Installation & Service Instructions
Performa
24 Eco HE
2
Burner On
Reset
Flame Failure
Power On
bar
This is a Wall Mounted Powered Flue Condensing Combination Boiler Gas Fired Central Heating Unit.
The boiler meets the requirements of Statutory Instrument “ The Boiler (Efficiency) Regulations 1993 No 3083” and is
deemed to meet the requirements of Directive 92/42/EEC on the energy efficiency requirements for new hot water
boilers fired with liquid or gaseous fuels:-
Type test for purpose of Regulation 5 certified by:
Notified Body 0051.
Product/Production certified by:
Notified Body 0086.
For use in GB/IE only.
These instructions include the Benchmark Commissioning Checklist and should be left with the User for safe keeping.
INSTALLER NOTIFICATION GUIDELINES
Choose Building
Regulations Notification
Route
Competent Person's
Building Control
Self Certification Scheme
Contact your relevant Local
Authority Building Control
(LABC) who will arrange
an inspection or contact
a government approved
inspector
Install and Commission this
appliance to manufacturer's
instructions
Complete the
Benchmark Checklist
If you notify via CORGI Scheme,
CORGI will then notify the
relevant Local Authority
Building Control Scheme
on member's behalf
Install and Commission this
appliance to manufacturer's
instructions
Scheme Members only
Complete the
Benchmark Checklist
Call CORGI on: 0870 88 88 777
or log onto:
within 10 days
You must ensure that the
notification number issued by
CORGI is written onto the
Benchmark Checklist
CORGI will record the data and
will send a certificate of
LABC will record the data
and will issue a
compliance to the property
certificate of compliance
Publication No. 5111811
3
LEGISLATION
IMPORTANT - Installation, Commissioning, Service & Repair
Potterton declare that no substances harmful to
health are contained in the appliance or used
during appliance manufacture.
This appliance must be installed in accordance with the manufacturer’s
instructions and the regulations in force. Read the instructions fully before
installing or using the appliance.
The appliance is suitable only for installation in GB
and IE and should be installed in accordance with
the rules in force, and only used in a suitably
ventilated location.
In GB, this must be carried out by a competent person as stated in the Gas
Safety (Installation & Use) Regulations.
In GB, the installation must be carried out by a CORGI
Registered Installer. It must be carried out in
accordance with the relevant requirements of the:
• Gas Safety (Installation & Use) Regulations.
• The appropriate Building Regulations either The
Building Regulations, The Building Regulations
(Scotland), Building Regulations (Northern Ireland).
• The Water Fittings Regulations or Water Byelaws in
Scotland.
Definition of competence: A person who works for a CORGI registered
company and holding current certificates in the relevant ACS modules, is
deemed competent.
In IE, this must be carried out by a competent person as stated in I.S. 813
“Domestic Gas Installations”.
• The Current I.E.E. Wiring Regulations.
Lifting - This product should be lifted and handled by two people. Stooping
should be avoided and protective equipment worn where necessary.
Carrying & lifting equipment should be used as required, e.g. when installing
in a loft space.
Where no specific instructions are given, reference
should be made to the relevant British Standard Code
of Practice.
In IE, the installation must be carried out by a
competent Person and installed in accordance with the
current edition of I.S. 813 ‘Domestic Gas Installations’,
the current Building Regulations and reference should
be made to the current ETCI rules for electrical
installation.
The addition of anything that may interfere with the normal operation of the
appliance without express written permission from the manufacturer or his
agent could invalidate the appliance warranty. In GB this could also infringe
the Gas Safety (Installation and Use) Regulations.
Warning - Check the information on the data plate is compatible with local
All systems must be thoroughly flushed and
treated with inhibitor (see section 6.2).
supply conditions.
Codes of Practice, most recent version should
be used
In GB the following Codes of Practice apply:
Standard
BS 6891
BS 5546
Scope
Gas Installation.
Installation of hot water supplies for
domestic purposes.
BS 5449
BS 6798
BS 5440 Part 1
BS 5440 Part 2
BS 7074
Forced circulation hot water systems.
Installation of gas fired hot water boilers.
Flues.
Ventilation.
Expansion vessels and ancillary equipment
for sealed water systems.
Treatment of water in domestic hot water
central heating systems.
BS 7593
All CORGI registered installers carry a CORGI identification card and have a
registration number. You can check your installer is registered by
telephoning 0870 4012300 or writing to:-
1 Elmwood,
In IE the following Codes of Practice apply:
Standard
I.S. 813
Scope
Domestic Gas Installations.
The following BS standards give valuable additional information;
Chineham Business Park,
Crockford Lane,
Basingstoke. RG24 8WG
BS 5546
Installation of hot water supplies for
domestic purposes.
Forced circulation hot water systems.
Expansion vessels and ancillary equipment
for sealed water systems.
BS 5449
BS 7074
BS 7593
Treatment of water in domestic hot water
central heating systems.
4
Publication No. 5111811
1.0 INTRODUCTION
1.1
Description
1. The Potterton Performa 24 Eco HE is a fully
automatic gas fired wall mounted condensing
combination boiler. It is room sealed and fan
assisted, and will provide central heating and mains
fed domestic hot water.
Case Front Panel
2. The boiler is set to give a maximum output of
25.2 kW (condensing).
3. It is designed for use on Natural Gas (G20) and can
be converted to use Propane.
4. The boiler is suitable for use only on fully pumped
sealed heating systems. Priority is given to domestic
hot water.
5. The boiler data badge gives details of the model,
serial number and Gas Council number and is
situated on the control box. It is visible when the
case front panel is removed (Fig. 1).
6. The boiler is intended to be installed in residential /
commercial / light industrial E.M.C. environments on
a governed meter supply only.
Control Box
7. The boiler must be installed with one of the
purpose designed flues such as the standard
horizontal flue kit, part no. 5111073.
Fig. 1
8. All systems must be thoroughly flushed and
treated with inhibitor (see section 6.2).
Data Badge
1.2
Optional Extras
1. Various flue extensions, bends, vertical flue kits,
control accessories etc. are available as optional
extras. These are detailed in a separate publication.
Publication No. 5111811
5
2.0 GENERAL LAYOUT
2.1
Layout
1
1.
Air Pressure Switch
2.
Expansion Vessel
20
3.
Burner Manifold
19
4.
Automatic Air Vent
5.
DHW Plate Heat Exchanger
Circulation Pump
6.
7.
Drain Off Point
18
17
8.
Pressure Relief Valve
Optional Integral Timer Position
Central Heating System Pressure Gauge
Control PCB
9.
10.
11.
12.
13.
14.
15.
16.
17.
18.
19.
20.
21.
22.
23.
24.
25.
26.
2
3
Control Box
16
15
3-Way Valve Assembly
Condensate Trap
Flame Sensing Electrode
Spark Electrode
Burner
4
5
13
Primary Heat Exchanger
Fan Assembly
6
Secondary Heat Exchanger
On / Off / Reset Selector Switch
Burner & Fault Indicator Neon
Power Neon
7
Flame Failure & Fault Indicator Neon
Central Heating Temperature Control
Hot Water Temperature Control
8
14
12
11
Fig. 2
10
9
2
Burner On
Flame Failure
Power On
Reset
bar
Performa 24 Eco HE
Fig. 3
21
22
23
24
25
26
10
9
6
Publication No. 5111811
3.0 APPLIANCE OPERATION
NOTE: All delay timers mentioned in 3.1 and 3.2
are overridden by domestic hot water demand.
1
Central Heating Circuit
3.1
Central Heating Mode (Fig. 4)
27
7
1. With a demand for heating, the pump circulates
water through the primary circuit. At a pre-
determined flow rate the central heating flow switch
operates, initiating the ignition sequence.
2
3
5
4
26
6
2. The main burner ignites at low rate, then the gas
valve controls the gas rate to maintain the heating
temperature measured by the temperature sensor.
25
24
3. When the flow temperature exceeds the setting
temperature, a 3 minute delay occurs before the
burner relights automatically (anti-cycling). The pump
continues to run during this period.
8
23
9
22
21
11
17
15
10
3.2
Domestic Hot Water Mode (Fig. 5)
20
18
Fig. 4
16
14
13
12
1. Priority is given to the domestic hot water supply.
A demand at a tap or shower will override any central
heating requirement.
19
Key
2. The flow of water will operate the DHW flow switch
which causes the 3 way valve to change position.
This will allow the pump to circulate the primary water
through the DHW plate heat exchanger.
1
2
3
4
5
6
7
8
9
Primary Heat Exchanger
Burner
Ignition Electrode
Flame Sensing Electrode
Gas Valve
14 Gas Inlet
15 Domestic Hot Water Outlet
16 Heating Flow
17 Pressure Gauge
18 Hydraulic Differential Pressure Sensor Microswitch
19 Automatic By-Pass
20 Hydraulic Differential Pressure Sensor
21 Diverter Valve Assembly
22 Domestic Hot Water Flow Priority Assembly
23 Domestic Hot Water Flow Priority Microswitch
24 Temperature Sensor
Pump
Automatic Air Vent
Plate Heat Exchanger
Flow Sensor with Filter
3. The burner will light automatically and the
temperature of the domestic hot water is controlled
by the temperature sensor.
10 Pressure Relief Valve
11 Boiler Drain Point
12 Heating Return
25 Overheat Thermostat
13 Cold Water Inlet On/Off Valve and Filter 26 Expansion Vessel
27 Secondary Heat Exchanger
4. When the domestic hot water demand ceases the
burner will extinguish and the diverter valve will
remain in the domestic hot water mode, unless there
is a demand for central heating.
1
Domestic Hot Water Circuit
IMPORTANT: When the selector switch is in the
‘0’ (Off) position the electrical supply to the boiler
is isolated. The boiler will not operate and the
integral timer (if fitted) will require resetting once
the selector switch is turned to either the DHW
or CH position.
