Lincoln Impinger X2 Ovens with Push Button Controls 3262 2 User Manual

SERVICE MANUAL  
(DOMESTIC & INTERNATIONAL)  
IMPINGER X2 OVENS  
WITH ANALOG CONTROLS  
MODEL  
3240-2, 3262-2, 3270-2  
Lincoln Foodservice Products, LLC  
1111 North Hadley Road  
Fort Wayne, Indiana 46804  
United States of America  
Phone: (800) 374-3004  
U.S. Fax: (888) 790-8193 • Int’l Fax: (260) 436-0735  
Technical Service Hot Line  
(800) 678-9511  
X2svcmanual  
REV: 1/8/07  
SEQUENCE OF OPERATION  
IMPINGER X2 OVENS  
3240-2*  
3262-2*  
3270-2*  
230VAC  
230VAC  
230VAC  
50 HZ.  
50 HZ.  
50 HZ.  
1 PHASE  
1 PHASE  
1 PHASE  
*NOTE:  
Model number ending in TS indicates top belt is split belt  
Model number ending in SB indicates bottom belt is split belt  
Model number ending in SS indicates both belts are split belts  
POWER SUPPLY  
Electrical power to be supplied to the oven by a three conductor service for single phase  
or a five conductor service for three phase.  
Black conductor is hot.  
Red conductor is hot.  
Orange conductor is hot.  
White conductor is neutral.  
Green conductor is ground.  
MAIN FAN CIRCUIT  
BURNER CIRCUIT  
Power is permanently supplied to the normally open contacts of the main fan relay.  
Power is also supplied, through a 2 amp. fuse, to the 30 minute time delay relay.  
Closing the oven fan switch enables the 30 minute time delay relay. The 30 minute time  
delay relay supplies 220/240VAC to the coil of the main fan relay. These normally open  
contacts now close energizing the main fan motor. Closing the main fan switch also  
supplies 220/240VAC to the burner and conveyor switches.  
Closing the main fan switch supplies 220/240VAC to the normally open burner switch.  
Closing the burner switch supplies 220/240VAC, through the EMI filter, to the electronic  
temperature control. 220/240VAC is supplied, through the air pressure switch and the  
oven cavity hi-limit thermostat, to the burner control. When the burner control is  
energized, 220/240VAC is supplied to the burner blower motor. The normally open air  
pressure switch closes upon sensing air pressure. After a pre-purge of 30 seconds, the  
pilot valve and spark are energized. Ignition should now occur. After the pilot flame is  
proven, the main valve is energized.  
TEMPERATURE CONTROL  
CONVEYOR DRIVE  
Closing the main fan switch and burner switch supplies 220/240VAC to the electronic  
temperature control. The electronic temperature control is adjusted to the desired  
temperature. The thermocouple will provide varying millivolts to the electronic  
temperature control. The temperature control supplies 220/240VAC to the temperature  
regulation valve at intermittent intervals to maintain desired temperature.  
THE OVEN WILL CONTAIN BETWEEN TWO AND FOUR SEPARATE CONVEYOR  
DRIVE SYSTEMS. THE SEQUENCE OF OPERATIONS WILL BE THE SAME FOR  
EACH MOTOR SYSTEM.  
Closing the main fan switch supplies 220/240VAC, through the EMI filter, to the normally  
open conveyor switch, through a 2 Amp. fuse, to the conveyor control. AC voltage is  
converted to DC voltage and DC voltage is supplied, at terminals A+ and A-, to the  
conveyor motor. Adjusting the conveyor control will vary the DC output voltage. The  
speed of the motor will increase or decrease as the DC voltage from the conveyor  
control increases or decreases.  
NOTE: The conveyor control uses a hall effect sensor and magnet, mounted on the conveyor  
motor that senses motor speed. The sensor detects any change in motor load (± RPM)  
and the voltage to the motor is adjusted accordingly.  
AUTOMATIC COOL DOWN  
When the oven is started, the 30 minute time delay relay is enabled, permitting the oven  
fan to operate for approximately 30 minutes after the oven is shut off, to cool the oven.  
When the oven is shut off, the 30 minute time delay relay will keep the coil of the main  
fan relay closed for 30 minutes, maintaining operation of the main fan motor.  
Impinger X2 – Analog Service Manual – Dom & Int’l  
3
SCHEMATIC DIAGRAM  
MODEL 3240-2, 3262-2, 3270-2 60 HZ.  
4
Impinger X2 – Analog Service Manual – Dom & Int’l  
SCHEMATIC DIAGRAM  
MODEL 3240-2, 3262-2, 3270-2 50 HZ.  
Impinger X2 – Analog Service Manual – Dom & Int’l  
5
TROUBLESHOOTING GUIDE  
3240-2*  
3240-2*  
3262-2*  
3262-2*  
3270-2*  
3270-2*  
120/230VAC  
120/230VAC  
120/230VAC  
120/230VAC  
120/230VAC  
120/230VAC  
60 HZ.  
60 HZ.  
60 HZ.  
60 HZ.  
60 HZ.  
60 HZ.  
1 PHASE  
3 PHASE  
1 PHASE  
3 PHASE  
1 PHASE  
3 PHASE  
*NOTE:  
Model number ending in TS indicates top belt is split belt  
Model number ending in SB indicates bottom belt is split belt  
Model number ending in SS indicates both belts are split belts  
SYMPTOM  
Oven fan will not run  
POSSIBLE CAUSE  
Incoming power supply  
EVALUATION  
Check circuit breakers. Reset if required. Call power  
co. if needed.  
Fuse, 2 Amp, control (F7)  
Fuse holder  
Switch, oven fan  
Check, replace if necessary.  
Check, replace if necessary.  
Check continuity between switch terminals. Replace  
switch as needed.  
30 minute time delay relay  
Check for supply voltage to 30 minute time delay relay  
at terminals #2 and #3. If no voltage is present, trace  
wiring back to main power switch. If there is supply  
voltage at terminals #2 and #3, check for output voltage  
at terminals #1 and #3. If there is incoming voltage but  
no output voltage, and the main power switch is on,  
replace the 30 minute time delay relay.  
Relay, main fan  
Check for supply voltage to relay contacts, if no voltage  
is present, trace wiring back to power supply. Check for  
120VAC to the coil of the main fan relay. If no voltage is  
present, trace wiring back to the 30 minute time delay  
relay, check to be sure that the Overload Protector  
contacts are closed. If contacts are open, see  
“Overload Protector” below. If voltage is present, check  
to insure relay contacts are closing. Replace relay as  
needed.  
Overload protector, main fan  
Check to be sure overload contacts are closed. If not  
closed, re-set overload. If contacts do not close,  
replace overload protector. If contacts close, test for  
proper operation. If the overload contacts do not stay  
closed, and the amperage is below the overload  
setting, replace the overload protector.  
3240 should be set at 13A  
3260 should be set at 18A  
3270 should be set at 18A  
Main fan motor  
Capacitor  
Check for supply voltage at motor. If no voltage is  
present, trace wiring back to the overload protector.  
WITH POWER OFF: Check for opens, shorts or  
grounds. Turn motor shaft to check for locked rotor.  
Check for shorts or grounds.  
WARNING: Capacitor has a stored charge, discharge  
before testing.  
Check for loose or broken drive belt. Adjust motor for  
proper belt tension (maximum of 3/8-inch deflection), or  
replace drive belt as needed.  
Drive belt  
Bearings, Fan shaft  
Check for any damage or excessive wear on the shaft  
Impinger X2 – Analog Service Manual – Dom & Int’l  
6
bearings. Replace bearings as needed.  
Check for adequate gas supply to oven.  
Oven will not heat  
Gas supply  
Manual gas shut off valve  
Check to see that the manual gas shut off valve is  
open. Also, check flexible gas line connection for any  
damage.  
Main fan motor  
Relay, main fan  
Check for main fan operation. If it is not operating, refer  
to “Oven fan will not run”.  
Check for 120VAC supplied to relay terminal #13. If  
voltage is not present, trace wiring back to power  
supply. If voltage is present, check for 120VAC at  
terminal #14. If there is no voltage at terminal #14, and  
the relay is energized, replace the main fan relay.  
Check, replace if necessary.  
Fuse, 2 Amp, control (F8)  
Fuse holder  
Check, replace if necessary.  
