General-Purpose AC Servo
J2-Super Series
Built-In Positioning Function
MODEL
MR-J2S- CP
SERVO AMPLIFIER
INSTRUCTION MANUAL
G
Safety Instructions
(Always read these instructions before using the equipment.)
Do not attempt to install, operate, maintain or inspect the servo amplifier and servo motor until you have read
through this Instruction Manual, Installation guide, Servo motor Instruction Manual and appended documents
carefully and can use the equipment correctly. Do not use the servo amplifier and servo motor until you have a
full knowledge of the equipment, safety information and instructions.
In this Instruction Manual, the safety instruction levels are classified into "WARNING" and "CAUTION".
Indicates that incorrect handling may cause hazardous conditions,
WARNING
resulting in death or severe injury.
Indicates that incorrect handling may cause hazardous conditions,
CAUTION
resulting in medium or slight injury to personnel or may cause physical
damage.
Note that the CAUTION level may lead to a serious consequence according to conditions. Please follow the
instructions of both levels because they are important to personnel safety.
What must not be done and what must be done are indicated by the following diagrammatic symbols:
: Indicates what must not be done. For example, "No Fire" is indicated by
: Indicates what must be done. For example, grounding is indicated by
.
.
In this Instruction Manual, instructions at a lower level than the above, instructions for other functions, and so
on are classified into "POINT".
After reading this installation guide, always keep it accessible to the operator.
A - 1
1. To prevent electric shock, note the following:
WARNING
Before wiring or inspection, turn off the power and wait for 15 minutes or more until the charge lamp turns
off. Then, confirm that the voltage between P and N is safe with a voltage tester and others. Otherwise, an
electric shock may occur. In addition, always confirm from the front of the servo amplifier, whether the
charge lamp is off or not.
Connect the servo amplifier and servo motor to ground.
Any person who is involved in wiring and inspection should be fully competent to do the work.
Do not attempt to wire the servo amplifier and servo motor until they have been installed. Otherwise, you
may get an electric shock.
Operate the switches with dry hand to prevent an electric shock.
The cables should not be damaged, stressed, loaded, or pinched. Otherwise, you may get an electric shock.
During power-on or operation, do not open the front cover of the servo amplifier. You may get an electric
shock.
Do not operate the servo amplifier with the front cover removed. High-voltage terminals and charging area
are exposed and you may get an electric shock.
Except for wiring or periodic inspection, do not remove the front cover even of the servo amplifier if the
power is off. The servo amplifier is charged and you may get an electric shock.
2. To prevent fire, note the following:
CAUTION
Install the servo amplifier, servo motor and regenerative resistor on incombustible material. Installing them
directly or close to combustibles will lead to a fire.
Always connect a magnetic contactor (MC) between the main circuit power supply and L1, L2, and L3 of
the servo amplifier, and configure the wiring to be able to shut down the power supply on the side of the
servo amplifier’s power supply. If a magnetic contactor (MC) is not connected, continuous flow of a large
current may cause a fire when the servo amplifier malfunctions.
When a regenerative resistor is used, use an alarm signal to switch main power off. Otherwise, a
regenerative transistor fault or the like may overheat the regenerative resistor, causing a fire.
3. To prevent injury, note the follow
CAUTION
Only the voltage specified in the Instruction Manual should be applied to each terminal, Otherwise, a
burst, damage, etc. may occur.
Connect the terminals correctly to prevent a burst, damage, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands and parts (cables, etc.)
with the servo amplifier heat sink, regenerative resistor, servo motor, etc.since they may be hot while
power is on or for some time after power-off. Their temperatures may be high and you may get burnt or a
parts may damaged.
During operation, never touch the rotating parts of the servo motor. Doing so can cause injury.
A - 2
4. Additional instructions
The following instructions should also be fully noted. Incorrect handling may cause a fault, injury, electric
shock, etc.
(1) Transportation and installation
CAUTION
Transport the products correctly according to their weights.
Stacking in excess of the specified number of products is not allowed.
Do not carry the servo motor by the cables, shaft or encoder.
Do not hold the front cover to transport the servo amplifier. The servo amplifier may drop.
Install the servo amplifier in a load-bearing place in accordance with the Instruction Manual.
Do not climb or stand on servo equipment. Do not put heavy objects on equipment.
The servo amplifier and servo motor must be installed in the specified direction.
Leave specified clearances between the servo amplifier and control enclosure walls or other equipment.
Do not install or operate the servo amplifier and servo motor which has been damaged or has any parts
missing.
Provide adequate protection to prevent screws and other conductive matter, oil and other combustible
matter from entering the servo amplifier and servo motor.
Do not drop or strike servo amplifier or servo motor. Isolate from all impact loads.
When you keep or use it, please fulfill the following environmental conditions.
Conditions
Environment
Servo amplifier
0 to 55 (non-freezing)
32 to 131 (non-freezing)
20 to 65 (non-freezing)
4 to 149 (non-freezing)
Servo motor
0 to 40 (non-freezing)
32 to 104 (non-freezing)
15 to 70 (non-freezing)
5 to 158 (non-freezing)
In
[
[
[
[
]
]
]
]
operation
Ambient
temperature
In storage
Ambient
humidity
In operation
In storage
90%RH or less (non-condensing)
90%RH or less (non-condensing)
80%RH or less (non-condensing)
Ambience
Altitude
Indoors (no direct sunlight) Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280 ft) above sea level
HC-KFS Series
HC-MFS Series
HC-UFS13 to 73
HC-SFS81
X
Y : 49
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72 152
HC-SFS121 201
HC-SFS202 352
HC-SFS203 353
HC-UFS202
X
Y : 24.5
[m/s2]
5.9 or less
X : 24.5
Y : 49
X : 24.5
Y : 29.4
HC-SFS301
(Note)
Vibration
HC-KFS Series
HC-MFS Series
HC-UFS 13 to 73
HC-SFS81
X
Y : 161
HC-SFS52 to 152
HC-SFS53 to 153
HC-RFS Series
HC-UFS 72 152
HC-SFS121 201
HC-SFS202 352
HC-SFS203 353
HC-UFS202
X
Y : 80
[ft/s2]
19.4 or less
X : 80
Y : 161
X : 80
Y : 96
HC-SFS301
Note. Except the servo motor with reduction gear.
A - 3
CAUTION
Securely attach the servo motor to the machine. If attach insecurely, the servo motor may come off during
operation.
The servo motor with reduction gear must be installed in the specified direction to prevent oil leakage.
Take safety measures, e.g. provide covers, to prevent accidental access to the rotating parts of the servo
motor during operation.
Never hit the servo motor or shaft, especially when coupling the servo motor to the machine. The encoder
may become faulty.
Do not subject the servo motor shaft to more than the permissible load. Otherwise, the shaft may break.
When the equipment has been stored for an extended period of time, consult Mitsubishi.
(2) Wiring
CAUTION
Wire the equipment correctly and securely. Otherwise, the servo motor may misoperate.
Do not install a power capacitor, surge absorber or radio noise filter (FR-BIF option) between the servo
motor and servo amplifier.
Connect the output terminals (U, V, W) correctly. Otherwise, the servo motor will operate improperly.
Connect the servo motor power terminal (U, V, W) to the servo motor power input terminal (U, V, W)
directly. Do not let a magnetic contactor, etc. intervene.
Servo amplifier
Servo motor
Servo amplifier
Servo motor
U
V
U
V
U
V
U
V
M
M
W
W
W
W
Do not connect AC power directly to the servo motor. Otherwise, a fault may occur.
The surge absorbing diode installed on the DC output signal relay of the servo amplifier must be wired in
the specified direction. Otherwise, the emergency stop (EMG) and other protective circuits may not
operate.
Servo amplifier
Servo amplifier
COM
COM
(24VDC)
(24VDC)
Control
output
signal
Control
output
signal
RA
RA
When the cable is not tightened enough to the terminal block (connector), the cable or terminal block
(connector) may generate heat because of the poor contact. Be sure to tighten the cable with specified
torque.
A - 4
(3) Test run adjustment
CAUTION
Before operation, check the parameter settings. Improper settings may cause some machines to perform
unexpected operation.
The parameter settings must not be changed excessively. Operation will be insatiable.
(4) Usage
CAUTION
Provide an external emergency stop circuit to ensure that operation can be stopped and power switched
off immediately.
Any person who is involved in disassembly and repair should be fully competent to do the work.
Before resetting an alarm, make sure that the run signal of the servo amplifier is off to prevent an accident.
A sudden restart is made if an alarm is reset with the run signal on.
Do not modify the equipment.
Use a noise filter, etc. to minimize the influence of electromagnetic interference, which may be caused by
electronic equipment used near the servo amplifier.
Burning or breaking a servo amplifier may cause a toxic gas. Do not burn or break a servo amplifier.
Use the servo amplifier with the specified servo motor.
The electromagnetic brake on the servo motor is designed to hold the motor shaft and should not be used
for ordinary braking.
For such reasons as service life and mechanical structure (e.g. where a ballscrew and the servo motor are
coupled via a timing belt), the electromagnetic brake may not hold the motor shaft. To ensure safety,
install a stopper on the machine side.
(5) Corrective actions
CAUTION
When it is assumed that a hazardous condition may take place at the occur due to a power failure or a
product fault, use a servo motor with electromagnetic brake or an external brake mechanism for the
purpose of prevention.
Configure the electromagnetic brake circuit so that it is activated not only by the servo amplifier signals but
also by an external forced stop (EMG).
Contacts must be open when
servo-off, when an trouble (ALM)
and when an electromagnetic brake
interlock (MBR).
Circuit must be
opened during
forced stop (EMG).
Servo motor
RA EMG
24VDC
Electromagnetic brake
When any alarm has occurred, eliminate its cause, ensure safety, and deactivate the alarm before
restarting operation.
When power is restored after an instantaneous power failure, keep away from the machine because the
machine may be restarted suddenly (design the machine so that it is secured against hazard if restarted).
A - 5
(6) Maintenance, inspection and parts replacement
CAUTION
With age, the electrolytic capacitor of the servo amplifier will deteriorate. To prevent a secondary accident
due to a fault, it is recommended to replace the electrolytic capacitor every 10 years when used in general
environment.
Please consult our sales representative.
(7) General instruction
To illustrate details, the equipment in the diagrams of this Specifications and Instruction Manual may have
been drawn without covers and safety guards. When the equipment is operated, the covers and safety
guards must be installed as specified. Operation must be performed in accordance with this Specifications
and Instruction Manual.
About processing of waste
When you discard servo amplifier, a battery (primary battery), and other option articles, please follow the law of
each country (area).
FOR MAXIMUM SAFETY
These products have been manufactured as a general-purpose part for general industries, and have not
been designed or manufactured to be incorporated in a device or system used in purposes related to
human life.
Before using the products for special purposes such as nuclear power, electric power, aerospace,
medicine, passenger movement vehicles or underwater relays, contact Mitsubishi.
These products have been manufactured under strict quality control. However, when installing the product
where major accidents or losses could occur if the product fails, install appropriate backup or failsafe
functions in the system.
EEP-ROM life
The number of write times to the EEP-ROM, which stores parameter settings, etc., is limited to 100,000. If
the total number of the following operations exceeds 100,000, the servo amplifier and/or converter unit may
fail when the EEP-ROM reaches the end of its useful life.
Write to the EEP-ROM due to parameter setting changes
Home position setting in the absolute position detection system
Write to the EEP-ROM due to device changes
Write to the EEP-ROM due to point table changes
PRECAUTIONS FOR CHOOSING THE PRODUCTS
Mitsubishi will not be held liable for damage caused by factors found not to be the cause of Mitsubishi;
machine damage or lost profits caused by faults in the Mitsubishi products; damage, secondary damage,
accident compensation caused by special factors unpredictable by Mitsubishi; damages to products other
than Mitsubishi products; and to other duties.
A - 6
COMPLIANCE WITH EC DIRECTIVES
1. WHAT ARE EC DIRECTIVES?
The EC directives were issued to standardize the regulations of the EU countries and ensure smooth
distribution of safety-guaranteed products. In the EU countries, the machinery directive (effective in
January, 1995), EMC directive (effective in January, 1996) and low voltage directive (effective in January,
1997) of the EC directives require that products to be sold should meet their fundamental safety
requirements and carry the CE marks (CE marking). CE marking applies to machines and equipment
into which servo amplifiers have been installed.
(1) EMC directive
The EMC directive applies not to the servo units alone but to servo-incorporated machines and
equipment. This requires the EMC filters to be used with the servo-incorporated machines and
equipment to comply with the EMC directive. For specific EMC directive conforming methods, refer to
the EMC Installation Guidelines (IB(NA)67310).
(2) Low voltage directive
The low voltage directive applies also to servo units alone. Hence, they are designed to comply with
the low voltage directive.
This servo is certified by TUV, third-party assessment organization, to comply with the low voltage
directive.
(3) Machine directive
Not being machines, the servo amplifiers need not comply with this directive.
2. PRECAUTIONS FOR COMPLIANCE
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier series :MR-J2S-10CP to MR-J2S-700CP
MR-J2S-10CP1 to MR-J2S40CP1
Servo motor series
:HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
HC-LFS
(2) Configuration
Control box
Reinforced
insulating type
24VDC
power
supply
Reinforced
insulating
transformer
No-fuse
breaker
Magnetic
contactor
Servo
motor
Servo
amplifier
MC
M
NFB
(3) Environment
Operate the servo amplifier at or above the contamination level 2 set forth in IEC60664-1. For this
purpose, install the servo amplifier in a control box which is protected against water, oil, carbon, dust,
dirt, etc. (IP54).
A - 7
(4) Power supply
(a) Operate the servo amplifier to meet the requirements of the overvoltage category II set forth in
IEC60664-1. For this purpose, a reinforced insulating transformer conforming to the IEC or EN
Standard should be used in the power input section.
(b) When supplying interface power from external, use a 24VDC power supply which has been
insulation-reinforced in I/O.
(5) Grounding
(a) To prevent an electric shock, always connect the protective earth (PE) terminals (marked ) of the
servo amplifier to the protective earth (PE) of the control box.
(b) Do not connect two ground cables to the same protective earth (PE) terminal (marked
connect the cables to the terminals one-to-one.
). Always
PE terminals
PE terminals
(c) If a leakage current breaker is used to prevent an electric shock, the protective earth (PE) terminals
(marked ) of the servo amplifier must be connected to the corresponding earth terminals.
(6) Wiring
(a) The cables to be connected to the terminal block of the servo amplifier must have crimping
terminals provided with insulating tubes to prevent contact with adjacent terminals.
Crimping terminal
Insulating tube
Cable
(b) Use the servo motor side power connector which complies with the EN Standard. The EN Standard
compliant power connector sets are available from us as options. (Refer to section 14.1.4)
(7) Auxiliary equipment and options
(a) The circuit breaker and magnetic contactor used should be the EN or IEC standard-compliant
products of the models described in section 14.2.2.
(b) The sizes of the cables described in section 14.2.1 meet the following requirements. To meet the
other requirements, follow Table 5 and Appendix C in EN60204-1.
Ambient temperature: 40 (104) [
Sheath: PVC (polyvinyl chloride)
(
)]
Installed on wall surface or open table tray
(c) Use the EMC filter for noise reduction.
(8) Performing EMC tests
When EMC tests are run on a machine/device into which the servo amplifier has been installed, it
must conform to the electromagnetic compatibility (immunity/emission) standards after it has
satisfied the operating environment/electrical equipment specifications.
For the other EMC directive guidelines on the servo amplifier, refer to the EMC Installation
Guidelines (IB(NA)67310).
A - 8
CONFORMANCE WITH UL/C-UL STANDARD
(1) Servo amplifiers and servo motors used
Use the servo amplifiers and servo motors which comply with the standard model.
Servo amplifier series :MR-J2S-10CP to MR-J2S-700CP
MR-J2S-10CP1 to MR-J2S-40CP1
Servo motor series
:HC-KFS
HC-MFS
HC-SFS
HC-RFS
HC-UFS
HA-LFS
HC-LFS
(2) Installation
Install a cooling fan of 100CFM (2.8m3/min) air flow 4 [in] (10.16 [cm]) above the servo amplifier or
provide cooling of at least equivalent capability.
(3) Short circuit rating
This servo amplifier conforms to the circuit whose peak current is limited to 5000A or less. Having
been subjected to the short-circuit tests of the UL in the alternating-current circuit, the servo
amplifier conforms to the above circuit.
(4) Capacitor discharge time
The capacitor discharge time is as listed below. To ensure safety, do not touch the charging section for
15 minutes after power-off.
Servo amplifier
Discharge time [min]
MR-J2S-10CP(1) 20CP(1)
MR-J2S-40CP(1) 60CP
MR-J2S-70CP to 350CP
MR-J2S-500CP 700CP
1
2
3
5
(5) Options and auxiliary equipment
Use UL/C-UL standard-compliant products.
(6) Attachment of a servo motor
For the flange size of the machine side where the servo motor is installed, refer to “CONFORMANCE
WITH UL/C-UL STANDARD” in the Servo Motor Instruction Manual.
(7) About wiring protection
For installation in United States, branch circuit protection must be provided, in accordance with the
National Electrical Code and any applicable local codes.
For installation in Canada, branch circuit protection must be provided, in accordance with the Canada
Electrical Code and any applicable provincial codes.
<<About the manuals>>
This Instruction Manual and the MELSERVO Servo Motor Instruction Manual are required if you use
the MR-J2S-CP for the first time. Always purchase them and use the MR-J2S-CP safely.
Relevant manuals
Manual name
MELSERVO-J2-Super Series To Use the AC Servo Safely
MELSERVO Servo Motor Instruction Manual
EMC Installation Guidelines
Manual No.
IB(NA)0300010
SH(NA)3181
IB(NA)67310
A - 9
MEMO
A - 10
CONTENTS
1. FUNCTIONS AND CONFIGURATION
1- 1 to 1-26
1.1 Introduction.............................................................................................................................................. 1- 1
1.1.1 Function block diagram ................................................................................................................... 1- 1
1.1.2 System configuration........................................................................................................................ 1- 4
1.1.3 I/O devices ......................................................................................................................................... 1- 9
1.2 Servo amplifier standard specifications............................................................................................... 1-10
1.3 Function list ............................................................................................................................................ 1-12
1.4 Model code definition ............................................................................................................................. 1-13
1.5 Combination with servo motor.............................................................................................................. 1-14
1.6 Structure.................................................................................................................................................. 1-15
1.6.1 Part names ....................................................................................................................................... 1-15
1.6.2 Removal and reinstallation of the front cover .............................................................................. 1-19
1.7 Servo system with auxiliary equipment............................................................................................... 1-21
2. INSTALLATION
2- 1 to 2- 4
2.1 Environmental conditions ...................................................................................................................... 2- 1
2.2 Installation direction and clearances .................................................................................................... 2- 2
2.3 Keep out foreign materials ..................................................................................................................... 2- 3
2.4 Cable stress.............................................................................................................................................. 2- 4
3. SIGNALS AND WIRING
3- 1 to 3-42
3.1 Standard connection example ................................................................................................................ 3- 2
3.2 Internal connection diagram of servo amplifier ................................................................................... 3- 3
3.3 I/O signals................................................................................................................................................. 3- 4
3.3.1 Connectors and signal arrangements............................................................................................. 3- 4
3.3.2 Signal (devices) explanations .......................................................................................................... 3- 5
3.4 Detailed description of signals (devices) .............................................................................................. 3-13
3.4.1 Forward rotation start Reverse rotation start Temporary stop/restart................................. 3-13
3.4.2 Movement finish Rough match In position............................................................................... 3-14
3.4.3 Override............................................................................................................................................ 3-16
3.4.4 Torque limit...................................................................................................................................... 3-17
3.5 Alarm occurrence timing chart ............................................................................................................. 3-19
3.6 Interfaces................................................................................................................................................. 3-20
3.6.1 Common line .................................................................................................................................... 3-20
3.6.2 Detailed description of the interfaces............................................................................................ 3-21
3.7 Input power supply circuit..................................................................................................................... 3-25
3.7.1 Connection example ........................................................................................................................ 3-25
3.7.2 Terminals.......................................................................................................................................... 3-27
3.7.3 Power-on sequence........................................................................................................................... 3-28
3.8 Connection of servo amplifier and servo motor ................................................................................... 3-29
3.8.1 Connection instructions .................................................................................................................. 3-29
3.8.2 Connection diagram ........................................................................................................................ 3-29
3.8.3 I/O terminals .................................................................................................................................... 3-31
3.9 Servo motor with electromagnetic brake ............................................................................................. 3-33
1
3.10 Grounding ............................................................................................................................................. 3-37
3.11 Servo amplifier terminal block (TE2) wiring method....................................................................... 3-38
3.11.1 For the servo amplifier produced later than Jan. 2006............................................................. 3-38
3.11.2 For the servo amplifier produced earlier than Dec. 2005.......................................................... 3-40
3.12 Instructions for the 3M connector....................................................................................................... 3-42
4. OPERATION
4- 1 to 4-46
4.1 When switching power on for the first time.......................................................................................... 4- 1
4.1.1 Pre-operation checks ........................................................................................................................ 4- 1
4.1.2 Startup............................................................................................................................................... 4- 2
4.2 Automatic operation mode...................................................................................................................... 4- 5
4.2.1 What is automatic operation mode? ............................................................................................... 4- 5
4.2.2 Absolute value command system.................................................................................................... 4- 8
4.2.3 Incremental value command system............................................................................................. 4-10
4.2.4 Absolute value command/incremental value command specifying system ............................... 4-12
4.2.5 Automatic operation timing chart.................................................................................................. 4-14
4.2.6 Automatic continuous operation .................................................................................................... 4-15
4.3 Manual operation mode ......................................................................................................................... 4-22
4.3.1 Jog operation.................................................................................................................................... 4-22
4.3.2 Manual pulse generator operation................................................................................................. 4-24
4.4 Manual home position return mode ..................................................................................................... 4-26
4.4.1 Outline of home position return..................................................................................................... 4-26
4.4.2 Dog type home position return....................................................................................................... 4-28
4.4.3 Count type home position return ................................................................................................... 4-30
4.4.4 Data setting type home position return ........................................................................................ 4-31
4.4.5 Stopper type home position return ................................................................................................ 4-32
4.4.6 Home position ignorance (servo-on position defined as home position)..................................... 4-34
4.4.7 Dog type rear end reference home position return....................................................................... 4-35
4.4.8 Count type front end reference home position return.................................................................. 4-36
4.4.9 Dog cradle type home position return ........................................................................................... 4-37
4.4.10 Home position return automatic return function....................................................................... 4-38
4.4.11 Automatic positioning function to the home position ................................................................ 4-39
4.5 Absolute position detection system....................................................................................................... 4-40
4.6 Serial communication operation ........................................................................................................... 4-43
4.6.1 Positioning operation in accordance with point tables ................................................................ 4-43
4.6.2 Positioning operation....................................................................................................................... 4-44
4.6.3 Multidrop system............................................................................................................................. 4-44
4.6.4 Group designation ........................................................................................................................... 4-45
5. PARAMETERS
5- 1 to 5-24
5.1 Parameter list .......................................................................................................................................... 5- 1
5.1.1 Parameter write inhibit ................................................................................................................... 5- 1
5.1.2 List ..................................................................................................................................................... 5- 2
5.2 Detailed explanation .............................................................................................................................. 5-19
5.2.1 Electronic gear ................................................................................................................................. 5-19
5.2.2 Changing the status display screen............................................................................................... 5-20
5.2.3 S-pattern acceleration/deceleration ............................................................................................... 5-21
5.2.4 Analog output................................................................................................................................... 5-21
2
5.2.5 Changing the stop pattern using a limit switch...........................................................................5-24
5.2.6 Alarm history clear.......................................................................................................................... 5-24
5.2.7 Rough match output........................................................................................................................ 5-24
5.2.8 Software limit................................................................................................................................... 5-24
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6- 1 to 6-20
6.1 Specifications ........................................................................................................................................... 6- 1
6.2 System configuration............................................................................................................................... 6- 1
6.3 Station setting.......................................................................................................................................... 6- 3
6.4 Parameters............................................................................................................................................... 6- 4
6.5 Point table ................................................................................................................................................ 6- 6
6.6 Device assignment method..................................................................................................................... 6- 8
6.7 Test operation ......................................................................................................................................... 6-12
6.7.1 Jog operation.................................................................................................................................... 6-12
6.7.2 Positioning operation....................................................................................................................... 6-14
6.7.3 Motor-less operation........................................................................................................................ 6-16
6.7.4 Output signal (DO) forced output .................................................................................................. 6-17
6.7.5 Single-step feed................................................................................................................................ 6-18
6.8 Alarm history.......................................................................................................................................... 6-19
7. DISPLAY AND OPERATION
7- 1 to 7-26
7.1 Display flowchart..................................................................................................................................... 7- 1
7.2 Status display .......................................................................................................................................... 7- 2
7.2.1 Display transition............................................................................................................................. 7- 2
7.2.2 Display examples.............................................................................................................................. 7- 3
7.2.3 Status display list............................................................................................................................. 7- 4
7.3 Diagnosis mode........................................................................................................................................ 7- 5
7.3.1 Display transition............................................................................................................................. 7- 5
7.3.2 Diagnosis mode list........................................................................................................................... 7- 6
7.4 Alarm mode.............................................................................................................................................. 7- 8
7.4.1 Display transition............................................................................................................................. 7- 8
7.4.2 Alarm mode list................................................................................................................................. 7- 9
7.5 Point table mode..................................................................................................................................... 7-11
7.5.1 Point table transition ...................................................................................................................... 7-11
7.5.2 Point table mode setting screen sequence..................................................................................... 7-12
7.5.3 Operation method............................................................................................................................ 7-13
7.6 Parameter mode ..................................................................................................................................... 7-15
7.6.1 Parameter mode transition............................................................................................................. 7-15
7.6.2 Operation example .......................................................................................................................... 7-16
7.7 External I/O signal display.................................................................................................................... 7-18
7.8 Output signal (DO) forced output......................................................................................................... 7-19
7.9 Test operation mode............................................................................................................................... 7-20
7.9.1 Mode change..................................................................................................................................... 7-20
7.9.2 Jog operation.................................................................................................................................... 7-21
7.9.3 Positioning operation....................................................................................................................... 7-22
7.9.4 Motor-less operation........................................................................................................................ 7-23
7.10 Teaching function ................................................................................................................................. 7-24
7.10.1 Preparations for teaching ............................................................................................................. 7-24
3
7.10.2 Position data setting method........................................................................................................ 7-25
8. GENERAL GAIN ADJUSTMENT 8- 1 to 8-12
8.1 Different adjustment methods ............................................................................................................... 8- 1
8.1.1 Adjustment on a single servo amplifier.......................................................................................... 8- 1
8.1.2 Adjustment using MR Configurator (servo configuration software)........................................... 8- 2
8.2 Auto tuning .............................................................................................................................................. 8- 3
8.2.1 Auto tuning mode ............................................................................................................................. 8- 3
8.2.2 Auto tuning mode operation............................................................................................................ 8- 4
8.2.3 Adjustment procedure by auto tuning............................................................................................ 8- 5
8.2.4 Response level setting in auto tuning mode .................................................................................. 8- 6
8.3 Manual mode 1 (simple manual adjustment)....................................................................................... 8- 7
8.3.1 Operation of manual mode 1 ........................................................................................................... 8- 7
8.3.2 Adjustment by manual mode 1 ....................................................................................................... 8- 7
8.4 Interpolation mode ................................................................................................................................. 8-10
8.5 Differences in auto tuning between MELSERVO-J2 and MELSERVO-J2-Super.......................... 8-11
8.5.1 Response level setting ..................................................................................................................... 8-11
8.5.2 Auto tuning selection....................................................................................................................... 8-11
9. SPECIAL ADJUSTMENT FUNCTIONS
9- 1 to 9-10
9.1 Function block diagram .......................................................................................................................... 9- 1
9.2 Machine resonance suppression filter ................................................................................................... 9- 1
9.3 Adaptive vibration suppression control................................................................................................. 9- 3
9.4 Low-pass filter ......................................................................................................................................... 9- 4
9.5 Gain changing function........................................................................................................................... 9- 5
9.5.1 Applications....................................................................................................................................... 9- 5
9.5.2 Function block diagram ................................................................................................................... 9- 5
9.5.3 Parameters........................................................................................................................................ 9- 6
9.5.4 Gain changing operation.................................................................................................................. 9- 8
10. INSPECTION
10- 1 to 10- 2
11. TROUBLESHOOTING
11- 1 to 11- 10
11.1 Trouble at start-up ..............................................................................................................................11- 1
11.2 When alarm or warning has occurred...............................................................................................11- 2
11.2.1 Alarms and warning list ..............................................................................................................11- 2
11.2.2 Remedies for alarms.....................................................................................................................11- 3
11.2.3 Remedies for warnings.................................................................................................................11- 9
11.3 MR-DP60 external digital display error...........................................................................................11-10
12. OUTLINE DIMENSION DRAWINGS
12- 1 to 12- 8
12.1 Servo amplifiers...................................................................................................................................12- 1
12.2 Connectors............................................................................................................................................12- 6
4
13. CHARACTERISTICS
13- 1 to 13- 8
13.1 Overload protection characteristics...................................................................................................13- 1
13.2 Power supply equipment capacity and generated loss....................................................................13- 2
13.3 Dynamic brake characteristics...........................................................................................................13- 4
13.3.1 Dynamic brake operation.............................................................................................................13- 4
13.3.2 The dynamic brake at the load inertia moment........................................................................13- 6
13.4 Encoder cable flexing life....................................................................................................................13- 6
13.5 Inrush currents at power-on of main circuit and control circuit ....................................................13- 7
14. OPTIONS AND AUXILIARY EQUIPMENT
14- 1 to 14-50
14.1 Options..................................................................................................................................................14- 1
14.1.1 Regenerative options....................................................................................................................14- 1
14.1.2 FR-BU2 brake unit.......................................................................................................................14- 9
14.1.3 Power regeneration converter ....................................................................................................14-15
14.1.4 Cables and connectors.................................................................................................................14-18
14.1.5 Junction terminal block (MR-TB20)..........................................................................................14-26
14.1.6 Maintenance junction card (MR-J2CN3TM) ............................................................................14-28
14.1.7 External digital display (MR-DP60)..........................................................................................14-30
14.1.8 Manual pulse generator (MR-HDP01) ......................................................................................14-32
14.1.9 Battery (MR-BAT, A6BAT).........................................................................................................14-33
14.2 Auxiliary equipment ..........................................................................................................................14-34
14.2.1 Recommended wires....................................................................................................................14-34
14.2.2 Circuit breakers, fuses, magnetic contactors............................................................................14-36
14.2.3 Power factor improving reactors................................................................................................14-36
14.2.4 Relays............................................................................................................................................14-37
14.2.5 Surge absorbers ...........................................................................................................................14-37
14.2.6 Noise reduction techniques.........................................................................................................14-38
14.2.7 Leakage current breaker ............................................................................................................14-45
14.2.8 EMC filter.....................................................................................................................................14-47
14.2.9 Setting potentiometers for analog inputs..................................................................................14-50
15. COMMUNICATION FUNCTIONS
15- 1 to 15-40
15.1 Configuration .......................................................................................................................................15- 1
15.1.1 RS-422 configuration....................................................................................................................15- 1
15.1.2 RS-232C configuration.................................................................................................................15- 2
15.2 Communication specifications............................................................................................................15- 3
15.2.1 Communication overview.............................................................................................................15- 3
15.2.2 Parameter setting.........................................................................................................................15- 4
15.3 Protocol.................................................................................................................................................15- 5
15.4 Character codes ...................................................................................................................................15- 7
15.5 Error codes ...........................................................................................................................................15- 8
15.6 Checksum.............................................................................................................................................15- 8
15.7 Time-out operation..............................................................................................................................15- 9
15.8 Retry operation....................................................................................................................................15- 9
15.9 Initialization........................................................................................................................................15-10
15.10 Communication procedure example ...............................................................................................15-10
5
15.11 Command and data No. list.............................................................................................................15-11
15.11.1 Read commands.........................................................................................................................15-11
15.11.2 Write commands........................................................................................................................15-14
15.12 Detailed explanations of commands...............................................................................................15-17
15.12.1 Data processing..........................................................................................................................15-17
15.12.2 Status display ............................................................................................................................15-19
15.12.3 Parameter...................................................................................................................................15-20
15.12.4 External I/O signal statuses.....................................................................................................15-22
15.12.5 Input devices ON/OFF ..............................................................................................................15-24
15.12.6 Disable/enable of I/O devices (DIO) .........................................................................................15-25
15.12.7 Input devices ON/OFF (test operation)...................................................................................15-26
15.12.8 Test operation mode..................................................................................................................15-27
15.12.9 Output signal pin ON/OFF output signal (DO) forced output..............................................15-30
15.12.10 Alarm history...........................................................................................................................15-31
15.12.11 Current alarm..........................................................................................................................15-32
15.12.12 Point table ................................................................................................................................15-33
15.12.13 Servo amplifier group designation.........................................................................................15-39
15.12.14 Software version ......................................................................................................................15-40
APPENDIX
App- 1 to App- 4
App 1. Status indication block diagram ................................................................................................. App- 1
App 2. Junction terminal block (MR-TB20) terminal block labels...................................................... App- 2
App 3. Combination of servo amplifier and servo motor ...................................................................... App- 3
App 4. Change of connector sets to the RoHS compatible products.................................................... App- 4
6
Optional Servo Motor Instruction Manual CONTENTS
The rough table of contents of the optional MELSERVO Servo Motor Instruction Manual is introduced
here for your reference. Note that the contents of the Servo Motor Instruction Manual are not included in
the Servo Amplifier Instruction Manual.
1. INTRODUCTION
2. INSTALLATION
3. CONNECTORS USED FOR SERVO MOTOR WIRING
4. INSPECTION
5. SPECIFICATIONS
6. CHARACTERISTICS
7. OUTLINE DIMENSION DRAWINGS
8. CALCULATION METHODS FOR DESIGNING
7
MEMO
8
1. FUNCTIONS AND CONFIGURATION
1. FUNCTIONS AND CONFIGURATION
1.1 Introduction
The MR-J2S-CP AC servo amplifier with built-in positioning functions is the MR-J2S-A general-purpose
AC servo amplifier which incorporate single-axis positioning functions. These functions perform
positioning operation by merely setting the position data (target positions), servo motor speeds,
acceleration and deceleration time constants, etc. to point tables as if setting them in parameters. The
servo amplifier is the most appropriate to configure a program-free, simple positioning system or to
simplify a system, for example.
There are 3 points of point tables as standard, and they can be increased up to 31 points by using the MR
Configurator (servo configuration software).
You can choose a configuration suitable for your purpose, e.g. simple positioning system using external
I/O signals (DI/O), operation using DI/O and RS-422 serial communication, or multi drop operation using
RS-422 serial communication.
All servo motors are equipped with an absolute position encoder as standard. An absolute position
detection system can be configured by merely adding a battery to the servo amplifier. Once the home
position has been set, home position return is not required at power on, alarm occurrence, etc.
The MR-J2S-CP AC servo amplifier with positioning function is made easier to use and higher in function
by using it with the MR Configurator (servo configuration software).
1.1.1 Function block diagram
The function block diagram of this servo is shown below.
1 - 1
1. FUNCTIONS AND CONFIGURATION
(1) MR-J2S-350CP or less
Regenerative option
Servo amplifier
Diode
Servo motor
P
C
D
(Note 1)
NFB
Relay
stack
MC
L1
L2
L3
U
U
(Note 2)
Power
supply
Current
detector
V
V
Regenerative
transistor
M
W
W
CHARGE
lamp
Dynamic
brake
(Note 3) Cooling fan
L11
B1
B2
Control
power
supply
Electro-
magnetic
brake
L21
Base
amplifier
Voltage
detection
Current
detection
Overcurrent
protection
Encoder
Current
control
Point table
Acceleration Deceleration
Position
data
No.
Dwell Auxiliary
Speed time
time
constant
80
constant
1
2
3
4
5
6
7
8
1000 1000
80
100
60
0
0
0
0
1
1
0
Speed
control
2000 2000
4000 2000
500 2000
100
70
500
1000
0
60
80
70
1000 2000
2000 1000
1000 1000
80
80
80
0
Position
control
80
80
100
100
80
0
0
0
00
100
1000
0
0
1000
000
31 2000 2000
80
0
0
Position
command
creation
MR-BAT
Optional battery
(for absolute position
detection system)
RS-232C
RS-422
A/D
D/A
I/F
CN1A CN1B
CN3
Analog monitor
(2 channels)
Controller
D I/O control
Servo on
Start
RS-422/RS-232C
Analog
(2 channels)
Failure, etc.
To other servo
amplifier
Note 1. The built-in regenerative resistor is not provided for the MR-J2S-10CP (1).
2. For 1-phase 230VAC, connect the power supply to L1, L2 and leave L3 open. Refer to section 1.2 for the power supply
specification. L3 is not provided for a 1-phase 100 to120VAC power supply.
3. Servo amplifiers MR-J2S-200CP have a cooling fan.
1 - 2
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-500CP 700CP
Regenerative option
Servo amplifier
Diode
Servo motor
P
C N
NFB
Relay
stack
MC
L1
L2
L3
U
U
(Note)
Power
supply
Current
detector
V
V
Regenerative
transistor
M
W
W
CHARGE
lamp
Dynamic
brake
Cooling fan
L11
B1
B2
Control
power
supply
Electro-
magnetic
brake
L21
Base
amplifier
Voltage
detection
Current
detection
Overcurrent
protection
Encoder
Current
control
Point table
Acceleration Deceleration
Position
data
Dwell
Auxiliary
No.
Speed time
time
constant
80
constant
1
2
3
4
5
6
7
8
1000 1000
80
100
60
0
0
0
0
1
1
0
Speed
control
2000 2000
4000 2000
500 2000
100
70
500
1000
0
60
80
70
1000 2000
2000 1000
1000 1000
80
80
80
0
Position
control
80
80
100
100
80
0
0
0
00
100
1000
0
0
1000
000
31 2000 2000
80
0
0
Position
command
creation
MR-BAT
Optional battery
(for absolute position
detection system)
RS-232C
RS-422
A/D
D/A
I/F
CN1A CN1B
CN3
Analog monitor
(2 channels)
Controller
D I/O control
Servo on
Start
RS-422/RS-232C
Analog
(2 channels)
Failure, etc.
To other servo
amplifier
Note. Refer to section 1.2 for the power supply specification.
1 - 3
1. FUNCTIONS AND CONFIGURATION
1.1.2 System configuration
This section describes operations using this servo.
You can arrange any configurations from a single-axis to max. 32-axis systems. Further, the connector
pins in the interface section allow you to assign the optimum signals to respective systems. (Refer to
sections 1.1.3 and 3.3.2.) The MR Configurator (servo configuration software) (refer to chapter 6) and
personal computer are required to change or assign devices.
Set the following values to the point table.
Name
Setting range
Unit
0.001[mm]
0.01[mm]
0.1[mm]
1[mm]
[r/min]
[ms]
Position data
999999 to 999999
Servo motor speed
Acceleration time constant
Deceleration time constant
Dwell
0 to max. speed
0 to 20000
0 to 20000
[ms]
0 to 20000
[ms]
0 to 3
Auxiliary function
(Refer to section 4.2)
(1) Operation using external input signals
(a) Description
The following configuration example assumes that external input signals are used to control all
signals (devices).
The I/O signals are as factory-set.
(b) Configuration
The following configuration uses external I/O signals. The personal computer is used with MR
Configurator (servo configuration software) to set, change and monitor the parameters and point
tables.
Personal
computer
MR Configurator
(Servo configuration
Software)
External I/O
signals
Servo amplifier
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1 - 4
1. FUNCTIONS AND CONFIGURATION
(2) Operation using external input signals and communication
(a) Description
Communication can be used to change the point table data, choose the point table, change
parameter values, and confirm monitor data, for example. Enter a forward rotation start (ST1) or
reverse rotation start (ST2) through the external I/O. Use this system when position data/speed
setting or the host personal computer or the like is used to change the parameter values, for
example.
(b) Configuration
1) One servo amplifier is connected with the personal computer by RS-232C.
Personal
computer
MR Configurator
(Servo configuration
Software)
External I/O
signals
Servo amplifier
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1 - 5
1. FUNCTIONS AND CONFIGURATION
2) Several (up to 32) servo amplifiers are connected with the personal computer by RS-422.
Use parameter No. 16 to change the communication system.
Personal
computer
MR Configurator
(Servo configuration
Software)
External I/O
signals
Servo amplifier (axis 1)
CN1A CN1B
RS–232C
RS–422
CN2 CN3
RS–232C/RS-422 converter
(to be prepared by the customer)
Power supply
Servo motor
RS–422
External I/O
signals
Servo amplifier (axis 2)
CN1A CN1B
CN2 CN3
Power supply
To the next axis
Servo motor
1 - 6
1. FUNCTIONS AND CONFIGURATION
(3) Operation using communication
(a) Description
Analog input, forced stop (EMG) and other signals are controlled by external I/O signals and the
other devices controlled through communication. Also, you can set each point table, choose the
point table, and change or set parameter values, for example. Up to 32 axes may be controlled.
(b) Configuration
1) One servo amplifier is connected with the personal computer by RS-232C.
MR Configurator
(Servo configuration
Software)
Personal
computer
External I/O
signals
Servo amplifier
CN1A CN1B
RS–232C
CN2 CN3
Power supply
Servo motor
1 - 7
1. FUNCTIONS AND CONFIGURATION
2) Several (up to 32) servo amplifiers are connected with the personal computer by RS-422.
Use parameter No. 16 to change the communication system.
MR Configurator
(Servo configuration
Software)
Personal
computer
External I/O
signals
Servo amplifier (axis 1)
CN1A CN1B
RS–232C
RS–422
CN2 CN3
RS–232C/RS-422 converter
(to be prepared by the customer)
Power supply
Servo motor
RS–422
External I/O
signals
Servo amplifier (axis 2)
CN1A CN1B
CN2 CN3
Power supply
To the next axis
Servo motor
1 - 8
1. FUNCTIONS AND CONFIGURATION
1.1.3 I/O devices
This servo amplifier allows devices to be allocated to the pins of connector CN1A/CN1B as desired. The
following devices can be allocated. For device details, refer to section 3.3.2.
Factory-
Factory-
Input device
Proximity dog
Symbol
Output device
Symbol
allocated pin
allocated pin
DOG
SON
LSP
LSN
ST1
ST2
MD0
DI0
CN1A-8
CN1B-15
CN1B-16
CN1B-17
CN1B-8
CN1B-9
CN1B-7
CN1B-5
CN1B-14
Home position return completion
Rough match
ZP
CPO
MEND
ALM
RD
CN1A-18
CN1B-4
CN1B-6
CN1B-18
CN1B-19
Servo-on
Forward rotation stroke end
Reverse rotation stroke end
Forward rotation start
Reverse rotation start
Automatic/manual selection
Point table No. selection 1
Point table No. selection 2
Point table No. selection 3
Point table No. selection 4
Point table No. selection 5
Forced stop
Movement finish
Trouble
Ready
Electromagnetic brake interlock
Position range output
Warning output
MBR
POT
WNG
BWNG
TLC
PUS
INP
DI1
Battery warning output
Limiting torque
DI2
DI3
Temporary stop
DI4
In position
EMG
RES
OVR
TL
Point No. output 1
Point No. output 2
Point No. output 3
Point No. output 4
Point No. output 5
PT0
Reset
PT1
Override selection
PT2
External torque limit selection
Internal torque limit selection
PT3
TL2
PC
PT4
Proportion control
Temporary stop/restart
Manual pulse generator
multiplication 1
Manual pulse generator
multiplication 2
Gain switch
STP
TP0
TP1
CDP
TCH
Teach
1 - 9
1. FUNCTIONS AND CONFIGURATION
1.2 Servo amplifier standard specifications
Servo amplifier
MR-J2S-
10CP 20CP 40CP 60CP 70CP 100CP 200CP 350CP 500CP 700CP 10CP1 20CP1 40CP1
Item
3-phase 200 to 230VAC, 50/60Hz
or 1-phase 230VAC, 50/60Hz
3-phase 200 to 230VAC:
170 to 253VAC
1-phase 230VAC: 207 to 253VAC
1-phase 100 to
120VAC 50/60Hz
Voltage/frequency
3-phase 200 to 230VAC, 50/60Hz
3-phase 170 to 253VAC
1-phase
85 to 127VAC
Permissible voltage fluctuation
Permissible frequency fluctuation
Power supply capacity
Inrush current
Within 5%
Refer to section13.2
Refer to section13.5
Control system
Dynamic brake
Sine-wave PWM control, current control system
Built-in
Overcurrent shut-off, regenerative overvoltage shut-off, overload shut-off (electronic
thermal relay), servo motor overheat protection, encoder error protection, regenerative
brake error protection, undervoltage, instantaneous power failure protection, overspeed
protection, excessive error protection
Protective functions
Operational
Positioning by specifying the point table No. (31 points)
specifications
Position command
input
Set in point table. 1-point feed length setting range: 1[ m] to 999.999[mm]
Point table
number
input
Speed command
input
Set in point table. Acceleration/deceleration time is set in point table.
S-pattern acceleration/deceleration time constant is set in parameter No.14.
Signed absolute value command system, incremental value command system, signed
absolute value command/incremental value command specifying system
Positioning using RS-422 (232C) communication data
System
Operational
specifications
Position command
input
Setting through RS-422 (232C) communication
1-point feed length setting range: 1[ m] to 999.999[mm]
Setting through RS-422 (232C) communication
Position
data input
Speed command
input
Acceleration/deceleration time is also set through RS-422 (232C) communication.
S-pattern acceleration/deceleration time constant is set in parameter No.14.
Signed absolute value command system, incremental value command system, signed
absolute value command/incremental value command specifying system
Point table number input, position data input system
System
Automatic Point table
operation
Positioning operation is performed once in accordance with the position and speed
commands.
mode
Automatic continuous Varied speed operation (2 to 31 speeds), automatic continuous positioning operation (2 to
operation
31 points)
Jog operation is performed in accordance with the parameter-set speed command by
contact input or through RS-422 (232C) communication.
Manual feed is made by manual pulse generator.
Command pulse multiplication: 1, 10 or 100 is selected using parameter.
Home position return is made starting with Z-phase pulse after passage of proximity dog.
Home position address may be set. Home position shift distance may be set. Home position
return direction may be selected.
Manual
operation
mode
Jog
Manual pulse
generator
Dog type
Automatic at-dog home position return return/automatic stroke return function
Home position return is made by counting encoder pulses after contact with proximity dog.
Home position address may be set. Home position shift value may be set. Home position
return direction may be set.
Automatic at-dog home position return return/automatic stroke return function
Home position return is made without dog.
Manual
home
position
return
mode
Count type
Data setting type
Stopper type
Home position may be set at any position by manual operation, etc. Home position address
may be set.
Home position return is made by pressing machine part against stroke end.
Home position address may be set. Home position return direction may be set.
1 - 10
1. FUNCTIONS AND CONFIGURATION
Servo amplifier
MR-J2S-
10CP 20CP 40CP 60CP 70CP 100CP 200CP 350CP 500CP 700CP 10CP1 20CP1 40CP1
Item
Position where servo-on (SON) is switched on is defined as home position.
Home position address may be set.
Home position
ignorance
(Servo-on position as
home position)
Home position return is made with respect to the rear end of a proximity dog.
Home position address may be set. Home position shift value may be set. Home position
return direction may be set.
Automatic at-dog home position return return/automatic stroke return function
Home position return is made with respect to the front end of a proximity dog.
Home position address may be set. Home position shift value may be set. Home position
return direction may be set.
Dog type rear end
reference
Manual
home
position
return
mode
Count type front end
reference
Automatic at-dog home position return return/automatic stroke return function
Home position return is made with respect to the front end of a proximity dog by the first
Z-phase pulse.
Home position address may be set. Home position shift value may be set. Home position
return direction may be set.
Dog cradle type
Automatic at-dog home position return return/automatic stroke return function
High-speed automatic return to a defined home position.
Automatic positioning to home
position
Absolute position detection, backlash function
Overtravel prevention using external limit switch
Software stroke limit, override using external analog signal
Amplifier front button-operated teaching function/external teaching pendant input
signal interface
Other functions
Structure
Self-cooled,
Self-cooled, open (IP00)
Force-cooling, open (IP00)
open (IP00)
[
[
[
[
] 0 to 55 (non-freezing)
] 32 to 131 (non-freezing)
In Operation
In storage
Ambient
temperature
]
]
20 to 65 (non-freezing)
4 to 149 (non-freezing)
Ambient
humidity
In Operation
In storage
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Ambient
Altitude
Vibration
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280ft) above sea level
5.9 [m/s2] or less
19.4 [ft/s2] or less
[kg] 0.7
[lb] 1.5
0.7
1.5
1.1
2.4
1.1
2.4
1.7
1.7
2.0
4.4
2.0
4.4
4.9
7.2
0.7
0.7
1.5
1.1
2.4
Mass
3.75 3.75
10.8 15.87 1.5
1 - 11
1. FUNCTIONS AND CONFIGURATION
1.3 Function list
The following table lists the functions of this servo. For details of the functions, refer to the reference field.
Function
Description
Reference
Select the required ones from among 31 preset point tables and
perform operation in accordance with the set values.
Use the external input signal or communication function to choose
the point tables.
Positioning by automatic operation
Section 4.2
Servo motor speed can be varied continuously until the preset
moving distance is reached. (Max. set speeds: 31 speeds)
By merely choosing one point table and starting operation,
positioning can be executed continuously in accordance with
several point tables.
Varied speed operation
Section 4.2.6 (2)
Section 4.2.6 (1)
Automatic continuous positioning
operation
Dog type, count type, data setting type, stopper type, home
position ignorance, dog type rear end reference, count type front
end reference, dog cradle type
Manual home position return
Section 4.4
Up to 32 axes of MR-J2S-CP are controllable simultaneously by
RS-422 communication.
Section 4.6.3
Chapter 15
Multidrop communication
High-resolution encoder
High-resolution encoder of 131072 pulses/rev is used as a servo
motor encoder.
By merely setting the home position once, home position return
need not be done at each power on.
Absolute position detection system
Gain changing function
Section 4.5
Section 9.5
Section 9.3
Section 9.4
You can switch between gains during rotation and gains during
stop or use an external signal to change gains during operation.
Servo amplifier detects mechanical resonance and sets filter
characteristics automatically to suppress mechanical vibration.
Suppresses high-frequency resonance which occurs as servo
system response is increased.
Adaptive vibration suppression control
Low-pass filter
Analyzes the frequency characteristic of the mechanical system by
simply connecting a MR Configurator (servo configuration
software)-installed personal computer and servo amplifier.
Can simulate machine motions on a personal computer screen on
the basis of the machine analyzer results.
Machine analyzer function
Machine simulation
Personal computer changes gains automatically and searches for
overshoot-free gains in a short time.
Gain search function
Slight vibration suppression control
Vibration of 1 pulse at servo motor stop is suppressed.
The electronic gear is used to make adjustment so that the servo
amplifier setting matches the machine moving distance. Also,
changing the electronic gear value allows the machine to be moved
at any multiplication ratio to the moving distance using the servo
amplifier.
Parameter No. 20
Section 5.2.1
Electronic gear
Automatically adjusts the gain to optimum value if load applied to
the servo motor shaft varies. Higher in performance than MR-J2
series servo amplifier.
Auto tuning
Chapter 8
Section 5.2.3
Section 14.1.1
S-pattern acceleration/deceleration time
constant
Acceleration/deceleration can be made smoothly.
Used when the built-in regenerative resistor of the servo amplifier
does not have sufficient regenerative capability for the
regenerative power generated.
Regenerative option
Brake unit
Used when the regenerative option cannot provide enough
regenerative power.
Can be used with the MR-J2S-500CP MR-J2S-700CP.
Used when the regenerative option cannot provide enough
regenerative power.
Section 14.1.2
Section 14.1.3
Return converter
Can be used with the MR-J2S-500CP MR-J2S-700CP.
1 - 12
1. FUNCTIONS AND CONFIGURATION
Function
Description
Reference
Analog monitor
Alarm history
The servo status is output in terms of voltage in real time.
By using the MR Configurator (servo configuration software), the
current alarm and five past alarm numbers are stored and
displayed.
Section 5.2.4
Section 6.8
Section 6.6
Section 3.4.4
By using the MR Configurator (servo configuration software), any
devices can be assigned to 9 input, 5 output and 1 I/O pins.
Servo motor-torque is limited.
I/O signal selection (Device setting)
Torque limit
Parameter
2 limit value
1 limit value
Analog input
The servo motor speed is limited by analog input.
The ratio of override to the set speed can be changed between 0 to
200%.
Override (speed limit)
Section 3.4.3
Status display
The servo status is displayed.
Section 7.2
Section 6.7
Jog operation, positioning operation, motor-less operation, DO
forced output, 1-step feed
Test operation mode
The servo motor travel region can be limited using the forward
rotation stroke end (LSP)/reverse rotation stroke end (LSN).
The travel region is limited using parameters in terms of address.
The function similar to that of a limit switch is limited by
parameter.
Limit switch
Section 5.2.5
Section 5.2.8
Software limit
1.4 Model code definition
(1) Rating plate
AC SERVO
MITSUBISHI
Model
MODEL
MR-J2S-60CP
Capacity
POWER : 600W
INPUT : 3.2A 3PH 1PH200-230V 50Hz
3PH 1PH200-230V 60Hz
5.5A 1PH 230V 50/60Hz
Applicable power supply
OUTPUT : 170V 0-360Hz 3.6A
Rated output current
Serial number
SERIAL : A5
TC3
AAAAG52
PASSED
MITSUBISHI ELECTRIC CORPORATION
MADE IN JAPAN
1 - 13
1. FUNCTIONS AND CONFIGURATION
(2) Model
MR–J2S– CP
MR–J2S–100CP or less
MR–J2S–200CP 350CP
Series
Power Supply
Symbol
Power supply
3-phase 200 to 230VAC
(Note 1) 1-phase 230VAC
None
(Note 2)
Rating plate
1-phase 100V to 120VAC
1
Rating plate
Note 1. 1-phase 230V is supported
by 750W or less.
2. 1-phase 100V to 120V is
supported by 400W or less.
MR-J2S-500CP
MR-J2S-700CP
Built-in positioning functions
Rated output
Rated
output [W]
Rated
output [W]
Symbol
Symbol
10
20
40
60
70
100
200
400
600
750
100
200
350
500
700
1000
2000
3500
5000
7000
Rating plate
Rating plate
1.5 Combination with servo motor
The following table lists combinations of servo amplifiers and servo motors. The same combinations apply
to the models with electromagnetic brakes and the models with reduction gears.
Servo motors
Servo amplifier
HC-SFS
HC-UFS
HC-KFS
HC-MFS
HC-RFS
1000r/min 2000r/min 3000r/min
2000r/min
3000r/min
MR-J2S-10CP(1)
MR-J2S-20CP (1)
MR-J2S-40CP (1)
MR-J2S-60CP
053 13
23
053 13
23
13
23
43
43
43
52
53
MR-J2S-70CP
73
73
72
73
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-700CP
81
102
103
121 201 152 202 153 203
103 153
203
152
202
301
352
502
702
353
353 503
352 502
Servo motors
Servo amplifier
HA-LFS
(Note 1)
HC-LFS
1000r/min
1500r/min
2000r/min
MR-J2S-60CP
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-700CP
52
102
152
202
302
502
702
(Note 2)601 (Note 2)701M
Note 1. These servo motors may not be connected depending on the production time of the servo amplifier. Please refer to Appendix 3.
2. Consult us since the servo amplifier to be used with any of these servo motors is optional.
1 - 14
1. FUNCTIONS AND CONFIGURATION
1.6 Structure
1.6.1 Part names
(1) MR-J2S-100CP or less
Name/Application
Reference
Battery holder
Contains the battery for absolute position data backup.
Section4.5
Battery connector (CON1)
Used to connect the battery for absolute position data
backup.
Section4.5
Chapter7
Display
The 5-digit, seven-segment LED shows the servo
status and alarm number.
Operation section
Used to perform status display, diagnostic, alarm,
parameter and point table setting operations.
MODE
SET
UP
DOWN
UP DOWN
MODE
SET
Used to set data.
Chapter7
Used to change the
display or data in each
mode.
Used to change the
mode.
I/O signal connector (CN1A)
Used to connect digital I/O signals.
Section3.3
Section3.3
I/O signal connector (CN1B)
Used to connect digital I/O signals.
Communication connector (CN3)
Used to connect a command device (RS-422/RS-232C)
and output analog monitor data.
Chapter6
Chapter15
Section14.1.4
Name plate
Section1.4
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Section3.3
Section14.1.4
Encoder connector (CN2)
Used to connect the servo motor encoder.
Main circuit terminal block (TE1)
Used to connect the input power supply and servo
motor.
Section3.7.2
Section12.1
Section3.7.2
Section12.1
Section14.1.1
Control circuit terminal block (TE2)
Used to connect the control circuit power supply and
regenerative option.
Protective earth (PE) terminal (
Ground terminal.
)
Section3.10
Fixed part (2 places)
(For MR-J2S-70CP 100CP 3 places)
1 - 15
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-200CP MR-J2S-350CP
POINT
This servo amplifier is shown without the front cover. For removal of the
front cover, refer to section 1.6.2.
Reference
Name/Application
Battery holder
Contains the battery for absolute position data backup.
Section4.5
Battery connector (CON1)
Used to connect the battery for absolute position data
backup.
Section4.5
Chapter7
Display
The 5-digit, seven-segment LED shows the servo
status and alarm number.
Operation section
Used to perform status display, diagnostic, alarm,
parameter and point table setting operations.
MODE
UP
DOWN
SET
UP DOWN
MODE
SET
Used to set data.
Chapter7
Used to change the
display or data in each
mode.
Used to change the
mode.
I/O signal connector (CN1A)
Used to connect digital I/O signals.
Section3.3
Section3.3
I/O signal connector (CN1B)
Used to connect digital I/O signals.
Communication connector (CN3)
Used to connect a command device (RS-422/RS-232C)
and output analog monitor data.
Chapter6
Chapter15
Section14.1.4
Name plate
Section1.4
Charge lamp
Lit to indicate that the main circuit is charged. While
this lamp is lit, do not reconnect the cables.
Encoder connector (CN2)
Used to connect the servo motor encoder.
Section3.3
Section14.1.4
Main circuit terminal block (TE1)
Used to connect the input power supply and servo
motor.
Section3.7.2
Section12.1
Section3.7.2
Section12.1
Section14.1.1
Control circuit terminal block (TE2)
Used to connect the control circuit power supply and
regenerative option.
Cooling fan
Protective earth (PE) terminal (
Ground terminal.
)
Section3.10
Fixed part (4 places)
1 - 16
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500CP
POINT
The servo amplifier is shown without the front cover. For removal of the
front cover, refer to section 1.6.2.
Name/Application
Reference
Battery connector (CON1)
Used to connect the battery for absolute position data
backup.
Section4.5
Battery holder
Contains the battery for absolute position data backup.
Section4.5
Chapter7
Display
The 5-digit, seven-segment LED shows the servo
status and alarm number.
Operation section
Used to perform status display, diagnostic, alarm,
parameter and point table setting operations.
MODE
UP
DOWN
SET
MODE UP
DOWN SET
Used to set data.
Chapter7
Used to change the
display or data in each
mode.
Used to change the
mode.
Fixed part
(4 places)
I/O signal connector (CN1A)
Section3.3
Section3.3
Used to connect digital I/O signals.
I/O signal connector (CN1B)
Used to connect digital I/O signals.
Communication connector (CN3)
Used to connect a command device (RS-422/RS-232C)
and output analog monitor data.
Chapter6
Chapter15
Section14.1.4
Encoder connector (CN2)
Section3.3
Used to connect the servo motor encoder.
Section14.1.4
Charge lamp
Lit to indicate that the main circuit is charged.
While this lamp is lit, do not reconnect the cables.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply and
regenerative option.
Section3.7.2
Section12.1
Main circuit terminal block (TE1)
Used to connect the input power supply and servo
motor.
Section3.7.2
Section12.1
Section14.1.1
Name plate
Section1.4
Cooling fan
Protective earth (PE) terminal (
Ground terminal.
)
Section3.10
1 - 17
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700CP
POINT
The servo amplifier is shown without the front cover. For removal of the
front cover, refer to next page.
Reference
Name/Application
Battery connector (CON1)
Used to connect the battery for absolute position data
backup.
Section4.5
Battery holder
Contains the battery for absolute position data backup.
Section4.5
Chapter7
Display
The 5-digit, seven-segment LED shows the servo
status and alarm number.
Operation section
Used to perform status display, diagnostic, alarm,
parameter and point table setting operations.
MODE
UP
DOWN
SET
MODE
UP
DOWN SET
Used to set data.
Chapter7
Used to change the
display or data in each
mode.
Used to change the
mode.
I/O signal connector (CN1A)
Used to connect digital I/O signals.
Section3.3
Section3.3
I/O signal connector (CN1B)
Used to connect digital I/O signals.
Communication connector (CN3)
Used to connect a command device (RS-422/RS-232C)
and output analog monitor data.
Chapter6
Chapter15
Section14.1.4
Charge lamp
Lit to indicate that the main circuit is charged.
While this lamp is lit, do not reconnect the cables.
Control circuit terminal block (TE2)
Used to connect the control circuit power supply.
Section3.7.2
Section12.1
Encoder connector (CN2)
Section3.3
Used to connect the servo motor encoder.
Section14.1.4
Section1.4
Name plate
Main circuit terminal block (TE1)
Used to connect the input power supply, regenerative
option and servo motor.
Section3.7.2
Section12.1
Section14.1.1
Cooling fan
Protective earth (PE) terminal (
Ground terminal.
)
Section3.10
Fixed part
(4 places)
1 - 18
1. FUNCTIONS AND CONFIGURATION
1.6.2 Removal and reinstallation of the front cover
Before removing or installing the front cover, turn off the power and wait for 15
minutes or more until the charge lamp turns off. Then, confirm that the voltage
between P and N is safe with a voltage tester and others. Otherwise, an electric
shock may occur. In addition, always confirm from the front of the servo amplifier
whether the charge lamp is off or not.
WARNING
(1) For MR-J2S-200CP or more
Removal of the front cover
1)
Reinstallation of the front cover
Front cover hook
(2 places)
2)
2)
Front cover
1)
Front cover socket
(2 places)
1) Hold down the removing knob.
2) Pull the front cover toward you.
1) Insert the front cover hooks into the front cover sockets of
the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
(2) For MR-J2S-500CP
Removal of the front cover
1)
Reinstallation of the front cover
Front cover hook
(2 places)
2)
2)
1)
Front cover
Front cover socket
(2 places)
1) Hold down the removing knob.
2) Pull the front cover toward you.
1) Insert the front cover hooks into the front cover sockets of
the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
1 - 19
1. FUNCTIONS AND CONFIGURATION
(3) For MR-J2S-700CP
Removal of the front cover
Reinstallation of the front cover
Front cover
hook
(2 places)
A)
B)
2)
2)
1)
A)
1)
Front cover socket
(2 places)
1) Push the removing knob A) or B), and put you
finger into the front hole of the front cover.
2) Pull the front cover toward you.
1) Insert the two front cover hooks at the bottom into the
sockets of the servo amplifier.
2) Press the front cover against the servo amplifier until the
removing knob clicks.
1 - 20
1. FUNCTIONS AND CONFIGURATION
1.7 Servo system with auxiliary equipment
To prevent an electric shock, always connect the protective earth (PE) terminal
(terminal marked ) of the servo amplifier to the protective earth (PE) of the control
box.
