INSTALLATION INSTRUCTIONS
A95DF, A93DF, 95G1DF & 92G1DF
Warm Air Gas Furnace / Downflow Air Discharge
This manual must be left with the homeowner for future reference.
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in
manuals, be alert to the potential for personal injury or death.
WARNING
CAUTION
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal injury
or loss of life. Installation and service must be performed
by a licensed professional installer (or equivalent), service
agency or the gas supplier.
As with any mechanical equipment, personal injury can
result from contact with sharp sheet metal edges. Be
careful when you handle this equipment.
TABLE OF CONTENTS
Unit Dimensions............................................................ 2
A95/A93/95G1/92G1DF Parts Arrangement................. 3
A95/A93/95G1/92G1DF Gas Furnace .......................... 4
Shipping and Packing List ............................................ 4
Safety Information ......................................................... 4
Use of Furnace as a Construction Heater .................... 5
General ......................................................................... 6
Combustion, Dilution, Ventilation Air............................. 6
Setting Equipment ........................................................ 9
Filters .......................................................................... 12
Duct System................................................................ 12
Pipe and Fittings Specifications .................................. 12
Joint Cementing Procedure ........................................ 14
Venting Practices ........................................................ 14
Vent Piping Guidelines................................................ 15
Gas Piping .................................................................. 28
Electrical ..................................................................... 31
Unit Start Up................................................................ 34
Gas Pressure Adjustment ........................................... 36
High Altitude Information............................................. 36
Other Unit Adjustments ............................................... 39
Blower Motor Performance ......................................... 40
Service ........................................................................ 42
Planned Service.......................................................... 44
Diagnostic Codes........................................................ 44
Repair Parts List ......................................................... 45
Start Up Checklist ....................................................... 46
Manufactured By
Allied Air Enterprises, Inc.
A Lennox International, Inc. Company
215 Metropolitan Drive
*P506725-01*
(P) 506725-01
West Columbia, SC 29170
506725-01
Page 1 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
PARTS ARRANGEMENT
CONTROL BOX
(Includes integrated control,
transformer and door switch)
BAG ASSEMBLY
BLOWER MOTOR
(hidden)
BLOWER
COMPARTMENT
ACCESS
PANEL
COMBUSTION
AIR INDUCER
BLOWER DECK
PRIMARY LIMIT
HEATING
COMPARTMENT
ACCESS
COLD END HEADER BOX
HEAT EXCHANGER
PANEL
GAS VALVE
BURNER BOX ASSEMBLY
(includes flame sensor, rollout switches and ignitor)
FIGURE 1
506725-01
Page 3 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Furnace
Safety Information
This Category IV gas furnace is shipped ready for installation
in the downflow position.
WARNING
The furnace is equipped for installation in natural gas
applications. Aconversion kit (ordered separately) is required
for use in propane/LP gas applications.
Improper installation, adjustment, alteration, service or
maintenance can cause property damage, personal injury
or loss of life. Installation and service must be performed
by a licensed professional installer (or equivalent), service
agency or the gas supplier.
This unit can be installed as either a Direct Vent or a
Non-Direct Vent gas central furnace
NOTE: In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged outdoors. In
Non-Direct Vent installations, combustion air is taken from
indoors and flue gases are discharged outdoors. See Figure
2 for applications involving roof termination.
CAUTION
As with any mechanical equipment, personal injury can
result from contact with sharp sheet metal edges. Be
careful when you handle this equipment.
DANGER
DANGER OF EXPLOSION!
There are circumstances in which odorant used with LP/
Propane gas can lose its scent. In case of a leak, LP/
Propane gas will settle close to the floor and may be difficult
to smell. An LP/Propane leak detector should be installed
in all LP applications.
Use only the type of gas approved for use with this furnace.
Refer to unit nameplate.
This unit is CSA International certified to ANSI Z21.47 and
CSA 2.3 standards.
FIGURE 2
Building Codes
In the USA, installation of gas furnaces must conform with
local building codes. In the absence of local codes, units
must be installed according to the current National Fuel Gas
Code (ANSI Z223.1/NFPA54). The National Fuel Gas Code
is available from the American National Standards
Institute, Inc., 11 West 42nd Street, New York, NY 10036.
Shipping and Packing List
Package 1 of 1 contains:
1 - Assembled Gas Unit
1 - Bag assembly containing the following:
3 - Wire nuts
1 - Snap bushing
1 - Snap Plug
1 - Wire tie
1 - Condensate trap
In Canada, installation must conform with current National
Standard of Canada CSA-B149 Natural Gas and Propane
Installation Codes, local plumbing or waste water codes and
other applicable local codes.
1 - Condensate trap cap
1 - Condensate trap clamp
1 - 2” diameter debris screen
In order to ensure proper unit operation in non-direct vent
applications, combustion and ventilation air supply must be
provided according to the current National Fuel Gas Code
or CSA-B149 standard.
Check equipment for shipping damage. If you find any
damage, immediately contact the last carrier.
Please refer to specification sheets for available accessories.
Page 4 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
Locations and Clearances
Heating Unit Installed Parallell to Air Handler Unit
This furnace is CSA International certified for installation
clearances to combustible material as listed on the unit
nameplate and in the table in Figure 11. Accessibility and
service clearances must take precedence over fire protection
clearances.
NOTE: When furnace is installed on a combustible floor, a
downflow combustible flooring base must be installed
between the furnace and the floor.
AIR HANDLER
GAS UNIT
For installation in a residential garage, the furnace must be
installed so that the burner(s) and the ignition source are
located no less than 18 inches (457 mm) above the floor.
The furnace must be located or protected to avoid physical
damage by vehicles. When a furnace is installed in a public
garage, hangar, or other building that has a hazardous
atmosphere, the furnace must be installed according to
recommended good practice requirements and current
National Fuel Gas Code or CSA B149 standards.
Dampers
(open during cooling
operation only)
Dampers
(open during heating
operation only)
FIGURE 3
Note: Furnace must be adjusted to obtain a temperature
rise within the range specified on the unit nameplate. Failure
to do so may cause erratic limit operation and premature
heat exchanger failure.
NOTE: This furnace is designed for a minimum continuous
return air temperature of 60°F (16°C) or an intermittent
operation down to 55°F (13°C) dry bulb for cases where a
night setback thermostat is used. Return air temperature
must not exceed 85°F (29°C) dry bulb.
This gas furnace must be installed so that its electrical
components are protected from water.
This gas furnace may be installed in alcoves, closets, attics,
basements, garages, and utility rooms.
Installed in Combination with a Cooling Coil
When this furnace is used with cooling units (Figure 3), it
shall be installed in parallel with, or on the upstream side of,
cooling units to avoid condensation in the heating
compartment. With a parallel flow arrangement, a damper
(or other means to control the flow of air) must adequately
prevent chilled air from entering the furnace. If the damper
is manually operated, it must be equipped to prevent
operation of either the heating or the cooling unit, unless it
is in the full HEAT or COOL setting.
This furnace design has NOT been CSA certified for
installation in mobile homes, recreational vehicles, or
outdoors.
Never use an open flame to test for gas leaks. Check all
connections using a commercially available soap solution
made specifically for leak detection.
Use of Furnace as Construction Heater
These units are not recommended for use as a construction
heater during any phase of construction. Very low return air
temperature, harmful vapors and operation of the unit with
clogged or misplaced filters will damage the unit.
When installed, this furnace must be electrically grounded
according to local codes. In addition, in the United States,
installation must conform with the current National Electric
Code, ANSI/NFPANo. 70. The National Electric Code (ANSI/
NFPA No. 70) is available from the following address:
These units may be used for heating of buildings or structures
under construction, if the following conditions are met:
National Fire Protection Association
1 Battery March Park
Quincy, MA 02269
•
The vent system must be permanently installed per these
installation instructions.
•
Aroom thermostat must control the furnace. The use of
fixed jumpers that will provide continuous heating is not
allowed.
The return air duct must be provided and sealed to the
furnace.
Return air temperature range between 60°F (16°C) and
80°F (27°C) must be maintained.
Air filters must be installed in the system and must be
maintained during construction.
In Canada, all electrical wiring and grounding for the unit
must be installed according to the current regulations of the
Canadian Electrical Code Part I (CSAStandard C22.1) and/
or local codes.
•
•
•
506725-01
Page 5 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
•
•
Air filters must be replaced upon construction completion.
The input rate and temperature rise must be set per the
furnace rating plate.
WARNING
•
One hundred percent (100%) outdoor air must be provided
for combustion air requirements during construction.
Temporary ducting may supply outdoor air to the furnace.
Do not connect duct directly to the furnace. Size the
temporary duct following the instructions in section for
Combustion, Dilution and Ventilation Air in a confined
space with air from outside.
Product Contains Fiberglass Wool.
Disturbing the insulation in this product during
installation, maintenance, or repair will expose you to
fiberglass wool. Breathing this may cause lung cancer.
(Fiberglass wool is known to the State of California to
cause cancer.)
•
•
The furnace heat exchanger, components, duct system,
air filters and evaporator coils must be thoroughly
cleaned following final construction cleanup.
All furnace operating conditions (including ignition, input
rate, temperature rise and venting) must be verified
according to these installation instructions.
Fiberglass wool may also cause respiratory, skin, and
eye irritation.
To reduce exposure to this substance or for further
information, consult material safety data sheets available
from address shown below, or contact your supervisor.
Allied Air Enterprises, Inc.
215 Metropolitan Drive
West Columbia, SC 29170
General
These instructions are intended as a general guide and do
not supersede local codes in any way. Consult authorities
having jurisdiction before installation.
Combustion, Dilution & Ventilation Air
If this unit is installed as a Non-Direct Vent Furnace,
follow the guidelines in this section.
In addition to the requirements outlined previously, the
following general recommendations must be considered
when installing one of these furnaces:
NOTE: In Non-Direct Vent Installations, combustion air is
taken from indoors and flue gases are discharged outdoors.
•
•
Place the furnace as close to the center of the air
distribution system as possible. The furnace should also
be located close to the vent termination point.
When the furnace is installed in non-direct vent
applications, do not install the furnace where drafts might
blow directly into it. This could cause improper
combustion and unsafe operation.
When the furnace is installed in a non-direct vent
applications, do not block the furnace combustion air
opening with clothing, boxes, doors, etc. Air is needed
for proper combustion and safe unit operation.
When the furnace is installed in an attic or other insulated
space, keep insulation away from the furnace.
When the furnace is installed in an unconditioned space,
consider provisions required to prevent freezing of the
condensate drain system.
WARNING
Insufficient combustion air can cause headaches,
nausea, dizziness or asphyxiation. It will also cause
excess water in the heat exchanger resulting in rusting
and premature heat exchanger failure. Excessive
exposure to contaminated combustion air will result in
safety and performance related problems. Avoid
exposure to the following substances in the combustion
air supply:
•
•
•
Permanent wave solutions
Chlorinated waxes and cleaners
Chlorine base swimming pool chemicals
Water softening chemicals
De-icing salts or chemicals
Carbon tetrachloride
Halogen type refrigerants
NOTE: The Commonwealth of Massachusetts stipulates
Cleaning solvents (such as perchloroethylene)
Printing inks, paint removers, varnishes, etc.
Hydrochloric acid
Cements and glues
Antistatic fabric softeners for clothes dryers
Masonry acid washing materials
these additional requirements:
•
Gas furnaces shall be installed by a licensed plumber
or fitter only.
•
•
The gas cock must be “T handle” type.
When a furnace is installed in an attic, the passageway
to and service area surrounding the equipment shall be
floored.
In the past, there was no problem in bringing in sufficient
outdoor air for combustion. Infiltration provided all the air
that was needed. In today’s homes, tight construction
practices make it necessary to bring in air from outside for
combustion. Take into account that exhaust fans, appliance
vents, chimneys, and fireplaces force additional air that could
be used for combustion out of the house. Unless outside
CAUTION
These units should not be installed in areas normally
subject to freezing temperatures.
Page 6 of 48
Issue 1109
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
air is brought into the house for combustion, negative
pressure (outside pressure is greater than inside pressure)
will build to the point that a down draft can occur in the furnace
vent pipe or chimney. As a result, combustion gases enter
the living space creating a potentially dangerous situation.
infiltration. If the furnace is located in a building of tight
construction with weather stripping and caulking around the
windows and doors, follow the procedures in the “Air from
Outside” section.
Confined Space
In the absence of local codes concerning air for combustion
and ventilation, use the guidelines and procedures in this
section to install these furnaces to ensure efficient and safe
operation. You must consider combustion air needs and
requirements for exhaust vents and gas piping. Aportion of
this information has been reprinted with permission from
the National Fuel Gas Code (ANSI-Z223.1/NFPA 54). This
reprinted material is not the complete and official position of
ANSI on the referenced subject, which is represented only
by the standard in its entirely.
A confined space is an area with a volume less than 50
cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the
combined input rating of all appliances installed in that space.
This definition includes furnace closets or small equipment
rooms.
When the furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space
containing the furnace, the return air must be handled by
ducts which are sealed to the furnace casing and which
terminate outside the space containing the furnace. This is
especially important when the furnace is mounted on a
platform in a confined space such as a closet or small
equipment room. Even a small leak around the base of the
unit at the platform or at the return air duct connection can
cause a potentially dangerous negative pressure condition.
Air for combustion and ventilation can be brought into the
confined space either from inside the building or from outside.
In Canada, refer to the CSA B149 Installation codes.
CAUTION
Do not install the furnace in a corrosive or contaminated
atmosphere. Meet all combustion and ventilation air
requirements, as well as all local codes.
Air from Inside
If the confined space that houses the furnace adjoins a space
categorized as unconfined, air can be brought in by providing
two permanent openings between the two spaces. Each
opening must have a minimum free area of 1 square inch
(645 mm²) per 1,000 Btu (.29 kW) per hour of total input
rating of all gas-fired equipment in the confined space. Each
opening must be at least 100 square inches (64516 mm²).
One opening shall be within 12 inches (305 mm) of the top
of the enclosure and one opening within 12 inches (305 mm)
of the bottom. See Figure 4.
All gas-fired appliances require air for the combustion
process. If sufficient combustion air is not available, the
furnace or other appliance will operate inefficiently and
unsafely. Enough air must be provided to meet the needs
of all fuel-burning appliances and appliances such as exhaust
fans which force air out of the house. When fireplaces,
exhaust fans, or clothes dryers are used at the same time
as the furnace, much more air is required to ensure proper
combustion and to prevent a down draft. Insufficient air
causes incomplete combustion which can result in carbon
monoxide.
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE
In addition to providing combustion air, fresh outdoor air
dilutes contaminants in the indoor air. These contaminants
may include bleaches, adhesives, detergents, solvents and
other contaminants which can corrode furnace components.
