ACDelco Portable Generator AC G0002 User Manual

Model # AC-G0002  
3500 Surge Watts / 3000 Running Watts  
PORTABLE GENERATOR  
INSTRUCTION MANUAL  
Thank you for purchasing this high quality ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator. This manual  
provides important information on properly operating and maintaining this ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts  
Portable Generator. Every effort has been made to ensure the accuracy of this manual. We reserve the right to change this product at any time  
without prior notice.  
This manual contains important information regarding safety, operation, maintenance and storage of this product. Before use, read carefully and  
understand all warnings, cautions, instructions and labels. Failure to do so could result in serious personal injury, property damage or even death.  
SAVE THESE INSTRUCTIONS FOR FUTURE REFERENCE.  
STOP!  
DO NOT RETURN THIS GENERATOR TO THE RETAILER.  
Questions? Problems? CONTACT BUFFALO TOOLS.  
Or, call our customer help line at 1-866-460-9437, Monday-Friday, 8 AM - 4 PM Central Time. A copy of the sales receipt is required.  
c/o  
New Buffalo Corporation  
1220 North Price Road  
St. Louis MO 63132  
Phone: 866-460-9437 or  
314-373-2740  
Fax: 636-537-1055  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
1
Download from Www.Somanuals.com. All Manuals Search And Download.  
TABLE OF CONTENTS  
ACDelco, ACDelco Emblems, and ACDelco related graphics are Trademarks of General Motors Corporation, used under license to and distributed  
by New Buffalo Corporation.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
3
Download from Www.Somanuals.com. All Manuals Search And Download.  
RECOGNIZE SAFETY SYMBOLS, WORDS AND LABELS  
What You Need to Know About Safety Instructions  
Warning and Important Safety Instructions appearing in this manual are not meant to cover all possible conditions and  
situations that may occur. Common sense, caution and care must be exercised when operating or cleaning tools and  
equipment.  
Always contact your dealer, distributor, service agent or manufacturer about problems or conditions you do not understand.  
This is the safety alert symbol. It is used to alert you to potential  
personal injury hazards. Obey all safety messages that follow this  
symbol to avoid possible injury or death.  
DANGER indicates an imminently hazardous situation  
which, if not avoided, will result in death or serious injury.  
WARNING indicates a potentially hazardous situation which,  
if not avoided, could result in death or serious injury.  
CAUTION indicates a potentially hazardous situation which,  
if not avoided, may result in minor or moderate injury.  
CAUTION used without the safety alert symbol indicates a  
potentially hazardous situation which, if not avoided, may  
result in property damage.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
4
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Notice Regarding Emissions:  
Engines certified to comply with California and U.S. EPA emission regulations for SORE (Small Off Road Equipment) are certified to operate on  
regular unleaded gasoline and may include the following emission control systems: Three-Way Catalyst (TWC) (if equipped), and Engine  
Modifications (EM).  
Legal Requirements:  
Federal and/or State Occupational Safety and Health Administration (OSHA) regulations, local codes, and/or ordinances may apply to the intended  
use of this generator. Consult a qualified electrician, electrical inspector, and/or the local agency having jurisdiction. Some areas require generators  
to be registered with local utility companies. Additional regulations may apply if this generator will be used at a construction site.  
IMPORTANT SAFETY INSTRUCTIONS  
STOP!  
Before using this generator and if you have any questions regarding the hazard and safety notices listed in this manual and/or on this  
generator, call 1-866-460-9437, Monday - Friday, 8 AM - 4 PM Central Time.  
Carbon Monoxide Gas: When in operation, the exhaust from this generator contains poisonous carbon  
monoxide gas. Carbon monoxide gas is both odorless and colorless AND may be present even if you do not  
see or smell gas. Breathing this poison gas can lead to headaches, dizziness, drowsiness, loss of  
consciousness and eventually death.  
• Use this generator ONLY outdoors in non-confined areas.  
• Keep at least several feet of clearance on all sides to allow proper ventilation for this generator.  
Chemicals: According to the State of California, the exhaust from this generator contains chemicals known to  
cause cancer, birth defects, or other reproductive harm.  
Flammable Gasoline: This generator may emit highly flammable and explosive gasoline vapors, which can  
cause severe burns or even death. A nearby open flame can lead to an explosion even if not directly in contact  
with gasoline.  
• Do not operate this generator near open flame.  
• Do not smoke near this generator.  
• Always operate this generator on a firm, level surface.  
Gasoline is highly flammable and explosive. Handling fuel can result in serious injury or burns.  
• Always shut down this generator before refueling. Refuel in a well-ventilated area. Keep heat, sparks and flame away  
while refueling and away from the location where gasoline is stored. Never refuel indoors where gasoline fumes may  
reach flames and/or sparks.  
• Allow this generator to cool for at least 2 minutes before removing the fuel tank cap. Loosen the cap slowly to relieve  
pressure in the fuel tank. Avoid spilling fuel.  
• Do not fill the fuel tank above the upper limit line. Gasoline may expand during operation. Do not fill to the top of the  
tank.  
• Always check for spilled gasoline and immediately wipe it up before starting this generator.  
• Empty the fuel tank before storing or transporting this generator.  
• Always handle fuel outdoors.  
• Before transporting, turn the fuel valve to the "off" position and disconnect the spark plug.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
5
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Powerful Voltage: This generator produces powerful voltage, which can result in electrocution.  
• ALWAYS ground this generator before using it. (See “Ground the Generator” section in this manual).  
• Only electrical devices should be plugged into this generator, either directly or with an extension cord. NEVER  
connect a building electrical system to this generator without a qualified electrician. Such connections must isolate  
generator power from utility power and comply with local electrical laws and codes. Failure to comply can create a back  
feed into utility lines creating an electrocution hazard, which may result in serious injury or death to utility workers.  
Such a back feed may cause this generator to explode, burn and create fires when utility power is restored.  
• Use a ground fault circuit interrupter (GFCI) in highly conductive areas such as metal decking or steel work. GFCIs  
are available in-line with some extension cords.  
