Smith Cast Iron Boilers Series 28A User Manual

28A-IOM-7  
MEA#273-89-E  
SERIES 28A  
GAS OR OIL BOILER  
INSTALLATION & OPERATING  
INSTRUCTIONS  
DESIGNED AND TESTED ACCORDING TO A.S.M.E. BOILER AND PRESSURE  
VESSEL CODE, SECTION IV FOR A MAXIMUM ALLOWABLE WORKING PRESSURE  
OF: 15 PSI STEAM OR 80 PSI WATER.  
TO INSTALLER  
READ THESE INSTRUCTIONS CAREFULLY. THEY WILL  
SAVEYOU VALUABLE TIME WHEN ASSEMBLING THE BOILER.  
WARNING: If the information in this manual is not followed exactly, a fire or explosion  
may result causing property damage, personal injury or loss of life.  
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of  
this or any other appliance.  
WHAT TO DO IFYOU SMELL GAS:  
• Do not try to light any appliance.  
• Do not touch any electrical switch. Do not use any phone in your building.  
• Immediately call your gas supplier from a neighbor’s phone. Follow the gas  
supplier’s instructions.  
• If you cannot reach your gas supplier, call the fire department.  
Installation and service must be performed by a qualified installer, service agency or  
the gas supplier.  
INSTALLER, THESE INSTRUCTIONS TO BE AFFIXED ADJACENT TO THE BOILER.  
CONSUMER, RETAIN THESE INSTRUCTIONS FOR FUTURE REFERENCE PURPOSES.  
FOR JACKET ASSEMBLY AND BURNER SET UP SEE SEPARATE INSTRUCTIONS.  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  
In Canada: 5211 Creekbank Road, Mississauga, Ont. L4W 1R3 (905) 625-2991 Fax (905) 625-6610  
Page 3  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 1- Service Clearances to Adjacent Construction  
COMBUSTION AIR & VENTILATION  
WARNING: Never install a 28A boiler on top of  
combustible flooring without consulting the  
local building authorities for proper installation  
guidelines! A minimum clearance of 6 in,  
0.15 m must be maintained between the boiler  
and combustible construction. Failure to comply  
with this warning may result in a fire causing  
extensive property damage, severe personal  
injury or death!  
WARNING: This boiler must be supplied with  
combustion and ventilation air in accordance  
with Section 5.3, Air for Combustion &  
Ventilation, of the latest revision of the National  
Fuel Gas Code, ANSI Z223.1/NFPA 54 and all  
applicable local building codes. Canadian  
installations must comply with CAN/CGA B149.1  
or .2 Installation Code. Failure to provide  
adequate combustion air for this boiler can  
result in excessive levels of carbon monoxide  
which can result in severe personal injury or  
death!  
4. DO NOT install this boiler in a location that would  
subject any of the electrical components to direct  
contact with water or excessive moisture during  
operation or servicing.  
To operate properly and safely this boiler requires a  
continuous supply of air for combustion. An adequate  
supply of air must be available to replace the air used  
by the combustion process. NEVER store objects on or  
around the boiler.  
5. DO NOT place this boiler in a location that would  
restrict the introduction of combustion air into the  
boiler.  
WARNING: Never store combustible materials,  
gasoline or any product containing flammable  
vapors or liquids in the vicinity of the boiler.  
Failure to comply with this warning can result  
in an explosion or fire causing extensive  
property damage, severe personal injury or  
death!  
CAUTION: Never use an exhaust fan in the boiler  
room. The boiler room must never be under a  
negative pressure or improper burner operation will  
occur!  
NOTE: Forced make-up air supplied to the boiler  
room must be approved by the local authorities. A  
minimum of 30 ft3/GAL, 0.22 m3/L for oil or  
20 ft3/100 MBH (Therm), 0.024 m3/kW for gas must  
be provided.  
Page 4  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
All Air From Inside The Building  
If the boiler is to be located in a confined space mini-  
Table 1- Make-up Air Louver Sizing  
Required Cross Sectional Area (in2)  
mum clearances of 24 in, 610 mm must be maintained  
between the boiler and any adjacent construction. When  
installed in a confined space, two permanent openings  
communicating with an additional room(s) are required.  
The combined volume of these spaces must have  
sufficient volume to meet the criteria for an unconfined  
space. The total air requirements of all fuel burning  
equipment or any type of exhaust fan must be  
considered when making this determination.  
Metal  
Louvers  
75% Free Area  
333  
Wooden  
Input  
(MBH)  
1000  
1200  
1400  
1600  
1800  
2000  
2200  
2400  
2600  
2800  
3000  
3200  
3400  
3600  
3800  
4000  
4200  
4400  
4600  
4800  
1/4" Wire  
Screen  
250  
Louvers  
25% Free Area  
1000  
1200  
1400  
1600  
1800  
2000  
2200  
2400  
2600  
2800  
3000  
3200  
3400  
3600  
3800  
4000  
4200  
4400  
4600  
4800  
300  
350  
400  
450  
500  
550  
600  
650  
700  
750  
800  
850  
900  
950  
400  
467  
533  
600  
667  
733  
800  
867  
Each opening must have a minimum free area of 1 in2/  
1000 Btu/hr, 140 in2/GPH, 2200 mm2/kW based on the  
total input rating of ALL fuel burning equipment in the  
confined area. Each opening must be no less than 100  
in2, 64,516 mm2 in size. The upper opening must be  
within 12 in, 305 mm of, but not less than 3 in, 76 mm  
from, the top of the enclosure.  
934  
1000  
1066  
1134  
1200  
1267  
1334  
1400  
1467  
1533  
1600  
The bottom opening must be within 12 in, 305 mm of,  
but not less than 3 in, 76 mm from, the bottom of the  
enclosure.  
1000  
1050  
1100  
1150  
1200  
All Air From Outside The Building  
When installed in a confined space Two permanent  
openings communicating directly with, or by ducts to,  
the outdoors or spaces that freely communicate with the  
outdoors must be present. The upper opening must be  
within 12 in, 305 mm of, but not less than 3 in, 76 mm  
from, the top of the enclosure. The bottom opening must  
be within 12 in, 305 mm of, but not less than 3 in,  
76 mm from, the bottom of the enclosure.  
CHIMNEY & VENT PIPE  
CONNECTIONS  
WARNING: The vent installation must be in  
accordance with Part 7, Venting of Equipment,  
of the National Fuel Gas Code, ANSI Z223.1/  
NFPA 54-latest revision, the ASHRAE Equipment  
Handbook on Venting or applicable provisions  
of the local building codes. Canadian  
installations must comply with CAN/CGA B149.1  
or .2 Installation Code. Improper venting of this  
boiler can result in excessive levels of carbon  
monoxide which can result in severe personal  
injury or death!  
Where directly communicating with the outdoors or  
communicating with the outdoors through vertical ducts,  
each opening shall have a minimum free area of 1 in2/  
4000 Btu/hr, 35 in2/GPH, 550 mm2/kW of the total input  
rating of all of the equipment in the enclosure.  
Where communicating with the outdoors through  
horizontal ducts, each opening shall have a minimum  
free area of 1 in2/2000 Btu/hr, 70 in2/GPH, 1100 mm2/  
kW of the total input rating of all of the equipment in  
the enclosure. When ducts are used, they must have the  
same cross-sectional area as the free area of the  
opening to which they connect. When calculating the  
free area necessary to meet the make-up air  
requirements of the enclosure, consideration must be  
given to the blockage effects of louvers, grills and  
screens. Screens must have a minimum mesh size of  
1/4 in, 6.4mm. If the free area through a louver or grill  
is not known the louver or grill should be sized per Table 1.  
