ABB ACS880 User Manual

ABB industrial drives  
Firmware manual  
ACS880 primary control program  
Firmware manual  
ACS880 primary control program  
2012 ABB Oy. All Rights Reserved.  
3AUA0000085967 Rev C  
EN  
EFFECTIVE: 2012-04-01  
Table of contents 5  
Table of contents  
 
6 Table of contents  
Table of contents 7  
01 Actual values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76  
03 Input references . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77  
04 Warnings and faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77  
05 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78  
06 Control and status words . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79  
07 System info . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82  
10 Standard DI, RO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83  
11 Standard DIO, FI, FO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88  
12 Standard AI . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93  
13 Standard AO . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95  
19 Operation mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99  
20 Start/stop/direction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100  
21 Start/stop mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108  
22 Speed reference selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113  
23 Speed reference ramp . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119  
24 Speed reference conditioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123  
25 Speed control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126  
26 Torque reference chain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131  
28 Frequency reference chain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135  
30 Limits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 143  
31 Fault functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 145  
32 Supervision . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 150  
33 Maintenance timer & counter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 153  
35 Motor thermal protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 159  
36 Load analyzer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166  
40 Process PID set 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 169  
41 Process PID set 2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 180  
43 Brake chopper . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 181  
44 Mechanical brake control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 183  
45 Energy efficiency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 187  
46 Monitoring/scaling settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 189  
47 Data storage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191  
49 Panel port communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193  
50 Fieldbus adapter (FBA) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 193  
51 FBA A settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197  
52 FBA A data in . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198  
53 FBA A data out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199  
90 Feedback selection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199  
91 Encoder module settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 204  
92 Encoder 1 configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 206  
93 Encoder 2 configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 211  
95 HW configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 213  
96 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 215  
97 Motor control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216  
98 User motor parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 218  
8 Table of contents  
99 Motor data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 220  
10 Table of contents  
Introduction to the manual 11  
1
Introduction to the manual  
What this chapter contains  
This chapter describes the contents of the manual. It also contains information on the  
compatibility, safety and intended audience.  
Applicability  
This manual applies to the ACS880 primary control program (version 1.10 or later).  
The firmware version of the control program is visible in parameter 07.05 Firmware  
Safety instructions  
Follow all safety instructions delivered with the drive.  
• Read the complete safety instructions before you install, commission, or use  
the drive. The complete safety instructions are delivered with the drive as either  
part of the Hardware manual, or, in the case of ACS880 multidrives, as a separate  
document.  
• Read the firmware function-specific warnings and notes before changing  
parameter values. These warnings and notes are included in the parameter  
descriptions presented in chapter Parameters.  
Target audience  
This manual is intended for people who design, commission, or operate the drive  
system.  
         
12 Introduction to the manual  
Contents of the manual  
This manual consists of the following chapters:  
Using the control panel provides the basic instructions for use of the control panel.  
Control locations and operating modes describes the control locations and  
operating modes of the drive.  
Program features contains descriptions of the features of the ACS880 primary  
control program.  
Application macros contains a short description of each macro together with a  
connection diagram.  
Parameters describes the parameters of the drive.  
Additional parameter data contains further information on the parameters.  
Fault tracing lists the warning and fault messages with possible causes and  
remedies.  
communication to and from a fieldbus network using the embedded fieldbus  
interface of the drive.  
Fieldbus control through a fieldbus adapter describes the communication to and  
from a fieldbus network using an optional fieldbus adapter module.  
Drive-to-drive link describes the communication between drives connected  
together by the drive-to-drive (D2D) link.  
Related documents  
Note: A quick start-up sequence for a speed control application is provided by  
ACS880 drives with primary control program, Quick start-up guide  
(3AUA0000098062), delivered with the drive.  
A list of related manuals is printed on the inside of the front cover.  
Terms and abbreviations  
Term/abbreviation  
Definition  
ACS-AP-I  
AI  
Type of control panel used with ACS880 drives  
Analog input; interface for analog input signals  
Analog output; interface for analog output signals  
Type of control unit used in ACS880 drives.  
DC circuit between rectifier and inverter  
AO  
BCU  
DC link  
DDCS  
Distributed drives communication system; a protocol used in  
optical fiber communication  
     
Introduction to the manual 13  
Term/abbreviation  
Definition  
DI  
Digital input; interface for digital input signals  
DIO  
Digital input/output; interface that can be used as a digital input  
or output  
DO  
Digital output; interface for digital output signals  
Direct torque control  
DTC  
EFB  
Embedded fieldbus  
FBA  
Fieldbus adapter  
FEN-01  
FEN-11  
FEN-21  
FEN-31  
FIO-01  
FIO-11  
FCAN-0x  
FDNA-0x  
FECA-01  
FENA-11  
FLON-0x  
FPBA-0x  
FSCA-0x  
HTL  
Optional TTL encoder interface module  
Optional absolute encoder interface module  
Optional resolver interface module  
Optional HTL encoder interface module  
Optional digital I/O extension module  
Optional analog I/O extension module  
Optional CANopen adapter  
Optional DeviceNet adapter  
Optional EtherCAT® adapter  
Optional Ethernet/IP adapter  
®
Optional LONWORKS adapter  
Optional PROFIBUS DP adapter  
Optional Modbus adapter  
High-threshold logic  
IGBT  
Insulated gate bipolar transistor; a voltage-controlled  
semiconductor type widely used in inverters due to their easy  
controllability and high switching frequency  
I/O  
Input/Output  
ID run  
Motor identification run. During the identification run, the drive  
will identify the characteristics of the motor for optimum motor  
control.  
LSB  
Least significant bit  
Least significant word  
Most significant bit  
Most significant word  
LSW  
MSB  
MSW  
14 Introduction to the manual  
Term/abbreviation  
Definition  
Network control  
With fieldbus protocols based on the Common Industrial  
Protocol (CIPTM), such as DeviceNet and Ethernet/IP, denotes  
the control of the drive using the Net Ctrl and Net Ref objects of  
the ODVA AC/DC Drive Profile. For more information, see  
www.odva.org, and the following manuals:  
• FDNA-01 DeviceNet adapter module User’s manual  
(3AFE68573360 [English]), and  
FENA-01/-11 Ethernet adapter module User’s manual  
(3AUA0000093568 [English]).  
Parameter  
User-adjustable operation instruction to the drive, or signal  
measured or calculated by the drive  
PID controller  
Proportional–integral–derivative controller. Drive speed control  
is based on PID algorithm.  
PLC  
Programmable logic controller  
Power unit  
Contains the power electronics and connections of the drive.  
The drive control unit is connected to the power unit.  
PTC  
RFG  
RO  
Positive temperature coefficient  
Ramp function generator.  
Relay output; interface for a digital output signal. Implemented  
with a relay.  
SSI  
Synchronous serial interface  
Safe torque off  
STO  
TTL  
UPS  
Transistor-transistor logic  
Uninterruptible power supply; power supply equipment with  
battery to maintain output voltage during power failure  
ZCON  
ZCU  
Type of control board used in ACS880 drives. The board is  
either integrated into the drive or fitted in a plastic housing (see  
Type of control unit used in ACS880 drives that consists of a  
ZCON board built into a plastic housing.  
The control unit may be fitted onto the drive/inverter module, or  
installed separately.  
   
Using the control panel 15  
2
Using the control panel  
Refer to ACS-AP-I and ACS-AP-S assistant control panels user’s manual  
(3AUA0000085685 [English]).  
   
16 Using the control panel  
Control locations and operating modes 17  
3
Control locations and  
operating modes  
What this chapter contains  
This chapter describes the control locations and operating modes supported by the  
control program.  
     
18 Control locations and operating modes  
Local control vs. external control  
The ACS880 has two main control locations: external and local. The control location  
is selected with the Loc/Rem key on the control panel or in the PC tool.  
ACS880  
External control  
2)  
I/O 1)  
PLC  
(= Programmable  
logic controller)  
Local control  
Drive-to-drive (D2D)  
link or Embedded  
fieldbus interface  
Fieldbus adapter or DDCS  
communication module  
Fxxx  
Control panel or Drive composer  
PC tool (optional)  
M
3~  
Encoder  
1) Extra inputs/outputs can be added by installing optional I/O extension modules (FIO-xx) in  
drive slots.  
2) Encoder or resolver interface module(s) (FEN-xx) installed in drive slots.  
Local control  
The control commands are given from the control panel keypad or from a PC  
equipped with Drive composer when the drive is in local control. Speed and torque  
control modes are available for local control; frequency mode is available when scalar  
motor control mode is used (see parameter 19.16 Local control mode).  
Local control is mainly used during commissioning and maintenance. The control  
panel always overrides the external control signal sources when used in local control.  
Changing the control location to local can be prevented by parameter 19.17 Local  
The user can select by a parameter (49.05 Communication loss action) how the drive  
reacts to a control panel or PC tool communication break. (The parameter has no  
effect in external control.)  
     
Control locations and operating modes 19  
External control  
When the drive is in external control, control commands are given through the  
fieldbus interface (via or an optional fieldbus adapter module), the I/O terminals  
(digital and analog inputs), or optional I/O extension modules.  
Two external control locations, EXT1 and EXT2, are available. The user can select  
the sources of the start and stop commands separately for each location by  
parameters 20.0120.10. The operating mode can be selected separately for each  
location, which enables quick switching between different operating modes, for  
example speed and torque control. Selection between EXT1 and EXT2 is done via  
any binary source such as a digital input or fieldbus control word (see parameter  
19.11 Ext1/Ext2 selection). The source of reference is selectable for each operating  
mode separately.  
 
20 Control locations and operating modes  
Operating modes of the drive  
The drive can operate in several operating modes with different types of reference.  
The mode is selectable for each control location (Local, EXT1 and EXT2) in  
parameter group 19 Operation mode.  
The following is a general representation of the reference types and control chains.  
The page numbers refer to detailed diagrams in chapter Control chain diagrams.  
Speed  
reference  
source selection  
I
Speed reference  
source selection  
II  
Speed reference  
ramping and  
shaping  
Speed error  
calculation  
(page 292)  
Motor feedback  
configuration  
(page 291)  
(page 289)  
(page 290)  
(page 288)  
Torque  
reference  
Speed controller  
(page 293)  
source selection  
and modification  
(page 294)  
Reference  
selection for  
torque controller  
(page 295)  
Process PID  
setpoint and  
feedback source  
selection  
(page 300)  
Torque  
controller  
Reference  
modification for  
torque controller  
(page 296)  
Process PID  
controller  
DTC motor  
control mode  
(page 301)  
Scalar motor  
control mode  
Frequency  
reference  
source selection  
and modification  
(page 298)  
Speed control mode  
The motor follows a speed reference given to the drive. This mode can be used either  
with estimated speed used as feedback, or with an encoder or resolver for better  
speed control accuracy.  
     
Control locations and operating modes 21  
Speed control mode is available in both local and external control. It is also available  
both in DTC (Direct Torque Control) and scalar motor control modes.  
Torque control mode  
Motor torque follows a torque reference given to the drive. This mode can be used  
either with or without an encoder or resolver. When used with an encoder or resolver,  
this mode provides for more accurate and dynamic motor control.  
Torque control mode is available in both local and external control.  
Frequency control mode  
The motor follows a frequency reference given to the drive. Frequency control is only  
available for scalar motor control.  
Special control modes  
In addition to the above-mentioned control modes, the following special control  
modes are available:  
• Process PID control. For more information, see section Process PID control (page  
• Emergency stop modes OFF1 and OFF3: Drive stops along the defined  
deceleration ramp and drive modulation stops.  
• Jogging mode: Drive starts and accelerates to the defined speed when the  
jogging signal is activated. For more information, see section Jogging (page 31).  
     
22 Control locations and operating modes  
Program features 23  
4
Program features  
What this chapter contains  
This chapter describes the features of the control program.  
     
24 Program features  
Drive configuration and programming  
The drive control program is divided into two parts:  
• firmware program  
• application program.  
Drive control program  
Firmware  
Application program  
Speed control  
Torque control  
Frequency control  
Drive logic  
I/O interface  
Fieldbus interface  
Protections  
Function block  
program  
Parameter  
interface  
E
M
Standard  
block library  
Feedback  
The firmware program performs the main control functions, including speed and  
torque control, drive logic (start/stop), I/O, feedback, communication and protection  
functions. Firmware functions are configured and programmed with parameters.  
Programming via parameters  
Parameters can be set via  
• the control panel, as described in chapter Using the control panel  
• the Drive composer PC tool, as described in Drive composer user’s manual  
(3AUA0000094606 [English]), or  
• the fieldbus interface, as described in chapters Fieldbus control through the  
All parameter settings are stored automatically to the permanent memory of the drive.  
However, if an external +24 V DC power supply is used for the drive control unit, it is  
highly recommended to force a save by using parameter 96.07 Parameter save  
before powering down the control unit after any parameter changes.  
If necessary, the default parameter values can be restored by parameter 96.06  
Application programming  
The functions of the firmware program can be extended with application  
programming. (A standard drive delivery does not include an application program.)  
     
Program features 25  
Application programs can be built out of function blocks based on the IEC-61131  
standard.  
26 Program features  
Control interfaces  
Programmable analog inputs  
The drive control unit has two programmable analog inputs. Each of the inputs can be  
independently set as a voltage (0/2…10 V or -10…10 V) or current (0/4…20 mA)  
input by a jumper on the drive control unit. Each input can be filtered, inverted and  
scaled. The number of analog inputs can be increased by using FIO-xx I/O  
extensions.  
Settings  
Parameter group 12 Standard AI (page 93).  
Programmable analog outputs  
The drive control unit has two current (0…20 mA) analog outputs. Each output can be  
filtered, inverted and scaled. The number of analog outputs can be increased by  
using FIO-xx I/O extensions.  
Settings  
Parameter group 13 Standard AO (page 95).  
Programmable digital inputs and outputs  
The drive has six digital inputs, a digital start interlock input, and two digital  
input/outputs.  
One digital input (DI6) doubles as a PTC thermistor input. See section Motor thermal  
Digital input/output DIO1 can be used as a frequency input, DIO2 as a frequency  
output.  
The number of digital inputs/outputs can be increased by using FIO-xx I/O  
extensions.  
Settings  
Parameter groups 10 Standard DI, RO (page 83) and 11 Standard DIO, FI, FO (page  
Programmable relay outputs  
The drive control unit has three relay outputs. The signal to be indicated by the  
outputs can be selected by parameters.  
Relay outputs can be added by using FIO-0x I/O extensions.  
         
Program features 27  
Settings  
Parameter group 10 Standard DI, RO (page 83).  
Programmable I/O extensions  
The number of inputs and outputs can be increased by using FIO-xx I/O extensions.  
The I/O configuration parameters (parameter groups 10…13) include the maximum  
number of DI, DIO, AI, AO and RO that can be in use with different FIO-xx  
combinations.  
The table below shows the possible I/O combinations:  
Digital  
inputs  
(DI)  
Digital I/Os  
Analog  
inputs  
(AI)  
Analog  
outputs  
(AO)  
Relay  
outputs  
(RO)  
Location  
(DIO)  
Drive control unit  
FIO-01  
7
-
2
4
2
2
-
2
-
3
2
-
FIO-11  
-
3
1
For example, with an FIO-01 and an FIO-11 connected to the drive, parameters  
controlling DI1…7, DIO1…8, AI1…5, AO1…3 and RO1…5 are in use.  
Settings  
Fieldbus control  
The drive can be connected to several different automation systems through its  
fieldbus interfaces. See chapter Fieldbus control through a fieldbus adapter (page  
Settings  
   
28 Program features  
Motor control  
Direct torque control (DTC)  
The motor control of the ACS880 is based on direct torque control (DTC). The  
switching of the output semiconductors is controlled to achieve the required stator  
flux and motor torque. The switching frequency is changed only if the actual torque  
and stator flux values differ from their reference values by more than the allowed  
hysteresis. The reference value for the torque controller comes from the speed  
controller or directly from an external torque reference source.  
Motor control requires measurement of the DC voltage and two motor phase  
currents. Stator flux is calculated by integrating the motor voltage in vector space.  
Motor torque is calculated as a cross product of the stator flux and the rotor current.  
By utilizing the identified motor model, the stator flux estimate is improved. Actual  
motor shaft speed is not needed for the motor control.  
The main difference between traditional control and DTC is that torque control has  
the same time level as the power switch control. There is no separate voltage and  
frequency controlled PWM modulator; the output stage switching is wholly based on  
the electromagnetic state of the motor.  
The best motor control accuracy is achieved by activating a separate motor  
identification run (ID run).  
See also section Scalar motor control (page 33).  
Settings  
(page 222).  
Reference ramping  
Acceleration and deceleration ramping times can be set individually for speed, torque  
and frequency reference.  
With a speed or frequency reference, the ramps are defined as the time it takes for  
the drive to accelerate or decelerate between zero speed or frequency and the value  
defined by parameter 46.01 Speed scaling or 46.02 Frequency scaling. The user can  
switch between two preset ramp sets using a binary source such as a digital input.  
For speed reference, also the shape of the ramp can be controlled.  
With a torque reference, the ramps are defined as the time it takes for the reference  
to change between zero and nominal motor torque (parameter 01.30 Nominal torque  
scale).  
       
Program features 29  
Special acceleration/deceleration ramps  
The acceleration/deceleration times for the jogging function can be defined  
separately; see section Jogging (page 31). Furthermore, a deceleration ramp can be  
defined for emergency stop (“Off3” mode).  
Settings  
• Speed reference ramping: Parameters 23.1123.19 and 46.01  
(pages 119 and 189).  
Torque reference ramping: Parameters 01.30, 26.18 and 26.19  
(pages 77 and 133).  
• Frequency reference ramping: Parameters 28.7128.75 and 46.02  
(pages 139 and 189).  
• Jogging: Parameters 23.20 and 23.21 (page 122).  
• Emergency stop (“Off3” mode): Parameter 23.23 Emergency stop time  
(page 122).  
Constant speeds (frequencies)  
It is possible to predefine up to 7 constant speeds. Constant speeds can be activated,  
for example, through digital inputs. Constant speeds override the normal speed  
reference.  
For frequency control, seven constant frequencies can be defined in the same way.  
Settings  
Critical speeds (frequencies)  
A critical speeds function is available for applications where it is necessary to avoid  
certain motor speeds or speed ranges because of, for example, mechanical  
resonance problems.  
A similar function is available for scalar motor control with a frequency reference.  
     
30 Program features  
Example  
A fan has vibrations in the range of 540 to 690 rpm and 1380 to 1560 rpm. To make  
the drive jump over these speed ranges,  
• enable the critical speeds function by turning on bit 0 of parameter 22.51 Critical  
• set the critical speed ranges as in the figure below.  
Motor speed  
(rpm)  
1
2
3
4
Par. 22.52 = 540 rpm  
Par. 22.53 = 690 rpm  
Par. 22.54 = 1380 rpm  
Par. 22.55 = 1560 rpm  
1560  
1380  
690  
540  
Speed reference  
(rpm)  
1
2
3
4
Settings  
Encoder support  
The program supports two single-turn or multiturn encoders (or resolvers). The  
following optional interface modules are available:  
• Absolute encoder interface FEN-11: absolute encoder input, TTL input, TTL  
output (for encoder emulation and echo) and two digital inputs for position latching  
• Resolver interface FEN-21: resolver input, TTL input, TTL output (for encoder  
emulation echo) and two digital inputs for position latching  
• HTL encoder interface FEN-31: HTL encoder input, TTL output (for encoder  
emulation and echo) and two digital inputs for position latching.  
The interface module is installed onto any option slot on the drive control unit, or onto  
an FEA-xx extension adapter.  
Quick configuration of HTL encoder feedback  
1. Specify the type of the encoder interface module (parameter 91.11 Module 1 type  
= FEN-31) and the slot the module is installed into (91.12 Module 1 location).  
2. Specify the type of the encoder (92.01 Encoder 1 type = HTL). The parameter  
listing will be re-read from the drive after the value is changed.  
   
Program features 31  
3. Specify the interface module the encoder is connected to (92.02 Encoder 1  
4. Set the number of pulses according to encoder nameplate  
5. If the encoder rotates at a different speed to the motor (ie. is not mounted directly  
on the motor shaft), enter the gear ratio in 90.43 Motor gear numerator and  
6. Set parameter 91.10 Encoder parameter refresh to Configure to apply the new  
parameter settings. The parameter will automatically revert to Done.  
7. Check that 91.02 Module 1 status and 92.03 Encoder 1 type act are showing the  
correct interface module and encoder types (HTL and FEN-31 respectively). Also  
check the status of the FEN-31 module; both LEDs should be glowing green.  
8. Start the motor with a reference of eg. 400 rpm.  
9. Compare the estimated speed (01.02 Motor speed estimated) with the measured  
speed (01.04 Encoder 1 speed filtered). If the values are the same, set the  
encoder as the feedback source (90.41 Motor feedback selection = Encoder 1).  
10. Specify the action taken in case the feedback signal is lost (90.45 Motor feedback  
Settings  
(page 211).  
Jogging  
Two jogging functions (1 or 2) are available. When a jogging function is activated, the  
drive starts and accelerates to the defined jogging speed (parameter 22.42 Jogging 1  
ref or 22.43 Jogging 2 ref) along the defined jogging acceleration ramp (23.20 Acc  
time jogging). When the function is deactivated (Jogging 1/2 start = 0), the drive  
decelerates to a stop along the defined jogging deceleration ramp (23.21 Dec time  
jogging). One push button can be used to start and stop the drive during jogging. The  
jogging function is typically used during servicing or commissioning to control the  
machinery locally.  
Jogging functions 1 and 2 are activated by a parameter or through fieldbus. For  
activation through fieldbus, see parameter 06.01 Main control word.  
The figure and table below describe the operation of the drive during jogging. (Note  
that they cannot be directly applied to jogging commands through fieldbus as those  
require no enable signal; see parameter 20.25 Jogging enable.) They also represent  
how the drive shifts to normal operation (= jogging inactive) when the drive start  
command is switched on. Jog cmd = State of the jogging input (20.26 Jogging 1 start  
   
32 Program features  
or 20.27 Jogging 2 start); Jog enable = State of the source set by 20.25 Jogging  
enable; Start cmd = State of the drive start command.  
Speed  
Time  
1
2
3
4
5
6
7
8
9
10 11  
12 13 14 15 16  
Jog  
Jog  
Start  
Phase  
Description  
cmd enable cmd  
1-2  
1
1
0
Drive accelerates to the jogging speed along the acceleration  
ramp of the jogging function.  
2-3  
3-4  
1
0
1
1
0
0
Drive runs at the jogging speed.  
Drive decelerates to zero speed along the deceleration ramp  
of the jogging function.  
4-5  
5-6  
0
1
1
1
0
0
Drive is stopped.  
Drive accelerates to the jogging speed along the acceleration  
ramp of the jogging function.  
6-7  
7-8  
8-9  
1
x
x
1
0
0
0
1
1
Drive runs at the jogging speed.  
Jog enable is not active; normal operation continues.  
Normal operation overrides the jogging. Drive follows the  
speed reference.  
9-10  
x
0
0
Drive decelerates to zero speed along the selected  
deceleration ramp (parameters 23.1123.19).  
10-11  
11-12  
x
x
0
0
0
1
Drive is stopped.  
Normal operation overrides the jogging. Drive accelerates to  
the speed reference along the selected acceleration ramp  
(parameters 23.1123.19).  
12-13  
13-14  
1
1
1
1
1
0
Start command overrides the jog enable signal.  
Drive decelerates to the jogging speed along the  
deceleration ramp of the jogging function.  
14-15  
15-16  
1
x
1
0
0
0
Drive runs at the jogging speed.  
Drive decelerates to zero speed along the selected  
deceleration ramp (parameters 23.1123.19).  
Program features 33  
Notes:  
• Jogging is not operational when the drive start command is on, or if the drive is in  
local control.  
• The ramp shape time is set to zero during jogging.  
Settings  
Scalar motor control  
It is possible to select scalar control as the motor control method instead of DTC  
(Direct Torque Control). In scalar control mode, the drive is controlled with a speed or  
frequency reference. However, the outstanding performance of DTC is not achieved  
in scalar control.  
It is recommended to activate scalar motor control mode in the following situations:  
• In multimotor drives: 1) if the load is not equally shared between the motors, 2) if  
the motors are of different sizes, or 3) if the motors are going to be changed after  
motor identification (ID run)  
• If the nominal current of the motor is less than 1/6 of the nominal output current of  
the drive  
• If the drive is used without a motor connected (for example, for test purposes)  
• If the drive runs a medium-voltage motor through a step-up transformer.  
In scalar control, some standard features are not available.  
IR compensation for scalar motor control  
IR compensation is available only when  
the motor control mode is scalar. When  
Motor voltage  
IR compensation is activated, the drive  
gives an extra voltage boost to the  
IR compensation  
motor at low speeds. IR compensation  
is useful in applications that require a  
high break-away torque.  
No compensation  
In Direct Torque Control (DTC), no IR  
compensation is possible or needed.  
f (Hz)  
Settings  
• Parameter group 28 Frequency reference chain (page 135).  
     
34 Program features  
Autophasing  
Autophasing is an automatic measurement routine to determine the angular position  
of the magnetic flux of a permanent magnet synchronous motor or the magnetic axis  
of a synchronous reluctance motor. The motor control requires the absolute position  
of the rotor flux in order to control motor torque accurately.  
Sensors like absolute encoders and resolvers indicate the rotor position at all times  
after the offset between the zero angle of rotor and that of the sensor has been  
established. On the other hand, a standard pulse encoder determines the rotor  
position when it rotates but the initial position is not known. However, a pulse encoder  
can be used as an absolute encoder if it is equipped with Hall sensors, albeit with  
coarse initial position accuracy. The Hall sensors generate so-called commutation  
pulses that change their state six times during one revolution, so it is only known  
within which 60° sector of a complete revolution the initial position is.  
N
Rotor  
%
Absolute encoder/resolver  
S
The autophasing routine is performed with permanent magnet synchronous motors  
and synchronous reluctance motors in the following cases:  
1. One-time measurement of the rotor and encoder position difference when an  
absolute encoder, a resolver, or an encoder with commutation signals is used  
2. At every power-up when an incremental encoder is used  
3. With open-loop motor control, repetitive measurement of the rotor position at  
every start.  
Several autophasing modes are available (see parameter 21.13 Autophasing mode).  
The turning mode is recommended especially with case 1 as it is the most robust and  
accurate method. In turning mode, the motor shaft is turned back and forward  
(±360/polepairs)° in order to determine the rotor position. In case 3 (open-loop  
control), the shaft is turned only in one direction and the angle is smaller.  
   
Program features 35  
The standstill modes can be used if the motor cannot be turned (for example, when  
the load is connected). As the characteristics of motors and loads differ, testing must  
be done to find out the most suitable standstill mode.  
A rotor position offset used in motor control can also be given by the user. See  
The drive is capable of determining the rotor position when started to a running motor  
in open-loop or closed-loop modes. In this situation, the setting of 21.13 Autophasing  
mode has no effect.  
Settings  
Flux braking  
The drive can provide greater deceleration by raising the level of magnetization in the  
motor. By increasing the motor flux, the energy generated by the motor during  
braking can be converted to motor thermal energy.  
T
Motor  
speed  
Br  
TBr = Braking torque  
TN = 100 Nm  
(%)  
TN  
60  
No flux braking  
40  
20  
Flux braking  
Flux braking  
No flux braking  
f (Hz)  
t (s)  
The drive monitors the motor status continuously, also during flux braking. Therefore,  
flux braking can be used both for stopping the motor and for changing the speed. The  
other benefits of flux braking are:  
• The braking starts immediately after a stop command is given. The function does  
not need to wait for the flux reduction before it can start the braking.  
• The cooling of the induction motor is efficient. The stator current of the motor  
increases during flux braking, not the rotor current. The stator cools much more  
efficiently than the rotor.  
• Flux braking can be used with induction motors and permanent magnet  
synchronous motors.  
Two braking power levels are available:  
• Moderate braking provides faster deceleration compared to a situation where flux  
braking is disabled. The flux level of the motor is limited to prevent excessive  
heating of the motor.  
 
36 Program features  
• Full braking exploits almost all available current to convert the mechanical braking  
energy to motor thermal energy. Braking time is shorter compared to moderate  
braking. In cyclic use, motor heating may be significant.  
Settings  
DC magnetization  
DC magnetization can be applied to the motor to lock the rotor at or near zero speed.  
Pre-magnetization  
Pre-magnetization refers to DC magnetization of the motor before start. Depending  
on the selected start mode (21.01 Start mode), pre-magnetization can be applied to  
guarantee the highest possible breakaway torque, up to 200% of the nominal torque  
of the motor. By adjusting the pre-magnetization time (21.02 Magnetization time), it is  
possible to synchronize the motor start and, for example, the release of a mechanical  
brake.  
DC hold  
The function makes it possible to lock the rotor at (near) zero speed in the middle of  
normal operation. DC hold is activated by parameter 21.08 DC current control. When  
both the reference and motor speed drop below a certain level (parameter 21.09 DC  
hold speed), the drive will stop generating sinusoidal current and start to inject DC  
into the motor. The current is set by parameter 21.10 DC current reference. When the  
reference exceeds parameter 21.09 DC hold speed, normal drive operation  
continues.  
DC hold  
Motor speed  
t
Reference  
t
Note: DC hold is only available in speed control.  
     
Program features 37  
Post-magnetization  
This feature keeps the motor magnetized for a certain period (parameter 21.11 Post  
magnetization time) after stopping. This is to prevent the machinery from moving  
under load, for example before a mechanical brake can be applied. Post-  
magnetization is activated by parameter 21.08 DC current control. The magnetization  
current is set by parameter 21.10 DC current reference.  
Note: Post-magnetization is only available when ramping is the selected stop mode  
(see parameter 21.03 Stop mode).  
Settings  
 
38 Program features  
Application control  
Application macros  
Process PID control  
There is a built-in process PID controller in the drive. The controller can be used to  
control process variables such as pressure, flow or fluid level.  
In process PID control, a process reference (setpoint) is connected to the drive  
instead of a speed reference. An actual value (process feedback) is also brought  
back to the drive. The process PID control adjusts the drive speed in order to keep  
the measured process quantity (actual value) at the desired level (setpoint).  
The simplified block diagram below illustrates the process PID control. For a more  
detailed block diagram, see page 300.  
Setpoint  
Limitation  
Speed, torque or  
frequency  
reference chain  
Process  
PID  
Filter  
AI1  
AI2  
Process  
actual  
values  
• • •  
D2D  
FBA  
The control program contains two complete sets of process PID controller settings  
that can be alternated whenever necessary; see parameter 40.57 Sel between set1  
Quick configuration of the process PID controller  
1. Activate the process PID controller (parameter 40.07 PID operation mode).  
2. Select a feedback source (parameters 40.0840.11).  
3. Select a setpoint source (parameters 40.1640.25).  
4. Set the gain, integration time, derivation time, and the PID output levels (40.32  
5. The PID controller output is shown by parameter 40.01 Process PID actual value.  
Select it as the source of, for example, 22.11 Speed ref1 selection.  
       
Program features 39  
Sleep function for process PID control  
The sleep function can be used in PID control applications where the consumption  
varies. When used, it stops the pump completely during low demand, instead of  
running the pump slowly below its efficient operating range. The following example  
visualizes the operation of the sleep function.  
The drive controls a pressure boost pump. The water consumption falls at night. As a  
consequence, the process PID controller decreases the motor speed. However, due  
to natural losses in the pipes and the low efficiency of the centrifugal pump at low  
speeds, the motor would never stop rotating. The sleep function detects the slow  
rotation and stops the unnecessary pumping after the sleep delay has passed. The  
drive shifts into sleep mode, still monitoring the pressure. The pumping resumes  
when the pressure falls under the wake-up level (setpoint - wake-up deviation) and  
the wake-up delay has passed.  
 
40 Program features  
Setpoint  
Sleep boost time (40.45)  
Sleep boost step (40.46)  
Time  
Time  
Time  
Wake-up delay  
Actual value  
Non-inverted (40.31 = Ref - Fbk)  
Wake-up level  
(Setpoint - Wake-up deviation [40.47])  
Actual value  
Wake-up level  
(Setpoint + Wake-up deviation [40.47])  
Motor speed  
tsd = Sleep delay (40.44)  
Sleep mode  
t < t  
t
sd  
sd  
Sleep level  
Time  
STOP  
START  
Tracking  
In tracking mode, the PID block output is set directly to the value of parameter 40.50  
(or 41.50) Tracking ref selection. The internal I term of the PID controller is set so that  
no transient is allowed to pass on to the output, so when the tracking mode is left,  
normal process control operation can be resumed without a significant bump.  
Settings  
• Parameter 96.04 Macro select (macro selection)  
(page 180).  
 
Program features 41  
Mechanical brake control  
A mechanical brake can be used for holding the motor and driven machinery at zero  
speed when the drive is stopped, or not powered. The brake control logic observes  
the settings of parameter group 44 Mechanical brake control as well as several  
external signals, and moves between the states presented in the diagram on page  
42. The tables below the state diagram detail the states and transitions. The timing  
diagram on page 44 shows an example of a close-open-close sequence.  
Inputs of the brake control logic  
The start command of the drive (bit 5 of 06.16 Drive status word 1) is the main control  
source of the brake control logic. An external open/close signal can optionally be  
selected by 44.12 Brake close request. The two signals interact as follows:  
• Start command = 1 AND signal selected by 44.12 Brake close request = 0  
Request brake to open  
• Start command = 0 OR signal selected by 44.12 Brake close request = 1  
Request brake to close  
Another external signal – for example, from a higher-level control system – can be  
connected via parameter 44.11 Keep brake closed to prevent the brake from opening.  
Other signals that affect the state of the control logic are  
• brake status acknowledgement (optional, defined by 44.07 Brake acknowledge  
• bit 2 of 06.11 Main status word (indicates whether the drive is ready to follow the  
given reference or not),  
• bit 6 of 06.16 Drive status word 1 (indicates whether the drive is modulating or  
not),  
• optional FSO-xx safety functions module.  
Outputs of the brake control logic  
The mechanical brake is to be controlled by bit 0 of parameter 44.01 Brake control  
status. This bit should be selected as the source of a relay output (or a digital  
input/output in output mode) which is then wired to the brake actuator through a relay.  
See the wiring example on page 45.  
The brake control logic, in various states, will request the drive control logic to hold  
the motor, increase the torque, or ramp down the speed. These requests are visible in  
Settings  
   
42 Program features  
Brake state diagram  
(from any state)  
(from any state)  
2
1
BRAKE DISABLED  
BRAKE CLOSED  
BRAKE OPENING  
3
BRAKE OPENING WAIT  
6
10  
4
BRAKE OPENING  
DELAY  
3
8
5
6
BRAKE CLOSING  
BRAKE OPEN  
BRAKE CLOSING  
DELAY  
7
BRAKE CLOSING WAIT  
6
9
State descriptions  
State name  
Description  
Brake control is disabled (parameter 44.06 Brake control enable = 0, and 44.01  
Brake control status b4 = 0). The open signal is active (44.01 Brake control  
Brake has been requested to open. The drive logic is requested to increase the  
torque up to opening torque to hold the load in place (44.01 Brake control status  
b1 = 1 and b2 = 1). The state of 44.11 Keep brake closed is checked; if it is not  
0 within a reasonable time, the drive trips on a 71A5 Mechanical brake opening  
not allowed fault*.  
BRAKE OPENING DELAY Opening conditions have been met and open signal activated (44.01 Brake  
control status b0 is set). The opening torque request is removed (44.01 Brake  
0). The load is held in place by the speed control of the  
drive until 44.08 Brake open delay elapses.  
the logic proceeds to BRAKE OPEN state. If an acknowledgement signal  
source has been selected, its state is checked; if the state is not “brake open”,  
the drive trips on a 71A3 Mechanical brake opening failed fault*.  
The brake is open (44.01 Brake control status b0 = 1). Hold request is removed  
(44.01 Brake control status b2 0), and the drive is allowed to follow the  
=
reference.  
                           
Program features 43  
State name  
Description  
Brake has been requested to close. The drive logic is requested to ramp down  
the speed to a stop (44.01 Brake control status b3 = 1). The open signal is kept  
active (44.01 Brake control status b0 = 1). The brake logic will remain in this  
state until the motor speed has remained below 44.14 Brake close level for the  
BRAKE CLOSING DELAY Closing conditions have been met. The open signal is deactivated (44.01 Brake  
0) and the closing torque written into 44.02 Brake torque  
memory. The ramp-down request is maintained (44.01 Brake control status b3  
= 1). The brake logic will remain in this state until 44.13 Brake close delay has  
elapsed.  
the logic proceeds to BRAKE CLOSED state. If an acknowledgement signal  
source has been selected, its state is checked; if the state is not “brake closed”,  
the drive generates an A7A1 Mechanical brake closing failed warning. If 44.17  
The brake is closed (44.01 Brake control status b0 = 0). The drive is not  
necessarily modulating.  
*A warning can alternatively be selected by 44.17 Brake fault function; if so, the drive will keep modulating  
and remain in this state.  
State change conditions (  
)
n
1
2
Brake control disabled (parameter 44.06 Brake control enable  
0).  
06.11 Main status word, bit 2 = 0 or brake is forced to close by optional FSO-xx safety functions  
module.  
3
4
5
Brake has been requested to open and 44.16 Brake reopen delay has expired.  
Brake open conditions (such as 44.10 Brake open torque) fulfilled and 44.11 Keep brake closed = 0.  
44.08 Brake open delay has elapsed and brake open acknowledgement (if chosen by 44.07 Brake  
acknowledge selection) has been received.  
6
7
Brake has been requested to close.  
Motor speed has remained below closing speed 44.14 Brake close level for the duration of 44.15  
8
44.13 Brake close delay has elapsed and brake close acknowledgement (if chosen by 44.07 Brake  
acknowledge selection) has been received.  
9
Brake has been requested to open.  
10 Brake control enabled (parameter 44.06 Brake control enable  
1).  
44 Program features  
Operation time scheme  
The simplified time scheme below illustrates the operation of the brake control  
function. Refer to the state diagram above.  
Start command  
(06.16 b5)  
Modulating (06.16 b6)  
tmd  
Ready ref (06.11 b2)  
Torque reference  
Ts  
Tmem  
Speed reference  
ncs  
trod  
Brake control signal  
tod  
tccd  
Opening torque  
tcd  
tcfd  
request (44.01 b1)  
Hold stopped request  
(44.01 b2)  
Ramp to stopped  
request (44.01 b3)  
BOW  
BOD  
BCW  
BCD  
State  
1
2
3
4
5
6
7
8
9
Ts  
Start torque at brake open (parameter 44.03 Brake open torque reference)  
Tmem Stored torque value at brake close (44.02 Brake torque memory)  
tmd  
tod  
Motor magnetization delay  
Brake open delay (parameter 44.08 Brake open delay)  
Brake close speed (parameter 44.14 Brake close level)  
Brake close command delay (parameter 44.15 Brake close level delay)  
Brake close delay (parameter 44.13 Brake close delay)  
Brake close fault delay (parameter 44.18 Brake fault delay)  
Brake reopen delay (parameter 44.16 Brake reopen delay)  
ncs  
tccd  
tcd  
tcfd  
trod  
BCD  
 
Program features 45  
Wiring example  
The figure below shows a brake control wiring example. The brake control hardware  
and wiring is to be sourced and installed by the customer.  
WARNING! Make sure that the machinery into which the drive with brake  
control function is integrated fulfils the personnel safety regulations. Note  
that the frequency converter (a Complete Drive Module or a Basic Drive  
Module, as defined in IEC 61800-2), is not considered as a safety device  
mentioned in the European Machinery Directive and related harmonised standards.  
Thus, the personnel safety of the complete machinery must not be based on a  
specific frequency converter feature (such as the brake control function), but it has to  
be implemented as defined in the application specific regulations.  
The brake is controlled by bit 0 of parameter 44.01 Brake control status. The source  
of brake acknowledge (status supervision) is selected by parameter 44.07 Brake  
acknowledge selection. In this example,  
• parameter 10.24 RO1 source is set to Open brake command (ie. bit 0 of 44.01  
Drive control unit  
Brake control  
hardware  
XRO1  
115/230 VAC  
1 NC  
2 COM  
3 NO  
Emergency  
brake  
XD24  
4 +24VD  
XDIO  
5 DI5  
M
Mechanical brake  
Motor  
 
46 Program features  
DC voltage control  
Overvoltage control  
Overvoltage control of the intermediate DC link is typically needed when the motor is  
in generating mode. To prevent the DC voltage from exceeding the overvoltage  
control limit, the overvoltage controller automatically decreases the generating torque  
when the limit is reached.  
Undervoltage control  
If the incoming supply voltage is cut off, the drive will continue to operate by utilizing  
the kinetic energy of the rotating motor. The drive will be fully operational as long as  
the motor rotates and generates energy to the drive. The drive can continue  
operation after the break if the main contactor (if present) remained closed.  
Note: Units equipped with a main contactor must be equipped with a hold circuit (e.g.  
UPS) to keep the contactor control circuit closed during a short supply break.  
Umains  
TM  
fout  
UDC  
(Nm) (Hz) (V DC)  
UDC  
160  
120  
80  
80  
60  
40  
20  
520  
390  
260  
130  
fout  
TM  
40  
t (s)  
1.6  
4.8  
8
11.2  
14.4  
UDC= intermediate circuit voltage of the drive, fout = output frequency of the drive, TM = motor torque  
Loss of supply voltage at nominal load (fout = 40 Hz). The intermediate circuit DC voltage drops to the  
minimum limit. The controller keeps the voltage steady as long as the mains is switched off. The drive runs  
the motor in generator mode. The motor speed falls but the drive is operational as long as the motor has  
enough kinetic energy.  
     
Program features 47  
Automatic restart  
It is possible to restart the drive automatically after a short (max. 5 seconds) power  
supply failure by using the Automatic restart function provided that the drive is  
allowed to run for 5 seconds without the cooling fans operating.  
When enabled, the function takes the following actions upon a supply failure to  
enable a successful restart:  
• The undervoltage fault is suppressed (but a warning is generated)  
• Modulation and cooling is stopped to conserve any remaining energy  
• DC circuit pre-charging is enabled.  
If the DC voltage is restored before the expiration of the period defined by parameter  
21.18 Auto restart time and the start signal is still on, normal operation will continue.  
However, if the DC voltage remains too low at that point, the drive trips on a fault,  
Voltage control and trip limits  
The control and trip limits of the intermediate DC voltage regulator are relative to the  
supply voltage as well as drive/inverter type. The DC voltage (U ) is approximately  
DC  
1.35 times the line-to-line supply voltage, and is displayed by parameter 01.11 DC  
The following diagram shows the relation of selected DC voltage levels. Note that the  
absolute voltages vary according to drive/inverter type and AC supply voltage range.  
Overvoltage fault level (1.3 × UDCmax)*  
Overvoltage control level (1.25 × UDCmax)**  
Overvoltage warning level (1.15 × UDCmax  
)
UDCmax  
UDCmin  
Undervoltage control/warning level (0.85 × UDCmin  
)
Undervoltage fault level (0.6 × UDCmin  
)
U
U
DCmax = DC voltage corresponding to the maximum of the AC supply voltage range  
DCmin = DC voltage corresponding to the minimum of the AC supply voltage range  
* For 500 V AC supply voltage range, 1.25 × UDCmax  
.
** For 500 V AC supply voltage range, 1.20 × UDCmax  
.
   
48 Program features  
Settings  
Brake chopper  
A brake chopper can be used to handle the energy generated by a decelerating  
motor. When the DC voltage rises high enough, the chopper connects the DC circuit  
to an external brake resistor. The chopper operates on the pulse width modulation  
principle.  
The internal brake choppers of ACS880 drives start conducting when the DC link  
voltage reaches approximately 1.15 × U  
. 100% pulse width is reached at  
DCmax  
approximately 1.2 × U  
. (U  
is the DC voltage corresponding to the  
DCmax  
DCmax  
maximum of the AC supply voltage range.)  
For information on external brake choppers, refer to their documentation.  
Settings  
Parameter 01.11 DC voltage (page 76); parameter group 43 Brake chopper (page  
 
Program features 49  
Safety and protections  
Emergency stop  
The emergency stop signal is connected to the input selected by parameter 21.05  
Emergency stop source. The mode of the emergency stop is selected by parameter  
21.04 Emergency stop mode. An emergency stop can also be generated through a  
fieldbus (parameter 06.01 Main control word, bits 0…2).  
Notes:  
• The installer of the equipment is responsible for installing the emergency stop  
devices and all additional devices needed for the emergency stop function to fulfill  
the required emergency stop categories. For more information, contact your local  
ABB representative.  
• After an emergency stop signal is detected, the emergency stop function cannot  
be canceled even though the signal is canceled.  
• If the minimum (or maximum) torque limit is set to 0%, the emergency stop  
function may not be able to stop the drive.  
Motor thermal protection  
The control program features two separate motor temperature monitoring functions.  
The temperature data sources and warning/trip limits can be set up independently for  
each function.  
The motor temperature can be monitored using  
• the motor thermal protection model (estimated temperature), or  
• sensors installed in the windings. This will result in a more accurate motor model.  
Motor thermal protection model  
The drive calculates the temperature of the motor on the basis of the following  
assumptions:  
1. When power is applied to the drive for the first time, the motor is at ambient  
temperature (defined by parameter 35.50 Motor ambient temperature). After this,  
when power is applied to the drive, the motor is assumed to be at the estimated  
temperature.  
2. Motor temperature is calculated using the user-adjustable motor thermal time and  
motor load curve. The load curve should be adjusted in case the ambient  
temperature exceeds 30 °C.  
Note: The motor thermal model can be used when only one motor is connected to  
the inverter.  
       
50 Program features  
Temperature monitoring using PTC sensors  
One PTC sensor can be connected to digital input DI6. FEN-xx encoder interfaces  
(optional) also have a connection for one PTC sensor.  
Connecting a PTC sensor to DI6 requires a voltage divider circuit such as the one  
pictured below.  
+24VD  
T
DI6  
1 kohm  
DICOM  
The resistance of a PTC sensor increases when its temperature rises. The increasing  
resistance of the sensor decreases the voltage over the 1 kohm resistor, and  
eventually the state of DI6 switches from 1 to 0, indicating overtemperature.  
The figure below shows typical PTC sensor resistance values as a function of  
temperature.  
Ohm  
4000  
1330  
550  
100  
T
For detailed wiring information, refer to the Hardware Manual of the drive, or the User  
manual of the FEN-xx encoder interface.  
Temperature monitoring using Pt100 sensors  
1…3 Pt100 sensors can be connected in series to an analog input and an analog  
output.  
Program features 51  
The analog output feeds a constant excitation current of 9.1 mA through the sensor.  
The sensor resistance increases as the motor temperature rises, as does the voltage  
over the sensor. The temperature measurement function reads the voltage through  
the analog input and converts it into degrees Celsius.  
It is possible to adjust the motor temperature supervision limits and select how the  
drive reacts when overtemperature is detected.  
For the wiring of the sensor, refer to the Hardware Manual of the drive.  
Temperature monitoring using KTY84 sensors  
One KTY84 sensor can be connected to an analog input and an analog output either  
on the control unit or on an optional FIO-21 analog extension.  
The analog output feeds a constant excitation current of 2.0 mA through the sensor.  
The sensor resistance increases as the motor temperature rises, as does the voltage  
over the sensor. The temperature measurement function reads the voltage through  
the analog input and converts it into degrees Celsius.  
FEN-xx encoder interfaces (optional) also have a connection for one PTC sensor.  
The figure and table below show typical KTY84 sensor resistance values as a  
function of the motor operating temperature.  
Ohm  
3000  
2000  
KTY84 scaling  
90 °C = 936 ohm  
110 °C = 1063 ohm  
130 °C = 1197 ohm  
150 °C = 1340 ohm  
1000  
0
T oC  
-100  
0
100  
200  
300  
It is possible to adjust the motor temperature supervision limits and select how the  
drive reacts when overtemperature is detected.  
For the wiring of the sensor, refer to the Hardware Manual of the drive.  
52 Program features  
Settings  
Programmable protection functions  
External events (parameters 31.01 and 31.02)  
An external event signal can be connected to a selectable input. When the signal is  
lost, an external event (fault, warning, or a mere log entry) is generated.  
Motor phase loss detection (parameter 31.19)  
The parameter selects how the drive reacts whenever a motor phase loss is detected.  
Earth fault detection (parameter 31.20)  
The earth fault detection function is based on sum current measurement. Note that  
• an earth fault in the supply cable does not activate the protection  
• in a grounded supply, the protection activates in 200 milliseconds  
• in an ungrounded supply, the supply capacitance should be 1 microfarad or more  
• the capacitive currents caused by shielded motor cables up to 300 meters will not  
activate the protection  
• the protection is deactivated when the drive is stopped.  
Supply phase loss detection (parameter 31.21)  
The parameter selects how the drive reacts whenever a supply phase loss is  
detected.  
Safe torque off detection (parameter 31.22)  
The drive monitors the status of the Safe torque off input. For more information on the  
Safe torque off function, see the Hardware manual.  
Switched supply and motor cabling (parameter 31.23)  
The drive can detect if the supply and motor cables have accidentally been switched  
(for example, if the supply is connected to the motor connection of the drive). The  
parameter selects if a fault is generated or not.  
Stall protection (parameters 31.2431.28)  
The drive protects the motor in a stall situation. It is possible to adjust the supervision  
limits (current, frequency and time) and choose how the drive reacts to a motor stall  
condition.  
 
Program features 53  
Overspeed protection (parameter 31.30)  
The user can set overspeed (and overfrequency) limits by specifying a margin that is  
added to the currently-used maximum and minimum speed (or frequency) limits.  
Local control loss detection (parameter 49.05)  
The parameter selects how the drive reacts to a control panel or PC tool  
communication break.  
Automatic fault resets  
The drive can automatically reset itself after overcurrent, overvoltage, undervoltage,  
external and “analog input below minimum” faults. The user can also specify a fault  
that is automatically reset.  
By default, automatic resets are off and must be specifically activated by the user.  
Settings  
Parameters 31.1231.16 (page 147).  
 
54 Program features  
Diagnostics  
Signal supervision  
Three signals can be selected to be supervised by this function. Whenever a  
supervised signal exceeds or falls below predefined limits, a bit in 32.01 Supervision  
status is activated, and a warning or fault generated. The supervised signal is low-  
pass filtered.  
Settings  
Parameter group 32 Supervision (page 150).  
Maintenance timers and counters  
The program has six different maintenance timers or counters that can be configured  
to generate a warning when a pre-defined limit is reached. The timer/counter can be  
set to monitor any parameter. This feature is especially useful as a service reminder.  
There are three types of counters:  
• On-time timers. Measures the time a binary source (for example, a bit in a status  
word) is on.  
• Signal edge counters. The counter is incremented whenever the monitored binary  
source changes state.  
• Value counters. The counter measures, by integration, the monitored parameter.  
An alarm is given when the calculated area below the signal peak exceeds a  
user-defined limit.  
Settings  
Energy savings calculator  
This feature consists of the following functionalities:  
• An energy optimizer that adjusts the motor flux in such a way that the total  
efficiency is maximized  
• A counter that monitors used and saved energy by the motor and displays them in  
kWh, currency or volume of CO emissions, and  
2
• A load analyzer showing the load profile of the drive (see separate section on  
page 55).  
Note: The accuracy of the energy savings calculation is directly dependent on the  
accuracy of the reference motor power given in parameter 45.19 Comparison power.  
Settings  
Parameter group 45 Energy efficiency (page 187).  
             
Program features 55  
Load analyzer  
Peak value logger  
The user can select a signal to be monitored by a peak value logger. The logger  
records the peak value of the signal along with the time the peak occurred, as well as  
motor current, DC voltage and motor speed at the time of the peak.  
Amplitude loggers  
The control program has two amplitude loggers.  
For amplitude logger 2, the user can select a signal to be sampled at 200 ms intervals  
when the drive is running, and specify a value that corresponds to 100%. The  
collected samples are sorted into 10 read-only parameters according to their  
amplitude. Each parameter represents an amplitude range 10 percentage points  
wide, and displays the percentage of the collected samples that fall within that range.  
Amplitude ranges  
(parameters 36.4036.49)  
Amplitude logger 1 is fixed to monitor motor current, and cannot be reset. With  
amplitude logger 1, 100% corresponds to the maximum output current of the drive  
(I  
). The distribution of samples is shown by parameters 36.2036.29.  
max  
Settings  
Parameter group 36 Load analyzer (page 166).  
   
56 Program features  
Miscellaneous  
Data storage parameters  
Twenty-four (sixteen 32-bit, eight 16-bit) parameters are reserved for data storage.  
These parameters are unconnected by default and can be used for linking, testing  
and commissioning purposes. They can be written to and read from using other  
parameters’ source or target selections.  
Settings  
Parameter group 47 Data storage (page 191).  
     
Application macros 57  
5
Application macros  
What this chapter contains  
This chapter describes the intended use, operation and default control connections of  
the application macros.  
More information on the connectivity of the control unit is given in the Hardware  
manual of the drive.  
General  
Application macros are sets of default parameter values suitable for the application in  
question. When starting up the drive, the user typically selects the best-suited  
application macro as a basis and makes the necessary changes.  
Application macros can be selected by parameter 96.04 Macro select.  
       
