AEG Network Cables Thyro P User Manual

BETRIEBSANLEITUNG/OPERATING INSTRUCTIONS  
Thyro-P  
Thyristor-Leistungssteller  
kommunikationsfähig  
Thyristor Power Controller  
Communication Capable  
DE EN  
Download from Www.Somanuals.com. All Manuals Search And Download.  
3
MALOPERATION AND THE RESULTS  
With maloperation, it is possible that power, voltage or current levels which are higher than planned  
reach the Thyristor Power Controller or load. On principle, this can lead to the Power Controller or  
load being damaged. It is important that preset parameters are not adjusted in any way that may  
cause the Power Controller to overload.  
TRANSPORT  
Thyristor Power Controllers are only to be transported in their original packaging (protection  
against damage, e.g. due to impact, being knocked, soiling).  
INSTALLATION  
• If the Thyristor Power Controller is brought into the operations room from a cold environment,  
moisture can occur. Prior to it being commissioned, the Thyristor Power Controller must be  
absolutely dry. For this reason, wait for a minimum period of two hours before commissioning.  
• Install the device upright.  
CONNECTION  
• Prior to connection, it must be ensured that the voltage information on the type plate corres-  
ponds with the mains voltage.  
• The electrical connection is carried out at the designated points with the required cross section  
and the appropriate screw cross sections.  
OPERATION  
• The Thyristor Power Controller may only be connected to the mains voltage if it has been ensured  
that any hazard to people and system, especially in the load section, has been eliminated.  
• Protect the device from dust and moisture.  
• Do not block vents.  
MAINTENANCE, SERVICE, MALFUNCTIONS  
The icons used below are explained in the chapter safety regulations.  
CAUTION  
Should smoke, smell or fire occur the Power Controller must be disconnected from the mains  
immediately.  
CAUTION  
For maintenance and repair work, the Power Controller must be disconnected from all external vol-  
tage sources and protected against restarting. Make sure to wait minimum 1 minute after switch-off  
(discharge time of the attenuation capacitors). The voltage-free state is to be determined by means  
of suitable measuring instruments. This work is only to be carried out by a skilled electrician. The  
electrical regulations which are locally valid are to be adhered to.  
CAUTION  
The Thyristor Power Controller contains hazardous voltages. Repairs may generally only be perfor-  
med by qualified and trained maintenance personnel.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
4
CAUTION  
Hazard of electrical shock. Even after disconnection from the mains voltage, capacitors may still  
contain a dangerously high power level.  
CAUTION  
Hazard of electrical shock. Even when the Thyristor Power Controller is not triggered, the load  
circuit is not disconnected from the mains.  
ATTENTION  
Different components in the power section are screwed in place using exact torques. For safety  
reasons, power components repairs must be performed by AEG Power Solutions GmbH.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
5
TABLE OF CONTENTS  
Safety instructions  
Schedule of Illustrations and Tables  
Safety Regulations  
2
7
8
Remarks on the present operating instructions and Thyro-P  
11  
1. Introduction  
13  
13  
13  
14  
1.1 General  
1.2 Specific characteristics  
1.3 Type designation  
2. Functions  
15  
15  
16  
18  
18  
19  
19  
19  
20  
21  
24  
2.1 Overview of operating modes  
2.2 Set point control characteristic  
2.3 Control types  
2.3.1 Controlled value  
2.4 Indications  
2.4.1 LED indications  
2.4.2 Relay indications K1-K2-K3  
2.5 Monitoring  
2.5.1 Load monitoring  
2.5.2 Ventilator monitoring  
3. Mode of Operation  
25  
25  
25  
26  
27  
32  
32  
33  
33  
33  
34  
34  
34  
36  
3.1 Local operating and display unit (LBA)  
3.1.1 LBA keyboard functions  
3.1.2 LBA main menu  
3.1.3 LBA submenus  
3.1.4 Copying function using the LBA  
3.1.5 Operation display  
3.1.6 Line diagram  
3.1.7 Last function  
3.1.8 Status line  
3.1.9 LBA submenus with password protection  
3.2 Cabinet installation kit (SEK)  
3.3 Thyro-Tool Family  
3.4 Diagnosis / fault indications  
4. External Connections  
4.1 Power supply for Thyro-P  
4.2 Power supply for the control device A70  
4.3 Power supply for the ventilator  
4.4 RESET  
38  
38  
38  
38  
39  
39  
39  
40  
40  
40  
40  
41  
41  
42  
44  
45  
4.4.1 Software-RESET  
4.5 Controller lock  
4.6 QUIT  
4.7 Set point value inputs  
4.8 ASM input  
4.9 Analog outputs  
4.10 Current transformer  
4.11 Voltage transformer  
4.12 Other connections and terminal strips  
4.13 Synchronization  
4.14 Component mounting diagram control device  
5. Interfaces  
46  
47  
5.1 RS 232 interface  
Download from Www.Somanuals.com. All Manuals Search And Download.  
6
5.2 Fibre optic interfaces  
5.2.1 Fibre optic distribution system  
5.3 Bus interfaces (option)  
5.3.1 Profibus  
48  
48  
51  
51  
55  
55  
5.3.2 Modbus RTU  
5.3.3 DeviceNet  
6. Mains Load Optimization  
6.1 SYT-9 procedure  
56  
56  
56  
56  
6.2 Software synchronization  
6.3 ASM procedure (patented)  
7. Connecting diagrams  
7.1 1-phase  
58  
58  
59  
60  
7.2 2-phase  
7.3 3-phase  
8. Special Remarks  
8.1 Installation  
8.2 Comissioning  
8.3 Service  
61  
61  
61  
62  
62  
8.4 Checklist  
9. Type Overview  
64  
64  
65  
66  
9.1 Type range 400 volts  
9.2 Type range 500 volts  
9.3 Type range 690 volts  
10. Specifications  
67  
70  
83  
84  
11. Dimensional Drawings  
12. Accessories and Options  
13. Approvals and Conformities  
Download from Www.Somanuals.com. All Manuals Search And Download.  
7
SCHEDULE OF ILLUSTRATIONS AND TABLES  
Fig. 1  
Fig. 2  
Fig. 3  
Fig. 4  
Fig. 5  
Fig. 6  
Fig. 7  
Fig. 8  
Fig. 9  
Control characteristic for U control  
Total set point  
Switch-on fault bridging  
Absolute value monitoring  
Relative monitoring  
Local operating and display unit (LBA)  
Operation display  
17  
17  
20  
21  
21  
25  
32  
34  
35  
45  
46  
47  
48  
49  
50  
52  
53  
54  
55  
57  
Cabinet installation kit  
Example for the user interface Thyro-Tool Familiy  
Fig. 10 File component mounting diagram control device  
Fig. 11 Interfaces of Thyro-P  
Fig. 12 Connection of a PC to Thyro-P via RS 232  
Fig. 13 X10-allocation  
Fig. 14 Signal converter RS 232/fibre optic  
Fig. 15 Schematic diagram fibre optic Thyro-P with LLV and PC  
Fig. 16 Profibus slot card  
Fig. 17 Special function Motorpoti  
Fig. 18 Special inputs  
Fig. 19 Modbus slot card  
Fig. 20 ASM wiring  
Tab. 1  
Tab. 2  
Tab. 3  
Tab. 4  
Tab. 5  
Tab. 6  
Tab. 7  
Tab. 8  
Tab. 9  
Behaviour in case of load change  
19  
22  
23  
23  
26  
27  
32  
33  
33  
37  
38  
39  
39  
40  
41  
41  
42  
42  
43  
43  
44  
44  
49  
51  
53  
Partial load breakdown with heating elements switched in parallel, undercurrent  
Partial short-circuit with heating elements switched in series, overcurrent  
Overview monitoring  
Functions of the LBA-keys  
LBA main menu  
Copying function using the LBA  
Line diagram time base  
Elements of the status line  
Tab. 10 Allocation of the message register  
Tab. 11 Terminal strip X1  
Tab. 12 RESET  
Tab. 13 Controller lock  
Tab. 14 QUIT  
Tab. 15 Current transformer  
Tab. 16 Voltage transformer  
Tab. 17 Voltage measurement jumper  
Tab. 18 Terminal strip X2 for K1, K2, K3  
Tab. 19 Terminal strip X5  
Tab. 20 Terminal strip X6  
Tab. 21 Terminal strip X7  
Tab. 22 Synchronization jumper  
Tab. 23 Fibre optic distances  
Tab. 24 Profibus baud rates  
Tab. 25 Pin assignment X21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
8
SAFETY REGULATIONS  
IMPORTANT INSTRUCTIONS AND EXPLANATIONS  
Operation and maintenance according to regulation as well as observance of the listed safety  
regulations is required for protection of the staff and to preserve readiness to operate. Personnel  
installing/uninstalling the devices, commissioning them, operating them, maintaining them must  
know and observe these safety regulations. All work may only be performed by specialist personnel  
trained for this purpose using the tools, devices, test instruments and consumables provided for  
this purpose and in good shape.  
In the present operating instructions, important instructions are marked using the terms  
„CAUTION“, „ATTENTION“ and „REMARK“ as well as using the icons explained below.  
CAUTION  
This instruction shows work and operating procedures to be observed exactly to exclude hazards  
for persons.  
ATTENTION  
This instruction refers to work and operating procedures to be observed exactly to avoid damage  
or destruction of Thyro-P or parts thereof.  
REMARK  
This is where remarks about technical requirements and additional information is given, which the  
user has to observe.  
ACCIDENT PREVENTION RULES  
The accident prevention rules of the application country and the generally applicable safety  
regulations must be observed in any case.  
CAUTION  
Before starting any work on Thyro-P, the following safety regulations must be observed:  
• switch voltage-free,  
• secure against switching on,  
• determine if it is voltage-free,  
• ground and short-circuit it,  
• cover or block neighboring parts under voltage.  
QUALIFIED PERSONNEL  
Thyro-P may only be transported, installed, connected, commissioned, maintained and operated  
by specialists in command of the respective applicable safety and installation regulations. All work  
must be monitored by the responsible specialist personnel. The specialist personnel must be  
authorized for the work required by the person responsible for the safety of the system.  
Specialists are persons who  
- have received training and have experience in the respective field of work,  
- know the respective applicable standards, regulations, terms and accident prevention rules,  
- have been familiarized with the function and operating conditions of Thyro-P,  
- are able to detect and avoid hazards.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
9
WORK OBSERVING SAFETY REGULATIONS  
Before removing safety installations for performance of maintenance and repair work or other work,  
measures due to operation must be initiated.  
Work observing safety regulations also means to point out faulty behaviour to colleagues and to  
notify the office or person responsible about defects detected.  
INTENDED USE  
CAUTION  
The Thyristor Power Controller may only be employed in the sense of its purpose of use (see the  
section of the chapter safety instructions under the same name), otherwise hazards for persons (for  
instance electrical shock, burns) and systems (for instance overload) may occur.  
Any unauthorized reconstruction and modification of Thyro-P, use of spare and exchange parts not  
approved by AEG Power Solutions as well as any other use of Thyro-P is not allowed. The person  
responsible for the system must ensure that  
- hints on safety and operating instructions are available and observed,  
- operation conditions and specifications are observed,  
- protective installations are used,  
- required maintenance work is performed,  
- maintenance personnel are immediately notified or Thyro-P is immediately put out of commission  
if abnormal voltages or noises, higher temperatures, vibrations or similar occur to determine the  
causes.  
These operating instructions contain all information required by specialists for use of Thyro-P.  
Additional information and hints for unqualified persons and for use of Thyro-P outside of industrial  
installations are not contained in these operating instructions.  
The warranty obligation of the manufacturer applies only if these operating instructions are observed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
10  
LIABILITY  
In case of use of Thyro-P for applications not provided for by the manufacturer, no liability is  
assumed. The responsiblity for required measures to avoid hazards to persons and property is  
borne by the operator respectively the user. In case of complaints, please immediately notify us  
stating:  
- type name,  
- production number,  
- objection,  
- duration of use,  
- ambient conditions,  
- operating mode.  
GUIDELINES  
The devices of the type range Thyro-P conform to the currently applicable EN 50178 and  
EN 60146-1-1.  
The CE mark on the device confirms observation of the general EG guidelines for 2006/95/EG –  
low voltage and for 2004/108/EG – electromagnet compatibility, if the instructions on installation  
and commissioning described in the operating instructions are observed.  
Regulations and definitions for qualified personnel are contained in DIN 57105/VDE 0105 Part 1.  
Safe isolation to VDE 0160 (EN 50178 Chapter 3)  
Download from Www.Somanuals.com. All Manuals Search And Download.  
11  
REMARKS ON THE PRESENT OPERATING INSTRUCTIONS AND THYRO-P  
VALIDITY  
These operating instructions refer to latest technical specification of Thyro-P at the time of publi-  
cation and are for information purposes only. Every effort has been taken to ensure the accuracy of  
this specification, however, in order to maintain our technological lead and for product enhance-  
ment, we are continually improving our products which could, without notice, result in amendments  
or omissions to this specification. AEG PS cannot accept responsibility for damage, injury, loss or  
expenses resulting therefrom.  
HANDLING  
These operating instructions for Thyro-P are organized so that all work required for commissioning,  
maintenance and repair may be performed by corresponding specialist personnel.  
If hazards to personnel and property cannot be excluded for certain work, then this work is marked  
using certain icons. The meaning of these icons may be found in the prior chapter safety regula-  
tions.  
ABBREVIATIONS  
In this description, the following specific abbreviations are used:  
AEG PS  
ASM  
=
=
AEG Power Solutions GmbH  
automatic synchronization in multiple Power Controller application  
(dynamic network load optimization)  
data logger (fault storage)  
lokal operating and display unit  
cabinet installation kit  
DaLo  
LBA  
SEK  
LL  
=
=
=
=
=
=
=
=
=
=
fibre optic  
LLS  
fibre optic transmitter  
LLE  
fibre optic receiver  
LLV.V  
LLV.4  
SYT  
TAKT  
fibre optic distribution supply  
fibre optic distribution, 4-fold  
synchronized clock  
Pulse full cycle  
WARRANTY  
Customer shall provide written particulars, enclosing the delivery note, within 8 working days to  
AEG PS on becoming aware of any defects in the goods during the Warranty period and shall use  
its best endeavours to provide AEG PS with all necessary access, facilities and information to  
enable AEG PS to ascertain or verify the nature and cause of the defect and carry out its warranty  
obligations.  
If goods are found not to be defective or if any defect is attributable to Customer’s design or mate-  
rial in operation of the goods, AEG PS will levy a testing charge and where relevant will return the  
goods to Customer at Customer’s expense, and shall be entitled to payment in advance of the  
whole testing and transport charge before such return.  
AEG PS accepts no liability for defects caused by the Customer’s design or installation of the  
goods; or if the goods have been modified or repaired otherwise than as authorised in writing by  
AEG PS; or if the defect arises because of the fitting of the goods to unsuitable equipment.  
AEG PS will cancel all possible obligations incurred by AEG PS and its dealers, such as warranty  
commitments, service agreements, etc., without prior notice if other than original AEG spare parts  
or spare parts purchased from AEG PS are used for maintenance or repair.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
12  
SERVICE HOTLINE  
Our service is available to you through the following hotline:  
AEG Power Solutions GmbH  
Emil-Siepmann-Straße 32  
D-59581 Warstein  
Phone +49 (0) 2902 763-100  
INTERNET  
Further information on our company or our products can be found on the internet under  
COPYRIGHT  
Passing on, duplication and/or takeover of these operating instructions using electronic or mechani-  
cal means, even in excerpts, is subject to express prior written approval of AEG PS.  
© Copyright AEG Power Solutions 2012. All rights reserved.  
Copyright notice  
Thyro-P is an internationally registered trademark of AEG Power Solutions GmbH.  
Windows and Windows NT are registered trademarks of Microsoft Corporation.  
All other company and product names are (registered) trademarks of their respective owners.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
13  
1. INTRODUCTION  
For transport, assembly, installation, commissioning, operation and decommissioning, the safety  
instructions contained in these operating instructions must be applied in any case and made  
available to all persons handling this product.  
CAUTION  
It is important that preset parameters are not adjusted in any way that may cause the Power Con-  
troller to overload. In case of uncertainties or missing information, please contact your supplier.  
1.1 GENERAL  
Thyro-P is a Thyristor Power Controller able to communicate. Below, it is also referred to simply  
as Power Controller. It may be employed in any place where voltage, current or power has to be  
controlled or regulated in processing technology. Several modes of operation and control, good  
coupling ability to process and automation technology, high control precision by application of a  
32 bit RISC processor and simple handling ensure that Thyro-P is suitable for new applications as  
well.  
Thyro-P is suitable for  
• direct supply of ohmic loads  
• for loads with large Rhot/Rcold ratio  
• as primary Power Controller for a transformer with subsequent load  
Due to use of state-of-the-art thyristors, the Thyristor Power Controller Thyro-P has a type range  
up to 2900A, the nominal design loads reach up to about 2860kW.  