WARNING
(1) MR-J2S-100CP or less
(a) For 3-phase 200V to 230VAC or 1-phase 230VAC
(Note 2)
Power supply
Options and auxiliary equipment
Circuit breaker
Options and auxiliary equipment
Reference
Reference
Section 14.2.2 Cables
Section 14.2.1
Section 14.1.8
Magnetic contactor
Section 14.2.2 Manual pulse generator
MR Configurator
(Servo configuration software)
External digital display
Chapter 6
Section 14.1.7
Power factor improving reactor Section 14.2.3
Regenerative option
Section 14.1.1
Circuit breaker
(NFB) or fuse
Command device
Servo amplifier
Junction terminal block
To CN1A
Manual pulse generator
External digital display
Magnetic
contactor
(MC)
To CN1B
To CN3
Power
factor
improving
reactor
(FR-BAL)
MR Configurator
CHARGE
(Servo configuration
software
Personal
computer
MRZJW3-SETUP151E)
To CN2
L1
L2
L3
U
V
W
Protective earth (PE) terminal
(Note 1)
Encoder cable
(Note 1)
Power supply lead
D
Control circuit terminal block
L21
L11
P
Regenerative option
Servo motor
C
Note 1. The HC-SFS, HC-RFS, HC-UFS 2000r/min series have cannon connectors.
2. A 1-phase 230VAC power supply may be used with the servo amplifier of MR-J2S-70CP or less.
For 1-phase 230VAC, connect the power supply to L1 L2 and leave L3 open. Refer to section 1.2 for the power supply
specification.
1 - 21
1. FUNCTIONS AND CONFIGURATION
(b) For 1-phase 100V to 120VAC
(Note 2)
Power supply
Options and auxiliary equipment
Circuit breaker
Options and auxiliary equipment
Reference
Reference
Section 14.2.2 Cables
Section 14.2.1
Section 14.1.8
Section 14.1.7
Magnetic contactor
Section 14.2.2 Manual pulse generator
MR Configurator
(Servo configuration software)
External digital display
Chapter 6
Power factor improving reactor
Section 14.1.1
Section 14.2.3
Circuit breaker
(NFB) or fuse
Regenerative option
Servo amplifier
Command device
Junction terminal block
To CN1A
Magnetic
contactor
(MC)
Manual pulse generator
To CN1B
To CN3
External digital display
MR Configurator
(Servo configuration
software
CHARGE
Personal
computer
Power
factor
MRZJW3-SETUP151E)
To CN2
improving
reactor
(FR-BAL)
L1
L2
U
V
W
Protective earth (PE) terminal
(Note 1)
Encoder cable
(Note 1)
Power supply lead
D
Control circuit terminal block
L21
L11
P
Regenerative option
Servo motor
C
Note 1. The HC-SFS, HC-RFS, HC-UFS 2000 r/min series have cannon connectors.
2. Refer to section 1.2 for the power supply specification.
1 - 22
1. FUNCTIONS AND CONFIGURATION
(2) MR-J2S-200CP MR-J2S-350CP
(Note)
Options and auxiliary equipment
Power supply
Reference
Options and auxiliary equipment
Cables
Reference
Circuit breaker
Section 14.2.2
Section 14.2.2
Section 14.2.1
Section 14.1.8
Magnetic contactor
Manual pulse generator
External digital display
MR Configurator
(Servo configuration software)
Section 14.1.7
Section 14.2.3
Chapter 6
Circuit
Power factor improving reactor
breaker
(NFB) or
fuse
Regenerative option
Section 14.1.1
Servo amplifier
Command device
Junction terminal
block
To CN1A
Magnetic
contactor
(MC)
Manual pulse
generator
To CN1B
To CN3
External digital display
Power
factor
improving
reactor
(FR-BAL)
MR Configurator
(Servo
To CN2
configuration
software
MRZJW3-
SETUP151E)
Personal
computer
L11
L21
L1
L2
L3
U
V
W
P
C
Regenerative option
Note. Refer to section 1.2 for the power supply specification.
1 - 23
1. FUNCTIONS AND CONFIGURATION
(3) MR-J2S-500CP
(Note 2)
Power supply
Options and auxiliary equipment
Reference
Options and auxiliary equipment
Cables
Reference
Circuit breaker
Section 14.2.2
Section 14.2.2
Section 14.2.1
Section 14.1.8
Circuit
breaker
(NFB) or
Magnetic contactor
Manual pulse generator
External digital display
MR Configurator
fuse
Section 14.1.7
Chapter 6
(Servo configuration software)
Power factor improving reactor Section 14.2.3
Regenerative option
Section 14.1.1
Magnetic
contactor
(MC)
Command device
Power
factor
improving
reactor
Servo amplifier
Junction terminal
block
(FR-BAL)
To CN1A
Manual pulse
generator
L1
L2
L3
To CN1B
To CN3
To CN2
External digital display
(Note 1)
Regenerative option
C
P
U
V
W
MR Configurator
(Servo
configuration
software
MRZJW3-
Personal
computer
L11
L21
SETUP151E)
Note 1. When using the regenerative option, remove the lead wires of the built-in regenerative resistor.
2. Refer to section 1.2 for the power supply specification.
1 - 24
1. FUNCTIONS AND CONFIGURATION
(4) MR-J2S-700CP
Options and auxiliary equipment
Reference
Options and auxiliary equipment
Reference
Circuit breaker
Section 14.2.2 Cables
Section 14.2.1
Section 14.1.8
Magnetic contactor
Section 14.2.2 Manual pulse generator
(Note 2)
Power supply
MR Configurator
(Servo configuration software)
External digital display
Chapter 6
Section 14.1.7
Power factor improving reactor Section 14.2.3
Regenerative option
Section 14.1.1
Command device
Circuit
breaker
(NFB) or
fuse
Junction terminal
block
Servo amplifier
L11
To CN1A
L21
Manual pulse
generator
Magnetic
contactor
(MC)
To CN1B
To CN3
To CN2
External digital display
Power
factor
improving
reactor
(FR-BAL)
MR Configurator
(Servo
configuration
software
Personal
computer
MRZJW3-
SETUP151E)
L3
L2
L1
U
V
W
C
P
(Note 1)
Regenerative option
Note 1. When using the regenerative option, remove the lead wires of the built-in regenerative resistor.
2. Refer to section 1.2 for the power supply specification.
1 - 25
1. FUNCTIONS AND CONFIGURATION
MEMO
1 - 26
2. INSTALLATION
2. INSTALLATION
Stacking in excess of the limited number of products is not allowed.
Install the equipment on incombustible material. Installing them directly or close to
combustibles will lead to a fire.
Install the equipment in a load-bearing place in accordance with this Instruction
Manual.
Do not get on or put heavy load on the equipment to prevent injury.
Use the equipment within the specified environmental condition range. (For the
environmental conditions, refer to section 2.1.)
Provide an adequate protection to prevent screws, metallic detritus and other
conductive matter or oil and other combustible matter from entering the servo
amplifier.
CAUTION
Do not block the intake/exhaust ports of the servo amplifier. Otherwise, a fault may
occur.
Do not subject the servo amplifier to drop impact or shock loads as they are
precision equipment.
Do not install or operate a faulty servo amplifier.
When the product has been stored for an extended period of time, consult
Mitsubishi.
When treating the servo amplifier, be careful about the edged parts such as the
corners of the servo amplifier.
2.1 Environmental conditions
Environment
Conditions
In
[
[
[
[
]
]
]
]
0 to 55 (non-freezing)
32 to 131 (non-freezing)
20 to 65 (non-freezing)
4 to 149 (non-freezing)
operation
Ambient
temperature
In storage
In operation
In storage
Ambient
humidity
90%RH or less (non-condensing)
Indoors (no direct sunlight)
Ambience
Altitude
Free from corrosive gas, flammable gas, oil mist, dust and dirt
Max. 1000m (3280 ft) above sea level
[m/s2] 5.9 [m/s2] or less
[ft/s2] 19.4 [ft/s2] or less
Vibration
2 - 1
2. INSTALLATION
2.2 Installation direction and clearances
Do not hold the front cover to transport the servo amplifier. The servo amplifier
may drop.
The equipment must be installed in the specified direction. Otherwise, a fault may
CAUTION
occur.
Leave specified clearances between the servo amplifier and control box inside
walls or other equipment.
(1) Installation of one servo amplifier
Control box
Control box
40mm
(1.6 in.)
or more
Servo amplifier
Wiring clearance
70mm
Up
(2.8 in.)
10mm
10mm
(0.4 in.)
or more
(0.4 in.)
or more
Down
40mm
(1.6 in.)
or more
2 - 2
2. INSTALLATION
(2) Installation of two or more servo amplifiers
Leave a large clearance between the top of the servo amplifier and the internal surface of the control
box, and install a cooling fan to prevent the internal temperature of the control box from exceeding the
environmental conditions.
Control box
10mm
(0.4 in.)
or more
100mm
(4.0 in.)
or more
30mm
30mm
(1.2 in.)
or more
(1.2 in.)
or more
40mm
(1.6 in.)
or more
(3) Others
When using heat generating equipment such as the regenerative option, install them with full
consideration of heat generation so that the servo amplifier is not affected.
Install the servo amplifier on a perpendicular wall in the correct vertical direction.
2.3 Keep out foreign materials
(1) When installing the unit in a control box, prevent drill chips and wire fragments from entering the
servo amplifier.
(2) Prevent oil, water, metallic dust, etc. from entering the servo amplifier through openings in the control
box or a cooling fan installed on the ceiling.
(3) When installing the control box in a place where there are much toxic gas, dirt and dust, conduct an
air purge (force clean air into the control box from outside to make the internal pressure higher than
the external pressure) to prevent such materials from entering the control box.
2 - 3
2. INSTALLATION
2.4 Cable stress
(1) The way of clamping the cable must be fully examined so that flexing stress and cable's own weight
stress are not applied to the cable connection.
(2) For use in any application where the servo motor moves, fix the cables (encoder, power supply, brake)
supplied with the servo motor, and flex the optional encoder cable or the power supply and brake
wiring cables. Use the optional encoder cable within the flexing life range. Use the power supply and
brake wiring cables within the flexing life of the cables.
(3) Avoid any probability that the cable sheath might be cut by sharp chips, rubbed by a machine corner
or stamped by workers or vehicles.
(4) The flexing lives of the cables are shown below. In actuality, provide a little allowance for these values.
For installation on a machine where the servo motor will move, the flexing radius should be made as
large as possible. Refer to section 13.4 for the flexing life.
2 - 4
3. SIGNALS AND WIRING
3. SIGNALS AND WIRING
Any person who is involved in wiring should be fully competent to do the work.
Before wiring, turn off the power and wait for 15 minutes or more until the charge
lamp turns off. Then, confirm that the voltage between P and N is safe with a
voltage tester and others. Otherwise, an electric shock may occur. In addition,
always confirm from the front of the servo amplifier whether the charge lamp is off
or not.
WARNING
Ground the servo amplifier and the servo motor securely.
Do not attempt to wire the servo amplifier and servo motor until they have been
installed. Otherwise, you may get an electric shock.
The cables should not be damaged, stressed excessively, loaded heavily, or
pinched. Otherwise, you may get an electric shock.
Wire the equipment correctly and securely. Otherwise, the servo motor may
misoperate, resulting in injury.
Connect cables to correct terminals to prevent a burst, fault, etc.
Ensure that polarity ( , ) is correct. Otherwise, a burst, damage, etc. may occur.
The surge absorbing diode installed to the DC relay designed for control output
should be fitted in the specified direction. Otherwise, the signal is not output due to
a fault, disabling the forced stop (EMG) and other protective circuits.
Servo amplifier
Servo amplifier
COM
COM
(24VDC)
(24VDC)
Control output
signal
Control output
signal
RA
RA
CAUTION
Use a noise filter, etc. to minimize the influence of electromagnetic interference,
which may be given to electronic equipment used near the servo amplifier.
Do not install a power capacitor, surge suppressor or radio noise filter (FR-BIF
option) with the power line of the servo motor.
When using the regenerative resistor, switch power off with the alarm signal.
Otherwise, a transistor fault or the like may overheat the regenerative resistor,
causing a fire.
Do not modify the equipment.
During power-on, do not open or close the motor power line. Otherwise, a
malfunction or faulty may occur.
POINT
CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of
the connectors will lead to a failure. Connect them correctly.
3 - 1
3. SIGNALS AND WIRING
3.1 Standard connection example
Servo amplifier
(Note 3, 7) (Note 3, 7)
CN1A
9
CN1A
8
DOG
COM
Proximity dog
(Note 4)
RA5
Home position
return completion
SG 10
18 ZP
10m (32.79ft.) or less
(Note 3, 7) (Note 3, 7)
10m (32.81ft.) or less
(Note 12)
CN1B
15
CN1B
3
SON
LSP
VDD
Servo-on
16
Forward rotation stroke end
Reverse rotation stroke end
COM
CPO
MEND
13
4
(Note 5)
(Note 2, 4)
17
7
LSN
MD0
DI0
RA1
Rough match
Automatic/manual selection
Point table No. selection 1
Point table No. selection 2
Forward rotation start
Movement finish
6
RA2
RA3
RA4
5
14
8
DI1
ST1
ST2
SG
ALM
RD
18
19
Trouble (Note 6)
Ready
Reverse rotation start
9
10
Upper limit setting
(Note 8) Override
P15R 11
(Note 3, 7)
CN3
2
1
VC
LG
4
3
MO1
LG
A
A
(Note 10)
10k
10k
Monitor output
Max. 1mA
meter
Upper limit setting
(Note 9) Analog torque limit
14 MO2
LG
12
TLA
SD
Zero center
13
Plate
Plate SD
2m (6.56ft.) or less
(Note 11)
2m (6.56ft.) or less
Personal
computer
MR Configurator
(Servo Configuration
software)
(Note 10)
Communication cable
CN3
(Note 1)
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal of the servo amplifier to the protective earth
(PE) of the control box.
2. Connect the diode in the correct direction. If it is connected reversely, the servo amplifier will be faulty and will not output
signals, disabling the forced stop and other protective circuits.
3. CN1A, CN1B, CN2 and CN3 have the same shape. Wrong connection of the connectors will lead to a fault.
4. The sum of currents that flow in the external relays should be 80mA max. If it exceeds 80mA, supply interface power from
external.
5. When starting operation, always connect the forward/reverse rotation stroke end (LSN/LSP) with SG. (Normally closed
contacts)
6. Trouble (ALM) is connected with COM in normal alarm-free condition.
7. The pins with the same signal name are connected in the servo amplifier.
8. When using override (VC), make the override selection (OVR) device available.
9. When using analog torque limit (TLA), make the external torque limit selection (TL) devices available.
10. When connecting the personal computer together with monitor outputs 1, 2, use the maintenance junction card (MR-
J2CN3TM). (Refer to section 14.1.6).
11. Use MRZJW3-SETUP 151E.
12. When using the internal power supply (VDD), always connect VDD-COM. Do not connect them when supplying external
power. Refer to section 3.6.2.
3 - 2
3. SIGNALS AND WIRING
3.2 Internal connection diagram of servo amplifier
This section gives the internal connection diagram where the signal assignment is in the initial status.
Servo amplifier
CN1B
24VDC
3
VDD
13
COM
CN1A
18
CN1A
9
COM
DOG
SG
ZP
Approx. 4.7k
8
10, 20
CN1B
4
CPO
CN1B
5
DI0
MD0
ST1
ST2
DI1
6
MEND
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
Approx. 4.7k
7
8
9
18
19
ALM
RD
14
15
16
17
SON
LSP
LSN
Approx. 4.7k
Approx. 4.7k
CN1A
6
LA
16
SG 10, 20
CN1A
LAR
7
17
5
LB
LBR
OPC
PG
PP
11
13
LZ
Approx. 100
Approx. 100
Approx. 1.2k
3
15
14
1
LZR
OP
LG
NG
NP
12
Approx. 1.2k
2
Casing
SD
CN3
4
MO1
MO2
RXD
CN1B
2
VC
14
2
TLA
12
15VDC
P15R
LG
11
1
TXD
SDP
SDN
RDP
RDN
12
9
SD Casing
19
5
CN1A
P15R
15
PE
4
3 - 3
3. SIGNALS AND WIRING
3.3 I/O signals
3.3.1 Connectors and signal arrangements
POINT
The connector pin-outs shown above are viewed from the cable connector
wiring section side.
(1) Signal arrangement
CN1A
CN1B
1
LG
3
11
OPC
13
1
11
P15R
13
2
NP
4
12
2
12
LG
3
TLA
VC
14
OP
16
4
14
DI1
16
PP
5
VDD
5
COM
15
CPO
P15R
6
15
6
Servo amplifier
DI0
7
LZ
7
SON
17
LZR
17
MEND
LSP
LAR
18
LA
8
8
18
ALM
20
LB
9
MD0
9
LBR
19
LSN
19
ST1
ZP
20
DOG
10
10
COM
RD
ST2
SG
SG
SG
SG
CN2
CN3
1
LG
3
11
LG
13
1
LG
3
11
LG
13
2
12
LG
14
2
RXD
4
12
TXD
14
LG
4
LG
5
LG
15
MO1
6
MO2
16
5
15
6
MD
8
16
MDR
18
RDP
7
RDN
17
7
MR
9
17
The connector frames are
connected with the PE (earth)
terminal inside the servo amplifier.
8
18
MRR
19
P5
9
19
10
20
10
20
BAT
P5
SDP
SDN
P5
TRE
P5
3 - 4
3. SIGNALS AND WIRING
3.3.2 Signal (devices) explanations
(1) I/O devices
POINT
The devices not indicated in the Connector Pin No. field of the I/O devices
can be assigned to the connector CN1A/CN1B using the MR Configurator
(servo configuration software).
(a) Pins whose devices can be changed
Refer to section 3.6.2 for the I/O interfaces (symbols in the I/O Division field in the table) of the
corresponding connector pins.
Pin type
Connector pin No.
CN1B-5
I/O division
Device in initial status
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Proximity dog (DOG)
CN1B-14
CN1A-8
CN1B-15
CN1B-16
CN1B-17
CN1B-7
Servo-on (SON)
Input-only pins
DI-1
Forward rotation stroke end (LSP)
Reverse rotation stroke end (LSN)
Automatic/manual selection (MD0)
Forward rotation start (ST1)
Reverse rotation start (ST2)
No device has been assigned in the initial
status. You can assign an I/O device using
the MR Configurator (servo configuration
software).
CN1B-8
CN1B-9
I/O pin
CN1A-19
DI-1 or DO-1
CN1B-4
CN1B-6
Rough match (CPO)
Movement finish (MEND)
Trouble (ALM)
Output-only pins
DO-1
CN1B-18
CN1B-19
CN1A-18
Ready (RD)
Home position return completion(ZP)
(b) Input devices
Devices
Connector
pin No.
Device name
Functions/Applications
symbol
Forced stop
EMG
When EMG-SG are opened, the servo amplifier is placed in the forced stop status,
the servo switches off, and the dynamic brake is operated to bring the servo motor
to a sudden stop.
Short EMG-SG in the forced stop status to cancel the forced stop status.
Connect SON-SG to switch on the base circuit and make the servo amplifier ready
to operate (servo-on).
Servo-on
Reset
SON
RES
CN1B
15
Disconnect SON-SG to shut off the base circuit and coast the servo motor (servo-
off) .
Disconnect RES-SG for more than 50ms to reset the alarm.
Some alarms cannot be deactivated by the reset signal. Refer to section 11.2.1
If RES-SG are shorted in no alarm status, the base circuit is not shut off.
Set "
1
" in parameter No. 55 to shut off the base circuit.
Since this device is not designed for stopping. Do not switch it on during operation.
3 - 5
3. SIGNALS AND WIRING
Devices Connector
Device name
Functions/Applications
symbol
pin No.
CN1B To start operation, short LSP-SG and/or LSN-SG. Open them to bring the motor to
Forward rotation
stroke end
LSP
16
a sudden stop and make it servo-locked.
Set "
1" in parameter No. 22 to make a slow stop.
(Refer to section 5.2.5.)
(Note) Input signal
Operation
CCW
direction
CW
LSP
LSN
direction
1
0
1
0
1
1
0
0
Reverse rotation stroke
end
LSN
ST1
CN1B
17
Note. 0: LSP/LSN-SG off (open)
1: SP/LSN-SG on (short)
Forward rotation start
CN1B 1. In the case of the absolute value command system.
8
When ST1-SG are shorted in the automatic operation mode, positioning is
executed once on the basis of the position data set to the point table.
In home position return mode, home position return starts as soon as ST1-SG
are shorted.
In jog operation mode, the servo motor rotates in the forward rotation direction
while ST1-SG are shorted.
2. In the case of the incremental value command system.
When ST1-SG are shorted in the automatic operation mode, positioning is
executed once on the basis of the position data set to the point table.
In home position return mode, home position return starts as soon as ST1-SG
are shorted.
In jog operation mode, the servo motor rotates in the forward rotation direction
while ST1-SG are shorted.
Forward rotation denotes the direction in which the address is incremented.
3. In absolute value command /incremental value command specifying system
When ST1-SG are shorted in the automatic operation mode, positioning is
executed once on the basis of the position data set to the point table.
In home position return mode, home position return starts as soon as ST1-SG
are shorted.
In jog operation mode, the servo motor rotates in the forward rotation direction
while ST1-SG are shorted.
Reverse rotation start
ST2
CN1B This device is used in the incremental value command system.
9
When ST2-SG are shorted in the automatic operation mode, positioning is executed
once in the reverse rotation direction on the basis of the position data set to the
point table.
In jog operation mode, the servo motor rotates in the reverse rotation direction
while ST2-SG are shorted.
Reverse rotation denotes the direction in which the address is decremented.
The reverse rotation start (ST2) is also used as the start signal of the function to
perform high-speed positioning to the home position. (Refer to section 4.4.11.)
Automatic/manual
selection
MD0
DOG
CN1B Short MD0-SG to choose the automatic operation mode, or open them to choose the
manual operation mode.
CN1A When terminals DOG-SG are shorted, the proximity dog signal is detected. The
7
Proximity dog
8
polarity of dog detection input can be changed with the parameter.
Polarity of proximity dog
Parameter No.8
detection input
0
1
(initial value)
DOG-SG are opened.
DOG-SG are shorted.
3 - 6
3. SIGNALS AND WIRING
Devices Connector
Device name
Functions/Applications
symbol
pin No.
Point table No.
selection 1
DI0
CN1B The following table lists the point table numbers that may be chosen by the
5
combinations of DI0, DI1, DI2, DI3 and DI4.
(Note)Input signal
Point table No.
Point table No.
selection 2
DI1
CN1B
14
DI4
DI3
DI2
DI1
DI0
0 (Manual home
position return)
0
0
0
0
0
Point table No.
selection 3
DI2
DI3
DI4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1
2
Point table No.
selection 4
3
4
Point table No.
selection 5
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Note. 0: DI0/DI1/DI2/DI3/DI4-SG off (open)
1: DI0/DI1/DI2/DI3/DI4-SG on (short)
Override selection
External torque limit
selection
OVR
TL
Short OVR-SG to make override (VC) valid.
Short TL-SG to make external analog torque limit valid.
For more information, refer to section 3.4.4.
Internal torque limit
selection
TL2
PC
Open TL2-SG to make the torque limit value set in parameter No.28 (TL1) valid, or
short them to make the value set in parameter No.29 (TL2) valid.
For more information, refer to section 3.4.4.
Proportion control
Connect PC-SG to switch the speed amplifier from the proportional integral type to
the proportional type.
If the servo motor at a stop is rotated even one pulse due to any external factor, it
generates torque to compensate for a position shift. In such a case where the axis
will be locked mechanically after Movement finish (MEND) has turned off, turning
Proportion control (PC) on as soon as Movement finish (MEND) turns off can
suppress unnecessary torque that attempts to compensate for a position shift.
When the shaft is to be locked for a long time, switch on the proportion control (PC)
and torque (TL) at the same time to make the torque less than the rated by the
analog torque limit (TLA).
3 - 7
3. SIGNALS AND WIRING
Devices Connector
Functions/Applications
Device name
Temporary
symbol
pin No.
STP
Short STP-SG during automatic operation to make a temporary stop. Short STP-
SG again to make a restart.
stop/Restart
Shorting the forward rotation start (ST1) or reverse rotation start (ST2) during a
temporary stop is ignored. Switching from automatic operation mode to manual
operation mode during a temporary stop clears the remaining moving distance.
During home position return and jog operation, the temporary stop/restart input is
ignored. Refer to section 4.2.6 (3).
Manual pulse
generator
multiplication 1
Manual pulse
generator
multiplication 2
TP0
TP1
Used to select the multiplication factor of the manual pulse generator.
When it is not selected, the parameter No.1 setting is made valid.
(Note) Input signal
Manual pulse generator
multiplication factor
TP1
TP0
0
0
1
1
0
1
0
1
Parameter No.1 setting
1 time
10 times
100 times
Note. 0: TP1/TP0-SG open
1: TP1/TP0-SG shorted
Gain switch
Teach
CDP
TCH
Connect CDP-SG to change the load inertia moment ratio into the parameter No.
64 setting and the gain values into the values multiplied by the parameter No. 65
to 67 settings.
Used when performing teaching. Shorting TCH-SG in the teaching setting mode
chooses this device and changes the position data of the point table No. to the
current position. (Refer to section 7.10.)
3 - 8
3. SIGNALS AND WIRING
(c) Output devices
Devices Connector
Device name
Trouble
Functions/Applications
symbol
pin No.
CN1B ALM-SG are disconnected when power is switched off or the protective circuit is
ALM
18
activated to shut off the base circuit. Without alarm, ALM-SG are connected within
about 1s after power-on.
Ready
RD
CN1B RD-SG are connected when the servo is switched on and the servo amplifier is
19 ready to operate.
CN1B MEND-SG are connected when the in-position device (INP) turns on and the
Movement finish
MEND
6
command remaining distance is "0". (Refer to section 3.4.2.)
MEND-SG are connected at servo on.
Rough match
CPO
ZP
CN1B CPO-SG are connected when the remaining command distance falls within the
4
parameter-set rough match output range.
This signal is not output while the base circuit is off. Servo-on connects CPO-SG.
During home position return and manual operation, CPO-SG are kept connected.
Home position return
completion
CN1A ZP-SG are connected on completion of home position return.
18
In the absolute position system, ZP-SG are connected when the servo amplifier is
ready to operate but are disconnected if.
1) SON-SG are opened.
2) EMG-SG are opened.
3) RES-SG are shorted.
4) Alarm occurs.
5) Limit switch opens.
6) Home position return has not been made after the purchase of the product.
7) Home position return has not been made after the occurrence of absolute position
erasure (AL. 25) or absolute position counter warning (AL. E3).
8) Home position return has not been made after the changing of the electronic gear
value.
9) Home position return has not been made after the absolute position system was
made valid.
10) The ST1 coordinate system (000 in parameter No.1) has been changed.
11) Software limit is valid.
12) Home position return completion.
If the status is not any of 1) to 12) and the home position setting has already been
completed at least once, home position return completion (ZP) is placed in the same
output status as ready (RD).
Electromagnetic brake
interlock
MBR
POT
In the servo-off or alarm status, MBR-SG are disconnected.
When an alarm occurs, they are disconnected independently of the base circuit
status.
Position range (POT) is on when the current position is within the range set in
parameters No. 50 to 53. If the current position is within the set range, the device
is off when a home position return is not yet complete or while the base circuit is off
(during servo off, alarm occurrence or alarm reset).
When warning has occurred, WNG-SG are connected.
When there is no warning, WNG-SG are disconnected within about 1s after power-
on.
Position range
Warning
WNG
Battery warning
BWNG
BWNG-SG are connected when battery cable breakage warning (AL.92) or battery
warning (AL.9F) has occurred.
When there is no battery warning, BWNG-SG are disconnected within about 1s
after power-on.
Limiting torque
Temporary stop
In position
TLC
PUS
INP
TLC-SG are connected when the torque generated reaches the value set to the
internal torque limit 1 (parameter No. 28), internal torque limit 1 (parameter No.
29) or analog torque limit (TLA).
PUS-SG are connected when deceleration to a stop is started by the temporary stop
signal. PUS-SG is disconnected when operation is resumed by making the
temporary stop signal valid again.
INP-SG are connected when the number of droop pulses is in the preset in-position
range. The in-position range can be changed using parameter No. 6.
When the in-position range is increased, INP-SG may be kept connected during
low-speed rotation. Servo-on connects INP-SG.
3 - 9
3. SIGNALS AND WIRING
Devices Connector
Device name
Functions/Applications
symbol
pin No.
Point table No. output 1
PT0
As soon as Movement finish (MEND) turns on, the point table No. is output as a 5-
bit code.
Point table No. output 2
Point table No. output 3
Point table No. output 4
Point table No. output 5
PT1
PT2
PT3
PT4
(Note) Output signal
Point table No.
PT4
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
PT3
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
PT2
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
PT1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
PT0
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Note. 0: DI-SG open
1: DI-SG shorted
In any of the following states, PT0 to PT4-SG are opened.
Power on
Servo off
During home position return
Home position return completion
In any of the following states, PT0 to PT4 maintain the status (shorted/open) prior
to a change.
At operation mode changing
When the automatic/manual selection device (MD0) is turned from OFF to ON or
from ON to OFF to switch the operation mode.
During manual operation
During execution of automatic positioning to the home position
3 - 10
3. SIGNALS AND WIRING
(2) Input signal
For the input interfaces (symbols in I/O column in the table), refer to section 3.6.2.
Signal Connector
I/O
Signal
Functions/Applications
symbol
PP
pin No.
CN1A-3 Used to connect the manual pulse generator (MR-HDP01).
division
Manual pulse
generator
For details, refer to section 14.1.8.
NP
CN1A-2
CN1B-2
Override
VC
10 to 10V is applied to across VC-LG to limit the servo motor speed.
Apply 10[V] for 0[%] override, 0[V] for 100[%], or 10[V] for 200[%].
Analog
input
Analog torque limit
TLA
CN1B To use this signal, set any of MR Configurator (servo configuration
12 software) to make the external torque limit selection (TL) available.
When the analog torque limit (TLA) is valid, torque is limited in the full Analog
servo motor output torque range. Apply 0 to 10VDC across TLA-LG.
Connect the positive terminal of the power supply to TLA. Maximum
torque is generated at 10V. (Refer to in section 3.4.4.) Resolution:10bits
input
(3) Output signal
For the output interfaces (symbols in I/O column in the table), refer to section 3.6.2.
Signal Connector
I/O
Signal
Functions/Applications
symbol
pin No.
CN1A Outputs the zero-point signal of the encoder. One pulse is output per
division
Encoder Z-phase pulse
(open collector)
OP
14
servo motor revolution. OP and LG are connected when the zero-point
position is reached. (Negative logic)
DO-2
The minimum pulse width is about 400 s. For home position return
using this pulse, set the creep speed to 100r/min. or less.
Encoder A-phase pulse
(differential line driver)
LA
LAR
LB
CN1A Outputs pulses per servo motor revolution set in parameter No. 27 in the
differential line driver system. In CCW rotation of the servo motor, the
CN1A encoder B-phase pulse lags the encoder A-phase pulse by a phase angle
6
DO-2
DO-2
DO-2
16
CN1A
7
of /2.
The relationships between rotation direction and phase difference of the
A- and B-phase pulses can be changed using parameter No. 58.
Encoder B-phase pulse
(differential line driver)
LBR
LZ
CN1A
17
Encoder Z-phase pulse
(differential line driver)
CN1A The same signal as OP is output in the differential line driver system.
5
LZR
MO1
MO2
CN1A
15
Analog monitor 1
Analog monitor 2
CN3
4
Used to output the data set in parameter No.17 to across MO1-LG in
terms of voltage. Resolution 10 bits
Analog
output
Analog
output
CN3
14
Used to output the data set in parameter No.17 to across MO2-LG in
terms of voltage. Resolution 10 bits
3 - 11
3. SIGNALS AND WIRING
(4) Communication
POINT
Refer to chapter 15 for the communication function.
Signal Connector
Signal
RS-422 I/F
Functions/Applications
symbol
pin No.
SDP
CN3
9
RS-422 and RS-232C functions cannot be used together.
Choose either one in parameter No. 16.
SDN
RDP
RDN
TRE
CN3
19
CN3
5
CN3
15
RS-422 termination
RS-232C I/F
CN3
10
Termination resistor connection terminal of RS-422 interface.
When the servo amplifier is the termination axis, connect this terminal to RDN
(CN3-15).
TXD
RXD
CN3
2
RS-422 and RS-232C functions cannot be used together.
Choose either one in parameter No. 16.
CN3
12
(5) Power supply
Signal Connector
Signal
Functions/Applications
symbol
pin No.
I/F internal power
supply
VDD
CN1B Used to output 24V 10% to across VDD-SG.
3
When using this power supply for digital interface, connect it with COM.
Permissible current : 80mA
Digital I/F power
supply input
COM
CN1A Used to input 24VDC (200mA or more) for input interface.
Connect the positive ( ) terminal of the 24VDC external power supply.
9
CN1B 24VDC 10%
13
Open collector power
input
OPC
SG
CN1A When you use a manual pulse generator , supply this terminal with the positive ( )
11
power of 24VDC.
Digital I/F common
CN1A Common terminal for input signals such as SON and EMG. Pins are connected
10
20
internally.
Separated from LG.
CN1B
10
20
15VDC power supply
Control common
P15R
LG
CN1A Outputs 15VDC to across P15R-LG. Available as power for VC and VLA.
4
Permissible current: 30mA
CN1B
11
CN1A Common terminal for TLA, VC, OP, MO1, MO2 and P15R.
1
Pins are connected internally.
CN1B
1
CN3
1, 11
3, 13
Shield
SD
Plate Connect the external conductor of the shield cable.
3 - 12
3. SIGNALS AND WIRING
3.4 Detailed description of signals (devices)
3.4.1 Forward rotation start Reverse rotation start Temporary stop/restart
(1) A forward rotation start (ST1) or a reverse rotation start (ST2) should make the sequence which can
be used after the main circuit has been established. These signals are invalid if it is switched on before
the main circuit is established.
Normally, it is interlocked with the ready signal (RD).
(2) A start in the servo amplifier is made when the external start signal changes from OFF to ON. The
delay time of the servo amplifier's internal processing is max. 3ms. The delay time of other signals is
max. 10ms.
3ms or less
3ms or less
Servo motor speed
10ms
or less
Forward rotation start (ST1)
or reverse rotation start (ST2)
5ms or more
Temporary stop/Restart (STP)
(3) When a programmable controller is used, the ON time of the start/stop signal should be 5ms or longer
to prevent a malfunction.
(4) During operation, the forward rotation start (ST1) or reverse rotation start (ST2) is not accepted. The
next operation should always be started after the rough match (CPO) is output with the rough match
output range set to 0 or after the movement finish (MEND) is output.
3 - 13
3. SIGNALS AND WIRING
3.4.2 Movement finish Rough match In position
POINT
If an alarm cause, etc. are removed and servo-on occurs after a stop is
made by servo-off, alarm occurrence or Forced stop (EMG) ON during
automatic operation, Movement finish (MEND), Rough-match, (CPO) and
In position (INP) are turned on. To resume operation, confirm the current
position and the selected point table No. for preventing unexpected
operation.
(1) Movement finish
The following timing charts show the output timing relationships between the position command
generated in the servo amplifier and the movement finished (MEND). This timing can be changed
using parameter No. 6 (in-position range). MEND-SG are connected in the servo-on status.
ON
Forward rotation start (ST1)
or reverse rotation start (ST2)
OFF
Position command
3ms or less
Servo motor speed
Position command and
servo motor speed
In-position range
ON
Movement finish (MEND)
OFF
When parameter No. 6 is small
ON
Forward rotation start (ST1)
or reverse rotation start (ST2)
OFF
Position command
3ms or less
Servo motor speed
Position command and
servo motor speed
In-position range
ON
Movement finish (MEND)
OFF
When parameter No. 6 is large
(2) Rough match
The following timing charts show the relationships between the signal and the position command
generated in the servo amplifier. This timing can be changed using parameter No. 12 (rough match
output range). CPO-SG are connected in the servo-on status.
Forward rotation start
(ST1) or
reverse rotation start
(ST2)
ON
ON
Forward rotation start
(ST1) or
reverse rotation start
(ST2)
OFF
OFF
Rough match output range
3ms or less
3ms or less
Position command
Position command
ON
ON
Rough match (CPO)
Rough match (CPO)
OFF
OFF
When "0" is set in parameter No. 12
When more than "0" is set in parameter No. 12
3 - 14
3. SIGNALS AND WIRING
(3) In position
The following timing chart shows the relationship between the signal and the feedback pulse of the
servo motor. This timing can be changed using parameter No. 6 (in-position range). INP-SG are
connected in the servo-on status.
ON
Forward rotation start (ST1)
or reverse rotation start (ST2)
Servo motor speed
OFF
In-position range
3ms or less
ON
In position (INP)
OFF
When positioning operation is performed once
ON
Forward rotation start (ST1)
or reverse rotation start (ST2)
OFF
3ms or less
In-position range
Forward
rotation
Servo motor speed
Reverse
rotation
ON
In position (INP)
OFF
When servo motor reverses rotation direction during automatic continuous operation
3 - 15
3. SIGNALS AND WIRING
3.4.3 Override
POINT
When using the override (VC), make the override selection (OVR) device
available.
The override (VC) may be used to change the servo motor speed. The following table lists the signals and
parameter related to the override.
Item
Name
Remarks
Analog input signal
Override (VC)
MR Configurator (servo configuration software)
setting required.
Contact input signal
Parameter
Override selection (OVR)
No.25 override offset
999 to 999mV
(1) Override (VC)
By applying a voltage ( 10 to 10V) to the override (VC) terminal, change values can be set from
outside consecutively. The following graph shows the relationship between the input voltage and the
ratio of actual speed to preset speed.
Servo amplifier
[%]
200
OVR
Override selection (OVR)
SG
100
VC
LG
SD
Override (VC)
10 to 10V
0
0
10
10
[V]
Override (VC) application voltage
(2) Override selection (OVR)
Used to make the override (VC) valid or invalid.
Servo amplifier
Motor
Override selection
(OVR)
Override (VC)
10 to 10V
Using the override selection (OVR), choose a change value as follows.
(Note)
Speed change value
External input signal
OVR
0
1
No change
Override (VC) setting is made valid.
Note. 0 : Off (open) across OVR-SG
1 : On (shorted) across OVR-SG
(3) Override offset (parameter No.25)
Using parameter No.25, the offset voltage can be set relative to the input voltage for the override (VC).
The setting is between 999 to 999mV.
3 - 16
3. SIGNALS AND WIRING
3.4.4 Torque limit
POINT
To use the torque limit, make the external torque limit selection (TL) and
internal torque limit selection (TL2) available.
The following table lists the signals and parameters related to the torque limit.
Item
Name
Remarks
Analog input signal
Analog torque limit (TLA)
External torque limit selection (TL)
Internal torque limit selection (TL2)
Limiting torque (TLC)
Contact input signals
Contact output signal
MR Configurator (servo configuration
software) setting required.
No.28 (internal torque limit 1)
No.29 (internal torque limit 2)
No.26 (torque limit offset)
0 to 100%
0 to 100%
Parameters
999 to 999mV
Selection of the rotation direction in which
torque limit is executed
No.59 (function selection 2)
The torque limit is available in two types: internal torque limit set in parameters and analog torque limit
(TLA) using analog input signal. This function limits torque on the assumption that the maximum torque
of the servo motor is 100%.
(1) Internal torque limits 1, 2
Use parameter No.28 and 29 to set the internal torque limit values. The following graph shows the
torque relative to the setting.
Max. torque
0
0
100
Torque limit value [%]
(2) Analog torque limit (TLA)
By applying a voltage (0 to 10V) to the analog torque limit (TLA) terminal, limit values can be set from
outside consecutively. The following graph shows the relationship between input voltage and limit
value.
Depending on the servo amplifier, the limit value has about 5% variations to the input voltage. As this
may not cause torque to be limited sufficiently at less than 0.05V, use this function at the voltage of
0.05V or more.
Refer to the following diagram when using the 15V power output (P15R) of the servo amplifier:
Servo amplifier
100
TL
SG
P15R
5%
2k
2k
TLA
LG
0
Japan Resistor RRS10
or equivalent
0 0.05
10
SD
TLA application voltage [V]
TLA Application Voltage vs.
Torque Limit Value
Connection Example
3 - 17
3. SIGNALS AND WIRING
(3) External torque limit selection (TL), internal torque limit selection (TL2)
To use the external torque limit selection (TL) and internal torque limit selection (TL2), make them
available using the MR Configurator (servo configuration software) (refer to chapter 6).
These input signals may be used to choose the torque limit values made valid.
(Note) External input signals
Torque limit value made valid
TL2
TL
0
0
Internal torque limit value 1 (parameter No. 28)
TLA Parameter No. 28: Parameter No. 28
TLA Parameter No. 28: TLA
0
1
1
1
0
1
Parameter No. 29 Parameter No. 28: Parameter No. 28
Parameter No. 29 Parameter No. 28: Parameter No. 29
TLA Parameter No. 29: Parameter No. 29
TLA Parameter No. 29: TLA
Note. 0: TL/TL2-SG off (open)
1: TL/TL2-SG on (short)
(4) External torque limit offset (parameter No.26)
Using parameter No.26, the offset voltage can be set relative to the input voltage of the analog torque
limit (TLA). The setting is between 999 to 999mV.
(5) Selection of rotation direction for torque limit execution (parameter No.59)
Using parameter No.59, the rotation direction for torque limit execution can be selected.
Rotation direction for torque limit execution
Parameter No.59 setting
CCW direction
CW direction
0
1
2
(initial value)
For example, when “
1
” is set in parameter No.59, torque limit is executed in the CCW direction
but not in CW direction.
CCW rotation: Torque limit is executed.
CW rotation: Torque limit is not executed.
3 - 18
3. SIGNALS AND WIRING
3.5 Alarm occurrence timing chart
When an alarm has occurred, remove its cause, make sure that the operation
signal is not being input, ensure safety, and reset the alarm before restarting
operation.
CAUTION
As soon as an alarm occurs, turn off Servo-on (SON) and power off.
When an alarm occurs in the servo amplifier, the base circuit is shut off and the servo motor is coated to a
stop. Switch off the main circuit power supply in the external sequence. To reset the alarm, switch the
control circuit power supply from off to on, press the "SET" button on the current alarm screen, or turn
the reset (RES) from off to on. However, the alarm cannot be reset unless its cause is removed.
(Note)
Main circuit
control circuit
power supply
ON
OFF
ON
Power off
Power on
Base circuit
OFF
Dynamic brake Valid
Invalid
Brake operation
Brake operation
Servo-on
(SON)
ON
OFF
ON
Ready
(RD)
OFF
ON
Trouble
(ALM)
OFF
ON
1s
Reset
(RES)
OFF
50ms or more
60ms or more
Alarm occurs.
Remove cause of trouble.
Note. Switch off the main circuit power as soon as an alarm occurs.
(1) Overcurrent, overload 1 or overload 2
If operation is repeated by switching control circuit power off, then on to reset the overcurrent
(AL.32), overload 1 (AL.50) or overload 2 (AL.51) alarm after its occurrence, without removing
its cause, the servo amplifier and servo motor may become faulty due to temperature rise.
Securely remove the cause of the alarm and also allow about 30 minutes for cooling before
resuming operation.
(2) Regenerative alarm
If operation is repeated by switching control circuit power off, then on to reset the regenerative
(AL.30) alarm after its occurrence, the external regenerative resistor will generate heat,
resulting in an accident.
(3) Instantaneous power failure
Undervoltage (AL.10) occurs when the input power is in either of the following statuses.
A power failure of the control circuit power supply continues for 60ms or longer and the
control circuit is not completely off.
The bus voltage dropped to 200VDC or less for the MR-J2S- CP, or to 158VDC or less for the
MR-J2S- CP1.
(4) Incremental system
When an alarm occurs, the home position is lost. When resuming operation after deactivating
the alarm, make a home position return.
3 - 19
3. SIGNALS AND WIRING
3.6 Interfaces
3.6.1 Common line
The following diagram shows the power supply and its common line.
CN1A
CN1B
CN1A
CN1B
24VDC
RA
VDD
ALM,etc
COM
DO-1
SON,etc.
Dl-1
SG
OPC
Manual pulse generator
MR-HDP01
5V
A(B)
0V
PP(NP)
SG
SG
<Isolated>
OP
LG
5V
15VDC 10% 30mA
P15R
LA,etc
Differential line driver
LAR,etc
output
LG
SD
35mA or less
TLA
VC,
etc.
Analog input
(
10V/max. current)
MO1
MO2
CN3
Analog monitor
LG
SD
LG
Single-phase
100 to 200VAC
SDP
SDN
RDP
RXD L1
RXD L2
TXD
RDN
LG
SD
TXD
LG
E
Servo motor encoder
CN2
MR
Servo motor
M
MRR
SD
Ground
3 - 20
3. SIGNALS AND WIRING
3.6.2 Detailed description of the interfaces
This section gives the details of the I/O signal interfaces (refer to I/O Division in the table) indicated in
sections 3.3.2. Refer to this section and connect the interfaces with the external equipment.
(1) Digital input interface DI-1
Give a signal with a relay or open collector transistor. Source input is also possible. Refer to (6) of this
section.
For use of internal power supply
For use of external power supply
Servo amplifier
Do not connect
VDD-COM.
24VDC
VDD
Servo amplifier
R: Approx. 4.7k
COM
24VDC
VDD
24VDC
R: Approx. 4.7k
200mA or more
COM
(Note)
For a transistor
SON, etc.
Approx. 5mA
SON, etc.
Switch
TR
SG
Switch
V CES 1.0V
I CEO 100
SG
A
Note. This also applies to the use of the external power supply.
(2) Digital output interface DO-1
A lamp, relay or photocoupler can be driven. Provide a diode (D) for an inductive load, or an inrush
current suppressing resister (R) for a lamp load. (Permissible current: 40mA or less, inrush current:
100mA or less) A maximum of 2.6V voltage drop occurs in the servo amplifier.
(a) Inductive load
For use of internal power supply
For use of external power supply
Servo amplifier
Servo amplifier
Do not connect
VDD-COM.
24VDC
24VDC
VDD
VDD
COM
COM
(Note)
24VDC
10%
Load
Load
ALM, etc
SG
ALM, etc
SG
If the diode is not
connected as shown,
the servo amplifier
will be damaged.
If the diode is not
connected as shown,
the servo amplifier
will be damaged.
Note. If the voltage drop (maximum of 2.6V) interferes with the
relay operation, apply high voltage (up to 26.4V) from
external source.
3 - 21
3. SIGNALS AND WIRING
(b) Lamp load
For use of internal power supply
For use of external power supply
Servo amplifier
Servo amplifier
Do not connect
24VDC
24VDC
VDD
VDD
VDD-COM.
COM
COM
R
R
(Note)
24VDC
10%
ALM, etc
SG
ALM, etc
SG
Note. If the voltage drop (maximum of 2.6V) interferes with the
relay operation, apply high voltage (up to 26.4V) from
external source.
(3) Encoder pulse output DO-2
(a) Open collector system
Interface
Max. output current : 35mA
Servo amplifier
Servo amplifier
5 to 24VDC
OP
LG
OP
LG
Photocoupler
SD
SD
(b) Differential line driver system
1) Interface
Max. output current: 35mA
Servo amplifier
Servo amplifier
LA
(LB, LZ)
LA
(LB, LZ)
Am26LS32 or equivalent
150
High-speed photocoupler
100
LAR
LAR
(LBR, LZR)
(LBR, LZR)
LG
SD
SD
3 - 22
3. SIGNALS AND WIRING
2) Output pulse
Servo motor CCW rotation
LA
LAR
LB
The time cycle (T) is determined by
the setting of the parameter No. 27 and 58.
T
LBR
/2
LZ
LZR
400 s or more
OP
(4) Analog input
Input impedance 10k to 12k
Servo amplifier
15VDC
P15R
Upper limit setting 2k
VC‚ etc
2k
Approx.
10k
LG
SD
(5) Analog output
Output voltage 10V
Max.1mA
Max. output current
Resolution : 10bits
Servo amplifier
10k
MO1
(MO2)
Reading in one or
both directions
1mA meter
A
LG
SD
3 - 23
3. SIGNALS AND WIRING
(6) Source input interface
When using the input interface of source type, all Dl-1 input signals are of source type. Source output
cannot be provided.
For use of internal power supply
For use of external power supply
Servo amplifier
Servo amplifier
SG
SG
R: Approx. 4.7k
COM
(Note)
R: Approx. 4.7k
COM
For a transistor
Approx. 5mA
SON,
etc.
Switch
Switch
SON,etc.
24VDC
VDD
TR
24VDC
200mA or more
VCES 1.0V
ICEO 100 A
Note. This also applies to the use of the external power supply.
Since source output is not provided, make the following circuit.
For use of internal power supply For use of external power supply
Servo amplifier
Servo amplifier
Do not connect
VDD-COM.
24VDC
24VDC
VDD
VDD
COM
COM
(Note)
24VDC
10%
Load
Load
ALM, etc
SG
ALM, etc
SG
If the polarity of diode
is not correct, the
servo amplifier will
become faulty.
If the polarity of diode
is not correct, the
servo amplifier will
become faulty.
Note. If the voltage drop (maximum of 2.6V) interferes with the
relay operation, apply high voltage (up to 26.4V) from
external source.
3 - 24
3. SIGNALS AND WIRING
3.7 Input power supply circuit
Always connect a magnetic contactor (MC) between the main circuit power supply
and L1, L2, and L3 of the servo amplifier, and configure the wiring to be able to shut
down the power supply on the side of the servo amplifier’s power supply. If a
magnetic contactor (MC) is not connected, continuous flow of a large current may
cause a fire when the servo amplifier malfunctions.
CAUTION
Use the trouble signal to switch power off. Otherwise, a regenerative transistor
fault or the like may overheat the regenerative resistor, causing a fire.
3.7.1 Connection example
Wire the power supply and main circuit as shown below so that the servo-on (SON) turns off as soon as
alarm occurrence is detected and power is shut off.
A circuit breaker (NFB) must be used with the input cables of the power supply.
(1) For 3-phase 200 to 230VAC power supply
Forced
ON
OFF
stop
RA
MC
SK
MC
NFB
MC
Servo amplifier
L1
3-phase
200 to 230 VAC
L2
L3
L11
L21
EMG
SON
SG
Forced stop
Servo-on
VDD
COM
ALM
Trouble
RA
3 - 25
3. SIGNALS AND WIRING
(2) For 1-phase 100 to 120VAC or 1-phase 230VAC power supply
Forced
stop
ON
MC
OFF
RA
MC
SK
NFB
MC
Power supply
1-phase 100 to
120VAC or
Servo amplifier
(Note)
L1
L2
1-phase 230VAC
L3
L11
L21
EMG
SON
SG
Forced stop
Servo-on
VDD
COM
ALM
Trouble
RA
Note : Not provided for 1-phase 100 to 120VAC.
3 - 26
3. SIGNALS AND WIRING
3.7.2 Terminals
The positions and signal arrangements of the terminal blocks change with the capacity of the servo
amplifier. Refer to section 12.1.
Connection Target
Symbol
Description
(Application)
Supply L1, L2 and L3 with the following power.
For 1-phase 230VAC, connect the power supply to L1/L2 and leave L3 open.
Servo amplifier MR-J2S-10CP MR-J2S-100CP MR-J2S-10CP1
Power supply
to 70CP
L1 L2 L3
L1 L2
to 700CP
to 40CP1
3-phase 200 to 230VAC,
50/60Hz
L1, L2, L3
Main circuit power supply
1-phase 230VAC,
50/60Hz
1-phase 100 to 120VAC,
50/60Hz
L1 L2
Connect to the servo motor power supply terminals (U, V, W).
U, V, W
Servo motor output
During power-on, do not open or close the motor power line. Otherwise, a
malfunction or faulty may occur.
Servo amplifier
MR-J2S-10CP to
700CP
MR-J2S-10CP1 to
40CP1
Power supply
1-phase 200 to 230VAC,
50/60Hz
L11, L21
Control circuit power supply
L11 L21
1-phase 100 to 120VAC,
50/60Hz
L11 L21
1) MR-J2S-350CP or less
When using servo amplifier built-in regenerative resistor, connect between P-D
terminals. (Wired by default)
When using regenerative option, disconnect between P-D terminals and
connect regenerative option to P terminal and C terminal.
2) MR-J2S-500CP or 700CP
P, C, D
Regenerative option
MR-J2S-500CP and 700CP do not have D terminal.
When using servo amplifier built-in regenerative resistor, connect P terminal
and C terminal. (Wired by default)
When using regenerative option, disconnect P terminal and C terminal and
connect regenerative option to P terminal and C terminal.
Refer to section 14.1.1 for details.
When using brake unit, connect to P terminal and N terminal.
Do not connect to servo amplifier MR-J2S-200CP or less.
For details, refer to section 14.1.2, 14.1.3.
Return converter
Brake unit
N
Connect this terminal to the protective earth (PE) terminals of the servo motor
and control box for grounding.
Protective earth (PE)
3 - 27
3. SIGNALS AND WIRING
3.7.3 Power-on sequence
(1) Power-on procedure
1) Always wire the power supply as shown in above section 3.7.1 using the magnetic contactor with
the main circuit power supply (three-phase 200V: L1, L2, L3, single-phase 230V single-phase
100V: L1, L2). Configure up an external sequence to switch off the magnetic contactor as soon as an
alarm occurs.
2) Switch on the control circuit power supply L11, L21 simultaneously with the main circuit power
supply or before switching on the main circuit power supply. If the main circuit power supply is not
on, the display shows the corresponding warning. However, by switching on the main circuit power
supply, the warning disappears and the servo amplifier will operate properly.
3) The servo amplifier can accept the servo-on (SON) about 1 to 2s after the main circuit power supply
is switched on. Therefore, when servo-on (SON) is switched on simultaneously with the main circuit
power supply, the base circuit will switch on in about 1 to 2s, and the ready (RD) will switch on in
further about 20ms, making the servo amplifier ready to operate. (Refer to paragraph (2) of this
section.)
4) When the reset (RES) is switched on, the base circuit is shut off and the servo motor shaft coasts.
(2) Timing chart
SON accepted
(1 to 2s)
ON
Power supply
OFF
ON
Base circuit
OFF
60ms
10ms
10ms
10ms
Servo-on
(SON)
ON
OFF
60ms
Reset
(RES)
ON
OFF
20ms
20ms
10ms
20ms
10ms
Ready
(RD)
ON
OFF
(3) Forced stop
Provide an external forced stop circuit to ensure that operation can be stopped and
power switched off immediately.
CAUTION
Forced stop (EMG) can be used by making device setting on the MR Configurator (servo configuration
software).
Make up a circuit which shuts off main circuit power as soon as EMG-SG are opened at a forced stop.
To ensure safety, always install an external forced stop switch across EMG-SG. By disconnecting
EMG-SG, the dynamic brake is operated to bring the servo motor to a sudden stop. At this time, the
display shows the servo forced stop warning (AL.E6).
During ordinary operation, do not use the external forced stop (EMG) to alternate stop and run.
The servo amplifier life may be shortened.
Servo amplifier
VDD
COM
EMG
Forced stop
SG
3 - 28
3. SIGNALS AND WIRING
3.8 Connection of servo amplifier and servo motor
3.8.1 Connection instructions
Insulate the connections of the power supply terminals to prevent an electric
WARNING
shock.
Connect the wires to the correct phase terminals (U, V, W) of the servo amplifier
and servo motor. Otherwise, the servo motor will operate improperly.
CAUTION
Do not connect AC power supply directly to the servo motor. Otherwise, a fault
may occur.
POINT
Do not apply the test lead bars or like of a tester directly to the pins of the
connectors supplied with the servo motor. Doing so will deform the pins,
causing poor contact.
The connection method differs according to the series and capacity of the servo motor and whether or not
the servo motor has the electromagnetic brake. Perform wiring in accordance with this section.
(1) For grounding, connect the earth cable of the servo motor to the protective earth (PE) terminal of the
servo amplifier and connect the ground cable of the servo amplifier to the earth via the protective
earth of the control box. Do not connect them directly to the protective earth of the control panel.
Control box
Servo
amplifier
Servo motor
PE terminal
(2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
3.8.2 Connection diagram
During power-on, do not open or close the motor power line. Otherwise, a
CAUTION
malfunction or faulty may occur.
The following table lists wiring methods according to the servo motor types. Use the connection diagram
which conforms to the servo motor used. For cables required for wiring, refer to section 14.2.1. For
encoder cable connection, refer to section 14.1.4. For the signal layouts of the connectors, refer to section
3.8.3.
For the servo motor connector, refer to chapter 3 of the Servo Motor Instruction Manual.
3 - 29
3. SIGNALS AND WIRING
Servo motor
Connection diagram
Servo amplifier
Servo motor
Motor
U (Red)
U
V
V (White)
W (Black)
(Green)
W
24VDC
(Note 1)
B1
B2
(Note 2)
HC-KFS053 (B) to 73 (B)
HC-MFS053 (B) to 73 (B)
HC-UFS13 (B) to 73 (B)
Electromagnetic
brake
EMG
To be shut off when servo-on (SON)
switches off or by Trouble (ALM)
CN2
Encoder
Encoder cable
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo amplifier
Servo motor
Motor
U
V
U
V
W
W
(Note 1) 24VDC
EMG
B1
B2
HC-SFS121 (B) to 301 (B)
HC-SFS202 (B) to 702 (B)
HC-SFS203 (B) 353 (B)
HC-UFS202 (B) to 502 (B)
HC-RFS353 (B) to 503 (B)
(Note 2)
Electromagnetic
brake
To be shut off when servo-on (SON)
switches off or by Trouble (ALM)
CN2
Encoder
Encoder cable
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
Servo amplifier
Servo motor
Motor
U
V
U
V
W
W
24VDC
(Note 1)
HC-SFS81(B)
B1
B2
(Note 2)
HC-SFS52 (B) to 152 (B)
HC-SFS53 (B) to 153 (B)
HC-RFS103 (B) to 203 (B)
HC-UFS72 (B) 152 (B)
EMG
Electromagnetic
brake
To be shut off when servo-on (SON)
switches off or by Trouble (ALM)
CN2
Encoder
Encoder cable
Note 1. To prevent an electric shock, always connect the protective earth (PE) terminal ( ) of the
servo amplifier to the protective earth (PE) of the control box.
2. This circuit applies to the servo motor with electromagnetic brake.
3 - 30
3. SIGNALS AND WIRING
3.8.3 I/O terminals
(1) HC-KFS HC-MFS HC-UFS3000r/min series
Encoder connector signal arrangement
Power supply lead
4-AWG19 0.3m (0.98ft.)
1
MR
4
2
MRR
5
3
BAT
6
Power supply connector (Molex)
Without electromagnetic brake
5557-04R-210 (receptacle)
5556PBTL (Female terminal)
With electromagnetic brake
5557-06R-210 (receptacle)
5556PBTL (Female terminal)
a
MD
7
MDR
8
Encoder cable 0.3m (0.98ft.)
With connector 1-172169-9
(Tyco Electronics)
b
9
P5
LG
SHD
Power supply
connector
View a
Power supply
connector
5557-06R-210
Pin
1
2
3
4
Signal
Pin
1
2
3
4
Signal
U
V
5557-04R-210
U
V
W
1
2
3
4
1
2
3
4
5
6
W
(Earth)
(Earth)
(Note)
View b
5
6
B1
B2
View b
(Note)
Note:For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
3 - 31
3. SIGNALS AND WIRING
(2) HC-SFS HC-RFS HC-UFS2000 r/min series
Servo motor side connectors
Servo motor
Electromagnetic
For power supply For encoder
brake connector
HC-SFS81(B)
The connector
for power is
shared.
CE05-2A22-
23PD-B
HC-SFS52(B) to 152(B)
HC-SFS53(B) to 153(B)
HC-SFS121(B) to 301(B)
HC-SFS202(B) to 502 (B)
HC-SFS203(B) 353(B)
CE05-2A24-
10PD-B
MS3102A10SL-
4P
CE05-2A32-
HC-SFS702(B)
17PD-B
MS3102A20-
29P
CE05-2A22-
23PD-B
HC-RFS103(B) to 203 (B)
HC-RFS353(B) 503(B)
HC-UFS72(B) 152(B)
HC-UFS202(B) to 502(B)
a
The connector
for power is
shared.
CE05-2A24-
10PD-B
Encoder connector
b
CE05-2A22-
23PD-B
c
Brake connector
Power supply connector
CE05-2A24-
10PD-B
MS3102A10SL-
4P
Power supply connector signal arrangement
CE05-2A22-23PD-B
Key
CE05-2A24-10PD-B
CE05-2A32-17PD-B
Key
Key
Pin
Signal
U
V
W
(Earth)
Pin
A
B
C
D
E
Signal
Pin
A
B
C
D
Signal
U
V
W
(Earth)
U
V
W
A
B
C
D
E
F
F
E
F
A
C
A
G
H
A
B
D
C
B
E
B
G
C
D
(Earth)
(Note) B1
(Note) B2
D
View c
View c
F
(Note) B1
(Note) B2
G
H
G
Note:For the motor with
Note:For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
Encoder connector signal arrangement
Electromagnetic brake connector signal arrangement
MS3102A20-29P
Key
MS3102A10SL-4P
Key
Pin
A
B
Signal
(Note)B1
(Note)B2
Pin
Signal
Pin
Signal
M
B
A
C
L
N
A
B
C
D
E
F
G
H
J
K
L
M
N
P
R
S
T
MD
MDR
MR
D
K
T
P
A
B
J
E
S
R
Note:For the motor with
electromagnetic brake,
supply electromagnetic
brake power (24VDC).
There is no polarity.
F
H
G
MRR
SD
View a
View b
BAT
LG
LG
P5
3 - 32
3. SIGNALS AND WIRING
3.9 Servo motor with electromagnetic brake
Configure the electromagnetic brake operation circuit so that it is activated not only
by the servo amplifier signals but also by an external forced stop (EMG).
Contacts must be open when
Circuit must be
opened during
forced stop (EMG).
servo-on (SON) is off or when a trouble (ALM)
is present when a electromagnetic brake
interlock (MBR).
Servo motor
RA EMG
24VDC
CAUTION
Electromagnetic brake
The electromagnetic brake is provided for holding the motor shaft. Do not use it for
ordinary braking.
Before performing the operation, be sure to confirm that the electromagnetic brake
operates properly.
POINT
For the power supply capacity, operation delay time and other
specifications of the electromagnetic brake, refer to the Servo Motor
Instruction Manual.
Note the following when the servo motor equipped with electromagnetic brake is used.
1) In the device setting of the MR Configurator (servo configuration software), make the
electromagnetic brake interlock (MBR) available.
2) Do not share the 24VDC interface power supply between the interface and electromagnetic brake.
Always use the power supply designed exclusively for the electromagnetic brake.
3) The brake will operate when the power (24VDC) switches off.
4) While the reset (RES) is on, the base circuit is shut off. When using the servo motor with a vertical
shaft, use the electromagnetic brake interlock (MBR).
5) Turn off the servo-on (SON) after the servo motor has stopped.
(1) Connection diagram
Servo amplifier
Servo motor
Forced
stop
RA
B1
Z
VDD
COM
MBR
RA
24VDC
B2
(2) Setting
1) In the device setting of the MR Configurator (servo configuration software), make the
electromagnetic brake interlock (MBR) available.
2) Using parameter No. 33 (electromagnetic brake sequence output), set a time delay (Tb) at servo-off
from electromagnetic brake operation to base circuit shut-off as in the timing chart shown in (3) of
this section.
