Burnham 20_PV_I User Manual

INSTALLATION, OPERATING AND  
SERVICE INSTRUCTIONS FOR  
SERIES 2PV  
POWER VENT  
GAS - FIRED BOILER  
For service or repairs to boiler, call your heating contractor. When seeking information on  
boiler, provide Boiler Model Number and Serial Number as shown on Rating Label.  
Installation Date  
Boiler Model Number  
Boiler Serial Number  
20_PV_I -_ _ _ _  
6_ _ _ _ _ _ _  
Phone Number  
Heating Contractor  
Address  
Price - $3.00  
8141775R12-3/01  
3
I.Pre-Installation  
WARNING  
C. Appliance is design certified for installation on  
combustible flooring. The boiler must not be installed  
on carpeting.  
Carefully read all instructions before  
installing boiler. Failure to follow all  
instructions in proper order can cause  
personal injury or death.  
D. Provide clearance between boiler jacket and  
combustible material in accordance with local fire  
ordinance. See Figure 2 for minimum clearance from  
combustible material for closet installation. For alcove  
installation provide top clearance of 27 inches and right  
side clearance of 6 inches. Recommended service  
clearance is 24 inches from left side, right side and front.  
Service clearances may be reduced to minimum  
clearances to combustible materials.  
A. Inspect shipment carefully for any signs of damage. All  
equipment is carefully manufactured, inspected and  
packed. Our responsibility ceases upon delivery of  
boiler to carrier in good condition. Any claim for damage  
or shortage in shipment must be filed immediately  
against carrier by consignee. No claims for variances or  
shortages will be allowed by Boiler Manufacturer,  
unless presented within sixty (60) days after receipt of  
equipment.  
E. Install on level floor. For basement installation provide  
solid base, such as concrete, if floor is not level or if  
water may be encountered on floor around boiler.  
F. Install near outside wall for through wall venting. Refer  
to Section V: Venting, for vent length limitations.  
B. Installation must conform to the requirements of the  
authority having jurisdiction. In the absence of such  
requirements, installation must conform to National  
Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/  
CGA B149 Installation Codes. Where required by the  
authority having jurisdiction, the installation must  
conform to the Standard for Controls and Safety  
Devices for Automatically Fired Boilers, ANSI/ASME  
CSD-1.  
WARNING  
Certified as Category III appliance. Install  
vent system in accordance with Section  
V: Venting. Do not vent using masonry  
chimney, Type B gas vent, or other  
Category I venting system.  
G. Protect gas ignition system components from water  
(dripping, spraying, rain, etc.) during boiler operation  
and service (circulator replacement, condensate trap,  
control replacement, etc.).  
H. Provide combustion and ventilation air in accordance  
with applicable provisions of local building codes, or  
National Fuel Gas Code, NFPA 54/ANSI Z223.1,  
Section 5.3, Air for Combustion and Ventilation, or  
Sections 7.2, 7.3 or 7.4 of CAN/CGA B149 Installation  
Codes.  
WARNING  
Adequate combustion and ventilation air  
must be provided to assure proper  
combustion.  
The following guideline is based on the National Fuel  
Gas Code, NFPA 54/ANSI Z223.1.  
1. Determine volume of space (boiler room). Rooms  
communicating directly with space (through  
openings not furnished with doors) are considered  
part of space.  
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]  
Figure 2: Minimum Clearances to Combustible  
Construction for Closet Installation  
4
2. Determine Total Input of all appliances in space.  
Round result to nearest 1,000 Btu per hour (Btuh).  
a. Direct communication with outdoors. Minimum  
free area of 1 square inch per 4,000 Btu per hour  
input of all equipment in space.  
3. Determine type of space. Divide Volume by Total  
Input.  
b. Vertical ducts. Minimum free area of 1 square  
inch per 4,000 Btu per hour input of all equipment  
in space. Duct cross-sectional area shall be same  
as opening free area.  
a. If result is greater than or equal to 50 ft³ per 1,000  
Btuh, space is considered an unconfined space.  
b. If result is less than 50 ft³ per 1,000 Btuh, space is  
c. Horizontal ducts. Minimum free area of 1 square  
inch per 2,000 Btu per hour input of all equipment  
in space. Duct cross-sectional area shall be same  
as opening free area.  
considered a confined space.  
4. Determine building type. A building of unusually  
tight construction has the following characteristics:  
a. Walls and ceiling exposed to outside atmosphere  
have a continuous water vapor retarder with a  
rating of 1 perm or less with openings gasketed  
and sealed, and;  
Alternate method for boiler located within confined  
space. Use indoor air if two permanent openings  
communicate directly with additional space(s) of  
sufficient volume such that combined volume of all  
spaces meet criteria for unconfined space. Size each  
opening for minimum free area of 1 square inch per  
1,000 Btu per hour input of all equipment in spaces,  
but not less than 100 square inches.  
b. Weather-stripping has been added on openable  
windows and doors, and;  
c. Caulking or sealants applied in joints around  
window and door frames, between sole plates  
and floors, between wall-ceiling joints, between  
wall panels, at plumbing and electrical  
7. Ventilation Duct Louvers and Grilles. Equip outside  
openings with louvers to prevent entrance of rain  
and snow, and screens to prevent entrance of  
insects and rodents. Louvers and grilles must be  
fixed in open position or interlocked with equipment  
to open automatically before burner operation.  
Screens must not be smaller than ¼ inch mesh.  
penetrations, and at other openings.  
5. For boiler located in an unconfined space in a  
building of other than unusually tight construction,  
adequate combustion and ventilation air is normally  
provided by fresh air infiltration through cracks  
around windows and doors.  
Consider the blocking effect of louvers, grilles and  
screens when calculating the opening size to provide  
the required free area. If free area of louver or grille is  
not known, assume wood louvers have 20-25 percent  
free area and metal louvers and grilles have 60-75  
percent free area.  
6. For boiler located within unconfined space in  
building of unusually tight construction or within  
confined space, provide outdoor air through two  
permanent openings which communicate directly or  
by duct with the outdoors or spaces (crawl or attic)  
freely communicating with the outdoors. Locate one  
opening within 12 inches of top of space. Locate  
remaining opening within 12 inches of bottom of  
space. Minimum dimension of air opening is 3  
inches. Size each opening per following:  
I. Do not install boiler where gasoline or other flammable  
vapors or liquids, or sources of hydrocarbons (i.e.  
bleaches, cleaners, chemicals, sprays, paint removers,  
fabric softeners, etc.) are used or stored.  
II.UnpackBoiler  
CAUTION  
D. Remove all boiler hold-down fasteners.  
Do not drop boiler. Do not bump boiler  
jacket against floor.  
E. Tilt the boiler to one side and slide a wooden slat under  
the two raised feet.  
A. Move boiler to approximate installed position.  
F. Tilt the boiler to the other side and slide another  
wooden slat under the two raised feet.  
B. Remove all crate fasteners.  
G. Slide the boiler forward or backward off the skid using  
C. Lift outside container and remove with all other inside  
protective spacers and bracing. Save two of the  
wooden slats from the container sleeve for use in  
Paragraphs E and F.  
the two wooden slats as runners.  