1.2 SPECIFIC CHARACTERISTICS  
Thyro-P is characterized by a multitude of specific characteristics, for instance:  
• easy handling  
• menu-driven user interface  
• type range 230-690 Volts, 37-2900A, single, double, triple phase  
• broadband power supply AC 200-500V, 45-65Hz  
• ohmic load and transformer load  
• as well as load with large Rhot/Rcold for 1P and 3P  
• soft start function for transformer load  
• load circuit monitoring  
• automatical rotating field recognition for 2P and 3P  
• U, U2, I, I2, P control as well as without control  
• operating modes TAKT, VAR, Soft-Start-Soft-Down, MOSI, ASM  
(optional sub-operating mode of TAKT)  
• control of analog set points or via interfaces  
• fibre optic and RS 232 interfaces as standard  
• electrical separation according to EN 50178 chap. 3  
• Measured values are given at analog outputs  
• 4 set point channels incl. Motorpoti, which parameters can be set  
The specific characteristics especially include the following options:  
Bus connection via bus adaptor cards to plug into the Thyro-P Power Controller, coupling to  
different bus systems, for instance Profibus, other bus systems upon enquiry.  
• Patented ASM procedure for dynamic mains load optimization. The ASM procedure (automated  
synchronization of multiple Power Controller applications) is used for dynamic mains load optimi-  
zation. It reacts to changes in load and set point, minimizes mains load peaks and associated mains  
feedback. Minimizing of mains load peaks means cost savings in operating and investment cost.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
14  
Local operating and display unit (LBA), able for graphics display, menu-driven, pluggable. The  
integrated copying function by replugging the LBA enables simple transfer of Power Controller  
parameters between power controllers of the type Thyro-P.  
• Cabinet installation kit (SEK) for the local operating and display unit. The SEK enables installation  
of the local operating and display unit into the switching cabinet door. It consists of cables and  
an installation frame.  
• The PC-Software Thyro-Tool Familiy for effective commissioning and simple visualization tasks.  
Functions are for instance loading, storing, modification, comparing and printing of parameters,  
set points and actual value processing, line diagrams of process data (including printing and  
storing option), bar diagrams, simultaneous display of process data from different Power Con-  
trollers, simultaneous connection of up to 998 Thyro-P Power Controllers.  
1.3 TYPE DESIGNATION  
The type designation of the Thyristor Power Controllers are derived from the construction of its  
power section:  
TYPE RANGE DESIGNATION  
FEATURES  
Thyro-P  
1P  
single phase power section,  
for single phase operation  
2P  
double phase power section, for three phase operation  
in three phase economizing circuits,  
not for phase-angle control (VAR)  
three phase power section,  
3P  
for three phase operation  
.P400  
Type voltage 230-400 Volt, 45-65 Hz  
Type voltage 500 Volt, 45-65 Hz  
Type voltage 690 Volt, 45-65 Hz  
Type current 37A (Typecurrent range 37A-2900 A)  
Integrated semi-conductor fuse (all Thyro-P)  
Forced air cooling with integrated ventilators  
.P500  
.P690  
.P ...-0037  
.. ...-.... . H  
.. ...-.... . F  
The complete type range can be found in the type overview in chapter 9.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
15  
2. FUNCTIONS  
For optimum adjustment to different products and production processes as well as differently  
electrical loads, the most favorable operating and control modes may be set according to the  
following overview.  
2.1 OVERVIEW OF OPERATING MODES  
This chapter gives an overview of the various, partly type-specific and optional operating modes.  
Full wave switch mode (TAKT)  
Depending on the prescribed set point, the  
mains voltage is periodically switched. In this  
operating mode, almost no harmonics are  
created. Whole multiples of the mains periods  
are switched, avoiding DC components. The full  
oscillation clock principle is especially suited for  
loads with thermal inertia. For optimization of  
the mains load, the optional ASM process may  
be applied in this operating mode.  
Phase-angle principle (VAR, with 1P and 3P)  
Depending on the prescribed set point, the sine  
oscillation of the mains voltage is gated using a  
larger or smaller control angle a. This operating  
mode is characterized by high control dynamics.  
In case of phase-angle control, it is possible to  
compensate harmonics of the mains voltage by  
using circuit variants (for instance vector group  
transformer).  
Soft-Start-Soft-Down (SSSD)  
The operation of large individual loads using the operating mode TAKT may lead to voltage varia-  
tions on the mains side. The operating mode SSSD greatly reduces the pulse-shaped mains load.  
MOSI operation for 1P and 3P  
MOSI is a sub-operating mode of the operating modes TAKT and VAR for sensitive heating materi-  
als with a high Rhot/Rcold ratio, for instance molybdenum disilicide. The Power Controller always  
starts with phase-angle maximum value and actual value to avoid high current amplitudes during  
the heating-up phase and then automatically switches to the set operating mode.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
16  
Mains load optimization (ASM procedure)  
For systems in which several Power Controllers are employed in full wave switch mode TAKT, it is  
possible that individual Power Controllers are synchronized so that a regular mains load is achieved  
by defined switching of the individual Power Controller in sequence. This avoids load peaks by  
random simultaneous switching of many Power Controllers and load troughs are filled up. The  
upstream transformer and/or the upstream feed point may be designed for a lower load. Besides  
savings in investment and operating cost, lower mains reactions also result.  
2.2 SET POINT CONTROL CHARACTERISTIC  
The set point control characteristic of Thyro-P may be easily adapted for the control output signal  
of the upstream process controller or automation system. All signals customary on the market may  
be used. The adaption is made by changing the starting and ending points of the control characte-  
ristic. Inverted operation (ending value is smaller than the starting value in voltage or current) is also  
possible.  
The effective set point is the total set point. It is formed by adding the four set points as shown in  
fig. 2.  
In the simplest case all the set point values are added algebraically. The prerequisite for a set point  
to influence the total set point value is that it must be enabled by the set point Enable Register.  
Set point 1 (X5.2.10 - X5.1.13 ground) 0-20mA default  
Set point 2 (X5.2.11 - X5.1.13 ground) 0-5V default  
The inputs set point 1, 2 are two electrically equal analogue inputs for current or voltage signals,  
with subsequent A/D converter (resolution 0.025% of the final value), and they may be set to the  
following signal ranges:  
0(4)-20 mA (Ri about 250)  
max. 24mA  
max. 12V  
max. 12V  
siehe ”ATTENTION“  
0-5  
V
V
(Ri about 8,8k)  
(Ri about 5k)  
0-10  
The following table shall be used for the hardware configuration of the set point inputs (see also  
FILE COMPONENT MOUNTING DIAGRAM CONTROL DEVICE, figure 10). If the hardware con-  
figuration is changed, the Thyro-P parameters must be changed accordingly with the LBA or the  
Thyro-Tool.  
X221 for Set point input 1  
Bridge X221  
closed*  
Signal range  
0(4) -20mA  
0-5V / 0-10V  
Set point input 1  
(X5.2.10)  
open  
(X5.2.10)  
X222 for Set point input 2  
Bridge X222  
closded  
Signal range  
Set point input 2  
(X5.2.11)  
0(4)-20mA  
open*  
0-5V / 0-10V  
(X5.2.11)  
* default  
ATTENTION  
If the open-circuit voltage of the connected set point exceeds 12V in the 20mA signal range, the  
set point inputs can be destroyed, if the belonging bridge (X221, X222) is open.  
Within the stated input ranges, these values with the control characteristic may be adjusted to any  
common signal characteristic.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
17  
FIG. 1 CONTROL CHARACTERISTIC FOR U CONTROL  
For a set point poti (e.g. 5-10 K) 5V supply voltage can be taken from terminal X5.2.5 (Ri = 220,  
short-circuit-proof).  
SET POINT CONTROL CHARACTERISTICS  
The set point control characteristic (Fig. 1) of Thyro-P may be easily adapted for the control output  
signal of the upstream process controller or automation system. All signals customary on the market  
may be used.  
The adaption is made by changing the starting and ending points of the control characteristic. Inver-  
ted operation (ending value is smaller than the starting value in voltage or current) is also possible.  
Set point 3:  
Set point of the superordinate system or PC via fibre optic connection (standard) X30, X31 or via  
the optional bus interface.  
Set point 4:  
Set point input (motor potentiometer function) via LBA or RS 232 from the superordinate system or  
PC. Set point 4 is stored in case of mains failure.  
EFFECTIVE TOTAL SET POINT VALUE  
The algebraic addition of the results of set point (1,2) to set point 3 and 4 gives the (effective) total  
set point value for the set point control characteristic as shown in the following figure.  
FIG. 2  
TOTAL  
SET POINT  
Download from Www.Somanuals.com. All Manuals Search And Download.  
18  
The prerequisite for a set point to influence the total set point value is that it must be enabled by  
the set point Enable Register. Set point 1 and 2 can be linked using the following functions. The  
result of this link is called set point (1,2).  
Set point link  
ADD Set point (1,2) = Set point 1 + Set point 2  
IADD Set point (1,2) = Set point 1 - Set point 2  
Set point 2 [%]  
_Pro Set point (1,2) = Set point 1 *  
100%  
Set point 2 [%]  
_IPro Set point (1,2) = Set point 1 * (1 -  
)
100%  
VALUE RANGE OF SET POINT (1,2)  
For the link result of set point (1,2) the following value range applies:  
0 ͨ Set point (1,2) ͨ Set point max (Umax, Imax, Pmax).  
SET POINT ENABLE REGISTER  
The set point Enable Register (AD_P_SW_ENABLE, adr. 94) enables the 4 set points to be shut off  
or enabled independently. Only enabled set point inputs are part of the effective total set point  
value.  
The shut off or inactive set points are shown by the LBA and can thus, if necessary, be checked  
before connecting.  
The set point Enable Register can be changed from all service units (Bus, Thyro-Tool Familiy, LBA).  
Example:  
8
1
1
0
0
0
4
1
0
1
0
0
2
1
0
0
1
0
1
1
0
0
1
0
VALUE ABBR.  
EXPLANATION  
15  
8
STD  
Standard (all ON)  
LOC  
Motor poti-set point 4 (LOCAL)  
Bus set point 3  
4
REMOTE  
ANA  
3
Analog-set points 1,2  
All set points inactive  
0
2.3 CONTROL TYPES  
Thyro-P has five control types effective as underlying controls. Mains voltage variations and load  
changes are directly and therefore quickly adjusted by bypassing of the slow temperature control  
system.  
Before commissioning of the Power Controller and selection of a control type, you should be  
familiar with the operating procedure respectively the effect for application.  
2.3.1 CONTROLLED VALUE  
The controlled value effective on the load is proportionate to the total set point, depending on the  
control type:  
CONTROL TYPE  
P control  
CONTROL VALUE (PROPORTIONATE TO THE TOTAL SET POINT)  
output (active) power, P  
U control  
U2 control  
output voltage, Urms  
output voltage, U2rms  
I control  
I2 control  
output current, Irms  
output current, I2rms  
LIMITING OF SIGNALS  
Independent of the control type set, additionally minimum and maximum limiting values may be  
set. For this purpose, also refer to Fig. 1 control characteristic.  
The maximum limiting values determine the maximum modulation of the load.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
19  
The minimum limiting values should ensure minimum modulation via the control angle (for instance  
minimum heating of the load).  
CONTROLLER RESPONSE  
If the load resistance changes, for instance due to temperature effect, ageing or load fault, then the  
values effective on the load change as follows:  
UNDERLYING  
LOAD RESISTANCE  
DECREASES  
LOAD RESISTANCE  
INCREASES  
EFFECTIVE*  
LIMITATIONS  
CONTROL  
LIMIT  
Urms max  
Urms max  
Irms max  
Irms max  
Pmax  
P
ULOAD  
=
ILOAD  
larger  
larger  
=
P
ULOAD  
=
ILOAD  
U
larger  
larger  
smaller  
smaller  
=
smaller  
smaller  
larger  
larger  
=
smaller  
smaller  
=
Irms max  
Pmax  
U2 (UxU)  
=
=
Irms max  
Pmax  
I
smaller  
smaller  
larger  
larger  
larger  
=
Urms max  
Urms max  
Urms max  
Pmax  
I2 (IxI)  
=
=
Pmax  
P
smaller larger  
larger  
smaller  
smaller  
Irms max  
Irms max  
without control  
larger  
=
smaller  
Urms max  
Pmax  
* If one of the limits is exceeded, then the signaling relay K2 and the LED „limit“ react  
(default values of parameter settings).  
General modulation limit  
Ts=Ts max  
=max  
TAB. 1 BEHAVIOUR IN CASE OF LOAD CHANGE  
2.4 INDICATIONS  
2.4.1 LED INDICATIONS  
The LEDs on the front side signal the following states:  
ON  
green: operating indication, power supply controller board  
red: RESET active  
CONTROL  
LIMIT  
modulation percentage indication, flashing*  
limitation is active, relay K2 switches*  
Controller Lock active, but load control is continued at pulse limits  
(default value = 0)*  
PULSE LOCK  
FAULT  
fault present*  
OVERHEAT  
overheating of power section  
(in case of ..HF types, check ventilator)*  
* Default setting  
Activation of the integrated semiconductor fuse may be signalled using the fault indicating relay K1  
rest current, contactor, otherwise separate supply of the control device required). In case of Power  
Controllers from model current 495A, additional signalling is performed via an indicator at the  
semiconductor fuse.  
2.4.2 RELAY INDICATIONS K1-K2-K3  
The Thyro-P Power Controller is fitted with three relays. Each of these relays has a change over  
contact in principle be allocated a value in the event register. The following table shows the contac-  
tor allocation of the relays at the corresponding terminal strips. Presets of parameters by the works  
(default values) may be found in chapter 3.4.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
20  
ALARM RELAY K1  
The relay K1 is activated if a fault is detected in the system. The effective direction, whether it  
should close or open in case of fault, may be set using the parameter K1 closed-circuit OFF, ON by  
using LBA or Thyro-Tool Familiy. Which indications lead to switching of the relay may also be set.  
Recommendation: keep the default setting.  
LIMITING RELAY K2  
The relay K2 only closes (in default setting) if at least one of the following values is exceeded:  
• 1. max. admissible effective value of the load current  
• 2. max. admissible effective value of the load voltage  
• 3. max. admissible active power of the load  
The relay releases if none of the values is exceeded anymore. It is possible to set which indications  
lead to switching of the relay. Recommendation: keep the default setting.  
OPTIONAL RELAY K3  
If changes are made to the default relay settings due to the application, then preferrably the relay  
K3 should be reparameterized.  
It is possible to realize functions like for instance a follow-up relay for ventilator control or by pass  
the alarm relay at startup of the system. It may also be used as a further alarm relay or limiting relay,  
by reparameterization.  
The illustration shows the relay K3 for bridging the startup alarm.  
FIG. 3 SWITCH-ON FAULT BRIDGING  
2.5 MONITORING  
Faults occurring in the Power Controller or in the load circuit are signalled. Signalling is performed  
via LED (FAULT) and via relay with potential-free change-over contact. The fault buffer may be  
read via LBA or the interface after selecting the status line. Simultaneously with the fault signal,  
the pulse shutdown may optionally also be set (Imp.-Absch. OFF, ON). Faults having occurred are  
shown in the display of LBA by text status indications in the status line. After selecting the status  
line, the indication may be called up.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
21  
2.5.1 LOAD MONITORING  
MONITORING OF THE LOAD AND MAINS VOLTAGE  
Each power section is fitted with its own transformer for creating the synchronization voltages. This  
also allows monitoring of the phase voltages. In the LBA menu monitoring, the limits may be set for  
ULine min and ULine max. If larger deviations are detected, then a fault indication is generated.  
ABSOLUTE OR RELATIVE MONITORING  
Relative monitoring for heating elements for Rhot/Rcold 1 and absolute monitoring for heating  
elements with Rhot/Rcold 1 are possible.  
ABSOLUTE VALUE MONITORING CURRENT  
This function allows monitoring of a freely selectable absolute current limit. The parameters for  
the value may be set in ampere.  
i
I < threshold  
T
L
indication 16,17 (Chap. 3.4)  
tV  
FIG. 4 ABSOLUTE VALUE MONITORING  
This absolute value monitoring lends itself to one or more load resistances organized in parallel or  
in series. Generally, the effective current value measured is continuously compared with a preset-  
table absolute current limit for undercurrent or overcurrent. If these limits are undercut or exceeded  
an indication shows. In case of resistor elements organized in parallel, it is therefore possible, using  
the lower current limit, to select a partial load interruption. Using the upper current limit, in case of  
resistors switched in series, short-circuiting of an element may be detected.  
RELATIVE MONITORING  
This monitoring is sensible if the resistance value of the load slowly changes. Changes in resistance  
may for instance be caused by temperature changes or by ageing. The current (b) of the Power  
Controller is regarded as 100% load current (current in fault-free state) after activation of the RESET  
or CONTROLLER LOCK. The RESET is automatically activated after each startup, restart or after  
mains outage. In case of relatively slow changes of the current, due to characteristics of the above  
mentioned heating elements, automatic adjustment of the internal reference value to 100% is  
performed (b‘).  
FIG. 5 RELATIVE MONITORING  
Download from Www.Somanuals.com. All Manuals Search And Download.  
22  
Quick current changes, which may for instance occur in case of partial.  
Quick current changes, which may for instance occur in case of partial short-circuit, may be  
detected by overcurrent monitoring (max., a – a‘).  