• Do not use this generator in wet conditions (rain, snow, active sprinkler system, wet hands, etc.). Always keep this  
generator dry and operate it with dry hands.  
• Do not touch bare wires or outlets (receptacles).  
• Do not allow children or non-qualified persons to operate this generator.  
High Temperatures: This generator produces heat when in operation. Temperatures near the exhaust can  
exceed 150 Degrees Fahrenheit (65 Degrees Celsius).  
• Do not touch hot surfaces. Observe all warning placards on this generator denoting hot surfaces.  
• Allow this generator to cool for several minutes after use before touching the engine, muffler or other areas that are  
hot during operation and before storing indoors.  
• Hot exhaust may ignite some materials. Keep flammable materials away from this generator.  
• Keep at least several feet of clearance on all sides of this generator during operation. Do not enclose this generator in  
any structure.  
Usage: Misuse of this generator can damage it or shorten its life.  
• Use this generator only for its intended purpose.  
• Operate this generator only on a dry, level surface.  
• Allow this generator to run for several minutes before connecting any electrical devices.  
• Promptly turn off any malfunctioning devices and disconnect them.  
• Do not operate an excessive number of electrical devices in excess of the wattage capacity of this generator.  
• Do not turn on electrical devices until after they are connected to this generator.  
• Turn off all connected electrical devices before stopping this generator.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
6
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
7
Download from Www.Somanuals.com. All Manuals Search And Download.  
In addition to the previously described safety information, familiarize yourself with all safety and hazard placards on this generator.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
8
Download from Www.Somanuals.com. All Manuals Search And Download.  
PACKAGE CONTENTS  
The following items are supplied with this ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator. Verify that all  
items are included.  
STOP!  
If there are missing items, call 1-866-460-9437, Monday - Friday, 8 AM - 4 PM Central Time for customer service. DO NOT RETURN THIS  
GENERATOR TO THE RETAILER.  
Item List:  
NEMA L14-30 plug for connecting 240 Volt electrical devices  
Set of 2 DC connector wires for connecting 12 Volt automotive-type batteries  
Spark plug wrench  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
9
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
GENERATOR COMPONENTS  
Observe the locations and functions of the various components and controls of this generator.  
(1) 120/240 Volt AC Outlet - Used for connecting electrical devices  
that run on 120 and/or 240 Volt, 60 Hz, single phase, AC current.  
(2) Ground Terminal - Used for connecting grounding wires to  
properly ground this generator.  
(8) Engine Switch - Used for starting/stopping the engine.  
(9) Recoil Starter - Pull-cord for starting the engine.  
(10) Fuel Filter Cup - Traps dirt and water from the fuel prior to  
entering the engine.  
(3) 120 Volt AC Outlet - Used for connecting electrical devices that  
run on 120 Volt, 60 Hz, single phase, AC current.  
(4) Voltage Selector - Used to select between 120 or 240 Volt output.  
(5) Circuit Breaker- Reset switch that protects this generator from  
electrical overload.  
(6) 12 Volt DC Outlet - Only used for charging 12 Volt automotive-  
type batteries.  
(7) Oil Filler/Dipstick Cap - Location for checking and filling the  
engine crankcase oil.  
(11) Fuel Valve - Allows gasoline to pass into the engine.  
(12) Air Filter - A removable, cleanable, sponge-like element that limits  
the amount of dirt pulled into the engine.  
(13) Choke Lever - Adjusts the amount of air allowed into the engine.  
(14) Fuel Gauge - Indicates the amount of gasoline remaining in the  
fuel tank.  
(15) Fuel Tank Cap - Access to the fuel tank for adding gasoline.  
(16) Volt Meter - A gauge indicating the voltage output.  
(17) Muffler - Reduces the engine noise level.  
(18) Spark Plug - Provides ignition to the engine.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
10  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
PREPARING THE GENERATOR FOR USE  
Using this Generator for the First-Time  
STOP!  
The following section describes the required steps for preparing this generator for the first use. Failure to correctly perform these steps  
can damage this generator and/or shorten its life. If still unsure about how to perform any of these steps after reading this section, call  
1-866-460-9437 Monday - Friday, 8 AM - 4 PM Central Time for customer service.  
If this generator is being used for the first time, the following few steps are required to prepare it for operation:  
Step 1 - Add Oil  
This generator requires engine oil to function. Engine oil is a major factor affecting engine performance and service life. When new from  
the package, this generator contains no oil in the engine crankcase. The correct quantity of oil is equal to the oil capacity of the engine crankcase  
and is 20 fluid oz (0.6 L) for this ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator. Add the correct quantity of  
oil before operating this generator for the first time. When replenishing oil for subsequent use of this generator, always determine that this generator  
has the correct quantity of oil.  
Model AC-G0002 Oil Capacity (fluid oz./L)  
Model AC-G0002 Oil Type Recommended  
20 / 0.6  
SAE-30  
To add oil:  
1. Confirm that this generator is on a level surface.  
2. Unscrew the oil filler/dipstick cap from the engine as illustrated in Figure 1.  
3. Using a funnel, add high detergent motor oil to fill the engine crankcase to the correct quantity as stated above. SAE-30 oil is recommended for  
general, all-temperature use. When the engine crankcase is full, the oil level should reach the lower lip of the oil filling opening as illustrated in  
Figure 2.  
4. Replace the oil filler/dipstick cap.  
Figure 1 - Unscrewing the Oil Cap  
Figure 2 - Adding Oil  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
11  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Step 2 - Add Gasoline  
Gasoline and gasoline fumes are highly flammable and explosive. Handling fuel can result in serious injury or burns.  
• Do not fill the fuel tank near a heat, sparks or an open flame. Keep gasoline away from appliance pilot lights, barbecues, electric appliances, power  
tools, etc.  
• Do not overfill the fuel tank. Always check for fuel spills and immediately wipe them up. Spilled fuel is a fire hazard and causes environmental  
damage.  
