLC60-65  
GLC80-105  
72.0  
78.0  
88.0  
88.0  
72.0  
108.0  
118.0  
118.0  
4.0  
26.1  
33.0  
38.0  
38.0  
11.75  
30.0  
30.0  
30.0  
31.5  
44.0  
44.0  
44.0  
30.5  
42.5  
42.5  
42.5  
17.6ꢀ  
34.2ꢀ  
6.0  
6.0  
6.0  
21  
58  
88.0  
23  
63  
88.0  
27  
68  
A
d
d
1
1
.
7
5
i
n
f
o
r
W
e
a
t
h
e
r
&
S
o
u
n
d
A
t
t
e
n
u
a
t
e
d
e
n
c
l
o
s
u
r
e
s
.
Table 3‐3 Stub Up Detail  
Stub Up Area  
Generator  
Fuel Connection (NG or LP Vapor)  
3/4” NPT, C/L is 3” above base bottom.  
3/4” NPT, C/L is 12” above base bottom.  
1- 1/4” NPT, C/L is 12” above base bottom.  
1- 1/4” NPT, C/L is 12” above base bottom.  
Electrical  
Fuel  
GLC10-25  
GLC30-45  
GLC60-65  
GLC80-105  
6.25” x 5”  
15” x 6”  
21” x 6”  
16” x 6”  
5” x 18”  
18”x 6”  
20” x 6”  
21” x 6”  
3‐2 Receiving & Installation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Secure the Generator  
Six (eight for the GLC125) mounting bolts in the base frame secure the generator to the shipping  
pallet. Remove these bolts, lift the generator and remove the shipping pallet. Secure the  
generator to the concrete pad using 3/8anchor hardware (not provided) in the base frame  
generator mounting frame.  
Engine Cooling A sufficient flow of clean, cool air is required for combustion and to dissipate the heat produced  
by the engine. Approximately 60% of the heat value of the fuel used is given off as heat (cooling  
air and exhaust).  
The air that will cool the engine must be brought in from outside the building. A sufficient air-flow  
of rate “Cubic Feet per Minute” (CFM) will allow the incoming fresh air to cool the engine. This  
requires a power ventilation system of sufficient CFM to be located at the highest possible point  
of the building to exhaust hot air and draw in cool fresh air.  
Note: The exhaust fan must not be located where it could easily become blocked by leaves,  
snow, water, debris, etc.  
It is recommended that the cool air intake have at least three (3) times the cross-sectional area  
of the power ventilation system. It is also recommended that the cool air intake be located as  
close as possible to the top of the generator set.  
The exhaust fan must be connected to the AC power terminals of the generator set so that when  
the generator set starts it will provide immediate cooling air flow. The fan will operate until the  
generator set stops. To test the ventilation system, do the following:  
Ventilation Test  
1. Place a thermometer as close to the cool air intake of the engine's blower housing as  
you can without allowing the thermometer to touch any material surface.  
2. Place another thermometer outside of the building or compartment in the open air  
(Keep the thermometer out of direct sunlight or any other heat sources).  
3. Run the engine under maximum load for an extended period of time (at least one hour).  
4. The temperature difference between the two should not exceed 15 degrees F.  
Note that opening any door, window or other opening can upset the air-flow pattern and result in  
a significant reduction in the cooling air-flow across the generator set. This may result in  
overheating, fire, or explosion.  
MN2408  
Receiving & Installation 3‐3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Hot Exhaust Gasses  
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never  
breath exhaust fumes produced by a running engine. Only run the engine outdoors where  
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and  
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon  
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or  
incoherence. If you or anyone else experiences these symptoms, get out into fresh air  
immediately. Stop the engine and do not restart the engine until it has been inspected and if  
necessary repaired or reinstalled in a well ventilated area.  
WARNING: Hot exhaust gasses must never be directed toward anything that may catch fire or explode.  
It is extremely important to discharge engine exhaust gasses away from the engine and out of  
the building. If these gasses remain in the cylinder, poor performance or eventual engine damage  
may result. This condition results from excessive back-pressure, which could be caused by any  
one or a combination of the following conditions:  
1. Exhaust pipe too long or the diameter is too small.  
2. Excessive number of sharp bends in the exhaust system.  
3. Obstruction in the exhaust system.  
Backpressure must not exceed 20” of water column.  
The direction of the discharged hot air and hot exhaust gases is important as they have the  
potential to create brown spots on the lawn or adjacent structures. In extreme cases this  
extremely hot air could cause dried grass or other debris to ignite.  
Exhaust lines should be as short and straight as possible. Long pipe lengths and elbows tend to  
resist the flow of gases and accumulate carbon deposits. Each pipe fitting and elbow will further  
restrict the exhaust flow.  
Guidelines for Exhaust System  
1. If you are using a remote muffler it should be mounted as close to the engine as  
possible, since it will clog with carbon if it's operating temperature is too low.  
2. If you are using a remote muffler a flexible coupling of 12” or more must be installed  
between the exhaust line and the manifold to absorb the engine's vibration. However,  
a short, solid section of pipe between 6” and 8” long should be placed between the  
connection of the manifold and the flexible coupling. This nipple will reduce the  
possibility of the hot gases burning up the flexible coupling.  
3. It is extremely important that you do not allow the hot exhaust gases to re-circulate into  
the engine's cooling air intake.  
4. Water is one by-product of combustion and is present in the exhaust pipes or muffler.  
This water must be kept from draining back into the engine. This can be done by  
slanting the horizontal section of the exhaust system piping downward slightly, away  
from the engine. A water trap consisting of a tee extension with a drain cock should  
also be provided. This water trap should be located between the flex coupling and the  
muffler, but as close to the engine as possible on a horizontal section of the exhaust  
piping.  
5. It is also recommended that an exhaust rain cap be used whenever it is possible that  
rain could get into the system. This will help to prevent corrosion and damage to the  
exhaust system and engine.  
6. The exhaust system is subject to the engine's vibration and it must therefore be solidly  
secured to reduce mechanical stress and the potential for breakage.  
7. The engine's exhaust system is the hottest component of the installation and extreme  
care and considerations must be given to it.  
3‐4 Receiving & Installation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8. As much of the exhaust piping as possible should be located near the power ventilation  
exhaust. This will reduce the radiant exhaust heat inside the building.  
9. Keep all fuel and its associated piping away from all components of the engine exhaust  
system.  
10. After the exhaust system is installed it should be inspected on a regular basis to assure  
there are no toxic exhaust gas leaks. In some areas this inspection may be provided by  
your local public service.  
11. A carbon monoxide tester may be installed to detect the presence of the deadly gas  
during times when you are in the building with the engine running (during testing or  
maintenance).  
WARNING: Never allow the exhaust outlet to be positioned so that the exhaust gases are directed  
towards any openings or air entry routes (doors, windows, vents, etc...) of an occupied  
building. When discharging the hot exhaust gases out of the building do not direct them  
towards anything that could catch fire or explode.  
WARNING: Exhaust fumes/gases are extremely dangerous and can cause severe illness or death. Never  
breath exhaust fumes produced by a running engine. Only run the engine outdoors where  
ventilation is plentiful. Exhaust gases contain carbon monoxide, a colorless, odorless and  
extremely dangerous gas that can cause unconsciousness or death. Symptoms of carbon  
monoxide poisoning include: dizziness, nausea, headaches, sleepiness, vomiting or  
incoherence. If you or anyone else experiences these symptoms, get out into fresh air  
immediately. Stop the engine and do not restart the engine until it has been inspected and if  
necessary repaired or reinstalled in a well ventilated area.  
MN2408  
Receiving & Installation 3‐5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation  
The generator is completely assembled, tested and adjusted at the factory before it is shipped to  
you. The procedures presented in this manual are suggestions and it is the responsibility of the  
Owner/Operator to arrange for these procedures to be performed by licensed contractors  
according to all applicable codes including local codes for your Municipality/City/County and  
State. External connections required at the time of installation are:  
1. Fuel System.  
2. Electrical Connections - power wiring (optional transfer switch) and control wiring.  
3. Battery (not included).  
4. Ground Connection.  
After installation, the post installation checks must be performed prior to starting the engine.  
After these checks have been performed and the system operation is verified to be good, refer to  
Section 5 Maintenance for periodic checks that must be performed at scheduled intervals to  
ensure continued operation with minimal problems.  
Fuel Connections  
Fuel selection is Natural Gas or LPV (Liquid Propane Vapor). If natural gas supply is used,  
follow the “Natural Gas Connections” procedure. If LPV supply is used, follow the “LP Vapor  
Table 3‐4 Fuel Consumption Natural and LPV  
Model  
Model  
Fuel Consumption at 100% load  
cubic ft/Hr (cubic m/Hr)  
Fuel Consumption at 100% load  
cubic ft/Hr (cubic m/Hr)  
Natural Gas  
348(9.9)  
LP Vapor  
145.2(4.1)  
189.3(5.4)  
233.4(6.6  
277.5(7.9)  
197(5.6)  
Natural Gas  
584(16.5)  
731(20.7)  
780(22.1)  
1012(28.7)  
1133(32.1)  
1651(46.8)  
LP Vapor  
242(6.9)  
269(8.2)  
321(9.1)  
425(12)  
GLC10  
GLC15  
GLC20  
GLC25  
GLC30  
GLC35  
GLC45  
GLC50  
GLC60  
GLC80  
GLC100  
GLC125  
438(12.4)  
528(15.0)  
618(17.5)  
526(14.9)  
575(16.3)  
487(13.8)  
852(16.5)  
240(6.0)  
General Considerations  
1. A generator set needs the engine to deliver 2 hp of energy to the alternator for every  
1000 watts of electric output power (example: an 8000 watt generator needs the engine  
to deliver 16 hp of energy to the generator end).  
2. An engine needs 10,000 BTU's of fuel energy per horsepower of engine power to  
provide a sufficient supply of fuel (example: a 16 Hp engine needs 160,000 BTU's of  
fuel energy for it to work properly). This fuel must be supplied to the regulator on the  
generator set at a pressure of 6 oz (11 inches of water column). To achieve this 6 oz.  
pressure in a L.P. System, you will normally have to reduce the tank pressure by  
means of a primary regulator or a regulator system of 2 or more regulators.  
3. There are 2,516 BTU's in one cubic foot of Propane (LP Fuel).  
There are 1,096 BTU's in one cubic foot of Natural Gas.  
4. There are 36.39 cubic feet in one gallon of Propane.  
There are 57.75 cubic feet in one gallon of Natural Gas.  
5. There are 8.58 cubic feet per pound of Propane.  
There are 23.56 cubic feet per pound of Natural Gas.  
6. When installing the piping for the gaseous fuel supply please refer to the pipe chart in  
the necessary amount of fuel.  
7. If copper tubing is used, it should be “K” or “L” having a minimum wall thickness of  
0.032 inches. Black Iron Pipe is recommended but follow building codes for your area.  
The following pamphlets are available from:  
National Fire Protection Association (NFPA) P.O. Box 9101 Quincy, MA 02269  
No. 37 - Combustion Engines  
No. 54 - Gaseous Appliances and piping  
No. 58 - Storage and handling LPV  
3‐6 Receiving & Installation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Example: Determining Pipe Size for Natural Gas  
A generator has a 16Hp engine 60 feet from the supply.  
Determine the supply pipe size for Natural Gas fuel.  
16 x 10,000 = 160,000 BTU's / per hour for proper operation.  
160, 000  
1, 096  
Ă +Ă 146ĂcubicĂfeetĂperĂhour.  
Natural Gas Connections  
The incoming pressure must be 11 inches water column (6 oz. pressure).  
Table 3‐5 Natural Gas Flow Rate (Cubic Feet per Hour) per Pipe Length  
Iron Pipe Size  
Pipe  
Length  
(Feet)  
15  
1/2″  
3/4″  
1″  
1- 1/4″  
1- 1/2″  
2″  
2- 1/2″  
3″  
4″  
6″  
8″  
73  
50  
41  
37  
165  
115  
95  
332  
232  
191  
166  
149  
137  
126  
115  
105  
96  
722  
515  
418  
366  
332  
298  
274  
260  
233  
216  
197  
183  
171  
164  
1174  
818  
673  
587  
524  
433  
2386  
1712  
1419  
1241  
1077  
962  
3704  
2646  
2213  
1924  
1684  
1501  
1376  
1289  
1174  
1077  
991  
6253  
4521  
3752  
3319  
2886  
2597  
2357  
2213  
2011  
1876  
1712  
1616  
1520  
1433  
13352  
9331  
7600  
6542  
5772  
5291  
4906  
4618  
4185  
3848  
3559  
3357  
3127  
2886  
37229  
26330  
22462  
18595  
16652  
15200  
14064  
13160  
11775  
10736  
9937  
30  
45  
53728  
43867  
37999  
33959  
31025  
28715  
26859  
24050  
21934  
20298  
18990  
17903  
16998  
60  
83  
75  
74  
90  
67  
105  
120  
150  
180  
210  
240  
270  
300  
63  
885  
404  
366  
337  
308  
289  
274  
260  
827  
750  
693  
89  
635  
596  
933  
9235  
558  
875  
8658  
524  
827  
8177  
Note: Almost all operation problems are related to the installation techniques used. Do Not  
guess, be sure pipe size is adequate for required flow rate.  
1. Connect the proper size gas pipe at the Inlet Connection to the Fuel Lock Solenoid.  
the required flow rate and length of pipe. Refer to Table 3‐5 for pipe size. Be certain  
that all connections are sealed and no leaks are present. The installer must ensure  
that all gas connections comply with all building codes.  
2. Verify Fuel Supply Pressure  
Prior to initial operation of generator, verify that fuel system pressure is 11Water  
Column (6 oz. pressure) and fuel pipe sizes comply with Table 3‐5.  
3. Proceed to Electrical Connections.  
Figure 3‐3 Gas Line Connections  
Air Cleaner  
Carburetor  
External Supply Piping (by installer)  
U.L. requires a second shutoff valve and regulator to be installed in the supply piping to  
control the gas supply to the generator.  
Solenoid, Fuel Lock  
Inlet Connection  
Supply Piping  
To Inlet  
Connection  
Mounting Bracket  
Additional Regulator  
(11 - 14” water column pressure)  
Additional Valve  
(Safety Shutoff Valve)  
MN2408  
Receiving & Installation 3‐7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Example: Determining Pipe Size for LPV  
A generator has a 16Hp engine 60 feet from the supply.  
Determine the supply pipe size for Natural Gas fuel.  
16 x 10,000 = 160,000 BTU's / per hour for proper operation.  
160, 000  
2, 516  
Ă +Ă 63.5ĂcubicĂfeetĂperĂhour.  
LP Vapor Connections (vapor withdrawal only)  
The LPV connections should only be made if your generator is setup to run on LPV. If it is setup  
to run on Natural Gas, contact your Baldor representative and do not continue with installation.  
The incoming pressure must be 11 inches water column (6 oz. pressure).  
Table 3‐6 LP Vapor Flow Rate (Cubic Feet per Hour) per Pipe Length  
Iron Pipe Size  
Pipe  
Length  
(Feet)  
15  
1/2″  
3/4″  
1″  
1- 1/4″  
1- 1/2″  
2″  
2- 1/2″  
3″  
4″  
6″  
8″  
48  
33  
27  
24  
109  
76  
63  
54  
49  
44  
41  
218  
153  
126  
110  
98  
475  
339  
275  
241  
218  
196  
180  
171  
153  
142  
130  
120  
113  
108  
772  
538  
443  
386  
345  
310  
285  
266  
241  
222  
202  
190  
180  
171  
1570  
1127  
934  
817  
709  
633  
582  
544  
494  
456  
418  
393  
367  
345  
2437  
1741  
1456  
1266  
1108  
987  
4115  
2975  
2469  
2184  
1899  
1709  
1551  
1456  
1323  
1234  
1127  
1063  
1000  
943  
8786  
6140  
5001  
4304  
3798  
3482  
3228  
3038  
2754  
2532  
2342  
2209  
2057  
1899  
24497  
17325  
14781  
12236  
10957  
10001  
9254  
50007  
35353  
28865  
25004  
22345  
20414  
18895  
17673  
15825  
14432  
13356  
12405  
11780  
11179  
30  
45  
60  
75  
90  
89  
105  
120  
150  
180  
210  
240  
270  
300  
83  
905  
76  
848  
8659  
69  
772  
7748  
63  
709  
7064  
58  
652  
6439  
614  
6077  
576  
5697  
544  
5381  
Note: Almost all operation problems are related to the installation techniques used.  
Do Not guess, be sure pipe size is adequate for required flow rate.  
1. Connect the proper size gas pipe at the input to the LP Vapor regulator. Connect the  
sealed and no leaks are present. The installer must ensure that all gas connections  
comply with all building codes.  
2. Verify Fuel Supply Pressure  
Prior to initial operation of generator, verify that fuel system pressure is 11Water  
Column (6 oz. pressure) and fuel pipe sizes comply with Table 3‐6.  
3. Proceed to Electrical Connections.  
3‐8 Receiving & Installation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Electrical Connections Class 1 wiring methods must be used for field wiring connections to terminals of a class  
2 circuit. It is the responsibility of the owner/operator to arrange for these procedures to be  
performed by a licensed electrical contractor and ensure conformance to all applicable codes  
including local codes peculiar to your municipality/city/county and state. Wire size and insulation  
type should be as required by NEC (National Electrical Code) and local codes.  
Warning: Never connect this generator to the electrical system of any building unless a licensed  
electrician has installed an approved transfer switch. The national electrical code (NEC)  
requires that connection of a generator to any electrical circuit normally powered by means of  
an electric utility must be connected by means of approved transfer switch equipment to  
isolate the electrical circuit from the utility distribution system when the generator is  
operating. Failure to isolate the electrical circuits by such means may result in injury or death  
to utility power workers due to backfeed of electrical energy onto the utility lines.  
Warning: Incorrect installation of this generator set could result in property damage, injury or death.  
