Raypak RAYTHERM 0133 4001 User Manual

CATALOGNO. 3000.52H  
Effective:  
Replaces:  
07-15-06  
11-01-04  
INSTALLATION  
AND OPERATING  
INSTRUCTIONS  
TM  
RAYTHERM  
HOT WATER SUPPLY  
HEATERS  
Models 0133-4001  
Types WH & NH  
FOR YOUR SAFETY  
Do not store or use gasoline or other flammable vapors and liquids or other combustible  
materials in the vicinity of this or any other appliance. To do so may result in an explosion  
or fire.  
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause  
property damage, personal injury or loss of life. Refer to this manual. Installation and service  
must be performed by a qualified installer, service agency or the gas supplier.  
FOR YOUR SAFETY  
WHAT TO DO IF YOU SMELL GAS  
*Do not try to light any appliance.  
*Do not touch any electrical switch; do not use any phone in your building.  
*Immediately call your gas supplier from a neighbor's phone. Follow the gas supplier's  
instructions.  
*If you cannot reach your gas supplier, call the fire department.  
This manual should be maintained in legible  
condition and kept adjacent to the heater or in a  
safe place for future reference.  
P/N241075Rev. 1  
RECEIVING EQUIPMENT  
ALL MODELS (APPROVED)  
On receipt of the equipment, visually check for  
All models are National Board approved. Tem-  
external damage to the carton or the shipping crate. If perature and pressure gauge is standard. Intermittent  
the carton or shipping crate is damaged, make a note ignition device is standard on models 0514 and up.  
on the Bill of Lading and report the damage to the  
Carrier immediately. Remove the heater from the pass.  
carton or the shipping crate.  
Model 0133 has 4-pass heat exchanger, 1 tube per  
Models 0181-0401 have 2-pass heat exchangers,  
Do NOT use the shipping crate base as an instal- 5 tubes first pass, 4 tubes second pass.  
lation base. Models 0514-1826 have 2-pass heat exchangers,  
On occasion, items are shipped loose. Be sure that 5 tubes first pass, 4 tubes second pass.  
you receive the number of packages indicated on the  
Bill of Lading.  
Models 2100-4001 have 2-pass heat exchangers,  
9 tubes per pass.  
When ordering parts, you must specify Model and  
Serial Number of the heater. When ordering under  
warranty conditions, you must also specify date of  
installation.  
Raypak recommends that this manual be reviewed  
thoroughly before installing your Raypak heater. If  
there are any questions which this manual does not  
answer, please contact the factory or your local Raypak  
representative.  
Claims for shortages and damages must be filed  
with carrier by consignee. Permission to return goods  
must be factory-authorized and are subject to a stock-  
ing charge.  
Purchased parts are subject to replacement only  
under the manufacturer's warranty. Debits for defec-  
tive replacement parts will not be accepted and will be  
replaced in kind only per our standard warranties.  
Models 926-4001 have optional single pass with  
cast iron headers only.  
HOT WATER SUPPLY HEATERS  
All Raypak hot water supply heaters are ASME and  
design certified as hot water heaters, with 125 PSI  
pressure relief valves.  
TYPE WH1 WITH ON/OFF CONTROLS  
Models 0133-4001  
To be used with storage tank systems. Available  
with integrally mounted pump, factory mounted and  
wired for models 0133-1826. Models 181,261,331 and  
401 are Low NOx Hot Water Heaters.  
TYPE WH2 WITH MODULATING CONTROLS  
Models 0133-4001  
Hot water supply heater with 110°-170°F gas  
modulation. Available with integrally mounted pump,  
factory mounted and wired for models 0133-1826. To  
be used with storage tank systems.  
MODEL IDENTIFICATION  
The model identification number and the heater  
serial number are found on the heater data plate. The  
model number will have the form WH1-0514A or simi-  
lar depending on the heater model.  
(WH = Hot Water Supply System, 1 = on/off firing, 0514  
= size of heater).  
Rated inputs are suitable for up to 2000 feet eleva-  
tion. For elevations above 2000 feet, reduce input 4%  
for each 1000 feet above sea level.  
TYPE WH3 WITH 2-STAGE CONTROLS  
Models 0181-4001  
Hot water supply heater with low-high fire for  
2-stage control. Available with integrally mounted  
pump, factory mounted and wired for models 0181-  
1826. To be used with storage tank systems.  
TYPE NH INSTANT-PAK  
Models 0514-1826  
GENERAL SPECIFICATIONS  
Tankless instantaneous direct fired hot water sup-  
ply heater with 110°-170°F gas modulation, factory  
mounted bronze body or cast iron bronze fitted pump  
and flow switch.  
The Raypak water heaters are design certified and  
tested under the latest requirements of the American  
NationalStandard,ANSIZ21.10.3/CSA4.3. Eachheater  
hasbeenconstructedandpressuretestedinaccordance  
with the requirements of Section IV of the American  
Society of Mechanical Engineers Code, and factory fire  
tested.  
CALIFORNIA PROPOSITION 65 WARNING:  
This product contains chemicals known to the State  
of California to cause cancer, birth defects or other  
reproductive harm.  
3
!
General Safety Precautions  
Be sure to read and understand the entire Instruction Manual before attempting to install or operate this water heater. Pay  
particular attention to the following general Safety Precautions. Failure to follow these warnings could result in a fire or  
explosion, causing property damage, bodily injury or death. Should you have any problems understanding the instructions  
in this manual, STOP, and get help from a qualified installer or service technician or the gas supplier.  
!
!
DANGER  
WARNING  
Gasoline, as well as other flammable materials and liquids PROPANE MODELS – Propane must be used with great  
(adhesives, solvents, etc.), and the vapors they produce, are caution.  
extremely dangerous. DO NOT handle, use or store gasoline • It is heavier than air and will collect first in lower areas  
or other flammable or combustible materials anywhere near making it hard to detect at nose level.  
or in the vicinity of a water heater. Be sure to read and follow • Make sure to look and smell for propane leaks before  
thewarninglabelpicturedbelowandotherlabelsonthewater attempting to light appliance. Use a soapy solution to check  
heater, as well as the warnings printed in this manual. Failure all gas fittings and connections. Bubbling at a connection  
to do so can result in property damage, bodily injury, or death. indicates a leak that must be corrected. When smelling to  
detect a propane leak, be sure to sniff near the floor too.  
• Gas detectors are recommended in propane applications  
and their installation should be in accordance with the  
!
DANGER  
Failure to install the drafthood and properly vent the water manufacturer's recommendations and/or local laws, rules,  
heater to the outdoors as outlined in the Venting Section of regulations or customs.  
this manual can result in unsafe operation of the water heater. • It is recommended that more than one method be used to  
To avoid the risk of fire, explosion, or asphyxiation from detect leaks in propane applications.  
carbon monoxide, never operate this water heater unless it is IF PROPANE IS PRESENT OR SUSPECTED:  
properly vented and has an adequate air supply for proper • DO NOT attempt to find the cause yourself;  
operation. Be sure to inspect the vent system for proper DO NOT try to light any appliance;  
installation at initial start-up; and at least annually thereafter. • DO NOT touch any electrical switch;  
Refer to the Venting section of this manual (pg. 11) for more • DO NOT use any phone in your building.  
information regarding vent system inspections.  
• Leave the building immediately and make sure that every-  
one else leaves also.  
• Leave the doors open for ventilation and contact the gas  
supplier, a qualified service agency or the fire department.  
• Keep the area clear until the service call has been made,  
the leak is corrected, and a qualified agency has determined  
the area to be safe.  
DANGER  
!
!
WARNING  
Both propane and natural gas have an odorant added to help  
detection. Some people may not physically be able to smell  
or recognize this odorant. If unsure or unfamiliar about the  
smell associated with propane or natural gas, ask the gas  
supplier. Other conditions, such as "Odorant Fade", which  
causes the odorant to "fade", or diminish in intensity can also  
hide or camouflage a gas leak.  
Vapors from flammable liquids Water heater has a main  
will explode and catch fire burner and pilot flame.  
causing death or severe The pilot flame:  
burns.  
1. Is on all the time or intermit-  
!
DANGER  
Do not use or store flammable tently (IID).  
products such as gasoline sol- 2. Will ignite flammable va-  
ventsoradhesivesinthesame pors.  
room or area near the water  
heater.  
Water heaters utilizing propane are different from natural gas  
models. A natural gas heater will not function safely on  
propane and vice versa. Conversion from natural gas to  
propane (or vice versa) must be done by a qualified service  
technician. To avoid possible equipment damage, personal  
injury or fire: DO NOT connect this water heater to a fuel type  
not in accordance with unit data plate. Use propane for  
propane units, natural gas for natural gas units. These units  
are not certified for any other type fuel.  
Vapors:  
1. Cannot be seen,  
Keep flammable products:  
1. Far away from heater,  
2. In approved containers,  
3. Tightly closed and  
2. Are heavier than air,  
3. Go a long way on the floor,  
4. Can be carried from other  
rooms to the pilot flame by air  
currents.  
4. Out of children's reach.  
Installation:  
!
WARNING  
Do not install water heater where flammable products will be  
stored or used unless the main burner and pilot flames are at  
least 18" above the floor. This will reduce, but not eliminate, the  
Propane appliances should not be installed below-grade (for  
example, in a basement) if such installation is prohibited by  
federal, state and/or local laws, rules, regulations or customs.  
risk of vapors being ignited by the main burner or pilot flame.  
Read and follow water heater warnings and instructions. If  
owners manual is missing, contact the retailer or manufacturer.  
4
INSTALLATION INSTRUCTIONS  
INSTALLATION CODES  
Installation must be in accordance with local codes, or, in the absence of local codes, with the latest editions  
of the National Fuel Gas Code, ANSI Z223.1/NFPA 54, and the National Electrical Code, ANSI/NFPA 70. In  
Canada installations must conform with the current CAN/CSA B149.1 and the Canadian Electrical Code Part 1  
CSA C22.2 No.1. Where required by the authority having jurisdiction, the installation must conform to American  
SocietyofMechanicalEngineersSafetyCodeforControlsandSafetyDevicesforAutomaticallyFiredHeaters,CSD-  
1.  
