EMERSON LIEBERT GTX4 10000RT230 User Manual

Liebert® GXT4  
User Manual – 5000VA ~ 10000VA (230V)  
Important Safety Precautions  
Save These Instructions  
This manual contains important safety instructions. Read all safety and operating instructions before operating  
the uninterruptible power system (UPS). Adhere to all warnings on the unit and in this manual. Follow all  
operating and user instructions. This equipment can be operated by individuals without previous training.  
This product is designed for commercial/industrial use only. It is not intended for use with life support and other  
designated ‘critical’ devices. Maximum load must not exceed that shown on the UPS rating label. The UPS is  
designed for data processing equipment. If uncertain, consult your dealer or local Emerson Network Power  
representative.  
This UPS is designed for use on a properly earthed (grounded), 220-240 VAC, 50Hz or 60Hz supply, for  
installation by qualified personnel. A qualified electrician must review and approve customer supplied wiring,  
circuit breakers, intended loads and verify correct input, output and earth connections to ensure compliance with  
technical standards and local electrical codes of practice.  
Installation instructions and warning notices only for use by qualified personnel are located after the UPS  
operator instructions in this manual.  
Warning  
The battery can present a risk of electrical shock and high short circuit current. The following precautions should  
be observed when replacing the battery pack:  
Wear rubber gloves and boots  
Remove rings, watches and other metal objects.  
Use tools with insulated handles.  
Do not lay tools or other metal objects on the batteries.  
If the battery kit is damaged in any way or shows signs of leakage, contact your local Emerson  
representative immediately.  
Do not dispose of batteries in a fire. The batteries may explode.  
Handle, transport and recycle batteries in accordance with local regulations.  
Warning  
Although the Liebert GXT4 has been designed and manufactured to ensure personal safety, improper use can  
result in electrical shock or fire. To ensure safety, observe the following precautions:  
Turn Off and unplug the Liebert GXT4 before cleaning it.  
Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.  
Never block or insert any objects into the ventilation holes or other openings of the UPS.  
Do not place the Liebert GXT4 power cord where it might be damaged.  
Notice  
If this UPS is supplied from an ‘IT’ electrical power system, the jumper on the rear panel must be disconnected.  
Refer to 8.8 IT Power System Configuration for details. If connecting to an ‘IT’ system, the installer must  
provide a 2-pole upstream circuit breaker. Refer to all local and national codes when installing the upstream  
breaker.  
ELECTROMAGNETIC COMPATIBILITY—The Liebert® GXT4™ complies with the limits of Category C2,  
pursuant to IEC/EN/AS 62040-2. Operation is subject to the following conditions:  
The output cables shall be no longer than 10m (32ft).  
This device may not cause harmful interference.  
This device must accept any interference received, including interference that may cause undesired  
operation. Operating this device in a residential area is likely to cause harmful interference that users must  
correct at their own expense.  
The Liebert GXT4 series complies with the requirements of EMC Directive 2004/108/EC and the published  
technical standards. Continued compliance requires installation in accordance with these instructions and use of  
accessories approved by Emerson.  
Notice  
1. This is a Category C2 UPS product. In a residential environment, this product may cause radio interference, in  
which case the user may be required to take additional measures.  
2. Operate the UPS in an indoor environment only in an ambient temperature range of 0-40°C (32-104°F). Install  
it in a clean environment, free from moisture, flammable liquids, gases and corrosive substances.  
3. This UPS contains no user-serviceable parts except the internal battery pack. The UPS Enter push button do  
not electrically isolate internal parts. Under no circumstances attempt to gain access internally due to the risk of  
electric shock or burn.  
4. Do not continue to use the UPS if the front panel indications are not in accordance with these operating  
instructions or the UPS performance alters in use. Refer all faults to your dealer.  
5. Servicing of batteries should be performed or supervised by personnel knowledgeable of batteries and the  
required precautions. Keep unauthorized personnel away from the batteries. Keep unauthorized personnel away  
from the batteries. Proper disposal of batteries is required. Refer to your local laws and regulations for disposal  
requirements.  
6. Never block or insert any object into the ventilation holes or other openings.  
7. DO NOT CONNECT equipment that could overload the UPS or demand DC current from the UPS, for  
example: electric drills, vacuum cleaners, laser printers, hair dryers or any appliance using halfwave rectification.  
8. Storing magnetic media on top of the UPS may result in data loss or corruption.  
9. Turn Off and isolate the UPS before cleaning it. Use only a soft cloth, never liquid or aerosol cleaners.  
Information for the Protection of the Environment  
UPS SERVICING—This UPS makes use of components dangerous for the environment (electronic cards,  
electronic components). The components removed must be taken to specialized collection and disposal centers.  
NOTICE TO EUROPEAN UNION CUSTOMERS: DISPOSAL OF OLD APPLIANCES—This product has been  
supplied from an environmentally aware manufacturer that complies with the Waste Electrical and Electronic  
Equipment (WEEE) Directive 2002/96/CE.  
The ‘crossed-out wheelie bin’ symbol at right is placed on this product to encourage you to recycle wherever  
possible. Please be environmentally responsible and recycle this product through your recycling facility at its end  
of life. Do not dispose of this product as unsorted municipal waste. Follow local municipal waste ordinances for  
proper disposal provisions to reduce the environmental impact of waste electrical and electronic equipment  
(WEEE).  
For information regarding the scrapping of this equipment, please browse  
technical support.  
Toll Free: 00 80011554499  
Toll Number Based in Italy: +39 0298250222  
Contents  
Chapter 8 Operation...................................................................................................................................................27  
Chapter 1 Introduction  
1
Chapter 1 Introduction  
Congratulations on your choice of the Liebert® GXT4™ uninterruptible power system (UPS). The Liebert GXT4  
comes in nominal power ratings of 5000VA, 6000VA and 10,000VA. It is designed to provide conditioned power to  
microcomputers and other sensitive electronic equipment.  
When it is generated, alternating current is clean and stable. However, during transmission and distribution it is  
subject to voltage sags, spikes and complete power failure that may interrupt computer operations, cause data loss  
and even damage equipment. The Liebert GXT4 protects equipment from these disturbances.  
The Liebert GXT4 is a compact, on-line UPS. An on-line UPS continuously conditions and regulates its output voltage,  
whether utility power is present or not. It supplies connected equipment with clean, sinewave power. Sensitive  
electronic equipment operates best from sinewave power.  
The Liebert GXT4 features a multicolor LCD display to indicate load percentage, input/output voltage and current,  
runtime of battery and so on. It also provides self-diagnostic tests by visual configuration.  
The Liebert GXT4 can be operated at high efficiency mode (Green Mode) which efficiency could up to 97%.  
The Liebert GXT4 includes E models without rack slide kits for different requirement of user.  
The Liebert GXT4 has a Liebert IntelliSlot® port for communication between the UPS and a network server or other  
computer systems. This port provides detailed operating information including voltages, currents and alarm status to  
the host system when used in conjunction with Liebert MultiLink®. Liebert MultiLink can also remotely control UPS  
operation.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
2
Chapter 2 System Description  
Chapter 2 System Description  
The operating principle of the UPS is shown in Figure 2-1.  
Dynamic Bypass  
Output  
Input  
Rectifier/PFC  
DC-to-DC  
Converter  
TVSS &  
EMI/RFI  
Filters  
L1  
N
L1  
N
Inverter  
Battery  
charger  
Battery  
G
G
Figure 2-1 Operating principle diagram  
2.1 Transient Voltage Surge Suppression (TVSS) and EMI/RFI Filters  
These UPS components provide surge protection and filter both electromagnetic interference (EMI) and radio  
frequency interference (RFI). They minimize any surges or interference present in the utility line and keep the  
sensitive equipment protected.  
2.2 Rectifier/Power Factor Correction (PFC) Circuit  
In normal operation, the rectifier/power factor correction (PFC) circuit converts utility AC power to regulated DC power  
for use by the inverter while ensuring that the waveshape of the input current used by the UPS is near ideal.  
Extracting this sinewave input current achieves two objectives:  
The utility power is used as efficiently as possible by the UPS.  
The amount of distortion reflected on the utility is reduced.  
This results in cleaner power being available to other devices in the building not being protected by the Liebert®  
GXT4™.  
2.3 Inverter  
In normal operation, the inverter utilizes the DC output of the power factor correction circuit and inverts it into precise,  
regulated sinewave AC power. Upon a utility power failure, the inverter receives its required energy from the battery  
through the DC-to-DC converter. In both modes of operation, the UPS inverter is on-line and continuously generating  
clean, precise, regulated AC output power.  
2.4 Battery Charger  
The battery charger utilizes energy from the utility power and precisely regulates it to continuously float charge the  
batteries. The batteries are being charged whenever the Liebert GXT4 is connected to mains power.  
2.5 DC-to-DC Converter  
The DC-to-DC converter utilizes energy from the battery system and raises the DC voltage to the optimum operating  
voltage for the inverter. This allows the inverter to operate continuously at its optimum efficiency and voltage, thus  
increasing reliability.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
           
