QHT Boiler User Manual

3Wood Cast Iron Boiler  
SAVE THESE INSTRUCTIONS  
Must be installed by  
For wood and  
a qualified licensed  
soft coal only.  
Heating Contractor.  
IMPORTANT:  
OWNER:  
PLEASE READ THESE INSTRUCTIONS  
For service and repairs to the  
CAREFULLY BEFORE PROCEEDING WITH  
heating system, please contact your  
THE INSTALLATION OF THE BOILER.  
Heating Contractor. The following  
THESE INSTRUCTIONS MUST BE POSTED  
information should be filled in by  
NEAR THE BOILER AND MAINTAINED IN  
your Heating Contractor, and used  
LEGIBLE CONDITION FOR REFERENCE  
by you when seeking information  
BY THE OWNER OR SERVICE PERSON.  
concerning the boiler.  
Boiler Serial No._____________  
Address:_________________________  
Model No.___________  
_________________________  
Telephone Number:  
Heating Contractor:____________________  
_________________________  
Rev. B 9/15/10  
Table of Contents  
4
5-6  
7
Important Information  
Warnings and safety rules, Identification  
Procedure in event of power failure  
Refueling the Boiler  
8
9
Wood Burning  
10  
Heat value of wood, Wood Storage, Ash Removal  
Creosote, Runaway Fire  
11  
12  
Chimneys  
13  
Coal Firing  
14  
3Wood Design  
15  
Installation Considerations  
Layout of Main Components  
Transporting and Minimum Clearances  
Flue Gas Outlet and Combustion Air  
Assembling the Casing  
16  
17  
18  
19  
20  
Installation of Controls  
21,22  
23  
Installations of Flue Gas Partition and Draft Regulator  
Commissioning the Boiler  
24,25  
26,27,28  
29,30,31  
32,33,34  
35  
3WOOD as only boiler piping and wiring  
4 Way Mixing Valve Piping and Wiring  
Parallel Piping and Wiring  
Boiler and Casing Parts  
Useful References  
Shutdown  
36  
Troubleshooting  
System Checkout  
Warranty  
37  
38  
39  
3
IMPORTANT INFORMATION  
Please read this page carefully.  
ALL BOILERS MUST BE INSTALLED IN ACCORDANCE WITH NATIONAL, STATE AND LOCAL PLUMBING,  
HEATING AND ELECTRICAL CODES AND ORDINANCES, AS WELL AS THE REGULATIONS OF THE SERVING  
ELECTRICAL, WATER AND GAS UTILITIES.  
All systems should be designed and installed by licensed heating contractors who are knowledgeable in the layout and  
installation of multi-fuel heating systems.  
WARNING  
The 3WOOD Boiler must be positioned to provide at least 36of clearance between any combustible material and the  
sides, rear, and top of the boiler. At least 60must be provided between the front of the boiler and any combustible  
material. Boiler must be set on a non-combustible floor.  
Do not burn volatile garbage, gasoline, naphtha, propane, engine oil, or other flammable liquids. All flammable liquids  
(especially gasoline), debris, rags, paper, wood scraps, etc., should be kept clear of the boiler at all times. Keep the  
boiler area clean and free of fire hazards.  
All 3WOOD Boilers must be connected to a tile-lined flue with a minimum size of 8x 8or to an insulated metal chimney  
with a minimum size of 6. NO OTHER APPLIANCE SHOULD BE VENTED THROUGH THIS FLUE! Your chimney flue  
should be inspected regularly (BI-Monthly) for any build up of fly ash or creosote.  
It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly  
when the installation is completed.  
Please read the literature and warranty supplied by the manufacturer of the various accessory devices.  
These devices are warranted by the manufacturer, not by QHT, Inc. or BIASI. These accessory devices must be  
installed and used according to the recommendations of the manufacturer.  
Do not use self contained, non-electrical zone valves in the zone controlled by the overheat control.  
When references are made to tapping numbers, please refer to the specifications sections.  
All firewood used in this boiler must be dried to moisture content of 20% or less. (see pg.11)  
Homeowners should read and familiarize themselves with Procedure In Event Of Power Failure. (see pg.9)  
Anyone who is going to operate this boiler MUST read and familiarize himself or herself with Starting And Maintaining A  
Fire. (see pg.23)  
DANGER  
COAL FIRES CAN PRODUCE POISONOUS GASES!  
All coal fires produce large quantities of carbon monoxide (CO), a highly poisonous gas. Exposure to this gas produces  
drowsiness, sleep and, in some cases, brain damage or even death. Since carbon monoxide is odorless and colorless, the  
victim is rarely aware that he or she is being overcome until it is too late.  
Normally, carbon monoxide burns as a blue flame over the coal bed, but under and of the following conditions, unburnt  
carbon monoxide gas could escape from the combustion chamber, stove pipe, flue or chimney and enter the house:  
·
·
A blocked chimney  
An internal blockage in the heating appliance that can be caused by a build up of ashes, poor positioning of the coal,  
or firing with too much fuel.  
A closed smoke pipe damper  
A poor chimney draft  
·
·
If you are burning coal or plan to burn coal, make certain that none of the conditions listed above exist. If you have any  
questions about coal burning, please consult with your contractor or the BIASI Distributor.  
Codes and Regulations  
Installation of the boiler, and related equipment must conform to national, state and local regulations codes applicable to  
the installation of the equipment. In the absence of local requirements, the following codes apply:  
National Fire Protection Association (NFPA)  
CSA International  
Battery March Park  
8501 East Pleasant Valley Road  
Quincy, MA 02269  
Cleveland, OH 44134  
4
WARNING  
SAFETY RULES  
After removing the packaging, check that the material supplied is intact and complete; if this is not the case, contact  
the heating contractor that sold the 3WOOD Boiler.  
The 3WOOD Boiler must be installed by a licensed heating contractor in compliance with the National, State and  
Local codes in force and the instructions provided in the manual supplied with the 3WOOD.  
The 3WOOD Boiler must be used for the intended purpose. QHT BIASI is not liable for any injury or damages  
caused to people, animals or things due to errors in installation, operation, maintenance and improper use of the  
boiler.  
In the event of water leaks, close the water supply and call your Heating Contractor.  
The manual is an integral part of the 3WOOD and consequently must ALWAYS be kept with the 3WOOD  
Boiler when transferred to another owner or user, or installed in another system. The manual must be kept carefully  
and if damaged or lost a replacement can be ordered by calling QHT Biasi.(1-800-501-7697)  
The 3WOOD Boiler is not to be used with an automatic stoker unless so certified.  
The 3WOOD Boiler must be serviced at least once a year.  
Caution: Hot surfaces; keep children away. Do not touch during operation.  
WARNING RISK OF FIRE.  
DO NOT allow the boiler to be controlled by children or incapable persons without supervision.  
DO NOT use chemicals or fluids to start the fire.  
DO NOT burn garbage, gasoline, naphtha, propane, engine oil, or other flammable materials.  
DO NOT fire the 3WOOD during a power failure. Use a wood stove during a power failure not a wood boiler.  
DO NOT dispose of ashes in anything other then a steel container and do not store it in house.  
DO NOT let the chimney draft exceed .2 inches of water column  
DO NOT adjust or tamper with the chain which connects the Samson draft regulator to the air damper  
DO NOT perform any cleaning operations when the boiler is hot or when there are coals inside the boiler.  
