246646-YTG-C-0606  
TECHNICAL  
GUIDE  
®
DESCRIPTION  
ASHRAE 90.1 COMPLIANT  
®
®
YORK Predator units are convertible single packages with a  
common footprint cabinet and common roof curb for all 6-1/2  
through 12-1/2 ton models. All units have two compressors with  
independent refrigeration circuits to provide 2 stages of cooling.  
The units were designed for light commercial applications and  
can be easily installed on a roof curb, slab, or frame.  
HIGH EFFICIENCY  
SINGLE PACKAGE AIR CONDITIONERS AND  
SINGLE PACKAGE GAS/ELECTRIC UNITS  
®
All Predator units are self-contained and assembled on rigid  
full perimeter base rails allowing for 3-way forklift access and  
overhead rigging. Every unit is completely charged, wired,  
piped, and tested at the factory to provide a quick and easy field  
installation.  
DH 078, 090, 102, 120 and 150  
6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 NOMINAL TONS  
10.0-11.5 EER  
All units are convertible between side and down airflow. Inde-  
pendent economizer designs are used on side and down dis-  
charge applications, as well as all tonnage sizes.  
®
Predator units are available in the following configurations:  
cooling only, cooling with electric heat, and cooling with gas  
heat. Electric heaters are available as factory-installed options  
or field-installed accessories.  
Tested in accordance with:  
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE  
246646-YTG-C-0606  
6LPSOLFLW\Šꢈ&RQWURO  
'LVFRQQHFW ORFDW LRQ  
RSWLRQDO GLVFRQQHFW VZLWFKꢂ  
%RDUGꢈZꢇVFUHZ  
FRQQHFWRUꢈIRUꢈ7ꢀVWDW  
ZLULQJꢈDQGꢈQHWZRUN  
FRQQHFWLRQV  
)LOWHUꢈDFFHVV  
ꢁꢄꢋꢈWKURZꢀDZD\ꢂ  
)LOWHUꢈGULHUꢈ  
ꢁVROLGꢈFRUHꢂ  
7HUPLQDO EORFN I RU  
KLꢀYROWDJH FRQQHFWLRQ  
&RQGHQVHU VHFWLRQ  
6HFRQG PRGHO  
QDPHSODWH  
LQVLGH KLQJHG  
DFFHVV SDQHO  
6OLGHꢀRXW PRWRU DQG  
EORZHU DVVHPEO\ IRU  
HDV\ DGMXVWPHQW DQG  
VHUYLFH  
%HOWꢀGULYH  
EORZHUꢈPRWRU  
'XDOꢈVWDJHꢈFRROLQJ  
IRUꢈPD[LPXPꢈ  
FRPIRUW  
3RZHU YHQWRU PRWRU  
&RPSUHVVRU ꢆꢄ  
JDXJH DOXPLQL]HG  
VWHHO WXEXODU KHDW  
H[FKDQJHU IRU ORQJ OLIH  
ꢁVWDLQOHVV VWHHO RSWLRQꢂ  
DFFHVV ꢁKLJKꢀHIILꢀ  
FLHQF\ FRPSUHVVRU  
ZꢇFUDQNFDVH KHDWHUꢂ  
%DVHꢈUDLOVꢈZꢇIRUNOLIW  
7ZRꢀVWDJH JDV  
KHDWLQJ WR PDLQWDLQ  
ZDUPꢃ FRPIRUWDEOH  
WHPSHUDWXUH  
6OLGHꢀRXWꢈGUDLQꢈSDQ  
ZLWKꢈVWHHOꢈꢉꢇꢊꢋꢈ137ꢃ  
)HPDOHꢈFRQQHFWLRQ  
VORWVꢈꢁꢉꢈVLGHVꢂꢈDQG  
OLIWLQJꢈKROHV  
5RRIꢈFXUEVꢈLQꢈHLJKWꢈDQG  
&RPSUHVVRUꢈꢆꢌꢈDFFHVV  
ꢁKLJKꢀHIILFLHQF\ꢈFRPSUHVVRU  
ZꢇFUDQNFDVHꢈKHDWHUꢂ  
IRXUWHHQꢈLQFKꢈKHLJKWVꢍꢈ  
5RRIꢈFXUEVꢈIRUꢈ  
,QWHOOLJHQW  
FRQWUROꢈERDUG  
IRUꢈVDIHꢈDQG  
HIILFLHQW  
6LGHꢈHQWU\ꢈSRZHU  
7RROꢀOHVVꢈ  
GRRUꢈODWFK  
DQGꢈFRQWUROꢈZLULQJ  
NQRFNRXWV  
WUDQVLWLRQLQJꢈIURPꢈ  
<RUNꢈ6XQOLQHŒꢈIRRWSULQW  
WRꢈWKHꢈ')ꢈ6HULHVꢈIRRWSULQWV  
DUHꢈDOVRꢈDYDLODEOH  
RSHUDWLRQ  
ꢁILHOGꢀLQVWDOOHGꢈDFFHVVRU\ꢂ  
®
FIGURE 1 - PREDATOR COMPONENT LOCATION (DH120 SHOWN)  
FEATURES  
High Efficiency – High efficiency units reach as high as  
11.5 EER. Gas/electric units have electronic spark igni-  
tion and power vented combustion with steady state effi-  
ciencies of 80%. These efficiencies exceed all legislated  
minimum levels and provide low operating costs.  
Service windows have been placed in both condenser  
section walls. Rotation of the cover allows easy access  
to the condenser coils for cleaning or inspection.  
Both the unit control board and ignition control board uti-  
lize flash codes to aid in diagnosis of unit malfunctions.  
Unique alarm codes quickly identify the source of the  
unit alarm.  
®
Service Friendly – The Predator incorporates a num-  
ber of enhancements which improve serviceability.  
All units use the same standard filter size. This standard-  
ization removes any confusion on which filter sizes are  
needed for replacement.  
The motor and blower slide out of the unit as a common  
assembly. This facilitates greater access to all the indoor  
airflow components, thus simplifying maintenance and  
adjustment.  
The non-corrosive drain pan slides out of the unit to per-  
mit easy cleaning. The drain pan is accessed by remov-  
ing the drain pan cover plate on the rear of the unit. Once  
the plate is removed, the drain pan slides out through the  
rear of the unit.  
Service time is reduced through the use of hinged,  
toolless panels. Such panels provide access to  
frequently inspected components and areas, including  
the control box, compressors, filters, indoor motor &  
blower, and the heating section. The panels are screwed  
in place at the factory to prevent access by children or  
other unauthorized persons. It is recommended that the  
panels be secured with screws once service is complete.  
®
All Predator units have a second model nameplate  
located inside the control access door. This is to prevent  
deterioration of the nameplate through weathering.  
Unitary Products Group  
3
246646-YTG-C-0606  
Environmentally Aware – For improved Indoor Air  
Quality, foil faced insulation is used exclusively through-  
out the units.  
low-pressure switches and the freezestats must trip  
three times within two hours before the unit control  
board will lock out the associated compressor.  
®
Balanced Heating – The Predator offers “Ultimate Heat-  
On Board Diagnostics - Each alarm will energize a  
trouble light on the thermostat, if so equipped, and  
flash an alarm code on the control board LED. Each  
high and low-pressure switch alarm as well as each  
freezestat alarm has its own flash code. The control  
board saves the five most recent alarms in memory,  
and these alarms can be reviewed at any time.  
Alarms and programmed values are retained  
through the loss of power.  
st  
nd  
ing Comfort” with a balance between 1 and 2 stage  
®
gas heating. The first stage of a gas heat Predator unit  
provides 60% of the heating capacity. Balanced heating  
allows the unit to better maintain desired temperatures.  
Convertible Airflow Design – The side duct openings  
are covered when they leave the factory. If a side supply/  
return is desired, the installer simply removes the two  
side duct covers from the outside of the unit and installs  
them over the down shot openings. No panel cutting is  
required. Convertible airflow design allows maximum  
field flexibility and minimum inventory.  
Reliable – From the beginning – All units undergo com-  
puter automated testing before they leave the factory.  
Units are tested for refrigerant charge and pressure, unit  
amperage, and 100% functionality. For the long term –  
System Protection - Suction line freezestats are supplied  
on all units to protect against loss of charge and coil frost-  
ing when the economizer operates at low outdoor air tem-  
peratures while the compressors are running. Every unit  
has solid-core liquid line filter-driers and high and low-  
pressure switches. Internal compressor protection is stan-  
dard on all compressors. Crankcase heaters are standard  
on reciprocating compressors. Scroll compressors do not  
require crankcase heaters. Phase Monitors are standard  
on units with scroll compressors. This accessory monitors  
the incoming power to the unit and protects the unit from  
phase loss and reversed phase rotation.  
®
All Predator units are painted with a long lasting, pow-  
der paint that stands up over the life of the unit. The paint  
used has been proven by a 1000 hour salt spray test.  
Flexible Placement – All models and configurations  
share the same cabinet/footprint and thus the same roof  
curb. You have the flexibility to set one curb and choose  
the correct tonnage size and heating option after the  
internal loads have been determined.  
®
To further simplify planning and installation, Predator  
cabinets are designed to fit your roof. With the optional  
roof curb, the unit ductwork is designed to fit around 24”  
on-center joists or between 48” on-center joists.  
Advanced Controls - S implicity™ control boards have  
standardized a number of features previously available  
only as options or by utilizing additional controls.  
The drain pan can be rotated to drain to either the front  
or the rear of the unit. Additionally, the drain pan can be  
fitted to drain through the roof curb. As it is sometimes  
difficult to have a level installation, the drain pan features  
a generous slope to ensure proper drainage.  
Low Ambient - An integrated low-ambient control  
allows all units to operate in the cooling mode down  
to 0°F outdoor ambient without additional assistance.  
Optionally, the control board can be programmed to  
lockout the compressors when the outdoor air tem-  
perature is low or when free cooling is available.  
Full Perimeter Base Rails – The permanently attached  
base rails provide a solid foundation for the entire unit and  
protect the unit during shipment. The rails offer forklift  
access from 3 sides, and rigging holes are available so that  
an overhead crane can be used to place the units on a roof.  
Anti-Short Cycle Protection - To aid compressor  
life, an anti-short cycle delay is incorporated into the  
standard controls. Compressor reliability is further  
ensured by programmable minimum run times. For  
testing, the anti-short cycle delay can be temporarily  
overridden with the push of a button.  
Easy Installation – Gas and electric utility knockouts are  
supplied in the unit underside as well as the side of the unit.  
A clearly identified location is provided to mount a field sup-  
plied electrical disconnect switch. Utility connections can be  
made quickly and with a minimum amount of field labor.  
Fan Delays - Fan on and fan off delays are fully pro-  
grammable. Furthermore, the heating and cooling  
fan delay times are independent of one another. All  
units are programmed with default values based  
upon their configuration of cooling and heat.  
All units are shipped with 2” throw-away filters installed.  
Wide Range of Indoor Airflows – All indoor fan motors  
are belt-drive type providing maximum flexibility to han-  
dle most airflow requirements. For high static applica-  
tions, factory installed alternate indoor fan motors are  
available. With the optional indoor fan motor, all units can  
supply nominal airflow at a minimum of 1.5” ESP.  
Safety Monitoring - The control board monitors the  
high and low-pressure switches, the freezestats, the  
gas valve, if applicable, and the temperature limit  
switch on gas and electric heat units. The unit con-  
trol board will alarm on ignition failures, compressor  
lockouts and repeated limit switch trips.  
Warranty - All models include a 1-year limited warranty  
on the complete unit. Compressors and electric heater  
elements each carry a 5-year warranty. Aluminized steel  
and stainless steel tubular heat exchangers carry a 10-  
year warranty.  
Nuisance Trip Protection and Strikes - To prevent  
nuisance trouble calls, the control board uses a  
“three times, you’re out” philosophy. The high and  
4
Unitary Products Group  
246646-YTG-C-0606  
input, the economizer control monitors outdoor air. The  
dual enthalpy kit provides a second input used to mon-  
itor the return air. With a dual input kit installed, the  
economizer control compares the values of the two  
enthalpy or temperature inputs and positions the  
dampers to provide the maximum efficiency possible.  
FACTORY INSTALLED OPTIONS  
®
YORK offers several equipment options factory installed, for  
®
the Predator line.  
Optional Factory Installed Economizers - Predator units  
offer a variety of optional factory installed economizers with  
low leak dampers. The outdoor air enthalpy sensor enables  
economizer operation if the outdoor enthalpy is less than  
the setpoint of the economizer logic module. See Table 41  
to determine the correct economizer for your application.  
Power Exhaust (Downflow only) - This accessory  
installs in the unit with a down flow economizer.  
Motorized Outdoor Air Damper - The motorized out-  
door air damper includes a slide-in/plug-in damper  
assembly with an outdoor air hood and filters. The out-  
door air dampers open to the preset position when the  
indoor fan motor is energized. The damper has a range  
of 0% to 100% outdoor air entry. Factory installed option  
or field installed accessory.  
Downflow Economizer - (With barometric relief) -  
The economizer is provided with a single enthalpy  
input. The economizer is 2% low leakage type, and is  
shipped installed and wired. The installer needs only  
to assemble and mount the outdoor air hood (Pro-  
vided). The economizer has spring return, fully modu-  
lating damper actuators and is capable of introducing  
up to 100% outdoor air. As the outdoor air intake  
dampers open, the return air dampers close. The  
changeover from mechanical refrigeration to econo-  
mizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry  
bulb available. To meet regulated air standards, the  
Alternate Indoor Blower Motor - For applications with  
high static restrictions, units are offered with optional  
indoor motors that provide higher static output and/or  
higher airflow, depending upon the installer’s needs.  
Aluminized Steel Gas Heat Exchanger - For applica-  
tions in non-corrosive environments.  
Stainless Steel Gas Heat Exchanger - For applications  
in corrosive environments, this option provides a full  
stainless steel heat exchanger assembly.  
economizer control accepts an optional CO input for  
2
demand ventilation. With single enthalpy input, the  
economizer control monitors outdoor air. The dual  
enthalpy kit provides a second input used to monitor  
the return air. With a dual input kit installed, the econ-  
omizer control compares the values of the two  
enthalpy or temperature inputs and positions the  
dampers to provide the maximum efficiency possible.  
Stainless Steel Drain Pan - An optional rust-proof stain-  
less steel drain pan is available to provide years of trou-  
ble-free operation in corrosive environments.  
Electric Heaters - The electric heaters range from 9kW  
to 54kW and are available in all the voltage options of the  
base units. All heaters are dual staged. All heaters are  
intended for single point power supply.  
Horizontal Economizer - (Without barometric  
relief) - All features of the downflow economizer  
exist except you must order the duct mount baro-  
metric relief separately. You must order a 1EH0408  
if you are installing a power exhaust. You can  
order a 1RD0411 Barometric Relief for horizontal  
flow economizers only.  
Disconnect Switch - For gas heat units and cooling  
units with electric heat, a HACR breaker sized to the unit  
is provided. For cooling only units, a switch sized to the  
largest electric heat available for the particular unit is  
provided. Factory installed option only.  
Convenience Outlet - (Non-Powered/Powered) - This  
option locates a 120V single-phase GFCI outlet with  
cover, on the corner of the unit housing adjacent to the  
compressors. The “Non-powered” option requires the  
installer to provide the 120V single-phase power source  
and wiring. The “Powered” option is powered by a step-  
down transformer in the unit. Factory installed option only.  
