Trane Air Conditioner Unt Svx07a En User Manual

Installation, Operation,  
and Maintenance  
UniTrane Fan-Coil & Force Flo  
Air Conditioners  
200 to 1,200 cfm  
Models FC & FF  
ZO” and later design sequence  
Low vertical models FCKB & FCLB:  
“SO” and later design sequence  
April 2005  
UNT-SVX07A-EN  
contents  
Cross reference to related publications/information for UniTrane™ fan-coil & Force  
Flo™ equipment:  
• RoverInstallation, Operation and Programming Guide, EMTX-SVX01D-EN  
TracerZN510 Unit Controller, CNT-IOP-1  
TracerZN520 Unit Controller, CNT-SVX04A-EN  
• UniTraneFan-Coil Catalog, UNT-PRC001-EN  
• Force FloCabinet Heater Catalog, CAB-PRC001-EN  
Installation …………………………………………………………2  
general information …………………………………………2  
dimensions & weights …………………………………… 10  
pre-installation considerations ………………………………28  
mechanical requirements …………………………………30  
electrical requirements ……………………………………36  
installation procedure ………………………………………41  
pre-startup requirements ……………………………………46  
Operation …………………………………………………………49  
general information ………………………………………49  
sequence of operation ……………………………………50  
Maintenance………………………………………………………60  
diagnostics ……………………………………………………60  
troubleshooting ………………………………………………64  
maintenance procedures …………………………………67  
typical wiring diagrams ……………………………………71  
UNT-SVX07A-EN  
3
general  
inform ation  
General  
Model Number  
switch option, can be ordered with a low  
voltage(24 volts AC) transformer and  
three fan speed relays. The ship seperate  
three-speed switch option, only comes  
with a low voltage (24 volt AC) trans-  
former and three fan speed relays.  
Each UniTrane fan-coil and Force-Flo  
cabinet heater has a multiple character  
model number unique to that particular  
unit. To determine a units specific options,  
reference the model number on the unit  
nameplate on the fan scroll. The unit  
nameplate also identifies the serial  
number, sales order number, and  
installation and operating specifications.  
UniTrane fan-coil and Force Flo units are  
intended for single zone applications.  
These units have load capabilities of 200  
to 1200 cfm. See Figure I-GI-1 for unit  
components. Fan-coil units are available  
as two-pipe, with or without electric heat  
(one hydronic circuit) or four-pipe (two  
hydronic circuits). Force-Flo units feature  
two-pipe hydronic, electric heat only, or  
steam only. Also, these units feature a  
variety of factory mounted piping  
packages.  
The Tracer ZN010, ZN510, and ZN520  
controllers are included inside the units  
control box assembly. These controllers  
utilize analog signals from a unit-mounted  
control device or from a control device  
mounted in the occupied space.  
Following is a complete description of the  
fan-coil model number. Each digit in the  
model number has a corresponding code  
that identifies specific unit options.  
The controls interface option, includes a  
24 volt AC transformer, and an interface  
terminal board. Controls provided by an  
external source, can be tied into the  
Units with the three-speed fan switch  
only, are available with the switch  
mounted on the unit, or shipped sepa-  
rately, to be mounted in the occupied  
space. The unit mounted three-speed  
1
interface terminal board, utilizing /4"  
female spade connectors.  
Factory assembled,  
Smaller unit footprint  
installed and tested piping  
package with IAQ drain pan  
to collect condensate  
Factory installed  
and tested controls  
Two, three or  
four-row coils  
Quiet operation  
Removable, noncorrosive,  
positively-sloped drain pan thats  
easy to clean  
Easy to remove fan assembly  
Cleanable closed-  
cell insulation (non-  
fiberglass)  
16-gage steel construction  
Easy filter access  
without front panel  
removal  
Damper allows up  
to 100% fresh air  
Figure I-GI-1. UniTrane fan-coil unit components. Vertical cabinet model is shown.  
4
UNT-SVX07A-EN  
general  
Installation  
inform ation  
Model Number Description  
FC B B 020 1 C P0 A 0 G 1 0 A A 2 M 000 0 0 1 0 0 0 A A 000 000 0 0 0 0 A 0 0  
10 15 20 25 30 35 40 44  
1
5
G = back open return  
L = 3 row cooling/heating w/ elec heat  
M= 4 row cooling/heating w/ elec heat  
P = 2 row cooling/heating w/1 row heat  
Q = 2 row cooling/heating w/2 row heat  
R = 3 row cooling/heating w/1 row heat  
Digits 1, 2 — unit type  
FC = fan-coil  
H = back stamped louver  
FF = force flo  
Digit 13 — fresh air damper  
0 = none  
A = manual, bottom opening  
B = manual, back opening  
C = manual, top opening  
Digit 3 — cabinet type  
A = vertical concealed  
B = vertical cabinet  
C = horizontal concealed  
D = horizontal cabinet  
E = horizontal recessed  
F = vertical wall hung  
H = vertical recessed  
J = vertical cabinet slope top  
K = low vertical concealed  
L = low vertical cabinet  
M = inverted vertical cabinet  
N = inverted vertical recessed  
Digit 19 — coil series  
2 = 144 FPF  
D = auto, 2-position, bottom opening  
E = auto, 2-position, back opening  
F = auto, 2-position, top opening  
G = auto, economizer, bottom opening  
H = auto, economizer, back opening  
J = auto, economizer, top opening  
K = no damper, bottom opening  
L = no damper, back opening  
Digit 20 — coil air vent  
A = automatic air vent  
M= manual air vent  
Digits 21, 22, 23 — electric heat (208V  
derate)  
M= no damper, top opening  
000 = no electric heat  
010 = 1.0 kW (0.75 kW)  
015 = 1.5 kW (1.1 kW)  
020 = 2.0 kW (1.5 kW)  
025 = 2.5 kW (1.9 kW)  
030 = 3.0 kW (2.3 kW)  
040 = 4.0 kW (3.0 kW)  
050 = 5.0 kW (3.8 kW)  
060 = 6.0 kW (4.5 kW)  
070 = 7.0 kW (5.3 kW)  
08 0= 8.0 kW (6.0 kW)  
100 = 10.0 kW  
Digit 14 — outlets  
A = front duct collar  
B = front bar grille  
C = front stamped louver  
D = front quad grille  
G = top quad grille  
H = top bar grille  
Digit 4 — development sequence “B”  
Digits 5, 6, 7 — unit size  
020 040 080  
030 060 100  
120  
J = top duct collar  
Digit 8 — unit voltage  
1 = 115/60/1 4 = 230/60/1  
2 = 208/60/1 9 = 220/50/1  
3 = 277/60/1  
Digit 15 — color  
0 = no paint (concealed units only)  
1 = deluxe beige 4 = driftwood grey  
Digit 24 — reheat coil  
2 = soft dove  
5 = stone grey  
0 = none  
A = steam coil  
B = hot water coil  
3 = cameo white 6 = rose mauve  
Digit 9 — piping system/placement  
A = no piping, RH, w/o aux drn pan  
B = no piping, LH, w/o aux drn pan  
C = no piping, RH, w/ aux drn pan  
D = no piping, LH, w/ aux drn pan  
E = no piping, RH, w/o aux drn pan,  
extended end pocket  
Digit 16 — tamperproof locks/leveling  
feet  
0 = none  
A = locking panel  
B = keylock access door  
C = locking panel & keylock access door  
D = leveling feet  
F = locking panel w/ leveling feet  
G = keylock panel, keylock access door  
w/ leveling feet  
Digit 25 — disconnect switch  
0 = none  
D = disconnect switch  
Digit 26 — filter  
0 = none  
F = no piping, LH, w/o aux drn pan,  
extended end pocket  
1 = 1” throwaway filter  
2 = 1” throwaway pleated media filter  
3 = 1” throwaway, qty 2  
G = no piping, RH, w/ aux drn pan,  
extended end pocket  
4 = 1” throwaway pltd media, qty 2  
5 = 1” throwaway, qty 3  
H = no piping, LH, w/ aux drn pan,  
extended end pocket  
Digit 17 — motor  
A = free discharge  
B = high static  
6 = 1” throwaway pltd media, qty 3  
7 = 1” throwaway, qty 4  
8 = 1” throwaway pltd media, qty 4  
J = piping package, RH  
K = piping package, LH  
L = piping package, RH, extd end pkt  
M = piping package, LH, extd end pkt  
Digit 18 — coil  
Digit 27 — main control valve  
0 = none  
A = 2 row cooling/heating  
B = 3 row cooling/heating  
C = 4 row cooling/heating  
D = 2 row cooling/1 row heating  
E = 2 row cooling/2 row heating  
F = 3 row cooling/1 row heating  
G = 2 row cooling only  
Digits 10, 11 — design sequence  
A = 2-way, 2-position, NO (30 psig)  
B = 3-way, 2-position, NO (28 psig)  
C = 2-way, 2-position, NC (30 psig)  
D = 3-way, 2-position, NC (20 psig)  
E = 2-way, 2-position, NO (50 psig)  
F = 3-way, 2-position, NO (28 psig)  
G = 2-way, 2-position, NC (50 psig)  
H = 3-way, 2-position, NC (28 psig)  
Digit 12 — inlets  
A = front toe space  
B = front bar grille  
C = front stamped louver  
D = bottom stamped louver  
E = bottom toe space  
F = back duct collar  
H = 3 row cooling only  
J = 4 row cooling only  
K = 2 row cooling/heating w/ elec heat  
UNT-SVX07A-EN  
5
general  
Installation  
inform ation  
Digits 37, 38 — future cntrl functions  
J = 2-way, modulating, 0.7 Cv (50 psig)*  
K = 3-way, modulating, 0.7 Cv (50 psig)*  
L = 2-way, modulating, 1.1 Cv (60 psig)*  
M= 3-way, modulating, 1.1 Cv (60 psig)*  
N = 2-way, modulating, 2.3 Cv (60 psig)*  
P = 3-way, modulating, 2.7 Cv (60 psig)*  
Q = 2-way, modulating, 3.3 Cv (60 psig)*  
R = 3-way, modulating, 3.8 Cv (60 psig)*  
X = field-supplied, NO  
G = Tracer ZN520  
H = CSTI  
Digit 39 — projection panel/falseback  
0 = none  
Digit 31 — control option  
D = unit mtd fan mode, unit voltage,  
K = wall mtd fan mode  
V = unit mtd fan sp w/ setpnt  
X = unit mtd fan sp w/ wall mtd setpnt  
Y = unit mtd fan sp & wall mtd setpnt w/  
comm.  
Z = unit mtd fan sp, on/cancel, setpnt w/  
comm.  
1 = wall mtd on/cancel w/ comm.  
2 = wall mtd fan speed, setpnt, on/cancel  
w/ comm.  
3 = unit mtd fan speed switch, low voltage  
4 = wall mtd digital zone sensor, fan sp w/  
setpnt, on/cancel, comm.  
5 = wall mtd digital zone sensor, setpnt,  
on/cancel, comm.  
A = 5/8”standard vertical recessed panel  
B = 2” projection panel  
C = 2.5” projection panel  
D = 3” projection panel  
E = 3.5” projection panel  
F = 4” projection panel  
G = 4.5” projection panel  
H = 5” projection panel  
J = 5.5”projection panel  
K = 6” projection panel  
L = 2”falseback  
Y = field-supplied, NC  
Z = field-supplied 3-wire modulating  
Digit 28 — auxiliary control valve  
0 = none  
A = 2-way, 2-position, NO (30 psig)  
B = 3-way, 2-position, NC (28 psig)  
C = 2-way, 2-position, NC (30 psig)  
D = 3-way, 2-position, NC (20 psig)  
E = 2-way, 2-position, NO (50 psig)  
F = 3-way, 2-position, NO (28 psig)  
G = 2-way, 2-position, NC (50 psig)  
H = 3-way, 2-position, NC (28 psig)  
J = 2-way, modulating, 0.6 Cv (60 psig)  
K = 3-way, modulating, 0.6 Cv (60 psig)  
L = 2-way, modulating, 1.1 Cv (60 psig)  
M= 3-way, modulating, 1.1 Cv (60 psig)  
N = 2-way, modulating, 2.3 Cv (60 psig)  
P = 3-way, modulating, 2.7 Cv (60 psig)  
Q = 2-way, modulating, 3.3 Cv (60 psig)  
R = 3-way, modulating, 3.8 Cv (60 psig)  
X = field-supplied, NO  
M = 3” falseback  
N = 4” falseback  
P = 5” falseback  
Q = 6” falseback  
R = 7” falseback  
T = 8” falseback  
Digit 32 — IAQ options  
0 = none  
1 = dehumidification  
4 = dehumidification w/sensor  
Digit 40 — main autoflow gpm  
A = 0.5  
G = 3.0  
N = 7.0  
P = 8.0  
Q = 9.0  
R = 10.0  
T = 11.0  
U = 12.0  
B = 0.75 H = 3.5  
Digit 33 — cntrl function #1  
0 = w/o exhaust fan/damper or alarm  
C = 1.0  
D = 1.5  
E = 2.0  
F = 2.5  
J = 4.0  
K = 4.5  
L = 5.0  
M= 6.0  
Digit 34 — cntrl function #2  
0 = w/o occupant call or IAQ status  
Y = field-supplied, NC  
Z = field-supplied 3-wire modulating  
Digit 41 — auxiliary autoflow gpm  
Digit 35 — control function #3  
0 = none  
1 = occ/unocc control  
2 = condensate overflow detection  
3 = occ/unocc & condensate overflow  
A = 0.5  
F = 2.5  
L = 5.0  
M= 6.0  
N = 7.0  
P = 8.0  
B = 0.75 G = 3.0  
Digit 29 — piping packages  
C = 1.0  
D = 1.5  
E = 2.0  
H = 3.5  
J = 4.0  
K = 4.5  
0 = none  
A = basic ball valve S & R  
B = basic ball valve S/man. crkt set  
C = basic ball valve S & R w/auto crkt set  
D = deluxe ball valve S & R  
Digit 36 — cntrl function #4  
0 = none  
1 = smoke input  
2 = low temperature detection  
3 = smoke input & low limit sensor  
Digit 42 — subbase  
0 = none  
A = 2” subbase  
B = 3” subbase  
C = 4” subbase  
E = deluxe ball valve S /man. crkt set R  
F = deluxe ball valve S & R w/auto crkt set  
D =5” subbase  
E =6” subbase  
F =7” subbase  
Digit 30 — control type  
0 = none  
A = fan speed switch  
E = Tracer ZN010  
F = Tracer ZN510  
Digit 43 — recessed flange  
0 = none  
A = recessed flange  
Digit 44 — wall boxes  
0 = none  
A = anodized wall box  
6
UNT-SVX07A-EN  
general  
Installation  
inform ation  
Table I-GI-1. Fan-coil component data  
unit size  
02  
03  
04  
06  
08  
10  
12  
Coil Data  
Face Area — Ft2 (cm2)  
LxDxH — In. (cm)  
2-Row  
0.8 (743)  
0.8 (743)  
1.1 (1020)  
1.6 (1490)  
2.1 (1950)  
3.2 (2970)  
3.2 (2970)  
15x1.7x8  
(38x4x20)  
15x2.6x8  
(38x7x20)  
15x3.5x8  
(38x9x20)  
15x1.7x8  
(38x4x20)  
15x2.6x8  
(38x7x20)  
15x3.5x8  
(38x9x20)  
20x1.7x8  
(51x4x20)  
20x2.6x8  
(51x7x20)  
20x3.5x8  
(51x9x20)  
29.5x1.7x8  
(75x4x20)  
29.5x2.6x8  
(75x7x20)  
29.5x3.5x8  
(75x9x20)  
38x1.7x8  
(97x4x20)  
38x2.6x8  
(97x7x20)  
38x3.5x8  
(97x9x20)  
57x1.7x8  
(145x4x20)  
57x2.6x8  
(145x7x20)  
57x3.5x8  
(145x9x20)  
57x1.7x8  
(145x4x20)  
57x2.6x8  
(145x7x20)  
57x3.5x8  
(145x9x20)  
3-Row  
4-Row  
Volume — Gal. (Liters)  
1-Row (Heat)  
2-Row  
3-Row  
4-Row  
.06 (.23)  
.12 (.45)  
.18 (.68)  
.24 (.91)  
.06 (.23)  
.12 (.45)  
.18 (.68)  
.24 (.91)  
.08 (.30)  
.15 (.57)  
.23 (.87)  
.30 (1.14)  
.11 (.42)  
.22 (.83)  
.33 (1.25)  
.44 (1.67)  
.14 (.53)  
.28 (1.06)  
.42 (1.59)  
.56 (2.12)  
.21 (.79)  
.42 (1.59)  
.62 (2.35)  
.83 (3.14)  
.21 (.79)  
.42 (1.59)  
.62 (2.35)  
.83 (3.14)  
Fins/Ft (cm)  
2-Row  
3-Row  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
4-Row  
Reheat Coil Data (1-Row)  
Hot Water or Steam  
Face Area — Ft2 (cm2)  
0.6  
0.6  
0.8  
1.2  
1.6  
2.4  
2.4  
(557)  
(557)  
(743)  
(1120)  
(1490)  
(2230)  
(2230)  
LxDxH — In. (cm)  
15x1.5x6  
(38x4x15)  
.12 (.45)  
48 (1.6)  
15x1.5x6  
(38x4x15)  
.12 (.45)  
48 (1.6)  
20x1.5x6  
(51x4x15)  
.15 (.57)  
48 (1.6)  
29.5x1.5x6  
(75x4x15)  
.22 (.83)  
48 (1.6)  
38x1.5x6  
(97x4x15)  
.28 (1.06)  
48 (1.6)  
57x1.5x6  
(145x4x15)  
.42 (1.59)  
48 (1.6)  
57x1.5x6  
(145x4x15)  
.42 (1.59)  
48 (1.6)  
Volume — Gal. (Liters)  
Fins/Ft (cm)  
Fan/Motor Data  
Fan Quantity  
1
1
1
2
2
3
3
Size — Dia” x Width” (cm)  
6.31x4  
(16x10)  
6.31x6.5  
(16x17)  
6.31x7.5  
(16x19)  
6.31x6.5  
(16x17)  
6.31x7.5  
(16x19)  
(1) 6.31x7.5  
(16x19)  
(2) 6.31x6.5  
(16x6.5)  
2
6.31x7.5  
(16x19)  
Size — Dia” x Width” (cm)  
Motor Quantity  
Filter Data  
1
1
1
1
1
2
1” (cm) TA and Pl. Media  
Quantity  
Size — In. (cm)  
1
1
1
1
1
1
1
87/8 x 191/8  
(23x49)  
87/8 x 191/8  
(23x49)  
87/8 x 241/8  
(23x61)  
87/8 x 335/8  
(23x85)  
87/8 x 421/8  
(23x107)  
87/8 x 611/8  
(23x155)  
87/8 x 611/8  
(23x155)  
1” Fresh Air Filter (only on cabinet styles D, E, and H with bottom return and fresh air opening)  
Quantity  
Size — In. (cm)  
(14 x 49)  
1
1
1
1
1
1
1
51/2 x 191/8  
(14 x 49)  
51/2 x 191/8  
(14 x 61)  
51/2 x 241/8  
(14 x 85)  
51/2 x 335/8  
(14 x 107)  
51/2 x 421/8  
(14 x 156)  
51/2 x 611/8  
(14 x 156)  
51/2 x 611/8  
Table I-GI-2. Low vertical fan-coil component data  
unit size  
03  
04  
06  
Coil Data  
Face Area — Ft2 (cm2)  
LxDxH — In. (cm)  
2-Row  
1.1 (1020)  
1.6 (1490)  
2.1 (1950)  
20x1.7x8 (51x4x20)  
20x2.6x8 (51x7x20)  
29.5x1.7x8 (75x4x20)  
29.5x2.6x8 (75x7x20)  
38x1.7x8 (97x4x20)  
38x2.6x8 (97x7x20)  
3-Row  
Volume — Gal. (Liters)  
1-Row (Heat)  
2-Row  
.08 (.30)  
.15 (.57)  
.23 (.87)  
.11 (.42)  
.22 (.83)  
.33 (1.25)  
.14 (.53)  
.28 (1.06)  
.42 (1.59)  
3-Row  
Fins/Ft  
2-Row  
3-Row  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
144 (4.7)  
Fan/Motor Data  
Fan Quantity  
Size — Dia”x Width” (cm)  
Motor Quantity  
Filter Data  
1
1
1
5x23 (13x59)  
1
5x32 (13x83)  
1
5x41 (13x105)  
1
1” (2.5 cm) TA  
Quantity  
Size — In. (cm)  
1
1
1
87/8x241/8 (23x61)  
87/8x335/8 (23x85)  
87/8 x 421/8 (23x107)  
UNT-SVX07A-EN  
7
general  
Installation  
inform ation  
Available Models  
m odel B vertical cabinet  
m odel C horizontal concealed  
m odel A vertical concealed  
m odel E horizontal recessed  
m odel F wall hung cabinet  
m odel D horizontal cabinet  
m odel K low vertical cabinet  
m odel H vertical recessed  
m odel L low vertical concealed  
m odel M inverted vertical cabinet  
m odel N inverted vertical recessed  
m odel J slope-top cabinet  
(Force Flo only)  
(Force Flo only)  
8
UNT-SVX07A-EN  
general  
Installation  
inform ation  
Factory-Installed Piping Packages  
Note: This figure shows piping package components and basic arrangement. It is not  
an accurate pictorial of what factory-installed piping packages look like.  
UNT-SVX07A-EN  
9
dim ensions  
& w eights  
Installation  
Vertical Concealed, Model A  
Vertical Concealed Unit Dimensions & weights, in-lbs.  
Unit  
Size  
A
B
C
D
E
02-03  
04  
06  
08  
10-12  
2-8 11/16” 3-1 11/16” 3-11 3/16” 4-7 11/16” 6-2 11/16”  
1-9 5/16” 2-2 5/16” 2-11 13/16” 3-8 5/16” 5-3 5/16”  
1-10 13/16” 2-3 13/16” 3-1 5/16” 3-9 13/16” 5-4 13/16”  
1-5 5/16” 1-10 5/16” 2-7 13/16” 3-4 5/16” 4-11 5/16”  
1-7 5/16” 2-0 5/16”  
2-9 13/16” 3-6 5/16” 5-1 5/16”  
operating weight  
shipping weight  
81  
68  
109  
96  
139  
123  
147  
131  
200  
182  
Notes:  
1. Coil connections are always on the drain pan side and opposite the control  
box.  
5
2. Coil connections are  
/8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See fresh air opening dim ensions on pages 23-24.  