To add gasoline:  
To ensure that this generator runs smoothly, use only FRESH, UNLEADED GASOLINE WITH AN OCTANE RATING OF 87 OR HIGHER. Unleaded  
gasoline produces fewer engine and spark plug deposits and extends the life of the exhaust system.  
1. Confirm that this generator is on a level surface.  
2. Unscrew fuel tank cap and set aside. (NOTE: The fuel tank cap may be tight and difficult to unscrew.)  
3. Slowly add fresh, unleaded gasoline (with an octane rating 87 or higher) to the fuel tank. Be careful not to fill the fuel tank above the upper limit  
line. The fuel tank capacity for this ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator is 4 gallons (15 L). The  
fuel gauge, located on the top of this generator, indicates how much gasoline is currently in the fuel tank. NOTE: Because gasoline can expand, do  
not fill the fuel tank to the very top.  
4. Securely tighten the fuel tank cap and immediately wipe up any spilled gasoline with a dry cloth.  
Model AC-G0002 Fuel Tank Capacity (gals /L)  
Model AC-G0002 Fuel Type  
4 / 15  
Fresh, Unleaded Gasoline Octane Rating 87 or Higher  
IMPORTANT:  
• Use only UNLEADED gasoline with an octane rating of 87 or higher.  
• Never use a mixture of oil and gasoline.  
• Never use old and/or contaminated gasoline.  
• Avoid getting dirt and/or water in the fuel tank.  
• Gasoline can age in the fuel tank and make it difficult to start this generator. Never store this generator for extended time with gasoline in the fuel  
tank.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
12  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Step 3 - Ground the Generator  
Failure to properly ground this generator can result in electrocution.  
Ground this generator by tightening the grounding nut against a grounding wire as illustrated in Figure 3. A No. 12 AWG (American Wire Gauge)  
stranded copper wire is generally an acceptable grounding wire. The other end of this grounding wire should be connected to a copper or brass  
grounding rod that is driven into the earth.  
Grounding codes can vary by location. Contact a local electrician for information on grounding regulations for your area.  
Figure 3 - Attaching the Grounding Wire to this Generator  
Subsequent Use of this Generator  
For subsequent uses of this generator after the first use, certain steps still must be completed to prepare it for operation.  
IMPORTANT: Be familiar with the procedures described in the previous section titled “Using the Generator for the First Time” of this  
manual. If not, review this section now.  
Step 1 - Verify Oil Level  
Even though this generator is equipped with an automatic shutoff to protect it from damage due to low oil, it is important to check the oil level in the  
engine crankcase before each use to ensure that there is sufficient quantity.  
1. Verify that this generator is on a level surface.  
2. Unscrew the oil filler/dipstick cap from the engine.  
3. With a dry cloth, wipe the oil off of the dipstick that is located on the inside of the cap.  
4. Fully insert the dipstick without screwing the filler/dipstick cap and then remove again. There should be oil on the dipstick. If there is no oil on the  
dipstick, or oil is visible only at the very end of the dipstick, add oil until the engine crankcase is filled. (See “Changing/Adding Oil” in the  
“Maintenance/Care” section of this manual).  
5. Confirm that the oil filler/dipstick cap is properly screwed in place when finished verifying the oil level.  
NOTE: The oil capacity for this ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator is 20 fluid oz (0.6 L).  
Model AC-G0002 Oil Capacity (fluid oz./L)  
Model AC-G0002 Oil Type Recommended  
20 / 0.6  
SAE-30  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
13  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Step 2 - Verify Gas Level  
Before starting this generator, verify that there is sufficient gasoline in the fuel tank. The fuel gauge, located on the top of this generator, indicates the  
gas level currently in the fuel tank. If necessary, add fresh unleaded gasoline with an octane rating of 87 or higher according to “Step 2 - Add  
Gasoline” of the “Using this Generator for the First Time” section of this manual.  
Model AC-G0002 Fuel Tank Capacity (gals /L)  
Model AC-G0002 Fuel Type  
4 / 15  
Fresh, Unleaded Gasoline Octane Rating 87 or Higher  
Gasoline and gasoline fumes are highly flammable and explosive. Handling fuel can result in serious injury or burns.  
• Do not fill the fuel tank near a heat, sparks or an open flame. Keep gasoline away from appliance pilot lights, barbecues, electric appliances, power  
tools, etc.  
• Always allow several minutes for the engine to cool before refueling.  
• Do not overfill the fuel tank. Always check for fuel spills and immediately wipe them up. Spilled fuel is a fire hazard and causes environmental  
damage.  
IMPORTANT:  
• Use only fresh UNLEADED gasoline with an octane rating of 87 or higher.  
• Never use old and/or contaminated gasoline.  
• Never use a mixture of oil and gasoline.  
• Avoid getting dirt and/or water in the fuel tank.  
• Never store generator for extended time with gasoline in the fuel tank.  
Step 3 - Ground the Generator  
Failure to properly ground this generator can result in electrocution.  
Ground this generator by tightening the grounding nut against a grounding wire as previously illustrated in Figure 3. A generally acceptable  
grounding wire is a No. 12 AWG (American Wire Gauge) stranded copper wire. The other end of this grounding wire should be connected to a  
copper or brass grounding rod that is driven into the earth.  
Grounding codes can vary by location. Contact a local electrician for information on grounding regulations for your area.  
STARTING THE GENERATOR  
STOP!  
Before starting this generator, confirm that all the steps in the section titled, “Preparing the Generator for Use,” of this manual have been  
correctly completed. If unsure about how to perform any of these steps, call 1-866-460-9437, Monday - Friday, 8 AM - 4 PM Central Time for  
customer service.  
Disconnect all electrical loads from this generator before attempting to start.  
To start this generator:  
1. Confirm that there are no electrical devices connected to this generator. Connected devices may increase the difficulty in starting the engine.  