DO NOT adjust the safety or control devices without consulting with the instructions of the manufacturer of the boiler.  
DO NOT plug or reduce the size of the ventilation openings in the room where the boiler is installed and on the boiler  
(if present). The ventilation openings are essential for correct combustion.  
DO NOT leave containers with flammable substances in the boiler room where the boiler is installed.  
DO NOT operate with fuel loading or ash doors open.  
DO NOT store fuel or other combustible materials within marked installation clearances.  
DO NOT overload the combustion chamber.  
NOTE: Inspect and clean chimney flue regularly.  
DANGER  
DO NOT connect to any chimney or vent serving another appliance.  
NOTE: For Canadian Installations, the boiler must be installed as per the following  
Requirements:  
CAN/CSA-B365 Changes to the installation must comply with CAN/CGA-B149.1  
Can/CGA-B149.2 (for gas fired), C22.1 (for electric), CSA B139 (for oil fired)  
5
WARNING  
-Canadian  
Operate the (gas, Oil, Electric) boiler periodically to ensure that it will operate satisfactory when needed.  
DO NOT relocate or by-pass any of the safety controls in the original boiler installation.  
The operation of the gas boiler must be verified for acceptance operation before and after installation of the  
add-on boiler by a gas filter who is recognized by a regulatory body.  
Note: Only wood and bituminous coal can be burned in this boiler.  
IDENTIFICATION  
The 3WOOD Boiler is identified by:  
The ETL Name Plate that MUST be applied by QHT Inc, so that it is legible when the 3WOOD is installed  
(for example, on the top panel as shown on page 20).  
The ASME Plate is fastened to the front of the boiler on the casting.  
Before Installing  
WHEN SERVICING BOILER  
To avoid electric shock, disconnect electrical supply before performing maintenance.  
To avoid severe burns, allow boiler to cool before performing maintenance.  
BOILER OPERATION  
Do not block flow of combustion or ventilation air to boiler.  
Should overheating occur do not disconnect electrical supply to circulator. Instead, open all the flow checks external  
to the Boilers.  
Do not use this boiler if any part has been under water. Immediately call a qualified service technician to inspect the  
boiler and to replace any part of the control system.  
Do not overload the boiler.  
BOILER WATER  
If you have an old system with cast iron radiators, thoroughly flush the system (without boiler connected) to remove  
sediment.  
Do not use petroleum-based cleaning or sealing compounds in boiler system.  
Use only inhibits propylene glycol which are specifically formulated for hydronic systems.  
Continual fresh make-up water will reduce boiler life. Mineral buildup in heat exchanger reduces heat transfer,  
overheats the stainless steel heat exchanger, and causes failure. Addition of oxygen carried in by make-up water can  
cause internal corrosion in system components. Leaks in boiler or piping must be repaired at once to prevent make-  
up water.  
6
PROCEDURE IN EVENT OF POWER FAILURE  
Should your electricity go off during the heating season, there are several procedures that should be  
followed in order that you may continue to safely operate your heating system. These procedures apply to the  
solid-fuel boiler, as the gas or oil-fired boiler, if any, will be completely inoperative.  
1. Locate any flow-checkvalves in the system (See Pg. 7), and completely unscrew the knob on the top of  
all these valves. (This will allow a certain amount of heated water to circulate by convection throughout the  
house, preventing the pipes from freezing and keeping the house partially heated).  
Note: This does not apply to gravity systems, as they have no flow-check  
valves, and will continue to operate normally without electricity.  
2. The automatic draft regulator will continue to control the wood fire in the absence of electric power. It is  
important to remember that the heating system cannot dispose of a great deal of fuel without a circulator  
running.  
Exploded view of top bushing arrangement  
1. Remove factory bushing and re-  
place with provided steel adapter  
(1)  
2. Place OverHeat aquastat in a tee  
(not provided) above the steel  
adapter (provided) into the short  
3/4 immersion well. (provided)  
PIPING NOTES:  
1. This drawing is meant to show system piping  
concept only. The installer is responsible for all  
equipment & detailing required by local codes.  
2. Discharge of Pressure Relief Valve must be piped  
without valves to within 3of the floor.  
3. Where required, Low Water Cutoff must be  
installed in the Supply piping of the oil/gas boiler  
7
REFUELING THE BOILER  
CAUTION  
Use extreme caution when refueling the boiler. If the door is opened too quickly, the unburned hot gases  
may ignite and cause a back puff. This is especially true with very dry wood.  
DO NOT tamper with the chain on the draft regulator as it could cause the fire to burn out of control.  
Keep ash and fuel doors closed if not refueling boiler.  
DO NOT overload the boiler.  
Adjusting the Flue Gas Damper  
To Re-fire the boiler, open the flue gas damper to establish more draft through the combustion chamber. Af-  
ter refueling, when the fire is established, it probably will be necessary to close the flue gas damper to match  
the heating requirements and accommodate the chimney draft.  
Reloading Wood  
CAUTION  
To reload wood in the firebox, Carefully open the top fire door an inch or so until you can see that the fire is  
burning well and the smoke is exhausting up into the heat exchanger above the firebox. While loading, the door can  
be left fully open and logs can be added by swinging the flue gas damper open. Logs should be 1or 2shorter than  
the firebox in the boiler and should be of such diameter as not to bridgeor jam in the firebox. Logs of 2to 4in  
diameter should be used whenever possible. This will produce an even burning and efficient fire. Wood split to this  
size also dries much more quickly. The logs should be stacked and lined up horizontally so the burning wood can  
settle easily. Add the largest wood when the fire is burning well and some coals are forming. After you have filled  
the firebox to the desired level, close the loading door securely. Damage or injury will result if wood is not loaded  
carefully generally level with bottom of flue gas damper. If loaded in-correctly there is a risk of fire or injury.  
In long- term maintenance of the boiler fire, frequent stoking with small amounts of wood is better than in-  
frequent stoking with larger amounts. When you stoke the fire, pull some of the hot coals forward in the firebox  
where they can get sufficient air to burn thereby enabling them to set fire to the next load of wood.  
Draft Regulator  
The draft regulator should be adjusted as follows:  
It may take several trials adjusting the Samson control setting to maintain the proper boiler temperature during  
wood firing of approximately 180-190°F. The final control setting may be a little more or a little less then the red  
80°C on the dial. During normal operation, especially in the spring or fall, it is necessary to allow air to enter  
through the secondary air damper. This method reduces the possibility of creosote formation when the lower air flap  
is fully closed.  
1. Turn the black knob counterclockwise to set the red number from 40°C to 80°C at the red line.  
2. Allow the wood fire to slowly bring the boiler temperature up to about 180°F on the temperature gauge.  
3. As this temperature is reached, the lower door air inlet flap will begin to close because the proper combustion of  
air has entered the firebox to maintain the selected boiler temperature.  
DO NOT tamper with the chain on the draft regulator as it could cause the fire to burn out of control.  
CAUTION  
Empty the ashes before they touch the grates so they will not interfere with the airflow to the vertical flue  
passages  
8
WOOD BURNING  
Overview  
Burn dry and well-seasoned hardwood with a moisture content of 20% or less. Wood must  
be seasoned at least six months; however, it is preferable to season it for a year to eighteen  
months. Seasoned wood will not only reduce creosote but will also produce more heat. Some sea-  
soned hardwoods will yield 20-25% more heat. Wood-burners who ignore this advice are likely to  
have dirty chimneys and inadequate performance from their boilers.  