10  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Vertical Cabinet, Model B  
Vertical Cabinet Unit Dimensions, in-lbs.  
unit  
size  
A
B
C
02-03  
04  
06  
08  
10-12  
2-9 5/16”  
3-2 5/16” 3-11 3/16” 4-8 5/16” 6-3 5/16”  
1-9 5/16”  
2-2 5/16” 2-11 3/16” 3-8 5/16” 5-3 5/16”  
5
1
7
1
5
7
/8  
7
/8  
8
/8  
7
/8  
7
/8  
D
E
F
1-6”  
2-0”  
2-6”  
3-6”  
5-0”  
1-7 5/16”  
2-0 5/16” 2-9 13/16” 3-6 5/16” 5-1 5/16”  
3-5 5/16” 3-10 5/16” 4-7 3/16” 5-4 5/16” 6-11 5/16”  
operating weight 97  
shipping weight 84  
125  
112  
155  
139  
164  
148  
218  
200  
Notes:  
1. Coil connections are always on the drain pan side and opposite the control box.  
5
2. Coil connections are /8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
11  
dim ensions  
& w eights  
Installation  
Horizontal Concealed, Model C  
Horizontal Concealed Unit Dimensions, in-lbs.  
unit  
size  
A
B
C
D
E
02-03  
04  
06  
08  
10-12  
2-8 11/16” 3-1 11/16” 3-11 3/16” 4-7 11/16” 6-2 11/16”  
1-9 5/16” 2-2 5/16” 2-11 13/16” 3-8 5/16” 5-3 5/16”  
1-10 13/16” 2-3 13/16” 3-1 5/16” 3-9 13/16” 5-4 13/16”  
3
3
7
3
3
1-7  
1-6  
/
/8  
8
2-0  
/
/
8
2-9  
2-8  
/
8
3-6  
3-5  
/
8
5-1  
5-0  
/8  
1
1
5
1
1
1-11  
8
/
8
/
8
/8  
F
1-7 5/16” 2-0 5/16” 2-9 13/16” 3-6 5/16” 5-1 5/16”  
operating weight 81  
109  
96  
139  
123  
147  
131  
200  
182  
shipping weight  
68  
Notes:  
1. Coil connections are always on the drain pan side and opposite the control  
box.  
2. Coil connections are 5  
/8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
12  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Horizontal Cabinet, Model D  
Horizontal Cabinet Unit Dimensions, in-lbs.  
unit  
size  
A
B
02-03  
04  
06  
08  
10-12  
2-9 5/16”  
3-2 5/16” 3-11 3/16” 4-8 5/16” 6-3 5/16”  
2-2 5/16” 2-11 13/16” 3-8 5/16” 5-3 5/16”  
1-9 5/16”  
5
1
7
1
5
C
7
/8  
7
/8  
8
/8  
7
/8  
7
/8  
D
E
F
G
H
J
1-6”  
2-0”  
2-6”  
3-6”  
5-0”  
1
1
3
1
1
1-5  
/
4
1-10  
/
4
2-7  
/4  
3-4  
/4  
4-11  
/
4
3-5 5/16”  
3-10 5/16” 4-7 3/16” 5-4 5/16” 6-11 5/16”  
5
1
7
1
5
8
/8  
8
/8”  
9
/8  
8
/8  
8
/8  
1’ -4”  
1-10”  
2-4”  
3-4”  
4-10”  
3
3
3
3
3
1-7  
/4  
1-11  
/
4
2-7  
/4  
3-3  
/4  
4-11  
218  
200  
/
4
operating weight 97  
shipping weight  
125  
112  
155  
139  
164  
148  
84  
Notes:  
1. Coil connections are always on the drain pan side and opposite the control  
box.  
5
2. Coil connections are  
/8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
UNT-SVX07A-EN  
13  
dim ensions  
& w eights  
Installation  
Horizontal Recessed, Model E  
Horizontal Recessed Unit Dimensions, in-lbs.  
unit  
size  
A
B
C
D
E
F
G
H
02-03  
2-11 13/16” 3-4 13/16” 4-2 5/16” 4-10 13/16” 6-5 13/16”  
1-9 5/16” 2-2 5/16” 2-11 13/16” 3-8 5/16” 5-3 5/16”  
04  
06  
08  
10-12  
1-10 13/16” 2-3 13/16” 3-1 5/16” 3-9 13/16” 5-4 13/16”  
3
3
7
3
3
1-7  
1-6  
/
/8  
8
2-0  
1-11  
/
/
8
2-9  
2-8  
/
/8  
8
3-6  
3-5  
/
/8  
8
5-1  
5-0  
/
8
8
1
1
5
1
1
8
/
2-8 7/16”  
3-1 7/16” 3-10 15/16” 4-7 7/16” 6-2 7/16”  
2-10 5/16”  
3-3 5/16” 4-0 13/16” 4-9 5/16” 6-4 5/16”  
3
3
3
3
3
1-7  
/4  
1-11  
88  
78  
/
4
2-7  
/4  
3-3  
/4  
4-11  
253  
243  
/
4
operating weight 78  
shipping weight  
128  
118  
139  
129  
68  
Notes:  
1. Coil connections are always on the drain pan side and opposite the control  
box.  
5
2. Coil connections are  
/8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
14  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Vertical Wall Hung Cabinet, Model F  
Vertical wall hung cabinet unit dimensions & weights, in-lbs.  
unit  
size  
A
B
C
02-03  
04  
06  
08  
10-12  
2-9 5/16”  
3-2 5/16” 3-11 13/16” 4-8 5/16” 6-3 5/16”  
1-9 5/16”  
2-2 5/16” 2-11 13/16” 3-8 5/16” 5-3 5/16”  
5
1
7
1
5
7
/8  
7
/
8
8
/
8
7
/
8
7
/8  
D
E
F
1-6”  
2-0”  
2-6”  
3-6”  
5-0”  
1-7 5/16”  
2-0 5/16”  
2-9 13/16” 3-6 5/16” 5-1 5/16”  
3
3
3
3
3
1-7  
/4  
1-11  
/
4
2-7  
/4  
3-3  
/4  
4-11  
218  
200  
/
4
operating weight  
shipping weight  
97  
84  
125  
112  
155  
139  
164  
148  
Notes:  
1. Coil connections are always on the side opposite the control box.  
5
2. Coil connections are /8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
UNT-SVX07A-EN  
15  
dim ensions  
& w eights  
Installation  
Vertical Recessed, Model H  
Vertical Recessed Unit Dimensions, in-lbs.  
unit  
size  
A
B
C
D
E
F
G
02-03  
04  
06  
08  
10-12  
2-8 11/16” 3-1 11/16” 3-11 3/16” 4-7 11/16” 6-2 11/16”  
1-9 5/16”  
2-2 5/16” 2-11 13/16” 3-8 5/16” 5-3 5/16”  
1-10 13/16” 2-3 13/16” 3-1 5/16” 3-9 13/16” 5-4 13/16”  
1-5 5/16” 1-10 5/16” 2-7 13/16” 3-4 5/16” 4-11 5/16”  
1
1
3-11”  
4-3”  
5-3”  
5-5  
2-9  
/
/
2
7-5  
2-9  
/
2
2
1
1
2-6”  
2-6”  
2-6”  
2
/
3
3
3
1
1
2
/8”  
2
/8  
2
/8”  
4
/8  
4
/8  
H
J
3-6”  
4-0”  
4-9”  
5-3”  
7-3”  
1
1
1
1
1
2-2  
/2  
2-2  
/2  
2-2  
128  
118  
/
2
2-3  
139  
129  
/
2
2-3  
253  
243  
/
2
operating weight 78  
shipping weight  
88  
78  
68  
Notes:  
1. Coil connections are always on the drain pan side and opposite the control  
box.  
2. Coil connections are 5  
/8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
5. Dim ension 'G' refers to the required m inim um distance between the finished  
floor, and the bottom of the unit.  
16  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Vertical Slope Top, Model J  
Vertical Slope Top Unit Dimensions, in-lbs.  
unit  
size  
A
B
02-03  
04  
06  
08  
10-12  
2-9 5/16”  
3-2 5/16” 3-11 13/16”  
4-8 5/16”  
6-3 5/16”  
1-9 5/16”  
2-2 5/16” 2-11 13/16”  
3-8 5/16”  
5-3 5/16”  
5
1
7
1
5
C
7
/8  
7
/8  
8
/8  
7
/8  
7
/8  
D
E
F
1-6”  
2-0”  
2-6”  
3-6”  
3-6 5/16”  
5-4 5/16”  
164  
5-0”  
5-1 5/16”  
6-11 5/16”  
218  
1-7 5/16”  
2-0 5/16”  
2-9 13/16”  
3-5 5/16” 3-10 5/16” 4-7 13/16”  
operating weight 97  
shipping weight  
125  
112  
155  
139  
84  
148  
200  
Notes:  
1. Coil connections are always on the drain pan side and opposite the control box.  
5
2. Coil connections are /8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
UNT-SVX07A-EN  
17  
dim ensions  
& w eights  
Installation  
Low Vertical Concealed, Model K  
Low Vertical Concealed Unit Dimensions, in-lbs.  
unit size  
A
B
C
D
E
03  
04  
06  
3-5 7/16”  
4-2 15/16” 4-11 7/16”  
1
3
1
2-2  
/4  
2-11  
/4  
3-8  
/
4
2-3 15/16”  
3-0 13/16” 3-9 15/16”  
1-10 5/16”  
2-7 13/16” 3-4 5/16”  
1
3
1
2-0  
/4  
2-9  
139  
123  
/4  
3-6  
147  
131  
/
4
operating weight  
shipping weight  
109  
96  
Notes:  
1. Coil connections are always on the drain pan side and opposite  
the control box.  
2. Coil connections are  
5
/8” O.D. sweat.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
18  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Low Vertical Cabinet, Model L  
Low Vertical Cabinet Unit Dimensions, in-lbs.  
unit  
size  
A
B
C
03  
04  
06  
3-10 15/16” 4-8 7/16” 5-4 15/16”  
1
3
1
2-2  
/
4
2-11  
1-1 5/16”  
/4  
3-8  
/
4”  
11 7/16”  
11 7/16”  
D
E
2-0”  
2-6”  
3-6”  
1
3
1
2-0  
/4  
2-9  
/4  
3-6  
/4  
operating weight  
shipping weight  
125  
112  
155  
139  
164  
148  
Notes:  
1. Coil connections are always on the drain pan side and  
opposite the control box.  
5
2. Coil connections are  
/
8” O.D. sweat.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
UNT-SVX07A-EN  
19  
dim ensions  
& w eights  
Installation  
Inverted Vertical Cabinet, Model M  
Inverted vertical cabinet unit dimensions & weights, in-lbs.  
unit  
size  
A
B
C
02-03  
04  
06  
08  
10-12  
2-9 5/16”  
3-2 5/16”  
3-11 13/16”  
4-8 5/16”  
6-3 5/16”  
1-9 5/16”  
2-2 5/16”  
2-11 13/16”  
3-8 5/16”  
5-3 5/16”  
5
1
7
1
5
7
/8  
7
/8  
8
/8  
7
/8  
7
/8  
D
E
F
G
1-6”  
2-0”  
2-6”  
3-6”  
5-0”  
1
1-7”  
2-0”  
2-9  
/
/4  
2
3-6”  
5-1”  
3
3
3
3
3
1-7  
8
/
4
1-11  
/
4
2-7  
3-3  
8
/
4
4-11  
/
4
5
1
7
1
5
/
8
8
/
8”  
9
/8  
/
8
8
/
8
H
1-4”  
97  
84  
1-10”  
125  
112  
2-4”  
155  
139  
3-4”  
164  
148  
4-10”  
218  
200  
operating weight  
shipping weight  
Notes:  
1. Coil connections are always on the side opposite the control box.  
5
2. Coil connections are /8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
20  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Inverted Vertical Recessed, Model N  
Inverted vertical recessed unit dimensions & weights, in-lbs.  
unit  
size  
A
B
C
D
E
F
G
02-03  
04  
06  
08  
10-12  
7
7
3
7
7
2-3  
/
8
2-8  
/
8
3-6  
/
8
4-2  
/
8
5-9  
5-3 5/16”  
3-9 13/16” 5-4 13/16”  
/8  
1-9 5/16”  
2-2 5/16”  
2-11 13/16” 3-8 5/16”  
1-10 13/16”  
2-3 13/16”  
3-1 5/16”  
3
3
3
1
1
2
/8  
2
/8  
2
/8  
4
/
8
/
/
/
4
/
8
/2  
/2  
/2  
1
1
1
1
1
1
3-11”  
4-3”  
2-6”  
5-3”  
2-6”  
5-5  
2-9  
2-3  
2
7-5  
2-9  
2-3  
2-6”  
2
1
1
1
2-2  
/2  
2-2  
/
4-0”  
88  
2
2-2  
/
4-9”  
128  
2
2
H
3-6”  
78  
68  
5-3”  
139  
129  
7-3”  
253  
243  
operating weight  
shipping weight  
78  
118  
Notes:  
1. Coil connections are always on the side opposite the control box.  
5
2. Coil connections are /8” O.D. sweat. See pages 21-22 for locations.  
3. All duct collar dim ensions are to the outside of the collar.  
4. See pages 23-24 for fresh air opening dim ensions.  
Dimension 'D' refers to the required  
minimum distance between the finished  
floor, and the bottom of the unit.  
UNT-SVX07A-EN  
21  
dim ensions  
& w eights  
Installation  
Fan-Coil  
Coil Connections  
Vertical Units  
Fan-Coil  
Coil Connections  
Horizontal Units  
22  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Force Flo  
Coil Connections,  
Vertical Units  
Force Flo  
Force Flo  
Coil Connections,  
Inverted Units  
Coil Connections,  
Horizontal Units  
HR - Hot Water Return  
HS - Hot Water Supply  
UNT-SVX07A-EN  
23  
dim ensions  
& w eights  
Installation  
Fresh Air Opening Locations  
Horizontal Units Models C, D, and E  
Fresh Air Opening Dimensions, Horizontal Units  
Unit  
Size  
A
B
02-03  
1-6”  
04  
1-11”  
06  
2-8  
08  
3-5”  
10-12  
5-0”  
5-3 5/16”  
1
/2  
1-9 5/16” 2-2 5/16” 2-11 13/16” 3-8 5/16”  
24  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Fresh Air Opening Locations  
Vertical Units Models A, B, F, & J  
WALL HUNG  
Fresh Air Opening Dimensions, Vertical Units  
Unit  
Size  
A
B
02-03  
1-6”  
04  
1-11”  
06  
2-8  
08  
3-5”  
10-12  
5-0”  
5-3 5/16”  
1
/2  
1-9 5/16” 2-2 5/16” 2-11 13/16” 3-8 5/16”  
UNT-SVX07A-EN  
25  
dim ensions  
& w eights  
Installation  
Wall Box  
CONTINUOUS  
MORTAR RIBS  
TOP AND  
Wall Box Dimensions  
Unit Size  
Ref. Only  
02 - 03  
04  
Dimensions  
A x B  
Internal  
Supports  
BOTTOM  
3
3
24  
24  
/
/
x 4  
x 7  
7
/
1
1
2
3
4
8
4
3
1
/
2
8
1
06  
08  
33 1/8 x  
/
/
1
1
1
2
8
1
1
37  
58  
/
x 7  
x 7  
/
2
2
/
8
1
10 -12  
/
4
/
1
2
/
2
3
/
4
1
/
2
3
1 /8  
1
/
8
4
WOVENALUMINUM  
INSECTSCREEN  
CLEARANCE  
FOR DRAINAGE  
5
ADDITIONAL INTERNAL  
SUPPORTS EQUALLY SPACED.  
NOT TO EXCEED 12” O.C.  
/
8
CONTINUOUS DRIP LIP  
TOP AND BOTTOM  
26  
UNT-SVX07A-EN  
dim ensions  
& w eights  
Installation  
Projection Panel  
Projection Panel Dimensions  
Unit  
Size  
A
B
02 - 03  
3-11”  
2-6”  
04  
4-3”  
2-6”  
06  
5-3”  
2-6”  
08  
5-5  
2-9  
10 - 12  
1
1
1
/
/2  
2
7-5  
2-9  
/
/2  
2
1
UNIT TO WALL — TOP VIEW  
Projection Panel, All Unit Sizes  
C
D
E
2”  
1
8
2
1
8
1/2” 3”  
3
2
7
1/2” 4”  
4
3
6
1/2” 5”  
5
4
5
1/2” 6”  
1/8“  
5/8“  
5/8“  
1/8“  
2
7
1/8“  
5/8“  
5/8“  
1/8“  
3
6
1/8“  
5/8“  
5/8“  
1/8“  
4
5
1/8“  
5/8“  
5/8“  
1/8“  
5
4
1/8“  
5/8“  
FRONT VIEW ISO  
REAR VIEW ISO  
UNT-SVX07A-EN  
27  
pre-installation  
considerations  
Installation  
Installation Preparation  
!If a unit appears damaged, inspect it  
immediately before accepting the  
shipment. Manually rotate the fan  
wheel to ensure it turns freely. Make  
specific notations concerning the  
damage on the freight bill. Do not  
refuse delivery.  
!Inspect the unit for concealed damage  
before it is stored and as soon as  
possible after delivery. Report  
concealed damage to the freight line  
within the allotted time after delivery.  
Check with the carrier for their allotted  
time to submit a claim.  
!Do not move damaged material from  
the receiving location. It is the receivers  
responsibility to provide reasonable  
evidence that concealed damage did  
not occur after delivery.  
!Do not continue unpacking the  
shipment if it appears damaged. Retain  
all internal packing, cartons, and crate.  
Take photos of damaged material.  
!Notify the carriers terminal of the  
damage immediately by phone and  
mail. Request an immediate joint  
inspection of the damage by the carrier  
and consignee.  
!Notify your Trane representative of  
the damage and arrange for repair.  
Have the carrier inspect the damage  
before making any repairs to the unit.  
!Compare the electrical data on the unit  
nameplate with the ordering and  
shipping information to verify the  
correct unit is received.  
WARNING  
Before installing the unit, consider the  
following unit location recommendations  
to ensure proper unit operation.  
1. Clearances: Allow adequate service  
and code clearances as recommended  
in Service Access” section. Position  
the unit and skid assembly in its final  
location.  
2. Structural support: Ensure the  
structural support is strong enough to  
adequately support the unit. The  
installer is responsible for supply  
support rods for installation of ceiling  
units.  
3. Level: Verify the floor or foundation is  
level. Shim or repair as necessary. To  
ensure proper unit operation, install the  
unit level (zero tolerance) in both  
horizontal axes. Failure to level the unit  
properly can result in condensate  
management problems, such as  
standing water inside the unit.  
Ha za rd o u s Vo lt a g e w /Ca p a c it o rs !  
Disconnect all electric power, including  
rem ote disconnects and discharge all  
m otor start/run capacitors before  
servicing. Follow proper lockout/  
tagout procedures to ensure the  
power cannot be inadvertently  
energized. For variable frequency  
drives or other energy storing  
com ponents provided by Trane or  
others, refer to the appropriate  
m anufacturers literature for allowable  
waiting periods for discharge of  
capacitors. Verify with an appropriate  
voltm eter that all capacitors have  
discharged. Failure to disconnect  
power and discharge capacitors  
before servicing could result in death  
or serious injury.  
4. Condensate line & piping: Consider coil  
piping and condensate drain  
Receiving and Handling  
requirements. Verify condensate line is  
continuously pitched 1 inch per 10 feet  
of condensate line run to adequately  
drain condensate.  
5. Wall & ceiling openings: Vertical  
recessed/concealed units require wall/  
ceiling openings. Refer to submittal for  
specific dimensions before attempting  
to install. Horizontal recessed/concealed  
units must meet the requirements of  
the National Fire Protection Association  
(NFPA) Standard 90A or 90B  
concerning the use of concealed ceiling  
spaces as return air plenums. Refer to  
the submittal for specific dimensions of  
ceiling openings.  
6. Exterior: Touch up painted panels if  
necessary. If panels need paint, sanding  
is not necessary. However, clean the  
surface of any oil, grease, or dirt  
residue so the paint will adhere.  
Purchase factory approved touch up  
epoxy paint from your local Trane  
Service Parts Center and apply.  
Upon delivery, inspect all components for  
possible shipping damage. See the  
Receiving Checklist section for detailed  
instructions. Trane recommends leaving  
units and accessories in their shipping  
packages/skids for protection and ease of  
handling until installation.  
Shipping Package  
UniTrane fan-coil and Force Flo cabinet  
heaters ship in individual cartons for  
handling and storage ease. Each carton  
has tagging information such as the  
model number, sales order number, serial  
number, unit size, piping connections, and  
unit style to help properly locate the unit  
in the floor plan. If specified, the unit will  
ship with tagging designated by the  
customer.  
Jobsite Storage  
This unit is intended for indoor use only.  
Store the unit indoors to protect the unit  
from damage due to the elements. If  
indoor storage is not possible, make the  
following provisions for outdoor storage:  
1. Place the unit(s) on a dry surface or  
raised off the ground to assure  
adequate air circulation beneath unit  
and to assure that no portion of the unit  
contacts standing water at any time.  
2. Cover the entire unit with a canvas  
tarp only. Do not use clear, black or  
plastic tarps as they may cause  
Receiving Checklist  
Complete the following checklist  
immediately after receiving unit shipment  
to detect possible shipping damage.  
!
Inspect individual cartons before  
accepting. Check for rattles, bent carton  
corners, or other visible indications of  
shipping damage.  
excessive moisture condensation and  
equipment damage.  
28  
UNT-SVX07A-EN  
pre-installation  
considerations  
Installation  
Service Access  
Service access is available from the front  
on vertical units and from the bottom on  
horizontal units. Cabinet and recessed  
units have removable front or bottom  
panels to allow access into the unit. See  
Figure I-PC-1 for recommended service  
and operating clearances.  
24"  
12"  
both sides  
8.5"  
both sides  
Units have either right or left hand piping.  
Reference piping locations by facing the  
front of the unit (airflow discharges from  
the front). The control panel is always on  
the end opposite the piping.  
3"  
m odel A, vertical concealed  
m odel K, low vertical concealed  
m odel H, vertical recessed  
m odel B, vertical cabinet  
m odel L, low vertical cabinet  
The fan board assembly and main drain  
pan are easily removable for cleaning.  
See the“Maintenance” section for more  
details on servicing.  
36"  
Pre-Installation Checklist  
Complete the following checklist before  
beginning unit installation.  
12"  
both sides  
8.5"  
both sides  
24"  
front discharge  
!Verify the unit size and tagging with the  
unit nameplate.  
!Make certain the floor or foundation is  
level, solid, and sufficient to support the  
unit and accessory weights. See the  
Dimensions and Weights section. Level  
or repair the floor before positioning the  
unit if necessary.  
28"  
28"  
m odel C, horizontal concealed  
m odel E, horizontal recessed  
m odel D, horizontal cabinet  
!Allow minimum recommended  
clearances for routine maintenance and  
service. Refer to unit submittals for  
dimensions.  
Figure I-PC-1. Recommended service clearances  
!Allow one and one half fan diameters  
above the unit before the discharge  
ductwork makes any turns.  
