Kenmore THE ECONOMIZER 15333206 User Manual

Owner’s Manual  
THE ECONOMIZER™ 6  
GAS WATER HEATER  
POWER VENTED GAS MODELS  
WITH HOT SURFACE IGNITION  
FOR POTABLE WATER HEATING ONLY.  
NOT SUITABLE FOR SPACE HEATING.  
NOT FOR USE IN MOBILE HOMES.  
• Safety Instructions  
• Installation  
• Operation  
MODEL NO.  
• Care and Maintenance  
• Troubleshooting  
• Parts List  
153.332040  
153.332050  
153.332060  
153.332070  
40 Gallon Nat  
50 Gallon Nat  
40 Gallon LP  
50 Gallon LP  
For Your Safety  
AN ODORANT IS ADDED TO THE GAS USED BY THIS WATER HEATER.  
C3 Technology® Gas Water Heaters meet  
the new ANSI Z21.10.1 standard that deals  
with the accidental or unintended ignition of  
ammable vapors, such as those emitted  
by gasoline.  
ADVERTENCIA  
Si no puede leer o entender el inglés y necesita el manual  
instructivo y/o etiquetas en español puede obtenerlos llamando al  
1-800-821-2017. NO TRATE DE INSTALAR O OPERAR ESTE  
CALENTADOR DEAGUAsi no entiende la información en las etiquetas  
o en el manual instructivo. No hacer caso de esta advertencia podría  
resultar en la MUERTE O GRAVES LESIONES CORPORALES.  
Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A  
PRINTED IN THE U.S.A. 0308  
www.sears.com  
PART NO. 185249-002  
SAFETY PRECAUTIONS  
3
TABLE OF CONTENTS  
SAFE INSTALLATION, USE AND SERVICE...................................................................................................................................... 2  
SAFETY PRECAUTIONS................................................................................................................................................................... 3  
TABLE OF CONTENTS...................................................................................................................................................................... 4  
CUSTOMER RESPONSIBILITIES..................................................................................................................................................... 5  
PRODUCT SPECIFICATIONS........................................................................................................................................................... 5  
INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS ............................................................ 6  
MATERIALS AND BASIC TOOLS NEEDED...................................................................................................................................... 7  
TYPICAL INSTALLATION................................................................................................................................................................ 8-9  
INSTALLATION INSTRUCTIONS ................................................................................................................................................. 9-22  
Removing the Old Water Heater ................................................................................................................................................. 9  
Facts to Consider About the Location ...................................................................................................................................10-11  
Insulation Blankets.....................................................................................................................................................................11  
Combustion Air and Ventilation for Appliances Located in Unconned Spaces.........................................................................11  
Combustion Air and Ventilation for Appliances Located in Conned Spaces........................................................................11-12  
Water Piping......................................................................................................................................................................... 13-14  
Temperature-Pressure Relief Valve...................................................................................................................................... 14-15  
Gas Piping................................................................................................................................................................................. 15  
Sediment Traps......................................................................................................................................................................... 16  
Filling the Water Heater............................................................................................................................................................. 16  
Blower Assembly Installation................................................................................................................................................ 16-17  
Vent Connections to Blower Assembly...................................................................................................................................... 18  
Venting and Installation........................................................................................................................................................ 18-19  
Condensation............................................................................................................................................................................ 18  
Maximum Vent Lengths............................................................................................................................................................. 18  
Venting ...................................................................................................................................................................................... 19  
Vent Terminal Installation ..................................................................................................................................................... 19-20  
Vertical Vent Through Roof ....................................................................................................................................................... 20  
Vertical Vent Restrictions........................................................................................................................................................... 20  
Vent Pipe Preparation .......................................................................................................................................................... 21-22  
OPERATING INSTRUCTIONS.................................................................................................................................................... 23-24  
Lighting and Operating Label.................................................................................................................................................... 23  
Temperature Regulation............................................................................................................................................................ 24  
FOR YOUR INFORMATION............................................................................................................................................................. 25  
Start Up Conditions................................................................................................................................................................... 25  
Operational Conditions.............................................................................................................................................................. 26  
SERVICE AND ADJUSTMENT ................................................................................................................................................... 26-28  
Venting System Inspection........................................................................................................................................................ 26  
Burner Operation and Inspection ......................................................................................................................................... 26-27  
Burner Cleaning ........................................................................................................................................................................ 27  
Housekeeping ........................................................................................................................................................................... 27  
Anode Rod Inspection............................................................................................................................................................... 27  
Temperature-Pressure Relief Valve Operation..................................................................................................................... 27-28  
Draining..................................................................................................................................................................................... 28  
Drain Valve Washer Replacement............................................................................................................................................. 28  
Service ...................................................................................................................................................................................... 28  
LEAKAGE CHECKPOINTS.............................................................................................................................................................. 29  
TROUBLESHOOTING GUIDELINES.......................................................................................................................................... 30-32  
PARTS ORDER LIST ....................................................................................................................................................................... 33  
WARRANTY..................................................................................................................................................................................... 36  
4
CUSTOMER RESPONSIBILITIES  
Thank You for purchasing a Kenmore water heater. Properly installed  
2. The installation must conform with these instructions and the local code  
authority having jurisdiction. In the absence of local codes, installations  
shall comply with the National Fuel Gas Code ANSI Z223.1/NFPA  
54 and the National Electrical Code, NFPA 70. These publications  
are available from The National Fire Protection Association, 1  
Batterymarch Park, Quincy, MA 02269.  
and maintained, it should give you years of trouble free service. If you  
should decide that you want the new water heater professionally installed  
by Sears call 1-800-4-MY-HOME®. They will arrange for prompt, quality  
installation by Sears authorized contractors.  
Abbreviations Found In This Instruction Manual:  
• CSA - Canadian Standards Association  
3. The water heater when installed must be grounded in accordance  
with the local codes, or in the absence of local codes, the National  
Electrical Code NFPA 70.  
• ANSI - American National Standards Institute  
• NFPA - National Fire Protection Association  
• ASME - American Society of Mechanical Engineers  
• GAMA - Gas Appliance Manufacturer’s Association  
• UL - Underwriters Laboratories Inc.  
4. If after reading this manual you have any questions or do not  
understand any portion of the instructions, call the local gas utility or  
the Sears Service Center.  
This gas-red water heater is listed by Underwriters Laboratories Inc.  
underAmerican National Standard/CSAStandard for Gas Water Heaters  
ANSI Z21.10.1 • CSA 4.1 (current edition).  
5. Carefully plan the place where you are going to put the water heater.  
Correct combustion, vent action, and vent pipe installation are  
very important in preventing death from possible carbon monoxide  
poisoning and res.  
PREPARING FOR THE INSTALLATION  
Examine the location to ensure the water heater complies with the  
“Facts to Consider About the Location” section in this manual.  
1. Read the “Safety Precautions” section, page 3 of this manual rst and  
then the entire manual carefully. If you don’t follow the safety rules,  
the water heater will not operate properly. It could cause DEATH,  
SERIOUS BODILY INJURY AND/OR PROPERTY DAMAGE.  
6. For California installation this water heater must be braced, anchored,  
or strapped to avoid falling or moving during an earthquake. See  
instructions for correct installation procedures. Instructions may be  
obtained from California Ofce of the State Architect, 400 P Street,  
Sacramento, CA 95814.  
This manual contains instructions for the installation, operation,  
and maintenance of the gas-red water heater. It also contains  
warnings throughout the manual that you must read and be aware  
of. All warnings and all instructions are essential to the proper  
operation of the water heater and your safety. Since we cannot put  
everything on the rst few pages, READ THE ENTIRE MANUAL  
BEFORE ATTEMPTING TO INSTALL OR OPERATE THE WATER  
HEATER.  
7. Massachusetts Code requires this water heater to be installed in  
accordance with Massachusetts 248-CMR 2.00: State Plumbing Code  
and 248-CMR 5.00. For more information see next page.  
PRODUCT SPECIFICATIONS  
TANK  
CAPACITY  
IN GALS.  
(LTRS)  
RECOVERY  
MINIMUM  
VENT PIPE  
INCHES  
(mm)  
INPUT  
RATE  
RATE GALS.  
DIAMETER  
INCHES  
DIMENSIONS IN  
INCHES (mm) HEIGHT  
TO JACKET TOP  
55 (1,397)  
MODEL  
TYPE OF  
GAS  
PER HOUR  
NUMBER  
(Btu/hr)  
40,000  
40,000  
40,000  
40,000  
@ 90°F RISE  
(mm)  
153.332040  
153.332050  
153.332060  
153.332070  
40 (151)  
50 (189)  
40 (151)  
50 (189)  
NATURAL  
NATURAL  
PROPANE  
PROPANE  
44  
44  
44  
44  
2 (51)  
18 1/2 (470)  
20 (508)  
2 (51)  
56 3/4 (1,441)  
2 (51)  
18 1/2 (470)  
20 (508)  
55 (1,397)  
2 (51)  
56 3/4 (1,441)  
5
INSTALLATION REQUIREMENTS FOR THE COMMONWEALTH OF MASSACHUSETTS  
For all side wall terminated, horizontally vented power vent, direct vent, and power direct vent gas fueled water heaters installed  
in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by  
the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above nished grade in the  
area of the venting, including but not limited to decks and porches, the following requirements shall be satised:  
INSTALLATION OF CARBON MONOXIDE DETECTORS At the time of installation of the side wall horizontal vented gas  
fueled equipment, the installing plumber or gastter shall observe that a hard wired carbon monoxide detector with an alarm  
and battery back-up is installed on the oor level where the gas equipment is to be installed. In addition, the installing plumber  
or gastter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each  
additional level of the dwelling, building or structure served by the sidewall horizontal vented gas fueled equipment. It shall  
be the responsibility of the property owner to secure the services of qualied licensed professionals for the installation of hard  
wired carbon monoxide detectors.  
In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired  
carbon monoxide detector with alarm and battery back-up may be installed on the next adjacent oor level.  
In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall  
have a period of thirty (30) days to comply with the above requirements provided that during said thirty (30) day period, a bat-  
tery operated carbon monoxide detector with an alarm shall be installed.  
APPROVED CARBON MONOXIDE DETECTORS Each carbon monoxide detector as required in accordance with the above  
provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and CSA certied.  
SIGNAGE Ametal or plastic identication plate shall be permanently mounted to the exterior of the building at a minimum height  
of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appli-  
ance or equipment. The sign shall read, in print size no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY BELOW.  
KEEP CLEAR OF ALL OBSTRUCTIONS.”  
INSPECTION The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the  
installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance  
with the provisions of 248 CMR 5.08(2)(a) 1 through 4.  
EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:  
1. The equipment listed in Chapter 10 entitled “Equipment Not Required To Be Vented” in the most current edition of NFPA 54  
as adopted by the Board; and  
2. Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the  
dwelling, building, or structure used in whole or in part for residential purposes.  
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM PROVIDED When the manufacturer of Product  
Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with  
the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall  
include:  
1. Detailed instructions for the installation of the venting system design or the venting system components; and  
2. A complete parts list for the venting system design or venting system.  
MANUFACTURER REQUIREMENTS - GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED When the manufacturer of  
a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the ue gases,  
but identies “special venting systems,” the following requirements shall be satised by the manufacturer:  
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation  
instructions; and  
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a  
parts list and detailed installation instructions.  
A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment, all venting  
instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or  
equipment at the completion of the installation.  
6
MATERIALS AND BASIC TOOLS NEEDED  
Materials Needed  
To simplify the installation Sears has available the installation parts shown below. You may or may not need all of these materials,  
depending on your type of installation.  
DRAIN PANS AVAILABLE IN  
EXPANSION TANKS FOR  
THERMAL EXPANSION  
CONDITIONS AVAILABLE  
IN 2 GALLONS  
20” (508 mm) DIAMETER FOR  
WATER HEATERS HAVING A  
DIAMETER 18” (457 mm) OR  
LESS, 24” (610mm) DIAMETER  
FOR WATER HEATERS HAVING  
A DIAMETER 22” (559 mm)  
OR LESS AND AVAILABLE IN  
28” (711 mm) DIAMETER FOR  
WATER HEATERS HAVING A  
DIAMETER 26” (660 mm) OR  
LESS.  