Switch, oven fan  
Check for 120VAC to the switch, if no voltage is  
present, trace wiring back to the main fan relay. Check  
continuity between switch terminals. Replace switch as  
needed.  
Switch, burner  
Check for 120VAC to the switch, if no voltage is  
present, trace wiring back to the oven fan switch.  
Check continuity between switch terminals. Replace  
switch as needed.  
Air pressure switch  
Check for 120VAC to the air pressure switch. If no  
voltage is present, trace wiring back to burner switch.  
This normally open switch should close when the main  
fan is activated. Check air switch tube for blockage or  
any obstructions, repair as needed. Refer to the  
“Removal and installation” section for proper  
adjustment of air pressure switch. Replace air pressure  
switch as needed.  
Transformer, burner  
Relay, burner blower  
Check for 120VAC supplied to primary of transformer. If  
no voltage is present, trace wiring back to the air  
pressure switch. If voltage is present, check for 24VAC  
at transformer secondary. If there is primary voltage but  
no secondary voltage, replace burner transformer.  
Check for 24VAC supply to relay coil. If no voltage is  
present, trace wiring back to burner transformer. Check  
for 120VAC to relay contact. If no voltage is present,  
trace wiring back to air pressure switch. When 24VAC  
is applied to the coil, there will be a delay of 20 – 30  
seconds. After this time delay, the relay contacts  
should close. If there is 24VAC applied, but the  
contacts do not close, replace the burner blower relay.  
Check for 120VAC supplied to the burner blower motor.  
If no voltage is present, trace wiring back to the burner  
blower relay. If voltage is present, and the motor is not  
turning, check for opens, shorts or grounds.  
WITH POWER OFF: Check for locked rotor.  
Replace burner blower motor as needed.  
Motor, burner blower  
Centrifugal switch of  
Burner blower motor  
Check for 24VAC supplied to centrifugal switch at wire  
S5. If no voltage is present, trace wiring back to the  
burner transformer. If voltage is present, check for  
24VAC out of centrifugal switch at wire #32. If there is  
voltage in, but there is no voltage out, and the burner  
blower motor is running, replace the burner blower  
motor.  
Burner control  
Check for 24VAC supplied to the burner control at  
terminals #5 and #6. If no voltage is present, trace  
Impinger X2 – Analog Service Manual – Dom & Int’l  
7
wiring back to the centrifugal switch of the burner  
blower motor. If voltage is present, check for 24VAC at  
pins #3 and #2 (pilot valve). If voltage is not present,  
replace burner control. If the pilot valve is energized,  
check to see that the high voltage igniter circuit is also  
energized. To check, turn power off, disconnect the  
igniter lead from the ignition control. Turn power on. If  
no spark is visible, replace burner control. If a spark is  
visible at burner control, proceed.  
Check for 24VAC supplied to pilot valve. If no voltage is  
present, trace wiring back to burner control. If voltage is  
present, check for gas pressure at the pilot line  
connection. If no gas pressure is present during  
ignition, check for any blockage in the assembly. If  
there are no obstructions, and there is gas supplied to  
the oven, replace the gas valve.  
Pilot valve  
No pilot flame  
Pilot tube  
If the ignition control is supplied with 24VAC and the  
pilot valve and igniter circuits are energized, visually  
check for a pilot flame. This may be done by looking  
through the inspection view port on the end of the  
burner. If no pilot flame is visible, check the pilot tube.  
Check for gas pressure at the pilot tube. Disconnect  
pilot tube at the burner And connect manometer to pilot  
tube. If no gas pressure is present during ignition,  
check for blockage of the pilot tube. If the pilot tube is  
clear, proceed.  
Pilot orifice  
If there is gas pressure at the pilot tube, check the pilot  
orifice for blockage or obstructions. Replace pilot orifice  
as needed.  
Burner igniter  
Check the burner igniter head for any damage or  
obstructions also check for frayed or broken wire.  
Check spark gap, gap should be 3/32” If there is visible  
damage, replace burner igniter.  
NOTE: Flame should be  
On at this time  
Electronic temperature  
control  
Pilot flame, but no main flame  
Check for 120VAC supplied to electronic temperature  
control at terminals #13 and #12. Of there is no voltage,  
trace wiring back to the burner switch. Also check for  
120VAC supplied to terminal #20 on the electronic  
temperature control. If there is no voltage at terminal  
#20, trace wiring back to terminal #13. Set temperature  
control to maximum temperature and check for  
120VAC output at terminal #21 and neutral. If 120VAC  
is present at terminal #20 and neutral, and the unit is  
not heating, refer to “Temperature regulation valve” for  
next check. If 120 VAC is not present, proceed.  
WITH POWER ON AND THERMOCOUPLE LEADS  
ATTACHED TO THE ELECTRONIC TEMPERATURE  
CONTROL: Measure the D.C. millivolt output of these  
leads. Refer to chart in the “Removal, Installation and  
Adjustment” section for proper readings. If these  
readings are not achieved, replace thermocouple.  
Check for 24VAC supplied to main valve. If no voltage  
is present, trace wiring back to burner control. If there is  
no voltage output, replace burner control.  
Check to see that the switch on the valve is in the “ON”  
position. Check for 24VAC supplied to main valve. If  
there is voltage present, check to see that valve is  
opening. Connect manometer to pressure tap on outlet  
side of valve. If there is voltage to the valve, but no  
output gas pressure, replace the valve.  
Thermocouple probe  
Burner control.  
Main gas valve  
8
Impinger X2 – Analog Service Manual – Dom & Int’l  
Temperature regulation valve If 120VAC is present on the electronic temperature  
control, terminal #13 to neutral, check for voltage at  
temperature regulation valve. If no voltage is present,  
trace wiring back to electronic temperature control. If  
voltage is present, listen for valve to open and close.  
Also check for opens or shorts in the operating coil.  
Replace temperature regulation valve as needed.  
Thermal/Overload of main fan The main fan motor and burner blower motor are  
Intermittent heating  
Conveyor will not run  
and burner blower motors  
equipped with internal thermal protection and will cease  
to operate if overheating occurs. As the motors over-  
heat and then cool, this will cause the units to cycle on  
and off intermittently. Improper ventilation or lack of  
preventive maintenance may cause this. Also, most of  
the problems listed under “Oven will not heat” can  
cause intermittent failure.  
NOTE: The ovens may contain two, three or four conveyor drive systems using like  
components. The trouble shooting sequence will be the same for each of the conveyor  
drive systems  
Power supply  
Check circuit breakers, reset if required. Check power  
plug to be sure it is firmly in receptacle. Measure  
incoming power, call power co. if needed.  
Switch, oven fan  
Relay, main fan  
Check continuity between switch terminals. Replace  
switch as needed.  
Check for 120VAC supplied to relay terminal #13. If  
voltage is not present, trace wiring back to power  
supply. If voltage is present, check for 120VAC at  
terminal #14. If there is no voltage at terminal #14, and  
the relay is energized, replace the main fan relay.  
Check, replace if necessary.  
Check for 120VAC supplied to fuse holder. If no voltage  
is present, trace wiring back to main fan relay. Check  
fuse holder, replace if necessary.  
Fuse, 2 Amp  
Fuse holder  
Switch, conveyor  
Control, conveyor  
Check for 120VAC supplied to conveyor switch. If no  
voltage is present, trace wiring back to fuse holder.  
Check continuity between switch terminals. Replace  
switch as needed.  
Check for 120VAC supplied to conveyor control at  
terminals #1 (AC) and #2 (AC). If no voltage is present,  
trace wiring back to conveyor switch. If AC voltage is  
present, check for DC voltage output at terminals #3  
(A-) and #4 (A+). If there is AC voltage in, but no DC  
voltage out of the conveyor control. Replace the  
conveyor control. If there is D.C. voltage output,  
proceed.  
Fuse, 2 Amp  
Fuse holder  
Check, replace if necessary.  
Check for D.C. voltage supplied to fuse holder. If no  
voltage is present, trace wiring back to conveyor  
control. Check fuse holder, replace if necessary.  
Check for D.C. voltage supplied to the reversing switch.  
If no voltage is present, trace wiring back to the fuse  
holder. Check continuity between switch terminals.  
Replace switch as needed.  
Check for D.C. voltage to the conveyor motor. If no  
voltage is present, trace wiring back to the reversing  
switch. If voltage is present and the motor will not run,  
check the motor windings for opens or shorts. Check  
motor brushes for excessive wear. Replace motor  
brushes as needed.  