INSTALLATION BASE  
The heater should be mounted on a level, non-combustible surface. Heater must not be installed on  
carpeting. The heater can be installed on a combustible surface only when the appropriate listed floor shield base  
is provided. An optional listed floor shield base is available for factory installation with the heater on all indoor  
models. Do NOT use the shipping base crate as an installation base.  
NOTE: The heater should be located in an area where water leakage will not result in damage to the area adjacent  
to the appliance or to the structure. When such locations cannot be avoided, it is recommended that a suitable  
drain pan, adequately drained, be installed under the appliance. The pan must not restrict air flow.  
In addition, the heater shall be installed such that the gas ignition system components are protected from water  
(dripping, spraying, rain, etc.) during appliance operation and service (circulator replacement, control replace-  
ment, etc.).  
Combustible floorshield ordering information:  
ALTERNATE METHOD FOR PROVIDING A NON-  
COMBUSTIBLE BASE  
Fig.# 8148  
5
CLEARANCES  
CLEARANCES TO PROTECTED SURFACES  
INSTALLATION CLEARANCES  
(All Dimensions Are In Inches)  
Note: The heater shall be installed in a space large in  
comparison to the size of the heater. Large space is  
defined as having a volume at least sixteen (16) times  
the total volume of the heater.  
CLEARANCES FROM COMBUSTIBLE  
SURFACES  
Note 1:  
Combustible floor shield is required when heater is to  
be installed on a combustible surface. (See ordering  
info. on pg.5.)  
Note 2:  
Servicing Clearances: Provide at least 24" (Models  
0133-1826), 48" (Models 2100-4001) in front of unit for  
removal & servicing of the Controls & Burner Tray.  
Provide at least 18" on side opposite water connec-  
tions for deliming of Heat Exchanger Tubes.  
*Vent includes factory supplied drafthoods and does  
not include field supplied vent systems above the  
drafthood. On Models 2100-4001 drafthood is built  
into heater.  
6
SPECIFICATIONS AND DIMENSIONS  
MODEL 133  
NOTE:  
Ratingsareshownforelevationsupto2,000feet. Forelevationsover  
2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.  
* Recovery based on manufacturer's rating.  
MODELS 182-400 and 181-401  
NOTE:  
Ratings are shown for elevations up to 2,000  
feet. For elevations over 2,000 feet, reduce  
ratings 4% for each 1,000 feet above sea level.  
Bold type indicates Low NOx models.  
* Recovery based on manufacturer's rating.  
7
MODELS 514-824  
NOTE:  
Ratings are shown for elevations up to 2,000 feet. For  
elevations over 2,000 feet, reduce ratings 4% for each 1,000  
feet above sea level.  
*Recovery based on manufacturer's rating.  
MODELS 962-1826  
NOTE:  
Ratings are shown for elevations  
up to 2,000 feet. For elevations  
over 2,000 feet, reduce ratings  
4% for each 1,000 feet above sea  
level.  
*Recovery based on manufacturer's rating.  
8
MODELS 926-1758  
NOTE:  
Ratingsareshownforelevationsupto2,000feet. Forelevationsover  
2,000 feet, reduce ratings 4% for each 1,000 feet above sea level.  
*Recovery based on manufacturer's rating.  
MODELS 2100-4000  
NOTE:  
Ratings are shown for elevations up to 2,000 feet. For  
elevations over 2,000 feet, reduce ratings 4% for each 1,000  
feet above sea level.  
*Recovery based on manufacturer's rating.  
9
OUTDOOR WATER HEATERS  
These heaters are design certified for out-  
door installation. Heaters must not be installed  
under an overhang of less than three (3) feet from  
the top on the heater. Three (3) sides must be  
open in the area under the overhang. Roof water  
drainage must be diverted away from the heaters  
installed under overhangs with the use of gutters.  
The point from where the flue products exit  
the heater must be a minimum of four (4) feet  
below, four (4) feet horizontally from or one (1)  
foot above any door, window or gravity inlet to a  
building. The top surface of the heater shall be at  
least three (3) feet above any forced air inlet, or  
intake ducts located within ten (10) feet horizon-  
tally.  
Fig. #8245  
HIGH WIND CONDITIONS (Outdoor Units Only)  
In areas where high winds are frequent, it may be necessary to locate the heater a minimum of 3' from high  
vertical walls, or install a wind break so the heater is not in direct wind current.  
COMBUSTION AIR (Indoor Units Only) Air For Combustion And Ventilation  
The heater must have both combustion and ventilation air. Minimum requirements for net free air supply  
openings are 12 inches from ceiling for ventilation and 12 inches from the floor for combustion air as outlined  
in ANSI Z223.1, and any local codes that may have jurisdiction.  
CAUTION: Combustion air must not be contaminated by corrosive chemical fumes which can damage the heater.  
Measures must be taken to prevent the entry of corrosive chemical fumes to the combustion and ventilation air  
supply. Such chemicals include, but are not limited to, chlorinated and/or fluorinated hydrocarbons such as found  
in refrigerants, aerosol propellants, dry-cleaning fluids, degreasers, and paint removers. Other harmful elements  
may come from bleaches, air fresheners, or mastics. Vapors from these types of products can form corrosive  
acid compounds when burned in a gas flame. The resulting acid condensate can damage or substantially reduce  
the life of the heater. It may become necessary to provide outside air directly to the heater in order to avoid this  
problem.  
a. All Air From Inside The Building:  
b. All Air From Outdoors:  
Each opening shall have a minimum net free square When air is supplied directly from outside of building,  
inches as noted:  
each opening shall have a minimum net free square  
inches as noted:  
NOTE: If louvers, grills or screens are used on the openings, obtain the net free area from their supplier or manufacturer. If  
the design free area of a louver is not known nor available, it shall be assumed that wood louvers will have 20-25 percent  
free area and metal louvers will have 60-75 percent free area as shown in Sec. 5.3.5 National Fuel Gas Code.  
10  
VENTING  
MODELS 514-824  
OUTDOOR INSTALLATIONS  
Step 1: Lower outdoor "Stackless" top onto unit.  
Position top so it is centered on unit from  
side-to-side and front-to-rear.  
MODEL 133  
Step 1: Remove the front (4) screws.  
Step 2: Line up outdoor top vent opening over heater  
vent opening.  
Step 3: Lower outdoor top onto unit lining up slots in  
the outdoor top with screws holes in jacket top.  
Step 4: Reinstall (5) screws to secure jacket top and  
outdoor top to unit.  
Fig# 8166  
Fig. #8114  
Step 2: Tighten the (4) screws (Shown below) until  
they come in contact with the unit jacket top,  
then evenly tighten all (4) screws to secure  
to unit.  
MODELS 181-401 and 182-400  
Fig# 8278.1  
VENT TERMINAL (Outdoor) Stackless Top Installa-  
tion  
1. Insert tabs into  
keyhole (4 places).  
2. Snap tabs into keyholes  
so as not to pull out.  
Fig# 8233  
MODELS 926-1758  
Heaters are shipped with outdoor vent terminal  
factory installed.  
MODELS 2100-4001  
These units are not certified for outdoor installa-  
tion.  
Pagoda Top (Shipped Loose with Heater)  
Fig. #RP8280.1  
11  
INDOOR INSTALLATIONS  
MODEL 133  
Step 1. Shut-off main electrical power switch to heater.  
Step 2. Turn heater manual switch, located in upper control panel, to the "OFF" position.  
Step 3. Shut-off gas supply and water supply to the heater.  
Step 4. Mount drafthood on heater and attach with the 8 sheet metal screws provided. Drafthood  
should be positioned with the vent sensor located on the front left side as shown.  
Step 5. Remove plastic plug from left side of heater jacket and install the plastic grommet provided.  
Step 6. Route flue sensor wire harness through the grommet installed in Step 5.  
. #8946  
Step
BEFORE  
AFTER  
INSTALLATION  
OF DRAFTHOOD  
INSTALLATION  
OF DRAFTHOOD  
. #8947  
Step 8. Disconnect male/female connector and attach to the 2 wires from drafthood vent sensor harness.  
12  
MODELS 514-824  
MODELS 181-401 and 182-400  
VENT TERMINAL/INDOOR STACK  
INSTALLATION  
Locate and assemble as shown below. Secure with  
screws supplied in envelope in carton.  
1. Remove the louvered jacket top by removing  
four (4) #10 flathead screws.  
2. If originally installed, remove "Pagoda" top  
from the louvered jacket top.  
3. Place the inner stack adapter panel over the  
flue collector inside the heater. Make sure  
the flanged side of the flue opening is up.  
4. Turn the stack (drafthood) upside  
down and set it down bottom side up.  
5. Turn the jacket top panel (removed in step 1)  
upside down and place it through the stack.  
6. Attach the three (3) mounting brackets to the  
stack using the screws provided and the holes  
that are pre-drilled in the stack. Make sure the  
bracketsarepositionedwiththeflangenearthe  
top side of the stack (see illustration 8246.5).  
Caution must be taken not to over tighten and  
strip the screw threads.  
7. Turn the assembled stack and jacket top, right side  
up. The jacket top will be trapped between the  
brackets and the top of the stack. Place the stack  
over the inner adapter panel flanged hole and  
lower the louvered jacket top panel back into its  
original position. Reinstall the four (4) green #10  
flathead screws removed in step 1 above.  
Fig. # 8167  
MODELS 962-1826  
Locate and assemble as shown below. Secure with  
screws supplied in envelope in carton.  
Fig. # 8165  
MODELS 2100-4001  
These models have built-in drafthoods. For proper  
operation, the drafthood outlet must be connected to  
the venting system.  
