Trane Pkg Prc002 En User Manual

Commercial Self-Contained  
IntelliPak® Signature Series  
20-80 Ton Water-Cooled Air Conditioners  
20-60 Ton Air-Cooled Air Conditioners  
Remote Air-Cooled Condensers  
December 2001  
PKG-PRC002-EN  
Contents  
Introduction  
2
4
8
Features and Benefits  
Application Considerations  
Selection Procedure  
Model Number Description  
General Data  
12  
14  
17  
Performance Data  
22  
Airside Pressure Drops  
Waterside Pressure Drops  
Water-Cooled Units  
Air-Cooled Units  
22  
29  
31  
60  
68  
Heating Coils  
Controls  
69  
79  
81  
Electrical Data  
Dimensions and Weights  
Mechanical Specifications  
95  
97  
Options  
PKG-PRC002-EN  
3
Features and  
Benefits  
Lower Installed Cost  
• Multiple compressor design reduces  
acoustical levels. Scroll compressor  
design smooths gas flow for quieter  
operation  
Why consider the  
Signature Series  
self-contained floor-by-floor  
systems?  
• Single point power connection  
• Single point water connection  
• Factory commissioned and tested  
controls  
• Factory installed options  
• Internally trapped drain connection  
Indoor Air Quality (IAQ) Features  
• Sloped drain pan  
Improved Cash Management  
• Factory-installed and tested options  
reduce field labor and installation risk,  
while improving system reliability  
• Requires less sophisticated  
• Stainless steel sloped drain pan option  
• Internally trapped drain connection  
• Double wall construction option  
• Matt-faced fiberglass insulation  
• High efficiency throwaway filter option  
• Easily cleanable evaporator,  
condensers, and waterside  
Economical Operation  
• Free cooling with waterside or airside  
economizer  
maintenance than built-up systems  
• Energy savings with floor-by-floor  
system since only units on floors  
requiring cooling need to operate  
• Significant annual energy consumption  
reduction due to partial occupancy  
after-hours, when compared to a  
central chilled water system  
• Simple heating alternatives include  
perimeter radiation and fan-powered  
VAV  
Tenant Satisfaction  
economizers  
• Complete HVAC system on each floor  
minimizes tenant inconvenience during  
routine maintenance  
• Filter access door allows easy removal  
to encourage frequent filter changing  
• Airside economizer withTraq™ damper  
allows direct measurement and control  
of outdoor air  
Tenants can control system after hours  
to increase productivity and minimize  
expense  
• Energy savings from the integrated  
water valve control using pump  
unloading  
Enhanced Serviceability  
Low First Cost  
• Self-supporting removable panels  
• Quick access service panel fasteners  
• Eye level control/service center  
• Refrigerant line sight glasses in view  
during operation  
• Reduce field labor, installation time, and  
cost with factory packaged controls and  
piping  
Assured Acoustical Performance  
• Flexible, horizontal discharge plenum  
provides smooth airflow, reducing static  
pressure losses for optimum acoustical  
performance  
• Reduce installed tonnage up to 20  
percent by taking advantage of building  
diversity andVAV flexibility  
• Flexible air discharge arrangement  
matches most building configurations  
4
PKG-PRC002-EN  
Features and  
Benefits  
Standard Features  
• Condensing pressure control on all  
FC FansWith Inlet GuideVanes  
• 20 through 80 ton industrial/commercial  
water-cooled self-contained units  
• 20 through 60 ton industrial/commercial  
remote air-cooled self-contained units  
• Fully integrated, factory-installed, and  
commissioned microelectronic controls  
• Unit mounted human interface panel  
with a two line x 40 character clear  
language (English, Spanish, or French)  
display and a 16-function keypad that  
includes custom, diagnostics, and  
service test mode menu keys  
• ImprovedTrane 3-D® scroll compressor  
• Compressor lead/lag  
variable water flow systems with valves Trane’s forward-curved fans with inlet  
• Programmable water purge during  
unoccupied mode  
• High entering air temperature limit  
• Low entering air temperature limit with  
waterside economizer or hydronic heat  
guide vanes pre-rotate the air in the  
direction of the fan wheel. This decreases  
static pressure and horsepower.The  
unloading characteristics of aTrane FC  
fan with inlet guide vanes results in  
superior part load performance.  
Optional Features  
Trane communication interface module:  
ICS interface control module  
• Generic BAS interface  
Variable Frequency Drives (VFD)  
Variable frequency drives are factory  
installed, wired, and tested to provide  
supply fan motor speed modulation.  
VFDs are quieter and more efficient than  
inlet quide vanes and may even be  
eligible for utility rebates.TheVFDs are  
available with and without a manual  
integrated bypass option, controlled  
through the human interface (HI) panel.  
Bypass control provides full nominal  
airflow control to CV zone setpoints in the  
unlikely event of a drive failure by  
manually placing the drive in the bypass  
mode.  
• Comparative enthalpy control  
Ventilation override from up to five  
external inputs  
• Remote human interface controls up to  
four units  
• Fully integrated, factory-installed/  
commissioned variable frequency drive  
control with or without optional  
integrated bypass  
• Fully integrated, factory-installed and  
commissioned inlet guide vanes on FC  
supply fan  
• Waterside economizer with factory  
installed piping and controls  
• Waterside modulating condensing  
temperature control valves include  
factory installed piping and control  
wiring  
• Removable cast iron headers on  
cleanable waterside economizer  
• Flexible horizontal discharge plenum  
with or without factory cut holes  
• Heating options include hot water,  
steam, and electric  
• CV orVAV system control  
• Low ambient compressor lockout  
adjustable control input  
• FROSTATcoil frost protection on all  
units  
• Daytime warmup (occupied mode) on  
units with heat and morning warmup  
operation on all units  
• Supply air static overpressurization  
protection on units with inlet guide  
vanes or variable frequency drives  
(VFDs)  
• Supply airflow proving  
• Supply air tempering control with  
heating option  
• Supply air heating control onVAV with  
hydronic heating option  
• Emergency stop input  
• Mappable sensors and setpoint sources  
• Occupied/unoccupied switching  
• Timed override activation  
• Refrigeration circuits are completely  
factory piped and tested on water-  
cooled units  
• Factory piped and tested, mechanically  
cleanable water-cooled condensers  
Two-bolt removable condenser  
waterboxes for quick and easy cleaning  
• Sloped drain pans to ensure complete  
condensate removal for IAQ  
Field Installed Accessories  
• Airside economizer control with or  
without mixing box  
• Programmable sensors with or without  
night set back for CV andVAV systems  
• ICS zone sensors used withTracer®  
system for zone control  
• Field installed module kits available for  
field upgrade of controls  
• Ultra low leak dampers for 0-100  
percent modulating fresh air  
economizer  
• Refrigerant suction discharge line  
service (shut-off) valves  
• Protective coatings for the unit and/or  
evaporator coils  
• Double wall construction  
• Stainless steel sloped drain pan  
• Medium efficiency throwaway filters  
• Through-the-door non-fused disconnect  
switch  
Trane’s air qualityTraqdamper in  
airside economizer mixing box  
• High duct temperature thermostat  
• Dual electrical power connection  
• CO2 reset input  
• Internally trapped drain connection with  
cleanout  
• Internally isolated centrifugal supply fan  
• 14-gauge galvanized steel framework  
with easily removable painted exterior  
panels of 18-gauge galvanized steel  
• UL listing on standard options  
• Fan belts and grease lines are easily  
accessible  
• Access panels and clearance provided  
to clean both evaporator and waterside  
economizer coil fins  
PKG-PRC002-EN  
5
Features and  
Benefits  
Integrated Self-Contained  
Systems  
Integrated ComfortSystem (ICS)  
Tranes Integrated Comfortsystem  
(ICS) increases job control by combining  
IntelliPak® Signature Series self-  
contained units and aTracer® building  
management system. This integrated  
system provides total building comfort  
and control. Building owners and  
managers not only save energy when  
using ICS—they have the ability to  
automate their facilities and the  
convenience of a control system  
interface.  
Simplifying The Comfort System  
Trane’s designers combined new  
technology and innovation to bring you  
more system capabilities and flexibility.  
Our Integrated Comfortsystem (ICS)  
with HVAC equipment is easy to use,  
install, commission, and service.  
IntelliPak® Signature Series self-  
contained monitoring points available  
using Tracer®  
• Compressor on/off status  
Ventilation status  
• Condenser water flow status  
• Heat status  
• Supply air pressure  
Everything you need to know about your  
self-containedVAV system is available  
usingTracer®,Tranes family of building  
automation products.Tracer® is a  
software package that minimizes custom  
programming requirements and allows  
easy system setup and control using  
your personal computer. Operating data  
from all system components is readily  
available for evaluation.You can control,  
monitor, and service your facility—all  
from your personal computer.  
The IntelliPak® self-contained unit, as  
part ofTrane ICS, provides powerful  
maintenance monitoring, control, and  
reporting capabilities.Tracer® places the  
self-contained unit in the appropriate  
operating mode for: system on/off, night  
setback, demand limiting, setpoint  
adjustment based on outside  
parameters and much more.You can  
monitor unit diagnostic conditions  
throughTracer such as: sensor failures,  
loss of supply airflow, and an inoperative  
refrigerant circuit.  
• Supply air temperature  
• Suction temperature of each circuit  
• Entering economizer water  
temperature  
• Zone temperature  
• Entering condenser water temperature  
• Supply air temperature reset signal  
• Morning warmup sensor temperature  
• Entering air temperature  
Tracer control points for IntelliPak®  
Signature Series Self-Contained Units  
• Cooling and heating setpoints  
VAV discharge air temperature  
setpoints  
• Supply air pressure setpoint  
• Cooling and heating enable/disable  
• Air economizer enable/disable  
• Airside economizer minimum position  
• Unit priority shutdown  
Commissioning, control, efficiency, and  
information…it simply all adds up to one  
reliable source…Trane.  
6
PKG-PRC002-EN  
Features and  
Benefits  
Trane 3-D® Scroll Compressor  
Simple Design with 70% Fewer Parts  
Fewer parts than an equal capacity  
reciprocating compressor means  
significant reliability and efficiency  
benefits. The single orbiting scroll  
eliminates the need for pistons,  
connecting rods, wrist pins, and valves.  
Fewer parts lead to increased reliability.  
Fewer moving parts, less rotating mass,  
and less internal friction means greater  
efficiency than reciprocating compressors.  
Patented 3-D Scroll Compliance  
Trane 3-D scroll compliance provides  
important reliability and efficiency  
benefits. 3-D compliance allows the  
orbiting scrolls to touch in all three  
dimensions, forming a completely  
enclosed compression chamber that leads  
to increased efficiency. In addition, 3-D  
compliance means the orbiting scrolls only  
touch with enough force to create a seal—  
so there is no wear between the scroll  
plates. The fixed and orbiting scrolls are  
made of high strength cast iron—resulting  
in less thermal distortion, less leakage,  
and higher efficiencies. The most  
outstanding feature of the scroll  
compressor 3-D compliance is that  
slugging will not cause failure. In a  
reciprocating compressor, however, liquid  
or dirt can cause serious damage.  
Low Torque Variation  
The 3-D scroll compressor has a very  
smooth compression cycle with torque  
variations that are only 30 percent of that  
produced by a reciprocating compressor.  
This means the scroll compressor  
imposes very little stress on the motor for  
greater reliability. Low torque variation  
means reduced noise and vibration.  
Suction Gas Cooled Motor  
Compressor motor efficiency and  
reliability are further optimized with this  
design. Cool suction gas keeps the motor  
cooler for longer life and better efficiency.  
Proven DesignThroughTesting and  
Research  
With over twenty years of development  
and testing,Trane 3-D scroll compressors  
have undergone more than 400,000 hours  
of laboratory testing and field operation.  
This work combined with over 25 patents  
makesTrane the worldwide leader in air  
conditioning scroll compressor technology.  
One of two matched scroll plates — the  
distinguishing feature of the scroll  
compressor.  
The Chart above illustrates low torque  
variation of 3-D Scroll compressors as  
compared to a reciprocating compressor.  
PKG-PRC002-EN  
7
Application  
Considerations  
Self-Contained  
transmit sound. In addition, small aspect  
ratios will minimize potentialoil canning”  
of the duct due to flow turbulence.  
Return Air Ductwork  
Self-Contained Acoustical  
Duct the return air into the mechanical  
equipment room. Connect ductwork to  
the unit if local code dictates. The return  
air ductwork must have an elbow inside  
the equipment room. This elbow will  
reduce sound transmissions through the  
return duct. Extend the ductwork from  
the elbow far enough to block the “line of  
sight” to the exterior of the equipment  
room. Use a minimum ductwork length  
of 15 feet to the equipment room  
exterior. Line the duct with two-inch,  
three-pound density insulation. Use  
multiple, small return ducts for better  
acoustical performance to the occupied  
space.  
Recommendations  
Successful acoustical results are  
dependent on many system design  
factors.  
The flexible horizontal discharge plenum  
option helps avoid complicated ductwork  
transitions. Ductwork turning vanes  
typically improve pressure drop but  
degrade acoustical performance.  
Following are general acoustical  
recommendations. For more information,  
or if there is concern about a particular  
installation, contact a professional  
acoustical consultant.  
Recommended Maximum AirVelocities  
The maximum recommended velocity  
for the discharge air duct is 2,000 fpm.  
The maximum recommended velocity  
for the return air duct is 1,000 fpm. Limit  
air velocities below these operating  
points to minimize the risk of flow  
turbulence that causes regenerated  
noise. Using round supply duct and static  
regain allows maximum discharge air  
velocities up to 3,000 fpm. Lining round  
supply duct also substantially lowers  
frequency noise attenuation. However,  
flow regenerated noise potential  
Location and Orientation of the  
Mechanical Equipment Room  
Locate the equipment room adjacent to  
stairwells, utility rooms, electrical closets,  
and rest rooms if possible (See figure  
below). This minimizes the acoustic  
effects and risk of workmanship or  
installation errors. Place the discharge  
and return air ductwork over these less  
acoustically sensitive areas, using vertical  
or horizontal fresh air shafts. Consult code  
requirements for fresh air and smoke  
purge constraints.  
Supply Air Ductwork  
Insulate the supply air duct with two-inch,  
three-pound density insulation. Extend  
this lining at least 15 feet out from the  
equipment room wall, keeping the duct  
aspect ratio as small as possible.  
Minimize large flat panels since they  
increases dramatically at air velocities  
over 3000 fpm.  
Equipment Room Location and Orientation  
8
PKG-PRC002-EN  
Application  
Considerations Self-Contained  
Equipment Room Construction Options  
The preferred equipment room wall  
construction is concrete block. If this is not  
feasible then a double stud offset wall is  
suggested (See figure). This removes  
physical contact that would transmit  
sound through the equipment room wall  
to the occupied space. Interweave  
fiberglass insulation between the wall  
studs. Use two layers of sheetrock on  
each side of the wall.  
Workmanship details are critical to  
acoustical performance. Seal all wall and  
floor penetrations by the ductwork, water  
piping, and equipment room access  
doors with a flexible material such as  
caulk and/or gasketing to stop noise and  
air leaks.  
Double Stud Offset Wall with Interwoven Insulation  
Locate the equipment room door away  
from acoustically sensitive areas like  
conference rooms. The door should  
swing out of the equipment room, if  
possible, so that the low pressure in the  
equipment room pulls the door in to help  
maintain a tight seal.  
Piping Connections  
Free Cooling Opportunities  
Rubber isolator connectors are  
and Alternatives  
recommended for condenser piping to  
Free cooling is available with either the  
prevent vibration transmission to or from  
airside or waterside economizer options.  
the building plumbing. The Signature  
Waterside Economizer  
The waterside economizer substantially  
reduces the compressor energy  
requirements because it uses the cooling  
water before it enters the condensers.  
Additional equipment room space is not  
required since the coils are contained  
within the overall unit dimensions.  
Series self-contained unit is internally  
isolated and does not require additional  
isolation. However, ensure proper  
system vibration isolation design  
Equipment Options  
The flexible horizontal discharge plenum  
allows multiple tested outlet options. This  
minimizes the risk of acoustic and/or  
pressure drop problems by avoiding  
complex transitions close to the fan  
discharge.  
prevents vibration transmission from the  
building plumbing to the unit. Also be sure  
to properly isolate the drain line.  
Disadvantages include higher airside  
pressure drop and a higher head on  
condenser water pumps.  
Static Pressure Versus Acoustics  
Design the system to minimize the total  
static pressure required from the self-  
contained unit fan.Typically a change in  
static pressure of only 0.5 inches can  
reduce NC level by approximately 2 or 3  
in the occupied space.  
Condenser Water Piping  
Piping Location and Arrangement  
Provide at least 24 inches of clearance  
between the piping and the unit for  
service. Place the risers away from the  
side of the unit if possible. Be sure to  
allow sufficient space for valves and  
unions between the piping and the self-  
contained unit. Lay out condenser piping  
in reverse returns to help balance the  
system. This is accomplished by  
equalizing the supply and return pipe  
length. Multi-story buildings may use a  
direct return system with balancing  
valves at each floor. Install all heat  
exchangers and most cooling tower  
piping below the sump operating water  
level to prevent overflow during unit and/  
or system shut down.  
The coils may be mechanically cleanable  
(optional) for ease in maintenance versus  
expensive and difficult chemical cleaning  
methods.  
Airside Economizer  
The airside economizer substantially  
reduces compressor, cooling tower, and  
condenser water pump energy  
requirements using outside air for free  
cooling. It also reduces tower make up  
water needs and related water  
treatment.  
Isolation Recommendations  
Unit  
The Signature Series unit fan and  
compressors are internally isolated.  
Therefore, external isolation is not  
required. Consult a vibration specialist  
before considering external or double  
vibration isolation.  
Disadvantages include building  
requirements that locate the mechanical  
room and self-contained unit toward an  
exterior wall to minimize ductwork ,  
building barometric control, or additional  
air shafts. Also, airside economizers  
require additional mechanical room  
space.  
Ductwork  
Design duct connections to the unit using  
a flexible material. Consult local codes for  
approved flexible duct material to  
prevent fire hazard potential.  
PKG-PRC002-EN  
9
Application  
Considerations Self-Contained  
Recommended Pump Location  
utilize this feature, the building water  
system must be capable of operating at  
reduced water flow rates through the  
self-contained units. It is imperative to  
install variable volume pumps or an  
external bypass in the water distribution  
system.  
strainer while allowing other units in the  
system to remain in operation.  
Locate pump downstream of the cooling  
tower and upstream of the self-contained  
unit. This provides smoother and more  
stable unit operation.  
Pressure Gauges  
Install pressure gauges on the inlet and  
outlet of the self-contained unit. Select  
the gauge’s scale so that the unit design  
operating point is approximately mid-  
scale.  
When the tower and pump are both roof  
mounted, be sure to provide the  
necessary net positive suction head  
pressure to prevent cavitation. Raise the  
tower or submerge the pump in a sump  
to provide positive suction.To prevent an  
on-line pump failure, use a standby pump  
to avoid a complete system shutdown.  
Several partial capacity pumps or  
variable speed pumps may be used.  
Review the economics of these alternate  
pumping options.  
Waterside Economizer Flow Control  
Units equipped with waterside  
economizer control valves can be set up  
for variable or constant water flow.  
Thermometers  
Install thermometers on the condenser  
water inlet and outlet lines to each unit for  
system analysis.Trane Company  
recommends using a thermometer  
temperature range of 40 to 140 F, using  
a 2 F temperature increment.  
Use constant water flow setup on water  
systems that are not capable of  
unloading water supply to the unit. The  
economizer and condenser valves will  
operate in complement to one another to  
provide continuous water flow.  
Drains  
The unit condensate drain is internally  
trapped to offset the pressure differential  
that exists during fan operation. Install a  
trapped drain in the low point of the  
mechanical equipment room floor to  
collect water from cleaning operations.  
Strainers and Water Treatment  
Water strainers are required at the unit  
inlet to eliminate potential unit damage  
from dirty water. Specify a water basket-  
type strainer to avoid an incorrect  
stream strainer application. Untreated or  
poorly treated water may result in  
equipment damage. Consult a water  
treatment specialist for treatment  
recommendations.  
Use variable water flow setup with water  
flow systems that can take advantage of  
pump unloading for energy savings.  
Since non-cooling operation restricts  
water flow during part load economizing  
or condensing temperature control, it is  
imperative to install variable volume  
pumps or an external bypass in the water  
distribution system.  
Condensing Pressure Control  
(Water-Cooled condensers)  
Often cold condensing water applications  
between 35 F (1.7 C) and 54 F (12.2 C)  
require a condensing pressure control  
valve. Any unit with variable-flow  
waterside valves can modulate water  
flow to maintain a user defined  
Unit Operating Limits  
Airflow  
Isolation Valves  
Install isolation valves at each unit before  
the strainer and after the condenser.This  
allows periodic servicing of the unit or  
The minimum recommended airflow for  
properVAV system staging and  
temperature control is 35 percent of  
nominal design airflow. AdjustingVAV  
boxes with the appropriate minimum  
settings will prevent the self-contained  
unit from operating in a surge condition at  
airflows below this point. Continuous  
operation in a surge condition can cause  
fan failure. Reference General Data  
Tables on pages 17-20 for minimum  
airflow conditions.  
condensing temperature. However, to  
Signature Series self-contained units use  
fixed pitch sheaves. Adjust air balancing  
by obtaining alternate fixed pitch sheave  
selections from the localTrane sales  
office.  
Waterflow  
Use 3 gpm/ton for optimum unit capacity  
and efficiency. Use 2.5 or 2 gpm/ton to  
reduce pump energy, cooling tower and  
piping costs. However, these reduced  
waterflows may impact unit capacity and  
efficiency by one or two percent. Consult  
General DataTables on pages 17-20 for  
unit specific waterflow ranges.  
Waterside Economizer Piping  
10  
PKG-PRC002-EN  
Application  
Considerations  
Air Cooled  
Condenser  
Ambient Limitations  
Remote Air-Cooled Condenser  
Clearance  
Standard ambient control allows  
operation down to 45 F (7.2 C) with  
cycling of condenser fans. Units with the  
low ambient option are capable of  
starting and operating in ambient  
temperatures down to 0 F (-17.8 C).  
Optional low ambient units use a  
condenser fan damper arrangement that  
controls condenser capacity by  
Ensure vertical condenser air discharge  
is unobstructed. While it is difficult to  
predict the degree of warm air  
recirculation, a unit installed with a ceiling  
or other obstruction above it will  
experience a capacity reduction that will  
reduce the maximum ambient operation  
limit. Nuisance high head pressure  
tripouts may also occur.  
Unit Location  
Unobstructed condenser airflow is  
essential to maintaining capacity and  
operating efficiency.When determining  
unit placement, give careful  
consideration to assure sufficient airflow  
across the condenser coils. Avoid these  
two detrimental conditions: warm air  
recirculation and coil starvation.  
modulating damper airflow in response  
to saturated condenser temperature.  
The coil inlet must also be unobstructed.  
A unit installed closer than the minimum  
recommended distance to a wall or other  
vertical riser will experience a  
combination of coil starvation and warm  
air recirculation. This may result in unit  
capacity and efficiency reductions, as  
well as possible excessive head  
Both warm air recirculation and coil  
starvation cause reductions in unit  
efficiency and capacity because of the  
higher head pressure associated with  
them. In more severe cases, nuisance  
unit shutdowns will result from excessive  
head pressures.  
Maximum ambient temperature  
operation of a standard condenser is 115  
F (46.1 C). Operation at design ambient  
above 115 F can result in excessive head  
pressures. For applications above 115 F,  
contact the localTrane sales office.  
pressures. Reference the service  
clearance section on page 93 for  
recommended lateral distances.  
PKG-PRC002-EN  
11  
Selection  
Procedure  
Self-Contained  
8
Following is a sample selection for a  
standard applied water-cooled self-  
contained at particular operating  
conditions. UseTrane Official Product  
Selection System, TOPSS, for making  
all final selections or contact your local  
Trane representative.  
Refer toTrane psychometric chart to  
determine leaving air temperatures.  
Waterside Economizer Capacity  
1
After determining that the unit will meet  
the required mechanical cooling capacity,  
determine the waterside economizer  
capacity by referring to the appropriate  
two-row (low capacity) or four-row (high  
capacity) waterside economizer capacity  
tables on pages 32-58.  
Unit Capacities  
1
Determine entering air temperature dry  
bulb and wet bulb and entering water  
temperature.  
2
2
Determine entering air temperature dry  
bulb and wet bulb, condenser water flow  
(gpm), and economizer entering water  
temperature.  
Refer to the Performance Data section  
beginning on page 32 to find gross total  
and sensible capacity that best meets  
capacity requirements.  
3
3
Refer to the appropriate waterside  
economizer table to find gross total and  
sensible capacity and the leaving water  
temperature.  
Apply the cfm correction factors from the  
capacity correction factorTable  
PD-1 on page 31 to determine gross total  
and gross sensible capacities at desired  
cfm.  
4
Apply the cfm correction factor for the  
waterside economizer from the  
appropriate table to determine the gross  
total and sensible capacities at the desired  
cfm.  
4
Multiply condenser water delta T by  
the total capacity cfm correction factor to  
determine new condenser water deltaT.  
5
5
Using design cfm, determine static air  
pressure drops for accessories from the  
air pressure drop Charts PD-1 through  
PD-18. Add accessory static pressure  
drops to external supply and return static  
air pressure drops. Use the total air  
pressure drop to determine rpm and  
brake horsepower requirements from the  
appropriate fan curve. Note: The fan  
curves include refrigerant coil and internal  
cabinet static loses.  
Multiply the condenser water delta T by  
the total capacity cfm correction factor to  
determine the new deltaT.  
6
Calculate supply fan motor heat by using  
the following equation:  
Fan motor heat (MBh) = 2.8 x fan motor  
brake horsepower  
7
Determine net total and sensible capacity  
by subtracting fan motor heat from gross  
total and sensible capacity.  
6
Calculate supply fan motor heat by using  
the following equation:  
Fan motor heat (MBh) = 2.8 x fan motor  
brake horsepower  
8
Refer to theTrane psychometric chart to  
determine leaving air temperatures.  
7
Determine net total capacity and net  
sensible capacity by subtracting fan  
motor heat from gross total capacity and  
gross sensible capacity.  
12  
PKG-PRC002-EN  
Selection  
Procedure  
Self-Contained  
Selection Example  
Refer toTable PD-1 on page 31 to obtain  
the capacity correction factors for +6% of  
nominal cfm:  
Cooling capacity multiplier = 1.009  
Sensible capacity multiplier = 1.027  
Determine net capacities by subtracting  
fan motor heat from gross capacities:  
2.8 x 16 bhp = 44.8 MBh  
Net total capacity = 422.8 MBh -  
44.8 MBh = 378.0 MBh  
Net sensible capacity = 317.3 MBh -  
44.8 MBh = 272.5 MBh  
Design Conditions  
Total gross capacity required =  
420 MBh = 35.2Tons  
Total sensible capacity required =  
315 MBh  
Entering air temperature = 80/67  
Entering water temperature = 85  
Water flowrate = 105 gpm  
Airflow = 14840 cfm at 2.5-inch  
duct static pressure  
Multiply the capacities by the correction  
factors:  
419 MBh x 1.009 = 422.8 MBh  
309 MBh x 1.027 = 317.3 MBh  
The SCWF 35 meets the total and  
sensible design requirements.  
Determine waterside economizer  
capacity by referring toTable PD-17 on  
page 42. Use entering air of 80/67 and  
entering water temperature of 55 deg F  
at 105 gpm. The table provides a gross  
total capacity of 282.1 MBh and gross  
sensible capacity of 277.2 MBh and  
60.4 deg F leaving water temperature at  
nominal cfm.  
Unit includes:  
Inlet guide vanes  
Waterside economizer  
Medium velocity throwaway filters  
Multiply the deltaT of 9.7 F, by the cooling  
capacity correction factor of 1.009 to  
obtain new delta T of 9.79 and add this to  
the entering water temperature to obtain  
the actual leaving water temperature of  
94.79 F.  
Unit Selection  
Tentatively select a 35 ton unit  
Model SCWF 35.  
Refer toTable PD-19 on page 43 to obtain  
gross total and sensible unit capacities,  
and gpm at the design conditions:  
Total capacity = 419.0 MBh  
Sensible capacity = 309.0 MBh  
Leaving water temperature = 94.7 F  
Determine gross capacities at design cfm  
by applying the cfm correction factors  
from waterside economizer fromTable  
PD-1 on page 31. Use the following  
correction factors:  
282.1 MBh x 1.009 = 284.6 MBh  
277.2 MBh x 1.027 = 284.7 MBh  
Determine static air pressure drops  
through the accessories at the design cfm  
from Chart PD-3 on page 22:  
4-row waterside economizer = 0.37 in.  
Medium velocity filters = 0.28 in.  
add this to the 2.5 inch duct static  
pressure for a total external static  
pressure of 3.15 inches.  