(7.6 LITERS) AND  
5 GALLONS (18.9 LITERS)  
CAPACITY THROUGH  
LOCAL SEARS STORE  
OR SERVICE CENTER.  
WATER HEATER INSTALLATION KIT WITH  
FLEXIBLE CONNECTORS FOR 3/4”  
(19.05 mm) OR 1/2” (12.7 mm) THREADED  
OR COPPER PLUMBING AND FLEXIBLE GAS  
CONNECTOR WITH FITTINGS.  
Basic Tools  
Additional Tools Needed  
When Sweat Soldering  
You may or may not need all these tools, depending on your  
type of installation. These tools can be purchased at your local  
Sears Store.  
• Tubing Cutters or Hacksaw  
• Propane Tank  
• Soft Solder  
• Solder Flux  
• Emery Cloth  
• Pipe Wrenches (2) 14” (356 mm)  
• Screwdriver  
• Tin Snips  
• 6’ (1.82 m) Tape or Folding Ruler  
• Garden Hose  
• Wire Brushes  
• Drill  
• Pipe Dope or Teon Tape  
DRILL  
PROPANE  
TORCH  
TUBING CUTTER  
SLOT-HEAD SCREWDRIVER  
TIN SNIPS  
PHILLIPS SCREWDRIVER  
ROLL OF  
HACKSAW  
EMERY CLOTH  
PIPE DOPE  
(SQUEEZE TUBE)  
USE FOR WATER AND GAS  
CONNECTIONS  
ROLL OF TEFLON  
TAPE (USE ONLY ON  
WATER CONNECTIONS)  
3/4” (19 mm) WIRE BRUSH  
ROLL OF LEAD-FREE  
SOFT SOLDER  
SOLDER  
FLUX  
6 FOOT TAPE  
GARDEN HOSE  
PIPE WRENCH  
1/2” (13 mm) WIRE BRUSH  
7
TYPICAL INSTALLATION  
GET TO KNOW YOUR WATER HEATER - GAS MODELS  
A
B
C
D
E
F
G
H
J
Vent Pipe–Exhaust  
Vent Terminal  
K
L
Hot Water Outlet  
V
W
X
Y
Z
Drip Leg (Sediment Trap)  
Drain Valve  
Gas Valve-Thermostat  
Drain Pan  
Outlet Receptacle (115 VAC)  
Temperature-Pressure Relief Valve  
Flue  
Flue Bafe Assembly**  
Insulation  
Control Harness  
Rating Plate  
Gas Supply  
Manual Gas Shut-off Valve  
Ground Joint Union  
Vent Adapter-Rubber Boot  
Blower Assembly  
Cold Water Inlet  
Inlet Water Shut-off Valve  
Union  
M
N
O
P
Q
R
S
T
Air Intake Screen - Base Pan  
AA Inner Door  
B B Outer Door  
CC HSI Burner Assembly  
D D Air Intake Screen -  
Blower Assembly  
Inlet Dip Tube  
Anode**  
U
E E FV Sensor Assembly  
* ALL PIPING MATERIALS TO BE SUPPLIED BY CUSTOMERS.  
** LOCATED UNDER THE BLOWER ASSEMBLY.  
NATURAL HOT SURFACE IGNITER & MAIN BURNER  
HOT  
SURFACE  
IGNITOR  
SENS
PROPANE HOT SURFACE IGNITER & MAIN BURNER  
HOT  
SURFACE  
IGNITOR  
SENSOR  
TEMPERATURE INDICATORS  
*CAUTION: 115 VAC IN CONTROL HARNESS  
AND INSIDE OUTER DOOR  
TE
GAS MODELS  
WITH HOT SURFACE IGNITION  
& 2”, 3” OR 4” PVC VENT CAPABILITY  
FIGURE 1.  
8
INSTALLATION INSTRUCTIONS  
4. Attach a hose to the water heater drain  
valve and put the other end in a oor  
Removing the Old Water Heater  
drain or outdoors. Open the water  
heater drain valve. Open a nearby hot  
water faucet which will relieve pressure  
in the water heater and speed draining.  
The water passing out of the drain valve  
may be extremely hot. To avoid being  
scalded, make sure all connections are  
tight and that the water ow is directed  
away from any person, see Figures 2  
and 5.  
FIGURE 5.  
5. Disconnect the vent pipe from the blower assembly where it connects  
to the water heater. In most installations the vent pipe can be lifted  
off after any screw or other attached devices are removed. Make sure  
existing vent complies with maximum and minimum vent lengths on  
page 17.  
6. If you have copper piping to the water heater, the two copper water  
pipes can be cut with a hacksaw approximately four inches away  
from where they connect to the water heater, see Figure 6. This will  
avoid cutting off pipes too short. Additional cuts can be made later  
if necessary. Disconnect the temperature-pressure relief valve drain  
line. When the water heater is drained, disconnect the hose from the  
drain valve. Close the drain valve. The water heater is now completely  
disconnected and ready to be removed.  
FIGURE 2.  
1. Turn “OFF” the gas supply to the water  
heater.  
If the main gas line Shut-off valve  
serving all gas appliances is used, also  
shut “OFF” the gas at each appliance.  
Leave all gas appliances shut “OFF”  
until the water heater installation is  
completed, see Figures 2 and 3.  
FIGURE 6.  
If you have galvanized pipes to the water heater, loosen the two  
galvanized pipes with a pipe wrench at the union in each line. Also  
disconnect the piping remaining to the water heater, see Figure 7.  
These pieces should be saved since they may be needed when  
reconnecting the new water heater. Disconnect the temperature-  
pressure relief valve drain line. When the water heater is drained,  
disconnect the hose from the drain valve. Close the drain valve.  
The water heater is now completely disconnected and ready to be  
removed. Mineral buildup or sediment may have accumulated in the  
old water heater. This causes the water heater to be much heavier  
than normal and this residue, if spilled out, could cause staining.  
FIGURE 3.  
2. Turn “OFF” the water supply to the water  
heater at the water shut off valve or  
water meter. Some installations require  
that the water be turned off to the entire  
house, see Figures 2 and 4.  
FIGURE 4.  
3. Check again to make sure the gas supply is “OFF” to the water heater.  
Then disconnect the gas supply connection from the gas control  
valve.  
FIGURE 7.  
9
FACTS TO CONSIDER ABOUT THE LOCATION  
Carefully choose an indoor location for the new water heater, because  
the placement is a very important consideration for the safety of the  
occupants in the building and for the most economical use of the  
appliance. This water heater is not for use in manufactured (mobile)  
homes or outdoor installation.  
FIGURE 8.  
Whether replacing an old water heater or putting the water heater in a  
new location, the following critical points must be observed:  
1. Select a location indoors as close as practical to the vent terminal or  
location to which the water heater vent piping is going to be connected,  
and as centralized with the water piping system as possible.  
2. Selected location must provide adequate clearances for servicing  
and proper operation of the water heater.  
Installation of the water heater must be accomplished in such a manner  
that if the tank or any connections should leak, the ow will not cause  
damage to the structure. For this reason, it is not advisable to install the  
water heater in an attic or upper oor. When such locations cannot be  
avoided, a suitable drain pan should be installed under the water heater.  
Drain pans are available at your local hardware store. Such a drain pan  
must have a minimum length and width of at least 2” (5.1 cm) greater  
than the water heater dimensions and must be piped to an adequate  
drain. The pan must not restrict combustion air ow.  
Also, the water heater must be located and/or protected so it is not subject  
to physical damage by a moving vehicle.  
Water heater life depends upon water quality, water pressure and the  
environment in which the water heater is installed. Water heaters are  
sometimes installed in locations where leakage may result in property  
damage, even with the use of a drain pan piped to a drain. However,  
unanticipated damage can be reduced or prevented by a leak detector  
or water shut-off device used in conjunction with a piped drain pan.  
These devices are available from some plumbing supply wholesalers  
and retailers, and detect and react to leakage in various ways:  
• Sensors mounted in the drain pan that trigger an alarm or turn off the  
incoming water to the water heater when leakage is detected.  
• Sensors mounted in the drain pan that turn off the water supply to the  
entire home when water is detected in the drain pan.  
This water heater must not be installed directly on carpeting. Carpeting  
must be protected by metal or wood panel beneath the appliance  
extending beyond the full width and depth of the appliance by at least  
3” (7.6 cm) in any direction, or if the appliance is installed in an alcove  
or closet, the entire oor must be covered by the panel. Failure to heed  
this warning may result in a re hazard.  
• Water supply shut-off devices that activate based on the water pressure  
differential between the cold water and hot water pipes connected to  
the water heater.  
• Devices that will turn off the gas supply to a gas water heater while at  
the same time shutting off its water supply.  
INSTALLATIONS INAREAS WHERE FLAMMABLE LIQUIDS (VAPORS)  
ARE LIKELY TO BE PRESENT OR STORED (GARAGES, STORAGE  
AND UTILITY AREAS, ETC.): Flammable liquids (such as gasoline,  
solvents, propane (LP or butane, etc.) and other substances (such as  
adhesives, etc.) emit ammable vapors which can be ignited by a gas  
water heater’s hot surface igniter or main burner. The resulting ashback  
and re can cause death or serious burns to anyone in the area. This  
water heater is equipped with a FV sensor for detecting the presence of  
ammable vapors, see Figure 8. When the sensor detects those vapors,  
the unit will shut down and not operate. Should this happen, please  
refer to the troubleshooting guide on pages 29-30. Even though this  
water heater is a ammable vapors ignition resistant water heater and  
is designed to reduce the chances of ammable vapors being ignited,  
gasoline and other ammable substances should never be stored or  
used in the same vicinity or area containing a gas water heater or other  
open ame or spark producing appliance.  
Minimum clearances between the water heater and combustible  
construction are 0 inch at the sides and rear, 5” (12.7 cm) from the front  
10  
and 12” (30.5 cm) from the top. (Standard clearance.) If clearances  
stated on the heater differ from standard clearances, install water heater  
according to clearances stated on the heater.  
in many cases, will also react to form corrosive hydrochloric acid when  
exposed to the combustion products of the water heater. The results  
can be hazardous, and also cause product failure.  
INSULATION BLANKETS  
Adequate clearance for servicing this appliance should be considered  
before installation, such as changing the anodes, etc.  
Insulation blankets are available to the general public for external use  
on gas water heaters but are not necessary with Kenmore products.  
The purpose of an insulation blanket is to reduce the standby heat loss  
encountered with storage tank heaters. Your Kenmore water heater  
meets or exceeds the National Appliance Energy Conservation Act  
standards with respect to insulation and standby loss requirements,  
making an insulation blanket unnecessary.  
A minimum clearance of 5” (12.7 cm) must be allowed for access  
to replaceable parts such as the thermostats, drain valve and relief  
valve.  
When installing the heater, consideration must be given to proper location.  
Location selected should be as close to the wall as practicable and as  
centralized with the water piping system as possible.  
FIGURE 9.  
Should you choose to apply an insulation blanket to this heater, you  
should follow these instructions (For identification of components  
mentioned below, see Figure 1). Failure to follow these instructions can  
restrict the air ow required for proper combustion, potentially resulting  
in re, asphyxiation, serious personal injury or death.  
• Do not apply insulation to the top of the water heater, as this will  
interfere with safe operation of the blower assembly.  
• Do not cover the outer door, thermostat or temperature & pressure  
relief valve.  
• Do not allow insulation to come within 2” (5.1 cm) of the oor to  
prevent blockage of combustion air ow to the burner.  
• Do not cover the instruction manual. Keep it on the side of the  
water heater or nearby for future reference.  
• Do obtain new warning and instruction labels from Sears  
for placement on the blanket directly over the existing labels.  
• Do inspect the insulation blanket frequently to make certain it  
does not sag, thereby obstructing combustion air ow.  
A gas water heater cannot operate properly without the correct amount  
of air for combustion. Do not install in a conned area such as a closet,  
unless you provide air as shown in the “Facts to Consider About the  
Location” section. Never obstruct the ow of ventilation air. If you have  
any doubts or questions at all, call your gas supplier. Failure to provide  
the proper amount of combustion air can result in a re or explosion and  
cause death, serious bodily injury, or property damage.  
COMBUSTION AIR AND VENTILATION FOR APPLIANCES  
LOCATED IN UNCONFINED SPACES  
UNCONFINED SPACE is space whose volume is not less than  
50 cubic feet per 1,000 Btu per hour (4.8 cubic meters per kW) of the  
aggregate input rating of all appliances installed in that space. Rooms  
communicating directly with the space in which the appliances are  
installed, through openings not furnished with doors, are considered a  
part of the unconned space.  