H. Move boiler to its permanent location.  
5
III. WaterPipingandTrim  
CAUTION  
F. Space heating and domestic water heating with Alliance  
water heater. Install Alliance water heater as a separate  
heating zone. Refer to Alliance Installation, Operating and  
Service Instructions for additional information.  
Failure to properly pipe boiler may result in  
improper operation and damage to boiler or  
building.  
G. If boiler is used in connection with refrigeration systems ,  
boiler must be installed with chilled medium piped in  
parallel with the heating boiler using appropriate valves to  
prevent chilled medium from entering boiler, see Figure 4.  
Also consult I=B=R Installation and Piping Guides.  
A. Design and install boiler and system piping to prevent  
oxygen contamination of boiler water.  
H. If boiler is connected to heating coils located in air  
handling units where they may be exposed to refrigerated  
air, boiler piping must be equipped with flow control  
valves to prevent gravity circulation of boiler water during  
operation of cooling system.  
CAUTION  
Oxygen contamination of boiler water will  
cause corrosion of iron and steel boiler  
components, and can lead to boiler failure.  
Burnham's standard warranty does not  
cover problems caused by oxygen  
contamination of boiler water.  
I. Use a boiler bypass if the boiler is to be operated in a  
system which has a large volume or excessive radiation  
where low boiler water temperatures may be encountered  
(i.e. converted gravity circulation system, etc.).  
Install pipe tee between circulator and boiler return along  
with second tee in supply piping as shown in Figure 3.  
Bypass should be same size as the supply and return lines  
with valves located in bypass and supply outlet as  
illustrated in Figure 3 in order to regulate water flow to  
maintain higher boiler water temperatures.  
Oxygen contamination sources are system leaks  
requiring addition of makeup water, fittings, and oxygen  
permeable materials in distribution system. Eliminate  
oxygen contamination by repairing system leaks,  
repairing fittings, and using nonpermeable materials in  
distribution system.  
After the boiler is operational (reference Section VII.  
System Start-Up) set by-pass and boiler supply valves to  
half throttle position to start. Operate boiler until system  
water temperature reaches normal operating range.  
Adjust valves to provide 180° to 200°F supply water  
temperature. Opening the boiler supply valve will raise  
system temperature, while opening the by-pass valve will  
lower system supply temperature.  
B. Connect system supply and return piping to boiler. See  
Figure 3. Also consult I=B=R Installation and Piping  
Guides. Maintain minimum ½ inch clearance from hot  
water piping to combustible materials.  
C. Install Circulator with flanges, gaskets and bolts  
provided. Five foot circulator harness allows circulator  
to be mounted on supply or return. Connect harness to  
J. A hot water boiler installed above radiation level must be  
provided with a low water cut-off device as part of  
installation.  
circulator and secure any excess conduit.  
D. Install Safety Relief Valve. See Figure 3. Safety Relief  
Valve must be installed with spindle in vertical position.  
Installation of the relief valve must be consistant with  
the ANSI/ASME Boiler and Pressure Vessel Code,  
Section IV.  
K. Oil, grease, and other foreign materials which  
accumulate in new hot water boilers and a new or  
reworked system should be boiled out, and then  
thoroughly flushed. A qualified water treatment chemical  
specialist should be consulted for recommendations  
regarding appropriate chemical compounds and  
concentrations which are compatible with local  
environmental regulations.  
WARNING  
Safety relief valve discharge piping must be  
piped near floor to eliminate potential of  
severe burns. Do not pipe in any area  
where freezing could occur. Do not install  
any shut-off valves.  
L. After the boiler and system have been cleaned and  
flushed, and before refilling the entire system add  
appropriate water treatment chemicals, if necessary, to  
bring the pH between 7 and 11.  
E. Install Drain Valve in ¾" NPT connection in tee  
provided. See Figure 1.  
6
Figure 3: Recommended Boiler Piping For Series - Loop Hot Water Heating Systems  
Figure 4: Recommended Piping for Combination Heating & Cooling (Refrigeration) Systems  
7
IV. GasPiping  
A. Size gas piping. Design system to provide adequate  
3. Install sediment trap, ground-joint union and manual  
shut-off valve upstream of boiler gas control valve  
and outside jacket. See Figure 6.  
gas supply to boiler. Consider these factors:  
1. Allowable pressure drop from point of delivery to  
boiler. Maximum allowable system pressure is ½  
psig. Actual point of delivery pressure may be less;  
contact gas supplier for additional information.  
Minimum gas valve inlet pressure is listed on  
rating label.  
4. All above ground gas piping upstream from manual  
shut-off valve must be electrically continuous and  
bonded to a grounding electrode. Do not use gas  
piping as grounding electrode. Refer to National  
Electrical Code, ANSI/NFPA 70 and/or CSA C22  
Electrical Code.  
2. Maximum gas demand. Table 1 lists boiler input  
rate. Also consider existing and expected future gas  
utilization equipment (i.e. water heater, cooking  
equipment).  
C. Pressure test. The boiler and its gas connection must  
be leak tested before placing boiler in operation.  
1. Protect boiler gas control valve. For all testing over  
½ psig, boiler and its individual shut-off valve must  
be disconnected from gas supply piping. For testing  
at ½ psig or less, isolate boiler from gas supply  
piping by closing boiler's individual manual shut-off  
valve.  
Table 1: Rated Input  
Input Rate  
[cubic feet per hour]  
Boiler  
Model  
Number  
Gas  
Connection  
Size  
Natural Gas LP/Propane  
2. Locate leaks using approved combustible gas  
detector, soap and water, or similar nonflammable  
solution. Do not use matches, candles, open flames,  
or other ignition source.  
203PV  
204PV  
205PV  
206PV  
62  
24¾  
38½  
52  
½
½
½
½
96  
130  
164  
65¾  
3. Length of piping and number of fittings. Refer to  
Table 2 for maximum capacity of Schedule 40 pipe.  
Table 3 lists equivalent pipe length for standard  
fittings.  
4. Specific gravity of gas. Gas piping systems for gas  
with a specific gravity of 0.70 or less can be sized  
directly from Table 2, unless authority having  
jurisdiction specifies a gravity factor be applied. For  
specific gravity greater than 0.70, apply gravity  
factor from Table 4. If exact specific gravity is not  
shown choose next higher value.  
For materials or conditions other than those listed  
above, refer to National Fuel Gas Code, NFPA 54/  
ANSI Z223.1, or size system using standard  
engineering methods acceptable to authority having  
jurisdiction.  
B. Connect boiler gas valve to gas supply system.  
1. Use methods and materials in accordance with local  
plumbing codes and requirements of gas supplier.  
In absence of such requirements, follow National  
Fuel Gas Code, NFPA 54/ANSI Z223.1 and/or  
CAN/CGA B149 Installation Codes.  
2. Use thread (joint) compounds (pipe dope) resistant  
to action of liquefied petroleum gas.  