Apply the cooling correction factor to  
water delta T to determine new delta T of  
5.45 F.  
Since the design cfm is greater than the  
nominal cfm, adjust the capacities and  
condenser water delta T to reflect the  
higher cfm:  
Refer to the fan curve with inlet guide  
vanes, Chart PD-38 on page 43, to  
determine approximate brake  
horsepower and fan rpm:  
Fan brake horsepower = 16 bhp  
Fan rpm = 1020 rpm  
Determine net capacities by subtracting  
fan motor heat for net total capacity of  
239.8 MBh and net sensible capacities of  
239.9 MBh.  
design cfm 14840 = +6% of nom. cfm  
nominal  
cfm  
14000  
PKG-PRC002-EN  
13  
Selection  
Procedure  
Model Number  
Description  
Self-Contained Model Number Description  
S C W F N 20 4 2 BO A B 2  
10  
065  
B
A 1 0 1 0 A A C F  
A
1
1 0 T 2  
0
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36  
Digit 1 - Unit Model  
Digit 10, 11 - Design Sequence  
Digit 17, 18, 19 - Fan RPM  
040 = 400 rpm  
045 = 450 rpm  
050 = 500 rpm  
055 = 550 rpm  
060 = 600 rpm  
065 = 650 rpm  
070 = 700 rpm  
075 = 750 rpm  
080 = 800 rpm  
085 = 850 rpm  
090 = 900 rpm  
095 = 950 rpm  
100 = 1000 rpm  
105 = 1050 rpm  
110 = 1100 rpm  
115 = 1150 rpm  
120 = 1200 rpm  
125 = 1250 rpm  
130 = 1300 rpm  
135 = 1350 rpm  
140 = 1400 rpm  
145 = 1450 rpm  
150 = 1500 rpm  
S = Self Contained  
BO = “B” Design  
Digit 2 - UnitType  
C = Commercial  
I = Industrial  
Digit 12 - Unit Construction  
A = Vertical Discharge  
B =Vertical Discharge with DoubleWall  
Digit 3 - Condenser Medium  
W = Water-Cooled  
R = Air-Cooled  
Digit 13 - Flexible Horizontal Discharge  
PlenumType  
B = Std Plenum w/ Factory Cut Holes  
C = Low Plenum w/ Factory Cut Holes  
E = Std Plenum w/ Field Cut Holes  
F = Low Plenum w/ Field Cut Holes  
H = Std Plenum Double wall  
w/ Field Cut Holes  
J = Low Plenum Double wall  
w/ Field Cut Holes  
K = 45” Plenum w/Factory Cut Holes,  
Ship Separate  
L = Std Plenum w/Factory Cut Holes,  
Ship Separate  
M = Low Plenum w/Factory Cut Holes,  
Ship Separate  
N = 45” Plenum w/Field ut Holes, Ship  
Separate  
P = Std Plenum w/Field Cut Holes, Ship  
Separate  
R = Low Plenum w/Field Cut Holes, Ship  
Separate  
T = 45” Double Wall Plenum w/Field Cut  
Holes, Ship Separate  
U = Std Double Wall Plenum w/Field Cut  
Holes, Ship Separate  
V = Low Double Wall Plenum w/Field  
Cut Holes, Ship Separate  
0 = None  
Digit 4 - Development Sequence  
F = Signature Series  
Digit 5 - Refrigerant Circuit Configuration  
N = Independent (Water-Cooled)  
M = Manifolded (30, 35, 40, 50, 60-Ton Air-  
Cooled Only)  
Digit 6, 7 - Unit Nominal Capacity  
20 = 20Tons (Water or Air)  
22 = 22Tons (Water Only)  
25 = 25Tons (Water or Air)  
29 = 29Tons (Water or Air)  
30 = 30Tons (Air Only)  
32 = 32Tons (Water Only)  
35 = 35Tons (Water or Air)  
38 = 38Tons (Water Only)  
40 = 40Tons (Air Only)  
42 = 42Tons (Water Only)  
46 = 46Tons (Water Only)  
50 = 50Tons (Air Only)  
52 = 52Tons (Water Only)  
58 = 58Tons (Water Only)  
60 = 60Tons (Air Only)  
Digit 20 - HeatingType  
A = Steam Coil  
B = Hot Water Coil  
C = Electric Heat (1 Stage)  
F = Hydronic Heat Ctrl Interface  
G = Elec. Heat Ctrl Interface (1 stage)  
K = Steam Coil Ship Separate  
L = Hot Water Coil Ship Separate  
0 = Without Heat  
65 = 65Tons (Water Only)  
72 = 72Tons (Water Only)  
80 = 80Tons (Water Only)  
Digit 21 - Unit Isolators  
A = Isopads  
B = Spring Isolators  
0 = None  
Digit 14 - MotorType  
1 = Std Eff. ODP Motor  
2 = Premium Eff. ODP Motor  
3 =Totally Enclosed Motor  
Digit 8 - UnitVoltage  
6 = 200Volt/60 Hz/3 ph  
4 = 460Volt/60 Hz/3 ph  
5 = 575Volt/60 Hz/3 ph  
Digit 22 - Unit Finish  
1 = Paint - Executive Beige  
2 = Protective Coating  
Digit 15, 16 - Motor HP  
05 = 5 HP Motor  
Digit 9 -AirVolume/Temp Control  
1 = IGV and Supply AirTemp Ctrl  
2 =VFD and Supply AirTemp Ctrl  
3 = VFD w/ Bypass and Supply  
AirTemp Ctrl  
4 = w/oVol. CTRL, w/ ZoneTemp Cool  
5 = w/oVol. CTRL, w/ ZoneTemp  
Heat/Cool  
3 = Protective Coating w/ Finish Coat  
07 = 7.5 HP Motor  
10 = 10 HP Motor  
Digit 23 - Future Use  
0 = None  
15 = 15 HP Motor  
20 = 20 HP Motor  
Digit 24 - Unit Connection  
1 = Disconnect Switch  
2 =Terminal Block  
25 = 25 HP Motor  
30 = 30 HP Motor  
40 = 40 HP Motor  
6 = w/oVol. CTRL and Supply Air  
Temp Ctrl  
3 = Dual Point Power (2 Blocks)  
50 = 50 HP Motor (460V & 575V Only)  
14  
PKG-PRC002-EN  
Selection  
Procedure  
Model Number  
Description  
Self-Contained Model Number Continued —  
Digit 25 - Industrial Options  
A = Protective Coating Evaporator Coil  
B = Silver Solder  
H = GBAS and RHI  
Digit 29 - Water Piping  
D = Left Hand Basic Piping  
F = Left Hand Intermediate Piping  
K = Left Hand Basic w/ Flow Switch  
M = Left Hand Intermediate  
w/ Flow Switch  
J = VOM and RHI  
K = TCI and RHI  
C = Stainless Steel Screws  
D = A and B  
L = GBAS, VOM, and TCI  
M = GBAS, VOM, and RHI  
N = GBAS, TCI, and RHI  
P = VOM, TCI, and RHI  
R = GBAS, VOM, TCI, and RHI  
0 = None  
E = A and C  
F = B and C  
0 = None  
G = A, B, and C  
Digit 30 - CondenserTubeType  
A = Standard CondenserTubes  
B = 90/10 CuNi CondenserTubes  
0 = None (Air-cooled Only)  
0 = None  
Digit 26 - Drain PanType  
A = Galvanized Sloped  
B = Stainless Steel Sloped  
Digit 34 - Agency  
T = UL Agency Listing  
0 = None  
Digit 31 - Compressor ServiceValves  
1 = With Service Valves  
0 = None  
Digit 27 - Waterside Economizer  
A = Mechanical Clean Full Capacity (4-row)  
B = Mechanical Clean Low Capacity (2-row)  
C = Chemical Clean Full Capacity (4-row)  
D = Chemical Clean Low Capacity (2-row)  
0 = None  
Digit 35 - FilterType  
1 = Construction Throwaway  
2 = Med Eff. Throwaway  
Digit 32 - Miscellaneous System Control  
1 =Timeclock  
Digit 36 - Miscellaneous Control Option  
A = Low Entering AirTemp. Protect  
Device (LEATPD)  
B = High DuctTempT-Stat  
(Ship Separate)  
2 = Interface for Remote HI (IPCB)  
3 = Dirty Filter Switch  
4 = 1 and 2  
Digit 28 -Ventilation Control  
B = Airside Econ w/TraqDamper  
(Top O/A)  
5 = 1 and 3  
C = Plenum High Static Switch  
(Ship Separate)  
6 = 2 and 3  
C = Airside Econ w/ Standard  
Damper (Top O/A)  
7 = 1, 2 and 3  
E = A and B  
0 = None  
E = Airside Econ w/TraqDamper and  
Comparative Enthalpy  
F = A and C  
Digit 33 - Control Interface Options  
A = Generic BAS Module (GBAS)  
B =Ventilation Override Module  
(VOM)  
C =Tracer Comm. Interface Module  
(TCI)  
D = Remote Human Interface (RHI)  
E = GBAS and TCI  
F = VOM and TCI  
G = GBAS and VOM  
H = B and C  
(Top O/A)  
L = A, B, and C  
F = Airside Econ w/ Standard Damper and  
Comparative Enthalpy (Top O/A)  
H = None, 2-Position DamperVentilation  
Interface  
0 = None  
J = Airside Economizer Interface  
K = Airside Economizer Interface w/  
Comparative Enthalpy  
Self-Contained Accessory Model Number Description  
P
1
S
2
W
3
F
4
S
A
6
1
1
8
0
9
AO  
10 11  
5
7
Digit 1 - Parts/Accessories  
Digit 7 - Low Entering AirTemperature  
Protection Device (Field Installed)  
1 = Low Entering AirTempeature  
Protection Device  
C = BAYSENS014 - ZoneTemp with  
P = Parts/Accessories  
Timed Override Button, Setpoint Dial  
(CV andVAV)  
Digit 2 - Unit Model  
S= Self-Contained  
E = BAYSENS008 - CV Zone Sensor  
F = BAYSENS010 - CV Zone Sensor with  
Indicator Lights  
G = BAYSENS019 - CV Programmable  
Night Setback Sensor  
H = BAYSENS021 -VAV Zone Sensor  
with Indicator Lights  
J = BAYSENS020 -VAV Programmable  
Night Setback Sensor  
K = Remote Sensor Kit  
L = Outside AirTemperature Sensor Kit  
M = Outside Air Humidity Sensor Kit  
0 = None  
0 = None  
Digit 3 - Shipment  
W = With Unit  
Digit 8 - Carbon Dioxide Sensor (field  
installed)  
1 = Carbon Dioxide Sensor Kit  
0 = None  
Digit 4 - Development Sequence  
F = Signature Series  
G = Modular Series  
Digit 9 - Not Used  
0 = None  
Digit 5 - Sensors and Other Accessories  
S = Sensors  
Digit 10, 11 - Design Sequence  
A0 = A Design  
Digit 6 - Sensors (Field Installed)  
A = BAYSENS017 - ZoneTemp Only (CV  
andVAV)  
B = BAYSENS013 - ZoneTemp with  
Timed Override Button (CV andVAV)  
PKG-PRC002-EN  
15  
Selection  
Procedure  
Model Number  
Description  
Remote Air-Cooled Condenser Model Number Description  
C
C
2
R
3
C
4
020  
5 6 7  
4
8
A
9
AO  
1011  
1
12  
A
13  
0
14  
0
15  
T
16  
1
Digit 1 - Unit Model  
3 = Protective Coating with  
Finish Coat  
Digit 8 - UnitVoltage  
4 = 460Volt/60 Hz/3 ph  
5 = 575Volt/60 Hz/3 ph  
6 = 200Volt/60 Hz/3 ph  
C = Condenser  
Digit 2 - UnitType  
C = Commercial  
I = Industrial  
Digit 13 - Coil Options  
A = Non-Coated Aluminum  
C = Protective Coating Aluminum  
Digit 9 - Control Option  
0 = No Low Ambient Damper, I-Pak.  
A = No Low Ambient Damper,T-Stat.  
B = Low Ambient, I-Pak.  
Digit 3 - Condenser Medium  
Digit 14 - Unit Isolators  
0 = None  
A = Spring Isolators  
B = Isopads  
R = Remote  
Digit 4 - Development Sequence  
C = C  
C = Low Ambient,T-Stat.  
Digit 10, 11 - Design Sequence  
AO = “A” Design Sequence  
Digit 15 - Panels  
0 = None  
1 = Louvered Panels  
Digit 5, 6, 7 - Nominal Capacity  
020 = 20Tons  
Digit 12 - Unit Finish  
1 = Paint (Executive Beige)  
2 = Protective Coating  
029 = 29Tons  
035 = 35Tons  
Digit 16 - Agency Listing  
0 = None  
U =With UL Listing  
040 = 40Tons  
050 = 50Tons  
060 = 60Tons  
16  
PKG-PRC002-EN  
SCWF/SIWF  
20-38 Tons  
General Data  
Table GD-1. SCWF/SIWFWater-Cooled Self-Contained, 20-38Tons  
Unit Size  
20  
22  
25  
29  
32  
35  
38  
Compressor Data  
Quantity  
NominalTon/Comp  
Circuits  
2
10  
2
2
10  
2
2
10  
2
1/1  
15/10  
2
1/1  
15/10  
2
3
10  
3
3
10  
3
EvaporatorCoilData  
Rows  
2
2
3
2
4
3
4
Sq. Ft.  
21.81  
(2.03)  
144  
21.81  
(2.03)  
144  
21.81  
(2.03)  
144  
29.98  
(2.79)  
144  
29.98  
(2.79)  
144  
31.35  
(2.91)  
120  
31.35  
(2.91)  
144  
Sq. m  
FPF  
CondenserData  
MinimumGPMw/oEcon  
36  
36  
(2.27)  
41  
(2.59)  
80  
36  
(2.27)  
41  
(2.59)  
80  
46  
(2.9)  
60  
(3.79)  
102  
46  
(2.9)  
60  
(3.79)  
102  
54  
(3.41)  
65  
(4.1)  
119  
54  
(3.41)  
65  
(4.1)  
119  
Minimum liters / sec. w/o Econ (2.27)  
MinimumGPMw/Econ  
Minimum liters / sec. w/ Econ  
MaximumGPM  
Maximum liters / sec.  
EvaporatorFanData  
Quantity  
41  
(2.59)  
80  
(5.05)  
(5.05)  
(5.05)  
(6.44)  
(6.44)  
(7.51)  
(7.51)  
1
1
1
1
1
1
1
Size (Dia. - inches)  
Size (Dia. - mm)  
MinimumHP  
MinimumkW  
MaximumHP  
MaximumkW  
MinimumDesignCFM  
Minimum Design liter / sec.  
MaximumDesignCFM  
Maximum Design liter / sec.  
General Data  
EER  
IPLV  
16.5"  
(419.1)  
5
(3.73)  
20  
(14.91)  
6325  
(2985)  
8500  
(4012)  
16.5"  
(419.1)  
5
(3.73)  
20  
(14.91)  
6325  
(2985)  
9350  
(4413)  
16.5"  
(419.1)  
5
(3.73)  
20  
(14.91)  
6500  
(3068)  
10625  
(5014)  
18.25"  
(463.6)  
5
(3.73)  
25  
(18.64)  
8700  
(4106)  
12325  
(5817)  
18.25"  
(463.6)  
5
(3.73)  
25  
(18.64)  
8700  
(4106)  
13600  
(6418)  
20"  
(508)  
5
(3.73)  
25  
(18.64)  
9100  
(4295)  
14875  
(7020)  
20"  
(508)  
5
(3.73)  
25  
(18.64)  
9880  
(4663)  
16150  
(7622)  
12.9  
13.6  
12.6  
12.9  
13.4  
13.6  
14.1  
14.5  
13.6  
13.0  
13.3  
12.8  
13.4  
12.4  
Refrigerant Charge - lbs. R-22  
Circuit A  
Circuit B  
24  
24  
-
24  
24  
-
24  
24  
-
28  
24  
-
30  
25  
-
24  
24  
24  
25  
25  
25  
Circuit C  
Refrigerant Charge - kg R-22  
Circuit A  
Circuit B  
Circuit C  
(10.9)  
(10.9)  
-
(10.9)  
(10.9)  
-
(10.9)  
(10.9)  
-
(12.7)  
(10.9)  
-
(13.6)  
(11.3)  
-
(10.9)  
(10.9)  
(10.9)  
(11.3)  
(11.3)  
(11.3)  
Capacity Steps - %  
Filter Data  
Quantity  
100/53/0  
100/53/0  
100/53/0  
100/62/39/0  
100/59/39/0  
100/65/31/0  
100/65/30/0  
8
8
8
8
8
8
8
Size (inches)  
Size (mm)  
Quantity  
20x18x2  
20x18x2  
20x18x2  
(508 X 457 X 51)  
4
20x18x2  
(508 X 457 X 51)  
4
20x18x2  
(508 X 457 X 51)  
4
20x18x2  
20x18x2  
(508 X 457 X 51) (508 X 457 X 51)  
(508 X 457 X 51) (508 X 457 X 51)  
4
4
4
4
Size (inches)  
Size (mm)  
20x20x2  
20x20x2  
20x20x2  
(508 X 508 X 51)  
20x20x2  
(508 X 508 X 51)  
20x20x2  
(508 X 508 X 51)  
20x20x2  
20x20x2  
(508 X 508 X 51) (508 X 508 X 51)  
(508 X 508 X 51) (508 X 508 X 51)  
Notes:  
1. Compressors areTrane 3D® scroll.  
2. EER and IPV are rated in accordance to the ARI Standard 340/360-93. Based on 80/67 F (26.7/19.4 C) to the evaporator coil,  
nominal airflow and 85-95 F (29.4/35 C) condenser water.  
3. All units operate with R-22. Units ships with full operating charge.  
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.  
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.  
6. Filter sizes are for units without hot water or steam heating coils.  
Table GD-2. SCWF/SIWF Refrigerant Circuits,  
Number of Compressors by Circuit  
Circuit  
1
2
3
4
Unit Size  
20/22/25Ton  
1- 10T 1- 10T  
1- 15T 1- 10T  
29/32Ton  
35/38Ton  
42/46Ton  
52/58Ton  
60/72Ton  
80Ton  
1- 10T 1- 10T 1- 10T  
1- 15T 1- 10T 1- 10T  
1- 15T 1- 15T 1- 15T  
1- 15T 1- 15T 1- 15T 1- 10T  
1- 15T 1- 15T 1- 15T 1- 15T  
Note: This table depicts compressor location in unit, plan  
view from left corner.  
PKG-PRC002-EN  
17  
SCWF/SIWF  
42-80 Tons  
General Data  
Table GD-3. SCWF/SIWF Water-Cooled Self-Contained, 42-80Tons  
Unit Size  
42  
46  
52  
58  
65  
72  
80  
Compressor Data  
Quantity  
NominalTon/Comp  
Circuits  
2/1  
10/15  
3
2/1  
10/15  
3
3
15  
3
3
15  
3
3/1  
15/10  
4
3/1  
15/10  
4
4
15  
4
EvaporatorCoilData  
Rows  
3
4
2
4
3
4
6
Sq. Ft.  
38.57  
(3.58)  
144  
38.57  
(3.58)  
144  
49.09  
(4.56)  
144  
49.09  
(4.56)  
144  
49.09  
(4.56)  
144  
49.09  
(4.56)  
144  
49.09  
(4.56)  
144  
Sq. m  
FPF  
CondenserData  
MiniumGPMw/oEcon  
Minium liters / sec. w/o Econ  
MinimumGPMw/Econ  
Minium liters / sec. w/ Econ  
MaximumGPM  
Maximum liters / sec.  
EvaporatorFanData  
Quantity  
Size (Dia. - inches)  
Size (Dia. - mm)  
MinimumHP  
MinimumkW  
MaximumHP  
MaximumkW  
MinimumDesignCFM  
Minimum Design liter / sec.  
MaximumDesignCFM  
Maximum Design liter / sec.  
General Data  
EER  
64  
(4.04)  
64  
(4.04)  
142  
(8.96)  
64  
(4.04)  
64  
(4.04)  
142  
(8.96)  
84  
(5.3)  
84  
(5.3)  
186  
84  
(5.3)  
84  
(5.3)  
186  
102  
(6.43)  
102  
(6.43)  
226  
102  
(6.43)  
102  
(6.43)  
226  
112  
(7.07)  
112  
(7.07)  
248  
(11.73)  
(11.73)  
(14.26)  
(14.26)  
(15.65)  
1
25"  
(635)  
7.5  
(5.59)  
30  
(22.37)  
11200  
(5286)  
17850  
(8424)  
1
25"  
(635)  
7.5  
(5.59)  
30  
(22.37)  
11960  
(5645)  
19550  
(9227)  
1
25"  
(635)  
10  
(7.46)  
50  
(37.29)  
14250  
(6725)  
22100  
(10430)  
1
25"  
(635)  
10  
(7.46)  
50  
(37.29)  
15080  
(7117)  
24650  
(11634)  
1
1
1
27.5"  
(698.5)  
10  
(7.46)  
50  
(37.29)  
16900  
(7976)  
27625  
(13038)  
27.5"  
(698.5)  
10  
(7.46)  
50  
(37.29)  
18700  
(8825)  
29800  
(14064)  
27.5"  
(698.5)  
10  
(7.46)  
50  
(37.29)  
20800  
(9817)  
29800  
(14064)  
14.1  
13.9  
14.2  
13.6  
13.1  
12.9  
13.5  
12.5  
13.1  
12.4  
13.0  
11.8  
13.0  
11.4  
IPLV  
Refrigerant Charge - lbs. R-22  
Circuit A  
Circuit B  
Circuit C  
Circuit D  
28  
24  
24  
-
30  
25  
25  
-
28  
28  
28  
-
30  
30  
30  
-
28  
28  
28  
24  
30  
30  
30  
25  
32  
32  
32  
32  
Refrigerant Charge - kg R-22  
Circuit A  
Circuit B  
(12.7)  
(10.9)  
(13.6)  
(11.3)  
(12.7)  
(12.7)  
(13.6)  
(13.6)  
(12.7)  
(12.7)  
(13.6)  
(13.6)  
(14.5)  
(14.5)  
Circuit C  
Circuit D  
Capacity Steps - %  
Filter Data  
(10.9)  
-
100/71/43/26/0  
(11.3)  
-
100/70/41/30/0  
(12.7)  
-
100/65/32/0  
(13.6)  
-
100/65/30/0  
(12.7)  
(10.9)  
100/71/44/24/0  
(13.6)  
(11.3)  
100/71/43/23/0  
(14.5)  
(14.5)  
100/73/46/20/0  
Quantity  
Size (inches)  
Size (mm)  
Quantity  
Size (inches)  
Size (mm)  
4
4
4
16x20x2  
4
16x20x2  
4
16x20x2  
4
4
16x20x2  
16x20x2  
16x20x2  
16x20x2  
(406 X 508 X 51) (406 X 508 X 51)  
(406 X 508 X 51)  
8
(406 X 508 X 51)  
8
(406 X 508 X 51)  
8
(406 X 508 X 51) (406 X 508 X 51)  
8
8
8
8
16x25x2  
16x25x2  
16x25x2  
16x25x2  
16x25x2  
16x25x2  
16x25x2  
(406 X 635 X 51) (406 X 635 X 51)  
(406 X 635 X 51)  
2
(406 X 635 X 51)  
2
(406 X 635 X 51)  
2
(406 X 635 X 51) (406 X 635 X 51)  
Quantity  
Size  
2
2
2
2
20x20x2  
20x20x2  
20x20x2  
20x20x2  
20x20x2  
20x20x2  
20x20x2  
Size (mm)  
Quantity  
Size  
(508 X 508 X 51) (508 X 508 X 51)  
(508 X 508 X 51)  
4
(508 X 508 X 51)  
4
(508 X 508 X 51)  
4
(508 X 508 X 51) (508 X 508 X 51)  
4
4
4
4
20x25x2  
20x25x2  
20x25x2  
20x25x2  
20x25x2  
20x25x2  
20x25x2  
Size (mm)  
(508 X 635 X 51) (508 X 635 X 51)  
(508 X 635 X 51)  
(508 X 635 X 51)  
(508 X 635 X 51)  
(508 X 635 X 51) (508 X 635 X 51)  
Notes:  
1. Compressors areTrane 3D® scroll.  
2. EER and IPV are rated in accordance to the ARI Standard 340/360-93. Based on 80/67 F (26.7/19.4 C) to the evaporator coil, nominal airflow and 85-95 F (29.4/35 C) condenser  
water.  
3. All units operate with R-22. Units ships with full operating charge.  
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.  
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.  
6. Filter sizes are for units without hot water or steam heating coils  
18  
PKG-PRC002-EN  
SCRF/SIRF  
20-60 Tons  
General Data  
Table GD-4. SCRF/SIRFAir-Cooled Self-Contained  
Unit Size  
20  
25  
29  
30  
35  
40  
50  
60  
Compressor Data  
Quantity  
NominalTon/Comp  
Circuits  
2
10  
2
1/1  
15/10  
2
1/1  
15/10  
2
3
10  
2
3
10  
2
2/1  
10/15  
2
3
15  
2
4
15  
2
EvaporatorCoilData  
Rows  
Sq. Ft.  
Sq. m  
FPF  
3
2
4
3
4
4
4
6
21.81  
(2.03)  
144  
29.98  
(2.79)  
144  
29.98  
(2.79)  
144  
31.35  
(2.91)  
120  
31.35  
(2.91)  
144  
38.57  
(3.58)  
144  
49.09  
(4.56)  
144  
49.09  
(4.56)  
144  
EvaporatorFanData  
Quantity  
1
1
1
1
1
1
1
1
Size (Dia. - inches)  
Size (Dia. - mm)  
MinimumHP  
MinimumkW  
MaximumHP  
MaximumkW  
MinimumDesignCFM  
Minimum Design liters / sec.  
MaximumDesignCFM  
16.5"  
(419.1)  
5
(3.73)  
20  
(14.91)  
6500  
(3068)  
10625  
18.25"  
(463.6)  
5
(3.73)  
25  
(18.64)  
8700  
(4106)  
12325  
(5817)  
18.25"  
(463.6)  
5
(3.73)  
25  
(18.64)  
8700  
(4106)  
13600  
(6418)  
20"  
(508)  
5
(3.73)  
25  
(18.64)  
9100  
(4295)  
14875  
(7020)  
20"  
(508)  
5
(3.73)  
25  
(18.64)  
9880  
(4663)  
16150  
(7622)  
25"  
(635)  
7.5  
(5.59)  
40  
(22.37)  
11960  
(5645)  
19550  
(9227)  
25"  
(635)  
10  
(7.46)  
40  
(37.29)  
15080  
(7117)  
24650  
(11634)  
27.5"  
(698.5)  
10  
(7.46)  
50  
(37.29)  
20800  
(9817)  
29800  
(14064)  
Maximum Design liters / sec. (5014)  
General Data  
EER  
10.8  
11.8  
57.2  
10.8  
12.1  
66.7  
10.8  
11.4  
72  
11.0  
12.8  
57  
11.2  
12.6  
57.2  
11.3  
12.5  
66.7  
10.8  
12.0  
72  
9.9  
10.0  
72  
IPLV  
Refrigerant Charge - lbs. R-22  
Refrigerant Charge - kg R-22 (25.9)  
(30.3)  
(32.7)  
(25.9)  
(25.9)  
(30.3)  
(32.7)  
(32.7)  
Capacity Steps - %  
Filter Data  
Quantity  
Size (inches)  
Size (mm)  
Quantity  
100/53/0  
100/62/39/0  
100/59/39/0  
100/65/31/0  
100/65/30/0 100/70/41/30/0  
100/65/30/0  
100/73/46/20/0  
8
8
8
8
8
4
16x20x2  
(406x508x51)  
8
4
16x20x2  
(406x508x51)  
8
4
16x20x2  
(406x508x51)  
8
20x18x2  
20x18x2  
20x18x2  
20x18x2  
(508x457x51)  
4
20x18x2  
(508x457x51)  
4
(508x457x51) (508x457x51) (508x457x51)  
4
4
4
Size (inches)  
Size (mm)  
Quantity  
20x20x2  
20x20x2  
20x20x2  
20x20x2  
(508x508x51)  
20x20x2  
(508x508x51)  
16x25x2  
(406x635x51)  
2
16x25x2  
(406x635x51)  
2
16x25x2  
(406x635x51)  
2
(508x508x51) (508x508x51) (508x508x51)  
Size (inches)  
Size (mm)  
Quantity  
20x20x2  
(508x508x51)  
4
20x20x2  
(508x508x51)  
4
20x20x2  
(508x508x51)  
4
Size  
Size (mm)  
CCRC/CIRC Unit Match  
20x25x2  
(508x635x51)  
40  
20x25x2  
(508x635x51)  
50  
20x25x2  
(508x635x51)  
60  
20  
29  
29  
35  
35  
Notes:  
1. Compressors areTrane 3D® scroll.  
2.EER and IPLV are rated in accordance to the ARI Standard 340/360-93. Based on 80/67 F (26.7/19.4 C) to the evaporator coil, nominal airflow and 95 F (35 C) ambient.  
3.All units operate with R-22. Units ships with a dry nitrogen holding charge.  
4. Maximum cfm limits are set to prevent moisture carryover on the evaporator coil.  
5. Minimum cfm limits are set to ensure stable thermal expansion valve operation at low load conditions.  
6. Filter sizes are for units without hot water or steam heating coils  
Table GD-5. SCRF/SIRF Refrigerant Circuits,  
Number of Compressors by Circuit  
Circuit  
1
2
Unit Size  
20 Ton  
1-10T  
1-15T  
1- 10T  
1-10T  
1-10T  
1-15T  
1-15T  
2-15T  
25/29Ton  
30/35Ton  
40Ton  
2-10T  
1-10T, 1-15T  
2-15T  
50Ton  
60Ton  
2-15T  
Note: This table depicts compressor location in unit, plan  
view from left corner  
PKG-PRC002-EN  
19  
General Data  
CCRC/CIRC  
Table GD-6. CCRC/CIRC Remote Air-Cooled Condenser  
Unit Size  
20  
493  
29  
538  
35  
640  
40  
725  
50  
1040  
(304.8)  
60  
1122  
(328.8)  
Gross Heat Rejection (MBH)  
Gross Heat Rejection (kW)  
Condenser Fan Data  
Number/Type  
(144.5)  
(157.7)  
(187.6)  
(212.5)  
4/Prop  
26  
4/Prop  
26  
6/Prop  
26  
6/Prop  
26  
8/Prop  
26  
8/Prop  
26  
Size (inches)  
Size (mm)  
Fan Drive  
No. of Motors/HP ea.  
NominalCFM  
Nominal (liters / sec)  
Condenser Coil Data  
Circuit 1 Size (in.)  
Circuit 1 Size (mm)  
Circuit 2 No./Size (in.)  
Circuit 2 No./Size (mm)  
Face Area (sq. ft.)  
Face Area (sq.m)  
Rows/fpf  
(660.4)  
Direct  
4/1  
18,800  
(8873)  
(660.4)  
Direct  
4/1  
21,200  
(10005)  
(660.4)  
Direct  
6/1  
35,600  
(16801)  
(660.4)  
Direct  
6/1  
39,800  
(18784)  
(660.4)  
Direct  
8/1  
46,200  
(21804)  
(660.4)  
Direct  
8/1  
56,400  
(26618)  
1/46x71  
(1/1168x1803)  
1/46x71  
(1/1168x1803)  
45.4  
1/64x71  
(1/1626x1803)  
1/46x71  
(1/1168x1803)  
54.2  
2/46x71  
(2/1168x1803)  
1/46x71  
(1/1168x1803)  
68  
2/46x71  
2/64x71  
2/64x71  
(2/1626x1803)  
2/64x71  
(2/1626x1803)  
126.2  
(2/1168x1803)  
1/64x71  
(1/1626x1803)  
76.9  
(2/1626x1803)  
1/64x71  
(1/1626x1803)  
94.7  
(4.2)  
4/144  
(5)  
4/144  
(6.3)  
4/144  
(7.1)  
4/144  
(8.8)  
4/144  
(11.7)  
4/144  
Ambient Temperature Operating Range  
Standard Ambient (F)  
50-115  
50-115  
(10 - 46.1)  
0-115  
50-115  
(10 - 46.1)  
0-115  
50-115  
(10 - 46.1)  
0-115  
50-115  
(10 - 46.1)  
0-115  
50-115  
(10 - 46.1)  
0-115  
Standard Ambient (C)  
Low Ambient Option (F)  
Low Ambient Option (C)  
(10 - 46.1)  
0-115  
(-17.8 - 46.1)  
(-17.8 - 46.1)  
(-17.8 - 46.1)  
(-17.8 - 46.1)  
(-17.8 - 46.1)  
(-17.8 - 46.1)  
Notes:  
1. Gross Heat Rejection is at a 20 F (-6.7 C) ITD (InitialTemperature Difference) between condensing temperature and ambient air entering condenser (includes the effect of  
subcooling).  
2. Operating charge is for entire unit, including 100 feet of interconnecting piping.  
3. At conditions of 95 F (35 C), condenser is 95 percent full.  
Table GD-7. SCRF/SIRF Air–Cooled Self–Contained and CCRC/CIRC Remote Air-Cooled Condenser  
Unit Size  
20  
29  
35  
40  
50  
60  
Refrigerant Circuit General Data  
No. of Refrigerant Circuits  
Operating Charge - lbs. R-22  
Operating Charge - kg R-22  
Cond. Storage Cap. - lbs. R-22  
Cond. Storage Cap. - kg R-22  
2
2
2
2
2
2
36/36  
58/36  
72/36  
94/36  
115/58  
115/115  
(52.2/56.7)  
122/122  
(55.3/55.3)  
(16.3/16.3)  
44/44  
(20/20)  
(26.3/16.3)  
61/44  
(27.7/20)  
(32.7/16.3)  
88/44  
(39.9/20)  
(42.6/16.3)  
105/44  
(47.6/20)  
(52.2/26.3)  
122/122  
(55.3/55.3)  
Notes:  
1. Gross heat rejection is at a 20 F (-6.7 C) ITD (initial temperature difference) between condensing temperature and ambient air entering condenser (includes the effect of  
subcooling).  
2. Operating charge is for entire system, which includes the air–cooled self–contained, remote air–cooled condenser, and 25 feet of interconnecting refrigerant piping.  
3. At conditions of 95 F (35 C), condenser storage capacity is 95% full.  
4. To determine the correct amount of refrigerant needed for a particuliar application, reference the Trane Reciprocating Refrigeration Manual.  
20  
PKG-PRC002-EN  
Heating Coil  
General Data  
Table GD-7. Self-Contained Heating Coil  
Unit Size  
SCWF 20 - 38  
SCWF 42 - 80  
SCRF 20 - 35  
SCRF 40 - 60  
Steam Coil  
CoilType  
NS  
NS  
NS  
NS  
Rows Rows  
No./Size (inches)  
No./Size(mm)  
FPF  
1
((2) 24x58)  
((2) 609.6x1473.2)  
42  
1
((2) 30x81)  
((2) 762x2057.4)  
42  
1
((2) 24x58)  
((2) 609.6x1473.2)  
42  
1
((2) 30x81)  
((2) 762x2057.4)  
42  
Hot Water Coil  
CoilType  
Rows  
No./Size (inches)  
No./Size(mm)  
FPF  
WC  
WC  
WC  
WC  
1
(2) 24x58  
((2) 609.6x1473.2)  
80  
1
(2) 30x81  
((2) 762x2057.4)  
80  
1
(2) 24x58  
((2) 609.6x1473.2)  
80  
1
(2) 30x81  
((2) 762x2057.4)  
80  
Filter Data  
Quantity  
4
4
4
4
Size (inches)  
Size (mm)  
Quantity  
Size (inches)  
Size (mm)  
Quantity  
20x18x2  
(508x457x51)  
8
20x20x2  
(508x508x51)  
16x20x2  
(406x508x51)  
8
16x25x2  
(406x635x51)  
2
20x18x2  
(508x457x51)  
8
20x20x2  
(508x508x51)  
16x20x2  
(406x508x51)  
8
16x25x2  
(406x635x51)  
2
Size (inches)  
Size (mm)  
Quantity  
Size (inches)  
Size (mm)  
20x20x2  
(508x508x51)  
4
20x25x2  
(508x635x51)  
20x20x2  
(508x508x51)  
4
20x25x2  
(508x635x51)  
Notes:  
1. Hot water and steam heating coils have Prima-Flo® fins without turbulators.  
2. For coil capacites, useTOPSS(Trane Official Product Selection Program).  
3. Full capacity coils consist of two coils stacked and piped in parallel.  
PKG-PRC002-EN  
21  
Performance  
Data  
Airside Pressure  
Drops  
Chart PD-1. Airside Pressure Drop  
SCWF/SIWF 20, 22, 25 and SCRF/SIRF 20  
Chart PD-2. Airside Pressure Drop  
SCWF/SIWF 29, 32 and SCRF/SIRF 25, 29  
Chart PD-3. Airside Pressure Drop  
SCWF/SIWF 35, 38 and SCRF/SIRF 30, 35  
Chart PD-4. Airside Pressure Drop  
SCWF/SIWF 42, 46 and SCRF/SIRF 40  
Notes:  
1. Dotted line on construction filters indicates cfm where face velocity exceeds manufacturers recommended maximum of 300 fpm. After startup, construction filters must be  
replaced with medium velocity or high velocity filters.  