2. Confirm that this generator is properly grounded. (See “Ground the Generator” section of this manual.)  
3. Turn the fuel valve to the “on” position as shown in Figure 4.  
4. Move the choke lever to the “closed” position as shown in Figure 5.  
5. Set the engine switch to the “on” position.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
14  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
6. Slowly pull on the recoil starter handle, shown in Figure 6, until a slight resistance is felt. Then pull briskly to start the engine. Gently return the  
cord into the generator to avoid damage to the starter or housing. Never allow the cord to snap back.  
7. If the engine fails to start, repeat step 6. NOTE: After repeated attempts to start the engine, consult the troubleshooting guide before attempting  
again. If problems persist, call 1-866-460-9437, Monday - Friday, 8 AM - 4 PM Central Time.  
8. Once the engine has started and runs for about a minute, move the choke lever approximately half way towards the “open” position. Wait an  
additional 30 seconds and then move the choke lever completely over to the “open” position.  
9. Allow this generator to run for several minutes before connecting any electrical devices.  
Figure 4 - Fuel Valve in the “on” position  
Figure 5 - Choke Lever in the “closed” position. (Refer to the Generator  
Components chart to find the location of the Choke Lever.)  
Figure 6 - Pull-cord for starting the engine.  
USING THE GENERATOR  
After the engine has been running for several minutes, electrical devices may be connected to this generator.  
AC Usage  
Electrical devices running on AC current may be connected according to their wattage requirements. The rated (running) and surge wattage for this  
ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator is 3,000 and 3,500, respectively.  
Model AC-G0002 Rated (Running) Wattage  
Model AC-G0002 Surge Wattage  
3000  
3500  
The rated (running) wattage corresponds to the maximum wattage a generator can output on a continuous basis.  
The surge wattage corresponds to the maximum amount of power a generator can output for a short time. Many electrical devices, such as a  
refrigerator, require short bursts of extra power for starting and stopping fan motors, etc., in addition to their listed rated wattage. Motorized devices  
typically require more than their rated wattage for startup. The surge wattage ability of a generator allows for this extra power requirement.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
15  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
The total running wattage requirement of the electrical devices connected to a generator should not exceed the rated wattage of the generator itself.  
To calculate the total wattage requirement of the electrical devices to be connected, look up the rated (running) wattage of each device and add  
these numbers together to find the total wattage that all of the devices together will draw from the generator. If the total wattage of the selected  
devices exceeds the rated wattage of the generator, DO NOT connect all of the devices. Select a combination of the electrical devices that will have  
a total wattage less than or equal to the rated wattage for the generator, i.e., no more than 3000 for this ACDelco Model AC-G0002 3500 Surge  
Watts / 3000 Running Watts Portable Generator.  
This generator can run at its surge wattage capacity for only a short time. Connect electrical devices requiring a rated (running) wattage  
equal to or less than the rated wattage of this generator. Never connect devices requiring a rated wattage equal to the surge wattage of a  
generator.  
A device's rated (running) wattage should be listed somewhere on the device itself and/or in its manual. If the wattage specification for a device is not  
available, the wattage can be calculated by multiplying the Voltage requirement (120 or 240) by the Amperage drawn.  
Watts = Volts x Amperes  
Or, the wattage required by a device can be estimated by using the following chart (see Figure 7). The chart provides only estimates and it is better  
to know the exact wattage of each electrical device to be powered by this generator.  
Electrical Device  
Rated (Running) Watts Additional Surge Watts  
air compressor (1 HP)  
air compressor (1 - 1/2 HP)  
airless sprayer (1/3 HP)  
box fan  
1500  
2500  
600  
300  
300  
3000  
2500  
1200  
600  
0
clock radio AM/FM  
coffee maker  
computer w/17 inch monitor  
deep freezer  
electric drill (1/2 HP)  
DVD/CD player or VCR  
furnace fan blower (1/2 HP)  
garage door opener (1/2 HP)  
hot plate  
1500  
800  
500  
1000  
100  
800  
480  
2500  
75  
0
0
500  
1000  
0
1300  
520  
0
light bulb (75 watt)  
0
microwave oven (1000 watt)  
quartz halogen work light  
refrigerator/freezer (18 Cu. Ft.)  
saw - circular (7 1/4 inch)  
saw - miter (10 inch)  
saw - radial arm  
saw - reciprocating  
saw - table/radial (10 inch)  
security system  
1000  
1000  
800  
1500  
1800  
2000  
960  
0
0
1600  
1500  
1800  
2000  
1040  
2000  
0
2000  
180  
stereo receiver  
450  
0
electric stove - single element  
sump pump  
1500  
800  
1800  
500  
4000  
1000  
1200  
300  
0
1200  
1800  
0
table planer (6 inch)  
television (27 inch color)  
electric water heater (40 gallon)  
well water pump (1/3 HP)  
window air conditioner (10000 BTU)  
window fan  
0
2000  
1800  
600  
Figure 7 - Estimated wattage requirements for common electrical devices.  
Connect electrical devices to this generator according to the following procedure:  
1. Allow the engine to run for several minutes after it has been started.  
2. Confirm that the electrical device is switched off prior to plugging it into this generator.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
16  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Connect only electrical devices that are in good working order. Faulty devices or power cords present the risk of electrical shock.  
Immediately turn off and disconnect any device that commences to operate abnormally, sluggish or abruptly stops. Determine if the  
problem was the device or the rated load capacity of this generator has been exceeded.  
NOTE: Plug appliances into the correct outlet. Connect standard 120 Volt, single phase, 60 Hz loads to the 120 Volt outlet. Connect 240/120Volt,  
single phase, 60Hz loads with a NEMA L14-30 plug only to the 240/120 Volt outlet. See Figure 8 for an illustration of these outlets.  
Even though this ACDelco AC-G0002 Portable Generator has an overall rated wattage of 3000, do not attempt to draw more than 3400  
Watts (20 A) from any ONE of the 120 Volt outlets. Draws higher than 3400 Watts (20 A) will damage this generator and void the warranty.  
3. Switch the circuit breaker to the “on” position.  
NOTE: While this generator is running, power is available from either the standard 120 Volt outlets or the 240/120 Volt NEMA outlet. Both 120 Volts  
and 240 Volts can be simultaneously drawn from this generator.  