UNT-SVX07A-EN  
29  
m echanical  
Installation  
requirem ents  
Duct Connections  
Note: Do not run screws through the  
removable front panel on concealed  
units.  
Connecting field piping to coil  
1. Remove the auxiliary drain pan, if it is  
in place, to prevent exposureto  
dripping solder or excessive  
temperatures.  
Install all air ducts according to National  
Fire Protection Association standards for  
the Installation of Air Conditioning and  
Ventilating Systems (NFPA 90A and 90B).  
Install all air ducts according to the  
National Fire Protection Association  
standards for the “Installation of Air  
Conditioning and Ventilation Systems  
other than Residence Type (NFPA 90A)  
and Residence Type Warm Air Heating  
and Air Conditioning Systems (NFPA  
90B).  
Ductwork Recommendations  
Follow the general recommendations  
listed below when installing  
2. Slide a 1/2-inch sweat connection  
coupling (installer provided) onto the  
coil headers.  
ductwork for the unit.  
1. Discharge ductwork should run in a  
straight line, unchanged in size or  
direction, for a minimum equivalent  
distance of three fan diameters from  
the unit (approximately 20 inches).  
2. When making duct turns and  
transitions avoid sharp turns and use  
proportional splits, turning vanes, and  
air scoops when necessary.  
Note: For vertical fan-coil units, push the  
main condensate drain hose and  
overflow condensate drain hose through  
the inside of the chassis end panel to  
prevent them from getting burned when  
making sweat connections. Be sure to  
pull the hoses back through and route to  
the auxiliary drain pan when the end  
panel has cooled.  
WARNING Ha za rd o u s  
Vo lt a g e w /Ca p a c it o rs ! Disconnect  
all electric power, including rem ote  
disconnects and discharge all m otor  
start/run capacitors before servicing.  
Follow proper lockout/tagout  
procedures to ensure the power  
cannot be inadvertently energized.  
For variable frequency drives or other  
energy storing com ponents provided  
by Trane or others, refer to the  
appropriate m anufacturers literature  
for allowable waiting periods for  
discharge of capacitors. Verify with an  
appropriate voltm eter that all  
capacitors have discharged. Failure to  
disconnect power and discharge  
capacitors before servicing could  
result in death or serious injury.  
3. When possible, construct, and orient  
supply ductwork turns in the same  
direction as the fan rotation.  
3. Solder the joint using bridgit lead-free  
solder (ASTM B32-89) to provide a  
watertight connection. Avoid  
overheating factory soldered joints  
when soldering field connections to the  
coil to prevent leakage from occurring.  
4. Insulate all piping to coil connections as  
necessary after connections are  
complete.  
Piping Considerations  
Hydronic Coil Piping  
Before installing field piping to the coil,  
consider the following .  
5
• All coil connections are /8-inch O.D. (or  
1/2-inch nominal) female copper  
connections.  
Note: Maintain a minimum distance of  
one foot between the reduction fitting for  
• The supply and return piping should not  
interfere with the auxiliary drain pan or  
condensate line. See “Connecting the  
Condensate Drain” section for more  
detailed information.  
• The installer must provide adequate  
piping system filtration and water  
treatment.  
1
the /2-inch diameter line and the fan-coil  
unit piping connections.  
5. Install the optional auxiliary drain pan,  
which ships in the accessory packet.  
• Exterior condensate may be an issue  
(fan-coils only) if field piping does not  
have a control valve. Refer to the  
supply and return header locations in  
the “Dimensions and Weights” section.  
The units airflow configuration varies  
dependent on the model and options  
ordered. A one-inch duct collar is  
provided on units with a ducted return  
and/or discharge to attach ductwork to  
the unit.  
Note: When using a field supplied piping  
package in a fan-coil unit, allow sufficient  
room to install the auxiliary drain pan. In  
addition, piping package must not extend  
over edges of auxiliary drain pan.  
Trane recommends using galvanized  
sheet metal ductwork with fan-coil and  
cabinet heater units. Slide the sheetmetal  
duct over the duct collar flange of the unit,  
seal the joint and fasten with sheetmetal  
screws.  
30  
UNT-SVX07A-EN  
m echanical  
Installation  
requirem ents  
Water Piping Connections to Factory-  
Installed Piping Package  
3. Slide the copper pipe over the drain  
pan nipple and tighten the collar on the  
pipe with a hose clamp (installer  
supplied).  
Automatic Changeover Sensor  
Two-pipe changeover units with either  
the Tracer ZN010, ZN510, and ZN520  
controls have an automatic changeover  
sensor that determines heating or cooling  
mode based on the supply water  
temperature. On units with a factory  
piping package, the factory straps the  
changeover sensor to the piping supply  
water pipe. See Figure I-MR-3 and I-MR-  
4.  
Before installing water piping supply and  
return lines to factory piping package,  
note the following items.  
Maintain a continuous drain line pitch of  
one inch per ten feet of drain line run to  
provide adequate condensate drainage.  
Extend the drain line straight from the  
drain pan a minimum distance of six  
inches before making any turns. The  
installer must provide proper support for  
the drain line to prevent undue stress on  
the auxiliary drain pan.  
• All piping connections are 5/8-inch O.D.  
(1/2-inch nominal) female copper  
connections.  
• The fan-coil supply and return piping  
should not interfere with the auxiliary  
drain pan or condensate line. See  
Connecting the Condensate Drain”  
section for more information.  
• The installer must provide adequate  
piping system filtration and water  
treatment.  
If the unit has a factory deluxe piping  
package, the piping includes a strainer  
with a 20-mesh size screen, which  
allows minimal protection from debris.  
Therefore, clean the strainer regularly.  
If the unit does not have a factory piping  
package, the factory attaches the sensor  
and coiled lead wires to the piping side  
end panel. The installer should attach the  
sensor parallel to and in direct contact  
with the supply water pipe.  
Install a secondary overflow drain line if  
necessary by punching out the overflow  
drain nipple on the auxiliary drain pan.  
3
Next, place a /8-inch inside diameter  
flexible plastic tube over the nipple and  
secure with a field supplied hose clamp.  
Note: The installer is responsible to  
ensure the changeover sensor is installed  
in a location that can sense active water  
temperature. Otherwise, the unit may fail  
to sense the correct operating mode and  
disable temperature control.  
Note: The installer is responsible for  
adequately insulating field piping. See the  
External Insulating Requirements  
section for more information.  
Note: Maintain a minimum distance of  
one foot between the reduction fitting for  
1
the /2-inch diameter line and the fan-coil  
piping connections.  
When using field supplied three-way  
valves, install the changeover sensor  
upstream of the valve on the supply  
water pipe. When using field supplied  
two-way control valves, install the  
changeover sensor in a location that will  
detect active water temperature. The  
unit must always be able to sense the  
correct system water temperature,  
regardless of the control valve position.  
Condensate Overflow Detection Device  
The condensate overflow detection  
device is an option on fan-coil units with  
either a Tracer ZN010, ZN510, ZN520 or  
the customer-supplied control interface.  
The float switch, mounting bracket, and  
coiled leads ship attached inside the  
piping end pocket of the unit. Install the  
switch by placing the hole or slot in the  
bracket over the condensate overflow  
drain (of the auxiliary drain pan) with the  
switch float extending over the pan.  
Secure the drain pan by attaching the  
pans bracket with the factory  
1. The factory piping package ships with  
brackets to adequately support the  
piping during shipment. Remove these  
brackets before connecting water  
piping to the unit.  
2. Close the piping end valves to the fully  
open position to prevent damage to the  
valve seat during brazing.  
3. Remove the auxiliary drain pan, if it is  
in place, to prevent exposure to  
dripping solder or excessive  
Note: The maximum length of the  
automatic changeover wire cannot  
exceed ten feet from the control panel. If  
the sensor extends beyond the unit  
chassis, use shielded conductors to  
eliminate radio frequency interference  
(RFI).  
temperatures.  
4. Solder water piping connections to  
supply and return end connections.  
Avoid overheating factory soldered  
joints to prevent the possibility of  
leakage.  
provided clip. See Figures I-MR-1 and I-  
MR-2.  
5. Insulate fan-coil piping to auxiliary  
drain pan connections and any piping  
that is not above the auxiliary drain pan.  
Condensate Drain  
1. De-burr the pipe end before making  
the connection to the drain pan.  
7
2. Connect a /8-inch O.D. copper pipe or  
tube, with a 0.20 inch wall thickness, to  
the auxiliary drain pan. This should be a  
mechanical connection that allows easy  
removal of the auxiliary drain pan  
when servicing the piping end pocket.  
Figure I-MR-1. Condensate float switch  
installed in horizontal auxilliary drain pan.  
Figure I-MR-2. Condensate float switch  
installed in vertical auxilliary drain pan.  
UNT-SVX07A-EN  
31  
m echanical  
Installation  
requirem ents  
Automatic Electric Heat Lockout Switch  
Two-pipe fan-coil units with auxiliary  
electric heat have an automatic electric  
heat lockout switch that disengages the  
electric heat when hydronic heat enables.  
If the unit has a factory piping package  
and electric heat, the factory attaches the  
switch to the supply water pipe. When  
the lockout switch detects the supply  
water temperature above 95°F, it  
disengages the electric heat. This  
eliminates electric heat and hydronic heat  
working simultaneously.  
Figure I-MR-7. Electric heat lock out switch  
installed  
Figure I-MR-3. Attach the changeover  
sensor to the entering water pipe as shown  
for changeover to work properly  
If the fan-coil unit does not have a factory  
piping package, the switch and coiled lead  
wires ship inside the piping side end  
panel. The installer should position the  
lockout switch on the supply water line of  
the unit by sliding its spring connector  
over the pipe. See I-MR-7.  
External Insulating Requirements  
Insulate and vapor seal surfaces colder  
than surrounding air dew-point a to  
prevent unplanned condensation. Trane  
recommends field-insulation of the  
following areas to prevent potential  
condensate problems:  
1. Supply and return water piping  
connections  
2. Condensate drain lines and  
connections  
Venting the Hydronic Coil  
The hydronic coil contains a vent, either  
manual or automatic, to release air from  
the unit. This vent is not sufficient for  
venting the water piping system in the  
building.  
3. Fresh air intake duct connections  
4. Discharge duct connections  
5. Wall boxes  
The coil air vent is on the piping side,  
above the coil connections on the unit.  
See Figure I-MR-5 and I-MR-6. Perform  
the following steps to vent the coil after  
installing the unit.  
Figure I-MR-4. Close-up view of the  
changeover sensor  
1. Pressurize the building piping system  
with water and vent any trapped air at  
system vents.  
2. For units with manual air vents, back  
the set screw out to expel air from the  
unit and then re-tighten the set screw.  
The automatic air vent should require no  
adjustment for the coil to vent. However,  
if the coil does not vent immediately,  
unscrew the outer portion of the fitting to  
expel air from the port.  
Figure I-MR-5. Manual coil air vent with set  
screw  
If debris has become trapped in the vent,  
completely remove the outer portion of  
the fitting and clean.  
Figure I-MR-6. Manual coil air vent with  
Shrader fitting  
32  
UNT-SVX07A-EN  
m echanical  
Installation  
requirem ents  
Balancing The Manual Circuit Setter  
Valve  
5. Adjust the circuit setter valve by  
turning the valve stem until the  
The manual circuit setter valve is an  
optional end valve supplied on the return  
pipe of the factory piping package. The  
valve allows the operator to regulate  
water flow through the hydronic coil,  
balance the water flow through the unit  
with other units in the piping system, and  
serves as a shutoff or end valve. See  
Figure I-MR-8.  
appropriate pressure drop is achieved.  
6. After achieving the proper setting,  
slightly loosen the two socket head cap  
screws and rotate the memory stop  
around until it touches the back side of  
the indicator. Then tighten the screws to  
securely set the open memory position.  
The memory stop indicates the last set  
open position.  
7. If using a three-way valve: close the  
control valve to the coil, with the  
differential pressure meter still  
connected. This will divert flow to the  
bypass side of a three-way valve.  
Follow the procedure below to set  
maximum water flow through the coil.  
1. Establish water flow through the coil.  
Perform an open override of the valve if  
the control valve is closed to the coil,  
either manually or by Tracer.  
If the piping package has two-position,  
normally closed valves: Drive open the  
valve using a 24V signal.  
Figure I-MR-9. Automatic circuit setter valve  
Adjust the balancing fitting to obtain the  
same pressure drop across the circuit  
setter valve as in step two when the  
control valve was open to the coil.  
If the piping package has two-position,  
normally open valves: Manually drive  
open the valve by removing power to  
the valve.  
If the piping package has modulating  
valves: To manually drive the valve  
open, depress the button stem on top of  
the valve and push the lever located on  
the side of the valve to the full open  
position.  
Figure I-MR-10. Automatic circuit setter  
valve  
2. For presetting, use the appropriate  
valve curve shown in Chart I-MR-1 on  
page 34 to determine which setting is  
necessary to achieve the appropriate  
pressure drop. The “M” line is the  
appropriate line.  
Figure I-MR-8. Manual circuit setter valve  
3. Carefully remove the Schrader  
pressure port connection caps on the  
manual circuit setter, since they will be  
at the same temperature as the  
pipeline.  
4. Bleed all air from the hoses and meter  
before reading the pressure drop. Refer  
to the gauge operating instructions.  
UNT-SVX07A-EN  
33  
m echanical  
Installation  
requirem ents  
Note: Instructions for using this chart are on the previous page. For the manual  
circuit setter provided with the fan-coil or Force Flo, use the 'M' line for reference.  
Chart I-MR-1. Manual circuit setter valve, differential pressure vs. flow  
34  
UNT-SVX07A-EN  
m echanical  
Installation  
requirem ents  
Steam Piping  
CAUTION  
Co il Da m a g e !  
In all steam coil installations, the  
condensate return connections m ust  
be at the low point of the coil to  
ensure condensate flows freely from  
the coil at all tim es. Failure to do so  
m ay cause physical coil dam age from  
water ham m er, unequal therm al  
stresses,freeze-up and/or corrosion.  
1. Make piping connections to the steam  
coil as shown in Figure I-MR-11. Cap the  
unused connection.  
2. The coil is already pitched within the  
unit to provide proper pitch to drain  
condensate out of the coil. Verify that  
the unit has been properly leveled.  
1
3. Install a /2-inch, 15-degree swing check  
vacuum breaker in the unused  
condensate return tapping as close as  
possible to the coil.  
4. Vent the vacuum breaker line to  
atmosphere or connect it into the return  
main at the discharge side of the steam  
trap.  
5. Pitch all steam supply and return mains  
down a minimum of one inch per ten  
feet in the direction of flow.  
6. Do not drain the steam mains or take-  
off through the coils. Drain the mains  
ahead of the coils through a steam trap  
to the return line.  
7. Overhead returns require one psig of  
pressure at the steam trap discharge  
for each two-feet elevation to ensure  
continuous condensate removal.  
8. Proper steam trap selection and  
installation is necessary for satisfactory  
coil performance and service life. For  
installation, use the following steps:  
a. Position the steam trap discharge at  
least 12 inches below the condensate  
return connection. This provides  
sufficient hydrostatic head pressure to  
overcome trap losses and ensure  
complete condensate removal.  
Figure I-MR-2. Typical Piping for Steam Coils  
Code of System Components in Piping  
Diagram  
FT  
Float and thermostatic steam trap  
Bucket steam trap  
Gate valve  
Automatic two-position (on-off) control valve  
Automatic three-way control valve  
Vacuum breaker  
Check valve  
Strainer  
Automatic or manual air vent  
BT  
GV  
OV  
TV  
VB  
CV  
ST  
AV  
b. Trane recommends using flat and  
thermostatic traps because of gravity  
drain and continuous discharge  
operation.  
c. Use float and thermostatic traps with  
atmospheric pressure gravity  
condensate return, with automatic  
controls or where the possibility of low  
pressure supply steam exists.  
d. Always install strainers as close as  
possible to the trap inlet side. Reference  
Figure I-MR-10 for an example of a  
properly piped steam coil.  
vacuum breaker (if desired)  
steam supply  
plugged  
condensate return  
Figure I-MR-11. Main steam coil connection  
diagram  
UNT-SVX07A-EN  
35  
electrical  
Installation  
requirem ents  
Unit Wiring Diagrams  
Specific unit wiring diagrams are  
Note: All field wiring should conform to  
NEC and all applicable state and local  
code requirements. The control panel box  
is always on the end opposite the piping  
connections. Access the control box by  
removing the two screws that secure the  
front cover. This will allow the panel to be  
removed, to provide access to the  
electrical components.  
Wall Mounted Control  
Interconnection Wiring  
provided inside each unit and can be  
easily removed for reference.Use these  
diagrams for connections or trouble  
analysis. Wiring diagrams are attached  
on the inside of the front panel of vertical  
cabinet & recessed models and on the fan  
and motor panel of vertical concealed &  
all horizontal models.  
The installer must provide interconnec-  
tion wiring to connect wall mounted  
devices such as a fan mode switch or  
zone sensor module.  
Refer to the unit wiring schematic for  
specific wiring details and point-to-point  
wiring connections. Dashed lines indicate  
field wiring on the unit wiring schematics.  
All interconnection wiring must conform  
to NEC Class 2 wiring requirements and  
any state and local requirements.  
WARNING  
Supply Power Wiring  
Ha za rd o u s Ele c t ric a l S h o rt s !  
Insulate all power wire from sheet  
m etal ground. Failure to do so m ay  
cause electrical shorts that could  
result in death or serious injury.  
WARNING  
Refer to Table I-ER-1 for the wire size  
range and maximum wiring distance for  
each device.  
Ha za rd o u s Vo lt a g e w /Ca p a c it o rs !  
Disconnect all electric power, including  
rem ote disconnects and discharge all  
m otor start/run capacitors before  
servicing. Follow proper lockout/  
tagout procedures to ensure the  
power cannot be inadvertently  
energized. For variable frequency  
drives or other energy storing  
com ponents provided by Trane or  
others, refer to the appropriate  
m anufacturers literature for allowable  
waiting periods for discharge of  
capacitors. Verify with an appropriate  
voltm eter that all capacitors have  
discharged. Failure to disconnect  
power and discharge capacitors  
before servicing could result in death  
or serious injury.  
Recommendation: Do not bundle or run  
interconnection wiring in parallel with or  
in the same conduit with any high-voltage  
wires (110V or greater). Exposure of  
interconnection wiring to high voltage  
wiring, inductive loads, or RF transmitters  
may cause radio frequency interference  
(RFI). In addition, improper separation  
may cause electrical noise problems.  
Therefore, use shielded wire (Beldon  
83559/83562 or equivalent) in applica-  
tions that require a high degree of noise  
immunity. Connect the shield to the  
If the unit does not have a disconnect  
switch, the power leads and capped  
ground wire are inside the control panel.  
If the unit has a disconnect switch, the  
power leads are wired to the junction box  
switch on the control panel. Pull the  
capped ground wire into the junction box.  
Electrical Grounding  
Restrictions  
chassis ground and tape at the other end.  
All sensor and input circuits are normally  
at or near ground (common) potential.  
When wiring sensors and other input  
devices to the Tracer controller, avoid  
creating ground loops with grounded  
conductors external to the unit control  
circuit. Ground loops can affect the  
Table I-ER-1. Maximum wiring distances for  
low voltage controls, ft.  
device  
wire size  
range  
500  
measurement accuracy of the controller.  
Refer to the unit nameplate to obtain the  
minimum circuit ampacity (MCA) and  
maximum fuse size (MFS) or maximum  
circuit breaker (MCB) to properly size field  
supply wiring and fuses or circuit  
breakers.  
fan speed switch  
zone sensor  
14 - 22 AWG  
16 - 22 AWG  
200  
CAUTION  
Eq u ip m e n t Da m a g e !  
Note: Do not connect any sensor or input  
circuit to an external ground connection.  
Unit transform er IT1 provides power  
to fan-coil unit only. Field connections  
to the transform er IT1 m ay create  
im m ediate or prem ature unit  
com ponent failure.  
Refer to the unit operating voltage listed  
on the unit wiring schematic, submittal, or  
nameplate. Reference the wiring sche-  
matic for specific wiring connections.  
All input/output circuits (except isolated  
relay contacts and optically isolated  
inputs) assume a grounded source, either  
a ground wire at the supply transformer  
to control panel chassis, or an installer  
supplied ground.  
CAUTION  
Us e Co p p e r Co n d u c t o rs On ly!  
Unit term inals are not designed to  
accept other type conductors. Failure  
to use copper conductors m ay result  
in equipm ent dam age.  
36  
UNT-SVX07A-EN  
electrical  
Installation  
requirem ents  
Table I-ER-2. Low vertical free discharge  
motors, 115 volt  
Table I-ER-4. Free discharge motors on units with two-row, electric, or steam coils  
unit  
size  
02  
115 volt  
FLA hp (kW)  
0.6 .03 (.02)  
0.7 .04 (.02)  
0.9 .05 (.04)  
1.2 .07 (.05)  
1.4 .12 (.09)  
0.9 .05 (.04)  
1.2 .07 (.05)  
0.9 .05 (.04)  
1.4 .12 (.09)  
208-230 volt  
FLA hp (kW)  
0.3 .03 (.02)  
0.4 .04 (.02)  
0.5 .05 (.04)  
0.6 .07 (.05)  
0.9 .12 (.09)  
0.5 .05 (.04)  
0.6 .07 (.05)  
0.5 .05 (.04)  
0.9 .12 (.09)  
277-480 volt  
FLA hp (kW)  
0.2 .03 (.02)  
0.3 .04 (.02)  
0.4 .05 (.04)  
0.5 .07 (.05)  
0.6 .12 (.09)  
0.4 .05 (.04)  
0.5 .07 (.05)  
0.4 .05 (.04)  
0.6 .12 (.09)  
rpm  
M
H
L
size  
03  
FLA  
0.7  
HP (kW)  
.03 (0)  
RPM  
1090  
980 840 655  
980 780 580  
1050 780 580  
1030 780 580  
1080 800 600  
1050 780 580  
1030 780 580  
1050 780 580  
108 800 600  
H
M
L
H
M
L
H
M
L
03  
04  
06  
08  
770  
560  
1090  
750  
560  
1115  
760  
04  
06  
0.8  
1.1  
.03 (0)  
.03 (0)  
10  
12  
560  
Note:  
Actual rpm will vary with application and configuration.  