Connection of the generator to its fuel source must be done by a qualified professional  
technician or contractor.  
WARNING: Be sure the system is properly grounded before applying power. Do not apply AC power  
before you ensure that grounds are connected. Electrical shock can cause serious or fatal  
injury. NEC requires that the frame and exposed conductive surfaces (metal parts) be  
connected to an approved earth ground. Local codes may also require proper grounding of  
generator systems.  
Intended Use The intended purpose of this generator set is to provide emergency power when the main utility  
power supply is interrupted. Therefore, it is important that all the wiring that connects the generator  
set with your house, transfer switch, distribution box, battery charger, etc. be properly installed.  
Circuit Protection Circuit protection is not provided within the generator. Circuit Breaker protection is an option.  
If purchased with your generator, the breaker box is mounted to the generator prior to shipment.  
If the optional circuit breaker protection was not ordered, see “GLC Circuit Breaker & Wire Size  
Data” in Appendix A for recommendations.  
Wire Size  
Proper lead wire from the circuit breaker to the automatic transfer switch (or load switching  
device) is mandatory. See transfer switch information for connection information. When  
connecting the generator output to an electrical load, a UL listed circuit breaker with the  
appropriate ratings must be provided within 25 feet of the generator set. Use only copper wires.  
Generator Rating  
Input Breaker Rating (at 115% FLA)  
3 Phase Amps (240VAC) * 3 Phase Amps (480VAC) *  
1 Phase Amps  
(240VAC) *  
Kilowatt (kW)  
Rating  
Catalog No.  
LPV/Nat. Gas  
Delta (Wye)  
Nat. Gas  
Delta (Wye)  
LPV  
Delta (Wye)  
Nat. Gas  
Delta (Wye)  
LPV  
Delta (Wye)  
GLC10  
GLC15  
GLC20  
GLC25  
GLC30  
GLC35  
GLC45  
GLC50  
GLC60  
GLC80  
GLC100  
GLC125  
10  
15  
50  
70  
20  
100  
125  
110  
125  
150  
175  
200  
300  
300  
450  
25  
30  
110  
125  
150  
175  
200  
300  
300  
450  
110  
125  
60  
60  
60  
60  
35  
45  
175  
70  
80  
50  
175  
90  
90  
60  
200(225)  
300  
100  
150  
150  
225  
110  
150  
175  
200  
80  
100  
125  
350  
400  
MN2408  
Receiving & Installation 3‐9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Transfer Switch Considerations  
The following are general considerations for the safe use of a transfer switch:  
1. The transfer switch should be located inside the building near the main breaker box or  
the disconnect box.  
2. The transfer switch must be kept away from any location that might allow water to get  
on it.  
3. If the transfer switch is mounted outside, it must be protected from the environment and  
it's elements.  
4. Do not mount the transfer switch on the generator set.  
5. Do not mount the transfer switch where flammable liquids or vapors are present.  
Figure 3‐4 Basic Power Transfer System  
Utility Power  
Generator Power  
Remote Start  
Contact  
L1 L2  
N
Ground  
L1 L2  
N
Fuses or  
Circuit  
Breakers  
Fuses or  
Circuit  
Breakers  
Main Panel  
Earth  
Ground  
Transfer  
Switch  
Mechanical  
Interlock  
Ground  
L1  
L2  
N
Power To Load  
Remote Start  
Connect the remote start start contact (from transfer switch) to GLC Remote Start terminals.  
Single Phase Power Connections  
Output power connections must be fused within 25 feet of the generator. If the wires to the  
transfer switch are shorter than 25 feet, connect L1, L2 and N to the transfer switch being sure to  
follow NEC and local codes. If the wires to the transfer switch are longer than 25 feet, UL  
requires that branch circuit protection be provided.  
Power connections are made at L1, L2, Neutral and Ground points indicated in the Customer  
3‐10 Receiving & Installation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 3‐5 Single Phase Connections  
From Alternator  
(Factory Wired)  
Bond Jumper  
Note: Remove the Bonding  
jumper to meet local  
codes if required.  
NEUTRAL  
Neutral  
Connections  
L1  
L2  
LOAD  
GROUND  
Ground  
Connections  
AC Power Connections  
Customer Connections  
Figure 3‐6 Three Phase WYE and DELTA Connections  
N
L3  
N
L2  
L1  
L1  
L2  
L3  
N
L1  
L2  
L3  
N
MN2408  
Receiving & Installation 3‐11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Battery Charger Considerations  
1. Mount the battery charger on the generator or as close to the generator as possible.  
2. If you mount the battery charger inside the building, mount it near the main breaker box  
or disconnect box.  
3. If you mount the battery charger outside, you must protect it from the environment and  
the elements.  
4. Do not mount the battery charger where flammable liquids or vapors are present.  
General Wiring Considerations  
1. When routing the interface wiring, do not route it up against anything that could cut or  
chafe the wiring. do not route the wire up against any hot or potentially hot object.  
2. Make sure that all the electrical components (generator set, transfer switch, battery  
charger, etc.) share a common hard wired ground.  
3. Check with your local building inspector to determine what you must do to comply with  
the local regulations for grounding of this type of permanent installation.  
3‐12 Receiving & Installation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Battery Connections The generator may be shipped with no battery installed.  
Procedure: The correct type battery must be installed in the battery compartment provided, see Table 3‐7.  
Installation and servicing of batteries is to be performed or supervised by personnel  
knowledgeable of batteries and the required precautions.  
Keep unauthorized personnel away from batteries.  
1. Open access doors and locate battery tray.  
2. Place the correct battery (see Table 3‐7) on the tray.  
a. Place the bent end of the Battery Hold Down Rod through the hole in the Battery  
Tray.  
b. Place the threaded end of the Battery Hold Down Rod through the hole in the  
Battery Hold Down Bar and secure with flat washer, lock washer and nut.  
c. Repeat steps a and b for the other Battery Hold Down Rod.  
Figure 3‐7 Battery Installation  
The + and - terminals of your battery may  
be different than shown. Be sure that the  
Positive lead is connected to the positive  
(+) terminal of your battery.  
Washers & Nut  
Battery Hold Down Bar  
(Install away from terminals)  
Battery  
Washers & Nut  
Battery Hold Down Rod  
Battery Tray  
4. Connect the positive lead to the positive (+) battery terminal.  
5. Connect the negative lead to the negative (-) battery terminal.  
6. Do not lay tools or metal parts on top of batteries.  
7. Connect charging source to the battery terminals.  
8. Disconnect the battery's ground terminal before working in the vicinity of the battery or  
battery wires. Contact with the battery can result in electrical shock when a tool  
accidently touches the positive battery terminal or wire. The risk of such shock is  
reduced when the ground lead is removed during installation and maintenance.  
Recommended Engine Oil and Battery Type  
When replacing batteries, use only the recommended battery for your generator, see Table 3‐7.  
Table 3‐7  
SUMMER  
OIL  
WINTER  
OIL  
OIL  
RECOMMENDED  
BATTERY  
(AMPS) COLD  
CRANKING  
675  
MODEL  
CAPACITY  
5.0 QTS  
6.0 QTS  
6.0 QTS  
6.0 QTS  
6.2 QTS  
6.2 QTS  
6.5 QTS  
6.5 QTS  
6.5 QTS  
GLC10-25  
GLC30  
GLC35  
GLC45  
GLC50  
GLC60  
GLC80  
GLC100  
GLC125  
SAE. 30  
SAE. 30  
SAE. 30  
SAE. 30  
SAE. 30  
SAE. 30  
SAE. 30  
SAE. 30  
SAE. 30  
5W/30  
5W/30  
5W/30  
5W/30  
5W/30  
5W/30  
5W/30  
5W/30  
5W/30  
BCI Group 31  
BCI Group 31  
BCI Group 31  
BCI Group 31  
BCI Group 31  
BCI Group 31  
BCI Group 31  
BCI Group 31  
BCI Group 31  
925  
925  
925  
925  
925  
925  
925  
925  
MN2408  
Receiving & Installation 3‐13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Post Installation Checks  
When the initial installation is complete, these checks must be performed before starting the  
engine. These checks are not required before each start, only after the initial installation.  
1. Generators that have been in transit or storage for long periods may be subjected to  
extreme temperature and moisture changes. This can cause excessive condensation,  
and the generator windings should be thoroughly dried before bringing the generator  
up to full nameplate voltage. If this precaution is not taken, serious damage to the  
generator can result.  
Caution: Do not apply high voltage to windings (do not start the generator) in a moisture-saturated  
condition. Moisture can cause insulation breakdown, making it necessary to return the  
generator for repair.  
Note: These precautions are especially necessary in locations such as seaboard installations  
and other high humidity areas. Some installations will be in atmospheres that are much  
more corrosive than others.  
2. Verify that the transfer switch is in Utility Power mode. No power must be present at  
the generator or transfer switch connections. Verify with a voltmeter.  
3. Verify that the engine starting battery is disconnected so accidental starting is not  
possible.  
4. Verify that the generator is securely mounted and anchored to its cement pad.  
5. Verify that proper clearance exists on all sides and top of enclosure.  
6. Verify that generator power is properly connected to the transfer switch.  
7. Verify that generator and transfer switch are properly grounded.  
8. Assure that generator is a safe distance from any flammable or combustible material.  
9. Verify that the generator and transfer switch load are voltage compatible.  
10. Verify that no load is connected to the circuit breaker and/or transfer switch.  
11. Inspect the engine and generator and verify that there are no loose wires or  
components. Tighten if necessary.  
12. Verify that the ground conductor is of correct wire size and properly connected.  
13. Verify engine oil level is full. Refer to engine manual if necessary.  
14. Verify engine coolant level is full. Refer to engine manual if necessary.  
15. Verify exhaust system to assure it is in properly connected and pointing away from  
combustible materials.  
16. Verify that the Master Control Switch is still in the “Stop” position.  
Connect the engine starting battery to the starter. Verify it is installed correctly.  
17. Verify the fuel source is ON and the pressure and flow rate are correct.  
18. Remove all tools, rags, etc. from inside the generator enclosure. Close all enclosure  
doors and be sure no hands are inside the generator enclosure when it starts.  
19. Verify all loads are disconnected.  
20. Start the generator. (Refer to Section 4 Operation for details).  
21. The engine should begin to crank and start when the fuel moves through the pipe to  
the carburetor. If the engine fails to start, refer to Section 5 Troubleshooting.  
3‐14 Receiving & Installation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Post Installation Checks Continued  
22. With the engine running, several checks must be made:  
a. Verify there are no fuel leaks. If a fuel leak is detected, stop the engine  
immediately (move the Master Control Switch to the “Stop” position) and  
repair the leak before proceeding.  
b. Verify there are no coolant or oil leaks. If a leak is detected, stop the engine  
immediately and repair the leak before proceeding.  
c. Verify that operation is smooth. If belt squeals, vibrations or other sources of  
noise exist, stop the engine immediately and repair before proceeding.  
d. Verify that the correct voltage exists (line-to-line and line-to-neutral) at the  
generator and at the transfer switch.  
e. Minor adjustment of the output voltage is made using the “Voltage Adjust”  
potentiometer on the control panel.  
WARNING: Engine coolant is under pressure and is near the boiling point of water when engine is hot.  
Do not open the coolant system until the engine has completely cooled. Hot coolant can  
cause severe burns and other injuries. When engine is cool, coolant level can be checked.  
23. After the operation checks are made, stop the engine (move the Master Control Switch  
to the “Stop” position) and wait at least 2 hours for the engine to cool. When the  
engine is cool, check engine oil and coolant levels as instructed in the engine operation  
manual.  
24. Close all enclosure covers. The post installation checks are now complete.  
MN2408  
Receiving & Installation 3‐15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3‐16 Receiving & Installation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 4  
Operation  
Digital Engine Controller Description EM0046A21 (MRS17)  
Figure 4‐8 Operator Control Panel  
Operating Modes and  
Horn & Fault Reset  
Manual  
Run  
Display  
Stop  
Menu  
Group  
LED Indicators  
Note: The operator control panel is equyipped with a heater element that allows the LCD display  
to operate to -40°C (not the entire generator set, see generator specifications). This  
heater operates from the main battery power.  
LED Indicators  
Alarm (red) - Alarm (shutdown) condition occurred. Annunciates & shuts down generator.  
Not In Auto (red) - Control is not in auto mode and cannot provide standby power.  
Running (green) - Generator is running, no alarms or warnings.  
Warning (yellow) - A warning condition has occurred. Annunciates only.  
Ready/Auto (green) - Control is in Auto mode and ready to provide standby power.  
Supplying Load (green) - Generator is providing output voltage to load.  
Table 4‐8 Alarm & Warning Conditions  
Alarm  
Warning  
X
X
X
X
X
X
X
X
X
X
X
X
X
High Coolant temperature  
Low Oil pressure  
Low Fuel level  
Generator Under/Over Voltage  
Generator Under/Over Frequency  
Generator Over Current  
Generator Overspeed  
X
X
Coolant temperature Low  
Starting battery Under/Over Voltage  
Manual Run  
Start  
Immediately begins the crank cycle to start engine and produce power (MAN mode only).  
Start generator set operation (MAN mode only).  
Stop  
Stops the Engine and generator set (MAN mode only).  
Displays setpoints, adjustments, Alarms and Warning conditions and Operating Mode selections.  
Changes menu displayed - Measurement, Adjustment or History.  
Allows selection of OFF - MAN - AUTO mode choices.  
Deactivates the Horn output.  
Display  
Page  
Mode A and "  
Horn Reset  
Fault Reset  
Y and B  
Reset Alarms and Warnings.  
Selects the menu choice, select the setpoint or select the menu or increase/decrease the  
setpoint value.  
Enter  
Confirm and accept changed setpoint value.  
Enter + Y and B Adjusts display contrast.  
Enter+ Fault Reset Clears engine ECU faults.  
MN2408  
Operation 4‐1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Digital Engine Controller Description EM0046A21 (MRS17) Continued  
Operating Mode Press Mode or to scroll though the list of operating modes: Off, Manual and Automatic.  
The control mode is shown in the highlighted area at the top of the display, Figure 4‐9.  
When the desired Control Mode is highlighted, press Start to begin operation.  
Press Stop to terminate operation.  
OFF -  
Generator set operation is not allowed.  
MAN - Press Start to manually start the generator set immediately.  
Press Stop to stop the generator set immediately.  
AUT - Start and Stop buttons are ignored.  
The binary input terminal conditions start and stop the generator set.  
Display Menus  
Three display menus are available: Measurement, Adjustment and history.  
Press the Page button repeatedly to display each menu. Use ꢃ ꢄ and Enter keys to change  
and accept setpoint values or press the Page button to cancel changes.  
Measurement Menu  
parameters such as kW, engine RPM etc.  
Figure 4‐9 Measurement Menu  
Control Mode  
OFF MAN AUT = Control operating mode (highlighted)  
! = Alarm indication is active  
Operating Modes and  
Horn & Fault Reset  
OFF MAN AUT  
!
Ready  
Ready = Status  
kW = Active power produced by generator  
PF = Power Factor  
RPM = Engine speed in revolutions per minute  
Timer = Event counting time (e.g. prestart, cooling etc.)  
PF  
0.00  
RPM  
Timer  
0
0
0
kW  
OFF Mode  
Starting of the generator set is not possible. Outputs STARTER (BO1) and FUEL SOLENOID  
(BO2) are not energized. No action if buttons START and STOP are pressed.  
MAN Mode  
START button starts the generator set.  
STOP stops the generator set.  
This operation is further defined in Table 4‐9.  
AUT Mode  
No action if buttons START and STOP are pressed.  
Engine Start/Stop request is given by binary input REM Start/Stop (BI1).  
4‐2 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Digital Engine Controller Description EM0046A21 (MRS17) Continued  
Table 4‐9 Manual Mode Sequence Description  
Action  
Menu  
Status  
Condition of Transition  
PRESTART on,  
Prestart time counter started  
Next State  
Start request  
PRESTART  
RPM > 2 or Oil pressure detected or  
Gen voltage > 10V  
Stop (Stop fail)  
Ready  
OFF mode selected or Shut down alarm active  
Not Ready  
Ready  
Not Ready  
Prestart  
RPM < 2, Oil pressure not detected, Vgen < 10V,  
no shutdown alarm active, other than OFF mode  
selected  
Prestart time elapsed  
STARTER on, FUEL SOLENOID on,  
MaxCrank time counter started  
Cranking  
RPM> Start RPM  
STARTER off, PRESTART off  
STARTER off, PRESTART off  
Starting  
D+ input activated or oil pressure detected or  
Gen voltage > 25% Vgnom  
Cranking  
Cranking  
MaxCrank time elapsed, 1st attempt  
STARTER off, FUEL SOLENOID off,  
STOP SOLENOID on,  
CrankFail pause timer started  
Crank pause  
MaxCrank time elapsed, last attempt  
STARTER off, PRESTART off  
Shutdown (Start fail)  
Cranking  
Main  
Measurement  
Crank Pause CrankFail pause elapsed  
STARTER on, FUEL SOLENOID on,  
STOP SOLENOID off,  
MaxCrank time counter started  
Starting  
30% Nominal speed reached  
Stop request  
READY TO LOAD on,  
MaxStabTime counter started  
Running  
Cooling  
READY TO LOAD off,  
Cooling time timer started  
Running  
Loaded  
RPM = 0 or any other shutdown condition  
RPM = 0 or any other shutdown condition  
Cooling time elapsed  
READY TO LOAD off,  
FUEL SOLENOID off  
Shutdown  
Shutdown  
Stop  
FUEL SOLENOID off, STOP SOLENOID  
on, READY TO LOAD off  
FUEL SOLENOID off,  
STOP SOLENOID on  
RPM = 0 or any other shutdown condition  
FUEL SOLENOID off,  
STOP SOLENOID on  
Shutdown  
Cooling  
Stop  
Start request  
READY TO LOAD on  
Running  
RPM = 0, Oil pressure not detected, Vgen < 10V  
60 sec. Elapsed  
Ready  
Stop (Stop fail)  
Some output conditions are optional and may require additional programming of field connection.  
