Munchkin Gas Fired Hot Water Boiler User Manual

• Installation  
• Startup  
• Maintenance  
• Parts  
Boiler  
Manual  
WARNING  
This manual must only be used by a qualified heating installer/service technician. Read all instructions  
in this manual before installing. Perform steps in the order given. Failure to comply could result in  
severe personal injury, death or substantial property damage.  
GAS-FIRED BOILER  
Boiler Manual  
CONTENTS (CONT’D)  
Part 8 – Gas Piping. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45-47  
A. Gas Connection  
B. Gas Piping  
C. Gas Table  
D. Dungs Gas Valve  
Part 9 – Field Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47-49  
A. Installation Must Comply With  
B. Field Wiring  
C. Line Voltage Wiring  
D. Thermostat  
Part 10 – Field Wiring – Vision 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50  
Part 11 – Start Up Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51-53  
A. Check/Control Water Chemistry  
B. Freeze Protection (when used)  
C. Fill and Test Water System  
D. Purge Air from Water System  
E. Check for Gas Leaks  
F. Check Thermostat Circuit(s)  
G. Condensate Removal  
H. Final Checks Before Starting Boiler  
Part 12 – Start-Up Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53-55  
A. Operating Instructions  
B. Adjusting the Set Point  
C. Status Menu  
D. Test Mode  
Part 13 – Start-Up Procedures With The Vision 1 Option . . . . . . . . . . . . . . . . . . . . . . 55-58  
A. Programming the Vision I Option  
B. Vision I Program Access  
C. Vision I Program Navigation  
Part 14 – Trouble Shooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59-61  
A. Munchkin Error Code  
B. Boiler Error  
C. Boiler Fault  
Part 15 – Maintenance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61-66  
A. Maintenance Procedures  
B. Combustion Chamber Coil Cleaning Instructions  
Part 16 – Boiler Inspection and Maintenance Start-Up Charts . . . . . . . . . . . . . . . . . . 67-69  
2
GAS-FIRED BOILER  
Boiler Manual  
PART 1: PRODUCT AND SAFETY INFORMATION  
SPECIAL ATTENTION BOXES  
The following defined terms are used throughout this manual to bring attention to the presence of  
hazards of various risk levels or to important information concerning the product.  
DEFINITIONS  
DANGER  
CAUTION  
DANGER indicates an imminently hazardous  
situation which, if not avoided, will result in  
death or serious injury.  
CAUTION Indicates a potentially hazardous  
situation which, if not avoided, may result in  
minor or moderate injury.  
WARNING  
CAUTION  
WARNING indicates a potentially hazardous  
situation which, if not avoided, could result in  
death or serious injury.  
CAUTION used without the safety alert symbol  
indicates a potentially hazardous situation which,  
if not avoided, may result in property damage.  
WARNING  
If the information in this manual is not followed exactly, a fire or explo-  
sion may result causing property damage, personal injury or loss of life.  
Do not store or use gasoline or other flammable vapors and  
liquids in the vicinity of this or any other appliance.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electrical switch: do not use any phone in  
your building.  
• Immediately call your gas supplier from a neighbor's phone.  
Follow the gas supplier's instructions.  
• If you cannot reach your gas supplier, call the fire department.  
Installation and service must be performed by a qualified  
installer, service agency or the gas supplier.  
NOTICE  
Heat Transfer Products, Inc., reserves the right to make product changes or updates without notice  
and will not be held liable for typographical errors in literature.  
3
GAS-FIRED BOILER  
Boiler Manual  
PART 1: PRODUCT AND SAFETY INFORMATION (CONT’D)  
supply at a location external to the appliance.  
WARNING  
Installer — Read all instructions in this manual,  
and Munchkin Venting section, before installing.  
Perform steps in the order given.  
Do not use this boiler if any part has been  
under water. Immediately call a qualified  
service technician to inspect the boiler and to  
replace any part of the control system and  
any gas control that has been under water.  
User — This manual is for use only by a  
qualified heating installer/service technician.  
Refer to User’s Information Manual for your  
reference.  
BOILER WATER  
If you have an old system with cast iron  
radiators, thoroughly flush the system (without  
boiler connected) to remove sediment. The  
high-efficiency heat exchanger can be damaged  
by build-up or corrosion due to sediment.  
User — Have this boiler serviced/inspected by  
a qualified service technician annually.  
Failure to comply with the above could result in  
severe personal injury, death or substantial  
property damage.  
Do not use petroleum-based cleaning or sealing  
compounds in boiler system. Gaskets and seals  
in the system may be damaged. This can result  
in substantial property damage.  
WARNING  
Failure to adhere to the guidelines on this page  
can result in severe personal injury, death or  
substantial property damage.  
Do not use “homemade cures” or “boiler patent  
medicines.” Substantial property damage,  
damage to boiler, and/or serious personal injury  
may result.  
Continual fresh make-up water will reduce boiler  
life. Mineral buildup in heat exchanger reduces  
heat transfer, overheats the stainless steel heat  
exchanger, and causes failure. Addition of  
oxygen carried in by make-up water can cause  
internal corrosion in system components. Leaks  
in boiler or piping must be repaired at once to  
prevent make-up water.  
WARNING  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Do not touch any electric switch; do not use  
any phone in your building.  
• Immediately call your gas supplier from a  
neighbor's phone. Follow the gas suppliers'  
instructions.  
FREEZE PROTECTION FLUIDS  
• If you cannot reach your gas supplier, call the  
fire department.  
CAUTION  
NEVER use automotive or standard glycol  
antifreeze, even ethylene glycol made for  
hydronic systems. Use only inhibited propylene  
glycol solutions, which are specifically  
formulated for hydronic systems. Ethylene  
glycol is toxic and can attack gaskets and seals  
used in hydronic systems.  
Before Installing  
WHEN SERVICING BOILER  
To avoid electric shock, disconnect electrical  
supply before performing maintenance.  
To avoid severe burns, allow boiler to cool  
before performing maintenance.  
BOILER OPERATION  
CAUTION  
Consider piping and installation when  
determining boiler location. Any claims for  
damage or shortage in shipment must be filed  
immediately against the transportation  
company by the consignee.  
Do not block flow of combustion or  
ventilation air to boiler.  
Should overheating occur or gas supply fail to  
shut off, do not turn off or disconnect electrical  
supply to circulator. Instead, shut off the gas  
4
GAS-FIRED BOILER  
Boiler Manual  
PART 2: HOW BOILER OPERATES  
Munchkin Condensing Technology is an intelli-  
gent system that delivers highly efficient hydron-  
ic heating, while maximizing efficiency by meas-  
uring the Data Parameters of your heating sys-  
tem.  
temperature and pressure.  
7. Control  
The integrated control system monitors the  
return and supply water and regulates the fan  
speed to regulate the unit’s BTU output. This  
allows the unit to only deliver the amount of  
heated energy required and nothing more!  
1. Stainless Steel Heat Exchanger  
The highly efficient durable Munchkin  
Stainless Steel Heat Exchanger is designed to  
take the colder return water from the system  
and extract the last bit of energy before it is  
exhausted. The heat exchanger design is  
separated by an internal baffle which diverts  
the exhaust gas through the primary heat  
exchanger into the secondary heat exchanger  
where the colder return water extracts the last  
residual heat.  
8. Burner  
Constructed of high grade stainless steel  
construction, the burner uses pre-mixed air  
and gas and provides a wide range of firing  
rates.  
9. Electrical field connections with terminal  
strips  
The electrical cover plate allows access the  
line voltage terminal strip and the low voltage  
terminal strip. Attach line voltage conduits to  
the three holes at the right of the line voltage  
terminal strip for power, CH pump and DHW  
pump. Route low voltage wires through the  
opening to the left of the low voltage terminal  
strip. (See Field Wiring Instructions Part 9.)  
2. Modulating Combustion System  
Modulation during the central heating  
operation is based on the supply temperature.  
The set point used for the control depends  
upon the programmed central heating curve.  
The slope of the heating curve can be changed  
by the installer of the Munchkin in the sense  
that both turning points of the curve can be  
moved. The control monitors the system to  
regulate the output of the burner during  
operation to match the system demand. This  
increase in efficiency allows for substantial fuel  
savings.  
10. Condensate drain connection  
This is a condensing high efficiency appliance,  
therefore this unit has a condensate removal  
system. Condensate is nothing more than  
water vapor, derived from the combustion  
products, similar to an automobile when it is  
initially started. It is very important that the  
condensate line is sloped away from the boiler  
and down to a suitable inside drain, if the  
condensate outlet on the Munchkin is lower  
than the drain, you must use a condensate  
removal pump (kit p/n 554200 available from  
Heat Transfer Products, Inc.) A condensate  
filter, if required by local authorities can be  
made up of lime crystals, marble or phosphate  
chips and will neutralize the condensate. This  
can be done in the field by the installer or you  
may purchase one from Heat Transfer  
Products, Inc. (P/N N1100). It is also very  
important that the condensate line is not  
exposed to freezing temperatures or any other  
type of blockage. Plastic tubing must be the  
only material used for the condensate line.  
Steel, brass, copper or others will be subject  
to corrosion or deterioration. A second vent  
may be necessary to prevent condensate line  
vacuum lock if a long horizontal run is used.  
3. Gas Valve  
The gas valve senses suction from the blower,  
allowing gas to flow only if the gas valve is  
powered and combustion air is flowing.  
4. Supply water temperature sensor  
This sensor monitors boiler output water  
temperature (system supply). The control  
module adjusts the boiler firing rate so the  
outlet temperature is correct.  
5. Return water temperature sensor  
This sensor monitors the return water  
temperature (system return). The control  
module reduces or increases boiler input,  
depending on how close the return water  
temperature is to the outlet water  
temperature.  
6. Temperature and pressure gauge  
Allows the user to monitor the systems  
5
GAS-FIRED BOILER  
Boiler Manual  
PART 2: HOW BOILER OPERATES (CONT’D)  
Also, an increase in pipe size may be  
necessary to drain properly. Support of the  
condensation line may be necessary to avoid  
blockage of the condensate flow.  
temperature for central heating and the other  
temperature to the Super Stor Ultra Indirect  
water heater. This allows the user to increase  
the temperature supplied to the Super Stor  
Ultra indirect water heater to get a fast  
recovery by prioritizing the flow at a higher  
temperature than may be needed for the  
central heating circuits (this will require two  
separate circulators). You must follow the  
piping, wiring and programming instructions  
located in the Vision One section of this  
manual. The Vision 1 kit consists of the  
following, which is included with your  
equipment  
11. Spark ignition  
The burner flame is ignited by applying a high  
voltage to the system spark electrode. This  
causes a spark from electrode to ground.  
12. The Vision 1 System  
The Vision I System will allow the installing  
contractor to take the highly efficient  
modulating Munchkin and make it even more  
efficient by controlling the temperature  
delivered to the central heating circuits based  
on the outside temperature. The Vision I  
system is also a two temperature system, one  
Outdoor sensor – 7250P-319  
Indirect tank sensor – 7250P-325  
PART 3: PREPARE BOILER LOCATION  
A. BOILER LOCATION SHOULD BE LEVEL  
CAUTION  
When preparing the boiler location, make sure the area where you are placing the boiler is level. In order  
for the condensate to flow to the location of the condensate hose, the boiler must be slightly pitched  
back to assure proper flow direction. The Munchkin Boiler comes equipped with leveling feet. Should  
you find the floor beneath the boiler is uneven, with a wrench, adjust the leveling feet so the boiler is  
pitched back at 1/8” per foot  
INCORRECT  
CORRECT  
6
GAS-FIRED BOILER  
Boiler Manual  
PERFORMANCE RATINGS  
CONNECTION SIZES  
FAN SPEEDS  
Supply/  
Gas  
Shipping  
Weight  
Vent  
Dia.  
Model Input Modulation  
DOE Heating  
AFUE  
*IBR  
Return Connection  
High  
Low  
Connection  
Size  
T50M  
T80M  
80M  
18,000 to 50,000 16,000 to 46,000 92% 58 lbs. 40,000 1 1/4" NPT  
19,000 to 80,000 17,000 to 74,000 92% 58 lbs. 64,000 1 1/4" NPT  
27,000 to 80,000 25,000 to 74,000 92% 75 lbs. 64,000 1 1/4" NPT  
3/4"  
3/4"  
2"  
2"  
3"  
3"  
3"  
4"  
3000  
4250  
3700  
3550  
4800  
5700  
1250  
1200  
1600  
1400  
1550  
1675  
3/4"  
140M 46,000 to 140,000 43,000 to 129,000 92% 101 lbs. 112,000 1 1/4" NPT  
199M 66,000 to 199,000 61,000 to 183,000 92% 111 lbs. 159,000 1 1/4" NPT  
399M 100,000 to 399,000 93,000 to 279,000 92% 252 lbs.  
3/4"  
3/4"  
1-1/4"  
N/A  
2" NPT  
DIMENSIONS  
T50M/T80M  
Figure 2-1  
7
GAS-FIRED BOILER  
Boiler Manual  
DIMENSIONS  
80M  
Figure 2-2  
140M/199M  
Figure 2-3  
8
GAS-FIRED BOILER  
Boiler Manual  
DIMENSIONS  
399M  
Figure 2-4  
PART 3: PREPARE BOILER LOCATION (CONTINUED)  
B. INSTALLATIONS MUST COMPLY WITH:  
C. BEFORE LOCATING THE BOILER  
Local, state, provincial, and national codes,  
laws, regulations and ordinances.  
1. Check for nearby connection to:  
System water piping  
National Fuel Gas Code, ANSI Z223.1 – latest  
edition.  
Venting connections  
Gas supply piping  
Electrical power  
Standard for Controls and Safety Devices for  
Automatically Fired Boilers, ANSI/ASME  
CSD-1, when required.  
2. Check area around boiler. Remove any  
combustible materials, gasoline and other  
flammable liquids.  
National Electrical Code.  
For Canada only: B149.1 or B149.2  
Installation Code, CSA C22.1 Canadian  
Electrical Code Part 1 and any local codes.  
WARNING  
Failure to keep boiler area clear and free of  
combustible materials, gasoline and other  
flammable liquids and vapors can result in  
severe personal injury, death or substantial  
property damage.  
NOTICE  
The Munchkin Boiler gas manifold and controls  
met safe lighting and other performance criteria  
when boiler underwent tests specified in ANSI  
Z21.13 — latest edition.  
3. The Munchkin gas control system components  
are protected from dripping or spraying water  
9
GAS-FIRED BOILER  
Boiler Manual  
PART 3: PREPARE BOILER LOCATION (CONTINUED)  
or rain during operation or service.  
WARNING  
4. If the Munchkin Boiler is to replace an  
The space must be provided with combus-  
tion/ventilation air openings correctly sized for  
all other appliances located in the same space as  
the Munchkin boiler. The boiler cover must be se-  
curely fastened to the boiler to prevent boiler  
from drawing air from inside the boiler room.  
This is particularly important if the boiler is lo-  
cated in the same room as other appliances.  
Failure to comply with the above warnings could  
result in severe personal injury, death or sub-  
stantial property damage.  
existing boiler, check for and correct any  
existing system problems such as:  
System leaks.  
Incorrectly-sized expansion tank.  
Lack of freeze protection in boiler water  
causing system and boiler to freeze and leak.  
Excessive glycol which will affect the  
boiler system operation.  
D. CLEARANCES FOR SERVICE ACCESS  
1. See Figure 3-1 for recommended service  
clearances. If you do not provide minimum  
clearances shown, it might not be possible to  
service the boiler without removing it from  
the space.  
E. RESIDENTIAL GARAGE INSTALLATION  
Precautions  
Take the following special precautions when  
installing the boiler in a residential garage. If the  
boiler is located in a residential garage, per ANSI  
Z223.1, paragraph 5.1.9:  
80M/140M/199M/399M  
Mount the boiler with a minimum of 18  
inches above the floor of the garage to the  
bottom of the boiler to ensure the burner and  
ignition devices will be no less than 18 inches  
above the floor.  
Locate or protect the boiler so it cannot be  
damaged by a moving vehicle.  
F. EXHAUST VENT AND INTAKE AIR VENT  
The Munchkin Boiler requires a special vent sys-  
tem, designed for pressurized venting.  
Munchkin Boilers are rated ANSI Z21.13  
Category IV (pressurized vent, likely to con-  
dense in the vent).  
T50M/T80M  
You must also install air intake piping from out-  
side to the boiler flue adaptor. The resultant  
installation is categorized as direct vent (sealed  
combustion). Note: To prevent combustion  
air contamination see Table 3-2 in this  
section when considering exhaust vent  
and intake air vent termination.  
Intake and exhaust must terminate near each  
other and may be vented vertically through the  
roof or out a side wall. The intake and exhuast  
venting methods are detailed in the Venting  
Section. Do not attempt to install the Munchkin  
Boiler using any other means. Be sure to locate  
the boiler such that the air intake and exhaust  
Figure 3-1: Clearances required  
10  
GAS-FIRED BOILER  
Boiler Manual  
PART 3: PREPARE BOILER LOCATION (CONTINUED)  
vent piping can be routed through the building  
and properly terminated. The air intake and  
exhaust vent piping lengths, routing and termi-  
nation method must all comply with the methods  
and limits given in the Venting section.  
H. WHEN REMOVING A BOILER FROM AN  
EXISTING COMMON VENT SYSTEM  
DANGER  
Do not install the Munchkin Boiler into a  
common vent with any other appliance. This  
will cause flue gas spillage or appliance  
malfunction, resulting in possible severe  
personal injury, death or substantial property  
damage.  
G. PREVENT COMBUSTION AIR CONTAMINATION  
Install intake air piping for the Munchkin Boiler  
as described in the Venting section. Do not ter-  
minate exhaust in locations that can allow con-  
tamination of intake air.  