3 - 33
3. SIGNALS AND WIRING
(3) Timing charts
(a) Servo-on (SON) command (from controller) ON/OFF
Tb (ms) after servo-on (SON) is switched off, servo lock is released and the servo motor coasts.
If the electromagnetic brake is made valid in the servo lock status, the brake life may be shorter.
For use in vertical lift and similar applications, therefore, set delay time (Tb) to the time which is
about equal to the electromagnetic brake operation delay time and during which the load will not
drop.
Coasting
Servo motor speed
Base circuit
0 r/min
ON
(60ms)
(80ms)
Tb
OFF
Electromagnetic
brake operation
delay time
Electromagnetic
brake interlock
(MBR)
(Note 1) ON
OFF
ON
Servo-on(RYn0)
OFF
(Note 3)
Forward rotation start
(ST1) or reverse rotation
start (ST2)
ON
OFF
Release
Activate
Electromagnetic
brake
Release delay time and external relay (Note 2)
Note 1. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
2. Electromagnetic brake is released after delaying for the release delay time of electromagnetic brake and operation time of
external circuit relay. For the release delay time of electromagnetic brake, refer to the Servo Motor Instruction Manual.
3. After the electromagnetic brake is released, turn ON the ST1 or ST2.
(b) Forced stop (EMG) ON/OFF
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
Forward
rotation
0r/min
Servo motor speed
Base circuit
Electromagnetic brake release
(180ms)
(10ms)
ON
OFF
(180ms)
(Note) ON
Electromagnetic brake
operation delay time
Electromagnetic
brake interlock (MBR)
OFF
Invalid(ON)
Valid (OFF)
Forced stop (EMG)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 34
3. SIGNALS AND WIRING
(c) Alarm occurrence
Dynamic brake
Dynamic brake
Electromagnetic brake
Forward
rotation
0r/min
Servo motor speed
Base circuit
Electromagnetic brake
(10ms)
ON
OFF
(Note) ON
Electromagnetic brake
operation delay time
Electromagnetic
brake interlock (MBR)
OFF
No (ON)
Yes (OFF)
Trouble (ALM)
Note. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
(d) Both main and control circuit power supplies off
Dynamic brake
Dynamic brake
(10ms)
(Note 1)
15 to 60ms
Electromagnetic brake
Forward
rotation
Servo motor speed
Base circuit
Electromagnetic brake
0r/min
ON
OFF
(Note 2) ON
Electromagnetic
brake interlock (MBR)
OFF
No (ON)
Yes (OFF)
ON
Electromagnetic brake
operation delay time
Trouble (ALM)
Main circuit
power
Control circuit
OFF
Note 1. Changes with the operating status.
2. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 35
3. SIGNALS AND WIRING
(e) Only main circuit power supply off (control circuit power supply remains on)
Dynamic brake
Dynamic brake
Electromagnetic brake
Electromagnetic brake
(10ms)
(Note 1)
15 or more
Forward
rotation
Servo motor speed
Base circuit
0r/min
ON
OFF
(Note 3) ON
Electromagnetic
brake interlock (MBR)
OFF
No (ON)
Yes (OFF)
ON
Electromagnetic brake
operation delay time
(Note 2)
Trouble (ALM)
Main circuit
power supply
OFF
Note 1. Changes with the operating status.
2. When the main circuit power supply is off in a motor stop status, the main circuit off warning (AL.E9) occurs and the trouble
(ALM) does not turn off.
3. ON: Electromagnetic brake is not activated.
OFF: Electromagnetic brake is activated.
3 - 36
3. SIGNALS AND WIRING
3.10 Grounding
Ground the servo amplifier and servo motor securely.
To prevent an electric shock, always connect the protective earth (PE) terminal of
the servo amplifier with the protective earth (PE) of the control box.
WARNING
The servo amplifier switches the power transistor on-off to supply power to the servo motor. Depending on
the wiring and ground cable routing, the servo amplifier may be affected by the switching noise (due to
di/dt and dv/dt) of the transistor. To prevent such a fault, refer to the following diagram and always
ground.
To conform to the EMC Directive, refer to the EMC Installation Guidelines (IB (NA) 67310).
Control box
Servo motor
NFB
MC
Servo amplifier
L1
CN2
Encoder
(Note)
Power supply
L2
L3
L11
L21
U
U
V
V
M
W
W
CN1A CN1B
Ensure to connect it to PE
terminal of the servo amplifier.
Do not connect it directly to
the protective earth of
the control panel.
Outer
box
Protective earth(PE)
Note. For 1-phase 230VAC, connect the power supply to L1 L2 and leave L3 open.
There is no L3 for 1-phase 100 to 120VAC power supply. Refer to section 1.2 for the power supply specification.
3 - 37
3. SIGNALS AND WIRING
3.11 Servo amplifier terminal block (TE2) wiring method
POINT
Refer to Table 14.1 in section 14.2.1 for the wire sizes used for wiring.
3.11.1 For the servo amplifier produced later than Jan. 2006
(1) Termination of the cables
(a) Solid wire
After the sheath has been stripped, the cable can be used as it is.
Sheath
Core
Approx. 10mm
(b) Twisted wire
1) When the wire is inserted directly
Use the cable after stripping the sheath and twisting the core. At this time, take care to
avoid a short caused by the loose wires of the core and the adjacent pole. Do not solder the
core as it may cause a contact fault. Alternatively, a bar terminal may be used to put the
wires together.
2) When the wires are put together
Using a bar terminal.
Cable Size
Bar Terminal Type
For 1 cable For 2 cables
AI-TWIN 1.5-10BK
Crimping Tool
Manufacturer
2
[mm ] AWG
1.25/1.5 16 AI1.5-10BK
2/2.5 14 AI2.5-10BU
CRIMPFOX ZA 3
Phoenix Contact
Cut the wire running out of bar terminal to less than 0.5mm.
Less than 0.5mm
When using a bar terminal for two wires, insert the wires in the direction where the
insulation sleeve does not interfere with the next pole and pressure them.
Pressure
Pressure
3 - 38
3. SIGNALS AND WIRING
(2) Termination of the cables
(a) When the wire is inserted directly
Insert the wire to the end pressing the button with a small flat blade screwdriver or the like.
Button
Small flat blade
screwdriver or the like
When removing the short-circuit bar
from across P-D, press the buttons
of P and D alternately pulling the
short-circuit bar. For the installation,
insert the bar straight to the end.
Twisted wire
(b) When the wires are put together using a bar terminal
Insert a bar terminal with the odd-shaped side of the pressured terminal on the button side.
Bar terminal for one
wire or solid wire
Bar terminal for two wires
3 - 39
3. SIGNALS AND WIRING
3.11.2 For the servo amplifier produced earlier than Dec. 2005
1) Termination of the cables
Solid wire: After the sheath has been stripped, the cable can be used as it is.
Approx. 10mm
(0.39inch)
Twisted wire: Use the cable after stripping the sheath and twisting the core. At this time, take
care to avoid a short caused by the loose wires of the core and the adjacent pole.
Do not solder the core as it may cause a contact fault. Alternatively, a bar
terminal may be used to put the wires together.
Cable size
Bar terminal type
For 1 cable For 2 cables
AI-TWIN 1.5-10BK
Manufacturer
Crimping tool
2
[mm ] AWG
1.25/1.5 16 AI1.5-10BK
2/2.5 14 AI2.5-10BU
CRIMPFOX ZA3
or
Phoenix Contact
CRIMPFOX UD 6
2) Connection
Insert the core of the cable into the opening and tighten the screw with a flat-blade screwdriver
so that the cable does not come off. (Tightening torque: 0.3 to 0.4N m (2.7 to 3.5Ib in)) Before
inserting the cable into the opening, make sure that the screw of the terminal is fully loose.
2
When using a cable of 1.5mm or less, two cables may be inserted into one opening.
3 - 40
3. SIGNALS AND WIRING
Flat-blade screwdriver
Tip thickness 0.4 to 0.6mm (0.016 to 0.024in.)
Overall width 2.5 to 3.5mm (0.098 to 0.138in.)
To loosen. To tighten.
Cable
Opening
Control circuit terminal block
Use of a flat-blade torque screwdriver is recommended to manage the screw tightening torque. The
following table indicates the recommended products of the torque screwdriver for tightening torque
management and the flat-blade bit for torque screwdriver. When managing torque with a Phillips bit,
please consult us.
Product
Torque screwdriver
Model
Manufacturer/Representative
Nakamura Seisakusho
Shiro Sangyo
N6L TDK
Bit for torque screwdriver
B-30, flat-blade, H3.5 X 73L
3 - 41
3. SIGNALS AND WIRING
3.12 Instructions for the 3M connector
When fabricating an encoder cable or the like, securely connect the shielded external conductor of the
cable to the ground plate as shown in this section and fix it to the connector shell.
External conductor
Sheath
Core
External conductor
Pull back the external conductor to cover the sheath
Sheath
Strip the sheath.
Screw
Cable
Screw
Ground plate
3 - 42
4. OPERATION
4. OPERATION
4.1 When switching power on for the first time
4.1.1 Pre-operation checks
Before starting operation, check the following.
(1) Wiring
(a) A correct power supply is connected to the power input terminals (L1, L2, L3, L11, L21) of the servo
amplifier.
(b) The servo motor power supply terminals (U, V, W) of the servo amplifier match in phase with the
power input terminals (U, V, W) of the servo motor.
(c) The servo motor power supply terminals (U, V, W) of the servo amplifier are not shorted to the
power input terminals (L1, L2, L3) of the servo motor.
(d) The earth terminal of the servo motor is connected to the PE terminal of the servo amplifier.
(e) Note the following when using the regenerative option, brake unit or power regeneration converter.
1) For the MR-J2S-350CP or less, the lead has been removed from across D-P of the control circuit
terminal block, and twisted cables are used for its wiring.
2) For the MR-J2S-500CP or more, the lead has been removed from across P-C of the servo
amplifier built-in regenerative resistor, and twisted cables are used for its wiring.
(f) When stroke end limit switches are used, the signals across LSP-SG and LSN-SG are on during
operation.
(g) 24VDC or higher voltages are not applied to the pins of connectors CN1A and CN1B.
(h) SD and SG of connectors CN1A and CN1B are not shorted.
(i) The wiring cables are free from excessive force.
(2) Environment
Signal cables and power cables are not shorted by wire offcuts, metallic dust or the like.
(3) Machine
(a) The screws in the servo motor installation part and shaft-to-machine connection are tight.
(b) The servo motor and the machine connected with the servo motor can be operated.
4 - 1
4. OPERATION
4.1.2 Startup
Do not operate the switches with wet hands. You may get an electric shock.
Before starting operation, check the parameters. Some machines may perform
WARNING
unexpected operation.
Take safety measures, e.g. provide covers, to prevent accidental contact of hands
and parts (cables, etc.) with the servo amplifier heat sink, regenerative resistor,
servo motor, etc.since they may be hot while power is on or for some time after
power-off. Their temperatures may be high and you may get burnt or a parts may
damaged.
CAUTION
During operation, never touch the rotating parts of the servo motor. Doing so can
cause injury.
Connect the servo motor with a machine after confirming that the servo motor operates properly alone.
For startup reference, a single machine structure will be described. Refer to this section and start up the
machine safely.
(1) Machine conditions
P
Reduction ratio
1/n 1/2
Servo amplifier
Ballscrew
PB 10mm(0.39inch)
PB
Position data (P) 200mm(787.40inch)
Speed (V) 2500r/min
Acceleration time constant (Ta) 200ms
Deceleration time constant (Tb) 300ms
Servo motor
HC-MFS131072pulse/rev
Ta
Tb
V
Regenerative
option
MR-RB032
Servo motor
speed
0r/min
Point table No. 1
1) Absolute position detection system used
2) Command resolution: 10 m
3) Command system: Absolute value command system
4) Electronic gear calculation
CMX(pulse)
CDV( m)
131072
131072
131072
5000
32768
1250
........................................................(4.1)
1
n
1
2
1000
10 1000
PB
CMX 32768
CDV 1250
5) For the device command method, external input signals are used by the point table selection,
forward rotation start (ST1), servo-on (SON) and other commands.
6) Point table No.1 is used to execute automatic operation once.
4 - 2
4. OPERATION
(2) Startup procedure
(a) Power on
1) Switch off the servo-on (SON).
2) When main circuit power/control circuit power is switched on, "PoS" (Current position) appears
on the servo amplifier display.
In the absolute position detection system, first power-on results in the absolute position lost
(AL.25) alarm and the servo system cannot be switched on. This is not a failure and takes place
due to the uncharged capacitor in the encoder.
The alarm can be deactivated by keeping power on for a few minutes in the alarm status and
then switching power off once and on again.
Also in the absolute position detection system, if power is switched on at the servo motor speed
of 500r/min or higher, position mismatch may occur due to external force or the like. Power must
therefore be switched on when the servo motor is at a stop.
(b) Test operation
Using jog operation in the "test operation mode" of the MR Configurator (servo configuration
software), confirm that the servo motor operates at the slowest speed. (Refer to section 6.7.1, 7.9.2)
(c) Parameter setting
Set the parameters according to the structure and specifications of the machine. Refer to chapter 5
for the parameter definitions and to sections 6.4 and 7.6 for the setting method.
Parameter
Name
Setting
Description
20
Command system, regenerative
option selection
Absolute value command system.
MR-RB032 regenerative option is used.
No.0
10
When forward rotation start (ST1) is
valid, address is incremented in CCW
direction.
No.1
No.2
Feeding function selection
Function selection 1
Since command resolution is 10 times,
feed length multiplication factor of 10
times is selected.
1
Absolute position detection system.
No.4
No.5
Electronic gear numerator (CMX)
Electronic gear denominator (CDV)
32768
1250
From calculation result of formula (4.1)
From calculation result of formula (4.1)
After setting the above parameters, switch power off once. Then switch power on again to make the
set parameter values valid.
(d) Point table setting
Set the point table according to the operation pattern. Refer to section 4.2 for the point table
definitions and to sections 6.5 and 7.5 for the setting method.
Position data
Servo motor
Acceleration time
constant [ms]
Deceleration time
constant [ms]
Auxiliary
function
Dwell [ms]
[
10STM m]
speed [r/min]
20000
2500
200
300
0
0
(e) Servo-on
Switch the servo-on in the following procedure.
1) Switch on main circuit/control circuit power.
2) Switch on the servo-on (SON).
When placed in the servo-on status, the servo amplifier is ready to operate and the servo motor is
locked. By using the sequence in the diagnostic mode in section 7.3, the ready status can be shown
on the servo amplifier display. In the operation-ready status, the following screen appears.
4 - 3
4. OPERATION
(f) Home position return
Perform home position return as required. Refer to section 4.4 for home position return types. A
parameter setting example for dog type home position return is given here.
Parameter
Name
Setting
Description
000
Dog type home position return is selected.
Home position return is started in address
incremented direction.
No.8
Home position return type
Proximity dog (DOG) is valid when DOG-
SG are opened.
No.9
No.10
No.11
Home position return speed
Creep speed
1000
10
Motion is made up to proximity dog at 1000r/min.
Motion is made up to home position at 10r/min.
No home position shift
Home position shift distance
0
Use to set the current position on completion of home
position return.
No.42
No.43
Home position return position data
Moving distance after proximity dog
Not used in dog type home position return.
After setting the above parameters, switch power off once. Then switch power on again to make the
set parameter values valid.
Set the input signals as listed below and switch on the forward rotation start (ST1) to execute
home position return.
Device name
Automatic/manual selection
Point table No. selection 1
Point table No. selection 2
Forward rotation stroke end
Reverse rotation stroke end
Servo-on
Symbol
MD0
DI0
ON/OFF
Description
ON
Home position return mode is selected.
OFF
OFF
ON
DI1
LSP
CCW rotation side limit switch is turned on.
CW rotation side limit switch is turned on.
Servo is switched on.
LSN
SON
ON
ON
(g) Automatic operation
Set the input signals as listed below and switch on the forward rotation start (ST1) to execute
automatic operation in accordance with point table No.1.
Device name
Automatic/manual selection
Servo-on
Symbol
MD0
SON
LSP
ON/OFF
Description
ON
ON
Automatic operation mode is selected.
Servo is switched on.
Forward rotation stroke end
Reverse rotation stroke end
Point table No. selection 1
Point table No. selection 2
ON
CCW rotation side limit switch is turned on.
CW rotation side limit switch is turned on.
LSN
DI0
ON
ON
Point table No.1 is selected.
DI1
OFF
(h) Stop
In any of the following statuses, the servo amplifier interrupts and stops the operation of the servo
motor.
When the servo motor used is equipped with an electromagnetic brake, refer to section 3.9 (3). Note
that forward rotation stroke end (LSP), reverse rotation stroke end (LSN) off has the same
stopping pattern as described below.
1) Servo-on (SON) OFF
The base circuit is shut off and the servo motor coasts.
2) Alarm occurrence
When an alarm occurs, the base circuit is shut off and the dynamic brake is operated to bring the
servo motor to a sudden stop.
3) Forced stop (EMG) OFF
The base circuit is shut off and the dynamic brake is operated to bring the servo motor to a
sudden stop. Servo forced warning (AL.E6) occurs.
4) Forward rotation stroke end (LSP), reverse rotation stroke end (LSN) OFF
The droop pulse value is erased and the servo motor is stopped and servo-locked. It can be run in
the opposite direction.
4 - 4
4. OPERATION
4.2 Automatic operation mode
4.2.1 What is automatic operation mode?
(1) Command system
After selection of preset point tables using the input signals or communication, operation is started by
the forward rotation start (ST1) or reverse rotation start (ST2). Automatic operation has the absolute
value command system, incremental value command system and absolute value
command/incremental value command specifying system.
(a) Absolute value command system
As position data, set the target address to be reached.
Setting range: 999999 to 999999 [ 10STM m] (STM feed length multiplication parameter No.1)
999999
999999
Position data setting range
10STM m]
[
(b) Incremental value command system
As position data, set the moving distance from the current address to the target address.
Setting range: 0 to 999999 [ 10STM m] (STM feed length multiplication parameter No.1)
Current address
Target address
Position data |target address - current address|
(c) Absolute value command/incremental value command specifying system
You can set the absolute value address or incremental value address to each point table as position
data. After the axis has been positioned at the target address, it can be moved a given distance.
4 - 5
4. OPERATION
(2) Point table
(a) Point table setting
Up to 15 point tables may be set. To use point table No.s 4 to 31, however, the point table No.
selection 3 (DI2), point table No. selection 4 (DI3) and point table No. selection 5 (DI4) should be
made valid in "I/O Devices" on the MR Configurator (servo configuration software).
Set the point tables using the MR Configurator (servo configuration software) or the servo
amplifier operation section.
The following table lists what to set. Refer to section 4.2.2, section 4.2.3 and section 4.2.4 for details
of the settings.
Name
Description
Position data
Set the position data for movement.
Servo motor speed
Acceleration time constant
Deceleration time constant
Dwell
Set the command speed of the servo motor for execution of positioning.
Set the acceleration time constant.
Set the deceleration time constant.
Set the waiting time when performing automatic continuous operation.
Set when performing automatic continuous operation.
Auxiliary function
(b) Selection of point table
Using the input signal or communication function, select the point table No. with a command from
the command device (controller) such as a personal computer.
The following table lists the point table No. selected in response to the input signals/commands.
Note that when the input signals are used, the point tables used as standard are No.1 to 3. To use
No.4 to 31, the point table No. selection 3 (DI2), point table No. selection 4 (DI3) and point table
No. selection 5 (DI4) should be made valid in "I/O Devices" (Refer to chapter 6) on the MR
Configurator (servo configuration software).
When the communication function is used to select the point tables, refer to chapter 15 for details
of the command transmission method, etc.
4 - 6
4. OPERATION
(Note 2) Input signals
(Note 1) DI4 (Note 1) DI3 (Note 1) DI2
Selected point table No.
DI1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
DI0
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0 (Manual home position return mode)
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Note 1. Make signals valid in "I/O Devices" on the MR Configurator (servo configuration software).
2. "1": short
"0": open
4 - 7
4. OPERATION
4.2.2 Absolute value command system
(1) Point table
Set the point table values using the MR Configurator (servo configuration software) or from the
operating section.
Set the position data, motor speed, acceleration time constant, deceleration time constant, dwell and
auxiliary function to the point table. The following table gives a setting example.
Name
Setting range
Unit
Description
Set the target address (absolute value).
This value can also be set using the teaching function. (Refer to section
10STM m] 7.10.)
The unit can be changed using feed length multiplication factor selection of
Position data
999999 to 999999
[
parameter No. 1.
Set the command speed of the servo motor for execution of positioning.
The setting should be equal to or less than the instantaneous permissible
speed of the servo motor.
Motor speed
0 to permissible speed
r/min
Acceleration
time constant
Deceleration
time constant
Set the acceleration time constant.
0 to 20000
0 to 20000
ms
ms
Set the time until the rated speed of the servo motor is reached.
Set the deceleration time constant.
Set the time until the servo motor running at rated speed comes to a stop.
Set the dwell.
Set "0" in the auxiliary function to make the dwell invalid.
Set "1" in the auxiliary function and 0 in the dwell to perform continuous
operation.
Dwell
0 to 20000
ms
When the dwell is set, the position command of the selected point table is
completed, and after the set dwell has elapsed, the position command of the
next point table is started.
Set the auxiliary function.
0: Automatic operation is performed in accordance with a single point table
chosen.
1: Operation is performed in accordance with consecutive point tables
without a stop.
Auxiliary
function
0
1
When a different rotation direction is set, smoothing zero (command
output) is confirmed and the rotation direction is then reversed.
Setting "1" in point table No.31 results in an error.
For full information, refer to section 4.2.6.
(2) Parameter setting
Set the following parameters to perform automatic operation.
(a) Command mode selection (parameter No.0)
Select the absolute value command system.
Parameter No. 0
0
Absolute value command system
4 - 8
4. OPERATION
(b) ST1 coordinate system selection (parameter No.1)
Choose the servo motor rotation direction at the time when the forward rotation start (ST1) is
switched on.
Servo motor rotation direction
Parameter No. 1 setting
when forward rotation start (ST1) is switched on
CCW rotation with position data
0
CW rotation with
position data
CW rotation with position data
1
CCW rotation with
position data
CCW
CW
(c) Feed length multiplication selection (parameter No.1)
Set the unit multiplication factor (STM) of position data.
Parameter No.1 setting
Position data input range [mm]
0
1
2
3
999.999 to 999.999
9999.99 to 9999.99
99999.9 to 99999.9
999999 to 999999
(3) Operation
Choose the point table using DI0 to DI4 and short ST1-SG to perform positioning to the position data
under the conditions of the preset speed, acceleration time constant and deceleration time constant. At
this time, reverse rotation start (ST2) is invalid.
Item
Setting method
Description
Automatic operation mode selection
Automatic/manual selection (MD0)
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Point table No. selection 3 (DI2)
Point table No. selection 4 (DI3)
Point table No. selection 5 (DI4)
Forward rotation start (ST1)
MD0 is turned on.
Point table selection
Start
Refer to section 4.2.1, (2).
Short ST1-SG (ON) to start.
4 - 9
4. OPERATION
4.2.3 Incremental value command system
(1) Point table
Set the point table values using the MR Configurator (servo configuration software) or from the
operating section.
Set the position data, motor speed, acceleration time constant, deceleration time constant, dwell and
auxiliary function to the point table. The following table gives a setting example.
Name
Setting range
Unit
Description
Set the moving distance.
The teaching function is unusable.
Position data 0 to 999999
Servo motor
10STM
m
The unit can be changed using feed length multiplication factor selection of
parameter No. 1.
Set the command speed of the servo motor for execution of positioning.
The setting should be equal to or less than the instantaneous permissible
speed of the servo motor.
0 to permissible speed
r/min
speed
Acceleration
time constant
Deceleration
time constant
Set the acceleration time constant.
0 to 20000
0 to 20000
ms
ms
Set the time until the rated speed of the servo motor is reached.
Set the deceleration time constant.
Set the time until the servo motor running at rated speed comes to a stop.
Set the dwell.
Set "0" in the auxiliary function to make the dwell invalid.
Set "1" in the auxiliary function and 0 in the dwell to perform continuous
operation.
Dwell
0 to 20000
ms
When the dwell is set, the position command of the selected point table is
completed, and after the set dwell has elapsed, the position command of the
next point table is started.
Set the auxiliary function.
0: Automatic operation is performed in accordance with a single point table
chosen.
Auxiliary
function
0
1
1: Operation is performed in accordance with consecutive point tables
without a stop.
Setting "1" in point table No.31 results in an error.
For full information, refer to section 4.2.6.
(2) Parameter setting
Set the following parameters to perform automatic operation.
(a) Command mode selection (parameter No.0)
Select the incremental value command system.
Parameter No. 0
1
Incremental value command system
4 - 10
4. OPERATION
(b) ST1 coordinate system selection (parameter No.1)
Choose the servo motor rotation direction at the time when the forward rotation start (ST1) signal
or reverse rotation start (ST2) signal is switched on.
Servo motor rotation direction
Parameter No.1 setting
Forward rotation start (ST1) ON
CCW rotation (address incremented)
CW rotation (address incremented)
Reverse rotation start (ST2) ON
CW rotation (address decremented)
CCW rotation (address decremented)
0
1
ST1:ON
CCW
ST2:ON
CCW
CW
ST1:ON
Parameter No. 1
CW
ST2:ON
Parameter No. 1
0
1
(c) Feed length multiplication selection (parameter No.1) Set the unit multiplication factor (STM) of
position data.
Parameter No.1 setting
Position data input range [mm]
0
1
2
3
0 to 999.999
0 to 9999.99
0 to 99999.9
0 to 999999
(3) Operation
Choose the point table using DI0 to DI4 and short ST1-SG to make a motion in the forward rotation
direction over the distance of the position data under the conditions of the preset speed, acceleration
time constant and deceleration time constant. Short ST2-SG to make a motion in the reverse rotation
direction in accordance with the point table settings.
Item
Setting method
Description
Automatic operation mode selection
Automatic/manual selection (MD0)
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Point table No. selection 3 (DI2)
Point table No. selection 4 (DI3)
Point table No. selection 5 (DI4)
MD0 is turned on.
Point table selection
Refer to section 4.2.1, (2).
Short ST1-SG (ON) to start motion
in forward rotation direction.
Forward rotation start (ST1)
Reverse rotation start (ST2)
Start
Short ST2-SG (ON) to start motion
in reverse rotation direction.
4 - 11
4. OPERATION
4.2.4 Absolute value command/incremental value command specifying system
This system is an auxiliary function for point tables to use them by specifying the absolute value
command and incremental value command.
(1) Point table
Set each value of point tables by using MR Configurator (Setup software) or operation section.
Set to point tables the following, "Position data", "Servo motor speed", "Acceleration time constant",
"Deceleration time constant", "Dwell time" and "Auxiliary function".
To specify the command system, set "Auxiliary function" as shown below.
For absolute value command system, set "0" or "1".
For incremental value command system, set "2" or "3".
Name
Setting range
Unit
Description
(1) When this point table is used in an absolute value command system
Set the target address (absolute value).
This value can also be set using the teaching function. (Refer to section
7.10.)
(2) When this point table is used in an incremental value command system
Set the moving distance. A " " sign indicates a reverse rotation
command.
10STM
m
Position data
999999 to 999999
The teaching function is unusable.
Set the command speed of the servo motor for execution of positioning.
The setting should be equal to or less than the instantaneous permissible
speed of the servo motor.
Servo motor
speed
0 to permissible speed
r/min
Acceleration
time constant
Deceleration
time constant
Set the acceleration time constant.
Set the time until the rated speed of the servo motor is reached.
Set the deceleration time constant.
Set the time until the servo motor running at rated speed comes to a stop.
Set the dwell.
0 to 20000
0 to 20000
ms
ms
Set "0" or "2" in the auxiliary function to make the dwell invalid.
Set "1" or "3" in the auxiliary function and 0 in the dwell to perform
continuous operation.
Dwell
0 to 20000
ms
When the dwell is set, the position command of the selected point table is
completed, and after the set dwell has elapsed, the position command of the
next point table is started.
Set the auxiliary function.
(1) When this point table is used in an absolute value command system
0: Automatic operation is performed in accordance with a single point table
chosen.
1: Operation is performed in accordance with consecutive point tables
without a stop.
(2) When this point table is used in an incremental value command system
2: Automatic operation is performed in accordance with a single point table
chosen.
Auxiliary
function
0 to 3
3: Operation is performed in accordance with consecutive point tables
without a stop.
When a different rotation direction is set, smoothing zero (command
output) is confirmed and the rotation direction is then reversed.
Setting "1" or "3" in point table No.31 results in an error.
For full information, refer to section 4.2.6.
4 - 12
4. OPERATION
(2) Parameter setting
Set the following parameters to perform automatic operation.
(a) Command mode selection (parameter No.0)
Choose the absolute value command/incremental value command specifying system.
Parameter No. 0
2
Absolute value command/incremental value command specifying system
(b) ST1 coordinate system selection (parameter No.1)
Choose the servo motor rotation direction at the time when the forward rotation start (ST1) is
switched on.
Servo motor rotation direction
Parameter No. 1 setting
when forward rotation start (ST1) is switched on
CCW rotation with position data
0
CW rotation with
position data
CW rotation with position data
1
CCW rotation with
position data
CCW
CW
(c) Feed length multiplication selection (parameter No.1) Set the unit multiplication factor (STM) of
position data.
Parameter No.1 setting
Position data input range [mm]
0
1
2
3
0 to 999.999
0 to 9999.99
0 to 99999.9
0 to 999999
(3) Operation
Choose the point table using DI0 to DI4 and short ST1-SG to perform positioning to the position data
under the conditions of the preset speed, acceleration time constant and deceleration time constant. At
this time, reverse rotation start (ST2) is invalid.
Item
Setting method
Description
Automatic operation mode selection
Automatic/manual selection (MD0)
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Point table No. selection 3 (DI2)
Point table No. selection 4 (DI3)
Point table No. selection 5 (DI4)
Forward rotation start (ST1)
MD0 is turned on.
Point table selection
Start
Refer to section 4.2.1, (2).
Short ST1-SG (ON) to start.
4 - 13
4. OPERATION
4.2.5 Automatic operation timing chart
The timing chart is shown below.
ON
OF
ON
OF
ON
OF
ON
OF
Automatic/manual
selection (MD0)
Servo-on (SON)
(Note 2)
3ms or more
Forward rotation
start (ST1)
5ms or more
Reverse rotation
start (ST2) (Note 1)
3ms or more
5ms or more
2
1
Point table No.
3ms or less
Forward
rotation
0r/min
Point table No. 1
Servo motor speed
Reverse
Point table No. 2
rotation
ON
OF
ON
OF
ON
OF
In position (INP)
Rough match (CPO)
Movement finish
(MEND)
Point No. output
(PT0 to PT4)
1
2
ON
OF
ON
OF
Ready (RD)
Trouble (ALM)
Note 1: Reverse rotation start (ST2) is invalid in the absolute value command system and absolute value command/incremental
value command specifying system.
2: External input signal detection delays by the input filter setting time of parameter No. 2. Also, make up a sequence
that will change the point table selection earlier by the time that takes into account the output signal sequence from
the controller and the variation of a signal change due to the hardware.
4 - 14
4. OPERATION
4.2.6 Automatic continuous operation
(1) What is automatic continuous operation?
By merely choosing one point table and making a start (ST1 or ST2), operation can be performed in
accordance with the point tables having consecutive numbers.
Automatic operation is available in two types: varied speed operation and automatic continuous
positioning operation.
Either type may be selected as follows.
(a) In absolute value command system or incremental value command system
Point table setting
Dwell
0
Auxiliary function
Speed changing operation
Automatic continuous
operation
1
1
Automatic continuous
positioning operation
1 or more
(b) In absolute value command /incremental value command specifying system
Point table setting
Auxiliary function
Dwell
When position data is
absolute value
When position data is
incremental value
Speed changing operation
Automatic continuous
operation
0
1
1
3
3
Automatic continuous
positioning operation
1 or more
(2) Varied speed operation
Speed during positioning operation can be changed by setting the auxiliary function of the point table.
Use the number of point tables equal to the number of speeds to be set.
By setting "1" to the auxiliary function, operation is performed at the speed set in the next point table
during positioning. The position data valid at this time is the data selected at start and the
acceleration and deceleration time constants of the subsequent point tables are made invalid.
By setting "1" to the auxiliary function of up to point table No.30, operation can be performed at a
maximum of 31 speeds. Set "0" to the auxiliary function of the last point table.
When performing varied speed operation, always set "0" to the dwell. If "1" or more is set, automatic
continuous positioning operation is made valid.
The following table gives a setting example.
Point table No.
Dwell [ms] (Note 1)
Auxiliary function
Variable speed operation
1
0
0
0
0
0
0
0
1
Consecutive point table data
2
1
3
0 (Note 2)
4
1
5
1
1
Consecutive point table data
6
7
0 (Note 2)
Note 1. Always set "0".
2. Always set "0" or "2" to the auxiliary function of the last point table among the consecutive point tables.
4 - 15
4. OPERATION
(a) Absolute value command system
1) Positioning in single direction
The position data (addresses) of the midway point tables are not used for positioning and speed
is changed continuously to move to the set address in the last point table.
The operation example given below assumes that the set values are as indicated in the following
table.
Point table
No.
Position data
Servo motor
speed [r/min]
Acceleration time constant
[ms]
Deceleration time constant
[ms]
Dwell [ms]
(Note 1)
Auxiliary
function
[
10STM m]
1
2
3
5.00
3000
2000
1000
100
150
0
0
0
1
1
10.00
Invalid
Invalid
Invalid
Invalid
15.00
0 (Note 2)
Note 1. Always set "0".
2. Always set "0" to the auxiliary function of the last point table among the consecutive point tables.
Acceleration time constant
Deceleration time constant
of point table No. 1 (100)
of point table No. 1 (150)
Forward
rotation
Speed
(3000)
Servo motor speed
Speed
(2000)
Speed (1000)
0
Position address
0
5.00
10.00
15.00
Selected point table No.
1
ON
Forward rotation start
(ST1)
OFF
Point No. out put
(PT0 to PT4)
1
4 - 16
4. OPERATION
2) Positioning that reverses the direction midway
The position data (addresses) of the midway point tables are used for positioning and the
direction is reversed to reach the positioning address set in the last point table.
The operation example given below assumes that the set values are as indicated in the following
table.
Point table
No.
Position data
Servo motor
speed [r/min]
Acceleration time constant
[ms]
Deceleration time constant
[ms]
Dwell [ms]
(Note 1)
Auxiliary
function
[
10STM m]
1
2
10.00
3000
2000
100
150
0
0
1
5.00
Invalid
Invalid
0 (Note 2)
Note 1. Always set "0".
2. Always set "0" to the auxiliary function of the last point table among the consecutive point tables.
Deceleration time constant
of point table No. 1 (150)
Acceleration time constant
of point table No. 1 (100)
Speed
(3000)
Forward
rotation
0
Servo motor speed
Speed
(2000)
Reverse
rotation
Position address
0
5.00
10.00
1
Selected point table No.
ON
Forward rotation start
(ST1)
OFF
Point No. out put
(PT0 to PT4)
1
4 - 17
4. OPERATION
(b) Incremental value command system
The position data of the incremental value command system is the sum of the position data of the
consecutive point tables.
The operation example given below assumes that the set values are as indicated in the following
table.
Point table
No.
Position data
Servo motor
speed [r/min]
Acceleration time constant
[ms]
Deceleration time constant
[ms]
Dwell [ms]
(Note 1)
Auxiliary
function
[
10STM m]
1
2
3
5.00
3000
2000
1000
100
150
0
0
0
1
1
6.00
Invalid
Invalid
Invalid
Invalid
3.00
0 (Note 2)
Note 1. Always set "0".
2. Always set "0" to the auxiliary function of the last point table among the consecutive point tables.
Acceleration time constant
Deceleration time constant
of point table No. 1 (150)
of point table No. 1 (100)
Forward
Speed
(3000)
Servo motor speed
Speed
(2000)
rotation
Speed
(1000)
0
5.00
6.00
3.00
Position address
0
5.00
11.00
14.00
Selected point table No.
1
(Note)
ON
Forward rotation start (ST1)
OFF
Point No. out put
(PT0 to PT4)
1
Note. Turning on Reverse rotation start (ST2) starts positioning in the reverse rotation direction.
4 - 18
4. OPERATION
(c) Absolute value command/incremental value command specifying system
This system is an auxiliary function for point tables to perform automatic operation by specifying
the absolute value command or incremental value command.
1) Positioning in single direction
The operation example given below assumes that the set values are as indicated in the following
table. Here, the point table No. 1 uses the absolute value command system, the point table No. 2
the incremental value command system, the point table No. 3 the absolute value system, and the
point table No. 4 the incremental value command system.
Point table
No.
Position data
Servo motor
speed [r/min]
Acceleration time constant
[ms]
Deceleration time constant
[ms]
Dwell [ms]
(Note 1)
Auxiliary
function
[
10STM m]
1
2
3
4
5.00
3000
2000
1000
500
100
150
0
0
0
0
1
3.00
Invalid
Invalid
Invalid
Invalid
Invalid
Invalid
3
1
10.00
6.00
0 (Note 2)
Note 1. Always set "0".
2. Always set "0" or "2" to the auxiliary function of the last point table among the consecutive point tables.
0: When point table is used in absolute value command system
1: When point table is used in incremental value command system
Acceleration time constant
Deceleration time constant
of point table No. 1 (100)
of point table No. 1 (150)
Speed
(1000)
Forward
rotation
Speed
(3000)
Servo motor speed
Speed
(2000)
Speed (500)
0
3.00
6.00
Position address
0
5.00
8.00
1
10.00
16.00
Selected point table No.
ON
Forward rotation start
(ST1)
OFF
Point No. out put
(PT0 to PT4)
1
4 - 19
4. OPERATION
2) Positioning that reverses the direction midway
The operation example given below assumes that the set values are as indicated in the following
table. Here, the point table No. 1 uses the absolute value command system, the point table No. 2
the incremental value command system, and the point table No. 3 the absolute value system.
Point table
No.
Position data
Servo motor
speed [r/min]
Acceleration time constant
[ms]
Deceleration time constant
[ms]
Dwell [ms]
(Note 1)
Auxiliary
function
[
10STM m]
1
2
3
5.00
3000
2000
1000
100
150
0
0
0
1
1
7.00
Invalid
Invalid
Invalid
Invalid
8.00
0 (Note 2)
Note 1. Always set "0".
2. Always set "0" or "2" to the auxiliary function of the last point table among the consecutive point tables.
0: When point table is used in absolute value command system
1: When point table is used in incremental value command system
Acceleration time constant
Deceleration time constant
of point table No. 1 (100)
of point table No. 1 (150)
Speed
Speed
(3000)
Forward
rotation
(2000)
Servo motor speed
0
Speed (1000)
Reverse
rotation
Acceleration time constant
of point table No. 1 (100)
7.00
8.00
Position address
0
5.00
12.00
Selected point table No.
1
ON
Forward rotation start
(ST1)
OFF
Point No. out put
(PT0 to PT4)
1
4 - 20
4. OPERATION
(4) Temporary stop/restart
When STP-SG are connected during automatic operation, the motor is decelerated to a temporary stop
at the deceleration time constant in the point table being executed. When STP-SG are connected
again, the remaining distance is executed.
If the forward/reverse rotation start signal is ignored if it is switched on during a temporary stop.
The remaining moving distance is cleared when the operation mode is changed from the automatic
mode to the manual mode during a temporary stop.
The temporary stop/restart input is ignored during zeroing and jog operation.
(a) When the servo motor is rotating
Acceleration time constant
of point table No. n
Deceleration time constant
of point table No. n
Remaining
distance
Servo motor speed
0
No. n
Point table
Forward rotation start (ST1)
or reverse rotation start (ST2)
ON
OFF
ON
OFF
Temporary stop/Restart (STP)
ON
OFF
Temporary stop (PUS)
Rough match (CPO)
ON
OFF
ON
OFF
In position (INP)
ON
OFF
Movement finish (MEND)
Point No. out put
(PT0 to PT4)
No. n
(b) During dwell
Point table No. n
Point table No. n
1
Dwell ta tb
tb
ta
Servo motor speed
0
Point table
No. n
Forward rotation start (ST1)
or reverse rotation start (ST2) OFF
ON
ON
Temporary stop/Restart (STP)
OFF
ON
Temporary stop (PUS)
OFF
ON
Rough match (CPO)
OFF
ON
OFF
In position (INP)
ON
Movement finish (MEND)
OFF
Point No. out put
(PT0 to PT4)
No. n
4 - 21
4. OPERATION
4.3 Manual operation mode
For machine adjustment, home position matching, etc., jog operation or a manual pulse generator may be
used to make a motion to any position.
4.3.1 Jog operation
(1) Setting
Set the input signal and parameters as follows according to the purpose of use. In this case, the point
table No. selection 1 to 5 (DI0 to DI4) are invalid.
Item
Manual operation mode selection
Servo motor rotation direction
Jog speed
Setting method
Automatic/manual selection (MD0)
Parameter No.1
Description
Open MD0-SG (OFF).
Refer to (2) of this section.
Parameter No.13
Set the speed of the servo motor.
Use the acceleration/deceleration
time constants in point table No.1.
Acceleration/deceleration time constant
Point table No.1
(2) Servo motor rotation direction
Servo motor rotation direction
Parameter No. 1 setting
Forward rotation start (ST1) ON
CCW rotation
Reverse rotation start (ST2) ON
0
1
CW rotation
CW rotation
CCW rotation
ST1:ON
CCW
ST2:ON
CCW
CW
ST1:ON
Parameter No. 1
CW
ST2:ON
Parameter No. 1
0
1
(3) Operation
By shorting ST1-SG, operation is performed under the conditions of the jog speed set in the parameter
and the acceleration and deceleration time constants in set point table No.1. For the rotation direction,
refer to (2) of this section. By shorting ST2-SG, the servo motor rotates in the reverse direction to
forward rotation start (ST1).
4 - 22
4. OPERATION
(4) Timing chart
ON
Servo-on (SON)
OFF
ON
80ms
Ready (RD)
OFF
ON
Trouble (ALM)
OFF
Automatic/manual
selection (MD0)
ON
OFF
ON
Movement finish
(MEND)
OFF
ON
Rough match (CPO)
OFF
Forward
rotation
0r/min
Servo motor speed
Reverse
rotation
ON
Forward rotation start
(ST1)
Forward rotation jog
OFF
ON
Reverse rotation start
(ST2)
Reverse rotation jog
OFF
4 - 23
4. OPERATION
4.3.2 Manual pulse generator operation
(1) Setting
Set the input signal and parameters as follows according to the purpose of use. In this case, the point
table No. selection 1 to 5 (DI0 to DI4) are invalid.
Item
Setting method
Description
Manual operation mode selection
Automatic/manual selection (MD0)
Open MD0-SG (OFF).
Set the multiplication ratio of servo
motor rotation to the pulses generated by
the manual pulse generator.
For more information, refer to (3) of this
section.
Manual pulse generator
multiplication
Parameter No.1
Parameter No.1
Servo motor rotation direction
Refer to (2) of this section.
(2) Servo motor rotation direction
Servo motor rotation direction
Parameter No. 1 setting
Manual pulse generator: forward rotation
CCW rotation
Manual pulse generator: reverse rotation
0
1
CW rotation
CW rotation
CCW rotation
CCW
CW
Forward rotation
(3) Manual pulse generator multiplication
(a) Using the parameter for setting
Use parameter No.1 to set the multiplication ratio of the servo motor rotation to the manual pulse
generator rotation.
Multiplication ratio of servo motor rotation to manual
Parameter No. 1 setting
Moving distance
pulse generator rotation
1 time
0
1
2
1[ m]
10[ m]
100[ m]
10 times
100 times
4 - 24
4. OPERATION
(b) Using the input signals for setting
Set the pulse generator multiplication 1 (TP0) and pulse generator multiplication 2 (TP1) to the
input signals in "Device setting" on the MR Configurator (servo configuration software) (refer to
chapter 6).
(Note) Pulse generator
multiplication 2
(Note) Pulse generator
multiplication 1
Multiplication ratio of servo motor
rotation to manual pulse generator
rotation
Moving distance
(across TP1)
(across TP0)
0
0
1
1
0
1
0
1
Parameter No.1 setting valid
1 time
10 times
100 times
1[ m]
10[ m]
100[ m]
Note. 0: Open across TP1/TP0-SG
1: Shorted across TP1/TP0-SG
(4) Operation
Turn the manual pulse generator to rotate the servo motor. For the rotation direction of servo motor,
refer to (2) of this section.
4 - 25
4. OPERATION
4.4 Manual home position return mode
4.4.1 Outline of home position return
Home position return is performed to match the command coordinates with the machine coordinates. In
the incremental system, home position return is required every time input power is switched on. In the
absolute position detection system, once home position return is done at the time of installation, the
current position is retained if power is switched off. Hence, home position return is not required when
power is switched on again.
This servo amplifier has the home position return methods given in this section. Choose the most
appropriate method for your machine structure and application.
This servo amplifier has the home position return automatic return function which executes home
position return by making an automatic return to a proper position if the machine has stopped beyond or
at the proximity dog. Manual motion by jog operation or the like is not required.
(1) Manual home position return types
Choose the optimum home position return according to the machine type, etc.
Type
Home position return method
Features
General home position return method using a
proximity dog.
Repeatability of home position return is
excellent.
The machine is less burdened.
Used when the width of the proximity dog can
be set greater than the deceleration distance
of the servo motor.
With deceleration started at the front end of a
proximity dog, the position where the first
Z-phase signal is given past the rear end of the dog or
a motion has been made over the home position shift
distance starting from the Z-phase signal is defined as
a home position.(Note)
Dog type home position
return
With deceleration started at the front end of a
proximity dog, the position where the first Z-phase
signal is given after advancement over the preset
moving distance after the proximity dog or a motion
has been made over the home position shift distance
starting from the Z-phase signal is defined as a home
position.
Home position return method using a
proximity dog.
Used when it is desired to minimize the length
of the proximity dog.
Count type home position
return
Data setting type home
position return
The position reached after any automatic motion is
defined as a home position.
No proximity dog required.
Since the machine part collides with the
machine be fully lowered.
The machine and stopper strength must be
increased.
The position where the machine stops when its part is
pressed against a machine stopper is defined as a
home position.
Stopper type home
position return
Home position ignorance
(Servo-on position as
home position)
The position where servo is switched on is defined as
a home position.
The position where the axis, which had started
decelerating at the front end of a proximity dog, has
moved the after-proximity dog moving distance and
home position shift distance after it passed the rear
end is defined as a home position.
The Z-phase signal is not needed.
The Z-phase signal is not needed.
Dog type rear end
reference
The position where the axis, which had started
decelerating at the front end of a proximity dog, has
moved the after-proximity dog moving distance and
home position shift distance is defined as a home
position.
Count type front end
reference
The position where the first Z-phase signal is issued
after detection of the proximity dog front end is
defined as a home position.
Dog cradle type
Note. The Z-phase signal is a signal recognized in the servo amplifier once per servo motor revolution and cannot be used as an output
signal.
4 - 26
4. OPERATION
(2) Home position return parameter
When performing home position return, set parameter No.8 as follows.
Parameter No. 8
0
Home position return method························································1)
0: Dog type
1: Count type
2: Data setting type
3: Stopper type
4: Home position ignorance (Servo-on position as home position)
5: Dog type rear end reference
6: Count type front end reference
7: Dog cradle type
Home position return direction ······················································2)
0: Address increment direction
1: Address decrement direction
Proximity dog input polarity ·····································3)
0: Dog is detected when DOG-SG are opened.
1: Dog is detected when DOG-SG are shorted.
1) Choose the home position return method.
2) Choose the starting direction of home position return. Set "0" to start home position return in the
direction in which the address is incremented from the current position, or "1" to start home
position return in the direction in which the address is decremented.
3) Choose the polarity at which the proximity dog is detected. Set "0" to detect the dog when the
proximity dog device (across DOG-SG) is opened, or "1" to detect the dog when the device is shorted.
(3) Instructions
1) Before starting home position return, always make sure that the limit switch operates.
2) Confirm the home position return direction. Incorrect setting will cause the machine to run
reversely.
3) Confirm the proximity dog input polarity. Otherwise, misoperation can occur.
4 - 27
4. OPERATION
4.4.2 Dog type home position return
A home position return method using a proximity dog. With deceleration started at the front end of the
proximity dog, the position where the first Z-phase signal is given past the rear end of the dog or a motion
has been made over the home position shift distance starting from the Z-phase signal is defined as a home
position.
(1) Signals, parameters
Set the input signals and parameters as follows.
Item
Device/Parameter used
Automatic/manual selection (MD0)
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Description
Short MD0-SG (ON).
Manual home position return
mode selection
Open DI0-SG (OFF).
Open DI1-SG (OFF).
0 :Dog type home position return is
Dog type home position return
Home position return direction
Dog input polarity
Parameter No.8
Parameter No.8
Parameter No.8
selected.
Refer to section 4.4.1 (2) and choose home
position return direction.
Refer to section 4.4.1 (2) and choose dog
input polarity.
Home position return speed
Creep speed
Parameter No.9
Parameter No.10
Set speed until detection of dog.
Set speed after detection of dog.
Set when shifting the home position
starting at the first Z-phase signal after
passage of proximity dog rear end.
Home position shift distance
Parameter No.11
Home position return
acceleration/deceleration time
constants
Use the acceleration/deceleration time
constants of point table No.1.
Point table No.1
Parameter No.42
Home position return position
data
Use to set the current position on
completion of home position return.
(2) Length of proximity dog
To ensure that the Z-phase signal of the servo motor is generated during detection of the proximity
dog (DOG), the proximity dog should have the length which satisfies formulas (4.2) and (4.3).
V
60
td
2
.............................................................................. (4.2)
L1
L
1
: Proximity dog length [mm]
V
: Home position return speed [mm/min]
td : Deceleration time [s]
L
L
2
S ................................................................................... (4.3)
2
: Proximity dog length [mm]
2
S : Moving distance per servo motor revolution [mm]
4 - 28
4. OPERATION
(3) Timing chart
ON
OFF
Movement finish (MEND)
ON
OFF
Rough match (CPO)
Home position return
completion (ZP)
ON
OFF
Home position shift
Point table No. 1
Home position return
Point table No. 1
distance Parameter No. 11
Deceleration time constant
Creep speed
speed Parameter No. 9
Acceleration time
constant
Home position
Parameter No. 10
Servo motor speed
td
3ms or less
Proximity dog
Home position address
Parameter No. 42
ON
OFF
Z-phase
Proximity dog (DOG)
ON
OFF
5ms or more
ON
OFF
Forward rotation start (ST1)
Reverse rotation start (ST2)
ON
OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
(4) Adjustment
In dog type home position return, adjust to ensure that the Z-phase signal is generated during dog
detection. Locate the rear end of the proximity dog (DOG) at approximately the center of two
consecutive Z-phase signals.
The position where the Z-phase signal is generated can be monitored in "Within one-revolution
position" of "Status display".
0
65536
0
Servo motor
Z-phase
Proximity
dog
Proximity dog
ON
(DOG) OF
4 - 29
4. OPERATION
4.4.3 Count type home position return
In count type home position return, a motion is made over the distance set in parameter No.43 (moving
distance after proximity dog) after detection of the proximity dog front end. The position where the first Z-
phase signal is given after that is defined as a home position. Hence, if the proximity dog (DOG) is 10ms
or longer, there is no restriction on the dog length. This home position return method is used when the
required proximity dog length cannot be reserved to use dog type home position return or when the
proximity dog (DOG) is entered electrically from a controller or the like.
(1) Signals, parameters
Set the input signals and parameters as follows.
Item
Device/Parameter used
Automatic/manual selection (MD0)
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Description
Short MD0-SG (ON).
Open DI0-SG (OFF).
Open DI1-SG (OFF).
Manual home position return
mode selection
1 : Count type home position return
is selected.
Refer to section 4.4.1 (2) and choose home
position return direction.
Refer to section 4.4.1 (2) and choose dog
input polarity.
Count type home position return
Home position return direction
Dog input polarity
Parameter No.8
Parameter No.8
Parameter No.8
Home position return speed
Creep speed
Parameter No.9
Parameter No.10
Set speed until detection of dog.
Set speed after detection of dog.
Set when shifting the home position,
starting at the first Z-phase signal given
after passage of the proximity dog front end
and movement over the moving distance.
Set the moving distance after passage of
proximity dog front end.
Home position shift distance
Parameter No.11
Moving distance after proximity
dog
Home position return
acceleration/deceleration time
constants
Parameter No.43
Point table No.1
Parameter No.42
Use the acceleration/deceleration time
constants of point table No.1.
Home position return position
data
Use to set the current position on
completion of home position return.
(2) Timing chart
ON
Movement finish (MEND)
OFF
Rough match
(CPO)
ON
OFF
Home position return
completion (ZP)
ON
OFF
Home position
shift distance
Parameter No. 11
Point table No. 1
Deceleration time
constant
Home position return
Point table No. 1
Acceleration time constant speed Parameter No. 9
Creep speed
Parameter No. 10
Home position
Servo motor speed
3ms or less
Proximity dog
Moving distance after
proximity dog
Parameter No. 43
Home position address
Parameter No. 42
ON
OFF
ON
Z-phase
Proximity dog (DOG)
OFF
5ms or more
ON
OFF
Forward rotation
start (ST1)
ON
Reverse rotation
start (ST2) OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 30
4. OPERATION
4.4.4 Data setting type home position return
Data setting type home position return is used when it is desired to determine any position as a home
position. JOG operation, manual pulse generator operation or like can be used for movement.
(1) Signals, parameters
Set the input signals and parameters as follows.
Item
Device/Parameter used
Description
Automatic/manual selection (MD0) Short MD0-SG (ON).
Manual home position return mode
selection
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Open DI0-SG (OFF).
Open DI1-SG (OFF).
2 : Data setting type home position
Data setting type home position return
Home position return position data
Parameter No.8
Parameter No.42
return is selected.
Use to set the current position on completion
of home position return.
(2) Timing chart
ON
OFF
Automatic/manual selection
(MD0)
ON
OFF
Movement finish (MEND)
Rough match ON
(CPO)
OFF
Home position
return completion
(ZP)
ON
OFF
Home position address
Parameter No. 42
Servo motor speed
3ms or less
Forward rotation
start (ST1)
5ms or more
ON
OFF
Reverse rotation
start (ST2)
ON
OFF
Movement to the home position
Operation for home position return
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 31
4. OPERATION
4.4.5 Stopper type home position return
In stopper type home position return, a machine part is pressed against a stopper or the like by jog
operation, manual pulse generator operation or the like to make a home position return and that position
is defined as a home position.
(1) Signals, parameters
Set the input signals and parameters as follows.
Item
Device/Parameter used
Automatic/manual selection (MD0)
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Description
Short MD0-SG (ON).
Manual home position return
mode selection
Open DI0-SG (OFF).
Open DI1-SG (OFF).
Stopper type home position
return
3 : Stopper type home position return is
Parameter No.8
selected.
Home position return
direction
Refer to section 4.4.1 (2) and choose the home
position return direction.
Parameter No.8
Parameter No.9
Home position return speed
Set the speed till contact with the stopper.
Time from when the part makes contact with
the stopper to when home position return data is
obtained to output home position return
completion (ZP)
Stopper time
Parameter No.44
Stopper type home position
return torque limit
Set the servo motor torque limit value for
execution of stopper type home position return.
Use the acceleration time constant of point table
No.1.
Parameter No.45
Point table No.1
Parameter No.42
Home position return
acceleration time constant
Home position return
position data
Use to set the current position on completion of
home position return.
4 - 32
4. OPERATION
(2) Timing chart
ON
Automatic/manual
selection (MD0)
OFF
ON
Movement finish
(MEND)
OFF
ON
Rough match
(CPO)
OFF
ON
Home position
return completion
(ZP)
OFF
Point table No.1
Acceleration time constant
Home position address
Parameter No. 42
Home position return
speed Parameter No.9
Servo motor speed
3ms or less
Stopper
ON
Forward rotation start
(ST1)
5ms or more
OFF
ON
Forward rotation start
(ST2)
OFF
Stopper time
Parameter No. 44
ON
Limiting torque (TLC)
Torque limit value
OFF
Parameter No.28
(Note)Parameter No.45
Parameter No.28
Note. The torque limit that is enabled at this point is as follows.
(Note)
Torque limit to be
enabled
Limit value status
I/O devices
TL1
TL
0
0
0
Parameter No.45
Parameter No.45
TLA
TLA
TLA
Parameter No.45
1
0
1
Parameter No.45
Parameter No.45
Parameter No.45
Parameter No.45
Parameter No.45
Parameter No.29
Parameter No.29
TLA
Parameter No.45
Parameter No.45
Parameter No.45
TLA
1
1
TLA
Note. 0: OFF
1: ON
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 33
4. OPERATION
4.4.6 Home position ignorance (servo-on position defined as home position)
The position where servo is switched on is defined as a home position.
(1) Signals, parameter
Set the input signals and parameter as follows.
Item
Device/Parameter used
Description
Home position ignorance
Home position return position
data
Parameter No.8
4 : Home position ignorance is selected.
Use to set the current position on completion of
home position return.
Parameter No.42
(2) Timing chart
ON
OFF
Servo-on (SON)
ON
Ready (RD)
OFF
Automatic/manual
selection (MD0)
ON
OFF
ON
OFF
Movement finish (MEND)
Rough match
(CPO)
ON
OFF
Home position
return completion
(ZP)
ON
OFF
Home position address
Parameter No. 42
Servo motor speed
The parameter No.42 (home position return position data) setting value is the positioning address after
the home position return is completed.
4 - 34
4. OPERATION
4.4.7 Dog type rear end reference home position return
POINT
This home position return method depends on the timing of reading
Proximity dog (DOG) that has detected the rear end of a proximity dog.
Hence, if a home position return is made at the creep speed of 100r/min, an
error of 200 pulses will occur in the home position. The error of the home
position is larger as the creep speed is higher.
The position where the axis, which had started decelerating at the front end of a proximity dog, has
moved the after-proximity dog moving distance and home position shift distance after it passed the rear
end is defined as a home position. A home position return that does not depend on the Z-phase signal can
be made.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Item
Device/Parameter used
Description
Automatic/manual selection (MD0) Short (turn on) MD0-SG.
Manual home position return mode
selection
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Open (turn off) DI0-SG.
Open (turn off) DI1-SG.
Dog type rear end reference home
position return
Parameter No.8
5: Select the dog type rear end reference.
Home position return direction
Dog input polarity
Home position return speed
Creep speed
Parameter No.8
Parameter No.8
Parameter No.9
Parameter No.10
Refer to section 4.4.1 (2) and select the home position return direction.
Refer to section 4.4.1 (2) and select the dog input polarity.
Set the speed till the dog is detected.
Set the speed after the dog is detected.
Set when the home position is moved from where the axis has passed
the proximity dog rear end.
Home position shift distance
Parameter No.11
Set the moving distance after the axis has passed the proximity dog
rear end.
Moving distance after proximity dog Parameter No.43
Home position return acceleration/
Point table No.1
Use the acceleration/deceleration time constant of point table No. 1.
Use to set the current position on completion of home position return.
deceleration time constants
Home position return position data
Parameter No.42
(2) Timing chart
ON
Automatic/manual
selection (MD0)
OFF
ON
Movement finish (MEND)
Rough match (CPO)
OFF
ON
OFF
ON
Home position return
completion (ZP)
OFF
Moving distance after proximity dog
Home position return speed
Home position shift distance
Creep speed
Servo motor speed
3ms or less
Proximity dog
Home position address
Parameter No. 42
ON
Proximity dog (DOG)
OFF
ON
Forward rotation start (ST1)
OFF
5ms or more
ON
Reverse rotation start (ST2)
OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 35
4. OPERATION
4.4.8 Count type front end reference home position return
POINT
This home position return method depends on the timing of reading
Proximity dog (DOG) that has detected the front end of a proximity dog.
Hence, if a home position return is made at the home position return speed
of 100r/min, an error of 200 pulses will occur in the home position. The
error of the home position is larger as the home position return speed is
higher.
The position where the axis, which had started decelerating at the front end of a proximity dog, has
moved the after-proximity dog moving distance and home position shift distance is defined as a home
position. A home position return that does not depend on the Z-phase signal can be made. The home
position may change if the home position return speed varies.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Item
Device/Parameter used
Description
Automatic/manual selection (MD0) Short (turn on) MD0-SG.
Manual home position return mode
selection
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Open (turn off) DI0-SG.
Open (turn off) DI1-SG.
Count type dog front end reference
home position return
Parameter No.8
Parameter No.8
6: Select the count type dog front end reference.
Refer to section 4.4.1 (2) and select the home position return
direction.
Home position return direction
Dog input polarity
Home position return speed
Creep speed
Parameter No.8
Parameter No.9
Parameter No.10
Refer to section 4.4.1 (2) and select the dog input polarity.
Set the speed till the dog is detected.
Set the speed after the dog is detected.
Set when the home position is moved from where the axis has passed
the proximity dog rear end.
Home position shift distance
Parameter No.11
Parameter No.43
Set the moving distance after the axis has passed the proximity dog
rear end.
Moving distance after proximity dog
Home position return acceleration/
deceleration time constants
Home position return position data
Point table No.1
Parameter No.42
Use the acceleration/deceleration time constant of point table No. 1.
Use to set the current position on completion of home position return.
(2) Timing chart
ON
Automatic/manual
selection (MD0)
OFF
ON
Movement finish (MEND)
Rough match (CPO)
OFF
ON
OFF
ON
Home position return
completion (ZP)
OFF
Moving distance after proximity dog
Home position return speed
Home position shift distance
Creep speed
Servo motor speed
Proximity dog (DOG)
3ms or less
Home position address
Parameter No. 42
Proximity dog (DOG)
ON
OFF
ON
Forward rotation
start (ST1)
OFF
5ms or more
ON
Reverse rotation
start (ST2)
OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 36
4. OPERATION
4.4.9 Dog cradle type home position return
The position where the first Z-phase signal is issued after detection of the proximity dog front end can be
defined as a home position.
(1) Signals, parameters
Set the input signals and parameters as indicated below.
Item
Device/Parameter used
Description
Automatic/manual selection (MD0) Short (turn on) MD0-SG.
Manual home position return mode
selection
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Open (turn off) DI0-SG.
Open (turn off) DI1-SG.
Dog cradle type home position return Parameter No.8
7: Select the dog cradle type.
Refer to section 4.4.1 (2) and select the home
position return direction.
Home position return direction
Dog input polarity
Parameter No.8
Parameter No.8
Refer to section 4.4.1 (2) and select the dog input
polarity.
Home position return speed
Creep speed
Parameter No.9
Parameter No.10
Set the speed till the dog is detected.
Set the speed after the dog is detected.
Set when the home position is moved from the Z-
phase signal position.
Home position shift distance
Parameter No.11
Point table No.1
Parameter No.42
Home position return
acceleration/deceleration time
constants
Use the acceleration/deceleration time constant of
point table No. 1.
Use to set the current position on completion of
home position return.
Home position return position data
(2) Timing chart
ON
Automatic/manual
selection (MD0)
OFF
ON
Movement finish (MEND)
Rough match (CPO)
OFF
ON
OFF
Home position return ON
completion (ZP)
OFF
Home position return speed
Creep speed
Home position shift distance
Servo motor speed
3ms or less
Home position address
Parameter No. 42
Proximity dog
ON
Z-phase
OFF
ON
Proximity dog (DOG)
OFF
ON
Forward rotation
start (ST1)
OFF
5ms or more
Reverse rotation
start (ST2)
ON
OFF
The parameter No.42 (home position return position data) setting value is the positioning address
after the home position return is completed.