In unconned spaces in buildings, inltration may be adequate to provide  
air for combustion, ventilation and dilution of ue gases. However, in  
buildings of tight construction (for example, weather stripping, heavily  
insulated, caulked, vapor barrier, etc.), additional air may need to be  
provided using the methods described in “CombustionAir and Ventilation  
for Appliances Located in Conned Spaces.”  
FIGURE 10.  
COMBUSTION AIR AND VENTILATION FOR APPLIANCES  
LOCATED IN CONFINED SPACES  
If this water heater will be used in beauty shops, barber shops, cleaning  
establishments, or self-service laundries with dry cleaning equipment, it  
is imperative that the water heater or water heaters be installed so that  
combustion and ventilation air be taken from outside these areas.  
CONFINED SPACE is a space whose volume is less than 50 cubic feet  
per 1,000 Btu per hour (4.8 cubic meters per kW) of the aggregate input  
rating of all appliances installed in that space.  
Propellants of aerosol sprays and volatile compounds, (cleaners, chlorine  
based chemicals, refrigerants, etc.) in addition to being highly ammable  
11  
Chemical vapor corrosion of the ue, blower assembly and vent system  
may occur if air for combustion contains certain chemical vapors. Spray  
can propellants, cleaning solvents, refrigerator and air conditioner  
refrigerants, swimming pool chemicals, calcium and sodium chloride,  
waxes, bleach and process chemicals are typical compounds which  
are potentially corrosive.  
3. When communicating with the outdoors through horizontal ducts,  
each opening shall have a minimum free area of 1 square inch per  
2,000 Btu per hour (11 cm2/kW)) of total input rating of all equipment  
in the enclosure, see Figure 14.  
4. When ducts are used, they shall be of the same cross-sectional area  
as the free area of the openings to which they connect. The minimum  
short side dimension of rectangular air ducts shall not be less than  
3 inches (7.6 cm), see Figure 14.  
A. ALL AIR FROM INSIDE BUILDINGS: (See Figure 10 and 11)  
The conned space shall be provided with two permanent openings  
communicating directly with an additional room(s) of sufcient volume  
so that the combined volume of all spaces meets the criteria for an  
unconned space. The total input of all gas utilization equipment  
installed in the combined space shall be considered in making this  
determination. Each opening shall have a minimum free area of one  
square inch per 1,000 Btu per hour (22 cm2/kW) of the total input rating of  
all gas utilization equipment in the conned space, but not less than 100  
square inches (645 cm2). One opening shall commence within 12 inches  
(31 cm) of the top and one commencing within 12 inches (31 cm) of the  
bottom of the enclosures.  
FIGURE 14.  
FIGURE 11.  
B. ALL AIR FROM OUTDOORS: (See Figures 12, 13 and 14)  
The conned space shall be provided with two permanent openings,  
one commencing within 12 inches (31 cm) of the top and one  
commencing within 12 inches (31 cm) from the bottom of the enclosure.  
The openings shall communicate directly, or by ducts, with the outdoors  
or spaces (crawl or attic) that freely communicate with the outdoors.  
1. When directly communicating with the outdoors, each opening shall  
have a minimum free area of 1 square inch per 4,000 Btu per hour  
(5.5 cm2/kW) of total input rating of all equipment in the enclosure,  
see Figure 12.  
FIGURE 14A.  
5. Alternatively a single permanent opening may be used when  
communicating directly with the outdoors, or with spaces that freely  
communicate with the outdoors. The opening shall have a minimum  
free area of 1 square inch per 3,000 BTU per hour (8.3 cm2/kW) of  
total input rating of all equipment in the enclosure. See Figure 14A.  
6. Louvers and Grilles: In calculating free area, consideration shall be  
given to the blocking effect of louvers, grilles or screens protecting  
openings. Screens used shall not be smaller than 1/4 inch  
(6.4 mm) mesh. If the free area through a design of louver or grille  
is known, it should be used in calculating the size opening required  
to provide the free area specied. If the design and free area is not  
known, it may be assumed that wood louvers will be 20-25 percent  
free area and metal louvers and grilles will have 60-75 percent  
free area. Louvers and grilles shall be xed in the open position or  
interlocked with the equipment so that they are opened automatically  
during equipment operation.  
FIGURE 12.  
7. Special Conditions Created by Mechanical Exhausting or Fireplaces:  
operation of exhaust fans, ventilation systems, clothes dryers or  
replaces may create conditions requiring special attention to avoid  
unsatisfactory operation of installed gas utilization equipment.  
FIGURE 13.  
2. When communicating with the outdoors through vertical ducts, each  
opening shall have a minimum free area of 1 square inch per 4,000  
Btu per hour (5.5 cm2/kW) of total input rating of all equipment in the  
enclosure, see Figure 13.  
12  
WATER PIPING  
Toxic chemicals, such as those used for boiler treatment shall not be  
introduced into this system.  
When the system requires water at temperatures higher than required for  
domestic water purposes, a tempering valve must be installed. Please  
refer to Figure 15 for suggested piping arrangement.  
Water supply systems may, because of such events as high line pressure,  
frequent cut-offs, the effects of water hammer among others, have  
installed devices such as pressure reducing valves, check valves, back  
ow preventers, etc. to control these types of problems. When these  
devices are not equipped with an internal by-pass, and no other measures  
are taken, the devices cause the water system to be closed. As water is  
heated, it expands (thermal expansion) and closed systems do not allow  
for the expansion of heated water.  
The water within the water heater tank expands as it is heated and  
increases the pressure of the water system. If the relieving point of the  
water heater’s temperature-pressure relief valve is reached, the valve will  
relieve the excess pressure. The temperature-pressure relief valve is  
not intended for the constant relief of thermal expansion. This is an  
unacceptable condition and must be corrected.  
It is recommended that any devices installed which could create a closed  
system have a by-pass and/or the system have an expansion tank to  
relieve the pressure built by thermal expansion in the water system.  
Thermal expansion tanks are available from Sears stores and through  
the Sears Service Centers. Contact the local plumbing inspector, water  
supplier and/or the Sears Service Center for assistance in controlling  
these situations.  
HOTTER WATER CAN SCALD:  
Water heaters are intended to produce hot water. Water heated to a  
temperature which will satisfy space heating, clothes washing, dish  
washing, cleaning and other sanitizing needs can scald and permanently  
injure you upon contact. Some people are more likely to be permanently  
injured by hot water than others. These include the elderly, children, the  
inrm, or physically/mentally handicapped. If anyone using hot water in  
your home ts into one of these groups or if there is a local code or state  
law requiring a certain temperature water at the hot water tap, then you  
must take special precautions. In addition to using the lowest possible  
temperature setting that satises your hot water needs, a means such  
as a *mixing valve, should be used at the hot water taps used by these  
people or at the water heater, see Figure 15. Valves for reducing point of  
use temperature by mixing cold and hot water are also available:  
NOTE: To protect against untimely corrosion of hot and cold  
water ttings, it is strongly recommended that di-electric unions  
or couplings be installed on this water heater when connected to  
copper pipe.  
Figure 16 shows the typical attachment of the water piping to the  
water heater. The water heater is equipped with 3/4 inch NPT water  
connections.  
FIGURE 15.  
Consult Sears Service Center. Follow manufacturer’s instructions for  
installation of the valves. Before changing the factory setting on the  
thermostat, read the “Temperature Regulation” section in this manual.  
NOTE: If using copper tubing, solder tubing to an adapter before  
attaching the adapter to the cold water inlet connection. Do not  
solder the cold water supply line directly to the cold water inlet. It  
will harm the dip tube and damage the tank.  
Look at the top cover of the water heater. The water outlet is marked  
“HOT”. Put two or three turns of teon tape around the threaded end  
of the threaded-to-sweat coupling and around both ends of the 3/4”  
NPT threaded nipple. Using exible connectors, connect the hot water  
pipe to the hot water outlet on the water heater.  
Look at the top of the water heater. The cold water inlet is marked  
“COLD”. Put two or three turns of teon tape around the threaded  
end of the threaded-to-sweat coupling and around both ends of the  
3/4” NPT threaded nipple. Using exible connectors, connect the cold  
water pipe to the cold water inlet of the water heater.  
This water heater shall not be connected to any heating system or  
component or used as a non-potable water heating appliance.  
All piping components connected to this unit shall be suitable for use with  
potable water.  
13  
TEMPERATURE-PRESSURE RELIEF VALVE  
INSTALLATION COMPLETED USING INSTALLATION KIT  
This heater is provided with a properly certified combination  
temperature - pressure relief valve by the manufacturer.  
The valve is certied by a nationally recognized testing laboratory that  
maintains periodic inspection of production of listed equipment of materials  
as meeting the requirements for Relief Valves for Hot Water Supply  
Systems, ANSI Z21.22 • CSA 4.4, and the code requirements of ASME.  
If replaced, the valve must meet the requirements of local codes, but not  
less than a combination temperature and pressure relief valve certied  
as indicated in the above paragraph.  
The valve must be marked with a maximum set pressure not to  
exceed the marked hydrostatic working pressure of the water heater  
(150 psi = 1,035 kPa) and a discharge capacity not less than the water  
heater input rate as shown on the model rating plate.  
FIGURE 16.  
For safe operation of the water heater, the relief valve must not be removed  
from its designated opening nor plugged.  
T & P Valve and Pipe Insulation (if supplied)  
The temperature-pressure relief valve must be installed directly into the  
tting of the water heater designed for the relief valve. Position the valve  
downward and provide tubing so that any discharge will exit only within 6  
inches (15.2 cm) above, or at any distance below the structural oor. Be  
certain that no contact is made with any live electrical part. The discharge  
opening must not be blocked or reduced in size under any circumstances.  
Excessive length, over 30 feet (9.14 m), or use of more than four elbows  
can cause restriction and reduce the discharge capacity of the valve, see  
Figures 16 or 20.  
Remove insulation for T & P valve and pipe connections from carton.  
No valve or other obstruction is to be placed between the relief valve  
and the tank. Do not connect tubing directly to discharge drain unless a  
6” (15.2 cm) air gap is provided. To prevent bodily injury, hazard to life,  
or property damage, the relief valve must be allowed to discharge water  
in quantities should circumstances demand. If the discharge pipe is not  
connected to a drain or other suitable means, the water ow may cause  
property damage.  
FIGURE 17.  
Fit pipe insulation over the incoming cold water line and the hot water line.  
Make sure that the insulation is against the top cover of the heater.  
Fit T & P valve insulation over valve. Make sure that the insulation does  
not interfere with the lever of the T & P valve.  
Secure all insulation using tape.  
14  
If the main gas line Shut-off serving all gas appliances is used, also turn  
“off” the gas at each appliance. Leave all gas appliances shut “off” until  
the water heater installation is complete.  
The Discharge Pipe:  
• Shall not be smaller in size than the outlet pipe size of the valve, or  
have any reducing couplings or other restrictions.  
• Shall not be plugged or blocked.  
• Shall be of material listed for hot water distribution.  
• Shall be installed so as to allow complete drainage of both the  
temperature-pressure relief valve, and the discharge pipe.  
• Shall terminate at an adequate drain.  
A gas line of sufcient size must be run to the water heater. Consult the  
current edition of National Fuel Gas Code ANSI Z223.1/NFPA 54 and  
your gas supplier concerning pipe size.  
There must be:  
• Shall not have any valve between the relief valve and tank.  
Areadily accessible manual shut off valve in the gas supply line serving  
the water heater, and  
Adrip leg (sediment trap) ahead of the gas control valve to help prevent  
dirt and foreign materials from entering the gas control valve.  
• A exible gas connector or a ground joint union between the shut off  
valve and control valve to permit servicing of the unit.  
Be sure to check all the gas piping for leaks before lighting the water  
heater. Use a soapy water solution, not a match or open ame. Rinse  
off soapy solution and wipe dry.  
The temperature-pressure relief valve must be manually operated at  
least once a year. Caution should be taken to ensure that (1) no one  
is in front of or around the outlet of the temperature-pressure relief  
valve discharge line, and (2) the water manually discharged will not  
cause any bodily injury or property damage because the water may  
be extremely hot.  