Figure 6: Recommended Gas Piping  
8
Table 2: Maximum Capacity of Schedule 40 Pipe in CFH For Gas Pressures of 0.5 psig or Less  
0.3 inch w.c. Pressure Drop  
0.5 inch w.c. Pressure Drop  
Length  
[Feet]  
½
132  
92  
73  
63  
56  
50  
46  
43  
40  
38  
¾
1
1¼  
1,050  
730  
590  
500  
440  
400  
370  
350  
320  
305  
½
175  
120  
97  
¾
1
1¼  
1,400  
950  
770  
660  
580  
530  
490  
460  
430  
400  
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
278  
190  
152  
130  
115  
105  
96  
520  
350  
285  
245  
215  
195  
180  
170  
160  
150  
360  
250  
200  
170  
151  
138  
125  
118  
110  
103  
680  
465  
375  
320  
285  
260  
240  
220  
205  
195  
82  
73  
66  
61  
90  
57  
84  
53  
79  
50  
Table 3: Fitting Equivalent Lengths  
Nominal Pipe Size  
Table 4: Specific Gravity Correction Factors  
Specific  
Gravity  
Correction  
Factor  
Specific  
Gravity  
Correction  
Factor  
Fitting  
0.50  
0.55  
0.60  
0.65  
0.70  
0.75  
0.80  
1.10  
1.04  
1.00  
0.96  
0.93  
0.90  
0.87  
1.30  
1.40  
1.50  
1.60  
1.70  
1.07  
1.04  
1.00  
0.97  
0.94  
½
¾
1
1
1¼  
1.6  
3.5  
6.9  
45° Ell  
90° Ell  
0.7  
1.6  
3.1  
1.2  
2.6  
5.2  
2.1  
4.1  
Tee (As Elbow)  
V. Venting  
A. General Guidelines.  
Flex-L International Inc., - Star-34, Protech Systems,  
Inc. - FasNSeal™, and Z-Flex U. S., Inc. - Z-Vent.  
The use of these alternate manufacturer's venting  
systems will require adapters to connect to the  
Burnham supplied vent connector and vent terminal.  
These adapters are not supplied with this unit and  
should be obtained from the supplier of the alternate  
manufacturer's venting system. See Table 5 for  
complete list of Burnham Vent System Components.  
1. Vent system installation must be in accordance with  
National Fuel Gas Code, NFPA 54/ANSI Z221.3,  
Part 7, Venting of Equipment; and/or CAN/CGA  
B149 Installation Codes, Section 7, Venting Systems  
and Air Supply for Appliances; or applicable  
provisions of local building codes. Contact local  
building or fire officials about restrictions and  
installation inspection in your area.  
2. This appliance requires a Special Gas Vent. Use Vent  
Connector and Vent Terminal in Vent Accessory  
Carton provided with boiler (See Repair Parts, Key  
No. 8). The product is designed to use Burnham  
supplied AL 29-4C® Stainless Steel vent system  
components. The following manufacturers offer  
similar AL 29-4C® components and are approved for  
use with this product: Heat-Fab Inc. - Saf-T-Vent,  
WARNING  
Do not use this appliance with nonmetallic  
vent systems such as Hart & Cooley  
Ultravent, Plexco Plexvent, or Selkirk-  
Metalbestos Sel-Vent.  
9
Table 5: Burnham Vent System Components  
(d) Place in operation the appliance being inspected.  
Follow the Lighting (or Operating) Instructions.  
Adjust thermostat so appliance will operate  
continuously.  
Burnham  
*Cartoned  
Part  
Burnham  
Vent System  
Component  
Component  
Part  
(e) Test for spillage at the drafthood relief opening after  
5 minutes of main burner operation. Use the flame of  
a match or candle, or smoke from a cigarette, cigar or  
pipe.  
Number  
Number  
3" Dia. Pipe x 1 Ft  
3" Dia. Pipe x 3 Ft  
3" Dia. Pipe x 4 Ft  
3" Dia. Pipe x 5 Ft  
3" Dia. 90° Elbow  
3" Dia. 45° Elbow  
61160112  
61160101  
**  
8116135  
8116058  
8116176  
8116059  
8116060  
8116061  
(f) After it has been determined that each appliance  
remaining connected to the common venting system  
properly vents when tested as outlined above,  
return doors, windows, exhaust fans, fireplace  
dampers and any other gas burning appliance to  
their previous conditions of use.  
61160111  
61160121  
61160131  
(g) Any improper operation of the common venting  
system should be corrected so the installation  
conforms with the National Fuel Gas Code, NFPA  
54/ANSI Z223.1. When resizing any portion of the  
common venting system, the common venting  
system should be resized to approach the minimum  
size as determined using the appropriate tables in  
Part II in the National Fuel Gas Code, NFPA 54/  
ANSI Z223.1.  
*
Complete with Locking Band(s)  
* * 6116033 Contains (4) 4 ft. lengths  
6116040 Contains (2) 4 ft. lengths  
3. Vent length restrictions are based on equivalent feet  
of vent pipe (total length of straight pipe in feet plus  
5 equivalent feet for each 45° or 90° elbow). Do not  
exceed the maximum certified vent length of 25  
equivalent feet. The minimum certified vent length is  
7 equivalent feet. Do not include vent terminal or  
vent connector in equivalent feet calculations.  
C. Install Vent Connector.  
1. Remove vent connector from vent accessory carton.  
4. Do not install venting system components on the  
exterior of the building except as specifically required  
by these instructions.  
2. Remove gaskets, orifice plate and hardware from  
blower outlet flange.  
3. Assemble orifice plate gaskets, orifice plate, and  
vent connector. See Figure 7.  
B. Removal of Existing Boiler. For installations not  
involving the replacement of an existing boiler, proceed  
to Step C.  
4. Secure vent connector with washers and locknuts.  
When an existing boiler is removed from a common  
venting system, the common venting system is likely to  
be too large for proper venting of the remaining  
appliances. At the time of removal of an existing boiler,  
the following steps shall be followed with each  
appliance remaining connected to the common venting  
system placed in operation, while the other appliances  
remaining connected to the common venting system are  
not in operation:  
(a) Seal any unused openings in the common venting  
system.  
(b) Visually inspect the venting system for proper size  
and horizontal pitch and determine there is no  
blockage or restriction, leakage, corrosion, and other  
deficiencies which could cause an unsafe condition.  
(c) Insofar as is practical, close all building doors and  
windows and all doors between the space in which  
the appliances remaining connected to the common  
venting system are located and other spaces of the  
building. Turn on clothes dryers and any appliance  
not connected to the common venting system. Turn  
on any exhaust fans, such as range-hoods and  
bathroom exhausts, so they will operate at maximum  
speed. Do not operate a summer exhaust fan. Close  
fireplace dampers.  
Figure 7: Vent Connector Installation  
10  
2. Vent terminal location restricted per following:  
D. Install Vent Pipe, General.  
a. Minimum 12 inches above grade plus normally  
expected snow accumulation level, or 7 feet  
above grade if located adjacent to public  
walkway. Do not install over public walkway  
where local experience indicates condensate or  
vapor from Category III appliances creates a  
nuisance or hazard.  