4 - 37
4. OPERATION
4.4.10 Home position return automatic return function
If the current position is at or beyond the proximity dog in the home position return using the proximity
dog, this function starts home position return after making a return to the position where the home
position return can be made.
(1) When the current position is at the proximity dog
When the current position is at the proximity dog, an automatic return is made before home position
return.
Home position return direction
Proximity dog
Home position return
start position
Makes an automatic return
to a position before the
proximity dog, then executes
home position return at this position.
(2) When the current position is beyond the proximity dog
At a start, a motion is made in the home position return direction and an automatic return is made on
detection of the stroke end (LSP or LSN). The motion stops past the front end of the proximity dog,
and home position return is resumed at that position. If the proximity dog cannot be detected, the
motion stops on detection of the opposite LSP or LSN and home position return incomplete warning
(AL. 90) occurs.
Stroke end
(LSP or LSN)
Home position return direction
Proximity dog
Home position return
start position
Makes an automatic return
to a position before the
proximity dog, then executes
home position return at this position.
Software limit cannot be used with these functions.
4 - 38
4. OPERATION
4.4.11 Automatic positioning function to the home position
POINT
You cannot perform automatic positioning from outside the position data
setting range to the home position. In this case, make a home position
return again using a manual home position return.
If this function is used when returning to the home position again after performing a manual home
position return after a power-on and deciding the home position, automatic positioning can be carried out
to the home position at high speed. In an absolute position system, manual home position return is not
required after power-on.
Please perform a manual home position return beforehand after a power-on.
Set the input signals and parameter as follows.
Item
Device/Parameter used
Description
Automatic/manual selection (MD0) Short MD0-SG (ON).
Manual home position return mode
selection
Point table No. selection 1 (DI0)
Point table No. selection 2 (DI1)
Parameter No.9
Open DI0-SG (OFF).
Open DI1-SG (OFF).
Speed is set up.
Home position return speed
Home position return acceleration
time constant
Use the acceleration time constant of point table
No.1.
Point table No.1
Set up the home position return speed of the automatic positioning function to the home position by
parameter No.9. Use the data of point table No.1 to set the acceleration time constant and deceleration
time constant. When reverse rotation start (ST2) is ON, it will position automatically at the home
position.
Home position return speed Deceleration time constant
Acceleration time constant
Parameter No. 9
of point table No. 1
of point table No. 1
Servo motor speed
Home position
ON
OFF
Forward rotation start (ST1)
Reverse rotation start (ST2)
ON
OFF
4 - 39
4. OPERATION
4.5 Absolute position detection system
If an absolute position erase alarm (AL.25) or an absolute position counter warning
(AL.E3) has occurred, always perform home position setting again. Not doing so
can cause runaway.
CAUTION
POINT
When the following parameters are changed, the home position is lost
when turning on the power after the change. Execute the home position
return again when turning on the power.
First digit of parameter No.1 (ST1 coordinate system selection)
Parameter No. 4 (Electronic gear numerator)
Parameter No. 5 (Electronic gear denominator)
Parameter No. 42 (Home position return position data)
This servo amplifier contains a single-axis controller. Also, all servo motor encoders are compatible with
an absolute position system. Hence, an absolute position detection system can be configured up by merely
loading an absolute position data back-up battery and setting parameter values.
(1) Restrictions
An absolute position detection system cannot be built under the following conditions.
1) Stroke-less coordinate system, e.g. rotary shaft, infinite positioning.
2) Operation performed in incremental value command type positioning system.
(2) Specifications
Item
Description
Electronic battery backup system
System
Battery
1 piece of lithium battery ( primary battery, nominal 3.6V)
Type: MR-BAT or A6BAT
Maximum revolution range
(Note 1) Maximum speed at power failure
(Note 2) Battery backup time
(Note 3) Data holding time during battery
replacement
Home position 32767 rev.
500r/min
Approx. 10,000 hours (battery life with power off)
2 hours at delivery, 1 hour in 5 years after delivery
Battery storage period
5 years from date of manufacture
Note 1. Maximum speed available when the shaft is rotated by external force at the time of power failure or the like.
2. Time to hold data by a battery with power off. It is recommended to replace the battery in three years independently of
whether power is kept on or off.
3. Period during which data can be held by the super capacitor in the encoder after power-off, with the battery voltage low or
the battery removed, or during which data can be held with the encoder cable disconnected.
Battery replacement should be finished within this period.
4 - 40
4. OPERATION
(3) Structure
Component
Description
Servo amplifier
Servo motor
Battery
Use standard models.
MR-BAT or A6BAT
Use a standard model.
Encoder cable
When fabricating, refer to (2), section 14.1.4.
(4) Outline of absolute position detection data communication
For normal operation, as shown below, the encoder consists of a detector designed to detect a position
within one revolution and a cumulative revolution counter designed to detect the number of
revolutions.
The absolute position detection system always detects the absolute position of the machine and keeps
it battery-backed, independently of whether the general-purpose programming controller power is on
or off. Therefore, once the home position is defined at the time of machine installation, home position
return is not needed when power is switched on thereafter.
If a power failure or a fault occurs, restoration is easy.
Also, the absolute position data, which is battery-backed by the super capacitor in the encoder, can be
retained within the specified period (cumulative revolution counter value retaining time) if the cable is
unplugged or broken.
Servo amplifier
Home position return
data
Point table No. selection
(DI0 to DI3), etc.
EEP-ROM memory
I/O circuit
Current position
LSO
1XO
Backup at
power off
Position data, speed data
(current position read)
1X
LS
Detection of position
within one revolution
Speed detection
Battery MR-BAT
Servo motor
1 pulse/rev. Cumulative
High-speed serial
communication
revolution counter
Super capacitor
Within one-revolution counter
(5) Battery installation procedure
Before installing a battery, turn off the main circuit power while keeping the control
circuit power on. Wait for 15 minutes or more until the charge lamp turns off. Then,
confirm that the voltage between P and N is safe with a voltage tester and others.
Otherwise, an electric shock may occur. In addition, always confirm from the front
of the servo amplifier whether the charge lamp is off or not.
WARNING
POINT
The internal circuits of the servo amplifier may be damaged by static
electricity.
Always take the following precautions.
Ground human body and work bench.
Do not touch the conductive areas, such as connector pins and electrical
parts, directly by hand.
4 - 41
4. OPERATION
1) Open the operation window. (When the model used is the MR-J2S-200CP MR-J2S-350CP or more,
also remove the front cover.)
2) Install the battery in the battery holder.
3) Install the battery connector into CON1 until it clicks.
Battery connector
Battery connector
Operation window
CON1
CON1
Battery
Battery holder
Battery
Battery holder
For MR-J2S-100CP or less
For MR-J2S-200CP MR-J2S-350CP
Battery connector
CON1
Battery holder
Battery
For MR-J2S-500CP MR-J2S-700CP
(6) Parameter setting
Set parameter No.2 (Function selection 1) as indicated below to make the absolute position detection
system valid.
Parameter No.2
1
Selection of absolute position detection system
0: Incremental system
1: Absolute position detection system
4 - 42
4. OPERATION
4.6 Serial communication operation
The RS-422 or RS-232C communication function may be used to operate the servo amplifier from a
command device (controller) such as a personal computer. Positioning operation can be performed with
the positioning operation/position specified by selection of the point tables. Note that the RS-422 and RS-
232C communication functions cannot be used at the same time.
This section provides a data transfer procedure. Refer to chapter 15 for full information on the connection
and transferred data between the controller and servo amplifier.
4.6.1 Positioning operation in accordance with point tables
By selecting the point table No. and switching on the forward rotation start (ST1) or reverse rotation start
(ST2) using the communication function, positioning operation in accordance with point tables can be
started.
(1) Selection of point tables
Using the device forced output from the controller (command [9][2], data No. [6][0]), choose point
tables from among No.1 to 31.
(2) Timing chart
5ms or more
5ms or more
4) 5)
5ms or more
4) 5)
Transmission
data
1)
4)
5)
2)
3)
Servo motor
speed
3ms
Point table No. 2
Point table No. 1
Point table No. 3
No.
Transmission data
Command
[9] [2]
Data No.
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
1)
2)
3)
4)
5)
Point table No.2 selection
Point table No.1 selection
[9] [2]
Point table No.3 selection
[9] [2]
Forward rotation start (ST1) ON
Forward rotation start (ST1) OFF
[9] [2]
[9] [2]
4 - 43
4. OPERATION
4.6.2 Positioning operation
Positioning operation can be performed by changing the point table settings and making a start. For
example, positioning operation can be performed by writing the data of point table No.1, then specifying
point table No.1, and making a start.
For transmission data details, refer to chapter 15.
5ms or more
Transmission data
1)
2)
3)
4)
5)
6)
7)
8)
Servo motor speed
3ms
Values set with transmission data 1) to 5) are used for operation.
No.
Transmission data
Command
[C] [0]
[C] [6]
[C] [7]
[C] [8]
[C] [B]
[9] [2]
Data No.
[0] [1]
[0] [1]
[0] [1]
[0] [1]
[0] [1]
[6] [0]
[6] [0]
[6] [0]
1)
2)
3)
4)
5)
6)
7)
8)
Point table No.1 position data write
Point table No.1 speed
Point table No.1 acceleration time constant
Point table No.1 deceleration time constant
Point table No.1 auxiliary function
Point table No.1 selection
Forward rotation start (ST1) ON
Forward rotation start (ST1) OFF
[9] [2]
[9] [2]
4.6.3 Multidrop system
The RS-422 communication function can be used to operate several servo amplifiers on the same bus. In
this case, set the station numbers to the servo amplifiers to determine the destination servo amplifier of
the currently transmitted data. Use parameter No.15 to set the station numbers.
Always set one station number to one servo amplifier. Normal communication cannot be made if one
station number is set to two or more servo amplifiers. When using one command to operate several servo
amplifiers, use the group designation function described in section 4.6.4.
MITSUBISHI
MITSUBISHI
MITSUBISHI
MITSUBISHI
To CN3
To CN3
To CN3
To CN3
CHARGE
CHARGE
CHARGE
CHARGE
Axis 1
(Station 0)
Axis 2
(Station 1)
Axis 3
(Station 2)
Axis 32
(Station 31)
Controller
RS-422
For cable connection diagram,
refer to section 15.1.1.
4 - 44
4. OPERATION
4.6.4 Group designation
When using several servo amplifiers, command-driven parameter settings, etc. can be made on a group
basis.
You can set up to six groups, a to f. Set the group to each station using the communication command.
(1) Group setting example
Group a
Group b
MITSUBISHI
MITSUBISHI
MITSUBISHI
MITSUBISHI
MITSUBISHI
To CN3
To CN3
To CN3
To CN3
To CN3
CHARGE
CHARGE
CHARGE
CHARGE
CHARGE
Axis 1
(Station 0)
Axis 2
(Station 1)
Axis 3
(Station 2)
Axis 4
(Station 3)
Axis 5
(Station 4)
Controller
RS-422
For cable connection diagram,
refer to section 15.1.1.
MITSUBISHI
MITSUBISHI
MITSUBISHI
MITSUBISHI
MITSUBISHI
CHARGE
CHARGE
CHARGE
CHARGE
CHARGE
To CN3
To
To CN3
To
To CN3
CN3
CN3
(Station 6)
Axis 10
(Station 9)
Axis 9
(Station 8)
Axis 8
(Station 7)
Axis 7
Axis 6
(Station 5)
Group d
Group c
Servo amplifier station No.
Station 0
Group setting
Station 1
a
Station 2
Station 3
Station 4
b
c
Station 5
Station 6
Station 7
Station 8
d
Station 9
4 - 45
4. OPERATION
(2) Timing chart
In the following timing chart, operation is performed group-by-group in accordance with the values set
in point table No.1.
Transmission data
7)
9)
11)
12)
1)
2)
3)
4)
5)
6)
8)
10)
Station 0
Servo motor
speed
Station 1
Servo motor
speed
Station 2
Servo motor
speed
Group a
Station 3
Servo motor
speed
Station 4
Servo motor
speed
Group b
Station 5
Servo motor
speed
Station 6
Servo motor
speed
Station 7
Servo motor
speed
Group c
Group d
Station 8
Servo motor
speed
Station 9
Servo motor
speed
No.
Transmission data
Command
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
[9] [2]
Data No.
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
[6] [0]
1)
2)
3)
4)
5)
6)
7)
8)
9)
Selection of point table No.1 of group a
Forward rotation start (ST1) ON
Forward rotation start (ST1) OFF
Selection of point table No.1 of group b
Forward rotation start (ST1) ON
Forward rotation start (ST1) OFF
Selection of point table No.1 of group c
Forward rotation start (ST1) ON
Forward rotation start (ST1) OFF
10) Selection of point table No.1 of group d
11) Forward rotation start (ST1) ON
12) Forward rotation start (ST1) OFF
In addition, parameter values common to the stations of each group can be written and alarm reset
can be made, for example.
(3) Group setting instructions
Only one servo amplifier may send a reply in any group. If two or more servo amplifiers send reply
data at the same time, they may become faulty.
4 - 46
5. PARAMETERS
5. PARAMETERS
CAUTION
Never adjust or change the parameter values extremely as it will make operation
instable.
5.1 Parameter list
5.1.1 Parameter write inhibit
POINT
Set "000E" when using the MR Configurator (servo configuration
software) to make device setting.
After setting the parameter No.19 value, switch power off, then on to
make that setting valid.
In the servo amplifier, its parameters are classified into the basic parameters (No.0 to 19), expansion
parameters 1 (No.20 to 53), expansion parameters 2 (No.54 to 77) and special parameters (No.78 to 90)
according to their safety aspects and frequencies of use. In the factory setting condition, the customer can
change the basic parameter values but cannot change the expansion parameter 1,2 values and special
parameter values. When fine adjustment, e.g. gain adjustment, is required, change the parameter No.19
setting to make the expansion parameters write-enabled.
The following table lists the parameters whose values are made valid for reference/write by setting
parameter No. 19. Operation can be performed for the parameters marked
.
Expansion parameters 2
No.54 to No.77
Parameter No.19
setting
Basic parameters
No.0 to No.19
Expansion parameters 1
No.20 to No.53
Operation
special parameters (No.78 to 90)
0000
Reference
Write
(initial value)
Reference
Write
No.19 only
No.19 only
000A
000B
000C
000E
Reference
Write
Reference
Write
Reference
Write
5 - 1
5. PARAMETERS
5.1.2 List
POINT
The parameters marked * before their symbols are made valid by
switching power off once and then switching it on again after parameter
setting.
Refer to the corresponding reference items for details of the parameters.
(1) Item list
Customer
setting
Class No.
Symbol
Name and Function
Initial value
Unit
0
1
*STY
*FTY
*OP1
ATU
Command system/regenerative option selection
Feeding function selection
Function selection 1
0000
0000
0002
0105
1
2
3
Auto tuning
4
*CMX Electronic gear numerator
5
*CDV
INP
Electronic gear denominator
In-position range
1
6
100
35
pulse
rad/s
7
PG1
Position control gain 1
8
*ZTY
ZRF
Home position return type
Home position return speed
Creep speed
0010
500
10
9
r/min
r/min
m
10
11
12
13
14
15
16
17
18
19
CRF
ZST
Home position shift distance
Rough match output range
Jog speed
0
CRP
JOG
*STC
*SNO
*BPS
MOD
0
10STM
r/min
ms
m
100
0
S-pattern acceleration/deceleration time constant
Station number setting
0
station
Communication baud rate selection, alarm history clear
Analog monitor output
0000
0100
0000
0000
*DMD Status display selection
*BLK Parameter write inhibit
5 - 2
5. PARAMETERS
Customer
setting
Class No.
Symbol
Name and Function
Initial value
Unit
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
51
52
53
*OP2
Function selection 2
0000
0002
0000
0
For manufacturer setting
Function selection 4
*OP4
SIC
Serial communications time-out selection
Feed forward gain
FFC
VCO
TLO
0
%
mV
Override offset
0
Torque limit offset
0
mV
*ENR Encoder output pulses
4000
100
100
0
pulse/rev
%
TL1
TL2
Internal torque limit 1
Internal torque limit 2
%
*BKC
MO1
MO2
MBR
GD2
PG2
VG1
VG2
VIC
Backlash compensation
pulse
mV
Analog monitor 1 offset
0
Analog monitor 2 offset
0
mV
Electromagnetic brake sequence output
Ratio of load inertia moment to Servo motor inertia moment
Position control gain 2
100
70
ms
0.1 times
rad/s
rad/s
rad/s
ms
35
Speed control gain 1
177
817
48
Speed control gain 2
Speed integral compensation
Speed differential compensation
VDC
980
0
For manufacturer setting
0
*ZPS
DCT
ZTM
ZTT
Home position return position data
0
10STM
10STM
m
Moving distance after proximity dog
1000
100
15
m
Stopper type home position return stopper time
Stopper type home position return torque limit value
ms
%
*LMP Software limit
*LMN Software limit
0
0
0
0
10STM
10STM
10STM
10STM
m
m
m
m
*LPP
*LNP
Position range output address
Position range output address
5 - 3
5. PARAMETERS
Customer
setting
Class No.
Symbol
Name and Function
For manufacturer setting
Initial value
Unit
54
55
56
57
58
59
60
61
62
63
64
65
66
67
68
69
70
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
0000
0000
0000
0000
0000
0000
0000
0000
0000
0000
70
*OP6
Function selection 6
For manufacturer setting
*OP8
*OP9
*OPA
Function selection 8
Function selection 9
Function selection A
For manufacturer setting
NH1
NH2
LPF
Machine resonance suppression filter 1
Machine resonance suppression filter 2
Low-pass filter, adaptive vibration suppression control
GD2B Ratio of load inertia moment to Servo motor inertia moment 2
PG2B Position control gain 2 changing ratio
VG2B Speed control gain 2 changing ratio
0.1 times
100
%
%
%
100
VICB
*CDP
CDS
Speed integral compensation changing ratio
Gain changing selection
100
0000
10
Gain changing condition
(Note)
CDT
Gain changing time constant
1
ms
100
10000
10
For manufacturer setting
10
100
100
100
0000
0009
080A
0706
020B
0504
0002
0000
0005
0D04
0102
0
For manufacturer setting
0
Note. Depends on the parameter No. 68 setting.
5 - 4
5. PARAMETERS
(2) Detail list
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
Command system, regenerative option selection
Used to select the command system and regenerative option.
0
*STY
0000
Refer to
Name
and
0
0
function
column.
Selection of command system (Refer to section 4.2)
0: Absolute value command system
1: Incremental value command system
2: Absolute value command/incremental
value command specifying system
Selection of regenerative option
(Refer to section 14.1.1)
0: Not used (The built-in regenerative resistor is used.
However, the MR-J2S-10CP does not have a built-in
regenerative resistor and therefore cannot use it.)
1: FR-RC, FR-BU2
2: MR-RB032
3: MR-RB12
4: MR-RB32
5: MR-RB30
6: MR-RB50 (Cooling fan is required)
8: MR-RB31
9: MR-RB51 (Cooling fan is required)
If the regenerative option selected is not for use with the
servo amplifier, parameter error occurs
Feeding function selection
Used to set the feed length multiplication factor and manual pulse generator
multiplication factor.
1
*FTY
0000
Refer to
Name
and
function
column.
ST1 coordinate system selection
(Refer to section 4.2.2 to 4.2.4)
0: Address is incremented in CCW direction
1: Address is incremented in CW direction
Feed length multiplication factor (STM)
(Refer to section 4.2.2 to 4.2.4)
0: 1 time
1: 10 times
2: 100 times
3: 1000 times
Manual pulse generator multiplication factor
(Refer to section 4.3.2)
0: 1 time
1: 10 times
2: 100 times
Servo-on (SON) -off, forced stop (EMG) -off
follow-up for absolute value command
in incremental system or absolute value command/
incremental value command specifying system
0: Invalid
1: Valid
Normally, when this servo amplifier is used
in the absolute value command method of the
incremental system, placing it in a servo off or
forced stop status will erase the home position.
When "1" is set in this parameter, the home
position will not be erased if the servo amplifier
is placed in a servo off or forced stop status.
Operation can be resumed when servo-on (SON)
is turned on again or forced stop (EMG) is canceled.
5 - 5
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
Function selection 1
Used to select the input filter and absolute position detection system.
2
*OP1
0002
Refer to
Name
and
0 0
function
column.
Input filter
If external input signal causes chattering due
to noise, etc., input filter is used to suppress it.
0: None
1: 0.88[ms]
2: 1.77[ms]
3: 2.66[ms]
4: 3.55[ms]
5: 4.44[ms]
Selection of absolute position detection system
(Refer to section 4.5)
0: Incremental system
1: Absolute position detection system
Auto tuning
3
ATU
0105
Refer to
Name
Used to selection the response level, etc. for execution of auto tuning.
(Refer to chapter 7)
and
0
0
function
column.
Auto tuning response level setting
Set Response Machine resonance
value
1
level
Low
frequency guideline
15Hz
response
2
20Hz
3
25Hz
4
30Hz
5
35Hz
6
45Hz
7
8
9
55Hz
70Hz
85Hz
Middle
response
A
B
C
D
E
F
105Hz
130Hz
160Hz
200Hz
240Hz
300Hz
High
response
If the machine hunts or generates large gear sound,
decrease the set value.
To improve performance, e.g. shorten the settling time,
increase the set value.
Gain adjustment mode selection
(For more information, refer to section 8.1.1.)
Set value Gain adjustment mode
Description
Fixes position control gain 1
(parameter No. 6).
0
Interpolation mode
Auto tuning mode 1
Auto tuning mode 2
Ordinary auto tuning.
Fixes the load inertia moment
ratio set in parameter No. 34.
Response level setting can be
changed.
1
2
Manual mode 1
Manual mode 2
Simple manual adjustment.
Manual adjustment of all gains.
3
4
5 - 6
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
4
*CMX Electronic gear numerator
1
0 to
Set the value of electronic gear numerator. Setting "0" automatically sets the
resolution of the servo motor connected. (Refer to section 5.2.1)
*CDV Electronic gear denominator
65535
5
6
7
1
1 to
65535
0 to
Set the value of electronic gear denominator. (Refer to section 5.2.1)
INP
In-position range
100
36
m
Used to set the droop pulse range when the in-position (INP) is output.
10000
4 to 1000
PG1 Position control gain 1
Used to set the gain of position loop 1. (Refer to chapter 8)
rad/s
Increase the gain to improve tracking performance in response to the position
command.
8
*ZTY Home position return type
0010
Refer to
Name
Used to set the home position return system, home position return direction and
proximity dog input polarity.
and
function
column.
0
Home position return system
0: Dog type
1: Count type
2: Data setting type
3: Stopper type
4: Home position ignorance
(Servo-on position as home position)
5: Dog type rear end reference
6: Count type front end reference
7: Dog cradle type
Home position return direction
0: Address increment direction
1: Address decrement direction
Proximity dog input polarity
0: Dog is detected when DOG-SG are opened
1: Dog is detected when DOG-SG are shorted
Home position return speed
Used to set the servo motor speed for home position return.
(Refer to section 4.4)
9
ZRF
CRF
500
10
r/min
r/min
m
0 to
permissible
speed
Creep speed
10
0 to
Used to set the creep speed after proximity dog detection.
(Refer to section 4.4)
permissible
speed
Home position shift distance
Used to set the shift distance starting at the Z-phase pulse detection position
inside the encoder.
11
12
13
ZST
CRP
JOG
0
0
0 to 65535
10STM 0 to 65535
m
Rough match output range
Used to set the command remaining distance range where the rough match
(CPO) is output.
Jog speed
Used to set the jog speed command.
100
r/min
0 to
permissible
speed
S-pattern acceleration/deceleration time constant
14
*STC
0
0
ms
0 to 100
Set when inserting S-pattern time constant into the acceleration/deceleration
time constant of the point table. (Refer to section 5.2.3)
This time constant is invalid for home position return.
RS-422 station number setting
15 *SNO
Station
0 to 31
Used to specify the station number for RS-422 multidrop communication.
(Refer to section 4.6.3)
Always set one station to one axis of servo amplifier. If one station number is set
to two or more stations, normal communication cannot be made.
5 - 7
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
16
*BPS Serial communication function selection, alarm history clear
Used to select the serial communication baud rate, select various
communication conditions, and clear the alarm history.
0000
Refer to
Name
and
function
column.
Serial baud rate selection
(Refer to section 15.2.2)
0: 9600 [bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
4: 4800[bps] (For MR-DP60)
Alarm history clear (Refer to section 5.2.6)
0: Invalid
1: Valid
When alarm history clear is made valid,
the alarm history is cleared at next power-on.
After the alarm history is cleared, the setting
is automatically made invalid (reset to 0).
Serial communication standard selection
(Refer to section 15.2.2)
0: RS-232C used
1: RS-422 used
Serial communication response delay time
(Refer to section 15.2.2)
0: Invalid
1: Valid, reply sent after delay time of 800 s
or more
17
MOD Analog monitor output
0100
Refer to
Name
Used to select the signals to be output to the analog monitor 1 (MO2) and analog
monitor 2 (MO2). (Refer to section 5.2.4)
and
function
column.
0
0
Setting Analog monitor 2 (MO2) Analog monitor 1 (MO1)
0
1
2
3
4
5
6
7
8
9
A
B
Servo motor speed ( 8V/max. speed)
Torque ( 8V/max. torque) (Note)
Servo motor speed ( 8V/max. speed)
Torque ( 8V/max. torque) (Note)
Current command ( 8V/max. current command)
Command pulse frequency ( 10V/500kpulse/s)
Droop pulses ( 10V/128 pulses)
Droop pulses ( 10V/2048 pulses)
Droop pulses ( 10V/8192 pulses)
Droop pulses ( 10V/32768 pulses)
Droop pulses ( 10V/131072 pulses)
Bus voltage ( 8V/400V)
Note. 8V is outputted at the maximum torque. However, when parameter
No. 28 29 are set to limit torque, 8V is outputted at the torque highly
limited.
5 - 8
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
18 *DMD Status display selection
0000
Refer to
Name
Used to select the status display shown at power-on. (Refer to section 7.2)
and
function
column.
Status display on servo amplifier display
at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Point table No.
04: Cumulative feedback pulses
05: Servo motor speed
06: Droop pulses
07: Override voltage
08: Analog torque limit voltage
09: Regenerative load ratio
0A: Effective load ratio
0B: Peak load ratio
0C: Instantaneous torque
0D: Within one-revolution position low
0E: Within one-revolution position high
0F: ABS counter
10: Load inertia moment ratio
11: Bus voltage
Status display of MR-DP60 at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Point table No.
04: Cumulative feedback pulses
05: Servo motor speed
06: Droop pulses
07: Override voltage
08: Analog torque limit voltage
09: Regenerative load ratio
0A: Effective load ratio
0B: Peak load ratio
0C: Instantaneous torque
0D: Within one-revolution position
0E: ABS counter
0F: Load inertia moment ratio
10: Bus voltage
5 - 9
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
19 *BLK Parameter write inhibit
Used to select the reference and write ranges of the parameters.
Operation can be performed for the parameters marked
0000
Refer to
Name
.
and
function
column.
Expansion parameters 2
No.54 to 77
Basic
parameters parameters 1
No.0 to 19 No.20 to 53
Expansion
Set
Operation
value
special parameters
(No. 78 to 90)
0000
(initial
value)
Reference
Write
Reference No.19 only
000A
000B
000C
Write
Reference
Write
No.19 only
Reference
Write
(Note)
Reference
Write
000E
Note. Set this parameter when making device setting using the MR Configurator
(servo configuration software).
20
*OP2 Function selection 2
Used to select slight vibration suppression control.
0000
Refer to
Name
and
0
0 0
function
column.
Slight vibration suppression control selection
0: Invalid
1: Valid
21
22
For manufacturer setting
0002
0000
Do not change this value by any means.
*OP4 Function selection 4
Refer to
Name
Used to select stop processing at forward rotation stroke end (LSP), reverse
rotation stroke end (LSN) off.
and
function
column.
0 0 0
Stopping method used when forward rotation
stroke end (LSP), reverse rotation stroke
end (LSN) device or software limit is valid
(Refer to section 5.2.5)
0: Sudden stop
1: Slow stop
23
SIC
Serial communication time-out selection
0
0 to 60
Used to choose the time-out period of communication protocol.
Setting
Description
No time-out check
0
Time-out check period setting
Check period setting [s]
1 to 60
5 - 10
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
24
FFC Feed forward gain
0
%
0 to 100
Set the feed forward gain. When the setting is 100%, the droop pulses during
operation at constant speed are nearly zero. However, sudden
acceleration/deceleration will increase the overshoot. As a guideline, when the
feed forward gain setting is 100%, set 1s or more as the
acceleration/deceleration time constant up to the rated speed.
25
VCO Override offset
Used to set the offset voltage to analog override.
TLO Torque limit offset
0
0
mV
mV
999 to
999
26
999 to
999
1
to
Used to set the offset voltage to analog torque limit (TLA).
Encoder output pulses
27 *ENR
4000 pulse/
rev
Used to set the encoder pulses (A-phase, B-phase) output by the servo
amplifier.
65535
Set the value 4 times greater than the A-phase or B-phase pulses.
You can use parameter No. 58 to choose the output pulse setting or output
division ratio setting.
The number of A/B-phase pulses actually output is 1/4 times greater than the
preset number of pulses.
The maximum output frequency is 1.3Mpps (after multiplication by 4). Use
this parameter within this range.
For output pulse designation
Set " 0
" (initial value) in parameter No. 58.
Set the number of pulses per servo motor revolution.
Output pulse set value [pulses/rev]
At the setting of 5600, for example, the actually output A/B-phase pulses are
as indicated below.
5600
A
B-phase output pulses
1400[pulse]
4
For output division ratio setting
Set " 1 " in parameter No. 58.
The number of pulses per servo motor revolution is divided by the set value.
Resolution per servo motor revolution
Output pulse
[pulses/rev]
Set value
At the setting of 8, for example, the actually output A/B-phase pulses are as
indicated below.
131072
8
1
4
A
B-phase output pulses
4096[pulse]
28
29
TL1
TL2
Internal torque limit 1
100
100
%
%
0 to 100
0 to 100
Used to limit servo motor-torque on the assumption that the maximum torque
is 100%. When 0 is set, torque is not produced.
Internal torque limit 2
Used to limit servo motor-torque on the assumption that the maximum torque
is 100%. When 0 is set, torque is not produced.
Made valid by switching on the internal torque limit selection (TL2).
30 *BKC Backlash compensation
Used to set the backlash compensation made when the command direction is
0
pulse
(Note)
0
reversed.
to
This function compensates for the number of backlash pulses in the opposite
direction to the home position return direction. In the absolute position
detection system, this function compensates for the backlash pulse count in
the direction opposite to the operating direction at power-on.
Note. The setting range differs depending on the software version of servo
amplifiers.
1600
Version A4 or later: 0 to 1600
Version A3 or before: 0 to 1000
5 - 11
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
31
32
33
MO1 Analog monitor 1 (MO1) offset
0
mV
999 to
999
Used to set the offset voltage of the analog monitor 1 (MO1) output.
MO2 Analog monitor 2 (MO2) offset
0
mV
ms
999 to
999
Used to set the offset voltage of the analog monitor 2 (MO2) output.
MBR Electromagnetic brake sequence output
100
0 to 1000
Used to set the delay time (Tb) between when the electromagnetic brake
interlock (MBR) switches off and when the base circuit is shut off.
(Refer to section 3.9)
34
35
GD2 Ratio of load inertia moment to servo motor inertia moment
Used to set the ratio of the load inertia moment to the servo motor shaft
inertia moment. (Refer to chapter 8)
70
35
0.1 0 to 1000
times
When auto tuning is selected, the result of auto tuning is automatically set.
PG2 Position control gain 2
rad/s 1 to 1000
Used to set the gain of the position loop. (Refer to chapter 8)
Set this parameter to increase the position response level to load disturbance.
Higher setting increases the response level but is liable to generate vibration
and/or noise.
When auto tuning is selected, the result of auto tuning is automatically set.
VG1 Speed control gain 1
36
37
177
817
rad/s
rad/s
ms
20 to
8000
Normally this parameter value need not be changed.
Higher setting increases the response level but is liable to generate vibration
and/or noise. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
VG2 Speed control gain 2
20 to
Set this parameter when vibration occurs on machines of low rigidity or large
backlash. Higher setting increases the response level but is liable to generate
vibration and/or noise. (Refer to chapter 8)
20000
When auto tuning is selected, the result of auto tuning is automatically set.
38
39
VIC
Speed integral compensation
48
1 to 1000
0 to 1000
Used to set the integral time constant of the speed loop. (Refer to chapter 8)
When auto tuning is selected, the result of auto tuning is automatically set.
VDC Speed differential compensation
980
Used to set the differential compensation. (Refer to chapter 8)
Made valid when the proportion control (PC) is switched on.
For manufacturer setting
40
41
42
0
0
0
Do not change this value by any means.
*ZPS Home position return position data
10STM
m
32768
to
Used to set the current position on completion of home position return.
(Refer to section 4.4)
32767
0 to
43
44
DCT Moving distance after proximity dog
1000
100
10STM
m
Used to set the moving distance after proximity dog in count type home
position return. (Refer to section 4.4.3)
65535
ZTM Stopper type home position return stopper time
In stopper type home position return, used to set the time from when the
machine part is pressed against the stopper and the torque limit set in
parameter No.45 is reached to when the home position is set.
(Refer to section 4.4.5)
ms
5 to 1000
45
ZTT Stopper type home position return torque limit
Used to set the torque limit value relative to the max. torque in [%] in stopper
type home position return. (Refer to section 4.4.5)
15
%
1 to 100
5 - 12
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
46 *LMP Software limit
0
10STM
m
999999
to
47
Used to set the address increment side software stroke limit. The software limit
is made invalid if this value is the same as in "software limit ".
(Refer to section 5.2.8)
999999
Set the same sign to parameters No.46 and 47. Setting of different signs will
result in a parameter error.
Set address:
Lower 3
digits
Upper 3
digits
Parameter No. 47
Parameter No. 46
10STM
m
999999
to
Software limit
48 *LMN
49
0
Used to set the address decrement side software stroke limit. The software limit
is made invalid if this value is the same as in "software limit ".
(Refer to section 5.2.8)
999999
Set the same sign to parameters No.48 and 49. Setting of different signs will
result in a parameter error.
Set address:
Lower 3
digits
Upper 3
digits
Parameter No. 49
Parameter No. 48
10STM
m
999999
to
Position range output address
50
51
*LPP
0
Used to set the address increment side position range output address. Set the
same sign to parameters No.50 and 51. Setting of different signs will result in a
parameter error.
999999
In parameters No. 50 to 53, set the range where position range (POT) turns on.
Set address:
Upper 3
digits
Lower 3
digits
Parameter No. 51
Parameter No. 50
10STM
m
999999
to
Position range output address
52
53
*LNP
0
Used to set the address decrement side position range output address. Set the
same sign to parameters No.52 and 53. Setting of different signs will result in a
parameter error.
999999
Set address:
Lower 3
digits
Upper 3
digits
Parameter No. 53
Parameter No. 52
5 - 13
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
54
55
For manufacturer setting
Do not change this value by any means.
*OP6 Function selection 6
Used to select how to process the base circuit when reset (RES) is valid.
0000
0000
Refer to
Name
and
0
0 0
function
column.
Processing of the base circuit when reset (RES) is valid.
0: Base circuit shut off
1: Base circuit not shut off
56
57
For manufacturer setting
0000
0000
Do not change this value by any means.
*OP8 Function selection 8
Used to select the protocol of serial communication.
Refer to
Name
and
0
0
function
column.
Protocol checksum selection
0: Yes (checksum added)
1: No (checksum not added)
Protocol checksum selection
0: With station numbers
1: No station numbers
58
*OP9 Function selection 9
0000
Refer to
Name
Use to select the encoder output pulse direction and encoder pulse output
setting.
and
function
column.
0 0
Encoder pulse output phase changing
Changes the phases of A, B-phase encoder pulses output .
Servo motor rotation direction
CCW CW
Set
value
A-phase
B-phase
A-phase
B-phase
0
1
A-phase
B-phase
A-phase
B-phase
Encoder output pulse setting selection
(Refer to parameter No. 27)
0: Output pulse designation
1: Division ratio setting
5 - 14
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
59 *OPA Function selection A
Used to select the alarm code.
0000
Refer to
Name
and
0 0
function
column.
Rotation direction in which torque limit is made valid
Setting
CCW direction
CW direction
0
1
2
Setting of alarm code output
Connector pins
CN1A-18
Set
value
CN1B-19
CN1A-19
0
1
Signals assigned to corresponding pins are output.
Alarm code is output at alarm occurrence.
(Note) Alarm code
Alarm
display
Name
CN1B
pin 19
CN1A
pin 19
CN1A
pin 18
88888 Watchdog
AL.12 Memory error 1
AL.13 Clock error
AL.15 Memory error 2
AL.17 Board error 2
AL.19 Memory error 3
AL.37 Parameter error
0
0
0
AL.8A
Serial communication time-out error
AL.8E Serial communication error
AL.30 Regenerative error
AL.33 Overvoltage
0
0
0
1
1
0
AL.10 Undervoltage
AL.45 Main circuit device overheat
AL.46 Servo motor overheat
AL.50 Overload 1
0
1
1
AL.51 Overload 2
AL.24 Main circuit
1
1
0
0
0
1
AL.32 Overcurrent
AL.31 Overspeed
AL.35 Command pulse frequency error
AL.52 Error excessive
AL.61 Home operation alarm
AL.16 Encoder error 1
AL.1A Motor combination error
AL.20 Encoder error 2
1
1
0
AL.25 Absolute position erase
Note: 0:Pin-SG off (open)
1:Pin-SG on (short)
5 - 15
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
60
61
For manufacturer setting
Do not change this value by any means.
0000
NH1 Machine resonance suppression filter 1
Used to selection the machine resonance suppression filter.
(Refer to section 9.1.)
0000
Refer to
Name
and
function
column.
0
Notch frequency selection
Set "00" when you have set adaptive vibration
suppression control to be "valid" or "held"
(parameter No. 63:
1
or
2
).
Setting
value
Setting
value
Setting
value
Setting
value
Frequency
Frequency
Frequency
Frequency
00
01
02
03
04
05
06
07
Invalid
4500
2250
1500
1125
900
08
562.5
500
10
11
12
13
14
15
16
17
281.3
264.7
250
18
187.5
180
09
19
0A
0B
0C
0D
0E
0F
450
1A
1B
1C
1D
1E
1F
173.1
166.7
160.1
155.2
150
409.1
375
236.8
225
346.2
321.4
300
214.3
204.5
195.7
750
642.9
145.2
Notch depth selection
Setting
Depth
Gain
value
0
1
40dB
Deep
to
14dB
2
3
8dB
4dB
Shallow
62
NH2 Machine resonance suppression filter 2
0000
Refer to
Name
Used to set the machine resonance suppression filter.
and
0
function
column.
Notch frequency
Same setting as in parameter No. 61
However, you need not set "00" if you have
set adaptive vibration suppression control to
be "valid" or "held".
Notch depth
Same setting as in parameter No. 61
5 - 16
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
63
LPF Low-pass filter/adaptive vibration suppression control
Used to selection the low-pass filter and adaptive vibration suppression
control. (Refer to chapter 9)
0000
Refer to
Name
and
function
column.
0
Low-pass filter selection
0: Valid (Automatic adjustment)
1: Invalid
When you choose "valid", the filter of the handwidth
represented by the following expression is set automatically.
For 1kW or less
VG2 setting 10
[Hz]
2
(1 GD2 setting 0.1)
For 2kW or more
VG2 setting
(1 GD2 setting 0.1)
5
[Hz]
2
Adaptive vibration suppression control selection
Choosing "valid" or "held" in adaptive vibration
suppression control selection makes the machine
resonance control filter 1 (parameter No. 61) invalid.
0: Invalid
1: Valid
Machine resonance frequency is always detected
and the filter is generated in response to resonance
to suppress machine vibration.
2: Held
The characteristics of the filter generated so far are held,
and detection of machine resonance is stopped.
Adaptive vibration suppression control sensitivity selection
Used to set the sensitivity of machine resonance detection.
0: Normal
1: Large sensitivity
64 GD2B Ratio of load inertia moment to servo motor inertia moment 2
Used to set the ratio of load inertia moment to servo motor inertia moment
when gain changing is valid.
70
0.1 0 to 3000
times
65 PG2B Position control gain 2 changing ratio
Used to set the ratio of changing the position control gain 2 when gain
changing is valid.
100
%
%
%
10 to 200
Made valid when auto tuning is invalid.
66 VG2B Speed control gain 2 changing ratio
Used to set the ratio of changing the speed control gain 2 when gain changing
is valid.
100
100
10 to 200
Made valid when auto tuning is invalid.
67
VICB Speed integral compensation changing ratio
50 to
1000
Used to set the ratio of changing the speed integral compensation when gain
changing is valid. Made valid when auto tuning is invalid.
5 - 17
5. PARAMETERS
Initial
value
Setting
range
Class No. Symbol
Name and Function
Unit
68 *CDP Gain changing selection
0000
Refer to
Name
Used to select the gain changing condition. (Refer to section 9.5)
and
0 0 0
function
column.
Gain changing selection
Gains are changed in accordance with the settings
of parameters No. 64 to 67 under any of the following
conditions:
0: Invalid
1: Gain changing (CDP) signal is ON
2: Command frequency is equal to higher than
parameter No. 69 setting
3: Droop pulse value is equal to higher than
parameter No. 69 setting
4: Servo motor speed is equal to higher than
parameter No. 69 setting
69
70
CDS Gain changing condition
10
1
kpps
pulse
r/min
10 to
9999
Used to set the value of gain changing condition (command frequency, droop
pulses, servo motor speed) selected in parameter No. 68. The set value unit
changes with the changing condition item. (Refer to section 9.5)
CDT Gain changing time constant
ms
0 to 100
Used to set the time constant at which the gains will change in response to the
conditions set in parameters No. 68 and 69.
(Refer to section 9.5)
71
72
73
74
75
76
77
78
79
80
81
82
83
84
85
86
87
88
89
90
For manufacturer setting
10
10000
10
Do not change this value by any means.
10
100
100
100
For manufacturer setting
0000
0009
080A
0706
020B
0504
0002
0000
0005
0D04
0102
0
The settings are automatically changed.
For manufacturer setting
Do not change this value by any means.
0
5 - 18
5. PARAMETERS
5.2 Detailed explanation
5.2.1 Electronic gear
False setting will result in unexpected fast rotation, causing injury.
POINT
CAUTION
This parameter is made valid when power is switched off, then on after
setting, or when the controller reset has been performed.
1
10
CMX
CDV
The range of the electronic gear setting is
. If you set
1000
any value outside this range, a parameter error (A37) occurs.
After setting the parameter No.4, 5 value, switch power off, then on to
make that setting valid.
(1) Concept of electronic gear
Use the electronic gear (parameters No.4, 5) to make adjustment so that the servo amplifier setting
matches the moving distance of the machine. Also, by changing the electronic gear value, the machine
can be moved at any multiplication ratio to the moving distance on the servo amplifier.
Motor
Parameter No. 4
Parameter No. 5
CMX
CDV
+
-
Deviation
counter
CMX
CDV
Encoder feedback pulses
Electronic gear
Parameters No. 4, 5
Encoder
The following examples are used to explain how to calculate the electronic gear value.
POINT
The following specification symbols are needed for electronic gear
calculation.
Pb : Ballscrew lead [mm(in.)]
n
: Reduction ratio
Pt : Servo motor resolution [pulse/rev]
S
: Travel per servo motor revolution [mm/rev]
(a) Ballscrew setting example
Machine specifications
n
n=NL/NM=1/2
NL
Ballscrew lead: Pb 10 (0.39) [mm(in.)]
Reduction ratio: n 1/2
Servo motor resolution: Pt 131072 [pulse/rev]
Pb=10(0.39)[mm(in.)]
NM
Servo motor 131072[pulse/rev]
pt
pb
pt
S
32768
1250
131072
1/2 10 1000
131072
5000
CMX
CDV
n
1000
Hence, set 32768 to CMX and 1250 to CDV.
r=160(6.30)[mm(in.)]
(b) Conveyor setting example
Machine specifications
Pulley diameter: r 160 (6.30) [mm(in.)]
Reduction ratio: n 1/3
Servo motor
131072[pulse/rev]
n
NL
NM
Servo motor resolution: Pt 131072 [pulse/rev]
n=NL/NM=1/3
pt
S
pt
131072
1/3 160
32768
41888
131072
167551.61
CMX
CDV
1000
n r
1000
Reduce CMX and CDV to the setting range or less, and round off the first decimal place.
Hence, set 32768 to CMX and 41888 to CDV.
5 - 19
5. PARAMETERS
5.2.2 Changing the status display screen
The status display item of the servo amplifier display and the display item of the external digital display
(MR-DP60) shown at power-on can be changed by changing the parameter No.18 (status display
selection) settings. In the initial condition, the servo amplifier display shows the servo motor speed and
the MR-DP60 shows the current position.
For display details, refer to section 7.2.
Parameter No. 18
Status display on servo amplifier display
at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Point table No.
04: Cumulative feedback pulses
05: Servo motor speed
06: Droop pulses
07: Override voltage
08: Analog torque limit voltage
09: Regenerative load ratio
0A: Effective load ratio
0B: Peak load ratio
0C: Instantaneous torque
0D: Within one-revolution position low
0E: Within one-revolution position high
0F: ABS counter
10: Load inertia moment ratio
11: Bus voltage
Status display of MR-DP60 at power-on
00: Current position (initial value)
01: Command position
02: Command remaining distance
03: Point table No.
04: Cumulative feedback pulses
05: Servo motor speed
06: Droop pulses
07: Override voltage
08: Analog torque limit voltage
09: Regenerative load ratio
0A: Effective load ratio
0B: Peak load ratio
0C: Instantaneous torque
0D: Within one-revolution position
0E: ABS counter
0F: Load inertia moment ratio
10: Bus voltage
5 - 20
5. PARAMETERS
5.2.3 S-pattern acceleration/deceleration
In servo operation, linear acceleration/deceleration is usually made. By setting the S-pattern
acceleration/deceleration time constant (parameter No.14), a smooth start/stop can be made. When the S-
pattern time constant is set, smooth positioning is executed as shown below. When the S-pattern
acceleration/deceleration time constant is set, the time from when the positioning starts until the
movement finish (MEND) is output will increase by the time equivalent to the S-pattern time constant
setting.
Acceleration time
constant
Deceleration time
constant
Rated
speed
Preset
speed
Servo motor
speed
0 [r/min]
Tb Ts
Tb
Ta
Ta Ts
Ta: Time until preset speed is reached
Tb: Time until stop
Ts: S-pattern acceleration/deceleration time constant
(parameter No. 14)
Setting range 0 to 100ms
5.2.4 Analog output
The servo status can be output to two channels in terms of voltage. The servo status can be monitored
using an ammeter.
(1) Setting
Change the following digits of parameter No.17.
Parameter No. 17
0
0
Analog monitor 1 (MO1) output selection
(Signal output to across MO1-LG)
Analog monitor 2 (MO2) output selection
(Signal output to across MO2-LG)
Parameters No.31 and 32 can be used to set the offset voltages to the analog output voltages. The
setting range is between 999 and 999mV.
Parameter
Parameter No.31
Parameter No.32
Description
Setting range [mV]
Used to set the offset voltage for the analog monitor 1 (MO1) output.
Used to set the offset voltage for the analog monitor 2 (MO2) output.
999 to 999
5 - 21
5. PARAMETERS
(2) Contents of a setting
The servo amplifier is factory-set to output the servo motor speed to analog monitor 1 and the torque
to analog monitor 2. The setting can be changed as listed below by changing the parameter No.17
(analog monitor output) value.
Refer to (3) for the measurement point.
Setting
Output item
Description
Setting
Output item
Description
CCW direction
CCW direction
0
Servo motor speed
6
Droop pulses (Note 1)
( 10V/128pulse)
10[V]
8[V]
128[pulse]
Max. speed
0
0
Max. speed
128[pulse]
-8[V]
-10[V]
CW direction
8[V]
CW direction
10[V]
CCW direction
1
2
3
4
5
Torque (Note 2)
Servo motor speed
Torque (Note 2)
Current command
Speed command
7
Droop pulses (Note 1)
Driving in CCW direction
( 10V/2048pulse)
2048[pulse]
Max. torque
0
0
2048[pulse]
Max. torque
-10[V]
-8[V]
Driving in CW direction
CW direction
10[V]
CCW direction
8
Droop pulses (Note 1)
CW
direction
CCW
direction
( 10V/8192pulse)
8[V]
8192[pulse]
0
8192[pulse]
Max. speed
0
Max. speed
-10[V]
CW direction
10[V]
CCW direction
9
Droop pulses (Note 1)
Driving in
CCW direction
Driving in
CW direction
( 10V/32768pulse)
8[V]
32768[pulse]
0
32768[pulse]
Max. torque
8[V]
Max. command
current
0
Max. torque
-10[V]
CW direction
10[V]
CCW direction
CCW direction
A
Droop pulses (Note 1)
( 10V/131072pulse)
131072[pulse]
0
0
Max. command
current
131072[pulse]
-8[V]
-10[V]
CW direction
8[V]
CW direction
8[V]
CCW direction
B
Bus voltage
Max. speed
0
Max. speed
0
400[V]
-8[V]
CW direction
Note 1. Encoder pulse unit.
2. 8V is outputted at the maximum torque. However, when parameter No. 28 29 are set to limit torque, 8V is outputted at the
torque highly limited.
5 - 22
5. PARAMETERS
Command
speed
Current
command
Droop pulse
Bus voltage
Speed
command
differentiation
Current encoder
M
Position
control
Current
control
Speed
control
Command
position
Servo Motor
Encoder
PWM
Current feedback
Differ-
ential
Position feedback
Servo Motor
speed
Torque
5 - 23
5. PARAMETERS
5.2.5 Changing the stop pattern using a limit switch
The servo amplifier is factory-set to make a sudden stop when the limit switch or software limit is made
valid. When a sudden stop is not required, e.g. when there is an allowance from the limit switch
installation position to the permissible moving range of the machine, a slow stop may be selected by
changing the parameter No.22 setting.
Parameter No. 22 setting
Description
0(initial value)
1
Droop pulses are reset to make a stop. (Sudden stop)
Droop pulses are drawn out to make a slow stop. (Slow stop)
5.2.6 Alarm history clear
The alarm history can be confirmed by using the MR Configurator (Set-up Software) or communication
function. The servo amplifier stores one current alarm and five past alarms from when its power is
switched on first. To control alarms which will occur during operation, clear the alarm history using
parameter No.16 (alarm history clear) before starting operation. Clearing the alarm history automatically
returns to “
0
”.
This parameter is made valid by switching power off, then on after setting.
Parameter No. 16
Alarm history clear
0: Invalid (not cleared)
1: Valid (cleared)
5.2.7 Rough match output
Rough match (CPO) is output when the command remaining distance reaches the value set in parameter
No. 12 (rough match output range). The set remaining distance is 0 to 65535 [ 10STM m].
Command remaining distance ( 10STM m)
set in parameter No. 12
Actual servo motor speed
Servo motor
Command pulse
speed
Rough match
(CPO)
ON
OFF
ON
OFF
In position (INP)
5.2.8 Software limit
A limit stop using a software limit is made as in stroke end operation. When a motion goes beyond the
setting range, the motor is stopped and servo-locked. This function is made valid at power-on but made
invalid during home position return. This function is made invalid when the software limit setting is
the same as the software limit
setting. A parameter error (AL. 37) will occur if the software limit
setting is less than the software limit setting.
Inhibited area
Unmovable
Movable area
Movable
Current position
Software limit
5 - 24
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
POINT
Some functions of the MR Configurator (servo configuration software)
may be unavailable for some versions. For details, please contact us.
The MR Configurator (servo configuration software) (MR2JW3-SETUP151E or more) uses the
communication function of the servo amplifier to perform parameter setting changes, graph display, test
operation, etc. on a personal computer.
6.1 Specifications
Item
Communication signal
Baud rate[bps]
System
Description
Conforms to RS-232C.
57600, 38400, 19200, 9600
Station selection
Batch display, high-speed display, graph display
Monitor
Alarm
Minimum resolution changes with the processing speed of the personal computer.
Alarm display, alarm history, data display at alarm occurrence
I/O display, function device display, no-rotation reason display, cumulative power-on time display,
software number display, motor information display, tuning data display, ABS data display, shaft
name setting.
Diagnostic
Parameters
Test operation
Advanced function
Parameter setting, list display, change list display, detailed display, turning, device setting.
Jog operation, positioning operation, motor-less operation, DO forced output, single-step feed.
Machine analyzer, gain search, machine simulation.
Position-Data
File operation
Others
Point Tables
Data read, save, print
Station setting, help display
6.2 System configuration
(1) Components
To use this software, the following components are required in addition to the servo amplifier and
servo motor.
Model
(Note 1) Description
IBM PC-AT compatible where the English version of Windows® 95, Windows® 98, Windows® Me, Windows
NT® Workstation 4.0, Windows® 2000 Professional, Windows® XP Professional or Windows® XP Home
Edition operates
Processor: Pentium® 133MHz or more (Windows® 95, Windows® 98, Windows NT® Workstation 4.0,
Windows® 2000 Professional)
(Note 2)
Personal
computer
Pentium® 150MHz or more (Windows® Me)
Pentium® 300MHz or more (Windows® XP Professional, Windows® XP Home Edition)
Memory: 16MB or more (Windows® 95), 24MB or more (Windows® 98)
32MB or more (Windows® Me, Windows NT® Workstation 4.0, Windows® 2000 Professional)
128MB or more (Windows® XP Professional, Windows® XP Home Edition)
Free hard disk space: 60MB or more
Serial port used
Windows® 95, Windows® 98, Windows® Me, Windows NT® Workstation 4.0, Windows® 2000 Professional,
Windows® XP Professional, Windows® XP Home Edition (English version)
One whose resolution is 800 600 or more and that can provide a high color (16 bit) display.
Connectable with the above personal computer.
OS
Display
Keyboard
Mouse
Connectable with the above personal computer.
Connectable with the above personal computer. Note that a serial mouse is not used.
Printer
Connectable with the above personal computer.
Communication MR-CPCATCBL3M
cable
When this cannot be used, refer to section 14.1.4 (3) and fabricate.
Note 1. Windows and Windows NT are the registered trademarks of Microsoft Corporation in the United State and other countries.
Pentium is the registered trademarks of Intel Corporation.
2. On some personal computers, this software may not run properly.
6 - 1
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(2) Configuration diagram
(a) For use of RS-232C
Servo amplifier
Personal computer
U
V
W
Communication cable
Servo motor
CN3
CN2
To RS-232C connector
(b) For use of RS-422
Up to 32 axes may be multidropped.
Servo amplifier
Personal computer
RS-232C/RS-422
(Note 1)
Communication cable
converter
Servo motor
CN3
CN2
(Axis 1)
To RS-232C
connector
Servo amplifier
Servo motor
CN3
CN2
(Axis 2)
Servo amplifier
Servo motor
CN3
CN2
(Axis 32)
Note. Refer to Section 15.1.1 for cable connections.
6 - 2
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.3 Station setting
Click “System” on the menu bar and click “Station Selection” on the menu.
When the above choices are made, the following window appears.
(1) Station number setting
Choose the station number in the combo box and click the “Station Settings” button to set the station
number.
POINT
This setting should be the same as the station number which has been set
in the parameter in the servo amplifier used for communication.
(2) Closing of the station setting window
Click the “Close” button to close the window.
6 - 3
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.4 Parameters
Click “Parameters” on the menu bar and click “Parameter List” on the menu.
When the above choices are made, the following window appears.
a)
b)
c)
d)
e)
f)
g)
i)
h)
(1) Parameter value write ( a) )
Click the parameter whose setting was changed and press the “Write” button to write the new
parameter setting to the servo amplifier.
(2) Parameter value verify ( b) )
Click the “Verify” button to verify all parameter values being displayed and the parameter values of
the servo amplifier.
6 - 4
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(3) Parameter value batch-read ( c) )
Click the “Read All” button to read and display all parameter values from the servo amplifier.
(4) Parameter value batch-write ( d) )
Click the “Write All” button to write all parameter values to the servo amplifier.
(5) Parameter change list display ( e) )
Click the “Change List” button to show the numbers, names, initial values and current values of the
parameters whose initial value and current value are different. In the offline mode, the parameter
change list is not shown.
(6) Parameter detail information ( f) )
Click the “Help” button or double-click the display field to show the detailed explanation of each
parameter.
(7) Parameter default value indication ( g) )
Click the “Set to default” button to show the initial value of each parameter.
(8) Parameter value change ( h) )
Choose the parameter to be changed, enter a new value into the “Parameter value” input field, and
press the enter key or Enter Data button.
(9) Parameter data file read
Used to read and display the parameter values stored in the file. Use the file selection window to read.
(10) Parameter value storage
Used to store all parameter values being displayed on the window into the specified file. Use the file
selection window to store.
(11) Parameter data list print
Used to print all parameter values being displayed on the window. Use the “File” menu on the menu
bar to print.
(12) Parameter list window closing ( i) )
Click the “Close” button to close the window. If the “Close” button is clicked without (1) parameter
value write or (4) parameter value batch-write being performed, the parameter value changed is
made invalid.
6 - 5
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.5 Point table
Click “Position-Data” on the menu bar and click “Point Tables” on the menu.
When the above choices are made, the following window appears.
a)
b)
c)
d)
h)
g)
f)
e)
(1) Point table data write ( a) )
Click the point table data changed and press the “Write” button to write the new point table data to the
servo amplifier.
(2) Point table data verify ( b) )
Click the “Verify” button to verify all data being displayed and the data of the servo amplifier.
6 - 6
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(3) Point table data batch-read ( c) )
Click the “Read All” button to read and display all point table data from the servo amplifier.
(4) Point table data batch-write ( d) )
Click the “Write All” button to write all point table data to the servo amplifier.
(5) Point table data insertion ( e) )
Click the “Insert Row” button to insert one block of data into the position before the point table No.
chosen. The blocks after the chosen point table No. are shifted down one by one.
(6) Point table data deletion ( f) )
Click the “Delete Row” button to delete all data in the point table No. chosen. The blocks after the
chosen point table No. are shifted up one by one.
(7) Point table data change ( g) )
Click the data to be changed, enter a new value into the “Setting” input field, and press the enter key
or Enter Data button.
(8) Point table data file read
Used to read and display the point table data stored in the file. Use the “File” menu on the menu bar to
read.
(9) Point table data storage
Used to store all point table data being displayed on the window into the specified file. Use the “File”
menu on the menu bar to store.
(10) Point table data list print
Used to print all point table data being displayed on the window. Use the “File” menu on the menu
bar to print.
(11) Point table data list window closing ( h) )
Click the “Close” button to close the window.
6 - 7
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.6 Device assignment method
POINT
When using the device setting, preset “000E” in parameter No. 19.
(1) How to open the setting screen
Click “Parameters” on the menu bar and click “Device setting” in the menu.
Making selection displays the following window.
Click “Yes” button reads and displays the function assigned to each pin from the interface unit and
extension IO unit.
Click “No” button displays the initial status of the interface unit and extension IO unit.
Click “Cancel” button terminates the processing.
Click “Yes” button or “No” button displays the following two windows.
6 - 8
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(2) Screen explanation
(a) DIDO device setting window screen
This is the device assignment screen of the servo amplifier displays the pin assignment status of
the servo amplifier.
a)
b)
d)
c)
1) Read of function assignment ( a) )
Click the “Read” button reads and displays all functions assigned to the pins from the servo
amplifier.
2) Write of function assignment ( b) )
Click the “Write” button writes all pins that are assigned the functions to the servo amplifier.
3) Verify of function assignment ( c) )
Click the “Verify” button verifies the function assignment in the servo amplifier with the device
information on the screen.
4) Initial setting of function assignment ( d) )
Click the “Set to Default” button initializes the function assignment.
6 - 9
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(b) DIDO function display window screen
This screen is used to select the device assigned to the pins.
The functions displayed below * and * are assignable.
a)
b)
Move the pointer to the place of the function to be assigned. Drag and drop it as-is to the pin you
want to assign in the DIDO device setting window.
1) Assignment checking, automatic ON setting ( a) )
Press this button to display the screen that shows the assignment list and enables auto ON
setting.
Refer to (4) of this section for more information.
2) Quitting
Click “Close” button to exit from the window. ( b) )
6 - 10
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(c) Function device assignment checking auto ON setting display
Click the “ / ” button in the DIDO function display window displays the following window.
a)
b)
c)
d)
e)
The assigned functions are indicated by
.
The functions assigned by auto ON are grayed. When you want to set auto ON to the function that
is enabled for auto ON, click the corresponding cell. Clicking it again disables auto ON.
1) Auto ON read of function assignment ( a) )
Click “Auto ON read” button reads the functions set for auto ON from the interface unit and
extension IO unit.
2) Auto ON write of function assignment ( b) )
Click “Auto ON write” button writes the functions currently set for auto ON to the interface unit
and extension IO unit.
3) Auto ON verify of function assignment ( c) )
Click “Auto ON verify” button verifies the current auto ON setting in the interface unit and
extension IO unit with the auto ON setting on the screen.
4) Auto ON initial setting of function assignment ( d) )
Click “Auto ON initial setting” button initializes the auto ON setting.
5) Quitting the function device assignment checking/auto ON setting window ( e) )
Click “Close” button exits from the window.
6 - 11
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7 Test operation
When confirming the machine operation in the test operation mode, use the
machine after checking that the safety mechanism such as the forced stop (EMG)
operates.
CAUTION
If any operational fault has occurred, stop operation using the forced stop (EMG).
6.7.1 Jog operation
POINT
For the program operation, refer to the manual of MR Configurator.
The servo motor will not operate if the forced stop (EMG), forward
rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device
setting to assign them as external input signals and turn ON across these
signals and SG. (Refer to section 6.6.)
When an alarm occurs, the JOG operation is automatically canceled.
Hold down the “Forward” or “Reverse” button to rotate the servo motor. Release the “Forward” or
“Reverse” button to stop.
Click “Test” on the menu bar and choose “Jog” on the menu.
When the above choices are made, the following window appears.
a)
c)
b)
d)
e)
f)
6 - 12
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(1) Servo motor speed setting ( a) )
Enter a new value into the “Motor speed” input field and press the enter key.
(2) Acceleration/deceleration time constant setting ( b) )
Enter a new value into the “Accel/decel time” input field and press the enter key.
(3) Servo motor start ( c), d) )
Hold down the “Forward” button to rotate the servo motor in the CCW rotation direction.
Hold down the “Reverse” button to rotate the servo motor in the CW rotation direction.
(4) Servo motor stop ( e) )
Release the “Forward” or “Reverse” button to stop the rotation of the servo motor.
(5) Jog operation window closing ( f) )
Click the “Close” button to cancel the jog operation mode and close the window.
6 - 13
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7.2 Positioning operation
POINT
The servo motor will not operate if the forced stop (EMG), forward
rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device
setting to assign them as external input signals and turn ON across these
signals and SG. (Refer to section 6.6.)
When an alarm occurs, the positioning operation is automatically
canceled.
Click the “Forward” or “Reverse” button to start and rotate the servo motor by the preset moving distance
and then stop.
Click “Test” on the menu bar and click “Positioning” on the menu.
When the above choices are made, the following window appears.
a)
d)
b)
e)
c)
f)
g)
6 - 14
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
(1) Servo motor speed setting ( a) )
Enter a new value into the “Motor speed” input field and press the enter key.