ROOF TERMINATED
EXHAUST PIPE
The requirements for providing air for combustion and
ventilation depend largely on whether the furnace is installed
in an unconfined or a confined space.
OPENINGS
(To Adjacent
Unconfined
Space)
Unconfined Space
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
An unconfined space is an area such as a basement or
large equipment room with a volume greater than 50 cubic
feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the
combined input rating of all appliances installed in that space.
This space also includes adjacent rooms which are not
separated by a door. Though an area may appear to be
unconfined, it might be necessary to bring in outdoor air for
combustion if the structure does not provide enough air by
NOTE− Each opening shall have a free area of at least one square inch
2
per 1,000 Btu (645 mm per .29 kW) per hour of the total input rating of
all equipment in the enclosure, but not less than 100 square inches
2
(64516 mm ).
FIGURE 4
506725-01
Page 7 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
to 25 percent free area and metal louvers and grilles will
have 60 to 75 percent free area. Louvers and grilles must
be fixed in the open position or interlocked with the equipment
so that they are opened automatically during equipment
operation.
Air from Outside
If air from outside is brought in for combustion and ventilation,
the confined space shall be provided with two permanent
openings. One opening shall be within 12” (305 mm) of the
top of the enclosure and one within 12” (305 mm) of the
bottom. These openings must communicate directly or by
ducts with the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors or indirectly through vertical
ducts. Each opening shall have a minimum free area of 1
square inch per 4,000 Btu (645 mm² per .59 kW) per total
input rating of all equipment in the enclosure (See Figure 5).
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(All Air Through Ventilated Attic)
ROOF TERMINATED
EXHAUST PIPE
VENTILATION LOUVERS
(Each end of attic)
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)
OUTLET
AIR
VENTILATION LOUVERS
(Each end of attic)
ROOF TERMINATED
EXHAUST PIPE
INLET AIR
(Ends 12" above
bottom)
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
OUTLET
AIR
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
FURNACE
NOTE−The inlet and outlet air openings shall each have a free area of
2
VENTILATION
LOUVERS
(For unheated
crawl space)
at least one square inch per 4,000 Btu (645 mm per 1.17 kW) per hour
INLET
AIR
of the total input rating of all equipment in the enclosure.
FIGURE 6
NOTE−The inlet and outlet air openings shall each have a free area
2
of at least one square inch per 4,000 Btu (645 mm per 1.17 kW) per
hour of the total input rating of all equipment in the enclosure.
FIGURE 5
If air from outside is brought in for combustion and ventilation,
the confined space must have two permanent openings. One
opening shall be within 12 inches (305 mm) of the top of the
enclosure and one opening within 12 inches (305 mm) of
the bottom. These openings must communicate directly or
by ducts with the outdoors or spaces (crawl or attic) that
freely communicate with the outdoors or indirectly through
vertical ducts. Each opening shall have a minimum free
area of 1 square inch (645 mm²) per 4,000 Btu (1.17 kW)
per hour of total input rating of all equipment in the enclosure.
See figures 5 and 6. When communicating with the outdoors
through horizontal ducts, each opening shall have a minimum
free area of 1 square inch (645 mm²) per 2,000 Btu (.56
kW) per total input rating of all equipment in the enclosure.
See Figure 7.
EQUIPMENT IN CONFINED SPACE −
ALL AIR FROM OUTSIDE
ROOF TERMINATED
EXHAUST PIPE
OUTLET AIR
FURNACE
SIDE WALL
TERMINATED
EXHAUST PIPE
(ALTERNATE
LOCATION)
INLET AIR
When ducts are used, they shall be of the same cross-
sectional area as the free area of the openings to which
they connect. The minimum dimension of rectangular air
ducts shall be no less than 3 inches (75 mm). In calculating
free area, the blocking effect of louvers, grilles, or screens
must be considered. If the design and free area of protective
covering is not known for calculating the size opening
required, it may be assumed that wood louvers will have 20
NOTE−Each air duct opening shall have a free area of at least one
2
square inch per 2,000 Btu (645 mm per .59 kW) per hour of the total
input rating of all equipment in the enclosure. If the equipment room
is located against an outside wall and the air openings communi-
cate directly with the outdoors, each opening shall have a free area
2
of at least 1 square inch per 4,000 Btu (645 mm per 1.17 kW) per
hour of the total input rating of all other equipment in the enclosure.
FIGURE 7
Page 8 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
INSTALLATION – Setting Equipment
NOTE: These units may be equipped with a shipping pad
under the blower housing. Remove the shipping pad prior
to operation.
WARNING
Do not install the furnace on its front, back or in the
horizontal position. See Figure 10. Do no connect the
return air ducts to the back of the furnace. Doing so will
adversely affect the operation of the safety control
devices, which could result in personal injury or death.
Allow for clearances to combustible materials as indicated
on the unit nameplate. Minimum clearances for closet or
alcove installations are shown in Figure 11.
Select a location that allows for the required clearances that
are listed on the unit nameplate. Also consider gas supply
connections, electrical supply, vent connection, condensate
trap and drain connections, and installation and service
clearances [24 inches (610 mm) at unit front]. The unit must
be level from side to side. Tilt the unit slightly (maximum
1/2 in. from level) from back to front to aid in the draining of
the heat exchanger. See Figure 9.
WARNING
Blower access panel must be securely in place when
blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Shipping Bolt Removal
SETTING EQUIPMENT
NOTE: Units with a 1/2 hp blower motors are equipped with
three flexible legs and one rigid leg. The rigid leg is equipped
with a shipping bolt and a flat white plastic washer (rather
than the rubber mounting grommet used with a flexible
mounting leg). See Figure 8. The bolt and washer must
be removed before the furnace is placed into operation.
After the bolt and washer have been removed, the rigid leg
will not touch the blower housing.
AIR FLOW
AIR FLOW
AIR FLOW
UNITS WITH 1/2 HP BLOWER MOTOR
1/2"
max.
RIGID LEG
(remove shipping bolt and washer)
FRONT VIEW
SIDE VIEW
SIDE VIEW
Unit must be level side−to−side. Unit may be positioned
from level to 1/2" toward the front to aid in draining.
FIGURE 9
FIGURE 8
Figure 10
506725-01
Page 9 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Installation on Non-Combustible Flooring (Figure 12)
1. Cut floor opening keeping in mind clearances listed on
unit rating plate. Also keep in mind gas supply
connections, electrical supply, flue and air intake
connections and sufficient installation and servicing
clearances. See Table 1 for correct floor opening size.
2. Flange warm air plenum and lower the plenum into the
opening.
WARNING
Improper installation of the furnace can result in personal
injury or death. Combustion and flue products must
never be allowed to enter the return air system or air in
the living space. Use sheet metal screws and joint tape
to seal return air system to furnace.
3. Set the unit over the plenum and seal the plenum to the
unit.
4. Ensure that the seal is adequate.
In platform installations with furnace return, the furnace
should be sealed airtight to the return air plenum. A
door must never be used as a portion of the return air
duct system. The base must provide a stable support
and an airtight seal to the furnace. Allow absolutely no
sagging, cracks, gaps, etc.
NON−COMBUSTIBLE FLOOR OPENING SIZE
Front to Rear
Side to Side
For no reason should return and supply air duct systems
ever be connected to or from other heating devices such
as a fireplace or stove, etc. Fire, explosion, carbon
monoxide poisoning, personal injury and/or property
damage could result.
Cabinet Width
in.
mm
in.
mm
422
511
B Cabinet (17.5")
C Cabinet (21")
19 − 3/4
19 − 3/4
502
502
16 − 5/8
20−1/8
NOTE: Floor opening dimensions listed are 1/4 inch (6 mm) larger than
the unit opening. See dimension drawing on page 2.
The unit may be installed three ways in downflow applica-
tions: on non-combustible flooring, on combustible flooring
using an additive base, or on a reverse-flow cooling coil
cabinet. Do not drag the unit across the floor in the
downflow position. Floor and furnace flange damage
will result.
TABLE 1
Refer to Figure 11 for clearances in downflow applica-
tions.
FURNACE
Downflow Application Installation Clearances
Top
PROPERLY
SIZED FLOOR
OPENING
SUPPLY AIR
PLENUM
Left Side
Right Side
FIGURE 12
Bottom
Installation on Combustible Flooring (Figure 13)
1. When unit is installed on a combustible floor, a downflow
combustible flooring base must be installed between the
furnace and the floor. The base must be ordered
separately. See Table 2 for opening size to cut in floor.
Top
*Front
Back
0
0
0
Sides
Vent
0†
0
CAUTION
Floor
NC ‡
The furnace and combustible flooring base shall not be
installed directly on carpeting, tile, or other combustible
material other than wood flooring.
*Front clearance in alcove installation must be 24 in. (610 mm).
Maintain a minimum of 24 in. (610 mm) for front service access.
†Allow proper clearances to accommodate condensate trap.
‡The furnace may be installed on a combustible wood floor if an optional
additive base is installed between the furnace and the combustible floor.
FIGURE 11
Page 10 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
COMBUSTIBLE FLOORING BASE OPENING SIZE
Front to Rear
Side to Side
Cabinet
Width
Catalog
Number
in.
22
mm
559
in.
mm
FURNACE
B Cabinet
(17.5")
11M60
11M61
18 − 3/4
476
578
C Cabinet
(21")
22
559
22 − 3/4
COOLING COIL
PLENUM
TABLE 2
PROPERLY
SIZED FLOOR
OPENING
FURNACE
SUPPLY AIR
PLENUM
PROPERLY
SIZED FLOOR
OPENING
COMBUSTIBLE
FLOORING BASE
FIGURE 14
Return Air Opening - Downflow Units
Return air may be brought in only through the top opening
of a furnace installed in the downflow position. The following
steps should be taken when installing plenum:
1. Bottom edge of plenum should be flanged with a
hemmed edge (See Figure 15 or 16).
2. Sealing strips should be used to ensure an airtight seal
between the cabinet and the plenum.
3. In all cases, plenum should be secured to top of furnace
using sheet metal screws.
4. Make certain that an adequate seal is made.
FIGURE 13
2. After opening is cut, set the combustible flooring base
into opening.
3. Check fiberglass strips on the combustible flooring base
to make sure they are properly glued and positioned.
4. Lower supply air plenum into the combustible flooring
base until plenum flanges seal against fiberglass strips.
er opening is
PLENUM
(Field Provided)
NOTE: Be careful not to damage fiberglass strips. Check
for a tight seal.
SECURE FROM
OUTSIDE CABINET
5. Set the furnace over the plenum.
6. Ensure that the seal between the furnace and plenum
is adequate.
CABINET
SEALING STRIP
SIDE PANEL
(Field Provided)
Side View
Installation on Cooling Coil Cabinet (Figure 14)
FIGURE 15
NOTE: Downflow combustible flooring kit is not used.
PLENUM
(Field Provided)
SEALING STRIP
1. Refer to reverse-flow coil installation instructions for
correctly sized opening in floor and installation of
cabinet.
(Field Provided)
2. When cooling cabinet is in place, set and secure the
furnace according to the instructions that are provided
with the cooling coil. Secure the furnace to the cabinet.
3. Seal the cabinet and check for air leaks.
CABINET
SIDE PANEL
SECURE FROM
INSIDE CABINET
Side View
FIGURE 16
506725-01
Page 11 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Filters
Pipe & Fittings Specifications
This unit is not equipped with a filter or rack. Afield provided
filter is required for the unit to operate properly. Table 3 lists
recommended filter sizes.
All pipe, fittings, primer and solvent cement must conform
withAmerican National Standard Institute and theAmerican
Society for Testing and Materials (ANSI/ASTM) standards.
The solvent shall be free flowing and contain no lumps,
undissolved particles or any foreign matter that adversely
affects the joint strength or chemical resistance of the
cement. The cement shall show no gelation, stratification,
or separation that cannot be removed by stirring. Refer to
Table 4 below for approved piping and fitting materials.
A filter must be in place whenever the unit is operating.
Furnace
Filter Size
Cabinet Width
17−1/2"
21"
16 x 25 x 1 (1)
TABLE 3
CAUTION
Duct System
Use industry-approved standards to size and install the
supply and return air duct system. This will result in a quiet
and low-static system that has uniform air distribution.
Solvent cements for plastic pipe are flammable liquids
and should be kept away from all sources of ignition.
Do not use excessive amounts of solvent cement when
making joints. Good ventilation should be maintained
to reduce fire hazard and to minimize breathing of
solvent vapors. Avoid contact of cement with skin and
eyes.
NOTE: This furnace is not certified for operation in heating
mode (indoor blower operating at selected heating speed)
with an external static pressure which exceeds 0.5 inches
w.c. Operation at these conditions may result in improper
limit operation.
Supply Air Plenum
PIPING AND FITTINGS SPECIFICATIONS
If the fumace is installed without a cooling coil, a removable
access panel should be installed in the supply air duct. The
access panel should be large enough to permit inspection
(by reflected light) of the heat exchanger for leaks after the
furnace is installed. The furnace access panel must always
be in place when the furnace is operating and it must not
allow leaks into the supply air duct system.
Schedule 40 PVC (Pipe)
D1785
F891
Schedule 40 PVC (Cellular Core Pipe)
Schedule 40 PVC (Fittings)
D2466
F441
Schedule 40 CPVC (Pipe)
Schedule 40 CPVC (Fittings)
SDR−21 PVC or SDR−26 PVC (Pipe)
SDR−21 CPVC or SDR−26 CPVC (Pipe)
Schedule 40 ABS Cellular Core DWV (Pipe)
Schedule 40 ABS (Pipe)
F438
D2241
F442
F628
Return Air Plenum
D1527
D2468
Schedule 40 ABS (Fittings)
NOTE: Return air must not be drawn from a room where
this furnace, or any other gas-fueled appliance (i.e.,
water heater), or carbon monoxide-producing device
(i.e., wood fireplace) is installed.
ABS−DWV (Drain Waste & Vent)
(Pipe & Fittings)
D2661
D2665
PVC−DWV (Drain Waste & Vent)
Pipe & Fittings)
ASTM
SPECIFICATION
PRIMER & SOLVENT CEMENT
When return air is drawn from a room, a negative pressure
is created in the room. If a gas appliance is operating in a
room with negative pressure, the flue products can be pulled
back down the vent pipe and into the room. This reverse
flow of the flue gas may result in incomplete combustion
and the formation of carbon monoxide gas. This toxic gas
might then be distributed throughout the house by the furnace
duct system.