2. Air pressure drop through electric heat is 0.5 inches WC.  
3. Refer to Page 25-26 for pressure drop through flexible horizontal discharge plenum.  
4. Refer to Page 24 for pressure drop through heating coils.  
22  
PKG-PRC002-EN  
Performance  
Data  
Airside Pressure  
Drops  
Chart PD-5. Airside Pressure Drop  
SCWF/SIWF 52, 58 and SCRF/SIRF 50  
Chart PD-6. Airside Pressure Drop  
SCWF/SIWF 65  
Chart PD-8. Airside Pressure Drop  
Chart PD-7. Airside Pressure Drop  
SCWF/SIWF 72  
SCWF/SIWF 80 and SCRF/SIRF 60  
Notes:  
1. Dotted line on construction filters indicates cfm where face velocity exceeds manufacturers recommended maximum of 300 fpm. After startup, construction filters must be  
replaced with medium velocity or high velocity filters.  
2. Air pressure drop through electric heat is 0.5 inches WC.  
3. Refer to Page 25-26 for pressure drop through flexible horizontal discharge plenum.  
4. Refer to Page 24 for pressure drop through heating coils.  
PKG-PRC002-EN  
23  
Performance  
Data  
Airside Pressure  
Drops  
Heating Coils  
Chart PD-10. Airside Pressure Drop  
Chart PD-9. Airside Pressure Drop  
Steam Coil  
Hot Water Coil  
20 to 80-Ton Units  
20 to 80-Ton Units  
For NS Coils  
24  
PKG-PRC002-EN  
Performance  
Data  
Airside Pressure  
Drops  
Discharge Plenum  
Chart PD-11. Airside Pressure Drop  
Standard Height Discharge Plenum  
Chart PD-10. Airside Pressure Drop,  
Standard Height Discharge Plenum  
42 to 80Ton Unit  
20 to 38Ton Unit  
Chart PD-12. Airside Pressure Drop  
Chart PD-13. Airside Pressure Drop  
Low Height Discharge Plenum  
20 to 38Ton Unit  
Low Height Discharge Plenum  
42 to 80Ton Unit  
Note:  
“Primary” refers to the side where the static pressure drop was measured. This value  
must be added to the unit external static pressure for proper fan horsepower  
determination.  
PKG-PRC002-EN  
25  
Performance  
Data  
Airside Pressure  
Drops  
Chart PD-14. Airside Pressure Drop  
Discharge Plenum  
Extended Height Discharge Plenum  
20 to 38-Ton Unit  
Chart PD-15. Airside Pressure Drop  
Extended Height Discharge Plenum  
42 to 80-Ton Unit  
26  
PKG-PRC002-EN  
Performance  
Data  
Airside Pressure  
Drops  
Chart PD-16. Airside Pressure Drop  
Airside Economizer with  
Standard Damper  
Airside Economizer with Standard Damper  
20 to 38-Ton Unit  
Chart PD-17. Airside Pressure Drop  
Airside Economizer with Standard Damper  
42 to 80-Ton Unit  
PKG-PRC002-EN  
27  
Performance  
Data  
Airside Pressure  
Drops  
Chart PD-18. Airside Pressure Drop  
Airside Economizer with  
Traq™ Damper  
Airside Economizer with Traq™ Damper  
Air Flow Rate CFM  
28  
PKG-PRC002-EN  
Performance Waterside  
Data Pressure Drop  
Chart PD-20. Waterside Pressure Drop  
SCWF/SIWF 29, 32  
Chart PD-19. Waterside Pressure Drop  
SCWF/SIWF 20, 22, 25  
Chart PD-22. Waterside Pressure Drop  
SCWF/SIWF 42, 46  
Chart PD-21. Waterside Pressure Drop  
SCWF/SIWF 35, 38  
Note: Each curve provides total water pressure drop through the entire unit including all accessories and internal valves and piping. Do not add curves together.  
PKG-PRC002-EN  
29  
Performance Waterside  
Data Pressure Drop  
Chart PD-23. Waterside Pressure Drop  
SCWF/SIWF 52, 58  
Chart PD-24. Waterside Pressure Drop  
SCWF/SIWF 65  
Chart PD-25. Waterside Pressure Drop  
SCWF/SIWF 72  
Chart PD-26. Waterside Pressure Drop  
SCWF/SIWF 80  
Note: Each curve provides total water pressure drop through the entire unit including all accessories and internal valves and piping. Do not add curves together.  
30  
PKG-PRC002-EN  
Performance  
Data  
Table PD-1. CFM Capacity CorrectionTable  
Cfm Compared  
To Rated  
Quanitity  
-20%  
Cooling  
Capacity  
Multiplier  
0.970  
Sensible  
Capacity  
Multiplier  
0.910  
-10%  
0.985  
0.955  
DX Cooling  
Std  
+3%  
+6%  
-20%  
-10%  
Std  
1.000  
1.005  
1.009  
0.970  
0.985  
1.000  
1.000  
1.014  
1.027  
0.910  
0.955  
1.000  
Waterside  
Economizer  
+3%  
+6%  
1.005  
1.009  
1.014  
1.027  
PKG-PRC002-EN  
31  
Performance  
Data  
Water-Cooled  
20 Ton  
Table PD-2. SCWF/SIWF 20 - Economizer Full Capacity - 8,000 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
132.5  
136.2  
138.9  
119.1  
122.4  
125.0  
92.8  
Flow  
gpm  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
210.3  
220.8  
228.8  
265.7  
284.6  
299.0  
339.2  
364.8  
383.9  
230.9  
239.2  
245.2  
271.3  
288.1  
300.9  
338.5  
363.9  
383.0  
262.5  
270.4  
275.9  
283.5  
298.0  
309.0  
340.7  
364.4  
382.6  
189.3  
193.7  
197.1  
160.4  
167.9  
173.7  
133.9  
143.3  
150.5  
226.2  
234.5  
240.6  
204.6  
211.3  
216.5  
176.3  
185.8  
193.1  
262.5  
270.4  
275.9  
251.3  
257.1  
261.6  
219.3  
228.2  
235.1  
53.4  
52.4  
51.5  
55.6  
54.5  
53.5  
58.6  
57.2  
56.0  
54.2  
53.0  
52.0  
55.9  
54.6  
53.6  
58.5  
57.1  
55.9  
55.5  
54.0  
52.9  
56.3  
54.9  
53.8  
58.6  
57.1  
55.9  
132.5  
136.2  
138.9  
155.2  
164.4  
171.8  
221.4  
238.3  
251.4  
165.6  
170.2  
173.5  
171.1  
178.2  
183.7  
222.0  
238.0  
250.6  
198.6  
204.1  
208.0  
199.2  
204.8  
208.8  
230.6  
244.2  
255.1  
60.3  
59.5  
59.0  
61.2  
60.5  
59.9  
63.9  
62.9  
62.2  
61.6  
60.7  
60.0  
61.8  
60.9  
60.2  
63.9  
62.9  
62.2  
62.9  
61.8  
60.9  
63.0  
61.8  
61.0  
64.2  
63.1  
62.3  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
98.5  
103.0  
165.6  
170.2  
173.5  
166.8  
169.4  
171.4  
135.4  
140.8  
145.1  
198.6  
204.1  
208.0  
199.2  
204.8  
208.8  
180.5  
185.1  
188.8  
80  
85  
Table PD-3. SCWF/SIWF 20 - Economizer Low Capacity - 8,000 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
135.3  
144.0  
146.2  
114.8  
119.7  
123.3  
90.6  
55 F  
Sensible  
MBh  
92.8  
96.1  
98.4  
88.3  
90.3  
92.0  
64.5  
Flow  
gpm  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
50  
60  
70  
Total  
MBh  
LWT  
F
Total  
MBh  
92.8  
LWT  
F
F
F
140.0  
147.0  
152.4  
175.6  
188.4  
198.0  
224.3  
241.1  
253.7  
160.2  
166.4  
170.7  
177.8  
189.3  
198.1  
223.8  
240.5  
253.1  
183.2  
190.2  
195.1  
188.1  
197.7  
205.0  
223.6  
240.0  
252.6  
50.6  
49.9  
49.4  
52.0  
51.3  
50.7  
54.0  
53.0  
52.2  
51.4  
50.5  
49.9  
52.1  
51.3  
50.7  
54.0  
53.0  
52.2  
52.3  
51.3  
50.6  
52.5  
51.6  
50.9  
53.9  
53.0  
52.2  
58.7  
58.2  
57.8  
59.1  
58.6  
58.2  
60.9  
60.2  
59.7  
59.6  
59.0  
58.5  
59.7  
59.0  
58.5  
60.8  
60.2  
59.7  
60.6  
59.8  
59.2  
60.6  
59.8  
59.2  
61.0  
60.3  
59.8  
62  
96.1  
98.4  
102.0  
107.8  
112.6  
146.7  
157.3  
165.5  
116.1  
120.1  
123.0  
116.4  
120.8  
124.2  
146.2  
156.8  
165.0  
139.3  
144.1  
147.6  
139.6  
144.4  
147.9  
151.1  
159.8  
166.7  
75  
67  
72  
62  
67  
72  
62  
67  
72  
96.5  
68.0  
70.7  
101.0  
160.2  
166.4  
170.7  
149.8  
154.2  
157.5  
124.8  
130.7  
135.2  
183.2  
190.2  
195.1  
187.8  
191.4  
194.3  
158.9  
164.7  
169.2  
116.1  
120.1  
123.0  
111.3  
115.7  
119.1  
98.8  
102.2  
104.8  
139.3  
144.1  
147.6  
139.6  
144.4  
147.9  
134.6  
137.4  
139.7  
80  
85  
32  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
20 Ton  
Table PD-4. SCWF/SIWF 20 Gross Cooling Capacity - 8,000 cfm, 60 gpm  
Entering WaterTemp  
Entering Air  
EDB EWB  
75 F  
Total Sensible  
85 F  
Total Sensible  
95 F  
Total Sensible  
F
F
62  
67  
72  
62  
67  
72  
62  
67  
72  
MBh  
244  
266  
289  
244  
266  
289  
247  
265  
288  
MBh  
185  
150  
114  
218  
183  
147  
246  
216  
180  
LWT  
84.7  
85.5  
86.3  
84.7  
85.5  
86.3  
84.8  
85.5  
86.3  
MBh  
235  
256  
278  
235  
256  
278  
239  
256  
278  
MBh  
181  
146  
110  
214  
179  
143  
239  
211  
176  
LWT  
94.7  
95.4  
96.2  
94.7  
95.4  
96.1  
94.8  
95.4  
96.1  
MBh  
225  
246  
267  
226  
245  
267  
231  
245  
267  
MBh  
176  
141  
106  
209  
174  
139  
231  
207  
171  
LWT  
104.6  
105.3  
106.0  
104.6  
105.3  
106.0  
104.8  
105.3  
106.0  
75  
80  
85  
Chart PD-27. SCWF/SIWF 20 Fan Performance for CV or with VFD  
Chart PD-28. SCWF/SIWF 20 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal  
cabinet static losses. To determine static pressure to  
be used with these curves, add filter, economizer,  
flexible horizontal discharge and heat pressure  
drops to external duct static pressure.  
PKG-PRC002-EN  
33  
Performance  
Data  
Water-Cooled  
22 Ton  
Table PD-5. SCWF/SIWF 22 - Economizer Full Capacity - 8,800 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
Flow  
gpm  
Total  
MBh  
LWT  
MBh  
Total  
MBh  
LWT  
F
F
F
F
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
226.8  
237.6  
245.9  
286.3  
305.8  
320.8  
365.5  
391.8  
411.9  
249.7  
258.1  
264.5  
292.3  
309.6  
322.9  
364.6  
390.8  
410.9  
284.2  
292.5  
298.4  
305.7  
320.5  
332.0  
366.9  
391.3  
410.3  
205.7  
210.2  
213.8  
173.7  
181.4  
187.5  
144.5  
154.1  
161.6  
244.6  
253.0  
259.4  
222.0  
228.8  
234.2  
190.8  
200.5  
208.1  
284.2  
292.5  
298.4  
273.1  
279.0  
283.6  
237.7  
246.8  
254.0  
53.2  
52.2  
51.4  
55.4  
54.3  
53.3  
58.3  
56.9  
55.7  
54.1  
52.8  
51.9  
55.6  
54.4  
53.4  
58.3  
56.8  
55.7  
55.3  
53.9  
52.7  
56.1  
54.7  
53.6  
58.3  
56.9  
55.7  
143.3  
147.3  
150.2  
167.0  
176.4  
184.2  
238.0  
255.6  
269.5  
179.1  
184.0  
187.6  
184.5  
191.8  
197.6  
238.6  
255.2  
268.6  
214.8  
220.7  
225.0  
215.5  
221.4  
225.8  
247.9  
262.1  
273.5  
143.3  
147.3  
150.2  
129.3  
132.6  
135.4  
100.2  
106.1  
110.8  
179.1  
184.0  
187.6  
181.5  
184.1  
186.2  
146.7  
152.2  
156.8  
214.8  
220.7  
225.0  
215.5  
221.4  
225.8  
195.9  
200.7  
204.6  
60.2  
59.5  
58.9  
61.1  
60.3  
59.8  
63.7  
62.7  
62.0  
61.5  
60.6  
59.9  
61.7  
60.8  
60.1  
63.7  
62.7  
62.0  
62.8  
61.7  
60.8  
62.8  
61.7  
60.9  
64.0  
62.9  
62.1  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
Table PD-6. SCWF/SIWF 22 - Economizer Low Capacity - 8,800 cfm  
Entering Water Temp  
55 F  
Entering Air  
EDB EWB  
45 F  
Total  
Flow  
gpm  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
55  
66  
77  
Sensible  
MBh  
LWT  
F
Total  
MBh  
99.6  
Sensible  
MBh  
99.6  
102.9  
105.4  
95.1  
97.1  
98.9  
69.2  
72.6  
LWT  
F
F
F
MBh  
150.1  
157.1  
162.5  
188.1  
200.9  
210.7  
240.1  
256.9  
269.8  
172.2  
178.4  
182.9  
190.4  
201.9  
210.8  
239.6  
256.4  
269.2  
196.8  
203.9  
209.0  
201.6  
211.1  
218.5  
239.3  
255.8  
268.6  
145.0  
155.1  
157.3  
123.5  
128.4  
132.1  
97.1  
50.5  
49.8  
49.2  
51.8  
51.1  
50.5  
53.7  
52.8  
52.0  
51.3  
50.4  
49.7  
51.9  
51.1  
50.5  
53.7  
52.8  
52.0  
52.2  
51.2  
50.4  
52.3  
51.4  
50.7  
53.7  
52.8  
52.0  
58.6  
58.1  
57.7  
59.0  
58.5  
58.1  
60.7  
60.1  
59.6  
59.5  
58.9  
58.4  
59.5  
58.9  
58.4  
60.7  
60.1  
59.6  
60.4  
59.7  
59.1  
60.4  
59.7  
59.1  
60.9  
60.2  
59.6  
62  
102.9  
105.4  
108.9  
114.8  
119.7  
156.6  
167.3  
175.9  
124.5  
128.6  
131.7  
124.8  
129.2  
132.7  
156.1  
166.8  
175.3  
149.5  
154.4  
158.1  
149.7  
154.7  
158.4  
161.4  
170.1  
177.3  
75  
67  
72  
62  
67  
72  
62  
67  
72  
103.0  
107.6  
172.2  
178.4  
182.9  
161.4  
165.8  
169.2  
134.1  
140.0  
144.6  
196.8  
203.9  
209.0  
195.7  
206.2  
209.0  
171.1  
177.0  
181.5  
75.4  
124.5  
128.6  
131.7  
119.3  
123.7  
127.1  
106.2  
109.7  
112.4  
149.5  
154.4  
158.1  
149.7  
154.7  
158.4  
145.1  
147.9  
150.2  
80  
85  
34  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
22 Ton  
Table PD-7 — SCWF/SIWF 22 Gross Cooling Capacity - 8,800 cfm, 66 gpm  
EnteringWaterTemp  
EnteringAir  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
257  
280  
305  
257  
280  
304  
262  
280  
304  
Sensible  
MBh  
197  
159  
120  
Total  
MBh  
248  
270  
294  
248  
270  
294  
254  
270  
293  
Sensible  
MBh  
193  
Total  
MBh  
238  
259  
282  
238  
259  
282  
246  
259  
282  
Sensible  
MBh  
188  
150  
112  
F
F
LWT  
84.3  
85.0  
85.8  
84.3  
85.0  
85.8  
84.4  
85.0  
85.8  
LWT  
94.3  
94.9  
95.7  
94.3  
94.9  
95.7  
94.4  
94.9  
95.7  
LWT  
104.2  
104.9  
105.6  
104.2  
104.9  
105.6  
104.4  
104.8  
105.6  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
155  
116  
233  
228  
223  
80  
85  
194  
190  
186  
156  
152  
147  
261  
254  
246  
230  
226  
221  
191  
187  
183  
Chart PD-29 — SCWF/SIWF 22 Fan Performance for CV or with VFD  
Chart PD-30 — SCWF/SIWF 22 Fan Performance with Inlet Guide Vanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
35  
Performance  
Data  
Water-Cooled  
25 Ton  
Table PD-8. SCWF/SIWF 25 - Economizer Full Capacity -10,000 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
250.7  
261.4  
265.2  
316.1  
335.6  
342.5  
404.1  
429.9  
439.1  
276.9  
285.3  
288.2  
322.6  
339.8  
345.9  
403.2  
428.9  
438.1  
315.6  
324.1  
326.9  
337.7  
352.4  
357.6  
404.8  
429.2  
438.0  
229.6  
234.1  
235.7  
193.1  
200.8  
203.6  
160.2  
169.5  
172.9  
271.1  
279.5  
282.4  
247.4  
254.2  
256.6  
212.1  
221.6  
225.0  
315.6  
324.1  
326.9  
304.9  
310.7  
312.8  
264.6  
273.6  
276.9  
53.0  
52.0  
51.6  
55.0  
53.9  
53.6  
57.8  
56.5  
56.0  
53.8  
52.6  
52.2  
55.2  
54.1  
53.6  
57.8  
56.4  
56.0  
55.0  
53.6  
53.2  
55.7  
54.4  
53.9  
57.9  
56.4  
55.9  
159.0  
163.2  
164.6  
183.8  
193.5  
197.0  
262.3  
280.2  
286.5  
198.7  
203.9  
205.6  
203.9  
211.3  
213.9  
262.8  
279.7  
285.8  
238.3  
244.6  
246.6  
239.1  
245.3  
247.4  
273.0  
287.4  
292.5  
159.0  
163.2  
164.6  
144.0  
147.5  
148.7  
110.9  
116.9  
119.0  
198.7  
203.9  
205.6  
202.9  
205.6  
206.5  
163.2  
168.8  
170.9  
238.3  
244.6  
246.6  
239.1  
245.3  
247.4  
218.6  
223.4  
225.1  
60.0  
59.4  
59.1  
60.8  
60.2  
59.9  
63.3  
62.5  
62.2  
61.3  
60.4  
60.1  
61.5  
60.6  
60.3  
63.3  
62.5  
62.1  
62.6  
61.5  
61.2  
62.6  
61.5  
61.2  
63.7  
62.7  
62.3  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
Table PD-9. SCWF/SIWF 25 - Economizer Low Capacity - 10,000 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
109.2  
112.6  
113.7  
104.8  
106.8  
107.6  
75.8  
Flow  
gpm  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
63  
75  
80  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
164.5  
171.1  
173.5  
205.7  
218.1  
222.4  
262.5  
278.7  
284.5  
189.1  
195.2  
197.2  
208.1  
219.1  
223.1  
262.0  
278.1  
283.9  
216.2  
223.0  
225.4  
220.7  
229.7  
233.0  
261.5  
277.6  
283.2  
158.7  
170.9  
171.9  
136.0  
140.7  
142.3  
106.4  
112.1  
114.1  
189.1  
195.2  
197.2  
178.0  
182.2  
183.7  
147.5  
153.2  
155.2  
216.2  
223.0  
225.4  
214.1  
227.2  
228.4  
188.6  
194.2  
196.2  
50.2  
49.6  
49.3  
51.5  
50.8  
50.6  
53.3  
52.4  
52.1  
51.0  
50.2  
49.9  
51.6  
50.8  
50.6  
53.3  
52.4  
52.1  
51.9  
50.9  
50.6  
52.0  
51.1  
50.8  
53.3  
52.4  
52.1  
109.2  
112.6  
113.7  
118.7  
124.5  
126.7  
170.7  
181.4  
185.2  
136.5  
140.7  
142.2  
136.8  
141.1  
142.6  
170.2  
180.8  
184.6  
163.9  
168.9  
170.6  
164.2  
169.2  
170.9  
175.9  
184.5  
187.7  
58.5  
58.0  
57.8  
58.8  
58.3  
58.2  
60.4  
59.8  
59.6  
59.3  
58.8  
58.6  
59.3  
58.8  
58.6  
60.4  
59.8  
59.6  
60.2  
59.5  
59.3  
60.2  
59.5  
59.3  
60.6  
59.9  
59.7  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
79.2  
80.4  
136.5  
140.7  
142.2  
136.8  
134.8  
136.4  
116.9  
120.4  
121.6  
163.9  
168.9  
170.6  
164.2  
169.2  
170.9  
160.0  
162.8  
163.8  
80  
85  
36  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
25 Ton  
Table PD-10. SCWF/SIWF 25 Gross Cooling Capacity - 10,000 cfm, 75 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
281  
306  
332  
284  
306  
332  
298  
306  
332  
Sensible  
MBh  
234  
184  
133  
Total  
MBh  
270  
294  
319  
274  
294  
319  
288  
295  
319  
Sensible  
MBh  
229  
Total  
MBh  
259  
281  
305  
263  
281  
305  
278  
283  
305  
Sensible  
MBh  
224  
174  
124  
F
F
LWT  
83.9  
84.5  
85.3  
83.9  
84.5  
85.3  
84.3  
84.6  
85.2  
LWT  
93.8  
94.4  
95.1  
93.8  
94.4  
95.1  
94.3  
94.4  
95.1  
LWT  
103.6  
104.3  
105.0  
103.8  
104.3  
104.9  
104.2  
104.3  
104.9  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
179  
129  
278  
272  
263  
80  
85  
231  
227  
221  
180  
176  
171  
298  
288  
278  
278  
272  
267  
228  
223  
218  
Chart PD-31. SCWF/SIWF 25 Fan Performance for CV or with VFD  
Chart PD-32. SCWF/SIWF 25 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to external  
duct static pressure.  
PKG-PRC002-EN  
37  
Performance  
Data  
Water-Cooled  
29 Ton  
Table PD-11. SCWF/SIWF 29 - Economizer Full Capacity - 11,600 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
73  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
302.2  
316.4  
327.9  
382.0  
407.4  
428.3  
488.3  
522.1  
549.9  
332.2  
343.2  
352.0  
389.9  
412.4  
431.0  
487.3  
520.9  
548.6  
377.9  
388.6  
396.6  
407.5  
426.8  
442.8  
489.7  
521.5  
547.9  
272.9  
278.8  
283.8  
231.0  
241.1  
249.5  
192.9  
205.3  
215.7  
325.4  
336.5  
345.3  
294.8  
303.8  
311.3  
254.1  
266.7  
277.2  
377.9  
388.6  
396.6  
362.3  
370.0  
376.5  
316.0  
327.9  
337.9  
53.3  
52.3  
51.4  
55.5  
54.4  
53.4  
58.4  
57.0  
55.8  
54.1  
52.9  
51.9  
55.7  
54.5  
53.5  
58.4  
57.0  
55.8  
55.4  
53.9  
52.8  
56.2  
54.8  
53.7  
58.4  
57.0  
55.7  
190.6  
195.7  
199.7  
222.7  
235.2  
245.9  
318.0  
340.8  
360.0  
238.2  
244.5  
249.4  
245.9  
255.3  
263.4  
318.8  
340.3  
358.8  
285.7  
293.2  
299.0  
286.6  
294.2  
300.1  
331.0  
349.3  
365.1  
190.6  
195.7  
199.7  
171.6  
176.0  
179.8  
133.5  
141.2  
147.7  
238.2  
244.5  
249.4  
240.6  
244.0  
246.9  
195.0  
202.2  
208.5  
285.7  
293.2  
299.0  
286.6  
294.2  
300.1  
260.1  
266.3  
271.7  
60.2  
59.5  
58.9  
61.1  
60.4  
59.8  
63.7  
62.8  
62.1  
61.5  
60.6  
59.9  
61.7  
60.9  
60.2  
63.7  
62.8  
62.0  
62.8  
61.7  
60.9  
62.9  
61.8  
60.9  
64.1  
63.0  
62.2  
62  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
87  
102  
Table PD-12. SCWF/SIWF 29 - Economizer Low Capacity - 11,600 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
133.0  
137.3  
140.7  
126.7  
129.3  
131.8  
92.5  
Flow  
gpm  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
73  
87  
102  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
200.6  
209.8  
217.4  
251.7  
268.6  
282.3  
321.4  
343.5  
361.6  
229.7  
237.9  
244.1  
254.7  
269.9  
282.5  
320.7  
342.8  
360.8  
262.7  
271.9  
279.0  
269.4  
282.0  
292.4  
320.3  
342.1  
360.0  
193.8  
206.5  
209.6  
164.8  
171.2  
176.4  
129.8  
137.7  
144.1  
229.7  
237.9  
244.1  
215.0  
220.8  
225.6  
179.0  
186.8  
193.2  
262.7  
271.9  
279.0  
261.6  
274.4  
278.4  
228.1  
235.8  
242.2  
50.5  
49.8  
49.3  
51.9  
51.2  
50.5  
53.8  
52.9  
52.1  
51.3  
50.5  
49.8  
52.0  
51.2  
50.5  
53.8  
52.9  
52.1  
52.2  
51.3  
50.5  
52.4  
51.5  
50.7  
53.8  
52.9  
52.1  
133.0  
137.3  
140.7  
145.8  
153.5  
160.5  
209.9  
223.9  
235.8  
166.2  
171.6  
175.9  
166.6  
172.4  
177.4  
209.2  
223.2  
235.0  
199.5  
205.9  
211.0  
199.9  
206.3  
211.5  
216.1  
227.6  
237.6  
58.6  
58.2  
57.8  
59.0  
58.5  
58.1  
60.7  
60.1  
59.6  
59.6  
58.9  
58.4  
59.6  
59.0  
58.5  
60.7  
60.1  
59.6  
60.5  
59.7  
59.1  
60.5  
59.7  
59.1  
60.9  
60.2  
59.7  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
97.0  
100.9  
166.2  
171.6  
175.9  
159.4  
165.1  
170.0  
141.7  
146.2  
150.0  
199.5  
205.9  
211.0  
199.9  
206.3  
211.5  
193.2  
196.9  
200.2  
80  
85  
73  
87  
102  
38  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
29 Ton  
Table PD-13. SCWF/SIWF 29 Gross Cooling Capacity - 11,600 cfm, 87 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
335  
365  
397  
336  
365  
396  
347  
365  
396  
Sensible  
MBh  
266  
211  
157  
Total  
MBh  
323  
352  
383  
325  
352  
381  
337  
351  
381  
Sensible  
MBh  
259  
Total  
MBh  
309  
337  
366  
311  
337  
366  
325  
337  
366  
Sensible  
MBh  
254  
201  
146  
F
F
LWT  
84.2  
84.9  
85.6  
84.2  
84.9  
85.6  
84.4  
84.9  
85.6  
LWT  
94.1  
94.8  
95.5  
94.1  
94.8  
95.5  
94.4  
94.8  
95.5  
LWT  
104.0  
104.7  
105.4  
104.0  
104.6  
105.4  
104.3  
104.7  
105.3  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
206  
152  
315  
309  
301  
80  
85  
262  
256  
251  
208  
202  
196  
347  
337  
325  
312  
306  
300  
258  
253  
246  
Chart PD-33. SCWF/SIWF 29 Fan Performance for CV or with VFD  
Chart PD-34. SCWF/SIWF 29 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
39  
Performance  
Data  
Water-Cooled  
32 Ton  
Table PD-14. SCWF/SIWF 32 - Economizer Full Capacity - 12,800 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
80  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
325.8  
340.9  
345.5  
410.8  
438.2  
446.8  
524.5  
561.3  
572.8  
359.2  
371.0  
374.6  
419.5  
443.6  
451.2  
523.3  
560.0  
571.4  
409.2  
420.9  
424.4  
439.0  
459.6  
466.1  
526.4  
560.6  
571.4  
296.8  
303.2  
305.1  
250.1  
260.9  
264.3  
207.6  
221.1  
225.3  
351.8  
363.6  
367.2  
320.1  
329.6  
332.6  
274.5  
288.2  
292.5  
409.2  
420.9  
424.4  
394.1  
402.3  
404.9  
342.5  
355.2  
359.3  
53.1  
52.1  
51.8  
55.3  
54.1  
53.8  
58.1  
56.7  
56.2  
54.0  
52.7  
52.3  
55.5  
54.2  
53.8  
58.1  
56.7  
56.2  
55.2  
53.8  
53.3  
56.0  
54.6  
54.1  
58.2  
56.7  
56.2  
206.2  
212.0  
213.7  
239.5  
252.7  
257.1  
341.3  
366.1  
374.0  
257.7  
264.8  
266.9  
265.0  
275.3  
278.6  
342.0  
365.5  
373.1  
309.1  
317.6  
320.1  
310.1  
318.6  
321.2  
355.4  
375.4  
381.8  
206.2  
212.0  
213.7  
186.4  
191.1  
192.7  
144.0  
152.2  
154.9  
257.7  
264.8  
266.9  
262.1  
265.8  
267.0  
211.3  
219.1  
221.7  
309.1  
317.6  
320.1  
310.1  
318.6  
321.2  
282.6  
289.3  
291.5  
60.2  
59.4  
59.2  
61.0  
60.3  
60.0  
63.5  
62.6  
62.3  
61.4  
60.5  
60.2  
61.6  
60.7  
60.5  
63.6  
62.6  
62.3  
62.7  
61.6  
61.3  
62.8  
61.6  
61.3  
63.9  
62.8  
62.5  
62  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
96  
102  
Table PD-15. SCWF/SIWF 32 - Economizer Low Capacity - 12,800 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
142.6  
147.3  
148.7  
136.5  
139.3  
140.3  
99.0  
103.8  
105.3  
178.3  
184.1  
185.9  
178.6  
176.7  
178.6  
152.4  
157.2  
158.7  
214.0  
220.9  
223.0  
214.4  
221.3  
223.5  
208.3  
212.2  
213.5  
Flow  
gpm  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
80  
96  
102  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
214.8  
224.4  
227.4  
268.8  
286.5  
292.0  
343.2  
366.3  
373.5  
246.7  
255.3  
257.8  
272.1  
287.9  
292.9  
342.5  
365.5  
372.7  
282.0  
291.8  
294.7  
288.3  
301.4  
305.5  
342.0  
364.8  
371.9  
207.4  
222.7  
223.9  
177.2  
183.8  
185.9  
138.9  
147.1  
149.6  
246.7  
255.3  
257.8  
231.7  
237.7  
239.6  
192.3  
200.4  
202.9  
282.0  
291.8  
294.7  
279.8  
296.0  
297.6  
245.6  
253.6  
256.1  
50.4  
49.7  
49.5  
51.7  
51.0  
50.7  
53.6  
52.6  
52.3  
51.2  
50.3  
50.1  
51.8  
51.0  
50.7  
53.6  
52.6  
52.3  
52.0  
51.1  
50.8  
52.2  
51.3  
51.0  
53.5  
52.6  
52.3  
142.6  
147.3  
148.7  
155.5  
163.6  
166.4  
223.5  
238.5  
243.3  
178.3  
184.1  
185.9  
178.6  
184.7  
186.7  
222.8  
237.7  
242.5  
214.0  
220.9  
223.0  
214.4  
221.3  
223.5  
230.4  
242.5  
246.5  
58.6  
58.1  
57.9  
58.9  
58.4  
58.3  
60.6  
60.0  
59.8  
59.5  
58.8  
58.6  
59.5  
58.8  
58.7  
60.6  
60.0  
59.8  
60.3  
59.6  
59.4  
60.4  
59.6  
59.4  
60.8  
60.1  
59.8  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
80  
96  
102  
40  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
32 Ton  
Table PD-16. SCWF/SIWF 32 Gross Cooling Capacity - 12,800 cfm, 96 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
367  
398  
432  
374  
398  
431  
393  
401  
431  
Sensible  
MBh  
317  
246  
175  
Total  
MBh  
352  
382  
415  
361  
382  
415  
380  
386  
414  
Sensible  
MBh  
310  
Total  
MBh  
337  
365  
397  
348  
365  
397  
367  
369  
395  
Sensible  
MBh  
303  
233  
163  
F
F
LWT  
83.9  
84.6  
85.3  
84.1  
84.6  
85.3  
84.5  
84.7  
85.3  
LWT  
93.8  
94.5  
95.2  
94.0  
94.5  
95.2  
94.4  
94.6  
95.2  
LWT  
103.7  
104.3  
105.0  
103.9  
104.3  
105.0  
104.3  
104.4  
105.0  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
240  
169  
372  
360  
348  
80  
85  
313  
307  
300  
241  
236  
229  
393  
380  
367  
377  
370  
361  
308  
302  
296  
Chart PD-35. SCWF/SIWF 32 Fan Performance for CV or with VFD  
Chart PD-36. SCWF/SIWF 32 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to external  
duct static pressure.  