(2) Acceleration/deceleration time constant setting ( b) )
Enter a new value into the “Accel/decel time” input field and press the enter key.
(3) Moving distance setting ( c) )
Enter a new value into the “Move distance” input field and press the enter key.
(4) Servo motor start ( d), e) )
Click the “Forward” button to rotate the servo motor in the forward rotation direction.
Click the “Reverse” button to rotate the servo motor in the reverse rotation direction.
(5) Temporary stop of servo motor ( f) )
Click the “Pause” button to stop the servo motor temporarily.
(6) Positioning operation window closing ( g) )
Click the “Close” button to cancel the positioning operation mode and close the window.
6 - 15
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7.3 Motor-less operation
POINT
When this operation is used in an absolute position detection system, the
home position cannot be restored properly.
Without a servo motor being connected, the output signals are provided and the servo amplifier display
shows the status as if a servo motor is actually running in response to the external I/O signals.
The sequence of the host programmable controller can be checked without connection of a servo motor.
Click “Test” on the menu bar and click “Operation w/o Motor” on the menu.
When the above choices are made, the following window appears.
a)
b)
(1) Execution of motor-less operation ( a) )
Click “Start” to perform motor-less operation.
(2) Termination of motor-less operation ( b) )
Click “Close” to close the window.
(3) Cancel of motor-less operation
To cancel motor-less operation, switch off the power of the servo amplifier.
6 - 16
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7.4 Output signal (DO) forced output
POINT
When an alarm occurs, the DO forced output is automatically canceled.
Each servo amplifier output signal is forcibly switched on/off independently of the output condition of the
output signal.
Click “Test” on the menu bar and click “Forced Output” on the menu.
When the above choices are made, the following window appears.
a)
b)
c)
(1) Signal ON/OFF setting ( a), b) )
Choose the signal name or pin number and click the “ON” or “OFF” button to write the corresponding
signal status to the servo amplifier.
(2) DO forced output window closing ( c) )
Click the “Close” button to cancel the DO forced output mode and close the window.
6 - 17
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.7.5 Single-step feed
POINT
In the jog operation mode, do not rewrite data from the point table list
screen or the servo amplifier's front panel. Otherwise, the set values are
made invalid.
The servo motor will not operate if the forced stop (EMG), forward
rotation stroke end (LSP) and reverse rotation stroke end (LSN) are off.
Make automatic ON setting to turn on these devices or make device
setting to assign them as external input signals and turn ON across these
signals and SG. (Refer to section 6.6.)
Operation is performed in accordance with the preset point table No.
Click “Test” on the menu bar and click “Single-step Feed” on the menu.
When the above choices are made, the following window appears.
a)
b)
c)
d)
(1) Point table No. setting ( a) )
Enter the point table No. into the “Point table No.” input field and press the enter key.
(2) Servo motor start ( b) )
Click the “Start” button to rotate the servo motor.
(3) Temporary stop of servo motor ( c) )
Press the “Pause” button to stop the servo motor temporarily.
Click the “Start” button to resume rotation.
(4) Servo motor stop ( d) )
Click the “Pause” button again during a temporary stop of the servo motor to clear the remaining
moving distance.
(5) Single-step feed window closing ( e) )
Click the “Close” button to cancel the single-step feed mode and close the window.
6 - 18
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
6.8 Alarm history
Click “Alarms” on the menu bar and click “History” on the menu.
When the above choices are made, the following window appears.
(1) Alarm history display
The most recent six alarms are displayed. The smaller numbers indicate newer alarms.
(2) Alarm history clear
Click the “Clear” button to clear the alarm history stored in the servo amplifier.
(3) Closing of alarm history window
Click the “Close” button to close the window.
6 - 19
6. MR Configurator (SERVO CONFIGURATION SOFTWARE)
MEMO
6 - 20
7. DISPLAY AND OPERATION
7. DISPLAY AND OPERATION
7.1 Display flowchart
Use the display (5-digit, 7-segment LED) on the front panel of the servo amplifier for status display,
parameter setting, etc. Set the parameters before operation, diagnose an alarm, confirm external
sequences, and/or confirm the operation status. Press the "MODE" "UP" or "DOWN" button once to move
to the next screen. Refer to section 7.2 and later for the description of the corresponding display mode.
To refer to or set the expansion parameters 1, expansion parameters 2 and special parameters, make
them valid with parameter No.19 (parameter write disable).
Display mode transition
Initial screen
Function
Servo status display.
Reference
appears at power-on.
Section 7.2
Alarm display, external signal display, output
signal (DO) forced output, test operation,
software version display, VC automatic offset,
motor series ID display, motor type ID display,
encoder ID display
Status display
Diagnosis
Alarm
Section 7.3
Section 7.4
Section 7.5
Current alarm display, alarm history display,
parameter error No. display, point table error
No. display.
Display and setting of point table data.
Point table
button
MODE
Display and setting of basic parameters.
Display and setting of expansion parameters 1.
Display and setting of expansion parameters 2.
Display and setting of special parameters.
Basic parameter
Expansion parameter 1
Expansion parameter 2
Special parameter
Section 7.6
7 - 1
7. DISPLAY AND OPERATION
7.2 Status display
The servo status during operation is shown on the 5-digit, 7-segment LED display. Press the "UP" or
"DOWN" button to change display data as desired. When the required data is selected, the corresponding
symbol appears. Press the "SET" button to display its data. At only power-on, however, data appears after
the symbol of the status display selected in parameter No. 18 has been shown for 2[s].
The servo amplifier display shows the lower five digits of 16 data items such as the motor speed.
7.2.1 Display transition
After choosing the status display mode with the "MODE" button, pressing the "UP" or "DOWN" button
changes the display as shown below.
To Bus voltage
Current position
Regenerative load ratio
Effective load ratio
Peak load ratio
Command position
Command remaining
distance
Point table No.
Instantaneous torque
Within one-revolution
position low
Cumulative feedback
pulses
UP
DOWN
Within one-revolution
position high
Servo motor speed
Droop pulses
Override
ABS counter
Load inertia moment ratio
Bus voltage
Analog torque
limit voltage
To Current position
7 - 2
7. DISPLAY AND OPERATION
7.2.2 Display examples
The following table lists display examples.
Displayed data
Item
Status
Servo amplifier display
MR-DP60
Forward rotation
at 2500r/min
Servo motor
speed
Reverse rotation
at 3000r/min
Reverse rotation is indicated by " ".
Load inertia
moment
15.5 times
11252pulse
Multi-
revolution
counter
12566pulse
Lit
Negative value is indicated by the lit
decimal points in the upper four
digits.
7 - 3
7. DISPLAY AND OPERATION
7.2.3 Status display list
The following table lists the servo statuses that may be shown.
Display range
Status display Symbol
Unit
Description
Servo amplifier
MR-DP60
display
Current
PoS
10STM The current position from the machine home position of 0 is
mm displayed.
99999 to
99999
999999 to
999999
position
Command
position
10STM The command position is displayed.
mm
99999 to
99999
999999 to
999999
CPoS
Command
remaining
distance
The command remaining distance of the currently selected
point table is displayed.
10STM
mm
99999 to
99999
999999 to
999999
rn
Point table No.
PT
The point table No. being executed is displayed.
0 to 31
0 to 31
Feedback pulses from the servo motor encoder are counted
and displayed.
When the value exceeds 9999999, it returns to zero.
Press the "SET" button to reset the display value to zero.
Cumulative
feedback
pulses
99999 to
99999
999999 to
999999
C
r
pulse
The servo motor speed is displayed.
Servo motor
speed
5400 to
5400
5400 to
5400
r/min
pulse
"
" is added to the speed of the servo motor rotating in the
CW rotation.
The number of droop pulses in the deviation counter is
displayed.
99999 to
99999
999999 to
999999
Droop pulses
Override
E
"
" is added to the droop pulses in the CW rotation.
The displayed number of pulses is not yet multiplied by the
electronic gear value.
The override setting is displayed.
100% is displayed when override is invalid.
The voltage of the Analog torque limit (TLA) is displayed.
F
u
L
%
V
0 to 200
0 to 200
Analog torque
limit voltage
Regenerative
load ratio
0.00 to 10.00 0.00 to 10.00
The ratio of regenerative power to permissible regenerative
power is displayed in %.
%
0 to 100
0 to 300
0 to 100
0 to 300
The continuous effective load torque is displayed.
The effective value in the past 15 seconds is displayed
relative to the rated torque of 100%.
Effective load
ratio
J
b
%
%
%
The maximum torque generated during
acceleration/deceleration, etc.
The highest value in the past 15 seconds is displayed
relative to the rated torque of 100%.
Peak load ratio
0 to 300
0 to 400
0 to 300
0 to 400
Torque that occurred instantaneously is displayed.
The value of the torque that occurred is displayed in real
time relative to the rate torque of 100%.
Position within one revolution is displayed in encoder
pulses.
The value returns to 0 when it exceeds the maximum
number of pulses.
The value is incremented in the CCW direction of rotation.
The within one-revolution position is displayed in 100 pulse
increments of the encoder.
The value returns to 0 when it exceeds the maximum
number of pulses.
The value is incremented in the CCW direction of rotation.
Travel value from the home position in the absolute position
detection systems is displayed in terms of the absolute
position detectors counter value.
Instantaneous
torque
T
Within one-
revolution
position low
Cy1
pulse
0 to 99999
0 to 1310
(Note)
0 to 131071
Within one-
revolution
position high
100
pulse
Cy2
LS
32768 to
32767
32768 to
32767
ABS counter
rev
Load inertia
moment ratio
The estimated ratio of the load inertia moment to the servo
motor shaft inertia moment is displayed.
The voltage (across P-N) of the main circuit converter is
displayed.
dC
Pn
times
V
0.0 to 300.0
0 to 450
0.0 to 300.0
0 to 450
Bus voltage
Note. The MR-DP60 can display the status without dividing it into the high and low orders. The unit is [pulse].
7 - 4
7. DISPLAY AND OPERATION
7.3 Diagnosis mode
7.3.1 Display transition
After choosing the diagnosis mode with the "MODE" button, pressing the "UP" or "DOWN" button changes
the display as shown below.
To Teaching
Sequence
Software version Low
Software version High
For manufacturer setting
Motor series ID
External I/O signal display
Output signal (DO)
forced output
Test operation mode
Jog feed
UP
DOWN
Test operation mode
Positioning operation
Motor type ID
Encoder ID
Teaching
Test operation mode
Motorless operation
Test operation mode
Machine analyzer operation
To Sequence
7 - 5
7. DISPLAY AND OPERATION
7.3.2 Diagnosis mode list
Name
Display
Description
Not ready.
Indicates that the servo amplifier is being initialized or an alarm
has occurred.
Sequence
Ready.
Indicates that the servo was switched on after completion of
initialization and the servo amplifier is ready to operate.
Indicates the ON-OFF states of the external I/O signals.
The upper segments correspond to the input signals and the
lower segments to the output signals.
Lit: ON
External I/O signal
display
Refer to section 7.7.
Extinguished: OFF
The I/O signals can be changed using the MR Configurator (servo
configuration software).
The digital output signal can be forced on/off. (Refer to section
7.8)
Output signal (DO)
forced output
Jog operation can be performed when there is no command from
the external command device. (Refer to section 7.9.2)
Jog feed
The MR Configurator (servo configuration software MRZJW3-
SETUP151E) is required for positioning operation. This operation
cannot be performed from the operation section of the servo
amplifier.
Positioning operation can be performed once when there is no
command from the external command device.
Without connection of the servo motor, the servo amplifier
provides output signals and displays the status as if the servo
motor is running actually in response to the external input
signal. (Refer to section 7.9.4)
Positioning
operation
Test
operation
mode
Motorless
operation
Merely connecting the servo amplifier allows the resonance point
of the mechanical system to be measured.
The MR Configurator (servo configuration software MRZJW3-
SETUP151E or later) is required for machine analyzer operation.
Machine
analyzer
operation
Indicates the version of the software.
Software version Low
Software version High
Indicates the system number of the software.
Manufacturer setting screen. Do not perform operation on this
screen.
For manufacturer
setting
7 - 6
7. DISPLAY AND OPERATION
Name
Display
Description
Press the "SET" button to show the motor series ID of the servo
motor currently connected.
Motor series
For indication details, refer to the optional MELSERVO Servo
Motor Instruction Manual.
Press the "SET" button to show the motor type ID of the servo
motor currently connected.
Motor type
Encoder
For indication details, refer to the optional MELSERVO Servo
Motor Instruction Manual.
Press the "SET" button to show the encoder ID of the servo motor
currently connected.
For indication details, refer to the optional MELSERVO Servo
Motor Instruction Manual.
Pressing the "SET" button selects the teaching mode. Refer to
Section 7.10 for details.
Teaching
7 - 7
7. DISPLAY AND OPERATION
7.4 Alarm mode
The current alarm, past alarm history and parameter error are displayed. The lower 2 digits on the
display indicate the alarm number that has occurred or the parameter number in error. Display examples
are shown below.
7.4.1 Display transition
After choosing the alarm mode with the "MODE" button, pressing the "UP" or "DOWN" button changes the
display as shown below.
To Parameter error No.
Alarm history
(Fourth alarm in past)
Current alarm
Alarm history
(Last alarm)
Alarm history
(Fifth alarm in past)
UP
Alarm history
Alarm history
(Second alarm in past)
DOWN
(Sixth alarm in past)
Alarm history
(Third alarm in past)
Parameter error No.
To Current alarm
7 - 8
7. DISPLAY AND OPERATION
7.4.2 Alarm mode list
Name
Display
Description
Indicates no occurrence of an alarm.
Current alarm
Indicates the occurrence of overvoltage (AL.33).
Flickers at occurrence of the alarm.
Indicates that the last alarm is overload 1 (AL.50).
Indicates that the second alarm in the past is overvoltage
(AL.33).
Indicates that the third alarm in the past is undervoltage
(AL.10).
Alarm history
Indicates that the fourth alarm in the past is overspeed (AL.31).
Indicates that there is no fifth alarm in the past.
Indicates that there is no sixth alarm in the past.
Indicates no occurrence of parameter error.
Indicates that the data of parameter No. 1 is faulty.
Parameter error No.
Displayed when any of the set point table values exceeds the
setting range.
The display given on the left indicates an error in the position
data of point table No. 1.
P: Position data, d: Servo motor speed, A: Acceleration time
constant, b: Deceleration time constant, n: Dwell,
H: Auxiliary function
7 - 9
7. DISPLAY AND OPERATION
Functions at occurrence of an alarm
(1) Any mode screen displays the current alarm.
(2) Even during alarm occurrence, the other screen can be viewed by pressing the button in the operation
area. At this time, the decimal point in the fourth digit remains flickering.
(3) For any alarm, remove its cause and clear it in any of the following methods (for clearable alarms,
refer to section 11.2.1).
(a) Switch power OFF, then ON.
(b) Press the "SET" button on the current alarm screen.
(c) Turn on the reset (RES) signal.
(4) Use parameter No. 16 to clear the alarm history.
(5) Pressing "SET" on the alarm history display screen for 2s or longer shows the following detailed
information display screen. Note that this is provided for maintenance by the manufacturer.
(6) Press "UP" or "DOWN" to move to the next history.
7 - 10
7. DISPLAY AND OPERATION
7.5 Point table mode
You can set the target position, servo motor speed, acceleration time, deceleration time, dwell and auxiliary
function.
7.5.1 Point table transition
After choosing the point table mode with the "MODE" button, pressing the "UP" or "DOWN" button
changes the display as shown below.
Point table No. 1
Point table No. 2
UP
DOWN
Point table No. 30
Point table No. 31
7 - 11
7. DISPLAY AND OPERATION
7.5.2 Point table mode setting screen sequence
Press "SET" in the point table mode. The following screen appears.
Press "UP" or "DOWN" to move to the next screen.
Target position
Servo motor speed
Acceleration time constant
UP
Deceleration time constant
DOWN
Dwell
Auxiliary function
7 - 12
7. DISPLAY AND OPERATION
7.5.3 Operation method
(1) Setting of 5 or less-digit value
The following example provides the after-power-on operation procedure to set "1" in the auxiliary
function of point table No.1.
(Note)
Press MODE three times.
··········The point table No. appears.
Press UP or DOWN to choose point table No. 1.
Press SET once.
Press UP five times.
Press SET twice.
··········The setting of the specified point table No. flickers.
Press UP once.
··········The setting can be changed during flickering.
Use UP or DOWN to change the setting.
Press SET to enter the value.
Note. The example assumes that the status display screen that appears at power-on has been
set to the servo motor speed in parameter No. 18.
Press "UP" or "DOWN" after completion of the setting to return to the setting item screen. Further,
press "UP" and "DOWN" together to return to the point table No. display screen.
7 - 13
7. DISPLAY AND OPERATION
(2) Setting of 6 or more-digit value
The following example gives the after-power-on operation procedure to change the target value of
point table No.1 to "123456".
(Note)
Press MODE three times. Press UP or DOWN to choose point table No. 1.
Press SET once.
Press SET once.
Setting of lower 3 digits
Setting of upper 3 digits
Press MODE once.
Press SET once.
The screen flickers.
Press UP or DOWN to
change the setting.
Press SET once.
Enter the setting.
Press MODE once.
Note. The example assumes that the status display screen that appears at power-on has been
set to the servo motor speed in parameter No. 18.
Press "UP" or "DOWN" after completion of the setting to return to the setting item screen. Further,
press "UP" and "DOWN" together to return to the point table No. display screen.
7 - 14
7. DISPLAY AND OPERATION
7.6 Parameter mode
POINT
To use the expansion parameters, change the parameter No. 19 (parameter
write inhibit) value. (Refer to section 5.1.1)
7.6.1 Parameter mode transition
After choosing the corresponding parameter mode with the "MODE" button, pressing the "UP" or "DOWN"
button changes the display as shown below.
To status display mode
MODE
Expansion parameters 1
Expansion parameters 2
Special parameters
Basic parameters
Parameter No. 54
Parameter No. 55
Parameter No. 0
Parameter No. 1
Parameter No. 20
Parameter No. 21
Parameter No. 78
Parameter No. 79
UP
DOWN
Parameter No. 89
Parameter No. 90
Parameter No. 18
Parameter No. 19
Parameter No. 52
Parameter No. 53
Parameter No. 76
Parameter No. 77
The parameter whose abbreviation is marked is made valid by switching power off, then on after
*
changing its setting. (Refer to section 5.1.2)
7 - 15
7. DISPLAY AND OPERATION
7.6.2 Operation example
(1) Parameter of 5 or less digits
The following example shows the operation procedure performed after power-on to change the home
position setting method (Parameter No.8) into the data setting type. Press "MODE" to switch to the
basic parameter screen.
Press MODE four times. Select parameter No.8 with UP or DOWN.
The parameter number is displayed.
Press UP orDOWN to change the number.
Press SET twice.
The set value of the specified parameter number flickers.
Press UP twice.
During flickering, the set value can be changed.
Use UP orDOWN .
(
2: Data setting type)
Press SET to enter.
To shift to the next parameter, press the "UP" or "DOWN" button.
When changing the parameter No.8 (home position return type) setting, change its set value, then
switch power off once and switch it on again to make the new value valid.
7 - 16
7. DISPLAY AND OPERATION
(2) Signed 5-digit parameter
The following example gives the operation procedure to change the home position return position data
(parameter No. 42) to "-12345".
(Note)
Press MODE three times. Press UP or DOWN to choose parameter No. 42.
Press SET once.
Setting of lower 4 digits
Setting of upper 1 digits
Press MODE once.
Press SET once.
The screen flickers.
Press UP or DOWN to
change the setting.
Press SET once.
Enter the setting.
Press MODE once.
Note. The example assumes that the status display screen that appears at power-on has been
set to the servo motor speed in parameter No. 18.
When changing the parameter No. 42 setting, change its set value, then switch power off once and
switch it on again to make the new value valid.
7 - 17
7. DISPLAY AND OPERATION
7.7 External I/O signal display
The ON/OFF states of the digital I/O signals connected to the servo amplifier can be confirmed.
(1) Operation
Call the display screen shown after power-on.
Using the "MODE" button, show the diagnostic screen.
Press UP once.
External I/O signal display screen
(2) Display definition
The segments of the seven-segment LEDs correspond to the pins.
CN1A
19
CN1B CN1B
CN1B CN1B
CN1A CN1B
14
CN1B CN1B
17
CN1B
16
15
9
8
7
8
5
Input signals
Always lit
Output signals
CN1A
14
CN1B
18
CN1B CN1B
CN1B CN1A
CN1A
19
4
6
19
18
Lit: ON
Extinguished: OFF
The 7-segment LED shown above indicates ON/OFF.
Each segment at top indicates the input signal and each segment at bottom indicates the output
signal. The signals corresponding to the pins in the respective control modes are indicated below.
7 - 18
7. DISPLAY AND OPERATION
7.8 Output signal (DO) forced output
POINT
When the servo system is used in a vertical lift application, turning on the
electromagnetic brake interlock (MBR) after assigning it to pin CN1B-19
will release the electromagnetic brake, causing a drop. Take drop
preventive measures on the machine side.
The output signal can be forced on/off independently of the servo status. This function is used for output
signal wiring check, etc. This operation must be performed in the servo off state (SON off).
Call the display screen shown after power-on.
Using the "MODE" button, show the diagnostic screen.
Press UP twice.
Press SET for more than 2 seconds.
Switch on/off the signal below the lit segment.
Always lit
Indicates the ON/OFF of the output signal. The correspondences
between segments and signals are as in the output signals of the
external I/O signal display.
CN1A
14
CN1B CN1B CN1B CN1B CN1A CN1A
18 19 18 19
4
6
(Lit: ON, extinguished: OFF)
Press MODE once.
The segment above CN1A-pin 18 is lit.
Press UP once.
CN1A-pin 18 is switched on.
(CN1A-pin 18-SG conduct.)
Press DOWN once.
CN1A-pin 18 is switched off.
Press SET for more than 2 seconds.
7 - 19
7. DISPLAY AND OPERATION
7.9 Test operation mode
The test operation mode is designed to confirm servo operation and not to confirm
machine operation. In this mode, do not use the servo motor with the machine.
Always use the servo motor alone.
CAUTION
If any operational fault has occurred, stop operation using the forced stop (EMG) .
POINT
The test operation mode cannot be used in the absolute position detection
system. Use it after choosing "Incremental system" in parameter No. 1.
The MR Configurator (servo configuration software) is required to perform
positioning operation.
Test operation cannot be performed if the servo-on (SON) signal is not
turned OFF.
7.9.1 Mode change
Call the display screen shown after power-on. Choose jog operation/motor-less operation in the following
procedure. Using the "MODE" button, show the diagnostic screen.
Press UP three times.
Press UP five times.
Press SET for more
than 2s.
Press SET for more than 2s.
When this screen
appears, jog feed can
be performed.
When this screen is displayed,
motor-less operation can be
performed.
Flickers in the test operation mode.
7 - 20
7. DISPLAY AND OPERATION
7.9.2 Jog operation
Jog operation can be performed when there is no command from the external command device.
(1) Operation
Connect EMG-SG to start jog operation and connect VDD-COM to use the internal power supply.
Hold down the "UP" or "DOWN" button to run the servo motor. Release it to stop. When using the MR
Configurator (servo configuration software), you can change the operation conditions. The initial
conditions and setting ranges for operation are listed below.
Item
Initial setting
Setting range
0 to instantaneous permissible speed
0 to 50000
Speed [r/min]
Acceleration/deceleration time constant [ms]
200
1000
How to use the buttons is explained below.
Button
Description
Press to start CCW rotation.
Release to stop.
"UP"
Press to start CW rotation.
Release to stop.
"DOWN"
If the communication cable is disconnected during jog operation performed by using the MR
Configurator (servo configuration software), the servo motor will be decelerated to a stop.
(2) Status display
You can confirm the servo status during jog operation.
Pressing the "MODE" button in the jog operation-ready status calls the status display screen. With
this screen being shown, perform jog operation with the "UP" or "DOWN" button. Every time you press
the "MODE" button, the next status display screen appears, and on completion of a screen cycle,
pressing that button returns to the jog operation-ready status screen. For full information of the status
display, refer to section 7.2. In the test operation mode, you cannot use the "UP" and "DOWN" buttons
to change the status display screen from one to another.
(3) Termination of jog operation
To end the jog operation, switch power off once or press the "MODE" button to switch to the next
screen and then hold down the "SET" button for 2 or more seconds.
7 - 21
7. DISPLAY AND OPERATION
7.9.3 Positioning operation
POINT
The MR Configurator (servo configuration software) is required to perform
positioning operation.
Positioning operation can be performed once when there is no command from the external command
device.
(1) Operation
Connect EMG-SG to start positioning operation and connect VDD-COM to use the internal power
supply.
Pressing the "Forward" or "Reverse" button on the MR Configurator (servo configuration software)
starts the servo motor, which will then stop after moving the preset travel distance. You can change
the operation conditions on the MR Configurator (servo configuration software). The initial conditions
and setting ranges for operation are listed below.
Item
Travel distance [pulse]
Initial setting
10000
Setting range
0 to 9999999
Speed [r/min]
200
0 to instantaneous permissible speed
0 to 50000
Acceleration/deceleration time constant [ms]
1000
How to use the keys is explained below.
Key
Description
"Forward"
Click to start positioning operation CCW.
"Reverse"
Click to start positioning operation CW.
Click during operation to make a temporary stop. Clicking the
"Pause" button again erases the remaining distance.
To resume operation, press the button that was pressed to
start the operation.
"Pause"
If the communication cable is disconnected during positioning operation, the servo motor will come to
a sudden stop.
(2) Status display
You can monitor the status display even during positioning operation.
7 - 22
7. DISPLAY AND OPERATION
7.9.4 Motor-less operation
Without connecting the servo motor, you can provide output signals or monitor the status display as if the
servo motor is running in response to external input signals. This operation can be used to check the
sequence of a host programmable controller or the like.
(1) Operation
After turning off the signal across SON-SG, choose motor-less operation. After that, perform external
operation as in ordinary operation.
(2) Status display
You can confirm the servo status during motor-less operation.
Pressing the "MODE" button in the motor-less operation-ready status calls the status display screen.
With this screen being shown, perform motor-less operation. Every time you press the "MODE" button,
the next status display screen appears, and on completion of a screen cycle, pressing that button
returns to the motor-less operation-ready status screen. For full information of the status display,
refer to section 7.2. In the test operation mode, you cannot use the "UP" and "DOWN" buttons to
change the status display screen from one to another.
(3) Termination of motor-less operation
To terminate the motor-less operation, switch power off.
7 - 23
7. DISPLAY AND OPERATION
7.10 Teaching function
POINT
This function is available for the absolute value command system. It is not
available for the incremental value command system.
This function is enabled after a home position return.
After making sure that the servo motor has stopped, press the "SET"
button in the operation section or turn teach (TCH) ON and set the
position data.
Position data can be imported by pressing the "SET" button in the operation section or turning teach
(TCH) ON after moving the axis to the target position by JOG operation or manual pulse generator
operation.
7.10.1 Preparations for teaching
Press the "MODE" button to choose the diagnosis mode.
This screen displays the servo off status.
Press
Press
or
to switch to the teaching setting initial screen.
DOWN
UP
for 2s or longer to choose the teaching setting mode.
SET
The lower two digits flicker in the teaching setting mode.
Press UP or
to call the point table No. where position data will be set.
DOWN
For example, point table No. 2 is called here.
7 - 24
7. DISPLAY AND OPERATION
7.10.2 Position data setting method
When the preparations for teaching are over, set position data in the following procedure.
(1) When determining position data by JOG operation
1) Turn automatic/manual selection (MD0) OFF to choose the manual operation mode. (Refer to
section 4.3)
2) Turn forward rotation start (ST1) or reverse rotation start (ST2) ON to rotate the servo motor
until the target position is reached. (Refer to section 4.3.1)
3) When positioning is completed, press the "SET" button in the operation section or turn teach
(TCH) ON. This sets the address of positioning as the position data of the point table.
(2) When determining position data by manual pulse generator operation
1) Turn automatic/manual selection (MD0) OFF to choose the manual operation mode. (Refer to
section 4.3)
2) Turn the manual pulse generator to rotate the servo motor until the target position is reached.
(Refer to section 4.3.2)
3) When positioning is completed, press the "SET" button in the operation section or turn teach
(TCH) ON. This sets the address of positioning as the position data of the point table.
When the setting is completed correctly, the upper digits in the display section flicker as shown below.
Press
to complete this point table position setting.
SET
Press the "MODE" button on the flickering screen to return to the teaching initial screen.
7 - 25
7. DISPLAY AND OPERATION
MEMO
7 - 26
8. GENERAL GAIN ADJUSTMENT
8. GENERAL GAIN ADJUSTMENT
8.1 Different adjustment methods
8.1.1 Adjustment on a single servo amplifier
The gain adjustment in this section can be made on a single servo amplifier. For gain adjustment, first
execute auto tuning mode 1. If you are not satisfied with the results, execute auto tuning mode 2, manual
mode 1 and manual mode 2 in this order.
(1) Gain adjustment mode explanation
Parameter No. 3
setting
Estimation of load inertia
moment ratio
Automatically set
parameters
Gain adjustment mode
Manually set parameters
PG1 (parameter No. 7)
GD2 (parameter No. 34)
PG2 (parameter No. 35)
VG1 (parameter No. 36)
VG2 (parameter No. 37)
VIC (parameter No. 38)
PG1 (parameter No. 7)
PG2 (parameter No. 35)
VG1 (parameter No. 36)
VG2 (parameter No. 37)
VIC (parameter No. 38)
Auto tuning mode 1
(initial value)
Response level setting of
parameter No. 3
010
Always estimated
GD2 (parameter No. 34)
Response level setting of
parameter No. 3
Auto tuning mode 2
Manual mode 1
020
030
PG1 (parameter No. 7)
GD2 (parameter No. 34)
VG2 (parameter No. 37)
VIC (parameter No. 38)
PG1 (parameter No. 7)
GD2 (parameter No. 34)
PG2 (parameter No. 35)
VG1 (parameter No. 36)
VG2 (parameter No. 37)
VIC (parameter No. 38)
PG2 (parameter No. 35)
VG1 (parameter No. 36)
Fixed to parameter No.
34 value
Manual mode 2
040
000
GD2 (parameter No. 34)
PG2 (parameter No. 35)
VG2 (parameter No. 37)
VIC (parameter No. 38)
PG1 (parameter No. 7)
VG1 (parameter No. 36)
Interpolation mode
Always estimated
8 - 1
8. GENERAL GAIN ADJUSTMENT
(2) Adjustment sequence and mode usage
START
Usage
Yes
Used when you want to
match the position gain
(PG1) between 2 or more
axes. Normally not used for
other purposes.
Interpolation
made for 2 or more
axes?
Interpolation mode
Operation
No
Allows adjustment by merely
changing the response level
setting.
Auto tuning mode 1
Operation
First use this mode to make
adjustment.
Yes
No
Used when the conditions of
auto tuning mode 1 are not
met and the load inertia
moment ratio could not be
estimated properly, for
example.
OK?
OK?
Yes
No
Auto tuning mode 2
Operation
Yes
OK?
No
This mode permits
adjustment easily with three
gains if you were not satisfied
with auto tuning results.
Manual mode 1
Operation
Yes
OK?
You can adjust all gains
manually when you want to
do fast settling or the like.
No
Manual mode 2
END
8.1.2 Adjustment using MR Configurator (servo configuration software)
This section gives the functions and adjustment that may be performed by using the servo amplifier with
the MR Configurator (servo configuration software) which operates on a personal computer.
Function
Description
Adjustment
With the machine and servo motor
coupled, the characteristic of the
mechanical system can be measured by
giving a random vibration command from
the personal computer to the servo and
measuring the machine response.
You can grasp the machine resonance frequency and
determine the notch frequency of the machine
resonance suppression filter.
You can automatically set the optimum gains in
response to the machine characteristic. This simple
adjustment is suitable for a machine which has large
machine resonance and does not require much settling
time.
Machine analyzer
Executing gain search under to-and-fro
positioning command measures settling
characteristic while simultaneously
changing gains, and automatically
searches for gains which make settling
time shortest.
You can automatically set gains which make positioning
settling time shortest.
Gain search
Response at positioning settling of a
machine can be simulated from machine
analyzer results on personal computer.
You can optimize gain adjustment and command
pattern on personal computer.
Machine simulation
8 - 2
8. GENERAL GAIN ADJUSTMENT
8.2 Auto tuning
8.2.1 Auto tuning mode
The servo amplifier has a real-time auto tuning function which estimates the machine characteristic (load
inertia moment ratio) in real time and automatically sets the optimum gains according to that value. This
function permits ease of gain adjustment of the servo amplifier.
(1) Auto tuning mode 1
The servo amplifier is factory-set to the auto tuning mode 1.
In this mode, the load inertia moment ratio of a machine is always estimated to set the optimum gains
automatically.
The following parameters are automatically adjusted in the auto tuning mode 1.
Parameter No.
Abbreviation
PG1
Name
7
Position control gain 1
34
35
36
37
38
GD2
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
PG2
VG1
Speed control gain 1
VG2
Speed control gain 2
VIC
Speed integral compensation
POINT
The auto tuning mode 1 may not be performed properly if the following
conditions are not satisfied.
Time to reach 2000r/min is the acceleration/deceleration time constant of
5s or less.
Speed is 150r/min or higher.
The ratio of load inertia moment to motor inertia moment is not more than
100 times.
The acceleration/deceleration torque is 10% or more of the rated torque.
Under operating conditions which will impose sudden disturbance torque
during acceleration/deceleration or on a machine which is extremely loose,
auto tuning may not function properly, either. In such cases, use the auto
tuning mode 2 or manual mode 1,2 to make gain adjustment.
(2) Auto tuning mode 2
Use the auto tuning mode 2 when proper gain adjustment cannot be made by auto tuning mode 1.
Since the load inertia moment ratio is not estimated in this mode, set the value of a correct load
inertia moment ratio (parameter No. 34).
The following parameters are automatically adjusted in the auto tuning mode 2.
Parameter No.
Abbreviation
PG1
Name
7
Position control gain 1
Position control gain 2
Speed control gain 1
35
36
37
38
PG2
VG1
VG2
Speed control gain 2
VIC
Speed integral compensation
8 - 3
8. GENERAL GAIN ADJUSTMENT
8.2.2 Auto tuning mode operation
The block diagram of real-time auto tuning is shown below.
Load inertia
moment
Automatic setting
Encoder
Control gains
Command
Current
control
Servo
motor
PG1,VG1
PG2,VG2,VIC
Current feedback
Real-time auto
tuning section
Position/speed
feedback
Set 0 or 1 to turn on.
Load inertia
moment ratio
estimation section
Gain
table
Switch
Speed feedback
Parameter No. 34
Parameter No. 3
Load inertia moment
ratio estimation value
First digit
Response level setting
Auto tuning selection
Third digit
When a servo motor is accelerated/decelerated, the load inertia moment ratio estimation section always
estimates the load inertia moment ratio from the current and speed of the servo motor. The results of
estimation are written to parameter No. 34 (load inertia moment ratio). These results can be confirmed on
the status display screen of the servo amplifier display section.
If the value of the load inertia moment ratio is already known or if estimation cannot be made properly,
chose the "auto tuning mode 2" (parameter No.3 :
2
) to stop the estimation of the load inertia
moment ratio (Switch in above diagram turned off), and set the load inertia moment ratio (parameter No.
34) manually.
From the preset load inertia moment ratio (parameter No. 34) value and response level (The first digit of
parameter No. 3), the optimum control gains are automatically set on the basis of the internal gain tale.
The auto tuning results are saved in the EEP-ROM of the servo amplifier every 60 minutes since power-
on. At power-on, auto tuning is performed with the value of each control gain saved in the EEP-ROM
being used as an initial value.
POINT
If sudden disturbance torque is imposed during operation, the estimation of
the inertia moment ratio may malfunction temporarily. In such a case,
choose the "auto tuning mode 2" (parameter No. 3:
correct load inertia moment ratio in parameter No. 34.
2
) and set the
When any of the auto tuning mode 1, auto tuning mode 2 and manual mode
1 settings is changed to the manual mode 2 setting, the current control
gains and load inertia moment ratio estimation value are saved in the EEP-
ROM.
8 - 4
8. GENERAL GAIN ADJUSTMENT
8.2.3 Adjustment procedure by auto tuning
Since auto tuning is made valid before shipment from the factory, simply running the servo motor
automatically sets the optimum gains that match the machine. Merely changing the response level
setting value as required completes the adjustment. The adjustment procedure is as follows.
Auto tuning adjustment
Acceleration/deceleration repeated
Yes
Load inertia moment ratio
estimation value stable?
No
Auto tuning
conditions not satisfied.
(Estimation of load inertia
moment ratio is difficult)
No
Yes
Choose the auto tuning mode 2
(parameter No.3 :
2
) and set
the load inertia moment ratio
(parameter No.34) manually.
Adjust response level setting
so that desired response is
achieved on vibration-free level.
Acceleration/deceleration repeated
Requested
performance satisfied?
No
Yes
END
To manual mode
8 - 5
8. GENERAL GAIN ADJUSTMENT
8.2.4 Response level setting in auto tuning mode
Set the response (The first digit of parameter No.3) of the whole servo system. As the response level
setting is increased, the track ability and settling time for a command decreases, but a too high response
level will generate vibration. Hence, make setting until desired response is obtained within the vibration-
free range.
If the response level setting cannot be increased up to the desired response because of machine resonance
beyond 100Hz, adaptive vibration suppression control (parameter No. 63) or machine resonance
suppression filter (parameter No. 61 62) may be used to suppress machine resonance. Suppressing
machine resonance may allow the response level setting to increase. Refer to section 9.3 for adaptive
vibration suppression control and section 9.2 for machine resonance suppression filter.
Parameter No. 3
Response level setting
Auto tuning selection
Machine characteristic
Response level setting
Machine resonance
frequency guideline
Machine rigidity
Guideline of corresponding machine
1
2
Low
15Hz
20Hz
25Hz
30Hz
35Hz
45Hz
55Hz
70Hz
85Hz
105Hz
130Hz
160Hz
200Hz
240Hz
300Hz
3
Large conveyor
4
5
Arm robot
6
7
General machine
tool conveyor
8
Middle
9
Precision
working
machine
A
B
C
D
E
F
Inserter
Mounter
Bonder
High
8 - 6
8. GENERAL GAIN ADJUSTMENT
8.3 Manual mode 1 (simple manual adjustment)
If you are not satisfied with the adjustment of auto tuning, you can make simple manual adjustment with
three parameters.
8.3.1 Operation of manual mode 1
In this mode, setting the three gains of position control gain 1 (PG1), speed control gain 2 (VG2) and
speed integral compensation (VIC) automatically sets the other gains to the optimum values according to
these gains.
GD2
User setting
PG1
PG2
VG2
VG1
Automatic setting
VIC
Therefore, you can adjust the model adaptive control system in the same image as the general PI control
system (position gain, speed gain, speed integral time constant). Here, the position gain corresponds to
PG1, the speed gain to VG2 and the speed integral time constant to VIC. When making gain adjustment
in this mode, set the load inertia moment ratio (parameter No. 34) correctly.
8.3.2 Adjustment by manual mode 1
POINT
If machine resonance occurs, adaptive vibration suppression control
(parameter No. 63) or machine resonance suppression filter (parameter No.
61 62) may be used to suppress machine resonance. (Refer to section 9.2,
9.3.)
(1) For speed control
(a) Parameters
The following parameters are used for gain adjustment.
Parameter No.
Abbreviation
PG1
Name
7
Position control gain 1
34
37
38
GD2
Ratio of load inertia moment to servo motor inertia moment
Speed control gain 2
VG2
VIC
Speed integral compensation
(b) Adjustment procedure
Step
Operation
Description
Set an estimated value to the ratio of load inertia moment to servo motor
inertia moment (parameter No. 34).
Increase the speed control gain 2 (parameter No. 37) within the vibration- Increase the speed control gain.
and unusual noise-free range, and return slightly if vibration takes place.
Decrease the speed integral compensation (parameter No. 38) within the Decrease the time constant of the speed
vibration-free range, and return slightly if vibration takes place.
If the gains cannot be increased due to mechanical system resonance or
the like and the desired response cannot be achieved, response may be
increased by suppressing resonance with adaptive vibration suppression
control or machine resonance suppression filter and then executing steps
2 and 3.
1
2
3
integral compensation.
Suppression of machine resonance.
Refer to section 9.2, 9.3.
4
5
While checking the settling characteristic and rotational status, fine-
adjust each gain.
Fine adjustment
8 - 7
8. GENERAL GAIN ADJUSTMENT
(c) Adjustment description
1) Speed control gain 2 (parameter No. 37)
This parameter determines the response level of the speed control loop. Increasing this value
enhances response but a too high value will make the mechanical system liable to vibrate. The
actual response frequency of the speed loop is as indicated in the following expression.
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment)
Speed loop response
frequency(Hz)
2
2) Speed integral compensation (VIC: parameter No. 38)
To eliminate stationary deviation against a command, the speed control loop is under
proportional integral control. For the speed integral compensation, set the time constant of this
integral control. Increasing the setting lowers the response level. However, if the load inertia
moment ratio is large or the mechanical system has any vibratory element, the mechanical
system is liable to vibrate unless the setting is increased to some degree. The guideline is as
indicated in the following expression.
2000 to 3000
Speed integral compensation
setting(ms)
Speed control gain 2 setting/
(1 ratio of load inertia moment to
servo motor inertia moment setting 0.1)
(2) For position control
(a) Parameters
The following parameters are used for gain adjustment.
Parameter No.
Abbreviation
PG1
Name
7
Position control gain 1
34
37
38
GD2
Ratio of load inertia moment to servo motor inertia moment
Speed control gain 2
VG2
VIC
Speed integral compensation
(b) Adjustment procedure
Step
Operation
Description
Set an estimated value to the ratio of load inertia moment to servo motor
inertia moment (parameter No. 34).
1
2
3
Set a slightly smaller value to the position control gain 1 (parameter No.
7).
Increase the speed control gain 2 (parameter No. 37) within the vibration- Increase the speed control gain.
and unusual noise-free range, and return slightly if vibration takes place.
Decrease the speed integral compensation (parameter No. 38) within the Decrease the time constant of the speed
4
5
vibration-free range, and return slightly if vibration takes place.
Increase the position control gain 1 (parameter No. 7).
If the gains cannot be increased due to mechanical system resonance or
the like and the desired response cannot be achieved, response may be
increased by suppressing resonance with adaptive vibration suppression
control or machine resonance suppression filter and then executing steps
3 to 5.
integral compensation.
Increase the position control gain.
Suppression of machine resonance.
Refer to section 9.2, 9.3.
6
7
While checking the settling characteristic and rotational status, fine-
adjust each gain.
Fine adjustment
8 - 8
8. GENERAL GAIN ADJUSTMENT
(c) Adjustment description
1) Position control gain 1 (parameter No. 7)
This parameter determines the response level of the position control loop. Increasing position
control gain 1 improves track ability to a position command but a too high value will make
overshooting liable to occur at the time of settling.
1
3
1
5
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment)
Position control
gain 1 guideline
to
)
(
2) Speed control gain 2 (VG2: parameter No. 37)
This parameter determines the response level of the speed control loop. Increasing this value
enhances response but a too high value will make the mechanical system liable to vibrate. The
actual response frequency of the speed loop is as indicated in the following expression.
Speed control gain 2 setting
(1 ratio of load inertia moment to servo motor inertia moment)
Speed loop response
frequency(Hz)
2
3) Speed integral compensation (parameter No. 38)
To eliminate stationary deviation against a command, the speed control loop is under
proportional integral control. For the speed integral compensation, set the time constant of this
integral control. Increasing the setting lowers the response level. However, if the load inertia
moment ratio is large or the mechanical system has any vibratory element, the mechanical
system is liable to vibrate unless the setting is increased to some degree. The guideline is as
indicated in the following expression.
2000 to 3000
Speed integral
compensation setting(ms)
Speed control gain 2 setting/
(1 ratio of load inertia moment to
servo motor inertia moment 2 setting 0.1)
8 - 9
8. GENERAL GAIN ADJUSTMENT
8.4 Interpolation mode
The interpolation mode is used to match the position control gains of the axes when performing the
interpolation operation of servo motors of two or more axes for an X-Y table or the like. In this mode, the
position control gain 2 and speed control gain 2 which determine command track ability are set manually
and the other parameter for gain adjustment are set automatically.
(1) Parameter
(a) Automatically adjusted parameters
The following parameters are automatically adjusted by auto tuning.
Parameter No.
Abbreviation
GD2
Name
Ratio of load inertia moment to servo motor inertia moment
Position control gain 2
34
35
37
38
PG2
VG2
Speed control gain 2
VIC
Speed integral compensation
(b) Manually adjusted parameters
The following parameters are adjustable manually.
Parameter No.
Abbreviation
PG1
Name
7
Position control gain 1
Speed control gain 1
36
VG1
(2) Adjustment procedure
Step
Operation
Description
Set 15Hz (parameter No. 3: 010 ) as the machine resonance frequency of response
in the auto tuning mode 1.
1
2
Select the auto tuning mode 1.
During operation, increase the response level setting (parameter No. 2), and
return the setting if vibration occurs.
Adjustment in auto tuning mode 1.
Check the values of position control gain 1 (parameter No. 7) and speed control
gain 1 (parameter No. 36).
3
4
Check the upper setting limits.
Select the interpolation mode.
Set the interpolation mode (parameter No. 3: 000 ).
Set the position control gain 1 of all the axes to be interpolated to the same value.
5
At that time, adjust to the setting value of the axis, which has the smallest Set position control gain 1.
position control gain 1.
Using the speed control gain 1 value checked in step 3 as the guideline of the
upper limit, look at the rotation status and set in speed control gain 1 the value Set speed control gain 1.
three or more times greater than the position control gain 1 setting.
6
7
Looking at the interpolation characteristic and rotation status, fine-adjust the
Fine adjustment.
gains and response level setting.
(3) Adjustment description
(a) Position control gain 1 (parameter No.7)
This parameter determines the response level of the position control loop. Increasing position
control gain 1 improves track ability to a position command but a too high value will make
overshooting liable to occur at the time of settling. The droop pulse value is determined by the
following expression.
Rotation speed (r/min) 131,072(pulse)
Droop pulse value (pulse)
Position control gain 1 setting
(b) Speed control gain 1 (parameter No. 36)
Set the response level of the speed loop of the model. Make setting using the following expression
as a guideline.
Speed control gain 1 setting Position control gain 1 setting 3
8 - 10
8. GENERAL GAIN ADJUSTMENT
8.5 Differences in auto tuning between MELSERVO-J2 and MELSERVO-J2-Super
8.5.1 Response level setting
To meet higher response demands, the MELSERVO-J2-Super series has been changed in response level
setting range from the MELSERVO-J2 series. The following table lists comparison of the response level
setting.
Parameter No. 3
Response level setting
MELSERVO-J2 series
MELSERVO-J2-Super series
Response level setting
Machine resonance frequency
Response level setting
Machine resonance frequency guideline
1
2
15Hz
20Hz
25Hz
30Hz
35Hz
45Hz
55Hz
70Hz
85Hz
105Hz
130Hz
160Hz
200Hz
240Hz
300Hz
1
20Hz
3
4
5
2
40Hz
6
7
3
4
5
60Hz
80Hz
8
9
100Hz
A
B
C
D
E
F
Note that because of a slight difference in gain adjustment pattern, response may not be the same if the
resonance frequency is set to the same value.
8.5.2 Auto tuning selection
The MELSERVO-J2-Super series has an addition of the load inertia moment ratio fixing mode. It also has
the addition of the manual mode 1 which permits manual adjustment with three parameters.
Parameter No. 3
Auto tuning selection
Auto tuning selection
Gain adjustment mode
Remarks
MELSERVO-J2 series
MELSERVO-J2-Super series
Interpolation mode
Auto tuning mode 1
0
1
0
1
Position control gain 1 is fixed.
Ordinary auto tuning
Estimation of load inertia moment
ratio stopped.
Auto tuning
Auto tuning mode 2
2
Response level setting valid.
Simple manual adjustment
Manual adjustment of all gains
Auto tuning Manual mode 1
invalid
3
4
Manual mode 2
2
8 - 11
8. GENERAL GAIN ADJUSTMENT
MEMO
8 - 12
9. SPECIAL ADJUSTMENT FUNCTIONS
9. SPECIAL ADJUSTMENT FUNCTIONS
POINT
The functions given in this chapter need not be used generally. Use them
if you are not satisfied with the machine status after making adjustment
in the methods in chapter 8.
If a mechanical system has a natural resonance point, increasing the servo system response may cause
the mechanical system to produce resonance (vibration or unusual noise) at that resonance frequency.
Using the machine resonance suppression filter and adaptive vibration suppression control functions can
suppress the resonance of the mechanical system.
9.1 Function block diagram
Speed
control
Parameter
No.61
Parameter
No.63
Parameter
No.62
Parameter Current
No.63 command
00
0
00
0
Low-pass
filter
Servo
motor
Encoder
1
Machine resonance
suppression filter 1
Machine resonance
suppression filter 2
00
00
except
except
Adaptive vibration
suppression control
or
1
2
9.2 Machine resonance suppression filter
(1) Function
The machine resonance suppression filter is a filter function (notch filter) which decreases the gain of
the specific frequency to suppress the resonance of the mechanical system. You can set the gain
decreasing frequency (notch frequency) and gain decreasing depth.
Machine resonance point
Mechanical
system
response
Frequency
Notch
depth
Frequency
Notch frequency
9 - 1
9. SPECIAL ADJUSTMENT FUNCTIONS
You can use the machine resonance suppression filter 1 (parameter No. 61) and machine resonance
suppression filter 2 (parameter No. 62) to suppress the vibration of two resonance frequencies. Note
that if adaptive vibration suppression control is made valid, the machine resonance suppression filter
1 (parameter No. 61) is made invalid.
Machine resonance point
Mechanical
system
response
Frequency
Notch
depth
Frequency
Parameter No. 61 Parameter No. 62
POINT
The machine resonance suppression filter is a delay factor for the servo
system. Hence, vibration may increase if you set a wrong resonance
frequency or a too deep notch.
(2) Parameters
(a) Machine resonance suppression filter 1 (parameter No. 61)
Set the notch frequency and notch depth of the machine resonance suppression filter 1 (parameter
No. 61)
When you have made adaptive vibration suppression control selection (parameter No. 63) "valid" or
"held", make the machine resonance suppression filter 1 invalid (parameter No. 61: 0000).
Parameter No. 61
0
Notch frequency
Setting
value
Setting
value
Setting
value
Setting
value
Frequency
Frequency
Frequency
Frequency
562.5
500
10
11
12
13
14
15
16
17
281.3
264.7
250
18
19
187.5
180
00
01
02
03
04
05
06
07
Invalid
4500
2250
1500
1125
900
08
09
450
173.1
166.7
160.1
155.2
150
0A
0B
0C
0D
0E
0F
1A
1B
1C
1D
1E
1F
409.1
375
236.8
225
346.2
321.4
300
214.3
204.5
195.7
750
642.9
145.2
Notch depth
Setting
value
Depth (Gain)
Deep ( 40dB)
( 14dB)
0
1
2
3
( 8dB)
Shallow( 4dB)
9 - 2
9. SPECIAL ADJUSTMENT FUNCTIONS
POINT
If the frequency of machine resonance is unknown, decrease the notch
frequency from higher to lower ones in order. The optimum notch
frequency is set at the point where vibration is minimal.
A deeper notch has a higher effect on machine resonance suppression but
increases a phase delay and may increase vibration.
The machine characteristic can be grasped beforehand by the machine
analyzer on the MR Configurator (servo configuration software). This
allows the required notch frequency and depth to be determined.
Resonance may occur if parameter No. 61 62 is used to select a close
notch frequency and set a deep notch.
(b) Machine resonance suppression filter 2 (parameter No. 62)
The setting method of machine resonance suppression filter 2 (parameter No. 62) is the same as
that of machine resonance suppression filter 1 (parameter No. 61). However, the machine
resonance suppression filter 2 can be set independently of whether adaptive vibration suppression
control is valid or invalid.
9.3 Adaptive vibration suppression control
(1) Function
Adaptive vibration suppression control is a function in which the servo amplifier detects machine
resonance and sets the filter characteristics automatically to suppress mechanical system vibration.
Since the filter characteristics (frequency, depth) are set automatically, you need not be conscious of
the resonance frequency of a mechanical system. Also, while adaptive vibration suppression control is
valid, the servo amplifier always detects machine resonance, and if the resonance frequency changes,
it changes the filter characteristics in response to that frequency.
Machine resonance point
Machine resonance point
Mechanical
system
Mechanical
system
response
response
Frequency
Frequency
Notch
depth
Notch
depth
Frequency
Frequency
Notch frequency
Notch frequency
When machine resonance is large and frequency is low When machine resonance is small and frequency is high
POINT
The machine resonance frequency which adaptive vibration suppression
control can respond to is about 150 to 500Hz. Adaptive vibration
suppression control has no effect on the resonance frequency outside this
range. Use the machine resonance suppression filter for the machine
resonance of such frequency.
Adaptive vibration suppression control may provide no effect on a
mechanical system which has complex resonance characteristics or which
has too large resonance.
Under operating conditions in which sudden disturbance torque is imposed
during operation, the detection of the resonance frequency may malfunction
temporarily, causing machine vibration. In such a case, set adaptive
vibration suppression control to be "held" (parameter No. 63:
2
) to fix
the characteristics of the adaptive vibration suppression control filter.
9 - 3
9. SPECIAL ADJUSTMENT FUNCTIONS
(2) Parameters
The operation of adaptive vibration suppression control selection (parameter No.63).
Parameter No. 63
Adaptive vibration suppression control selection
Choosing "valid" or "held" in adaptive vibration suppression
control selection makes the machine resonance suppression
filter 1 (parameter No. 61) invalid.
0: Invalid
1: Valid
Machine resonance frequency is always detected to
generate the filter in response to resonance, suppressing
machine vibration.
2: Held
Filter characteristics generated so far is held, and detection of
machine resonance is stopped.
Adaptive vibration suppression control sensitivity selection
Set the sensitivity of detecting machine resonance.
0: Normal
1: Large sensitivity
POINT
Adaptive vibration suppression control is factory-set to be invalid
(parameter No. 63: 0000).
The filter characteristics generated are saved in the EEP-ROM every 60
minutes since power-on. At next power-on, vibration suppression control is
performed with this data saved in the EEP-ROM being used as an initial
value.
Setting the adaptive vibration suppression control sensitivity can change
the sensitivity of detecting machine resonance. Setting of "large sensitivity"
detects smaller machine resonance and generates a filter to suppress
machine vibration. However, since a phase delay will also increase, the
response of the servo system may not increase.
9.4 Low-pass filter
(1) Function
When a ballscrew or the like is used, resonance of high frequency may occur as the response of the
servo system is increased. To prevent this, the low-pass filter is factory-set to be valid for a torque
command. The filter frequency of this low-pass filter is automatically adjusted to the value in the
following expression.
Speed control gain 2 setting 10
Filter frequency(Hz)
(1 Ratio of load inertia moment to servo motor inertia moment setting 0.1)
2
(2) Parameter
Set the operation of the low-pass filter (parameter No. 63.)
Parameter No. 63
Low-pass filter selection
0: Valid (automatic adjustment) initial value
1: Invalid
POINT
In a mechanical system where rigidity is extremely high and resonance is
difficult to occur, setting the low-pass filter to be "invalid" may increase
the servo system response to shorten the settling time.
9 - 4
9. SPECIAL ADJUSTMENT FUNCTIONS
9.5 Gain changing function
This function can change the gains. You can change between gains during rotation and gains during stop
or can use an external signal to change gains during operation.
9.5.1 Applications
This function is used when.
(1) You want to increase the gains during servo lock but decrease the gains to reduce noise during rotation.
(2) You want to increase the gains during settling to shorten the stop settling time.
(3) You want to change the gains using an external signal to ensure stability of the servo system since the
load inertia moment ratio varies greatly during a stop (e.g. a large load is mounted on a carrier).
9.5.2 Function block diagram
The valid control gains PG2, VG2, VIC and GD2 of the actual loop are changed according to the conditions
selected by gain changing selection CDP (parameter No. 68) and gain changing condition CDS (parameter
No. 69).
CDP
Parameter No.68
External signal
CDP
Command pulse
frequency
Droop pulses
Changing
Model speed
Comparator
CDS
Parameter No.69
GD2
Parameter No.34
Valid
GD2
GD2 value
Parameter No.64
PG2
Parameter No.35
Valid
PG2 PG2B
100
PG2 value
VG2
Parameter No.37
Valid
VG2 VG2B
100
VG2 value
VIC
Parameter No.38
Valid
VIC VICB
100
VIC value
9 - 5
9. SPECIAL ADJUSTMENT FUNCTIONS
9.5.3 Parameters
When using the gain changing function, always set "
4
" in parameter No.3 (auto tuning) to choose
the manual mode of the gain adjustment modes. The gain changing function cannot be used in the auto
tuning mode.
Parameter Abbrev-
Name
Unit
Description
No.
7
iation
PG1
VG1
Position control gain 1
Speed control gain 1
rad/s Position and speed gains of a model used to set the response
level to a command. Always valid.
Control parameters before changing
36
rad/s
0.1
Ratio of load inertia moment to
servo motor inertia moment
Position control gain 2
Speed control gain 2
34
GD2
times
rad/s
rad/s
ms
35
37
38
PG2
VG2
VIC
Speed integral compensation
Ratio of load inertia moment to
servo motor inertia moment 2
Position control gain 2 changing
ratio
0.1
Used to set the ratio of load inertia moment to servo motor
64
65
66
GD2B
PG2B
VG2B
VICB
times inertia moment after changing.
Used to set the ratio (%) of the after-changing position
%
control gain 2 to position control gain 2.
Speed control gain 2 changing
ratio
Used to set the ratio (%) of the after-changing speed control
%
gain 2 to speed control gain 2.
Speed integral compensation
changing ratio
Used to set the ratio (%) of the after-changing speed integral
67
68
%
compensation to speed integral compensation.
CDP Gain changing selection
Used to select the changing condition.
kpps
pulse
r/min
Used to set the changing condition values.
69
70
CDS Gain changing condition
You can set the filter time constant for a gain change at
changing.
CDT Gain changing time constant
ms
9 - 6
9. SPECIAL ADJUSTMENT FUNCTIONS
(1) Parameters No. 7, 34 to 38
These parameters are the same as in ordinary manual adjustment. Gain changing allows the values of
ratio of load inertia moment to servo motor inertia moment, position control gain 2, speed control gain
2 and speed integral compensation to be changed.
(2) Ratio of load inertia moment to servo motor inertia moment 2 (GD2B: parameter No. 64)
Set the ratio of load inertia moment to servo motor inertia moment after changing. If the load inertia
moment ratio does not change, set it to the same value as ratio of load inertia moment to servo motor
inertia moment (parameter No. 34).
(3) Position control gain 2 changing ratio (parameter No. 65), speed control gain 2 changing ratio (parameter
No. 66), speed integral compensation changing ratio (parameter No. 67)
Set the values of after-changing position control gain 2, speed control gain 2 and speed integral
compensation in ratio (%). 100% setting means no gain change.
For example, at the setting of position control gain 2 100, speed control gain 2 2000, speed integral
compensation 20 and position control gain 2 changing ratio 180%, speed control gain 2 changing
ratio 150% and speed integral compensation changing ratio 80%, the after-changing values are as
follows.
Position control gain 2 Position control gain 2 Position control gain 2 changing ratio /100 180rad/s
Speed control gain 2 Speed control gain 2
Speed control gain 2 changing ratio /100 3000rad/s
Speed integral compensation Speed integral compensation Speed integral compensation changing
ratio /100 16ms
(4) Gain changing selection (parameter No. 68)
Used to set the gain changing condition. Choose the changing condition in the first digit. If you set "1"
here, you can use the gain changing (CDP) external input signal for gain changing. The gain changing
signal (CDP) can be assigned to the pins using the MR Configurator (servo configuration software).
Parameter No. 68
Gain changing selection
Gains are changed in accordance with the settings of
parameters No. 64 to 67 under any of the following conditions:
0: Invalid
1: Gain changing (CDP) input is ON
2: Command frequency is equal to higher than parameter No. 69 setting
3: Droop pulse value is equal to higher than parameter No. 69 setting
4: Servo motor speed is equal to higher than parameter No. 69 setting
(5) Gain changing condition (parameter No. 69)
When you selected "command frequency", "droop pulses" or "servo motor speed" in gain changing
selection (parameter No.68), set the gain changing level.
The setting unit is as follows.
Gain changing condition
Command frequency
Droop pulses
Unit
kpps
pulse
r/min
Servo motor speed
(6) Gain changing time constant (parameter No. 70)
You can set the primary delay filter to each gain at gain changing. This parameter is used to suppress
shock given to the machine if the gain difference is large at gain changing, for example.
9 - 7
9. SPECIAL ADJUSTMENT FUNCTIONS
9.5.4 Gain changing operation
This operation will be described by way of setting examples.
(1) When you choose changing by external input
(a) Setting
Parameter No.
Abbreviation
PG1
Name
Setting
100
Unit
rad/s
rad/s
7
Position control gain 1
Speed control gain 1
36
VG1
1000
Ratio of load inertia moment to
servo motor inertia moment
Position control gain 2
Speed control gain 2
34
GD2
40
0.1 times
35
37
38
PG2
VG2
VIC
120
3000
20
rad/s
rad/s
ms
Speed integral compensation
Ratio of load inertia moment to
servo motor inertia moment 2
Position control gain 2
changing ratio
64
65
66
67
GD2B
PG2B
VG2B
VICB
100
70
0.1 times
%
%
%
Speed control gain 2 changing
ratio
133
250
Speed integral compensation
changing ratio
0001
(Changed by ON/OFF of
pin CN1A-8)
100
68
70
CDP
CDT
Gain changing selection
Gain changing time constant
ms
(b) Changing operation
OFF
OFF
ON
Gain changing
(CDP)
After-changing gain
Before-changing gain
Change of
each gain
CDT 100ms
Position control gain 1
100
Speed control gain 1
1000
Ratio of load inertia moment
to servo motor inertia moment
Position control gain 2
4.0
10.0
4.0
120
3000
20
84
4000
50
120
3000
20
Speed control gain 2
Speed integral compensation
9 - 8
9. SPECIAL ADJUSTMENT FUNCTIONS
(2) When you choose changing by droop pulses
(a) Setting
Parameter No.
Abbreviation
PG1
Name
Setting
100
Unit
rad/s
rad/s
7
Position control gain 1
Speed control gain 1
36
VG1
1000
Ratio of load inertia moment to
servo motor inertia moment
Position control gain 2
Speed control gain 2
34
GD2
40
0.1 times
35
37
38
PG2
VG2
VIC
120
3000
20
rad/s
rad/s
ms
Speed integral compensation
Ratio of load inertia moment to
servo motor inertia moment 2
Position control gain 2
changing ratio
64
65
66
67
68
GD2B
PG2B
VG2B
VICB
CDP
100
70
0.1 times
%
%
%
Speed control gain 2 changing
ratio
133
250
Speed integral compensation
changing ratio
0003
Gain changing selection
(Changed by droop pulses)
69
70
CDS
CDT
Gain changing condition
50
pulse
ms
Gain changing time constant
100
(b) Changing operation
Command pulse
Droop pulses
CDS
CDS
Droop pulses [pulses]
0
After-changing gain
Before-changing gain
Change of each gain
CDT 100ms
Position control gain 1
100
Speed control gain 1
1000
Ratio of load inertia moment
4.0
10.0
4.0
10.0
to servo motor inertia moment
Position control gain 2
120
3000
20
84
4000
50
120
3000
20
84
4000
50
Speed control gain 2
Speed integral compensation
9 - 9
9. SPECIAL ADJUSTMENT FUNCTIONS
MEMO
9 - 10
10. INSPECTION
10. INSPECTION
Before starting maintenance and/or inspection, turn off the power and wait for 15
minutes or more until the charge lamp turns off. Then, confirm that the voltage
between P and N is safe with a voltage tester and others. Otherwise, an electric
shock may occur. In addition, always confirm from the front of the servo amplifier
whether the charge lamp is off or not.