Theoretically, there are about 8,600 BTU available as heat from each pound of wood. It  
takes about 1,000 BTU to evaporate each pound of moisture from a log. The wetter the wood, the  
more energy it takes to get the moisture out of the firewood resulting in less energy to heat your  
home. In addition, green wood usually burns at a low temperature, robbing you of even more heat  
in the form of unburned chemicals and gases that it sends up the chimney. The moral is: do not  
burn green wood.  
Selecting Your Wood  
If you buy green wood, season it before using. With some experience, you can spot green  
wood easily. It is heavier and it looks different. Seasoned wood will often show cracks radiating  
outward from the heartwood toward the bark, like wheel spokes. Green wood will not show this  
pattern of cracks.  
You get roughly the same amount of heat from a pound of equivalently dry wood no matter  
what species of tree it comes from. But wood is not sold by the pound; it is sold by the cord i.e. by  
volume. Therefore, the dense heavy woods are the ones to buy, the ones that give you more  
pounds per cord. A cord of wood measures 4 feet x 4 feet x 8 feet. A cord of 4-foot logs thus  
stacked occupies 128 cubic feet and contains about 80 cubic feet of solid wood, with the rest be-  
ing air space between the logs. If you buy a cord of wood, cut it to length and split it, you will find  
it does not occupy 128 cubic feet when stacked. You have not necessarily been cheated. A cord cut  
to length and split packs more tightly thereby occupying less space. Often the best time to buy  
wood is in late winter or early spring. Green wood can sometimes be purchased at low prices in  
spring or early summer.  
Cutting and Drying Your Own Wood  
A good time to cut your own wood is in the late winter or early spring, as soon as the woods  
are free of snow. Then hold the wood for use in 18 months. If you cut trees in the spring or sum-  
mer, let them lie a while until the leaves wither. The leaves will draw moisture from the wood;  
drying it more quickly than if you limbed the tree immediately.  
If you want your wood to dry as quickly as possible, cut it to length and split it. Stack it  
where the air can move through the pile and shelter it from the weather. A wood shed with air  
vents in the sidewalls, like a tobacco-drying barn, is effective.  
9
The Heat Value of Wood  
The following chart compiled by the United States Forest Products Laboratory indicates the  
amount of heat available per cord of wood from a few representative tree species. Other good to  
very good species would include apple, walnut, pecan, dogwood, cypress, sycamore and gum. The  
latter two are hard to split, as is elm.  
Available Heat Per Cord  
In Millions of BTU/ HR  
Green Wood  
Air-Dry  
20.0  
12.5  
21.8  
21.3  
18.0  
17.2  
24.8  
18.8  
21.3  
21.3  
22.7  
13.3  
20.5  
Percent More Heat For Air-Dry Wood  
Species  
Ash  
16.5  
21  
25  
26  
23  
38  
20  
19  
24  
16  
19  
18  
10  
44  
Aspen (Popple, Poplar)  
Beech, American  
Birch, Yellow  
10.3  
17.3  
17.3  
Douglas Fir, Heartwood  
Elm. American  
Hickory, Shagbark  
Maple, Red  
13.0  
14.3  
20.7  
15.0  
Maple, Sugar  
18.4  
Oak, Red  
17.9  
Oak, White  
19.2  
Pine, Easter White  
Pine, Southern yellow  
13.1  
14.2  
WOOD STORAGE  
Store your wood outside of the minimum clearances recommended on the drawings on page 19.  
Generally wood should be stored in the basement or barn, garage where insects wont bother the house. If fans  
are installed within fuel storage area, they should not create negative pressure in the room where the 3WOOD  
is located.  
CAUTION  
ASH REMOVAL  
Before refueling the boiler, check the ash pan under grates and remove and dump ashes if full into a  
metal container. Replace the ash pan and close the ash door. After re-fueling, take the ash container and leave  
it outside the house.  
10  
CREOSOTE  
Creosote condenses from the flue gases more quickly when the temperature in the chimney is  
low. The actual amount of creosote deposited is dependent on:  
1. The amount of moisture in the flue gases.  
2. The temperature of the stack,  
3. The rate at which the wood is burned.  
4. The amount of draft in the stack.  
5. How completely the combustible elements in the flue gases have been burned in the combustion  
chamber. Most problems with creosote are due to insufficiently dry wood, poor chimney with low draft  
and cold walls, and/or a low rate of burning when little heat is required during the spring and fall  
months.  
Moisture in the flue gases may be controlled by:  
Using properly seasoned firewood.  
Mixing small pieces (preferably slab wood) with every full load.  
Never use only large wood (usually less dry) during mild weather when combustion is relatively slow.  
The temperature in the stack may be controlled by:  
Using as short a length of stovepipe with as few elbows as possible between the boiler and the  
chimney.  
The amount of draft in the stack may be controlled by:  
Insuring adequate chimney height and preventing air leaks in places such as around the ash pit door.  
Eliminating external obstructions in the chimney outlet.  
Insulating chimney from heat loss.  
CAUTION  
Procedure in the event of a runaway fire or chimney fire  
If the Boiler-Fire is out of control (or creosote in chimney has caught fire) Do  
the Following:  
Close flue gas damper  
Turn knob on draft regulator to 40°C  
Turn-up thermostats in house  
DO NOT dose the fire with water as injury from steam could occur  
11  
Chimneys  
WARNING  
Do NOT connect this unit to a chimney flue serving another appliance.  
Downdrafts  
Downdrafts can result from improper chimney height, nearby buildings, tree that are taller then the chimney,  
and too large of a flue. To help minimize this problem, the top of the chimney must be at least three feet above the  
point at which it passes through the roof and two feet above the highest point of the roof. In addition, the chimney  
should be at least as high or higher than the tallest section of any adjacent roof.  
WARNING  
Chimney Construction  
Fire insurance underwriters favor and sometimes require masonry construction for chimneys because tile-  
lined masonry chimneys are strong and not likely to crack from high temperatures.  
Insulating your chimney flue liner will create a consistent natural draft by keeping the temperature of the flue  
gasses higher then the atmospheric temperature around the chimney. Insulation will also reduce creosote deposits by  
reducing the moisture condensation from the flue gases.  
3WOOD must be connected to its own separate flue. It must NOT be installed in a flue which is connected to  
another appliance.  
The recommended low heat, tile lined, masonry chimney should have a minimum 8x 8flue and be at least 18  
feet tall.  
A H.T. metal chimney is recommended and should have a stainless steel liner 7ø.  
The exhaust pipe should be minimum 24 gauge and 7ø black or blued steel. It is suggested to point the  
male end of the pipe downward to prevent leaking creosote.  
Chimney Cleaning  
Check your chimney and flue pipe at least twice during the heating season. check it more frequently if you  
are new to wood or believe that there is soot or creosote build up.  
A small amount of smoke can infiltrate the room when you refuel the boiler.  
However, if this happens increasingly you may have a chimney blockage. To find out the cause, look into the  
chimney from above or below. If neither option is convenient, then use a mirror and a flashlight to look up the flue  
utilizing the clean out door as an access point.  