CAUTION: The products of combustion from a 28A  
must be safely vented to the outdoors while  
ensuring that the flue gasses do not cool  
prematurely. Its critical that the chimney system be  
properly designed to handle the flue gases. An  
oversized or uninsulated chimney can cause the  
moisture in the flue gases to condense resulting in  
damage to the chimney system unless its  
specifically designed for condensate. If this is the  
case a suitable condensate drain must be used to  
protect the boiler from condensate.  
NOTE: Our warranty does not cover corrosion  
damage to the boiler or its vent system caused by  
flue gas condensate!  
Page 5  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Chimney Inspection & Sizing  
The 28A is designed for pressurized operation with a  
If this boiler will be connected to a masonry chimney, a  
thorough inspection of the chimney must be performed.  
Ensure that the chimney is clean, properly constructed,  
lined and properly sized, see Figure 2. Table 2 lists the  
equivalent breeching and flue sizes required for the 28A  
boilers.  
back pressure of 0.10 in, 2.54 mm W.C. before the  
smoke hood slide damper. If the vent configuration  
results in a back pressure greater than this, the burner  
capacity may have to be verified. Contact the Smith  
Technical Service Department to verify the burner  
capacity.  
Table 2 - Equivalent Breeching & Chimney Size  
The chimney must be able to provide 0.10" WC at the  
boiler outlet. If the chimney is 50 ft. or taller it may  
produce excessive draft (approx. - 0.25" WC) and a  
barometric draft regulator may be needed.  
Boiler Model  
Breeching Size  
Chimney Size  
in  
mm  
254  
254  
254  
305  
305  
356  
356  
356  
356  
356  
406  
406  
406  
406  
457  
in  
mm  
254  
254  
254  
305  
305  
356  
356  
356  
356  
356  
406  
406  
406  
406  
457  
28A-4  
28A-5  
28A-6  
28A-7  
28A-8  
28A-9  
28A-10  
28A-11  
28A-12  
28A-13  
28A-14  
28A-15  
28A-16  
28A-17  
28A-18  
10  
10  
10  
12  
12  
14  
14  
14  
14  
14  
16  
16  
16  
18  
18  
10  
10  
10  
12  
12  
14  
14  
14  
14  
14  
16  
16  
16  
18  
18  
When more than one appliance is connected to the  
same chimney flue the flue must be large enough to  
safely vent the combined output of all the appliances.  
WARNING: If an appliance using any type of  
a mechanical draft system operating under  
positive pressure is connected to a chimney  
flue, never connect a Category I appliance to  
this flue. Doing so can result in the  
accumulation of carbon monoxide which can  
cause severe personal injury or death!  
Note: These sizes are based on a 20 foot chimney height.  
Figure 2 - Vertical Venting  
Page 6  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
WARNING: Failure to maintain minimum  
VENT CONNECTIONS  
clearances between vent connectors and any  
combustible material can result in a fire causing  
extensive property damage, severe personal  
injury or death!  
WARNING: Never modify or alter any part of the  
boilers smoke hood. This includes the removal  
or alteration of any baffles. Never install a vent  
pipe of a diameter different than that of the  
boiler smoke hood outlet. Failure to comply with  
this warning can result in severe personal injury  
or death.  
COMMON VENT SYSTEMS  
If an existing boiler is removed from a common venting  
system, the common venting system may then be too  
large for the proper venting of the remaining appliances  
connected to it. At the time of removal of an existing  
boiler, the following steps shall be followed with each  
appliance remaining connected to the common venting  
system placed in operation, while the other appliances  
remaining connected to the common venting system are  
not in operation.  
Locate the boiler as close to the chimney as possible.  
Use the shortest, straightest vent connector possible for  
the installation. If horizontal runs exceed 5 ft, 1.5 m they  
must be supported at 3 ft, 0.9 m intervals with overhead  
hangers. Use a single wall stainless or single wall  
galvanized steel vent pipe the same diameter as the flue  
collar to connect the boiler to a masonry chimney. When  
using an approved metal chimney system use the  
appropriate vent connector. The vent connector should  
be sloped up toward the chimney at a minimum rate of  
1/4 in/ft, 2 cm/m. On masonry chimneys the connector  
must terminate flush with the inside of the chimney flue.  
Fasten each single wall vent connection with at least 3  
corrosion resistant sheet metal screws.  
Au moment du retrait d'une chaudière existante, les  
mesures suivantes doivent être prises pour chaque  
appareil toujours raccordé au système d'évacuation  
commun et qui fonctionne alors que d'autres appareils  
toujours raccordés au système d'évacuation ne  
fonctionnent pas: système d'évacuation  
a) Seal any unused openings in the common venting  
system.  
The vent materials used in positive pressure vent  
systems must be certified to UL 1738 for installations  
in the United States, ULS636 for installations in Canada.  
The following manufactures have systems that meet  
these requirements:  
Sceller toutes les ouvertures non utilisées du  
système d'évacuation.  
b) Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion and other  
deficiencies which could cause an unsafe condition.  
Heat-Fab, Inc.  
38 Hayward Street  
Greenfield, MA 01301, (800) 772-0739.  
Z-Flex U.S., Inc.  
20 Commerce Park  
North, Bedford, NH 03110-6911, (800) 654-5600.  
Inspecter de façon visuelle le système d'évacuation  
pour déterminer la grosser et l'inclinaison  
horizontale qui conviennent et s'assurer que le  
système est exempt d'obstruction, d'étranglement  
de fruite, de corrosion et autres défaillances qui  
pourraient présenter des risques.  
Protech Systems Inc.  
26 Gansevoort Street,  
Albany, NY 12202 (518) 463-7284  
WARNING: Breeching under positive pressure  
must be certified to UL 1738 for installations in  
the United States, ULS636 for installations in  
Canada. Type B1 vent SHALL NOT be used.  
Failure to comply with this warning can result  
in severe personal injury or death.  
Always provide a minimum clearance of 6 inches  
between single wall metal vent pipe and all combustible  
materials.  
Page 7  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
c) Insofar as is practical, close all building doors and  
g) Any improper operation of the venting system  
windows and all doors between the space in which  
the appliances remaining connected to the common  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any appliance  
not connected to the common venting system. Turn  
on any exhaust fans, such as range hoods and  
bathroom exhaust, so they will operate at maximum  
speed. Do not operate a summer exhaust fan for a  
boiler installation. Close fireplace dampers.  
should be corrected so the installation conforms with  
the National Fuel Gas Code, ANSI Z223.1/NFPA 54.  
When resizing any portion of the common venting  
system, the common venting system should be  
resized to approach the minimum size as  
determined using the appropriate tables in  
Appendix F in the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 and or CSA B149 Installation  
Codes.  
Dans la mesure du possible, fermer toutes les  
portes et les fenêtres du bâtiment et toutes les  
portes entre l'espace où les appareils toujours  
raccordés du système d'évacuation sont installés et  
les autres espaces du bâtiment. Mettre en marche  
les sécheuses, tous les appareils non raccordés au  
système d'évacuation commun et tous les  
ventilateurs d'extraction comme les hottes de  
cuisinère et les ventilateurs des salles de bain.  
S'assurer que ces ventilateurs fonctionnent à la  
vitesse maximale. Ne pas faire fonctionner les  
ventilateurs d'été. Fermer les registres des  
cheminées.  
Tout mauvais fonctionnement du systéme  
d'évacution commun devrait étré corrigé de façor  
que l'installation soit conforme au National Fue Gas  
Code, ANSI Z223.1/NFPA 54 et (ou) aux codes  
d'installation CAN/CGA-B149. Si la grosseur d'une  
section du système d' évacuation doit étré modifiée,  
le système devrait étré modifié pour respecter les  
valeurs minimales des tableaux pertinents de  
l'appendice F du National Fuel Gas Code, ANSI  
Z223.1/NFPA 54 et (ou) des codes d'installation  
CSA-B149.  