PVC & CPVC Primer
PVC Solvent Cement
CPVC Solvent Cement
ABS Solvent Cement
F656
D2564
F493
D2235
PVC/CPVC/ABS All Purpose Cement For
Fittings & Pipe of the same material
D2564, D2235, F493
D3138
ABS to PVC or CPVC Transition Solvent
Cement
CANADA PIPE & FITTING & SOLVENT
CEMENT
Use fiberglass sealing strips, caulking, or equivalent sealing
method between the plenum and the furnace cabinet to
ensure a tight seal. If a filter is installed, size the return air
duct to fit the filter frame.
MARKING
PVC & CPVC Pipe and Fittings
PVC & CPVC Solvent Cement
ULCS636
ABS to PVC or CPVC Transition Cement
TABLE 4
Page 12 of 48
Issue 1109
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
vent pipe hangers. Uniformly apply a liberal coat of PVC
primer for PVC or use a clean dry cloth for ABS to clean
inside socket surface of fitting and male end of pipe to depth
of fitting socket.
IMPORTANT
The exhaust and intake connections are made of PVC.
Use PVC primer and solvent cement when using PVC
vent pipe. When using ABS vent pipe, use transitional
solvent cement to make connections to the PVC fitting in
the unit.
Canadian Applications Only
Pipe, fittings, primer and solvent cement used to vent
(exhaust) this appliance must be certified to ULC S636 and
supplied by a single manufacturer as part of an approved
vent (exhaust) system. When bonding the vent system to
the furnace, use ULC S636 approved One-Step Transition
Cement to bond the pipe to the flue collar. In addition, the
first three feet of vent pipe from the furnace flue collar must
be accessible for inspection.
Use PVC primer and solvent cement orABS solvent cement
meeting ASTM specifications, refer to Table 4. As an
alternate, use all purpose cement, to bond ABS, PVC, or
CPVC pipe when using fittings and pipe made of the same
materials. Use transition solvent cement when bondingABS
to either PVC or CPVC.
Table 5 Lists the available exhaust termination kits. All vent
terminations are PVC.
Low temperature solvent cement is recommended during
cooler weather. Metal or plastic strapping may be used as
OUTDOOR TERMINATION KITS USAGE
STANDARD
CONCENTRIC
Outdoor
Exhaust
Accelerator
(Dia. X
Length)
Outdoor
Flush-
Mount
Kit
1−1/2"
2"
3"
Concentric Concentric Concentric
Exhaust
Accelerator
(Dia. X
VENT
PIPE
DIA.
(in.)
A95DF
A93DF
95G1DF
92G1DF
Kit
Kit
Kit
Length)
60L46
or
44W93
71M80
or
44W92
69M29
or
44W92
1−1/2" X 12"
2" X 12"
51W11**
2
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
2−1/2
045
3
2
2−1/2
070
090
110
3
2
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
YES
2−1/2
3
2
2−1/2
3
*Requires field−provided and installed 1−1/2" exhaust accelerator.
** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all 45,000 and 70,000 furnace installations.
†† The 44W92 Concentric kit is provided with a 1-1/2” accelerator which must be installed on the exhaust outlet when
this kit is used with the 45,000 and 70,000 furnaces.
TABLE 5
506725-01
Page 13 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Joint Cementing Procedure
All cementing of joints should be done according to the
specifications outlined in ASTM D 2855.
Venting Practices
Piping Suspension Guidelines
NOTE: A sheet metal screw may be used to secure the
intake pipe to the connector, if desired. Use a drill or self
tapping screw to make a pilot hole.
SCHEDULE 40
PVC − 5’
all other pipe* − 3’
DANGER
* See Table 4 for allowable pipe.
DANGER OF EXPLOSION!
NOTE: Isolate piping at the point where it exits the outside wall or
roof in order to prevent transmission of vibration to the structure.
Fumes from PVC glue may ignite during system check.
Allow fumes to dissipate for at least 5 minutes before
placing unit into operation.
Wall Thickness Guidelines
24" maximum
3/4" minimum
1. Measure and cut vent pipe to desired length.
2. Debur and chamfer end of pipe, removing any ridges or
rough edges. If end is not chamfered, edge of pipe
may remove cement from fitting socket and result in a
leaking joint.
Wall
inside
outside
3. Clean and dry surfaces to be joined.
4. Test fit joint and mark depth of fitting on outside of pipe.
5. Uniformly apply a liberal coat of PVC primer for PVC or
use a clean dry cloth for ABS to clean inside socket
surface of fitting and male end of pipe to depth of fitting
socket.
6. Promptly apply solvent cement to end of pipe and inside
socket surface of fitting. Cement should be applied
lightly but uniformly to inside of socket. Take care to
keep excess cement out of socket. Apply second coat
to end of pipe.
insulation
(if required)
FIGURE 17
REPLACING FURNACE THAT
WAS PART OF A COMMON
VENT SYSTEM
CHIMNEY
OR GAS
VENT
(Check sizing
for remaining
appliance)
NOTE: Time is critical at this stage. Do Not allow Primer to
dry before applying cement.
7. Immediately after applying last coat of cement to pipe,
and while both inside socket surface and end of pipe
are wet with cement, forcefully insert end of pipe into
socket until it bottoms out. Turn PVC pipe 1/4 turn during
assembly (but not after pipe is fully inserted) to distribute
cement evenly. Do not turn ABS or cellular core pipe.
FURNACE
WATER
HEATER
(Removed from
from common
vent system)
OPENINGS
(To Adjacent
Room)
NOTE: Assembly should be completed within 20 seconds
after last application of cement. Hammer blows should not
be used when inserting pipe.
If this gas furnace replaces a furnace which was
commonly vented with another gas appliance,
the size of the existing vent pipe for that gas ap-
pliance must be checked. Without the heat of the
original furnace flue products, the existing vent pipe
is probably oversized for the single water heater or
other appliance. The vent should be checked for
proper draw with the remaining appliance.
8. After assembly, wipe excess cement from pipe at end
of fitting socket. A properly made join will show a bead
around its entire perimeter. Any gaps may indicate an
improper defective assembly due to insufficient solvent.
9. Handle joints carefully until completely set.
FIGURE 18
Page 14 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
1. In areas where piping penetrates joist or interior walls,
hole must be large enough to allow clearance on all
sides of pipe through center of hole using a hanger.
2. When furnace is installed in a residence where unit is
shut down for an extended period of time, such as a
vacation home, make provisions for draining condensate
collection trap and lines.
Use the following steps to correctly size vent pipe diameter.
045, 070,
090, 110
1
Furnace capacity?
Exhaust Piping (Figure 20)
Route piping to outside of structure. Continue with
installation following instructions given in piping termination
section.
Standard or
Concentric?
See Table 5
Which termination?
2
CAUTION
Do not discharge exhaust into an existing stack or stack
that also serves another gas appliance. If vertical
discharge through an existing unused stack is required,
insert PVC pipe inside the stack until the end is even
with the top or outlet end of the metal stack.
Which needs
most elbows?
Intake or
exhaust
3
CAUTION
The exhaust vent pipe operates under positive pressure
and must be completely sealed to prevent leakage of
combustion products into the living space.
How many?
4
5
Vent Piping Guidelines
2", 2 1/2"
or 3"
Desired pipe size?
This gas furnace can be installed as either a Non-Direct
Vent or a Direct Vent gas central furnace.
NOTE: In non-Direct Vent installations, combustion air is
taken from indoors and flue gases are discharged outdoors.
In Direct Vent installations, combustion air is taken from
outdoors and flue gases are discharged outdoors.
6
7
What is the altitude?
Intake and exhaust pipe sizing - Size pipe according toTables
6 and 7. Table 6 lists the minimum vent pipe lengths
permitted. Table 7 lists the maximum pipe lengths permitted.
Use Table 7 to find
max intake or exhaust
pipe length.
Regardless of the diameter of pipe used, the standard roof
and wall terminations described in section Exhaust Piping
Terminations should be used. Exhaust vent termination pipe
is sized to optimize the velocity of the exhaust gas as it exits
the termination.
FIGURE 19
In some applications which permit the use of several different
sizes of vent pipe, a combination vent pipe may be used.
Contact Allied Air Technical Service for assistance in sizing
vent pipe in these applications.
MINIMUM VENT PIPE LENGTHS
IMPORTANT
A95DF, 95G1DF, A93DF, & 92G1DF
MIN. VENT LENGTH*
MODELS
Do not use screens or perforated metal in exhaust or
intake terminations. Doing so will cause freeze-ups and
may block the terminations.
15 ft. or
5 ft plus 2 elbows or
10 ft plus 1 elbow
045, 070, 090, 110
*Any approved termination may be added to the minimum length listed.
TABLE 6
506725-01
Page 15 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
A95DF / 95G1DF and A93DF / 92G1DF
Maximum Allowable Intake or Exhaust Vent Length in Feet
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total.
Both Intake and Exhaust must be same pipe size.
Standard Termination at Elevation 0 − 10,000 ft.
2" Pipe
Model
2−1/2" Pipe
Model
3" Pipe
Model
Number
Of 90°
Elbows
Used
045
61
56
51
46
41
36
31
26
21
16
070
46
41
36
31
26
21
16
11
090
24
110
045
100
95
90
85
80
75
70
65
60
55
070
090
110
045
127
122
117
112
107
102
97
070
127
122
117
112
107
102
97
090
108
103
98
110
108
103
98
1
2
80
75
70
65
60
55
50
45
40
35
43
38
33
28
23
18
13
19
3
14
4
93
93
5
88
88
n/a
n/a
6
83
83
7
78
78
n/a
8
92
92
73
73
9
87
87
68
68
n/a
n/a
10
82
82
63
63
Concentric Termination Elevation 0 − 10,000 ft.
2" Pipe
Model
2−1/2" Pipe
Model
3" Pipe
Model
Number
Of 90°
Elbows
Used
045
53
48
43
38
33
28
23
18
13
n/a
070
38
33
28
23
18
13
090
22
110
045
90
85
80
75
70
65
60
55
50
45
070
70
65
60
55
50
45
40
35
30
25
090
39
34
29
24
19
14
110
045
111
106
101
96
070
111
106
101
96
090
104
99
94
89
84
79
74
69
64
59
110
104
99
94
89
84
79
74
69
64
59
1
2
17
3
12
4
5
91
91
n/a
n/a
6
86
86
7
81
81
n/a
8
76
76
n/a
n/a
9
71
71
10
66
66
TABLE 7
Page 16 of 48
Issue 1109
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL EXHAUST PIPE CONNECTIONS
Pipe size determined in Table 7.
2”
2”
2”
2”
2”
or
3”
TRANSITION
*2”
INTAKE
EXHAUST
DO NOT transition from smaller
to larger pipe size in horizontal
runs of exhaust pipe.
TOP VIEW
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE: Exhaust pipe and intake pipe must be the same diameter.
FIGURE 20
TYPICAL INTAKE PIPE CONNECTIONS (DIRECT VENT APPLICATIONS)
2”
2”
Pipe size determined in Table 7.
2”
2”
2”
or
TRANSITION
3”
3”
*2”
*2”
TRANSITION
*2”
INTAKE
EXHAUST
TOP VIEW
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.
NOTE: Intake pipe and exhaust pipe must be the same diameter.
FIGURE 21
506725-01
Page 17 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Intake Piping
General Guidelines for Vent Terminations
In Non-Direct Vent applications, combustion air is taken from
indoors and the flue gases are discharged to the outdoors.
This unit is then classified as a non-direct vent, Category IV
gas furnace.
This furnace may be installed in either direct vent or non-
direct vent applications. In non-direct vent applications,
when intake air will be drawn into the furnace from the
surrounding space, the indoor air quality must be considered.
Guidelines listed in Combustion, Dilution and VentilationAir
section must be followed.
In Direct Vent applications, combustion air is taken from
outdoors and the flue gases are discharged to the outdoors.
This unit is then classified as a direct vent, Category IV gas
furnace.
Follow the next two steps when installing the unit in Direct
Vent applications, where combustion air is taken from
outdoors and flue gases are discharged outdoors. The
provided air intake screen must not be used in direct
vent applications (outdoors).
1. Use cement or a sheet metal screw to secure the intake
pipe to the inlet air connector.
2. Route piping to outside of structure. Continue with
installation following instructions given in general guide
lines for piping terminations and intake and exhaust
piping terminations for direct vent sections. Refer to
Table 7 for pipe sizes.
In both Non-Direct Vent and Direct Vent applications, the
vent termination is limited by local building codes. In the
absence of local codes, refer to the current National Fuel
Gas CodeANSI Z223-1/NFPA54 in U.S.A., and current CSA-
B149 Natural Gas and Propane Installation Codes in Canada
for details.
Position termination according to location given in Figure 23
or 24. In addition, position termination so it is free from any
obstructions and 12" above the average snow accumulation.
At vent termination, care must be taken to maintain protective
coatings over building materials (prolonged exposure to
exhaust condensate can destroy protective coatings). It is
recommended that the exhaust outlet not be located within
6 feet (1.8 m) of a condensing unit because the condensate
can damage the painted coating.
TYPICAL AIR INTAKE PIPE CONNECTIONS
NON−DIRECT VENT APPLICATIONS
AIR
INTAKE
SCREEN
(Provided)
NOTE: If winter design temperature is below 32° F (0° C), it is
recommended that the exhaust piping be insulated with 1/2" (13
mm), Armaflex or equivalent when run through an unconditioned
area. In extremely cold climate areas with temperature below 20°
F (6.7° C) it is recommended that 3/4" (19 mm) Armaflex or
equivalent be used. Insulation on outside runs of exhaust pipe
may be painted or wrapped to protect insulation from deterioration
in accordance with the insulation manufacturers recommendation.
Exhaust pipe insulation may not be necessary in some specific
applications.
NOTE: During extremely cold temperatures, below approximately
20° F (6° C), units with long runs of vent pipe through unconditioned
space, even when insulated, may form ice in the exhaust
termination that prevents the unit from operating properly. Longer
run times of at least 5 minutes will alleviate most icing problems.
Also, a heating cable may be installed on exhaust piping and
termination to prevent freeze-ups. Heating cable installation kits
are available, see unit specification sheets for part numbers.
NOTE: Air intake screen and elbow may be rotated, so that
screen may be positioned to face forward or to either side.
FIGURE 22
Follow the next two steps when installing the unit in
Non-Direct Vent applications where combustion air is
taken from indoors and flue gases are discharged outdoors.
1. Use field-provided materials and the factory-provided
air intake screen to route the intake piping as shown in
Figure 23. Maintain a minimum clearance of 3" (76 mm)
around the air intake opening. The air intake opening
(with the protective screen) should always be directed
forward, or sideways.
IMPORTANT
Do not use screens or perforated metal in exhaust
terminations. Doing so will cause freeze-ups and may
block the terminations.
IMPORTANT
For Canadian Installations Only:
In accordance to CSA International B149 installation
codes, the minimum allowed distance between the
combustion air intake inlet and the exhaust outlet of
other appliances shall not be less than 12 inches (305
mm).