13  
VENT PIPING  
WARNING: Indoor heaters require a drafthood that  
The weight of the vent stack or chimney must not rest  
must be connected to a vent pipe and properly vented on heater drafthood. Support must be provided in  
to the outside. Failure to follow this procedure can compliance with applicable codes. The heater top and  
cause fire or fatal carbon monoxide poisoning.  
drafthood must be readily removable for maintenance  
and inspection. Vent pipe should be adequately sup-  
Vent piping of the same size as the drafthood outlet ported to maintain proper clearances from combustible  
is recommended, however, when the total vent height construction Type "B" double wall or equivalent vent  
is at least ten (10) feet (drafthood relief opening to vent pipe is recommended. However single wall metal vent  
terminal), the vent pipe size may be reduced as speci- pipe may be used as specified in the latest edition of the  
fiedintheNationalFuelGasCode,ANSIZ223.1. Avoid  
longhorizontalrunsofventpipeandtoomanyelbows. If  
installationrequireshorizontalnon-verticalruns,thevent  
pipe must have a minimum of  
National Flue Gas Code ANSI Z223.1.  
Manifolds that connect more than one heater to a  
common chimney must be sized to handle the com-  
bined load. Consult available guides for proper sizing  
1/4 inch per foot rise and should be supported at not of the manifold and the chimney. At no time should the  
more than five foot intervals. Plumber's tape, criss- area be less than the area of the largest outlet.  
crossed, will serve to space both horizontal and vertical  
piping. Gas vents supported only by the flashing and  
extending above the roof more than five feet should be  
securely guyed or braced to withstand snow and wind  
loads. We recommend use of an insulated vent pipe  
spacer through the roofs and walls.  
For protection against rain or blockage by snow, the  
vent pipe must terminate with a vent cap which com-  
plies with the local codes or, in the absence of such  
codes, to the latest edition of the National Fuel Gas  
Code, ANSI Z223.1.  
The discharge opening must be a minimum of two  
Fig. #7043.1  
feet vertically from the roof surface and at least 2 feet  
higher than any part of the building or equipment within  
At the time of removal of an existing heater, the follow-  
tenfeet. Theventstackshallbeatleast5feetinvertical  
ing steps shall be followed with each appliance remain-  
height above the drafthood outlet. The vent cap loca-  
ing connected to the common venting system placed in  
tion shall have a minimum clearance of 4 feet horizon-  
operation, while the other appliances remaining con-  
tally from, and in no case above or below, unless a 4-  
nected to the common venting system are not in  
foot horizontal distance is maintained, from electric  
operation.  
meters, gas meters regulators and relief equipment.  
.
(a) Seal any unused openings in the common venting  
system.  
10' OR LESS  
VENT CAP  
(b) Visually inspect the venting system for proper size  
2' MIN  
and horizontal pitch and make sure there is no  
blockage or restriction, leakage, corrosion or  
2' MIN  
other deficiency which could cause an unsafe  
condition.  
5' MIN  
VENT PIPE  
(c) Insofar as is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the com-  
mon venting system are located and other spaces  
DRAFT HOOD  
of the building. Turn on clothes dryers and any  
appliance not connected to the common venting  
system. Turn on any exhaust fans, such as range  
hoods and bathroom exhausts, so they will oper-  
HEATER  
ate at maximum speed. Do not operate a summer  
exhaust fan. Close fireplace dampers.  
14  
(d) Place in operation the appliance being inspected. (g) Any improper operation of the common venting  
Follow the lighting instructions. Adjust thermostat  
so appliance will operate continuously.  
system should be corrected so that the installation  
conforms with the latest edition of the National Fuel  
Gas Code, ANSI Z223.1. When re-sizing any  
portion of the common venting system, the com-  
mon venting system should be re-sized to  
approach the minimum size as determined using  
the appropriate tables in Part 11 of the National  
Fuel Gas Code, ANSI Z223.1.  
(e) Test for spillage at the drafthood relief opening  
after 5 minutes of main burner operation. Use the  
flame of a match or candle, or smoke from a  
cigarette, cigar or pipe.  
(f) After it has been determined that each appliance  
remaining connected to the common venting sys- For special venting applications that require reduced  
tem is venting properly, return doors, windows, vent sizes and through-the-wall venting, the Type D  
exhaust fans, fireplace dampers and any other gas Induced Draft Assembly can be used. Consult the  
burning appliance to their previous conditions of  
use.  
factory or your local Raypak representative.  
VENT DAMPER INSTALLATION  
MODELS133THROUGH180  
(WHERE REQUIRED)  
LOCATION  
The vent damper must be located in the vent so  
that it serves only the appliance for which it is intended.  
If improperly installed, a hazardous condition, such  
as an explosion or carbon monoxide poisoning, could  
result. Make certain that it is mounted in an accessible  
location at least 6 in. from any combustible material or  
the heat exchanger and that the position indicator is in  
a visible location.  
The vent damper must be installed after the appli-  
ance drafthood, as close to the drafthood as practi-  
cable, and without modification of the drafthood.  
Fig. # 8182.0  
WARNING: Do not use thermally actuated vent dampers on modulating heater. To do so, may result in  
asphyxiation. Use only a mechanically actuated vent damper device that is electrically interlocked with the  
modulating heater operation.  
MOUNTING  
On vertical vents, the vent damper may be mounted with the actuator in any position. On horizontal vents,  
do not mount the actuator either directly above or directly below the vent pipe; mount the vent damper actuator  
to the side of the vent.  
The vent damper is set up for a continuous pilot system. If the vent damper is installed on an Intermittent  
Pilot or Direct Spark Ignition equipped system, the energy savings of the vent damper can be improved by  
plugging the hole in the vent damper blade using the knockout plug, Part No. 105612R, provided in the parts  
envelope.  
DO NOT plug the hole if installing the vent damper on a continuous pilot system as this will create a hazardous  
condition.  
15  
HORIZONTAL INSTALLATION  
D808  
FLOW >  
NO  
NO  
N.O.  
N.C.  
End  
Switch  
1K2  
YES  
YES  
C.  
1K1  
HEATER  
TO
D808  
TO CHIMNEY  
Motor  
R
1K3  
VERTICAL  
INSTALLATION  
1R  
INSTALL VENT  
DAMPER WITH  
ACTUATOR TO  
SIDES OF VENT  
ONLY. DO NOT  
4
1
2
3
5
TO CHIMNEY  
D808  
Yellow Blue  
Black  
Orange  
Red  
Optional Limit  
Location  
Limit  
Thermostat or  
Controller  
MOUNT ABOVE OR  
BELOW VENT.  
L1  
(Hot)  
Dual Valve  
L2  
Combination Gas  
Control or  
ACTUATOR MAY BE  
INSTALLED IN ANY  
POSITION ON  
1
Transformer  
Ignition System  
HEATER  
TO
1
Powersupplyprovidedisconnect meansanoverloadprotection as required.  
VERTICAL PIPE.  
Fig. # 8615.0  
Fig. # 8183.0  
INSTALLING THE VENT DAMPER  
VENT DAMPER GENERAL WIRING DIAGRAM  
INSTALL THE VENT DAMPER TO SERVICE ONLY THE SINGLE APPLIANCE FOR WHICH IT IS INTENDED.  
IF IMPROPERLY INSTALLED, A HAZARDOUS CONDITION, SUCH AS AN EXPLOSION OR CARBON  
MONOXIDE POISONING, COULD RESULT.  
2. Turn the thermostat or controller up to call for heat  
and check that the vent damper indicator points to  
the open position, Fig. 4.  
3. Turn the thermostat or controller down again and  
check that the vent damper position indicator  
returns to the closed position.  
VENT DAMPER  
For safe, efficient operation, the vent damper and  
all flue product carrying areas of the appliance must be  
checked annually, with particular attention given to  
deterioration from corrosion or other sources. Check  
vent damper operation as follows:  
THE VENT DAMPER MUST BE INSPECTED AT  
LEAST ONCE  
A
YEAR BY  
A
TRAINED,  
EXPERIENCED SERVICE TECHNICIAN. THE  
NAME OF THE PERSON WHO ORIGINALLY  
INSTALLED YOUR VENT DAMPER IS SHOWN ON  
THE INSTALLATION LABEL. DAMPER MUST BE IN  
THE OPEN POSITION WHEN HEATER MAIN  
BURNERS ARE OPERATING.  
1. When the heater is off, check that the vent  
damper position indicator points to the closed  
position, Fig. 4.  
Damper  
Position  
Indicator  
Damper  
Position  
Indicator  
Fig. # 8181.0  
DAMPER OPEN  
DAMPER CLOSED  
FIG. 4 - VENT DAMPER POSITON INDICATOR SHOWING OPEN & CLOSED POSITIONS.  
16  
PLUMBING  
GENERAL  
CAUTION: The heater and its manual shut-off valve  
must be disconnected from the gas supply during any  
pressure testing of that system at test pressures in  
excess of 1/2 PSI. Dissipate test pressure in the gas  
supply line before reconnecting the heater and its  
manual shut-off valve to gas supply line. FAILURE TO  
FOLLOW THIS PROCEDURE MAY DAMAGE THE  
GAS VALVE. OVER-PRESSURED GAS VALVES  
ARE NOT COVERED BY WARRANTY. The heater  
and its gas connections shall be leak tested before  
placing the appliance in operation. Use soapy water  
for leak test. DO NOT use open flame.  
Heater should be located so that any water leaks  
will not cause damage to any adjacent areas or struc-  
tures.  
GAS SUPPLY CONNECTIONS  
Gas piping must have a sediment trap ahead of the  
heater gas controls, and a manual shut-off valve  
located outside the heater jacket. All gas piping should  
be tested after installation in accordance with local  
codes.  
NOTE: Do notuseTeflontapeongaslinepipethread.  
A flexible sealant is recommended.  