See appropriate wiring diagram.  
Adjustment Menu  
Passwords, Pre-Start Time, Crank Time, Cool Down Time, Alarm Conditions and values,  
Shutdown Conditions and values, power transfer settings, etc.  
Figure 4‐10 Adjustment Menu  
Use and  
Press ENTER to select the parameter group.  
Press PAGE to move to the next page of menu items.  
to move the cursor to the desired parameter.  
> ENGINE BASIC  
ENGINE PROT  
GEN BASIC  
GEN PROTECT  
Alarm List  
Shows the active alarms and warnings. Press fault reset to clear the list.  
ECU Alarm List  
Shows the active ECU (engine control unit) fault codes. Press ENTER + fault reset to clear the  
list.  
MN2408  
Operation 4‐3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Alarms  
Following alarms are available:  
Sensor fail (FLS) see Table 4‐10  
Sensor fail is detected when measured value is 6% out of selected sensor characteristic.  
Sensor fail is indicated by ##### symbol instead measured value.  
Warning (WRN) see Table 4‐10  
When warning comes up, only alarm outputs and common warning output are closed.  
Shut down (SD) see Table 4‐10  
When the shut-down alarm comes up, InteliLite opens outputs GCB CLOSE/OPEN, FUEL  
SOLENOID, STARTER and PRESTART to stop the engine immediately. Alarm outputs and  
common shutdown output are closed. Active or not reset protection disables start.  
Table 4‐10 Possible Warnings  
Events specification  
Wrn Oil press  
Sd Oil press  
Wrn Water temp  
Sd Water temp  
Wrn Wtemp Low  
Wrn Fuel Level  
Sd Fuel Level  
Battery voltage <, >  
Battery flat  
Protection type  
WRN  
SD  
WRN  
SD  
WRN  
WRN  
SD  
WRN  
SD  
Start fail  
SD  
Vgen <, >  
SD  
Vgen unbl  
SD  
Fgen <, >  
SD  
Igen unbl  
SD  
Overload  
SD  
RPM over  
SD  
RPM under  
SD  
PickupFault  
SD  
Stop fail  
SD  
WrnServiceTime  
Emergency Stop  
ECU Common Warning  
ECU Shutdown  
WRN  
SD  
WRN  
SD  
4‐4 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Inputs and Outputs  
Any Binary input or output can be configured to any controller terminal Inputs are BI1 - BI6,  
Outputs are BO1 - BO6) or changed to different function by LiteEdit software.  
There is fixed 1 sec delay when any binary input is configured as protection.  
Table 4‐11 Binary Inputs  
Alarm  
Alarm type Warning or Shut down  
Alarm active All the time, or Engine running only  
Rem start/stop  
External request for engine run. AUT mode only.  
Emergency stop  
If the input is opened, shut down is immediately activated. Input is  
inverted (normally closed).  
Rem start/stop  
External request for engine run. AUT mode only.  
Table 4‐12 Binary outputs  
Starter (relay output)  
The closed relay energizes the starter motor.  
The relay opens if:  
The firing speed is reached or  
Maximum time of cranking is exceeded or  
Request to stop occurs  
Fuel solenoid (relay output)  
Closed output opens the fuel solenoid and enables the engine start.  
The output opens if:  
Emergency stop occurs or  
Cooled gen-set is stopped or  
In pause between repeated starts  
Prestart  
Output is closed prior to the engine start (Prestart) and opens when  
START RPM speed is reached.  
During repeated crank attempts the output is closed too.  
The output could be used for pre-glow, pre-heat or prelubrication.  
Common Sd  
Output closes when any shut-down alarm appears.  
The output opens, if alarm is not active and FAULT RESET is pressed.  
Used for shunt trip.  
MN2408  
Operation 4‐5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Analog Inputs  
Three analog inputs for resistive sensor 0 to 2400 ohms measuring are available on IL controller.  
Use LiteEdit software to modify configuration.  
The Analog inputs values assignment (AI1 = Oil press, AI2 = Water temp, AI3 = Fuel level) is fix.  
It is possible to configure on each Analog input:  
Reading from IL Analog inputs or from Engine Control Unit via CAN bus (J1939)  
Sensor characteristics - from the list,  
Value dimension (e.g. psi - bars, °F - °C, % - l)  
Number of decimal points (0, 1, 2, ...).  
Note: Corresponding Analog input terminal is dead when reading is switched to ECU.  
All values from ECU shall show ####, but no alarm is displayed when CAN communication  
is interrupted.  
Warning and shut-down limits are adjusted in Engine protection group.  
Table 4‐13 Analog Inputs  
AI1 Oil press  
AI2 Water temp  
AI3 Fuel level  
Oil pressure analog input. Default VDO sensor in range 0 to 145 psi.  
Water temperature analog input. Default VDO sensor in range 32 to 212°F  
Fuel level analog input. Default VDO sensor 0-180R = 0-100%.  
Set points  
Table 4‐14 Basic Setpoints  
EnterPassword  
Password is a four-digit number. Password enables change of relevant  
protected set points Use or keys to set and ENTER key to enter the  
password.  
ChangePassword  
Gen-set name  
Use or keys to set and ENTER key to change the password.  
User defined name, used for InteliLite identification at remote phone or  
mobile connection. Gen-set name is max 14 characters long and have to  
be entered using LiteEdit software.  
Nomin power(3ph)  
Nomin power(1ph)  
CT Ratio  
Nominal power of the generator in three phases connection.  
Step: 1 kW; Range: 1 - 3000 kW  
Nominal power of the generator in single-phase connection.  
Step: 1 kW; Range: 1 - 3000 kW  
Gen-set phases current transformers ratio.  
Step: 1 A; Range: 1 - 5000 A / 5A  
PT ratio  
Gen-set potential transformers ratio.  
Step: 0,1 V / V; Range: 0,1 - 500,0 V / V  
Nominal freq  
Gear teeth  
Nominal generator frequency (usually 50 or 60 Hz )  
Step: 1Hz; Range: 45 - 65 Hz  
Number of teeth on the engine gear for the pick-up. Set to zero, if no  
pick-up is used. Engine speed is counted from the generator frequency.  
Step: 1; Range: 0 - 500  
Note: Generator frequency can be used only when generator voltage  
(min 5V) is present before reaching of the firing speed  
(Starting RPM) after start.  
Nominal RPM  
Nominal engine speed. Step: 1RPM; Range: 100 - 4000 RPM.  
FLTRESGOTOMAN  
DISABLED: Controller stays in AUT mode after Fault reset .  
ENABLED: Automatic switch from AUT (or TEST) to MAN mode after  
Fault reset to avoid automatic engine start. This function is active for Shut  
down protection only.  
DispBackLightTO  
Timeout after which the display backlight is switched off.  
Step: 1 min Range: 0 - 60 min  
Default value: 0 = the display lights all the time  
Mode IL [ OFF, MAN, AUT ]  
Equivalent to Controller mode changes by MODEor MODEbuttons.  
Note: Controller Mode change can be separately password protected.  
RS232 mode  
[Standard/Modbus ]  
Communication protocol switch.  
Standard: LiteEdit communication protocol. Modbus: Modbus protocol.  
Note: For detail description see chapter Modbus protocol.  
Num rings AA  
Number of rings prior to open modem connection. Step: 1; Range: 1 - 30  
Note: NumberRings AA change is not activated immediately. It is activated  
after controller is switched on or when modem is connected to controller.  
4‐6 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4‐15 Engine Setpoints  
“Firing” speed when iL controller stops cranking (starter goes OFF).  
Step: 1% of nominal RPM; Range: 5 - 50 %  
Start RPM  
Starting POil  
When reached controller stops cranking (starter goes OFF).  
Step: 0,1 psi; Range: -100 - 10000  
Note: There are three conditions for stop cranking: Starting RPM,  
StartingPOil and D+ (when enabled). Starter goes off when any  
of these conditions is valid.  
Prestart time  
Time of closing of the PRE-START output prior to the engine start.  
Set to zero if you want to leave the output PRE-START open.  
Step: 1s; Range: 0 - 600 s  
MaxCrank time  
CrnkFail pause  
Crank attemps  
Idle time  
Maximum time limit of cranking. Step: 1s; Range: 1 - 60 s  
Pause between crank attempts. Step: 1s; Range: 5 - 60 s  
Max number of crank attempts. Step: 1; Range: 1 - 10  
Idle time delay starts when RPM exceeds Start RPM . Start fail is detected  
when during Idle state RPM decreases below 2.  
During the Idle time timer running the binary output IDLE/NOMINAL is  
opened, when it elapses the IDLE/NOMINAL output closes.  
Binary output IDLE/NOMINAL opens during Cooling period again.  
Step: 1 s; Range: 0 - 600 s  
Note: If the IDLE function not supported on the governor, set the Idle time  
nevertheless to minimum 5s to avoid Underspeed possibly  
caused by instability of the engine short after start.  
GCB CloseDelay  
Stabil time  
GCB can be closed earliest GCB CloseDelay after Stabil time when all  
electric values are in overunder voltage and over-under frequency limits.  
Step: 1 s; Range: 0 - 300 s  
Generator Nominal voltage is detected during genset start after starter is  
switched off and Idle time elapses. Electric generator protections are  
active since detection. Step: 1 s; Range: 0 - 300 s  
MinStpValvTime  
Binary output Stop solenoid closes when stop sequence begins and  
closes at least for MinStpValvTime. Example MinStpValvTime = 20 sec.  
a) When engine stops (RPM=0) in 10 seconds, Binary output Stop  
solenoid still stays closed for 10 sec.  
b) When engine stops in 30 seconds, Binary output Stop solenoid opens  
10 seconds after RPM=0 and Vg =0 and Oil pressure = 0. Those 10 sec is  
fix time for safe stop. Step: 1s; Range: 0 - 180 s  
Note: Stop of engine is detected when all following conditions are met:  
RPM =0, Oil pressure < StartingPOil and Generator voltage < 10 VAC.  
Stop fail is detected when is difference between those conditions, e.g  
RPM=O and Generator voltage > 10V.  
RPM  
Start RPM  
RPM  
RPM = 2  
Idle Function  
BāOā Sātarter  
BāOā IDLEā/RAāTāEāD  
Idle time  
Min stab time  
Electric protections  
activāe  
Start Fail  
Stabil Time  
MN2408  
Operation 4‐7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Runtime of the unloaded gen-set to cool the engine before stop.  
Step: 1s; Range: 0 - 3600 s  
Cooling time  
AfterCoolTime  
Runtime of engine after cooling pump. Binary output Cooling pump is  
closed when the engine starts and opens AfterCool time delayed after  
gen-set stops. Step: 1s Range: 0 - 3600s  
CoolingSpeed  
Selects the function of the Binary output IDLE/NOMINAL during engine  
Cooling state.  
NOMINAL : Cooling is executed at Nominal speed and generator  
protections are active.  
IDLE: Cooling is executed at Idle speed and generator protections are  
switched off.  
Hint: Binary output IDLE/NOMINAL must be configured and connected to  
speed governor. Engine Idle speed must be adjusted on speed governor.  
D+ function  
ENABLED: The D+ terminal is used for both functions “running engine”  
detection and charge fail detection.  
CHRGFAIL: The D+ terminal is used for charge fail detection only  
DISABLED: The D+ terminal is not used.  
Note: Magnetization current is independent of this setpoint value.  
Table 4‐16 Engine Protect Setpoints  
ECUFreqSelect  
This setpoint should be used only for Volvo and Scania engines.  
This setpoint should be used only for Volvo and Scania engines.  
ECU Speed Adjust  
WTBF Accept RPM  
The WtBfAcceptRPM delay setpoint will start to count down since  
cranking. Controller waits before communicating with the ECU for this  
time. This is because the JD engine passes some erroneous RPM signals  
during the first 500ms. Step: 0,1s Range: 0 - 3s  
Eng prot del  
During the start of the gen-set, some engine protections have to be  
blocked (e.g. Oil pressure). The protections are unblocked after the  
Protection del time. The time starts after reaching Start RPM.  
Step: 1s; Range: 0 - 300 s  
Horn timeout  
Overspeed  
Max time limit of horn sounding. Set to zero if you want to leave the output  
HORN open. Step: 1s; Range: 0 - 600 s  
Threshold for over speed protection.  
Step: 1% of nominal RPM; Range: 100 - 150%  
Wrn Oil press  
Sd Oil press  
Warning threshold level for ANALOG INPUT 1.  
Step: 1 psi; Range: Sd Oil press - 10000  
Shutdown threshold level for ANALOG INPUT 1.  
Step: 1 psi; Range: -100 - Wrn Oil press  
Oil press del  
Delay for ANALOG INPUT 1. Step: 1 s; Range: 0 - 180  
Sd Water temp  
Warning threshold level for ANALOG INPUT 2.  
Step: 1 °C; Range: Wrn Wtemp - 10000  
Warning threshold level for ANALOG INPUT 2.  
Step: 1 °F; Range: Wrn Wtemp low - Sd Water temp  
Warning threshold level for low value on ANALOG INPUT 2.  
Wrn Water temp  
Wrn Wtemp low  
Step: 1 °F; Range: -100 - Wrn Water temp  
Water temp Low del  
Water temp del  
Delay for ANALOG INPUT 2 Wrn Wtemp low. Step: 1 s; Range:1-180 s  
Delay for ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 - 180 s  
Wrn Fuel Level  
Warning threshold level for ANALOG INPUT 3.  
Step: 1 %; Range: Sd Fuel Level - 10000  
Sd Fuel Level  
Shutdown threshold level for ANALOG INPUT 3.  
Step: 1 %; Range: -100 - Wrn Fuel Level  
Fuel Level del  
Batt overvolt  
Delay for ANALOG INPUT 3. Step: 1 s; Range: 0 - 180 s  
Warning threshold for high battery voltage.  
Step: 0,1 V; Range: Batt undervolt - 40V  
Batt undervolt  
Warning threshold for low battery voltage.  
Step: 0,1 V; Range: 8V - Batt overvolt  
Batt volt del  
Delay for low battery voltage alarm. Step: 1s; Range: 0 - 600 s  
NextServTime  
Counts down when engine running. If reaches zero, an alarm appears.  
Step: 1h; Range: 0 -65535h  
4‐8 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4‐17 Generator Protect Setpoints  
Overload  
Threshold for generator overload (in % of Nominal power)  
Step: 1% of Nominal power; Range: 0 - 200%  
Overload Wrn  
Threshold for generator overload warning (in % of Nominal power)  
Step: 1% of Nominal power; Range: 0 - 200%  
Overload del  
Ishort  
Delay for generator overload alarm. Step: 0.1s; Range: 0 - 60.0 s  
Shutdown occurs when short circuit limit Ishort limit is reached.  
Step: 1 % of Nominal current; Range: 100 - 500 %  
2Inom del  
IDMT curve shape selection. 2Inom del is Reaction time of IDMT  
protection for 200% overcurrent Igen = 2* Nominal current.  
Step: 0,1 s; Range: 0,1 - 20 s  
IDMT is “very inverse” generator over current protection. Reaction time is  
not constant but depends on generator over current level according  
following formula. Reaction time is limited up to 900 sec = 15 minutes.  
IDMT protection is not active for Reaction time values longer than 15  
minutes.  
2lnomĂdelĂ *Ă NominĂcurrent  
lgenĂ *Ă NominĂcurrent  
ReactionĂTimeĂ +  
Curr unbal  
Threshold for generator current asymmetry (unbalance).  
Step: 1% of Nominal current; Range: 1 - 100% of Nominal current  
Curr unbal del  
Gen >V  
Delay for generator current assymetry. Step: 0.1 s; Range: 0 - 60.0 s  
Shutdown level for generator overvoltage. All three phases are checked.  
Maximum out of three is used.  
Step: 1% of Nominal voltage; Range: Gen >V Wrn -200%  
Gen >V Wrn  
Gen <V Wrn  
Gen <V  
Warning level for generator overvoltage. All three phases are checked.  
Maximum out of three is used.  
Step: 1% of Nominal voltage; Range: Gen <V Wrn - Gen >V  
Warning level for generator under voltage. All three phases are checked.  
Minimum out of three is used.  
Step: 1% of Nominal voltage; Range: Gen <V - Gen >V Wrn  
Shutdown level for generator under voltage. All three phases are checked.  
Minimum out of three is used.  
Step: 1% of Nominal voltage; Range: 0% - Gen <V Wrn  
Gen V del  
Volt unbal  
Volt unbal del  
Gen >f  
Delay for generator under voltage and over voltage alarm  
Step: 0.1s; Range: 0 - 60 s  
Threshold for generator voltage unbalance alarm.  
Step: 1% of Nominal voltage; Range: 0 - 100% of Nominal voltage  
Delay for generator voltage unbalance alarm.  
Step: 0.1s; Range: 0 - 60.0 s  
Shutdown level for generator over frequency.  
Step: 0.1% of Nominal frequency; Range: Gen > Wrn - 200.0%  
Gen >f Wrn  
Gen <f  
Warning level for generator over frequency.  
Step: 0.1% of Nominal frequency; Range: Gen <f Wrn - Gen >V  
Shutdown level for generator under frequency.  
Step: 0.1% of Nominal frequency; Range: 0.0 - Gen <f Wrn  
Gen <f Wrn  
Gen f del  
Warning level for generator under frequency.  
Step: 0.1% of Nominal frequency; Range: Gen <f - Gen >f Wrn  
Delay for generator under frequency and over frequency alarm.  
Step: 0.1s; Range: 0 - 60.0 s  
MN2408  
Operation 4‐9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Table 4‐18 Sensor Spec Setpoints  
Calibr AI1,AI2, AI3  
AnOut-kW/20mA  
Calibrating constant to adjust the measured value of IL analog inputs.  