Quick current changes, which may for instance occur in case of load breakdown may be detected  
by undercurrent monitoring (min., c – c‘).  
NOTE FOR LOAD MONITORING:  
Changes of the burden resistor and parameters can be necessary in case of small load currents or  
small current flow angles (i. e. small phase angles).  
If a Thyro-P 3P is used in phase-angle operating mode, the star point of the load and the star point  
of the (built-in) voltage transformers should be connected together to ensure an accurate load  
monitoring. Please contact us in case of need..  
The values in the following table apply to ohmic loads.  
Different values apply may be required for specific hea-  
ting resistors, for instance IR radiators. The adjustable %  
values shown in the tables are load current variations on  
the present operating values.  
Star connection  
with separate star points  
Star connection  
with neutral conductor  
Delta connection  
Star connection  
without neutral conductor  
HEATING  
1P  
2P*/3P  
3P  
ELEMENTS  
IN PARALLEL  
FOR EACH  
STRAND  
STAR CONNECTION  
WITH SEPARATE  
STARPOINTS  
STAR CONNECTION  
DELTA  
STAR CONNEC-  
WITHOUT CONNEC-  
CONNECTION TION WITH  
CONNECTED  
TED NEUTRAL  
CONDUCTOR  
NEUTRAL CONDUCTOR  
10%  
5
4
3
2
1
10%  
13%  
17%  
25%  
50%  
10%  
13%  
17%  
25%  
50%  
10%  
13%  
20%  
50%  
13%  
17%  
25%  
50%  
10%  
12%  
21%  
* for Thyro-P 2P: additional external converters in phase L2 are possible.  
TAB. 2 PARTIAL LOAD BREAKDOWN WITH HEATING ELEMENTS SWITCHED IN PARALLEL,  
UNDERCURRENT, RELATIVE MONITORING  
Download from Www.Somanuals.com. All Manuals Search And Download.  
23  
Star connection  
Delta connection  
Star connection  
without neutral conducter  
with neutral conductor  
HEATING  
1P  
2P  
3P  
ELEMENTS  
IN SERIES FOR  
EACH STRAND  
STAR CONNECTION  
DELTA CONNECTION  
STAR CONNECTION  
WITH CONNECTED  
WITHOUT CONNECTED  
NEUTRAL CONDUCTOR  
NEUTRAL CONDUCTOR  
6
5
4
3
2
10%  
13%  
17%  
25%  
50%  
10%  
13%  
17%  
25%  
50%  
10%  
10%  
14%  
25%  
10%  
13%  
26%  
TAB. 3 PARTIAL SHORT-CIRCUIT WITH HEATING ELEMENTS SWITCHED IN SERIES, OVERCUR-  
RENT, RELATIVE MONITORING  
AGEING OF LOAD RESISTORS  
Thyro-P determines the load conductance separately for each phase. These values are available  
from LBA, Thyro-Tool Familiy and the Bus interface. The current resistance can be determined by  
reading out and converting from the conductance.  
The following table offers an overview of the possible monitoring functions of the Thyristor Power  
Controller Thyro-P.  
TYPE OF  
PARAMETER  
DEFAULT /  
MONITORING  
Unet max  
SETTINGS  
REMARKS  
mains overvoltage  
mains undervoltage  
overcurrent  
input in volts  
Type voltage + 20%  
Type voltage - 20%  
REL_ABS = REL  
UE_S = ON  
Unet min  
input in volts  
Iload max-REL  
0-100%  
overcurrent relative  
Re: measured load current  
after each RESET/control lock  
input in ampere  
Iload max-ABS  
Iload min-REL  
overcurrent  
absolute  
REL_ABS = ABS  
UE_S = ON  
undercurrent  
relative  
0 to 99%  
REL_ABS = REL  
UN_S = ON  
Re: measured load current  
after each RESET/control lock  
input in ampere  
Iload min-ABS  
undercurrent  
absolute  
REL_ABS = ABS  
UN_S = ON  
pulse switch  
pulse switch off  
ON: pulse switch off after  
fault indication  
indication is always  
issued  
off by software  
OFF: in case of fault  
in case of synchronization  
SYT 9, RESET of all Power  
Controllers is required  
K1  
alarm relay K1  
ON: relay K1  
open circuit  
released in case of fault  
OFF: relay K1  
the alarm relay switches  
upon activation of  
RESET  
pulled-in in case of fault  
TAB. 4 OVERVIEW MONITORING  
Download from Www.Somanuals.com. All Manuals Search And Download.  
24  
2.5.2 VENTILATOR MONITORING  
The separately ventilated Power Controllers (-...HF) are fitted with thermal monitoring. The tempe-  
rature is measured on the heat sink. In case of a temperature overrange, a fault inducation is issued  
(Profibus, LED OVERHEAT).  
ATTENTION  
Activating this monitoring function is obligatory if the Thyro-P is operated under UL conditions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
25  
3. MODE OF OPERATION  
This chapter shows the operating options of Thyro-P using LBA and Thyro-Tool Familiy.  
3.1 LOCAL OPERATING AND DISPLAY UNIT (LBA)  
The optional LBA (IP30, protection classification 3) has five keys and a backlit graphical LC display  
for 7 x 19 characters respectively 64 x 114 pixels. In the standard version, the languages German,  
English and French are available.  
FIG. 6 LOCAL OPERATING AND  
DISPLAY UNIT (LBA)  
The LBA may be connected or disconnected from the RS 232 interface of the Thyro-P control device  
during operation. After plugging into the interface and automatic loading of the parameters, the  
LBA displays its main menu.  
ATTENTION  
Before storing (store in Thyro-P / LBA under Thyro-P) the parameters must always be saved in the  
EEPROM of the LBA first (store in LBA).  
If no key is pressed for one minute the operation display appears. This does not apply if a line  
diagram is running. If no communication is achieved after plugging in the LBA between LBA and  
Power Controller in case of fault, then a self-test is performed. Using the LBA, Thyro-P may be  
parameterized and monitored under menu control. It is possible to display up to three process  
data values (for instance the actual values of current, voltage or power occurring at the load) in  
double character height. Further values which may be displayed are the set point value as well as  
parameter data and fault indications. Furthermore, display of a value in graphical form as line dia-  
gram is possible. The time and value axes may be set by parameters and so adjusted to require-  
ments. Using the LBA, the parameters of one Thyro-P may be copied to another Thyro-P. More  
details on this can be found in the chapter LBA menus.  
3.1.1 LBA KEYBOARD FUNCTIONS  
The LBA has a total of 5 standard keys: with an activatable parameterizing lock (see table 5). Four  
arrow keys and one OK key. By moving the cursor mark (>) using the corresponding keys (up arrow,  
down arrow), the desired function may then be selected using the OK key. An underlined language/  
function is in each case selected. An unnamed 6th key is available behind the opening in the front  
of the LBA, the reset key. If this is operated, then the functions RESET of Thyro-P is performed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
26  
FUNCTIONS OF LBA KEYS:  
KEY  
DISPLAY  
FUNCTION  
Cursor before menu text: selection of the higher level (back)  
Cursor on the figure:  
Cursor on the figure:  
select prior (higher value) position  
select next (lower value) position  
Cursor before menu text: move cursor to the prior line, possible scroll  
upward (only indented lines may be scrolled)  
Cursor on the figure:  
increase value  
Cursor on the parameter: switch on  
Cursor before menu text: cursor on subsequent line, possible scroll down-  
ward  
Cursor on the figure:  
reduce value until minimal admissible value is  
reached  
Cursor on the parameter: switch off  
OK  
Cursor before menu text: selection of a figure or of an input field  
Cursor on the figure:  
takeover of the modification into Thyro-P and  
deselection of the selected field  
Cursor on the parameter: takeover of the modification into Thyro-P and  
deselection of the selected field  
Operation display:  
deselection of the operation display  
Parameter loading process Parameterizing process is temporarily  
Thyro-P LBA  
inactivated  
OK OK  
Line diagram:  
deselection of the line diagram display  
operation display is activated; this does  
not apply in case of selected line diagram  
Parameterizing lock is self-activating on release  
No key pressed  
(for 1 minute)  
Operation display:  
TAB. 5 FUNCTIONS OF THE LBA-KEYS  
3.1.2 LBA MAIN MENU  
The top line always contains the name of the menu or of the submenu. The lowest line, the status  
line, always contains the configuration of the Power Controller or in case of existing indications,  
the word status indication.  
The main menu (function selection menu) appears on the LBA display after plugging the LBA into  
Thyro-P. It looks like this:  
Download from Www.Somanuals.com. All Manuals Search And Download.  
27  
MAIN MENU  
FUNCTION  
Language  
selection operating language  
load and store data  
Load/store data  
Set points/characteristics  
Parameter  
set point processing  
display and modification of parameters  
select operation display  
energy and operating hours  
Operation display  
Last function  
TAB. 6 LBA MAIN MENU  
3.1.3 LBA SUBMENUS  
The first six lines of the above main menu contain the names of the sub-menus. These are shown  
below, with explanations, in the sequence they are contained in the menu.  
= Main menu (appears after plugging in the LBA)  
Default User  
Menu  
Remarks  
Value Value  
Sprache/language  
Deutsch  
English  
x
Francais  
Open/save data  
Thyro-P -> LBA  
Loading, storing, copying of parameter sets  
1
2
LBA  
-> Thyro-P  
Parameter from LBA-EEPROM to Thyro-P RAM  
Parameter from LBA-RAM to LBA-EEPROM  
Parameter from Thyro-P RAM to Thyro-P EEPROM  
Store in LBA  
Save Thyro-P  
1
2
Open data again  
Thyro-P -> LBA  
waiting time  
Store parameters from Thyro-P in LBA  
Observe waiting time! OK key during charging releases  
the parameter lock  
ASIC-SW  
Code LBA  
Shows production date of controller software  
Shows version of LBA software  
Save data again  
LBA -> Thyro-P  
waiting time  
Store parameters from LBA in Thyro-P  
Observe waiting time!  
Set points/curve  
motor pot.  
Term. (10)  
Remark: Display is refreshed after max. 10 sec.  
Display and modification set point 4  
Display set point 1  
0
Term. (11)  
Master(bus)  
Display set point 2  
Display set point 3 (bus)  
Display total set point  
Act.pwr.tot:xx,xxmA  
Absolute set points  
During active circuit set point is displayed  
in a submenue depending on control mode  
Choice of set point inputs  
STD,LOC,REMOTE,ANA  
ADD,IADD, PRO,IPRO  
5V,10V,mA term(10)  
5V,10V,mA term(11)  
Ctrl.start1 4.00mA  
Ctrl.end1 20.00mA  
Ctrl.start220.00V  
Ctrl.end2 10.00V  
STD  
ADD  
SW1+SW2, SW1-SW2, SW1*SW2%/100%, SW1*(1-SW2%/100%)  
Selection signal type for set point 1*  
Selection signal type for set point 2*  
Control start set point SW1  
mA  
5V  
0.3mA  
20.0mA  
0.07V  
5.0V  
Control start set point SW1  
Control start set point SW2  
Control end set point SW2  
* refer to ”ATTENTION” on page 16  
Adress  
Bus+LL-compound xxx  
100  
xxx for fibre optic 001 - 998  
in case of Profibus DP 001 - 125  
000 and 999 have specific functions  
Download from Www.Somanuals.com. All Manuals Search And Download.  
28  
= Main menu (appears after plugging in the LBA)  
Default User  
Menu  
Remarks  
Value Value  
Act. val. select  
Analog outp.(32)  
Parameterization for analog output 1, terminal 32  
Parameterization for analog output 2, terminal 33  
Parameterization for analog output 3, terminal 34  
Parameterization for operation display, value top  
Parameterization for operation display, value middle  
Parameterization for operation display, value bottom  
Mean value analog display of xx mains/cycle periods  
Parameterization line diagram  
Analog outp.(33)  
Analog outp.(34)  
Display top  
3
4
5
Display middle  
Display bottom  
Average xx  
25  
Graphics  
Analog outp.(32)  
Analog outp.(33)  
Analog outp.(34)  
Analog outp.(xx)  
Select and OK  
3
Selected analog output 1,2,3 (terminal 32,33,34)  
Selection of (if ecisting in the Power Controller):  
U1, I1, P1, PG  
U1, I1, P1, PG  
U2, I2, P2  
U1(32)  
I1(33)  
P1(34)  
U2, I2, P2  
U3, I3, P3, alpha  
U3, I3, P3, setpoint  
U ,I ,P  
U3, I3, P3, alpha, total set point  
Display total set point  
Minimum and maximum values of U, I, P since  
last RESET respectively voltage startup.  
Changeover 10V/20mA  
min  
min  
min  
U ,I ,P  
max  
max  
max  
Current output OFF,ON  
Full scale xx,xmA  
Offset  
Measuring device end scale deflection e.g. 20mA  
Offset signal for output value, for instance 4mA  
Y=dimension depending on display V, A, kW  
0mA  
Full scale value xxx y  
Display top  
4
Display middle  
Display bottom  
Display  
Operation display: top, middle, bottom (3 values)  
Selection of (if ecisting in the Power Controller):  
U1, I1, P1, PG  
Select and OK  
U1, I1, P1, PG  
U2, I2, P2  
U2, I2, P2  
U3, I3, P3, alpha  
U3, I3, P3, setpoint  
U ,I ,P  
U3, I3, P3, alpha, total set point  
Display total set point  
Minimum and maximum values of U, I, P since  
last RESET respectively voltage startup.  
min  
min  
min  
U ,I ,P  
max  
max  
max  
5
Line diagram  
X - axis - time  
1,5min;30min;1h;3h  
Y - axis - value  
U1, I1, P1, PG  
Scaling of the time axis (resolution pixels)  
Selection of (if existing in the Power Controller type):  
1.5min  
U1  
U1, I1, P1, PG  
(resolution 50 pixels)  
U2, I2, P2, alpha  
U3, I3, P3, setpoint  
Start graphic  
U2, I2, P2, alpha,  
U3, I3, P3, total set point,  
Start line diagram  
bar, average value  
Display band (all measured values) or average value  
limitations  
Presets limiting values  
U
I
P
xxxxV  
xxxxA  
xxxxkW  
xxxxms  
xxx°e  
type  
Display/default (at 3P default setting phase voltage)  
Display/default  
rms max  
type  
rms max  
type  
Display/default  
max  
op. time  
1000ms  
Only for the operating modes TAKT and SSSD (< To)  
Only for the operating mode VAR  
Only for VAR  
max  
Ft.  
180  
0
Imp End  
Rr.  
xxx°e  
Imp End  
on. time  
xxxxms  
xxxxV  
xxxxA  
xxxxkW  
*
*
*
*
0
min  
U
0
rms min  
I
0
rms min  
P
0
min  
Phase swingL xxx  
* password protection  
0
Phase swing for L1, L2, L3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
29  
= Main menu (appears after plugging in the LBA)  
Default User  
Menu  
Remarks  
Value Value  
Operating mode  
TAKT/FC  
VAR /PA  
TAKT  
1
Operating mode selection fulloscillationclockprinciple  
Operating mode selectionphase-angle principle  
Operating mode selectionSoft-Start-Soft-Down  
Reserve  
SSSD/FC-PA  
Res  
No.ctrld.phase 123  
Load R,RL,transf.,C  
Number of phases controlled (power paths)  
R: without startup ramps, C: like R, only for TAKT  
Operation without controls or limitations  
Display for ASM process  
Service  
ASM OFF,  
OFF,ON  
ON, OFF  
OFF  
OFF  
Uses analog output 2, terminal 33  
R: ramp, S: steer  
Only for 3-phase and VAR  
MoSi OFF,R,S  
Afterpulse OFF,ON  
OFF  
ON  
TDS  
Neutral  
OFF,ON  
OFF,ON  
OFF  
OFF  
Only for 3-phase and VAR  
Only for 3-phase  
Hardware parameters  
Curr.conv.  
Volt.conv.  
X501-3 1-2,2-3,3-4  
xxxxx  
xxxx  
100  
16  
Transformation ratio ü:1  
Transformation ratio ü:1  
Voltage adjustment measurement range 3 see chapter  
Voltage transformer  
See name plate  
Type current xxxxx  
Type voltage xxxx  
Burden load. xxx,xx  
type  
type  
1 Ohm  
See name plate  
current transformer adjustment incl. tolerances  
Frequency  
Date  
Time  
Only display of the mains frequency  
Input and display  
Input and display  
yyyymmdd  
hhmmss  
Cntr. data log. x  
Peak value xxxxx  
Current count of data logger counter 1 to 16  
Peak current value at which instant impulse lock  
shall be set (in Ampere)  
65000  
SW_FA_1-6  
*
*
list_L1-3_FA  
DAC1-3_FA  
TI_FA  
*
*
KP_FA  
Puls.s.off OFF,ON  
K1 closed-c OFF,ON  
*
ON  
ON  
IMAB: shutdown of the Power Controller in case of fault  
K1RU: switching open contact/closed contact (only K1)  
*
Monitoring  
Display/setting of the monitoring values  
Relative/Absolute  
Undercurrent OFF/ON  
Overcurrent OFF/ON  
R/A  
x
y
Monit. L2  
Monit. L3  
OFF/ON  
OFF/ON  
xxxV  
1)  
U
absolute limiting value, see Fig. 4  
absolute limiting value, see Fig. 4  
line max  
1)  
U
xxxV  
line max  
1)  
Temperature  
Messages  
6
7
change of absolute limiting value is only possible if  
the corresponding relative limiting value are zero/255.  
