Allied Air Enterprises Furnace 92G1DF User Manual

INSTALLATION INSTRUCTIONS  
A95DF, A93DF, 95G1DF & 92G1DF  
Warm Air Gas Furnace / Downflow Air Discharge  
This manual must be left with the homeowner for future reference.  
This is a safety alert symbol and should never be ignored. When you see this symbol on labels or in  
manuals, be alert to the potential for personal injury or death.  
WARNING  
CAUTION  
Improper installation, adjustment, alteration, service or  
maintenance can cause property damage, personal injury  
or loss of life. Installation and service must be performed  
by a licensed professional installer (or equivalent), service  
agency or the gas supplier.  
As with any mechanical equipment, personal injury can  
result from contact with sharp sheet metal edges. Be  
careful when you handle this equipment.  
TABLE OF CONTENTS  
Unit Dimensions............................................................ 2  
A95/A93/95G1/92G1DF Parts Arrangement................. 3  
A95/A93/95G1/92G1DF Gas Furnace .......................... 4  
Shipping and Packing List ............................................ 4  
Safety Information ......................................................... 4  
Use of Furnace as a Construction Heater .................... 5  
General ......................................................................... 6  
Combustion, Dilution, Ventilation Air............................. 6  
Setting Equipment ........................................................ 9  
Filters .......................................................................... 12  
Duct System................................................................ 12  
Pipe and Fittings Specifications .................................. 12  
Joint Cementing Procedure ........................................ 14  
Venting Practices ........................................................ 14  
Vent Piping Guidelines................................................ 15  
Gas Piping .................................................................. 28  
Electrical ..................................................................... 31  
Unit Start Up................................................................ 34  
Gas Pressure Adjustment ........................................... 36  
High Altitude Information............................................. 36  
Other Unit Adjustments ............................................... 39  
Blower Motor Performance ......................................... 40  
Service ........................................................................ 42  
Planned Service.......................................................... 44  
Diagnostic Codes........................................................ 44  
Repair Parts List ......................................................... 45  
Start Up Checklist ....................................................... 46  
Manufactured By  
Allied Air Enterprises, Inc.  
A Lennox International, Inc. Company  
215 Metropolitan Drive  
*P506725-01*  
(P) 506725-01  
West Columbia, SC 29170  
506725-01  
Page 1 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PARTS ARRANGEMENT  
CONTROL BOX  
(Includes integrated control,  
transformer and door switch)  
BAG ASSEMBLY  
BLOWER MOTOR  
(hidden)  
BLOWER  
COMPARTMENT  
ACCESS  
PANEL  
COMBUSTION  
AIR INDUCER  
BLOWER DECK  
PRIMARY LIMIT  
HEATING  
COMPARTMENT  
ACCESS  
COLD END HEADER BOX  
HEAT EXCHANGER  
PANEL  
GAS VALVE  
BURNER BOX ASSEMBLY  
(includes flame sensor, rollout switches and ignitor)  
FIGURE 1  
506725-01  
Page 3 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Gas Furnace  
Safety Information  
This Category IV gas furnace is shipped ready for installation  
in the downflow position.  
WARNING  
The furnace is equipped for installation in natural gas  
applications. Aconversion kit (ordered separately) is required  
for use in propane/LP gas applications.  
Improper installation, adjustment, alteration, service or  
maintenance can cause property damage, personal injury  
or loss of life. Installation and service must be performed  
by a licensed professional installer (or equivalent), service  
agency or the gas supplier.  
This unit can be installed as either a Direct Vent or a  
Non-Direct Vent gas central furnace  
NOTE: In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged outdoors. In  
Non-Direct Vent installations, combustion air is taken from  
indoors and flue gases are discharged outdoors. See Figure  
2 for applications involving roof termination.  
CAUTION  
As with any mechanical equipment, personal injury can  
result from contact with sharp sheet metal edges. Be  
careful when you handle this equipment.  
DANGER  
DANGER OF EXPLOSION!  
There are circumstances in which odorant used with LP/  
Propane gas can lose its scent. In case of a leak, LP/  
Propane gas will settle close to the floor and may be difficult  
to smell. An LP/Propane leak detector should be installed  
in all LP applications.  
Use only the type of gas approved for use with this furnace.  
Refer to unit nameplate.  
This unit is CSA International certified to ANSI Z21.47 and  
CSA 2.3 standards.  
FIGURE 2  
Building Codes  
In the USA, installation of gas furnaces must conform with  
local building codes. In the absence of local codes, units  
must be installed according to the current National Fuel Gas  
Code (ANSI Z223.1/NFPA54). The National Fuel Gas Code  
is available from the American National Standards  
Institute, Inc., 11 West 42nd Street, New York, NY 10036.  
Shipping and Packing List  
Package 1 of 1 contains:  
1 - Assembled Gas Unit  
1 - Bag assembly containing the following:  
3 - Wire nuts  
1 - Snap bushing  
1 - Snap Plug  
1 - Wire tie  
1 - Condensate trap  
In Canada, installation must conform with current National  
Standard of Canada CSA-B149 Natural Gas and Propane  
Installation Codes, local plumbing or waste water codes and  
other applicable local codes.  
1 - Condensate trap cap  
1 - Condensate trap clamp  
1 - 2” diameter debris screen  
In order to ensure proper unit operation in non-direct vent  
applications, combustion and ventilation air supply must be  
provided according to the current National Fuel Gas Code  
or CSA-B149 standard.  
Check equipment for shipping damage. If you find any  
damage, immediately contact the last carrier.  
Please refer to specification sheets for available accessories.  
Page 4 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
Locations and Clearances  
Heating Unit Installed Parallell to Air Handler Unit  
This furnace is CSA International certified for installation  
clearances to combustible material as listed on the unit  
nameplate and in the table in Figure 11. Accessibility and  
service clearances must take precedence over fire protection  
clearances.  
NOTE: When furnace is installed on a combustible floor, a  
downflow combustible flooring base must be installed  
between the furnace and the floor.  
AIR HANDLER  
GAS UNIT  
For installation in a residential garage, the furnace must be  
installed so that the burner(s) and the ignition source are  
located no less than 18 inches (457 mm) above the floor.  
The furnace must be located or protected to avoid physical  
damage by vehicles. When a furnace is installed in a public  
garage, hangar, or other building that has a hazardous  
atmosphere, the furnace must be installed according to  
recommended good practice requirements and current  
National Fuel Gas Code or CSA B149 standards.  
Dampers  
(open during cooling  
operation only)  
Dampers  
(open during heating  
operation only)  
FIGURE 3  
Note: Furnace must be adjusted to obtain a temperature  
rise within the range specified on the unit nameplate. Failure  
to do so may cause erratic limit operation and premature  
heat exchanger failure.  
NOTE: This furnace is designed for a minimum continuous  
return air temperature of 60°F (16°C) or an intermittent  
operation down to 55°F (13°C) dry bulb for cases where a  
night setback thermostat is used. Return air temperature  
must not exceed 85°F (29°C) dry bulb.  
This gas furnace must be installed so that its electrical  
components are protected from water.  
This gas furnace may be installed in alcoves, closets, attics,  
basements, garages, and utility rooms.  
Installed in Combination with a Cooling Coil  
When this furnace is used with cooling units (Figure 3), it  
shall be installed in parallel with, or on the upstream side of,  
cooling units to avoid condensation in the heating  
compartment. With a parallel flow arrangement, a damper  
(or other means to control the flow of air) must adequately  
prevent chilled air from entering the furnace. If the damper  
is manually operated, it must be equipped to prevent  
operation of either the heating or the cooling unit, unless it  
is in the full HEAT or COOL setting.  
This furnace design has NOT been CSA certified for  
installation in mobile homes, recreational vehicles, or  
outdoors.  
Never use an open flame to test for gas leaks. Check all  
connections using a commercially available soap solution  
made specifically for leak detection.  
Use of Furnace as Construction Heater  
These units are not recommended for use as a construction  
heater during any phase of construction. Very low return air  
temperature, harmful vapors and operation of the unit with  
clogged or misplaced filters will damage the unit.  
When installed, this furnace must be electrically grounded  
according to local codes. In addition, in the United States,  
installation must conform with the current National Electric  
Code, ANSI/NFPANo. 70. The National Electric Code (ANSI/  
NFPA No. 70) is available from the following address:  
These units may be used for heating of buildings or structures  
under construction, if the following conditions are met:  
National Fire Protection Association  
1 Battery March Park  
Quincy, MA 02269  
The vent system must be permanently installed per these  
installation instructions.  
Aroom thermostat must control the furnace. The use of  
fixed jumpers that will provide continuous heating is not  
allowed.  
The return air duct must be provided and sealed to the  
furnace.  
Return air temperature range between 60°F (16°C) and  
80°F (27°C) must be maintained.  
Air filters must be installed in the system and must be  
maintained during construction.  
In Canada, all electrical wiring and grounding for the unit  
must be installed according to the current regulations of the  
Canadian Electrical Code Part I (CSAStandard C22.1) and/  
or local codes.  
506725-01  
Page 5 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Air filters must be replaced upon construction completion.  
The input rate and temperature rise must be set per the  
furnace rating plate.  
WARNING  
One hundred percent (100%) outdoor air must be provided  
for combustion air requirements during construction.  
Temporary ducting may supply outdoor air to the furnace.  
Do not connect duct directly to the furnace. Size the  
temporary duct following the instructions in section for  
Combustion, Dilution and Ventilation Air in a confined  
space with air from outside.  
Product Contains Fiberglass Wool.  
Disturbing the insulation in this product during  
installation, maintenance, or repair will expose you to  
fiberglass wool. Breathing this may cause lung cancer.  
(Fiberglass wool is known to the State of California to  
cause cancer.)  
The furnace heat exchanger, components, duct system,  
air filters and evaporator coils must be thoroughly  
cleaned following final construction cleanup.  
All furnace operating conditions (including ignition, input  
rate, temperature rise and venting) must be verified  
according to these installation instructions.  
Fiberglass wool may also cause respiratory, skin, and  
eye irritation.  
To reduce exposure to this substance or for further  
information, consult material safety data sheets available  
from address shown below, or contact your supervisor.  
Allied Air Enterprises, Inc.  
215 Metropolitan Drive  
West Columbia, SC 29170  
General  
These instructions are intended as a general guide and do  
not supersede local codes in any way. Consult authorities  
having jurisdiction before installation.  
Combustion, Dilution & Ventilation Air  
If this unit is installed as a Non-Direct Vent Furnace,  
follow the guidelines in this section.  
In addition to the requirements outlined previously, the  
following general recommendations must be considered  
when installing one of these furnaces:  
NOTE: In Non-Direct Vent Installations, combustion air is  
taken from indoors and flue gases are discharged outdoors.  
Place the furnace as close to the center of the air  
distribution system as possible. The furnace should also  
be located close to the vent termination point.  
When the furnace is installed in non-direct vent  
applications, do not install the furnace where drafts might  
blow directly into it. This could cause improper  
combustion and unsafe operation.  
When the furnace is installed in a non-direct vent  
applications, do not block the furnace combustion air  
opening with clothing, boxes, doors, etc. Air is needed  
for proper combustion and safe unit operation.  
When the furnace is installed in an attic or other insulated  
space, keep insulation away from the furnace.  
When the furnace is installed in an unconditioned space,  
consider provisions required to prevent freezing of the  
condensate drain system.  
WARNING  
Insufficient combustion air can cause headaches,  
nausea, dizziness or asphyxiation. It will also cause  
excess water in the heat exchanger resulting in rusting  
and premature heat exchanger failure. Excessive  
exposure to contaminated combustion air will result in  
safety and performance related problems. Avoid  
exposure to the following substances in the combustion  
air supply:  
Permanent wave solutions  
Chlorinated waxes and cleaners  
Chlorine base swimming pool chemicals  
Water softening chemicals  
De-icing salts or chemicals  
Carbon tetrachloride  
Halogen type refrigerants  
NOTE: The Commonwealth of Massachusetts stipulates  
Cleaning solvents (such as perchloroethylene)  
Printing inks, paint removers, varnishes, etc.  
Hydrochloric acid  
Cements and glues  
Antistatic fabric softeners for clothes dryers  
Masonry acid washing materials  
these additional requirements:  
Gas furnaces shall be installed by a licensed plumber  
or fitter only.  
The gas cock must be “T handle” type.  
When a furnace is installed in an attic, the passageway  
to and service area surrounding the equipment shall be  
floored.  
In the past, there was no problem in bringing in sufficient  
outdoor air for combustion. Infiltration provided all the air  
that was needed. In today’s homes, tight construction  
practices make it necessary to bring in air from outside for  
combustion. Take into account that exhaust fans, appliance  
vents, chimneys, and fireplaces force additional air that could  
be used for combustion out of the house. Unless outside  
CAUTION  
These units should not be installed in areas normally  
subject to freezing temperatures.  
Page 6 of 48  
Issue 1109  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
air is brought into the house for combustion, negative  
pressure (outside pressure is greater than inside pressure)  
will build to the point that a down draft can occur in the furnace  
vent pipe or chimney. As a result, combustion gases enter  
the living space creating a potentially dangerous situation.  
infiltration. If the furnace is located in a building of tight  
construction with weather stripping and caulking around the  
windows and doors, follow the procedures in the “Air from  
Outside” section.  
Confined Space  
In the absence of local codes concerning air for combustion  
and ventilation, use the guidelines and procedures in this  
section to install these furnaces to ensure efficient and safe  
operation. You must consider combustion air needs and  
requirements for exhaust vents and gas piping. Aportion of  
this information has been reprinted with permission from  
the National Fuel Gas Code (ANSI-Z223.1/NFPA 54). This  
reprinted material is not the complete and official position of  
ANSI on the referenced subject, which is represented only  
by the standard in its entirely.  
A confined space is an area with a volume less than 50  
cubic feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the  
combined input rating of all appliances installed in that space.  
This definition includes furnace closets or small equipment  
rooms.  
When the furnace is installed so that supply ducts carry air  
circulated by the furnace to areas outside the space  
containing the furnace, the return air must be handled by  
ducts which are sealed to the furnace casing and which  
terminate outside the space containing the furnace. This is  
especially important when the furnace is mounted on a  
platform in a confined space such as a closet or small  
equipment room. Even a small leak around the base of the  
unit at the platform or at the return air duct connection can  
cause a potentially dangerous negative pressure condition.  
Air for combustion and ventilation can be brought into the  
confined space either from inside the building or from outside.  
In Canada, refer to the CSA B149 Installation codes.  
CAUTION  
Do not install the furnace in a corrosive or contaminated  
atmosphere. Meet all combustion and ventilation air  
requirements, as well as all local codes.  
Air from Inside  
If the confined space that houses the furnace adjoins a space  
categorized as unconfined, air can be brought in by providing  
two permanent openings between the two spaces. Each  
opening must have a minimum free area of 1 square inch  
(645 mm²) per 1,000 Btu (.29 kW) per hour of total input  
rating of all gas-fired equipment in the confined space. Each  
opening must be at least 100 square inches (64516 mm²).  
One opening shall be within 12 inches (305 mm) of the top  
of the enclosure and one opening within 12 inches (305 mm)  
of the bottom. See Figure 4.  
All gas-fired appliances require air for the combustion  
process. If sufficient combustion air is not available, the  
furnace or other appliance will operate inefficiently and  
unsafely. Enough air must be provided to meet the needs  
of all fuel-burning appliances and appliances such as exhaust  
fans which force air out of the house. When fireplaces,  
exhaust fans, or clothes dryers are used at the same time  
as the furnace, much more air is required to ensure proper  
combustion and to prevent a down draft. Insufficient air  
causes incomplete combustion which can result in carbon  
monoxide.  
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM INSIDE  
In addition to providing combustion air, fresh outdoor air  
dilutes contaminants in the indoor air. These contaminants  
may include bleaches, adhesives, detergents, solvents and  
other contaminants which can corrode furnace components.  
ROOF TERMINATED  
EXHAUST PIPE  
The requirements for providing air for combustion and  
ventilation depend largely on whether the furnace is installed  
in an unconfined or a confined space.  
OPENINGS  
(To Adjacent  
Unconfined  
Space)  
Unconfined Space  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
FURNACE  
An unconfined space is an area such as a basement or  
large equipment room with a volume greater than 50 cubic  
feet (1.42 m³) per 1,000 Btu (.29 kW) per hour of the  
combined input rating of all appliances installed in that space.  
This space also includes adjacent rooms which are not  
separated by a door. Though an area may appear to be  
unconfined, it might be necessary to bring in outdoor air for  
combustion if the structure does not provide enough air by  
NOTE− Each opening shall have a free area of at least one square inch  
2
per 1,000 Btu (645 mm per .29 kW) per hour of the total input rating of  
all equipment in the enclosure, but not less than 100 square inches  
2
(64516 mm ).  