Chapter 2 System Description  
3
2.6 Battery  
The Liebert® GXT4™ utilizes valve-regulated, nonspillable, lead acid batteries. To maintain battery design life,  
operate the UPS in an ambient temperature of 15°C to 25°C (59°F to 77°F). Optional external battery cabinets are  
available to extend battery run times. For run times, see Table 11-5.  
2.7 Dynamic Bypass  
The Liebert GXT4 provides an alternate path for utility power to the connected load in the unlikely event of a UPS  
malfunction. Should the UPS have an overload, overtemperature or any other UPS failure condition, the UPS  
automatically transfers the connected load to bypass.  
NOTE  
The bypass power path does NOT protect the connected equipment from disturbances in the mains supply.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
   
4
Chapter 3 Major Components  
Chapter 3 Major Components  
The Liebert® GXT4™ is composed of three major assemblies to provide easier handling, installation and versatility.  
3.1 Main Frame and Electronics  
The cabinet is shipped with internal batteries installed and a basic, hardwire distribution box attached and ready to  
install.  
Note: 10,000VA model's front layout is identical;  
the battery compartment is larger.  
Upper Bezel  
Operation and display panel  
Operation and  
display panel  
Upper Bezel  
Lower bezel and battery access door  
Figure 3-1 Liebert GXT4 5000VA and 6000VA (front view)  
Lower bezel and battery access door  
C19 output power  
receptacles  
REPO connection block  
Terminal block communication  
External battery connector  
USB port  
Liebert IntelliSlot port  
Output circuit  
breakers  
IT power system  
access cover  
C13 output  
receptacles  
Input circuit breaker  
Maintenance  
bypass breaker  
Output circuit  
breaker  
Knockouts for  
hardwired power input  
Liebert GXT4 5000VA and 6000VA  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
   
Chapter 3 Major Components  
5
C19 output power receptacles  
USB port  
Reserved  
Output circuit breaker  
REPO  
Terminal block  
communication  
Maintenance  
bypass breaker  
Input circuit  
breaker  
External battery  
connector  
Output circuit  
breaker  
Liebert IntelliSlot  
port  
C13 output  
receptacles  
Output circuit  
breaker  
Knockouts for  
hardwired power input  
IT power system  
access cover  
Liebert GXT4 10,000VA  
Figure 3-2 Liebert® GXT4™ (rear view)  
3.2 Removable Power Distribution Box  
The UPS is shipped with a power distribution pack installed, as shown in Figure 3-3 and Figure 3-4. This box contains  
the UPS input circuit breaker.  
Outer surface view of power distribution box  
for 5000VA and 6000VA models  
PD2-CE6HDWRMBS  
Quick-connect  
Figure 3-3 Power distribution box for GXT4 5000VA and 6000VA models  
Quick-connect  
Inner surface view of power distribution box  
for 10000VA model (PD2-CE10HDWRMBS)  
Front view  
Figure 3-4 Power distribution box for GXT4 10,000VA model  
Note  
Hardwire and hardwire/receptacle boxes that include a manual bypass switch allow AC power to continue to flow from the mains  
input to the load while the box is removed from the UPS. For details, refer to 5.3 Connect Input/Output Power.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
6
Chapter 3 Major Components  
3.3 Internal Battery Packs  
The UPS has two internal battery packs behind a battery access door on the front of the unit. Each internal battery  
pack is fitted with a connector to link to the UPS.  
Battery handle  
Battery connector  
Front of battery pack  
Figure 3-5 Internal battery pack features  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
Chapter 4 What’s Included  
7
Chapter 4 What’s Included  
The Liebert® GXT4™ is shipped with the following items:  
Terminal Block Communication terminals  
Compact disc with:  
Liebert MultiLink®  
Configuration program & Multi-languages package  
User manual (electronic version)  
USB cable, one; 2m (6-1/2 ft.) long  
Mounting hardware, including screws and handles  
Rack slide kits(E models do not include)  
Power Distribution Box, installed on Liebert GXT4  
Support base set, one  
Warnings, safety instructions booklet and WEEE recycling sheet (ISO 14001 compliance)  
Note  
The Liebert GXT4 External Battery Cabinet shipping package includes one battery cabinet, two spacers for tower configuration  
and one DC power cable.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
8
Chapter 5 Installation and Configuration  
Chapter 5 Installation and Configuration  
Do NOT attempt to start the UPS, turn on any circuit breaker or energize the input power until instructed to do so in  
8.2 Initial Startup And Electrical Checks.  
Visually inspect the UPS for shipping damage. Report any damage to the carrier and your local dealer or Emerson  
representative.  
Caution  
The UPS is heavy (refer to Chapter 11 Specifications). Take proper precautions when lifting or moving it.  
Install the Liebert® GXT4™ indoors in a controlled environment, where it cannot be accidentally turned off. Place it  
where air flows unrestricted around the unit. The installation location must be free of water, flammable liquids, gases,  
corrosives and conductive contaminants. Maintain a minimum clearance of 100mm (4 inches) in the front and rear of  
the UPS. Maintain an ambient temperature range of 0 to 40°C (32°F ~104°F).  
Note  
UPS operation in sustained temperatures outside the range of 15°C ~ 25°C (59°F ~ 77°F) reduces battery life.  
5.1 Install Main Cabinet  
The Liebert GXT4 may be installed in either a tower configuration or in a rack, depending on available space and use  
considerations. Determine the type of installation and follow the appropriate instructions in either 5.1.1 Tower UPS  
Installation or 5.1.2 Rack-Mount UPS Installation.  
5.1.1 Tower UPS Installation  
To install the Liebert GXT4 as a tower:  
1. Take the support bases out of the accessories bag (see Figure 5-1).  
Connector  
Spacer  
Support bases  
Figure 5-1 Support bases  
2. If optional Liebert external battery cabinets will be connected to the Liebert GXT4, take out the spacers shipped  
with the battery cabinet.  
3. Connect the spacers and the support bases as shown in Figure 5-1. Each Liebert GXT4 needs two assembled  
support bases, one in the front and one in the rear.  
4. Adjust the direction of the operation and display panel and logo on the Liebert GXT4.  
1) Remove the front plastic bezel cover as shown in Figure 5-2.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
     
Chapter 5 Installation and Configuration  
9
Front plastic  
bezel cover  
Figure 5-2 Remove the front plastic bezel cover  
2) Pull the operation and display panel gently, rotate it 90 degrees clockwise and snap it back into position, as shown  
in Figure 5-3.  
Operation and  
display panel rotated  
clockwise 90 degrees  
Figure 5-3 Rotate the operation and display panel  
3) Pull the logo on the front plastic bezel cover gently, rotate it 90 degrees clockwise and snap it back into position.  
The rotated front plastic bezel cover is shown in Figure 5-3.  
4) Replace the front plastic bezel cover on the Liebert® GXT4™. At this point, the UPS operation and display panel  
and logo have been rotated 90 degrees clockwise, which provides upright viewing for users.  
5. Place the Liebert GXT4 and any battery cabinets on the support bases. Each Liebert GXT4 needs two support  
assemblies, as shown Figure 3-1.  
5.1.2 Rack-Mount UPS Installation  
When using the Liebert GXT4 in a rack, the UPS must be supported by a slide kit, fixed rails or a shelf.  
When using the Adjustable Rack Mount Kit, you will use the following instructions. The figures accompanying 5.1.3  
Installing Adjustable Rack-Mount Kit—Sold Separately shows the positioning of the rack-mounting brackets. Emerson  
recommends taking the internal batteries out of the UPS during rack installation. This will make the UPS cabinet  
lighter and easier to handle.  
Caution  
The Liebert GXT4 is heavy; refer to Chapter 12 Specifications. The UPS must be installed as near the bottom of a rack as  
possible. If placed too high, it can make the rack top-heavy and prone to tipping over.  
5.1.3 Installing Adjustable Rack-Mount Kit—Sold Separately  
This kit contains parts needed to mount several different models of UPS and external battery cabinets into EIA310-D  
standard four-post racks that are 18" ~ 32" deep (457mm ~ 813mm). The weight limit per pair of adjustable  
rack-mounting brackets is 91kg (200lb). Parts included are shown in Table 5-1.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
   