2)  
change of absolute limiting value is only possible if  
the corresponding relative limiting value are zero/5000.  
Monitoring Relativ  
Undercurrent  
Overcurrent  
Value unequal  
ZERO!  
xx %  
xx %  
Cursor is in front of the selected value  
XR  
YR  
Monitoring absolut  
Undercurrent  
Overcurrent  
ZERO!  
xx A  
xxx A  
Cursor is in front of the selected value  
XA  
YA  
* password protection  
Download from Www.Somanuals.com. All Manuals Search And Download.  
30  
= Main menu (appears after plugging in the LBA)  
Default User  
Menu  
Remarks  
Value Value  
6
Temperature  
PT1000,PT100,NTC  
Ch.curve no.  
PT1000  
type  
Sensor used  
X
Type-dependent, see chapter type overview  
Display actual temperature (relative value)  
Temperature xxx°C  
Lev.wire br.  
*
*
*
Lev. sh-circ.  
Comp.val.DAC  
7
No.,DaLo,K1,K2,K3  
Status- / fault name  
1
2
3
4
5
6
7
8
9
10  
Communication with RS 232 active  
Communication with fibre optic active  
Power value negative  
Communication fault RS 232 or fibre optic  
Synchr. interfacesfailure(e.g. Profibus)  
External processor on the SSC signals fault  
K3 after RESET  
RESET active  
Data in EEPROM invalid (reload parameters)  
Internal message  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
x
K2  
Limiting value is exceed  
Excess device temperature is present  
Instant current interruption has responded  
Internal message  
Fault exists in load circuit-collective fault 16,17  
Undercurrent exists in the load circuit  
Overcurrent exists in the load circuit  
Internal message  
x
Dalo  
Circuit OK  
Undervoltage exists in the power section  
Overvoltage in the power section  
Internal message  
Internal message  
x
K1  
Synchronization fault  
Collective fault 4,6,9,10,11,12,14-24  
(each fault leads to switching)  
Internal message  
26  
27  
28  
29  
30  
Internal message  
Internal message  
Internal message  
Power Controller is in peak current limitation  
(only for operating mode MOSI)  
Temperature sensor, short circuit or sensor break  
31  
Controls  
2
U ^  
load  
Parameterization control characteristic  
2
Selection control characteristic U  
load  
UxU  
U
UxU  
U
Selection control characteristic U  
load rms  
load  
2
I ^  
load  
2
IxI  
I
Selection control characteristic I  
load  
I
Selection control characteristic I  
load rms  
load  
Active power  
No control  
PID factors  
P
Selection control characteristic effective load, P  
Selection set operation (phase-angle control angle)  
Parameterization controller parameters, password prot.  
8
8
PID factors  
Sta.-Regl. OFF,ON  
ON  
With standard control OFF the control parameters  
can be stipulated  
P - part  
I - part  
D - part  
type  
type  
type  
Controller parameters, P-part  
Controller parameters, I-part  
Controller parameters, D-part  
* password protection  
Download from Www.Somanuals.com. All Manuals Search And Download.  
31  
= Main menu (appears after plugging in the LBA)  
Default User  
Menu  
Remarks  
Value Value  
Times  
Approach 1.  
Softdown  
xx°e  
xx,xs  
60°el  
0.3  
60°el. in case of 1P, otherwise 90°el., default value for transformers  
0 to (To-20ms), default value 400ms, ramp time up  
0 to (To-20ms), default value 400ms, ramp time down  
Display/Default of pulse period duration To  
Display of on-time Ts  
Softdown  
xx,xs  
0.3  
Cl.puls.dur  
On-time  
xxxxxms  
xxxxms  
xxxms  
1.000  
Sync.del.  
Min. pause  
Puls.dur.max  
Display of on-time Ts  
60ms  
50s  
Transformer dependent, default value  
Fixed parameter control range, default value,  
password protection  
Set pointm2 OFF/ON  
9
OFF  
On activating, a jump is made from the operation  
display directly into this set point menu. The main  
menu can be reached from here with the left key  
.
9 Local/Remote  
Local/Remote  
Set point menu 2 direct from the operation display  
when parameter set point 2=ON  
Motorp SW  
Master SW  
Total Pwr  
xx  
%, kW, A depending on set cascade control  
xx  
x
%, total power; U1, I1 depending on set cascade  
control  
Total SW  
x
Total set point value also in %, kW, V, A  
Pa-lock OFF,ON  
OFF  
With parameter lock ON, the lock, which is enabled  
with OK, is reactivated after one minute of operation  
display  
Password  
Password entry  
Enabling of password functions  
Condition: Consultation/training  
Valid until LBA is unplugged from the Power  
-----------------  
****** o.k.  
Controller  
-----------------  
Code xxxxxxxxxx  
EEPROM version number  
Operation display  
Current operation indication, exit using OK  
Display top  
U1  
I1  
P1  
456,7V  
1567,9A  
1234,8kW  
Display middle  
Display bottom  
Status messages  
11  
Display of status information: select this line  
and confirm using OK  
11 State messages  
jjjjmmtt ddmmss  
Limit  
Examples for status indications  
jjjjmmtt ddmmss  
Limit  
jjjjmmtt ddmmss  
Undervoltage  
Last function  
Return to the parameter last processed  
REMARK  
Type  
setting dependent on the type  
Some further menues are only accessible after input of a password.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
32  
3.1.4 COPYING FUNCTION USING THE LBA  
It is possible to load the complete user-specific data record (parameters) of a Power Controller  
(for instance no. 1) into the memory of the LBA (RAM), store it in the LBA (EEPROM) and then  
copy it into another Power Controller (for instance no. 2):  
PLUG LBA INTO POWER CONTROLLER NO. 1  
1. reload data (data is stored in the LBA RAM)  
2. storing in the LBA  
(data is copied into the LBA-EEPROM)  
After the waiting time unplug LBA from Power Controller 1.  
Plug LBA into Power Controller no. 2  
3. LBA -> Thyro-P  
After the waiting time data from LBA are in Power Controller 2.  
4. Save Thyro-P  
TAB. 7 COPYING FUNCTION USING THE LBA  
Data from Power Controller 1 have now been copied to Power Controller 2.  
ATTENTION  
Only parameters of equal Power Controllers (for instance type voltage, type current, phase  
number) may be copied.  
3.1.5 OPERATION DISPLAY  
On the operation display, one, two or three actual values are optionally displayed in double digit  
size. An example for the operation display able to be configured using parameters is shown  
below:  
U1  
I1  
PG  
456.7V  
1567.9A  
1234.8kW  
Status messages  
FIG. 7 OPERATION DISPLAY  
The operating data displayed are the values U, I and P (Pges for 3-phase system) of phase 1. It is  
also possible to display data of other phases. The lowest line is the status line; this is where the  
device configuration is displayed, if no indications are waiting. Otherwise, „status messages“ is  
displayed. By selecting the key, the indications are displayed:  
Status messages  
^v  
fault type, load, Power  
yyyymmdd  
limit  
hhmmss  
1250kW  
Controller type, limitations,  
etc. are notified with the  
corresponding time of day. etc.  
yyyymmdd  
hhmmss  
<360V  
undervoltage  
Download from Www.Somanuals.com. All Manuals Search And Download.  
33  
With the ǟ key it is possible to leave the status messages display. The operation display now  
appears without the word status message. Only when new information arrives does status message  
appear again in the bottom line of the operation display.  
Additionally, input error indications or further parameters may be stated, which are self-explaining  
in connection with the menu heading.  
As shown before, automatic switch to this display is made if more than one minute has passed  
since the last key has been pressed. The operation display is exited by simple acknowledgement  
(OK key).  
3.1.6 LINE DIAGRAM  
The line diagram has the same functionality as a page recorder. The „writing pen“ and therefore  
the current measurement value are found on the Y axis. The line diagram is scrolled left pixel by  
pixel. Measured value collection supplies one measured value each second. Because the time axis  
is resolved in 90 pixels, the following values result for the time bases from 1.5min up to 3h:  
TIME BASE  
1.5 min  
30 min  
1 h  
MEASURED VALUES PER TIME-PIXEL  
1 *  
20  
40  
3 h  
120  
*) for this resolution, no band display is possible  
TAB. 8 LINE DIAGRAM TIME BASE  
There are two display modes: band and average value display. In case of band display, each measu-  
red value is displayed unfiltered. The number of measured values displayed for each time pixel  
is shown in the above table.  
In case of average value display, the average value is formed from several measured values and  
displayed in one pixel.  
The „windmill“ icon on the LBA display shows current data transfer between LBA and Power  
Controller. In case of still or non-existant icon, the data transfer is faulty.  
To exit the line diagram, the OK key must be pressed twice.  
3.1.7 LAST FUNCTION  
If the OK key is pressed during operation display, then the LBA will display the main menu. If the  
lowest menu item last function is selected, then the menu is displayed which has been processed  
last before operation display.  
3.1.8 STATUS LINE  
The status line is the lowest line of each menu. It looks like this:  
1P VAR Trafo UxU  
Example for status line  
and may contain the following values:  
1P, 2P or 3P  
for the Power Controller type  
for the operating mode  
for the load type  
VAR, TAKT, SSSD  
Trafo, R-Last or RL-La.  
U, UxU, I, IxI or P  
for the control type  
TAB. 9 ELEMENTS OF THE STATUS LINE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
34  
3.1.9 LBA SUBMENUS WITH PASSWORD PROTECTION  
REMARK  
After password input, further parameters may be modified. These are mainly adjusting parameters  
required for achieving power control specifications. The modification of these parameters requires  
extended specialist knowledge (for instance by training) and is not required under normal circum-  
stances.  
3.2 CABINET INSTALLATION KIT (SEK)  
Using the cabinet installation kit, the LBA may be installed in switching cabinet doors with a thick-  
ness of up to 4 mm. It consists of an adaptor frame 96x72mm (cut-out dimensions 92x68mm) and  
a cable. Using the cable, the LBA is connected to the RS 232 interface of Thyro-P.  
The LBA locks in the adaptor frame and may only be removed with the cabinet door open. This  
enables an instructed specialist to set parameters (for instance adjustment to changing tools) and  
manual setting of set points (motor potentiometer) as well as for reading the actual value display  
without opening the cabinet door (VBG4). In order to avoid the accidental input of data by touch-  
ing the LBA, there is a self-activating parameterizing lock to enable (see Table 5).  
FIG. 8 CABINET  
INSTALLATION KIT  
If the LBA is connected to the Power Controller using a longer cable and does not operate, then  
this may possibly be remedied by increasing the supply voltage (open the jumper R 155 in the  
control device).  
ATTENTION  
In case of open jumper R 155, the LBA may not be connected to the Power Controller without  
cable (hazard of destruction). The position of the jumper on the control device PCB can be found in  
the component mounting diagram (Fig. 10, page 45).  
3.3 THYRO-TOOL FAMILY  
Thyro-Tool Familiy is an optional software for commissioning and visualization under Windows  
95/98/NT 4.0/XP and higher. It includes all functions of Thyro-Tool P and it is connected to Thyro-P  
via either one of the two standard interfaces (RS 232 respectively fibre optic).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
35  
Thyro-Tool Familiy may be employed as an alternative to LBA and as already stated above has the  
following functions, for which several windows may be opened simultaneously:  
• set point and actual value processing with overview display for 22 set point/actual value input  
options for Motorpoti and total set points.  
• loading, storing, modification and printing of parameters  
• comparison of parameters  
It is possible to compare two sets of parameters (Power Controller or data file). It is thus possible,  
to detect deviations from the desired configuration.  
• line diagrams of process data with printing function, as well as storage of faults (diverse measured  
values from different Thyristor Power Controllers may be displayed simultaneously).  
• bar diagram display  
It is possible to simultaneously display several bar diagrams. Each diagram has its own window.  
These can be adjusted in size and location. The configuration of the display may be stored.  
• simultaneous display of data and parameters from several Power Controllers  
• simultaneous connection of up to 998 Thyro-P Power Controllers using fibre optic distributors  
• settings of the interface (baud rate, com...)  
Thyro-Tool Familiy is supplied with a help system and installed on the PC under user guidance  
using an installation software.  
FIG. 9 EXAMPLE FOR THE USER INTERFACE THYRO-TOOL FAMILY  
In the above illustration, you can see windows containing:  
- 1 line diagram with several measured values  
- 4 bar diagram (several are possible), as well as  
- 1 parameter input section  
- 1 actual value display  
The location of the windows may be adjusted to the requirements by the user.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
36  
3.4 DIAGNOSIS / FAULT INDICATIONS  
Faults can occur in the load circuit and in the Power Controller itself. Often, the sequence of fault  
indications or events is decisive for a positive diagnosis. Diagnosis of unexpected operating behavi-  
our is performed by LEDs on the front panel of the control device, with parameter comparison  
(whereby the modified parameters may be listed), as well as by reading from the Thyro-P fault  
memory (data log). In Thyro-P, faults occurring and indications are entered in the fault memory with  
the event time and are preserved in case of mains outage as well. Up to 16 entries are possible.  
If further entries are made, then the first entry is overwritten. Therefore, the most current 16 events  
may be recalled at any time. Should faults or incidents occur, the selected operation display on the  
LBA will show status indications.  
The indication is of the format  
yyyymmdd hhmmss [ fault ] [ value ]  
The status line only appears in the operation display (see fig. 7).  
When using Thyro-Tool Familiy and an active line diagram, for any faults occuring their respective  
indications are displayed in a window and stored on disk associated with the line diagram.  
Using an optional bus interfecace (e.g. Profibus DP, a corresponding indication is automatically  
issued.  
The status indications (faults, warnings, messages) generated by Thyro-P may, as already menti-  
oned, be classified as load and as Power Controller faults. Depending on the application, warnings  
or status messages may be read.  
Data log  
yyyymmdd hhmmss  
[ fault no. ] [ limiting value ]  
All indications may be switched to the data log and the relays deviating from default settings.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
37  
EVENT NO.  
PRESET  
LOG  
STATUS MESSAGE  
RELAY  
1
2
3
4
5
6
7
8
9
Communication RS 232 interface active  
Communication fibre optic interface active  
Negative power (calculated value)  
Communication fault RS 232 or fibre optic interface  
Synchronous interface fault (for instance Profibus)  
External processor on the SSC signals fault  
after RESET - monoflop function  
Controller lock is active  
K3  
K2  
Data in the EEPROM invalid  
(then reload Thyro-P parameter memory using  
Thyro-Tool Familiy)  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
21  
22  
23  
24  
25  
Internal message  
Limiting exceeded  
Device overtemperature  
Quick circuit interruption has responded  
Internal message  
Failure in load circuit, collective failure  
Undercurrent in load circuit, when activated  
Overcurrent in load circuit, when activated  
Internal message  
DaLo  
Indication appears on return of supply  
Undervoltage in the power section  
Overvoltage in the power section  
Internal message  
Internal message  
K1  
Synchronization fault  
Collective fault  
(each fault leads to switching of the output)  
Internal message  
26  
27  
28  
29  
30  
Internal message  
Internal message  
Internal message  
For the operating mode MOSI:  
Power Controller has run into peak current limitation  
Temperature sensor, short circuit or sensor break  
31  
TAB. 10 ALLOCATION OF THE MESSAGE REGISTER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
38  
4. EXTERNAL CONNECTIONS  
This chapter describes external connections of the Thyro-P as well as all available terminal strips  
and signals as necessary. Shielded cables grounded on the Thyro-P side must be used for the con-  
nection of the control signals (setpoint inputs and analogue outputs). For the connections to RESET,  
Controller lock and QUIT, twisted cables must be used.  
Bus interfaces can be found in chapter 5 INTERFACES. To operate the Thyro-P at least the following  
signals described up to chapter 4.5 QUIT must be connected.  
4.1 POWER SUPPLY FOR THYRO-P  
In the case of types 400V and 500V, connecting the regulator to the power supply also connects the  
control device Thyro-P to the power supply (see also chapter POWER SUPPLY FOR THE CONTROL  
DEVICE A70). The control device for 690V types must be supplied separately.  
Details on connecting power supply can be taken from the chapters TECHNICAL DATA and con-  
necting diagrams. This particularly applies when using the control device in UL applications.  
4.2 POWER SUPPLY FOR THE CONTROL DEVICE A7  
The Thyristor Power Controller Thyro-P is fitted with a wide-band power supply. The mains connec-  
tion is designed for input voltages from 230V -20% to 500V +10% and nominal frequencies from  
45Hz to 65Hz. The power consumption is max. 30W. Depending on the switch mode power supply,  
a 100VA control transformer must be used.  
For the type ranges 400V (230-400V) and 500V nominal mains voltage, the control device is sup-  
plied directly from the power section. It is therefore a unit ready to connect.  
STRIP TERMINAL X1  
X1  
1
mains supply connected internally  
phase  
2
N or phase  
TAB. 11 STRIP TERMINAL X1  
REMARK  
If required, e.g. when operating with Profibus, the control device can also be supplied separately.  