To clean your chimney, you can contact a professional chimney sweep or use several do-it-yourself cleaning  
methods. The most efficient device for scrubbing your chimney flue is a wire chimney brush that is designed for  
cleaning solid fuel flues. These brushes are available in standard sizes for both rectangular and round flues. Another  
option is to fill a burlap bag with straw or rolled up chicken wire, tie it to a rope and drop the rope down to a helper.  
You can then pull the bag up and down in the chimney to scrub away and buildup. Similar methods include using a  
bunch of tire chains tied to a rope or tying a burlap sack to the end of a long pole, provided your chimney is not to  
tall.  
Chemical chimney cleaners such as chimney sweepare available. These products are added to the hot fire  
in order to break down the creosote. We do not know how their long term effects on a chimney or boiler, but we  
have been advised that any chemical salt added to the fire may cause corrosion in insulated metal chimneys, boilers,  
and stovepipes. In addition, these products can be harmful to your health.  
12  
COAL FIRE  
DANGER  
COAL FIRES CAN PRODUCE POISONOUS GASES!  
All coal fires produce large quantities of carbon monoxide (CO) a highly poisonous gas. Exposure to this gas produces  
drowsiness, sleep, and in some cases, brain damage or even death. Since carbon monoxide is odorless and colorless, the victim is  
rarely aware that he or she is being overcome until it is too late.  
Normally, carbon monoxide burns as a blue flame over the coal bed, but under any of the following conditions, unburnt  
carbon monoxide gas could escape from the combustion chamber, stove pipe, flue or chimney and enter the house:  
A blocked chimney  
An internal blockage in the heating appliance that can be caused by a building up of ashes, poor positioning of the fuel, or firing  
with too much fuel.  
A closed smoke pipe damper  
A poor chimney draft.  
If you are burning coal or plan to burn coal, make certain that none of the conditions listed above exist. If you have any questions  
about coal burning, starting or maintaining a coal fire please consult with your contractor.  
CAUTION  
BURN BITUMINOUS (SOFT) COAL ONLY  
Your success with coal burning will improve with experience, as it takes time to familiarize yourself with your new boiler and various  
fuels. Getting the maximum heat out of your coal generally depends on these factors:  
Proper firing technique with adequate draft.  
Clean heat exchanger surfaces in you boilers.  
Quality Bituminous (soft) coal of the proper size.(1-1/2-2-1/2diameter coal).  
It is best to build a coal fire by gradually adding coal over a well established bed of wood coals. Before adding fuel, check to see that  
the ashes are removed from the lower door and that there is clear draft up through the grate area.  
The type, quality and size of the coal you are using will affect the kindling rate and time required to establish a good, deep coal bed.  
There are no set rules, but the following suggestions may help:  
1. Dont run too low a fire. Once you have a good hot coal bed, keep the firebox full to the level of the fire door. Bank the coal bed  
sloping down to the sides and the front below the bottom of loading door. A good deep fire is more economical than a low, thin  
one. DO NOT overload the combustion chamber.  
2. Be sure to leave a hot spot(an area of exposed, glowing coals) to ignite the gases released from the fresh coal.  
3. Be sure to clean out ashes from below grates before adding fuel. Be sure to remove and store ashes only in a metal container,  
preferably with a cover like a trash can, some people even sift ashes to remove large unburned chunks of coal to be reburned.  
Glowing embers in a bed of ashes can remain hot for many daysso be very careful of how you dispose of ash from both wood  
and coal fires!  
4. Dont allow coal dust and soot to accumulate on the inside surfaces of your boiler. Coal dust has an even higher insulating value  
than creosote, so it is a good habit to brush away any accumulation daily. Be careful to check the cleanout in the rear smoke  
hood at least once a week.  
5. Dont disturb the fire once you have a good coal bed.  
6. If you have trouble starting or maintaining a fire, you may want to mix fuels. Generally, softer coals kindle and burn better in  
smaller fireboxes and start up better. Coal over wood coals and gradually establish a good coal fire with bituminous chestnut,  
stove, or eggcoal. You can also freely mix various wood types. A good way to clean any creosote buildup from a regular wood  
fire is to occasionally burn 100-200 pounds of coal.)  
SPECIAL PRECAUTIONS MUST BE TAKEN WHEN BURNING COAL TO AVOID DANGER DUE TO CARBON MONOXIDE GAS  
POISONING.  
13  
The 3WOOD Design  
The 3WOOD Boilers are hot water generators that operate by combustion of hard wood or soft coal.  
They feature a high quality and extremely thick ASME class 20 cast-iron body, protected by high-density  
insulation that limits heat loss.  
The large heat exchange surface and the fins in the flue gas path ensure exceptional resistance to  
corrosion and very high efficiency that remains constant over time (self-cleaning effect).  
The combustion chamber and the upper door for loading the wood are sufficiently large to maximize the  
burn time and limit the number of times the door needs to be opened for refueling.  
The front air grille for secondary air in the upper door and the flue gas damper are easily adjusted for  
tending the fire.  
Secondary combustion chamber  
Technology with 3 Pass:  
1st Pass  
The combustion chamber gasses are carried by a special passage in the rear element. In the same area,  
very hot secondary air is combined with combustion gases which enhance their oxidation.  
2nd Pass  
The gases from the rear element are reburned in the secondary combustion chamber,  
3rd Pass  
The third Pass consists of a wide-finned, self-cleaning zone which directs the smoke towards the flue  
attachment with adjustment shutter and door cleaning.  
14  
Installation considerations  
When the 3WOOD is installed, check that The flue, if reused:  
Supplies the negative pressure required for the new boiler (see the table of technical specifications  
on page 10);  
is suitable for the temperature of the products of combustion, and has been calculated and  
constructed according to the required standards; recommended by NFPA  
is as straight as possible, airtight, insulated and is not blocked or choked;  
is fitted with a cleanout door  
The heating system should be flushed, cleaned of any slime and deposits, vented and tested for  
water tightness.  
The heating system should be equipped with a new expansion tank of sufficient size to handle the  
volume of both boilers.  
The 3WOOD Boiler should be equipped with its own make-up water.  
1 1/2”  
1 1/2”  
Model #  
Min. Output  
(BTU/HR)  
FIREBOX  
DEPTH  
Width  
(inches) (inches)  
Height  
WATER  
CONTENT  
(US-GALLONS)  
Draft  
(inch)  
Weight  
(LBS)  
Length  
(inches)  
3Wood 5  
3Wood 6  
3Wood 7  
89,000  
104,000  
120,000  
16.5”  
20”  
25  
30  
34  
11  
12.5  
14  
.07  
.10  
.12  
695  
804  
903  
24”  
38”  
23.5”  
15  
LAYOUT OF THE MAIN COMPONENTS  
Pressure Gauge  
Flame Inspection Window  
Loading Door  
1.  
2.  
13.  
14.  
15.  
16.  
17.  
18.  
19.  
20.  
21.  
22.  
23.  
24.  
Temperature Gauge  
Flue Gas Chamber  
Mobile Smoke Plate  
Loading / Combustion Chamber  
Flue Gas Baffle  
Draft Regulator  
3.  
Flue Attachment  
4.  
Flue Gas Damper  
5.  
Flue Cleanout Door  
Casing  
6.  
Ash Collection Chamber  
Ash Pit Door  
7.  
Insulation  
8.  
Ash Tray  
1 1/2Flange for Overheat control  
1 1/2Nipple (Supply Outlet)  
1 1/2Bushing (Operating Control)  
1 1/2Flange (Return Outlet)  
9.  