FIGURE 4  
506725-01  
Page 7 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
to 25 percent free area and metal louvers and grilles will  
have 60 to 75 percent free area. Louvers and grilles must  
be fixed in the open position or interlocked with the equipment  
so that they are opened automatically during equipment  
operation.  
Air from Outside  
If air from outside is brought in for combustion and ventilation,  
the confined space shall be provided with two permanent  
openings. One opening shall be within 12” (305 mm) of the  
top of the enclosure and one within 12” (305 mm) of the  
bottom. These openings must communicate directly or by  
ducts with the outdoors or spaces (crawl or attic) that freely  
communicate with the outdoors or indirectly through vertical  
ducts. Each opening shall have a minimum free area of 1  
square inch per 4,000 Btu (645 mm² per .59 kW) per total  
input rating of all equipment in the enclosure (See Figure 5).  
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE  
(All Air Through Ventilated Attic)  
ROOF TERMINATED  
EXHAUST PIPE  
VENTILATION LOUVERS  
(Each end of attic)  
EQUIPMENT IN CONFINED SPACE − ALL AIR FROM OUTSIDE  
(Inlet Air from Crawl Space and Outlet Air to Ventilated Attic)  
OUTLET  
AIR  
VENTILATION LOUVERS  
(Each end of attic)  
ROOF TERMINATED  
EXHAUST PIPE  
INLET AIR  
(Ends 12" above  
bottom)  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
FURNACE  
OUTLET  
AIR  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
FURNACE  
NOTE−The inlet and outlet air openings shall each have a free area of  
2
VENTILATION  
LOUVERS  
(For unheated  
crawl space)  
at least one square inch per 4,000 Btu (645 mm per 1.17 kW) per hour  
INLET  
AIR  
of the total input rating of all equipment in the enclosure.  
FIGURE 6  
NOTE−The inlet and outlet air openings shall each have a free area  
2
of at least one square inch per 4,000 Btu (645 mm per 1.17 kW) per  
hour of the total input rating of all equipment in the enclosure.  
FIGURE 5  
If air from outside is brought in for combustion and ventilation,  
the confined space must have two permanent openings. One  
opening shall be within 12 inches (305 mm) of the top of the  
enclosure and one opening within 12 inches (305 mm) of  
the bottom. These openings must communicate directly or  
by ducts with the outdoors or spaces (crawl or attic) that  
freely communicate with the outdoors or indirectly through  
vertical ducts. Each opening shall have a minimum free  
area of 1 square inch (645 mm²) per 4,000 Btu (1.17 kW)  
per hour of total input rating of all equipment in the enclosure.  
See figures 5 and 6. When communicating with the outdoors  
through horizontal ducts, each opening shall have a minimum  
free area of 1 square inch (645 mm²) per 2,000 Btu (.56  
kW) per total input rating of all equipment in the enclosure.  
See Figure 7.  
EQUIPMENT IN CONFINED SPACE −  
ALL AIR FROM OUTSIDE  
ROOF TERMINATED  
EXHAUST PIPE  
OUTLET AIR  
FURNACE  
SIDE WALL  
TERMINATED  
EXHAUST PIPE  
(ALTERNATE  
LOCATION)  
INLET AIR  
When ducts are used, they shall be of the same cross-  
sectional area as the free area of the openings to which  
they connect. The minimum dimension of rectangular air  
ducts shall be no less than 3 inches (75 mm). In calculating  
free area, the blocking effect of louvers, grilles, or screens  
must be considered. If the design and free area of protective  
covering is not known for calculating the size opening  
required, it may be assumed that wood louvers will have 20  
NOTE−Each air duct opening shall have a free area of at least one  
2
square inch per 2,000 Btu (645 mm per .59 kW) per hour of the total  
input rating of all equipment in the enclosure. If the equipment room  
is located against an outside wall and the air openings communi-  
cate directly with the outdoors, each opening shall have a free area  
2
of at least 1 square inch per 4,000 Btu (645 mm per 1.17 kW) per  
hour of the total input rating of all other equipment in the enclosure.  
FIGURE 7  
Page 8 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
INSTALLATION – Setting Equipment  
NOTE: These units may be equipped with a shipping pad  
under the blower housing. Remove the shipping pad prior  
to operation.  
WARNING  
Do not install the furnace on its front, back or in the  
horizontal position. See Figure 10. Do no connect the  
return air ducts to the back of the furnace. Doing so will  
adversely affect the operation of the safety control  
devices, which could result in personal injury or death.  
Allow for clearances to combustible materials as indicated  
on the unit nameplate. Minimum clearances for closet or  
alcove installations are shown in Figure 11.  
Select a location that allows for the required clearances that  
are listed on the unit nameplate. Also consider gas supply  
connections, electrical supply, vent connection, condensate  
trap and drain connections, and installation and service  
clearances [24 inches (610 mm) at unit front]. The unit must  
be level from side to side. Tilt the unit slightly (maximum  
1/2 in. from level) from back to front to aid in the draining of  
the heat exchanger. See Figure 9.  
WARNING  
Blower access panel must be securely in place when  
blower and burners are operating. Gas fumes, which  
could contain carbon monoxide, can be drawn into living  
space resulting in personal injury or death.  
Shipping Bolt Removal  
SETTING EQUIPMENT  
NOTE: Units with a 1/2 hp blower motors are equipped with  
three flexible legs and one rigid leg. The rigid leg is equipped  
with a shipping bolt and a flat white plastic washer (rather  
than the rubber mounting grommet used with a flexible  
mounting leg). See Figure 8. The bolt and washer must  
be removed before the furnace is placed into operation.  
After the bolt and washer have been removed, the rigid leg  
will not touch the blower housing.  
AIR FLOW  
AIR FLOW  
AIR FLOW  
UNITS WITH 1/2 HP BLOWER MOTOR  
1/2"  
max.  
RIGID LEG  
(remove shipping bolt and washer)  
FRONT VIEW  
SIDE VIEW  
SIDE VIEW  
Unit must be level side−to−side. Unit may be positioned  
from level to 1/2" toward the front to aid in draining.  
FIGURE 9  
FIGURE 8  
Figure 10  
506725-01  
Page 9 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Installation on Non-Combustible Flooring (Figure 12)  
1. Cut floor opening keeping in mind clearances listed on  
unit rating plate. Also keep in mind gas supply  
connections, electrical supply, flue and air intake  
connections and sufficient installation and servicing  
clearances. See Table 1 for correct floor opening size.  
2. Flange warm air plenum and lower the plenum into the  
opening.  
WARNING  
Improper installation of the furnace can result in personal  
injury or death. Combustion and flue products must  
never be allowed to enter the return air system or air in  
the living space. Use sheet metal screws and joint tape  
to seal return air system to furnace.  
3. Set the unit over the plenum and seal the plenum to the  
unit.  
4. Ensure that the seal is adequate.  
In platform installations with furnace return, the furnace  
should be sealed airtight to the return air plenum. A  
door must never be used as a portion of the return air  
duct system. The base must provide a stable support  
and an airtight seal to the furnace. Allow absolutely no  
sagging, cracks, gaps, etc.  
NON−COMBUSTIBLE FLOOR OPENING SIZE  
Front to Rear  
Side to Side  
For no reason should return and supply air duct systems  
ever be connected to or from other heating devices such  
as a fireplace or stove, etc. Fire, explosion, carbon  
monoxide poisoning, personal injury and/or property  
damage could result.  
Cabinet Width  
in.  
mm  
in.  
mm  
422  
511  
B Cabinet (17.5")  
C Cabinet (21")  
19 − 3/4  
19 − 3/4  
502  
502  
16 − 5/8  
20−1/8  
NOTE: Floor opening dimensions listed are 1/4 inch (6 mm) larger than  
the unit opening. See dimension drawing on page 2.  
The unit may be installed three ways in downflow applica-  
tions: on non-combustible flooring, on combustible flooring  
using an additive base, or on a reverse-flow cooling coil  
cabinet. Do not drag the unit across the floor in the  
downflow position. Floor and furnace flange damage  
will result.  
TABLE 1  
Refer to Figure 11 for clearances in downflow applica-  
tions.  
FURNACE  
Downflow Application Installation Clearances  
Top  
PROPERLY  
SIZED FLOOR  
OPENING  
SUPPLY AIR  
PLENUM  
Left Side  
Right Side  
FIGURE 12  
Bottom  
Installation on Combustible Flooring (Figure 13)  
1. When unit is installed on a combustible floor, a downflow  
combustible flooring base must be installed between the  
furnace and the floor. The base must be ordered  
separately. See Table 2 for opening size to cut in floor.  
Top  
*Front  
Back  
0
0
0
Sides  
Vent  
0†  
0
CAUTION  
Floor  
NC ‡  
The furnace and combustible flooring base shall not be  
installed directly on carpeting, tile, or other combustible  
material other than wood flooring.  
*Front clearance in alcove installation must be 24 in. (610 mm).  
Maintain a minimum of 24 in. (610 mm) for front service access.  
†Allow proper clearances to accommodate condensate trap.  
The furnace may be installed on a combustible wood floor if an optional  
additive base is installed between the furnace and the combustible floor.  
FIGURE 11  
Page 10 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
COMBUSTIBLE FLOORING BASE OPENING SIZE  
Front to Rear  
Side to Side  
Cabinet  
Width  
Catalog  
Number  
in.  
22  
mm  
559  
in.  
mm  
FURNACE  
B Cabinet  
(17.5")  
11M60  
11M61  
18 − 3/4  
476  
578  
C Cabinet  
(21")  
22  
559  
22 − 3/4  
COOLING COIL  
PLENUM  
TABLE 2  
PROPERLY  
SIZED FLOOR  
OPENING  
FURNACE  
SUPPLY AIR  
PLENUM  
PROPERLY  
SIZED FLOOR  
OPENING  
COMBUSTIBLE  
FLOORING BASE  
FIGURE 14  
Return Air Opening - Downflow Units  
Return air may be brought in only through the top opening  
of a furnace installed in the downflow position. The following  
steps should be taken when installing plenum:  
1. Bottom edge of plenum should be flanged with a  
hemmed edge (See Figure 15 or 16).  
2. Sealing strips should be used to ensure an airtight seal  
between the cabinet and the plenum.  
3. In all cases, plenum should be secured to top of furnace  
using sheet metal screws.  
4. Make certain that an adequate seal is made.  
FIGURE 13  
2. After opening is cut, set the combustible flooring base  
into opening.  
3. Check fiberglass strips on the combustible flooring base  
to make sure they are properly glued and positioned.  
4. Lower supply air plenum into the combustible flooring  
base until plenum flanges seal against fiberglass strips.  
er opening is  
PLENUM  
(Field Provided)  
NOTE: Be careful not to damage fiberglass strips. Check  
for a tight seal.  
SECURE FROM  
OUTSIDE CABINET  
5. Set the furnace over the plenum.  
6. Ensure that the seal between the furnace and plenum  
is adequate.  
CABINET  
SEALING STRIP  
SIDE PANEL  
(Field Provided)  
Side View  
Installation on Cooling Coil Cabinet (Figure 14)  
FIGURE 15  
NOTE: Downflow combustible flooring kit is not used.  
PLENUM  
(Field Provided)  
SEALING STRIP  
1. Refer to reverse-flow coil installation instructions for  
correctly sized opening in floor and installation of  
cabinet.  
(Field Provided)  
2. When cooling cabinet is in place, set and secure the  
furnace according to the instructions that are provided  
with the cooling coil. Secure the furnace to the cabinet.  
3. Seal the cabinet and check for air leaks.  
CABINET  
SIDE PANEL  
SECURE FROM  
INSIDE CABINET  
Side View  
FIGURE 16  
506725-01  
Page 11 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Filters  
Pipe & Fittings Specifications  
This unit is not equipped with a filter or rack. Afield provided  
filter is required for the unit to operate properly. Table 3 lists  
recommended filter sizes.  
All pipe, fittings, primer and solvent cement must conform  
withAmerican National Standard Institute and theAmerican  
Society for Testing and Materials (ANSI/ASTM) standards.  
The solvent shall be free flowing and contain no lumps,  
undissolved particles or any foreign matter that adversely  
affects the joint strength or chemical resistance of the  
cement. The cement shall show no gelation, stratification,  
or separation that cannot be removed by stirring. Refer to  
Table 4 below for approved piping and fitting materials.  
A filter must be in place whenever the unit is operating.  
Furnace  
Filter Size  
Cabinet Width  
17−1/2"  
21"  
16 x 25 x 1 (1)  
TABLE 3  
CAUTION  
Duct System  
Use industry-approved standards to size and install the  
supply and return air duct system. This will result in a quiet  
and low-static system that has uniform air distribution.  
Solvent cements for plastic pipe are flammable liquids  
and should be kept away from all sources of ignition.  
Do not use excessive amounts of solvent cement when  
making joints. Good ventilation should be maintained  
to reduce fire hazard and to minimize breathing of  
solvent vapors. Avoid contact of cement with skin and  
eyes.  
NOTE: This furnace is not certified for operation in heating  
mode (indoor blower operating at selected heating speed)  
with an external static pressure which exceeds 0.5 inches  
w.c. Operation at these conditions may result in improper  
limit operation.  
Supply Air Plenum  
PIPING AND FITTINGS SPECIFICATIONS  
If the fumace is installed without a cooling coil, a removable  
access panel should be installed in the supply air duct. The  
access panel should be large enough to permit inspection  
(by reflected light) of the heat exchanger for leaks after the  
furnace is installed. The furnace access panel must always  
be in place when the furnace is operating and it must not  
allow leaks into the supply air duct system.  
Schedule 40 PVC (Pipe)  
D1785  
F891  
Schedule 40 PVC (Cellular Core Pipe)  
Schedule 40 PVC (Fittings)  
D2466  
F441  
Schedule 40 CPVC (Pipe)  
Schedule 40 CPVC (Fittings)  
SDR−21 PVC or SDR−26 PVC (Pipe)  
SDR−21 CPVC or SDR−26 CPVC (Pipe)  
Schedule 40 ABS Cellular Core DWV (Pipe)  
Schedule 40 ABS (Pipe)  
F438  
D2241  
F442  
F628  
Return Air Plenum  
D1527  
D2468  
Schedule 40 ABS (Fittings)  
NOTE: Return air must not be drawn from a room where  
this furnace, or any other gas-fueled appliance (i.e.,  
water heater), or carbon monoxide-producing device  
(i.e., wood fireplace) is installed.  
ABS−DWV (Drain Waste & Vent)  
(Pipe & Fittings)  
D2661  
D2665  
PVC−DWV (Drain Waste & Vent)  
Pipe & Fittings)  
ASTM  
SPECIFICATION  
PRIMER & SOLVENT CEMENT  
When return air is drawn from a room, a negative pressure  
is created in the room. If a gas appliance is operating in a  
room with negative pressure, the flue products can be pulled  
back down the vent pipe and into the room. This reverse  
flow of the flue gas may result in incomplete combustion  
and the formation of carbon monoxide gas. This toxic gas  
might then be distributed throughout the house by the furnace  
duct system.  
PVC & CPVC Primer  
PVC Solvent Cement  
CPVC Solvent Cement  
ABS Solvent Cement  
F656  
D2564  
F493  
D2235  
PVC/CPVC/ABS All Purpose Cement For  
Fittings & Pipe of the same material  
D2564, D2235, F493  
D3138  
ABS to PVC or CPVC Transition Solvent  
Cement  
CANADA PIPE & FITTING & SOLVENT  
CEMENT  
Use fiberglass sealing strips, caulking, or equivalent sealing  
method between the plenum and the furnace cabinet to  
ensure a tight seal. If a filter is installed, size the return air  
duct to fit the filter frame.  
MARKING  
PVC & CPVC Pipe and Fittings  
PVC & CPVC Solvent Cement  
ULCS636  
ABS to PVC or CPVC Transition Cement  
TABLE 4  
Page 12 of 48  
Issue 1109  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
vent pipe hangers. Uniformly apply a liberal coat of PVC  
primer for PVC or use a clean dry cloth for ABS to clean  
inside socket surface of fitting and male end of pipe to depth  
of fitting socket.  
IMPORTANT  
The exhaust and intake connections are made of PVC.  
Use PVC primer and solvent cement when using PVC  
vent pipe. When using ABS vent pipe, use transitional  
solvent cement to make connections to the PVC fitting in  
the unit.  