10  
Chapter 5 Installation and Configuration  
Table 5-1 Included parts in rack-mount kit  
Item  
Quantity  
Rear bracket members  
Front bracket members  
Inner bracket members  
M4 machine screws  
M4 locking hex nuts  
M5 machine screws  
2
2
2
16  
8
8
Tools needed for installation are:  
one Phillips screwdriver  
one 7mm wrench  
The adjustable rack-mounting brackets (Part#: RMKIT18-32) feature retaining latches to prevent users from  
inadvertently sliding the UPS or battery cabinet out of the rack.  
To install the rack mount brackets:  
1. Unpack two rack-mounting bracket assemblies and mounting hardware from this kit. Bracket assemblies are  
interchangeable between left-hand or right-hand.  
2. Remove inner member of each bracket assembly shown in Figure 5-4 by extending it to its outermost position,  
depressing the retaining latch and then pulling the inner member out of the bracket assembly.  
Rear member  
Front member  
Retaining latch  
Inner member  
Figure 5-4 Removing inner member of each bracket assembly  
3. Determine the height position inside the rack enclosure where you want to mount the UPS or battery cabinet.  
Caution  
Reduce the risk of tipping the rack enclosure by placing the UPS or battery cabinet in the lowest possible rack position.  
4. Install the rear member of each bracket assembly into the rack enclosure with two M5 screws provided in this kit  
(see figure at right). The return flanges on the bracket assembly fit to the inside of rack mounting rails. Insert screws  
loosely (finger-tight) into the top and bottom holes of the return flange on the rear member.  
Mounting rail  
M5 screw (4 pcs)  
Rear member  
Front member  
Figure 5-5 Installing rear member of each bracket assembly  
5. Extend the bracket assembly by sliding the front member forward until it touches the front rack mounting rail. Insert  
two M5 screws loosely (finger-tight) into the top and bottom holes of the return flange on each front member. Make  
sure that the bracket assemblies are at the same mounting height on all four (4) rack mounting rails.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
Chapter 5 Installation and Configuration  
11  
e
lid  
S
Front vertical pole  
Front member  
Rear member  
M5 screw (4 pcs)  
Figure 5-6 Installing front member of each bracket assembly  
6. Get eight M4 screws and eight M4 nuts from the hardware pack in this kit. Each nut has a locking, nylon insert that  
begins gripping the screw when it is halfway tight. Make sure to tighten the nut and screw completely to ensure  
locking action. Fasten the rear member and the front member together using four screws and four nuts per bracket  
assembly as shown in Figure 5-6. For maximum support, insert fasteners for each bracket assembly as far apart as  
possible, depending on rack depth, while still joining both members (see figures at right). Check alignment of bracket  
assemblies and TIGHTEN ALL SCREWS FROM Step 3 to Step 5.  
Rear member  
M4 screw (8 pcs)  
M4 nut (8 pcs)  
Front member  
Figure 5-7 Fastening the rear member and the front member together  
7. Prepare the UPS or battery cabinet (the ‘equipment’) for rack mounting by following instructions in the equipment’s  
user manual. The equipment may require additional parts to be added or parts to be removed for rack mounting. After  
it is prepared, lay the equipment in rack-mounting position. Fasten the inner members from Step 2 to the equipment  
on both sides as shown at right with eight M4 screws provided in the kit. Make sure retaining latch is near the rear of  
the equipment as shown (see figure at right).  
UPS  
Inner member  
Retaining latch  
+-  
1
2
M4 screw (8 pcs)  
Figure 5-8 Fastening the inner members to the equipment  
8. If available, apply a bead of grease 1" (25mm) long at four places inside the bottom, curved tracks of the front  
members as shown below right. The grease will allow the equipment to slide into the bracket assemblies more easily.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
12  
Chapter 5 Installation and Configuration  
Caution  
1. Lifting equipment into the rack may be a two-person job, depending on the weight of the equipment.  
2. Liebert® recommends taking the internal batteries out of the UPS during rack installation. This will make the UPS cabinet  
lighter and easier to handle.  
3. The Liebert GXT4™ weighs 151 lb. (67kg). For the UPS weight, see Table 11-1; for the battery cabinet’s weight, see Table  
11-5.  
4. Factory-supplied rack handles are not intended to be used to lift the UPS. The handles are intended to be used to slide the UPS  
into and out of the rack.  
9. Insert the equipment, with inner members attached in Step 7, into the bracket assemblies by inserting the top and  
bottom edges of the inner members into the top and bottom curved tracks of the front members and sliding the  
equipment into the rack (see Figure 5-9). Ends of inner members are tapered to allow the rear of the equipment to be  
angled upward before insertion, if space allows.  
Then the rear, bottom edges of the inner members can be placed into the front edge of the bottom tracks and the  
front of the equipment can be tipped up so they are level to insert the top edges of the inner members before sliding  
the equipment into the rack (see Figure 5-9). The equipment should move smoothly into the bracket assemblies. If it  
does not, recheck the alignment of the front and rear members from Steps 4 and 5.  
Insert  
Front member  
Inner member  
Figure 5-9 Inserting the UPS  
10. Secure the front of the equipment to the rack mounting rails to prevent the equipment from sliding out of position.  
If securing holes are provided on the front of the equipment that align with the center holes on the return flange of the  
front members, you can use the four extra M5 screws provided in the kit to secure the equipment. Otherwise, the  
equipment should be secured to the front of the rack with four customer-supplied fasteners.  
5.2 External Battery Cabinet Installation  
Optional Liebert® external battery cabinets may be connected to the UPS to provide additional battery run time.  
External battery cabinets are designed to be placed on one side of the UPS or stacked beneath the UPS. External  
battery cabinets can be used in either a rack-mount or tower configuration.  
Caution  
The external battery cabinet(s) are heavy (refer to Chapter 12 Specifications). Take proper precautions when lifting them.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
Chapter 5 Installation and Configuration  
13  
10,000VA  
Liebert GXT4  
Cables connecting  
battery cabinets to  
10,000VA  
Liebert GXT4  
Battery cabinet  
Figure 5-10 External battery cabinets connected to 10,000VA Liebert® GXT4™  
1. Inspect the external battery cabinet for freight damage. Report damage to the carrier and your local dealer or  
Emerson representative.  
2. For slide rail installations, first remove the top/side fin. Top/side fin slides forward and then lift up to remove.  
Optional rack-mount handles are shipped with the external battery cabinet and may be installed at this time if desired.  
3. Securing hardware and slide rails are sold separately. Please contact your local dealer or Emerson representative  
for these additional options and any assistance needed. Fasten the slides into position with the screws per the  
instructions included with the slide rails.  
4. Use the enclosed support bases for the tower option to prevent tip-over. One additional set of support base  
extensions ships with each external battery cabinet.  
5. Put the UPS in Bypass Mode by operating LCD configuration  
6. Verify the External Battery Cabinet breaker is in the Off position.  
7. Connect the supplied external battery cabinet cable to the rear of the external battery cabinet, then to the rear of  
the UPS.  
8. Turn the External Battery Cabinet breaker to the On position.  
9. Operating LCD panel to return the unit to Inverter Mode.  
10. Verify the circuit breaker on the External Battery Cabinet is in the On position.  
11. Use the included configuration program or LCD to program the UPS for the number of external battery cabinets  
connected. Instructions for the configuration program are in 6.0 Configuration Program.  
12. The UPS is now equipped with additional backup battery run time. For approximate battery run times, refer to  
Table 11-5.  
Note  
1. When removing the External Battery Cabinet, the circuit breaker on the rear of the cabinet must be turned off before  
disconnecting the cable.  
2. If the UPS is to be shipped or stored for an extended time, the connector should be disconnected. This will minimize any  
standby current drain on the batteries and help attain their design life.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
14  
Chapter 5 Installation and Configuration  
5.3 Connect Input/Output Power  
Extract these captive screws  
Extract these captive screws  
Maintenance bypass breaker  
Power distribution box removal from  
5000VA and 6000VA models  
Maintenance bypass breaker  
Power distribution box removal from 10,000VA model  
Figure 5-11 Power Distribution box removal—captive screws and maintenance bypass breaker  
The UPS should arrive with the power distribution box attached. If the box needs to be removed for maintenance or  
replacement, follow these instructions to remove and install the power distribution pack.  
To remove:  
1. Ensure maintenance bypass lamp is on. To place the unit in maintenance bypass, refer to 8.4 Put Liebert GXT4  
In Bypass.  
2. Loosen one captive screw over the maintenance bypass breaker.  
3. Turn the maintenance bypass breaker on.  
Notice  
The load is unprotected from disturbances in the power supply while the UPS is on bypass.  
4. Turn the output and input breaker off.  
5. Loosen other captive screws until the power distribution box releases.  
6. Remove the power distribution box from the UPS and set it aside.  
7. Loosen screws over the plastic cover for the connector on the rear of the panel.  
8. Slide plastic cover over connector and tighten screws.  
Note  
Do not operate the UPS with this box removed. To disconnect all power to this box and load, the utility input power also must be  
disconnected.  
To install:  
1. Align connectors and press box onto UPS  
2. Hold box firmly against UPS and tighten captive screws except one over the maintenance bypass breaker.  
3. Turn the output and input breaker on.  
4. Start the UPS according to startup instructions.  
5. Verify that the UPS lamp is illuminated.  
6. Turn the maintenance bypass breaker off.  
7. Insert the maintenance bypass cover behind the captive screw and tighten the screw.  
Note  
The maintenance bypass breaker cover must be installed behind the captive screw and the screw must be tightened for the UPS to  
operate in inverter mode.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
Chapter 5 Installation and Configuration  
15  
Distribution box electrical connections  
Electrical connections are made through a removable power distribution box that attaches to the rear of the UPS.  
PD2-CE6HDWRMBS fits the 5000 and 6000VA models of the Liebert GXT4  
PD2-CE10HDWRMBS fits the 10,000VA model of the Liebert GXT4  
The installer must provide an upstream branch circuit breaker. The input circuit breaker on the distribution box and  
the output circuit breaker on the rear of the power distribution box disconnect all power between the main cabinet and  
the distribution box.  
Models equipped with a manual bypass breaker pass bypass power directly to the bypass breaker from the input  
terminal block. The input circuit breaker on the distribution box does not disconnect power from the manual bypass  
breaker.  
Table 5-2 Branch circuit breaker ratings  
Unit Rating  
5000VA  
Maximum Breaker Rating  
D Type 32A  
6000VA  
10,000VA  
D Type 63A  
Figure 5-12 Distribution box electrical connections diagram  
Terminal block connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS  
Conduit entry holes are provided on the rear and side of the box. Input and output wiring should not share the same  
conduit. Emerson recommends using strain relief when installing the wire.  
Table 5-3 Electrical specifications  
Recommended  
(Maximum) External  
Overcurrent Protection  
Recommended Wire  
(Including ground wire)  
(75°C copper wire)  
Maximum Wire  
Accepted by  
Terminal  
Tightening  
Torque  
UPS Model  
Terminal Block  
GXT4-5000RT230  
GXT4-5000RT230E  
GXT4-6000RT230  
GXT4-6000RT230E  
GXT4-10000RT230  
GXT4-10000RT230E  
32A  
63A  
4mm2 (10AWG)  
10mm2 (6AWG)  
6mm2 (8AWG)  
16mm2 (4AWG)  
2.26Nm (20 in-lb)  
PD2-CE6HDWRMBS  
PD2-CE10HDWRMBS  
Figure 5-13 Terminal block connections—PD2-CE6HDWRMBS and PD2-CE10HDWRMBS  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
16  
Chapter 5 Installation and Configuration  
Note  
1. The installer must provide circuit breaker protection according to local codes. The utility disconnect should be within sight of  
the UPS or have appropriate an appropriate lock-out. Maintain service space around the UPS or use flexible conduit.  
2. The installer must provide output distribution panels, circuit breaker protection or emergency disconnects according to local  
codes. Output circuits must not share a common conduit with any other wiring.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
Chapter 6 Configuration Program  
17  
Chapter 6 Configuration Program  
The final step of installation may require custom configuration of your UPS using the enclosed configuration program.  
Some configuration settings may be changed only while the UPS is off. These should be set before the UPS is put  
into full-time service powering the critical load.  
For most users operating with 230VAC and with no external batteries, the factory default settings will be adequate.  
6.1 Configuration Program Features  
Select L-N output voltages to match local voltages.  
Enable/Disable Auto-Restart.  
Select frequency converter operation with a fixed output frequency of 50 or 60 Hz.  
Set the Low Battery Warning alarm time from 2 to 30 minutes.  
Enable/Disable the Auto-Battery test.  
Set the Auto-Battery test to 8, 12, 16, 20 or 26 weeks.  
Specify the number of external battery cabinets connected to the UPS to adjust the remaining run time  
calculations reported by Liebert® software products.  
Modify the shutdown setting of the terminal block (for information on pin assignments, see Table 5-3).  
6.2 What You Will Need  
In addition to the Liebert GXT4™ UPS, you will need the configuration program CD and USB cable included in the  
UPS accessory box. A Windows 95® or later computer, desktop or laptop, is also required to set up and run the  
configuration program.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
     