Switch, conveyor reversing  
Conveyor motor  
If any of the above fails, replace conveyor motor.  
Check for any mechanical problems in the conveyor  
Conveyor  
Impinger X2 – Analog Service Manual – Dom & Int’l  
9
assembly. Check for damaged or torn belting. Check  
conveyor shaft bearings for damage or excessive wear.  
Repair or replace conveyor components as needed.  
Check for a steady 120VAC supply to the conveyor  
control. If voltage is not steady, trace back to power  
supply.  
Check for a steady DC voltage output at terminals A+  
and A-. If voltage is not steady, proceed. Check for  
5 VDC output from the conveyor control at terminals  
+5V(red) and COM (black). If there is no voltage output,  
replace the conveyor control. If there is DC output,  
proceed.  
Conveyor speed varying or  
intermittent  
Power supply  
Control, conveyor  
Motor, conveyor  
Check conveyor motor and gearbox for any visible  
damage. If there is apparent damage, repair or replace  
conveyor motor. Check motor brushes for excessive or  
abnormal wear. Replace motor brushes as needed.  
Check to be sure that the Hall effect sensor and  
magnet are mounted on the motor. Check for any  
visible damage to the Hall effect sensor and magnet. If  
there is visible damage, repair or replace as needed. If  
there is no visible damage, check for a frequency  
output from the hall effect sensor at terminals SIG  
(white) and COM (black).  
Hall effect sensor/magnet  
Readings should be as follows:  
2:15 cook time  
5:00  
56 Hz. approx.  
25 Hz. approx.  
13 Hz. approx.  
8 Hz. approx.  
10:00  
16:00  
If these readings are not achieved, replace the Hall  
effect sensor/magnet  
10  
Impinger X2 – Analog Service Manual – Dom & Int’l  
TROUBLESHOOTING GUIDE  
3240-2*  
3262-2*  
3270-2*  
230VAC  
230VAC  
230VAC  
50 HZ.  
50 HZ.  
50 HZ.  
1 PHASE  
1 PHASE  
1 PHASE  
*NOTE:  
Model number ending in TS indicates top belt is split belt  
Model number ending in SB indicates bottom belt is split belt  
Model number ending in SS indicates both belts are split belts  
SYMPTOM  
Oven fan will not run  
POSSIBLE CAUSE  
Incoming power supply  
EVALUATION  
Check circuit breakers. Reset if required. Call power  
co. if needed.  
Fuse, 2 Amp, control (F7)  
Fuse holder  
Switch, oven fan  
Check, replace if necessary.  
Check, replace if necessary.  
Check continuity between switch terminals. Replace  
switch as needed.  
30 minute time delay relay  
Check for supply voltage to 30 minute time delay relay  
at terminals #2 and #3. If no voltage is present, trace  
wiring back to main power switch. If there is supply  
voltage at terminals #2 and #3, check for output voltage  
at terminals #1 and #3. If there is incoming voltage but  
no output voltage, and the main power switch is on,  
replace the 30 minute time delay relay.  
Relay, main fan  
Check for supply voltage to relay contacts, if no voltage  
is present, trace wiring back to power supply. Check for  
supply voltage to the coil of the main fan relay. If no  
voltage is present, trace wiring back to the 30 minute  
time delay relay, check to be sure that the Overload  
Protector contacts are closed. If contacts are open, see  
“Overload Protector” below. If voltage is present, check  
to insure relay contacts are closing. Replace relay as  
needed.  
Overload protector, main fan  
Check to be sure overload contacts are closed. If not  
closed, re-set overload. If contacts do not close,  
replace overload protector. If contacts close, test for  
proper operation. If the overload contacts do not stay  
closed, and the amperage is below the overload  
setting, replace the overload protector.  
3240 should be set at 13A  
3260 should be set at 18A  
3270 should be set at 18A  
Main fan motor  
Capacitor  
Check for supply voltage at motor. If no voltage is  
present, trace wiring back to the overload protector.  
WITH POWER OFF: Check for opens, shorts or  
grounds. Turn motor shaft to check for locked rotor.  
Check for shorts or grounds.  
WARNING: Capacitor has a stored charge, discharge  
before testing.  
Check for loose or broken drive belt. Adjust motor for  
proper belt tension (maximum of 3/8-inch deflection), or  
replace drive belt as needed.  
Drive belt  
Bearings, Fan shaft  
Check for any damage or excessive wear on the shaft  
bearings. Replace bearings as needed.  
Impinger X2 – Analog Service Manual – Dom & Int’l  
11  
Oven will not heat  
Gas supply  
Manual gas shut off valve  
Check for adequate gas supply to oven.  
Check to see that the manual gas shut off valve is  
open. Also, check flexible gas line connection for any  
damage.  
Main fan motor  
Relay, main fan  
Check for main fan operation. If it is not operating, refer  
to “Oven fan will not run”.  
Check for supply voltage to relay terminal #13. If  
voltage is not present, trace wiring back to power  
supply. If voltage is present, check for supply voltage at  
terminal #14. If there is no voltage at terminal #14, and  
the relay is energized, replace the main fan relay.  
Check, replace if necessary.  
Fuse, 2 Amp, control (F8)  
Fuse holder  
Check, replace if necessary.  
Switch, oven fan  
Check for supply voltage to the switch, if no voltage is  
present, trace wiring back to the main fan relay. Check  
continuity between switch terminals. Replace switch as  
needed.  
Switch, burner  
Check for supply voltage to the switch, if no voltage is  
present, trace wiring back to the oven fan switch.  
Check continuity between switch terminals. Replace  
switch as needed.  
Air pressure switch  
Check for supply voltage to the air pressure switch. If  
no voltage is present, trace wiring back to burner  
switch. This normally open switch should close when  
the main fan is activated. Check air switch tube for  
blockage or any obstructions, repair as needed. Refer  
to the “Removal and installation” section for proper  
adjustment of air pressure switch. Replace air pressure  
switch as needed.  
Thermostat, hi-limit  
Burner control  
Terminals are normally closed. If open, reset and test  
oven for proper operation. If thermostat will not hold for  
maximum oven temperature, and oven is not exceeding  
temperature control setting, check for proper location of  
capillary tube in the oven cavity. If above checks okay,  
replace hi-limit thermostat.  
Check for supply voltage to the burner control at  
terminals #1 and #3. If no voltage is present, trace  
wiring back to the hi-limit thermostat. If voltage is  
present, check for supply voltage at pins #8 and #3  
(burner blower motor). If voltage is not present, replace  
burner control. If voltage is present, proceed.  
Check for supply voltage to the burner blower motor. If  
no voltage is present, trace wiring back to the burner  
control. If voltage is present, and the motor is not  
turning, check for opens, shorts or grounds.  
WITH POWER OFF: Check for locked rotor.  
Replace burner blower motor as needed.  
Motor, burner blower  
Air pressure switch  
(burner motor)  
Check for supply voltage at the COM terminal on the air  
pressure switch. If no voltage is present, trace wiring  
back to burner control. If voltage is present, check for  
supply voltage switching to the NO terminal on the air  
pressure switch. If the burner blower motor is running,  
but voltage is not switching to the NO terminal of the air  
pressure switch, check air switch tube for blockage or  
any obstructions, repair as needed. Refer to the  
“Removal and installation” section for proper  
adjustment of air pressure switch. Replace air pressure  
switch as needed.  
12  
Impinger X2 – Analog Service Manual – Dom & Int’l  
Burner control  
Pilot valve  
Check for supply voltage at terminal #7 on burner  
control. If no voltage is present, trace wiring back to air  
pressure switch. If voltage is present, check for output  
voltage (after the 30 second delay) from terminal #8 on  
the burner control. If there is no output voltage from  
terminal #8, (after the 30 second delay) replace the  
burner control. If there is output voltage, proceed.  
Check for supply voltage to pilot valve. If no voltage is  
present, trace wiring back to burner control. If voltage is  
present, check for gas pressure at the pilot line  
connection. If no gas pressure is present during  
ignition, check for any blockage in the assembly. If  
there are no obstructions, and there is gas supplied to  
the oven, replace the gas valve.  
Burner control  
Check to see that the high voltage igniter circuit on the  
burner control is energized. To check, turn power off,  
disconnect the igniter lead from the burner control. Turn  
power on. If no spark is visible, replace burner control.  