1. Start at vent connector. Work toward vent terminal.  
2. Use ¾ inch pipe strap to support horizontal runs,  
maintain vent location and slope, and prevent sags.  
Do not restrict thermal expansion movement.  
Maximum support spacing is 5 feet.  
3. Provide minimum 5 inch clearance to combustible  
materials. Use thimble when penetrating combustible  
wall.  
a. 203PV and 204PV - Single wall thimble, Burnham  
Part No. 8116116. Other wall thimble  
manufacturers are American Metal Products, Hart  
& Cooley, and Metal Fab.  
b. 205PV and 206PV - Double wall thimble, Burnham  
Part No. 8116115 (accomodates 5" to 8¾" wall  
thickness). Another wall thimble manufacturer is  
Hart & Cooley.  
4. Cut pipe to length using hacksaw with minimum 32  
teeth per inch or circular saw with metal abrasive  
wheel. Remove bead end only - bell end accepts next  
fitting or pipe. Cut must be square with pipe. Scrape  
off burrs with sharp edged tool.  
Figure 8: Typical Joint Detail  
Note: If remaining pipe (less bell) must be used,  
beaded end of mating pipe/fitting must be crimped.  
b. Minimum 3 feet above any forced air inlet located  
within 10 feet.  
5. Seal all joints using Dow Corning Silastic 732 RTV,  
Dow Corning Silastic 736 RTV, Polybac #500 RTV, or  
Sil-bond RTV 4500 (Acetoxy). Do not use other  
adhesives or sealants.  
c. Minimum 4 foot below, 4 foot horizontally from,  
or 1 foot above any door, window, or gravity air  
inlet.  
d. Minimum 4 feet horizontally from, and in no case  
above or below, unless a 4-foot horizontal  
distance is maintained, from electric meters, gas  
meters, regulators and relief equipment.  
6. Procedure for joining pipe and fittings. See Figure 8.  
a. Clean pipe or fitting. Remove all dirt and grease.  
b. Slip locking band over pipe/fitting bell.  
e. Minimum 12 inches from overhang or corner.  
c. Apply continuous ¼ inch bead of sealant around  
bead end of pipe/fitting no more than 1/8 inch  
from end.  
3. Use wall thimble when passing through combustible  
outside wall (thimble use optional for  
noncombustible wall). Insert thimble through wall  
from outside. Secure outside flange to wall with nails  
or screws, and seal with adhesive material. Install  
inside flange to inside wall, secure with nails or  
screws, and seal with adhesive material.  
d. Insert pipe/fitting into bell. Smooth sealant for  
continuous seal around gap between bead and  
bell. Apply additional sealant if necessary.  
e. Slip locking band over joint and tighten. Do not  
secure joint with sheet metal screws or pop rivets.  
4. For noncombustible wall when thimble is not used,  
size opening such that bell with locking band  
attached cannot pass through.  
E. Horizontal (Through Wall) Vent Installation.  
1. Maintain minimum ¼ inch per foot slope in  
horizontal runs. Slope pipe down toward vent  
terminal.  
5. Join vent terminal to vent pipe. Cut vent pipe to  
locate vent terminal 3 inches (minimum) and 6 inches  
(recommended) from wall when joined to inside vent  
piping. See Figure 9. Vent terminal clearance to vinyl  
wall surfaces is 6 inches.  
CAUTION  
Moisture and ice may form on surfaces  
around vent terminal. To prevent  
deterioration, surfaces should be in good  
repair (sealed, painted etc.)  
6. Insert vent pipe through thimble/opening from  
outside and join to vent system. Apply sealant  
between vent pipe and opening/thimble to provide  
weathertight seal.  
11  
Figure 9: Recommendations for Thimble and Wall Penetration  
VI.Electrical  
A. General. Install wiring and ground boiler in  
accordance with requirements of authority having  
jurisdiction, or in absence of such requirements the  
National Electrical Code, ANSI/NFPA 70, and/or the  
CSA C22.1 Electric Code.  
Instructions.  
1. Zoning with Circulators, Domestic Hot Water  
Priority. Provide DPDT relay (included with PAL).  
Connect coil to Alliance thermostat (prewired with  
PAL). Connect normally open contacts (red and  
white wires in PAL control harness) to transformer  
terminals 'R' and 'Y'. Disconnect yellow circulator  
wire. Connect normally closed contacts (violet  
wires in PAL boiler harness) to yellow relay wire  
and yellow circulator wire.  
B. Install thermostat. Locate on inside wall approximately  
4 feet above floor. Do not install on outside wall, near  
fireplace, or where influenced by drafts or restricted air  
flow, hot or cold water pipes, lighting fixtures,  
television, or sunlight. Allow free air movement by  
avoiding placement of furniture near thermostat.  
2. Zoning with Circulators, Nonpriority. Connect  
Alliance circulator zone control (or red and white  
wires in PAL control harness) to transformer  
terminals 'R' and 'Y'.  
C. Wire thermostat. Provide Class II circuit between  
thermostat and boiler. Run wires through grommet in  
Jacket Left Side Panel. Set thermostat heat anticipator  
to 0.6 amps. See Figure 10.  
3. Zoning with Zone Valves. Connect Alliance  
thermostat to zone valve. Connect zone valve end  
switch to relay terminals 'R' and 'G'. See Paragraph  
F.  
D. Wire boiler. Boiler is rated for 120 VAC, 60 hertz, less  
than 12 amperes. Provide individual branch circuit with  
fused disconnect. Connect to black and white wires and  
F. For installations using zone valves provide separate  
transformer for zone valve wiring. Consult zone valve  
manufacturer for assistance.  
green ground screw. See Figure 10.  
E. Alliance water heater (if used). See Figure 10. Also refer  
to Alliance Installation, Operating and Service  
12  
Figure 10: Wiring Diagram  
VII.SystemStart-up  
8. Open zone valve to second zone to be purged, then  
close first. Repeat this step until all zones have been  
purged, but always have one zone open. At  
completion, open all zone valves.  
A. Safe operation and other performance criteria were met  
with gas manifold and control assembly provided on  
boiler when boiler underwent tests specified in  
American National Standard for Gas-Fired Low-  
Pressure Steam and Hot Water Boilers, ANSI Z21.13.  
9. Close bib cock, continue filling system until pressure  
gauge reads 12 psi. Close fill valve.  
B. Fill heating system with water and vent air from system.  
Use the following procedure on a Series Loop System  
equipped with zone valves. See Figure 3.  
Note: If makeup water line is equipped with pressure  
reducing valve, system will automatically fill to 12  
psi. Leave globe valve open.  
1. Close isolation valve in boiler supply piping.  
10. Open isolation valve in boiler supply piping.  
11. Remove hose from bib cock.  
2. Isolate all circuits by closing zone valves or  
balancing valves.  
3. Attach hose to bib cock located just below isolation  
valve in boiler supply piping. Terminate hose in five  
gallon bucket at a suitable floor drain or outdoor  
area).  
C. Check main burners. See Figure 11. Rear of burner  
must be in vertical slot in rear of burner tray. Front of  
burner must be seated on orifice.  