2. Use a sheet metal screw to secure the intake pipe to
the connector, if desired.
Page 18 of 48
Issue 1109
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
VENT TERMINATION CLEARANCES
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
B
B
B
I
C
B
Fixed
Closed
Operable
Fixed
M
Closed
F
Operable
K
J
A
AREA WHERE TERMINAL
IS NOT PERMITTED
AIR SUPPLY INLET
US Installations
VENT TERMINAL
1
2
Canadian Installations
A =
Clearance above grade, veranda,
porch, deck or balcony
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
B =
Clearance to window or
door that may be opened
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
C =
D =
Clearance to permanently
closed window
* 12"
* 12"
Vertical clearance to ventilated soffit
* Equal to or greater than soffit depth.
* Equal to or greater than soffit depth.
located above the terminal within a
horizontal distance of 2 feet (mm)
from the center line of the terminal
* Equal to or greater than soffit depth.
E =
F =
G =
Clearance to unventilated soffit
Clearance to outside corner
* Equal to or greater than soffit depth.
* No minimum to outside corner
*
* No minimum to outside corner
*
Clearance to inside corner
H = Clearance to each side of center line ex-
tended above meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
*
I =
Clearance to service regulator
vent outlet
3 feet (.9m)
* 3 feet (.9m)
J =
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
4 feet (1.2 m) below or to side of opening;
1 foot (30 cm) above opening
K =
L =
Clearance to mechanical air sup-
ply inlet
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
Clearance above paved sidewalk or
paved driveway located on public property
M =
Clearance under veranda, porch,
deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1,
clearance will be in accordance with local installation codes and the re-
quirements of the gas supplier and these installation instructions."
2
In accordance with the current CSA B149.1, N
atural Gas and Pr opane Inst allation Code
between two single family dwellings and serves both dwellings.
sides beneath the floor. Lennox recommends avoiding this location if possible.
FIGURE 23
506725-01
Page 19 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
VENT TERMINATION CLEARANCES
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA
INSIDE CORNER
DETAIL
G
H
A
D
E
B
L
B
B
B
I
C
B
Fixed
Closed
Operable
Fixed
M
Closed
F
Operable
K
J
A
AREA WHERE TERMINAL
IS NOT PERMITTED
AIR SUPPLY INLET
US Installations
VENT TERMINAL
1
2
Canadian Installations
A =
Clearance above grade, veranda,
porch, deck or balcony
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
12 inches (305mm) or 12 in. 305mm)
above average snow accumulation.
B =
Clearance to window or
door that may be opened
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
* 12"
C =
D =
Clearance to permanently
closed window
* 12"
Vertical clearance to ventilated soffit
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
located above the terminal within a
horizontal distance of 2 feet (mm)
from the center line of the terminal
* Equal to or greater than soffit depth
* Equal to or greater than soffit depth
E =
F =
G =
Clearance to unventilated soffit
Clearance to outside corner
Clearance to inside corner
* No minimum to outside corner
*
* No minimum to outside corner
*
H = Clearance to each side of center line ex-
tended above meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
3 feet (.9m) within a height 15 feet (4.5m)
above the meter / regulator assembly
I =
Clearance to service regulator
vent outlet
3 feet (.9m)
* 3 feet (.9m)
J =
Clearance to non−mechanical air
supply inlet to building or the com-
bustion air inlet to any other ap-
pliance
6 inches (152mm) for appliances <10,000
Btuh (3kw), 9 inches (mm) for appliances
> 10,000 Btuh (3kw) and <50,000 Btuh
(15 kw), 12 inches (305mm) for ap-
pliances > 50,000 Btuh (15kw)
6 inches (152mm) for appliances <10,000
Btuh (3kw), 12 inches (305mm) for
appliances > 10,000 Btuh (3kw) and
<100,000 Btuh (30kw), 36 inches (.9m)
for appliances > 100,000 Btuh (30kw)
K =
L =
Clearance to mechanical air sup-
ply inlet
Clearance above paved sidewalk or
paved driveway located on public property
3 feet (.9m) above if within 10 feet
(3m) horizontally
6 feet (1.8m)
* 7 feet (2.1m)
M =
Clearance under veranda, porch,
deck or balcony
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA
B149.1, clear-
ance will be in accordance with local installation c odes and the requirements
of the gas supplier and these installation instructions."
2
In accordance with the current CSA B149.1, Natura
l Gas and Prop ane Installation Code
between two single family dwellings and serves both dwellings.
sides beneath the floor. Lennox recommends avoiding this location if possible.
FIGURE 24
Page 20 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
Details of Intake and Exhaust Piping Terminations for
Direct Vent Installations
DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
3"(76mm) MAX.
SIZE TERMINATION
PIPE PER TABLE 8.
Inches(mm)
NOTE: In Direct Vent installations, combustion air is taken
from outdoors and flue gases are discharged to outdoors.
UNCONDITIONED
ATTIC SPACE
8" (203mm) MIN
NOTE: Flue gas may be slightly acidic and may adversely
affect some building materials. If any vent termination is
used and the flue gases may impinge on the building
material, a corrosion-resistant shield (minimum 24 inches
square) must be used to protect the wall surface. If the
optional tee is used, the protective shield is required. The
shield should be constructed using wood, plastic, sheet metal
or other suitable material. All seams, joints, cracks, etc. in
the affected area should be sealed using an appropriate
sealant. See Figure 27.
1/2" (13mm) FOAM
INSULATION IN
12" (305mm) ABOVE
AVERAGE SNOW
ACCUMULATION
UNCONDITIONED
(IF REQUIRED)
SPACE
3" (76mm) OR
2" (51mm) PVC
PROVIDE SUPPORT
FOR INTAKE AND
EXHAUST LINES
Intake and exhaust pipes may be routed either horizontally
through an outside wall or vertically through the roof. In
attic or closet installations, vertical termination through the
roof is preferred. Figures 25 through 33 show typical
terminations.
FIGURE 25
FLUSH−MOUNT SIDE WALL TERMINATION
51W11
2" EXTENSION
FOR 2" PVC PIPE
1" EXTENSION
FOR 3" PVC PIPE
1. Exhaust and intake exits must be in same pressure zone.
Do not exit one through the roof and one on the side.
Also, do not exit the intake on one side and the exhaust
on another side of the house or structure.
2. Intake and exhaust pipes should be placed as close
together as possible at termination end (refer to
illustrations). Maximum separation is 3" (76 mm) on
roof terminations and 6" (152 mm) on side wall
terminations.
3. On roof terminations, the intake piping should terminate
straight down using two 90° elbows (See Figure 25).
4. Exhaust piping must terminate straight out or up as
shown. Areducer may be required on the exhaust piping
at the point where it exits the structure to improve the
velocity of exhaust away from the intake piping. See
Table 8.
FURNACE
EXHAUST
PIPE
4’’
FURNACE
INTAKE PIPE
GLUE EXHAUST
END FLUSH INTO
TERMINATION
FLAT SIDE
1−1/2" ACCELERATOR
(all −45, −070 and −090 units)
FIGURE 26
EXHAUST PIPE TERMINATION SIZE REDUCTION
6. On field supplied terminations, a minimum distance
between the end of the exhaust pipe and the end of the
intake pipe without a termination elbow is 8" and a
minimum distance of 6" with a termination elbow. See
Figures 28 and 29.
7. If intake and exhaust piping must be run up a side wall
to position above snow accumulation or other
obstructions, piping must be supported every 24" (610
mm) as shown in Figures 28 and 29.
Termination
MODEL
Exhaust Pipe Size
Pipe Size
1−1/2" (38mm)
2" (51mm)
2" (51mm)
2" (51mm), 2−1/2" (64mm),
3" (76mm)
*045 and *070
*090
3" (76mm)
110
TABLE 8
*045, 070and090unitswiththe flush−mounttermination
must use the 1−1/2"accelerator supplied with the kit.
5. On field supplied terminations for side wall exit, exhaust
piping may extend a maximum of 12 inches (305 mm)
for 2" PVC and 20 inches (508 mm) for 3" (76 mm) PVC
beyond the outside wall. Intake piping should be as
short as possible. See Figures 28 and 29.
When exhaust and intake piping must be run up an
outside wall, the exhaust piping must be terminated with
pipe sized per Table 8. The intake piping may be
equipped with a 90° elbow turndown. Using turndown
will add 5 feet (1.5 m) to the equivalent length of the
pipe.
NOTE: Care must be taken to avoid recirculation of exhaust
back into intake pipe.
8. Based on the recommendation of the manufacturer, a
multiple furnace installation may use a group of up to
four terminations assembled together horizontally, as
shown in Figure 32.
506725-01
Page 21 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
B
B
D
D
C
3
Intake
C
1
Front View of
Intake and Exhaust
A
Exhaust
A
2
Intake
Exhaust
D
TABLE 9
1
E
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
B
A− Clearance above
grade or average snow
accumulation
12" (508MM) Min.
12" (508MM) Min.
12"
B −Horizontal
separation between
intake and exhaust
6" (152MM) Min.
24" (610 MM) Max
6" (152MM) Min.
24" (610 MM) Max
9" (227MM) Min.
C
2
C −Minimum from
end of exhaust to
inlet of intake
A
9" (227MM) Min.
12" (305MM) Min.
16" (405 MM) Max.
12" (305MM) Min.
20" (508MM) Max.
D−Exhaust pipe length
E −Wall support distance
from top of each pipe
(intake/exhaust)
6" (152MM) Max.
6" (152MM) Max.
1
The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recom-
mended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,
cracks, etc. in affected area, should be sealed using an appropriate sealant.
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away
from adjacent property. The exhaust must never be directed toward the combustion air inlet.
FIGURE 27
Page 22 of 48
Issue 1109
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
FIELD SUPPLIED WALL TERMINATION
FIELD SUPPLIED WALL TERMINATION
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
NOTE − FIELD PROVIDED
REDUCER MAY BE
REQUIRED TO ADAPT
LARGER VENT PIPE SIZE
TO TERMINATION
1/2" (13mm) ARMAFLEX
1/2" (13mm) ARMAFLEX
INSULATION IN UN-
CONDITIONED SPACE
(IF REQUIRED)
INSULATION IN UN-
CONDITIONED SPACE
(IF REQUIRED)
SIZE TERMINATION
PER TABLE 8
SIZE TERMINATION
PER TABLE 8
D
B
D
B
STRAIGHT
STRAIGHT
C
APPPLICATION
C
A
APPPLICATION
A
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE (IF REQUIRED)
1/2" (13mm) ARMAFLEX INSULATION
IN UNCONDITIONED SPACE (IF REQUIRED)
D
D
E
* WALL
SUPPORT
E
* WALL
SUPPORT
B
B
A
A
EXTENDED
APPLICATION
C
C
EXTENDED
APPLICATION
See venting Table 7 for maximum venting lengths with this
arrangement.
See venting Table 7 for maximum venting lengths with this
arrangement.
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
* Use wall support every 24" (610 mm). Use two wall supports if
extension is greater than 24" (610 mm) but less than 48" (1219 mm).
NOTE − One wall support must be 6" (152 mm) from top of each pipe
(intake and exhaust)
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
2" (51mm)
Vent Pipe
3" (76mm)
Vent Pipe
A−Minimum clearance
above grade or average
snow accumulation
A−Minimum clearance
above grade or average
snow accumulation
12" (508MM)
12" (508MM)
12" (508MM)
6" (152MM)
8" (203MM)
12" (508MM)
6" (152MM)
8" (203MM)
B −Maximum horizontal
separation between
intake and exhaust
C −Minimum from
end of exhaust to
inlet of intake
B −Maximum horizontal
separation between
intake and exhaust
6" (152MM)
6" (152MM)
C −Minimum from
end of exhaust to
inlet of intake
6" (152MM)
20" (508MM)
6" (152MM)
6" (152MM)
12" (305MM)
6" (152MM)
D−Maximum exhaust
D−Maximum exhaust
pipe length
12" (305MM)
6" (152MM)
20" (508MM)
6" (152MM)
pipe length
E −Maximum wall support
distance from top of each
pipe (intake/exhaust)
E −Maximum wall support
distance from top of each
pipe (intake/exhaust)
FIGURE 29
FIGURE 28
506725-01
Page 23 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION
71M80, 69M29 or 60L46 (US)
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT
44W92 or 44W93 (Canada)
1 1/2" (38mm) accelerator
provided on 71M80 & 44W92
12"
EXHAUST
VENT
(305mm)
EXHAUST
VENT
5−1/2"
5"
(140mm)
(127mm)
INTAKE
AIR
FLASHING
(Not Furnished)
12” (305mm)
Minimum
INTAKE
AIR
18" MAX.
(457mm)
Front View
Above Average
Snow
EXHAUST VENT
Accumulation
12" (305mm) Min.
above grade or
average snow
accumulation.
Inches (mm)
INTAKE
AIR
SHEET METAL STRAP
(Clamp and sheet metal strap
must be field installed to support
the weight of the termination kit.)
optional intake elbow
CLAMP
Side View
FIGURE 32
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
FIGURE 30
DIRECT VENT CONCENTRIC WALL TERMINATION
71M80, 69M29 or 60L46 (US)
DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
44W92 or 44W93 (Canada)
STRAIGHT−CUT OR
FIELD−PROVIDED
REDUCER MAY BE REQUIRED
1−1/2" (38mm) accelerator
provided on 71M80 & 44W92
ANGLE−CUT IN DIRECTION
OF ROOF SLOPE *
3"−8"
(76mm−203mm)
TO ADAPT LARGER VENT
PIPE SIZE TO TERMINATION
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
INSULATION
8" − 12"
(203mm − 305mm)
OUTSIDE
WALL
INTAKE
AIR
EXHAUST
VENT
EXHAUST
VENT
SHOULDER OF FITTINGS
PROVIDE SUPPORT
Minimum 12" (305MM)
above chimney top
plate or average snow
accumulation
INTAKE PIPE
INSULATION (optional)
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
ALTERNATE
INTAKE PIPE
12" (305mm) Min.
INTAKE
INTAKE
AIR
CLAMP
(Not Furnished)
above grade or
average snow
accumulation.
AIR
3" − 8"
(76mm−
203mm)
INSULATE
TO FORM
SEAL
EXTERIOR
PORTION OF
CHIMNEY
GRADE
FIGURE 31
*SIZE TERMINATION
PIPE PER TABLE 6.
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
FIGURE 33
Page 24 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
Details of Exhaust Piping Terminations for Non-Direct
VentApplications
NON−DIRECT VENT FIELD SUPPLIED WALL
TERMINATION EXTENDED
Exhaust pipe may be routed either horizontally through an
outside wall or vertically through the roof. In attic or closet
installations, vertical termination through the roof is preferred.