If a spark is visible at burner control, proceed.  
Check the burner igniter head for any damage or  
obstructions also check for frayed or broken wire.  
Check spark gap, gap should be 3/32” If there is visible  
damage, replace burner igniter.  
If there is supply voltage to the burner control, and the  
pilot valve and igniter circuits are energized, visually  
check for a pilot flame. This may be done by looking  
through the inspection view port on the end of the  
burner. If no pilot flame is visible, check the pilot tube.  
Check for gas pressure at the pilot tube. Disconnect  
pilot tube at the burner and connect manometer to pilot  
tube. If no gas pressure is present during ignition,  
check for blockage of the pilot tube. If the pilot tube is  
clear, proceed.  
Burner igniter  
No pilot flame  
Pilot tube  
Pilot orifice  
If there is gas pressure at the pilot tube, check the pilot  
orifice for blockage or obstructions. Replace pilot orifice  
as needed.  
Burner igniter  
Check the burner igniter head for any damage or  
obstructions also check for frayed or broken wire.  
Check spark gap, gap should be 3/32” If there is visible  
damage, replace burner igniter.  
Flame sensor  
(There should be a visible pilot flame at this time.)  
To check for proper flame sensor operation, connect a  
digital multimeter (capable of measuring D.C. micro  
amps) in series between the flame sensor wire  
(normally connected to terminal #13 on the burner  
control) and terminal #13 on the burner control. With a  
visible pilot flame, the current reading should be 0.7  
micro amp minimum. NOTE: The D.C. micro amp test  
must be conducted with the oven in low flame operation  
only. If these values are not achieved, replace flame  
sensor. Also check for any type of damage to flame  
sensor wire and connections.  
Power supply  
Burner control  
If there is a pilot flame, and there is sufficient micro  
amp. current, but the flame will not stay on, check for  
proper polarity of the power supply.  
If there is sufficient micro amp current, and there is  
proper polarity of the power supply, but the burner will  
not stay on, check the reset button for the burner  
control. If the reset switch checks okay, replace the  
burner control.  
Pilot flame, but no main flame  
Impinger X2 – Analog Service Manual – Dom & Int’l  
NOTE: Flame should be  
Check for supply voltage to electronic temperature  
13  
On at this time  
Electronic temperature  
control  
control at terminals #13 and #12. Of there is no voltage,  
trace wiring back to the burner switch. Also check for  
supply voltage to terminal #20 on the electronic  
temperature control. If there is no voltage at terminal  
#20, trace wiring back to terminal #13. Set temperature  
control to maximum temperature and check for output  
voltage at terminal #21 and neutral. If voltage is present  
at terminal #20 and neutral, and the unit is not heating,  
refer to “Temperature regulation valve” for next check.  
If voltage is not present, proceed.  
Thermocouple probe  
WITH POWER ON AND THERMOCOUPLE LEADS  
ATTACHED TO THE ELECTRONIC TEMPERATURE  
CONTROL: Measure the D.C. millivolt output of these  
leads. Refer to chart in the “Removal, Installation and  
Adjustment” section for proper readings. If these  
readings are not achieved, replace thermocouple.  
Check for supply voltage to main valve. If no voltage is  
present, trace wiring back to burner control. If there is  
no voltage output, replace burner control.  
Check for supply voltage to main valve. If there is  
voltage present, check to see that valve is opening.  
Connect manometer to pressure tap on outlet side of  
valve. If there is voltage to the valve, but no output gas  
pressure, replace the valve.  
Burner control.  
Main gas valve  
Temperature regulation valve If supply voltage is present on the electronic  
temperature control, terminal #13 to neutral, check for  
voltage at temperature regulation valve. If no voltage is  
present, trace wiring back to electronic temperature  
control, terminal #20. If voltage is present, listen for  
valve to open and close. Also check for opens or shorts  
in the operating coil. Replace temperature regulation  
valve as needed.  
Intermittent heating  
Conveyor will not run  
Thermal/Overload of main fan The main fan motor and burner blower motor are  
and burner blower motors  
equipped with internal thermal protection and will cease  
to operate if overheating occurs. As the motors over-  
heat and then cool, this will cause the units to cycle on  
and off intermittently. Improper ventilation or lack of  
preventive maintenance may cause this. Also, most of  
the problems listed under “Oven will not heat” can  
cause intermittent failure.  
NOTE: The ovens may contain two, three or four conveyor drive systems using like  
components. The trouble shooting sequence will be the same for each of the conveyor  
drive systems  
Power supply  
Check circuit breakers, reset if required. Check power  
plug to be sure it is firmly in receptacle. Measure  
incoming power, call power co. if needed.  
Switch, oven fan  
Relay, main fan  
Check continuity between switch terminals. Replace  
switch as needed.  
Check for supply voltage to relay terminal #13. If  
voltage is not present, trace wiring back to power  
supply. If voltage is present, check for supply voltage at  
terminal #14. If there is no voltage at terminal #14, and  
the relay is energized, replace the main fan relay.  
Check, replace if necessary.  
Check for supply voltage to fuse holder. If no voltage is  
present, trace wiring back to main fan relay. Check fuse  
holder, replace if necessary.  
Fuse, 2 Amp  
Fuse holder  
Switch, conveyor  
Check for supply voltage to conveyor switch. If no  
voltage is present, trace wiring back to fuse holder.  
Check continuity between switch terminals. Replace  
Impinger X2 – Analog Service Manual – Dom & Int’l  
14  
switch as needed.  
Control, conveyor  
Check for supply voltage to conveyor control at  
terminals #1 (AC) and #2 (AC). If no voltage is present,  
trace wiring back to conveyor switch. If AC voltage is  
present, check for DC voltage output at terminals #3  
(A-) and #4 (A+). If there is AC voltage in, but no DC  
voltage out of the conveyor control. Replace the  
conveyor control. If there is D.C. voltage output,  
proceed.  
Fuse, 2 Amp  
Fuse holder  
Check, replace if necessary.  
Check for D.C. voltage supplied to fuse holder. If no  
voltage is present, trace wiring back to conveyor  
control. Check fuse holder, replace if necessary.  
Check for D.C. voltage supplied to the reversing switch.  
If no voltage is present, trace wiring back to the fuse  
holder. Check continuity between switch terminals.  
Replace switch as needed.  
Check for D.C. voltage to the conveyor motor. If no  
voltage is present, trace wiring back to the reversing  
switch. If voltage is present and the motor will not run,  
check the motor windings for opens or shorts. Check  
motor brushes for excessive wear. Replace motor  
brushes as needed.  
Switch, conveyor reversing  
Conveyor motor  
If any of the above fails, replace conveyor motor.  
Check for any mechanical problems in the conveyor  
assembly. Check for damaged or torn belting. Check  
conveyor shaft bearings for damage or excessive wear.  
Repair or replace conveyor components as needed.  
Check for a steady supply voltage to the conveyor  
control. If voltage is not steady, trace back to power  
supply.  
Check for a steady DC voltage output at terminals A+  
and A-. If voltage is not steady, proceed. Check for  
5 VDC output from the conveyor control at terminals  
+5V(red) and COM (black). If there is no voltage output,  
replace the conveyor control. If there is DC output,  
proceed.  
Conveyor  
Conveyor speed varying or  
intermittent  
Power supply  
Control, conveyor  
Motor, conveyor  
Check conveyor motor and gearbox for any visible  
damage. If there is apparent damage, repair or replace  
conveyor motor. Check motor brushes for excessive or  
abnormal wear. Replace motor brushes as needed.  
Check to be sure that the Hall effect sensor and  
magnet are mounted on the motor. Check for any  
visible damage to the Hall effect sensor and magnet. If  
there is visible damage, repair or replace as needed. If  
there is no visible damage, check for a frequency  
output from the hall effect sensor at terminals SIG  
(white) and COM (black).  
Hall effect sensor/magnet  
Readings should be as follows:  
2:15 cook time  
5:00  
56 Hz. approx.  
25 Hz. approx.  
13 Hz. approx.  
8 Hz. approx.  
10:00  
16:00  
If these readings are not achieved, replace the Hall  
effect sensor/magnet  
Impinger X2 – Analog Service Manual – Dom & Int’l  
15  
REMOVAL, INSTALLATION & ADJUSTMENTS  
IMPINGER X2 SERIES OVENS  
CAUTION!  