With supply voltages outside the nominal range the control device must be supplied separately  
with an input voltage within the above-mentioned voltage range. The phase position of this control  
voltage is optional. In this case the plug (A70/X1) must be pulled.  
CAUTION  
The pulled plug has mains voltage of the load circuit! The new connecting lines must be fused  
according to the applicable regulations (plug see chapter 12).  
4.3 POWER SUPPLY FOR THE VENTILATOR  
With Thyro-P Thyristor Power Controllers furnished with integrated ventilators (HF types), the venti-  
lator must be supplied with a voltage of 230V 50/60Hz according to the connecting plans and the  
dimensional drawings. The ventilator’s power consumption is given in chapter 10, Technical Data.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
39  
ATTENTION  
The ventilator must run when the Power Controller is switched on.  
4.4 RESET  
The input RESET (terminals X5.2.12-X5.1.14) is separated from the remaining system by an opto-  
electronic coupler. By opening the RESET jumper the Thyristor Power Controller is locked (load:  
24V/20mA), i.e. the power sections are no longer triggered. On activating RESET, LED “ON” lights  
up red.  
Functional procedure:  
TERMINALS  
FUNCTION  
X5.12-14 closed  
X5.12-14 open  
Enables the power sections, Power Contr. in operation  
Power Controller out of operation, communication via interfaces not  
possible  
X5.12-14  
system reinitialisation  
is closed  
TAB. 12 RESET  
The hardware RESET must be applied when synchronising the software of several Power Controllers  
(chapter 6.2 Software synchronisation). If the Power Controller is equipped with a Bus option, a Bus  
RESET also ensues from the hardware RESET. Apart from opening the jumper terminal X5.2.12-  
X5.1.14, the hardware RESET is also activated by supply voltage OFF or by reducing the supply  
voltage at the Power Controller (A70-X1) to below 160V.  
4.4.1 SOFTWARE-RESET  
The RESET function can be activated by signals via the status register (software RESET). The soft-  
ware RESET does not influence the Bus function.  
4.5 CONTROLLER LOCK  
The input controller lock (terminals X5.2.15 and X5.1.14) is electrically identical to the input RESET  
(electrical data as under 4.4.).  
ATTENTION  
When activating controller lock, the LED „PULSE LOCK“ is lit and the control device remains com-  
pletely in operation. The total set point is therefore without effect, but the min. limiting values (TS-  
MIN, HIME) remain active. This enables securing a certain quantity of electrical energy at the load.  
TERMINALS  
FUNCTION  
X5.15-14 closed  
X5.15-14 open  
Power Controller operating  
control pulses OFF (default value) or pulse limit  
TAB. 13 CONTROLLER LOCK  
All other functions of the Power Controller remain in operation. The state of the signalling relay  
does not change (parameter-dependent) and communications remains active. After closing the  
controller lock jumper, the controller is back in operation.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
40  
4.6 QUIT  
The input acknowledge (Quit, X5.2.19) has a circuit identical with the input RESET. It must be  
short-circuited against ground (X5.1.14) so that any faults are acknowledged. The fault signalling  
relay is reset. The input must remain closed for at least 2 line periods to perform acknowledgement.  
After acknowledgement, the contactor must in turn be opened.  
Function:  
TERMINALS  
FUNCTION  
X5.19-14 open  
controller operating  
faults are reset  
X5.19-14 closed*  
* for at least 2 line periods  
TAB. 14 QUIT  
If the QUIT contact is reopened the Controller will reassume operation with its preset operating  
and control modes as well as its set point and limiting values.  
4.7 SET POINT VALUE INPUTS  
The set point inputs are described in chapter 2.2. Set point control characteristic.  
4.8 ASM INPUT  
This input (analog voltage signal) serves to measure the total current signal of the external apparent  
ohmic resistance. For further information refer to chapter ”ASM procedure“.  
4.9 ANALOG OUTPUTS  
The electrical values for current, voltage and power at the load as well as the set point are recorded  
by the Power Controller Thyro-P and may be optionally displayed using an external instrument or  
logged using a graph recorder.  
For connection of external instruments, there are three actual value outputs (terminals X5.2.32,  
X5.2.33, X5.2.34, against X5.1.13). The selectable signal levels are 0-10 volts, 0-20mA, 4-20mA or -  
setting different parameters at a maximum compliance voltage of 10V. In case of active ASM proce-  
dure, only two of these three analog outputs are freely available (terminal X5.2.32, X5.2.34).  
Each output has its own D/A converter. By setting parameters, it is possible to adjust the outputs  
to stored-program controls, measuring instruments, etc.  
For instance, the following values may be output:  
• currents, voltages or power of the individual phases, total power  
• minimum or maximum values  
• set points  
• phase angles  
The signals of the analog outputs are updated in each line (VAR) or TAKT period. Actual values  
always relate to the previous period. In operation mode VAR at a net period (e.g. 50Hz:20ms) and  
in operation mode TAKT at T0 (e.g. 1 sec.). Different factors (e.g. set point variations, load varia-  
tions, limitings and the influence of operating modes with SSSD and MOSI) give the actual value  
signals dynamic rations which can be smoothed with a smoothing stage. The MEAN (VALUE) para-  
meter is applied here. The following setting is recommended: MEAN(VALUE) = 25.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
41  
4.10 CURRENT TRANSFORMER  
ATTENTION  
By standard, each power section of the Power Controller has a current transformer. When using  
external current transformers, for instance on the secondary side of a transformer, these must be  
connected to the terminals X7.1 and X7.2 and terminated using a burden resistor! The burden  
resistor must be designed so that at nominal current a voltage drop of 1.0Vrms occurs at the bur-  
den resistance. For connection, take care to have the respective correct phase angle.  
The internal current transformers may not be shunted, because the burden resistor R 40 is on the  
control cards. If load current monitoring of the phase 2 (not controlled) is desired for Thyro-P 2P,  
then an external current transformer and an external voltage transformer must be provided for  
this purpose.  
CURRENT TRANSFORMER  
phase L1  
TERMINAL X7.2  
.11(k)  
TERMINAL X7.1  
.12(l)  
phase L2  
.21(k)  
.22(l)  
phase L3  
.31(k)  
.32(l)  
TAB. 15 CURRENT TRANSFORMER  
The following parameters must be checked or adjusted:  
HARDWARE PARAMETER  
current transformer  
type current  
xxxxx  
xxxxx  
xxx,xx  
UE_I  
I_TYP  
burden resistance  
R_BUERDE_I  
LIMITATIONS  
Irms maxI1  
xxxx  
A IEMA  
REMARK  
Current measuring in not-controlled phases  
Thyro-P 2P  
Although phase 2 is not controlled in Thyro-P 2P, it is possible to take measuring values during this  
phase. A current transformer corresponding to T1 must be used and burdened (see type overview).  
It is connected as in table 23 to X7.1.22 – X7.2.21.  
Thyro-P 1P  
As only phase 1 is controlled with Thyro-P 1P, the measuring systems of phase 2 and 3 can be used  
freely. The corresponding current transformers (with max. 1V at nominal current) must be applied  
and burdened. Connection is carried out as in table 23 to terminal strips X7.1.22 – X7.2.21 for  
“phase 2”, and to X7.1.32 – X7.2.31 for “phase” 3.  
The measuring values given do not influence the controller and are available for Bus interfaces,  
display and analog outputs. Parameter values must not be changed.  
4.11 VOLTAGE TRANSFORMER  
As standard, each power section is fitted with a voltage transformer for recording the load voltage.  
It is possible to measure voltages of up to 690V. The voltage transformers are wired to the control  
device A70 by the works.  
LOAD VOLTAGE  
phase L1  
TERMINAL X7.2  
TERMINAL X7.1  
.15  
.25  
.35  
.16  
.26  
.36  
phase L2  
phase L3  
TAB. 16 VOLTAGE TRANSFORMER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
42  
In case of the Power Controller type 2P, the voltage transformers output the voltages L1-L2 and  
L3-L1. To achieve a good resolution of the voltage measurement, 3 measuring ranges are provided.  
Selection of the ranges is performed by means of 4-pin bars, which have been set to the Power  
Controller type voltage by the works. The pin bars are found on the control device A70 above the  
terminal X7.  
MAINS  
SHORT CIRCUIT JUMPERS  
MAX.  
VOLTAGE  
X501, X502, X503  
MEASURING  
253V  
230V  
1 - 2  
2 - 3  
3 - 4  
400V  
440V  
500V respectively 690V  
760V  
TAB. 17 VOLTAGE MEASUREMENT JUMPER  
If the jumpers are changed, then a change of parameters is required.  
Hardware parameters  
Type voltage  
U emax  
U_TYP  
UEMA  
X501-3,1-2,2-3,3-4  
Mains voltage  
TYP-BEREICH  
U_NETZ_ANW  
(Thyro-Tool Family)  
REMARK  
Voltage readings in not-controlled phases  
Thyro-P 2P  
Although phase 2 is not controlled with Thyro-P 2P, it is possible to take measuring values during  
this phase. The voltage transformer suitable for standard rail assembly (order no. 2000000399) is  
to be used. Connection is made as in table 21 to X7.1.26 – X7.2.25. The maximum induced voltage  
of the transformer (incl. over-voltage) must be less than 50 volts.  
Thyro-P 1P  
As only phase 1 is controlled with Thyro-P 1P, the reading systems of phase 2 and 3 can be used  
freely. The voltage transformer suitable for rail assembly (order no. 2000000399) is to be used.  
Connection is made as in table 23 to terminals X7.1.26 – X7.2.25 for “phase 2” and X7.1.36 –  
X7.2.35 for “phase 3”.  
The measuring values do not influence the controller and are available for Bus interfaces, display  
and analog outputs. Parameter values must not be changed.  
4.12 OTHER CONNECTIONS AND TERMINAL STRIPS  
ROOT*  
X2.7  
BREAK CONTACT CLOSER  
Alarm relay K1  
Limiting K2  
Option K3  
X2.8  
X2.9  
X2.10  
X2.13  
X2.11  
X2.14  
X2.12  
X2.15  
* tie point  
TAB. 18 TERMINAL STRIP X2 FOR K1, K2, K3  
Download from Www.Somanuals.com. All Manuals Search And Download.  
43  
TERMINAL STRIP X5 IN THE CONTROL DEVICE  
X5.1  
5
FUNCTION  
+5V  
X5.2  
5
FUNCTION  
+5V  
13  
13  
13  
13  
13  
13  
21  
14  
14  
14  
14  
20  
ground 5V  
ground 5V  
ground 5V  
ground 5V  
ground 5V  
ground 5V  
-15V  
10  
11  
32  
33  
34  
16  
17  
12  
15  
18  
19  
20  
set point 1  
set point 2  
analog output 1  
analog output 2  
analog output 3  
ASM input  
GSE connection  
RESET  
ground 24V  
ground 24V  
ground 24V  
ground 24V  
+24V*  
controller lock  
SYT9 connection  
QUIT  
+24V*  
* Loading: IX5.1.20 + IX5.2.20 + IX21.9 ͨ max. 80mA  
TAB. 19 TERMINAL STRIP X5  
Terminal strip X6 in the control device  
At the terminal strip X6, wiring between the control device A70 and the control cards A1, A3 and  
A5 of the power section is performed by the works. Allocation of the terminal strip is as follows:  
X6  
11  
12  
13  
21  
22  
23  
31  
32  
33  
41  
42  
Name  
thyristor L1 neg.  
+5V  
thyristor L1 pos.  
thyristor L2 neg.  
+5V  
thyristor L2 pos.  
thyristor L3 neg.  
+5V  
thyristor L3 pos.  
input temperature sensor  
ground temperature sensor  
TAB. 20 TERMINAL STRIP X6  
Each thyristor is controlled by 20mA current supply switching to ground.  
The ventilator monitor is connected to the terminals X6.41 and X6.42 in separately ventilated  
devices (..HF). The temperature of the power section is monitored using a PT 1000 temperature  
sensor. In case of overheating of the power section, for instance caused by outage of the ventilator,  
a fault indication is generated and the alarm relay is activated (default values). The temperature  
may be enquired by the interfaces.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
44  
4.13 SYNCHRONIZATION  
By standard, each power section is fitted with a transformer for an input voltage of up to 690V.  
After filtering, the synchronization signal for control of the thyristors is generated from the secondary  
voltage. The connections are wired by the works. This includes the following terminals:  
TERMINAL STRIP X7  
X7.1  
12  
14  
16  
22  
24  
26  
32  
34  
36  
X7.2  
11  
13  
15  
21  
23  
25  
31  
33  
35  
NAME  
current transformer phase L1  
sync phase L1  
load voltage phase L1  
current tranformer phase L2  
sync phase L2  
load voltage phase L2  
current tranformer phase L3  
sync phase L3  
load voltage phase L3  
TAB. 21 TERMINAL STRIP X7  
For the synchronization the following jumpers are necessary on the componentry of the control  
device.  
THYRO-P  
SHORT CIRCUIT JUMPER  
1P  
2P  
3P  
X507  
X507  
-
X508  
-
-
TAB. 22 SYNCHRONIZATION JUMPER  
Download from Www.Somanuals.com. All Manuals Search And Download.  
45  
4.14 COMPONENT MOUNTING DIAGRAM CONTROL DEVICE  
BR155  
BR806  
BR808  
X700  
X702  
X706  
X701  
X707  
X713  
X603  
+5V output  
5
for poti, etc.  
5
X509  
setpoint 1 10  
setpoint 2 11  
analog output 1 32  
analog output 2 33  
analog output 3 34  
M 5V setpoint 1 13  
M 5V setpoint 2  
13  
X510  
X201  
X221  
X222  
GND 5V, 0-20mA, 10V 13  
GND 5V, 0-20mA, 10V 13  
GND 5V, 0-20mA, 10V 13  
ASM input  
GND 5V  
-3,3V  
GND 24V, open=blocked  
GND 24V, open=blocked  
M 24V  
16  
17  
12  
15  
18  
19  
20  
signal  
13  
21  
14  
14  
14  
14  
20  
pulse lock  
controller lock  
SYT 9  
acknowledgement  
+24V output  
function  
V261  
V271  
V281  
R147  
GND 24V, short circuit  
+24V  
application reference  
X501  
X502  
X503  
X7.1 (-)  
X7.2 (+)  
1
2
X1  
X 6  
FIG. 10 FILE COMPONENT MOUNTING DIAGRAM CONTROL DEVICE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
46  
5. INTERFACES  
Necessary process optimization as well as the requirements made of high, continuous and docu-  
mentable quality in production processes often require the use of digital process communications.  
It allows interlinking of many signals and enables their evaluation in an efficient manner.  
FIG. 11 INTERFACES OF THYRO-P  
Download from Www.Somanuals.com. All Manuals Search And Download.  
47  
With the Power Controller Thyro-P, the following interfaces may be used for this (see also fig. 11 on  
previous page):  
• X10, RS 232  
• X30, fibre optic receiver  
• X31, fibre optic transmitter  
as well as optional interfaces, for instance  
• X20, bus interface, e.g. for Profibus DP  
All internally processed data like current, voltage, power, set point value, limitations, etc. may be  
enquired, processed and modified during operation (online operation) in master-slave process.  
Under assistance of corresponding automation technology, it is possible to do without connection  
of process controls, potentiometers, instruments, LBA, etc.  
The existing interfaces may operated simultaneously, so that for instance the following system  
configuration would be possible: a stored-program control via Profibus supplies the set points,  
a PC visualizes (fibre optic interface/Thyro-Tool Familiy) the data and on location the device status  
and selected operating values are displayed via LBA (using the RS 232).  
Therefore, the Power Controller Thyro-P is transparent to all levels of production and the process  
may therefore be securely handled.  
5.1 RS 232 INTERFACE  
The isolated RS 232 interface is provided for direct connection of an LBA (with cabinet installation  
kit also indirect via cable) or a PC. Setting of parameters of the interface is performed using Thyro-  
Tool Familiy or LBA. The default baud rate is set to 9600 baud, no parity, 8 data bits, 1 stop bit.  
The following illustration shows connection of a Thyro-P to a PC using the RS 232 interface (also  
possible via fibre optic or Profibus).  
RS 232  
COM 1  
or  
COM 2  
FIG. 12 CONNECTION OF A PC TO  
THYRO-P VIA RS 232  
For connecting the PC, an RS 232 cable is required. On the Thyro-P side, a 9-pin sub-D plug and on  
the PC side a 9-pin sub-D socket must be available.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
48  
The connecting socket X10 of the Power Controller is allocated as follows (1:1 connection):  
FIG. 13 X10-ALLOCATION  
ATTENTION  
The LBA receives its power supply (+5V) via pin 8 of the socket X10. It is imperative that this voltage  
is not short-circuited. Otherwise, damage to Thyro-P may be incurred.  
If a PC is connected to the RS 232 interface, then this pin should be left unconnected, since it is not  
needed for data transfer.  
Generally, all devices with an RS 232 interface may communicate with Thyro-P. The protocol used  
may simply be created by the user himself.  
For this purpose, a detailed description of the protocol used may be requested from AEG PS (refer  
to application document).  