58 Application macros  
Factory macro  
The Factory macro is suited to relatively straightforward speed control applications  
such as conveyors, pumps and fans, and test benches.  
In external control, the control location is EXT1. The drive is speed-controlled with the  
reference signal connected to analog input AI1. The start/stop commands are given  
through digital input DI1; running direction is determined by DI2.  
Faults are reset through digital input DI3.  
DI4 switches between acceleration/deceleration time sets 1 and 2. The acceleration  
and deceleration times, as well as ramp shapes, are defined by parameters  
DI5 activates constant speed 1.  
Default parameter settings for the Factory macro  
The default parameter settings for the Factory macro are listed under Parameter  
     
Application macros 59  
Default control connections for the Factory macro  
XPOW External power input  
1
2
+24VI  
GND  
24 V DC, 2 A  
XAI  
1
2
Reference voltage and analog inputs  
+VREF 10 V DC, RL 1…10 kohm  
-VREF -10 V DC, RL 1…10 kohm  
AGND Ground  
3
4
5
6
7
AI1+  
AI1-  
AI2+  
AI2-  
Speed reference  
0(2)…10 V, Rin > 200 kohm  
By default not in use.  
0(4)…20 mA, Rin > 100 ohm  
XAO Analog outputs  
1
2
3
4
AO1  
AGND  
AO2  
Motor speed rpm  
0…20 mA, RL < 500 ohm  
Motor current  
0…20 mA, RL < 500 ohm  
AGND  
XD2D Drive-to-drive link  
1
2
3
B
A
Drive-to-drive link  
BGND  
XRO1, XRO2, XRO3 Relay outputs  
1
2
3
1
2
3
1
2
3
NC  
COM  
NO  
NC  
COM  
NO  
NC  
COM  
NO  
Ready  
250 V AC / 30 V DC  
2 A  
Running  
250 V AC / 30 V DC  
2 A  
Faulted(-1)  
250 V AC / 30 V DC  
2 A  
Fault  
XD24 Digital interlock  
1
2
3
4
5
DIIL  
Digital interlock. By default, not in use.  
+24VD +24 V DC 200 mA  
DICOM Digital input ground  
+24VD +24 V DC 200 mA  
DIOGND Digital input/output ground  
XDIO Digital input/outputs  
1
2
DIO1  
DIO2  
Output: Ready  
Output: Running  
XDI  
1
2
3
4
Digital inputs  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
Stop (0) / Start (1)  
Forward (0) / Reverse (1)  
Reset  
Acc/Dec time set 1 (0) / set 2 (1)  
Constant speed 1 (1 = On)  
By default, not in use.  
5
6
Safe torque off circuits must be closed for the drive to start. See  
Hardware manual of drive.  
XSTO  
X12  
X13  
Safety options connection  
Control panel connection  
X205 Memory unit connection  
 
60 Application macros  
Hand/Auto macro  
The Hand/Auto macro is suited to speed control applications where two external  
control devices are used.  
The drive is speed-controlled from the external control locations EXT1 (Hand control)  
and EXT2 (Auto control). The selection between the control locations is done through  
digital input DI3.  
The start/stop signal for EXT1 is connected to DI1 while running direction is  
determined by DI2. For EXT2, start/stop commands are given through DI6, the  
direction through DI5.  
The reference signals for EXT1 and EXT2 are connected to analog inputs AI1 and  
AI2 respectively.  
A constant speed (by default, 300 rpm) can be activated through DI4.  
Default parameter settings for the Hand/Auto macro  
Below is a listing of default parameter values that differ from those listed for the  
Parameter  
Hand/Auto macro default  
No.  
Name  
1500.000  
     
Application macros 61  
Default control connections for the Hand/Auto macro  
XPOW External power input  
1
2
+24VI  
GND  
24 V DC, 2 A  
XAI  
1
2
Reference voltage and analog inputs  
+VREF 10 V DC, RL 1…10 kohm  
-VREF -10 V DC, RL 1…10 kohm  
AGND Ground  
3
4
5
6
7
AI1+  
AI1-  
AI2+  
AI2-  
Speed reference (Hand)  
0(2)…10 V, Rin > 200 kohm  
Speed reference (Auto)  
0(4)…20 mA, Rin > 100 ohm  
XAO Analog outputs  
1
2
3
4
AO1  
AGND  
AO2  
Motor speed rpm  
0…20 mA, RL < 500 ohm  
Motor current  
0…20 mA, RL < 500 ohm  
AGND  
XD2D Drive-to-drive link  
1
2
3
B
A
Drive-to-drive link  
BGND  
XRO1, XRO2, XRO3 Relay outputs  
1
2
3
1
2
3
1
2
3
NC  
COM  
NO  
NC  
COM  
NO  
NC  
COM  
NO  
Ready  
250 V AC / 30 V DC  
2 A  
Running  
250 V AC / 30 V DC  
2 A  
Faulted(-1)  
250 V AC / 30 V DC  
2 A  
Fault  
XD24 Digital interlock  
1
2
3
4
5
DIIL  
Digital interlock. By default, not in use.  
+24VD +24 V DC 200 mA  
DICOM Digital input ground  
+24VD +24 V DC 200 mA  
DIOGND Digital input/output ground  
XDIO Digital input/outputs  
1
2
DIO1  
DIO2  
Output: Ready  
Output: Running  
XDI  
1
2
3
4
Digital inputs  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
Stop (0) / Start (1) – Hand  
Forward (0) / Reverse (1) – Hand  
Hand (0) / Auto (1)  
Constant speed 1 (1 = On)  
Forward (0) / Reverse (1) – Auto  
Stop (0) / Start (1) – Auto  
5
6
Safe torque off circuits must be closed for the drive to start. See  
Hardware manual of drive.  
XSTO  
X12  
X13  
Safety options connection  
Control panel connection  
X205 Memory unit connection  
 
62 Application macros  
PID control macro  
The PID control macro is suitable for process control applications, for example  
closed-loop pressure, level or flow control systems such as  
• pressure boost pumps of municipal water supply systems  
• level-controlling pumps of water reservoirs  
• pressure boost pumps of district heating systems  
• material flow control on a conveyor line.  
The process reference signal is connected to analog input AI1 and the process  
feedback signal to AI2. Alternatively, a direct speed reference can be given to the  
drive through AI1. Then the PID controller is bypassed and the drive no longer  
controls the process variable.  
Selection between direct speed control (control location EXT1) and process variable  
control (EXT2) is done through digital input DI3.  
The stop/start signals for EXT1 and EXT2 are connected to DI1 and DI6 respectively.  
A constant speed (by default, 300 rpm) can be activated through DI4.  
   
64 Application macros  
Default control connections for the PID control macro  
XPOW External power input  
1
2
+24VI  
GND  
24 V DC, 2 A  
XAI  
1
2
Reference voltage and analog inputs  
+VREF 10 V DC, RL 1…10 kohm  
-VREF -10 V DC, RL 1…10 kohm  
AGND Ground  
3
4
5
6
7
AI1+  
AI1-  
AI2+  
AI2-  
Process or Speed reference  
0(2)…10 V, Rin > 200 kohm  
Process feedback*  
P
I
0(4)…20 mA, Rin > 100 ohm  
XAO Analog outputs  
1
2
3
4
AO1  
AGND  
AO2  
Motor speed rpm  
0…20 mA, RL < 500 ohm  
Motor current  
0…20 mA, RL < 500 ohm  
AGND  
XD2D Drive-to-drive link  
1
2
3
B
A
Drive-to-drive link  
BGND  
XRO1, XRO2, XRO3 Relay outputs  
1
2
3
1
2
3
1
2
3
NC  
COM  
NO  
NC  
COM  
NO  
NC  
COM  
NO  
Ready  
250 V AC / 30 V DC  
2 A  
Running  
250 V AC / 30 V DC  
2 A  
Faulted(-1)  
250 V AC / 30 V DC  
2 A  
Fault  
XD24 Digital interlock  
1
2
3
4
5
DIIL  
Digital interlock. By default, not in use.  
+24VD +24 V DC 200 mA  
DICOM Digital input ground  
+24VD +24 V DC 200 mA  
DIOGND Digital input/output ground  
XDIO Digital input/outputs  
1
2
DIO1  
DIO2  
Output: Ready  
Output: Running  
XDI  
1
2
3
4
Digital inputs  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
Stop (0) / Start (1) – Speed control  
By default, not in use.  
Speed control (0) / Process control (1)  
Constant speed 1 (1 = On)  
By default, not in use.  
5
6
Stop (0) / Start (1) – Process control  
Safe torque off circuits must be closed for the drive to start. See  
Hardware manual of drive.  
XSTO  
X12 Safety options connection  
X13 Control panel connection  
X205 Memory unit connection  
*For sensor connection examples, see page 65.  
 
Application macros 65  
Sensor connection examples  
XAI  
+
0/4…20 mA  
6
7
AI2+  
AI2-  
Actual value measurement  
-20…20 mA. Rin = 100 ohm  
P
I
Note: The sensor must be powered externally.  
XAI  
+
OUT  
Reference voltage output  
Ground  
1
3
+VREF  
P
AGND  
I
0/4…20 mA  
6
7
AI2+  
AI2-  
Actual value measurement  
-20…20 mA. Rin = 100 ohm  
XAI  
1
+
Reference voltage output  
Ground  
+VREF  
AGND  
P
P
3
I
0/4…20 mA  
0/4…20 mA  
6
7
AI2+  
AI2-  
Actual value measurement  
-20…20 mA. Rin = 100 ohm  
Drive 1 / XAI  
+
6
7
AI2+  
AI2-  
Actual value measurement  
-20…20 mA. Rin = 100 ohm  
I
Drive 2 / XAI  
+24V  
Power  
supply  
6
7
AI2+  
AI2-  
Actual value measurement. -20…20 mA.  
Rin = 100 ohm  
Drive 3 / XAI  
6
7
AI2+  
AI2-  
Actual value measurement. -20…20 mA.  
Rin = 100 ohm  
 
66 Application macros  
Torque control macro  
This macro is used in applications in which torque control of the motor is required.  
Torque reference is given through analog input AI2, typically as a current signal in the  
range of 0…20 mA (corresponding to 0…100% of rated motor torque).  
The start/stop signal is connected to digital input DI1. The direction is determined by  
DI2.  
Through digital input DI3, it is possible to select speed control instead of torque  
control. It is also possible to change the control to local (control panel or PC tool) by  
pressing the Loc/Rem key. By default, the local reference is speed; if a torque  
reference is required, the value of parameter 19.16 Local control mode should be  
changed to Torque.  
A constant speed (by default, 300 rpm) can be activated through DI4. DI5 switches  
between acceleration/deceleration time sets 1 and 2. The acceleration and  
deceleration times, as well as ramp shapes, are defined by parameters  
Default parameter settings for the Torque control macro  
Below is a listing of default parameter values that differ from those listed for the  
Parameter  
Torque control macro  
default  
No.  
Name  
DI3  
     
Application macros 67  
Default control connections for the Torque control macro  
XPOW External power input  
1
2
+24VI  
GND  
24 V DC, 2 A  
XAI  
1
2
Reference voltage and analog inputs  
+VREF 10 V DC, RL 1…10 kohm  
-VREF -10 V DC, RL 1…10 kohm  
AGND Ground  
3
4
5
6
7
AI1+  
AI1-  
AI2+  
AI2-  
Speed reference  
0(2)…10 V, Rin > 200 kohm  
Torque reference  
0(4)…20 mA, Rin > 100 ohm  
XAO Analog outputs  
1
2
3
4
AO1  
AGND  
AO2  
Motor speed rpm  
0…20 mA, RL < 500 ohm  
Motor current  
0…20 mA, RL < 500 ohm  
AGND  
XD2D Drive-to-drive link  
1
2
3
B
A
Drive-to-drive link  
BGND  
XRO1, XRO2, XRO3 Relay outputs  
1
2
3
1
2
3
1
2
3
NC  
COM  
NO  
NC  
COM  
NO  
NC  
COM  
NO  
Ready  
250 V AC / 30 V DC  
2 A  
Running  
250 V AC / 30 V DC  
2 A  
Faulted(-1)  
250 V AC / 30 V DC  
2 A  
Fault  
XD24 Digital interlock  
1
2
3
4
5
DIIL  
Digital interlock. By default, not in use.  
+24VD +24 V DC 200 mA  
DICOM Digital input ground  
+24VD +24 V DC 200 mA  
DIOGND Digital input/output ground  
XDIO Digital input/outputs  
1
2
DIO1  
DIO2  
Output: Ready  
Output: Running  
XDI  
1
2
3
4
Digital inputs  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
Stop (0) / Start (1)  
Forward (0) / Reverse (1)  
Speed control (0) / Torque control (1)  
Constant speed 1 (1 = On)  
Acc/Dec time set 1 (0) / set 2 (1)  
By default, not in use.  
5
6
Safe torque off circuits must be closed for the drive to start. See  
Hardware manual of drive.  
XSTO  
X12  
X13  
Safety options connection  
Control panel connection  
X205 Memory unit connection  
 
68 Application macros  
Sequential control macro  
The Sequential control macro is suited for speed control applications in which a  
speed reference, multiple constant speeds, and two acceleration and deceleration  
ramps can be used.  
The macro offers seven preset constant speeds which can be activated by digital  
inputs DI4…DI6 (see parameter 22.21 Constant speed function). An external speed  
reference can be given through analog input AI1. The reference is active only when  
no constant speed is activated (digital inputs DI4…DI6 are all off). Operational  
commands can also be given from the control panel.  
The start/stop commands are given through digital input DI1; running direction is  
determined by DI2.  
Two acceleration/deceleration ramps are selectable through DI3. The acceleration  
and deceleration times, as well as ramp shapes, are defined by parameters  
Operation diagram  
The figure below shows an example of the use of the macro.  
Speed  
Speed 3  
Speed 2  
Stop along deceleration  
ramp  
Speed 1  
Time  
Accel1  
Accel1  
Accel2  
Decel2  
Start/Stop  
Accel1/Decel1  
Speed 1  
Speed 2  
Accel2/Decel2  
Speed 3  
     
Application macros 69  
Selection of constant speeds  
By default, constant speeds 1…7 are selected using digital inputs DI4…DI6 as  
follows:  
DI4  
DI5  
DI6  
Constant speed active  
None (External speed  
reference used)  
0
0
0
1
0
1
0
1
0
1
0
1
1
0
0
1
1
0
0
0
1
1
1
1
Constant speed 1  
Constant speed 2  
Constant speed 3  
Constant speed 4  
Constant speed 5  
Constant speed 6  
Constant speed 7  
Default parameter settings for the Sequential control macro  
Below is a listing of default parameter values that differ from those listed for the  
Parameter  
Sequential control macro  
default  
No.  
Name  
DI3  
01b (Bit 0 = Packed)  
600.00 rpm  
900.00 rpm  
1200.00 rpm  
1500.00 rpm  
2400.00 rpm  
3000.00 rpm  
   
70 Application macros  
Default control connections for the Sequential control macro  
XPOW External power input  
1
2
+24VI  
GND  
24 V DC, 2 A  
XAI  
1
2
Reference voltage and analog inputs  
+VREF 10 V DC, RL 1…10 kohm  
-VREF -10 V DC, RL 1…10 kohm  
AGND Ground  
3
4
5
6
7
AI1+  
AI1-  
AI2+  
AI2-  
External speed reference  
0(2)…10 V, Rin > 200 kohm  
By default, not in use.  
0(4)…20 mA, Rin > 100 ohm  
XAO Analog outputs  
1
2
3
4
AO1  
AGND  
AO2  
Motor speed rpm  
0…20 mA, RL < 500 ohm  
Motor current  
0…20 mA, RL < 500 ohm  
AGND  
XD2D Drive-to-drive link  
1
2
3
B
A
Drive-to-drive link  
BGND  
XRO1, XRO2, XRO3 Relay outputs  
1
2
3
1
2
3
1
2
3
NC  
COM  
NO  
NC  
COM  
NO  
NC  
COM  
NO  
Ready  
250 V AC / 30 V DC  
2 A  
Running  
250 V AC / 30 V DC  
2 A  
Faulted(-1)  
250 V AC / 30 V DC  
2 A  
Fault  
XD24 Digital interlock  
1
2
3
4
5
DIIL  
Digital interlock. By default, not in use.  
+24VD +24 V DC 200 mA  
DICOM Digital input ground  
+24VD +24 V DC 200 mA  
DIOGND Digital input/output ground  
XDIO Digital input/outputs  
1
2
DIO1  
DIO2  
Output: Ready  
Output: Running  
XDI  
1
2
3
4
Digital inputs  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
Stop (0) / Start (1)  
Forward (0) / Reverse (1)  
Acc/Dec time set 1 (0) / set 2 (1)  
Constant speed selection (see page 69)  
5
6
Safe torque off circuits must be closed for the drive to start. See  
Hardware manual of drive.  
XSTO  
X12 Safety options connection  
X13 Control panel connection  
X205 Memory unit connection  
 
Application macros 71  
Fieldbus control macro  
This application macro is not supported by the current firmware version.  
   
72 Application macros  
Parameters 73  
6
Parameters  
What this chapter contains  
The chapter describes the parameters, including actual signals, of the control  
program.  
Terms and abbreviations  
Term  
Definition  
Actual signal  
Type of parameter that is the result of a measurement or calculation by  
the drive, or contains status information. Most actual signals are read-  
only, but some (especially counter-type actual signals) can be reset.  
Def  
(In the following table, shown on the same row as the parameter name)  
The default value of a parameter for the Factory macro. For information  
on macro-specific parameter values, see chapter Application macros  
(page 57).  
FbEq16  
(In the following table, shown on the same row as the parameter range,  
or for each selection)  
16-bit fieldbus equivalent: The scaling between the value shown on the  
panel and the integer used in fieldbus communication when a 16-bit value  
is selected in parameter group 52 FBA A data in or 53 FBA A data out.  
A dash (-) indicates that the parameter is not accessible in 16-bit format.  
The corresponding 32-bit scalings are listed in chapter Additional  
Other [bit]  
Parameter  
p.u.  
The value is taken from a specific bit in another parameter. The source is  
selected from a parameter list.  
Either an user-adjustable operating instruction for the drive, or an actual  
Per unit  
             
74 Parameters  
Summary of parameter groups  
selection; positive/negative reference enable signal source  
selection; DC magnetization settings; autophasing mode  
 
76 Parameters  
Parameter listing  
No.  
Name/Value  
Description  
Def/FbEq16  
01  
Basic signals for monitoring of the drive.  
All parameters in this group are read-only unless otherwise  
noted.  
Measured or estimated motor speed depending on which  
type of feedback is used (see parameter 90.41 Motor  
feedback selection). A filter time constant for this signal can  
be defined by parameter 46.11 Filter time motor speed.  
-
-30000.00 …  
30000.00 rpm  
Measured or estimated motor speed.  
1 = 1 rpm  
-
Estimated motor speed in rpm. A filter time constant for this  
signal can be defined by parameter 46.11 Filter time motor  
-30000.00 …  
30000.00 rpm  
Estimated motor speed.  
1 = 1 rpm  
Speed of encoder 1 in rpm.A filter time constant for this signal  
can be defined by parameter 46.11 Filter time motor speed.  
-
-30000.00 …  
30000.00 rpm  
Encoder 1 speed.  
1 = 1 rpm  
Speed of encoder 2 in rpm.A filter time constant for this signal  
can be defined by parameter 46.11 Filter time motor speed.  
-
-30000.00 …  
30000.00 rpm  
Encoder 2 speed.  
1 = 1 rpm  
-
Estimated drive output frequency in Hz. A filter time constant  
for this signal can be defined by parameter 46.12 Filter time  
-3000.00 …  
3000.00 Hz  
Estimated output frequency.  
1 = 1 Hz  
Measured (absolute) motor current in A.  
-
0.00 … 30000.00 A Motor current.  
1 = 1 A  
-
Motor torque % Motor torque in percent of the nominal motor torque. See also  
A filter time constant for this signal can be defined by  
-1600.0 … 1600.0% Motor torque.  
1 = 1%  
Measured intermediate circuit voltage.  
-
0.00 … 2000.00 V  
Intermediate circuit voltage.  
10 = 1 V  
-
Drive output power in kW. A filter time constant for this signal  
can be defined by parameter 46.14 Filter time power out.  
-32768.00 …  
32767.00 kW  
Output power.  
1 = 1 kW  
-
Amount of energy that has passed through the drive (in either  
direction) in full gigawatt-hours. The minimum value is zero.  
0…65535 GWh  
Energy in GWh.  
1 = 1 GWh  
                                                         
Parameters 77  
No.  
Name/Value  
Description  
Def/FbEq16  
Amount of energy that has passed through the drive (in either  
direction) in full megawatt-hours. Whenever the counter rolls  
over, 01.18 Inverter GWh counter is incremented.The  
minimum value is zero.  
-
0…999 MWh  
Energy in MWh.  
1 = 1 MWh  
-
Amount of energy that has passed through the drive (in either  
direction) in full kilowatt-hours. Whenever the counter rolls  
over, 01.19 Inverter MWh counter is incremented.The  
minimum value is zero.  
0…999 kWh  
0…200%  
Energy in kWh.  
10 = 1 kWh  
Used flux reference in percent of nominal flux of motor.  
Flux reference.  
-
1 = 1%  
-
Torque that corresponds to 100% of nominal motor torque.  
Note: This value is copied from parameter 99.12 Motor  
nominal torque if entered. Otherwise the value is calculated  
from other motor data.  
0… N•m  
Nominal torque.  
1 = 100 N•m  
-
Measured temperature of incoming cooling air in °C.  
-32768.0 …  
32767.0 °C  
Cooling air temperature.  
1 = 1 °C  
03  
Values of references received from various sources.  
All parameters in this group are read-only unless otherwise  
noted.  
04  
Reference given from the control panel or PC tool.  
Control panel or PC tool reference.  
-
-100000.00 …  
100000.00  
1 = 10  
Reference 1 received through fieldbus adapter A.  
Reference 1 from fieldbus adapter A.  
-
-100000.00 …  
100000.00  
1 = 10  
Reference 2 received through fieldbus adapter A.  
Reference 2 from fieldbus adapter A.  
-
-100000.00 …  
100000.00  
1 = 10  
Information on warnings and faults that occurred last.  
For explanations of individual warning and fault codes, see  
All parameters in this group are read-only unless otherwise  
noted.  
Code of the 1st active fault (the fault that caused the current  
trip).  
-
0000h…FFFFh  
1st active fault.  
1 = 1  
Code of the 2nd active fault.  
2nd active fault.  
-
0000h…FFFFh  
1 = 1  
-
Code of the 3rd active fault.  
3rd active fault.  
0000h…FFFFh  
1 = 1  
-
Code of the 4th active fault.  
4th active fault.  
0000h…FFFFh  
1 = 1  
                                         
78 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Code of the 5th active fault.  
5th active fault.  
-
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
1 = 1  
05  
Code of the 1st active warning.  
1st active warning.  
-
1 = 1  
Code of the 2nd active warning.  
2nd active warning.  
-
1 = 1  
Code of the 3rd active warning.  
3rd active warning.  
-
1 = 1  
Code of the 4th active warning.  
4th active warning.  
-
1 = 1  
Code of the 5th active warning.  
5th active warning.  
-
1 = 1  
Code of the 1st stored (non-active) fault.  
1st stored fault.  
-
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
1 = 1  
Code of the 2nd stored (non-active) fault.  
2nd stored fault.  
-
1 = 1  
Code of the 3rd stored (non-active) fault.  
3rd stored fault.  
-
1 = 1  
Code of the 4th stored (non-active) fault.  
4th stored fault.  
-
1 = 1  
Code of the 5th stored (non-active) fault.  
5th stored fault.  
-
1 = 1  
Code of the 1st stored (non-active) warning.  
1st stored warning.  
-
1 = 1  
Code of the 2nd stored (non-active) warning.  
2nd stored warning.  
-
1 = 1  
Code of the 3rd stored (non-active) warning.  
3rd stored warning.  
-
1 = 1  
-
Code of the 4th stored (non-active) warning.  
4th stored warning.  
1 = 1  
-
Code of the 5th stored (non-active) warning.  
5th stored warning.  
1 = 1  
Various run-time-type counters and measurements related to  
drive maintenance.  
All parameters in this group are read-only unless otherwise  
noted.  
On-time counter. The counter runs when the drive is  
powered.  
-
0…4294967295 d  
On-time counter.  
1 = 1 d  
-
Motor run-time counter. The counter runs when the inverter  
modulates.  
0…4294967295 d  
Motor run-time counter.  
1 = 1 d  
   
Parameters 79  
No.  
Name/Value  
Description  
Def/FbEq16  
Running time of the drive cooling fan. Can be reset on the  
control panel by keeping Reset depressed for over 3  
seconds.  
-
0…4294967295 d  
Cooling fan run-time counter.  
1 = 1 d  
-
Estimated drive temperature in percent of fault limit.  
-40.0 … 160.0%  
Drive temperature in percent.  
Drive control and status words.  
1 = 1%  
06  
The main control word of the drive. This parameter shows the  
control signals as received from the selected sources (such  
as digital inputs, the fieldbus interface and the application  
program).  
-
The bit assignments of the word are as described on page  
279. The related status word and state diagram are presented  
on pages 280 and 281 respectively.  
This parameter is read-only.  
0000h…FFFFh  
Main control word.  
1 = 1  
-
The drive control word received from the application program  
(if any). The bit assignments are described on page 279.  
This parameter is read-only.  
0000h…FFFFh  
Application program control word.  
1 = 1  
-
The unaltered control word received from the PLC through  
fieldbus adapter A.  
This parameter is read-only.  
00000000h …  
FFFFFFFFh  
Control word received through fieldbus adapter A.  
-
-
Main status word of the drive.  
The bit assignments are described on page 280. The related  
control word and state diagram are presented on pages 279  
and 281 respectively.  
This parameter is read-only.  
0000h…FFFFh  
Main status word.  
1 = 1  
                           
80 Parameters  
No.  
Name/Value  
Drive status word 1 Drive status word 1.  
This parameter is read-only.  
Description  
Def/FbEq16  
-
Bit  
Name  
Description  
0
Enabled  
1 = Both run enable (see par. 20.12) and start enable (20.19) signals are  
present. Note: This bit is not affected by the presence of a fault.  
1
2
3
Inhibited  
1 = Start inhibited. To start the drive, the inhibiting signal (see par. 06.18)  
must be removed and the start signal cycled.  
Operation  
allowed  
1 = Drive is ready to operate  
Ready to  
start  
1 = Drive is ready to receive a start command  
4
Running  
Started  
1 = Drive is ready to follow given reference  
1 = Drive has been started  
5
6
Modulating 1 = Drive is modulating (output stage is being controlled)  
Limiting 1 = Any operating limit (speed, torque, etc.) is active  
7
8
Local control 1 = Drive is in local control  
Network ctrl 1 = Drive is in network control  
Ext1 active 1 = Control location EXT1 active  
Ext2 active 1 = Control location EXT2 active  
9
10  
11  
12…15 Reserved  
0000h…FFFFh  
Status word 1.  
1 = 1  
-
Drive status word 2 Drive status word 2.  
This parameter is read-only.  
Bit  
0
Name  
Description  
Identification run done 1 = Motor identification (ID) run has been performed  
1
Magnetized  
1 = The motor has been magnetized  
1 = Torque control mode active  
1 = Speed control mode active  
1 = Power control mode active  
2
Torque control  
Speed control  
Power control  
3
4
5
Safe reference active 1 = A “safe” reference is applied by functions such as  
parameters 49.05 and 50.02  
6
Last speed active  
Loss of reference  
1 = A “last speed” reference is applied by functions such as  
parameters 49.05 and 50.02  
7
8
1 = Reference signal lost  
Emergency stop failed 1 = Emergency stop failed  
9…15 Reserved  
0000h…FFFFh  
Control status word 1.  
1 = 1  
           
Parameters 81  
No.  
Name/Value  
Description  
Def/FbEq16  
Start inhibit status word. This word specifies the source of the  
inhibiting signal that is preventing the drive from starting.  
The conditions marked with an asterisk (*) only require that  
the start command is cycled. In all other instances, the  
inhibiting condition must be removed first.  
-
See also parameter 06.16 Drive status word 1, bit 1.  
This parameter is read-only.  
Bit  
Name  
Description  
0
Not ready run  
1 = DC voltage is missing or drive has not been parametrized  
correctly. Check the parameters in groups 95 and 99.  
1
2
3
4
5
6
7
8
Ctrl location changed * 1 = Control location has changed  
SSW inhibit  
Fault reset  
1 = Control program is keeping itself in inhibited state  
* 1 = A fault has been reset  
Lost start enable  
Lost run enable  
FSO inhibit  
STO  
1 = Start enable signal missing  
1 = Run enable signal missing  
1 = Operation prevented by FSO-xx safety functions module  
1 = Safe torque off active  
Current calibration  
ended  
* 1 = Current calibration routine has finished  
9
ID run ended  
Auto phase ended  
Em Off1  
* 1 = Motor identification run has finished  
* 1 = Autophasing routine has finished  
1 = Emergency stop signal (mode off1)  
1 = Emergency stop signal (mode off2)  
1 = Emergency stop signal (mode off3)  
1 = The autoreset function is inhibiting operation  
10  
11  
12  
13  
14  
15  
Em Off2  
Em Off3  
Auto reset inhibit  
Reserved  
0000h…FFFFh  
Start inhibit status word.  
1 = 1  
-
Speed control status word.  
This parameter is read-only.  
Bit  
Name  
Description  
0
Zero speed  
1 = Drive is running at zero speed  
1 = Drive is running in forward direction above zero speed limit  
(par. 21.06)  
1
2
3
Forward  
1 = Drive is running in reverse direction above zero speed limit  
(par. 21.06)  
Reverse  
1 = Motor speed outside speed window (see par. group 24  
Out of window  
4
5
6
Internal speed feedback 1 = Estimated speed feedback used (see par. 90.41)  
Encoder 1 feedback  
Encoder 2 feedback  
1 = Encoder 1 used for speed feedback (see par. 90.41)  
1 = Encoder 2 used for speed feedback (see par. 90.41)  
Any constant speed  
request  
7
1 = A constant speed has been selected; see par. 06.20.  
8…15 Reserved  
0000h…FFFFh  
Speed control status word.  
1 = 1  
     
82 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Constant speed status word. Indicates which constant speed  
is active (if any). See also parameter 06.19 Speed control  
-
This parameter is read-only.  
Bit  
0
Name  
Description  
Constant speed 1  
Constant speed 2  
Constant speed 3  
Constant speed 4  
Constant speed 5  
Constant speed 6  
Constant speed 7  
1 = Constant speed 1 selected  
1 = Constant speed 2 selected  
1 = Constant speed 3 selected  
1 = Constant speed 4 selected  
1 = Constant speed 5 selected  
1 = Constant speed 6 selected  
1 = Constant speed 7 selected  
1
2
3
4
5
6
7…15 Reserved  
0000h…FFFFh  
Constant speed status word.  
1 = 1  
07  
User bit 0 selection Selects a binary source whose status is transmitted as bit 11 False  
False  
0.  
1
2
-
True  
1.  
A specific bit in another parameter.  
User bit 1 selection Selects a binary source whose status is transmitted as bit 12 False  
False  
0.  
1
2
-
True  
1.  
A specific bit in another parameter.  
User bit 2 selection Selects a binary source whose status is transmitted as bit 13 False  
False  
0.  
1
2
-
True  
1.  
A specific bit in another parameter.  
User bit 3 selection Selects a binary source whose status is transmitted as bit 14 False  
False  
0.  
1
2
-
True  
1.  
A specific bit in another parameter.  
Drive hardware and firmware information.  
All parameters in this group are read-only.  
Type of the drive/inverter unit.  
Firmware identification.  
-
-
Version number of the firmware.  
Microprocessor load in percent.  
Microprocessor load.  
-
-
0…100%  
1 = 1%  
                                 
Parameters 83  
No.  
10  
Name/Value  
Description  
Def/FbEq16  
Configuration of digital inputs and relay outputs.  
Displays the electrical status of digital inputs DIIL and  
-
DI8…DI1. The activation/deactivation delays of the inputs (if  
any are specified) are ignored.  
Bits 0…5 reflect the status of DI1…DI6; bit 15 reflects the  
status of the DIIL input. Example: 1000000000010011 = DIIL,  
DI5, DI2 and DI1 are on, DI3, DI4 and DI6 are off.  
This parameter is read-only.  
0000h…FFFFh  
Status of digital inputs.  
1 = 1  
-
Displays the status of digital inputs DIIL and DI6…DI1. This  
word is updated only after activation/deactivation delays.  
Bits 0…5 reflect the delayed status of DI1…DI6; bit 15  
reflects the delayed status of the DIIL input.  
This parameter is read-only.  
0000h…FFFFh  
Delayed status of digital inputs.  
1 = 1  
The electrical statuses of the digital inputs can be overridden 0000h  
for eg. testing purposes. A bit in parameter 10.04 DI force  
data is provided for each digital input, and its value is applied  
whenever the corresponding bit in this parameter is 1.  
Bit  
0
Value  
1 = Force DI1 to value of bit 0 of parameter 10.04 DI force data.  
1 = Force DI2 to value of bit 1 of parameter 10.04 DI force data.  
1 = Force DI3 to value of bit 2 of parameter 10.04 DI force data.  
1 = Force DI4 to value of bit 3 of parameter 10.04 DI force data.  
1 = Force DI5 to value of bit 4 of parameter 10.04 DI force data.  
1 = Force DI6 to value of bit 5 of parameter 10.04 DI force data.  
1
2
3
4
5
6…14 Reserved  
15  
1 = Force DIL to value of bit 15 of parameter 10.04 DI force data.  
0000h…FFFFh  
Override selection for digital inputs.  
1 = 1  
Contains the values of digital inputs that are used instead of  
the electrical statuses if selected in parameter 10.03 DI force  
selection. Bit 0 is the forced value for DI1; bit 15 is the forced  
value for the DIIL input.  
0000h  
0000h…FFFFh  
Forced values of digital inputs.  
1 = 1  
0.0 s  
Defines the activation delay for digital input DI1.  
1
*DI status  
0
1
**Delayed DI status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
t
On  
Off  
*Electrical status of digital input. Indicated by 10.01 DI status.  
                         
84 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
10 = 1 s  
0.0 s  
0.0 … 3000.0 s  
Activation delay for DI1.  
Defines the deactivation delay for digital input DI1. See  
0.0 … 3000.0 s  
Deactivation delay for DI1.  
10 = 1 s  
0.0 s  
Defines the activation delay for digital input DI2.  
1
*DI status  
0
1
**Delayed DI status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
On  
t
Off  
*Electrical status of digital input. Indicated by 10.01 DI status.  
0.0 … 3000.0 s  
Activation delay for DI2.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for digital input DI2. See  
0.0 … 3000.0 s  
Deactivation delay for DI2.  
10 = 1 s  
0.0 s  
Defines the activation delay for digital input DI3.  
1
*DI status  
0
1
**Delayed DI status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
On  
t
Off  
*Electrical status of digital input. Indicated by 10.01 DI status.  
0.0 … 3000.0 s  
Activation delay for DI3.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for digital input DI3. See  
0.0 … 3000.0 s  
Deactivation delay for DI3.  
10 = 1 s  
                   
Parameters 85  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the activation delay for digital input DI4.  
0.0 s  
1
*DI status  
0
1
**Delayed DI status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
t
On  
Off  
*Electrical status of digital input. Indicated by 10.01 DI status.  
0.0 … 3000.0 s  
Activation delay for DI4.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for digital input DI4. See  
0.0 … 3000.0 s  
Deactivation delay for DI4.  
10 = 1 s  
0.0 s  
Defines the activation delay for digital input DI5.  
1
*DI status  
0
1
**Delayed DI status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
t
On  
Off  
*Electrical status of digital input. Indicated by 10.01 DI status.  
0.0 … 3000.0 s  
Activation delay for DI5.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for digital input DI5. See  
0.0 … 3000.0 s  
Deactivation delay for DI5.  
10 = 1 s  
               
86 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the activation delay for digital input DI6.  
0.0 s  
1
*DI status  
0
1
**Delayed DI status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
On  
t
Off  
*Electrical status of digital input. Indicated by 10.01 DI status.  
0.0 … 3000.0 s  
Activation delay for DI6.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for digital input DI6. See  
0.0 … 3000.0 s  
Deactivation delay for DI6.  
10 = 1 s  
-
Status of relay outputs RO8…RO1. Example: 00000001b =  
RO1 is energized, RO2…RO8 are de-energized.  
0000h…FFFFh  
Not energized  
Energized  
Ready run  
Enabled  
Status of relay outputs.  
1 = 1  
Selects a drive signal to be connected to relay output RO1.  
Relay output is not energized.  
0
Relay output is energized.  
1
Inverted bit 3 of 06.11 Main status word (see page 79).  
2
4
Started  
5
Magnetized  
Running  
6
7
Ready ref  
At setpoint  
Zero speed  
Neg speed  
Above limit  
Warning  
8
9
10  
11  
12  
13  
14  
15  
22  
Fault  
Fault (-1)  
Open brake  
command  
Ext2 active  
Remote control  
A specific bit in another parameter.  
23  
24  
-
                           
Parameters 87  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the activation delay for relay output RO1.  
0.0 s  
1
Status of selected  
source  
0
1
RO status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
t
On  
Off  
0.0 … 3000.0 s  
Activation delay for RO1.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for relay output RO1. See  
0.0 … 3000.0 s  
Deactivation delay for RO1.  
10 = 1 s  
Selects a drive signal to be connected to relay output RO2.  
For the available selections, see parameter 10.24 RO1  
Defines the activation delay for relay output RO2.  
0.0 s  
1
Status of selected  
source  
0
1
RO status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
t
On  
Off  
0.0 … 3000.0 s  
Activation delay for RO2.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for relay output RO2. See  
0.0 … 3000.0 s  
Deactivation delay for RO2.  
10 = 1 s  
Selects a drive signal to be connected to relay output RO3.  
For the available selections, see parameter 10.24 RO1  
               
88 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the activation delay for relay output RO3.  
0.0 s  
1
Status of selected  
source  
0
1
RO status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
On  
t
Off  
0.0 … 3000.0 s  
Activation delay for RO3.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for relay output RO3. See  
0.0 … 3000.0 s  
Deactivation delay for RO3.  
10 = 1 s  
11  
Configuration of digital input/outputs and frequency  
inputs/outputs.  
Displays the electrical status of digital input/outputs  
DIO8…DIO1. The activation/deactivation delays (if any are  
specified) are ignored.  
-
Example: 0000001001 = DIO1 and DIO4 are on, remainder  
are off.  
This parameter is read-only.  
0000h…FFFFh  
Status of digital input/outputs.  
1 = 1  
-
DIO delayed status Displays the status of digital input/outputs DIO8…DIO1. This  
word is updated only after activation/deactivation (if any)  
delays.  
Example: 0000001001 = DIO1 and DIO4 are on, remainder  
are off.  
This parameter is read-only.  
0000h…FFFFh  
Delayed status of digital input/outputs.  
1 = 1  
DIO1 configuration Selects whether DIO1 is used as a digital output or input, or a Output  
frequency input.  
Output  
DIO1 is used as a digital output.  
DIO1 is used as a digital input.  
DIO1 is used as a frequency input.  
0
Input  
1
Frequency  
2
DIO1 output source Selects a drive signal to be connected to digital input/output  
DIO1 when parameter 11.05 DIO1 configuration is set to  
Not energized  
Energized  
Ready run  
Enabled  
Relay output is not energized.  
0
1
2
4
5
6
7
Relay output is energized.  
Started  
Magnetized  
Running  
                                   
Parameters 89  
No.  
Name/Value  
Ready ref  
At setpoint  
Zero speed  
Neg speed  
Above limit  
Warning  
Description  
Def/FbEq16  
Inverted bit 3 of 06.11 Main status word (see page 79).  
8
9
10  
11  
12  
13  
14  
15  
22  
Fault  
Fault (-1)  
Open brake  
command  
Ext2 active  
A specific bit in another parameter.  
23  
24  
-
Remote control  
Defines the activation delay for digital input/output DIO1  
(when used as a digital output or digital input).  
0.0 s  
1
*DIO status  
0
1
**Delayed DIO status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
t
= 11.08 DIO1 OFF delay  
On  
Off  
*Electrical status of DIO (in input mode) or status of selected source (in output mode). Indicated by 11.01 DIO status.  
0.0 … 3000.0 s  
Activation delay for DIO1.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for digital input/output DIO1  
(when used as a digital output or digital input). See parameter  
0.0 … 3000.0 s  
Deactivation delay for DIO1.  
10 = 1 s  
DIO2 configuration Selects whether DIO2 is used as a digital output or input, or a Output  
frequency output.  
Output  
DIO2 is used as a digital output.  
DIO2 is used as a digital input.  
DIO2 is used as a frequency output.  
0
Input  
1
Frequency  
2
DIO2 output source Selects a drive signal to be connected to digital input/output  
DIO2 when parameter 11.09 DIO2 configuration is set to  
For the available selections, see parameter 11.06 DIO1  
         
90 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the activation delay for digital input/output DIO2  
(when used as a digital output or digital input).  
0.0 s  
1
*DIO status  
0
1
**Delayed DIO status  
0
Time  
t
t
t
t
Off  
On  
Off  
On  
t
On  
t
Off  
*Electrical status of DIO (in input mode) or status of selected source (in output mode). Indicated by 11.01 DIO status.  
0.0 … 3000.0 s  
Activation delay for DIO2.  
10 = 1 s  
0.0 s  
Defines the deactivation delay for digital input/output DIO2  
(when used as a digital output or digital input). See parameter  
0.0 … 3000.0 s  
Deactivation delay for DIO2.  
10 = 1 s  
-
Displays the value of frequency input 1 before scaling. See  
This parameter is read-only.  
0 … 16000 Hz  
Unscaled value of frequency input 1.  
1 = 1 Hz  
-
Displays the value of frequency input 1 after scaling. See  
This parameter is read-only.  
-32768.000 …  
32767.000  
Scaled value of frequency input 1.  
1 = 1  
0 Hz  
Defines the minimum input frequency for frequency input 1  
(DIO1 when it is used as a frequency input).  
The incoming frequency signal (11.38 Freq in 1 actual value)  
is scaled into an internal signal (11.39 Freq in 1 scaled) by  
parameters 11.4211.45 as follows:  
0 … 16000 Hz  
Minimum frequency of frequency input 1 (DIO1).  
1 = 1 Hz  
                   
Parameters 91  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the maximum input frequency for frequency input 1  
(DIO1 when it is used as a frequency input). See parameter  
16000 Hz  
0 … 16000 Hz  
Maximum frequency for frequency input 1 (DIO1).  
1 = 1 Hz  
0.000  
Defines the value that corresponds to the minimum input  
frequency defined by parameter 11.42 Freq in 1 min. See  
diagram at parameter 11.42 Freq in 1 min.  
-32768.000 …  
32767.000  
Value corresponding to minimum of frequency input 1.  
1 = 1  
Defines the value that corresponds to the maximum input  
frequency defined by parameter 11.43 Freq in 1 max. See  
diagram at parameter 11.42 Freq in 1 min.  
1500.000  
-32768.000 …  
32767.000  
Value corresponding to maximum of frequency input 1.  
1 = 1  
-
Displays the value of frequency output 1 after scaling. See  
parameter 11.58 Freq out 1 src min.  
This parameter is read-only.  
0 … 16000 Hz  
Value of frequency output 1.  
1 = 1  
Selects a signal to be connected to frequency output 1.  
Zero  
None.  
0
Motor speed used  
Output frequency  
Motor current  
Motor torque  
1
3
4
6
Dc-voltage  
7
Power inu out  
Speed ref ramp in  
Speed ref ramped  
Speed ref used  
Torq ref used  
Freq ref used  
Process PID out  
Process PID fbk  
Process PID act  
Process PID dev  
Other  
8
23.01 Speed ref ramp in (page 119).  
40.01 Process PID actual value (page 169).  
The value is taken from another parameter.  
10  
11  
12  
13  
14  
16  
17  
18  
19  
-
                 
92 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the real value of the signal (selected by parameter  
out 1 actual value) that corresponds to the minimum value of  
frequency output 1 (defined by parameter 11.60 Freq out 1 at  
0.000  
11.58  
Signal (real)  
selected by  
11.58  
Signal (real)  
selected by  
-32768.000 …  
32767.000  
Real signal value corresponding to minimum value of  
frequency output 1.  
1 = 1  
Freq out 1 src max Defines the real value of the signal (selected by parameter  
out 1 actual value) that corresponds to the maximum value of  
frequency output 1 (defined by parameter 11.61 Freq out 1 at  
src max). See parameter 11.58 Freq out 1 src min.  
1500.000  
-32768.000 …  
32767.000  
Real signal value corresponding to maximum value of  
frequency output 1.  
1 = 1  
0 Hz  
Defines the minimum value of frequency output 1. See  
diagrams at parameter 11.58 Freq out 1 src min.  
0…16000 Hz  
Minimum value of frequency output 1.  
1 = 1 Hz  
Defines the maximum value of frequency output 1. See  
diagrams at parameter 11.58 Freq out 1 src min.  
16000 Hz  
0…16000 Hz  
Maximum value of frequency output 1.  
1 = 1 Hz  
         
Parameters 93  
No.  
12  
Name/Value  
Description  
Def/FbEq16  
Configuration of analog inputs.  
Displays the value of analog input AI1 in mA or V (depending  
on whether the input is set to current or voltage by jumper J1).  
This parameter is read-only.  
-
-22.000 … 22.000  
mA or V  
Value of analog input AI1.  
1000 = 1 mA  
or V  
Displays the value of analog input AI1 after scaling. See  
-
This parameter is read-only.  
-32768.000 …  
32767.000  
Scaled value of analog input AI1.  
1 = 1  
Selects the unit for readings and settings related to analog  
input AI1.  
Note: This setting must match the corresponding jumper  
setting on the drive control unit (see the hardware manual of  
the drive). Control board reboot (either by cycling the power  
or through parameter 96.08 Control board boot) is required to  
validate any changes in the jumper settings.  
V
Volts.  
2
mA  
Milliamperes.  
10  
Defines the filter time constant for analog input AI1.  
0.100 s  
%
Unfiltered signal  
100  
63  
Filtered signal  
t
T
O = I × (1 - e-t/T  
)
I = filter input (step)  
O = filter output  
t = time  
T = filter time constant  
Note: The signal is also filtered due to the signal interface  
hardware (approximately 0.25 ms time constant). This cannot  
be changed by any parameter.  
0.000 … 30.000 s  
Filter time constant.  
1000 = 1 s  
Defines the minimum value for analog input AI1.  
Minimum value of AI1.  
0.0 mA or V  
-22.000 … 22.000  
mA or V  
1000 = 1 mA  
or V  
Defines the maximum value for analog input AI1.  
Maximum value of AI1.  
20.0 mA or V  
-22.000 … 22.000  
mA or V  
1000 = 1 mA  
or V  
                             
94 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the real value that corresponds to the minimum  
analog input AI1 value defined by parameter 12.17 AI1 min.  
0.000  
-32768.000 …  
32767.000  
Real value corresponding to minimum AI1 value.  
1 = 1  
Defines the real value that corresponds to the maximum  
analog input AI1 value defined by parameter 12.18 AI1 max.  
See the drawing at parameter 12.19 AI1 scaled at AI1 min.  
1500.0  
-32768.000 …  
32767.000  
Real value corresponding to maximum AI1 value.  
1 = 1  
-
Displays the value of analog input AI2 in mA or V (depending  
on whether the input is set to current or voltage by jumper J2).  
This parameter is read-only.  
-22.000 … 22.000  
mA or V  
Value of analog input AI2.  
1000 = 1 mA  
or V  
Displays the value of analog input AI2 after scaling. See  
-
This parameter is read-only.  
-32768.000 …  
32767.000  
Scaled value of analog input AI2.  
1 = 1  
Selects the unit for readings and settings related to analog  
input AI2.  
Note: This setting must match the corresponding jumper  
setting on the drive control unit (see the hardware manual of  
the drive). Control board reboot (either by cycling the power  
or through parameter 96.08 Control board boot) is required to  
validate any changes in the jumper settings.  
V
Volts.  
2
mA  
Milliamperes.  
10  
Defines the filter time constant for analog input AI2. See  
0.100 s  
0.000 … 30.000 s  
Filter time constant.  
1000 = 1 s  
Defines the minimum value for analog input AI2.  
0.000 mA or  
V
-22.000 … 22.000  
mA or V  
Minimum value of AI2.  
1000 = 1 mA  
or V  
                   
Parameters 95  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the maximum value for analog input AI2.  
20.000 mA or  
V
-22.000 … 22.000  
mA or V  
Maximum value of AI2.  
1000 = 1 mA  
or V  
Defines the real value that corresponds to the minimum  
analog input AI2 value defined by parameter 12.27 AI2 min.  
0.000  
12.27  
12.28  
-32768.000 …  
32767.000  
Real value corresponding to minimum AI2 value.  
1 = 1  
Defines the real value that corresponds to the maximum  
analog input AI2 value defined by parameter 12.28 AI2 max.  
See the drawing at parameter 12.29 AI2 scaled at AI2 min.  
100.000  
-32768.000 …  
32767.000  
Real value corresponding to maximum AI2 value.  
1 = 1  
13  
Configuration of analog outputs.  
Displays the value of AO1 in mA.  
This parameter is read-only.  
-
0.000 … 22.000 mA Value of AO1.  
1000 = 1 mA  
Selects a signal to be connected to analog output AO1.  
Alternatively, sets the output to excitation mode to feed a  
constant current to a temperature sensor.  
Motor speed  
used  
Zero  
None.  
0
Motor speed used  
Output frequency  
Motor current  
Motor torque  
DC voltage  
23.01 Speed ref ramp in (page 119).  
1
3
4
6
7
Power inu out  
Speed ref ramp in  
8
10  
11  
12  
13  
14  
Speed ref ramp out 23.02 Speed ref ramp out (page 119).  
Speed ref used  
Torq ref used  
Freq ref used  
                       
96 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Process PID out  
Process PID fbk  
Process PID act  
Process PID dev  
40.01 Process PID actual value (page 169).  
16  
17  
18  
19  
Force PT100  
excitation  
The output is used to feed an excitation current to 1…3 Pt100 20  
sensors. See section Motor thermal protection (page 49).  
Force KTY84  
excitation  
The output is used to feed an excitation current to a KTY84  
sensor. See section Motor thermal protection (page 49).  
21  
Other  
The value is taken from another parameter.  
-
Defines the filtering time constant for analog output AO1.  
0.100 s  
%
Unfiltered signal  
100  
63  
Filtered signal  
t
T
O = I × (1 - e-t/T  
)
I = filter input (step)  
O = filter output  
t = time  
T = filter time constant  
0.000 … 30.000 s  
Filter time constant.  
1000 = 1 s  
       
Parameters 97  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the real value of the signal (selected by parameter  
13.12 AO1 source) that corresponds to the minimum AO1  
output value (defined by parameter 13.19 AO1 out at AO1 src  
0.0  
IAO1 (mA)  
Signal (real)  
selectedbypar.  
IAO1 (mA)  
Signal (real)  
selectedbypar.  
-32768.0 …  
32767.0  
Real signal value corresponding to minimum AO1 output  
value.  
1 = 1  
Defines the real value of the signal (selected by parameter  
13.12 AO1 source) that corresponds to the maximum AO1  
output value (defined by parameter 13.20 AO1 out at AO1 src  
1500.0  
-32768.0 …  
32767.0  
Real signal value corresponding to maximum AO1 output  
value.  
1 = 1  
AO1 out at AO1 src Defines the minimum output value for analog output AO1.  
0.000 mA  
See also drawing at parameter 13.17 AO1 source min.  
0.000 … 22.000 mA Minimum AO1 output value.  
1000 = 1 mA  
20.000 mA  
AO1 out at AO1 src Defines the maximum output value for analog output AO1.  
See also drawing at parameter 13.17 AO1 source min.  
0.000 … 22.000 mA Maximum AO1 output value.  
1000 = 1 mA  
-
Displays the value of AO2 in mA.  
This parameter is read-only.  
0.000 … 22.000 mA Value of AO2.  
AO2 source Selects a signal to be connected to analog output AO2.  
1000 = 1 mA  
Alternatively, sets the output to excitation mode to feed a  
constant current to a temperature sensor.  
For the selections, see parameter 13.12 AO1 source.  
                 
98 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the filtering time constant for analog output AO2. See 0.100 s  
0.000 … 30.000 s  
Filter time constant.  
1000 = 1 s  
Defines the real value of the signal (selected by parameter  
13.22 AO2 source) that corresponds to the minimum AO2  
output value (defined by parameter 13.29 AO2 out at AO2 src  
0.0  
IAO2 (mA)  
Signal (real)  
selectedbypar.  
IAO2 (mA)  
Signal (real)  
selectedbypar.  
-32768.0 …  
32767.0  
Real signal value corresponding to minimum AO2 output  
value.  
1 = 1  
Defines the real value of the signal (selected by parameter  
13.22 AO2 source) that corresponds to the maximum AO2  
output value (defined by parameter 13.30 AO2 out at AO2 src  
100.0  
-32768.0 …  
32767.0  
Real signal value corresponding to maximum AO2 output  
value.  
1 = 1  
AO2 out at AO2 src Defines the minimum output value for analog output AO2.  
0.000 mA  
See also drawing at parameter 13.27 AO2 source min.  
0.000 … 22.000 mA Minimum AO2 output value.  
1000 = 1 mA  
20.000 mA  
AO2 out at AO2 src Defines the maximum output value for analog output AO2.  
See also drawing at parameter 13.27 AO2 source min.  
0.000 … 22.000 mA Maximum AO2 output value.  
1000 = 1 mA  
             
Parameters 99  
No.  
19  
Name/Value  
Description  
Def/FbEq16  
Selection of external control location sources and operating  
modes.  
Displays the operation mode currently used.  
See parameters 19.1119.14.  
-
This parameter is read-only.  
Zero  
None.  
1
2
3
4
Speed  
Torque  
Min  
Speed control (in DTC motor control mode).  
Torque control (in DTC motor control mode).  
The torque selector is comparing the output of the speed  
reference (26.74 Torque ref ramped) and the smaller of the  
two is used.  
Max  
The torque selector is comparing the output of the speed  
reference (26.74 Torque ref ramped) and the greater of the  
two is used.  
5
Add  
The speed controller output is added to the torque reference.  
Frequency control in scalar motor control mode.  
Speed control in scalar motor control mode.  
Motor is in magnetizing mode.  
6
Scalar (Hz)  
Scalar (rpm)  
Forced magn.  
10  
11  
20  
Ext1/Ext2 selection Selects the source for external control location EXT1/EXT2  
selection.  
0 = EXT1  
1 = EXT2  
EXT1  
EXT2  
EXT1.  
EXT2.  
0
1
2
MCW bit11: Ext ctrl 06.01 Main control word (page 79), bit 11.  
loc  
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
3
DI2  
4
DI3  
5
DI4  
6
DI5  
7
DI6  
8
DIO1  
DIO2  
11  
12  
-
Ext1 control mode 1 Selects the operating mode for external control location  
Speed  
EXT1.  
Zero  
None.  
1
2
Speed  
Speed control. The torque reference used is 25.01 Torque  
reference speed control (output of the speed reference  
chain).  
Torque  
Torque control. The torque reference used is 26.74 Torque ref  
3
ramped (output of the torque reference chain).  
                         
100 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Minimum  
Combination of selections Speed and Torque: the torque  
selector compares the speed controller output (25.01 Torque  
Torque ref ramped) and selects the smaller of the two.  
If speed error becomes negative, the drive follows the speed  
controller output until speed error becomes positive again.  
This prevents the drive from accelerating uncontrollably if the  
load is lost in torque control.  
4
Maximum  
Combination of selections Speed and Torque: the torque  
selector compares the speed controller output (25.01 Torque  
Torque ref ramped) and selects the greater of the two.  
If speed error becomes positive, the drive follows the speed  
controller output until speed error becomes negative again.  
This prevents the drive from accelerating uncontrollably if the  
load is lost in torque control.  
5
Add  
Combination of selections Speed and Torque: Torque selector  
adds the speed reference chain output to the torque  
reference chain output.  
6
Ext2 control mode 1 Selects the operating mode for external control location  
EXT2.  
Speed  
For the selections, see parameter 19.12 Ext1 control mode 1.  
Local control mode Selects the operating mode for local control.  
Speed  
Speed  
Speed control. The torque reference used is 25.01 Torque  
reference speed control (output of the speed reference  
chain).  
0
Torque  
Torque control. The torque reference used is 26.74 Torque ref  
1
ramped (output of the torque reference chain).  
Enables/disables local control.  
WARNING! Before disabling local control, ensure that  
the control panel is not needed for stopping the drive.  
No  
Local control enabled.  
Local control disabled.  
0
Yes  
1
Selects the reference type for scalar motor control mode.  
See also section Operating modes of the drive (page 20), and  
Hz  
Hz. The reference is taken from parameter 28.02 Frequency  
ref ramped (output of the frequency control chain).  
0
1
Rpm  
Rpm. The reference is taken from parameter 23.02 Speed ref  
ramp out (speed reference after ramping and shaping).  
20  
Start/stop/direction and run/start/jog enable signal source  
selection; positive/negative reference enable signal source  
selection.  
For information on control locations, see section Local control  
Selects the source of start, stop and direction commands for In1 Start; In2  
external control location 1 (EXT1).  
Dir  
See also parameters 20.0220.05.  
Not sel  
No start or stop command sources selected.  
0
                                   
Parameters 101  
No.  
Name/Value  
Description  
Def/FbEq16  
In1 Start  
The source of the start and stop commands is selected by  
parameter 20.03 Ext1 in1. The state transitions of the source  
bits are interpreted as follows:  
1
State of source 1 (20.03) Command  
Start  
0
Stop  
In1 Start; In2 Dir  
The source selected by 20.03 Ext1 in1 is the start signal; the  
source selected by 20.04 Ext1 in2 determines the direction.  
The state transitions of the source bits are interpreted as  
follows:  
2
State of source 1  
State of source 2  
Command  
0
Any  
0
Stop  
Start forward  
Start reverse  
0 -> 1 (20.02 = Edge)  
1
In1 Start fwd; In2  
Start rev  
The source selected by 20.03 Ext1 in1 is the forward start  
signal; the source selected by 20.04 Ext1 in2 is the reverse  
start signal. The state transitions of the source bits are  
interpreted as follows:  
3
State of source 1  
State of source 2  
Command  
Stop  
0
0
0 -> 1 (20.02 = Edge)  
0
Start forward  
0 -> 1 (20.02 = Edge)  
0
1
Start reverse  
Stop  
1
In1P Start; In2 Stop The sources of the start and stop commands are selected by  
parameters 20.03 Ext1 in1 and 20.04 Ext1 in2. The state  
4
transitions of the source bits are interpreted as follows:  
State of source 1  
State of source 2  
Command  
-
0 > 1  
1
0
Start  
Stop  
Any  
Notes:  
• Parameter 20.02 Ext1 start trigger has no effect with this  
setting.  
• When source 2 is 0, the Start and Stop keys on the control  
panel are disabled.  
 