BAS Ready Economizer -(With barometric relief) -  
The economizer is provided with a Belimo actuator  
that requires a 0-10V DC input from an external  
source (i.e., field installed building automation system  
controller). Power exhaust options are available. The  
economizer is 2% low leakage type with spring return  
and fully modulating dampers capable of introducing  
up to 100% outside air. Also include 2” pleated filters.  
Smoke Detectors - The smoke detectors stop operation  
of the unit by interrupting power to the control board if  
smoke is detected within the air compartment. Available  
for both the supply and/or return air.  
Slab Economizer for Energy Recovery Ventilators-  
(With barometric relief and Fresh Air Hood) - The  
economizer is provided with a single enthalpy input.  
The economizer is 2% low leakage type, and is  
shipped installed and wired. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the  
outdoor air intake dampers open, the return air damp-  
ers close. The changeover from mechanical refrigera-  
tion to economizer operation is regulated by the  
standard single enthalpy input. There is an optional  
input dual dry bulb available. To meet regulated air  
standards, the economizer control accepts an optional  
Factory installed smoke detectors in the return air,  
may be subjected to freezing temperatures during  
"off" times due to out side air infiltration. These  
smoke detectors have an operational limit of 32 °F  
to 131°F. Smoke detectors installed in areas that  
could be out side those limitations will have to be  
moved to prevent having false alarms.  
CO input for demand ventilation.With single enthalpy  
2
Unitary Products Group  
5
246646-YTG-C-0606  
Phase Monitors - Designed to prevent unit damage. The  
phase monitor will shut the unit down in an out-of phase  
condition. (Standard on units with Scroll Compressors.)  
supply air sensor, return air sensor, dirty filter indicator  
switch, and air proving switch.  
Johnson Controls BAS Control - The Johnson Control  
YK-UNT-1126 building automation system controller is  
factory installed. Includes supply air sensor, return air  
sensor, dirty filter indicator switch, and air proving switch.  
Coil Guard - Customers can purchase a coil guard kit to  
protect the condenser coil from damage. Additionally,  
this kit stops animals and foreign objects from entering  
the space between the inner condenser coil and the  
main cabinet. This is not a hail guard kit.  
CPC BAS Control - The Computer Process Controls  
Model 810-3060 ARTC Advanced Rooftop building auto-  
mation system controller is factory installed. Includes  
supply air sensor, return air sensor, dirty filter indicator  
switch and air proving switch.  
Dirty Filter Switch - This kit includes a differential pres-  
sure switch that energizes the fault light on the unit ther-  
mostat, indicating that there is an abnormally high  
pressure drop across the filters. Factory installed option  
or field installed accessory.  
Honeywell BAS Control - The Honeywell W7750C  
building automation system controller is factory installed.  
Includes air supply sensor, return air sensor, dirty filter  
indicator switch, and air proving switch.  
Technicoat Condenser Coils - The condenser coils are  
coated with a phenolic coating for protection against cor-  
rosion due to harsh environments.  
FIELD INSTALLED ACCESSORIES  
Technicoat Evaporator Coil - The evaporator coils are  
coated with a phenolic coating for protection against cor-  
rosion due to harsh environments.  
®
YORK offers several equipment accessories for field instal-  
®
lation, for the Predator line.  
Downflow Economizer - (With barometric relief) - The  
economizer is provided with a single enthalpy input. The  
economizer is 2% low leakage type. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the  
outdoor air intake dampers open, the return air dampers  
close. The changeover from mechanical refrigeration to  
economizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry bulb  
available. To meet regulated air standards, the econo-  
BAS - Building Automation System Controls S implic-  
ity™ INTELLI-Comfort™ Control - The York® S implic-  
ity™ INTELLI-Comfort™ control is factory installed. It  
includes a supply air sensor, a return air sensor, and an  
outside air sensor. There are provisions for a field  
installed dirty filter indicator switch, an air-proving switch,  
an Outside Air Humidity sensor, a Return Air Humidity  
sensor, an Inside IAQ sensor, and an Outside Air IAQ  
sensor. Construction mode operation, 365-day real time  
clock with 7 day programming plus holiday scheduling is  
built-in. Two different modes of demand ventilation are  
mizer control accepts an optional CO input for demand  
2
achieved through the INTELLI-Comfort™ using CO  
ventilation. With single enthalpy input, the economizer  
control monitors outdoor air. The dual enthalpy kit pro-  
vides a second input used to monitor the return air. With  
a dual input kit installed, the economizer control com-  
pares the values of the two enthalpy or temperature  
inputs and positions the dampers to provide the maxi-  
mum efficiency possible  
2
sensors. It uses an inside CO sensor to perform  
2
Demand Ventilation. It can also use an Outside CO sen-  
2
sor to perform Differential Demand Ventilation. It uses a  
Patented Comfort Ventilation algorithm to provide com-  
fortable ventilation air temperature. The patented econo-  
mizer-loading algorithm will protect the equipment when  
harsh operating conditions exist. Humidity in the occu-  
pied space or return duct can be monitored and con-  
trolled via humidity sensors and the on-board connection  
for hot gas re-heat system. It uses the INTELLI-Start™  
algorithm to maximize energy savings by recovering the  
building from the Unoccupied Setpoints to the Occupied  
Setpoints just in time for the Occupied Time Period to  
begin. The S implicity™ INTELLI-Comfort™ balances  
Horizontal Economizer - (Without barometric relief) -  
All features of the downflow economizer exist except you  
must order the duct mount barometric relief separately.  
You must order a 1EH0408 if you are installing a  
power exhaust. You can order a 1RD0411 Barometric  
Relief for horizontal flow economizer.  
Slab Economizer for Energy Recovery Ventilator-  
(Without barometric relief or Fresh Air Hood) - The  
economizer is provided with a single enthalpy input. The  
economizer is 2% low leakage type. The economizer has  
spring return, fully modulating damper actuators and is  
capable of introducing up to 100% outdoor air. As the  
outdoor air intake dampers open, the return air dampers  
close. The changeover from mechanical refrigeration to  
economizer operation is regulated by the standard single  
enthalpy input. There is an optional input dual dry bulb  
available. To meet regulated air standards, the econo-  
space temperature, ventilation air temperature, CO and  
2
humidity for ultimate comfort.  
S implicity™ INTELLI-Comfort™ with ModLINC  
Control - The York® S implicity™ INTELLI-Comfort™  
with ModLINC control is factory installed. It includes all  
the features of the INTELLI-Comfort™ control with an  
additional control to translate communications from  
MODBUS to the BACnet MSTP protocol.  
Novar® BAS Control - The Novar® ETC-3 building  
automation system controller is factory installed. Incudes  
mizer control accepts an optional CO input for demand  
2
6
Unitary Products Group  
246646-YTG-C-0606  
ventilation.With single enthalpy input, the economizer  
control monitors outdoor air. The dual enthalpy kit pro-  
vides a second input used to monitor the return air. With  
a dual input kit installed, the economizer control com-  
pares the values of the two enthalpy or temperature  
inputs and positions the dampers to provide the maxi-  
mum efficiency possible.  
-60°F Gas Heat Kit - For installations which require gas  
heat units to perform in low ambient temperatures, a gas  
section heating kit is available. This kit provides electric  
heat in the gas heat controls section to ensure the gas  
valve and controls will continue to function properly at  
extremely low temperatures.  
Gas Heat High Altitude Kit - This kit converts a gas  
heat unit to operate at high altitudes, 2,000 to 6,000 feet.  
Conversion kits are available for natural gas and pro-  
pane.  
You can order 1EH0409 Barometric Relief/FA Hood  
for field installations without an ERV.  
Dual Enthalpy Control, Accessory - This kit contains  
the required components to convert a single enthalpy  
economizer to dual enthalpy.  
Gas Heat Propane Conversion Kit - This kit converts a  
gas-fired heater from natural gas to propane. It contains  
the main burner orifices and gas valve replacement  
springs.  
Barometric Relief Damper - Zero to 100% capacity  
barometric relief dampers for use with horizontal flow, or  
field installed slab economizers.  
Gas Piping Kit - Contains pipe nipples, fittings and gas  
cock required for gas supply connection with external  
shut off.  
Power Exhaust - This accessory installs in the unit with  
a down flow economizer. Power exhaust plugs into the  
connector in the unit bulkhead. You must purchase  
1EH0408 barometric relief when applying to a hori-  
zontal flow application.  
Electric Heaters - The electric heaters range from 9 kW  
to 54kW and are available in all the voltage options of the  
base units. All heaters are dual staged. Cooling units  
include an adapter panel for easy installation of the elec-  
tric heaters. Necessary hardware and connectors are  
included with the heaters. All heaters are intended for  
single point power supply.  
Manual Outdoor Air Damper - Like the motorized out-  
door air damper, each manual outdoor air damper  
includes a slide-in damper assembly with an outdoor air  
hood and filters. Customers have a choice of dampers  
with ranges of 0% to 100% or 0% to 35% outdoor air  
entry.  
Low Limit / Compressor Lockout Kit  
1. Compressor Lockout (CLO): To prevent mechani-  
cal (compressorized) operation of the unit during  
cold outdoor conditions where there is a risk of  
returning liquid refrigerant back to the compressors.  
Motorized Outdoor Air Damper - The motorized out-  
door air damper includes a slide-in/plug-in damper  
assembly with an outdoor air hood and filters. The out-  
door air dampers open to the preset position when the  
indoor fan motor is energized. The damper has a range  
of 0% to 100% outdoor air entry. Factory installed option  
or field installed accessory.  
2. Low Limit Control (LLC): To prevent the supply air  
from dropping below a specified setpoint by utilizing  
the units first stage heating means when there is a  
demand for cooling during cold outside conditions.  
Smoke Detectors - The smoke detectors stop operation  
of the unit by interrupting power to the control board if  
smoke is detected within the air compartment.  
Metal Frame Filter Kit - Metal frame with polyester filter  
medium.  
Permanent Filters - Permanent filters are available.  
CO Sensor - Senses CO levels and automatically  
2
2
Roof Curbs - The roof curbs have insulated decks and  
are shipped disassembled The roof curbs are available  
in 8” and 14” heights. For applications with security con-  
cerns, burglar bars are available for the duct openings of  
the roof curbs.  
overrides the economizer when levels rise above the  
preset limits.  
Dirty Filter Switch - This kit includes a differential pres-  
sure switch that energizes the fault light on the unit ther-  
mostat, indicating that there is an abnormally high  
pressure drop across the filters.  
Roof Curb Transition - Single Piece Adapter (10” High)  
- Roof curbs for transitioning from Sunline™ units to  
®
Coil Guard - Field installed decorative wire coil guard.  
Predator units. Fits 7.5 to 12.5 Sunline™ roof curbs  
only.  
Hail Guard - This kit includes a sloped hood which  
installs over the outside condenser coil and prevents  
damage to the coil fins from hail strikes. Field installed  
accessory only.  
Burglar Bars - Mount in the supply and return openings  
to prevent entry into the duct work.  
Thermostat - The units are designed to operate with 24-  
volt electronic and electro-mechanical thermostats. All  
units (with or without an economizer) operate with two-  
stage heat/two-stage cool or two-stage cooling only ther-  
mostats, depending upon unit configuration.  
Flue Exhaust Extension Kit - In locations with wind or  
weather conditions which may interfere with proper  
exhausting of furnace combustion products, this kit can  
be installed to prevent the flue exhaust from entering  
nearby fresh air intakes.  
Unitary Products Group  
7
246646-YTG-C-0606  
TABLE 1: ACCESSORIES  
Part Number  
Description  
Weight  
1RC0470  
Roof Curb, 8" Height  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1RC0471  
Roof Curb, 14" Height  
1RC0472  
Roof Curb, Transition (7.5 T through 12.5 T)  
Burglar Bars, Downflow  
1BD0408  
2TP04520925  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
2TP04520946  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
2TP04520958  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
1FA0411  
Electric Heat 9kW 230V  
Electric Heat 18kW 230V  
Electric Heat 24kW 230V  
Electric Heat 36kW 230V  
Electric Heat 54kW 230V  
Electric Heat 9kW 460V  
Electric Heat 18kW 460V  
Electric Heat 24kW 460V  
Electric Heat 36kW 460V  
Electric Heat 54kW 460V  
Electric Heat 9kW 575V  
Electric Heat 18kW 575V  
Electric Heat 24kW 575V  
Electric Heat 36kW 575V  
Electric Heat 54kW 575V  
Electric Heat 9kW 230V, 42" Tall Cabinet  
Electric Heat 18kW 230V, 42" Tall Cabinet  
Electric Heat 24kW 230V, 42" Tall Cabinet  
Electric Heat 36kW 230V, 42" Tall Cabinet  
Electric Heat 9kW 460V, 42" Tall Cabinet  
Electric Heat 18kW 460V, 42" Tall Cabinet  
Electric Heat 24kW 460V, 42" Tall Cabinet  
Electric Heat 36kW 460V, 42" Tall Cabinet  
Electric Heat 9kW 575V, 42" Tall Cabinet  
Electric Heat 18kW 575V, 42" Tall Cabinet  
Electric Heat 24kW 575V, 42" Tall Cabinet  
Electric Heat 36kW 575V, 42" Tall Cabinet  
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)  
1FA0412  
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)  
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)  
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)  
Economizer, Downflow (Incl. Barometric Relief & All Hoods)  
-
-
2MD04702724  
2MD04703324  
2EE04705424  
2EE04705524  
2EE04705224  
2EE04705624  
2PE04703225  
2PE04703246  
2PE04703258  
2EC04700924  
1EH0407  
124 lbs.  
97 lbs.  
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)  
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)  
"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet  
Power Exhaust, Downflow, 230V (For Units with Economizer only)  
Power Exhaust, Downflow, 460V(For Units with Economizer only)  
Power Exhaust, Downflow, 580V (For Units with Economizer only)  
Dual Enthalpy Control (Use with Single Enthalpy Economizer)  
-
-
-
-
-
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)  
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)  
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)  
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)  
CO2 Detector Unit Mount  
1RD0411  
1EH0408  
25 lbs.  
1EH0409  
-
-
-
-
2AQ04700424  
2AQ04700324  
2SD04700424  
2MK04700624  
1CG0419  
CO2 Detector Space Mount  
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)  
Low Limit / Compressor Lockout Kit  
Coil Guard (Electric / Electric & HP models)  
-
8
Unitary Products Group  
246646-YTG-C-0606  
TABLE 1: ACCESSORIES (CONTINUED)  
Part Number  
Description  
Weight  
1CG0420  
1CG0427  
1CG0428  
1HG0411  
1HG0415  
1GP0405  
1NP0442  
1HA0442  
1HA0443  
1FE0412  
Coil Guard (Gas / Electric models)  
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Coil Guard (Electric / Electric & HP Models), 42" Tall Cabinet  
Coil Guard (Gas / Electric Models), 42" Tall Cabinet  
Hail Guard Kit  
Hail Guard Kit, 42" Tall Cabinet  
Gas Piping Kit  
Propane Conversion Kit  
High Altitude Kit for Natural Gas  
High Altitude Kit for Propane  
Flue Exhaust Extension Kit  
2BC04700106  
2BC04700151  
2BC04700154  
1FL0402  
Gas Heat Kit, -60 deg F, 230V  
Gas Heat Kit, -60 deg F, 460V  
Gas Heat Kit, -60 deg F, 575V  
Permanent Filter Kit  
1FL0423  
Permanent Filter Kit, 42" Tall Cabinet  
Dirty Filter Switch  
2DF0401  
1FF0410  
Filter Frame Kit, Metal  
1FF0411  
Metal Filter Frame Kit, 42" Tall Cabinet  
Unitary Products Group  
9
246646-YTG-C-0606  
NOMENCLATURE  
®
6.5-12.5 Ton York Model Number Nomenclature  
D H 090 N10 A 2 A AA 3 0 1 2 4 A  
Product Category  
Product Style  
D = A/C, Single Pkg., R-22  
A = Style A  
B = Style B  
C = Style C  
Product Identifier  
Configuration Options (not required for all units)  
These four digits will not be assigned until a quote is requested, or an order placed.  