Table I-ER-5. High static motors on units with two-row, electric, or steam coils  
unit  
size  
02  
03  
04  
06  
08  
10  
115 volt  
FLA hp (kW)  
1.1 .07 (.05)  
1.4 .08 (.06)  
1.6 .10 (.07)  
2.6 .16 (.12)  
3.4 .24 (.18)  
1.6 .10 (.07)  
2.6 .16 (.12)  
1.6 .10 (.07)  
3.4 .24 (.18)  
208-230 volt  
FLA hp (kW)  
0.6 .07 (.05)  
0.7 .08 (.06)  
0.8 .10 (.07)  
1.2 .16 (.12)  
1.4 .24 (.18)  
0.8 .10 (.07)  
1.2 .16 (.12)  
0.5 .10 (.07)  
0.9 .24 (.18)  
277- 480 volt  
FLA hp (kW)  
0.5 .07 (.05)  
0.6 .08 (.06)  
0.7 .10 (.07)  
1.0 .16 (.12)  
1.1 .24 (.18)  
0.7 .10 (.07)  
1.0 .16 (.12)  
0.7 .10 (.12)  
1.1 .24 (.18)  
rpm  
M
1480 1110  
1400 1175  
1475 1315 1070  
1400 1070  
1475 1285  
1475 1315 1070  
1400 1070 855  
1475 1315 1240  
1475 1285 975  
Table I-ER-3. Decimal to fractional HP (kW)  
conversion  
H
L
865  
860  
FC  
02  
Decimal  
.03  
Fraction  
1/30  
1/15  
1/25  
1/20  
1/12  
1/20  
1/16  
1/10  
1/8  
.07  
855  
975  
03  
04  
.04  
.05  
.08  
.05  
12  
.06  
.10  
.13  
06  
.07  
.12  
1/15  
1/8  
Table I-ER-6. Free discharge motors on units with three and four-row coils  
.16  
.24  
.12  
.13  
1/6  
1/4  
1/8  
1/8  
unit  
size  
02  
03  
04  
06  
08  
10  
115 volt  
FLA hp(kW)  
208-230 volt  
FLA hpP (kW)  
0.3 .03 (.02)  
0.5 .05 (.04)  
0.6 .06 (.04)  
0.9 .12 (.09)  
1.0 .13 (.10)  
0.6 .06 (.04)  
0.9 .12 (.09)  
0.6 .06 (.04)  
1.0 .13 (.10)  
277-480 volt  
FLA hp (kW)  
0.2 .03 (.02)  
0.4 .05 (.04)  
0.5 .06 (.04)  
0.6 .12 (.09)  
0.8 .13 (.10)  
0.5 .06 (.04)  
0.6 .12 (.09)  
0.5 .06 (.04)  
0.8 .13 (.10)  
rpm  
M
H
980  
L
08  
10  
0.6  
0.8  
1.0  
1.4  
1.7  
1.0  
1.4  
1.0  
1.7  
.03 (.02)  
.05 (.04)  
.06 (.04)  
.12 (.09)  
.13 (.10)  
.06 (.04)  
.12 (.09)  
.06 (.04)  
.13 (.10)  
840  
800  
800  
800  
800  
800  
800  
800  
800  
655  
600  
600  
600  
600  
600  
600  
600  
600  
1080  
1080  
1080  
1080  
1080  
1080  
1080  
1080  
.24  
1/4  
.05  
.07  
.12  
.16  
.24  
.12  
.13  
.24  
.24  
1/20  
1/15  
1/8  
1/6  
1/4  
1/8  
1/8  
1/4  
1/4  
.06  
.10  
.13  
.05  
.06  
.10  
.13  
1/16  
1/10  
1/8  
1/20  
1/16  
1/10  
1/8  
12  
12  
low vertical  
03, 04, 06  
.03  
1/30  
Table I-ER-7. High static motors on units with three and four-row coils  
unit  
size  
02  
115 volt  
hp (kW)  
.07 (.05)  
.08 (.06)  
.13 (.10)  
.24 (.18)  
.24 (.18)  
.13 (.10)  
.24 (.18)  
.13 (.10)  
.24 (.18)  
208-230 volt  
FLA hp (kW)  
0.6 .07 (.05)  
0.7 .08 (.06)  
0.9 .13 (.10)  
1.4 .24 (.18)  
1.4 .24 (.18)  
0.9 .13 (.10)  
1.4 .24 (.18)  
0.9 .13 (.10)  
1.4 .24 (.18)  
277-480 volt  
FLA hp (kW)  
0.5 .07 (.05)  
0.5 .08 (.06)  
0.7 .13 (.10)  
1.1 .24 (.18)  
1.1 .24 (.18)  
0.7 .13 (.10)  
1.1 .24 (.18)  
0.7 .13 (.10 )  
1.1 .24 (.18)  
rpm  
M
Note:  
FLA  
1.1  
1.3  
2.1  
3.4  
3.4  
2.1  
3.4  
2.1  
3.4  
H
L
865  
1110  
1240  
975  
975  
1240  
975  
1240  
975  
Values for fractional HPs (kWs) are approximate values and  
not necessarily the actual HP (kW).  
1480 1110  
1500 1355  
1580 1375  
1475 1285  
1475 1285  
1580 1375  
1475 1285  
1580 1375  
1475 1285  
03  
04  
06  
08  
10  
12  
Note: Actual rpm will vary with application and configuration. Size 10 & 12 units have two m otors.  
UNT-SVX07A-EN  
37  
electrical  
Installation  
requirem ents  
Table I-ER-8. Fan-coil electric heat kW  
Unit Size  
02  
Unit Voltage  
115  
230  
277  
208  
115  
230  
277  
208  
115  
230  
277  
208  
115  
230  
277  
208  
115  
230  
277  
208  
115  
230  
277  
208  
115  
230  
277  
208  
kW  
1.0  
1.0  
1.0  
0.8  
1.0  
1.0  
1.0  
0.8  
kW  
1.5  
1.5  
1.5  
1.1  
1.5  
1.5  
1.5  
1.1  
kW  
2.0  
2.0  
2.0  
1.5  
2.0  
2.0  
2.0  
1.5  
2.0  
2.0  
2.0  
1.5  
2.0  
2.0  
2.0  
1.5  
2.0  
2.0  
2.0  
1.5  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
kW  
1.9  
2.5  
2.5  
2.5  
1.9  
2.5  
2.5  
2.5  
1.9  
03  
04  
06  
08  
10  
12  
2.3  
3.0  
3.0  
3.0  
2.3  
3.0  
3.0  
3.0  
2.3  
3.0  
3.0  
3.0  
2.3  
3.0  
3.0  
3.0  
2.3  
3.0  
3.0  
3.0  
2.3  
3.0  
4.0  
4.0  
3.0  
5.0  
5.0  
3.8  
6.0  
6.0  
4.5  
5.3  
4.0  
4.0  
3.0  
5.0  
5.0  
3.8  
6.0  
6.0  
4.5  
7.0  
7.0  
5.3  
6.0  
4.0  
4.0  
3.0  
5.0  
5.0  
3.8  
6.0  
6.0  
4.5  
7.0  
7.0  
5.3  
8.0  
8.0  
6.0  
4.0  
4.0  
3.0  
5.0  
5.0  
3.8  
6.0  
6.0  
4.5  
7.0  
7.0  
5.3  
8.0 10.0  
8.0 10.0  
6.0  
Table I-ER-9. Electric heat kW, low vertical fan-coils  
unit size  
unit voltage  
kW  
1.0  
1.0  
1.0  
kW  
1.5  
1.5  
1.5  
kW  
kW  
03  
04  
06  
115  
115  
115  
2.0  
2.0  
2.0  
2.5  
2.5  
Low vertical units are only available with electric heat in combination with the two-row cooling coil.  
Minimum Circuit Ampacity (MCA) and Maximum Fuse Size (MFS) Calculations for  
Fan-Coils with Single Phase Electric Heat  
Heater amps = (heater kW x 1000)/heater voltage  
Note: Use 120V heater voltage for 115V units. Use 240V heater voltage for 230V units.  
MCA = 1.25 x (heater amps + all motor FLAs)  
MFS or HACR type circuit breaker = (2.25 x largest motor FLA) + second motor FLA  
+ heater amps (if applicable)  
HACR (heating, air-conditioning and refrigeration) type circuit breakers are required in  
the branch circuit wiring for all fan-coils with electric heat.  
Select a standard fuse size or HACR type circuit breaker equal to the MCA.  
Use the next larger standard size if the MCA does not equal a standard size.  
Standard fuse sizes are: 15, 20, 25, 30, 35, 40, 45, 50, 60 amps  
Fan-coil electric heat MBh = (heater kW) (3.413)  
38  
UNT-SVX07A-EN  
electrical  
requirem ents  
Installation  
Table I-ER-10. Force Flo single-stage, max kW electric heat  
unit  
size  
heater  
kW  
2.25  
3.0  
3.0  
2.25  
3.0  
3.0  
4.5  
6.0  
6.0  
4.5  
6.0  
6.0  
5.7  
7.5  
7.5  
5.7  
7.5  
heater  
amps/ph  
10.9  
12.5  
10.9  
6.3  
volts  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
hz  
60  
phase  
wires  
2
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
3
4
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
02  
03  
04  
06  
7.3  
3.7  
21.7  
25.0  
21.7  
12.6  
14.5  
7.3  
27.5  
31.3  
27.1  
15.9  
18.1  
9.1  
38.0  
43.8  
38.0  
21.9  
25.3  
12.7  
60  
60  
60  
7.5  
7.9  
10.5  
10.5  
7.9  
10.5  
10.5  
Note: All data based on individual units. Electric heat will operate only with fan at high speed.  
Table I-ER-11. Force Flo single stage, low kW electric heat  
unit size  
02  
voltage  
# wires  
kW  
amps/ph  
kW amps/ph  
kW  
amps/ph  
208/60/1  
240/60/1  
277/60/1  
2
2
2
0.75  
1.0  
1.0  
3.7  
4.2  
3.7  
1.5  
2.0  
2.0  
7.3  
8.4  
7.3  
03  
04  
06  
08  
10  
12  
208/60/1  
240/60/1  
277/60/1  
208/60/3  
240/60/3  
480/60/3  
2
2
2
3
3
4
2.25  
3.0  
10.9  
12.5  
10.9  
6.3  
3.0  
2.25  
3.0  
3.0  
7.3  
3.7  
208/60/1  
240/60/1  
277/60/1  
208/60/3  
240/60/3  
480/60/3  
2
2
2
3
3
4
2.25  
3.0  
10.9  
12.5  
10.9  
6.3  
7.3  
3.7  
3.0  
2.25  
3.0  
3.0  
208/60/1  
240/60/1  
277/60/1  
208/60/3  
240/60/3  
480/60/3  
2
2
2
3
3
4
2.25  
3.0  
10.9  
12.5  
10.9  
6.3  
7.3  
3.7  
3.3  
4.5  
4.5  
3.3  
4.5  
4.5  
15.9  
18.8  
16.3  
9.2  
10.9  
5.5  
3.0  
2.25  
3.0  
3.0  
208/60/1  
240/60/1  
277/60/1  
208/60/3  
240/60/3  
480/60/3  
2
2
2
3
3
4
2.25  
3.0  
10.9  
12.5  
10.9  
6.3  
7.3  
3.7  
3.3  
4.5  
4.5  
3.3  
4.5  
4.5  
15.9  
18.8  
16.3  
9.2  
10.9  
5.5  
4.5  
6.0  
6.0  
4.5  
6.0  
6.0  
21.7  
25.0  
21.7  
12.5  
14.5  
7.3  
3.0  
2.25  
3.0  
3.0  
208/60/1  
240/60/1  
277/60/1  
208/60/3  
240/60/3  
480/60/3  
2
2
2
3
3
4
2.25  
3.0  
10.9  
12.5  
10.9  
6.3  
7.3  
3.7  
3.3  
4.5  
4.5  
3.3  
4.5  
4.5  
15.9  
18.8  
16.3  
9.2  
10.9  
5.5  
5.7  
7.5  
7.5  
5.7  
7.5  
7.5  
27.5  
31.3  
27.1  
15.9  
18.1  
9.1  
3.0  
2.25  
3.0  
3.0  
208/60/1  
240/60/1  
277/60/1  
208/60/3  
240/60/3  
480/60/3  
2
2
2
3
3
4
2.25  
3.0  
10.9  
12.5  
10.9  
6.3  
7.3  
3.7  
3.3  
4.5  
4.5  
3.3  
4.5  
4.5  
15.9  
18.8  
16.3  
9.2  
10.9  
5.5  
6.6  
9.0  
9.0  
6.6  
9.0  
9.0  
31.8  
37.5  
32.5  
18.4  
21.7  
10.9  
3.0  
2.25  
3.0  
3.0  
Note: All data based on individual units. Electric heat will operate only with fan at high speed.  
UNT-SVX07A-EN  
39  
electrical  
requirem ents  
Installation  
Table I-ER-12. Force Flo 2-stage electric heat  
unit  
size  
1st stage  
kW  
0.75  
1.0  
1.0  
0.75  
1.0  
1.0  
1.5  
2.0  
2.0  
1.5  
2.0  
2.0  
1.9  
2.5  
2.5  
1.9  
2.5  
2.5  
3.4  
4.5  
4.5  
3.4  
4.5  
4.5  
4.5  
6.0  
6.0  
4.5  
6.0  
6.0  
6.0  
8.0  
8.0  
6.0  
8.0  
8.0  
6.8  
9.0  
9.0  
6.8  
9.0  
9.0  
total  
kW  
2.25  
3.0  
3.0  
2.25  
3.0  
3.0  
4.5  
6.0  
6.0  
4.5  
6.0  
6.0  
5.7  
7.5  
7.5  
5.7  
7.5  
total  
amps/ph  
10.9  
12.5  
10.9  
6.3  
volts  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
208  
240  
277  
208  
240  
480  
hz  
60  
phase  
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
1
1
1
3
3
3
wires  
2
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
3
4
2
2
2
3
3
4
02  
7.3  
3.7  
21.7  
25.0  
21.7  
12.6  
14.5  
7.3  
27.5  
31.3  
27.1  
15.9  
18.1  
9.1  
38.0  
43.8  
38.0  
21.9  
25.3  
12.7  
48.8  
56.3  
48.8  
28.2  
32.5  
16.3  
65.0  
75.0  
65.0  
37.6  
43.3  
21.7  
72.3  
83.4  
72.3  
41.7  
48.2  
24.1  
03  
04  
06  
08  
10  
12  
60  
60  
60  
60  
60  
60  
7.5  
7.9  
10.5  
10.5  
7.9  
10.5  
10.5  
10.1  
13.5  
13.5  
10.1  
13.5  
13.5  
13.5  
18.0  
18.0  
13.5  
18.0  
18.0  
15.0  
20.0  
20.0  
15.0  
20.0  
20.0  
Note: When both stages are on, the electric heat will operate only when fan is in high speed. All data based on  
individual units.  
40  
UNT-SVX07A-EN  
installation  
procedure  
Installation  
5. Complete piping and wiring  
connections.  
necessary ductwork as instructed in the  
following sections. Ensure that the  
auxiliary drain pan is in position on fan-  
coil units.  
6. Install the bottom panel before starting  
the unit.  
7. Ensure condensate drain line is pitched  
one inch per ten feet of pipe away from  
the fan-coil unit.  
bottom. Slide the front panel down onto  
the tabs while holding the panel close as  
possible to the cabinet. While the bottom  
tabs are engaged, slide the front panel  
upward enough to allow the top engaging  
edge of the front panel to lap over the  
engaging edge of the unit. This should  
allow the panel to drop down and lock  
into position.  
Installing the Unit  
Follow the procedures below to install the  
unit properly. Reference the “Dimensions  
and Weights” section for specific unit  
dimensions and mounting hole locations.  
Vertical Units  
CAUTION  
Ele c t ric a l Wirin g !  
On recessed units, install the front panel  
by aligning and locking together the  
Do not allow electrical wire to fall  
between the unit and installation  
surface. Failure to com ply m ay result  
in electrical shorts or difficulty  
accessing wires.  
Cabinet units  
interlocking support channel of the panel  
and unit. While holding the panel against  
the unit, tighten the screws at the top of  
the panel until it fits tight against the units  
front. Do not over tighten the screws.  
Install the bottom panel by placing the  
hinged end on the units hinged end  
(always at the return end of the unit).  
Reference the Dimensions & Weights  
section for keyslot hanger hole locations.  
Swing the panel upward into position.  
Secure the panel with the fasteners  
provided. Do not overtighten the  
fasteners.  
Install vertical units in an upright position  
using the 5/8-inch diameter double key slot  
hanger holes, located on the back of unit.  
The hanger holes allow a maximum  
shank size of 5/16-inch diameter threaded  
rods or lag screws (installer provides).  
1. Prepare wall openings for recessed  
units. Reference unit submittal for each  
unit size dimensions. When installing  
vertical units, consideration should be  
given for units with an outside air  
intake.  
CAUTION  
Mo t o r Ove rlo a d !  
All unit panels and filters m ust be in  
place prior to unit startup. Failure to  
have panels and filters in place m ay  
cause m otor overload.  
Recessed units  
Reference the Dimensions & Weights  
section for mounting locations and unit  
weights. Follow the procedure below and  
reference Figure I-IP-1.  
1. Insert the mounting bolts through the  
panel brackets of the trim ring and  
secure to the hanger holes on the unit.  
Tighten the mounting bolts to pull the  
trim ring snug against the finished  
ceiling.  
2. Install the bottom panel by placing the  
hinged end on the trim ring hinged end  
(always at the units return end).  
3. Adjust the expansion collars inner duct  
(only on fan-coil units with a bottom  
return) to ensure a tight fit against the  
insulation located on the perimeter of  
the bottom panels return louver.  
4. Close the s-hook on each end of safety  
chain assembly. Insert s-hooks through  
holes in unit and door. Close s-hook on  
door.  
Horizontal Units  
Install horizontal units suspended from  
the ceiling using the four 5/8-inch diameter  
double key slot hanger holes, located on  
the top of the unit. The hanger holes allow  
a maximum shank size of 5/16-inch  
diameter threaded rods or lag screws  
(installer provided). Follow the installation  
procedure below.  
2. If the unit has leveling legs, adjust them  
correctly to level unit.  
3. Mark the position of the keyslot hanger  
holes on the wall according to the  
dimensions given in the Dimensions &  
Weights section for each unit model  
and size. Align the hole locations evenly.  
4. Insert the threaded rods or lag screws  
in the wall before setting the unit in  
place.  
5. Remove the front panel (cabinet unit  
only) by lifting it upward.  
6. Position the hanger holes, located on  
the back of the unit, over the rod or lag  
screw heads, pushing the unit  
downward to properly position.  
7. Complete piping and wiring  
Note: Follow the requirements of  
National Fire Protection Association  
(NFPA) Standard 90A or 90B, concerning  
the use of concealed ceiling spaces as  
return air plenums.  
1. Prepare the ceiling opening for  
recessed units. Reference the unit  
submittals for dimensions.  
2. Position and install the suspension rods  
or a suspension device (supplied by  
installer) according to the unit model  
and size in the Dimensions & Weights  
section.  
3. On cabinet units, remove the bottom  
panel by using a 5/32-inch Allen wrench  
to unscrew fasteners. Swing the panel  
down and lift outward.  
4. Level the unit by referencing the  
chassis end panels. Adjust the  
suspension device.  
5. Insert retaining screws through bottom  
panel door and place retaining rings on  
screws.  
6. Swing the bottom panel upward into  
position. Hook the safety chain to the  
bottom panel and the unit. Tighten the  
panel to the unit with the fasteners  
provided.  
connections, in addition to any  
necessary ductwork to the unit as  
instructed in the following sections.  
Ensure that the auxiliary drain pan is in  
position on fan-coil units.  
8. Install the front panel before starting  
the unit.  
On cabinet units, replace the front panel  
by aligning the bottom tabs on the unit  
with the respective slots on the panel  
UNT-SVX07A-EN  
41  
installation  
procedure  
Installation  
CAUTION  
Unit Leveling!  
All unit panels and filters m ust be in  
place prior to unit start-up. Failure to  
have panels and filters in place m ay  
cause m otor overload.  
Note: The trim ring assembly cannot  
accomodate unlevel ceilings.  
Note: On sizes 8, 10, & 12 center installa-  
tion position and use 2 or 3.5-inch bolts,  
whichever is best suited for installation.  
Also, install two safety chains assemblies  
on these sizes.  
Note: Expansion collar is furnished with  
fan-coil with bottom return only. The  
collar is not necessary for Force Flo units.  
Figure I-IP-1. Installing the trim ring assembly on horizontal recessed units.  
42  
UNT-SVX07A-EN  
installation  
procedure  
Installation  
Wall-Mounted Control Options  
Figure I-IP-4. Zone sensor with  
setpoint knob, on/cancel, & comm  
jack.  
Figure I-IP-2. Zone sensor with off/  
auto/high/low fan speeds, setpoint  
knob, on/cancel, and comm jack.  
Figure I-IP-3. Zone sensor with on/cancel  
and comm jack.  
Figure I-IP-5. Zone sensor only,  
Figure I-IP-6. Digital zone sensor option  
UNT-SVX07A-EN  
43  
installation  
procedure  
Installation  
Installing Wall Mounted  
Controls  
3. To install the zone sensor module  
without a junction box (directly to the  
wall):  
a. Using the module base as a  
template, mark the the rectangular  
cutout for the control wiring and module  
installation holes. Ensure the base is  
level.  
• Concealed pipes, air ducts, or chimneys  
in partition spaces behind the controller.  
Fan Mode Switch Installation  
The fan mode switch ships loose inside  
the unit accessory bag. Follow the steps  
below to install the fan mode switch.  
Items needed:  
Reference the wall-mounted zone sensor  
dimensions in Figure I-IP-6. Position the  
controller on an inside wall three to five  
feet above the floor and at least 18  
inches from the nearest outside wall.  
Installing the controller at a lower height  
may give the advantage of monitoring  
the temperature closer to the zone, but it  
also exposes the controller to airflow  
obstructions. Ensure that air flows freely  
over the controller.  
2 x 4 electrical junction box  
b. Set the base aside and make the  
1. Remove the brown wire if not using a  
field-supplied damper. Remove the  
terminals, cut and strip wires as  
required for installation.  
2. Level and position a 2 x 4 electrical  
junction box. Follow the instructions  
given in the “Interconnection Wiring”  
section and route the wires as shown in  
the wiring diagram. Refer to the typical  
wiring diagram or to the unit specific  
diagram on the unit.  
3
cutout. Then, drill two /16” diameter  
holes approximately one-inch deep.  
Insert and fully seat the plastic anchors.  
c. Pull the control wires through the  
cutout and attach the module to the wall  
using the screws provided.  
4. To install the zone sensor module to a  
standard junction box:  
a. Level and install a 2“ x 4” junction  
box (installer supplied) vertically on the  
wall.  
b. Pull the control wires through the  
cutout. Attach the module to the wall  
using the screws provided.  
Before beginning installation, follow the  
wiring instructions below. Also, refer to  
the unit wiring schematic for specific  
wiring details and point connections.  
Wiring Instructions  
3. Position the fan mode switch over the  
junction box with the two screws  
supplied.  
Avoid mounting the controller in an area  
subject to the following conditions:  
• Dead spots, such as behind doors or in  
corners that do not allow free air  
circulation.  
• Air drafts from stairwells, outside doors,  
or unsectioned hollow walls.  