Physical dimension of calibrating constant is corresponding to Analog  
input. Step: 1; Range: -1000 to +1000  
Conversion coefficient from gen-set power to iG-IOM or PTM analog  
output. Step: 1; Range: 1 to 32000  
Table 4‐19 IOM/PTM Module Setpoints  
AnlInIOM1 lev1  
AnlInIOM1 lev2  
The level for IOM ANALOG INPUT 1 alarm detection.  
Step: 1; Range: -100 to +10000  
The level for IOM ANALOG INPUT 1 alarm detection.  
Step: 1; Range: -100 to+10000  
AnlInIOM1 del  
AnlInIOM2 lev1  
Delay for IOM ANALOG INPUT 1 alarm. Step: 1 s; Range: 0 - 180 s  
The level for IOM ANALOG INPUT 2 alarm detection.  
Step: 1; Range: -100 to +10000  
AnlInIOM2 lev2  
The level for IOM ANALOG INPUT 2 alarm detection.  
Step: 1; Range: -100 to +10000  
AnlInIOM2 del  
AnlInIOM3 lev1  
Delay for IOM ANALOG INPUT 2 alarm. Step: 1 s; Range: 0 - 180 s  
The level for IOM ANALOG INPUT 3 alarm detection.  
Step: 1; Range: -100 to +10000  
AnlInIOM3 lev2  
AnlInIOM3 del  
AnlInIOM4 lev1  
AnlInIOM4 lev2  
AnlInIOM4 del  
Calibr AInIOM 1..4  
The level for IOM ANALOG INPUT 3 alarm detection.  
Step: 1; Range: -100 to +10000  
Delay for IOM ANALOG INPUT 3 alarm.  
Step: 1 s; Range: 0 - 180 s  
The level for IOM ANALOG INPUT 4 alarm detection.  
Step: 1; Range: -100 to +10000  
The level for IOM ANALOG INPUT 4 alarm detection.  
Step: 1; Range: -100 to +10000  
Delay for IOM ANALOG INPUT 4 alarm. Step: 1 s; Range: 0 - 180 s  
The protection of IOM/PTM inputs is activated by over crossing the limits.  
Calibrating constant to adjust the measured value of IOM/PTM analog  
inputs. Physical dimension of calibrating constant is corresponding to  
Analog input. Step: 1; Range: -1000 to +1000  
4‐10 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Digital Engine Controller Description EM0046A21 (MRS17) Continued  
Figure 4‐11 Controller Connection Diagram  
LOAD  
GENERATOR  
DIꢁ ESEꢁ Lꢁ /GASꢂENGINꢁ E  
L1  
L2  
L3  
G
N
Remote  
Start  
PE  
RPM  
+
-
BATTERY  
STARTꢁ ER  
GENERATOR  
CURRENT  
0- ā 5A  
GENERā ATOR  
Vā Oā LTAĂGā E  
3ăxă230Ăā /ăā 400ăV  
BINARYăINPā UTS  
CAN  
BOOTăā JUMPER  
RPM  
ANALOG INPUTS  
BIā NAā RY  
OUTPUTS  
POā Wā ER  
8- 36VDC  
-
+
BINARYăOUTPUTS  
TO BATTERY  
MN2408  
Operation 4‐11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Digital Engine Controller Description EM0046A21 (MRS17) Continued  
Figure 4‐12 Controller Connection Diagram  
LOAD  
GENERATOR  
DIꢁ ESEꢁ Lꢁ /GASꢂENGINꢁ E  
L1  
L2  
L3  
G
N
Remote  
Start  
PE  
JDIC  
+ -  
+
-
TO BATTERY  
BATTERY  
STARTꢁ ER  
GENERATOR  
CURRENT  
0- ā 5A  
GENERā ATOR  
Vā Oā LTAĂGā E  
3ăxă230Ăā /ăā 400ăV  
BINARYăINPā UTS  
CAN  
BOOTăā JUMPER  
RPM  
ANALOG INPUTS  
BIā NAā RY  
OUTPUTS  
POā Wā ER  
8- 36VDC  
-
+
Ground  
BINARYăOUTPUTS  
TO BATTERY  
4‐12 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Operator Control Panel (MICROPROCESSOR Engine Controller Only)  
WARNING: Never connect this generator to any buildings electrical system unless a licensed electrician  
has installed an approved transfer switch. The National Electrical Code (NEC) requires that  
connection of a generator to any electrical circuit normally powered by means of an electric  
utility must be connected by means of approved transfer switch equipment so as to isolate  
the electrical circuit from the utility distribution system when the generator is operating.  
Failure to isolate the electrical circuits by such means may result in injury or death to utility  
power workers due to backfeed of electrical energy onto the utility lines.  
Figure 4‐13 Digital Operator Control Panel  
MICROPROCESSOR ENGINE CONTROLLER  
ALARM  
READY  
Vavg Aavg Freq  
000  
000  
000  
SHUTDOWN  
SPEED SIGNAL  
LAMP TEST  
SILENCE  
RESET  
EXIT  
DECREMENT  
INCREMENT  
ENTER  
LOAD  
TEST  
EMERGENCY  
STOP  
RUN  
OFF  
AUTO  
-
+
VOLTAGE  
ADJUST  
LCD Display -  
Vavg (average voltage) display 0-999 volts.  
Aavg (average amperage) display 0-999 amperes.  
Freq (frequency) display 0-999 hertz.  
Alarm LED-  
Flashes when a fault is detected.  
Flashes when a fault is detected.  
Shutdown LED-  
Ready LED-  
Speed Signal LED-  
On when the generator set is ready for automatic operation and no Shutdown or Alarm faults are detected.  
On when the engine speed signal is detected (i.e. the engine is cranking).  
Emergency Stop LED- On when the Emergency Stop Switch is used to stop the engine.  
Emergency Stop Switch- When pushed, the engine is stopped immediately. The engine cannot be restarted until the controller is reset.  
Programming Keys  
Exit pushbutton used to scroll backward through the status menus or programming prompts to the previous item.  
Note: The longer the push-button is held down, the faster the menu prompts appear.  
Decrement pushbutton used to reduce a programming value while in the programming mode.  
Note: The longer the push-button is held down, the faster the value will be decremented.  
Increase pushbutton used to increase a programming value while in the programming mode.  
Note: The longer the push-button is held down, the faster the value will be incremented.  
Enter pushbutton used to scroll forward through the status menus or programming prompts to the next item.  
Note: The longer the push-button is held down, the faster the menu prompts appear.  
Run Switch-  
When pushed, initiates a manual start signal to start the engine. The engine will start and operate continuously providing no  
shutdown faults are active. All protective circuits are operative in this mode. There will be no cool down cycle at the end of a  
manual run sequence.  
Run LED-  
OFF Switch-  
OFF LED-  
On when the Run switch is used to start the engine (generator set).  
When pushed, sends a stop signal to the engine to stop the engine.  
On when the OFF Switch is used to stop the engine.  
MN2408  
Operation 4‐13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Operator Control Panel Continued  
Auto Switch -  
When pushed, initiates automatic operation of the engine (generator set). Starting and stopping of the engine is controlled by a  
remote contact (transfer switch). When the remote start signal is removed the engine will continue to run for the cool down period  
(if selected) then stop. Pushing the Off switch will stop the engine immediately, even if the cool down period is not complete.  
On when the Auto Switch is used to start automatic operation.  
Auto LED-  
Load Test Switch -  
When pushed, initiates a load test of the generator set with the associated transfer switch. Only operative for AMF connections or  
if one of the programmable output contacts is configured for “ATS Test” and the remote transfer switch has remote testing circuitry.  
When pushed, a signal is issued to the remote transfer switch to permit an automatic engine start and load transfer. Once initiated,  
the engine will receive a start signal from the transfer switch and upon the generator reaching nominal voltage and frequency  
levels, a load transfer will be initiated. The generator set will remain running at load until a different operating mode is selected or  
the generator set develops an alarm or shutdown fault condition.  
Load Test LED -  
On when the load test of the generator set is active.  
Special Function Switches Silence  
Horn Silence. Press both “Exit and Decrement” at the same time.  
This will silence the audible alarm horn without resetting the fail condition.  
Lamp Test Press both “Decrement and Increment” at the same time.  
Causes the LED's and LCD display to illuminate for approximately 2 seconds then return to their original status.  
Note: The emergency stop LED is not affected by this test.  
Reset  
Fault Reset. Press both “Increment and Enter” at the same time.  
Resets the controller when in a shutdown mode.  
Note: To reset after a fault, the engine must come to a complete stop and the controller's “OFF” switch must be pressed.  
Voltage Adjust -  
Increase or Decrease the Generator output voltage (displayed on VOLTAGE meter)  
Operating Procedures  
The engine-generator controller is designed to start and stop an engine from either a  
local (“Manual”) or remote (“Automatic”) modes. When a start command is issued, the controller  
issues a run and crank output signal. The controller then monitors engine speed and when crank  
disconnect speed is reached, the crank signal is terminated. While the engine accelerates to  
normal speed, the controller continuously monitors the engines speed signal. Should the engine  
speed exceed the maximum predetermined setpoint, the overspeed shutdown fault circuit will  
activate, terminating the run signal.  
In addition to overspeed shutdown, the engine controller also monitors many other engine  
protection circuits and should they be activated, the engine will be stopped and/or alarm initiated.  
The engine will automatically stop for any shutdown condition, or when the remote and/or local  
start signal is removed. The engine controller operation includes time delay circuits for normal  
operating conditions such as start delays, cool down and cranking periods.  
Manual Start/Stop  
To manually Start the Gen-Set, push the “RUN” push-button. The following happens:  
1. When the “RUN” push-button is pressed, an ENGINE START DELAY timer is initiated.  
(The start sequence will not be initiated if any shutdown fault condition is present.)  
2. When the engine start delay time expires, an engine RUN and CRANK output signal  
will be initiated. (The RUN output may be programmed to only energize when a start  
signal is initiated and an engine speed signal is detected.)  
3. When the engine starts and begins to accelerate to nominal speed, the controllers  
speed sensor will terminate the CRANK output when engine speed reaches  
approximately 20% speed (i.e. CRANK DISCONNECT speed setpoint). Immediately  
upon reaching crank disconnect speed, the controller will initiate the BYPASS DELAY  
time delay function. After the BYPASS DELAY time period (typically 10 seconds) all  
fault circuits programmed as BYPASS DELAY=YES are active. (All fault circuits  
programmed as BYPASS DELAY=NO are continuously armed irrespective of any  
operation sequence.)  
To manually Stop the Gen-Set, push the “OFF” push-button. The controllers RUN output will be  
immediately terminated which will initiate the engine stop sequence.  
Automatic Start/Stop  
To setup the generator for automatic operation, pressing the “AUTO” push-button.  
The following happens:  
1. The engine will automatically start upon activation of the remote start contact input. The  
remote device initiates a start sequence upon contact closure.  
2. When the remote start signal is activated, the engine will start as per the sequence of  
operation described for the manual start sequence.  
3. The automatic stop sequence will be initiated by removal of the remote start signal.  
4. When the start signal is removed, a cool down delay function will be initiated.  
4‐14 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5. When the cool down time delay period expires (typically 5 minutes), the controllers  
RUN output will be immediately terminated which will initiate the engine to stop.  
Automatic Fault Shutdown  
When a fault circuit is programmed as a SHUTDOWN, the engine will immediately stop when the  
fault is activated. A specific shutdown fault can be programmed with a definite time transient  
delay period that must expire before the shutdown is activated. The stop sequence will cause the  
controllers RUN output to be immediately terminated which will cause the engine to stop. This  
will prevent subsequent operation of the generator set. The Run/Stop/Auto selector switch on the  
operator control panel must be momentarily placed in the “Stop” position to reset the fault.  
Automatic Mains Failure (AMF)  
Figure 4‐14 Auto Mains Failure (AMF) Connections  
Transfer  
Switch  
MN2408  
Operation 4‐15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
When the controller is applied in an Auto Mains Failure (AMF) application with a transfer switch,  
Ready To Load and programmable output #4 must be selected for Gen Ready To Load. After the  
controller is programmed, the AMF sequence of operation will be as follows:  
Utility Normal Condition:  
1. Remote Start input signal (terminals 16 & 17) is not activated (i.e. normal).  
2. Utility Ready To Load output is energized (i.e. signal to transfer switch to transfer to  
utility power).  
3. Generator Ready To Load output is de-energized.  
Utility Power Failure Conditions:  
1. Remote Start input signal is activated (i.e. remote start contact closes when utility  
power fails, as sensed by utility voltage sensor).  
2. Engine starts after the Engine Start Delay timer (Utility Ready To Load output stays  
energized).  
3. After the engine has started and the generator output rises above the programmed  
voltage and frequency limits, a Warm-Up timer is initiated.  
4. After the Warm-Up timer expires the Utility Ready to Load output de-energizes and the  
NEUTRAL Delay timer is initiated.  
5. After the NEUTRAL DELAY timer expires the Gen Ready to Load output energizes to  
signal the transfer switch to transfer to the generator supply. Note: The neutral delay  
function is only operative with an electrically-held type transfer switch mechanism  
(ie. electrical contactor type).  
Utility Power Restored:  
1. Remote Start input signal is removed and the Return Delay timer is initiated (i.e. Utility  
Voltage returns to normal and the Utility voltage sensor contact opens).  
2. After the Return Delay timer expires, the Generator Ready to Load output  
de-energizes and the Neutral Delay timer is initiated.  
3. After the Neutral Delay timer expires the Utility Ready to Load output energizes to  
signal the transfer switch to transfer to the utility supply. Note: If the generator has a  
shutdown during the Return or Neutral Delay periods, the timers are bypassed, and the  
Utility Ready to Load output immediately energizes.  
4. The generator Cool down Timer starts after the Return Delay timer.  
5. The generator stops after the Cool down Timer.  
Load Test Push-button Operation  
1. When the Load Test pushbutton is pressed, the logic will internally simulate receiving a  
remote start input.  
2. Engine starts after the Engine Start delay timer.  
3. After the engine has started and the generator output rises above the programmed  
voltage and frequency limits, a Warm-Up timer is initiated.  
4. After the Warm-Up timer expires the Utility Ready to Load output de-energizes and the  
Neutral Delay timer is initiated.  
5. After the Neutral Timer expires the Gen Ready To Load output energizes to signal the  
transfer switch to transfer to the generator supply.  
Note: If a generator shutdown occurs during a Load Test Operation, the Load Test mode will be  
de-activated.  
When Auto Mode is restored (after Load Test Operation) the following occurs:  
1. Simulated Remote Start input signal is removed.  
2. Gen Ready To Load output de-energizes, and Neutral Delay timer is initiated.  
3. After the Neutral Delay timer expires The Utility Ready To Load output energizes to  
signal the transfer switch to transfer to the utility supply.  
4. The generator Cool down timer starts timing following the transfer to the utility supply.  
5. The generator stops after the Cool down timer.  
4‐16 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
No Load Test  
To allow a timed No Load Test of the engine/generator set while using the AMF control  
application, a digital input contact from an external timer must be programmed for NO LOAD Test  
The sequence of operation for a No Load Test condition is as follows:  
1. With the utility supply normal and the generator stopped, a no load test sequence may  
be initiated by closing an external exercise timer contact to the programmed digital  
input for No Load Test.  
2. After the external exercise timer contact closes, the engine will start and come-up to  
normal operating speed and voltage. The controller will issue an alarm of a No Load  
Test condition. The connected transfer switch will remain on the utility and the  
generator will not transfer on load. Note: should the utility supply fail, the generator will  
automatically transfer on load.  
3. The engine will continue to run as long as the external exercise timer contact remains  
closed.  
4. After the external exercise timer contact opens, the engine will continue to run for its  
cool down time as programmed, then it will automatically stop.  
Standard Faults When a fault occurs, information about the fault is displayed. The engine controller has many  
analog and digital inputs for monitoring and control operations. Three types of faults are used:  
1. Internal Faults are derived from a combination of digital and analog inputs.  
2. Digital Input Faults are initiated from external contact inputs.  
3. Analog Input Faults are initiated from external analog signal inputs.  
A description of each is provided.  
Internal Faults  
Overspeed Shutdown  
Overspeed Shutdown is initiated when the engine's speed has increased above the overspeed setpoint. The overspeed fault  
circuit is internally programmed as a latching shutdown fault. The overspeed shutdown fault circuit is programmable for the  
percentage of nominal engine speed (i.e. overspeed setpoint) and for the transient time delay period. The programming  
prompts for overspeed are located in the main menu programming loop.  
Loss of Speed  
Alarm/Shutdown  
Loss Of Speed is initiated when the engine's speed sensing circuit does not detect a speed signal for a period more than 2  
seconds following a run signal. The loss of speed fault may be user programmed as a latching shutdown fault or alarm only.  
The programming prompts for loss of speed are located in the main menu programming loop.  
Overcrank Shutdown  
Switch not in AUTO  
Overcrank Shutdown is initiated when the engine fails to start after the selected crank time or number of crank cycles. The  
overcrank fault circuit is internally programmed as a latching shutdown fault and is not user programmable.  
Switch not in AUTO is initiated when the controller's operating mode switch is changed from the auto position to any other  
position (ON the keypad). This fault is internally programmed as a non latching alarm. In the main programming loop, this  
alarm may be user programmed to initiate the common fail output relay.  
Digital Input Faults  
Digital Inputs (N/O or N/C)  
Four digital faults are provided and these are user programmable. Each digital fault input circuit is activated by a remote  
sensing contact that is external to the controller. Each digital fault input circuit may be programmed with a unique fault label  
description as stored in the controller's non-volatile memory.  
