SERIES
OTC25 N/L/P
DIGITAL TEMPERATURE
CONTROLLERS
Instruction
Manual
Download from Www.Somanuals.com. All Manuals Search And Download.
Table of
Contents
Installation
1
1
Mounting
Wiring
2
Operation
2
4
OTC25 N On/Off Controller
OTC25 L Limit Controller
OTC25 P PID Controller
5
7
Calibration
10
11
11
12
14
Error Codes
IEC Requirements
Warranty/Repair Information
Technical Specifications
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation
Pre-Installation Instructions
1. Inspect shipping carton for obvious signs of mishandling.
2. After removing the controller from the shipping carton,
inspect it carefully for damage. Never attempt to install and
use a damaged unit.
3. Verify that the ordering code number indicated on the side of
the controller matches what was ordered.
3.780”
3.5”
(88.9mm)
0.25”
(96mm)
(6.35mm)
°F
3.780”
(96mm)
ACTUAL
SETPOINT
01
02
Figure 1. Case Dimensions
Prior to mounting the OTC25 in your panel, make sure
that the cutout opening is of the right size, 3.622" x 3.622"
(92 mm x 92 mm), and deburred to enable a smooth fit.
A minimum of 5.0" (127.0 mm) of depth behind the panel
is required.
Mounting
Figure 2. Mounting Diagram
3.5”
(88.9mm)
(
3.780”
0.25”
(96mm)
(6.35mm)
3.780”
(96mm)
MOUNTING
SCREWS
ACTUAL
SETPOINT
HEAT
GASKET
BRACKET
PANEL
Before installing OTC25, ensure gasket seats evenly
around edges of unit and that there are no breaks or tears
in the gasket.
Insert the OTC25 through the front panel cutout, slide
mounting “U” bracket around unit and secure it with the
screws provided.
Gasket should be evenly compressed around all sides to
provide liquid-tight mounting.
1
Download from Www.Somanuals.com. All Manuals Search And Download.
Wiring
IMPORTANT: All electrical wiring connections should be made
only by trained personnel using Class 1 wiring, and in strict
accordance with the National Electrical Code and local regula-
tions. Both of the incoming power lines should be fused with
2AG, 0.5 A maximum rated fuses.
The OTC25 controller has built-in circuitry to reduce the effects
of electrical noise (RFI) from various sources;
however, power and signal wires should always be kept
separate. We recommend separating wires into one bundle for
power (from line power and output) and one bundle for signal
(from thermocouple).
The OTC25 power supply accepts 100 through 250 Vac and 120
through 250 Vdc line power without any switch settings or
polarity considerations.
COM.
OUTPUT #2
N.O.
COM.
OUTPUT #1
N.O.
L2
(-)
T/C
(+)
L1
Figure 3. Wiring Connections
Operation
Athena Series OTC25 Digital
Temperature Controller
Just a few easy steps are required before your OTC25
can be placed into service. After completing the mounting
and wiring procedures as previously instructed, set each
controller parameter using the simple front-panel keys
as instructed.
Power On
When power is first applied to the OTC25, all segments
of the LED display, as well as the discrete indicators, will be
momentarily illuminated while the instrument goes through a
series of diagnostic checks to verify proper operation of the unit.
A software version will then be displayed, e.g.,
. The last
two digits of this code indicate the software revision supplied
with your controller. Please provide this revision number when
contacting us regarding your unit. This display is followed by a
mnemonic code representing the OTC25 model type.
2
Download from Www.Somanuals.com. All Manuals Search And Download.
To enter the configuration menu, press and hold the Parameter
key for 10 seconds until the display changes to the parameter
mode. Press the Parameter key again to index through the avail-
able parameters. Pressing the Parameter Key for 3 seconds or
allowing 60 seconds of inactivity will cause the OTC25 N to exit the
menu system and return to normal operating mode.
