ABB BSFC 02C User Manual

ABB industrial drives  
Hardware manual  
BSFC-02C charging controller  
Hardware manual  
BSFC-02C charging controller  
2017 ABB Oy. All Rights Reserved.  
3AXD50000027498 Rev A  
EN  
EFFECTIVE: 2017-04-10  
5
Table of contents  
 
Introduction to the manual 7  
1
Introduction to the manual  
Contents of this chapter  
This chapter gives the basic information on the manual.  
Compatibility  
The manual is compatible with the BSFC-02C charging controller.  
Safety instructions  
Follow all safety instructions delivered with the drive equipment.  
Read the complete safety instructions before you install, commission, or use the drive.  
The complete safety instructions are given in ACS880 multidrive cabinets and  
modules safety instructions [3AUA0000102301(English)].  
Note: The installation must always be designed and made according to applicable local  
laws and regulations. ABB does not assume any liability whatsoever for any installation  
that breaches the local laws and/or other regulations. Furthermore, if the  
recommendations given by ABB are not followed, the drive system may experience  
problems that the warranty does not cover.  
WARNING! Perform the electrical safety precautions before starting any work on  
the installation. Ignoring the precautions can cause physical injury or death, or  
damage to the equipment. Only a qualified electrician is allowed to work on the  
installation.  
       
8 Introduction to the manual  
1. Clearly identify the work location.  
2. Disconnect the circuit to be worked on completely. After disconnection, always wait for  
5 minutes to let the capacitors discharge.  
3. Secure against re-connection. Lock the disconnectors and attach warning notices.  
4. Provide protection against adjacent live parts.  
5. Verify by measuring that there is no voltage present.  
6. Carry out grounding and short-circuiting when necessary. Refer to local regulations  
and EN 50110-1:2004.  
Ask for a work permit. Only the nominated person in control of the electrical installation  
work is allowed to issue a work permit.  
Static electricity  
WARNING! Circuit boards contain components sensitive to electrostatic  
discharge (ESD). Wear a grounding wrist band when handling the boards. Do not  
touch the boards unnecessarily.  
Intended audience  
The manual is intended for cabinet designers, and installation, commissioning and  
maintenance personnel of ACS800 and ACS880LC multidrive modules.  
The reader is expected to know the standard electrical wiring practices, electronic  
components, and electrical schematic symbols.  
Contents of the manual  
This manual consists of the following chapters:  
Hardware description describes BSFC-02C unit.  
Installation guides in planning the installation of the BSFC-02C unit.  
Technical data contains technical specifications.  
Circuit diagrams contains connection diagrams.  
Dimension drawings contains the dimensional drawings of the BSFC-02C unit.  
Inquiries  
Address any inquiries about the product to the local ABB representative, quoting the type  
code and the serial number of the unit. If the local ABB representative cannot be  
contacted, address inquiries to the manufacturing facility.  
       
Hardware description 9  
2
Hardware description  
Contents of this chapter  
This chapter shows an overview of the BSFC unit and describes the connectors, settings  
and LEDs. In addition, it contains circuit diagram examples of the DC supply circuit of  
ACS880 frame R8i modules, and describes switch-on and switch-off sequences of the  
units.  
BSFC unit overview  
ACS880 frame size R8i inverter modules can be connected to the drive DC bus through a  
switch/disconnector (or switch fuse). This configuration requires a charging circuit to  
charge the DC capacitors of the modules in a controlled way. The DC voltage can be  
directly connected to the modules only after the capacitors are charged to a sufficient  
level. The BSFC is a unit that monitors the charging, and controls switch-on and switch-off  
of the DC voltage.  
In addition to inverter units, the BSFC can be used with other units consisting of R8i  
modules, such as brake or DC/DC converter units. One BFSC unit controls the charging of  
1...3 frame R8i modules.  
The BSFC unit can be snapped onto a standard mounting rail.  
       