Canadian Applications Only  
Pipe, fittings, primer and solvent cement used to vent  
(exhaust) this appliance must be certified to ULC S636 and  
supplied by a single manufacturer as part of an approved  
vent (exhaust) system. When bonding the vent system to  
the furnace, use ULC S636 approved One-Step Transition  
Cement to bond the pipe to the flue collar. In addition, the  
first three feet of vent pipe from the furnace flue collar must  
be accessible for inspection.  
Use PVC primer and solvent cement orABS solvent cement  
meeting ASTM specifications, refer to Table 4. As an  
alternate, use all purpose cement, to bond ABS, PVC, or  
CPVC pipe when using fittings and pipe made of the same  
materials. Use transition solvent cement when bondingABS  
to either PVC or CPVC.  
Table 5 Lists the available exhaust termination kits. All vent  
terminations are PVC.  
Low temperature solvent cement is recommended during  
cooler weather. Metal or plastic strapping may be used as  
OUTDOOR TERMINATION KITS USAGE  
STANDARD  
CONCENTRIC  
Outdoor  
Exhaust  
Accelerator  
(Dia. X  
Length)  
Outdoor  
Flush-  
Mount  
Kit  
1−1/2"  
2"  
3"  
Concentric Concentric Concentric  
Exhaust  
Accelerator  
(Dia. X  
VENT  
PIPE  
DIA.  
(in.)  
A95DF  
A93DF  
95G1DF  
92G1DF  
Kit  
Kit  
Kit  
Length)  
60L46  
or  
44W93  
71M80  
or  
44W92  
69M29  
or  
44W92  
1−1/2" X 12"  
2" X 12"  
51W11**  
2
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
2−1/2  
045  
3
2
2−1/2  
070  
090  
110  
3
2
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
YES  
2−1/2  
3
2
2−1/2  
3
*Requires field−provided and installed 1−1/2" exhaust accelerator.  
** Kit 51W11 is provided with a 1−1/2" accelerator which must be used for all 45,000 and 70,000 furnace installations.  
†† The 44W92 Concentric kit is provided with a 1-1/2” accelerator which must be installed on the exhaust outlet when  
this kit is used with the 45,000 and 70,000 furnaces.  
TABLE 5  
506725-01  
Page 13 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Joint Cementing Procedure  
All cementing of joints should be done according to the  
specifications outlined in ASTM D 2855.  
Venting Practices  
Piping Suspension Guidelines  
NOTE: A sheet metal screw may be used to secure the  
intake pipe to the connector, if desired. Use a drill or self  
tapping screw to make a pilot hole.  
SCHEDULE 40  
PVC − 5’  
all other pipe* − 3’  
DANGER  
* See Table 4 for allowable pipe.  
DANGER OF EXPLOSION!  
NOTE: Isolate piping at the point where it exits the outside wall or  
roof in order to prevent transmission of vibration to the structure.  
Fumes from PVC glue may ignite during system check.  
Allow fumes to dissipate for at least 5 minutes before  
placing unit into operation.  
Wall Thickness Guidelines  
24" maximum  
3/4" minimum  
1. Measure and cut vent pipe to desired length.  
2. Debur and chamfer end of pipe, removing any ridges or  
rough edges. If end is not chamfered, edge of pipe  
may remove cement from fitting socket and result in a  
leaking joint.  
Wall  
inside  
outside  
3. Clean and dry surfaces to be joined.  
4. Test fit joint and mark depth of fitting on outside of pipe.  
5. Uniformly apply a liberal coat of PVC primer for PVC or  
use a clean dry cloth for ABS to clean inside socket  
surface of fitting and male end of pipe to depth of fitting  
socket.  
6. Promptly apply solvent cement to end of pipe and inside  
socket surface of fitting. Cement should be applied  
lightly but uniformly to inside of socket. Take care to  
keep excess cement out of socket. Apply second coat  
to end of pipe.  
insulation  
(if required)  
FIGURE 17  
REPLACING FURNACE THAT  
WAS PART OF A COMMON  
VENT SYSTEM  
CHIMNEY  
OR GAS  
VENT  
(Check sizing  
for remaining  
appliance)  
NOTE: Time is critical at this stage. Do Not allow Primer to  
dry before applying cement.  
7. Immediately after applying last coat of cement to pipe,  
and while both inside socket surface and end of pipe  
are wet with cement, forcefully insert end of pipe into  
socket until it bottoms out. Turn PVC pipe 1/4 turn during  
assembly (but not after pipe is fully inserted) to distribute  
cement evenly. Do not turn ABS or cellular core pipe.  
FURNACE  
WATER  
HEATER  
(Removed from  
from common  
vent system)  
OPENINGS  
(To Adjacent  
Room)  
NOTE: Assembly should be completed within 20 seconds  
after last application of cement. Hammer blows should not  
be used when inserting pipe.  
If this gas furnace replaces a furnace which was  
commonly vented with another gas appliance,  
the size of the existing vent pipe for that gas ap-  
pliance must be checked. Without the heat of the  
original furnace flue products, the existing vent pipe  
is probably oversized for the single water heater or  
other appliance. The vent should be checked for  
proper draw with the remaining appliance.  
8. After assembly, wipe excess cement from pipe at end  
of fitting socket. A properly made join will show a bead  
around its entire perimeter. Any gaps may indicate an  
improper defective assembly due to insufficient solvent.  
9. Handle joints carefully until completely set.  
FIGURE 18  
Page 14 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
1. In areas where piping penetrates joist or interior walls,  
hole must be large enough to allow clearance on all  
sides of pipe through center of hole using a hanger.  
2. When furnace is installed in a residence where unit is  
shut down for an extended period of time, such as a  
vacation home, make provisions for draining condensate  
collection trap and lines.  
Use the following steps to correctly size vent pipe diameter.  
045, 070,  
090, 110  
1
Furnace capacity?  
Exhaust Piping (Figure 20)  
Route piping to outside of structure. Continue with  
installation following instructions given in piping termination  
section.  
Standard or  
Concentric?  
See Table 5  
Which termination?  
2
CAUTION  
Do not discharge exhaust into an existing stack or stack  
that also serves another gas appliance. If vertical  
discharge through an existing unused stack is required,  
insert PVC pipe inside the stack until the end is even  
with the top or outlet end of the metal stack.  
Which needs  
most elbows?  
Intake or  
exhaust  
3
CAUTION  
The exhaust vent pipe operates under positive pressure  
and must be completely sealed to prevent leakage of  
combustion products into the living space.  
How many?  
4
5
Vent Piping Guidelines  
2", 2 1/2"  
or 3"  
Desired pipe size?  
This gas furnace can be installed as either a Non-Direct  
Vent or a Direct Vent gas central furnace.  
NOTE: In non-Direct Vent installations, combustion air is  
taken from indoors and flue gases are discharged outdoors.  
In Direct Vent installations, combustion air is taken from  
outdoors and flue gases are discharged outdoors.  
6
7
What is the altitude?  
Intake and exhaust pipe sizing - Size pipe according toTables  
6 and 7. Table 6 lists the minimum vent pipe lengths  
permitted. Table 7 lists the maximum pipe lengths permitted.  
Use Table 7 to find  
max intake or exhaust  
pipe length.  
Regardless of the diameter of pipe used, the standard roof  
and wall terminations described in section Exhaust Piping  
Terminations should be used. Exhaust vent termination pipe  
is sized to optimize the velocity of the exhaust gas as it exits  
the termination.  
FIGURE 19  
In some applications which permit the use of several different  
sizes of vent pipe, a combination vent pipe may be used.  
Contact Allied Air Technical Service for assistance in sizing  
vent pipe in these applications.  
MINIMUM VENT PIPE LENGTHS  
IMPORTANT  
A95DF, 95G1DF, A93DF, & 92G1DF  
MIN. VENT LENGTH*  
MODELS  
Do not use screens or perforated metal in exhaust or  
intake terminations. Doing so will cause freeze-ups and  
may block the terminations.  
15 ft. or  
5 ft plus 2 elbows or  
10 ft plus 1 elbow  
045, 070, 090, 110  
*Any approved termination may be added to the minimum length listed.  
TABLE 6  
506725-01  
Page 15 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
A95DF / 95G1DF and A93DF / 92G1DF  
Maximum Allowable Intake or Exhaust Vent Length in Feet  
*Size intake and exhaust pipe length separately. Values in table are for Intake OR Exhaust, not combined total.  
Both Intake and Exhaust must be same pipe size.  
Standard Termination at Elevation 0 − 10,000 ft.  
2" Pipe  
Model  
2−1/2" Pipe  
Model  
3" Pipe  
Model  
Number  
Of 90°  
Elbows  
Used  
045  
61  
56  
51  
46  
41  
36  
31  
26  
21  
16  
070  
46  
41  
36  
31  
26  
21  
16  
11  
090  
24  
110  
045  
100  
95  
90  
85  
80  
75  
70  
65  
60  
55  
070  
090  
110  
045  
127  
122  
117  
112  
107  
102  
97  
070  
127  
122  
117  
112  
107  
102  
97  
090  
108  
103  
98  
110  
108  
103  
98  
1
2
80  
75  
70  
65  
60  
55  
50  
45  
40  
35  
43  
38  
33  
28  
23  
18  
13  
19  
3
14  
4
93  
93  
5
88  
88  
n/a  
n/a  
6
83  
83  
7
78  
78  
n/a  
8
92  
92  
73  
73  
9
87  
87  
68  
68  
n/a  
n/a  
10  
82  
82  
63  
63  
Concentric Termination Elevation 0 − 10,000 ft.  
2" Pipe  
Model  
2−1/2" Pipe  
Model  
3" Pipe  
Model  
Number  
Of 90°  
Elbows  
Used  
045  
53  
48  
43  
38  
33  
28  
23  
18  
13  
n/a  
070  
38  
33  
28  
23  
18  
13  
090  
22  
110  
045  
90  
85  
80  
75  
70  
65  
60  
55  
50  
45  
070  
70  
65  
60  
55  
50  
45  
40  
35  
30  
25  
090  
39  
34  
29  
24  
19  
14  
110  
045  
111  
106  
101  
96  
070  
111  
106  
101  
96  
090  
104  
99  
94  
89  
84  
79  
74  
69  
64  
59  
110  
104  
99  
94  
89  
84  
79  
74  
69  
64  
59  
1
2
17  
3
12  
4
5
91  
91  
n/a  
n/a  
6
86  
86  
7
81  
81  
n/a  
8
76  
76  
n/a  
n/a  
9
71  
71  
10  
66  
66  
TABLE 7  
Page 16 of 48  
Issue 1109  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL EXHAUST PIPE CONNECTIONS  
Pipe size determined in Table 7.  
2”  
2”  
2”  
2”  
2”  
or  
3”  
TRANSITION  
*2”  
INTAKE  
EXHAUST  
DO NOT transition from smaller  
to larger pipe size in horizontal  
runs of exhaust pipe.  
TOP VIEW  
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.  
NOTE: Exhaust pipe and intake pipe must be the same diameter.  
FIGURE 20  
TYPICAL INTAKE PIPE CONNECTIONS (DIRECT VENT APPLICATIONS)  
2”  
2”  
Pipe size determined in Table 7.  
2”  
2”  
2”  
or  
TRANSITION  
3”  
3”  
*2”  
*2”  
TRANSITION  
*2”  
INTAKE  
EXHAUST  
TOP VIEW  
* When transitioning up in pipe size, use the shortest length of 2” PVC pipe possible.  
NOTE: Intake pipe and exhaust pipe must be the same diameter.  
FIGURE 21  
506725-01  
Page 17 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Intake Piping  
General Guidelines for Vent Terminations  
In Non-Direct Vent applications, combustion air is taken from  
indoors and the flue gases are discharged to the outdoors.  
This unit is then classified as a non-direct vent, Category IV  
gas furnace.  
This furnace may be installed in either direct vent or non-  
direct vent applications. In non-direct vent applications,  
when intake air will be drawn into the furnace from the  
surrounding space, the indoor air quality must be considered.  
Guidelines listed in Combustion, Dilution and VentilationAir  
section must be followed.  
In Direct Vent applications, combustion air is taken from  
outdoors and the flue gases are discharged to the outdoors.  
This unit is then classified as a direct vent, Category IV gas  
furnace.  
Follow the next two steps when installing the unit in Direct  
Vent applications, where combustion air is taken from  
outdoors and flue gases are discharged outdoors. The  
provided air intake screen must not be used in direct  
vent applications (outdoors).  
1. Use cement or a sheet metal screw to secure the intake  
pipe to the inlet air connector.  
2. Route piping to outside of structure. Continue with  
installation following instructions given in general guide  
lines for piping terminations and intake and exhaust  
piping terminations for direct vent sections. Refer to  
Table 7 for pipe sizes.  
In both Non-Direct Vent and Direct Vent applications, the  
vent termination is limited by local building codes. In the  
absence of local codes, refer to the current National Fuel  
Gas CodeANSI Z223-1/NFPA54 in U.S.A., and current CSA-  
B149 Natural Gas and Propane Installation Codes in Canada  
for details.  
Position termination according to location given in Figure 23  
or 24. In addition, position termination so it is free from any  
obstructions and 12" above the average snow accumulation.  
At vent termination, care must be taken to maintain protective  
coatings over building materials (prolonged exposure to  
exhaust condensate can destroy protective coatings). It is  
recommended that the exhaust outlet not be located within  
6 feet (1.8 m) of a condensing unit because the condensate  
can damage the painted coating.  
TYPICAL AIR INTAKE PIPE CONNECTIONS  
NON−DIRECT VENT APPLICATIONS  
AIR  
INTAKE  
SCREEN  
(Provided)  
NOTE: If winter design temperature is below 32° F (0° C), it is  
recommended that the exhaust piping be insulated with 1/2" (13  
mm), Armaflex or equivalent when run through an unconditioned  
area. In extremely cold climate areas with temperature below 20°  
F (6.7° C) it is recommended that 3/4" (19 mm) Armaflex or  
equivalent be used. Insulation on outside runs of exhaust pipe  
may be painted or wrapped to protect insulation from deterioration  
in accordance with the insulation manufacturers recommendation.  
Exhaust pipe insulation may not be necessary in some specific  
applications.  
NOTE: During extremely cold temperatures, below approximately  
20° F (6° C), units with long runs of vent pipe through unconditioned  
space, even when insulated, may form ice in the exhaust  
termination that prevents the unit from operating properly. Longer  
run times of at least 5 minutes will alleviate most icing problems.  
Also, a heating cable may be installed on exhaust piping and  
termination to prevent freeze-ups. Heating cable installation kits  
are available, see unit specification sheets for part numbers.  
NOTE: Air intake screen and elbow may be rotated, so that  
screen may be positioned to face forward or to either side.  
FIGURE 22  
Follow the next two steps when installing the unit in  
Non-Direct Vent applications where combustion air is  
taken from indoors and flue gases are discharged outdoors.  
1. Use field-provided materials and the factory-provided  
air intake screen to route the intake piping as shown in  
Figure 23. Maintain a minimum clearance of 3" (76 mm)  
around the air intake opening. The air intake opening  
(with the protective screen) should always be directed  
forward, or sideways.  
IMPORTANT  
Do not use screens or perforated metal in exhaust  
terminations. Doing so will cause freeze-ups and may  
block the terminations.  
IMPORTANT  
For Canadian Installations Only:  
In accordance to CSA International B149 installation  
codes, the minimum allowed distance between the  
combustion air intake inlet and the exhaust outlet of  
other appliances shall not be less than 12 inches (305  
mm).  
2. Use a sheet metal screw to secure the intake pipe to  
the connector, if desired.  
Page 18 of 48  
Issue 1109  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT TERMINATION CLEARANCES  
FOR NON−DIRECT VENT INSTALLATIONS IN THE USA AND CANADA  
INSIDE CORNER  
DETAIL  
G
H
A
D
E
B
L
B
B
B
I
C
B
Fixed  
Closed  
Operable  
Fixed  
M
Closed  
F
Operable  
K
J
A
AREA WHERE TERMINAL  
IS NOT PERMITTED  
AIR SUPPLY INLET  
US Installations  
VENT TERMINAL  
1
2
Canadian Installations  
A =  
Clearance above grade, veranda,  
porch, deck or balcony  
12 inches (305mm) or 12 in. 305mm)  
above average snow accumulation.  
12 inches (305mm) or 12 in. 305mm)  
above average snow accumulation.  
B =  
Clearance to window or  
door that may be opened  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
C =  
D =  
Clearance to permanently  
closed window  
* 12"  
* 12"  
Vertical clearance to ventilated soffit  
* Equal to or greater than soffit depth.  
* Equal to or greater than soffit depth.  
located above the terminal within a  
horizontal distance of 2 feet (mm)  
from the center line of the terminal  
* Equal to or greater than soffit depth.  