4. Starting with one circuit, open zone valve.  
5. Open bib cock.  
6. Open fill valve. Makeup water line should be located  
directly above isolation valve in boiler supply  
piping.  
7. Allow water to overflow from bucket until discharge  
from hose is bubble free for 30 seconds.  
13  
Figure 11: Main Burner Installation  
Figure 12: Gas Valve Pressure Tap  
D. Prepare to check operation.  
1. Obtain gas heating value (in Btu per cubic foot) from  
gas supplier.  
2. Connect manometer to pressure tap on gas valve.  
See Figure 12.  
3. For natural gas fired boiler, temporarily turn off all  
other gas-fired appliances.  
E. Follow Operating Instructions to place boiler in  
operation. See Figure 17.  
F. Sequence of Operation. See Figure 14. If boiler fails to  
operate properly, see Troubleshooting Tree on pages  
17-18.  
G. Check gas piping and connections between Gas Valve  
and Manifold, Orifices and Pilot Tubing. Use soap  
solution or other approved method. See Figure 13.  
H. Check pilot burner flame. See Figure 15. Flame should  
be steady, medium hard blue enveloping 3/8 to ½ inch  
of sensing probe.  
I. Check main burner flame. See Figure 16. Flame should  
have clearly defined inner cone with no yellow tipping.  
Orange-yellow streaks should not be confused with true  
yellow tipping.  
Figure 14: Sequence of Operation  
14  
Figure 13: Schematic Pilot and Gas Piping  
Figure 15: Pilot Burner Flame  
Table 6: Gas Flow Rate in Cubic Feet per Hour  
Size of Gas Meter Dial  
Seconds  
for One  
Revolution  
One-Half  
Cu. Ft.  
One  
Cu. Ft.  
Two  
Cu. Ft.  
30  
32  
34  
36  
38  
40  
42  
44  
46  
48  
50  
52  
54  
56  
58  
60  
60  
56  
53  
50  
47  
45  
43  
41  
39  
37  
36  
35  
33  
32  
31  
30  
120  
113  
106  
100  
95  
240  
225  
212  
200  
189  
180  
172  
164  
157  
150  
144  
138  
133  
129  
124  
120  
90  
86  
Figure 16: Main Burner Flame  
82  
78  
J. Check thermostat operation. Raise and lower  
75  
temperature setting to start and stop boiler operation.  
72  
K. Check ignition control module shut-off. Disconnect  
igniter/sensor cable from Terminal 9 (SPARK). Gas valve  
should close and pilot and main burners should  
extinguish.  
69  
67  
64  
L. Check low water cut-off (if used). Drain boiler water  
62  
below LWCO set point. Burners should extinguish.  
60  
M. Check limit.  
1. Adjust thermostat to highest setting.  
a. Boiler must not be overfired. Reduce input rate  
by decreasing manifold pressure. Do not reduce  
more than 0.3 inch w.c. If boiler is still overfired,  
contact your Burnham distributor or Regional  
Office for replacement Gas Orifice.  
2. Observe temperature gauge. When temperature is  
indicated, adjust limit to setting below observed  
temperature. Main burners and pilot burner should  
extinguish and blower stop.  
b. Increase input rate if less than 98% of rating label  
input. Increase manifold gas pressure no more  
than 0.3 inch w.c. If measured input rate is still  
less than 98% of rated input:  
3. Adjust limit to setting above observed temperature.  
Ignition sequence should begin.  
4. Adjust thermostat to lowest setting. Adjust limit to  
desired setting.  
i. Remove Main Burners per procedure in  
Section VIII: Service.  
N. Adjust gas input rate to boiler (Natural Gas).  
ii. Remove gas orifices. Drill one (1) drill size  
larger (drill size is stamped on orifice, or see  
Key No. 4D).  
1. Adjust thermostat to highest setting.  
2. Check manifold gas pressure. Manifold pressure is  
listed on rating label. Adjust gas valve pressure  
regulator as necessary (turn adjustment screw  
counterclockwise to decrease manifold pressure, or  
clockwise to increase manifold pressure). If pressure  
can not be attained, check gas valve inlet pressure.  
If less than minimum gas supply pressure listed on  
rating label, contact gas supplier for assistance.  
iii. Reinstall gas orifices and main burners.  
Measure input rate.  
6. Recheck Main Burner Flame.  
7. Adjust thermostat to normal setting.  
8. Return other gas-fired appliances to previous  
conditions of use.  
3. Clock gas meter for at least 30 seconds. Use Table 6  
to determine gas flow rate in Cubic Feet per Hour.  
O. Adjust gas input rate to boiler (LP/Propane).  
4. Determine Input Rate. Multiply gas flow rate by gas  
heating value.  
1. Adjust thermostat to highest setting.  
2. Check manifold pressure. Adjust gas valve pressure  
regulator to obtain 10 inches w.c. manifold pressure.  
5. Compare measured input rate to input rate listed on  
rating label.  
15  
Figure 17: Operating Instructions  
Adjust gas valve pressure regulator as necessary  
subsequent boiler operation.  
(turn adjustment screw counterclockwise to  
decrease manifold pressure, or clockwise to increase  
manifold pressure). If pressure can not be attained,  
check gas valve inlet pressure. If less than minimum  
gas supply pressure listed on rating label, contact  
gas supplier for assistance.  
2. Ventilate the boiler room, set the high limit to its  
maximum setting, set the thermostat to call for heat.  
Allow the boiler to fire for at least an hour or until  
the odor from the cornstarch has dissipated.  
3. Return the high limit and thermostat to their desired  
settings.  
3. Recheck Main Burner Flame  
4. Adjust thermostat to normal setting.  
Q. Review User's Information Manual and system  
operation with owner or operator.  
P. COMBUSTION CHAMBER BURN-OFF  
R. Post instructions near boiler for reference by owner and  
service personnel. Maintain instructions in legible  
condition.  
1. The mineral wool combustion chamber panels  
contain a cornstarch based binder that must be  
burned out at installation to prevent odors during  
16  
TROUBLE SHOOTING GUIDE  
SPLIT (SEPARATE) CONTROLS, 24 VOLT OPERATION WITH  
ELECTRONIC IGNITION AND INTERMITTENT CIRCULATION  
NOTE: 1. Read Sequence of Operation prior to using Trouble Shooting Guide.  
See Page 14.  
2. Prior to replacing a control, always check for broken wires or loose connectors that  
provide power to that control.  
17  
18  
Note: Minimum pilot signal should be 1.0 microamps. Disconnect Pilot Ground wire from Module and connect  
DC microammeter between Ground Terminal and Pilot Ground wire.  
19  
Important Product Safety Information  
Refractory Ceramic Fiber Product  
Warning:  
This product contains refractory ceramic fibers (RCF). RCF has been classified  
as a possible human carcinogen. After this product is fired, RCF may, when  
exposed to extremely high temperature (>1800F), change into a known human  
carcinogen. When disturbed as a result of servicing or repair, RCF becomes  
airborne and, if inhaled, may be hazardous to your health.  