OTC25 N
Operation
Parameter Range Range Display Options Default Default
°F
°C
°F
°C
Default
Display
Control
Hysteresis
2 to
252
1 to
140
Display
Offset
-126 to -70 to
126 70
Deviation
OFF, 1 OFF, 1
Band Alarm to 252 to 140
Display
Units
Low
Fixed
Fixed
Fixed
Fixed
Calibration
High
Calibration
Figure 5a. Series OTC25 N Parameters and Default Settings
Parameter Descriptions
Default Display
This parameter determines whether the OTC25 N’s display shows the
Setpoint or the actual temperature by default. Regardless of the selection
made here, the operator can observe the other value by momentarily
pressing the Parameter
Key. This will cause the alternate value to be
displayed for five seconds.
Control Hysteresis
Control Hysteresis is adjustable between 2 and 252° F (1 to 140° C ). This
parameter is used by the control algorithm to prevent rapid cycling of the
output around Setpoint. The default value is 4° F (2° C). This means the
heat will turn OFF when the Actual Temperature exceeds the Setpoint by 2°
F (1° C). Conversely, the heater will not turn ON until the Actual
Temperature drops 2° F (1° C) below the Setpoint.
Display Offset
Display Offset is adjustable from -126 to 126° F (-70 to 70° C). It can be
used to provide limited adjustment of the displayed temperature as a com-
pensation for offsets between the true temperature and the temperature
seen by the thermocouple.
3
Download from Www.Somanuals.com. All Manuals Search And Download.
Operation
°
Three-Digit
LED Display
Displays measured
temperature, setpoint,
or parameter labels
and settings.
ACTUAL
SETPOINT
HEAT
Figure 4. Front Panel Controls and Indicators
Parameter Key
Used to access available parameters to set or change values.
Raise Key
Used to scroll up through available parameter settings or to
increase values. (Hold for fast-step progression)
Lower Key
Used to scroll down through available parameter settings or
to decrease values. (Hold for fast-step progression)
Discrete LED Indicators
OTC25 N
OTC25 L
OTC25 P
Actual: amber
Setpoint: amber
Heat: orange
Actual: amber
Setpoint: amber
Limit: orange
Actual: amber
Setpoint: amber
Output 1: orange
Output 2: orange
OTC25 N
Operation
OTC25 N On/Off Temperature Controller
The Calibration High
and Calibration Low
selections are accessi-
ble only when the
calibration jumper is
installed as instructed
on page 10 (Figure 6).
Normal Operation
The factory default display setting of the OTC25 N is for Actual
Temperature
setpoint temperature by selecting Setpoint
Display parameter selection. When the Default Display is
changed to Setpoint, the setpoint temperature may be adjusted
by using the Raise or Lower keys. The setpoint is
. The default display may be changed to
at the Default
adjustable from 32 to 905° F (0 to 485° C).
When the Default Display setting is “Actual”
, adjustment
of the Setpoint may only be accomplished by pressing the
Parameter Key momentarily to switch the display to Setpoint,
and then using the Raise or Lower Keys
to change the Setpoint Value. The display will automatically
revert back to “Actual” five seconds after the last keypress.
Parameter Configuration
Your OTC25 N controller’s parameter selections are explained
on the next page, with default settings shown in Figure 5a.
4
Download from Www.Somanuals.com. All Manuals Search And Download.
OTC25 N
Operation
Deviation Band Alarm
A Deviation Band is a pre-set number of degrees, plus and
+
minus, around the Setpoint Value, ex. 10° F. A Deviation
Band Alarm provides an indication to the operator that the Actual
Temperature has either exceeded or dropped below the chosen
deviation. This parameter can be turned off
or adjusted
from 1 to 252° F (1 to 140° C). When the process variable is out-
side the deviation band, the alarm is indicated by flashing the
display (regardless of whether setpoint or actual temperature is
displayed) and the optional alarm output is activated.
Display Units
This allows the operator to have the display indicate either
degrees Fahrenheit or degrees Celsius.
OTC25 L
Operation
OTC25 L Limit Controller
Normal Operation
The factory default display setting of the OTC25 L is for Actual
Temperature
setpoint temperature by selecting Limit Setpoint
Default Display parameter selection.