H = 11.0+ EER A/C  
SS Drain Pan  
CPC Controller, DFS, APS  
Nominal Cooling Capacity  
Johnson Controller, DFS, APS  
Honeywell Controller, DFS, APS  
Novar Controller, DFS, APS  
078 = 6.5 Ton  
090 = 7.5 Ton  
102 = 8.5 Ton  
120 = 10.0 Ton  
150 = 12.5 Ton  
Simplicity IntelliComfort Controller  
Simplicity IntelliComfort Controller w/ModLinc  
2" Pleated filters  
BAS Ready Unit with Belimo Economizer  
Shipping Bag  
Heat Type and Nominal Heat Capacity  
C00 = Cooling Only. No heat installed  
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned  
Gas Heat Options  
Product Generation  
N10 = 100 MBH Output Aluminized Steel  
N15 = 150 MBH Output Aluminized Steel  
N20 = 200 MBH Output Aluminized Steel  
S10 = 100 MBH Output Stainless Steel  
S15 = 150 MBH Output Stainless Steel  
S20 = 200 MBH Output Stainless Steel  
3 = Third Generation  
4 = Fourth Generation  
5 = Fifth Generation  
Additional Options  
RC = Coil Guard, Shipping Bag & American Flag  
TA = Technicoat Condenser Coil  
Electric Heat Options  
AA = None  
AB = Phase Monitor  
E09 = 9 KW  
E18 = 18 KW  
E24 = 24 KW  
E36 = 36 KW  
E54 = 54 KW  
AC = Coil Guard  
AD = Dirty Filter Switch  
TJ = Technicoat Evaporator Coil  
TS = Technicoat Evaporator & Condenser Coils  
AE = Phase Monitor & Coil Guard  
AF = Phase Monitor & Dirty Filter Switch  
AG = Coil Guard & Dirty Filter Switch  
AH = Phase Monitor, Coil Guard & Dirty Filter Switch  
Airflow  
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be  
located in digits 15-18.  
A = Std. Motor  
B = Std. Motor/Econo./Barometric Relief (Downflow  
Only)  
C = Std. Motor/Econo./Power Exhaust (Downflow Only)  
D = Std. Motor/Motorized Damper (Downflow Only)  
E = Std. Motor/Horizontal Economizer (No Baro.)  
F = Std. Motor/Slab Econo./Power Exhaust  
(Downflow Only)  
Installation Options  
A = No Options Installed  
B = Option 1  
C = Option 2  
G = Std. Motor/Slab Econo./Barometric Relief  
(Downflow Only)  
N = Hi Static Mtr.  
D = Options 1 & 2  
E = Option 3  
F = Option 4  
P = Hi Static Mtr./Econo./Barometric Relief  
(Downflow Only)  
G = Options 1 & 3  
H = Options 1 & 4  
J = Options 1, 2 & 3  
K = Options 1, 2, & 4  
L = Options 1,3 & 4  
M = Options 1, 2, 3, & 4  
N = Options 2 & 3  
P = Options 2 & 4  
Q = Options 2, 3, & 4  
R = Options 3 & 4  
S = Option 5  
Q = Hi Static Mtr./Econo./Power Exhaust  
(Downflow Only)  
R = Hi Static Mtr./Motorized Damper (Downflow Only)  
S = Hi Static Mtr./Horizontal Economizer (No Baro.)  
T = Hi Static Mtr./Slab Econo./Power Exhaust  
(Downflow Only)  
U = Hi Static Mtr./Slab Econo./Barometric Relief  
(Downflow only)  
T = Options 1 & 5  
U = Options 1, 3, & 5  
V = Options 1, 4, & 5  
W = Options 1, 3, 4, & 5  
X = Options 3 & 5  
Y = Options 4 & 5  
Z = Options 3, 4 & 5  
Voltage  
2 = 208/230-3-60  
4 = 460-3-60  
5 = 575-3-60  
Options  
1 = Disconnect  
2 = Non-Pwr'd Conv. Outlet  
3 = Smoke Detector S.A.  
4 = Smoke Detector R.A.  
5 = Pwr'd Conv. Outlet  
10  
Unitary Products Group  
246646-YTG-C-0606  
TABLE 2: DH PHYSICAL DATA  
Component  
Models  
102  
078  
090  
120  
150  
Blower, Centrifugal  
12 x 12  
12 x 12  
12 X 12  
15 x 15  
15 x 15  
(Dia. X Wd. in.)  
Motor, Standard (HP)  
Motor, Optional (HP)  
Rows  
Evaporator  
Blower  
1-1/2  
2
2
3
3
3
2
3
3
5
3
3
3
4
4
Fins per Inch  
15  
15  
15  
15  
40  
13.2  
15  
40  
13.2  
Evaporator  
Coil  
Height (in.)  
32  
32  
32  
Face Area (ft.2 each)  
10.67  
10.67  
10.67  
Propeller Dia.  
(in., each)  
24  
24  
24  
24  
24  
Condenser  
Fan  
(2 per Unit)  
Motor (HP, each)  
1/3  
1/3  
1/3  
3/4  
3/4  
CFM, Nominal (each)  
3400  
3400  
3400  
4400  
4400  
Sys 1: 2 Row  
Rows (each)  
2
2
2
2
Sys 2: 1 Row  
Condenser  
Coil  
(2 per unit)  
Fins per Inch  
20  
36  
20  
36  
20  
36  
20  
44  
20  
44  
Height (in., each)  
Face Area (ft.2 each)  
System 1 (lb./oz.)  
System 2 (lb./oz.)  
Quantity  
12  
12  
12  
14.5  
12/0  
11/0  
2
14.5  
9/14  
9/4  
8/0  
8/12  
9/0  
2
9/8  
8/2  
2
Refrigerant  
Charge  
4/12  
2
2
Compressors  
Air Filters  
Type  
Recip.  
Recip  
Recip.  
Recip  
Scroll  
Size (Wd. x Ht. x  
Thickness in.)  
25x16x2  
4
25x16x2  
4
25x16x2  
4
25x20x2  
4
25x20x2  
4
Number Per Unit  
Unitary Products Group  
11  
246646-YTG-C-0606  
TABLE 3: DH CAPACITY RATINGS  
Cooling Capacity  
Nominal  
Electric  
Heat  
Gas Heat Capacity  
Seasonal  
1
Gas  
Line  
ARI Ratings  
Sound  
Rating  
Size  
Model  
(Tons)  
CFM  
Temp.  
Rise  
(°F)  
Size  
(in. OD)  
2
3
Input Output  
(MBH) (MBH)  
(dB)  
Capacity  
(kW)  
MBH EER IPLV  
Efficiency  
(%)  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
9, 18, 24,  
36  
078  
(6-1/2)  
75  
11.5  
11.5  
11.0  
11.0  
11.90 2421  
84  
84  
84  
90  
90  
Gas Heat  
Gas Heat  
-
-
120  
180  
96  
80  
80  
20-50  
35-65  
3/4  
3/4  
144  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
090  
(7-1/2)  
18, 36  
89  
12.0  
3000  
Gas Heat  
Gas Heat  
-
-
120  
180  
96  
80  
80  
15-45  
30-60  
3/4  
3/4  
144  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
9, 18, 24,  
36  
102  
(8-1/2)  
99  
11.50 2692  
Gas Heat  
Gas Heat  
-
-
120  
180  
96  
80  
80  
15-45  
30-60  
3/4  
3/4  
144  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
18, 24, 36,  
54  
120  
(10)  
115  
11.70 3840  
Gas Heat  
Gas Heat  
-
-
180  
240  
144  
192  
80  
80  
20-50  
35-65  
3/4  
3/4  
Cooling  
Only  
-
-
-
-
-
-
-
-
-
-
-
Electric  
Heat  
18, 24, 36,  
54  
150  
(12-1/2)  
146  
10.0 10.70 4100  
Gas Heat  
Gas Heat  
-
-
180  
240  
144  
192  
80  
80  
10-40  
25-55  
3/4  
3/4  
1
2
3
Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.  
Rated in accordance with ARI 270 standard.  
See Table 20.  
TABLE 4: UNIT VOLTAGE LIMITATIONS  
POWER RATING  
208/230-3-60  
460-3-60  
MIN.  
187  
432  
540  
MAX.  
252  
504  
575-3-60  
630  
12  
Unitary Products Group  
246646-YTG-C-0606  
TABLE 5: COOLING CAPACITY DH078 (6-1/2 TON) UNIT  
Air On  
Temperature of Air on Condenser Coil 75°F  
Evap. Coil  
Temperature of Air on Condenser Coil 85°F  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)*  
Tot.  
Tot.  
Cap.1 Input2  
(MBH)  
Tot.  
Tot.  
Cap.1  
(MBH)  
WB  
(°F)  
Input2  
Return Dry Bulb (°F)  
CFM  
1950  
2275  
2600  
2925  
3250  
(kW)  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
88.9  
85.5  
80.0  
78.2  
91.3  
87.9  
82.2  
80.4  
93.8  
90.2  
84.4  
82.6  
94.5  
90.9  
85.0  
83.1  
95.1  
91.5  
85.6  
83.7  
4.8  
4.8  
4.7  
4.7  
4.8  
4.8  
4.7  
4.7  
4.8  
4.8  
4.8  
4.7  
4.8  
4.8  
4.8  
4.7  
4.9  
4.8  
4.8  
4.7  
51.3 45.8 40.2 34.6 29.1  
-
-
84.6  
79.8  
74.2  
73.1  
87.1  
82.2  
76.4  
75.2  
89.6  
84.5  
78.6  
77.4  
90.5  
85.4  
79.4  
78.2  
91.4  
86.3  
80.2  
79.0  
5.3  
5.2  
5.1  
5.1  
5.3  
5.3  
5.2  
5.2  
5.4  
5.3  
5.2  
5.2  
5.4  
5.3  
5.2  
5.2  
5.4  
5.3  
5.2  
5.2  
49.4 43.9 38.3 32.7 27.2  
-
-
65.4 59.9 54.3 48.7 43.2 37.6 32.1  
80.0 73.8 68.2 62.7 57.1 51.5 46.0  
78.2 76.8 71.3 65.7 60.2 54.6 49.0  
62.9 57.4 51.8 46.2 40.7 35.1 29.6  
74.2 69.8 64.3 58.7 53.1 47.6 42.0  
73.1 71.6 66.0 60.5 54.9 49.4 43.8  
56.3 49.7 43.2 36.6 30.0  
-
-
54.5 47.9 41.4 34.8 28.2  
-
-
71.4 64.9 58.3 51.7 45.1 38.6 32.0  
82.2 79.1 73.3 66.7 60.1 53.5 47.0  
80.4 79.7 76.5 70.0 63.4 56.8 50.3  
69.1 62.5 56.0 49.4 42.8 36.2 29.7  
76.4 74.2 69.4 62.8 56.3 49.7 43.1  
75.2 74.5 71.3 64.8 58.2 51.6 45.0  
61.3 53.7 46.1 38.5 30.9  
-
-
59.6 52.0 44.4 36.9 29.3  
-
-
77.4 69.9 62.3 54.7 47.1 39.5 31.9  
84.4 84.4 78.3 70.7 63.1 55.5 47.9  
82.6 82.6 81.8 74.2 66.6 59.1 51.5  
75.3 67.7 60.1 52.5 44.9 37.4 29.8  
78.6 78.6 74.6 67.0 59.4 51.8 44.2  
77.4 77.4 76.6 69.0 61.5 53.9 46.3  
65.3 56.6 48.0 39.4 30.7  
-
-
63.7 55.1 46.5 37.8 29.2  
-
-
83.2 73.5 64.8 56.2 47.6 38.9 30.3  
85.0 85.0 82.0 73.3 64.7 56.0 47.4  
83.1 83.1 82.8 74.1 65.5 56.9 48.2  
80.1 71.5 62.8 54.2 45.6 36.9 28.3  
79.4 79.4 77.4 68.8 60.1 51.5 42.9  
78.2 78.2 77.8 69.2 60.5 51.9 43.3  
69.3 59.6 49.9 40.2 30.5  
-
-
67.8 58.2 48.5 38.8 29.1  
-
-
88.9 77.1 67.4 57.7 48.0 38.3 28.6  
85.6 85.6 85.6 75.9 66.3 56.6 46.9  
83.7 83.7 83.7 74.0 64.4 54.7 45.0  
84.9 75.2 65.6 55.9 46.2 36.5 26.8  
80.2 80.2 80.2 70.6 60.9 51.2 41.5  
79.0 79.0 79.0 69.3 59.6 49.9 40.2  
Temperature of Air on Condenser Coil 95°F  
Temperature of Air on Condenser Coil 105°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
80.3  
74.1  
68.5  
68.0  
82.8  
76.5  
70.7  
70.1  
85.4  
78.8  
72.9  
72.2  
86.5  
79.9  
73.9  
73.2  
87.7  
81.0  
74.9  
74.2  
5.8  
5.7  
5.6  
5.6  
5.8  
5.7  
5.6  
5.6  
5.9  
5.8  
5.7  
5.7  
5.9  
5.8  
5.7  
5.7  
5.9  
5.8  
5.7  
5.7  
47.5 42.0 36.4 30.8 25.3  
-
-
74.6  
67.4  
63.3  
63.0  
76.8  
69.4  
65.2  
64.8  
78.9  
71.3  
67.0  
66.6  
80.0  
72.3  
67.9  
67.5  
81.0  
73.2  
68.8  
68.4  
6.3  
6.1  
6.0  
6.1  
6.3  
6.2  
6.1  
6.1  
6.4  
6.2  
6.1  
6.2  
6.4  
6.3  
6.2  
6.2  
6.4  
6.3  
6.2  
6.2  
45.1 39.6 34.0 28.5 22.9  
-
-
60.4 54.9 49.3 43.7 38.2 32.6 27.1  
68.5 65.8 60.3 54.7 49.2 43.6 38.0  
68.0 66.4 60.8 55.2 49.7 44.1 38.6  
57.6 52.1 46.5 40.9 35.4 29.8 24.3  
63.3 60.8 55.2 49.7 44.1 38.6 33.0  
63.0 61.2 55.6 50.1 44.5 39.0 33.4  
1950  
2275  
2600  
2925  
3250  
52.7 46.2 39.6 33.0 26.4  
-
-
50.2 43.7 37.1 30.5 23.9  
-
-
66.8 60.2 53.6 47.0 40.5 33.9 27.3  
70.7 69.4 65.6 59.0 52.4 45.8 39.3  
70.1 69.3 66.1 59.6 53.0 46.4 39.8  
63.0 57.3 50.7 44.1 37.6 31.0 24.4  
65.2 63.9 60.2 53.7 47.1 40.5 33.9  
64.8 63.9 60.7 54.1 47.5 40.9 34.4  
57.9 50.4 42.8 35.2 27.6  
-
-
55.3 47.7 40.2 32.6 25.0  
-
-
73.1 65.5 57.9 50.4 42.8 35.2 27.6  
72.9 72.9 70.8 63.2 55.7 48.1 40.5  
72.2 72.2 71.5 63.9 56.3 48.7 41.1  
68.5 62.5 54.9 47.3 39.7 32.2 24.6  