WARNING  
WARNING  
You must pipe outside air to the boiler air  
intake. Ensure that the intake air will not  
contain any of the contaminants below.  
Contaminated air will damage the boiler,  
resulting in possible severe personal injury,  
death or substantial property damage. For  
example, do not pipe intake air vent near a  
swimming pool. Also avoid areas subject to  
exhaust fumes from laundry facilities. These  
areas will always contain contaminants.  
Failure to follow all instructions can result in  
flue gas spillage and carbon monoxide  
emissions, causing severe personal injury or  
death.  
At the time of removal of an existing boiler, the  
following steps shall be followed with each  
appliance remaining connected to the common  
venting system placed in operation, while the  
other appliances remaining connected to the  
common venting system are not in operation.  
Table 3-2: Corrosive contaminants and sources  
a. Seal any unused openings in the common  
venting system.  
Products to avoid  
Spray cans containing fluorocarbons  
Permanent wave solutions  
b. Visually inspect the venting system for  
proper size and horizontal pitch and  
determine there is non blockage or  
restriction, leakage, corrosion and other  
deficiencies which could cause an unsafe  
condition.  
Chlorinated waxes/cleaners  
Chlorine-based swimming pool chemicals  
Calcium chloride used for thawing  
Sodium chloride used for water softening  
Refrigerant leaks  
Paint or varnish removers  
Hydrochloric acid/muriatic acid  
Cements and glues  
Antistatic fabric softeners used in clothes dryers  
Chlorine-type bleaches, detergents, and cleaning  
solvents found in household laundry rooms  
Adhesives used to fasten building products and  
other similar products  
c. Insofar as is practical, close all building doors  
and windows and all doors between the  
space in which the appliances remaining  
connected to the common venting system  
are located and other spaces of the building.  
Turn on clothes dryers and any appliance not  
connected to the common venting system.  
Turn on any exhaust fans, such as range  
hoods and bathroom exhausts, so they will  
operate at maximum speed. Do not operate  
a summer exhaust fan. Close fireplace  
dampers.  
Areas likely to have contaminants  
Dry cleaning/laundry areas and establishments  
Swimming pools  
Metal fabrication plants  
Beauty shops  
Refrigeration repair shops  
Photo processing plants  
Auto body shops  
Plastic manufacturing plants  
Furniture refinishing areas and establishments  
New building construction  
Remodeling areas  
d. Place in operation the appliance being  
inspected. Follow the lighting instructions.  
Adjust thermostat so appliance will operate  
continuously.  
Garages and workshops  
e. Test for spillage at draft hood opening after 5  
11  
GAS-FIRED BOILER  
Boiler Manual  
PART 3: PREPARE BOILER LOCATION (CONTINUED)  
minutes of main burner operation. Use the  
flame of a match or candle, or smoke from a  
cigarette, cigar, or pipe.  
g. Any improper operation of common venting  
system should be corrected so the  
installation conforms with the National Fuel  
Gas Code, ANSI Z223.1 — latest edition.  
Correct by resizing to approach the minimum  
size as determined using the appropriate  
tables in Table 13 of NFPA54 ANSI Z223.1  
2006 of that code. Canadian installations  
must comply with B149.1 or B149.2  
Installation Code.  
f. After it has been determined that each  
appliance remaining connected to the  
common venting system properly vents  
when tested as outlined herein, return doors,  
windows, exhaust fans, fireplace dampers,  
and any other gas-burning appliance to their  
previous conditions of use.  
PART 4: PREPARE BOILER  
A. REMOVE BOILER FROM BOX  
CAUTION  
1. Prior to installing, care must be taken to place  
boiler in a safe location prior to installation on  
the wall to prevent damage to the mechanical  
connections.  
Cold weather handling — If boiler has been  
stored in a very cold location (below 0°F) before  
installation, handle with care until the plastic  
components come to room temperature.  
PART 5: BOILER PIPING  
A. RELIEF VALVE  
Connect discharge piping to safe disposal loca-  
tion, following guidelines in the WARNING below.  
WARNING  
To avoid water damage or scalding due to relief valve operation:  
• Discharge line must be connected to relief valve outlet and run to a safe place of disposal. Terminate the  
discharge line in a manner that will prevent possibility of severe burns or property damage should the valve  
discharge.  
• Discharge line must be as short as possible and be the same size as the valve discharge connection  
throughout its entire length.  
• Discharge line must pitch downward from the valve and terminate at least 6” above the floor drain where  
any discharge will be clearly visible.  
• The discharge line shall terminate plain, not threaded, with a material serviceable for temperatures of 375  
°F or greater.  
• Do not pipe the discharge to any place where freezing could occur.  
• No shutoff valve shall be installed between the relief valve and boiler, or in the discharge line. Do not plug  
or place any obstruction in the discharge line.  
Test the operation of the valve after filling and pressurizing system by lifting the lever. Make sure the valve  
discharges freely. If the valve fails to operate correctly, replace it with a new relief valve.  
• Failure to comply with the above guidelines could result in failure of the relief valve to operate, resulting in  
possibility of severe personal injury, death or substantial property damage.  
12  
GAS-FIRED BOILER  
Boiler Manual  
PART 5: BOILER PIPING (CONTINUED)  
and system water volume and temperature.  
Allow 3 gallons for boiler and its piping and  
4 gallons for the 399.  
B. GENERAL PIPING INFORMATION  
NOTICE  
The Munchkin Boiler control module uses  
temperature sensors to provide both high limit  
protection and modulating temperature control.  
The control module also provides low water  
protection by sensing the water pressure of the  
heat exchanger. Some codes/jurisdictions may  
require additional external controls for high  
limit and/or low water cutoff protection.  
CAUTION  
Undersized expansion tanks cause system  
water to be lost from relief valve and makeup  
water to be added through fill valve. Eventual  
boiler failure can result due to excessive make-  
up water addition.  
2. Expansion tank must be located as shown in  
Boiler Piping Part 5, or following recognized  
design methods. See tank manufacturer’s  
instructions for details.  
C. SEPARATE LOW WATER CUTOFF  
A low water cutoff may be required by state  
local code or some insurance companies. Check  
code requirements before installation of the  
Munchkin Boiler. It is also required that a low  
water cutoff be used if the boiler is installed  
above the piping level.  
3. Connect the expansion tank to the air  
separator only if the separator is on the  
suction side of the circulator. Always install  
the system fill connection at the same point  
as the expansion tank connection to the  
system.  
If required:  
• Use a low water cutoff designed for  
hydronic installations that is an electrode  
probe type  
• Install in a tee on the supply piping above  
the boiler  
• Follow low water cutoff manufacturer’s  
instructions  
4. Most chilled water systems are piped using a  
closed type expansion tank.  
Diaphragm (or bladder) expansion tank  
1. Always install an automatic air vent on top of  
the air separator to remove residual air from  
the system.  
D. BACKFLOW PREVENTER  
F. CIRCULATORS  
Use a backflow preventer specifically designed  
for hydronic boiler installations. This valve  
should be installed on the cold water fill supply  
line per local codes. (See piping details at the  
end of this section.)  
CAUTION  
DO NOT install automatic air vents on closed-  
type expansion tank systems. Air must remain  
in the system and return to the tank to provide  
its air cushion. An automatic air vent would  
cause air to leave system, resulting in water-  
logging the expansion tank.  
CAUTION  
All piping methods shown in this manual use  
primary/secondary connection to the boiler loop.  
This is to avoid the possibility of noise or actuator  
problems in zone valves because of the high-head  
boiler circulator. For other piping methods, consult  
your local Heat Transfer Products representative  
or refer to separate Munchkin Boiler piping details  
in this manual (Part 5).  
CAUTION  
DO NOT use the boiler circulator in any location  
other than the ones shown in this manual. The  
boiler circulator is selected to ensure adequate  
flow through the Munchkin Boiler. Failure to  
comply could result in unreliable performance  
and nuisance shut downs from insufficient flow.  
E. SYSTEM WATER PIPING METHODS  
Expansion tank and make-up water  
Sizing space heat system piping  
1. Ensure expansion tank size will handle boiler  
1. See Piping Details in this manual Part 5. In all  
13  
GAS-FIRED BOILER  
Boiler Manual  
PART 5: BOILER PIPING (CONTINUED)  
diagrams, the space heating system is  
isolated from the boiler loop by the  
primary/secondary connection.  
certain that the system fluid is checked for the  
correct glycol concentration and inhibitor level.  
The system should be tested at least once a year  
and as recommend by the producer of the glycol  
solution. Allowance should be made for the  
expansion of the glycol solution in the system  
piping. Example 50% by volume solution  
expands 4.8% in volume for the temperature  
increase from 32 F to 180 F, while water expands  
3% with the same temperature rise.  
2. Size the piping and components in the space  
heating system using recognized design  
methods.  
G. HYDRONIC PIPING WITH CIRCULATORS,  
ZONE VALVES AND MULTIPLE BOILERS  
The Munchkin Boiler is designed to function in a  
closed loop 15 PSI System. A factory installed  
water pressure switch will ensure that you have  
adequate pressure in the system. The Munchkin  
Boiler will not operate without a minimum of 10  
PSI water pressure. This assures you that if the  
system does have leak, the Munchkin Boiler will  
lock out (PRO on the display) before it damages  
the Stainless Steel Heat Exchanger. We have also  
included a Temperature and Pressure gauge  
which allows the user to monitor the system  
pressure and outlet temperature from the  
Munchkin Boiler. It is important to note that the  
Munchkin Boiler has a minimal amount of  
pressure drop and must be calculated when  
sizing the circulators. Each Munchkin Boiler  
installation must have an Air Elimination device  
that will remove air from the system. Install the  
Munchkin Boiler so the gas ignition system  
components are protected from water (dripping,  
spraying, etc.) allowing clearance for basic  
service of circulator replacement, valves and  
other. Observe minimum 1” clearance around all  
un-insulated hot water pipes when openings  
around pipes are not protected by non-  
combustible materials. On a Munchkin Boiler  
installed above radiation level, some states and  
local codes require a low water cut off device at  
the time of installation (See Part C this section). If  
the Munchkin Boiler supplies hot water to heating  
coils in air handler units, flow control valves or  
other devices must be installed to prevent gravity  
circulation of heater water in the coils during the  
cooling cycle. Chilled Water Medium must be  
piped in parallel with the heater. Freeze Protection  
for new or existing systems must use glycol that  
is specifically formulated for this purpose. It will  
include inhibitors that will prevent the glycol from  
attacking the metallic system components. Make  
Basic steps are listed below, with Illustration,  
which will guide you through the installation of  
the Munchkin.  
CAUTION  
The Munchkin Boiler should not be operated as  
a potable Hot Water Heater. It should not be  
used as a direct Hot Water Heating Device.  
1. Connect the system return marked “Heater In”.  
2. Connect the system supply marked “Heater Out”.  
3. Install Purge and Balance Valve or shut off  
valve and drain on system return to purge air  
out of each zone.  
4. Install a Back Flow preventor on the Cold Feed  
Make-Up Water line.  
5. Install a Pressure Reducing Valve on the Cold  
Feed Make-Up Water line, (15 PSI nominal on  
the system return). Check Temperature and  
Pressure Gauge which should read minimum  
pressure of 12 PSI.  
6. Install a circulator as shown in piping details  
(this section). Make sure the circulator is  
properly sized for the system and friction loss.  
7. Install an Expansion Tank on the system  
supply. Consult the tank manufacturer’s  
instruction for specific information relating to  
expansion tank installation. Size the expansion  
tank for the required system volume and  
capacity.  
8. Install an Air Elimination Device on the system  
supply.  
9. Install a drain valve at the lowest point of the  
system. Note: The Munchkin Boiler can not be  
drained completely of water without purging  
the unit with an air pressure 15 PSI.  
14  
GAS-FIRED BOILER  
Boiler Manual  
PART 5: BOILER PIPING (CONTINUED)  
10. The Safety Relief Valve is installed at the  
factory. Pipe the discharge of the safety relief  
valve to prevent injury in the event of pressure  
relief. Pipe the discharge 6” above the drain to  
a drain. Provide piping that is the same size as  
the safety relief valve outlet. Never block the  
outlet of safety relief valve.  
H. CIRCULATOR SIZING  
The Munchkin Boiler Heat Exchanger does have  
pressure drop which must be considered in  
your system design. Refer to the graph in Fig. 5-  
1 below for pressure drop through the  
Munchkin Boiler Heat Exchanger for recom-  
mended pump selection at a 20t design.  
Figure 5-1  
32  
30  
28  
26  
24  
22  
20  
18  
16  
14  
12  
10  
8
6
4
2
0
5
10  
15  
20  
25  
30  
35  
37.5  
40  
Flow in Gallons per Minute  
MUNCHKIN 399M  
* NOTE: The recommended circulators are based on 1 gpm per 10,000 btu/hr with 20°t.  
Figure 5-2  
CIRCULATOR SIZING CHART  
for Central Heating Circulator (P1)* and SuperStor Ultra Circulator (P2)*  
Taco  
Grundfos  
Bell & Gossett  
P1  
P1  
007  
0010  
0011  
1400-50  
P2  
009  
0011  
0013  
1400-50  
P1  
P2  
UPS15-58F SPD-3  
26-96F  
P2  
T50/T80/80M  
140M  
UPS15-58F SPD-2  
26-64F  
NRF-22  
NRF-33  
NRF-36  
PL-55  
NRF-22  
NRF-36  
NRF-36  
PL-55  
199M  
399M  
26-96F  
UPS 32-160  
26-96F  
UPS 32-160  
Note: SuperStor Ultra Indirect pump assumes the following: (6) 90 degree elbows and (1) tee on the run of 20' and 1" of copper tube size,  
but does not include any flow checks or zone valves.  
*See drawings on the following pages  
15  
GAS-FIRED BOILER  
Boiler Manual  
PART 5: BOILER PIPING (CONTINUED)  
The chart below represents the various system temperatures, their respective flows and friction loss  
through the Munchkin which will aid in circulator selection.  
SYSTEM TEMPERATURE RISE CHART  
20°t  
Flow  
G P M  
25°t  
Flow  
G P M  
30°t  
Flow  
G P M  
35°t  
Flow  
G P M  
40°t  
Flow  
G P M  
45°t  
Flow  
G P M  
Friction  
Feet  
Friction  
Feet  
Friction  
Feet  
Friction  
Feet  
Friction  
Feet  
Friction  
Feet  
Model  
T-50  
T-80  
80M  
140M  
199M  
399M  
6.5’  
7.8’  
7.8’  
11’  
17’  
21’  
5
8
8
14  
19  
39  
4.5’  
4.7’  
4.7’  
8’  
12.3’  
9’  
4
6.4  
6.4  
11.2  
15.2  
31.2  
3’  
2.9’  
2.9’  
6’  
8.5’  
7’  
3.3  
5.3  
5.3  
9.3  
12.6  
26  
2’  
2’  
2’  
4.75’  
5.75’  
6’  
2.5  
4.6  
4.6  
8
10.8  
22.3  
N/A  
1.5’  
1.5’  
3.75’  
4’  
N/R  
4
4
7
9.5  
19.5  
N/A  
1’  
1’  
2.5’  
2.5’  
4’  
N/R  
3.5  
3.5  
6.2  
8.4  
5’  
17.3  
N/R = Not Recommended  
N/A = Not Available  
Upon completion, make sure that the fill valve is  
in automatic position and each zone balance and  
purge or shut off is in an open position and zone  
valves are positioned for automatic operation.  
I. FILL AND PURGE HEATING SYSTEM  
Attach the hose to balance and purge hose  
connector or drain valve and run hose to  
nearest drain  
WARNING  
Close the other side of the balance and purge  
valve or the shut off valve after the drain.  
Use only inhibited propylene glycol solutions  
which are specially formulated for hydronic  
systems. Ethylene glycol is toxic and can attack  
gaskets and seals used in hydronic systems.  
Glycol mixtures should not exceed 50%.  
Open first zone balance and purge or drain  
valve to let water flow out the hose. If zone  
valves are used, open the valves one at a  
time manually. (Note: You should check valve  
manufacturer’s instruction prior to opening  
valves manually, so as not to damage the  
valve.)  
1. Glycol in hydronic applications which is  
specially formulated for this purpose includes  
inhibitors that prevent the glycol from  
attacking metallic system components. Make  
certain that the system fluid is checked for  
the correct glycol concentration and inhibitor  
level.  
Manually operate fill valve regulator. When  
water runs out of the hose, while it’s  
connected to the balance and purge valve or  
drain you will see a steady stream of water  
(without bubbles). Close balance and purge  
valve or drain to stop the water from flowing.  
Disconnect the hose and connect it to next  
zone to be purged.  
2. The glycol solution should be tested at least  
once a year and as recommended by the  
glycol manufacturer.  
Repeat this procedure for additional zones  
(one at time).  
3. Anti-freeze solutions expand more than  
water. For example a 50% by volume solution  
expands 4.8% in volume for a temperature  
increase from 32° F to 180° F, while water  
expands 3% with the same temperature rise.  
Allowances must be made for this expansion  
in the system design.  
CAUTION  
For installation that incorporates standing Iron  
Radiation and systems with manual vents at the  
high points. Follow above section and starting  
with the nearest manual air vent, open vent  
until water flows out, then close vent. Repeat  
procedure, working your way toward furthest  
air vent. It may be necessary to install a basket  
strainer in an older system where larger  
amounts of sediment may be present. Annual  
cleaning of the strainer may be necessary.  
4. A 30% mixture of glycol will result in a BTU  
output loss of 15% with a 5% increase in  
head against system circulator.  
5. A 50% mixture of glycol will result in a BTU  
output loss of 30% with a 50% increase in  
head against system circulator.  