If after manually operating the valve, it fails to completely reset and  
continues to release water, immediately close the cold water inlet  
to the water heater, follow the draining instructions, and replace the  
temperature-pressure relief valve with a new one.  
Water heaters covered in this manual have been tested and approved for  
installation at elevations up to 7,700 feet (2,347 m) above sea level. When  
installed at elevations above 7,700 feet (2,347 m), input rating should  
be reduced at the rate of 4 percent for each 1,000 feet (305 m) above  
sea level which requires replacement of the burner orice in accordance  
with National Fuel Gas Code ANSI Z223.1/NFPA 54. Contact your local  
gas supplier for further information.  
GAS PIPING  
Failure to replace the standard orice with a high altitude orice when  
installed at elevations above 7,700 feet (2,347 m) could result in improper  
and inefcient operation of the appliance, producing carbon monoxide  
gas in excess of safe limits. This could result in serious injury or death.  
Contact your gas supplier for any specic changes which may be required  
in your area.  
Make sure the gas supplied is the same type listed on the model rating  
plate. The inlet gas pressure must not exceed 14 inch water column (3.5  
kPa) for natural and propane gas (L.P.). The minimum inlet gas pressure  
shown on the rating plate is that which will permit ring at rated input.  
All gas piping must comply with local codes and ordinances or with the  
National Fuel Gas Code (ANSI Z223.1/ NFPA-54) whichever applies.  
Copper and brass tubing and ttings (except tin lined copper tubing)  
shall not be used.  
Use pipe joint compound or teon tape marked as being resistant to the  
action of petroleum [Propane (L.P.)] gases.  
If the gas control valve is subjected to pressures exceeding 1/2 psi  
(3.5 kPa), the damage to the gas control valve could result in a re or  
explosion from leaking gas.  
15  
The appliance and its gas connection must be leak tested before placing  
the appliance in operation.  
The appliance and its individual Shut-off valve shall be disconnected  
from the gas supply piping system during any pressure testing of  
that system at test pressures in excess of 1/2 pound per square inch  
(3.5 kPa). It shall be isolated from the gas supply piping system by  
closing its individual manual Shut-off valve during any pressure testing  
of the gas supply piping system at test pressures equal to or less than  
1/2 pound per square inch (3.5 kPa).  
Connecting the gas piping to the gas control valve of the water heater  
can be accomplished by either of the two methods shown in Figures  
18 and 19.  
FIGURE 18. GAS PIPING WITH  
FLEXIBLE CONNECTOR.  
FIGURE 20.  
FILLING THE WATER HEATER  
FIGURE 19. GAS PIPING WITH ALL  
BLACK IRON PIPE TO GAS CONTROL.  
Never use this water heater unless it is completely full of water. To prevent  
damage to the tank, the tank must be lled with water. Water must ow  
from the hot water faucet before turning “ON” gas to the water heater.  
SEDIMENT TRAPS  
To ll the water heater with water:  
1. Close the water heater drain valve by turning the handle to the  
right (clockwise). The drain valve is on the lower front of the water  
heater.  
2. Open the cold water supply valve to the water heater.  
NOTE: The cold water supply valve must be left open when the  
water heater is in use.  
3. To insure complete lling of the tank, allow air to exit by opening the  
nearest hot water faucet. Allow water to run until a constant ow is  
obtained. This will let air out of the water heater and the piping.  
4. Check all water piping and connections for leaks. Repair as  
needed.  
Contaminants in the gas lines may cause improper operation of the gas  
control valve that may result in re or explosion. Before attaching the  
gas line be sure that all gas pipe is clean on the inside. To trap any  
dirt or foreign material in the gas supply line, a drip leg (sometimes  
called a sediment trap) must be incorporated in the piping. The drip leg  
must be readily accessible. Install in accordance with the “Gas Piping”  
section. Refer to the current edition of the National Fuel Gas Code,  
ANSI Z223.1/NFPA 54.  
BLOWER ASSEMBLY INSTALLATION  
SEQUENCE OF INSTALLATION  
1. This power vented water heater comes with the blower assembly  
installed.  
2. After the unit is set in place, make sure the blower assembly is still  
mounted securely and the air intake screen of the blower assembly  
is installed in the dilution air opening. Also make sure the drain port  
of the rubber boot vent adapter is capped off. Lastly, make sure there  
is no damage to the blower.  
Asediment trap shall be installed as close to the inlet of the water heater  
as practical at the time of water heater installation. The sediment trap  
shall be either a tee tting with a capped nipple in the bottom outlet or  
other device recognized as an effective sediment trap. If a tee tting is  
used, it shall be installed in conformance with one of the methods of  
installation shown in Figures 18 and 19.  
3. Make sure there is no packing material in the discharge of the blower  
or the intake of the dilution air restrictor, see Figure 21.  
16  
4. Make sure that the plastic tubing is still attached from the air pressure  
switch to the port on the blower housing. Make sure the plastic tubing  
is not folded anywhere between the pressure switch and the blower  
housing.  
7. Do not plug in power cord until vent system is completely installed.  
This power vent heater operates on 110-120 Vac, therefore a  
grounded outlet must be within reach of the six (6) foot (1.8 m) exible  
power cord supplied with the unit (see Figure 1). The power cord  
supplied may be used only where local codes permit. If local codes  
do not permit the use of a exible power supply cord:  
5. Make sure the ON/OFF switch is in the OFF position and that the outer  
harness is connected from the blower control box to the connector  
on the bottom side of the gas valve.  
a.) Make sure the unit is unplugged from wall outlet. Remove screws  
and open panel on front of control box.  
6. If the outer harness is not factory installed, make sure the ON/OFF  
switch is in the OFF position and then connect the harness from the  
blower control box to the connector on the bottom side of the gas  
valve.  
b.) Cut the exible power cord, leaving enough to be able to make  
connections and remove the strain relief tting from box.  
c.) Install suitable conduit tting in side of enclosure and then follow (d.)  
and (e.) below.  
d.) Splice eld wiring into existing wiring using code authorized method  
(wire nuts, etc.).  
e.) Be certain that neutral and live connections are not reversed when  
making these connections.  
f.) Close panel on the side of control box, make sure that access panel  
is secured shut.  
17  
pipe is NOT ALLOWED. If 2” pipe is to be used, then a 2” to 3” bell  
reducer is recommended. Figure 21 shows the recommended location  
for the bell reducer. If the bell reducer is located at the rubber boot on the  
blower assembly, then a short section of 3” vent pipe needs to be installed  
in the rubber boot for proper connection of the 2” to 3” bell reducer. That  
length can be the minimum length required for the connection.  
VENT CONNECTIONS TO BLOWER ASSEMBLY  
Figure 21 shows the optimal placement of the 2” to 3” or 3” to 4” reducer;  
however, the vent can be reduced at any point in the vent system as long  
as the maximum vent length is not exceeded.  
If 4” pipe is to be used, then a 3” to 4” bell reducer is recommended.  
Figure 21 shows the recommended location for the bell reducer. If the  
bell reducer is located at the rubber boot on the blower assembly, then  
a short section of 3” vent pipe needs to be installed in the rubber boot  
for proper connection of the 3” to 4” bell reducer. That length can be  
the minimum length required for the connection.  
FIGURE 21.  
The water heaters covered by this manual are supplied with a 2”  
Schedule 40 PVC 22.5° Vent Terminal. If you decide to vent with 3”  
or 4” pipe, a Schedule 40 DWV 45° Vent Terminal must be used. For  
your convenience, we have included a screen for both 3” and 4” Vent  
Terminals.  
VENTING AND INSTALLATION  
Plan the layout of the vent system from the vent termination to the water  
heater considering all of the 90° and 45° elbows plus the number of feet  
of pipe that would be needed to install the total vent system. The water  
heater must be vented to the outdoors as described in these instructions.  
DO NOT connect this water heater to an existing vent or chimney. It must  
be vented separately from all other appliances. Nonmetallic vent may be  
used if it has “Heat Deection Temperature” (HDT@66 psi) or 455 kPa of  
at least 157°F or 69°C. Typical nonmetallic vent materials meeting this  
requirement are: PVC (Schedule 40,ASTM D-1785), Coex Cellular Core  
(Schedule 40, ASTM F-441), CPVC (Schedule 40, ASTM D-2846), ABS  
(Schedule 40, ASTM D-2661). The ttings, other than the supplied Vent  
Termination should be equivalent to the following: PVC (Schedule 40,  
DWV, ASTM D-2665), CPVC (Schedule 40, DWV, ASTM F-438), ABS  
(Schedule 40 DWV, ASTM D-2661).  
The vent piping should be connected to the blower with a rubber adapter  
and secured with hose clamps. The adapter and clamps are provided  
with the heater.  
Even though the ue gas temperature leaving the blower is between  
140°F (69°C) and 175°F (79°C), some installations will have water  
vapor condense in the vent piping. If this occurs, then adequate means  
of draining and disposing of the condensate needs to be made by  
the installer.  
CONDENSATION  
Condensate formation does not occur in all installations of power vented  
water heaters, but should be protected against on installations where it  
can form in the venting system. Condensation in the venting system of  
power vented water heaters is dependent upon installation conditions  
including, but not limited to ambient temperature and humidity of  
installation location, ambient temperature and humidity of venting space,  
vent discharge and slope, and product usage. In certain conditions,  
installations in unconditioned space or having long horizontal or vertical  
vent runs may accumulate condensate. In these conditions, the vent  
pipe should be sloped downward away from the blower assembly 1/4”  
(6.4 mm) per ve feet (1.5 m) of pipe but not more than 1 1/2” (3.8 cm) in  
the total vent length. If the vent piping is vented level or sloped upwards  
away from the blower assembly, then adequate means for draining  
and disposing of the condensate needs to be made by the installer  
(if condensate is detected). If you have condensate, then a 3/8” drain  
hose can be connected to the built-in drain port of the rubber boot on  
the blower assembly. For your convenience, the rubber boot is supplied  
with a removable cap on the built-in drain port. Prior to operating the  
water heater, make sure the removable cap is installed on the drain port  
(if a drain hose is not needed).  
The cement used should be as recommended by the vent pipe  
manufacturer. See the instructions on pages 20 and 21 for the proper  
method of cutting and cementing the PVC pipe and ttings.  
The unit may be vented horizontally through a wall or vertically through  
the roof. Pipe runs must be adequately supported along both vertical  
and horizontal runs as follows:  
• For Schedule 40, 2” PVC, ABS, Coex Cellular Core vent pipe: Every  
3 feet (0.9 m).  
• For Schedule 40, 3” PVC, ABS, Coex Cellular Core vent pipe: Every  
3.5 feet (1.1 m).  
• For Schedule 40, 4” PVC, ABS, Coex Cellular Core vent pipe: Every  
4 feet (1.2 m).  
• For Schedule 40, 2” CPVC vent pipe: Every 5 feet (1.5 m).  
• For Schedule 40, 3” CPVC vent pipe: Every 6 feet (1.8 m).  
• For Schedule 40, 4” CPVC vent pipe: Every 6.5 feet (2.0 m).  
MAXIMUM VENT LENGTHS  
40,000 BTU Units:  
It is imperative that the rst hanger (or support) be located on the  
horizontal run immediately adjacent to the rst 90-degree elbow from  
the vertical rise. Support method used should isolate the vent pipe from  
the oor joists or other structural members to prevent the transmission  
of noise and vibration. Do not support, pin, or otherwise secure the  
venting system in a way that restricts the normal thermal expansion and  
contraction of the chosen venting material.  
For 2” Venting, the maximum equivalent feet of pipe allowed is 40  
feet (12.2 m). This does not include the supplied vent termination for the  
water heater. For the 2” venting, one 90° elbow is approximately equal  
to 5 feet (1.5 m). One 45° elbow is approximately equal to 2.5 feet (0.8  
m). It is recommended that at least 2 feet (0.6 m) of spacing be used in  
between all 45° elbows and all 90°elbows.  
If the water heater is being installed as a replacement for an existing  
power vented heater in pre-existing venting, a thorough inspection of  
the existing venting system must be performed prior to any installation  
work. Verify that the correct material as detailed above has been used,  
and that the minimum or maximum vent lengths and terminal location  
as detailed in this manual have been met. Carefully inspect the entire  
venting system for any signs of cracks or fractures, particularly at the  
joints between elbows and other ttings and the straight runs of vent pipe.  