Primary Air Damper  
Secondary Combustion Cover  
Secondary Air Regulator  
10.  
11.  
12.  
16  
Transporting  
Once the packaging has been removed, cut the  
straps and remove the casing in such a way as to  
avoid damaging it.  
If hoisting equipment is available, suitable for  
the weight of the boiler, use the eyebolts (1)  
provided on the body to lift it  
If no suitable hoisting equipment is available,  
handle the boiler manually, as follows:  
Remove the fastening screws (2) for the  
baseboard (3) and take it off, so as to allow  
the pallet to be tilted  
Insert a suitably sized bar through the two  
eyebolts (4) and lift the boiler body.  
WARNING  
Use safety equipment.  
Must be Installed on non combustible floor or  
cinder blocks extending at least 16" in front and  
8" on either side of the 3 WOOD.  
Construction of cement block pad under 3WOOD  
should extend at least 8to each side of the  
boiler and extend at least 2on either side of the  
chimney connector  
Recommended  
Minimum Clearances  
CAUTION  
The room where the 3WOOD Boiler is  
installed must be heated and must always  
comply with the technical standards and  
the local codes.  
Allow for the space required to access the  
safety / control devices and to perform the  
maintenance and loading operations.  
Do Not install the 3WOOD appliances:  
Outdoors, as they are not designed for  
this type of installation.  
In an unheated room.  
In rooms with exhaust fans.  
In houses with heat recovery ventilation  
systems. (HRV) with out having a  
outside source of ventilation air for the  
boiler room.  
17  
WARNING  
FLUE GAS OUTLET  
The chimney and flue must be made in compliance with building codes and resistant to  
high temperature, condensate and mechanical stress, and that are airtight.  
Do not connect to any chimney flue or vent servicing another appliance.  
The 3WOOD takes in the combustion air from the room where the boiler is installed, which  
MUST FEATURE ventilation openings as required by NFPA standards.  
The flue (1) must ensure the minimum negative draft between .07 and .12 as specified in the  
draft section specified on page 17.  
Undersized or incorrectly sized flues (1) and exhaust pipes (2) will cause problems of  
condensation, which will affect combustion and plug the flue.  
The joints should be installed with male ends facing down and sealed using materials that can  
resist temperatures of at least 700°F.  
WARNING  
Note: Material of the chimney connector  
(minimum 24 gauge black or blued steel)  
NO GALVANIZED PIPE.  
7  
COMBUSTION AIR INTAKE  
A separate source of combustion air may be necessary if:  
1. The solid-fuel-fired boiler does not draw steadily, smells,  
experiences smoke roll-out or burns poorly.  
2. Any of the above symptoms are alleviated by opening a  
window slightly on a calm day.  
3. The house or basement is equipped with a well-  
sealed vapor barrier insulation envelope tight  
fitting windows and/or has any powered devices  
that exhaust house air.  
4. There is excessive condensation on windows in  
the winter.  
5. A ventilation system is installed in the house.  
SOURCES OF COMBUSTION AIR ARE:  
A mechanical Fan in a Can.  
A natural make-up air duct system with heat trap.  
18  
ASSEMBLING THE CASING  
A. Remove the outlet and return stubs from the cardboard box inside  
the loading/combustion chamber, and install them  
B. Fit a screw and nut in the holes on the four bottom brackets (1),  
without tightening them  
C. Insert them in the top of the four slots provided at the bottom of  
the boiler, and secure them with the nuts.  
D. Fit a bolt and nut in the holes on the four bottom brackets (1),  
without tightening them  
E. Insert them in the four slots at the bottom of the boiler and tighten  
them  
F. Insert the four top brackets (2) on the studs and tighten them with  
the nuts (3)  
G. Apply the insulation (4) around the boiler body  
H. Fit the side panels (5), hooking the slots (6) on the bottom of the  
panels to the bottom brackets (1)  
I. Fasten the panels (6) to the top brackets (2) using the  
screws (7) supplied with the casing. Leave the right side loose  
after removing the plug in the top of rear section  
J. Fit the top rear panel (8), resting it on the side panels, and secure it with two screws (9)  
K. Apply the rear insulation (10), inserting the edges in the openings at the side and top  
L. Fit the rear panel (11) and fasten it with the six screws (12) supplied  
M. Insert the top centre panel (13) underneath the top rear panel (8) and rest it on the side  
panels  
19  
Installation of Controls  
A. Insert the temperature gauge (16) in the housing on the front panel (15) and secure it  
B. Partially unwind the capillary tube from the thermometer, insert the sensor in the probe socket (17)  
and secure it with the fastening spring  
C. Fit the front panel (15), handling the temperature gauge capillary tube to make sure it is not  
damaged, and inserting the regulator in the opening provided  
D. Secure it to the side panels using the screws supplied.  
E. Insert pressure gauge (13) and capillary tube through the panel (15) and install probe into the  
tapping on the upper right side of rear section of the boiler (17).  
F. Tighten the draft regulator (14) in the housing provided on the boiler body. The cam w/bolt of the  
regulator must be in the bottom position.  
17  
20  
Installation of Flue Gas Partition  
A. Open the loading door (1)  
B. Remove the flue gas cover (2) by  
turning the latch (3)  
C. Insert the flue gas partition (4) in the  
guide provided and press it fully into  
the rear of the boiler.  
D. Replace the cover (2) and secure  
it with the latch (3)  
E. Open the door on the ash collection  
chamber (5) and insert the ash tray  
(6)  
Installation of Draft Regulator  
A. The draft regulator is installed  
horizontally. The hexagon screw (8)  
must be facing bottom.  
21  
B. Hold the cam in position by hand,  
remove the protector (9) and replace it  
with the hexagonal handle (10) at a 45°  
angle up from the center of the regulator.  
C. Set the regulator knob (7) by turning  
knob of regulator counter clockwise to  
the white 30° mark which is the minimum  
position (90°F).  
D. Remove chain from bag and cut it 32  
long and install the hook and eyelet.  
E. Secure the handle (10) by tightening  
screw (11) Connect one end of the chain  
to the hook and attach the hook to  
handle (10).  
F. Tighten the rod (12) into the threaded  
hole on the door (must be level with  
bottom of door) and secure it, using the  
nut (14), in a horizontal position so the  
end of rod is facing to the right  
32”  
G. Attach the 2nd hook to the other end of  
the chain and connect it to the end of the  
rod (12). In this position the air door (13)  
is fully  
open.  
CAUTION  
NOTE:  
Chain must be exactly 32 inches long.  
IMPORTANT:  
When assembly has been completed, the  
Heating Contractor must make sure that the  
ETL TECHNICAL RATING PLATE is attached  
to the top panel of casing.  
22  
Commissioning the 3WOOD Boiler:  
WARNING  
PRELIMINARY CHECKS/ Starting The Fire  
Before starting a fire in the 3 WOOD, check that:  
1. The 3WOOD is filled with water.  
2. The valves are open in the distribution system.  
3. The distribution system has been purged of all its air.  
4. The exhaust pipe and combustion air controls and  
dampers have been installed correctly.  
5. The seals on flue and ash door are in good condition.  
___________________________________________  
STARTING AND MAINTAING A WOOD FIRE  
A. Completely open the flue gas damper (1)  
(horizontal position) on breaching.  