16  
GAS-FIRED BOILER  
Boiler Manual  
PART 5: BOILER PIPING (CONTINUED)  
K. ZONING WITH CIRCULATORS  
CAUTION  
1. Connect boiler to system when circulator  
zoning as shown in 1C and 1D in Piping  
Details when zoning with circulators. The  
boiler circulator cannot be used for a zone. It  
must supply only the boiler loop.  
It is highly recommended that you carefully  
follow the glycol manufacturer’s recommended  
concentrations, expansion requirements and  
maintenance recommendations (pH additive  
breakdown, inhibitor reduction, etc.). You must  
carefully figure the additional friction loss in the  
system as well as the reduction in heat transfer  
co-efficients.  
2. Install a separate circulator for each zone.  
3. Connect DHW (domestic hot water) piping to  
indirect storage water heater as shown.  
J. ZONING WITH ZONE VALVES  
L. MULTIPLE BOILERS  
1. Connect boiler to system as shown in 2A and  
2B in Piping Details when zoning with zone  
valves. The primary/secondary piping shown  
ensures the boiler loop will have sufficient  
flow. It also avoids applying the high head of  
the boiler circulator to the zone valves.  
1. Connect multiple boilers as shown in 1E and  
1F in Piping Details.  
2. All piping shown is reverse return to assure  
balanced flow through the connected boilers.  
3. Each connected boiler must have its own  
circulator pump to assure adequate flow.  
2. Connect DHW (domestic hot water) piping to  
indirect storage water heater as shown.  
4. Connect DHW (domestic hot water) piping to  
indirect storage water heater as shown.  
17  
GAS-FIRED BOILER  
Boiler Manual  
M. BOILER PIPING DETAILS  
Piping Symbol Legend  
circulator  
pressure reducing valve  
diff. pressure bypass  
(w/ isolation flanges)  
circulator w/  
integral flow check)  
gate valve  
globe valve  
ball valve  
anti-scald rated  
mixing valve  
pressure gauge  
swing-check valve  
4-way motorized  
mixing valve  
flow-check valve  
spring-loaded check valve  
3-way motorized  
mixing valve  
Munchkin heater  
hose bib / boiler drain  
pressure relief valve  
backflow preventer  
thermostatic radiator valve  
TRV (straight)  
thermostatic radiator valve  
TRV (angle)  
float -type  
air vent  
circuit setter  
union  
manual 3-way valve  
heat exchanger  
zone valve  
air separator  
vacuum breaker  
Super Stor  
indirect DHW tank  
diaphragm-type  
expansion tank  
radiant manifold  
18  
GAS-FIRED BOILER  
Boiler Manual  
Standard Munchkin boiler  
Preferred piping (zoning with valves)  
Space heating mode  
Drawing 2A  
zone valves  
make-up water  
P2  
closely  
spaced  
tees  
differential  
pressure  
bypass  
valve  
purging  
valves  
V1  
OFF  
anti-scald  
mixing valve  
cold  
water  
P1  
T/P  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
1.  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure  
drop operates by itself.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler is 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
NOTE: For Vision piping applications, refer to the Vision Installation Piping Diagrams.  
19  
GAS-FIRED BOILER  
Boiler Manual  
Standard Munchkin boiler  
Preferred piping (zoning with valves)  
Domestic water heating mode  
Drawing 2B  
zone valves  
make-up water  
P2  
closely  
spaced  
tees  
differential  
pressure  
bypass  
valve  
purging  
valves  
V1  
anti-scald  
mixing valve  
cold  
water  
P1  
T/P  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
1.  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure  
drop operates by itself.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler is 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
NOTE: For Vision piping applications, refer to the Vision Installation Piping Diagrams.  
20  
GAS-FIRED BOILER  
Boiler Manual  
Standard Munchkin boiler  
Preferred piping (zoning with circulators)  
Space heating mode  
Drawing 2C  
space heating zone circuit  
zone  
circulators  
make-up water  
closely  
spaced  
tees  
purging  
valves  
anti-scald  
mixing valve  
P2  
cold  
water  
P1  
T/P  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
NOTE: For Vision piping applications, refer to the Vision Installation Piping Diagrams.  
21  
GAS-FIRED BOILER  
Boiler Manual  
Standard Munchkin boiler  
Preferred piping (zoning with circulators)  
Domestic water heating mode  
Drawing 2D  
space heating zone circuit  
zone  
circulators  
make-up water  
closely  
spaced  
tees  
purging  
valves  
anti-scald  
mixing valve  
P2  
cold  
water  
P1  
T/P  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
1.  
2.  
3.  
4.  
5.  
6.  
7.  
8.  
9.  
NOTE: For Vision piping applications, refer to the Vision Installation Piping Diagrams.  
22  
GAS-FIRED BOILER  
Boiler Manual  
Standard Munchkin boiler  
Preferred piping  
(multiple boilers / zoning with circulators)  
Space heating mode  
Drawing 2E  
space heating zone circuit  
zone  
circulators  
make-up water  
closely  
spaced  
tees  
purging  
valves  
anti-scald  
mixing valve  
cold  
water  
P2  
PB1  
PB2  
T/P  
T/P  
Super Stor  
indirect DHW tank  
Munchkin boiler  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
1.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
2.  
3.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M  
4.  
5.  
6.  
7.  
8.  
9.  
.
All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
NOTE: For Vision piping applications, refer to the Vision Installation Piping Diagrams.  
23  
GAS-FIRED BOILER  
Boiler Manual  
Standard Munchkin boiler  
Preferred piping  
(multiple boilers / zoning with circulators)  
Domestic water heating mode  
Drawing 2F  
space heating zone circuit  
zone  
circulators  
make-up water  
closely  
spaced  
tees  
purging  
valves  
anti-scald  
mixing valve  
cold  
water  
P2  
PB1  
PB2  
T/P  
T/P  
Super Stor  
indirect DHW tank  
Munchkin boiler  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
1.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
2.  
3.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M  
4.  
5.  
6.  
7.  
8.  
9.  
.
All pumps are shown with isolation flanges. The alternative is standard flanges with full port ball valves.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
NOTE: For Vision piping applications, refer to the Vision Installation Piping Diagrams.  
24  
GAS-FIRED BOILER  
Boiler Manual  
PART 6. BOILER PIPING WITH VISION I SYSTEM  
(DHW PRIORITY WITH OUTDOOR RESET)  
2. Connect the DHW circulator (P2) directly to  
the boiler as shown as shown in the piping  
details. The boiler circulator (P1) will shut  
down when there is a DHW demand.  
A. VISION I SYSTEM PIPING  
It is important that the system piping is done  
correctly when using the Vision 1 System.  
Follow the piping diagrams 2A through 3G when  
piping your Munchkin Boiler with Vision I. All  
general piping practices should still be main-  
tained.  
C. ZONING WITH CIRCULATORS USING VISION I  
1. Connect the boiler to the system as shown in  
piping details 4A through 4G.  
B. ZONING WITH ZONE VALVES USING VISION I  
2. Connect the DHW circulator (P2) directly to  
the boiler as shown in the piping details. The  
boiler circulator (P1) will shut down when  
there is a DHW demand.  
1. Connect the boiler to the system as shown in  
piping details 3A through 3C.  
25  
GAS-FIRED BOILER  
Boiler Manual  
D. BOILER PIPING DETAILS WITH THE VISION I SYSTEM  
Munchkin VISION 1 system  
(zoning with valves)  
Space heating mode  
Drawing 3A  
zone  
valves  
high limit safety  
make-up water  
purge  
differential  
pressure  
bypass  
valve  
anti-scald mixing valve  
cold  
water  
P1  
DHW  
temperature  
sensor  
outdoor  
temperature  
sensor  
OFF  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
1.  
2.  
3.  
4.  
5.  
6.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure  
drop operates by itself.  
7.  
8.  
9.  
10.  
26  
GAS-FIRED BOILER  
Boiler Manual  
Munchkin VISION 1 system  
(zoning with valves)  
Domestic water heating mode  
Drawing 3B  
zone  
valves  
high limit safety  
OFF  
make-up water  
purge  
differential  
pressure  
bypass  
valve  
anti-scald mixing valve  
cold  
water  
OFF  
DHW  
temperature  
sensor  
P1  
outdoor  
temperature  
sensor  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
1.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
2.  
3.  
4.  
5.  
6.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure  
drop operates by itself.  
7.  
8.  
9.  
10.  
27  
GAS-FIRED BOILER  
Boiler Manual  
Munchkin VISION 1 system  
(zoning with valves)  
Space heating mode (w/ submixing)  
Drawing 3C  
3-way  
(manually-set)  
mixing valve  
low temperature  
manifold station  
vent  
air handler  
high limit safety  
make-up water  
purge  
differential  
pressure  
bypass  
balancing  
valve  
valve  
anti-scald  
mixing valve  
cold  
water  
DHW  
temperature  
sensor  
P1  
outdoor  
temperature  
sensor  
OFF  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
1.  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
2.  
3.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M  
All pumps are shown with isolation flanges and integral flow check valves.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
4.  
5.  
6.  
.
7.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
Adjust differential pressure bypass valve to eliminate any flow velocity noise when zone with highest pressure  
drop operates by itself.  
8.  
9.  
10.  
Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.  
11.  
28  
GAS-FIRED BOILER  
Boiler Manual  
Munchkin VISION 1 system  
(zoning with circulators)  
Space heating mode  
Drawing 4A  
make-up water  
high limit safety  
zone  
circulators  
make-up water  
purge  
closely spaced tees  
anti-scald mixing valve  
cold  
water  
DHW  
temperature  
sensor  
P1  
outdoor  
temperature  
sensor  
OFF  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
1.  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
2.  
3.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
4.  
5.  
6.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
7.  
8.  
9.  
29  
GAS-FIRED BOILER  
Boiler Manual  
Munchkin VISION 1 system  
(zoning with circulators)  
Domestic water heating mode  
Drawing 4B  
zone  
circulators  
high limit safety  
make-up water  
purge  
closely spaced tees  
anti-scald mixing valve  
cold  
water  
OFF  
DHW  
temperature  
sensor  
P1  
outdoor  
temperature  
sensor  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
1.  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
2.  
3.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
4.  
5.  
6.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
7.  
8.  
9.  
30  
GAS-FIRED BOILER  
Boiler Manual  
Munchkin VISION 1 system  
(zoning with circulators)  
Space heating mode (w/ submixing)  
Drawing 4C  
3-way  
(manually-set)  
mixing valve  
vent  
air handler  
low temperature  
manifold station  
high limit safety  
make-up water  
purge  
balancing  
valve  
anti-scald mixing valve  
cold  
water  
DHW  
P1  
temperature  
outdoor  
temperature  
sensor  
sensor  
OFF  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
1.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
2.  
3.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
4.  
5.  
6.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.  
7.  
8.  
9.  
10.  
31  
GAS-FIRED BOILER  
Boiler Manual  
Munchkin VISION 1 system  
(zoning with circulators)  
Drawing 4E  
Space heating mode (3 fully reset supply temperatures)  
medium temperature  
manifold station  
vent  
air handler  
(higher temp.)  
vent  
high limit safety  
make-up water  
low temperature  
manifold station  
purge  
balancing  
valves  
3-way (manually-set) mixing valve  
anti-scald mixing valve  
cold  
water  
DHW  
temp.  
sensor  
P1  
outdoor  
temperature  
sensor  
OFF  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
1.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
2.  
3.  
4.  
5.  
6.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Do not use valve actuators on manifolds supplied by manually-set 3-way mixing valves.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
7.  
8.  
9.  
10.  
Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.  
32  
GAS-FIRED BOILER  
Boiler Manual  
Munchkin VISION 1 system  
(zoning with circulators)  
Drawing 4F  
Space heating mode (3 different supply temperatures)  
3-way manually-set  
mixing valve  
vent  
air handler  
(higher temp.)  
vent  
low temperature  
manifold station  
high limit safety  
variable  
speed  
make-up water  
injection  
mixing  
purge  
balancing  
valves  
medium  
temperature  
manifold station  
anti-scald  
mixing valve  
cold  
water  
purge  
DHW  
temp.  
sensor  
P1  
outdoor  
temperature  
sensor  
OFF  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin boiler  
NOTES:  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
1.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
2.  
3.  
4.  
5.  
6.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Follow all instructions for installation of injection mixing system.  
7.  
8.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
Adjust 3-way manually-set mixing valve to yield proper supply temperature to lower temperature load.  
9.  
10.  
33  
GAS-FIRED BOILER  
Boiler Manual  
Drawing 4G  
Munchkin VISION 1 system  
Multiple high temperature priority loads controlled with zone valves  
high temperature loads  
low temperature loads  
air handler  
make-up water  
high limit safety  
zone  
circulators  
air handler  
closely spaced tees  
purge  
multi-zone  
relay center  
anti-scald  
mixing valve  
OFF  
P1  
outdoor  
temperature  
sensor  
T/P  
P2  
purge  
differential pressure  
bypass valve  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin heater  
NOTES:  
This drawing is meant to show system piping concept only.  
Installer is responsible for all equipment & detailing required by local codes.  
1.  
2.  
3.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
4.  
5.  
6.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
7.  
8.  
9.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
High temperature loads cannot operate simultaneously with low temperature loads.  
Supply water temperature to high temperature loads is not reset based on outdoor temperature.  
Domestic water heating is highest priority load, and controlled through priority zone of multi-zone relay center  
10.  
11.  
12.  
34  
GAS-FIRED BOILER  
Boiler Manual  
Drawing 4H  
Munchkin VISION 1 system  
Multiple high temperature priority loads  
controlled with zone circulators  
Multiple low temperature load controls with zone circulators  
high temperature loads  
low temperature loads  
air handler  
make-up water  
high limit safety  
zone  
circulators  
air handler  
closely spaced tees  
purge  
multi-zone  
relay center  
anti-scald  
mixing valve  
OFF  
P1  
outdoor  
temperature  
sensor  
T/P  
P2  
purge  
thermal trap  
(w/ drain plug)  
Super Stor  
indirect DHW tank  
Munchkin heater  
NOTES:  
This drawing is meant to show system piping concept only.  
1.  
Installer is responsible for all equipment & detailing required by local codes.  
All closely spaced tees shall be within 4 pipe diameter center to center spacing.  
2.  
3.  
A minimum of 6 pipe diameters of straight pipe shall be installed upstream and downstream  
of all closely spaced tees.  
The minimum pipe size for connecting a Super Stor water heater is 1 inch.  
4.  
5.  
6.  
The minimum pipe size for connecting a Munchkin boiler shall be 1.25 inches and 2 inches for the 399M.  
All pumps are shown with isolation flanges and integral flow check valves.  
The alternative is standard flanges with full port ball valves and a separate flow check valve.  
The anti-scald mixing valve is recommended if the DHW temperature is set above the factory setting of 119˚F.  
Install a minimum of 12 diameters of straight pipe upstream of all circulators.  
7.  
8.  
9.  
A purging valve may be used in lieu of the ball valve / hose bib combination shown.  
High temperature loads cannot operate simultaneously with low temperature loads.  
Supply water temperature to high temperature loads is not reset based on outdoor temperature.  
Domestic water heating is highest priority load, and controlled through priority zone of multi-zone relay center  
10.  
11.  
12.  
35  
GAS-FIRED BOILER  
Boiler Manual  
PART 7: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL  
b. Non Foam Core CPVC (Chlorinated  
DANGER  
Polyvinyl Chloride) Pipe conforming to  
ASTM D-1785.  
Munchkin Boiler must be vented as detailed in  
Venting section Part 7. Ensure the exhaust and  
intake piping comply with these instructions  
regarding vent system.  
Inspect finished combustion air intake and  
exhaust piping thoroughly to ensure all joints  
are well secured and airtight and comply with  
all applicable code requirements, as well as  
with the instructions provided in this manual.  
Failure to provide a properly installed vent  
system will cause severe personal injury or  
death.  
c. Non Foam Core ABS (Acrylonitrile-  
Butadiene- Styrene) Pipe conforming to  
ASTM D3965 Class 3-2-2-2-2.  
WARNING  
Do not use Foam Core Pipe in any portion of the  
exhaust piping from this boiler. Use of Foam  
Core Pipe may result in severe personal injury,  
death, or substantial property damage.  
2. Cellular foam core piping may be used on air  
inlet piping only. Never use cellular foam core  
material for exhaust vent piping.  
A. INSTALLING EXHAUST VENT AND  
INTAKE AIR VENT  
D. EXHAUST VENT AND INTAKE AIR VENT  
PIPE LOCATION  
WARNING  
This vent system will operate with a positive  
pressure in the pipe. Do not connect vent  
connectors serving appliances vented by natural  
draft into any portion of mechanical draft  
systems operating under positive pressure.  
Follow the venting instructions below carefully.  
Failure to do so may result in severe personal  
injury, death, or substantial property damage.  
WARNING  
Both exhaust and intake air vents must exit  
from the same side of the building to assure  
correct appliance operation.  
1. Determine exhaust vent location:  
a. The vent piping for this boiler is approved  
for zero clearance to combustible  
construction.  
B. GENERAL  
1. Install the boiler venting system in  
accordance with these instructions and with  
the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54, CAN/CGA B149, and/or  
applicable provisions of local building codes.  
b. See illustration within this section of  
clearances for location of exit terminals of  
direct-vent venting systems.  
c. This boiler vent system shall terminate at  
least 3 feet (0.9 m) above any forced air  
intake located within 10 ft (3 m). Note:  
this does not apply to the combustion air  
intake of a direct-vent appliance.  
2. This boiler is a direct vent appliance and is  
listed as a Category IV appliance with  
Underwriters Laboratories, Inc. VENT AND  
INTAKE AIR PIPE  
d. Provide a minimum of 1 foot distance  
from any door, operable window, or  
gravity intake into any building.  
