		 Outdoor unit specifications   
					HP   
					4 
					5 
					6 
					Model name   
					Power supply   
					(SPW-)   
					CR365GX56   
					CR365GXH56   
					CR485GX56   
					CR485GXH56   
					CR605GX56   
					CR605GXH56   
					220/230/240V-1 phase/50, 60Hz   
					(kW)   
					11.2   
					11.2   
					14.0   
					14.0   
					15.5   
					15.5   
					Cooling   
					38,200   
					38,200   
					47,800   
					47,800   
					52,900   
					52,900   
					(BTU/h)   
					Capacity   
					(kW)   
					(BTU/h)   
					(W/W)   
					(W/W)   
					(mm)   
					(kg)   
					12.5   
					16.0   
					17.6   
					Heating   
					42,700   
					54,600   
					60,000   
					Cooling   
					Heating   
					4.06   
					4.06   
					4.34   
					3.66   
					3.66   
					4.10   
					3.39   
					3.39   
					3.84   
					COP   
					x 
					x 
					x 
					x 
					Dimension (H W D)   
					1,230 940 340   
					Net weight   
					130   
					Running amperes   
					(A)   
					14.8/14.1/13.5   
					2.76   
					14.8/14.1/13.5   
					2.76   
					20.5/19.6/18.8   
					3.83   
					20.5/19.6/18.8   
					3.83   
					24.4/23.4/22.4   
					4.57   
					24.4/23.4/22.4   
					4.57   
					Cooling   
					Heating   
					Power input   
					(kW)   
					Running amperes   
					Power input   
					(A)   
					15.4/14.7/14.1   
					2.88   
					20.8/19.9/19.1   
					3.90   
					24.5/23.4/22.5   
					4.58   
					(kW)   
					Color (munsell color chart)   
					Air circulation   
					Silky shade (1Y8.5/0.5)   
					(m3/min)   
					(kg)   
					95   
					95   
					95   
					3.5   
					ø19.05 x 1   
					Refrigerant amount at   
					shipment   
					3.5   
					3.5   
					Gas pipe   
					(mm)   
					(mm)   
					ø15.88   
					(Flare)   
					Piping   
					connections   
					Liquid pipe   
					ø9.52   
					(Flare)   
					+ 
					+ 
					Ambient temperature operating range   
					Cooling:-10°C DB   
					43°C DB,heating:-20°CWB 15°CWB   
					Maximum number of   
					connectable indoor units   
					6 
					8 
					9 
					Normal mode   
					dB(A)   
					dB(A)   
					51   
					48   
					52   
					49   
					52   
					49   
					53   
					50   
					53   
					50   
					54   
					51   
					Operating sound   
					Silent mode   
					* The values for performance and electric characteristics apply under the following test conditions.   
					At the time of cooling:Indoor suction air temperature 27°C DB,19°C WB,outdoor suction air temperature 35°C DB   
					At the time of heating:Indoor suction air temperature 20°C DB,outdoor suction air temperature 7°C DB,6°C WB   
					* The operating sound has been measured in an anechoic chamber,and it is the value one meter in front of the outdoor unit at a height   
					of 1.5 m.With actual installation,the indication value normally differs widely according to the surrounding noise and reverberations.   
					*1;Tube discharge assy supplied with outdoor unit   
				 |