Factory settings have four standard digital faults as follows:  
Fault  
Action  
Fault  
Name  
Digital Inputs  
Terminal #  
Low Oil Pressure  
High Engine Temperature  
Battery Charger Input Fail  
Low Fuel Level  
Shutdown  
Shutdown  
Alarm  
1
2
3
4
Alarm  
The following is a list of all digital faults:  
High Bearing Temp  
High Cooler Vibration  
High Engine Temp  
High Engine Vibration  
High Fuel Level  
Failed To Sync  
Low Fuel Press  
Low Engine Temp  
Low Oil Pressure  
Low Fuel Level  
Low Oil Level  
Reverse Power  
Fail To Sync  
Vent Damper Fail  
Gen Breaker Open  
Ground Fault  
Bat Charger Input Fail  
Bat Chrg Trouble  
Bat Charger Fail  
DC Fail  
Breaker Tripped  
Basin Rupture  
High Oil Level  
High Oil Temp  
No Load Test  
ATS In Bypass  
Fuel Leak  
High Winding Temp Low Fuel Press  
*Highintkmanftemp Low Coolant Level  
“Blank” (i.e. no text for unused inputs)  
Remote Emerg. Stop  
Air Damper Tripped  
MN2408  
Operation 4‐17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 4‐15 Engine Controller Inputs & Outputs  
4‐18 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Analog Faults  
Eight analog fault inputs are user programmable for 12 fault conditions. Each analog fault input requires a specific analog  
signal type.  
Fault  
Name  
Fault  
Action  
Inputs  
Signal  
Low Engine Temperature  
Alarm  
Alarm  
Engine Temperature  
Engine Temperature  
Engine Temperature  
Oil Pressure  
High Engine Temperature #1  
High Engine Temperature # 2 Shutdown  
Low Oil Pressure #1  
Low Oil Pressure #2  
Low Battery Voltage  
High Battery Voltage  
Weak Battery  
Alarm  
Shutdown  
Alarm  
Oil Pressure  
Battery Voltage  
Battery Voltage  
Battery Voltage  
Voltage  
Alarm  
Alarm  
Undervoltage  
Shutdown  
Shutdown  
Under frequency  
AC Frequency  
Low Engine Temperature  
An analog DC signal is provided from an engine mounted sender. The low engine temperature fault is activated when engine  
temperature is below a pre-determined setpoint for a specified time delay. This fault is programmable for temperature  
setpoint level, transient time delay settings and other functions.  
High Engine Temperature #1 An analog DC signal is provided from an engine mounted sender. The high engine temperature fault is activated when  
engine temperature is above a pre-determined setpoint for a specified time delay. This fault is programmable for the level of  
temperature setpoint, transient time delay settings and other functions.  
High Engine Temperature # 2 An analog DC signal is provided from an engine mounted sender. The high engine temperature fault is activated when the  
engine temperature rises above a pre-determined setpoint for a specified time delay. This fault is programmable for the level  
of temperature setpoint, transient time delay settings and other functions.  
Low Oil Pressure #1  
Low Oil Pressure #2  
Low Battery Voltage  
An analog DC signal is provided from an engine mounted sender. The low oil pressure alarm fault is activated when the oil  
pressure is below a pre-determined setpoint for a specified time delay. This fault is programmable for pressure setpoint level,  
transient time delay settings and other functions.  
An analog DC signal is provided from an engine mounted sender. The low oil pressure shutdown fault is activated when the  
oil pressure is below a pre-determined setpoint for a specified time delay. This fault is programmable for pressure setpoint  
level, transient time delay settings and other functions.  
The low battery voltage alarm fault is activated when the battery voltage drops below a pre-determined setpoint for a  
specified time delay. This fault is programmable for the voltage setpoint level, transient time delay settings and other  
functions.  
High Battery Voltage  
Weak Battery  
The high battery voltage alarm fault is activated when the battery voltage rises above a pre-determined setpoint for a  
specified time delay. This fault is programmable for voltage setpoint level, transient time delay settings and other functions.  
The weak battery alarm fault is activated when the battery voltage drops below a pre-determined setpoint for a specified  
time delay. The weak battery alarm detects a low capacity (i.e. “weak“) battery condition during the cranking cycle. The weak  
battery alarm is programmed for a lower battery voltage setpoint and shorter time delay than the low battery alarm function.  
This fault is programmable for voltage setpoint level, transient time delay settings and other functions.  
Undervoltage  
All 3-phases of the generator output are monitored for an undervoltage condition. The undervoltage sensor is programmable  
for type of fault action (alarm or shutdown), pickup and dropout voltage setpoints (i.e. adjustable hysteresis) and transient  
time delay settings.  
Under frequency  
The generator output is monitored for an under frequency condition. The under frequency sensor is programmable for type of  
fault action (alarm or shutdown), frequency setpoint, and transient time delay settings.  
Engine Speed Analog Input A magnetic pickup (engine speed sensor) measures engine speed. The engine speed sensor allows the controller to perform  
the following control functions:  
Overspeed shutdown  
Crank Disconnect control  
Loss of speed signal detection  
Starter Re-engage control  
RPM display  
MN2408  
Operation 4‐19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Output Contacts All output contacts are non-powered (i.e. dry contacts) and are rated 10A/240VAC, 8A/28VDC  
resistive (3A inductive, 0.4pf). Output contacts are not fused therefore external overcurrent  
protection (maximum 10A) is required for all control circuits using these contacts. Contacts are  
shown in a de-energized state and will change state upon activation.  
Run  
The Run contact is a Form “A” dry contact to control the engines “Run” circuit. This typically includes external control devices  
such as “Fuel Rack Solenoids” or electronic governors.  
Note:  
Note:  
An additional pilot relay will be required to energize high current devices that exceed the 10A resistive rating. The run output  
control logic provides an “Energize To Run Signal“ (i.e. the run contact closes when a run condition is activated).  
For energize to stop control logic, refer to the programmable output control function.  
Crank  
The Crank output contact is a Form “A” dry contact and is used to control an external crank pilot relay that directly controls the  
engine starter motor.  
An external crank pilot relay is required to energize the high current starter motor pinion solenoid that exceeds the 10A  
resistive crank output contact rating. The crank output contact closes when a crank condition is activated and the contact will  
automatically open when crank disconnect speed is obtained and/or the generators output AC voltage exceeds 10% of  
nominal level. The generators output AC voltage is utilized for back-up crank disconnect protection should the speed sensor  
fail.  
Programmable Contacts  
Energize To Stop  
Four (4) standard programmable output contacts are provided, #1, #2, #3 and #4. Each programmable output is a Form “C”  
dry contact that is programmable for any of the following conditions:  
The output relay will energize when a stop signal has been activated. The output will remain energized for 10 seconds  
after the engine has come to a complete stop, then de-energizes.  
The output relay will energize when the controller's operation mode switch is not in the auto position.  
Switch Not In Auto  
Engine Ready  
The output relay will energize when the controller's mode switch is in the auto mode and no shutdown or alarm  
conditions are present.  
Preheat  
The output relay will energize during the start delay timer period and cranking period until the engine starts and reaches  
crank disconnect speed. The preheat output is typically used for an engine starting aid such as glow plugs.  
Note: An external pilot relay is required to switch the high current glow plug load.  
GEN Ready To Load  
The output relay will energize when the generators output voltage and frequency exceeds predetermined setpoints (e.g.  
voltage 90% nominal, frequency 95% nominal as user programmed) and a warm-up time delay period expires. After the  
output has energized, it will remain on (regardless of voltage/frequency levels) until the controller either has a  
stop/shutdown signal, or the engine's speed drops below crank disconnect level. The voltage, frequency and time delay  
levels are programmable. This output is typically used in an Auto Mains Failure (AMF) application.  
Utility Ready To Load  
The output relay will energize when the remote start input has not been activated (i.e. contact on terminals 16 & 17 not  
closed) and the Return Delay & Neutral Delays have expired (if programmed). The output will de-energize when the  
remote start input has been activated and the Engine Start Delay & Warm-Up Delays have expired (if programmed). This  
output is typically used for Auto Mains Failure (AMF) applications.  
Engine Running  
Engine Run (Fuel)  
The output relay will energize when the engine has started and has reached crank disconnect speed.  
The output relay will energize when the engine “RUN” (i.e. FUEL) energizes prior to the engine starting. The output will  
remain on until the engine has reached a “stop” or “shutdown” command.  
Airflap  
The output relay will energize when the engine's speed exceeds the overspeed setpoint level. The output will remain  
energized until the engine's speed drops below the low speed setpoint (typically 5% of rated speed).  
Note: An external pilot relay is required if the main air flap solenoid current rating exceeds the contact rating.  
ATS Test  
This feature is only operative if the remote transfer switch is interconnected with remote testing capability.  
The output relay will energize when a load test operating mode is selected by the “Load Test” keypad push-button. After  
initiated, the engine will receive a start signal from the transfer switch and when the generator reaches nominal voltage  
and frequency levels, a load transfer will be initiated. The generator set will remain running on load until a different  
operating mode is selected or the generator set develops an alarm or shutdown condition.  
Note 1: When the “Utility Ready to Load” and “Generator Ready to Load” outputs are programmed, the “Load Test”  
programmable output is not required as the engine starting logic is internally initiated.  
Note 2: When both “Utility Ready to Load” and “Generator Ready to Load” outputs are programmed for an AMF control  
configuration, the ATS Output is not used (i.e. engine start signal is internally generated).  
Oil Bypass Timer Complete The output relay will energize when the controller's oil bypass delay timer expires, following a normal start sequence.  
Common Alarm  
Common Fail  
The output relay will energize when any alarm fault has been activated.  
The output relay will energize when any alarm or shutdown fault has been activated.  
The output relay will energize when any shutdown fault has been activated.  
Common Shutdown  
EPS Supplying Load  
The output relay will energize when the engine is running and the generator is supplying current to the load more than or  
equal to 10% of nominal CT ratio.  
4‐20 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Display Modes The controller is in the display mode at all times except when in the programming mode. The  
display screens and menus may be selected by pressing the Enter or Exit keys to access  
Operating Status Display, Fault Display, Timer Countdown, Generator AC Metering or  
Programming Menus. The LCD display shows the status of the generator output:  
Operating Status The controller will power-up into an Emergency Stop failure mode, preventing possible engine  
operation. The controller must be manually reset before normal operation can be established. To  
reset the Emergency Stop condition, press the “OFF” push-button first, then press both  
“INCREMENT” and “ENTER” push-buttons simultaneously. The controller will then reset, if a  
remote emergency stop condition is not activated. The Utility Ready to Load programmable  
output will energize if the remote start contact is open. The Main LCD Display will be shown.  
Action  
Description  
Display  
Comments  
Apply Power and  
Reset faults.  
Main LCD Display.  
Vavg  
000  
Aavg  
000  
Freq  
000  
Press Enter key  
Press or key  
Press or key  
Press or key  
Press or key  
Show Operating Status screens  
Scroll to next.  
Controller is in “Auto” position and there  
are no active faults.  
UNIT READY  
Controller is in “OFF” position from the  
front panel keypad push-button.  
SWITCH IN OFF  
UNIT RUNNING  
Scroll to next.  
Engine is running and all conditions are  
normal.  
Scroll to next.  
A shutdown fault is active. The specific  
fault will be automatically displayed.  
UNIT SHUTDOWN  
UNIT ALARM  
Scroll to next.  
One or more faults are active. The  
display will automatically scroll through  
all active faults at a two second rate.  
Fault Display The fault display menu is automatically displayed when an alarm or shutdown fault is activated.  
The specific alarm or shutdown fault label will be displayed and if multiple alarm conditions are  
present, the display will automatically scroll through all active faults.  
MN2408  
Operation 4‐21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Timer Countdown Timer countdown menus are automatically displayed when a specific time delay function  
occurs during a control sequence. When a time delay begins, the LCD display will show the time  
delay function name (i.e. Engine Start Delay) and the current time remaining in the countdown  
sequence. When the timing function has expired, the LCD display will automatically change to  
either the next timing sequence countdown display or return to the original system status menu.  
Action  
Description  
Display  
Comments  
Apply Power and  
Reset faults.  
Main LCD Display.  
Vavg  
000  
Aavg  
000  
Freq  
000  
Show Operating Status screens  
Other time delay functions are:  
Displays specific time delay function  
name and remaining time.  
ENGINE START  
DELAY 45 SEC  
ENGINE START  
DELAY 45 SEC  
CRANK PERIOD  
XX SEC  
REST PERIOD  
XX SEC  
STARTER RE-ENGAGE  
DELAY XX SEC  
BYPASS  
DELAY XX SEC  
COOLDOWN  
DELAY XXXX SEC  
WARMUP  
DELAY XX SEC  
RETURN  
DELAY XX SEC  
NEUTRAL  
DELAY XX SEC  
Note: Countdown screens only appear if Utility/Gen Ready To Load outputs are programmed.  
4‐22 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Generator AC Metering The controller is in the display mode at all times except when in the programming  
mode. The display screens and menus may be selected by pressing the Enter or Exit keys to  
access Operating Status Display, Fault Display, Timer Countdown, Generator AC Metering or  
Programming Menus. The LCD display shows the status of the generator output:  
Generator Average Output Display  
Vavg  
000  
Aavg  
000  
Freq  
000  
Average Voltage  
Average Current  
Displays the average generator voltage as follows:  
3-phase system: AVERAGE LINE TO LINE VOLTAGE--Phases  
1-phase system: LINE TO LINE VOLTAGE--Phases A to B  
Displays the average generator current as follows:  
3-phase system: AVERAGE LINE CURRENT--Phases A,B,C  
1-phase system: AVERAGE LINE CURRENT--Phases A,B  
Displays generator frequency in hertz (HZ). The frequency is displayed with a resolution of 1/10 of a hertz.  
Frequency  
Generator KVA Display  
KVA  
632.23  
KVA  
Displays the generator's total power output in kilo-voltamperes (KVA).  
Generator Phase Voltage Display  
(Line to Line)  
Vab  
600  
Vbc  
600  
Vca  
600  
Vab  
Vbc  
Vca  
Displays the generator's output voltage:  
3-phase system: LINE TO LINE VOLTAGE--Phases A to B  
1-phase system: LINE TO LINE VOLTAGE--Phases A to B  
Displays the generator's output voltage:  
3-phase system: LINE TO LINE VOLTAGE--Phases B to C  
1-phase system: LINE TO NEUTRAL VOLTAGE--Phases A-N  
Displays the generator's output voltage:  
3-phase system: LINE TO LINE VOLTAGE--Phases C to A  
1-phase system: LINE TO NEUTRAL VOLTAGE--Phases B-N  
Generator Phase/Neutral Voltage Display  
(Line to Neutral)  
Van  
347  
Vbn  
347  
Vcn  
347  
Note: The generator's neutral must be connected to controller terminal TB1-VN and the “neutral connected” prompt in the main  
program menu must be selected as “Yes”.  
Van  
Vbn  
Vcn  
Displays generator voltage Phase A to Neutral.  
Displays generator voltage Phase B to Neutral.  
Displays generator voltage Phase C to Neutral.  
Generator Phase Current Display  
a
408  
b
451  
c
415  
Amps  
Amps a  
Amps b  
Amps c  
Displays generator load current as follows:  
3-phase system: PHASE A CURRENT  
1-phase system: PHASE A CURRENT  
Displays generator load current as follows:  
3-phase system: PHASE B CURRENT  
1-phase system: PHASE B CURRENT  
Displays generator load current as follows:  
3-phase system: PHASE C CURRENT  
1-phase system: not applicable  
Generator Frequency/Hourmeter Display  
FREQ 60.1 Hz  
HOURS 56788 Hrs  
FREQ  
HOURS  
Displays generator frequency in hertz (HZ). The frequency is displayed with a resolution of 1/10 of a hertz.  
Displays unit operating hours.  
MN2408  
Operation 4‐23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Engine Parameter Display Two engine operating parameter screens are provided.  
Battery Voltage/Engine Speed  
(Tachometer)  
BATTERY 27.0 Vdc  
SPEED 1800 rpm  
Battery  
Speed  
Displays battery voltage in DC volts. The voltage is displayed with a resolution of 1/10 of a volt.  
Displays engine speed in revolutions per minute (RPM).  
Engine Temperature/Oil Pressure  
ENG TEMP  
OIL PRESS  
57 Deg C  
200 KPA  
ENG TEMP  
OIL PRESS  
Displays engine temperature in either degrees Celsius or Fahrenheit (as selected).  
Displays engine oil pressure in either pounds per square inch (PSI) or in Kilopascals (KPA) (as selected).  
Program Menus The programming menu is used to change values such as time delays, analog fault settings,  
digital fault settings. Access to the programming sub-menus may only be obtained with a  
security password number. The sub menus are organized as follows:  
Program Menu  
PROGRAM MENU?  
NO  
Displays two messages that may be toggled between YES and NO by pressing the INCREMENT push-button.  
NO Programming sub-menus are disabled when NO is displayed.  
YES Programming sub-menus are enabled when YES is displayed and a valid password number is entered.  
PASSWORD  
0
Press INCREMENT or DECREMENT to change the password. Press ENTER when the correct number is displayed.  
Read Only Mode  
User can view the parameters but cannot change any values. The factory setting for this level is one (1).  
Read / Write Mode  
User can view and modify any parameter value. The factory setting for this level is two (2).  
Master Read / Write Mode  
User can view and modify any parameter value and view/modify the security password level numbers.  
Contact Baldor for master password if required.  
The values of the parameter settings for your generator-set can be recorded for future reference  
After the correct password number is entered, the you may choose one of four programming  
menus. Press INCREMENT or DECREMENT to find the desired menu then press ENTER.  
MAIN MENU LOOP  
ANALOG FAULT MENU LOOP  
DIGITAL FAULT MENU LOOP  
CALIBRATION MENU LOOP  
4‐24 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Navigation Hints  
Programming parameters are displayed in the same order as the Programming Sheets (see  
Figures 4‐17 to 4‐20). To skip over parameters that do not require changes, push and hold the  
ENTER push-button until the desired parameter is displayed. The EXIT push-button may be  
used to scroll backwards through the programming parameter loops.  
To change a parameter value, use the INCREMENT or DECREMENT push-buttons to scroll  
through the available options or to adjust a value as desired and press the ENTER to accept the  
new value.  