B. Turn draft regulator knob clockwise to the red  
mark 90°C  
C. Move the secondary air regulator (3) to the  
middle position  
D. Adjust the primary air damper (4) so it is open  
1/32at the bottom (minimum opening) using  
the screw (5). Lock it in place with the lock nut.  
The regulator arm should be in a level position.  
Note: Never detach the chain from the rods  
or the handle.  
1/32”  
E. Open the loading door (6), place small pieces  
of paper and dry kindling wood on the top of  
the grates and ignite them  
DO NOT OVERLOAD ABOVE FLAP  
F. Wait for kindling to ignite, complete the load  
with larger pieces of wood not higher than  
bottom of flap, then close the loading door (6)  
G. Ensure the boiler has adequate combustion air  
from vents to the boiler room. Air can be taken  
from basement brought in from the outside.  
23  
3WOOD boiler piping and wiring Considerations  
Before choosing a particular system for your installation, the possibility of using a mixing valve  
arrangement to avoid the problems of overheating should be considered. These systems will continuously  
release heat to the distribution system in proportion to the outside temperature or other load factor. Such an  
arrangement can be added to any heating system, and is one of the most sophisticated methods of heating  
system regulation available. We strongly recommend a mixing system with all of our solid fuel systems.  
A.  
3WOOD AS THE ONLY BOILER  
The 3WOOD boiler can be used as the only boiler in your heating system. Of course, the disadvantage  
of the installation is that there will be no automatic back-up system for times when the solid fuel fire  
will be unattended. For automatic switch-over from solid fuel to oil or gas, a tandem hookup of the  
3WOOD with a second oil or gas boiler is recommended (see Section B). The obvious advantage of  
this set-up is the cost saving involved in the elimination of the conventional boiler, controls and piping  
required. It should be noted that the 3WOOD boiler is extremely efficient when fired with wood or  
coal. Many people use the 3WOOD boiler in conjunction with direct vent gas or electric space heaters  
located in the living spaces.  
The following outlines a typical installation of a stand-alone 3WOOD boiler in a system planned for  
solid fuel firing.  
1. The supply tapping goes to the heating radiation. Install a teewith a 1branch in the line to the  
radiation, as close to the boiler as possible. This branch tee should point up and will route the  
piping to the dump zone. There must not be a valve or any potential restriction between the  
boiler and this tee.  
2. in the boiler supply piping, install an air purger and expansion tank sized to handle the water in the  
distribution system as well as the 3WOOD boiler.  
3. Pipe the make-up water into the boiler through a Watts 1156F fill valve (pressure reducing valve)  
into the lower rear ½tapping at the bottom of the boiler.  
4. Install a tee with a 1branch for the dump zone in the return tapping. Point the branch of the tee  
up.  
5. The circulator should be installed in the return line from the heating radiation. The return is piped  
into the boiler through the running end of the tee.  
6. A circulator relay, Honeywell R845 or equivalent may control the circulator. Both the room  
thermostat and the Overheat Aquastat installed in the 3WOOD boiler control this relay.  
NOTE: In a case where the thermostat is calling for heat and boiler fire is out or otherwise unable to meet the  
heating demands of the house, the circulator will continue to run. This has the advantage of helping  
prevent the water in the system from freezing if the house temperature drops below 32F. If the  
circulator is deactivated, the system must be drained if subfreezing interior temperatures are  
anticipated! As an alternative to draining the system, a mixture of heating system, anti-freeze  
(propylene glycol) and water can be used in place of normal water in the system. Such a mixture  
should only be added after the system is thoroughly checked for leaks.  
24  
Note: Power failure  
reference page 9.  
Thermostat  
NOTE: All wiring must be done in accordance with applicable state, local and national codes. Use only copper conductors.  
3Wood installed in combination with a oil/gas boiler  
Note: The operation of the gas boiler must be verified for acceptable operation before and after  
installation of the add-on appliance by a gas fitter who is recognized by the regulatory  
authority.  
CAUTION  
PIPING NOTES:  
1. This drawing is meant to show system piping concept only.  
2. The installer is responsible for all equipment & detailing required by local codes.  
3. Discharge of Pressure Relief Valve must be piped without valves to within 3of the floor.  
4. Where required, Low Water Cutoff must be installed in the Supply piping of the oil/gas boiler.  
5. DO NOT interfere with the normal delivery of heated water from the original boiler to the system.  
6. Make sure that excessive pressure will not be developed in any portion of the boiler or system through  
properly sizing the expansion tank.  
25  
B.  
4-WAY MIXING VALVE Installed with 3WOOD Boiler in Combination with Oil/Gas Boiler  
1. A mixing valve arrangement is a method of controlling house temperature that is different than traditional American  
systems. In the average hydronic system, circulating or not circulating water of a fairly high and relatively constant  
temperature to radiation controls temperature in the house or zone. The thermostat used in such a system is a simple  
switch to a relay, which turns the circulator on and off. In a mixing valve controlled system, the circulator runs  
continuously, and the temperature of the water flowing to the house is varied by the mixing valve, which adds more or  
less cooler return water to the boiler-heated, water being pumped to the radiation. The valve is controlled manually by  
the homeowner (a very common system in Europe), or is controlled automatically by an outdoor reset control.  
A system controlled by a mixing valve has several advantages over a conventional off/on system.  
Fuel savings of 20%  
Longer boiler life due to elimination of thermal shock to the boiler caused by surges of cold return water at  
circulator start-up  
A quieter and more comfortable house, because heat is more even. Rather than having the heat turn  
completely on and completely off in response to heating demands, causing fluctuation in the house  
temperature, the heat is always onwith the temperature of the radiation adjusting gradually to respond to  
the houses needs.  
In addition, a mixing valve arrangement has very important advantages for solid fuel burning hot water systems.  
Because there is constant circulation, there is always some heat being drawn from the boiler. Since a solid fuel is  
always generating a certain amount of heat, such a system will dispose of this heat efficiently. In conventional  
system, there is a grater possibility of the boiler overheating (when there is no circulation) and creosote formation  
(caused by the fire burning too slowly). A mixing valve system minimizes the possibility of either of those  
problems occurring, thus increasing both the safety and efficiency of the solid fuel system.  
Mixing valve arrangements can be added to any of the systems described in this section or, in fact, to any  
conventional heating system as well. We recommend the 4-way mixing valve to control the temperature of the  
heating radiation. To mix wood heated boiler water with the return water from the distribution system, the boiler  
supply pipe must enter the mixing valve opposite the heating return pipe.  
The following outlines a typical installation of a mixing valve controlled distribution system with a 3WOOD boiler in a system  
planned for solid fuel firing with back-up from a oil or gas-fired boiler.  
1. The line from the 3WOOD boiler supply tapping goes to the oil/gas boiler supply pipe. Install a teewith a 1branch in the  
line as close to the 3WOOD boiler as possible. This branch tee should point up and will route the piping to the dump zone.  
There must not be a valve or any potential restriction between the boiler and this tee.  
2. Immediately after the dump-zonetee, install another tee with a ½ inch branch to install the L4006B aquastat to operate the  
overheat override.  
3. In the boiler supply piping install an air purger and expansion tank sized to handle the water in the distribution system as well  
as the 3WOOD boiler.  