27
7
2
3
5
4
26
6
25
24
8
23
22
9
11
21
17
15
10
20
18
Fig. 5
16
14
13
12
19
Publication No. 5111811
7
4.0 TECHNICAL DATA
Appliance Type
C12
C32
Electrical Protection
IPX4D
Central Heating Primary Circuit
Pressures
Appliance Category
CAT II
2H 3P
NO Class
3
bar
3
2.5
0.5
1-2
x
Safety Discharge
Max Operating
Min Operating
Heat Input CH
Condensate Drain
1” BSP
Max
Min
Flue Terminal
Diameter
100mm
125mm
kW
24.8
10.6
Recommend Operating
Dimensions
Projection
DHW Circuit
Pressures
Max Operating
Min Operating
bar
Heat Output CH (Non-Condensing)
Max
Min
Connections
Gas Supply
Central Heating Flow
Central Heating Return
Cold Water Mains Inlet
DHW Flow
copper tails
22mm
22mm
22mm
15mm
8
0.2
kW
24
9.8
-
-
-
-
-
-
Heat Output CH (Condensing)
Min Operating Pressure
at 11.1 l/min
Max
Min
0.9
kW
25.2
10.1
15mm
15mm
Flow Rates
DHW Flow Rate
@ 30°CRise
l/min
Pressure Relief Discharge
Heat Input DHW
Max
Outercase Dimensions
Casing Height
Overall Height Inc Flue
Elbow
Casing Width
Casing Depth
11.5
9.8
kW
24.8
-
780mm
DHW Flow Rate
@ 35°CRise
Heat Output DHW
Max
-
-
-
965mm
450mm
345mm
Min Working
DHW Flow Rate
2.5
kW
24
Pump
Available Head
Max Gas Rate (Natural Gas - G20)
Clearances
See graph below
(After 10 mins)
Above Casing
Below Casing
Front
Front
L.H. Side
R.H. Side
200 mm Min
200 mm Min
m3/h
2.62
Expansion Vessel - (For Central Heating
only. Integral with appliance)
bar
450 mm Min (For Servicing)
5 mm Min (In Operation)
5 mm Min
5 mm Min (In Operation)
20 mm Min (See Note*)
Burner Pressure (Natural Gas - G20)
Max Rate
10.2 0.5
Min Rate
2 0.2
Min Pre-charge Pressure 0.5
mbar
litre
Inlet Pressure (Natural Gas - G20)
mbar 20
Max Capacity of
CH System
*NOTE: The boiler can be operated with a
clearance of 5mm at the right. This is also
sufficient for routine maintenance.
However a clearance of 20mm is required
if it is necessary to remove the secondary
heat exchanger. This should be considered
when siting the appliance and in the event
of any subsequent alterations in the area
of installation
125
1.0
Primary Water Content
of Boiler (unpressurised)
Burner Injector (Natural Gas - G20)
15 x 1.18mm Diameter
Electrical Supply
230V~ 50H
z
Temperatures
C.H. Flow Temp (adjustable)
(Appliance must be connected to an
earthed supply)
35°C to 85°C max ( 5°C)
Power Consumption
170W
3A
D.H.W. Flow Temp
Weights
Packaged Boiler Carton
Installation Lift Weight
kg
50
43.5
35°C to 65°C max ( 5°C)
dependent upon flow rate
External Fuse Rating
Internal Fuse Rating
Fuse 2A Fast Blow to BS 4265
SEDBUK Declaration For Performa 24 Eco HE
Pump - Available Head
5
The seasonal efficiency (SEDBUK) is 87.3% (89.3% LPG)
4.5
4
Band B
This value is used in the UK Government’s Standard Assessment
Procedure (SAP) for energy rating of dwellings. The test data from
which it has been calculated have been certified by 0051.
3.5
3
2.5
2
LPG Propane - G31
1.5
1
Burner Injector 15 x 0.77mm diameter
0.5
0
Burner Pressure
Propane
Max Rate Min Rate
mbar
21.8 0.5 4.4 0.2
0
200
400
600
800
1000
1200
Inlet Pressures
Flow Rate (l/h)
37
mbar
8
Publication No. 5111811
5.0 DIMENSIONS AND FIXINGS
E
G
A
Dimensions
A 780mm
B 345mm
C 450mm
D 116mm Ø Min.
E 185mm
B
360° Orientation
F 190mm
C
D
G 131mm
Tube Ø 100mm
Fig. 6
F
68mm
Gas Inlet
Heating
Flow
Domestic Hot
Water Outlet
Cold Water
Inlet
Heating
Return
95mm
65mm
65mm
65mm
65mm
265mm
165.7mm
View from under the appliance
Left Hand Side
of Boiler
130mm
Fig. 7
Publication No. 5111811
9
6.0 SYSTEM DETAILS
6.1
Information
1. The Potterton Performa 24 Eco HE Condensing
Combination Boiler is a ‘Water Byelaws Scheme -
Approved Product’. To comply with the Water
Byelaws your attention is drawn to the following
installation requirements and notes (IRN).
a) IRN 001 - See text of entry for installation
requirements and notes.
b) IRN 302 - Byelaw 14.
2. Reference to the WRc publications, ‘Water fittings and
materials directory’ and ‘Water supply byelaws guide’
give full details of byelaws and the IRNs.
6.2
Central Heating Circuit
1. The appliance is suitable for fully pumped SEALED
SYSTEMS ONLY.
Treatment of Water Circulating Systems
• All recirculatory water systems will be subject to
corrosion unless an appropriate water treatment is
applied. This means that the efficiency of the system will
deteriorate as corrosion sludge accumulates within the
system, risking damage to pump and valves, boiler noise
and circulation problems.
• When fitting new systems flux will be evident within the
system, which can lead to damage of system
components.
• All systems must be thoroughly drained and flushed
out. Using for example Betz-Dearborn Sentinel X300 or
X400 or Fernox Superfloc Universal Cleanser which
should be used following the flushing agent
manufacturer’s instructions.
• System additives - corrosion inhibitors and flushing
agents/descalers should be suitable for aluminium and
comply to BS7593 requirements, e.g. Betz-Dearborn
Sentinel X100 and Fernox-Copal which should be used
following the inhibitor manufacturer’s instructions.
Failure to flush and add inhibitor to the system will
invalidate the appliance warranty.
• It is important to check the inhibitor concentration
after installation, system modification and at every
service in accordance with the manufacturer’s
instructions. (Test kits are available from inhibitor
stockists.)
• For information or advice regarding any of the above
contact the Potterton Helpline.
6.3
Bypass
1. The boiler is fitted with an automatic integral
bypass.
6.4
System Control
1. The boiler is designed for use in a heating system
that incorporates external controls, i.e. a minimum of
a timer device.
2. An integral electro-mechanical or electronic timer is
available as an optional extra.
3. For optimum operating conditions and maximum
economy the fitting of a programmable thermostat is
recommended.
10
Publication No. 5111811
6.0 SYSTEM DETAILS
6.5
System Filling and Pressurising
1. A filling point connection on the central heating
return pipework must be provided to facilitate initial
filling and pressurising and also any subsequent
water loss replacement/refilling.
Double
Check
Valve
Stop
Valve
Stop
Valve
2. There are connection points on the mains cold
water inlet and central heating return isolating taps to
which the optional filling loop kit (Part No. 248221)
can be assembled.
3. The filling method adopted must be in accordance
with all relevant water supply regulations and use
approved equipment.
Temporary
Hose
CH
Return
DHW
Mains
Inlet
4. Your attention is drawn to:
Fig. 8
for GB: Guidance G24.2 and recommendation R24.2
of the Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
5. The sealed primary circuits may be filled or
replenished by means of a temporary connection
between the circuit and a supply pipe, provided a
‘Listed’ double check valve or some other no less
effective backflow prevention device is permanently
connected at the inlet to the circuit and the
temporary connection is removed after use.
6.6
Expansion Vessel
(Central Heating only)
1. The appliance expansion vessel is pre-charged to
0.5 bar. Therefore, the minimum cold fill pressure is
0.5 bar. The vessel is suitable for correct operation
for system capacities up to 125 litres. For greater
system capacities an additional expansion vessel
must be fitted. For GB refer to BS 7074 Pt 1. For IE,
the current edition of I.S. 813 “Domestic Gas
Installations”.
Pressure Relief Valve
6.7
Pressure Relief Valve (Fig. 9)
1. The pressure relief valve is set at 3 bar, therefore
all pipework, fittings, etc. should be suitable for
pressures in excess of 3 bar.
Fig. 9
2. The pressure relief discharge pipe should be not
less than 15mm dia, run continuously downward,
and discharge outside the building, preferably over a
drain. It should be routed in such a manner that no
hazard occurs or causes damage to wiring or
electrical components. The end of the pipe should
terminate facing down and towards the wall.
Discharge Pipe
3. The discharge must not be above a window,
entrance or other public access. Consideration must
be given to the possibility that boiling water/steam
could discharge from the pipe.
Publication No. 5111811
11
6.0 SYSTEM DETAILS
6.8
Domestic Hot Water Circuit
Other Tap
Outlets
1. All DHW circuits, connections, fittings, etc. should
be fully in accordance with relevant standards and
water supply regulations.
Boiler
Expansion
Vessel
2. Your attention is drawn to:
for GB: Guidance G17 to G24 and recommendation
R17 to R24 of the Water Regulations Guide.
for IE: the current edition of I.S. 813 “Domestic Gas
Installations”.
Check
Valve
3. A single check valve must be fitted as shown in
Fig. 10 to prevent backflow to the supply pipe and to
ensure the efficient operation of the expansion vessel
which is required to accommodate the thermal
expansion of the water.
Pressure
Reducing Valve
To Hot
Taps
Stop Tap
4. When the domestic water system includes any
device which prevents water expanding back
towards the supply (check valve, loose jumpered
stopcock, water meter, water treatment device) then
Fig. 10
an expansion vessel must be fitted (eg. Zilmet 160ml,
1
2
R / 15bar).
5. If the hot water expansion is not provided for, then
high pressures can develop which may result in
damage to fittings and devices on the system.