C. APPROVED MATERIALS FOR EXHAUST  
VENT AND INTAKE AIR VENT  
1. Use only Non Foam Core venting material.  
The following materials are approved for use  
as vent pipe for this boiler:  
e. Provide a minimum of 1 foot clearance  
from the bottom of the exhaust above the  
expected snow accumulation level. Snow  
removal may be necessary to maintain  
clearance.  
a. Non Foam Core PVC (Polyvinyl Chloride)  
Pipe conforming to ASTM D-1785.  
36  
GAS-FIRED BOILER  
Boiler Manual  
PART 7: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)  
f. Provide 4 feet horizontal clearance from  
electrical meters, gas meters, gas  
regulators and relief equipment. In no  
case shall the exit terminal be above or  
below the aforementioned equipment  
unless the 4 foot horizontal distance is  
maintained.  
2. Determine air intake vent location.  
a. Provide 1 foot clearance from the bottom  
of the intake air vent and the level of  
maximum snow accumulation. Snow  
removal may be necessary to maintain  
clearances.  
b. Do not locate intake air vent in a parking  
area where machinery may damage the  
pipe.  
g. Do not locate the exhaust over public  
walkways where condensate could drip  
and/or freeze and create a nuisance or  
hazard.  
c. When venting with a two pipe system,  
maximum distance between intake air  
vent and exhaust vent is 6 feet (1.8 m).  
Minimum distance between exhaust vent  
and intake air vent on single boiler is 8”  
(0.2 m) center-to-center. Minimum  
distance between exhaust vents and  
intake air vents on multiple boilers is 8”  
(0.2 m) center-to-center.  
h. When adjacent to a public walkway,  
locate exit terminal at least 7 feet above  
grade.  
i. Do not locate the exhaust directly under  
roof overhangs to prevent icicles from  
forming.  
j. Provide 4 feet clearance from the inside  
corner of vertical walls, chimneys, etc., as  
well as horizontal corners created by roof  
overhangs.  
37  
GAS-FIRED BOILER  
Boiler Manual  
Location of exit terminals of mechanical draft and direct-vent venting systems.  
(Reference: National Fuel Gas Code ANSI Z223.1/NFPA 54 2002).  
Fig. 7-1  
Fig. 7-2 Multiple Vent Spacing*  
*Note: Exhaust must extend out 1 foot  
Figure 7-4 Multiple Boiler Installations  
Fig. 7-3 Multiple Stainless Steel Horizontal Vent Kit Installation – Front View  
38  
GAS-FIRED BOILER  
Boiler Manual  
PART 7: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)  
d. Effort should be made to keep a  
minimum difference in equivalent length  
between the intake air vent pipe and the  
exhaust vent.  
E. EXHAUST VENT AND INTAKE AIR VENT  
SIZING  
1. The exhaust vent and intake air vent pipes  
should be 2" for the T50/T80, 3" for the  
80M/140M/199M and 4" for the 399M.  
3. The minimum combined equivalent length is  
16 equivalent feet.  
2. The total combined equivalent length of  
exhaust vent and intake air pipe should not  
exceed 85 feet.  
F. LONGER VENT RUNS  
1. The maximum combined equivalent length  
can be extended by increasing the diameter  
of both exhaust vent and intake air vent pipe  
equally. However, the transitions should  
begin a minimum of 15 equivalent feet from  
the boiler.  
a. The equivalent length of elbows, tees,  
and other fittings are listed in the Friction  
Loss Table 7.5.  
Table 7.5  
FRICTION LOSS EQUIVALENT IN PIPING AND FITTINGS  
a. The maximum equivalent length for the  
increased diameter vent pipes is 125 feet.  
FITTINGS OR PIPING  
EQUIVALENT FEET  
6"  
3'  
2"  
5'  
3"  
5'  
4"  
3'  
b. Transitions should always be made in  
vertical sections of pipe to prevent the  
condensate from pooling in the vent  
pipe.  
90 DEGREE ELBOW*  
45 DEGREE ELBOW  
COUPLING  
1'  
3'  
3'  
1'  
0'  
0'  
0'  
0'  
Table 7.6: Vent Run Transition  
0'  
AIR INLET TEE  
0'  
0'  
0'  
Vent  
Reducing  
Coupling  
Vent  
1'  
STRAIGHT PIPE  
1'  
1'  
1'  
Connection  
Transition  
N/A  
N/A  
1'  
CONCENTRIC VENT KIT  
V500 2" VENT KIT  
V1000 3" VENT KIT  
V2000 4" VENT KIT  
3'  
3'  
N/A  
N/A  
1'  
2"  
3"  
4"  
3" x 2"  
4" x 3"  
6" x 4"  
3"  
4"  
6"  
1'  
N/A  
1'  
N/A  
N/A  
1'  
1'  
1'  
c. If the transition occurs at a distance  
greater than 15 equivalent feet from the  
boiler, the maximum equivalent length  
will be reduced. See Table 7.7.  
*Friction loss for long radius elbow is 1 foot less.  
b. For example: If the exhaust vent has two  
90° elbows and 10 feet of PVC pipe we  
will calculate:  
Table 7.7: Vent Termination Kits  
Transition  
Point  
TEL of  
Standard  
2" Vent  
TEL of  
Exhaust Vent Pipe Equivalent Length = (2x5)+10=20 feet  
Maximum  
TEL of all  
Oversized  
2", 3" or 4"  
Vent Pipe (ft)  
(ft from  
boiler)  
Further, if the intake air vent pipe has two  
90° elbows, one 45° elbow and 10 feet of  
PVC pipe, the following calculation  
applies:  
Vent Pipe (ft)  
Pipe (ft)  
15  
20  
30  
40  
50  
60  
70  
80  
85  
95  
77-1/2  
60-1/2  
43  
125  
117-1/2  
110-1/2  
103  
25  
Intake Air Vent Pipe Equivalent Length = (2x5)+3+10=23 feet  
30  
Finally, if a concentric vent kit is used we  
find:  
35  
26  
96  
40  
8-1/2  
0
88-1/2  
85  
Total Combined Equivalent Length = 20+23+3=46 feet  
None  
Therefore, the total combined equivalent  
length is 46 feet which is well below the  
maximum of 85 feet.  
TEL = Total Equivalent Length  
G. EXHAUST VENT AND INTAKE AIR PIPE  
INSTALLATION  
c. The intake air vent pipe and the exhaust  
vent are intended to penetrate the same  
wall or roof of the building.  
1. Use only solid PVC, CPVC, or ABS schedule  
39  
GAS-FIRED BOILER  
Boiler Manual  
PART 7: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)  
40 or 80 pipe. FOAM CORE PIPING IS NOT  
APPROVED.  
G. HEATER REMOVAL FROM A COMMON  
VENT SYSTEM  
2. Remove all burrs and debris from joints and  
fittings.  
At the time of removal of an existing heater, the  
following steps shall be followed with each  
appliance remaining connected to the common  
venting system placed in operation, while the  
other appliances remaining connected to com-  
mon venting system are not operating.  
3. All joints must be properly cleaned, primed,  
and cemented. Use only cement and primer  
approved for use with the pipe material.  
Cement must conform to ASTM D2564 for  
PVC or CPVC pipe and ASTM D2235 for ABS  
pipe.  
1. Seal any unused openings in the common  
venting system.  
WARNING  
All joints of positive pressure vent systems  
must be sealed completely to prevent leakage  
of flue products into the living space.  
2. Visually inspect the venting system for proper  
size and horizontal pitch to determine if there  
is blockage, leakage, corrosion or other defi-  
ciencies that could cause an unsafe condition.  
3. If practical, close all building doors, windows  
and all doors between the space in which the  
appliance remains connected to the common  
venting system located and other spaces in  
the building. Turn on clothes dryers and any  
appliances not connected to the common  
venting system. Turn on any exhaust fans,  
such as range hoods and bathroom exhausts,  
at maximum speed. Do not operate a summer  
exhaust fan. Close all fireplace dampers.  
4. Horizontal lengths of exhaust vent must slope  
back towards the boiler not less than ¼" per  
foot to allow condensate to drain from the  
vent pipe. If the exhaust pipe must be piped  
around an obstacle that results in the creation  
of a low point, condensate will collect in this  
low point and form a blockage. This  
condensate must be drained away using a  
field-installed condensate drain assembly as  
shown.  
4. Place in operation the appliance being  
inspected. Follow the lighting instructions.  
Adjust the thermostat so the appliance will  
operate continuously.  
5. All piping must be fully supported. Use pipe  
hangers at a minimum of 4 foot intervals to  
prevent sagging of the pipe where  
condensate may form.  
5. Test for spillage at the draft hood relief  
opening after 5 minutes of main burner  
operation. Use the flame of a match or candle  
or smoke from a cigarette.  
6. Do not use the boiler to support any piping.  
7. A screened straight coupling is provided with  
the boiler for use as an outside exhaust  
termination.  
6. After it has been determined that each  
appliance remaining connected to common  
venting system properly vents when tested as  
outlined, return doors, windows, exhaust fans,  
fireplace dampers and any other gas burning  
appliance to their previous condition of use.  
8. A screened inlet air tee is provided with the  
boiler to be used as an outside intake  
termination.  
9. The following information on Table 7.7 are  
optional intake air/exhaust vent terminations  
available from Heat Transfer Products, Inc.  
7. Any improper operation of the common  
venting system should be corrected so the  
installation conforms with the National Fuel  
Gas Code, ANSI Z223.1. When resizing any  
portion of the common venting system, the  
common venting system should be resized to  
approach the minimum size as determined  
using the appropriate tables in Appendix G in  
the National Fuel Gas Code , ANSI Z 223.1  
Table 7.8: Vent Termination Kits  
Description  
Stock Code  
2" PVC Concentric Vent Termination Kit  
3" PVC Concentric Vent Termination Kit  
2" Stainless Steel Vent Termination Kit  
3" Stainless Steel Vent Termination Kit  
4" Stainless Steel Vent Termination Kit  
KGAVT0501CVT  
KGAVT0601CVT  
V500  
V1000  
V2000  
40  
GAS-FIRED BOILER  
Boiler Manual  
PART 7: VENTING, COMBUSTION AIR & CONDENSATE REMOVAL (CONTINUED)  
I. CONDENSATE REMOVAL SYSTEM  
CAUTION  
This is a condensing high efficiency appliance,  
therefore this unit has a condensate removal  
system. Condensate is nothing more than water  
vapor, derived from the combustion products,  
similar to an automobile when it is initially start-  
ed. It is very important that the condensate line  
is sloped away from the boiler and down to a  
suitable inside drain, if the condensate outlet on  
the Munchkin Boiler is lower than the drain, you  
must use a condensate removal pump (kit P/N  
554200 available from Heat Transfer Products,  
Inc.) A condensate filter, if required by local  
authorities can be made up of lime crystals,  
marble or phosphate chips will neutralize the  
condensate. This can be done in the field by the  
installer or you may purchase one from Heat  
Transfer Products, Inc. (P/N N1100) It is also very  
important that the condensate line is not  
exposed to freezing temperatures, or any other  
type of blockage. Plastic tubing must be the only  
material used for the condensate line. Steel,  
brass, copper or others will be subject to corro-  
sion or deterioration. A second vent may be  
necessary to prevent condensate line vacuum  
lock if a long horizontal run is used. Also, an  
increase in pipe size may be necessary to drain  
properly. Support of the condensation line may  
be necessary to avoid blockage of the conden-  
sate flow.  
The condensate line must remain unobstructed,  
allowing free flow of condensate. If condensate  
is allowed to freeze in the line or if the line is  
obstructed in any other manor, condensate can  
exit from the boiler tee, resulting in potential  
water damage to property.  
NOTICE  
Use materials approved by the authority having  
jurisdiction. In the absence of other authority,  
PVC and CPVC pipe must comply with ASTM  
D1785, F441 or D2665. Cement and primer must  
comply with ASTM D2564 or F493. For Canada,  
use CSA or ULC certified PVC or CPVC pipe,  
fittings and cement.  
When installing a condensate pump, select one  
approved for use with condensing boilers and  
furnaces. The pump should have an overflow  
switch to prevent property damage from  
condensate spillage.  
Condensate from the Munchkin Boiler will be  
slightly acidic (typically with a pH from 3.2 to  
4.5). Install a neutralizing filter if required by  
local codes.  
41  
GAS-FIRED BOILER  
Boiler Manual  
J. DIAGRAMS FOR SIDEWALL VENTING  
SIDEWALL VENTING WITH TEE (INTAKE)  
AND COUPLING (EXHAUST)  
SIDEWALL VENTING WITH TEE (INTAKE)  
AND COUPLING (EXHAUST)  
INTAKE AIR  
VENT  
INTAKE AIR  
VENT  
1" MIN.  
TEE  
TEE  
STRAIGHT  
COUPLING  
12" MIN.  
TOP VIEW  
EXTERIOR WALL  
EXHAUST  
VENT  
STRAIGHT  
COUPLING  
EXHAUST  
VENT  
TOP VIEW  
1" MIN.  
12" MIN.  
1" MIN.  
12" MIN.  
SUPPORT BRACKETS  
MUST BE USED ON  
STRAIGHT  
COUPLING  
ALL HORIZONTAL  
TEE  
AND VERTICAL PIPING  
SUPPORT BRACKETS  
STRAIGHT  
COUPLING  
MUST BE USED ON  
ALL HORIZONTAL  
INTAKE AIR  
VENT  
AND VERTICAL PIPING  
TEE  
RIGHT SIDE VIEW  
EXTERIOR WALL  
EXHAUST  
VENT  
RIGHT SIDE  
VIEW  
EXTERIOR WALL  
Figure 7-9  
Figure 7-10  
GENERAL NOTE: All vent pipes must be glued, properly supported and the exhaust must be pitched a  
minimum of a ¼" per foot back to the heater (to allow drainage of condensate).  
NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the  
appliance and the balance at 4 foot invervals on the vent pipe. The boiler venting must be readily  
accessible for visual inspection for the first three feet from the boiler.  
42  
GAS-FIRED BOILER  
Boiler Manual  
SIDWALL VENTING WITH KIT  
SIDEWALL VENTING WITH  
CONCENTRIC VENT KIT  
INTAKE AIR  
VENT  
VENT KIT  
SUPPORT BRACKETS  
MUST BE USED ON  
ALL HORIZONTAL  
AND VERTICAL PIPING  
NOTE: INTAKE LEG  
MUST BE FACING UP  
1" MIN.  
TOP VIEW  
EXHAUST  
VENT  
VENT KIT  
INTAKE AIR  
VENT  
NOTE: EXTENDED VENT  
RUNS WHEN TRANSITIONING  
TO A LARGER DIAMETER  
MUST ALWAYS TAKE PLACE  
IN A VERTICAL POSITION  
TO PREVENT CONDENSATE  
BLOCKAGE.  
EXHAUST  
VENT  
SUPPORT BRACKETS  
MUST BE USED ON  
ALL HORIZONTAL  
AND VERTICAL PIPING  
RIGHT SIDE VIEW  
EXTERIOR WALL  
SIDEWALL VENTING WITH  
CONCENTRIC VENT KIT  
RIGHT SIDE  
VIEW  
SUPPORT BRACKETS  
MUST BE USED ON  
EXTERIOR WALL  
1" MIN.  
ALL HORIZONTAL  
NOTE: INTAKE LEG  
MUST BE FACING UP  
AND VERTICAL PIPING  
SIDEWALL VENTING WITH KIT  
INTAKE AIR  
VENT  
EXHAUST  
VENT  
VENT KIT  
INTAKE AIR  
VENT  
EXHAUST  
VENT  
SUPPORT BRACKETS  
MUST BE USED ON  
ALL HORIZONTAL  
AND VERTICAL PIPING  
FRONT VIEW  
EXTERIOR WALL  
RIGHT SIDE VIEW  
EXTERIOR WALL  
Figure 7-11  
Figure 7-12  
NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the  
appliance and the balance at 4 foot invervals on the vent pipe. The boiler venting must be readily  
accessible for visual inspection for the first three feet from the boiler.  
GENERAL NOTE: All vent pipes must be glued, properly supported and the exhaust must be pitched a  
minimum of a ¼" per foot back to the heater (to allow drainage of condensate).  
43  
GAS-FIRED BOILER  
Boiler Manual  
K. DIAGRAMS FOR VERTICAL VENTING  
ROOF VENT WITH TEE (INTAKE)  
AND COUPLING (EXHAUST)  
ROOF VENT WITH  
CONCENTRIC VENT KIT  
10'-0" MIN.  
STRAIGHT  
COUPLING  
24" MIN.  
10'-0" MIN.  
TEE  
12" OVER MAXIMUM  
SNOW LEVEL OR 24"  
WHICHER IS GREATER  
12" OVER MAXIMUM  
SNOW LEVEL OR 24"  
WHICHEVER IS GREATER  
SUPPORT BRACKETS  
MUST BE USED ON  
ALL HORIZONTAL  
AND VERTICAL PIPING  
SUPPORT BRACKETS  
MUST BE USED ON  
ALL HORIZONTAL  
AND VERTICAL PIPING  
INTAKE AIR  
VENT  
EXHAUST  
VENT  
INTAKE AIR  
VENT  
RIGHT SIDE VIEW  
EXTERIOR WALL  
RIGHT SIDE VIEW  
EXTERIOR WALL  
ROOF VENT WITH  
EXHAUST  
VENT  
CONCENTRIC VENT KIT  
ROOF VENT WITH TEE (INTAKE)  
AND COUPLING (EXHAUST)  
10'-0" MIN.  
EXHAUST VENT  
(STRAIGHT  
COUPLING)  
24" MIN.  
10'-0" MIN.  