67.0 67.0 65.2 57.6 50.1 42.5 34.9  
66.6 66.6 65.7 58.1 50.5 42.9 35.3  
62.2 53.6 44.9 36.3 27.6  
-
-
59.6 50.9 42.3 33.7 25.0  
-
-
77.0 69.5 60.8 52.2 43.6 34.9 26.3  
73.9 73.9 72.8 64.2 55.6 46.9 38.3  
73.2 73.2 72.8 64.2 55.6 46.9 38.3  
70.8 66.0 57.8 49.2 40.6 31.9 23.3  
67.9 67.9 67.0 58.4 49.7 41.1 32.5  
67.5 67.5 67.0 58.4 49.7 41.1 32.5  
66.4 56.7 47.1 37.4 27.7  
-
-
63.8 54.1 44.4 34.8 25.1  
-
-
81.0 73.4 63.7 54.0 44.4 34.7 25.0  
74.9 74.9 74.9 65.2 55.5 45.8 36.1  
74.2 74.2 74.2 64.5 54.9 45.2 35.5  
73.2 69.4 60.8 51.1 41.4 31.7 22.0  
68.8 68.8 68.8 59.1 49.4 39.7 30.0  
68.4 68.4 68.4 58.7 49.0 39.3 29.6  
Temperature of Air on Condenser Coil 115°F  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
69.0  
60.7  
58.2  
58.0  
70.7  
62.3  
59.6  
59.4  
72.5  
63.8  
61.1  
60.9  
73.4  
64.6  
61.9  
61.7  
74.3  
65.5  
62.7  
62.5  
6.8  
6.6  
6.5  
6.6  
6.8  
6.7  
6.6  
6.7  
6.9  
6.7  
6.6  
6.7  
6.9  
6.7  
6.7  
6.7  
7.0  
6.8  
6.7  
6.8  
42.8 37.2 31.6 26.1 20.5  
-
-
63.3  
54.0  
53.0  
53.0  
64.6  
55.2  
54.1  
54.1  
66.0  
56.3  
55.3  
55.3  
66.8  
57.0  
55.9  
55.9  
67.6  
57.7  
56.6  
56.6  
7.3  
7.1  
7.0  
7.1  
7.4  
7.1  
7.1  
7.2  
7.4  
7.2  
7.1  
7.2  
7.5  
7.2  
7.1  
7.3  
7.5  
7.3  
7.2  
7.3  
40.4 34.8 29.2 23.7 18.1  
-
-
54.8 49.3 43.7 38.2 32.6 27.0 21.5  
58.2 55.8 50.2 44.7 39.1 33.5 28.0  
58.0 56.0 50.5 44.9 39.3 33.8 28.2  
52.0 46.5 40.9 35.4 29.8 24.2 18.7  
53.0 50.7 45.2 39.6 34.1 28.5 23.0  
53.0 50.9 45.3 39.7 34.2 28.6 23.1  
1950  
2275  
2600  
2925  
3250  
47.7 41.2 34.6 28.0 21.4  
-
-
45.2 38.7 32.1 25.5 18.9  
-
-
59.3 54.4 47.8 41.2 34.7 28.1 21.5  
59.6 58.5 54.9 48.3 41.8 35.2 28.6  
59.4 58.5 55.2 48.6 42.0 35.5 28.9  
55.2 51.5 44.9 38.3 31.8 25.2 18.6  
54.1 53.0 49.6 43.0 36.4 29.9 23.3  
54.1 53.1 49.7 43.1 36.6 30.0 23.4  
52.7 45.1 37.5 30.0 22.4  
-
-
50.1 42.5 34.9 27.3 19.8  
-
-
63.8 59.5 51.9 44.3 36.7 29.1 21.6  
61.1 61.1 59.6 52.0 44.4 36.9 29.3  
60.9 60.9 59.9 52.3 44.7 37.2 29.6  
56.3 56.3 48.9 41.3 33.7 26.1 18.5  
55.3 55.3 54.0 46.4 38.8 31.2 23.7  
55.3 55.3 54.1 46.5 39.0 31.4 23.8  
57.0 48.3 39.7 31.0 22.4  
-
-
54.3 45.7 37.1 28.4 19.8  
-
-
64.6 62.5 54.8 46.2 37.6 28.9 20.3  
61.9 61.9 61.2 52.5 43.9 35.2 26.6  
61.7 61.7 61.2 52.6 43.9 35.3 26.7  
57.0 57.0 51.8 43.2 34.6 25.9 17.3  
55.9 55.9 55.3 46.7 38.0 29.4 20.8  
55.9 55.9 55.4 46.7 38.1 29.5 20.8  
61.2 51.5 41.8 32.1 22.4  
-
-
58.6 48.9 39.2 29.5 19.8  
-
-
65.5 65.5 57.8 48.1 38.4 28.7 19.0  
62.7 62.7 62.7 53.0 43.3 33.6 23.9  
62.5 62.5 62.5 52.8 43.1 33.4 23.7  
57.7 57.7 54.8 45.1 35.5 25.8 16.1  
56.6 56.6 56.6 46.9 37.2 27.6 17.9  
56.6 56.6 56.6 46.9 37.2 27.6 17.9  
1
2
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower  
Performance Table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.  
Unitary Products Group  
13  
246646-YTG-C-0606  
TABLE 6: COOLING CAPACITY DH090 (7-1/2 TON) UNIT  
Air On  
Temperature of Air on Condenser Coil 75°F  
Evap. Coil  
Temperature of Air on Condenser Coil 85°F  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Tot.  
Cap.1 Input2  
(MBH)  
Tot.  
Tot.  
Cap.1 Input2  
(MBH)  
Tot.  
WB  
(°F)  
CFM  
2250  
2625  
3000  
3375  
3750  
(kW)  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
102.7  
98.7  
95.0  
5.7  
5.6  
5.6  
5.5  
5.7  
5.6  
5.6  
5.5  
5.7  
5.6  
5.6  
5.5  
5.7  
5.6  
5.6  
5.5  
5.7  
5.6  
5.6  
5.5  
60.1  
75.6  
95.0  
96.7  
65.5  
82.0  
97.2  
98.9  
70.9  
88.3  
99.4  
53.7  
69.2  
87.3  
90.6  
57.9  
74.4  
93.4  
95.9  
62.1  
79.5  
99.4  
47.3 40.9 34.5  
-
-
98.5  
93.0  
88.7  
88.4  
100.9  
95.2  
90.8  
90.5  
103.2  
97.4  
92.9  
92.6  
104.6  
98.7  
94.2  
93.9  
106.0  
6.2  
6.1  
6.1  
6.0  
6.2  
6.1  
6.1  
6.1  
6.3  
6.2  
6.1  
6.1  
6.3  
6.2  
6.1  
6.1  
6.3  
6.2  
6.1  
6.1  
58.2 51.8 45.4 39.0 32.5  
-
-
62.8 56.4 50.0 43.5 37.1  
80.9 74.5 68.0 61.6 55.2  
84.1 77.7 71.3 64.9 58.5  
73.4 67.0 60.5 54.1 47.7 41.3 34.9  
88.7 82.4 76.0 69.6 63.2 56.8 50.4  
88.4 84.3 77.9 71.5 65.0 58.6 52.2  
96.7  
105.1  
101.0  
97.2  
50.3 42.8 35.2  
-
-
63.8 56.2 48.6 41.1 33.5  
-
-
66.8 59.2 51.6 44.0 36.5  
86.1 78.5 70.9 63.3 55.7  
89.6 82.0 74.4 66.8 59.2  
53.4 44.6 35.9  
70.8 62.0 53.3 44.5 35.8  
91.2 82.5 73.8 65.0 56.3  
80.1 72.5 64.9 57.3 49.7 42.2 34.6  
90.8 87.7 81.5 73.9 66.3 58.8 51.2  
90.5 88.5 83.5 75.9 68.3 60.7 53.2  
98.9  
107.5  
103.3  
99.4  
-
-
69.4 60.7 51.9 43.2 34.4  
-
-
86.8 78.0 69.3 60.5 51.8 43.0 34.3  
92.9 92.9 87.0 78.2 69.5 60.7 52.0  
92.6 92.6 89.1 80.3 71.6 62.8 54.1  
101.2  
108.5  
104.3  
100.4  
102.2  
109.6  
105.4  
101.4  
103.3  
101.2 101.2 95.0 86.2 77.5 68.7 60.0  
75.3  
94.8  
100.4 100.4 95.9 85.9 76.0 66.0 56.0  
102.2 102.2 99.1 89.2 79.2 69.2 59.3  
79.8  
101.3 87.3  
101.4 101.4 100.5 89.4 78.2 67.0 55.8  
103.3 103.3 103.3 92.1 80.9 69.7 58.6  
65.4  
83.4  
55.4 45.4 35.5  
73.5 63.5 53.6 43.6 33.6  
-
-
74.2 64.3 54.3 44.3 34.4  
-
-
92.4 82.4 72.5 62.5 52.5 42.6 32.6  
94.2 94.2 91.0 81.0 71.0 61.1 51.1  
93.9 93.9 92.1 82.1 72.2 62.2 52.3  
68.6  
57.4 46.2 35.1  
76.2 65.0 53.8 42.6 31.5 100.1  
-
-
79.0 67.9 56.7 45.5 34.3  
-
-
98.0 86.8 75.6 64.5 53.3 42.1 30.9  
95.4 95.4 95.0 83.8 72.6 61.4 50.3  
95.1 95.1 95.1 83.9 72.8 61.6 50.4  
95.4  
95.1  
Temperature of Air on Condenser Coil 95°F  
Temperature of Air on Condenser Coil 105°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
94.3  
87.3  
82.4  
80.1  
96.6  
89.4  
84.4  
82.1  
98.9  
91.5  
86.4  
84.0  
100.6  
93.1  
87.9  
85.5  
102.4  
94.7  
89.4  
87.0  
6.7  
6.7  
6.5  
6.5  
6.8  
6.7  
6.6  
6.6  
6.8  
6.7  
6.6  
6.6  
6.9  
6.8  
6.7  
6.6  
6.9  
6.8  
6.7  
6.7  
56.3  
71.1  
82.4  
80.1  
62.1  
78.2  
84.4  
82.1  
67.9  
85.2  
86.4  
84.0  
73.1  
90.0  
87.9  
85.5  
78.3  
94.7  
89.4  
87.0  
49.8  
64.7  
77.6  
78.0  
54.5  
70.6  
82.0  
81.0  
59.2  
76.5  
86.4  
84.0  
63.2  
81.4  
87.9  
85.5  
67.1  
86.3  
89.4  
87.0  
43.4 37.0 30.6  
-
-
87.5  
79.7  
76.0  
74.0  
89.8  
81.8  
78.0  
75.9  
92.1  
83.8  
80.0  
77.8  
93.4  
85.1  
81.2  
79.0  
94.8  
86.4  
82.4  
80.2  
7.3  
7.2  
7.1  
7.1  
7.4  
7.2  
7.1  
7.1  
7.4  
7.3  
7.2  
7.2  
7.4  
7.3  
7.2  
7.2  
7.5  
7.3  
7.2  
7.2  
53.7 47.2 40.8 34.4 28.0  
-
-
58.3 51.9 45.5 39.1 32.7  
71.2 64.8 58.4 51.9 45.5  
71.6 65.2 58.8 52.4 46.0  
67.8 61.4 55.0 48.6 42.2 35.8 29.4  
76.0 71.7 65.3 58.9 52.4 46.0 39.6  
74.0 72.0 65.6 59.2 52.7 46.3 39.9  
2250  
2625  
3000  
3375  
3750  
46.9 39.4 31.8  
-
-
59.6 52.0 44.4 36.8 29.3  
-
-
63.0 55.4 47.9 40.3 32.7  
76.9 69.4 61.8 54.2 46.6  
77.4 69.8 62.2 54.7 47.1  
74.3 67.4 59.9 52.3 44.7 37.1 29.5  
78.0 75.8 71.0 63.4 55.8 48.3 40.7  
75.9 74.9 71.3 63.8 56.2 48.6 41.0  
50.5 41.7 33.0  
-
-
65.5 56.8 48.0 39.3 30.5  
-
-
67.7 59.0 50.2 41.5 32.8  
82.7 73.9 65.2 56.4 47.7  
83.2 74.4 65.7 57.0 48.2  
80.7 73.5 64.7 56.0 47.2 38.5 29.7  
80.0 80.0 76.7 68.0 59.2 50.5 41.7  
77.8 77.8 77.1 68.3 59.6 50.8 42.1  
53.2 43.2 33.3  
-
-
70.8 60.8 50.8 40.9 30.9  
-
-
71.4 61.5 51.5 41.5 31.6  
86.1 76.1 66.1 56.2 46.2  
85.1 75.1 65.2 55.2 45.2  
83.5 77.8 68.5 58.6 48.6 38.6 28.7  
81.2 81.2 79.6 69.6 59.6 49.7 39.7  
79.0 79.0 78.6 68.7 58.7 48.7 38.8  
55.9 44.8 33.6  
-
-
76.0 64.9 53.7 42.5 31.3  
-
-
75.1 63.9 52.8 41.6 30.4  
89.4 78.2 67.1 55.9 44.7  
87.0 75.8 64.6 53.4 42.2  
86.4 82.2 72.4 61.2 50.0 38.8 27.6  
82.4 82.4 82.4 71.2 60.0 48.9 37.7  
80.2 80.2 80.2 69.0 57.8 46.6 35.5  
Temperature of Air on Condenser Coil 115°F  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
80.6  
72.0  
69.6  
67.8  
82.9  
74.1  
71.6  
69.7  
85.2  
76.1  
73.6  
71.6  
86.2  
77.1  
74.5  
72.5  
87.3  
78.0  
75.4  
73.4  
7.9  
7.7  
7.6  
7.6  
7.9  
7.7  
7.7  
7.7  
8.0  
7.8  
7.7  
7.7  
8.0  
7.8  
7.7  
7.8  
8.1  
7.9  
7.8  
7.8  
51.1  
64.6  
69.6  
67.8  
57.1  
70.3  
71.6  
69.7  
63.1  
76.1  
73.6  
71.6  
68.4  
77.1  
74.5  
72.5  
73.8  
78.0  
75.4  
73.4  
44.6  
58.1  
65.8  
66.0  
49.5  
64.3  
69.7  
68.8  
54.3  
70.4  
73.6  
71.6  
58.5  
74.2  
74.5  
72.5  
62.6  
78.0  
75.4  
73.4  
38.2 31.8 25.4  
-
-
73.7  
64.4  
63.2  
61.6  
76.0  
66.4  
65.2  
63.5  
78.3  
68.4  
67.2  
65.4  
79.0  
69.0  
67.8  
66.0  
79.7  
69.7  
68.4  
66.6  
8.4  
8.2  
8.1  
8.2  
8.5  
8.2  
8.2  
8.2  
8.5  
8.3  
8.2  
8.3  
8.6  
8.4  
8.3  
8.3  
8.7  
8.4  
8.3  
8.4  
48.4 42.0 35.6 29.2 22.8  
-
-
51.7 45.3 38.9 32.5 26.1  
59.4 52.9 46.5 40.1 33.7  
59.5 53.1 46.7 40.3 33.9  
61.3 54.8 48.4 42.0 35.6 29.2 22.8  
63.2 59.9 53.5 47.0 40.6 34.2 27.8  
61.6 59.9 53.5 47.1 40.7 34.3 27.8  
2250  
2625  
3000  
3375  
3750  
41.9 34.3 26.7  
-
-
54.5 47.0 39.4 31.8 24.2  
-
-
56.7 49.1 41.5 34.0 26.4  
65.1 57.5 49.9 42.3 34.7  
65.3 57.7 50.1 42.5 34.9  
66.4 61.1 53.5 46.0 38.4 30.8 23.2  
65.2 63.5 59.1 51.6 44.0 36.4 28.8  
63.5 62.7 59.2 51.6 44.0 36.4 28.9  
45.6 36.8 28.1  
-
-
60.6 51.9 43.1 34.4 25.6  
-
-
61.7 52.9 44.2 35.4 26.7  
70.8 62.0 53.3 44.5 35.8  
71.0 62.2 53.5 44.7 36.0  
68.4 67.4 58.6 49.9 41.1 32.4 23.6  
67.2 67.2 64.8 56.1 47.3 38.6 29.8  
65.4 65.4 64.9 56.1 47.4 38.6 29.9  
48.5 38.5 28.6  
-
-
66.1 56.1 46.1 36.2 26.2  
-
-
65.6 55.7 45.7 35.7 25.8  
73.1 63.1 53.2 43.2 33.2  
72.2 62.2 52.3 42.3 32.3  
69.0 69.0 62.7 52.8 42.8 32.8 22.9  
67.8 67.8 66.6 56.6 46.7 36.7 26.8  
66.0 66.0 65.8 55.8 45.8 35.9 25.9  
51.4 40.2 29.1  
-
-
71.5 60.3 49.2 38.0 26.8  
-
-
69.6 58.4 47.2 36.1 24.9  
75.4 64.2 53.0 41.9 30.7  
73.4 62.2 51.0 39.9 28.7  
69.7 69.7 66.8 55.6 44.5 33.3 22.1  
68.4 68.4 68.4 57.2 46.0 34.8 23.7  
66.6 66.6 66.6 55.4 44.3 33.1 21.9  
1
2
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower  
Performance Table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.  