E =  
F =  
G =  
Clearance to unventilated soffit  
Clearance to outside corner  
* Equal to or greater than soffit depth.  
* No minimum to outside corner  
*
* No minimum to outside corner  
*
Clearance to inside corner  
H = Clearance to each side of center line ex-  
tended above meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
*
I =  
Clearance to service regulator  
vent outlet  
3 feet (.9m)  
* 3 feet (.9m)  
J =  
Clearance to non−mechanical air  
supply inlet to building or the com-  
bustion air inlet to any other ap-  
pliance  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
4 feet (1.2 m) below or to side of opening;  
1 foot (30 cm) above opening  
K =  
L =  
Clearance to mechanical air sup-  
ply inlet  
3 feet (.9m) above if within 10 feet  
(3m) horizontally  
6 feet (1.8m)  
Clearance above paved sidewalk or  
paved driveway located on public property  
M =  
Clearance under veranda, porch,  
deck or balcony  
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code  
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA B149.1,  
clearance will be in accordance with local installation codes and the re-  
quirements of the gas supplier and these installation instructions."  
2
In accordance with the current CSA B149.1, N  
atural Gas and Pr opane Inst allation Code  
between two single family dwellings and serves both dwellings.  
sides beneath the floor. Lennox recommends avoiding this location if possible.  
FIGURE 23  
506725-01  
Page 19 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
VENT TERMINATION CLEARANCES  
FOR DIRECT VENT INSTALLATIONS IN THE USA AND CANADA  
INSIDE CORNER  
DETAIL  
G
H
A
D
E
B
L
B
B
B
I
C
B
Fixed  
Closed  
Operable  
Fixed  
M
Closed  
F
Operable  
K
J
A
AREA WHERE TERMINAL  
IS NOT PERMITTED  
AIR SUPPLY INLET  
US Installations  
VENT TERMINAL  
1
2
Canadian Installations  
A =  
Clearance above grade, veranda,  
porch, deck or balcony  
12 inches (305mm) or 12 in. 305mm)  
above average snow accumulation.  
12 inches (305mm) or 12 in. 305mm)  
above average snow accumulation.  
B =  
Clearance to window or  
door that may be opened  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 9 inches (mm) for appliances  
> 10,000 Btuh (3kw) and <50,000 Btuh  
(15 kw), 12 inches (305mm) for ap-  
pliances > 50,000 Btuh (15kw)  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
* 12"  
C =  
D =  
Clearance to permanently  
closed window  
* 12"  
Vertical clearance to ventilated soffit  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
located above the terminal within a  
horizontal distance of 2 feet (mm)  
from the center line of the terminal  
* Equal to or greater than soffit depth  
* Equal to or greater than soffit depth  
E =  
F =  
G =  
Clearance to unventilated soffit  
Clearance to outside corner  
Clearance to inside corner  
* No minimum to outside corner  
*
* No minimum to outside corner  
*
H = Clearance to each side of center line ex-  
tended above meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
3 feet (.9m) within a height 15 feet (4.5m)  
above the meter / regulator assembly  
I =  
Clearance to service regulator  
vent outlet  
3 feet (.9m)  
* 3 feet (.9m)  
J =  
Clearance to non−mechanical air  
supply inlet to building or the com-  
bustion air inlet to any other ap-  
pliance  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 9 inches (mm) for appliances  
> 10,000 Btuh (3kw) and <50,000 Btuh  
(15 kw), 12 inches (305mm) for ap-  
pliances > 50,000 Btuh (15kw)  
6 inches (152mm) for appliances <10,000  
Btuh (3kw), 12 inches (305mm) for  
appliances > 10,000 Btuh (3kw) and  
<100,000 Btuh (30kw), 36 inches (.9m)  
for appliances > 100,000 Btuh (30kw)  
K =  
L =  
Clearance to mechanical air sup-  
ply inlet  
Clearance above paved sidewalk or  
paved driveway located on public property  
3 feet (.9m) above if within 10 feet  
(3m) horizontally  
6 feet (1.8m)  
* 7 feet (2.1m)  
M =  
Clearance under veranda, porch,  
deck or balcony  
1
In accordance with the current ANSI Z223.1/NFPA 54 Natural Fuel Gas Code  
*For clearances not specified in ANSI Z223.1/NFPA 54 or CSA  
B149.1, clear-  
ance will be in accordance with local installation c odes and the requirements  
of the gas supplier and these installation instructions."  
2
In accordance with the current CSA B149.1, Natura  
l Gas and Prop ane Installation Code  
between two single family dwellings and serves both dwellings.  
sides beneath the floor. Lennox recommends avoiding this location if possible.  
FIGURE 24  
Page 20 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
Details of Intake and Exhaust Piping Terminations for  
Direct Vent Installations  
DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
3"(76mm) MAX.  
SIZE TERMINATION  
PIPE PER TABLE 8.  
Inches(mm)  
NOTE: In Direct Vent installations, combustion air is taken  
from outdoors and flue gases are discharged to outdoors.  
UNCONDITIONED  
ATTIC SPACE  
8" (203mm) MIN  
NOTE: Flue gas may be slightly acidic and may adversely  
affect some building materials. If any vent termination is  
used and the flue gases may impinge on the building  
material, a corrosion-resistant shield (minimum 24 inches  
square) must be used to protect the wall surface. If the  
optional tee is used, the protective shield is required. The  
shield should be constructed using wood, plastic, sheet metal  
or other suitable material. All seams, joints, cracks, etc. in  
the affected area should be sealed using an appropriate  
sealant. See Figure 27.  
1/2" (13mm) FOAM  
INSULATION IN  
12" (305mm) ABOVE  
AVERAGE SNOW  
ACCUMULATION  
UNCONDITIONED  
(IF REQUIRED)  
SPACE  
3" (76mm) OR  
2" (51mm) PVC  
PROVIDE SUPPORT  
FOR INTAKE AND  
EXHAUST LINES  
Intake and exhaust pipes may be routed either horizontally  
through an outside wall or vertically through the roof. In  
attic or closet installations, vertical termination through the  
roof is preferred. Figures 25 through 33 show typical  
terminations.  
FIGURE 25  
FLUSH−MOUNT SIDE WALL TERMINATION  
51W11  
2" EXTENSION  
FOR 2" PVC PIPE  
1" EXTENSION  
FOR 3" PVC PIPE  
1. Exhaust and intake exits must be in same pressure zone.  
Do not exit one through the roof and one on the side.  
Also, do not exit the intake on one side and the exhaust  
on another side of the house or structure.  
2. Intake and exhaust pipes should be placed as close  
together as possible at termination end (refer to  
illustrations). Maximum separation is 3" (76 mm) on  
roof terminations and 6" (152 mm) on side wall  
terminations.  
3. On roof terminations, the intake piping should terminate  
straight down using two 90° elbows (See Figure 25).  
4. Exhaust piping must terminate straight out or up as  
shown. Areducer may be required on the exhaust piping  
at the point where it exits the structure to improve the  
velocity of exhaust away from the intake piping. See  
Table 8.  
FURNACE  
EXHAUST  
PIPE  
4’’  
FURNACE  
INTAKE PIPE  
GLUE EXHAUST  
END FLUSH INTO  
TERMINATION  
FLAT SIDE  
1−1/2" ACCELERATOR  
(all −45, −070 and −090 units)  
FIGURE 26  
EXHAUST PIPE TERMINATION SIZE REDUCTION  
6. On field supplied terminations, a minimum distance  
between the end of the exhaust pipe and the end of the  
intake pipe without a termination elbow is 8" and a  
minimum distance of 6" with a termination elbow. See  
Figures 28 and 29.  
7. If intake and exhaust piping must be run up a side wall  
to position above snow accumulation or other  
obstructions, piping must be supported every 24" (610  
mm) as shown in Figures 28 and 29.  
Termination  
MODEL  
Exhaust Pipe Size  
Pipe Size  
1−1/2" (38mm)  
2" (51mm)  
2" (51mm)  
2" (51mm), 2−1/2" (64mm),  
3" (76mm)  
*045 and *070  
*090  
3" (76mm)  
110  
TABLE 8  
*045, 070and090unitswiththe flush−mounttermination  
must use the 1−1/2"accelerator supplied with the kit.  
5. On field supplied terminations for side wall exit, exhaust  
piping may extend a maximum of 12 inches (305 mm)  
for 2" PVC and 20 inches (508 mm) for 3" (76 mm) PVC  
beyond the outside wall. Intake piping should be as  
short as possible. See Figures 28 and 29.  
When exhaust and intake piping must be run up an  
outside wall, the exhaust piping must be terminated with  
pipe sized per Table 8. The intake piping may be  
equipped with a 90° elbow turndown. Using turndown  
will add 5 feet (1.5 m) to the equivalent length of the  
pipe.  
NOTE: Care must be taken to avoid recirculation of exhaust  
back into intake pipe.  
8. Based on the recommendation of the manufacturer, a  
multiple furnace installation may use a group of up to  
four terminations assembled together horizontally, as  
shown in Figure 32.  
506725-01  
Page 21 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
B
B
D
D
C
3
Intake  
C
1
Front View of  
Intake and Exhaust  
A
Exhaust  
A
2
Intake  
Exhaust  
D
TABLE 9  
1
E
2" (51mm)  
Vent Pipe  
3" (76mm)  
Vent Pipe  
B
A− Clearance above  
grade or average snow  
accumulation  
12" (508MM) Min.  
12" (508MM) Min.  
12"  
B −Horizontal  
separation between  
intake and exhaust  
6" (152MM) Min.  
24" (610 MM) Max  
6" (152MM) Min.  
24" (610 MM) Max  
9" (227MM) Min.  
C
2
C −Minimum from  
end of exhaust to  
inlet of intake  
A
9" (227MM) Min.  
12" (305MM) Min.  
16" (405 MM) Max.  
12" (305MM) Min.  
20" (508MM) Max.  
D−Exhaust pipe length  
E −Wall support distance  
from top of each pipe  
(intake/exhaust)  
6" (152MM) Max.  
6" (152MM) Max.  
1
The exhaust termination tee should be connected to the 2" or 3" PVC flue pipe as shown in the illustration. Do  
not use an accelerator in applications that include an exhaust termination tee. The accelerator is not required.  
2
As required. Flue gas may be acidic and may adversely affect some building materials. If a side wall vent  
termination is used and flue gases will impinge on the building materials, a corrosion−resistant shield (24 inches  
square) should be used to protect the wall surface. If optional tee is used, the protective shield is recom-  
mended. The shield should be constructed using wood, sheet metal or other suitable material. All seams, joints,  
cracks, etc. in affected area, should be sealed using an appropriate sealant.  
3
Exhaust pipe 45° elbow can be rotated to the side away from the combustion air inlet to direct exhaust away  
from adjacent property. The exhaust must never be directed toward the combustion air inlet.  
FIGURE 27  
Page 22 of 48  
Issue 1109  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
FIELD SUPPLIED WALL TERMINATION  
FIELD SUPPLIED WALL TERMINATION  
NOTE − FIELD PROVIDED  
REDUCER MAY BE  
REQUIRED TO ADAPT  
LARGER VENT PIPE SIZE  
TO TERMINATION  
NOTE − FIELD PROVIDED  
REDUCER MAY BE  
REQUIRED TO ADAPT  
LARGER VENT PIPE SIZE  
TO TERMINATION  
1/2" (13mm) ARMAFLEX  
1/2" (13mm) ARMAFLEX  
INSULATION IN UN-  
CONDITIONED SPACE  
(IF REQUIRED)  
INSULATION IN UN-  
CONDITIONED SPACE  
(IF REQUIRED)  
SIZE TERMINATION  
PER TABLE 8  
SIZE TERMINATION  
PER TABLE 8  
D
B
D
B
STRAIGHT  
STRAIGHT  
C
APPPLICATION  
C
A
APPPLICATION  
A
1/2" (13mm) ARMAFLEX INSULATION  
IN UNCONDITIONED SPACE (IF REQUIRED)  
1/2" (13mm) ARMAFLEX INSULATION  
IN UNCONDITIONED SPACE (IF REQUIRED)  
D
D
E
* WALL  
SUPPORT  
E
* WALL  
SUPPORT  
B
B
A
A
EXTENDED  
APPLICATION  
C
C
EXTENDED  
APPLICATION  
See venting Table 7 for maximum venting lengths with this  
arrangement.  
See venting Table 7 for maximum venting lengths with this  
arrangement.  
* Use wall support every 24" (610 mm). Use two wall supports if  
extension is greater than 24" (610 mm) but less than 48" (1219 mm).  
NOTE − One wall support must be 6" (152 mm) from top of each pipe  
(intake and exhaust)  
* Use wall support every 24" (610 mm). Use two wall supports if  
extension is greater than 24" (610 mm) but less than 48" (1219 mm).  
NOTE − One wall support must be 6" (152 mm) from top of each pipe  
(intake and exhaust)  
2" (51mm)  
Vent Pipe  
3" (76mm)  
Vent Pipe  
2" (51mm)  
Vent Pipe  
3" (76mm)  
Vent Pipe  
A−Minimum clearance  
above grade or average  
snow accumulation  
A−Minimum clearance  
above grade or average  
snow accumulation  
12" (508MM)  
12" (508MM)  
12" (508MM)  
6" (152MM)  
8" (203MM)  
12" (508MM)  
6" (152MM)  
8" (203MM)  
B −Maximum horizontal  
separation between  
intake and exhaust  
C −Minimum from  
end of exhaust to  
inlet of intake  
B −Maximum horizontal  
separation between  
intake and exhaust  
6" (152MM)  
6" (152MM)  
C −Minimum from  
end of exhaust to  
inlet of intake  
6" (152MM)  
20" (508MM)  
6" (152MM)  
6" (152MM)  
12" (305MM)  
6" (152MM)  
D−Maximum exhaust  
D−Maximum exhaust  
pipe length  
12" (305MM)  
6" (152MM)  
20" (508MM)  
6" (152MM)  
pipe length  
E −Maximum wall support  
distance from top of each  
pipe (intake/exhaust)  
E −Maximum wall support  
distance from top of each  
pipe (intake/exhaust)  
FIGURE 29  
FIGURE 28  
506725-01  
Page 23 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
DIRECT VENT CONCENTRIC ROOFTOP TERMINATION  
71M80, 69M29 or 60L46 (US)  
OPTIONAL VENT TERMINATION FOR MULTIPLE UNIT  
INSTALLATION OF DIRECT VENT WALL TERMINATION KIT  
44W92 or 44W93 (Canada)  
1 1/2" (38mm) accelerator  
provided on 71M80 & 44W92  
12"  
EXHAUST  
VENT  
(305mm)  
EXHAUST  
VENT  
5−1/2"  
5"  
(140mm)  
(127mm)  
INTAKE  
AIR  
FLASHING  
(Not Furnished)  
12” (305mm)  
Minimum  
INTAKE  
AIR  
18" MAX.  
(457mm)  
Front View  
Above Average  
Snow  
EXHAUST VENT  
Accumulation  
12" (305mm) Min.  
above grade or  
average snow  
accumulation.  
Inches (mm)  
INTAKE  
AIR  
SHEET METAL STRAP  
(Clamp and sheet metal strap  
must be field installed to support  
the weight of the termination kit.)  
optional intake elbow  
CLAMP  
Side View  
FIGURE 32  
FIELD−PROVIDED  
REDUCER MAY BE REQUIRED  
TO ADAPT LARGER VENT  
PIPE SIZE TO TERMINATION  
FIGURE 30  
DIRECT VENT CONCENTRIC WALL TERMINATION  
71M80, 69M29 or 60L46 (US)  
DIRECT VENT APPLICATION  
USING EXISTING CHIMNEY  
44W92 or 44W93 (Canada)  
STRAIGHT−CUT OR  
FIELD−PROVIDED  
REDUCER MAY BE REQUIRED  
1−1/2" (38mm) accelerator  
provided on 71M80 & 44W92  
ANGLE−CUT IN DIRECTION  
OF ROOF SLOPE *  
3"−8"  
(76mm−203mm)  
TO ADAPT LARGER VENT  
PIPE SIZE TO TERMINATION  
EXHAUST VENT  
1/2" (13mm)  
WEATHERPROOF  
INSULATION  
8" − 12"  
(203mm − 305mm)  
OUTSIDE  
WALL  
INTAKE  
AIR  
EXHAUST  
VENT  
EXHAUST  
VENT  
SHOULDER OF FITTINGS  
PROVIDE SUPPORT  
Minimum 12" (305MM)  
above chimney top  
plate or average snow  
accumulation  
INTAKE PIPE  
INSULATION (optional)  
OF PIPE ON TOP PLATE  
SHEET  
METAL TOP  
PLATE  
ALTERNATE  
INTAKE PIPE  
12" (305mm) Min.  