10 Hardware description  
BSFC layout  
Symbol  
Description  
Layout  
X4  
X5  
Switch status monitoring (Q10 and Q11).  
Power supply input for BSFC and operating  
voltage output for switch/disconnector locking  
solenoid.  
1
2
3
4
5
6
L
N
PE  
V1…V6  
S1…S3  
Fiber optic links to Inverter 1, 2 and 3.  
X5  
IND. CONT. EQ.  
1PD8  
Enable switches for charging circuit monitoring  
(Inverter 1, 2 and 3).  
LSOL  
NSOL  
RATINGS  
Note: The BSFC do not allow the closing of the  
DC switch/disconnector unless monitoring is  
enabled for at least one inverter module.  
SUPPLY VOLTAGE (X5)  
230 V, 50/60Hz, 20 mA  
115 V, 50/60 Hz, 40 mA  
SOLENOID CONTROL  
OUTPUT (X5) 115/230 V  
AC, MAX 2A  
EXCITATION VOLTAGE  
OUTPUT (X4)  
STAT 1…3  
Inverter charging status LEDs (3 pcs).  
Inverter “ready for start” LEDs (3 pcs).  
BSFC power on LED.  
15 V DC, MAX 10mA  
OPER. TEMPERATURE  
MAX +85 °C  
U
1…3  
DC  
STAT  
PWR  
1
2
3
4
15V  
AUX2  
GND  
GND  
X4  
PWR  
DIS  
S1  
EN  
UDC  
STAT  
TO BE USED WITH  
ABB DRIVES ONLY.  
MAXIMUM RATED  
SYSTEM VOLTAGE  
UL: 600 V AC  
V1  
INV1  
IEC: 690 V AC  
V2  
DIS  
EN  
S2  
UDC  
STAT  
V3  
INV2  
V4  
DIS  
S3  
EN  
UDC  
STAT  
V5  
INV3  
V6  
 
Hardware description 11  
BSFC connectors  
Connector Signal  
Description  
X4  
Switch status monitoring (inverter switch/disconnector (Q11), and inverter charging  
switch (Q10)).  
1
+15 V  
AUX2  
GND  
GND  
Supply voltage for switch status monitoring circuit (Q10 and Q11). Max. 10 mA  
Digital input monitoring the switch status (Q10 and Q11).  
Ground for control electronics  
2
3
4
Ground for control electronics  
X5  
1
Power supply input & switch/disconnector locking solenoid control output  
External 230/115 V AC input  
L
2
N
Neutral  
3
PE  
Protective Earth  
4
NC  
LSOL  
NSOL  
Not connected  
5
230/115 V AC control voltage for switch Q11 locking solenoid  
Neutral for switch Q11 locking solenoid  
6
V1  
V2  
V3  
V4  
V5  
V6  
INV1 EN Optical transmitter (start enable to Inverter 1)  
Optical receiver (U > 80% acknowledgement from Inverter 1)  
U
1
DC  
DC  
INV2 EN Optical transmitter (start enable to Inverter 2)  
Optical receiver (U > 80% acknowledgement from Inverter 2)  
U
2
DC  
DC  
INV3 EN Optical transmitter (start enable to Inverter 3)  
Optical receiver (U > 80% acknowledgement from Inverter 3)  
U
3
DC  
DC  
BSFC LEDs  
Name  
Colour  
Indication  
Illuminates when  
INV1 STAT Yellow  
INV2 STAT Yellow  
INV3 STAT Yellow  
Charging of Inverter 1 is in  
progress, or Inverter 1 is  
not in use  
Switch Q11 main contacts are open (auxiliary  
contact connected to connector X4 is open).  
Charging of Inverter 2 is in  
progress, or Inverter 2 is  
not in use  
See INV1 STAT.  
See INV1 STAT.  
Charging of Inverter 3 is in  
progress, or Inverter 3 is  
not in use  
INV1 U  
Green  
Inverter 1 ready to start  
Signal U 1 indicates that DC voltage of  
DC  
DC  
Inverter 1 capacitor bank is above 80% of the  
nominal.  
INV2 U  
INV3 U  
PWR  
Green  
Green  
Green  
Inverter 2 ready to start  
Inverter 3 ready to start  
BSFC power on  
See U 1.  
DC  
DC  
DC  
See U 1.  
DC  
Voltage for internal logic (5 V) is present.  
   