14  
Unitary Products Group  
246646-YTG-C-0606  
TABLE 7: COOLING CAPACITY DH102 (8-1/2 TON) UNIT  
Air On  
Temperature of Air on Condenser Coil 75°F  
Evap. Coil  
Temperature of Air on Condenser Coil 85°F  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)*  
Tot.  
Tot.  
Cap.1 Input2  
(MBH)  
Tot.  
Tot.  
Cap.1  
(MBH)  
WB  
(°F)  
Input2  
Return Dry Bulb (°F)  
CFM  
2550  
2975  
3400  
3825  
4250  
(kW)  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
117.0  
112.1  
104.1  
104.5  
120.7  
115.7  
107.5  
107.8  
124.5  
119.3  
110.8  
111.2  
125.4  
120.2  
111.6  
112.0  
126.3  
121.0  
112.4  
112.8  
1.8  
1.9  
2.0  
1.9  
4.3  
4.3  
4.4  
4.4  
6.8  
6.8  
6.9  
6.8  
6.9  
6.9  
6.9  
6.9  
6.9  
6.9  
7.0  
6.9  
66.8 59.5 52.2 44.9 37.7  
-
-
112.5  
106.1  
98.1  
7.6  
7.5  
7.4  
7.4  
7.6  
7.5  
7.4  
7.4  
7.6  
7.5  
7.4  
7.4  
7.7  
7.6  
7.5  
7.5  
7.7  
7.6  
7.5  
7.5  
64.3 57.0 49.8 42.5 35.2  
-
-
85.1 77.8 70.5 63.2 56.0 48.7 41.4  
104. 99.2 92.0 84.7 77.4 70.2 62.9  
104. 103. 96.0 88.7 81.5 74.2 66.9  
82.2 74.9 67.7 60.4 53.1 45.8 38.6  
98.1 93.4 86.1 78.8 71.6 64.3 57.0  
97.5 96.7 89.4 82.2 74.9 67.6 60.4  
97.5  
72.7 64.1 55.5 46.9 38.3  
-
-
116.0  
109.4  
101.1  
100.6  
119.6  
112.7  
104.2  
103.7  
120.8  
113.9  
105.3  
104.7  
122.1  
115.1  
106.4  
105.8  
70.5 61.9 53.3 44.7 36.1  
-
-
92.1 83.5 75.0 66.4 57.8 49.2 40.6  
107. 105. 97.8 89.2 80.6 72.0 63.4  
107. 107. 102. 93.5 84.9 76.3 67.7  
89.6 81.0 72.4 63.9 55.3 46.7 38.1  
101. 98.8 92.2 83.6 75.0 66.4 57.8  
100. 100. 95.8 87.2 78.6 70.0 61.4  
78.6 68.7 58.8 48.9 39.0  
-
-
76.6 66.7 56.8 46.9 37.0  
-
-
99.2 89.3 79.4 69.5 59.6 49.6 39.7  
110. 110. 103. 93.7 83.8 73.9 63.9  
111. 111. 108. 98.3 88.3 78.4 68.5  
97.1 87.1 77.2 67.3 57.4 47.5 37.6  
104. 104. 98.3 88.4 78.5 68.6 58.6  
103. 103. 102. 92.2 82.3 72.4 62.4  
83.4 72.2 60.9 49.6 38.3  
-
-
81.8 70.5 59.2 47.9 36.6  
-
-
104. 93.5 82.2 70.9 59.6 48.3 37.0  
111. 111. 108. 96.7 85.4 74.1 62.8  
112. 112. 110. 99.2 87.9 76.6 65.3  
103. 91.8 80.5 69.2 57.9 46.6 35.4  
105. 105. 102. 91.1 79.8 68.5 57.2  
104. 104. 104. 92.7 81.4 70.1 58.8  
88.3 75.6 62.9 50.3 37.6  
-
-
87.0 74.3 61.6 49.0 36.3  
-
-
110. 97.6 85.0 72.3 59.6 46.9 34.3  
112. 112. 112. 99.8 87.1 74.4 61.8  
112. 112. 112. 100. 87.5 74.8 62.2  
109. 96.5 83.8 71.1 58.5 45.8 33.1  
106. 106. 106. 93.8 81.1 68.4 55.8  
105. 105. 105. 93.2 80.5 67.8 55.2  
Temperature of Air on Condenser Coil 95°F  
Temperature of Air on Condenser Coil 105°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
108.0  
100.0  
92.0  
13.4  
13.1  
12.8  
12.9  
10.9  
10.7  
10.4  
10.5  
8.4  
8.2  
8.0  
8.1  
8.4  
8.3  
8.1  
8.1  
8.4  
8.3  
8.1  
8.1  
61.8 54.6 47.3 40.0 32.8  
-
-
99.4  
90.8  
82.0  
83.3  
102.8  
93.9  
84.8  
86.2  
106.2  
97.0  
87.6  
89.1  
107.6  
98.2  
88.8  
90.2  
108.9  
99.5  
89.9  
91.3  
11.5  
11.2  
11.0  
11.1  
10.3  
10.0  
9.8  
9.9  
9.1  
8.9  
8.7  
8.7  
9.1  
8.9  
8.7  
8.8  
9.2  
8.9  
8.8  
59.2 52.0 44.7 37.4 30.2  
-
-
79.3 72.1 64.8 57.5 50.3 43.0 35.7  
92.0 87.5 80.3 73.0 65.7 58.5 51.2  
90.5 90.2 82.9 75.6 68.3 61.1 53.8  
75.4 68.1 60.8 53.6 46.3 39.0 31.7  
82.0 79.8 72.7 65.4 58.2 50.9 43.6  
83.3 82.3 75.1 67.8 60.5 53.2 46.0  
2550  
2975  
3400  
3825  
4250  
90.5  
111.3  
103.1  
94.8  
68.2 59.7 51.1 42.5 33.9  
-
-
65.7 57.2 48.6 40.0 31.4  
-
-
87.1 78.5 69.9 61.4 52.8 44.2 35.6  
94.8 92.6 86.6 78.0 69.4 60.9 52.3  
93.3 93.1 89.5 80.9 72.3 63.7 55.1  
83.3 74.7 66.1 57.5 48.9 40.3 31.7  
84.8 83.7 79.0 70.4 61.8 53.2 44.6  
86.2 85.7 81.5 72.9 64.3 55.7 47.1  
93.3  
114.7  
106.2  
97.7  
74.6 64.7 54.8 44.9 35.0  
-
-
72.3 62.3 52.4 42.5 32.6  
-
-
94.9 85.0 75.1 65.2 55.3 45.3 35.4  
97.7 97.7 93.0 83.1 73.2 63.3 53.3  
96.1 96.1 96.0 86.1 76.2 66.3 56.4  
91.2 81.2 71.3 61.4 51.5 41.6 31.7  
87.6 87.6 85.2 75.3 65.4 55.5 45.6  
89.1 89.1 88.0 78.1 68.1 58.2 48.3  
96.1  
116.3  
107.7  
99.1  
80.2 68.9 57.6 46.3 35.0  
-
-
78.0 66.7 55.4 44.1 32.9  
-
-
101. 90.2 78.9 67.6 56.3 45.0 33.7  
99.1 99.1 96.7 85.4 74.1 62.8 51.6  
97.5 97.5 97.4 86.2 74.9 63.6 52.3  
95.0 86.7 75.4 64.1 52.8 41.6 30.3  
88.8 88.8 87.6 76.3 65.0 53.7 42.4  
90.2 90.2 89.7 78.4 67.1 55.8 44.5  
97.5  
117.9  
109.2  
100.5  
98.9  
85.7 73.0 60.3 47.7 35.0  
-
-
83.8 71.1 58.5 45.8 33.1  
-
-
108. 95.3 82.7 70.0 57.3 44.7 32.0  
100. 100. 100. 87.8 75.1 62.4 49.8  
98.9 98.9 98.9 86.2 73.5 60.8 48.2  
98.9 92.2 79.5 66.9 54.2 41.5 28.9  
89.9 89.9 89.9 77.2 64.6 51.9 39.2  
91.3 91.3 91.3 78.7 66.0 53.3 40.7  
8.8  
Temperature of Air on Condenser Coil 115°F  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
90.8  
81.6  
72.1  
76.2  
94.3  
84.7  
74.8  
79.1  
97.7  
87.8  
77.6  
82.0  
98.8  
88.8  
78.5  
82.9  
100.0  
89.8  
79.3  
83.8  
9.6  
9.4  
9.2  
9.3  
9.7  
9.4  
9.2  
9.3  
9.8  
9.5  
9.3  
9.4  
9.8  
9.5  
9.4  
9.5  
9.9  
9.6  
9.4  
9.5  
56.6 49.4 42.1 34.8 27.5  
-
-
82.2  
72.3  
62.1  
69.0  
85.8  
75.4  
64.8  
71.9  
89.3  
78.6  
67.5  
74.9  
90.1  
79.3  
68.2  
75.6  
91.0  
80.0  
68.8  
76.3  
7.8  
7.5  
7.3  
7.5  
9.1  
8.8  
8.6  
8.8  
54.0 46.8 39.5 32.2 24.9  
-
-
71.4 64.1 56.8 49.6 42.3 35.0 27.8  
72.1 72.1 65.1 57.9 50.6 43.3 36.0  
76.2 74.5 67.2 59.9 52.7 45.4 38.1  
67.4 60.1 52.9 45.6 38.3 31.0 23.8  
62.1 62.1 57.6 50.3 43.0 35.7 28.5  
69.0 66.7 59.4 52.1 44.8 37.6 30.3  
2550  
2975  
3400  
3825  
4250  
63.3 54.7 46.1 37.5 28.9  
-
-
60.8 52.2 43.6 35.0 26.4  
-
-
79.4 70.8 62.2 53.6 45.0 36.4 27.8  
74.8 74.8 71.3 62.7 54.1 45.5 36.9  
79.1 78.2 73.6 65.0 56.4 47.8 39.2  
75.4 66.9 58.3 49.8 41.2 32.6 24.0  
64.8 64.8 63.6 55.0 46.4 37.8 29.2  
71.9 70.8 65.6 57.0 48.4 39.8 31.3  
69.9 60.0 50.0 40.1 30.2  
-
-
10.5  
10.1  
9.9  
67.5 57.6 47.7 37.7 27.8  
-
-
87.4 77.5 67.6 57.7 47.8 37.8 27.9  
77.6 77.6 77.4 67.5 57.6 47.7 37.8  
82.0 82.0 79.9 70.0 60.1 50.2 40.3  
78.6 73.7 63.8 53.9 44.0 34.1 24.2  
67.5 67.5 67.5 59.7 49.8 39.9 30.0  
74.9 74.9 71.9 62.0 52.0 42.1 32.2  
10.1  
10.6  
10.2  
10.0  
10.1  
10.6  
10.3  
10.1  
10.2  
75.9 64.6 53.3 42.0 30.7  
-
-
73.7 62.5 51.2 39.9 28.6  
-
-
88.6 83.3 72.0 60.7 49.4 38.1 26.8  
78.5 78.5 78.4 67.1 55.8 44.5 33.2  
82.9 82.9 81.9 70.6 59.3 48.0 36.7  
79.3 79.3 68.5 57.2 46.0 34.7 23.4  
68.2 68.2 68.2 57.9 46.6 35.3 24.1  
75.6 75.6 74.1 62.8 51.5 40.2 28.9  
81.9 69.2 56.6 43.9 31.2  
-
-
80.0 67.3 54.7 42.0 29.3  
-
-
89.8 89.1 76.4 63.7 51.0 38.4 25.7  
79.3 79.3 79.3 66.7 54.0 41.3 28.7  
83.8 83.8 83.8 71.2 58.5 45.8 33.2  
80.0 80.0 73.2 60.6 47.9 35.2 22.6  
68.8 68.8 68.8 56.1 43.5 30.8 18.1  
76.3 76.3 76.3 63.7 51.0 38.3 25.6  
1
2
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower  
Performance Table for the kW of the supply air blower motor.  
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.  
Unitary Products Group  
15  
246646-YTG-C-0606  
TABLE 8: COOLING CAPACITY DH120 (10 TON) UNIT  
Air On  
Temperature of Air on Condenser Coil 85°F  
Evap. Coil  
Temperature of Air on Condenser Coil 95°F  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Tot.  
Cap.*  
(MBH)  
Tot.  
Input†  
(kW)  
Tot.  
Cap.* Input†  
(MBH)  
Tot.  