102 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
In1P Start; In2 Stop; The sources of the start and stop commands are selected by  
5
In3 Dir  
parameters 20.03 Ext1 in1 and 20.04 Ext1 in2. The source  
selected by 20.05 Ext1 in3 determines the direction. The  
state transitions of the source bits are interpreted as follows:  
State of  
source 1  
State of  
source 2  
State of  
source 3  
Command  
-
0 > 1  
1
1
0
0
1
Start forward  
Start reverse  
Stop  
-
0 > 1  
Any  
Any  
Notes:  
• Parameter 20.02 Ext1 start trigger has no effect with this  
setting.  
• When source 2 is 0, the Start and Stop keys on the control  
panel are disabled.  
In1P Start fwd; In2P The sources of the start and stop commands are selected by  
6
Start rev; In3 Stop  
in3. The source selected by 20.05 Ext1 in3 determines the  
direction. The state transitions of the source bits are  
interpreted as follows:  
State of  
source 1  
State of  
source 2  
State of  
source 3  
Command  
-
0 > 1  
Any  
1
1
0
Start forward  
Start reverse  
Stop  
-
Any  
Any  
0 > 1  
Any  
Note: Parameter 20.02 Ext1 start trigger has no effect with  
this setting.  
Fieldbus A  
The start and stop commands are taken from fieldbus adapter 12  
A.  
Embedded fieldbus Reserved.  
14  
15  
16  
D2D link  
Reserved.  
Reserved.  
ABB controller  
Application  
Program  
The start and stop commands are taken from the application 21  
program control word (parameter 06.02 Application control  
ATF  
Reserved.  
22  
Defines whether the start signal for external control location  
EXT1 is edge-triggered or level-triggered.  
Note: This parameter is not effective if a pulse-type start  
signal is selected. See the descriptions of the selections of  
Edge  
Level  
Off  
The start signal is edge-triggered.  
0
The start signal is level-triggered.  
1
Selects source 1 for parameter 20.01 Ext1 commands.  
0
0.  
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
2
                     
Parameters 103  
No.  
Name/Value  
DI2  
Description  
Def/FbEq16  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
3
4
5
6
7
DI3  
DI4  
DI5  
DI6  
DIO1  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
10  
11  
-
DIO2  
Selects source 2 for parameter 20.01 Ext1 commands.  
For the available selections, see parameter 20.03 Ext1 in1.  
Selects source 3 for parameter 20.01 Ext1 commands.  
For the available selections, see parameter 20.03 Ext1 in1.  
Selects the source of start, stop and direction commands for Not sel  
external control location 2 (EXT2).  
See also parameters 20.0720.10.  
Not sel  
No start or stop command sources selected.  
0
1
In1 Start  
The source of the start and stop commands is selected by  
parameter 20.08 Ext2 in1. The state transitions of the source  
bits are interpreted as follows:  
State of source 1 (20.08) Command  
Start  
0
Stop  
In1 Start; In2 Dir  
The source selected by 20.08 Ext2 in1 is the start signal; the  
source selected by 20.09 Ext2 in2 determines the direction.  
The state transitions of the source bits are interpreted as  
follows:  
2
State of source 1  
State of source 2  
Command  
0
Any  
0
Stop  
Start forward  
Start reverse  
0 -> 1 (20.07 = Edge)  
1
In1 Start fwd; In2  
Start rev  
The source selected by 20.08 Ext2 in1 is the forward start  
signal; the source selected by 20.09 Ext2 in2 is the reverse  
start signal. The state transitions of the source bits are  
interpreted as follows:  
3
State of source 1  
State of source 2  
Command  
Stop  
0
0
0 -> 1 (20.07 = Edge)  
0
Start forward  
0 -> 1 (20.07 = Edge)  
0
1
Start reverse  
Stop  
1
                                 
104 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
In1P Start; In2 Stop The sources of the start and stop commands are selected by  
4
transitions of the source bits are interpreted as follows:  
State of source 1  
State of source 2  
Command  
-
0 > 1  
1
0
Start  
Stop  
Any  
Notes:  
• Parameter 20.07 Ext2 start trigger has no effect with this  
setting.  
• When source 2 is 0, the Start and Stop keys on the control  
panel are disabled.  
In1P Start; In2 Stop; The sources of the start and stop commands are selected by  
5
In3 Dir  
parameters 20.08 Ext2 in1 and 20.09 Ext2 in2. The source  
selected by 20.10 Ext2 in3 determines the direction. The  
state transitions of the source bits are interpreted as follows:  
State of  
source 1  
State of  
source 2  
State of  
source 3  
Command  
-
0 > 1  
1
1
0
0
1
Start forward  
Start reverse  
Stop  
-
0 > 1  
Any  
Any  
Notes:  
• Parameter 20.07 Ext2 start trigger has no effect with this  
setting.  
• When source 2 is 0, the Start and Stop keys on the control  
panel are disabled.  
In1P Start fwd; In2P The sources of the start and stop commands are selected by  
6
Start rev; In3 Stop  
in3. The source selected by 20.10 Ext2 in3 determines the  
direction. The state transitions of the source bits are  
interpreted as follows:  
State of  
source 1  
State of  
source 2  
State of  
source 3  
Command  
-
0 > 1  
Any  
1
1
0
Start forward  
Start reverse  
Stop  
-
Any  
Any  
0 > 1  
Any  
Note: Parameter 20.07 Ext2 start trigger has no effect with  
this setting.  
Fieldbus A  
The start and stop commands are taken from fieldbus adapter 12  
A.  
Embedded fieldbus Reserved.  
14  
15  
16  
D2D link  
Reserved.  
Reserved.  
ABB controller  
Application  
Program  
The start and stop commands are taken from the application 21  
program control word (parameter 06.02 Application control  
ATF  
Reserved.  
22  
Parameters 105  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines whether the start signal for external control location  
EXT2 is edge-triggered or level-triggered.  
Note: In case the settings of parameters 20.06 and 20.07 are  
in conflict, the setting of parameter 20.06 takes preference.  
Edge  
The start signal is edge-triggered.  
The start signal is level-triggered.  
0
Level  
1
Selects source 1 for parameter 20.06 Ext2 commands.  
For the available selections, see parameter 20.03 Ext1 in1.  
Selects source 2 for parameter 20.06 Ext2 commands.  
For the available selections, see parameter 20.03 Ext1 in1.  
Selects source 3 for parameter 20.06 Ext2 commands.  
For the available selections, see parameter 20.03 Ext1 in1.  
Selects the way the motor is stopped when the run enable  
signal switches off.  
The source of the run enable signal is selected by parameter  
Coast  
Ramp  
Stop by cutting off the motor power supply. The motor coasts  
to a stop.  
0
1
WARNING! If a mechanical brake is used, ensure it is  
safe to stop the drive by coasting.  
Stop along the active deceleration ramp. See parameter  
Torque limit  
Stop according to torque limits (parameters 30.19 and 30.20). 2  
Selects the source of the external run enable signal. If the run On  
enable signal is switched off, the drive will not start. If already  
running, the drive will stop according to the setting of  
1 = Run enable signal on.  
Note: This parameter cannot be changed while the drive is  
running.  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Selects the source for the start enable signal.  
1 = Start enable.  
With the signal switched off, the drive will not start. (Switching  
the signal off while the drive is running will not stop the drive.)  
Off  
On  
0.  
1.  
0
1
                                                     
106 Parameters  
No.  
Name/Value  
DI1  
Description  
Def/FbEq16  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Selects the source of the positive speed enable command.  
1 = Positive speed enabled.  
0 = Positive speed interpreted as zero speed reference. In the  
figure below, 23.01 Speed ref ramp in is set to zero after the  
positive speed enable signal has cleared.  
Actions in different control modes:  
Speed control: Speed reference is set to zero and the motor is  
stopped along the currently active deceleration ramp. The  
rush controller prevents additional torque terms from running  
the motor in the positive direction.  
Torque control: The rush controller monitors the rotation  
direction of the motor.  
23.01 Speed ref ramp in  
Example: The motor is rotating in the forward direction. To  
stop the motor, the positive speed enable signal is  
deactivated by a hardware limit switch (e.g. via digital input).  
If the positive speed enable signal remains deactivated and  
the negative speed enable signal is active, only reverse  
rotation of the motor is allowed.  
Off  
0.  
0
1
2
3
4
5
6
7
On  
1.  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
     
Parameters 107  
No.  
Name/Value  
DIO1  
Description  
Def/FbEq16  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
10  
11  
-
DIO2  
Selects the source of the negative speed reference enable  
command. See parameter 20.23 Positive speed reference  
Selects the source for enabling parameters 20.26 Jogging 1  
1 = Jogging is enabled.  
0 = Jogging is disabled.  
Note: Jogging can be enabled using this parameter only  
when no start command from an external control location is  
active. On the other hand, if jogging is already enabled, the  
drive cannot be started from an external control location apart  
from jog commands through fieldbus.  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
If enabled by parameter 20.25 Jogging enable, selects the  
source for the activation of jogging function 1. (Jogging  
function 1 can also be activated through fieldbus regardless  
of parameter 20.25.)  
1 = Active.  
Notes:  
• The jogging functions can only be used in speed and  
frequency (scalar) control.  
• This parameter cannot be changed while the drive is  
running.  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
                       
108 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
If enabled by parameter 20.25 Jogging enable, selects the  
source for the activation of jogging function 2. (Jogging  
function 2 can also be activated through fieldbus regardless  
of parameter 20.25.)  
1 = Active.  
For the selections, see parameter 20.26 Jogging 1 start.  
Notes:  
• Jogging function 1 has priority over jogging function 2.  
• This parameter cannot be changed while the drive is  
running.  
21  
Start and stop modes; emergency stop mode and signal  
source selection; DC magnetization settings; autophasing  
mode selection.  
Selects the motor start function.  
See also section DC magnetization (page 36).  
Notes:  
• Selections Fast and Const time are ignored if parameter  
99.04 Motor ctrl mode is set to Scalar.  
• Starting to a rotating machine is not possible when DC  
magnetizing is selected (Fast or Const time).  
• With permanent magnet motors, Automatic start mode  
must be used.  
• This parameter cannot be changed while the drive is  
running.  
Fast  
The drive pre-magnetizes the motor before start. The pre-  
magnetizing time is determined automatically, being typically  
200 ms to 2 s depending on motor size. This mode should be  
selected if a high break-away torque is required.  
0
1
Const time  
The drive pre-magnetizes the motor before start. The pre-  
magnetizing time is defined by parameter 21.02  
Magnetization time. This mode should be selected if constant  
pre-magnetizing time is required (e.g. if the motor start must  
be synchronized with the release of a mechanical brake).  
This setting also guarantees the highest possible break-away  
torque when the pre-magnetizing time is set long enough.  
WARNING! The drive will start after the set  
magnetizing time has passed even if motor  
magnetization is not completed. In applications where  
a full break-away torque is essential, ensure that the constant  
magnetizing time is long enough to allow generation of full  
magnetization and torque.  
Automatic  
Automatic start guarantees optimal motor start in most cases.  
It includes the flying start function (starting to a rotating  
machine) and the automatic restart function (a stopped motor  
can be restarted immediately without waiting the motor flux to  
die away). The drive motor control program identifies the flux  
as well as the mechanical state of the motor and starts the  
motor instantly under all conditions.  
2
Note: If parameter 99.04 Motor ctrl mode is set to Scalar, no  
flying start or automatic restart is possible by default.  
                     
Parameters 109  
No.  
Name/Value  
Magnetization time Defines the pre-magnetization time.  
After the start command, the drive automatically  
Description  
Def/FbEq16  
500 ms  
premagnetizes the motor for the set time. To ensure full  
magnetizing, set this parameter to the same value as or  
higher than the rotor time constant. If not known, use the rule-  
of-thumb value given in the table below:  
Motor rated power  
< 1 kW  
Constant magnetizing time  
> 50 to 100 ms  
1 to 10 kW  
> 100 to 200 ms  
10 to 200 kW  
200 to 1000 kW  
> 200 to 1000 ms  
> 1000 to 2000 ms  
Note: This parameter cannot be changed while the drive is  
running.  
0 … 10000 ms  
Constant DC magnetizing time.  
1 = 1 ms  
Selects the way the motor is stopped when a stop command Coast  
is received.  
Coast  
Stop by cutting off the motor power supply. The motor coasts  
to a stop.  
0
1
WARNING! If a mechanical brake is used, ensure it is  
safe to stop the drive by coasting.  
Ramp  
Stop along the active deceleration ramp. See parameter  
Torque limit  
Stop according to torque limits (parameters 30.19 and 30.20). 2  
Selects the way the motor is stopped when an emergency  
stop command is received.  
The source of the emergency stop signal is selected by  
parameter 21.05 Emergency stop source.  
Ramp stop (Off1)  
With the drive running:  
0
• 1 = Normal operation.  
• 0 = Normal stop along the standard deceleration ramp  
defined for the particular reference type (see section  
Reference ramping [page 28]). The drive can be restarted  
by removing the emergency stop signal and switching the  
start signal from 0 to 1.  
With the drive stopped:  
• 1 = Starting allowed.  
• 0 = Starting not allowed.  
Coast stop (Off2)  
With the drive running:  
1
• 1 = Normal operation.  
• 0 = Stop by coasting. The drive can be restarted by  
restoring the start interlock signal and switching the start  
signal from 0 to 1.  
With the drive stopped:  
• 1 = Starting allowed.  
• 0 = Starting not allowed.  
                     
110 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Eme ramp stop  
(Off3)  
With the drive running:  
• 1 = Normal operation  
2
• 0 = Stop by ramping along emergency stop ramp defined  
by parameter 23.23 Emergency stop time. The drive can  
be restarted by removing the emergency stop signal and  
switching the start signal from 0 to 1.  
With the drive stopped:  
• 1 = Starting allowed  
• 0 = Starting not allowed  
Selects the source of the emergency stop signal. The stop  
mode is selected by parameter 21.04 Emergency stop mode. (true)  
Inactive  
0 = Emergency stop active  
1 = Normal operation  
Note: This parameter cannot be changed while the drive is  
running.  
Active (false)  
0.  
0
Inactive (true)  
1.  
1
DIIL  
DIIL input (10.02 DI delayed status, bit 15).  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI1  
3
DI2  
4
DI3  
5
DI4  
6
DI5  
7
DI6  
8
DIO1  
11  
DIO2  
12  
-
Defines the zero speed limit. The motor is stopped along a  
speed ramp until the defined zero speed limit is reached.  
After the zero speed delay, the motor coasts to a stop.  
30.00 rpm  
0.00 … 30000.00  
rpm  
Zero speed limit.  
1 = 1 rpm  
       
Parameters 111  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the delay for the zero speed delay function. The  
0 ms  
function is useful in applications where a smooth and quick  
restarting is essential. During the delay, the drive knows the  
rotor position accurately.  
Without zero speed delay:  
The drive receives a stop command and decelerates along  
a ramp. When actual motor speed falls below the value of  
parameter 21.06 Zero speed limit, inverter modulation is  
stopped and the motor coasts to a standstill.  
Speed  
Speed controller switched off:  
Motor coasts to a stop.  
Time  
With zero speed delay:  
The drive receives a stop command and decelerates along a  
ramp. When actual motor speed falls below the value of  
parameter 21.06 Zero speed limit, the zero speed delay  
function activates. During the delay the function keeps the  
speed controller live: the inverter modulates, motor is  
magnetized and the drive is ready for a quick restart. Zero  
speed delay can be used e.g. with the jogging function.  
Speed  
Speed controller remains  
active. Motor is decelerated to  
true zero speed.  
Time  
Delay  
Zero speed delay.  
0 … 30000 ms  
1 = 1 ms  
112 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Activates/deactivates the DC hold and post-magnetization  
functions. See section DC magnetization (page 36).  
Note: DC magnetization causes the motor to heat up. In  
applications where long DC magnetization times are required,  
externally ventilated motors should be used. If the DC  
magnetization period is long, DC magnetization cannot  
prevent the motor shaft from rotating if a constant load is  
applied to the motor.  
00b  
Bit  
Value  
0
1 = Enable DC hold. See section DC hold (page 36).  
Notes:  
• The DC hold function has no effect if the start signal is switched off.  
• The DC hold function can only be activated in speed control mode.  
• The DC hold function cannot be activated if parameter 99.04 Motor ctrl mode is set to  
Scalar.  
1
1 = Enable post-magnetization. See section Post-magnetization (page 37).  
Note: Post-magnetization is only available when ramping is the selected stop mode (see  
2…15 Reserved  
0000h…FFFFh  
DC magnetization selection.  
1 = 1  
Defines the DC hold speed. See parameter 21.08 DC current 5.0 rpm  
control, and section DC hold (page 36).  
0.0 … 1000.0 rpm  
DC hold speed.  
1 = 1 rpm  
30.0%  
Defines the DC hold current in percent of the motor nominal  
current. See parameter 21.08 DC current control, and section  
0.0 … 100.0%  
DC hold current.  
1 = 1%  
0 ms  
Post magnetization Defines the length of time for which post-magnetization is  
active after stopping the motor. The magnetization current is  
defined by parameter 21.10 DC current reference.  
See parameter 21.08 DC current control.  
0…30000 ms  
Post-magnetization time.  
1 = 1 ms  
Autophasing mode Selects the way autophasing is performed during the ID run. Turning  
See section Autophasing on page 34.  
Turning  
This mode gives the most accurate autophasing result. This  
mode can be used, and is recommended, if the motor is  
allowed to rotate during the ID run and the start-up is not  
time-critical.  
0
Note: This mode will cause the motor to rotate during the ID  
run.  
Standstill 1  
Standstill 2  
Faster than the Turning mode, but not as accurate. The motor  
will not rotate.  
1
2
An alternative standstill autophasing mode that can be used if  
the Turning mode cannot be used, and the Standstill 1 mode  
gives erratic results. However, this mode is considerably  
slower than Standstill 1.  
                           
Parameters 113  
No.  
Name/Value  
Description  
Def/FbEq16  
The motor can be automatically started after a short supply  
power failure using the automatic restart function. See section  
5.0 s  
When this parameter is set to 0.0 seconds, automatic  
restarting is disabled. Otherwise, the parameter defines the  
maximum duration of the power failure after which restarting  
is attempted. Note that this time also includes the DC pre-  
charging delay.  
0.0 s  
Automatic restarting disabled.  
0
0.1 … 5.0 s  
Maximum power failure duration.  
1 = 1 s  
22  
Speed reference selection.  
See the control chain diagrams on pages 288290.  
Speed ref unlimited Displays the output of the speed reference selection block.  
See the control chain diagram on page 289.  
-
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Value of the selected speed reference.  
1 = 1 rpm  
Selects speed reference source 1. See also parameter 22.13 AI1 scaled  
Zero  
None.  
0
AI1 scaled  
AI2 scaled  
FB A ref1  
FB A ref2  
PID  
Fieldbus adapter A reference 1.  
Fieldbus adapter A reference 2.  
1
2
4
5
40.01 Process PID actual value (output of the process PID  
15  
controller).  
Other  
The value is taken from another parameter.  
-
Selects speed reference source 2.  
For the selections, see parameter 22.11 Speed ref1 selection.  
Speed ref1 function Selects a mathematical function between the reference  
sources selected by parameters 22.11 Speed ref1 selection  
and 22.12 Speed ref2 selection. The result is available as  
Ref1  
Ref1  
Add  
Sub  
Signal selected by 22.11 Speed ref1 selection is used as  
speed reference 1 as such.  
0
1
2
The sum of the reference sources is used as speed reference  
1.  
ref2 selection]) of the reference sources is used as speed  
reference 1.  
Mul  
Min  
Max  
The multiplication of the reference sources is used as speed  
reference 1.  
3
4
5
The smaller of the reference sources is used as speed  
reference 1.  
The greater of the reference sources is used as speed  
reference 1.  
                                         
114 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Configures the selection between speed references 1 and 2. Speed  
(The sources for the references are defined by parameters  
respectively.)  
0 = Speed reference 1  
1 = Speed reference 2  
Speed reference 1  
Speed reference 2  
0.  
1.  
0
1
2
MCW bit11: Ext ctrl Bit 11 of 06.01 Main control word (page 79).  
loc  
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
A specific bit in another parameter.  
3
DI2  
4
DI3  
5
DI4  
6
DI5  
7
DI6  
8
DIO1  
DIO2  
11  
12  
-
Additive speed ref1 Defines a reference to be added to the speed reference after Zero  
reference selection (see page 288).  
For the selections, see parameter 22.11 Speed ref1 selection.  
Note: For safety reasons, the additive is not applied when  
any of the stop functions are active.  
Defines the scaling factor for speed reference 1/2 (speed  
reference 1 or 2 is multiplied by the defined value). Speed  
reference 1 or 2 is selected by parameter 22.14 Speed ref1/2  
1.000  
-8.000 …8.000  
Speed reference scaling factor.  
1000 = 1  
Additive speed ref2 Defines a reference to be added to the speed reference after Zero  
the speed share function (see page 288).  
For the selections, see parameter 22.11 Speed ref1 selection.  
Note: For safety reasons, the additive is not applied when  
any of the stop functions are active.  
                     
Parameters 115  
No.  
Name/Value  
Description  
Def/FbEq16  
Determines how constant speeds are selected, and whether 00b  
the rotation direction signal is considered or not when  
applying a constant speed.  
Bit  
Name  
Information  
0
Const speed  
mode  
1 = Packed: 7 constant speeds are selectable using the three sources  
defined by parameters 22.22, 22.23 and 22.24.  
0 = Separate: Constant speeds 1, 2 and 3 are separately activated by  
the sources defined by parameters 22.22, 22.23 and 22.24 respectively.  
In case of conflict, the constant speed with the smaller number takes  
priority.  
1
Dir ena  
1 = Start dir: To determine running direction for a constant speed, the  
sign of the constant speed setting (parameters 22.2622.32) is  
multiplied by the direction signal (forward: +1, reverse: -1). For example,  
if the direction signal is reverse and the active constant speed is  
negative, the drive will run in the forward direction.  
0 = Accord Par: The running direction for the constant speed is  
determined by the sign of the constant speed setting (parameters  
2…15 Reserved  
0000h…FFFFh  
Constant speeds configuration word.  
1 = 1  
When bit 0 of parameter 22.21 Constant speed function is 0  
(Separate), selects a source that activates constant speed 1.  
When bit 0 of parameter 22.21 Constant speed function is 1  
(Packed), this parameter and parameters 22.23 Constant  
sources whose states activate constant speeds as follows:  
Source defined Source defined Source defined  
Constant speed active  
by par. 22.22  
by par. 22.23  
by par. 22.24  
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
None  
Constant speed 1  
Constant speed 2  
Constant speed 3  
Constant speed 4  
Constant speed 5  
Constant speed 6  
Constant speed 7  
Off  
0.  
1.  
0
1
On  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
DIO1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
2
3
4
5
6
7
10  
                         
116 Parameters  
No.  
Name/Value  
DIO2  
Description  
Def/FbEq16  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
11  
-
When bit 0 of parameter 22.21 Constant speed function is 0  
(Separate), selects a source that activates constant speed 2.  
When bit 0 of parameter 22.21 Constant speed function is 1  
(Packed), this parameter and parameters 22.22 Constant  
sources that are used to activate constant speeds. See table  
For the selections, see parameter 22.22 Constant speed sel1.  
When bit 0 of parameter 22.21 Constant speed function is 0  
(Separate), selects a source that activates constant speed 3.  
When bit 0 of parameter 22.21 Constant speed function is 1  
(Packed), this parameter and parameters 22.22 Constant  
sources that are used to activate constant speeds. See table  
For the selections, see parameter 22.22 Constant speed sel1.  
Defines constant speed 1.  
Constant speed 1.  
300.00 rpm  
1 = 1 rpm  
-30000.00 …  
30000.00 rpm  
Defines constant speed 2.  
Constant speed 2.  
0.00 rpm  
1 = 1 rpm  
-30000.00 …  
30000.00 rpm  
Defines constant speed 3.  
Constant speed 3.  
0.00 rpm  
1 = 1 rpm  
-30000.00 …  
30000.00 rpm  
Defines constant speed 4.  
Constant speed 4.  
0.00 rpm  
1 = 1 rpm  
-30000.00 …  
30000.00 rpm  
Defines constant speed 5.  
Constant speed 5.  
0.00 rpm  
1 = 1 rpm  
-30000.00 …  
30000.00 rpm  
Defines constant speed 6.  
Constant speed 6.  
0.00 rpm  
1 = 1 rpm  
-30000.00 …  
30000.00 rpm  
Defines constant speed 7.  
Constant speed 7.  
0.00 rpm  
1 = 1 rpm  
-30000.00 …  
30000.00 rpm  
Defines a safe speed reference that is used with supervision 0.00 rpm  
parameters such as  
-30000.00 …  
30000.00 rpm  
Safe speed reference.  
1 = 1 rpm  
Defines the speed reference for jogging function 1. For more 0.00 rpm  
information on jogging, see page 31.  
-30000.00 …  
30000.00 rpm  
Speed reference for jogging function 1.  
1 = 1 rpm  
                                                   
Parameters 117  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the speed reference for jogging function 2. For more 0.00 rpm  
information on jogging, see page 31.  
-30000.00 …  
30000.00 rpm  
Speed reference for jogging function 2.  
1 = 1 rpm  
00b  
Enables/disables the critical speeds function. Also  
determines whether the specified ranges are effective in both  
rotating directions or not.  
Bit  
Name  
Information  
0
Enable  
1 = Enable: Critical speeds enabled.  
0 = Disable: Critical speeds disabled.  
1
Sign mode  
1 = Signed: The signs of parameters 22.5222.57 are taken into  
account.  
0 = Absolute: Parameters 22.5222.57 are handled as absolute values.  
Each range is effective in both directions of rotation.  
2…15 Reserved  
0000h…FFFFh  
Critical speeds configuration word.  
1 = 1  
Critical speed 1 low Defines the low limit for critical speed range 1.  
Note: This value must be less than or equal to the value of  
0.00 rpm  
-30000.00 …  
30000.00 rpm  
Low limit for critical speed 1.  
1 = 1 rpm  
0.00 rpm  
Defines the high limit for critical speed range 1.  
Note: This value must be greater than or equal to the value of  
-30000.00 …  
30000.00 rpm  
High limit for critical speed 1.  
1 = 1 rpm  
0.00 rpm  
Critical speed 2 low Defines the low limit for critical speed range 2.  
Note: This value must be less than or equal to the value of  
-30000.00 …  
30000.00 rpm  
Low limit for critical speed 2.  
1 = 1 rpm  
0.00 rpm  
Defines the high limit for critical speed range 2.  
Note: This value must be greater than or equal to the value of  
-30000.00 …  
30000.00 rpm  
High limit for critical speed 2.  
1 = 1 rpm  
0.00 rpm  
Critical speed 3 low Defines the low limit for critical speed range 3.  
Note: This value must be less than or equal to the value of  
-30000.00 …  
30000.00 rpm  
Low limit for critical speed 3.  
1 = 1 rpm  
0.00 rpm  
Defines the high limit for critical speed range 3.  
Note: This value must be greater than or equal to the value of  
-30000.00 …  
30000.00 rpm  
High limit for critical speed 3.  
1 = 1 rpm  
                                       
118 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Speed reference 1 Displays the value of speed reference source 1 (selected by  
-
parameter 22.11 Speed ref1 selection). See the control chain  
diagram on page 288.  
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Value of reference source 1.  
1 = 1 rpm  
-
Speed reference 2 Displays the value of speed reference source 2 (selected by  
parameter 22.12 Speed ref2 selection). See the control chain  
diagram on page 288.  
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Value of reference source 2.  
1 = 1 rpm  
-
Speed reference 3 Displays the value of speed reference after the mathematical  
function applied by parameter 22.13 Speed ref1 function and  
reference 1/2 selection (22.14 Speed ref1/2 selection). See  
the control chain diagram on page 288.  
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Speed reference after source selection.  
1 = 1 rpm  
-
Speed reference 4 Displays the value of speed reference after application of 1st  
speed additive (22.15 Additive speed ref1). See the control  
chain diagram on page 288.  
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Speed reference after additive 1.  
1 = 1 rpm  
-
Speed reference 5 Displays the value of speed reference after the application of  
the speed share scaling factor (22.16 Speed share). See the  
control chain diagram on page 288.  
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Speed reference after speed share scaling.  
1 = 1 rpm  
-
Speed reference 6 Displays the value of speed reference after application of 2nd  
speed additive (22.17 Additive speed ref2). See the control  
chain diagram on page 288.  
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Speed reference after additive 2.  
1 = 1 rpm  
-
Speed reference 7 Displays the value of speed reference before application of  
critical speeds. See the control chain diagram on page 289.  
The value is received from 22.86 Speed reference 6 act  
unless overridden by  
• any constant speed  
• a jogging reference  
network control reference  
• control panel reference  
• safe speed reference.  
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Speed reference before application of critical speeds.  
1 = 1 rpm  
           
Parameters 119  
No.  
23  
Name/Value  
Description  
Def/FbEq16  
Speed reference ramp settings.  
See the control chain diagram on page 290.  
Displays the used speed reference before ramping and  
shaping in rpm. See the control chain diagram on page 290.  
This parameter is read-only.  
-
-30000.00 …  
30000.00 rpm  
Speed reference before ramping and shaping.  
1 = 1 rpm  
-
Speed ref ramp out Displays the ramped and shaped speed reference in rpm.  
See the control chain diagram on page 290.  
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Speed reference after ramping and shaping.  
1 = 1 rpm  
Ramp set selection Selects the source that switches between the two sets of  
acceleration/deceleration times defined by parameters  
0 = Acceleration time 1 and deceleration time 1 are in force  
1 = Acceleration time 2 and deceleration time 2 are in force  
Acc/Dec time 1  
0.  
1
Acc/Dec time 2  
1.  
2
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Acceleration time 1 Defines acceleration time 1 as the time required for the speed 20.000 s  
to change from zero to the speed defined by parameter 46.01  
Speed scaling.  
If the speed reference increases faster than the set  
acceleration rate, the motor speed will follow the acceleration  
rate.  
If the speed reference increases slower than the set  
acceleration rate, the motor speed will follow the reference.  
If the acceleration time is set too short, the drive will  
automatically prolong the acceleration in order not to exceed  
the drive torque limits.  
0.000 …1800.000 s Acceleration time 1.  
10 = 1 s  
                             
120 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Deceleration time 1 Defines deceleration time 1 as the time required for the speed 20.000 s  
to change from the speed defined by parameter 46.01 Speed  
scaling to zero.  
If the speed reference decreases slower than the set  
deceleration rate, the motor speed will follow the reference.  
If the reference changes faster than the set deceleration rate,  
the motor speed will follow the deceleration rate.  
If the deceleration rate is set too short, the drive will  
automatically prolong the deceleration in order not to exceed  
drive torque limits. If there is any doubt about the deceleration  
time being too short, ensure that DC overvoltage control is on  
Note: If a short deceleration time is needed for a high inertia  
application, the drive should be equipped with braking  
equipment such as a brake chopper and brake resistor.  
0.000 …1800.000 s Deceleration time 1.  
10 = 1 s  
20.000 s  
Acceleration time 2 Defines acceleration time 2. See parameter 23.12  
0.000 …1800.000 s Acceleration time 2.  
10 = 1 s  
20.000 s  
Deceleration time 2 Defines deceleration time 2. See parameter 23.13  
0.000 …1800.000 s Deceleration time 2.  
10 = 1 s  
     
Parameters 121  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the shape of the acceleration ramp at the beginning  
of the acceleration.  
0.0 s  
0.000 s: Linear ramp. Suitable for steady acceleration or  
deceleration and for slow ramps.  
0.001…1000.000 s: S-curve ramp. S-curve ramps are ideal  
for lifting applications. The S-curve consists of symmetrical  
curves at both ends of the ramp and a linear part in between.  
Acceleration:  
Linear ramp:  
23.17 = 0 s  
Speed  
Linear ramp:  
S-curve ramp:  
23.17 > 0 s  
S-curve ramp:  
23.16 > 0 s  
Time  
Deceleration:  
Speed  
S-curve ramp:  
Linear ramp:  
23.18 = 0 s  
S-curve ramp:  
23.19 > 0 s  
Linear ramp:  
Time  
0.000 …1800.000 s Ramp shape at start of acceleration.  
10 = 1 s  
Defines the shape of the acceleration ramp at the end of the 0.000 s  
acceleration. See parameter 23.16 Shape time acc 1.  
0.000 …1800.000 s Ramp shape at end of acceleration.  
10 = 1 s  
Defines the shape of the deceleration ramp at the beginning 0.000 s  
of the deceleration. See parameter 23.16 Shape time acc 1.  
0.000 …1800.000 s Ramp shape at start of deceleration.  
10 = 1 s  
Defines the shape of the deceleration ramp at the end of the 0.000 s  
deceleration. See parameter 23.16 Shape time acc 1.  
0.000 …1800.000 s Ramp shape at end of deceleration.  
10 = 1 s  
           
122 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the acceleration time for the jogging function i.e. the 60.000 s  
time required for the speed to change from zero to the speed  
value defined by parameter 46.01 Speed scaling.  
See section Jogging (page 31).  
0.000 …1800.000 s Acceleration time for jogging.  
10 = 1 s  
Defines the deceleration time for the jogging function i.e. the 60.000 s  
time required for the speed to change from the speed value  
defined by parameter 46.01 Speed scaling to zero.  
See section Jogging (page 31).  
0.000 …1800.000 s Deceleration time for jogging.  
10 = 1 s  
3.000 s  
Defines the time inside which the drive is stopped if an  
emergency stop Off3 is activated (i.e. the time required for the  
speed to change from the speed value defined by parameter  
46.01 Speed scaling to zero). Emergency stop mode and  
activation source are selected by parameters 21.04  
Emergency stop mode and 21.05 Emergency stop source  
respectively. Emergency stop can also be activated through  
fieldbus.  
Note: Emergency stop Off1 uses the standard deceleration  
ramp as defined by parameters 23.1123.19.  
0.000 …1800.000 s Emergency stop Off3 deceleration time.  
10 = 1 s  
Selects a source that forces the speed reference to zero.  
0 = Force speed reference to zero  
1 = Normal operation  
Active  
Inactive  
DI1  
0.  
0
1.  
1
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Selects the source for enabling/disabling speed reference  
ramp balancing. See parameter 23.27 Ramp out balance ref.  
0 = Disabled  
1 = Enabled  
Off  
0.  
0
1
2
3
4
5
6
7
On  
1.  
DI1  
DI2  
DI3  
DI4  
DI5  
DI6  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
                       
Parameters 123  
No.  
Name/Value  
DIO1  
Description  
Def/FbEq16  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
10  
DIO2  
11  
-
Defines the reference for speed ramp balancing. The output  
of the ramp generator is forced to this value when balancing  
is enabled by parameter 23.26 Ramp out balance enable.  
0.00 rpm  
-30000.00 …  
30000.00 rpm  
Speed ramp balancing reference.  
1 = 1 rpm  
Activates the variable slope function, which controls the slope Off  
of the speed ramp during a speed reference change.  
If the update interval of the signal from an external control  
system and the variable slope rate (23.29 Variable slope rate)  
are equal, speed reference 3 (22.83 Speed reference 3 act) is  
a straight line.  
Speed reference  
Speed  
reference  
t
A
Time  
t = update interval of signal from external control system  
A = speed reference change during t  
This function is only active in remote control.  
Off  
On  
Variable slope disabled.  
0
1
Variable slope enabled (not available in local control).  
Variable slope rate Defines the rate of the speed reference change when variable 50 ms  
slope is enabled by parameter 23.28 Variable slope enable.  
For the best result, enter the reference update interval into  
this parameter.  
2…30000 ms  
Variable slope rate.  
1 = 1 ms  
24  
Speed error calculation; speed error window control  
configuration; speed error step.  
See the control chain diagrams on pages 292 and 293.  
Displays the ramped and corrected speed reference (before  
speed error calculation). See the control chain diagram on  
page 292.  
-
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Speed reference used for speed error calculation.  
1 = 1 rpm  
                 
124 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Used actual speed Displays the speed feedback used for speed error calculation.  
See the control chain diagram on page 292.  
-
This parameter is read-only.  
-30000.00 …  
30000.00 rpm  
Speed feedback used for speed error calculation.  
1 = 1 rpm  
-
Speed error filtered Displays the filtered speed error. See the control chain  
diagram on page 292.  
This parameter is read-only.  
-30000.0 …  
30000.0 rpm  
Filtered speed error.  
1 = 1 rpm  
-
Displays the inverted (unfiltered) speed error. See the control  
chain diagram on page 292.  
This parameter is read-only.  
-30000.0 …  
30000.0 rpm  
Inverted speed error.  
1 = 1 rpm  
0
Defines a speed reference correction. This value is added to  
the existing reference between ramping and limitation. See  
the control chain diagram on page 292.  
-10000…10000  
Speed reference correction.  
1 = 1  
0 ms  
Defines the time constant of the speed error low-pass filter.  
If the used speed reference changes rapidly, the possible  
interferences in the speed measurement can be filtered with  
the speed error filter. Reducing the ripple with filter may cause  
speed controller tuning problems. A long filter time constant  
and fast acceleration time contradict one another. A very long  
filter time results in unstable control.  
0…10000 ms  
Speed error filtering time constant. 0 = filtering disabled.  
1 = 1 ms  
Parameters 125  
No.  
Name/Value  
Description  
Def/FbEq16  
Speed error window Enables or disables speed error window control.  
Speed error window control forms a speed supervision  
function for a torque-controlled drive. It supervises the speed  
error value (speed reference – actual speed). In the normal  
operating range, window control keeps the speed controller  
input at zero. The speed controller is evoked only if the speed  
error exits the speed error window.  
When the speed error moves outside the window, the  
exceeding part of the error value is connected to the speed  
controller. The speed controller produces a reference term  
relative to the input and gain of the speed controller  
(parameter 25.02 Proportional gain) which the torque selector  
adds to the torque reference. The result is used as the  
internal torque reference for the drive.  
The window boundaries are defined by parameters 24.43  
as follows:  
Speed (rpm)  
Reference + [24.44] rpm  
Speed error  
Reference  
window  
Reference - [24.43] rpm  
Forward  
0 rpm  
Reverse  
Reference + [24.43] rpm  
Speed error  
Reference  
window  
Reference - [24.44] rpm  
Note that it is parameter 24.44 (rather than 24.43) that  
defines the overspeed limit in both directions of rotation. This  
is because the function monitors speed error (which is  
negative in case of overspeed, positive in case of  
underspeed).  
Example: In a load loss condition, the internal torque  
reference of the drive is decreased to prevent an excessive  
rise of the motor speed. If window control were inactive, the  
motor speed would rise until a speed limit of the drive were  
reached.  
Disable  
Enable  
Speed error window control inactive.  
Speed error window control active.  
0
1
Speed error window Defines the upper boundary of the speed error window. See  
0 rpm  
0 … 3000 rpm  
Upper boundary of speed error window.  
1 = 1 rpm  
0 rpm  
Speed error window Defines the lower boundary of the speed error window. See  
0 … 3000 rpm  
Lower boundary of speed error window.  
1 = 1 rpm  
             
126 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines an additional speed step given to the input of the  
speed controller (and added to the speed error value).  
0.0 rpm  
-3000.0 … 3000.0  
rpm  
Speed error step.  
10 = 1 rpm  
25  
Speed controller settings.  
See the control chain diagrams on pages 292 and 293.  
Displays the speed controller output that is transferred to the  
torque controller. See the control chain diagram on page 293.  
This parameter is read-only.  
-
-1600.0 … 1600.0% Limited speed controller output torque.  
1 = 1%  
Defines the proportional gain (Kp) of the speed controller. Too 10.00  
high a gain may cause speed oscillation. The figure below  
shows the speed controller output after an error step when  
the error remains constant.  
%
Gain = Kp = 1  
TI = Integration time = 0  
TD= Derivation time = 0  
Error value  
Controller output  
Controller  
output = Kp × e  
e = Error value  
Time  
If gain is set to 1, a 10% change in error value (reference -  
actual value) causes the speed controller output to change by  
10%.  
0.00 …250.00  
Proportional gain for speed controller.  
100 = 1  
           
Parameters 127  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the integration time of the speed controller. The  
2.50 s  
integration time defines the rate at which the controller output  
changes when the error value is constant and the  
proportional gain of the speed controller is 1. The shorter the  
integration time, the faster the continuous error value is  
corrected. Too short an integration time makes the control  
unstable.  
If parameter value is set to zero, the I-part of the controller is  
disabled.  
Anti-windup stops the integrator if the controller output is  
limited.  
The figure below shows the speed controller output after an  
error step when the error remains constant.  
%
Controller output  
Gain = Kp = 1  
TI = Integration time > 0  
TD= Derivation time = 0  
Kp × e  
Kp × e  
e = Error value  
Time  
TI  
0.00 … 1000.00 s  
Integration time for speed controller.  
10 = 1 s  
128 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the derivation time of the speed controller. Derivative 0.000 s  
action boosts the controller output if the error value changes.  
The longer the derivation time, the more the speed controller  
output is boosted during the change. If the derivation time is  
set to zero, the controller works as a PI controller, otherwise  
as a PID controller. The derivation makes the control more  
responsive for disturbances.  
The speed error derivative must be filtered with a low pass  
filter to eliminate disturbances.  
The figure below shows the speed controller output after an  
error step when the error remains constant.  
%
Controller output  
e  
Kp × TD ×  
Ts  
Kp × e  
Error value  
Kp × e  
e = Error value  
Time  
TI  
Gain = Kp = 1  
TI = Integration time > 0  
TD= Derivation time > 0  
Ts= Sample time period = 250 µs  
e = Error value change between two samples  
Note: Changing this parameter value is recommended only if  
a pulse encoder is used.  
0.000 … 10000.000 Derivation time for speed controller.  
s
1000 = 1 s  
8.0 ms  
Derivation filter time Defines the derivation filter time constant. See parameter  
0.0 … 1000.0 ms  
Derivation filter time constant.  
1 = 1 ms  
   
Parameters 129  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the derivation time for acceleration(/deceleration)  
compensation. In order to compensate inertia during  
acceleration, a derivative of the reference is added to the  
output of the speed controller. The principle of a derivative  
action is described under parameter 25.04 Derivation time.  
Note: As a general rule, set this parameter to the value  
between 50 and 100% of the sum of the mechanical time  
constants of the motor and the driven machine.  
0.00 s  
The figure below shows the speed responses when a high  
inertia load is accelerated along a ramp.  
No acceleration compensation:  
Speed reference  
Actual speed  
Time  
Acceleration compensation:  
Speed reference  
Actual speed  
Time  
0.00 … 1000.00 s  
Acceleration compensation derivation time.  
10 = 1 s  
Acc comp filter time Defines the acceleration (or deceleration) compensation filter 8.0 ms  
time constant.. See parameters 25.04 Derivation time and  
0.0 … 1000.0 ms  
Acceleration/deceleration compensation filter time.  
1 = 1 ms  
   
130 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the droop rate in percent of the nominal motor speed. 0.00%  
Drooping decreases the drive speed slightly as the drive load  
increases. The actual speed decrease at a certain operating  
point depends on the droop rate setting and the drive load (=  
torque reference / speed controller output). At 100% speed  
controller output, drooping is at its nominal level, i.e. equal to  
the value of this parameter. The drooping effect decreases  
linearly to zero along with the decreasing load.  
The droop rate can be used e.g. to adjust the load sharing in  
a Master/Follower application run by several drives. In a  
Master/Follower application the motor shafts are coupled to  
each other.  
The correct droop rate for a process must be found out case  
by case in practice.  
Speed decrease = Speed controller output × Drooping × Nominal speed  
Example: Speed controller output is 50%, droop rate is 1%, nominal speed of the drive is  
1500 rpm.  
Speed decrease = 0.50 × 0.01 × 1500 rpm = 7.5 rpm.  
Motor speed in  
% of nominal  
No drooping  
100%  
D
roop  
ing  
Speed controller  
output / %  
Drive load  
100%  
0.00 … 100.00%  
Droop rate.  
100 = 1%  
Speed ctrl balance Selects the source for enabling/disabling speed controller  
output balancing. See parameter 25.10 Speed ctrl balance  
0 = Disabled  
1 = Enabled  
Off  
0.  
1
On  
1.  
2
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
         
Parameters 131  
No.  
Name/Value  
Description  
Def/FbEq16  
Speed ctrl balance Defines the reference used in speed controller output  
0
balancing. The output of the speed controller is forced to this  
value when balancing is enabled by parameter 25.09 Speed  
In order to guarantee smooth operation during output  
balancing, the D-part of the speed controller is disabled and  
the acceleration compensation term is set to zero.  
-300 … 300  
Speed control output balancing reference.  
1 = 1  
Defines the minimum speed controller output torque.  
-300.0%  
-1600.0 … 0.0%  
Minimum speed controller output torque.  
1 = 1%  
300.0%  
Defines the maximum speed controller output torque.  
0.0 … 1600.0%  
Maximum speed controller output torque.  
1 = 1%  
Defines the proportional gain for the speed controller when an 10.00  
emergency stop is active. See parameter 25.02 Proportional  
0.00 … 250.00  
Proportional gain upon an emergency stop.  
100 = 1  
26  
Displays the output of the proportional (P) part of the speed  
controller. See the control chain diagram on page 293.  
This parameter is read-only.  
-
-30000.0 …  
30000.0%  
P-part output of speed controller.  
1 = 1%  
-
Displays the output of the integral (I) part of the speed  
controller. See the control chain diagram on page 293.  
This parameter is read-only.  
-30000.0 …  
30000.0%  
I-part output of speed controller.  
1 = 1%  
-
Displays the output of the derivative (D) part of the speed  
controller. See the control chain diagram on page 293.  
This parameter is read-only.  
-30000.0 …  
30000.0%  
D-part output of speed controller.  
1 = 1%  
-
Displays the output of the acceleration compensation  
function. See the control chain diagram on page 293.  
This parameter is read-only.  
-30000.0 …  
30000.0%  
Output of acceleration compensation function.  
1 = 1%  
-
Displays the acceleration-compensated output of the speed  
controller. See the control chain diagram on page 293.  
This parameter is read-only.  
-30000.0 …  
30000.0%  
Acceleration-compensated output of speed controller.  
1 = 1%  
Settings of the torque reference chain.  
See the control chain diagrams on pages 294 and 296.  
Displays the torque reference given to the torque controller in  
percent. See the control chain diagram on page 296.  
This parameter is read-only.  
-
-1600.0 … 1600.0% Torque reference for torque control.  
10 = 1%  
                 
132 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Displays the torque reference after frequency, voltage and  
torque limitation in percent of motor nominal torque. See the  
control chain diagram on page 297.  
-
This parameter is read-only.  
-1600.0 … 1600.0% Torque reference for torque control.  
10 = 1%  
-300.0%  
10 = 1%  
300.0%  
10 = 1%  
Minimum torque ref Defines the minimum torque reference.  
-1000.0 … 0.0%  
Minimum torque reference.  
Maximum torque ref Defines the maximum torque reference.  
0.0 … 1000.0%  
Maximum torque reference.  
Selects torque reference source 1. See also parameter 26.13 Zero  
Zero  
None.  
0
AI1 scaled  
AI2 scaled  
FB A ref1  
FB A ref2  
PID  
1
2
4
5
40.01 Process PID actual value (output of the process PID  
15  
controller).  
Other  
The value is taken from another parameter.  
-
Selects torque reference source 2. See also parameter 26.13 Zero  
For the available selections, see parameter 26.11 Torque ref1  
Torque ref1 function Selects a mathematical function between the reference  
sources selected by parameters 26.11 Torque ref1 selection  
and 26.12 Torque ref2 selection. The result of the function is  
then selectable as torque reference 1 in parameter 26.14  
Ref 1  
Signal selected by 26.11 Torque ref1 selection is used as  
torque reference 1 as such.  
0
1
2
Add  
The sum of the reference sources is used as torque reference  
1.  
Sub  
ref2 selection]) of the reference sources is used as torque  
reference 1.  
Mul  
Min  
Max  
The multiplication of the reference sources is used as torque  
reference 1.  
3
4
5
The smaller of the reference sources is used as torque  
reference 1.  
The greater of the reference sources is used as torque  
reference 1.  
Configures the selection between torque references 1 and 2. Torque  
(The sources of the references are defined by parameters  
respectively.)  
0 = Torque reference 1  
1 = Torque reference 2  
Torque reference 1 0.  
Torque reference 2 1.  
0
1
                                         
Parameters 133  
No.  
Name/Value  
Description  
Source selection (see Terms and abbreviations on page 73).  
Def/FbEq16  
-
Defines the scaling factor for the torque reference (the torque 1.000  
reference is multiplied by the value).  
-8.000 … 8.000  
Torque reference scaling factor.  
1000 = 1  
Selects the source for torque reference additive 1.  
Note: For safety reasons, the additive is not applied when an  
emergency stop is active.  
See the control chain diagram on page 294.  
Zero  
None.  
0
AI1 scaled  
AI2 scaled  
FB A ref1  
FB A ref2  
PID  
1
2
4
5
40.01 Process PID actual value (output of the process PID  
15  
controller).  
Other  
The value is taken from another parameter.  
-
Torque ref filter time Defines a low-pass filter time constant for the torque  
0.000 s  
reference.  
0.000 … 30.000 s  
Filter time constant for torque reference.  
1000 = 1 s  
Defines the torque reference ramp-up time, ie. the time for the 0.000 s  
reference to increase from zero to nominal motor torque.  
0.000 … 60.000 s  
Torque reference ramp-up time.  
100 = 1 s  
Torque ramp down Defines the torque reference ramp-down time, ie. the time for 0.000 s  
the reference to decrease from nominal motor torque to zero.  
0.000 … 60.000 s  
Torque reference ramp-down time.  
100 = 1 s  
Selects the source of torque reference additive 2.  
The value received from the selected source is added to the  
torque reference after operating mode selection. Because of  
this, the additive can be used in speed and torque modes.  
Note: For safety reasons, the additive is not applied when an  
emergency stop is active.  
See the control chain diagram on page 296.  
Zero  
None.  
0
AI1 scaled  
AI2 scaled  
FB A ref1  
FB A ref2  
PID  
1
2
4
5
40.01 Process PID actual value (output of the process PID  
15  
controller).  
Other  
The value is taken from another parameter.  
-
Selects a source that forces torque reference additive 2 (see Off  
0 = Normal operation  
1 = Force torque reference additive 2 to zero.  
Off  
On  
DI1  
0.  
0
1
2
1.  
Digital input DI1 (10.02 DI delayed status, bit 0).  
             
134 Parameters  
No.  
Name/Value  
DI2  
Description  
Def/FbEq16  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
10  
11  
-
DIO2  
When enabled by parameter 26.42 Torque step enable, adds 0.00%  
an additional step to the torque reference.  
-300.00 … 300.00% Torque step.  
100 = 1%  
Torque step enable Enables a torque step (defined by parameter 26.41 Torque  
Disable  
Torque step disabled.  
Torque step enabled.  
0
1
-
Enable  
Displays the value of torque reference source 1 (selected by  
parameter 26.11 Torque ref1 selection). See the control chain  
diagram on page 294.  
This parameter is read-only.  
-1600.0 … 1600.0% Value of torque reference source 1.  
Torque ref2 actual Displays the value of torque reference source 2 (selected by  
10 = 1%  
-
parameter 26.12 Torque ref2 selection). See the control chain  
diagram on page 294.  
This parameter is read-only.  
-1600.0 … 1600.0% Value of torque reference source 2.  
10 = 1%  
-
Torque ref3 actual Displays the torque reference after the function applied by  
parameter 26.13 Torque ref1 function (if any), and after  
selection (26.14 Torque ref1/2 selection). See the control  
chain diagram on page 294.  
This parameter is read-only.  
-1600.0 … 1600.0% Torque reference after selection.  
10 = 1%  
-
Torque ref4 actual Displays the torque reference after application of reference  
additive 1. See the control chain diagram on page 294.  
This parameter is read-only.  
-1600.0 … 1600.0% Torque reference after application of reference additive A.  
10 = 1%  
-
Displays the torque reference after limiting and ramping. See  
the control chain diagram on page 294.  
This parameter is read-only.  
-1600.0 … 1600.0% Torque reference after limiting and ramping.  
10 = 1%  
-
Torque ref5 actual Displays the torque reference after control mode selection.  
See the control chain diagram on page 296.  
This parameter is read-only.  
-1600.0 … 1600.0% Torque reference after control mode selection.  
10 = 1%  
-
Displays the torque reference after application of reference  
additive 2. See the control chain diagram on page 296.  
This parameter is read-only.  
-1600.0 … 1600.0% Torque reference after application of reference additive 2.  
10 = 1%  
                 
Parameters 135  
No.  
Name/Value  
Description  
Def/FbEq16  
Displays the value of the source of torque reference additive  
2. See the control chain diagram on page 296.  
This parameter is read-only.  
-
-1600.0 … 1600.0% Torque reference additive 2.  
10 = 1%  
-
Displays the value of torque reference additive 2 before it is  
added to torque reference. See the control chain diagram on  
page 296.  
This parameter is read-only.  
-1600.0 … 1600.0% Torque reference additive 2.  
10 = 1%  
10.0  
Rush controller gain term.  
Rush controller gain.  
1.0 …10000.0  
1 = 1  
Rush controller integration time term.  
2.0 s  
0.1 …10.0 s  
Rush controller integration time.  
1 = 1 s  
28  
Settings of the frequency reference chain.  
See the control chain diagrams on pages 298 and 299.  
Frequency ref ramp Displays the used frequency reference before ramping. See  
-
the control chain diagram on page 299.  
This parameter is read-only.  
-3000.0 … 3000.0  
Hz  
Frequency reference before ramping.  
10 = 1 Hz  
-
Displays the final frequency reference (after selection,  
limitation and ramping). See the control chain diagram on  
page 299.  
This parameter is read-only.  
-3000.0 … 3000.0  
Hz  
Final frequency reference.  
10 = 1 Hz  
Selects frequency reference source 1. See also parameter  
Zero  
None.  
0
AI1 scaled  
AI2 scaled  
FB A ref1  
FB A ref2  
PID  
1
2
4
5
40.01 Process PID actual value (output of the process PID  
15  
controller).  
Other  
The value is taken from another parameter.  
-
Selects frequency reference source 2. See also parameter  
For the selections, see parameter 28.11 Frequency ref1  
Selects a mathematical function between the reference  
sources selected by parameters 28.11 Frequency ref1  
the function is then selectable as frequency reference 1 in  
Ref1  
Signal selected by 28.11 Frequency ref1 selection is used as  
0
frequency reference 1 as such.  
                             