18  
Chapter 7 Operation And Display Panel  
Chapter 7 Operation And Display Panel  
This chapter describes the operation and display panel of the Liebert GXT4, including LED indicators, control buttons  
and LCD display panel.  
The operation and display panel is on the front panel of the Liebert GXT4 (see Figure 7-1), which provides four  
control buttons, seven LED indicators and a LCD display panel, as shown in Figure 7-1.  
Inverter indicator Battery indicator  
Bypass indicator  
Fault indicator  
LCD display panel  
Green mode indicator  
ENTER button  
ESC button  
UP button DOWN button  
Figure 7-1 Operation and display panel  
7.1 LED Indicators  
The operation and display panel provides seven LED indicators: inverter indicator, bypass indicator, battery indicator,  
fault indicator, and green mode indicator. Their descriptions are listed in Table 7-1.  
Table 7-2 LED indicators  
LED Indicators  
Inverter indicator  
LED color  
Green  
Description  
On when the inverter is supplying power, and off otherwise  
On when the load is supplied by the mains through automatic/manual  
bypass, and off otherwise  
Bypass indicator  
Amber  
Battery indicator  
Fault indicator  
Amber  
Red  
On when the load is supplied by the battery, and off otherwise  
On when an error has occurred within the UPS, and off otherwise  
On when the UPS is in green mode, and off otherwise  
Green mode indicator  
Green  
Caution  
Do not switch off the UPS or switch from online to bypass, otherwise the loads will no longer be supported.  
7.2 Control Buttons  
The operation and display panel provides four control buttons: ESC button, UP button, DOWN button and ENTER  
button. Their descriptions are listed in Table 7-2.  
Table 7-3 Control buttons  
Control buttons  
ESC button  
Description  
Pressing this button returns to the previous menu or aborts any change in the input data field  
before confirming  
Pressing this button can move the cursor up or increase the value displayed in the input data  
field. When a menu is displayed on several screens, pressing the button can scroll up  
Pressing this button can move the cursor down or decrease the value displayed in the input  
data field. When a menu is displayed on several screens, pressing the button can scroll down  
Pressing this button can enter the next level menu or confirm the parameter setting value  
UP button  
DOWN button  
ENTER button  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
     
Chapter 7 Operation And Display Panel  
19  
7.3 LCD Display Panel  
The operation and display panel provides a LCD display panel, enabling you to view the UPS status and change the  
UPS settings.  
7.3.1 Startup Screen  
When the UPS is starting up, the UPS begins self-testing, and then the LCD display panel will display EMERSON  
icon for about 10s, as shown in Figure 7-2.  
Figure 7-2 Startup screen  
7.3.2 ON Screen  
About 10s later, the LCD display panel will display the corresponding ON screen depending on whether the AC is  
available, as shown in Figure 7-3.  
AC NOT AVAILABLE  
TURN ON UPS  
START ON BATTERY?  
YES NO  
YES NO  
O / P : 230V 50HZ 17.6A O / P : 230V 50HZ 17.6A  
I / P : 230V 50HZ 18.0A I / P : 230V 50HZ 18.0A  
BATT : 100% 100MINS  
LOAD : 80%  
BATT : 100% 100MINS  
LOAD : 80%  
Figure 7-3 Startup screen  
Select ‘YES’ and press the ENTER button, the UPS will start up, and the LCD display panel will display ‘START  
SUCCESSFUL’, as shown in Figure 7-4.  
START SUCCESSFUL  
O / P : 230V 50HZ 17.6A  
I / P : 230V 50HZ 18.0A  
BATT : 100% 100MINS  
LOAD : 80%  
Figure 7-4 ‘START SUCCESSFUL’ screen  
7.3.3 Default Screen  
Press any button in the ‘STATTUP SUCCESSFULLY’ screen to enter the default interface, as shown in Figure 7-5.  
GXT4 - UPS  
6KVA  
O / P : 230V 50HZ 17.6A  
I / P : 230V 50HZ 18.0A  
BATT : 100% 100MINS  
LOAD : 80%  
Figure 7-5 Default screen  
In the default screen, the LCD display panel will display the UPS model, operation mode (ONLINE, GREEN, GREEN  
AUTO, and BYPASS), output parameters, input parameters, battery capacity and load percentage.  
If no control button is pressed within two minutes, the LCD display panel will enter a screen-protection state (the back  
lighting is off) until any control button is pressed.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
       