6. The boiler’s maximum working mains pressure is 8
bar, therefore all pipework, connections, fittings, etc.
should be suitable for pressures in excess of 8 bar. A
pressure reducing valve must be fitted for pressures
in excess of 8 bar. The manufacturer of any outlet
fittings, such as a shower valve, may require a lower
maximum pressure. The pressure reduction must
take account of all fittings connected to the DHW
system.
6.9
Showers
1. If a shower control is supplied from the appliance
it should be of the thermostatic or pressure balanced
type. Thermostatic type shower valves provide the
best comfort and guard against water at too high a
temperature. Existing controls may not be suitable -
refer to the shower valve manufacturer.
6.10
Hard Water Areas
1. If the area of the installation is recognised as a
HARD WATER AREA then a suitable device should
be fitted to treat the mains water supply to the boiler.
Contact your Water Distribution Company for advice
on suitable devices.
12
Publication No. 5111811
7.0 SITE REQUIREMENTS
20mm/5mm Min
see *NOTE:
7.1
Location
450mm
5mm Min
1. The boiler may be fitted to any suitable wall with
the flue passing through an outside wall or roof and
discharging to atmosphere in a position permitting
satisfactory removal of combustion products and
providing an adequate air supply. The boiler should
be fitted within the building unless otherwise
protected by a suitable enclosure i.e. garage or
outhouse. (The boiler may be fitted inside a cupboard
- see Section 7.3).
200mm Min
2. If the boiler is sited in an unheated enclosure then it
is recommended that frost protection is incorporated
in the control system.
3. If the boiler is fitted in a room containing a bath or
shower reference must be made to the relevant
requirements.
In GB this is the current I.E.E. Wiring Regulations and
Building Regulations.
780mm
In IE reference should be made to the current edition
of I.S. 813 “Domestic Gas Installations” and the
current ETCI rules.
4. If the boiler is to be fitted into a building of timber
frame construction then reference must be made to
the current edition of Institute of Gas Engineers
Publication IGE/UP/7 (Gas Installations in Timber
Framed Housing).
2
Burner On
Flame Failure
Power On
Reset
bar
7.2
Clearances (Fig. 11 & 12)
200mm Min
1. A flat vertical area is required for the installation of
the boiler.
Fig. 11
2. These dimensions include the necessary
clearances around the boiler for case removal,
spanner access and air movement. Additional
clearances may be required for the passage of pipes
around local obstructions such as joists running
parallel to the front face of the boiler.
* NOTE: The boiler can be operated with a
clearance of 5mm at the right. This is also
sufficient for routine maintenance. However a
clearance of 20mm is required if it is necessary to
remove the secondary heat exchanger. This
should be considered when siting the appliance
and in the event of any subsequent alteration in
the area of installation.
450mm Min
For Servicing
Purposes
5mm Min
In Operation
Fig. 12
Publication No. 5111811
13
7.0 SITE REQUIREMENTS
7.3
Ventilation of Compartments
1. Where the appliance is installed in a cupboard or
compartment, no air vents are required.
2. BS 5440: Part 2 refers to room sealed appliances
installed in compartments. The appliance will run
sufficiently cool without ventilation.
7.4
Gas Supply
1. The gas installation should be in accordance with
the relevant standards. In GB this is BS 6891. In IE
this is the current edition of I.S. 813 “Domestic Gas
Installations”.
2. The connection to the appliance is a 22mm
copper tail located at the rear of the gas service
cock (Fig. 13).
3. Ensure that the pipework from the meter to the
appliance is of adequate size. Do not use pipes of a
smaller diameter than the boiler gas connection
(22mm).
7.5
Electrical Supply
1. External wiring must be correctly earthed,
polarised and in accordance with relevant
regulations/rules. In GB this is the current I.E.E.
Wiring Regulations. In IE reference should be made
to the current edition of ETCI rules.
Fig. 13
Gas Service Cock
2. The mains supply is 230V ~ 50Hz fused at 3A
maximum.
NOTE: The method of connection to the
electricity supply must facilitate complete
electrical isolation of the appliance.
Connection may be via a fused double-pole
isolator with a contact separation of at least 3mm
in all poles and servicing the boiler and system
controls only.
14
Publication No. 5111811
7.0 SITE REQUIREMENTS
7.6
Condensate Drain
Termination to an internal soil
Boiler
FAILURE TO INSTALL THE CONDENSATE DISCHARGE
PIPEWORK CORRECTLY WILL AFFECT THE RELIABLE
OPERATION OF THE BOILER
and vent pipe
The condensate discharge pipe MUST NOT RISE at any
point along its length. There MUST be a fall of AT LEAST
2.5° (50mm per metre) along the entire run.
1. The condensate outlet terminates in a 1” BSP nut and
3
4
seal for the connection of 21.5mm ( / in) plastic overflow
pipe which should generally discharge internally into the
household drainage system. If this is not possible,
discharge into an outside drain is acceptable.
450mm min
2. Ensure the discharge of condensate complies with any
national or local regulations in force.
External termination via internal
discharge branch
e.g sink waste - downstream
BS 6798:2000 & Part H1 of the Building Regulations
give further guidance.
Boiler
3. The discharge pipe should be run in a proprietary drain
pipe material e.g. PVC, PVC-U, ABS, PVC-C or PP.
Pipe must terminate
above water level but
below surrounding
surface
4. Metal pipework is NOT suitable for use in condensate
discharge systems.
Sink
5. The pipe should be a minimum of 21.5mm diameter
and must be supported using suitably spaced clips to
prevent sagging.
6. Any pipe fitted externally must not exceed 3 metres.
7. Any condensate discharge pipework external to the
building (or in an unheated part of it e.g. garage) must
be insulated to protect against frost. It is also
recommended that the pipe diameter is increased to
32mm.
External termination to a drain or gully
Boiler
Pipe must terminate
above water level but
below surrounding
surface
8. If the boiler is fitted in an unheated location the entire
condensate discharge pipe should be treated as an
external run.
9. In all cases discharge pipe must be installed to aid
disposal of the condensate. To reduce the risk of
condensate being trapped, as few bends and fittings as
possible should be used.
10. When discharging condensate into a soil stack or
waste pipe the effects of existing plumbing must be
considered. If soil pipes or waste pipes are subjected to
internal pressure fluctuations when WC's are flushed or
sinks emptied then back-pressure may force water out of
the boiler trap and cause appliance lockout.
External termination to a purpose
made soak-away
Boiler
500mm min
Examples are shown of the following methods of
termination:-
i) to an internal soil & vent pipe
ii) via an internal discharge branch (e.g. sink waste)
iii) to a drain or gully
Holes in the soak-away
must face away from the
building
iv) to a purpose made soakaway
Publication No. 5111811
15
7.0 SITE REQUIREMENTS
7.7
Flue
NOTE: Due to the nature of the boiler a plume of
water vapour will be discharged from the flue. This
should be taken into account when siting the flue
terminal.
1. The following guidelines indicate the general
requirements for siting balanced flue terminals. For
GB recommendations are given in BS 5440 Pt 1. For
IE recommendations are given in the current edition of
I.S. 813 “Domestic Gas Installations”.
2. If the terminal discharges onto a pathway or
passageway, check that combustion products will not
cause a nuisance and that the terminal will not
obstruct the passageway.
3. If a terminal is less than 2 metres above a balcony,
above ground or above a flat roof to which people
have access, then a suitable terminal guard must be
provided.
L
B,C
N
K
G
G
D
M
D
H,I
A
J
A
E
F
F
G
Likely flue positions requiring
a flue terminal guard
Fig. 14
Terminal Position with Minimum Distance (Fig. 14)
(mm)
A* Directly below an openable window, air vent or any other
ventilation opening.
300
25
25
25
25
B
C
D
E
F
G
H
I
Below gutters, drain/soil pipe.
Below eaves.
Below balcony/car port roof.
From vertical drain pipes and soil pipes.
From internal or external corners.
Above adjacent ground or balcony level.
From a surface or boundary facing the terminal.
Facing terminals.
300 min
Terminal
Assembly
25
300
600
1200
1200
1500
300
300
J
K
L
For opening (door/window) in car port into dwelling.
Vertically from a terminal on the same wall.
Horizontally from a terminal on the same wall.
Top View Rear Flue
M* Above an opening, air brick, opening window etc.
N* Horizontally to an opening, air brick, opening window etc.
300
Fig. 15
* In addition, the terminal should be no nearer than 150mm to an
opening in the building fabric formed for the purpose of
accommodating a built-in element such as a window frame. See
BS 5440 Pt. 1.
Property Boundary Line
16
Publication No. 5111811
7.0 SITE REQUIREMENTS
7.8
Flue Dimensions
The standard horizontal flue kit allows for flue lengths
between 100mm and 685mm from elbow to terminal
(Fig. 16).
The maximum permissible flue length is: 4 metres.
7.9
Flue Trim
1. The rubber flue trim supplied may be fitted to either
the outside wall or on the inner wall of installation.
Fig. 16
7.10
Terminal Guard (Fig. 17)
1. When codes of practice dictate the use of terminal
guards, they can be obtained from most Plumbers’ and
Builders’ Merchants.
2. There must be a clearance of at least 50mm
between any part of the terminal and the guard.
3. When ordering a terminal guard, quote the appliance
name and model number.
4. The flue terminal guard should be positioned
centrally over the terminal and fixed as illustrated.
Fig. 17
Publication No. 5111811
17
7.0 SITE REQUIREMENTS
7.11
Flue Options
1. The Potterton Performa 24 Eco HE can be fitted
with flue systems as illustrated.
B
2. The standard flue is suitable only for horizontal
applications.
A
3. Maximum permissible equivalent flue lengths
are:-
Horizontal Concentric
Vertical Concentric
Vertical Twin Pipe
4 metres
4 metres
12 metres
4. Any additional “in line” bends in the flue system
must be taken into consideration.