BEFORE REMOVING OR INSTALLING ANY COMPONENT IN THE IMPINGER X2  
OVEN BE SURE TO DISCONNECT ELECTRICAL POWER AND GAS SUPPLY  
MOTOR, MAIN FAN - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control box cover and control box rear cover.  
Disconnect motor wiring and mark all wiring for reassembly.  
Remove V-belt by loosening the four bolts on the motor mount plate and the two belt tensioning bolts.  
Remove motor and motor mount assembly. Remove motor from motor mount. Remove pulley from motor  
and install pulley on new motor.  
6.  
Reassemble in reverse order and check system operation. Be sure to check for proper tension on drive  
belt. Adjust tension bolts until there is no more than 3/8 inch deflection at the halfway point between the  
motor pulley and the driven pulley.  
SHAFT AND BLOWER WHEEL – REPLACEMENT  
1. Shut off power at main breaker.  
2. Remove cover panels form both sides.  
3. Remove back.  
4. Unbolt blower housings  
5. Remove thermocouple from mount  
6. Remove flanges from blower housing  
( mark position of flange for replacement)  
7. Unbolt air return panels from inside top  
8. Remove sheet metal from plenum  
16  
Impinger X2 – Analog Service Manual – Dom & Int’l  
9. Remove burner tube bracket  
and Burner tube.  
To remove burner tube,  
Remove cap from idle end of  
Oven wall and remove burner tube.  
10. Measure distance from end of shaft to the collar  
11. of blower wheel. Loosen blower wheels from shaft.  
(1/4" allen screws - use liquid wrench)  
Push blower wheels toward idle end.  
12.Loosen and remove idle and drive end bearings.  
13.Remove shaft and blower wheel assembles.( measure length of  
shaft extension from oven wall. Use same measurement when  
putting new shaft in)  
Remove shaft through idle end of oven.  
14.NOTE: When putting new shaft and blower wheels back in, the wheels will have to be removed from the shaft.  
It is important to mark the blowers left and right and to mark the positioning of the blowers on the shaft so as to  
maintain spacing and balance.  
When replacing the burner tube, the top  
of the holes in the burner tube should be  
12 3/8" from the bottom of the oven.  
15. When replacing the expansion bearing in  
the drive end, be sure the yoke of the bearing  
is pushed as far as possible towards the  
oven wall and tightened on the shaft. This  
will allow the bearing to expand outward.  
Align pulley on drive end of shaft with  
pulley on drive motor. Grease bearings  
before starting oven.  
Impinger X2 – Analog Service Manual – Dom & Int’l  
17  
RELAY, MAIN FAN, - REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect all wiring from relay and mark all wiring for reassembly.  
Remove main relay and overload protector.  
Remove overload protector from main relay and mount overload protector on new relay.  
Reassemble in reverse order and check system for proper operation.  
TIMER, 30 MINUTE COOL DOWN – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect all wiring from 30-minute cool down timer and mark all wires for reassembly.  
Remove one mounting bolt and remove 30-minute cool down timer.  
Reassemble in reverse order and check system operation.  
FUSE HOLDER – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect wiring from fuse holder and mark all wiring for reassembly.  
Remove mounting nut from fuse holder and remove fuse holder.  
Reassemble in reverse order and check system operation.  
SWITCH, ON/OFF – REPLACEMENT  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect wiring from switch and mark all wiring for reassembly.  
Remove switch by loosening the mounting screw at the bottom of the switch and lifting the  
release lever at the top of the switch. Lifting the release lever allows the front portion of the switch  
to separate from the rear portion of the switch.  
5.  
Reassemble in reverse order and check system operation.  
MOTOR, BURNER BLOWER – REPLACEMENT  
1.  
2.  
3.  
Shut off power at main breaker.  
Remove control box cover and front control box cover.  
Remove box cover from burner blower motor and disconnect wiring from motor. Mark all wiring  
for reassembly.  
4.  
5.  
Remove three mounting screws and remove burner blower motor assembly.  
Remove box and components from the old burner blower motor and mount on new burner blower  
motor. Mark all wiring for proper assembly. Remove air shutter assembly from old motor and  
mount on new motor.  
6.  
Reassemble in reverse order and check system operation.  
TRANSFORMER, BURNER – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control box cover and front control box cover.  
Remove box cover from burner blower motor.  
Disconnect wiring from burner transformer and mark all wiring for reassembly.  
Remove two mounting screws and remove burner transformer.  
Reassemble in reverse order and check system operation.  
RELAY, BURNER BLOWER – REPLACEMENT  
1.  
2.  
3.  
Shut off power at main breaker.  
Remove control box cover and front control box cover.  
Remove box cover from burner blower motor.  
18  
Impinger X2 – Analog Service Manual – Dom & Int’l  
4.  
5.  
6.  
Disconnect wiring from burner blower relay and mark all wiring for reassembly.  
Remove two mounting screws and remove burner blower relay.  
Reassemble in reverse order and check system operation.  
BURNER CONTROL – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control box cover  
Disconnect wiring from burner control and mark all wiring for reassembly.  
Remove mounting screws and remove burner control.  
Reassemble in reverse order and check system operation.  
AIR PRESSURE SWITCH – REPLACEMENT  
1.  
2.  
3.  
Shut off power at main breaker.  
Remove control box cover and rear control box cover.  
Remove cover from air pressure switch. Disconnect wiring from air pressure switch and mark all  
wiring for reassembly.  
4.  
Remove air switch tube from air pressure switch. Note location of air switch tube, tube must be  
connected to the “HIGH” port of the air pressure switch.  
Remove mounting screws and remove air pressure switch.  
Reassemble in reverse order. Adjust air pressure switch for proper operation (see below) and  
check system operation.  
5.  
6.  
AIR PRESSURE SWITCH – ADJUSTMENT  
1.  
Start the oven. After the burner ignites, turn the air pressure switch adjustment screw Clockwise  
until the burner shuts off.  
2.  
3.  
4.  
Turn the adjustment screw Counterclockwise until the burner ignites, plus one full turn.  
Seal adjustment screw with nail polish.  
Replace cover on air pressure switch.  
ELECTRONIC TEMPERATURE CONTROL – REPLACEMENT  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect wiring from electronic temperature control and mark all wiring for reassembly.  
Locate and remove mounting screw at the bottom center of the electronic temperature control.  
Remove control from control base.  
5.  
6.  
Remove two mounting screws from control base and remove control base from oven.  
Reassemble in reverse order and check calibration of new control (see below) and check system  
operation.  
ELECTRONIC TEMPERATURE CONTROL – CALIBRATION  
1.  
2.  
Turn burner switch off.  
Remove electronic temperature control from the mounting base by removing one retaining screw  
at the bottom of the electronic temperature control. Pull electronic temperature control from it’s  
mounting base.  
3.  
4.  
5.  
Locate Hairpin switch on the control and open the Hairpin switch. (See photo, next page)  
Replace control in the mounting base.  
Turn the burner switch on. If the display reads “CAL”, press the “UP” arrow until the display reads  
“Cnf” on the SV (orange) display.  
Press the FUNC key until the display reads “P13” in the SV (orange) portion of the display. Using  
the “UP” or “DOWN” arrows, adjust the “PV” (yellow) portion of the display to read 500. This is the  
offset point.  
Press the FUNC key until the display reads “P14” in the SV (orange) portion of the display. Using  
the “UP” or “DOWN” arrows, adjust the “PV” (yellow) portion of the display to read –50. This is the  
“offset value”. (continued next page)  
6.  
Impinger X2 – Analog Service Manual – Dom & Int’l  
19  
7.  
8.  
Press the “FUNC” key until the display reads “Cnf”. Shut off burner, remove control from the  
mounting base. Close the Hairpin switch on the control and replace the control in the mounting  
base.  
Turn the burner on. Set oven temperature to 500°F and verify calibration. Allow oven to preheat  
for at least 30 minutes. Place temperature probe in the center of the oven, on the top conveyor.  
If the actual temperature differs from the displayed temperature more than 5°, the “offset value”  
must be adjusted (steps 2 through 7), until the proper temperature is indicated on the display.  
Reassemble in reverse order and check system operation.  
9.  