When the Default Display is changed to Limit Setpoint, the limit
setpoint temperature may be adjusted by using the Raise or
Lower keys. The limit setpoint is adjustable from 32 to 905°
. The default display may be changed to
at the
F (0 to 485° C).
When the Default Display setting is “Actual”
, adjustment
of the Limit Setpoint may only be accomplished by pressing the
Parameter Key momentarily to switch the display to Limit
Setpoint, and then using the Raise or Lower Keys to
change the Limit Setpoint Value. The display will automatically
revert back to “Actual” five seconds after the last keypress.
Parameter Configuration
Your OTC25 L controller’s parameter selections are explained
on the next page, with default settings shown in Figure 5b.
To enter the configuration menu, press and hold the Parameter
key
for 10 seconds until the display changes to the parame-
ter mode. Press the Parameter key again to index through the
available parameters. Pressing the Parameter Key for 3 seconds
or allowing 60 seconds of inactivity will cause the OTC25 L to
exit the menu system and return to normal operating mode.
5
Download from Www.Somanuals.com. All Manuals Search And Download.
OTC25 L
Operation
Parameter Range Range Display Options Default Default
°F
°C
°F
°C
Default
Display
Limit
Setpoint
0 to
905
0 to
485
Operator
Selectable
Automatic
Startup
Reset
Display
Units
Low
Fixed
Fixed
Fixed
Fixed
Calibration
High
Calibration
Figure 5b. Series OTC25 L Parameters and Default Settings
Parameter Descriptions
Default Display
This parameter determines whether the OTC25 L’s display
shows the Limit Setpoint or the actual temperature by
default. Regardless of the selection made here, the operator
can observe the other value by momentarily pressing the
Parameter
Key. This will cause the alternate value to
be displayed for five seconds.
Limit Setpoint
The Limit Setpoint determines the temperature at which
the limit output will become inactive, interrupting power to
the process. It is operator-selectable from 32° to 905° F
(0° to 485° C).
Automatic Startup Reset
The automatic startup reset feature allows the limit output to be
automatically reset at startup or to be latched at startup. In the
latter condition, the limit output will have to be manually reset
before the limit output will be activated (relay closed allowing
power to flow to process heaters or coolers)
.
Display Units
This allows the operator to have the display indicate either
degrees Fahrenheit or degrees Celsius.
6
Download from Www.Somanuals.com. All Manuals Search And Download.
OTC25 P
Operation
OTC25 P PID Temperature Controller
Normal Operation
The factory default display setting of the OTC25 P is for Actual
Temperature
setpoint temperature by selecting Setpoint
Display parameter selection. When the Default Display is
changed to Setpoint, the setpoint temperature may be adjusted
by using the Raise or Lower keys. The setpoint is
. The default display may be changed to
at the Default
adjustable from 0 to 999° F (-17 to 537° C).
When the Default Display setting is “Actual”
, adjustment
of the Setpoint may only be accomplished by pressing the
Parameter Key momentarily to switch the display to
Setpoint, and then using the Raise or Lower Keys
to change the Setpoint Value. The display will automatically
revert back to “Actual” five seconds after the last keypress.
Parameter Configuration
Your OTC25 P controller’s parameter selections are explained
on the next page, with default settings shown in Figure 5c.
To enter the configuration menu, press and hold the Parameter
key
for 10 seconds until the display changes to the parameter
mode. Press the Parameter key again to index through the avail-
able parameters. Pressing the Parameter Key for 3 seconds or
allowing 60 seconds of inactivity will cause the OTC25 P to exit
the menu system and return to normal operating mode.
7
Download from Www.Somanuals.com. All Manuals Search And Download.
Parameter Range Range Display Options Default Default
°F °C °F °C
OTC25 P
Operation
Default
Display
Display
Offset
-126 to -70 to
126
70
Proportional 1 to
1 to
552
Operator
Selectable
Band
995
0 to
250 sec.
Rate
0 to
999 sec.
Reset
Heat Cycle
Time
0 to
120 sec.