WB  
(°F)  
CFM  
3000  
3500  
4000  
4500  
5000  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
136  
122  
110  
109  
140  
126  
114  
112  
144  
129  
117  
115  
151  
135  
122  
121  
157  
141  
128  
126  
8.8  
8.6  
8.3  
8.7  
8.9  
8.7  
8.4  
8.7  
9.0  
8.8  
8.5  
8.8  
9.1  
8.9  
8.6  
8.9  
9.2  
9.0  
8.7  
9.1  
79  
99  
71  
90  
62  
82  
98  
97  
68  
89  
53  
73  
89  
88  
58  
79  
97  
96  
62  
86  
45  
64  
81  
80  
48  
69  
87  
86  
51  
74  
93  
92  
53  
78  
96  
94  
55  
82  
98  
96  
-
-
126  
114  
108  
103  
130  
118  
112  
106  
134  
122  
115  
110  
139  
126  
120  
114  
144  
131  
124  
118  
9.4  
9.1  
9.0  
9.1  
9.5  
9.1  
9.0  
9.1  
9.5  
9.2  
9.1  
9.2  
9.6  
9.3  
9.2  
9.3  
9.7  
9.4  
9.3  
9.4  
79  
96  
70  
88  
61  
79  
97  
93  
67  
86  
53  
70  
89  
84  
57  
76  
96  
91  
61  
81  
44  
62  
80  
76  
47  
66  
86  
81  
49  
70  
91  
86  
52  
74  
93  
87  
54  
78  
94  
88  
-
-
56  
72  
71  
-
59  
77  
76  
-
62  
82  
80  
-
65  
82  
81  
-
47  
64  
63  
-
49  
67  
66  
-
51  
70  
69  
-
52  
69  
67  
-
53  
72  
67  
-
56  
76  
71  
-
58  
80  
75  
-
61  
79  
74  
-
45  
63  
59  
-
46  
65  
61  
-
46  
68  
63  
-
48  
66  
61  
-
110 107  
109 105  
88  
110 100  
114 112 107  
112 110 106  
108 106  
103 102  
87  
78  
77  
96  
106  
112 111 106  
106 106 101  
96  
116 105  
115 115 115 103  
110 110 110  
105 92 78  
124 114 101  
120 120 119 106  
114 114 114 100  
97  
86  
74  
97  
84  
72  
93  
121 109  
117 117 117 105  
115 115 115 104  
98  
65  
87  
106  
93  
80  
66  
91  
131 118 105  
122 122 122 109  
121 121 121 107  
115 100  
141 127 112  
85  
70  
97  
114  
99  
84  
69  
93  
67  
83  
81  
53  
68  
66  
131 123 108  
124 124 124 109  
118 118 118 103  
63  
79  
73  
49  
64  
58  
128 128 128 113  
126 126 126 111  
Temperature of Air on Condenser Coil 105°F  
Temperature of Air on Condenser Coil 115°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
116  
106  
98  
9.9  
9.6  
9.4  
9.5  
10.0  
9.7  
9.4  
9.6  
10.1  
9.7  
9.5  
9.7  
10.1  
9.8  
9.6  
9.8  
10.2  
9.9  
9.7  
9.8  
74  
92  
98  
96  
82  
66  
84  
97  
95  
72  
92  
57  
75  
88  
87  
62  
82  
96  
94  
67  
89  
49  
67  
80  
78  
52  
72  
86  
84  
56  
77  
93  
90  
60  
83  
93  
91  
64  
89  
94  
91  
40  
58  
71  
69  
42  
62  
76  
74  
44  
65  
81  
79  
46  
70  
80  
78  
49  
74  
79  
77  
-
-
106  
97  
88  
10.4  
10.1  
9.7  
10.0  
10.5  
10.2  
9.8  
10.1  
10.6  
10.3  
9.9  
10.2  
10.6  
10.3  
10.0  
10.3  
10.7  
10.4  
10.0  
10.3  
70  
89  
88  
88  
78  
96  
91  
91  
86  
104  
94  
94  
94  
61  
80  
88  
88  
68  
88  
91  
91  
74  
96  
94  
94  
81  
53  
72  
80  
80  
58  
78  
87  
87  
62  
84  
94  
94  
68  
92  
94  
95  
73  
99  
94  
95  
44  
63  
71  
72  
47  
68  
77  
77  
51  
73  
82  
83  
54  
78  
81  
81  
58  
84  
80  
80  
36  
55  
63  
63  
37  
58  
67  
67  
39  
61  
71  
71  
41  
65  
68  
68  
43  
69  
65  
65  
-
-
50  
63  
61  
-
52  
66  
64  
-
54  
69  
67  
-
56  
67  
64  
-
41  
54  
52  
-
42  
56  
54  
-
42  
58  
55  
-
43  
54  
51  
-
46  
54  
54  
-
48  
57  
57  
-
49  
59  
59  
-
52  
54  
55  
-
37  
46  
46  
-
38  
47  
47  
-
38  
47  
48  
-
39  
41  
42  
-
3000  
3500  
4000  
4500  
5000  
96  
88  
120  
109  
101  
99  
110  
100  
91  
101  
101 101  
99  
91  
110 100  
105 105 104  
102 102 102  
99  
79  
91  
124  
113  
105  
102  
126  
115  
107  
104  
129  
117  
109  
106  
114  
104  
94  
94  
99  
86  
73  
96  
114  
104  
94  
114 107  
107 107 107  
104 104 104  
104 100  
94  
95  
103  
104 104  
94  
95  
88  
95  
108  
93  
79  
114  
104  
94  
117 114 104  
109 109 109  
106 106 106  
59  
64  
62  
44  
50  
47  
54  
50  
50  
39  
35  
35  
94  
95  
94  
95  
95  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
97  
88  
78  
81  
100  
92  
81  
84  
104  
95  
83  
87  
101  
93  
82  
85  
99  
91  
80  
83  
10.8  
10.5  
10.1  
10.4  
11.0  
10.7  
10.2  
10.6  
11.1  
10.8  
10.3  
10.7  
11.1  
10.9  
10.4  
10.8  
11.2  
10.9  
10.4  
10.8  
66  
85  
78  
81  
73  
91  
81  
84  
80  
95  
83  
87  
89  
93  
82  
85  
97  
91  
80  
83  
57  
77  
78  
81  
63  
84  
81  
84  
69  
92  
83  
87  
76  
93  
82  
85  
82  
91  
80  
83  
48  
68  
71  
74  
53  
74  
77  
80  
57  
80  
83  
87  
62  
87  
82  
85  
67  
91  
80  
83  
40  
59  
63  
65  
43  
64  
67  
70  
46  
68  
72  
75  
49  
74  
69  
72  
52  
79  
65  
68  
31  
51  
54  
57  
33  
54  
57  
60  
34  
57  
61  
63  
36  
61  
55  
59  
38  
65  
50  
54  
-
-
*
These capacities are gross ratings. For net  
capacity, deduct air blower motor, MBH = 3.415  
x kW. Refer to the appropriate Blower Perfor-  
mance Table for the kW of the supply air  
blower motor.  
These ratings include condenser fan motors  
and the compressor motors but not the supply  
air blower motor.  
42  
45  
48  
-
44  
47  
50  
-
45  
49  
52  
-
47  
42  
45  
-
34  
37  
39  
-
34  
37  
40  
-
33  
37  
40  
-
34  
29  
32  
-
3000  
3500  
4000  
4500  
5000  
50  
35  
39  
35  
20  
24  
16  
Unitary Products Group  
246646-YTG-C-0606  
TABLE 9: COOLING CAPACITY DH150 (12-1/2 TON) UNIT  
Air On  
Temperature of Air on Condenser Coil 85°F  
Evap. Coil  
Temperature of Air on Condenser Coil 95°F  
Sensible Capacity (MBH)*  
Return Dry Bulb (°F)  
Sensible Capacity (MBH)*  
Tot.  
Tot.  
Cap.*  
(MBH)  
Tot.  
Input†  
(kW)  
Tot.  
Cap.* Input†  
(MBH)  
WB  
(°F)  
Return Dry Bulb (°F)  
CFM  
3750  
4375  
5000  
5625  
6250  
(kW)  
86  
83  
80  
77  
74  
71  
68  
86  
83  
80  
77  
74  
71  
68  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
165  
158  
148  
138  
169  
161  
151  
141  
172  
165  
155  
144  
172  
164  
154  
143  
171  
164  
154  
143  
11.9  
11.8  
11.6  
11.5  
11.9  
11.8  
11.7  
11.5  
12.0  
11.9  
11.7  
11.6  
11.9  
11.8  
11.7  
11.5  
11.9  
11.8  
11.6  
11.5  
95  
85  
74  
63  
92  
52  
82  
-
-
159  
151  
141  
132  
163  
155  
144  
135  
167  
159  
148  
139  
166  
158  
147  
138  
165  
157  
146  
137  
13.1  
13.0  
12.8  
12.8  
13.2  
13.1  
12.9  
12.8  
13.2  
13.1  
12.9  
12.9  
13.2  
13.1  
12.9  
12.8  
13.2  
13.1  
12.9  
12.8  
94  
83  
72  
62  
89  
51  
79  
-
-
124 114 103  
147 137 126 115 105  
138 135 124 113 103  
71  
94  
92  
-
73  
98  
96  
-
60  
83  
81  
-
61  
85  
83  
-
61  
88  
86  
-
56  
83  
77  
-
121 111 100  
141 135 124 113 103  
132 130 120 109  
103  
133 121 108  
144 141 134 121 109  
135 134 129 116 104  
68  
92  
87  
-
70  
96  
91  
-
57  
81  
77  
-
57  
83  
78  
-
58  
85  
80  
-
54  
78  
71  
-
98  
53  
83  
105  
92  
80  
67  
98  
54  
86  
91  
78  
65  
95  
136 124 111  
151 146 136 123 111  
141 139 134 121 109  
115 100  
148 134 119 105  
155 155 146 132 117 102  
144 144 144 129 115 100  
121 105  
156 139 122 106  
154 154 150 133 117 100  
143 143 143 127 110  
127 109  
163 144 126 107  
154 154 154 135 116  
143 143 143 124 106  
86  
71  
56  
90  
113  
98  
84  
69  
55  
87  
76  
145 131 116 101  
148 148 144 129 115 100  
139 139 139 124 109  
120 104  
151 137 120 104  
147 147 145 128 112  
138 138 138 121 104  
127 109  
157 143 125 106  
72  
95  
-
71  
95  
88  
-
69  
90  
81  
88  
71  
55  
89  
-
73  
87  
70  
54  
87  
94  
-
70  
98  
87  
90  
72  
53  
88  
90  
71  
53  
88  
51  
79  
68  
50  
71  
62  
146 146 146 127 108  
137 137 137 118 99  
Temperature of Air on Condenser Coil 105°F  
Temperature of Air on Condenser Coil 115°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
152  
143  
133  
124  
156  
147  
137  
127  
160  
150  
140  
130  
159  
149  
139  
129  
158  
148  
138  
128  
14.6  
14.5  
14.3  
14.2  
14.7  
14.5  
14.3  
14.3  
14.7  
14.5  
14.4  
14.3  
14.7  
14.5  
14.4  
14.3  
14.7  
14.5  
14.3  
14.3  
91  
80  
70  
97  
59  
86  
48  
75  
96  
90  
50  
80  
-
-
145  
135  
125  
116  
149  
138  
129  
119  
153  
142  
132  
122  
152  
141  
131  
121  
151  
140  
130  
120  
16.2  
15.9  
15.8  
15.7  
16.2  
15.9  
15.8  
15.7  
16.2  
15.9  
15.8  
15.8  
16.2  
15.9  
15.8  
15.8  
16.2  
15.9  
15.8  
15.8  
88  
78  
67  
93  
56  
82  
46  
72  
90  
81  
48  
77  
96  
87  
50  
81  
-
-
118 107  
133 128 118 107  
124 122 111 100  
64  
86  
79  
-
67  
90  
83  
-
70  
94  
87  
-
68  
88  
80  
-
54  
75  
68  
-
54  
77  
70  
-
55  
80  
72  
-
51  
72  
63  
-
114 104  
125 122 111 101  
61  
79  
71  
-
64  
84  
75  
-
67  
88  
78  
-
66  
81  
71  
-
50  
68  
60  
-
51  
71  
62  
-
52  
74  
64  
-
49  
65  
55  
-
3750  
4375  
5000  
5625  
6250  
116 113 103  
99 86 73  
127 114 102  
129 127 122 109  
119 118 112 100  
92  
61  
89  
101  
88  
76  
63  
92  
130 118 105  
137 134 128 115 103  
127 126 121 108  
111  
142 128 113  
140 140 138 123 109  
130 130 130 116 101  
118 102  
145 134 118 101  
95  
53  
84  
96  
82  
67  
99  
109  
94  
80  
65  
96  
140 125 111  
132 132 132 118 103  
122 122 122 108  
116 100  
140 132 115  
131 131 131 115  
121 121 121 105  
93  
50  
82  
98  
88  
49  
83  
93  
83  
85  
68  
52  
85  
83  
66  
99  
139 139 138 121 105  
129 129 129 113  
126 107 88 70  
148 141 122 104  
138 138 138 119 101  
128 128 128 110 91  
96  
51  
85  
124 105  
87  
68  
67  
82  
72  
48  
63  
54  
140 139 120 102  
130 130 130 112  
120 120 120 102  
64  
74  
64  
46  
56  
46  
Temperature of Air on Condenser Coil 125°F  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
72  
67  
62  
57  
138  
126  
118  
108  
142  
130  
121  
111  
146  
133  
124  
114  
145  
132  
123  
113  
144  
131  
122  
112  
17.7  
17.3  
17.2  
17.2  
17.7  
17.3  
17.2  
17.2  
17.7  
17.4  
17.2  
17.2  
17.7  
17.4  
17.3  
17.2  
17.7  
17.4  
17.3  
17.2  
86  
75  
64  
90  
54  
79  
94  
84  
58  
86  
43  
68  
83  
73  
46  
73  
90  
79  
48  
79  
97  
85  
48  
80  
91  
80  
47  
81  
85  
75  
-
-
*
These capacities are gross ratings. For net  
capacity, deduct air blower motor, MBH = 3.415  
x kW. Refer to the appropriate Blower Perfor-  
mance Table for the kW of the supply air  
blower motor.  
These ratings include condenser fan motors  
and the compressor motors but not the supply  
air blower motor.  
111 100  
118 116 105  
108 105  
96 84  
124 111  
58  
73  
62  
-
61  
78  
66  
-
64  
83  
70  
-
63  
75  
63  
-
47  
62  
52  
-
48  
65  
54  
-
50  
68  
56  
-
46  
58  
47  
-
3750  
4375  
5000  
5625  
6250  
94  
71  
99  
121 120 116 103  
111 109 104  
107 92 78  
133 122 108  
91  
63  
93  
124 124 124 112  
114 114 114  
114 98 81  
132 130 113  
99  
65  
96  
123 123 123 108  
113 113 113  
122 103 85  
131 131 118  
122 122 122 104  
112 112 112 93  
96  
66  
99  
62  
67  
56  
43  
48  
38  
Unitary Products Group  
17  
246646-YTG-C-0606  
TABLE 10: ELECTRICAL DATA DH078 (6-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
MCA  
Max Fuse Size  
w/Power  
Supply  
Blower  
Motor FLA Motor Outlet  
Pwr  
Exh  
Pwr  
Conv  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Max Fuse*  
Size (Amps)  
Compressors  
RLA LRA  
Electric Heater Actual Heater  
Exhaust  
(Amps)  
Voltage  
Model No.  
KW  
Amps  
FLA  
ea.  
1.5  
HP  
2
HP  
1.5  
HP  
2
HP  
1.5  
HP  
2
HP  
1.5  
HP  
35  
35  
60  
80  
2
1.5  
HP  
40  
40  
70  
80  
2
HP  
45  
45  
70  
80  
110  
45  
45  
80  
90  
125  
25  
25  
35  
45  
60  
20  
20  
30  
40  
50  
FLA  
FLA  
ea.  
ea.  