HAIRPIN SWITCH  
THERMOCOUPLE – REPLACEMENT  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect thermocouple from electronic temperature control. Note wire colors for reassembly.  
Remove oven back assy. Remove thermocouple from mounting flange in blower housing. Remove  
thermocouple from oven.  
5.  
Reassemble in reverse order and check system operation.  
THERMOSTAT, HI-LIMIT – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect all wiring from hi-limit thermostat and mark all wiring for reassembly.  
Remove oven back assy. Remove capillary tube from mounting bracket.  
Remove mounting nut and remove hi-limit thermostat from oven.  
Reassemble in reverse order and check system operation.  
NOTE: Depress reset button to insure thermostat is set for operation.  
TEMPERATURE REGULATION VALVE – REPLACEMENT  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Shut off the gas supply to the oven and disconnect the flexible gas hose from the oven.  
Remove control box cover.  
Disconnect all wiring from the temperature regulation valve and the main gas valve. Mark all wiring for  
reassembly.  
Remove pilot tube from gas valve. Disconnect pipe union at the burner and at the inlet side of the main  
gas valve. Loosen pipe clamp and remove valves and piping assembly.  
Remove piping from old valve and reassemble in reverse order.  
Check all gas line fittings for leaks and check system operation.  
5.  
6.  
7.  
GAS VALVE – REPLACEMENT  
1.  
2.  
3.  
Shut off power at main breaker.  
Shut off the gas supply to the oven and disconnect the flexible gas hose from the oven.  
Remove control box cover.  
20  
Impinger X2 – Analog Service Manual – Dom & Int’l  
4.  
5.  
Disconnect all wiring from the temperature regulation valve and the main gas valve. Mark all wiring for  
reassembly.  
Remove pilot tube from gas valve. Disconnect pipe unions at the burner and at the inlet side of the main  
gas valve. Loosen pipe clamp and remove valves and piping assembly.  
Remove piping from old valve and reassemble in reverse order.  
Check all gas line fittings for leaks and adjust manifold pressure on gas valve. Refer to the specification  
plate on the oven for proper gas manifold pressure. Check system operation.  
6.  
7.  
MAIN BURNER ORIFICE – REPLACEMENT  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Shut off the gas supply to the oven and disconnect the flexible gas hose from the oven.  
Remove control box cover and control box front cover.  
Remove pilot tube from gas valve. Disconnect pipe union at burner, loosen pipe union at inlet to gas  
valve, loosen pipe clamp and move piping away from burner.  
Remove two mounting nuts from burner flange and remove burner flange.  
Remove main burner orifice from the burner flange.  
5.  
6.  
7.  
8.  
Reassemble in reverse order.  
Check all gas line fittings for leaks and check system operation.  
PILOT ORIFICE – REPLACEMENT  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Shut off the gas supply to the oven and disconnect the flexible gas hose from the oven.  
Remove control box cover and control box front cover.  
Remove pilot tube from gas valve. Disconnect pipe union at burner and at inlet to main gas valve. Loosen  
pipe clamp and move piping away from burner.  
Disconnect wiring from burner and mark wiring for reassembly.  
Remove four screws from burner end plate and remove burner assembly from burner housing.  
Remove pilot tube from igniter assembly and remove pilot orifice.  
Reassemble in reverse order. Check all gas line fittings for leaks. Check system operation.  
5.  
6.  
7.  
8.  
SPARK IGNITER – REPLACEMENT  
1.  
2.  
3.  
4.  
Shut off power at main breaker.  
Shut off the gas supply to the oven and disconnect the flexible gas hose from the oven.  
Remove control box cover and control box front cover.  
Remove pilot tube from gas valve. Disconnect pipe union at burner and at inlet to main gas valve. Loosen  
pipe clamp and move piping away from burner.  
Disconnect wiring from burner and mark wiring for reassembly.  
Remove four screws from burner end plate and remove burner assembly from burner housing.  
Remove pilot tube, pilot shield and pilot orifice from spark igniter and remove spark igniter.  
Reassemble in reverse order and check system operation.  
5.  
6.  
7.  
8.  
CONVEYOR MOTOR – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
6.  
Shut off power at main breaker.  
Remove control box cover and front control box cover.  
Disconnect wiring from the conveyor motor assembly and mark all wiring for reassembly.  
Remove four screws and remove conveyor motor assembly.  
Remove hall effect sensor and magnet (one mounting nut) and mounting stud from old motor.  
Reassemble in reverse order and check system operation.  
REVERSING SWITCH – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect wiring from reversing switch and mark all wiring for reassembly.  
Remove mounting nut from reversing switch and remove reversing switch.  
Reassemble in reverse order and check system operation.  
Impinger X2 – Analog Service Manual – Dom & Int’l  
21  
HALL EFFECT SENSOR – REPLACEMENT  
1.  
2.  
3.  
4.  
5.  
Shut off power at main breaker.  
Remove control box cover.  
Disconnect all wiring from hall effect sensor and mark all wiring for reassembly.  
Remove mounting nut and remove hall effect sensor and magnet.  
Reassemble in reverse order and check system operation.  
CONVEYOR CONTROL – REPLACEMENT  
1.  
2.  
3.  
Shut off power at main breaker.  
Remove control box cover.  
Remove top and rear covers from conveyor control. Disconnect all wiring from the conveyor control and  
mark all wiring for reassembly.  
4.  
5.  
Remove two screws and remove faceplate from conveyor control. Remove two mounting screws and  
remove conveyor control.  
Reassemble in reverse order, set control for proper programming (see CONVEYOR CONTROL -  
PROGRAMMING) and check system operation.  
22  
Impinger X2 – Analog Service Manual – Dom & Int’l  
CONVEYOR CONTROL – PROGRAMMING  
1.  
2.  
Determine which brand of motor is connected to the conveyor control.  
Determine which type of dart conveyor control is installed in the oven. Looking at the face of the control,  
the old style control will have “up” and “down” keys only. The new style Dart conveyor control will have  
“up”, “down” and “enter” keys.  
3.  
4.  
Determine the type of drive, direct, 10/15 chain reduction or right angle drive.  
Determine the bake chamber size, 40”, 62” or 70”.  
“DART” Conveyor control with “UP” and “DOWN” keys only (OLD STYLE).  
DIP switches  
1.  
2.  
3.  
4.  
Remove control box cover.  
Remove top cover from conveyor control. Make sure that all DIP switches are in the OFF position.  
Turn oven on, turn conveyor on. Set switch #7 to ON position. Display should read “PROG”.  
Set switch #4 to ON position to set time mode. Press “UP” or “DOWN” keys to set value at :05. Set  
switch #4 to OFF, display should read “PROG” and a colon should be lit.  
5.  
Set switch #1 to ON position to set constant. Use the “UP” or “DOWN” keys to set the following:  
CHAMBER  
LENGTH  
DRIVE  
TYPE  
CONSTANT  
DAYTON  
CONSTANT  
GLEASON  
AVERY 60Hz.  
2:25  
CONSTANT  
GLEASON  
AVERY 50Hz.  
2:17  
40”  
62”  
70”  
Direct  
10/15 chain reduction  
Right angle motor  
2:00  
3:01  
1:31  
Direct  
10/15 chain reduction  
Right angle motor  
3:07  
4:40  
2:22  
3:45  
4:14  
3:33  
Direct  
10/15 chain reduction  
Right angle motor  
3:31  
5:16  
2:40  
6.  
7.  
Set switch #1 to OFF position, display should read “PROG”.  
Set switch #2 to ON position to set minimum setting. Use “UP” or “DOWN” keys to set to 2:15. Set switch  
#2 to OFF position, display should read “PROG”.  
Set switch #3 to ON position, to set maximum setting. Use “UP” or “DOWN” keys to set to 16:00. Set  
switch #3 to OFF position, display should read ”PROG”.  
Set switch #7 to OFF position. Programming is complete.  
Reassemble in reverse order and check system operation.  
8.  
9.  
10.  
Impinger X2 – Analog Service Manual – Dom & Int’l  
23  
CONVEYOR CONTROL – PROGRAMMING – DAYTON MOTOR, DIRECT DRIVE  
Jumper  
“DART” Conveyor control with “UP”, “DOWN” and “ENTER” keys (NEW STYLE).  
1.  
2.  
Remove control box cover.  
Remove top cover from conveyor control. Locate program jumper on conveyor control and set jumper to  
the “ON” position.  