20  
Chapter 7 Operation And Display Panel  
7.3.4 Main Menu Screen  
Press any button in the default screen to enter the Main Menu screen, as shown in Figure 7-6.  
1
2
3
4
5
STATUS  
CONFIGURATION  
CONTROL  
LOG  
ABOUT  
Figure 7-6 Main Menu screen  
To select a submenu, press the UP or DOWN button to move the cursor to the required item, and press the ENTER  
button to enter its submenu or set its parameter.  
STATUS screen  
Select Main Menu -> 1 STATUS to enter the STATUS screen, displaying OUTPUT, LOAD, INPUT,PARALLEL,  
BATTERY and TIME SINCE STARTUP, as shown in Figure 7-7.  
OUTPUT  
VOLT  
LOAD  
INPUT  
PARALLEL  
:
:
230V  
50Hz  
17.6A  
VOLT  
FREQ  
CURR  
:
:
:
230V  
50HZ  
18.6A  
VOLT  
FREQ  
CURR  
:
:
:
230V  
50HZ  
17.6A  
CAP  
WATT :  
VA  
:
90%  
4000W  
4000VA  
FREQ  
:
CURR  
POWER :  
:
POWER:  
4000WH  
4000WH  
BATTERY  
PARALLEL  
TIME SINCE STARTUP  
05D 15H 30M  
CAPACITY  
RUNTIME  
VOLTAGE  
:
:
:
90%  
100MINS  
148V  
CAP  
WATT :  
VA  
:
90%  
4000W  
4000VA  
:
Figure 7-7 STATUS screen  
CONFIGURATION screen  
Select Main Menu -> 2 CONFIGURATION to enter the CONFIGURATION screen. This menu has five submenus, as  
shown in Figure 7-8.  
1
2
3
4
5
UPS  
BATTERY  
ECO  
LCD  
FACTORY DEFAULT  
Figure 7-8 CONFIGURATION screen  
In the CONFIGURATION screen, press the UP or DOWN button to move the cursor to the required item, and press  
the ENTER button to enter its submenu or set its parameter.  
1. UPS screen  
Select Main Menu -> 2 CONFIGURATION -> 1 UPS to enter the UPS screen. This menu has seve n screens, as  
shown in Figure 7-9.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
Chapter 7 Operation And Display Panel  
21  
AUDIBLE ALARM  
ON OFF  
STARTUP ON BYPASS  
YES NO  
ENABLE AUTO RESTART  
YES NO  
GUARANTEE SHUTDOWN  
YES NO  
PARALLEL  
FREQUENCY SELECTION  
VOLTAGE SELECTION  
AUTO - BYPASS ENABLE  
AUTO - BYPASS DISABLE  
TYPE  
3
3
230  
ADDRESS  
Figure 7-9 UPS screen  
Press the UP or DOWN button to move the cursor to the required item, and press the ENTER button to confirm the  
settings.  
2. BATTERY screen  
Select Main Menu -> 2 CONFIGURATION -> 2 BATTERY to enter the BATTERY screen. This menu has four  
submenus, as shown in Figure 7-10.  
BATT REPLACE TIME  
EXT BATT CABINET  
CABINETS  
LOW BATTERY TIME  
0 2 CABINETS  
BATT TEST INTERVAL  
2 6 WEEKS  
0
2 0 13 Y 0 8 M 0 8 D  
Figure 7-10 BATTERY screen  
Press the UP or DOWN button to increase or decrease the value of the settings, and press the ENTER button to  
confirm it.  
3. OPERATION MODE screen  
Select Main Menu -> 2 CONFIGURATION -> 3 OPERATION MODE to enter the OPERATION MODE screen, as  
shown in Figure 7-11.  
OPERATION MODE  
ONLINE MODE  
GREEN MODE ON  
GREEN MODE AUTO  
Figure 7-11 OPERATION MODE screen  
Press the UP or DOWN button to move the cursor to the required item, and press the ENTER button to confirm the  
settings.  
4. LCD screen  
Select Main Menu -> 2 CONFIGURATION -> 6 LCD to enter the LCD screen. This menu has two submenus, as  
shown in Figure 7-12.  
1
2
LANGUAGE  
COLOR  
Figure 7-12 LCD screen  
1) Select ‘1 LANGUAGE’ and press the ENTER button to enter the LANGUAGE screen, as shown in Figure 7-13.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
22  
Chapter 7 Operation And Display Panel  
1
2
3
ENGLISH  
中文  
Upload others  
Figure 7-13 LANGUAGE screen  
2) Select ‘2 COLOR’ and press the ENTER button to enter the COLOR screen, as shown in Figure 7-14.  
EMERSON  
EMERSON  
EMERSON  
EMERSON  
Figure 7-14 COLOR screen  
5. FACTORY DEFAULT screen  
Select Main Menu -> 2 CONFIGURATION -> 7 FACTORY DEFAULT to enter the FACTORY DEFAULT screen, as  
shown in Figure 7-15.  
RESET ALL SETTINGS  
TO FACTORY DEFAULT  
SETTINGS?  
YES NO  
Figure 7-15 FACTORY DEFAULT screen  
CONTROL Screen  
Select Main Menu -> 3 CONTROL to enter the CONTROL screen, as shown in Figure 7-16.  
1
2
3
TURN ON & OFF  
ALARM CONTROL  
BATT TEST  
Figure 7-16 CONTROL screen  
In the CONTROL screen, press the UP or DOWN button to move the cursor to the required item, and press the  
ENTER button to enter its submenu.  
1. TURN ON & OFF screen  
Select Main Menu -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen, as shown in  
Figure 7-17.  
TURN UPS OFF  
TURN UPS ON  
TURN UPS BYPASS  
The UPS is off  
The UPS is on  
Figure 7-17 TURN ON & OFF screen  
2. ALARM CONTROL screen  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
Chapter 7 Operation And Display Panel  
23  
Select Main Menu -> 3 CONTROL -> 2 ALARM CONTROL to enter the ALARM CONTROL screen, as shown in  
Figure 7-18.  
1
2
AUDIBLE ALARM ON  
AUDIBLE ALARM OFF  
Figure 7-18 ALARM CONTROL screen  
3. BATT TEST screen  
Select Main Menu -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen, as shown in Figure 7-19.  
1
2
3
START  
CANCEL  
BATT TEST RESULT  
Figure 7-19 BATT TEST screen  
LOG Screen  
Select Main Menu -> 4 LOG to enter the LOG screen, as shown in Figure 7-20.  
1
2
EVENT LOG  
CLEAR LOG  
Figure 7-20 LOG screen  
1. Select Main Menu -> 4 LOG -> 1 EVENT LOG to enter the EVENT LOG screen, as shown in Figure 7-21.  
254/255  
255 OD 1H 17M AGO  
UPS switch to Online  
mode  
Figure 7-21 ALL LOG screen  
2. Select Main Menu -> 4 LOG -> 2 CLEAR LOG to enter the CLEAR LOG screen, as shown in Figure 7-22.  
DO YOU WANT TO  
CLEAR EVENT LOGS?  
YES NO  
Figure 7-22 CLEAR LOG screen  
Press the UP or DOWN button to move the cursor to the required item, and press the ENTER button to confirm the  
settings.  
ABOUT Screen  
Select Main Menu -> 5 ABOUT to enter the ABOUT screen, as shown in Figure 7-23.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
24  
Chapter 7 Operation And Display Panel  
Figure 7-23 ABOUT screen  
The ABOUT screen displays: UPS model, SN, software version and hardware version.  
Menu structure  
The menu structure of the LCD display panel is shown in Figure 7-24.  
Figure 7-24 Menu structure  
7.3.5 Prompt List  
A prompt screen is displayed during the operation of the system to alert you to certain conditions and/or to require  
your confirmation of a command or other operation. The prompts and meanings are given in Table 7-3.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
Chapter 7 Operation And Display Panel  
25  
Table 7-4 Prompts and meanings  
No.  
1
Prompt  
Utility power restored  
Meanings  
The utility power recovers, and the UPS transfers back to Utility (AC)  
mode  
The bypass power recovers, and the UPS can transfers back to  
bypass  
2
Bypass power restored  
3
4
UPS return from a low battery condition  
UPS return from battery mode  
The UPS transfers back to Utility (AC) mode from Battery low mode  
The UPS transfers back to Utility (AC) mode from Battery mode  
Conditions of battery test do not meet,UPS battery test is not  
allowed  
5
UPS battery test unallowed  
6
7
UPS self test successful  
UPS self test in progress  
UPS turn off  
The UPS self-test is successfully performed  
The UPS is performing self-test  
8
The UPS shuts down and has no output  
9
UPS TURN ON  
The UPS starts up successfully and supplies power to the load  
The UPS Maintenance bypass output  
10  
11  
UPS Maintenance bypass output  
UPS shutdown command received  
The UPS shuts down through communication  
The shutdown command sent through Multilink or SNMP card to the  
UPS is cancelled  
12  
13  
14  
UPS shutdown process had been cancelled  
UPS switch to Green mode  
The UPS transfers back to Green mode, saving more electricity  
When the input utility power satisfies the condition of Auto Green  
mode, the UPS will transfer back to Auto Green mode  
The UPS transfers back to Online mode, supplying power to the  
load through the inverter  
UPS switch to Auto Green mode  
15  
16  
17  
UPS switch to Online mode  
UPS internal temperature return to normal  
UPS load return from overload  
The internal temperature of the UPS recovers to normal range  
The loads are reduced, and the UPS recovers to normal state from  
overload  
The beeper is disabled, and no audible alarm will be generated  
when faults or warnings occur again  
18  
19  
Beeper Disable  
Beeper Enable  
The beeper is enabled, and audible alarms will be generated when  
faults or warnings occur again  
7.3.6 Warning List  
All UPS warning messages are described in Table 7-4.  
Table 7-5 Warning list  
No.  
1
Warning  
Description  
The utility power is not available, or it cannot satisfy the  
requirements for the UPS to operate  
Utility power not available  
2
UPS batteries low and exhausted soon  
UPS has switched to battery mode  
The battery capacity is low and will be exhausted soon  
The utility power is abnormal or the PFC side is faulty, the UPS  
transfers back to Battery mode  
3
The UPS transfers back to Bypass mode, at this point, the input  
utility power supplies power to the load directly, and the load is  
not protected  
4
UPS Switch to Bypass  
The bypass power is not available, or it cannot satisfy the  
requirements for the UPS to transfers to bypass (include phase  
angle abnormal for two phase model)  
5
6
Bypass power not available  
Input power wiring error  
Ground is not connected or L/N wires are reversed or Input  
phase error  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
26  
Chapter 7 Operation And Display Panel  
7.3.7 Fault List  
All UPS fault messages are described in Table 7-5.  
Table 7-6 Fault list  
No.  
1
Fault  
Description  
UPS self test failed  
PFC Out of Order  
UPS overload  
The battery is bad or weak  
2
PFCfailure occurs  
3
The UPS is overloaded  
The inverter is faulty  
The battery is bad or weak  
4
Inverter Out of Order  
Battery Weak/Bad  
Output Short-circuit  
DC Bus Over-voltage  
5
6
The output connection is short-circuited  
The DC bus is faulty  
7
Over-temperature occurs to the UPS and the UPS will transfer to  
Bypass mode  
8
UPS Over-temperature  
9
Charger Out of Order  
Fan Out of Order  
The charger is faulty  
10  
11  
At least one fan is faulty  
DC Bus Discharge Fail  
DCDC failure occurs  
If a fault occurs, the UPS automatically switches to Bypass mode. Only in the case of a battery disconnection fault will  
the original operating mode be maintained. The fault message alternates with UPS mode once a second, the red fault  
indicator on the operation and display panel lights up and the alarm sounds continuously.  
If a fault occurs, proceed as follows:  
1. Enter the ALARM CONTROL screen (see Figure 7-18), and select ‘AUDIABLE ALARM ON’ or ‘AUDIBLE ALARM  
OFF’ to switch on/off the alarm.  
2. Enter the EVENT LOG screen (see Figure 7-21), and select ‘3 CRITICAL’ to view the fault log.  
Note  
Please wait patiently when you enter the EVENT LOG screen to view the historical fault log. Because the LCD display panel  
needs to read the faults from the DSP at a relatively slow reading speed, the reading time depends on the uploaded information  
quantity.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
Chapter 8 Operation  
27  
Chapter 8 Operation  
This section describes checks to be made before starting the UPS, how to start the UPS, manual battery test, manual  
bypass, shutting down the UPS and disconnecting the utility power from the UPS.  
Note  
The Liebert® GXT4’s battery has been fully charged before delivery, but some charge will be lost during storage and shipping.  
To ensure that the battery has adequate reserve power to protect the connected load, charge the battery for three hours before  
putting the UPS into service.  
8.1 Startup Checklist For Liebert GXT4™  
Before starting the UPS, perform these checks:  
1. Check that the input plugs and loads are connected properly and reliably.  
2. Check that the battery cable is connected properly.  
3. Check that the communication cables are connected properly.  
8.2 Initial Startup And Electrical Checks  
1. Verify that the Input/Output circuit breakers are off.  
2. During initial system checks, disconnect all loads (open load disconnects).  
3. Inspect all wiring, cables and connection.  
4. If external battery cabinets are used, verify that the battery interconnect cables are fully inserted in the sockets.  
5. Place the manual bypass breaker in BYPASS position.  
6. Turn on the branch circuit disconnect to apply voltage to the input terminal block.  
7. Using a voltmeter, verify the expected L1-N (L2) voltage.  
Verify that the same voltages appear at the Output terminals. The Bypass lamp by the switch will light.  
8. After verifying proper input voltage to the UPS terminal block, turn off the branch circuit power, close all access  
panels to the distribution box and reapply input power.  
9. Close the Input circuit breaker located on the distribution box. The green AC INPUT lamp should illuminate on the  
front panel.  
10. Select Main Menu -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen, and select ‘TURN  
UPS ON’ to turn on the UPS.11. Close the Output circuit breaker on the rear of the power distribution box. The light  
by the input breaker will illuminate.  
12. Return the breaker to the Inverter position. The output terminal block will be powered at this time.  
13.Connect all loads for normal operation.  
8.3 Manual Battery Test  
To initiate a manual battery test,  
Select Main Menu -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen, and select ‘1 START’ to start  
manual battery test.  
while the UPS is operating from utility power with no alarm conditions present.  
8.4 Put Liebert® GXT4™ In Bypass  
Select Main Menu -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen, and select ‘TURN  
UPS BYPASS’ to transfer the UPS to bypass.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
         