Note: If programming mode is terminated before the last change is accepted (pressing ENTER),  
that parameter value will remain unchanged.  
Main Menu Loop The Main Menu Loop contains general system configuration programming such as system input  
voltages, currents, transformer ratios, as well as standard operating time delay functions.  
System Voltage  
Set to nominal system voltage as expressed in phase to phase voltage (i.e. a 347/600 volt system would be entered as  
600). The programmable range of values is 120V-15,000V.  
Set to nominal system frequency of either 50 HZ or 60 HZ.  
System Frequency  
System Phases  
Neutral Connected  
Set to match the power distribution system used on the generator set (i.e. either single phase or 3 phase system).  
Set to Yes if generator's neutral conductor is connected to controller terminal TB1-VN and it is desired to display  
line-neutral AC voltages for a 3 phase, 4 wire system.  
Voltage Sensing Ratio For direct voltage sensing wiring connections from 208 to 600 volts, enter 1 (i.e. a ratio of 1:1). When potential  
transformers are utilized for voltage sensing, enter the calculated transformer ratio (e.g. when using 600:120  
transformers, enter a number of 5).  
Current Sensing Ratio  
Temperature Scale  
Pressure Scale  
For current sensing wiring connections from current transformers (CT's), enter the calculated CT ratio (e.g. when using a  
600:5 CT, enter a number of 120).  
Select the desired units for engine temperature display and analog setpoints: Degrees Fahrenheit or Degrees Celsius.  
Note: Alarm setpoints do not automatically re-configure when changing between Fahrenheit or degrees Celsius.  
Select the desired units for engine pressure display and analog setpoints: Pounds per square inch (PSI) or Kilopascals  
(KPA). Note: Alarm setpoints do not automatically re-configure when changing between PSI and KPA.  
Start Delay  
Select desired engine start delay time in seconds. If engine start delay is not required, set to zero. Note: If preheat and  
or prelube functions are used, the engine start delay time should be set as required for these functions.  
Select desired cranking time in seconds. If cycle cranking is selected, this time will be the crank time per attempt.  
Crank Time  
Rest Time  
Select desired rest time between cranking attempts. (Only valid if multiple crank attempts are selected).  
Note: This value will be ignored if only one attempt has been programmed.  
Starter Re-Engage Duration This feature checks for a speed signal during cranking. If no speed signal is sensed, the controller assumes that the  
engine starter is not turning the engine over and disengages it after the programmed time delay, and re-engages it  
again. This process will repeat until a speed signal is sensed or cranking time expires, whichever occurs first.  
If a speed signal is sensed, cranking continues until the engine starts or an overcrank condition occurs.  
Set time in seconds as desired (i.e. a setting of 5 seconds will attempt cranking for 5 seconds after which time if no speed  
signal is detected, the crank output will be removed for a preset 1 second delay before re-engaging.)  
Note: This action is more than a cycle cranking function and is independent of the number of attempts selected.  
Therefore, the “crank” time should be considered. To disable this feature, set to zero.  
Number Of Crank Cycles Set to the number of cranking cycles required. (Zero will default to one.)  
Bypass Delay  
This setting is the time period that Alarm or Shutdown faults will be ignored after crank disconnect, allowing the engine to  
settle into its normal operating mode (i.e. proper oil pressure, etc.). Typically 10 seconds.  
Cool down Time  
Set to desired cool down time in seconds. Up to 9999 seconds of cool down time may be programmed. Set to zero if not  
required.  
Note: If the controller is used in an AMF application it is recommended to set the cool down timer to a minimum of 10  
seconds to allow the generator to transfer Off Load before enabling the cool down time. (Ensures the load is transferred  
off of generator prior to stopping the engine.)  
Nominal Engine RPM  
Flywheel Teeth  
Set to the nominal engine speed in revolutions per minute (RPM).  
Set to the number of ring gear teeth on the engine flywheel. The magnetic pick-up must be installed to sense the same  
teeth for speed sensing as programmed.  
Crank Disconnect Speed Set crank disconnect speed in percentage of nominal speed, i.e. 30% or 540 RPM on an 1800 RPM engine.  
Overspeed Set overspeed shutdown point in percentage of nominal speed (i.e. 110% or 1980 RPM on an 1800 RPM engine).  
Overspeed Transient Delay Select desired overspeed transient delay time in seconds. Time setting may be entered in tenths of seconds.  
Run Output Fail-safe  
When enabled (factory setting), this feature inhibits the run output until the controller receives a speed sensing signal.  
This prevents possible damage caused by starting the engine with no speed sensing for crank disconnect and  
overspeed. If selected, ensure that the speed signal is not less than 3.0VAC from the magnetic pick up while the engine  
is cranking.  
Note: If this feature is disabled, no overspeed protection or crank disconnect will be provided if the speed signal fails. If  
you disable this feature Baldor strongly recommends that backup crank disconnect protection and additional overspeed  
protection is provided.  
MN2408  
Operation 4‐25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Main Menu Loop Continued  
Loss Of Speed Signal  
Select the desired action (i.e. alarm or shutdown) when a loss of speed signal is detected during operation.  
Note: A loss of speed signal must be detected for longer than 2 seconds to initiate the desired action.  
Common Fail For “Not In Auto” Function Selects if a common fail alarm condition is to be activated during manual operation.  
Horn For Not In Auto  
The Horn may be programmed to sound when the controllers operating mode is switched from the Auto position. If the  
Horn is not to sound, select program setting No.  
Warm-up Delay  
The WARM-UP Delay menu appears when the Gen Ready To Load programmable output is selected (typically for AMF  
application). Set to the desired time in seconds, which the generator requires to effectively “warm-up” before accepting  
load. This is typically set for 3 seconds. The Warm-Up Delay is initiated after the generator is above programmed voltage  
and frequency limits (per the analog programming menus).  
Neutral Delay  
The Neutral Delay menu appears when the Utility Ready To Load programmable output is selected (typically for AMF  
application). The Neutral Delay timer is used when transferring between the available power sources. When transferring  
from the utility supply to the generator supply, the Neutral Delay timer will start when the Utility Ready To Load output  
de-energizes. When the Neutral Delay time period expires, the Generator Ready To Load output is energized. The  
purpose of the Neutral Delay timer is to prevent out of phase transfers, which may be caused by a fast transfer and the  
two sources of supply are out of synchronism. The Neutral Delay timer ensures the load voltages decay before the  
transfer is initiated. Set to the desired time in seconds. The Neutral Delay timer is typically set for 3 seconds.  
Note: The Neutral Delay feature is only effective when an electrically held “contactor-type” transfer switch is connected.  
Contact Baldor for further application information on use with other types of transfer switch mechanisms.  
Return Delay  
The Return Delay menu appears when the Utility Ready To Load output is selected (typically for AMF application). The  
Return Delay is initiated when the remote start signal is removed (signaling utility power is available). After the Return  
Delay timer expires, the Generator Ready To Load output is removed, and the Utility Ready To Load output energizes to  
signal transfer the load back to the utility supply. The purpose of the Return Delay timer is to ensure that the utility power  
has returned to a steady state for the selected time period before the load is transferred back to the utility supply. The  
Return Delay timer is typically set for 120 seconds.  
Caution: The Programmable Output Contacts selection must agree with the external control wiring  
prior to energizing the controller. Failure to do so may cause severe equipment damage.  
Programmable Output Contacts Select the desired function that will activate the programmable relay output contact.  
One of the following functions may be selected:  
Energize To Stop  
Oil Bypass Timer Complete  
Overspeed  
Low Bat Voltage  
ATS Test  
Low Oil Press #2 Shutdown  
Gen Ready To Load  
Common Fail  
Engine Ready  
Preheat High Bat Voltage  
Low Oil Press #1 Alarm  
High Eng Temp #1 Alarm  
Air Flap Eps Supplying Load  
Digital Faults #1 to4  
Loss Of Speed Signal  
Engine Running  
Common Alarm  
High Eng Temp #1 Shutdown  
Utility Ready To Load  
Switch Not In Auto  
Engine Run (Fuel)  
Weak Bat Voltage  
Common Shutdown  
Reset Run Hours  
The hourmeter may be reset to zero hours when yes is programmed.  
Note: This programming prompt is only accessible while using the “Master” programming security password.  
Analog Fault Menu Loop The controller's analog fault settings are described as follows:  
Level  
Sets the actual analog signal setpoint at which the selected fault type will be activated.  
Note: For AC voltage fault circuits, two levels (i.e. pick-up & drop-out) must be programmed.  
Allows a fault to be either an Alarm fault or a Shutdown fault.  
Action  
Alarm Latch  
If an fault was set as an Alarm, it may be selected as a “Latching” alarm or “Non-latching” alarm. A Latching alarm is not  
cleared until a reset command clears it.  
Note: This value only appears if alarm faults are programmed. Shutdown faults are automatically set as latching.  
Bypass On Start Delay Allows the alarm or shutdown fault to be disabled until after the bypass timer has expired. Faults that are not delayed are  
enabled at all times (i.e. engine running or stopped).  
Transient Delay Times Allows the selected fault to be disabled until the delay period has expired. Delay times are 0.0 to 999.9 seconds.  
4‐26 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Digital Fault Menu Loop The controller's digital fault settings are described as follows:  
Caution: The Digital Fault Label selection must agree with the external control wiring prior to  
energizing the controller. Failure to do so may cause severe equipment damage.  
Digital Fault Label  
Select the desired fault label, these are stored in non-volatile memory.  
Air Damper Tripped  
Bat Chrg Trouble  
DC Fail  
High Oil Temp  
Low Coolant Level  
Low Fuel Level  
Low Oil Level  
Remote Emerg.stop  
Basin Rupture  
Fuel Leak  
Bat Charger Input Fail  
Breaker Tripped  
Failed To Sync  
High Winding Temp  
Low Engine Temp  
Low Fuel Press  
Low Oil Pressure  
Reverse Power  
ATS In Bypass  
Gen Breaker Open  
High Bearing Temp  
High Engine Temp  
High Fuel Level  
No Load Test  
Ground Fault  
High Cooler Vibration  
High Engine Vibration  
High Oil Level  
*Highintkmanftemp  
“Blank” (i.e. no text for unused inputs)  
Low Fuel Press  
Vent Damper Fail  
Bat Charger Fail  
Fail To Sync  
Allows a fault to be either an Alarm fault or a Shutdown fault.  
High Fuel Level  
Action  
Note: Any activated alarm or shutdown fault will energize the “Common fail” fault and sound the alarm horn.  
Alarm Latch  
If an fault was set as an Alarm, it may be selected as a “Latching” alarm or “Non-latching” alarm. A Latching alarm is not  
cleared until a reset command clears it.  
Note: This value only appears if alarm faults are programmed. Shutdown faults are automatically set as latching.  
Polarity  
Allows the digital fault circuit to be set for Open to Fail or Close to Fail sensing contacts.  
Bypass On Start Delay Allows the alarm or shutdown fault to be disabled until after the bypass timer has expired. Faults that are not delayed are  
enabled at all times (i.e. engine running or stopped).  
Transient Delay Times Allows the selected fault to be disabled until the delay period has expired. Delay times are 0.0 to 999.9 seconds.  
Idle Control Digital Input Programming When a digital input is set to Idle function, these settings must be programmed to ensure correct operation:  
Alarm  
No  
Action  
Alarm Latch  
Polarity  
Bypass On Start  
Transient Time  
Close  
No  
0.1  
Note: The corresponding digital output must also be programmed for IDLE to enable correct operation.  
No Load Test Control Digital Input Programming  
The No Load Test digital input feature is typically used in an AMF application where it is required to do an automatic  
timed No Load Test of the engine/generator set. A contact from an external exercise clock timer is required to be  
connected to the digital input circuit which is programmed for “No Load Test”. When a digital input is programmed as No  
Load Test, these settings must be programmed to ensure correct operation:  
Action  
Alarm Latch  
Polarity  
Alarm  
No  
Close Or Open (dependent on external circuit used)  
Bypass On Start  
Transient Time  
No  
0.1  
Calibration Menu Loop AC Voltage, AC current and battery voltage analog circuits are factory calibrated and  
should not require field calibration. If field calibration is required, refer to the calibration  
procedure.  
Voltage Sensing Calibration (Phase To Phase or Phase To Neutral)  
VOLTS AB ZERO  
99  
600V  
Displays the generator phase voltages to be calibrated.  
Displays the type of calibration function, either ZERO or SPAN.  
Displays the calibration correction factor number (0-255) used to obtain the correct voltage reading.  
Note: To correctly calibrate any of the voltage sensors, the ZERO function must be calibrated before the SPAN function.  
Displays the actual voltage measurement that will be the same value as shown on the MEC 2 display menus for  
generator supply. This voltage reading may be calibrated higher or lower by changing the correction factor number.  
Voltage Calibration Procedure  
Note: Zero Calibration must be completed before Span Calibration.  
Zero Calibration  
Connect an external AC voltmeter of adequate voltage range and accuracy to the MEC 2 controller terminals associated  
with the voltage phases to be calibrated. With the generator stopped, confirm there is Zero volts on the phases to be  
calibrated. In the programming mode, scroll to each of the desired generator supply voltage phases (i.e. phase to phase  
or phase to neutral) with the ZERO function selected. Use the INCREMENT or DECREMENT push-buttons to adjust the  
correction factor number to obtain zero volts on the right hand side of the display as confirmed with the external  
voltmeter. The factory default correction factor is 127. Increasing this will raise the displayed value, conversely  
decreasing this value will decrease the displayed value. Note: Adjusting the ZERO function with voltage applied will result  
in non-linear voltage readings.  
With the correct voltage displayed, press the ENTER push-button to accept the correction factor number. Record the  
correction factor number on the programming sheet for future reference. Repeat this procedure for all remaining phases.  
MN2408  
Operation 4‐27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Span Calibration  
Energize the generator supply voltage to the controller at nominal level. Note: It may be necessary to program the  
optional under and over voltage shutdowns as alarms to ensure the generator will continue to operate during calibration.  
Caution must be taken to ensure the generator output voltage is set within nominal limits. In the programming mode,  
scroll to the desired generator supply voltage phases with the SPAN function selected. Connect an external AC voltmeter  
of adequate voltage range and accuracy to the controller terminals associated with the voltage phases to be calibrated.  
Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number while observing the  
displayed voltage level. Adjust the correction factor number to obtain an identical voltage reading as measured with the  
external AC voltmeter. With the correct voltage displayed, press the ENTER push-button to accept the correction factor  
number. Record the correction factor number on the programming sheet for future reference.  
Note: When the span calibration setting is complete, re-confirm the zero calibration points. If the zero calibration setpoint needs  
further adjustment, the span calibration point must also be re-calibrated.  
Current Sensing Calibration To accurately calibrate the current sensors, an external test AC ammeter and current clamp  
is required, with an accuracy of 0.5% or better.  
CURRENT A ZERO  
99  
350A  
Displays the generator load current (phase A, B or C) to be calibrated.  
Displays the type of calibration function, either ZERO or SPAN.  
Displays the calibration correction factor number (0-255) used to obtain the correct current reading.  
Note: To correctly calibrate any of the current sensors, the ZERO function must be calibrated before the SPAN function.  
Displays the actual current measurement that will be the same value as shown on the MEC 2 display menus for  
generator supply. This current reading may be calibrated higher or lower by changing the correction factor number.  
Zero Calibration  
Span Calibration  
Connect an external AC ammeter with current clamp of adequate current range to the controller terminals associated with  
the current phases to be calibrated. With the generator stopped, confirm there is “0” current on the phases to be  
calibrated. In the programming mode, scroll to each of the desired generator supply current phases with the ZERO  
function selected. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number while  
observing the displayed current level. Adjust the correction factor until “0” amps is displayed.  
With the correct current displayed, press the ENTER push-button to accept the correction factor number. Record the  
correction factor number on the programming sheet for future reference. Repeat for each phase.  
Apply 50%-100% load to the generator set. It is recommended to load the generator set to 100% rated load for  
calibration purposes to obtain good accuracy throughout the full span of operation. Do not exceed the current rating of  
the CT. Non-linear output of the CT will result when the secondary current exceeds 5 amps and will similarly effect the  
displayed values.  
In the programming mode, scroll to the desired generator supply current phases with the SPAN function selected.  
Connect an external AC ammeter and current clamp of adequate current range to the controller terminals associated with  
the current phases to be calibrated. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor  
number while observing the displayed current value. Adjust the correction factor number to obtain an identical current  
reading as measured with the external AC ammeter. With the correct current displayed, press the ENTER push-button to  
accept the correction factor number. Record the correction factor number on the programming sheet for future reference.  
Repeat for each phase.  
Note: When the span calibration setting is complete, re-confirm the zero calibration points. If the zero calibration setpoint needs  
further adjustment, the span calibration point must also be re-calibrated.  
Battery Voltage Calibration To accurately calibrate the MEC 2 battery voltage sensor, an external test DC voltmeter is  
required, with an accuracy of 0.5% or better.  
BAT VOLTS SPAN  
99  
24.6V  
Displays the type of calibration function (SPAN).  
Displays the calibration correction factor number (0-255) used to obtain the correct voltage reading.  
Displays the actual battery voltage measurement that will be the same value as shown on the MEC 2 display menu.  
This voltage reading may be calibrated higher or lower by changing the correction factor.  
SPAN Calibration  
Energize the battery supply voltage to the controller and connect the external test DC voltmeter to the battery terminals,  
B+ and B-. In the programming mode, scroll to the battery span calibration point. Use the INCREMENT or  
DECREMENT push-buttons to adjust the correction factor number while observing the displayed battery voltage level on  
the MEC 2. Adjust the correction factor number to obtain an identical voltage reading as measured with the external DC  
voltmeter. With the correct voltage displayed, press the ENTER push-button to accept the correction factor number.  
Record the correction factor number on the programming sheet for future reference.  
4‐28 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Engine Temperature & Oil Pressure Calibration  
To accurately calibrate the controller's temperature sensor, an external temporary engine mounted  
temperature gauge is required. The external temperature gauge should be connected as close as possible  
to the temperature sender.  