INTAKE  
INTAKE  
AIR  
CLAMP  
(Not Furnished)  
above grade or  
average snow  
accumulation.  
AIR  
3" − 8"  
(76mm−  
203mm)  
INSULATE  
TO FORM  
SEAL  
EXTERIOR  
PORTION OF  
CHIMNEY  
GRADE  
FIGURE 31  
*SIZE TERMINATION  
PIPE PER TABLE 6.  
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
FIGURE 33  
Page 24 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
Details of Exhaust Piping Terminations for Non-Direct  
VentApplications  
NON−DIRECT VENT FIELD SUPPLIED WALL  
TERMINATION EXTENDED  
Exhaust pipe may be routed either horizontally through an  
outside wall or vertically through the roof. In attic or closet  
installations, vertical termination through the roof is preferred.  
Figures 34 through 37 show typical terminations.  
12" (305mm) MAX. for 2" (51mm)  
20" (508mm) MAX. for 3" (76mm)  
UNCONDITIONED  
SPACE  
6" (152mm)  
Max  
SIZE TER-  
MINATION  
PIPE PER  
TABLE 8.  
1. Exhaust piping must terminate straight out or up as  
shown. The termination pipe must be sized as listed in  
Table 8. The specified pipe size ensures proper velocity  
required to move the exhaust gases away from the  
building.  
2. On field supplied terminations for side wall exit, exhaust  
piping may extend a maximum of 12 inches (305 mm)  
for 2” PVC and 20” (508 mm) for 3” (76 mm) PVC beyond  
the outside wall. See Figure 35.  
*WALL SUPPORT  
OUTSIDE WALL  
FIELD−PROVIDED  
REDUCER MAY BE  
REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE TO  
TERMINATION  
12" (305mm)  
ABOVE GRADE OR  
AVERAGE SNOW  
ACCUMULATION  
1/2" (13mm) FOAM  
INSULATION IN  
3. If exhaust piping must be run up a sidewall to position  
above snow accumulation or other obstructions, piping  
must be supported every 24” (610 mm) as shown in  
Figure 36. When exhaust piping must be run up an  
outside wall, any reduction in exhaust pipe size must be  
done after the final elbow.  
UNCONDITIONED  
SPACE (IF REQUIRED)  
1/2" (13mm) FOAM  
INSULATION (IF REQUIRED)  
*Use wall support every 24" (610). Use two supports if extension is  
greater than 24" but less than 48".  
FIGURE 36  
NON−DIRECT VENT ROOF TERMINATION KIT  
(15F75 or 44J41)  
SIZE TERMINATION  
PIPE PER TABLE 8.  
NON−DIRECT VENT APPLICATION  
USING EXISTING CHIMNEY  
12" (305mm)  
ABOVE AVE.  
SNOW  
ACCUMULATION  
STRAIGHT−CUT OR  
SIZE TERMINATION  
PIPE PER TABLE 8.  
ANGLE−CUT IN DIRECTION  
1/2" (13mm) FOAM  
INSULATION IF REQUIRED  
OF ROOF SLOPE  
EXHAUST VENT  
1/2" (13mm)  
WEATHERPROOF  
Minimum 12" (305MM)  
3" (76mm) OR  
2" (51mm) PVC  
INSULATION (IF REQUIRED)  
UNCONDITIONED  
ATTIC SPACE  
above chimney top  
plate or average snow  
SHOULDER OF FITTINGS  
accumulation  
PROVIDE SUPPORT  
PROVIDE SUPPORT  
FOR EXHAUST LINES  
OF PIPE ON TOP PLATE  
SHEET  
METAL TOP  
PLATE  
INSULATE  
TO FORM  
SEAL  
FIGURE 34  
EXTERIOR  
PORTION OF  
CHIMNEY  
NON−DIRECT VENT FIELD SUPPLIED WALL TERMINATION  
NOTE − Do not discharge exhaust gases directly into any chimney or vent stack. If ver-  
tical discharge through an existing unused chimney or stack is required, insert piping  
inside chimney until the pipe open end is above top of chimney and terminate as illus-  
trated. In any exterior portion of chimney, the exhaust vent must be insulated.  
12" (305mm) MAX. for 2" (51mm)  
20" (508mm) MAX. for 3" (76mm)  
1/2" (13mm) ARMAFLEX  
INSULATION IN  
UNCONDITIONED SPACE (IF REQUIRED)  
1/2" (13mm)  
ARMAFLEX  
FIGURE 37  
FIELD−PROVIDED  
REDUCER MAY  
INSULATION  
(IF REQUIRED)  
BE REQUIRED TO  
ADAPT LARGER  
VENT PIPE SIZE  
TO TERMINATION  
PVC REDUCER  
12" MIN.  
(305mm)  
Above Grade or  
average snow  
accumulation  
SIZE TERMINATION  
PIPE PER TABLE 8.  
FIGURE 35  
506725-01  
Page 25 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Condensate Piping  
This unit is designed for either right or left side exit of  
condensate piping in downflow applications.  
Figure 38 for condensate trap locations.  
Condensate line must slope downward away from the trap  
to drain. If drain level is above condensate trap, condensate  
pump must be used. Condensate drain line should be routed  
within the conditioned space to avoid freezing of condensate  
and blockage of drain line. If this is not possible, a heat  
cable kit may be used on the condensate trap and line.  
Heating cable kit is available in various lengths:  
Refer to  
NOTE: If necessary the condensate trap may be installed  
up to 5” away using PVC pipe from the furnace. Piping from  
furnace must slope down a minimum of 1/4” per ft. toward  
trap.  
6 ft. (1.8 m) - kit no. 26K68; 24 ft. (7.3 m) - kit no. 26K69;  
and 50 ft. (15.2 m) - kit no. 26K70.  
1. Determine which side condensate piping will exit the  
unit, location of trap, field-provided fittings and length of  
PVC pipe required to reach available drain.  
CONDENSATE TRAP LOCATION  
(shown with right side exit of condensation)  
2. Remove plug (Figure 38) from the cold end header box  
at the appropriate location on the side of the unit. Install  
field-provided 1/2 NPT male fitting into cold end header  
box. Use Teflon tape or appropriate pipe dope.  
Field Provided Vent  
min. 1" Above  
Condensate Drain  
3. Install the cap over the clean out opening at the base of  
the trap. Secure with clamp. See Figure 41.  
4. Install drain trap using appropriate PVC fittings, glue all  
Trap can be installed a  
maximum of 5 ft. from furnace.  
(*PVC Only)  
joints.  
Glue the provided drain trap as shown in  
1" min.  
Figure 41. Route the condensate line to an open drain.  
Condensate line must maintain a 1/4” downward slope  
from the furnace to the drain.  
5’ max.  
CAUTION  
to drain  
Do Not use copper tubing or existing copper condensate  
lines for drain line.  
*Piping from furnace must slope down a minimum of  
1/4" per ft. toward trap.  
5. If unit will be started immediately upon completion of  
installation, prime trap per procedure outlined in Unit  
Start-Up section.  
FIGURE 39  
UNIT WITH EVAPORATOR COIL  
CONDENSATE TRAP AND PLUG LOCATIONS  
Condensate trap and  
evaporator coil must drain  
separately as shown.  
Field−Provided Vent  
Trap  
(same on  
right side)  
Plug  
1−1/2 in.  
(same on left  
Drain  
side)  
FIGURE 40  
CAUTION  
A separate drain line must be run to the drain from the  
condensate trap to ensure proper drainage and pressure  
switch operation. DO NOT connect the condensate trap  
drain into the drain line from the evaporator coil.  
FIGURE 38  
Page 26 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
TRAP / DRAIN ASSEMBLY USING 1/2" PVC OR 3/4" PVC  
OPTIONAL Condensate Drain Connection  
Adapter 1/2 inch slip X  
Adapter 1/2 inch slip X  
1/2 inch mpt (Not Furnished)  
Condensate Drain  
Connection In Unit  
1/2 inch mpt (Not Furnished)  
Vent  
90° Street Elbow  
1 (25) Minimum  
1/2 inch PVC  
5 Feet  
Maximum  
(Not Furnished)  
Above Top of Condensate Drain  
Connection In Unit  
90° Elbow 1/2 inch PVC  
Condensate Drain  
Connection In Unit  
(Not Furnished)  
1/2 inch PVC Pipe  
(Not Furnished)  
1/2 inch PVC Pipe  
(Not Furnished)  
OPTIONAL Drain Piping  
Drain Assembly for 1/2 inch Drain Pipe  
Coupling 1/2 inch slip X slip  
(Not Furnished)  
1/2 inch PVC Pipe  
(Not Furnished)  
Drain Trap  
Assembly  
(Furnished)  
1/2 inch PVC  
90° Elbow  
(Not Furnished)  
1/2 inch PVC  
(Not Furnished)  
To  
To  
Drain  
Drain  
Drain Assembly for 3/4 inch Drain Pipe  
Drain Trap  
Clean Out  
90° Elbow  
90° Elbow  
3/4 inch PVC  
(Not Furnished)  
3/4 inch PVC  
(Not Furnished)  
To  
Drain  
To  
Drain  
Coupling 3/4 inch slip X slip  
(Not Furnished)  
Drain Trap Assembly with 3/4 inch Piping  
Drain Trap Assembly with 1/2 inch Piping  
1 inch (25mm) Minimum Above Top of  
Condensate Drain Connection In Unit  
1 inch (25mm) Minimum Above Top of  
Condensate Drain Connection In Unit  
Vent  
Drain Trap Assembly  
(Furnished)  
Vent  
3/4 inch  
Piping  
7
Condensate Drain  
Connection In Unit  
Condensate Drain  
Connection In Unit  
(178)  
To  
Drain  
To  
Drain  
FIGURE 41  
506725-01  
Page 27 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Gas Piping  
IMPORTANT  
Compounds used on threaded joints of gas piping must  
be resistant to the actions of liquified petroleum gases.  
CAUTION  
If a flexible gas connector is required or allowed by the  
authority that thas jurisdiction, black iron pipe shall be  
installed at the gas valve and extend outside the furnace  
cabinet. The flexible connector can then be added  
between the black iron pipe and the gas supply line.  
Leak Check  
After gas piping is completed, carefully check all piping  
connections (factory and field installed) for gas leaks. Use  
a leak detecting solution or other preferred means.  
The furnace must be isolated from the gas supply system  
by closing its individual manual shut off valve during any  
pressure testing of the gas supply system at pressures  
greater than or equal to 1/2 psig (3.48 kPa, 14 inches w.c.).  
WARNING  
Do Not exceed 600 in. lbs. (50 ft. lbs.) torque when  
attaching the gas piping to the gas valve.  
MANUAL MAIN SHUT−OFF  
FURNACE  
VALVE WILL NOT HOLD  
1. Gas piping may be routed into the unit through either  
the left or right hand side. Supply piping enters into  
the gas valve from the side of the valve as shown in  
Figure 43. Move bellows grommet to side of the cabinet  
which the gas line enters. Ensure opposite gas line  
entrance is plugged with supplied plug.  
NORMAL TEST PRESSURE  
ISOLATE  
1/8" N.P.T. PLUGGED TAP  
GAS VALVE  
CAP  
FIGURE 42  
IMPORTANT  
A low inlet pressure switch in LP/propane applications  
is recommended.  
IMPORTANT  
When testing pressure of gas lines, gas valve must be  
disconnected and isolated. (See Figure 42.) Gas  
Valves can be damaged if subjected to pressures  
greater than 1/2 psig (3.48 kPa).  
2. When connecting gas supply, factors such as length of  
run, number of fittings and furnace rating must be  
considered to avoid excessive pressure drop. Table 10  
lists recommended pipe sizes for typical applications.  
NOTE: Use two wrenches when connecting gas piping to  
avoid transferring torque to the manifold.  
WARNING  
3. Gas piping must not run in or through air ducts, clothes  
chutes, chimneys or gas vents, dumb waiters or elevator  
shafts. Center gas line through piping hole. Gas line  
should not touch side of unit. See Figures 43.  
4. Piping should be sloped 1/4 inch per 15 feet (6 mm per  
5.6 m) upward toward the gas meter from the furnace.  
The piping must be supported at proper intervals, every  
8 to 10 feet (2.44 to 3.05 m), using suitable hangers or  
straps. Install a drip leg in vertical pipe runs to serve as  
a trap for sediment or condensate.  
FIRE OR EXPLOSION HAZARD  
Failure to follow the safety warnings exactly could result  
in serious injury, death, or property damage. Never use  
an open flame to test for gas leaks. Check all  
connections using a commercially available soap  
solution made specifically for leak detection. Some  
soaps used for leak detection are corrosive to certain  
metals. Carefully rinse piping thoroughly after leak test  
has been completed.  
5. A1/8" N.P.T. plugged tap or pressure post is located on  
the gas valve to facilitate test gauge connection. See  
Figure 50.  
6. In some localities, codes may require installation of a  
manual main shut off valve and union (furnished by  
installer) external to the unit. Union must be of the  
ground joint type.  
Page 28 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
Left Side Piping  
(Standard)  
MANUAL  
MAIN SHUT−OFF  
VALVE  
(With 1/8 in. NPT  
Plugged Tap  
Shown)  
AUTOMATIC  
GAS VALVE  
(with manual  
shut−off valve)  
MANUAL  
MAIN SHUT−OFF  
VALVE  
(With 1/8 in. NPT  
Plugged Tap Shown)  
AUTOMATIC  
GAS VALVE  
(with manual  
shut−off valve)  
Plug  
Plug  
GROUND  
JOINT  
UNION  
GROUND  
JOINT  
UNION  
DRIP LEG  
Right Side Piping  
(Alternate)  
FIELD  
PROVIDED  
AND INSTALLED  
DRIP LEG  
Bellows Grommet  
Bellows Grommet  
NOTE − BLACK IRON PIPE ONLY TO BE ROUTED INSIDE OF CABINET  
FIGURE 43  
3
GAS PIPE CAPACITY − FT /HR (kL/HR)  
Length of Pipe−Feet(m)  
Nominal  
Iron Pipe Size  
−Inches(mm)  
Internal  
Diameter  
10  
(3.048)  
20  
30  
(9.144)  
40  
(12.192)  
50  
(15.240)  
60  
(18.288)  
70  
(21.336)  
80  
(24.384)  
90  
(27.432)  
100  
(30.480)  
−Inches(mm)  
(6.096)  
1/2  
(12.7)  
.622  
(17.799)  
175  
(4.96)  
120  
(3.40)  
97  
(2.75)  
82  
(2.32)  
73  
(2.07)  
66  
(1.87)  
61  
(1.73)  
57  
(1.61)  
53  
(1.50)  
50  
(1.42)  
3/4  
(19.05)  
.824  
(20.930)  
360  
(10.19)  
250  
(7.08)  
200  
(5.66)  
170  
(4.81)  
151  
(4.28)  
138  
(3.91)  
125  
(3.54)  
118  
(3.34)  
110  
(3.11)  
103  
(2.92)  
1
1.049  
(26.645)  
680  
(19.25)  
465  
(13.17)  
375  
(10.62)  
320  
(9.06)  
285  
(8.07)  
260  
(7.36)  
240  
(6.80)  
220  
(6.23)  
205  
(5.80)  
195  
(5.52)  
(25.4)  
1−1/4  
(31.75)  
1.380  
(35.052)  
1400  
(39.64)  
950  
(26.90)  
770  
(21.80)  
660  
(18.69)  
580  
(16.42)  
530  
(15.01)  
490  
(13.87)  
460  
(13.03)  
430  
(12.18)  
400  
(11.33)  
1−1/2  
(38.1)  
1.610  
(40.894)  
2100  
(59.46)  
460  
(41.34)  
1180  
(33.41)  
990  
(28.03)  
900  
(25.48)  
810  
(22.94)  
750  
(21.24)  
690  
(19.54)  
650  
(18.41)  
620  
(17.56)  
2
2.067  
(52.502)  
3950  
(111.85)  
2750  
(77.87)  
2200  
(62.30)  
1900  
(53.80)  
1680  
(47.57)  
1520  
(43.04)  
1400  
(39.64)  
1300  
(36.81)  
1220  
(34.55)  
1150  
(32.56)  
(50.8)  
2−1/2  
(63.5)  
2.469  
(67.713)  
6300  
(178.39)  
4350  
(123.17)  
3520  
(99.67)  
3000  
(84.95)  
2650  
(75.04)  
2400  
(67.96)  
2250  
(63.71)  
2050  
(58.05)  
1950  
(55.22)  
1850  
(52.38)  
3
3.068  
(77.927)  
11000  
(311.48)  
7700  
(218.03)  
6250  
(176.98)  
5300  
(150.07)  
4750  
(134.50)  
4300  
(121.76)  
3900  
(110.43)  
3700  
(104.77)  
3450  
(97.69)  
3250  
(92.03)  
(76.2)  
4
4.026  
(102.260)  
23000  
(651.27)  
15800  
(447.39)  
12800  
(362.44)  
10900  
(308.64)  
9700  
(274.67)  
8800  
(249.18)  
8100  
(229.36)  
7500  
(212.37)  
7200  
(203.88)  
6700  
(189.72)  
(101.6)  
NOTE − Capacity given in cubic feet of gas per hour (kilo liters of gas per hour) and based on 0.60 specific gravity gas.  