28  
Chapter 8 Operation  
8.5 Shut Down Liebert GXT4  
Select Main Menu -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen, and select ‘TURN  
UPS OFF’ to turn off the UPS.  
8.6 Disconnecting Input Power From Liebert GXT4  
1. After the UPS has been shut down as detailed in 8.5 Shut Down Liebert GXT4, turn off the Output Circuit  
Breaker.  
2. Wait 30 seconds and verify that all indicators have turned Off and the fan has stopped; this indicates that the  
power-off is complete.  
3. Turn the external battery cabinet breaker switch to the Off position if the UPS has an external battery cabinet.  
After powering off the UPS, the UPS ceases output and the load is powered Off.  
8.7 Maintenance Bypass  
Maintenance Bypass Mode is used when maintenance or replacement is required. To place the unit in  
Maintenance Bypass:  
1. Place the UPS on internal bypass. This may be done by either of the following methods:  
a. Turn the UPS to internal bypass based on 8.4 Put the Liebert GXT4 Bypass  
b. Slide the bracket away from the manual bypass breaker on the rear of the UPS. This requires loosening the  
captive screw and sliding the bracket up and away from the Manual Bypass breaker.  
2. Move the Manual Bypass breaker on the rear of the UPS to the bypass position. This requires loosening the  
captive screw and sliding the bracket up and away from the Manual Bypass breaker.  
8.8 IT Power System Configuration  
1. Remove screws on the IT Power System Access Cover, as shown in Figure 8-1.  
Remove screws  
Remove screws  
10,000VA model  
5000VA and 6000VA models  
Figure 8-1 Removing cover from IT Power System Connectors compartment  
2. Disconnect the connectors, as shown in Figure 8-2.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
       
Chapter 8 Operation  
29  
IT power system connectors  
IT power system connectors  
10,000VA model  
5000VA and 6000VA models  
Figure 8-2 Disconnecting the connectors  
3. Install IT Power System Access Cover and screws.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
30  
Chapter 9 Communication  
Chapter 9 Communication  
This chapter introduces communication of the Liebert® GXT4™ UPS, including communication interface port,  
terminal block, Liebert IntelliSlot® communication cards and remote emergency power off.  
9.1 Communication Interface Port  
The Liebert® GXT4™ UPS has a terminal block on the rear of the UPS unit. Several signals are provided on this port  
and are assigned as follows.  
9.2 Terminal Block  
The terminal block includes eight pins, as shown in Figure 9-1.  
Figure 9-1 Terminal block communication pin layout  
9.2.1 Any-Mode Shutdown  
The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier, inverter and static  
switch so that there is no power to the loads.  
Any Mode Shutdown can be operated locally or remotely:  
Local Any Mode Shutdown can be performed by shorting the pins in Set 3.  
Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and mounted at a  
remote location.  
Activation of the Any Mode Shutdown will be logged as an event in the event history log.  
Note  
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown. The current limited source for the  
optocoupler (+12VDC, 50mA) will be available from UPS. The connection to UPS for remote connection will be via terminal  
block connector. Any Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.  
Warning  
When the Auto-enable output option is selected and the UPS output is disabled using the pins in Set 3, the Liebert GXT4’s output  
can turn On automatically and without warning if the connection of the pins in Set 3 is changed.  
9.2.2 Battery Mode Shutdown  
Battery Mode Shutdown permits shutting down the UPS by turning off the rectifier, inverter and static switch so that  
there is no power to the load when the UPS is On Battery. The auxiliary power for the UPS will still be active.  
Battery Mode Shutdown can be performed locally or remotely:  
Local Battery Mode shutdown can be performed by shorting the pins in Set 4.  
Remote Battery Mode Shutdown can be performed using a switch connected to the pins in Set 4 and mounted  
at remote location.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
         
Chapter 9 Communication  
Activation of the Battery Mode Shutdown will be logged as an event in the event history log.  
31  
Note  
1. Remote Power Off will be performed by NO contact.  
2. The current limited source for the optocoupler (+12VDC, 50mA) will be available from UPS. The connection to the Liebert®  
GXT4™ for remote connection will be via terminal block connector.  
3. Battery Mode Shutdown wiring must conform to all national, regional and local wiring codes and laws.  
4. This signal must last for 1.5 seconds or longer.  
5. A battery shutdown signal will not cause an immediate shutdown. It will start a 2-minute shutdown timer. This timer cannot be  
stopped once triggered. If the utility power returns during this countdown, the Liebert GXT4 will still shut down and must remain  
shut down for 10 seconds. Whether the UPS turns back On when the power is restored depends on the auto-restart setting.  
9.2.3 On Battery  
On Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery this  
dry contact will be closed.  
9.2.4 Low Battery  
Low Battery signal is a Normally Open (NO) dry contact. When the UPS is supplying output power from the battery  
and has reached the Low Battery Warning time selected in the configuration program, this dry contact will be closed.  
Note  
The rated values for the dry contacts for the On Battery and Low Battery signals are:  
Rated Voltage: 30V (AC or DC)  
Rated Current: 300mA  
9.3 Liebert IntelliSlot® Communication Cards  
The Liebert IntelliSlot port accepts three optional cards:  
Liebert IntelliSlot SNMP Card  
Liebert IntelliSlot Relay Card  
Liebert IntelliSlot 485 Card  
The Liebert IntelliSlot SNMP Card provides SNMP monitoring and control of the UPS across the network.  
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom-wired applications and delivers  
support for built-in shutdown for AS/400 systems.  
The Liebert IntelliSlot 485 Card is used to connect the UPS and computer system.  
Follow instructions provided with the Liebert IntelliSlot card to configure Liebert MultiLink®, the UPS or any additional  
ancillary product for the Liebert GXT4. These instructions are available at multilink.liebert.com  
9.3.1 Liebert® MultiLink®  
Liebert MultiLink monitors the UPS continuously and can shut down a computer or server in the event of an extended  
power failure.  
Liebert MultiLink can also be configured for use without the USB cable when the Liebert IntelliSlot®  
SNMP/Web card is installed in the UPS. Additionally, Liebert MultiLink can be configured to coordinate shutdown  
across the network with other computers running Liebert MultiLink when you purchase  
a Liebert MultiLink License Kit. For more information about the Liebert IntelliSlot SNMP/Web  
representative.  
Several option cards are available for use in the Liebert IntelliSlot port of the Liebert GXT4™. The  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
       