136 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Add  
The sum of the reference sources is used as frequency  
reference 1.  
1
Sub  
Frequency ref2 selection]) of the reference sources is used  
as frequency reference 1.  
2
Mul  
Min  
Max  
The multiplication of the reference sources is used as  
frequency reference 1.  
3
4
5
The smaller of the reference sources is used as frequency  
reference 1.  
The greater of the reference sources is used as frequency  
reference 1.  
Configures the selection between frequency references 1 and Frequency  
2. (The sources of the references are defined by parameters reference 1  
selection respectively.)  
0 = Frequency reference 1  
1 = Frequency reference 2  
Frequency  
reference 1  
0.  
0
1
Frequency  
reference 2  
1.  
Source selection (see Terms and abbreviations on page 73).  
-
Constant frequency Determines how constant frequencies are selected, and  
00b  
whether the rotation direction signal is considered or not  
when applying a constant frequency.  
Bit  
Name  
Information  
0
Const freq  
mode  
1 = Packed: 7 constant frequencies are selectable using the three  
sources defined by parameters 28.22, 28.23 and 28.24.  
0 = Separate: Constant frequencies 1, 2 and 3 are separately activated  
by the sources defined by parameters 28.22, 28.23 and 28.24  
respectively. In case of conflict, the constant frequency with the smaller  
number takes priority.  
1
Dir ena  
1 = Start dir: To determine running direction for a constant frequency, the  
sign of the constant frequency setting (parameters 28.2628.32) is  
multiplied by the direction signal (forward: +1, reverse: -1). For example,  
if the direction signal is reverse and the active constant frequency is  
negative, the drive will run in the forward direction.  
0 = According to par: The running direction for the constant frequency is  
determined by the sign of the constant speed setting (parameters  
0000h…FFFFh  
Constant speeds configuration word.  
1 = 1  
         
Parameters 137  
No.  
Name/Value  
Description  
Def/FbEq16  
0 (Separate), selects a source that activates constant  
frequency 1.  
1 (Packed), this parameter and parameters 28.23 Constant  
three sources whose states activate constant frequencies as  
follows:  
Source defined Source defined Source defined  
Constant frequency  
active  
by par. 28.22  
by par. 28.23  
by par. 28.24  
0
1
0
1
0
1
0
1
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
None  
Constant frequency 1  
Constant frequency 2  
Constant frequency 3  
Constant frequency 4  
Constant frequency 5  
Constant frequency 6  
Constant frequency 7  
Off  
0.  
1.  
0
1
On  
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
0 (Separate), selects a source that activates constant  
frequency 2.  
1 (Packed), this parameter and parameters 28.22 Constant  
three sources that are used to activate constant frequencies.  
See table at parameter 28.22 Constant frequency sel1.  
For the selections, see parameter 28.22 Constant frequency  
0 (Separate), selects a source that activates constant  
frequency 3.  
1 (Packed), this parameter and parameters 28.22 Constant  
three sources that are used to activate constant frequencies.  
See table at parameter 28.22 Constant frequency sel1.  
For the selections, see parameter 28.22 Constant frequency  
             
138 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Constant frequency Defines constant frequency 1.  
0 Hz  
-3000.00 …  
3000.00 Hz  
Constant frequency 1.  
10 = 1 Hz  
0 Hz  
Constant frequency Defines constant frequency 2.  
-3000.00 …  
3000.00 Hz  
Constant frequency 2.  
10 = 1 Hz  
0 Hz  
Constant frequency Defines constant frequency 3.  
-3000.00 …  
3000.00 Hz  
Constant frequency 3.  
10 = 1 Hz  
0 Hz  
Constant frequency Defines constant frequency 4.  
-3000.00 …  
3000.00 Hz  
Constant frequency 4.  
10 = 1 Hz  
0 Hz  
Constant frequency Defines constant frequency 5.  
-3000.00 …  
3000.00 Hz  
Constant frequency 5.  
10 = 1 Hz  
0 Hz  
Constant frequency Defines constant frequency 6.  
-3000.00 …  
3000.00 Hz  
Constant frequency 6.  
10 = 1 Hz  
0 Hz  
Constant frequency Defines constant frequency 7.  
-3000.00 …  
3000.00 Hz  
Constant frequency 7.  
10 = 1 Hz  
0 Hz  
Defines a safe frequency reference that is used with  
supervision parameters such as  
-3000…3000 Hz  
Safe frequency reference.  
10 = 1 Hz  
00b  
Enables/disables the critical frequencies function. Also  
determines whether the specified ranges are effective in both  
rotating directions or not.  
Bit  
Name  
Information  
0
Crit freq  
1 = Enable: Critical frequencies enabled.  
0 = Disable: Critical frequencies disabled.  
1
Sign mode  
1 = According to par: The signs of parameters 28.5228.57 are taken  
into account.  
0 = Absolute: Parameters 28.5228.57 are handled as absolute values.  
Each range is effective in both directions of rotation.  
0000h…FFFFh  
Critical frequencies configuration word.  
1 = 1  
       
Parameters 139  
No.  
Name/Value  
Description  
Def/FbEq16  
Critical frequency 1 Defines the low limit for critical frequency 1.  
0.0 Hz  
Note: This value must be less than or equal to the value of  
-3000.00 …  
3000.00 Hz  
Low limit for critical frequency 1.  
10 = 1 Hz  
0.0 Hz  
Critical frequency 1 Defines the high limit for critical frequency 1.  
Note: This value must be greater than or equal to the value of  
-3000.00 …  
3000.00 Hz  
High limit for critical frequency 1.  
10 = 1 Hz  
0.0 Hz  
Critical frequency 2 Defines the low limit for critical frequency 2.  
Note: This value must be less than or equal to the value of  
-3000.00 …  
3000.00 Hz  
Low limit for critical frequency 2.  
10 = 1 Hz  
0.0 Hz  
Critical frequency 2 Defines the high limit for critical frequency 2.  
Note: This value must be greater than or equal to the value of  
-3000.00 …  
3000.00 Hz  
High limit for critical frequency 2.  
10 = 1 Hz  
0.0 Hz  
Critical frequency 3 Defines the low limit for critical frequency 3.  
Note: This value must be less than or equal to the value of  
-3000.00 …  
3000.00 Hz  
Low limit for critical frequency 3.  
10 = 1 Hz  
0.0 Hz  
Critical frequency 3 Defines the high limit for critical frequency 3.  
Note: This value must be greater than or equal to the value of  
-3000.00 …  
3000.00 Hz  
High limit for critical frequency 3.  
10 = 1 Hz  
Ramp set selection Selects a source that switches between the two sets of  
acceleration/deceleration times defined by parameters  
0 = Acceleration time 1 and deceleration time 1 are in force  
1 = Acceleration time 2 and deceleration time 2 are in force  
Acc/Dec time 1  
0.  
0
Acc/Dec time 2  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
                           
140 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Acceleration time 1 Defines acceleration time 1 as the time required for the  
frequency to change from zero to the frequency defined by  
parameter 46.02 Frequency scaling.  
20.000 s  
If the reference increases faster than the set acceleration  
rate, the motor will follow the acceleration rate.  
If the reference increases slower than the set acceleration  
rate, the motor frequency will follow the reference.  
If the acceleration time is set too short, the drive will  
automatically prolong the acceleration in order not to exceed  
the drive torque limits.  
0.000 … 1800.000 Acceleration time 1.  
s
10 = 1 s  
20.000 s  
Deceleration time 1 Defines deceleration time 1 as the time required for the  
frequency to change from the frequency defined by  
parameter 46.02 Frequency scaling to zero.  
If there is any doubt about the deceleration time being too  
short, ensure that DC overvoltage control (30.30 Overvoltage  
control) is on.  
Note: If a short deceleration time is needed for a high inertia  
application, the drive should be equipped with braking  
equipment such as a brake chopper and brake resistor.  
0.000 … 1800.000 Deceleration time 1.  
s
10 = 1 s  
60.000 s  
10 = 1 s  
60.000 s  
10 = 1 s  
Acceleration time 2 Defines acceleration time 2. See parameter 28.72  
0.000 … 1800.000 Acceleration time 2.  
s
Deceleration time 2 Defines deceleration time 2. See parameter 28.73  
0.000 … 1800.000 Deceleration time 2.  
s
Selects a source that forces the frequency reference to zero. Inactive  
0 = Force frequency reference to zero  
1 = Normal operation  
Active  
Inactive  
DI1  
0.  
0
1.  
1
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Selects a source that forces the output of the frequency ramp Inactive  
generator to actual frequency value.  
0 = Force ramp output to actual frequency  
1 = Normal operation  
Active  
0.  
0
             
Parameters 141  
No.  
Name/Value  
Inactive  
DI1  
Description  
Def/FbEq16  
1.  
1
2
3
4
5
6
7
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
DI2  
DI3  
DI4  
DI5  
DI6  
DIO1  
DIO2  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
10  
11  
-
Defines a reference for frequency ramp balancing. The output 0.0 Hz  
of the ramp generator is forced to this value when balancing  
is enabled by parameter 28.79 Ramp output balance ena.  
-3000.00 …  
3000.00 Hz  
Frequency ramp balancing reference.  
10 = 1 Hz  
Selects the source for enabling/disabling speed ramp  
balancing. See parameter 28.78 Ramp output balance.  
0 = Disabled  
1 = Enabled  
Off  
0.  
On  
1.  
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Frequency ref ramp Selects the signal source for the frequency ramp generator  
input.  
Not selected  
Freq ref unlimited  
Other  
None.  
0
-
The value is taken from another parameter.  
Selects the signal that is used as a frequency reference in  
scalar control.  
Not selected  
None.  
0
1
Frequency ref  
ramped  
28.02 Frequency ref ramped, ie. the frequency control chain.  
Other  
The value is taken from another parameter.  
-
             
142 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Frequency ref1 act Displays the value of frequency reference source 1 (selected  
by parameter 28.11 Frequency ref1 selection). See the  
control chain diagram on page 298.  
-
This parameter is read-only.  
-3000.00 …  
3000.00 Hz  
Value of frequency reference source 1.  
10 = 1 Hz  
-
Frequency ref2 act Displays the value of frequency reference source 2 (selected  
by parameter 28.12 Frequency ref2 selection). See the  
control chain diagram on page 298.  
This parameter is read-only.  
-3000.00 …  
3000.00 Hz  
Value of frequency reference source 2.  
10 = 1 Hz  
-
Frequency ref3 act Displays the frequency reference after the function applied by  
parameter 28.13 Frequency ref1 function (if any), and after  
selection (28.14 Frequency ref1/2 selection). See the control  
chain diagram on page 298.  
This parameter is read-only.  
-3000.00 …  
3000.00 Hz  
Frequency reference after selection.  
10 = 1 Hz  
-
Frequency ref7 act Displays the frequency reference after application of constant  
frequencies, control panel reference, etc. See the control  
chain diagram on page 298.  
This parameter is read-only.  
-3000.00 …  
3000.00 Hz  
Frequency reference 7.  
10 = 1 Hz  
-
Displays the frequency reference after application of critical  
frequencies, but before ramping and limiting. See the control  
chain diagram on page 299.  
This parameter is read-only.  
-3000.00 …  
3000.00 Hz  
Frequency reference before ramping and limiting.  
10 = 1 Hz  
     
Parameters 143  
No.  
30  
Name/Value  
Description  
Def/FbEq16  
Drive operation limits.  
Displays limit word 1.  
-
This parameter is read-only.  
Bit  
Name  
Description  
0
Torq lim  
1 = Drive torque is being limited by the motor control (undervoltage  
control, current control, load angle control or pull-out control), or by the  
torque limits defined by parameters.  
1
2
Spd ctl tlim min 1 = Speed controller output is being limited by 25.11 Min torque speed  
Spd ctl tlim max 1 = Speed controller output is being limited by 25.12 Max torque speed  
3
4
5
Torq ref max  
Torq ref min  
1 = Torque reference is being limited by 26.09 Maximum torque ref  
1 = Torque reference is being limited by 26.08 Minimum torque ref  
Tlim max speed 1 = Torque reference is being limited by the rush control because of  
maximum speed limit (30.12 Maximum speed)  
6
Tlim min speed 1 = Torque reference is being limited by the rush control because of  
minimum speed limit (30.11 Minimum speed)  
7
Max speed ref lim 1 = Speed reference is being limited by 30.12 Maximum speed  
Min speed ref lim 1 = Speed reference is being limited by 30.11 Minimum speed  
Max freq ref lim 1 = Frequency reference is being limited by 30.14 Maximum frequency  
8
9
10  
Min freq ref lim  
1 = Frequency reference is being limited by 30.13 Minimum frequency  
11…15 Reserved  
0000h…FFFFh  
Limit word 1.  
1 = 1  
   
144 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Displays the torque controller limitation status word.  
This parameter is read-only.  
-
Bit  
0
Name  
Description  
Undervoltage  
Overvoltage  
*1 = Intermediate DC circuit undervoltage  
*1 = Intermediate DC circuit overvoltage  
1
2
Minimum torque *1 = Torque is being limited by 30.19 Minimum torque  
3
Maximum torque *1 = Torque is being limited by 30.20 Maximum torque  
4
Internal current 1 = An inverter current limit (identified by bits 8…11) is active  
5
Load angle  
(With permanent magnet motors and reluctance motors only)  
1 = Load angle limit is active, ie. the motor cannot produce any more  
torque  
6
Motor pullout  
(With asynchronous motors only)  
Motor pull-out limit is active, ie. the motor cannot produce anymore  
torque  
7
Reserved  
8
Thermal  
1 = Input current is being limited by the main circuit thermal limit  
*1 = Maximum output current (IMAX) is being limited  
9
SOA current  
User current  
Thermal IGBT  
10  
11  
*1 = Output current is being limited by 30.17 Maximum current  
*1 = Output current is being limited by a calculated thermal current  
value  
12…15 Reserved  
*Only one out of bits 0…3, and one out of bits 9…11 can be on simultaneously. The bit typically  
indicates the limit that is exceeded first.  
0000h…FFFFh  
Torque limitation status word.  
1 = 1  
Defines the minimum allowed speed.  
WARNING! This value must not be higher than 30.12  
-1500.00 rpm  
WARNING! In frequency control mode, this limit is not  
effective. Make sure the frequency limits (30.13 and  
30.14) are set appropriately if frequency control is  
used.  
-30000.00 …  
30000.00 rpm  
Minimum allowed speed.  
1 = 1 rpm  
Defines the maximum allowed speed.  
WARNING! This value must not be lower than 30.11  
1500.00 rpm  
WARNING! In frequency control mode, this limit is not  
effective. Make sure the frequency limits (30.13 and  
30.14) are set appropriately if frequency control is  
used.  
-30000.00 …  
30000.00 rpm  
Maximum speed.  
1 = 1 rpm  
-50.0 Hz  
Minimum frequency Defines the minimum allowed frequency.  
WARNING! This value must not be higher than 30.14  
-3000.00 …  
3000.00 Hz  
Minimum frequency.  
10 = 1 Hz  
                   
Parameters 145  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the maximum allowed frequency.  
50 Hz  
WARNING! This value must not be lower than 30.13  
-3000.00 …  
3000.00 Hz  
Maximum frequency.  
10 = 1 Hz  
Defines the maximum allowed motor current.  
0.00 A  
0.00 … 30000.00 A Maximum motor current.  
Minimum torque Defines the minimum torque limit for the drive (in percent of  
nominal motor torque).  
-1600.0 … 1600.0% Minimum torque.  
1 = 1 A  
-300.0%  
1 = 1%  
Defines the maximum torque limit for the drive (in percent of 300.0%  
nominal motor torque).  
-1600.0 … 1600.0% Maximum torque.  
1 = 1%  
Defines the maximum allowed power fed by the inverter to the 300.00%  
motor in percent of nominal motor power.  
0.00 … 600.00%  
Maximum motoring power.  
1 = 1%  
Defines the maximum allowed power fed by the motor to the -300.00%  
inverter in percent of nominal motor power.  
-600.00 … 0.00%  
Maximum generating power.  
1 = 1%  
Overvoltage control Enables the overvoltage control of the intermediate DC link.  
Fast braking of a high inertia load causes the voltage to rise  
to the overvoltage control limit. To prevent the DC voltage  
from exceeding the limit, the overvoltage controller  
automatically decreases the braking torque.  
Enable  
Note: If the drive is equipped with a brake chopper and  
resistor, or a regenerative supply unit, the controller must be  
disabled.  
Disable  
Enable  
Overvoltage control disabled.  
Overvoltage control enabled.  
0
1
Enables the undervoltage control of the intermediate DC link. Enable  
If the DC voltage drops due to input power cut off, the  
undervoltage controller will automatically decrease the motor  
torque in order to keep the voltage above the lower limit. By  
decreasing the motor torque, the inertia of the load will cause  
regeneration back to the drive, keeping the DC link charged  
and preventing an undervoltage trip until the motor coasts to  
a stop. This will act as a power-loss ride-through functionality  
in systems with high inertia, such as a centrifuge or a fan.  
Disable  
Enable  
Undervoltage control disabled.  
Undervoltage control enabled.  
0
1
31  
Settings that define the behavior of the drive upon fault  
situations.  
Defines the source of external event 1. See also parameter  
0 = Trigger event  
1 = Normal operation  
Inactive (true)  
Active (false)  
DIIL  
1.  
0
1
2
0.  
DIIL input (10.02 DI delayed status, bit 15).  
                                           
146 Parameters  
No.  
Name/Value  
DI1  
Description  
Def/FbEq16  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
Selects the type of external event 1.  
3
DI2  
4
DI3  
5
DI4  
6
DI5  
7
DI6  
8
DIO1  
DIO2  
11  
12  
-
Fault  
The external event generates a fault.  
The external event generates a warning.  
0
1
Warning  
Selects the source of an external fault reset signal. The signal DI3  
resets the drive after a fault trip if the cause of the fault no  
longer exists.  
0 - 1 = Reset  
>
Note: A fault reset from the fieldbus interface is always  
observed regardless of this parameter.  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
                 
Parameters 147  
No.  
Name/Value  
Description  
Def/FbEq16  
Selects faults that are automatically reset. The parameter is a 0000h  
16-bit word with each bit corresponding to a fault type.  
Whenever a bit is set to 1, the corresponding fault is  
automatically reset.  
Note: The autoreset function is only available in external  
control; see section Local control vs. external control (page  
The bits of the binary number correspond to the following  
faults:  
Bit  
0
Fault  
Overcurrent  
Overvoltage  
1
2
Undervoltage  
3
AI < Min  
4…9  
10  
11  
Reserved  
Selectable fault (see parameter 31.13 Selectable fault)  
External fault 1 (from source selected by parameter 31.01 External event 1 source)  
12…15 Reserved  
0000h…FFFFh  
Automatic reset configuration word.  
1 = 1  
0
Defines the fault that can be automatically reset using  
parameter 31.12 Autoreset sel, bit 10. The code is given in  
decimal.  
The faults are listed in chapter Fault tracing (page 253).  
0…65535  
Fault code.  
10 = 1  
0
Defines the number of automatic fault resets the drive  
performs within the time defined by parameter 31.15 Trial  
0…5  
Number of automatic resets.  
10 = 1  
30.0 s  
Defines the time for the automatic reset function. See  
1.0 … 600.0 s  
Time for automatic resets.  
10 = 1 s  
0.0 s  
Defines the time that the drive will wait after a fault before  
attempting an automatic reset. See parameter 31.12  
0.0 … 120.0 s  
Autoreset delay.  
10 = 1 s  
Selects how the drive reacts when a motor phase loss is  
detected.  
Fault  
No  
No action taken.  
0
Fault  
The drive trips on fault 3381 Output phase loss.  
Selects how the drive reacts when an earth fault or current  
unbalance is detected in the motor or the motor cable.  
Fault  
No  
No action taken.  
0
Warning  
The drive generates an A2B3 Earth leakage warning.  
The drive trips on fault 2330 Earth leakage.  
1
Fault  
Selects how the drive reacts when a supply phase loss is  
detected.  
Fault  
No  
No action taken.  
0
                               
148 Parameters  
No.  
Name/Value  
Fault  
Description  
Def/FbEq16  
The drive trips on fault 3130 Input phase loss.  
Selects how the drive reacts when it detects the absence of  
one or both Safe torque off (STO) signals.  
Fault  
Note: This parameter only affects the supervision of the Safe  
torque off (STO) function. The STO operates regardless of  
the setting of this parameter: a running drive will stop upon  
STO activation, and will not start until both STO signals are  
restored and all faults reset.  
For more information on the STO, see the Hardware manual  
of the drive.  
Fault  
If only one of the STO signals is lost, the drive generates a  
off 1 or FA82 Safe torque off 2 fault. If both signals are lost,  
the drive only generates a 5091 Safe torque off fault.  
0
1
Warning  
Drive running:  
If only one of the STO signals is lost, the drive generates a  
off 1 or FA82 Safe torque off 2 fault. If both signals are lost,  
the drive only generates a 5091 Safe torque off fault.  
Drive stopped:  
If only one of the STO signals is lost, the drive generates a  
together with an A5A0 Safe torque off warning. If both signals  
are lost, the drive only generates an A5A0 Safe torque off  
warning.  
No  
Drive running:  
2
If only one of the STO signals is lost, the drive generates a  
off 1 or FA82 Safe torque off 2 fault. If both signals are lost,  
the drive only generates a 5091 Safe torque off fault.  
Drive stopped:  
If only one of the STO signals is lost, the drive trips on FA81  
lost, no action is taken.  
Only warning  
If only one of the STO signals is lost, the drive generates a  
together with an A5A0 Safe torque off warning. If both signals  
are lost, the drive only generates an A5A0 Safe torque off  
warning.  
3
Selects how the drive reacts to incorrect input power and  
motor cable connection (i.e. input power cable is connected  
to drive motor connection).  
Fault  
No  
No action taken.  
0
Fault  
The drive trips on fault 3181 Cross connection.  
Selects how the drive reacts to a motor stall condition.  
A stall condition is defined as follows:  
• The drive is at stall current limit (31.25 Stall current limit),  
and  
• the output frequency is below the level set by parameter  
31.27 Stall frequency high or the motor speed is below the  
level set by parameter 31.26 Stall speed high, and  
• the conditions above have been valid longer than the time  
set by parameter 31.28 Stall time.  
No  
None (stall supervision disabled).  
0
                 
Parameters 149  
No.  
Name/Value  
Warning  
Description  
Def/FbEq16  
The drive generates an A780 Motor stall warning.  
The drive trips on fault 7121 Motor stall.  
1
Fault  
Stall current limit in percent of the nominal current of the  
200.0%  
motor. See parameter 31.24 Stall function.  
0.0 … 1600.0%  
Stall current limit.  
-
Stall speed limit in rpm. See parameter 31.24 Stall function.  
150.0 rpm  
-
0.0 … 10000.0 rpm Stall speed limit.  
Stall frequency high Stall frequency limit. See parameter 31.24 Stall function.  
15.0 Hz  
Note: Setting the limit below 10 Hz is not recommended.  
0.0 … 1000.0 Hz  
Stall frequency limit.  
-
Stall time. See parameter 31.24 Stall function.  
Stall time.  
20 s  
0 … 3600 s  
-
Defines, together with 30.11 Minimum speed and 30.12  
Maximum speed, the maximum allowed speed of the motor  
(overspeed protection). If actual speed (01.01 Motor speed  
used) exceeds the speed limit defined by parameter 30.11 or  
30.12 by more than the value of this parameter, the drive trips  
on the 7310 Overspeed fault.  
500 rpm  
WARNING! This function only supervises the speed  
reference in DTC motor control mode. The function is  
not effective with other reference types or in scalar  
motor control mode.  
Example: If the maximum speed is 1420 rpm and speed trip  
margin is 300 rpm, the drive trips at 1720 rpm.  
Speed  
Overspeed trip level  
0
Time  
Overspeed trip level  
0…10000 rpm  
Overspeed trip margin.  
1 = 1 rpm  
                       
150 Parameters  
No.  
32  
Name/Value  
Description  
Def/FbEq16  
Configuration of signal supervision functions 1…3.  
Three values can be chosen to be monitored; a warning or  
fault is generated whenever predefined limits are exceeded.  
See also section Signal supervision (page 54).  
Signal supervision status word.  
000b  
Indicates whether the values monitored by the signal  
supervision functions are within or outside their respective  
limits.  
Note: This word is independent of the drive actions defined  
by parameters 32.06, 32.16 and 32.26.  
Bit  
0
Name  
Description  
Supervision 1 active  
Supervision 2 active  
Supervision 3 active  
1 = Signal selected by 32.07 is outside its limits.  
1 = Signal selected by 32.17 is outside its limits.  
1 = Signal selected by 32.27 is outside its limits.  
1
2
3…15 Reserved  
000…111b  
Signal supervision status word.  
1 = 1  
Selects the mode of signal supervision function 1. Determines Disabled  
how the monitored signal (see parameter 32.07) is compared  
to its lower and upper limits (32.09 and 32.10 respectively).  
The action to be taken when the condition is fulfilled is  
selected by 32.06.  
Disabled  
Low  
Signal supervision 1 not in use.  
0
1
2
Action is taken whenever the signal falls below its lower limit.  
High  
Action is taken whenever the signal rises above its upper  
limit.  
Abs Low  
Abs High  
Both  
Action is taken whenever the absolute value of the signal falls  
below its (absolute) lower limit.  
3
4
5
6
Action is taken whenever the absolute value of the signal  
rises above its (absolute) upper limit.  
Action is taken whenever the signal falls below its low limit or  
rises above its high limit.  
Abs Both  
Action is taken whenever the absolute value of the signal falls  
below its (absolute) low limit or rises above its (absolute) high  
limit.  
Selects the action the drive takes when the value monitored  
by signal supervision 1 exceeds its limits.  
Note: This parameter does not affect the status indicated by  
No  
No action taken.  
0
Warning  
Fault  
A warning (A8B0 Signal supervision) is generated.  
The drive trips on 80B0 Signal supervision.  
1
Selects the signal to be monitored by signal supervision  
function 1.  
Zero  
None.  
0
1
2
3
Speed  
Frequency  
Current  
                               
Parameters 151  
No.  
Name/Value  
Torque  
Description  
Def/FbEq16  
23.01 Speed ref ramp in (page 119).  
4
DC voltage  
Output power  
AI1  
5
6
7
AI2  
8
Speed ref ramp in  
15  
Speed ref ramp out 23.02 Speed ref ramp out (page 119).  
16  
Speed ref used  
Torque ref used  
Freq ref used  
17  
18  
19  
Process PID output 40.01 Process PID actual value (page 169).  
20  
Feedback act value 40.02 Feedback actual value (page 169).  
21  
Other  
The value is taken from another parameter.  
Defines the filter time constant for signal supervision 1.  
Signal filter time.  
-
0.000 … 30.000 s  
0.000 s  
1000 = 1 s  
0.00  
Defines the lower limit for signal supervision 1.  
Low limit.  
-21474836.48 …  
21474836.47  
-
Defines the upper limit for signal supervision 1.  
Upper limit.  
0.00  
-
-21474836.48 …  
21474836.47  
Selects the mode of signal supervision function 2. Determines Disabled  
how the monitored signal (see parameter 32.17) is compared  
to its lower and upper limits (32.19 and 32.20 respectively).  
The action to be taken when the condition is fulfilled is  
selected by 32.16.  
Disabled  
Low  
Signal supervision 2 not in use.  
0
1
2
Action is taken whenever the signal falls below its lower limit.  
High  
Action is taken whenever the signal rises above its upper  
limit.  
Abs Low  
Abs High  
Both  
Action is taken whenever the absolute value of the signal falls  
below its (absolute) lower limit.  
3
4
5
6
Action is taken whenever the absolute value of the signal  
rises above its (absolute) upper limit.  
Action is taken whenever the signal falls below its low limit or  
rises above its high limit.  
Abs Both  
Action is taken whenever the absolute value of the signal falls  
below its (absolute) low limit or rises above its (absolute) high  
limit.  
Selects the action the drive takes when the value monitored  
by signal supervision 2 exceeds its limits.  
Note: This parameter does not affect the status indicated by  
No  
No action taken.  
0
1
Warning  
Fault  
A warning (A8B0 Signal supervision) is generated.  
The drive trips on 80B0 Signal supervision.  
             
152 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Selects the signal to be monitored by signal supervision  
function 2.  
For the available selections, see parameter 32.07 Superv1  
0.000 … 30.000 s  
Defines the filter time constant for signal supervision 2.  
Signal filter time.  
0.000 s  
1000 = 1 s  
0.00  
Defines the lower limit for signal supervision 2.  
Low limit.  
-21474836.48 …  
21474836.47  
-
Defines the upper limit for signal supervision 2.  
Upper limit.  
0.00  
-
-21474836.48 …  
21474836.47  
Selects the mode of signal supervision function 3. Determines Disabled  
how the monitored signal (see parameter 32.27) is compared  
to its lower and upper limits (32.29 and 32.30 respectively).  
The action to be taken when the condition is fulfilled is  
selected by 32.26.  
Disabled  
Low  
Signal supervision 3 not in use.  
0
1
2
Action is taken whenever the signal falls below its lower limit.  
High  
Action is taken whenever the signal rises above its upper  
limit.  
Abs Low  
Abs High  
Both  
Action is taken whenever the absolute value of the signal falls  
below its (absolute) lower limit.  
3
4
5
6
Action is taken whenever the absolute value of the signal  
rises above its (absolute) upper limit.  
Action is taken whenever the signal falls below its low limit or  
rises above its high limit.  
Abs Both  
Action is taken whenever the absolute value of the signal falls  
below its (absolute) low limit or rises above its (absolute) high  
limit.  
Selects the action the drive takes when the value monitored  
by signal supervision 3 exceeds its limits.  
Note: This parameter does not affect the status indicated by  
No  
No action taken.  
0
Warning  
Fault  
A warning (A8B0 Signal supervision) is generated.  
The drive trips on 80B0 Signal supervision.  
1
Selects the signal to be monitored by signal supervision  
function 3.  
For the available selections, see parameter 32.07 Superv1  
0.000 … 30.000 s  
Defines the filter time constant for signal supervision 3.  
Signal filter time.  
0.000 s  
1000 = 1 s  
0.00  
Defines the lower limit for signal supervision 3.  
Low limit.  
-21474836.48 …  
21474836.47  
-
                       
Parameters 153  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the upper limit for signal supervision 3.  
Upper limit.  
0.00  
-
-21474836.48 …  
21474836.47  
33  
Configuration of maintenance timers/counters.  
Displays the maintenance timer/counter status word,  
indicating which maintenance timers/counters have exceeded  
their limits.  
-
This parameter is read-only.  
Bit  
0
Name  
Description  
On-time1  
On-time2  
Edge 1  
Edge 2  
Value 1  
Value 2  
1 = On-time timer 1 has reached its preset limit.  
1 = On-time timer 2 has reached its preset limit.  
1 = Signal edge counter 1 has reached its preset limit.  
1 = Signal edge counter 2 has reached its preset limit.  
1 = Value counter 1 has reached its preset limit.  
1 = Value counter 2 has reached its preset limit.  
1
2
3
4
5
6…15 Reserved  
0000h…FFFFh  
Maintenance time/counter status word.  
1 = 1  
-
Reading of on-time timer 1. Can be reset on the control panel  
by keeping Reset depressed for over 3 seconds.  
0…4294967295 s  
Reading of on-time timer 1.  
-
Sets the warning limit for on-time timer 1.  
Warning limit for on-time counter 1.  
-
0…4294967295 s  
-
Configures on-time timer 1. This timer runs whenever the  
signal selected by parameter 33.13 On-time 1 source is on.  
After the limit set by 33.11 On-time 1 limit is reached, the  
warning specified by 33.14 On-time 1 warning select is given  
(if enabled by this parameter), and the timer reset.  
The current value of the timer is readable from parameter  
indicates that the time has exceeded the limit.  
00b  
Bit  
Function  
0
Counter mode  
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds  
1 = Saturate: If warning is enabled by bit 1, it stays active until reset  
1
Warning enable  
0 = Disable: No warning is given when the limit is reached  
1 = Enable: A warning is given when the limit is reached  
2…15 Reserved  
0000h…FFFFh  
False  
On-time timer 1 configuration word.  
Selects the signal to be monitored by on-time timer 1.  
Constant 0.  
1 = 1  
0
1
2
True  
Constant 1.  
RO1  
                             
154 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Source selection (see Terms and abbreviations on page 73).  
Selects the warning message for on-time timer 1.  
-
On-time 1  
Pre-selectable warning message for on-time timer 1.  
Pre-selectable warning message for on-time timer 1.  
Pre-selectable warning message for on-time timer 1.  
0
6
7
Device clean  
Additional cooling  
fan  
Cabinet fan  
Pre-selectable warning message for on-time timer 1.  
Pre-selectable warning message for on-time timer 1.  
Pre-selectable warning message for on-time timer 1.  
8
DC-capacitor  
Motor bearing  
9
10  
-
Reading of on-time timer 2. Can be reset on the control panel  
by keeping Reset depressed for over 3 seconds.  
0…4294967295 s  
Reading of on-time timer 2.  
-
Sets the warning limit for on-time timer 2.  
Warning limit for on-time counter 2.  
0 s  
-
0…4294967295 s  
Configures on-time timer 2. This timer runs whenever the  
signal selected by parameter 33.23 On-time 2 source is on.  
After the limit set by 33.21 On-time 2 limit is reached, the  
warning specified by 33.24 On-time 2 warning select is given  
(if enabled by this parameter), and the timer reset.  
The current value of the timer is readable from parameter  
indicates that the time has exceeded the limit.  
00b  
Bit  
Function  
0
Counter mode  
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds  
1 = Saturate: If warning is enabled by bit 1, it stays active until reset  
1
Warning enable  
0 = Disable: No warning is given when the limit is reached  
1 = Enable: A warning is given when the limit is reached  
2…15 Reserved  
0000h…FFFFh  
False  
On-time timer 2 configuration word.  
Selects the signal to be monitored by on-time timer 2.  
Constant 0.  
1 = 1  
0
True  
Constant 1.  
1
RO1  
Source selection (see Terms and abbreviations on page 73).  
Selects the warning message for on-time timer 2.  
2
-
On-time 2  
Pre-selectable warning message for on-time timer 2.  
Pre-selectable warning message for on-time timer 2.  
Pre-selectable warning message for on-time timer 2.  
Pre-selectable warning message for on-time timer 2.  
Pre-selectable warning message for on-time timer 2.  
Pre-selectable warning message for on-time timer 2.  
1
Device clean  
Additional cool fan  
Cabinet fan  
6
7
8
DC-capacitor  
Motor bearing  
9
10  
                                     
Parameters 155  
No.  
Name/Value  
Description  
Def/FbEq16  
Reading of signal edge counter 1. Can be reset on the control  
panel by keeping Reset depressed for over 3 seconds.  
-
0…4294967295  
Reading of signal edge counter 1.  
-
Edge counter 1 limit Sets the warning limit for signal edge counter 1.  
0…4294967295 Warning limit for signal edge counter 1.  
0
-
Edge counter 1 func Configures signal edge counter 1. This counter is  
incremented every time the signal selected by parameter  
33.33 Edge counter 1 source switches on or off (or either,  
depending on the setting of this parameter). A divisor may be  
applied to the count (see 33.34 Edge counter 1 divider).  
After the limit set by 33.31 Edge counter 1 limit is reached,  
the warning specified by 33.35 Edge counter 1 warning  
selection is given (if enabled by this parameter), and the  
counter reset.  
0000b  
The current value of the counter is readable from parameter  
indicates that the count has exceeded the limit.  
Bit  
Function  
0
Counter mode  
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds  
1 = Saturate: If warning is enabled by bit 1, it stays active until reset  
1
2
3
Warning enable  
0 = Disable: No warning is given when the limit is reached  
1 = Enable: A warning is given when the limit is reached  
Count rising edges  
0 = Disable: Rising edges are not counted  
1 = Enable: Rising edges are counted  
Count falling edges  
0 = Disable: Falling edges are not counted  
1 = Enable: Falling edges are counted  
4…15 Reserved  
0000h…FFFFh  
Edge counter 1 configuration word.  
1 = 1  
Selects the signal to be monitored by signal edge counter 1. False  
False  
Constant 0.  
0
1
2
-
True  
Constant 1.  
RO1  
Source selection (see Terms and abbreviations on page 73).  
Divisor for signal edge counter 1. Determines how many  
signal edges increment the counter by 1.  
1
1…4294967295  
Divisor for signal edge counter 1.  
-
Selects the warning message for signal edge counter 1.  
Edge counter 1  
Main contactor  
Output relay  
Motor starts  
Power ups  
Pre-selectable warning message for signal edge counter 1.  
Pre-selectable warning message for signal edge counter 1.  
Pre-selectable warning message for signal edge counter 1.  
Pre-selectable warning message for signal edge counter 1.  
Pre-selectable warning message for signal edge counter 1.  
2
11  
12  
13  
14  
                               
156 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
DC-charge  
Pre-selectable warning message for signal edge counter 1.  
15  
-
Reading of signal edge counter 2. Can be reset on the control  
panel by keeping Reset depressed for over 3 seconds.  
0…4294967295  
Reading of signal edge counter 2.  
-
Edge counter 2 limit Sets the warning limit for signal edge counter 2.  
0
0…4294967295  
Warning limit for signal edge counter 2.  
-
Configures signal edge counter 2. This counter is  
incremented every time the signal selected by parameter  
33.43 Edge counter 2 source switches on or off (or either,  
depending on the setting of this parameter). A divisor may be  
applied to the count (see 33.44 Edge counter 2 divider).  
After the limit set by 33.41 Edge counter 2 limit is reached,  
the warning specified by 33.45 Edge counter 2 warning  
selection is given (if enabled by this parameter), and the  
counter reset.  
0000b  
The current value of the counter is readable from parameter  
indicates that the count has exceeded the limit.  
Bit  
Function  
Counter mode  
0
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds  
1 = Saturate: If warning is enabled by bit 1, it stays active until reset  
1
2
3
Warning enable  
0 = Disable: No warning is given when the limit is reached  
1 = Enable: A warning is given when the limit is reached  
Count rising edges  
0 = Disable: Rising edges are not counted  
1 = Enable: Rising edges are counted  
Count falling edges  
0 = Disable: Falling edges are not counted  
1 = Enable: Falling edges are counted  
4…15 Reserved  
0000h…FFFFh  
Edge counter 2 configuration word.  
1 = 1  
Selects the signal to be monitored by signal edge counter 2. False  
False  
0.  
0
1
2
-
True  
1.  
RO1  
Source selection (see Terms and abbreviations on page 73).  
Divisor for signal edge counter 2. Determines how many  
signal edges increment the counter by 1.  
1
1…4294967295  
Divisor for signal edge counter 2.  
-
Selects the warning message for signal edge counter 2.  
Edge counter 2  
Main contactor  
Output relay  
Pre-selectable warning message for signal edge counter 2.  
Pre-selectable warning message for signal edge counter 2.  
Pre-selectable warning message for signal edge counter 2.  
Pre-selectable warning message for signal edge counter 2.  
3
11  
12  
13  
Motor starts  
                               
Parameters 157  
No.  
Name/Value  
Power ups  
DC-charge  
Description  
Def/FbEq16  
Pre-selectable warning message for signal edge counter 2.  
Pre-selectable warning message for signal edge counter 2.  
14  
15  
-
Reading of value counter 1. Can be reset on the control panel  
by keeping Reset depressed for over 3 seconds.  
-2147483008 …  
2147483008  
Reading of value counter 1.  
-
Sets the warning limit for value counter 1.  
Warning limit for value counter 1.  
0
-2147483008 …  
2147483008  
-
Configures value counter 1. This counter measures, by  
integration, the area below the signal selected by parameter  
33.53 Value counter 1 source. A divisor may be applied to  
When the total area exceeds the limit set by parameter 33.51  
Value counter 1 limit, the warning specified by 33.55 Value  
counter 1 warning select is given (if enabled by this  
parameter).  
00b  
The signal is sampled at 1-second intervals. Note that the  
scaled (see the “Def/FbEq16column at the signal in  
question) value is used.  
The current value of the counter is readable from parameter  
indicates that the count has exceeded the limit.  
Bit  
Function  
Counter mode  
0
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds  
1 = Saturate: If warning is enabled by bit 1, it stays active until reset  
1
Warning enable  
0 = Disable: No warning is given when the limit is reached  
1 = Enable: A warning is given when the limit is reached  
2…15 Reserved  
0000h…FFFFh  
Value counter 1 configuration word.  
1 = 1  
Selects the signal to be monitored by value counter 1.  
Not selected  
Motor speed  
Other  
None.  
0
1
-
The value is taken from another parameter.  
Divisor for value counter 1. The value of the monitored signal 1.000  
is divided by this value before integration.  
0.001 …  
2147483.647  
Divisor for value counter 1.  
-
Selects the warning message for value counter 1.  
Value 1  
Pre-selectable warning message for value counter 1.  
Pre-selectable warning message for value counter 1.  
4
Motor bearing  
10  
                               
158 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Reading of value counter 2. Can be reset on the control panel  
by keeping Reset depressed for over 3 seconds.  
-
-2147483008 …  
2147483008  
Reading of value counter 2.  
-
Sets the warning limit for value counter 2.  
Warning limit for value counter 2.  
0
-2147483008 …  
2147483008  
-
Configures value counter 2. This counter measures, by  
integration, the area below the signal selected by parameter  
33.63 Value counter 2 source. A divisor may be applied to  
When the total area exceeds the limit set by parameter 33.61  
Value counter 2 limit, the warning specified by 33.65 Value  
counter 2 warning selection is given (if enabled by this  
parameter).  
00b  
The signal is sampled at 1-second intervals. Note that the  
scaled (see the “FbEq” column at the signal in question) value  
is used.  
The current value of the counter is readable from parameter  
indicates that the count has exceeded the limit.  
Bit  
Function  
Counter mode  
0
0 = Loop: If warning is enabled by bit 1, it stays active only for 10 seconds  
1 = Saturate: If warning is enabled by bit 1, it stays active until reset  
1
Warning enable  
0 = Disable: No warning is given when the limit is reached  
1 = Enable: A warning is given when the limit is reached  
2…15 Reserved  
0000h…FFFFh  
Value counter 2 configuration word.  
1 = 1  
Selects the signal to be monitored by value counter 2.  
Not selected  
Motor speed  
Other  
None.  
0
1
-
The value is taken from another parameter.  
Divisor for value counter 2. The value of the monitored signal 1.000  
is divided by this value before integration.  
0.001 …  
2147483.647  
Divisor for value counter 1.  
-
Selects the warning message for value counter 2.  
Value 2  
Pre-selectable warning message for value counter 2.  
Pre-selectable warning message for value counter 2.  
5
Motor bearing  
10  
                               
Parameters 159  
No.  
35  
Name/Value  
Description  
Def/FbEq16  
Motor thermal protection settings.  
Displays the motor temperature in degrees Celsius as  
estimated by the motor thermal protection model (see  
-
This parameter is read-only.  
-60 … 1000 °C  
Estimated motor temperature.  
1 = 1 °C  
-
Displays the temperature received through the source  
defined by parameter 35.11 Supervision 1 source.  
Note: With a PTC sensor, either 0 ohm (normal temperature)  
or the value of parameter 35.12 Supervision 1 fault limit  
(excessive temperature) is shown.  
This parameter is read-only.  
-10 … 1000 °C or  
ohm  
Measured temperature 1.  
1 = 1 unit  
-
Displays the temperature received through the source  
defined by parameter 35.21 Supervision 2 source.  
Note: With a PTC sensor, either 0 ohm (normal temperature)  
or the value of parameter 35.22 Supervision 2 fault limit  
(excessive temperature) is shown.  
This parameter is read-only.  
-10 … 1000 °C or  
ohm  
Measured temperature 2.  
1 = 1 unit  
Defines the action taken by the drive when measured  
temperature 1 (parameter 35.02) exceeds the appropriate  
limits set by parameters 35.12 Supervision 1 fault limit and  
No  
No action.  
0
1
Warning  
Warning A491 External temperature is generated when  
measured temperature 1 exceeds the limit set by parameter  
Fault  
Warning A491 External temperature is generated when  
measured temperature 1 exceeds the limit set by parameter  
35.13 Supervision 1 warning limit. The drive trips on fault  
4981 External temperature when measured temperature 1  
exceeds the limit set by parameter 35.12 Supervision 1 fault  
2
Selects the source from which measured temperature 1 is  
read.  
Disabled  
None. Temperature supervision 1 is disabled.  
0
1
Estimated  
Estimated motor temperature (see parameter 35.01 Motor  
temperature  
                                     
160 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
KTY84 StdIO /  
Extension module  
KTY84 sensor connected to the analog input selected by  
parameter 35.14 Supervision 1 AI select and an analog  
output.  
2
The following settings are required:  
• Set the hardware jumper or switch related to the analog  
input to U (voltage). Any change must be validated by a  
control unit reboot.  
• Set the appropriate analog input unit selection parameter  
in group 12 Standard AI to V (volt).  
• In parameter group 13 Standard AO, set the source  
selection parameter of the analog output to “Force KTY84  
The analog output feeds a constant current through the  
sensor. As the resistance of the sensor increases along with  
its temperature, the voltage over the sensor increases. The  
voltage is read by the analog input and converted into  
degrees.  
KTY84 module 1  
KTY84 module 2  
PT100 x1 StdIO  
KTY84 sensor connected to encoder interface 1.  
See also parameters 91.21 Temperature meas sel1 and  
3
4
5
KTY84 sensor connected to encoder interface 2.  
See also parameters 91.24 Temperature meas sel2 and  
Pt100 sensor connected to the analog input selected by  
parameter 35.14 Supervision 1 AI select and an analog  
output.  
The following settings are required:  
• Set the hardware jumper or switch related to the analog  
input to U (voltage). Any change must be validated by a  
control unit reboot.  
• Set the appropriate analog input unit selection parameter  
in group 12 Standard AI to V (volt).  
• In parameter group 13 Standard AO, set the source  
selection parameter of the analog output to “Force PT100  
The analog output feeds a constant current through the  
sensor. As the resistance of the sensor increases along with  
its temperature, the voltage over the sensor increases. The  
voltage is read by the analog input and converted into  
degrees.  
PT100 x2 StdIO  
PT100 x3 StdIO  
As selection PT100 x1 StdIO, but with two sensors connected  
in series. Using multiple sensors improves measurement  
accuracy significantly.  
6
7
As selection PT100 x1 StdIO, but with three sensors  
connected in series. Using multiple sensors improves  
measurement accuracy significantly.  
PTC DI6  
PTC sensor connected to digital input DI6.  
8
9
PTC module 1  
PTC sensor connected to encoder interface 1.  
PTC module 2  
PTC sensor connected to encoder interface 2.  
10  
       
Parameters 161  
No.  
Name/Value  
Description  
Def/FbEq16  
Direct temperature The temperature is taken from the source selected by  
11  
parameter 35.14 Supervision 1 AI select. The value of the  
source is assumed to be degrees Celsius.  
Defines the fault limit for temperature supervision 1. See  
130 °C  
Note: With a PTC sensor, the unit is ohm.  
-10 … 1000 °C or  
ohm  
Fault limit for temperature supervision 1.  
1 = 1 unit  
Defines the warning limit for temperature supervision 1. See 110 °C  
Note: With a PTC sensor, the unit is ohm.  
-10 … 1000 °C or  
ohm  
Warning limit for temperature supervision 1.  
1 = 1 unit  
Selects the input for parameter 35.11 Supervision 1 source,  
Not selected  
AI1 actual value  
AI2 actual value  
Other  
None.  
0
Analog input AI1 on the control unit.  
Analog input AI2 on the control unit.  
The value is taken from another parameter.  
1
2
-
Defines the action taken by the drive when measured  
temperature 2 (parameter 35.03) exceeds the appropriate  
limits set by parameters 35.22 Supervision 2 fault limit and  
No  
No action.  
0
1
Warning  
Warning A491 External temperature is generated when  
measured temperature 1 exceeds the limit set by parameter  
Fault  
Warning A491 External temperature is generated when  
measured temperature 1 exceeds the limit set by parameter  
35.23 Supervision 2 warning limit. The drive trips on fault  
4981 External temperature when measured temperature 1  
exceeds the limit set by parameter 35.22 Supervision 2 fault  
2
Selects the source from which measured temperature 2 is  
read.  
Disabled  
None. Temperature supervision 2 is disabled.  
0
1
Estimated  
Estimated motor temperature (see parameter 35.01 Motor  
temperature  
                             
162 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
KTY84 StdIO /  
Extension module  
KTY84 sensor connected to the analog input selected by  
parameter 35.24 Supervision 2 AI select and an analog  
output.  
2
The following settings are required:  
• Set the hardware jumper or switch related to the analog  
input to U (voltage). Any change must be validated by a  
control unit reboot.  
• Set the appropriate analog input unit selection parameter  
in group 12 Standard AI to V (volt).  
• In parameter group 13 Standard AO, set the source  
selection parameter of the analog output to “Force KTY84  
The analog output feeds a constant current through the  
sensor. As the resistance of the sensor increases along with  
its temperature, the voltage over the sensor increases. The  
voltage is read by the analog input and converted into  
degrees.  
KTY84 module 1  
KTY84 module 2  
PT100 x1 StdIO  
KTY84 sensor connected to encoder interface 1.  
See also parameters 91.21 Temperature meas sel1 and  
3
4
5
KTY84 sensor connected to encoder interface 2.  
See also parameters 91.24 Temperature meas sel2 and  
Pt100 sensor connected to the analog input selected by  
parameter 35.24 Supervision 2 AI select and an analog  
output.  
The following settings are required:  
• Set the hardware jumper or switch related to the analog  
input to U (voltage). Any change must be validated by a  
control unit reboot.  
• Set the appropriate analog input unit selection parameter  
in group 12 Standard AI to V (volt).  
• In parameter group 13 Standard AO, set the source  
selection parameter of the analog output to “Force PT100  
The analog output feeds a constant current through the  
sensor. As the resistance of the sensor increases along with  
its temperature, the voltage over the sensor increases. The  
voltage is read by the analog input and converted into  
degrees.  
PT100 x2 StdIO  
PT100 x3 StdIO  
As selection PT100 x1 StdIO, but with two sensors connected  
in series. Using multiple sensors improves measurement  
accuracy significantly.  
6
7
As selection PT100 x1 StdIO, but with three sensors  
connected in series. Using multiple sensors improves  
measurement accuracy significantly.  
PTC DI6  
PTC sensor connected to digital input DI6.  
8
9
PTC module 1  
PTC sensor connected to encoder interface 1.  
PTC module 2  
PTC sensor connected to encoder interface 2.  
10  
       
Parameters 163  
No.  
Name/Value  
Description  
Def/FbEq16  
Direct temperature The temperature is taken from the source selected by  
11  
parameter 35.24 Supervision 2 AI select. The value of the  
source is assumed to be degrees Celsius.  
Defines the fault limit for temperature supervision 2. See  
130 °C  
Note: With a PTC sensor, the unit is ohm.  
-10 … 1000 °C or  
ohm  
Fault limit for temperature supervision 2.  
1 = 1 unit  
Defines the warning limit for temperature supervision 2. See 110 °C  
Note: With a PTC sensor, the unit is ohm.  
-10 … 1000 °C or  
ohm  
Warning limit for temperature supervision 2.  
1 = 1 unit  
Selects the input for parameter 35.21 Supervision 2 source,  
Not selected  
AI1 actual value  
AI2 actual value  
Other  
None.  
0
Analog input AI1 on the control unit.  
Analog input AI2 on the control unit.  
The value is taken from another parameter.  
1
2
-
Defines the ambient temperature of the motor (in °C) for the  
motor thermal protection model.  
20 °C  
The motor thermal protection model estimates the motor  
temperature on the basis of the parameters in this group. The  
motor temperature increases if it operates in the region above  
the load curve, and decreases if it operates in the region  
below the load curve (if the motor is overheated).  
WARNING! The model cannot protect the motor if it  
does not cool properly because of dust, dirt, etc.  
-60 … 100 °C  
Ambient temperature.  
1 = 1 °C  
                     
164 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the motor load curve together with parameters 35.52 100%  
used by the motor thermal protection model to estimate the  
motor temperature.  
When the parameter is set to 100%, the maximum load is  
equal to the value of parameter 99.06 Motor nominal current  
(higher loads heat up the motor). The load curve level should  
be adjusted if the ambient temperature differs from the  
nominal value.  
I/IN  
I = Motor current  
(%)  
IN = Nominal motor current  
150  
100  
50  
Drive output  
frequency  
50 … 150%  
Maximum load for the motor load curve.  
1 = 1%  
Defines the motor load curve together with parameters 35.51 100%  
maximum motor load at zero speed of the load curve. A  
higher value can be used if the motor has an external motor  
fan to boost the cooling. See the motor manufacturer's  
recommendations.  
50 … 150%  
Zero speed load for the motor load curve.  
1 = 1%  
Defines the motor load curve together with parameters 35.51 45.00 Hz  
break point frequency of the load curve i.e. the point at which  
the motor load curve begins to decrease from the value of  
parameter 35.51 Motor load curve towards the value of  
1.00 … 500.00 Hz  
Break point for the motor load curve.  
1 = 1 Hz  
           
Parameters 165  
No.  
Name/Value  
Description  
Def/FbEq16  
Motor nominal temp Defines the temperature rise of the motor when the motor is  
80 °C  
loaded with nominal current. See the motor manufacturer's  
recommendations.  
Temperature  
Motor nominal  
temperature rise  
Ambient temperature  
Time  
0 … 300 °C  
Temperature rise.  
1 = 1 °C  
256 s  
Motor thermal time Defines the thermal time constant for the motor thermal  
protection model (i.e. time inside which the temperature has  
reached 63% of the nominal temperature). See the motor  
manufacturer's recommendations.  
Motor current  
100%  
Time  
Temperature rise  
100%  
63%  
Time  
Motor thermal time  
100 … 10000 s  
Motor thermal time constant.  
1 = 1 s  
 