TABLE 10  
506725-01  
Page 29 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Removal of the Furnace from Common Vent  
In the event that an existing furnace is removed from a  
venting system commonly run with separate gas appliances,  
the venting system is likely to be too large to properly vent  
the remaining attached appliances.  
3. Close all building doors and windows and all doors  
between the space in which the appliances remaining  
connected to the common venting system are located  
and other spaces of the building. Turn ON clothes dryers  
and any appliances not connected to the common  
venting system. Turn ON any exhaust fans, such as  
range hoods and bathroom exhausts, so they will  
operate at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers.  
Conduct the following test while each appliance is operating  
and the other appliances (which are not operating) remain  
connected to the common venting system. If the venting  
system has been installed improperly, you must correct the  
system as indicated in the general venting requirements  
section.  
4. Follow the lighting instructions. Turn ON the appliance  
that is being inspected. Adjust the thermostat so that  
the appliance operates continuously.  
5. After the main burner has operated for 5 minutes, test  
for leaks of flue gases at the draft hood relief opening.  
Use the flame of a match or candle.  
6. After determining that each appliance connected to the  
common venting system is venting properly, (step 3)  
return all doors, windows, exhaust fans, fireplace  
dampers, and any other gas burning appliances to their  
previous mode of operation.  
7. If a venting problem is found during any of the preceding  
tests, the common venting system must be modified to  
correct the problems.  
WARNING  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being placed  
into operation could result in carbon monoxide poisoning  
or death.  
The following steps shall be followed for each appliance  
connected to the venting system being placed into  
operation, while all other appliances connected to the  
venting system are not in operation.  
Resize the common venting system to the minimum vent  
pipe size determined by using the appropriate tables in  
Appendix G. These are in the current standards of the  
National Fuel Gas Code ANSI Z223.1.  
1. Seal any unused openings in the common venting  
system.  
2. Inspect the venting system for proper size and horizontal  
pitch. Determine that there is no blockage, restriction,  
leakage, corrosion, or other deficiencies which could  
cause an unsafe condition.  
Page 30 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
Electrical  
ELECTROSTATIC DISCHARGE (ESD)  
The unit is equipped with a field makeup box on the left  
hand side of the cabinet. A field-provided make-up box can  
be installed on the exterior of the right side of the furnace to  
facilitate installation. Seal unused openings on left side with  
plugs removed from right side. Secure the excess wire to  
the existing harness to protect it from damage.  
Precautions and Procedures  
CAUTION  
Electrostatic discharge can affect electronic  
components. Take precautions during furnace  
installation and service to protect the furnace’s electronic  
controls. Precautions will help to avoid control exposure  
to electrostatic discharge by putting the furnace, the  
control and the technician at the same electrostatic  
potential. Neutralize electrostatic charge by touching  
hand and all tools on an unpainted unit surface, such as  
the gas valve or blower deck, before performing any  
service procedure.  
Refer to Figure 47 for field wiring and Figure 48 for schematic  
wiring diagram and troubleshooting.  
The power supply wiring must meet Class I restrictions.  
Protected by either a fuse or circuit breaker, select circuit  
protection and wire size according to unit nameplate.  
NOTE: Unit nameplate states maximum current draw.  
Maximum Over-Current Protection allowed is 15 AMP.  
Holes are on both sides of the furnace cabinet to facilitate  
wiring.  
INTERIOR MAKE−UP BOX  
Install a separate (properly sized) disconnect switch near  
the furnace so that power can be turned off for servicing.  
(FACTORY− INSTALLED LEFT SIDE)  
Before connecting the thermostat check to make sure the  
wires will be long enough for servicing at a later date. Make  
sure that thermostat wire is long enough to facilitate future  
removal of blower for service.  
MAKE−UP  
BOX INSIDE  
Left side  
CABINET  
Complete the wiring connections to the equipment. Use the  
provided unit wiring diagram and the field wiring diagram  
shown in Figure 47. Use 18 gauge wire or larger that is  
suitable for Class II rating for thermostat connections.  
Electrically ground the unit according to local codes or, in  
the absence of local codes, according to the current National  
Electric Code (ANSI/HFPA No. 70) for the USA and current  
Canadian Electric Code Part 1 (CSA standard C22.1) for  
Canada. Agreen ground wire is provided in the field makeup  
box.  
FIGURE 44  
EXTERIOR MAKE−UP BOX  
(FIELD PROVIDED RIGHT SIDE)  
NOTE: The gas furnace contains electronic components  
that are polarity sensitive. Make sure that the furnace is  
wired correctly and is properly grounded.  
MAKE−UP  
BOX  
OUTSIDE  
CABINET  
Accessory Terminals  
One line voltage “EAC” 1/4” spade terminal is provided on  
the furnace control board. Any accessory rated up to one  
amp can be connected to this terminal with the neutral leg  
of the circuit being connected to one of the provided neutral  
terminals. If an accessory rated at greater than one amp is  
connected to this terminal, it is necessary to use an external  
relay. See Figure 49 for control board configuration. This  
terminal is energized when the indoor blower is operating.  
Right Side  
FIGURE 45  
506725-01  
Page 31 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
One line voltage “HUM” 1/4” spade terminal is provided on  
the furnace control board. Any humidifier rated up to one  
amp can be connected to this terminal with the neutral leg  
of the circuit being connected to one of the provided neutral  
terminals. If a humidifier rated at greater than one amp is  
connected to this terminal, it is necessary to use an external  
relay. See Figure 49 for control board configuration. This  
terminal is energized in the heating mode when the  
combustion air inducer is operating.  
Indoor Blower Speeds  
1. When the thermostat is set to “FAN ON”, the indoor  
blower will run continuously on the heating speed when  
there is no cooling or heating demand.  
2. When the furnace is running in the heating mode, the  
indoor blower will run on the heating speed.  
3. When there is a cooling demand, the indoor blower will  
run on the cooling speed.  
Generator Use - Voltage Requirements  
The following requirements must be kept in mind when  
specifying a generator for use with this equipment:  
Install the room thermostat according to the instructions  
provided with the thermostat. See Figure 46 for thermostat  
designations. If the furnace is being matched with a heat  
pump, refer to the FM21 installation instruction or appropriate  
dual fuel thermostat instructions.  
The furnace requires 120 volts ± 10% (Range: 108 volts  
to 132 volts).  
The furnace operates at 60 Hz ± 5% (Range: 57 Hz to  
63 Hz).  
The furnace integrated control requires both polarity and  
proper ground. Both polarity and proper grounding  
should be checked before attempting to operate the  
furnace on either permanent or temporary power.  
Generator should have a wave form distortion of less  
than 5% THD (total harmonic distortion).  
FURNACE and CONDENSING UNIT  
THERMOSTAT DESIGNATIONS  
(Refer to specific thermostat and outdoor unit.)  
Thermostat  
Furnace  
Condensing  
Unit  
*CONDENSING  
POWER  
HEAT  
R
R
W1  
Y
W
Y
CONDENSING  
CONDENSING  
COOLING  
INDOOR BLOWER  
COMMON  
G
C
G
C
FIGURE 46  
TYPICAL FIELD WIRING DIAGRAM  
IGNITOR  
*R  
FIGURE 47  
Issue 1109  
Page 32 of 48  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
TYPICAL WIRING DIAGRAM  
FIGURE 48  
506725-01  
Page 33 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
INTEGRATED CONTROL  
(Automatic Hot Surface Ignition System)  
HEAT BLOWER  
OFF DELAY JUMPER  
DIAGNOSTIC CODE  
RECALL BUTTON  
TERMINAL DESIGNATIONS  
Humidifier (120 VAC)  
Input (120 VAC)  
HUM  
L1  
XFMR  
5 AMP  
FUSE  
Transformer (120 VAC)  
Blower - Continuous Fan (120 VAC)  
Electronic Air Cleaner (120 VAC)  
Blower - Cooling Speed (120 VAC)  
CONT  
EAC  
COOL  
HEAT  
PARK  
Blower - Heating Speed (120 VAC)  
Dead terminals to park alternate spd taps  
NEUTRALS Neutral terminals (120 VAC)  
FIGURE 49  
Unit Start-Up  
FOR YOUR SAFETY READ BEFORE OPERATING  
CAUTION  
Before attempting to perform any service or  
maintenance, turn the electrical power to unit OFF at  
disconnect switch.  
WARNING  
Do not use this furnace if any part has been underwater.  
A flood-damaged furnace is extremely dangerous.  
Attempts to use the furnace can result in fire or  
explosion. Immediately call a qualified service technician  
to inspect the furnace and to replace all gas controls,  
control system parts, and electrical parts that have been  
wet or to replace the furnace, if deemed necessary.  
BEFORE LIGHTING the unit, smell all around the furnace  
area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floor.  
The gas valve on the unit is equipped with a gas control  
switch (lever). Use only your hand to move switch. Never  
use tools. If the switch will not move by hand, do not try to  
repair it. Force or attempted repair may result in a fire or  
explosion.  
WARNING  
Danger of explosion. Can cause injury  
or product or property damage. Should  
the gas supply fail to shut off or if  
overheating occurs, shut off the gas  
valve to the furnace before shutting off  
the electrical blower deck, before  
performing any service procedure.  
Placing the furnace into operation:  
This furnace is equipped with an automatic hot surface  
ignition system. Do not attempt to manually light burners on  
this furnace. Each time the thermostat calls for heat, the  
burners will automatically light. The ignitor does not get hot  
when there is no call for heat on these units.  
Page 34 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
Priming Condensate Trap  
9. Replace the heating compartment access panel.  
10. Turn on all electrical power to the unit.  
11. Set the thermostat to desired setting.  
The condensate trap should be primed with water prior to  
start-up to ensure proper condensate drainage. Either pour  
10 fl. oz. (300 ml) of water into the trap, or follow these  
steps to prime the trap:  
1. Follow the lighting instructions to place the unit into  
operation.  
NOTE: When unit is initially started, steps 1 through 11  
may need to be repeated to purge air from gas line.  
2. Set the thermostat to initiate a heating demand.  
3. Allow the burners to fire for approximately 3 minutes.  
4. Adjust the thermostat to deactivate the heating demand.  
5. Wait for the combustion air inducer to stop. Set the  
thermostat to initiate a heating demand and again allow  
the burners to fire for approximately 3 minutes.  
6. Adjust the thermostat to deactivate the heating demand  
and wait for the combustion air inducer to stop. At this  
point, the trap should be primed with sufficient water to  
ensure proper condensate drain operation.  
12. If the appliance will not operate, follow the instructions  
“Turning Off Gas to Unit” and call your service technician  
or gas supplier.  
Turning Off Gas to Unit  
1. Set the thermostat to the lowest setting.  
2. Turn off all electrical power to the unit if service is to be  
performed.  
3. Remove the heating compartment access panel.  
4. Move gas valve switch to OFF.  
5. Replace the heating compartment access panel.  
WARNING  
Failure To Operate  
If you do not follow these instructions exactly, a fire or  
explosion may result causing property damage, personal  
injury or death.  
If the unit fails to operate, check the following:  
1. Is the thermostat calling for heat?  
2. Are access panels securely in place?  
3. Is the main disconnect switch closed?  
4. Is there a blown fuse or tripped breaker?  
5. Is the filter dirty or plugged? Dirty or plugged filters will  
cause the limit control to shut the unit off.  
6. Is gas turned on at the meter?  
Gas Valve Operation (Figure 50)  
1. STOP! Read the safety information at the beginning of  
this section.  
2. Set the thermostat to the lowest setting.  
3. Turn OFF all electrical power to the unit.  
4. This furnace is equipped with an ignition device which  
automatically lights the burners. Do not try to light the  
burners by hand.  
7. Is the manual main shut–off valve open?  
8. Is the internal manual shut–off valve open?  
9. Is the unit ignition system in lockout? If the unit locks  
out again, inspect the unit for blockages.  
5. Remove the heating compartment access panel.  
6. Move gas valve switch to OFF. See Figure 50.  
7. Wait five minutes to clear out any gas. If you then smell  
gas, STOP! Immediately call your gas supplier from a  
neighbor’s phone. Follow the gas supplier’s  
instructions. If you do not smell gas go to next step.  
8. Move gas valve switch to ON. See Figure 50.  
Heating Sequence Of Operation  
1. When thermostat calls for heat, combustion air inducer  
starts.  
2. Combustion air pressure switch proves blower  
operation. Switch is factory set and requires no  
adjustment.  
3. After a 15 second prepurge, the hot surface ignitor  
energizes.  
4. After a 20 second ignitor warm-up period, the gas valve  
solenoid opens. A 4-second “Trial for Ignition” period  
begins.  
5. Gas is ignited, flame sensor proves the flame, and the  
combustion process continues.  
6. If flame is not detected after first ignition trial, the ignition  
control will repeat steps 3 and 4 four more times before  
locking out the gas valve. The ignition control will then  
automatically repeat steps 1 through 6 after 60 minutes.  
To interrupt the 60 minute lockout period, move  
thermostat from “Heat” to “OFF” then back to “Heat”.  
Heating sequence then restarts at step 1.  
GAS VALVE SHOWN IN ON POSITION  
MANIFOLD  
PRESSURE  
ADJUSTMENT  
SCREW  
MANIFOLD  
PRESSURE  
OUTLET  
(UNDER CAP)  
INLET  
PRESSURE  
PORT  
FIGURE 50  
506725-01  
Page 35 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Gas Pressure Adjustment  
Gas Flow (Approximate)  
Supply Line and Manifold Pressure (inches w.c.)  
Manifold  
GAS METER CLOCKING CHART  
Seconds for One Revolution  
Unit  
Fuel  
Line Pressure  
Pressure  
All  
All  
Nat. Gas  
L.P. Gas  
3.5  
4.5 − 10.5  
Natural  
LP  
Unit  
1 cu ft  
2 cu ft  
Dial  
1 cu ft  
Dial  
200  
136  
102  
82  
2 cu ft  
DIAL  
10.0  
11.0 − 13.0  
Dial  
80  
55  
41  
33  
27  
TABLE 12  
−045  
−070  
−090  
−110  
−135  
160  
110  
82  
400  
272  
204  
164  
136  
NOTE:A natural to L.P. propane gas changeover kit is necessary  
to convert this unit. Refer to the changeover kit installation  
instruction for the conversion procedure.  
66  
54  
68  
Natural−1000 btu/cu ft  
LP−2500 btu/cu ft  
TABLE 11  
Proper Combustion  
NOTE: To obtain accurate reading, shut off all other gas  
Furnace should operate minimum 15 minutes with correct  
manifold pressure and gas flow rate before checking  
combustion. Take combustion sample beyond the flue outlet  
and compare to the tables below. The maximum carbon  
monoxide reading should not exceed 50 ppm.  
appliances connected to meter.  
Furnace should operate at least 5 minutes before checking  
gas flow. Determine time in seconds for two revolutions of  
gas through the meter. (Two revolutions assures a more  
accurate time.) Divide by two and compare to time in  
Table 11. If manifold pressure matches Table 12 and rate  
is incorrect, check gas orifices for proper size and restriction.  
Remove temporary gas meter if installed.  
CO %  
CO %  
For L.P.  
Unit  
2
For Nat  
2
All  
7.2 − 7.9  
8.6 − 9.3  
Supply Pressure Measurement  
A threaded plug on the inlet side of the gas valve provides  
access to the supply pressure tap. Remove the threaded  
plug, install a field-provided barbed fitting and connect a  
manometer to measure supply pressure. Replace the  
threaded plug after measurements have been taken.  
The maximum carbon monoxide reading should not exceed 50 ppm.  
TABLE 13  
High Altitude Information  
Manifold Pressure Measurement  
1. Remove the threaded plug from the outlet side of the  
gas valve and install a field provided barbed fitting.  
Connect to a manometer to measure manifold pressure.  
2. Start unit and allow 5 minutes for unit to reach steady  
state.  
3. While waiting for the unit to stabilize, observe the flame.  
Flame should be stable and should not lift from burner.  
Natural gas should burn blue.  
