Burnham series Series 2B User Manual

INSTALLATION, OPERATING AND  
SERVICE INSTRUCTIONS FOR  
SERIES 2® (model B)  
GAS - FIRED BOILER  
For service or repairs to boiler, call your heating contractor. When seeking information on boiler,  
provide Boiler Model Number and Serial Number as shown on Rating Label.  
Boiler Model Number  
Installation Date  
Boiler Serial Number  
2
Phone Number  
Heating Contractor  
Address  
Price - $3.00  
81417032R24-10/08  
WARNING  
READ THESE INSTRUCTIONS CAREFULLY BEFORE PROCEEDING WITH THE INSTALLATION OF BOILER.  
POST INSTRUCTIONS NEAR BOILER FOR REFERENCE BY OWNER AND SERVICE TECHNICIAN. MAINTAIN  
INSTRUCTIONS IN LEGIBLE CONDITION.  
Dimensions [Inches]  
Gas  
Approx.  
Shipping  
Weight  
[lb.]  
Boiler  
Model  
Number  
Water Recommended  
Connection  
For Automatic  
Gas Valve  
Content  
[gallons]  
Vent Size  
[1] [2]  
A
B
C
D
E
F
G
202  
202X  
203  
204  
205  
206  
207  
208  
209  
210  
18-3/4 10-3/4 6-3/8  
4
4
4
5
6
6
7
7
8
8
45-5/8 8-1/2 10 [3]  
1/2  
1/2  
1/2  
1/2  
1/2  
1/2  
3/4  
3/4  
3/4  
3/4  
2.5  
3.2  
3.2  
4
3" dia. x 15 ft.  
4" dia. x 15 ft.  
4" dia. x 15 ft.  
5" dia. x 15 ft.  
6" dia. x 15 ft.  
6" dia. x 15 ft.  
7" dia. x 15 ft.  
7" dia. x 15 ft.  
8" dia. x 15 ft.  
8" dia. x 15 ft.  
212  
262  
262  
306  
354  
414  
458  
514  
550  
608  
20  
20  
12  
12  
6
6
45-5/8 8-1/2  
45-5/8 8-1/2  
47-1/8 9-1/8  
48-1/2 9-3/4  
48-1/2 9-3/4  
4-3/4  
4-3/4  
4-3/4  
5-1/4  
5-1/4  
23-1/4 15-1/4 7-5/8  
26-1/2 18-1/2 9-1/4  
29-3/4 21-3/4 10-7/8  
4.7  
5.5  
6.2  
7
33  
25  
12-1/2  
50-1/8 10-3/8 6-5/8  
50-1/8 10-3/8 6-5/8  
36-1/4 28-1/4 14-1/8  
39-1/2 31-1/2 15-3/4  
42-3/4 34-3/4 17-3/8  
52  
52  
11  
11  
7-1/4  
7-1/4  
7.7  
8.5  
[1] 15' chimney height is from bottom of draft hood opening to top of chimney.  
[2] Refer to the National Fuel Gas Code for equivalent areas of circular and rectangular flue linings.  
Maximum Allowable Working Pressure - 30 PSI (Water Only)  
[3] 202 only. Dimension 'G' includes allowance for 4" x 3" reducer furnished with boiler. See Figure 8.  
Figure 1  
3
I . Installation Instructions  
C. Save two of the wooden slats from the container  
sleeve for use in Steps D & E.  
1. INSPECT ShIPMENT carefully for any signs of  
damage. All equipment is carefully manufactured,  
inspected and packed. Our responsibility ceases upon  
delivery of Boiler to the carrier in good condition. Any  
claims for damage or shortage in shipment must be filed  
immediately against the carrier by the consignee. No  
claims for variances or shortages will be allowed by  
Boiler Manufacturer unless presented within sixty (60)  
days after receipt of equipment.  
D. Tilt the boiler to one side and slide a wooden slat  
under the two raised feet.  
E. Tilt the boiler to the other side and slide another  
wooden slat under the two raised feet.  
F. Slide the boiler forward or backward off the skid  
using the two wooden slats as runners.  
6. Move boiler to permanent position.  
2. BOILER INSTALLATION must conform to the  
requirements of the authority having jurisdiction, or in  
the absence of such requirements, to:  
7. PROvIDE CLEARANCE and AIR for COMBUS-  
TION and vENTILATION.  
U.S.A. -  
National Fuel Gas Code, ANSI Z223.1.  
When required by the authority having juris-  
diction, the installation must conform to  
ANSI/ASME No. CSD-1.  
WARNING  
Adequate combustion and ventilation air must be  
provided to assure proper combustion.  
CANADA - "Installation Codes for Natural and LP Gas  
Burning Appliances and Equipment, CAN/  
CSA-B149.1.  
A. CLEARANCES  
1. ALL INSTALLATIONS - Practical service  
clearances must be considered (see Figure 1). A  
minimum of 24" (6.0cm) from the left side and  
front jacket panels is recommended for servicing  
but may be reduced to minimum shown in  
Figure 2. Subject to boiler and system piping,  
left side clearance may be reduced to 1" (2.5cm)  
if right side clearance is increased to 9"  
(22.9cm).  
3. These Gas Boilers are DESIGN CERTIFIED FOR  
INSTALLATION ON COMBUSTIBLE FLOORING.  
DO NOT INSTALL ThESE BOILERS ON  
CARPETING.  
NOTICE  
Do not drop boiler. Do not bump boiler jacket  
against floor.  
2. ALCOvE INSTALLATIONS - An alcove is  
considered a closet as shown in Figure 2 less  
front. height clearance may be reduced to 27"  
(68.6cm).  
4. LOCATE BOILER in front of or behind installation  
position before removing Crate. Locate on a level floor  
as close to chimney as possible. For basement  
installations, provide a solid base such as concrete, if  
floor is not level or if water may be encountered on  
floor around Boiler.  
3. UNCONFINED SPACE (see definition,  
paragraph (B) below) - height clearance may be  
reduced to 27" (68.6cm).  
The boiler shall be installed such that the gas ignition  
system components are protected from water (dripping,  
spraying, rain, etc.) during boiler operation and service  
(circulator replacement, control replacement, etc.).  
B. PROvIDE COMBUSTION AND vENTILATION  
AIR in accordance with applicable provisions of  
local building codes, or: U.S.A. - National Fuel  
Gas Code, NFPA 54/ANSI Z223.1, Canada -  
Natural and Propane Gas Installation Code, CAN/  
CSA-B149.1.  
DANGER  
1. CLOSET INSTALLATIONS (confined space) in  
a building of other than unusually tight  
construction (see definition below), provide  
combustion and ventilation air as shown in  
Figure 2.  
Do not install boiler where gasoline or other  
flammable vapors or liquids, or sources of  
hydrocarbons (i.e. bleaches, cleaners, chemicals,  
sprays, paint removers, fabric softeners, etc.) are  
used or stored.  
2. Installations other than closet in paragraph (1) :  
a. Determine volume of space (boiler room).  
Rooms communicating directly with space  
(through openings not furnished with doors)  
are considered part of space.  
5. REMOvE CRATE -  
A. Remove all crate fasteners. Lift off outside  
container.  
B. Remove all screws and brackets securing boiler to  
skid.  
e. For boiler located in a building of other than  
unusually tight construction, adequate  
combustion and ventilation air is normally  
provided by fresh air infiltration through  
cracks around windows and doors.  
f. For boiler located in building of unusually  
tight construction, provide outdoor air  
through two permanent openings which  
communicate directly or by duct with the  
outdoors or spaces (crawl or attic) freely  
communicating with the outdoors. Locate  
one opening within 12 inches (30.5cm) of  
top of space. Locate remaining opening  
within 12 inches (30.5cm) of bottom of  
space. Minimum dimension of air opening is  
3 inches (7.6cm). Size each opening per  
following:  
i. Direct communication with outdoors.  
Minimum free area of 1 square inch  
(6.5cm2) per 4,000 Btu per hour input of  
all equipment in space.  
ii. vertical ducts. Minimum free area of 1  
square inch (6.5cm2) per 4,000 Btu per  
hour input of all equipment in space. Duct  
cross-sectional area shall be same as  
opening free area.  
Figure ꢀ: Minimum Clearances  
iii. Horizontal ducts. Minimum free area of 1  
square inch (6.5cm2) per 2,000 Btu per  
hour input of all equipment in space. Duct  
cross-sectional area shall be same as  
opening free area.  
volume [ft³](m3) = Length [ft](m) x Width  
[ft](m) x height [ft](m)  
b. Determine Total Input of all appliances in  
space. Round result to nearest 1,000 Btu per  
hour (Btuh).  
g. ventilation Duct Louvers and Grilles. Equip  
outside openings with louvers to prevent  
entrance of rain and snow, and screens to  
prevent entrance of insects and rodents.  
Louvers and grilles must be fixed in open  
position or interlocked with equipment to  
open automatically before burner operation.  
Screens must not be smaller than ¼ inch  
mesh.  
c. Determine type of space. Divide volume by  
Total Input.  
i. If result is greater than or equal to 50 ft³  
(1.4m3) per 1,000 Btuh, space is  
considered an unconfined space.  
ii. If result is less than 50 ft³ (1.4m3) per  
1,000 Btuh, space is considered a confined  
space.  
d. Determine building type. A building of  
unusually tight construction has the  
following characteristics:  
Consider the blocking effect of louvers,  
grilles and screens when calculating the  
opening size to provide the required free  
area. If free area of louver or grille is not  
known, assume wood louvers have 20-25  
percent free area and metal louvers and  
grilles have 60-75 percent free area.  
i. Walls and ceiling exposed to outside  
atmosphere have a continuous water vapor  
retarder with a rating of 1 perm or less  
with openings gasketed and sealed, and  
ii. Weather-stripping has been added on  
openable windows and doors, and  
iii. Caulking or sealants applied in joints  
around window and door frames, between  
sole plates and floors, between wall-  
ceiling joints, between wall panels, at  
plumbing and electrical penetrations, and  
at other openings.  
8. CONNECT GAS SERvICE from Meter to gas control  
assembly in accordance with Local Piping Codes and  
requirements of Gas Company, see Figure 1. They may  
require piping of larger size than Control Assembly  
Connection, especially if run from meter is long or  
includes several elbows. (See Figure 1 for size of Gas  
Connection to gas control assembly).  
Table 1: Maximum Capacity of Schedule ꢁ0 Pipe in CFH For Natural Gas Pressures of ½ psig or Less  
0.3 Inch w.c. Pressure Drop  
0.5 Inch w.c. Pressure Drop  
Length  
[Feet]  
½
¾
1
1¼  
½
¾
1
1¼  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
132  
92  
73  
63  
56  
50  
46  
43  
40  
38  
278  
190  
152  
130  
115  
105  
96  
520  
350  
285  
245  
215  
195  
180  
170  
160  
150  
1,050  
730  
590  
500  
440  
400  
370  
350  
320  
305  
175  
120  
97  
82  
73  
66  
61  
57  
53  
50  
360  
250  
200  
170  
151  
138  
125  
118  
110  
103  
680  
465  
375  
320  
285  
260  
240  
220  
205  
195  
1,400  
950  
770  
660  
580  
530  
490  
460  
430  
400  
90  
84  
79  
Table 2: Equivalent Length of Fittings  
Nominal Pipe Size  
Table 3: Specific Gravity Correction Factors for  
Natural Gas  
Specific  
Gravity  
Correction  
Factor  
Specific  
Gravity  
Correction  
Factor  
Fitting  
½
¾
1
1¼  
0.50  
0.55  
0.60  
0.65  
0.70  
0.75  
0.80  
1.10  
1.04  
1.00  
0.96  
0.93  
0.90  
0.87  
1.30  
1.40  
1.50  
1.60  
1.70  
---  
1.07  
1.04  
1.00  
0.97  
0.94  
---  
45° Ell  
90° Ell  
0.7  
1.6  
3.1  
1
1.2  
2.6  
5.2  
1.6  
3.5  
6.9  
2.1  
4.1  
Tee (As Elbow)  
This piping is to be supplied by the installer and must  
include a trap, a ground joint union and a manual  
shutoff valve upstream of the gas control assembly  
outside of the jacket when codes require, see Figure 1.  
A pipe thread compound resistant to the action of  
liquefied petroleum gases should be applied to all  
threaded joints in the gas piping. Pressure testing of the  
Gas Supply Piping Boiler and its connections is  
required before placing the boiler in operation.  
---  
---  
A. Allowable loss of pressure to assure a burner  
manifold pressure of 3½" (8.9cm) water for natural  
gas.  