HP  
40  
40  
60  
80  
None  
--  
6.8  
13.5  
18  
25.5  
--  
--  
29.5  
31.3  
54.6  
70.2  
96.2  
29.5  
34.8  
61.9  
79.9  
31.5 35.0 37.0  
33.8 38.2 40.7  
57.1 61.5 64.0  
72.7 77.1 79.6  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
18.9  
37.5  
50.0  
70.8  
--  
208  
230  
460  
575  
9.0  
72.0  
1.5  
1.5  
0.8  
0.6  
6.2  
6.2  
3.1  
2.4  
8.2  
8.2  
4.1  
3.6  
5.5  
0.0  
98.7 103.1 105.6 100 100 110  
31.5 35.0 37.0  
37.3 41.7 44.2  
64.4 68.8 71.3  
82.4 86.8 89.3  
35  
35  
70  
80  
40  
40  
70  
90  
40  
45  
70  
90  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
9
21.7  
43.3  
57.7  
81.8  
--  
9.0  
5.8  
4.5  
72.0  
45.0  
36.0  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
18  
24  
34  
--  
110.0 112.5 116.9 119.4 110 125 125  
17.8  
17.8  
30.9  
40  
18.8  
20  
21  
20  
20  
35  
40  
60  
15  
15  
25  
35  
45  
20  
20  
35  
45  
60  
15  
20  
30  
35  
50  
25  
25  
35  
45  
60  
20  
20  
30  
35  
50  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
None  
9
11.3  
22.6  
30.1  
42.7  
--  
18.8 20.2 21.4  
32.2 33.7 34.9  
18  
24  
34  
--  
41.2 42.7  
56.2 57.7  
44  
59  
55  
13.7  
13.8  
24.7  
31.9  
43.9  
14.9 15.5 16.7  
15.3 16.1 17.6  
26.2 26.9 28.4  
33.4 34.1 35.6  
45.4 46.1 47.6  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9
9.0  
18  
24  
34  
18.1  
24.1  
34.1  
TABLE 11: ELECTRICAL DATA DH078 (6-1/2 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET  
MCA  
Max Fuse Size  
w/Power  
Supply  
Blower  
Motor FLA Motor Outlet  
Pwr  
Exh  
Pwr  
Conv  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Max Fuse*  
Size (Amps)  
Compressors  
RLA LRA  
Electric Heater Actual Heater  
Exhaust  
(Amps)  
Voltage  
Model No.  
KW  
Amps  
FLA  
ea.  
1.5  
HP  
2
HP  
1.5  
HP  
39.7  
43.8  
67.1  
82.7  
2
HP  
1.5  
HP  
2
HP  
1.5  
HP  
45  
45  
70  
90  
2
1.5  
HP  
50  
60  
80  
90  
2
HP  
50  
FLA  
FLA  
ea.  
ea.  
HP  
50  
50  
70  
90  
None  
--  
6.8  
13.5  
18  
25.5  
--  
--  
41.7 45.2 47.2  
46.3 50.7 53.2  
69.6 74.0 76.5  
85.2 89.6 92.1  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
18.9  
37.5  
50.0  
70.8  
--  
60  
208  
230  
460  
575  
9.0  
72.0  
1.5  
1.5  
0.8  
0.6  
6.2  
6.2  
3.1  
2.4  
8.2  
8.2  
4.1  
3.6  
5.5  
10.0  
80  
100  
125  
50  
108.7 111.2 115.6 118.1 110 125 125  
39.7  
47.3  
74.4  
92.4  
41.7 45.2 47.2  
49.8 54.2 56.7  
76.9 81.3 83.8  
45  
50  
80  
50  
50  
80  
50  
60  
90  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
9
21.7  
43.3  
57.7  
81.8  
--  
60  
9.0  
5.8  
4.5  
72.0  
45.0  
36.0  
5.5  
2.2  
1.8  
10.0  
5.0  
18  
24  
34  
--  
90  
94.9 99.3 101.8 100 100 100  
110  
150  
30  
122.5 125.0 129.4 131.9 125 125 150  
22.8  
23.7  
37.2  
46.2  
61.2  
17.7  
18.8  
29.7  
36.9  
48.9  
23.8  
25  
26  
25  
25  
40  
50  
70  
20  
20  
30  
40  
50  
25  
25  
40  
50  
70  
20  
25  
35  
40  
60  
30  
30  
40  
50  
70  
20  
25  
35  
40  
60  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
None  
9
11.3  
22.6  
30.1  
42.7  
--  
24.9 26.4 27.7  
38.4 39.9 41.2  
30  
18  
24  
34  
--  
45  
47.5  
62.5  
49  
64  
50.2  
65.2  
60  
70  
18.9 19.5 20.7  
20.3 21.1 22.6  
31.2 31.9 33.4  
38.4 39.1 40.6  
50.4 51.1 52.6  
25  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9
9.0  
25  
4.0  
18  
24  
34  
18.1  
24.1  
34.1  
35  
45  
60  
18  
Unitary Products Group  
246646-YTG-C-0606  
TABLE 12: ELECTRICAL DATA DH090 (7-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
Supply  
Blower Motor  
FLA  
Pwr  
Conv  
Outlet  
Max Fuse Size  
w/Power Exhaust  
(Amps)  
OD Fan  
Motors  
Pwr Exh  
Motor  
Min. Circuit  
MCA w/Power  
Max Fuse*  
Compressors  
Electric Heater  
Model No.  
Actual  
KW  
Heater  
Amps  
Ampacity (Amps) Exhaust (Amps) Size (Amps)  
Voltage  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
2 HP 3 HP  
FLA  
FLA  
2 HP  
3 HP  
2 HP  
3 HP  
2 HP 3 HP 2 HP  
3 HP  
None  
--  
--  
42.9  
42.9  
57.1  
72.7  
98.7  
42.9  
42.9  
64.4  
82.4  
112.5  
21.7  
21.7  
32.2  
41.2  
56.2  
17.9  
17.9  
26.2  
33.4  
45.4  
45.6  
45.6  
60.5  
76.1  
102.1  
45.6  
45.6  
67.8  
85.8  
115.9  
22.9  
22.9  
33.7  
42.7  
57.7  
18.4  
18.4  
26.8  
34.0  
46.0  
48.4  
48.4  
64.0  
79.6  
105.6  
48.4  
48.4  
71.3  
89.3  
119.4  
23.9  
23.9  
34.9  
44.0  
59.0  
19.7  
19.7  
28.4  
35.6  
47.6  
51.1  
51.1  
67.3  
83.0  
109.0  
51.1  
51.1  
74.6  
92.7  
122.7  
25.1  
25.1  
36.4  
45.5  
60.5  
20.2  
20.2  
29.0  
36.2  
48.3  
50  
50  
60  
80  
50  
50  
70  
80  
60  
60  
70  
80  
110  
60  
60  
80  
90  
125  
30  
30  
35  
45  
60  
25  
25  
30  
40  
50  
60  
60  
70  
90  
110  
60  
60  
80  
100  
125  
30  
30  
40  
50  
70  
25  
25  
30  
40  
50  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
6.8  
13.5  
18.0  
25.5  
--  
18.9  
37.5  
50.0  
70.8  
--  
208  
230  
460  
575  
14.1  
14.1  
7.1  
110.0  
110.0  
54.0  
1.5  
1.5  
0.8  
0.6  
8.2  
8.2  
4.1  
3.6  
10.9  
10.9  
5.3  
5.5  
0.0  
100 110  
50  
50  
70  
90  
50  
50  
70  
90  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
9
21.7  
43.3  
57.7  
81.8  
--  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
18  
24  
34  
125 125  
--  
25  
25  
35  
45  
60  
20  
20  
30  
35  
50  
25  
25  
35  
45  
60  
20  
20  
30  
35  
50  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
None  
9.0  
18.0  
24.0  
34.0  
--  
11.3  
22.6  
30.1  
42.7  
--  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9.0  
18.0  
24.0  
34.0  
9.0  
5.8  
44.0  
4.1  
18.1  
24.1  
34.1  
TABLE 13: ELECTRICAL DATA DH090 (7-1/2 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET  
Supply  
Blower Motor  
FLA  
Pwr  
Conv  
Outlet  
Max Fuse Size  
w/Power Exhaust  
(Amps)  
OD Fan  
Motors  
Pwr Exh  
Motor  
Min. Circuit  
MCA w/Power  
Max Fuse*  
Compressors  
Electric Heater  
Model No.  
Actual  
KW  
Heater  
Amps  
Ampacity (Amps) Exhaust (Amps) Size (Amps)  
Voltage  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
2 HP 3 HP  
FLA  
FLA  
2 HP  
3 HP  
2 HP  
3 HP  
2 HP 3 HP 2 HP  
3 HP  
None  
--  
--  
52.9  
52.9  
69.6  
85.2  
111.2  
52.9  
52.9  
76.9  
94.9  
125.0  
26.7  
26.7  
38.4  
47.5  
62.5  
21.9  
21.9  
31.2  
38.4  
50.4  
55.6  
55.6  
73.0  
88.6  
114.6  
55.6  
55.6  
80.3  
98.3  
128.4  
27.9  
27.9  
39.9  
49.0  
64.0  
22.4  
22.4  
31.8  
39.0  
51.0  
58.4  
58.4  
76.5  
92.1  
118.1  
58.4  
58.4  
83.8  
101.8  
131.9  
28.9  
28.9  
41.2  
50.2  
65.2  
23.7  
23.7  
33.4  
40.6  
52.6  
61.1  
61.1  
79.8  
95.5  
121.5  
61.1  
61.1  
87.1  
105.2  
135.2  
30.1  
30.1  
42.7  
51.7  
66.7  
24.2  
24.2  
34.0  
41.2  
53.3  
60  
60  
70  
90  
60  
60  
80  
90  
70  
70  
70  
70  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
6.8  
13.5  
18.0  
25.5  
--  
18.9  
37.5  
50.0  
70.8  
--  
208  
230  
460  
575  
14.1  
14.1  
7.1  
110.0  
110.0  
54.0  
1.5  
1.5  
0.8  
0.6  
8.2  
8.2  
4.1  
3.6  
10.9  
10.9  
5.3  
5.5  
10.0  
80  
80  
100  
125  
70  
100  
125  
70  
125 125  
60  
60  
80  
60  
60  
90  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
9
21.7  
43.3  
57.7  
81.8  
--  
70  
70  
5.5  
2.2  
1.8  
10.0  
5.0  
18  
90  
90  
24  
100 100  
125 150  
110  
150  
35  
110  
150  
35  
34  
--  
30  
30  
40  
50  
70  
25  
25  
35  
40  
60  
30  
30  
40  
50  
70  
25  
25  
35  
40  
60  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
None  
9.0  
18.0  
24.0  
34.0  
--  
11.3  
22.6  
30.1  
42.7  
--  
35  
35  
45  
45  
60  
60  
70  
70  
25  
25  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9.0  
18.0  
24.0  
34.0  
9.0  
25  
25  
5.8  
44.0  
4.1  
4.0  
18.1  
24.1  
34.1  
35  
35  
45  
45  
60  
60  
Unitary Products Group  
19  
246646-YTG-C-0606  
TABLE 14: ELECTRICAL DATA DH102 (8-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
Max Fuse Size  
Pwr  
Conv  
Outlet  
Min. Circuit MCA w/Power  
OD Fan Supply Blower Pwr Exh  
Max Fuse*  
Size (Amps)  
w/Power  
Exhaust  
(Amps)  
Compressors  
Ampacity  
(Amps)  
Exhaust  
(Amps)  
Motors  
Motor FLA  
Motor  
Electric Heater Actual Heater  
Voltage  
Model No.  
KW  
Amps  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3 HP  
3 HP  
FLA  
FLA  
3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP  
None  
--  
6.8  
13.5  
18  
25.5  
--  
--  
44.2  
44.2  
60.5  
76.1  
44.2  
44.2  
60.5  
76.1  
49.7  
49.7  
67.3  
83.0  
49.7  
49.7  
67.3  
83.0  
50  
50  
70  
80  
110  
50  
50  
70  
90  
125  
25  
25  
35  
45  
60  
20  
20  
30  
35  
50  
50  
50  
70  
80  
110  
50  
50  
70  
90  
125  
25  
25  
35  
45  
60  
20  
20  
30  
35  
50  
60  
60  
70  
90  
110  
60  
60  
80  
100  
125  
30  
30  
40  
50  
70  
25  
25  
30  
40  
50  
60  
60  
70  
90  
110  
60  
60  
80  
100  
125  
30  
30  
40  
50  
70  
25  
25  
30  
40  
50  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
18.9  
37.5  
50.0  
70.8  
--  
208  
230  
460  
575  
11.7  
11.7  
6.4  
88.0  
88.0  
42.0  
36.0  
3.5  
3.5  
1.6  
1.3  
10.9  
10.9  
5.3  
10.9  
5.5  
5.5  
2.2  
1.8  
0.0  
102.1 102.1 109.0 109.0  
44.2  
44.2  
67.8  
85.8  
44.2  
44.2  
67.8  
85.8  
50.4  
50.4  
74.6  
92.7  
50.4  
50.4  
74.6  
92.7  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
None  
9
21.7  
43.3  
57.7  
81.8  
--  
10.9  
0.0  
0.0  
0.0  
18  
24  
34  
--  
115.9 115.9 122.7 122.7  
22.9  
22.9  
33.7  
42.7  
57.7  
18.2  
18.2  
26.8  
34  
22.9  
22.9  
33.7  
42.7  
57.7  
18.2  
18.2  
26.8  
34  
25.1  
25.1  
36.4  
45.5  
60.5  
20  
25.1  
25.1  
36.4  
45.5  
60.5  
20  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
None  
9
11.3  
22.6  
30.1  
42.7  
--  
5.3  
18  
24  
34  
--  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9
9.0  
20  
20  
5.1  
4.1  
4.1  
18  
24  
34  
18.1  
24.1  
34.1  
29  
29  
36.2  
48.3  
36.2  
48.3  
46  
46  
TABLE 15: ELECTRICAL DATA DH102 (8-1/2 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET  
Max Fuse Size  
Pwr  
Conv  
Outlet  
Min. Circuit MCA w/Power  
OD Fan Supply Blower Pwr Exh  
Max Fuse*  
Size (Amps)  
w/Power  
Exhaust  
(Amps)  
Compressors  
Ampacity  
(Amps)  
Exhaust  
(Amps)  
Motors  
Motor FLA  
Motor  
Electric Heater Actual Heater  
Voltage  
Model No.  