Figures 34 through 37 show typical terminations.
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
UNCONDITIONED
SPACE
6" (152mm)
Max
SIZE TER-
MINATION
PIPE PER
TABLE 8.
1. Exhaust piping must terminate straight out or up as
shown. The termination pipe must be sized as listed in
Table 8. The specified pipe size ensures proper velocity
required to move the exhaust gases away from the
building.
2. On field supplied terminations for side wall exit, exhaust
piping may extend a maximum of 12 inches (305 mm)
for 2” PVC and 20” (508 mm) for 3” (76 mm) PVC beyond
the outside wall. See Figure 35.
*WALL SUPPORT
OUTSIDE WALL
FIELD−PROVIDED
REDUCER MAY BE
REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE TO
TERMINATION
12" (305mm)
ABOVE GRADE OR
AVERAGE SNOW
ACCUMULATION
1/2" (13mm) FOAM
INSULATION IN
3. If exhaust piping must be run up a sidewall to position
above snow accumulation or other obstructions, piping
must be supported every 24” (610 mm) as shown in
Figure 36. When exhaust piping must be run up an
outside wall, any reduction in exhaust pipe size must be
done after the final elbow.
UNCONDITIONED
SPACE (IF REQUIRED)
1/2" (13mm) FOAM
INSULATION (IF REQUIRED)
*Use wall support every 24" (610). Use two supports if extension is
greater than 24" but less than 48".
FIGURE 36
NON−DIRECT VENT ROOF TERMINATION KIT
(15F75 or 44J41)
SIZE TERMINATION
PIPE PER TABLE 8.
NON−DIRECT VENT APPLICATION
USING EXISTING CHIMNEY
12" (305mm)
ABOVE AVE.
SNOW
ACCUMULATION
STRAIGHT−CUT OR
SIZE TERMINATION
PIPE PER TABLE 8.
ANGLE−CUT IN DIRECTION
1/2" (13mm) FOAM
INSULATION IF REQUIRED
OF ROOF SLOPE
EXHAUST VENT
1/2" (13mm)
WEATHERPROOF
Minimum 12" (305MM)
3" (76mm) OR
2" (51mm) PVC
INSULATION (IF REQUIRED)
UNCONDITIONED
ATTIC SPACE
above chimney top
plate or average snow
SHOULDER OF FITTINGS
accumulation
PROVIDE SUPPORT
PROVIDE SUPPORT
FOR EXHAUST LINES
OF PIPE ON TOP PLATE
SHEET
METAL TOP
PLATE
INSULATE
TO FORM
SEAL
FIGURE 34
EXTERIOR
PORTION OF
CHIMNEY
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-
tical discharge through an existing unused chimney or stack is required, insert piping
inside chimney until the pipe open end is above top of chimney and terminate as illus-
trated. In any exterior portion of chimney, the exhaust vent must be insulated.
12" (305mm) MAX. for 2" (51mm)
20" (508mm) MAX. for 3" (76mm)
1/2" (13mm) ARMAFLEX
INSULATION IN
UNCONDITIONED SPACE (IF REQUIRED)
1/2" (13mm)
ARMAFLEX
FIGURE 37
FIELD−PROVIDED
REDUCER MAY
INSULATION
(IF REQUIRED)
BE REQUIRED TO
ADAPT LARGER
VENT PIPE SIZE
TO TERMINATION
PVC REDUCER
12" MIN.
(305mm)
Above Grade or
average snow
accumulation
SIZE TERMINATION
PIPE PER TABLE 8.
FIGURE 35
506725-01
Page 25 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Condensate Piping
This unit is designed for either right or left side exit of
condensate piping in downflow applications.
Figure 38 for condensate trap locations.
Condensate line must slope downward away from the trap
to drain. If drain level is above condensate trap, condensate
pump must be used. Condensate drain line should be routed
within the conditioned space to avoid freezing of condensate
and blockage of drain line. If this is not possible, a heat
cable kit may be used on the condensate trap and line.
Heating cable kit is available in various lengths:
Refer to
NOTE: If necessary the condensate trap may be installed
up to 5” away using PVC pipe from the furnace. Piping from
furnace must slope down a minimum of 1/4” per ft. toward
trap.
6 ft. (1.8 m) - kit no. 26K68; 24 ft. (7.3 m) - kit no. 26K69;
and 50 ft. (15.2 m) - kit no. 26K70.
1. Determine which side condensate piping will exit the
unit, location of trap, field-provided fittings and length of
PVC pipe required to reach available drain.
CONDENSATE TRAP LOCATION
(shown with right side exit of condensation)
2. Remove plug (Figure 38) from the cold end header box
at the appropriate location on the side of the unit. Install
field-provided 1/2 NPT male fitting into cold end header
box. Use Teflon tape or appropriate pipe dope.
Field Provided Vent
min. 1" Above
Condensate Drain
3. Install the cap over the clean out opening at the base of
the trap. Secure with clamp. See Figure 41.
4. Install drain trap using appropriate PVC fittings, glue all
Trap can be installed a
maximum of 5 ft. from furnace.
(*PVC Only)
joints.
Glue the provided drain trap as shown in
1" min.
Figure 41. Route the condensate line to an open drain.
Condensate line must maintain a 1/4” downward slope
from the furnace to the drain.
5’ max.
CAUTION
to drain
Do Not use copper tubing or existing copper condensate
lines for drain line.
*Piping from furnace must slope down a minimum of
1/4" per ft. toward trap.
5. If unit will be started immediately upon completion of
installation, prime trap per procedure outlined in Unit
Start-Up section.
FIGURE 39
UNIT WITH EVAPORATOR COIL
CONDENSATE TRAP AND PLUG LOCATIONS
Condensate trap and
evaporator coil must drain
separately as shown.
Field−Provided Vent
Trap
(same on
right side)
Plug
1−1/2 in.
(same on left
Drain
side)
FIGURE 40
CAUTION
A separate drain line must be run to the drain from the
condensate trap to ensure proper drainage and pressure
switch operation. DO NOT connect the condensate trap
drain into the drain line from the evaporator coil.
FIGURE 38
Page 26 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
TRAP / DRAIN ASSEMBLY USING 1/2" PVC OR 3/4" PVC
OPTIONAL Condensate Drain Connection
Adapter 1/2 inch slip X
Adapter 1/2 inch slip X
1/2 inch mpt (Not Furnished)
Condensate Drain
Connection In Unit
1/2 inch mpt (Not Furnished)
Vent
90° Street Elbow
1 (25) Minimum
1/2 inch PVC
5 Feet
Maximum
(Not Furnished)
Above Top of Condensate Drain
Connection In Unit
90° Elbow 1/2 inch PVC
Condensate Drain
Connection In Unit
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
OPTIONAL Drain Piping
Drain Assembly for 1/2 inch Drain Pipe
Coupling 1/2 inch slip X slip
(Not Furnished)
1/2 inch PVC Pipe
(Not Furnished)
Drain Trap
Assembly
(Furnished)
1/2 inch PVC
90° Elbow
(Not Furnished)
1/2 inch PVC
(Not Furnished)
To
To
Drain
Drain
Drain Assembly for 3/4 inch Drain Pipe
Drain Trap
Clean Out
90° Elbow
90° Elbow
3/4 inch PVC
(Not Furnished)
3/4 inch PVC
(Not Furnished)
To
Drain
To
Drain
Coupling 3/4 inch slip X slip
(Not Furnished)
Drain Trap Assembly with 3/4 inch Piping
Drain Trap Assembly with 1/2 inch Piping
1 inch (25mm) Minimum Above Top of
Condensate Drain Connection In Unit
1 inch (25mm) Minimum Above Top of
Condensate Drain Connection In Unit
Vent
Drain Trap Assembly
(Furnished)
Vent
3/4 inch
Piping
7
Condensate Drain
Connection In Unit
Condensate Drain
Connection In Unit
(178)
To
Drain
To
Drain
FIGURE 41
506725-01
Page 27 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Piping
IMPORTANT
Compounds used on threaded joints of gas piping must
be resistant to the actions of liquified petroleum gases.
CAUTION
If a flexible gas connector is required or allowed by the
authority that thas jurisdiction, black iron pipe shall be
installed at the gas valve and extend outside the furnace
cabinet. The flexible connector can then be added
between the black iron pipe and the gas supply line.
Leak Check
After gas piping is completed, carefully check all piping
connections (factory and field installed) for gas leaks. Use
a leak detecting solution or other preferred means.
The furnace must be isolated from the gas supply system
by closing its individual manual shut off valve during any
pressure testing of the gas supply system at pressures
greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).
WARNING
Do Not exceed 600 in. lbs. (50 ft. lbs.) torque when
attaching the gas piping to the gas valve.
MANUAL MAIN SHUT−OFF
FURNACE
VALVE WILL NOT HOLD
1. Gas piping may be routed into the unit through either
the left or right hand side. Supply piping enters into
the gas valve from the side of the valve as shown in
Figure 43. Move bellows grommet to side of the cabinet
which the gas line enters. Ensure opposite gas line
entrance is plugged with supplied plug.
NORMAL TEST PRESSURE
ISOLATE
1/8" N.P.T. PLUGGED TAP
GAS VALVE
CAP
FIGURE 42
IMPORTANT
A low inlet pressure switch in LP/propane applications
is recommended.
IMPORTANT
When testing pressure of gas lines, gas valve must be
disconnected and isolated. (See Figure 42.) Gas
Valves can be damaged if subjected to pressures
greater than 1/2 psig (3.48 kPa).
2. When connecting gas supply, factors such as length of
run, number of fittings and furnace rating must be
considered to avoid excessive pressure drop. Table 10
lists recommended pipe sizes for typical applications.
NOTE: Use two wrenches when connecting gas piping to
avoid transferring torque to the manifold.
WARNING
3. Gas piping must not run in or through air ducts, clothes
chutes, chimneys or gas vents, dumb waiters or elevator
shafts. Center gas line through piping hole. Gas line
should not touch side of unit. See Figures 43.
4. Piping should be sloped 1/4 inch per 15 feet (6 mm per
5.6 m) upward toward the gas meter from the furnace.
The piping must be supported at proper intervals, every
8 to 10 feet (2.44 to 3.05 m), using suitable hangers or
straps. Install a drip leg in vertical pipe runs to serve as
a trap for sediment or condensate.
FIRE OR EXPLOSION HAZARD
Failure to follow the safety warnings exactly could result
in serious injury, death, or property damage. Never use
an open flame to test for gas leaks. Check all
connections using a commercially available soap
solution made specifically for leak detection. Some
soaps used for leak detection are corrosive to certain
metals. Carefully rinse piping thoroughly after leak test
has been completed.
5. A1/8" N.P.T. plugged tap or pressure post is located on
the gas valve to facilitate test gauge connection. See
Figure 50.
6. In some localities, codes may require installation of a
manual main shut off valve and union (furnished by
installer) external to the unit. Union must be of the
ground joint type.
Page 28 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
Left Side Piping
(Standard)
MANUAL
MAIN SHUT−OFF
VALVE
(With 1/8 in. NPT
Plugged Tap
Shown)
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
MANUAL
MAIN SHUT−OFF
VALVE
(With 1/8 in. NPT
Plugged Tap Shown)
AUTOMATIC
GAS VALVE
(with manual
shut−off valve)
Plug
Plug
GROUND
JOINT
UNION
GROUND
JOINT
UNION
DRIP LEG
Right Side Piping
(Alternate)
FIELD
PROVIDED
AND INSTALLED
DRIP LEG
Bellows Grommet
Bellows Grommet
NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET
FIGURE 43
3
GAS PIPE CAPACITY − FT /HR (kL/HR)
Length of Pipe−Feet(m)
Nominal
Iron Pipe Size
−Inches(mm)
Internal
Diameter
10
(3.048)
20
30
(9.144)
40
(12.192)
50
(15.240)
60
(18.288)
70
(21.336)
80
(24.384)
90
(27.432)
100
(30.480)
−Inches(mm)
(6.096)
1/2
(12.7)
.622
(17.799)
175
(4.96)
120
(3.40)
97
(2.75)
82
(2.32)
73
(2.07)
66
(1.87)
61
(1.73)
57
(1.61)
53
(1.50)
50
(1.42)
3/4
(19.05)
.824
(20.930)
360
(10.19)
250
(7.08)
200
(5.66)
170
(4.81)
151
(4.28)
138
(3.91)
125
(3.54)
118
(3.34)
110
(3.11)
103
(2.92)
1
1.049
(26.645)
680
(19.25)
465
(13.17)
375
(10.62)
320
(9.06)
285
(8.07)
260
(7.36)
240
(6.80)
220
(6.23)
205
(5.80)
195
(5.52)
(25.4)
1−1/4
(31.75)
1.380
(35.052)
1400
(39.64)
950
(26.90)
770
(21.80)
660
(18.69)
580
(16.42)
530
(15.01)
490
(13.87)
460
(13.03)
430
(12.18)
400
(11.33)
1−1/2
(38.1)
1.610
(40.894)
2100
(59.46)
460
(41.34)
1180
(33.41)
990
(28.03)
900
(25.48)
810
(22.94)
750
(21.24)
690
(19.54)
650
(18.41)
620
(17.56)
2
2.067
(52.502)
3950
(111.85)
2750
(77.87)
2200
(62.30)
1900
(53.80)
1680
(47.57)
1520
(43.04)
1400
(39.64)
1300
(36.81)
1220
(34.55)
1150
(32.56)
(50.8)
2−1/2
(63.5)
2.469
(67.713)
6300
(178.39)
4350
(123.17)
3520
(99.67)
3000
(84.95)
2650
(75.04)
2400
(67.96)
2250
(63.71)
2050
(58.05)
1950
(55.22)
1850
(52.38)
3
3.068
(77.927)
11000
(311.48)
7700
(218.03)
6250
(176.98)
5300
(150.07)
4750
(134.50)
4300
(121.76)
3900
(110.43)
3700
(104.77)
3450
(97.69)
3250
(92.03)
(76.2)
4
4.026
(102.260)
23000
(651.27)
15800
(447.39)
12800
(362.44)
10900
(308.64)
9700
(274.67)
8800
(249.18)
8100
(229.36)
7500
(212.37)
7200
(203.88)
6700
(189.72)
(101.6)
NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.
TABLE 10
506725-01
Page 29 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Removal of the Furnace from Common Vent
In the event that an existing furnace is removed from a
venting system commonly run with separate gas appliances,
the venting system is likely to be too large to properly vent
the remaining attached appliances.
3. Close all building doors and windows and all doors
between the space in which the appliances remaining
connected to the common venting system are located
and other spaces of the building. Turn ON clothes dryers
and any appliances not connected to the common
venting system. Turn ON any exhaust fans, such as
range hoods and bathroom exhausts, so they will
operate at maximum speed. Do not operate a summer
exhaust fan. Close fireplace dampers.