166 Parameters  
No.  
36  
Name/Value  
Description  
Def/FbEq16  
Peak value and amplitude logger settings.  
See also section Load analyzer (page 55).  
Selects the signal to be monitored by the peak value logger.  
The signal is filtered using the filtering time specified by  
The peak value is stored, along with other pre-selected  
signals at the time, into parameters 36.1036.15.  
The peak value logger can be reset using parameter 36.09  
Reset loggers. The date and time of the last reset are stored  
into parameters 36.16 and 36.17 respectively.  
Zero  
None (peak value logger disabled).  
0
Motor speed used  
Output frequency  
Motor current  
Motor torque  
Dc-voltage  
1
3
4
6
7
Power inu out  
Speed ref ramp in  
Speed ref ramped  
Speed ref used  
Torq ref used  
Freq ref used  
Process PID out  
Process PID fbk  
Process PID act  
Process PID dev  
Other  
8
23.01 Speed ref ramp in (page 119).  
40.01 Process PID actual value (page 169).  
The value is taken from another parameter.  
10  
11  
12  
13  
14  
16  
17  
18  
19  
-
Peak value logger filtering time. See parameter 36.01 PVL  
2.00 s  
0.00 … 120.00 s  
Peak value logger filtering time.  
100 = 1 s  
Selects the signal to be monitored by amplitude logger 2. The Motor torque  
signal is sampled at 200-millisecond intervals when the drive  
is running.  
The results are displayed by parameters 36.4036.49. Each  
parameter represents an amplitude range, and shows what  
portion of the samples fall within that range.  
The signal value corresponding to 100% is defined by  
Amplitude logger 2 can be reset using parameter 36.09 Reset  
loggers. The date and time of the last reset are stored into  
parameters 36.50 and 36.51 respectively.  
For the selections, see parameter 36.01 PVL signal.  
0.00 … 32767.00  
Defines the signal value that corresponds to 100% amplitude. 100.00  
Signal value corresponding to 100%.  
1 = 1  
Resets the peak value logger and/or amplitude logger 2.  
(Amplitude logger 1 cannot be reset.)  
Done  
Reset completed or not requested (normal operation).  
0
                           
Parameters 167  
No.  
Name/Value  
Description  
Def/FbEq16  
All  
Reset both the peak value logger and amplitude logger 2.  
Reset the peak value logger.  
1
PVL  
2
AL2  
Reset amplitude logger 2.  
3
Peak value recorded by the peak value logger.  
Peak value.  
0.00  
1 = 1  
-32768.00 …  
32767.00  
The date on which the peak value was recorded.  
Peak occurrence date.  
-
-
-
The time at which the peak value was recorded.  
Peak occurrence time.  
-
-
-
PVL current at peak Motor current at the moment the peak value was recorded.  
0.00 A  
1 = 1 A  
-32768.00 …  
32767.00 A  
Motor current at peak.  
Voltage in the intermediate DC circuit of the drive at the  
moment the peak value was recorded.  
0.00 V  
0.00 … 2000.00 V  
DC voltage at peak.  
10 = 1 V  
0.00 rpm  
1 = 1  
PVL speed at peak Motor speed at the moment the peak value was recorded.  
-32768.00 …  
32767.00 rpm  
Motor speed at peak.  
The date on which the peak value logger was last reset.  
Last reset date of the peak value logger.  
-
-
-
The time at which the peak value logger was last reset.  
Last reset time of the peak value logger.  
-
-
-
Percentage of samples recorded by amplitude logger 1 that  
fall between 0 and 10%.  
0.00%  
0.00 … 100.00%  
Amplitude logger 1 samples between 0 and 10%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 1 that  
fall between 10 and 20%.  
0.00 … 100.00%  
Amplitude logger 1 samples between 10 and 20%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 1 that  
fall between 20 and 30%.  
0.00 … 100.00%  
Amplitude logger 1 samples between 20 and 30%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 1 that  
fall between 30 and 40%.  
0.00 … 100.00%  
Amplitude logger 1 samples between 30 and 40%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 1 that  
fall between 40 and 50%.  
0.00 … 100.00%  
Amplitude logger 1 samples between 40 and 50%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 1 that  
fall between 50 and 60%.  
0.00 … 100.00%  
Amplitude logger 1 samples between 50 and 60%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 1 that  
fall between 60 and 70%.  
0.00 … 100.00%  
Amplitude logger 1 samples between 60 and 70%.  
1 = 1%  
         
168 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Percentage of samples recorded by amplitude logger 1 that  
fall between 70 and 80%.  
0.00%  
0.00 … 100.00%  
Amplitude logger 1 samples between 70 and 80%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 1 that  
fall between 80 and 90%.  
0.00 … 100.00%  
Amplitude logger 1 samples between 80 and 90%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 1 that  
exceed 90%.  
0.00 … 100.00%  
Amplitude logger 1 samples over 90%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 0 and 10%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 0 and 10%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 10 and 20%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 10 and 20%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 20 and 30%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 20 and 30%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 30 and 40%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 30 and 40%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 40 and 50%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 40 and 50%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 50 and 60%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 50 and 60%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 60 and 70%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 60 and 70%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 70 and 80%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 70 and 80%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
fall between 80 and 90%.  
0.00 … 100.00%  
Amplitude logger 2 samples between 80 and 90%.  
1 = 1%  
0.00%  
Percentage of samples recorded by amplitude logger 2 that  
exceed 90%.  
0.00 … 100.00%  
Amplitude logger 2 samples over 90%.  
1 = 1%  
The date on which amplitude logger 2 was last reset.  
Last reset date of amplitude logger 2.  
-
-
-
-
-
The time at which amplitude logger 2 was last reset.  
Last reset time of amplitude logger 2.  
-
             
Parameters 169  
No.  
40  
Name/Value  
Description  
Def/FbEq16  
Parameter values for process PID control.  
Two different sets of parameter values can be pre-defined.  
The first set is made up of parameters 40.0740.56*, the  
second set is defined by the parameters in group 41 Process  
PID set 2. The binary source that defines which set is used is  
selected by parameter 40.57 Sel between set1 set2.  
See also the control chain diagrams on pages 300 and 301.  
*The remaining parameters in this group are common for both  
sets.  
Process PID actual Displays the output of the process PID controller. See the  
-
control chain diagram on page 301.  
This parameter is read-only. The unit is selected by  
-32768 … 32767  
Process PID controller output.  
1 = 1 unit  
-
Displays the value of process feedback after source  
selection, mathematical function (parameter 40.10 Feedback  
function), and filtering. See the control chain diagram on page  
This parameter is read-only. The unit is selected by  
-32768 … 32767  
Process feedback.  
1 = 1 unit  
-
Displays the value of process PID setpoint after source  
selection, mathematical function (40.18 Setpoint function),  
limitation and ramping. See the control chain diagram on  
page 301.  
This parameter is read-only. The unit is selected by  
-32768 … 32767  
Setpoint for process PID controller.  
1 = 1 unit  
-
Displays the process PID deviation. By default, this value  
equals setpoint - feedback, but deviation can be inverted by  
parameter 40.31 Deviation inversion. See the control chain  
diagram on page 301.  
This parameter is read-only. The unit is selected by  
-32768 … 32767  
PID deviation.  
1 = 1 unit  
-
Displays the trimmed reference output. See the control chain  
diagram on page 301.  
This parameter is read-only. The unit is selected by  
-32768 … 32767  
Trimmed reference.  
1 = 1 unit  
                           
170 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Displays status information on process PID control.  
This parameter is read-only.  
-
Bit  
0
Name  
Value  
PID active  
1 = Process PID control active.  
1
Setpoint frozen  
Output frozen  
PID sleep mode  
Sleep boost  
1 = Process PID setpoint frozen.  
1 = Process PID controller output frozen.  
1 = Sleep mode active.  
2
3
4
1 = Sleep boost active.  
5
Trim mode  
1 = Trim function active.  
6
Tracking mode  
Output limit high  
Output limit low  
1 = Tracking function active.  
7
1 = PID output is being limited by par. 40.37.  
1 = PID output is being limited by par. 40.36.  
8
9
Deadband active 1 = Deadband active (see par. 40.39)  
PID set 0 = Parameter set 1 in use. 1 = Parameter set 2 in use.  
10  
11…15 Reserved  
0000h…FFFFh  
Process PID control status word.  
1 = 1  
0
PID operation mode Activates/deactivates process PID control.  
Off  
On  
Process PID control inactive.  
Process PID control active.  
1
On when drive  
running  
Process PID control is active when the drive is running.  
2
Feedback 1 source Selects the first source of process feedback. See the control AI1 scaled  
chain diagram on page 300.  
Zero  
Zero feedback.  
0
AI1 scaled  
AI2 scaled  
Freq in scaled  
Motor current  
Power inu out  
Motor torque  
Other  
The value is taken from another parameter.  
1
2
3
5
6
7
-
Feedback 2 source Selects the second source of process feedback.  
For the selections, see parameter 40.08 Feedback 1 source.  
Defines how process feedback is calculated from the two  
sources selected by parameters 40.08 Feedback 1 source  
In1  
Source 1.  
0
1
2
3
4
5
6
In1+In2  
In1-In2  
Sum of sources 1 and 2.  
Source 2 subtracted from source 1.  
Source 1 multiplied by source 2.  
Source 1 divided by source 2.  
Smaller of the two sources.  
Greater of the two sources.  
In1*In2  
In1/In2  
MIN(In1,In2)  
MAX(In1,In2)  
                                     
Parameters 171  
No.  
Name/Value  
AVE(In1,In2)  
sqrt(In1)  
Description  
Def/FbEq16  
Average of the two sources.  
7
Square root of source 1.  
8
sqrt(In1-In2)  
sqrt(In1+In2)  
sqrt(In1)+sqrt(In2)  
Square root of (source 1 - source 2).  
Square root of (source 1 + source 2).  
Square root of source 1 + square root of source 2.  
9
10  
11  
Feedback filter time Defines the filter time constant for process feedback.  
0.000 s  
1 = 1 s  
0.000 … 30.000 s  
Feedback filter time.  
Defines the unit for parameters 40.0140.05, 40.2140.24 rpm  
rpm  
rpm.  
%.  
7
%
4
Hz  
Hz.  
3
Defines, together with parameter 40.15 Output base, a  
general scaling factor for the process PID control chain.  
The scaling can be utilized when, for example, the process  
setpoint is input in Hz, and the output of the PID controller is  
used as an rpm value in speed control. In this case, this  
parameter might be set to 50, and parameter 40.15 to the  
nominal motor speed at 50 Hz.  
1500  
In effect, the output of the PID controller = [40.15] when  
deviation (setpoint - feedback) = [40.14] and [40.32] = 1.  
Note: The scaling is based on the ratio between 40.14 and  
40.15. For example, the values 50 and 1500 would produce  
the same scaling as 1 and 30.  
-32768 … 32767  
Process setpoint base.  
1 = 1  
1500  
1 = 1  
Process PID controller output base.  
-32768 … 32767  
Selects the first source of process PID setpoint. This setpoint AI2 scaled  
is available in parameter 40.25 Setpoint selection as setpoint  
1. See the control chain diagram on page 300.  
Zero  
Zero.  
0
1
2
Control panel  
Internal setpoint  
Internal setpoint. See parameter 40.19 Internal setpoint  
AI1 scaled  
The value is taken from another parameter.  
3
AI2 scaled  
4
Freq in scaled  
Other  
10  
-
Selects the second source of process setpoint. This setpoint Zero  
is available in parameter 40.25 Setpoint selection as setpoint  
2.  
For the selections, see parameter 40.16 Setpoint 1 source.  
Selects a mathematical function between the setpoint  
sources selected by parameters 40.16 Setpoint 1 source and  
In1 or In2  
In1+In2  
No mathematical function applied. The source selected by  
parameter 40.25 Setpoint selection is used.  
0
1
Sum of sources 1 and 2.  
                                             
172 Parameters  
No.  
Name/Value  
In1-In2  
Description  
Def/FbEq16  
Source 2 subtracted from source 1.  
Source 1 multiplied by source 2.  
Source 1 divided by source 2.  
Smaller of the two sources.  
2
In1*In2  
3
In1/In2  
4
MIN(In1,In2)  
MAX(In1,In2)  
AVE(In1,In2)  
sqrt(In1)  
5
Greater of the two sources.  
6
Average of the two sources.  
7
Square root of source 1.  
8
sqrt(In1-In2)  
sqrt(In1+In2)  
sqrt(In1)+sqrt(In2)  
Square root of (source 1 - source 2).  
Square root of (source 1 + source 2).  
Square root of source 1 + square root of source 2.  
9
10  
11  
internal setpoint out of the presets defined by parameters  
Source defined Source defined  
Setpoint preset active  
by par. 40.19  
by par. 40.20  
0
1
0
1
0
0
1
1
1 (par. 40.21)  
2 (par. 40.22)  
3 (par. 40.23)  
4 (par. 40.24)  
Not selected  
Selected  
DI1  
0.  
1.  
0
1
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
internal setpoint out of the presets defined by parameters  
Not selected  
Selected  
DI1  
0.  
0
1
2
3
4
5
6
7
1.  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
DI2  
DI3  
DI4  
DI5  
DI6  
           
Parameters 173  
No.  
Name/Value  
DIO1  
Description  
Def/FbEq16  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
10  
11  
-
DIO2  
Process setpoint preset 1. See parameter 40.19 Internal  
The unit is selected by parameter 40.12 Unit selection.  
0
-32768.0 …  
32767.0  
Process setpoint preset 1.  
1 = 1 unit  
0
Process setpoint preset 2. See parameter 40.19 Internal  
The unit is selected by parameter 40.12 Unit selection.  
-32768.0 …  
32767.0  
Process setpoint preset 2.  
1 = 1 unit  
0
Process setpoint preset 3. See parameter 40.19 Internal  
The unit is selected by parameter 40.12 Unit selection.  
-32768.0 …  
32767.0  
Process setpoint preset 3.  
1 = 1 unit  
0
Process setpoint preset 4. See parameter 40.19 Internal  
The unit is selected by parameter 40.12 Unit selection.  
-32768.0 …  
32767.0  
Process setpoint preset 4.  
1 = 1 unit  
Configures the selection between setpoint sources 1 (40.16) Off  
and 2 (40.17).  
This parameter is only effective when parameter 40.18  
0 = Setpoint source 1  
1 = Setpoint source 2  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Defines a minimum limit for the process PID controller  
setpoint.  
0.0  
-32768.0 …  
32767.0  
Minimum limit for process PID controller setpoint.  
1 = 1  
Defines a maximum limit for the process PID controller  
setpoint.  
32767.0  
1 = 1  
-32768.0 …  
32767.0  
Maximum limit for process PID controller setpoint.  
                               
174 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the minimum time it takes for the setpoint to increase 0.0 s  
from 0% to 100%.  
0.0 … 1800.0 s  
Setpoint increase time.  
1 = 1  
Defines the minimum time it takes for the setpoint to decrease 0.0 s  
from 100% to 0%.  
0.0 … 1800.0 s  
Setpoint decrease time.  
1 = 1  
Freezes, or defines a source that can be used to freeze, the  
setpoint of the process PID controller. This feature is useful  
when the reference is based on a process feedback  
connected to an analog input, and the sensor must be  
serviced without stopping the process.  
1 = Process PID controller setpoint frozen  
Not selected  
Selected  
DI1  
Process PID controller setpoint not frozen.  
0
Process PID controller setpoint frozen.  
1
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Deviation inversion Inverts the input of the process PID controller.  
0 = Setpoint - Feedback  
1 = Feedback - Setpoint  
Ref - Fbk  
Fbk - Ref  
0.  
0
1.  
1
Source selection (see Terms and abbreviations on page 73).  
-
Defines the gain for the process PID controller. See  
1.0  
0.1 … 100.0  
Gain for PID controller.  
100 = 1  
                                 
Parameters 175  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the integration time for the process PID controller.  
Error/Controller output  
60.0 s  
O
I
G × I  
G × I  
Time  
Ti  
I = controller input (error)  
O = controller output  
G = gain  
Ti = integration time  
Note: Setting this value to 0 disables the “I” part, turning the  
PID controller into a PD controller.  
0.0 … 3600.0 s  
Integration time.  
1 = 1 s  
Defines the derivation time of the process PID controller. The 0.0 s  
derivative component at the controller output is calculated on  
basis of two consecutive error values (EK-1 and EK) according  
to the following formula:  
PID DERIV TIME × (EK - EK-1)/TS, in which  
TS = 2 ms sample time  
E = Error = Process reference - process feedback.  
0.0 … 10.0 s  
Derivation time.  
1000 = 1 s  
Derivation filter time Defines the time constant of the 1-pole filter used to smooth  
0.0 s  
the derivative component of the process PID controller.  
%
Unfiltered signal  
100  
63  
Filtered signal  
t
T
O = I × (1 - e-t/T  
)
I = filter input (step)  
O = filter output  
t = time  
T = filter time constant  
0.0 … 10.0 s  
Filter time constant.  
10 = 1 s  
                       
176 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the minimum limit for the process PID controller  
output. Using the minimum and maximum limits, it is possible  
to restrict the operation range.  
-32768.0  
-32768.0 …  
32767.0  
Minimum limit for process PID controller output.  
1 = 1  
Defines the maximum limit for the process PID controller  
output. See parameter 40.36 Output min.  
32767.0  
1 = 1  
-32768.0 …  
32767.0  
Maximum limit for process PID controller output.  
Freezes, or defines a source that can be used to freeze, the  
output of the process PID controller. This feature can be used  
when, for example, a sensor providing process feedback  
must to be serviced without stopping the process.  
1 = Process PID controller output frozen  
Not selected  
Selected  
DI1  
Process PID controller output not frozen.  
0
Process PID controller output frozen.  
1
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
10  
11  
-
DIO2  
Defines a deadband around the setpoint. Whenever process 0.0  
feedback enters the deadband, a delay timer starts. If the  
feedback remains within the deadband longer than the delay  
(40.40 Deadband delay), the PID controller output is frozen.  
Normal operation resumes after the feedback value leaves  
the deadband.  
Setpoint  
Feedback  
PID controller  
output  
PID controller  
output frozen  
Time  
                         
Parameters 177  
No.  
Name/Value  
Description  
Def/FbEq16  
-32768.0 …  
32767.0  
Deadband range.  
1 = 1  
Delay for the deadband. See parameter 40.39 Deadband  
0.0 s  
0.0 … 3600.0 s  
Delay for deadband area.  
1 = 1 s  
Selects the mode of the sleep function.  
No  
Sleep function disabled.  
0
1
Internal  
The motor speed is compared to the value of 40.43 Sleep  
level. If the motor speed remains below this value longer than  
the sleep delay (40.44 Sleep delay), the drive enters sleep  
mode.  
Parameters 40.4440.48 are in force.  
External  
The sleep function is activated by the source selected by  
2
Parameters 40.4440.48 are in force.  
Defines a source that is used to activate the sleep function  
when parameter 40.41 Sleep mode is set to External.  
0 = Sleep function disabled  
1 = Sleep function activated  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Defines the start limit for the sleep function when parameter  
0.0  
0.0 … 32767.0  
Sleep start level.  
1 = 1  
Defines a delay for the sleep function.  
60.0 s  
The delay timer starts when the sleep condition selected by  
parameter 40.41 Sleep mode becomes true, and resets if the  
condition becomes false.  
0.0 … 3600.0 s  
Sleep start delay.  
1 = 1 s  
Defines a boost time for the sleep boost step. See parameter 0.0 s  
0.0 … 3600.0 s  
Sleep boost time.  
1 = 1 s  
When the drive is entering sleep mode, the process setpoint 0.0  
is increased by this percentage for the time defined by  
If active, sleep boost is aborted when the drive wakes up.  
0.0 … 32767.0  
Sleep boost step.  
1 = 1  
                                             
178 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Wake-up deviation Defines the wake-up level as deviation between process  
setpoint and feedback. The unit is selected by parameter  
0
When the deviation exceeds the value of this parameter, and  
remains there for the duration of the wake-up delay (40.48  
Wake up delay), the drive wakes up.  
-2147483648 …  
2147483647  
Wake-up level (as deviation between process setpoint and  
feedback).  
1 = 1 unit  
0.50 s  
Defines a wake-up delay for the sleep function. See  
The delay timer starts when the deviation exceeds the wake-  
up level (40.47 Wake-up deviation), and resets if the deviation  
falls below the wake-up level.  
0.00 … 60.00 s  
Wake-up delay.  
1 = 1 s  
Activates (or selects a source that activates) tracking mode.  
In tracking mode, the value selected by parameter 40.50  
Tracking ref selection is substituted for the PID controller  
output. See also section Tracking (page 40).  
1 = Tracking mode enabled  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Selects the value source for tracking mode. See parameter  
Zero  
None.  
0
AI1 scaled  
AI2 scaled  
FB A ref1  
FB A ref2  
Other  
Fieldbus adapter A reference 1.  
Fieldbus adapter A reference 2.  
The value is taken from another parameter.  
1
2
3
4
-
Activates the trim function and selects between direct and  
proportional trimming (or a combination of both). With  
trimming, it is possible to apply a corrective factor to the drive  
reference (setpoint). The output after trimming is available as  
See the control chain diagram on page 301.  
Off  
The trim function is inactive.  
0
                                 
Parameters 179  
No.  
Name/Value  
Description  
Def/FbEq16  
Direct  
The trim function is active. The trimming factor is relative to  
the maximum speed, torque or frequency; the selection  
between these is made by parameter 40.52 Trim selection.  
1
Proportional  
Combined  
The trim function is active. The trimming factor is relative to  
the reference selected by parameter 40.53 Trimmed ref  
2
The trim function is active. The trimming factor is a  
3
combination of both Direct and Proportional modes; the  
proportions of each are defined by parameter 40.54 Trim mix.  
Selects whether trimming is used for correcting the speed,  
torque or frequency reference.  
Torque  
Torque reference trimming.  
Speed reference trimming.  
Frequency reference trimming.  
1
Speed  
2
Frequency  
3
Trimmed ref pointer Selects the signal source for the trim reference.  
Zero  
None.  
0
AI1 scaled  
AI2 scaled  
FB A ref1  
FB A ref2  
Other  
Fieldbus adapter A reference 1.  
Fieldbus adapter A reference 2.  
The value is taken from another parameter.  
1
2
3
4
-
When parameter 40.51 Trim mode is set to Combined,  
defines the effect of direct and proportional trim sources in the  
final trimming factor.  
0.000 = 100% proportional  
0.500 = 50% proportional, 50% direct  
1.000 = 100% direct  
0.000  
0.000 … 1.000  
Trim mix.  
1 = 1  
Defines a multiplier for the trimming factor. This value is  
multiplied by the result of parameter 40.51 Trim mode.  
Consequently, the result of the multiplication is used to  
multiply the result of parameter 40.56 Correction source.  
1.000  
-100.000 …  
100.000  
Multiplier for trimming factor.  
1 = 1  
PID ref  
Selects the reference to be trimmed.  
PID setpoint.  
1
PID output  
PID controller output.  
2
Selects the source that determines whether process PID  
parameter set 1 (parameters 40.0740.56) or set 2 (group  
0 = Process PID parameter set 1 in use  
1 = Process PID parameter set 2 in use  
Not selected  
Selected  
DI1  
0.  
0
1
2
3
4
5
1.  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
DI2  
DI3  
DI4  
                                         
180 Parameters  
No.  
Name/Value  
DI5  
Description  
Def/FbEq16  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
6
DI6  
7
DIO1  
10  
11  
-
DIO2  
41  
A second set of parameter values for process PID control.  
The selection between this set and first set (parameter group  
See also parameters 40.0140.06, and the control chain  
diagrams on pages 300 and 301.  
AI1 scaled  
0.000 s  
See parameter 40.15 Output base.  
1500  
1500  
0.0  
32767.0  
0.0 s  
0.0 s  
1.0  
See parameter 40.32 Gain.  
60.0 s  
     
Parameters 181  
No.  
Name/Value  
Description  
Def/FbEq16  
0.0 s  
0.0 s  
See parameter 40.36 Output min.  
-32768.0  
32767.0  
See parameter 40.37 Output max.  
See parameter 40.41 Sleep mode.  
See parameter 40.43 Sleep level.  
See parameter 40.44 Sleep delay.  
0.0  
0.0 s  
0.0  
60.0 s  
0.0 s  
0.0  
0.50 s  
43  
See parameter 40.51 Trim mode.  
See parameter 40.54 Trim mix.  
0.000  
1.000  
See parameter 40.55 Trim adjust.  
Settings of the internal brake chopper.  
Displays the estimated temperature of the braking resistor.  
The value is given in percent of the temperature the resistor  
reaches when loaded with the power defined by parameter  
-
This parameter is read-only.  
0.0 … 120.0%  
Estimated brake resistor temperature.  
1 = 1%  
Enables brake chopper control.  
Note: Before enabling brake chopper control, ensure that  
• a brake resistor is connected  
Disabled  
• overvoltage control is switched off (parameter 30.30  
• the supply voltage range (parameter 95.01 Supply voltage)  
has been selected correctly.  
Disabled  
Brake chopper control disabled.  
0
1
Enabled with  
thermal model  
Brake chopper control enabled with resistor overload  
protection.  
         
182 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Enabled without  
thermal model  
Brake chopper control enabled without resistor overload  
protection. This setting can be used, for example, if the  
resistor is equipped with a thermal circuit breaker that is wired  
to stop the drive if the resistor overheats.  
2
Selects the source for quick run-time brake chopper control.  
0 = Brake chopper IGBT pulses are cut off  
1 = Normal brake chopper IGBT modulation.  
This parameter can be used to program the chopper control  
to function only when the drive is operating in generating  
mode.  
Off  
0.  
0
On  
1.  
1
Source selection (see Terms and abbreviations on page 73).  
-
Defines the thermal time constant of the brake resistor for  
overload protection.  
0 s  
0 … 10000 s  
Brake resistor thermal time constant.  
1 = 1 s  
-
Defines the maximum continuous braking power which will  
raise the resistor temperature to the maximum allowed value.  
The value is used in the overload protection.  
0.10 …  
Maximum continuous braking power.  
1 = 1 kW  
10000.00 kW  
Defines the resistance value of the brake resistor. The value 0 ohm  
is used for brake chopper protection.  
0…1000 ohm  
Brake resistor resistance value.  
1 = 1 ohm  
Brake resistor fault Selects the fault limit for the brake resistor temperature  
105%  
supervision. When the limit is exceeded, the drive trips on  
The value is given in percent of the temperature the resistor  
reaches when loaded with the power defined by parameter  
0 … 150%  
Brake resistor temperature fault limit.  
1 = 1%  
95%  
Selects the warning limit for the brake resistor temperature  
supervision. When the limit is exceeded, the drive generates  
The value is given in percent of the temperature the resistor  
reaches when loaded with the power defined by parameter  
0 … 150%  
Brake resistor temperature warning limit.  
1 = 1%  
               
Parameters 183  
No.  
44  
Name/Value  
Description  
Def/FbEq16  
Configuration of mechanical brake control.  
See also section Mechanical brake control (page 41).  
Brake control status Displays the mechanical brake control status word.  
-
This parameter is read-only.  
Bit  
Name  
Information  
0
Open command  
Close/open command to brake actuator (0 = close, 1 = open).  
Connect this bit to desired output.  
1
2
Opening torque  
1 = Opening torque requested from drive logic  
1 = Hold requested from drive logic  
Hold stopped  
request  
3
4
5
6
7
8
Ramp to stopped 1 = Ramping down to zero speed requested from drive logic  
Enabled  
Closed  
Opening  
Open  
1 = Brake control is enabled  
1 = Brake control logic in BRAKE CLOSED state  
1 = Brake control logic in BRAKE OPENING state  
1 = Brake control logic in BRAKE OPEN state  
1 = Brake control logic in BRAKE CLOSING state  
Closing  
9…15 Reserved  
0000h…FFFFh  
Mechanical brake control status word.  
1 = 1  
-
Torque (in percent). Memorized when a brake close  
command is issued.  
This value can be used as a reference for the brake open  
-1600.0 … 1600.0  
%
Torque at brake closure.  
-
-
Displays the currently active brake open torque. See  
This parameter is read-only.  
-1000 … 1000%  
Currently active brake open torque.  
1 = 1%  
Activates/deactivates (or selects a source that  
activates/deactivates) the mechanical brake control logic.  
0 = Brake control inactive  
1 = Brake control active  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
                                   
184 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Brake acknowledge Activates/deactivates (and selects the source for) brake  
open/close status (acknowledgement) supervision.  
When a brake control error (unexpected state of the  
acknowledgement signal) is detected, the drive reacts as  
defined by parameter 44.17 Brake fault function.  
0 = Brake open  
1 = Brake closed  
Off  
0.  
0
On  
1.  
1
No acknowledge  
Brake open/closed supervision disabled.  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI1  
3
DI2  
4
DI3  
5
DI4  
6
DI5  
7
DI6  
8
DIO1  
11  
DIO2  
12  
-
Defines the brake open delay, ie. the delay between the  
internal open brake command and the release of motor speed  
control. The delay timer starts when the drive has magnetized  
the motor and increased the motor torque to the level  
required for brake release (parameter 44.03 Brake open  
torque reference). Simultaneously with the timer start, the  
brake control logic energizes the brake control output and the  
brake starts to open.  
0.00 s  
Set this parameter to the value of mechanical opening delay  
specified by the brake manufacturer.  
0.00 … 5.00 s  
Brake open delay.  
100 = 1 s  
Brake open torque Defines a source that is used as a brake opening torque  
reference if  
• its absolute value is greater than the setting of parameter  
• its sign is the same as the setting of 44.10 Brake open  
Zero  
Zero.  
0
1
2
3
4
7
AI1 scaled  
AI2 scaled  
FBA ref1  
FBA ref2  
Fieldbus adapter A reference 1.  
Fieldbus adapter A reference 2.  
Brake torque  
memory  
Brake open torque Parameter 44.10 Brake open torque.  
Other The value is taken from another parameter.  
-
                       
Parameters 185  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the sign (ie. direction of rotation) and minimum  
absolute value of the brake open torque (motor torque  
requested at brake release in percent of motor nominal  
torque).  
0%  
The value of the source selected by parameter 44.09 Brake  
open torque source is used as the brake open torque only if it  
has the same sign as this parameter and has a greater  
absolute value.  
-1000 … 1000%  
Minimum torque at brake release.  
1 = 1%  
Keep brake closed Selects a source that prevents the brake from opening.  
0 = Normal brake operation  
1 = Keep brake closed  
Note: This parameter cannot be changed while the drive is  
running.  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
Brake close request Selects the source of an external brake close request signal. Off  
When on, the signal overrides the internal logic and closes  
the brake.  
0 = Normal operation/No external close signal connected  
1 = Close brake  
Note: This parameter cannot be changed while the drive is  
running.  
Off  
0.  
0
On  
1.  
1
DI1  
Digital input DI1 (10.02 DI delayed status, bit 0).  
Digital input DI2 (10.02 DI delayed status, bit 1).  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
2
DI2  
3
DI3  
4
DI4  
5
DI5  
6
DI6  
7
DIO1  
DIO2  
10  
11  
-
                   
186 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Specifies a delay between a close command (that is, when  
the brake control output is de-energized) and when the drive  
stops modulating. This is to keep the motor live and under  
control until the brake actually closes.  
0.00 s  
Set this parameter equal to the value specified by the brake  
manufacturer as the mechanical make-up time of the brake.  
0.00 … 60.00 s  
Brake close delay.  
100 = 1 s  
10.0 rpm  
Defines the brake close speed as an absolute value.  
After motor speed remains below this level for the duration of  
the brake close level delay (44.15 Brake close level delay), a  
close command is given.  
0.0 … 1000.0 rpm  
Brake close speed.  
10 = 1 rpm  
0.00 s  
Brake close level delay. See parameter 44.14 Brake close  
0.00 … 10.00 s  
Brake close level delay.  
100 = 1 s  
0.00 s  
Brake reopen delay Defines a minimum time between brake closure and a  
subsequent open command.  
0.00 … 10.00 s  
Brake reopen delay.  
100 = 1 s  
Brake fault function Determines how the drive reacts upon a mechanical brake  
control error.  
Note: If parameter 44.07 Brake acknowledge selection is set  
to No acknowledge, acknowledgement status supervision is  
disabled altogether and will generate no warnings or faults.  
However, the brake open conditions are always supervised.  
Fault  
71A3 Mechanical brake opening failed fault if the status of the  
acknowledgement does not match the status presumed by  
the brake control logic.  
allowed fault if the brake open conditions cannot be fulfilled  
(for example, the required motor starting torque is not  
achieved).  
0
1
2
Warning  
A7A2 Mechanical brake opening failed warning if the status of  
the acknowledgement does not match the status presumed  
by the brake control logic.  
allowed warning if the brake open conditions cannot be  
fulfilled (for example, the required motor starting torque is not  
achieved).  
Open fault  
Upon closing the brake, the drive generates a A7A1  
Mechanical brake closing failed warning if the status of the  
acknowledgement does not match the status presumed by  
the brake control logic.  
Upon opening the brake, the drive trips on a 71A3 Mechanical  
brake opening failed fault if the status of the  
acknowledgement does not match the status presumed by  
the brake control logic.  
allowed fault if the brake open conditions cannot be fulfilled  
(for example, the required motor starting torque is not  
achieved).  
                                   
Parameters 187  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines a close fault delay, ie. time between brake closure  
and brake close fault trip.  
0.00 s  
0.00 … 60.00 s  
Brake close fault delay.  
100 = 1 s  
45  
Settings of the energy savings calculator.  
Energy saved in GWh compared to direct-on-line motor  
connection. This parameter is incremented when 45.02  
-
This parameter is read-only (see parameter 45.21 Energy  
0…65535 GWh  
Energy savings in GWh.  
1 = 1 GWh  
-
Energy saved in MWh compared to direct-on-line motor  
connection. This parameter is incremented when 45.03  
Saved kW hours rolls over.  
When this parameter rolls over, parameter 45.01 Saved GW  
hours is incremented.  
This parameter is read-only (see parameter 45.21 Energy  
0…999 MWh  
Energy savings in MWh.  
1 = 1 MWh  
-
Energy saved in kWh compared to direct-on-line motor  
connection.  
If the internal braking chopper of the drive is enabled, all  
energy fed by the motor to the drive is assumed to be  
converted into heat.  
When this parameter rolls over, parameter 45.02 Saved MW  
hours is incremented.  
This parameter is read-only (see parameter 45.21 Energy  
0.0 … 999.9 kWh  
Energy savings in kWh.  
10 = 1 kWh  
-
Monetary savings in thousands compared to direct-on-line  
motor connection. This parameter is incremented when 45.06  
Saved money rolls over.  
The currency is defined by parameter 45.17 Tariff currency  
This parameter is read-only (see parameter 45.21 Energy  
0…4294967295  
thousands  
Monetary savings in thousands of units.  
1 = 1  
thousand  
Monetary savings compared to direct-on-line motor  
connection. This value is a calculated by multiplying the  
saved energy in kWh by the currently active energy tariff  
-
When this parameter rolls over, parameter 45.05 Saved  
money x1000 is incremented.  
The currency is defined by parameter 45.17 Tariff currency  
This parameter is read-only (see parameter 45.21 Energy  
0.00 … 999.99 units Monetary savings.  
1 = 1 unit  
                             
188 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Reduction in CO2 emissions in metric kilotons compared to  
direct-on-line motor connection. This value is incremented  
when parameter 45.09 CO2 reduction in tons rolls over.  
This parameter is read-only (see parameter 45.21 Energy  
-
0…65535 metric  
kilotons  
Reduction in CO2 emissions in metric kilotons.  
1 = 1 metric  
kiloton  
Reduction in CO2 emissions in metric tons compared to  
direct-on-line motor connection. This value is calculated by  
multiplying the saved energy in MWh by the value of  
parameter 45.18 CO2 conversion factor (by default, 0.5  
metric tons/MWh).  
-
When this parameter rolls over, parameter 45.08 CO2  
reduction in kilotons is incremented.  
This parameter is read-only (see parameter 45.21 Energy  
0.0 … 999.9 metric Reduction in CO2 emissions in metric tons.  
tons  
1 = 1 metric  
ton  
Enables/disables the energy optimization function. The  
function optimizes the flux so that total energy consumption  
and motor noise level are reduced when the drive operates  
below the nominal load. The total efficiency (motor and drive)  
can be improved by 1…10% depending on load torque and  
speed.  
Note: With a permanent magnet motor, energy optimization is  
always enabled regardless of this parameter.  
Disable  
Energy optimization disabled.  
Energy optimization enabled.  
0
1
Enable  
Defines energy tariff 1 (price of energy per kWh). Depending 1.000 units  
on the setting of parameter 45.14 Tariff selection, this value or  
45.13 Energy tariff 2 is used for reference when monetary  
savings are calculated.  
The currency is defined by parameter 45.17 Tariff currency  
Note: Tariffs are read only at the instant of selection, and are  
not applied retroactively.  
0.000 …  
Energy tariff 1.  
-
4294967295.000  
units  
Defines energy tariff 2 (price of energy per kWh).  
2.000 units  
-
0.000 …  
4294967295.000  
units  
Energy tariff 2.  
Selects (or defines a source that selects) which pre-defined  
energy tariff is used.  
Energy tariff 1  
Energy tariff 2  
DI1  
0.  
0
1
2
3
1.  
Digital input DI1 (10.02 DI delayed status, bit 0).  
DI2  
Digital input DI2 (10.02 DI delayed status, bit 1).  
                       
Parameters 189  
No.  
Name/Value  
Description  
Def/FbEq16  
DI3  
Digital input DI3 (10.02 DI delayed status, bit 2).  
Digital input DI4 (10.02 DI delayed status, bit 3).  
Digital input DI5 (10.02 DI delayed status, bit 4).  
Digital input DI6 (10.02 DI delayed status, bit 5).  
4
5
6
7
DI4  
DI5  
DI6  
DIO1  
Digital input/output DIO1 (11.02 DIO delayed status, bit 0).  
Digital input/output DIO2 (11.02 DIO delayed status, bit 1).  
Source selection (see Terms and abbreviations on page 73).  
Specifies the currency used for the savings calculations.  
Euro.  
10  
DIO2  
11  
EUR  
-
101  
102  
100  
USD  
US dollar.  
Local currency  
The currency is determined by the language selection (see  
Defines a factor for conversion of saved energy into CO2  
emissions (kg/kWh or tn/MWh).  
0.500  
tn/MWh  
0.000 … 65.535  
tn/MWh  
Factor for conversion of saved energy into CO2 emissions.  
1 = 1 tn/MWh  
Comparison power Motor power when connected directly to the supply. The  
value is used for reference when energy savings are  
calculated.  
-
Note: The accuracy of the energy savings calculation is  
directly dependent on the accuracy of this value.  
0.0 … 10000000.0  
kW  
Motor power.  
1 = 1 kW  
Energy calculations Resets the savings counter parameters 45.0145.09.  
Done  
Reset  
Reset not requested (normal operation).  
0
1
Reset the savings counter parameters. The value reverts  
automatically to Done.  
46  
Speed supervision settings; actual signal filtering; general  
scaling settings.  
Defines the terminal speed value used in acceleration and the 1500 rpm  
initial speed value used in deceleration (see parameter group  
Also defines the rpm value that corresponds to 20000 in  
fieldbus communication using the ABB Drives profile.  
0…30000 rpm  
Acceleration/deceleration terminal/initial speed.  
1 = 1 rpm  
Defines the terminal frequency value used in acceleration and 50.0 Hz  
the initial speed value used in deceleration (see parameter  
Also defines the output frequency value that corresponds to  
20000 in fieldbus communication.  
0.0 … 30000.0 Hz  
Frequency corresponding to 20000 on fieldbus.  
10 = 1 Hz  
Defines the output torque value (in percent of nominal motor 100.0%  
torque) that corresponds to 1000 in fieldbus communication.  
0.0 … 30000.0%  
Torque corresponding to 1000 on fieldbus.  
10 = 1%  
Defines the output power value that corresponds to 10000 in 1000.0 kW  
fieldbus communication.  
                                     
190 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
1 = 1 kW  
500 ms  
0.0 … 30000.0 kW Power corresponding to 10000 on fieldbus.  
Defines a filter time for signals 01.01 Motor speed used,  
01.02 Motor speed estimated, 01.04 Encoder 1 speed filtered  
2…20000 ms  
Motor speed signal filter time.  
1 = 1 ms  
500 ms  
Defines a filter time for signal 01.06 Output frequency.  
2…20000 ms  
Output frequency signal filter time.  
1 = 1 ms  
100 ms  
Defines a filter time for signal 01.10 Motor torque %.  
2…20000 ms  
Motor torque signal filter time.  
1 = 1 ms  
100 ms  
Defines a filter time for signal 01.14 Output power..  
2…20000 ms  
Output power signal filter time.  
1 = 1 ms  
Defines the absolute value for the motor speed window  
supervision, ie. the absolute value of the difference between  
actual speed and speed reference (90.01 Motor speed for  
100.00 rpm  
When motor speed is within the limits defined by this  
parameter, bit 8 of 06.11 Main status word is 1. If motor speed  
is not within the limits, bit 8 is 0.  
0.00 … 30000.00  
rpm  
Absolute value for motor speed window supervision.  
1 = 1 rpm  
10.00 Hz  
Frequency setpoint Defines the absolute value for the motor frequency window  
supervision, ie. the absolute value of the difference between  
actual frequency and frequency reference (01.06 Output  
When motor frequency is within the limits defined by this  
parameter, bit 8 of 06.11 Main status word is 1. If motor  
frequency is not within the limits, bit 8 is 0.  
0.00 … 3000.00 Hz Absolute value for motor frequency window supervision.  
1 = 1 Hz  
10%  
Defines the absolute value for the motor torque window  
supervision, ie. the absolute value of the difference between  
actual torque and torque reference (01.10 Motor torque % -  
When motor torque is within the limits defined by this  
parameter, bit 8 of 06.11 Main status word is 1. If motor  
torque is not within the limits, bit 8 is 0.  
0…300%  
Absolute value for motor torque window supervision.  
1 = 1%  
Defines the supervision limit for actual speed.  
0.00 rpm  
See also parameter 06.11 Main status word, bit 10.  
0.00 … 30000.00  
rpm  
Actual speed supervision limit.  
1 = 1 rpm  
0.00 Hz  
Defines the supervision limit for actual frequency.  
See also parameter 06.11 Main status word, bit 10.  
0.00 … 3000.00 Hz Actual frequency supervision limit.  
1 = 1 Hz  
0.0 N•m  
Defines the supervision limit for actual torque.  
See also parameter 06.11 Main status word, bit 10.  
0.0 … 300.0 N•m  
Actual torque supervision limit.  
1 = 1 N•m  
                   
Parameters 191  
No.  
47  
Name/Value  
Description  
Def/FbEq16  
Data storage parameters that can be written to and read from  
using other parameters’ source and target settings.  
Note that there are different storage parameters for different  
data types.  
Data storage parameter 1.  
0.000  
-2147483.008 …  
2147483.008  
32-bit data.  
-
Data storage parameter 2.  
32-bit data.  
0.000  
-2147483.008 …  
2147483.008  
-
Data storage parameter 3.  
32-bit data.  
0.000  
-2147483.008 …  
2147483.008  
-
Data storage parameter 4.  
32-bit data.  
0.000  
-2147483.008 …  
2147483.008  
-
Data storage parameter 5.  
32-bit data.  
0.000  
-2147483.008 …  
2147483.008  
-
Data storage parameter 6.  
32-bit data.  
0.000  
-2147483.008 …  
2147483.008  
-
Data storage parameter 7.  
32-bit data.  
0.000  
-2147483.008 …  
2147483.008  
-
Data storage parameter 8.  
32-bit data.  
0.000  
-2147483.008 …  
2147483.008  
-
Data storage parameter 9.  
32-bit data.  
0
-
-2147483648 …  
2147483647  
Data storage parameter 10.  
32-bit data.  
0
-
-2147483648 …  
2147483647  
Data storage parameter 11.  
32-bit data.  
0
-
-2147483648 …  
2147483647  
     
192 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Data storage parameter 12.  
0
-2147483648 …  
2147483647  
32-bit data.  
-
Data storage parameter 13.  
32-bit data.  
0
-
-2147483648 …  
2147483647  
Data storage parameter 14.  
32-bit data.  
0
-
-2147483648 …  
2147483647  
Data storage parameter 15.  
32-bit data.  
0
-
-2147483648 …  
2147483647  
Data storage parameter 16.  
32-bit data.  
0
-
-2147483648 …  
2147483647  
Data storage parameter 17.  
0
-32768 … 32767  
16-bit data.  
1 = 1  
0
Data storage parameter 18.  
-32768 … 32767  
16-bit data.  
1 = 1  
0
Data storage parameter 19.  
-32768 … 32767  
16-bit data.  
1 = 1  
0
Data storage parameter 20.  
-32768 … 32767  
16-bit data.  
1 = 1  
0
Data storage parameter 21.  
-32768 … 32767  
16-bit data.  
1 = 1  
0
Data storage parameter 22.  
-32768 … 32767  
16-bit data.  
1 = 1  
0
Data storage parameter 23.  
-32768 … 32767  
16-bit data.  
1 = 1  
0
Data storage parameter 24.  
-32768 … 32767  
16-bit data.  
1 = 1  
Parameters 193  
No.  
49  
Name/Value  
Description  
Def/FbEq16  
Communication settings for the control panel port on the  
drive.  
Defines the node ID of the drive. All devices connected to the  
network must have a unique node ID.  
1
Note: For networked drives, it is advisable to reserve ID 1 for  
spare/replacement drives.  
1…32  
Node ID.  
1 = 1  
38.4 kbps  
57.6 kbps  
86.4 kbps  
115.2 kbps  
230.4 kbps  
460.8 kbps  
Defines the transfer rate of the link.  
38.4 kbit/s.  
1
2
3
4
5
6
57.6 kbit/s.  
86.4 kbit/s.  
115.2 kbit/s.  
230.4 kbit/s.  
460.8 kbit/s.  
Sets a timeout for control panel (or PC tool) communication. If 10.0 s  
a communication break lasts longer than the timeout, the  
action specified by parameter 49.05 Communication loss  
action is taken.  
0.1 … 3000.0 s  
Panel/PC tool communication timeout.  
10 = 1 s  
Selects how the drive reacts to a control panel (or PC tool)  
communication break.  
No action  
Fault  
No action taken.  
0
2
Last speed  
Drive generates an A7EE Panel loss warning and freezes the  
speed to the level the drive was operating at. The speed is  
determined by using 10-second low-pass filtering.  
WARNING! Make sure that it is safe to continue  
operation in case of a communication break.  
Speed ref safe  
Drive generates an A7EE Panel loss warning and sets the  
speed to the speed defined by parameter 22.41 Speed ref  
reference is used).  
3
WARNING! Make sure that it is safe to continue  
operation in case of a communication break.  
Applies the settings of parameters 49.0149.05.  
Note: Refreshing may cause a communication break, so  
reconnecting the drive may be required.  
Done  
Refresh done or not requested.  
0
1
Configure  
Refresh parameters 49.0149.05. The value reverts  
automatically to Done.  
50  
Fieldbus communication configuration.  
Enables/disables communication between the drive and  
fieldbus adapter A.  
Disable  
Communication between drive and fieldbus adapter A  
disabled.  
0
                                   
194 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Enable  
Communication between drive and fieldbus adapter A  
enabled.  
1
Selects how the drive reacts upon a fieldbus communication No action  
break. The time delay is defined by parameter 50.03 FBA A  
No action  
Fault  
No action taken.  
0
1
Communication break detection active. Upon a  
communication break, the drive trips on a 7510 FBA A  
communication fault and coasts to a stop.  
Last speed  
Communication break detection active. Upon a  
communication break, the drive generates a warning (A7C1  
FBA A communication) and freezes the speed to the level the  
drive was operating at. The speed is determined by the  
average speed over the previous 10 seconds.  
2
3
WARNING! Make sure that it is safe to continue  
operation in case of a communication break.  
Speed ref safe  
Communication break detection active. Upon a  
communication break, the drive generates a warning (A7C1  
FBA A communication) and sets the speed to the value  
frequency ref when frequency reference is used).  
WARNING! Make sure that it is safe to continue  
operation in case of a communication break.  
FBA A comm loss t Defines the time delay before the action defined by parameter 0.3 s  
50.02 FBA A comm loss func is taken. Time count starts when  
the communication link fails to update the message.  
0.3 … 6553.5 s  
Time delay.  
1 = 1 s  
Selects the type and scaling of reference 1 received from  
fieldbus adapter A. The scaling of the reference is defined by  
parameters 46.0146.04, depending on which reference  
type is selected by this parameter.  
Auto  
Reference type and scaling is chosen automatically  
according to the currently active control mode.  
0
Transparent  
General  
No scaling is applied.  
1
2
3
4
Generic reference without a specific unit.  
The scaling is defined by parameter 46.03 Torque scaling.  
The scaling is defined by parameter 46.01 Speed scaling.  
Torque  
Speed  
Frequency  
Position  
The scaling is defined by parameter 46.02 Frequency scaling. 5  
Reserved.  
Reserved.  
Reserved.  
Reserved.  
Reserved.  
6
Velocity  
7
DC voltage  
Active power  
Reactive power  
8
9
10  
Selects the type and scaling of reference 2 received from  
fieldbus adapter A. The scaling of the reference is defined by  
parameters 46.0146.04, depending on which reference  
type is selected by this parameter.  
For the selections, see parameter 50.04 FBA A ref1 type.  
                                       
Parameters 195  
No.  
Name/Value  
Description  
Def/FbEq16  
Selects the source of the Status word to be sent to the  
fieldbus network through fieldbus adapter A.  
Auto  
Source of the Status word is chosen automatically.  
0
1
Transparent mode  
The source selected by parameter 50.09 FBA A SW  
transparent source is transmitted as the Status word to the  
fieldbus network through fieldbus adapter A.  
FBA A actual 1 type Selects the type and scaling of actual value 1 transmitted to  
the fieldbus network through fieldbus adapter A. The scaling  
of the value is defined by parameters 46.0146.04,  
depending on which actual value type is selected by this  
parameter.  
For the selections, see parameter 50.04 FBA A ref1 type.  
FBA A actual 2 type Selects the type and scaling of actual value 2 transmitted to  
the fieldbus network through fieldbus adapter A. The scaling  
of the value is defined by parameters 46.0146.04,  
depending on which actual value type is selected by this  
parameter.  
For the selections, see parameter 50.04 FBA A ref1 type.  
Selects the source of the fieldbus status word when  
Not selected  
Other  
No source selected.  
-
The value is taken from another parameter.  
When parameter 50.07 FBA A actual 1 type is set to  
-
transparent source Transparent, this parameter selects the source of actual value  
1 transmitted to the fieldbus network through fieldbus adapter  
A.  
Not selected  
Other  
No source selected.  
-
The value is taken from another parameter.  
-
When parameter 50.08 FBA A actual 2 type is set to  
transparent source Transparent, this parameter selects the source of actual value  
2 transmitted to the fieldbus network through fieldbus adapter  
A.  
Not selected  
Other  
No source selected.  
-
The value is taken from another parameter.  
-
Enables the display of raw (unmodified) data received from  
and sent to fieldbus adapter A in parameters 50.1350.18.  
This functionality should only be used for debugging.  
Disable  
Enable  
Display of raw data from fieldbus adapter A disabled.  
Display of raw data from fieldbus adapter A ensabled.  
0
1
-
FBA A control word Displays the raw (unmodified) control word sent by the  
master (PLC) to fieldbus adapter A if debugging is enabled by  
This parameter is read-only.  
00000000h …  
FFFFFFFFh  
Control word sent by master to fieldbus adapter A.  
-
-
Displays raw (unmodified) reference REF1 sent by the master  
(PLC) to fieldbus adapter A if debugging is enabled by  
This parameter is read-only.  
-2147483648 …  
2147483647  
Raw REF1 sent by master to fieldbus adapter A.  
-
                                                       
196 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
FBA A reference 2 Displays raw (unmodified) reference REF2 sent by the master  
(PLC) to fieldbus adapter A if debugging is enabled by  
-
This parameter is read-only.  
-2147483648 …  
2147483647  
Raw REF2 sent by master to fieldbus adapter A.  
-
-
FBA A status word Displays the raw (unmodified) status word sent by fieldbus  
adapter A to the master (PLC) if debugging is enabled by  
This parameter is read-only.  
00000000h …  
FFFFFFFFh  
Status word sent by fieldbus adapter A to master.  
-
-
FBA A actual value Displays raw (unmodified) actual value ACT1 sent by fieldbus  
adapter A to the master (PLC) if debugging is enabled by  
This parameter is read-only.  
-2147483648 …  
2147483647  
Raw ACT1 sent by fieldbus adapter A to master.  
-
-
FBA A actual value Displays raw (unmodified) actual value ACT2 sent by fieldbus  
adapter A to the master (PLC) if debugging is enabled by  
This parameter is read-only.  
-2147483648 …  
2147483647  
Raw ACT2 sent by fieldbus adapter A to master.  
-
FBA A timelevel sel Selects the communication time levels.  
In general, lower time levels of read/write services reduce  
CPU load. The table below shows the time levels of the  
read/write services for cyclic high and cyclic low data with  
each parameter setting.  
Selection  
Cyclic high *  
10 ms  
Cyclic low **  
10 ms  
2 ms  
10 ms  
500 µs  
2 ms  
250 µs  
2 ms  
* Cyclic high data consists of fieldbus Control and Status  
words, Ref1, Ref2, Act1 and Act2.  
** Cyclic low data consists of the parameter data mapped to  
Acyclic data is handled as a background task.  
Slow  
Slow speed.  
3
0
1
2
Normal  
Fast  
Normal speed.  
Fast speed.  
Very fast  
Very fast speed.  
                         
Parameters 197  
No.  
51  
Name/Value  
Description  
Def/FbEq16  
Fieldbus adapter A configuration.  
Displays the type of the connected fieldbus adapter module.  
0 = Module is not found or is not properly connected, or is  
disabled by parameter 50.01 FBA A enable; 1 = FPBA;  
32 = FCAN; 37 = FDNA; 128 = FENA-11; 135 = FECA;  
136 = FEPL; 485 = FSCA.  
-
This parameter is read-only.  
Parameters 51.0251.26 are adapter module-specific. For  
more information, see the documentation of the fieldbus  
adapter module. Note that not all of these parameters are  
necessarily in use.  
-
0…65535  
Fieldbus adapter configuration parameter.  
1 = 1  
0…65535  
See parameter 51.02 FBA Par2.  
Fieldbus adapter configuration parameter.  
1 = 1  
Validates any changed fieldbus adapter module configuration Done  
settings. After refreshing, the value reverts automatically to  
Note: This parameter cannot be changed while the drive is  
running.  
Done  
Refreshing done.  
Refreshing.  
0
1
-
Configure  
Displays the parameter table revision of the fieldbus adapter  
module mapping file (stored in the memory of the drive).  
In format axyz, where ax = major table revision number; yz =  
minor table revision number.  
This parameter is read-only.  
Parameter table revision of adapter module.  
-
-
Displays the drive type code in the fieldbus adapter module  
mapping file (stored in the memory of the drive).  
This parameter is read-only.  
0…65535  
Drive type code stored in the mapping file.  
1 = 1  
-
Displays the fieldbus adapter module mapping file revision  
stored in the memory of the drive in decimal format.  
This parameter is read-only.  
0…65535  
Mapping file revision.  
1 = 1  
-
Displays the status of the fieldbus adapter module  
communication.  
Idle  
Adapter is not configured.  
Adapter is initializing.  
0
1
2
Exec.init  
Time out  
A timeout has occurred in the communication between the  
adapter and the drive.  
Conf.err  
Off-line  
Adapter configuration error: mapping file not found in the file  
system of the drive, or mapping file upload has failed more  
than three times.  
3
4
Fieldbus communication is off-line.  
                       