B. Supply of gas to be provided in cubic feet.  
C. Length of piping and number of fittings.  
D. Specific gravity of gas.  
The boiler and shutoff valve must be disconnected from  
the gas supply piping system during any pressure  
testing at pressures greater than ½ psig (3.5kPa).  
E. Correction factor for specific gravity.  
9. BOILER PIPING  
The boiler must be isolated from the gas supply piping  
system by closing its individual manual shutoff valve  
during any pressure testing of the gas supply piping  
system at pressures equal to or less than ½ psig  
(3.5kPa).  
CAUTION  
Failure to properly pipe boiler may result in  
improper operation and damage to boiler or  
building.  
RECOMMENDED SIZING OF GAS SUPPLY  
PIPING TO BOILER FOR NATURAL GAS - shall  
be such as to provide the required supply of gas without  
undue loss of pressure between meter and the boiler.  
Gas supply piping should be sized in accordance with  
the Tables 1, 2 and 3. The following shall be taken into  
account:  
A. CLEARANCES - hot water pipes do not require  
clearance from combustible construction.  
B. Install drain valve and safety relief valve as shown  
in Figures 1 and 3. Note - Safety relief valve must  
be in vertical position.  
C. Pipe safety relief valve discharge to floor.  
Figure ꢁ: Recommended Piping  
for Combination Heating & Cooling  
(Refrigeration) Systems  
with flow control valves to prevent gravity  
circulation of boiler water during the  
operation of the cooling system.  
h. Use a boiler bypass if the boiler is to be  
operated in a system which has a large  
volume or excessive radiation where low  
boiler water temperatures may be  
encountered (i.e. converted gravity  
circulation system, etc.).  
Figure 3: Recommended Water Piping for  
Zone Valve Zoned Heating Systems  
Install a pipe tee at the boiler return along  
with a second tee in the supply piping as shown in  
Figure 3. The bypass should be the same size as the  
supply and return lines with valves located in the  
bypass and supply outlet as illustrated in Figure 3 in  
order to regulate water flow to maintain higher  
boiler water temperatures.  
WARNING  
Safety relief valve discharge piping must be  
piped near floor to eliminate potential of severe  
burns. Do not pipe in any area where freezing  
could occur. Do not install any shut-off valves.  
Set the by-pass and boiler supply valves to a half  
throttle position to start. Operate boiler until the  
system water temperature is at a normal operating  
range.  
D. Install circulator with flanges, gaskets and bolts  
provided. Five foot long circulator harness allows  
circulator to be mounted on supply or return.  
Connect harness to circulator and secure any excess  
conduit.  
Adjust the valves to provide 180° to 200°F supply  
water temperature. Opening the boiler supply valve  
will raise the system temperature, while opening the  
by-pass valve will lower the system supply  
temperature.  
E. For heating only system piping, see Figure 3.  
Consult also I=B=R Installation Guides.  
I. A hot water boiler installed above radiation level  
must be provided with a low water cutoff device as  
part of the installation.  
F. For space heating and domestic water heating with  
Alliance SL™ water heater (intermittent circulation  
only); install Alliance SL™ water heater as a  
separate heating zone. Refer to Alliance SL™  
Installation, Operating and Service Instructions for  
additional information.  
If a low water cut-off is required, it must be  
mounted in the system piping above the boiler.  
The minimum safe water level of a hot water boiler  
is just above the highest water containing cavity of  
the boiler; that is, a hot water boiler must be full of  
water to operate safely.  
G. If this boiler is used in connection with refrigeration  
systems, the boiler must be installed so that the  
chilled medium is piped in parallel with the heating  
boiler using appropriate valves to prevent the chilled  
medium from entering the boiler, see Figure 4. Also  
consult I=B=R Installation and Piping Guides.  
Refer to Section vI for low water cut-off piping and  
wiring instructions.  
J. If it is required to perform a long term pressure test  
of the hydronic system, the boiler should first be  
isolated to avoid a pressure loss due to the escape of  
air trapped in the boiler.  
If this Boiler is connected to heating coils located in  
air handling units where they may be exposed to  
refrigerated air, the boiler piping must be equipped  
To perform a long term pressure test including the  
boiler, ALL trapped air must first be removed from  
the boiler.  
A loss of pressure during such a test, with no visible  
water leakage, is an indication that the boiler  
contained trapped air.  
K. OxYGEN CORROSION:  
Oxygen contamination of the boiler water will cause  
corrosion of the iron and steel boiler components,  
which can lead to failure. As such, any system must  
be designed to prevent oxygen absorption in the first  
place or prevent it from reaching the boiler.  
Problems caused by oxygen contamination of boiler  
water are not covered by Burnham's standard  
warranty.  
There are many possible causes of oxygen  
contamination such as:  
1. Addition of excessive make-up water as a result  
of system leaks.  
2. Absorption through open tanks and fittings.  
3. Oxygen permeable materials in the distribution  
system.  
In order to insure long product life, oxygen  
sources should be eliminated. This can be  
accomplished by taking the following measures:  
Figure ꢃ  
1. Repairing system leaks to eliminate the need for  
addition of make-up water.  
B. Pinch the black strain relief bushing installed in the  
jacket right side panel to dislodge it from the jacket  
and pull just enough of the black power cord out so  
the blocked vent switch will reach the near side of  
the draft hood skirt. Do not pull out more power  
cord than necessary.  
2. Eliminating open tanks from the system.  
3. Eliminating and/or repairing fittings which allow  
oxygen absorption.  
4. Use of non-permeable materials in the  
distribution system.  
5. Isolating the boiler from the system water by  
installing a heat exchanger.  
C. Position the mounting bracket (with switch attached)  
onto the lower edge of the draft hood skirt by  
locating the center tooth (with the #10 sheet metal  
screw) on the outside and the other two teeth inside  
the draft hood skirt. See Figure 6.  
10. INSTALL DRAFT hOOD without modification on  
outlet of flue collector (See Figure 1). Secure with sheet  
metal screws.  
D. Slide the mounting bracket up tight against the  
lower edge of the draft hood skirt, so that the #10  
sheet metal screw is above the skirt's stiffening rib.  
WARNING  
Do not alter boiler draft hood or place any  
obstruction or non-approved damper in the  
breeching or vent system. Flue gas spillage can  
occur. ETL certification will become void.  
E. Secure the bracket in this position by tightening the  
#10 sheet metal screw against the outer surface of  
the draft hood skirt.  
F. Reinsert the excess power cord through the jacket  
side panel hole to take the slack out of the power  
cord running up to the blocked vent switch.  
11. INSTALL BLOCKED vENT SWITCh  
The blocked vent switch assembly shipped taped to the  
top of the boiler includes a power cord and a switch  
attached to a mounting bracket. The mounting bracket  
has a three tooth staggered comb stamping at one end  
with a #10 sheet metal screw in the center tooth.  
G. Reposition the strain relief bushing around the  
power cord at the jacket side panel, pinch the two  
halves of the bushing together, and snap it back into  
the hole in the jacket side panel to secure the power  
cord to the jacket.  
A. Untape the blocked vent switch assembly from the  
top of the boiler and uncoil the power cord.  
h. Be sure the power cord, mounting bracket, and  
switch are secure and located as shown in Figure 6.  
Figure ꢄ: Plug-in Damper Installation  
WARNING  
NOTICE  
Failure to properly install and use this Blocked  
Vent Switch may result in property damage,  
personal injury or loss of life.  
Provide adequate clearance for servicing.  
WARNING  
12. TO MEET FEDERALLY MANDATED  
EFFICIENCIES, ThIS BOILER MUST BE  
EQUIPPED WITh A vENT DAMPER.  
Provide ꢃ" (1ꢂ.ꢀcm) minimum clearance between  
damper and combustible construction.  
C. Install the 90° BX connector attached to the flexible  
conduit in the 7/8" knockout on the left side of the  
jacket. Plug the factory wired vent Damper harness  
into the polarized receptacle. Install a cable clamp  
around the flexible conduit and attach to the Jacket  
top panel. (See Figure 7).  
OPEN ThE vENT DAMPER CARTON and remove  
the Installation Instructions. READ ThE INSTALLA-  
TION INSTRUCTIONS ThOROUGhLY before  
proceeding.  
The automatic gas control valve supplied on each Series  
2™ boiler provides the redundancy referenced in the  
vent damper Installation Instructions.  
NOTICE  
CAUTION  
Please refer to the specifications, installation  
instructions and troubleshooting guide packed  
in the vent damper carton for complete detailed  
installation instructions. Also refer to Figure ꢄ in  
this manual.  
Do not use one vent damper to control two heating  
appliances.  
A. The vent damper should be the same size as the  
outlet of the Draft hood. (See Figure 1) Unpack the  
damper carefully - DO NOT FORCE IT CLOSED!  
Forcing the damper may damage the gear train and  
void the warranty. The damper assembly includes a  
prewired connection harness for use on all 24v  
Standing Pilot or electronic ignition control systems.  
D Continuous Ignition (Standing Pilot) Only. Remove  
knockout from vent damper blade.  
E. Size 202 Only. Install 4" x 3" reducing fitting on  
vent damper outlet.  
13. INSTALL vENT CONNECTOR from reducing  
fitting (202 Only), draft hood or damper to chimney, see  
Figure 8.  
B. Mount the vent damper assembly after the draft  
hood, as close to the draft hood as practicable  
without modification to the draft hood or vent  
damper. (Refer to Figure 7 and to instructions  
packed with the vent damper for specific  
instructions). This is a must for the wiring harness to  
fit and the damper position indicator to be visible to  
the users.  
boiler is served by the damper device. Installation  
per paragraph 12 complies with this provision.  
E. Where two or more appliances vent into a common  
vent, the area of the common vent should at least  
equal the area of the largest vent plus 50% of the  
area in the additional vents. Do not connect the vent  
of this appliance into any portion of mechanical  
draft system operating under positive pressure.  
F. vent pipe should have the greatest possible initial  
rise above the draft hood consistent with the head  
room available and the required clearance from  
adjacent combustible building structure. vent Pipe  
should be installed above the bottom of chimney to  
prevent blockage.  
G. vent pipe should slope upward from draft hood to  
chimney not less than one inch in four feet. Doivent  
présenter des tronçons horizontaux dont la pente  
montante est d’au moins ¼ po par pied (21 mm/m)  
entre la chaudière et l’évent. No portion of vent  
pipe should run downward or have dips or sags.  
vent pipe must be securely supported. Les sections  
horizontales doivent être supportées pour prévenir le  
fléchissement.  
Figure ꢅ: Typical Vent Installation  
DANGER  
Inspect existing chimney before installing boiler.  
Failure to clean or replace perforated pipe or tile  
lining will cause severe injury or death.  
h. vent pipe must be inserted into but not beyond  
inside wall of chimney liner. Seal tight between vent  
pipe and chimney.  
A. vent installation shall be in accordance with local  
building codes; or the local authority having  
jurisdiction; or the National Fuel Gas Code, ANSI  
Z223.1/NFPA 54; or the Standard for Chimneys,  
Fireplaces, vents, and Solid Fuel Burning  
I. Do not install non-listed (AGA, CGA, CSA, ETL or  
UL) vent damper or other obstruction in vent pipe.  
WARNING  
Appliances, ANSI/NFPA 211. Both of the  
14. IF AN ExISTING BOILER IS REMOvED -  
aforementioned standards, ANSI Z223.1 and ANSI/  
NFPA 211, specify Type B and Type L double wall  
metal vents and fire clay tile lined masonry  
chimneys as suitable chimney constructions for  
Category I, draft hood equipped appliances, such as  
this Series 2™ boiler. Both standards prohibit the  
use of unlined masonry construction as a chimney,  
with the exception in ANSI Z223.1/NFPA 54 that  
"Where permitted by the authority having  
jurisdiction, existing chimneys shall be permitted to  
have their use continued when an appliance is  
replaced by an appliance of similar type, input  
rating, and efficiency." ANSI/NFPA 211 prohibits  
the use of single wall metal vent as a chimney, while  
ANSI Z223.1 allows it under very restrictive  
conditions. In Canada refer to the Natural Gas and  
LP Installation Code, CAN/CSA-B149.1.  
When an existing boiler is removed from a common  
venting system, the common venting system is likely to  
be too large for proper venting of the appliances  
remaining to it.  
At the time of removal of an existing boiler, the  
following steps shall be followed with each  
appliance remaining connected to the common  
venting system placed in operation, while the other  
appliances remaining connected to the common  
venting system are not in operation:  
A. Seal any unused openings in the common venting  
system.  
B. Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion, and other  
deficiencies which could cause an unsafe condition.  