BOILER ASSEMBLY  
Locate the boiler installation site based on the guide-  
lines set forth in the BOILER LOCATION section.  
d) Place in operation the appliance being inspected.  
Follow the lighting instructions. Adjust thermostat so  
appliance will operate continuously.  
WARNING: Never install a 28A boiler on top of  
combustible flooring without consulting the  
local building authorities for proper installation  
guidelines! Failure to comply with this warning  
can result in a fire causing extensive property  
damage, severe personal injury or death!  
Mettre l'appareil inspecté en marche. Suivre les  
instructions d'allumage. Régler le thermostat de  
façon que l'appareil fonctionne de façon continue.  
e) Test for spillage at the draft hood relief opening after  
5 minutes of main burner operation. Use the flame  
of a match or candle, or smoke from a cigarette,  
cigar or pipe.  
Packaged Boilers/Factory Assembled Sections  
A careful inspection of all assemblies should be made  
to detect possible shipping damage. Packaged boilers  
and factory assembled blocks of sections are  
hydrostatically tested at the factory to insure pressure  
tightness. A hydrostatic retest should be performed  
before any piping connections are made to detect leaks  
caused by shipping.  
Faire fonctionner le brûleur principal pendant 5 min  
ensuite, déterminer si le coupetirage déborde à  
l'ouverture de décharge. Utiliser la flamme d'une  
allunette ou d'une chandelle ou la fumée d'une  
cigarette, d'un cigare ou d'une pipe.  
NOTE: All assembled boiler sections shall pass the  
hydrostatic tests prescribed in Section IV of the  
ASME Boiler and Pressure Vessel Code.  
f) After it has been determined that each appliance  
remaining connected to the common venting  
system properly vents when tested as outlined  
above, return doors, windows, exhaust fans,  
fireplace dampers and any other gas-burning  
appliance to their previous condition of use.  
CAUTION: Do not connect any boiler controls during  
the pressure test or they will be damaged!  
Une fois qu'il a été d éterminé, selon la métode  
indiquée cidessus, que chaque appareil raccordé  
au système d'évacuation est mis à l'air libre de façor  
adéquate. Remettre les portes et les fenêtres, les  
ventilateurs, les registres de cheminées et les  
appareils au gaz à leur position originale.  
Page 8  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Completed boilers must be tested as follows:  
Steam Boilers – the assembled boiler sections shall be  
2. Carefully place the back section in position on the  
angles as shown in Figure 4.  
subjected to a hydrostatic test pressure of not less than  
45 psig, 315 kPa.  
WARNING:The section MUST be fully supported  
to prevent it from falling! Failure to comply with  
this warning may result property damage,  
severe personal injury or death!  
Water Boilers – the assembled boiler sections shall be  
subjected to a hydrostatic test pressure of not less than  
1 1/2 times the maximum allowable working pressure.  
Figure 4 - Section Placement  
The hydrostatic pressure shall not exceed the required  
test pressure by more than 10 psig, 70 kPa during the  
test.  
WARNING: Never leak test the boiler using  
compressed air! Failure to comply with this  
warning may result in property damage, severe  
personal injury or death!  
1. Plug all openings in the boiler and fill it with water.  
2. Bleed any air off through one of the top tappings  
then increase the pressure as outlined above.  
3. Clean the hydronic port connector sealing surfaces  
and the rope grooves with a wire brush to remove  
any rust or debris.  
3. Maintain the test pressure while carefully checking  
for leaks. If a leak is found it must be eliminated,  
see Table 4 and supporting text. Once the  
assembled boiler sections pass the hydrostatic test  
drain them and remove the plugs from any tappings  
that will be used in service.  
4. Apply two coats of the spray adhesive supplied with  
the boiler to the rope groove. Allow time for the first  
coat to dry before applying the second coat. When  
the second coat is tacky press the rope into the rope  
groove. Trim the rope off leaving 1/8 in., 3.2 mm  
extending beyond the surface of the cast iron  
section, Figure 5.  
NOTE: The shipping lugs, lifting lugs and metal  
banding should be removed before installing the  
jacket on factory assembled sections.  
Figure 5 - Rope Installation  
CAUTION: Remove the left jacket panels on fully  
packaged boilers and ensure that the cleanout  
covers are secure and gas tight. Loose covers could  
damage the boiler.  
Assembly of Knocked-Down Boilers  
Drilled and tapped steel angles are furnished to provide  
a level footing, ease of section assembly and a point of  
jacket attachment.  
1. Set the angles as shown in Figure 3. They must be  
parallel and level. Grout under the angles to provide  
a continuous bearing surface.  
Figure 3 - Steel Angle Placement  
Page 9  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
5. Insert the large port connector with its steel inner  
Figure 6 - Section Alignment  
ring into the upper port.  
6. Insert the two round port connectors into the lower  
ports.  
NOTE: Apply the spray adhesive supplied with the  
boiler to the port recess to hold the port connector  
in place if necessary.  
7. Select the correct intermediate section and carefully  
Table 4 - Section Torque Sequence  
move it into place against the back section, Figure  
4.  
Step  
Rod Position  
Torque  
ft lbs  
25  
25  
25  
10  
50  
50  
50  
75  
75  
75  
30  
125  
125  
125  
125  
40  
Nm  
34  
34  
34  
14  
68  
68  
68  
102  
102  
102  
42  
169  
169  
169  
169  
54  
1
2
3
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
Upper Right  
Lower Left  
Lower Right  
Upper Left  
Upper Right  
Lower Left  
Lower Right  
Upper Right  
Lower Left  
Lower Right  
Upper Left  
Upper Right  
Lower Left  
Lower Right  
Upper Right  
Upper Left  
CAUTION: Any steam uptake and heater sections  
must be located as shown in Table 3. Failure to  
comply with this caution may result in poor boiler  
performance and prevent the jacket from fitting!  
Only one intermediate section with an external leg  
boss has been included. It should be located toward  
the front of the boiler for optional low water cutoff  
use. See Table 3.  
NOTE: A putty knife or similar tool can be used to  
hold the port connectors in place while the  
intermediate section is positioned. It must be  
removed before the sections make contact or the  
port connector will be damaged resulting in a leak!  
8. Insert the four draw rods through the casting  
bosses. Thread nuts onto one end of the rods. Place  
washers on the other end of the rods before  
threading nuts onto them. Snug the nuts finger tight.  
Use a spirit level to ensure that the first two sections  
are plumb and properly aligned, Figure 6. Check the  
rope to insure that it’s properly positioned. Once the  
sections are plumb and the rope and port  
connectors are properly positioned follow the torque  
sequence shown in Table 4.  
NOTE: With these initial torques the sections may  
not be metal to metal, which is acceptable. If any of  
the ports leak during the hydrostatic test the torque  
can be increased to 200 ft lbs, 271 Nm on the upper  
right rod.The torque on the lower left and right rods  
can be increased to 150 ft lbs, 203 Nm. Once the  
sections are metal to metal additional torque will not  
improve the seal.  