3.  
4.  
Turn oven on, turn conveyor on. Press and hold the “ENTER” key until the Parameter Selection Mode is  
entered (display will indicate “P 0”).  
Using the “UP” or “DOWN” keys, select the parameters to be changed (See chart below). When the  
parameter is selected, press “ENTER”. Use the “UP” or “DOWN” keys to set the desired parameter.  
Press “ENTER” to save the changes.  
After all parameters are programmed, select parameter 0 and press the “ENTER” key to return to the  
running mode.  
5.  
6.  
7.  
Set program jumper on conveyor control to “OFF”.  
Reassemble in reverse order and check system operation.  
Parameter  
40” Oven  
62” Oven  
70” Oven  
Explanation  
Time Mode Setting (MM:SS)  
10  
20  
21  
30  
31  
32  
50  
53  
98  
2
135  
960  
135  
1609  
1
7
1
5
2
135  
960  
135  
2494  
1
7
1
5
2
135  
960  
135  
2816  
1
7
1
5
Display minimum setting (value is in seconds)  
Display maximum setting (value is in seconds)  
Display setting at reference RPM, parameter 31  
RPM at which display reference, should be displayed  
Pulses per revolution of shaft encoder or pickup  
Activate alarm when pickup stalled  
Alarm flash enabled  
Save parameter settings to user default area  
24  
Impinger X2 – Analog Service Manual – Dom & Int’l  
CONVEYOR CONTROL – PROGRAMMING – DAYTON MOTOR, RIGHT ANGLE DRIVE  
Jumper  
“DART” Conveyor control with “UP”, “DOWN” and “ENTER” keys.  
8.  
9.  
Remove control box cover.  
Remove top cover from conveyor control. Locate program jumper on conveyor control and set jumper to  
the “ON” position.  
10.  
11.  
Turn oven on, turn conveyor on. Press and hold the “ENTER” key until the Parameter Selection Mode is  
entered (display will indicate “P 0”).  
Using the “UP” or “DOWN” keys, select the parameters to be changed (See chart below). When the  
parameter is selected, press “ENTER”. Use the “UP” or “DOWN” keys to set the desired parameter.  
Press “ENTER” to save the changes.  
After all parameters are programmed, select parameter 0 and press the “ENTER” key to return to the  
running mode.  
12.  
13.  
14.  
Set program jumper on conveyor control to “OFF”.  
Reassemble in reverse order and check system operation.  
Parameter  
62” Oven  
Explanation  
Time Mode Setting (MM:SS)  
10  
20  
21  
30  
31  
32  
50  
53  
98  
2
135  
960  
135  
1894  
1
7
1
5
Display minimum setting (value is in seconds)  
Display maximum setting (value is in seconds)  
Display setting at reference RPM, parameter 31  
RPM at which display reference, should be displayed  
Pulses per revolution of shaft encoder or pickup  
Activate alarm when pickup stalled  
Alarm flash enabled  
Save parameter settings to user default area  
Impinger X2 – Analog Service Manual – Dom & Int’l  
25  
CONVEYOR CONTROL – PROGRAMMING – GLEASON AVERY MOTOR, DIRECT DRIVE  
Jumper  
“DART” Conveyor control with “UP”, “DOWN” and “ENTER” keys.  
15.  
16.  
Remove control box cover.  
Remove top cover from conveyor control. Locate program jumper on conveyor control and set jumper to  
the “ON” position.  
17.  
18.  
Turn oven on, turn conveyor on. Press and hold the “ENTER” key until the Parameter Selection Mode is  
entered (display will indicate “P 0”).  
Using the “UP” or “DOWN” keys, select the parameters to be changed (See chart below). When the  
parameter is selected, press “ENTER”. Use the “UP” or “DOWN” keys to set the desired parameter.  
Press “ENTER” to save the changes.  
After all parameters are programmed, select parameter 0 and press the “ENTER” key to return to the  
running mode.  
19.  
20.  
21.  
Set program jumper on conveyor control to “OFF”.  
Reassemble in reverse order and check system operation.  
Parameter  
40” Oven  
62” Oven  
70” Oven  
Explanation  
Time Mode Setting (MM:SS)  
10  
20  
21  
30  
31  
32  
50  
53  
98  
2
135  
960  
135  
1933  
1
7
1
5
2
135  
960  
135  
2997  
1
7
1
5
2
135  
960  
135  
3383  
1
7
1
5
Display minimum setting (value is in seconds)  
Display maximum setting (value is in seconds)  
Display setting at reference RPM, parameter 31  
RPM at which display reference, should be displayed  
Pulses per revolution of shaft encoder or pickup  
Activate alarm when pickup stalled  
Alarm flash enabled  
Save parameter settings to user default area  
26  
Impinger X2 – Analog Service Manual – Dom & Int’l  
This page intentionally left blank.  
Impinger X2 – Analog Service Manual – Dom & Int’l  
27  
IMPINGER X2 OVENS  
GENERAL VIEW  
LETTER  
PART NUMBER  
DESCRIPTION  
A
B
C
D
E
F
G
H
I
9004415  
9004415  
9004422  
9004422  
9004416  
9004416  
7007757  
7007168  
7007168  
1111302010  
1001303010  
2001303020  
7007378  
7007378  
300801140-1  
100801140-1  
200801140-1  
300801140  
100801140  
200801140  
2805112  
100804622  
100302900  
100303900  
300202036  
100202036  
200202036  
9004447  
9004443  
9004417  
9004448  
9004434  
9004418  
100537902  
9409  
Finger housing, bottom (3240), #5 left (3262, 3270)  
Finger housing, bottom (3240), #6 right (3262, 3270)  
Finger housing, middle (3240), #3 left (3262, 3270)  
Finger housing, middle (3240), #4 right (3262, 3270)  
Finger housing, top, (3240), #1 left (3262, 3270)  
Finger housing, top, (3240), #2 right (3262, 3270)  
Finger cover, top  
Finger cover, middle  
Finger cover bottom  
Air return, middle, upper model 3262, 3270  
Air return, lower model 3262  
Air return, lower model 3270  
Finger guide assy. model 3240, 3262, 3270  
Finger guide, rear  
Door, solid - 3240  
Door, solid – 3262  
Door, solid – 3270  
Door, w/window – 3240  
Door, w/window – 3262  
Door, w/window – 3270  
Nameplate, Impinger X2  
Sandwich door assy.  
J
K
L
M
N
O
P
Q
Caster, 5”  
Caster, 5” w/brake  
R
S
T
Bottom finger support, 3240  
Bottom finger support, 3262  
Bottom finger support, 3270  
Center finger support, 3240  
Center finger support, 3262  
Center finger support, 3270  
Top finger support, 3240  
Top finger support, 3262  
Top finger support, 3270  
Door latch assy.  