B. Do not connect into same leg of chimney serving an  
C. Insofar as is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the common  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any appliance  
not connected to the common venting system. Turn  
on any exhaust fans, such as range-hoods and  
open fireplace.  
C. Inspect chimney for obstructions or restrictions and  
remove. Clean chimney if necessary.  
D. vent pipe to chimney must not be smaller than outlet  
on draft hood or damper. Although single wall vent  
pipe may be used, Type B is recommended. The  
venting system must be arranged so that only the  
bathroom exhausts, so they will operate at maximum  
10  
speed. Do not operate a summer exhaust fan. Close  
fireplace dampers.  
l’espace où les appareils toujours raccordés au  
système d’évacuation sont installés et les autres  
espaces du bâtiment. Mettre en marche les  
sécheuses, tous les appareils non raccordés au  
système d’évacuation commun et tous les  
ventilateurs d’extraction comme les hottes de  
cuisinière et les ventilateurs des salles de bain.  
S’assurer que ces ventilateurs fonctionnent à la  
vitesse maximale. Ne pas faire fonctionner les  
ventilateurs d’été. Fermer les registres des  
cheminées.  
D. Place in operation the appliance being inspected.  
Follow the Lighting (or Operating) Instructions.  
Adjust thermostat so appliance will operate  
continuously.  
E. Test for spillage at the draft hood relief opening  
after 5 minutes of main burner operation. Use the  
flame of a match or candle, or smoke from a  
cigarette, cigar or pipe.  
F. After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above, return  
doors, windows, exhaust fans, fireplace dampers and  
any other gas burning appliance to their previous  
conditions of use.  
D. Mettre l’appareil inspecté en marche. Suivre les  
instructions d’allumage. Régler le thermostat de  
facon que l’appareil fonctionne de facon continue.  
E. Faire fonctionner le brùleur principal pendant 5 min  
ensuite, déterminer si le coupe-tirage déborde à  
l’ouverture de décharge. Utiliser la flamme d’une  
allumette ou d’une chandelle ou la fumée d’une  
cigarette, d’un cigare ou d’une pipe.  
G. Any improper operation of the common venting  
system should be corrected so the installation  
conforms with the National Fuel Gas Code, ANSI  
Z223.1 and/or CAN/CSA B149.1, Installation  
Codes. When resizing any portion of the common  
venting system, the common venting system should  
be resized to approach the minimum size as  
determined using the National Fuel Gas Code,  
ANSI Z223.1 and/or CAN/CSA B149.1, Installation  
Codes.  
F. Une fois qu’il a été déterminé, selon la méthode  
indiquée ci-dessus, que chaque appareil raccordé au  
système d’évacuation est mis à l’air libre de facon  
adéquate. Remettre les portes et les fenêtres, les  
ventilateurs, les registres de cheminées et les  
appareils au gaz à leur position originale.  
G. Tout mauvais fonctionnement du système  
d’évacuation commun devrat être corrigé de facon  
que l’installation soit conforme au National Fuel  
Gas Code, ANSI Z223.1 et (ou) aux codes  
d’installation CAN/CSA-B149.1. Si la grosseur  
d’une section du système d’évacuation doit être  
modifiée, le système devrait être modifié pour  
respecter les valeurs minimales des tableaux  
pertinents de l’appendice F du National Fuel Gas  
Code, ANSI Z223.1 et (ou) des codes d’installation  
CAN/CSA-B149.1.  
Au moment du retrait d’une chaudière existante, les  
mesures suivantes doivent être prises pour chaque  
appareil toujours raccordé au système d’evacuation  
commun et qui fonctionne alors que d’autres  
appareils toujours raccordés au système  
d’évacuation ne fonctionnent pas:  
A. Sceller toutes les ouvertures non utilisées du  
système d’évacuation.  
B. Inspecter de facon visuelle le système d’évcuation  
pour déterminer la grosseur et l’inclinaison  
horizontale qui conviennent et s’assurer que le  
système est exempt d’obstruction, d’étranglement,  
de fuite, de corrosion et autres défaillances qui  
pourraient présenter des risques.  
15. INSTALL A ROOM ThERMOSTAT on an inside  
wall about four feet above floor. Never install  
thermostat on an outside wall or where it will be  
influenced by drafts, hot or cold water pipes, lighting  
fixtures, television, rays of the sun or near a fireplace.  
Keep large furniture away from thermostat so there will  
be free movement of room air around this control.  
C. Dans la mesure du possible, fermer toutes les portes  
et les fenêtres du bâtiment et toutes les portes entre  
Table ꢁ: Wiring Diagrams and Heat Anticipator Settings  
Thermostat Heat Anticipator  
Setting [Amps]  
Wiring  
Diagram Figure  
Ignition Type  
Circulation Method  
Intermittent  
Constant/Gravity  
Intermittent  
0.6  
1.0  
0.6  
1.0  
11  
14  
12  
15  
Continuous  
(Standing Pilot)  
Electronic  
Constant/Gravity  
If system tends to overheat above thermostat's temperature setting, reduce heat anticipator setting by  
0.1 or 0.2 amps. If system tends to shortcycle without reaching desired room temperature, increase heat  
anticipator setting by 0.1 or 0.2 amps.  
11  
heat Anticipator in Thermostat should be set to match  
the requirements of the control to which it is connected.  
See Table 4. If system tends to overheat above the  
thermostat's temperature setting, reduce heat anticipator  
setting by .1 or .2 amps. If system tends to short cycle  
without reaching desired room temperature, increase  
heat anticipator setting by .1 or .2 amps.  
17. vENT DAMPER SEQUENCE OF OPERATION.  
See Figure 9.  
A. The vent Damper is continuously powered at  
Terminal 1.  
B. When there is a call for heat, the damper relay coil is  
energized through Terminal 5 if all limits ahead of  
the damper are satisfied.  
16. INSTALL ELECTRIC WIRING in accordance with  
National Electric Code or the Canadian Electrical Code  
and local regulations. See Figures 11 through 16 for  
applicable wiring diagram. A separate electrical circuit  
must be run from the main electrical service with an  
over-current device/disconnect in the circuit. A service  
switch is recommended and may be required by some  
local jurisdictions. When installed, the boiler must be  
electrically grounded in accordance with local codes or,  
in the absence of local codes, with the National  
Electrical Code, ANSI/NFPA 70, and/or the CSA C22.1  
Electrical Code, if an external electrical source is  
utilized.  
C. The relay coil closes contacts which energize the  
damper motor, causing the damper to open.  
D. When the damper blade reaches the fully open  
position, power is sent back to the ignition circuit  
through Terminal 2 and the damper motor is de-  
energized.  
E. When the call for heat is satisfied, the damper relay  
coil is de-energized - closing contacts which  
energize the damper motor. This causes the damper  
to close. When the damper blade reaches the fully  
closed position, the damper motor is de-energized.  
POWER FAILURE - The damper blade will stop in  
the position it was in when power failed.  
(Combustion can never take place unless the damper  
blade is in the fully open position.)  
For zone valve wiring, a separate 24V transformer is  
required rather than attempting to use the boiler  
mounted control. Consult zone valve manufacturer for  
assistance.  
Figure ꢆ: Vent Damper Schematic Wiring Diagram  
CAUTION  
This boiler contains controls which may cause the boiler to shut down and not restart without service. If  
damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weath-  
er; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if  
the boiler is inoperative.  
CAUTION  
Avoid operating this boiler in an environment where saw dust, loose insulation fibers, dry wall dust, etc.  
are present. If boiler is operated under these conditions, the burner interior and ports must be cleaned and  
inspected daily to insure proper operation.  
1ꢀ  
Figure 11: Wiring Diagram, ꢀꢁ Volt Standing Pilot and Intermittent Circulation  
2. Blocked vent Switch  
SEQUENCE OF OPERATION  
In the event excessive blockage in the vent system is  
developed the blocked vent switch will open  
interrupting power to the gas valve. The main  
burners will be extinguished immediately, the  
circulator will continue to operate, and the vent  
damper will remain open until the thermostat is  
turned off. The source of blockage must be  
corrected by trained and skilled personnel from a  
qualified service agency before resetting switch.  
Normal Operation  
1. When the thermostat call for heat, the vent damper  
will open (see paragraphs 17A through 17D). The  
circulator is started through a relay and at the same  
time the gas valve is energized allowing main gas  
flow and ignition of main burners.  
2. Where condensation of flue gas is encountered in  
boiler flues a reverse acting circulator control should  
be installed to stop the circulator before the boiler  
water temperature drops to that which flue gas  
condensation may occur.  
3. Flame Rollout Switch  
In the event excessive blockage in the boiler section  
flue passageways is developed the flame rollout  
switch will open interrupting power to the gas valve.  
The main burners will be extinguished immediately,  
the circulator will continue to operate and the vent  
damper will remain open until the thermostat is  
turned off. If the flame rollout switch is activated do  
not attempt to place the boiler in operation. The  
source of blockage must be corrected and the flame  
rollout switch replaced by trained and skilled  
personnel from a qualified service agency.  
3. After the thermostat is satisfied the main valve will  
close and main burner flames will be extinguished.  
The vent damper will close (see paragraph 17E).  
SAFETY ShUTDOWN  
1. high Limit Switch  
In the event excessive boiler water temperature is  
developed the high limit switch will open  
interrupting power to the gas valve. The main  
burners will be extinguished immediately, and the  
vent damper will close at the same time, but the  
circulator will continue to operated. Normal  
operation will be resumed when the boiler water  
temperature drops to a point where the high limit  
switch closes.  
4. Pilot  
The thermocouple proves pilot flame and in the  
absence of such within 45-90 seconds causes the  
combination gas valve, which is equipped with a  
100% shut-off provision, to be de-energized, thus,  
preventing main gas or pilot gas flow.  
13  
Figure 1ꢀ: Wiring Diagram, Electronic Ignition (EI), Intermittent Circulation  
SEQUENCE OF OPERATION  
NORMAL OPERATION  
1. When the thermostat calls for heat, the relay is  
energized. The circulator starts and the vent damper  
opens (see Paragraphs 17A through 17D). When the  
damper blade reaches the fully open position, the  
ignition module is energized opening the pilot valve  
and energizing the igniter to ignite the pilot burner.  
2. Blocked vent Switch: Automatically interrupts  
main burner operation when excessive vent system  
blockage occurs. Control is a multiple use device. If  
blocked vent switch is activated do not attempt to  
place boiler in operation. Correct source of blockage  
and reset blocked vent switch.  
2. Sensor proves presence of pilot flame. Main valve  
3. Flame Roll-out Switch: Automatically interrupts  
boiler operation when flames or excessive heat are  
present in vestibule. Control is single use device. If  
flame roll-out switch is activated do not attempt to  
place boiler in operation. Correct source of blockage  
and replace flame roll-out switch.  
opens to ignite main burners.  
3. The burners and circulator will operate  
simultaneously until the thermostat is satisfied.  
4. After thermostat is satisfied, ignition module is de-  
energized, extinguishing pilot and main flame. Vent  
damper closes (see paragraph 17E).  
4. Igniter/Sensor: senses pilot flame and causes  
ignition module to turn off main burner and pilot  
burner gas flow should pilot burner flame  
SAFETY ShUTDOWN  
1. Limit: Automatically interrupts main burner  
operation when water temperature exceeds set point.  
Maximum allowable temperature is 250°F. Normal  
operation resumes when water temperature falls  
below set point.  
extinguish. Five to six minutes after shutdown,  
ignition module restarts ignition sequence.  
5. For Electronic Ignition Trouble Shooting Guide, see  
Page 25 of this manual.  
1ꢁ  
Figure 13: Wiring Diagram, ꢀꢁ Volt Standing Pilot with Continuous or Gravity Circulation  
SEQUENCE OF OPERATION  
2. Blocked vent Switch: In the event excessive  
blockage in the vent system is developed the  
blocked vent switch will open interrupting power to  
the gas valve. The main burners will be extinguished  
immediately and the vent damper will remain open  
until the thermostat is turned off. The source of  
blockage must be corrected by trained and skilled  
personnel from a qualified service agency before  
resetting switch.  
3. Flame Rollout Switch: In the event excessive  
blockage in the boiler section flue passageways is  
developed the flame rollout switch will open  
interrupting power to the gas valve. The main  
burners will be extinguished immediately and the  
vent damper will remain open until the thermostat is  
turned off. If the flame rollout switch is activated do  
not attempt to place the boiler in operation. The  
source of the blockage must be corrected and the  
flame rollout switch replaced by trained and skilled  
personnel from a qualified service agency.  
NORMAL OPERATION  
1. When the thermostat call for heat, the vent damper  
will open (see paragraphs 17A through 17D). The  
gas valve is energized allowing main gas to flow and  
operation of the main burners.  