32  
Chapter 9 Communication  
Liebert IntelliSlot SNMP/Web Card provides SNMP and Web-based monitoring and control of the UPS across the  
network.  
The Liebert IntelliSlot MultiPort 4 Card allows installing Liebert MultiLink software on four computers and coordinate  
shutdown in the event of a power failure.  
The Liebert IntelliSlot Relay Card provides dry contact relay outputs for custom wired applications and delivers  
support for built-in shutdown for AS/400 systems.  
Caution  
To maintain safety (SELV) barriers and for electromagnetic compatibility, signal cables should be shielded and run separate from  
all other power cables, where applicable.  
9.4 Remote Emergency Power Off  
The UPS is equipped with a Remote Emergency Power Off (REPO) connector.  
The user must supply a means of interfacing with the REPO circuit to allow disconnecting the UPS input feeder  
breaker to remove all sources of power to the UPS and connected equipment to comply with national and local wiring  
codes and regulations.  
Figure 9-2 REPO switch connection diagram  
Caution  
To maintain safety (SELV) barriers and electromagnetic compatibility, signal cables should be shielded and run separately from  
power cables.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
Chapter 10 Maintenance  
33  
Chapter 10 Maintenance  
This section describes replacing the internal battery pack, battery charging, precautions, checking UPS status,  
checking UPS functions.  
10.1 Replacing Internal Battery Pack  
The Liebert GXT4™ is designed to allow the user to replace the internal battery pack safely. Read the safety cautions  
before proceeding. Contact your local dealer or Emerson representative to obtain the part number and pricing of the  
appropriate replacement battery pack.  
Battery replacement procedures  
1. Gently remove the front plastic bezel cover from the UPS.  
2. Loosen and remove the six screws on the battery door, as shown in Figure 10-1.  
3. Lay the battery door and screws aside for reassembly.  
Screws  
Battery door  
(6pcs)  
Front bezel  
Figure 10-1 Removing the front plastic bezel cover and battery door  
Note  
10,000VA model is shown in Figure 10-1; 5000VA / 6000VA model arrangement is the same except smaller.  
4. Gently pull the battery wires out and disconnect the battery plugs and battery receptacles, as shown in Figure 10-2.  
Battery receptacle  
Battery connector  
Battery receptacle  
Battery connector  
Figure 10-2 Disconnecting the battery plug and battery receptacle (front view)  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
   
34  
Chapter 10 Maintenance  
Note  
10,000VA model is shown in Figure 10-2; 5000VA / 6000VA model arrangement is the same except smaller.  
5. Grasp the battery handle and pull one of the internal battery packs out of the UPS, as shown in Figure 10-3.  
Repeat this step if both battery packs will be replaced. Each model has two battery packs.  
Internal  
battery pack  
Battery handle  
Pull out with  
battery handle  
5000VA & 6000VA models  
Internal  
battery pack  
Battery  
handle  
Pull out with  
battery handle  
10,000VA models  
Figure 10-3 Pulling out the battery packs  
6. Unpack a new internal battery pack. Take care not to destroy the packing.  
Compare the new and old internal battery packs to make sure they are the same type and model.  
If they are the same, proceed with Step 7; if they are different, stop and contact your local Emerson representative or  
Emerson Channel Support.  
7. Line up and slide in the new internal battery pack.  
8. Repeat Steps 6 and 7 if replacing both battery packs. Each model has two battery packs  
9. Reconnect the battery plugs and battery receptacles.  
10. Gently push the battery wire into the UPS battery compartment.  
11. Reattach the front battery door with the six screws.  
12. Reattach the front plastic bezel cover to the UPS.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
Chapter 10 Maintenance  
35  
Note  
The internal battery pack is hot-swappable. However, caution should be exercised because the load is unprotected from  
disturbances and power failures during this procedure. Do not replace the battery while the UPS is operating in Battery Mode.  
This will result in a loss of output power and will drop the connected load.  
10.2 Battery Charging  
The batteries are valve-regulated, nonspillable, lead acid and should be kept charged to attain their design life. The  
Liebert® GXT4™ charges the batteries continuously when it is connected to the utility input power.  
If the Liebert GXT4 will be stored for a long time, Emerson recommends connecting the UPS to input power for at  
least 24 hours every four to six months to ensure full recharge of the batteries.  
10.3 Precautions  
Although the Liebert GXT4 has been designed and manufactured to ensure personal safety, improper use can result  
in electrical shock or fire. To ensure safety, observe the following precautions:  
Turn Off and unplug the Liebert GXT4 before cleaning it.  
Wear rubber gloves and boots.  
Clean the UPS with a dry cloth. Do not use liquid or aerosol cleaners.  
Never block or insert any objects into the ventilation holes or other openings of the UPS.  
Do not place the Liebert GXT4 power cord where it might be damaged.  
10.4 Checking UPS Status  
Emerson recommends checking the UPS operation status every six months.  
Check whether the UPS is faulty: Is the Fault Indicator on? Is the UPS sounding an alarm?  
Check whether the UPS is operating in Bypass Mode. Normally, the UPS operates in Normal Mode. If it is  
operating in Bypass Mode, stop and contact your local Emerson representative, or Emerson Channel Support.  
Check whether the battery is discharging. When the utility input is normal, the battery should not discharge. If  
the UPS is operating in Battery Mode, stop and contact your local Emerson representative or Emerson Channel  
Support.  
10.5 Checking UPS Functions  
Note  
UPS function check procedures may interrupt power supply to the connected load.  
Emerson recommends checking the UPS functions once every six months.  
Back up the load data before conducting the UPS functions check. Procedures are as follows:  
1. Select Main Menu -> 3 CONTROL -> 1 TURN ON & OFF to enter the TURN ON & OFF screen, and select ‘TURN  
UPS BYPASS’ to transfer the UPS to bypass. Check whether the LCD display panel displays the warning normally.  
2. Select Main Menu -> 2 CONFIGURATION -> 3 OPERATION MODE to enter the OPERATION MODE screen (see  
Figure 3-11), and select ‘GREEN MODE ON’ or ‘GREEN MODE AUTO’ to control the UPS operation mode. Check  
whether the LCD display panel displays the mode normally.  
3. Select Main Menu -> 3 CONTROL -> 3 BATT TEST to enter the BATT TEST screen, and select ‘1 START’ to start  
manual battery test. Check whether the UPS can operate normally in Battery mode. If not, stop and contact your local  
Emerson representative or Emerson Channel Support.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
       