Their equivalent lengths are:-
Horizontal
Flues
Concentric Pipes:
45° bend
93° bend
0.5 metres
1.0 metres
Twin Flue Pipe
45° bend
91.5° bend
0.25 metres
0.50 metres
The elbow supplied with the standard horizontal flue
is not included in any equivalent length calculations
5. The illustrations opposite show examples of
maximum equivalent lengths.
6. Instructions for guidance and fitting are included
in each kit, where appropriate.
Vertical
Flues
(Twin Pipe)
NOTE: Flue length is measured from point A to B
as shown.
B
A
Vertical
Flues
B
A
18
Publication No. 5111811
8.0 INSTALLATION
8.1
Initial Preparation
The gas supply, gas type and pressure must be
checked for suitability before connection (see
Section 7.4).
1. After considering the site requirements
(see Section 7.0) position the fixing template on the
wall ensuring it is level both horizontally and
vertically.
2. Mark the position of the two most suitable fixing
slots for the wall plate and boiler lower fixing holes.
It is preferable to use the horizontal fixing slots. For
side flue exit, mark as shown (Fig. 18).
190mm
3. Mark the position of the centre of the flue hole
(rear exit). For side flue exit, mark as shown.
4. If required, mark the position of the gas and water
pipes. Remove the template.
5. Cut the hole for the flue (minimum diameter
116mm).
6. Drill the wall as previously marked to accept the
wall plugs supplied. Secure the wall plate using two
of the fixing screws.
For Side Flue Exit
Fig. 18
7. Using a spirit level ensure that the plate is level
before finally tightening the screws.
8.2
Flushing
1. Connect a tube to the central heating flow or
return pipe (Fig. 19).
2. Flush thoroughly (see System Details, Section
6.2).
8.3
Preparing The Boiler
Flushing Tube
1. Remove all packaging.
2. Stand the boiler on its base by using the rear
lower edge as a pivot.
NOTE: A small amount of water may drain from
the boiler in the upright position.
Fig. 19
Central Heating Return
Publication No. 5111811
19
Wall Plate
8.0 INSTALLATION
8.4
Fitting The Boiler
1. Lift the boiler using the lower edges. Engage the
slots at the top rear of the boiler on the wall plate
hooks (Fig. 20).
2. Ensure that the boiler is level and sits against the
wall.
3. Take the two steel washers and remaining screws.
Using the previously drilled and plugged holes,
secure the bottom of the boiler to the wall (Fig. 21).
4. Remove the elbows, valves and sealing washers
from the packaging. The 3/4 in valve with internal
filter must be fitted to the central heating return. The
filter is visible through the branch connection of the
valve.
Fig. 20
Securing Screw
5. Using the sealing washers provided connect the
valves to the heating flow and return, and the cold
water inlet.
6. Connect the elbows to the gas service cock and
hot water outlet pipe, and then connect the elbows
to the boiler. Connect the elbows with flared ends to
the valves.
Washer
7. Ensure that the sealing washers are used on all
connections. The rubber washers must be used on
the gas connections.
Fig. 21
8. The gas and water supplies, central heating flow
and return and domestic hot water flow can now be
connected.
8.5
Fitting the Pressure Relief
Discharge Pipe (Fig. 22)
Pressure Relief Valve
1. Remove the discharge pipe from the kit.
2. Determine the routing of the discharge pipe in the
vicinity of the boiler. Make up as much of the
pipework as is practical, including the discharge pipe
supplied.
Fig. 22
3. The pipework must be at least 15mm diameter
and run continuously downwards to a discharge
point outside the building. See section 6.7 for further
details.
Discharge Pipe
4. Using one of the sealing washers, connect the
discharge pipe to the adaptor and tighten the nut.
5. Complete the discharge pipework and route it to
the outside discharge point.
IMPORTANT: Make all soldered joints before
connecting to the pressure relief valve.
20
Publication No. 5111811
8.0 INSTALLATION
8.6
Condensate Drain (see section 7.6)
1. Connect the condensate drain using the 1” BSP
nut and seal supplied.
Ensure the discharge of condensate complies with
any national or local regulations in force (see
British Gas “Guidance Notes for the Installation of
Domestic Gas Condensing Boilers”.
2. The condensate outlet terminates in a 1” BSP nut
3
4
and seal for the connection of 21.5mm ( / in) plastic
overflow pipe which should generally discharge
internally into the household drainage system. If this
is not possible, discharge into an outside drain is
acceptable.
Fig. 23
8.7
Fitting The Flue
HORIZONTAL FLUE
1. The standard flue is suitable for lengths between
100mm minimum and 685mm maximum, as
measured from the edge of the flue elbow outlet to
the joint between the terminal and air duct (Fig. 23).
Flue Elbow
Wall Thickness
2. Locate the flue elbow on the adaptor at the top of
the boiler. Set the elbow to the required orientation
(Fig. 24).
NOTE: The flue elbow is angled at 93 degrees to
ensure a fall back to the boiler.
(X)
Adaptor
3. Measure the distance from the outside wall face to
the elbow. This dimension will be known as ‘X’
(Fig. 25).
4. To dimension ‘X’ add 50mm. This dimension to be
known as ‘Y’.
IMPORTANT: Check all dimensions before cutting.
Fig. 24
(X)
Wall Thickness
Fig. 25
Publication No. 5111811
21
8.0 INSTALLATION
8.7
Fitting the Flue (Cont)
Waste
Y
5. Mark dimension ‘Y’ on the flue as shown (Fig. 26).
Carefully cut the waste material from the flue,
ensuring that the ducts are square and free from
burrs.
6. The inner flue duct support bracket may be in the
waste portion of the flue. In this case retrieve the
bracket before discarding the waste.
Flue
Fig. 26
7. Take the inner flue support bracket (if not already
fitted) and engage it over the flue duct. This will
centralise the flue and air ducts, and ease assembly
(Fig. 27).
Inner Flue Support Bracket
8. Insert the flue through the hole in the wall. Fit the
elbow to the boiler adaptor, ensuring that it is
pushed fully in.
9. Draw the flue back through the wall and engage it
in the elbow. It may be necessary to use soap
solution or similar to ease assembly of the elbow
adaptor and flue (Fig. 28).
Fig. 27
10. Make good between the wall and air duct
outside the building.
11. Fit the flue trim if required, and if necessary fit a
terminal guard (see Section 7.9 & 7.10).
VERTICAL FLUE
1. Only a flue approved with the Potterton Performa
24 Eco HE can be used.
2. For information on vertical flues consult the
Potterton Flue Guide brochure.
Flue Elbow
Flue Trim
Fig. 28
22
Publication No. 5111811
8.0 INSTALLATION
8.8
Making The Electrical Connections
Fig. 30
To connect the mains input cable proceed as follows:-
1. Slacken the facia panel securing screws and lift the
outercase panel so that its securing tabs are clear of
the facia. Remove the panel.
2. Completely undo the screws securing the facia
panel and hinge it down (Fig. 29).
Control Box Cover
3. Remove the control box cover securing screws.
Disengage the barbs on the control box from the
cover. Remove the cover (Fig. 30).
4. Slacken the cable clamp on the LH side of the
boiler chassis (Fig. 31). Insert the cable through the
clamp and route it to the terminal block.
5. Slacken the screws in the terminal block, connect
the input cable, and tighten the screws.
Fig. 29
Fig. 31
Facia Panel
6. If an external control is to be connected it can be
done at this point. Run the input cable from the
external control through the second cable clamp on
the boiler chassis. Refer to the instructions supplied
with the control.
Cable Clamp
Frost Thermostat
br
b
L
N
L
N
Fuse
External Clock
g/y
bk
bk
7. To connect external control(s) remove the link
between terminals 1 & 2. The 230V supply at
terminal 1 can be connected to the external
control as shown. The switched output from the
external control must be connected to terminal 2.
(Figs. 32).
Fused supply 3A
230V ~ 50Hz
Always fit fast
blow 2A fuse
1
230 V
N
2
br
b
Live (brown)
SL
Neutral (blue)
g/y
bk
bk
Earth (green/yellow)
Room Thermostat
1
230V
2
IMPORTANT: If an integral timer is fitted to the
boiler an external frost thermostat wired as
shown will not operate correctly. Only external
timers may be used in such installations, as in
the diagram.
NOTE: If the room thermostat being used
incorporates an anticipator it MUST be wired as
shown in Fig. 32.
Terminal Block
Fig. 32
IMPORTANT: The external control MUST be
suitable for 230V switching.
Functional Flow Diagram
8. Ensure that both mains input and, where fitted,
external control input cables have sufficient slack to
allow the control box to drop down. Tighten the cable
clamp(s) on the boiler chassis.
Pump
L
230 V
External
Controls
br
br
b
b
N
br
b
br
Pressure Switch
Fan
br
9. If an optional integral timer is to be used it should
be fitted at this point. Refer to the instructions
supplied with the timer. NOTE: An external frost
thermostat cannot be used with the integral timer.
Selector /
Reset Switch
N
b
bk
b
b
Flue Thermostat
Safety Overheat Thermostat
r
r
NTC Sensor
b
r
bk
PCB
bk
bk
Gas Valve Modulator
8.9
Preliminary Electrical Checks
Key to Wiring
b - blue
br - brown
bk - black
Spark Electrode
Gas Valve
b
br
bk
1. Prior to commissioning the boiler preliminary
electrical system checks should be carried out.
Condensate Trap
r
- red
Flame Sensing Electrode
Fig. 33
g - green
w - white
r
2. These should be performed using a suitable meter,
and include checks for Ground Continuity,
Resistance to Ground, Short Circuit and Polarity.
Hydraulic Differential Pressure Switch
DHW Flow Priority Microswitch
r
g
g
Publication No. 5111811
23
9.0 COMMISSIONING
9.1
Commissioning the Boiler
1. Reference should be made to BS 5449 Section 5
when commissioning the boiler.
2. Open the mains water supply to the boiler.
3. Open all hot water taps to purge the DHW system.
4. Ensure that the filling loop is connected and open,
then open the heating flow and return valves on the
boiler.
5. Open the screw on the automatic air vent
(Fig. 35).