Conduct the following test while each appliance is operating
and the other appliances (which are not operating) remain
connected to the common venting system. If the venting
system has been installed improperly, you must correct the
system as indicated in the general venting requirements
section.
4. Follow the lighting instructions. Turn ON the appliance
that is being inspected. Adjust the thermostat so that
the appliance operates continuously.
5. After the main burner has operated for 5 minutes, test
for leaks of flue gases at the draft hood relief opening.
Use the flame of a match or candle.
6. After determining that each appliance connected to the
common venting system is venting properly, (step 3)
return all doors, windows, exhaust fans, fireplace
dampers, and any other gas burning appliances to their
previous mode of operation.
7. If a venting problem is found during any of the preceding
tests, the common venting system must be modified to
correct the problems.
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation.
Resize the common venting system to the minimum vent
pipe size determined by using the appropriate tables in
Appendix G. These are in the current standards of the
National Fuel Gas Code ANSI Z223.1.
1. Seal any unused openings in the common venting
system.
2. Inspect the venting system for proper size and horizontal
pitch. Determine that there is no blockage, restriction,
leakage, corrosion, or other deficiencies which could
cause an unsafe condition.
Page 30 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
Electrical
ELECTROSTATIC DISCHARGE (ESD)
The unit is equipped with a field makeup box on the left
hand side of the cabinet. A field-provided make-up box can
be installed on the exterior of the right side of the furnace to
facilitate installation. Seal unused openings on left side with
plugs removed from right side. Secure the excess wire to
the existing harness to protect it from damage.
Precautions and Procedures
CAUTION
Electrostatic discharge can affect electronic
components. Take precautions during furnace
installation and service to protect the furnace’s electronic
controls. Precautions will help to avoid control exposure
to electrostatic discharge by putting the furnace, the
control and the technician at the same electrostatic
potential. Neutralize electrostatic charge by touching
hand and all tools on an unpainted unit surface, such as
the gas valve or blower deck, before performing any
service procedure.
Refer to Figure 47 for field wiring and Figure 48 for schematic
wiring diagram and troubleshooting.
The power supply wiring must meet Class I restrictions.
Protected by either a fuse or circuit breaker, select circuit
protection and wire size according to unit nameplate.
NOTE: Unit nameplate states maximum current draw.
Maximum Over-Current Protection allowed is 15 AMP.
Holes are on both sides of the furnace cabinet to facilitate
wiring.
INTERIOR MAKE−UP BOX
Install a separate (properly sized) disconnect switch near
the furnace so that power can be turned off for servicing.
(FACTORY− INSTALLED LEFT SIDE)
Before connecting the thermostat check to make sure the
wires will be long enough for servicing at a later date. Make
sure that thermostat wire is long enough to facilitate future
removal of blower for service.
MAKE−UP
BOX INSIDE
Left side
CABINET
Complete the wiring connections to the equipment. Use the
provided unit wiring diagram and the field wiring diagram
shown in Figure 47. Use 18 gauge wire or larger that is
suitable for Class II rating for thermostat connections.
Electrically ground the unit according to local codes or, in
the absence of local codes, according to the current National
Electric Code (ANSI/HFPA No. 70) for the USA and current
Canadian Electric Code Part 1 (CSA standard C22.1) for
Canada. Agreen ground wire is provided in the field makeup
box.
FIGURE 44
EXTERIOR MAKE−UP BOX
(FIELD PROVIDED RIGHT SIDE)
NOTE: The gas furnace contains electronic components
that are polarity sensitive. Make sure that the furnace is
wired correctly and is properly grounded.
MAKE−UP
BOX
OUTSIDE
CABINET
Accessory Terminals
One line voltage “EAC” 1/4” spade terminal is provided on
the furnace control board. Any accessory rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral
terminals. If an accessory rated at greater than one amp is
connected to this terminal, it is necessary to use an external
relay. See Figure 49 for control board configuration. This
terminal is energized when the indoor blower is operating.
Right Side
FIGURE 45
506725-01
Page 31 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
One line voltage “HUM” 1/4” spade terminal is provided on
the furnace control board. Any humidifier rated up to one
amp can be connected to this terminal with the neutral leg
of the circuit being connected to one of the provided neutral
terminals. If a humidifier rated at greater than one amp is
connected to this terminal, it is necessary to use an external
relay. See Figure 49 for control board configuration. This
terminal is energized in the heating mode when the
combustion air inducer is operating.
Indoor Blower Speeds
1. When the thermostat is set to “FAN ON”, the indoor
blower will run continuously on the heating speed when
there is no cooling or heating demand.
2. When the furnace is running in the heating mode, the
indoor blower will run on the heating speed.
3. When there is a cooling demand, the indoor blower will
run on the cooling speed.
Generator Use - Voltage Requirements
The following requirements must be kept in mind when
specifying a generator for use with this equipment:
Install the room thermostat according to the instructions
provided with the thermostat. See Figure 46 for thermostat
designations. If the furnace is being matched with a heat
pump, refer to the FM21 installation instruction or appropriate
dual fuel thermostat instructions.
•
•
•
The furnace requires 120 volts ± 10% (Range: 108 volts
to 132 volts).
The furnace operates at 60 Hz ± 5% (Range: 57 Hz to
63 Hz).
The furnace integrated control requires both polarity and
proper ground. Both polarity and proper grounding
should be checked before attempting to operate the
furnace on either permanent or temporary power.
Generator should have a wave form distortion of less
than 5% THD (total harmonic distortion).
FURNACE and CONDENSING UNIT
THERMOSTAT DESIGNATIONS
(Refer to specific thermostat and outdoor unit.)
Thermostat
Furnace
Condensing
Unit
•
*CONDENSING
POWER
HEAT
R
R
W1
Y
W
Y
CONDENSING
CONDENSING
COOLING
INDOOR BLOWER
COMMON
G
C
G
C
FIGURE 46
TYPICAL FIELD WIRING DIAGRAM
IGNITOR
*R
FIGURE 47
Issue 1109
Page 32 of 48
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
TYPICAL WIRING DIAGRAM
FIGURE 48
506725-01
Page 33 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
INTEGRATED CONTROL
(Automatic Hot Surface Ignition System)
HEAT BLOWER
OFF DELAY JUMPER
DIAGNOSTIC CODE
RECALL BUTTON
TERMINAL DESIGNATIONS
Humidifier (120 VAC)
Input (120 VAC)
HUM
L1
XFMR
5 AMP
FUSE
Transformer (120 VAC)
Blower - Continuous Fan (120 VAC)
Electronic Air Cleaner (120 VAC)
Blower - Cooling Speed (120 VAC)
CONT
EAC
COOL
HEAT
PARK
Blower - Heating Speed (120 VAC)
Dead terminals to park alternate spd taps
NEUTRALS Neutral terminals (120 VAC)
FIGURE 49
Unit Start-Up
FOR YOUR SAFETY READ BEFORE OPERATING
CAUTION
Before attempting to perform any service or
maintenance, turn the electrical power to unit OFF at
disconnect switch.
WARNING
Do not use this furnace if any part has been underwater.
A flood-damaged furnace is extremely dangerous.
Attempts to use the furnace can result in fire or
explosion. Immediately call a qualified service technician
to inspect the furnace and to replace all gas controls,
control system parts, and electrical parts that have been
wet or to replace the furnace, if deemed necessary.
BEFORE LIGHTING the unit, smell all around the furnace
area for gas. Be sure to smell next to the floor because
some gas is heavier than air and will settle on the floor.
The gas valve on the unit is equipped with a gas control
switch (lever). Use only your hand to move switch. Never
use tools. If the switch will not move by hand, do not try to
repair it. Force or attempted repair may result in a fire or
explosion.
WARNING
Danger of explosion. Can cause injury
or product or property damage. Should
the gas supply fail to shut off or if
overheating occurs, shut off the gas
valve to the furnace before shutting off
the electrical blower deck, before
performing any service procedure.
Placing the furnace into operation:
This furnace is equipped with an automatic hot surface
ignition system. Do not attempt to manually light burners on
this furnace. Each time the thermostat calls for heat, the
burners will automatically light. The ignitor does not get hot
when there is no call for heat on these units.
Page 34 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
Priming Condensate Trap
9. Replace the heating compartment access panel.
10. Turn on all electrical power to the unit.
11. Set the thermostat to desired setting.
The condensate trap should be primed with water prior to
start-up to ensure proper condensate drainage. Either pour
10 fl. oz. (300 ml) of water into the trap, or follow these
steps to prime the trap:
1. Follow the lighting instructions to place the unit into
operation.
NOTE: When unit is initially started, steps 1 through 11
may need to be repeated to purge air from gas line.
2. Set the thermostat to initiate a heating demand.
3. Allow the burners to fire for approximately 3 minutes.
4. Adjust the thermostat to deactivate the heating demand.
5. Wait for the combustion air inducer to stop. Set the
thermostat to initiate a heating demand and again allow
the burners to fire for approximately 3 minutes.
6. Adjust the thermostat to deactivate the heating demand
and wait for the combustion air inducer to stop. At this
point, the trap should be primed with sufficient water to
ensure proper condensate drain operation.
12. If the appliance will not operate, follow the instructions
“Turning Off Gas to Unit” and call your service technician
or gas supplier.
Turning Off Gas to Unit
1. Set the thermostat to the lowest setting.
2. Turn off all electrical power to the unit if service is to be
performed.
3. Remove the heating compartment access panel.
4. Move gas valve switch to OFF.
5. Replace the heating compartment access panel.
WARNING
Failure To Operate
If you do not follow these instructions exactly, a fire or
explosion may result causing property damage, personal
injury or death.
If the unit fails to operate, check the following:
1. Is the thermostat calling for heat?
2. Are access panels securely in place?
3. Is the main disconnect switch closed?
4. Is there a blown fuse or tripped breaker?
5. Is the filter dirty or plugged? Dirty or plugged filters will
cause the limit control to shut the unit off.
6. Is gas turned on at the meter?
Gas Valve Operation (Figure 50)
1. STOP! Read the safety information at the beginning of
this section.
2. Set the thermostat to the lowest setting.
3. Turn OFF all electrical power to the unit.
4. This furnace is equipped with an ignition device which
automatically lights the burners. Do not try to light the
burners by hand.
7. Is the manual main shut–off valve open?
8. Is the internal manual shut–off valve open?
9. Is the unit ignition system in lockout? If the unit locks
out again, inspect the unit for blockages.
5. Remove the heating compartment access panel.
6. Move gas valve switch to OFF. See Figure 50.
7. Wait five minutes to clear out any gas. If you then smell
gas, STOP! Immediately call your gas supplier from a
neighbor’s phone. Follow the gas supplier’s
instructions. If you do not smell gas go to next step.
8. Move gas valve switch to ON. See Figure 50.
Heating Sequence Of Operation
1. When thermostat calls for heat, combustion air inducer
starts.
2. Combustion air pressure switch proves blower
operation. Switch is factory set and requires no
adjustment.
3. After a 15 second prepurge, the hot surface ignitor
energizes.
4. After a 20 second ignitor warm-up period, the gas valve
solenoid opens. A 4-second “Trial for Ignition” period
begins.
5. Gas is ignited, flame sensor proves the flame, and the
combustion process continues.
6. If flame is not detected after first ignition trial, the ignition
control will repeat steps 3 and 4 four more times before
locking out the gas valve. The ignition control will then
automatically repeat steps 1 through 6 after 60 minutes.
To interrupt the 60 minute lockout period, move
thermostat from “Heat” to “OFF” then back to “Heat”.
Heating sequence then restarts at step 1.
GAS VALVE SHOWN IN ON POSITION
MANIFOLD
PRESSURE
ADJUSTMENT
SCREW
MANIFOLD
PRESSURE
OUTLET
(UNDER CAP)
INLET
PRESSURE
PORT
FIGURE 50
506725-01
Page 35 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Gas Pressure Adjustment
Gas Flow (Approximate)
Supply Line and Manifold Pressure (inches w.c.)
Manifold
GAS METER CLOCKING CHART
Seconds for One Revolution
Unit
Fuel
Line Pressure
Pressure
All
All
Nat. Gas
L.P. Gas
3.5
4.5 − 10.5
Natural
LP
Unit
1 cu ft
2 cu ft
Dial
1 cu ft
Dial
200
136
102
82
2 cu ft
DIAL
10.0
11.0 − 13.0
Dial
80
55
41
33
27
TABLE 12
−045
−070
−090
−110
−135
160
110
82
400
272
204
164
136
NOTE:A natural to L.P. propane gas changeover kit is necessary
to convert this unit. Refer to the changeover kit installation
instruction for the conversion procedure.
66
54
68
Natural−1000 btu/cu ft
LP−2500 btu/cu ft
TABLE 11
Proper Combustion
NOTE: To obtain accurate reading, shut off all other gas
Furnace should operate minimum 15 minutes with correct
manifold pressure and gas flow rate before checking
combustion. Take combustion sample beyond the flue outlet
and compare to the tables below. The maximum carbon
monoxide reading should not exceed 50 ppm.
appliances connected to meter.
Furnace should operate at least 5 minutes before checking
gas flow. Determine time in seconds for two revolutions of
gas through the meter. (Two revolutions assures a more
accurate time.) Divide by two and compare to time in
Table 11. If manifold pressure matches Table 12 and rate
is incorrect, check gas orifices for proper size and restriction.
Remove temporary gas meter if installed.
CO %
CO %
For L.P.
Unit
2
For Nat
2
All
7.2 − 7.9
8.6 − 9.3
Supply Pressure Measurement
A threaded plug on the inlet side of the gas valve provides
access to the supply pressure tap. Remove the threaded
plug, install a field-provided barbed fitting and connect a
manometer to measure supply pressure. Replace the
threaded plug after measurements have been taken.
The maximum carbon monoxide reading should not exceed 50 ppm.
TABLE 13
High Altitude Information
Manifold Pressure Measurement
1. Remove the threaded plug from the outlet side of the
gas valve and install a field provided barbed fitting.
Connect to a manometer to measure manifold pressure.
2. Start unit and allow 5 minutes for unit to reach steady
state.
3. While waiting for the unit to stabilize, observe the flame.
Flame should be stable and should not lift from burner.
Natural gas should burn blue.
NOTE: In Canada, certification for installations at elevations
over 4500 feet (1372 m) is the jurisdiction of local authorities.
The furnace requires no manifold pressure adjustments for
operation at altitudes up to 10,000 feet (3048 m) above sea
level. Units installed at altitudes of 4501 - 10,000 feet (1373
to 3048 m) require a pressure switch change which can be
ordered separately. Table 14 lists conversion kit and
pressure switch requirements at varying altitudes.