Table 3 - Section Locations  
Boiler  
Model  
28A-4  
Section Location Numbered From Front To Back  
1
F
F
F
F
F
F
F
F
F
F
F
F
F
F
F
2
T
3
H
T
H
H
H
H
T
T
T
T
T
T
T
T
T
4
B
H
T
5
6
7
8
9
10  
11  
F
12  
13  
14  
15  
16  
17  
18  
Front Section  
28A-5  
H
T
B
H
T
T
Intermediate Section w/ 5" Tapping & Boss  
Intermediate Section w/ Heater Opening  
Intermediate Section, Plain  
28A-6  
B
H
T
H
P
B
28A-7  
T
P
P
P
H
H
H
H
H
H
H
H
H
B
H
T
P
P
H
T
T
P
P
P
P
28A-8  
T
H
H
P
P
P
P
P
P
P
P
P
B
H
T
Back Section  
28A-9  
T
P
H
T
B
H
T
H
P
P
H
T
T
P
28A-10  
28A-11  
28A-12  
28A-13  
28A-14  
28A-15  
28A-16  
28A-17  
28A-18  
H
H
H
H
H
H
H
H
H
B
H
T
B
H
T
T
P
P
H
T
B
H
H
H
H
H
H
H
H
P
H
H
T
H
T
B
H
T
P
H
P
P
H
B
H
T
P
H
H
P
B
H
T
H
H
H
P
P
H
B
H
T
H
P
B
H
H
B
Page 10  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
9. Assemble the rest of the sections following steps 3  
through 8 above.  
Burner Mounting Plate Installation, Figure 8  
1. Apply two coats of the spray adhesive supplied with  
the boiler to the rope groove on the plate. Allow time  
for the first coat to dry then apply the second coat.  
When the second coat is tacky lay the 3/8 rope into  
the rope groove and press it into place.  
10. Hydrostatically test the boiler by following the  
instructions on page 8.  
11. While the boiler is being filled confirm that all  
of the draw rods are properly torqued and that  
there are no leaks.  
2. Screw the four 7/16-14 x 2 1/2" studs into the  
tapped holes in the boiler front section, Figure 8.  
12. If any leaks are found tighten the draw rods on that  
section until the leak stops.  
3. Install the burner mounting plate insulation block in  
the burner opening in the front section of the boiler.  
The small observation port cutout must be on the  
top, left side.  
Cleanout Cover Installation  
1. The cleanout covers come insulated from the  
factory. Inspect the covers to ensure that the  
insulation is not damaged or missing. If it is call the  
Smith Customer Service Department.  
4. Align the four holes in the burner mounting plate  
with the 7/16" studs and force the burner insulation  
block inward until the studs extend far enough  
through the burner mounting plate holes so the nuts  
can be started. Lightly tighten the nuts.  
2. Trim the 1/2" rope that's sticking out around the  
cleanout opening flush with the castings to insure  
an air-tight seal, see Figure 5.  
5. Carefully insert the 1/4-20 x 5" machine screws  
through the holes in the burner mounting plate and  
insulation block, Figure 8. Reach through the inside  
of the burner opening and install the stainless steel  
fender washers and nuts and snug the nuts down.  
3. Install the cleanout cover bolts from the inside of the  
cleanout cover and start the nuts, Figure 7.  
4. Insert the cleanout cover and tighten the nuts to  
15 ft lbs, 21 Nm.  
CAUTION: The burner insulation block must be  
supported from the inside to prevent it from tearing.  
Don't force the bolts through the block or over  
tighten the nuts or the block with be damaged!  
5. Apply a bead of high temperature silicone caulk  
around the perimeter of the cleanout cover to  
ensure an air tight seal.  
Figure 7 - Cleanout Cover Assembly  
Page 11  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 8 - Burner Mounting Plate Details  
Observation Port Assembly, Figure 9  
1. Position the hinged end of the steel flapper door,  
# 5, over the boss on the observation port cover,  
# 4.  
Figure 9 - Observation Port Assembly  
2. Drive the expansion pin, # 7, through the hinge  
bosses to secure the door to the cover.  
3. Insert the hex bolt, # 6, through the hole in the  
observation port cover.  
4. Install the spring, nut and knob, #"s 3, 2 & 1 on the  
bolt as shown. Use the nut as a jam nut against the  
knob.  
5. Apply the insulating tape to the back of the  
observation port cover as shown.  
Page 12  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Observation Port Installation  
1. Screw the four 5/16-18 x 1 1/2 studs into the tapped  
Smokehood Installation, Figure 10  
1. Screw the four 5/16-18 x 1 1/2 studs into the tapped  
holes around the smokehood opening in the back  
section.  
holes around the observation cover opening in the  
back section.  
2. Place the observation port cover assembly over the  
studs and install the washers and nuts. Tighten the  
nuts uniformly.  
2. Apply smokehood insulation tape to smokehood.  
3. Place the smokehood over the studs and install the  
washers and nuts. Tighten the nuts uniformly.  
4. Apply the 1/8" x 3/4" x 18" strip of insulating tape  
to the damper anchoring angle, Figure 10.  
5. Fully open the slide damper and leave it ready for  
adjustment during burner light off.  
Figure 10 - Smokehood Assembly  
Page 13  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Tankless Heater Installation - Optional  
5. Install the operating control in one of the heater  
1. Clean the heater flange to remove any rust or  
debris.  
mounting plates to ensure quick burner response  
when there is a demand for hot water. Figure 12  
illustrates an acceptable piping arrangement for  
multiple heaters.  
2. Install the four 7/16" x 1 1/2" studs into the tapped  
holes in the tankless heater flange on the section,  
Figure 11.  
Burner Mounting  
1. Clean the burner mounting flange to remove any  
rust or debris.  
Figure 11 - Tankless Heater Installation  
2. Install the four 3/8" x 1 1/4" studs into the tapped  
holes in the burner mounting plate.  
3. Use a hacksaw blade, or some other suitable tool,  
to properly size the opening in the burner mounting  
plate insulation block to match the burner air tube  
end diameter.  
NOTE:The opening should be a close fit, but not too  
snug or the insulation block may be damaged upon  
burner insertion!  
4. Place the burner gasket, supplied with the burner,  
over the studs and carefully insert the burner into  
the opening in the burner mounting plate.  
3. Place the heater gasket over the studs and carefully  
install the heater.  
4. Install the nuts and tighten evenly to ensure uniform  
compression of the gasket.  
CAUTION: Most burners require support to the floor.  
Follow the burner manufacturers instructions or the  
burner may be damaged!  
5. Install the 3/8" washers and nuts and tighten  
securely.  
Figure 12 - Multiple Tankless Heater Piping  
Page 14  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 14 - Back Section Tapping Locations  
GENERAL PIPING REQUIREMENTS  
CAUTION: Never use automotive antifreeze in the  
boiler or heating system. If antifreeze is necessary  
it must be formulated specifically for hydronic  
heating systems, such as ethylene or propylene  
glycol. Failure to comply with this caution will void  
the warranty!  
All heating system piping must be installed by a qualified  
technician in accordance with the latest revision of the  
ANSI/ASME Boiler and Pressure Vessel Code, Section  
IV. Also ANSI/ASME CSD-1, Standard for Controls and  
Safety Devices for Automatically Fired Boilers where  
required. All applicable local codes and ordinances must  
also be followed. A minimum clearance of 1" must be  
maintained between heating system pipes and all  
combustible construction.  
CAUTION: Improper piping of this boiler can result  
in poor performance and premature failure of the  
boiler voiding the warranty! Improper piping can  
also cause flooding and extensive property damage!  
Ensure that the boiler is level from front to back and from  
side to side. Use metal shims to level the boiler. NEVER  
use wood, plastic or other combustible materials as  
shims.  
Table 5 - Water & Steam Tappings  
Tapping Size  
Water  
Steam  
1
2
3
4
1/8"  
3/4"  
3/4"  
Chamber Pressure  
Chamber Pressure  
Probe LWCO  
If a boiler is installed above any radiation elements it  
must be fitted with a low water cutoff device.  
Temp./Pressure Gage  
3/4" Operating Control - Top  
Water Glass  
Manuel Reset High  
Limit & Steam Gage  
Water Column - Top  
Skim Tapping  
Manuel Reset  
NOTE: Install the observation port assembly before  
making any return piping connections as access  
may be blocked by piping.  