6. The system must be flushed in accordance with
BS 7593 (see Section 6.2) and the flushing agent
manufacturers instructions.
Screw
Fig. 35
7. Pressurise the system to at least 0.5 bar then close
and disconnect the filling loop (Fig. 34).
Pressure Gauge
2
8. Turn the gas supply on and purge the system
according to in GB BS 6891 and in IE I.S. 813
“Domestic Gas Installations”.
bar
Selector Switch
Fig. 34
9. Test for gas soundness.
Automatic Air Vent
10. If at any time during commissioning it is required
to terminate a particular cycle, turn the selector to the
OFF position and then back to either ( ) or (
(Fig. 36).
)
2
Burner On
Reset
Flame Failure
Power On
bar
Performa 24 Eco HE
Fig. 36
Central Heating
Hot Water
Temperature Control
Temperature Control
24
Publication No. 5111811
9.0 COMMISSIONING
9.2
Checking the Burner Pressure
1. Turn on the gas and electrical supplies to the boiler
and ensure that all external controls are calling for
heat.
2. Set the hot water and central heating temperature
controls to maximum and the selector switch to the
OFF position (Fig. 37).
Selector Switch
3. Slacken the pressure test point sealing screw on
the gas valve and connect a pressure gauge (Fig. 38).
4. Disconnect the sensing tube from the gas valve.
2
Burner On
Flame Failure
Power On
Reset
bar
5. Turn the selector switch fully anticlockwise against
the spring pressure to the reset position and hold for
2 seconds to reset the boiler.
Performa 24 Eco HE
Fig. 37
Central Heating
Temperature Control
Hot Water
Temperature Control
6. Turn the selector switch to the Cental Heating and
Domestic Hot Water position (
light ( ) will illuminate (Fig. 37).
). The power ON
7. Turn on a hot water tap to give a flow rate of at
least 10 l/min.
Pressure Test Point
Sealing Screw
8. The pressure should be :-
NG
Propane
10.2 mbar
21.8 mbar
If not, check that the gas supply pressure is correct
(Natural Gas 20mbar, and Propane 37mbar).
Gas Valve
Minimum
Pressure
Screw
9. The pressure can be adjusted if required.
10. To check and set minimum pressure first remove
one of the modulator wires.
Fig. 38
Adjusting the Pressure (Fig 39)
11. Remove the plastic protection cap from the
pressure adjustment nuts on the valve.
Plastic
12. The smaller nut (5mm) adjusts minimum pressure Protection
Cap
and the larger nut (8mm) maximum pressure.
13. Using a suitable spanner adjust the relevant nut
until the correct pressure is achieved.
14. Once the pressure has been set turn the boiler off Modulator
Wire
and disconnect the pressure gauge.
Maximum Rate
Adjustment Nut
Minimum Rate
Adjustment Nut
15. Tighten the pressure test screw and refit the
modulator to the valve. Reassemble in reverse order.
NOTE: Gas Valve Electrical
Plug/Igniter not shown for clarity.
Fig. 39
Publication No. 5111811
25
10.0 COMPLETION
Case Front Panel
10.1
Completion
1. Hinge the facia panel upwards and engage the
securing screws. Refit the case front panel and
tighten the screws (Fig. 40).
2. Instruct the user in the operation of the boiler and
system, explaining the operational sequence.
3. Carefully read and complete all sections of the
Benchmark Commissioning Checklist at the rear of
this publication that are relevant to the appliance
and installation. These details will be required in the
event of any warranty work. The publication must be
handed to the user for safe keeping and each
subsequent regular service visit recorded.
4. For IE, it is necessary to complete a “Declaration
of Conformity” to indicate compliance with I.S. 813.
An example of this is given in I.S. 813 “Domestic
Gas Installations”. This is in addition to the
Benchmark Commissioning Checklist.
Facia Panel
Fig. 40
5. Hand over the Users Operating, Installation and
Servicing Instructions, giving advice on the
necessity of regular servicing.
26
Publication No. 5111811
11.0 SERVICING THE BOILER
Case Front Panel
11 .1 Annual Servicing
1. For reasons of safety and economy, it is
recommended that the boiler is serviced annually.
Servicing must be performed by a competent person.
2. After servicing, complete the relevant Service
Interval Record section of the Benchmark
Commissioning Checklist at the rear of this
publication.
3. Ensure that the boiler is cool.
4. Ensure that both the gas and electrical supplies
to the boiler are isolated.
Fig. 41
5. Slacken the screws securing the facia panel. Lift the
outercase panel so that its securing tabs are clear of
the facia. Remove the panel (Fig. 41).
Facia Panel
6. Remove the screws securing the inner door panel.
Lift the panel slightly to disengage it from the studs on
top of the case (Fig. 43).
Fan Wires
Fan
7. Note the positions of the three wires on the fan
motor and remove them. Remove the sensing tube
from the fan spigot (Fig. 42).
8. Slacken the screws on the fan spigot outlet pipe
clamp. Ease the clamp inwards over the pipe.
Sensing
Tube
9. Remove the four screws securing the combustion
box door and remove the door (Fig. 43).
Ease Fan Spigot Outlet
Pipe Clamp Inwards
Fig. 42
Fan Spigot Outlet Pipe
Combustion
Box Door
Inner Door
Panel
Fig. 43
Publication No. 5111811
27
Baffle
11.0 SERVICING THE BOILER
Tab
Spring Clip
11.1
Annual Servicing (Cont)
10. Ease the front edge of the left hand baffle
upwards, disengaging the spring clip. Disengage the
tab on the baffle from the slot in the fan hood (Fig.44).
11. Undo the screws securing the fan hood assembly
to the appliance back panel, and draw the fan and
hood assembly forwards (Fig. 45).
Fig. 44
12. Draw the burner out of the combustion box,
pulling the electrode grommets from the slots in the
combustion box lower panel (Fig. 46).
Fan and Hood
Assembly
13. Disconnect the electrode leads and grommets
from the electrodes. Completely remove the burner
(Fig. 46).
Fig. 45
14. Brush any deposits from the injectors. Do not use
a pin or wire to clean them.
15. Brush the burner blades and venturis and clean
the combustion box.
16. Ensure that the heat exchanger fins are clear of
any obstruction.
Fig. 46
NOTE: If necessary the secondary heat exchanger
may be dismantled - see section 12.23
Electrode
Grommets
D.H.W. Filters (Fig. 48)
17. If the flow of domestic hot water is diminished, it
may be necessary to clean the filters.
Threaded
Bush
Fig. 47
18. Initially check the cold water inlet tap filter.
19. Turn the tap off. Undo the blanking cap and
remove the threaded bush (Fig. 47).
Burner
20. Extract the filter and rinse thoroughly in clean
water. Reassemble and check the flow. If required
clean the manifold filter as described below.
Electrode
Leads
Gas Supply Pipe
Blanking
Cap
Cold Water
Inlet Tap
21. Undo the filter cartridge from the inlet/return
manifold.
22. Dismantle the cartridge and carefully remove the
flow regulator and filter gauze. Rinse them thoroughly
in clean water and reassemble in reverse order.
Cartridge
Body
23. Check that the pressure vessel charge is 0.5bar,
reassemble in reverse order of dismantling.
Filter Gauze
24. Turn the selector switch fully anticlockwise
Fig. 48
against the spring pressure to position R and hold for
2 seconds to reset the boiler before recommissioning.
Fig. 55
Inlet / Return Manifold
25. Complete the relevant Service Interval Record
section of the Benchmark Commissioning Checklist
at the rear of this publication and then hand it back to
the user.
Flow
Regulator
Venturi
28
Publication No. 5111811
12.0 CHANGING COMPONENTS
IMPORTANT: When changing components ensure
that both the gas and electrical supplies to the
boiler are isolated before any work is started.
Pressure
Switch
See Section 11.1 “Annual Servicing” for removal of
case panel, door etc.
Fig. 49
Sensing
Tubes
12.1
Fan (Figs. 50 & 51)
-
+
1. Note the positions of the three wires on the fan
motor and remove them. Remove the sensing tube
from the fan spigot.
b
br
Pressure
Switch Wires
Fan Wires
2. Slacken the screws on the fan spigot outlet pipe
clamp. Ease the clamp inwards over the pipe.
3. Remove the four screws securing the combustion
box door and remove the door.
Fan
4. Ease the front edge of the left hand baffle upwards,
disengaging the spring clip. Disengage the tab on the
baffle from the slot in the fan hood.
5. Undo the screws securing the fan hood to the
appliance back panel, and draw the fan and hood
assembly forwards.
Sensing
Tube
6. Remove the screws and spring washers securing
the fan to the hood. Transfer the flue spigot outlet pipe
to the new fan.
Ease Fan Spigot Outlet
Pipe Clamp Inwards
7. Fit the new fan to the hood using the screws and
spring washers previously removed.
Fig. 50
8. Reassemble in reverse order of dismantling.
12.2
Pressure Switch (Fig. 49)
Fan Spigot Outlet Pipe
Baffle
1. Remove the fan as described in section 12.1.
2. Note the positions of the sensing tubes and wires
and remove them.
Tab
Spring Clip
3. Remove the two screws holding the pressure switch
to the bracket on the combustion box top panel.
Fan
4. Fit the new pressure switch and reassemble all
components in reverse order of dismantling.
Fan Hood
Fig. 51
Spring Washer
Securing Screw
Publication No. 5111811
29
12.0 CHANGING COMPONENTS
12.3
Heat Exchanger (Fig. 52)
1. Remove the fan as described in section 12.1.
2. Drain the primary circuit. Prise the pipe
connecting clips off the joints in the flow and return
pipes. Remove the heat exchanger return pipe.
Pipe Connecting Clips
3. Lift the heat exchanger to disconnect the flow
pipe joint. Withdraw it from the appliance, taking
care not to damage the rear insulation piece.
4. Fit the new heat exchanger, ensuring that the
tabs on the side insulation carriers engage in the
slots in the heat exchanger side plates.