5.2 FIBRE OPTIC INTERFACE  
This widely used interface (LL, X30 LLE blue, X31 LLS grey) for quick and secure data transfer is  
fitted to Thyro-P as standard and enables connection of up to 998 Thyro-P Power Controllers. Due  
to the good interference immunity, larger distances can be bridged and data can be transferred at  
higher speeds.  
To install a fibre optic system, the following interface components can be used.  
5.2.1 FIBRE OPTIC DISTRIBUTION SYSTEM  
Using the components described below, a complete fibre optic system for connection of up to 998  
Thyro-P may be created.  
SIGNAL CONVERTER RS 232 / FIBRE OPTIC  
Connection of the fibre optic to the PC interface (RS 232) is performed using the fibre optic / RS 232  
signal converter shown below. Power supply is via the plug-in power supply enclosed.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
49  
to the plug-in power supply  
fibre optic transmitter (LLS) X30  
fibre optic receiver (LLE) X31  
FIG. 14 SIGNAL CONVERTER RS 232/FIBRE OPTIC  
LLV.V  
The fibre optic distributor supply LLV.V is the basic component for the fibre optic system. It serves  
to connect star distributors and to amplify the light signals received. Its power supply is sufficient  
for supply of five fibre optic distribution components of the type LLV.4.  
The amplification of LLV.V in the fibre optic data path is sufficient for increasing the distance for  
each LLV.V by about 50 m, so that overall longer transmission paths are possible then.  
LLV.4  
The fibre optic distributor LLV.4 is connected to the base component LLV.V. It is able to distribute  
the optical signal to respectively receive from four connections and therefore multiplies the signal  
from the computer to Thyro-P by four units each. The maximum distance from LLV.4 to Thyro-P  
should not exceed about 25 m.  
In case of optimum installation conditions (number of bends, connection mounting, etc.), the dis-  
tances stated in the following table may be realized:  
DEVICE PC  
LLV.V  
50 m  
50 m  
50 m  
25 m  
LLV.4  
– –  
THYRO-P  
25 m  
25 m  
25 m  
– –  
PC  
– –  
LLV.V  
LLV.4  
50 m  
– –  
– –  
– –  
Thyro-P 25 m  
25 m  
TAB. 23 FIBRE OPTIC DISTANCES  
Download from Www.Somanuals.com. All Manuals Search And Download.  
50  
The following figure shows the fibre optic system with LLV, Thyro-P and PC.  
FIG. 15 SCHEMATIC DIAGRAM FIBRE OPTIC THYRO-P WITH LLV AND PC  
Download from Www.Somanuals.com. All Manuals Search And Download.  
51  
5.3 BUS INTERFACES (OPTION)  
The control device of Thyro-P may be optionally fitted with interface cards for interfaces customary  
for the industry. In case of bus systems not listed, please enquire about availability.  
5.3.1 PROFIBUS-DPV1  
With a Profibus interface card (order no. 2000000393) it is possible to connect the Thyro-P to a  
wide ranging Bus system. For use of Thyro-P in an automation network with SIEMENS PCS7,  
software modules are available (at SIEMENS).  
The Profibus slot card is plugged into the front of the control device and is immediately ready to  
operate after parametrization. In case of Profibus control, the control device should be supplied  
separately, so that should the power supply be switched off, the Power Controller is not interrupted  
resulting in an alarm message. The connector supplied must be removed (see chapter 4.2).  
Three 24V inputs are additionally available, which may be polled via Profibus (for instance for swit-  
ching state, power interruptor, monitoring the cabinet ventilator, monitoring the cabinet door, etc.).  
The Profibus option includes  
• 1 Profibus slot card  
• 1 diskette for configuration of Thyro-P as Profibus slave,  
• 1 covering frame for secure fixing of the slot card,  
• 1 short instruction booklet  
ATTENTION  
The mounting of the option must be made in voltageless state.  
GENERAL  
Up to 125 slaves may be connected to a Profibus system. 32 slaves are possible for each Profibus  
segment. Coupling of individual segments is performed using so-called repeaters. Profibus systems  
may be organized as line, bus or tree structures. Besides the usual electrical connections (RS 485  
technology), it is possible, for instance in highly interfering environment (magnetic fields, etc.) to  
use fibre optic as transmitting medium.  
The line length depends on the respective transmission rate and is possible up to 1200m (also refer  
to the table).  
Baud rate [kbits/s]  
Line length [m]  
9.6  
19.2  
45.45  
1200  
93.75  
1200  
187.5  
1000  
500  
400  
1500  
200  
1200  
1200  
TAB. 24 PROFIBUS BAUD RATES  
PROFIBUS SLOT CARD  
The Profibus slot card (about 86 x 70 mm) has two 9-pin SUB-D sockets on the front side. On the  
other side, there is a 9-pin SUB-D plug to be inserted into the Thyro-P control device. The Profibus  
slot card for instance contains driver circuits, galvanic separation for the bus circuit as well as a  
microcontroller for controlling bus access and other functions.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
52  
X21  
4 inputs for  
Profibus  
LED  
X24  
X20  
connection  
Thyro-P  
Profibus  
connection  
FIG. 16 PROFIBUS SLOT CARD  
After switching on Thyro-P, it will automatically detect the Profibus slot card. On the Thyro-P side,  
the device address must be set using the LBA or Thyro-Tool Familiy.  
After configuration of the Profibus, Thyro-P is ready for operation on the Profibus.  
CONNECTION TO THE PROFIBUS  
The Profibus is connected to the 9-pin SUB-D socket X20. The usual plug (see table) or an OLP  
module (fibre optic) may be used for this.  
The following plugs are recommended  
ORDER NO.  
DESCRIPTION:  
(SIEMENS)  
6ES7 972-0BA40-0XA0  
6ES7 972-0BA30-0XA0  
35° cable outlet including terminating resistors  
30° cable outlet without terminating resistors  
For connection of the OLP modules (Profibus via fibre optic), a 5V power supply voltage is provided  
on the Profibus socket X20, pin 6. This bears a load of at max. 80mA.  
TERMINATING RESISTORS  
Within a Profibus segment, terminating resistors must be switched in the first and the last device.  
Because the Profibus slot card does not have internal terminating resistors, plugs containing inte-  
grated terminating resistors must be used and these must be switched on, if the first or last device  
is a Thyro-P!  
REMARK  
FAILURE OF THYRO-P OR PROFIBUS  
If the Profibus fails during operation of Thyro-P, set points or actual values cease to be transmitted.  
Thyro-P continues to operate using the last current set point. If the Thyro-P fails as Profibus slave,  
then this fault is signaled on the Profibus system. If the RESET function on Thyro-P is activated,  
there will also be a RESET period the Bus function is interrupted.  
Additional digital inputs  
On the 9-pin SUB-D plug X21, the Profibus slot card has four digital inputs which are mapped to  
the 1st data byte of the reply from Thyro-P.  
Pin assignment of the plug is as follows:  
Download from Www.Somanuals.com. All Manuals Search And Download.  
53  
X21  
1
ASSIGNMENT  
PE (potential earthing)  
ground M1  
2
3
input 0/M1  
4
input 1/M1  
5
ground M24  
ground M2  
input 2/M2  
input 3/M2  
+24V  
/ 24V supply for the Profibus card  
6
7
8
/ special function = Motorpoti enable  
/ 24V supply for the Profibus card  
9
* Loading: IX5.1.20 + IX5.2.20 + IX21.9 max. 80mA  
TAB. 25 PIN ASSIGNMENT X21  
The inputs 0 and 1 refer to ground M1, the inputs 2 and 3 refer to ground M2. To connect simple  
transmitters like limit switches, etc., a 24V power supply is also available. The input IN3 (PIN 8) is  
taken up by a special function.  
Therefore, connection could for instance be as follows:  
local: Switch closed  
remote: Switch open  
FIG. 17 SPECIAL FUNCTION MOTORPOTI  
Download from Www.Somanuals.com. All Manuals Search And Download.  
54  
If the special function Motorpoti is not applied, 3 free inputs of the Bus card are available.  
Set out below are the most important features of the Profibus option.  
FIG. 18 SPECIAL INPUTS  
DETAILS OF THE PROFIBUS  
Further details for use of Thyro-P with Profibus like  
• organization of the messages  
• parameter setting messages  
(setting which data is to be cyclically transmitted)  
• cyclical parameters (REAL data format)  
• PKW interface, PNU table  
• diagnostic indications  
• GSD file  
are described in a separate file on the Profibus data media.  
The user can choose between different configurations and establish, for instance, the number of  
actual values etc. within them.  
HARDWARE CHARACTERISTICS  
The Profibus card has the following characteristics:  
• transmission speeds of 9600 Baud up to 12 MBaud  
• RS 485 galvanically separated up to 140V  
• optional fibre optic interface  
• 5V power supply, pin 6 max. 80mA  
• 3 additional inputs  
• 24V stored-program controller compatible  
• current consumption <20mA  
• galvanically separated (140V)  
IDENTIFICATION NO.  
A Thyro-P with Profibus slot card corresponds to a Profibus device according to EN 50170.  
Ident no.:  
06B4  
Associated GSD-file:  
PSS106B4.GSD  
Download from Www.Somanuals.com. All Manuals Search And Download.  
55  
5.3.2 MODBUS RTU  
With the Modbus interface component a connection is possible between Thyro-P and the wide-  
spread Modbus RTU. The slot card is inserted into the front of the control device and is ready for  
operation after parameterization. The control device must be supplied separately so that should  
the power supply be switched off, the Power Controller is not interrupted resulting in an alarm  
message (see chapter 4.2).  
As shown in both previous figures, Modbus RTU can also use either the special function Motorpoti  
or three available digital inputs (24V DC).  
Using commercial gateways it is possible to interconnect to various field buses as well as Ethernet  
systems with TCP/IP protocol.  
Further information can be obtained from the operating instructions of the Modbus option.  
FIG. 19 MODBUS SLOT CARD  
5.3.3 DEVICENET  
With the DeviceNet interface component (order no. 2.000.000.394) a connection is possible bet-  
ween Thyro-P and the wide ranging bus system. The slot card is inserted into the front of the con-  
trol device and is ready for operation after parameterization. The control device must be supplied  
separately so if the power supply is switched off, the power controller is not interrupted resulting in  
an alarm message (see chapter 4.2).  
DeviceNet can also use either the special function motor potentiometer or three available digital  
inputs (24 V DC).  
Download from Www.Somanuals.com. All Manuals Search And Download.  
56  
6. MAINS LOAD OPTIMIZATION  
Mains load optimization (option) is possible in multiple controller applications. The application of  
mains load optimization offers substantial advantages: reduction of mains load peaks and mains  
reactions, smaller sizes (for instance for the transformer, feed and other installations) and associated  
smaller operating and investment cost. Mains load optimization is possible in a dynamic (ASM  
process) and a static (SYT-9 process) mode. Both modes may also be used in combination with the  
Thyristor Power Controller Thyro-M.  
6.1 SYT-9 PROCEDURE  
A process for static mains load optimization: minimizes mains load peaks and associated mains  
reaction shares. For the SYT-9 process, set points and load changes are not automatically included  
in mains load optimization.  
The SYT-9 process requires an additional component. For Thyro-P, it should only be employed in  
connection with already installed controllers (Thyro-M, Thyrotakt MTL) under SYT-9 process.  
Then, the pulse of the SYT card must be connected to the terminal X5.1:18 and ground to X5.1:14.  
On the Thyro-P Power Controller, the jumper X201 (behind X5) must be pulled off. For this purpose,  
the texts BAL 00180 and operating instructions SYT-9 must be observed as described under Thyro-M.  
THYRO-P  
SYT9 NO. 1  
THYRO-P  
SYT9 NO. 1  
NO.  
1
NO.  
1
X5.2.5 - A10  
X5.2.18 - C10  
2
-
-
-
-
-
-
-
-
A12  
A14  
A16  
A18  
A20  
A22  
A24  
A26  
2
-
-
-
-
-
-
-
-
C12  
C14  
C16  
C18  
C20  
C22  
C24  
C26  
3
3
4
4
5
5
6
6
7
7
8
8
9
9
Connection of up to 9 Thyro-P at one SYT9-Module  
6.2 SOFTWARE SYNCHRONIZATION  
By means of different settings in the storage location SYNC_Adresse, a different startup of the  
individual Power Controllers (counter x 10ms) may be achieved. The counter is set to 0 after  
switching on the mains or RESET. While the counter is running, the Power Controller is switched  
passive, as during controller lock.  
It is possible to enter values in SYNC_Adresse larger than the clock time T0. Then, startup of the  
Power Controller is only during the next clock time. For instance, in an emergency power plant,  
slow switching of the total load is possible. The max. delay is 65535 x 10ms. This value also forms  
the base setting for the ASM process.  
6.3 ASM PROCEDURE (PATENTED)  
In systems, in which several equal Power Controllers are operated in the operating mode TAKT, the  
ASM process may be sensibly used for dynamic and automatic mains load optimization in multiple  
Power Controller applications. This patented world premiere independently minimizes mains load  
peaks and therefore mains reaction shares during the current process. In case of the ASM process  
(automated synchronization of multiple controller applications), changes in set point and load (for  
instance due to temperature-dependent load) are included in mains load optimization online. Espe-  
cially when using heating elements with a large aging effect, which during new operation have high  
current amplitudes with short startup time, lower investment cost may be achieved. For the ASM  
Download from Www.Somanuals.com. All Manuals Search And Download.  
57  
process the controller requires an ASM control device. An additional burden resistor is used for all  
controllers. Schematic wiring of Power Controllers for the ASM process can be seen in the following  
illustration:  
Power  
Power  
Controller 1  
Controller 2  
D
D
D
D
A
A
A
A
0-20mA  
0-20mA  
X5.2.16  
X5.2.33  
twisted/shielded  
Uburden  
X5.1.13  
Uburden = ( I1 +...+ In ) x Rburden  
Uburden = 0 -10 volts  
total burden  
FIG. 20 ASM WIRING  
When using the ASM option, the analog output 2 (X5.2.33 against ground X5.1.13) becomes an  
output proportionate to the current during the on-period TS. All Power Controllers connected to  
synchronization work on the same external burden. The burden resistor is calculated approximately  
as  
Rburden [k] = 10V / (n x 20mA)  
n = number of Power Controller  
The burden voltage is measured at the ASM input. The Power Controller searches within the clock  
control the place with the lowest mains load.  
Due to this automated, independent procedure, the process chain is ensured through the tempe-  
rature control circuit and the Power Controller without effects; negative effects like flicker and sub-  
harmonics of the mains frequency are balanced out during a current dynamic process. In this case,  
unfavorableshort-term overlapping may occur, for instance after set point jumps or voltage swing.  
The application document ASM-procedure gives further information on this.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
58  
7. CONNECTING DIAGRAMS  
7.1 1-PHASE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
59  
7.2 2-PHASE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
60  
7.3 3-PHASE  
Download from Www.Somanuals.com. All Manuals Search And Download.  
61  
8. SPECIAL REMARKS  
8.1 INSTALLATION  
The installation orientation of Thyro-P is vertical, so that ventilation of the thyristors fastened to  
heat sinks is ensured. In case of cabinet mounting, additionally sufficient ventilation of the cabi-  
net must be ensured. The distance between Power Controller and the bottom should be at least  
100mm; the distance to the ceiling 150mm. The devices may be installed next to each other with-  
out lateral distance. Heating up of the device by heat sources must be avoided. The dissipation of  
the Power Controller is stated in the table chapter type overview.  
Grounding must be performed according to local regulations of the utility company (grounding  
screw for protective conductor connection).  
8.2 COMMISSIONING  
The device must be connected to the mains and the associated load according to the wiring  
diagrams.  
REMARK  
It must be observed that with 1P, terminal A1 X1:3 is connected to the U2 on the opposite load  
side. With 2P it must be observed that terminal A1 X1:3 is connected to the non-controlled phase.  
Depending on connection system of the load (star, delta, etc.), it must be ensured that the load vol-  
tage transformers in the power sections are wired correctly (terminal strip X1 of the power section).  
The correct terminals may be found in the connecting diagrams.  
If the units 1P and 2P are operated at over 600 V and without load at the output side, voltages can  
occur above input voltage at the connection points U2 and W2. In this case, an additional 690 V  
damping card is to be used. (Section 12, Accessories and Options)  
On delivery, the device is parameterized adjusted to the respective power section. The operating  
mode TAKT is set. If a different operating mode is desired, then the user must set this using the  
LBA, PC, etc. Generally, the standard parameters (see menu list) should be reviewed and adjusted  
to the respective conditions for use by the user (for instance operating mode, control mode, limi-  
tations, monitoring, times, characteristics, actual value outputs, fault indications, relays, time and  
date, etc.).  
Besides the load, some control signals must be connected as well (refer to chapter 4). The following  
signals are always required for operation of the device:  
Set point  
(terminal 10 or 11/or via interfaces)  
RESET  
(on ground, on terminal 12, jumper set as standard)  
(on ground, on terminal 15, jumper set as standard)  
Regular inhibit  
If the RESET is not connected, then the device is in reset state and is not operating (LED „ON“  
shows red light), i.e. no communications is possible via interface. Further details of the RESET are  
described in chapter 4.4. If the regulator inhibit is not connected, then the device is fully operable,  
but the power section is only controlled using the values of the minimal limitations (LED „PULSE  
LOCK“ is on). Further details on the regulator inhibit may be found in the chapter 4.5 of the same  
name.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
62  
ATTENTION  
The controller lock may also be set via the interfaces!  