PKG-PRC002-EN  
41  
Performance  
Data  
Water-Cooled  
35 Ton  
Table PD-17. SCWF/SIWF 35 - Economizer Full Capacity - 14,000 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
88  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
335.2  
349.5  
358.9  
425.7  
451.9  
469.1  
544.6  
579.2  
602.1  
370.3  
381.4  
388.6  
432.4  
455.5  
470.9  
543.4  
577.9  
600.6  
422.4  
433.8  
440.9  
451.5  
471.1  
484.1  
544.2  
577.1  
599.3  
309.5  
315.4  
319.4  
260.8  
271.0  
277.9  
216.1  
228.9  
237.4  
362.2  
373.3  
380.5  
333.5  
342.6  
348.7  
286.3  
299.0  
307.6  
422.4  
433.8  
440.9  
410.9  
418.7  
423.9  
357.0  
369.2  
377.5  
52.6  
51.7  
51.0  
54.7  
53.6  
52.9  
57.4  
56.0  
55.1  
53.4  
52.3  
51.5  
54.8  
53.7  
52.9  
57.3  
56.0  
55.1  
54.6  
53.3  
52.4  
55.3  
54.0  
53.1  
57.4  
56.0  
55.1  
212.8  
218.4  
221.9  
246.3  
259.2  
268.1  
354.1  
377.7  
393.3  
265.9  
272.9  
277.3  
272.4  
282.1  
288.7  
353.7  
376.4  
391.9  
319.0  
327.3  
332.5  
319.9  
328.3  
333.5  
365.6  
384.6  
397.7  
212.8  
218.4  
221.9  
194.3  
198.8  
202.0  
149.9  
157.7  
162.9  
265.9  
272.9  
277.3  
263.1  
277.2  
279.6  
220.4  
228.0  
233.1  
319.0  
327.3  
332.5  
319.9  
328.3  
333.5  
294.8  
301.2  
305.6  
59.8  
59.2  
58.7  
60.6  
59.9  
59.5  
63.0  
62.2  
61.6  
61.0  
60.2  
59.7  
61.2  
60.4  
59.9  
63.0  
62.2  
61.6  
62.2  
61.2  
60.6  
62.3  
61.3  
60.6  
63.3  
62.3  
61.7  
62  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
105  
119  
Table PD-18. SCWF/SIWF 35 - Economizer Low Capacity - 14,000 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
88  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
216.3  
224.9  
230.7  
274.3  
290.2  
300.7  
350.3  
371.3  
385.1  
248.2  
255.9  
260.8  
275.7  
290.3  
300.2  
349.6  
370.5  
384.3  
283.7  
292.5  
298.0  
290.3  
302.1  
310.0  
348.9  
369.7  
208.3  
223.6  
225.9  
179.6  
185.6  
189.6  
141.5  
148.9  
153.9  
248.2  
255.9  
260.8  
233.7  
239.2  
243.0  
195.1  
202.4  
207.4  
283.7  
292.5  
298.0  
281.2  
297.2  
300.2  
248.6  
255.9  
49.9  
49.3  
48.9  
51.2  
50.5  
50.1  
53.0  
52.1  
51.5  
50.6  
49.9  
49.4  
51.3  
50.5  
50.0  
52.9  
52.1  
51.5  
51.4  
50.6  
50.0  
51.6  
50.8  
50.2  
52.9  
52.0  
143.3  
147.5  
150.3  
157.0  
164.7  
170.1  
228.0  
241.7  
250.9  
179.2  
184.4  
187.8  
179.5  
184.9  
188.6  
227.3  
241.0  
250.1  
215.0  
221.3  
225.3  
215.4  
221.7  
225.7  
232.4  
243.8  
143.3  
147.5  
150.3  
137.4  
140.1  
142.0  
100.5  
105.0  
107.9  
179.2  
184.4  
187.8  
179.5  
176.3  
179.9  
154.2  
158.6  
161.5  
215.0  
221.3  
225.3  
215.4  
221.7  
225.7  
209.6  
213.2  
58.3  
57.8  
57.5  
58.6  
58.1  
57.9  
60.2  
59.6  
59.2  
59.1  
58.5  
58.2  
59.1  
58.5  
58.2  
60.2  
59.6  
59.2  
59.9  
59.2  
58.8  
59.9  
59.2  
58.8  
60.3  
59.6  
62  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
105  
119  
88  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
105  
42  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
35 Ton  
Table PD-19. SCWF/SIWF 35 Gross Cooling Capacity - 14,000 cfm, 105 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
401  
436  
474  
402  
436  
473  
419  
435  
473  
Sensible  
MBh  
320  
254  
188  
Total  
MBh  
386  
420  
456  
388  
419  
455  
406  
419  
455  
Sensible  
MBh  
313  
Total  
MBh  
369  
402  
437  
373  
402  
436  
392  
402  
436  
Sensible  
MBh  
306  
240  
175  
F
F
LWT  
84.1  
84.8  
85.5  
84.1  
84.8  
85.5  
84.4  
84.8  
85.5  
LWT  
94.0  
94.7  
95.4  
94.0  
94.7  
95.4  
94.4  
94.7  
95.4  
LWT  
103.9  
104.6  
105.3  
104.0  
104.6  
105.3  
104.4  
104.6  
105.2  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
247  
182  
381  
373  
365  
80  
85  
316  
309  
302  
250  
243  
236  
419  
406  
392  
377  
370  
363  
311  
304  
297  
Chart PD-37. SCWF/SIWF 35 Fan Performance for CV or with VFD  
Chart PD-38. SCWF/SIWF 35 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to external  
duct static pressure.  
PKG-PRC002-EN  
43  
Performance  
Data  
Water-Cooled  
38 Ton  
Table PD-20. SCWF/SIWF 38 - Economizer Full Capacity - 15,200 cfm  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
95  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
355.5  
370.6  
374.1  
450.7  
478.7  
485.0  
576.2  
613.4  
621.8  
394.0  
405.8  
408.5  
457.8  
482.4  
488.0  
574.9  
612.0  
620.3  
449.7  
462.2  
464.8  
478.6  
499.4  
504.2  
575.8  
611.1  
619.2  
330.9  
337.2  
338.7  
277.7  
288.7  
291.2  
229.0  
242.7  
245.8  
385.2  
397.1  
399.7  
356.0  
365.7  
367.9  
304.5  
318.2  
321.3  
449.7  
462.2  
464.8  
439.4  
447.7  
449.6  
380.7  
393.6  
396.6  
52.5  
51.5  
51.3  
54.5  
53.4  
53.2  
57.1  
55.8  
55.4  
53.3  
52.1  
51.9  
54.6  
53.5  
53.2  
57.1  
55.7  
55.4  
54.5  
53.1  
52.8  
55.1  
53.8  
53.5  
57.1  
55.7  
55.4  
226.5  
232.7  
234.0  
260.8  
274.4  
277.6  
374.4  
399.7  
405.4  
283.0  
290.7  
292.4  
289.1  
299.5  
301.8  
374.0  
398.4  
404.0  
339.5  
348.7  
350.7  
340.5  
349.7  
351.7  
386.7  
407.1  
411.8  
226.5  
232.7  
234.0  
207.6  
212.4  
213.5  
159.1  
167.5  
169.4  
283.0  
290.7  
292.4  
279.0  
296.9  
297.8  
235.0  
243.1  
245.0  
339.5  
348.7  
350.7  
340.5  
349.7  
351.7  
315.1  
321.9  
323.5  
59.8  
59.1  
58.9  
60.5  
59.8  
59.7  
62.9  
62.0  
61.8  
61.0  
60.1  
59.9  
61.1  
60.3  
60.1  
62.9  
62.0  
61.8  
62.1  
61.1  
60.9  
62.2  
61.1  
60.9  
63.1  
62.1  
61.9  
62  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
114  
119  
Table PD-21. SCWF/SIWF 38 - Economizer Low Capacity - 15,200 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
95  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
228.0  
237.0  
239.0  
288.5  
305.2  
308.9  
368.4  
390.3  
395.3  
262.3  
270.4  
272.2  
290.0  
305.3  
308.8  
367.6  
389.5  
394.5  
299.8  
309.1  
311.1  
305.9  
318.2  
321.0  
366.9  
388.7  
393.6  
219.3  
228.2  
238.1  
190.0  
196.3  
197.7  
149.1  
156.8  
158.6  
262.3  
270.4  
272.2  
247.8  
253.5  
254.8  
206.3  
213.9  
215.7  
299.8  
309.1  
311.1  
296.1  
315.4  
316.5  
263.3  
270.9  
272.7  
49.8  
49.2  
49.0  
51.1  
50.4  
50.2  
52.8  
51.8  
51.6  
50.5  
49.7  
49.6  
51.1  
50.4  
50.2  
52.7  
51.8  
51.6  
51.3  
50.4  
50.2  
51.4  
50.6  
50.4  
52.7  
51.8  
51.6  
151.4  
155.9  
156.9  
165.1  
173.1  
175.0  
239.5  
254.0  
257.3  
189.2  
194.9  
196.1  
189.5  
195.2  
196.5  
238.7  
253.2  
256.4  
227.1  
233.8  
235.3  
227.5  
234.2  
235.7  
244.3  
256.2  
259.0  
151.4  
155.9  
156.9  
145.8  
148.5  
149.2  
106.0  
110.7  
111.8  
189.2  
194.9  
196.1  
189.5  
185.9  
187.2  
163.2  
167.9  
168.9  
227.1  
233.8  
235.3  
227.5  
234.2  
235.7  
222.3  
226.2  
227.1  
58.2  
57.7  
57.6  
58.5  
58.0  
57.9  
60.0  
59.5  
59.3  
59.0  
58.4  
58.3  
59.0  
58.4  
58.3  
60.0  
59.4  
59.3  
59.8  
59.1  
59.0  
59.8  
59.1  
59.0  
60.1  
59.5  
59.4  
62  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
114  
119  
95  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
114  
119  
44  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
38 Ton  
Table PD-22. SCWF/SIWF 38 Gross Cooling Capacity - 15,200 cfm, 114 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
434  
471  
511  
441  
470  
510  
465  
473  
510  
Sensible  
MBh  
373  
290  
206  
Total  
MBh  
416  
452  
490  
426  
452  
490  
450  
455  
489  
Sensible  
MBh  
365  
Total  
MBh  
398  
432  
469  
410  
432  
468  
433  
436  
468  
Sensible  
MBh  
357  
275  
192  
F
F
LWT  
83.9  
84.6  
85.3  
84.1  
84.6  
85.3  
84.5  
84.7  
85.3  
LWT  
93.8  
94.5  
95.2  
94.0  
94.5  
95.2  
94.4  
94.5  
95.2  
LWT  
103.7  
104.3  
105.0  
103.9  
104.3  
105.0  
104.4  
104.4  
105.0  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
283  
199  
441  
426  
410  
80  
85  
369  
361  
353  
285  
277  
270  
465  
444  
363  
450  
435  
355  
433  
425  
348  
Chart PD-39. SCWF/SIWF 38 Fan Performance for CV or with VFD  
Chart PD-40. SCWF/SIWF 38 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
45  
Performance  
Data  
Water-Cooled  
42 Ton  
Table PD-23. SCWF/SIWF 42 - Economizer Full Capacity - 16,800 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
438.5  
457.1  
468.6  
556.7  
591.2  
612.2  
711.9  
757.8  
786.0  
480.2  
494.6  
503.3  
566.9  
597.1  
615.8  
710.3  
756.0  
784.0  
545.5  
559.4  
567.3  
590.8  
616.6  
632.5  
712.7  
756.0  
782.8  
393.8  
401.7  
406.6  
335.0  
348.7  
357.2  
281.0  
297.9  
308.5  
470.5  
484.9  
493.6  
426.2  
438.3  
445.8  
368.9  
386.0  
396.7  
545.5  
559.4  
567.3  
522.7  
533.0  
539.5  
457.3  
473.6  
483.8  
53.4  
52.3  
51.6  
55.6  
54.4  
53.6  
58.6  
57.0  
56.1  
54.1  
52.9  
52.1  
55.8  
54.5  
53.7  
58.5  
57.0  
56.0  
55.4  
53.9  
53.0  
56.3  
54.8  
53.9  
58.6  
57.0  
56.0  
274.5  
281.4  
285.4  
322.8  
339.9  
350.8  
462.2  
494.2  
513.6  
343.0  
351.6  
356.5  
354.9  
367.9  
375.9  
462.7  
493.0  
511.9  
411.4  
421.6  
427.4  
412.7  
423.0  
428.9  
479.1  
504.7  
520.7  
274.5  
281.4  
285.4  
247.5  
253.6  
257.5  
193.6  
204.4  
211.0  
343.0  
351.6  
356.5  
346.2  
350.9  
353.8  
281.8  
291.9  
298.3  
411.4  
421.6  
427.4  
412.7  
423.0  
428.9  
374.9  
383.5  
388.9  
60.2  
59.5  
59.0  
61.1  
60.4  
59.9  
63.8  
62.8  
62.2  
61.5  
60.6  
60.0  
61.8  
60.8  
60.3  
63.8  
62.8  
62.2  
62.8  
61.7  
61.0  
62.9  
61.7  
61.0  
64.1  
63.0  
62.3  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
Table PD-24. SCWF/SIWF 42 - Economizer Low Capacity - 16,800 cfm  
Entering Water Temp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
105  
126  
142  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
291.1  
302.7  
310.0  
368.9  
390.4  
403.6  
471.3  
499.6  
517.1  
331.6  
341.5  
347.4  
566.9  
391.2  
403.5  
470.3  
498.5  
515.9  
379.0  
390.3  
397.0  
390.9  
406.8  
416.8  
469.3  
497.4  
514.8  
290.3  
295.0  
298.0  
238.2  
246.4  
251.5  
189.6  
199.7  
206.0  
331.6  
341.5  
347.4  
426.2  
316.4  
321.1  
259.3  
269.3  
275.6  
379.0  
390.3  
397.0  
385.8  
392.0  
395.8  
328.9  
338.8  
345.1  
50.5  
49.8  
49.4  
52.0  
51.2  
50.7  
54.0  
52.9  
52.3  
51.3  
50.4  
49.9  
55.8  
51.2  
50.7  
54.0  
52.9  
52.3  
52.2  
51.2  
50.6  
52.4  
51.5  
50.9  
53.9  
52.9  
52.3  
191.1  
196.7  
200.0  
211.6  
221.9  
228.7  
306.1  
325.0  
336.6  
238.9  
245.9  
250.0  
354.9  
247.4  
252.1  
305.1  
323.9  
335.5  
286.7  
295.0  
299.9  
287.3  
295.6  
300.5  
313.2  
328.7  
338.5  
191.1  
196.7  
200.0  
181.4  
184.9  
187.3  
133.9  
140.0  
143.8  
238.9  
245.9  
250.0  
346.2  
236.8  
241.5  
203.7  
209.7  
213.5  
286.7  
295.0  
299.9  
287.3  
295.6  
300.5  
276.2  
281.3  
284.5  
58.6  
58.1  
57.8  
59.0  
58.5  
58.2  
60.8  
60.2  
59.7  
59.6  
58.9  
58.5  
61.8  
58.9  
58.6  
60.8  
60.1  
59.7  
60.5  
59.7  
59.2  
60.5  
59.7  
59.2  
61.0  
60.2  
59.8  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
46  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
42 Ton  
Table PD-25. SCWF/SIWF 42 Gross Cooling Capacity - 16,800 cfm, 126 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
488  
530  
576  
493  
530  
576  
513  
532  
575  
Sensible  
MBh  
403  
317  
Total  
MBh  
469  
510  
554  
476  
510  
554  
496  
512  
553  
Sensible  
MBh  
394  
Total  
MBh  
449  
488  
531  
458  
488  
530  
479  
491  
530  
Sensible  
MBh  
385  
300  
215  
F
F
LWT  
84.1  
84.9  
85.6  
84.3  
84.9  
85.6  
84.6  
84.9  
85.6  
LWT  
94.1  
94.7  
95.5  
94.2  
94.7  
95.5  
94.5  
94.8  
95.5  
LWT  
104.0  
104.6  
105.3  
104.1  
104.6  
105.3  
104.5  
104.6  
105.3  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
309  
231  
223  
473  
460  
445  
80  
85  
397  
389  
380  
311  
303  
295  
512  
496  
479  
476  
467  
456  
391  
383  
375  
Chart PD-41. SCWF/SIWF 42 Fan Performance for CV or with VFD  
Chart PD-42. SCWF/SIWF 42 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to external  
duct static pressure.  
PKG-PRC002-EN  
47  
Performance  
Data  
Water-Cooled  
46 Ton  
Table PD-26. SCWF/SIWF 46 - Economizer Full Capacity - 18,400 cfm  
EnteringWaterTemp  
Entering Air  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
EDB  
F
EWB  
F
Flow  
gpm  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
469.0  
488.5  
491.5  
594.6  
630.9  
636.3  
760.7  
808.6  
815.8  
515.3  
530.5  
532.7  
605.5  
637.2  
642.0  
759.0  
806.6  
813.8  
586.3  
601.2  
603.4  
631.8  
658.8  
662.8  
761.0  
806.5  
813.3  
425.0  
433.3  
434.5  
360.1  
374.4  
376.6  
300.9  
318.4  
321.1  
504.7  
519.8  
522.0  
459.2  
471.8  
473.7  
396.1  
413.9  
416.6  
586.3  
601.2  
603.4  
564.1  
574.9  
576.6  
492.1  
509.1  
511.6  
53.2  
52.1  
51.9  
55.3  
54.1  
54.0  
58.2  
56.7  
56.5  
54.0  
52.7  
52.5  
55.5  
54.2  
54.0  
58.2  
56.7  
56.5  
55.2  
53.7  
53.5  
56.0  
54.5  
54.3  
58.2  
56.7  
56.5  
295.0  
302.5  
303.5  
344.7  
362.5  
365.3  
493.5  
526.8  
531.8  
368.6  
377.9  
379.2  
380.0  
393.5  
395.6  
493.9  
525.5  
530.3  
442.1  
453.1  
454.7  
443.5  
454.6  
456.2  
511.5  
538.2  
542.2  
295.0  
302.5  
303.5  
266.9  
273.2  
274.2  
207.5  
218.7  
220.3  
368.6  
377.9  
379.2  
374.4  
379.2  
380.0  
303.3  
313.9  
315.5  
442.1  
453.1  
454.7  
443.5  
454.6  
456.2  
404.5  
413.4  
414.8  
60.1  
59.4  
59.3  
61.0  
60.3  
60.1  
63.6  
62.6  
62.5  
61.4  
60.5  
60.3  
61.6  
60.7  
60.6  
63.6  
62.6  
62.5  
62.7  
61.6  
61.4  
62.7  
61.6  
61.4  
63.9  
62.8  
62.6  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
80  
85  
Table PD-27. SCWF/SIWF 46 - Economizer Low Capacity - 18,400 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB Water Flow  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
gpm  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
115  
138  
142  
309.1  
321.0  
322.8  
390.9  
413.0  
416.4  
499.2  
528.4  
532.8  
353.2  
363.6  
365.1  
394.0  
413.9  
417.0  
498.1  
527.3  
531.6  
403.6  
415.5  
417.2  
414.9  
431.2  
433.7  
497.1  
526.1  
530.5  
298.4  
315.6  
316.3  
254.1  
262.5  
263.8  
201.2  
211.6  
213.1  
353.2  
363.6  
365.1  
330.3  
337.9  
339.1  
276.3  
286.6  
288.1  
403.6  
415.5  
417.2  
413.1  
419.4  
420.3  
351.2  
361.4  
363.0  
50.4  
49.7  
49.5  
51.8  
51.0  
50.9  
53.7  
52.7  
52.5  
51.1  
50.3  
50.1  
51.9  
51.0  
50.9  
53.7  
52.6  
52.5  
52.0  
51.0  
50.9  
52.2  
51.2  
51.1  
53.6  
52.6  
52.5  
203.6  
209.4  
210.3  
224.1  
234.6  
236.3  
324.1  
343.5  
346.4  
254.4  
261.7  
262.8  
255.0  
262.9  
264.1  
323.0  
342.3  
345.2  
305.3  
314.0  
315.3  
305.9  
314.6  
315.9  
331.7  
347.6  
350.0  
203.6  
209.4  
210.3  
194.0  
197.6  
198.2  
142.3  
148.6  
149.6  
254.4  
261.7  
262.8  
243.6  
251.4  
252.5  
217.5  
223.7  
224.7  
305.3  
314.0  
315.3  
305.9  
314.6  
315.9  
295.6  
300.7  
301.5  
58.5  
58.0  
58.0  
58.9  
58.4  
58.3  
60.6  
60.0  
59.9  
59.4  
58.8  
58.7  
59.4  
58.8  
58.7  
60.6  
60.0  
59.9  
60.3  
59.6  
59.4  
60.3  
59.6  
59.4  
60.8  
60.0  
59.9  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
48  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
46 Ton  
Table PD-28. SCWF/SIWF 46 Gross Cooling Capacity - 18,400 cfm, 138 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
517  
561  
609  
530  
562  
609  
556  
567  
609  
Sensible  
MBh  
449  
348  
248  
Total  
MBh  
498  
540  
586  
511  
539  
586  
538  
546  
585  
Sensible  
MBh  
439  
340  
239  
Total  
MBh  
476  
516  
561  
491  
516  
560  
518  
524  
559  
Sensible  
MBh  
429  
331  
231  
F
F
LWT  
83.8  
84.4  
85.1  
84.0  
84.4  
85.1  
84.4  
84.5  
85.1  
LWT  
93.6  
94.3  
95.0  
93.9  
94.3  
95.0  
94.3  
94.4  
95.0  
LWT  
103.5  
104.1  
104.8  
103.8  
104.1  
104.8  
104.2  
104.3  
104.5  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
520  
505  
488  
80  
85  
444  
435  
425  
343  
334  
325  
556  
538  
518  
533  
521  
505  
437  
428  
420  
Chart PD-43. SCWF/SIWF 46 Fan Performance for CV or with VFD  
Chart PD-44. SCWF/SIWF 46 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
49  
Performance  
Data  
Water-Cooled  
52 Ton  
Table PD-29. SCWF/SIWF 52 - Economizer Full Capacity - 20,800 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
546.6  
570.0  
588.4  
694.3  
737.5  
771.2  
887.8  
945.5  
990.6  
598.2  
616.2  
630.1  
707.0  
744.9  
774.8  
885.8  
943.2  
988.1  
679.1  
696.3  
708.9  
736.6  
769.0  
794.5  
888.9  
943.3  
986.2  
489.7  
499.6  
507.5  
417.0  
434.2  
447.8  
350.3  
371.6  
388.5  
586.1  
604.1  
618.1  
530.2  
545.4  
557.5  
459.3  
480.9  
498.1  
679.1  
696.3  
708.9  
649.9  
662.9  
673.3  
569.1  
589.5  
606.0  
53.4  
52.3  
51.5  
55.7  
54.5  
53.5  
58.7  
57.1  
55.9  
54.2  
52.9  
51.9  
55.9  
54.5  
53.5  
58.6  
57.1  
55.9  
55.4  
53.9  
52.8  
56.3  
54.9  
53.7  
58.7  
57.1  
55.8  
341.8  
350.4  
356.6  
402.7  
424.2  
441.7  
576.6  
616.7  
647.8  
427.0  
437.6  
445.4  
442.3  
458.6  
471.5  
577.3  
615.2  
645.6  
512.1  
524.8  
534.0  
513.8  
526.6  
535.8  
597.7  
629.7  
655.5  
341.8  
350.4  
356.6  
307.8  
315.4  
321.7  
241.3  
254.8  
265.4  
427.0  
437.6  
445.4  
430.2  
436.1  
440.8  
350.6  
363.4  
373.7  
512.1  
524.8  
534.0  
513.8  
526.6  
535.8  
466.2  
477.0  
485.8  
60.3  
59.5  
58.9  
61.2  
60.4  
59.9  
63.9  
62.9  
62.1  
61.6  
60.6  
59.9  
61.8  
60.9  
60.2  
63.9  
62.9  
62.1  
62.9  
61.7  
60.9  
62.9  
61.8  
60.9  
64.2  
63.1  
62.2  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
Table PD-30. SCWF/SIWF 52 - Economizer Low Capacity - 20,800 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
130  
156  
182  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
363.7  
378.3  
390.1  
461.2  
488.3  
509.6  
589.2  
625.0  
653.2  
413.9  
426.4  
435.8  
464.9  
489.3  
509.2  
588.0  
623.6  
651.7  
473.1  
487.2  
497.9  
488.4  
508.5  
524.8  
586.7  
622.2  
650.2  
361.8  
367.7  
372.6  
297.3  
307.6  
315.8  
236.9  
249.6  
259.8  
413.9  
426.4  
435.8  
385.4  
394.7  
402.3  
323.6  
336.3  
346.4  
473.1  
487.2  
497.9  
480.9  
488.6  
494.9  
410.2  
422.8  
432.9  
50.6  
49.9  
49.3  
52.1  
51.3  
50.6  
54.1  
53.0  
52.2  
51.4  
50.5  
49.8  
52.2  
51.3  
50.6  
54.0  
53.0  
52.2  
52.3  
51.2  
50.5  
52.5  
51.5  
50.8  
54.0  
53.0  
52.1  
238.6  
245.6  
250.9  
264.6  
277.6  
288.6  
382.8  
406.6  
425.4  
298.2  
306.9  
313.5  
299.4  
309.0  
316.7  
381.6  
405.2  
423.9  
357.9  
368.3  
376.1  
358.6  
369.0  
376.9  
391.6  
411.1  
427.1  
238.6  
245.6  
250.9  
226.1  
230.6  
234.5  
167.2  
174.9  
181.1  
298.2  
306.9  
313.5  
286.4  
295.9  
303.6  
254.0  
261.7  
267.8  
357.9  
368.3  
376.1  
358.6  
369.0  
376.9  
344.3  
350.7  
355.9  
58.7  
58.1  
57.8  
59.1  
58.6  
58.2  
60.9  
60.2  
59.7  
59.6  
58.9  
58.4  
59.6  
59.0  
58.5  
60.9  
60.2  
59.7  
60.5  
59.7  
59.1  
60.5  
59.7  
59.1  
61.0  
60.3  
59.7  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
50  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
52 Ton  
Table PD-31. SCWF/SIWF 52 Gross Cooling Capacity - 20,800 cfm, 156 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
596  
650  
707  
598  
649  
706  
616  
649  
705  
Sensible  
MBh  
471  
376  
280  
Total  
MBh  
575  
626  
681  
577  
626  
680  
598  
625  
680  
Sensible  
MBh  
461  
Total  
MBh  
551  
601  
654  
555  
600  
653  
579  
601  
653  
Sensible  
MBh  
450  
356  
261  
F
F
LWT  
84.1  
84.8  
85.5  
84.1  
84.8  
85.5  
84.3  
84.8  
85.5  
LWT  
94.0  
94.7  
95.4  
94.0  
94.7  
95.4  
94.3  
94.7  
95.4  
LWT  
103.9  
104.6  
105.3  
104.0  
104.6  
105.3  
104.3  
104.6  
105.3  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
366  
271  
559  
548  
535  
80  
85  
465  
455  
445  
369  
360  
350  
616  
598  
579  
554  
544  
533  
458  
448  
438  
Chart PD-45. SCWF/SIWF 52 Fan Performance for CV or with VFD  
Chart PD-46. SCWF/SIWF 52 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
51  
Performance  
Data  
Water-Cooled  
58 Ton  
Table PD-32. SCWF/SIWF 58 - Economizer Full Capacity - 23,200 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
592.9  
617.6  
626.2  
751.8  
797.7  
813.5  
961.6  
1022.3  
1043.5  
651.2  
670.3  
676.9  
765.5  
805.6  
819.6  
959.5  
1019.8  
1040.9  
740.7  
759.6  
765.8  
798.6  
832.8  
844.7  
962.1  
1019.7  
1039.8  
536.8  
547.2  
550.8  
454.9  
473.1  
479.4  
380.3  
402.5  
410.3  
637.7  
656.9  
663.4  
580.0  
595.9  
601.5  
500.5  
523.0  
531.0  
740.7  
759.6  
765.8  
712.4  
726.1  
730.9  
621.6  
643.1  
650.7  
53.2  
52.1  
51.7  
55.4  
54.2  
53.7  
58.3  
56.8  
56.2  
54.0  
52.7  
52.3  
55.6  
54.3  
53.8  
58.2  
56.7  
56.2  
55.2  
53.7  
53.2  
56.0  
54.6  
54.1  
58.3  
56.7  
56.2  
372.8  
382.2  
385.2  
435.8  
458.4  
466.5  
623.9  
666.1  
680.7  
465.7  
477.4  
481.2  
480.3  
497.4  
503.4  
624.4  
664.5  
678.6  
558.6  
572.5  
577.0  
560.3  
574.3  
578.9  
646.7  
680.5  
692.4  
372.8  
382.2  
385.2  
337.1  
345.1  
348.0  
262.3  
276.4  
281.3  
465.7  
477.4  
481.2  
472.7  
478.9  
481.0  
383.1  
396.5  
401.3  
558.6  
572.5  
577.0  
560.3  
574.3  
578.9  
510.8  
522.2  
526.2  
60.1  
59.4  
59.1  
61.0  
60.3  
60.0  
63.6  
62.7  
62.3  
61.4  
60.5  
60.2  
61.6  
60.7  
60.4  
63.6  
62.6  
62.3  
62.7  
61.6  
61.2  
62.7  
61.6  
61.2  
63.9  
62.8  
62.4  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
Table PD-33. SCWFSIWF 58 - Economizer Low Capacity - 23,200 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
145  
174  
186  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
391.0  
406.1  
411.4  
494.5  
522.7  
532.4  
631.6  
668.7  
681.6  
446.6  
459.8  
464.3  
498.5  
523.8  
532.8  
630.3  
667.3  
680.1  
510.4  
525.4  
530.5  
524.8  
545.5  
552.8  
628.9  
665.8  
678.6  
377.5  
398.9  
401.1  
321.3  
331.9  
335.7  
254.6  
267.7  
272.3  
446.6  
459.8  
464.3  
417.6  
427.2  
430.6  
349.4  
362.4  
367.0  
510.4  
525.4  
530.5  
522.1  
530.1  
532.9  
444.0  
457.0  
461.5  
50.4  
49.7  
49.4  
51.8  
51.0  
50.7  
53.7  
52.7  
52.3  
51.2  
50.3  
50.0  
51.9  
51.0  
50.7  
53.7  
52.7  
52.3  
52.0  
51.0  
50.7  
52.2  
51.3  
50.9  
53.7  
52.7  
52.3  
257.4  
264.8  
267.3  
283.6  
296.9  
301.9  
410.1  
434.7  
443.2  
321.8  
331.0  
334.1  
322.6  
332.5  
336.0  
408.7  
433.2  
441.8  
386.1  
397.1  
400.8  
386.8  
397.9  
401.6  
419.7  
439.8  
447.0  
257.4  
264.8  
267.3  
245.2  
249.8  
251.5  
180.0  
188.0  
190.8  
321.8  
331.0  
334.1  
308.1  
318.0  
321.4  
275.0  
282.9  
285.6  
386.1  
397.1  
400.8  
386.8  
397.9  
401.6  
373.6  
380.2  
382.5  
58.6  
58.0  
57.9  
58.9  
58.4  
58.2  
60.7  
60.0  
59.8  
59.4  
58.8  
58.6  
59.4  
58.8  
58.6  
60.6  
60.0  
59.8  
60.3  
59.6  
59.3  
60.3  
59.6  
59.3  
60.8  
60.1  
59.8  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
52  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
58 Ton  
Table PD-34. SCWF/SIWF 58 Gross Cooling Capacity - 23,200 cfm, 174 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
663  
720  
782  
675  
720  
781  
712  
725  
781  
Sensible  
MBh  
571  
Total  
MBh  
637  
692  
751  
653  
692  
751  
689  
698  
750  
Sensible  
MBh  
559  
Total  
MBh  
610  
662  
719  
629  
662  
719  
665  
669  
718  
Sensible  
MBh  
547  
F
F
LWT  
83.9  
84.6  
85.3  
84.1  
84.6  
85.3  
84.5  
84.6  
85.3  
LWT  
93.8  
94.4  
95.2  
94.0  
94.4  
95.2  
94.4  
94.5  
95.1  
LWT  
103.7  
104.3  
105.0  
103.9  
104.3  
105.0  
104.3  
104.4  
105.0  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
444  
433  
421  
316  
306  
294  
674  
653  
629  
80  
85  
564  
553  
541  
436  
425  
414  
712  
689  
665  
679  
666  
652  
555  
545  
533  
Chart PD-47. SCWF/SIWF 58 Fan Performance for CV or with VFD  
Chart PD-48. SCWF/SIWF 58 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used with  
these curves, add filter, economizer, flexible horizontal  
discharge and heat pressure drops to external duct static  
pressure.  