5. Reassemble in reverse order of dismantling, and
repressurise the system.
12.4
Burner (Fig. 53)
1. Remove the four screws securing the combustion
box door and remove the door.
Fig. 52
2. Draw the burner out of the combustion box,
pulling the electrode grommets from the slots in the
combustion box lower panel.
Heat Exchanger
3. Disconnect the electrode leads and grommets
from the electrodes. Completely remove the burner.
4. Undo the screws securing the electrodes to the
burner. Examine the condition of the electrodes,
replacing if necessary. Fit the electrodes to the new
burner.
5. Engage the burner location brackets over the
studs on the injector manifold and reassemble in
reverse order.
Electrodes
Burner
Fig. 53
Electrode
Grommets
Electrode
Leads
30
Publication No. 5111811
12.0 CHANGING COMPONENTS
12.5
Injectors (Fig. 54)
Injector
Manifold
Inlet Elbow
1. Remove the burner as described in Section 12.4.
Injector
2. Undo the screws securing the injector manifold to
the inlet elbow and remove the manifold.
Fig. 54
3. Unscrew and replace injectors as required and
examine the sealing gasket, replacing as necessary.
Reassemble in reverse order.
Gasket
12.6
Electrodes (Fig. 54)
1. Remove the four screws securing the combustion
box door and remove the door.
Burner
Electrodes
2. Draw the burner out of the combustion box,
pulling the electrode grommets from the slots in the
combustion box lower panel.
Electrode
Grommets
3. Disconnect the lead and grommet from the
electrode being replaced. Undo the securing screw
and withdraw the electrode to the burner.
Electrode
Leads
4. Reassemble in reverse order.
12.7
Insulation (Fig. 55)
1. Remove the four screws securing the combustion
box door and remove the door.
2. Slide the side insulation pieces carefully out of
their carriers.
3. To replace the rear insulation piece it is necessary
to remove the heat exchanger as described in
Section 12.3 and slide out the side pieces.
4. The combustion box door insulation piece can be
replaced by carefully bending up the two retaining
tabs.
Side Insulation
Rear Insulation
5. Replace all insulation pieces and reassemble in
reverse order.
13.8
Side Insulation
Combustion
Box Door
Front Insulation
Fig. 55
Publication No. 5111811
31
12.0 CHANGING COMPONENTS
12.8
Gas Valve (Fig. 56)
Modulator
Wires
1. Undo the nut on the gas feed pipe at the tap rail
under the boiler.
Ignition
Lead
2. Completely undo the securing screws and hinge
the facia panel down.
Gas Valve
3. Disconnect the wires from the valve modulator and
the ignition lead from the spark generator. Disconnect
the pressure sensing pipe from the valve. Undo the
screw securing the spark generator electrical plug to
the valve and disconnect the plug.
4. Pull the earth wire off the spade terminal on the
valve.
Electrical
Plug
5. Remove the screws securing the inlet pipe flange
to the tap rail and those securing the outlet manifold
to the burner manifold.
Earth Wire
Inlet Pipe
6. Remove the valve from the boiler.
Gas Feed
Pipe
7. Note the orientation of the inlet pipe and outlet
manifold. Undo the securing screws and remove the
pipe and manifold.
Fig. 56
8. Examine the ‘O’ ring seals for damage, replacing
as necessary.
9. Fit the inlet pipe and outlet manifold to the new
valve, ensuring that the ‘O’ ring seals are in place.
10. Reassemble in reverse order and check the
burner pressure (Section 9.2).
Flow Pipe
12.9
Temperature Sensor (Fig. 57)
1. Ease the retaining tab on the sensor away and
disconnect the electrical plug.
Safety
Thermostat
2. Unscrew the sensor from it’s pocket and
reassemble in reverse order. The plug will only fit one
way.
12.10 Safety Thermostat (Fig. 57)
1. Pull the two electrical connections off the
thermostat.
Temperature
Sensor
2. Remove the screws securing the thermostat to the
mounting plate on the flow pipe.
Fig. 57
3. Reassemble in reverse order. The thermostat is not
polarised - either wire can fit either terminal on the
thermostat.
32
Publication No. 5111811
12.0 CHANGING COMPONENTS
12.11 Pump - Head Only (Figs. 58 & 59)
1. Drain the primary circuit and remove the socket
head screws securing the pump head to the body
and draw the head away.
2. Undo the screw on the pump wiring cover and
remove the cover. Using a suitable flat bladed screw
driver press the cable securing levers downwards to
release each wire after noting their position.
3. A standard Grundfos 15-60 replacement head can
now be fitted. Connect the wiring to the new head.
The pump speed must be set to 3.
4. Reassemble in reverse order.
12.12 Pump - Complete (Figs. 59 & 60)
1. Drain the primary circuit and unscrew the
automatic air vent from the pump body. Undo the
two screws securing the body to the pipe and
manifold and draw the pump forwards.
Pump Wiring
Cover
Pump Body
2. Undo the screw on the pump wiring cover and
remove the cover. Using a suitable flat bladed screw
driver press the cable securing levers downwards to
release each wire after noting their position.
3. Connect the wiring to the new pump. Examine the
‘O’ ring seals on the return pipe and manifold,
replacing if necessary.
Socket Headed
Screw
4. Fit the air vent to the pump body and reassemble
in reverse order.
Pump Head
Fig. 58
12.13 Automatic Air Vent (Fig. 60)
1. Drain the primary circuit and unscrew the
automatic air vent from the pump body.
2. Examine the ‘O’ ring seal, replacing if necessary,
and fit it to the new automatic air vent.
Pump Setting
Automatic
Air Vent
Fig. 59
3. Reassemble in reverse order.
Pump Wiring
Cover
Fig. 60
Publication No. 5111811
33
12.0 CHANGING COMPONENTS
12.14 Pressure Gauge (Figs. 61 & 62)
1. Drain the primary circuit and undo the nut on the
pressure gauge capillary.
2. Remove the timer cover and ease the timer wiring
aside. Undo the screws securing the gauge retaining
bracket.
Fig. 61
3. Remove the bracket and gauge assembly.
Depress the barbs on the side of the gauge and
remove the retaining bracket.
Pressure Gauge
Capillary
Gauge Retaining
Bracket
4. Reassemble in reverse order.
12.15 Expansion Vessel (Fig. 63)
1. To replace the expansion vessel it is necessary to
remove the boiler from the wall.
Timer Cover
NOTE: Alternatively a vessel of equivalent
capacity can be fitted on the system return pipe
as close as possible to the boiler.
Pressure Gauge
Fig. 62
2. Drain the system and undo all gas, water and
condensate drain connections. Remove the flue
elbow.
Expansion Vessel
3. Lift the boiler off the wall bracket and lay it on it’s
side on a clean flat surface.
4. Undo the nut on the vessel outlet spigot, and
remove the locknut and spring washer securing the
spigot to the boiler chassis.
Retaining Clip
Upper Cross
Member
5. Undo the screws and remove the appliance upper
cross member. Slide the expansion vessel out of the
retaining clips.
Fig. 63
6. Reassemble in reverse order. Fully recommission
the appliance and system.
Vessel Outlet
Spigot
Boiler
Chassis
12.16 Condensate Trap (Fig. 64)
Spring
Washer
Lock Nut
1. Disconnect the two sensing wires from the trap
connections.
2. Squeeze together the wire spring clip to release
and ease the inlet pipe from the trap spigot.
Inlet Pipe
Sensing Wires
Wire Spring
Clip
3. Undo the nut securing the condensate drain pipe
to the trap. Disconnect the pipe and sealing washer.
4. From underneath the boiler remove the screws
securing the trap bracket.
Condensate
Trap
5. Remove the trap and bracket from the boiler.
Undo the locknut securing the trap to the bracket.
Bracket
6. Reassemble in reverse order.
Fig. 64
Condensate
Drain Pipe
34
Publication No. 5111811
12.0 CHANGING COMPONENTS
12.17 Pressure Relief Valve (Fig. 65)
1. Drain the primary circuit.
2. Disconnect the discharge pipe from the valve.
Using a suitable hexagon key undo the grub screw
sufficiently to release the valve.
3. Note the orientation of the valve, rotate it and
withdraw it from the manifold.
4. Fit the new valve and ‘O’ ring seal and set to the
previously noted orientation. Reassemble in reverse
order.
12.18 P.C.B. (Fig. 67)
‘O’ ring seal
1. Note the settings of the temperature control
knobs. Rotate the knobs fully anticlockwise and pull
them off the drive pins.
Grub Screw
Pressure Relief Valve
2. Completely undo the screws securing the control
box cover and release the cover retaining barbs from
their slots. Disengage the rear of the cover from the
control box hinge pin (Fig. 66).
Fig. 65
Discharge Pipe
3. Note the position of all plugs and wires on the
P.C.B. and disconnect them. Pull the drive pins off
the P.C.B.
4. Undo the securing screws and remove the P.C.B.
5. Reassemble in reverse order, ensuring that the
temperature controllers are reset to their previous
positions.
Fig. 66
Control Box Cover
P.C.B.
12.19 Selector Switch (Fig. 67)
1. Note the setting of the selector switch knob and
carefully pull it off the facia.
Selector
Switch
2. Completely undo the screws securing the control
box cover and release the cover retaining barbs from
their slots. Disengage the rear of the cover from the
control box hinge pin (Fig. 66).
Drive Pins
3. Note the position of the electrical connections and
the orientation of the switch. Remove the electrical
connections.
Fig. 67
4. Remove the screws securing the switch to the
facia panel.
Facia
5. Fit the new switch, ensuring that it is correctly
positioned and reassemble in reverse order.
Selector Switch Knob
Temperature Control
Knobs
Publication No. 5111811
35
12.0 CHANGING COMPONENTS
Plate Heat Exchanger
12.20 Plate Heat Exchanger (Fig. 68)
Fig. 68
1. Drain the primary circuit.
2. While supporting the heat exchanger undo the
screws securing it to the brass manifolds.