Check the system for signs of sagging or other stresses in the joints as  
a result of misalignment of any components in the system. If any of  
these conditions are found, they must be corrected in accordance with  
the venting instructions in this manual before completing the installation  
and putting the water heater into service.  
For 3” Venting, the maximum equivalent feet of pipe allowed is  
120 feet (36.6 m). This does not include the Vent Termination (supplied  
locally) for the water heater. For the 3” venting, one 90° elbow is  
approximately equal to 5 feet (1.5 m). One 45° elbow is approximately  
equal to 2.5 feet (0.8 m). It is recommended that at least 2 feet (0.6 m)  
of spacing be used in between all 45° elbows and all 90°elbows.  
For 4” Venting, the maximum equivalent feet of pipe allowed is  
160 feet (48.8 m). This does not include the Vent Termination (supplied  
locally) for the water heater. For the 4” venting, one 90° elbow is  
approximately equal to 8 feet (2.4 m). One 45° elbow is approximately  
equal to 4 feet (1.2 m). It is recommended that at least 2 feet (0.6 m) of  
spacing be used in between all 45° elbows and all 90°elbows.  
Except where instructed in this manual, the mixing of 2”, 3” and 4” vent  
18  
Vent pipes serving power vented appliances are classied by building  
codes as “vent connectors”. Required clearances from combustible  
materials must be provided in accordance with information in this  
manual under FACTS TO CONSIDER ABOUT THE LOCATION and  
VENT TERMINAL INSTALLATIONS, and with the National Fuel Gas  
Code and local codes.  
VENTING  
VENT TERMINAL INSTALLATION  
1. After the point of termination has been determined, use the cover  
plate as a template to mark the hole for the vent pipe to insert through  
the wall. BEWARE OF CONCEALED WIRING AND PIPING INSIDE  
OF WALL.  
2. If the Vent Terminal is being installed on the outside of a nished wall,  
it may be easier to mark both the inside and outside wall. Align the  
holes by drilling a hole through the center of the template from the  
inside through to the outside. The template can now be positioned  
on the outside wall using the drilled hole as a centering point for the  
template.  
3. A) MASONRY SIDE WALLS  
Chisel an opening approximately one half inch larger than the marked  
circle.  
B) WOODEN SIDE WALLS  
Drill a pilot hole approximately one quarter inch outside of the marked  
circle. This pilot hole is used as a starting point for a saws-all or sabre  
saw blade. Cut around the marked circle staying approximately one  
quarter inch outside of the line. (This will allow the vent pipe to easily  
slide through the opening. The resulting gap will be covered up by  
the vent terminal cover plates.) Repeat this step on inside wall if  
necessary.  
4. When the vent piping cannot pass through an outside wall at a  
height greater than or equal to 12” above the ground (or above snow  
accumulation level), then the installation can be modied as shown  
below.  
The vent system must terminate so that proper clearances are maintained  
as cited in local codes or the current edition of the National Fuel Gas  
Code, ANSI Z223.1/NFPA 54, 7.3.4e and 7.8a,b, as follows:  
1. The exit terminals of a mechanical vent system shall be not less  
than 7 feet (2.13 m) above grade when located adjacent to public  
walkways, see Figure 23.  
2. A venting system shall terminate at least 3 feet (91 cm) above any  
forced air inlet located within 10 feet (3.1 m), see Figure 23.  
3. The venting system shall terminate at least 4 feet (1.2 m) below, 4 feet  
(1.2 m) horizontally from or, 12 in. (30 cm) above any door, window  
or gravity air inlet into any building.  
The manufacturer also recommends that the vent termination should  
not be installed closer than 3 feet (91 cm) from an inside corner of  
an L shaped structure and not be less than 12 in. (30 cm) above  
grade.  
The vent shall terminate a minimum of 12’’ (30.5 cm) above expected  
snowfall level to prevent blockage of vent termination, see Figure  
23.  
4. In cold climates, it is recommended that vent termination not be  
mounted directly above or within 3 feet (91 cm) horizontally from an oil  
tank vent or gas meter to avoid potential freeze-up from condensation,  
see Figure 23.  
FIGURE 22.  
Plan the vent system layout so that proper clearances are maintained  
from plumbing and wiring.  
19  
FIGURE 23.  
This unit can vent through 2”, 3” or 4” nonmetallic pipe and ttings.  
VERTICAL VENT TERMINATION RESTRICTIONS  
The vent pipe installation can be started from either the blower  
discharge or the termination wall. Keep in mind the total vent system  
(pipe and elbows) when installing the vent system, see VENTING AND  
INSTALLATION AND MAXIMUM VENT LENGTHS, page 17.  
1. Minimum of twelve 12” (30.5 cm) above the roof or twelve 12”  
(30.5 cm) above the anticipated snow level. Provide proper support  
FIGURE 24.  
The vent terminal should be kept as close as possible to the outside wall,  
but you need to allow at least 1.5” (3.8 cm) of pipe past the wall, for the  
wall ange and vent terminal to mount on the pipe.  
Before the vent terminal is installed, caulk (not supplied) around the  
pipe on the exterior wall and install the optional wall ange. The ange  
can be held to the outside wall by placing some of the caulking on the  
back of the ange. The wall ange is supplied for decorative purposes  
only and is not a requirement for the vent termination (if not needed by  
the installer).  
VERTICAL VENT THROUGH ROOF  
This unit is approved for venting through the roof with the type vent  
terminal that is included with the unit. Aproper ashing or “BOOT” should  
be used to seal the pipe where it exits the roof.  
FIGURE 25.  
2. 4’ (1.2 m) from or 1’ (0.3 m) above any gable, dormer, or other roof  
structure with access to interior of building (i.e.-vent, window etc.).  
The total vent system should not exceed that which is specied, see  
VENTING AND INSTALLATION, page 17.  
3. 3’ (0.9 m) above any forced air inlet located within 10’ (3.0 m).  
All of the pipe should be secured as per the instructions in the instructions  
in the VENTING AND INSTALLATION, page 17.  
20  
solvated with tetrahydrofuran (THF). Small quantities of dimethyl  
formamide (DMF) may be included to act as a retarding agent to extend  
curing time. Select the proper cement; Schedule 40 cement should be  
used for Schedule 40 pipe. Never use all-purpose cements, commercial  
glues and adhesives or ABS cement to join PVC or CPVC pipe and  
ttings.  
VENT PIPE PREPARATION  
1. INITIAL PREPARATION  
A. Make sure the solvent cement you are planning to use is  
designed for the specic application you are attempting.  
B. Know the physical and chemical characteristics and limitations  
of the PVC and CPVC piping materials that you are about to  
use.  
C. Know the reputation of your manufacturer and their products.  
D. Know your own qualications or those of your contractor. The  
solvent welding technique of joining PVC and CPVC pipe is a  
specialized skill just as any other pipe tting technique.  
APPLICATORS  
E. Closely supervise the installation and inspect the nished  
job before start-up.  
Select a suitable pure bristle type paint brush. Use a proper width brush  
or roller to apply the primer and cement (see chart below). Speedy  
application of cement is important due to its fast drying characteristics.  
IMPORTANT NOTE: A dauber type applicator should only be used on  
pipe sizes 2” and below. For larger diameter pipe, a brush or roller must  
be used.  
F. Contact the manufacturer, supplier, or competent consulting  
agency if you have any questions about the application or  
installation of PVC and CPVC pipe.  
G. Take the time and effort to do a professional job. Shortcuts will  
only cause you problems and delays in start-up. By far, the  
majority of failures in PVC and CPVC systems are the result of  
shortcuts and/or improper joining techniques.  
RECOMMENDED BRUSH* SIZE FOR PRIMER  
AND CEMENT APPLICATIONS  
2. SELECTION OF MATERIALS  
Nominal Pipe  
Size Brush Width  
(INS.)  
(IPS)  
Cutting Device - Saw or Pipe Cutter  
Deburring Tool, Knife, File, or Beveling Machine (2” and above)  
Brush - Pure Bristle  
2
3
1-1/2  
1-1/2 - 2-1/2  
*USE ONLY NATURAL BRISTLE  
3. MAKING THE JOINT  
A. Cutting  
Rag - Cotton (Not Synthetic)  
Primer and Cleaner  
Solvent Cement - PVC for PVC Components and CPVC for CPVC  
Components  
Pipe must be squarely cut to allow for the proper interfacing of the  
pipe end and the tting socket bottom. This can be accomplished  
with a miter box saw or wheel type cutter. Wheel type cutters are not  
generally recommended for larger diameters since they tend to are  
the corner of the pipe end. If this type of cutter is used, the are on  
the end must be completely removed.  
Containers - Metal or Glass to hold Primer and Cement. Select  
the type of PVC or CPVC materials to be used on the basis of their  
application with respect to chemical resistance, pressure rating,  
temperature characteristics, etc.  
NOTE: Power saws should be specically designed to cut plastic pipe.  
Insertion Tool - Helpful for larger diameter pipe and ttings 6 inches  
(15.2 cm) and above.  
PRIMER  
It is recommended that Tetrahydrofuran (THF) be used to prepare the  
surfaces of pipe and ttings for solvent welding. Do not use water, rags,  
gasoline or any other substitutes for cleaning PVC or CPVC surfaces.  
A chemical cleaner such as MEK may be used.  
CEMENT  
The cement should be a bodied cement of approximately 500 to 1600  
centipoise viscosity containing 10-20% (by weight) virgin PVC material  
STEP A  
21  
B. Deburring  
Use a knife, plastic pipe deburring tool, or le to remove burrs from  
the end of small diameter pipe. Be sure to remove all burrs from  
around the inside as well as the outside of the pipe. A slight chamfer  
(bevel) of about 10°-15° should be added to the end to permit easier  
insertion of the pipe into the end of the tting. Failure to chamfer the  
edge of the pipe may remove cement from the tting socket, causing  
the joint to leak.  
STEP E  
F. Joint assembly  
Working quickly, insert the pipe into the tting socket bottom and  
give the pipe or tting a 1/4 turn to evenly distribute the cement. Do  
not continue to rotate the pipe after it has hit the bottom of the tting  
socket. A good joint will have sufcient cement to make a bead all  
the way around the outside of the tting hub. The tting will have a  
tendency to slide back while the cement is still wet so hold the joint  
together for about 15 seconds.  
STEP B  
C. Test dry t of the joint  
Tapered tting sockets are designed so that an interfaced t should  
occur when the pipe is inserted about 1/3 to 2/3 of the way into the  
socket. Occasionally, when pipe tting dimensions are at the tolerance  
extremes, it will be possible to fully insert dry pipe to the bottom of  
the tting socket. When this happens, a sufcient quantity of cement  
must be applied to the joint to ll the gap between the pipe and tting.  
The gap must be lled to obtain a strong, leak-free joint.  
D. Inspection, cleaning, priming  
Visually inspect the inside of the pipe and tting sockets and remove  
all dirt, grease or moisture with a clean dry rag. If wiping fails to clean  
the surfaces, a chemical cleaner must be used. Check for possible  
damage such as splits or cracks and replace if necessary.  
STEP F  
Depth-of-entry  
Marking the depth of entry is a way to check if the pipe has reached  
the bottom of the tting socket in Step F. Measure the tting depth  
and mark this distance on the pipe O.D. You may want to add several  
inches to the distance and make a second mark as the primer and  
cement will most likely destroy your rst one.  
G. Cleanup and joint movement  
Remove all excess cement from around the pipe and tting with a  
dry cotton rag. This must be done while the cement is still soft.  
The joint should not be disturbed immediately after the cementing  
procedure, and sufcient time should be allowed for proper curing of  
the joint. Exact drying time is difcult to predict because it depends  
on variables such as temperature, humidity and cement integrity. For  
more specic information, you should contact your solvent cement  
manufacturer.  
Apply primer to the surface of the pipe and tting socket with a natural  
bristle brush. This process softens and prepares the PVC or CPVC  
for the solvent cementing step. Move quickly and without hesitation  
to the cementing procedure while the surfaces are still wet with  
primer.  
E. Application of solvent cement  
• Apply the solvent cement evenly and quickly around the outside  
of the pipe at a width a little greater than the depth of the tting  
socket.  
• Apply a light coat of cement evenly around the inside of the  
tting socket. Avoid puddling.  