Fig. # 8090.1  
17  
A minimum of 7" WC and a maximum of 10.5" WC upstream pressure under load, and no load conditions must  
be provided for natural gas or a minimum of 11" WC and a maximum of 13" for propane.  
* Models 181, 261, 331, and 401 are Low NOx units and are not available in propane.  
GAS PRESSURE REGULATOR  
The gas pressure regulator located in the gas valve is preset nominally at 4" WC for natural gas, and 11" WC  
for propane. Between the gas valve and the burners is a 1/8" pipe plug. The pressure at this point, taken with  
a manometer, should be about 3.7" WC natural gas and 10.5" WC propane. Models 181, 261, 331, and 401  
should be 3.9 wc natural gas. If an adjustment is needed, turn adjustment screw clockwise to increase pressure,  
or counter-clockwise to decrease pressure.  
VENTING OF DIAPHRAGM GAS COMPONENTS  
Gas train components that have diaphragms in their construction are supplied with a bleed line connection  
that must be connected to the outside atmosphere as required by the National Fuel Gas Code. Under NO  
circumstances shall bleed lines terminate in the gas utilization equipment flue or exhaust system.  
Fig # 8185.2  
18  
FLOW RATES  
19  
PIPING - DOMESTIC HOT WATER SUPPLY HEATERS  
GENERAL SPECIFICATIONS  
UNI-TEMP 80 HOT WATER SUPPLY SYSTEMS  
T = Temperature Rise, Degree F@GPM FLOW  
GPM = Gallons per Minute Flow  
P = Pressure Drop, Foot thru Heat Exchanger  
MPS = Minimum Pipe Size, NPT  
SHL = System Head Loss  
The table above provides data for selecting in-line pumps for use in a Uni-Temp 80 system for a single heater  
and tank according to the following:  
1. Flow rates are based on water hardness as measured in grains per gallon.  
Soft: 0-4 grains per gallon.  
Medium: 5-15 grains per gallon.  
Hard: 16 and over grains per gallon.  
2. Maximum Flow Rates:  
133  
22 GPM  
45 GPM  
90 GPM  
200 GPM  
181-401  
514-1826  
2100-4001  
3. Pressure drop values ( P and SHL) and minimum pipe sizes are for two-pass heaters.  
4. Sizing based on heater and tank being placed 5 feet apart. The equivalent length of pipe  
valves and fittings in the system is as follows:  
1-1/2" NPT = 70 Ft (181-401)  
2" NPT = 75 Ft (514-824)  
2-1/2" NPT = 80 Ft (926-1826)  
3" NPT = 85 Ft (2100-4001)  
Additional pipe fittings will increase the system head loss.  
5. Select a pump based on the water hardness, flow, and system head loss.  
6. If heater is more than two stories above the tank, consult the factory.  
NOTE:  
GPM flow rates are limited by maximum acceptable velocity through heat exchanger tubes. Heater models 514  
through 1826 may be provided with an integral rear-mounted pump. This must be specified at time of order. The  
integral pump will provide sufficient flow to meet the conditions listed in the table.  
20  
PIPING DIAGRAMS  
TYPE WH - UNITEMP 80 SYSTEM  
21  
TYPE NH - INSTANTANEOUS  
Type NH heaters provide instant hot water without a tank and are used in applications where scaling is  
prevalent and where hot water demand is fairly constant throughout the day, such as apartments, hotels, motels  
and industrial applications. The Type NH heater should not be used on apartments and hotels with fewer than  
30 dwelling units, nor should the heater be sized smaller than a 514.  
Use a minimum 20' of 3" pipe on outlet.  
22  
TYPE NH - DUAL MODELS 514-1826  
1. Estimate total length of supply and return loop.  
Refer to table.  
3. First fixture on supply line must be a minimum  
of 20 feet from the heater.  
2. If multiple loops are used:  
4. Supply line size must be 2" minimum. If not  
possible, add a tank between heater and first  
fixture.  
(A) Use multiple pumps and size return pipes  
according to table; or  
(B) Use one larger recirculating pump with  
balancing valves on each return line.  
MINIMUM INPUT ADJUSTMENT  
Model Types NH and WH have minimum input ratings as specified on their individual rating plates. Minimum  
input controllers have been pre-set at the factory. Consult with factory representatives if a minimum input  
problem should occur.  
23  
CONTROLS - GENERAL  
RELIEF VALVE  
ELECTRONIC IGNITION  
A new combination temperature and pressure  
The intermittent ignition device conserves energy  
(T&P) relief valve, complying with the Standard for by automatically extinguishing the pilot when desired  
Relief Valves and Automatic Gas Shut-Off Devices for temperature is reached. When additional heat is  
Hot Water Supply Systems, ANSI Z21.22, must be needed, the pilot re-ignites electrically, eliminating the  
installed in the opening provided on top of the storage fuel costs of maintaining a constant pilot. To assure  
tank at the time of installation. No valve is to be placed safe operation, the gas valve cannot open until the pilot  
between the relief valve and the storage tank.  
The pressure rating of the relief valve must not  
exceed the 160 maximum working pressure indicated  
onthewaterheaterratingplate. TheBTUHratingofthe  
relief valve must not be less than the BTUH input of the  
heater.  
relights and is confirmed.  
Connect the outlet of the relief valve to a suitable  
open drain. The discharge line must pitch downward  
from the valve to allow complete draining (by gravity) of  
the relief valve and discharge line. The discharge line  
should be no smaller than the outlet of the valve. The  
end of the discharge line should not be threaded or  
concealed, and should be protected from freezing. No  
valve of any type, restriction or reducer coupling,  
should be installed in the discharge line. Local codes  
shall govern installation of the relief valve.  
OPERATING CONTROLS  
On models 514-1826, models with mechanical  
modulating controls have one or more Robertshaw  
Unitrol 7000 Series hydraulic snap on thermostatic  
combination gas valves. These valves have the pres-  
sure regulator and 24-volt operator built-in. The hy-  
draulic actuator will throttle the heater input to adjust the  
firing rate and meet the required load. This, in effect,  
prevents costly fuel consumption, as compared to an  
on-off cycling heater. The valve has a remote capillary  
bulb immersed in a well, at the header outlet, to main-  
tain a constant outlet water temperature. When mul-  
tiple valves are furnished, they can be staged to give  
greater flexibility of control. Standard factory setting is  
at position 5. Consult the dial setting tag attached to the  
control for your desired temperature. See chart below.  
ECONOMASTER CONTROL  
The Economaster II is an electronic device that  
allows the operator to set the desired time for the pump  
to run after the heater shuts off. The time is factory-set  
at 7 minutes and it can be re-adjusted in the field  
anywhere from 3 to 10 minutes.  
In a conventional system, when the aquastat is  
satisfied, the main gas valve closes, but the pump  
continues operating. With the energy-conserving  
Economaster II, the heater pump is programmed to  
continue running for an optimum period of time in order  
to absorb the residual heat from the combustion cham-  
ber and use it in the system. The pump then shuts off  
until the next call for heat is received from the aquastat.  
NOTE: Pump will come on when power is first applied  
to the heater.  
Fig# 9331  
Fig # 9330.1  
24  
Fig # 9332  
MECHANICAL MODULATING VALVE LOCATION  
MODELS 0724-1336  
MOTORIZED GAS VALVE LOCATION  
MODEL 3001  
Fig # 9333.1  
LIMIT CONTROLS  
HIGH LIMIT  
whenever the pilot flame is interrupted. Pilot flame is  
automatically lit when the device is powered. Unit  
performs its own safety check and opens the main  
valve only after the pilot is proven to be lit.  
The heater is equipped with a manual reset High  
Limit. Push the reset button and set the limit(s) to  
30°F-4Fabove desiredoperatingtemperature. Maxi-  
mum setting is 210°F.  
LOW WATER CUT-OFF (OPTIONAL)  
FLOW SWITCH  
The low water cut-off automatically shuts down  
burner whenever water level drops below probe. 90-  
second time delay prevents premature lockout due to  
temporary conditions such as power failure or air  
pockets. Flush float type devices at beginning of each  
heating season.  
This dual-purpose control shuts off the heater in  
case of pump failure or low water condition and is  
strongly recommended. It is mounted and wired in  
series to the main gas valve.  
NOTE: The flow switch is a safety device and not a  
control. Do not operate the heater with flows less than  
the minimums stated in this manual.  
HIGH AND LOW GAS PRESSURE  
SWITCHES (OPTIONAL)  
100% PILOT SAFETY  
These switches sense either high or low gas pres-  
sures and automatically shut down burners if abnormal  
pressures exist.  
Models 514-4001 employ electronic devices which  
close the main gas valve within 8/10 of a second  
25  
COMPONENT IDENTIFICATION  
Fig# 8643  
Fig# 9314  
MANUAL RESET HIGH LIMIT  
THERMOSTAT CONTROL  
Fig# 9312  
Fig# 8929.1  
HIGH and/or LOW  
IGNITION CONTROL MODULE  
GAS PRESSURE SWITCH  
Fig# 9316  
Fig# 8995  
LOW WATER CUT-OFF  
MECHANICAL MODULATING VALVE  
Fig# 9317  
Fig# 8925  
FLOW SWITCH  
FLOW SWITCH PADDLE CUTTING GUIDE  
26  
ELECTRICAL CONNECTIONS  
control connection. 24 Volts are supplied to this con-  
nection through the heater transformer. DO NOT  
attach line voltage to the "TH" leads on models 514-  
1826. Before starting heater check to ensure proper  
voltage to heater and pump.  
CAUTION: Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause improper  
and dangerous operation. Verify proper operation after  
servicing.  
Heater must be electrically grounded in accor-  
dance with National Electrical Code ANSI/NFPA No  
70.  
DANGER - SHOCK HAZARD  
Make sure electrical power to the heater is discon-  
nected to avoid potential serious injury or damage to  
components.  
NOTES:  
1. Field install ground wire to inside of junction box.  
2. If any of the original wire supplied with the heater  
must be replaced, it must be replaced with 105°C  
wire or its equivalent.  