12" OVER MAXIMUM  
SNOW LEVEL OR 24"  
WHICHEVER IS GREATER  
12" OVER MAXIMUM  
SNOW LEVEL OR 24"  
WHICHEVER IS GREATER  
INTAKE AIR  
VENT  
(TEE)  
SUPPORT BRACKETS  
MUST BE USED ON  
ALL HORIZONTAL  
AND VERTICAL PIPING  
SUPPORT BRACKETS  
MUST BE USED ON  
ALL HORIZONTAL  
AND VERTICAL PIPING  
RIGHT SIDE  
VIEW  
RIGHT SIDE  
VIEW  
EXTERIOR WALL  
EXTERIOR WALL  
Figure 7-13  
Figure 7-14  
NOTE: When placing support brackets on vent piping, the first bracket must be within 1 foot of the  
appliance and the balance at 4 foot invervals on the vent pipe. The boiler venting must be readily  
accessible for visual inspection for the first three feet from the boiler.  
GENERAL NOTE: All vent pipes must be glued, properly supported and the exhaust must be pitched a  
minimum of a ¼" per foot back to the heater (to allow drainage of condensate).  
44  
GAS-FIRED BOILER  
Boiler Manual  
PART 8: GAS PIPING  
accordance with state and local  
requirements.  
WARNING  
Failure to follow all precautions could result in  
fire, explosion or death!  
C. GAS TABLE  
Refer to Table 8.1 to size the supply piping to  
minimize pressure drop between meter or  
regulator and unit.  
A. GAS CONNECTION  
The gas supply shall have a maximum inlet  
pressure of less than 14" water column (350  
mm), ½ pound pressure (3.5 kPa), and a mini-  
mum of 3.5" water column. The entire piping  
system, gas meter and regulator must be sized  
properly to prevent pressure drop greater than  
0.5" as stated in the National Fuel Gas Code. This  
information is listed on the rating plate.  
Maximum Capacity of Pipe in Cubic Feet of Gas  
per Hour for Gas Pressures of 0.5 psi or Less and  
a Pressure Drop of 0.3 Inch water Column  
Table 8-1 (Based on a 0.60 Specific Gravity Gas)  
Nominal  
Iron Pipe Internal  
Length of Pipe (Feet)  
Size  
Diameter  
(inches) (inches) 10 20 30 40 50 60 70  
WARNING  
3/4  
1
.824  
1.049  
278 190 152 130 115 105 96 BTU'S  
520 350 285 245 215 195 180 PER  
It is very important that you are connected to  
the type of gas as noted on the rating plate. "LP"  
for liquefied petroleum, propane gas or, "Nat"  
natural or city gas. All gas connections must be  
approved by the local gas supplier, or utility in  
addition to the governing authority, prior to  
turning the gas supply on.  
1 1/4  
1 1/2  
1.380 1,050 730 590 500 440 400 370 HOUR  
1.610 1,600 1,100 890 760 670 610 560 x1,000  
}
80 90 100 125 150 175 200  
3/4  
1
1 1/4  
1 1/2  
.824  
90 84 79 72 64 59 55 BTU'S  
170 160 150 130 120 110 100 PER  
1.049  
1.380  
1.610  
350 320 305 275 250 225 210 HOUR  
}
The nipple provided is ½" with a factory installed  
3/4" bell reducer. Do not remove this ¾" x ½" bell  
reducer! It is mandatory that this fitting is used  
for connection to a field fabricated drip leg as  
shown in the illustration above per the National  
Fuel Gas Code. You must ensure that the entire  
gas line to the connection at the Munchkin is no  
smaller than ¾". Once all the inspections have  
been performed, the piping must be leak tested.  
If the leak test requirement is a higher test pres-  
sure than the maximum inlet pressure, you must  
isolate the Munchkin from the gas line. In order  
to do this, you must shut the gas off using fac-  
tory and field-installed gas cocks. This will pre-  
vent high pressure. Failure to do so may dam-  
age the gas valve. In the event the gas valve is  
exposed to a pressure greater than ½ PSI, 14"  
water column, the gas valve must be replaced.  
Never use an open flame (match, lighter, etc.) to  
check gas connections.  
530 490 460 410 380 350 320 x1,000  
It is recommended that a soapy solution be used  
to detect leaks. Bubbles will appear on the pipe to  
indicate a leak is present. The gas piping must be  
sized for the proper flow and length of pipe, to  
avoid pressure drop. Both the gas meter and the  
gas regulator must be properly sized for the total  
gas load. If you experience a pressure drop greater  
than 1" WC, the meter, regulator or gas line is  
undersized or in need of service. You can attach a  
manometer to the incoming gas drip leg, by  
removing the cap and installing the manometer.  
The gas pressure must remain between 3.5" and  
14" during stand-by (static) mode and while in  
operating (dynamic) mode. If an in-line regulator  
is used, it must be a minimum of 10 feet from the  
Munchkin. It is very important that the gas line is  
properly purged by the gas supplier or utility.  
Failure to properly purge the lines or improper  
line sizing, will result in ignition failure. This  
problem is especially noticeable in NEW LP  
installations and also in empty tank situations. This  
can also occur when a utility company shuts off  
B. GAS PIPING  
1. Run the gas supply line in accordance with all  
applicable codes.  
2. Locate and install manual shutoff valves in  
45  
GAS-FIRED BOILER  
Boiler Manual  
PART 8: GAS PIPING (CONTINUED)  
service to an area to provide maintenance to their  
lines. This gas valve must not be replaced with a  
conventional gas valve under any circumstances.  
As an additional safety feature, this gas valve has  
a flanged connection to the swirl plate and blower.  
D. DUNGS GAS VALVE FOR T50/T80/80M/140M/199M  
PRESSURE TAP OUTLET  
OFF SET ADJUSTMENT  
CAUTION: DO NOT REMOVE  
THIS SCREW OR ATTEMPT TO  
MAKE ANY ADJUSTMENT TO  
THIS SCREW WITHOUT A  
COMBUSTION ANALYZER  
SEE PART 12 SECTION "D"  
FOR COMBUSTION SETTING  
TABLE.  
THROTTLE ADJUSTER  
NOTE: IF FOR ANY REASON THE  
THROTTLE NEEDS TO BE ADJUSTED,  
IT IS VERY IMPORTANT THAT A  
"COMBUSTION ANALYZER" BE USED  
TO ENSURE SAFE AND PROPER  
OPERATION. TURN THE ADJUSTER  
TO THE (+) TO INCREASE GAS OR  
THE (-) TO DECREASE THE GAS  
SUPPLY. THIS ADJUSTMENT COULD  
AFFECT CO/CO% LEVELS. MAKE  
SURE THE LEVELS CORRESPOND  
TO THE CHART IN COMBUSTION  
SETTINGS. SEE PART 12 FIGURE 12-1  
PRESSURE  
TAP INLET  
GAS VALVE  
GAS SHUT OFF  
VALVE  
Fig. 8-2  
WARNING  
For gas conversions for a boiler already installed, you must turn off gas supply, turn off power and allow  
boiler to cool before proceeding. You must also completely test the boiler after conversion to verify  
performance as described under “Startup” section of this manual. See separate natural to propane  
conversion instructions for conversion of an existing boiler available from Heat Transfer Products. Failure  
to comply with the proper gas conversion instructions could result in severe personal injury, death or  
substantial property damage. Failure to follow all precautions could result in fire, explosion or death!  
46  
GAS-FIRED BOILER  
Boiler Manual  
E. KROM SCHRODER VALVE FOR 399M  
GAS VALVE SHUT OFF  
INLET SOLENOID  
THROTTLE SCREW  
OUTLET SOLENOID  
WARNING: IF FOR ANY REASON THE THROTTLE  
NEEDS TO BE ADJUSTED, IT IS VERY IMPORTANT  
THAT A COMBUSTION ANALYZER BE USED TO  
ENSURE SAFE AND PROPER OPERATION.  
THE ADJUSTMENT COULD AFFECT THE CO/CO2  
LEVELS. MAKE SURE THE LEVELS CORRESPOND  
TO THE COMBUSTION SETTING CHART FIG 12-1  
IN PART 12  
MAIN GAS VALVE  
MEASURE OFFSET HERE  
FIRST VALVE  
OFFSET ADJUSTMENT  
Fig. 8-3  
PART 9: FIELD WIRING  
strip on the boiler cabinet and 120 volt terminal  
strip enclosed in the electrical box. Each terminal  
connection is clearly marked to assure correct in-  
stallation.  
WARNING  
ELECTRICAL SHOCK HAZARD — For your  
safety, turn off electrical power supply at service  
entrance panel before making any electrical  
connections to avoid possible electric shock  
hazard. Failure to do so can cause severe  
personal injury or death.  
C. LINE VOLTAGE WIRING  
1. Connect 120 VAC power wiring to the line  
voltage terminal strip located inside the  
electric junction box, as shown in figure 9.5.  
2. Wire the Boiler Primary Circulator (P1) to the  
terminal strip. See wiring diagram in this  
section.  
NOTICE  
Wiring must be N.E.C. Class 1.  
If original wiring as supplied with boiler must be  
replaced, use only TEW 105 °C wire or  
equivalent.  
Boiler must be electrically grounded as required  
by National Electrical Code ANSI/NFPA 70 —  
latest edition.  
D. THERMOSTAT  
1. Connect room thermostat or end switch  
2. Install thermostat on inside wall away from  
influences of drafts, hot or cold water pipes,  
lighting fixtures, television, sunrays or  
fireplaces.  
A. INSTALLATION MUST COMPLY WITH:  
3. Thermostat anticipator (if applicable):  
1. National Electrical Code and any other  
national, state, provincial or local codes or  
regulations.  
a. If connected directly to boiler, set for 0.1  
amps.  
b. If connected to relays or other devices,  
set to match total electrical power  
requirements of connected devices. See  
specifications of the device and  
thermostat instructions for details.  
2. In Canada, CSA C22.1 Canadian Electrical  
Code Part 1, and any local codes.  
B. FIELD WIRING  
The Munchkin Boiler box has a 24 volt terminal  
47  
GAS-FIRED BOILER  
Boiler Manual  
PART 9: FIELD WIRING (CONTINUED)  
Fig. 9-3  
Fig. 9-1  
Fig. 9-2  
Fig. 9-4  
48  
GAS-FIRED BOILER  
Boiler Manual  
PART 9: FIELD WIRING (CONTINUED)  
Fig. 9-5  
49  
GAS-FIRED BOILER  
Boiler Manual  
PART 10: FIELD WIRING – VISION 1  
Outdoor Sensor Function The user can pro-  
gram the desired supply temperature based on  
the heat transmitter (Baseboard, Radiant Floor,  
Air Handler) that will be used in the installation.  
Once the outdoor sensor (Light Green Wires) is  
connected to the control board, the water tem-  
perature of the boiler will adjust to run the boil-  
er more efficiently and provide greater comfort  
to the living space.  
1395 (Not included in Vision I Package) into the  
control well located in the front of the water  
heater. This will allow the installer to control the  
temperature of the indirect from the Munchkin  
Boiler and give the water heater priority over the  
Central Heating Circuit. Once the Water Heater is  
satisfied, the boiler will then switch back to the  
Central Heating Circuit only if there is a call for  
heat, otherwise the Munchkin Boiler will then  
shut down.  
Connection Specification – Wire 22 AWG  
maximum to 100 feet or 18 AWG up to  
150 feet. Length of wire run cannot  
exceed 150 feet.  
Indirect  
Circulator  
(P2)  
Program  
function: The indirect water heater circulator  
program function will automatically start when  
the water heater sensor reads a call for heat, the  
installer can also program the post purge  
function on the circulator. The Post purge  
circulator function ranges from 1-30 minutes.  
Outdoor Sensor is connected in the junction  
box on the Munchkin Boiler. Route wires from  
the Munchkin Boiler terminal strip to your out-  
door sensor, which will allow the user to change  
the temperature going to the Central Heating  
loop automatically. Place the outdoor sensor  
preferably to the north or northwest or to the  
side which will be affected by changing weather  
conditions outside. NOTE: Do not locate the  
sensor in the direct sunlight.  
Indirect Circulator (P2) is connected to the  
terminal strip on the Munchkin Boiler. Run the  
wire to the Super Stor Ultra Indirect circulating  
pump. The purple wire will be your neutral lead  
and the pink wire will be your hot. This will sup-  
ply 120 volts to the water heater circulator  
directly.  
CAUTION  
The wire to outdoor sensor must not be laid  
closer than 6' to line voltage wiring (120/240 V)  
and must never be in the same conduit.  
Fault Code Alarm Output is connected to  
the main controller on the Munchkin Boiler.  
Route wire from the Munchkin Boiler controller  
to an external relay or an audible alarm. The red  
wire will be your hot lead supplying 120 volts.  
The neutral connection will be connected to the  
neutral on the incoming power to the Munchkin  
Boiler.  
Indirect Sensor Function: The Maximum  
run time on priority function for the Super Stor  
Ultra Indirect Fired Water Heater is from 1-60  
minutes. The water temperature can only be  
adjusted when using a sensor (not a mechanical  
control). Temperature adjustments are from 95  
to 185 degrees, plus a differential 1-18 degrees  
(Note: It is recommend that you do not exceed  
5 minutes on the DHW pump post purge cycle  
to avoid cooling down your DHW tank).  
CAUTION  
Do not tie neutrals or hot wire leads to any  
o t h e r w i r e s , g o d i r e c t l y f r o m t h e  
Munchkin Boiler controller to the circulator.  
Connection Specification – Wire 18 AWG  
maximum. Length of wire run cannot  
exceed 100 feet.  
Indirect Sensor is connected to the main  
control on the Munchkin Boiler. Route wires  
from the terminal strip to the sensor or the  
mechanical control Honeywell Part # L4080b-  
50  
GAS-FIRED BOILER  
Boiler Manual  
PART 11. START-UP PREPARATION  
ically due to degradation of inhibitors over time.  
Follow all fluid manufacturer’s instructions.  
A. CHECK/CONTROL WATER CHEMISTRY  
WARNING  
B. FREEZE PROTECTION (WHEN USED)  
Do not use petroleum-based cleaning or sealing  
compounds in boiler system. Damage to  
elastomer seals and gaskets in system could  
occur, resulting in substantial property damage.  
WARNING  
NEVER use automotive or standard glycol  
antifreeze, even ethylene glycol made for  
hydronic systems. Use only freeze-prevention  
fluids certified by fluid manufacturer as suitable  
for use with stainless steel boilers, verified in  
fluid manufacturer’s literature.  
Throroughly clean and flush any system that  
has has used glycol before installing the new  
Boiler.  
Water pH between 6.0 and 8.0  
1. Maintain boiler water pH between 6.0 and 8.0.  
Check with litmus paper or have chemically  
analyzed by water treatment company.  
2. If pH differs from above, consult local water  
treatment company for treatment needed.  
Provide boiler owner with a material safety data  
sheet (MSDS) on the fluid used.  
Hardness less than 7 grains.  
1. Consult local water treatment companies for  
unusually hard water areas (above 7 grains  
hardness).  
1. Determine freeze protection fluid quantity  
using total system water content, following  
fluid manufacturer’s instructions. Remember  
to include expansion tank water content.  
Chlorine concentration less than 200 ppm  
1. Filling with chlorinated fresh water should be  
acceptable since drinking water chlorine  
levels are typically less than 5 ppm.  
2. Local codes may require back flow preventer  
or actual disconnect from city water supply.  
3. When using freeze protection fluid with  
automatic fill, install a water meter to monitor  
water makeup. Freeze protection fluid may  
leak before the water begins to leak, causing  
concentration to drop, reducing the freeze  
protection level.  
2. Do not use the boiler to directly heat  
swimming pool or spa water.  
3. Do not fill boiler or operate with water  
containing chlorine in excess of 200 ppm.  
Clean system to remove sediment  
C. FILL AND TEST WATER SYSTEM  
1. You must thoroughly flush the system  
(without boiler connected) to remove  
sediment. The high-efficiency heat exchanger  
can be damaged by buildup or corrosion due  
to sediment.  
1. Fill system only after ensuring the water  
meets the requirements of this manual.  
2. Close manual and automatic air vents and  
boiler drain valve.  
2. For zoned systems, flush each zone sepa-  
rately through a purge valve. (If purge valves  
and isolation valves are not already installed,  
install them to properly clean the system.)  
3. Fill to correct system pressure. Correct  
pressure will vary with each application.  
a. Typical cold water fill pressure for a  
residential system is 12 psi.  
b. Pressure will rise when boiler is turned  
on and system water temperature  
increases. Operating pressure must  
never exceed 25 psig.  
3. Flush system until water runs clean and you  
are sure piping is free of sediment.  
Test/replace freeze protection fluid  
1. For systems using freeze protection fluids,  
follow fluid manufacturer’s instructions to  
verify inhibitor level and that other fluid  
characteristics are satisfactory.  
4. At initial fill and during boiler startup and  
testing, check system thoroughly for any  
leaks. Repair all leaks before proceeding  
further.  
2. Freeze protection fluid must be replaced period-  
51  
GAS-FIRED BOILER  
Boiler Manual  
PART 11. START-UP PREPARATION (CONTINUED)  
one at a time, beginning with lowest  
floor. Close vent when water squirts out.  
Repeat with remaining vents.  
WARNING  
Eliminate all system leaks. Continual fresh  
make-up water will reduce boiler life. Minerals  
can build up in the heat exchanger, reducing  
heat transfer, overheating heat exchanger, and  
causing heat exchanger failure.  
j. Refill to correct pressure.  
E. CHECK FOR GAS LEAKS  
WARNING  
5. The system may have residual substances  
that could affect water chemistry. After the  
system has been filled and leak tested, verify  
water pH and chlorine concentrations are  
acceptable.  
Before starting the boiler, and during initial  
operation, smell near the floor and around the  
boiler for gas odorant or any unusual odor.  
Remove boiler front door and smell interior of  
boiler enclosure. Do not proceed with startup if  
there is any indication of a gas leak. Repair any  
leak at once.  
CAUTION  
It is important that you purge the system of air  
to avoid damage to the boiler.  