• Apply a second coat of cement to the pipe end.  
STEP G  
22  
OPERATING INSTRUCTIONS  
FOR YOUR SAFETY READ BEFORE LIGHTING  
WARNING: If you do not follow these instructions exactly, a fire or  
explosion may result causing property damage, personal injury  
or loss of life.  
FLAMMABLE  
BEFORE OPERATING: ENTIRE SYSTEM MUST BE FILLED WITH WATER AND AIR PURGED FROM ALL LINES.  
This appliance does not have a pilot. It is equipped with  
an ignitiion device which automatically lights the  
burner. Do not try to light the burner by hand.  
BEFORE OPERATING smell all around the appliance  
area for gas. Be sure to smell next to the floor because  
some gas is heavier than air and will settle on the floor.  
A.  
If you cannot reach your gas supplier, call the  
fire department.  
Use only your hand to push in the gas control but-  
tons. Never use tools. If the control buttons will not  
push in, don't try to repair them, call a qualified ser-  
vice technician. Force or attempted repair may  
result in a fire or explosion.  
C.  
D.  
B.  
WHAT TO DO IF YOU SMELL GAS:  
Do not try to light any appliance.  
Do not use this appliance if any part has been  
under water. Immediately contact a qualified  
installer or service agency to replace a flooded  
water heater. Do not attempt to repair the unit.  
It must be replaced!  
Do not touch any electric switch;  
do not use any phone in your building.  
Immediately call your gas supplier from a neighbor's  
phone. Follow the gas supplier's instructions.  
OPERATING INSTRUCTIONS  
5.  
This appliance is equipped with a device  
which automatically lights the burner.  
DO NOT TRY TO LIGHT THE BURNER BY HAND.  
VACATION  
A
B
C
VERY  
HOT  
WARM  
Wait five (5) minutes to  
If you then smell gas,  
clear out any gas.  
STOP! Follow "B" in  
6.  
COOLER  
HOTTER  
the safety information above on this label. If you  
don't smell gas, go to the next step.  
7.  
Turn on all electrical power to the appliance.  
--------------  
----------------------- ---------------------- ------------------------------  
8. Set the ON/OFF switch on the control box to the  
------------------------------------------------------  
* -----------------------------------------------------------------------  
* ----------------------------------------------------------  
--------------------------------------------------------------------------------------  
--------------------------------------------------------------------------------------  
* ------------------------------------------------------------------------  
-----------------------------------------------------------------------------------------------  
------------------------------------------------------------------------------------------------------------------------  
--------------------------------------------------------  
"ON" postition.  
Set the thermostat to the desired setting by first  
9.  
pressing the COOLER  
and HOTTER  
but-  
tons together and holding for 1 second. Then press  
the HOTTER button  
10.WATER TEMPERATURE ADJUSTMENT is  
1.  
2.  
3.  
STOP! Read the safety information above  
on this label.  
approximately 120oF.  
CAUTION: Hotter water increases the risk of  
scald injury. Consult the instruction  
manual before changing temperature.  
If the appliance will not operate, follow the instruc-  
tions "TO TURN OFF GAS TO APPLIANCE" and  
call your technician or gas supplier.  
Set the ON/OFF switch on the control box to the  
"ON" position.  
Set the thermostat to the lowest setting by first  
pressing the COOLER  
and HOTTER  
but-  
11.  
tons together and holding for 1 second. Then press  
the COOLER button  
light appears.  
until the Warm indicator  
WARNING: TURN OFF ALL ELECTRIC  
POWER BEFORE SERVICING.  
4.  
1.  
Set the ON/OFF switch on the control box to the  
"OFF" position.  
TO TURN OFF GAS TO APPLIANCE  
Set the thermostat to the lowest setting by first  
pressing the COOLER and HOTTER but-  
2. Set the ON/OFF switch on the control box to the  
"OFF" postition.  
Turn off all electrical power to the appliance if  
service is to be performed.  
tons together and holding for 1 second. Then press  
3.  
the COOLER button  
light appears.  
until the Warm indicator  
23  
1. “Wake Up” the temperature indicators by holding down both “COOLER”  
and “HOTTER” temperature adjustment buttons at the same time  
TEMPERATURE REGULATION  
Due to the nature of the typical gas water heater, the water temperature  
in certain situations may vary up to 30°F (16.7°C) higher or lower at the  
point of use such as, bathtubs, showers, sink, etc.  
for one second, see Figure 26. One or two of the temperature indicators  
will light up. These indicators will only remain on for 30 seconds if no  
further buttons are pressed. After 30 seconds the control will go back  
to “Sleep” mode.  
It is recommended that lower water temperatures be used to avoid the  
risk of scalding. It is further recommended, in all cases, that the water  
temperature be set for the lowest temperature which satises your hot  
water needs. This will also provide the most energy efcient operation  
of the water heater.  
2. Release both of the temperature adjustment buttons.  
a. To decrease the temperature press and release the “COOLER”  
button until the desired setting is reached.  
b. To increase the temperature press and release the “HOTTER”  
button until the desired setting is reached.  
NOTE: Holding down the button will not continue to lower or raise the  
temperature setting. The button must be pressed and released for each  
temperature change desired.  
Should overheating occur or the gas supply fail to shut off, turn off the  
manual gas control valve to the appliance.  
HOT WATER CAN SCALD: Water heaters are intended to produce hot  
water. Water heated to a temperature which will satisfy space heating,  
clothes washing, dish washing, and other sanitizing needs can scald  
and permanently injure you upon contact. Some people are more likely  
to be permanently injured by hot water than others. These include  
the elderly, children, the inrm, or physically/mentally handicapped. If  
anyone using hot water in your home ts into one of these groups or if  
there is a local code or state law requiring a certain temperature water  
at the hot water tap, then you must take special precautions. In addition  
to using the lowest possible temperature setting that satises your hot  
water needs, a means such as a mixing valve, should be used at the hot  
water taps used by these people or at the water heater. Mixing valves  
are available at plumbing supply or hardware stores, see Figure 15.  
Follow manufacturer’s instructions for installation of the valves. Before  
changing the factory setting on the thermostat, read the “Temperature  
Regulation” section in this manual, see Figure 26.  
Never allow small children to use a hot water tap, or to draw their own  
bath water. Never leave a child or handicapped person unattended in  
a bathtub or shower.  
The water heater should be located in an area where the general public  
does not have access.  
Time to Produce  
The water temperature setting was factory set at the lowest temperature;  
Pressing the “COOLER”  
button decreases temperature and pressing  
the “HOTTER” button increases the temperature.  
Display  
A B C  
2nd and 3rd Degree  
Burns on Adult Skin  
About 1/2 seconds  
About 1-1/2 seconds  
Less than 5 seconds  
About 30 seconds  
More than 5 minutes  
- - - - - - - - - - - - -  
Setting the water heater temperature at 120°F (49°C) (Approx. “ ” mark  
on temperature setting of gas valve) will reduce the risk of scalds. Some  
states require settings at specic lower temperatures.  
Temperature Setting  
C-Flashing = approx. 160°F (71°C)  
C = approx. 150°F (66°C)  
B = approx. 140°F (60°C)  
A = approx. 130°F (54°C)  
= approx. 120°F (49°C)  
To avoid any unintentional changes in water temperature settings, the  
control has a tamper resistant feature for changing the temperature  
setting. To change the temperature setting follow these instructions:  
WARM = approx. 80°F (27°C)  
FIGURE 26.  
24  
FOR YOUR INFORMATION  
START UP CONDITIONS  
Thermal Expansion Tank Specications  
Tank  
Capacity  
Dimensions  
in Inches  
Pipe  
Fitting  
CONDENSATE  
Model  
Whenever the water heater is lled with cold water, some condensate  
will form while the burner is on. A water heater may appear to be leaking  
when in fact the water is condensate. This usually happens when:  
Number  
In Gallons Diameter  
Length  
On Tank  
153.331020  
153.331050  
2
5
8 (203 mm) 12-3/4 (323 mm) 3/4” Male  
11 (279 mm) 14-3/4 (375 mm) 3/4” Male  
a. A new water heater is lled with cold water for the rst time.  
b. Burning gas produces water vapor in water heaters, particularly high  
efciency models where ue temperatures are lower.  
c. Large amounts of hot water are used in a short time and the rell  
water in the tank is very cold.  
Expansion Tank Sizing Chart  
Inlet*  
Water  
Pressure  
40psi  
Water Heater Capacity (Gallons)  
Moisture from the products of combustion condense on the cooler tank  
surfaces and form drops of water which may fall onto the burner or other  
hot surfaces to produce a “sizzling” or “frying” noise.  
30  
2
40  
2
50  
2
66  
5
80  
5
Expansion  
Tank  
50psi  
2
2
2
5
5
Because of the suddenness and amount of water, condensate water  
may be diagnosed as a “tank leak”. After the water in the tank warms  
up (about 1-2 hours), the condition should disappear.  
Capacity  
Needed  
60psi  
2
2
5
5
5
70psi  
2
2
5
5
5
80psi  
2
5
5
5
5
Do not assume the water heater is leaking until there has been enough  
time for the water in the tank to warm up.  
*Highest recorded inlet water pressure in a 24 hour period or regulated  
water pressure.  
An undersized water heater will cause more condensation. The water  
heater must be sized properly to meet the family’s demands for hot water  
including dishwashers, washing machines and shower heads.  
NOTE: Expansion tanks are pre-charged with a 40 psi air charge. If  
the inlet water pressure is higher than 40 psi, the expansion tank’s  
air pressure must be adjusted to match that pressure, but must not  
be higher than 80 psi.  
Excessive condensate may be noticed during the winter and early spring  
months when incoming water temperatures are at their lowest.  
Good venting is essential for a gas red water heater to operate properly  
as well as to carry away products of combustion and water vapor.  
SMOKE/ODOR  
It is not uncommon to experience a small amount of smoke and odor  
during the initial start-up. This is due to burning off of oil from metal parts,  
and will disappear in a short while.  
THERMAL EXPANSION  
Water supply systems may, because of such events as high line  
pressure, frequent cut-offs, the effects of water hammer among others,  
have installed devices such as pressure reducing valves, check valves,  
back ow preventers, etc. to control these types of problems. When  
these devices are not equipped with an internal by-pass, and no other  
measures are taken, the devices cause the water system to be closed.  
As water is heated, it expands (thermal expansion) and closed systems  
do not allow for the expansion of heated water.  
The water within the water tank expands as it is heated and increases  
the pressure of the water system. If the relieving point of the water  
heater’s temperature-pressure relief valve is reached, the valve will  
release the excess pressure. The temperature-pressure relief valve  
is not intended for the constant relief of thermal expansion. This is  
an unacceptable condition and must be corrected. It is recommended  
that any devices installed which could create a closed system have a  
by-pass and/or the system have an expansion tank or device to relieve  
the pressure built by thermal expansion in the water system. Expansion  
tanks are available through Sears stores and Sears Service Centers.  
Contact Sears Service Center for assistance in controlling these  
situations, see Figure 27.  
FIGURE 27.  
25  
STRANGE SOUNDS  
Possible noises due to expansion and contraction of some metal parts  
during periods of heat-up and cool-down do not necessarily represent  
harmful or dangerous conditions.  
“AIR” IN HOT WATER FAUCETS  
Condensation causes sizzling and popping within the burner area during  
heating and cooling periods and should be considered normal. See  
“Condensate” in this section.  
OPERATIONAL CONDITIONS  
SMELLY WATER  
In each water heater there is installed at least one anode rod (see parts  
section) for corrosion protection of the tank. Certain water conditions  
will cause a reaction between this rod and the water. The most common  
complaint associated with the anode rod is one of a “rotten egg smell”  
in the hot water. The smell is a result of four factors which must all be  
present for the odor to develop:  
HYDROGEN GAS: Hydrogen gas can be produced in a hot water  
system that has not been used for a long period of time (generally  
two weeks or more). Hydrogen gas is extremely ammable and  
explosive. To prevent the possibility of injury under these conditions,  
we recommend the hot water faucet, located farthest away, be  
opened for several minutes before any electrical appliances  
which are connected to the hot water system are used (such as a  
dishwasher or washing machine). If hydrogen gas is present, there  
will probably be an unusual sound similar to air escaping through the  
pipe as the hot water faucet is opened. There must be no smoking  
or open ame near the faucet at the time it is open.  
a. A concentration of sulfate in the supply water.  
b. Little or no dissolved oxygen in the water.  
c. A sulfate reducing bacteria which has accumulated within the water  
heater (this harmless bacteria is nontoxic to humans).  
d. An excess of active hydrogen in the tank. This is caused by the  
corrosion protective action of the anode.  