36  
Chapter 11 Specifications  
Chapter 11 Specifications  
Table 11-1 UPS specifications  
Product model  
GXT4-6000RT230  
GXT4-5000RT230  
GXT4-5000RT230E  
4000W/5000VA  
GXT4-10000RT230  
GXT4-10000RT230E  
9000W/10000VA  
Parameters  
GXT4-6000RT230E  
4800W/6000VA  
Dimensions, Rack Mount, W x D x H  
430 × 574 × 217 (16.9 × 22.4 × 8.5)  
Unit, mm (in)  
430 × 581 × 261 (16.9 × 22.9 × 10.3)  
530 × 745 × 563 (20.9 × 29.3 × 22.2)  
Shipping, mm (in)  
516 × 745 × 530 (20.3 × 29.3 × 20.9)  
Weight, kg (lb)  
Unit, kg (lb)  
60 (132.2)  
70 (154.3)  
Shipping, kg (lb)  
Input AC Parameters  
Nominal Operating  
Frequency  
50Hz or 60Hz (Factory Default is 50Hz)  
Factory Default VAC  
230Vac  
220/230/240Vac  
User Configurable VAC  
(May be modified using included configuration program)  
Operating Voltage Range  
Without Battery Operation  
Input Frequency w/o Battery  
Operation  
176Vac ~ 280Vac  
40Hz ~ 70Hz  
280Vac  
Maximum Allowable VAC  
PD2-CE10HDWRMBS Standard  
(See 3.3 Removable Power  
Distribution Box)  
PD2-CE6HDWRMBS Standard  
Input Power Connection  
(See 3.2 Removable Power Distribution Box)  
Output AC Parameters  
Factory Default VAC  
AC-AC Efficiency  
230Vac  
92% AC-AC  
PD2-CE10HDWRMBS Standard  
(See 3.2 Removable Power  
Distribution Box)  
PD2-CE6HDWRMBS Standard  
Output Connections  
(See 3.2 Removable Power Distribution Box)  
Frequency  
50Hz or 60Hz, Nominal  
Sinewave  
Waveform  
Main Mode Overload  
>200% for 5 cycles; 151 - 200% for 1 seconds; 131-150% 10 seconds; 105 - 130% 1 minute  
Internal Battery Charger  
Charger Current  
1.3  
2.6  
Battery Parameters  
Type  
Valve-regulated, non-spillable, lead acid  
20 × 12V  
Quantity × V  
9AH battery, CSB HR1234W  
or Panasonic UP-RW1245  
Battery Mfr. / Part #  
5AH battery, CSB HR1221W or YUASA NPH5-12  
See Table 11-5  
Backup Time  
Recharge Time (Internal  
Batteries)  
3 hr. to 90% capacity after full discharge into 100% load  
Bypass Protection Limits  
Disable Bypass Operation  
Re-Enable Bypass Operation  
Disable Bypass Operation  
If input voltage exceeds ±15% of the nominal voltage  
If input voltage returns to within ±10% of nominal output voltage  
When the input frequency prevents synchronous operation  
Environmental  
Operating Temp, °C (°F)  
Storage Temp, °C (°F)  
Relative Humidity  
0 to 40 (32 to 104)see Table 11-2  
-15 to 50 (5 to 122)  
0% to 95%, non-condensing  
Operating Elevation  
Up to 1000m (3281 ft) at 25°C (77°F) without derating  
Audible Noise less than <55 dBA, at 1 meter from the rear <50 dBA, at 1 meter from the front or sides  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 
Chapter 11 Specifications  
37  
Product model  
GXT4-6000RT230  
GXT4-5000RT230  
GXT4-5000RT230E  
4000W/5000VA  
GXT4-10000RT230  
GXT4-10000RT230E  
9000W/10000VA  
Parameters  
GXT4-6000RT230E  
4800W/6000VA  
Agency  
Safety  
IEC62040-1:2008 version, GS mark  
IEC/EN/AS 62040-2 2nd Ed (Cat 2 – Table 6)  
IEC/EN EN61000-4-2, Level 4, Criteria A  
IEC/EN EN61000-4-3, Level 3, Criteria A  
IEC/EN EN61000-4-4, Level 4, Criteria A  
IEC/EN EN61000-4-5, Level 3, Criteria A  
ISTA Procedure 1A&E  
EMI/EMC/C-Tick EMC  
ESD  
Radiated Susceptibility  
Electrical Fast Transient  
Surge Immunity  
Transportation  
Table 11-2 Operating temperature parameters  
Ambient Temperature, °C (°F)  
GXT4-5000/6000RT230  
GXT4-5000/6000RT230E  
GXT3-10000RT230  
pf @30°C ± 3°C (pf @ 86°F ± 5.4°F)  
0.8pf  
pf @40°C ± 3°C (pf @ 104°F ± 5.4°F)  
0.8pf  
0.9pf  
0.8pf  
GXT3-10000RT230E  
Table 11-3 Power distribution specifications  
Model Number  
PD2-CE6HDWRMBS  
32 Amps  
PD2-CE10HDWRMBS  
63 Amps  
Amp Rating  
Input Power Connection  
Output Power Connection  
Single-phase (L-N-G) hard-wired, 6mm2~ 10mm2 (8 ~ 10AWG)  
Single-phase (L-N-G) hard-wired, 6mm2 ~ 10mm2 (8 ~ 10AWG)  
Two IEC320 C19 16A/250V Sockets  
Four IEC320 C19 16A/250V Sockets,  
Four C13 10A/250V Sockets  
Includes:  
Six C13 10A/250V Sockets  
Manual Bypass Switch with Indicator Lamps  
Manual Bypass Switch with Indicator Lamps  
Input Branch Circuit  
32A  
63A  
Breaker, Supplied by User  
Table 11-4 External battery cabinet specifications  
Model Number  
Parameter  
GXT4-240VBATT  
GXT4-240VBATTE  
GXT4-5000RT230E  
GXT4-6000RT230E  
GXT4-10000RT230E  
GXT4-5000RT230  
GXT4-6000RT230  
GXT4-10000RT230  
Used UPS model  
Dimensions, Rack Mount, W × D × H, mm (in)  
Unit  
430 × 581 × 173 (16.9 × 22.9 × 6.8)  
530 × 745 × 475 (20.9 × 29.3 × 18.7)  
Weight, kg (lb)  
Shipping  
Unit  
65 (143.3)  
Shipping  
79.8 (175.6)  
76 (167.6)  
Battery Parameters  
Type  
Valve-regulated, non-spillable, lead acid  
20 × 12V × 9.0 AH  
Quantity × V × Rating  
Battery Mfr / Part #  
Backup Time  
CSB/HR12460  
See Table 11-5  
Environmental  
Operating Temp, °C (°F)  
Storage Temp, °C (°F)  
Relative Humidity  
0 to 40 (32 to 104);see Table 11-2  
-15 to 50 (5 to 122)  
0% to 95%, non-condensing  
Up to 1000m (3280.83 ft.) at 25°C (77°F)  
Agency  
Operating Elevation  
Safety  
IEC62040-1:2008 version  
ISTA Procedure 1E  
Transportation  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
38  
Chapter 11 Specifications  
Number of batteries  
Table 11-5 Battery run time  
230VAC RT Models  
Load  
5000VA  
96  
6000VA  
91  
10000VA  
104  
48  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
59  
50  
45  
35  
26  
31  
23  
18  
25  
18  
13  
Internal battery  
19  
14  
10  
14  
11  
7
13  
9
6
11  
8
4
9
7
4
337  
171  
121  
86  
309  
133  
93  
268  
112  
64  
67  
48  
70  
48  
35  
Internal battery + 1  
external battery cabinet  
52  
38  
27  
40  
30  
21  
35  
25  
17  
30  
22  
14  
25  
19  
13  
617  
337  
248  
164  
128  
99  
563  
276  
178  
120  
93  
423  
207  
110  
77  
Internal battery + 2  
57  
external battery cabinets  
73  
49  
75  
62  
40  
68  
53  
29  
63  
46  
25  
53  
39  
23  
842  
509  
344  
274  
216  
155  
120  
102  
93  
751  
364  
294  
201  
146  
113  
93  
576  
278  
167  
112  
83  
Internal battery + 3  
external battery cabinets  
66  
55  
77  
47  
67  
39  
77  
62  
35  
1208  
656  
486  
336  
291  
236  
173  
147  
132  
107  
1099  
540  
354  
279  
221  
159  
132  
106  
94  
668  
335  
232  
151  
113  
87  
Internal battery + 4  
external battery cabinets  
73  
58  
52  
85  
48  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
Chapter 11 Specifications  
39  
230VAC RT Models  
Number of batteries  
Load  
5000VA  
1427  
772  
605  
454  
336  
290  
239  
208  
179  
142  
1574  
1021  
685  
556  
443  
327  
283  
257  
233  
189  
6000VA  
1340  
649  
497  
326  
278  
228  
178  
142  
127  
111  
1500  
722  
593  
414  
317  
274  
232  
189  
158  
140  
10000VA  
905  
452  
275  
207  
140  
113  
89  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
10%  
20%  
30%  
40%  
50%  
60%  
70%  
80%  
90%  
100%  
Internal battery + 5  
external battery cabinets  
75  
61  
57  
1091  
535  
305  
247  
188  
137  
113  
88  
Internal battery + 6  
external battery cabinets  
77  
69  
Using the configuration program, the user may specify the number of external battery cabinets attached to the UPS.  
The factory default is programmed for internal batteries only.  
Table 11-5 shows the estimated run times at different loads.  
Auto-Learning Battery Run Times  
As batteries age, the estimated runtimes may become less accurate. The Liebert® GXT4 is programmed to “learn”  
from a full battery discharge and modify the estimated run time for the measured battery capacity. This can improve  
accuracy and compensate for aging batteries or batteries that operate at different ambient temperatures.  
The UPS will update the anticipated run time calculation only under certain conditions.  
The UPS must have a steady load that is greater than 20%.  
The UPS must be at 100% charge at the start of a battery discharge.  
The battery discharge must continue uninterrupted until the batteries reach their end-of-discharge voltage.  
If all conditions are not met, the run time calculation will not be modified.  
If the configuration program is used to change the number of battery cabinets, then the values in Table 11-5 will be  
restored. This will override any value that is Auto-Learned.  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
40  
Chapter 12 Product Warranty Registration  
Chapter 12 Product Warranty Registration  
To register for warranty protection, visit the Quick Links section of the Liebert Web site at:  
Click on Product Warranty Registration and fill in the form.  
If you have any questions, contact Emerson Channel Support at:  
North America: 800-222-5877  
Outside North America: 00-800-1155-4499  
Liebert GXT4 UPS 5000VA ~ 10000VA (230V) User Manual  
 

Savin 2535p User Manual
Samsung Us12a5 A6 Mc User Manual
Samsung Sh24ts6 User Manual
Samsung Avmwc040ca0 User Manual
Quasar Hq2201gh User Manual
NEC MULTISYNC P754Q User Manual
LG K30 LM X410TK User Manual
Lexmark X34x User Manual
JVC AV 28T4BK User Manual
CREE CS18 User Manual