To accurately calibrate the controller's pressure sensor, an external temporary engine mounted pressure  
gauge is required. The external pressure gauge should be connected as close as possible to the pressure  
sender.  
ENGINE TEMP  
127  
955C  
Displays the type of calibration function.  
Displays the calibration correction factor number (0-255) used to obtain the correct Temperature or Pressure reading.  
Displays the actual temperature or pressure measurement shown on the display menus.  
This reading may be calibrated higher or lower by changing the correction factor number.  
Engine Temperature  
The engine temperature analog circuit must be calibrated with the engine temperature sender mounted on the engine.  
Connect a temporary engine mounted temperature gauge of suitable accuracy and start the engine. After the engine  
reaches normal operating temperature, enter the programming mode and scroll to the “Engine Temperature Offset”  
calibration point. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number while  
observing the displayed temperature. Adjust the correction factor number to obtain the identical temperature reading as  
measured with the external temperature gauge. With the correct temperature displayed, press the “Enter” push-button to  
accept the correction factor number. Record the correction factor on the programming sheet for future reference.  
Oil Pressure  
Connect a temporary engine mounted pressure gauge of suitable accuracy and start the engine. After the engine  
reaches normal operating pressure and temperature, enter the programming mode and scroll to the “Engine Pressure  
Offset” calibration point. Use the INCREMENT or DECREMENT push-buttons to adjust the correction factor number  
while observing the displayed pressure. Adjust the correction factor number to obtain the identical pressure reading as  
measured with the external pressure gauge. With the correct pressure displayed, press the “Enter“ push-button to  
accept the correction factor. Record the correction factor on the programming sheet for future reference.  
Engine  
Temperature  
Sender  
Resistance  
Oil  
Pressure  
Sender  
Resistance  
5F  
5C  
200  
190  
180  
170  
160  
150  
140  
130  
120  
110  
100  
90  
Ohms  
20  
KPA  
1034  
965  
896  
827  
758  
689  
621  
552  
483  
414  
345  
276  
207  
138  
69  
PSI  
150  
140  
130  
120  
110  
100  
90  
Ohms  
38  
392  
374  
356  
338  
320  
302  
284  
266  
248  
230  
212  
194  
176  
150  
140  
122  
104  
86  
24  
42  
28  
48  
33  
54  
39  
62  
46  
70  
55  
79  
65  
80  
89  
76  
70  
101  
114  
127  
142  
160  
183  
206  
90  
60  
106  
147  
197  
290  
426  
622  
952  
1486  
2322  
3644  
6284  
50  
40  
80  
30  
70  
20  
60  
10  
50  
40  
30  
68  
20  
50  
10  
32  
0
Note: Sender resistance data shown are for Oil Pressure Sender p/n-003654 (Thompson p/n), Manufacturer- Datcon, p/n  
102227. Datcon Sender must be used with MEC software version 1.81 or greater (previous software versions cannot be  
used).  
MN2408  
Operation 4‐29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure 4‐16 Configuration Data Sheet  
j
j
j
j
j
j
j
j
j
4‐30 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 4‐17 Main Menu Loop Parameters  
Setting  
Parameter  
System Voltage (Line To Line)  
System Frequency  
Range  
XXXXX VAC  
50Hz/60Hz  
120-15000VAC  
Toggle Between 50/60 Hz  
Toggle Between 1 & 3 Phase  
Toggle Between Yes/No  
Voltage Sensing Pt Ratio  
Enter Number 1-208 (1=Direct)  
Current Sensing Ct Ratio  
Enter Number 1-999 (1=Direct)  
Toggle Between Deg C/Deg F  
Toggle Between Psi/Kpa  
0-999 Seconds  
System Phases  
1 Phase/3 Phase  
Neutral Connected  
Voltage Sensing  
Ratio XXX  
Current Sensing  
Ratio XXX  
Temperature Scale  
Pressure Scale  
Start Delay  
Deg C/Deg F  
PSI/KPA  
XXX Seconds  
XX Seconds  
XX Seconds  
XX Seconds  
XX Cranks  
Crank Time  
0-99 Seconds  
Rest Time  
0-99 Seconds  
Starter Re-engage Delay  
Number Of Cranks  
Bypass Delay  
0-99 Seconds 0=Disabled  
0-99 Times 0=Continuous  
0-99 Seconds  
XX Seconds  
XX Seconds  
XXXX RPM  
Cool down Delay  
Nominal RPM  
0-9999 Seconds  
0-4000RPM  
Flywheel Teeth (Engine Speed  
Sensing, Magnetic Pick Up  
XXX Teeth  
0-999 Teeth  
Crank Disconnect  
Overspeed  
XX %  
0-100%  
XX %  
100-150%  
Overspeed Transient  
Run Output  
X.X Seconds  
0.0-9.9 Seconds  
Fail Safe Yes/No  
Shutdown Alarm/Shutdown  
Not In Auto Yes/No  
Toggle Between Yes/No  
Toggle Between Alarm/Shutdown  
Toggle Between Yes/No  
Toggle Between Yes/No  
Common Fail (Factory setting)  
Common Fail (Factory setting)  
Common Fail (Factory setting)  
Common Fail (Factory setting)  
Common Fail (Factory setting)  
Common Fail (Factory setting)  
0-99 Seconds  
Loss Of Speed Signal  
Common Fail For  
Horn For Not In Auto  
Prog Output #1  
Prog Output #2  
Prog Output #3  
Prog Output #4  
Prog Output #5  
Prog Output #6  
Warm-up Delay  
Neutral Delay  
0-99 Seconds  
Return Delay  
0-999 Seconds  
Reset Run Hours  
Yes/No  
Access by Master Password Only  
Toggle Between Yes/No  
MN2408  
Operation 4‐31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 4‐18 Analog Fault Menu Loop Parameters  
Setpoint Level Setpoint Level Action  
Fault Name  
Input Analog  
Type  
Fault  
E=Enable  
D=Disable  
Alarm Latch  
Y=Yes  
N=No  
Bypass On  
Start  
Y=Yes  
N=No  
Transient  
Delay (Sec)  
(Pick-up)  
S=Shutdown  
A=Alarm  
(Drop-out)  
Under Voltage  
Under Frequency  
Weak Battery  
AC Voltage  
E*  
S
Y
Y
Y
N
Y*  
Y*  
N*  
N*  
5.0  
AC Frequency E*  
S
5.0  
DC Voltage  
DC Voltage  
E*  
E*  
18.0  
25.6  
N/A  
N/A  
A*  
A*  
3.0  
Low Battery  
Voltage  
120.0  
High Battery  
Voltage  
DC Voltage  
E*  
30.4  
N/A  
A*  
N
N*  
10.0  
Low Engine Temp Temp Sender E*  
95 °F  
198 °F  
N/A  
N/A  
A*  
A
Y
Y
N*  
Y
5.0  
2.0  
High ENG Temp #1 Temp Sender E*  
Alarm  
High ENG Temp #2 Temp Sender E*  
Shutdown  
206 °F  
30PSI  
20PSI  
N/A  
N/A  
N/A  
S
A
S
Y
Y
Y
Y
2.0  
2.0  
2.0  
Low Oil Press #1  
Alarm  
Press Sender E*  
Y*  
Y*  
Low Oil Press #2  
Shutdown  
Press Sender E*  
* Indicates parameter is non-programmable.  
Figure 4‐19 Digital Fault Menu Loop Parameters  
Fault Name  
Input #  
Action  
S=Shutdown  
A=Alarm  
Alarm Latch  
Y=Yes  
N=No  
Polarity  
O=Open  
C=Close  
Bypass On  
Start  
Y=Yes  
N=No  
Transient  
Delay (Sec)  
Low Oil Pressure  
High ENG TEMP  
Batt Chgr Input Fail  
Low Fuel Level  
1
2
3
4
S
S
A
A
-
O
O
C
C
Y
Y
N
N
0.5  
-
1.0  
Y
N
30.0  
0.1  
Figure 4‐20 Calibration Menu Loop Parameters  
Parameter  
Volts A-B  
Volts A-B  
Volts B-C  
Volts B-C  
Volts C-A  
Volts C-A  
Volts A-N  
Volts A-N  
Volts B-N  
Volts B-N  
Volts C-N  
Volts C-N  
Current A  
Setting  
Zero XXX  
Span XXX  
Zero XXX  
Span XXX  
Zero XXX  
Span XXX  
Zero XXX  
Zero XXX  
Zero XXX  
Zero XXX  
Zero XXX  
Zero XXX  
Zero XXX  
Span XXX  
Zero XXX  
Span XXX  
Zero XXX  
Span XXX  
Span XXX  
XXX  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXVAC  
XXXAAC  
XXXAAC  
XXXAAC  
XXXAAC  
XXXAAC  
XXXAAC  
XX.X VDC  
XXX C/F  
XXXX PSI/KPA  
Current A  
Current B  
Current B  
Current C  
Current C  
Battery Voltage  
Engine Temperature  
Oil Pressure  
XXX  
4‐32 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 4‐21 Engine Control Connections  
10A  
12VDC (24VDC)  
STARTING  
BATTERY  
1A  
1A  
1A  
-
+
GENERATOR  
OUTPUT VOLTAGE  
B +  
B -  
VA  
VB  
VC  
VN  
IA  
VA  
VB  
VC  
N
(DELETE PHASE VC  
FOR SINGLE PHASE  
SYSTEMS)  
GRD  
23  
24  
18  
19  
CRANK  
RUN  
CR  
CRANK PILOT RELAY  
RUN CIRCUIT  
GENERATOR OUTPUT  
CURRENT SENSING  
TRANSFORMERS  
5 Aac SECONDARY  
(DELETE PHASE C  
FOR SINGLE PHASE  
SYSTEMS)  
φA  
φB  
φC  
RUN CIRCUIT  
(FUEL SOL., GOV.)  
IB  
SPEED SENSING  
MAGNETIC PICKUP  
IC  
MP1  
MP2  
MEC 20  
IN  
GRD  
OIL PRESSURE SENDER  
37  
38  
13  
14  
15  
16  
17  
1
GRD  
ENGINE TEMPERATURE SENDER  
25  
26  
COMMON FAIL CONTACT  
(OPERATES ON AN ALARM OR  
SHUTDOWN CONDITION)  
REMOTE EMERGENCY STOP  
(CLOSE TO STOP)  
(25, 26, 27 Not used in MEC 2)  
REMOTE FAULT RESET  
(CLOSE TO RESET)  
27  
28  
29  
30  
31  
32  
REMOTE START CONTACT  
PROGRAMMABLE  
CONTACT #1  
DIGITAL FAULT INPUT  
CONTACTS  
(MEC 2 = 1-4  
2
MEC20 = 1-12)  
3
PROGRAMMABLE  
CONTACT #2  
4
33  
34  
5
6
PROGRAMMABLE  
CONTACT #3  
7
35  
8
36  
(Not used in MEC 2)  
9
22  
21  
10  
11  
12  
PROGRAMMABLE  
CONTACT #4  
20  
MN2408  
Operation 4‐33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4‐34 Operation  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Section 5  
Troubleshooting and Maintenance  
Maintenance  
This manual contains only very minimal engine maintenance instructions. Refer to the engine  
manufacturer's owner's manual for specific engine maintenance instructions for your generator  
set. Any maintenance instructions or recommendations in the engine owner's manual take  
precedence over any of the following general recommendations.  
General:  
1. Inspect the fuel system for leaks. Replace all defective components immediately.  
2. Inspect and replace any fuel line that shows signs of deterioration.  
3. Inspect all the fuel clamps to ensure they are tight.  
4. Inspect and clean the battery posts and the associated battery cable terminals.  
5. Inspect the external wire cables and connectors used with the generator set for cuts,  
fraying, or loose connections. Repair or replace any problems prior to using the unit.  
Engine:  
1. Clean and/or replace any fuel, oil, and/or air filters per the engine manufacturers'  
guidelines.  
2. Check oil level regularly; at least every 5 to 8 operating hours. Maintain the proper oil  
level.  
3. Change the oil as is recommended in the engine manufacturer's owner's manual.  
4. Replace the spark plug(s) as is recommended by the engine manufacturer.  
5. Clean the cooling fins on the engine to keep the engine's heat dissipation potential at  
it's maximum.  
6. Inspect and clean all governor and carburetor linkages so they operate properly.  
7. Inspect the recoil starting rope for any damage and replace it if necessary (if  
applicable).  
8. Clean the trash screen around the recoil starter or other cooling air intake.  
Alternator: ( also called Generator End)  
This generator set must be run at its proper speed to obtain the correct electrical power at its  
output. All engines have a tendency to slow down when a load is applied to it. The engine  
governor is designed to hold the operating speed as nearly constant as possible. When the  
electrical load is increased, the engine is more heavily loaded and engine speed drops slightly.  
This slight decrease in engine speed results in a slight decrease in generator voltage and  
frequency output. This voltage and frequency variation has no appreciable effect in the operation  
of motors, lights, and most appliances and tools. However, timing devices and clocks will not  
keep perfect time when used on this generator.  
1. Clean the generator set and remove any and all dust, dirt, or other foreign material.  
2. Inspect and clean the cooling air intake and exhaust louvers of the generator end.  
Make sure they are clean. Remove dirt or any buildup that may restrict the cooling air  
flow.  
3. Clean the generator set and its components with a damp cloth or sponge.  
Never use a water hose or pressure washer as this may damage electrical  
components.  
4. Inspect and replace any control panel components that are broken or not working  
properly (receptacles, circuit breakers, switches, etc.)  
MN2408  
Troubleshooting and Maintenance 5‐1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Problems and Solutions  
Some of the more common problems are listed in Table 5‐1. This information is intended to be a  
check or verification that simple causes can be located and fixed. It is not an exhaustive “how to”  
for all types of problems. Procedures that require in depth knowledge or skills (like flashing the  
field) should be referred to a qualified generator service center.  
Table 5‐1 General Troubleshooting Guide  
Problem  
Possible Cause  
Remedy  
Engine cranks but will not start  
No fuel.  
Check that fuel valves are ON. Check fuel level in fuel tank.  
Low Oil Pressure Sutdown activated. Replensih oil to full.  
Check/replace air filter.  
Check/replace spark plug(s).  
Check that engine switch is in Start position.  
The magnetic pickup must be correctly adjusted and operating.  
Low Oil Level  
Restricted air flow.  
No spark.  
No engine speed during crank  
Dead battery.  
Engine will not crank (electric start)  
Remove battery and trickle charge or replace with new battery.  
Never Jump Start.  
Reset controller after an Emergency Stop.  
Emergency Stop LED is ON  
Fuel or ignition problem  
Engine starts but will not run smoothly  
Engine overheats  
Refer to engine manual.  
Excessive load  
Debris or dirt buildup on engine  
Remove one or more electrical loads.  
Remove debris. Clean engine surfaces to allow cooling.  
No output voltage  
Ciruit Breaker tripped or failed.  
Internal failure of Alternator  
Reset circuit breaker or replace if required.  
Return to factory for repair.  
Output voltage varies  
Irregular speed (fixed speed mode)  
Fluctuating speed (fixed speed mode)  
Check engine for malfunction or load for fluctuation  
Stabilize load. The addition of a lamp load (resistance load) may  
compensate partially for load changes caused by intermittent motor  
operation. Do not overload.  
Loose terminal or load connections  
Verify all connections and terminal tighness.  
Low output voltage  
Low engine speed  
Excessive load  
High resistance connections -  
connections will be warm or hot  
Verify engine RPM.  
Check engine for malfunction or system for overload. Reduce load.  
Verify all connections and terminal tighness.  
Internal failure of Alternator  
Low power factor  
Return to factory for repair.  
Reduce inductive (motor) load. Some AC motors use about the  
same current regardless of load. Do not use motors of greater  
horsepower rating than is necessary to move the mechanical load.  
High output voltage  
Excessive speed (fixed speed mode)  
Check engine for malfunction. Verify engine RPM.  
Electrical shock when frame is touched  
Static charge.  
Grounded armature or field coil.  
Ground generator frame at local reference ground (see Section 3).  
Return to factory for repair  
Mechanical noise  
Internal failure of Alternator  
Loose or misaligned coupling  
Return to factory for repair  
Tighten; align coupling and alternator shaft to engine shaft.  
5‐2 Troubleshooting and Maintenance  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Table 5‐2 Troubleshooting Guide (Digital Controller Only)  
Problem  
Possible Cause  
Remedy  
Controller does not power up even with  
correct DC power applied  
Wiring Mistake  
Check that there are no wiring errors/short circuits connected to the  
controller.  
Overload Condition  
The MEC 20 contains an electronic fuse that trips when an overload  
condition exists and does not reset until the supply voltage is  
removed and reapplied after the overload condition is corrected.  
LCD Display cannot be viewed  
Microprocessor failure  
Check that the controller's microprocessor is running by observing a  
red flashing “watchdog” LED on the rear of the PCB. Replace  
controller if failed.  
Improper Supply Voltage  
Improper contrast adjustment  
Check DC supply voltage at terminals B+ & B- (10-30VDC).  
Adjust LCD contrast potentiometer (R115) on rear of PCB for best  
display.  
Controller cannot be “Reset”  
No “RUN” output signal  
Engine not stopped  
Controller not in OFF mode  
Verify the engine is at a complete stop before trying to reset.  
Set the controller to the OFF mode before trying to reset.  
“Shutdown Faults” not reset  
Engine speed not detected at cranking  
All shutdown faults must be reset (red shutdown LED must be off).  
Engine speed signal must be detected (speed signal green LED on)  
during cranking if the “run-output fail safe” feature is enabled. Verify  
correct magnetic pickup signal at cranking (2.0VAC min. during  
cranking).  
Run Contact not closing (terminals #18 & Check that the RUN output LED (on the rear of the PCB) is on.  
#19) If yes, verify relay contact operation on terminals #18 & #19.  