PKG-PRC002-EN  
53  
Performance  
Data  
Water-Cooled  
65 Ton  
Table PD-35. SCWF/SIWF 65 - Economizer Full Capacity - 26,000 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
644.4  
670.0  
689.7  
815.9  
863.7  
899.9  
1043.3  
1106.7  
1155.0  
710.6  
730.5  
745.5  
830.6  
872.3  
904.5  
1041.0  
1104.0  
1152.2  
809.6  
829.9  
844.4  
867.7  
903.1  
930.4  
1043.6  
1103.6  
1149.9  
590.0  
600.7  
609.0  
497.6  
516.4  
530.8  
413.8  
436.7  
454.5  
695.5  
715.4  
730.4  
636.1  
652.6  
665.4  
546.6  
569.9  
588.1  
809.6  
829.9  
844.4  
783.1  
797.2  
808.2  
680.9  
703.1  
720.5  
52.9  
51.9  
51.1  
55.0  
53.9  
53.0  
57.8  
56.4  
55.2  
53.7  
52.5  
51.6  
55.2  
53.9  
53.0  
57.8  
56.3  
55.2  
54.9  
53.5  
52.5  
55.6  
54.3  
53.2  
57.8  
56.3  
55.2  
407.4  
417.5  
424.7  
472.6  
495.9  
514.5  
676.7  
720.4  
753.5  
509.0  
521.6  
530.5  
522.6  
540.3  
553.9  
676.9  
718.5  
750.9  
610.6  
625.5  
636.1  
612.4  
627.4  
638.2  
701.3  
736.1  
763.4  
407.4  
417.5  
424.7  
370.1  
378.4  
385.0  
285.8  
300.4  
311.5  
509.0  
521.6  
530.5  
520.8  
527.1  
532.0  
419.8  
433.6  
444.5  
610.6  
625.5  
636.1  
612.4  
627.4  
638.2  
561.3  
573.0  
582.1  
60.0  
59.3  
58.8  
60.8  
60.1  
59.6  
63.3  
62.4  
61.7  
61.2  
60.3  
59.7  
61.4  
60.5  
59.9  
63.3  
62.4  
61.6  
62.5  
61.4  
60.6  
62.5  
61.4  
60.6  
63.6  
62.5  
61.8  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
Table PD-36. SCWF/SIWF 65 - Economizer Low Capacity - 26,000 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
163  
195  
226  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
420.9  
436.1  
448.0  
531.1  
559.7  
581.7  
678.2  
715.9  
744.8  
482.5  
496.2  
506.4  
535.3  
561.0  
581.3  
676.7  
714.3  
743.2  
551.5  
567.1  
578.6  
564.7  
585.6  
602.0  
675.3  
712.8  
741.5  
405.9  
433.3  
438.2  
347.9  
358.7  
367.0  
274.0  
287.3  
297.6  
482.5  
496.2  
506.4  
453.2  
463.0  
470.7  
377.8  
391.0  
401.3  
551.5  
567.1  
578.6  
547.6  
575.9  
582.2  
481.4  
494.6  
504.8  
50.2  
49.5  
49.0  
51.5  
50.7  
50.1  
53.3  
52.3  
51.6  
50.9  
50.1  
49.5  
51.6  
50.8  
50.1  
53.3  
52.3  
51.6  
51.8  
50.8  
50.1  
51.9  
51.0  
50.3  
53.3  
52.3  
51.6  
278.1  
285.8  
291.4  
304.3  
317.8  
329.0  
440.0  
464.9  
484.1  
347.6  
357.2  
364.2  
348.2  
358.2  
365.8  
438.6  
463.4  
482.5  
417.1  
428.5  
436.9  
417.9  
429.3  
437.7  
450.5  
470.8  
486.9  
278.1  
285.8  
291.4  
266.3  
271.0  
274.9  
194.2  
202.3  
208.5  
347.6  
357.2  
364.2  
348.2  
342.1  
349.7  
298.1  
306.1  
312.3  
417.1  
428.5  
436.9  
417.9  
429.3  
437.7  
406.1  
412.7  
417.9  
58.4  
57.9  
57.6  
58.7  
58.3  
57.9  
60.4  
59.8  
59.3  
59.3  
58.7  
58.2  
59.3  
58.7  
58.2  
60.4  
59.8  
59.3  
60.1  
59.4  
58.9  
60.1  
59.4  
58.9  
60.5  
59.8  
59.3  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
54  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
65 Ton  
Table PD-37. SCWF/SIWF 65 Gross Cooling Capacity - 26,000 cfm, 196 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
744  
809  
879  
749  
809  
878  
780  
809  
877  
Sensible  
MBh  
609  
480  
351  
Total  
MBh  
715  
779  
845  
722  
778  
844  
756  
779  
844  
Sensible  
MBh  
597  
Total  
MBh  
686  
746  
810  
694  
746  
810  
730  
747  
808  
Sensible  
MBh  
583  
455  
326  
F
F
LWT  
84.1  
84.8  
85.5  
84.1  
84.8  
85.5  
84.5  
84.8  
85.5  
LWT  
93.9  
94.6  
95.4  
94.0  
94.6  
95.4  
94.4  
94.6  
95.4  
LWT  
103.8  
104.5  
105.2  
104.0  
104.5  
105.2  
104.4  
104.5  
105.2  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
468  
338  
726  
711  
692  
80  
85  
601  
589  
576  
471  
459  
447  
780  
756  
730  
721  
708  
695  
592  
579  
567  
Chart PD-49. SCWF/SIWF 65 Fan Performance for CV or with VFD  
Chart PD-50. SCWF/SIWF 65 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
55  
Performance  
Data  
Water-Cooled  
72 Ton  
Table PD-38. SCWF/SIWF 72 - Economizer Full Capacity - 28,000 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
692.2  
719.4  
725.9  
874.7  
925.8  
937.7  
1117.6  
1185.9  
1201.8  
766.5  
787.8  
792.8  
890.5  
934.9  
945.5  
1114.9  
1183.0  
1198.9  
874.4  
896.7  
901.7  
931.6  
969.2  
978.2  
1118.3  
1182.3  
1197.5  
640.9  
652.3  
655.0  
537.8  
557.8  
562.5  
443.9  
469.3  
475.0  
749.8  
771.1  
776.1  
689.6  
707.0  
711.2  
589.6  
614.7  
620.6  
874.4  
896.7  
901.7  
850.8  
865.7  
869.3  
737.1  
760.6  
766.2  
52.7  
51.7  
51.4  
54.7  
53.6  
53.3  
57.4  
56.0  
55.6  
53.5  
52.3  
52.0  
54.9  
53.7  
53.4  
57.4  
56.0  
55.6  
54.7  
53.3  
53.0  
55.4  
54.0  
53.7  
57.4  
55.9  
55.6  
440.0  
451.1  
453.6  
506.6  
531.1  
537.2  
724.9  
771.3  
782.2  
549.8  
563.5  
566.6  
562.1  
580.8  
585.3  
724.9  
769.1  
779.7  
659.4  
675.8  
679.5  
661.3  
677.8  
681.6  
751.4  
788.3  
797.1  
440.0  
451.1  
453.6  
401.7  
410.4  
412.5  
307.7  
323.1  
326.7  
549.8  
563.5  
566.6  
542.9  
573.8  
575.4  
454.5  
469.2  
472.7  
659.4  
675.8  
679.5  
661.3  
677.8  
681.6  
609.6  
621.9  
624.8  
59.9  
59.2  
59.0  
60.6  
59.9  
59.8  
63.1  
62.1  
61.9  
61.1  
60.2  
60.0  
61.2  
60.4  
60.2  
63.1  
62.1  
61.9  
62.3  
61.3  
61.0  
62.3  
61.3  
61.0  
63.3  
62.3  
62.1  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
Table PD-39. SCWF/SIWF 72 - Economizer Low Capacity - 28,000 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
180  
216  
226  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
448.3  
464.1  
467.9  
564.0  
593.9  
601.0  
720.0  
759.4  
768.7  
515.6  
530.2  
533.5  
568.5  
595.3  
601.8  
718.5  
757.7  
767.0  
589.3  
605.9  
609.7  
601.1  
622.8  
628.0  
716.9  
756.1  
765.4  
431.7  
447.5  
467.4  
372.5  
383.7  
386.4  
291.7  
305.5  
308.8  
515.6  
530.2  
533.5  
486.6  
496.7  
499.1  
404.1  
417.8  
421.1  
589.3  
605.9  
609.7  
582.4  
619.2  
621.2  
516.2  
529.9  
533.2  
50.0  
49.3  
49.1  
51.3  
50.5  
50.3  
53.0  
52.0  
51.8  
50.7  
49.9  
49.7  
51.3  
50.5  
50.3  
53.0  
52.0  
51.8  
51.5  
50.6  
50.4  
51.7  
50.8  
50.6  
53.0  
52.0  
51.8  
297.1  
305.3  
307.1  
323.1  
337.1  
340.6  
466.8  
492.8  
499.0  
371.4  
381.5  
383.9  
372.0  
382.2  
384.7  
465.3  
491.2  
497.3  
445.6  
457.8  
460.6  
446.4  
458.6  
461.4  
478.3  
499.3  
504.4  
297.1  
305.3  
307.1  
286.1  
291.0  
292.2  
207.2  
215.6  
217.5  
371.4  
381.5  
383.9  
372.0  
364.5  
366.9  
319.7  
328.0  
330.0  
445.6  
457.8  
460.6  
446.4  
458.6  
461.4  
436.6  
443.4  
445.1  
58.3  
57.8  
57.7  
58.6  
58.1  
58.0  
60.2  
59.6  
59.4  
59.1  
58.5  
58.4  
59.1  
58.5  
58.4  
60.2  
59.5  
59.4  
60.0  
59.2  
59.1  
60.0  
59.2  
59.1  
60.3  
59.6  
59.5  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
56  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
72 Ton  
Table PD-40. SCWF/SIWF 72 Gross Cooling Capacity - 28,800 cfm, 216 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
799  
868  
941  
814  
868  
941  
859  
874  
940  
Sensible  
MBh  
690  
Total  
MBh  
768  
834  
905  
787  
833  
904  
832  
841  
904  
Sensible  
MBh  
675  
Total  
MBh  
735  
798  
866  
758  
798  
866  
802  
807  
865  
Sensible  
MBh  
660  
F
F
LWT  
83.7  
84.3  
85.0  
83.8  
84.3  
85.0  
84.2  
84.4  
85.0  
LWT  
93.6  
94.2  
94.9  
93.7  
94.2  
94.8  
94.2  
94.3  
94.8  
LWT  
103.4  
104.0  
104.7  
103.7  
104.0  
104.7  
104.1  
104.1  
104.7  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
536  
522  
509  
381  
368  
355  
812  
788  
758  
80  
85  
681  
668  
653  
526  
514  
500  
859  
832  
802  
819  
803  
786  
670  
658  
644  
Chart PD-51. SCWF/SIWF 72 Fan Performance for CV or with VFD  
Chart PD-52. SCWF/SIWF 72 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
57  
Performance  
Data  
Water-Cooled  
80 Ton  
Table PD-41. SCWF/SIWF 80 - Economizer Full Capacity - 29,800 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
Total  
MBh  
719.8  
746.6  
751.3  
915.9  
966.0  
974.5  
1171.5  
1238.3  
1249.7  
794.7  
LWT  
F
Total  
MBh  
LWT  
F
F
F
663.3  
674.5  
676.5  
559.9  
579.6  
583.0  
464.7  
489.6  
493.8  
777.5  
798.2  
801.7  
715.3  
732.5  
735.5  
614.9  
639.5  
643.7  
906.2  
927.8  
931.3  
880.5  
895.3  
897.8  
766.1  
789.5  
793.5  
52.2  
51.2  
51.1  
54.2  
53.1  
52.9  
56.7  
55.3  
55.1  
52.9  
51.8  
51.6  
54.3  
53.1  
52.9  
56.7  
55.3  
55.1  
54.1  
52.7  
52.5  
54.7  
53.4  
53.2  
56.7  
55.3  
55.0  
456.0  
466.7  
468.4  
527.8  
552.8  
557.1  
760.6  
805.9  
813.6  
569.7  
583.0  
585.1  
583.4  
601.8  
605.0  
759.4  
803.2  
810.8  
683.3  
699.1  
701.7  
685.2  
701.2  
703.8  
783.6  
820.2  
826.5  
456.0  
466.7  
468.4  
416.0  
424.9  
426.4  
321.6  
336.7  
339.3  
569.7  
583.0  
585.1  
563.2  
592.6  
593.8  
472.5  
487.1  
489.6  
683.3  
699.1  
701.7  
685.2  
701.2  
703.8  
631.4  
643.6  
645.7  
59.6  
58.9  
58.8  
60.3  
59.6  
59.5  
62.6  
61.7  
61.6  
60.7  
59.9  
59.7  
60.8  
60.0  
59.9  
62.6  
61.7  
61.5  
61.8  
60.8  
60.7  
61.9  
60.8  
60.7  
62.8  
61.8  
61.7  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
815.5  
819.0  
929.2  
973.1  
80  
85  
980.7  
1168.7  
1235.3  
1246.6  
906.2  
927.8  
931.3  
969.0  
1006.1  
1012.5  
1170.1  
1233.4  
1244.3  
Table PD-42. SCWF/SIWF 80 - Economizer Low Capacity - 29,800 cfm  
Entering WaterTemp  
Entering Air  
EDB EWB  
45 F  
Sensible  
MBh  
55 F  
Sensible  
MBh  
Flow  
gpm  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
200  
240  
248  
Total  
MBh  
LWT  
F
Total  
MBh  
LWT  
F
F
F
464.0  
479.5  
482.2  
587.4  
616.7  
621.7  
750.3  
788.8  
795.4  
533.0  
547.1  
549.4  
590.6  
617.2  
621.8  
748.7  
787.1  
793.7  
609.1  
625.1  
627.8  
622.3  
643.6  
647.3  
747.1  
785.4  
791.9  
446.9  
462.3  
480.6  
385.5  
396.5  
398.4  
303.3  
316.9  
319.2  
533.0  
547.1  
549.4  
502.1  
512.1  
513.9  
418.7  
432.2  
434.5  
609.1  
625.1  
627.8  
602.9  
637.3  
638.7  
533.8  
547.2  
549.5  
49.6  
49.0  
48.9  
50.9  
50.1  
50.0  
52.5  
51.6  
51.4  
50.3  
49.6  
49.4  
50.9  
50.1  
50.0  
52.5  
51.6  
51.4  
51.1  
50.2  
50.1  
51.2  
50.4  
50.2  
52.5  
51.5  
51.4  
307.0  
314.9  
316.2  
334.7  
349.2  
351.7  
486.5  
511.9  
516.3  
383.7  
393.5  
395.2  
384.4  
394.3  
396.0  
484.9  
510.2  
514.6  
460.4  
472.2  
474.1  
461.2  
473.0  
475.0  
496.6  
517.0  
520.6  
307.0  
314.9  
316.2  
294.7  
299.7  
300.6  
215.0  
223.2  
224.6  
383.7  
393.5  
395.2  
384.4  
375.9  
377.7  
330.5  
338.7  
340.1  
460.4  
472.2  
474.1  
461.2  
473.0  
475.0  
450.0  
456.6  
457.8  
58.1  
57.6  
57.6  
58.3  
57.9  
57.8  
59.9  
59.3  
59.2  
58.8  
58.3  
58.2  
58.8  
58.3  
58.2  
59.8  
59.3  
59.1  
59.6  
58.9  
58.8  
59.6  
58.9  
58.8  
60.0  
59.3  
59.2  
62  
75  
67  
72  
62  
67  
72  
62  
67  
72  
80  
85  
58  
PKG-PRC002-EN  
Performance  
Data  
Water-Cooled  
80 Ton  
Table PD-43. SCWF/SIWF 80 Gross Cooling Capacity - 29,800 cfm, 240 gpm  
Entering Water Temp  
Entering Air  
EDB EWB  
75 F  
85 F  
95 F  
Total  
MBh  
891  
Sensible  
MBh  
761  
Total  
MBh  
856  
Sensible  
MBh  
746  
Total  
MBh  
819  
887  
963  
847  
888  
963  
896  
899  
963  
Sensible  
MBh  
729  
F
F
LWT  
83.7  
84.3  
85.0  
83.8  
84.3  
85.0  
84.3  
84.4  
85.0  
LWT  
93.6  
94.2  
94.8  
93.8  
94.2  
94.8  
94.2  
94.3  
94.8  
LWT  
103.4  
104.0  
104.7  
103.7  
104.0  
104.7  
104.1  
104.1  
104.7  
62  
67  
72  
62  
67  
72  
62  
67  
72  
75  
966  
590  
928  
575  
559  
1049  
910  
419  
1007  
880  
405  
389  
896  
867  
834  
80  
85  
967  
752  
929  
737  
721  
1048  
961  
579  
1006  
930  
565  
550  
947  
916  
883  
975  
908  
938  
890  
871  
1047  
740  
1006  
725  
710  
Chart PD-53. SCWF/SIWF 80 Fan Performance for CV or with VFD  
Chart PD-54. SCWF/SIWF 80 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
59  
Performance  
Data  
Air-Cooled  
20 Ton  
Table PD-44. SCRF/SIRF 20 Gross Cooling Capacity - 10,000 cfm -Air Cooled  
Entering Ambient Air Temperature  
75 F  
Tot  
MBh  
85 F  
95 F  
105 F  
115 F  
EDB EWB  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
MBh  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
Sen  
F
F
MBh  
186.6  
135.2  
235.9  
184.3  
132.5  
280.6  
233.2  
181.3  
298.2  
281.1  
229.9  
MBh  
MBh  
242.6  
265.1  
243.4  
264.9  
288.7  
252.7  
264.8  
288.4  
267.6  
268.5  
288.2  
MBh  
70  
62  
67  
62  
67  
72  
62  
67  
72  
62  
67  
72  
287.5 191.1 277.4  
313.6 139.5 302.6  
287.3 240.4 277.4  
313.3 188.7 302.4  
341.1 136.8 329.2  
291.4 286.6 282.3  
313.1 237.6 302.1  
340.8 185.6 328.9  
306.9 306.9 298.1  
314.5 285.8 303.9  
340.5 234.2 328.6  
266.5 181.9 255.0  
290.9 130.6 278.4  
266.8 231.1 255.4  
290.7 179.7 278.2  
316.5 128.1 303.0  
272.9 273.1 263.2  
290.4 228.6 278.0  
316.2 176.8 302.7  
288.7 288.7 278.5  
292.7 275.9 280.9  
316.0 225.3 302.5  
176.9  
125.7  
226.0  
174.8  
123.3  
263.3  
223.7  
172.0  
278.6  
270.2  
220.5  
171.7  
120.6  
220.5  
169.7  
118.4  
252.7  
218.5  
167.1  
267.7  
263.6  
215.5  
75  
80  
85  
Chart PD-55. SCRF/SIRF 20 Fan Performance for CV or with VFD  
Chart PD-56. SCRF/SIRF 20 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
60  
PKG-PRC002-EN  
Performance  
Data  
Air-Cooled  
25 Ton  
Table PD-45. SCRF/SIRF 25 Gross Cooling Capacity - 11,600 cfm  
Entering Ambient Air Temperature  
75 F  
Tot  
MBh  
85 F  
95 F  
105 F  
115 F  
EDB EWB  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
Sen  
MBh  
Tot  
Sen  
Tot  
Sen  
F
F
MBh  
209.5  
156.6  
260.1  
207.1  
153.6  
309.5  
257.3  
203.7  
340.4  
307.3  
253.6  
MBh  
MBh  
MBh  
MBh  
285.7  
312.4  
285.5  
312.1  
340.3  
290.7  
311.9  
340.0  
306.7  
312.9  
339.8  
MBh  
70  
62  
67  
62  
67  
72  
62  
67  
72  
62  
67  
72  
336.8 214.8 325.2  
367.8 161.8 355.1  
336.5 265.4 324.9  
367.4 212.3 354.8  
400.2 158.7 386.5  
337.8 315.3 326.7  
367.1 262.6 354.5  
399.9 208.8 386.2  
349.9 350.0 340.3  
366.9 312.6 354.5  
399.6 258.8 385.9  
312.8 204.0 299.6  
341.7 151.1 327.5  
312.5 254.5 299.4  
341.4 201.6 327.2  
372.0 148.3 356.6  
315.1 303.1 303.0  
341.1 251.8 326.9  
371.7 198.4 356.3  
329.9 329.9 318.7  
341.3 301.6 327.4  
371.3 248.2 356.0  
198.1  
145.5  
248.7  
195.9  
142.8  
296.0  
246.1  
192.8  
318.7  
295.6  
242.6  
192.0  
139.5  
242.5  
189.9  
137.0  
287.2  
240.0  
187.0  
306.8  
289.1  
236.7  
75  
80  
85  
Chart PD-57. SCRF/SIRF 25 Fan Performance for CV or with VFD  
Chart PD-58. SCRF/SIRF 25 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal and heat discharge pressure drops to external  
duct static pressure.  
PKG-PRC002-EN  
61  
Performance  
Data  
Air-Cooled  
29 Ton  
Table PD-46. SCRF/SIRF 29 Gross Cooling Capacity - 12,800 cfm  
Entering Ambient Air Temperature  
75 F  
Tot  
MBh  
85 F  
95 F  
105 F  
115 F  
EDB EWB  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
Sen  
MBh  
Tot  
Sen  
Tot  
Sen  
F
F
MBh  
246.3  
175.4  
314.0  
243.1  
171.9  
366.5  
310.6  
239.1  
388.4  
375.3  
306.0  
MBh  
MBh  
MBh  
MBh  
309.7  
338.2  
311.9  
337.9  
367.9  
326.8  
338.7  
367.6  
346.3  
346.8  
367.7  
MBh  
70  
62  
67  
62  
67  
72  
62  
67  
72  
62  
67  
72  
370.7 252.4 356.6  
404.3 181.4 388.9  
371.5 320.3 357.6  
403.9 249.1 388.6  
439.4 177.7 422.8  
379.9 377.1 367.4  
403.9 316.7 388.8  
439.1 245.0 422.4  
400.8 400.9 388.3  
407.3 382.3 392.7  
438.8 312.0 422.2  
341.7 239.9 326.1  
372.8 169.2 355.9  
343.0 307.3 327.8  
372.5 236.9 355.6  
405.3 165.8 387.0  
354.5 354.6 341.1  
372.8 304.2 356.1  
405.0 233.0 386.7  
375.1 375.2 361.1  
377.6 367.3 362.5  
404.8 299.9 386.7  
233.2  
162.7  
300.3  
230.3  
159.5  
341.1  
297.5  
226.6  
361.1  
356.6  
293.4  
226.3  
156.0  
292.7  
223.6  
153.0  
326.8  
290.5  
220.1  
346.3  
344.2  
286.8  
75  
80  
85  
Chart PD-59. SCRF/SIRF 29 Fan Performance for CV or with VFD  
Chart PD-60. SCRF/SIRF 29 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
62  
PKG-PRC002-EN  
Performance  
Data  
Air-Cooled  
30 Ton  
Table PD-47. SCRF/SIRF 30 Gross Cooling Capacity - 14,000 cfm  
Entering Ambient Air Temperature  
75 F  
Tot  
MBh  
85 F  
95 F  
105 F  
115 F  
EDB EWB  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
Sen  
MBh  
Tot  
Sen  
Tot  
Sen  
F
F
MBh  
262.0  
193.7  
327.3  
258.9  
190.1  
390.3  
323.7  
254.7  
423.7  
388.0  
319.0  
MBh  
MBh  
MBh  
MBh  
352.1  
384.9  
352.0  
384.6  
419.4  
360.4  
384.3  
419.0  
381.6  
386.7  
418.7  
MBh  
70  
62  
67  
62  
67  
72  
62  
67  
72  
62  
67  
72  
415.4 268.4 401.2  
453.3 200.0 437.9  
415.0 333.7 400.9  
452.9 265.1 437.6  
493.3 196.1 476.6  
417.7 397.5 404.4  
452.6 330.0 437.2  
492.9 260.8 476.2  
435.7 435.8 423.7  
452.7 394.5 437.7  
492.5 325.2 475.8  
386.0 255.3 369.6  
421.4 187.1 403.8  
385.6 320.5 369.3  
421.1 252.2 403.4  
458.7 183.6 439.7  
390.2 382.3 375.4  
420.7 317.0 403.1  
458.4 248.2 439.3  
410.7 410.7 396.7  
421.7 381.1 404.7  
458.0 312.5 438.9  
248.1  
180.2  
313.3  
245.2  
176.8  
372.9  
309.9  
241.3  
396.7  
373.5  
305.6  
240.5  
172.8  
305.6  
237.8  
169.7  
360.8  
302.4  
234.1  
381.6  
365.2  
298.3  
75  
80  
85  
Chart PD-61. SCRF/SIRF 30 Fan Performance for CV or with VFD  
Chart PD-62. SCRF/SIRF 30 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
63  
Performance  
Data  
Air-Cooled  
35 Ton  
Table PD-48. SCRF/SIRF 35 Gross Cooling Capacity - 15,200 cfm  
Entering Ambient Air Temperature  
75 F  
Tot  
MBh  
85 F  
95 F  
105 F  
115 F  
EDB EWB  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
Sen  
MBh  
Tot  
Sen  
Tot  
Sen  
F
F
MBh  
291.9  
208.6  
371.6  
288.2  
204.5  
437.0  
367.6  
283.5  
462.1  
444.2  
362.2  
MBh  
MBh  
MBh  
MBh  
370.3  
404.5  
372.6  
404.2  
440.4  
389.9  
405.0  
440.1  
413.3  
413.2  
440.1  
MBh  
70  
62  
67  
62  
67  
72  
62  
67  
72  
62  
67  
72  
440.9 298.8 424.9  
480.9 215.4 463.5  
441.7 378.7 425.9  
480.6 295.0 463.2  
523.1 211.1 504.2  
450.4 450.2 436.9  
480.4 374.5 463.2  
522.7 290.2 503.8  
476.1 476.2 462.0  
484.2 451.9 467.5  
522.3 369.0 503.4  
407.8 284.5 389.6  
445.0 201.4 425.4  
409.1 364.0 391.4  
444.7 281.0 425.0  
484.1 197.5 462.9  
422.3 422.4 406.7  
444.9 360.2 425.5  
483.8 276.5 462.5  
446.9 446.9 430.7  
450.0 435.8 431.7  
483.4 355.1 462.3  
276.8  
193.9  
355.9  
273.4  
190.2  
406.7  
352.5  
269.1  
430.7  
426.0  
347.7  
268.6  
186.0  
347.1  
265.4  
182.5  
390.0  
344.3  
261.4  
413.3  
413.3  
339.8  
75  
80  
85  
Chart PD-63. SCRF/SIRF 35 Fan Performance for CV or with VFD  
Chart PD-64. SCRF/SIRF 35 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
64  
PKG-PRC002-EN  
Performance  
Data  
Air-Cooled  
40 Ton  
T
Table PD-49. SCRF/SIRF 40 Gross Cooling Capacity - 18,400 cfm  
Entering Ambient Air Temperature  
75 F  
Tot  
MBh  
85 F  
95 F  
105 F  
115 F  
EDB EWB  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
Sen  
MBh  
Tot  
Sen  
Tot  
Sen  
F
F
MBh  
335.8  
241.9  
425.8  
331.8  
237.4  
496.5  
421.3  
326.6  
532.0  
507.6  
415.5  
MBh  
MBh  
MBh  
MBh  
430.8  
471.1  
432.6  
470.7  
513.2  
449.8  
470.9  
512.8  
476.6  
480.1  
512.4  
MBh  
70  
62  
67  
62  
67  
72  
62  
67  
72  
62  
67  
72  
512.1 343.9 493.5  
559.2 249.9 539.0  
512.3 434.1 494.0  
558.7 339.8 538.5  
608.7 245.2 586.8  
522.3 509.6 505.7  
558.2 429.4 538.1  
608.2 334.4 586.3  
548.1 548.2 532.0  
561.3 516.7 542.0  
607.7 423.4 585.8  
473.8 327.2 452.9  
517.6 233.6 495.0  
474.6 417.0 454.1  
517.2 323.4 494.6  
563.6 229.2 539.0  
488.0 482.5 469.3  
516.9 412.9 494.5  
563.1 318.4 538.6  
514.7 514.8 496.2  
521.9 497.2 501.4  
562.6 407.2 538.1  
318.3  
224.8  
407.6  
314.6  
220.7  
467.3  
404.0  
309.8  
496.3  
483.4  
398.5  
308.9  
215.7  
397.5  
305.4  
211.8  
450.1  
394.6  
300.8  
476.6  
467.3  
389.5  
75  
80  
85  
Chart PD-65. SCRF/SIRF 40 Fan Performance for CV or with VFD  
Chart PD-66. SCRF/SIRF 40 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
65  
Performance  
Data  
Air-Cooled  
50 Ton  
Table PD-50. SCRF/SIRF 50 Gross Cooling Capacity - 23,200 cfm  
Entering Ambient Air Temperature  
75 F  
Tot  
MBh  
85 F  
95 F  
105 F  
115 F  
EDB EWB  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
Sen  
MBh  
Tot  
Sen  
Tot  
Sen  
F
F
MBh  
428.2  
309.7  
542.1  
423.2  
304.0  
645.5  
536.3  
416.7  
682.3  
647.9  
528.9  
MBh  
MBh  
MBh  
MBh  
553.7  
605.8  
555.0  
605.3  
660.5  
577.2  
604.7  
659.9  
611.7  
613.1  
659.3  
MBh  
70  
62  
67  
62  
67  
72  
62  
67  
72  
62  
67  
72  
658.4 438.9 633.9  
719.0 320.1 692.5  
657.8 552.9 633.5  
718.4 433.7 692.0  
783.0 314.2 754.3  
667.2 660.8 645.4  
717.8 546.8 691.4  
782.3 426.9 753.7  
703.3 703.4 682.2  
720.3 659.1 694.8  
781.7 539.2 753.0  
608.4 417.1 581.6  
664.9 298.9 636.0  
608.4 531.0 582.2  
664.3 412.3 635.4  
724.3 293.5 693.1  
623.7 623.8 601.1  
663.8 525.3 634.9  
723.7 406.1 692.5  
659.9 660.0 636.5  
668.4 635.9 641.1  
723.1 518.2 691.9  
405.6  
287.7  
519.4  
401.1  
282.6  
601.1  
514.0  
395.1  
636.5  
622.9  
507.1  
393.7  
276.2  
507.1  
389.4  
271.3  
577.3  
502.2  
383.7  
611.8  
608.0  
495.7  
75  
80  
85  
Chart PD-67. SCRF/SIRF 50 Fan Performance for CV or with VFD  
Chart PD-68. SCRF/SIRF 50 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
66  
PKG-PRC002-EN  
Performance  
Data  
Air-Cooled  
60-Ton  
Table PD-51. SCRF/SIRF 60 Gross Cooling Capacity - 29,800 cfm  
Entering Ambient Air Temperature  
75 F  
Tot  
MBh  
85 F  
95 F  
105 F  
115 F  
EDB EWB  
Sen  
MBh  
Tot  
MBh  
Sen  
Tot  
Sen  
MBh  
Tot  
Sen  
Tot  
Sen  
F
F
MBh  
576.2  
412.4  
733.7  
569.1  
404.3  
860.3  
725.1  
559.8  
909.6  
880.3  
714.7  
MBh  
MBh  
MBh  
MBh  
728.7  
796.1  
731.9  
795.4  
866.4  
764.2  
795.3  
865.7  
809.7  
809.7  
865.0  
MBh  
70  
62  
67  
62  
67  
874.8 591.1 840.5  
954.6 427.0 917.3  
874.6 748.6 840.9  
953.8 583.7 916.5  
804.8 560.8 767.6  
878.5 397.4 838.1  
805.9 718.3 769.5  
877.8 553.9 837.4  
955.6 389.7 911.8  
829.8 829.9 797.8  
877.0 709.8 836.7  
954.8 545.0 911.1  
877.8 877.9 844.6  
886.0 863.8 848.4  
954.0 699.7 910.3  
544.9  
381.9  
702.2  
538.3  
374.6  
797.9  
694.1  
529.8  
844.7  
845.4  
684.4  
528.5  
366.0  
685.6  
522.2  
359.1  
764.3  
678.0  
514.1  
809.8  
809.8  
668.6  
75  
80  
85  
72 1038.1 418.6 997.7  
62  
889.2 889.3 860.2  
67  
953.0 739.9 915.8  
72 1037.3 574.2 996.9  
62  
67  
939.6 939.6 909.5  
958.7 895.7 923.0  
72 1036.5 729.2 996.1  
Chart PD-69. SCRF/SIRF 60 Fan Performance for CV or with VFD  
Chart PD-70. SCRF/SIRF 60 Fan Performance with Inlet GuideVanes  
Note:  
1. Fan curves include refrigerant coil and internal cabinet  
static losses.To determine static pressure to be used  
with these curves, add filter, economizer, flexible  
horizontal discharge and heat pressure drops to  
external duct static pressure.  