4. Pipe the make-up water into the 3WOOD boiler and the oil/gas boiler through a Watts 1156F fill valve (pressure reducing  
valve) into the lower rear ½tapping at the bottom of the 3WOOD boiler and also into the oil/gas boiler.  
5. Install a tee with a 1branch for the dump zone in the return tapping as close to the 3WOOD boiler as possible. Point the  
branch of the tee up.  
6. The 3WOOD boiler circulator should be installed from the other pipe-leg of the tee to the return tapping of the gas/oil boiler.  
7. The 3WOOD boiler circulator may be controlled by an outdoor reset controller operating the mixing valve, the oil/gas boiler  
relay or a Honeywell R845 or equivalent if the mixing valve is manually operated. This relay is controlled by the 3WOOD  
boiler Aquastat.  
26  
27  
28  
C.  
3WOOD Boiler with circulator Piped in Parallel with Oil/Gas Boiler  
In the traditional American baseboard, hydronic system, the heating temperature in the house or zone is controlled by circulating  
or not circulating water of a fairly high and relatively constant temperature to radiation. The thermostat used in such a system is a  
simple switch to a relay which turns the circulator on and off. The vast majority of American heating systems use cast iron  
boilers which have internal tankless coils for producing domestic hot water. The parallel piping arrangement is the correct  
application for maintaining temperature in the oil/gas boiler with wood heated hot water as well as heating the radiation in the  
house. Since the specifics of such a system will vary from installation to installation, the following procedure provides an  
example of one specific installation which can be used as a model for actual situations.  
1. Insure that the existing system has flow checks or electric zone valves in the supply lines to the various heating zones, and that the  
Space heat and DHW circulators are mounted on the return line going back to the Oil/Gas boiler. If not, they must be installed in  
these locations.  
2. Remove the existing radiation supply and return lines from the oil or gas-fired boiler. Install pipe tees on the supply and returns  
from nipples coming out of the existing oil/gas boiler. NOTE: Occasionally, extra supply and return taps are available on oil/gas  
boilers. These plugs may be removed and used to run the lines between boilers. Re-install the supply and return lines.  
3. Install a tee with a 1branch coming out of the supply tapping of the 3WOOD boiler for the dump zone.  
4. Then install another tee with a ¾branch for the Aquastat for the 3WOOD boilers circulator. Install the Honeywell L4006B  
into the branch of the tee using the 3/4 immersion well. Caution: Be careful to maintain a 12minimum clearance between the  
flue pipe and the 3WOOD boiler aquastat.  
5. Pipe from this tee to the supply pipe on the existing oil/gas boiler.  
Note: By adding the gallonage from the addition of the 3WOOD boiler, an expansion tank should be added or the existing  
tank should be increased in capacity.  
6. Install a tee with a 1branch coming out of the return tapping of the 3WOOD boiler for the dump zone.  
7. Install piping, flow check and circulator from 3WOOD boiler to the return manifold installed on the oil/gas boiler.  
Note: Aquastat settings for the existing oil/gas boiler should be as follows:  
High Limit 165F  
Low Limit - 150F  
Circulator - 140F  
But these settings can be raised if the 3WOOD boiler isnt fired for extended periods of time.  
29  
30  
31  
32  
#
1
Description  
Stud Screw  
Bushing  
3WOOD 4,5,6,7  
59200619  
21  
22  
23  
24  
25  
26  
27  
28  
29  
30  
31  
32  
33  
34  
35  
36  
Bottom Door  
Hinge  
59200644  
59200645  
59200646  
59200729  
59200647  
59200648  
59200649  
59200650  
59200651  
59200652  
59200653  
59200654  
59200655  
59200656  
59200657  
Pin  
2
59200620  
Gasket  
3
Flange  
59200621  
Flame Guard  
Top Door  
4
Side Tapping  
Rear Boiler Section  
5
59200623  
Handle Catch  
Handle Catch  
Regulator  
6
Intermediate Boiler Sections 59200624  
7
Top Push Nipples  
Bottom Push Nipples  
Bushing  
59200625  
59200626  
59200627  
8
Lower Door Stop  
Air Baffle  
9
10  
Tie Rod  
59200628,59200629  
59200630,59200631  
Flame Guard  
Upper Door Stop  
Load Door Grille  
Secondary Air Grille  
Ash Tray  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
Front Boiler Section  
Temperature Gauge  
Bushing  
59200632  
59200633  
59200634  
59200635  
59200636  
59200637  
59200638  
59200639  
59200640  
Inspection Port  
Immersion Well  
Flue Gas Baffle  
Draft Regulator  
Flue Gas Baffle Lock  
Plate  
59200658,59200659,  
59200660,59200661  
37  
38  
39  
40  
Flue Collar Clean-Out  
Flue Collar Spacer  
Flue Damper  
59200662  
59200663  
59200664  
59200665  
Flue Collar  
Partition  
59200641,59200641  
59200642,59200643  
33  
#
1
2
3
4
5
6
7
Description  
Top Rear Panel  
Insulation Assembly  
Rear Panel  
3WOOD-4 3WOOD-5 3WOOD-6 3WOOD-7  
59200600  
59200601  
59200605  
59200606  
59200610  
59200614  
59200615  
59200600  
59200602  
59200605  
59200607  
59200611  
59200614  
59200616  
59200600  
59200603  
59200605  
59200608  
59200612  
59200614  
59200617  
59200600  
59200604  
59200605  
59200609  
59200613  
59200614  
59200618  
Cover Panel  
Right Side Panel  
Front Panel  
Left Side Panel  
34  
35  
SHUTDOWN  
Extended Shutdown:  
If the boiler is not used for an extended period, the following operations must be performed:  
Close the on-off valves connected to the 3WOOD Boiler.  
Remove the ash and clean the flue gas path.  
Assess whether the Technical Service needs to be contacted for more through cleaning.  
WARNING  
Empty the system or add NonToxic antifreeze fluids to the heat system if there is danger of  
frost.  
A container with powdered lime should be placed inside the boiler to absorb humidity.  
Maintenance:  
Periodical maintenance is a legal requirement and is essential for the safety, efficiency and life of the  
3WOOD Boiler.  
It must be performed by a qualified heating contractor at least once a year so as to clean the entire flue  
gas path : loading/combustion chamber, smoke box and flues.  
Routine Cleaning:  
Before starting any cleaning operations wait for the boiler to cool down.  
External Cleaning:  
The casing can be cleaned using cloths dipped in soap and water.  
For hard-to-remove stains, dip the cloth in a mixture of 50% water and denatured alcohol or other  
specific products. Once finished cleaning, carefully dry the 3WOOD Boiler.  
WARNING  
Do not use abrasive products, petrol or trichloroethylene.  
Always make sure there are NO hot coals underneath the ash.  
Use suitable safety equipment.  
The boiler is supplied without accessories, as cleaning can be performed using  
normal household utensils that can be purchased at shops that sell products for  
stoves and fireplaces.  
36  
Troubleshooting  
Problem  
Cause  
Corrective action  
Clean and check the tightness of the flue gas  
path  
Check that the loading and combustion  
chamber doors close correctly  
Fumes are escaping into the air  
Check correct operation and replace if  
necessary  
Draft Regulator  
There is a smell  
of fumes.  
Chain unhooked or broken  
Primary air regulator damper jammed  
Load wood  
Hook chain or replace it  
Release the damper  
Follow the procedure described in this manual  
Check and adjust the position, if necessary  
Vent the system  
Flue gas damper  
The boiler has  
reached the set  
temperature but  
the radiators are  
still cold.  