ATTENTION  
The control device is to be operated only with casing.  
8.3 SERVICE  
The devices delivered have been tested according to the state of the art and have been produced  
to a high quality standard (DIN EN ISO 9001). Still, should any faults or problems occur, our 24 hour  
service hotline, Tel.: +49 (0) 2902/763-100 is available to you.  
8.4 CHECKLIST  
No frontside LED is on:  
• for 690V devices, the power supply for the control device A70 to be provided by the customer is  
missing. (Attention, maximum nominal input voltage 500V)  
• check voltage at terminal X1.1 and X1.2 of the control device A70  
• check semiconductor fuse and the fuses F2 and F3 on the controller card A1.  
CAUTION  
In any case, set the device voltageless and check if it is voltageless  
Terminal X1.3 on the controller card A1 not connected.  
• if the semiconductor fuse is defective, then the following parameters must be checked in case of  
transformer load for the operating modes TAKT and SSSD:  
phase angle of the first half-wave (phase angle 1) = 60 degrees;  
possibly optimize. Check for the model type 1P, 2P or 3P  
Menu: Parameters/Operating mode/Number of phases controlled 1 2 3)  
No load current  
• RESET X5.2.12 is not jumpered for X5.1.14 (LED ON lit in red)  
• supply voltage of the control device outside of the tolerable range  
• controller lock X5.2.15 is not jumpered for X5.1.14 (LED PULSE LOCK is on)  
• no set point is set. Using the LBA, check the total set point (effective total), or measure set point  
on X5.2.10 and X5.2.11.  
• set points are not cleared (STD, Local, Remote, ANA)  
• parameterization of the set point inputs 20mA, 5V, 10V, does not matched to output of the  
temperature controller  
• parameters STA and STE of the control characteristic are wrong  
• parameter for linkage of the set points is not set to ”ADD“  
• parameters IEMA, UEMA, PMA are set too small  
• controller parameters Ti and Kp are set too large.  
CAUTION  
Check fuses on the controller cards A1, A3, A5. In any case, set the device voltageless and check if  
it is voltageless.  
• Load connection by the customer is missing (only for type 1P).  
Check connection on A1 terminal X1.3.  
• Check synchronization voltage at the control device A70 at the terminal blocks X7.1 and X7.2.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
63  
The thyristors are set to full scale  
• Was the set point set via motor potentiometer function? Check value using the LBA.  
• Check the control characteric (STA, STE, ADD).  
• Controller feedback signal available? Check current transformer and voltage transformer  
connections at the terminal blocks X7.1 and X7.2.  
• Parameters TSMI and H_IE, Urms min, Irms min, Pmin are larger than 0.  
• Controller parameters Ti and Kp are set too small.  
• Parameters IEMA, UEMA, PMA are set too large or the load current is too small.  
• Possibly thyristor short-circuit  
REMARK  
In case the load current is too small (connection of a test load), the device must be parameterized  
for U, U2 control or ”without control“. The regulation limits continue to remain active. Connection  
of a minimal load (e.g. 100W lightbulb) is necessary.  
Measures in case of other malfunction  
• Evaluation of incident register (data logger) with LBA or Thyro-Tool  
• Comparison of actual parameters of Thyro-P with parameters in type list.  
• Comparison of actual parameters of Thyro-P with the system dependent parameters stored in the  
PC.  
• Correct number of controlled phases ((parameters)  
• With activated trouble signal relay Evaluation which faults led to a response, eliminate the fault.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
64  
9. TYPE OVERVIEW  
9.1 TYPE RANGE 400 VOLTS  
TYPE VOLTAGE 230-400 VOLTS  
TYPE  
TYPE POWER  
(KVA)  
DISSIPA- DIMENSIONS  
WEIGHT DIM.  
TEMP.  
CURRENT BURDEN  
SEMICON-  
CURRENT  
(A)  
TION  
(W)  
(MM)  
W
(NET ABOUT DRAW. CHARACTE- TRANSF.  
RESISTOR DUCTOR FUSE*  
230V  
400V  
H
D
KG)  
(NO.)  
RISTIC (NO.) T1  
R40 (Ω)  
F1 (A)  
508  
THYRO-P 1P  
37 H  
8
15  
30  
105  
150 320 229  
150 320 229  
150 320 229  
200 320 229  
200 320 229  
200 370 229  
174 414 340  
174 414 340  
240 685 505  
240 685 505  
521 577 445  
603 577 470  
6
260  
1
1
2
2
2
2
3
3
4
5
6
7
100/1  
2.70  
1.30  
0.91  
1.10  
1.10  
1.00  
1.00  
1.00  
1.00  
1.00  
0.91  
1.00  
50  
75 H  
17  
25  
130  
175  
6
6
100/1  
100/1  
150/1  
200/1  
300/1  
500/1  
700/1  
1000/1  
1500/1  
2000/1  
3000/1  
100  
180  
110 H  
44  
130 H  
30  
52  
190  
8
263  
200  
170 H  
39  
68  
220  
8
315  
280 HF  
495 HF  
650 HF  
1000 HF  
1500 HF  
2100 HF  
2900 HF  
64  
112  
198  
260  
400  
600  
840  
365  
9
265  
266  
350  
114  
149  
230  
345  
483  
595  
15  
15  
35  
35  
50  
62  
630  
750  
900  
1450  
1775  
2600  
3400  
268  
2x1000  
4x900  
4x1000  
4x1500  
270  
271  
667 1160  
THYRO-P 2P  
37 H  
15  
30  
25  
52  
175  
220  
225 320 229  
225 320 229  
225 320 229  
325 320 229  
325 320 229  
325 397 229  
261 414 340  
261 414 340  
410 685 505  
410 685 505  
526 837 445  
10  
10  
10  
12  
12  
15  
22  
22  
54  
54  
84  
272  
275  
1
1
2
2
2
2
3
3
4
5
6
7
100/1  
100/1  
100/1  
150/1  
200/1  
300/1  
500/1  
700/1  
1000/1  
1500/1  
2000/1  
3000/1  
2.70  
1.30  
0.91  
1.10  
1.10  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
50  
100  
75 H  
110 H  
44  
76  
310  
180  
130 H  
52  
90  
350  
200  
170 H  
68  
118  
194  
343  
450  
693  
410  
315  
280 HF  
495 HF  
650 HF  
1000 HF  
1500 HF  
2000 HF  
2750 HF  
111  
197  
259  
398  
700  
277  
278  
350  
1150  
1465  
2865  
3510  
4800  
6200  
630  
900  
280  
2x1000  
4x900  
4x1000  
4x1500  
597 1039  
796 1385  
1095 1905  
282  
283  
603 837 470 107  
THYRO-P 3P  
37 H  
15  
30  
25  
52  
330  
400  
300 320 229  
300 320 229  
300 320 229  
450 320 229  
450 320 229  
450 397 229  
348 430 340  
348 430 340  
575 685 505  
575 685 505  
14  
14  
14  
17  
17  
20  
30  
30  
74  
74  
284  
287  
1
1
2
2
2
2
3
3
4
5
6
7
100/1  
100/1  
100/1  
150/1  
200/1  
300/1  
500/1  
700/1  
1000/1  
1500/1  
2000/1  
3000/1  
2.70  
1.30  
0.91  
1.10  
1.10  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.10  
50  
100  
75 H  
110 H  
44  
76  
540  
180  
130 H  
52  
90  
560  
200  
170 H  
68  
118  
194  
343  
450  
693  
650  
315  
280 HF  
495 HF  
650 HF  
1000 HF  
1500 HF  
1850 HF  
2600 HF  
111  
197  
259  
398  
1070  
1800  
2265  
4370  
5335  
6900  
8700  
289  
290  
350  
630  
900  
292  
2x1000  
4x900  
4x1000  
4x1500  
597 1039  
736 1281  
1035 1801  
526 1094 445 119  
603 1094 470 152  
294  
295  
* number of fuses per path of power section, built in  
Download from Www.Somanuals.com. All Manuals Search And Download.  
65  
9.2 TYPE RANGE 500 VOLTS  
TYPE VOLTAGE 500 VOLTS  
TYPE  
TYPE POWER  
(KVA)  
DISSIPA- DIMENSIONS  
WEIGHT DIM.  
TEMP.  
CURRENT BURDEN  
SEMICON-  
CURRENT  
(A)  
TION  
(W)  
(MM)  
W
(NET ABOUT DRAW. CHARACTE- TRANSF.  
RESISTOR DUCTOR FUSE*  
H
D
KG)  
(NO.)  
RISTIC (NO.) T1  
R40 (Ω)  
F1 (A)  
508  
THYRO-P 1P  
37 H  
18  
38  
105  
130  
150 320 229  
150 320 229  
150 320 229  
200 320 229  
200 320 229  
200 370 229  
174 414 340  
174 414 340  
240 685 505  
240 685 505  
521 577 445  
603 577 470  
6
260  
1
1
2
2
2
2
3
3
4
5
6
7
100/1  
2.70  
1.30  
0.91  
1.10  
1.10  
1.00  
1.00  
1.00  
1.00  
1.00  
0.91  
1.00  
50  
75 H  
6
6
100/1  
100/1  
150/1  
200/1  
300/1  
500/1  
700/1  
1000/1  
1500/1  
2000/1  
3000/1  
100  
180  
110 H  
55  
175  
130 H  
65  
190  
8
263  
200  
170 H  
85  
220  
8
315  
280 HF  
495 HF  
650 HF  
1000 HF  
1500 HF  
2100 HF  
2900 HF  
140  
248  
325  
500  
750  
1050  
1450  
365  
9
265  
266  
350  
595  
15  
15  
35  
35  
50  
62  
630  
750  
900  
1450  
1775  
2600  
3400  
268  
2x1000  
4x900  
4x1000  
4x1500  
270  
271  
THYRO-P 2P  
37 H  
32  
65  
175  
220  
225 320 229  
225 320 229  
225 320 229  
325 320 229  
325 320 229  
325 397 229  
261 414 340  
261 414 340  
410 685 505  
410 685 505  
526 837 445  
10  
10  
10  
12  
12  
15  
22  
22  
54  
54  
84  
272  
275  
1
1
2
2
2
2
3
3
4
5
6
7
100/1  
100/1  
100/1  
150/1  
200/1  
300/1  
500/1  
700/1  
1000/1  
1500/1  
2000/1  
3000/1  
2.70  
1.30  
0.91  
1.10  
1.10  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
50  
100  
75 H  
110 H  
95  
310  
180  
130 H  
112  
147  
242  
429  
563  
866  
1300  
1732  
2381  
350  
200  
170 H  
410  
315  
280 HF  
495 HF  
650 HF  
1000 HF  
1500 HF  
2000 HF  
2750 HF  
700  
277  
278  
350  
1150  
1465  
2865  
3510  
4800  
6200  
630  
900  
280  
2x1000  
4x900  
4x1000  
4x1500  
282  
283  
603 837 470 107  
THYRO-P 3P  
37 H  
32  
65  
330  
400  
300 320 229  
300 320 229  
300 320 229  
450 320 229  
450 320 229  
450 397 229  
348 430 340  
348 430 340  
575 685 505  
575 685 505  
14  
14  
14  
17  
17  
20  
30  
30  
74  
74  
284  
287  
1
1
2
2
2
2
3
3
4
5
6
7
100/1  
100/1  
100/1  
150/1  
200/1  
300/1  
500/1  
700/1  
1000/1  
1500/1  
2000/1  
3000/1  
2.70  
1.30  
0.91  
1.10  
1.10  
1.00  
1.00  
1.00  
1.00  
1.00  
1.00  
1.10  
50  
100  
75 H  
110 H  
95  
540  
180  
130 H  
112  
147  
242  
429  
563  
866  
1300  
1602  
2251  
560  
200  
170 H  
650  
315  
280 HF  
495 HF  
650 HF  
1000 HF  
1500 HF  
1850 HF  
2600 HF  
1070  
1800  
2265  
4370  
5335  
6900  
8700  
289  
290  
350  
630  
900  
292  
2x1000  
4x900  
4x1000  
4x1500  
526 1094 445 119  
603 1094 470 152  
294  
295  
* number of fuses per path of power section, built in  
Download from Www.Somanuals.com. All Manuals Search And Download.  
66  
9.3 TYPE RANGE 690 VOLT  
TYPE VOLTAGE 690 VOLTS  
TYPE  
TYPE POWER  
(KVA)  
DISSIPA- DIMENSIONS  
WEIGHT DIM.  
TEMP.  
CURRENT BURDEN  
SEMICON-  
CURRENT  
(A)  
TION  
(W)  
(MM)  
W
(NET ABOUT DRAW. CHARACTE- TRANSF.  
RESISTOR DUCTOR FUSE*  
H
D
KG)  
(NO.)  
RISTIC (NO.) T1  
R40 (Ω)  
F1 (A)  
THYRO-P 1P  
80 H  
55  
138  
125  
260  
200 320 229  
200 370 229  
174 414 340  
174 414 340  
240 685 505  
240 685 505  
521 577 445  
603 577 470  
8
263  
265  
266  
266  
268  
1
2
3
3
4
5
6
7
100/1  
1.20  
1.00  
1.00  
1.00  
1.20  
1.00  
1.00  
1.10  
100  
200 HF  
300 HF  
500 HF  
780 HF  
1400 HF  
2000 HF  
2600 HF  
9
15  
15  
35  
35  
62  
62  
200/1  
300/1  
250  
350  
207  
360  
345  
625  
500/1  
630  
538  
910  
1000/1  
1500/1  
2000/1  
3000/1  
2x630  
4x700  
4x900  
4x1400  
966  
1900  
3200  
3450  
1380  
1794  
270  
271  
THYRO-P 2P  
80 H  
35  
239  
225  
485  
325 320 229  
325 397 229  
261 414 340  
261 414 340  
410 685 505  
410 685 505  
526 837 445  
12  
15  
22  
22  
54  
54  
84  
275  
277  
278  
278  
280  
1
2
3
3
4
5
6
7
100/1  
200/1  
1.20  
1.00  
1.00  
1.00  
1.20  
1.00  
1.00  
1.20  
100  
250  
200 HF  
300 HF  
358  
640  
300/1  
350  
500 HF  
597  
1225  
1700  
3750  
5700  
6400  
500/1  
630  
780 HF  
932  
1000/1  
1500/1  
2000/1  
3000/1  
2x630  
4x700  
4x900  
4x1400  
1400 HF  
1850 HF  
2400 HF  
1673  
2210  
2868  
282  
283  
603 837 470 107  
THYRO-P 3P  
80 H  
95  
239  
350  
740  
450 320 229  
450 397 229  
348 430 340  
348 430 340  
575 685 505  
575 685 505  
17  
20  
30  
30  
74  
74  
287  
289  
290  
290  
292  
1
2
3
3
4
5
6
7
100/1  
200/1  
1.20  
1.00  
1.00  
1.00  
1.20  
1.00  
1.10  
1.30  
100  
250  
200 HF  
300 HF  
358  
1020  
1825  
2740  
5600  
8000  
9000  
300/1  
350  
500 HF  
597  
500/1  
630  
780 HF  
932  
1000/1  
1500/1  
2000/1  
3000/1  
2x630  
4x700  
4x900  
4x1400  
1400 HF  
1700 HF  
2200 HF  
1673  
2031  
2619  
526 1094 445 119  
603 1094 470 152  
294  
295  
* number of fuses per path of power section, built in  
Download from Www.Somanuals.com. All Manuals Search And Download.  
67  
10. SPECIFICATIONS  
TYPE VOLTAGE  
...P400...  
...P500...  
...P690...  
230 volts -20%  
230 volts -20%  
500 volts -20%  
to  
to  
to  
400 volts +10%  
500 volts +10%  
690 volts +10%  
MAINS FREQUENCY  
LOAD DESCRIPTION  
all models  
45Hz to 65Hz  
ohmic load (minimum 100W)  
ohmic load Rhot/Rcold ratio up to 20 (MOSI operation)  
transformer load  
TRANSFORMER  
The induction of the load side transformer should not exceed  
1.45T in case of mains overvoltage when using grain-oriented,  
cold-rolled plates. This corresponds to a nominal induction of  
approx. 1.3T.  
OPERATING MODES  
TAKT = full oscillation clock principle = default setting for the  
models 1P, 2P and 3P  
VAR = phase-angle control = only for the models 1P and 3P  
SSSD = soft-start-soft-down; a combination of  
„VAR“ und „TAKT“, for the models 1P, 2P and 3P,  
i.e. reduced mains surge load  
SET POINT INPUTS  
The Power Controller Thyro-P has 4 set point inputs.  
The set point inputs are indirectly connected to the mains  
(SELV, PELV).  
Set points 1, 2: external set point input  
signal ranges:  
0(4) - 20 mA Ri about 250max. 24mA*  
0
0
-
-
5
V
Ri about 8,8kmax. 12V  
Ri about 5kmax. 12V  
10 V  
* refer to ”ATTENTION” on page 16  
Set point 3: connection for fibre optic (LL) from the wuper-  
ordinate PC or automation system  
Set point 4: set point assignment via RS 232 (for instance LBA)  
The four set points are added internally and the total of the  
set points, for instance for power control, is proportionate to  
output power. For set point 2, there are different valuation  
options: it may be added to set point 1 or subtracted from set  
point 1.  