PKG-PRC002-EN  
67  
Performance  
Data  
Self-Contained  
Heating Coils  
Table PD-52. HotWater Heating Capacity  
180 F  
LAT  
F
200 F  
LAT  
F
Unit  
Size  
Airflow  
cfm  
8000  
Capacity  
MBh  
Flow  
gpm  
23.7  
24.9  
26.6  
28.7  
30.2  
31.6  
32.9  
47.1  
49.4  
52.6  
55.6  
58.9  
62.0  
63.1  
Capacity  
MBh  
Flow  
gpm  
28.7  
30.1  
32.2  
34.8  
36.6  
38.3  
39.9  
56.6  
59.3  
63.2  
66.9  
70.9  
74.6  
75.9  
20 tons  
22 tons  
25 tons  
29 tons  
32 tons  
35 tons  
38 tons  
42 tons  
46 tons  
52 tons  
58 tons  
65 tons  
72 tons  
80 tons  
237.2  
249.1  
266.2  
287.3  
302.2  
316.2  
329.6  
471.2  
494.0  
526.4  
556.7  
589.9  
620.9  
631.5  
87.3  
86.1  
84.5  
82.8  
81.8  
80.8  
80.0  
85.9  
84.8  
83.3  
82.1  
80.9  
79.9  
79.5  
287.6  
302.2  
323.0  
348.7  
366.8  
384.0  
400.2  
567.8  
595.3  
634.5  
671.2  
711.2  
748.7  
761.5  
93.2  
91.6  
89.8  
87.7  
86.4  
85.3  
84.3  
91.2  
89.8  
88.1  
86.7  
85.2  
84.0  
83.6  
8800  
10000  
11600  
12800  
14000  
15200  
16800  
18400  
20800  
23200  
26000  
28800  
29800  
Based on 60 degree F EAT with a 20 degree F water temperature differance.  
Table PD-53. Steam Heating Capacity  
2 psi  
Capacity  
5 psi  
10 psi  
Unit  
Airflow  
cfm  
8000  
LAT  
F
Capacity  
MBh  
LAT  
F
Capacity  
MBh  
LAT  
F
Size  
MBh  
257.4  
272.2  
292.7  
317.6  
334.7  
350.5  
365.3  
500.5  
526.7  
563.0  
596.3  
631.7  
663.9  
674.7  
20 tons  
22 tons  
25 tons  
29 tons  
32 tons  
35 tons  
38 tons  
42 tons  
46 tons  
52 tons  
58 tons  
65 tons  
72 tons  
80 tons  
89.7  
88.5  
87.0  
85.2  
84.1  
83.1  
82.2  
87.5  
86.4  
85.0  
83.7  
82.4  
81.3  
80.9  
271.6  
287.1  
308.8  
335.1  
353.2  
369.9  
385.4  
528.1  
555.7  
594.1  
629.3  
666.7  
700.7  
712.1  
91.3  
90.1  
88.5  
86.6  
85.4  
84.4  
83.4  
89.0  
87.8  
86.3  
85.0  
83.6  
82.4  
82.0  
291.6  
308.3  
331.6  
359.9  
379.3  
397.3  
414.0  
567.1  
596.8  
638.1  
675.9  
716.2  
752.8  
765.1  
93.6  
92.3  
90.6  
88.6  
87.3  
86.2  
85.1  
91.1  
89.9  
88.3  
86.9  
85.4  
84.1  
83.7  
8800  
10000  
11600  
12800  
14000  
15200  
16800  
18400  
20800  
23200  
26000  
28800  
29800  
Based on 60 degree F EAT  
68  
PKG-PRC002-EN  
Controls  
Signature Series Self-Contained Units  
We’ve redesigned the self-contained unit  
Comparative Enthalpy Module (ECEM)  
Option  
Available Input and Output  
with the latest control technology to make  
Points  
it even better! New modular DDC  
Analog inputs  
RTM Module (on all units)  
controls with human interface (HI) panel  
• Return air temperature  
• Return air humidity  
Binary inputs  
make self-contained units more flexible  
• Emergency stop  
and easier to operate.  
Ventilation Override Module (VOM)  
Option  
Binary inputs  
• VOM mode A, unit off  
• VOM mode B, pressurize  
• VOM mode C, exhaust  
• VOM mode D, purge  
• VOM mode E, purge w/duct pressure  
control  
Binary output  
V.O. relay  
Tracer® Interface (TCI ) option  
Binary input  
• Enthalpy enable airside economizer  
Binary outputs  
• Compressor on/off status  
Ventilation status  
• Condenser water flow status  
• Heat status  
• External auto/stop  
Controls areTrane-designed to work with  
• Unoccupied/occupied  
Trane equipment for optimum efficiency.  
• Dirty filter  
The factory installs and commissions  
VAV changeover with hydronic heat  
each control component to ensure simple  
• Units with staged heat interface have 1-  
and reliable operation.  
3 additional points  
Binary outputs  
Furthermore, the DDC controls modular  
design allows greater application  
VAV box drive max (VAV units only)  
• CV Unoccupied mode indicator (CV units  
only)  
flexibility using up to twelve different  
modules, dependent upon unit options.  
You can order exactly what the job  
requires as options, instead of one large  
control package. And since unit features  
are distributed among multiple printed  
circuit boards, field replacement is easy.  
• Alarm  
• Fan run request  
• Water pump request (water-cooled only)  
• Units with staged heat interface have 1-  
3 additional points  
Analog input  
• Airside economizer damper minimum  
position  
Analog output  
• Outside air damper actuator  
Depending upon unit options, IntelliPak®  
units can operate as:  
1) stand-alone  
2) interface withTrane’sTracer® building  
management system  
Analog outputs  
• Supply air pressure  
Heat Module Option  
• Analog output  
3) interface with a generic (non-Trane)  
building management system.  
• Supply air temperature  
• Suction temperature of each circuit  
• Entering economizer water  
temperature  
Generic BAS Option (GBAS)  
Binary inputs  
• Demand limit contacts  
Binary outputs  
• Dirty filter relay  
• Zone temperature  
• Entering condenser water temperature  
• Supply air temperature reset signal  
• Morning warmup sensor temperature  
• Entering air temperature  
Analog inputs  
• Refrigeration fail relay  
• Heat fail relay  
• Supply fan fail relay  
• Active diagnostics  
• Cooling and heating setpoints  
VAV discharge air temperature  
setpoints  
• Supply air pressure setpoint  
• Cooling and heating enable/disable  
• Air economizer enable/disable  
• Airside economizer minimum position  
• Unit priority shutdown  
Analog inputs  
• Occupied zone cooling setpoint  
• Occupied zone heating setpoint  
• Unoccupied zone cooling setpoint  
• Unoccupied zone heating setpoint or  
minimum outside air flow setpoint  
• Supply air cooling setpoint  
• Supply air heating setpoint  
• Supply air static pressure setpoint  
PKG-PRC002-EN  
69  
Controls  
Standard IntelliPak® Unit  
Control Features  
All set-up parameters are preset from the  
factory, requiring less start-up time during  
installation.  
The human interface panel is easy to  
read and requires less time for building  
maintenance personnel to learn to  
interact with the unit. It features a clear  
language display (in English, Spanish, or  
French) that shows all of the self-  
contained unit control parameters, such  
as system on/off; demand limiting type;  
night setback setpoints; and many other  
setpoints. All adjustments are done  
through the human interface key-pad.  
Also the human interface panel allows  
you to monitor diagnostic points such as;  
sensor failures; supply airflow loss; and  
inoperative refrigerant circuit. No special  
tools are required for servicing the unit.  
Diagnostics are held in memory, even  
during power loss. This allows the  
operator/servicer to diagnose the failure  
root cause.  
Human interface panel is  
available as unit or  
remote mounted.  
Human Interface Panel (HI)  
DIAGNOSTICS allows the user to  
review active and historical lists of  
diagnostic conditions. A total of 49  
different diagnostics can be read at the  
human interface (HI) panel and the last  
20 diagnostics can be held in an active  
history buffer log at the HI panel.  
SETUP allows the user to edit control  
parameters, sensor selections, setpoint  
source selections, output definitions,  
and numerous other points in this  
menu. All points have factory preset  
values to keep unnecessary editing to a  
minimum.  
CONFIGURATION allows changing of  
factory-preset unit configuration  
information. This information can be  
edited only if certain options are field-  
installed or deleted from the unit. For  
example, if aTrane communication  
interface (TCI) module or ventilation  
override module (VOM) were field-  
installed, the unit configuration will  
require editing to reflect those options  
for proper unit operation.  
IntelliPak® Unit Features  
The human interface panel provides a  
16-button keypad for monitoring, setting,  
editing and controlling. The HI panel is  
mounted in the units main control panel,  
accessible through the units control panel  
door.  
• Unit mounted human interface panel  
with a two line x 40 character language  
(English, Spanish, or French) display  
and a 16-function keypad that includes  
CUSTOM, DIAGNOSTICS, and SERVICE  
TEST MODE menu keys on IntelliPak®  
units  
The optional remote-mount version of the  
human interface (RHI) panel has all the  
functions of the unit-mounted version,  
except for the service mode.To use a  
RHI, the unit must be equipped with the  
remote HI interface option (model  
number digit 32 = 2), which includes an  
interprocessor communications bridge  
(IPCB). The RHI can be located up to 1,000  
feet (304.8 m) from the unit. A single RHI  
can be used to monitor and control up to  
four self-contained units, each containing  
an IPCB.  
• Compressor lead/lag  
• FROSTATcoil frost protection on all  
units  
• Daytime warmup (occupied mode) on  
units with heating options and morning  
warmup operation on all units  
• Supply air static overpressurization  
protection on units with inlet guide  
vanes and variable frequency drives  
(VFDs)  
• Supply airflow proving  
• Supply air tempering control with  
heating option  
• Supply air heating control onVAV with  
hydronic heating option  
• Mappable sensors and setpoint sources  
• Occupied/unoccupied switching  
• Timed override activation  
• Programmable water purge during  
unoccupied mode  
The main menus of the human interface  
panels are:  
STATUS is used to monitor all  
temperatures, pressures, humidities,  
setpoints, input and output status.  
• CUSTOM key allows the user to  
customize a status report - consisting of  
up to four screens of the data available  
in the main Status menu.  
SERVICE allows servicing or  
troubleshooting the unit by selecting  
component control outputs such as  
compressors, fans, damper position,  
etc. This menu is accessible only at the  
unit-mounted human interface panel.  
SETPOINT is used to edit all factory  
preset default setpoints.  
70  
PKG-PRC002-EN  
Sequence of  
Operation  
Controls  
is that sequence “A” (unit off) is first, with  
sequence “E” (purge with duct pressure  
control) last.  
•Exhaust fan (field-installed) - On  
Control Sequences of  
Operation  
Morning Warmup  
•Exhaust damper (field-installed) - Open  
• Purge sequence “D”  
• UNIT OFF sequence “A”  
When complete system shut down is  
required, the following sequence can be  
used.  
•Supply fan – Off  
•Supply fan VFD – Off (0 Hz)  
(if equipped)  
•Inlet guide vanes – closed  
(if equipped)  
•Outside air dampers – Closed  
•Heat – all stages – Off, Modulating heat  
output at 0 vdc  
•Occupied/Unoccupied output –  
Deenergized  
•VO relay – Energized  
This sequence could be used for purging  
the air out of a building before coming out  
of unoccupied mode of operation onVAV  
units. Also, it can be used to purge smoke  
or stale air.  
This feature is available on all types of  
factory-installed heat units and on units  
with no heat. This function may still be  
selected to support systems with heat  
sources not provided by the self-  
contained unit. At the conclusion of  
unoccupied mode, the selected zone is  
heated to the user-defined morning  
warmup setpoint. The unit is then  
released to occupied mode. There are  
two types of morning warmup: full  
capacity or cycling capacity.  
•Supply fan – On  
•Supply fan VFD – On (60 Hz)  
(if equipped)  
•Inlet guide vanes/VAV boxes – Open  
(if equipped)  
•Outside air damper – Open  
•Heat – all stages – Off, Modulating heat  
output at 0 vdc  
•Occupied/Unoccupied output – Energized  
•VO relay – Energized  
•Exhaust fan (field-installed) - On  
•Exhaust damper (field-installed) - Open  
• Full Capacity Morning Warmup (MWU)  
Full capacity morning warmup uses full  
heating capacity to heat the zone as  
quickly as possible. Full heating capacity  
is provided until the morning warmup  
setpoint is met. At this point, the unit is  
released to daytime mode.  
•Exhaust fan (field-installed) - Off  
•Exhaust damper (field-installed) - Closed  
• PRESSURIZE sequence “B”  
This override sequence can be used if a  
positively pressured space is desired  
instead of a negatively pressurized space.  
•Supply fan – On  
•Supply fan VFD – On (60 Hz)  
(if equipped)  
•Inlet guide vanes/VAV boxes – Open  
(if equipped)  
•Outside air dampers – Open  
•Heat – all stages – Off, Modulating heat  
output at 0 vdc  
•Occupied/ Unoccupied output -  
Energized  
•VO relay - Energized  
•Exhaust fan (field-installed) - Off  
•Exhaust damper (field-installed) - Closed  
• Purge with duct pressure control “E”  
This sequence can be used when supply  
air control is required for smoke control.  
• Supply fan – On  
•Supply fan VFD – On (if equipped)  
•Inlet guide vanes – controlled by supply  
air pressure control function with  
supply air pressure high limit disabled  
•Outside air dampers – Open  
•Heat – all stages – Off, Modulating heat  
output at 0 vdc  
•Occupied/Unoccupied output – Energized  
•VO relay – Energized  
• Cycling Capacity Morning Warmup  
(MWU)  
Cycling capacity morning warmup  
provides gradual heating to overcome  
“building sink” as the zone is heated.  
Normal zone temperature control with  
varying capacity is used to raise the zone  
temperature to the MWU zone  
temperature setpoint. Cycling capacity  
MWU will operate until MWU setpoint is  
reached or for 60 minutes. Then the unit  
switches to occupied mode. Cooling will  
suspend untill building load conditions  
exceed the MWU setpoint of 3 F (1.7 C),  
which is field adjustable.  
•Exhaust fan (field-installed) - On  
•Exhaust damper (field-installed) - Open  
Note: Each system (cooling, exhaust,  
supply air, etc.) within the unit can be  
redefined in the field for each of the five  
sequences, if required. Also the  
definitions of any or all of the five  
sequences may be locked into the  
software by simple key strokes at the  
human interface panel.  
• EXHAUST sequence “C”  
With the buildings exhaust fans running  
and the units supply fan off, the  
conditioned space becomes negatively  
pressurized. This is desirable for clearing  
the area of smoke when necessary; i.e.  
from an extinguished fire, to keep smoke  
out of areas that were not damaged.  
•Supply fan – Off  
•Supply fan VFD – Off (0 Hz)  
(if equipped)  
•Inlet guide vanes – Closed  
(if equipped)  
•Outside air dampers – Closed  
•Heat – all stages – Off, Modulating heat  
output at 0 vdc  
•Occupied/Unoccupied output –  
Deenergized  
•VO relay – Energized  
Note: When using the morning warmup  
option in a heating/cooling self-contained  
unit in aVAV system, it is important to  
maintain airflow through the unit. This  
can be accomplished by electrically tying  
theVAV boxes to theVAV drive max  
output relay contacts on the units RTM  
module board or by using changeover  
thermostats. Either of these methods will  
assure adequate airflow through the unit  
and satisfactory heating.  
Ventilation Override (VOM) Option  
The user can customize up to five  
different override sequences for  
purposes of ventilation override control. If  
more than one VOM sequence is being  
requested, the sequence with the highest  
priority is initiated first. Priority schedule  
PKG-PRC002-EN  
71  
Sequence of  
Operation  
Controls  
Generic Building Automation System  
Module (GBAS) Option  
shut off and will de-ice the coil.Timers  
prevent the compressors from rapid  
cycling.  
when the temperature rises 5 F above  
the setpoint.  
The generic building automation system  
module (GBAS) provides broad control  
capabilities for building automation  
systems other than Trane’sTracer®  
system. A field provided potentiometer  
or a 0-5 vdc signal can be applied to any  
of the inputs of the GBAS to provide the  
following inputs and outputs.  
Comparative Enthalpy Control of Airside  
Economizer Option  
Occupied/Unoccupied Switching  
There are four ways to switch occupied/  
unoccupied:  
An optional comparative enthalpy  
system is used to control the operation of  
the economizer and measures the  
temperature and humidity of both return  
air and outside air to determine which  
source has lower enthalpy.This system  
allows true comparison of outdoor air  
and return air enthalpy by measurement  
of outdoor and return air temperatures  
and humidities.  
(1) Programmable night setback sensor  
(2) Field-supplied contact closure  
(hardwired binary input to RTM)  
(3) Tracer®  
• GBAS Analog Inputs  
(4) Factory-mounted time clock  
Four analog inputs that can be configured  
to be any of the following:  
(1) Occupied zone cooling  
(2) Unoccupied zone cooling  
(3) Occupied zone heating  
(4) Unoccupied zone heating  
(5) SA cooling setpoint  
• Field Supplied Occupied/Unoccupied  
input on the RTM  
This input accepts a field supplied switch  
or contacts closure such as a time clock.  
Note: If comparative enthalpy is not  
ordered, the standard method compares  
outdoor air enthalpy with a fixed  
reference enthalpy, set through the  
human interface panel.  
Trane Tracer® System  
TheTraneTracer® system can control the  
occupied/unoccupied status of the self-  
contained unit.  
(6) SA heating setpoint  
(7) Space static pressure setpoint  
(8) SA static pressure setpoint  
Compressor Lead/Lag  
• Factory MountedTime Clock  
A time clock can control the  
occupied/unoccupied status of the  
self-contained unit.  
Compressor lead/lag is a user-selectable  
feature through the human interface  
panel available on all units. After each  
request for compressor operation, the  
lead refrigeration circuit or compressor  
switches, thereby causing a more  
equitable or balanced run time among  
compressors.  
• GBAS Binary Outputs  
Each of the five (5) relay outputs can be  
mapped to any/all of the available  
diagnostics.  
Timed Override Activation - ICS  
This function is operational whenever the  
units RTM module board is used as the  
zone temperature sensor source, which  
can be set at the human interface panel.  
When this function is initiated by the push  
of the override button on the zone sensor,  
the unit will switch to the occupied mode.  
Unit operation (occupied mode) during  
timed override is terminated by a signal  
from Tracer®.  
• Demand Limiting Binary Input  
This function is operational on units with a  
GBAS and is used to reduce electrical  
consumption at peak load times. There  
are two types of demand limiting, 50%  
and 100%. When demand limiting is  
needed, mechanical cooling and heating  
operation are either partially (50%), or  
completely disabled (100%) to save  
energy.The demand limit definition is  
user definable at the human interface  
panel. Demand limit binary input accepts  
a field supplied switch or contact closure.  
When the need for demand limiting has  
been discontinued, the units cooling/  
heating functions will again become fully  
enabled.  
Emergency Stop Input  
A binary input is provided on the unit’s  
RTM module board for installation of a  
field-provided switch or contacts to  
immediatly shutdown all unit functions.  
Water Flow Control  
With compatible piping configurations,  
the unit can be configured to provide:  
1) Constant water flow with basic or  
intermediate piping or 2)Variable water  
flow with intermediate piping only.  
Timed OverrideActivation - Non-ICS  
This function is active whenever the units  
RTM module board is selected as the  
zone temperature source, which can be  
set at the human interface panel. When  
this function is initiated by the push of the  
override button on the zone sensor, the  
unit will switch to the occupied mode.  
Automatic cancellation of the timed  
override mode occurs after three hours  
of operation.  
Constant water flow is for condenser  
pumping systems that are not capable of  
unloading the water-pumping system.  
Variable water flow maximizes energy  
saving by unloading the water pumping  
system.  
Evaporator Coil Frost Protection  
FROSTAT™  
A temperature sensor on the evaporator  
is used to determine if the coil is getting  
close to a freezing condition. Mechanical  
cooling capacity is shed as necessary to  
prevent icing.  
Low Ambient Compressor Lockout  
This function will lock out the compressor  
if the outdoor air temperature is below  
the low ambient compressor lock-out  
temperature setpoint when using a field-  
installed outside air sensor.This setpoint  
is adjustable at the human interface  
panel. Compressors will lock out when  
outdoor air temperature falls below that  
selected temperature and will start again  
Head Pressure Control  
• Water-Cooled Condensers  
Units that are set up for variable water  
flow will modulate a water valve to  
maintain a user-defined condensing  
temperature setpoint. Condensing  
temperature will be referenced utilizing  
factory installed sensors located at each  
condenser.  
The FROSTATsystem eliminates the  
need for hot gas bypass and adds a  
suction line surface temperature sensor  
mounted near the TXV bulb location to  
shut off the cooling when coil frosting  
conditions occur.The supply fan is not  
72  
PKG-PRC002-EN  
Sequence of  
Operation  
Controls  
• Air-Cooled Condensers  
Inlet guide vane assemblies installed on  
the supply fan inlet regulate fan capacity  
and limit horsepower at lower system air  
requirements. When in any position other  
than full open, the vanes pre-spin the air  
in the same direction as supply fan  
rotation. As the vanes approach the full-  
closed position, the amount of “spin”  
induced by the vanes increases at the  
same time that intake airflow and fan  
horsepower diminish. The inlet guide  
vanes will close when the supply fan is  
off.  
Bypass control is offered as an option to  
provide full nominal airflow in the event  
of drive failure. Manual bypass is initiated  
at the human interface panel. When in  
the bypass mode,VAV boxes will need to  
be fully opened. The self-contained unit  
will control heating and cooling functions  
to maintain setpoint from a user defined  
zone sensor. Supply air static pressure  
limit will be active in this mode.  
Condenser fans will stage per a user-  
defined setting. If the condenser is  
equipped with head pressure control (air  
modulation on last stage of condenser  
capacity), the condenser airflow will  
modulate to maintain condensing  
temperature setpoint. Condensing  
temperature is determined by sensors  
located at each condenser coil.  
Water Purge  
Supply Air Static Pressure Limit  
This user-definable feature allows the  
user to select a purge schedule to  
automatically circulate water through the  
economizer and condensers periodically  
during non-operational times. This allows  
fresh chemicals to circulate in waterside  
heat exchangers.  
The opening of the inlet guide vanes and  
VAV boxes are coordinated during unit  
start up and transition to/from occupied/  
unoccupied modes to prevent  
Variable Frequency Drive (VFD) Control  
Variable frequency drives are driven by a  
modulating 0-10 vdc signal from the RTM  
module. A pressure transducer  
measures duct static pressure, and the  
VFD adjusts the fan speed to maintain the  
supply air static pressure within an  
adjustable user-defined range. The range  
is determined by the supply air pressure  
setpoint and supply air pressure  
overpressurization of the supply air  
ductwork. However, if for any reason the  
supply air pressure exceeds the user-  
defined supply air static pressure limit  
that was set at the human interface  
panel, the supply fan/VFD is shut down  
and the inlet guide vanes close. Then unit  
will attempt to restart, up to three times. If  
the overpresssurization condition still  
occurs on the third restart, the unit shuts  
down and a manual reset diagnostic sets  
and displays at the human interface  
panel.  
Airside Options  
Inlet GuideVane Control  
Inlet guide vanes are driven by a  
modulating 0-10 vdc signal from the RTM  
module. A pressure transducer  
measures duct static pressure, and the  
inlet guide vanes modulate to maintain  
the supply air static pressure within an  
adjustable user-defined range. The range  
is determined by the supply air pressure  
setpoint and supply air pressure  
deadband, which are set through the  
human interface panel.  
deadband, which are set through the  
human interface panel.  
Variable frequency drives provide supply  
fan motor speed modulation. The drives  
will accelerate or decelerate as required  
to maintain the supply static pressure  
setpoint.  
PKG-PRC002-EN  
73  
Sequence of  
Operation  
Controls  
Auto Changeover  
dampers open. The rate of economizer  
modulation is based on deviation of the  
zone temperature from setpoint; i.e., the  
further away from setpoint, the faster the  
fresh air damper will open. First stage of  
cooling will start after the economizer  
reaches full open.  
Zone Temperature Control  
Unit Sequence Of Operation  
When the system mode is auto, the mode  
will change to cooling or heating as  
necessary to satisfy the zone cooling and  
heating setpoints. The zone cooling and  
heating setpoints can be as close as 2 F  
(1.1 C) apart.  
1
Occupied ZoneTemperature Control  
Cooling/Waterside Economizer  
2
Note that the airside economizer will only  
function freely if ambient conditions are  
below the enthalpy control settings or  
below the return air enthalpy if unit has  
comparative enthalpy installed. If outside  
air is not suitable for “economizing,” the  
fresh air dampers drive to the minimum  
open position. A field adjustable, factory  
default setting in the human interface  
panel orTracer® can provide the input to  
establish the minimum damper position.  
During occupied cooling mode, the  
waterside economizer option and  
mechanical cooling function to control  
zone temperature. If the entering  
condenser water temperature is  
appropriate to use “free cooling,” the  
economizer initiates to attempt to satisfy  
the cooling zone temperature setpoint  
with the compressors staging on as  
necessary. Minimum on/off timing of  
compressors prevents rapid cycling.  
Unoccupied ZoneTemperature Control  
Cooling and Heating  
Both cooling and heating modes can be  
selected to maintain unoccupied zone  
temperature deadbands. For unoccupied  
periods, heating, economizer operation,  
or compressor operation can be  
selectively locked out at the human  
interface panel.  
At outdoor air conditions above the  
enthalpy control setting, only mechanical  
cooling is used and the fresh air dampers  
remain at minimum position.  
Waterside economizing enables when  
the units entering water temperature is  
below the units entering mixed air  
temperature by 4 F plus the user  
adjustable economizer approach  
temperature. The approach temperature  
default is 4 F and is adjustable from 0-9 F  
at the human interface (HI) panel.  
Waterside economizing disables when  
the units entering water temperature is  
not below the units entering mixed air  
temperature by at least the water  
economizer approach temperature. The  
approach temperature defaults to 4 F and  
is adjustable from 0-9 F at the HI. The  
economizer acts as the first stage of  
cooling. If the economizer is unable to  
maintain the zone temperature setpoint,  
the compressor module will bring on  
compressors as required to meet the  
setpoint.  
If the unit does not include an airside  
economizer, only mechanical cooling will  
operate to satisfy cooling requirements.  
Heating: Electric  
On units with electric heating, the zone  
temperature can be controlled to a  
heating setpoint during the occupied  
mode by cycling a single stage electric  
heater. Interface is provided for field  
supplied single stage electric heat. The  
zone temperature heating setpoint and  
deadband are user defined at the human  
interface panel.  
Heating: Hot Water or Steam  
On units with hot water or steam heating,  
the zone temperature can be controlled  
to a heating setpoint during the occupied  
mode. The zone temperature heating  
setpoint and deadband are user defined  
at the human interface panel.  
If the unit does not include an economizer,  
only mechanical cooling will operate to  
satisfy cooling requirements.  
Cooling/Airside Economizer  
Supply AirTempering  
During occupied cooling mode, the  
economizer option and mechanical  
cooling operate to control zone  
For hot water, steam, or electric heat  
units in the heat mode but not actively  
heating, if the supply air temperature  
drops to 10 F (5.5 C) below the occupied  
zone heating temperature setpoint, one  
stage of heat will be brought on to  
maintain a minimum supply air  
temperature. If the outside air enthalpy is  
appropriate for airside economizing or  
“free cooling,” the economizer initiates to  
satisfy the cooling zone temperature  
setpoint with the compressors staging on  
as necessary. Minimum on/off timing of  
compressors will prevent rapid cycling.  
temperature. The unit transitions out of  
heat mode if the supply air temperature  
rises to 10 F above the occupied zone  
heating temperature setpoint.  
On units with an airside economizer, a call  
for cooling will modulate the fresh air  
74  
PKG-PRC002-EN  
Sequence of  
Operation  
Controls  
modulation is based on deviation of the  
discharge temperature from setpoint, i.e.,  
the further away from setpoint, the faster  
the fresh air damper will open. First stage  
of cooling initiates after the economizer  
reaches full open.  
lower usage of mechanical cooling, thus  
savings in compressor kW, but an  
increase in supply fan kW may occur.  
Supply Air Temperature  
Control Unit Sequence Of  
Operation  
Outdoor air heating reset is the inverse of  
cooling, with the same principles applied.  
1
For both outdoor air cooling reset and  
heating reset, there are three user  
defined parameters that are adjustable  
through the human interface panel.  
•Beginning reset temperature  
•Ending reset temperature  
•Maximum amount of temperature reset  
Note that the airside economizer is only  
allowed to function freely if ambient  
conditions are below the setpoint control  
settings or below the return air enthalpy,  
if unit has the comparative enthalpy  
option. If outside air is not suitable for  
“economizing,” the fresh air dampers  
drive to the minimum open position. A  
field adjustable, factory default setting in  
the human interface panel orTracer® can  
provide the input to establish the  
Occupied Supply AirTemperature  
Control  
Cooling/Waterside Economizer  
During occupied cooling mode, the  
waterside economizer option and  
mechanical cooling are used to control  
the supply air temperature. The supply  
air temperature setpoint and deadband  
are user defined at the human interface  
panel. Waterside economizing enables  
when the units entering water  
temperature is below the units entering  
mixed air temperature by 4 F plus the  
user adjustable economizer approach  
temperature. The approach temperature  
default is 4 F and is adjustable from 0-9 F  
at the HI. Waterside economizing disables  
when the units entering water  
temperature is not below the units  
entering mixed air temperature by at  
least the water economizer approach  
temperature.  