5
3/4"  
High Limit  
6
7
1"  
6"  
Air Removal  
Water Supply  
Tankless Heater  
Operating Control  
Figure 13 - Front Section Tapping Locations  
8
3/4"  
9
1 1/2"  
1"  
Inspection Tapping - Top  
10  
11  
12  
13  
Water Column - Bottom Water Column - Bottom  
4"  
Boiler Drain  
Return  
Boiler Drain/Blowoff  
Return  
4"  
Relief Valve  
Safety Valve  
Relief & Safety Valve Piping  
Install the pressure relief or safety valve in the 3" NPT  
opening in the top of the back section, Figure 14.  
WARNING: The discharge of the pressure relief  
or safety valve must be piped close to the floor  
to prevent scalding in the event of a discharge,  
see Figure 15. The discharge piping must be  
sized the same as the pressure relief or safety  
valve outlet. Never install any type of valve  
between the boiler and the pressure relief or  
safety valve! Failure to comply with this  
warning can result in an explosion causing  
extensive property damage, severe personal  
injury or death!  
Page 15  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 15 - Relief & Safely Valve Piping  
Table 7 - Boiler Water Content  
Boiler Model  
Water Boilers  
Steam Boilers  
Gallons Liters Gallons Liters  
28A-4  
28A-5  
28A-6  
28A-7  
28A-8  
28A-9  
28A-10  
28A-11  
28A-12  
28A-13  
28A-14  
28A-15  
28A-16  
28A-17  
28A-18  
123  
150  
177  
204  
231  
258  
285  
312  
339  
366  
392  
419  
446  
473  
500  
466  
568  
670  
772  
875  
104  
126  
148  
170  
192  
214  
236  
258  
280  
302  
324  
346  
368  
399  
412  
394  
477  
560  
644  
727  
810  
893  
977  
1060  
1143  
1227  
1310  
1393  
1511  
1560  
977  
1079  
1181  
1283  
1386  
1484  
1586  
1689  
1791  
1893  
Return Piping 10 Through 18 Section Boilers  
Install the two 4" NPT x 6" nipples per Figure 16.  
Assemble the rest of the return yoke as shown in Figure  
16.  
Control Installation  
Locate the temperature & pressure gage, low water  
cutoff, high limit and operating controls per Figures 13  
& 7. Optional controls must be installed in accordance  
with the control manufacturers instructions and Figures  
13 & 17.  
WATER BOILER PIPING  
The supply and return connections should be sized  
to suit the system, see Figures 13, 14, 16, 17 and Tables  
5 & 6. Do not pipe the supply from the bottom port or  
the return to the top port, the boiler will not work  
properly. Typical water boiler piping arrangements are  
shown in Figures 18 & 19. Swing joints should be used.  
NOTE: The front jacket panel MUST be installed  
before any controls are attached to the front boiler  
section!  
Install 3" nipples into the two 3" NPT tappings in the  
front section and cap them.  
CAUTION: The controls must be mounted in the  
correct location and according to the control  
manufacturers instructions or the boiler may not  
function properly!  
NOTE: See CLEANING OF WATER BOILERS on page  
18 before proceeding!  
Supply Piping  
Water Column Piping  
Install a reducing bushing in the 6" NPT tapping in the  
front section to obtain the correct supply pipe size,  
Figure 13 and Tables 5 & 6.  
A variety of water level controls are available for the 28A.  
The water column piping needed to properly mount each  
control is available from Smith. Figure 17 shows a typical  
water column piping arrangement. The 1" NPT x 7 1/2"  
nipple is always installed in the lower water column  
tapping, Figures 13 & 17 and Table 5.  
Table 6 - Water Boiler Piping  
Boiler Size  
# Sections  
4 & 5  
6 through 9  
10 through 18  
Return Size  
Supply Size  
NPT  
NPT  
3
4
5
3
4
5
Note: Sizes based on 20°F, 11.1°C, T for the system.  
Return Piping 4 Through 9 Section Boilers  
Install 3" x 4" NPT bushings in the two 4" NPT tappings  
at the bottom of the back section. Install the two 3" NPT  
x 6" nipples per Figure 16. Assemble the rest of the  
return yoke as shown in Figure 16.  
Page 16  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Piping For Use With Cooling Units  
When a boiler is connected to a heating coil that may  
be exposed to refrigerated air from an air handling  
device, the piping system must be equipped with flow-  
control valves or some other automatic means of  
preventing gravity circulation of the boiler water during  
the cooling cycle.  
The boiler, when used in connection with a refrigeration  
system, must be installed so the chilled medium is piped  
in parallel with the boiler. Appropriate valves must be  
used to prevent the chilled water from entering the  
boiler, see Figure 20.  
Figure 16 - Optional ReturnYoke  
Figure 17 - Boiler Control Locations  
STEAM  
WATER  
Page 17  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 18 -  
Typical Single  
Water Boiler Piping  
Figure 19 - Typical Multiple Water Boiler Piping  
Page 18  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
NOTE: Some locations do not allow this solution to  
Figure 20 - Chilled Medium Diagram  
be used. Check with the local authority having  
jurisdiction.  
NOTE  
FOR HEATING: VALVES “H” OPEN, VALVES “C” CLOSED.  
FOR COOLING: VALVES “H” CLOSED, VALVES “C” OPEN.  
4. Mix the cleaning chemicals with water to create a  
concentrated solution. Pour the cleaning solution  
through one of the top tappings in the front section  
and plug it.  
ROOM  
UNIT  
EXP. TANK  
VENT  
5. Immediately fill the rest of the boiler and the heating  
system with water.  
H
RELIEF  
VALVE  
6. Fire the boiler and maintain a water temperature  
of 160°F to 200°F, 71°C to 93°C it may be  
necessary to cycle the boiler.  
C
PUMP  
DRAIN  
FILL  
VALVE  
7. Run all of the system pumps during the cleaning  
procedure.  
C
H
DRAIN  
CHILLER  
BOILER  
WARNING: Monitor the boiler pressure  
constantly during the cleaning procedure. Do  
not allow the boiler pressure to exceed the  
pressure listed on the pressure relief valve or a  
discharge of hot water and steam will occur!  
Cleaning of Water Boilers  
Normally the cleaning of water boilers is unnecessary  
unless there is unusually heavy contamination of the  
boiler or system.  
8. Shut the boiler off and allow the boiler to cool to  
100°F, 38°C. Open the 3" ball valves and drain the  
boiler and heating system.  
The burner must be installed and made operational  
along with the operating, limit and other safety controls.  
The burner on oil boilers must be adjusted to prevent  
sooting of the boiler flues.  
9. Remove the 3" ball valve and install 3" pipe caps  
in the ends of the 3" NPT nipples.  
Final burner adjustment should be made after the boiler  
has been properly cleaned.  
10. Refill the boiler and heating system with water.  
WARNING: The pressure relief valve must be  
installed and piped to the floor to prevent  
scalding in the event of a discharge, see Figure  
15.The discharge piping must be sized the same  
as the pressure relief valve outlet. Never install  
any type of valve between the boiler and the  
pressure relief valve! Failure to comply with this  
warning can result in an explosion causing  
extensive property damage, severe personal  
injury or death!  
STEAM BOILER PIPING  
Steam Boiler Pipeing Connections  
Table 3 contains the steam riser location schedule.  
Riser, equalizer and header pipe sizes are located in  
Table 8. A typical single boiler piping arrangement is  
shown in Figure 21. Figures 22 & 23 contain typical  
piping diagrams for steam boilers in a battery.  
NOTE: See CLEANING OF STEAM BOILERS before  
connecting the return piping.  
1. Install ball valves on the two 3" NPT nipples in the  
bottom of the front section and pipe to a suitable  
drain.  