NOTE: In Canada, certification for installations at elevations  
over 4500 feet (1372 m) is the jurisdiction of local authorities.  
The furnace requires no manifold pressure adjustments for  
operation at altitudes up to 10,000 feet (3048 m) above sea  
level. Units installed at altitudes of 4501 - 10,000 feet (1373  
to 3048 m) require a pressure switch change which can be  
ordered separately. Table 14 lists conversion kit and  
pressure switch requirements at varying altitudes.  
4. After allowing unit to stabilize for 5 minutes, record  
manifold pressure and compare to value given in  
Table 12.  
The combustion air pressure switch is factory-set and  
requires no adjustment.  
NOTE: Shut unit off and remove manometer as soon as  
an accurate reading has been obtained. Take care to remove  
barbed fitting and replace threaded plug.  
Page 36 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
Burner Orifice Conversion Kits at Varying Altitudes  
0 - 7,500 ft  
(0 - 2,286 m)  
7,501 - 10,000 ft  
(2,286 - 3,038 m)  
High Altitude  
High Altitude  
LP/Propane  
Burner Orifice  
Kit  
Natural  
LP/Propane  
to  
Natural  
Burner Orifice  
Kit  
Unit  
Size  
to  
LP/Propane  
Natural  
All  
68W75*†  
73W80*  
51W01  
68W70*†  
* Conversion requires installation of a gas valve regulator spring which is provided with the gas conversion kit.  
† LP kit includes low line pressure switch.  
A93 and 92G1 Pressure Switches at Varying Altitudes  
Unit  
0 - 4,500 ft  
4,501 - 7,500 ft 7,501 - 10,000 ft  
(0 - 1,373 m)  
(1,373 - 2,286 m)  
(2,286 - 3,038 m)  
Size  
All  
No Change  
No Change  
74W91  
Pressure switch is factory set. No adjustment necessary.  
All models use the factory installed pressure switch from 0 - 7,500 feet.  
A95 and 95G1 Pressure Switches at Varying Altitudes  
Unit  
0 - 4,500 ft  
4,501 - 7,500 ft 7,501 - 10,000 ft  
(0 - 1,373 m)  
(1,373 - 2,286 m)  
(2,286 - 3,038 m)  
Size  
045  
070  
090  
110  
135  
No Change  
No Change  
No Change  
No Change  
No Change  
No Change  
77W43  
74W90  
73W22  
73W22  
73W22  
73W22  
77W42  
77W43  
77W42  
Pressure switch is factory set. No adjustment necessary.  
All models use the factory installed pressure switch from 0 - 4,500 feet.  
TABLE 14  
506725-01  
Page 37 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Testing for Proper Venting and Sufficient Combustion Air for Non-Direct Vent Applications  
6. Follow the lighting instruction to place the appliance  
being inspected into operation. Adjust thermostat so  
appliance will operate continuously.  
WARNING  
7. Use the flame of a match or candle to test for spillage  
of flue gases at the draft hood relief opening after 5  
minutes of main burner operation.  
CARBON MONOXIDE POISONING HAZARD  
Failure to follow the steps outlined below for each  
appliance connected to the venting system being placed  
into operation could result in carbon monoxide poisoning  
or death.  
8. If improper venting is observed during any of the above  
tests, the venting system must be corrected or sufficient  
combustion/makeup air must be provided. The venting  
system should be resized to approach the minimum  
size as determined by using the appropriate tables in  
appendix G in the current standards of the National Fuel  
Gas Code ANSI-Z223.1/NPFA 54 in the U.S.A., and  
the appropriate Natural Gas and Propane appliances  
venting sizing tables in the current standard of the CSA-  
B149 Natural Gas and Propane Installation Codes in  
Canada.  
9. After determining that each appliance remaining  
connected to the common venting system properly  
vents when tested as indicated in step 3, return doors,  
windows, exhaust fans, fireplace dampers and any other  
gas burning appliance to their previous condition of use.  
The following steps shall be followed for each appliance  
connected to the venting system being placed into  
operation, while all other appliances connected to the  
venting system are not in operation.  
After the gas furnace has been started, the following test  
should be conducted to ensure proper venting and sufficient  
combustion air has been provided to the unit as well as to  
other gas fired appliances which are separately vented.  
If this furnace replaces a Category I furnace which was  
commonly vented with another gas appliance, the size of  
the existing vent pipe for that gas appliance must be  
checked. Without the heat of the original furnace flue  
products, the existing vent pipe is probably oversized for  
the single water heater or other appliance. The vent should  
be checked for proper draw with the remaining appliance.  
The test should be conducted while all appliances (both in  
operation and those not in operation) are connected to the  
venting system being tested. If the venting system has been  
installed improperly, or if provisions have not been made  
for sufficient amounts of combustion air, corrections must  
be made as outlined in the previous section.  
1. Seal any unused openings in the venting system.  
2. Visually inspect the venting system for proper size and  
horizontal pitch. Determine there is no blockage or  
restriction, leakage, corrosion, or other deficiencies  
which could cause an unsafe condition.  
3. To the extent that it is practical, close all building doors  
and windows and all doors between the space in which  
the appliances connected to the venting system are  
located and other spaces of the building.  
4. Close fireplace dampers.  
5. Turn on clothes dryers and any appliances not  
connected to the venting system. Turn on any exhaust  
fans, such as range hoods and bathroom exhausts, so  
they will operate at maximum speed. Do not operate  
a summer exhaust fan.  
Page 38 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
Thermostat Heat Anticipation  
Other Unit Adjustments  
Set the heat anticipator setting (if adjustable) according to  
the amp draw listed on the wiring diagram that is attached  
to the unit.  
Primary Limit  
The primary limit is located on the heating compartment  
vestibule panel. This limit is factory set and requires no  
adjustment.  
Electrical  
1. Check all wiring for loose connections.  
2. Check for the correct voltage at the furnace (with  
furnace operating). Correct voltage is 120 VAC ± 10%.  
3. Check amp–draw on the blower motor with the blower  
compartment access panel in place.  
Flame Rollout Switches (Two)  
These manually reset switches are located on the front of  
the burner box. These limits are factory set and require no  
adjustment.  
Motor Nameplate__________Actual__________  
Pressure Switch  
The pressure switch is located in the heating compartment  
on the cold end header box. This switch checks for proper  
combustion air inducer operation before allowing ignition  
trial. The switch is factory set and must not be adjusted.  
Blower Speeds  
Follow the steps below to change the blower speeds.  
1. Turn off electrical power to furnace.  
2. Remove blower compartment access panel.  
3. Disconnect existing speed tap at control board speed  
terminal.  
Temperature Rise  
After the furnace has been started and supply and return  
air temperatures have been allowed to stabilize, check the  
temperature rise. If necessary, adjust the blower speed to  
maintain the temperature rise within the range shown on  
the unit nameplate. Increase the blower speed to decrease  
the the temperature. Decrease the blower speed to increase  
the temperature rise. Failure to adjust the temperature rise  
may cause erratic limit operation.  
NOTE: Termination of any unused motor leads must be  
insulated.  
4. Place unused blower speed tap on integrated control  
“PARK” terminal or insulate.  
5. Refer to blower speed selection chart on unit wiring  
diagram for desired heating or cooling speed. See  
Blower performance data beginning on the next page.  
6. Connect selected speed tap at control board speed  
terminal.  
7. Re-secure blower access panel.  
8. Turn on electrical power to furnace.  
9. Recheck temperature rise.  
Fan Control  
The fan ON time of 30 seconds is not adjustable. The fan  
OFF delay (amount of time that the blower operates after  
the heat demand has been satisfied) may be adjusted by  
changing the jumper position across the five pins on the  
integrated control. The unit is shipped with a factory heat  
fan OFF setting of 120 seconds. The fan OFF delay affects  
comfort and is adjustable to satisfy individual applications.  
Adjust the fan OFF delay to achieve a supply air temperature  
between 90° and 110° F at the moment that the blower is  
de-energized. Longer OFF delay settings provide lower  
return air temperatures; shorter settings provide higher  
return air temperatures. See Figure 51.  
Electronic Ignition  
The integrated control has an added feature of an internal  
Watchguard control. The feature serves as an automatic  
reset device for integrated control lockout caused by ignition  
failure. This type of lockout is usually due to low gas line  
pressure. After one hour of continuous thermostat demand  
for heat, the Watchguard will break and remake thermostat  
demand to the furnace and automatically reset the integrated  
control to begin the ignition sequence.  
HEAT FAN-OFF TIME IN SECONDS  
Exhaust and Air Intake Pipe  
1. Check exhaust and air intake connections for tightness  
and to make sure there is no blockage.  
2. Is pressure switch closed? Obstructed exhaust pipe  
will cause unit to shut off at pressure switch. Check  
termination for blockages.  
NO JUMPER  
To adjust fan−off timing, reposition jumper across pins to  
achieve desired setting.  
60 Second  
off Time  
90 Second  
off Time  
120 Second  
off Time  
180 Second  
off Time  
3. Obstructed pipe or termination may cause rollout  
switches to open. Reset manual flame rollout switches  
on burner box assembly if necessary.  
FIGURE 51  
506725-01  
Page 39 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER DATA A93DF1D / 92G1DF  
A93DF1D / 92G1DF 045*12B PERFORMANCE (Less Filter)  
A93DF1D / 92G1DF 090*16C PERFORMANCE (Less Filter)  
Air Volume / Watts at Various Blower Speeds  
Air Volume / Watts at Various Blower Speeds  
External  
External  
Static  
Medium-  
High  
Medium-  
Low  
Medium-  
High  
Medium-  
Low  
Static  
Pressure  
in. w.g.  
High  
Low  
High  
Low  
Pressure  
in. w.g.  
cfm Watts cfm Watts cfm Watts cfm Watts  
1615 650 1385 555 1205 465 1045 390  
1605 640 1375 545 1195 455 1035 380  
1500 620 1340 525 1165 445 1015 370  
1450 590 1290 490 1125 420 975 365  
1350 560 1235 480 1090 405 920 345  
1300 545 1170 450 1035 380 875 335  
1195 500 1095 425 990 365 840 320  
1140 485 1020 400 895 345 780 300  
1025 450 920 370 840 330 695 275  
945 435 800 335 700 295 605 250  
cfm Watts cfm Watts cfm Watts cfm Watts  
2145 900 1865 740 1545 635 1295 530  
2135 890 1855 730 1540 625 1290 520  
2065 845 1815 710 1525 600 1285 500  
2010 825 1760 685 1510 580 1275 485  
1930 775 1705 630 1495 575 1235 455  
1845 740 1645 610 1450 530 1215 450  
1745 700 1525 550 1380 505 1185 430  
1620 650 1460 535 1315 480 1110 405  
1450 585 1340 505 1220 445 1020 375  
1320 555 1130 450 1010 385 920 345  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
A93DF1D / 92G1DF 070*12B PERFORMANCE (Less Filter)  
A93DF1D / 92G1DF 110*20C PERFORMANCE (Less Filter)  
Air Volume / Watts at Various Blower Speeds  
External  
Air Volume / Watts at Various Blower Speeds  
External  
Medium-  
High  
Medium-  
Low  
Medium-  
High  
Medium-  
Low  
Static  
Pressure  
in. w.g.  
Static  
Pressure  
in. w.g.  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts  
1505 660 1310 570 1090 455 940 390  
1480 625 1295 550 1070 435 935 365  
1405 585 1255 515 1055 425 930 350  
1355 580 1225 475 1045 405 900 330  
1305 540 1165 470 1010 385 890 325  
1270 525 1110 425 975 370 835 305  
1175 500 1080 415 925 345 815 290  
1105 460 1000 395 855 320 745 270  
1040 440 925 365 790 300 670 250  
920 400 825 335 680 270 560 225  
cfm Watts cfm Watts cfm Watts cfm Watts  
2410 1390 2190 1080 1860 910 1560 735  
2405 1385 2180 1070 1855 905 1555 730  
2285 1345 2120 1030 1850 865 1540 720  
2220 1315 2015 1005 1770 840 1535 705  
2185 1295 1950 955 1750 815 1530 685  
2045 1240 1830 925 1680 790 1500 660  
1965 1220 1710 890 1575 755 1445 640  
1820 1165 1610 850 1495 720 1370 615  
1625 1155 1510 820 1400 695 1315 595  
1455 1110 1390 790 1350 660 1210 565  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES: All air data is measured external to unit without filter (not furnished - field provided)  
Page 40 of 48  
Issue 1109  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
BLOWER DATA A95DF1D / 95G1DF  
A95DF1D / 95G1DF 045*12B PERFORMANCE (Less Filter)  
A95DF1D / 95G1DF 090*20C PERFORMANCE (Less Filter)  
Air Volume / Watts at Various Blower Speeds  
Air Volume / Watts at Various Blower Speeds  
External  
External  
Static  
Medium-  
High  
Medium-  
Low  
Medium-  
High  
Medium-  
Low  
Static  
Pressure  
in. w.g.  
High  
Low  
High  
Low  
Pressure  
in. w.g.  
cfm Watts cfm Watts cfm Watts cfm Watts  
1615 650 1385 555 1205 465 1045 390  
1605 640 1380 545 1195 455 1035 380  
1500 620 1345 525 1165 445 1015 370  
1450 590 1290 490 1125 420 975 365  
1350 560 1235 480 1090 405 920 345  
1300 545 1170 450 1035 380 880 330  
1195 500 1095 425 990 365 840 320  
1140 480 1020 395 895 345 780 300  
1025 450 920 370 840 330 695 270  
945 430 800 335 700 290 605 250  
cfm Watts cfm Watts cfm Watts cfm Watts  
2305 1255 2145 950 1900 810 1515 670  
2295 1240 2135 940 1885 795 1500 665  
2200 1220 2085 915 1865 775 1525 655  
2160 1210 1990 875 1830 755 1545 640  
2055 1170 1935 865 1790 725 1530 620  
1970 1130 1855 835 1705 700 1500 600  
1890 1105 1765 805 1635 675 1495 580  
1775 1075 1680 785 1565 655 1430 560  
1690 1050 1590 760 1485 630 1370 540  
1580 1010 1485 735 1405 610 1270 510  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
A95DF1D / 95G1DF 070*12B PERFORMANCE (Less Filter)  
A95DF1D /95G1DF 110*20C PERFORMANCE (Less Filter)  
Air Volume / Watts at Various Blower Speeds  
External  
Air Volume / Watts at Various Blower Speeds  
External  
Medium-  
High  
Medium-  
Low  
Medium-  
High  
Medium-  
Low  
Static  
Pressure  
in. w.g.  
Static  
Pressure  
in. w.g.  
High  
Low  
High  
Low  
cfm Watts cfm Watts cfm Watts cfm Watts  
1515 620 1315 545 1095 465 910 390  
1490 585 1300 525 1075 445 890 375  
1445 555 1275 500 1065 425 910 360  
1380 520 1240 470 1060 400 900 340  
1315 495 1190 440 1020 385 875 325  
1270 470 1145 420 995 355 870 310  
1155 435 1075 390 940 330 820 300  
1075 415 1000 355 875 310 765 270  
975 380 900 325 800 285 715 250  
900 365 800 300 675 255 615 225  
cfm Watts cfm Watts cfm Watts cfm Watts  
2375 1250 2205 915 1975 785 1630 640  
2365 1235 2195 905 1960 775 1625 635  
2275 1200 2125 890 1950 760 1635 625  
2200 1180 2060 880 1900 735 1620 610  
2115 1150 1995 850 1845 710 1620 600  
2040 1115 1940 835 1795 695 1585 580  
1955 1090 1855 810 1745 670 1540 565  
1860 1070 1730 765 1640 650 1515 550  
1735 1030 1620 740 1590 620 1415 535  
1640 1010 1535 715 1480 600 1330 510  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
0.00  
0.10  
0.20  
0.30  
0.40  
0.50  
0.60  
0.70  
0.80  
0.90  
NOTES: All air data is measured external to unit without filter (not furnished - field provided)  
506725-01  
Page 41 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Service  
Winterizing and Condensate Trap Care  
1. Turn off power to the furnace.  
2. Have a shallow pan ready to empty condensate water.  
3. Remove the clean out cap from the condensate trap  
and empty water. Inspect the trap then reinstall the clean  
out cap.  
WARNING  
ELECTRICAL SHOCK, FIRE,  
OR EXPLOSION HAZARD.  
Failure to follow safety warnings exactly could result in  
dangerous operation, serious injury, death or property  
damage.  
Cleaning Heat Exchanger  
If cleaning the heat exchanger becomes necessary, follow  
the below procedures and refer to Figure 1 when  
disassembling unit. Use papers or protective covering in  
front of furnace while removing heat exchanger assembly.  