The economizer acts as the first stage of  
cooling. If the economizer is unable to  
maintain the supply air setpoint, the  
compressor module will bring on  
Reset based on zone temperature  
Zone reset is applied to the zone(s) in a  
building that tends to overcool or  
overheat. The supply air temperature  
setpoint is adjusted based on the  
temperature of the critical zone(s). This  
can have the effect of improving comfort  
and/or lowering energy usage. The user-  
defined parameters are the same as for  
outdoor air reset.  
minimum damper position.  
At outdoor air conditions above the  
setpoint or comparative enthalpy control  
setting, only mechanical cooling is used  
and the fresh air dampers remain at  
minimum position.  
Supply AirTempering (Hot Water and  
Steam Units Only)  
When supply air temperature falls below  
the supply air temperature deadband low  
end, the heating valve modulates open to  
maintain the minimum supply air  
temperature setpoint.  
If the unit does not include an  
economizer, only mechanical cooling  
operates to satisfy cooling requirements.  
Heating: Hot Water or Steam  
On units with hot water or steam heating,  
the supply air temperature can be  
controlled to a heating setpoint during the  
occupied mode. The supply air  
2
temperature heating setpoint and  
deadband are user defined at the human  
interface panel.VAV occupied heating on  
hot water and steam heat units is initiated  
by closing a field-supplied switch or  
contacts connected to a changeover input  
on the units RTM module board .  
Unoccupied Supply AirTemperature  
Control Zone Heating and Cooling  
During unoccupied mode, the unit  
operates to maintain zone temperature  
with fan cycling as needed for building  
load.VAV boxes drive full open. However,  
unit airflow modulation control operates  
to maintain duct static setpoint. The unit  
controls zone temperature within the  
unoccupied zone cooling and heating  
(heating units only) deadbands.  
compressors as required to meet the  
setpoint. If the unit does not include an  
economizer, only mechanical cooling will  
satisfy cooling requirements.  
Cooling/Airside Economizer  
During occupied cooling mode of  
operation, the airside economizer option  
and mechanical cooling are used to  
control the supply air temperature. The  
supply air temperature setpoint and  
deadband are user-defined at the human  
interface panel. If the temperature of the  
mixed air is appropriate to use “free  
cooling,” the economizer initiates to  
satisfy the supply air setpoint. Then if  
required, the mechanical cooling stages  
on to maintain supply air temperature  
setpoint. Minimum on/off timing of the  
mechanical cooling prevents rapid  
cycling.  
Supply Air Setpoint Reset  
Supply air reset can be used to adjust the  
supply air temperature setpoint on the  
basis of a zone temperature or outdoor  
air temperature. Supply air reset  
adjustment is available from the human  
interface panel for supply air heating and  
supply air cooling control.  
Daytime Warmup  
During occupied mode, if the zone  
temperature falls to a preset, user-  
defined zone low limit temperature  
setpoint, the unit is put into daytime  
warmup. The system changes over to CV  
heating, theVAV boxes drive full open.  
However, unit airflow modulation control  
operates to maintain duct static setpoint,  
and full heating capacity is provided until  
the daytime warmup setpoint is reached.  
The unit is then returned to normal  
occupied mode.  
Reset based on outdoor air temperature  
Outdoor air cooling reset is sometimes  
used in applications where the outdoor  
temperature has a large effect on  
building load. When the outside air  
temperature is low and the building  
cooling load is low, the supply air setpoint  
can be raised, thereby preventing  
On units with an airside economizer, a call  
for cooling will modulate the fresh air  
dampers open. The rate of economizer  
subcooling of critical zones. This reset can  
PKG-PRC002-EN  
75  
Zone Sensor  
Options  
Controls  
Standard On All Units  
VAV  
VAV  
Standard with all units  
Zone temperature sensor, Accessory  
Model Number Digit 6 = A, BAYSENS017  
Single setpoint sensor with system  
function lights, Accessory Model Number  
Digit 6 = H, BAYSENS021  
Programmable night-setback sensor,  
Accessory Model Number Digit 6 = J,  
BAYSENS020  
This programmable night setback sensor  
is for use inVAV applications.The sensor  
has a time clock function that provides  
communication to the self-contained unit  
through a 2-wire communications link.  
The desired transition times are  
programmed at the night setback sensor  
and communicated to the self-contained  
unit.  
This wall-mounted zone sensor ships with  
every Signature Series unit, CV orVAV.  
Additional sensors are also available for  
order using the accessory model number.  
It includes an internal thermistor and  
should be mounted in the zone. This  
sensor is available for use with all zone  
sensor options to provide remote sensing  
capabilities.  
This wall-mounted zone sensor option is  
for use inVAV applications. Features and  
system control functions are:  
Temperature sensing in the zone  
• System control switch with mode  
setting for Auto or Off  
• Supply air single temperature setpoint  
The programmable night setback  
(unoccupied mode) operates through the  
time clock provided in the sensors with  
night setback. When the time clock  
switches to night setback operation, the  
outdoor air dampers close and heating/  
cooling enables or disables, depending on  
set-up parameters. As the building load  
changes, the night setback sensor  
energizes the self-contained unit’s  
heating/cooling (if enabled) function and  
the evaporator fan. The self-contained  
unit will cycle through the evening as  
heating/cooling (if enabled) is required in  
the space. When the time clock switches  
from night setback to occupied mode, all  
heating/cooling functions begin normal  
operation.  
• Function status indicator lights:  
SYS ON glows continuously during  
normal operation, or blinks if system is  
in test mode.  
COOL glows continuously during  
cooling cycles or blinks to indicate a  
cooling system failure.  
HEAT glows continuously during  
heating cycles or blinks to indicate a  
heating system failure.  
SERVICE blinks or glows to indicate a  
problem. These signals vary depending  
on the particular equipment used.  
When using the night setback options  
with VAV heating/cooling, maintain  
airflow through the self-contained unit by  
electrically tying theVAV boxes to the  
unoccupied output relay contacts on the  
units RTM module board or by using  
changeover thermostats. Either of these  
methods will assure adequate airflow  
through the unit and satisfactory  
temperature control of the building.  
76  
PKG-PRC002-EN  
Zone Sensor  
Options  
Controls  
CV  
CV  
CV  
Programmable night setback sensor,  
Accessory Model Number Digit 6 = G,  
BAYSENS019  
Dual setpoint, manual/automatic  
changeover sensor with system function  
lights, Accessory Model Number Digit 6 = F,  
BAYSENS010  
Dual setpoint, manual/automatic  
changeover sensor, Accessory Model  
Number Digit 6 = E, BAYSENS008  
This zone sensor module is for use with  
cooling/heating CV applications. It  
provides the following features and  
system control functions:  
This zone sensor is for use with cooling/  
heating CV applications. It provides the  
following features and system control  
functions:  
The programmable night setback sensor  
is for use in CV applications. The sensor  
has a time clock function that provides  
communication to the self-contained unit  
through a 2-wire communications link.  
The desired transition times are  
programmed at the night setback sensor  
and communicated to the self-contained  
unit.  
• System control switch (Heat/Auto/Off/  
Cool): Allows you to select heating  
mode, cooling mode, automatic  
selection of heating or cooling as  
required, or turn the system off.  
• System control switch to select heating  
mode (HEAT), cooling mode (COOL),  
AUTO for automatic selection of  
heating or cooling as required, or OFF  
to turn the system off.  
The programmable night setback  
(unoccupied mode) operates through the  
time clock provided in the sensors with  
night setback. When the time clock  
switches to night setback operation, the  
outdoor air dampers close and heating/  
cooling enables or disables, depending on  
set-up parameters. As the building load  
changes, the night setback sensor  
energizes the self-contained units  
heating/cooling (if enabled) function and  
the evaporator fan. The self-contained  
unit will cycle through the evening as  
heating/cooling (if enabled) is required in  
the space. When the time clock switches  
from night setback to occupied mode, all  
heating/cooling functions begin normal  
operation.  
• Fan control switch (Auto/On): Allows you  
to select automatic fan operation while  
actively heating or cooling or  
• Fan control switch to select automatic  
fan operation while actively heating or  
cooling (AUTO), or continuous fan  
operation (ON).  
continuous fan operation.  
• Dual temperature setpoint levers allow  
you to set different cooling (blue lever)  
and heating setpoints (red lever).  
• Dual temperature setpoint levers for  
setting cooling (blue lever) or heating  
(red lever).  
• Thermometer to indicate temperature in  
the zone.  
• Thermometer to indicate temperatuare  
in the zone.  
• Function status indicator lights:  
SYS ON glows continuously during  
normal operation, or blinks if system is  
in test mode.  
COOL glows continuously during  
cooling cycles or blinks to indicate a  
cooling system failure.  
HEAT glows continuously during  
heating cycles or blinks to indicate a  
heating system failure.  
SERVICE blinks or glows to indicate a  
problem. These signals vary depending  
on the particular equipment used.  
PKG-PRC002-EN  
77  
Zone Sensor  
Options  
Controls  
Integrated ComfortSystems  
Sensors for CV and VAV  
Applications  
Zone temperature sensor w/timed override  
buttons, Accessory Model Number Digit 6  
= B, BAYSENS013C  
Zone temperature sensor w/timed override  
buttons and local setpoint adjustment,  
Accessory Model Number Digit 6 = C,  
BAYSENS014C  
This zone sensor is for use with  
cooling/heating ICS™. It provides the  
following features and system control  
functions:  
This zone sensor is for use with cooling/  
heating Integrated Comfort™ Systems  
(ICS). It provides the following features  
and system control functions:  
• Remote temperature sensing in the  
zone  
• Remote temperature sensing in the  
zone  
• A timed override button to move an  
Integrated Comfort ™ System or a  
building management system from  
unoccupied to occupied mode.  
• A timed override button to move an ICS  
or building management system from  
it unoccupied to occupied mode.  
• Cancel button to cancel the unoccupied  
override command.  
• Setpoint thumbwheel for local  
setpoint adjustment  
• Cancel button to cancel the  
unoccupied override command.  
78  
PKG-PRC002-EN  
Electrical Data  
Table ED-1. Number of Compressors per Unit  
Selection Procedures  
RLA = Rated Load Amps  
Compressor LRA = Locked Rotor Amps  
Fan Motor LRA = Locked Rotor Amps,  
N.E.C.Table 430 - 150  
SCRF/SIRF 20  
SCWF/SIWF 20 - 25  
25 - 29  
29 - 32  
30 - 35  
35 - 38  
40  
42 - 46  
2
1
50  
52 - 58  
-
3
60  
80  
-
65 - 72  
1
3
10  
15  
2
-
1
1
3
-
4
FLA = Full Load Amps, N.E.C.  
Table 430 - 150  
Table ED-2. SCWF/SIWF Compressor Electrical Data  
Voltage utilization range is 10 percent  
200V  
460V  
575V  
575V  
HP  
10  
15  
RLA  
33  
46  
LRA  
269  
409  
RLA  
14.5  
20.5  
LRA  
117  
178  
RLA  
11.5  
16.5  
LRA  
94  
143  
Determination of minimum circuit  
ampacity (MCA).  
MCA = 1.25 x largest motor amps/VFD  
amps (FLA or RLA) + the sum of the  
remaining motor amps.  
Table ED-3. SCRF/SIRF Compressor Electrical Data  
Determination of maximum fuse size  
(MFS) and maximum circuit breaker size  
(MCB)  
MFS and MCB = 2.25 x largest motor  
amps (FLA or RLA) + the sum of the  
remaining motor amps.  
200V  
460V  
460V  
HP  
10  
15  
RLA  
36.8  
61.1  
LRA  
269  
409  
RLA  
16.3  
26  
LRA  
117  
178  
RLA  
13.2  
21.5  
LRA  
94  
143  
Table ED-4. FanWithoutVFD Electrical Data  
Units with the dual power option require  
separate MFS and MCB calculations for  
each electrical circuit:  
200V  
575V  
HP  
5
FLA  
16.1  
25.0  
32.9  
44.8  
61.0  
74.0  
87.0  
113.0  
NA  
LRA  
105  
152  
193  
290  
373  
469  
552  
718  
NA  
FLA  
6.7  
LRA  
46  
66  
FLA  
5.4  
8.2  
11.4  
16.2  
20.0  
24.2  
28.6  
38.0  
49.2  
LRA  
37  
54  
1) fans and 2) compressors.  
7.5  
10  
15  
20  
25  
30  
40  
50  
10.8  
14.2  
20.3  
25.0  
31.0  
36.0  
47.8  
62.0  
84  
66  
If the rating value calulation does not  
equal a standard over current protective  
device rating, use the next lower standard  
rating as the maximum.  
126  
162  
204  
240  
312  
390  
102  
132  
162  
192  
246  
312  
Table ED-5. Fan withVFD Electrical Data  
200V  
460V  
HP  
7.5  
10  
15  
20  
25  
30  
40  
50  
FLA  
29.0  
38.3  
42.7  
55.2  
67.8  
82.0  
108.6  
NA  
LRA  
152  
193  
290  
373  
469  
552  
718  
NA  
FLA  
LRA  
66  
84  
126  
162  
204  
240  
312  
390  
14.3  
18.1  
25.8  
32.4  
38.9  
39.0  
51.0  
61.5  
Note: Values are at the maximum VFD input rating and not the reduced motor values.  
PKG-PRC002-EN  
79  
Electrical Data SCWF/SCRF  
Table ED-6. Single Stage Electric Heat Electrical Data  
SXWF  
Size  
20  
SXRF  
Size  
-
Heat  
Kw  
18  
200V  
Amps  
50  
460V  
Amps  
21.7  
21.7  
21.7  
27.7  
27.7  
32.5  
32.5  
37.9  
37.9  
46.9  
46.9  
57.7  
57.7  
57.7  
22  
-
18  
50  
25  
29  
32  
35  
38  
42  
46  
52  
58  
65  
72  
80  
20  
25  
29  
30  
35  
-
40  
-
50  
-
18  
23  
23  
27  
27  
31.5  
31.5  
39  
39  
48  
48  
48  
50  
63.8  
63.8  
75  
75  
87.4  
87.4  
108.3  
108.3  
133.2  
133.2  
133.2  
-
60  
Note:  
Electric heat amperage should not be considered when determining minimum circuit ampacity. The current of the  
unit in the heating mode will not exceed the current of the unit in the cooling mode.  
Table ED-7. CCRC/CIRC Condenser Electrical Data  
Unit Size  
Tons  
20, 29  
Rated  
Voltage  
200  
MFS.  
MCB  
20  
# Fans  
FLA (ea.)  
4.1  
LRA (ea.)  
20.7  
9
7.2  
20.7  
9
7.2  
20.7  
9
7.2  
MCA  
17.43  
7.65  
4
4
4
6
6
6
8
8
8
460  
1.8  
15  
575  
200  
460  
575  
200  
460  
575  
1.4  
4.1  
1.8  
1.4  
4.1  
1.8  
1.4  
5.95  
15  
30  
15  
15  
40  
20  
15  
35, 40  
50, 60  
25.63  
11.25  
8.75  
33.83  
14.85  
11.55  
Note:  
All motors for CCRC/CIRC units are rated at 1 hp (.7457 kW).  
80  
PKG-PRC002-EN  
Dimensions  
and Weights  
Self-Contained  
20-38 Tons  
20-38 Ton Self-Contained  
PKG-PRC002-EN  
81  
Dimensions  
and Weights  
Self-Contained  
40-80 Ton  
40-80 Ton Self-Contained  
82  
PKG-PRC002-EN  
Dimensions  
and Weights  
Self-Contained  
20-80 Tons  
Detail A  
Electrical Connections  
40 3/8” (20-38Ton)  
(1026 mm)  
Detail B  
Discharge Dimensions  
Discharge Dimensions - English - (inches)  
Unit Tons  
SXWF 20-25  
SXRF 20  
A
B
C
D
3
1
1
3
30 /8 26 /8 21 /4 25 /4  
7
1
3
SXWF 29-32  
SXRF 25-29  
SXWF 35-38  
SXRF 30-35  
SXWF 42-80  
SXRF 40-60  
31 /8 23 /2 23 1/8 20 /8  
1
1
1
3
30 /2 26 /8 21 /4 25 /4  
1
1
7
1
43 /8 33 /2 28 /8 34 /2  
Discharge Dimensions - Metric - (mm)  
Unit Tons  
A
B
C
D
SXWF 20-25  
772  
664  
540  
654  
SXRF 20  
SXWF 29-32  
SXRF 25-29  
SXWF 35-38  
SXRF 30-35  
SXWF 42-80  
SXRF 40-60  
810 597  
775 664  
1095 851  
587  
540  
733  
518  
654  
876  
PKG-PRC002-EN  
83  
Dimensions  
and Weights  
Air-Cooled  
Condenser  
CCRC Unit Dimensions  
Unit Dimensions - English - (inches)  
UnitTons  
AA  
AB  
7' - 4  
10' - 10  
AC  
1
CCRC/CIRC 20, 29  
CCRC/CIRC 35, 40  
CCRC/CIRC 50, 60  
70  
70  
70  
/
8
8
7' - 4  
7' - 4  
7' - 4  
(Optional) Low  
Ambient Damper  
(One Damper Per Circuit)  
1
1
3
/
/
/
4
8
14' - 8  
Refrigerant Line  
Connections  
Unit Dimensions - Metric (mm)  
UnitTons  
AA  
AB  
AC  
2235  
2235  
CCRC/CIRC 20, 29  
CCRC/CIRC 35, 40  
CCRC/CIRC 50, 60  
1781  
1781  
1781  
2235  
3321  
4470  
AA  
2235  
FrontalView  
AC  
CCRC/CIRC 20 and 2
AB  
(Optional) Low  
Ambient Damper  
(One Damper Per Circuit)  
Refrigerant Line  
Connections  
AA  
Frontal View  
AC  
AB  
CCRC/CIRC 35 and 40  
(Optional) Low  
Ambient Damper  
(One Damper Per Circuit)  
Refrigerant Line  
Connections  
AA  
Frontal View  
AB  
84  
PKG-PRC002-EN  
Dimensions  
and Weights  
Air-Cooled  
Condenser  
Refrigerant and Electrical Connections  
CIRCUIT 2  
CIRCUIT 1  
Front View Looking at Control Panel  
Electrical Connections - English - (inches)  
Unit  
A
B
C
D
CCRC/CIRC 20-32  
CCRC/CIRC 35-40  
CCRC/CIRC 50-60  
6 3/8  
6 3/8  
6 3/8  
12 1/4 15 1/4 18 1/4  
12 1/4 15 1/4 18 1/4  
12 1/4 15 1/4 18 1/4  
Electrical Connections - Metric - (mm)  
Unit  
A
B
C
D
CCRC/CIRC 20-32  
CCRC/CIRC 35-40  
CCRC/CIRC 50-60  
162  
162  
162  
311  
311  
311  
387  
387  
387  
464  
464  
464  
Refrigerant Connections - English - (inches)  
Unit  
E
F
G
H
J
K
L
M
N
5
5
/
CCRC/CIRC 20-32  
CCRC/CIRC 35-40  
CCRC/CIRC 50  
66 7/8 14 3/8 18 1/2 24 3/4 29  
66 7/8 14 3/8 18 1/2 24 3/4 29  
66 7/8 14 3/8 18 1/2 24 3/4 29  
66 7/8 14 3/8 18 1/2 24 3/4 29  
/
1 1/8  
1 1/8  
1 1/8  
1 5/8  
1 1/8  
1 3/8  
1 5/8  
1 5/8  
8
8
5
5
7
7
/
/
/
/
8
8
8
8
7
/
8
7
/
CCRC/CIRC 60  
8
Refrigerant Connections - Metric - (mm)  
Unit  
E
F
G
H
J
K
L
M
16  
22  
22  
22  
N
CCRC/CIRC 20-32  
CCRC/CIRC 35-40  
CCRC/CIRC 50  
CCRC/CIRC 60  
1699 365  
1699 365  
1699 365  
1699 365  
470  
470  
470  
470  
629  
629  
629  
629  
737  
737  
737  
737  
16  
16  
16  
22  
29  
29  
29  
41  
29  
35  
41  
41  
PKG-PRC002-EN  
85  
Dimensions  
and Weights  
Self-Contained  
Heating Coils  
Hot Water Coil  
Main Control Panel  
C
B
A
Hot Water Outlet Connection  
Notes:  
D
E
1. All coils are factory  
Hot Water Inlet Connection  
mounted, piped, and  
wired.  
Air Inlet  
G
F
2. All piping connections  
are 1-1/2” (38.1mm)  
female NPT fittings.  
H
Hot Water Coil Piping Locations - English (inches)  
A
B
C
18  
18  
D
E
F
G
H
Unit Sizes 20 - 38  
Unit Sizes 42 - 80  
60 3/8  
72 7/8  
82 7/8  
105 1/4  
20 5/8  
24 1/2  
8 1/8  
10 3/4  
22 3/8  
13 1/4  
3 5/8  
3 5/8  
8 1/4  
8 1/4  
Hot Water Coil Piping Locations - Metric (mm)  
A
B
C
D
E
F
G
H
Unit Sizes 20 - 38  
Unit Sizes 42 - 80  
1534  
1851  
2105  
2680  
457  
457  
524  
404.9  
206  
273  
568  
337  
92  
92  
210  
210  
Steam Coil  
Main Control Panel  
C
B
A
H
VacuumTrap Connection  
Condensate Return  
Notes:  
1. All coils are factory  
mounted, piped, and  
wired.  
2. All piping connections  
are 1-1/2” (38.1mm)  
female NPT fittings.  
J
VacuumTrap Connection  
Steam Inlet Connection  
M
N
Air Inlet  
Condensate Return  
F
K
L
Piping Locations For Steam Coils - English (inches)  
A
B
C
D
-
-
E
-
-
F
G
-
-
H
3
3
J
K
L
M
N
Unit Sizes 20 - 38  
Unit Sizes 42 - 80  
60 3/8 82 7/8 18  
72 7/8 105 1/4 18  
22 3/8  
13 1/4  
18 1/2 3 7/8  
22 1/8 6 3/8  
5
4 3/8  
4 3/8  
1 1/4  
1 1/4  
5 3/8  
Piping Locations For Steam Coils - Metric (mm)  
A
B
C
D
-
-
E
-
-
F
568  
337  
G
-
-
H
76  
76  
J
470  
562  
K
98  
162  
L
127  
137  
M
111  
111  
N
32  
32  
Unit Sizes 20 - 38  
Unit Sizes 42 - 80  
1534 2105 457  
1851 2680 457  
86  
PKG-PRC002-EN  
Dimensions  
and Weights  
Flexible Horizontal  
Discharge Plenum  
Flexible Horizontal  
Discharge Plenum  
A
C
B
Plenum Dimensions - English - (inches)  
A
B
C
Weight  
325 lbs.  
430 lbs.  
705 lbs.  
390 lbs.  
540 lbs.  
705 lbs.  
Low  
Std.  
Ext.  
Low  
Std.  
Ext.  
64 7/8  
64 7/8  
64 7/8  
80 3/8  
80 3/8  
80 3/8  
24 5/8  
32 3/  
45 8  
95 7/8  
95 7/8  
95 7/8  
119 7/8  
119 7/8  
119 7/8  
Unit Sizes 20-38  
Unit Sizes 42-80  
21 1/8  
28 5/  
45 8  
Plenum Dimensions - Metric - (mm)  
A
B
C
Weight  
147.4 kg  
195.0 kg  
320.0 kg  
176.9 kg  
244.9 kg  
320.0 kg  
Low  
Std.  
Ext.  
Low  
Std.  
Ext.  
1648  
1648  
1648  
2042  
2042  
2042  
625  
822  
1143  
537  
727  
1143  
2435  
2435  
2435  
3045  
3045  
3045  
Unit Sizes 20-38  
Unit SizesI 42-80  
PKG-PRC002-EN  
87  
Dimensions  
and Weights  
Airside  
Economizer  
Airside  
Economizer  
88  
PKG-PRC002-EN  
Dimensions  
and Weights  
Airside  
Economizer  
Airside Economizer Dimensions - English - (inches)  
Unit Model  
20 SXWF  
A
44  
B
74  
C
D
E
F (1)  
F (2)  
G (1)  
23 1/4  
G (2)  
20 1/2  
H (1) H (2)  
J
K
L
16  
M
22 3/8  
81 3/4  
8 3/4  
66 3/4  
49 3/4  
9 3/4  
7 1/4  
7 1/4  
9 3/4  
4 7/8  
4 7/8  
2 1/2  
6 7/8  
1 7/8  
11 1/8 20 1/2 22 1/4  
11 1/8 20 1/2 22 1/4  
11 1/8 20 1/2 22 1/4  
11 1/8 20 1/2 22 1/4  
11 1/8 20 1/2 22 1/4  
11 1/8 20 1/2 22 1/4  
49 3/4  
20 SXRF  
25 SXRF  
22 SXWF  
29 SXWF  
29 SXRF  
32 SXWF  
30 SXRF  
35 SXRF  
44  
44  
44  
44  
44  
74  
74  
74  
74  
74  
22 3/8  
22 3/8  
22 3/8  
22 3/8  
22 3/8  
81 3/4  
81 3/4  
81 3/4  
81 3/4  
81 3/4  
8 3/4  
8 3/4  
8 3/4  
8 3/4  
8 3/4  
8 7/8  
8 7/8  
8 7/8  
68 5/8  
68 5/8  
74 1/4  
73 1/2  
73 1/2  
83 5/8  
94 1/8  
96 5/8  
49 3/4  
49 3/4  
62 3/4  
62 3/4  
62 3/4  
63 1/2  
63 1/2  
63 1/2  
28 1/8  
28 1/8  
23 1/4  
33  
20 1/2  
20 1/2  
20 1/2  
20 1/2  
20 1/2  
26  
16  
49 3/4  
49 3/4  
62 3/4  
62 3/4  
62 3/4  
63 1/2  
63 1/2  
63 1/2  
16  
9 1/2  
9 1/2  
9 1/2  
20 3/8  
20 3/8  
20 3/8  
35 SXWF  
38 SXWF  
42 SXWF  
33  
57 3/8 86 1/2  
57 3/8 86 1/2  
57 3/8 86 1/2  
13 1/4 104 3/8  
13 1/4 104 3/8  
13 1/4 104 3/8  
33  
15  
15  
26  
26  
24 3/4  
24 3/4  
19  
40 SXRF  
46 SXWF  
28 1/8  
52  
26  
50 SXRF  
37 1/2  
9 1/4 37 1/2  
60 SXRF  
52-80 SXWF  
Airside Economizer Dimensions - Metric - (mm)  
Unit Model  
20 SXWF  
A
1118  
B
1880  
C
568  
D
2076  
E
222  
F (1)  
1695  
F (2)  
1264  
G (1)  
591  
G (2)  
521  
H (1) H (2)  
J
521  
K
565  
L
406  
M
1264  
248  
184  
184  
248  
124  
124  
64  
283  
283  
283  
283  
283  
283  
381  
381  
235  
20 SXRF  
1118 1880  
1118 1880  
568  
568  
568  
568  
568  
337  
337  
337  
2076  
2076  
2076  
2076  
2076  
2651  
2651  
2651  
222  
222  
222  
222  
222  
225  
225  
225  
1743  
1743  
1886  
1867  
1867  
2124  
2390  
2454  
1264  
1264  
1594  
1594  
1594  
1613  
1613  
1613  
714  
714  
591  
838  
838  
838  
714  
1321  
521  
521  
521  
521  
521  
660  
660  
953  
521  
521  
521  
521  
521  
660  
660  
953  
565  
565  
565  
565  
565  
629  
629  
483  
406  
406  
241  
241  
241  
518  
518  
518  
1264  
1264  
1594  
1594  
1594  
1613  
1613  
1613  
22 SXWF  
29 SXWF  
29 SXRF  
32 SXWF  
30 SXRF  
35 SXRF  
35 SXWF  
38 SXWF  
1118  
1880  
1118 1880  
1118 1880  
1457 2197  
1457 2197  
1457 2197  
42 SXWF  
40 SXRF  
46 SXWF  
175  
48  
50 SXRF  
60 SXRF  
52-80 SXWF  
PKG-PRC002-EN  
89  
Dimensions  
and Weights  
Field-Installed  
Zone Sensors  
(114 mm)  
(114 mm)  
(70 mm)  
(70 mm)  
Zone Temperature Sensor W/Timed  
Override Buttons  
Dual Setpoint, Manual/Automatic  
Changeover Sensor With System Function  
BAYSENS013  
Lights  
BAYSENS010  
(70 mm)  
(114 mm)  
(114 mm)  
(70 mm)  
(70 mm)  
Dual Setpoint, Manual/Automatic  
Changeover Sensor  
BAYSENS008  
Zone Temperature Sensor W/Timed  
Override Buttons and Local Setpoint  
Adjustment  
NOTE:Remote sensors are available for use with all zone  
sensors to provide remote sensing capabilities.  
BAYSENS014  
90  
PKG-PRC002-EN  
Dimensions  
and Weights  
Field-Installed  
Zone Sensors  
(114 mm)  
(114 mm)  
(70 mm)  
(70 mm)  
Single Setpoint Sensor With System  
Function Lights  
Zone Temperature Sensor Only  
BAYSENS017  
BAYSENS021  
(95 mm)  
(95mm)  
(140 mm)  
(140mm)  
Programmable Night Setback Sensor  
BAYSENS019B  
Programmable Night-Setback Sensor  
BAYSENS020B  
PKG-PRC002-EN  
91  
Dimensions  
and Weights  
Service  
Clearances  
Service/Code Clearance Requirements  
Self-Contained Models  
SCWF/SIWF/SCRF/SIRF  
Side  
Distance  
42 in. (1066 mm) (20-38Ton)  
48 in. (1219 mm) (42-80 Ton)  
36 in. (914 mm)  
Purpose  
NEC code requirement  
Fan service/removal  
Front  
Left  
Filter, refrigeration and waterside component service  
Non VFD w/ open return  
Right  
9 in. (229 mm)  
18 in. (457 mm)  
Non VFD w/ ducted return  
w/ VFD 7.5 to 20 HP  
24 in. (610 mm)  
36 in. (914 mm)  
18 in. (457 mm)  
w/ VFD 25 to 50 HP  
Provides uniform airflow  
Inlet  
18(457.2mm)  
Minimum  
Air Inlet  
36(914.4mm)  
Minimum  
SeeTable  
Control  
Panel  
42” (1066.8mm) (20-38Ton)  
Minimum  
48” (1219mm) (42-80Ton)  
Top View  
SCWF/SCRF/SIWF/SIRF  
92  
PKG-PRC002-EN  
Dimensions  
and Weights  
Service  
Clearances  
96” (2132 mm)  
Remote Air-Cooled Condensers  
Models CCRC/CIRC  
Top View  
C
D
B
A
CCRC/CIRC 20, 29  
48” (1066 mm)  
48” (1066 mm)  
Control  
Panel  
96” (2132 mm)  
96” (2132 mm)  
Top View  
CCRC/CIRC 35, 40  
F
E
C
D
B
A
96” (2132 mm)  
48” (1066 mm)  
Control  
Panel  
96” (2132 mm)  
96” (2132 mm)  
Top View  
CCRC/CIRC 50, 60  
G
H
F
B
A
C
48” (1066 mm)  
48” (1066 mm)  
D
E
Control  
Panel  
96” (2132 mm)  
PKG-PRC002-EN  
93  
Dimensions  
and Weights  
Weights  
Table W-1. Unit Weights - SCWF/SCRF/SIWF/SIRF  
2-Row  
Waterside  
Economizer  
lbs. (kg)  
4-Row  
Unit  
Size  
Base  
Airside  
Economizer  
lbs. (kg)  
Waterside  
Economizer  
lbs. (kg)  
Heating  
Coil Box  
lbs. (kg)  
Weight  
lbs. (kg)  
SCWF/SIWF  
20  
22  
25  
29  
32  
35  
38  
42  
46  
52  
58  
65  
72  
80  
3010(1365)  
3010(1365)  
3080(1400)  
3300(1500)  
3490(1585)  
3610(1640)  
3710(1685)  
4560(2070)  
4650(2110)  
4970(2255)  
5220(2365)  
5430(2465)  
5550(2520)  
5940(2695)  
430 (195)  
430 (195)  
430 (195)  
500 (225)  
500 (225)  
500 (225)  
500 (225)  
640 (290)  
640 (290)  
700 (315)  
700 (315)  
800 (360)  
800 (360)  
800 (360)  
140 (65)  
140 (65)  
140 (65)  
190 (85)  
340 (155)  
340 (155)  
340 (155)  
390 (175)  
390 (175)  
505 (230)  
505 (230)  
505 (230)  
505 (230)  
665 (300)  
665 (300)  
665 (300)  
665 (300)  
665 (300)  
460 (210)  
460 (210)  
460 (210)  
460 (210)  
460 (210)  
460 (210)  
460 (210)  
600 (270)  
600 (270)  
600 (270)  
600 (270)  
600 (270)  
600 (270)  
600 (270)  
190 (85)  
280 (130)  
280 (130)  
255 (115)  
255 (115)  
335 (150)  
335 (150)  
335 (150)  
335 (150)  
335 (150)  
SCRF/SIRF  
20  
25  
29  
30  
35  
40  
50  
60  
2920(1325)  
3140(1425)  
3330(1510)  
3370(1530)  
3470(1575)  
4410(2000)  
4980(2260)  
5620(2550)  
430 (195)  
500 (225)  
500 (225)  
500 (225)  
500 (225)  
640 (290)  
700 (315)  
800 (360)  
140 (65)  
190 (85)  
190 (85)  
280 (130)  
280 (130)  
255 (115)  
335 (150)  
335 (150)  
340 (155)  
390 (175)  
390 (175)  
505 (230)  
505 (230)  
505 (230)  
665 (300)  
665 (300)  
460 (210)  
460 (210)  
460 (210)  
460 (210)  
460 (210)  
600 (270)  
600 (270)  
600 (270)  
Notes:  
1. All unit weights include refrigerant, water, inlet guide vanes and controllers, electric heat and valves.  
2. Add 150 lbs. to total weight to obtain approximate shipping weight.  
3. Flexible horizontal discharge plenum option weights:  
45-inch plenum = 705 lbs.  