Cool Cycle
Time
0 to
120 sec.
Deviation
Band Alarm
1 to
252
1 to
140
Operator
Selectable
Output 2
Configuration
Display
Units
Input
Type
Low
Fixed
Fixed
Fixed
Fixed
Calibration
High
Calibration
“J” TC
“K” TC
Figure 5c. Series OTC25 P Parameters and Default Settings
Parameter Descriptions
Default Display
This parameter determines whether the OTC25 P’s display
shows the Setpoint or the actual temperature by default.
Regardless of the selection made here, the operator can
observe the other value by momentarily pressing the
Parameter
Key. This will cause the alternate value to
be displayed for five seconds.
Display Offset
Display Offset is adjustable from -126 to 126° F (-70 to 70° C).
It can be used to provide limited adjustment of the displayed
temperature as a compensation for offsets between the true
temperature and the temperature seen by the thermocouple.
8
Download from Www.Somanuals.com. All Manuals Search And Download.
OTC25 P
Operation
Proportional Band
Proportional Band is a PID parameter that represents the amount of
deviation of the controlled variable required to move through the full
range, expressed in % of span or degrees of temperature. This para-
meter can also be expressed as “Gain” (the wider the band, the lower
the gain).
Rate
Rate is a PID parameter (Derivative Action) that produces a corrective
signal proportional to the rate at which the controlled variable is
changing. It is used to correct for overshoot and undershoot.
Reset
Reset is a PID parameter (Integral Action) that produces a corrective
signal proportional to the length of time and magnitude that the con-
trolled variable has been off setpoint. It is used to accommodate load
changes.
Heat Cycle Time
Heat Cycle Time is displayed in seconds, and can be set from 0 to 120
seconds. A setting of zero represents a heat cycle time of 300 mil-
liseconds.
Cool Cycle Time
Cool Cycle Time is displayed in seconds, and can be set from 0 to 120
seconds. A setting of zero represents a cool cycle time of 300 mil-
liseconds. This menu parameter will only be displayed if output 2 is
configured to be a cool output.
Deviation Band Alarm
A Deviation Band is a pre-set number of degrees, plus and minus,
+
around the Setpoint Value, ex. 10° F. A Deviation Band Alarm provides
an indication to the operator that the actual temperature has either
exceeded or dropped below the chosen deviation. This parameter can
be turned off
or adjusted from 1 to 252° F (1 to 140° C). When
the process variable is outside the deviation band, the alarm is indicat-
ed by flashing the display (regardless of whether setpoint or actual
temperature is displayed and activating an output, if configured as
such).
Output 2 Configuration
Output 2 may be configured as either a control output or as an alarm
output for the deviation band alarm. When configured for control, out-
put 2 acts as a cool PID output. When configured for an alarm, output
2 is activated when the deviation alarm is active and deactivated when
the deviation alarm is inactive.
Display Units
This allows the operator to have the display indicate either degrees
Fahrenheit or degrees Celsius.
Input Type
Sensor input type may be either a Type J or Type K thermocouple.
9
Download from Www.Somanuals.com. All Manuals Search And Download.
Calibration
Calibration
,
The Calibration High
and Calibration Low
selections are accessi-
ble only when the
calibration jumper is
installed (Figure 6).
Calibration of the OTC25 controller requires the operator
to apply two separate fixed and specific signals (Calibration
Low and Calibration High) from a reference source
(thermocouple calibrator) to the controller. The Raise
Key “tells” the controller to read the applied signal and use
it as a reference point.
Figure 6. Location of Calibration Jumper.
Calibration Procedure
1. Prior to applying power to the unit, install the calibration
jumper on the microprocessor board as shown in
Figure 6.
2. With the instrument still unpowered, connect a calibration
reference source to the thermocouple input terminals on the
OTC25.
3. Apply power. Allow at least 15 minutes for the controller to
warm up before continuing.
4. Using the Parameter
Key, index to the Calibration Low
parameter. The display will alternately flash this
mnemonic and the number “32” (“0” for Celsius units).