1. Turn off electrical and gas supplies to the furnace.  
2. Remove the furnace access panels.  
3. Disconnect the 2 wires from the gas valve.  
4. Remove gas supply line connected to gas valve.  
Remove gas valve/manifold assembly.  
Improper servicing could result in dangerous operation,  
serious injury, death, or property damage.  
Before servicing, disconnect all electrical power to  
furnace.  
When servicing controls, label all wires prior to  
disconnecting. Take care to reconnect wires correctly.  
Verify proper operation after servicing.  
5. Remove sensor wire from sensor. Disconnect 2 pin  
plug from the ignitor.  
6. Disconnect wires from flame rollout switches.  
7. Loosen clamps at vent elbow. Disconnect condensate  
drain tubing from flue collar and remove the vent elbow.  
8. Remove four burner box screws at the vestibule panel  
and remove burner box. Set burner box assembly aside.  
At the beginning of each heating season, system should be  
checked as follows by a qualified service technician:  
Blower  
Check the blower wheel for debris and clean if necessary.  
The blower motors are prelubricated for extended bearing  
life. No further lubrication is needed.  
NOTE: If necessary, clean burners at this time. Follow  
procedures outlined in Burner Cleaning section.  
9. Mark and disconnect all combustion air pressure tubing  
from cold end header collector box.  
10. Mark and remove wires from pressure switches.  
Remove pressure switches. Keep tubing attached to  
pressure switches.  
11. Disconnect the plug from the combustion air inducer.  
Remove two screws which secure combustion air  
inducer to collector box. Remove combustion air inducer  
assembly. Remove ground wire from vest panel.  
12. Remove electrical junction box from the side of the  
furnace.  
13. Mark and disconnect any remaining wiring to heating  
compartment components. Disengage strain relief  
bushing and pull wiring and bushing through the hole in  
the blower deck.  
14. Remove the primary limit from the vestibule panel.  
15. Remove two screws from the front cabinet flange at the  
blower deck. Spread cabinet sides slightly to allow  
clearance for removal of heat exchanger.  
16. Remove screws along vestibule sides and bottom which  
secure vestibule panel and heat exchanger assembly  
to cabinet. Remove two screws from blower rail which  
secure bottom heat exchanger flange. Remove heat  
exchanger from furnace cabinet.  
17. Back wash heat exchanger with soapy water solution or  
steam. If steam is used it must be below 275°F (135°C).  
18. Thoroughly rinse and drain the heat exchanger. Soap  
solutions can be corrosive. Take care to rinse entire  
assembly.  
WARNING  
The blower access panel must be securely in place when  
the blower and burners are operating. Gas fumes, which  
could contain carbon monoxide, can be drawn into living  
space resulting in personal injury or death.  
Filters  
All air filters are installed external to the unit. Filters should  
be inspected monthly. Clean or replace the filters when  
necessary to ensure proper furnace operation. Table 3 lists  
recommended filter sizes.  
Exhaust and air intake pipes  
Check the exhaust and air intake pipes and all connections  
for tightness and to make sure there is no blockage.  
NOTE: After any heavy snow, ice or frozen fog event the  
furnace vent pipes may become restricted. Always check  
the vent system and remove any snow or ice that may be  
obstructing the plastic intake or exhaust pipes.  
Electrical  
1. Check all wiring for loose connections.  
2. Check for the correct voltage at the furnace (furnace  
operating). Correct voltage is 120 VAC ± 10%.  
3. Check amp-draw on the blower motor with the blower  
compartment access panel in place.  
Motor Nameplate__________Actual__________  
Page 42 of 48  
Issue 1109  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19. Reinstall heat exchanger into cabinet making sure that  
the clamshells of the heat exchanger assembly are  
resting on the support located at the rear of the cabinet.  
Remove the indoor blower to view this area through the  
blower opening.  
Cleaning the Burner Assembly  
1. Turn off electrical and gas power supplies to furnace.  
Remove upper and lower furnace access panels.  
2. Disconnect the 2 pin plug from the gas valve.  
3. Remove the burner box cover.  
20. Resecure the supporting screws along the vestibule  
sides and bottom to the cabinet. Reinstall blower and  
mounting screws.  
21. Reinstall cabinet screws on front flange at blower deck.  
22. Reinstall the primary limit on the vestibule panel.  
23. Route heating component wiring through hole in blower  
deck and reinsert strain relief bushing.  
4. Disconnect the gas supply line from the gas valve.  
Remove gas valve/manifold assembly.  
5. Mark and disconnect sensor wire from the sensor.  
Disconnect 2 pin plug from the ignitor at the burner box.  
6. Remove four screws which secure burner box assembly  
to vest panel. Remove burner box from the unit.  
7. Use the soft brush attachment on a vacuum cleaner to  
gently clean the face of the burners. Visually inspect  
the inside of the burners and crossovers for any blockage  
caused by foreign matter. Remove any blockage.  
8. Reconnect the sensor wire and reconnect the 2 pin plug  
to the ignitor wiring harness.  
24. Reinstall electrical junction box.  
25. Reinstall the combustion air inducer. Reconnect the  
combustion air inducer to the wire harness.  
26. Reinstall pressure switches and reconnect pressure  
switch wiring.  
27. Carefully connect combustion air pressure switch hosing  
from pressure switches to proper stubs on cold end  
header collector box.  
9. Reinstall the burner box assembly using the existing four  
screws. Make sure that the burners line up in the  
center of the burner ports.  
10. Reinstall the gas valve manifold assembly. Reconnect  
the gas supply line to the gas valve. Reinstall the burner  
box cover.  
28. Reinstall condensate trap.  
29. Reconnect exhaust piping and exhaust drain tubing.  
30. Reinstall burner box assembly in vestibule area.  
31. Reconnect flame rollout switch wires.  
11. Reconnect 2 pin plug to gas valve.  
32. Reconnect sensor wire and reconnect 2 pin plug from  
ignitor.  
33. Secure burner box assembly to vestibule panel using  
four existing screws. Make sure burners line up in  
center of burner ports.  
34. Reinstall gas valve manifold assembly. Reconnect gas  
supply line to gas valve.  
35. Reconnect 2 wires to gas valve.  
12. Replace the blower compartment access panel.  
13. Refer to instruction on verifying gas and electrical  
connections when re-establishing supplies.  
14. Follow lighting instructions to light and operate furnace  
for 5 minutes to ensure that heat exchanger is clean  
and dry and that furnace is operating properly.  
15. Replace heating compartment access panel.  
36. Replace the blower compartment access panel.  
37. Refer to instruction on verifying gas and electrical  
connections when re-establishing supplies.  
38. Follow lighting instructions to light and operate furnace  
for 5 minutes to ensure that heat exchanger is clean  
and dry and that furnace is operating properly.  
39. Replace heating compartment access panel.  
506725-01  
Page 43 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Planned Service  
DIAGNOSTIC CODES  
A service technician should check the following items during  
an annual inspection. Power to the unit must be shut off for  
safety.  
Fresh air grilles and louvers (on the unit and in the room  
where the furnace is installed) - Must be open and  
unobstructed to provide combustion air.  
Burners - Must be inspected for rust, dirt, or signs of water.  
Vent pipe - Must be inspected for signs of water, cracked,  
damaged or sagging pipe, or disconnected joints.  
Unit appearance - Must be inspected for rust, dirt, signs of  
water, burnt or damaged wires, or components.  
Blower access door - Must be properly in place and provide  
a seal between the return air and the room where the furnace  
is installed.  
Return air duct - Must be properly attached and provide  
an air seal to the unit.  
Operating performance - Unit must be observed during  
operation to monitor proper performance of the unit and  
the vent system.  
Combustion gases - Flue products must be analyzed and  
compared to the unit specifications.  
Problems detected during the inspection may make it  
necessary to temporarily shut down the furnace until the  
items can be repaired or replaced.  
Instruct the homeowners to pay attention to their  
furnace. Situations can arise between annual furnace  
inspections that may result in unsafe operation. For  
instance, items innocently stored next to the furnace may  
obstruct the combustion air supply. This could cause  
incomplete combustion and the production of carbon  
monoxide gas.  
Page 44 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  
REPAIR PARTS LIST  
The following repair parts are available through Allied Air dealers. When ordering parts, include the complete furnace model  
number listed on the CSAnameplate. Example: A93DF045P36B-01. All service must be performed by a licensed professional  
installer (or equivalent), service agency, or gas supplier.  
Cabinet Parts  
Heating Parts  
Heating Compartment Access Panel  
Blower Compartment Access Panel  
Top Cap  
Flame Sensor  
Heat Exchanger Assembly  
Gas Manifold  
Combustion Air Inducer  
Gas Valve  
Main Burner Cluster  
Main Burner Orifices  
Control Panel Parts  
Transformer  
Integrated Control Board  
Door Interlock Switch  
Pressure Switch  
Ignitor  
Primary Limit Control  
Blower Parts  
Blower Wheel  
Flame Rollout Switches  
Motor  
Motor Mounting Frame  
Motor Capacitor  
Blower Housing Cutoff Plate  
506725-01  
Page 45 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Start−Up & Performance Check List  
UNIT SET UP  
Furnace:  
Model Number_______________  
Serial Number_________________  
SUPPLY  
AIR  
Line Voltage  
2
4
1
GAS SUPPLY  
LP Propane Gas  
Natural Gas  
3
Piping Connections Tight  
Leak Tested  
Flter  
RETURN AIR  
2
1
Gas Supply Pressure  
DUCT SYSTEM  
3
1
SUPPLY AIR DUCT  
Sealed  
Insulated (if necessary)  
RETURN DUCT  
2
INTAKE / EXHAUST PIPE  
Sealed  
All Joints Primed and Glued  
Filter Installed and Clean  
Terminations Installed Properly  
Grilles Unobstructed  
Horizontal Pipes Sloped (if applicable)  
Condensate Trap Primed / Line Sloped  
VOLTAGE CHECK  
Supply Voltage _____  
4
Electrical Connections Tight  
Pipes Supported  
Heat Cable Installed and Operable (if applicable)  
Page 46 of 48  
Issue 1109  
506725-01  
Download from Www.Somanuals.com. All Manuals Search And Download.  
UNIT OPERATION  
HEATING MODE  
COOLING MODE  
1
2
GAS MANIFOLD PRESSURE “W.C.” ______  
3
4
INDOOR BLOWER AMPS ______  
COMBUSTION SAMPLE CO ______%  
CO _____ PPM  
TEMPERATURE DROP  
2
______  
Return Duct Temperature  
Supply Duct Temperature  
_
=
3
4
INDOOR BLOWER AMPS ______  
______  
______  
Temperature Drop  
TEMPERATURE RISE  
5
TOTAL EXTERNAL STATIC (dry coil)  
Supply Duct Temperature _  
______  
______  
Supply External Static  
Return External Static  
Total External Static  
DRAIN LINE  
Return Duct Temperature  
Temperature Rise  
______  
______  
______  
+
=
=
______  
5
TOTAL EXTERNAL STATIC  
Supply External Static  
Return External Static  
8
9
______  
______  
Leak Free  
+
=
Total External Static  
CONDENSATE LINE  
Leak Free  
______  
6
7
THERMOSTAT  
Adjusted and Programmed  
Explained Operation to Owner  
VENT PIPE  
Leak Free  
Combustion CO  
2
2
7
SUPPLY  
AIR  
Thermostat  
Temperatures  
8
Gas Manifold Pressure  
9
4
1
Blower Motor Amps  
6
3
Duct Static  
5
RETURN AIR  
Contractor’s: Name______________________________________Telephone________________Checklist Completed____________________  
Job Address_______________________________________________________Technician’s Name___________________________________  
506725-01  
Page 47 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
REQUIREMENTS for COMMONWEALTH of MASSACHUSETTS  
4. INSPECTION. The state or local gas inspector of the  
Modifications to NFPA-54, Chapter 10  
Revise NFPA-54 section 10.8.3 to add the following  
requirements:  
side wall, horizontally vented, gas-fueled equipment shall  
not approve the installation unless, upon inspection, the  
inspector observes carbon monoxide detectors and  
signage installed in accordance with the provisions of  
248 CMR 5.08(2)(a) 1 through 4.  
For all side wall, horizontally vented, gas fueled equipment  
installed in every dwelling, building or structure used in whole  
or in part for residential purposes, including those owned or  
operated by the Commonwealth and where the side wall  
exhaust vent termination is less than seven (7) feet above  
the finished grade in the area of the venting, including but  
not limited to decks and porches, the following requirements  
shall be satisfied:  
1. INSTALLATION OF CARBON MONOXIDE  
DETECTORS. At the time of installation of the side wall,  
horizontally vented, gas-fueled equipment, the installing  
plumber or gas fitter shall observe that a hard wired  
carbon monoxide detector with an alarm and battery  
backup is installed on the floor level where the gas  
equipment is to be installed. In addition, the installing  
plumber or gas fitter shall observe that a battery operated  
or hard wired carbon monoxide detector with an alarm  
is installed on each additional level of the dwelling,  
building or structure served by the side wall, horizontally  
vented, gas fueled equipment. It shall be the  
responsibility of the property owner to secure the  
services of qualified licensed professionals for the  
installation of hard wired carbon monoxide detectors.  
a. In the event that the side wall, horizontally vented,  
gas fueled equipment is installed in a crawl space  
or an attic, the hard wired carbon monoxide detector  
with alarm and battery backup may be installed on  
the next adjacent floor level.  
EXEMPTIONS: The following equipment is exempt from  
24 CMR 5.08(2)(a) 1 through 4:  
1. The equipment listed in Chapter 10 entitled “Equipment  
Not Required to Be Vented” in the most current edition  
of NFPA 54 as adopted by the Board; and  
2. Product Approved side wall, horizontally vented, gas  
fueled equipment installed in a room or structure  
separate from the dwelling, building or structure used in  
whole or in part for residential purposes.  
MANUFACTURER REQUIREMENTS -  
GAS EQUIPMENT VENTING SYSTEM PROVIDED.  
When the manufacturer of Product Approved side wall,  
horizontally vented, gas fueled equipment provides a venting  
system design or venting system components with the  
equipment, the instructions provided by the manufacturer  
for installation of the equipment and the venting system shall  
include:  
1. Detailed instructions for the installation of the venting  
system design or the venting system components: and  
2. A complete parts list for the venting system design or  
venting system.  
MANUFACTURER REQUIREMENTS -  
b. In the event that the requirements of this subdivision  
cannot be met at the time of completion of  
GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED.  
When the manufacturer of Product Approved sidewall,  
horizontally vented, gas fueled equipment does not provide  
the parts for venting the flue gases, but identifies “special  
venting systems,” the following requirements shall be  
satisfied by the manufacturer:  
1. The referenced “special venting system” instructions  
shall be included with the appliance or equipment  
installation instructions; and  
2. The “special venting systems” shall be Product  
Approved by the Board, and the instructions for that  
system shall include a parts list and detailed installation  
instructions.  
A copy of all installation instructions for all Product  
Approved side wall, horizontally vented, gas fueled  
equipment, all venting instructions, all parts lists for  
venting instructions, and/or all venting design  
instructions shall remain with the appliance or  
equipment at the completion of the installation.  
installation, the owner shall have a period of thirty  
(30) days to comply with the above requirements;  
provided, however, that during said thirty (30) day  
period, a battery operated carbon monoxide  
detector with an alarm shall be installed.  
2. APPROVED CARBON MONOXIDE DETECTORS.  
Each carbon monoxide detector as required in  
accordance with the above provisions shall comply with  
NFPA720 and beANSI/UL 2034 listed and IAS certified.  
3. SIGNAGE. A metal or plastic identification plate shall  
be permanently mounted to the exterior of the building  
at a minimum height of eight (8) feet above grade directly  
in line with the exhaust vent terminal for the horizontally  
vented, gas fueled heating appliance or equipment. The  
sign shall read, in print size no less than one half (1/2)  
inch in size, “GAS VENT DIRECTLY BELOW. KEEP  
CLEAR OF ALL OBSTRUCTIONS.”  
Page 48 of 48  
Issue 1109  
Download from Www.Somanuals.com. All Manuals Search And Download.  
506725-01  

Addonics Technologies Computer Drive HDMU3 User Manual
AEG Oven BP5003001 User Manual
Airlink101 TV Converter Box ATVC101 User Manual
Allied Telesis Switch AT LE700 User Manual
Ask Proxima Projector Pro AV 9410 User Manual
Audiovox Car Stereo System AVD200T User Manual
Audiovox Radio GMRS 2000 User Manual
Avet Reels Fishing Equipment MXJ 581 User Manual
Axis Communications Security Camera M3014 User Manual
Beckett Water Gardening Outdoor Fountain CGFK60 User Manual