The heater is normally wired for 120 Volts. The  
voltage is indicated on the tie-in leads. Consult the  
wiring diagram shipped with the heater in the instruc-  
tion packet. The "TH" leads are for the remote tank  
Fig # 9138.2  
Fig # 9138.1  
SINGLE-STAGE TANKSTAT  
2- STAGE TANKSTAT  
(2 ON/OFF UNITS)  
27  
LOCATION OF CONTROLS  
400  
WH1, WH2, WH3  
181 (LOW NOx)  
WH1  
Fig # 9360  
28  
LOCATION OF CONTROLS  
Fig. #9334  
29  
LOCATION OF CONTROLS  
Fig # 9335  
START-UP PROCEDURES  
INITIAL START-UP - PUMP AND MOTOR  
BEFORE START-UP  
Safe lighting and other performance criteria were  
Many pumps are now direct-drive. They have no  
met with the gas manifold and control assembly pro- coupler or bearing assembly. These pumps do not  
vided on the heater when the heater underwent tests require lubrication. Others require SAE-30 non-deter-  
specifiedinthelatesteditionoftheANSI-Z21.10.3/CSA  
4.3Standard.  
gent oil to lubricate both the motor and the bearing  
assembly. Check pump motor for type before adding  
oil.  
Clean dust and lint from pump and motor. Check  
pump coupler and tighten if necessary.  
Flush system before putting into operation to en-  
sure that foreign material does not damage pump  
seals.  
GENERAL  
Before lighting up a new installation, water should  
be flowing through the heater.  
Water pressure regulator should be set to mini-  
mum 25 PSI.  
CAUTION:  
CAUTION:  
Propane is heavier than air and sinks to the  
ground. Exercise extreme care in lighting heater in  
confined areas.  
A. Pump must be off to check oil in bearing assembly.  
B. Do not run pump without water in system.  
30  
General Safety Precautions  
To meet commercial water use needs, the thermostat The following chart details the relationship of water  
on this water heater is adjustable up to 190°F. How- temperature and time with regard to scald injury and  
ever, water temperatures over 125°F can cause instant  
severeburnsordeathfromscalds. Thisisthepreferred  
temperaturesettingwhensupplyinggeneralpurposehot  
water.  
may be used as a guide in determining the safest water  
temperature for your applications.  
Temperature  
120°F  
Time to Produce Serious Burn  
More than 5 minutes  
1-1/2 to 2 minutes  
Safety and energy conservation are factors to be  
considered when setting the water temperature on the  
thermostat. The most energy-efficient operation will  
result when the temperature setting is the lowest that  
satisfies the needs consistent with the application.  
125°F  
130°F  
About 30 seconds  
135°F  
About 10 Seconds  
140°F  
Less than 5 seconds  
Less than 3 seconds  
About 1-1/2 seconds  
About 1 second  
145°F  
150°F  
155°F  
Table courtesy of Shriners Burn Institute  
TIME/TEMPERATURE RELATIONSHIPS IN  
SCALDS  
The temperature of the water in the heater can be  
regulated by setting the temperature dial on the front of  
the thermostat. To comply with safety regulations, the  
thermostat was set at its lowest setting before the  
heater was shipped from the factory. The illustration  
below shows how to adjust the water temperature  
using the thermostat.  
To adjust the water tem-  
perature, insert a small  
straight screwdriver into  
slotted screw in hole in front  
of thermostat and turn  
wheel to desired setting.  
Thermostat is adjustable  
up to 190°F.  
Water temperature over 125°F can  
causeinstantsevereburnsordeath  
from scalds.  
Children, disabled, and elderly are  
at highest risk of being scalded.  
CAUTION!! - Hotter water  
increases the risk of  
SCALDING!  
See instruction manual before set-  
ting temperature at water heater.  
There is a hot water scald potential if the thermostat is  
set too high.  
Feel water before bathing or show-  
ering.  
NOTE: When this heater is supplying general purpose  
hot water requirements for use by individuals, a ther-  
mostatically controlled mixing valve for reducing point  
of use water temperature is recommended to reduce  
the risk of scald injury. Contact a licensed plumber or  
the local plumbing authority for further information.  
Temperature limiting valves are  
available, see manual.  
Maximum water temperatures occur just after burner  
has shut-off. To determine the water temperature  
being delivered, turn on the hot water only, place a  
thermometer in the stream, and read the thermom-  
eter.  
31  
LIGHTING INSTRUCTIONS FOR HEATERS WITH ELECTRONIC IGNITION (IID)  
FOR MODELS WITH MANUAL GAS VALVES  
FOR YOUR SAFETY READ BEFORE OPERATING  
WARNING:If you do not follow these instructions exactly, a fire or explosion may result causing  
property damage, personal injury or loss of life.  
A. This appliance is equipped with an ignition device  
which automatically lights the pilot. Do not try to light the  
pilot by hand.  
*
If you cannot reach your gas supplier, call the fire de-  
partment.  
C. Use only your hand to push in or turn the gas control  
knob. Never use tools. If the knob will not push in or turn  
by hand, do not try to repair it. Call a qualified service  
technician. Force or attempted repair may result in a fire  
or explosion.  
B. BEFORE OPERATING smell all around the appliance  
area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
*
*
*
*
Do not try to light any appliance.  
Do not touch any electric switch.  
Do not use any phone in your building.  
Immediately call your gas supplier from your  
neighbor’s phone. Follow the gas supplier’s instruc-  
tions.  
D. Do not use this appliance if any part has been under  
water. Immediately call a qualified service technician to  
inspect the appliance and to replace any part of the  
control system and any gas control which has been  
under water.  
OPERATING INSTRUCTIONS  
1. STOP! Read the safety information above.  
2. Set the thermostat on the lowest setting.  
3. Turn off all electric power to the appliance.  
4. This appliance is equipped with an ignition device which  
automatically lights the pilot. Do not try to light the pilot  
by hand.  
For Honeywell Gas Valve: Turn gas control knob counter-  
clockwise from “OFF” until it stops. Push in gas control  
knob and continue rotating counter-clockwise  
position. Make sure knob rests against stop.  
to “ON”  
5. Remove heater door panel.  
6. For Robertshaw gas valve: Turn gas control knob  
HONEYWELL  
clockwise  
For Honeywell Gas Valve: Turn gas control knob clock-  
wise to “OFF". Make sure knob rests against stop.  
to “OFF”.  
GAS CONTROL  
KNOB SHOWN  
IN "ON" POSITION  
For Honeywell Gas Valve: (Model 400 only)  
Push in gas control knob slightly and turn clockwise  
GAS INLET  
to “OFF”. Knob cannot be turned to  
“OFF”  
unless knob is pushed in slightly. Do not force.  
7. Wait five (5) minutes to clear out any gas. Then smell for  
gas, including near the floor. If you smell gas, STOP!  
Follow “B” in the safety information previously stated. If  
you do not smell gas, go to the next step.  
Fig. # 8082  
8. For Robertshaw Gas Valve: Turn gas control knob  
counter-clockwise  
to “ON”.  
9.  
Replace heater door panel.  
10. Turn on all electric power to the appliance.  
11. Set thermostat to desired setting.  
12. If the appliance will not operate, follow the instructions  
“To Turn Off Gas To Appliance” and call your service  
technician or gas supplier.  
ROBERT SHAW  
GAS CONTROL  
KNOB SHOWN  
IN "ON" POSITION  
GAS INLET  
Fig. # 8080  
TO TURN OFF GAS TO APPLIANCE  
1. Set the thermostat to the lowest setting.  
2. Turn off all the electric power to the appliance if service  
is to be performed.  
ForHoneywellGasValve: Turngascontrolknobclock-  
wise  
stop.  
to “OFF”. Make sure knob rests against  
3. Remove door panel.  
4. For Robertshaw Gas Valve: Turn gas control knob 5. Replace heater door panel.  
clockwise to “OFF”.  
32  
FOR MODELS WITH AUTOMATIC GAS VALVES  
PILOT SHUT-OFF  
VALVE CONTROL  
SHOWN IN "ON"  
POSITION  
1. Close all gas valves. Turn off electric power  
supply. Wait five (5) minutes.  
2. Open manual pilot valve. Turn on electric  
power. Pilot is automatically lighted.  
3. Open main gas valve.  
TO PILOT  
4. Set temperature controls to desired temperature.  
MAIN GAS  
SHUT-OFF  
VALVE  
SHOWN IN  
THE "ON"  
POSITION  
TO SHUT DOWN  
Close all manual gas valves. Turn off electric  
power.  
GAS INLET  
Fig# 8220  
AFTER START-UP  
INTERMITTENT PILOT SYSTEM CHECKOUT PROCEDURE (S8600)  
1. Turn on power to the ignition systems and turn  
gas supply off.  
3. Turn on gas supply.  
4. Set thermostat or controller above room temp-  
erature to call for heat.  
5. Systems should start as follows:  
a. Spark will turn on and pilot gas valve will  
open at once. Pilot burner should ignite  
after gas reaches the pilot burner.  
b. Spark ignition should cut-off when pilot  
flame is established.  
2. Check ignition module as follows:  
a. Set the thermostat or controller above  
room temperature to call for heat.  
b. Watch for continuous spark at the pilot  
burner.  
c. Time the spark operation. Time must be  
within the lockout timing period (15 or 90  
seconds).  
d. Turn thermostat down to end call for heat  
and wait 60 seconds on lockout models  
before beginning step 3.  
c. Main gas valve should open and main  
burner should ignite after gas reaches the  
burner port.  