Smelly water may be eliminated or reduced in some water heater models  
by replacing the anode(s) with one of less active material, and then  
chlorinating the water heater tank and all water lines. Contact Sears  
Service Center for further information concerning Anode Replacement  
Kit #9001453 and this chlorination treatment. Anode replacement and  
chlorination of the tank are not covered by the water heater’s limited  
warranty.  
HIGH WATER TEMPERATURE SHUT OFF SYSTEM  
This water heater is equipped with an automatic gas shut-off system.  
This system works when high water temperatures are present. Turn  
“OFF” the entire gas supply to the water heater. The high temperature  
shut-off is built into the gas control valve. It is non-resettable. If the  
high temperature shut-off activates, the gas control valve must be  
replaced. Contact your gas supplier or Sears Service Center.  
If the smelly water persists after the anode replacement and chlorination  
treatment, we can only suggest that chlorination or aeration of the water  
supply be considered to eliminate the water problem.  
Do not remove the anode leaving the tank unprotected. By doing  
so, all warranty on the water heater tank is voided.  
SERVICE AND ADJUSTMENT  
2. Damage or deterioration which could cause improper venting or  
leakage of combustion products.  
VENTING SYSTEM INSPECTION  
Be sure the vent piping is properly connected to prevent escape of  
dangerous ue gasses which could cause deadly asphyxiation.  
Obstructions and deteriorated vent systems may present serious health  
risk or asphyxiation.  
Chemical vapor corrosion of the ue and vent system may occur if air  
for combustion contains certain chemical vapors. Spray can propellants,  
cleaning solvents, refrigerator and air conditioner refrigerants, swimming  
pool chemicals, calcium and sodium chloride, waxes, bleach and process  
chemicals are typical compounds which are potentially corrosive.  
If after inspection of the vent system you found sooting or deterioration,  
something is wrong. Call the local gas utility to correct the problem and  
clean or replace the ue and venting before resuming operation of the  
water heater.  
BURNER OPERATION AND INSPECTION  
Flood damage to a water heater may not be readily visible or immediately  
detectable. However, over a period of time a ooded water heater will  
create dangerous conditions which can cause DEATH, SERIOUS  
BODILY INJURY, OR PROPERTY DAMAGE. Contact Sears Service  
Center to replace a ooded water heater. Do not attempt to repair the  
unit! It must be replaced!  
At least once a year a visual inspection should be made of the venting  
system. You should look for:  
1. Obstructions which could cause improper venting. The combustion  
and ventilation air ow must not be obstructed.  
26  
At least once a year a visual inspection should be made of the main burner  
and the hot surface igniter assembly for proper ame characteristics  
and ignition sequences. This can be done by removing the Outer Door  
and viewing the main burner operation through the Viewport on the  
Inner Door, see Figure 1. The main burner should provide complete  
combustion of gas, ignite rapidly, give reasonably quiet operation, and  
cause no excessive ame lifting from the burner ports. If the proper ame  
characteristics are not evident (see Figure 28), make sure that the ow  
of combustion and ventilation air is not blocked on the Air Intake Screen  
at the base of the water heater (see Figure 29), the Lint screen on the  
blower assembly (see Figure 1), and in the venting system.  
FIGURE 29.  
AT LEAST ONCE EVERY SIX MONTHS A VISUAL INSPECTION  
SHOULD BE MADE OF THE AIR INTAKE SCREENS ON THE BASE  
OF THE WATER HEATER AND THE BLOWER ASSEMBLY. CLEAN  
IF LINT ACCUMULATIONS ARE NOTICED.  
You should also check for sooting. Soot is not normal and will impair  
proper combustion. A visual inspection of the main burner and HSI  
igniter assembly should also be done at least once a year, see  
Figure 28.  
Soot build-up indicates a problem that requires correction before further  
use. Turn “OFF” gas to water heater and leave off until repairs are made,  
because failure to correct the cause of the sooting can result in a re  
causing death, serious injury, or property damage.  
INSTALLED IN SUITABLE AREA: To insure sufcient ventilation and  
combustion air supply, proper clearances from the water heater must  
be maintained. See “Facts to Consider About the Location” section.  
Combustible materials such as clothing, cleaning materials, or ammable  
liquids, etc. must not be placed against or adjacent to the water heater  
which can cause a re.  
ANODE ROD INSPECTION  
FIGURE 28.  
BURNER CLEANING  
In the event your burner or burner air openings require cleaning, turn  
the blower switch to the “OFF” position and allow the burner to cool. Call  
Sears Service Center to remove and clean the burner and correct the  
problem that required the burner to be cleaned.  
The anode rod is used to protect the tank from corrosion. Most hot water  
tanks are equipped with an anode rod. The submerged rod sacrices  
itself to protect the tank. Instead of corroding the tank, water ions attack  
and eat away the anode rod. This does not affect the water’s taste  
or color. The rod must be maintained to keep the tank in operating  
condition.  
HOUSEKEEPING  
Vacuum around base of water heater for dust, dirt, and lint on a regular basis.  
Anode deterioration depends on water conductivity, not necessarily water  
condition.Acorroded or pitted anode rod indicates high water conductivity  
and should be checked and/or replaced more often than an anode rod  
that appears to be intact. Replacement of a depleted anode rod can  
extend the life of your water heater. Inspection should be conducted by  
a qualied technician, and at a minimum should be checked annually  
after the warranty period.  
TEMPERATURE-PRESSURE  
RELIEF VALVE OPERATION  
This water heater unit is supplied with a plastic Air Intake Screen that  
will lter and prevent lint build-up on the bottom of the ame arrestor of  
this heater. To prevent the lint build-up on the arrestor, the lint screen  
must be installed on the Base Pan with the “arrows” pointing upwards as  
shown in Figure 29. If the Air Intake Screen is missing from this heater,  
please contact Sears Service Center for a replacement part.  
The temperature-pressure relief valve must be manually operated at  
least once a year.  
27  
5. OPEN the water heater drain valve to allow for tank draining.  
NOTE: If the water heater is going to be shut down and drained  
for an extended period, the drain valve should be left open with  
hose connected allowing water to terminate to an adequate  
drain.  
6. CLOSE the drain valve.  
7. Follow instructions in the “Filling The Water Heater” section.  
8. Follow the lighting instructions on the label or see page 22 under  
“Operating Instructions” to restart the water heater.  
FIGURE 30.  
When checking the temperature-pressure relief valve operation, make  
sure that (1) no one is in front of or around the outlet of the temperature-  
pressure relief valve discharge line, and (2) that the water discharge will  
not cause any property damage, as the water may be extremely hot,  
see Figure 30.  
DRAIN VALVE WASHER REPLACEMENT  
(See Figure 31)  
1. Turn “OFF” gas supply to water heater.  
2. Follow “Draining” instructions.  
If after manually operating the valve, it fails to completely reset and  
continues to release water, immediately close the cold water inlet  
to the water heater, follow the draining instructions, and replace the  
temperature-pressure relief valve with a new one.  
3. Turning counterclockwise (  
screw handle.  
), remove the hex cap below the  
If the temperature-pressure relief valve on the appliance weeps or  
discharges periodically, this may be due to thermal expansion. You  
may have a check valve installed in the water line or a water meter  
with a check valve. Consult your local water supplier or Sears Service  
Center for further information. Do not plug the temperature-pressure  
relief valve.  
4. Remove the washer and put the new one in place.  
5. Screw the handle and cap assembly back into the drain valve and  
retighten using a wrench. DO NOT OVER TIGHTEN.  
6. Follow instructions in the “Filling The Water Heater” section.  
7. Check for leaks.  
DRAINING  
8. Follow the lighting instructions in the “Operating Instructions” section  
to restart the water heater.  
The water heater should be drained if being shut down during freezing  
temperatures. Also periodic draining and cleaning of sediment from the  
tank may be necessary.  
FIGURE 31.  
1. Set the blower switch to the “OFF” position.  
SERVICE  
2. CLOSE the cold water inlet valve to the water heater.  
3. OPEN a nearby hot water faucet and leave open to allow for  
draining.  
If a condition persists or you are uncertain about the operation of  
the water heater contact Sears Service Center at 1-800-MY-HOME®  
(1-800-469-4663).  
4. Connect a hose to the drain valve and terminate to an adequate  
drain.  
28  
LEAKAGE CHECKPOINTS  
Use this guide to check a “Leaking” water heater. Many suspected  
“Leakers” are not leaking tanks. Often the source of the water can be  
found and corrected.  
Read this manual rst. Then before checking the water heater make  
sure the gas supply has been turned “OFF”, and never turn the gas “ON”  
before the tank is completely full of water.  
If you are not thoroughly familiar with gas codes, your water heater,  
and safety practices, contact Sears Service Center to check the water  
heater.  
Never use this water heater unless it is completely lled with water. To  
prevent damage to the tank, the tank must be lled with water. Water  
must ow from the hot water faucet before turning “ON” gas to the water  
heater.  
A. Water at the blower assembly is water vapor which has condensed  
out of the combustion products. This is caused by a problem in the  
vent. Contact the gas utility.  
B. *Condensation may be seen on pipes in humid weather or pipe  
connections may be leaking.  
C. *The anode rod tting may be leaking (anode is located under the  
Blower Assembly).  
D. Small amounts of water from temperature-pressure relief valve may  
be due to thermal expansion or high water pressure in your area.  
E. *The temperature-pressure relief valve may be leaking at the tank  
tting.  
F. Water from a drain valve may be due to the valve being slightly  
opened.  
G. *The drain valve may be leaking at the tank tting.  
H. Combustion products contain water vapor which can condense on  
the cooler surfaces of the tank. Droplets form and drip onto the  
burner or run on the oor. This is common at the time of start-up  
after installation and when incoming water is cold.  
I. Water in the water heater bottom or on the oor may be from  
condensation, loose connections, or the relief valve. DO NOT replace  
the water heater until a full inspection of all possible water sources  
is made and necessary corrective steps taken.  
Leakage from other appliances, water lines, or ground seepage should  
also be checked.  
*
To check where threaded portion enters tank, insert cotton swab  
between jacket opening and tting. If cotton is wet, follow “Draining”  
instructions in the “Periodic Maintenance” section and then remove  
tting. Put pipe dope or teon tape on the threads and replace.  
Then follow “Filling the Water Heater” instructions in the “Installation  
Instructions” section.  
29  
TROUBLESHOOTING GUIDELINES  
These guidelines should be used by a qualied service agent. Call Sears Service at 1-800-4-MY-HOME® (1-800-469-4663)  
for assistance. Inform the associate that this is a “Flammable Vapor Ignition Resistant” Product.  
#
1
LED STATUS  
PROBLEM  
SOLUTION  
1 Ensure the wall outlet (power supply) is properly  
grounded.  
The gas control valve has sensed  
inadequate or no earth ground.  
2 Ensure all ground connections/wires on the water  
heater are securely connected.  
1 Ensure the wall outlet/power supply is properly wired.  
The gas control valve has sensed  
reversed polarity in the 120 VAC  
power supply.  
2
3
2 Ensure all internal 120 VAC wiring connections and  
wiring harness have no reversed wires. 120 VAC "hot"  
wire must connect to the on/off switch.  
Pressure switch circuit remaining  
closed for more than 5 seconds  
after heating cycle begins.  
1 Ensure air pressure switch circuit wiring is correct and  
the air pressure switch is not jumpered.  
Blower may not start in this  
condition.  
2 Replace the air pressure switch.  
1 Ensure the air pressure switch sensing tube is properly  
connected at both ends and is not kinked or damaged.  
2 Ensure the correct size of vent and intake air pipe (direct  
vent products) was used per the installation instructions  
in the manual that came with the water heater.  
Pressure switch circuit remains  
open longer than 5 seconds after  
the blower is energized.  
4
3 Ensure maximum number of elbows or maximum  
equivalent feet of vent or intake air pipe has not been  
exceeded per the installation instructions in the manual  
that came with the water heater.  
Blower may run continuously in  
this condition.  