2. Where condensation of flue gas is encountered in  
boiler flues a reverse acting circulator control should  
be installed to stop the circulator before the boiler  
water temperature drops to that which flue gas  
condensation may occur.  
3. After the thermostat is satisfied the main valve will  
close and main burner flames will be extinguished.  
The vent damper will close (see paragraph 17E). If  
the boiler is so equipped, circulator will continue to  
run.  
SAFETY ShUTDOWN  
1. high Limit Switch: In the event excessive boiler  
water temperature is developed the high limit switch  
will open interrupting power to the gas valve. The  
main burners will be extinguished immediately.  
Normal operation will be resumed when the boiler  
water temperature drops to a point where the high  
limit switch closes.  
4. Pilot: The thermocouple proves pilot flame and in  
the absence of such within 45-90 seconds causes the  
combination gas valve, which is equipped with a  
100% shut-off provision, to be de-energized, thus,  
preventing main gas or pilot gas flow.  
1ꢂ  
Figure 1ꢁ: Wiring Diagram, Electronic Ignition (EI), Continuous or Gravity Circulation  
SEQUENCE OF OPERATION  
NORMAL OPERATION  
1. When the thermostat calls for heat the vent damper  
opens (see Paragraphs 17A through 17D). When the  
damper blade reaches the fully open position, the  
ignition module is energized opening the pilot valve  
and energizing the igniter to ignite the pilot burner.  
2. Blocked vent Switch: Automatically interrupts  
main burner operation when excessive vent system  
blockage occurs. Control is a multiple use device. If  
blocked vent switch is activated do not attempt to  
place boiler in operation. Correct source of blockage  
and reset blocked vent switch.  
2. Sensor proves presence of pilot flame. Main valve  
opens to ignite main burners.  
3. Flame Roll-out Switch: Automatically interrupts  
boiler operation when flames or excessive heat are  
present in vestibule. Control is single use device. If  
flame roll-out switch is activated do not attempt to  
place boiler in operation. Correct source of blockage  
and replace flame roll-out switch.  
3. The burners will operate until the thermostat is  
satisfied.  
4. When thermostat is satisfied, ignition module is de-  
energized, extinguishing pilot and main flame. If  
boiler is equipped with circulator, circulator will  
continue to run. vent damper closes (see Para-graph  
17E).  
4. Igniter/Sensor: senses pilot flame and causes  
ignition module to turn off main burner and pilot  
burner gas flow should pilot burner flame  
SAFETY ShUTDOWN  
extinguish. Five to six minutes after shutdown,  
ignition module restarts ignition sequence.  
1. Limit: Automatically interrupts main burner  
operation when water temperature exceeds set point.  
Maximum allowable temperature is 250°F. Normal  
operation resumes when water temperature falls  
below set point.  
5. For Electronic Ignition Trouble Shooting Guide, see  
Page 25 of this manual.  
1ꢃ  
Figure 1ꢂ: Wiring Schematic, Zone Valves  
Figure 1ꢃ: Wiring Schematic, Zone Circulators  
1ꢄ  
II. Operating Instructions  
Safe lighting and other performance criteria were met with the gas manifold and control assembly provided on the boiler when the  
boiler underwent tests specified in American National Standard for Gas-Fired Low-Pressure Steam and Hot Water Boilers, ANSI  
Z21.13b-1994.  
1. MAIN BURNER ChECK - Check main burners to  
see that they were not dislodged during shipment. Rear  
of burners should be in the slots in the rear of burner  
tray and the front of the burners should be seated  
completely on the orifices.  
2. INITIAL START -  
A. FILL ENTIRE hEATING SYSTEM WITh  
WATER and vent air from system. Use the  
following procedure on a Series Loop System  
equipped with zone valves. (See Figure 3).  
1. Close isolation valve in boiler supply piping.  
2. Isolate all circuits by closing zone valves or  
balancing valves.  
3. Attach a hose to hose bib located just below  
isolation valve in boiler supply piping. (Note -  
Terminate hose in five gallon bucket at a suitable  
floor drain or outdoor area).  
4. Starting with one circuit, open zone valve.  
Figure 1ꢄ: Schematic Pilot and Gas Piping  
Continuous Ignition (Standing Pilot)  
5. Open hose bib.  
6. Open fill valve (Make-up water line should be  
located directly above isolation valve in boiler  
supply piping).  
7. Allow water to overflow from bucket until  
discharge from hose is bubble free for 30  
seconds.  
8. Open zone valve to the second zone to be purged,  
then close the first. Repeat this step until all  
zones have been purged, but always have one  
zone open. At completion, open all zone valves.  
9. Close hose bib, continue filling the system until  
the pressure gauge reads 12 psi. Close fill valve.  
(Note - If make-up water line is equipped with  
pressure reducing valve, system will  
automatically fill to 12 psi. Leave globe valve  
open).  
Figure 1ꢅ: Schematic Pilot and Gas Piping  
Electronic Ignition (EI)  
10. Open isolation valve in boiler supply piping.  
11. Remove hose from hose bib.  
boiler model found on Rating Label with paragraph  
heading:  
B. Turn ROOM ThERMOSTAT to lowest setting.  
C. Be sure that gas to pilot and main burners has been  
off for at least five minutes and vent damper (if  
used) has been in the open position.  
1. Standing Pilot Models (Suffix C):  
a. Keep electric switch "OFF".  
b. Open Manual Shut-off valve upstream of  
D. Turn "OFF" the electric switch serving boiler.  
E. Open valve on main gas line at meter.  
Combination Gas valve.  
c. Disconnect Pilot Tubing at gas valve (Purge  
F. PURGE AIR FROM GAS PIPING. This  
procedure will vary with equipment furnished but in  
all cases adequate ventilation must be provided  
and no smoking or open flame permitted. To  
determine which of the procedures outlined in  
succeeding paragraphs is applicable, match suffix of  
must not be into combustion chamber).  
d. Turn Main Gas Knob on Combination Gas  
valve to "Pilot" Position. Depress and hold  
in this position until purging is complete.  
Turn Main Gas Knob to "off" position.  
1ꢅ  
Figure 1ꢆ: Top View of VR Gas Valves  
Figure ꢀ0: Operating Instructions, VRꢅꢀ0ꢁ and VRꢅ30ꢁ Gas Valves  
1ꢆ  
e. Reconnect pilot tubing and check pipe and  
fittings from meter to combination Gas  
valve for leaks using soap solution or other  
approved method.  
2. Electronic Ignition Models (Suffix I):  
a. Turn "ON" electric switch serving boiler.  
b. Open Manual Shut-off valve upstream of  
Combination Gas valve.  
c. Loosen or remove Inlet Pressure Tap Plug in  
Combination Gas valve and when purging is  
complete, tighten or replace plug. See Figure  
19.  
d. Check pipe and fittings from meter to  
Combination Gas valve using soap solution  
or other approved methods.  
Figure ꢀ1: LED Locations  
CAUTION  
Table ꢂ: Ignition Module Terminal Cross-  
Reference  
e. Test gas piping and connections between  
Combination Gas valve and manifold,  
orifices, and pilot piping for leaks after  
boiler is operating. Use soap solution or  
other approved method.  
Ignition Module  
Wiring Ladder Diagram  
Terminal Designation  
Terminal Number  
MV  
MV/PV  
PV  
1
2
3
3. INSTRUCTIONS TO PUT ThE BOILER IN  
OPERATION.  
A. See Figure 20 for electronic ignition (EI).  
Electronic Ignition Modules with LED indicators.  
Table 5 cross-references the ignition module  
terminal designations to the ignition terminal  
numbers in the wiring ladder diagrams. The yellow  
LED indicates the status of the flame, see Table 6.  
The green LED indicates the status of the system,  
see Table 7. See Figure 21 for LED locations. See  
Figure 28 for Troubleshooting Guide.  
GND  
4
5
24V (GND)  
24V  
6
9
SPARK  
Table ꢃ: Yellow LED Flame Codes  
Yellow LED Flash  
Indicates  
Recommended Service Action  
N/A  
Codea  
Heartbeat  
Normal Flame Signal  
Weak Flame Signal -  
System will operate reliably but flame signal is less than  
desired.  
Note: This indication may flash temporarily during or  
shortly after lightoff on some applications.  
Perform routine maintenance to  
assure optimum flame signal.  
2
Marginal Flame Signal (less than 1.1 µA) -  
System may not operate reliably over time. Service call Check gas supply, pilot burner, flame sense  
1
recommended.  
wiring, contamination of flame rod, burner  
Note: This indication may flash temporarily during or  
shortly after lightoff on some applications.  
ground connection.  
No Flame or Flame Signal -  
below minimum threshold for system  
operation.  
OFF  
N/A  
aFlash Code Descriptions  
-
Heartbeat: Constant ½ second bright, ½ second dim cycles.  
The flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then repeats sequence.  
-
ꢀ0  
Table ꢄ: Green LED Status Codes  
Green LED  
Flash Code  
Indicates  
Next System Action  
Recommended Service Action  
(X + Y)a  
OFF  
No “Call for Heat”  
N/A  
N/A  
N/A  
None  
None  
None  
Startup - Flame sense  
calibration  
Flash Fast  
Heartbeat  
Normal operation  
If system fails to light on next trial  
for ignition check gas supply, pilot  
burner, spark and flame sense wir-  
ing, flame rod contamination or out  
of position, burner ground connec-  
tion.  
5 minute Retry Delay-  
Pilot flame not detected  
during trial for ignition  
Initiate new trial for ignition after retry  
delay completed.  
2
If system fails to light on next trial  
for ignition check gas supply, pilot  
burner, flame sense wiring, flame  
rod contamination, burner ground  
connection.  
Initiate new trial for ignition. Flash  
code will remain through the ignition  
trial until flame is proved.  
Recycle- Flame failed  
during run  
3
4
If situation self corrects within 10  
Check for pilot flame. Replace gas  
valve if pilot flame present. If no  
pilot flame, cycle “Call for Heat.” If  
error repeats, replace control.  
seconds, control returns to normal  
sequence. If flame out of sequence re-  
mains longer than 10 seconds, control  
goes to Flash code 6+4 (see below)  
Flame sensed out of  
sequence  
Check flame sense lead wire for  
Control remains in wait mode. When  
damage or shorting. Check that  
Flame sense leakage to  
ground  
7
8
the fault corrects, control resumes nor- flame rod is in proper position.  
mal operation after a one minute delay. Check flame rod ceramic for cracks,  
damage or tracking.  
Check transformer and AC line for  
Control remains in wait mode. When  
proper input voltage to the control.  
Low secondary voltage  
supply- (below 15.5 Vac)  
the fault corrects, control resumes nor-  
Check with full system load on the  
mal operation after one minute delay.  
transformer.  
Check gas supply, pilot burner, spark  
5 minute Retry Delay-  
On every third retry on  
same “Call for Heat”  
Initiate new trial for ignition after retry  
delay completed.  
and flame sense wiring, flame rod  
contamination or out of position,  
burner ground connection.  
6 + 2  
6 + 3  
6 + 4  
ON  
On every 6th flame  
failure during run on the  
same “Call for Heat”  
Check gas supply, pilot burner, flame  
sense wiring, contamination of flame  
rod, burner ground connection.  
5 minute retry delay, then initiate new  
trial for ignition.  
Control waits until flame is no longer  
sensed and then goes to soft lockout.  
Flash code continues. Control auto  
Check for pilot flame. Replace gas  
valve if pilot flame present. If no  
pilot flame, cycle “Call for Heat.” If  
Flame sensed out of  
sequence- longer than  
10 seconds  
resets from soft lockout after one hour. error repeats, replace control.  
Soft lockout due to error  
detected during self  
check sequences  
Control auto resets from soft lockout  
after one hour.  
Reset by cycling “Call for Heat.” If  
error repeats, replace the control  
aFlash Code Descriptions:  
-
-
-
Flash Fast: rapid blinking  
Heartbeat: Constant ½ second bright, ½ second dim cycles.  
A single flash code number signifies that the LED flashes X times at 2Hz, remains off for two seconds, and then  
repeats the sequence.  
-
X + Y flash codes signify that the LED flashes X times at 2Hz, remains off for two seconds, flashes Y times at 2  
Hz, remains off for three seconds, and then repeats the sequence.  
ꢀ1  
Figure ꢀꢀ: Lighting Instructions  
ꢀꢀ  
more accurate check on input is necessary see  
(2) below.  
B. See Figure 22 for continuous ignition system  
(standing pilot).  