INSPECTION PROCEDURES  
BURNERS  
CONTROLS  
Clean main burners and air louvers free of dust, lint  
Check all controls to see that they are operational.  
and debris. Keep heater area clear and free from To check electronic safety (IID models), turn off main  
combustibles and flammable liquids. Do not obstruct burner. Observe pilot burner when shutting off pilot  
the flow of combustion and ventilation air. Make visual gas. Ignition spark should go on. Main gas valve will  
check of burner and pilot flame. Yellow flame indicates also drop out.  
clogging of air openings. Lifting or blowing flame indi-  
High Limit Switch - to check high limit switch, turn  
cates excessively high gas pressure. Low flame indi- dial setting down to a point slightly below the tempera-  
cates low gas pressure.  
ture of the water leaving the heater. The reset button  
should snap out and the burner should shut-off. Reset  
dial to 30°F to 40°F above desired operating tempera-  
ture and push reset button. Burner should light.  
Fig# 8144  
TYPICAL MAIN BURNER FLAME (Atmospheric models)  
NOTE: Modulating burner flame varies in height from  
approximately 1/4" at low fire to approximately 4" at  
high fire.  
33  
INSPECTION PROCEDURES  
7. Check flow switch paddle.  
8. Clean room air intake openings to assure  
adequate flow of combustion and ventilation air.  
Inspect on the first and third month after initial start-  
up and then on an annual basis. If problems are found,  
refer to the Troubleshooting sections of this manual for  
additional directions.  
CAUTION: Combustion air must not be contaminated  
by corrosive chemical fumes which can damage the  
heater and void the warranty.  
1. Remove top of heater and inspect heat exchanger  
for soot and examine venting system.  
2. Remove rear header and inspect for scale depos-  
its.  
9. Keep heater area clear and free from combustible  
materials, gasoline, and other flammable vapors  
and liquids.  
*3. Inspect pilot and main burner flame and firing rate.  
*4. Inspect and operate all controls and gas valve.  
*5. Visually inspect system for water leaks.  
*6. a. Oil pump motor and bearing assembly, if oil  
cups are provided.  
*Should be checked monthly.  
(Takes approximately 15 minutes).  
b. Disconnect pump from header and check  
condition of pump impeller. Check condition of  
bearing by attempting to move impeller from  
side to side. Replace any parts showing wear.  
c. Check pump coupler for wear and vibration.  
Fig# 9336  
PILOT BURNER FLAME-IID  
(atmospheric units)  
34  
ADDENDA: LOW NOx HEATERS Models 181 to 401  
The Raytherm Low NOx Heater is offered with WH1-  
On-Off firing (standard) or 2-stage firing (optional).  
3.Turn on gas supply.  
4.Set controller to call for heat.  
The heaters are certified and tested under the latest  
edition of the ANSI Z21.10.3/CSA 4.3 standard for hot  
waterheaters.  
5.System should start as follows:  
a. Spark will turn on and pilot gas valve will open and  
the blower will begin running.  
The heater should be installed to meet all local codes,  
the National Fuel Gas Code ANSI Z223.1, and the  
National Electrical Code, ANSI/NFPA 70-latest edition.  
b. Heater will operate until call for heat is satisfied.  
BURNER ADJUSTMENT  
This burner assembly does not require any primary air  
adjustments.  
VISUAL INSPECTION  
Flame can be observed through the slot opening above  
the plenum. Flame color is blue and evenly spread on  
the top surface of the burner. A visual inspection  
should be made monthly of the burners. In case flame  
lifting is observed on the burner, check gas pressure on  
manifold and static pressure in plenum. Gas pressure  
in manifold should be 3.9" WC and static pressure in  
plenum should be greater than 0.5" WC  
Fig # 9361  
ELECTRICAL  
OPERATION  
Be sure that electrical service to the heater has proper  
overload fuse or circuit breaker protection, and wire  
size and connections comply with all applicable codes.  
On call for heat, the ignition system, consisting of an  
electronic spark module, gas pilot system is energized.  
Providing pilot is proven, blower will start running, the  
main gas valve will open and the heater will operate.  
When the operating control is satisfied, the heater will  
shut down.  
HIGH GAS PRESSURE SWITCH  
Pressure switch senses high pressure and automati-  
cally shuts down burner if abnormal pressure exists.  
START-UP PROCEDURES  
(S8610B Ignition Module)  
PRESSURE  
SWITCH  
1.Turn on power to the heater with gas supply off.  
2.Check ignition module as follows:  
GAS MANIFOLD  
a. Set the thermostat or controller to call for heat.  
b. Watch for continuous spark at the pilot burner.  
c. Check the ignition spark operation. Time must be  
within the lockout timing period (15 or 90 seconds).  
d. Turn control down to end call for heat and wait 60  
seconds on lockout models before beginning step  
3.  
Fig. #8236.0  
35  
ADDENDA: LOW NOx HEATERS Models 181 to 401 (CONTINUED)  
sembly from the burner tray assembly.  
4. Use a long ½” socket wrench to remove orifices  
from the gas manifold.  
5. Remove burners by raising the bracket on the back  
end of the burners up and out of their slots.  
6. Reverse above procedure to re-install.  
Fig # 9362  
LOW NOx BURNER TRAY ASSEMBLY  
Fig # 9363  
BURNER TRAY REMOVAL  
IID PILOT  
1. Shut-off main electrical power switch to heater.  
2. Shut-off gas upstream of heater.  
3. Remove front door.  
PILOT REMOVAL  
4. Disconnect gas line from gas valve.  
5. Remove (2) screws that mount burner tray to unit,  
and (4) screws that secure gas valve to jacket.  
6. Disconnect wires that terminate at gas valve.  
7. Unscrew (4) screws that secure the control box.  
8. Disconnect pilot wire from the ignition module.  
9. Disconnect wire harness from the combustion  
blower.  
1. Disconnect pilot tubing from gas valve.  
2. Remove (4) screws from control box. Open the  
control box.  
3. Remove the pilot wire from the ignition wire.  
4. Remove (2) screws that mount the pilot bracket  
to the air manifold assembly.  
5. Pull the pilot bracket downwards and outwards.  
6. Reverse above procedure to re-install.  
10. Carefully slide out the burner tray assembly.  
11. Reverse above procedure to reinstall.  
COMBUSTION FAN REMOVAL  
GAS VALVE REMOVAL  
1. Remove burner tray. (See Burner Tray  
Removal procedure above.)  
2. Remove (4) screws the mount the combustion  
blower to the manifold assembly.  
1. Shut-off main electrical power switch to heater.  
2. Shut-off gas supply to the heater.  
3. Remove front door.  
4. Disconnect gas line from gas valve.  
5. Disconnect wires, pilot tubing and bleed line,  
if required.  
3. Reverse above procedure to re-install.  
6. Remove (2) screws that secure gas valve to  
jacket.  
7. Turn vertical gas pipe from manifold slightly  
and unscrew gas valve.  
8. Reverse above procedure to re-install.  
MAIN BURNER AND ORIFICE REMOVAL  
1. Remove burner tray. (See Burner Tray Removal  
procedure above.)  
2. Remove (8) screws from the hold-down brackets.  
3. Remove (8) screws from the left and right sides of  
the manifold assembly. Detach the manifold as-  
36  
WARNING  
HIGH VOLTAGE  
For qualified Technicians ONLY  
TROUBLESHOOTING - ELECTRICAL  
(ELECTRONIC IGNITION IID)  
NOTE: Some heaters may be equipped with  
an ignition module that shuts off pilot gas if  
pilot fails to light. To reset, interrupt power  
to heater.  
Intermittent Pilot System  
HONEYWELL S8600  
START  
TURN GAS SUPPLY OFF.  
TURN THERMOSTAT  
(CONTROLLER) TO CALL  
FOR HEAT  
NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout  
procedure.  
POWER TO MODULE  
(24 V NOMINAL)?  
YES  
Check line voltage power, low voltage transformer, limit controller, thermostat  
(controller) and wiring.  
NO  
NO  
Pull ignition lead and check spark at module.  
SPARK ACROSS  
IGNITER/SENSOR GAP?  
YES  
If spark is okay:  
• Check ignition cable, ground wiring, ceramic insulator and gap, and correct.  
• Check boot of the ignition cable for signs of melting or buckling. Take protective  
action to shield cable and boot from excessive temperatures.  
If not, replace module.  
TURN GAS SUPPLY ON  
PILOT BURNER LIGHTS?  
YES  
• Check that all manual gas valves are open, supply tubing and pressures are good,  
and pilot burner orifice is not blocked.  
• Check electrical connections between module and pilot operator on gas control.  
• Check for 24 Vac across PV-MV/PV terminals on module. If voltage is  
okay, replace gas control; if not, replace module.  
NO  
NO  
NOTE: If S8600H goes into lockout, reset system. Lockout is used on propane  
models.  
• Check continuity of ignition cable and ground wire.  
• Clean flame rod.  
• Check electrical connections between flame rod and module.  
• Check for cracked ceramic flame rod insulator.  
• Check that pilot flame covers flame rod and is steady and blue.  
• Adjust pilot flame.  
SPARK STOPS WHEN  
PILOT IS LIT?  
YES  
• If problem persists, replace module.  
• Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.  
• Check electrical connections between module and gas control. If okay, replace  
gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.  
NO  
NO  
MAIN BURNER LIGHTS?  
YES  
NOTE: IF S8600H goes into lockout, reset system.  
• Check continuity of ignition cable and ground wire.  
SYSTEM RUNS UNTIL  
CALL FOR HEAT ENDS?  
YES  
NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though  
operation is normal at the time of checkout.  
• Check that pilot flame covers flame rod and is steady and blue.  
• If checks are okay, replace module.  
CALL FOR HEAT ENDS  
SYSTEM SHUTS OFF?  
YES  
• Check for proper thermostat (controller) operation.  
• Remove MILLIVOLT lead at module; if valve closes, recheck temperature  
controller and wiring; if not, replace gas valve.  