AVOID Breathing Fiber Particulates and Dust  
Precautionary Measures:  
Do not remove or replace previously fired RCF (combustion chamber insulation,  
target walls, canopy gasket, flue cover gasket, etc.) or attempt any service or  
repair work involving RCF without wearing the following protective gear:  
1. A National Institute for Occupational Safety and Health (NIOSH)  
approved respirator  
2. Long sleeved, loose fitting clothing  
3. Gloves  
4. Eye Protection  
·
·
·
Take steps to assure adequate ventilation.  
Wash all exposed body areas gently with soap and water after contact.  
Wash work clothes separately from other laundry and rinse washing  
machine after use to avoid contaminating other clothes.  
·
Discard used RCF components by sealing in an air tight plastic bag.  
First Aid Procedures:  
·
·
·
If contact with eyes: Flush with water for at least 15 minutes. Seek  
immediate medical attention if irritation persists.  
If contact with skin: Wash affected area gently with soap and water.  
Seek immediate medical attention if irritation persists.  
If breathing difficulty develops: Leave the area and move to a location  
with clean fresh air. Seek immediate medical attention if breathing  
difficulties persist.  
·
Ingestion: Do not induce vomiting. Drink plenty of water. Seek  
immediate medical attention.  
20  
VIII. Service  
a. If passageways are free of soot and obstruction,  
replace canopy, secure and seal using kit  
available from Burnham Distributors, Part No.  
6111716.  
A. General. Inspection and service should be conducted  
annually. Turn off electrical power and gas supply while  
conducting service or maintenance. Follow instructions  
TO TURN OFF GAS TO APPLIANCE. See Figure 17.  
b. If passageways need cleaning, remove burners as  
described in Paragraph F below. Using long  
handle wire or bristle flue brush and vacuum,  
brush flueways thoroughly from top of boiler as  
illustrated in Figure 19. Replace canopy and seal  
using kit available from Burnham Distributors,  
Part No. 6111716.  
CAUTION  
Label all wires prior to disconnection when  
servicing controls. Wiring errors can cause  
improper and dangerous operation. Verify  
proper operation after servicing.  
WARNING  
B. Inspect Housekeeping. Boiler area must be clear and  
free from combustible materials, gasoline and other  
flammable vapors and liquids. Remove obstructions to  
the flow of combustion and ventilation air.  
Canopy must be resealed with RTV-732  
Silicone Rubber Sealant (500°F Intermittent  
Duty).  
C. Service Low water cut-off (if so equipped). Follow  
6. Reinstall jacket top panel, vent pipe and vent  
connector in reverse manner. Reconnect electrical  
connector to blower.  
instructions provided with low water cut-off  
D. Inspect Vent System for obstructions in vent pipe, soot  
accumulation, deterioration of pipe or joints, and proper  
support:  
F. Clean Main Burners and Firebox.  
1. Remove vent connector and vent pipe. See Figure  
19.  
1. To remove burners for cleaning, changing orifice  
plugs, or repairs:  
2. Remove all obstructions. Check and clean vent  
terminal screens.  
a. Remove jacket Front Panel.  
b. Disconnect pilot tubing at gas valve.  
3. Remove soot accumulations with wire brush and  
vacuum.  
c. Disconnect igniter/sensor cable and ground wire  
at Ignition Module.  
4. Replace deteriorated parts.  
d. Disconnect Flame Rollout Switch wires.  
e. Remove Burner Access Panel.  
5. Repair deteriorated joints. See Section V: Venting,  
Paragraph D.6.  
f. Mark Pilot Main Burner location on Manifold.  
E. Inspect Boiler Flue Passages for blockage or soot  
g. Hold burner on throat. Lift slightly to clear orifice.  
Pull burner from combustion chamber. See Figure  
11. Pilot Main Burner can only be removed by  
lifting at 45° angle after adjacent burner to right is  
removed.  
accumulation. See Figure 19.  
1. Disconnect vent connector from blower discharge  
flange.  
2. Remove sheet metal screws securing Jacket Top  
Panel. Lift panel and rotate about relief valve piping  
until top of boiler is exposed. If piping or wall  
prevent full rotation of top panel for access to  
canopy, cut slot into relief valve opening and  
remove top panel.  
2. Brush top of burners with a soft bristle brush. See  
Figure 19. Vacuum burners.  
3. Check orifices. Drilled passageways must be free of  
lint or dirt.  
4. Vacuum tip of Pilot Burner.  
3. Disconnect blower connection from wiring harness  
in vestibule.  
5. Clean firebox by vacuuming. Exercise care not to  
disturb insulation inside base.  
4. Remove bolts securing canopy to boiler sections.  
Cut silastic sealant around base of canopy, pry  
canopy from boiler sections and remove canopy/  
blower assembly from boiler.  
6. Install burners by reversing procedure used to  
remove burners. Burner with pilot assembly must be  
in same location as original installation. See Table 7.  
Burners must be properly located on support bracket  
5. Using flashlight, examine all flue passageways.  
21  
Table 7: Pilot Burner Location  
Pilot Burner Located  
Between Main  
Burners *  
Boiler  
M o d e l  
Main Burner with  
60° Pilot Bracket *  
2 0 3 P V  
2 0 4 P V  
2 0 5 P V  
2 0 6 P V  
1
2
3
4
1 & 2  
2 & 3  
3 & 4  
4 & 5  
* Main burners numbered left to right as viewed from  
front of boiler.  
at rear of burner. See Figure 11. Slide burner  
over orifice.  
7. Reconnect pilot gas supply, igniter/sensor  
cable, and ground wire. Reinstall Burner  
Access Panel. Reconnect Flame Rollout  
Switch wires.  
Figure 18: Spark Gap Setting  
G. Check operation. Follow Paragraphs D through  
O from Section VII: System Start-up.  
H. Removal or replacement of pilot assembly or  
pilot assembly parts. If pilot assembly, sensor or  
pilot orifice need replacing, remove main burner  
with pilot using procedure described in  
Paragraph F.1.  
1. To replace orifice.  
a. Disconnect pilot tubing. Pilot orifices  
screw into Pilot Burner. Replace with  
Honeywell 388146NE (Natural Gas) or  
Honeywell 388146KP (LP/Propane).  
b. Reconnect pilot tubing and check for  
leaks.  
2. To adjust or check spark gap between  
electrode and hood on Honeywell Q348A  
intermittent pilot. See Figure 18.  
a. Use round wire gauge to check spark  
gap.  
b. Spark gap should be 1/8 inch for optimum  
performance.  
3. To replace complete pilot assembly.  
a. Remove two machine screws holding  
pilot burner to pilot bracket.  
b. Disconnect pilot tubing.  
c. Disconnect all other leads to pilot.  
d. Select pilot assembly with identical model  
number, reconnect leads and pilot tubing.  
Resecure to pilot bracket.  
4. Reinstall main burner following procedure  
described in Paragraph F.  
Figure 19: Flueway Cleaning  
22  
Table 8: Minimum Suction Pressure  
Boiler Model Minimum Suction Pressure  
203PV  
204PV  
205PV  
206PV  
-0.50 inches w.c.  