• Radiant heat from the sun, fireplaces,  
appliances, etc.  
• Airflow from adjacent zones or other  
units.  
• Unheated or uncooled spaces behind  
the controller, such as outside walls or  
unoccupied spaces.  
Zone Sensor Installation  
Follow the procedure below to install the  
zone sensor module.  
5. Strip the insulation on the  
interconnection wires back 0.25 inch  
and connect to TB1. Screw down the  
terminal blocks.  
6. Replace the zone sensor cover and  
adjustment knob.  
1. Note the position of the setpoint  
adjustment knob and gently pry the  
adjustment knob from the cover using  
the blade of a small screwdriver.  
2. Insert the screwdriver blade behind the  
cover at the top of the module and  
carefully pry the cover away from the  
base.  
If installing a Tracer ZN510 or Tracer  
ZN520 zone sensor, see the Tracer  
Summit Communication section for more  
information.  
Figure I-IP-6. Wall mounted zone sensor dimensions.  
44  
UNT-SVX07A-EN  
installation  
procedure  
Installation  
Installation Checklist  
Protection Association (N.F.P.A.)  
Standard 90A or 90B concerning the  
use of concealed ceiling spaces as  
return air plenums. Verify correct ceiling  
opening dimensions on unit submittals.  
Secure the unit and any accessory items  
properly to the wall or ceiling support  
rods.  
The following checklist is only an  
abbreviated guide to the detailed  
installation procedures given in this  
manual. Use this list to ensure all  
necessary procedures are complete. For  
more detailed information, refer to the  
appropriate sections in this manual.  
!6. Complete all piping connections  
correctly.  
WARNING  
!7. Check field sweat connections for  
leaks and tighten the valve stem  
packing, and piping pkg unions if  
necessary.  
!8. Install the auxiliary drain pan  
properly under piping package on fan-  
coil units.  
!9. Complete condensate drain line  
connections on fan-coil units.  
!10. Pitch condensate drain line away  
from fan-coil one-inch drop per ten feet  
of pipe.  
!11. Install automatic changeover  
sensor option on the supply water line, if  
applicable.  
Ha za rd o u s Vo lt a g e w /Ca p a c it o rs !  
Disconnect all electric power,  
including rem ote disconnects and  
discharge all m otor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. Verify with  
an appropriate voltm eter that all  
capacitors have discharged. Failure to  
disconnect power and discharge  
capacitors before servicing could  
result in death or serious injury.  
!12. Install automatic electric heat  
lockout switch option on the supply  
water line, if applicable.  
!13. Install condensate overflow switch  
option correctly on the auxiliary drain  
pan, if applicable.  
!14. Ensure the low temperature  
detection device option is correctly  
installed.  
!1. Inspect the unit for shipping damage.  
!2. Level installation location to support  
the unit weight adequately. Make all  
necessary wall or ceiling openings to  
allow adequate air flow and service  
clearances.  
!3. Ensure the unit chassis is installed  
level.  
!15. Complete all necessary duct  
connections.  
!16. Complete all interconnection wiring  
for the wall mounted fan mode switch  
or zone sensor per the wiring schematic  
and guidelines established in the “Wall  
Mounted Control Interconnection  
Wiring” section.  
!17. Install the wall mounted fan mode  
switch, or zone sensor module options  
properly.  
CAUTION  
Un it Le ve lin g !  
The unit m ust be installed level (zero  
tolerance) in both horizontal axis for  
proper operation. Do not use the coil  
or drain pan as the reference point  
because the coil m ay be pitched and  
the drain pan has an inherent positive  
slope to provide proper drainage.  
!18. Connect electrical supply power  
according to the NEC and unit wiring  
diagrams.  
!19. Remove any miscellaneous debris,  
such as sheetrock dust, that may have  
infiltrated the unit during construction.  
!20. Replace the air filter as required.  
!4. Verify that wall and ceiling openins  
are properly cut per the unit submittals.  
!5. Verify that installation of horizontal  
concealed units meets the national Fire  
UNT-SVX07A-EN  
45  
pre-startup  
Installation  
requirem ents  
Communication Wiring  
Device Addressing  
LonTalk devices are given a unique  
address by the manufacturer. This  
address is called a Neuron ID. Each Tracer  
ZN510 and ZN520 controller can be  
identified by its unique Neuron ID, which  
is printed on a label on the controllers  
logic board. The Neuron ID is also  
displayed when communication is  
established using Tracer Summit or  
Rover service tool. The Neuron ID format  
is 00-01-64-1C-2B-00.  
Units with Tracer ZN510 and ZN520 Only  
Communications  
Tracer ZN510 and ZN520 controllers are  
LonTalk® devices that interface with the  
Trane Tracer Summit building  
management system. Reference the unit  
wiring diagram or submittals.  
Ground shields at each Tracer ZN510 and  
ZN520, taping the opposite end of each  
shield to prevent any connection be-  
tween the shield and anther ground.  
Refer to Trane publication, CNT-SVX04A-  
EN Installation, Operation and Program-  
ming Guide, for the communication  
wiring diagram.  
Wire Characteristics  
Controller communication-link wiring  
must be low capacitance, 18-gage,  
shielded, twisted pair with stranded,  
tinned-copper conductors. For daisy chain  
configurations, limit the wire run length to  
5,000 ft. Truck and branch configurations  
are significantly shorter. LonTalk wire  
length limitations can be extended  
through the use of a link repeater.  
Communication wire must conform to  
the following specification:  
1. Shielded twisted pair 18 AWG  
2. Capacitance 23 (21-25) picofarads (pF)  
per foot  
3. Listing/Rating – 300V 150C NEC 725-2  
(b) Class 2 Type CL2P  
4. Trane Part No. 400-20-28 or equivalent,  
available through Trane BAS Buying  
Group Accessories catalog.  
Recommended  
Communication Wiring  
Practices  
The following guidelines should be  
followed while installing communication  
wire.  
Note: Communication link wiring is a  
shielded, twisted pair of wire and must  
comply with applicable electrical codes.  
LonTalk is not polarity sensitive. Trane  
recommends that the installer keep  
polarity consistent throughout the site.  
• Only strip away two-inches maximum of  
the outer conductor of shielded cable.  
• Make sure that the 24VAC power  
supplies are consistent in how they are  
grounded. Avoid sharing 24VAC  
between LonTalk UCMs.  
• Avoid over-tightening cable ties and  
other forms of cable wraps. A tight tie  
or wrap could damage the wires inside  
the cable.  
• Do not run LonTalk cable alongside or in  
the same conduit as 24VAC power.  
In an open plenum, avoid lighting  
ballasts, especially those using 277VAC.  
• Do not use a trunk and branch  
configuration, if possible. Trunk and  
branch configurations shorten the  
distance cable can be run.  
Follow these general guidelines when  
installing communication wiring on units  
with a Tracer ZN510 or ZN520 controller:  
• Maintain a maximum 5000 ft.  
aggregate run.  
Install all communication wiring in  
accordance with the NEC and all local  
codes.  
• Solder the conductors and insulate  
(tape) the joint sufficiently when splicing  
communication wire. Do not use wire  
nuts to make the splice.  
• Do not pass communication wiring  
between buildings because the unit will  
assume different ground potentials.  
• Do not run power in the same conduit or  
wire bundle with communication link  
wiring.  
Note: You do not need to observe polarity  
for LonTalk communication links.  
46  
UNT-SVX07A-EN  
pre-startup  
Installation  
requirem ents  
Pre-Startup Checklist  
Unit Location  
1. Ensure the unit location is adequate for  
unit dimensions, ductwork, piping, and  
electrical connections.  
2. Ensure access and maintenance  
clearances around the unit are  
adequate.  
Complete this checklist after installing  
the unit to verify all recommended  
installation procedures are complete  
before unit startup. This does not replace  
the detailed instructions in the  
appropriate sections of this manual.  
Disconnect electrical power before  
performing this checklist. Always read  
the entire section carefully to become  
familiar with the procedures.  
Unit Mounting  
1. Ensure unit is installed level.  
Component Overview  
1. Ensure the fan rotates freely in the  
correct direction.  
WARNING Ha za rd o u s  
2. Ensure all unit access panels and air  
grilles are in place.  
Vo lt a g e w /Ca p a c it o rs !  
3. Verify that a clean air filter is in place.  
4. Properly set the damper position to  
meet the fresh air requirement.  
Disconnect all electric power,  
including rem ote disconnects and  
discharge all m otor start/run  
Unit Piping  
1. Properly vent the hydronic coil to allow  
water flow through the unit.  
2. Units with deluxe piping package:  
Tighten unions adequately.  
3. Set water flow to the unit properly if  
unit piping has the circuit setter valve.  
4. Check strainers (if supplied) for debris  
after apply system water.  
5. Install the auxiliary drain pan and route  
the main drain pan hoses to the  
auxiliary drain pan on vertical fan-coil  
units.  
6. Verify the condensate drain piping is  
complete for the unit drain pan.  
7. Ensure the drain pan and condensate  
line are not obstructed. Remove any  
foreign matter that may have fallen into  
the drain pan during installation.  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing com ponents provided by  
Trane or others, refer to the  
appropriate m anufacturers literature  
for allowable waiting periods for  
discharge of capacitors. Verify with  
an appropriate voltm eter that all  
capacitors have discharged. Failure  
to disconnect power and discharge  
capacitors before servicing could  
result in death or serious injury.  
Receiving  
Electrical  
!Inspect unit and components for  
shipping damage. File damage claims  
immediately with the delivering  
carrier.  
!Check unit for missing material. Look  
for ship-with options and sensors that  
may be packaged separately from the  
main unit. See the “Receiving and  
Handling” section.  
#Check all electrical connections for  
tightness.  
Note: Some circumstances may require  
the unit to run before building construc-  
tion is complete. These operating  
conditions may be beyond the design  
parameters of the unit and may ad-  
versely affect the unit.  
!Check nameplate unit data so that it  
matches the sales order requirements.  
UNT-SVX07A-EN  
47  
Installation  
startup  
Tracer™ ZN510 & ZN520 Unit  
Startup  
sensor module to 55°F for cooling or  
85°F for heating.  
Refer to the Trane publication, CNT-IOP-1  
Installation, Operation and Programming  
Guide for Tracer ZN510 and CNT-  
SVX04A-EN for Tracer ZN520. The  
factory pre-programs the Tracer ZN510  
and ZN520 with default values to control  
the temperature and unit airflow. Use  
Tracer Summit building automation  
system or Rover™ software to change  
the default values.  
The appropriate control valve will actuate  
assuming the following conditions:  
1. Room temperature should be greater  
than 55°F and less than 85°F.  
2. For a 2-pipe fan-coil unit with an  
automatic changeover sensor, the  
water temperature input is appropriate  
for the demand placed on the unit. For  
example, cooling operation is  
requested and cold water (5° lower  
than room temperature) flows into the  
unit.  
Follow the procedure below to operate  
the Tracer ZN510 or ZN520 in a stand-  
alone operation:  
1. Turn power on at the disconnect switch  
option.  
2. Position the fan mode switch to either  
high, medium, low, or the auto position.  
3. Rotate the setpoint dial on the zone  
3. Select the correct temperature  
setpoint.  
Note: Select and enable zone sensor  
temperature settings to prevent freeze  
damage to unit.  
48  
UNT-SVX07A-EN  
general  
inform ation  
Operation  
General Information  
The unit-mounted option operates on line  
voltage. The wall mounted option is low-  
voltage and has three 24-volt relays using  
a factory-wired transformer and relays to  
control the fan motor.  
Relay Board  
The relay board is a new component on  
all models (except those with a unit-  
mounted, line-voltage fan speed switch)  
that replaces all the loose wires in the  
control box. It consolidates many control  
components onto one board, therefore  
making it easy to troubleshoot in the field.  
There is an LED on the board that  
indicates when power is supplied to the  
board. All connections are made to match  
up only with the applicable component to,  
thus prevent miswiring. Factory switches  
are pre-set and locked in place with lock-  
tight. The switch settings can be broken if  
field-modifications are needed. However,  
switches must be properly set for the unit  
to operate safely and properly. See  
Figure O-GI-1.  
Tracer ZN010 & ZN510  
Tracer ZN010 is a stand-alone device that  
controls fan-coils and cabinet heaters.  
Tracer ZN510 can be stand-alone or use  
peer-to-peer communications.  
The controller is easily accessible in the  
control end panel for service. The control  
end panel is on the end of the unit  
opposite the piping. Reference Figure O-  
GI-3.  
Figure O-GI-2. Fan speed switch  
Manual Fan Mode Switch  
The manual fan mode switch is available  
with a four-position switch (off-hi-med-lo)  
allows manual fan mode selection and is  
available unit or wall mounted. See  
Figure O-GI-2.  
Figure O-GI-1. Relay board  
Figure O-GI-3. Tracer ZN010 board  
UNT-SVX07A-EN  
49  
sequence of  
operation  
Operation  
Fan Mode Switch Operation  
Tracer ZN520 Operation  
Off  
Off  
Fan is turned off, two-position damper  
Fan is off; control valve options and fresh  
air damper options close. The low air  
temperature detection option is still  
active.  
option spring-returns closed.  
Hi, Med, Lo  
Fan runs continuously at the selected  
speed. The two-position damper option  
opens to an adjustable mechanical stop  
position.  
Auto  
Fan speed control in the auto setting  
allows the modulating (3-wire floating  
point) or 2–position control valve option  
and three-speed fan to work  
Tracer ZN010 & ZN510  
Operation  
cooperatively to meet precise capacity  
requirement, while minimizing fan speed  
(motor/energy/acoustics ) and valve  
position (pump energy, chilled water  
reset ). As the capacity requirement  
increases at low fan speed, the water  
valve opens. When the low fan speed  
capacity switch point is reached, the fan  
switches to medium speed and the water  
valve repositions to maintain an  
equivalent capacity. The reverse  
sequence takes place with a decrease in  
required capacity.  
Off  
Fan is off; control valves and fresh air  
damper option close. Low air  
temperature detection option is still  
active.  
Auto (Fan Cycling)  
Fan and fresh air damper cycle with  
control valve option to maintain setpoint  
temperature. In cooling mode, the fan  
cycles from off to medium and in heating  
mode it cycles from off to low. When no  
heating or cooling is required, the fan is  
off and the fresh air damper option  
closes.  
Low/Med/High  
The fan runs continuously at the selected  
speed and the valve option will cycle to  
meet setpoint.  
Low/Med/High (Continuous Fan)  
Fan operates continuously while control  
valve option cycles to maintain setpoint  
temperature. Fresh air damper option is  
open.  
50  
UNT-SVX07A-EN  
sequence of  
operation  
Operation  
Sequence of Operation  
Tracer ZN010 and ZN510  
Table O-SO-1. Unit mode as related to water temperature  
unit type  
EWT sensor required?  
coil water temperature  
2-pipe changeover  
4-pipe changeover  
yes  
yes  
COOLS if: space temp - EWT 5°F  
Note: this section applies only to units  
with a Tracer ZN010 or ZN510 controller.  
HEATS if: EWT - space temp 5°F  
COOLS if: space temp - EWT 5°F  
HEATS if: EWT - space temp5°F  
Power-Up Sequence  
2-pipe heating only  
2-pipe cooling only  
no  
no  
hot water assumed  
cold water assumed  
When 24 VAC power is initially applied to  
the Tracer ZN010 or ZN510, the following  
sequence occurs:  
4-pipe heat/cool  
no  
cold water assumed in main coil  
hot water assumed in aux. coil  
1. All outputs are controlled off.  
2. Tracer ZN010 and ZN510 reads all  
input values to detemine initial values.  
3. The random start time (0-25 seconds)  
expires.  
Binary Inputs  
BIP3: Occupancy Sensor  
Binary input #3 (BIP3) on Tracer ZN010  
and ZN510 is available for field- wiring an  
occupancy sensor, such as a binary  
switch or a timeclock, to detect  
occupancy. The sensor can be either  
normally open or normally closed.  
Reference Table O-SO-2.  
BIP1: Low Temperature Detection  
Option  
The factory hard wires the low  
temperature detection sensor to binary  
input #1 (BIP1) on the Tracer ZN010 and  
ZN510. The sensor defaults normally  
closed (N.C.), and will trip off the unit on a  
low temperature diagnostic when  
detecting low temperature. In addition,  
the Tracer ZN010 and ZN510 control unit  
devices as listed below:  
4. Normal operation begins.  
Entering Water Temperature Sampling  
Function  
Both Tracer ZN010 and ZN510 use an  
entering water temperature sampling  
function to test for the correct water  
temperature for the unit operating mode.  
For all applications not involving  
changeover, the water temperature does  
not affect unit operation.  
Binary Outputs  
Reference Table O-SO-3 for the Tracer  
ZN010 and ZN510s six binary outputs.  
fan: off  
valves: open  
electric heat: off  
damper: closed  
The entering water temperature sam-  
pling function opens the main hydronic  
valve, waits no more than three minutes  
to allow the water temperature to  
stabilize, then measures the entering  
water temperature to see if the correct  
water temperature is available.  
Table O-SO-3. Binary outputs  
binary output  
BOP1  
description  
pin  
fan high speed  
J1-1  
J1-2  
J1-4  
J1-5  
J1-6  
J1-7  
Note: See the “Diagnostics” section for  
more information.  
BOP2  
fan medium speed  
fan low speed  
BOP3  
BOP4  
main valve  
BIP2: Condensate Overflow Detection  
Option  
BOP5  
auxiliary valve/electric heat  
2-position fresh air damper  
The entering water must be five degrees  
or more above the space temperature to  
allow hydronic heating and five degrees  
or more below the space temperature to  
allow hydronic cooling.  
BOP6  
The factory hard wires the condensate  
overflow sensor to binary input #2 (BIP2)  
on the Tracer ZN010 and ZN510. The  
sensor defaults normally closed (N.C.),  
and will trip off the unit on a condensate  
overflow diagnostic if condensate  
reaches the trip point. In addition, the  
Tracer ZN010 and ZN510 control unit  
devices as listed below:  
Notes:  
1. In a four-pipe application, BOP4 is used for cooling and  
BOP5 is used for heating.  
2. If no valves are ordered with the unit, the factory default  
for the Tracer ZN010 and ZN510 controller are:  
BOP4 configured as norm ally closed  
BOP5 configured as norm ally open  
3. If the fresh air dam per option is not ordered on the unit,  
BOP6 will be configured as none.  
If the correct water temperature is  
available, the unit begins normal heating  
or cooling operation. If the measured  
entering water temperature is too low or  
high, the controller closes the valve and  
waits 60 minutes before attempting to  
sample the entering water. Reference  
Table O-SO-1.  
fan: off  
valves: closed  
electric heat: off  
Table O-SO-2. Occupancy sensor state table  
sensor type  
sensor position  
open  
unit occupancy mode  
occupied  
normally open  
normally open  
closed  
unoccupied  
normally closed open  
normally closed closed  
unoccupied  
occupied  
UNT-SVX07A-EN  
51  
sequence of  
operation  
Operation  
Analog Inputs  
Table O-SO-4. Analog inputs  
Both Tracer ZN010 and ZN510 accept a  
maximum of five analog inputs.  
Reference Table O-SO-4.  
analog input  
description  
application  
zone  
space temperature  
local setpoint  
space temperature detection  
thumbwheel setpoint  
set  
Zone Sensors  
fan  
fan mode input  
zone sensor fan switch  
The zone sensors available with the  
Tracer ZN010 and ZN510 provide up to  
three different inputs  
1. Space temperature measurement  
(10Kthermistor)  
2. Local setpoint  
analog input 1 (AI1)  
analog input 2 (AI2)  
entering water temperature  
discharge air temperature  
entering water temperature detection  
discharge air temperature detection  
Notes:  
1.The zone sensor, entering water tem perature sensor, and the discharge air tem perature sensor are 10Ktherm istors.  
Figure 26 provides the resistance-tem perature curve for these therm istors.  
2. Zone sensor:  
Wall m ounted sensors include a therm istor soldered to the sensors circuit board  
Unit m ounted sensors include a return air sensor in the units return air stream .  
3. Changeover units include an entering water tem perature sensor.  
3. Fan mode switch  
Wall mounted zone sensors include a  
thermistor as a component of the  
internal printed circuit board. Unit  
mounted zone sensors use a sensor  
placed in the units return air stream.  
Table O-SO-5. Fan mode operation  
heating mode  
fan mode  
off  
cooling mode  
unoccupied  
off  
occupied  
off  
occupied  
off  
unoccupied  
off  
low  
low  
off/high (3)  
off/high (3)  
off/high (3)  
low  
off/high (3)  
off/high (3)  
off/high (3)  
Each zone sensor is equipped with a  
thumbwheel for setpoint adjustment.  
medium  
high  
medium  
high  
medium  
high  
Fan Mode Switch  
auto  
The zone sensor may be equipped with a  
fan mode switch. The fan mode switch  
offers selections of off, low, medium,  
high, or auto.  
continuous  
heat default off/high (3)  
cool default  
off/high (3)  
off/high (3)  
cycling off/heat default  
off/high (3)  
off/cool default  
Notes:  
1. During the transition from off to any fan speed but high, Tracer ZN010 and ZN510 autom atically starts the fan on high  
speed and runs for three seconds before transitioning to the selected speed (if it is other than high). This provides  
enough torque to start all fan m otors from the off position.  
Supply Fan Operation  
Reference Table O-SO-5 for fan mode  
operation. Reference Table O-SO-5 for  
fan mode operation. Tracer ZN010 and  
ZN510 will operate in either continuous  
fan or fan cycling mode. The fan cycles  
when the fan mode switch is placed in  
auto. The fan runs continuous when  
placed in the high, medium, or low  
position. Use Rover, Tranes installation  
and service tool, to change auto defaults.  
2. When the heating output is controlled off, Tracer ZN010 and ZN510 autom atically controls the fan on for an additional 30  
seconds. This delay allows the fan to dissipate any residual heat from the heating source, such as electric heat.  
3. Whenever two states are listed for the fan:  
The first state (off) applies when there is not a call for heating or cooling.  
The second state (varies) applies when there is a call for heating or cooling.  
The heat default is factory configured for low fan speed, and the cool default is m edium .  
Table O-SO-6. Valid operating range and factory default setpoints  
setpoint/parameter  
default setting  
85° F  
valid operating range  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
40 to 115° F  
0 to 240 sec  
unoccupied cooling setpoint  
occupied cooling setpoint  
occupied heating setpoint  
unoccupied heating setpoint  
cooling setpoint high limit  
cooling setpoint low limit  
heating setpoint high limit  
heating setpoint low limit  
power-up control wait  
74° F  
71° F  
60° F  
110° F  
40° F  
105° F  
40° F  
0 sec  
52  
UNT-SVX07A-EN  
sequence of  
operation  
Operation  
heating or cooling capacity is defined by  
unit type and whether heating or cooling  
is enabled or disabled. For example, if  
the economizer is enabled and possible, it  
will be the primary cooling capacity. If  
hydronic heating is possible, it will be the  
primary heating capacity.  