NO  
TROUBLESHOOTING ENDS  
37  
WIRING DIAGRAMS  
WIRING DIAGRAM - WH2 182/260  
38  
WIRING DIAGRAM - WH2 330/400  
39  
WIRING DIAGRAM - WH2 514/624  
40  
WIRING DIAGRAM - WH2 724-1336  
41  
WIRING DIAGRAM - WH2 1414-1826  
42  
WIRING DIAGRAM - WH2 2100-2500  
43  
WIRING DIAGRAM - WH2 3001-4001  
44  
WIRING DIAGRAM - WH1 181/261 LOW NOx  
45  
WIRING DIAGRAM - WH1 331/401 LOW NOx  
46  
TROUBLESHOOTING  
MECHANICAL PROBLEM  
POSSIBLE CAUSE  
CORRECTIVE ACTION  
When heater is turned on nothing  
happens.  
No power to the heater…………………. Check the circuit breaker, outdoor con-  
troller, etc., upstream of heater.  
Bad transformer…………………………. If power to Leads L1 and L2 of trans-  
former, but no power on 24V side, re-  
place.  
Inoperative thermostat………………….. Jumper thermostat, replace with new if  
heater fires.  
Inoperative toggle switch……………….. If power to toggle switch, but not through  
switch, replace.  
Inoperative relay…………………………. If power to relay, but not operating, re-  
place.  
Thermostat in "ON" position causes  
relay and pump to operate, but  
heater does not fire.  
Main gas valve closed………………...... Open valve.  
Plugged bleed line on gas valve or  
gas pressure regulator………………….. Loosen bleed line and clean.  
Broken pump coupler…………………… Replace coupler. Inspect bearing as-  
sembly, and if frozen, lubricate or re-  
place.  
Shutdown by low water cut-off,  
caused by air…………………………….. Bleed air from system.  
Gas valve defective…………………….. Checkforpowertogasvalve. Ifvalvehas  
power but will not open, check vent tube  
for blockage. If clear, replace valve.  
Continuous shut down of manual  
reset High Limit.  
Temperature setting too low……………. Reset High Limit to higher temperature.  
Low water flow…………………………… Check system water pumps.  
Interrupted pump operation…………….. Check pump oil if necessary.  
Modulating control set too high……….. Reset modulator to a lower setting.  
Mechanical modulating control………… Check and replace if necessary.  
Sooting  
Air starvation…………………………….. Refer to installation instructions regard-  
ing combustion air requirements.  
Condensation……………………………. Set bypass valve to prevent heater inlet  
CAUTION-Soot may be combus-  
tible. Wet down and exercise  
caution when cleaning.  
Toxic fumes which cause a chemical  
reaction with copper tubes or destroy  
temperature from dropping below 105° F.  
combustion………………………………. Remove all sources of fumes, such as  
freon or chloride, or isolate the heater.  
Improper venting………………………… Follow recommended vent installation  
instructions.  
Continuous shut down of low water  
cut-off or flow switch.  
Insufficient system flow…………………. Check pumps and piping.  
Low water due to leaking……………….. Inspect for leaking and repair.  
Air in system……………………………... Inspect for leakage and repair. Install an  
automatic air vent.  
Line strainer dirty………………………… Clean.  
Lime in Heat Exchanger………………… Ream tubes.  
Low flame.  
Low gas supply………………………….. Debris in gas line (pipe dope, rocks, etc.).  
Gas line too small.  
Improper size gas meter.  
Gas regulator adjustment.  
Insects or debris clogging………………. Clean burners.  
Burner intake ports low gas pressure…. Adjust gas pressure.  
Venting or combustion air………………. Refer to installation instructions regard-  
ing combustion air requirement.  
Outer jacket very hot (blistered paint)  
Broken refractory…..……………………. Replace refractory panels.  
Combustion fan not running.  
(If applicable)  
Fan relay................................................ Replace fan relay.  
Fan......................................................... Loose wire connection.  
Failed fan motor.  
47  
TROUBLESHOOTING - PUMPS  
FAILURE TO PUMP  
PUMP LOSES PRIME  
1. Pump not properly primed.  
2. Wrong direction of rotation.  
3. Speed too low.  
1. Air leaks in suction line.  
2. Excess air in water.  
3. Water seal in stuffing box not functioning.  
4. Excessive suction lift and pump operating too  
near shut-off point.  
4. Total head too high.  
REDUCED CAPACITY AND/OR HEAD  
1. Air pockets or leaks in suction line.  
2. Clogged impeller.  
3. Foot valve strainer too small or clogged.  
4. Excessive suction lift (over 15 feet).  
5. Insufficient positive suction head (for hot water).  
6. Total head more than that for which pump is  
intended.  
OVERLOADED DRIVING UNIT  
1. Head much lower than that for which pump is  
designed.  
2. Speed too high or higher than that contem-  
plated.  
MECHANICAL TROUBLES AND NOISE  
1. Misalignment.  
7. Excessively worn impeller and wearing rings.  
2. Excessive suction lift or vapor binding (hot  
water).  
RAPIDWEAR OF COUPLING  
1. Misalignment or a bent shaft.  
2. Sagging motor mounts (over-oiling).  
3. Bent shaft and/or damaged bearings.  
4. Suction and discharge piping not properly  
supported and anchored.  
SERVICE AND MAINTENANCE PROCEDURES  
Fig. # 8154  
RAYPAK TUBE CLEANING KIT  
Extension Pieces (5)  
Auger with Carbide Tip  
Wire Brush  
TUBE CLEANING  
sure the residue does not get into the system.  
Note that you do not remove the top pan or the  
Establish a regular inspection schedule, the frequency  
depending on the local water condition and severity of  
service. Do not let the tubes clog up solidly. Clean out heat exchanger generally.  
deposits over 1/16" in thickness.  
After reaming with the auger, mount the wire brush  
The heater may be cleaned from the side opposite and clean out the debris remaining in the tubes.  
the water connections as shown, without breaking pipe  
connections. It is preferable, however, to remove both ream tubes and immerse heat exchanger in non-  
headers for better visibility through the tubes and to be  
Another method is to remove the heat exchanger,  
inhibited de-scale solvent.  
48  
COMBINATION FLAME SENSOR/  
BURNER ORIFICES  
IGNITOR AND PILOT BURNER LOCATION  
BURNERS  
BURNER HOLD-DOWN LOCATION  
TYPICAL BURNER TRAY ILLUSTRATED  
BURNER TRAY REMOVAL  
PILOT REMOVAL AND CLEANING  
1. Shut-off power and gas supply to the heater.  
Disconnect union(s) and pilot tubing, then  
loosen and remove burner hold-down screws.  
2. Disconnect wires at gas valve and slide burner  
drawer out.  
1. Disconnect pilot tubing at pilot and sensor/igniter  
wire. Remove screws holding pilot bracket to  
burner tray.  
2. Remove pilot and bracket, clean pilot of debris,  
small bugs, etc., with wire or small brush.  
3. Replace pilot, pilot tubing, sensor ignition wires  
and check for leaks.  
GAS VALVE REMOVAL  
1. Shut-off gas supply to the heater. Remove gas  
piping to gas valve inlet.  
HIGH LIMIT OR TANKSTAT REMOVAL  
2. Disconnect wires, pilot tubing and bleed line, if  
required.  
3. Turn vertical gas pipe from manifold slightly and  
unscrew gas valve.  
1. Turn off electrical power.  
2. Remove front inspection panel.  
3. Remove wires to high limit and loosen screws  
holding high limit to cabinet.  
4. Reverse above procedure to re-install.  
4. Remove wedge clip holding sensing bulb in  
control well.  
5. Remove high limit and install a new one.  
6. Check control operation before leaving job.  
MAIN BURNER AND ORIFICE REMOVAL  
1. Remove screws and burner hold-down bracket.  
HEAT EXCHANGER REMOVAL  
NOTE: If the heat exchanger is sooted badly, the  
burner hold-down bracket and spacer can become  
distorted from direct flame impingement and this usu-  
ally necessitates replacement of these parts.  
1. Shut water, gas and electricity off, close valves  
and relieve pressure, remove relief valve.  
2. Remove side inspection panels.  
3. Remove top holding screws.  
2. Lift burners from slotted spacer and slide from  
orifices. Clean with a wire brush.  
4. Remove draft diverter, lift and remove top and  
flue collector on stack type models. Remove  
inspection panels.  
5. Loosen bolts and disconnect flange nuts on  
in/out header, loosen union (s) at gas  
pipe, and slide heater away from piping until  
studs clear the heater.  
6. Remove heat exchanger corner brackets.  
7. Remove combustion chamber clips at the four  
corners of the heat exchanger.  
3. Orifices usually do not need to be replaced.  
To clean, run either copper wire or wood  
through orifice. Do not enlarge hole. To  
remove orifice, use a socket wrench and  
remove the manifold. DO NOT overtighten  
when reinstalling.  
8. Lift heat exchanger straight up using caution not to  
damage refractory.  
49  
HEAT EXCHANGER RE-ASSEMBLY  
COMBUSTION CHAMBER REMOVAL  
1. Heat exchanger water header O-rings should be  
replaced with new ones.  
To remove combustion chamber you must first  
have removed the heat exchanger. Unbolt metal  
combustion chamber retainer from top and remove  
combustion chamber panels individually.  
2. Install in/out and return water headers and  
install header retainer nuts and torque nuts evenly.  
3. Install the four (4) corner clips between tube  
sheets and refractory. Replace "V" baffles.  
4. Install thermostat sensing bulbs in header wells  
and replace bulb retaining clips.  
5. Install inlet and return pipes in water headers  
using pipe thread sealant.  
6. Install water pressure relief valve, flow switch, and  
low water cut-off devices (if so equipped).  
7. Open water supply and return shut-off valves. Fill  
heater and water piping system with water. Check  
heater and piping system for leaks at full line pres-  
sure. Run system circulating pump for a minimum  
of 1/2 hour with heater shut-off.  
REFRACTORY PANELS TOP VIEW  
8. Shut down entire system and vent all radiation  
units and high points in system piping. Check all  
strainers for debris. Expansion tank water level  
should be at the 1/4 mark and the balance of  
the tank filled with air.  