12 Hardware description  
Connections of the DC supply circuit  
DC bus  
-A11.1  
BSFC-XX  
SWITCH FUSE CONTROLLER  
-Q11.1  
-Q10.1  
X1:1  
IR+  
X1:2  
X1:3  
IR-  
DIS  
X2:1  
X2:2  
X2:3  
S1  
S2  
S3  
-K11.1  
A2  
IR2+  
IR2-  
IR3+  
IR3-  
EN  
A1  
DIS  
EN  
X3:1  
X3:2  
X3:3  
DIS  
EN  
X4:1  
X4:2  
X4:3  
X4:4  
15V  
AUX2  
GND  
GND  
=-DOOR  
-P11.1  
X5:1  
X5:2  
X5:3  
X5:4  
X5:5  
X5:6  
L
N
L
230V AC; 115V AC  
N
PE  
GREEN  
Chg OK  
LSOL  
NSOL  
;I1V60  
;I1V50  
V1  
V2  
STAT  
UDC  
INV 1  
R8i module 1  
V3  
V4  
STAT  
UDC  
INV 2  
INV 3  
V5  
V6  
STAT  
UDC  
DC supply  
to R8i module  
No. Description  
1
2
3
4
5
6
7
8
Drive DC bus  
Main DC switch disconnecter  
Charging switch fuse  
Charging resistors  
Solenoid that locks the manual operation mechanism  
Indicator lamp on the cabinet door  
BSFC unit  
R8i module DC input connection  
 
Hardware description 13  
Inverter power switch-on sequence  
The terms and designations used in the table below refer to the diagram in section  
Operation  
What happens  
1.  
User turns charging  
circuit switch Q10 to 1  
(ON) position.  
Charging of inverter capacitors starts through the charging resistors [R10].  
Auxiliary contact 1-2 of Q10 opens. BSFC prevents starting of inverter and  
closing of switch/disconnector Q11.  
“INV1 STAT” and “PWR” LEDs are on.  
2.  
3.  
Inverter capacitor bank  
charges.  
BSFC monitors inverter U signal through fiber optic link(s) INV1…INV3.  
DC  
“INV STAT” and “PWR” LEDs are on.  
BSFC unit detects that  
the charging is  
BSFC connects operating voltage to solenoid of switch/disconnector Q11.  
Solenoid releases the locking mechanism enabling operation of the  
handle.  
completed: U  
DC  
signal(s) are received  
from inverters  
“INV UDC” and “PWR” LEDs are on. The “charging OK” light on the  
cabinet door illuminates indicating that capacitor charging is complete and  
operation of the switch/disconnector Q11 is allowed.  
(U > 80%  
DC  
acknowledgement from  
Inverter(s)).  
4.  
5.  
User turns  
switch/disconnector  
Q11 to 1 (on) position.  
Main contacts 1-2…7-8 of switch Q11 connect inverter(s) to DC power  
supply.  
Auxiliary contact 13-14 of switch Q11 closes.  
Auxiliary contact 21-22 of switch Q11 opens, de-energizing the solenoid  
and the “charging OK” LED on the cabinet door.  
“INV UDC” and “PWR” LEDs are on.  
User turns switch Q10  
to 0 (off) position.  
BSFC receives “main switch ON, charging switch OFF” indication through  
terminal AUX2.  
BSFC sends an enable signal to inverter through the fiber optic link.  
“INV UDC” and “PWR” LEDs on.  
Miscellaneous  
Details of the locking solenoid control  
The closing of the DC switch/disconnector is enabled by locking solenoid when:  
DC voltage of all inverter modules monitored by the BSFC unit exceed 80% of the  
nominal value. (BSFC receives UDC signals from inverters).  
Switch/disconnector handle is in 0 (off) position.  
     