WARNING  
D. PURGE AIR FROM WATER SYSTEM  
Propane boilers only — Your propane supplier  
mixes an odorant with the propane to make its  
presence detectable. In some instances, the  
odorant can fade, and the gas may no longer  
have an odor. Before startup (and periodically  
thereafter), have the propane supplier verify the  
correct odorant level in the gas.  
1. Purge air from system:  
a. Connect a hose to the purge valve and  
route hose to an area where water can  
drain and be seen.  
b. Close the boiler or system isolation valve  
between the purge valve and fill  
connection to the system.  
c. Close zone isolation valves.  
d. Open quick-fill valve on cold water make-  
up line.  
F. CHECK THERMOSTAT CIRCUIT(S)  
1. Disconnect the two external wires connected  
to the boiler thermostat terminals (low  
voltage terminal strip terminals 5 and 6).  
e. Open purge valve.  
2. Connect a voltmeter across these two  
incoming wires. Close each thermostat, zone  
valve and relay in the external circuit one at  
a time and check the voltmeter reading  
across the incoming wires.  
f. One zone at a time, open the isolation  
valves. Allow water to run through the  
zone, pushing out the air. Run until no  
noticeable air flow is present. Close the  
zone isolation valves and proceed with  
the next zone. Follow this procedure until  
all zones are purged.  
g. Close the quick-fill water valve and purge  
valve and remove the hose. Open all  
isolation valves. Watch that system  
pressure rises to correct cold-fill  
pressure.  
3. There should NEVER be a voltage reading.  
4. If a voltage does occur under any condition,  
check and correct the external wiring. (This is  
a common problem when using 3-wire zone  
valves.)  
5. Once the external thermostat circuit wiring is  
checked and corrected if necessary,  
reconnect the external thermostat circuit  
wires to boiler low voltage terminal strip  
Allow the boiler to cycle.  
h. After the system has operated for a  
while, eliminate any residual air by using  
the manual air vents located throughout  
the system.  
i. If purge valves are not installed in  
system, open manual air vents in system  
52  
GAS-FIRED BOILER  
Boiler Manual  
PART 11. START-UP PREPARATION (CONTINUED)  
3. The Munchkin Boiler is equipped with an  
internal vent on the top plug connection to  
assure adequate flow of condensate. This  
vent should never be blocked.  
G. CHECK CONDENSATE REMOVAL  
1. The Munchkin Boiler is a high efficiency  
condensing boiler, there, the unit has a  
condensation drain. Condensate is nothing  
more than water vapor, derived from  
combustion products, similar to an  
automobile when it is initially started. The  
condensation is slightly acidic (typically with  
pH of 3 to 5) and must be piped with the  
correct materials. Never pipe the condensate  
using steel, copper, brass or other materials  
that will be subject to corrosion. Plastic PVC  
or CPVC pipe are the only approved  
materials. A condensate filter, if required by  
local authorities, can be made up of lime  
crystal,s marble or phosphate chips that will  
neutralize the condensate. This may be done  
by the installer or you may purchase a  
condensate neutralizer from Heat Transfer  
Products, Inc. (P/N N1100)  
4. If a long horizontal run is used, it may be  
necessary to create a second vent to prevent  
a vacuum lock in the condensate line. Do not  
expose the condensate to freezing  
temperatures.  
5. Do not expose the condensate to freezing  
temperatures.  
6. It is very important you support the  
condensation line to assure proper drainage.  
H. FINAL CHECKS BEFORE STARTING BOILER  
1. Read Startup Procedures within this manual  
for proper steps to start boiler. (See Startup  
Report to record steps for future reference.)  
2. Verify the boiler and system are full of water  
and all system components are correctly set  
for operation.  
2. The Munchkin Boiler is equipped with a ¾  
pipe connection that runs the condensation  
line to a local drain. It is very important that  
the condensate line is sloped away from the  
heater and down to a suitable inside drain. If  
the condensate outlet is lower than the drain,  
you must use a condensate removal pump,  
available at Heat Transfer Products (#554200).  
This pump is equipped with two leads that  
can be connected to an alarm or another type  
of warning device to alert residents of a  
condensate overflow, which, if not corrected,  
could cause property damage.  
3. Fill condensate trap with water.  
4. Verify electrical connections are correct and  
securely attached.  
5. Inspect intake piping and exhaust piping for  
signs of deterioration from corrosion, physical  
damage or sagging. Verify intake piping and  
exhaust piping are intact and correctly  
installed per Venting section and local code.  
PART 12. START-UP PROCEDURE  
FOR YOUR OWN SAFETY READ BEFORE OPERATING  
• If you cannot reach your gas supplier, call the fire department.  
1. This appliance does not have pilot. It is equipped with an ignition  
device which automatically lights the burner. Do not try to light the  
burner by hand.  
3. Turn on gas shutoff valve (located inside of the Boiler) so that the  
handle is aligned with the gas pipe. If the handle will not turn by  
hand, don't try to repair it, call a qualified service technician. Force  
or attempted repair may result in a fire or explosion.  
4. Do not use this appliance if any part has been under water.  
Immediately call a qualified service technician to inspect the  
appliance and to replace any part of the control system and any gas  
control which has been under water.  
5. The Munchkin Boiler shall be installed so the gas ignition system  
components are protected from water (dripping, spraying, rain, etc.)  
during appliance operation and service (circulator replacement,  
condensate trap, control replacement, etc.)  
2. BEFORE OPERATING smell all around the appliance area for gas. Be  
sure to smell next to the floor because some gas is heavier than air  
and will settle on the floor.  
WHAT TO DO IF YOU SMELL GAS  
• Do not try to light any appliance.  
• Donottouch any electricswitch;do notuseany phoneinyourbuilding.  
• Immediately call your gas supplier from a neighbor's phone.  
Follow the gas suppliers' instructions.  
53  
GAS-FIRED BOILER  
Boiler Manual  
PART 12. START-UP PROCEDURE (CONTINUED)  
– 3. Celsius to Fahrenheit measurement. Simply  
press in the {S3/Program} key to get to next value,  
the Munchkin Boiler differential setting will  
appear in the display ch and alternating value of  
30. This allows the installer to adjust the activa-  
tion of the burner based on the differential tem-  
perature setting of the Munchkin. The burner  
will not start until the outlet water temperature  
reaches a temperature that is equal to the tem-  
perature setting for the Munchkin Boiler, minus  
the differential EX: The Boiler is set to heat at  
180° F degrees and the differential is set at 30° F.  
The burner will not start until the outlet temper-  
ature of the system reaches 149° F degrees (180°  
A. OPERATING INSTRUCTIONS  
Remove boiler cover. If you smell gas, STOP.  
Follow listed safety instructions. If you do not  
smell gas, follow the next steps.  
1. Turn on all electric power to appliance.  
2. Adjust the temperature setpoint of the  
Munchkin Boiler if desired. The factory  
default setting is 180°. If changes are  
ncessary follow Adjusting The Munchkin  
Setpoint” in this section.  
3. Set the thermostat to the desired setting.  
4. If the appliance fails to start, refer to the  
Troubleshooting section in the back of this  
manual.  
– 30° F = 150° F). To adjust, press either {S1/-}  
(Decrease Value) or {S2/+} (Increase Value)  
Ranges 5° F to 30° F. Press the {S3/Program} key  
again and you will see the Indirect Setting de  
and an alternative value of 119 (with Vision  
DANGER  
Water temperature over 125  
degrees F. can cause severe  
burns instantly, or death from  
scalds. Children, disabled, and  
Systems) To adjust, press either {S1/  
-} Decrease  
Value) or {S2/+} (Increase Value).  
The final adjustment in this mode is the Fahrenheit  
to Celcius measurement. Press the {S3/Program}  
key again and you will see t and alternating value  
of F. To change value press the {S1/-} or {S2/+} to  
choose the correct measurement.  
elderly are at highest risk of  
being scalded. See instruction  
manual before setting temperature at water  
heater. Feel water before bathing or showering!  
Temperature limiting valves are available.  
C. STATUS MENU  
Installers are also able to check the current status  
of the Munchkin Boiler parameters by pressing  
{S4/RESET} key for 3 seconds. Once activated, the  
display will show |d1| alternating value of the actu-  
al outlet temperature. Actual values are displayed  
for each function. To view the next value simply  
press the {S/4} key to go to the next displayed  
value. Listed below are the values which can be  
displayed. These values cannot be changed. To  
exit this menu, simply press {S3/Program} key to  
resume normal operation.  
B. ADJUSTING THE SETPOINT  
1. Before you can change the temperature from  
the factory setting of 180 degrees. You must  
make sure that none of the thermostats are call-  
ing for heat. The controller will not memorize a  
program setting while in a heating cycle. To  
adjust the temperature to the Munchkin simply  
press in the {S3/Program} key for three seconds  
until you see a flashing (C) then an alternate  
value of (180). This number is the factory set  
point of the unit, which is 180 degrees. To  
change the temperature, simply push either the  
Function Value  
d1 — Actual Temperature from outlet sensor  
d2 — Actual Temperature from inlet sensor  
{S1/-} or {S2/+} on the display. The {S1/-} button  
will decrease the temperature while the {S2/+}  
will increase the temperature of the Munchkin.  
The temperature of the boiler can be set as low  
as 50 Degrees and as high 180 Degrees. These  
ranges are your maximum and minimum ranges  
of the boiler. In addition to changing the tem-  
perature you are also allowed to change three  
more settings in this model (1. Munchkin differ-  
ential – 2. Indirect setting (with Vision System)  
d3 — If using a standard mechanical control,  
the control will display |1| for closed |0|  
for open  
If the sensor is connected to the  
SuperStor Indirect Fired Water Heater  
it will measure the actual temperature.  
(Vision option.)  
d4 — Not used  
54  
GAS-FIRED BOILER  
Boiler Manual  
PART 12. START-UP PROCEDURE (CONTINUED)  
Function Value  
d5 — Actual Temperature from the outdoor  
sensor. (Vision option.)  
d6 — Actual Fan speed multiplied by 10  
(Example: If fan speed displayed is  
|410| RPM x 10 = 4100 actual fan  
speed)  
the Combustion Settings. Automatic modulation  
does not take place when the controller is in Test  
mode, only temperature limitation based on the  
Munchkin Boiler Central Heating set point. The  
user will be allowed to increase or decrease the  
fan speed by pressing in either the {S1/  
-} or {S2/+}  
keys.  
d7 — Actual Ionization current read from  
Flame Rectification probe  
d8 — Actual Status of the Central Heating  
Circulator Off = |0|, On = |1|. (Vision  
option.)  
d9 — Actual Status of the Indirect Fired  
Circulator Off = |0|, On = |1|. (Vision  
option.)  
To activate the Test mode simply press the {S2/+}  
and {S3/Program} key together for 1 second. Once  
activated, you will see in the display {Ser} and the  
actual fan speed. The measurement of the com-  
bustion levels should always be taken at the high-  
est and lowest fan speed. After 10 minutes, the  
Test mode stops automatically. To exit Test Mode  
press {S1/-} and {S2/+} key together for 1 second.  
d10 — Actual Status bus communication  
Fig. 12-1  
|co| = connected, |no| = not connected  
d11 — Central Heating Set Point  
d12 — Power On Hours in units  
d13 — Total Central Heat Hours  
d14 — Total Indirect/dhw Hours  
d15 — Passed Ignition Attempts  
COMBUSTION SETTINGS  
HIGH FIRING RATES and LOW FIRING RATES ON ALL MODELS  
Natural Gas Propane LP  
low  
high  
low  
high  
Carbon  
Monoxide 0–20 ppm 70 ppm–135 ppm 0–20 ppm 80 ppm–150 ppm  
(CO %)  
D. TEST MODE  
This function is intended to simplify the gas valve  
adjustment if needed. Listed below are the rec-  
ommended limits on each Munchkin Boiler and  
Carbon  
Dioxide  
8½% – 9½% 8½% – 9½% 9½% – 10½% 9½% – 10½%  
(CO %)  
2
PART 13: START-UP PROCEDURES WITH THE VISION 1  
The Vision I option allows the user to have one  
temperature for central heating and another  
temperature for the Super Stor Ultra Indirect  
Fired Water Heater. This allows the user to  
increase the temperature supplied to the Super  
Stor Ultra indirect water heater to get a fast  
recovery by prioritizing the flow at a higher tem-  
perature than may be needed for the Central  
Heating Circuits (this will require two separate  
circulators). Once the Super Stor Ultra Indirect is  
satisfied, the Vision I system will switch back to  
the Central Heating Circuit to continue to heat  
the living space at a temperature based on out-  
side temperature. This gives you a higher com-  
fort level and further increases the efficiency of  
the Munchkin Boiler.  
A. PROGRAMMING THE VISION I OPTION  
The Vision I allows the installer to set system  
limits and the heat curve for the Munchkin  
Boiler. These system limits should not be  
changed by the user. It is important to document  
your settings within this manual after you pro-  
gram the sytem parameters so this will be  
recorded for future reference.  
B. VISION 1 PROGRAM ACCESS  
To start, press down and hold the {S/3} and {S/4}  
simultaneously for three seconds. You will notice  
that the display will change to |000|. Then, with  
your {S1/-} key on the display press down until you  
see |925|. This is the pass code. To confirm that  
55  
GAS-FIRED BOILER  
Boiler Manual  
PART 13: START-UP PROCEDURES WITH THE VISION 1 (CONTINUED)  
the pass code is correct, you will need to press  
and hold the {S3/Program} for 1 second to confirm.  
If the pass code is entered incorrectly, the con-  
troller program function will be cancelled and the  
control returns to normal operation. If the code is  
entered correctly, the control will switch off the  
gas valve and purge fan while showing a solid  
Default Function  
Function Value Description  
6
0 Min. Allows the installer to change the  
Indirect Circulator Post Purge  
Time once the sensor is satisfied  
(Note: it is recommend that  
Circulator Post Purge Time be set  
no greater than 5 minutes).  
Range: 0 to 60 minutes  
|---| in the display. The display will than show a  
|1| alternating to |de|. This first function verifies that  
the control will address the requirements of the  
Superstor Indirect Fired Water Heater.  
7
68ºF Outdoor temperature that you  
wish the central heating should be  
disabled—(warm weather shut-  
off) Range: 41ºF to 122ºF  
C. VISION 1 PROGRAM NAVIGATION  
Next you will have to press the {S/3} key to move  
through each function. To increase or decrease  
*8  
5ºF Allows the installer to change the  
Minimum Outside Design  
Temperature. Range: –49ºF to  
32ºF (See Chart 13-1 to set out-  
door reset curve)  
a value, you will need to press either the {S/1  
-}  
key or {S/2+} key to change the default values. If  
there is no key action for 1 minute, the display  
returns to normal operation. Changes are effec-  
tive immediately but not directly stored until the  
{S/4} key is pressed down for 3 seconds then the  
new values are stored. Listed below are the vari-  
ety of functions the installer can program into  
the Vision I System.  
*9  
180ºF Allows the installer to change the  
D e s i g n S u p p l y Wa t e r  
Temperature from the Munchkin  
based on the Minimum Outside  
Design Temperature Range: 77ºF  
to 185ºF  
CAUTION  
*10  
*11  
68ºF Allows the installer to change the  
Maximum Outside Design  
Temperature for Central Heating.  
Range: 95ºF to 32ºF  
95ºF Allows the installer to change the  
Design Supply Water  
The Boiler cannot be programmed while  
there is a call for heat.  
NOTE: See Chart 13-1 in Part 13 to set outdoor  
reset curve.  
Default Function  
Function Value Description  
Temperature from the Munchkin  
based on the Maximum Outside  
Design Temperature. Range:  
32ºF to 180ºF  
1
2
3
de  
Not Applicable  
149ºF Not Applicable  
160ºF Maximum Domestic Delivery  
Water Temperature Setpoint the  
Installer will program for  
SuperStor Indirect Fired Water  
Heater (Note: Does not apply if  
used with Mechanical Control)  
Range: 95ºF to 160ºF  
12  
68º F Allows the installer to set the low-  
est temperature on the Munchkin  
for Central Heating. Range: 32ºF  
to 180ºF  
13 0 Min. Allows the installer to change the  
Central Heating Circulator Post  
Purge Time once the thermostat is  
satisfied. Range 0 to 10 minutes.  
4
5
36ºF Not Applicable  
7ºF Allows the installer to change the  
differential in the Indirect Fired  
Water Heater (Does not apply if  
used with a Mechanical Control)  
Range: 1ºF to 18ºF  
56  
GAS-FIRED BOILER  
Boiler Manual  
PART 13: START-UP PROCEDURES WITH THE VISION 1 (CONTINUED)  
Default Function  
The central heating demand is detected when  
Function Value Description  
the room thermostat closes. When an outside  
sensor is also connected, the supply tempera-  
ture will depend on the factory default central  
heating curve.  
14 30 Min. Allows the installer to set the  
Maximum run time for the Indirect  
Fired Water Heater and the  
Minimum run time for Central  
Heating. Range 0 to 60 Minutes  
To set your heat curve you will have to set the  
following parameters  
15  
0
Bus address (0=zone master 1–8  
— cascade slave) (Not currently  
used.)  
1. Minimum outside design temperature:  
Function 8  
2. Design Supply water temperature at the  
minimum design outside temperature:  
Function 9  
16  
0
Interface Board Activation  
0 = not active  
1 = active  
3. Maximum outside design temperature:  
WARNING: Never change the de-  
fault setting without the Munchkin  
Interface Board installed.**  
Interface Board Function  
0 = Building Management  
1 = Enables Tekmar Modulating  
control.  
(Consult with Tekmar to assure  
the Tekmar Control is compati-  
ble)  
Function 10  
4. Design Supply water temperature at the  
maximum outside temperature: Function 11  
17  
18  
0
1
NOTICE  
It is important to note that the homeowner can  
adjust the heat curve down by adjusting the  
central heating temperature to a lower setting.  