-0.50 inches w.c.  
-0.80 inches w.c.  
-0.80 inches w.c.  
I. Lubrication. There are no parts requiring lubrication by  
service technician or owner. Circulator bearings are  
water lubricated. Blower motor bearings are factory  
sealed.  
Figure 20: Procedure for Measuring Fan Suction  
Pressure  
23  
IX.RepairParts  
All Series 2PV Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance  
in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham products or repair parts,  
please contact your Burnham Regional Sales Office as listed below.  
Burnham Corporation Regional Offices  
A. Burnham Corporation - Central & Western Regions C. Burnham Corporation - Metropolitan Region  
P.O. Box 3079  
P.O. Box 3079  
Lancaster, PA 17604-3079  
Phone: (717) 481-8400  
FAX: (717) 481-8408  
Lancaster, PA 17604-3079  
Phone: (717) 481-8400  
FAX: (717) 481-8409  
B. Burnham Sales Corporation - Northeast Region  
19-27 Mystic Avenue  
D. Burnham Corporation - Mid-Atlantic Region  
P.O. Box 3079  
Somerville, MA 02145  
Lancaster, PA 17604-3079  
Phone: (617) 625-9735  
Phone: (717) 481-8400  
FAX: (617) 625-9736  
FAX: (717) 481-8409  
Contact Regional Office Indicated for your State  
Alabama  
Alaska  
A Nebraska  
A Oregon  
A
A Nevada  
A Pennsylvania  
B Rhode Island  
South Carolina  
South Dakota  
Tennessee  
D
B
A
A
A
A
A
B
Arizona  
A New Hampshire  
A New Jersey  
Arkansas  
California  
Colorado  
Connecticut  
Delaware  
Florida  
A
A
B
D
A
A
Atlantic, Burlington, Camden,  
Cape May, Cumberland,  
Gloucester, Mercer,  
Monmouth, Ocean, Salem  
Counties  
D
Texas  
Utah  
Vermont  
C Virginia  
Georgia  
Hawaii  
All other Counties  
A New Mexico  
A New York  
A
Arlington,Accomack,Clarke,  
Idaho  
Fairfax,Frederick,Fauquier,  
Loudoun,Northampton and  
Prince William Counties  
All other Counties  
D
Illinois  
A
A
A
A
A
Albany, Fulton, Montgomery,  
Rensselaer, Saratoga,  
Indiana  
B
Iowa  
Schenectady, Schoharie,  
Warren, Washington Counties  
All Other Counties  
A
A
D
D
A
A
Kansas  
Washington  
Kentucky  
Louisiana  
Maine  
C Washington, D.C.  
A West Virginia  
A Wisconsin  
A North Carolina  
B North Dakota  
D Ohio  
Maryland  
Massachusetts  
Michigan  
Minnesota  
Mississippi  
Missouri  
Montana  
Wyoming  
B
A
A
A
A
Athens, Belmont, Gallia,  
Jefferson, Lawrence, Meigs,  
Monroe, and Washington  
Counties  
D
A
All other Counties  
A Oklahoma  
A Canada  
A
24  
[Quantity] Part Number  
204PV 205PV  
Key  
No.  
Description  
203PV  
206PV  
1. Section Assembly  
617170321 617170421 617170521 617170621  
2. Canopy/Blower Assembly  
[1]  
[1]  
[1]  
[1]  
2A Canopy  
61117034  
61117044 61117054  
[2] Common Hardware  
[10] Common Hardware  
[2] Common Hardware  
61117064  
2B Carriage Bolt, ¼-20 x 1"  
2C Washer, ¼, SAE  
2D Nut,¼-20, Heavy Hex  
2E Blower Mounting Gasket [Included in Key No. 2F]  
2F Blower  
[1] 8206048  
[1] 8206049  
[1] 6111714  
[2] 8206042  
[1] 6111715  
[2] 8206035  
2G Orifice Plate Gasket [(2) Included in Key No. 2F]  
[1]  
71117035  
[1]  
[1]  
[1]  
2H Orifice Plate  
71117045 71117055  
71117065  
2J Pressure Fitting, Dwyer A308  
2K Hex Nut, 1/4-20, Brass [(4) Included in Key No. 2F]  
2L Hex Locknut, ¼-20  
[1] 822657  
[4] 80860424  
[4] Common Hardware  
25  
[Quantity] Part Number  
204PV 205PV  
Key  
No.  
Description  
203PV  
206PV  
3. Base Assembly Group  
3
Base Assembly, Complete  
[1] 618600391 [1] 618600491 [1] 618600591 [1] 618600691  
[1] 718600391 [1] 718600491 [1] 718600591 [1] 718600691  
[1] 718600311 [1] 718600411 [1] 718600511 [1] 718600611  
3A Base Tray Assembly  
3B Base Wrapper  
3B1 Base End Insulation  
3B2 Base Rear Insulation  
3C Base Front Panel Assembly  
3D Burner Tray  
[2] 720601  
[1] 72060035 [1] 72060045 [1] 72060055 [1] 72060065  
[1] 618600341 [1] 618600441 [1] 618600541 [1] 618600641  
[1] 718600305 [1] 718600405 [1] 718600505 [1] 718600605  
3E Base Leg Assembly  
3E1 Base Leg  
[4] 6186001  
[4] 71860021  
3E2 Nylon Glide  
8186006  
3F Burner Access Panel  
3G Jacket Attachment Bracket, Left  
3H Jacket Attachment Bracket, Right  
[1] 718600361 [1] 718600461 [1] 718600561 [1] 718600661  
[1] 70460011  
[1] 70460012  
Cerafelt Gasket, ½" x 2"  
3J  
[1] 6206002  
Johns-Mansville CRF-400  
Screw, Self-Tapping Type F, Phillips Pan  
Head, ¼-20 x ½", Plated  
3K  
[20] 80860700  
3L Screw, Self Tapping, 5/16"-18 x 1¼"  
3M Flat Washer, 5/16"  
[4] 80860717  
[4] Common Hardware  
[4] 80860464  
3N Hex Lock Nut, 5/16"-18  
3P Screw, Sheet Metal, Phillips Head, #8 x ½"  
[2] Common Hardware  
26  
[Quantity] Part Number  
Key No.  
Description  
203PV  
204PV  
205PV  
206PV  
4. Manifold and Main Burners  
4A  
4B  
4C  
Main Burner  
[2] 8236099  
[4] 8236099  
[6] 8236099  
[8] 8236099  
Main Burner with 60° Pilot Bracket  
Manifold  
[1] 8236098  
[1] 82260033 [1] 82260043 [1] 82260053 [1] 82260063  
Main Burner Orifice, #44, Orange  
Main Burner Orifice, #45, Pink  
[3] 822712  
-----  
-----  
-----  
-----  
4D (Natural  
Gas Only)  
[5] 822711  
[7] 822711  
[9] 822711  
4D  
Main Burner Orifice, #55, Green  
[3] 822708  
-----  
-----  
-----  
-----  
(LP/Propane  
Only)  
Main Burner Orifice, 1.25mm, Purple  
Screw, Machine, #10-32 x 3/16"  
[5] 822705  
[7] 822705  
[9] 822705  
4E  
4F  
[2] 80860800  
[4] 80860700  
Screw, Self-Tapping Type F, Phillips Pan  
Head, 1/4-20 x 1/2", Plated  
27  
[Quantity] Part Number  
204PV 205PV  
Key  
No.  