14 Hardware description  
Inverter power switch-off sequence  
The terms and designations used in the table below refer to section Connections of the DC  
Operation  
What happens  
1.  
2.  
User stops the inverters.  
(Do not open the  
switch/disconnector while  
the inverters are loaded).  
User turns switch Q11  
Switch Q11 disconnects inverter(s) from the DC power supply.  
handle to 0 (off) position.  
Contact 13-14 of Q11 switches off the AUX2 signal on the BSFC unit.  
BSFC switches INV1 EN signal off disabling inverter start.  
Auxiliary contact 21-22 closes energizing the solenoid of switch Q11.  
Solenoid releases the locking mechanism of switch Q11. Normal  
operation (on/off) of the handle is possible as long as inverter DC  
voltage remains high.  
“INV UDC” and “PWR” LEDs. LED “Charging OK” light on the cabinet  
door illuminates.  
3.  
Inverter capacitor bank  
discharges.  
Inverter DC voltage decreases to zero gradually. When below 80% of  
nominal:  
• Inverters switch off U signals from BSFC unit.  
DC  
• BSFC switches off the operating voltage to solenoid of switch Q11.  
Locking mechanism activates preventing operation of switch into on  
position.  
“INV UDC” and “PWR” LEDs are on.  
 
Installation 15  
3
Installation  
Contents of this chapter  
This chapter instructs how to install the BSFC unit into a user-defined cabinet.  
Planning the installation of the BSFC unit  
Placing  
Install the BSFC unit in a heated indoor environment. Ensure the temperature meets the  
requirement given in chapter Technical data. Also ensure that the ambient conditions meet  
the requirements of the hardware manual of the inverter modules.  
Do not install the BSFC unit far from the inverters. The fiber optic cable(s) between the unit  
and inverter(s) must not exceed four meters in length.  
WARNING! No condensation is allowed. There are connectors that are connected  
to drive main circuit potential.  
Wire selection  
See chapter Circuit diagrams on page 19.  
           
16 Installation  
Protecting against contact  
WARNING! Protect the BSFC unit against accidental contact. There are  
connectors that are connected to drive main circuit potential.  
List of components needed in power supply circuit  
Component  
Acquire…  
Switch/disconnector kit(DC  
switch/disconnector, BSFC  
unit, charging switch,  
…from ABB.  
charging resistors)  
DC fuses for inverter  
Charging circuit fuses  
…from ABB or according to the ABB specification.  
…from ABB or according to the ABB specification.  
…from ABB or according to the ABB specification.  
Pair of fibre optic cables for  
BSFC – inverter connection  
Main DC supply  
cables/busbars  
… according to the ABB specification.  
Charging circuit cables,  
BSFC power supply  
cables,switch/disconnector  
control cables  
… from any source according to the ABB specification.  
Charging circuit wire specification, see chapter Circuit diagrams on page 19.  
Always use the cables recommended by ABB or equivalent. The cables are  
connected to drive main circuit.  
Mounting and removing the BSFC unit  
1. Mount the unit by snapping the feet onto a 35 mm EN50022 mounting rail (1a).  
2. Remove the unit by bending the feet outwards lightly (2) and lifting the unit  
simultaneously (3).  
Mounting  
Removing  
1b  
3
2
1a  
2
Wiring the BSFC unit  
Connect the wiring according to the diagrams in chapter Circuit diagrams on page 19.  
       