Oven base, high – 3240  
U
V
9414  
9402  
Oven base, low –3240  
Oven base, high – 3262  
9411  
9404  
Oven base, low – 3262  
Oven base, high – 3270  
9412  
Oven base, low – 3270  
Hinge plate, left  
Hinge plate, right  
Center air return, upper – 3262  
Center air return, upper – 3270  
Center air return, middle – 3263  
Center air return, middle – 3270  
Center air return, lower – 3262  
Center air return, lower - 3270  
W
X
Y
Z
108003-1EP  
108003-2EP  
9004439  
9004436  
9004440  
9004437  
9004441  
9004438  
28  
Impinger X2 – Analog Service Manual – Dom & Int’l  
Impinger X2 – Analog Service Manual – Dom & Int’l  
29  
IMPINGER X2 OVENS  
OVEN CAVITY  
LETTER  
A
PART NUMBER  
DESCRIPTION  
Guard, shaft – 3262  
Guard, shaft – 3270  
9004435  
9004419  
B
C
4071215  
Housing, blower  
100601417  
200601417  
100601417  
200601417  
100601394  
100110224  
100102601  
100106000  
300601280  
100601280  
200601280  
300601328  
100601328  
200601328  
3001401011  
1001401011  
2001401011  
100601334/100601336  
100601324  
390048  
Air return plate, right – 3240, 3262  
Air return plate, right – 3270  
Air return plate, left – 3240, 3262  
Air return plate, left – 3270  
Air dam, upper  
Close-off, upper plenum  
Support, oven cavity  
D
E
F
G
H
I
Plate, connector  
Extension tube, burner – 3240  
Extension tube, burner – 3262  
Extension tube, burner – 3270  
Shaft, blower wheel assy. – 3240  
Shaft, blower wheel assy. – 3262  
Shaft, blower wheel assy. – 3270  
Oven back – 3240  
Oven back – 3262  
Oven back – 3270  
Burner heat shield, outer, inner  
Burner opening cover  
Heat slinger – 3240  
J
K
L
M
N
390047  
390063  
9004431  
100120224  
100110204  
7007374  
Heat slinger – 3262, 3270  
Bearing, idler  
Top cover, idler end  
O
P
Q
R
S
Cover, idler end  
Flange, thermocouple mount  
Guard, center air return – 3262  
Guard, center air return - 3270  
7007375  
30  
Impinger X2 – Analog Service Manual – Dom & Int’l  
Impinger X2 – Analog Service Manual – Dom & Int’l  
31  
IMPINGER X2 OVENS  
CONTROL BOX  
LETTER  
PART NUMBER  
DESCRIPTION  
Coupling w/sleeve  
Front cover –2 oven  
Front cover – 2TS oven (split belt top)  
Front cover – 2SB oven (split belt bottom)  
Front cover –2SS oven (split belt top and bottom)  
Conveyor drive motor  
A
B
508120EP  
100501329  
100501327  
100501326  
100501325  
501176MEP  
501110EP  
100507900/100507705  
508202EP  
390069  
C
D
E
F
Hall effect sensor  
Pulley, shaft/ Sheave, driver  
V-belt, 3240, 3262, 3270 – 60Hz. (BK 52 x 7/8”)  
V-belt, 3240, 3262, 3270 – 50Hz. (BK 45 x 7/8”)  
Pulley, motor, 3240, 3262, 3270 – 60 Hz.  
Pulley, motor, 3240, 3262, 3270 – 50 Hz.  
Motor, main fan – 60 Hz. 1 phase  
Motor, main fan – 60 Hz. 3 phase  
Motor, main fan – 50 Hz. 1 phase  
Air pressure switch  
Air pressure switch (CE ovens)  
Switch, conveyor reversing  
Ignition control, 60 Hz. ovens  
Ignition control, 50 Hz. ovens  
Relay/overload, 3240  
Relay/overload, 3262, 3270  
Cool-down timer, 120VAC  
Cool-down timer, 230VAC  
Terminal block, 5-pole  
Cover, rear  
Cover, control box top  
G
H
390070  
390059  
4060276  
4060274  
4060275  
501070EP  
369575  
390075  
501250-2EP  
370396  
390067  
390068  
601492EP  
370466  
4000214  
100501232  
9004432  
369368  
4090413  
501201EP  
4070599  
I
J
K
L/M  
N
O
P
Q
R
S
T
Thermostat, oven cavity hi-limit  
Fuse holder, 6 position  
Fuse, 2A  
Fuse holder, 60 Hz. ovens  
Fuse holder, CE ovens (50 Hz.)  
Plug connector, diagnostic (part of wire harness)  
Control, conveyor  
U
370342  
V
W
X
501100EP  
390060  
Switch, ON/OFF  
Y
Z
AA  
501085EP  
501090EP  
9004363  
9004364  
9004365  
9004347  
4071191  
370180  
Control, temperature  
Thermocouple, type ”J”  
Control panel, -2 oven  
Control panel, -2SB oven (split belt bottom)  
Control panel, -2TS oven (split belt top)  
Control panel, -2SS oven (split belt top and bottom)  
Strain relief  
EMI Filter (Export only)  
RFI Filter (Export only)  
BB  
Not shown  
Not shown  
370184  
32  
Impinger X2 – Analog Service Manual – Dom & Int’l  
Impinger X2 – Analog Service Manual – Dom & Int’l  
33  
IMPINGER X2 OVENS  
BURNER/DRIVE END  
LETTER  
PART NUMBER  
DESCRIPTION  
Flange, burner  
Heat slinger, 3240  
A
B
7007124  
390048  
390047  
Heat slinger, 3262, 3270  
Bearing, drive end  
Motor, burner blower  
Relay, time delay  
Transformer, 120/24VAC  
Flame target  
Igniter/sensor assy.  
C
D
E
F
G
H
I
507500EP  
501260EP  
501250-8EP  
369531  
369142  
501250-1EP  
100501271  
Shield, pilot  
J
K
Cable, spark  
Orifice, pilot, Nat.  
2605078  
Orifice, pilot, L.P.  
Manifold, burner  
L
M
370059  
369398  
Valve, temperature regulation (120 VAC)  
Valve, temperature regulation (CE ovens, 220VAC)  
Valve, main gas (24VAC)  
Valve, main gas (CE ovens, 220 VAC)  
Orifice, main burner, Nat.  
Orifice, Main burner, L.P.  
Moveable plate, air shutter  
Air shutter  
370186  
50150-5EP  
370433  
N
O
2605080  
P
Q
369400  
369399  
34  
Impinger X2 – Analog Service Manual – Dom & Int’l  
Impinger X2 – Analog Service Manual – Dom & Int’l  
35  
IMPINGER X2 OVENS  
CONVEYOR, SINGLE  
LETTER  
A
PART NUMBER  
DESCRIPTION  
Shelf, infeed side  
Shelf, out take side  
Pan stop, zero stop  
Crumb pan (bottom conveyor only)  
Connecting link  
Conveyor belt - complete, 3240  
Conveyor belt - complete, 3262  
Conveyor belt - complete, 3270  
Conveyor belt –1ft. section  
Bushing assembly, single belt  
Shaft, idle end  
100403103  
100403101  
100403107  
10040710  
369005  
100405831  
100405810  
100405830  
405830-1EP  
390051  
100404710  
406000EP  
405900EP  
300403331  
100403361  
200403390  
300403330  
100403360  
200403380  
508103EP  
100404810  
B
C
D
E
F
G
H
I
Roller, smooth  
Roller, notched  
J
Frame assembly, upper conveyor, 3240  
Frame assembly, upper conveyor, 3262  
Frame assembly, upper conveyor, 3270  
Frame assembly, lower conveyor, 3240  
Frame assembly, lower conveyor, 3262  
Frame assembly, lower conveyor, 3270  
Coupling half  
K
L
Shaft, drive end  
36  
Impinger X2 – Analog Service Manual – Dom & Int’l  
Impinger X2 – Analog Service Manual – Dom & Int’l  
37  
IMPINGER X2 OVENS  
CONVEYOR, DUAL BELT  
LETTER  
A
PART NUMBER  
DESCRIPTION  
100403103  
100403101  
100403107  
100403710  
405849-2EP  
100405847  
405849EP  
100405844  
405849-1EP  
390050  
100404710  
406000EP  
405900EP  
300403331  
100403361  
200403390  
300403330  
100403360  
200403380  
508103EP  
100404810  
Take off shelf, infeed side  
Take off shelf, out take side  
Pan stop, zero stop  
Crumb pan (bottom conveyor only)  
Connecting link  
Conveyor belt, complete, 3240  
Conveyor belt, complete, 3262  
Conveyor belt, complete, 3270  
Conveyor belt, 1ft. section  
Bushing assembly, dual belt  
Shaft, idle end  
B
C
D
E
F
G
H
I
Roller, smooth  
Roller, notched  
J
Frame assembly, upper conveyor, 3240  
Frame assembly, upper conveyor, 3262  
Frame assembly, upper conveyor, 3270  
Frame assembly, lower conveyor, 3240  
Frame assembly, lower conveyor, 3262  
Frame assembly, lower conveyor, 3270  
Coupling half  
K
L
Shaft, drive  
38  
Impinger X2 – Analog Service Manual – Dom & Int’l  
Impinger X2 – Analog Service Manual – Dom & Int’l  
39  
40  
Impinger X2 – Analog Service Manual – Dom & Int’l  

IBM T 541 User Manual
Kenwood Computer Monitor DDX790 User Manual
LG Electronics LG Life Good Computer Monitor L1742P User Manual
Marshall electronic Marshall Electronics Computer Monitor M LYNX 10W User Manual
Mitsubishi Electronics CK 35308 User Manual
NEC MULTISYNC P1150 User Manual
Panasonic CT 36SF24 User Manual
Panasonic CT G2178X User Manual
Philips 21PT134B User Manual
Philips CD485 User Manual