For minor input changes readjust Regulator Gas  
valve to increase or decrease manifold pressure  
to obtain corresponding increase or decrease in  
gas input. If it is necessary to increase manifold  
pressure more than 0.3" of water to obtain rated  
input, remove orifices and drill one size larger.  
Reinstall and recheck input rate.  
4. ChECK GAS INPUT RATE TO BOILER  
NOTICE  
USA boilers built for installation at altitudes greater  
than 2,000 feet above sea level have been specially  
orificed to reduce gas input rate 4 percent per 1,000 feet  
above sea level per the National Fuel Gas Code, NFPA  
54/ANSI Z223.1, Section 8.1.2 and Appendix F.  
Canadian boilers' orifice sizing is indicated on the rating  
label. High altitude boiler models are identifiable by  
the fourth digit after the dash in the model number. 2:  
0-2000', 4 or 5: above 2000'.  
2. Additional Check on Input - Since input is a  
function of heating value, specific gravity, and  
volume of gas flow contact your utility for the  
first two items in order to utilize the formula  
below. The gas meter should then be clocked for  
three (3) minutes with stop watch and  
substituting the appropriate values in the formula  
below, determine what the gas flow should be in  
this 3 minute period to give the input shown on  
the Rating Label:  
A. Input Rate and Maximum Inlet Pressure shown on  
Rating Label must not be exceeded. Inlet pressure  
must not be lower than minimum inlet pressure  
shown on Rating Label.  
Gas Input  
(cu. ft.)  
Btuh Input  
B. All Rate checks and all adjustments are to be made  
while boiler is firing - all other appliances connected  
to the same meter as the boiler must be off.  
=
Heating  
Value  
Multiplier  
from  
per 3 min.  
X
of Gas  
Table 3  
C. With boiler off, water Manometer or water column  
gauge should be connected to a shut-off valve  
installed in the 1/8" outlet pressure tap in the gas  
valve (see Figure 19). By installing gas valve  
upstream of manometer, gas pressure can be  
introduced gradually - without shut-off valve, surge  
of pressure when boiler is turned on, could blow  
liquid out of manometer. Replace plug in gas valve  
when rate check is finished.  
(Btu / cu. ft.  
5. MAIN BURNER FLAMES should have a clearly  
defined inner cone (see Figure 23 or 24) with no yellow  
tipping. Orange-yellow streaks caused by dust should  
not be confused with true yellow tipping.  
D. LP Gas Input:  
Adjust Regulator on Gas valve so that manifold  
pressure is 10 inches water column. Turning  
Regulator Adjusting Screw Clockwise increases  
pressure. Counterclockwise rotation decreases  
pressure.  
Figure ꢀꢁ: 1 Inch Main Burner Flame  
The main burners in this boiler will not operate cleanly  
or efficiently if they are contaminated with dirt and/or  
construction dust. Burners should be cleaned and the  
combustion chamber vacuumed following instructions  
in Section Iv. Service.  
Figure ꢀ3: ꢁ0mm Main Burner Flame  
E. Natural Gas Input  
6. ChECK PILOT BURNER FLAME.  
A. Continuous Ignition (Standing Pilot)  
LP gas Models 202 and 202x. See Figure 25.  
1. Appx. Input - Adjust regulator on Gas valve so  
that manifold pressure is three and a half (3½)  
inches water column. Turning Regulator  
Natural gas Models 202 through 206 and 207 with  
1" diameter burners. See Figure 25.  
Adjusting Screw Clockwise increases pressure,  
Counterclockwise rotation decreases pressure. If  
ꢀ3  
Figure ꢀꢂ: Typical Pilot Flame, Honeywell Q3ꢂ0  
The pilot produces a single flame. The flame should  
be steady, medium hard blue enveloping 3/8 to a 1/2  
inch of thermocouple.  
Figure ꢀꢄ: Typical Pilot Flame, Honeywell Q3ꢁꢅA  
B. Continuous Ignition (Standing Pilot)  
7. ChECK ThERMOSTAT OPERATION. Raise and  
lower temperature setting as required to start and stop  
burners.  
Natural gas Models 207 with 40mm (1-9/16")  
diameter burners and 208 through 210.  
See Figure 26.  
8. ChECK hIGh LIMIT CONTROL. Jumper  
Thermostat Terminals or Thermostat connections in  
Limit Control. Allow burners to operate until shutdown  
by limit. REMOvE JUMPER.  
LP gas Models 203 through 210. See Figure 26.  
The pilot produces three (3) flames. The center  
flame should be steady, medium hard blue  
enveloping 3/8 to a 1/2 inch of thermocouple.  
9. ChECK DAMPER OPERATION. vent Damper must  
be open when boiler is running. Le registre doit être  
ouvert lorsque le brûleur principal de l’appareil  
fonctionne. Start boiler, refer to instructions on damper  
to determine if damper is in the full open position.  
10. ChECK IGNITION SYSTEM SAFETY ShUT-OFF  
DEvICE.  
A. 24 volt-loosen thermocouple at gas valve.  
B. Electronic Ignition - Remove pilot lead wires from  
gas valve.  
If burners do not shut down determine cause of  
malfunction. Replace necessary items and check  
operation.  
11. COMBUSTION ChAMBER BURN-OFF  
A. The mineral wool combustion chamber panels may  
contain a cornstarch based binder that must be  
burned out at installation to prevent odors during  
subsequent boiler operation.  
Figure ꢀꢃ: Typical Pilot Flame, Honeywell Q3ꢀꢄ  
C. Electronic Ignition (EI), see Figure 27.  
B. ventilate the boiler room, set the high limit to its  
maximum setting, set the thermostat to call for heat.  
Allow the boiler to fire for at least an hour or until  
the odor from the cornstarch has dissipated.  
The pilot produces three (3) flames. The center  
flame should be steady, medium hard blue  
enveloping 3/8 to a ½ inch of sensing probe.  
C. Return the high limit and thermostat to their desired  
settings.  
ꢀꢁ  
III. Trouble Shooting  
Honeywell Electronic Ignition Troubleshooting Guide  
Figure ꢀꢅ: Troubleshooting Guide, Honeywell Electronic Ignition (EI)  
ꢀꢂ  
IV. Service  
Reinstall Jacket Top Panel, draft hood, blocked vent  
switch, damper (if boiler is so equipped), and vent  
pipe.  
1. Inspection should be conducted annually. Service as  
frequently as specified in paragraphs below. While  
service or maintenance is being done, Electrical Power  
and all Gas Supply to the Boiler must be "off".  
If the flue passageways need cleaning, remove  
burners as described in paragraph 4 below. Using  
long handle wire or bristle flue brush and vacuum,  
brush flueways thoroughly from top of boiler as  
illustrated in Figure 29. Replace canopy and seal  
with boiler putty. Reinstall Jacket Top Panel, draft  
hood, blocked vent switch, damper (if boiler is so  
equipped), and vent pipe.  
CAUTION  
Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause  
improper and dangerous operation. Verify  
proper operation after servicing.  
ATTENTION. Au moment de l’entretien des  
commandes, étiquetez tous les fils avant  
de les débrancher. Les erreurs de câblage  
peuvent nuire au bon fonctionnement et être  
dangereuses.  
NOTICE  
4. BURNERS AND FIREBOx ShOULD BE CLEANED  
ANNUALLY, AND IF NECESSARY ADJUSTED  
ONCE A YEAR BY A QUALIFIED SERvICE  
AGENCY.  
S’assurer que l’appareil fonctionne  
adéquatement une fois l’entretien terminé.  
A. TO REMOvE BURNERS FOR CLEANING,  
ChANGING ORIFICE PLUGS, OR REPAIRS.  
1. Remove the jacket front panel.  
2. vENT SYSTEM. vent system (see Figure 8 for typical  
installation) should be checked annually for:  
A. Obstructions.  
2. Disconnect pilot tubing at the gas valve. See  
Figure 17.  
B. Accumulations of soot.  
3. Disconnect thermocouple (standing pilot) or pilot  
lead wires (electronic ignition) at the gas valve.  
4. 40mm burners only. Remove injection shield  
assembly, where used. See Figure 30.  
5. Remove wires to flame roll-out switch.  
6. Remove the burner access panel.  
7. Mark the location of the pilot main burner on the  
manifold if the marking on manifold is missing  
or obliterated.  
C. Deterioration of vent pipe or vent accessories due to  
condensation or other reasons.  
D. Proper support - no sags, particularly in horizontal  
runs.  
E. Tightness of joints.  
F. Proper vent damper operation - see Section II  
Operating Instructions, paragraph 9.  
G. Remove all accumulations of soot with wire brush  
and vacuum, see Figure 29. Remove all  
obstructions. Replace all deteriorated parts and  
support properly. Seal all joints.  
3. CLEANING BOILER FLUES, see Figure 29.  
Flue passageways in the boiler sections should be  
checked annually for any blockage or accumulation of  
soot. To obtain access to flueways:  
A. Remove vent pipe, damper (if boiler is so equipped),  
blocked vent switch, and draft hood.  
B. Remove sheet metal screws securing Jacket Top  
Panel, lift panel and rotate about relief valve piping  
until top of boiler is exposed.  
C. Remove bolts securing Canopy to Boiler Sections.  
Remove Canopy - flueways are now exposed.  
D. Models with flue gas baffles only: Remove baffles  
by lifting out of flueways.  
Using flashlight, examine all flue passageways. If  
passageways are free of soot and obstruction,  
replace canopy (and flue gas baffles, if applicable),  
and seal.  
Figure ꢀꢆ: Cleaning of Vent System  
and Boiler Flues  
ꢀꢃ  
8. hold burner at throat. Lift front of burner to  
clear orifice. Burner which holds pilot can only  
be removed by lifting the burner adjacent to its  
right first.  
If pilot assembly, thermocouple or pilot orifice need  
replacing, remove main burner with pilot using  
procedure described in paragraph 4.  
A. To replace orifice:  
1" Burner  
1. Disconnect pilot tubing. The honeywell Q350  
pilot orifices are insert type retained by the  
compression fitting. The Honeywell Q327 and  
Q348A pilot orifices are spud type screwed into  
pilot burner. Replace with desired orifice. See  
Key No. 5B.  
2. Reconnect pilot tubing and check for leaks.  
B. To replace honeywell Q309A thermocouple in  
Q327 or Q350 pilot:  
1. Loosen attachment nut securing thermocouple to  
barrel of pilot burner. Disconnect other end at  
combination gas valve.  
ꢁ0mm Burner  
2. Remove thermocouple and replace with equal.  
C. To replace complete pilot assembly.  
1. Remove machine screws holding pilot burner to  
pilot bracket.  
2. Disconnect pilot piping.  
3. Disconnect all other leads to pilot.  
4. Select pilot assembly with identical model  
number, reconnect leads and pilot tubing -  
resecure to pilot bracket.  
D. To adjust or check spark gap between electrode and  
hood on honeywell Q348A pilot.  
Figure 30: Burner Cleaning and Installation  
1. Use round wire gauge to check spark gap.  
2. Spark gap should be 1/8 inch for optimum  
performance.  
9. Brush top of burners with a soft bristle brush, see  
Figure 30. Vacuum burners. Check orifices to see  
that drilled passageways are free of lint or dirt.  
E. Reinstall main burner following procedure described  
in paragraph 4.  
10. vacuum tip of Pilot Burner.  
7. LUBRICATION  
B. CLEAN FIREBOx by vacuuming. Exercise care  
There are no parts requiring lubrication on the part of  
the service technician or the User. Circulator bearings  
are water lubricated.  
not to disturb insulation inside the base.  
C. INSTALL BURNERS by reversing procedure used  
to remove burners. Make sure burner with pilot  
assembly is in same location as original installation  
- see Table 8.  
Table ꢅ: Pilot Burner Location  
Pilot Burner Located  
Main Burner with  
Check burners to see that they are located properly  
in slot at rear of burner tray, see Figure 30.  
Reinstall injection shield assembly (40mm burners  
only, where used) and burner access panel.  
Reconnect flame roll-out switch wires, pilot gas  
supply, thermocouple lead or pilot lead.  
Between Main  
Boiler  
Pilot Bracket *  
Burners *  
Model  
1 Inch  
40mm  
1 Inch  
1 & 2  
1 & 2  
1 & 2  
2 & 3  
3 & 4  
4 & 5  
6 & 7  
7 & 8  
8 & 9  
9 & 10  
40mm  
---  
202  
202X  
203  
204  
205  
206  
207  
208  
209  
210  
1
1
1
2
3
4
6
7
8
9
1
1
1
2
2
3
3
4
4
5
1 & 2  
1 & 2  
2 & 3  
2 & 3  
3 & 4  
3 & 4  
4 & 5  
4 & 5  
5 & 6  
D. ChECK MAIN BURNER and PILOT FLAMES,  
see procedure Section II Operating Instructions,  
paragraphs 5 and 6.  