3. Withdraw the heat exchanger upwards and to the
left of the gas valve, taking care not to damage any
wires or controls.
Rubber Seal
Seals
4. There are four rubber seals between the manifolds
and heat exchanger which may need replacement.
5. Ease the seals out of the manifold. Replace
carefully, ensuring that when the seal is inserted into
the manifold it is parallel and pushed fully in.
6. When fitting the new heat exchanger note that the
left hand location stud is offset towards the centre
more than the right hand one.
7. Reassemble in reverse order.
12.21 Diverter Valve Assembly (Fig. 69)
The diverter valve assembly comprises of a central
heating pressure differential valve and a domestic
hot water pressure differential valve. These are
connected to a manifold which is joined to the plate
heat exchanger.
Sensing Pipes
Manifold
DHW Pressure Differential Valve (Fig. 70)
1. Drain the primary circuit.
Microswitch
Bracket
2. Undo the screw securing the microswitch bracket
to the valve (Fig. 69).
Grub Screws
3. Disconnect the two sensing pipes and slacken the
grub screws securing the valve to the diverter
manifold.
DHW Pressure
Differential Valve
Fig. 69
Diaphragm
4. Draw the valve away from the diverter manifold.
The valve may now be replaced or split to examine
the diaphragm.
Diaphragm
Spring
5. To examine the diaphragm hold the valve body
securely and carefully remove the six screws. The
diaphragm spring will force apart the two halves of
the valve.
Plastic Disc
6. Remove the plastic disc and pushrod assembly.
Carefully examine the diaphragm and replace it if
there is any damage.
Pushrod
Fig. 70
7. Reassemble in reverse order.
36
Publication No. 5111811
12.0 CHANGING COMPONENTS
12.21 Diverter Valve Assembly (Cont)
Central Heating
Pressure Differential
Valve
Microswitch &
Bracket
CH Pressure Differential Valve (Fig. 71)
1. Remove the DHW pressure differential valve as
described above.
Sensing Pipe
2. From the brass diverter manifold undo the nut on
the heating flow pipe. Remove the screw securing the
diverter manifold to the appliance lower bracket.
By-pass
Pipe
Diaphragm
3. Disconnect the pressure gauge capillary from the
diverter manifold and remove the two wires from the
microswitch.
Spring Clip
Heating
Flow Pipe
4. Prise off the spring clip securing the by-pass pipe
to the diverter manifold and disconnect the sensing
pipe.
Fig. 71
5. Ease the diverter manifold out of the plate heat
exchanger manifold. Remove the assembly from the
appliance.
Diverter Manifold
Pressure Gauge
Capillary
6. Undo the screw securing the microswitch bracket
to the valve body. The sensor may now be
dismantled to examine the diaphragm.
7. To examine the diaphragm hold the assembly
securely and carefully remove the four screws. The
diaphragm spring will force the two halves of the
valve apart.
8. Carefully examine the diaphragm and replace it if
there is any damage.
9. Reassemble in reverse order.
CH Pressure Microswitch (Fig. 71)
1. Remove the two wires from the pressure
microswitch.
2. Undo the screw securing the microswitch bracket
to the valve body.
3. Reassemble in reverse order.
12.22 Flow Regulator (Figs. 71 & 72)
1. Undo the filter cartridge from the inlet/return
manifold.
Cartridge
Body
2. Unscrew the venturi and remove the flow regulator.
Filter Gauze
3. Check the cleanliness of the filter gauze, rinsing
thoroughly in clean water as necessary. Fit the new
flow regulator and reassemble in reverse order.
Fig. 85
Inlet / Return Manifold
Flow
Regulator
Fig. 72
Venturi
Publication No. 5111811
37
12.0 CHANGING COMPONENTS
Secondary
Heat Exchanger
12.23 Secondary Heat Exchanger (Fig. 73)
1. Drain the primary circuit
Pipe Connecting Clip
2. Undo the four screws securing the right hand
case panel. Remove the panel.
Fan Spigot Outlet
3. Prise the connecting clips from the heat
exchanger return pipe and the boiler return pipe.
Remove the pipes.
Pipe Clamp
Outer Drum
4. Slacken the screws on the fan spigot outlet
pipe clamp. Ease the clamp to the left. Undo the
screw at the left hand end of the pipe.
Boiler Return Pipe
Heat Exchanger
Return Pipe
5. Remove the nut securing the elbow to the
secondary heat exchanger. Draw the elbow and
outlet pipe forwards.
Elbow
Fan Spigot
Outlet Pipe
Fig. 73
6. Remove the secondary heat exchanger from
the outer drum by easing it forward.
7. Reassemble in reverse order of dismantling.
12.24 Flue Overheat Thermostat (Fig. 74)
NOTE: The flue overheat thermostat includes
a reset button. Check that the thermostat will
not reset before replacing.
1. Remove the fan spigot outlet pipe from the fan
and elbow.
2. Pull the two wires off the terminals on the flue
overheat thermostat. Unscrew the thermostat
from the adaptor in the outlet elbow.
3. Reassemble in reverse order of dismantling.
Ease Fan Spigot Outlet
Pipe Clamp Inwards
Fan Spigot Outlet Pipe
Fig. 74
Overheat Thermostat
38
Publication No. 5111811
13.0 ELECTRICAL
13.1
Illustrated Wiring Diagram
Pump
Mains Input
Link
g/y
On/Off/Reset
Selector Switch
b
br
Fuse
Temperature Sensor
bk
g/y
bk
br
b
8
b
b
b
9
Hydraulic Differential
Pressure Switch
10
br
1
bk
2
bk
11
r
3
1
4
br
12
13
14
15
16
17
br
r
2
3
4
5
6
7
br
bk
18
19
20
b
r
Flue Thermostat
r
M3
b
r
Optional Timers
Gas Valve
M1
35
b
bk
Control PCB
36
37
38
39
M2
M7
bk
br
b
44
43
42
M4
bk
bk
Safety Thermostat
32
31
30
29
28
b
b
Air Pressure
Switch
3-Way Valve
Microswitch
br
br
27
g/y
M5
FA2
Fan
g/y
Flame
Sensing
Electrode
Condensate
Trap
br - brown
bk - black
b
r
- blue
- red
y
- yellow
g/y - green / yellow
- white
gr - grey
w
Publication No. 5111811
39
14.0 SHORT PARTS LIST
140
Short Parts List
Key G.C. Description
No. No.
Manufacturers
Part No.
5112627
5112999
5112431
5112770
248210
44
22
Fan
22
23
Pressure Switch
Heat Exchanger
Burner
32
41
131
135
A
44
E66 402 Injector - 1.18 NG
E66 408 Electrode Lead
63
59
248037
63
E66 411 Spark or Sensing Electrode 247384
72
Pump Complete
248042
101
102
103
131
135
140
154
169
371
A
E66 432 Hydraulic Outlet Assembly 248061
E66 434 Valve - 3-Way Assembly
343 619 Pressure Differential Assy
Temperature Sensor
248062
248063
5108265
248078
5107339
5112657
248090
5112385
5112395
154
23
E66 697 Safety Limit Thermostat
Gas Valve
PCB
41
E66 453 Pressure Gauge
Igniter/Gas Valve Cable
Flue Overheat Thermostat
72
101
59
102
103
169
371
32
40
Publication No. 5111811
15.0 FAULT FINDING
Carry out initial fault finding checks
1. Check that gas, water and electrical supplies are available at the boiler. Electrical supply = 230V ~ 50 Hz.
CH water system pressurised to 0.5 bar when the boiler is cold. The preferred minimum gas pressure is 19.5mbar (natural gas),
or 36mbar (propane).
2. Carry out electrical system checks, i.e. Ground Continuity, Resistance to Ground, Short Circuit and Polarity with a suitable meter.
NOTE: These checks must be repeated after any servicing or fault finding.
3. Ensure all external controls are calling for heat and check all external and internal fuses. Before any servicing or replacement of parts
ensure the gas and electrical supplies are isolated.
Refer to Section 13.1 “Illustrated Wiring Diagram” for position of numbered terminals
Central Heating - Follow operational sequence
NOTE: When instructed to turn the Selector
to the reset position turn the Selector
Switch fully anticlockwise against the spring
pressure and hold for 2 seconds to reset
the boiler.
Turn selector to
neon illuminated
NO
NO
Go to section ‘A’
YES
Go to section ‘B’
YES
Turn
thermostat
to max.
External controls and,
where fitted, integral timer
calling for heat
Ensure controls are set to
demand and verify the
contacts are closed
NO
Pump runs
YES
NO
NO
Primary flow switch
operated
Go to section ‘C’
YES
Turn the selector switch
to the ‘Reset’ position
and hold for at least 2
seconds. If regular
resetting is required, or
appliance still does not
operate, investigation is
necessary
Go to sections ‘J’, ‘L’ &
‘D’
Fan runs at max speed
YES
NO
NO
Air pressure
switch proved
Go to section ‘E’
YES
Spark at ignition
electrodes for up to 10
seconds
YES
Turn selector to the reset
position. If the light does
not extinguish go to
sections H & K
illuminated
NO
YES
Replace PCB
NO
Burner on
neon
Go to section ‘F’
Go to section ‘I’
illuminated
YES
YES
Burner extinguishes
after 10 seconds
NO
Burner output
modulates until set
temperature is reached
NO
Go to section ‘G’
Fan stops
YES
YES
YES
YES
Operation sequence
Burner goes out
Pump stops
correct
Publication No. 5111811
41
15.0 FAULT FINDING
Domestic Hot Water - Follow operational sequence
Turn selector to
neon illuminated
NO
Replace diaphragm
Go to section ‘A’
YES
YES
Is mains water
filter and differential
assembly clean?
YES
DHW flow valve
diaphragm damaged
NO
YES
Turn
thermostat to
max. Open DHW tap fully.
DHW flow switch operated
NO
DHW flow rate more than
2.5l/min.