4. After allowing unit to stabilize for 5 minutes, record
manifold pressure and compare to value given in
Table 12.
The combustion air pressure switch is factory-set and
requires no adjustment.
NOTE: Shut unit off and remove manometer as soon as
an accurate reading has been obtained. Take care to remove
barbed fitting and replace threaded plug.
Page 36 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
Burner Orifice Conversion Kits at Varying Altitudes
0 - 7,500 ft
(0 - 2,286 m)
7,501 - 10,000 ft
(2,286 - 3,038 m)
High Altitude
High Altitude
LP/Propane
Burner Orifice
Kit
Natural
LP/Propane
to
Natural
Burner Orifice
Kit
Unit
Size
to
LP/Propane
Natural
All
68W75*†
73W80*
51W01
68W70*†
* Conversion requires installation of a gas valve regulator spring which is provided with the gas conversion kit.
† LP kit includes low line pressure switch.
A93 and 92G1 Pressure Switches at Varying Altitudes
Unit
0 - 4,500 ft
4,501 - 7,500 ft 7,501 - 10,000 ft
(0 - 1,373 m)
(1,373 - 2,286 m)
(2,286 - 3,038 m)
Size
All
No Change
No Change
74W91
Pressure switch is factory set. No adjustment necessary.
All models use the factory installed pressure switch from 0 - 7,500 feet.
A95 and 95G1 Pressure Switches at Varying Altitudes
Unit
0 - 4,500 ft
4,501 - 7,500 ft 7,501 - 10,000 ft
(0 - 1,373 m)
(1,373 - 2,286 m)
(2,286 - 3,038 m)
Size
045
070
090
110
135
No Change
No Change
No Change
No Change
No Change
No Change
77W43
74W90
73W22
73W22
73W22
73W22
77W42
77W43
77W42
Pressure switch is factory set. No adjustment necessary.
All models use the factory installed pressure switch from 0 - 4,500 feet.
TABLE 14
506725-01
Page 37 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Testing for Proper Venting and Sufficient Combustion Air for Non-Direct Vent Applications
6. Follow the lighting instruction to place the appliance
being inspected into operation. Adjust thermostat so
appliance will operate continuously.
WARNING
7. Use the flame of a match or candle to test for spillage
of flue gases at the draft hood relief opening after 5
minutes of main burner operation.
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each
appliance connected to the venting system being placed
into operation could result in carbon monoxide poisoning
or death.
8. If improper venting is observed during any of the above
tests, the venting system must be corrected or sufficient
combustion/makeup air must be provided. The venting
system should be resized to approach the minimum
size as determined by using the appropriate tables in
appendix G in the current standards of the National Fuel
Gas Code ANSI-Z223.1/NPFA 54 in the U.S.A., and
the appropriate Natural Gas and Propane appliances
venting sizing tables in the current standard of the CSA-
B149 Natural Gas and Propane Installation Codes in
Canada.
9. After determining that each appliance remaining
connected to the common venting system properly
vents when tested as indicated in step 3, return doors,
windows, exhaust fans, fireplace dampers and any other
gas burning appliance to their previous condition of use.
The following steps shall be followed for each appliance
connected to the venting system being placed into
operation, while all other appliances connected to the
venting system are not in operation.
After the gas furnace has been started, the following test
should be conducted to ensure proper venting and sufficient
combustion air has been provided to the unit as well as to
other gas fired appliances which are separately vented.
If this furnace replaces a Category I furnace which was
commonly vented with another gas appliance, the size of
the existing vent pipe for that gas appliance must be
checked. Without the heat of the original furnace flue
products, the existing vent pipe is probably oversized for
the single water heater or other appliance. The vent should
be checked for proper draw with the remaining appliance.
The test should be conducted while all appliances (both in
operation and those not in operation) are connected to the
venting system being tested. If the venting system has been
installed improperly, or if provisions have not been made
for sufficient amounts of combustion air, corrections must
be made as outlined in the previous section.
1. Seal any unused openings in the venting system.
2. Visually inspect the venting system for proper size and
horizontal pitch. Determine there is no blockage or
restriction, leakage, corrosion, or other deficiencies
which could cause an unsafe condition.
3. To the extent that it is practical, close all building doors
and windows and all doors between the space in which
the appliances connected to the venting system are
located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliances not
connected to the venting system. Turn on any exhaust
fans, such as range hoods and bathroom exhausts, so
they will operate at maximum speed. Do not operate
a summer exhaust fan.
Page 38 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
Thermostat Heat Anticipation
Other Unit Adjustments
Set the heat anticipator setting (if adjustable) according to
the amp draw listed on the wiring diagram that is attached
to the unit.
Primary Limit
The primary limit is located on the heating compartment
vestibule panel. This limit is factory set and requires no
adjustment.
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (with
furnace operating). Correct voltage is 120 VAC ± 10%.
3. Check amp–draw on the blower motor with the blower
compartment access panel in place.
Flame Rollout Switches (Two)
These manually reset switches are located on the front of
the burner box. These limits are factory set and require no
adjustment.
Motor Nameplate__________Actual__________
Pressure Switch
The pressure switch is located in the heating compartment
on the cold end header box. This switch checks for proper
combustion air inducer operation before allowing ignition
trial. The switch is factory set and must not be adjusted.
Blower Speeds
Follow the steps below to change the blower speeds.
1. Turn off electrical power to furnace.
2. Remove blower compartment access panel.
3. Disconnect existing speed tap at control board speed
terminal.
Temperature Rise
After the furnace has been started and supply and return
air temperatures have been allowed to stabilize, check the
temperature rise. If necessary, adjust the blower speed to
maintain the temperature rise within the range shown on
the unit nameplate. Increase the blower speed to decrease
the the temperature. Decrease the blower speed to increase
the temperature rise. Failure to adjust the temperature rise
may cause erratic limit operation.
NOTE: Termination of any unused motor leads must be
insulated.
4. Place unused blower speed tap on integrated control
“PARK” terminal or insulate.
5. Refer to blower speed selection chart on unit wiring
diagram for desired heating or cooling speed. See
Blower performance data beginning on the next page.
6. Connect selected speed tap at control board speed
terminal.
7. Re-secure blower access panel.
8. Turn on electrical power to furnace.
9. Recheck temperature rise.
Fan Control
The fan ON time of 30 seconds is not adjustable. The fan
OFF delay (amount of time that the blower operates after
the heat demand has been satisfied) may be adjusted by
changing the jumper position across the five pins on the
integrated control. The unit is shipped with a factory heat
fan OFF setting of 120 seconds. The fan OFF delay affects
comfort and is adjustable to satisfy individual applications.
Adjust the fan OFF delay to achieve a supply air temperature
between 90° and 110° F at the moment that the blower is
de-energized. Longer OFF delay settings provide lower
return air temperatures; shorter settings provide higher
return air temperatures. See Figure 51.
Electronic Ignition
The integrated control has an added feature of an internal
Watchguard control. The feature serves as an automatic
reset device for integrated control lockout caused by ignition
failure. This type of lockout is usually due to low gas line
pressure. After one hour of continuous thermostat demand
for heat, the Watchguard will break and remake thermostat
demand to the furnace and automatically reset the integrated
control to begin the ignition sequence.
HEAT FAN-OFF TIME IN SECONDS
Exhaust and Air Intake Pipe
1. Check exhaust and air intake connections for tightness
and to make sure there is no blockage.
2. Is pressure switch closed? Obstructed exhaust pipe
will cause unit to shut off at pressure switch. Check
termination for blockages.
NO JUMPER
To adjust fan−off timing, reposition jumper across pins to
achieve desired setting.
60 Second
off Time
90 Second
off Time
120 Second
off Time
180 Second
off Time
3. Obstructed pipe or termination may cause rollout
switches to open. Reset manual flame rollout switches
on burner box assembly if necessary.
FIGURE 51
506725-01
Page 39 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
BLOWER DATA A93DF1D / 92G1DF
A93DF1D / 92G1DF 045*12B PERFORMANCE (Less Filter)
A93DF1D / 92G1DF 090*16C PERFORMANCE (Less Filter)
Air Volume / Watts at Various Blower Speeds
Air Volume / Watts at Various Blower Speeds
External
External
Static
Medium-
High
Medium-
Low
Medium-
High
Medium-
Low
Static
Pressure
in. w.g.
High
Low
High
Low
Pressure
in. w.g.
cfm Watts cfm Watts cfm Watts cfm Watts
1615 650 1385 555 1205 465 1045 390
1605 640 1375 545 1195 455 1035 380
1500 620 1340 525 1165 445 1015 370
1450 590 1290 490 1125 420 975 365
1350 560 1235 480 1090 405 920 345
1300 545 1170 450 1035 380 875 335
1195 500 1095 425 990 365 840 320
1140 485 1020 400 895 345 780 300
1025 450 920 370 840 330 695 275
945 435 800 335 700 295 605 250
cfm Watts cfm Watts cfm Watts cfm Watts
2145 900 1865 740 1545 635 1295 530
2135 890 1855 730 1540 625 1290 520
2065 845 1815 710 1525 600 1285 500
2010 825 1760 685 1510 580 1275 485
1930 775 1705 630 1495 575 1235 455
1845 740 1645 610 1450 530 1215 450
1745 700 1525 550 1380 505 1185 430
1620 650 1460 535 1315 480 1110 405
1450 585 1340 505 1220 445 1020 375
1320 555 1130 450 1010 385 920 345
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
A93DF1D / 92G1DF 070*12B PERFORMANCE (Less Filter)
A93DF1D / 92G1DF 110*20C PERFORMANCE (Less Filter)
Air Volume / Watts at Various Blower Speeds
External
Air Volume / Watts at Various Blower Speeds
External
Medium-
High
Medium-
Low
Medium-
High
Medium-
Low
Static
Pressure
in. w.g.
Static
Pressure
in. w.g.
High
Low
High
Low
cfm Watts cfm Watts cfm Watts cfm Watts
1505 660 1310 570 1090 455 940 390
1480 625 1295 550 1070 435 935 365
1405 585 1255 515 1055 425 930 350
1355 580 1225 475 1045 405 900 330
1305 540 1165 470 1010 385 890 325
1270 525 1110 425 975 370 835 305
1175 500 1080 415 925 345 815 290
1105 460 1000 395 855 320 745 270
1040 440 925 365 790 300 670 250
920 400 825 335 680 270 560 225
cfm Watts cfm Watts cfm Watts cfm Watts
2410 1390 2190 1080 1860 910 1560 735
2405 1385 2180 1070 1855 905 1555 730
2285 1345 2120 1030 1850 865 1540 720
2220 1315 2015 1005 1770 840 1535 705
2185 1295 1950 955 1750 815 1530 685
2045 1240 1830 925 1680 790 1500 660
1965 1220 1710 890 1575 755 1445 640
1820 1165 1610 850 1495 720 1370 615
1625 1155 1510 820 1400 695 1315 595
1455 1110 1390 790 1350 660 1210 565
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
NOTES: All air data is measured external to unit without filter (not furnished - field provided)
Page 40 of 48
Issue 1109
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
BLOWER DATA A95DF1D / 95G1DF
A95DF1D / 95G1DF 045*12B PERFORMANCE (Less Filter)
A95DF1D / 95G1DF 090*20C PERFORMANCE (Less Filter)
Air Volume / Watts at Various Blower Speeds
Air Volume / Watts at Various Blower Speeds
External
External
Static
Medium-
High
Medium-
Low
Medium-
High
Medium-
Low
Static
Pressure
in. w.g.
High
Low
High
Low
Pressure
in. w.g.
cfm Watts cfm Watts cfm Watts cfm Watts
1615 650 1385 555 1205 465 1045 390
1605 640 1380 545 1195 455 1035 380
1500 620 1345 525 1165 445 1015 370
1450 590 1290 490 1125 420 975 365
1350 560 1235 480 1090 405 920 345
1300 545 1170 450 1035 380 880 330
1195 500 1095 425 990 365 840 320
1140 480 1020 395 895 345 780 300
1025 450 920 370 840 330 695 270
945 430 800 335 700 290 605 250
cfm Watts cfm Watts cfm Watts cfm Watts
2305 1255 2145 950 1900 810 1515 670
2295 1240 2135 940 1885 795 1500 665
2200 1220 2085 915 1865 775 1525 655
2160 1210 1990 875 1830 755 1545 640
2055 1170 1935 865 1790 725 1530 620
1970 1130 1855 835 1705 700 1500 600
1890 1105 1765 805 1635 675 1495 580
1775 1075 1680 785 1565 655 1430 560
1690 1050 1590 760 1485 630 1370 540
1580 1010 1485 735 1405 610 1270 510
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
A95DF1D / 95G1DF 070*12B PERFORMANCE (Less Filter)
A95DF1D /95G1DF 110*20C PERFORMANCE (Less Filter)
Air Volume / Watts at Various Blower Speeds
External
Air Volume / Watts at Various Blower Speeds
External
Medium-
High
Medium-
Low
Medium-
High
Medium-
Low
Static
Pressure
in. w.g.
Static
Pressure
in. w.g.
High
Low
High
Low
cfm Watts cfm Watts cfm Watts cfm Watts
1515 620 1315 545 1095 465 910 390
1490 585 1300 525 1075 445 890 375
1445 555 1275 500 1065 425 910 360
1380 520 1240 470 1060 400 900 340
1315 495 1190 440 1020 385 875 325
1270 470 1145 420 995 355 870 310
1155 435 1075 390 940 330 820 300
1075 415 1000 355 875 310 765 270
975 380 900 325 800 285 715 250
900 365 800 300 675 255 615 225
cfm Watts cfm Watts cfm Watts cfm Watts
2375 1250 2205 915 1975 785 1630 640
2365 1235 2195 905 1960 775 1625 635
2275 1200 2125 890 1950 760 1635 625
2200 1180 2060 880 1900 735 1620 610
2115 1150 1995 850 1845 710 1620 600
2040 1115 1940 835 1795 695 1585 580
1955 1090 1855 810 1745 670 1540 565
1860 1070 1730 765 1640 650 1515 550
1735 1030 1620 740 1590 620 1415 535
1640 1010 1535 715 1480 600 1330 510
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
NOTES: All air data is measured external to unit without filter (not furnished - field provided)
506725-01
Page 41 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Service
Winterizing and Condensate Trap Care
1. Turn off power to the furnace.
2. Have a shallow pan ready to empty condensate water.
3. Remove the clean out cap from the condensate trap
and empty water. Inspect the trap then reinstall the clean
out cap.
WARNING
ELECTRICAL SHOCK, FIRE,
OR EXPLOSION HAZARD.
Failure to follow safety warnings exactly could result in
dangerous operation, serious injury, death or property
damage.