Step Modulation – Regulates the  
burner output in 6 steps in one-  
minute intervals. This reduces  
short cycling.  
1 = on  
0 = off  
19  
20  
185° Indirect boiler set point (flow)  
Temperature default = 119° to  
180°  
1
Not applicable  
* Central Heating Curve Function  
57  
GAS-FIRED BOILER  
Boiler Manual  
PART 13: START-UP PROCEDURES WITH THE VISION 1 OPTION (CONTINUED)  
CENTRAL HEATING CURVE  
CENTRAL HEATING CURVE  
Plot your Curve  
Factory Default  
212  
203  
194  
185  
176  
167  
158  
149  
131  
122  
113  
104  
95  
212  
203  
194  
185  
176  
167  
158  
149  
131  
122  
113  
104  
95  
201˚  
FUNCTION 9  
DEFAULT RESET CURVE  
FUNCTION 11  
86  
86  
77  
77  
68  
68  
59  
59  
50  
50  
41  
41  
32  
32  
0
0
-59  
-41  
-24  
-9  
9
63  
99  
27  
45  
81  
68˚  
-59  
-41  
-24  
-9  
9
63  
99  
27  
45  
81  
5˚  
OUTSIDE TEMPERATURE (F)  
OUTSIDE TEMPERATURE (F)  
Fig. 13-1  
Fig. 13-2  
CONTROL PROGRAM REFERENCE CHART  
Function  
Default Setting  
Programmed Setting  
1
2
3
de  
149 F  
160 F  
36 F  
No change allowed  
No change allowed  
4
No change allowed  
5
6
7
7 F  
0 minutes  
68 F  
8
9
5 F  
180 F  
68 F  
95 F  
68 F  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
0 minutes  
30 minutes  
0
0
0
1
180°F  
Fig. 13-3  
58  
GAS-FIRED BOILER  
Boiler Manual  
PART 14: TROUBLESHOOTING  
A. MUNCHKIN ERROR CODE  
WARNING  
An error code may occur in the installation of  
the Munchkin. This condition may lead to a lock  
out condition of the controller, which will need  
to be manually reset through the S4/Reset but-  
ton. These temporary codes will help the  
installer correct the problem before going into a  
lock out condition, which will require a manual  
reset.  
When servicing or replacing any components of this  
boiler be certain that:  
• The gas is off.  
• All electrical power is disconnected  
DANGER  
When servicing or replacing that are in direct contact  
with the boiler water, be certain that:  
• There is no pressure in the boiler. (Pull the release  
on the relief valve. Do not depend on the pressure  
gauge reading).  
• The boiler water is not hot  
• The electrical power is off  
B. BOILER ERROR  
1. When an error condition occurs the controller  
will display an error code on the display  
module.  
2. These error codes and several suggested  
corrective actions are included in Table 14-1.  
WARNING  
Do not use this appliance if any part has been under  
water. Improper or dangerous operation may result.  
Contact a qualified service technician immediately to  
inspect the boiler and to repair or replace any part of  
the boiler which has been under water.  
3. In the case of E00, E13, and E14 this error, if  
uncorrected, will go into a fault condition as  
described is Paragraph C (Boiler Fault).  
C. BOILER FAULT  
CAUTION  
This appliance has wire function labels on all internal  
wiring. Observe the position of each wire before re-  
moving it. Wiring errors may cause improper and dan-  
gerous operation. Verify proper operation after servicing.  
1. When a fault condition occurs the controller  
will illuminate the red “fault” indication light  
and display a fault code in the format  
(Example: |F00|) on the display module.  
2. Note the fault code and refer to Table 14-2 for  
an explanation of the fault code along with  
several suggestions for corrective actions.  
CAUTION  
If overheating occurs or the gas supply fails to shut  
off, do not turn off electrical power to the circulating  
pump. This may aggravate the problem and increase  
the likelihood of boiler damage. Instead, shut off the  
gas supply to the boiler at the gas service valve.  
3. Press the reset key to clear the fault and  
resume operation. Be sure to observe the  
operation of the unit to prevent a recurrence  
of the fault.  
Table 14-1 : 925 Control Board ERROR Codes  
Code  
Description  
Duration  
Corrective Action  
1. Check circulation pump operation.  
2. Assure that there is adequate flow through the boiler  
by accessing the status menu and assuring that there  
is less than a 50°F rise from the return thermister to  
the supply thermister.  
High Limit Exceeded  
50 Sec.  
E00  
3. Replace switch if faulty.  
Combustion Fan Speed Low.The boil-  
er combustion air fan speed less  
than 70% of expected.  
Combustion Fan Speed High. The  
boiler combustion air fan speed is  
more than 130% of expected.  
1. Check the combustion air fan wiring.  
2. Replace the combustion air fan.  
3. Replace the control board.  
1. Check the combustion air fan wiring.  
2. Replace the combustion air fan.  
3. Replace the control board.  
60 Sec.  
E13  
60 Sec.  
Until  
E14  
1. Assure that the system pressure is above 10 psig.  
WaterPressure Switch Open  
PR0  
Corrected 2. Check for leaks in the system piping.  
1. Assure that the vent is not blocked  
Until  
Blocked Vent Pressure Switch Open  
2. Check the switch operation by applying a jumper. (If  
Corrected  
FLU  
the switch is not functioning properly, replace it.)  
59  
GAS-FIRED BOILER  
Boiler Manual  
PART 14: TROUBLESHOOTING (CONTINUED)  
Table 14-2: 925 Control Board FAULT Codes  
Code  
Description  
Remedy  
1. Check circulation pump operation  
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the  
return thermister to the supply thermister.  
3. Check thermister reading on supply thermister. Replace switch if faulty.  
4. If this is a new installation, disconnect the two light grey wires from the zone control, and twist the wires together. Depress the S4 reset  
button. If the fault clears, the problem is outside the boiler  
High Limit Exceeded.  
F00  
5. If this is an existing installation with glycol in it, check the condition of the water pressure switch. It may be necessary to jump out the water  
pressure switch (temporarily only, as a trouble shooting aid) The 24 VAC signal, may have grounded through the glycol if the water pressure  
switch is leaking.  
1. Push the red reset button on the switch.  
2. Check the flue temperature during operation using a combustion analyzer.  
3. Replace the vent limit switch if faulty.  
Vent Temperature Limit Exceeded.  
F01  
4. Verify the combustion drain if clear and draining properly.  
5. Visually inspect the target wall to see if it is intact. If not intact replace target wall.  
1. Check the electrical connection to the thermister on the outlet manifold. Verify 5 VDC by checking in Molex connector. Verify thermister  
Interrupted or Shorted  
values by referencing chart in this manual.  
F02  
Supply (Outlet) Thermister.  
2. Replace thermister if necessary.  
1. Check the electrical connection to the thermister on the inlet manifold. Verify 5 VDC by checking in Molex connector. Verify thermister  
Interrupted or Shorted  
Return (Inlet) Thermister.  
values by referencing chart in this manual.  
F03  
2. Replace thermister if necessary.  
1. Check circulation pump operation.  
Supply (Outlet)  
Temperature exceeds 230°F.  
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the  
F05  
return thermister to the supply thermister.  
1. Check circulation pump operation.  
Return (Inlet) Temperature  
Exceeded 230°F.  
2. Assure that there is adequate flow through the boiler by accessing the status menu and assuring that there is less than a 50°F rise from the  
return thermister to the supply thermister.  
F06  
3. Check direction of flow on boiler circulator. (See Piping Details in this manual.)  
1. Watch the igniter through the observation window provided.  
2. If there is no spark, check the spark electrode for the proper ¼” gap. Use 2 quarters together as a gauge to hold ignitor against to check  
gap distance.  
No flame detected – The boiler will  
make three attempts at ignition  
before the control goes into this  
lockout condition. *See spark  
electrode detail.  
3. Remove any corrosion from the spark electrode and flame rectifier probe.  
4. If there is a spark but no flame, check the gas supply to the boiler.  
5. If there is a flame, check the flame sensor.  
F09  
6. Check any flue blockage or condensate blocks.  
1. Monitor the gas pressure to the unit while in operation.  
2. Assure that the flame is stable when lit.  
Loss of Flame Signal – The boiler  
3. Check to see if the green light on the display module is out while the boiler is running.  
will relight 4 times before the control 4. If the green light doesn’t come on or goes off during operation check the flame signal on the status menu.  
F10  
goes into this lockout condition.  
5. If the signal reads less than 1 microampere, clean the flame rectifier probe.  
6. If the flame rectifier probe continues to read low, replace it.  
7. Check the stability of the flame rectification signal. If the signal is unstable, you may need to replace the burner gasket.  
1. Turn the gas off to the unit at the service valve.  
2. If the flame signal is still present replace the igniter.  
False Flame Signal – The boiler will 3. If the flame signal is not present after turning off the gas supply, check the gas valve electrical connection.  
lock out if it senses a flame signal  
4. If there is no power to the gas valve, remove the valve and check for obstruction in the valve seat or replace the gas valve.  
F11  
when there should be none present. 5. Turn the gas on at the service valve after corrective action is taken.  
6. Check for condensate back up. Condensate back up can damage the refractory wall, and if the wall falls against the rectifier probe, it may  
conduct the signal to ground, giving a false reading.  
Combustion Fan Speed Low – The  
boiler will lock out if it senses that  
the fan speed is less than 70% of  
expected rate for more than 60  
seconds.  
1. Check the combustion air fan wiring.  
1a. Check the quality of the 24 VAC signal by measuring from any connected safety to ground. A low voltage situation may cause a “false”  
error code  
2. Replace the combustion air fan.  
3. Replace the control board.  
F13  
Combustion Fan Speed High – The  
boiler will lock out if the fan speed is  
more than 130% of expected rate for  
more than 60 seconds.  
1. Check the combustion air fan wiring.  
2. Replace the combustion air fan.  
3. Replace the control board.  
F14  
1. Make sure the connector is correctly connected to the gas valve.  
2. Check the electrical wiring from the valve to the control board.  
2a. Voltage readings will be from 18-22 VDC on the outlet of the gas valve plug from any pin to ground, the connector must remain in contact  
with the pins.  
Gas Valve Error  
F18  
2b. On the 399M only, check the 24 VAC relay block.  
3. Replace the low voltage wiring harness assembly.  
4. Replace control board.  
Supply voltage frequency out of range. (92-132 VAC 60 Hz)  
F19  
F30  
Watchdog  
Call factory for further assistance. Watchdog  
Parameter Memory  
Parameter Memory Write Error  
Programming Error  
Call factory for further assistance. Parameter memory error, reprogramming needed  
Call factory for further assistance. Parameter memory write error  
Call factory for further assistance. Parameter memory error, reprogramming needed  
Press S4 reset  
F31  
F32  
F33  
Parameters Programmed  
PP  
Internal processor error, due to incoming voltage problems. (92-132 VAC 60 Hz). May also occur if neutral wire has been broken or damaged.  
Internal error  
Nc  
F
60  
GAS-FIRED BOILER  
Boiler Manual  
PART 14: TROUBLESHOOTING (CONTINUED)  
Resistance Tables  
Indirect Sensor  
(7250P-320)  
Outdoor Sensor (7250P-319)  
Boiler Sensor (7250P-667)  
Outside Temperature (°F) Resistance (ohms)  
Boiler and Indirect Temperature (°F) Resistance (ohms)  
–22  
–13  
–4  
171800  
129800  
98930  
76020  
58880  
45950  
36130  
28600  
22800  
18300  
14770  
12000  
9804  
32  
41  
32550  
25340  
19870  
15700  
12490  
10000  
8059  
6535  
5330  
4372  
3605  
2989  
2490  
2084  
1753  
1481  
1256  
1070  
915  
50  
5
59  
14  
23  
32  
41  
50  
59  
68  
77  
86  
95  
104  
113  
68  
77  
86  
95  
104  
113  
122  
131  
140  
149  
158  
167  
176  
185  
194  
203  
212  
8054  
Fig. 14-3  
6652  
NOTE: If receiving an  
F09 fault code, check  
t h e g a p s p a c i n g  
between points on the  
electrode by holding  
two quarters together  
a n d s l i d i n g t h e m  
through the gap. There  
should be a slight  
resistance.  
5522  
786  
667  
Fig. 14-4  
PART 15: MAINTENANCE  
A. MAINTENANCE PROCEDURES  
WARNING  
Periodic maintenance should be performed  
once a year by a qualified service technician to  
assure that all the equipment is in safe efficient  
operation. The owner can make necessary  
arrangements with a qualified heating contrac-  
tor for periodic maintenance of the heater.  
Installer must also inform the owner that the lack  
of proper care and maintenance of the heater  
may result in a hazardous condition. The  
installer should discuss the contents of the  
User's Information Manual with the owner.  
BEFORE EACH HEATING SEASON A trained  
and qualified service technician should perform  
the inspections as per the boiler inspection and  
maintenance schedule in the back of manual.  
Failure to do so could result in death or serious  
injury.  
61  
GAS-FIRED BOILER  
PART 15: MAINTENANCE (CONTINUED)  
WARNING  
The combustion chamber insulation in  
this product contains ceramic fiber  
material. Ceramic fibers can be  
converted to cristobalite in very high  
temperature applications. The  
International Agency for Research on  
Cancer (IARC) has concluded,  
“Crystalline silica inhaled in the form of  
quartz or cristobalite from occupational  
sources is carcinogenic to humans  
Boiler Manual  
Munchkin Boiler side), so the flow can  
be observed.  
c. Disconnect connections from the gas  
valve, spark electrode and flame rectifi-  
cation probe and combustion blower.  
d. Remove the (4) screws on the aluminum  
½” NPT connector on the gas valve.  
e. Disconnect the wiring connected to the  
combustion blower motor.  
f. Remove the (6) 10MM nuts from the  
burner plate assembly to access the  
coils.  
g. Pull the entire burner plate assembly with  
blower still attached towards you, while  
removing or pushing aside any wiring to  
allow the removal of the assembly.  
(Group1).”:  
ƒ Avoid breathing dust and contact with skin and  
eyes.  
2. Using a spray bottle filled with the recommeded  
product “RYDLYME” or “CLR”, spray liberally on  
the coils, making sure the solution penetrates  
and funnels down through the condensate hose.  
If the condensate hose is blocked, let the chem-  
ical penetrate for at least 15 minutes or until it  
drains.  
3. Use the nylon, stainless or brass brush (do not  
use steel) and scrub coils to remove any buildup,  
then vacuum the debris from the coils. WARN-  
ING: Follow precautions above  
4. Spray the coils with clear water, making sure to  
confine the spray to the area being cleaned (Try  
to avoid getting the back ceramic wall of the unit  
wet). Flush the combustion chamber with fresh  
water. At this point, the Munchkin should be  
ready to power back up.  
• Use NIOSH certified dust respirator (N95). This  
type of respirator is based on the OSHA  
requirements for cristobalite at the time this  
document was written. Other types of respirators  
may be needed depending on the job site  
conditions. Current NIOSH recommendations  
can be found on the NIOSH website at  
NIOSH approved respirators, manufacturers, and  
phone numbers are also listed on this website.  
• Wear long-sleeved, loose fitting clothing,  
gloves, and eye protection.  
ƒ Apply enough water to the combustion chamber  
lining to prevent dust  
ƒ Wash potentially contaminated clothes separately  
from other clothing. Rinse clothes washer  
thoroughly.  
NIOSH stated First Aid.  
ƒ Eye: Irrigate immediately  
ƒ Breathing: Fresh air.  
Before powering up the Munchkin Boiler follow the  
steps below  
B. COMBUSTION CHAMBER COIL  
CLEANING INSTRUCTIONS  
a. Re-install the burner assembly  
b. Tighten the (6) 10MM nuts to the burner  
plate  
c. Re-connect all wiring connections  
e. Replace the (4) screws on the aluminum  
½” NPT connector on the gas valve. Turn  
the gas back on. (IMPORTANT: CHECK  
FOR GAS LEAKS)  
f. Re-set thermostats (IMPORTANT: MAKE  
SURE EXHAUST VENT IS NO LONGER  
BLOCKED!)  
g. Turn the Munchkin Boiler back on and  
observe condensate flow.  