5. Adjust the reference source to output a voltage equivalent to
that generated by a “J” or “K” (OTC25 P) thermocouple at
32° F (0° C). Allow reference to settle for 10 seconds before
proceeding.
6. Press the Raise key
once to set this reference point. The
display will stop flashing momentarily while the
controller self-calibrates (approx. 3 seconds), and then
resume flashing.
7. Press the Parameter
Key, index to the Calibration High
10
Download from Www.Somanuals.com. All Manuals Search And Download.
Calibration
parameter. The display will alternately flash this
mnemonic and the temperature value it expects to see.
8. Adjust the reference source to output a voltage equivalent to
that generated by a “J” or “K” (OTC25 P) thermocouple at
the temperature flashing on the display. (Allow reference to
settle for 10 seconds before proceeding.)
9. Repeat Step 6 for this reference point.
10. Press the Parameter
Key for 10 seconds or allow
60 seconds of inactivity.
11. Adjust the reference source to output a voltage equivalent to
that generated by a “J” or “K” (OTC25 P) thermocouple at
32° F (0° C). Verify that (after settling), the OTC25
indicates a measured temperature of 32° F (0° C).
12. Repeat Step 11 for the upper reference point.
Error Codes
Display
Problem
Possible Solution
Broken thermocouple
lead wire or defective
sensor.
Verify wiring.
Replace sensor.
Input Signal is below
calibration of unit.
Verify Input Signal;
check calibration.
IEC
Requirements
USE OF THIS EQUIPMENT IN A MANNER NOT SPECIFIED BY
THE MANUFACTURER MAY IMPAIR PROTECTION PROVIDED
BY THE EQUIPMENT!
The maximum supply current is line voltage dependent:
60 mA for an 100-250 Vac input
fuse rating: 2AG, 0.5 A
Output Specifications
Output 1 Type Max current
Voltage
400 Vpk
380 V
Leakage
1 mA
—
T (Triac)
2 A
5 A
B (Relay)
Output 2 Type Max current
Voltage
400 Vpk
380 V
Leakage
1 mA
—
T (SSR)
0.5 A
5 A
B (Relay)
CLEANING INSTRUCTIONS
1. Remove power from the unit prior to any
cleaning operation.
2. Use a cotton cloth to gently and sparingly apply isopropyl
alcohol only. Do not use cleaners or other solvents as they
may damage the unit.
11
3. Allow the unit to dry completely prior to reapplying power.
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty/Repair
Information
Two-Year Limited Warranty
THIS EQUIPMENT IS WARRANTED TO BE FREE FROM DEFECTS
OF MATERIAL AND WORKMANSHIP. IT IS SOLD SUBJECT TO
OUR MUTUAL AGREEMENT THAT THE LIABILITY OF ATHENA
CONTROLS, INCORPORATED IS TO REPLACE OR REPAIR THIS
EQUIPMENT AT ITS FACTORY, PROVIDED THAT IT IS RETURNED
WITH TRANSPORTATION PREPAID WITHIN TWO (2) YEARS OF
ITS PURCHASE.
THE PURCHASER AGREES THAT ATHENA CONTROLS, INCORPO-
RATED ASSUMES NO LIABILITY UNDER ANY CIRCUMSTANCES
FOR CONSEQUENTIAL DAMAGES RESULTING FROM ITS USE OR
FROM IMPROPER HANDLING OR PACKAGING OF SHIPMENTS
RETURNED TO THE FACTORY.
COMPONENTS WHICH WEAR OR WHICH ARE DAMAGED BY MIS-
USE ARE NOT WARRANTED. THESE INCLUDE CONTACT POINTS,
FUSES, ELECTROMECHANICAL RELAYS, AND TRIACS. UNITS
WHICH HAVE BEEN MODIFIED BY A CUSTOMER IN ANY WAY
ARE NOT WARRANTED.
Other than those expressly stated herein, THERE ARE NO OTHER
WARRANTIES OF ANY KIND, EXPRESS OR IMPLIED, AND
SPECIFICALLY EXCLUDED BUT NOT BY WAY OF LIMITATION, ARE
THE IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR
PURPOSE AND MERCHANTABILITY.