5. ChECK ALL CONTROL AND DAMPER  
OPERATION ANNUALLY see procedure in Section II  
Operating Instructions, paragraphs 7 through 10.  
6. REMOvAL OR REPLACEMENT OF PILOT  
ASSEMBLY OR PILOT ASSEMBLY PARTS  
* Main burners numbered left to right as viewed from  
front of boiler.  
ꢀꢄ  
Important Product Safety Information  
Refractory Ceramic Fiber Product  
Warning:  
The Repair Parts list designates parts that contain refractory ceramic fibers  
(RCF). RCF has been classified as a possible human carcinogen. When  
exposed to temperatures about 1805°F, such as during direct flame contact,  
RCF changes into crystalline silica, a known carcinogen. When disturbed as a  
result of servicing or repair, these substances become airborne and, if inhaled,  
may be hazardous to your health.  
AVOID Breathing Fiber Particulates and Dust  
Precautionary Measures:  
Do not remove or replace RCF parts or attempt any service or repair work  
involving RCF without wearing the following protective gear:  
1. A National Institute for Occupational Safety and Health (NIOSH)  
approved respirator  
2. Long sleeved, loose fitting clothing  
3. Gloves  
4. Eye Protection  
• Take steps to assure adequate ventilation.  
• Wash all exposed body areas gently with soap and water after contact.  
• Wash work clothes separately from other laundry and rinse washing  
machine after use to avoid contaminating other clothes.  
• Discard used RCF components by sealing in an airtight plastic bag. RCF  
and crystalline silica are not classified as hazardous wastes in the United  
States and Canada.  
First Aid Procedures:  
• If contact with eyes: Flush with water for at least 15 minutes. Seek  
immediate medical attention if irritation persists.  
• If contact with skin: Wash affected area gently with soap and water.  
Seek immediate medical attention if irritation persists.  
• If breathing difficulty develops: Leave the area and move to a location  
with clean fresh air. Seek immediate medical attention if breathing  
difficulties persist.  
• Ingestion: Do not induce vomiting. Drink plenty of water. Seek  
immediate medical attention.  
ꢀꢅ  
V. Repair Parts  
Section Assembly and Canopy Group............................30  
Base Assembly ..................................................................32  
Manifold and Main Burners  
1 Inch Main Burners..................................................34  
40mm Main Burners..................................................36  
Pilot Burner and Gas Valve  
Continuous Ignition (Standing Pilot) .......................38  
Electronic Ignition .....................................................40  
Jacket Assembly ...............................................................41  
Water Trim .......................................................................44  
Controls.............................................................................46  
Draft Hood and Vent Damper.........................................47  
Quantity  
202 202X 203 204 205 206 207 208 209 210  
Key  
Description  
No.  
Part No.  
1. Section Assembly (Intermittent and Continuous Circulation Only)  
617170221  
617170321  
617170421  
617170521  
617170621  
617170721  
617170821  
617170921  
617171021  
1
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
1
Section Assembly, Complete  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
1. Section Assembly (Gravity Circulation Only)  
617170231  
1
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
617170331  
617170431  
617170531  
617170631  
617170731  
617170831  
617170931  
617171031  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
1
Section Assembly, Complete  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
ꢀꢆ  
Quantity  
Key  
No.  
Description  
Part No.  
202 202X 203 204 205 206 207 208 209 210  
ꢀ. Canopy Group  
61117022  
611170300  
611170302  
611170402  
611170502  
611170602  
611170702  
611170802  
611170902  
611171002  
6111706010  
80860115  
80860603  
80860407  
6206001  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
---  
2
---  
---  
---  
---  
---  
---  
---  
2
Canopy Assembly (except for 206H)  
---  
---  
---  
---  
---  
---  
2
2A  
---  
---  
---  
---  
1
---  
---  
---  
---  
2
---  
---  
---  
2
---  
---  
2
Canopy Assembly 206H  
---  
2
2B Carriage Bolt, 1/4-20 x 1"  
2C Flat Washer, 1/4"  
2
2
2
2
2
2
2
2
2
2
2
2D Nut, Hex, 1/4-20  
2
2
2
2
2
2
2
2
2
2
2E Cerafelt Sealing Strip, 1/2" x 1" x 10'  
1
1
1
1
1
1
1
1
1
1
Flue Gas Baffle (*Standing Pilot 1"  
Burners Only)  
(** LP Standing Pilot 1" Burners Only)  
2F  
71106001  
1***  
---  
2**  
3**  
4**  
5**  
6**  
7*  
8*  
9*  
(*** Standing Pilot Models Only)  
Section Assembly and Canopy Group  
30  
THIS PAGE LEFT INTENTIONALLY BLANK  
31  
Base Assembly  
Key  
No.  
Boiler  
Size  
Key  
No.  
Boiler  
Size  
Description  
Part No. Qty.  
Description  
Part No.  
Qty.  
3. Base Assembly Continued  
3. Base Assembly  
202  
718600211  
718600311  
718600311  
718600411  
718600511  
718600611  
718600711  
718600811  
718600911  
718601011  
720601  
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
202  
202X  
203  
204  
205  
206  
207  
208  
209  
210  
202  
202X  
203  
204  
205  
206  
207  
208  
209  
210  
618600291  
618600391  
618600391  
618600491  
618600591  
618600691  
618600791  
618600891  
618600991  
618601091  
718600291  
718600391  
718600391  
718600491  
718600591  
718600691  
718600791  
718600891  
718600991  
718601091  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
202X  
203  
204  
205  
206  
207  
208  
209  
210  
All  
Base Assembly  
(Complete)  
Available for 1 Inch  
3B Base Wrapper  
3
Burners Only  
3B1 Base End Insulation  
202  
202X  
203  
204  
205  
206  
207  
208  
209  
210  
72060025  
72060035  
72060035  
72060045  
72060055  
72060065  
72060075  
72060085  
72060095  
72060105  
3A Base Tray  
3B2 Base Rear Insulation  
3ꢀ  
Key  
No.  
Boiler  
Size  
Key  
No.  
Boiler  
Size  
Description  
Part No. Qty.  
Description  
Part No. Qty.  
3. Base Assembly Continued  
3. Base Assembly Continued  
3E Base Leg Assembly  
3E1 Base Leg  
All  
6186001  
71860021  
8186006  
4
4
4
202  
618600241  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
All  
All  
202X 618600341  
3E2 Nylon Glide  
203  
204  
205  
206  
207  
208  
209  
210  
202  
618600341  
618600441  
618600541  
618600641  
618600741  
618600841  
618600941  
618601041  
718600205  
202  
718600261  
1
1
1
1
1
1
1
1
1
1
202X 718600361  
Base Front Panel  
Assembly  
3C  
203  
204  
205  
206  
207  
208  
209  
210  
718600361  
718600461  
718600561  
718600661  
718600761  
718600861  
718600961  
718601061  
3F Burner Access Panel  
202X 718600305  
203  
204  
205  
206  
207  
208  
209  
210  
202  
202X  
203  
204  
205  
206  
207  
208  
209  
210  
718600305  
718600405  
718600505  
718600605  
718600705  
718600805  
718600905  
718601005  
718600206  
71806037  
71806037  
71806047  
71806057  
71806067  
71806077  
718600806  
718600906  
718601006  
Cerafelt Sealing Strip,  
3G 1" x 2" x 10' (Section  
Assembly to Base)  
All  
6206002  
1
Burner Tray (1" Main  
Burners)  
202  
thru  
206  
80860700  
80860700  
20  
21  
Self-Tapping Screw,  
1/4" -20 x 1/2"  
3H  
207  
thru  
210  
3D  
Self-Tapping Screw,  
3J  
All  
All  
80860717  
80860601  
4
4
5/16" -18 x 1-1/4"  
Flat Washer, 5/16",  
USS  
3K  
Hex Lock Nut,  
5/16 -18  
3L  
All  
80860464  
4
Burner Tray  
(40mm Main Burners)  
33  
Manifold and Main Burners  
(1 Inch Main Burners)  
3ꢁ  
Quantity  
Key  
No.  
Description  
Part No.  
202 202X 203 204 205 206 207 208 209 210  
ꢁ. Manifold and Main Burners (1 Inch Main Burners Only)  
4A Main Burner  
8236099  
-----  
1
2
2
4
6
8
11  
13  
15  
17  
4B Main Burner with Pilot Bracket  
See Table Below  
82260023  
82260033  
82260043  
82260053  
82260063  
82260073  
82260083  
82260093  
82260103  
-----  
1
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
4C Manifold  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
4D Main Burner Orifice  
See Table Below  
Screw, Machine, Slotted Round Head,  
#10 -32 x 3/16" (Standing Pilot)  
80860800  
80860874  
80860700  
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
2
1
4
4E  
Screw, Machine, Philips Head  
w/Captive Lockwasher, #10 -32 x 1/4"  
(Electronic Ignition)  
Screw, Self Tapping, Philips Pan  
Head, 1/4 - 20 x 1/2"  
4F  
ꢁB. 1 Inch Main Burner with Pilot Bracket, ꢀꢁ-volt Continuous Ignition (Standing Pilot) Natural Gas Only  
Main Burner with 70° Q350 Pilot  
Bracket and Offset Lancings  
8236097  
8236098  
1
1
1
1
1
1
1
---  
1
---  
1
---  
1
4B  
Main Burner with 60° Pilot Bracket  
---  
---  
---  
---  
---  
---  
---  
ꢁB. 1 Inch Main Burner with Pilot Bracket, ꢀꢁ-volt Continuous Ignition (Standing Pilot) LP Gas Only  
4B Main Burner with 45° Pilot Bracket  
8236111  
---  
---  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
ꢁB. ꢅ Inch Main Burner with Pilot Bracket, Electronic Ignition Only  
4B Main Burner with 60° Pilot Bracket  
8236098  
1
1
4D. 1 Inch Main Burner Orifices, Natural Gas, Normal Altitude, U.S.A. and Canada  
Main Burner Orifice, #47 (White)  
Main Burner Orifice, #45 (Pink)  
822710  
822711  
2
3
---  
3
---  
5
---  
7
---  
9
12  
---  
14  
---  
16  
---  
18  
---  
4D  
---  
---  
4D. 1 Inch Main Burner Orifices, LP/Propane, Normal Altitude, U.S.A. and Canada  
Main Burner Orifice, 1.25 mm (Purple)  
4D Main Burner Orifice, #55 (Green)  
Main Burner Orifice, 3/64" (Blue)  
822705  
822708  
822704  
2
---  
---  
3
---  
3
5
7
9
---  
---  
12  
---  
---  
14  
---  
---  
16  
---  
---  
18  
---  
---  
---  
---  
---  
---  
---  
---  
---  
3ꢂ  
Manifold and Main Burners  
(ꢁ0mm Main Burners)  
Quantity  
202X 203 204 205 206 207 208 209 210  
Key  
No.  
Description  
Part No.  
ꢁ. ꢁ0 MM Main Burners Only  
4A  
Main Burner  
8236135  
1
1
2
3
4
5
6
7
8
ꢁB. ꢁ0 MM Main Burner, Electronic Ignition Only  
Main Burner with 48° Pilot Bracket  
Main Burner with 41° Pilot Bracket  
8236143  
8236136  
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
4B  
ꢁB. ꢁ0 MM Main Burner, ꢀꢁ-volt Continuous Ignition (Standing Pilot) Natural Gas Only  
Main Burner with 48° Pilot Bracket  
Main Burner with 41° Pilot Bracket  
8236143  
8236136  
1
1
1
1
1
1
1
1
1
4B  
---  
---  
---  
---  
---  
---  
---  
---  
---  
ꢁB. ꢁ0 MM Main Burner, ꢀꢁ-volt Continuous Ignition (Standing Pilot) LP Gas Only  
Main Burner with 48° Pilot Bracket  
Main Burner with 41° Pilot Bracket  
8236143  
8236136  
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
4B  
---  
3ꢃ  
Quantity  
Key  
No.  
Description  
Part No.  