WARNING
Any person who is involved in inspection should be fully competent to do the work.
Otherwise, you may get an electric shock. For repair and parts replacement,
contact your safes representative.
POINT
Do not test the servo amplifier with a megger (measure insulation
resistance), or it may become faulty.
Do not disassemble and/or repair the equipment on customer side.
(1) Inspection
It is recommended to make the following checks periodically.
(a) Check for loose terminal block screws. Retighten any loose screws.
(b) Check the cables and the like for scratches and cracks. Perform periodic inspection according to
operating conditions.
(2) Life
The following parts must be changed periodically as listed below. If any part is found faulty, it must be
changed immediately even when it has not yet reached the end of its life, which depends on the
operating method and environmental conditions. For parts replacement, please contact your sales
representative.
Part name
Life guideline
Smoothing capacitor
10 years
Number of power-on and number of forced
stop times : 100,000 times
Relay
Servo amplifier
Cooling fan
10,000 to 30,000hours (2 to 3 years)
Refer to section 4.5
Absolute position battery
(a) Smoothing capacitor
Affected by ripple currents, etc. and deteriorates in characteristic. The life of the capacitor greatly
depends on ambient temperature and operating conditions. The capacitor will reach the end of its
life in 10 years of continuous operation in normal air-conditioned environment.
(b) Relays
Their contacts will wear due to switching currents and contact faults occur. Relays reach the end of
their life when the cumulative number of power-on and forced stop times is 100,000, which depends
on the power supply capacity.
(c) Servo amplifier cooling fan
The cooling fan bearings reach the end of their life in 10,000 to 30,000 hours. Normally, therefore,
the cooling fan must be changed in a few years of continuous operation as a guideline.
It must also be changed if unusual noise or vibration is found during inspection.
10 - 1
10. INSPECTION
MEMO
10 - 2
11. TROUBLESHOOTING
11. TROUBLESHOOTING
11.1 Trouble at start-up
Excessive adjustment or change of parameter setting must not be made as it will
CAUTION
make operation instable.
POINT
Using the MR Configurator (servo configuration software), you can refer to
unrotated servo motor reasons, etc.
The following faults may occur at start-up. If any of such faults occurs, take the corresponding action.
No.
Start-up sequence
Fault
Investigation
Possible cause
Reference
1
Power on
LED is not lit.
LED flickers.
Not improved if connectors
1. Power supply voltage fault
CN1A, CN1B, CN2 and CN3 2. Servo amplifier is faulty.
are disconnected.
Improved when connectors
CN1A and CN1B are
disconnected.
Power supply of CN1 cabling is
shorted.
Improved when connector
CN2 is disconnected.
1. Power supply of encoder
cabling is shorted.
2. Encoder is faulty.
Power supply of CN3 cabling is
shorted.
Improved when connector
CN3 is disconnected.
Alarm occurs.
Alarm occurs.
Refer to section 11.2 and remove cause.
Refer to section 11.2 and remove cause.
Section 11.2
Section 11.2
2
Switch on servo-on
signal.
Servo motor shaft is 1. Check the display to see if 1. Servo-on signal is not input. Section 7.3.2
not servo-locked
(is free).
the servo amplifier is
ready to operate.
(Wiring mistake)
2. 24VDC power is not
supplied to COM.
2. Check the external I/O
signal indication to see if
the servo-on (SON) signal
is ON.
3
Gain adjustment
Rotation ripples
Make gain adjustment in the Gain adjustment fault
Chapter 7
(speed fluctuations) following procedure.
are large at low
speed.
1. Increase the auto tuning
response level.
2. Repeat acceleration and
deceleration several times
to complete auto tuning.
If the servo motor may be
Large load inertia
Gain adjustment fault
Chapter 7
moment causes the run with safety, repeat
servo motor shaft to acceleration and
oscillate side to side. deceleration several times to
complete auto tuning.
4
Cyclic operation
Position shift occurs Confirm the cumulative
Pulse counting error, etc.
command pulses, cumulative due to noise.
feedback pulses and actual
servo motor position.
11 - 1
11. TROUBLESHOOTING
11.2 When alarm or warning has occurred
POINT
Configure up a circuit which will detect the trouble (ALM) signal and turn
off the servo-on (SON) signal at occurrence of an alarm.
11.2.1 Alarms and warning list
When a fault occurs during operation, the corresponding alarm or warning is displayed. If any alarm or
warning has occurred, refer to section 11.2.2 or 11.2.3 and take the appropriate action.
Set "1
" in parameter No. 59 to output the alarm code in ON/OFF status across the corresponding
pin and SG. Warnings (AL.90 to AL.E9) have no alarm codes. Any alarm code is output at occurrence of
the corresponding alarm. In the normal status, the signals available before alarm code setting (CN1B-19,
CN1A-18, CN1A-19) are output.
After its cause has been removed, the alarm can be deactivated in any of the methods marked
alarm deactivation column.
in the
(Note 2) Alarm code
Alarm deactivation
Press
"SET" on
current
alarm
screen.
Alarm
Display
Name
CN1B-19
CN1A-18
pin
CN1A-19
Power
OFF ON
reset
(RES)
signal
pin
pin
AL.10
AL.12
AL.13
AL.15
AL.16
AL.17
AL.19
AL.1A
AL.20
AL.24
AL.25
AL.30
AL.31
AL.32
AL.33
AL.35
AL.37
AL.45
AL.46
AL.50
AL.51
AL.52
AL.61
AL.8A
AL.8E
88888
AL.90
AL.92
AL.96
AL.98
AL.9F
AL.E0
AL.E1
AL.E3
AL.E6
AL.E9
0
0
0
0
1
0
0
1
1
1
1
0
1
1
0
1
0
0
0
0
0
1
1
0
0
0
1
0
0
0
1
0
0
1
1
0
1
0
0
0
0
0
0
1
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
0
1
1
0
1
1
1
1
1
1
0
0
0
Undervoltage
Memory error 1
Clock error
Memory error 2
Encoder error 1
Board error
Memory error 3
Motor combination error
Encoder error 2
Main circuit error
Absolute position erase
Regenerative error
Overspeed
Overcurrent
Overvoltage
Command pulse frequency error
Parameter error
Main circuit device overheat
Servo motor overheat
Overload 1
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
(Note 1)
Overload 2
Error excessive
Home operation alarm
Serial communication time-out error
Serial communication error
Watchdog
Home position return incomplete
Open battery cable warning
Home position setting warning
Software limit warning
Battery warning
Excessive regenerative warning
Overload warning
Absolute position counter warning
Servo forced stop warning
Main circuit off warning
Removing the cause of occurrence
deactivates the alarm
automatically.
Note 1. Deactivate the alarm about 30 minutes of cooling time after removing the cause of occurrence.
2. 0: Pin-SG off (open)
1: Pin-SG on (short)
11 - 2
11. TROUBLESHOOTING
11.2.2 Remedies for alarms
When any alarm has occurred, eliminate its cause, ensure safety, then reset the
alarm, and restart operation. Otherwise, injury may occur.
If an absolute position erase alarm (AL.25) occurred, always make home position
setting again. Otherwise, misoperation may occur.
CAUTION
POINT
When any of the following alarms has occurred, always remove its cause
and allow about 30 minutes for cooling before resuming operation. If
operation is resumed by switching control circuit power off, then on to reset
the alarm, the servo amplifier and servo motor may become faulty.
Regenerative error (AL.30)
Overload 1 (AL.50)
Overload 2 (AL.51)
The alarm can be deactivated by switching power off, then on press the
"SET" button on the current alarm screen or by turning on the reset (RES).
For details, refer to section 11.2.1.
When an alarm occurs, the trouble (ALM) switches off and the dynamic is operated to stop the servo
motor. At this time, the display indicates the alarm No.
The servo motor comes to a stop. Remove the cause of the alarm in accordance with this section. The
optional MR Configurator (servo configuration software) may be used to refer to the cause.
Display
Name
Definition
Cause
Action
Power supply
voltage dropped.
MR-J2S- CP:
160VAC or less
MR-J2S- CP1:
83VAC or less
1. Power supply voltage is low.
2. There was an instantaneous
control power failure of 60ms or
longer.
3. Shortage of power supply capacity
caused the power supply voltage to
drop at start, etc.
Review the power supply.
AL.10 Undervoltage
4. The bus voltage dropped to the
folllowing value or less.
MR-J2S- CP: 200VDC
MR-J2S- CP1: 158VDC
5. Faulty parts in the servo amplifier
Change the servo amplifier.
Change the servo amplifier.
Change the servo amplifier.
Checking method
Alarm (AL.10) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
Faulty parts in the servo amplifier
Checking method
Alarm (any of AL.12 and 13)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
AL.12 Memory error 1 RAM, memory fault
AL.13 Clock error Printed board fault
1. Faulty parts in the servo amplifier
Checking method
AL.15 Memory error 2 EEP-ROM fault
Alarm (AL.15)
occurs if power is switched on
after disconnection of all cables
but the control circuit power
supply cables.
2. The number of write times to EEP-
ROM exceeded 100,000.
1. Encode connector (CN2)
disconnected.
AL.16 Encoder error 1 Communication
error occurred
Connect correctly.
between encoder
and servo amplifier.
2. Encoder fault
3. Encoder cable faulty
(wire breakage or short)
Change the servo motor.
Repair or change the cable.
11 - 3
11. TROUBLESHOOTING
Display
Name
Definition
Cause
Action
AL.17
Board error
CPU/parts fault
1. Faulty parts in the servo amplifier. Change the servo amplifier.
Checking method
Alarm (AL.17) occurs if power is
switched on after disconnection
of all cable but the control circuit
power supply cable.
The output terminals 2. The wiring of U, V, W is
Correctly connect the output terminals U,
V, W of the servo amplifier and the input
terminals U, V, W of the servo motor.
U, V, W of the servo
amplifier and the
disconnected or not connected.
input terminals U, V,
W of the servo motor
are not connected.
AL.19
Memory error 3 ROM memory fault Faulty parts in the servo amplifier.
Checking method
Change the servo amplifier.
Alarm (AL.19) occurs if power is
switched on after disconnection
of all cable but the control circuit
power supply cable.
AL.1A Motor
combination
error
Wrong combination Wrong combination of servo amplifier Use correct combination.
of servo amplifier
and servo motor connected.
and servo motor.
AL.20 Encoder error 2 Communication
1. Encoder connector (CN2)
disconnected.
2. Encoder fault
3. Encoder cable faulty
(wire breakage or shorted)
Connect correctly.
error occurred
between encoder and
servo amplifier.
Change the servo motor.
Repair or change the cable.
Encoder detected
acceleration error.
1. Decrease the speed control gain 2.
2. Decrease the auto tuning response level.
4. Excessive acceleration is occurred
due to oscillation and others.
AL.24 Main circuit
error
Ground fault
1. Power input wires and servo motor Connect correctly.
occurred at the servo
motor outputs (U,V
and W phases) of the
servo amplifier.
output wires are in contact at main
circuit terminal block (TE1).
2. Sheathes of servo motor power
cables deteriorated, resulting in
ground fault.
Change the cable.
3. Main circuit of servo amplifier
failed.
Change the servo amplifier.
Checking method
AL.24 occurs if the servo is
switched on after disconnecting
the U, V, W power cables from
the servo amplifier.
AL.25 Absolute
Absolute position
1. Reduced voltage of super capacitor After leaving the alarm occurring for a few
position erase data in error
in encoder
minutes, switch power off, then on again.
Always make home position setting again.
Change battery.
2. Battery voltage low
Always make home position setting again.
3. Battery cable or battery is faulty.
Power was switched 4. Super capacitor of the absolute
After leaving the alarm occurring for a few
minutes, switch power off, then on again.
Always make home position setting again.
on for the first time
in the absolute
position detection
system.
position encoder is not charged
11 - 4
11. TROUBLESHOOTING
Display
Name
Definition
Permissible
regenerative power
of the built-in
regenerative resistor
or regenerative
option is exceeded.
Cause
Action
AL.30 Regenerative
error
1. Wrong setting of parameter No. 0 Set correctly.
2. Built-in regenerative resistor or
regenerative option is not
connected.
3. High-duty operation or continuous 1. Reduce the frequency of positioning.
regenerative operation caused the 2. Use the regenerative option of larger
permissible regenerative power of
the regenerative option to be
exceeded.
Connect correctly
capacity.
3. Reduce the load.
Checking method
Call the status display and check
the regenerative load ratio.
4. Power supply voltage is abnormal.
MR-J2S- CP:260VAC or more
MR-J2S- CP1:135VAC or more
5. Built-in regenerative resistor or
regenerative option faulty.
Review power supply
Change servo amplifier or regenerative
option.
Regenerative
transistor fault
Change the servo amplifier.
6. Regenerative transistor faulty.
Checking method
1) The regenerative option has
overheated abnormally.
2) The alarm occurs even after
removal of the built-in
regenerative resistor or
regenerative option.
AL.31 Overspeed
Speed has exceeded 1. Input command pulse frequency
Set command pulses correctly.
the instantaneous
permissible speed.
exceeded the permissible
instantaneous speed frequency.
2. Small acceleration/deceleration
Increase acceleration/deceleration time
time constant caused overshoot to constant.
be large.
3. Servo system is instable to cause
overshoot.
1. Re-set servo gain to proper value.
2. If servo gain cannot be set to proper
value.
1) Reduce load inertia moment ratio; or
2) Reexamine acceleration/
deceleration time constant.
Set correctly.
4. Electronic gear ratio is large
(parameters No. 4, 5)
5. Encoder faulty.
Change the servo motor.
11 - 5
11. TROUBLESHOOTING
Display
Name
Definition
Cause
Action
Correct the wiring.
AL.32 Overcurrent
Current that flew is 1. Short occurred in servo amplifier
higher than the
output phases U, V and W.
2. Transistor (IPM) of the servo
amplifier faulty.
permissible current
of the servo
Change the servo amplifier.
amplifier. (If the
alarm (AL.32) occurs
again when turning
ON the servo after
resetting the alarm
by turning OFF/ON
the power when the
alarm (AL.32) first
occurred, the
Checking method
Alarm (AL.32) occurs if power is
switched on after U,V and W
are disconnected.
3. Ground fault occurred in servo
amplifier output phases U, V and
W.
Correct the wiring.
4. External noise caused the
overcurrent detection circuit to
misoperate.
Take noise suppression measures.
transistor (IPM,
IGBT) of the servo
amplifier may be at
fault. In the case, do
not repeat to turn
OFF/ON the power.
Check the transistor
with the checking
method of “Cause
2”.)
Converter bus
voltage exceeded
400VDC.
AL.33 Overvoltage
1. Regenerative option is not used.
Use the regenerative option.
2. Though the regenerative option is Make correct setting.
used, the parameter No. 0 setting
is "
0
(not used)".
3. Lead of built-in regenerative
resistor or regenerative option is
open or disconnected.
1. Change lead.
2. Connect correctly.
4. Regenerative transistor faulty.
5. Wire breakage of built-in
regenerative resistor or
Change servo amplifier
1. For wire breakage of built-in
regenerative resistor, change servo
amplifier.
regenerative option
2. For wire breakage of regenerative
option, change regenerative option.
Add regenerative option or increase
capacity.
6. Capacity of built-in regenerative
resistor or regenerative option is
insufficient.
7. Power supply voltage high.
Review the power supply.
8. The jumper across BUE-SD of the Fit the jumper across BUE-SD.
FR-BU2 brake unit is removed.
Input pulse
AL.35 Command pulse
frequency error
1. Pulse frequency of the manual
pulse generator is too high.
Change the pulse frequency to a proper
frequency of the
command pulse is
too high.
value.
2. Noise entered the pulses of the
manual pulse generator.
Take action against noise.
3. Manual pulse generator failure
Change the manual pulse generator.
11 - 6
11. TROUBLESHOOTING
Display
Name
Definition
Parameter setting is 1. Servo amplifier fault caused the
wrong. parameter setting to be rewritten.
Cause
Action
AL.37 Parameter
error
Change the servo amplifier.
2. Regenerative option not used with Set parameter No.0 correctly.
servo amplifier was selected in
parameter No.0.
3. Value outside setting range has
been set in some parameter.
4. Value outside setting range has
been set in electronic gear.
5. Opposite sign has been set in
software limit increasing side
(parameters No. 46, 47). Similarly,
opposite sign has been set in
software limit decreasing side
(parameters No. 48, 49).
Set the parameter correctly.
Set parameters No. 4, 5 correctly.
Set parameters No. 46 to 49 correctly.
6. Opposite sign has been set in
position range output address
increasing side (parameters No. 50,
51). Similarly, opposite sign has
been set in position range output
address decreasing side
Set parameters No. 50 to 53 correctly.
(parameters No. 52, 53).
7. The number of write times to EEP- Change the servo amplifier.
ROM exceeded 100,000 due to
parameter write, program write,
etc.
AL.45 Main circuit
Main circuit device 1. Servo amplifier faulty.
Change the servo amplifier.
The drive method is reviewed.
device overheat overheat
2. The power supply was turned on
and off continuously by overloaded
status.
3. Air cooling fan of servo amplifier
stops.
1. Exchange the cooling fan or the servo
amplifier.
2. Reduce ambient temperature.
Review environment so that ambient
temperature is 0 to 40 (32 to 104 ).
1. Reduce load.
2. Review operation pattern.
3. Use servo motor that provides larger
output.
AL.46 Servo motor
overheat
Servo motor
temperature rise
actuated the
1. Ambient temperature of servo
motor is over 40 (104 ).
2. Servo motor is overloaded.
thermal sensor.
3. Thermal sensor in encoder is faulty. Change servo motor.
1. Servo amplifier is used in excess of 1. Reduce load.
AL.50 Overload 1
Load exceeded
overload protection
characteristic of
servo amplifier.
its continuous output current.
2. Review operation pattern.
3. Use servo motor that provides larger
output.
2. Servo system is instable and
hunting.
1. Repeat acceleration/
deceleration to execute auto tuning.
2. Change auto tuning response setting.
3. Set auto tuning to OFF and make gain
adjustment manually.
3. Machine struck something.
1. Review operation pattern.
2. Install limit switches.
4. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's
input terminals U, V, W.
Connect correctly.
5. Encoder faulty.
Change the servo motor.
Checking method
When the servo motor shaft is
rotated with the servo off, the
cumulative feedback pulses do
not vary in proportion to the
rotary angle of the shaft but the
indication skips or returns midway.
11 - 7
11. TROUBLESHOOTING
Display
Name
Definition
Cause
Action
AL.51 Overload 2
Machine collision or 1. Machine struck something.
the like caused max.
1. Review operation pattern.
2. Install limit switches.
Connect correctly.
For the time of the
alarm occurrence,
refer to the section
13.1.
2. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's
input terminals U, V, W.
3. Servo system is instable and
hunting.
1. Repeat acceleration/deceleration to
execute auto tuning.
2. Change auto tuning response setting.
3. Set auto tuning to OFF and make gain
adjustment manually.
4. Encoder faulty.
Checking method
Change the servo motor.
When the servo motor shaft is
rotated with the servo off, the
cumulative feedback pulses do
not vary in proportion to the
rotary angle of the shaft but the
indication skips or returns midway.
AL.52 Error excessive The difference
between the model
position and the
1. Acceleration/deceleration time
constant is too small.
2. Internal torque limit 1 (parameter Increase the torque limit value.
No.28) is too small.
3. Motor cannot be started due to
torque shortage caused by power
supply voltage drop.
Increase the acceleration/deceleration
time constant.
actual servo motor
position exceeds 2.5
rotations. (Refer to
the function block
diagram in section
1.1.1)
1. Review the power supply capacity.
2. Use servo motor which provides larger
output.
4. Position control gain 1 (parameter Increase set value and adjust to ensure
No.7) value is small.
5. Servo motor shaft was rotated by
external force.
proper operation.
1. When torque is limited, increase the
limit value.
2. Reduce load.
3. Use servo motor that provides larger
output.
6. Machine struck something.
1. Review operation pattern.
2. Install limit switches.
Change the servo motor.
Connect correctly.
7. Encoder faulty
8. Wrong connection of servo motor.
Servo amplifier's output terminals
U, V, W do not match servo motor's
input terminals U, V, W.
AL.61 Operation
alarm
"1" or more has been Setting mistake of auxiliary function Set "0" to auxiliary function of point table
set to auxiliary
function of point
table No. 31.
of point table No. 31.
No. 31.
AL.8A Serial
RS-232C or RS-422 1. Communication cable breakage.
Repair or change communication cable
Set correct value in parameter.
communication communication
time-out error stopped for longer
2. Communication cycle longer than
parameter No. 23 setting.
3. Wrong protocol.
than the time set in
parameter No.23.
Serial
Correct protocol.
AL.8E Serial
1. Communication cable fault
(Open cable or short circuit)
Repair or change the cable.
communication communication
error
error occurred
between servo
amplifier and
2. Communication device (e.g.
personal computer) faulty
Change the communication device (e.g.
personal computer).
communication
device (e.g. personal
computer).
88888 Watchdog
CPU, parts faulty
Change servo amplifier.
Fault of parts in servo amplifier
Checking method
Alarm (88888) occurs if power is
switched on after disconnection
of all cables but the control
circuit power supply cables.
11 - 8
11. TROUBLESHOOTING
11.2.3 Remedies for warnings
If an absolute position counter warning (AL.E3) occurred, always make home
CAUTION
position setting again. Otherwise, misoperation may occur.
POINT
When any of the following alarms has occurred, do not resume operation by
switching power of the servo amplifier OFF/ON repeatedly. The servo
amplifier and servo motor may become faulty. If the power of the servo
amplifier is switched OFF/ON during the alarms, allow more than 30
minutes for cooling before resuming operation.
Excessive regenerative warning (AL.E0)
Overload warning 1 (AL.E1)
If AL.E6 occurs, the servo off status is established. If any other warning occurs, operation can be
continued but an alarm may take place or proper operation may not be performed. Use the optional MR
Configurator (servo configuration software) to refer to the cause of warning.
Display
Name
Definition
Cause
Action
1. Positioning operation was performed
without home position return.
AL.90 Home position
return
Positioning operation
was performed
Perform home position return.
incomplete
without home
position return.
2. Home position return speed could not be
decreased to creep speed.
3. Limit switch was actuated during home
position return starting at other than
position beyond dog.
Home position return
ended abnormally.
Review home position return
speed/creep speed/moving
distance after proximity dog.
1. Positioning operation was performed
without home position setting.
Positioning operation
was performed
Perform home position setting.
without home
position setting.
2. Home position setting speed could not be
decreased to creep speed.
3. Limit switch was actuated during home
position setting starting at other than
position beyond dog.
Home position setting
ended abnormally.
Review home position setting
speed/creep speed/moving
distance after proximity dog.
4. Voltage drop in encoder
(Battery disconnected.)
Operation was
After leaving the alarm
occurring for a few minutes,
switch power off, then on again.
Always make home position
setting again.
performed without
making home position
setting while an
absolute position
erase (AL.25) is being
occurred.
5. Battery voltage low
6. Battery cable or battery is faulty.
Change battery. Always make
home position setting again.
Repair cable or changed.
Change battery.
AL.92 Open battery
cable warning
Absolute position
detection system battery
voltage is low.
1. Battery cable is open.
2. Battery voltage supplied from the servo
amplifier to the encoder fell to about
3.2V or less.
(Detected with the encoder)
AL.96 Home position
Home position setting
1. Droop pulses remaining are greater
than the in-position range setting.
Remove the cause of droop pulse
occurrence
setting warning could not be made.
2. Command pulse entered after clearing Do not enter command pulse
of droop pulses.
after clearing of droop pulses.
Reduce creep speed.
3. Creep speed high.
11 - 9
11. TROUBLESHOOTING
Display
Name
Definition
Cause
Action
AL.98 Software limit
warning
Software limit set in
parameter is reached.
1. Software limit was set within actual
operation range.
Set parameter No. 48 to 51
correctly.
2. Point table of position data in excess of Set point table correctly.
software limit was executed.
3. Software limit was reached during JOG Perform operation within
operation or manual pulse generator
operation.
software limit range.
AL.9F Battery warning Voltage of battery for
absolute position
Battery voltage fell to 3.2V or less.
(Detected with the servo amplifier)
Change the battery.
detection system reduced.
AL.E0 Excessive
regenerative
warning
There is a possibility that Regenerative power increased to 85% or
regenerative power may more of permissible regenerative power of
1. Reduce frequency of
positioning.
2. Change regenerative option
for the one with larger
capacity.
exceed permissible
regenerative power of
built-in regenerative
resistor or regenerative
option.
built-in regenerative resistor or
regenerative option.
Checking method
Call the status display and check
regenerative load ratio.
3. Reduce load.
AL.E1 Overload
warning
There is a possibility that Load increased to 85% or more of overload Refer to AL.50, AL.51.
overload alarm 1 or 2
may occur.
alarm 1 or 2 occurrence level.
Cause, checking method
Refer to AL.50,51.
AL.E3
Absolute position Absolute position encoder 1. Noise entered the encoder.
counter warning pulses faulty.
Take noise suppression
measures.
2. Encoder faulty.
Change servo motor.
The multi-revolution counter 3. The movement amount from the home Make home position setting
value of the absolute position
encoder exceeded the
maximum revolution range.
position exceeded a 32767 rotation or again.
37268 rotation in succession.
AL.E6 Servo forced stop EMG-SG are open.
warning
External forced stop was made valid.
(EMG-SG opened.)
Ensure safety and deactivate
forced stop.
AL.E9 Main circuit off Servo was switched on
Switch on main circuit power.
warning
with main circuit power
off.
11.3 MR-DP60 external digital display error
When MR-DP60 external digital display detects an error, the following alarms are displayed. The alarms
are displayed only on the MR-DP60, but not on the servo amplifier display.
Display
AL. CPU CPU error
AL. C0 Communication Communication error
error occurred between MR-DP60
Name
Definition
Cause
Action
Exchange the MR-D60.
Connect correctly.
CPU error
Faulty parts in the MR-D60.
1. CN3 connector disconnected.
2. Wire breakage of the cable.
Repair or exchange the cable.
and MR-J2S-CP.
11 - 10
12. OUTLINE DIMENSION DRAWINGS
12. OUTLINE DIMENSION DRAWINGS
12.1 Servo amplifiers
(1) MR-J2S-10CP to MR-J2S-60CP
MR-J2S-10CP1 to MR-J2S-40CP1
[Unit: mm]
([Unit: in])
Approx.70 (2.76)
A
135 (5.32)
6 ( 0.24) mounting hole
Terminal layout
(Terminal cover open)
MITSUBISHI
B
MITSUBISHI
OPEN
OPEN
C
N
1
C
N
1
C
N
1
C
N
1
A
B
A
B
Name plate
C
N
2
E
N
C
C
N
3
C
N
2
E
N
C
C
N
3
TE1
L1 L2 L3
(Note)
U
V
W
TE2
PE terminal
6
(0.24)
4(0.16)
Variable dimensions
Mass
Servo amplifier
[kg]([lb])
A
B
MR-J2S-10CP(1)
MR-J2S-20CP(1)
MR-J2S-40CP(1)
MR-J2S-60CP
50 (1.97)
70 (2.76)
6 (0.24)
0.7 (1.54)
1.1 (2.43)
22 (0.87)
Note. This data applies to the 3-phase 200 to 230VAC and 1-phase 230VAC power supply models.
Terminal signal layout
TE1
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
For 3-phase 200 to 230VAC and 1-phase 230VAC
For 1-phase 100 to 120VAC
L1
U
L2
V
L3
W
L1
U
L2
W
V
(28.676 [lb in])
Terminal screw: M4
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
Tightening torque: 1.2 [N m] (10.6 [lb in])
TE2
PE terminals
Front
D
C
P
L21 L11
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
12 - 1
12. OUTLINE DIMENSION DRAWINGS
(2) MR-J2S-70CP MR-J2S-100CP
[Unit: mm]
([Unit: in])
6 ( 0.24)
70(2.76)
mounting hole
Approx.70(2.76)
190(7.48)
22
Terminal layout
(Terminal cover open)
MITSUBISHI
(0.87)
MITSUBISHI
OPEN
OPEN
C
N
1
C
N
1
C
N
1
C
N
1
A
B
A
B
Name plate
C
N
2
C
N
3
C
N
2
C
N
3
E
N
C
E
N
C
L1 L2 L3
U
V
W
PE terminal
6(0.24)
TE2
TE1
6(0.24)
42
22
(0.87) (1.65)
6(0.24)
Mass
Servo amplifier
[kg]([lb])
MR-J2S-70CP
MR-J2S-100CP
1.7
(3.75)
Terminal signal layout
TE1
L1
Mounting Screw
Screw Size:M5
Tightening torque:3.24[N m](28.676 [lb in])
L2
V
L3
W
U
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
TE2
Front
D
C
P
L21 L11
N
PE terminals
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
12 - 2
12. OUTLINE DIMENSION DRAWINGS
(3) MR-J2S-200CP MR-J2S-350CP
[Unit: mm]
([Unit: in])
2- 6 ( 0.24)
mounting hole
Approx.70 (2.76)
195(7.68)
90(3.54)
78(3.07)
6
(0.24)
Terminal layout
MITSUBISHI
MITSUBISHI
TE2
TE1
PE terminal
Cooling fan wind direction
Mass
Servo amplifier
[kg]([lb])
MR-J2S-200CP
MR-J2S-350CP
2.0
(4.41)
Terminal signal layout
PE terminals
TE1
L1
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
L2
L3
U
V
W
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
(28.676 [lb in])
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
TE2
L11 L21
D
P
C
N
Terminal screw: M4
Tightening torque: 1.2 [N m] (10.6 [lb in])
12 - 3
12. OUTLINE DIMENSION DRAWINGS
(4) MR-J2S-500CP
2- 6( 0.24)
mounting hole
[Unit: mm]
([Unit: in])
(0.24)
6
130(5.12) (0.24) Approx.70
200(7.87)
(0.19) 5
6
(2.76)
118(4.65)
Terminal layout
MITSUBISHI
OPEN
MITSUBISHI
OPEN
OPEN
TE1
C
N
1
C
N
1
C
N
1
C
N
1
A
B
A
B
C
N
2
C
N
3
C
N
2
C
N
3
TE2
N.P.
N.P.
6(0.24)
Cooling fan
Cooling fan wind direction
Mass
Servo amplifier
MR-J2S-500CP
[kg]([lb])
4.9(10.8)
Terminal signal layout
PE terminals
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
TE1
Built-in regenerative resistor lead
terminal fixing screw
Terminal screw : M4
L1
L2
L3
C
Tightening torque : 1.2 [N m](10.6 [lb in])
(28.676 [lb in])
P
N
U
V
W
Terminal screw : M4
Tightening torque : 1.2 [N m](10[lb in])
TE2
Terminal screw : M3.5
Tightening torque : 0.8 [N m](7[lb in])
L11
L21
12 - 4
12. OUTLINE DIMENSION DRAWINGS
(5) MR-J2S-700CP
2- 6( 0.24)
mounting hole
[Unit: mm]
([Unit: in])
Approx.70
10 (2.76)
200(7.87)
138(5.43)
180(7.09)
160(6.23)
(0.39)
10
62
6(0.24)
(2.44)
(0.39)
Terminal layout
MITSUBISHI
MITSUBISHI
OPEN
OPEN
C
N
1
C
N
1
C
N
1
C
N
1
A
B
A
B
C
N
3
C
N
3
C
N
2
C
N
2
TE2
OPEN
Cooling fan
TE1
6 (0.24)
Cooling fan wind direction
Mass
Servo amplifier
MR-J2S-700CP
[kg]([lb])
7.2(15.9)
Terminal signal layout
PE terminals
Mounting Screw
Screw Size:M5
Tightening torque:
3.24[N m]
TE1
L1
Terminal screw : M4
Tightening torque : 1.2 [N m](10.6 [lb in])
L2
L3
C
P
N
U
V
W
Built-in regenerative
resistor lead terminal
fixing screw
(28.676 [lb in])
Terminal screw : M4
Tightening torque : 1.2 [N m](10.6 [lb in])
TE2
Terminal screw : M3.5
Tightening torque : 0.8 [N m](7 [lb in])
L11
L21
12 - 5
12. OUTLINE DIMENSION DRAWINGS
12.2 Connectors
(1) Servo amplifier side
<3M >
(a) Soldered type
Model
Connector
Shell kit
[Unit: mm]
([Unit: in])
: 10120-3000VE
: 10320-52F0-008
12.0(0.47)
14.0
22.0 (0.87)
(0.55)
Logo, etc. are indicated here.
33.3 (1.31)
12.7(0.50)
(b) Threaded type
Model
Connector
Shell kit
[Unit: mm]
([Unit: in])
: 10120-3000VE
: 10320-52A0-008
12.0
(0.47)
Note. This is not available as option
and should be user-prepared.
22.0
14.0
(0.55)
)
(1.08)
27.4
(0.87
12.7
33.3
(1.31)
(0.50)
(c) Insulation displacement type
Model
Connector
Shell kit
[Unit: mm]
([Unit: in])
: 10120-6000EL
: 10320-3210-000
6.7
(
0.26)
20.9 (0.82)
2- 0.5 (0.02)
Logo, etc. are indicated here.
29.7 (1.17)
12 - 6
12. OUTLINE DIMENSION DRAWINGS
(2) Communication cable connector
<JAE>
[Unit: mm]
([Unit: in])
B
A
Fitting fixing screw G
E (max. diameter of
cable used)
F
C
D
A
B
C
D
F
Type
DE-C1-J6-S6
E
G
1
1
0.25
1
reference
34.5 (1.36)
19 (0.75)
24.99 (0.98)
33 (1.30)
6 (0.24)
18 (0.71)
#4-40
12 - 7
12. OUTLINE DIMENSION DRAWINGS
MEMO
12 - 8
13. CHARACTERISTICS
13. CHARACTERISTICS
13.1 Overload protection characteristics
An electronic thermal relay is built in the servo amplifier to protect the servo motor and servo amplifier
from overloads. Overload 1 alarm (AL.50) occurs if overload operation performed is above the electronic
thermal relay protection curve shown in any of Figs 13.1. Overload 2 alarm (AL.51) occurs if the
maximum current flew continuously for several seconds due to machine collision, etc. Use the equipment
on the left-hand side area of the continuous or broken line in the graph.
In a machine like the one for vertical lift application where unbalanced torque will be produced, it is
recommended to use the machine so that the unbalanced torque is 70% or less of the rated torque.
1000
100
10
1000
During rotation
During rotation
100
During stop
10
1
During stop
1
0.1
0
0.1
0
50
100
150
200
250
300
50
150
200
250
300
100
(Note) Load ratio [%]
(Note) Load ratio [%]
b. MR-J2S-200CP to MR-J2S-350CP
a. MR-J2S-10CP to MR-J2S-100CP
10000
1000
During rotation
During servo lock
100
10
1
0
50
100
150
200
250
300
(Note) Load ratio [%]
c. MR-J2S-500CP MR-J2S-700CP
Note. If operation that generates torque more than 100% of the rating is performed with an abnormally high frequency in a servo motor
stop status (servo lock status) or in a 30r/min or less low-speed operation status, the servo amplifier may fail even when the
electronic thermal relay protection is not activated.
Fig 13.1 Electronic thermal relay protection characteristics
13 - 1
13. CHARACTERISTICS
13.2 Power supply equipment capacity and generated loss
(1) Amount of heat generated by the servo amplifier
Table 12.1 indicates servo amplifier's power supply capacities and losses generated under rated load.
For thermal design of an enclosure, use the values in Table 13.1 in consideration for the worst
operating conditions. The actual amount of generated heat will be intermediate between values at
rated torque and servo-off according to the duty used during operation. When the servo motor is run at
less than the maximum speed, the power supply capacity will be smaller than the value in the table,
but the servo amplifier's generated heat will not change.
Table 13.1 Power supply capacity and generated heat per servo amplifier at rated output
(Note 1)
Power supply
capacity[kVA]
(Note 2)
Area required for heat dissipation
Servo amplifier
MR-J2S-10CP(1)
MR-J2S-20CP(1)
MR-J2S-40CP(1)
MR-J2S-60CP
Servo motor
Servo amplifier-generated heat[W]
At rated torque
With servo off
[m2]
0.5
0.5
0.5
0.5
0.5
0.5
0.7
0.7
0.7
0.8
0.8
0.8
1.0
1.0
1.0
1.0
1.0
1.0
1.8
1.8
1.8
1.8
1.0
1.8
1.8
1.8
2.7
2.7
1.8
1.8
1.8
3.9
2.7
3.9
3.9
3.9
2.4
3.9
6.0
6.0
[ft2]
5.4
5.4
5.4
5.4
5.4
5.4
7.5
7.5
7.5
8.6
8.6
8.6
10.8
10.8
10.8
10.8
10.8
10.8
19.4
19.4
19.4
19.4
10.8
19.4
19.4
19.4
29.1
29.1
19.4
19.4
19.4
42.0
29.1
42.0
42.0
42.0
25.8
42.0
64.6
64.6
HC-KFS053 13
HC-MFS053 13
HC-UFS13
HC-KFS23
HC-MFS23
HC-UFS23
HC-KFS43
HC-MFS43
HC-UFS43
0.3
0.3
0.3
0.5
0.5
0.5
0.9
0.9
0.9
1.0
1.0
1.0
1.3
1.3
1.3
1.5
1.7
1.7
2.1
3.5
2.5
3.5
1.8
2.5
2.5
2.5
4.8
5.5
3.5
3.5
3.5
7.5
5.5
7.5
5.5
7.5
4.5
7.5
10.0
10.6
25
25
25
25
25
25
35
35
35
40
40
40
50
50
50
50
50
50
90
90
90
90
50
90
90
90
120
130
90
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
15
20
20
20
20
15
20
20
20
20
20
20
20
20
25
HC-SFS52
HC-SFS53
HC-LFS52
HC-KFS73
MR-J2S-70CP
HC-MFS73
HC-UFS72 73
HC-SFS81
MR-J2S-100CP
HC-SFS102 103
HC-LFS102
HC-SFS121
HC-SFS201
HC-SFS152 153
HC-SFS202 203
HC-RFS103
HC-RFS153
HC-UFS152
HC-LFS152
HC-SFS301
HC-SFS352 353
HC-RFS203
HC-UFS202
HC-LFS202
HC-SFS502
HC-RFS353
HC-RFS503
HC-UFS352
HC-UFS502
HC-LFS302
HA-LFS502
HC-SFS702
HA-LFS702
MR-J2S-200CP
MR-J2S-350CP
90
90
195
135
195
195
195
120
195
300
300
25
25
25
25
25
25
25
25
MR-J2S-500CP
MR-J2S-700CP
Note 1. Note that the power supply capacity will vary according to the power supply impedance. This value assumes that the power
factor improving reactor is not used.
2. Heat generated during regeneration is not included in the servo amplifier-generated heat. To calculate heat generated by the
regenerative option, Refer to section 14.1.1.
13 - 2
13. CHARACTERISTICS
(2) Heat dissipation area for enclosed servo amplifier
The enclosed control box (hereafter called the control box) which will contain the servo amplifier
should be designed to ensure that its temperature rise is within 10
( 50 ) at the ambient
temperature of 40 (104 ). (With a 5 (41 ) safety margin, the system should operate within a
maximum 55 (131 ) limit.) The necessary enclosure heat dissipation area can be calculated by
Equation 13.1.
P
............................................................................................................................................. (13.1)
A
K
T
where, A
P
: Heat dissipation area [m2]
: Loss generated in the control box [W]
T : Difference between internal and ambient temperatures [
: Heat dissipation coefficient [5 to 6]
]
K
When calculating the heat dissipation area with Equation 13.1, assume that P is the sum of all losses
generated in the enclosure. Refer to Table 13.1 for heat generated by the servo amplifier. "A" indicates
the effective area for heat dissipation, but if the enclosure is directly installed on an insulated wall,
that extra amount must be added to the enclosure's surface area.
The required heat dissipation area will vary wit the conditions in the enclosure. If convection in the
enclosure is poor and heat builds up, effective heat dissipation will not be possible. Therefore,
arrangement of the equipment in the enclosure and the use of a cooling fan should be considered.
Table 13.1 lists the enclosure dissipation area for each servo amplifier when the servo amplifier is
operated at the ambient temperature of 40 (104 ) under rated load.
(Outside)
(Inside)
Air flow
Fig. 13.2 Temperature distribution in enclosure
When air flows along the outer wall of the enclosure, effective heat exchange will be possible, because
the temperature slope inside and outside the enclosure will be steeper.
13 - 3
13. CHARACTERISTICS
13.3 Dynamic brake characteristics
13.3.1 Dynamic brake operation
(1) Calculation of coasting distance
Fig. 13.3 shows the pattern in which the servo motor comes to a stop when the dynamic brake is
operated. Use Equation 13.2 to calculate an approximate coasting distance to a stop. The dynamic
brake time constant varies with the servo motor and machine operation speeds. (Refer to (2) of this
section.)
ON
Forced stop (EMG)
OFF
Time constant
V0
Machine speed
Time
te
Fig. 13.3 Dynamic brake operation diagram
JL
JM
V0
60
Lmax
te
....................................................................................................................... (13.2)
1
Lmax
: Maximum coasting distance .................................................................................................[mm][in]
: Machine rapid feed rate........................................................................................ [mm/min][in/min]
: Servo motor inertial moment.................................................................................[kg cm2][oz in2]
: Load inertia moment converted into equivalent value on servo motor shaft.....[kg cm2][oz in2]
: Brake time constant........................................................................................................................ [s]
0
V
M
J
L
J
te
: Delay time of control section........................................................................................................... [s]
(There is internal relay delay time of about 30ms.)
(2) Dynamic brake time constant
The following shows necessary dynamic brake time constant for the equations (13.2).
0.02
0.018
0.016
0.014
0.012
0.01
16
14
12
23
10
8
73
23
053
73
6
0.008
0.006
0.004
0.002
0
4
2
0
053
43
43
13
0
500 1000 1500 2000 2500 3000
Speed [r/min]
13
0
500 1000 1500 2000 2500 3000
Speed [r/min]
a. HC-KFS series
b. HC-MFS series
13 - 4
13. CHARACTERISTICS
0.045
0.04
0.035
0.03
0.025
0.02
0.015
0.01
0.005
0
0.04
0.035
0.03
0.025
0.02
0.015
0.01
0.005
0
121
201
702
352
202
52
301
502
152
102
81
1000
0
50
500
0
500
1000 1500 2000
Speed [r/min]
Speed [r/min]
c. HC-SFS1000r/min series
d. HC-SFS2000r/min series
0.12
0.1
0.018
0.016
0.014
0.012
0.01
203
53
0.08
0.06
0.04
0.02
0
103
503
0.008
0.006
153
353
0.004
0.002
0
103
353
203
153
50 500 1000 1500 2000 2500 3000
Speed [r/min]
0
500 1000 1500 2000 2500 3000
Speed [r/min]
0
e. HC-SFS3000r/min series
f. HC-RFS series
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
73
0.1
0.09
0.08
0.07
0.06
0.05
0.04
0.03
0.02
0.01
0
72
502
352
43
23
13
202
152
0
50 500 10001500200025003000
Speed [r/min]
0
500
1000 1500 2000
Speed [r/min]
g. HC-UFS 2000r/min series
h. HC-UFS3000r/min series
40.0
35.0
30.0
25.0
302
20.0
15.0
10.0
5.0
0
0
500
1000 1500 2000
Speed [r/min]
i. HC-LFS series
13 - 5
13. CHARACTERISTICS
13.3.2 The dynamic brake at the load inertia moment
Use the dynamic brake under the load inertia moment ratio indicated in the following table. If the load
inertia moment is higher than this value, the built-in dynamic brake may burn. If there is a possibility
that the load inertia moment may exceed the value, contact Mitsubishi.
Servo amplifier
Load inertia moment ratio [times]
MR-J2S-10CP to MR-J2S-200CP
MR-J2S-10CP1 to MR-J2S-40CP1
MR-J2S-350CP
30
16
15
MR-J2S-500CP MR-J2S-700CP
13.4 Encoder cable flexing life
The flexing life of the cables is shown below. This graph calculated values. Since they are not guaranteed
values, provide a little allowance for these values.
1
5
108
107
a
1
5
107
106
a : Long flexing-life encoder cable
MR-JCCBL M-H
MR-JHSCBL M-H
MR-ENCBL M-H
1
5
106
105
b : Standard encoder cable
MR-JCCBL M-L
MR-JHSCBL M-L
1
5
105
104
1
5
104
103
b
1
103
4
7
10
20
40
70 100
200
Flexing radius [mm]
13 - 6
13. CHARACTERISTICS
13.5 Inrush currents at power-on of main circuit and control circuit
The following table indicates the inrush currents (reference value) that will flow when the maximum
permissible voltage (253VAC) is applied at the power supply capacity of 2500kVA and the wiring length of
1m.
Inrush Currents (A0-p
)
Servo Amplifier
Main circuit power supply (L1, L2, L3)
30A (Attenuated to approx. 5A in 10ms)
30A (Attenuated to approx. 5A in 10ms)
54A (Attenuated to approx. 12A in 10ms)
Control circuit power supply (L11, L21)
MR-J2S-10CP 20CP
MR-J2S-40CP 60CP
MR-J2S-70CP 100CP
70 to 100A
(Attenuated to approx. 0A in 0.5 to 1ms)
100 to 130A
(Attenuated to approx. 0A in 0.5 to 1ms)
30A
MR-J2S-200CP 350CP
120A (Attenuated to approx. 12A in 20ms)
MR-J2S-500CP
MR-J2S-700CP
44A (Attenuated to approx. 20A in 20ms)
88A (Attenuated to approx. 20A in 20ms)
59A (Attenuated to approx. 5A in 4ms)
72A (Attenuated to approx. 5A in 4ms)
(Attenuated to approx. 0A in several ms)
MR-J2S-10CP1 20CP1
MR-J2S-40CP1
100 to 130A
(Attenuated to approx. 0A in 0.5 to 1ms)
Since large inrush currents flow in the power supplies, always use no-fuse breakers and magnetic
contactors. (Refer to section 14.2.2.)
When circuit protectors are used, it is recommended to use the inertia delay type that will not be tripped
by an inrush current.
13 - 7
13. CHARACTERISTICS
MEMO
13 - 8
14. OPTIONS AND AUXILIARY EQUIPMENT
14. OPTIONS AND AUXILIARY EQUIPMENT
Before connecting any option or peripheral equipment, turn off the power and wait
for 15 minutes or more until the charge lamp turns off. Then, confirm that the
voltage between P and N is safe with a voltage tester and others. Otherwise, an
electric shock may occur. In addition, always confirm from the front of the servo
amplifier whether the charge lamp is off or not.
WARNING
Use the specified auxiliary equipment and options. Unspecified ones may lead to a
fault or fire.
CAUTION
14.1 Options
14.1.1 Regenerative options
The specified combinations of regenerative options and servo amplifiers may only
be used. Otherwise, a fire may occur.
CAUTION
(1) Combination and regenerative power
The power values in the table are resistor-generated powers and not rated powers.
Regenerative power[W]
(Note)
(Note)
MR-RB51
[6.7 ]
Servo amplifier
Built-in regenerative MR-RB032 MR-RB12
MR-RB32
[40 ]
MR-RB30
[13 ]
MR-RB31
[6.7 ]
MR-RB50
[13 ]
resistor
[40 ]
[40 ]
MR-J2S-10CP(1)
MR-J2S-20CP (1)
MR-J2S-40CP (1)
MR-J2S-60CP
30
30
30
30
30
30
10
10
10
20
20
100
100
130
170
100
100
100
100
100
MR-J2S-70CP
300
300
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-700CP
300
300
300
500
500
500
300
500
Note. Always install a cooling fan.
(2) Selection of the regenerative option
(a) Simple selection method
In horizontal motion applications, select the regenerative option as described below.
When the servo motor is run without load in the regenerative mode from the running speed to a
stop, the permissible duty is as indicated in section 5.1 of the separately available Servo Motor
Instruction Manual.
For the servo motor with a load, the permissible duty changes according to the inertia moment of
the load and can be calculated by the following formula.
Permissible duty for servo motor with no load (value indication section 5.1 in Servo Motor Instruction Manual)
Permissible
duty
(m 1)
2
ratedspeed
running speed
[times/min]
where m
load inertia moment/servo motor inertia moment
From the permissible duty, find whether the regenerative option is required or not.
Permissible duty number of positioning times [times/min]
Select the regenerative option out of the combinations in (1) of this section.
14 - 1
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) To make selection according to regenerative energy
Use the following method when regeneration occurs continuously in vertical motion applications or
when it is desired to make an in-depth selection of the regenerative option.
a. Regenerative energy calculation
Use the following table to calculate the regenerative energy.
tf(1 cycle)
N0
Up
Time
Down
M
t1
Tpsa1
t2
t3
t4
Tpsd1
Tpsa2
Tpsd2
Firiction
torque
1)
( )
(Driving)
2)
TF
4)
8)
5)
TU
6)
3)
7)
(Regenerative)
( )
Formulas for calculating torque and energy in operation
Torque applied to servo motor [N m]
Regenerative power
Energy [J]
(JL JM)
9.55 104
T2 TU TF
N0
1
0.1047
2
1)
2)
T1
TU
TF
E1
N0 T1 Tpsa1
Tpsa1
E2 0.1047 N0 T2 t1
0.1047
(JL JM)
9.55 104
N0
1
3)
T3
TU
TF
E3
N0 T3 Tpsd1
2
Tpsd1
4), 8)
5)
T4 TU
E4 0 (N0 regeneration)
0.1047
(JL JM)
N0
104
1
T
5
TU TF
E5
N0 T5 Tpsa2
2
Tpsa2
9.55
6)
T6
T7
TU TF
E6 0.1047 N0 T6 t3
0.1047
(JL JM)
9.55 104
N0
1
7)
TU TF
E7
N0 T7 Tpsd2
2
Tpsd2
From the calculation results in 1) to 8), find the absolute value (Es) of the sum total of negative
energies.
b. Losses of servo motor and servo amplifier in regenerative mode
The following table lists the efficiencies and other data of the servo motor and servo amplifier in
the regenerative mode.
Servo amplifier
MR-J2S-10CP
MR-J2S-10CP1
MR-J2S-20CP
MR-J2S-20CP1
MR-J2S-40CP
MR-J2S-40CP1
MR-J2S-60CP
MR-J2S-70CP
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-700CP
Inverse efficiency[%]
Capacitor charging[J]
55
55
70
70
85
85
85
80
80
85
85
90
90
9
4
9
4
11
12
11
18
18
40
40
45
70
14 - 2
14. OPTIONS AND AUXILIARY EQUIPMENT
Inverse efficiency ( )
:Efficiency including some efficiencies of the servo motor and servo
amplifier when rated (regenerative) torque is generated at rated speed.
Since the efficiency varies with the speed and generated torque, allow for
about 10%.
Capacitor charging (Ec) :Energy charged into the electrolytic capacitor in the servo amplifier.
Subtract the capacitor charging from the result of multiplying the sum total of regenerative energies by
the inverse efficiency to calculate the energy consumed by the regenerative option.
ER [J]
Es Ec
Calculate the power consumption of the regenerative option on the basis of single-cycle operation period tf
[s] to select the necessary regenerative option.
PR [W] ER/tf
(3) Connection of the regenerative option
Set parameter No.0 according to the option to be used.
Parameter No.0
Selection of regenerative
0: Not used. (The built-in regenerative resistor is used. However, the MR-J2S-10CP
does not have a built-in regenerative resistor and therefore cannot use it.)
1: FR-RC, FR-BU2
2: MR-RB032
3: MR-RB12
4: MR-RB32
5: MR-RB30
6: MR-RB50(Cooling fan is required)
8: MR-RB31
9: MR-RB51(Cooling fan is required)
14 - 3
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Connection of the regenerative option
POINT
When the MR-RB50 MR-RB51 is used, a cooling fan is required to cool it.
The cooling fan should be prepared by the customer.
The regenerative option will generate heat of about 100 . Fully examine heat dissipation, installation
position, used cables, etc. before installing the option. For wiring, use flame-resistant cables and keep
them clear of the regenerative option body. Always use twisted cables of max. 5m (16.4ft) length for
connection with the servo amplifier.
(a) MR-J2S-350CP or less
Always remove the wiring from across P-D and fit the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is opened when the regenerative option
overheats abnormally.
Always remove the lead from across P-D.
Servo amplifier
Regenerative option
D
P
P
C
C
G3
(Note 2)
G4
5m (16.4 ft) or less
Cooling fan(Note 1)
Note 1. When using the MR-RB50, forcibly cool it with a cooling fan (92 92, minimum air flow : 1.0m3).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
For the MR-RB50 install the cooling fan as shown.
[Unit : mm(in)]
Cooling fan installation screw hole dimensions
2-M3 screw hole
Top
(for cooling fan installation)
Depth 10 or less
Cooling fan
Terminal block
(Screw hole already
machined)
Thermal relay
Bottom
82.5
40 (1.58)
(3.25)
Installation surface
Horizontal installation
Vertical
installation
14 - 4
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-J2S-500CP MR-J2S-700CP
Always remove the wiring (across P-C) of the servo amplifier built-in regenerative resistor and fit
the regenerative option across P-C.
The G3 and G4 terminals act as a thermal sensor. G3-G4 is opened when the regenerative option
overheats abnormally.
Always remove wiring (across P-C) of servo
amplifier built-in regenerative resistor.
Servo amplifier
Regenerative option
P
C
P
C
G3
(Note 2)
G4
5m(16.4ft) or less
Cooling fan(Note 1)
Note 1. When using the MR-RB50 MR-RB51, forcibly cool it with a cooling fan (92 92, minimum air flow : 1.0m3).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
When using the regenerative resistor option, remove the servo amplifier's built-in regenerative
resistor terminals (across P-C), fit them back to back, and secure them to the frame with the
accessory screw as shown below.
Mounting method
Accessory screw
For MR-J2S-700CP
For MR-J2S-500CP
Accessory screw
Accessory screw
14 - 5
14. OPTIONS AND AUXILIARY EQUIPMENT
For the MR-RB50 MR-RB51 install the cooling fan as shown.
[Unit : mm(in)]
Cooling fan installation screw hole dimensions
2-M3 screw hole
Top
(for cooling fan installation)
Depth 10 or less
Cooling fan
Terminal block
(Screw hole already
machined)
Thermal relay
Bottom
82.5
40 (1.58)
(3.25)
Installation surface
Horizontal installation
Vertical
installation
14 - 6
14. OPTIONS AND AUXILIARY EQUIPMENT
(5) Outline drawing
(a) MR-RB032 MR-RB12
[Unit: mm (in)]
LA
6 (0.24) mounting hole
LB
MR-RB
TE1
Terminal block
5 (0.20)
G3
G4
P
G3
G4
TE1
P
C
C
Terminal screw: M3
Tightening torque:
0.5 to 0.6 [N m](4 to 5 [lb in])
Mounting screw
6 (0.24)
1.6 (0.06)
Screw size: M5
20
(0.79)
LD
LC
Tightening torque:
3.24 [N m](28.676 [lb in])
Regenerative
option
Variable dimensions
Mass
LA
LB
LC
LD [kg] [lb]
30
15
119
99
MR-RB032
MR-RB12
0.5 1.1
(1.18) (0.59) (4.69) (3.9)
40 15 169 149
(1.58) (0.59) (6.69) (5.87)
1.1 2.4
(b) MR-RB30 MR-RB31 MR-RB32
[Unit: mm (in)]
Terminal block
P
C
Terminal screw: M4
G3 Tightening torque: 1.2 [N m] (10.6 [Ib in])
G4
Mounting screw
Screw: M6
318 (12.52)
7 (0.28)
Tightening torque: 5.4 [N m] (47.79 [Ib in])
17
335 (13.19)
(0.67)
90 (3.54)
10
(0.39)
Regenerative
Mass [kg] (Ib)
option
100 (3.94)
MR-RB30
MR-RB31
MR-RB32
2.9 (6.4)
14 - 7
14. OPTIONS AND AUXILIARY EQUIPMENT
(c) MR-RB50 MR-RB51
[Unit: mm (in)]
Fan mounting screw
(2-M3 screw)
On opposite side
Terminal block
P
C
Terminal screw: M4
Tightening torque: 1.2 [N m]
(10.6 [Ib in])
49
(1.93)
82.5
(3.25)
G3
G4
Mounting screw
Screw: M6
Tightening torque: 5.4 [N m]
(47.79 [Ib in])
7 14
slot
Regenerative
Mass [kg] (Ib)
option
Wind blows in the
arrow direction
MR-RB50
5.6 (12.3)
MR-RB51
7 (0.28)
108 (4.25)
120 (4.73)
2.3
(0.09)
Approx.30 (1.18)
8 (0.32)
200 (7.87)
217 (8.54)
17
(0.67)
12
(0.47)
14 - 8
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.2 FR-BU2 brake unit
POINT
Use a 200V class brake unit and a resistor unit with a 200V class servo
amplifier. Combination of different voltage class units and servo amplifier
cannot be used.
Install a brake unit and a resistor unit on a flat surface vertically. When
the unit is installed horizontally or diagonally, the heat dissipation effect
diminishes.
Temperature of the resistor unit case rises to higher than 100 . Keep
cables and flammable materials away from the case.
Ambient temperature condition of the brake unit is between 10 (14 )
and 50 (122 ). Note that the condition is different from the ambient
temperature condition of the servo amplifier (between 0 (32 ) and
55 (131 )).
Configure the circuit to shut down the power-supply with the alarm
output of the brake unit and resistor unit under abnormal condition.
Use the brake unit with a combination indicated in this section (1).
For executing a continuous regenerative operation, use FR-RC power
regeneration converter.
Brake unit and regenerative options (Regenerative resistor) cannot be
used simultaneously.
Connect the brake unit to the bus of the servo amplifier. As compared to the MR-RB regenerative option,
the brake unit can return larger power. Use the brake unit when the regenerative option cannot provide
sufficient regenerative capability.
When using the brake unit, set the parameter No.0 of the servo amplifier to " 01
".
When using the brake unit, always refer to the FR-BU2-(H) Brake Unit Instruction Manual.
(1) Selection
Use a combination of servo amplifier, brake unit and resistor unit listed below.
Number of
connected
units
Permissible
continuous
power [kW]
Total
Applicable servo
amplifier
Brake unit
Resistor unit
resistance
[
]
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-500CP
MR-J2S-700CP
FR-BU2-15K
FR-BU2-30K
FR-BR-15K
FR-BR-30K
1
1
0.99
1.99
8
4
14 - 9
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Brake unit parameter setting
Normally, when using the FR-BU2, changing parameters is not necessary. Whether a parameter can
be changed or not is listed below.
Parameter
Name
Change
possible/
impossible
Remarks
No.
0
1
Brake mode switchover
Impossible Do not change the parameter.
Monitor display data selection
Possible
Refer to the FR-BU2-(H) Brake Unit
Instruction Manual.
2
3
Input terminal function selection 1
Input terminal function selection 2
Parameter write selection
Impossible Do not change the parameter.
77
78
Cumulative energization time
carrying-over times
CLr Parameter clear
ECL Alarm history clear
C1
For manufacturer setting
14 - 10
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Connection example
POINT
Connecting PR terminal of the brake unit to P terminal of the servo
amplifier results in brake unit malfunction. Always connect the PR
terminal of the brake unit to the PR terminal of the resistor unit.
ALM
RA1
ON
MC
EMG
OFF
MC
SK
Servo amplifier
CN1B
NFB
MC
(Note 9)
EMG
SG
L1
(Note 1)
Power
supply
10
L2
FR-BR
3
VDD
L3
(Note 4)
TH1
TH2
13 COM
18 ALM
P
L11
L21
RA1
PR
FR-BU2
D
P
PR
P/
MSG
(Note 6)
SD
A
(Note 3)
(Note 7)
N/
B
C
N
C
BUE
(Note 8)(Note 5)
SD
(Note 2)
Note 1. For power supply specifications, refer to section 1.2.
2. For the servo amplifier of 5k and 7kW, always disconnect the lead of built-in regenerative resistor, which is connected to the P
and C terminals.
3. Connect the P/ and N/ terminals of the brake unit to a correct destination. Wrong connection results in servo amplifier and
brake unit malfunction.
4. Contact rating: 1b contact, 110VAC_5A/220VAC_3A
Normal condition: TH1-TH2 is conducting. Abnormal condition: TH1-TH2 is not conducting.
5. Contact rating: 230VAC_0.3A/30VDC_0.3A
Normal condition: B-C is conducting/A-C is not conducting. Abnormal condition: B-C is not conducting/A-C is conducting.
6. For the servo amplifier of 3.5kW, always disconnect the wiring between P and D terminals.
7. Do not connect more than one cable to each P to N terminals of the servo amplifier.
8. Always connect between BUE and SD terminals (Factory-wired).
9. In the device setting, assign the forced stop (EMG) to any pin (Refer to section 6.6).
14 - 11
14. OPTIONS AND AUXILIARY EQUIPMENT
(a) Precautions for wiring
The cables between the servo amplifier and the brake unit, and between the resistor unit and the
brake unit should be as short as possible. Always twist the cable longer than 5m (twist five times
or more per one meter). Even when the cable is twisted, the cable should be less than 10m. Using
cables longer than 5m without twisting or twisted cables longer than 10m, may result in the brake
unit malfunction.
Servo amplifier
Servo amplifier
Brake unit
Resistor unit
Brake unit
Resistor unit
Twist
Twist
P
N
P
N
P
PR
P
PR
P
N
P
N
P
PR
P
PR
5m or less
5m or less
10m or less
10m or less
(b) Cables
1) Cables for the brake unit
For the brake unit, HIV cable (600V grade heat-resistant PVC insulated wire) is recommended.
a) Main circuit terminal
Main
circuit
terminal
screw
size
Crimping
terminal
Cable size
Tightening
torque
N/ , P/ , PR,
Brake unit
[N m]
N/ , P/
PR,
,
HIV cables,
etc. [mm2]
AWG
([Ib in])
N/
P/
PR
FR-BU2-15K
FR-BU2-30K
M4
M5
5.5-4
5.5-5
1.5(13.3)
2.5(22.1)
3.5
5.5
12
10
Terminal block
14 - 12
14. OPTIONS AND AUXILIARY EQUIPMENT
b) Control circuit terminal
POINT
Undertightening can cause a cable disconnection or malfunction.
Overtightening can cause a short circuit or malfunction due to damage to
the screw or the brake unit.
Sheath
RES
MSG MSG
SD
SD SD
Core
BUE
PC
SD
Jumper
A
B
C
6mm
Terminal block
Wire the stripped cable after twisting to prevent the cable
from becoming loose. In addition, do not solder it.
Screw size: M3
Tightening torque: 0.5N m to 0.6N
Cable size: 0.3mm2 to 0.75 mm2
m
Screw driver: Small flat-blade screwdriver
(Tip thickness: 0.4mm/Tip width 2.5mm)
(c) Crimping terminals for P and N terminals of servo amplifier
POINT
Always use recommended crimping terminals or equivalent since some
crimping terminals cannot be installed depending on the size.