CAUTION: Improper placement of steam risers will  
result in poor steam quality!  
Table 8 - Steam Boiler Piping Sizes  
2. Fill the boiler 3/4 full with water.  
Boiler  
Model  
Number of  
5" NPT Risers Size, NPT Size, NPT  
Header  
Equalizer  
3. Make a cleaning solution by mixing 1 lb, 0.45 kg  
each off caustic soda and trisodium phosphate for  
every 50 ga, 189 L of water, see Table 7.  
4 & 5  
6 & 7  
8 Through 10  
11 Through 18  
1
2
2
3
5"  
5"  
6"  
8"  
2 1/2"  
2 1/2"  
4"  
4"  
NOTE:The water content of the heating system must  
be added to the boiler water content.  
The steam piping should be pitched so the condensate  
flows in the direction of steam travel. The return tappings  
should be yoked to equalize the return flow, Figure 16.  
Swing joints should be used.  
CAUTION: Avoid skin contact with cleaning solution  
to prevent injury! If eye or skin contact occurs flush  
with large quantities of water.  
Page 19  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Table 9 - Steam Boiler Capacities  
Minimum Feed Water  
Pumping Rate  
Condensate Receiver  
Capacity  
Gallons  
I=B=R Gross Output  
Evaporation Rate  
Boiler  
Model  
MBH  
900  
kW  
264  
GPM  
1.9  
2.5  
3.1  
3.7  
4.2  
4.8  
5.4  
5.9  
6.5  
7.1  
7.7  
8.2  
8.8  
9.4  
9.9  
L/hr  
7.3  
9.5  
GPM  
3.9  
L/hr  
14.8  
18.9  
23.5  
27.6  
31.8  
36.3  
40.5  
45.1  
49.2  
53.8  
57.9  
62.5  
66.6  
70.8  
75.3  
Liters  
140  
182  
223  
261  
303  
345  
386  
428  
469  
511  
549  
591  
632  
674  
716  
28A-S-4  
28A-S-5  
28A-S-6  
28A-S-7  
28A-S-8  
28A-S-9  
28A-S-10  
28A-S-11  
28A-S-12  
28A-S-13  
28A-S-14  
28A-S-15  
28A-S-16  
28A-S-17  
28A-S-18  
37  
48  
59  
69  
80  
1166  
1433  
1699  
1965  
2232  
2498  
2764  
3031  
3297  
3563  
3830  
4096  
4362  
4629  
342  
420  
498  
576  
654  
732  
810  
888  
5.0  
6.2  
7.3  
8.4  
11.7  
13.8  
16.0  
18.1  
20.3  
22.5  
24.7  
26.8  
29.0  
31.2  
33.3  
35.5  
37.6  
9.6  
91  
10.7  
11.9  
13.0  
14.2  
15.3  
16.5  
17.6  
18.7  
19.9  
102  
113  
124  
135  
145  
156  
167  
178  
189  
966  
1044  
1122  
1200  
1278  
1356  
Note: These recommendations are considered normal for compact buildings. Where buildings are spread out,  
additional receiver capacity may be necessary because of the extended time required for condensate to return to  
the receiver.  
Figure 21 - Typical Single Boiler Steam Piping  
Page 20  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 22 - Typical Steam Piping - Gravity Return for Multiple Boilers  
Figure 23 - Typical Steam Piping - Pumped Return for Multiple Boilers  
Page 21  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Install 3" nipples and ball valves in the two 3" NPT front  
section tappings so the boiler can be blown down.  
to prevent injury! If eye or skin contact occurs flush  
with large quantities of water.  
The feed water requirements for steam boilers at full  
input are shown in Table 9. The addition of water to the  
boiler should be controlled by sensing the actual boiler  
water level. 1" NPT water column tappings are provided  
on the front section for the mounting of the required  
water level controls, see Figure 17.  
NOTE: Some locations do not allow this solution to  
be used. Check with the local authority having  
jurisdiction.  
5. Mix the cleaning chemicals with water to create a  
concentrated solution. Pour the cleaning solution  
through one of the top tappings in the front section  
and plug it.  
CAUTION: Makeup water connections must be made  
to the return piping and not to the boiler or the  
boiler may be damaged voiding the warranty!  
6. Immediately fire the boiler and maintain a steam  
pressure of 0 to 2 psig, 0 to 13.8 kPa. It may be  
necessary to cycle the boiler.  
Cleaning of Steam Boilers  
The burner must be installed and made operational  
along with the operating, limit and other safety controls.  
The burner on oil boilers must be adjusted to prevent  
sooting of the boiler flues. Final burner adjustment  
should be made after the boiler has been properly  
cleaned.  
WARNING: Monitor the boiler pressure  
constantly during the cleaning procedure. Do  
not allow the boiler pressure to exceed 15 PSI,  
103 kPa or a discharge of hot water and steam  
will occur!  
CAUTION: Failure to properly clean the boiler can  
result in foaming and surging and prevent proper  
operation of the boiler! Boiler damage can occur  
voiding the warranty!  
7. Adjust the water feed to prevent the build up of  
pressure within the boiler. Continue the skimming  
process until the discharge runs clear.  
8. Shut the boiler off and allow the boiler to cool to  
100°F, 34°C. Remove the skim piping and plug the  
tapping. Open the blowdown valve and flush the  
boiler until the discharge runs clear.  
NOTE: Do not connect the boiler to the return piping  
until the system piping has been thoroughly flushed  
or recontamination of the boiler can occur.  
1. Plug the 4" NPT return tappings in the back section  
and any other unused tappings, see step 5 below.  
9. Close the blowdown valve and fill the boiler with  
water to a level 1in., 25 mm below the normal water  
level line.  
WARNING: The safety valve must be installed  
and piped to the floor to prevent scalding in the  
event of a discharge, see Figure 15. The  
discharge piping must be sized the same as the  
safety valve outlet. Never install any type of  
valve between the boiler and the safety valve!  
Failure to comply with this warning can result  
in an explosion causing extensive property  
damage, severe personal injury or death!  
10. Check the traps and vents for proper operation.  
BURNER INSTALLATION  
WARNING: The burner must be installed in  
accordance with the burner manufactures  
instructions. Check the boiler rating plate to  
make sure that the boiler is for the type of fuel  
that will be used. If it isnt, do not connect the  
burner to the fuel supply. Failure to comply with  
this warning can result in extensive property  
damage, severe personal injury or death!  
2. Fill the boiler with water to a level 1 in., 25.4 mm  
below the normal water level line of 50 1/2 in.,  
1.28 m from the floor.  
3. Pipe a skimmer off the 6" NPT tapping in the front  
section using 1 1/2" NPT pipe.  
Follow the burner manufacturer’s installation instructions  
for the proper installation, fuel piping, wiring, burner  
adjustment and servicing. Mount the burner per the  
instructions on page 13.  
4. Make a cleaning solution by mixing 1 lb, 0.45 kg  
each off caustic soda and trisodium phosphate for  
every 50 ga, 189 L of water, see Table 7.  
When applicable, provisions for vent, bleed and gas  
relief lines must be made in accordance with the latest  
revision of ANSI Z223.1/NFPA 54.  
CAUTION: Avoid skin contact with cleaning solution  
Page 22  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
WARNING: Never use an open flame to test for  
gas leaks. Always use an approved leak  
detection method. Failure to comply with this  
warning can cause extensive property damage,  
severe personal injury or death!  
Water Boilers  
Fill the boiler and all of the radiation with water to the  
required system pressure. Completely purge the system  
of air and adjust the system pressure as needed.  
CAUTION: Thermal shock of water boilers must be  
avoided! Water circulation must be established  
before the burner is fired. If hot standby is required,  
special piping and operation procedures are  
necessary, consult your Smith representative.  