*Before beginning this procedure, you must have on  
hand the following items:  
– a nylon, stainless or brass brush (not steel)  
– “Rydlyme” (recommended for best  
r e s u l t s ) ( a v a i l a b l e o n l i n e  
most hardware stores)  
– Gloves, eye protection  
1. Shut down the Munchkin Boiler by using the fol-  
lowing steps:  
a. Close the gas valve, shut down the unit  
and wait for the unit to be cool to the  
touch  
h. Re-connect the condensate hose to the  
outside connection.  
b. Disconnect the condensate hose from  
the outside connection, (not from the  
62  
GAS-FIRED BOILER  
Boiler Manual  
PART 15: MAINTENANCE (CONTINUED)  
5
2
3
6
1
5
13  
12  
17  
16  
14  
15  
4
7
11  
19  
18  
8
21  
22  
9
20  
10  
23  
43  
24  
42  
25  
35  
40  
41  
36  
37  
34  
39  
38  
33  
T50M/T80M  
32  
29  
27  
31  
30  
28  
23  
25  
T
26  
REPLACEMENT PARTS  
Item  
#
Item  
Description  
Thermodisc Flue ECO 210 F  
Steel Push Retainer (Thermodisc Flue ECO)  
Part #  
#
Description  
Part #  
1
2
3
4
5
6
7
7250P-089  
7250P-151  
7250P-311  
7250P-080  
7250P-059  
7250P-081  
7250P-019  
22 Nut M5 (Aluminum Elbow to Air Channel)  
23 Gasket (Flame Rec./Spark Electrode)  
24 Spark Electrode (w/Gasket)  
7250P-063  
7250P-005  
PVC Black Tubing 1/8 ID (Thermodisc Flue ECO)  
Relief Valve  
7250P-421 (T50M)  
7250P-058 (T80M)  
7250P-069  
Thermistor  
25 Screws M4 x 8MM (Probe/Electrode)  
26 Flame Rectification Probe (w/Gasket)  
Water Pressure Switch  
ECO High Limit Sensor  
7250P-049  
27 Screws Torx M5 X 22MM (Air Channel to Burner Door) 7250P-206  
8
9
Aluminum Elbow  
7250P-445  
7250P-061  
7250P-003  
7250P-144  
7250P-085  
7250P-644  
28 Air Channel  
7250P-178  
7250P-170  
7500P-067  
7250P-169  
7250P-702  
7250P-070  
Screws M5 X 25MM (Aluminum Elbow to Air Channel)  
29 Gasket (Burner Door to Air Channel)  
30 Nuts M6 (Burner Door)  
31 Burner Door  
10 Gasket (Aluminum Elbow to Air Channel)  
11 Gasket (Aluminum Elbow to Combustion Blower)  
12 Combustion Blower  
32 Burner Door Ceramic Refractory  
33 Gasket (Burner)  
13 Gas Valve Adapter Plate (w/Screws)  
14 Screws M5 x 12MM (Gas Valve Adapter Plate)  
15 Swirl Plate  
7250P-484  
34 Burner  
7250P-216 (T50M)  
7500P-091 (T50M)  
7500P-092 (T80M)  
7250P-448 (T50M)  
7250P-449 (T80M)  
N/A  
7250P-248 (T80M)  
7250P-204  
7250P-704  
7500P-109  
7250P-160  
7250P-212  
SN1018  
35 Screws (Burner)  
16 Dungs Gas Valve  
36 Screw M4 x 8MM (Ceramic Target Wall)  
37 Washer M4 (Ceramic Target Wall)  
38 Ceramic Target Wall  
17 Gas Piping Assembly (w/Shut-off Valve, Screws)  
18 Screws M4 x 12MM (Gas Valve Piping Assy)  
19 O-Ring (Gas Valve Piping Assy)  
7500P-099  
39 Brass 90 Street Elbow 3/4 NPT  
40 Brass Nipple 3/4 NPT x 3"  
7500P-094  
20 Screws M4 x 18MM (Gas Valve)  
Screws M4 x 19MM (Gas Valve)  
7250P-716 (T50M)  
7250P-717 (T80M)  
7250P-060  
41 Brass 90 Elbow 3/4 NPT  
42 Gasket (Top Flue Exhaust to Module)  
43 Top Flue Exhaust  
7250P-313  
7250P-428  
7250P-394  
21 Screw M5 x 20MM (Combustion Blower)  
63  
GAS-FIRED BOILER  
Boiler Manual  
PART 15: MAINTENANCE (CONTINUED)  
1
2
4
3
16  
5
7
6
11  
15  
12  
14  
9
13  
8
BOILER  
SWITCH  
CONDENSATE  
OUTLET  
17  
18  
19  
20  
21  
10  
22  
23  
24  
25  
26  
27  
28  
31  
30  
T50M/T80M  
T50M/T80M  
29  
REPLACEMENT PARTS  
Item  
#
Item  
Description  
Exhaust Vent Pipe - 2" PVC  
Pipe Coupling  
Part #  
#
Description  
Part #  
1
2
3
4
5
6
N/A  
17 5 Pin Wiring Harness (location)  
18 9 Pin Wiring Harness (location)  
19 Low Voltage Wiring Harness (location)  
7250P-696  
7250P-697  
7250P-700  
F3001  
Exhaust Manifold Tube  
Air Inlet Baffle  
7250P-444  
7250P-145  
20 Hose Barb 1/4 x 10-32 (Blocked Vent Pressure Switch) 7250P-154  
Plastic Tubing 3/16" ID (Blocked Vent Pressure Switch) 7000P-805  
21 O-Ring 007 (Blocked Vent Pressure Switch)  
7250P-152  
7250P-153  
Control Board Display (w/Ribbon Cable)  
7250P-332  
22 S.S. Hex Nut 10-32 (Blocked Vent Pressure Switch)  
7
8
Blocked Vent Pressure Switch  
7250P-150  
7250P-133  
23 S.S. Hex Nuts  
7250P-559  
7250P-427  
Screws # 8 x 1/2" (Blocked Vent Pressure Switch)  
24 Gasket (Top Flue Exhaust Pipe)  
9
Cover  
N/A  
25 Poly Plug 3/4 NPT (Condensate Assy)  
26 PVC Tee Sch. 40 3/4 NPT (Condensate Assy)  
27 Screw # 8 x 1/2" (Condensate Assy)  
28 PVC Nipple Sch. 80 3/4 NPT (Condensate Assy)  
29 Cable Clamp (Condensate Assy)  
30 Condensate Hose Assy  
7250P-647  
7250P-646  
7250P-133  
7250P-648  
7250P-649  
7250P-460  
7250P-302  
10 Brass Nipple 1 x 1-1/4 x 4-5/8"  
11 Fuse (Control Board)  
7250P-008  
7250P-378  
7250P-317  
7250P-352  
7250P-651  
7250P-114  
7250P-133  
12 Control Board (w/Fuse)  
13 Control Board Hold Down Clips  
14 Control Board Mounting Panel (w/Screws)  
15 Electrical Box (w/Screws, Covers)  
16 Screws # 8 x 1/2" (Electrical Box)  
31 Spring Clamp (Condensate Assy)  
64  
GAS-FIRED BOILER  
Boiler Manual  
PART 15: MAINTENANCE (CONTINUED)  
12  
13  
14  
3
2
7
1
5
6
8
4
1
9
10  
15  
11  
16  
17  
18  
35  
19  
20  
34  
33  
32  
30  
31  
29  
28  
21  
27  
25  
24  
23  
26  
80M/140M/199M  
19  
22  
REPLACEMENT PARTS  
Item #  
Description  
Part #  
Item #  
Description  
Part #  
7250P-685 (80M)  
7250P-687 (140M/199M)  
7250P-005  
1
2
3
4
Thermistor  
Thermodisc Flue ECO 210 F  
Steel Push Retainer (Thermodisc Flue ECO)  
7250P-667  
7250P-089  
7250P-151  
18  
Air/Gas Channel  
19  
20  
Gasket (Flame Rec./Spark Electrode)  
Spark Electrode (w/Gasket)  
PVC Black Tubing 1/8 ID (Thermodisc Flue ECO) 7250P-311  
7500P-040  
5
6
7
Water Pressure Switch  
Eco/High Limit Sensor  
Dungs Gas Valve  
7250P-096  
21  
22  
23  
Screws M4 x 8MM (Probe/Electrode)  
Flame Rectification Probe (w/Gasket)  
7250P-069  
7500P-039  
7250P-019  
7250P-450 (80M)  
Screws Torx M5 x 22M (Air/Gas Channel to Burner Door) 7250P-206  
7250P-451 (140M)  
7250P-452 (199M)  
7500P-099  
24  
25  
Gasket (Air/Gas Channel to Burner)  
NIT Burner  
7500P-074  
7500P-016 (80M)  
7250P-102 (140M)  
7250P-117 (199M)  
7500P-067  
8
9
Screws M4 x 12MM (Gas Valve)  
Swirl Plate  
7500P-092 (80M)  
7500P-093 (140M/199M)  
7250P-644  
26  
27  
Nut M6 (Burner Door)  
Burner Door  
10 Gas Valve Adapter Plate (w/Screws)  
11 Screws M5 x 12MM (Gas Valve Adapter Plate)  
12 Relief Valve  
7250P-684  
7250P-484  
28  
29  
30  
31  
32  
33  
34  
35  
Burner Door Ceramic Refractory  
7250P-702  
7250P-704  
7500P-109  
7250P-160  
N/A  
7250P-080  
Screw M4 x 8MM (Ceramic Target Wall)  
Washer M4 (Ceramic Target Wall)  
Ceramic Target Wall  
13 Brass Nipple 3/4 NPT x 3"  
SN1018  
14 Brass 90 Elbow - 3/4 NPT  
7250P-313  
15 Combustion Blower (w/Gasket)  
7250P-084 (80M)  
7250P-086 (140M)  
7250P-087 (199M)  
7250P-478  
Screws M4 x 30MM Allen Head (Gas Piping Assy)  
Screws M4 x 12MM Allen Head (Gas Piping Assy)  
Gas Piping Assembly (w/Shut-off Valve, Screws)  
Welded Module  
N/A  
7250P-705  
7250P-298 (80M)  
7250P-299 (140M)  
7250P-300 (199M)  
16 Screws M5 x 14MM (Combustion Blower)  
17 Gasket (Air/Gas Channel to Combustion Blower) 7500P-075  
Fig. 15-1  
65  
GAS-FIRED BOILER  
Boiler Manual  
PART 15: MAINTENANCE (CONTINUED)  
1
2
6
8
7
9
3
4
11  
16  
10  
12  
13  
BOILER  
SWITCH  
5
CONDENSATE  
OUTLET  
30  
29  
28  
27  
14  
26  
25  
15  
16  
24  
23  
22  
21  
20  
17  
19  
18  
80M/140M/199M  
REPLACEMENT PARTS  
Item  
#
Item  
Description  
Part #  
Description  
Part #  
#
1
Blocked Vent Pressure Switch  
7250P-150  
16 Cabinet Latch and Gasket Kit (w/Screws)  
7250P-668 (80M)  
2
3
4
Screws # 8 x 1/2" (Blocked Vent Pressure Switch)  
Low Voltage Wiring Harness (location)  
9 Pin Wiring Harness (location)  
7250P-133  
7250P-700  
7250P-697  
7250P-669 (140M/199M)  
7250P-673  
17 Leveling Foot  
18 Condensate Hose Assy  
7250P-082  
5
6
7
8
9
5 Pin Wiring Harness (location)  
7250P-696  
7250P-651  
19 PVC Nipple Sch. 80 3/4 NPT (Condensate Assy)  
20 Spring Clamp (Condensate Assy)  
21 PVC Tee Sch. 40 3/4 NPT (Condensate Assy)  
22 Cable Clamp (Condensate Assy)  
23 Screw # 8 x 1/2 Self Tapping (Condensate Assy)  
24 Poly Plug 3/4 NPT (Condensate Assy)  
25 Band Clamp (Exhaust Assy)  
7250P-648  
7250P-302  
7250P-646  
7250P-649  
7250P-133  
7250P-647  
CA2000  
Control Board Mounting Panel (w/Screws)  
Screw 1/4-20 x 1/2" (Control Board Mounting Panel) 7250P-184  
Control Board Hold Down Clips  
Control Board (w/Fuse)  
7250P-352  
7250P-317  
7250P-378  
7250P-332  
7250P-707  
7250P-133  
7250P-221  
7250P-235 (80M)  
10 Fuse (Control Board)  
11 Control Board Display (w/Ribbon Cable)  
12 Electrical Box (w/Screws)  
26 PVC Pipe Sch. 40 3" (Exhaust Assy)  
27 S.S. Hex Nut 10-32 (Blocked Vent Pressure Switch)  
28 O-Ring 007 (Blocked Vent Pressure Switch)  
7250P-242  
7250P-153  
7250P-152  
13 Screws # 8 x 1/2" Self Tapping (Electrical Box)  
14 Brass Nipple 1 x 1-1/4 x 3-3/4"  
15 Cabinet Cover  
29 Hose Barb 1/4 x 10-32 (Blocked Vent Pressure Switch) 7250P-154  
7250P-231 (140M/199M) 30 Plastic Tubing 3/16" ID (Blocked Vent Pressure Switch 7000P-805  
Fig. 15-2  
66  
GAS-FIRED BOILER  
Boiler Manual  
PART 15: MAINTENANCE (CONTINUED)  
2
3
4
1
5
4
14  
7
12  
13  
10  
8
9
11  
15  
16  
17  
18  
6
19  
20  
31  
30  
29  
28  
21  
24  
23  
27  
25  
399M  
26  
19  
22  
REPLACEMENT PARTS  
Item  
#
Item  
Description  
Thermodisc Flue ECO 210 F  
Steel Push Retainer (Thermodisc Flue ECO)  
Part #  
Description  
Part #  
#
1
2
3
4
5
6
7250P-089  
7250P-151  
16 Screws M5 x 14MM (Combustion Blower)  
7250P-478  
17 Gasket (Air/Gas Channel to Combustion Blower)  
18 Air/Gas Channel  
7500P-075  
7250P-687  
7250P-005  
7500P-040  
7250P-069  
7250P-049  
PVC Black Tubing 1/8 ID (Thermodisc Flue ECO) 7250P-311  
Thermistor  
7250P-667  
7250P-096  
7250P-695  
19 Gasket (Flame Rec./Spark Electrode)  
20 Spark Electrode (w/Gasket)  
Water Pressure Switch  
Krom Schroder Gas Valve Assembly  
21 Screws M4 x 8MM (Probe/Electrode)  
22 Flame Rectification Probe (w/Gasket)  
7
8
Gas Valve Solenoid Kit  
Eco/High Limit Sensor  
7250P-701  
7250P-019  
23 Screws Torx M5 x 22MM (Air/Gas Channel to Burner Door) 7250P-206  
9
Screws M4 x 16MM (Air/Gas Mixer)  
7250P-708  
24 Gasket (Air/Gas Channel to Burner)  
7500P-074  
10 Welded Module  
7250P-622  
7250P-545  
25 NIT Burner  
7250P-703  
7500P-067  
11 Air/Gas Mixer (w/Rings, Cork Gasket, Screws)  
26 Nuts M6 (Burner Door)  
12 Relief Valve  
7250P-080  
SN1018  
27 Burner Door  
7250P-684  
7250P-702  
7250P-704  
7500P-109  
7250P-160  
13 Brass Nipple 3/4 NPT x 3"  
14 Brass 90 Elbow - 3/4 NPT  
15 Combustion Blower (w/Gasket)  
28 Burner Door Ceramic Refractory  
29 Screw M4 x 8MM (Ceramic Target Wall)  
30 Washer M4 (Ceramic Target Wall)  
31 Ceramic Target Wall  
7250P-313  
7250P-518  
67  
GAS-FIRED BOILER  
Boiler Manual  
PART 15: MAINTENANCE (CONTINUED)  
1
2
4
29  
30  
31  
6
3
7
14  
5
9
10  
11  
8
28  
27  
BOILER  
SWITCH  
CONDENSATE  
OUTLET  
26  
25  
12  
13  
14  
24  
22  
23  
21  
20  
15  
19  
16  
17  
18  
399M  
REPLACEMENT PARTS  
Item  
#
Item  
Description  
Part #  
#
Description  
Part #  
1
Blocked Vent Pressure Switch  
7250P-150  
7250P-133  
7250P-580  
7250P-651  
17 PVC Nipple Sch. 80 3/4 NPT (Condensate Assembly)  
18 Spring Clamp (Condensate Assembly)  
7250P-648  
7250P-302  
7250P-646  
7250P-649  
2
3
4
Screws # 8 x 1/2" Self Tapping (Blocked Vent Pressure Switch)  
Relay Board  
19 PVC Tee Sch. 30 3/4 NPT (Condensate Assembly)  
20 Cable Clamp (Condensate Assembly)  
Control Board Mounting Panel (w/Screws)  
5
6
7
8
9
Screw 1/4-20 x 1/2" (Control Board Mounting Panel)  
Control Board Hold Down Clips  
Control Board (w/Fuse)  
7250P-184  
7250P-352  
7250P-317  
7250P-378  
7250P-332  
7250P-707  
7250P-133  
7250P-514  
7250P-501  
7250P-671  
7250P-673  
7250P-082  
21 Screw # 8 x 1/2" Self Tapping (Condensate Assembly)  
22 Poly Plug 3/4 NPT (Condensate Assembly)  
23 Band Clamp (Exhaust Assembly)  
7250P-133  
7250P-647  
7250P-549  
7250P-524  
7250P-153  
7250P-152  
Fuse (Control Board)  
24 PVC Pipe Sch. 40 4" (Exhaust Assembly)  
25 S.S. Hex Nut 10-32 (Blocked Vent Pressure Switch)  
26 O-Ring 007 (Blocked Vent Pressure Switch)  
Control Board Display (w/Ribbon Cable)  
10 Electrical Box (w/Screws)  
11 Screws # 8 x 1/2" Self Tapping (Electrical Box)  
12 Brass Nipple 1-1/2 x 2 x 3-3/4"  
13 Cabinet Cover  
27 S.S. Hose Barb 1/4 x 10-32 (Blocked Vent Pressure Switch) 7250P-154  
28 Plastic Tubing 3/16" ID (Blocked Vent Pressure Switch)  
29 5 Pin Wiring Harness (location)  
7000P-805  
7250P-696  
7250P-697  
7250P-699  
14 Cabinet Latch and Gasket Kit (w/Screws)  
15 Leveling Foot  
30 9 Pin Wiring Harness (location)  
31 Low Voltage Wiring Harness (location)  
16 Condensate Hose Assy  
68  
GAS-FIRED BOILER  
Boiler Manual  
69  
GAS-FIRED BOILER  
Boiler Manual  
70  
GAS-FIRED BOILER  
Boiler Manual  
71  
MAINTENANCE NOTES  
72  
MAINTENANCE NOTES  
73  
MAINTENANCE NOTES  
74  
© 2007 Heat Transfer Products, Inc.  
LP-185 REV. 2/20/07  

Realistic Car Stereo System PRO 53 User Manual
PYLE Audio PQA4100 User Manual
Panasonic Camcorder AG HPX250 User Manual
Olympus EPL2BLK User Manual
MTX Audio MTX Thunder TA4501 User Manual
Milwaukee 9571 User Manual
Life is good Blu ray Disc Player BD530 User Manual
Kenwood KFC 1685 User Manual
JVC LYT1829 001D User Manual
JVC GY HM700CHE User Manual