4. Turn on the connected electrical devices beginning with the device with the highest rated wattage requirement and then each additional device  
with the next lower rated wattage requirement.  
Do not connect 50Hz or 3-phase loads to this generator.  
Figure 8 - Outlets Available on this Generator, from left to right,  
12V DC, 120V AC, and 240/120 AC (NEMA L14-30 plug).  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
17  
Download from Www.Somanuals.com. All Manuals Search And Download.  
SOME NOTES ABOUT POWER CORDS  
Long or thin cords can require more wattage from a generator to power an electrical device. Figure 9 shows the recommended cords according to  
the power requirement of the electrical device. When using cords that exceed these specifications, allow for the electrical device to have a slightly  
higher rated wattage requirement.  
Device Requirements  
Max. Cord Length (ft) by Wire Gauge  
Amps  
2.5  
5
7.5  
10  
15  
20  
25  
30  
Watts (120V)  
300  
Watts (240V)  
600  
#8 wire #10 wire #12 wire #14 wire #16 wire  
NR  
NR  
NR  
NR  
NR  
175  
150  
125  
90  
1000  
500  
350  
250  
150  
125  
100  
65  
600  
300  
200  
150  
100  
75  
60  
NR  
NR  
375  
200  
125  
100  
65  
250  
125  
100  
50  
NR  
NR  
NR  
NR  
NR  
600  
900  
1200  
1800  
2400  
3600  
4800  
6000  
7200  
9600  
1200  
1800  
2400  
3000  
3600  
4800  
50  
NR  
NR  
NR  
40  
NR  
NR = Not Recommended.  
Figure 9 - Maximum Extension Cord Lengths by Power Requirement  
DC Usage  
The DC outlet is only for recharging 12 Volt automotive-type batteries. Do not connect any other device to this outlet.  
Use this generator only for recharging 12 Volt batteries. NEVER attempt to jumpstart a car with this generator.  
Failing to use the correct procedure can cause a battery to explode, seriously injuring anyone nearby. Keep heat, sparks, flame and  
smoking materials away from the battery.  
To connect 12 Volt batteries to the DC outlet:  
1. Connect one charging wire to the positive terminal of the battery and the other charging wire to the negative terminal of the battery.  
2. Connect the free end of the positive wire to the positive side of the outlet on this generator.  
3. Start this generator.  
4. Carefully connect the free end of the negative wire to the negative side of the outlet on this generator.  
5. When disconnecting, always disconnect the wires from this generator first to avoid a spark.  
Storage batteries emit highly explosive hydrogen gas when charged.  
Batteries also contain acid, which can cause severe chemical burns.  
• Do not allow open flames or cigarettes nearby for several minutes after charging a battery.  
• Always wear protective goggles and rubber gloves when charging a battery.  
• If battery acid gets on the skin, flush with water.  
• If battery acid gets in the eyes, flush with water and immediately call a physician.  
• If battery acid is swallowed, drink large quantities of milk and immediately call a physician.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
18  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
STOPPING THE GENERATOR  
To stop this generator:  
1. Turn off all connected electrical devices and then unplug them.  
2. Switch the circuit breaker to the “off” position.  
3. Allow this generator to run for several more minutes with no electrical devices connected to help stabilize the temperature of this generator.  
4. Set the engine switch to the “off” position.  
5. Turn the fuel valve to the “off” position.  
Allow this generator to cool down before touching areas that become hot during operation.  
Allowing gasoline to sit in this generator's fuel tank for extended time without use can increase the difficulty in starting this generator in  
the future. Never store this generator for extended time with gasoline in the fuel tank.  
MAINTENANCE/CARE  
Proper routine maintenance of this generator is essential for safe, economical, and trouble-free operation. It will help prolong the life of this generator  
as well as help reduce air pollution. Perform maintenance checks and procedures according to the schedule in Figure 10.  
STOP!  
If you have questions about any maintenance procedures described in this manual, call 1-866-460-9437 , Monday - Friday, 8 AM - 4 PM Central  
Time.  
Never perform maintenance procedures while this generator is running. Allow this generator to cool before commencing any maintenance  
procedures. Keep heat, sparks and flame away.  
Improper maintenance and/or failure to correct any problems prior to operating this generator can cause a malfunction which could cause  
death or serious injury. Always follow the inspection and maintenance recommendations and schedules in this manual.  
Recommended Maintenance Schedule  
Each Use  
Every Month or  
Each 20 Hrs  
Every 3 Months or Every 6 Months or Every Year or  
Each 50 Hrs  
Each 100 Hrs  
Each 300 Hrs  
Engine Oil  
Air Filter  
Check Level  
Replace  
Check  
X
X
X
Clean  
X
Fuel Filler Cap  
Spark Plug  
Fuel Tank  
Clean  
X
X
Check/Clean  
Verify Gas Level  
Clean  
X
X
Figure 10 - Recommended maintenance schedule  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
19  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Cleaning the Generator  
Always try to use this generator in a cool dry place. If this generator becomes dirty, the exterior can be cleaned with a damp cloth, soft brush,  
vacuum and/or pressurized air.  
Never clean this generator with a bucket of water and/or a hose as water can get inside and cause a short circuit or corrosion.  
Never use gasoline to clean parts of this generator.  
Checking the Oil Level  
Even though this generator is equipped with an automatic shutoff to protect it from damage due to low oil, it is important to check the oil level in the  
engine crankcase before each use to ensure that there is a sufficient quantity.  
To check the oil level:  
1. Verify that this generator is shut down and on a level surface.  
2. Unscrew the oil filler/dipstick cap from the engine as illustrated in Figure 11.  
3. With a dry cloth, wipe the oil off of the dipstick that is located on the inside of the cap.  
4. Insert the dipstick as if replacing the cap and then remove again. There should be oil on the dipstick. If there is no oil on the dipstick, or oil is  
visible only at the very end of the dipstick, add oil until the engine crankcase is filled (see “Changing/Adding Oil” in this section of this manual).  