Failure to protect the boiler from thermal shock can  
damage the boiler, voiding the warranty!  
Whenever the gas supply piping is pressure tested the  
boiler gas controls must be protected. If the test  
pressure is equal to, or less than 1/2 psig, 3.5 kPa,  
isolate the boiler by closing the manual shut off valve  
in the gas supply pipe to the boiler. If the test pressure  
is greater than, or equal to 1/2 psig, 3.5 kPa, disconnect  
the boiler and its individual shut-off valve from the gas  
supply.  
Steam Boilers  
Fill the boiler with water to the normal water level line  
of 50 1/2 in., 1.28 m from the floor.  
ELECTRICAL WIRING  
Electrical Power Connections  
If the boiler is connected to a hot steam line, keep the  
cold boiler valved off line and fire the burner until the  
boiler pressure exceeds the system pressure by 1 to 2  
psig, 7 to 14 kPa. Slowly open the main isolation valve  
on the boiler to bring it on line.  
CAUTION: Label all wires prior to disconnection  
when servicing controls. Wiring errors can cause  
improper and dangerous operation! Verify proper  
operation after servicing.  
CAUTION: Never place a cold boiler into service on  
a hot steam line or severe damage to the boiler and  
piping can occur voiding the warranty!  
The electrical connections to this boiler must be made  
in accordance with all applicable local codes and the  
latest revision of the National Electrical Code, ANSI/  
NFPA-70. Installation should also conform with CSA  
C22.1 Canadian Electrical Code Part I if installed in  
Canada. Install a separate circuit properly rated for the  
boiler. A shut-off switch should be located at the boiler.  
Steam entering a cold boiler will cool quickly and can  
cause severe steam hammer and boiler flooding. Idle  
boilers not valved off from the system should have an  
overflow installed to prevent it from being flooded.  
The boiler must be grounded in accordance with the  
authority having jurisdiction, or if none, the latest revision  
of the National Electrical Code, ANSI/NFPA-70.  
If an overflow trap is not installed per Figure 24, and  
the boiler becomes flooded, the flooded boiler must be  
heated to a near steaming condition, 210°F, 99°C, then  
drained to the correct water level.  
Line voltage field wiring of any controls or other devices  
must conform to the temperature limitation of type T wire  
at 95°F, 35°C above room temperature. Use copper  
conductors with a minimum size of #14 awg.  
Water and Steam Boilers  
Follow the burner manufactures lighting instructions that  
were supplied with the burner.  
BOILER OPERATION  
WARNING: Never attempt to start the burner if  
the combustion chamber contains excess oil or  
gas, when the boiler is full of vapor or the  
combustion chamber is very hot. Failure to  
comply with this warning can result in an  
explosion causing extensive property damage,  
severe personal injury or death!  
WARNING: Before proceeding read and fully  
understand the instructions contained in this  
manual. Do not attempt to operate this boiler if  
it has not been installed in accordance with the  
guidelines set forth in this manual. Failure to  
comply with this warning can result in extensive  
property damage, severe personal injury or  
death!  
A properly adjusted gas burner on high fire will produce  
a CO2 of 8.5 to 9.5% with a CO level under 300 ppm.  
When firing on oil at high fire, the burner should be  
adjusted to produce a CO2 of 11.0 to 12.0% with a zero  
smoke. The flue gas samples should be taken at the  
smoke hood. Confirm proper burner adjustment with a  
calibrated combustion analyzer.  
CAUTION:The supply temperature of a boiler set for  
a 20°F, 11°C temperature rise must not be below  
140 °F, 60°C for an oil boiler, 149°F, 65°C for a gas  
boiler. Failure to protect the boiler from low return  
water temperatures will damage the boiler, voiding  
the warranty!  
Page 23  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Hi Limit  
BOILER CHECKING & ADJUSTMENT  
The aquastat high limit controls the maximum water  
CAUTION: Never increase the input to the boiler  
above that for which it is rated. Doing so can cause  
premature failure of the boiler!  
temperature in the boiler. It is adjustable from 140°F,  
60°C to 240°F, 116°C. If the water temperature reaches  
the set temperature before the demand for heat has  
been met, the aquastat high limit should shut the boiler  
off. The water temperature should never exceed the  
maximum set point of 240°F, 116°C. The aquastat high  
limit cannot be repaired. If it fails to function properly  
replace it.  
Low Water Cutoff  
Ensure that the low water cutoff device(s) function(s)  
properly. Test in accordance with the manufacturer’s  
instructions included with the device(s).  
Figure 24 - Recommended Overflow Trap Piping  
Heat Exchanger Cleaning  
A flue temperature over 550°F, 288°C, indicates that the  
boiler needs to be cleaned.  
BOILER MAINTENANCE  
WARNING: Servicing, inspection and adjustment  
of the boiler must be done by a trained  
technician in accordance with all applicable  
local and national codes. Improper servicing or  
adjustment can result in property damage,  
severe personal injury or death!  
1. Shut off the electrical power and the fuel supply to  
the boiler.  
2. Remove the left side jacket panels.  
3. Remove the cleanout covers, Figure 7.  
4. Clean each flue passage with a wire brush.  
The boiler should be cleaned and inspected once a year,  
before each heating season.  
5. If heavy deposits are present, pull the burner and  
vacuum out the combustion chamber.  
Page 24  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
6. Vacuum out the burner base and clean and inspect  
Controls  
all of the components. Replace any damaged or  
badly corroded parts.  
1. Low water cutoff devices must be serviced per the  
manufacture’s instructions.  
7. Inspect the cleanout cover insulation and rope seal.  
If damaged or deteriorated replace them.  
2. The relief valve should vent water when the test  
lever is lifted. It should not weep or discharge water  
at normal system pressure.  
8. Install the clean out covers and reseal them with a  
silicone caulk rated for 500°F, 260°C.  
WARNING: Never try to clean or repair the relief  
valve! If the valve fails to operate properly,  
replace it! Failure to comply with this warning  
can result in an explosion causing extensive  
property damage, severe personal injury or  
death!  
9. Install the left jacket panels and remount the burner.  
10. Restore electrical power and fuel to the boiler.  
Vent System  
Thoroughly inspect the vent system for any signs of  
blockage, corrosion or leakage. Immediately replace any  
unsound vent system piping.  
3. Use a combustion analyzer to ensure that the  
burner is adjusted properly, see BOILER  
OPERATION.  
Page 25  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Figure 25 - Boiler Assembly  
Page 26  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Number of Sections with Item Quantities Below  
Ref #  
Name of Part  
Part #  
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
1
2
Front Section  
3621  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Graphite Port Connector Set  
Draw Rod Washers  
60375  
3
4
5
6
7
8
9
10 11 12 13 14 15 16 17  
3
62099 12 16 20 24 28 32 36 40 44 48 52 56 60 64 68  
60102 12 16 20 24 28 32 36 40 44 48 52 56 60 64 68  
60877 24 32 40 48 56 64 72 80 88 96 104 112 120 128 136  
4
5/8" x 11" Draw Rods  
5
Draw Rod Hex Nuts  
6
8(2)  
Rope, 1/2" x 12 1/2 feet  
Cleanout Cover Assembly  
Cleanout Cover Nut  
70660  
70592  
60245  
62095  
76538  
61414  
70614  
69371  
69372  
69373  
69904  
70633  
70611  
70612  
70613  
74301  
61997  
61998  
61999  
62000  
62002  
61983  
61984  
61985  
61986  
61987  
3630  
3
3
6
6
1
6
1
1
4
4
8
8
1
8
1
1
5
5
6
6
7
7
8
8
9
9
10 11 12 13 14 15 16 17  
10 11 12 13 14 15 16 17  
9
10 12 14 16 18 20 22 24 26 28 30 32 34  
10 12 14 16 18 20 22 24 26 28 30 32 34  
10  
11  
12  
13  
Cleanout Cover Washer  
Cleanout Cover Rope Seal, 3/8" x 45"  
Cleanout Cover Bolt  
1
1
1
1
1
1
1
1
1
1
1
1
1
10 12 14 16 18 20 22 24 26 28 30 32 34  
Rear Observation Port Assembly  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
14  
15  
Slide Damper  
1
1
1
1
1
1
1
1
1
1
1
1
Flue Outlet Increaser, 16" to 18"  
Smoke Hood Assembly, 10"  
Smoke Hood Assembly, 12"  
Smoke Hood Assembly, 14"  
Smoke Hood Assembly, 16"  
Smokehood insulating tape  
1
1
1
1
1
1
1
1
1
16(1)  
16A  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
3/4" Water Relief Valve, 40 lb.  