202X 203 204 205 206 207 208 209 210  
ꢁ. ꢁ0 MM Main Burners Only (Continued)  
ꢁC. ꢁ0MM Main Burner Manifold  
82260028  
82260038  
82260048  
82260058  
82260068  
82260078  
82260088  
82260098  
82260108  
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
4C  
Manifold  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
ꢁD. ꢁ0 MM Main Burner, Natural Gas, ꢀ001-ꢂ000 Ft. USA Only  
#43  
#39  
#38  
822713  
822727  
822720  
2
---  
2
---  
3
---  
---  
4
---  
---  
5
---  
---  
6
---  
---  
7
---  
---  
8
---  
---  
9
4D  
---  
---  
---  
---  
ꢁD. ꢁ0 MM Main Burner, LP Gas, ꢀ001-ꢂ000 Ft. USA Only  
#54  
#53  
822734  
822722  
2
---  
2
---  
3
---  
4
---  
5
---  
6
---  
7
---  
8
---  
9
4D  
---  
ꢁD. ꢁ0 MM Main Burner, Natural Gas, ꢂ001-ꢆ000 Ft. USA Only  
#41  
#40  
822729  
822728  
N/A  
---  
2
3
---  
4
---  
5
---  
6
---  
7
---  
8
---  
9
4D  
---  
---  
ꢁD. ꢁ0 MM Main Burner, LP Gas, ꢂ001-ꢆ000 Ft. USA Only  
#54  
#53  
822734  
822722  
N/A  
---  
2
---  
3
---  
4
---  
5
---  
6
---  
7
---  
8
---  
9
4D  
---  
ꢁD. ꢁ0 MM Main Burner, Natural Gas, ꢀ001-ꢁꢂ00 Ft. Canada Only  
#37  
#36  
822719  
822771  
N/A  
---  
2
3
4
---  
5
---  
6
---  
7
---  
8
---  
9
4D  
---  
---  
---  
ꢁD. ꢁ0 MM Main Burner, LP Gas, ꢀ001-ꢁꢂ00 Ft. Canada Only  
4D  
#52  
822721  
N/A  
2
2
2
3
2
4
2
5
2
6
2
7
2
8
2
9
2
Screw, Machine, Slotted Round Head,  
#10-32 x 3/16" (Standing Pilot)  
80860800  
4E  
Screw, Machine, Philips Head  
w/Captive Lockwasher, #10-32 x 1/4"  
(Electronic Ignition)  
80860874  
1
1
4
1
4
1
4
1
4
1
4
1
4
1
4
1
4
Screw, Self Tapping, Philips Pan Head,  
1/4 -20 x 1/2"  
4F  
80860700  
4
4G  
Injection Shield Assembly  
71860_ _62  
A/R  
A/R A/R A/R A/R A/R A/R A/R A/R  
_ _: number of cast iron sections  
3ꢄ  
* 1" Burner Only  
** ꢁ0mm Burner Only  
Quantity  
Key  
No.  
Description  
Part No.  
202 202X 203 204 205 206 207 208 209 210  
ꢂ. Pilot Burner and Gas Valve, ꢀꢁ-volt Continuous Ignition, Natural Gas (1 Inch and ꢁ0mm Main Burners)  
Pilot Burner, Honeywell Q350A1321  
Pilot Burner, Honeywell Q327A1006  
Pilot Orifice, Honeywell 390686-22 .012"  
Pilot Orifice, Honeywell 388146AG .026"  
8236065  
8236022  
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
1
*1  
**1  
---  
1
---  
1
---  
1
---  
1
5A  
5B  
---  
1
---  
1
---  
1
Included  
with 5A  
---  
2
---  
2
---  
2
---  
2
---  
2
---  
2
5C Adptr, 1/4"OD x 1/4" NPT Included w/5A & 5E 8236109  
2
2
2
2
Pilot Tubing, 1/4" OD x 30" LG  
8236122  
8236123  
81660143  
1
1
1
1
1
1
1
---  
1
---  
1
---  
1
5D  
5E  
Pilot Tubing, 1/4" OD x 40" LG  
---  
1*  
---  
1*  
---  
1**  
---  
1
---  
1*  
---  
---  
1*  
---  
---  
1*  
---  
---  
1*  
---  
---  
---  
1*  
---  
Gas Valve, Honeywell VR8200C3005  
Gas Valve, Honeywell VR8300C4027  
Gas Valve, Honeywell VR8200C6065  
Gas Valve, Honeywell VR8300C4266  
---  
1*  
---  
---  
1*  
---  
---  
1*  
---  
81660154 ---  
100333-01 1**  
100334-01 ---  
1** 1** 1** 1**  
---  
1
---  
1
---  
1
---  
1
1** 1** 1** 1**  
5F Thermocouple, 30", Honeywell Q309A  
8236024  
1
1
1
1
1
3ꢅ  
Quantity  
Key  
No.  
Description  
Part No.  
202 202X 203 204 205 206 207 208 209 210  
5. Pilot Burner and Gas Valve, 24-volt Continuous Ignition, LP/Propane (1 Inch and 40mm Main Burners)  
Pilot Burner, Honeywell Q327A1147  
8236023  
---  
---  
1
1
1
1
1
1
1
1
5A  
5B  
Pilot Burner Assembly, Honeywell Q350A  
(Includes 5B & 5F)  
8236105  
1
1
---  
---  
---  
---  
---  
---  
---  
---  
Pilot Orifice, Honeywell 388146KR (.014")  
Pilot Orifice, Honeywell 390686-23 (.008")  
---  
1
---  
1
1
---  
2
1
---  
2
1
---  
2
1
---  
2
1
---  
2
1
---  
2
1
---  
2
1
---  
2
Included  
with 5A  
5C Adptr, 1/4"OD x 1/4" NPT Included w/5A & 5E 8236109  
2
2
Pilot Tubing, 1/4" OD x 30" LG  
8236122  
8236123  
81660144  
1
1
1
1
1
1
1
---  
1
---  
1
---  
1
5D  
5E  
Pilot Tubing, 1/4" OD x 40" LG  
---  
1
---  
1
---  
1
---  
1
---  
1
---  
1
---  
---  
1
Gas Valve, Honeywell VR8200C3013  
Gas Valve, Honeywell VR8300C4035  
---  
1
---  
1
---  
1
81660163 ---  
8236024  
---  
1
---  
1
---  
1
---  
1
---  
1
5F Thermocouple, 30", Honeywell Q309A  
1
1
1
1
1
3ꢆ  
Quantity  
Key  
No.  
Description  
Part No.  
202 202X 203 204 205 206 207 208 209 210  
ꢂ. Pilot Burner and Gas Valve, Electronic Ignition (EI), Natural Gas  
5A Pilot Burner, Honeywell Q348A1002  
8236072  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Included  
with 5A  
5B Pilot Orifice, Honeywell 388146NE  
Compression Nut/Fitting, 1/4" OD x 1/4 C.C.  
(Included with 5A and 5E)  
5C  
8236109  
2
2
2
2
2
2
2
2
2
2
Pilot Tubing, 1/4" OD x 30"  
5D  
8236122  
8236123  
81660145  
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
1
1
---  
---  
1
---  
1
---  
1
---  
1
Pilot Tubing, 1/4" OD x 40"  
Gas Valve, Honeywell VR8204C3007  
5E  
---  
1
---  
1
---  
1
Gas Valve, Honeywell VR8304P4306  
81660161 ---  
---  
---  
---  
---  
---  
5F Igniter/Sensor Cable, 36", Honeywell 394800  
5G Ground Wire Assembly  
8236084  
6136054  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
5. Pilot Burner and Gas Valve, Electronic Ignition (EI), LP/Propane  
5A Pilot Burner, Honeywell Q348A1010  
8236081  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
Included  
with 5A  
5B Pilot Orifice, Honeywell 388146KP  
Compression Nut/Fitting, 1/4" OD x 1/4 C.C.  
(Included with 5A and 5E)  
5C  
8236109  
2
2
1
2
1
2
1
2
1
2
1
2
1
2
2
2
Pilot Tubing, 1/4" OD x 30"  
5D  
8236122  
8236123  
81660146  
1
---  
1
---  
---  
---  
Pilot Tubing, 1/4" OD x 40"  
---  
1
---  
1
---  
1
---  
1
---  
1
---  
---  
1
1
---  
1
1
---  
1
1
---  
1
Gas Valve, Honeywell VR8204C3015  
5E  
Gas Valve, Honeywell VR8304P4314  
81660160 ---  
---  
1
---  
1
---  
1
---  
1
---  
1
5F Igniter/Sensor Cable, 36", Honeywell 394800  
5G Ground Wire Assembly  
8236084  
6136054  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
ꢁ0  
Quantity  
Key  
No.  
Description  
Part No.  
202 202X 203 204 205 206 207 208 209 210  
ꢃ. Jacket Assembly, Complete  
604170254  
604170354  
604170454  
604170554  
604170654  
604170754  
604170854  
604170954  
604171054  
1
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
6
Jacket Assembly, Complete  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
ꢃ. Jacket Assembly  
604170215  
604170315  
604170415  
604170515  
604170615  
604170715  
604170815  
604170915  
604171015  
1
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
6A  
Jacket Wrap-Around Panel  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
ꢁ1  
ꢁꢀ  
Quantity  
Key  
No.  
Description  
Part No.  
202 202X 203 204 205 206 207 208 209 210  
ꢃ. Jacket Assembly (Continued)  
604170223  
604170323  
604170423  
604170523  
604170623  
604170723  
604170823  
604170923  
604171023  
604170233  
604170333  
604170433  
604170533  
604170633  
604170733  
604170833  
604170933  
604171033  
604170242  
604170342  
604170442  
604170542  
604170642  
604170742  
604170842  
604170942  
604171042  
604170216  
604170316  
604170416  
604170516  
604170616  
604170716  
604170816  
604170916  
604171016  
1
---  
1
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
6B  
6C  
6D  
Jacket Vestibule Panel  
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
Jacket Top Panel  
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
Jacket Front Removable Door  
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
6E  
6F  
Jacket Lower Front Panel  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
Sheet Metal Screw, Type AB, Phillips  
Truss Head, #8 x 1/2"  
80860000  
26  
26  
26  
26  
26  
26  
26  
26  
26  
26  
6G Snap Bushing, Heyco SB-1093-15  
6H Snap Bushing, Heyco SB-437-5  
8136257  
8136048  
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
ꢁ3  
Water Trim  
ꢁꢁ  
Key  
No.  
Description  
Part No.  
Quantity  
Safety Relief Valve, 30 psi, 3/4 NPT, Conbraco 10-408-05  
Safety Relief Valve, 50 psi, 3/4 NPT, Conbraco 10-303-10  
81660319  
101662-01  
1
1
7
ꢅ. Circulator, Bell & Gossett SLC-30 Option (Intermittent and Continuous Circulation Only)  
8A  
8B  
Circulator with Gaskets, Bell & Gossett NRF-22  
Gasket, Bell & Gossett NRF-22  
8056174  
1
2
806602029  
ꢅ. Circulator, Grundfos Option (Intermittent and Continuous Circulation Only)  
8A  
8B  
Circulator with Gaskets, Grundfos UP 15-42F  
Gasket, Grundfos 510179  
8056173  
1
2
806602016  
ꢅ. Circulator, Taco 00ꢄ Option (Intermittent and Continuous Circulation Only)  
8A  
8B  
Circulator with Gaskets, Taco 007F  
Gasket, Taco '00' Series  
8056170  
1
2
806602006  
ꢅ. Circulator, Taco 0010 Option (Intermittent and Continuous Circulation Only)  
8A  
8B  
Circulator with Gaskets, Taco 0010  
Gasket, Taco '00' Series  
8056176  
1
2
806602006  
ꢆ. Miscellaneous Circulator Hardware (Intermittent and Continuous Circulation Only)  
9A  
9B  
9C  
Flange, 1-1/4 NPT  
806602013  
80861301  
80860406  
2
4
4
Screw, Cap Hex Head, 7/16 -14 x 1-1/2"  
Nut, Hex, 7/16 -14  
10. Limit Control  
10A  
10B  
10C  
10D  
Limit, Honeywell L4080D1234  
100189-01  
----  
1
1
1
1
Well, 1/2 NPT (Included w/10A)  
Limit, Honeywell L4080B1212 (Dual Limit Only)  
Well, 3/4 NPT, Honeywell 123870A (Dual Limit Only)  
80160474  
80160426  
11. Miscellaneous Trim  
11A  
11B  
11C  
11D  
11E  
Drain Valve, Conbraco 35-302-03  
806603061  
8056164U  
806600005  
806601002  
806600028  
1
1
Temperature - Pressure Gauge  
Nipple, 1-1/4 NPT x 3"  
1 or 2  
1 or 2  
1
Tee, 1-1/4 x 3/4 x 1-1/4 NPT  
Nipple, 1-1/4 NPT x 4"  
ꢁꢂ  
Key  
No.  
Description  
Part No.  