9. Install flue collector, jacket top and inspection  
panels. Install top holding screws. Install draft  
diverter and vent piping if so equipped.  
10. If gas piping was disconnected, reconnect gas  
piping system and check for leakage using a  
soap solution.  
CONTROL WELL REPLACEMENT  
Remove top, sensing bulb and clip. Collapse well  
tube at the open and with a chisel, push through into  
header and remove the well through header. Insert a  
new well and roll into place. If a roller is not available,  
solder the well in place with silver solder.  
TUBE REPLACEMENT  
1. Remove heat exchanger from heater following  
instructions outlined under HEAT EXCHANGER  
REMOVAL above.  
2. Remove in/out and return headers. Remove  
"V" baffle from damaged tube.  
11. Check for correct water pressure and water level in  
the system. Make sure that system pump operates  
immediately on the call for heat. The system is  
ready for operation.  
3. Remove damaged tube by cutting with a hack saw  
or shearing with a chisel adjacent to each tube  
sheet.  
12. Within two (2) days of start-up, recheck all air vents  
and expansion tank levels.  
4. Collapse stub ends in tube sheets using a chisel or  
screwdriver. DO NOT cut into tube sheet or mar  
surface in tube hole in any way.  
5. Insert replacement tube by inserting the end with  
the most fins removed in the opening of one tube  
sheet. Slide tube until the opposite end clears the  
other tube sheet and fit the tube into the hole.  
6. Insert the tube roller into tube opening up to stop,  
making certain that 1/8" of tube projects beyond  
the tube sheet.  
7. Attach drill to tube roller, holding it straight and  
level.  
Note: Use a 3/8" heavy duty, reversible, electric drill or  
larger. Proceed to expand tube until tool starts to grab.  
Approximately 1/2 to 1" of the tool shank will be visible.  
Fig# 9337  
TYPICAL HEAT EXCHANGER CONFIGURATION  
8. Reverse drill motor and withdraw tube roller, If  
necessary wrench out by hand.  
50  
9. DO NOT apply excessive torque during rolling  
operation and avoid thinning any wall of the tube  
beyond 0.015".  
10. Use same procedure on opposite end.  
11. Apply line pressure test. Re-roll if necessary.  
12. Reinstall as outlined under HEAT EXCHANGER  
REASSEMBLY.  
REPLACEMENT PARTS  
See separate parts sheet in instruction envelope.  
NOTE: To supply the correct part it is important that you  
state the model number, serial number and type of gas  
when applicable.  
Any part returned for replacement under standard  
company warranties must be properly tagged with  
RAYPAK return parts tag, completely filled in with the  
heater serial number, model number, etc., and shipped  
to the Company freight prepaid.  
CLEANING FLUE GAS PASSAGEWAYS  
Soot will clog areas between fins and cause even-  
tual tube failure. Any sign of soot at base of burners or  
around outer jacket indicates a need for cleaning.  
1. Lift off drafthood and flue collector by removing  
bolts and screws.  
If determined defective by the Company and within  
warranty, the part will be returned in kind or equal  
substitution, freight collect. Credit will not be issued.  
2. Remove "V" baffles from heat exchanger.  
3. Remove burner tray.  
4. Take garden hose and wash heat exchanger,  
making sure soot is removed from between fins.  
(Avoid excessive water against refractory).  
5. Reassemble: When heater is fired, some steam  
will form from wet refractory. This is normal.  
6. Identify and correct reason for soot formation.  
RAYPAK, INC.  
2151 Eastman Avenue  
Oxnard, CA 93030  
NOTE: In extreme cases it may be necessary to  
remove the heat exchanger completely for cleaning.  
The simplest method is high pressure cleaning at a  
local car wash. DO NOT WIRE BRUSH!  
CAUTION:  
Soot is combustible, so exercise extreme care.  
ILLUSTRATED PARTS LIST  
AVAILABLE AT  
WWW.RAYPAK.COM  
CATALOG  
MODEL  
NUMBER  
133  
9300.11  
9300.203  
9300.35  
9300.50  
9300.60  
181-401  
334-824  
926-1826  
2001-2500  
51  
WARRANTY  
LIMITED PARTS WARRANTY  
RAYTHERM™ COMMERCIAL HEATERS  
TYPES H, NH & WH  
MODELS 133 TO 4001  
SCOPE:  
Raypak, Inc. ("Raypak") warrants to the original owner that all parts of this heater which are actually manufactured by Raypak will  
be free from failure under normal use and service for the specified warranty periods and subject to the conditions set forth in this  
Warranty. Labor charges and other costs for parts removal or reinstallation, shipping and transportation are not covered by this  
Warranty but are the owner's responsibility.  
ANY PART MANUFACTURED BY RAYPAK:  
One (1) year warranty from date of heater installation, or eighteen (18) months from date of factory shipment based on  
Raypak's records, whichever comes first.  
SATISFACTORY PROOF OF INSTALLATION DATE, SUCH AS INSTALLER INVOICE, IS REQUIRED. THIS WARRANTY WILL  
BE VOID IF THE HEATER RATING PLATE IS ALTERED OR REMOVED.  
HEAT EXCHANGER WARRANTY:  
Domestic Hot Water  
Five (5) years from date of heater installation. Includes copper heat exchanger with bronze and cast iron waterways.  
Ten (10) years from date of heater installation. Includes only cupro-nickel heat exchanger with bronze or cast iron waterways.  
Space Heating (Closed Loop System)  
Ten (10) years from date of heater installation. Includes both cupro-nickel and copper heat exchanger with bronze or cast iron  
waterways.  
Thermal Shock Warranty  
Twenty (20) years from date of heater installation against "Thermal Shock" (excluded, however, if caused by heater operation at large  
changes exceeding 150°F between the water temperature at intake and heater temperature, or operating at heater temperatures exceeding  
230°F).  
ADDITIONAL WARRANTY EXCLUSIONS:  
This warranty does not cover failures or malfunctions resulting from:  
1. Failure to properly install, operate or maintain the heater in accordance with our printed instructions provided;  
2. Abuse, alteration, accident, fire, flood and the like;  
3. Sediment or lime build-up, freezing, or other conditions causing inadequate water circulation;  
4. High velocity flow exceeding heater design rates;  
5. Failure of connected systems devices, such as pump or controller;  
6. Use of non-factory authorized accessories or other components in conjunction with the heater system;  
7. Failure to eliminate air from, or replenish water in, the connected water system;  
8. Chemical contamination of combustion air or use of chemical additives to water.  
PARTS REPLACEMENT:  
Under this Warranty, Raypak will furnish a replacement for any failed part. The failed part must first be returned to Raypak if  
requested, with transportation charges prepaid, and all applicable warranty conditions satisfied. The replacement part will  
be warranted for only the unexpired portion of the original warranty. Raypak makes no warranty whatsoever on parts manufactured  
by others, but Raypak will apply any such warranty as may be provided by the parts manufacturers.  
TO MAKE WARRANTY CLAIM:  
Promptly notify the original installer, supplying the model and serial numbers of the unit, date of installation and description of the  
problem. The installer must then notify a Raypak distributor for instructions regarding the claim. If either is not available, contact  
Service Manager, Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA or call (805) 278-5300. In all cases proper authorization must first  
be received from Raypak before replacement of any part.  
EXCLUSIVE WARRANTY - LIMITATION OF LIABILITY:  
This is the only warranty given by Raypak. No one is authorized to make any other warranties on Raypak's behalf. THIS  
WARRANTY IN LIEU OF ALL OTHER WARRANTIES, EXPRESS OR IMPLIED, INCLUDING BUT NOT LIMITED TO IMPLIED  
WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE. RAYPAK'S SOLE LIABILITY AND THE  
SOLE REMEDY AGAINST RAYPAK WITH RESPECT TO DEFECTIVE PARTS SHALL BE AS PROVIDED IN THIS WARRANTY.  
IT IS AGREED THAT RAYPAK SHALL HAVE NO LIABILITY, WHETHER UNDER THIS WARRANTY, OR IN CONTRACT, TORT,  
NEGLIGENCE OR OTHERWISE, FOR ANY SPECIAL, CONSEQUENTIAL, OR INCIDENTAL DAMAGE, INCLUDING DAMAGE  
FROM WATER LEAKAGE. Some states do not allow limitations on how long an implied warranty lasts, or for the exclusion of  
incidental or consequential damages. So the above limitation or exclusion may not apply to you.  
This Limited Warranty gives you specific legal rights. You may also have other rights which may vary from state to state. We  
suggest that you complete the information below and retain this certificate in the event warranty service is needed. Reasonable  
proof of the effective date of the warranty (date of installation) must be presented, otherwise, the effective date will be based on  
the date of manufacture plus thirty (30) days.  
_____________________________________________________  
Name of Owner  
______________________________________________  
Name of Dealer  
_____________________________________________________  
Address  
______________________________________________  
Address  
_____________________________________________________  
______________________________________________  
_____________________________________________________  
Model No.  
______________________________________________  
Serial No.  
Date of Installation:_____________________________________  
Date of Initial Operation: ___________________________  
P/N: 240532  
52  
Raypak, Inc., 2151 Eastman Avenue, Oxnard, CA 93030 (805) 278-5300 FAX (800) 872-9725  
Raypak Canada LTD, 2805 Slough Street, Mississauga, Ontario, Canada L4T 1G2 (905) 677-7999 FAX (905) 677-8036  
Litho in U.S.A.  

RCA VHS C User Manual
Pyramid Car Audio PDVD79 User Manual
Planar Systems Car Video System PT1550MX User Manual
Pentax TS2V114E (C70100) User Manual
Panasonic HDC SDX1P User Manual
Panasonic DV PROLINE AG DVC180B User Manual
Oster Blender FPSTFP4263 DFL User Manual
Niles Audio TODDLER BED 8833 User Manual
Lennox Hearth SP5050 User Manual
Kenwood KMD 44 User Manual