Tracer ZN520 Sequence of  
Operation  
The Tracer ZN520 operates the fan in the  
following modes:  
1) occupied  
2) unoccupied  
3) occupied standby  
4) occupied bypass  
5) Tracer Summit with supply fan control  
When the controller is in unoccupied  
mode, you can press the On button on the  
zone sensor to place the controller into  
occupied bypass mode for the duration of  
the bypass time (typically 120 minutes).  
Occupancy Sources  
There are four ways to control the  
controllers occupancy:  
• Communicated request (usually  
provided by the building automation  
system or peer device)  
• By pressing the zone sensors timed  
override On button  
Occupied Standby Mode  
The controller can be placed into the  
occupied standby mode when a  
Occupied  
communicated occupancy request is  
combined with the local (hardwired)  
occupancy binary input signal. When the  
communicated occupancy request is  
unoccupied, the occupancy binary input  
(if present) does not affect the controllers  
occupancy. When the communicated  
occupancy request is occupied, the  
controller uses the local occupancy  
binary input to switch between the  
occupied and occupied standby modes.  
When the controller is in the occupied  
mode, the unit attempts to maintain the  
space temperature at the active occupied  
heating or cooling setpoint, based on the  
measured space temperature, the  
discharge air temperature, the active  
setpoint, and the proportional/integral  
control algorithm. The modulating control  
algorithm used when occupied or in  
occupied standby is described in the  
following sections. Additional information  
related to the handling of the controller  
setpoints can be found in the previous  
Setpoint operation section.  
• Occupancy binary input  
• Default operation of the controller  
(occupied mode)  
A communicated request from a building  
automation system or another peer  
controller can change the controllers  
occupancy. However, if communication is  
lost, the controller reverts to the default  
operating mode (occupied) after 15  
minutes (configurable, specified by the  
“receive heartbeat time”), if no local  
hardwired occupancy signal exists.  
During occupied standby mode, the  
controllers economizer damper position  
goes to the economizer standby mini-  
mum position. The economizer standby  
minimum position can be changed using  
Rover service tool.  
Unoccupied Mode  
When the controller is in the unoccupied  
mode, the controller attempts to maintain  
the space temperature at the stored  
unoccupied heating or cooling setpoint,  
based on the measured space  
temperature, the active setpoint and the  
control algorithm, regardless of the  
presence of a hardwired or  
communicated setpoint. Similar to other  
configuration properties of the controller,  
the locally stored unoccupied setpoints  
can be modified using Rover™ service  
tool.  
A communicated request can be pro-  
vided to control the occupancy of the  
controller. Typically, the occupancy of the  
controller is determined by using time-of-  
day scheduling of the building automation  
system. The result of the time-of-day  
schedule can then be communicated to  
the unit controller.  
In the occupied standby mode, the  
controller uses the occupied standby  
cooling and heating setpoints. Because  
the occupied standby setpoints typically  
cover a wider range than the occupied  
setpoints, the TracerZN520 controller  
reduces the demand for heating and  
cooling the space. Also, the outdoor air  
economizer damper uses the econo-  
mizer standby minimum position to  
reduce the heating and cooling demands.  
Tracer Summit with Supply Fan Control  
If the unit is communicating with Tracer  
Summit and the supply fan control  
programming point is configured for  
Tracer (the factory configures as local),  
Tracer Summit will control the fan  
regardless of the fan mode switch  
position.  
When no occupancy request is commu-  
nicated, the occupancy binary input  
switches the controllers operating mode  
between occupied and unoccupied.  
When no communicated occupancy  
request exists, the unit cannot switch to  
occupied standby mode.  
In unoccupied mode, a simplified zone  
control algorithm is run. During the  
cooling mode, when the space tempera-  
ture is above the cool setpoint, the  
primary cooling capacity operates at  
100%. If more capacity is needed, the  
supplementary cooling capacity turns on  
(or opens to 100%). During the heating  
mode, when the space temperature is  
below the heat setpoint, the primary  
heating capacity turns on. All capacity is  
turned off when the space temperature is  
between the unoccupied cooling and  
heating setpoints. Note that primary  
When the fan mode switch is set to Off or  
when power is restored to the unit, all  
Tracer ZN520 lockouts (latching diagnos-  
tics) are manually reset. The last diagnos-  
tic to occur is retained until the unit power  
is disconnected. Refer to Trane publica-  
tion, CNT-SVX04A-EN Tracer ZN520  
Installation Operation and Programming  
Guide, for specific instructions regarding  
the procedure for running the Tracer  
ZN520.  
Occupied Bypass Mode  
The controller can be placed in occupied  
bypass mode by either communicating  
an occupancy request of Bypass to the  
controller or by using the timed override  
On button on the Trane zone sensor.  
UNT-SVX07A-EN  
53  
sequence of  
operation  
Operation  
Cooling Operation  
The heating and cooling setpoint high  
and low limits are always applied to the  
occupied and occupied standby  
setpoints. During the cooling mode, the  
Tracer ZN520 controller attempts to  
maintain the space temperature at the  
active cooling setpoint. Based on the  
controllers occupancy mode, the active  
cooling setpoint is one of the following:  
• Occupied cooling setpoint  
Unit diagnostics can affect the Tracer  
ZN520 controller operation, causing unit  
operation to be defined as abnormal.  
Refer to the Troubleshooting section for  
more information about abnormal unit  
operation.  
The economizer is used for cooling  
purposes whenever the outdoor tem-  
perature is below the economizer enable  
setpoint and there is a need for cooling.  
The economizer is used first to meet the  
space demand, and other forms of  
cooling are used if the economizer cannot  
meet the demand alone. See modulating  
outdoor air damper operation for  
additional information.  
The heating output is controlled based on  
the heating capacity. At 0% capacity, the  
heating output is off continuously.  
Between 0 and 100% capacity, the  
heating output is controlled according to  
modulating valve logic (modulating  
valves) or cycled on (two-position  
valves). As the load increases, modulat-  
ing outputs open further and binary  
outputs are energized longer. At 100%  
capacity, the heating valve is fully open  
(modulating valves) or on continuously  
(two-position valves).  
Cascade cooling control initiates a  
• Occupied standby cooling setpoint  
• Unoccupied cooling setpoint  
discharge air tempering function if the  
discharge air temperature falls below the  
discharge air temperature control low  
limit, all cooling capacity is at minimum,  
and the discharge control loop deter-  
mines a need to raise the discharge air  
temperature. The controller then pro-  
vides heating capacity to raise the  
The controller uses the measured space  
temperature, the active cooling setpoint,  
and discharge air temperature along  
with the control algorithm to determine  
the requested cooling capacity of the unit  
(0-100%). The outputs are controlled  
based on the unit configuration and the  
required cooling capacity. To maintain  
space temperature control, the Tracer  
ZN520 cooling outputs (modulating  
hydronic valve, two-position hydronic  
valve, or outdoor air economizer  
discharge air temperature to its low limit.  
The TracerZN520 fan output(s) normally  
run continuously during the occupied and  
occupied standby modes, but cycle  
between high and off speeds with  
heating/cooling during the unoccupied  
mode. When in the occupied mode or  
occupied standby mode and the fan  
speed is set at the high, medium, or low  
position, the fan runs continuously at the  
selected speed. Refer to the Trouble-  
shooting section for more information on  
abnormal fan operation.  
Discharge Air Tempering  
The discharge air tempering function  
enables when cold outdoor air is brought  
in through the outdoor air damper,  
causing the discharge air to fall below the  
discharge air temperature control low  
limit. The controller exits the discharge air  
tempering function when heat capacity  
has been at 0% for five minutes.  
damper) are controlled based on the  
cooling capacity output.  
The cooling output is controlled based on  
the cooling capacity. At 0% capacity, all  
cooling capacities are off and the  
damper is at minimum position. Between  
0 and 100% capacity, the cooling outputs  
are controlled according to modulating  
valve logic (modulating valves) or cycled  
on (2-position valves). As the load  
increases, modulating outputs open  
further and binary outputs are energized  
longer. At 100% capacity, the cooling  
valve or damper is fully open (modulat-  
ing valves) or on continuously (and 2-  
position valves).  
Heating Operation  
When the units supply fan is set to auto,  
the controllers configuration determines  
the fan speed when in the occupied mode  
or occupied standby mode. The fan runs  
continuously at the configured heating  
fan speed or cooling fan speed. For all fan  
speed selections except off, the fan  
During heating mode, the TracerZN520  
controller attempts to maintain the space  
temperature at the active heating  
setpoint. Based on the occupancy mode  
of the controller, the active heating  
setpoint is one of the following:  
• Occupied heating  
cycles off during unoccupied mode.  
• Occupied standby heating  
• Unoccupied heating  
The economizer outdoor air damper is  
never used as a source of heating.  
Instead, the economizer damper (when  
present) is only used for ventilation;  
therefore, the damper is at the occupied  
minimum position in the occupied mode.  
The damper control is primarily associ-  
ated with occupied fan operation.  
During dehumidification in the heating  
mode, the controller adjusts the heating  
setpoint up to the cooling setpoint. This  
reduces the relative humidity in the space  
with a minimum of energy usage.  
Unit diagnostics can affect fan operation,  
causing occupied and occupied standby  
fan operation to be defined as abnormal.  
Refer to the Troubleshooting section for  
more information about abnormal fan  
operation.  
The controller uses the measured space  
temperature, the active heating setpoint,  
and discharge air temperature, along  
with the control algorithm, to determine  
the requested heating capacity of the unit  
(0-100%). The outputs are controlled  
based on the unit configuration and the  
required heating capacity.  
The Tracer ZN520 controller operates the  
supply fan continuously when the  
controller is in the occupied and occupied  
standby modes, for either heating or  
cooling. The controller only cycles the fan  
off with heating and cooling capacity in  
the unoccupied mode.  
54  
UNT-SVX07A-EN  
sequence of  
operation  
Operation  
Fan Mode Operation  
Table O-SO-8. Local fan switch enabled  
Continuous Fan Operation  
During occupied and occupied standby  
modes, the fan normally is on. For  
multiple speed fan applications, the fan  
normally operates at the selected or  
default speed (off, high, medium, or low).  
When fan mode is auto, the fan operates  
at the default fan speed.  
For multiple fan speed applications, the  
TracerZN520 controller offers additional  
fan configuration flexibility. Separate  
default fan speeds for heating and cooling  
modes can be configured. The fan runs  
continuously for requested speeds (off,  
high, medium, or low). When the fan  
mode switch is in the Auto position or a  
hardwired fan mode input does not exist,  
the fan operates at the default configured  
speed. See Table 21 for default fan  
configuration for heat and cool mode.  
During unoccupied mode, the fan cycles  
between high speed and off with heating  
and cooling fan modes. If the requested  
speed is off, the fan always remains off.  
Communicated Fan switch (local) Fan operation  
fan speed input  
Off  
Low  
Ignored  
Ignored  
Off  
Low  
Medium  
High  
Ignored  
Ignored  
Off  
Medium  
High  
Auto  
Low  
During unoccupied mode, the controller  
controls the fan off. While unoccupied, the  
controller heats and cools to maintain the  
unoccupied heating and cooling setpoints.  
In unoccupied mode, the fan is controlled  
on high speed only with heating or  
cooling.  
Medium  
High  
Auto  
Off  
Low  
Medium  
High  
Auto (configured default, determined by heat/cool  
mode)  
The unit fan is always off during occupied,  
occupied standby, and unoccupied modes  
when the unit is off due to a diagnostic or  
when the unit is in the off mode due to the  
local zone sensor module, a communi-  
cated request, or the default fan speed  
(off).  
During dehumidification, when the fan is  
on Auto, the fan speed can switch  
depending on the error. Fan speed  
increases as the space temperature rises  
above the active cooling setpoint.  
Table O-SO-9. Fan operation in heating and  
cooling modes  
Heating  
Fan mode Occ. Unocc.  
Cooling  
Occ.  
Unocc.  
off  
off  
off  
off  
off  
Additional flexibility built into the control-  
ler allows you to enable or disable the  
local fan switch input. The fan mode  
request can be either hardwired or  
communicated to the controller. When  
both are present, the communicated  
request has priority over the hardwired  
input. See Tables 22, 23, and 24.  
If both a zone sensor module and  
communicated request exist, the commu-  
nicated request has priority.  
Low  
low  
med  
high  
off/high  
off/high  
off/high  
low  
med  
high  
off/high  
off/high  
off/high  
Medium  
High  
Auto  
Fan Cycling Operation  
default off/high  
fan sp.  
default off/high  
fan sp.  
TracerZN520 does not support fan  
cycling in occupied mode. The fan cycles  
between high speed and off in the  
unoccupied mode only. The controllers  
cascade control algorithm requires  
continuous fan operation in the occupied  
mode.  
Table O-SO-10. Local fan switch disabled or  
not present  
Table O-SO-7. Fan configuration  
Communicated fan speed input  
Fan operation  
Off  
auto fan  
operation  
fan speed  
default  
Off  
Fan Off Delay  
Heating  
Cooling  
continuous  
off  
low  
medium  
high  
Low  
Low  
When a heating output is controlled off,  
the Tracer ZN520 controller automatically  
holds the fan on for an additional 30  
seconds. This 30-second delay gives the  
fan time to blow off any residual heat  
from the heating source, such as a steam  
coil. When the unit is heating, the fan off  
delay is normally applied to control the  
fan; otherwise, the fan off delay does not  
apply.  
Medium  
Medium  
High  
High  
continuous  
off  
low  
medium  
high  
Auto (or not present)  
Auto (fan runs at  
the default speed  
Table O-SO-11. Relationship between outdoor temperature sensors and damper position  
Outdoor Air Temp.  
Modulating Outdoor Air Damper  
occupied or occupied bypass  
occupied standby  
unoccupied  
none or invalid  
open to occupied minimum position  
open to occupied minimum position  
economizing minimum postion to 100%  
open to occupied standby minimum position  
open to occuied standby minimum position  
closed  
closed  
failed  
present and economizing feasible  
economizing between occupied standby  
minimum position to 100%  
open & economizing when  
unit is operating, closed  
otherwise  
present & economizing not feasible open to occupied minimum position  
open to occupied standby minimum position  
closed  
UNT-SVX07A-EN  
55  
sequence of  
operation  
Operation  
Fan Start on High Speed  
temperature is not usable for the desired  
mode, the controller continues to com-  
pare the entering water temperature  
against the effective space temperature  
for a maximum of three minutes.  
Economizer Damper Option  
On a transition from off to any other fan  
speed, the Tracer ZN520 controller  
automatically starts the fan on high speed  
and runs the fan at high speed for 0.5  
seconds. This provides the ample torque  
required to start all fan motors from the  
off position.  
With a valid outdoor air temperature  
(either hardwired or communicated),  
Tracer ZN520 uses the modulating  
economizer damper as the highest  
priority source of cooling. Economizer  
operation is only possible through the use  
of a modulating damper.  
The controller automatically disables the  
entering water temperature sampling  
and closes the main hydronic valve when  
the measured entering water exceeds  
the high entering water temperature limit  
(110°F). When the entering water  
temperature is warmer than 110°F, the  
controller assumes the entering water  
temperature is hot because it is unlikely  
the coil would drift to a high temperature  
unless the actual loop temperature was  
very high.  
Entering Water Temperature Sampling  
Function  
Only units using the main hydronic coil for  
both heating and cooling (2-pipe  
changeover and 4-pipe changeover  
units) use the entering water  
temperature sampling function. Two-pipe  
changeover and 4-pipe changeover  
applications allow the main coil to be  
used for heating and for cooling;  
therefore, these applications require an  
entering water temperature sensor.  
Economizing is possible during the  
occupied, occupied standby, unoccupied,  
and occupied bypass modes.  
The controller initiates the economizer  
function if the outdoor air temperature is  
cold enough to be used as free cooling  
capacity. If the outdoor air temperature is  
less than the economizer enable setpoint  
(absolute dry bulb), the controller  
If the entering water temperature is  
unusable — too cool to heat or too warm  
to cool — the controller closes the  
hydronic valve and waits 60 minutes  
before initializing another sampling. If the  
controller determines the entering water  
temperature is valid for heating or  
cooling, it resumes normal heating/  
cooling control and effectively disables  
entering water temperature sampling  
until it is required.  
modulates the outdoor air damper  
(between the active minimum damper  
position and 100%) to control the amount  
of outdoor air cooling capacity. When the  
outdoor air temperature rises 5°F above  
the economizer enable point, the control-  
ler disables economizing and moves the  
outdoor air damper back to its predeter-  
mined minimum position based on the  
current occupancy mode or communi-  
cated minimum damper position.  
When three-way valves are ordered with  
a Tracer ZN520 control, the controller is  
factory-configured to disable the entering  
water temperature sampling function,  
and the entering water sensor is  
mounted in the proper location. Disabling  
entering water temperature sampling  
eliminates unnecessary water flow  
through the main coil when three-way  
valves are used.  
Electric Heat Operation  
Dehumidification  
The Tracer ZN520 controller supports one  
or two-stage electric heat operation for  
heating. To control the space  
temperature, electric heat is cycled to  
control the discharge air temperature.  
The rate of cycling is dependent upon the  
load in the space and the temperature of  
the incoming fresh air from the  
Dehumidification is possible when  
mechanical cooling is available, the  
heating capacity is located in the reheat  
position, and the space relative humidity  
setpoint is valid.The controller starts  
dehumidifying the space when the space  
humidity exceeds the humidity setpoint.  
The controller invokes entering water  
temperature sampling only when the  
measured entering water temperature is  
too cool to heat or too warm to cool.  
Entering water is cold enough to cool  
when it is five degrees below the mea-  
sured space temperature. Entering water  
is warm enough to heat when it is five  
degrees above the measured space  
temperature.  
The controller continues to dehumidify  
until the sensed humidity falls below the  
setpoint minus the relative humidity  
offset.The controller uses the cooling and  
reheat capacities simultaneously to  
dehumidify the space. While dehumidify-  
ing, the discharge air temperature is  
controlled to maintain the space tem-  
perature at the current setpoint.  
economizer (if any). Two-pipe  
changeover units with electric heat use  
the electric heat only when hot water is  
not available.  
When the controller invokes the entering  
water temperature sampling function, the  
unit opens the main hydronic valve for no  
more than three minutes before consid-  
ering the measured entering water  
temperature. An initial stabilization period  
is allowed to flush the coil. This period is  
equal to 30 seconds plus ½ the valve  
stroke time. Once this temperature  
stabilization period has expired, the  
controller compares the entering water  
temperature against the effective space  
temperature (either hardwired or  
Manual Fresh Air Damper  
Units with the manual fresh air damper  
option ship with the damper in the closed  
position, which is adjustable from zero to  
100% in 25% increments. To adjust the  
position, first remove the air filter to  
expose the damper stop screw on the  
control panel end. Relocate the stop  
screw to the appropriate position. Then  
loosen the stop screw wingnut and  
adjust the linkage.  
A typical scenario involves high humidity  
and high temperature load of the  
space.The controller sets the cooling  
capacity to 100% and uses the reheat  
capacity to warm the discharge air to  
maintain space temperature control.  
Dehumidification may be disabled via  
Tracer or configuration.  
communicated) to determine whether  
the entering water can be used for the  
desired heating or cooling. If the water  
56  
UNT-SVX07A-EN  
sequence of  
operation  
Operation  
Binary Outputs  
Binary outputs are configured to support  
the following:  
Note: If the unit is in the unoccupied  
mode, the dehumidification routine will  
not operate.  
Note: The generic binary input can be  
used with a Tracer Summit® building  
automation system only.  
• Three fan stages (when one or two fan  
stages are present, medium fan speed  
can be configured as exhaust fan)  
• One hydronic cooling stage  
• One hydronic heating stage  
(dehumidification requires this to be in  
the reheat position)  
Data Sharing  
Because this controller utilizes  
LonWorks™ technology, the controller  
can send or receive data (setpoint, heat/  
cool mode, fan request, space  
Each binary input default configuration  
(including normally open/closed) is set at  
the factory. However, you can configure  
each of the four binary inputs as normally  
open or normally closed. The controller  
will be set properly for each factory-  
supplied binary input end-device. When  
no device is connected to the input,  
configure the controllers input as not  
used.  
temperature, etc.) to and from other  
controllers on the communication link,  
with or without the existence of a building  
automation system. This applies to  
applications where multiple unit  
controllers share a single space  
temperature sensor (for rooms with  
multiple units but only one zone sensor)  
for both standalone (with communication  
wiring between units) and building  
automation system applications. For this  
application you will need to use the Rover  
service tool. For more information on  
setup, refer to the Trane publication  
EMTX-IOP-2.  
• One DX cooling stage  
• One or two-stage electric heat  
(dehumidification requires this to be in  
the reheat position)  
• Face and bypass damper  
• Modulating outdoor air damper  
• One baseboard heat stage  
For more information, see Table O-SO-13.  
Table O-SO-12. Binary input configurations  
binary  
input  
controller operation  
contact closed contact open  
description  
configuration  
BI 1  
BI 2  
low temperature detection Note 1  
normally closed  
normally closed  
normal  
normal  
diagnostic Note 5  
condensate overflow Note 1  
diagnostic Note 5  
Binary Inputs  
BI 3  
BI 3  
BI 4  
occupancy  
normally open  
normally open  
normally open  
unoccupied  
normal Note  
normal  
occupied  
normal Note  
diagnostic Note 4  
The Tracer ZN520 controller has four  
available binary inputs. See Table O-SO-  
12. Normally, these inputs are factory-  
configured for the following functions:  
• Binary input 1: Low temperature  
detection (freezestat)  
• Binary input 2: Condensate overflow  
• Binary input 3: Occupancy/ Generic  
• Binary input 4: Fan status  
3
3
generic binary input  
fan status Note 1  
No t e  
1
During low tem perature, condensate overflow, and fan status diagnostics, the Tracer ZN520 control disables all  
No t e  
norm al unit operation of the fan, valves, and dam per.  
as an occupied/unoccupied input. However, when the controller receives a com m unicated occupied/unoccupied request,  
the com m unicated request has priority over the hardwired input.  
2 The occupancy binary input is for standalone unit controllers  
No t e  
3
The generic binary input does not affect unit  
No t e  
4
operation. A building autom ation system reads this input as a generic binary input.  
If the fan m ode input is in the  
off position or the controller is in the unoccupied m ode with the fan off, the fan status input will be open. A diagnostic  
will not be generated when the controller com m ands the fan off. A diagnostic will only be generated if the fan status  
input does not close after one m inute from energizing a fan output or any tim e the input is open for one m inute. The  
controller waits up to one m inute after energizing a fan output to allow the differential pressure to build up across the  
No t e  
5
fan.  
The table below shows the controllers response to low tem perature detection, condensate overflow, and fan  
status diagnostics.  