Standard height plenum = 430 lbs.  
Low height plenum = 325 lbs.  
Table W-2. Unit Weights - CCRC/CIRC  
Table W-3.Variable Frequency Drive Weights  
Shipping  
Weight  
lbs (kg).  
Operating  
Weight  
lbs.(kg)  
Motor HP  
Weight  
Voltage  
Unit  
Size  
lbs. (kg)  
26 (12)  
15 (7)  
CCRC/CIRC 20  
CCRC/CIRC 29  
CCRC/CIRC 32  
CCRC/CIRC 35  
CCRC/CIRC 40  
CCRC/CIRC 50  
CCRC/CIRC 60  
2030 (920)  
2084 (945)  
2138 (970)  
3018 (1370)  
3072 (1395)  
3995 (1810)  
4275 (1940)  
1906 (865)  
1960 (890)  
2014 (915)  
2833 (1285)  
2887 (1310)  
3695 (1675)  
3975 (1805)  
7.5  
7.5  
10  
10  
15  
15  
20  
20  
25  
200V  
460V  
200V  
460V  
200V  
460V  
200V  
460V  
200V  
26 (12)  
26 (12)  
75 (34)  
26 (12)  
75 (34)  
31 (14)  
126 (57)  
25  
30  
30  
40  
40  
50  
460V  
200V  
460V  
200V  
460V  
460V  
75 (34)  
126 (57)  
75 (34)  
126 (57)  
75 (34)  
126 (57)  
94  
PKG-PRC002-EN  
Mechanical  
Specifications  
Self-Contained  
with intertwined circuiting and no more  
than 12 fins per inch.  
efficiency.  
Signature Series Self-  
Contained Units  
Cabinet  
The unit framework shall be formed  
structural steel members of 14-gauge  
galvanized steel. Exterior panels shall be  
fabricated from 18-gauge galvanized  
steel. The fan and compressor sections  
shall be insulated with ¾-inch (19 mm) of  
1.75 lb./cu. ft. (28 kg./cu. ft.) density  
fiberglass insulation.  
Supply fan motor shall have a standardT-  
frame. All drive components shall be  
accessible without using scaffolds or  
ladders.  
The drain pan shall be positively sloped in  
all directions to ensure proper condensate  
removal. The drain pan shall be fabricated  
of galvanized steel and insulated with ¾-  
inch (19 mm) of 1-lb. (0.5 kg) density  
fiberglass. Drain piping, including a trap  
with cleanout, shall be provided with a  
single-point connection to the units  
exterior.  
The entire fan assembly, including drive  
components, shall be mounted on a  
common base. The fan base shall be  
isolated inside the unit. The entire  
assembly shall be statically and  
dynamically balanced at the factory.  
Refrigerant Circuit (SCWF only)  
Filters  
The unit shall be provided with removable  
panels to allow service access to  
compressors, condensers, fan motor, fan  
bearings, coils, and valves. Removable  
panels shall be secured with quick-acting  
fasteners. The refrigerant sight glasses  
shall be accessible during operation. The  
control panel door shall have lift-off  
hinges.  
Refrigerant circuits shall be independent  
and completely piped including sight  
glasses, distributors, thermal expansion  
valves with adjustable superheat and  
external equalizer, and high pressure  
relief valves with ½-inch (13 mm) flare  
connection. Filter driers ship loose for field  
installation. Unit shall be provided with  
adequate means of frost control.The  
circuits shall be factory dehydrated,  
charged with oil and refrigerant 22.  
Compressors shall be mounted on  
rubber-in-shear isolators for vibration  
isolation.  
Two-inch (51 mm) throwaway fiberglass  
filters shall be provided for installation  
during construction.  
Unit Controls - DDC  
Microprocessor controls shall be provided  
to control all unit functions. The control  
system shall be suitable to control CV or  
VAV applications.The controls shall be  
factory-installed and mounted in the main  
control panel. All factory-installed controls  
shall be fully commissioned (run tested) at  
the factory.The unit shall have a human  
interface panel with 16-key keypad, a  
two line, 40 character clear language  
(English, French, or Spanish) display as  
standard to provide the operator with full  
adjustment and display of control data  
functions. The unit controls shall be used  
as a stand-alone controller or as part of a  
building management system involving  
multiple units.  
Compressors  
Units shall have multiple compressors  
with independent circuits for water-cooled  
units and manifolded circuits for air-  
cooled units. Compressors shall be  
manufactured by the unit manufacturer.  
Scroll compressors shall be heavy duty  
suction cooled type with suction screen,  
centrifugal oil pump with dirt separator, oil  
charging valve, and oil sight glass.  
Protective devices for low pressure, high  
pressure, and motor temperature shall be  
provided. The compressors shall be  
mounted on isolators for vibration  
isolation.  
Refrigerant Circuit (SCRF/SIRF only)  
Two refrigerant circuits shall be piped to  
the units exterior.The refrigerant piping  
includes filter driers (for field installation),  
sight glasses, distributors, thermal  
expansion valves with adjustable  
superheat and external equalizer. Unit  
shall be provided with adequate means of  
frost control. The circuits shall be factory  
tested, dehydrated and then charged with  
dry nitrogen. Compressors shall be  
mounted on rubber-in-shear isolators for  
vibration isolation.  
The unit shall be equipped with a  
complete microprocessor control system.  
This system shall consist of temperature  
and pressure (thermistor and static  
pressure transducer) sensors, printed  
circuit boards (modules) and a unit  
mounted human interface panel. Modules  
(boards) shall be individually replaceable  
for service ease. All microprocessors,  
boards, and sensors shall be factory  
mounted, wired, and tested.  
Condenser (SCWF/SIWF only)  
One condenser shall be provided for each  
compressor.The condensers shall be  
shell-and-tube design with removable  
heads and mechanically cleanable tubes.  
Tubes shall be ¾-inch (19mm) OD and  
constructed of copper. Condenser  
waterside working pressure shall be 400  
psig. All condenser water piping including,  
cleanouts, shall be factory installed to  
provide single connections for water inlet  
and outlet.  
Supply Fan  
The supply fan shall be a single forward  
curved medium pressure fan secured to a  
solid steel shaft with grease lubricated  
bearings designed for 200,000 hours.  
Both fan bearings shall have greaselines  
extended to a common location. The drive  
components shall include fixed pitch  
sheaves and multipleV-belt sized for  
130% nominal motor horsepower.The  
supply fan motor shall have a service  
factor of 1.15. The supply fan motor shall  
be either:  
The microprocessor boards shall be  
stand-alone DDC controls not dependent  
on communications with an on-site PC or  
building management network. The  
microprocessors shall be equipped with  
on-board diagnostics, indicating that all  
hardware, software, and interconnecting  
wiring are in proper operating condition.  
The modules (boards) shall be protected  
to prevent RFI and voltage transients  
from affecting the boards circuits. All field  
Evaporator  
The evaporator coil shall be seamless  
copper tubes expanded into aluminum  
fins.Tubes shall be ½-inch (13mm) OD  
with internally enhanced surfaces. Coil  
shall have staggered tube arrangement  
Standard efficiency open drip-proof  
Premium efficiency open drip-proof  
Totally enclosed fan cooled standard  
PKG-PRC002-EN  
95  
Mechanical  
Air-Cooled  
Specifications Condenser  
wiring shall be terminated at a separate,  
clearly marked terminal strip. Direct field  
wiring to the I/O boards is not acceptable.  
The microprocessors memory shall be  
nonvolatile EEPROM type requiring no  
battery or capacitive backup, while  
maintaining all data.  
Remote Air-Cooled Condenser  
Cabinet  
The unit framework shall be formed  
structural steel members of 14-gauge  
galvanized steel. Panels and access doors  
shall be 18-gauge galvanized steel. The  
unit exterior shall be phosphatized and  
finished with air-dried enamel paint.  
Protective Coating (Option)  
Unit  
The units interior and exterior shall have  
a 4 to 6 mil coat of protective coating  
applied with an air-dry process.  
Condenser Coils  
The condenser coil shall have a 4 to 6 mil  
coat of protective coating applied by a  
multiple dip-and-bake process.  
Zone sensors shall be available in several  
combinations with selectable features  
depending on sensor.  
Refrigerant Circuits and Controls  
All sizes shall have dual refrigerant  
circuits and shall include an integral  
subcooling circuit for each circuit. All  
necessary controls to run unit fans shall  
be factory installed. The control panel  
shall include fan motor contactors,  
terminal block connection for compressor  
interlock, and 115-volt control power  
transformer.  
Low Ambient Operation Option  
Standard ambient control allows  
The human interface panel’s keypad  
display character format shall be 40  
characters x two lines. The character font  
shall be 5 x 7 dot matrix plus cursor.The  
display shall be supertwist liquid crystal  
display (LCD) with blue characters on a  
gray/green background which provides  
high visibility and interface ease. The  
display format shall be in clear language:  
English, French, or Spanish.  
operation down to 45 F (-7.2 C) by cycling  
the condenser fans. Low ambient control  
damper shall allow the unit to operate  
down to 0 F (-17.8 C) by utilizing additional  
fan cycling and an external damper  
assembly.The low ambient control  
damper shall include a 16-gauge damper  
assembly.The damper is controlled by  
the air-cooled unit’s DDC controller.  
Condenser Coils  
The condenser coil arrangement shall be  
slab type. Coils shall be seamless  
3/8-inch (10mm) OD copper tubes  
expanded into aluminum fins. Each circuit  
shall include an integral subcooler.The  
coil shall be leak tested at 450 psig air  
pressure.  
The keypad shall be equipped with 16  
individual touch sensitive membrane key  
switches. The switches shall be divided  
into four separate sections and password  
protected to prevent tampering by  
unauthorized personnel. The six main  
menus shall be STATUS, SETPOINTS,  
DIAGNOSTICS, SETUP, CONFIGURATION,  
and SERVICE MODE.  
Louvered Coil Guards Option  
The unit coils shall be covered with a  
factory installed decorative louvered grill  
type panel for protection.  
Agency Listing  
The unit shall have the US/Canada  
Underwriters Laboratory agency listing.  
Condenser Fans and Motor  
Vertical discharge direct drive fans shall  
be statically and dynamically balanced at  
the factory. Motors shall be three-phase  
with permanently lubricated ball bearings,  
built-in current and thermal overload  
protection and weathertight rain slinger  
over the fan shaft.  
Agency Listing  
The unit shall have the US/Canada  
Underwriters Laboratory agency listing.  
96  
PKG-PRC002-EN  
Mechanical  
Specifications Options  
seamless copper tubes expanded into  
the motor to meet the dynamic  
Self-Contained Options  
Air Volume/Temperature Control  
aluminum fins. The evaporator and  
economizer coils share a common sloped  
(IAQ) drain pan. Drain pan options are  
either galvanized or stainless steel and  
insulated and internally trapped.  
requirements at the motor shaft and  
meet the system static. Other control  
components include a discharge air  
microprocessor controller and discharge  
air sensor.The microprocessor controller  
coordinates the economizer control and  
the stages of cooling with discharge air  
temperature reset capabilities. Includes  
factory installed and tested variable  
frequency drive (VFD) to provide supply  
fan motor speed modulation. The VFD  
receives 0-10vdc signal from the unit  
microprocessor based upon supply static  
pressure and causes the drive to  
accelerate or decelerate as required to  
maintain the supply static pressure  
setpoint.  
• ZoneTemperature Control  
This option includes a zone sensor,  
microprocessor unit control module, a  
microprocessor compressor controller,  
and a unit-mounted human interface  
panel. The unit operates at a design  
airflow based on the fan and motor drive  
selections.  
The waterside economizer coil options  
have either two or four rows with no  
more than 12 fins per inch. The tubes are  
arranged in a staggered pattern to  
maximize heat transfer.The coil has  
round copper supply and return headers  
with removable cleanout and vent plugs.  
The optional mechanically cleanable  
economizer has removable cast iron  
headers to allow easy mechanical  
cleaning of the tubes. The waterside  
working pressure is rated for 400 psig  
(2758 kPa).  
• Supply AirTemperature Control  
with Inlet GuideVanes  
This option controls supply air  
temperature to the specified supply air  
cooling setpoint by modulating the  
economizer option and/or staging  
mechanical cooling on and off as  
required. Control components include a  
discharge air microprocessor controller,  
discharge air sensor, pressure sensor,  
and inlet guide vanes. The  
microprocessor controller coordinates  
the economizer control and the cooling  
stages with zone or outdoor air reset  
capabilities and an adjustable control  
band to fine-tune the control to specific  
applications. The inlet guide vanes (IGV)  
operate with the self-contained unit to  
control duct static pressure. The IGV  
option includes vanes and static pressure  
controls.  
Supply Air Temperature Control With  
Variable Frequency Drive with Bypass  
Manual bypass control provides full  
nominal airflow and zone temperature  
control in the event of a drive failure. The  
VFD with bypass is factory mounted  
completely wired and tested. A motor  
overload relay and fuses are provided to  
properly size motor protection during  
both drive and bypass modes.  
Waterside Economizer  
The waterside economizer takes  
advantage of cooling tower water to  
either pre-cool the entering air to aid the  
mechanical cooling process or, provides  
total system cooling if the water  
temperature is low enough. Waterside  
economizing enables when the units  
entering water temperature is below the  
units entering mixed air temperature by  
a minimum of 4 F plus the economizers  
approach temperature. The approach  
temperature default is 4 F and is  
Side View of Unit with Waterside  
Economizer with Removable Headers  
adjustable from 0 to 9 F.Waterside  
economizing disables when the units  
entering water temperature is not below  
the units entering mixed air temperature  
by at least the water economizer  
approach temperature. The economizer  
acts as the first stage of cooling. If the  
economizer is unable to maintain the  
supply air setpoint, the unit control  
module brings on compressors as  
required to meet the setpoint.  
The waterside economizer includes a coil,  
modulating valves, controls, and piping  
with cleanouts. All components are  
factory installed in the unit cabinet. The  
coil construction is ½-inch (13mm) OD  
Inlet Guide Vanes  
• Supply AirTemperature Control  
With Variable Frequency Drive  
This option controls theVAV self-  
contained unit from the discharge air  
temperature using a factory mounted  
variable frequency drive (VFD). The VFD  
safely varies the fan motor speed to allow  
PKG-PRC002-EN  
97  
Mechanical  
Specifications  
Options  
Airside Economizer  
purposes. Also, the ability to alter the  
outside air damper position to  
allow using outside air for the first stage  
of cooling, in occupied or unoccupied  
mode and when ambient conditions are  
favorable for economizing. Inherent in the  
unit controller is the ability to suppress  
the setpoint below the normal unit  
setpoint. This allows the building to  
improve comfort levels when possible,  
and at the same time, optimize building  
mechanical cooling operation for peak  
operating efficiency. A factory-installed  
control board, with outside and return air  
temperature and relative humidity  
sensors, are provided for monitoring  
outside and return air.The sensors are  
field installed. Economizer operation  
enables when the outside air enthalpy is  
3 BTUs/lb. less than the return air  
enthalpy. During occupied mode, the  
outside air damper opens to 15%  
(adjustable 0-100%) for ventilation  
purposes. Also, the ability to alter the  
outside air damper position to  
Units with the airside economizer option  
are equipped with the necessary control  
sequences to use outside air for the first  
stage of cooling, in occupied or  
compensate forVAV supply air  
modulation is inherent in the unit controls,  
and can be enabled by the operator.  
unoccupied mode and when ambient  
conditions are favorable for economizing.  
Inherent in the unit controller is the ability  
to suppress the setpoint below the normal  
unit setpoint. This allows the building to  
improve comfort levels when possible,  
and at the same time, optimize building  
mechanical cooling operation for peak  
operating efficiency. An outside air  
temperature and relative humidity sensor  
are provided to allow monitoring of  
reference enthalpy and are field installed.  
Economizer operation enables when the  
outside air enthalpy is less than 25 BTUs/  
lb. default (adjustable 19-28 BTUs/lb.).  
During occupied mode, the outside air  
damper opens to 15% (adjustable 0-  
100%) for ventilation purposes. Also, the  
ability to alter the outside air damper  
position to compensate forVAV supply air  
modulation is inherent in the unit controls,  
and can be enabled by the operator.  
The mixing box fabrication is 16-gauge  
galvanized steel. Opposed low leak  
damper blades are fabricated from 16-  
gauge galvanized steel and rotate on  
rustproof nylon bushings. A factory  
installed 24V modulating spring return  
actuator controls both damper positions.  
•StandardTwo-Position Damper  
Interface  
Units with the two-position damper  
interface are provided with a 0-10 VDC  
control output suitable for controlling a  
field-provided modulating actuator. In  
occupied mode, the output drives to the  
maximum position.  
• Airside Economizer Interface  
Units with airside economizer interface  
are equipped with the necessary control  
sequences to allow using outside air for  
the first stage of cooling, in occupied or  
unoccupied mode and when ambient  
conditions are favorable for economizing.  
Inherent in the unit controller is the ability  
to suppress the setpoint below the normal  
unit setpoint. This allows the building to  
improve comfort levels when possible,  
and at the same time, optimize building  
mechanical cooling operation for peak  
operating efficiency. An outside air  
temperature and relative humidity sensor  
are provided for field installation to  
monitor reference enthalpy. Economizer  
operation enables when the outside air  
enthalpy is less than 25 BTUs/lb.  
compensate forVAV supply air  
modulation is inherent in the unit  
controls, and can be enabled by the  
operator. An analog 2-10VDC output  
(adjustable (0-10 VDC) is provided to  
modulate the field-provided 30-second  
damper actuators (adjustable 1-255  
seconds).  
The mixing box fabrication is 16-gauge  
galvanized steel. Opposed low leak  
damper blades are fabricated from 16-  
gauge galvanized steel and rotate on  
rustproof nylon bushings. A factory  
installed 24V modulating spring return  
actuator controls both damper positions.  
Basic Water Piping  
This option is available on units without a  
waterside economizer and with  
condenser water applications above 54 F  
(12.2 C) that do not require condensing  
pressure control. Left hand water  
connections and piping are extended to  
the unit exterior. Manifold piping is  
factory installed.  
• Comparative Enthalpy Control  
Units with comparative enthalpy control  
are equipped with the necessary control  
sequences to allow using outside air for  
the first stage of cooling, in occupied or  
unoccupied mode and when ambient  
conditions are favorable for economizing.  
Inherent in the unit controller is the ability  
to suppress the setpoint below the normal  
unit setpoint. This allows the building to  
improve comfort levels when possible,  
and at the same time, optimize building  
mechanical cooling operation for peak  
operating efficiency. A factory-installed  
control board, with field-installed outside  
and return air temperature and relative  
humidity sensors, allows monitoring of  
outside and return air. Economizer  
(adjustable 19-28 BTUs/lb). During  
Intermediate Water Piping  
This option provides condensing  
occupied mode, the outside air damper  
opens to 15% (adjustable 0-100%) for  
ventilation purposes. Also, the ability to  
alter the outside air damper position to  
compensate forVAV supply air  
temperature control when the unit is  
configured (user defined at the HI) for  
variable water flow with or without a  
waterside economizer. A two-way  
modulating control valve is wired and  
installed in the unit to maintain a specific  
range of water temperature rise through  
the condenser when entering fluid  
temperature is less than 58 F (15 C). This  
option allows the compressor to operate  
with entering fluid temperature down to  
35 F (2 C). The minimum valve position to  
maintain minimum condenser flow rates  
is user-defined at the human interface.  
This valve drives closed if the unit shuts  
down or if a power failure occurs.  
PKG-PRC002-EN  
modulation is inherent in the unit controls,  
and can be enabled by the operator. An  
analog 2-10 VDC output (adjustable (0-10  
VDC) is provided to modulate the field-  
provided 30 second damper actuators  
(adjustable 1-255 seconds).  
• Airside Economizer Interface with  
Comparative Enthalpy  
Units with airside economizer interface  
and comparative enthalpy are equipped  
with the necessary control sequences to  
operation enables when the outside air  
enthalpy is 3 BTUs/lb. less than the return  
air enthalpy. During occupied mode, the  
outside air damper opens to 15%  
(adjustable 0-100%) for ventilation  
98  
Mechanical  
Specifications Options  
Waterside Economizer Flow Control  
Units equipped with a waterside  
economizer can be set from the human  
interface panel for variable or constant  
water flow.  
Service Valves  
Factory provided controls limit the steam  
Service valves are factory installed on  
each circuit before and after the  
compressor to allow compressor  
isolation for servicing.  
coil leaving air temperature to no more  
than 105 F (41 C) at all operating  
conditions.  
Single Stage Electric Heat Interface  
A heat control module will be factory  
installed and wired for customer supplied  
and powered electric heat. This module  
will allow the unit to stage the customer-  
provided electric heat. Single stage  
electric heat control will be accomplished  
with one dry binary output rated at one  
amp for 115 VAC.  
• Constant Water Flow  
Heating Coils  
Two-way modulating control shutoff  
valves are wired, controlled, and installed  
in the unit. One valve is located in the  
economizers water inlet, and the other is  
in the condenser bypass water inlet.  
When the waterside economizer enables,  
the two-way valve modulates to maintain  
the discharge air temperature setpoint.  
As the economizer valve opens, the  
condenser bypass valve closes, and vice  
versa. Full water flow is always  
• Electric Heat  
A single stage electric heating coil and  
controls are factory installed inside the  
unit casing at the fan discharge. An open  
construction type coil is provided. Power  
to the electric heater is factory wired to  
the units single-point power connection.  
Hydronic Heating Control Interface  
A heat control module will be factory  
installed and wired for customer supplied  
hydronic heating. This control will be  
accomplished with a dry binary output, 0-  
10 VDC analog control signal.  
• Hot Water  
The hot water heating assembly includes  
the coil and filter section and is factory  
installed on the units inlet. A three-way  
modulating valve, actuator, manifold  
piping, and automatic air vent are also  
factory installed.The coil is aTrane type  
WC, constructed of 5/8-inch (16 mm) OD  
copper tubes arranged in a parallel  
pattern. The copper tubes are expanded  
into aluminum fins positioned  
maintained through the condensers. Both  
valves will close in the event of a power  
failure.  
Time Clock  
Variable Water Flow  
A factory-installed programmable time  
clock is wired to the unoccupied mode  
binary input to provide on/off control. The  
timer is accessible without opening the  
control panel door, and is a seven-day  
type with a maximum of four operations  
per day. A permanent built-in  
Two-way modulating control shutoff  
valves are wired, controlled, and installed  
in the unit. One valve is located in the  
economizers water inlet, and the other is  
in the condenser bypass water inlet.  
When the economizer valve is active, the  
condenser bypass valve closes. The  
economizer valve modulates, thus water  
flow through the unit modulates. If the  
water is cool enough for economizing, but  
mechanical cooling is also required, the  
economizer valve fully opens to establish  
full water flow through the condensers.  
Whenever the water is too warm for  
economizing and there is a call for  
cooling, the economizer valve fully closes  
and the bypass valve fully opens,  
establishing full water flow through the  
condensers. Full water flow is always  
maintained through the condensers  
when mechanical cooling is required.  
Both valves close whenever cooling is  
not required and in the event of a power  
failure.  
continuously across the entire coil width,  
not exceeding 12 fins per inch. The coil  
casing is 16-gauge steel. Coil  
performance is rated at a maximum  
working pressure of 200 psig in  
accordance with ARI Standard 410.  
Supply and return water header  
connections are female tapered NPT and  
are accessed from the units left side.  
rechargeable battery pack is provided.  
Low Entering AirTemperature Protection  
Device  
A thermostat limit switch is factory  
mounted on the unit’s entering air side  
with a capillary tube serpentine across  
the coil face. If the temperature falls  
below 35 F (2 C), the fan shuts down and  
the waterside economizer and/or  
hydronic heat valve option opens to allow  
full water flow.The heat output also  
energizes. A manual reset is required.  
Note: this option is standard on units with  
a waterside economizer or hydronic  
heat.  
• Steam  
The steam heating assembly includes the  
coil and filter section, factory installed on  
the units inlet. A two-way modulating  
valve, actuator, and manifold piping are  
also factory installed. Also, connections  
are provided for field installing a vacuum  
breaker.The coil is aTrane type NS,  
constructed of one inch (25 mm) OD  
copper tubes arranged in a parallel  
pattern. The copper tubes are expanded  
into aluminum fins positioned  
Non-fused Disconnect Switch  
The unit has a factory mounted non-fused  
disconnect switch accessible without  
opening the control panel door.  
Water Flow Switch  
continuously across the entire coil width,  
not exceeding 42 fins per foot. The coil  
casing is 16-gauge steel. Coil  
performance is rated at a maximum  
working pressure of 100 psig in  
accordance with ARI Standard 410.  
Supply and return steam header  
connections are female tapered NPT and  
are accessed from the units left side.  
A water flow switch is factory installed in  
the condenser water pipe within the unit.  
Whenever the flow switch detects a  
water flow loss prior to or during  
mechanical cooling, compressor  
operation locks out and a diagnostic code  
displays. If water flow is restored, the  
compressor operation automatically  
restores.  
Dual Point PowerTerminal Blocks  
Two separate power terminal blocks are  
available to bring power to the unit; one  
terminal block provides power to the  
compressors and the other provides  
power to the fan motor and controls.  
Note: a single point power terminal block  
is standard.  
PKG-PRC002-EN  
99  
Mechanical  
Specifications Options  
Protective Coating  
Filters  
Flexible Horizontal Discharge Plenum  
Medium Efficiency  
• Cabinet  
• Low and Standard Height  
Two-inch (51 mm) medium efficiency  
throwaway fiberglass filters are installed  
in the unit filter section.  
The unit exterior and exposed interior  
surfaces have a four to six mil coat of  
protective coating.  
Units are provided with a factory installed  
horizontal discharge plenum that permits  
multi-directional duct connections. The  
plenum is insulated with two inches (51  
mm) of 1.75 lb. (0.79 kg) density fiberglass  
for sound attenuation. Discharge  
Remote Human Interface Panel  
• Coils  
The remote human interface panel (RHI)  
can perform all the same functions as  
the unit mounted human interface panel,  
except the service mode function. A  
single RHI can monitor and control up to  
four units. The panel includes a 2 x 40  
character clear language (English,  
Spanish, or French) display, a red LED  
light to indicate an alarm condition, a  
simple 16-key keypad for making unit  
setpoint and configuration changes, and  
hinged access door.The panel can be  
mounted up to 5,000 feet (1524 m) from  
the unit and is wired to the inter-  
A three to five mil coat of protective  
coating is applied to the coil using a  
multiple dip-and-bake process.  
openings can either be field cut or factory  
cut based on duct dimensions supplied by  
the customer. A two-inch duct collar is  
provided for field duct connections. On  
unit sizes 20-38 tons, the low height  
plenum is 24 5/8 inches (625 mm) and the  
standard height plenum is 32 3/8 inches  
(822 mm). On unit sizes 42-80 tons, the  
low height plenum is 21 1/8 inches (537  
mm) and the standard height plenum is  
28 5/8 inches (727 mm).  
Cupro-Nickel Condenser  
One condenser is provided for each  
compressor.The condensers are a shell-  
and-tube design with removable heads  
to allow mechanical tube cleaning.Tubes  
are ¾-inch (19mm) OD and constructed  
of copper cupro-nickel (90/10).  
Stainless Steel Drain Pan  
The drain pan is positively sloped,  
fabricated from 304L stainless steel, and  
insulated with ¾-inch (19 mm) of  
1-lb. (0.5 kg) density fiberglass. The drain  
pan contains a factory piped trap with  
cleanout.  
• Extended Height, 45-inch (1143m)  
Units are provided with a horizontal  
discharge plenum that permits multi-  
directional duct connections. The plenum  
is insulated with four inches (102 mm) of  
1.75 lb. (0.79 kg) density fiberglass for  
sound attenuation. Double-wall perf is  
also available. Discharge openings can  
either be field cut or factory cut based on  
duct dimensions supplied by the  
processor communications bridge (IPCB)  
mounted in the unit with twisted wire  
pair communication wiring and 24V  
wiring.  
Generic Building Automation System  
Module (GBAS)  
Dirty Filter Sensor  
A factory installed pressure switch  
senses the pressure differential across  
the filters. When the differential pressure  
exceeds 0.9-inches (23 mm) WG, contact  
closure occurs.  
The GBAS module is for use with a non-  
Trane building management system.The  
module provides a binary input for  
demand limiting, four analog inputs for  
setpoint adjustment, and five relay  
outputs for diagnostic reporting. Inputs  
can use a potentiometer or 0-5 vdc  
signal.  
customer. A two-inch duct collar is  
provided for field duct connections.  
A field installed indicator device may be  
wired to relay terminals that indicate  
when filter service is required. Contacts  
are rated at 115 VAC and are powered  
by a field supplied transformer.  
High Duct Temperature Thermostat  
A factory-supplied temperature limit  
switch with reset element detects the  
supply air duct temperature. This sensor  
should be field-installed downstream  
from the unit’s discharge in the supply air  
duct. If the supply air duct temperature  
exceeds 240 F (115.6 C), the unit shuts  
down and displays a diagnostic. A manual  
reset is required at the unit. The high duct  
temperature can be adjusted at the  
thermostat.  
Ventilation Override Module (VOM)  
The VOM allows you to program the unit  
with up to five ventilation sequences:  
smoke purge, evacuation, pressurization,  
purge, and purge with duct control.  
Typically, a hard-wire short from a  
smoke detector or fire control panel will  
cause a binary input on the VOM to  
close, thus causing the programmed  
sequence to occur.  
Plenum High Static Switch  
Trane Communication Interface (TCI)  
TheTCI provides interface to aTrane  
Integrated Comfort™ system (ICS). It  
allows remote control and monitoring of  
the self-contained unit using a personal  
computer withTracer® building  
A factory supplied sensor provides  
additional protection from ductwork over-  
pressurization. This sensor should be  
field-installed downstream of the units  
discharge in the supply air duct.  
management software.  
Dirty Filter Switch  
100  
PKG-PRC002-EN  
Literature Order Number  
File Number  
PKG-PRC002-EN  
TheTrane Company  
A Division of American Standard Inc.  
www.trane.com  
PL-UN-PKG-PRC002-EN-1201  
PKG-PRC002-EN 01/01  
La Crosse - Inland  
Supersedes  
For more information contact  
your localTrane office or  
Stocking Location  
e-mail comfort@trane.com  
TheTrane Company has a policy of continuous product improvement and reserves the right to change design and  
specifications without notice.  

Trion T2002 User Manual
Smc Networks Robo Cylinder Ra4c User Manual
Schumacher Xc10 User Manual
Sanyo Cl2472 User Manual
Samsung Us07s8gb User Manual
NEC NP54 User Manual
NEC MULTISYNC P462 02 User Manual
Lfwc18t6lb User Manual
CRAFTSMAN 316.350220 User Manual
BLACK DECKER SPACEMAKER EK970 User Manual