ANALOG OUTPUTS  
3 outputs: signal level 0-10 volts, 0-20mA or parameters may be  
set differently. The maximum burden voltage is 10V  
The control characteristic is established by the maximum value  
of the dimensions to be controlled and the key values of the  
set point. Using these key values, the linear control characte-  
ristic may be set at will.  
CONTROL CHARACTERISTIC  
Every controller (for instance temperature controller), whose  
output signal is in the range of 0-20mA/0-5V/0-10V may be  
easily adapted to the Power Controller.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
68  
CONTROL TYPES  
Voltage control Urms  
Voltage control U2rms = default setting  
Current control Irms  
Current control I2rms  
Power control P  
Without control  
PRECISION  
U-control: Better than 0.5% and 1 digit with reference to  
the end value.  
LIMITATIONS  
Voltage limitation Urms  
Current limitaion Irms = default setting  
Effective power limitation P  
Peak current limitation, MOSI operation  
Upon reaching one of these limits, the LED ”Limit“ on the  
front panel of Thyro-P is on and the relay K2 is activated.  
(terminal strip X2, terminals 10/11/12)  
Relay K1, K2, K3  
Contact load:  
AC max:  
AC min:  
DC max:  
DC min :  
250V/6A (1500VA)  
>10VA;  
300V/0.25A (62.5W)  
5V/20mA  
contactor material: AgCdO  
AC max: 250V/4A  
WITH UL APPLICATIONS  
AMBIENT TEMPERATURE  
35°C external cooling (F models)  
45°C self air cooling  
At higher temperatures it is possible to operate with reduced  
type current:  
I/IRATED CURRENT  
COOLANT  
TEMPERATURE  
FORCED COOLING  
SELF COOLING  
[°C]  
(VENTILATOR TYPES)  
-10 bis 25  
1.10  
1.05  
1.00  
0.96  
0.91  
0.87  
0.81  
1.10  
1.10  
1.10  
1.05  
1.00  
0.95  
0.88  
30  
35  
40  
45  
50  
55  
WITH UL APPLICATIONS UP TO +40°C  
I/IRating  
1.2  
Coolant temperature  
Self cooling  
1.1  
1.0  
0.9  
0.8  
0.7  
0.6  
Forced cooling  
20  
25  
30  
35  
40  
45  
50  
55  
60  
65  
Download from Www.Somanuals.com. All Manuals Search And Download.  
69  
TABLE TERMINAL SCREWS  
THYRO-P 1P, 2P, 3P  
CONNECTOR  
EARTHING SCREW  
U1, V1, W1, U2, V2, W2  
37H, 75H  
M 6  
M 8  
M 6  
M 8  
M 10  
M
6
80H  
M 10  
110H  
M
6
130H, 170H  
M 10  
M 10  
200HF, 280HF, 300HF  
495HF, 500HF, 650HF  
780HF, 1000HF, 1400HF,  
1500HF, 1700HF, 1850HF,  
2000HF, 2100HF, 2200HF,  
2400HF, 2600HF, 2750HF,  
2900HF  
M 12  
M 12  
WITH UL APPLICATIONS  
POWER CONNECTION  
USE ONLY 60°/75°C COPPER CONDUCTORS (UL SPECIFICATION)  
STUD TORQUE FOR  
TABLE TERMINAL SCREWS  
[Nm]  
SCREW  
MIN  
0.2  
RATED  
0.25  
4.4  
MAX  
5.9  
M
M
M
2
6
8
3.0  
22.5  
44  
11.5  
22.0  
38.0  
17.0  
33.0  
56.0  
M 10  
M 12  
75  
75.0  
[Pound inches]  
SCREW  
MIN  
1.9  
RATED  
2.2  
MAX  
2.5  
M
M
M
2
6
8
26.1  
101.8  
194.7  
336.3  
38.9  
52.2  
150.5  
292.1  
495.6  
199.1  
389.4  
663.8  
M 10  
M 12  
THYRO-P (HF-TYPES)  
TYPE CURRENT  
50HZ 60HZ  
AIR VOLUME SOUND PRESS.  
IN 1 M DIST.  
VENTILATOR 230 V,  
50-60 HZ  
I [A]  
I [A]  
[M3/H]  
[DBA]  
1P  
200HF, 280HF  
0.22  
0.50  
0.55  
1.00  
0.22  
0.38  
0.60  
1.20  
120  
150  
53  
67  
75  
81  
300HF, 495HF, 500HF, 650HF  
780HF, 1000HF, 1400HF, 1500HF  
2000HF, 2100HF, 2600HF, 2900HF  
2P  
580  
2200  
200HF, 280HF  
0.50  
0.50  
1.00  
1.00  
0.38  
0.38  
1.20  
1.20  
200  
230  
67  
67  
81  
81  
300HF, 495HF, 500HF, 650HF  
780HF, 1000HF, 1400HF, 1500HF  
1850HF, 2000HF, 2400HF, 2750HF  
3P  
1200  
2100  
200HF, 280HF  
0.50  
1.20  
1.00  
1.00  
0.38  
0.85  
1.20  
1.20  
260  
450  
67  
72  
81  
81  
300HF, 495HF, 500HF, 650HF  
780HF, 1000HF, 1400HF, 1500HF  
1700HF, 1850HF, 2200HF, 2600HF  
1600  
2000  
The ventilators (with HF types) must run with Thyro-P switched on.  
Connection according to connecting diagrams.  
Longer cooling fan start-up times can be expected when operating.  
Thyro-P at temperatures below 10° C. Therefore the adjustment range of upstream protection  
devices should be at least the 2-fold of the indicated steady current.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
70  
11. DIMENSIONAL DRAWINGS  
Thyro-P 1P (37 H, 75 H, 110 H)  
Dimensional Drawing 260  
M 1:5  
Thyro-P 1P (80 H, 130 H, 170 H)  
Dimensional Drawing 263  
M 1:5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
71  
Thyro-P 1P (200 HF, 280 HF)  
Dimensional Drawing 265  
M 1:5  
495 HF  
650 HF  
300 HF  
Thyro-P 1P (300 HF, 495 HF, 500 HF, 650 HF)  
Dimensional Drawing 266  
Download from Www.Somanuals.com. All Manuals Search And Download.  
72  
780 HF  
1000 HF - 1500 HF  
Thyro-P 1P (780 HF, 1000 HF, 1400 HF, 1500 HF)  
Dimensional Drawing 268  
M 1:8  
Thyro-P 1P (2000 HF, 2100 HF)  
Dimensional Drawing 270  
M 1:8  
Download from Www.Somanuals.com. All Manuals Search And Download.  
73  
Thyro-P 1P (2600 HF, 2900 HF)  
Dimensional Drawing 271  
M 1:8  
Thyro-P 2P (37 H, 75 H, 110 H)  
Dimensional Drawing 272  
M 1:5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
74  
Thyro-P 2P (80 H, 130 H, 170 H)  
Dimensional Drawing 275  
M 1:5  
Thyro-P 2P (200 HF, 280 HF)  
Dimensional Drawing 277  
M 1:5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
75  
495 HF  
650 HF  
300 HF  
Thyro-P 2P (300 HF, 495 HF, 500 HF, 650 HF)  
Dimensional Drawing 278  
780 HF  
1000 HF - 1500 HF  
Thyro-P 2P (780 HF, 1000 HF, 1400 HF, 1500 HF)  
Dimensional Drawing 280  
Download from Www.Somanuals.com. All Manuals Search And Download.  
76  
X7  
X10  
X30  
X31  
X50  
Cu 80x10; ø14  
Cu 3.149x0.393; ø 0.551  
U2  
U1  
W2  
W1  
ø9 für Erdung  
40  
210  
365  
15  
9x15  
1.575  
8.268  
14.370  
.591  
ø
0.354 for earthing  
0.54x0.590  
225  
31  
63  
2.480  
395  
91  
8.858  
1.220  
15.551  
3.583  
284  
549  
21.614  
11.161  
445  
17.526  
470 bei 2P 690-1850 HF  
18.5 for 2P 690- 1850 HF  
Thyro-P 2P (1850 HF, 2000 HF)  
Dimensional Drawing 282  
Download from Www.Somanuals.com. All Manuals Search And Download.  
77  
Thyro-P 2P (2400 HF, 2750 HF)  
Dimensional Drawing 283  
Thyro-P 3P (37 H, 75 H, 110H)  
Dimensional Drawing 284  
M 1:5  
Download from Www.Somanuals.com. All Manuals Search And Download.  
78  
Thyro-P 3P (80 H, 130 H, 170 H)  
Dimensional Drawing 287  
Thyro-P 3P (200 HF, 280 HF)  
Dimensional Drawing 289  
Download from Www.Somanuals.com. All Manuals Search And Download.  
79  
495 HF  
650 HF  
300 HF  
Thyro-P 3P (300 HF, 495 HF, 500 HF, 650 HF)  
Dimensional Drawing 290  
M 1:6  
Download from Www.Somanuals.com. All Manuals Search And Download.  
80  
780 HF  
1000 HF - 1500 HF  
Thyro-P 3P (780 HF, 1000 HF, 1400 HF, 1500 HF)  
Dimensional Drawing 292  
M 1:9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
81  
457  
17.973  
X7  
X10  
X30  
X31  
X50  
Cu 80x10; ø14  
U2  
U1  
Cu 3.149x0.393;ø0.551  
V2  
V1  
W2  
W1  
ø9 für Erdung  
0.354 for earthing  
365  
15  
ø
40  
210  
14.370  
395  
.591  
9x15  
63  
2.480  
91  
1.575  
8.268  
15.551  
3.583  
31  
225  
1.220  
549  
21.614  
8.858  
284  
11.161  
445  
17.520  
470 bei 3P 690-1700 HF  
18.5 for 3P 690-1700 HF  
Thyro-P 3P (1700 HF, 1850 HF)  
Dimensional Drawing 294  
Download from Www.Somanuals.com. All Manuals Search And Download.  
82  
Thyro-P 3P (2200 HF, 2600 HF)  
Dimensional Drawing 295  
M 1:9  
Download from Www.Somanuals.com. All Manuals Search And Download.  
83  
12. ACCESSORIES AND OPTIONS  
ORDER NO.  
DESCRIPTION  
Thyro-Tool Familiy, commissioning and visualization tool for simple visualization  
2000000380  
tasks; software under Windows 95/NT4.0 and later  
Thyro-P interface card Profibus-DP  
2000000393  
2000000392  
2000000394  
2000000400  
2000000401  
Thyro-P interface card Modbus RTU  
Thyro-P interface card DeviceNet  
control device for Thyro-1P, -2P and -3P  
control device as above, but using the ASM process for dynamic mains load  
optimization  
2000000406  
2000000405  
2000000399  
37259800  
37259900  
37295190  
0017381  
LBA, local operating and display unit, menu-driven, including copy function  
SEK, cabinet installation kit for LBA installation in switching cabinet door  
Voltage transformer 690V/43V (UE_U=016), for mounting on standard rails  
LLV.V, bre optic distribution power supply  
LLV.4, fibre optic distribution  
LL/RS 232 plug, (interface 9-pin) including power supply  
fibre optic plug  
0017574  
fibre optic cable  
8000007874  
0048764  
plug 2 pin for A70, X1  
data cable to the PC (RS 232)  
2000003203  
Damping card 690V  
Download from Www.Somanuals.com. All Manuals Search And Download.  
84  
13. APPROVALS AND CONFORMITIES  
Due to European harmonization and international reconciliation, the standards will be subject to  
years of adjustment and renumbering. The detailed schedule therefore contains the current stan-  
dards as well, even if the date for their expiry has already been set. There is no product norm for  
Thyristor Power Controllers, so that a sensible norm structure must be created from the correspon-  
ding basic norms, which ensures safe application and opportunity for comparison.  
CAUTION  
Thyristor Power Controllers are non-valid devices for disconnection and may therefore be operated  
only in connection with a suitable mains isolating device (for instance switch) connected on line side.  
Approvals and conformities are available for Thyro-P:  
• Quality standard according to ISO 9001  
• Registration in acc. to UL 508, file no. E 135074  
Investigated under consideration to Canadian National Standard C22.2 No. 14-95  
• UL Markings:  
· Field wiring terminal markings (see Chapter 4. „External Connections“)  
· Use 60/75°C Copper Conductors only  
· Tightening torque (pound inches) see Chapter 10. „Technical data“  
· Devices are suitable for the following short circuit current ratings:  
Devices rated 300A  
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical  
Amperes, xxx Volts Maximum, When Protected by RK5 Class Fuses, sized max. 600A / 600V“  
Devices rated 495A and 695A:  
„Suitable For Use On A Circuit Capable Of Delivering Not More Than 100kA rms Symmetrical  
Amperes, xxx Volts Maximum“  
NOTE:  
xxx = max. allowable voltage depending upon rating of the device  
· „Branch circuit protection must be provided and sized according National Electrical Code and  
any additional local codes“  
• CE conformity  
Low Voltage Directive 73/23 EEC;  
EMV Directive 89/336 EEC;  
Marking Directive 93/68 EEC  
• Interference suppression  
The RegTP confirms the compliance with the interference suppression regulations for the power  
control device  
Download from Www.Somanuals.com. All Manuals Search And Download.  
85  
IN DETAIL:  
CONDITIONS FOR USE OF THE DEVICE  
Built-in unit  
EN 50 178  
General requirements  
Design, vertical installation  
Operating conditions  
EN 60146-1-1  
EN 60 146-1-1; K. 2.5  
CISPR 6  
Operating location, industry sector  
Temperature performance  
Storage temperature  
EN 60 146-1-1; K 2.2  
-25°C - +55°C  
Transport temperature  
Operating temperature  
-25°C - +70°C  
-10°C - +35°C for external cooling ( 280A)  
-10°C - +45°C for self air cooling  
-10°C - +55°C for reduced type current -2%/°C  
up to 40°C  
with UL applications  
Load class  
1
EN 60 146-1-1 T.2  
Humidity class  
B
EN 50 178 Tab. 7  
Overvoltage voltage category ÜIII  
Degree of pollution  
Air pressure  
EN 50 178 Tab. 3  
2
EN 50 178 Tab. 2  
900mbar  
1000m above zero level  
Safe isolation  
up to 500V mains voltage:  
EN 50 178 chap. 3  
Air and creeping distances according  
to DIN EN 50178  
casing/mains potential  
5.3mm  
casing/control potential  
mains voltage/control  
potential  
5.3mm  
7.2mm and 10mm  
in the power section  
2.5mm  
interface/control potential  
mains voltage/interface  
7.2mm  
mains voltage among themselves 5.5mm  
EN 50 178 Tab 18  
Test voltage  
Tests according to  
EN 60 146-1-1 4.  
EMV noise emission  
Moise suppression (control device)  
EN 61000-6-4  
class A  
CISPR 11  
EMV noise resistance  
Compatibility level  
ESD  
EN 61000-6-2  
EN 61000-2-4  
EN 61000-4-2  
class 3  
8 kV  
Electromagnetic fields  
Burst on mains lines  
Burst on control lines  
Surge on mains lines  
Surge on control lines  
Line-conducted  
10V/m EN 61000-4-3  
2kV  
EN 61000-4-4  
EN 61000-4-5  
EN 61000-4-6  
0.5kV  
2kV  
0.5kV  
Further norms are observed, for instance voltage dips according to 61000-4-11 are ignored by the control  
device, or registered by triggering of monitoring. Generally, an automated start is made after the mains  
returns within tolerances.  
Therefore, the conditions of the norm EN 61326 (controller standard) are also observed, even though this  
norm by its structure is not applicable to power electronics > 10 respectively > 25A.  
Download from Www.Somanuals.com. All Manuals Search And Download.  
OPERATING INSTUCTION / BETRIEBSANLEITUNG BAL 8000003232,  
DE - EN, 06/12 - V6  
Due to our policy of continuous development, the data in this document is subject to change without notice.  
AEG is a registered trademark used under licence from AB Electrolux.  
Aufgrund unserer kontinuierlichen Weiterentwicklung können die Daten in diesem Dokument ohne vorherige Ankündigung geändert werden.  
AEG ist ein eingetragenes Warenzeichen verwendet unter Lizenz von AB Electrolux  
AEG Power Solutions GmbH  
Emil-Siepmann-Str. 32  
59581 Warstein-Belecke - Germany  
Tel.: +49 (0) 2902 763-520/-290 - Fax: +49 (0) 2902 763-1201  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Aastra Telecom Two Way Radio 41 001286 00 User Manual
Abocom Network Card WPG2400 User Manual
Abocom Switch LF560MX User Manual
ADC Clothes Dryer AD 30V User Manual
AEG Power Supply 6000BP User Manual
Agilent Technologies Network Hardware 06 296 90001 User Manual
Agilent Technologies Sprinkler 81133A User Manual
Air King Fan 9025 User Manual
Axis Communications Security Camera M3007P User Manual
Behringer Music Pedal AB200 User Manual