Replace controller if failed.  
Overspeed shutdown occurs at normal  
speed  
Controller programmed values are wrong Verify the controller programmed values are correct for the number  
or controller has failed. of flywheel teeth, nominal RPM, and overspeed setpoint  
percentage. Replace controller if failed.  
Voltage or current metering is incorrect  
Controller programmed values are wrong Verify the controller programmed values are correct for the voltage  
sensing PT ratio and/or current sensing CT ratio.  
Ground is missing  
Verify that the battery supply DC negative conductor is properly  
grounded to the engine block (i.e. to a common ground point).  
Verify that the controller's analog input is properly calibrated.  
Verify the voltage sensing wiring connection to the MEC 20 matches  
power distribution type.  
Analog input needs to be calibrated  
Voltage sensing wiring mistake  
Note: standard direct voltage connection requires that the  
generators neutral is solidly grounded.  
Engine temperature or oil pressure  
display is incorrect  
Analog input needs to be calibrated  
Failed engine sensor  
Verify that the controller's analog input is properly calibrated.  
Verify engine sensors.  
Note: engine sensors must be factory supplied units only.  
Verify that the battery supply DC negative conductor is properly  
grounded to the engine block (i.e. to a common ground point).  
Ground is missing  
Engine temperature or oil pressure  
displays 9999  
OR  
Engine alarms are ON for high engine  
temperature or low oil pressure when  
engine is operating properly  
Sending unit is disconnected (open  
circuit)  
Defective sending unit  
Verify the sending units wiring to controller terminals #37 & #38 (i.e.  
wiring is not open or shorted).  
Verify the engine mounted senders have correct resistance values  
for corresponding input temperature or pressure.  
Verify calibration.  
Wrong Temp or pressure calibration  
Keypad not connected to controller  
Keypad Buttons (switches) do not  
operate.  
Verify the interconnecting ribbon cable between the lexan faceplate  
and main printed circuit board is correctly connected.  
Replace controller if failed.  
MN2408  
Troubleshooting and Maintenance 5‐3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Note: See Engine Controller manual for additional information.  
Table 5‐3 Troubleshooting Guide (Analog Controller Only)  
Problem  
Possible Cause  
Remedy  
Controller cannot be “Reset”  
Engine not stopped  
Controller not in OFF mode  
Verify the engine is at a complete stop before trying to reset.  
Set the controller to the OFF mode before trying to reset.  
Engine alarms are ON for high engine  
temperature or low oil pressure when  
engine is operating properly  
Sending unit is disconnected (open  
circuit)  
Defective sending unit  
Verify the sending units wiring to controller terminals is not open or  
shorted.  
Verify the engine mounted senders have correct resistance values  
for corresponding input temperature or pressure.  
Overspeed shutdown occurs at normal  
speed  
Controller has failed or input from  
Magnetic pickup is incorrect.  
Verify the adjustments. Replace controller if failed.  
Service  
Parts  
Service for your generator can be obtained from to a qualified generator service center.  
Please have the following information available and ready:  
The model number and serial number of the generator set.  
A complete and accurate description of the problem.  
Parts for your generator can be obtained from to a qualified generator service center.  
Please have the following information available and ready:  
The model number and serial number of the generator set.  
A complete and accurate description of the part (part number if known).  
Note: Engine parts can usually be obtained from a local distributor by using the information in  
the engine manufacturer's owner's manual.  
5‐4 Troubleshooting and Maintenance  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix A  
Options & Accessories  
Battery Charger  
BTCGR6 Battery Charger - 12 Volt / 6 Amp Float. Includes 6 ft power cord with grounding plug  
for AC input power and 4 ft power cord with ring terminals for DC output. UL Listed.  
BTCGR10A Battery Charger - 12 Volt /10 Amp Float. Includes terminal strip for AC input power  
and DC output.UL Listed.  
Figure A‐1 Recommended Mounting Locations  
GLC30-45 Battery Charger  
Mounting Locations  
GLC60-105 Battery Charger  
Mounting Locations  
BTCGR6  
Battery  
Tray  
BTCGR10A  
Battery  
Tray  
BTCGR10A  
BTCGR6  
Installation Considerations:  
Shore power must be available (120VAC or 240VAC) to power the battery charger and other  
components that may be installed). Shore power outlets or wiring must be located close to  
Battery Charger.  
BTCGR6 Charger (refer to charger manual for specific details)  
2. Connect charger negative wire to battery ”-” negative terminal.  
3. Connect charger positive wire (with fuse) to battery ”+” positive terminal.  
4. Connect charger AC power cord to shore power outlet.  
BTCGR10A Charger (refer to charger manual for specific details)  
2. Connect charger negative wire (Black) to battery ”-” negative terminal.  
3. Connect charger positive wire (Red) to battery”+” positive terminal.  
4. Connect charger AC power cord to shore power outlet.  
MN2408  
Options & Accessories A‐1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Battery Heaters Battery Heater (BTHTR81) - 120 Volt / 80 Watt. Includes 6 ft power cord.  
Installation Considerations:  
Shore power must be available (120VAC or 240VAC) to power the battery heater and other  
components that may be installed). Shore power outlets or wiring must be located close to  
battery heater.  
Figure A‐2 Battery Heating Pad Installation  
BTHTR81 Heater  
1. Carefully disconnect the Negative battery terminal from the battery.  
2. Carefully disconnect the Positive battery terminal from the battery.  
3. Remove battery hold down bracket.  
4. Remove battery.  
should match the battery tray.  
6. Install battery on top of Heating Pad.  
7. Install battery hold down bracket.  
8. Carefully install the Positive battery terminal to the battery.  
9. Carefully install the Negative battery terminal to the battery.  
10. Connect the AC power cord to shore power outlet.  
A‐2 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Engine Block Heater  
Installation Considerations:  
Shore power must be available (120VAC or 240VAC) to power the block heater and other  
components that may be installed). Shore power outlets or wiring must be located close to block  
heater.  
Figure A‐3  
Catalog # G10A Block Heater (refer to block heater manual for specific details)  
2. Connect the inlet hose to the inlet hose bib on the block heater.  
3. Connect the outlet hose to the outlet hose bib on the block heater.  
4. Connect the AC power cord to shore power outlet.  
MN2408  
Options & Accessories A‐3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Silencers  
Refer to enclosure procedure to install silencer when enclosure is present.  
Industrial Silencer for Open Skid Mount Units - Provides silenced exhaust for up to 11 dBA  
sound attenuation. Kit includes engine adapters, flex pipe, clamps, silencer, and rain cap.  
Critical Silencer for Open Skid Mount Units - Provides silenced exhaust for up to 18 dBA sound  
attenuation. Kit includes engine adapters, flex pipe, clamps, silencer, and rain cap.  
Figure A‐4  
Industrial Silencer  
GLCIS-3SU-  
GLCIS-4SU-  
GLCIS-6SU-  
GLCIS-7SU-  
GLC10-25  
GLC30-45  
GLC60-90  
GLC100-105  
Critical Silencer  
GLCCS-4SU-  
GLCCS-6SU-  
GLCCS-7SU-  
GLC30-45  
GLC60-90  
GLC100-105  
1. Attach the Silencer to the Exhaust Output of the engine, refer to Figure B-4.  
2. Use correct size clamp to attach extension pipe to Exhaust Output pipe from engine.  
3. Be sure the Extension pipe fits securely over Exhaust Output pipe so that no exhaust  
leaks can occur.  
A‐4 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Fuel Strainers & Fuel Lines  
A fuel strainer and flexible fule line can be installed at the fuel pressure regulator to make  
connection to the fuel main shutoff valve easier. Either 1-1/4” or 2” fittings may be specified.  
Figure A‐5 Fuel Strainer and Flex Fuel Line Connections  
GLCFFL1 3/4” NPT Female fittings, 12” long  
GLCFFL2 1 - 1/4” NPT Female fittings, 18” long  
GLCFFL3 2” NPT Female fittings, 12” long  
GLCFFS1-  
GLCFFLS3  
3/4” NPT Fuel Strainer female Inlet, male outlet.  
2” NPT Fuel Strainer female Inlet, male outlet.  
Fuel Strainer  
Fuel Flex Line  
Installation: Use appropriate thread sealer as required by plumbing codes.  
1. Thread Fuel strainer onto NPT close pipe nipple.  
2. Install NPT close pipe nipple to Fuel strainer input.  
3. Thread Flex Fuel Line onto NPT close pipe nipple.  
4. Connect other end of Flex Fuel Line to site fuel supply pipe as required by plumbing  
codes.  
MN2408  
Options & Accessories A‐5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
E-Stop  
E-Stop Switch Kit - Mounts to Baldor supplied Enclosure to provide easy access to shut down  
engine with the press of a button. Connects to Remote Run Terminals on genset. Must be  
adapted for remote mounting when used with open skid mount units.  
Figure A‐6  
1
3
Installation:  
2. Mount the E-Stop Switch box to the enclosure,  
3. Install the E-Stop assembly into the E-Stop Switch box enclosure.  
4. Connect the E-Stop Switch cable into the connections for BW0052D.  
A‐6 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Remote Annuciators  
Remote Annunciator - For use with MEC2 Controller. Provides remote anunciation of faults and  
generator status. Up to 20 individual fault conditions are remotely monitored utilizing both visual  
LED lights & audible alarm annunciation. Lamp test and alarm horn silence pushbuttons are  
provided. Each fault is individually programmable for audible horn operation and alarm labels are  
field configurable. Requires 12VDC 100mA power supply to operate (engine starting battery can  
be power supply).”  
Figure A‐7 MEC2 Remote Annunciator  
Figure A‐8 Intelilite Remote Annunciator  
AB  
DC power  
supply  
+
120R *  
CAN bus Connection (200m Maximum)  
*
Only one 120R resistor can be connected  
to the CAN bus (If it is the last device on the  
network (termination).  
MN2408  
Options & Accessories A‐7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Radiator Duct Flange  
Radiator Duct Flange for Open Skid Mount - Provides easy connection to air ducting to carry  
away hot air from engine radiator. Duct flange mounts to front of engine radiator.  
Add 3” to length.  
Figure A‐9  
Table A‐1 Mounting Dimensions  
B
Generator  
GLC10-25  
A
C
3.00  
3.00  
3.00  
22.00  
20.00  
GLC30-60  
26.00  
26.38  
26.70  
29.50  
GLC80-100  
A‐8 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Enclosures  
Weather Resistant Enclosure - Heavy-duty 12 gauge hot rolled steel with welded corners and  
baked powder coat finish. Fasteners are zinc chromate plated and the locking latches are  
chrome plated on the lift off access doors. Silencer is mounted on top of reinforced pitched roof.  
Sound Attenuated Enclosure - Heavy-duty 12 gauge hot rolled steel with welded corners and  
baked powder coat finish includes sound deadening insulation for 15 dB of attenuation.  
Fasteners are zinc chromate plated and the locking latches are chrome plated on the lift off  
access doors. Silencer is internally mounted in end-housing unit located in front of the engine  
radiator.  
Figure A‐10 Generator Lifting  
GLC10-25  
GLC30-45  
GLC60-90  
GLC100-105  
H1=36.0”  
GLC10-25  
GLC30-45  
GLC60-90  
GLC100-105  
L1=11.75”  
H1=52.1”, H2=66.6”  
H1=64.2”, H2=76.8”  
H1=64.2”, H2=87.6”  
L1=30”, H2=52.0”  
L1=30”, H2=64.2”  
L1=30”, H2=64.2”  
MN2408  
Options & Accessories A‐9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A‐10 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Appendix B  
Series GLC Information & Wiring Diagrams  
GLC Circuit Breaker & Electrical Data  
Circuit Breaker Size  
Qty per Phase  
Min Wire Gauge OSH Plant  
Ampacity @125C  
90  
15  
20  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
2
2
2
2
3
3
3
3
4
4
5
6
7
8
#16  
#16  
#14  
#12  
#10  
#8  
1 - #8 EPDM PER PHASE  
1 - #8 EPDM PER PHASE  
1 - #8 EPDM PER PHASE  
1 - #8 EPDM PER PHASE  
1 - #8 EPDM PER PHASE  
1 - #8 EPDM PER PHASE  
1 - #8 EPDM PER PHASE  
1 - #8 EPDM PER PHASE  
1 - #6 EPDM PER PHASE  
1 - #6 EPDM PER PHASE  
1 - #6 EPDM PER PHASE  
1 - #4 EPDM PER PHASE  
1 - #4 EPDM PER PHASE  
1 - #1 EPDM PER PHASE  
1 - #1 EPDM PER PHASE  
1 - #1 EPDM PER PHASE  
1 - #1/0 EPDM PER PHASE  
1 - #2/0 EPDM PER PHASE  
1 - #3/0 EPDM PER PHASE  
1 - #4/0 EPDM PER PHASE  
2 - #1/0 EPDM PER PHASE  
2 - #1/0 EPDM PER PHASE  
2 - #2/0 EPDM PER PHASE  
2 - #3/0 EPDM PER PHASE  
2 - #4/0 EPDM PER PHASE  
3 - #2/0 EPDM PER PHASE  
3 - #3/0 EPDM PER PHASE  
3 - #4/0 EPDM PER PHASE  
4 - #4/0 EPDM PER PHASE  
4 - #4/0 EPDM PER PHASE  
5 - #4/0 EPDM PER PHASE  
6 - #4/0 EPDM PER PHASE  
7 - #4/0 EPDM PER PHASE  
9 - #4/0 EPDM PER PHASE  
90  
30  
90  
40  
90  
50  
90  
60  
90  
70  
#8  
90  
80  
#6  
90  
90  
#6  
125  
100  
110  
125  
150  
175  
200  
225  
250  
300  
350  
400  
450  
500  
600  
700  
800  
900  
1000  
1200  
1400  
1600  
2000  
2500  
3000  
4000  
#6  
125  
#6  
125  
#4  
170  
#2  
170  
#2  
265  
#1  
265  
1/0  
2/0  
4/0  
4/0  
#1  
265  
305  
355  
410  
475  
1/0  
1/0  
3/0  
4/0  
2/0  
3/0  
3/0  
250  
4/0  
250  
250  
250  
250  
300  
610  
610  
710  
820  
950  
1065  
1230  
1425  
1900  
1900  
2375  
2850  
3325  
4275  
Wiring Diagrams Wiring diagrams for these generators are contained on the following pages of this appendix.  
MN2408  
Series GLC B‐1  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐11 Customer Interface Connection Diagram  
MEC20  
MEC2  
B‐2 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐12 Customer Interface (w/o Breaker) Power Connection Diagram  
MN2408  
Series GLC B‐3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐13 Single Phase - (w/o Breaker) Connection Diagram  
B‐4 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐14 Single Phase - One Breaker Connection Diagram  
MN2408  
Series GLC B‐5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐15 Single Phase - Two Breaker Connection Diagram  
B‐6 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐16 Single Phase Connection Diagram (Wire 1/0 and Larger w/Breaker)  
MN2408  
Series GLC B‐7  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐17 Single Phase Connection Diagram (Wire 1/0 and Smaller w/Breaker)  
B‐8 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐18 Single Phase Connection Diagram (Wire 1/0 and Smaller w/o Breaker)  
MN2408  
Series GLC B‐9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐19 Single Phase Connection Diagram (Wire Larger than 1/0 w/o Breaker)  
B‐10 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐20 Three Phase Connection Diagram  
MN2408  
Series GLC B‐11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐21 Three Phase Connection Diagram with PMG  
B‐12 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐22 Three Phase Connection Diagram (Wire 1/0 and larger)  
MN2408  
Series GLC B‐13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐23 Three Phase Connection Diagram (Wire Larger than 1/0 w/Breaker)  
B‐14 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐24 Three Phase Connection Diagram (Wire 1/0 and Smaller w/Breaker)  
MN2408  
Series GLC B‐15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐25 Three Phase Connection Diagram (Wire Larger than 1/0 w/o Breaker)  
B‐16 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐26 Three Phase Connection Diagram (Wire 1/0 and Smaller w/o Breaker)  
MN2408  
Series GLC B‐17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐27 Control Box Connections with MEC20 Controller  
B‐18 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐28 Control Box Connections with MEC20 Controller & Governor  
MN2408  
Series GLC B‐19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐29 Control Box Connections with MEC2 Controller  
B‐20 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐30 Engine Wiring, Woodward 4.3L GM  
MN2408  
Series GLC B‐21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐31 Engine Wiring, Woodward 5.7L GM  
B‐22 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Figure B‐32 Engine Wiring, Woodward 8.1L GM  
MN2408  
Series GLC B‐23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B‐24 Series GLC  
MN2408  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Baldor District Offices  
Download from Www.Somanuals.com. All Manuals Search And Download.  
WARNING:  
CALIFORNIA PROPOSITION 65 WARNING:  
Engine exhaust from this product contains chemicals known  
to the state of California to cause cancer, birth defects and  
other reproductive harm.  
WARNING:  
CALIFORNIA PROPOSITION 65 WARNING:  
Battery posts, terminals and related accessories are known to  
the state of California to cause cancer, birth defects and other  
reproductive harm.  
BALDOR ELECTRIC COMPANY  
World Headquarters  
P.O. Box 2400 Fort Smith, AR 72901-2400  
(479) 646-4711 Fax (479) 648-5792  
www.baldor.com  
© Baldor Electric Company  
MN2408  
All Rights Reserved. Printed in USA  
2/08  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Actiontec electronic Network Card 802CAT1 User Manual
ADS Technologies Switch USBH 2004 User Manual
Advantech Computer Hardware PCI 6872 User Manual
Agri Fab Lawn Mower Accessory 45 02932 User Manual
Airstream Clothes Dryer PNEG 339 User Manual
American Audio Musical Instrument XDM 3633 User Manual
ATI Technologies Home Theater System 137 40188 60 User Manual
Audiovox Remote Starter 128 8110 User Manual
Banner American Products Network Card Wireless Network User Manual
BC Speakers Speaker 15NW76 User Manual