198 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
On-line  
Fieldbus communication is on-line, or fieldbus adapter has  
been configured not to detect a communication break. For  
more information, see the documentation of the fieldbus  
adapter.  
5
Reset  
Adapter is performing a hardware reset.  
6
-
52  
FBA comm SW ver Displays the common program revision of the adapter module  
in format axyz, where a = major revision number, xy = minor  
revision number, z = correction number or letter.  
Example: 190A = revision 1.90A.  
Common program revision of adapter module.  
Displays the application program revision of the adapter  
module in format axyz, where a = major revision number, xy =  
minor revision number, z = correction number or letter.  
Example: 190A = revision 1.90A.  
Application program version of adapter module.  
-
Selection of data to be transferred from drive to fieldbus  
controller through fieldbus adapter A.  
Note: 32-bit values require two consecutive parameters.  
Whenever a 32-bit value is selected in a data parameter, the  
next parameter is automatically reserved.  
Parameters 52.0152.12 select data to be transferred from  
the drive to the fieldbus controller through fieldbus adapter A.  
None  
None.  
0
CW 16bit  
Ref1 16bit  
Ref2 16bit  
SW 16bit  
Act1 16bit  
Act2 16bit  
CW 32bit  
Ref1 32bit  
Ref2 32bit  
SW 32bit  
Act1 32bit  
Act2 32bit  
SW2 16bit  
Other  
Control Word (16 bits)  
Reference REF1 (16 bits)  
Reference REF2 (16 bits)  
Status Word (16 bits)  
1
2
3
4
Actual value ACT1 (16 bits)  
Actual value ACT2 (16 bits)  
Control Word (32 bits)  
Reference REF1 (32 bits)  
Reference REF2 (32 bits)  
Status Word (32 bits)  
5
6
11  
12  
13  
14  
15  
16  
24  
-
Actual value ACT1 (32 bits)  
Actual value ACT2 (32 bits)  
Status Word 2 (16 bits)  
The value is taken from another parameter.  
                     
Parameters 199  
No.  
53  
Name/Value  
Description  
Def/FbEq16  
Selection of data to be transferred from fieldbus controller to  
drive through fieldbus adapter A.  
Note: 32-bit values require two consecutive parameters.  
Whenever a 32-bit value is selected in a data parameter, the  
next parameter is automatically reserved.  
Parameters 53.0153.12 select data to be transferred from  
the fieldbus controller to the drive through fieldbus adapter A.  
None  
None.  
0
CW 16bit  
Ref1 16bit  
Ref2 16bit  
CW 32bit  
Ref1 32bit  
Ref2 32bit  
CW2 16bit  
Other  
Control Word (16 bits)  
Reference REF1 (16 bits)  
Reference REF2 (16 bits)  
Control Word (32 bits)  
Reference REF1 (32 bits)  
Reference REF2 (32 bits)  
Control Word 2 (16 bits)  
The value is taken from another parameter.  
1
2
3
11  
12  
13  
21  
-
90  
Motor speed feedback configuration.  
See also section Encoder support (page 30), and the diagram  
on page 291.  
Displays the estimated or measured motor speed that is used  
for motor control, ie. final motor speed feedback selected by  
-
This parameter is read-only.  
-21474836.48 …  
21474836.47 rpm  
Motor speed used for control.  
-
-
Displays the motor position received from the source selected  
This parameter is read-only.  
-21474836.48 …  
21474836.47 rev  
Motor position.  
-
-
Displays the estimated or measured load speed that is used  
for motor control, ie. final load speed feedback selected by  
This parameter is read-only.  
-21474836.48 …  
21474836.47 rpm  
Load speed.  
-
-
Displays the load position received from the source selected  
This parameter is read-only.  
-2147483648 …  
2147483647 rev  
Load position.  
-
                                   
200 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Displays the load position scaled with feed constant (see  
-
This parameter is read-only.  
-2147483648 …  
2147483647  
Scaled load position.  
-
-
-
-
Displays encoder 1 speed in rpm.  
This parameter is read-only.  
-21474836.48 …  
21474836.47 rpm  
Encoder 1 speed.  
Encoder 1 position Displays the actual position of encoder 1 within one  
revolution.  
This parameter is read-only.  
-21474836.48 …  
21474836.47 rev  
Encoder 1 position within one revolution.  
-
-
Encoder 1 multiturn Displays the actual position of encoder 1 in full revolutions.  
This parameter is read-only.  
0 … 4294967295  
Encoder 1 position in revolutions.  
-
-
Displays the revolution counter extension for encoder 1. The  
revolution extension counter is incremented when encoder position (parameter  
90.11) wraps around in the positive direction, and  
decremented in the negative direction.  
This parameter is effective only if position is absolute;  
updated for both single-turn and multiturn encoders.  
This parameter is read-only.  
-2147483648 …  
2147483647  
Encoder 1 revolution counter extension.  
-
-
Encoder 1 position Displays encoder 1 position within one revolution as an 24-bit  
unsigned integer received from the encoder interface.  
This parameter is read-only.  
0.00 … 65535.00  
Raw encoder 1 position within one revolution.  
-
-
Displays encoder 1 revolutions as a raw measurement.  
This parameter is read-only.  
0…65535  
Raw encoder 1 revolution count.  
-
-
Displays encoder 2 speed in rpm.  
This parameter is read-only.  
-21474836.48 …  
21474836.47 rpm  
Encoder 2 speed.  
-
-
Encoder 2 position Displays the actual position of encoder 2 within one  
revolution.  
This parameter is read-only.  
-21474836.48 …  
21474836.47 rev  
Encoder 2 position within one revolution.  
-
-
Encoder 2 multiturn Displays the actual position of encoder 2 in full revolutions.  
This parameter is read-only.  
0 … 4294967295  
Encoder 2 position in revolutions.  
-
               
Parameters 201  
No.  
Name/Value  
Description  
Displays the revolution counter extension for encoder 2. The  
Def/FbEq16  
-
revolution extension counter is incremented when encoder position (parameter  
90.21) wraps around in the positive direction, and  
decremented in the negative direction.  
This parameter is effective only if position is absolute;  
updated for both single-turn and multiturn encoders.  
This parameter is read-only.  
-2147483648 …  
2147483647  
Encoder 2 revolution counter extension.  
-
-
Encoder 2 position Displays encoder 2 position within one revolution as a raw  
(24-bit unsigned integer) measurement.  
This parameter is read-only.  
0…65535  
Raw encoder 2 position within one revolution.  
-
-
Displays encoder 2 revolutions as a raw measurement.  
This parameter is read-only.  
0…65535  
Raw encoder 2 revolution count.  
-
-
Displays the motor revolution counter extension. The counter  
is incremented when encoder position wraps around in the  
positive direction, and decremented in the negative direction.  
This parameter is effective only if position is absolute;  
updated for both single-turn and multiturn encoders.  
This parameter is read-only.  
-2147483648 …  
2147483647  
Motor revolution counter extension.  
-
-
Displays the load revolution counter extension. The counter is  
incremented when encoder position wraps around in the  
positive direction, and decremented in the negative direction.  
This parameter is effective only if position is absolute;  
updated for both single-turn and multiturn encoders.  
This parameter is read-only.  
-2147483648 …  
2147483647  
Load revolution counter extension.  
-
Selects the motor speed feedback value used in control.  
A calculated speed estimate is used.  
Estimate  
0
1
Encoder 1  
Actual speed measured by encoder 1. The encoder is set up  
by the parameters in group 92 Encoder 1 configuration.  
Encoder 2  
Actual speed measured by encoder 2. The encoder is set up  
2
by the parameters in group 93 Encoder 2 configuration.  
Defines a filter time for motor speed feedback used for control 3 ms  
0 … 10000 ms  
Motor speed filter time.  
1 = 1 ms  
               
202 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Parameters 90.43 and 90.44 define a gear function between  
the motor speed feedback and motor control. The gear is  
used to correct a difference between the motor and encoder  
speeds for example if the encoder is not mounted directly on  
the motor shaft.  
1
Motor speed  
=
Encoder speed  
-2147483648 …  
2147483647  
Motor gear numerator.  
-
Motor gear denominator.  
-2147483648 …  
2147483647  
-
Selects how the drive reacts to loss of motor feedback.  
Fault  
Drive trips on a 7301 Motor speed feedback fault.  
Drive generates a A7B0 Motor speed feedback warning.  
No action taken.  
0
Warning  
None  
1
2
No  
Forces the use of estimated speed feedback.  
0
The feedback selected by 90.41 Motor feedback selection is  
used.  
Yes  
Calculated speed estimate is used (regardless of setting of  
1
Selects the load speed feedback value used in control.  
No load feedback selected.  
None  
0
1
Encoder 1  
Actual speed measured by encoder 1. The encoder is set up  
by the parameters in group 92 Encoder 1 configuration.  
Encoder 2  
Actual speed measured by encoder 2. The encoder is set up  
2
by the parameters in group 93 Encoder 2 configuration.  
Estimate  
A calculated speed estimate is used.  
3
4
Motor feedback  
The source selected by parameter 90.41 Motor feedback  
selection for motor feedback is also used for load feedback.  
Any difference between the motor and load speeds can be  
compensated by using the load gear function; see parameter  
Defines a filter time for load speed feedback (90.03 Load  
4 ms  
-
0 … 10000 ms  
Load speed filter time.  
                                     
Parameters 203  
No.  
Name/Value  
Description  
Def/FbEq16  
Parameters 90.53 and 90.54 define a gear function between  
the load (ie. driven equipment) speed feedback and motor  
control. The gear is used to correct a difference between the  
load and encoder speeds for example if the encoder is not  
mounted directly on the rotated machinery.  
1
Load speed  
=
Encoder speed  
-2147483648 …  
2147483647  
Load gear numerator.  
-
-2147483648 …  
2147483647  
Load gear denominator.  
-
Load position offset Load-side position offset. The resolution is determined by  
0 rev  
-
-32768 … 32767  
rev  
Load-side position offset.  
Defines how many bits are used for load position count within 16  
one revolution.  
0…32  
Load position resolution.  
-
Parameters 90.61 and 90.62 define a gear function between  
1
the motor and load speeds.  
Motor speed  
Load speed  
=
-2147483648 …  
2147483647  
Gear numerator (motor-side).  
-
-
-2147483648 …  
2147483647  
Gear denominator (load-side).  
Parameters 90.63 and 90.64 define the feed constant for the  
position calculation:  
1
The feed constant converts rotational motion into translatory  
motion. The feed constant is the distance the load moves  
during one turn of the motor shaft.  
The translatory load position is shown by parameter 90.05  
-2147483648 …  
2147483647  
Feed constant numerator.  
-
Feed constant denominator.  
-
-2147483648 …  
2147483647  
                           
204 Parameters  
No.  
91  
Name/Value  
Description  
Def/FbEq16  
Configuration of encoder interface modules.  
Displays the status of the digital inputs of FEN-xx encoder  
interface modules.  
-
This parameter is read-only.  
Bit  
0
Name  
DI1 of interface 1 (see parameters 91.11 and 91.12)  
DI2 of interface 1 (see parameters 91.11 and 91.12)  
Reserved  
1
2…3  
4
DI1 of interface 2 (see parameters 91.13 and 91.14)  
DI2 of interface 2 (see parameters 91.13 and 91.14)  
5
6…15 Reserved  
0000h…FFFFh  
Status word of digital inputs on FEN-xx modules.  
1 = 1  
-
Displays the type of the interface module found in the location  
specified by parameter 91.12 Module 1 location.  
0 = No module found; 1 = No communication; 2 = Unknown;  
3 = FEN-01; 4 = FEN-11; 5 = FEN-21; 6 = FEN-31.  
This parameter is read-only.  
Displays the type of the interface module found in the location  
specified by parameter 91.14 Module 2 location.  
0 = No module found; 1 = No communication; 2 = Unknown;  
3 = FEN-01; 4 = FEN-11; 5 = FEN-21; 6 = FEN-31.  
This parameter is read-only.  
-
-
Displays the temperature measured through the sensor input  
of interface module 1.  
This parameter is read-only.  
0…1000 °C  
Temperature measured through interface module 1.  
-
-
Displays the temperature measured through the sensor input  
of interface module 2.  
This parameter is read-only.  
0…1000 °C  
Temperature measured through interface module 2.  
-
Encoder parameter Forces a reconfiguration of the FEN-xx encoder interface  
modules, which is needed for any parameter changes in  
groups 90…93 to take effect.  
Note: The parameter cannot be changed while the drive is  
running.  
Done  
Reconfiguration done (normal operation).  
0
Configure  
None  
Reconfigure. The value reverts automatically to Done.  
Defines the type of the module used as interface module 1.  
None (communication disabled).  
0
1
2
3
4
FEN-01  
FEN-11  
FEN-21  
FEN-31  
FEN-01.  
FEN-11.  
FEN-21.  
FEN-31.  
                             
Parameters 205  
No.  
Name/Value  
Description  
Def/FbEq16  
Specifies the slot (1…3) on the control unit of the drive into  
which the interface module is installed.  
1
1…254  
Slot number.  
-
None  
Defines the type of the module used as interface module 2.  
None (communication disabled).  
0
1
2
3
4
1
FEN-01  
FEN-01.  
FEN-11.  
FEN-21.  
FEN-31.  
FEN-11  
FEN-21  
FEN-31  
Specifies the slot (1…3) on the control unit of the drive into  
which the interface module is installed.  
1…254  
Slot number.  
-
Temperature meas Specifies the type of temperature sensor connected to  
interface module 1.  
None  
PTC  
None.  
0
PTC.  
1
KTY-84  
KTY84.  
2
Defines a filtering time for the temperature measurement  
through interface module 1.  
1500 ms  
0…10000 ms  
Filtering time for temperature measurement.  
-
Defines how many consecutive samples must be received by  
interface module 1 before the status of a PTC sensor is  
interpreted as true instead of false.  
1
0…65535  
Number of samples.  
-
Temperature meas Specifies the type of temperature sensor connected to  
interface module 2.  
None  
PTC  
None.  
0
PTC.  
1
KTY-84  
KTY84.  
2
Defines a filtering time for the temperature measurement  
through interface 2.  
1500 ms  
0…10000 ms  
Filtering time for temperature measurement.  
-
Defines how many consecutive samples must be received by  
interface module 2 before the status of a PTC sensor is  
interpreted as true instead of false.  
1
0…65535  
Number of samples.  
-
                                               
206 Parameters  
No.  
92  
Name/Value  
Description  
Def/FbEq16  
Settings for encoder 1.  
Notes:  
• The contents of the parameter group vary according to the  
selected encoder type.  
• It is recommended that encoder connection 1 (this group)  
is used whenever possible since the data received through  
that interface is fresher than the data received through  
Activates the communication with optional encoder/resolver  
interface module 1.  
None  
Inactive.  
0
3
Abs enc  
Communication active. Module type: FEN-11 Absolute  
Encoder Interface. Input: Absolute encoder input (X42).  
Resolver  
Communication active. Module type: FEN-21 Resolver  
Interface. Input: Resolver input (X52).  
4
HTL  
Communication active. Module type: FEN-31 HTL Encoder  
Interface. Input: HTL encoder input (X82).  
5
Selects the interface module that the encoder is connected  
to. (The physical locations and types of encoder interface  
modules are defined in parameter group 91 Encoder module  
Module 1  
Module 2  
Interface module 1.  
Interface module 2.  
1
2
-
Encoder 1 type act Displays the type of optional encoder/resolver interface 1.  
For the possible values, see parameter 92.01 Encoder 1 type.  
This parameter is read-only.  
Defines the number of sine/cosine wave cycles within one  
revolution.  
0
Note: This parameter need not be set when an EnDat or SSI  
encoder is used in continuous mode. See parameter 92.30  
0…65535  
Number of sine/cosine wave cycles within one revolution.  
-
Defines the frequency of the excitation signal.  
1 kHz  
1…20 kHz  
Excitation signal frequency.  
1 = 1 kHz  
0
Defines the pulse number per revolution.  
0…65535  
Number of pulses.  
-
Selects the source of the absolute position information.  
None  
Not selected.  
0
1
2
3
4
5
Commut sig  
EnDat  
Commutation signals.  
Serial interface: EnDat encoder.  
Serial interface: HIPERFACE encoder.  
Serial interface: SSI encoder.  
Serial interface: Tamagawa 17/33-bit encoder.  
Hiperface  
SSI  
Tamagawa  
                                                                     
Parameters 207  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the amplitude of the excitation signal.  
4.0 V  
4.0 … 12.0 V  
Excitation signal amplitude.  
10 = 1 V  
Selects the type of encoder.  
Quadrature  
Quadrature encoder (has two channels, A and B)  
Single-track encoder (has one channel, A)  
0
Single track  
1
Enables the encoder zero pulse for the absolute encoder  
input (X42) of the FEN-11 interface module.  
Note: No zero pulse exists with serial interfaces, ie. when  
Disable  
Enable  
Zero pulse disabled.  
Zero pulse enabled.  
0
1
1
Defines the number of pole pairs of the encoder.  
1…32  
Number of encoder pole pairs.  
1 = 1  
Selects the speed calculation mode.  
*With a single-track encoder (parameter 92.11 Pulse encoder  
type is set to Single track), the speed is always positive.  
A&B all  
A all  
Channels A and B: Rising and falling edges are used for  
speed calculation.  
*Channel B: Defines the direction of rotation.  
Note: With a single-track encoder (parameter 92.11 Pulse  
encoder type), this setting acts like setting A all.  
0
1
Channel A: Rising and falling edges are used for speed  
calculation.  
*Channel B: Defines the direction of rotation.  
A rising  
Channel A: Rising edges are used for speed calculation.  
*Channel B: Defines the direction of rotation.  
2
3
4
A falling  
Auto rising  
Channel A: Falling edges are used for speed calculation.  
*Channel B: Defines the direction of rotation.  
One of the above modes is selected automatically depending  
on the pulse frequency as follows:  
Pulse frequency of the  
Used mode  
channel(s)  
< 2442 Hz  
2442…4884 Hz  
> 4884 Hz  
Auto falling  
One of the above modes is selected automatically depending  
on the pulse frequency as follows:  
5
Pulse frequency of the  
Used mode  
channel(s)  
< 2442 Hz  
2442…4884 Hz  
> 4884 Hz  
                                   
208 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the number of bits used to indicate position within  
one revolution. For example, a setting of 15 bits corresponds  
to 32768 positions per revolution.  
0
The value is used when parameter 92.11 Absolute position  
source is set to EnDat, Hiperface or SSI. When parameter  
parameter is internally set to 17.  
0…32  
Number of bits used in position indication within one  
revolution.  
1 = 1  
Selects whether position estimation is used with encoder 1 to  
increase position data resolution or not.  
Disable  
Measured position used. (The resolution is 4 × pulses per  
revolution for quadrature encoders, 2 × pulses per revolution  
for single-track encoders.)  
0
Enable  
Estimated position used. (Uses position interpolation;  
extrapolated at the time of data request.)  
1
0
Defines the number of bits used in revolution counting with an  
multiturn encoder. For example, a setting of 12 bits would  
support counting up to 4096 revolutions.  
The value is used when parameter 92.11 Absolute position  
source is set to EnDat, Hiperface or SSI. When parameter  
this parameter to a non-zero value activates multiturn data  
requesting.  
0…32  
Number of bits used in revolution count.  
1 = 1  
Selects whether calculated or estimated speed is used.  
Estimation increases the speed ripple in steady state  
operation, but improves the dynamics.  
Disable  
Last calculated speed used. (The calculation interval is 62.5  
microseconds to 4 milliseconds.)  
0
Enable  
Estimated speed (estimated at the time of data request) is  
used.  
1
Activates transient filtering for the encoder (changes in  
direction of rotation are ignored above the selected pulse  
frequency).  
4880 Hz  
2440 Hz  
1220 Hz  
Disabled  
Change in direction of rotation allowed below 4880 Hz.  
Change in direction of rotation allowed below 2440 Hz.  
Change in direction of rotation allowed below 1220 Hz.  
0
1
2
3
Change in direction of rotation allowed at any pulse  
frequency.  
Selects the action taken by the drive in case an encoder  
wiring fault is detected by the FEN-31 encoder interface.  
No  
Wiring fault monitoring disabled.  
0
1
Warning  
Fault  
The drive generates a warning (A7E1 Encoder 1).  
The drive trips on 7381 Encoder 1.  
                                   
Parameters 209  
No.  
Name/Value  
Description  
Def/FbEq16  
Selects which encoder cable channels and wires are  
monitored for wiring faults. See also parameter 92.20 Enc  
A, B  
A and B.  
0
1
2
3
A, B, Z  
A, B and Z.  
A+, A-, B+, B-  
A+, A-, B+ and B-.  
A+, A-, B+, B-, Z+ and Z-.  
A+, A-, B+, B-, Z+,  
Z-  
Selects the serial link mode with an EnDat or SSI encoder.  
Initial pos.  
Single position transfer mode (initial position).  
Continuous position data transfer mode.  
0
Continuous  
1
Selects the maximum encoder calculation time for an EnDat  
encoder.  
Note: This parameter needs to be set only when an EnDat  
encoder is used in continuous mode, ie. without incremental  
sin/cos signals (supported only as encoder 1). See also  
10 us  
10 microseconds.  
100 microseconds.  
1 millisecond.  
0
100 us  
1
1 ms  
2
50 ms  
50 milliseconds.  
3
Selects the transmission cycle for an SSI encoder.  
Note: This parameter needs to be set only when an SSI  
encoder is used in continuous mode, ie. without incremental  
sin/cos signals (supported only as encoder 1). See also  
50 us  
50 microseconds.  
100 microseconds.  
200 microseconds.  
500 microseconds.  
1 millisecond.  
0
1
2
3
4
5
2
100 us  
200 us  
500 us  
1 ms  
2 ms  
2 milliseconds.  
Defines the length of an SSI message. The length is defined  
as the number of clock cycles. The number of cycles can be  
calculated by adding 1 to the number of bits in an SSI  
message frame.  
2…127  
SSI message length.  
-
1
With an SSI encoder, defines the location of the MSB (most  
significant bit) of the position data within an SSI message.  
1…126  
Position data MSB location (bit number).  
-
                                   
210 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
With an SSI encoder, defines the location of the MSB (most  
significant bit) of the revolution count within an SSI message.  
1
1…126  
Revolution count MSB location (bit number).  
-
Selects the data format for an SSI encoder.  
binary  
Binary code.  
Gray code.  
0
gray  
1
Selects the baud rate for an SSI encoder.  
10 kBit/s  
10 kbit/s.  
0
50 kBit/s  
50 kbit/s.  
1
100 kBit/s  
200 kBit/s  
500 kBit/s  
1000 kBit/s  
100 kbit/s.  
200 kbit/s.  
500 kbit/s.  
1000 kbit/s.  
2
3
4
5
Defines the phase angle within one sine/cosine signal period  
that corresponds to the value of zero on the SSI serial link  
data. The parameter is used to adjust the synchronization of  
the SSI position data and the position based on sine/cosine  
incremental signals. Incorrect synchronization may cause an  
error of ±1 incremental period.  
Note: This parameter needs to be set only when an SSI  
encoder is used in initial position mode (see parameter 92.30  
315-45 deg  
315-45 degrees.  
45-135 degrees.  
135-225 degrees.  
225-315 degrees.  
0
45-135 deg  
1
135-225 deg  
225-315 deg  
2
3
Defines the use of parity and stop bits with a HIPERFACE  
encoder.  
Typically this parameter need not be set.  
Odd  
Odd parity indication bit, one stop bit.  
Even parity indication bit, one stop bit.  
0
Even  
1
Defines the transfer rate of the link with a HIPERFACE  
encoder.  
Typically this parameter need not be set.  
4800 bits/s  
9600 bits/s  
19200 bits/s  
38400 bits/s  
4800 bit/s.  
9600 bit/s.  
19200 bit/s.  
38400 bit/s.  
0
1
2
3
                                 
Parameters 211  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the node address for a HIPERFACE encoder.  
Typically this parameter need not be set.  
64  
0…255  
HIPERFACE encoder node address.  
-
92  
Settings for encoder 2.  
Notes:  
• The contents of the parameter group vary according to the  
selected encoder type.  
• It is recommended that encoder connection 1 (group 92  
Encoder 1 configuration) is used whenever possible since  
the data received through that interface is fresher than the  
data received through connection 2 (this group).  
Activates the communication with optional encoder/resolver  
interface module 2.  
None  
None  
Inactive.  
0
3
Abs enc  
Communication active. Module type: FEN-11 Absolute  
Encoder Interface. Input: Absolute encoder input (X42).  
Resolver  
Communication active. Module type: FEN-21 Resolver  
Interface. Input: Resolver input (X52).  
4
HTL  
Communication active. Module type: FEN-31 HTL Encoder  
Interface. Input: HTL encoder input (X82).  
5
Selects the interface module that the encoder is connected  
to. (The physical locations and types of encoder interface  
modules are defined in parameter group 91 Encoder module  
Module 1  
Module 2  
Interface module 1.  
Interface module 2.  
1
2
-
Encoder 2 type act Displays the type of optional encoder/resolver interface  
module 1.  
For the possible values, see parameter 93.01 Encoder 2 type.  
This parameter is read-only.  
Sine/cosine number (Visible when 93.01 Encoder 2 type = Abs enc)  
0
(Visible when 93.01 Encoder 2 type = Resolver)  
1 kHz  
0
(Visible when 93.01 Encoder 2 type = HTL)  
(Visible when 93.01 Encoder 2 type = Abs enc)  
(Visible when 93.01 Encoder 2 type = Resolver)  
4.0 V  
Pulse encoder type (Visible when 93.01 Encoder 2 type = HTL)  
1
(Visible when 93.01 Encoder 2 type = Abs enc)  
Resolver polepairs (Visible when 93.01 Encoder 2 type = Resolver)  
(Visible when 93.01 Encoder 2 type = HTL)  
                       
212 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Position data width (Visible when 93.01 Encoder 2 type = Abs enc)  
0
Position estimation (Visible when 93.01 Encoder 2 type = HTL)  
0
(Visible when 93.01 Encoder 2 type = Abs enc)  
(Visible when 93.01 Encoder 2 type = HTL)  
(Visible when 93.01 Encoder 2 type = HTL)  
Enc cable fault func (Visible when 93.01 Encoder 2 type = HTL)  
(Visible when 93.01 Encoder 2 type = HTL)  
(Visible when 93.01 Encoder 2 type = Abs enc)  
2
(Visible when 93.01 Encoder 2 type = Abs enc)  
(Visible when 93.01 Encoder 2 type = Abs enc)  
(Visible when 93.01 Encoder 2 type = Abs enc)  
(Visible when 93.01 Encoder 2 type = Abs enc)  
1
SSI revolution msb (Visible when 93.01 Encoder 2 type = Abs enc)  
1
(Visible when 93.01 Encoder 2 type = Abs enc)  
(Visible when 93.01 Encoder 2 type = Abs enc)  
(Visible when 93.01 Encoder 2 type = Abs enc)  
(Visible when 93.01 Encoder 2 type = Abs enc)  
Hiperface baud rate (Visible when 93.01 Encoder 2 type = Abs enc)  
64  
(Visible when 93.01 Encoder 2 type = Abs enc)  
Parameters 213  
No.  
95  
Name/Value  
Description  
Def/FbEq16  
Various hardware-related settings.  
Selects the supply voltage range. This parameter is used by  
the drive to determine the nominal voltage of the supply  
network. The parameter also affects the current ratings and  
the DC voltage control functions (trip and brake chopper  
activation limits) of the drive.  
WARNING! An incorrect setting may cause the motor  
to rush uncontrollably, or the overloading of the brake  
chopper or resistor.  
Not given  
No voltage defined. The drive will not start modulating before  
another value is selected.  
0
208…240 V  
380…415 V  
440…480 V  
500 V  
208…240 V  
380…415 V  
440…480 V  
500 V  
1
2
3
4
525…600 V  
660…690 V  
525…600 V  
660…690 V  
5
6
Enables adaptive voltage limits.  
Adaptive voltage limits can be used if, for example, an IGBT  
supply unit is used to raise the DC voltage level. If the  
communication between the inverter and IGBT supply unit is  
active, the voltage limits are fixed to the DC voltage reference  
from the IGBT supply unit. Otherwise the limits are calculated  
based on the measured DC voltage at the end of the pre-  
charging sequence.  
Disable  
Enable  
Adaptive voltage limits disabled.  
0
Adaptive voltage limits enabled.  
1
Specifies how the control unit of the drive is powered.  
Internal 24V  
The drive control unit is powered from the drive power unit it  
is connected to. This is the default setting.  
0
1
External 24V  
The drive control unit is powered from an external power  
supply.  
                 
214 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Enables/disables DC switch monitoring via the DIIL input.  
This setting is intended for use with inverter modules with an  
internal charging circuit that are connected to the DC bus  
through a DC switch.  
An auxiliary contact of the DC switch must be wired to the  
DIIL input so that the input switches off when the DC switch is  
opened.  
DC bus  
DC switch  
Inverter module  
Charging  
logic  
Charging  
contactor  
M
If the DC switch is opened with the inverter running, the  
inverter is given a coast-to-stop command, and its charging  
circuit activated.  
Starting the inverter is prevented until the DC switch is closed  
and the DC circuit in the inverter unit recharged.  
Note: An internal charging circuit is standard on some  
inverter module types but optional on others; check with your  
local ABB representative.  
Disable  
Enable  
DC switch monitoring through the DIIL input disabled.  
DC switch monitoring through the DIIL input enabled.  
0
1
Fuse switch control Activates communication to a BSFC-xx switch fuse controller. Disable  
This setting is intended for use with inverter modules that are  
connected to a DC bus through a DC switch/charging circuit  
controlled by a BSFC-xx switch fuse controller.  
The BSFC controls and monitors the charging of the inverter  
unit, and sends an enable command when the charging has  
finished. When the DC switch is opened, the BSFC stops the  
inverter.  
For more information, see BSFC documentation.  
Disable  
Enable  
Communication with BSFC disabled.  
Communication with BSFC enabled.  
0
1
   
Parameters 215  
No.  
96  
Name/Value  
Description  
Def/FbEq16  
Language selection; parameter save and restore; control unit  
reboot.  
Selects the language of the parameter interface and other  
displayed information when viewed on the control panel.  
Notes:  
-
• Not all languages listed below are necessarily supported.  
• This parameter does not affect the languages visible in the  
Drive composer PC tool. (Those are specified under View  
– Settings.)  
Not selected  
English US  
Deutsch  
None.  
0
US English.  
German.  
Italian.  
1033  
1031  
1040  
3082  
2070  
1043  
1036  
1030  
1035  
1053  
1049  
1055  
0
Italiano  
Español  
Spanish.  
Portuguese.  
Dutch.  
Portugues  
Nederlands  
Français  
Dansk  
French.  
Danish.  
Suomi  
Finnish.  
Svenska  
Russki  
Swedish.  
Russian.  
Turkish.  
Reserved.  
Pass code.  
Türkçe  
0…99999999  
-
Selects the application macro. See chapter Application  
macros (page 57) for more information.  
After a selection is made, the parameter reverts automatically  
Done  
Macro selection complete; normal operation.  
Factory macro (see page 58).  
Hand/Auto macro (see page 60).  
PID control macro (see page 62).  
Torque control macro (see page 66).  
Sequential control macro (see page 68).  
Reserved.  
0
Factory  
1
Hand/Auto  
PID-CTRL  
T-CTRL  
2
3
4
Sequence control  
FIELDBUS  
5
6
Shows which application macro is currently selected. See  
chapter Application macros (page 57) for more information.  
To change the macro, use parameter 96.04 Macro select.  
Factory  
Factory  
Factory macro (see page 58).  
1
2
3
4
5
6
Hand/Auto  
PID-CTRL  
T-CTRL  
Hand/Auto macro (see page 60).  
PID control macro (see page 62).  
Torque control macro (see page 66).  
Sequential control macro (see page 68).  
Fieldbus control macro (see page 71).  
Sequence control  
FIELDBUS  
                 
216 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Restores the original settings of the control program, ie.  
parameter default values.  
Note: This parameter cannot be changed while the drive is  
running.  
Done  
Restoring is completed.  
0
8
Restore defaults  
All editable parameter values are restored to default values,  
except  
• motor data and ID run results  
• control panel/PC communication settings  
• fieldbus adapter settings  
• encoder configuration data.  
Clear all  
All editable parameter values are restored to default values,  
except  
62  
• control panel/PC communication settings  
• fieldbus adapter settings  
• encoder configuration data.  
PC tool communication is interrupted during the restoring.  
The drive control unit is re-booted after the restoring is  
completed.  
Saves the valid parameter values to permanent memory.  
Note: A new parameter value is saved automatically when  
changed from the PC tool or panel but not when altered  
through a fieldbus adapter connection.  
Done  
Save  
Save completed.  
Save in progress.  
0
1
0
Control board boot Changing the value of this parameter to 1 reboots the control  
unit. The value reverts to 0 automatically.  
0…4294967295  
1 = Reboot control unit.  
1 = 1  
96  
Switching frequency; slip gain; voltage reserve; flux braking;  
signal injection; IR compensation.  
An optimization setting for balancing between control  
performance and motor noise level.  
Cyclic  
Control performance optimized for cyclic load applications.  
Note: With this setting, the maximum motor cable length is  
smaller than with Normal.  
0
Low noise  
Minimizes motor noise; control performance optimized for  
high (> 300 Hz) output frequencies.  
1
2
Note: Drive loadability is reduced with this setting and some  
derating must be applied if a certain constant output current is  
needed. This setting is not recommended for cyclic load  
applications. The maximum motor cable length is 50 m  
(164 ft) with drives up to 45 kW.  
Normal  
Control performance optimized for long motor cables.  
                           
Parameters 217  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the slip gain which is used to improve the estimated 100%  
motor slip. 100% means full slip gain; 0% means no slip gain.  
The default value is 100%. Other values can be used if a  
static speed error is detected despite of the full slip gain.  
Example (with nominal load and nominal slip of 40 rpm): A  
1000 rpm constant speed reference is given to the drive.  
Despite of the full slip gain (= 100%), a manual tachometer  
measurement from the motor axis gives a speed value of 998  
rpm. The static speed error is 1000 rpm - 998 rpm = 2 rpm. To  
compensate the error, the slip gain should be increased. At  
the 105% gain value, no static speed error exists (2 rpm / 40  
rpm = 5%).  
0 … 200%  
Slip gain.  
1 = 1%  
0%  
Defines the minimum allowed voltage reserve. When the  
voltage reserve has decreased to the set value, the drive  
enters the field weakening area.  
If the intermediate circuit DC voltage Udc = 550 V and the  
voltage reserve is 5%, the RMS value of the maximum output  
voltage in steady-state operation is  
0.95 × 550 V / sqrt(2) = 369 V  
The dynamic performance of the motor control in the field  
weakening area can be improved by increasing the voltage  
reserve value, but the drive enters the field weakening area  
earlier.  
-4 … 50%  
Disabled  
Voltage reserve.  
1 = 1%  
Defines the level of braking power.  
Flux braking is disabled.  
0
1
Moderate  
Flux level is limited during the braking. Deceleration time is  
longer compared to full braking.  
Full  
Maximum braking power. Almost all available current is used  
to convert the mechanical braking energy to thermal energy  
in the motor.  
2
Defines the source of flux reference.  
Zero  
None.  
0
User flux reference Parameter 97.07 User flux reference.  
Other The value is taken from another parameter.  
-
User flux reference Defines the flux reference when parameter 97.06 Flux  
100%  
0…200%  
User-defined flux reference.  
100 = 1%  
Enables signal injection: a high-frequency alternating signal is Disabled  
injected to the motor in the low speed region to improve the  
stability of torque control. Signal injection can be enabled with  
different amplitude levels.  
Notes:  
• Use as low a level as possible that gives satisfactory  
performance.  
• Signal injection cannot be applied to asynchronous  
motors.  
Disabled  
Signal injection disabled.  
0
1
2
Enabled (5 %)  
Enabled (10 %)  
Signal injection enabled with amplitude level of 5%.  
Signal injection enabled with amplitude level of 10%.  
                 
218 Parameters  
No.  
Name/Value  
Enabled (15 %)  
Enabled (20 %)  
Description  
Def/FbEq16  
Signal injection enabled with amplitude level of 15%.  
Signal injection enabled with amplitude level of 20%.  
3
4
Rotor time constant tuning.  
100%  
This parameter can be used to improve torque accuracy in  
closed-loop control of an induction motor. Normally, the motor  
identification run provides sufficient torque accuracy, but  
manual fine-tuning can be applied in exceptionally  
demanding applications to achieve optimal performance.  
25…400%  
Rotor time constant tuning.  
1 = 1%  
0.00%  
Defines the relative output voltage boost at zero speed (IR  
compensation). The function is useful in applications with a  
high break-away torque where direct torque control (DTC  
mode) cannot be applied.  
U / UN  
(%)  
Relative output voltage. IR  
compensation set to 15%.  
100%  
Relative output voltage. No  
15%  
IR compensation.  
f (Hz)  
Field weakening point  
50% of nominal  
frequency  
page 33.  
0.00 … 50.00%  
Voltage boost at zero speed in percent of nominal motor  
voltage.  
1 = 1%  
98  
Motor values supplied by the user that are used in the motor  
model.  
Activates the motor model parameters 98.0298.14 and the No  
rotor angle offset parameter 98.15.  
Notes:  
• Parameter value is automatically set to zero when ID run is  
The values of parameters 98.0298.15 are updated  
according to the motor characteristics identified during the  
ID run.  
• Measurements made directly from the motor terminals are  
likely to produce slightly different values than those  
detected by the ID run.  
• This parameter cannot be changed while the drive is  
running.  
No  
Parameters 98.0298.15 inactive.  
0
         
Parameters 219  
No.  
Name/Value  
Description  
Def/FbEq16  
Motor parameters  
The values of parameters 98.0298.14 are used in the motor  
model.  
1
2
3
Position offset  
The value of parameter 98.15 is used as the rotor angle  
offset. Parameters 98.0298.14 are inactive.  
Motor parameters & The values of parameters 98.0298.14 are used in the motor  
position offset  
model, and the value of parameter 98.15 is used as the rotor  
angle offset.  
Defines the stator resistance RS of the motor model.  
With a star-connected motor, RS is the resistance of one  
winding. With a delta-connected motor, RS is one-third of the  
resistance of one winding.  
0.00000 p.u.  
0.00000 … 0.50000 Stator resistance in per unit.  
p.u.  
-
Defines the rotor resistance RR of the motor model.  
Note: This parameter is valid only for asynchronous motors.  
0.00000 p.u.  
0.00000 … 0.50000 Rotor resistance in per unit.  
p.u.  
-
Defines the main inductance LM of the motor model.  
Note: This parameter is valid only for asynchronous motors.  
0.00000 p.u.  
0.00000 …  
10.00000 p.u.  
Main inductance in per unit.  
-
Defines the leakage inductance LS.  
0.00000 p.u.  
-
Note: This parameter is valid only for asynchronous motors.  
0.00000 … 1.00000 Leakage inductance in per unit.  
p.u.  
Defines the direct axis (synchronous) inductance.  
0.00000 p.u.  
Note: This parameter is valid only for permanent magnet  
motors.  
0.00000 …  
Direct axis inductance in per unit.  
-
10.00000 p.u  
Defines the quadrature axis (synchronous) inductance.  
Note: This parameter is valid only for permanent magnet  
motors.  
0.00000 p.u.  
0.00000 …  
10.00000 p.u  
Quadrature axis inductance in per unit.  
-
Defines the permanent magnet flux.  
Note: This parameter is valid only for permanent magnet  
motors.  
0.00000 p.u.  
0.00000 … 2.00000 Permanent magnet flux in per unit.  
p.u  
-
Defines the stator resistance RS of the motor model.  
0.00000 ohm  
-
0.00000 …  
100.00000 ohm  
Stator resistance.  
Defines the rotor resistance RR of the motor model.  
Note: This parameter is valid only for asynchronous motors.  
0.00000 ohm  
-
0.00000 …  
Rotor resistance.  
100.00000 ohm  
 
220 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the main inductance LM of the motor model.  
0.00 mH  
Note: This parameter is valid only for asynchronous motors.  
0.00 …100000.00  
mH  
Main inductance.  
1 = 10000  
mH  
Defines the leakage inductance LS.  
0.00 mH  
Note: This parameter is valid only for asynchronous motors.  
0.00 …100000.00  
mH  
Leakage inductance.  
1 = 10000  
mH  
Defines the direct axis (synchronous) inductance.  
Note: This parameter is valid only for permanent magnet  
motors.  
0.00 mH  
0.00 …100000.00  
mH  
Direct axis inductance.  
1 = 10000  
mH  
Defines the quadrature axis (synchronous) inductance.  
Note: This parameter is valid only for permanent magnet  
motors.  
0.00 mH  
0.00 …100000.00  
mH  
Quadrature axis inductance.  
1 = 10000  
mH  
Position offset user Defines an angle offset between the zero position of the  
synchronous motor and the zero position of the position  
sensor.  
0°  
Notes:  
• The value is in electrical degrees. The electrical angle  
equals the mechanical angle multiplied by the number of  
motor pole pairs.  
• This parameter is valid only for permanent magnet motors.  
0…360°  
Angle offset.  
1 = 1°  
99  
Motor configuration settings.  
Selects the motor type.  
Note: This parameter cannot be changed while the drive is  
running.  
Asynchronous  
motor  
Asynchronous induction motor.  
0
1
Permanent magnet Permanent magnet motor. Three-phase AC synchronous  
motor  
motor with permanent magnet rotor and sinusoidal BackEMF  
voltage.  
Selects the motor control mode.  
DTC  
DTC  
Direct torque control. This mode is suitable for most  
applications.  
0
Note: Instead of direct torque control, use scalar control  
• with multimotor applications 1) if the load is not equally  
shared between the motors, 2) if the motors are of different  
sizes, or 3) if the motors are going to be changed after the  
motor identification (ID run)  
• if the nominal current of the motor is less than 1/6 of the  
nominal output current of the drive  
• if the drive is used with no motor connected (for example,  
for test purposes).  
                       
Parameters 221  
No.  
Name/Value  
Description  
Def/FbEq16  
Scalar  
Scalar control. The outstanding motor control accuracy of  
DTC cannot be achieved in scalar control. Some standard  
features are disabled in scalar control mode.  
Note: Correct motor run requires that the magnetizing current  
of the motor does not exceed 90% of the nominal current of  
the inverter.  
1
See also section Scalar motor control on page 33.  
Defines the nominal motor current. Must be equal to the value 0.0 A  
on the motor rating plate. If multiple motors are connected to  
the drive, enter the total current of the motors.  
Notes:  
• Correct motor run requires that the magnetizing current of  
the motor does not exceed 90% of the nominal current of  
the drive.  
• This parameter cannot be changed while the drive is  
running.  
0.0 … 6400.0 A  
Nominal current of the motor. The allowable range is 1/6…2 × 1 = 1 A  
IHd of the drive (0…2 × IHd with scalar control mode).  
Defines the nominal motor voltage as fundamental phase-to- 0.0 V  
phase rms voltage supplied to the motor at the nominal  
operating point. This setting must match the value on the  
rating plate of the motor.  
Notes:  
• With permanent magnet motors, the nominal voltage is the  
BackEMF voltage at nominal speed of the motor. If the  
voltage is given as voltage per rpm, e.g. 60 V per 1000  
rpm, the voltage for a nominal speed of 3000 rpm is  
3 × 60 V = 180 V. Note that the nominal voltage is not  
equal to the equivalent DC motor voltage (EDCM)  
specified by some motor manufacturers. The nominal  
voltage can be calculated by dividing the EDCM voltage by  
1.7 (or square root of 3).  
• The stress on the motor insulation is always dependent on  
the drive supply voltage. This also applies to the case  
where the motor voltage rating is lower than that of the  
drive and the supply.  
• This parameter cannot be changed while the drive is  
running.  
0.0 … 800.0  
Nominal voltage of the motor.  
10 = 1 V  
Defines the nominal motor frequency.  
Note: This parameter cannot be changed while the drive is  
running.  
50.0 Hz  
0.0 … 500.0 Hz  
Nominal frequency of the motor.  
10 = 1 Hz  
Defines the nominal motor speed. The setting must match the 0 rpm  
value on the rating plate of the motor.  
Note: This parameter cannot be changed while the drive is  
running.  
0 … 30000 rpm  
Nominal speed of the motor.  
1 = 1 rpm  
   
222 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Defines the nominal motor power. The setting must match the 0.00 kW  
value on the rating plate of the motor. If multiple motors are  
connected to the drive, enter the total power of the motors.  
Note: This parameter cannot be changed while the drive is  
running.  
-10000.00 …  
10000.00 kW  
Nominal power of the motor.  
1 = 1 kW  
Motor nominal cosfii Defines the cosphi of the motor for a more accurate motor  
model. (Not applicable to permanent magnet motors.) Not  
obligatory; if set, should match the value on the rating plate of  
the motor.  
0.00  
Note: This parameter cannot be changed while the drive is  
running.  
0.00 … 1.00  
Cosphi of the motor.  
100 = 1  
Defines the nominal motor shaft torque for a more accurate  
motor model. Not obligatory.  
0.000 N•m  
Note: This parameter cannot be changed while the drive is  
running.  
0.00 …  
Nominal motor torque.  
1 = 100 N•m  
4294672329.296  
N•m  
Selects the type of the motor identification performed at the  
next start of the drive (for Direct Torque Control). During the  
identification, the drive will identify the characteristics of the  
motor for optimum motor control. After the ID run, the drive is  
stopped. Note: This parameter cannot be changed while the  
drive is running.  
No  
Once the ID run is activated, it can be cancelled by stopping  
the drive: If ID run has already been performed once,  
parameter is automatically set to NO. If no ID run has been  
performed yet, parameter is automatically set to Standstill. In  
this case, the ID run must be performed.  
Notes:  
• ID run cannot be performed if parameter 99.04 Motor ctrl  
mode is set to Scalar.  
• ID run must be performed every time any of the motor  
parameters (99.04, 99.0699.12) have been changed.  
Parameter is automatically set to Standstill after the motor  
parameters have been set.  
With a permanent magnet or synchronous reluctance  
motor, the motor shaft must NOT be locked and the load  
torque must be < 10% during the ID run  
(Normal/Reduced/Standstill). For the Advanced ID run, the  
machinery must always be de-coupled from the motor.  
• Ensure that possible Safe Torque Off and emergency stop  
circuits are closed during ID run.  
• Mechanical brake is not opened by the logic for the ID run.  
No  
No motor ID run is requested. This mode can be selected  
only if the ID run (Normal/Reduced/Standstill/Advanced) has  
already been performed once.  
0
           
Parameters 223  
No.  
Name/Value  
Description  
Def/FbEq16  
Normal  
Normal ID run. Guarantees good control accuracy for all  
1
cases. The ID run takes about 90 seconds. This mode should  
be selected whenever it is possible.  
Notes:  
• The driven machinery must be de-coupled from the motor  
with Normal ID run, if the load torque is higher than 20%,  
or if the machinery is not able to withstand the nominal  
torque transient during the ID run.  
• Check the direction of rotation of the motor before starting  
the ID run. During the run, the motor will rotate in the  
forward direction.  
WARNING! The motor will run at up to approximately  
50…100% of the nominal speed during the ID run.  
ENSURE THAT IT IS SAFE TO RUN THE MOTOR  
BEFORE PERFORMING THE ID RUN!  
Reduced  
Reduced ID Run. This mode should be selected instead of  
the Normal or Advanced ID Run if  
2
• mechanical losses are higher than 20% (i.e. the motor  
cannot be de-coupled from the driven equipment), or if  
• flux reduction is not allowed while the motor is running (i.e.  
in case of a motor with an integrated brake supplied from  
the motor terminals).  
With Reduced ID run, the control in the field weakening area  
or at high torques is not necessarily as accurate as with the  
Normal ID run. Reduced ID run is completed faster than the  
Normal ID Run (< 90 seconds).  
Note: Check the direction of rotation of the motor before  
starting the ID run. During the run, the motor will rotate in the  
forward direction.  
WARNING! The motor will run at up to approximately  
50…100% of the nominal speed during the ID run.  
ENSURE THAT IT IS SAFE TO RUN THE MOTOR  
BEFORE PERFORMING THE ID RUN!  
Standstill  
Standstill ID run. The motor is injected with DC current. With  
an asynchronous motor, the motor shaft is not rotating (with  
permanent magnet motor the shaft can rotate < 0.5  
revolution).  
Note: This mode should be selected only if the Normal,  
Reduced or Advanced ID run is not possible due to the  
restrictions caused by the connected mechanics (e.g. with lift  
or crane applications).  
3
4
Autophasing  
During autophasing, the start angle of the motor is  
determined. Note that other motor model values are not  
updated. See also parameter 21.13 Autophasing mode.  
Notes:  
• Autophasing can only be selected after the  
Normal/Reduced/Standstill/Advanced ID run has been  
performed once. Autophasing is used with a permanent  
magnet motor when an absolute encoder, a resolver or an  
encoder with commutation signals has been added or  
replaced, and there is no need to perform the  
Normal/Reduced/Standstill/Advanced ID run again.  
• During Autophasing, the motor shaft must NOT be locked  
and the load torque must be < 5%.  
Current  
measurement  
calibration  
Current offset and gain measurement calibration. The  
calibration will be performed at next start.  
5
   
224 Parameters  
No.  
Name/Value  
Description  
Def/FbEq16  
Advanced  
Advanced ID run. Guarantees the best possible control  
accuracy. The ID run can take a couple of minutes. This mode  
should be selected when top performance is needed in the  
whole operating area.  
6
Notes:  
• The driven machinery must be de-coupled from the motor  
because of high torque and speed transients that are  
applied.  
• During the run, the motor may rotate both in the forward  
and reverse direction.  
WARNING! The motor may run at up to the maximum  
(positive) and minimum (negative) allowed speed  
during the ID run. Several accelerations and  
decelerations are done. The maximum torque, current and  
speed allowed by the limit parameters may be utilized.  
ENSURE THAT IT IS SAFE TO RUN THE MOTOR BEFORE  
PERFORMING THE ID RUN!  
Shows the mode of the ID run that was performed last. For  
more information of the different modes, see the selections of  
No  
No ID run has been performed.  
Normal ID run.  
0
1
2
3
Normal  
Reduced  
Standstill  
Autophasing  
Reduced ID run.  
Standstill ID run.  
Current  
measurement  
calibration  
Advanced  
6
0…1000  
Calculated number of pole pairs in the motor.  
Number of pole pairs.  
0
1 = 1  
Switches the rotation direction of motor. This parameter can  
be used if the motor turns in the wrong direction (for example,  
because of the wrong phase order in the motor cable), and  
correcting the cabling is considered impractical.  
Note: After changing this parameter, the sign of encoder  
feedback (if any) must be checked. This can be done by  
Estimate, and comparing the sign of 90.01 Motor speed for  
speed). If the sign of the measurement is incorrect, the  
encoder wiring must be corrected or the sign of 90.43 Motor  
U V W  
U W V  
Normal.  
0
1
Reversed rotation direction.  
       
Additional parameter data 225  
7
Additional parameter data  
What this chapter contains  
This chapter lists the parameters with some additional data. For parameter  
descriptions, see chapter Parameters (page 73).  
Terms and abbreviations  
Term  
Definition  
Actual signal  
Signal measured or calculated by the drive. Usually can only be monitored  
but not adjusted; some counter-type signals can however be reset.  
Analog src  
Binary src  
The parameter can be set to the value of another parameter by choosing  
“Other”, and selecting the source parameter from a list.  
In addition to the “Other” selection, the parameter may offer other pre-  
selected settings.  
The value of the parameter can be taken from a specific bit in another  
parameter value (“Other”). Sometimes the value can be fixed to 0 (false) or  
1 (true). In addition, the parameter may offer other pre-selected settings.  
Data  
Data parameter.  
FbEq32  
32-bit fieldbus equivalent: The scaling between the value shown on the  
panel and the integer used in fieldbus communication when a 32-bit value  
is selected in parameter group 52 FBA A data in or 53 FBA A data out.  
The corresponding 16-bit scalings are listed in chapter Parameters (page  
List  
No.  
Selection list.  
Parameter number.  
             
226 Additional parameter data  
Term  
PB  
Definition  
Packed Boolean (bit list).  
Real  
Type  
Real number.  
Parameter type. See Analog src, Binary src, List, PB, Real.  
Fieldbus addresses  
Refer to the User’s Manual of the fieldbus adapter.  
     