Table O-SO-13. Binary output configuration  
binary output  
J1-1  
configuration  
fan high  
J1-2  
fan medium  
J1-3  
fan low  
J1-4  
(Key)  
Note 1  
J1-5  
cool valve – open, or 2-position valve  
Note 1  
J1-6  
cool valve – close  
Note 1  
J1-9  
heat valve – open, or 2 position valve, or 1st electric heat stage  
Note 1  
J1-10  
J1-11  
J1-12  
TB4-1  
TB4-2  
heat valve – close or 2nd Electric heat stage  
fresh air damper - open  
fresh air damper - close  
generic / baseboard heat output  
24VAC  
No t e  
1
For Tracer ZN520 units configured and applied as 2-pipe hydronic heat/cool changeover, term inals J 1-5 and J 1-6 are  
used to control the prim ary valve for both heating and cooling. For Tracer ZN520 units configured and applied as 2-pipe  
hydronic heat/cool changeover with electric heat, term inals J 1-5 and J 1-6 are used to control the prim ary valve (for both  
cooling and heating), and term inals J 1-9 and J 1-10 are used only for the electric heat stage. For those 2-pipe changeover  
units, electric heat will not be energized while the hydronic supply is hot (5° or m ore above the space tem perature).  
UNT-SVX07A-EN  
57  
sequence of  
operation  
Operation  
Table O-SO-14. Analog inputs  
description  
terminals  
function  
range  
zone  
ground  
set  
TB3-1  
TB3-2  
TB3-3  
B3-4  
space temperature input  
analog ground  
5° to 122°F (-15° to 50°C)  
NA  
setpoint input  
40° to 115°F (4.4° to 46.1°C)  
4821 to 4919 W (off)  
2297 to 2342 W (auto)  
10593 to 10807 W (low)  
13177 to 13443 W (medium)  
15137 to 16463 W (high)  
fan  
fan switch input  
ground  
TB3-6  
analog ground  
NA  
analog input 1  
J3-1  
J3-2  
entering water temperature  
analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
analog input 2  
analog input 3  
analog input 4  
J3-3  
J3-4  
discharge air temperature  
Analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
J3-5  
J3-6  
fresh air temp/generic temp  
Analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
J3-7  
universal input  
generic 4-20ma  
humidity  
0 – 100%  
0 – 100%  
0 – 2000ppm  
2
CO  
J3-8  
J3-9  
analog ground  
NA  
NA  
ground  
Notes:  
analog ground  
1. The zone sensor, entering water tem perature sensor, discharge air sensor, and the outside air tem perature sensor are  
10Kthermistors.  
2. Zone sensor: Wall m ounted sensors include a therm istor soldered to the sensors circuit board. Unit m ounted sensors  
include a return air sensor in the units return air stream .  
3. Changeover units include an entering water tem perature sensor.  
Table O-SO-15. Analog inputs  
description  
terminals  
function  
range  
zone  
ground  
set  
TB3-1  
TB3-2  
TB3-3  
B3-4  
space temperature input  
analog ground  
5° to 122°F (-15° to 50°C)  
NA  
setpoint input  
40° to 115°F (4.4° to 46.1°C)  
4821 to 4919 W (off)  
2297 to 2342 W (auto)  
10593 to 10807 W (low)  
13177 to 13443 W (medium)  
15137 to 16463 W (high)  
fan  
fan switch input  
ground  
TB3-6  
analog ground  
NA  
analog input 1  
J3-1  
J3-2  
entering water temperature  
analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
analog input 2  
analog input 3  
analog input 4  
J3-3  
J3-4  
discharge air temperature  
Analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
J3-5  
J3-6  
fresh air temp/generic temp  
Analog ground  
-40° to 212°F (-40° to 100°C)  
NA  
J3-7  
universal input  
generic 4-20ma  
humidity  
CO2  
analog ground  
0 – 100%  
0 – 100%  
0 – 2000ppm  
J3-8  
J3-9  
NA  
NA  
ground  
Notes:  
analog ground  
1. The zone sensor, entering water tem perature sensor, discharge air sensor, and the outside air tem perature sensor are  
10KW therm istors.  
2. Zone sensor: Wall m ounted sensors include a therm istor soldered to the sensors circuit board. Unit m ounted sensors  
include a return air sensor in the units return air stream .  
3. Changeover units include an entering water tem perature sensor.  
58  
UNT-SVX07A-EN  
sequence of  
operation  
Operation  
Zone Sensor  
mode, the heating and cooling mode, and  
other factors, the calculated setpoint is  
validated against the following setpoint  
limits:  
• Heating setpoint high limit  
• Heating setpoint low limit  
• Cooling setpoint high limit  
• Cooling setpoint low limit  
On/Cancel Buttons  
The TracerZN520 controller accepts the  
following zone sensor module inputs:  
• Space temperature measurement  
(10kthermistor)  
Local setpoint (either internal or  
external on the zone sensor module)  
• Fan switch  
Timed override (On) and Cancel timed  
override  
• Communication jack  
Momentarily pressing the on button  
during unoccupied mode places the  
controller in occupied bypass mode for  
120 minutes. You can adjust the number  
of minutes in the unit controller  
configuration using Rover service tool.  
The controller remains in occupied  
bypass mode until the override time  
expires or until you press the Cancel  
button.  
These setpoint limits only apply to the  
occupied and occupied standby heating  
and cooling setpoints. These setpoint  
limits do not apply to the unoccupied  
heating and cooling setpoints stored in  
the controllers configuration.  
Space Temperature Measurement  
Trane zone sensors use a 10kW  
thermistor to measure the space  
temperature. Typically, zone sensors are  
wall-mounted in the room and include a  
space temperature thermistor. As an  
option, the zone sensor can be unit-  
mounted with a separate space  
temperature thermistor located in the  
units return air stream. If both a  
hardwired and communicated space  
temperature value exist, the controller  
ignores the hardwired space  
Communication jack  
Use the RJ-11 communication as the  
connection point from Rover™ service  
tool to the communication link — when  
the communication jack is wired to the  
communication link at the controller. By  
accessing the communication jack via  
Rover™, you can access any controller  
on the link.  
When the controller is in unoccupied  
mode, it always uses the stored unoccu-  
pied heating and cooling setpoints.The  
unit can also be configured to enable or  
disable the local (hardwired) setpoint.  
This parameter provides additional  
flexibility to allow you to apply communi-  
cated, hardwired, or default setpoints  
without making physical changes to the  
unit.  
Communications  
TracerZN520 controller communicates  
via Tranes LonTalk protocol. Typically, a  
communication link is applied between  
unit controllers and a building automation  
system. Communication also is possible  
via Rover, Tranes service tool. Peer-to-  
peer communication across controllers is  
possible even when a building  
temperature input and uses the  
communicated value.  
Similar to hardwired setpoints, the  
effective setpoint value for a communi-  
cated setpoint is determined based on  
the stored default setpoints (which  
determines the occupied and occupied  
standby temperature deadbands) and  
the controllers occupancy mode.  
External Setpoint Adjustment  
Zone sensors with an external setpoint  
adjustment (1k) provide the Tracer  
ZN520 controller with a local setpoint (50  
to 85°F or 10 to 29.4°C). The external  
setpoint is exposed on the zone sensors  
front cover.  
automation system is not present. You do  
not need to observe polarity for LonTalk  
communication links.  
Fan Switch  
The controller provides six 0.25-inch  
quick-connect terminals for the LonTalk  
communication link connections, as  
follows:  
Two terminals for communication to the  
board  
Two terminals for communication from  
the board to the next unit (daisy chain)  
Two terminals for a connection from the  
zone sensor back to the controller  
The zone sensor fan switch provides the  
controller with an occupied (and occupied  
standby) fan request signal (Off, Low,  
Medium, High, Auto). If the fan control  
request is communicated to the  
controller, the controller ignores the  
hardwired fan switch input and uses the  
communicated value. The zone sensor  
fan switch input can be enabled or  
disabled through configuration using the  
Rover service tool. If the zone sensor  
switch is disabled, the controller resorts  
to its stored configuration default fan  
speeds for heating and cooling, unless the  
controller receives a communicated fan  
input.  
When the hardwired setpoint adjustment  
is used to determine the setpoints, all unit  
setpoints are calculated based on the  
hardwired setpoint value, the configured  
setpoints, and the active mode of the  
controller. The hardwired setpoint is used  
with the controllers occupancy mode  
(occupied, occupied standby, or unoccu-  
pied), the heating or cooling mode, the  
temperature deadband values, and the  
heating and cooling setpoints (high and  
low limits) to determine the controllers  
active setpoint.  
Table O-SO-16. Zone sensor wiring  
connections  
When a building automation system or  
other controller communicates a setpoint  
to the controller, the controller ignores  
the hardwired setpoint input and uses  
the communicated value. The exception  
is the unoccupied mode, when the  
controller always uses the stored default  
unoccupied setpoints. After the controller  
completes all setpoint calculations, based  
on the requested setpoint, the occupancy  
TB1  
1
description  
space temperature  
common  
When the fan switch is in the off position,  
the controller does not control any unit  
capacity. The unit remains powered and  
all outputs drive to the closed position.  
Upon a loss of signal on the fan speed  
input, the controller reports a diagnostic  
and reverts to using the default fan  
speed.  
2
3
setpoint  
4
fan mode  
5
communications  
communications  
6
UNT-SVX07A-EN  
59  
Maintenance  
diagnostics  
Diagnostics  
Table M-D-1. Tracer ZN520 Diagnostics  
Diagnostic  
Fan  
Off  
Other Outputs (Note 1)  
Condensate overflow  
Valves Closed, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Low temperature detection  
Low air flow - fan failure  
Space temperature failure  
Entering water temp failure  
Discharge air temp low limit  
Discharge air temp failure  
Fresh air temp failure  
Relative humidity failure  
Generic 4-20ma failure  
CO2 Input failure  
Off  
Off  
Off  
On  
Off  
Off  
On  
On  
On  
On  
On  
On  
On  
Off  
On  
Valves Open, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Valves Closed, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Valves Closed, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Valves Enabled (Note 2), Fresh air damper Enabled (Note 2),  
electric heat Enabled (Note 2), Baseboard heat Off  
Valves Open, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off  
Valves Closed, Fresh air damper Closed, electric heat Off,  
Baseboard heat Off,  
Valves Enabled, Fresh air damper Minimum position3, electric  
heat Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Maintenance required  
Local fan mode failure  
Local setpoint failure  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, Electric Heat  
Enabled, Baseboard heat Enabled  
Valves Enabled, Fresh air damper Enabled, electric heat  
Enabled, Baseboard heat Enabled  
Invalid unit configuration  
Normal – power up  
Valves Disabled, Fresh air damper Disabled, electric heat  
Disabled, Baseboard heat Disabled  
Valves Enabled, Fresh air damper Enabled, Electric heat Enabled  
Note 1: The generic binary output (TB4-1, TB4-2) state is unaffected by all unit diagnostics.  
Note 2: When the entering water tem perature is required but not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition. The  
controller autom atically clears the diagnostic once a valid entering water tem perature value is present (non-latching diagnostic). When the entering water  
tem perature sensor fails, the controller prohibits all hydronic cooling operation, but allows the delivery of heat when heating is required. In the Cool m ode, all cooling  
is locked-out, but norm al fan and outdoor air dam per operation is perm itted.  
Note 3: When the outdoor air tem perature sensor has failed or is not present, the Tracer ZN520 controller generates a diagnostic to indicate the sensor loss condition.  
The controller autom atically clears the diagnostic once a valid outdoor air tem perature value is present (non-latching diagnostic). When the outdoor air tem perature  
sensor fails or is not present, the controller prohibits econom izer operation.  
60  
UNT-SVX07A-EN  
Maintenance  
diagnostics  
Translating Multiple Diagnostics  
The controller senses and records each  
diagnostic independently of other  
diagnostics. It is possible to have multiple  
diagnostics present simultaneously. The  
diagnostics are reported in the order they  
occur.  
Table M-D-2. Tracer ZN510 controller diagnostics  
diagnostic  
latching?  
no  
fan  
valves  
elec heat damper  
auxiliary  
temp. failure  
enabled no action no action no action  
condensate  
overflow  
yes  
no  
off  
closed  
enabled  
enabled  
off  
closed  
detection  
entering  
water temp.  
failure  
enabled  
enabled  
enabled enabled  
Possible diagnostics include:  
Low temperature detection  
• Condensate overflow  
fan mode  
failure  
no  
enabled enabled  
disabled disabled  
Low air flow - fan status  
• Discharge air temp limit  
• Space temperature failure1  
• Entering water temp failure1  
• Discharge air temp failure1  
• Outdoor air temp failure1  
Local setpoint failure1  
invalid unit  
configuration  
failure  
yes  
disabled disabled  
low temp.  
detection  
yes  
yes  
off  
open  
off  
closed  
maintenance  
required  
enabled no action no action no action  
enabled no action no action no action  
setpoint  
no  
no  
Local fan mode failure1  
• CO2 sensor failure1  
zone temp. failure  
Notes:  
off  
closed  
off  
closed  
• Generic AIP failure1  
• Humidity input failure1  
• Defrosting compressor lockout1  
• Maintenance required  
Priority Level: Diagnostics are listed in order from highest to lowest priority. The controller senses and  
records each diagnostic independently of other diagnostics. It is possible to have m ultiple diagnostics  
present sim ultaneously. The diagnostics affect unit operation according to priority level.  
Latching: A latching diagnostic requires a m anual reset of the controller; while a non-latching diagnostic  
autom atically resets when the input is present and valid.  
Enabled: End device is allowed to run if there is a call for it to run.  
Disabled: End device is not allowed to run even if there is a call for it to run.  
No Action: The diagnostic has no affect on the end device.  
Invalid unit configuration  
• Generic temperature failure  
• Discharge air low limit  
1 Non-latching diagnostics automatically  
reset when the input is present and valid.  
Cycling Power to the Controller  
After the controller detects the first  
special diagnostic, the unit waits 30  
minutes before invoking the automatic  
diagnostic reset function. The automatic  
diagnostic reset function clears the  
special diagnostic and attempts to restore  
the controller to normal operation. The  
controller resumes normal operation until  
another diagnostic occurs.  
After removing and reapplying the 24  
VAC power from the board, the unit  
cycles through a power-up sequence. By  
default, the controller attempts to reset all  
diagnostics present at power-up.  
Diagnostics present at power-up and  
those that occur after power-up are  
handled according to Table M-D-2.  
Resetting Diagnostics  
There are a number of ways in which  
diagnostics are reset:  
1. Automatic reset by the controller  
2. By initiating a manual output test at the  
controller  
3. By cycling power to the controller  
4. Through Rover™, Tranes service tool  
5. Tracer ZN520: by using any other  
communicating device ab le to access  
the controllers diagnostic reset input.  
6. Tracer ZN520: by cycling the fan switch  
from Off to any speed setting.  
Using Tranes Service Tool, Rover™  
Rover™, Tranes service tool, can reset  
diagnostics present in the controller and  
troubleshoot the unit. For more  
information, refer to the Trane publication  
EMTX-SVX01D-EN, Rover Installation,  
Operation and Programming Guide.  
Note: The automatic diagnostic reset  
function does not operate during the  
manual output test sequence.  
If a special diagnostic occurs within 24  
hours after an automatic diagnostic reset,  
the controller must be manually reset.  
Other possible methods of resetting  
diagnostics are described in the sections  
that follow.  
Automatic Reset by the Controller  
The controller includes an automatic  
diagnostic reset function that attempts to  
automatically restore the unit when a low  
temperature diagnostic occurs.  
Diagnostic Reset  
Any device that can communicate the  
network variable nviRequest  
(enumeration “clear_alarm”) can reset  
diagnostics in the Tracer ZN520  
controller.The controller also attempts to  
reset diagnostics whenever power is  
cycled.  
Note: The controller implements the  
automatic diagnostic reset function only  
once every 24 hours. For the controller to  
increment the 24 hour timer, you must  
maintain power to the controller. Cycling  
power resets all timers and counters.  
Manual Output Test  
To verify proper end device operation,  
press the controllers Test button. This  
exercise will verify all outputs in a  
predefined sequence, the first of which  
will attempt to reset the controller  
diagnostics if any are present.  
Cycling the Fan Switch  
Cycle the fan speed switch from Off to  
any speed and the controller resets all  
diagnostics. Diagnostics may recur  
immediately if the problem still exists.  
UNT-SVX07A-EN  
61  
diagnostics  
Maintenance  
Table M-D-3. Fan outputs do not energize  
Probable Cause  
Random start  
Explanation  
After power-up, the controller always observes a random start that varies observed between 0 and 25 seconds. The controller  
remains off until the random start time expires.  
Power-up control wait  
When power-up control wait is enabled (non-zero time), the controller remains off until one of two conditions occurs:  
1. The controller exits power-up control wait once it receives communicated information.  
2. The controller exits power-up control wait once the power-up control wait time expires.  
Cycling fan operation  
Unoccupied operation  
When the fan mode switch is in the auto postion, the unit fan cycles off when there is no call for heating or cooling. The heating/  
cooling sources cycle on oroff periodically with the unit fan to match the capacity according to pulse-width-modulation (PWM) logic.  
The fan cycles with capacity when the unit is in unoccupied mode. This occurs even if the unit is in continuous fan operation. While  
unoccupied, the fan cycleson or off with heating/cooling to provide varying amounts of heating or cooling to the space. to match the  
capacity according to pulse-width-modulation (PWM) logic.  
Fan mode off  
When using the local fan mode switch to determine the fan operation, the off position controls the unit fan to off.  
Requested mode: off  
It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When “off” is communicated to the  
controller, the unitcontrols the fan to off. The unit is not capable of heating or cooling when the controller is in this mode.  
Diagnostic present  
A specific list of diagnostics effects fan operation. For more information, see the “Diagnostics” section.  
No power to the  
controller  
If the controller does not have power, the unit fan will not operate. For the controller  
controller to operate  
normally, it must have an input voltage of 24 VAC. Whenthe green LED is off continuously, the controller does not have sufficient  
power or the controller has failed.  
Manual output test  
Unit wiring  
The controller includes a manual output test sequence to verify binary output operation and the associated wiring. However, based  
on the current step in the test sequence, the unit fan may not be powered on. Refer to the “Manual Output Test” section.  
The wiring between the controller outputs and the fan relays and contacts must be present and correct for normal fan operation.  
Refer to the typical unit wiringdiagrams in the Appendix of this manual.  
Table M-D-4. Valves Stay Closed  
Probable Cause  
Explanation  
Normal operation  
Requested mode: off  
The controller opens and closes the valves to meet the unit capacity requirements.  
It is possible to communicate the operating mode (such as off, heat, and cool) to the controller. When off is communicated to the  
controller, the unitcontrols the fan to off. The unit is not capable of heating or cooling when the controller is in this mode.  
Valve override  
The controller can communicate a valve override request. This request effects the valve operation.  
Manual output test  
The controller includes a manual output test sequence to verify analog and binary output operation and the associated wiring.  
However, based on thecurrent step in the test sequence, the valves may not be open. Refer to the “Manual Output Test” section.  
Diagnostic present  
Sampling logic  
A specific list of diagnostics affects valve operation. For more information, see the “Diagnostics” section.  
The controller includes entering water temperature sampling logic that automatically invokes during 2-pipe or 4-pipe changeover. It  
determines whenthe entering water temperature is either too cool or too hot for the desired heating or cooling mode. Refer to the  
Entering Water section.  
Unit configuration  
No power to the  
The controller must be properly configured based on the actual installed end devices and application. When the unit configuration  
does not match the actualend device, the valves may not work correctly.  
If the controller does not have power, the valves do not operate. For the controller controller to operate normally,  
it must have an input voltage of 24 VAC. When the green LED is off continuously, the controller does not have sufficient power,or the  
controller has failed.  
Unit wiring  
The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation. Refer to the  
typical unit wiring diagrams in the Appendix of this manual.  
Table M-D-5. Valves Stay Open  
Probable Cause  
Normal operation  
Valve override  
Explanation  
The controller opens and closes the valves to meet the unit capacity requirements.  
The controller can communicate a valve override request to affect the valve operation.  
Manual output test  
The controller includes a manual output test sequence that verifies analog and binary output operation and the associated wiring.  
However, based on thecurrent step in the test sequence, the valves may be open. Refer to the “Manual Output Test” section.  
Diagnostic present  
Sampling logic  
A specific list of diagnostics affects valve operation. For more information, see the “Diagnostics” section.  
The controller includes entering water temperature sampling logic that automatically invokes during 2-pipe or 4-pipe  
changeover to determine if the entering water temperature is correct for the unit operating mode. Refer to the “Entering Water  
Temperature Sampling” section.  
Unit configuration  
Unit wiring  
The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does  
not match the actual end device, the valves may not work correctly.  
The wiring between the controller outputs and the valve(s) must be present and correct for normal valve operation. Refer to the  
typical unit wiring diagrams inthe Appendix of this manual.  
62  
UNT-SVX07A-EN  
diagnostics  
Maintenance  
Table M-D-6. Electric Heat Not Operating  
Probable Cause  
Explanation  
Normal operation  
Requested mode: off  
The controller cycles electric heat on and off to meet the unit capacity requirements.  
It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated to the controller,  
the units shuts off the electric heat.  
Communicated disable  
Manual output test  
Numerous communicated requests may disable electric heat, including an auxiliary heat enable input and the heat/cool mode input.  
Depending on the state of the communicated request, the unit may disable electric heat.  
The controller includes a manual output test sequence that verifies analog and binary output operation and associated output  
wiring. However, based on the current step in the test sequence, the electric heat may not be on. Refer to the “Manual Output Test”  
section.  
Diagnostic present  
Unit configuration  
A specific list of diagnostics affects electric heat operation. For more information, see the “Diagnostics” section.  
The controller must be properly configured based on the actual installed end devices and application. When the unit configuration does  
not match the actual end device, the electric heat may not work properly.  
No power to the controller  
Unit Wiring  
If the controller does not have power, electric heat does not operate. For the controller to operate normally, a  
24VAC input voltage must be applied. Whenthe green LED is off continuously, the controller does not have sufficient power or has  
failed.  
The wiring between the controller outputs and the electric heat contacts must be present and correct for normal electric heat  
operation. Refer to the typicalunit wiring diagrams in the Appendix of this manual.  
Table M-D-7. Fresh Air Damper Stays Open  
Probable Cause  
Explanation  
Normal operation  
The controller opens and closes the fresh air damper based on the controllers occupancy mode and fan status. Normally, the  
fresh air damper is open during m occupied mode when the fan is running and closed during unoccupied mode.  
Manual output test  
The controller includes a manual output test sequence that verifies analog and binary output operation and associated output  
wiring. However, based on thecurrent step in the test sequence, the fresh air damper may not be open. Refer to  
the “Manual Output Test” section.  
Unit configuration  
Unit wiring  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actualend device, the damper may not work correctly.  
The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper operation. Refer  
to the typical unit wiringdiagrams in the Appendix of this manual.  