5. Confirm that the oil filler/dipstick cap is properly in place when finished verifying the oil level.  
Figure 11 - Checking the Oil  
Changing/Adding Oil  
The oil level in this generator should be checked before each use. (See Figure 10.) When the oil level is low, add oil until the level is sufficient to  
operate this generator.  
The oil capacity for this ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator engine is 20 fluid oz. (0.6 L).  
To drain the oil from this generator:  
It is necessary to drain the oil from the crankcase only if it has become contaminated with water and/or dirt.  
1. Place a bucket underneath this generator to catch oil as it drains.  
2. Using a 10 mm hex wrench, unscrew the oil drain plug located on the crankcase underneath the oil filler/dipstick cap as illustrated in Figure 12.  
3. Allow all the oil to drain from this generator.  
4. Replace the oil drain plug and tighten with a 10 mm hex wrench.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
20  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NOTE: Never dispose of used motor oil in the trash, down a drain or on the ground. Put oil in a sealed container and contact your local  
recycling center or auto garage to arrange oil disposal.  
To add oil to the engine crankcase:  
1. Confirm that this generator is on a level surface.  
2. Unscrew the oil filler/dipstick cap from the engine as illustrated in Figure 11 above.  
3. Using a funnel, add high detergent motor oil to fill the engine crankcase to the correct quantity. SAE-30 oil is recommended for general use. When  
the engine crankcase is full, the oil level should reach the lower lip of the oil filling opening as shown in Figure 13.  
Model AC-G0002 Oil Capacity (fluid oz./L)  
Model AC-G0002 Oil Type Recommended  
20 / 0.6  
SAE-30  
Figure 12 - Draining Oil  
Figure 13 - Adding Oil  
Air Filter Maintenance  
Routine maintenance of the air filter helps maintain proper airflow to the carburetor.  
Occasionally verify that the air filter is free of excessive dirt. The air filter will require more frequent cleaning when operating this generator in  
extremely dusty areas.  
1. Unhinge the clasps at the top and bottom of the air filter cover as shown in Figure 14.  
2. Remove the sponge-like elements from the casing.  
3. Wipe the dirt from inside the empty air filter casing.  
4. Wash the sponge-like elements in household detergent and warm water. Do not use gasoline or a flammable solvent.  
5. Allow the sponge-like elements to dry thoroughly.  
6. Soak the dry sponge-like elements in engine oil. Squeeze out any excess oil. The engine will smoke during initial startup if too much oil is left in  
the air filter.  
7. Replace the sponge-like elements in the air filter casing (the fine element first) and replace the cover.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
21  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Figure 14 - Removing the Air Filter Casing.  
Fuel Filter Cup Cleaning  
The fuel filter cup is a small well underneath the fuel valve which helps trap dirt and water that may be in the fuel tank before entering the engine.  
To clean the fuel filter cup:  
1. Turn the fuel valve to the “off” position.  
2. Unscrew the fuel filter cup from the fuel valve using a wrench. (Turn the valve toward you to unscrew as illustrated in Figure 15.)  
3. Using a rag or brush, clean the cup of all sediment.  
4. Reinstall the fuel filter cup.  
Figure 15 - Removing the Fuel Filter Cup  
Spark Plug Maintenance  
The spark plug is essential for proper engine operation. The spark plug should be intact, free of deposits, and properly gapped. A bad or incorrectly  
installed spark plug can cause engine damage.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
22  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Model AC-G0002 Spark Plug Type  
F6TC  
Model AC-G0002 Spark Plug Gap (in/mm)  
0.028-0.031/0.7-0.8  
To inspect the spark plug:  
1. Remove the spark plug by pulling on the spark plug cap.  
2. Unscrew the spark plug from this generator by using the included spark plug wrench as illustrated in Figure 16.  
3. Visually inspect the spark plug. If it is cracked and/or chipped, discard and install a new spark plug. A F6TC spark plug, such as NGK BPR5ES, is  
recommended.  
4. Measure the spark plug electrode gap with a gauge. The gap should be 0.028-0.031in (0.7-0.8mm). (See Figure 17.)  
5. If re-using the spark plug, use a wire brush to clean any dirt from around the spark plug base and then re-gap the spark plug.  
6. Screw the spark plug back into place on this generator by using the included spark plug wrench.  
7. Replace the spark plug cap.  
Figure 16 - Removing the Spark Plug  
Figure 17 - Measuring the Spark Plug Gap  
Emptying the Fuel Tank  
To store this generator for extended time, drain the gasoline from the fuel tank.  
To drain gasoline from this generator:  
1. Turn the fuel valve to the “off” position.  
2. Remove the fuel filter cup. (See “Fuel Filter Cup Cleaning” earlier in this section.)  
3. Empty the fuel filter cup of any fuel.  
4. Place a receptacle underneath this generator to catch gasoline as it drains.  
5. Turn the fuel valve to the “on” position and allow all gasoline to drain.  
6. Turn the fuel valve to the “off” position.  
7. Replace the fuel filter cup.  
8. Store the drained gasoline in a suitable place.  
Do not store gasoline for more than 3 months.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
23  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
STORAGE/TRANSPORT PROCEDURES  
Never place any type of storage cover on this generator while it is still hot.  
When transporting or storing this generator for extended time:  
• Allow generator to fully cool before moving it. A hot engine and exhaust system can burn you and ignite some materials.  
• Empty the fuel tank. (See “Emptying the Fuel Tank” in the “Maintenance/Care” section.)  
• Turn the fuel valve to the “off” position.  
• Disconnect the spark plug. (See Figure 16, Removing the spark plug.)  
• Do not obstruct any ventilation openings.  
• Do not drop or strike this generator while moving it.  
• Store this generator in a cool dry area, free of excessive dust.  
Storage Time  
Less than 1 month  
1 to 2 months  
Recommended Storage Procedure (which will help prevent difficult starts)  
No storage procedure required.  