Additional parameter data 227  
Parameter groups 1…9  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
01 Actual values  
01.01 Motor speed used  
01.02 Motor speed estimated  
01.04 Encoder 1 speed filtered  
01.05 Encoder 2 speed filtered  
01.06 Output frequency  
01.07 Motor current  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-3000.00 … 3000.00  
0.00 … 30000.00  
-1600.0 … 1600.0  
0.00 … 2000.00  
-32768.00 … 32767.00  
0…65535  
rpm  
rpm  
rpm  
rpm  
Hz  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 Hz  
100 = 1 A  
A
01.10 Motor torque %  
%
10 = 1%  
01.11 DC voltage  
V
100 = 1 V  
01.14 Output power  
kW  
GWh  
MWh  
kWh  
%
100 = 1 kW  
1 = 1 GWh  
1 = 1 MWh  
1 = 1 kWh  
1 = 1%  
01.18 Inverter GWh counter  
01.19 Inverter MWh counter  
01.20 Inverter kWh counter  
01.24 Flux actual %  
0…999  
0…999  
0…200  
01.30 Nominal torque scale  
01.31 Ambient temperature  
-
N•m  
°C  
1000 = 1 N•m  
10 = 1 °C  
-32768.0…32767.0  
03 Input references  
03.01 Panel reference  
03.05 FB A reference 1  
03.06 FB A reference 2  
03.15 Application reference 1  
03.16 Application reference 2  
04 Warnings and faults  
04.01 Tripping fault  
-100000.00 … 100000.00  
-100000.00 … 100000.00  
-100000.00 … 100000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-
-
-
-
-
100 = 1  
100 = 1  
100 = 1  
100 = 1  
100 = 1  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
04.02 Active fault 2  
04.03 Active fault 3  
04.04 Active fault 4  
04.05 Active fault 5  
04.06 Active warning 1  
04.07 Active warning 2  
04.08 Active warning 3  
04.09 Active warning 4  
04.10 Active warning 5  
04.11 Latest fault  
04.12 2nd latest fault  
04.13 3rd latest fault  
04.14 4th latest fault  
04.15 5th latest fault  
04.16 Latest warning  
04.17 2nd latest warning  
                                                                                                                                                   
228 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
1 = 1  
04.18 3rd latest warning  
04.19 4th latest warning  
04.20 5th latest warning  
05 Diagnostics  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
-
-
-
1 = 1  
1 = 1  
05.01 On-time counter  
05.02 Run-time counter  
05.04 Fan on-time counter  
05.11 Inverter temperature %  
06 Control and status words  
06.01 Main control word  
06.02 Application control word  
0…4294967295  
0…4294967295  
0…4294967295  
-40.0 … 160.0  
d
d
1 = 1 d  
1 = 1 d  
1 = 1 d  
10 = 1%  
d
%
0000h…FFFFh  
0000h…FFFFh  
-
-
-
1 = 1  
1 = 1  
1 = 1  
06.03 FBA A transparent control  
word  
00000000h…FFFFFFFFh  
06.11 Main status word  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
-
-
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
06.16 Drive status word 1  
06.17 Drive status word 2  
06.18 Start inhibit status word  
06.19 Speed control status word  
06.20 Constant speed status word  
06.30 User bit 0 selection  
Binary  
src  
06.31 User bit 1 selection  
06.32 User bit 2 selection  
06.33 User bit 3 selection  
Binary  
src  
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
Binary  
src  
Binary  
src  
07 System info  
07.03 Drive rating id  
07.04 Firmware name  
07.05 Firmware version  
07.11 Cpu usage  
0…999  
-
-
1 = 1  
1 = 1  
-
-
1 = 1  
0…100  
%
1 = 1%  
                                                                                                     
Additional parameter data 229  
Parameter groups 10…99  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
10 Standard DI, RO  
10.01 DI status  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0000h…FFFFh  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0.0 … 3000.0  
0000h…FFFFh  
-
-
-
1 = 1  
1 = 1  
10.02 DI delayed status  
10.03 DI force selection  
10.04 DI force data  
10.05 DI1 ON delay  
10.06 DI1 OFF delay  
10.07 DI2 ON delay  
10.08 DI2 OFF delay  
10.09 DI3 ON delay  
10.10 DI3 OFF delay  
10.11 DI4 ON delay  
10.12 DI4 OFF delay  
10.13 DI5 ON delay  
10.14 DI5 OFF delay  
10.15 DI6 ON delay  
10.16 DI6 OFF delay  
10.21 RO status  
-
1 = 1  
-
1 = 1  
s
s
s
s
s
s
s
s
s
s
s
s
-
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
10 = 1 s  
1 = 1  
10.24 RO1 source  
Binary  
src  
-
1 = 1  
10.25 RO1 ON delay  
10.26 RO1 OFF delay  
10.27 RO2 source  
0.0 … 3000.0  
0.0 … 3000.0  
-
s
s
-
10 = 1 s  
10 = 1 s  
1 = 1  
Binary  
src  
10.28 RO2 ON delay  
10.29 RO2 OFF delay  
10.30 RO3 source  
0.0 … 3000.0  
0.0 … 3000.0  
-
s
s
-
10 = 1 s  
10 = 1 s  
1 = 1  
Binary  
src  
10.31 RO3 ON delay  
10.32 RO3 OFF delay  
0.0 … 3000.0  
0.0 … 3000.0  
s
s
10 = 1 s  
10 = 1 s  
11 Standard DIO, FI, FO  
11.01 DIO status  
00000000b…11111111b  
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
11.02 DIO delayed status  
11.05 DIO1 configuration  
11.06 DIO1 output source  
00000000b…11111111b  
0…2  
-
Binary  
src  
11.07 DIO1 ON delay  
11.08 DIO1 OFF delay  
11.09 DIO2 configuration  
11.10 DIO2 output source  
0.0 … 3000.0  
s
s
-
10 = 1 s  
10 = 1 s  
1 = 1  
0.0 … 3000.0  
0…2  
-
Binary  
src  
1 = 1  
                                                                                                                                             
230 Additional parameter data  
No.  
Name  
Type  
Range  
0.0 … 3000.0  
0.0 … 3000.0  
0…16000  
Unit  
s
FbEq32  
10 = 1 s  
10 = 1 s  
1 = 1 Hz  
1000 = 1  
1 = 1 Hz  
1 = 1 Hz  
1000 = 1  
1000 = 1  
1 = 1 Hz  
1 = 1  
11.11 DIO2 ON delay  
11.12 DIO2 OFF delay  
11.38 Freq in 1 actual value  
11.39 Freq in 1 scaled  
11.42 Freq in 1 min  
s
Hz  
-
-32768.000 … 32767.000  
0…16000  
Hz  
Hz  
-
11.43 Freq in 1 max  
0…16000  
11.44 Freq in 1 scaled at min  
11.45 Freq in 1 scaled at max  
11.54 Freq out 1 actual value  
11.55 Freq out 1 source  
-32768.000 … 32767.000  
-32768.000 … 32767.000  
0…16000  
-
Hz  
-
-
11.58 Freq out 1 src min  
11.59 Freq out 1 src max  
11.60 Freq out 1 at src min  
11.61 Freq out 1 at src max  
-32768.000 … 32767.000  
-32768.000 … 32767.000  
0…16000  
-
1000 = 1  
1000 = 1  
1 = 1 Hz  
1 = 1 Hz  
-
Hz  
Hz  
0…16000  
12 Standard AI  
12.11 AI1 actual value  
12.12 AI1 scaled value  
12.15 AI1 unit selection  
12.16 AI1 filter time  
12.17 AI1 min  
-22.000 … 22.000  
-32768.000 … 32767.000  
-
mA or V 1000 = 1 unit  
-
-
1000 = 1  
1 = 1  
0.000 … 30.000  
-22.000 … 22.000  
s
1000 = 1 s  
mA or V 1000 = 1 mA  
or V  
12.18 AI1 max  
-22.000 … 22.000  
mA or V 1000 = 1 mA  
or V  
12.19 AI1 scaled at AI1 min  
12.20 AI1 scaled at AI1 max  
12.21 AI2 actual value  
-32768.000 … 32767.000  
-32768.000 … 32767.000  
-22.000 … 22.000  
-
-
1000 = 1  
1000 = 1  
mA or V 1000 = 1 mA  
or V  
12.22 AI2 scaled value  
12.25 AI2 unit selection  
12.26 AI2 filter time  
12.27 AI2 min  
-32768.000 … 32767.000  
-
-
-
1000 = 1  
1 = 1  
0.000 … 30.000  
-22.000 … 22.000  
s
1000 = 1 s  
mA or V 1000 = 1 mA  
or V  
12.28 AI2 max  
-22.000 … 22.000  
mA or V 1000 = 1 mA  
or V  
12.29 AI2 scaled at AI2 min  
12.30 AI2 scaled at AI2 max  
13 Standard AO  
-32768.000 … 32767.000  
-32768.000 … 32767.000  
-
-
1000 = 1  
1000 = 1  
13.11 AO1 actual value  
13.12 AO1 source  
0.000 … 22.000  
-
mA  
-
1000 = 1 mA  
1 = 1  
13.16 AO1 filter time  
13.17 AO1 source min  
0.000 … 30.000  
s
-
1000 = 1 s  
10 = 1  
-32768.0 … 32767.0  
                                                                                                                                           
Additional parameter data 231  
No.  
Name  
Type  
Range  
-32768.0 … 32767.0  
0.000 … 22.000  
0.000 … 22.000  
0.000 … 22.000  
-
Unit  
-
FbEq32  
10 = 1  
13.18 AO1 source max  
13.19 AO1 out at AO1 src min  
13.20 AO1 out at AO1 src max  
13.21 AO2 actual value  
13.22 AO2 source  
mA  
mA  
mA  
-
1000 = 1 mA  
1000 = 1 mA  
1000 = 1 mA  
1 = 1  
13.26 AO2 filter time  
0.000 … 30.000  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
0.000 … 22.000  
s
-
1000 = 1 s  
10 = 1  
13.27 AO2 source min  
13.28 AO2 source max  
13.29 AO2 out at AO2 src min  
13.30 AO2 out at AO2 src max  
-
10 = 1  
mA  
mA  
1000 = 1 mA  
1000 = 1 mA  
0.000 … 22.000  
19 Operation mode  
19.01 Actual operation mode  
19.11 Ext1/Ext2 selection  
-
-
-
-
1 = 1  
1 = 1  
Binary  
src  
19.12 Ext1 control mode 1  
19.14 Ext2 control mode 1  
19.16 Local control mode  
19.17 Local control disable  
19.20 Scalar control reference unit  
20 Start/stop/direction  
1…6  
1…6  
0…1  
0…1  
0…1  
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
20.01 Ext1 commands  
20.02 Ext1 start trigger  
20.03 Ext1 in1  
-
0…1  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
Binary  
src  
20.04 Ext1 in2  
20.05 Ext1 in3  
Binary  
src  
-
-
-
-
1 = 1  
1 = 1  
Binary  
src  
20.06 Ext2 commands  
20.07 Ext2 start trigger  
20.08 Ext2 in1  
-
0…1  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
Binary  
src  
20.09 Ext2 in2  
20.10 Ext2 in3  
Binary  
src  
-
-
-
-
1 = 1  
1 = 1  
Binary  
src  
20.11 Run enable stop mode  
20.12 Run enable 1  
0…2  
-
-
-
1 = 1  
1 = 1  
Binary  
src  
20.19 Enable start command  
Binary  
src  
-
-
-
-
1 = 1  
1 = 1  
20.23 Positive speed reference  
enable  
Binary  
src  
                                                                                                                               
232 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
20.24 Negative speed reference  
enable  
Binary  
src  
-
-
1 = 1  
20.25 Jogging enable  
20.26 Jogging 1 start  
20.27 Jogging 2 start  
Binary  
src  
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
Binary  
src  
Binary  
src  
21 Start/stop mode  
21.01 Start mode  
0…2  
0…10000  
0…1  
-
ms  
-
1 = 1  
1 = 1 ms  
1 = 1  
21.02 Magnetization time  
21.03 Stop mode  
21.04 Emergency stop mode  
21.05 Emergency stop source  
0…2  
-
1 = 1  
Binary  
src  
-
-
1 = 1  
21.06 Zero speed limit  
21.07 Zero speed delay  
21.08 DC current control  
21.09 DC hold speed  
0.00 … 30000.00  
0…30000  
rpm  
ms  
-
100 = 1 rpm  
1 = 1 ms  
1 = 1  
00b…11b  
0.0 … 1000.0  
0.0 … 100.0  
0…30000  
rpm  
%
100 = 1 rpm  
10 = 1%  
1 = 1 ms  
1 = 1  
21.10 DC current reference  
21.11 Post magnetization time  
21.13 Autophasing mode  
21.18 Auto restart time  
ms  
-
0…2  
0.0, 0.1 … 5.0  
s
10 = 1 s  
22 Speed reference selection  
22.01 Speed ref unlimited  
22.11 Speed ref1 selection  
-30000.00 … 30000.00  
-
rpm  
-
100 = 1 rpm  
1 = 1  
22.12 Speed ref2 selection  
-
-
1 = 1  
22.13 Speed ref1 function  
0…5  
-
-
-
1 = 1  
1 = 1  
22.14 Speed ref1/2 selection  
Binary  
src  
22.15 Additive speed ref1  
-
-
1 = 1  
22.16 Speed share  
-8.000 … 8.000  
-
-
-
1000 = 1  
1 = 1  
22.17 Additive speed ref2  
22.21 Constant speed function  
22.22 Constant speed sel1  
00b…11b  
-
-
-
1 = 1  
1 = 1  
Binary  
src  
22.23 Constant speed sel2  
22.24 Constant speed sel3  
22.26 Constant speed 1  
Binary  
src  
-
-
-
1 = 1  
1 = 1  
Binary  
src  
-
-30000.00 … 30000.00  
rpm  
100 = 1 rpm  
                                                                                                                           
Additional parameter data 233  
No.  
Name  
Type  
Range  
Unit  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
-
FbEq32  
22.27 Constant speed 2  
22.28 Constant speed 3  
22.29 Constant speed 4  
22.30 Constant speed 5  
22.31 Constant speed 6  
22.32 Constant speed 7  
22.41 Speed ref safe  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
00b…11b  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
1 = 1  
22.42 Jogging 1 ref  
22.43 Jogging 2 ref  
22.51 Critical speed function  
22.52 Critical speed 1 low  
22.53 Critical speed 1 high  
22.54 Critical speed 2 low  
22.55 Critical speed 2 high  
22.56 Critical speed 3 low  
22.57 Critical speed 3 high  
22.81 Speed reference 1 act  
22.82 Speed reference 2 act  
22.83 Speed reference 3 act  
22.84 Speed reference 4 act  
22.85 Speed reference 5 act  
22.86 Speed reference 6 act  
22.87 Speed reference 7 act  
23 Speed reference ramp  
23.01 Speed ref ramp in  
23.02 Speed ref ramp out  
23.11 Ramp set selection  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
-30000.00 … 30000.00  
rpm  
rpm  
-
100 = 1 rpm  
100 = 1 rpm  
1 = 1  
-30000.00 … 30000.00  
-
Binary  
src  
23.12 Acceleration time 1  
23.13 Deceleration time 1  
23.14 Acceleration time 2  
23.15 Deceleration time 2  
23.16 Shape time acc 1  
23.17 Shape time acc 2  
23.18 Shape time dec 1  
23.19 Shape time dec 2  
23.20 Acc time jogging  
23.21 Dec time jogging  
23.23 Emergency stop time  
23.24 Ramp in zero  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
-
s
s
s
s
s
s
s
s
s
s
s
-
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1 = 1  
Binary  
src  
                                                                                                                                                         
234 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
23.26 Ramp out balance enable  
Binary  
src  
-
-
1 = 1  
23.27 Ramp out balance ref  
23.28 Variable slope enable  
23.29 Variable slope rate  
-30000.00 … 30000.00  
0…1  
rpm  
-
100 = 1 rpm  
1 = 1  
2…30000  
ms  
1 = 1 ms  
24 Speed reference conditioning  
24.01 Used speed reference  
24.02 Used actual speed  
24.03 Speed error filtered  
24.04 Speed error negative  
24.11 Speed correction  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-30000.0 … 30000.0  
-30000.0 … 30000.0  
-10000…10000  
0…10000  
rpm  
rpm  
rpm  
rpm  
-
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1  
24.12 Speed error filter time  
ms  
-
1 = 1 ms  
24.41 Speed error window control  
enable  
0…1  
1 = 1  
24.43 Speed error window high  
24.44 Speed error window low  
24.46 Speed error step  
0…3000  
0…3000  
rpm  
rpm  
rpm  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 rpm  
-3000.0 … 3000.0  
25 Speed control  
25.01 Torque reference speed  
control  
-1600.0 … 1600.0  
%
10 = 1%  
25.02 Proportional gain  
25.03 Integration time  
0.00 … 250.00  
0.00 … 1000.00  
0.000 … 10000.000  
0.0 … 1000.0  
0.00 … 1000.00  
0.0 … 1000.0  
0.00 … 100.00  
-
-
s
100 = 1  
100 = 1 s  
1000 = 1 s  
1 = 1 ms  
100 = 1 s  
10 = 1 ms  
100 = 1%  
1 = 1  
25.04 Derivation time  
s
25.05 Derivation filter time  
25.06 Acc comp derivation time  
25.07 Acc comp filter time  
25.08 Drooping rate  
ms  
s
ms  
%
-
25.09 Speed ctrl balance enable  
Binary  
src  
25.10 Speed ctrl balance reference  
25.11 Min torque speed control  
25.12 Max torque speed control  
25.15 Proportional gain em stop  
25.53 Torque prop reference  
25.54 Torque integ reference  
25.55 Torque der reference  
25.56 Torque acc compensation  
25.57 Torque reference unbalanced  
26 Torque reference chain  
-300 … 300  
-
10 = 1  
-1600.0 … 0.0  
%
%
-
10 = 1%  
10 = 1%  
100 = 1  
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1%  
0.0 … 1600.0  
0.00 … 250.00  
-30000.0 … 30000.0  
-30000.0 … 30000.0  
-30000.0 … 30000.0  
-30000.0 … 30000.0  
-30000.0 … 30000.0  
%
%
%
%
%
26.01 Torque ref to TC  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
-1000.0 … 0.0  
%
%
%
10 = 1%  
10 = 1%  
10 = 1%  
26.02 Torque ref used  
26.08 Minimum torque ref  
                                                                                                                                                 
Additional parameter data 235  
No.  
Name  
Type  
Range  
Unit  
%
FbEq32  
10 = 1%  
1 = 1  
26.09 Maximum torque ref  
26.11 Torque ref1 selection  
0.0 … 1000.0  
-
-
26.12 Torque ref2 selection  
-
-
1 = 1  
26.13 Torque ref1 function  
0…5  
-
-
-
1 = 1  
1 = 1  
26.14 Torque ref1/2 selection  
Binary  
src  
26.15 Load share  
-8.000 … 8.000  
-
-
-
1000 = 1  
1 = 1  
26.16 Torque additive 1 source  
26.17 Torque ref filter time  
26.18 Torque ramp up time  
26.19 Torque ramp down time  
26.25 Torque additive 2 source  
0.000 … 30.000  
0.000 … 60.000  
0.000 … 60.000  
-
s
s
s
-
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1 = 1  
26.26 Force torque ref add 2 zero  
Binary  
src  
-
-
1 = 1  
26.41 Torque step  
-300.00 … 300.00  
0…1  
%
-
100 = 1%  
1 = 1  
26.42 Torque step enable  
26.70 Torque ref1 actual  
26.71 Torque ref2 actual  
26.72 Torque ref3 actual  
26.73 Torque ref4 actual  
26.74 Torque ref ramped  
26.75 Torque ref5 actual  
26.76 Torque ref6 actual  
26.77 Torque ref add A actual  
26.78 Torque ref add B actual  
26.81 Rush control gain  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
1.0 … 10000.0  
0.1 … 10.0  
%
%
%
%
%
%
%
%
%
-
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1%  
10 = 1  
26.82 Rush control integration time  
28 Frequency reference chain  
28.01 Frequency ref ramp in  
28.02 Frequency ref ramped  
28.11 Frequency ref1 selection  
s
10 = 1 s  
-3000.0 … 3000.0  
Hz  
Hz  
-
100 = 1 Hz  
100 = 1 Hz  
1 = 1  
-3000.0 … 3000.0  
-
28.12 Frequency ref2 selection  
-
-
1 = 1  
28.13 Frequency ref1 function  
28.14 Frequency ref1/2 selection  
0…5  
-
-
-
1 = 1  
1 = 1  
Binary  
src  
28.21 Constant frequency function  
28.22 Constant frequency sel1  
00b…11b  
-
-
-
1 = 1  
1 = 1  
Binary  
src  
                                                                                                                                     
236 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
28.23 Constant frequency sel2  
Binary  
src  
-
-
1 = 1  
28.24 Constant frequency sel3  
Binary  
src  
-
-
1 = 1  
28.26 Constant frequency 1  
28.27 Constant frequency 2  
28.28 Constant frequency 3  
28.29 Constant frequency 4  
28.30 Constant frequency 5  
28.31 Constant frequency 6  
28.32 Constant frequency 7  
28.41 Failure frequency ref  
28.51 Critical frequency function  
28.52 Critical frequency 1 low  
28.53 Critical frequency 1 high  
28.54 Critical frequency 2 low  
28.55 Critical frequency 2 high  
28.56 Critical frequency 3 low  
28.57 Critical frequency 3 high  
28.71 Ramp set selection  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
00b…11b  
Hz  
Hz  
Hz  
Hz  
Hz  
Hz  
Hz  
Hz  
-
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
1 = 1  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-
Hz  
Hz  
Hz  
Hz  
Hz  
Hz  
-
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
1 = 1  
Binary  
src  
28.72 Acceleration time 1  
28.73 Deceleration time 1  
28.74 Acceleration time 2  
28.75 Deceleration time 2  
28.76 Ramp in zero  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
0.000 …1800.000  
-
s
s
s
s
-
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1000 = 1 s  
1 = 1  
Binary  
src  
28.77 Ramp hold  
Binary  
src  
-
-
1 = 1  
28.78 Ramp output balance  
-3000.00 … 3000.00  
-
Hz  
-
100 = 1 Hz  
1 = 1  
28.79 Ramp output balance ena  
Binary  
src  
28.80 Frequency ref ramp in sel  
-
-
-
-
1 = 1  
1 = 1  
28.81 Frequency ref in scalar control Analog  
28.90 Frequency ref1 act  
28.91 Frequency ref2 act  
28.92 Frequency ref3 act  
28.96 Frequency ref7 act  
28.97 Frequency ref unlimited  
30 Limits  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
Hz  
Hz  
Hz  
Hz  
Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 Hz  
30.01 Limit word 1  
0000h…FFFFh  
0000h…FFFFh  
-
-
1 = 1  
1 = 1  
30.02 Torque limit status  
                                                                                                                                             
Additional parameter data 237  
No.  
Name  
Type  
Range  
-30000.00 … 30000.00  
-30000.00 … 30000.00  
-3000.00 … 3000.00  
-3000.00 … 3000.00  
0.00 … 30000.00  
-1600.0 … 1600.0  
-1600.0 … 1600.0  
0.00 … 600.00  
Unit  
rpm  
rpm  
Hz  
Hz  
A
FbEq32  
100 = 1 rpm  
100 = 1 rpm  
100 = 1 Hz  
100 = 1 Hz  
100 = 1 A  
10 = 1%  
30.11 Minimum speed  
30.12 Maximum speed  
30.13 Minimum frequency  
30.14 Maximum frequency  
30.17 Maximum current  
30.19 Minimum torque  
%
30.20 Maximum torque  
30.26 Power motoring limit  
30.27 Power generating limit  
30.30 Overvoltage control  
30.31 Undervoltage control  
31 Fault functions  
%
10 = 1%  
%
100 = 1%  
100 = 1%  
1 = 1  
-600.00 … 0.00  
0…1  
%
-
0…1  
-
1 = 1  
31.01 External event 1 source  
Binary  
src  
-
-
1 = 1  
31.02 External event 1 type  
31.11 Fault reset selection  
0…1  
-
-
-
1 = 1  
1 = 1  
Binary  
src  
31.12 Autoreset sel  
31.13 Selectable fault  
31.14 Number of trials  
31.15 Trial time  
0000h…FFFFh  
0…65535  
0…5  
-
1 = 1  
1 = 1  
-
-
1 = 1  
1.0 … 600.0  
0.0 … 120.0  
0…1  
s
10 = 1 s  
10 = 1 s  
1 = 1  
31.16 Delay time  
s
31.19 Motor phase loss  
31.20 Earth fault  
-
0…2  
-
-
1 = 1  
31.21 Supply phase loss  
31.22 STO diagnostics  
31.23 Cross connection  
31.24 Stall function  
31.25 Stall current limit  
31.26 Stall speed high  
31.27 Stall frequency high  
31.28 Stall time  
0…1  
1 = 1  
0…3  
-
1 = 1  
0…1  
-
1 = 1  
0…2  
-
1 = 1  
0.0 … 1600.0  
0.0 … 10000.0  
0.0 … 1000.0  
0…3600  
0…10000  
%
rpm  
Hz  
s
10 = 1%  
100 = 1 rpm  
100 = 1 Hz  
1 = 1 s  
100 = 1 rpm  
31.30 Speed trip margin  
32 Supervision  
rpm  
32.01 Supervision status  
32.05 Superv1 function  
32.06 Superv1 action  
32.07 Superv1 signal  
000b…111b  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
0…6  
0…2  
-
32.08 Superv1 filter time  
32.09 Superv1 lo  
0.000 … 30.000  
s
-
1000 = 1 s  
100 = 1  
-21474836.48 …  
21474836.47  
                                                                                                                                                   
238 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
32.10 Superv1 hi  
-21474836.48 …  
21474836.47  
-
100 = 1  
32.15 Superv2 function  
32.16 Superv2 action  
32.17 Superv2 signal  
0…6  
0…2  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
32.18 Superv2 filter time  
32.19 Superv2 lo  
0.000 … 30.000  
s
-
1000 = 1 s  
100 = 1  
-21474836.48 …  
21474836.47  
32.20 Superv2 hi  
-21474836.48 …  
21474836.47  
-
100 = 1  
32.25 Superv3 function  
32.26 Superv3 action  
32.27 Superv3 signal  
0…6  
0…2  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
32.28 Superv3 filter time  
32.29 Superv3 lo  
0.000 … 30.000  
s
-
1000 = 1 s  
100 = 1  
-21474836.48 …  
21474836.47  
32.30 Superv3 hi  
-21474836.48 …  
21474836.47  
-
100 = 1  
33 Maintenance timer & counter  
33.01 Counter status  
000000b…111111b  
0…4294967295  
0…4294967295  
00b…11b  
-
s
s
-
1 = 1  
1 = 1 s  
1 = 1 s  
1 = 1  
33.10 On-time 1 actual  
33.11 On-time 1 limit  
33.12 On-time 1 function  
33.13 On-time 1 source  
Binary  
src  
-
-
1 = 1  
33.14 On-time 1 warning select  
33.20 On-time 2 actual  
33.21 On-time 2 limit  
-
-
s
s
-
1 = 1  
1 = 1 s  
1 = 1 s  
1 = 1  
0…4294967295  
0…4294967295  
00b…11b  
-
33.22 On-time 2 function  
33.23 On-time 2 source  
Binary  
src  
-
1 = 1  
33.24 On-time 2 warning select  
33.30 Edge counter 1 actual  
33.31 Edge counter 1 limit  
33.32 Edge counter 1 func  
33.33 Edge counter 1 source  
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
0…4294967295  
0…4294967295  
0000b…1111b  
-
Binary  
src  
33.34 Edge counter 1 divider  
1…4294967295  
-
-
-
1 = 1  
1 = 1  
33.35 Edge counter 1 warning  
selection  
33.40 Edge counter 2 actual  
33.41 Edge counter 2 limit  
33.42 Edge counter 2 function  
0…4294967295  
0…4294967295  
0000b…1111b  
-
-
-
1 = 1  
1 = 1  
1 = 1  
                                                                                                                                     
Additional parameter data 239  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
33.43 Edge counter 2 source  
Binary  
src  
-
-
1 = 1  
33.44 Edge counter 2 divider  
1…4294967295  
-
-
-
1 = 1  
1 = 1  
33.45 Edge counter 2 warning  
selection  
33.50 Value counter 1 actual  
-2147483008 …  
2147483008  
-
-
1 = 1  
1 = 1  
33.51 Value counter 1 limit  
-2147483008 …  
2147483008  
33.52 Value counter 1 function  
33.53 Value counter 1 source  
00b…11b  
-
-
-
1 = 1  
1 = 1  
33.54 Value counter 1 divider  
33.55 Value counter 1 warning select  
33.60 Value counter 2 actual  
0.001 … 2147483.647  
-
-
-
-
1000 = 1  
1 = 1  
-2147483008 …  
2147483008  
1 = 1  
33.61 Value counter 2 limit  
-2147483008 …  
2147483008  
-
1 = 1  
33.62 Value counter 2 function  
33.63 Value counter 2 source  
00b…11b  
-
-
-
1 = 1  
1 = 1  
33.64 Value counter 2 divider  
0.001 … 2147483.647  
-
-
-
1000 = 1  
1 = 1  
33.65 Value counter 2 warning  
selection  
35 Motor thermal protection  
35.01 Motor estimated temperature  
35.02 Measured temperature 1  
-60 … 1000  
-10 … 1000  
°C  
1 = 1 °C  
1 = 1 °C  
°C or  
ohm  
35.03 Measured temperature 2  
-10 … 1000  
°C or  
ohm  
1 = 1 °C  
35.10 Supervision 1 protection  
35.11 Supervision 1 source  
35.12 Supervision 1 fault limit  
0…2  
0…11  
-
-
1 = 1  
1 = 1  
-10 … 1000  
°C or  
ohm  
1 = 1 °C  
35.13 Supervision 1 warning limit  
35.14 Supervision 1 AI select  
-10 … 1000  
-
°C or  
ohm  
1 = 1 °C  
1 = 1  
-
35.20 Supervision 2 protection  
35.21 Supervision 2 source  
35.22 Supervision 2 fault limit  
0…2  
0…11  
-
-
1 = 1  
1 = 1  
-10 … 1000  
°C or  
ohm  
1 = 1 °C  
35.23 Supervision 2 warning limit  
35.24 Supervision 2 AI select  
35.50 Motor ambient temperature  
-10 … 1000  
-
°C or  
ohm  
1 = 1 °C  
1 = 1  
-
-60…100  
°C  
1 = 1 °C  
                                                                                                                     
240 Additional parameter data  
No.  
Name  
Type  
Range  
50…150  
Unit  
%
FbEq32  
1 = 1%  
35.51 Motor load curve  
35.52 Zero speed load  
35.53 Break point  
50…150  
%
1 = 1%  
1.00 … 500.00  
0…300  
Hz  
°C  
s
100 = 1 Hz  
1 = 1 °C  
1 = 1 s  
35.54 Motor nominal temp rise  
35.55 Motor thermal time const  
36 Load analyzer  
100…10000  
36.01 PVL signal  
-
-
1 = 1  
36.02 PVL filter time  
36.06 AL2 signal  
0.00 … 120.00  
-
s
-
100 = 1 s  
1 = 1  
36.07 AL2 signal base  
36.09 Reset loggers  
36.10 PVL peak value  
36.11 PVL peak date  
36.12 PVL peak time  
36.13 PVL current at peak  
36.14 PVL DC voltage at peak  
36.15 PVL speed at peak  
36.16 PVL reset date  
36.17 PVL reset time  
36.20 AL1 0 to 10%  
36.21 AL1 10 to 20%  
36.22 AL1 20 to 30%  
36.23 AL1 30 to 40%  
36.24 AL1 40 to 50%  
36.25 AL1 50 to 60%  
36.26 AL1 60 to 70%  
36.27 AL1 70 to 80%  
36.28 AL1 80 to 90%  
36.29 AL1 over 90%  
36.40 AL2 0 to 10%  
36.41 AL2 10 to 20%  
36.42 AL2 20 to 30%  
36.43 AL2 30 to 40%  
36.44 AL2 40 to 50%  
36.45 AL2 50 to 60%  
36.46 AL2 60 to 70%  
36.47 AL2 70 to 80%  
36.48 AL2 80 to 90%  
36.49 AL2 over 90%  
36.50 AL2 reset date  
0.00 … 32767.00  
0…3  
-
-
100 = 1  
1 = 1  
-32768.00 … 32767.00  
-
-
100 = 1  
-
1 = 1  
-
-
1 = 1  
-32768.00 … 32767.00  
0.00 … 2000.00  
-32768.00 … 32767.00  
-
A
100 = 1 A  
100 = 1 V  
100 = 1 rpm  
1 = 1  
V
rpm  
-
-
-
1 = 1  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
0.00 … 100.00  
-
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
%
-
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
100 = 1%  
1 = 1  
                                                                                                                                                             
Additional parameter data 241  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
36.51 AL2 reset time  
-
-
1 = 1  
40 Process PID set 1  
40.01 Process PID actual value  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
40.02 Feedback actual value  
40.03 Setpoint actual value  
40.04 Deviation actual value  
40.05 Trim output actual value  
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz  
or Hz  
1 = 1  
1 = 1  
1 = 1  
40.06 PID status word  
0000h…FFFFh  
-
-
-
40.07 PID operation mode  
40.08 Feedback 1 source  
0…2  
-
40.09 Feedback 2 source  
-
-
1 = 1  
40.10 Feedback function  
40.11 Feedback filter time  
40.12 Unit selection  
0…11  
0.000 … 30.000  
0…2  
-
s
-
1 = 1  
1000 = 1 s  
1 = 1  
40.14 Setpoint base  
40.15 Output base  
-32768 … 32767  
-32768 … 32767  
-
-
100 = 1  
100 = 1  
1 = 1  
-
40.16 Setpoint 1 source  
-
40.17 Setpoint 2 source  
-
-
1 = 1  
40.18 Setpoint function  
0…11  
-
-
-
1 = 1  
1 = 1  
40.19 Internal setpoint selection 1  
Binary  
src  
40.20 Internal setpoint selection 2  
40.21 Internal setpoint 1  
40.22 Internal setpoint 2  
40.23 Internal setpoint 3  
40.24 Internal setpoint 4  
40.25 Setpoint selection  
Binary  
src  
-
-
1 = 1  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
-
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz  
or Hz  
Binary  
src  
-
1 = 1  
40.26 Setpoint min  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
0.0 … 1800.0  
-
-
100 = 1  
100 = 1  
10 = 1 s  
10 = 1 s  
40.27 Setpoint max  
40.28 Setpoint increase time  
40.29 Setpoint decrease time  
s
s
0.0 … 1800.0  
                                                                                                                     
242 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
40.30 Setpoint freeze enable  
Binary  
src  
-
-
1 = 1  
40.31 Deviation inversion  
Binary  
src  
-
-
1 = 1  
40.32 Gain  
0.1 … 100.0  
0.0 … 3600.0  
0.0 … 10.0  
-
s
s
s
-
100 = 1  
10 = 1 s  
1000 = 1 s  
10 = 1 s  
10 = 1  
40.33 Integration time  
40.34 Derivation time  
40.35 Derivation filter time  
40.36 Output min  
0.0 … 10.0  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
-
40.37 Output max  
-
10 = 1  
40.38 Output freeze enable  
Binary  
src  
-
1 = 1  
40.39 Deadband range  
40.40 Deadband delay  
40.41 Sleep mode  
-32768.0 … 32767.0  
-
s
-
10 = 1  
10 = 1 s  
1 = 1  
0.0 … 3600.0  
0…2  
-
40.42 Sleep enable  
Binary  
src  
-
1 = 1  
40.43 Sleep level  
0.0 … 32767.0  
0.0 … 3600.0  
0.0 … 3600.0  
0.0 … 32767.0  
-
s
s
-
10 = 1  
10 = 1 s  
10 = 1 s  
10 = 1  
40.44 Sleep delay  
40.45 Sleep boost time  
40.46 Sleep boost step  
40.47 Wake-up deviation  
-2147483648 …  
2147483647  
rpm, %or 100 = 1 rpm, %  
Hz  
or Hz  
100 = 1 s  
1 = 1  
40.48 Wake up delay  
40.49 Tracking mode  
0.00 … 60.00  
-
s
Binary  
src  
-
40.50 Tracking ref selection  
-
-
1 = 1  
40.51 Trim mode  
0…3  
1…3  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
40.52 Trim selection  
40.53 Trimmed ref pointer  
40.54 Trim mix  
0.000 … 1.000  
-
-
-
-
1000 = 1  
1000 = 1  
1 = 1  
40.55 Trim adjust  
-100.000 … 100.000  
40.56 Correction source  
40.57 Sel between set1 set2  
1…2  
-
Binary  
src  
1 = 1  
41 Process PID set 2  
41.07 PID operation mode  
41.08 Feedback 1 source  
0…2  
-
-
-
1 = 1  
1 = 1  
41.09 Feedback 2 source  
-
-
1 = 1  
41.10 Feedback function  
41.11 Feedback filter time  
0…11  
-
1 = 1  
0.000 … 30.000  
s
1000 = 1 s  
                                                                                                                                   
Additional parameter data 243  
No.  
Name  
Type  
Range  
0…2  
Unit  
FbEq32  
1 = 1  
41.12 Unit selection  
41.14 Setpoint base  
41.15 Output base  
41.16 Setpoint 1 source  
-
-
-
-
-32768 … 32767  
-32768 … 32767  
-
100 = 1  
100 = 1  
1 = 1  
41.17 Setpoint 2 source  
-
-
1 = 1  
41.18 Setpoint function  
0…11  
-
-
-
1 = 1  
1 = 1  
41.19 Internal setpoint selection 1  
Binary  
src  
41.20 Internal setpoint selection 2  
41.21 Internal setpoint 1  
41.22 Internal setpoint 2  
41.23 Internal setpoint 3  
41.24 Internal setpoint 4  
41.25 Setpoint selection  
Binary  
src  
-
-
1 = 1  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
-
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz or Hz  
rpm, % or 100 = 1 rpm, %  
Hz  
or Hz  
Binary  
src  
-
1 = 1  
41.26 Setpoint min  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
0.0 … 1800.0  
0.0 … 1800.0  
-
-
-
100 = 1  
100 = 1  
10 = 1 s  
10 = 1 s  
1 = 1  
41.27 Setpoint max  
41.28 Setpoint increase time  
41.29 Setpoint decrease time  
41.30 Setpoint freeze enable  
s
s
-
Binary  
src  
41.31 Deviation inversion  
Binary  
src  
-
-
1 = 1  
41.32 Gain  
0.1 … 100.0  
0.0 … 3600.0  
0.0 … 10.0  
-
s
s
s
-
100 = 1  
10 = 1 s  
1000 = 1 s  
10 = 1 s  
10 = 1  
41.33 Integration time  
41.34 Derivation time  
41.35 Derivation filter time  
41.36 Output min  
0.0 … 10.0  
-32768.0 … 32767.0  
-32768.0 … 32767.0  
-
41.37 Output max  
-
10 = 1  
41.38 Output freeze enable  
Binary  
src  
-
1 = 1  
41.39 Deadband range  
41.40 Deadband delay  
41.41 Sleep mode  
-32768.0 … 32767.0  
-
s
-
10 = 1  
10 = 1 s  
1 = 1  
0.0 … 3600.0  
0…2  
-
41.42 Sleep enable  
Binary  
src  
-
1 = 1  
41.43 Sleep level  
41.44 Sleep delay  
0.0 … 32767.0  
0.0 … 3600.0  
-
10 = 1  
s
10 = 1 s  
                                                               
244 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
10 = 1 s  
10 = 1  
41.45 Sleep boost time  
41.46 Sleep boost step  
41.47 Wake-up deviation  
0.0 … 3600.0  
0.0 … 32767.0  
s
-
-2147483648 …  
2147483647  
rpm, %or 100 = 1 rpm, %  
Hz  
or Hz  
100 = 1 s  
1 = 1  
41.48 Wake-up delay  
41.49 Tracking mode  
0.00 … 60.00  
-
s
Binary  
src  
-
41.50 Tracking ref selection  
-
-
1 = 1  
41.51 Trim mode  
0…3  
1…3  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
41.52 Trim selection  
41.53 Trimmed ref pointer  
41.54 Trim mix  
0.000 … 1.000  
-100.000 … 100.000  
1…2  
-
-
-
1000 = 1  
1000 = 1  
1 = 1  
41.55 Trim adjust  
41.56 Correction source  
43 Brake chopper  
43.01 Braking resistor temperature  
43.06 Brake chopper enable  
43.07 Brake chopper runtime enable  
0.0 … 120.0  
%
-
10 = 1%  
1 = 1  
0…2  
-
Binary  
src  
-
1 = 1  
43.08 Brake resistor thermal tc  
43.09 Brake resistor Pmax cont  
43.10 Brake resistance  
0…10000  
0.10 … 10000.00  
0…1000  
s
kW  
ohm  
%
1 = 1 s  
100 = 1 kW  
10 = 1 ohm  
1 = 1%  
43.11 Brake resistor fault limit  
43.12 Brake resistor warning limit  
44 Mechanical brake control  
44.01 Brake control status  
0…150  
0…150  
%
1 = 1%  
00000000b…11111111b  
-1600.0 … 1600.0  
-1000…1000  
-
-
1 = 1  
10 = 1%  
10 = 1%  
1 = 1  
44.02 Brake torque memory  
44.03 Brake open torque reference  
44.06 Brake control enable  
%
%
-
Binary  
src  
44.07 Brake acknowledge selection  
Binary  
src  
-
-
1 = 1  
44.08 Brake open delay  
0.00 … 5.00  
-
s
-
100 = 1 s  
1 = 1  
44.09 Brake open torque source  
44.10 Brake open torque  
44.11 Keep brake closed  
-1000…1000  
-
%
-
10 = 1%  
1 = 1  
Binary  
src  
44.12 Brake close request  
Binary  
src  
-
-
1 = 1  
44.13 Brake close delay  
44.14 Brake close level  
0.00 … 60.00  
0.0 … 1000.0  
s
100 = 1 s  
rpm  
100 = 1 rpm  
                                                                                                           
Additional parameter data 245  
No.  
Name  
Type  
Range  
0.00 … 10.00  
0.00 … 10.00  
0…2  
Unit  
FbEq32  
100 = 1 s  
100 = 1 s  
1 = 1  
44.15 Brake close level delay  
44.16 Brake reopen delay  
44.17 Brake fault function  
44.18 Brake fault delay  
s
s
-
0.00 … 60.00  
s
100 = 1 s  
45 Energy efficiency  
45.01 Saved GW hours  
45.02 Saved MW hours  
45.03 Saved kW hours  
45.05 Saved money x1000  
45.06 Saved money  
0…65535  
0…999  
GWh  
MWh  
kWh  
1 = 1 GWh  
1 = 1 MWh  
10 = 1 kWh  
0.0 … 999.0  
0…4294967295  
0.00 … 999.99  
thousand 1 = 1 thousand  
(selecta-  
ble)  
100 = 1 unit  
45.08 CO2 reduction in kilotons  
45.09 CO2 reduction in tons  
0…65535  
0.0 … 999.9  
0…1  
metric kil- 1 = 1 metric  
oton  
kiloton  
metric  
ton  
10 = 1 metric  
ton  
45.11 Energy optimizer  
45.12 Energy tariff 1  
-
1 = 1  
0.000 … 4294967295.000 (selecta- 1000 = 1 unit  
ble)  
45.13 Energy tariff 2  
45.14 Tariff selection  
0.000 … 4294967295.000 (selecta- 1000 = 1 unit  
ble)  
Binary  
src  
-
-
1 = 1  
45.17 Tariff currency unit  
100…102  
-
1 = 1  
45.18 CO2 conversion factor  
0.000 … 65.535  
metric  
ton/ MWh  
1000 = 1  
metric  
ton/MWh  
45.19 Comparison power  
45.21 Energy calculations reset  
46 Monitoring/scaling settings  
46.01 Speed scaling  
0.0 … 10000000.0  
0…1  
kW  
-
10 = 1 kW  
1 = 1  
0.00 … 30000.00  
0.00 … 30000.00  
0.0 … 30000.0  
0.0 … 30000.0  
2…20000  
rpm  
Hz  
100 = 1 rpm  
100 = 1 Hz  
10 = 1%  
46.02 Frequency scaling  
46.03 Torque scaling  
%
46.04 Power scaling  
kW  
ms  
ms  
ms  
ms  
rpm  
Hz  
10 = 1 kW  
1 = 1 ms  
46.11 Filter time motor speed  
46.12 Filter time output frequency  
46.13 Filter time motor torque  
46.14 Filter time power out  
46.21 Speed setpoint hysteresis  
46.22 Frequency setpoint hysteresis  
46.23 Torque setpoint hysteresis  
46.31 Above speed limit  
2…20000  
1 = 1 ms  
2…20000  
1 = 1 ms  
2…20000  
1 = 1 ms  
0.00 … 30000.00  
0.00 … 3000.00  
0.00 … 3000.00  
0.00 … 30000.00  
0.00 … 3000.00  
0.0 … 300.0  
100 = 1 rpm  
100 = 1 Hz  
1 = 1%  
%
rpm  
Hz  
100 = 1 rpm  
100 = 1 Hz  
10 = 1 N•m  
46.32 Above frequency limit  
46.33 Above torque limit  
N•m  
                                                                                                                                       
246 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
47 Data storage  
47.01 Data storage 1 real32  
47.02 Data storage 2 real32  
47.03 Data storage 3 real32  
47.04 Data storage 4 real32  
47.05 Data storage 5 real32  
47.06 Data storage 6 real32  
47.07 Data storage 7 real32  
47.08 Data storage 8 real32  
47.11 Data storage 1 int32  
47.12 Data storage 2 int32  
47.13 Data storage 3 int32  
47.14 Data storage 4 int32  
47.15 Data storage 5 int32  
47.16 Data storage 6 int32  
47.17 Data storage 7 int32  
47.18 Data storage 8 int32  
-2147483.008 …  
2147483.008  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1000 = 1  
1000 = 1  
1000 = 1  
1000 = 1  
1000 = 1  
1000 = 1  
1000 = 1  
1000 = 1  
1 = 1  
-2147483.008 …  
2147483.008  
-2147483.008 …  
2147483.008  
-2147483.008 …  
2147483.008  
-2147483.008 …  
2147483.008  
-2147483.008 …  
2147483.008  
-2147483.008 …  
2147483.008  
-2147483.008 …  
2147483.008  
-2147483648 …  
2147483647  
-2147483648 …  
2147483647  
1 = 1  
-2147483648 …  
2147483647  
1 = 1  
-2147483648 …  
2147483647  
1 = 1  
-2147483648 …  
2147483647  
1 = 1  
-2147483648 …  
2147483647  
1 = 1  
-2147483648 …  
2147483647  
1 = 1  
-2147483648 …  
2147483647  
1 = 1  
47.21 Data storage 1 int16  
47.22 Data storage 2 int16  
47.23 Data storage 3 int16  
47.24 Data storage 4 int16  
47.25 Data storage 5 int16  
47.26 Data storage 6 int16  
47.27 Data storage 7 int16  
47.28 Data storage 8 int16  
49 Panel port communication  
49.01 Node ID number  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
-32768 … 32767  
-
-
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1…32  
1…6  
-
-
1 = 1  
1 = 1  
49.03 Baud rate  
49.04 Communication loss time  
49.05 Communication loss action  
0.1 … 3000.0  
0…3  
s
-
10 = 1 s  
1 = 1  
                                                                                                                   
Additional parameter data 247  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
49.06 Refresh settings  
50 Fieldbus adapter (FBA)  
50.01 FBA A enable  
0…1  
-
1 = 1  
0…1  
0…3  
-
-
s
-
-
-
-
-
-
1 = 1  
1 = 1  
10 = 1 s  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
50.02 FBA A comm loss func  
50.03 FBA A comm loss t out  
50.04 FBA A ref1 type  
50.05 FBA A ref2 type  
50.06 FBA A SW sel  
0.3 … 6553.5  
0…10  
0…10  
0…1  
50.07 FBA A actual 1 type  
50.08 FBA A actual 2 type  
0…10  
0…10  
-
50.09 FBA A SW transparent source Analog  
50.10 FBA A act1 transparent source Analog  
-
-
-
-
1 = 1  
1 = 1  
50.11 FBA A act2 transparent source Analog  
50.12 FBA A debug enable  
50.13 FBA A control word  
50.14 FBA A reference 1  
0…1  
-
-
-
1 = 1  
1 = 1  
1 = 1  
00000000h … FFFFFFFFh  
-2147483648 …  
2147483647  
50.15 FBA A reference 2  
-2147483648 …  
2147483647  
-
1 = 1  
50.16 FBA A status word  
50.17 FBA A actual value 1  
00000000h … FFFFFFFFh  
-
-
1 = 1  
1 = 1  
-2147483648 …  
2147483647  
50.18 FBA A actual value 2  
-2147483648 …  
2147483647  
-
-
1 = 1  
1 = 1  
50.21 FBA A timelevel sel  
51 FBA A settings  
51.01 FBA type  
0…3  
-
-
-
1 = 1  
1 = 1  
51.02 FBA Par2  
0…65535  
-
51.26 FBA Par26  
0…65535  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
51.27 FBA par refresh  
51.28 Par table ver  
0…1  
-
-
-
51.29 Drive type code  
51.30 Mapping file ver  
51.31 D2FBA comm sta  
51.32 FBA comm SW ver  
51.33 FBA appl SW ver  
0…65535  
-
0…65535  
-
0…6  
-
-
-
-
-
52 FBA A data in  
52.01 FBA data in1  
-
-
1 = 1  
                                                                                                                                 
248 Additional parameter data  
No.  
Name  
Type  
Range  
Unit  
FbEq32  
52.12 FBA data in12  
53 FBA A data out  
-
-
1 = 1  
53.01 FBA data out1  
-
-
-
-
1 = 1  
1 = 1  
53.12 FBA data out12  
90 Feedback selection  
90.01 Motor speed for control  
-21474836.48 …  
21474836.47  
rpm  
rev  
rpm  
rev  
-
100 = 1 rpm  
100 = 1 rev  
100 = 1 rpm  
1 = 1 rev  
1 = 1  
90.02 Motor position  
90.03 Load speed  
-21474836.48 …  
21474836.47  
-21474836.48 …  
21474836.47  
90.04 Load position  
-2147483648 …  
2147483647  
90.05 Load position scaled  
90.10 Encoder 1 speed  
90.11 Encoder 1 position  
-2147483648 …  
2147483647  
-21474836.48 …  
21474836.47  
rpm  
rev  
-
100 = 1 rpm  
100 = 1 rev  
1 = 1  
-21474836.48 …  
21474836.47  
90.12 Encoder 1 multiturn  
revolutions  
0…4294967295  
90.13 Encoder 1 revolution  
extension  
-2147483648 …  
2147483647  
-
1 = 1  
90.14 Encoder 1 position raw  
90.15 Encoder 1 revolutions raw  
90.20 Encoder 2 speed  
0.00 … 65535.00  
0…65535  
-
-
100 = 1  
1 = 1  
-21474836.48 …  
21474836.47  
rpm  
100 = 1 rpm  
90.21 Encoder 2 position  
-21474836.48 …  
21474836.47  
rev  
100 = 1 rev  
1 = 1  
90.22 Encoder 2 multiturn  
revolutions  
0…4294967295  
-
-
90.23 Encoder 2 revolution  
extension  
-2147483648 …  
2147483647  
1 = 1  
90.24 Encoder 2 position raw  
90.25 Encoder 2 revolutions raw  
90.26 Motor revolution extension  
0…65535  
0…65535  
-
-
-
100 = 1  
100 = 1  
1 = 1  
-2147483648 …  
2147483647  
90.27 Load revolution extension  
-2147483648 …  
2147483647  
-
1 = 1  
90.41 Motor feedback selection  
90.42 Motor speed filter time  
90.43 Motor gear numerator  
90.44 Motor gear denominator  
90.45 Motor feedback fault  
90.46 Force open loop  
0…2  
0…10000  
-32768…32767  
-32768…32767  
0…2  
-
1 = 1  
1 = 1 ms  
1 = 1  
ms  
-
-
-
-
1 = 1  
1 = 1  
0…1  
1 = 1  
                                                                                                                   
Additional parameter data 249  
No.  
Name  
Type  
Range  
0…4  
Unit  
FbEq32  
1 = 1  
90.51 Load feedback selection  
90.52 Load speed filter time  
90.53 Load gear numerator  
-
ms  
-
0…10000  
1 = 1 ms  
1 = 1  
-2147483648 …  
2147483647  
90.54 Load gear denominator  
-2147483648 …  
2147483647  
-
1 = 1  
90.56 Load position offset  
90.57 Load position resolution  
90.61 Gear numerator  
-32768 … 32767  
0…32  
rev  
1 = 1 rev  
1 = 1  
-
-
-2147483648 …  
2147483647  
1 = 1  
90.62 Gear denominator  
-2147483648 …  
2147483647  
-
-
-
1 = 1  
1 = 1  
1 = 1  
90.63 Feed constant numerator  
90.64 Feed constant denominator  
-2147483648 …  
2147483647  
-2147483648 …  
2147483647  
91 Encoder module settings  
91.01 FEN DI status  
000000b…111111b  
-
-
1 = 1  
1 = 1  
91.02 Module 1 status  
-
91.03 Module 2 status  
-
-
1 = 1  
91.04 Module 1 temperature  
91.06 Module 2 temperature  
91.10 Encoder parameter refresh  
91.11 Module 1 type  
0…1000  
0…1000  
0…1  
°C  
1 = 1 °C  
1 = 1 °C  
1 = 1  
°C  
-
0…4  
-
1 = 1  
91.12 Module 1 location  
91.13 Module 2 type  
1…254  
0…4  
-
1 = 1  
-
1 = 1  
91.14 Module 2 location  
91.21 Temperature meas sel1  
91.22 Temperature filtering time 1  
91.23 PTC filtering 1  
1…254  
0…2  
-
-
1 = 1  
1 = 1  
0…10000  
0…65535  
0…2  
ms  
-
1 = 1 ms  
1 = 1  
91.24 Temperature meas sel2  
91.25 Temperature filtering time 2  
91.26 PTC filtering 2  
-
1 = 1  
0…10000  
0…65535  
ms  
-
1 = 1 ms  
1 = 1  
92 Encoder 1 configuration  
92.01 Encoder 1 type  
-
1…2  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
92.02 Encoder 1 source  
92.03 Encoder 1 type act  
Other parameters in this group when parameter 92.01 Encoder 1 type = Abs enc  
92.10 Sine/cosine number  
92.11 Absolute position source  
92.12 Zero pulse enable  
92.13 Position data width  
92.14 Revolution data width  
0…65535  
0…5  
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
0…1  
0…32  
0…32  
                                                                                                                                           
250 Additional parameter data  
No.  
Name  
Type  
Range  
0…1  
Unit  
FbEq32  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
92.30 Serial link mode  
92.31 EnDat max calculation time  
92.32 SSI cycle time  
-
-
-
-
-
-
-
-
-
-
-
-
0…3  
0…5  
92.33 SSI clock cycles  
92.34 SSI position msb  
92.35 SSI revolution msb  
92.36 SSI data format  
92.37 SSI baud rate  
2…127  
1…126  
1…126  
0…1  
0…5  
92.40 SSI zero phase  
0…3  
92.45 Hiperface parity  
92.46 Hiperface baud rate  
92.47 Hiperface node address  
0…1  
0…3  
0…255  
Other parameters in this group when parameter 92.01 Encoder 1 type = Resolver  
92.10 Excitation signal frequency  
92.11 Excitation signal amplitude  
92.12 Resolver polepairs  
1…20  
4.0 … 12.0  
1…32  
kHz  
1 = 1 kHz  
10 = 1 V  
1 = 1  
V
-
Other parameters in this group when parameter 92.01 Encoder 1 type = HTL  
92.10 Pulses/revolution  
92.11 Pulse encoder type  
92.12 Speed calculation mode  
92.13 Position estimation enable  
92.14 Speed estimation enable  
92.15 Transient filter  
0…65535  
0…1  
-
-
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
0…5  
0…1  
0…1  
0…3  
92.20 Enc cable fault func  
92.21 Enc cable fault mode  
93 Encoder 2 configuration  
93.01 Encoder 2 type  
0…2  
0…3  
-
1…2  
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
93.02 Encoder 2 source  
93.03 Encoder 2 type act  
Other parameters in this group when parameter 93.01 Encoder 2 type = Abs enc  
93.10 Sine/cosine number  
93.11 Absolute position source  
93.12 Zero pulse enable  
93.13 Position data width  
93.14 Revolution data width  
93.30 Serial link mode  
93.31 EnDat calc time  
0…65535  
0…5  
-
-
-
-
-
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
0…1  
0…32  
0…32  
0…1  
0…3  
93.32 SSI cycle time  
0…5  
93.33 SSI clock cycles  
93.34 SSI position msb  
93.35 SSI revolution msb  
2…127  
1…126  
1…126  
                                                                                                                                                   
Additional parameter data 251  
No.  
Name  
Type  
Range  
0…1  
Unit  
FbEq32  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
93.36 SSI data format  
93.37 SSI baud rate  
-
-
-
-
-
-
0…5  
93.40 SSI zero phase  
93.45 Hiperface parity  
93.46 Hiperface baud rate  
93.47 Hiperface node address  
0…3  
0…1  
0…3  
0…255  
Other parameters in this group when parameter 93.01 Encoder 2 type = Resolver  
93.10 Excitation signal frequency  
93.11 Excitation signal amplitude  
93.12 Resolver polepairs  
1…20  
4.0 … 12.0  
1…32  
kHz  
1 = 1 kHz  
10 = 1 V  
1 = 1  
V
-
Other parameters in this group when parameter 93.01 Encoder 2 type = HTL  
93.10 Pulses/revolution  
93.11 Pulse encoder type  
93.12 Speed calc mode  
93.13 Position estimation ena  
93.14 Speed estimation enable  
93.15 Transient filter  
0…65535  
0…1  
-
-
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
0…5  
0…1  
0…1  
0…3  
93.20 Enc cable fault func  
93.21 Enc cable fault mode  
95 HW configuration  
0…2  
0…3  
95.01 Supply voltage  
95.02 Adaptive voltage limits  
95.04 Control board supply  
95.08 Forced charging enable  
95.09 Fuse switch control  
96 System  
0…6  
0…1  
0…1  
0…1  
0…1  
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
enum  
enum  
96.01 Language  
enum  
enum  
-
-
-
-
-
-
-
-
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
1 = 1  
96.02 Pass code  
0…99999999  
96.04 Macro select  
0…6  
96.05 Macro active  
0…6  
96.06 Parameter restore  
96.07 Parameter save  
96.08 Control board boot  
-
0…1  
0…4294967295  
97 Motor control  
97.01 Switching frequency mode  
97.03 Slip gain  
0…2  
0…200  
-4…50  
0…2  
-
-
%
%
-
1 = 1  
1 = 1%  
1 = 1%  
1 = 1  
97.04 Voltage reserve  
97.05 Flux braking  
97.06 Flux reference select  
Binary  
src  
-
1 = 1  
97.07 User flux reference  
0…200  
%
100 = 1%  
                                                                                                                                                 
252 Additional parameter data  
No.  
Name  
Type  
Range  
0…4  
Unit  
-
FbEq32  
1 = 1  
97.10 Signal injection  
97.11 TR tuning  
25…400  
0.00 … 50.00  
%
1 = 1%  
100 = 1%  
97.13 IR compensation  
98 User motor parameters  
98.01 User motor model  
98.02 Rs user  
%
0…3  
-
1 = 1  
0.0000 … 0.50000  
p.u.  
100000 = 1  
p.u.  
98.03 Rr user  
0.0000 … 0.50000  
0.00000 … 10.00000  
0.00000 … 1.00000  
0.00000 … 10.00000  
0.00000 … 10.00000  
0.00000 … 2.00000  
0.00000 … 100.00000  
0.00000 … 100.00000  
p.u.  
p.u.  
p.u.  
p.u.  
p.u.  
p.u.  
ohm  
ohm  
100000 = 1  
p.u.  
98.04 Lm user  
98.05 SigmaL user  
98.06 Ld user  
100000 = 1  
p.u.  
100000 = 1  
p.u.  
100000 = 1  
p.u.  
98.07 Lq user  
100000 = 1  
p.u.  
98.08 PM flux user  
98.09 Rs user SI  
98.10 Rr user SI  
100000 = 1  
p.u.  
100000 = 1  
p.u.  
100000 = 1  
p.u.  
98.11 Lm user SI  
0.00 … 100000.00  
0.00 … 100000.00  
0.00 … 100000.00  
0.00 … 100000.00  
0…360  
mH  
mH  
mH  
mH  
100 = 1 mH  
100 = 1 mH  
100 = 1 mH  
100 = 1 mH  
98.12 SigmaL user SI  
98.13 Ld user SI  
98.14 Lq user SI  
98.15 Position offset user  
° electri- 1 = 1° electri-  
cal  
cal  
99 Motor data  
99.03 Motor type  
0…1  
0…1  
-
1 = 1  
1 = 1  
99.04 Motor ctrl mode  
-
99.06 Motor nominal current  
99.07 Motor nominal voltage  
99.08 Motor nominal frequency  
99.09 Motor nominal speed  
99.10 Motor nominal power  
99.11 Motor nominal cosfii  
99.12 Motor nominal torque  
99.13 Identification run request  
99.14 Identification run performed  
99.15 Motor polepairs  
0.0 … 6400.0  
0.0 … 800.0  
0.0 … 500.0  
0 … 30000  
-10000.00 … 10000.00  
0.00 … 1.00  
0.00 … 4294672329.296  
0…6  
A
10 = 1 A  
10 = 1 V  
10 = 1 Hz  
1 = 1 rpm  
100 = 1 kW  
100 = 1  
1000 = 1 N•m  
1 = 1  
V
Hz  
rpm  
kW  
-
N•m  
-
-
-
-
0…6  
1 = 1  
0…1000  
1 = 1  
99.16 Phase order  
0…1  
1 = 1  
                                                                                                                               
Fault tracing 253  
8
Fault tracing  
What this chapter contains  
The chapter lists the warning and fault messages including possible causes and  
corrective actions.  
The warning/fault code is displayed on the control panel of the drive, as well as the  
Drive composer PC tool. A warning or a fault message indicates abnormal drive  
status. Most warning and fault causes can be identified and corrected using the  
information in this chapter. If not, an ABB representative should be contacted.  
In this chapter, the warnings and faults are sorted by code.  
Safety  
WARNING! Only qualified electricians are allowed to service the drive. Read  
the Safety instructions on the first pages of the Hardware manual before  
working on the drive.  
How to reset  
After the cause of the fault has been corrected, the active fault can be reset from the  
control panel or Drive composer PC tool. When the fault has been removed, the drive  
can be restarted.  
Faults can also be reset from an external source selected by parameter 31.11 Fault  
         
254 Fault tracing  
Warning/fault history  
Event log  
When a warning or fault is detected, it is stored in the event log with a time stamp and  
other information. The event log stores information on the 16 latest faults and 16  
latest warnings that occurred.  
The event log can be accessed from the main Menu on the control panel. It can also  
be accessed (and reset) using the Drive composer PC tool.  
Auxiliary code  
Some events generate an auxiliary code that often helps in pinpointing the problem.  
On the control panel, the auxiliary code is stored as part of the details of the event; in  
the Drive composer PC tool, the auxiliary code is shown in the event listing.  
Parameters that contain warning/fault information  
The codes of active warnings and faults (maximum five each), and five previously  
occurred warnings and faults are stored in the parameters of groups 04 Warnings and  
     
Fault tracing 255  
Warning messages  
Code Warning  
(hex)  
Cause  
What to do  
A2A1 Current calibration  
A2B1 Overcurrent  
Current measurement  
calibration will occur at next  
start.  
Informative warning.  
Output current has exceeded  
internal fault limit.  
Check motor load.  
Check acceleration times in parameter  
(torque control) or 28 Frequency  
reference chain (frequency control). Also  
check parameters 46.01 Speed scaling,  
Check motor and motor cable (including  
phasing and delta/star connection).  
Check that the start-up data in parameter  
group 99 corresponds to the motor rating  
plate.  
Check that there are no power factor  
correction capacitors or surge absorbers  
in motor cable.  
Check encoder cable (including  
phasing).  
A2B3 Earth leakage  
Drive has detected load  
unbalance typically due to  
earth fault in motor or motor  
cable.  
Check there are no power factor  
correction capacitors or surge absorbers  
in motor cable.  
Check for an earth fault in motor or motor  
cables by measuring the insulation  
resistances of motor and motor cable.  
If no earth fault can be detected, contact  
your local ABB representative.  
A2B4 Short circuit  
Short-circuit in motor cable(s)  
or motor.  
Check motor and motor cable.  
Check there are no power factor  
correction capacitors or surge absorbers  
in motor cable.  
A2BA IGBT overload  
Excessive IGBT junction to  
case temperature. This  
Check motor cable.  
warning protects the IGBT(s)  
and can be activated by a short  
circuit in the motor cable.  
A3A1 DC link overvoltage  
A3A2 DC link undervoltage  
A3AA DC not charged  
Intermediate circuit DC voltage Check the supply voltage setting  
too high (when the drive is  
stopped).  
(parameter 95.01 Supply voltage). Note  
that the wrong setting of the parameter  
may cause the motor to rush  
uncontrollably, or the overloading of the  
brake chopper or resistor.  
Intermediate circuit DC voltage  
too low (when the drive is  
stopped).  
Check the supply voltage.  
The voltage of the intermediate  
DC circuit has not yet risen to  
operating level.  
If the problem persists, contact your local  
ABB representative.  
A3C1 DC voltage difference Difference in DC voltages  
between parallel-connected  
Contact your local ABB representative.  
inverter modules.  
     