Technical data 17  
4
Technical data  
Contents of this chapter  
This chapter contains the technical specifications of the BSFC unit.  
Power supply input  
(X5)  
Operating voltage 115…230 V AC +10/%, 50/60 Hz  
Current consumption 40/80 mA typical (230/115 V AC)  
Protection by Microfuse 2 A, slow  
6-position detachable screw terminal block (FCI OQ0601500000G), wire size max.  
2
2.5 mm .  
Solenoid control  
output (X5)  
Control voltage 115 or 230 V AC, +10/-15%  
Control current max. 2 A for 3.5 s or max. 4 A for 20 ms  
Protection by Microfuse 2 A, slow (common with power supply input)  
2
6-position detachable screw terminal block, wire size max. 2.5 mm  
Switch feedback input Voltage output 15 V DC max. 10 mA  
(X4)  
4-position detachable screw terminal block (FCI OQ0471500000G), wire size max.  
2.5 mm  
2
Optical links (V1…V6) Avago Versatile Link series 5 MBd optical transmitters & receivers  
Max. optical cable (POF) length 5 m  
     
18 Technical data  
Standards applied  
Safety requirements: EN 50178 Electronic equipment for use in power installations  
IEC 61800-5-1 Semiconductor power converters for adjustable frequency drive  
systems  
UL 508 C Industrial Control Equipment  
EMC emission: EN/IEC 6100-6-4:2007 Emission standard for industrial  
environments  
EMC immunity: EN/IEC 61000-6-2:2005 Immunity for industrial environments  
Operating temperature Free air circulation: +0...+50 °C (+32 ... +122 °F)  
Forced convection cooling: Max. +70 °C, min. air flow 2 m/s  
Dimensions  
(L × W × D)  
247 × 79 × 66.5 mm (9.72” x 3.11” x 2.62”)  
Mounting  
On 35 mm mounting rail EN 50022, vertical or horizontal  
UL approved (UL Listed according to UL 508 C)  
Conformal coating as standard  
Other features  
Optical components  
Handle fiber optic cables with care. When unplugging optic cables, always grab the  
connector, not the cable itself. Do not touch the ends of the fibers with bare hands as the  
fiber is extremely sensitive to dirt. The specifications of the optic cable are as follows:  
Storage temperature: -55...+85 °C (-67…+185 °F)  
Installation temperature: -20...+70 °C (-4…+158 °F)  
Maximum short-term tensile force: 50 N (11.2 lbf)  
Minimum short-term bend radius: 25 mm (1.0”)  
Minimum long-term bend radius: 35 mm (1.4”)  
Maximum long-term tensile load: 1 N (3.6 ozf)  
Flexing: Max. 1000 cycles  
ABB drive products in general utilize 5 and 10 MBd (megabaud) optical components from  
Avago Technologies’ Versatile Link range. Please note that the optical component type is  
not directly related to the actual communication speed.  
Note: The optical components (transmitter and receiver) on a fiber optic link must be of the  
same type.  
Plastic optical fiber (POF) cables can be used with both 5 MBd and 10 MBd optical  
components. 10 MBd components also enable the use of Hard Clad Silica (HCS®) cables,  
which allow longer connection distances thanks to their lower attenuation. HCS® cables  
cannot be used with 5 MBd optical components.  
 
Circuit diagrams 19  
5
Circuit diagrams  
Contents of this chapter  
This chapter shows the connections between the switch/disconnector, the charging  
controller and one or two inverters. The BSFC unit is supplied from 115...230 V AC power  
source.  
     
20 Circuit diagrams  
Charging circuit 1xR8i  
4 1  
3 3  
4 2  
3 4  
2 1  
2 2  
6 : 3 1 ; X  
5 : 3 1 ; X  
4 : 3 1 ; X  
3 : 3 1 ; X  
2 K  
2 K  
1 3  
1 4  
4
3
1
1
2
D C U - + =  
D C U - + =  
2
1
2
D C U - - =  
D C U - - =  
=-R1.1  
2
1
1
3
3
=-R2.1  
2
=-R3.1  
2
1
1
3
3
=-R4.1  
2
2 H  
3 D  
1 : 1 1 0 Q ; .  
2 : 1 1 0 Q ; .  
1
2
7
5
3
1
8
6
4
2
X 1  
X 2  
6 : 3 1 ; X  
5 : 3 1 ; X  
4 : 3 1 ; X  
3 : 3 1 ; X  
E
E
1 5  
7 D  
: 1 . 1 0 1 Q ;  
1 4  
E P 1 .  
1
= -  
E
1 P  
 