Air in the system  
Check valves, pumps, room. Thermostats.  
Take and necessary action where required  
System components  
Float valve in the open expansion vessel  
Draft regulator  
Check operation and replace if necessary  
Check operation and replace if necessary  
Hook the chain back on or replace  
Release the damper  
Chain unhooked or broken  
Primary air regulator damper jammed  
The boiler does  
not reach the set  
temperature  
Clean the flue gas path  
Clean the boiler  
Flue gas path and/ or boiler dirty  
Load wood  
Follow the procedure described in this manual  
Check and adjust the position, if necessary  
Flue gas damper  
Flue blocked  
Boiler dirty  
Ash tray full  
Clean the flue gas path  
Clean the boiler  
Empty and clean the ash tray  
Check the correct operation of the draft  
regulator  
Air adjustment  
Check chimney draft  
Check the position of flue gas damper and  
adjust it if necessary  
Flue gas  
emissions dark in  
color  
Check correct operation and replace if  
necessary  
Draft regulator  
Unseasoned wood  
Load wood  
Use seasoned wood (12-20% UR)  
Follow the procedure described in this manual  
37  
System Checkout:  
Boiler Model No._________________  
Original Purchaser:  
Serial No.__________  
Installer:  
_________________________  
_________________________  
_________________________  
______________________  
______________________  
______________________  
Boiler Performance Tests:  
GROSS STACK TEMPERATURE --------------------  
ROOM TEMPERATURE (AMBIENT) -------------------  
NET STACK TEMPERATURE ---------------------  
CO2 -----------------  
O2----------------  
SMOKE READING ----------------  
COMBUSTION EFFICIENCY----------------------  
COMMENTS:  
38  
Warranty for BIASI - 3WOOD Residential  
Cast-Iron Water Boilers  
FIRST YEAR-WARRANTY FOR 3WOOD SERIES  
QHT and Biasi will not be responsible for:  
RESIDENTIAL HOT WATER BOILERS: QHT warrants that its  
1. Components that are part of the heating system, but  
cast-iron boiler and casing are free from defects in material and  
were not manufactured by Biasi or QHT as part of the boiler.  
workmanship for one year from the date of installation. If the boiler 2. The workmanship of the installers of 3WOOD boilers.  
is found to be defective within this period, QHT will replace the  
boiler block or casing.  
Furthermore, this warranty does not assume any liability for  
unsatisfactory performance caused by improper installation.  
3. Any costs for labor to remove or replace the faulty  
component.  
4. Improper burner application or adjustments, control settings,  
care or maintenance.  
LIFETIME WARRANTY-WARRANTY FOR THE CAST IRON  
BOILER BLOCKS OF THE 3WOOD SERIES RESIDENTIAL  
BOILERS: Biasi warrants that the cast-iron sections and nipples  
of the BIASI 3WOOD boilers are free from defects in material and 5. Any damage associated with corrosion or leakage due to the  
workmanship for the lifetime of the original single family home  
installation. If the 3WOOD boiler block is then found to be  
defective, QHT and Biasi will replace the original cast iron boiler  
block.  
use of "non-barrier", plastic pipe in the heating system.  
*THIS WARRANTY DOES NOT EXTEND TO ANYONE EXCEPT  
THE FIRST PURCHASER AT RETAIL AND ONLY WHEN THE  
BOILER IS IN THE ORIGINAL INSTALLATION SITE.  
These warranties are subject to the condition that a heating  
*IMPLIED WARRANTIES OF FITNESS FOR A PARTICULAR  
contractor whose principal occupation is the sale and installation PURPOSE AND MERCHANTABILITY SHALL BE LIMITED TO  
of heating equipment must have installed the boiler.  
PARTS, WHICH ARE COVERED, consists of all materials  
supplied by Biasi, identified by QHT's part numbers in its  
literature. Other parts supplied in the casing, trim kit or in the  
burner pack carry their own warranty and each manufacturer has  
responsibility for its own products.  
THE DURATION OF THE EXPRESSED WARRANTY. BIASI  
AND QHT EXPRESSLY DISCLAIM AND EXCLUDE ANY  
LIABILITY FOR CONSEQUENTIAL OR INCIDENTAL DAMAGES  
FOR BREACH OF ANY EXPRESSED OR IMPLIED WARRANTY.  
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS, AND  
YOU MAY HAVE OTHER RIGHTS THAT VARY FROM STATE  
TO STATE.  
NOTE: ANY PART, WHICH IS REPLACED UNDER  
WARRANTY, CARRIES ONLY THE UNEXPIRED PORTION OF  
THE ORIGINAL WARRANTY.  
For prompt warranty service, notify the installer, who, in turn, will  
notify the distributor from whom he purchased the boiler. If this  
OWNER RESPONSIBILITIES:  
1. Provide for proper installation, which includes pressure relief does not result in corrective action, contact Biasi through Quincy  
and pressure reducing valves and high limit safety controls on Hydronic Technologies (Address Below) with details in support of  
closed systems.  
the warranty claim. All claims must be processed through proper  
2. Provide qualified periodic service to prolong proper operation trade channels. Contact with Biasi directly is not recommended for  
and service.  
rapid claim settlement.  
3. Insure that boiler is installed with approved burner and that  
installation conforms to all codes and ordinances.  
4. This warranty does not apply to boilers, which are subject to  
misuse, abuse, neglect, alteration, accident, excessive  
temperature, excessive pressure, or corrosive water or  
atmosphere.  
Quincy Hydronic Technologies,  
3560 Lafayette Rd.  
Portsmouth, NH, 03801  
Tel. (603) 334-6400  
5. Owner will be responsible for return of faulty components to  
QHT Inc. Portsmouth, NH, freight pre-paid.  
BIASI BOILER WARRANTY REGISTRATION  
IMPORTANT., Registration required. To gain complete warranty  
protection, fill in and mail this card immediately.  
PLACE  
STAMP  
HERE  
NAME  
STREET  
QHT Inc.  
3560 Lafayette Rd  
Portsmouth, NH 03801  
CITY  
STATE  
ZIP  
BOILER SERIAL NO.  
NAME OF INSTALL CO.  
STREET  
DATE OF INSTALL  
CITY  
STATE  
ZIP  
B10 BOILER SIZE (EX. 4 SECTION)  
SILVER RATINGS LABEL SERIAL #  
HOW DID YOU HEAR ABOUT BIASI?  
DEALER/INSTALLER  
OTHER  
WEBSITE  
FRIEND/NEIGHBOR  
For service please contact:  
QHT Inc.  
3560 Lafayette RD  
Portsmouth, NH 03801  
3 WOOD Boiler  
Manufactured by:  
Biasi S.p.A  
Telephone: 800-501-7697  
Fax: 603-334-6401  
Verona, Italy  

PYLE Audio View Series PLVSMN6 User Manual
Pioneer Car Stereo System DEH 600BT User Manual
Philips SJM3302H User Manual
Philips AW 7092 User Manual
Panasonic VDR D220 User Manual
Panasonic AJ D610WBp User Manual
O'Brien RELAX 3 2101518 User Manual
NEC Electronics America Calculator NDA 30103 004 User Manual
Metz Mecablitz 36 AF 3N User Manual
JVC LYT0873 001A User Manual