Fill with fresh gasoline and add gasoline conditioner  
2 months to 1 year  
1 year or more  
Empty the fuel tank. (See “Emptying the Fuel Tank” in the “Maintenance/Care” section.)  
Empty the fuel tank. (See “Emptying the Fuel Tank” in the “Maintenance/Care” section.)  
Disconnect the spark plug. (See Figure 16, Removing the spark plug.)  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
24  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
TROUBLESHOOTING  
IMPORTANT: If trouble persists, call our customer help line at 1-866-460-9437, Monday - Friday, 8 AM - 4 PM Central Time.  
Symptom  
Cause  
Solution  
Engine will not start.  
Engine switch is set to "off."  
Fuel valve is turned to "closed."  
Choke is open.  
Set engine switch to "on."  
Turn fuel valve to "open."  
Close the choke.  
Engine is out of gasoline.  
Engine is filled with contaminated and/or old  
gasoline.  
Add gasoline.  
Drain gasoline from the engine and add new  
gasoline.  
Spark plug is dirty.  
Clean spark plug.  
Spark plug is broken.  
Generator is not on level surface.  
Replace spark plug.  
Move generator to a level surface to prevent  
triggering the low oil shutdown.  
Add or replace oil.  
Oil is low.  
Engine runs but there is no electrical output.  
Circuit breaker is off.  
Reset button is "off."  
Bad connecting wires/cables.  
Bad electrical device connected to generator.  
Flip circuit breaker to "on."  
Push reset button to "on."  
Try a different extension cord.  
Disconnect device, try connecting another  
device.  
Generator runs but does not support all  
connected electrical devices.  
Generator is overloaded.  
Reduce draw on generator to within this  
generator's rated wattage by reducing number  
of connected electrical devices.  
Disconnect any faulty or short-circuited  
electrical loads.  
Short in one of the connected devices.  
Air filter is dirty.  
Clean or replace air filter.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
25  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
SPECIFICATIONS  
ACDelco Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
Generator  
Type  
Brush, Revolving Magnetic Field, Self Exciting, 2-Pole, Single Phase  
AC Output  
Rated Wattage (W)  
Surge Wattage (W)  
Rated Voltage (V)  
Rated Amperage  
3000  
3500  
120/240  
12.5A+12.5Aat 120 V  
12.5 A at 240 V  
Rated Frequency (Hz)  
Phase  
60  
Single  
DC Output  
Voltage (V)  
12  
Circuit Breaker Amperage (A)  
8.3  
Dimensions and Weight  
Dimensions (in.)  
Gross Weight (lbs)  
Net Weight (lbs)  
23.2 Length, 17.2 Width, 17.2 Height  
115  
106  
Engine  
Approvals  
CARB/EPA/MTL/CTL  
Engine Model (HP)  
Engine Type  
6.5  
4-stroke OHV single cylinder with forced air cooling system.  
Ignition System  
Starting System  
Displacement (cm3)  
Max Output (hp/rpm)  
non-contact transistor (T.C.I.)  
Recoil  
196  
6.5/3600  
Fuel Tank Capacity (Fresh, Unleaded gasoline, 87 or higher octane) (US 4 / 15  
gal./L)  
Continuous Operating Hours  
9 @ 50% Load  
Oil Capacity (SAE-30) (fl oz./Qts/L)  
Run Time on 50% Load (hours)  
Noise Rating (at 7 m, 0% load) (dB)  
20 / 0.63 / 0.6  
9
<78  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
26  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Model AC-G0002 3500 EXPLODED VIEW AND PARTS LIST  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
27  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Model AC-G0002 3500 PARTS LIST  
Item Part  
Qty Description  
Item Part  
Qty Description  
Bolt 8 mm × 205 mm  
1
1
3
1
1
1
1
1
1
2
4
4
4
1
2
1
1
4
1
1
1
3
1
1
1
1
2
2
6
1
1
2
3
4
5
6
7
8
9
168F-2BV  
Gasoline engine  
39 31933  
1
2
2
8
4
4
4
1
1
1
Generator fan  
41100  
Frame complete  
Bottom rubber mount A  
Bottom rubber mount B  
Flange nut 8 mm  
Nut 6 mm  
40 31141/2GF-3  
41 31996/2GF-3  
42 30100  
Bolt 5 mm × 14 mm  
Stator & rotor Assembly  
Fuel tank  
41310/2GF-3  
41320/2GF-3  
GB6177-86  
GB802-88  
41350/2GF-3  
GB5787-86  
41116  
43 16610/2GF-3  
44 16500/2GF-3  
45 16521/2GF-3  
46 16916/2GF-3  
47 37820/2GF-3  
48 GB819-85  
49 GB5787-86  
50 16821/2GF-3  
51 16811/2GF-3  
Fuel filler cap complete  
Packing ring  
Cushion, frame  
Fuel filler  
Bolt 6 mm × 12 mm  
Rubber pad  
Fuel sensor  
Screw 5 mm × 10 mm  
Flange bolt 6 mm × 22 mm  
Washer  
10 32520  
Ground connector  
Wire harness Assembly  
Receptacle (DC)  
Current protector 8A  
Receptacle (4 holes)  
Low oil indicator  
Control panel Assembly  
Control panel case  
Flange bolt 6 mm × 12 mm  
Circuit protector  
Ignition switch  
11 32100  
12 35550  
1
1
1
Cushion  
13 31750  
52  
Outlet pipe (φφ4.5×130)  
Tube clip  
14 35510  
16931/2GF-3  
15 37880  
1
1
53 16937/168F  
54 16930/2GF-3  
55 16812/2GF-3  
56 16824/2GF-3  
57 37825/2GF-3  
58 18300/168F-BV  
59 18611/2GF-3  
60 GB5787-86  
61 18110/168F-BV  
62 18221/168F-BV  
63 18720/2GF-3  
64 18710/2GF-3  
65 GB5787-86  
66 GB6187-86  
67 GB5787-86  
68 12255/168F  
69 GB5787-86  
70 37330  
Fuel cock  
16 37300  
1
4
1
1
1
Stripe, fuel tank  
Fitting brush, fuel tank  
Gasket, fuel sensor  
Muffler  
17 37321  
18 GB5787-86  
19 31710  
20 35410  
Muffler guard  
21 37420  
Voltmeter  
Flange bolt 8 mm × 16 mm  
Exhaust pipe complete  
Muffler gasket  
22 31820  
1
1
1
2
Voltage selector switch  
Receptacle (GFCI)  
Handle unit  
23 35540  
24 47160  
Supporting plate  
Muffler stay  
25 41136  
Feet  
26 GB5787-86  
27 GB6187-86  
28 31200  
2
1
Bolt 8 mm x 40 mm  
Nut 8 mm  
Bolt 8 mm × 25 mm  
Nut 8 mm  
1
1
1
1
1
1
3
1
1
1
4
Stator Assembly  