4 Ensure there are no obstructions in the vent or intake  
air pipe.  
1 Check wiring to the hot surface igniter assembly -  
replace igniter assembly if wiring is damaged or worn.  
2 Check resistance of the igniter at igniter assembly plug  
- should be between 11 and 18 ohms - replace igniter if  
open or shorted.  
The gas control valve has detected  
an open igniter circuit.  
5
3 Check igniter assembly plug and the socket on the  
bottom of the gas control valve for good connection.  
4 Replace igniter assembly if the plug is worn or  
damaged.  
5 Replace the gas control valve if the igniter assembly  
socket on the bottom of the control is worn or damaged.  
1 Gas supply is turned off - pressure is too low.  
Ignition/ame failure.  
2 Ensure the ame sensor is clean - use ne steel wool  
to clean the ame sensor.  
The gas control valve has reached  
the maximum number or retries (3)  
for ignition and is currently locked  
out for one hour.  
3 Manifold gas pressure to the burner is too low.  
6
4 Check igniter assembly plug and the socket on the bottom  
of the gas control valve for good connection. Replace  
igniter assembly if the plug is worn or damaged replace  
the gas control valve if socket is worn or damaged.  
Cycle the power to the water heater  
off and on to reset.  
5 Replace igniter assembly.  
30  
TROUBLESHOOTING GUIDELINES  
These guidelines should be used by a qualied service agent. Call Sears Service at 1-800-4-MY-HOME® (1-800-469-4663)  
for assistance. Inform the associate that this is a “Flammable Vapor Ignition Resistant” Product.  
#
LED STATUS  
PROBLEM  
SOLUTION  
7
8
9
1 Turn the power off for 10-20 seconds then on again to  
clear these error codes.  
The gas control valve has detected  
a problem with the gas valve driver  
circuit, internal microprocessor, or  
other internal circuits.  
2 If any of these error codes persist or cannot be cleared  
- replace the gas control valve.  
1 Turn the power off for 10-20 seconds then on again to  
clear these error codes.  
The gas control valve has sensed  
main burner ame out of proper  
sequence.  
10  
11  
12  
13  
2 Replace the gas control valve if this error code persists.  
The gas control valve has detected  
excessive water temperature in the  
tank and has activated the ECO  
(energy cut off) high temperature  
limit.  
1 Turn the power off for 10-20 seconds then on again to  
clear these error codes.  
2 Replace the gas control valve if the error code persists.  
1 Press and release both temperature adjust buttons  
several times - cycle water heater power off and on.  
The gas control valve has detected  
that one or both of the temperature  
adjust buttons are stuck.  
2 Replace the gas control valve if the error code persists.  
The gas control valve has detected  
the water temperature sensor  
(located in the control valve's  
immersion probe) is either open or  
shorted.  
1 Turn the power off for 10-20 seconds then on again to  
clear these error codes.  
2 Replace the gas control valve if the error code persists.  
1 Ensure all FV sensor wiring is correct and the igniter  
assembly plug and socket connections on the bottom  
of the gas control valve are making good contact.  
The gas control valve has detected  
the FV (ammable vapor) sensor is  
either open or shorted.  
14  
2 Replace the FV sensor.  
1 Do not touch any electrical switch, do not use any  
phone in your building, and do not try to light any  
appliance.  
2 Smell around the water heater to ensure there are no  
gas leaks at the gas control valve, in the supply gas  
line(s), or any other type of ammable vapor(s) in the  
area.  
The gas control valve has detected  
the presence of ammable vapors  
from the FV (ammable vapor)  
sensor.  
15  
3 Carefully inspect the area surrounding the water heater  
for any substances such as gasoline, paint, paint  
thinners, varnish, or cleaners that could emit ammable  
vapors. Remove anything that can potentially emit  
ammable vapors from the area and store it properly in  
a different location.  
4 Call the technical information support phone number  
shown on the water heater labeling for further  
assistance.  
1 On models equipped with a dilution air intake screen on  
the blower assembly - check/clean this screen.  
The gas control valve has detected  
the air pressure switch circuit is  
opening repeatedly during one  
heating cycle.  
2 On models equipped with a combustion air intake  
screen on the base ring (bottom) of the water heater -  
check/clean the screen.  
16  
LDO (Lint, Dust, and Oil) lockout  
condition.  
3 Ensure intake air screen(s) on models so equipped are  
not obstructed.  
31  
TROUBLESHOOTING GUIDELINES  
These guidelines should be utilized by a qualied service agent. When calling for service notify the service agent  
that this is a “Flammable Vapor Ignition Resistant” Product.  
32  
REPAIR PARTS LIST  
THE ECONOMIZER™ 6 GAS WATER HEATER  
MODEL NO’S  
40 Gallon Natural Gas  
153.332040  
153.332050  
153.332060  
153.332070  
50 Gallon Natural Gas  
40 Gallon Propane (L.P.)  
50 Gallon Propane (L.P.)  
BURNER ASSEMBLY  
OUTER DOOR  
(ALTERNATE)  
1
16  
Model Numbers  
153.332050  
Key No. Part Description  
153.332040  
9005938  
9003385  
9005950(#32)  
9005951  
9005958  
9003400  
9003401  
9005959  
9003445  
9004316  
9003406  
9003447  
9005962  
9002402  
9001584  
9005966  
9003972  
9000071  
9003414  
9002846  
9002847  
9002848  
9002850  
185249-002  
9005967  
9005968  
9005969  
9003977  
185110-000  
153.332060  
9005943  
9005948  
9003495(#50)  
9005954  
9005958  
9003398  
9003401  
9005959  
9003445  
9004316  
9003406  
9003447  
9005963  
9002402  
9001584  
9005966  
9003972  
9000071  
9003414  
9002846  
9002847  
9002848  
9002850  
185249-002  
9005967  
9005968  
9005969  
9003977  
185110-000  
153.332070  
9005944  
9005948  
9003495(#50)  
9005955  
9005958  
9003398  
9003401  
9005959  
9003445  
9004316  
9003406  
9002547  
9005963  
9002402  
9001584  
9005966  
9003891  
9000071  
9003414  
9002846  
9002847  
9002848  
9002850  
185249-002  
9005967  
9005968  
9005969  
9003977  
185110-000  
1
2
Burner Assembly  
Burner Head  
9005939  
9003385  
9005950(#32)  
9005952  
9005958  
9003400  
9003401  
9005959  
9003445  
9004316  
9003406  
9002547  
9005962  
9002402  
9001584  
9005966  
9003891  
9000071  
9003414  
9002846  
9002847  
9002848  
9002850  
185249-002  
9005967  
9005968  
9005969  
9003977  
185110-000  
3
Burner Orice  
4
Burner Tube  
5
6
HSI Ignition Assembly  
Inner Door  
7
8
Inner Door Gasket  
Flue Bafe  
9
Flue Restrictor  
10  
11  
12  
13  
14  
15  
16  
17  
18  
19  
20  
Blower Assembly  
Air Intake Screen - Base Pan  
Inlet Tube  
Gas Control Valve  
Drain Valve  
Drain Valve Washer  
Outer Door  
Anode Rod  
Temperature-Pressure Relief Valve  
Viewport Assembly  
20” Dia. Drain Pan w/Side Drain (optional)  
22” Dia. Drain Pan w/Side Drain (optional)  
24” Dia. Drain Pan w/Side Drain (optional)  
28” Dia. Drain Pan w/Side Drain (optional)  
Instruction Manual  
*21  
22  
23  
Air Intake Screen - Blower Assembly  
FV Sensor  
24  
FV Sensor Bracket  
25  
26  
Nipple (cold inlet or hot outlet)  
Blower Assembly Pressure Switch  
* Not shown  
Now that you have purchased your gas water heater, should  
a need ever exist for repair parts or service, simply contact  
any Sears Service Center or call 1-800-4-MY-HOME®  
(1-800-469-4663).  
WHEN ORDERING REPAIR PARTS,ALWAYS GIVE THE FOLLOWING  
INFORMATION:  
MODEL NUMBER  
TYPE GAS (NATURAL OR PROPANE (L.P.)  
SERIAL NUMBER  
Be sure to provide all pertinent facts when you call or visit.  
PART DESCRIPTION  
The model number of your Gas Water Heater will be found on the rating  
place located above the gas control valve.  
THIS IS A REPAIR PARTS LIST, NOT A PACKING LIST.  
33  
NOTES:  
34  
NOTES:  
35  
6 YEAR LIMITED WARRANTY ON WATER HEATER  
For six years from date of purchase, if this water heater is installed and operated in a single-family home in accordance with the owner’s  
manual instructions and all local applicable plumbing codes, Sears will supply a free water heater for one that develops a leak.  
For the second through sixth year from purchase date, you must pay the labor cost for installation of water heater.  
For commercial, institutional, industrial, or residential use by two or more families, the above limited warranty is only for two years.  
During the second year you must pay the labor cost for water heater installation.  
1 YEAR EXCLUSIVE KENMORE LABOR WARRANTY  
For the rst year from the date of purchase, Sears will, free of charge, supply and install new water heater parts for defective ones  
or a new water heater for one that develops a leak.  
WARRANTY SERVICE  
To obtain warranty service, call 1-800-4-MY-HOME® (1-800-469-4663). This warranty applies only while this product is in use in the  
United States.  
This warranty gives you specic legal rights and you may also have other rights which vary from state to state.  
SEARS, ROEBUCK AND CO., Dept. 817 WA, HOFFMAN ESTATES, IL 60179  
The price of your water heater does not include a free checkup service call. On water heater installations arranged by Sears, Sears warrants  
the installation.  
A charge will be made on service calls due to poor or incomplete installation. These include:  
a. Adjusting thermostat  
b. Leaks in pipes or ttings  
c. Condensation  
MASTER PROTECTION AGREEMENTS  
Fast help by phone - phone support from a Sears technician  
on products requiring in-home repair, plus convenient repair  
scheduling.  
Congratulations on making a smart purchase. Your new Kenmore®  
product is designed and manufactured for years of dependable operation.  
But like all products, it may require preventive maintenance or repair  
from time to time. That’s when having a Master Protection Agreement  
can save you money and aggravation.  
Power surge protection against electrical damage due to power  
uctuations.  
Rental reimbursement if repair of your covered product takes longer  
than promised.  
Purchase a Master ProtectionAgreement now and protect yourself from  
unexpected hassle and expense.  
Once you purchase the Agreement, a simple phone call is all that it  
takes for you to schedule service. You can call anytime day or night, or  
schedule a service appointment on-line.  
The Master ProtectionAgreement also helps extend the life of your new  
product. Here’s what’s included in the Agreement:  
Sears has over 12,000 professional repair specialist, who have access  
to over 4.5 million quality parts and accessories. That’s the kind of  
professionalism you can count on to help prolong the life of your new  
purchase for years to come. Purchase your Master ProtectionAgreement  
today!  
Expert Service by our 12,000 professional repair specialists.  
Unlimited service and no charge for parts and labor on all covered  
repairs.  
Some limitations and exclusions apply. For prices and additional  
information call 1-800-827-6655.  
“No-lemon” guarantee - replacement of your covered product if  
four or more product failures occur within twelve months.  
Product replacement if your covered product can’t be xed.  
SEARS INSTALLATION SERVICE  
Annual Preventive Maintenance Check at your request - no extra  
charge.  
For Sears professional installation of home appliances, garage door  
openers, water heaters and other major home items, in the U.S.A., call  
1-800-4-MY-HOME®.  
For in-home major brand repair service  
Call 24 hours a day, 7 days a week (U.S.A. and Canada)  
1-800-4-MY-HOME®  
(1-800-469-4663)  
The model number of your water heater is found on the model rating plate on the front of the water heater  
Sears, Roebuck and Co., Hoffman Estates, IL 60179 U.S.A.  

Planar Systems Car Video System LA1950RTR User Manual
Pioneer S BD50SW User Manual
Panasonic DMCFH25K User Manual
Panasonic Camcorder DMC SZ9 User Manual
Numark Industries Car Stereo System NDX800 User Manual
Melissa Electronic Wine Cooler 758039 User Manual
Lochinvar Condensing Boiler User Manual
Lennox International Inc Boiler Gas Fired Hot Water Boiler User Manual
Kenwood DNX9280BT User Manual
Kathrein MobiSet 3 Digital CAP 700 User Manual