Circuit diagrams 21  
Charging circuit 2xR8i  
4 1  
3 3  
4 2  
3 4  
2 1  
2 2  
6 : 3 1 ; X  
5 : 3 1 ; X  
4 : 3 1 ; X  
3 : 3 1 ; X  
2 K  
2 K  
2
D C U - + =  
2
D C U - - =  
1 3  
1 4  
8
7
5
3
1
1
D C U - + =  
6
4
2
1
D C U - - =  
=-R1.1  
2
1
1
1
3
3
3
=-R2.1  
2
=-R3.1  
2
=-R4.1  
2
1
1
1
3
3
3
=-R5.1  
2
=-R6.1  
2
2 H  
3 D  
1 : 1 1 0 Q ; .  
2 : 1 1 0 Q ; .  
1
2
7
5
3
1
8
6
4
2
X 1  
X 2  
6 : 3 1 ; X  
5 : 3 1 ; X  
4 : 3 1 ; X  
3 : 3 1 ; X  
E
E
1 5  
7 D  
: 1 . 1 0 1 Q ;  
1 5  
E P 1 .  
1
= -  
E
1 P  
 
22 Circuit diagrams  
Dimension drawings 23  
6
Dimension drawings  
Contents of this chapter  
This chapter contains dimension drawings of BSFC-02C charging controller.  
     
24 Dimension drawings  
BSFC-02C  
1
2
3
L
N
PE  
X5  
4
IND. CONT. EQ.  
1PD8  
5
6
LSOL  
NSOL  
RATINGS  
SUPPLY VOLTAGE (X5)  
230 V, 50/60Hz, 20 mA  
115 V, 50/60 Hz, 40 mA  
SOLENOID CONTROL  
OUTPUT (X5) 115/230 V  
AC, MAX 2A  
EXCITATION VOLTAGE  
OUTPUT (X4)  
15 V DC, MAX 10mA  
OPER. TEMPERATURE  
MAX +85 °C  
STAT  
1
2
15V  
AUX2  
GND  
GND  
X4  
3
PWR  
DIS  
4
S1  
EN  
UDC  
STAT  
TO BE USED WITH  
ABB DRIVES ONLY.  
MAXIMUM RATED  
SYSTEM VOLTAGE  
UL: 600 V AC  
V1  
INV1  
IEC: 690 V AC  
V2  
DIS  
EN  
S2  
UDC  
STAT  
V3  
INV2  
V4  
DIS  
S3  
EN  
UDC  
STAT  
V5  
INV3  
V6  
 
Further information  
Product and service inquiries  
Address any inquiries about the product to your local ABB representative, quoting the type  
designation and serial number of the unit in question. A listing of ABB sales, support and  
service contacts can be found by navigating to www.abb.com/searchchannels.  
Product training  
For information on ABB product training, navigate to new.abb.com/service/training.  
Providing feedback on ABB Drives manuals  
Your comments on our manuals are welcome. Navigate to  
Document library on the Internet  
You can find manuals and other product documents in PDF format on the Internet at  
           
Contact us  
3AXD50000027498 Rev A (EN) 2017-04-10  

Maxtor 1925 User Manual
Kompernass KH 2233 User Manual
Kenwood KDC 3029 User Manual
JVC KD G420 User Manual
Hitachi Travelstar HTS725040A9A364 User Manual
GE ZET1 User Manual
Clarion CD Player BD329R User Manual
Brinkmann 844 0350 S User Manual
Black Box Computer Accessories KV1408A User Manual
Adobe ADBCD17648MC User Manual