Quantity  
12. Transformer/Relay Assembly (Intermittent Circulation Only)  
12A Junction Box, 4" x 4" x 1-1/2"  
8136259  
80160155U  
80160096U  
1
1
1
12B Transformer/Relay, Honeywell R8285D5001  
12C Relay, Honeywell R8222U1006  
1ꢀ. Transformer (Continuous and Gravity Circulation Only)  
12A Junction Box, 4" x 4" x 1-1/2"  
8136259  
1
1
12D Transformer, 40VA, Honeywell AT140D1012 or AT72D1188  
13. Flame Rollout Switch  
80160039  
13A Flame Rollout Switch  
80160044  
7186018  
1
1
13B Flame Rollout Switch Mounting Bracket  
1ꢁ. Blocked Vent Switch  
14  
Blocked Vent Switch Replacement Assembly  
6016058  
1
1ꢂ. Ignition Module (EI Only)  
15A Ignition Module, Honeywell S8610M3009  
15B Ignition Module Support Bracket  
100958-01  
7016001  
1
1
ꢁꢃ  
Quantity  
Key  
No.  
Description  
Part No.  
202 202X 203 204 205 206 207 208 209 210  
1ꢃ. Draft Hood Carton  
8116067  
8111702  
8111703  
8111704  
8111705  
1
1
1
---  
1
---  
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
16  
Draft Hood  
---  
---  
---  
---  
---  
---  
---  
---  
---  
1ꢄ. Vent Damper  
4"  
5"  
8116321  
8116322  
8116323  
8116324  
8116325  
1
1
1
---  
1
---  
---  
1
---  
---  
1
---  
---  
---  
1
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
17  
6"  
7"  
8"  
---  
---  
---  
---  
---  
---  
---  
---  
---  
1ꢅ. Vent Reducer  
18  
Reducer, 4" x 3"  
1
---  
---  
---  
---  
---  
---  
---  
---  
---  
---  
ꢁꢄ  
SERVICE RECORD  
DATE  
SERVICE PERFORMED  
ꢁꢅ  
SERVICE RECORD  
DATE  
SERVICE PERFORMED  
ꢁꢆ  
SERVICE RECORD  
DATE  
SERVICE PERFORMED  
ꢂ0  
VI. Low Water Cut Off (LWCO)  
WARNING  
DO NOT ATTEMPT to cut factory wires to install an aftermarket Low Water Cut Off (LWCO). Only use  
connections specifically identified for Low Water Cut Off.  
In all cases, follow the Low Water Cut Off (LWCO) manufacturer's instructions.  
manufacturers recommend an annual inspection of the  
probe.  
When  
A low water cutoff is required to protect a hot water  
boiler when any connected heat distributor (radiation) is  
installed below the top of the hot water boiler (i.e.  
baseboard on the same floor level as the boiler). In  
addition, some jurisdictions require the use of a LWCO  
with a hot water boiler.  
How to Wire  
LWCO’s are available in either 120 vAC or 24 vAC  
configurations. The 120 VAC configuration can be  
universally applied to both gas and oil boilers by wiring  
it in the line voltage service to the boiler (after the  
service switch, if so equipped).  
Where  
The presence of water in a properly installed LWCO  
will cause the normally open contact of the LWCO to  
close, thus providing continuity of the 120 vAC service  
to the boiler.  
It is recommended to supply power to the probe LWCO  
with the same line voltage boiler service as shown  
below.  
The universal location for a LWCO on both gas and oil  
hot water boilers is above the boiler, in either the supply  
or return piping. The minimum safe water level of a  
water boiler is at the uppermost top of the boiler; that is,  
it must be full of water to operate safely.  
What Kind  
Typically, in residential applications, a probe type  
LWCO is used instead of a float type, due to their  
relative costs and the simplicity of piping for a probe  
LWCO.  
How to Pipe  
A “tee” is commonly used to connect the probe LWCO  
to the supply or return piping, as shown below.  
Wiring of Typical LWCO  
A 24 VAC LWCO is used primarily for gas fired boilers  
where a 24 volt control circuit exists within the boiler.  
however, a 24 vAC LWCO can only be used if the  
boiler manufacturer has provided piping and wiring  
connections and instructions to allow for this  
application.  
LWCO Location  
Select the appropriate size tee using the LWCO  
manufacturer’s instructions. Often, the branch  
connection must have a minimum diameter to  
prevent bridging between the probe and the tee. Also,  
the run of the tee must have a minimum diameter to  
prevent the end of the probe from touching or being  
located too close to the inside wall of the run of the tee.  
How to Test  
Shut off fuel supply. Lower water level until water  
level is BELOW the LWCO. Generate a boiler demand  
by turning up thermostat. Boiler should not attempt to  
operate. Increase the water level by filling the system.  
The boiler should attempt to operate once the water  
level is above the LWCO.  
Ideally, manual shutoff valves should be located above  
the LWCO and the boiler to allow for servicing. This  
will allow probe removal for inspection without  
draining the heating system. Many probe LWCO  
ꢂ1  
Limited Warranty  
FOR RESIDENTIAL CAST IRON WATER BOILERS  
Subject to the terms and conditions set forth below, U.S. Boiler  
boiler for its intended purposes and its maintenance accordance with U.  
S. Boiler Co., Inc. recommendations and hydronics industry standards.  
These warranties will be inapplicable if the residential grade water boiler  
is used or operated over its rated capacity, is subjected to unauthorized  
modification, or is damaged as a result of being otherwise improperly  
operated or serviced including, but not limited to, damage from any of the  
following: operation with insufficient water, allowing the boiler to freeze,  
subjecting the boiler to flood conditions, and operation with unapproved  
water or fuel additives which cause deposits or corrosion.  
Co., Inc. Lancaster, pennsylvania hereby extends the following limited  
warranties to the original owner of a residential grade water boiler  
manufactured and shipped on or after July 1,1991:  
ONEYEAR LIMITED WARRANTY  
ON RESIDENTIAL GRADE WATER BOILERS  
U.S. Boiler Co., Inc. warrants to the original owner that its residential  
grade water boilers comply at the time of manufacture with recognized  
hydronic industry standards and requirements then in effect and will be  
free of defects in material and workmanship under normal usage for a  
period of one year from the date of original installation. If any part of a  
water boiler is found to be defective in material or workmanship during  
this one year period, U.S. Boiler Co., Inc. will, at its option, repair or  
replace the defective part.  
5. Removal and Installation: These warranties do not cover expenses  
of removal or reinstallation. The owner is responsible for the cost of  
removing and reinstalling any defective part and its replacements and all  
labor and material connected therewith.  
6. Exclusive Remedy: U.S. Boiler Co., Inc. obligation for any breach of  
these warranties is limited to the repair or replacement of its parts in  
accordance with the terms and conditions of these warranties.  
LIFETIME LIMITED WARRANTY ON HEAT EXCHANGER  
7. Limitation of Damages: Under no circumstances shall U.S. Boiler Co.,  
Inc. be liable for incidental, indirect, special or consequential damages  
of any kind whatsoever under these warranties, including, but not limited  
to, injury or damage to persons or property and damages for loss of use,  
inconvenience or loss of time. U.S. Boiler Co., Inc. liability under these  
warranties shall under no circumstances exceed the purchase price paid  
by the owner for the residential grade water boiler involved. Some states  
do not allow the exclusion or limitation of incidental or consequential  
damages, so the above limitation or exclusion may not apply to you.  
U.S. Boiler Co., Inc. warrants to the original owner that the heat  
exchanger of its residential grade water boilers will remain free from  
defects in material and workmanship under normal usage for the  
lifetime of the original owner at the original place of installation. If a  
claim is made under this warranty during the first ten years from the  
date of original installation, U.S. Boiler Co., Inc. will, at its option, repair  
or replace the heat exchanger. If a claim is made under this warranty  
after the expiration of ten years from the date of original installation,  
U.S. Boiler Co., Inc. will, at its option and upon payment of the pro-rated  
service charge set forth below, repair or replace the heat exchanger.  
The service charge applicable to a heat exchanger warranty claim is  
based upon the number of years the heat exchanger has been in service  
and will be determined as a percentage of the retail price of the heat  
exchanger model involved at the time the warranty claim is made as  
follows:  
8. Limitation of Warranties: These warranties set forth the entire  
obligation of U.S. Boiler Co., Inc. with respect to any defect in a  
residential grade water boiler and U.S. Boiler Co., Inc. shall have no  
express obligations, responsibilities or liabilities of any kind  
whatsoever other than those set forth herein. These warranties are given  
in lieu of all other express warranties.  
ALL AppLICABLE ImpLIED WARRAnTIES, If Any, InCLUDIng  
Any WARRAnTy of mERChAnTABILITy oR fITnESS foR A  
pARTICULAR pURpoSE ARE ExpRESSLy LImITED In DURATIon  
To A pERIoD of onE yEAR ExCEpT ThAT ImpLIED WARRAnTIES,  
If Any, AppLICABLE To ThE hEAT ExChAngER In A RESIDEnTIAL  
gRADE WATER BoILER ShALL ExTEnD To ThE oRIgInAL  
oWnER foR ThE LIfETImE of ThE oRIgInAL oWnER AT ThE  
oRIgInAL pLACE of InSTALLATIon. SomE STATES Do no ALLoW  
LImITATIon on hoW Long An ImpLIED WARRAnTy LASTS, So  
ThE ABovE LImITATIon mAy noT AppLy To yoU.  
Years  
In Service  
1-10  
11  
5
12  
10  
13  
15  
14  
20  
15  
25  
16  
30  
17  
35  
Service Charge  
as % of  
Retail Price  
No  
Charge  
Years  
In Service  
25 and  
above  
18  
40  
19  
45  
20  
50  
21  
55  
22  
60  
23  
65  
24  
70  
Service Charge  
as % of  
75  
Retail Price  
PROCEDURE FOR OBTAINING WARRANTY SERVICE  
In order to assure prompt warranty service, the owner is requested to  
complete and mail the attached Warranty Card within ten days after the  
installation of the boiler, although failure to comply with this request will  
not void the owner’s rights under these warranties.  
noTE: If the heat exchanger model involved is no longer available  
due to product obsolescence or redesign, the value used to establish  
the retail price will be the published price as shown in the Burnham  
hydronics Repair parts price Sheet where the heat exchanger last  
appeared or the current retail price of the then nearest equivalent heat  
exchanger.  
Upon discovery of a condition believed to be related to a defect in  
material or workmanship covered by these warranties, the owner should  
notify the installer, who will in turn notify the distributor. If this action is  
not possible or does not produce a prompt response, the owner should  
write to U.S. Boiler Co., Inc., Burnham hydronics, at p.o. Box 3079,  
Lancaster, pA 17604, giving full particulars in support of the claim.  
ADDITIONAL TERMS AND CONDITIONS  
1. Applicability: The limited warranties set forth above are extended  
only to the original owner at the original place of installation within the  
United States and Canada. These warranties are applicable only to  
water boilers designated as residential grade by U.S. Boiler Co., Inc. and  
installed in a single or two-family residence and do not apply to steam  
boilers of any kind or to commercial grade boilers.  
The owner is required to make available for inspection by U.S.  
Boiler Co., Inc. or its representative the parts claimed to be defective  
and, if requested by U.S. Boiler Co., Inc. to ship these parts prepaid to  
U.S. Boiler Co., Inc. at the above address for inspection or repair. In  
addition, the owner agrees to make all reasonable efforts to settle any  
disagreement arising in connection with a claim before resorting to legal  
remedies in the courts.  
2. Components manufactured by others: Upon expiration of the  
one year limited warranty on residential grade water boilers, all boiler  
components manufactured by others but furnished by U.S. Boiler Co.,  
Inc. (such as oil burner, circulator and controls) will be subject only to the  
manufacturer’s warranty, if any.  
ThIS WARRAnTy gIvES yoU SpECIfIC LEgAL RIghTS AnD  
yoU mAy ALSo hAvE oThER RIghTS WhICh vARy fRom STATE  
To STATE.  
3. proper Installation: The warranties extended by U.S. Boiler Co., Inc.  
are conditioned upon the installation of the residential grade water boiler  
in strict compliance with U.S. Boiler Co., Inc. installation instructions. U.  
S. Boiler Co., Inc. specifically disclaims liability of any kind caused by or  
relating to improper installation.  
4. proper Use and maintenance: The warranties extended by U.S.  
Boiler Co., Inc. conditioned upon the use of the residential grade water  
03/03  

AIPTEK Pocket DV 4100 User Manual
Burley 09 Solo User Manual
Bushnell Binoculars 202310 User Manual
Canon LA DC52D User Manual
Casio ALGEBRA PLUS FX 2 0 User Manual
Clarion DB268RMP User Manual
Hypertec 3111 User Manual
JAMO 50 User Manual
JBL 28T 60 User Manual
JVC CS CN100 User Manual