IT IS UNDERSTOOD AND AGREED THE SELLER’S LIABILITY
WHETHER IN CONTRACT, IN TORT, UNDER ANY WARRANTY, IN
NEGLIGENCE OR OTHERWISE SHALL NOT EXCEED THE RETURN
OF THE AMOUNT OF THE PURCHASE PRICE PAID BY THE PUR-
CHASER AND UNDER NO CIRCUMSTANCES SHALL SELLER BE
LIABLE FOR SPECIAL, INDIRECT, INCIDENTAL OR CONSEQUEN-
TIAL DAMAGES. THE PRICE STATED FOR THE EQUIPMENT IS A
CONSIDERATION IN LIMITING SELLER’S LIABILITY. NO ACTION,
REGARDLESS OF FORM, ARISING OUT OF THE TRANSACTIONS
OF THIS AGREEMENT MAY BE BROUGHT BY PURCHASER MORE
THAN ONE YEAR AFTER THE CAUSE OF ACTION HAS ACCRUED.
SELLER’S MAXIMUM LIABILITY SHALL NOT EXCEED AND
BUYER’S REMEDY IS LIMITED TO EITHER (i) REPAIR OR
REPLACEMENT OF THE DEFECTIVE PART OR PRODUCT, OR AT
SELLER’S OPTION (ii) RETURN OF THE PRODUCT AND REFUND
OF THE PURCHASE PRICE, AND SUCH REMEDY SHALL BE
BUYER’S ENTIRE AND EXCLUSIVE REMEDY.
THE SPECIFICATIONS PUT FORTH IN THIS MANUAL ARE SUB-
JECT TO CHANGE WITHOUT NOTICE.
12
Download from Www.Somanuals.com. All Manuals Search And Download.
Warranty/Repair
Information
Unit Repairs
It is recommended that units requiring service be returned to an
authorized service center. Before a controller is returned for ser-
vice, please consult the service center nearest you. In many
cases, the problem can be cleared up over the telephone. When
the unit needs to be returned, the service center will ask for a
detailed explanation of problems encountered and a Purchase
Order to cover any charge. This information should also be put
in the box with the unit. This should expedite return of the unit
to you.
This document is based on information available at the time of
its publication. While efforts have been made to render accuracy
to its content, the information contained herein does not purport
to cover all details or variations in hardware, nor to provide for
every possible contingency in connection with the installation
and maintenance. Features may be described herein which are
not present in all hardware. Athena Controls assumes no obliga-
tion of notice to holders of this document with respect to
changes subsequently made.
Proprietary information of Athena Controls, Inc. is furnished for
customer use only. No other use is authorized without the writ-
ten permission of Athena Controls, Inc.
13
Download from Www.Somanuals.com. All Manuals Search And Download.
Technical
Specifications
Operating Limits
Ambient Temperature
Relative Humidity
Tolerance
32° F to 140° F (0° C to 60° C)
20% to 95%, Non-Condensing
85 to 250 V 10%, 50/60 Hz
(Single-Phase) 120 to 250 Vdc
Power
Sensor Range
Type J Thermocouple
OTC25 N/L: 6 to 926° F
(-14 to 496° C)
OTC25 P: 32 to 999° F
(0 to 537° C)
OTC25 P: 0 to 999° F
(-17 to 537° C)
Type K Thermocouple
Performance
Accuracy
0.3% of Full Scale
( 0.10% Typical), 1 Digit
1° F/C
Setpoint Resolution
Repeatability
1 Count
Temperature Stability
TC Cold-End Tracking
Noise Rejection
5 µV /° C (Maximum)
0.05° C /° C Ambient
100 dB Common Mode,
70 dB Series Mode
3.7 Hz (270 ms)
Temperature Sampling
Control Characteristics
Control Hysteresis
Display Offset
2 to 252° F (1 to 140° C)
-126 to 126° F (-70 to 70° C)
Mechanical Characteristics
Display
7-segment LED,
alphanumeric: 3 digits
0.56" (14.22 mm)
Orange
Display Height
Color
Front-Panel Cutout
3.622" x 3.622"
(92 mm x 92 mm)
Bezel Outside Dimensions 3.780" x 3.780"
(96 mm x 96 mm)
Bezel Height
Case Depth
Weight
Connections
Contacts
0.250" (6.35 mm)
3.515" (89.28 mm)
< 15 oz (425 g)
7
“Fast-On” .250” (6.35 mm)
14
Download from Www.Somanuals.com. All Manuals Search And Download.