Number of
Servo amplifier
Brake unit
connected Crimping terminal Applicable tool
units
Manufacturer
MR-J2S-350CP
MR-J2S-500CP
FR-BU2-15K
FR-BU2-15K
FR-BU2-30K
FR-BU2-30K
1
1
Japan Solderless
Terminal
FVD5.5-S4
YNT-1210S
1
1
MR-J2S-700CP
14 - 13
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Outline dimension drawings
(a) FR-BU2 brake unit
[Unit: mm]
FR-BU2-15K
5 hole
(Screw size: M4)
Rating
plate
4
5
18.5
6
56
68
6
52
62
132.5
FR-BU2-30K
2- 5 hole
(Screw size: M4)
Rating
plate
5
5
96
6
6
18.5
52
59
108
129.5
14 - 14
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) FR-BR resistor unit
[Unit: mm]
2
C
(Note)
Control circuit
terminal
(Note)
Main circuit
terminal
C
C
Approx. 35
Approx. 35
W1
1
W
5
Note. Ventilation ports are provided on both sides and the top. The bottom is open.
Approximate
Resistor unit
W
W1
H
H1
H2
H3
D
D1
C
mass
[kg]([Ib])
FR-BR-15K
FR-BR-30K
170 100 450 410 20 432 220 3.2
340 270 600 560 20 582 220
6
15(33.1)
30(66.1)
4
10
14.1.3 Power regeneration converter
When using the power regeneration converter, set "01
(1) Selection
" in parameter No.0.
The converters can continuously return 75% of the nominal regenerative power. They are applied to
the servo amplifiers of the MR-J2S-500CP and MR-J2S-700CP.
Power
Nominal
500
regeneration
converter
regenerative
power (kW)
Servo amplifier
300
200
FR-RC15
FR-RC30
15
30
MR-J2S-500CP
MR-J2S-700CP
100
50
30
20
0
50
75 100
150
Nominal regenerative power (%)
14 - 15
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Connection example
Servo amplifier
L11
L21
Power factor improving reactor
NFB
MC
FR-BAL
L1
(Note 3)
Power
supply
L2
L3
VDD
COM
SG
EMG
SON
RA2
ALM
(Note 2)
N
P
C
5m(16.4ft) or less
N/
P/
RDY
SE
A
Ready
RDY
output
B
C
B
C
R/L1
Alarm
output
S/L2
T/L3
RX
R
(Note 1)
SX
S
Phase detection
terminals
TX
T
Power regeneration
converter FR-RC
FR-RC
Operation ready
ON
EMG
RA2
OFF
B
C
MC
SK
MC
Note 1. When not using the phase detection terminals, fit the jumpers across RX-R, SX-S and TX-T. If the jumpers remain removed, the
FR-RC will not operate.
2. When using servo amplifiers of 5kW and 7kW, always remove the lead of built-in regenerative resistor connected to P terminal
and C terminal.
3. Refer to section 1.2 for the power supply specification.
14 - 16
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outside dimensions of the power regeneration converters
[Unit : mm(in)]
Mounting foot (removable)
Mounting foot
movable
2- D hole
Rating plate
Front cover
Display
panel
window
Cooling fan
K
D
F
AA
A
C
Heat generation area outside mounting dimension
Power
Approx.
regeneration
converter
A
AA
B
BA
C
D
E
EE
K
F
Mass [kg(Ib)]
270
200
450
432
195
10
10
8
3.2
87
19
FR-RC-15K
FR-RC-30K
(10.630) (7.874) (17.717) (17.008) (7.677) (0.394) (0.394) (0.315) (0.126) (3.425)
340 270 600 582 195 10 10 3.2 90
(13.386) (10.630) (23.622) (22.913) (7.677) (0.394) (0.394) (0.315) (0.126) (3.543)
(41.888)
31
8
(68.343)
(4) Mounting hole machining dimensions
When the power regeneration converter is fitted to a totally enclosed type box, mount the heat
generating area of the converter outside the box to provide heat generation measures. At this time, the
mounting hole having the following dimensions is machined in the box.
[Unit : mm(in)]
(2- D hole)
Approx. AA
Model
A
B
D
AA
BA
260
412
10
200
432
FR-RC-15K
(10.236) (16.220) (0.394) (7.874) (17.009)
330 562 10 270 582
(12.992) (22.126) (0.394) (10.630) (22.913)
FR-RC-30K
(Mounting hole)
a
14 - 17
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.4 Cables and connectors
(1) Cable make-up
The following cables are used for connection with the servo motor and other models. Those indicated
by broken lines in the figure are not options.
Servo amplifier
9)
Operation
panel
CN1A CN1B
Personal
computer
CN2 CN3
14)
Controller
13)
10)
10)
12)
11)
11)
To U, V, W,
19) 20)
HC-KFS
HC-MFS
HC-UFS 3000 r/min
1) 2)
6)
HC-SFS
HC-RFS
HC-UFS 2000r/min
15) 16) 17) 18)
3) 4) 5)
7) 8)
14 - 18
14. OPTIONS AND AUXILIARY EQUIPMENT
No.
1) Standard encoder MR-JCCBL M-L Connector: 10120-3000PE
cable Refer to (2) of this Shell kit: 10320-52F0-008
section. (3M or equivalent)
Product
Model
Description
Housing: 1-172161-9
Connector pin: 170359-1
Application
Standard
flexing life
(Tyco Electronics or equivalent) IP20
Cable clamp: MTI-0002
(Toa Electric Industry)
2) Long flexing life MR-JCCBL M-H
Long flexing
encoder cable
Refer to (2) of this
section.
life
IP20
3) Standard encoder MR-JHSCBL M-L Connector: 10120-3000PE
cable Refer to (2) of this Shell kit: 10320-52F0-008
section. (3M or equivalent)
4) Long flexing life MR-JHSCBL M-H
Connector: D/MS3106B20-29S
Cable clamp: D/MS3057-12A
(DDK)
Standard
flexing life
IP20
Long flexing
life
encoder cable
Refer to (2) of this
section.
5) IP65-compliant
encoder cable
MR-ENCBL M-H Connector: 10120-3000PE
Refer to (2) of this Shell kit: 10320-52F0-008
Connector: D/MS3106A20-29S
(D190)
Long flexing
life
section.
(3M or equivalent)
Cable clamp: CE3057-12A-3-D
Back shell: CE02-20BS-S-D
(DDK)
IP65
IP67
Not oil-
resistant.
6) Encoder
connector set
MR-J2CNM
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Housing: 1-172161-9
Pin: 170359-1
IP20
(Tyco Electronics or equivalent)
Cable clamp: MTI-0002
(Toa Electric Industry)
7) Encoder
connector set
MR-J2CNS
MR-ENCNS
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Connector: D/MS3106B20-29S
Cable clamp: D/MS3057-12A
(DDK)
IP20
8) Encoder
connector set
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Connector: D/MS3106A20-29S
(D190)
IP65
IP67
Cable clamp: CE3057-12A-3-D
Back shell: CE02-20BS-S-D
(DDK)
14 - 19
14. OPTIONS AND AUXILIARY EQUIPMENT
No.
Product
Model
MR-J2CN1
Description
Application
9) Control signal
connector set
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
(3M or equivalent)
Qty: 2 each
Connector: 10120-6000EL
10) Junction
terminal block
cable
MR-J2TBL
Refer to
M
Connector: HIF3BA-20D-2.54R
(Hirose Electric)
For junction
terminal
block
Shell kit: 10320-3210-000
(3M or equivalent)
section14.1.5.
connection
11) Junction
terminal block
12) Bus cable
MR-TB20
Refer to section 14.1.5.
MR-J2HBUS
Refer to
M
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
Connector: 10120-6000EL
Shell kit: 10320-3210-000
(3M or equivalent)
For
maintenance
junction
card
section14.1.6.
connection
13) Maintenance
junction card
MR-J2CN3TM
Refer to section 14.1.6.
14) Communication MR-CPCATCBL3M Connector: 10120-6000EL
Connector: DE-9SF-N
Case: DE-C1-J6-S6
(JAE)
For
cable
Refer to (3) of this Shell kit: 10320-3210-000
connection
with PC-AT-
compatible
personal
computer
section.
(3M or equivalent)
15) Power supply
connector set
MR-PWCNS1
Refer to the Servo
Motor Instruction
Manual.
Connector: CE05-6A22-23SD-D-BSS
Cable clamp:CE3057-12A-2-D
(DDK)
Must be
used to
16) Power supply
connector set
MR-PWCNS2
Refer to the Servo
Motor Instruction
Manual.
Connector: CE05-6A24-10SD-D-BSS
Cable clamp: CE3057-16A-2-D
(DDK)
comply with
the EN
Standard.
IP65 IP67
17) Power supply
connector set
MR-PWCNS3
Refer to the Servo
Motor Instruction
Manual.
Plug: CE05-6A32-17SD-D-BSS
Cable clamp: CE3057-20A-1-D
(DDK)
18) Brake connector MR-BKCN
Plug: D/MS3106A10SL-4S (D190) (DDK)
Cable connector: YS010-5-8 (Daiwa Dengyo)
EN
set
Refer to the Servo
Standard-
compliant
IP65 IP67
IP20
Motor Instruction
Manual.
19) Power supply
connector set
MR-PWCNK1
Refer to the Servo
Motor Instruction
Manual.
Plug: 5559-04P-210
Terminal: 5558PBT3L (For AWG16)(6 pcs.)
(Molex)
20) Power supply
connector set
MR-PWCNK2
Plug: 5559-06P-210
For motor
with brake
IP20
Terminal: 5558PBT3L (For AWG16)(8 pcs.)
(Molex)
14 - 20
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Encoder cable
If you have fabricated the encoder cable, connect it correctly.
CAUTION
Otherwise, misoperation or explosion may occur.
POINT
The encoder cable is not oil resistant.
Refer to section 13.4 for the flexing life of the encoder cable.
When the encoder cable is used, the sum of the resistance values of the
cable used for P5 and the cable used for LG should be within 2.4 .
When soldering the wire to the connector pin, insulate and protect the
connection portion using heat-shrinkable tubing.
Generally use the encoder cable available as our options. If the required length is not found in the
options, fabricate the cable on the customer side.
(a) MR-JCCBL M-L MR-JCCBL M-H
These encoder cables are used with the HC-KFS HC-MFS HC-UFS3000r/min series servo
motors.
1) Model explanation
Model: MR-JCCBL M-
Symbol
Specifications
Standard flexing life
Long flexing life
L
H
Symbol (Note) Cable length [m(ft)]
2
5
2 (6.56)
5 (16.4)
10
20
30
40
50
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
Note: MR-JCCBL M-H has
no 40m(131.2ft) and 50m(164.0ft) sizes.
2) Connection diagram
For the pin assignment on the servo amplifier side, refer to section 3.3.1.
Encoder cable
Servo amplifier
supplied to servo motor
Encoder connector
Encoder connector
172161-9 (Tyco Electronics)
Servo motor
Encoder
Encoder cable
(option or fabricated)
1
2
3
MR MRR BAT
CN2
4
5
6
MD MDR
50m(164.0ft) max.
30cm
(0.98ft)
7
8
9
P5
LG SHD
14 - 21
14. OPTIONS AND AUXILIARY EQUIPMENT
MR-JCCBL10M-L
MR-JCCBL10M-H
to
MR-JCCBL2M-L
MR-JCCBL5M-L
MR-JCCBL2M-H
MR-JCCBL5M-H
to
MR-JCCBL30M-L
MR-JCCBL50M-H
Servo amplifier side
Encoder side
7
Servo amplifier side
Encoder side
7
Servo amplifier side
Encoder side
7
P5
LG
P5
LG
P5
LG
19
11
20
12
18
2
P5
LG
P5
LG
P5
LG
19
11
20
12
18
2
P5
LG
P5
LG
P5
LG
19
11
20
12
18
2
8
1
2
4
5
3
8
1
2
4
5
3
8
1
2
4
5
3
MR
7
MR
7
MR
7
MRR 17
MD
MDR 16
MRR 17
MD
MDR 16
MRR 17
MD
MDR 16
6
6
6
BAT
LG
9
1
BAT
LG
9
1
BAT
LG
9
1
(Note)
(Note)
(Note)
Plate
Plate
Plate
SD
9
SD
9
SD
9
Note. Always make connection for use in an absolute position detection system.
This wiring is not needed for use in an incremental system.
When fabricating an encoder cable, use the recommended wires given in section 14.2.1 and the MR-
J2CNM connector set for encoder cable fabrication, and fabricate an encoder cable as shown in the
following wiring diagram. Referring to this wiring diagram, you can fabricate an encoder cable of up to
50m(164.0ft) length including the length of the encoder cable supplied to the servo motor.
When the encoder cable is to be fabricated by the customer, the wiring of MD and MDR is not required.
Refer to chapter 3 of the servo motor instruction guide and choose the encode side connector according to
the servo motor installation environment.
For use of AWG22
Servo amplifier side
(3M)
Encoder side
7
19
11
20
12
18
2
P5
LG
P5
LG
P5
LG
8
1
2
7
MR
17
MRR
9
1
3
BAT
LG
(Note)
9
Plate
SD
Note. Always make connection for use in an absolute position detection system.
This wiring is not needed for use in an incremental system.
14 - 22
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-JHSCBL M-L MR-JHSCBL M-H MR-ENCBL M-H
These encoder cables are used with the HC-SFS HC-RFS HC-UFS2000r/min series servo motors.
1) Model explanation
Model: MR-JHSCBL M-
Symbol
Specifications
Standard flexing life
Long flexing life
L
H
Symbol
Cable length [m(ft)]
2
5
2 (6.56)
5 (16.4)
10
20
30
40
50
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
Note: MR-JHSCBL M-L has
no 40(131.2) and 50m(164.0ft) sizes.
Model: MR-ENCBL M-H
Long flexing life
Symbol
Cable length [m(ft)]
2
5
2 (6.56)
5 (16.4)
10
20
30
40
50
10 (32.8)
20 (65.6)
30 (98.4)
40 (131.2)
50 (164.0)
2) Connection diagram
For the pin assignment on the servo amplifier side, refer to section 3.3.1.
Servo amplifier
Encoder connector
Encoder connector
Pin Signal
Pin Signal
K
L
Servo motor
Encoder cable
(Optional or fabricated)
A
B
C
D
E
F
G
H
J
MD
MDR
MR
A
M
T
B
P
C
L
N
M
K
J
D
E
F
MRR
N
P
R
S
SHD
CN2
Encoder
S
R
H
G
BAT
LG
LG
P5
T
50m(164.0ft) max.
14 - 23
14. OPTIONS AND AUXILIARY EQUIPMENT
MR-JHSCBL2M-L
MR-JHSCBL5M-L
MR-JHSCBL2M-H
MR-JHSCBL5M-H
MR-ENCBL2M-H
MR-ENCBL5M-H
MR-JHSCBL10M-L
MR-JHSCBL10M-H
to
to
MR-JHSCBL30M-L
MR-JHSCBL50M-H
MR-ENCBL10M-H
to
MR-ENCBL50M-H
Servo amplifier side
Encoder side Servo amplifier side
Encoder side Servo amplifier side
Encoder side
19
11
20
12
18
2
S
P5
LG
P5
LG
P5
LG
19
11
20
12
7
19
11
20
12
18
2
P5
LG
P5
LG
P5
LG
P5
S
S
LG
P5
LG
R
C
D
MR
MRR
P5
17
18
2
R
C
D
LG
R
C
D
7
MR
9
7
MR
BAT
LG
F
17
MRR 17
MRR
1
G
(Note1)
SD
N
Plate
9
1
BAT
LG
9
1
BAT
LG
F
F
(Note2) Use of AWG24
(Less than 10m(32.8ft))
G
G
(Note1)
(Note1)
SD
SD
N
N
Note1: This wiring is required for use in the absolute
position detection system. This wiring is not
needed for use in the incremental system.
Plate
Plate
Use of AWG22
(10m(32.8ft) to 50m(164.0ft))
Use of AWG24
(10m(32.8ft) to 50m(164.0ft))
2: AWG28 can be used for 5m(16.4ft) or less.
When fabricating an encoder cable, use the recommended wires given in section 14.2.1 and the MR-
J2CNS connector set for encoder cable fabrication, and fabricate an encoder cable in accordance with
the optional encoder cable wiring diagram given in this section. You can fabricate an encoder cable of
up to 50m(164.0ft) length.
Refer to chapter 3 of the servo motor instruction guide and choose the encode side connector according
to the servo motor installation environment.
14 - 24
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Communication cable
POINT
This cable may not be used with some personal computers. After fully
examining the signals of the RS-232C connector, refer to this section and
fabricate the cable.
(a) Model definition
Model : MR-CPCATCBL3M
Cable length 3[m](10[ft])
(b) Connection diagram
MR-CPCATCBL3M
Personal computer side
Servo amplifier side
Plate FG
RXD
TXD
3
2
1
LG
TXD
LG
RXD
GND
RTS
CTS
DSR
DTR
2
5
7
8
6
4
12
11
D-SUB9 pins
Half-pitch 20 pins
When fabricating the cable, refer to the connection diagram in this section.
The following must be observed in fabrication.
1) Always use a shielded, multi-core cable and connect the shield with FG securely.
2) The optional communication cable is 3m(10ft) long. When the cable is fabricated, its maximum
length is 15m(49ft) in offices of good environment with minimal noise.
14 - 25
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.5 Junction terminal block (MR-TB20)
POINT
When using the junction terminal block, you cannot use SG of CN1A-20
and CN1B-20. Use SG of CN1A-4 and CN1B-4.
(1) How to use the junction terminal block
Always use the junction terminal block (MR-TB20) with the junction terminal block cable (MR-J2TBL
M) as a set. A connection example is shown below.
Servo amplifier
Junction terminal block
Cable clamp
MR-TB20
(AERSBAN- ESET)
CN1A
or
Junction terminal
block cable
CN1B
(MR-J2TBL M)
Ground the junction terminal block cable on the junction terminal block side with the standard
accessory cable clamp fitting (AERSBAN- ESET). For the use of the cable clamp fitting, refer to
section 13.2.6, (2)(c).
(2) Terminal labels
The junction terminal block does not include the terminal block labels which indicate the signal
layouts for MR-J2S-CP. Cut off the terminal block label in Appendix 2 at the dotted line and fold it up
at the centerline for use.
1) For CN1A
2) For CN1B
LG PP
COM OPC PG
DOG SG NG
LG VDD DIO MD0 ST2 P15R COM SON LSN RD
MEND
ST1 SG TLA DI1 LSP ALM SD
NP P15R
ZP SD
VC CPO
(3) Outline drawing
[Unit: mm]
([Unit: in.])
126(4.96)
117(4.61)
B10
B1
A1
A10
MITSUBISHI
MR-TB20
16 17 18 19
10 11 12 13 14 15
Terminal
block No.
3
6
0
1
2
5
7
8
9
2- 4.5(0.18)
4
Terminal screw: M3.5
Applicable cable: Max. 2mm2
(Crimping terminal width: 7.2mm (0.283 in) max.)
14 - 26
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Junction terminal block cable (MR-J2TBL M)
Model : MR-J2TBL
M
Symbol Cable length[m(ft)]
05
1
0.5 (1.64)
1 (3.28)
Servo amplifier side (CN1A CN1B) connector (3M)
10120-6000EL (connector)
Junction terminal block side connector (Hirose Electric)
HIF3BA-20D-2.54R (connector)
10320-3210-000 (shell kit)
Pin
No.
Terminal block label Junction terminal
Pin
No.
block terminal No.
For CN1A For CN1B
LG
VC
VDD
CPO
DI0
MEND
MD0
ST1
10
0
11
1
12
2
13
3
14
4
15
5
16
6
17
7
B1
A1
B2
A2
B3
A3
B4
A4
B5
A5
B6
A6
B7
A7
B8
A8
B9
A9
B10
A10
1
2
LG
NP
PP
3
4
5
6
7
8
9
P15R
DOG
COM
SG
OPC
NG
PG
ST2
SG
10
11
12
13
14
15
16
17
18
19
20
Plate
P15R
TLA
COM
DI1
SON
LSP
LSN
ALM
RD
18
8
19
9
ZP
SD
SD
14 - 27
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.6 Maintenance junction card (MR-J2CN3TM)
(1) Usage
The maintenance junction card (MR-J2CN3TM) is designed for use when a personal computer and
analog monitor are used at the same time.
Communication cable
Servo amplifier
Maintenance junction card (MR-J2CN3TM)
Bus cable
MR-J2HBUS
M
CN3B
CN3
CN3A
CN3C
B1 B5 B6 A5 A6
B2
A1 A2 A3 A4 B4 B3
LG LG MO1 MO2
VDD COM EM1 DI MBR EMGO SG PE
Not used.
Analog monitor 2
Analog monitor 1
(2) Connection diagram
TE1
B5
LG
B6
LG
CN3A
CN3B
1
2
3
4
5
6
7
8
CN3C
1
2
3
4
5
6
7
8
A5
1
1
LG
MO1
2
RXD
A6
3
4
5
3
MO2
LG
4
MO1
5
RDP
6
MO73
8
SD9P
9
9
A1
A2
A3
A4
B4
B3
B2
B1
10
VDD
COM
EM1
DI
TRE
10
10
11
12
13
14
15
16
17
18
19
20
10
11
12
13
14
15
16
17
18
19
20
LG
11
TXD
12
13
14
15
LG
13
MO2
14
15
16
17
18
Not used.
MBR
EMGO
SG
19
20
SDN
19
P5
20
Shell
Shell
Shell
PE
14 - 28
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline drawing
[Unit: mm]
([Unit: in])
CN3A
CN3B
CN3C
2- 5.3(0.21)(mounting hole)
A1
B1
A6
B6
TE1
3(0.12)
88(3.47)
41.5(1.63)
100(3.94)
Mass: 110g(0.24Ib)
(4) Bus cable (MR-J2HBUS M)
Model: MR-J2HBUS
M
Symbol
Cable length [m(ft)]
05
1
5
0.5 (1.64)
1 (3.28)
5 (16.4)
MR-J2HBUS05M
MR-J2HBUS1M
MR-J2HBUS5M
10120-6000EL (connector)
10320-3210-000 (shell kit)
10120-6000EL (connector)
10320-3210-000 (shell kit)
1
11
2
1
11
2
12
3
12
3
13
4
13
4
14
5
14
5
15
6
15
6
16
7
16
7
17
8
17
8
18
9
18
9
19
10
20
19
10
20
Plate
Plate
14 - 29
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.7 External digital display (MR-DP60)
The data equivalent to the servo amplifier status display can be displayed on the MR-DP60. When using
the MR-DP60, set "
1
4" in parameter No. 16. The items that appear at the time of power-on can be
selected in parameter No.18.
(1) Specifications
Item
Specifications
Red seven-segment LED, signed, six digits
Single-phase, 85 to 253VAC, 50/60Hz
Within 200mA
Display
Power supply
Permissible voltage fluctuation
Current consumption
Interface
Communication
Conforms to RS-422
Baud rate
4800bps, asynchronous
Bit length
Start bit 1, date bit 8, parity bit 1, stop bit
MELSERVO protocol
1
Protocol
Communication commands
Commands dedicated to MELSERVO
Operating temperature / humidity range
0
to 60 (32 to 140 ),
90%RH or less, non-condensing
Storage temperature range
5
to 70 (23 to 158
)
(2) Connection example
NFB
MC
L1
(Note)
Power supply
L2
Servo amplifier
L3
External digital display
L11
L21
MR-DP60
L1
L2
CN3
5
15
9
RDP
RDN
SDP
SDN
LG
TXD
TXD
RXD
RXD
LG
19
1
Plate
SD
Note. Refer to section 1.2 for the power supply specification.
(3) Terminal arrangement
Signal
Description
L1
L2
100 to 230VAC power input
TB2
Ground
L1
L2
RXD
RXD
TXD
TXD
P5
Receive signal input
Inverse receive signal input
Inverse transmission signal output
Transmission signal output
5VDC output (Note)
TB1
TXD TXD RXDRXD P5 LG
LG
Control common
Note. The 5VDC output is designed for the internal control circuit and used to make a voltage check, etc. Do not use this terminal to
supply a voltage to the other equipment.
14 - 30
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Mounting
[Unit: mm (in)]
Inside mounting
Front mounting
Square hole
Square hole
2- 5 (0.20)
2- 5 (0.20)
95(3.74)
141(5.55)
150(5.91)
150(5.91)
(5) Outline dimension drawing
[Unit: mm (in)]
TB2
TB1
MITSUBISHI
MR-DP60
150(5.91)
7.5
7.5
(0.30)
2- 4.5 (0.18) mounting hole
2- 6.5 (0.26), depth 1 (0.04)
(0.30)
165(6.50)
14 - 31
14. OPTIONS AND AUXILIARY EQUIPMENT
14.1.8 Manual pulse generator (MR-HDP01)
(1) Specifications
Item
Specifications
Voltage
4.5 to 13.2VDC
60mA max.
Power supply
Current consumption
Interface
Output current max. 20mA for open collector output
A-phase and B-phase signals with 90°phase difference
100pulse / rev
Pulse signal form
Pulse resolution
Max. speed
Instantaneous max. 600r/min, ordinary 200r/min
Operating temperature range
Storage temperature range
10 to 60 (14 to 140
30 to 80 22 to 176
)
(
)
(2) Connection example
Use an external power supply to supply power to the manual pulse generator.
Servo amplifier
CN1B
3
VDD
CN1A
11
SV
A
OPC
PP
3
10
2
Manual pulse generator
MR-HDP01
OV
B
SG
NP
External
power
supply
+5
SD
Plate
GND
(3) Terminal arrangement
Signal name
Description
Power input
+5 to
5 to 12V
12V 0V
A
B
0V
A
Power and signal common
A-phase pulse output
B-phase pulse output
B
14 - 32
14. OPTIONS AND AUXILIARY EQUIPMENT
(4) Mounting
[Unit: mm(in)]
Panel cutting
3- 4.8(0.189)
equally divided
(5) Outline dimension drawing
[Unit: mm(in)]
3.6(0.142)
Packing t2.0
3-M4 stud L10
P.C.D.72 equally divided
5V to
12V 0V
A
B
M3 6 may only be used.
7.6(0.299)
27.0
0.5
8.89
(0.35)
16
20
(0.63)(0.787) (1.063
0.02)
14.1.9 Battery (MR-BAT, A6BAT)
POINT
The revision (Edition 44) of the Dangerous Goods Rule of the
International Air Transport Association (IATA) went into effect on
January 1, 2003 and was enforced immediately. In this rule, "provisions of
the lithium and lithium ion batteries" were revised to tighten the
restrictions on the air transportation of batteries. However, since this
battery is non-dangerous goods (non-Class 9), air transportation of 24 or
less batteries is outside the range of the restrictions. Air transportation of
more than 24 batteries requires packing compliant with the Packing
Standard 903. When a self-certificate is necessary for battery safety tests,
contact our branch or representative. For more information, consult our
branch or representative. (As of September, 2007).
Use the battery to build an absolute position detection system.
14 - 33
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2 Auxiliary equipment
Always use the devices indicated in this section or equivalent. To comply with the EN Standard or UL/C-
UL (CSA) Standard, use the products which conform to the corresponding standard.
14.2.1 Recommended wires
(1) Wires for power supply wiring
The following diagram shows the wires used for wiring. Use the wires given in this section or
equivalent.
1) Main circuit power supply lead
3) Motor power supply lead
Servo motor
Servo amplifier
Power supply
L1
U
V
U
V
L2
L3
Motor
W
W
L11
L21
5) Electromagnetic
brake lead
6) Power regeneration
converter lead
2) Control power supply lead
Electro-
magnetic
brake
B1
B2
Power regeneration
converter
N
Regenerative option
C
P
Encoder
Encoder cable (refer to section 14.1.4)
4) Regenerative option lead
The following table lists wire sizes. The wires used assume that they are 600V vinyl wires and the
wiring distance is 30m(98.4ft) max. If the wiring distance is over 30m(98.4ft), choose the wire size in
consideration of voltage drop.
The alphabets (a, b, c) in the table correspond to the crimping terminals (Table 14.2) used to wire the
servo amplifier. For connection with the terminal block TE2 of the MR-J2S-100CP or less, refer to
section 3.11.
The servo motor side connection method depends on the type and capacity of the servo motor. Refer to
section 3.8.
To comply with the UL/C-UL (CSA) Standard, use UL-recognized copper wires rated at 60 (140) or
more for wiring.
Table 14.1 Recommended wires
2
(Note 1) Wires [mm ]
Servo amplifier
1) L1 L2 L3
2) L11 L21
3) U
V
W
4) P
C
5) B1 B2
MR-J2S-10CP(1)
MR-J2S-20CP(1)
MR-J2S-40CP(1)
MR-J2S-60CP
1.25 (AWG16) : a
2 (AWG14) : a
MR-J2S-70CP
2 (AWG14) : a
3.5(AW12) : c
1.25 (AWG16)
1.25 (AWG16)
MR-J2S-100CP
MR-J2S-200CP
2 (AWG14) : a
3.5 (AWG12) : b
(Note 2)
3.5 (AWG12) : b
5.5 (AWG10) : b
8 (AWG8) : c
MR-J2S-350CP
5.5 (AWG10) : b
5.5 (AWG10) : b
8 (AWG8) : c
MR-J2S-500CP
MR-J2S-700CP
Note 1. For the crimping terminals and applicable tools, refer to table 14.2.
2. 3.5mm2 for use of the HC-RFS203 servo motor.
14 - 34
14. OPTIONS AND AUXILIARY EQUIPMENT
Use wires 6) of the following sizes with the power regeneration converter (FR-RC).
Model
Wires[mm2]
FR-RC-15K
14(AWG6)
Table 14.2 Recommended crimping terminals
Servo amplifier side crimping terminals
Symbol
Crimping terminal
32959
Applicable tool
Manufacturer
a
b
47387
YNT-1210S
Tyco Electronics
EVD5.5-4
Body YF-1 E-4
Head YNE-38
Die DH-111 DH-121
Japan Solderless
Terminal
c
FVD8-5
(2) Wires for cables
When fabricating a cable, use the wire models given in the following table or equivalent.
Table 14.3 Wires for option cables
Characteristics of one core
Conductor Insulation coating
[Wires/mm] resistance[ /mm] ODd[mm] (Note 1)
(Note 3)
Finishing
OD [mm]
Length
[m(ft)]
Core size Number
Type
Model
Wire model
Structure
[mm2]
of Cores
2 to 10
(6.56 to 32.8)
20 30
12
(6 pairs)
12
(6 pairs)
12
(6 pairs)
14
(7 pairs)
UL20276 AWG#28
6pair (BLACK)
UL20276 AWG#22
6pair (BLACK)
(Note 2)
0.08
0.3
7/0.127
12/0.18
40/0.08
40/0.08
7/0.127
12/0.18
40/0.08
40/0.08
40/0.08
40/0.08
7/0.127
7/0.127
222
62
0.38
1.2
5.6
8.2
7.2
8.0
4.7
8.2
6.5
7.2
6.5
7.2
4.6
6.1
MR-JCCBL M-L
(65.6 98.4)
2 5
(6.56 16.4)
10 to 50
0.2
105
105
222
62
0.88
0.88
0.38
1.2
A14B2343 6P
(Note 2)
MR-JCCBL M-H
MR-JHSCBL M-L
MR-JHSCBL M-H
0.2
(32.8 to 164)
A14B0238 7P
UL20276 AWG#28
4pair (BLACK)
UL20276 AWG#22
6pair (BLACK)
(Note 2)
A14B2339 4P
(Note 2)
A14B2343 6P
(Note 2)
2 5
(6.56 16.4)
10 to 30
8
0.08
0.3
(4 pairs)
12
(6 pairs)
Encoder cable
(32.8 to 98.4)
2 5
(6.56 16.4)
10 to 50
8
0.2
105
105
105
105
222
222
0.88
0.88
0.88
0.88
0.38
0.38
(4 pairs)
12
(6 pairs)
0.2
(32.8 to 164)
2 5
(6.56 16.4)
10 to 50
8
0.2
(4 pairs)
12
(6 pairs)
A14B2339 4P
(Note 2)
MR-ENCBL M-H
MR-CPCATCBL3M
0.2
(32.8 to 164)
A14B2343 6P
UL20276 AWG#28
3pair (BLACK)
UL20276 AWG#28
10pair (CREAM)
Communication
cable
6
3 (9.84)
0.08
0.08
(3 pairs)
20
(10 pairs)
0.5 to 5
(1.64 to 16.4)
Bus cable
MR-J2HBUS
M
Note 1. d is as shown below.
d
Conductor Insulation sheath
2. Purchased from Toa Electric Industry
3. Standard OD. Max. OD is about 10% greater.
14 - 35
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.2 Circuit breakers, fuses, magnetic contactors
Always use one circuit breaker and one magnetic contactor with one servo amplifier. When using a fuse
instead of the circuit breaker, use the one having the specifications given in this section.
Fuse
Servo amplifier
Circuit breaker
Magnetic contactor
Class Current [A] Voltage [V]
MR-J2S-10CP(1)
MR-J2S-20CP
30 frame 5A
30 frame 5A
30 frame 10A
30 frame 15A
30 frame 15A
30 frame 15A
30 frame 20A
30 frame 30A
50 frame 50A
100 frame 75A
K5
K5
K5
K5
K5
K5
K5
K5
K5
K5
10
10
MR-J2S-40CP 20CP1
MR-J2S-60CP 40CP1
MR-J2S-70CP
15
S-N10
20
20
250AC
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-700CP
25
40
70
S-N18
S-N20
S-N35
S-N50
125
150
14.2.3 Power factor improving reactors
The input power factor is improved to be about 90%. For use with a 1-phase power supply, it may be
slightly lower than 90%.
Servo amplifier
FR-BAL
FR-BAL
FR-BAL
[Unit : mm]
([Unit : in.])
MR-J2S- CP
MC
MC
MC
NFB
R
S
T
X
Y
Z
L1
3-phase
200 to 230VAC
L2
L3
Servo amplifier
MR-J2S- CP
NFB
R
S
T
X
Y
Z
D1
W
L1
L2
L3
(Note)
1-phase
230VAC
Installation screw
RXSYT Z
W1
Servo amplifier
MR-J2S- CP
C
NFB
R
S
T
X
Y
Z
1-phase
100 to120VAC
L1
L2
Note. Connect a 1-phase 230VAC power supply to L1/L2 and keep L3 open.
14 - 36
14. OPTIONS AND AUXILIARY EQUIPMENT
Dimensions [mm (in) ]
Mounting Terminal
screw size screw size
Mass
Servo amplifier
Model
[kg (lb)]
W
W1
H
D
D1
45
(1.77
57
(2.24
55
(2.17
75
(2.95
70
(2.76
100
(3.94
100
(3.94
110
C
MR-J2S-10CP(1)/20CP FR-BAL-0.4K
135 (5.31) 120 (4.72) 115 (4.53) 59 (2.32)
7.5 (0.29)
M4
M4
M4
M4
M5
M5
M6
M6
M3.5
M3.5
M3.5
M3.5
M4
2.0 (4.4)
2.8 (6.17)
3.7 (8.16)
5.6 (12.35)
8.5 (18.74)
14.5 (32.0)
19 (41.9)
)
)
)
)
)
)
)
)
MR-J2S-40CP/20CP1 FR-BAL-0.75K 135 (5.31) 120 (4.72) 115 (4.53) 69 (2.72)
MR-J2S-60CP/ 70CP/
7.5 (0.29)
7.5 (0.29)
7.5 (0.29)
10 (0.39)
10 (0.39)
12.5 (0.49)
12.5 (0.49)
FR-BAL-1.5K
FR-BAL-2.2K
FR-BAL-3.7K
FR-BAL-7.5K
FR-BAL-11K
FR-BAL-15K
160 (6.30) 145 (5.71) 140 (5.51) 71 (2.79)
160 (6.30) 145 (5.71) 140 (5.51) 91 (3.58)
220 (8.66) 200 (7.87) 192 (7.56) 90 (3.54)
220 (8.66) 200 (7.87) 194 (7.64) 120 (4.72)
280 (11.02) 255 (10.04) 220 (8.66) 135 (5.31)
295 (11.61) 270 (10.62) 275 (10.83) 133 (5.24)
40CP1
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-700CP
M5
M6
M6
27 (59.5)
(4.33
14.2.4 Relays
The following relays should be used with the interfaces.
Interface
Selection example
Relay used for input signals (interface DI-1) signals
To prevent defective contacts , use a relay for small signal
(twin contacts).
(Ex.) Omron : type G2A , MY
Relay used for digital output signals (interface DO-1)
Small relay with 12VDC or 24VDC of 40mA or less
(Ex.) Omron : type MY
14.2.5 Surge absorbers
A surge absorber is required for the electromagnetic brake. Use the following surge absorber or equivalent.
Insulate the wiring as shown in the diagram.
Maximum rating
Static
capacity
(reference
value)
Maximum
limit voltage
Varistor voltage
rating (range) V1mA
Permissible circuit
voltage
Surge
immunity
Energy
immunity
Rated
power
AC[Vma]
140
DC[V]
180
[A]
[J]
5
[W]
0.4
[A]
25
[V]
[pF]
[V]
220
(Note)
360
300
500/time
(198 to 242)
Note. 1 time
8
20 s
(Example) ERZV10D221 (Matsushita Electric Industry)
TNR-10V221K (Nippon chemi-con)
Outline drawing [mm] ( [in] ) (ERZ-C10DK221)
13.5 (0.53)
4.7 1.0 (0.19 0.04)
Vinyl tube
Crimping terminal
for M4 screw
0.8 (0.03)
14 - 37
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.6 Noise reduction techniques
Noises are classified into external noises which enter the servo amplifier to cause it to malfunction and
those radiated by the servo amplifier to cause peripheral devices to malfunction. Since the servo amplifier
is an electronic device which handles small signals, the following general noise reduction techniques are
required.
Also, the servo amplifier can be a source of noise as its outputs are chopped by high carrier frequencies. If
peripheral devices malfunction due to noises produced by the servo amplifier, noise suppression measures
must be taken. The measures will vary slightly with the routes of noise transmission.
(1) Noise reduction techniques
(a) General reduction techniques
Avoid laying power lines (input and output cables) and signal cables side by side or do not bundle
them together. Separate power lines from signal cables.
Use shielded, twisted pair cables for connection with the encoder and for control signal
transmission, and connect the shield to the SD terminal.
Ground the servo amplifier, servo motor, etc. together at one point (refer to section 3.10).
(b) Reduction techniques for external noises that cause the servo amplifier to malfunction
If there are noise sources (such as a magnetic contactor, an electromagnetic brake, and many
relays which make a large amount of noise) near the servo amplifier and the servo amplifier may
malfunction, the following countermeasures are required.
Provide surge absorbers on the noise sources to suppress noises.
Attach data line filters to the signal cables.
Ground the shields of the encoder connecting cable and the control signal cables with cable clamp
fittings.
Although a surge absorber is built into the servo amplifier, to protect the servo amplifier and
other equipment against large exogenous noise and lightning surge, attaching a varistor to the
power input section of the equipment is recommended.
14 - 38
14. OPTIONS AND AUXILIARY EQUIPMENT
(c) Techniques for noises radiated by the servo amplifier that cause peripheral devices to malfunction
Noises produced by the servo amplifier are classified into those radiated from the cables connected
to the servo amplifier and its main circuits (input and output circuits), those induced
electromagnetically or statically by the signal cables of the peripheral devices located near the
main circuit cables, and those transmitted through the power supply cables.
Noise radiated directly
from servo amplifier
Noises produced
by servo amplifier
Noises transmitted
in the air
Route 1)
Route 2)
Route 3)
Noise radiated from the
power supply cable
Noise radiated from
servo motor cable
Magnetic induction
noise
Routes 4) and 5)
Static induction
noise
Route 6)
Noises transmitted
through electric
channels
Noise transmitted through
power supply cable
Route 7)
Route 8)
Noise sneaking from
grounding cable due to
leakage current
5)
7)
7)
2)
1)
7)
Sensor
power
supply
Servo
amplifier
2)
Instrument
Receiver
3)
8)
6)
Sensor
4)
3)
Servo motor
M
14 - 39
14. OPTIONS AND AUXILIARY EQUIPMENT
Noise transmission route
Suppression techniques
When measuring instruments, receivers, sensors, etc. which handle weak signals and may
malfunction due to noise and/or their signal cables are contained in a control box together with the
servo amplifier or run near the servo amplifier, such devices may malfunction due to noises
transmitted through the air. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo
amplifier.
1) 2) 3)
3. Avoid laying the power lines (Input cables of the servo amplifier) and signal cables side by side or
bundling them together.
4. Insert a line noise filter to the I/O cables or a radio noise filter on the input line.
5. Use shielded wires for signal and power cables or put cables in separate metal conduits.
When the power lines and the signal cables are laid side by side or bundled together, magnetic
induction noise and static induction noise will be transmitted through the signal cables and
malfunction may occur. The following techniques are required.
1. Provide maximum clearance between easily affected devices and the servo amplifier.
2. Provide maximum clearance between easily affected signal cables and the I/O cables of the servo
amplifier.
4) 5) 6)
3. Avoid laying the power lines (Input cables of the servo amplifier) and signal cables side by side or
bundling them together.
4. Use shielded wires for signal and power cables or put the cables in separate metal conduits.
When the power supply of peripheral devices is connected to the power supply of the servo
amplifier system, noises produced by the servo amplifier may be transmitted back through the
power supply cable and the devices may malfunction. The following techniques are required.
1. Insert the radio noise filter (FR-BIF) on the power cables (Input cables) of the servo amplifier.
2. Insert the line noise filter (FR-BSF01 FR-BLF) on the power cables of the servo amplifier.
When the cables of peripheral devices are connected to the servo amplifier to make a closed loop
circuit, leakage current may flow to malfunction the peripheral devices. If so, malfunction may be
prevented by disconnecting the grounding cable of the peripheral device.
7)
8)
(2) Noise reduction products
(a) Data line filter
Noise can be prevented by installing a data line filter onto the encoder cable, etc.
For example, the ZCAT3035-1330 of TDK and the ESD-SR-25 of NEC Tokin make are available as
data line filters.
As a reference example, the impedance specifications of the ZCAT3035-1330 (TDK) are indicated
below.
This impedances are reference values and not guaranteed values.
[Unit: mm]([Unit: in.])
Impedance[ ]
10 to 100MHz
80
100 to 500MHz
150
39 1(1.54 0.04)
Loop for fixing the
cable band
34 1
(1.34 0.04)
TDK
Product name Lot number
Outline drawing (ZCAT3035-1330)
14 - 40
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge suppressor
The recommended surge suppressor for installation to an AC relay, AC valve, AC electromagnetic
brake or the like near the servo amplifier is shown below. Use this product or equivalent.
MC
Relay
Surge suppressor
Surge suppressor
Surge suppressor
This distance should be short
(within 20cm(0.79 in.)).
(Ex.) 972A.2003 50411
(Matsuo Electric Co., Ltd. 200VAC rating)
Rated
voltage
AC[V]
Outline drawing [Unit: mm] ([Unit: in.])
C [ F] R [
]
Test voltage AC[V]
Vinyl sheath
18 1.5
(0.71 0.06)
Blue vinyl cord
Red vinyl cord
50
(1W)
Across
6(0.24)
200
0.5
T-C 1000(1 to 5s)
10(0.39)or less
15 1(0.59 0.04)
10(0.39)or less
4(0.16)
10 3
(0.39
0.12)
10 3
31(1.22)
(0.39
0.15)
200(7.87)
200(7.87)
48 1.5
or more (1.89 0.06) or more
Note that a diode should be installed to a DC relay, DC valve or
the like.
RA
Maximum voltage: Not less than 4 times the drive voltage of
the relay or the like
Diode
Maximum current: Not less than twice the drive current of
the relay or the like
(c) Cable clamp fitting (AERSBAN- SET)
Generally, the earth of the shielded cable may only be connected to the connector's SD terminal.
However, the effect can be increased by directly connecting the cable to an earth plate as shown
below.
Install the earth plate near the servo amplifier for the encoder cable. Peel part of the cable sheath
to expose the external conductor, and press that part against the earth plate with the cable clamp.
If the cable is thin, clamp several cables in a bunch.
The clamp comes as a set with the earth plate.
Cable
Cable clamp
Earth plate
(A,B)
Strip the cable sheath of
the clamped area.
cutter
cable
External conductor
Clamp section diagram
14 - 41
14. OPTIONS AND AUXILIARY EQUIPMENT
Outline drawing
[Unit: mm]
([Unit: in.])
Earth plate
Clamp section diagram
2- 5(0.20) hole
installation hole
17.5(0.69)
L or less
10(0.39)
22(0.87)
6
(Note)M4 screw
35(1.38)
(0.24)
Note:Screw hole for grounding. Connect it to the earth plate of the control box.
Type
A
B
C
Accessory fittings
Clamp fitting
L
100
86
30
70
AERSBAN-DSET
clamp A: 2pcs.
A
(3.94) (3.39) (1.18)
70 56
(2.76) (2.20)
(2.76)
45
AERSBAN-ESET
clamp B: 1pc.
B
(1.77)
14 - 42
14. OPTIONS AND AUXILIARY EQUIPMENT
(d) Line noise filter (FR-BLF, FR-BSF01)
This filter is effective in suppressing noises radiated from the power supply side and output side of
the servo amplifier and also in suppressing high-frequency leakage current (zero-phase current)
especially within 0.5MHz to 5MHz band.
Connection diagram
Outline drawing [Unit: mm] ([Unit: in.])
Use the line noise filters for wires of the main power supply
FR-BSF01(for MR-J2S-200CP or less)
Approx.110(4.33)
(L1 L2
L3) and of the motor power supply (U
V
W). Pass
each of the 3-phase wires through the line noise filter an equal
number of times in the same direction. For the main power supply,
the effect of the filter rises as the number of passes increases, but
generally four passes would be appropriate. For the motor power
supply, passes must be four times or less. Do not pass the
grounding (earth) wire through the filter, or the effect of the filter
will drop. Wind the wires by passing through the filter to satisfy the
required number of passes as shown in Example 1. If the wires
are too thick to wind, use two or more filters to have the required
number of passes as shown in Example 2. Place the line noise
filters as close to the servo amplifier as possible for their best
performance.
2- 5(0.20)
95 0.5(3.74 0.02)
Approx.65 (2.56)
33(1.30)
Example 1
NFB MC
Servo amplifier
Power
supply
L1
L2
L3
FR-BLF (MR-J2S-350CP or more)
7(0.28)
Line noise
filter
(Number of turns: 4)
130(5.12)
85(3.35)
Example 2
MC
NFB
Servo amplifier
Power
supply
L1
L2
L3
160(6.30)
180(7.09)
Line noise
filter
Two filters are used
(Total number of turns: 4)
(e) Radio noise filter (FR-BIF)...for the input side only
This filter is effective in suppressing noises radiated from the power supply side of the servo
amplifier especially in 10MHz and lower radio frequency bands. The FR-BIF is designed for the
input only.
Connection diagram
Outline drawing (Unit: mm) ([Unit: in.])
Leakage current: 4mA
Make the connection cables as short as possible.
Grounding is always required.
Red White Blue
Green
When using the FR-BIF with a single-phase wire,
always insulate the wires that are not used for wiring.
Servo amplifier
NFB
MC
L1
Power
supply
L2
29 (1.14)
5 (0.20)
hole
L3
Radio noise
filter FR-BIF
29 (1.14)
44 (1.73)
58 (2.28)
7 (0.28)
14 - 43
14. OPTIONS AND AUXILIARY EQUIPMENT
(f) Varistors for input power supply (Recommended)
Varistors are effective to prevent exogenous noise and lightning surge from entering the servo
amplifier. When using a varistor, connect it between each phase of the input power supply of the
equipment. For varistors, the TND20V-431K and TND20V-471K, manufactured by NIPPON
CHEMI-CON, are recommended. For detailed specification and usage of the varistors, refer to the
manufacturer catalog.
Maximum rating
Static
capacity
(reference
value)
Varistor voltage
rating (range)
V1mA
Maximum limit
voltage
Rated
pulse
power
[W]
Permissible circuit Surge current
Energy
Varistor
voltage
immunity
immunity
AC[Vrms]
DC[V]
350
8/20 s[A]
10000/1 time
7000/2 time
2ms[J]
195
[A]
[V]
710
775
[pF]
1300
1200
[V]
TND20V-431K
TND20V-471K
275
300
430(387 to 473)
470(423 to 517)
1.0
100
385
215
[Unit: mm]
D
H
T
E
(Note)L
min.
d
W
D
T
Model
Max.
Max.
Max.
1.0
0.05
1.0
TND20V-431K
TND20V-471K
6.4
6.6
3.3
3.5
21.5
24.5
20
0.8
10.0
Note. For special purpose items for lead length (L), contact the manufacturer.
W
E
d
14 - 44
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.7 Leakage current breaker
(1) Selection method
High-frequency chopper currents controlled by pulse width modulation flow in the AC servo circuits.
Leakage currents containing harmonic contents are larger than those of the motor which is run with a
commercial power supply.
Select a leakage current breaker according to the following formula, and ground the servo amplifier,
servo motor, etc. securely.
Make the input and output cables as short as possible, and also make the grounding cable as long as
possible (about 30cm (11.8 in)) to minimize leakage currents.
Rated sensitivity current 10 {Ig1 Ign Iga K (Ig2 Igm)} [mA] ..........(14.1)
K: Constant considering the harmonic contents
Cable
Leakage current breaker
K
Type
Mitsubishi products
Noise
filter
NV
NV-SP
NV-SW
NV-CP
NV-CW
NV-HW
BV-C1
NFB
Servo
amplifier
Cable
Ig2
M
Models provided with
harmonic and surge
reduction techniques
1
3
Ig1 Ign
Iga
Igm
General models
NV-L
Ig1:
Ig2:
Leakage current on the electric channel from the leakage current breaker to the input terminals
of the servo amplifier (Found from Fig. 14.1.)
Leakage current on the electric channel from the output terminals of the servo amplifier to the
servo motor (Found from Fig. 14.1.)
Ign:
Iga:
Igm:
Leakage current when a filter is connected to the input side (4.4mA per one FR-BIF)
Leakage current of the servo amplifier (Found from Table 14.5.)
Leakage current of the servo motor (Found from Table 14.4.)
Table 14.4 Servo motor's
leakage current
Table 14.5 Servo amplifier's
leakage current
120
100
80
60
40
20
0
example (Igm)
example (Iga)
Servo motor
output [kW]
Leakage
current [mA]
Servo amplifier
Leakage
capacity [kW]
current [mA]
0.05 to 0.5
0.6 to 1.0
1.2 to 2.2
3 to 3.5
5
0.1
0.1
0.2
0.3
0.5
0.7
0.1 to 0.6
0.1
0.15
2
0.7 to 3.5
5
7
[mA]
7
Table 14.6 Leakage circuit breaker selection example
Rated sensitivity
2
3.5 8 1422 38 80 150
5.5 30 60 100
Cable size[mm2]
Servo amplifier
current of leakage
circuit breaker [mA]
Fig. 14.1 Leakage current example
(Ig1, Ig2) for CV cable run
in metal conduit
MR-J2S-10CP to MR-J2S-350CP
MR-J2S-10CP1 to MR-J2S-40CP1
MR-J2S-500CP
15
30
50
MR-J2S-700CP
14 - 45
14. OPTIONS AND AUXILIARY EQUIPMENT
(2) Selection example
Indicated below is an example of selecting a leakage current breaker under the following conditions.
2mm2 5m(196.85inch)
2mm2 5m(196.85inch)
NV
Servo
amplifier
M
HC-MFS73
MR-J2S-60CP
Ig1
Iga
Ig2
Igm
Use a leakage current breaker designed for suppressing harmonics/surges.
Find the terms of Equation (14.1) from the diagram.
5
1000
Ig1
Ig2
20
20
0.1 [mA]
0.1 [mA]
5
1000
Ign 0 (not used)
Iga 0.1 [mA]
Igm 0.1 [mA]
Insert these values in Equation (14.1).
Ig 10 {0.1 0 0.1 1 (0.1 0.1)}
4 [mA]
According to the result of calculation, use a leakage current breaker having the rated sensitivity
current (Ig) of 4[mA] or more. A leakage current breaker having Ig of 15[mA] is used with the NV-
SP/CP/ SW/CW/HW series.
14 - 46
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.8 EMC filter
For compliance with the EMC Directive of the EN Standard, it is recommended to use the following filter.
Some EMC filters are large in leakage current.
(1) Combination with the servo amplifier
Recommended filter
Servo amplifier
Mass [kg]([lb])
Model
Leakage current [mA]
MR-J2S-10CP to MR-J2S-100CP
MR-J2S-10CP1 to MR-J2S-40CP1
MR-J2S-200CP MR-J2S-350CP
MR-J2S-500CP
SF1252
38
0.75 (1.65)
SF1253
57
1.5
1.5
1.37 (1.65)
5.5 (12.13)
6.7 (14.77)
(Note) HF-3040A-TM
(Note) HF-3050A-TM
MR-J2S-700CP
Note. Soshin Electric. A surge protector is separately required to use any of these EMC filters. (Refer to the EMC Installation
Guidelines.)
(2) Connection example
EMC filter
EMC filter
(SOSHIN Electric Co., Ltd)
(SF1252, SF1253)
Servo amplifier
Servo amplifier
NFB
NFB
MC
MC
LINE
LOAD
L1
L2
L3
L1
L2
L3
L1
L2
L3
L1
L2
L3
1
2
3
4
5
6
E
(Note 1)
Power
supply
(Note 1)
Power
supply
(Note 2)
L11
L21
L11
L21
1
2
3
Surge protector 1
(RAV-781BYZ-2)
(OKAYA Electric Industries
Co., Ltd.)
Surge protector 2
(RAV-781BXZ-4)
1 2 3
(OKAYA Electric Industries Co., Ltd.)
Note 1. For 1-phase 230VAC power supply, connect the power supply to L1,L2 and leave L3 open.
There is no L3 for 1-phase 100 to 120VAC power supply. Refer to section 1.2 for the power supply specification.
2. Connect when the power supply has earth.
14 - 47
14. OPTIONS AND AUXILIARY EQUIPMENT
(3) Outline drawing
(a) EMC filter
[Unit: mm(in)]
6.0(0.236)
SF1252
SF1253
6.0(0.236)
LINE
149.5(5.886)
209.5(8.248)
L1
L2
L3
L1
L2
L3
LINE
(input side)
(input side)
L1'
L2'
L3'
L1'
L2'
L3'
LOAD
(output side)
LOAD
(output side)
8.5
(0.335)
16.0(0.63)
23.0(0.906)
8.5
(0.335)
42.0
49.0
(1.654)
(1.929)
HF3040-TM HF-3050A-TM
6-K
3-L
3-L
M
J
2
C
1
C
1
H
2
B
A
2
5
Dimensions [mm(in)]
Model
A
B
C
D
E
F
G
H
J
K
L
M
260
210
85
155
140
125
(4.92)
160
44
140
70
HF3040A-TM
HF3050A-TM
M5
M6
M4
R3.25,
length 8
(10.23) (8.27)
290 240
(11.42) (9.45)
(3.35)
100
(6.10)
190
(5.51)
175
(1.73)
44
(5.51)
170
(2.76)
100
M4
(3.94)
(7.48)
(6.89)
(6.30)
(1.73)
(5.51)
(3.94)
14 - 48
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) Surge protector
[Unit: mm]
RAV-781BYZ-2
1)
2)
3)
Black Black Black
4.2 0.2
UL-1015AWG16
1
2
3
41 1.0
[Unit: mm]
RAV-781BXZ-4
1)
2)
3)
4)
4.2 0.2
UL-1015AWG16
1
2
3
41 1.0
14 - 49
14. OPTIONS AND AUXILIARY EQUIPMENT
14.2.9 Setting potentiometers for analog inputs
The following variable resistors are available for use with analog inputs.
(1) Single-revolution type
WA2WYA2SEBK2K (Japan Resistor make)
Resistance
tolerance
Dielectric strength
(for 1 minute)
Insulation
resistance
Mechanical
rotary angle
Rated power Resistance
2W 2k
Rotary torque
10%
700V A.C
100M or more
300
5
10 to 100g-cm or less
Connection diagram
Outline dimension drawing
Panel hole machining diagram
[Unit: mm (in)]
[Unit: mm (in)]
20 (0.79)
2.5 (0.10)
25 (0.98)
10 (0.39)
30 (1.18)
2.8 (0.11)
3.6 (0.14) hole
10 (0.37) hole
1.6 (0.06)
1
2
3
M9 0.75 (0.03)
3
(0.08)
3- 1.54 (0.56) hole
1
3
2
(2) Multi-revolution type
Position meter: RRS10M202 (Japan Resistor make)
Analog dial: 23M (Japan Resistor make)
Resistance
tolerance
Dielectric strength
(for 1 minute)
Insulation
resistance
Mechanical
Rotary torque
rotary angle
Rated power Resistance
10
0
1W 2k
10%
700V A.C
1000M or more
3600
100g-cm or less
Connection diagram
Panel hole machining diagram
1
3
[Unit: mm (in)]
Panel thickness: 2 to 6 (0.08 to 0.24)
CW
2
9 (0.35) hole
2.1 (0.08) hole
Outline dimension drawing
RRS10M202
23M
[Unit: mm (in)]
12.5 (0.49)
[Unit: mm (in)]
1)
15 (0.59)
2)
3)
30
3)
1)
2)
M9 0.75 (0.03)
12 (0.47)
6 (0.24)
1.2
(0.05)
20.5
(0.81)
7.5
(0.3)
23 (0.91)
L
14 - 50
15. COMMUNICATION FUNCTIONS
15. COMMUNICATION FUNCTIONS
This servo amplifier has the RS-422 and RS-232C serial communication functions. These functions can be
used to perform servo operation, parameter changing, monitor function, etc.
However, the RS-422 and RS-232C communication functions cannot be used together. Select between RS-
422 and RS-232C with parameter No.16. (Refer to section 15.2.2.)
15.1 Configuration
15.1.1 RS-422 configuration
(1) Outline
Up to 32 axes of servo amplifiers from stations 0 to 31 can be operated on the same bus.
Servo amplifier
Servo amplifier
Servo amplifier
MITSUBISHI
MITSUBISHI
MITSUBISHI
Controller such as
personal computer
CHARGE
CHARGE
CHARGE
To CN3
To CN3
To CN3
RS-232C/
RS-422
converter
Axis 1 (Station 0)
Axis 2 (Station 1)
RS-422
Axis 32 (Station 31)
Unavailable as option.
To be prepared by customer.
(2) Cable connection diagram
Wire as shown below.
(Note 3) 30m (98.4ft) or less
(Note 1)
Axis 32 (last axis)
(Note 1)
(Note 1)
servo amplifier
CN3 connector
Axis 1 servo amplifier
CN3 connector
Axis 2 servo amplifier
CN3 connector
Plate
9
SD
Plate
9
Plate SD
SD
SDP
SDN
RDP
RDN
TRE
LG
9
19
5
SDP
SDN
RDP
RDN
TRE
LG
SDP
SDN
RDP
RDN
TRE
LG
19
5
19
5
15
10
11
1
15
10
11
1
15
10
11
1
(Note 2)
LG
LG
LG
RS-422
output unit
RDP
RDN
SDP
SDN
GND
GND
Note 1. Connector set MR-J2CN1 (3M)
Connector: 10120-3000PE
Shell kit: 10320-52F0-008
2. In the last axis, connect TRE and RDN.
3. 30m (98.4ft) or less in environment of little noise.
15 - 1
15. COMMUNICATION FUNCTIONS
15.1.2 RS-232C configuration
(1) Outline
A single axis of servo amplifier is operated.
Servo amplifier
MITSUBISHI
CHARGE
To CN3
RS-232C
Controller such as
personal computer
(2) Cable connection diagram
Wire as shown below. The communication cable for connection with the personal computer (MR-
CPCATCBL3M) is available. (Refer to section 14.1.4.)
(Note 1)
Servo amplifier
CN3 connector
(Note 2) 15m (49.2ft) or less
Personal computer
connector D-SUB9 (socket)
Plate
2
FG
RXD
GND
TXD
GND
3
TXD
1
12
11
2
5
7
8
6
4
RXD
GND
RTS
CTS
DSR
DTR
Note 1. Connector set MR-J2CN1 (3M)
Connector: 10120-6000EL
Shell kit: 10320-3210-000
2. 15m (49.2ft) or less in environment of little noise. However, this distance should be 3m (9.84ft) or less for use at 38400bps
or more baud rate.
15 - 2
15. COMMUNICATION FUNCTIONS
15.2 Communication specifications
15.2.1 Communication overview
This servo amplifier is designed to send a reply on receipt of an instruction. The device which gives this
instruction (e.g. personal computer) is called a master station and the device which sends a reply in
response to the instruction (servo amplifier) is called a slave station. When fetching data successively, the
master station repeatedly commands the slave station to send data.
Item
Baud rate
Description
9600/19200/38400/57600 asynchronous system
Start bit
Data bit
Parity bit
Stop bit
: 1 bit
: 8 bits
: 1 bit (even)
: 1 bit
Transfer code
Transfer protocol Character system, half-duplex communication system
(LSB)
0
(MSB)
7
Next
start
Start
Parity
Stop
1
2
3
4
5
6
Data
1 frame (11bits)
15 - 3
15. COMMUNICATION FUNCTIONS
15.2.2 Parameter setting
When the RS-422/RS-232C communication function is used to operate the servo, set the communication
specifications of the servo amplifier in the corresponding parameters.
After setting the values of these parameters, they are made valid by switching power off once, then on
again.
(1) Serial communication baud rate
Choose the communication speed. Match this value to the communication speed of the sending end
(master station).
Parameter No. 16
Communication baud rate
0: 9600[bps]
1: 19200[bps]
2: 38400[bps]
3: 57600[bps]
(2) Serial communication selection
Select the RS-422 or RS-232C communication standard. RS-422 and RS-232C cannot be used together.
Parameter No. 16
Serial communication standard selection
0: RS-232C used
1: RS-422 used
(3) Serial communication response delay time
Set the time from when the servo amplifier (slave station) receives communication data to when it
sends back data. Set "0" to send back data in less than 800 s or "1" to send back data in 800 s or more.
Parameter No. 16
Serial communication response delay time
0: Invalid
1: Valid, reply sent in 800 s or more
(4) Station number setting
Set the station number of the servo amplifier in parameter No. 15. The setting range is stations 0 to
31.
(5) Protocol station number selection
When communication is made without setting station numbers to servo amplifiers, choose "no station
numbers" in parameter No. 57. The communication protocol will be free of station numbers.
Parameter No. 57
Protocol station number selection
0: With station numbers
1: No station numbers
15 - 4
15. COMMUNICATION FUNCTIONS
15.3 Protocol
POINT
Whether station number setting will be made or not must be selected if
the RS-232C communication function is used. Note that choosing "no
station numbers" in parameter No. 57 will make the communication
protocol free of station numbers.
Since up to 32 axes may be connected to the bus, add a station number or group to the command, data
No., etc. to determine the destination servo amplifier of data communication. Set the station number to
each servo amplifier using the parameter and set the group to each station using the communication
command. Transmission data is valid for the servo amplifier of the specified station number or group.
When " " is set as the station number added to the transmission data, the transmission data is made
*
valid for all servo amplifiers connected. However, when return data is required from the servo amplifier
in response to the transmission data, set "0" to the station number of the servo amplifier which must
provide the return data.
(1) Transmission of data from the controller to the servo
10 frames (data)
S
O
H
S
T
X
E
T
X
Controller side
(Master station)
Data
No.