Table M-D-8. Fresh Air Damper Stays Closed  
Probable Cause  
Explanation  
Normal operation  
The controller opens and closes the fresh air damper based on the controllers occupancy mode and fan status. Normally, the  
fresh air damper is open during m occupied mode when the fan is running and closed during unoccupied mode.  
Warmup and cooldown  
Requested mode: off  
Manual output test  
The controller includes both a warmup and cooldown sequence to keep the fresh air damper closed during the transition from  
unoccupied to occupied. This is an attempt to bring the space under control as quickly as possible.  
It is possible to communicate the operating mode (such as off, heat, cool) to the controller. When off is communicated to the  
controller, the unit closes the fresh air damper.  
The controller includes a manual output test sequence that verifies analog and binary output operation and associated output  
wiring. However, based on thecurrent step in the test sequence, the fresh air damper may not be open. Refer to  
the “Manual Output Test” section.  
Diagnostic present  
Unit configuration  
A specific list of diagnostics effects fresh air damper operation. For more information, see the “Diagnostics” section.  
The controller must be properly configured based on the actual installed end devices and application. When the unit  
configuration does not match the actualend device, the damper may not work correctly.  
No power to the controller  
Unit wiring  
If the controller does not have power, the fresh air damper does not operate. For the controller to operate normally, a  
24 VAC input voltage must be applied.When the green LED is off continuously, the controller does not have sufficient power or has  
failed.  
The wiring between the controller outputs and the fresh air damper must be present and correct for normal damper operation. Refer  
to the typical unit wiringdiagrams in the Appendix of this manual.  
UNT-SVX07A-EN  
63  
Maintenance  
troubleshooting  
Board switches are factory set based on  
unit control options. Figure M-T-2 shows a  
relay board detail. Additional information  
on switch settings follows.  
Switch SW1: Controller Type  
SW1 determines the unit control type.  
Position 1 indicates one of the following:  
• generic field controller  
• low-voltage fan speed switch  
Tracer ZN010  
Tracer ZN510  
Position 2 indicates Tracer ZN520.  
Switch SW2: Electric Heat  
SW2 determines if the unit has electric  
heat.  
Switch SW3: High-Speed Interlock  
SW3 determines if the unit will have a  
safety-mandated “high-speed interlock”  
with electric heat. High-speed interlock  
ensures heat dissipates in a manner that  
keeps the unit in a safe operating  
condition. SW3 configures the unit to  
actuate high-speed interlock if the first or  
second stage is on.  
Figure M-T-1. Resistance temperature curve for the zone sensor, entering water temperature  
sensor, and discharge air sensor. Thermisitor = 10kat 77°F.  
interface to  
LED indicates  
Tracer ZN controller  
power  
SW3 is a three-position slide switch that  
actuates high-speed interlock to operate  
with specific electric heat coils.  
configuration switches  
(factory pre-set)  
• Position 1: default position and for low  
vertical units with electric heat  
• Position 2: single-stage electric heat,  
model number digit 18 = N  
• Position 3: two-stage electric  
connection to valve  
piping sensor crossover  
harness  
&
Switch SW4: Electric Heat Lockout  
SW4 allows the unit to use the electric  
heat lockout function when hydronic heat  
is in operation. Electric heat lockout  
prevents electric heat from enabling  
when hydronic heating is available. This  
feature is on models with both hydronic  
and electric heat. Low vertical models  
with electric heat, switch SW4 to position  
2 (on).  
Do not adjust these  
sw itch positions because  
it m ay result in a safety  
h a za rd !  
Note: HAZARDOUS voltage  
in dashed area of board!  
Figure M-T-2. Relay board detail  
Troubleshooting the Relay  
Board  
If the board needs replacement, the  
switches on the new board must be field-  
set in the same positions as the old board,  
as shown in the unit wiring diagram.  
The relay board serves as a common  
interface to all of the standard end  
devices, and has an LED that indicates  
power to the board. Factory switches are  
pre-set and locked in place with lock-tight.  
However, these seals can be broken if  
field-modifications are needed.  
Note: SW3 and SW4 affect safety  
functionality, and they are factory  
secured. When replacing a board with  
SW3 and SW4, be sure to affix the switch  
positions with 3M 3764Q or equivalent.  
64  
UNT-SVX07A-EN  
Maintenance  
troubleshooting  
Troubleshooting Tracer ZN010, ZN510 & ZN520  
Gre e n S TATUS LED  
indicates whether  
the controller is  
powered on (24  
VAC supplied)  
Ye llo w COMM LED  
indicates if  
communication is  
functioning  
Re d S ERVICE LED  
indicates is  
service is needed  
Figure M-T-1. The Tracer ZN010 board  
If the LED blinks (1/4 second on, 1/4 second  
off for 10 seconds) the controller is in the  
“Wink” mode.  
Red SERVICE LED  
During normal operation, the LED is off  
continuously when power  
is applied to the controller.  
Note: The “wink” feature allows the  
identification of a particular controller.  
When sending a request from a device,  
such as Rover™, the controller will  
“wink” to indicate it received the signal.  
If the LED is on continuously, even when  
power is applied to the controller means  
that someone is pressing the SERVICE  
button or that the controller has failed.  
If the LED flashes once every second, use  
Rover™, Tranes service tool, to restore  
the unit to normal operation. Refer to the  
Rover™ product literature for more  
information.  
If the LED is off, either the power is off, an  
abnormal condition is present or the  
TEST button is pressed.  
Yellow COMM LED  
Note: If the Service button is held down  
for more than 15 seconds on the Tracer  
ZN520 controller, it will uninstall itself  
from the ICS communication network and  
shut down all unit operation.  
If the LED is off continuously, the  
controller is not detecting any  
communication. This is normal for units in  
standalone applications.  
If the LED blinks, the controller detects  
communication.  
Green STATUS LED  
During normal operation, the LED is on  
continuously.  
If the LED is on continuously, this indicates  
an abnormal condition.  
Manual Output Test  
If the LED blinks once, the controller is in  
Manual output test mode.  
The purpose of the manual output test  
sequence is to verify output and end  
device operation. Use the manual output  
test to:  
If the LED blinks twice the controller is in  
Manual output test mode, with one or  
more diagnostics present.  
UNT-SVX07A-EN  
65  
Maintenance  
troubleshooting  
Manual Output Test Procedure  
Follow the procedure below to test the  
Tracer ZN010, ZN510, and ZN520  
controllers.  
Verify output wiring and operation  
without using Rover™, service tool  
• Force the water valve to open and  
balance the hydronic system  
1. Press and hold the TEST button for at  
least two seconds (not exceeding 5  
seconds), and then release, to start the  
test mode.  
2. The test sequence will turn off all  
outputs and then attempt to clear all  
diagnostics.  
3. Press the TEST button several more  
times (no more than once per second)  
to advance through the test sequence.  
Note: The manual output test is not an  
automatic cycle. You must press the  
TEST button to proceed through each  
step.  
The controller observes all diagnostics  
that occur during the test sequence.  
Although an automatic diagnostic reset  
sequence exists as part of the controllers  
normal operation, the automatic diagnos-  
tic reset feature is not active during the  
test sequence.  
The outputs are not subject to minimum  
times during the test sequence. However,  
the test sequence only permits one step  
per second which limits minimum output  
time.  
If left in an individual test step, the  
controller remains in test mode for 60  
minutes and then exits to normal  
operation.  
The green LED is turned off when the  
TEST button is pressed. To begin the  
manual output test mode, press and hold  
the TEST button (turning off the green  
LED) for at least two seconds.The green  
LED will begin to blink, indicating the  
controller is in test mode.  
Many service calls are due to unit  
diagnostics. The test sequence resets  
unit diagnostics and attempts to restore  
normal unit operation prior to testing the  
outputs. If the diagnostics remain after a  
reset, the STATUS LED indicates the  
diagnostic condition is still present (two  
blinks).  
Table M-T-1. Test sequence for 1-heat/1-cool configurations  
steps  
fan  
BOP1-3  
cool output  
BOP4 (1)  
heat output damper  
BOP5 BOP6  
1. off  
off  
off  
off  
off  
off  
on  
off closed  
2. fan High  
3. fan medium  
4. fan low  
5. cool  
high  
medium  
low  
off  
off  
off  
off  
on  
off  
closed  
closed  
closed  
closed  
closed  
open  
high  
high  
high  
6. heat  
off  
off  
7. fresh air  
damper (3)  
8. exit  
(2)  
Notes:  
(1) At the beginning of step 2, the controller attem pts to clear all diagnostics.  
(2) For all 1-heat/1-cool applications including 2-pipe changeover, BOP4 energizes in  
the cooling test stage and BOP5 energizes in the heat test stage.This occurs even  
though during norm al 2-pipe changeover operation BOP4 controls the unit valve  
for both cooling and heating.  
(2) After the Fresh Air Dam per step, the test sequence perform s the Exit step.This  
initiates a reset and attem pts to return the controller to norm al operation.  
(3) The fresh air dam per (BOP6) only energizes during this step if binary output 6  
has been configured as a fresh air dam per.  
66  
UNT-SVX07A-EN  
m aintenance  
procedures  
Maintenance  
Maintenance Procedures  
Perform the following maintenance  
procedures to ensure proper unit  
operation.  
All models except vertical cabinets  
Remove the front panel of the vertical  
recessed unit and open the bottom panel  
door of the horizontal cabinet and  
horizontal recessed unit to access the  
filter. The front panel of the vertical  
cabinet unit does not require removal to  
change the filter.  
Co il  
WARNING  
S id e  
Live Ele c t ric a l Co m p o n e n t s !  
During installation, testing, servicing,  
and troubleshooting this equipm ent, it  
m ay be necessary to work with live  
electrical com ponents. Have a  
qualified licensed electrician or other  
individual who is properly trained in  
handling live electrical com ponents  
perform these tasks. Failure to follow  
all electrical com ponents could result  
in death or serious injury.  
Main Drain  
Z-Bar  
Note: Vertical recessed, horizontal  
cabinet, & horizontal recessed units with  
a bottom return have filter guides to  
secure the filter in position. Also, if these  
unit types have a fresh air opening, they  
require an additional filter for the fresh air  
opening.  
Figure M-MP-1. When replacing the fan-  
coils main drain pan, install it correctly  
under the z-bar.  
Main Drain Pan  
See Figure M-MP-1 to replace main drain  
correctly.  
CAUTION  
Re p la c e a ll p a n e ls a n d filt e rs  
properly!  
All unit panels and filters m ust be in  
place prior to unit startup. Failure to  
have panels and filters in place m ay  
result in equipm ent dam age.  
Vertical Units  
WARNING  
To remove the main drain pan on vertical  
fan-coil units, disconnect the clips holding  
the pan to the fanboard. Disconnect the  
main and overflow drain hoses and slide  
pan forward to remove. See Figure M-  
MP-3.  
Ha za rd o u s Vo lt a g e w /Ca p a c it o rs !  
Disconnect all electric power,  
including rem ote disconnects and  
discharge all m otor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing com ponents provided by  
Trane or others, refer to the  
Inspecting and Cleaning Drain Pans  
Clean the fan-coil units main and  
auxiliary drain pans to ensure the unit  
drains condensate properly.  
Horizontal Units  
To remove the main drain pan on a  
horizontal fan-coil unit, peel the insulation  
from the edges of the pans underside to  
access the mounting screws. Remove the  
screws and lower the end of the drain  
pan closest to the control box. Remove  
the drain spout by pulling it from the hole  
in the chassis end panel. See Figure M-  
MP-4.  
Check the condensate drain pan and  
drain line to assure the condensate drains  
properly at least every six months or as  
dictated by operating experience.  
appropriate m anufacturers literature  
for allowable waiting periods for  
discharge of capacitors. Verify with an  
appropriate voltm eter that all  
If evidence of standing water or conden-  
sate overflow exists, immediately identify  
and remedy the cause.  
capacitors have discharged. Failure to  
disconnect power and discharge  
capacitors before servicing could  
result in death or serious injury.  
Note: Do not operate the fan-coil unit  
without the main and auxiliary drain pans  
in place to prevent condensate leakage.  
Clean the drain pans of any moisture or  
debris.  
Auxiliary Drain Pan  
1. To remove the auxiliary drain pan,  
loosen the hose clamp (installer  
supplied) around the drain connection  
collar and disconnect the drain line.  
2. Remove the overflow drain line to the  
auxiliary drain pan if it was installed.  
3. Remove the condensate overflow  
switch option from the auxiliary drain  
pan.  
4. Slide the pan horizontally towards the  
end of the large groove of the mounting  
slots in the chassis end panel and  
remove pan from unit. See Figure M-  
MP-2.  
Air Filters  
Change or clean air filters at least twice a  
year. Filters require more frequent care  
under high load or dirty air conditions  
since a clogged filter reduces airflow.  
Table M-A-1 lists filter size and quantity  
by unit size. Throwaway and pleated  
media filters are available for all units.  
Follow the instructions below to replace  
the disposable filters.  
aux. drain pan attaches to these slots  
Figure M-MP-2. Insert the auxiliary drain pan  
tabs into these slots in the fan-coils chassis  
end panel. A horizontal unit shown.  
UNT-SVX07A-EN  
67  
m aintenance  
procedures  
Maintenance  
Coil Maintenance  
Inspect coils at least every six months or  
more frequently as dictated by operating  
experience. Cleaning frequently is  
dependent upon system operating  
hours, filter maintenance, and efficiency  
and dirt load. Follow the suggested  
methods in the following paragraphs.  
Keep coils clean to maintain maximum  
performance. For operation at its highest  
efficiency, clean the coil often during  
periods of high demand or when dirty  
conditions prevail. Clean the coil a  
minimum of once a year to prevent dirt  
buildup in the coil fins, where it may not  
be visible.  
clips hold drain pan in place  
Steam and Hydronic Coil Cleaning  
Procedure  
Remove large debris from the coils and  
straighten fins before cleaning. Remove  
filters before cleaning.  
1. Disconnect all electrical power to the  
unit.  
Figure M-MP-3. To remove the main drain  
pan on vertical fan-coil units, disconnect  
the clips holding the pan to the fanboard.  
2. Don the appropriate personal  
protective equipment (PPE).  
3. Access both sides of the coil.  
4. Use a soft brush to remove loose  
debris from both sides of the coil.  
5. Use a steam cleaning machine,  
starting from the top of the coil and  
working downward. Clean the leaving  
air side of the coil first, then the  
entering air side. Use a block-off to  
prevent steam from blowing through  
the coil and into a dry section of the  
unit.  
6. Repeat step five as necessary.  
Confirm that the drain line is open  
following completion of the cleaning  
process.  
7. Allow the unit to dry thoroughly before  
putting the system back into service.  
8. Straighten any coil fins that may be  
damaged with a fin rake.  
Clean the coil fins using steam with  
detergent, hot water spray and deter-  
gent, or a commercially available  
chemical coil cleaner. Be sure to rinse  
coils thoroughly after cleaning.  
WARNING  
m ounting screw s  
Ha za rd o u s Ch e m ic a ls !  
Coil cleaning agents can be either  
acidic or highly alkaline. Handle  
chem ical carefully. Proper handling  
should include goggles or face shield,  
chem ical resistant gloves, boots,  
apron or suit as required. For  
personal safety refer to the cleaning  
agent m anufacturers Materials  
Safety Data Sheet and follow all  
recom m ended safe handling  
practices. Failure to follow all safety  
instructions could result in death or  
serious injury.  
Figure M-MP-4. To remove the main drain  
pan on horizontal fan-coil units, peel the  
insulation from the edges of the pans  
underside to access the mounting screws.  
9. Replace all panels and parts and  
restore electrical power to the unit.  
Winterizing the Coil  
Make provisions to drain coils that are  
not in use, especially when subjected to  
freezing temperatures.  
Inspecting and Cleaning Coils  
Coils become externally fouled as a  
result of normal operation. Dirt on the  
coil surface reduces its ability to transfer  
heat that can result in comfort problems,  
increased airflow resistance and thus  
increased operating energy costs. If the  
coil surface dirt becomes wet, which  
commonly occurs with cooling coils,  
microbial growth (mold) may result,  
causing unpleasant odors and serious  
health-related indoor air quality  
problems.  
To drain the coil, blow the coil out with  
compressed air. Next, fill and drain the  
tubes with full-strength ethylene glycol  
several times. Drain the coil as com-  
pletely as possible.  
CAUTION  
Co il Fre e ze -u p Da m a g e !  
Failure to properly drain and vent  
coils when not in use during freezing  
tem peratures m ay result in coil  
freeze-up dam age.  
68  
UNT-SVX07A-EN  
m aintenance  
procedures  
Maintenance  
Fan Board Assembly Removal  
Follow the procedure below when  
replacing the coil or making repairs to the  
fan or motor.  
CAUTION  
He a vy Ob je c t !  
Support the fanboard when rem oving  
it from the unit. Failure to properly  
support fanboard m ay result in m inor  
to m oderate personal injury.  
WARNING  
Ha za rd o u s Vo lt a g e w /Ca p a c it o rs !  
Disconnect all electric power,  
including rem ote disconnects and  
discharge all m otor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing com ponents provided by  
Trane or others, refer to the  
appropriate m anufacturers literature  
for allowable waiting periods for  
discharge of capacitors. Verify with an  
appropriate voltm eter that all  
capacitors have discharged. Failure to  
disconnect power and discharge  
capacitors before servicing could  
result in death or serious injury.  
Replacing the Motor  
The capacitor for all unit motors can be  
replaced should it fail. Contact the local  
Trane service department to replace the  
motor capacitor in the event it fails.  
However, the motor itself cannot be  
repaired or rewound. If the motor fails,  
record the model number from the unit  
nameplate and present to the local Trane  
Service Parts Center to purchase a  
replacement. The motor bearings are  
permanently lubricated and do not  
require any further oiling.  
After removing the fanboard assembly  
from the unit, disconnect the fan wheel/  
wheels from the motor shaft by loosening  
the Allen head setscrew on the fan wheel  
hub collar. Next, remove the mounting  
bolts holding the fan motor plate to the  
mounting bracket of the fanboard. Then  
remove the motor by sliding the fan shaft  
from the fan wheel hub.  
Vertical Units  
1. Remove the front panel of cabinet and  
recessed units.  
2. Pull the main and overflow drain hoses  
of the main drain pan into the inside of  
the fan-coil chassis end panel.  
3. Remove the two fanboard mounting  
screws.  
During re-assembly, make certain the fan  
wheel(s) is/are properly centered in the  
fan housing to prevent the fan wheel  
from contacting the housing on either  
side. After the unit has been re-as-  
sembled, verify that no unusual noise or  
vibration is present at startup.  
4. Slide the fanboard out horizontally to  
remove.  
Control Device Replacement  
To order control components such as  
relays, contactors, transformers, low  
temperature detection devices,  
Horizontal Units  
1. Open the bottom panel of cabinet and  
recessed models.  
condensate overflow detection devices,  
differential pressure switches, sensors,  
control valves and actuators, contact the  
local Trane Service Parts Center. To order,  
the Trane parts center will need the unit  
model number (which can be found on  
the unit nameplate), the serial number,  
and the part name or ID.  
2. Remove the main drain pan following  
the instructions given under the drain  
pan section above for horizontal fan-coil  
units.  
3. While supporting the fanboard in place,  
remove the two fanboard mounting  
screws which secure the fanboard to  
the unit.  
UNT-SVX07A-EN  
69  
m aintenance  
procedures  
Maintenance  
Periodic Maintenance  
Checklists  
Monthly Maintenance  
1. Inspect unit air filters. Clean or replace  
if airflow is blocked or if filters are dirty.  
2. Check the main and auxiliary drain  
pans on fan-coil units to be  
sure the pans are clean and do not  
impede the condensate flow  
through the drain line.  
Monthly Checklist  
The following check list provides the  
recommended maintenance schedule to  
keep the unit running efficiently.  
WARNING  
Annual Maintenance  
Check and tighten all set screws, bolts,  
locking collars and sheaves.  
1. Inspect the unit cabinetry for chips or  
corrosion. Clean or repair to  
provide unit protection.  
2. Inspect the fan wheel and housing for  
damage. Rotate the fan  
wheel manually to be sure movement  
is not blocked by obstructions.  
3. Inspect the coil fins for excessive dirt or  
damage. Remove dirt and  
Live Ele c t ric a l Co m p o n e n t s !  
During installation, testing, servicing,  
and troubleshooting this equipm ent, it  
m ay be necessary to work with live  
electrical com ponents. Have a  
qualified licensed electrician or other  
individual who is properly trained in  
handling live electrical com ponents  
perform these tasks. Failure to follow  
all electrical com ponents could result  
in death or serious injury.  
straighten fins.  
4. Clean and tighten all electrical  
connections.  
5. Inspect the strainer option for debris  
trapped in the filter screen.  
WARNING  
Ha za rd o u s Vo lt a g e w /Ca p a c it o rs !  
Disconnect all electric power,  
including rem ote disconnects and  
discharge all m otor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing com ponents provided by  
Trane or others, refer to the  
appropriate m anufacturers literature  
for allowable waiting periods for  
discharge of capacitors. Verify with an  
appropriate voltm eter that all  
capacitors have discharged. Failure to  
disconnect power and discharge  
capacitors before servicing could  
result in death or serious injury.  
70  
UNT-SVX07A-EN  
typical w iring  
diagram  
Maintenance  
CSTI Fan Speed Switch  
UNT-SVX07A-EN  
71  
typical w iring  
diagram  
Maintenance  
CSTI Non Fan Speed Switch  
72  
UNT-SVX07A-EN  
typical w iring  
diagram  
Maintenance  
Line voltage fan speed switch  
UNT-SVX07A-EN  
73  
typical w iring  
diagram  
Maintenance  
Tracer ZN010 with electric heat  
74  
UNT-SVX07A-EN  
typical w iring  
diagram  
Maintenance  
Tracer ZN510 with main and auxilliary valves  
UNT-SVX07A-EN  
75  
typical w iring  
diagram  
Maintenance  
ZN520 with 2-stage electric heat  
76  
UNT-SVX07A-EN  
US  
Literature Order Number  
UNT-SVX07A-EN  
File Number  
PL-TD-UNT-SVX07A-EN 0405  
UNT-IOM-6 04/00  
Supersedes  
a business of Am erican Standard Inc.  
www.trane.com  
Stocking Location  
LaCrosse - Inland  
For more information contact  
your local office or e-mail us at  
Trane has a policy of continuous product improvement and reserves the right to change design and specifications  
without notice. Only qualified technicians should install and service equipment.  

Xerox Bhwm 129 User Manual
Samsung Avmkc032ca0 User Manual
MAKITA FS6300A User Manual
KENWOOD LVD 68 User Manual
HP CQ1859S User Manual
FUJITSU LIFEBOOK E743 User Manual
CRAFTSMAN 917.271080 User Manual
ASUS ZENFONE A501CG User Manual
ASUS VS229D User Manual
ACER ASPIRE 4310 User Manual