256 Fault tracing  
Code Warning  
(hex)  
Cause  
What to do  
A490 Incorrect temperature Sensor type mismatch or  
sensor setup  
Check the settings of supervision source  
parameters 35.11 and 35.21 against  
Faulty wiring between an  
encoder interface module and  
the temperature sensor.  
Check the wiring of the sensor.  
The auxiliary code (see the event log)  
identifies the interface module. (0 =  
Module 1, 1 = Module 2).  
A491 External temperature  
Measured temperature 1 or 2  
has exceeded warning limit.  
Check the values of parameters 35.02  
Check the cooling of the motor (or other  
equipment whose temperature is being  
measured).  
Check the warning limits for measured  
temperatures 1 and 2 in parameter group  
A4A1 IGBT overtemperature Estimated drive IGBT  
temperature is excessive.  
Check ambient conditions.  
Check air flow and fan operation.  
Check heatsink fins for dust pick-up.  
Check motor power against drive power.  
A4A9 Cooling  
Drive module temperature is  
excessive.  
Check ambient temperature. If it exceeds  
40 °C (104 °F), ensure that load current  
does not exceed derated load capacity of  
drive. See appropriate Hardware Manual.  
Check drive module cooling air flow and  
fan operation.  
Check inside of cabinet and heatsink of  
drive module for dust pick-up. Clean  
whenever necessary.  
A4B0 Excess temperature  
Power unit module  
Check ambient conditions.  
temperature is excessive.  
Check air flow and fan operation.  
Check heatsink fins for dust pick-up.  
Check motor power against drive power.  
A4B1 Excess temperature  
difference  
High temperature difference  
between the IGBTs of different  
phases.  
Check the motor cabling.  
Check cooling of drive module(s).  
A4F6 IGBT temperature  
Drive IGBT temperature is  
excessive.  
Check ambient conditions.  
Check air flow and fan operation.  
Check heatsink fins for dust pick-up.  
Check motor power against drive power.  
A580 PU communication  
A5A0 Safe torque off  
Communication errors  
detected between the drive  
control unit and the power unit.  
Check the connections between the drive  
control unit and the power unit.  
Safe torque off function is  
active, i.e. safety circuit  
signal(s) connected to  
connector XSTO is lost.  
Check safety circuit connections. For  
more information, see appropriate drive  
hardware manual and description of  
parameter 31.22 STO diagnostics (page  
Programmable warning:  
A5EA Measurement circuit  
temperature  
Problem with internal  
temperature measurement of  
the drive.  
Contact your local ABB representative.  
A5EB PU board powerfail  
Power unit power supply  
failure.  
Contact your local ABB representative.  
       
Fault tracing 257  
Code Warning  
(hex)  
Cause  
What to do  
A5EC PU communication  
internal  
Communication errors  
detected between the drive  
control unit and the power unit.  
Check the connections between the drive  
control unit and the power unit.  
A5ED Measurement circuit  
ADC  
Measurement circuit fault.  
Contact your local ABB representative.  
Contact your local ABB representative.  
Contact your local ABB representative.  
A5EE Measurement circuit  
DFF  
Measurement circuit fault.  
A5EF PU state feedback  
State feedback from output  
phases does not match control  
signals.  
A5F0 Charging feedback  
A6A4 Motor nominal value  
Charging feedback signal  
missing.  
Check the feedback signal coming from  
the charging system.  
The motor parameters are set Check the settings of the motor  
incorrectly.  
configuration parameters in group 99.  
The drive is not dimensioned  
correctly.  
Check that the drive is sized correctly for  
the motor.  
A6A5 No motor data  
Parameters in group 99 have  
not been set.  
Check that all the required parameters in  
group 99 have been set.  
Note: It is normal for this warning to  
appear during the start-up until the motor  
data is entered.  
A6A6 Voltage category  
unselected  
The supply voltage range has Define supply voltage range (parameter  
not been defined.  
A6D1 FBA A parameter  
conflict  
The drive does not have a  
functionality requested by  
PLC, or requested functionality  
has not been activated.  
Check PLC programming.  
Check settings of parameter groups 50  
A6E5 AI parametrization  
The current/voltage jumper  
Adjust either the jumper setting (on the  
setting of an analog input does drive control unit) or parameter  
not correspond to parameter  
settings.  
Note: Control board reboot (either by  
cycling the power or through parameter  
validate any changes in the jumper  
settings.  
A780 Motor stall  
Motor is operating in stall  
region because of e.g.  
excessive load or insufficient  
motor power.  
Check motor load and drive ratings.  
Check fault function parameters.  
Programmable warning:  
A782 FEN temperature  
Error in temperature  
measurement when  
temperature sensor (KTY or  
PTC) connected to encoder  
interface FEN-xx is used.  
Check that parameter 35.11 Supervision  
setting corresponds to actual encoder  
interface installation.  
Error in temperature  
FEN-01 does not support temperature  
measurement with KTY sensor. Use PTC  
sensor or other encoder interface  
module.  
measurement when KTY  
sensor connected to encoder  
interface FEN-01 is used.  
A791 Brake resistor  
Brake resistor broken or not  
connected.  
Check that a brake resistor has been  
connected.  
Check the condition of the brake resistor.  
   
258 Fault tracing  
Code Warning  
(hex)  
Cause  
What to do  
A793 BR excess  
temperature  
Brake resistor temperature has Stop drive. Let resistor cool down.  
exceeded warning limit defined  
by parameter 43.12 Brake  
Check resistor overload protection  
function settings (parameter group 43  
Check warning limit setting, parameter  
Check that braking cycle meets allowed  
limits.  
A794 Brake resistor wiring  
A79B BC short circuit  
Brake resistor short circuit or  
brake chopper control fault  
Check brake chopper and brake resistor  
connection.  
Ensure brake resistor is not damaged.  
Short circuit in brake chopper  
IGBT  
Replace brake chopper.  
Ensure brake resistor is connected and  
not damaged.  
A79C BC IGBT excess  
temperature  
Brake chopper IGBT  
temperature has exceeded  
internal warning limit.  
Let chopper cool down.  
Check for excessive ambient  
temperature.  
Check for cooling fan failure.  
Check for obstructions in the air flow.  
Check the dimensioning and cooling of  
the cabinet.  
Check resistor overload protection  
function settings (parameters  
Check that braking cycle meets allowed  
limits.  
Check that drive supply AC voltage is not  
excessive.  
A7A1 Mechanical brake  
closing failed  
Status of mechanical brake  
acknowledgement is not as  
expected during brake close.  
Check mechanical brake connection.  
Check mechanical brake settings in  
parameter group 44 Mechanical brake  
Programmable warning:  
Check that acknowledgement signal  
matches actual status of brake.  
A7A2 Mechanical brake  
opening failed  
Status of mechanical brake  
acknowledgement is not as  
expected during brake open.  
Check mechanical brake connection.  
Check mechanical brake settings in  
parameter group 44 Mechanical brake  
Programmable warning:  
Check that acknowledgement signal  
matches actual status of brake.  
A7A5 Mechanical brake  
opening not allowed  
Open conditions of mechanical Check mechanical brake settings in  
brake cannot be fulfilled (for  
example, brake has been  
prevented from opening by  
parameter group 44 Mechanical brake  
Check that acknowledgement signal (if  
used) matches actual status of brake.  
Programmable warning:  
A7B0 Motor speed feedback No motor speed feedback is  
Check the settings of the parameters in  
received.  
Programmable warning:  
Check encoder installation.  
                   
Fault tracing 259  
Code Warning  
(hex)  
Cause  
What to do  
A7C1 FBA A communication Cyclical communication  
between drive and fieldbus  
Check status of fieldbus communication.  
See user documentation of fieldbus  
adapter module A or between interface.  
PLC and fieldbus adapter  
module A is lost.  
Check settings of parameter groups 50  
Check cable connections.  
Check if communication master is able to  
communicate.  
A7E1 Encoder 1  
Encoder 1 error.  
Check that the parameter settings in  
correct.  
Note: New settings will only take effect  
after parameter 91.10 Encoder  
parameter refresh is used or after the  
drive control unit is powered up the next  
time.  
Check the event log for an auxiliary code.  
See appropriate actions for each code  
below.  
Aux code: 410  
Data read error  
Overspeed  
Contact your local ABB representative.  
Aux code: 411  
Aux code: 412  
Aux code: 413  
Pulse overfrequency  
Cable fault  
Check the wiring of the encoder.  
See also parameters 92.20 Enc cable  
Aux code: 414  
Aux code: 415  
Aux code: 416  
Aux code: 424  
Aux code: 425  
Resolver ID run fault  
Resolver SW version  
Resolver speed scale  
Data read error  
Contact your local ABB representative.  
Cable fault mode not  
supported  
Current setting of 92.21 Enc cable fault  
mode not supported by the FEN-xx  
module.  
Aux code: 514  
Communication loss  
Check the wiring of the encoder.  
A7E2 Encoder 2  
Encoder 2 has been activated Check that the parameter settings in  
by parameter but the encoder groups 93 Encoder 2 configuration are  
interface (FEN-xx) cannot be  
found.  
correct.  
Note: New settings will only take effect  
after parameter 91.10 Encoder  
parameter refresh is used or after the  
drive control unit is powered up the next  
time.  
Check the event log for an auxiliary code.  
See appropriate actions for each code at  
A7EE Panel loss  
Control panel or PC tool  
selected as active control  
location for drive has ceased  
communicating.  
Check PC tool or control panel  
connection.  
Check control panel connector.  
Replace control panel in mounting  
platform.  
Programmable warning:  
               
260 Fault tracing  
Code Warning  
(hex)  
Cause  
What to do  
A880 Motor bearing warning Warning generated by an on-  
Check the event log for an auxiliary code.  
Check the source of the warning  
corresponding to the code:  
time timer or a value counter.  
Programmable warnings:  
A881 Output relay warning  
A882 Motor starts warning  
A883 Power ups warning  
Warning generated by an edge Check the event log for an auxiliary code.  
counter.  
Check the source of the warning  
corresponding to the code:  
Programmable warnings:  
A884 Main contactor  
warning  
A885 DC charge warning  
A886 On-time 1 warning  
Warning generated by on-time Check the source of the warning  
timer 1. (parameter 33.13 On-time 1 source).  
Programmable warning:  
A887 On-time 2 warning  
Warning generated by on-time Check the source of the warning  
timer 2.  
Programmable warning:  
A888 Edge counter 1  
warning  
Warning generated by edge  
counter 1.  
Check the source of the warning  
Programmable warning:  
A889 Edge counter 2  
warning  
Warning generated by edge  
counter 2.  
Check the source of the warning  
Programmable warning:  
A88A Value integrator 1  
warning  
Warning generated by value  
counter 1.  
Check the source of the warning  
Programmable warning:  
A88B Value integrator 2  
warning  
Warning generated by value  
counter 2.  
Check the source of the warning  
Programmable warning:  
A88C Device clean warning Warning generated by an on-  
time timer.  
A88D DC capacitor warning  
Programmable warnings:  
Check the event log for an auxiliary code.  
Check the source of the warning  
corresponding to the code:  
A88E Cabinet fan warning  
A88F Cooling fan warning  
A890 Additional cooling fan  
warning  
A8B0 Signal supervision  
Warning generated by a signal Check the source of the warning  
supervision function. (parameter 32.07, 32.17 or 32.28).  
Programmable warning:  
   
Fault tracing 261  
Code Warning  
(hex)  
Cause  
What to do  
A981 External warning 1  
Warning generated by an  
external device. (This  
information is configured  
through one of programmable  
digital inputs.)  
Check external devices.  
Programmable warning:  
AF8C Process PID sleep  
mode  
The drive is entering sleep  
mode.  
Informative warning. See section Sleep  
39), and parameters 40.4140.48.  
AFAA Autoreset  
A fault is about to be autoreset. Informative warning. See the settings in  
parameter group 31 Fault functions.  
AFE1 Emergency stop (off2) Drive has received an  
emergency stop (mode  
Check that it is safe to continue  
operation.  
selection off2) command.  
Return emergency stop push button to  
normal position.  
Restart drive.  
AFE2 Emergency stop (off1 Drive has received an  
or off3)  
emergency stop (mode  
selection off1 or off3)  
command.  
AFEA Enable start signal  
missing  
No enable start signal  
received.  
Check the setting of (and the source  
selected by) parameter 20.19 Enable  
AFEB Run enable missing  
No run enable signal is  
received.  
Check setting of parameter 20.12 Run  
enable 1. Switch signal on (e.g. in the  
fieldbus Control Word) or check wiring of  
selected source.  
AFF6 Identification run  
AFF7 Autophasing  
Motor ID run will occur at next Informative warning.  
start.  
Autophasing will occur at next Informative warning.  
start.  
262 Fault tracing  
Fault messages  
Code Fault  
(hex)  
Cause  
What to do  
2281 Calibration  
Measured offset of output  
Try performing the current calibration  
phase current measurement or again (select Current measurement  
difference between output  
phase U2 and W2 current  
calibration at parameter 99.13). If the  
fault persists, contact your local ABB  
measurement is too great (the representative.  
values are updated during  
current calibration).  
2310 Overcurrent  
Output current has exceeded  
internal fault limit.  
Check motor load.  
Check acceleration times in parameter  
(torque control) or 28 Frequency  
reference chain (frequency control). Also  
check parameters 46.01 Speed scaling,  
Check motor and motor cable (including  
phasing and delta/star connection).  
Check that the start-up data in parameter  
group 99 corresponds to the motor rating  
plate.  
Check that there are no power factor  
correction capacitors or surge absorbers  
in motor cable.  
Check encoder cable (including  
phasing).  
2330 Earth leakage  
Drive has detected load  
unbalance typically due to  
earth fault in motor or motor  
cable.  
Check there are no power factor  
correction capacitors or surge absorbers  
in motor cable.  
Check that there is no earth fault in motor  
or motor cables:  
Programmable fault: 31.20  
Measure insulation resistances of motor  
and motor cable.  
If no earth fault can be detected, contact  
your local ABB representative.  
2340 Short circuit  
Short-circuit in motor cable(s)  
or motor  
Check motor and motor cable.  
Check there are no power factor  
correction capacitors or surge absorbers  
in motor cable.  
2381 IGBT overload  
Excessive IGBT junction to  
case temperature. This fault  
protects the IGBT(s) and can  
be activated by a short circuit  
in the motor cable.  
Check motor cable.  
3130 Input phase loss  
Intermediate circuit DC voltage Check input power line fuses.  
is oscillating due to missing  
input power line phase or  
blown fuse.  
Programmable fault: 31.21  
Check for input power supply imbalance.  
3180 Charge relay lost  
3181 Cross connection  
No acknowledgement received Contact your local ABB representative.  
from charge relay.  
Incorrect input power and  
motor cable connection (i.e.  
input power cable is connected  
to drive motor connection).  
Check input power connections.  
Programmable fault: 31.23  
             
Fault tracing 263  
Code Fault  
(hex)  
Cause  
What to do  
3210 DC link overvoltage  
Excessive intermediate circuit Check that overvoltage control is on  
DC voltage.  
Check that the supply voltage matches  
the nominal input voltage of the drive.  
Check the supply line for static or  
transient overvoltage.  
Check brake chopper and resistor (if  
present).  
Check deceleration time.  
Use coast-to-stop function (if applicable).  
Retrofit drive with brake chopper and  
brake resistor.  
3220 DC link undervoltage  
3280 Standby timeout  
Intermediate circuit DC voltage Check supply cabling, fuses and  
is not sufficient because of a  
missing supply phase, blown  
fuse or fault in the rectifier  
bridge.  
switchgear.  
Automatic restart failed (see  
page 47).  
Check the condition of the supply  
(voltage, cabling, fuses, switchgear).  
3291 DC voltage difference Difference in DC voltages  
between parallel-connected  
Contact your local ABB representative.  
Connect motor cable.  
inverter modules.  
3381 Output phase loss  
Motor circuit fault due to  
missing motor connection (all  
three phases are not  
connected).  
Programmablefault: 31.19  
3385 Autophasing  
Autophasing routine (see  
section Autophasing on page  
34) has failed.  
Try other autophasing modes (see  
possible.  
4210 IGBT overtemperature Estimated drive IGBT  
temperature is excessive.  
Check ambient conditions.  
Check air flow and fan operation.  
Check heatsink fins for dust pick-up.  
Check motor power against drive power.  
4290 Cooling  
Drive module temperature is  
excessive.  
Check ambient temperature. If it exceeds  
40 °C (104 °F), ensure that load current  
does not exceed derated load capacity of  
drive. See appropriate Hardware Manual.  
Check drive module cooling air flow and  
fan operation.  
Check inside of cabinet and heatsink of  
drive module for dust pick-up. Clean  
whenever necessary.  
4310 Excess temperature  
Power unit module  
Check ambient conditions.  
temperature is excessive.  
Check air flow and fan operation.  
Check heatsink fins for dust pick-up.  
Check motor power against drive power.  
4380 Excess temperature  
difference  
High temperature difference  
between the IGBTs of different  
phases.  
Check the motor cabling.  
Check cooling of drive module(s).  
       
264 Fault tracing  
Code Fault  
(hex)  
Cause  
What to do  
42F1 IGBT temperature  
Drive IGBT temperature is  
excessive.  
Check ambient conditions.  
Check air flow and fan operation.  
Check heatsink fins for dust pick-up.  
Check motor power against drive power.  
4981 External temperature  
Measured temperature 1 or 2  
has exceeded fault limit.  
Check the values of parameters 35.02  
Check the cooling of the motor (or other  
equipment whose temperature is being  
measured).  
Check the fault limits for measured  
temperatures 1 and 2 in parameter group  
5080 Fan  
Cooling fan stuck or  
disconnected.  
Check fan operation and connection.  
Replace fan if faulty.  
5090 STO hardware failure Safe torque off hardware  
failure.  
Contact your local ABB representative.  
5091 Safe torque off  
Safe torque off function is  
active, i.e. safety circuit  
signal(s) connected to  
connector XSTO is broken  
during start or run, or while  
drive is stopped and parameter  
Check safety circuit connections. For  
more information, see appropriate drive  
hardware manual and description of  
parameter 31.22 STO diagnostics (page  
Programmable fault: 31.22  
5092 PU logic error  
Power unit memory has  
cleared.  
Contact your local ABB representative.  
5093 Rating ID mismatch  
The hardware of the drive does Cycle the power to the drive.  
not match the information  
stored in the memory unit. This  
may occur eg. after a firmware  
update or memory unit  
replacement.  
5681 PU communication  
5682 Power unit lost  
Communication errors  
detected between the drive  
control unit and the power unit.  
Check the connection between the drive  
control unit and the power unit.  
Connection between the drive Check the connection between the  
control unit and the power unit control unit and the power unit.  
is lost.  
5690 PU communication  
internal  
Internal communication error.  
Contact your local ABB representative.  
Contact your local ABB representative.  
Contact your local ABB representative.  
Contact your local ABB representative.  
5691 Measurement circuit  
ADC  
Measurement circuit fault.  
5692 PU board powerfail  
Power unit power supply  
failure.  
5693 Measurement circuit  
DFF  
Measurement circuit fault.  
5694 PU communication  
configuration  
Version check cannot find a  
matching power unit FPGA  
logic.  
Update the FPGA logic of the power unit.  
Contact your local ABB representative.  
5696 PU state feedback  
State feedback from output  
phases does not match control  
signals.  
Contact your local ABB representative.  
       
Fault tracing 265  
Code Fault  
(hex)  
Cause  
What to do  
5697 Charging feedback  
Charging feedback signal  
missing.  
Check the feedback signal coming from  
the charging system.  
5698 Unknown power unit  
fault  
Unidentified power unit logic  
fault.  
Check power unit logic and firmware  
compatibility.  
Contact your local ABB representative.  
6180 Internal SW error  
Internal error.  
Contact your local ABB representative.  
Quote the auxiliary code (check the  
event details in the event log).  
6181 FPGA version  
incompatible  
Firmware and FPGA versions Update power unit FPGA logic or  
are incompatible.  
firmware (whichever is older).  
Contact your local ABB representative.  
6306 FBA A mapping file  
6481 Task overload  
Fieldbus adapter A mapping  
file read error.  
Contact your local ABB representative.  
Internal fault.  
Contact your local ABB representative.  
Note: This fault cannot be  
reset.  
6487 Stack overflow  
64A1 Internal file load  
Internal fault.  
Note: This fault cannot be  
reset.  
Contact your local ABB representative.  
Contact your local ABB representative.  
Contact your local ABB representative.  
File read error.  
Note: This fault cannot be  
reset.  
64A2 Internal record load  
64A3 Application loading  
Internal record load error.  
Application file incompatible or Contact your local ABB representative.  
corrupted.  
Note: This fault cannot be  
reset.  
64B2 User set fault  
Loading of user parameter set Ensure that a valid user parameter set  
failed because  
exists. Reload.  
• requested set does not exist  
• set is not compatible with  
control program  
• drive was switched off  
during loading.  
64E1 Kernel overload  
Operating system error.  
Note: This fault cannot be  
reset.  
Contact your local ABB representative.  
6581 Parameter system  
Parameter load or save failed. Try forcing a save using parameter 96.07  
65A1 FBA A parameter  
conflict  
The drive does not have a  
functionality requested by  
PLC, or requested functionality  
has not been activated.  
Check PLC programming.  
Check settings of parameter groups 50  
6881 Text data overflow  
Internal fault.  
Internal fault.  
Internal fault.  
Reset the fault. Contact your local ABB  
representative if the fault persists.  
6882 Text 32-bit table  
overflow  
Reset the fault. Contact your local ABB  
representative if the fault persists.  
6883 Text 64-bit table  
overflow  
Reset the fault. Contact your local ABB  
representative if the fault persists.  
266 Fault tracing  
Code Fault  
(hex)  
Cause  
What to do  
6885 Text file overflow  
Internal fault.  
Reset the fault. Contact your local ABB  
representative if the fault persists.  
7080 Option module comm Communication between drive Check that the option modules are  
loss  
and option module (FEN-xx  
and/or FIO-xx) is lost.  
properly seated in their slots.  
Check that the option modules or slot  
connectors are not damaged. To pinpoint  
the problem, try installing the modules  
into different slots.  
7081 Panel port  
Control panel or PC tool  
selected as active control  
location for drive has ceased  
communicating.  
Check PC tool or control panel  
connection.  
Check control panel connector.  
Replace control panel in mounting  
platform.  
communication  
Programmable fault: 49.05  
7121 Motor stall  
Motor is operating in stall  
region because of e.g.  
excessive load or insufficient  
motor power.  
Check motor load and drive ratings.  
Check fault function parameters.  
Programmable fault: 31.24  
7181 Brake resistor  
Brake resistor broken or not  
connected.  
Check that a brake resistor has been  
connected.  
Check the condition of the brake resistor.  
Check the dimensioning of the brake  
resistor.  
7183 BR excess  
temperature  
Brake resistor temperature has Stop drive. Let resistor cool down.  
exceeded fault limit defined by  
Check resistor overload protection  
function settings (parameter group 43  
Check fault limit setting, parameter 43.11  
Check that braking cycle meets allowed  
limits.  
7184 Brake resistor wiring  
7191 BC short circuit  
Brake resistor short circuit or  
brake chopper control fault.  
Check brake chopper and brake resistor  
connection.  
Ensure brake resistor is not damaged.  
Short circuit in brake chopper  
IGBT.  
Ensure brake resistor is connected and  
not damaged.  
Check the electrical specifications of the  
brake resistor against the Hardware  
manual.  
Replace brake chopper (if replaceable).  
7192 BC IGBT excess  
temperature  
Brake chopper IGBT  
temperature has exceeded  
internal fault limit.  
Let chopper cool down.  
Check for excessive ambient  
temperature.  
Check for cooling fan failure.  
Check for obstructions in the air flow.  
Check the dimensioning and cooling of  
the cabinet.  
Check resistor overload protection  
function settings (parameter group 43  
Check that braking cycle meets allowed  
limits.  
Check that drive supply AC voltage is not  
excessive.  
         
Fault tracing 267  
Code Fault  
(hex)  
Cause  
What to do  
71A2 Mechanical brake  
closing failed  
Mechanical brake control fault. Check mechanical brake connection.  
Activated eg. if brake  
Check mechanical brake settings in  
parameter group 44 Mechanical brake  
acknowledgement is not as  
expected during brake closing.  
Programmablefault: 44.17  
Check that acknowledgement signal  
matches actual status of brake.  
71A3 Mechanical brake  
opening failed  
Mechanical brake control fault. Check mechanical brake connection.  
Activated eg. if brake  
acknowledgement is not as  
expected during brake  
opening.  
Check mechanical brake settings in  
parameter group 44 Mechanical brake  
Check that acknowledgement signal  
matches actual status of brake.  
Programmablefault: 44.17  
71A5 Mechanical brake  
opening not allowed  
Open conditions of mechanical Check mechanical brake settings in  
brake cannot be fulfilled (for  
example, brake has been  
prevented from opening by  
parameter group 44 Mechanical brake  
Check that acknowledgement signal (if  
used) matches actual status of brake.  
Programmablefault: 44.17  
7301 Motor speed feedback No motor speed feedback  
Check the setting of parameter 90.41  
source selected.  
received.  
Programmablefault: 90.45  
7310 Overspeed  
Motor is turning faster than  
highest allowed speed due to  
incorrectly set  
minimum/maximum speed,  
insufficient braking torque or  
changes in load when using  
torque reference.  
Check minimum/maximum speed  
settings, parameters 30.11 Minimum  
Check adequacy of motor braking torque.  
Check applicability of torque control.  
Check need for brake chopper and  
resistor(s).  
7380 Encoder internal  
7381 Encoder 1  
Internal fault.  
Contact your local ABB representative.  
Encoder 1 feedback fault.  
If fault appears during first start-up before  
encoder feedback is used:  
- Check cable between encoder and  
encoder interface module (FEN-xx) and  
order of connector signal wires at both  
ends of cable.  
If fault appears after encoder feedback  
has already been used or during drive :  
- Check that encoder connection wiring  
or encoder is not damaged.  
- Check that encoder interface module  
(FEN-xx) connection or module is not  
damaged.  
- Check earthings (when disturbances  
are detected in communication between  
encoder interface module and encoder).  
For more information on encoders, see  
parameter groups 90 Feedback  
Check the event log for an auxiliary code.  
See appropriate actions for each code at  
7391 Encoder 2  
Encoder 2 feedback fault.  
See fault 7381.  
                       
268 Fault tracing  
Code Fault  
(hex)  
Cause  
What to do  
73A0 Speed feedback  
configuration  
Speed feedback configuration Check the feedback source selection  
incorrect, eg. an encoder that  
is not present is selected as  
the feedback interface.  
parameters in group 90 Feedback  
selection. In case the source is an  
encoder interface, check parameter  
settings in groups 91 Encoder module  
73A1 Load feedback  
No load feedback received.  
Check the setting of parameter 90.51  
Load feedback selection, and the actual  
source selected. In case the source is an  
encoder interface, check parameter  
settings in groups 91 Encoder module  
7510 FBA A communication Cyclical communication  
Check status of fieldbus communication.  
See user documentation of fieldbus  
between drive and fieldbus  
Programmable fault: 50.02  
adapter module A or between interface.  
PLC and fieldbus adapter  
module A is lost.  
Check settings of parameter groups 50  
Check cable connections.  
Check if communication master is able to  
communicate.  
80B0 Signal supervision  
Fault generated by a signal  
supervision function.  
Check the source of the fault (parameter  
Programmable fault:  
9081 External fault 1  
Fault in external device 1.  
(This information is configured  
through one of programmable  
digital inputs.)  
Check external devices for faults.  
Check setting of parameter 31.01  
Programmable fault: 31.01  
FA81 Safe torque off 1  
FA82 Safe torque off 2  
FF61 ID run  
Safe torque off function is  
active, ie. STO circuit 1 is  
broken.  
Check safety circuit connections. For  
more information, see appropriate drive  
hardware manual, description of  
parameter 31.22 (page 148).  
Safe torque off function is  
active, ie. STO circuit 2 is  
broken.  
Motor ID run was not  
completed successfully.  
Check the nominal motor values in  
parameter group 99 Motor data.  
Check that no external control system is  
connected to the drive.  
Cycle the power to the drive (and its  
control unit, if powered separately).  
Check that no operation limits prevent  
the completion of the ID run. Restore  
parameters to default settings and try  
again.  
Check that the motor shaft is not locked.  
FF81 FB A force trip  
A fault trip command has been Check the fault information provided by  
received through fieldbus  
adapter A.  
the PLC.  
               
Fault tracing 269  
Code Fault  
(hex)  
Cause  
What to do  
FF82 FB B force trip  
A fault trip command has been Check the fault information provided by  
received through fieldbus  
adapter B.  
the PLC.  
FF8E EFB force trip  
A fault trip command has been Check the fault information provided by  
received through the  
the PLC.  
embedded fieldbus interface.  
270 Fault tracing  
Fieldbus control through the embedded fieldbus interface (EFB) 271  
9
Fieldbus control through the  
embedded fieldbus interface  
(EFB)  
This feature is not supported by the current firmware version.  
   
272 Fieldbus control through the embedded fieldbus interface (EFB)  
Fieldbus control through a fieldbus adapter 273  
10  
Fieldbus control through a  
fieldbus adapter  
What this chapter contains  
This chapter describes how the drive can be controlled by external devices over a  
communication network (fieldbus) through an optional fieldbus adapter module.  
The fieldbus control interface of the drive is described first, followed by a  
configuration example.  
     
274 Fieldbus control through a fieldbus adapter  
System overview  
The drive can be connected to an external control system through a serial  
communication link using a fieldbus adapter. The fieldbus adapter can be installed  
into any free drive slot.  
Drive  
Fieldbus  
controller  
Fieldbus  
Other  
devices  
Type Fxxx fieldbus  
adapter installed on  
drive  
Data Flow  
Control word (CW)  
References  
Process I/O (cyclic)  
Status word (SW)  
Actual values  
Process I/O (cyclic) or  
Service messages (acyclic)  
Parameter R/W requests/responses  
The drive can be set to receive all of its control information through the fieldbus  
interface, or the control can be distributed between the fieldbus interface and other  
available sources such as digital and analog inputs.  
Fieldbus adapters are available for various serial communication systems and  
protocols, for example  
• PROFIBUS DP (FPBA-01 adapter)  
• CANopen (FCAN-01 adapter)  
• DeviceNet (FDNA-01 adapter)  
• EtherNet/IPTM (FENA-11 adapter)  
• EtherCAT® (FECA-01 adapter).  
 
Fieldbus control through a fieldbus adapter 275  
Basics of the fieldbus control interface  
The cyclic communication between a fieldbus system and the drive consists of 16/32-  
bit input and output data words. The drive supports at the maximum the use of 12  
data words (16 bits) in each direction.  
Data transmitted from the drive to the fieldbus controller is defined by parameters  
52.01 FBA data in1 52.12 FBA data in12. The data transmitted from the fieldbus  
controller to the drive is defined by parameters 53.01 FBA data out1 53.12 FBA  
Fieldbus network  
1)  
Fieldbus adapter  
DATA  
FBA Profile  
EXT1/2  
Start func  
Profile  
selection  
OUT 2)  
FBA MAIN CW  
FBA REF1  
4)  
4)  
1
FBA REF2  
DATA OUT  
selection  
2
3
3)  
Speed/Torque  
REF1 sel  
12  
Par. 10.01…99.99  
DATA  
IN 2)  
Profile  
selection  
Group 53  
5)  
FBA MAIN SW  
FBA ACT1  
5)  
1
FBA ACT2  
DATA IN  
selection  
2
Speed/Torque  
REF2 sel  
3
3)  
12  
Par. 01.01…99.99  
Cyclic communication  
Acyclic communication  
Group 52  
See the manual of the fieldbus  
adapter module.  
Parameter  
table  
1) See also other parameters which can be controlled from fieldbus.  
2) The maximum number of used data words is protocol-dependent.  
3) Profile/instance selection parameters. Fieldbus module specific parameters. For more  
information, see the User’s Manual of the appropriate fieldbus adapter module.  
4) With DeviceNet, the control part is transmitted directly.  
5) With DeviceNet, the actual value part is transmitted directly.  
 
276 Fieldbus control through a fieldbus adapter  
Control word and Status word  
The Control word is the principal means for controlling the drive from a fieldbus  
system. It is sent by the fieldbus master station to the drive through the adapter  
module. The drive switches between its states according to the bit-coded instructions  
on the Control word, and returns status information to the master in the Status word.  
The contents of the Control word and the Status word are detailed on pages 279 and  
280 respectively. The drive states are presented in the state diagram (page 281).  
If parameter 50.12 FBA A debug enable is set to Enable, the Control word received  
from the fieldbus is shown by parameter 50.13 FBA A control word, and the Status  
word transmitted to the fieldbus network by 50.16 FBA A status word.  
 
Fieldbus control through a fieldbus adapter 277  
References  
References are 16-bit words containing a sign bit and a 15-bit integer. A negative  
reference (indicating reversed direction of rotation) is formed by calculating the two’s  
complement from the corresponding positive reference.  
ABB drives can receive control information from multiple sources including analog  
and digital inputs, the drive control panel and a fieldbus adapter module. In order to  
have the drive controlled through the fieldbus, the module must be defined as the  
source for control information, e.g. Reference.  
If parameter 50.12 FBA A debug enable is set to Enable, the references received  
from the fieldbus are displayed by 50.14 FBA A reference 1 and 50.15 FBA A  
Scaling of references  
The references are scaled as shown below. The values REFx MIN and REFx MAX  
are set by parameters 46.0146.04; which scaling is in use depends on the setting  
Fieldbus  
Drive  
REF2: 10000  
REF1: 20000  
REFx MAX  
0
0
REF2: -10000  
REF1: -20000  
-(REFx MAX)  
The scaled references are shown by parameters 03.05 FB A reference 1 and 03.06  
 
278 Fieldbus control through a fieldbus adapter  
Actual values  
Actual values are 16-bit words containing information on the operation of the drive.  
The types of the monitored signals are selected by parameters 50.07 FBA A actual 1  
If parameter 50.12 FBA A debug enable is set to Enable, the actual values sent to the  
Scaling of actual values  
The actual values are scaled as shown below. The values REFx MIN and REFx MAX  
are set by parameters 46.0146.04; which scaling is in use depends on the setting  
of parameters 50.04 and 50.05.  
Fieldbus  
Drive  
ACT2: 10000  
ACT1: 20000  
REFx MAX  
0
0
ACT: -10000  
ACT: -20000  
-(REFx MAX)  
 
Fieldbus control through a fieldbus adapter 279  
Contents of the fieldbus Control word  
The upper case boldface text refers to the states shown in the state diagram (page  
281).  
Bit  
Name  
Value STATE/Description  
0
Off1 control  
1
0
Proceed to READY TO OPERATE.  
Stop along currently active deceleration ramp. Proceed to OFF1  
ACTIVE; proceed to READY TO SWITCH ON unless other interlocks  
(OFF2, OFF3) are active.  
1
2
Off2 control  
Off3 control  
1
0
Continue operation (OFF2 inactive).  
Emergency OFF, coast to a stop.  
Proceed to OFF2 ACTIVE, proceed to SWITCH-ON INHIBITED.  
1
0
Continue operation (OFF3 inactive).  
Emergency stop, stop within time defined by drive parameter.  
Proceed to OFF3 ACTIVE; proceed to SWITCH-ON INHIBITED.  
WARNING: Ensure motor and driven machine can be  
stopped using this stop mode.  
3
Run  
1
Proceed to OPERATION ENABLED.  
Note: Run enable signal must be active; see drive documentation. If  
the drive is set to receive the Run enable signal from the fieldbus, this  
bit activates the signal.  
0
1
Inhibit operation. Proceed to OPERATION INHIBITED.  
Normal operation. Proceed to RAMP FUNCTION GENERATOR:  
OUTPUT ENABLED.  
Force Ramp function generator output to zero. The drive will  
immediately decelerate to zero speed (observing the torque limits).  
Enable ramp function.  
Proceed to RAMP FUNCTION GENERATOR: ACCELERATOR  
ENABLED.  
Halt ramping (Ramp Function Generator output held).  
Normal operation. Proceed to OPERATING.  
Note: This bit is effective only if the fieldbus interface is set as the  
source for this signal by drive parameters.  
Force Ramp function generator input to zero.  
Fault reset if an active fault exists. Proceed to SWITCH-ON  
INHIBITED.  
4
5
6
7
Ramp out zero  
Ramp hold  
Ramp in zero  
Reset  
0
1
0
1
0
0=>1  
Note: This bit is effective only if the fieldbus interface is set as the  
source for this signal by drive parameters.  
0
1
0
1
0
1
0
Continue normal operation.  
Accelerate to inching (jogging) setpoint 1.  
Inching (jogging) 1 disabled.  
Accelerate to inching (jogging) setpoint 2.  
Inching (jogging) 2 disabled.  
Fieldbus control enabled.  
8
Inching 1  
9
Inching 2  
10  
Remote cmd  
Control word and reference not getting through to the drive, except  
for bits OFF1, OFF2 and OFF3.  
11  
Ext ctrl loc  
1
0
Select External Control Location EXT2. Effective if control location  
parameterized to be selected from fieldbus.  
Select External Control Location EXT1. Effective if control location  
parameterized to be selected from fieldbus.  
12 to 15 Reserved.  
   
280 Fieldbus control through a fieldbus adapter  
Contents of the fieldbus Status word  
The upper case boldface text refers to the states shown in the state diagram (page  
281).  
Bit  
Name  
Value STATE/Description  
0
Ready to switch  
ON  
1
0
1
0
1
0
1
0
1
0
1
0
READY TO SWITCH ON.  
NOT READY TO SWITCH ON.  
READY TO OPERATE.  
OFF1 ACTIVE.  
OPERATION ENABLED.  
OPERATION INHIBITED.  
FAULT.  
No fault.  
OFF2 inactive.  
OFF2 ACTIVE.  
OFF3 inactive.  
OFF3 ACTIVE.  
SWITCH-ON INHIBITED.  
1
2
3
4
5
6
7
8
Ready run  
Ready ref  
Tripped  
Off 2 inactive  
Off 3 inactive  
Switch-on inhibited 1  
0
Warning  
1
0
1
Warning active.  
No warning active.  
OPERATING. Actual value equals reference = is within tolerance  
limits, i.e. in speed control, speed error is 10% max. of nominal motor  
speed.  
At setpoint  
0
1
0
1
Actual value differs from reference = is outside tolerance limits.  
Drive control location: REMOTE (EXT1 or EXT2).  
Drive control location: LOCAL.  
Actual speed, frequency or torque equals or exceeds supervision  
limit. Valid in both directions of rotation. The supervision limits are  
defined by parameters 46.3146.33.  
Actual speed, frequency or torque within supervision limit.  
9
Remote  
10  
Above limit  
0
-
-
-
-
11  
12  
13  
14  
15  
User bit 0  
User bit 1  
User bit 2  
User bit 3  
Reserved  
   
Fieldbus control through a fieldbus adapter 281  
The state diagram  
SWITCH-ON  
INHIBITED  
from any state  
Fault  
MAINS OFF  
SW b6=1  
SW b0=0  
Power ON  
CW b0=0  
FAULT  
NOT READY TO  
SWITCH ON  
SW b3=1  
A
B
C
D
CW b7=1  
CW=xxxx x1xx xxxx x110  
CW b3=0  
READY TO  
SWITCH ON  
OPERATION  
INHIBITED  
SW b0=1  
from any state  
SW b2=0  
Emergency stop  
OFF2 (CW b1=0)  
operation  
inhibited  
CW=xxxx x1xx xxxx x111  
OFF2  
ACTIVE SW b4=0  
READY TO  
OPERATE  
from any state  
OFF1 (CW b0=0)  
SW b1=1  
CW=xxxx x1xx xxxx 1111 and  
SW b12=1  
OFF1  
ACTIVE  
SW b1=0  
from any state  
CW b3=1 and  
SW b12=1  
Emergency stop  
OFF3 (CW b2=0)  
n(f) = 0 / I = 0  
B C D  
CW b4=0  
OFF3  
SW b5=0  
ACTIVE  
n(f) = 0 / I = 0  
OPERATION  
ENABLED  
C D  
SW b2=1  
A
CW=xxxx x1xx xxx1 1111  
CW b5=0  
STATE  
RFG: OUTPUT  
ENABLED  
condition  
D
B
rising edge of  
bit  
CW=xxxx x1xx xx11 1111  
CW b6=0  
CW = Control word  
SW = Status word  
RFG: ACCELERATOR  
ENABLED  
bx  
n
= bit x  
C
D
= Speed  
CW=xxxx x1xx x111 1111  
I
= Input Current  
RFG = Ramp Function  
Generator  
OPERATION  
f
= Frequency  
SW b8=1  
   
282 Fieldbus control through a fieldbus adapter  
Setting up the drive for fieldbus control  
Before configuring the drive for fieldbus control, the adapter module must be  
mechanically and electrically installed according to the instructions given in the  
User’s manual of the appropriate fieldbus adapter module.  
1. Power up the drive.  
2. Enable the communication between the drive and the fieldbus adapter module by  
3. With 50.02 FBA A comm loss func, select how the drive should react to a fieldbus  
communication break.  
Note: This function monitors both the communication between the fieldbus  
master and the adapter module and the communication between the adapter  
module and the drive.  
4. With 50.03 FBA A comm loss t out, define the time between communication break  
detection and the selected action.  
5. Select application-specific values for the rest of the parameters in group 50  
Fieldbus adapter (FBA), starting from 50.04. Examples of appropriate values are  
shown in the tables below.  
6. Set the fieldbus adapter module configuration parameters in group 51 FBA A  
settings. At the minimum, set the required node address and the communication  
profile.  
7. Define the process data transferred to and from the drive in parameter groups 52  
Note: The adapter module sets the Status word and Control word automatically  
into parameters 52.01 and 53.01 respectively.  
8. Save the valid parameter values to permanent memory by setting parameter  
9. Validate the settings made in parameter groups 51 52 and 53 by setting  
10. Set the relevant drive control parameters to control the drive according to the  
application. Examples of appropriate values are shown in the tables below.  
 
Fieldbus control through a fieldbus adapter 283  
Parameter setting example: FPBA (PROFIBUS DP)  
This example shows how to configure a basic speed control application that uses the  
PROFIdrive communication profile with PPO Type 2. The start/stop commands and  
reference are according to the PROFIdrive profile, speed control mode.  
The reference value ±16384 (4000h) corresponds to parameter 46.01 Speed scaling  
in the forward and reverse directions.  
Direction  
PZD1  
PZD2  
PZD3  
PZD4  
PZD5  
PZD6  
Out  
In  
Control word  
Status word  
Speed reference  
Acc time 1  
Dec time 1  
DC voltage  
Speed actual value Motor current  
The table below gives the recommended drive parameter settings.  
Drive parameter  
Setting for ACS880 Description  
drives  
Enables communication between the  
drive and the fieldbus adapter module.  
Selects the fieldbus A reference 1 type  
and scaling.  
Selects the actual value type and scaling  
according to the currently active Ref1  
mode defined in parameter 50.04.  
51.02 Node address  
51.03 Baud rate  
51.04 MSG type  
51.05 Profile  
1 = FPBA1)  
Displays the type of the fieldbus adapter  
module.  
32)  
Defines the PROFIBUS node address of  
the fieldbus adapter module.  
120001)  
Displays the current baud rate on the  
PROFIBUS network in kbit/s.  
1 = PPO11)  
0 = PROFIdrive  
0 = Disabled  
Displays the telegram type selected by  
the PLC configuration tool.  
Selects the Control word according to the  
PROFIdrive profile (speed control mode).  
51.07 RPBA mode  
Disables the RPBA emulation mode.  
52.01 FBA data in1  
52.02 FBA data in2  
52.03 FBA data in3  
52.05 FBA data in5  
53.01 FBA data out1  
53.02 FBA data out2  
53.03 FBA data out3  
53.05 FBA data out5  
4 = SW 16bit1)  
5 = Act1 16bit  
01.072)  
Status word  
Actual value 1  
Motor current  
01.112)  
DC voltage  
1 = CW 16bit1)  
2 = Ref1 16bit  
23.122)  
Control word  
Reference 1 (speed)  
Acceleration time 1  
Deceleration time 1  
23.132)  
 
284 Fieldbus control through a fieldbus adapter  
Drive parameter  
Setting for ACS880 Description  
drives  
Validates the configuration parameter  
settings.  
Selects speed control as the control  
mode 1 for external control location  
EXT1.  
Selects fieldbus adapter A as the source  
of the start and stop commands for  
external control location EXT1.  
Selects fieldbus A reference 1 as the  
source for speed reference 1.  
1) Read-only or automatically detected/set  
2) Example  
The start sequence for the parameter example above is given below.  
Control word:  
• 47Eh (1150 decimal) –> READY TO SWITCH ON  
• 47Fh (1151 decimal) –> OPERATING (Speed mode)  
Drive-to-drive link 285  
11  
Drive-to-drive link  
This feature is not supported by the current firmware version.  
   
286 Drive-to-drive link  
Control chain diagrams 287  
12  
Control chain diagrams  
What this chapter contains  
The chapter presents the reference chains of the drive. For a general diagram, see  
     
288 Control chain diagrams  
Speed reference source selection I  
>
>
>
>
>
>
   
Control chain diagrams 289  
Speed reference source selection II  
>
>
>
>
>
   
290 Control chain diagrams  
Speed reference ramping and shaping  
>
>
>
   
Control chain diagrams 291  
Motor feedback configuration  
>
>
   
292 Control chain diagrams  
Speed error calculation  
   
Control chain diagrams 293  
Speed controller  
>
   
294 Control chain diagrams  
Torque reference source selection and modification  
>
>
>
>
   
Control chain diagrams 295  
Reference selection for torque controller I  
>
>
>
>
   
296 Control chain diagrams  
Reference selection for torque controller II  
>
>
>
   
Control chain diagrams 297  
Torque limitation  
   
298 Control chain diagrams  
Frequency reference selection  
>
>
>
>
>
>
>
   
Control chain diagrams 299  
Frequency reference modification  
>
>
>
>
   
300 Control chain diagrams  
Process PID setpoint and feedback source selection  
>
>
>
>
>
>
>
>
>
   
Control chain diagrams 301  
Process PID controller  
>
>
>
>
>
>
>
>
>
   
302 Control chain diagrams  
Further information  
Product and service inquiries  
Address any inquiries about the product to your local ABB representative, quoting  
the type designation and serial number of the unit in question. A listing of ABB sales,  
support and service contacts can be found by navigating to www.abb.com/drives and  
selecting Sales, Support and Service network.  
Product training  
For information on ABB product training, navigate to www.abb.com/drives and select  
Training courses.  
Providing feedback on ABB Drives manuals  
Your comments on our manuals are welcome. Go to www.abb.com/drives and select  
Document Library Manuals feedback form (LV AC drives).  
Document library on the Internet  
You can find manuals and other product documents in PDF format on the Internet.  
Go to www.abb.com/drives and select Document Library. You can browse the library  
or enter selection criteria, for example a document code, in the search field.  
           
Contact us  
ABB Oy  
ABB Inc.  
ABB Beijing Drive Systems Co. Ltd.  
No. 1, Block D, A-10 Jiuxianqiao Beilu  
Chaoyang District  
Drives  
Automation Technologies  
Drives & Motors  
P.O. Box 184  
FI-00381 HELSINKI  
FINLAND  
16250 West Glendale Drive  
New Berlin, WI 53151  
USA  
Beijing, P.R. China, 100015  
Telephone +86 10 5821 7788  
Telephone +358 10 22 11  
Fax  
+86 10 5821 7618  
Fax  
+358 10 22 22681  
Telephone 262 785-3200  
1-800-HELP-365  
Fax  
262 780-5135  

Motorola PC_MILLER i88s User Manual
Microsoft Office_mac 2008 Home and Student Edition GZA 00006 User Manual
La Crosse Technology WT 3143H User Manual
Imation BLACK WATCH 9940 User Manual
Dell MINI 3IX User Manual
Craftsman LAP30ULV CT User Manual
Corel Easy Vhs To Dvd V30 Plus 251000 User Manual
Centon electronic DataStick Bolt 4GBDSB BLUE User Manual
Blackberry Pearl8110Titanium User Manual
Audiovox P 48 User Manual