Check
sum
Station number
Data*
or
group
S
T
X
E
T
X
Servo side
(Slave station)
Station number
Check
sum
or
group
6 frames
Positive response: Error code
A
Negative response: Error code other than A
(2) Transmission of data request from the controller to the servo
10 frames
S
O
H
S
T
X
E
T
X
Data
No.
Check
sum
Station number
Controller side
(Master station)
or
group
S
T
X
E
T
X
Station number
Check
sum
Servo side
(Slave station)
Data*
or
group
6 frames (data)
15 - 5
15. COMMUNICATION FUNCTIONS
(3) Recovery of communication status by time-out
EOT causes the servo to return to
the receive neutral status.
E
O
T
Controller side
(Master station)
Servo side
(Slave station)
(4) Data frames
The data length depends on the command.
or
Data
Data
or 12 frames or 16 frames
4 frames
8 frames
15 - 6
15. COMMUNICATION FUNCTIONS
15.4 Character codes
(1) Control codes
Hexadecimal
Personal computer terminal key operation
(General)
Code name
Description
(ASCII code)
SOH
STX
ETX
EOT
01H
02H
03H
04H
start of head
start of text
ctrl
ctrl
ctrl
ctrl
A
B
C
D
end of text
end of transmission
(2) Codes for data
ASCII codes are used.
b
8
b
7
b
6
b
5
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
b to
C
8
b
4
b
3
b
2
b
1
0
1
2
3
4
5
6
7
b
R
5
0
0
0
0
0
NUL DLE Space
0
1
2
3
4
5
6
7
8
9
:
@
A
B
C
D
E
F
G
H
I
P
Q
R
S
`
a
b
c
p
q
r
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
0
0
0
1
1
1
1
0
0
0
0
1
1
1
1
0
1
1
0
0
1
1
0
0
1
1
0
0
1
1
1
0
1
0
1
0
1
0
1
0
1
0
1
0
1
1
2
3
4
5
6
7
8
9
SOH DC
STX DC
ETX DC
!
“
1
2
3
#
$
%
&
‘
s
T
U
V
W
X
Y
Z
d
e
f
t
u
v
w
x
y
z
{
g
h
i
(
)
10
11
12
13
14
15
J
j
;
K
L
M
N
O
[
k
l
,
|
}
]
m
n
o
_
.
/
^
_
?
DEL
(3) Station numbers
You may set 32 station numbers from station 0 to station 31 and the ASCII unit codes are used to
specify the stations.
Station number
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
10
A
11
B
12
C
13
D
14
E
15
F
ASCII code
Station number
16
G
17
H
18
I
19
J
20
K
21
L
22
M
23
N
24
O
25
P
26
Q
27
R
28
S
29
T
30
U
31
V
ASCII code
For example, "30H" is transmitted in hexadecimal for the station number of "0" (axis 1).
(4) Group
Group
ASCII code
a
a
b
b
c
c
d
d
e
e
f
f
All group
For example, "61H" is transmitted in hexadecimal for group a.
15 - 7
15. COMMUNICATION FUNCTIONS
15.5 Error codes
Error codes are used in the following cases and an error code of single-code length is transmitted.
On receipt of data from the master station, the slave station sends the error code corresponding to that
data to the master station.
The error code sent in upper case indicates that the servo is normal and the one in lower case indicates
that an alarm occurred.
Error code
Error name
Description
Remarks
Servo normal
Servo alarm
[A]
[B]
[C]
[a]
[b]
[c]
Normal operation
Parity error
Data transmitted was processed properly.
Parity error occurred in the transmitted data.
Checksum error occurred in the transmitted data.
Character not existing in the specifications was
transmitted.
Positive response
Checksum error
[D]
[E]
[F]
[d]
[e]
[f]
Character error
Command error
Data No. error
Negative response
Command not existing in the specifications was
transmitted.
Data No. not existing in the specifications was
transmitted.
15.6 Checksum
The checksum is a ASCII-coded hexadecimal representing the lower two digits of the sum of ASCII-coded
hexadecimal numbers up to ETX, with the exception of the first control code (STX or SOH).
Station number
(Example)
or
group
S
T
X
E
T
X
[0] [A] [1] [2] [5] [F]
[5] [2]
02H 30H 41H 31H 32H 35H 46H 03H
STX or
SOH
ETX Check
30H 41H 31H 32H 35H 46H 03H
152H
Checksum range
Lower 2 digits 52 is sent after conversion into ASCII code [5][2].
15 - 8
15. COMMUNICATION FUNCTIONS
15.7 Time-out operation
The master station transmits EOT when the slave station does not start reply operation (STX is not
received) 300[ms] after the master station has ended communication operation. 100[ms] after that, the
master station retransmits the message. Time-out occurs if the slave station does not answer after the
master station has performed the above operation three times. (Communication error)
100ms
100ms
100ms
*Time-out
300ms
300ms
300ms
300ms
E
O
T
E
O
T
E
O
T
Controller
(Master station)
Servo
(Slave station)
15.8 Retry operation
When a fault occurs in communication between the master and slave stations, the error code in the
response data from the slave station is a negative response code ([B] to [F], [b] to [f]). In this case, the
master station retransmits the message which was sent at the occurrence of the fault (Retry operation). A
communication error occurs if the above operation is repeated and results in the error three or more
consecutive times.
*Communication error
Controller
(Master station)
Servo
(Slave station)
S
T
X
S
T
X
S
T
X
Station number
Station number
Station number
or
or
or
group
group
group
Similarly, when the master station detects a fault (e.g. checksum, parity) in the response data from the
slave station, the master station retransmits the message which was sent at the occurrence of the fault. A
communication error occurs if the retry operation is performed three times.
15 - 9
15. COMMUNICATION FUNCTIONS
15.9 Initialization
After the slave station is switched on, it cannot reply to communication until the internal initialization
processing terminates. Hence, at power-on, ordinary communication should be started after.
(1) 1s or more time has elapsed after the slave station is switched on; and
(2) Making sure that normal communication can be made by reading the parameter or other data which
does not pose any safety problems.
15.10 Communication procedure example
The following example reads the set value of parameter No.2 "function selection 1" from the servo
amplifier of station 0.
Data item
Station number
Command
Value
0
Description
Servo amplifier station 0
Read command
05
Data No.
02
Parameter No.2
Axis No. Command
Data No.
ETX
Start
Data [0] 0 5 STX 0 2 ETX
Data make-up
[0][0][5]
[0][2]
STX
Checksum 30H 30H 35H 02H 30H 32H 03H FCH
Checksum calculation and
addition
Transmission data SOH
0 5 STX 0 2 ETX F C 46H 43H
Master station slave station
0
Addition of SOH to make
up transmission data
Data transmission
Data receive
Master station slave station
No
Is there receive data?
Yes
No
300ms elapsed?
Yes
No
3 consecutive times?
Yes
Master station slave station
Yes
Other than error code
[A] [a]?
100ms after EOT transmission
No
3 consecutive times?
No
Error processing
Yes
Receive data analysis
Error processing
End
15 - 10
15. COMMUNICATION FUNCTIONS
15.11 Command and data No. list
POINT
If the command/data No. is the same, its data may be different from the
interface and drive units and other servo amplifiers.
15.11.1 Read commands
(1) Status display (Command [0][1])
Command Data No.
Description
Display item
Current position
Frame length
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[0][1]
[8][0]
[8][1]
[8][2]
[8][3]
[8][4]
[8][5]
[8][6]
[8][7]
[8][8]
[8][9]
[8][A]
[8][B]
[8][C]
[8][D]
[8][E]
[8][F]
[9][0]
Status display data value and
processing information
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
Command position
Command remaining distance
Point table No.
Cumulative feedback pulses
Servo motor speed
Droop pulses
Override
Torque limit voltage
Regenerative load ratio
Effective load ratio
Peak load ratio
Instantaneous torque
Within one-revolution position
ABS counter
Load inertia moment ratio
Bus voltage
(2) Parameter (Command [0][5])
Command Data No.
Description
Frame length
Current value of each parameter
[0][0] to
[5][A]
[0][5]
The decimal equivalent of the data No. value (hexadecimal) corresponds
to the parameter number.
8
(3) External I/O signals (Command [1][2])
Command Data No.
Description
Frame length
[1][2]
[1][2]
[1][2]
[1][2]
[1][2]
[0][0]
[4][0]
[6][0]
[8][0]
[C][0]
Input device statuses
8
8
8
8
8
External input pin statuses
Statuses of input devices switched on through communication
Output device statuses
External output pin statuses
15 - 11
15. COMMUNICATION FUNCTIONS
(4) Alarm history (Command [3][3])
Command Data No.
Description
Alarm occurrence sequence
Most recent alarm
Frame length
[3][3]
[3][3]
[3][3]
[3][3]
[3][3]
[3][3]
[3][3]
[3][3]
[3][3]
[3][3]
[3][3]
[3][3]
[1][0]
[1][1]
[1][2]
[1][3]
[1][4]
[1][5]
[2][0]
[2][1]
[2][2]
[2][3]
[2][4]
[2][5]
Alarm number in alarm history
4
4
4
4
4
4
8
8
8
8
8
8
First alarm in past
Second alarm in past
Third alarm in past
Fourth alarm in past
Fifth alarm in past
Most recent alarm
Alarm occurrence time in alarm
history
First alarm in past
Second alarm in past
Third alarm in past
Fourth alarm in past
Fifth alarm in past
(5) Current alarm (Command [0][2] [3][5])
Command Data No.
Description
Frame length
[0][2]
[0][0]
Current alarm number
4
Command Data No.
Description
Status display item
Current position
Frame length
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[3][5]
[8][0]
[8][1]
[8][2]
[8][3]
[8][4]
[8][5]
[8][6]
[8][7]
[8][8]
[8][9]
[8][A]
[8][B]
[8][C]
[8][D]
[8][E]
[8][F]
[9][0]
Status display data value and
processing information at alarm
occurrence
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
12
Command position
Command remaining distance
Point table No.
Cumulative feedback pulses
Servo motor speed
Droop pulses
Override
Torque limit voltage
Regenerative load ratio
Effective load ratio
Peak load ratio
Instantaneous torque
Within one-revolution position
ABS counter
Load inertia moment ratio
Bus voltage
15 - 12
15. COMMUNICATION FUNCTIONS
(6) Point table/position data (Command [4][0])
Command Data No.
Description
Frame length
Position data read
[0][1] to
[4][0]
The decimal equivalent of the data No. value (hexadecimal) corresponds
to the Point table No.
8
[1][F]
(7) Point table/speed data (Command [5][0])
Command Data No.
Description
Frame length
Speed data read
[0][1] to
[5][0]
The decimal equivalent of the data No. value (hexadecimal) corresponds
to the Point table No.
8
[1][F]
(8) Point table/acceleration time constant (Command [5][4])
Command Data No.
Description
Frame length
Acceleration time constant read
[0][1] to
[5][4]
The decimal equivalent of the data No. value (hexadecimal) corresponds
to the Point table No.
8
[1][F]
(9) Point table/deceleration time constant (Command [5][8])
Command Data No.
Description
Frame length
Deceleration time constant read
[0][1] to
[5][8]
The decimal equivalent of the data No. value (hexadecimal) corresponds
to the Point table No.
8
[1][F]
(10) Point table/dwell (Command [6][0])
Command Data No.
Description
Frame length
Dwell read
[0][1] to
[6][0]
The decimal equivalent of the data No. value (hexadecimal) corresponds
to the Point table No.
8
[1][F]
(11) Point table/auxiliary function (Command [6][4])
Command Data No.
Description
Frame length
Auxiliary function read
[0][1] to
[6][4]
The decimal equivalent of the data No. value (hexadecimal) corresponds
to the Point table No.
8
[1][F]
(12) Group setting (Command [1][F])
Command Data No.
Description
Description
Frame length
[1][F]
[0][0]
Reading of group setting value
4
(13) Software version (Command [0][2])
Command Data No.
Frame length
[0][2]
[7][0]
Software version
16
15 - 13
15. COMMUNICATION FUNCTIONS
15.11.2 Write commands
(1) Status display (Command [8][1])
Command Data No.
Description
Description
Setting range Frame length
1EA5
[8][1]
[0][0]
Status display data clear
4
(2) Parameter (Command [8][4])
Command Data No.
Setting range Frame length
Each parameter write
Depends on
[0][0] to
[5][A]
[8][4]
The decimal equivalent of the data No. value
the parameter.
8
(hexadecimal) corresponds to the parameter number.
(3) External I/O signal (Command [9][2])
Command Data No.
Description
Setting range Frame length
Communication input device signal
Refer to
8
[9][2]
[6][0]
section 15.12.5
(4) Alarm history (Command [8][2])
Command Data No.
Description
Description
Description
Setting range Frame length
[8][2]
[2][0]
Alarm history clear
1EA5
4
(5) Current alarm (Command [8][2])
Command Data No.
Setting range Frame length
1EA5
[8][2]
[0][0]
Alarm reset
4
(6) Point table/position data (Command [C][0])
Command Data No.
Setting range Frame length
Position data write
[0][1] to
999999 to
[C][0]
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
999999
8
[1][F]
(7) Point table/speed data (Command [C][6])
Command Data No.
Description
Setting range Frame length
Speed data write
[0][1] to
0 to Permissible
[C][6]
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
instantaneous
speed
8
[1][F]
(8) Point table/acceleration time constant (Command [C][7])
Command Data No.
Description
Setting range Frame length
Acceleration time constant write
0 to 20000
8
[0][1] to
[C][7]
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
[1][F]
15 - 14
15. COMMUNICATION FUNCTIONS
(9) Point table/deceleration time constant (Command [C][8])
Command Data No.
Description
Setting range Frame length
Deceleration time constant write
0 to 20000
8
[0][1] to
[C][8]
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
[1][F]
(10) Point table/dwell (Command [C][A])
Command Data No.
Description
Setting range Frame length
Dwell write
[0][1] to
0 to 20000
8
[C][A]
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
[1][F]
(11) Point table/auxiliary function (Command [C][B])
Command Data No.
Description
Setting range Frame length
Auxiliary function write
0, 1
[0][1] to
[C][B]
The decimal equivalent of the data No. value
(hexadecimal) corresponds to the Point table No.
8
[1][F]
(12) External input signal disable (Command [9][0])
Command Data No. Description
Setting range Frame length
Turns off the input devices, external analog input signals
and pulse train inputs with the exception of EMG, LSP and
LSN, independently of the external ON/OFF statuses.
Disables all output devices (DO).
1EA5
[9][0]
[9][0]
[9][0]
[9][0]
[0][0]
[0][3]
[1][0]
[1][3]
4
1EA5
1EA5
4
4
4
Enables the disabled input devices (DI), external analog
input signals and pulse train inputs with the exception of
EMG, LSP and LSN.
Enables the disabled output devices (DO).
1EA5
(13) Operation mode selection (Command [8][B])
Command Data No. Description
Setting range Frame length
Operation mode changing
0000 to 0004
0000: Exit from test operation mode
0001: Jog operation
[8][B]
[0][0]
4
0002: Positioning operation
0003: Motor-less operation
0004: Output signal (DO) forced output
15 - 15
15. COMMUNICATION FUNCTIONS
(14) Data for test operation mode (Command [9][2] [A][0])
Command Data No.
Description
Input signal for test operation
Setting range Frame length
[9][2]
[0][0]
Refer to
section 15.12.7
Refer to
8
[9][2]
[A][0]
Forced output from signal pin
8
section 15.12.9
Command Data No.
Description
Setting range Frame length
Writes the speed of the test operation mode (jog operation,
positioning operation).
0000 to 7FFF
4
[A][0]
[A][0]
[A][0]
[A][0]
[A][0]
[1][0]
[1][1]
[1][2]
[1][3]
[1][5]
Writes the acceleration/deceleration time constant of the
test operation mode (jog operation, positioning operation).
Clears the acceleration/deceleration time constant of the
test operation mode (jog operation, positioning operation).
Writes the moving distance (in pulses) of the test operation
mode (jog operation, positioning operation).
00000000 to
8
7FFFFFFF
1EA5
4
80000000 to
8
7FFFFFFF
Temporary stop command of the test operation mode (jog
operation, positioning operation)
1EA5
4
(15) Group setting (Command [9][F])
Command Data No.
Description
Setting range Frame length
[9][F]
[0][0]
Setting of group
a to f
4
15 - 16
15. COMMUNICATION FUNCTIONS
15.12 Detailed explanations of commands
15.12.1 Data processing
When the master station transmits a command data No. or a command data No. data to a slave
station, the servo amplifier returns a reply or data according to the purpose.
When numerical values are represented in these send data and receive data, they are represented in
decimal, hexadecimal, etc.
Therefore, data must be processed according to the application.
Since whether data must be processed or not and how to process data depend on the monitoring,
parameters, etc., follow the detailed explanation of the corresponding command.
The following methods are how to process send and receive data when reading and writing data.
(1) Processing the read data
When the display type is 0, the eight-character data is converted from hexadecimal to decimal and a
decimal point is placed according to the decimal point position information.
When the display type is 1, the eight-character data is used unchanged.
The following example indicates how to process the receive data "003000000929" given to show.
The receive data is as follows.
0 0 3 0 0 0 0 0 0 9 2 9
Data 32-bits length (hexadecimal representation)
(Data conversion is required as indicated in the display type)
Display type
0: Data must be converted into decimal.
1: Data is used unchanged in hexadecimal.
Decimal point position
0: No decimal point
1: First least significant digit (normally not used)
2: Second least significant digit
3: Third least significant digit
4: Forth least significant digit
5: Fifth least significant digit
6: Sixth least significant digit
Since the display type is "0" in this case, the hexadecimal data is converted into decimal.
00000929H 2345
As the decimal point position is "3", a decimal point is placed in the third least significant digit.
Hence, "23.45" is displayed.
15 - 17
15. COMMUNICATION FUNCTIONS
(2) Writing the processed data
When the data to be written is handled as decimal, the decimal point position must be specified. If it is
not specified, the data cannot be written. When the data is handled as hexadecimal, specify "0" as the
decimal point position.
The data to be sent is the following value.
0
Data is transferred in hexadecimal.
Decimal point position
0: No decimal point
1: First least significant digit
2: Second least significant digit
3: Third least significant digit
4: Forth least significant digit
5: Fifth least significant digit
By way of example, here is described how to process the set data when a value of "15.5" is sent. Since
the decimal point position is the second digit, the decimal point position data is "2". As the data to be
sent is hexadecimal, the decimal data is converted into hexadecimal.
155 9B
Hence, "0200009B" is transmitted.
15 - 18
15. COMMUNICATION FUNCTIONS
15.12.2 Status display
(1) Status display data read
When the master station transmits the data No. to the slave station, the slave station sends back the
data value and data processing information.
(a) Transmission
Transmit command [0][1] and the data No. corresponding to the status display item to be read.
Refer to section 15.11.1.
(b) Reply
The slave station sends back the status display data requested.
0 0
Data 32 bits long (represented in hexadecimal)
(Data conversion into display type is required)
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Decimal point position
0: No decimal point
1: Lower first digit (usually not used)
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
5: Lower fifth digit
6: Lower sixth digit
(2) Status display data clear
The cumulative feedback pulse data of the status display is cleared. Send this command immediately
after reading the status display item. The data of the status display item transmitted is cleared to
zero.
Command Data No.
[8][1] [0][0]
Data
1EA5
For example, after sending command [0][1] and data No. [8][0] and receiving the status display data,
send command [8][1], data No. [0][0] and data [1EA5] to clear the cumulative feedback pulse value to
zero.
15 - 19
15. COMMUNICATION FUNCTIONS
15.12.3 Parameter
(1) Parameter read
Read the parameter setting.
(a) Transmission
Transmit command [0][5] and the data No. corresponding to the parameter No.
Command Data No.
Data No. definition
[0][0] to
[0][5]
Corresponds to the parameter No.
[5][A]
(b) Reply
The slave station sends back the data and processing information of the requested parameter No.
Data is transferred in hexadecimal.
Decimal point position
0: No decimal point
1: Lower first digit
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
0
5: Lower fifth digit
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Parameter write type
0: Valid after write
1: Valid when power is switched on again after write
Read enable/disable
0: Read enable
1: Read disable
Enable/disable information changes according to the setting of parameter No.19 "parameter write
inhibit". When the enable/disable setting is read disable, ignore the parameter data part and
process it as unreadable.
15 - 20
15. COMMUNICATION FUNCTIONS
(2) Parameter write
POINT
If setting values need to be changed with a high frequency (i.e. one time or
more per one hour), write the setting values to the RAM, not the EEP-
ROM. The EEP-ROM has a limitation in the number of write times and
exceeding this limitation causes the servo amplifier to malfunction. Note
that the number of write times to the EEP-ROM is limited to
approximately 100, 000.
Write the parameter setting.
Write the value within the setting range. Refer to section 5.1 for the setting range.
Transmit command [8][4], the data No., and the set data.
The data number is represented in hexadecimal. The decimal value converted from the data number
value corresponds to the parameter number. Refer to (1) (a) of this section.
When the data to be written is handled as decimal, the decimal point position must be specified. If it is
not specified, data cannot be written. When the data is handled as hexadecimal, specify 0 as the
decimal point position.
Write the data after making sure that it is within the upper/lower limit value range given in section
5.1.2. Read the parameter data to be written, confirm the decimal point position, and create
transmission data to prevent error occurrence. On completion of write, read the same parameter data
to verify that data has been written correctly.
Command Data No.
Set data
[0][0] to
[8][4]
See below.
[5][A]
Data is transferred in hexadecimal.
Decimal point position
0: No decimal point
1: Lower first digit
2: Lower second digit
3: Lower third digit
4: Lower forth digit
5: Lower fifth digit
Write mode
0: Write to EEP-ROM
3: Write to RAM
When the parameter data is changed frequently through communication,
set "3" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour),
do not write it to the EEP-ROM.
15 - 21
15. COMMUNICATION FUNCTIONS
15.12.4 External I/O signal statuses
(1) Reading of input device statuses
Read the statuses of the input devices.
(a) Transmission
Transmit command [1][2] and data No. [0][0].
Command
Data No.
[1][2]
[0][0]
(b) Reply
The slave station sends back the statuses of the input pins.
b31
b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
bit
0
1
Signal name
bit
Signal name
bit
Signal name
Servo-on (SON)
12 Reverse rotation start (ST2)
13
24 Temporary stop/restart (STP)
Forward rotation stroke limit (LSP)
Reverse rotation stroke limit (LSN)
External torque limit selection (TL)
Internal torque limit selection (TL2)
Proportion control selection (PC)
Reset (RES)
Manual pulse generator
multiplication 1 (TP0)
25
2
14
3
15
Manual pulse generator
26
multiplication 2 (TP1)
4
16 Forced stop (EMG)
17 Automatic/manual selection (MD0)
18 Proximity dog (DOG)
19 Point table No. selection 1 (DI0)
20 Point table No. selection 2 (DI1)
21 Point table No. selection 3 (DI2)
22 Point table No. selection 4 (DI3)
23 Override selection (OVR)
5
27 Gain switch (CDP)
6
28
7
8
29 Point table No. selection 5 (DI4)
30 Teach (TCH)
31
9
10
11 Forward rotation start (ST1)
(2) External input pin status read
Read the ON/OFF statuses of the external output pins.
(a) Transmission
Transmit command [1][2] and data No. [4][0].
Command
Data No.
[1][2]
[4][0]
(b) Reply
The ON/OFF statuses of the input pins are sent back.
b31
b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
bit
0
External input pin
CN1B-16
bit
5
External input pin
CN1A-8
1
CN1B-17
6
CN1B-7
2
CN1B-15
7
CN1B-8
3
CN1B-5
8
CN1B-9
4
CN1B-14
9
CN1A-19
15 - 22
15. COMMUNICATION FUNCTIONS
(3) Read of the statuses of input devices switched on through communication
Read the ON/OFF statuses of the input devices switched on through communication.
(a) Transmission
Transmit command [1][2] and data No. [6][0].
Command
Data No.
[1][2]
[6][0]
(b) Reply
The slave station sends back the statuses of the input pins.
b31
b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
bit
0
1
Signal name
bit
Signal name
bit
Signal name
Servo-on (SON)
12 Reverse rotation start (ST2)
13
24 Temporary stop/restart (STP)
Forward rotation stroke limit (LSP)
Reverse rotation stroke limit (LSN)
External torque limit selection (TL)
Internal torque limit selection (TL2)
Proportion control selection (PC)
Reset (RES)
Manual pulse generator
multiplication 1 (TP0)
25
2
14
3
15
Manual pulse generator
26
multiplication 2 (TP1)
4
16 Forced stop (EMG)
17 Automatic/manual selection (MD0)
18 Proximity dog (DOG)
19 Point table No. selection 1 (DI0)
20 Point table No. selection 2 (DI1)
21 Point table No. selection 3 (DI2)
22 Point table No. selection 4 (DI3)
23 Override selection (OVR)
5
6
27 Gain switch (CDP)
28
7
29 Point table No. selection 5 (DI4)
8
9
30 Teach (TCH)
31
10
11 Forward rotation start (ST1)
(4) External output pin status read
Read the ON/OFF statuses of the external output pins.
(a) Transmission
Transmit command [1][2] and data No. [C][0].
Command
Data No.
[1][2]
[C][0]
(b) Reply
The slave station sends back the ON/OFF statuses of the output pins.
b31
b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
bit
External output pin
CN1A-19
bit
5
6
External output pin
CN1B-18
0
1
2
3
4
CN1A-18
CN1B-19
CN1B-6
CN1B-4
CN1A-14
15 - 23
15. COMMUNICATION FUNCTIONS
(5) Read of the statuses of output devices
Read the ON/OFF statuses of the output devices.
(a) Transmission
Transmit command [1][2] and data No. [8][0].
Command
Data No.
[1][2]
[8][0]
(b) Reply
The slave station sends back the statuses of the output devices.
b31
b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the master
station as hexadecimal data.
bit
0
1
2
3
4
5
6
7
8
9
Signal name
bit
Signal name
bit
Signal name
Ready (RD)
10 Electromagnetic brake (MBR)
11 Dynamic brake interlock (DBR)
12
13
19 Temporary stop (PUS)
20 Point No. output 1 (PT0)
21 Point No. output 2 (PT1)
22 Point No. output 3 (PT 2)
23 Point No. output 4 (PT 3)
24 Point No. output 5 (PT 4)
Limiting torque (TLC)
In position (INP)
14
15 Battery warning (BWNG)
16 Rough match (CPO)
Warning (WNG)
Trouble (ALM)
Home position return completion
17
(ZP)
18 Position range (POT)
15.12.5 Input devices ON/OFF
POINT
The ON/OFF states of all devices in the servo amplifier are the states of
the data received last. Hence, when there is a device which must be kept
ON, send data which turns that device ON every time.
Each input device can be switched on/off. However, when the device to be switched off exists in the
external input signal, also switch off that input signal.
Send command [9][2], data No. [6][0] and data.
Command
Data No.
Set data
See below.
[9][2]
[6][0]
b31
b1 b0
1:ON
0:OFF
Command of each bit is transmitted to the slave
station as hexadecimal data.
bit
0
Signal name
Servo-on (SON)
bit
Signal name
bit
Signal name
12 Reverse rotation start (ST2)
24 Temporary stop/restart (STP)
1
Forward rotation stroke limit (LSP)
Reverse rotation stroke limit (LSN)
External torque limit selection (TL)
Internal torque limit selection (TL2)
Proportion control selection (PC)
Reset (RES)
13
Manual pulse generator
multiplication 1 (TP0)
25
2
14
3
15
Manual pulse generator
26
multiplication 2 (TP1)
4
16 Forced stop (EMG)
5
17 Automatic/manual selection (MD0)
18 Proximity dog (DOG)
27 Gain switch (CDP)
6
28
7
19 Point table No. selection 1 (DI0)
20 Point table No. selection 2 (DI1)
21 Point table No. selection 3 (DI2)
22 Point table No. selection 4 (DI3)
23 Override selection (OVR)
29 Point table No. selection 5 (DI4)
8
30 Teach (TCH)
31
9
10
11 Forward rotation start (ST1)
15 - 24
15. COMMUNICATION FUNCTIONS
15.12.6 Disable/enable of I/O devices (DIO)
Inputs can be disabled independently of the I/O devices ON/OFF. When inputs are disabled, the input
signals (devices) are recognized as follows. Among the input devices, EMG, LSP and LSN cannot be
disabled.
Signal
Status
OFF
0V
Input devices (DI)
External analog input signals
Pulse train inputs
None
(1) Disabling/enabling the input devices (DI), external analog input signals and pulse train inputs with
the exception of EMG, LSP and LSN.
Transmit the following communication commands.
(a) Disable
Command
Data No.
Data
[9][0]
[0][0]
1EA5
(b) Enable
Command
Data No.
Data
[9][0]
[1][0]
1EA5
(2) Disabling/enabling the output devices (DO)
Transmit the following communication commands.
(a) Disable
Command
Data No.
Data
[9][0]
[0][3]
1EA5
(b) Enable
Command
Data No.
Data
[9][0]
[1][3]
1EA5
15 - 25
15. COMMUNICATION FUNCTIONS
15.12.7 Input devices ON/OFF (test operation)
Each input devices can be turned on/off for test operation. when the device to be switched off exists in the
external input signal, also switch off that input signal.
Send command [9] [2], data No. [0] [0] and data.
Command
Data No.
Set data
[9][2]
[0][0]
See below
b31
b1 b0
1: ON
0: OFF
Command of each bit is transmitted to the slave
station as hexadecimal data.
bit
0
Signal name
bit
Signal name
bit
Signal name
Servo-on (SON)
12 Reverse rotation start (ST2)
24 Temporary stop/restart (STP)
1
Forward rotation stroke limit (LSP)
Reverse rotation stroke limit (LSN)
External torque limit selection (TL)
Internal torque limit selection (TL2)
Proportion control selection (PC)
Reset (RES)
13
Manual pulse generator
multiplication 1 (TP0)
25
2
14
3
15
Manual pulse generator
26
multiplication 2 (TP1)
4
5
16 Forced stop (EMG)
17 Automatic/manual selection (MD0)
18 Proximity dog (DOG)
27 Gain switch (CDP)
6
28
7
19 Point table No. selection 1 (DI0)
20 Point table No. selection 2 (DI1)
21 Point table No. selection 3 (DI2)
22 Point table No. selection 4 (DI3)
23 Override selection (OVR)
29 Point table No. selection 5 (DI4)
8
30 Teach (TCH)
31
9
10
11 Forward rotation start (ST1)
15 - 26
15. COMMUNICATION FUNCTIONS
15.12.8 Test operation mode
(1) Instructions for test operation mode
The test operation mode must be executed in the following procedure. If communication is interrupted
for longer than 0.5s during test operation, the servo amplifier causes the motor to be decelerated to a
stop and servo-locked. To prevent this, continue communication without a break, e.g. monitor the
status display.
(a) Execution of test operation
1) Turn off all input devices.
2) Disable the input devices.
Command Data No.
[9][0] [0][0]
Data
1EA5
3) Choose the test operation mode.
Command Data No.
Transmission data
Selection of test operation mode
Test operation mode cancel
Jog operation
[8][B]
[8][B]
[8][B]
[8][B]
[8][B]
[0][0]
[0][0]
[0][0]
[0][0]
[0][0]
0000
0001
0002
0003
0004
Positioning operation
Motor-less operation
DO forced output
4) Set the data needed for test operation.
5) Start.
6) Continue communication using the status display or other command.
(b) Termination of test operation
To terminate the test operation mode, complete the corresponding operation and.
1) Clear the test operation acceleration/deceleration time constant.
Command Data No.
[A][0] [1][2]
Data
1EA5
2) Cancel the test operation mode.
Command Data No.
Data
[8][B]
[0][0]
0000
3) Enable the disabled input devices.
Command Data No.
Data
[9][0]
[1][0]
1EA5
15 - 27
15. COMMUNICATION FUNCTIONS
(2) Jog operation
Transmit the following communication commands.
(a) Setting of jog operation data
Item
Command Data No.
Data
Speed
[A][0]
[1][0] Write the speed [r/min] in hexadecimal.
Acceleration/deceleration
time constant
Write the acceleration/deceleration time constant
[ms] in hexadecimal.
[A][0]
[1][1]
(b) Start
Turn on the input devices SON
[0][0].
and ST1/ST2 by using command [9][2] data No.
LSP LSN
Item
Command Data No.
Data
00000807: Turns on SON
00001007: Turns on SON
00000007: Turns on SON
and ST1.
and ST2.
.
LSN
Forward rotation start
Reverse rotation start
Stop
[9][2]
[9][2]
[9][2]
[0][0]
[0][0]
[0][0]
LSP LSN
LSP LSN
and
LSP
(3) Positioning operation
Transmit the following communication commands.
(a) Setting of positioning operation data
Item
Command Data No.
Data
Speed
[A][0]
[A][0]
[A][0]
[1][0] Write the speed [r/min] in hexadecimal.
Acceleration/deceleration
time constant
Moving distance
Write the acceleration/deceleration time constant
[ms] in hexadecimal.
[1][1]
[1][3] Write the moving distance [pulse] in hexadecimal.
(b)
Input of servo-on stroke end
Turn on the input devices SON
by using command [9][2] data No. [0][0].
LSN
LSP
and
Item
Command Data No.
Data
Servo-on
Servo OFF
Stroke end ON
[9][2]
[9][2]
[0][0] 00000001: Turns on SON.
00000006: Turns off SON and turns on LSP
[0][0]
LSN.
Servo-on
Stroke end OFF
[9][2]
[0][0] Turns on SON LSP LSN.
15 - 28
15. COMMUNICATION FUNCTIONS
(c) Start of positioning operation
Transmit the speed and acceleration/deceleration time constant, turn on the servo-on (SON) and
forward/reverse rotation stroke end (LSP LSN , and then send the moving distance to start
)
positioning operation. After that, positioning operation will start every time the moving distance is
transmitted. To start opposite rotation, send the moving distance of a negative value.
When the servo-on (SON) and forward/reverse rotation stroke end (LSP LSN) are off, the
transmission of the moving distance is invalid. Therefore, positioning operation will not start if the
servo-on (SON) and forward/reverse rotation stroke end (LSP LSN) are turned on after the setting
of the moving distance.
(d) Temporary stop
A temporary stop can be made during positioning operation.
Command Data No.
[A][0] [1][5]
Data
1EA5
Retransmit the same communication commands as at the start time to resume operation.
To stop positioning operation after a temporary stop, retransmit the temporary stop
communication command. The remaining moving distance is then cleared.
15 - 29
15. COMMUNICATION FUNCTIONS
15.12.9 Output signal pin ON/OFF output signal (DO) forced output
In the test operation mode, the output signal pins can be turned on/off independently of the servo status.
Using command [9][0], disable the output signals in advance.
(1) Choosing DO forced output in test operation mode
Transmit command [8][B] data No. [0][0] data "0004" to choose DO forced output.
0 0 0 4
Selection of test operation mode
4: DO forced output (output signal forced output)
(2) External output signal ON/OFF
Transmit the following communication commands.
Command Data No.
[9][2] [A][0]
Setting data
See below.
b31
b1 b0
1: ON
0: OFF
Command of each bit is sent to the slave station in hexadecimal.
bit External output pin
bit External output pin
bit External output pin
bit External output pin
0
1
2
3
4
5
6
7
CN1A-19
CN1A-18
CN1B-19
CN1B-6
8
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
9
10
11
12
13
14
15
CN1B-4
CN1B-18
CN1A-14
15 - 30
15. COMMUNICATION FUNCTIONS
15.12.10 Alarm history
(1) Alarm No. read
Read the alarm No. which occurred in the past. The alarm numbers and occurrence times of No.0 (last
alarm) to No.5 (sixth alarm in the past) are read.
(a) Transmission
Send command [3][3] and data No. [1][0] to [1][5]. Refer to section 15.11.1.
(b) Reply
The alarm No. corresponding to the data No. is provided.
0 0
Alarm No. is transferred in decimal.
For example, "0032" means AL.32 and "00FF" AL._ (no alarm).
(2) Alarm occurrence time read
Read the occurrence time of alarm which occurred in the past.
The alarm occurrence time corresponding to the data No. is provided in terms of the total time
beginning with operation start, with the minute unit omitted.
(a) Transmission
Send command [3][3] and data No. [2][0] to [2][5].
Refer to section 15.11.1.
(b) Reply
The alarm occurrence time is transferred in decimal.
Hexadecimal must be converted into decimal.
For example, data [0][1][F][5] indicates that the alarm occurred 501 hours after start of operation.
(3) Alarm history clear
Erase the alarm history.
Send command [8][2] and data No. [2][0].
Command Data No.
[8][2] [2][0]
Data
1EA5
15 - 31
15. COMMUNICATION FUNCTIONS
15.12.11 Current alarm
(1) Current alarm read
Read the alarm No. which is occurring currently.
(a) Transmission
Send command [0][2] and data No. [0][0].
Command Data No.
[0][2]
[0][0]
(b) Reply
The slave station sends back the alarm currently occurring.
0 0
Alarm No. is transferred in decimal.
For example, "0032" means AL.32 and "00FF" AL._ (no alarm).
(2) Read of the status display at alarm occurrence
Read the status display data at alarm occurrence. When the data No. corresponding to the status
display item is transmitted, the data value and data processing information are sent back.
(a) Transmission
Send command [3][5] and any of data No. [8][0] to [8][E] corresponding to the status display item to
be read. Refer to section 15.11.1.
(b) Reply
The slave station sends back the requested status display data at alarm occurrence.
0 0
Data 32 bits long (represented in hexadecimal)
(Data conversion into display type is required)
Display type
0: Conversion into decimal required
1: Used unchanged in hexadecimal
Decimal point position
0: No decimal point
1: Lower first digit (usually not used)
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
5: Lower fifth digit
6: Lower sixth digit
(3) Current alarm clear
As by the entry of the Reset (RES), reset the servo amplifier alarm to make the servo amplifier ready
to operate. After removing the cause of the alarm, reset the alarm with no command entered.
(a) Transmission
Command Data No.
[8][2] [0][0]
Data
1EA5
15 - 32
15. COMMUNICATION FUNCTIONS
15.12.12 Point table
(1) Data read
(a) Position data
Read the position data of the point table.
1) Transmission
Transmit command [4][0] and any of data No. [0][1] to [1][F] corresponding to the point table to
be read. Refer to section 15.11.1.
2) Reply
The slave station sends back the position data of the requested point table.
Hexadecimal data
Decimal point position
0: No decimal point
1: Lower first digit (usually not used)
2: Lower second digit
3: Lower third digit
0 0
4: Lower fourth digit
5: Lower fifth digit
6: Lower sixth digit
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Position data write type
0: Valid after write
1: Valid when power is switched on again after write
(b) Speed data
Read the speed data of the point table.
1) Transmission
Transmit command [5][0] and any of data No. [0][1] to [0][F] corresponding to the point table to
be read. Refer to section 15.11.1.
2) Reply
The slave station sends back the speed data of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Speed data write type
0: Valid after write
1: Valid when power is switched on again after write
15 - 33
15. COMMUNICATION FUNCTIONS
(c) Acceleration time constant
Read the acceleration time constant of the point table.
1) Transmission
Transmit command [5][4] and any of data No. [0][1] to [1][F] corresponding to the point table to
be read. Refer to section 15.11.1.
2) Reply
The slave station sends back the acceleration time constant of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Accelevation time constant write type
0: Valid after write
1: Valid when power is switched on again after write
(d) Deceleration time constant
Read the deceleration time constant of the point table.
1) Transmission
Transmit command [5][8] and any of data No. [0][1] to [1][F] corresponding to the point table to
be read. Refer to section 15.11.1.
2) Reply
The slave station sends back the deceleration time constant of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Deceleration time constant write type
0: Valid after write
1: Valid when power is switched on again after write
15 - 34
15. COMMUNICATION FUNCTIONS
(e) Dwell
Read the dwell of the point table.
1) Transmission
Transmit command [6][0] and any of data No. [0][1] to [1][F] corresponding to the point table to
be read. Refer to section 15.11.1.
2) Reply
The slave station sends back the dwell of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Dwell write type
0: Valid after write
1: Valid when power is switched on again after write
(f) Auxiliary function
Read the auxiliary function of the point table.
1) Transmission
Transmit command [6][4] and any of data No. [0][1] to [1][F] corresponding to the point table to
be read. Refer to section 15.11.1.
2) Reply
The slave station sends back the auxiliary function of the requested point table.
0
Hexadecimal data
0 0
Display type
0: Used unchanged in hexadecimal
1: Conversion into decimal required
Auxiliary function write type
0: Valid after write
1: Valid when power is switched on again after write
15 - 35
15. COMMUNICATION FUNCTIONS
(2) Data write
POINT
If setting values need to be changed with a high frequency (i.e. one time or
more per one hour), write the setting values to the RAM, not the EEP-
ROM. The EEP-ROM has a limitation in the number of write times and
exceeding this limitation causes the servo amplifier to malfunction. Note
that the number of write times to the EEP-ROM is limited to
approximately 100, 000.
(a) Position data
Write the position data of the point table.
Transmit command [C][0], any of data No. [0][1] to [1][F] corresponding to the point table to be
written to, and the data. Refer to section 15.11.2.
Command
Data No.
[0][1] to
[0][F]
Data
[C][0]
See below.
Hexadecimal data
Decimal point position
0: No decimal point
1: Lower first digit
2: Lower second digit
3: Lower third digit
4: Lower fourth digit
5: Lower fifth digit
6: Lower sixth digit
The decimal point position should be the same as
the feed length multiplication (STM) set in parameter
No. 1. The slave station will not accept the decimal
point position which is different from the STM setting.
Write mode
0: EEP-ROM, RAM write
1: RAM write
When the position data is changed frequently through communication,
set "1" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour),
do not write it to the EEP-ROM.
(b) Speed data
Write the speed data of the point table.
Transmit command [C][6], any of data No. [0][1] to [1][F] corresponding to the point table to be
written to, and the data. Refer to section 15.11.2.
Command
Data No.
Data
[0][1] to
[0][F]
[C][6]
See below.
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
When the speed data is changed frequently through communication,
set "1" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour),
do not write it to the EEP-ROM.
15 - 36
15. COMMUNICATION FUNCTIONS
(c) Acceleration time constant
Write the acceleration time constant of the point table.
Transmit command [C][7], any of data No. [0][1] to [1][F] corresponding to the point table to be
written to, and the data. Refer to section 15.11.2.
Command Data No.
Data
[0][1] to
[C][7]
See below.
[0][F]
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
When the acceleration time constant is changed frequently through communication,
set "1" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour),
do not write it to the EEP-ROM.
(d) Deceleration time constant
Write the deceleration time constant of the point table.
Transmit command [C][8], any of data No. [0][1] to [1][F] corresponding to the point table to be
written to, and the data. Refer to section 15.11.2.
Command Data No.
Data
[0][1] to
[C][8]
See below.
[0][F]
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
When the deceleration time is changed frequently through communication,
set "1" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour),
do not write it to the EEP-ROM.
15 - 37
15. COMMUNICATION FUNCTIONS
(e) Dwell
Write the dwell of the point table.
Transmit command [C][A], any of data No. [0][1] to [1][F] corresponding to the point table to be
written to, and the data. Refer to section 15.11.2.
Command Data No.
Data
[0][1] to
[C][A]
See below.
[0][F]
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
When the dwell constant is changed frequently through communication,
set "1" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour),
do not write it to the EEP-ROM.
(f) Auxiliary function
Write the auxiliary function of the point table.
Transmit command [C][B], any of data No. [0][1] to [1][F] corresponding to the point table to be
written to, and the data. Refer to section 15.11.2.
Command Data No.
Data
[0][1] to
[C][B]
See below.
[0][F]
0
Hexadecimal data
Write mode
0: EEP-ROM, RAM write
1: RAM write
When the auxiliary function constant is changed frequently through communication,
set "1" to the write mode to change only the RAM data in the servo amplifier.
When changing data frequently (once or more within one hour),
do not write it to the EEP-ROM.
15 - 38
15. COMMUNICATION FUNCTIONS
15.12.13 Servo amplifier group designation
With group setting made to the slave stations, data can be transmitted simultaneously to two or more
slave stations set as a group through RS-422 communication.
(1) Group setting write
Write the group designation value to the slave station.
(a) Transmission
Transmit command [9][F], data No. [0][0] and data.
Command
Data No.
Data
[9][F]
[0][0]
See below.
0
0
Group designation
0: No group designation
1: Group a
2: Group b
3: Group c
4: Group d
5: Group e
6: Group f
Response command enable
Set whether data can be sent back or not in
response to the read command of the master station.
0: Response disable
Data cannot be set back.
1: Response enable
Data can be set back.
(2) Group setting read
Read the set group designation value from the slave station.
(a) Transmission
Transmit command [1][F] and data No. [0][0].
Command
Data No.
[1][F]
[0][0]
(b) Reply
The slave station sends back the group setting of the point table requested.
0
0
Group designation
0: No group designation
1: Group a
2: Group b
3: Group c
4: Group d
5: Group e
6: Group f
Response command enable
0: Response disable
1: Response enable
15 - 39
15. COMMUNICATION FUNCTIONS
15.12.14 Software version
Reads the software version of the servo amplifier.
(a) Transmission
Send command [0] [2] and data No. [7] [0].
Command
Data No.
[0][2]
[7][0]
(b) Reply
The slave station returns the software version requested.
Space
Software version (15 digits)
15 - 40
APPENDIX
App 1. Status indication block diagram
App - 1
APPENDIX
App 2. Junction terminal block (MR-TB20) terminal block labels
For CN1A
For CN1B
9
8
7
6
5
4
3
2
1
0
9
8
7
6
5
4
3
2
1
0
9
9
8
7
6
5
4
3
2
1
0
1 9
1 8
1 7
1 6
1 5
1 4
1 3
1 2
1 1
1 0
1 9
1 8
1 7
1 6
1 5
1 4
1 3
1 2
1 1
1 0
1 9
1 9
1 8
1 7
1 6
1 5
1 4
1 3
1 2
1 1
1 0
8
7
6
5
4
3
2
1
0
1 8
1 7
1 6
1 5
1 4
1 3
1 2
1 1
1 0
App - 2
APPENDIX
App 3. Combination of servo amplifier and servo motor
The servo amplifier software versions compatible with the servo motors are indicated in the parentheses.
The servo amplifiers whose software versions are not indicated can be used regardless of the versions.
Servo amplifier
Servo amplifier
Servo motor
HC-KFS053
HC-KFS13
HC-KFS23
Servo motor
(Software version)
(Software version)
MR-J2S-10CP
HC-RFS103
HC-RFS153
HC-RFS203
HC-RFS353
HC-RFS503
HC-UFS72
HC-UFS152
HC-UFS202
HC-UFS352
HC-UFS502
MR-J2S-200CP
MR-J2S-10CP1
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-500CP
MR-J2S-70CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-500CP
MR-J2S-10CP
MR-J2S-10CP1
MR-J2S-10CP
MR-J2S-10CP1
MR-J2S-20CP
MR-J2S-20CP1
MR-J2S-40CP
MR-J2S-40CP1
HC-KFS43
HC-KFS73
HC-MFS053
MR-J2S-70CP
MR-J2S-10CP
MR-J2S-10CP1
HC-UFS13
HC-UFS23
HC-UFS43
MR-J2S-10CP
MR-J2S-10CP1
HC-MFS13
HC-MFS23
HC-MFS43
MR-J2S-20CP
MR-J2S-20CP1
MR-J2S-20CP
MR-J2S-20CP1
MR-J2S-40CP
MR-J2S-40CP1
MR-J2S-40CP
MR-J2S-40CP1
HC-UFS73
HC-LFS52
HC-LFS102
HC-LFS152
HC-LFS202
HC-LFS302
HA-LFS502
HA-LFS702
MR-J2S-70CP
HC-MFS73
HC-SFS81
HC-SFS121
HC-SFS201
HC-SFS301
HC-SFS52
HC-SFS102
HC-SFS152
HC-SFS202
HC-SFS352
HC-SFS502
HC-SFS702
HC-SFS53
HC-SFS103
HC-SFS153
HC-SFS203
HC-SFS353
MR-J2S-70CP
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-60CP
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-500CP
MR-J2S-700CP
MR-J2S-60CP
MR-J2S-100CP
MR-J2S-200CP
MR-J2S-200CP
MR-J2S-350CP
MR-J2S-60CP (Version A2 or later)
MR-J2S-100CP (Version A2 or later)
MR-J2S-200CP (Version A2 or later)
MR-J2S-350CP (Version A2 or later)
MR-J2S-500CP (Version A2 or later)
MR-J2S-500CP
MR-J2S-700CP
App - 3
APPENDIX
App 4. Change of connector sets to the RoHS compatible products
Connector sets (options) in the following table are changed to the RoHS compatible products after September,
2006 shipment.
Please accept that the current products might be mixed with RoHS compatible products based on availability.
Model
Current Product
RoHS Compatible Product
MR-J2CNM
MR-J2CN1
MR-J2CNS
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
Encoder connector (DDK)
Encoder connector (DDK)
MS3057-12A (Cable clump)
D/MS3057-12A (Cable clump)
D/MS3106B20-29S (Straight plug)
Amplifier connector (3M or equivalent)
10120-3000PE (connector)
MS3106B20-29S (Straight plug)
Amplifier connector (3M or equivalent)
10120-3000VE (connector)
MR-ENCNS
MS3106A20-29S (D190) (Plug, DDK)
CE3057-12A-3 (D265) (Cable clump, DDK)
CE02-20BS-S (Back shell, DDK)
Power supply connector (DDK)
CE05-6A22-23SD-B-BSS (Connector and back
shell)
D/MS3106A20-29S (D190) (Plug, DDK)
CE3057-12A-3-D (Cable clump, DDK)
CE02-20BS-S-D (Back shell, DDK)
Power supply connector (DDK)
CE05-6A22-23SD-D-BSS (Connector and back
shell)
MR-PWCNS1
MR-PWCNS2
MR-PWCNS3
MR-BKCN
CE3057-12A-2 (D265) (Cable clump)
Power supply connector (DDK)
CE05-6A24-24SD-B-BSS (Connector and back
shell)
CE3057-12A-2-D (Cable clump)
Power supply connector (DDK)
CE05-6A24-10SD-B-BSS (Connector and back
shell)
CE3057-16A-2 (D265) (Cable clump)
Power supply connector (DDK)
CE05-6A32-17SD-B-BSS (Connector and back
shell)
CE3057-16A-2-D (Cable clump)
Power supply connector (DDK)
CE05-6A32-17SD-D-BSS (Connector and back
shell)
CE3057-20A-1 (D265) (Cable clump)
Electromagnetic brake connector
MS3106A10SL-4S (D190) (Plug, DDK)
CE3057-20A-1-D (Cable clump)
Electromagnetic brake connector
D/MS3106A10SL-4S (D190) (Plug, DDK)
App - 4
REVISIONS
*The manual number is given on the bottom left of the back cover.
Print Data
*Manual Number
Revision
Jan., 2002 SH(NA)030017-A First edition
Oct., 2002 SH(NA)030017-B Addition of Note to the environment conditions in Safety Instructions 4 (1)
Addition of "About processing of waste"
Addition of "EEP-ROM life"
COMPLIANCE WITH EC DIRECTIVES 1. (1): Sentence change
(1): HA-LFS , HC-LFS addition
(6) (a): Deletion
(7) (c): Sentence change
CONFORMANCE WITH UL/C-UL STANDARD (1): HA-LFS , HC-LFS
addition
(7): Addition
Section 1.5: HA-LFS , HC-LFS addition
Section 2.4 (2): Sentence change
Section 3.3.2 (1) (c): Sentence change to "Position range (POT)"
Section 3.5: Addition of Note into Figure
Section 3.8.1: POINT addition
Section 3.8.3 (1) Lead wire color deletion
Section 4.1.1 (1) (b): Sentence change
Section 4.2.6 (2) (a) 1): Figure change
2): Figure change
(b): Figure change
(c) 1): Figure change
2): Figure change
(3): Figure change
Section 5.2.1 (2): Addition of sentence to parameters No. 50, 51
Change of No. 55 setting
Section 6.2 (1): Change to display contents
Section 7.1: Change to initial screen of point table
Section 7.2.2: POINT addition
Section 7.5.1: Figure change
Section 7.5.3 (1): Figure change, Note addition
(2): Figure change, Note addition
Section 7.6.2 (2): Signed 5-digit parameter addition
Section 8.2.2: POINT addition
Section 11.2.1: Addition of Note to AL.30
Addition of AL.61 home operation alarm
Section 11.2.2: Deletion of Cause 4 from AL.16
Addition of Causes 3 - 6 to AL.37
Addition of AL.61 home operation alarm
Section 13.1: Note addition
Section 13.2: Change of "zero torque" representation to "servo off"
Section 14.1.1 (1): Note described for MR-RB50, MR-RB51
(4): Note addition, cooling fan mounting diagram addition
Section 14.1.4 (2) (a): POINT addition
Fabricating connection diagram change
Section 14.2.6 (2) (b): Figure change
Section 14.2.8: Sentence addition
Section 14.2.9: Figure change
Print data
*Manual number
Revision
Oct., 2002
SH(NA)030017-B Section 15.10: Figure change
Section 15.12.3 (2): POINT addition
Mar., 2004 SH(NA)030017-C Safety Instructions: Overall reexamination
Section 1.1.1: Partial figure reexamination
Section 1.5: Note addition
Section 1.7 (3): Note addition
Section 1.7 (4): Note addition
Section 3.1: Partial figure reexamination/Addition of Note 13
Section 3.6.1: Partial figure reexamination
Section 3.8.2: Figure reexamination
Section 3.8.3: Overall reexamination
Section 3.9: Figure reexamination of CAUTION
Section 4.1.2: Partial addition of CAUTION sentence
Section 4.1.2 (f): Partial table change
Section 4.2.2 (3): Partial table addition
Section 4.2.3 (3): Partial table addition
Section 4.2.4: Overall reexamination
Section 4.3.2: Partial table deletion
Section 4.4.2 (3): Partial changing of text/Partial figure addition
Section 4.4.3: Partial changing of figure, table and text
Section 4.4.4: Partial changing of figure, table and text
Section 4.4.5: Partial changing of figure, table and text
Section 4.4.6: Partial changing of figure, table and text
Section 4.4.7 (2): Partial changing of table and text/Partial figure addition
Section 4.4.8 (2): Partial changing of table and text/Partial figure addition
Section 4.4.9 (2): Partial changing of table and text/Partial figure addition
Section 4.4.11: Partial figure addition
Section 5.1.2 (2): Partial addition of parameter No.0/change Setting range of
parameter No.35 to No.37, Partial text addition of parameter
No.63
Section 5.2.3: Partial text change
Chapter 6: Title reexamination
Section 6.2 (1): Table change
Section 6.7.2: Partial addition of POINT sentence
Section 6.7.5: POINT addition
Section 6.4 (2): Change
Section 11.2: Partial text change
Section 11.2.2: Changing of alarm 12 to 15/addition of alarm 37 cause 7/Partial
text change of alarm 51 52
Section 12.1: Overall reexamination
Section 13.2: Table reexamination
Section 13.3: Partial addition of text
Section 13.5: Addition
Section 14.1.1 (3): Partial figure change
Section 14.1.1 (4): Partial text change
Section 14.1.1 (5): Partial reexamination
Section 14.1.2: Partial addition of text
Section 14.1.2 (2): Changing of Note 2
Section 14.1.3: Partial addition of text
Section 14.1.3 (2): Partial figure reexamination/Addition of Note 2
Section 14.1.7: Partial addition of text
Print data
*Manual number
Revision
Mar., 2004 SH(NA)030017-C Section 14.1.9: POINT addition
Section 14.2.8 (3): Partial figure reexamination
Section 14.2.6 (2) (d): Partial figure change
Section 14.2.6 (2) (e): Partial figure change
Section 14.2.8: Partial figure change
Appendix: Addition
Mar., 2005 SH(NA)030017-D COMPLIANCE WITH EC DIRECTIVES: “1. WHAT ARE EC DIRECTIVES?“
Sentence reexamination
Section 1. 1. 1 (1): Reexamination of words in figure
Section 1. 1. 1 (2): Addition, reexamination of the function block diagram for
MR-J2S-500CP, 700CP
Section 1. 4 (2): Note reexamination
Section 3. 1: Figure reexamination
Section 3. 3. 1 (2): Signal arrangement Deletion of PG, NG
Section 3. 3. 2 (1) (c): Sentence addition of rough match device
Section 3. 3. 2 (2): Input signal Deletion of PG, NG
Section 3. 5: Addition of CAUTION sentence (3) Sentence reexamination
Section 3. 6. 2 (3) 2): Figure reexamination of output pulse
Section 3. 6. 2 (6): Figure correction
Section 3. 7. 2: Addition of explanation on the power supply terminals
Section 3. 7. 3 (1) 1): Sentence addition
Section 3.9: Sentence reexamination (3) (d), (e) Figure change
Section 3. 11: POINT addition (1) Sentence reexamination
Section 4. 2. 1 (2) (b): Note reexamination
Section 4. 3. 2 (3) (b): Reexamination of sentence in table, note
Section 4. 5: POINT addition, reexamination (1) Sentence reexamination
Section 5. 1. 2 (1): No.60, No.87 Correction of initial value
Reexamination of words in table
Section 5. 1. 2 (2): No.46 Figure reexamination No.87 Changing of initial
value
No.55 Reexamination of words in table
Reexamination of words in table
Section 6. 2 (1): Note sentence addition
Section 7. 5. 3 (2): Partial changing of figure
Section 7. 6: Reexamination of words in POINT
Section 7. 6. 2 (2): Partial changing of figure
Section 9. 4 (1): Calculation reexamination
Section 11. 2. 1: Addition of words in table
Section 11. 2. 2: AL. 10 Sentence reexamination
AL. 17, AL. 19 Sentence reexamination, addition
AL. 33 Sentence addition
AL. 46 Sentence reexamination
Section 11. 2. 3: Addition of CAUTION sentence
AL. E3 Sentence addition
Section 13.1: Note change
Section 13.3: Addition of HC-LFS series graph Sentence reexamination
Section 14. 1. 1 (2): (b) Figure addition
Section 14. 1. 1 (4): POINT addition
Section 14. 1. 1 (4) (a): Sentence reexamination
Section 14. 1. 1 (4) (b): Sentence reexamination
Section 14. 1. 1 (5) (b): Reexamination of words in figure
Print data
*Manual number
Revision
Mar., 2005 SH(NA)030017-D Section 14. 1. 1 (5) (c): Partial changing of figure
Section 14. 1. 2 (2): Note reexamination
Section 14. 1. 3 (2): Note reexamination
Section 14. 1. 4 (1): Sentence reexamination (2) Sentence reexamination
Section 14. 1. 9: Correction of words in POINT
Section 14. 2. 3: Addition of MR-J2S- CP
Crossing change
Section 14. 2. 6 (2): (d) Sentence reexamination (e) Connection diagram change
Section 15. 8: Sentence reexamination
App 3: Partial change
Jan., 2006 SH(NA)030017-E Safety Instructions: 4. (2) (4) Sentence addition
Section 1.1.1: Correction of error in writing
Section 1.4 (2): Note reexamination
Section 1.6.1: Correction of instructions
Section 1.7: Note reexamination
Chapter 2: CAUTION addition
Section 3.6.2 (3) (b): 2) Addition of descriptions
Section 3.8.3: Change of signal expression
Section 3.9: CAUTION addition
Section 4.1.2 (2) (b): Sentence change
Section 4.2.3 (2) (c): Sentence change/Partial figure reexamination
Section 4.2.4 (2) (c): Sentence change/Partial figure reexamination
Section 4.2.5 (2) (c): Sentence change/Partial figure reexamination
Section 4.4.10: Home position return automatic return function: Correction of
error in writing
Section 5.1.2 (2): Note addition of parameter No. 17, No. 30
Section 5.2.4: Sentence change
Section 5.2.4 (2): Note addition
Section 11.2.3: Sentence addition
Section 12.1: Correction of error in writing
Section 14.2.6 (2) (d): Change of outline drawing
Section 15.2.3 (2): Change of POINT sentence
Section 15.12.12: POINT addition
Section 15.12.12 (3): Correction of error in writing
Section 15.12.12 (4): Correction of error in writing
Section 15.12.12 (5): Correction of error in writing
Section 15.12.12 (6): Correction of error in writing
SH(NA)030017-F Safety Instructions: 4. Additional instructions (2) Figure change
Section 1.1 (2): Figure correction
Jul., 2006
Section 1.1.2: Correction of description for auxiliary functions
Section 1.6.2: Correction of words in CAUTION
Chapter 2: Addition of CAUTION sentence
Chapter 3: Addition of CAUTION sentence
Section 3.7.2: Addition of sentence in Table
Section 3.7.3 (3): CAUTION addition
Section 3.8.2: CAUTION addition
Section 4.2.2 (2): Sentence reexamination
Section 4.4.8: Correction of POINT sentence
Section 4.5 (1): Sentence reexamination
Section 5.2.1: Correction of POINT sentence
Section 6.2 (1): Table change
Print data
*Manual number
Revision
Jul., 2006
SH(NA)030017-F Section 7.2.3: Correction of description for command position
Section 8.3.1 (1) (a): Addition of parameter in Table
Section 8.4 (2): Correction of description for Step 5
Section 11.2.2: Correction of name for Al. 17
Section 11.2.3: Correction of description for Al. 90
Section 12.2 (1) (b): Correction of error in dimensions
Section 14.1.1 (2): Correction of formula in Table
Section 14.1.1 (4): Sentence reexamination
Section 14.1.5 (3): Addition of pin No. in figure
Section 14.1.7 (2): Correction of signal name for CN3-1 pin
Section 14.1.9: POINT reexamination
Section 15.12.3 (2): Correction of POINT sentence
Section 15.12.5: Sentence addition
Section 15.12.12: Description reexamination
Sep., 2007 SH(NA)-030017-G Safety Instructions
1. To prevent electric shock: Partial change of sentence
2. To prevent fire: Partial change of sentence
4. Additional Instructions
(2) Wiring: Addition of sentence
Section 1.1.1: Addition of Note
Section 1.6.2: WARNING Change of sentence
Section 1.7: Addition of Note
Chapter 3: WARNING Change of sentence
Section 3.6.2 (2): Addition of sentence Addition of Note
Section 3.6.2 (6): Addition of Note
Section 3.7: CAUTION Change of sentence
Section 3.9 (3): Change of timing chart
Section 4.4.5 (3): Addition of Note
Section 4.4.8: POINT Change of sentence
Section 4.5: POINT addition
Section 4.5 (5): CAUTION Change of sentence
Section 5.1.2 (2): Partial change of parameter No.0
Chapter 10: WARNING Change of sentence
Section 11.2: Addition of AL. 20 Definition
Change of sentence in AL. 32. Definition
Change of sentence in AL. 33. Definition
Addition of Cause 6 for AL. 50
Change of sentence in AL. 51. Definition
Section 11.3: New addition
Chapter 14: WARNING Change of sentence
Section 14.1.1 (3): Change of parameter No.0 definition
Section 14.1.1 (5) (b), (c): Change of outline dimension drawing
Section 14.1.2: Overall change to FR-BU2
Section 14.1.4: Change of some connectors to RoHS compatible products
Section 14.2.1 (1): Partial change of table 14.2
Section 14.2.6 (2) (d): Change of sentence
Section 14.2.8: Addition of connection diagram and surge protector
Appendix 6: Addition
MODEL
MODEL
CODE
HEAD OFFICE : TOKYO BLDG MARUNOUCHI TOKYO 100-8310
This Instruction Manual uses recycled paper.
Specifications subject to change without notice.
SH (NA) 030017-G (0709) MEE
Printed in Japan
|