1" Water Relief Valve, 40 lb.  
17  
18  
1 1/4" Water Relief Valve, 40 lb.  
1 1/2" Water Relief Valve, 40 lb.  
2" Water Relief Valve, 40 lb.  
1
1
1
1
1
1
1
1
1
1
1 1/4" Steam Safety Valve, 15 lb.  
1 1/2"Steam Safety Valve, 15 lb.  
2" Steam Safety Valve, 15 lb.  
2 1/2"Steam Safety Valve, 15 lb.  
3" Steam Safety Valve, 15 lb.  
Back Section  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
19  
20  
1
Intermediate Section w/ 5" Tapping & Boss  
Intermediate Section, Plain with Boss  
Intermediate Section, Plain w/o Boss  
Int. Section w/ Heater Opening w/o Boss  
Hi Limit Control, L4006E  
3624  
Section quantities based on model ordered  
Section quantities based on model ordered  
One per water boiler  
3622  
21  
3658  
3623  
22  
23  
50507  
60327  
50653  
50655  
70628  
50510  
60267  
61931  
60317  
60326  
60318  
60314  
3420  
Tankless Cover Plate & Coil Gasket  
Tankless Heater, 8 GPM, 30 L/H  
Tankless Heater, 12 GPM, 45 L/H  
Tankless Cover Plate with Gasket  
Operating Control, L4007A  
Quantities based on model ordered  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
Quantities based on model ordered  
One per water boiler  
3 1/2" Temperature/Pressure Gage  
Gauge Glass, 5/8" x 11 1/2"  
Observation Glass Gasket, Inner  
Observation Glass  
One per water boiler  
One per steam boiler  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Observation Glass Gasket, Outer  
Observation Glass Holder  
Observation Glass Cover Plate  
(1) Smokehood assembly includes the smokehood, slide damper, angle bracket and hardware.  
(2) Cleanout cover assembly includes the cleanout cover, insulation, rope and mounting hardware.  
Page 27  
SERIES 28A BOILER INSTALLATION AND OPERATION INSTRUCTIONS  
Number of Sections with Item Quantities Below  
Ref #  
Name of Part  
Part #  
4
5
6
7
8
9
10  
11  
12  
13  
14  
15  
16  
17  
18  
ns  
Rear Observation Port Hardware  
71301  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Burner Mounting Plate Assembly, 9"  
Burner Mounting Plate Assembly, 10 1/4"  
Burner Mounting Plate Assembly, 12 1/2"  
Burner Mounting Plate Assembly, 10 1/4"  
Burner Mounting Plate Assembly, 7 3/4"  
Burner Mounting Plate Hardware  
70641  
70640  
70510  
70672  
70669  
71267  
69645  
34(3)  
Burner mounting plate determined by burner selection  
ns  
35  
36  
ns  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Burner Mounting Plate Insulating Block  
Burner Mounting Plate Rope Seal, 3/8 x 7 ft. 76540  
Burner Mtg. Plate Ins. Block Hardware  
Operating Control, PA404A  
3 1/2" Steam Gage  
71268  
50493  
60269  
50494  
70492  
60090  
37  
38  
39  
n/s  
n/s  
One per steam boiler  
One per steam boiler  
One per steam boiler  
Hi Limit Control, L404C  
Can of Spray Adhesive  
Flue Brush  
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
(3) Burner mounting plate assembly includes the burner mounting plate with the observation glass and cover.  
WARNING  
Any appliance that burns natural gas, propane gas, fuel oil, wood or coal is capable of producing carbon  
monoxide (CO).  
Carbon Monoxide (CO) is a gas which is odorless, colorless and tasteless but is very toxic.  
If your Smith boiler is not working properly, or is not vented properly, dangerous levels of CO may accumulate.  
CO is lighter than air and thus may travel throughout the building. BRIEF EXPOSURE TO HIGH  
CONCENTRATIONS OF CO, OR PROLONGED EXPOSURE TO LESSER AMOUNTS OF CO MAY RESULT IN  
CARBON MONOXIDE POISONING.  
EXPOSURE CAN BE FATAL AND EXPOSURE TO HIGH CONCENTRATIONS MAY RESULT IN THE  
SUDDEN ONSET OF SYMPTOMS INCLUDING UNCONSCIOUSNESS.  
Symptoms of CO poisoning include the following:  
dizziness  
headaches  
nausea  
vision problems  
loss of muscle control  
weakness  
shortness of breath  
unclear thinking  
unconsciousness  
The symptoms of CO poisoning are often confused with those of influenza, and the highest incidence of poisoning  
occurs at the onset of cold weather or during flu season. A victim may not experience any symptoms, only one  
symptom, or a few symptoms. Suspect the presence of carbon monoxide if symptoms tend to disappear when  
you leave your home.  
The following signs may indicate the presence of carbon monoxide:  
• Hot gases from appliance, venting system, pipes or chimney, escaping into the living space.  
• Flames coming out around the appliance.  
• Yellow colored flames in the appliance.  
• Stale or smelly air.  
• The presence of soot or carbon in or around the appliance.  
• Very high unexplained humidity inside the building.  
If any of the symptoms of CO poisoning occur, or if any of the signs of carbon monoxide are present, VACATE  
THE PREMISES IMMEDIATELY AND CONTACT A QUALIFIED HEATING SERVICE COMPANY OR THE GAS  
COMPANY OR THE FIRE DEPARTMENT.  
To reduce the risk of CO poisoning, have your heating system “tuned up” by a licensed heating contractor or the  
gas company -- preferably before each heating season. Also have the service company check your chimney or  
vent pipes for blockage.  
Your home should also be adequately ventilated, particularly if you have insulated your home.  
ONLY QUALIFIED, LICENSED SERVICE CONTRACTORS  
SHOULD PERFORM WORK ON YOUR SMITH BOILER.  
WARNING  
Install, operate and maintain unit in accordance with manufacturer's instructions to avoid exposure to fuel sub-  
stances or substances from incomplete combustion which can cause death or serious illness. The State of  
California has determined that these substances may cause cancer, birth defects, or other reproductive harm.  
Also, install and service this product to avoid exposure to airborne particles of glasswool fibers and/or ceramic  
fibers known to the State of California to cause cancer through inhalation.  
In an effort to continually improve our products, Smith reserves the right to make changes without notice.  
WESTCAST, INC.  
260 NORTH ELM STREET WESTFIELD, MA 01085  
TEL. (413) 562-9631 FAX (413) 562-3799  

Vivitar DVR 940HD User Manual
Vivitar 840XHD User Manual
Uniden ECO TERRA GMR635 2CK User Manual
Toshiba Camileo S30 User Manual
Sony XR CA360 User Manual
Sony TRV815 User Manual
Sony CFS W338S User Manual
Sharp XE A22S Cash Register XE A22S User Manual
Samsung T50200IB User Manual
Samsung ST80 User Manual