DHW flow valve rod
obstructed
YES
NO
Replace DHW flow
microswitch
Continuity across DHW
flow microswitch
terminals and PCB - M1
connector terminals 13 &
14 (terminals 12-14 open)
Primary water is diverted
from CH system to DHW NO
heat exchanger and flow
microswitch operated
YES
Replace PCB
YES
NO
Pump runs
Go to section ‘B’
YES
NO
NO
Primary flow switch
operated
Go to section ‘C’
YES
Turn the selector switch
to the ‘Reset’ position
and hold for at least 2
seconds. If regular
Go to section ‘J’, ‘L’ & ‘D’
Fan runs at max speed
YES
resetting is required, or
appliance still does not
operate investigation is
necessary
NO
NO
Air pressure switch
proved
Go to section ‘E’
YES
Turn the selector to the
reset position. If the light
does not extinguish go to
section H & K
Spark at ignition
electrodes for up to 10
seconds
YES
neon illuminated
NO
YES
Replace PCB
NO
Burner on
neon
Go to section ‘F’
illuminated
YES
YES
Burner extinguishes
after 10 seconds
Go to section ‘I’
NO
Reduce the DHW flow
rate. If burner does not
modulate clean
temperature sensor and
DHW heat exchanger. If
modulation does not
occur go to section ‘G’
NO
Burner output modulates
to maintain temperature
set at thermostat
YES
Close DHW tap
YES
DHW flow valve
senses no flow.
Primary water diverted to
CH system. DHW flow
switch released off
NO
NO
Diverter valve spindle
assembly faulty
YES
YES
YES
Operation sequence
Burner goes out
Fan stops
Pump stops
correct
42
Publication No. 5111811
15.0 FAULT FINDING
Fault Finding Solutions Sections A to E
Is there 230V at:
A
NO
1.
2.
3.
Main terminals L and N
Check electrical supply
Replace fuse
YES
Main terminal fuse
NO
neon
illuminated
Replace PCB
NO
Selector terminals a & b
and a & 3. PCB - M1
Check wiring
Replace selector
connector terminals 9 & 10
Is there 230V at:
B
C
D
NO
NO
1.
2.
Pump
If pump jammed, release
Replace pump
Replace PCB
PCB - M1 connector terminals 8 & 15
YES
Change pump supply cable
NO
1.
2.
CH system pressure 0.5 to 1.5 bar
Re-pressurise system
NO
Check the tap of the
automatic air vent is opened
Open the automatic air vent
YES
3.
Primary flow valve diaphragm damaged
NO
Replace diaphragm
Flow valve rod obstructed
1.
2.
3.
Continuity across flow
NO
Replace microswitch
Replace sensor
microswitch and PCB M2
connector terminals 3 & 4
Primary temperature sensor faulty.
Cold resistance approx. 11K ohms
(resistance reduces with increase in temp.)
YES
Fan connections correct at fan.
YES
YES
PCB - M5 connector, is 230V
across terminals 28 & 29
Fan jammed or faulty winding
Replace PCB
Replace fan
NO
Publication No. 5111811
43
15.0 FAULT FINDING
E
F
Check and correct if necessary
1. Electrical and pressure tube connections
2. Blockage of pressure tubes
3. Restriction in flue
NO
Replace air
pressure switch
4. Venturi
NO
Gas at burner
Ensure gas is on and purged
YES
PCB - M4 connector is approx 230V AC,
terminals 36 & 38
Replace gas valve
NO
YES
Turn selector switch
to ‘Reset’ position
neon illuminated
NO
Replace PCB
G
H
1.
2.
Check the burner setting pressure of
the gas valve
(see Section 9.2 of Commissioning)
Voltage at modulating coil of gas valve is:
Max. burner press.approx 9V DC (13V DC LPG)
Min. burner press.approx 1V DC
YES
NO
Replace gas valve
Replace PCB
Current at modulating coil of gas valve is:
(Use an instrument with average function for this
measure)
30 ÷ 230 mA DC (45 ÷ 310 mA DC LPG)
NO
Check and correct if necessary
1. Ignition electrode and lead
2. Electrode connection
Replace PCB
230V at Main PCB - M4
connector across terminals
37 & 38. Check wiring
YES
YES
Replace gas valve
electrical
3. Spark gap and position
plug/igniter assy
44
Publication No. 5111811
15.0 FAULT FINDING
Ensure that mains input
terminal L is Live (230V) and N
is Neutral (0V)
I
YES
Check and correct if necessary
1. Flame sensing electrode and lead connections
2. Electrode position
YES
NO
Replace PCB
Flame current should be 1 µA approx.
Replace flame sensing electrode
Boiler overheat thermostat
NO
Allow to cool. Continuity
across thermostat terminals
more than 1.5 ohm
J
YES
Replace boiler
overheat thermostat
operated or faulty, i.e. continuity
across thermostat terminals
YES
Replace
PCB
NO
Check terminal 1 of ON/OFF/RESET selector is in
connection with PCB - M1 connector terminal 16
Check electrical continuity across terminals 1 & a of
ON/OFF/RESET selector when turned to ‘Reset’ position
Replace ON/OFF/RESET selector
Replace PCB
K
L
YES
Press the reset button on the flue overheat thermostat. If
the boiler does not relight or repeatedly cuts out check
the operation of the flue system or replace the flue
overheat thermostat. If the flue overheat thermostat has
not been activated see section ‘D’
Publication No. 5111811
45
5 1 1 1 8 1 1
BENCHMARK No.
GAS BOILER COMMISSIONING CHECKLIST
C O L L E C T I V E M A R K
BOILER SERIAL No.
NOTIFICATION No.
CONTROLS To comply with the Building Regulations, each section must have a tick in one or other of the boxes
TIME & TEMPERATURE CONTROL TO HEATING ROOM T/STAT & PROGRAMMER/TIMER
TIME & TEMPERATURE CONTROL TO HOT WATER CYLINDER T/STAT & PROGRAMMER/TIMER
PROGRAMMABLE ROOMSTAT
COMBI BOILER
HEATING ZONE VALVES
FITTED
FITTED
FITTED
FITTED
NOT REQUIRED
HOT WATER ZONE VALVES
NOT REQUIRED
THERMOSTATIC RADIATOR VALVES
AUTOMATIC BYPASS TO SYSTEM
NOT REQUIRED
FOR ALL BOILERS CONFIRM THE FOLLOWING
THE SYSTEM HAS BEEN FLUSHED IN ACCORDANCE WITH THE BOILER MANUFACTURER’S INSTRUCTIONS?
THE SYSTEM CLEANER USED
THE INHIBITOR USED
FOR THE CENTRAL HEATING MODE, MEASURE & RECORD
GAS RATE
ft3/hr
mbar
°C
m3/hr
N/A
BURNER OPERATING PRESSURE (IF APPLICABLE)
CENTRAL HEATING FLOW TEMPERATURE
CENTRAL HEATING RETURN TEMPERATURE
°C
FOR COMBINATION BOILERS ONLY
HAS A WATER SCALE REDUCER BEEN FITTED?
YES
NO
WHAT TYPE OF SCALE REDUCER HAS BEEN FITTED?
FOR THE DOMESTIC HOT WATER MODE, MEASURE & RECORD
GAS RATE
ft3/hr
mbar
°C
m3/hr
N/A
MAXIMUM BURNER OPERATING PRESSURE (IF APPLICABLE)
COLD WATER INLET TEMPERATURE
HOT WATER OUTLET TEMPERATURE
WATER FLOW RATE
°C
lts/min
FOR CONDENSING BOILERS ONLY CONFIRM THE FOLLOWING
THE CONDENSATE DRAIN HAS BEEN INSTALLED IN ACCORDANCE WITH
THE MANUFACTURER’S INSTRUCTIONS?
YES
FOR ALL INSTALLATIONS CONFIRM THE FOLLOWING
THE HEATING AND HOT WATER SYSTEM COMPLIES
WITH CURRENT BUILDING REGULATIONS
THE APPLIANCE AND ASSOCIATED EQUIPMENT HAS BEEN INSTALLED AND COMMISSIONED
IN ACCORDANCE WITH THE MANUFACTURER’S INSTRUCTIONS
IF REQUIRED BY THE MANUFACTURER, HAVE YOU RECORDED A CO/CO2 RATIO READING? N/A
YES
CO/CO2 RATIO
THE OPERATION OF THE APPLIANCE AND SYSTEM
CONTROLS HAVE BEEN DEMONSTRATED TO THE CUSTOMER
THE MANUFACTURER’S LITERATURE HAS BEEN LEFT WITH THE CUSTOMER
COMMISSIONING ENG’S NAME PRINT
CORGI ID No.
DATE
SIGN
46
SERVICE INTERVAL RECORD
It is recommended that your heating system is serviced regularly
and that you complete the appropriate Service Interval Record Below.
Service Provider. Before completing the appropriate Service Interval Record below, please ensure you have carried out the service
as described in the boiler manufacturer’s instructions. Always use the manufacturer’s specified spare part when replacing all controls
SERVICE 1 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 2 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 3 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 4 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 5 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 6 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 7 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 8 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
SERVICE 9 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
SERVICE 10 DATE
ENGINEER NAME
COMPANY NAME
TEL No.
CORGI ID CARD SERIAL No.
COMMENTS
CORGI ID CARD SERIAL No.
COMMENTS
SIGNATURE
SIGNATURE
47
Publication No. 5111811 - Iss. 4 (04/2006)
General Enquiries (GB)
Tel.
Tel.
08706 060 780
Technical (GB)
08706 049 049
Service (GB)
Tel.
08706 096 096
Fax.
01926 410 006
Literature Request (GB)
Tel.
Tel.
08706 060 623
Technical (IE)
1850 560570
All descriptions and illustrations provided in this leaflet have been
carefully prepared but we reserve the right to make changes and
improvements in our products which may affect the accuracy of
the information contained in this leaflet. All goods are sold subject
to our standard Conditions of Sale which are available on request.
BAXI Heating UK
Brownedge Road Bamber Bridge Preston Lancashire PR5 6UP
After Sales Service 08706 096 096 Technical Enquiries 08706 049 049
|