Stator cover  
Flange bolt 6 mm × 12 mm  
Exhaust pipe gasket  
29 31936  
30 31100  
Rotor Assembly  
Brush Assembly  
Generator stay  
31 31370  
8
2
1
2
2
1
2
1
1
Bolt 6 mm × 12 mm  
Curved panel  
32 31411/2GF-3  
33 31938/2GF-3  
34 31995/2GF-3  
35 31600  
Generator end cover  
Bolt 5 mm×12 mm  
Voltage regulator  
Bearing 6202-2RS  
Plain washer  
71 42000  
Wheel kit Assembly  
Bolt 8 mm × 16 mm  
Wheel kit  
72 GB5787-86  
73 42150  
36 GB276-89/2GF-3  
37 31134/2GF-3  
38 31931  
74 GB6187-86  
75 42130  
Nut 8 mm  
Wheel axel  
Flange bolt 6 mm × 150 mm  
76 16650  
Carbon Canister  
Spark Plug Cap  
77 34310/168F  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
28  
Download from Www.Somanuals.com. All Manuals Search And Download.  
MODEL AC-G0002 3500 SURGE WATTS / 3000 RUNNING WATTS PORTABLE GENERATOR  
WIRING DIAGRAM  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
29  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
NOTES:  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
30  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
WARRANTY  
LIMITED WARRANTY for ACDelco Generators from New Buffalo Corporation.  
Remember to save your receipt and to accurately fill out and mail your product registration card. You must provide proof of purchase for  
all warranty work.  
ACDelco generators are warranted to be free from defects in materials and workmanship for a period of one (1) year from date of original purchase.  
Generators used for Commercial or Rental use have a warranty period of 90 days from date of original purchase. Keep purchase receipt and mail in  
the product registration card for proof of purchase.  
ACDelco by New Buffalo Corporation will repair or replace, at its discretion, any part that is proven to be defective in materials or workmanship under  
normal use during the one (1) year warranty period. Warranty repairs or replacements will be made without charge for parts or labor. Parts replaced  
during warranty repairs will be considered as part of the original product and will have the same warranty period as the original product.  
To exercise this warranty, DO NOT RETURN TO RETAILER. Instead, call the toll free Customer Service number: 1-866-460-9437 and you will be  
instructed on where to take the engine for warranty service. Take this generator and proof of purchase (your receipt) to the repair facility  
recommended by the Customer Service Representative.  
The warranty does not extend to generators damaged or affected by fuel contamination, accidents, neglect, misuse, unauthorized alterations, use in  
an application for which the product was not designed and any other modifications or abuse.  
ACDelco by New Buffalo Corporation is not liable for any indirect, incidental or consequential damages from the sale or use of this product. Any  
implied warranties are limited to one (1) year as stated in this written limited warranty. Some states do not allow the exclusion or limitation of  
incidental or consequential damages. Some states do not allow limitation on the length of an implied warranty. This warranty gives you specific legal  
rights, and you may have other rights that vary from state to state.  
c/o  
New Buffalo Corporation  
1220 North Price Road  
St. Louis MO 63132  
Phone: 866-460-9437 or  
314-373-2740  
Fax: 636-537-1055  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
31  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
32  
Download from Www.Somanuals.com. All Manuals Search And Download.  
PORTABILITY KIT INSTALLATION  
The manufacturer recommends when using your ACDelco generator for recreational or utility functions that you properly install the Portability Kit  
included with your generator purchase. All ACDelco generator models include a Portability Kit for optional installation. Portability Kits are not  
required for ACDelco generators to properly operate.  
Model # AC-G0002  
3500 Watt Generator  
Step 1  
1. Install wheel axle, insert bolts (2) 8mm x 16mm through axle and generator's frame and tighten 8mm nut (2) onto bolt.  
2. Slip wheels (2) over the axle on both ends, insert cotter pins (2) through axle and spread the pins to hold wheels in place.  
Step 2  
1. Install stabilizer feet (2), insert bolts (4) 6mm x 12mm through feet and generator frame and tighten 6mm nut (2) onto bolt.  
Step 3  
1. Insert handle unit into the center of the stationary bracket located on the top center of the frame, slide bolt 8mm x 40mm through both bracket  
and handle unit, tighten 8mm nut onto bolt.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
33  
Download from Www.Somanuals.com. All Manuals Search And Download.  
 
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
34  
Download from Www.Somanuals.com. All Manuals Search And Download.  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
35  
Download from Www.Somanuals.com. All Manuals Search And Download.  
(AC3500070922)  
Model AC-G0002 3500 Surge Watts / 3000 Running Watts Portable Generator  
36  
Download from Www.Somanuals.com. All Manuals Search And Download.  

Acer Personal Computer 5625 User Manual
Addlogix Lawn Mower MAC1700RMA User Manual
Aiphone Caller ID Box TC 10MD User Manual
Airlink Network Router ARW027 User Manual
Alliance Laundry Systems Washer BF35PV User Manual
Altec Lansing Stereo Amplifier 9444B User Manual
AMX Work Light RDM INC50 User Manual
ATI Technologies Lawn Mower Lawn Mower User Manual
Bakers Pride Oven Oven GP 51 User Manual
Behringer Music Mixer PMP530M User Manual