Cleaning Heat Exchanger
If cleaning the heat exchanger becomes necessary, follow
the below procedures and refer to Figure 1 when
disassembling unit. Use papers or protective covering in
front of furnace while removing heat exchanger assembly.
1. Turn off electrical and gas supplies to the furnace.
2. Remove the furnace access panels.
3. Disconnect the 2 wires from the gas valve.
4. Remove gas supply line connected to gas valve.
Remove gas valve/manifold assembly.
Improper servicing could result in dangerous operation,
serious injury, death, or property damage.
Before servicing, disconnect all electrical power to
furnace.
When servicing controls, label all wires prior to
disconnecting. Take care to reconnect wires correctly.
Verify proper operation after servicing.
5. Remove sensor wire from sensor. Disconnect 2 pin
plug from the ignitor.
6. Disconnect wires from flame rollout switches.
7. Loosen clamps at vent elbow. Disconnect condensate
drain tubing from flue collar and remove the vent elbow.
8. Remove four burner box screws at the vestibule panel
and remove burner box. Set burner box assembly aside.
At the beginning of each heating season, system should be
checked as follows by a qualified service technician:
Blower
Check the blower wheel for debris and clean if necessary.
The blower motors are prelubricated for extended bearing
life. No further lubrication is needed.
NOTE: If necessary, clean burners at this time. Follow
procedures outlined in Burner Cleaning section.
9. Mark and disconnect all combustion air pressure tubing
from cold end header collector box.
10. Mark and remove wires from pressure switches.
Remove pressure switches. Keep tubing attached to
pressure switches.
11. Disconnect the plug from the combustion air inducer.
Remove two screws which secure combustion air
inducer to collector box. Remove combustion air inducer
assembly. Remove ground wire from vest panel.
12. Remove electrical junction box from the side of the
furnace.
13. Mark and disconnect any remaining wiring to heating
compartment components. Disengage strain relief
bushing and pull wiring and bushing through the hole in
the blower deck.
14. Remove the primary limit from the vestibule panel.
15. Remove two screws from the front cabinet flange at the
blower deck. Spread cabinet sides slightly to allow
clearance for removal of heat exchanger.
16. Remove screws along vestibule sides and bottom which
secure vestibule panel and heat exchanger assembly
to cabinet. Remove two screws from blower rail which
secure bottom heat exchanger flange. Remove heat
exchanger from furnace cabinet.
17. Back wash heat exchanger with soapy water solution or
steam. If steam is used it must be below 275°F (135°C).
18. Thoroughly rinse and drain the heat exchanger. Soap
solutions can be corrosive. Take care to rinse entire
assembly.
WARNING
The blower access panel must be securely in place when
the blower and burners are operating. Gas fumes, which
could contain carbon monoxide, can be drawn into living
space resulting in personal injury or death.
Filters
All air filters are installed external to the unit. Filters should
be inspected monthly. Clean or replace the filters when
necessary to ensure proper furnace operation. Table 3 lists
recommended filter sizes.
Exhaust and air intake pipes
Check the exhaust and air intake pipes and all connections
for tightness and to make sure there is no blockage.
NOTE: After any heavy snow, ice or frozen fog event the
furnace vent pipes may become restricted. Always check
the vent system and remove any snow or ice that may be
obstructing the plastic intake or exhaust pipes.
Electrical
1. Check all wiring for loose connections.
2. Check for the correct voltage at the furnace (furnace
operating). Correct voltage is 120 VAC ± 10%.
3. Check amp-draw on the blower motor with the blower
compartment access panel in place.
Motor Nameplate__________Actual__________
Page 42 of 48
Issue 1109
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
19. Reinstall heat exchanger into cabinet making sure that
the clamshells of the heat exchanger assembly are
resting on the support located at the rear of the cabinet.
Remove the indoor blower to view this area through the
blower opening.
Cleaning the Burner Assembly
1. Turn off electrical and gas power supplies to furnace.
Remove upper and lower furnace access panels.
2. Disconnect the 2 pin plug from the gas valve.
3. Remove the burner box cover.
20. Resecure the supporting screws along the vestibule
sides and bottom to the cabinet. Reinstall blower and
mounting screws.
21. Reinstall cabinet screws on front flange at blower deck.
22. Reinstall the primary limit on the vestibule panel.
23. Route heating component wiring through hole in blower
deck and reinsert strain relief bushing.
4. Disconnect the gas supply line from the gas valve.
Remove gas valve/manifold assembly.
5. Mark and disconnect sensor wire from the sensor.
Disconnect 2 pin plug from the ignitor at the burner box.
6. Remove four screws which secure burner box assembly
to vest panel. Remove burner box from the unit.
7. Use the soft brush attachment on a vacuum cleaner to
gently clean the face of the burners. Visually inspect
the inside of the burners and crossovers for any blockage
caused by foreign matter. Remove any blockage.
8. Reconnect the sensor wire and reconnect the 2 pin plug
to the ignitor wiring harness.
24. Reinstall electrical junction box.
25. Reinstall the combustion air inducer. Reconnect the
combustion air inducer to the wire harness.
26. Reinstall pressure switches and reconnect pressure
switch wiring.
27. Carefully connect combustion air pressure switch hosing
from pressure switches to proper stubs on cold end
header collector box.
9. Reinstall the burner box assembly using the existing four
screws. Make sure that the burners line up in the
center of the burner ports.
10. Reinstall the gas valve manifold assembly. Reconnect
the gas supply line to the gas valve. Reinstall the burner
box cover.
28. Reinstall condensate trap.
29. Reconnect exhaust piping and exhaust drain tubing.
30. Reinstall burner box assembly in vestibule area.
31. Reconnect flame rollout switch wires.
11. Reconnect 2 pin plug to gas valve.
32. Reconnect sensor wire and reconnect 2 pin plug from
ignitor.
33. Secure burner box assembly to vestibule panel using
four existing screws. Make sure burners line up in
center of burner ports.
34. Reinstall gas valve manifold assembly. Reconnect gas
supply line to gas valve.
35. Reconnect 2 wires to gas valve.
12. Replace the blower compartment access panel.
13. Refer to instruction on verifying gas and electrical
connections when re-establishing supplies.
14. Follow lighting instructions to light and operate furnace
for 5 minutes to ensure that heat exchanger is clean
and dry and that furnace is operating properly.
15. Replace heating compartment access panel.
36. Replace the blower compartment access panel.
37. Refer to instruction on verifying gas and electrical
connections when re-establishing supplies.
38. Follow lighting instructions to light and operate furnace
for 5 minutes to ensure that heat exchanger is clean
and dry and that furnace is operating properly.
39. Replace heating compartment access panel.
506725-01
Page 43 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Planned Service
DIAGNOSTIC CODES
A service technician should check the following items during
an annual inspection. Power to the unit must be shut off for
safety.
Fresh air grilles and louvers (on the unit and in the room
where the furnace is installed) - Must be open and
unobstructed to provide combustion air.
Burners - Must be inspected for rust, dirt, or signs of water.
Vent pipe - Must be inspected for signs of water, cracked,
damaged or sagging pipe, or disconnected joints.
Unit appearance - Must be inspected for rust, dirt, signs of
water, burnt or damaged wires, or components.
Blower access door - Must be properly in place and provide
a seal between the return air and the room where the furnace
is installed.
Return air duct - Must be properly attached and provide
an air seal to the unit.
Operating performance - Unit must be observed during
operation to monitor proper performance of the unit and
the vent system.
Combustion gases - Flue products must be analyzed and
compared to the unit specifications.
Problems detected during the inspection may make it
necessary to temporarily shut down the furnace until the
items can be repaired or replaced.
Instruct the homeowners to pay attention to their
furnace. Situations can arise between annual furnace
inspections that may result in unsafe operation. For
instance, items innocently stored next to the furnace may
obstruct the combustion air supply. This could cause
incomplete combustion and the production of carbon
monoxide gas.
Page 44 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
REPAIR PARTS LIST
The following repair parts are available through Allied Air dealers. When ordering parts, include the complete furnace model
number listed on the CSAnameplate. Example: A93DF045P36B-01. All service must be performed by a licensed professional
installer (or equivalent), service agency, or gas supplier.
Cabinet Parts
Heating Parts
Heating Compartment Access Panel
Blower Compartment Access Panel
Top Cap
Flame Sensor
Heat Exchanger Assembly
Gas Manifold
Combustion Air Inducer
Gas Valve
Main Burner Cluster
Main Burner Orifices
Control Panel Parts
Transformer
Integrated Control Board
Door Interlock Switch
Pressure Switch
Ignitor
Primary Limit Control
Blower Parts
Blower Wheel
Flame Rollout Switches
Motor
Motor Mounting Frame
Motor Capacitor
Blower Housing Cutoff Plate
506725-01
Page 45 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
Start−Up & Performance Check List
UNIT SET UP
Furnace:
Model Number_______________
Serial Number_________________
SUPPLY
AIR
Line Voltage
2
4
1
GAS SUPPLY
LP Propane Gas
Natural Gas
3
Piping Connections Tight
Leak Tested
Flter
RETURN AIR
2
1
Gas Supply Pressure
DUCT SYSTEM
3
1
SUPPLY AIR DUCT
Sealed
Insulated (if necessary)
RETURN DUCT
2
INTAKE / EXHAUST PIPE
Sealed
All Joints Primed and Glued
Filter Installed and Clean
Terminations Installed Properly
Grilles Unobstructed
Horizontal Pipes Sloped (if applicable)
Condensate Trap Primed / Line Sloped
VOLTAGE CHECK
Supply Voltage _____
4
Electrical Connections Tight
Pipes Supported
Heat Cable Installed and Operable (if applicable)
Page 46 of 48
Issue 1109
506725-01
Download from Www.Somanuals.com. All Manuals Search And Download.
UNIT OPERATION
HEATING MODE
COOLING MODE
1
2
GAS MANIFOLD PRESSURE “W.C.” ______
3
4
INDOOR BLOWER AMPS ______
COMBUSTION SAMPLE CO ______%
CO _____ PPM
TEMPERATURE DROP
2
______
Return Duct Temperature
Supply Duct Temperature
_
=
3
4
INDOOR BLOWER AMPS ______
______
______
Temperature Drop
TEMPERATURE RISE
5
TOTAL EXTERNAL STATIC (dry coil)
Supply Duct Temperature _
______
______
Supply External Static
Return External Static
Total External Static
DRAIN LINE
Return Duct Temperature
Temperature Rise
______
______
______
+
=
=
______
5
TOTAL EXTERNAL STATIC
Supply External Static
Return External Static
8
9
______
______
Leak Free
+
=
Total External Static
CONDENSATE LINE
Leak Free
______
6
7
THERMOSTAT
Adjusted and Programmed
Explained Operation to Owner
VENT PIPE
Leak Free
Combustion CO
2
2
7
SUPPLY
AIR
Thermostat
Temperatures
8
Gas Manifold Pressure
9
4
1
Blower Motor Amps
6
3
Duct Static
5
RETURN AIR
Contractor’s: Name______________________________________Telephone________________Checklist Completed____________________
Job Address_______________________________________________________Technician’s Name___________________________________
506725-01
Page 47 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
REQUIREMENTS for COMMONWEALTH of MASSACHUSETTS
4. INSPECTION. The state or local gas inspector of the
Modifications to NFPA-54, Chapter 10
Revise NFPA-54 section 10.8.3 to add the following
requirements:
side wall, horizontally vented, gas-fueled equipment shall
not approve the installation unless, upon inspection, the
inspector observes carbon monoxide detectors and
signage installed in accordance with the provisions of
248 CMR 5.08(2)(a) 1 through 4.
For all side wall, horizontally vented, gas fueled equipment
installed in every dwelling, building or structure used in whole
or in part for residential purposes, including those owned or
operated by the Commonwealth and where the side wall
exhaust vent termination is less than seven (7) feet above
the finished grade in the area of the venting, including but
not limited to decks and porches, the following requirements
shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE
DETECTORS. At the time of installation of the side wall,
horizontally vented, gas-fueled equipment, the installing
plumber or gas fitter shall observe that a hard wired
carbon monoxide detector with an alarm and battery
backup is installed on the floor level where the gas
equipment is to be installed. In addition, the installing
plumber or gas fitter shall observe that a battery operated
or hard wired carbon monoxide detector with an alarm
is installed on each additional level of the dwelling,
building or structure served by the side wall, horizontally
vented, gas fueled equipment. It shall be the
responsibility of the property owner to secure the
services of qualified licensed professionals for the
installation of hard wired carbon monoxide detectors.
a. In the event that the side wall, horizontally vented,
gas fueled equipment is installed in a crawl space
or an attic, the hard wired carbon monoxide detector
with alarm and battery backup may be installed on
the next adjacent floor level.
EXEMPTIONS: The following equipment is exempt from
24 CMR 5.08(2)(a) 1 through 4:
1. The equipment listed in Chapter 10 entitled “Equipment
Not Required to Be Vented” in the most current edition
of NFPA 54 as adopted by the Board; and
2. Product Approved side wall, horizontally vented, gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure used in
whole or in part for residential purposes.
MANUFACTURER REQUIREMENTS -
GAS EQUIPMENT VENTING SYSTEM PROVIDED.
When the manufacturer of Product Approved side wall,
horizontally vented, gas fueled equipment provides a venting
system design or venting system components with the
equipment, the instructions provided by the manufacturer
for installation of the equipment and the venting system shall
include:
1. Detailed instructions for the installation of the venting
system design or the venting system components: and
2. A complete parts list for the venting system design or
venting system.
MANUFACTURER REQUIREMENTS -
b. In the event that the requirements of this subdivision
cannot be met at the time of completion of
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.
When the manufacturer of Product Approved sidewall,
horizontally vented, gas fueled equipment does not provide
the parts for venting the flue gases, but identifies “special
venting systems,” the following requirements shall be
satisfied by the manufacturer:
1. The referenced “special venting system” instructions
shall be included with the appliance or equipment
installation instructions; and
2. The “special venting systems” shall be Product
Approved by the Board, and the instructions for that
system shall include a parts list and detailed installation
instructions.
A copy of all installation instructions for all Product
Approved side wall, horizontally vented, gas fueled
equipment, all venting instructions, all parts lists for
venting instructions, and/or all venting design
instructions shall remain with the appliance or
equipment at the completion of the installation.
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide
detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS.
Each carbon monoxide detector as required in
accordance with the above provisions shall comply with
NFPA720 and beANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall
be permanently mounted to the exterior of the building
at a minimum height of eight (8) feet above grade directly
in line with the exhaust vent terminal for the horizontally
vented, gas fueled heating appliance or equipment. The
sign shall read, in print size no less than one half (1/2)
inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS.”
Page 48 of 48
Issue 1109
Download from Www.Somanuals.com. All Manuals Search And Download.
506725-01
|