Technical
Specifications
Input Source (Temperature Sensor)
Thermocouple Range:
Type J
OTC25 N/L:
6 to 926° F
(-14 to 496° C)
32 to 999° F
(0 to 537° C)
N/A
0 to 999° F
(-17 to 537° C)
OTC25 P:
Type K
OTC25 N/L:
OTC25 P:
Output Source (Power to Heater)
Solid-State Relay (Output 1) 120/250 Vac, Zero-Voltage
Switched, 2 A Continuous/
10 A Surge @ 25° C
Solid-State Relay (Output 2) 120/250 Vac, Zero-Voltage
Switched, 0.5 A Continuous/
10 A Surge @ 25° C
Electromechanical Relay
5 A, 250 Vac/5 A, 30 Vdc
Max Switching Capacity,
150 W
15
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
16
Download from Www.Somanuals.com. All Manuals Search And Download.
Keep This Information in a Safe Place
Configured Parameters Reference Information
Series OTC25 Temperature Controller
Model Number:
Zone Location:
Firmware Version No. :
_____________________
_____________________
_______________
(Displayed when the controller is powered up after all the segments on both lines
of the display have been tested).
Dear Customer:
Please keep this information handy - in case your controller should lose its configured initial parameter values or for easy refer-
ence when setting up a new controller. After auto-tuning, and when your controller is controlling well, we suggest you write the
displayed value for each of the menu parameters listed below. If you do not use a listed parameter, indicate “N/A”. Using this
page to document your parameter settings could reduce your downtime.
If you have any questions, or need further assistance, please contact Athena Controls Technical Support:
Toll-free (in U.S.): 800.782.6776
Telephone: 610.828.2490
Fax: 610.828.7084
E-Mail: [email protected]
OTC25-N
OTC25-P
OTC25-L
17
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
18
Download from Www.Somanuals.com. All Manuals Search And Download.
Keep This Information in a Safe Place
Configured Parameters Reference Information
Series OTC25 Temperature Controller
Model Number:
Zone Location:
Firmware Version No. :
_____________________
_____________________
_______________
(Displayed when the controller is powered up after all the segments on both lines
of the display have been tested).
Dear Customer:
Please keep this information handy - in case your controller should lose its configured initial parameter values or for easy refer-
ence when setting up a new controller. After auto-tuning, and when your controller is controlling well, we suggest you write the
displayed value for each of the menu parameters listed below. If you do not use a listed parameter, indicate “N/A”. Using this
page to document your parameter settings could reduce your downtime.
If you have any questions, or need further assistance, please contact Athena Controls Technical Support:
Toll-free (in U.S.): 800.782.6776
Telephone: 610.828.2490
Fax: 610.828.7084
E-Mail: [email protected]
OTC25-N
OTC25-P
OTC25-L
19
Download from Www.Somanuals.com. All Manuals Search And Download.
NOTES
20
Download from Www.Somanuals.com. All Manuals Search And Download.
For technical assistance, call toll free
1-800-782-6776 (in the U.S.) or 610-828-
2490 (from anywhere in the world), or
e-mail [email protected].
Athena Controls, Inc.
5145 Campus Drive
Plymouth Meeting, PA 19462 USA
Toll-free: 800.782.6776
Tel: 610.828.2490
Fax: 610.828.7084
athenacontrols.com
900M015U00 REV “B” - 082504
Download from Www.Somanuals.com. All Manuals Search And Download.
|