Description  
203PV  
206PV  
5. Pilot Burner and Gas Valve  
P i l o t A s s e m b l y , N a t u r a l G a s , H o n e y w e l l Q 3 4 8 A 1 3 3 3  
[1] 8236104  
5A  
Pilot Assembly, LP Gas, Honeywell Q348A1341  
[1] 8236107  
Pilot Orifice, Natural Gas Honeywell 388146NE  
5B  
Included with Key No.5A  
Pilot Orifice, LP/Propane Honeywell 388146KP  
5C  
5D  
Compression Nut/Fitting, 1/8" OD x ¼ NPT  
Pilot Tubing, 1/8" OD x 30"  
Included with Key No.5A and 5E  
[1] 8236110  
G a s V a l v e , ½ x ½ , N a t u r a l G a s , H o n e y w e l l V R 8 2 0 4 C 6 0 0 0  
[1] 81660176  
5E  
G a s V a l v e , ½ x ½ , L P / P r o p a n e , H o n e y w e l l V R 8 2 0 4 C 6 0 1 8  
[1] 81660180  
5F  
Igniter/Sensor Cable, 36", Honeywell 394800-36  
Ground Wire Assembly  
[1] 8236084  
[1] 6136054  
5G  
28  
[Quantity] Part Number  
Key  
No.  
Description  
203PV  
204PV  
205PV  
206PV  
6. Jacket  
6A  
6B  
6C  
6D  
6E  
6F  
6G  
6H  
6J  
Jacket Wrap-A-Round Panel (1)  
[1] 604170312  
[1] 6041703221  
[1] 6041703222  
[1] 604170334  
[1] 604170344  
[1] 604170313  
[1] 604170412  
[1] 6041704221  
[1] 6041704222  
[1] 604170434  
[1] 604170444  
[1] 604170413  
[1] 604170512  
[1] 6041705221  
[1] 6041705222  
[1] 604170534  
[1] 604170544  
[1] 604170513  
[1] 604170612  
[1] 6041706221  
[1] 6041706222  
[1] 604170634  
[1] 604170644  
[1] 604170613  
Jacket Upper Vestibule Panel (1)  
Jacket Lower Vestibule Panel  
Jacket Top Panel (1) (2)  
Jacket Front Removable Door  
Jacket Lower Front Panel  
Screw, Sheet Metal, #8 x ½"  
Snap Bushing, Heyco SB-1093-15  
Snap Bushing, Heyco SB-2000-26  
Snap Bushing, Heyco SB-437-5  
Burnham Logo Plate  
[20] Common Hardware  
[2] 8136257  
[1] 8136266  
[1] 8136048  
[1] 81460107  
6K  
6L  
(1) For boilers installed in Canada, indicate 'For Canada' when ordering.  
(2) For boilers installed in California, indicate 'For California' when ordering.  
29  
30  
[Quantity] Part Number  
204PV 205PV  
Key No. Description  
203PV  
206PV  
7. Miscellaneous Trim and Controls  
Safety Relief Valve, 30 psi, ¾ NPT,  
7A  
[1] 81660319  
Conbraco 10-408-05  
7B  
Limit, Honeywell L4080D1036  
Immersion Well, ½ NPT  
[1] 80160156  
7 B 1  
Included with 7B  
Immersion Well, ¾ NPT, Honeywell 123870A  
(Dual Limit Only)  
7 B 2  
[1] 80160426  
7 B 3  
7C  
Limit Honeywell L4080B1212 (Dual Limit Only)  
Transformer/Relay, Honeywell R8285D5001  
Relay, DPST, Honeywell R8222U1006  
Junction Box, 4" x 4" x 1½"  
[1] 80160474  
[ 1 ] 8 0 1 6 0 1 5 5 U  
[ 1 ] 8 0 1 6 0 0 9 6 U  
[1] 8136259  
7 C 1  
7 C 2  
7D  
Flame Rollout Switch  
[1] 80160044  
[1] 7186018  
7 D 1  
7E  
Flame Rollout Switch Bracket  
Suction Pressure Switch  
[1] 80160180  
[1] 80160181  
Silicone Tubing, 1/8" x 11"  
Silicone Tubing, 1/8" x 12½"  
7 E 1  
9016001 (Specify Length)  
Silicone Tubing, 1/8" x 13-5/8"  
Silicone Tubing, 1/8" x 15¼"  
7F  
Ignition Module, Honeywell S8670E1007  
Temperature-Pressure Gauge  
[1] 80160108  
[1] 8056164U  
7G  
Circulator with Gaskets, Bell & Gossett NFR-22  
Circulator with Gaskets, Grundfos UP15-42F  
Circulator with Gaskets, Taco 007F  
Circulator with Gaskets, Taco 0010  
Gasket, Bell & Gossett NFR-22 (SLC-30)  
Gasket, Grundfos 510179  
[1] 8056174  
[1] 8056173  
7H  
[1] 8056170  
[1] 8056176  
[ 2 ] 8 0 6 6 0 2 0 2 9  
[ 2 ] 8 0 6 6 0 2 0 1 6  
[ 2 ] 8 0 6 6 0 2 0 0 6  
[ 2 ] 8 0 6 6 0 2 0 1 3  
[4] Common Hardware  
[4] Common Hardware  
[1] 806603011  
7 H 1  
Gasket, Taco '00' Series  
7J  
7 J 1  
7 J 2  
7K  
F l a n g e , 1 ¼ N P T  
Screw, Cap Hex Head, 7/16-14 x 1½"  
Nut, Hex, 7/16-14  
Drain Valve, ¾ NPT, Conbraco 31-606-02  
[Quantity] Part Number  
Key No.  
Description  
203PV  
204PV  
205PV  
206PV  
8. Vent Accessory Carton  
611170322  
611170522  
8A  
8B  
8C  
Vent Connector  
Vent Terminal  
Locking Band  
[1] 8116102  
[1] 8116103  
[1] 8116063  
[1] 8116101  
Silicone Sealant, 3 oz. tube, Dow  
Corning Silastic 732 RTV, or Sil-Bond  
RTV 4500 (Acetoxy)  
8D  
[1] 8056052  
31  
32  

Ativa AT P2000 User Manual
Clarion PROAUDIO DRX7575Z User Manual
Crown Boiler BSI069 User Manual
Cuisinart DLC 2007N User Manual
Follett U155 User Manual
Fujitsu Siemens Computers Convertible Bump Case none User Manual
Indesit Camcorder S 3000 User Manual
Jensen VOM 7SN User Manual
JVC Camcorder GC XA2 User Manual
JVC Everio GZ MS130BU User Manual