KW  
Amps  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3 HP  
3 HP  
FLA  
FLA  
3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP  
None  
--  
--  
54.2  
54.2  
73.0  
88.6  
54.2  
54.2  
73.0  
88.6  
59.7  
59.7  
79.8  
95.5  
59.7  
59.7  
79.8  
95.5  
60  
60  
60  
60  
70  
70  
70  
70  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
6.8  
18.9  
37.5  
50.0  
70.8  
208  
230  
460  
575  
11.7  
11.7  
6.4  
88.0  
88.0  
42.0  
36.0  
3.5  
3.5  
1.6  
1.3  
10.9  
10.9  
5.3  
10.9  
5.5  
5.5  
2.2  
1.8  
10.0  
13.5  
18  
80  
80  
80  
80  
90  
90  
100  
125  
100  
125  
25.5  
114.6 114.6 121.5 121.5  
125  
125  
None  
--  
9
--  
54.2  
54.2  
80.3  
98.3  
54.2  
54.2  
80.3  
59.7  
59.7  
87.1  
59.7  
59.7  
87.1  
60  
60  
60  
60  
70  
70  
70  
70  
2TP04540925  
2TP04541825  
2TP04542425  
2TP04543625  
21.7  
43.3  
57.7  
81.8  
10.9  
10.0  
10.0  
10.0  
18  
24  
34  
90  
90  
90  
90  
98.3 105.2 105.2  
100  
150  
100  
150  
110  
150  
110  
150  
128.4 128.4 135.2 135.2  
None  
--  
--  
27.9  
27.9  
39.9  
49  
27.9  
27.9  
39.9  
49  
30.1  
30.1  
42.7  
51.7  
66.7  
30.1  
30.1  
42.7  
51.7  
66.7  
30  
30  
40  
50  
70  
30  
30  
40  
50  
70  
35  
35  
45  
60  
70  
35  
35  
45  
60  
70  
2TP04540946  
2TP04541846  
2TP04542446  
2TP04543646  
9
11.3  
22.6  
30.1  
42.7  
5.3  
18  
24  
34  
64  
64  
None  
--  
--  
22.2  
22.2  
31.8  
39  
22.2  
22.2  
31.8  
39  
24  
24  
24  
24  
25  
25  
35  
40  
60  
25  
25  
35  
40  
60  
25  
25  
35  
45  
60  
25  
25  
35  
45  
60  
2TP04540958  
2TP04541858  
2TP04542458  
2TP04543658  
9
9.0  
5.1  
4.1  
4.1  
18  
24  
34  
18.1  
24.1  
34.1  
34  
34  
41.2  
53.3  
41.2  
53.3  
51  
51  
20  
Unitary Products Group  
246646-YTG-C-0606  
TABLE 16: ELECTRICAL DATA DH120 (10 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
2
3
2
3
2
3
2
3
2
HP  
70  
3
FLA  
FLA  
HP  
HP  
HP  
HP  
HP  
HP  
HP HP  
HP  
70  
None  
--  
13.5  
18  
25.5  
40.6  
--  
--  
51.2  
57.1  
72.7  
53.9 56.7 59.4 60 60  
60.5 64.0 67.3 60 70  
76.1 79.6 83.0 80 80  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
37.5  
50.0  
70.8  
70  
70  
208  
230  
460  
16.0 137.0  
3.5  
3.5  
1.6  
1.3  
8.2 10.9  
5.5  
0.0  
80  
90  
98.7 102.1 105.6 109.0 100 110  
110  
175  
70  
110  
175  
70  
112.7 151.1 154.5 158.0 161.4 175 175  
--  
51.2  
64.4  
82.4  
53.9 56.7 59.4 60 60  
67.8 71.3 74.6 70 70  
85.8 89.3 92.7 90 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
18  
24  
34  
54  
--  
43.3  
57.7  
80  
80  
16.0 137.0  
8.2 10.9  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
90  
100  
125  
175  
35  
81.8 112.5 115.9 119.4 122.7 125 125  
129.9 140.2 143.5 147.0 150.4 150 175  
125  
175  
35  
--  
26  
27.2 28.2 29.4 30 35  
33.7 34.9 36.4 35 35  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
18  
24  
34  
54  
--  
22.6  
30.1  
42.7  
67.8  
--  
32.2  
41.2  
56.2  
70.1  
20.6  
26.2  
33.4  
45.4  
56.5  
35  
40  
8.3  
6.4  
69.0  
58.0  
4.1  
3.6  
5.3  
4.1  
42.7  
57.7  
44  
59  
45.5 45 45  
60.5 60 60  
45  
50  
60  
70  
71.6 72.8 74.3 80 80  
21.1 22.4 22.9 25 25  
80  
80  
25  
25  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18  
24  
34  
54  
18.1  
24.1  
34.1  
54.2  
26.8 28.4  
29  
30 30  
30  
30  
575  
34  
46  
35.6 36.2 35 35  
47.6 48.3 50 50  
40  
40  
50  
70  
50  
70  
57.1 58.7 59.3 70 70  
*
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 17: ELECTRICAL DATA DH120 (10 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET  
MCA  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
w/Power  
Exhaust  
(Amps)  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
2
3
2
3
2
3
2
3
2
3
FLA  
FLA  
HP  
HP  
HP  
HP  
HP  
HP  
HP HP  
HP  
80  
HP  
80  
None  
--  
13.5  
18  
25.5  
40.6  
--  
--  
61.2  
69.6  
85.2  
63.9 66.7 69.4 70 70  
73.0 76.5 79.8 70 80  
88.6 92.1 95.5 90 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
37.5  
50.0  
80  
80  
208  
230  
460  
16.0 137.0  
3.5  
3.5  
1.6  
1.3  
8.2 10.9  
5.5  
10.0  
100  
125  
175  
80  
100  
125  
175  
80  
70.8 111.2 114.6 118.1 121.5 125 125  
112.7 163.6 167.0 170.5 173.9 175 175  
--  
61.2  
76.9  
94.9  
63.9 66.7 69.4 70 70  
80.3 83.8 87.1 80 90  
98.3 101.8 105.2 100 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
18  
24  
34  
54  
--  
43.3  
57.7  
90  
90  
16.0 137.0  
8.2 10.9  
5.5  
2.2  
1.8  
10.0  
5.0  
110  
150  
175  
40  
110  
150  
175  
40  
81.8 125.0 128.4 131.9 135.2 125 150  
129.9 152.7 156.0 159.5 162.9 175 175  
--  
31  
32.2 33.2 34.4 35 40  
39.9 41.2 42.7 40 40  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
18  
24  
34  
54  
--  
22.6  
30.1  
42.7  
67.8  
--  
38.4  
47.5  
62.5  
76.3  
24.6  
31.2  
38.4  
50.4  
61.5  
45  
45  
8.3  
6.4  
69.0  
58.0  
4.1  
3.6  
5.3  
4.1  
49  
64  
50.2 51.7 50 50  
65.2 66.7 70 70  
60  
60  
70  
70  
77.8 79.1 80.6 90 90  
25.1 26.4 26.9 30 30  
90  
90  
30  
30  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18  
24  
34  
54  
18.1  
24.1  
34.1  
54.2  
31.8 33.4  
34  
35 35  
35  
35  
575  
4.0  
39  
51  
40.6 41.2 40 40  
52.6 53.3 60 60  
45  
45  
60  
60  
62.1 63.7 64.3 70 70  
70  
70  
*
Maximum HACR breaker of the same AMP size is applicable.  
Unitary Products Group  
21  
246646-YTG-C-0606  
TABLE 18: ELECTRICAL DATA DH150 (12-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET  
MCA  
w/Power  
Exhaust  
(Amps)  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3
5
3
5
3
5
3
5
3
5
FLA  
FLA  
HP  
HP  
HP  
HP  
HP  
HP  
HP HP  
HP  
80  
HP  
90  
None  
--  
13.5  
18  
25.5  
40.6  
--  
--  
60.4  
60.5  
76.1  
65.6 65.9 71.1 70 80  
67.0 67.3 73.8 70 80  
82.6 83.0 89.5 80 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
37.5  
50.0  
80  
90  
208  
230  
460  
18.9 146.0  
3.5  
3.5  
1.6  
1.3  
10.9 16.1  
10.9 16.1  
5.5  
0.0  
90  
90  
70.8 102.1 108.6 109.0 115.5 110 110  
112.7 154.5 161.0 161.4 167.9 175 175  
110  
175  
80  
125  
175  
90  
--  
60.4  
67.8  
85.8  
65.6 65.9 71.1 70 80  
74.3 74.6 81.1 70 80  
92.3 92.7 99.2 90 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
18  
24  
34  
54  
--  
43.3  
57.7  
80  
90  
18.9 146.0  
5.5  
2.2  
1.8  
0.0  
0.0  
0.0  
100  
125  
175  
40  
100  
150  
175  
40  
81.8 115.9 122.4 122.7 129.2 125 125  
129.9 143.5 150.0 150.4 156.9 175 175  
--  
29.9  
33.7  
42.7  
57.7  
71.6  
23.8  
26.8  
34  
32.7 32.1 34.9 35 40  
37.2 36.4 39.9 35 40  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
18  
24  
34  
54  
--  
22.6  
30.1  
42.7  
67.8  
--  
40  
40  
9.5  
7.6  
73.0  
58.4  
5.3  
4.1  
8.1  
6.0  
46.2 45.5  
61.2 60.5  
49  
64  
45 50  
60 70  
50  
50  
70  
70  
75.1 74.3 77.8 80 90  
25.7 25.6 27.5 30 30  
80  
90  
30  
35  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18  
24  
34  
54  
18.1  
24.1  
34.1  
54.2  
29.2  
29  
31.4 30 30  
30  
35  
575  
*
36.4 36.2 38.6 35 40  
48.4 48.3 50.6 50 50  
59.5 59.3 61.7 70 70  
40  
40  
46  
57.1  
50  
70  
60  
70  
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 19: ELECTRICAL DATA DH150 (12-1/2 TON) HIGH EFFICIENCY W/PWRD CONVENIENCE OUTLET  
MCA  
w/Power  
Exhaust  
(Amps)  
Max  
Fuse*  
Size  
Max Fuse* Size  
w/Power  
Supply  
Blower  
Pwr  
Pwr  
Min. Circuit  
Ampacity  
(Amps)  
OD Fan  
Motors  
Compressors  
Exh Conv  
Electric Heater Actual Heater  
Exhaust  
Voltage  
Motor FLA Motor Outlet  
Model No.  
KW  
Amps  
(Amps)  
(Amps)  
RLA  
ea.  
LRA  
ea.  
FLA  
ea.  
3
5
3
5
3
5
3
5
3
5
FLA  
FLA  
HP  
HP  
HP  
HP  
HP  
HP  
HP HP  
HP  
90  
HP  
100  
100  
110  
150  
200  
100  
100  
125  
150  
175  
45  
None  
--  
13.5  
18  
25.5  
40.6  
--  
--  
70.4  
73.0  
88.6  
75.6 75.9 81.1 80 90  
79.5 79.8 86.3 80 90  
95.1 95.5 102.0 90 100  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
37.5  
50.0  
90  
208  
230  
460  
18.9 146.0  
3.5  
3.5  
1.6  
1.3  
10.9 16.1  
10.9 16.1  
5.5  
10.0  
100  
125  
175  
90  
70.8 114.6 121.1 121.5 128.0 125 125  
112.7 167.0 173.5 173.9 180.4 175 175  
--  
70.4  
80.3  
75.6 75.9 81.1 80 90  
86.8 87.1 93.6 90 90  
2TP04521825  
2TP04522425  
2TP04523625  
2TP04525425  
None  
18  
24  
34  
54  
--  
43.3  
57.7  
90  
18.9 146.0  
5.5  
2.2  
1.8  
10.0  
5.0  
98.3 104.8 105.2 111.7 100 110  
110  
150  
175  
45  
81.8 128.4 134.9 135.2 141.7 150 150  
129.9 156.0 162.5 162.9 169.4 175 175  
--  
34.9  
39.9  
49  
37.7 37.1 39.9 40 45  
43.4 42.7 46.2 40 45  
52.5 51.7 55.2 50 60  
67.5 66.7 70.2 70 70  
81.3 80.6 84.1 90 90  
29.7 29.6 31.5 35 35  
2TP04521846  
2TP04522446  
2TP04523646  
2TP04525446  
None  
18  
24  
34  
54  
--  
22.6  
30.1  
42.7  
67.8  
--  
45  
50  
9.5  
7.6  
73.0  
58.4  
5.3  
4.1  
8.1  
6.0  
60  
60  
64  
70  
80  
77.8  
27.8  
31.8  
39  
90  
90  
35  
35  
2TP04521858  
2TP04522458  
2TP04523658  
2TP04525458  
18  
24  
34  
54  
18.1  
24.1  
34.1  
54.2  
34.2  
34  
36.4 35 35  
35  
40  
575  
*
4.0  
41.4 41.2 43.6 40 45  
53.4 53.3 55.6 60 60  
64.5 64.3 66.7 70 70  
45  
45  
51  
62.1  
60  
70  
60  
70  
Maximum HACR breaker of the same AMP size is applicable.  
TABLE 20: ELECTRIC HEAT MULTIPLIERS  
NOTES FOR TABLES 21 THROUGH TABLE 30:  
VOLTAGE  
Blower performance includes dry coil and 2” throwaway  
filters.  
kW Cap. Multiplier  
NOMINAL  
RATING  
208  
0.75  
0.92  
0.92  
0.92  
Blower performance for gas heat includes the maximum  
number of heat tubes available for each tonnage.  
240  
230  
480  
600  
460  
ESP (External Static Pressure) given is that available for the  
supply and return air duct system. All internal resistances  
have been deducted from the total static pressure of the  
blower.  
575  
NOTE: Electric heaters are rated at nominal voltage. Use  
this table to determine the electric heat capacity for  
heaters supplied at lower voltages.  
22  
Unitary Products Group  
246646-YTG-C-0606  
Unitary Products Group  
23  
246646-YTG-C-0606  
24  
Unitary Products Group  
246646-YTG-C-0606  
Unitary Products Group  
25  
246646-YTG-C-0606  
26  
Unitary Products Group  
246646-YTG-C-0606  
Unitary Products Group  
27  
246646-YTG-C-0606  
28  
Unitary Products Group  
246646-YTG-C-0606  
Unitary Products Group  
29  
246646-YTG-C-0606  
30  
Unitary Products Group  
246646-YTG-C-0606  
Unitary Products Group  
31  
246646-YTG-C-0606  
32  
Unitary Products Group  
246646-YTG-C-0606  
TABLE 31: ADDITIONAL STATIC RESISTANCE DH120 AND 150  
Electric Heat KW2  
24  
1
2 3  
CFM  
Cooling Only  
Economizer  
9
18  
36  
54  
1900  
2100  
2300  
2500  
2700  
2900  
3100  
3300  
3500  
3700  
3900  
4100  
4300  
4500  
4700  
4900  
5100  
5300  
5500  
5700  
5900  
6100  
6300  
0.06  
0.07  
0.08  
0.09  
0.11  
0.12  
0.14  
0.16  
0.18  
0.20  
0.23  
0.25  
0.28  
0.30  
0.33  
0.36  
0.39  
0.42  
0.45  
0.48  
0.52  
0.56  
0.60  
0.02  
0.02  
0.02  
0.02  
0.03  
0.03  
0.03  
0.03  
0.04  
0.04  
0.04  
0.04  
0.05  
0.05  
0.05  
0.05  
0.06  
0.06  
0.06  
0.06  
0.07  
0.07  
0.07  
0.05  
0.06  
0.07  
0.08  
0.09  
0.10  
0.12  
0.13  
0.15  
0.17  
0.19  
0.21  
0.23  
0.25  
0.28  
0.30  
0.33  
0.35  
0.38  
0.41  
0.44  
0.47  
0.50  
0.06  
0.07  
0.08  
0.09  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.26  
0.29  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.07  
0.08  
0.09  
0.10  
0.12  
0.13  
0.15  
0.17  
0.19  
0.21  
0.23  
0.25  
0.28  
0.30  
0.33  
0.35  
0.38  
0.41  
0.44  
0.47  
0.50  
0.53  
0.56  
0.08  
0.09  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.26  
0.29  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.56  
0.59  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.26  
0.28  
0.31  
0.34  
0.37  
0.40  
0.43  
0.46  
0.49  
0.53  
0.56  
0.59  
0.62  
0.65  
1
2
3
Add these resistance values to the available static resistance in the respective Blower Performance Tables.  
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.  
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return  
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
TABLE 32: ADDITIONAL STATIC RESISTANCE DH078, 090, 102  
Electric Heat KW2  
24  
1
2 3  
CFM  
Cooling Only  
Economizer  
9
18  
36  
54  
1900  
2100  
2300  
2500  
2700  
2900  
3100  
3300  
3500  
3700  
3900  
4100  
4300  
-0.004  
0.01  
0.01  
0.02  
0.03  
0.04  
0.05  
0.06  
0.07  
0.08  
0.09  
0.09  
0.10  
0.07  
0.09  
0.11  
0.13  
0.16  
0.18  
0.20  
0.22  
0.24  
0.27  
0.29  
0.31  
0.33  
0.05  
0.06  
0.07  
0.08  
0.09  
0.10  
0.12  
0.13  
0.15  
0.17  
0.19  
0.21  
0.23  
0.06  
0.07  
0.08  
0.09  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.07  
0.08  
0.09  
0.10  
0.12  
0.13  
0.15  
0.17  
0.19  
0.21  
0.23  
0.25  
0.28  
0.08  
0.09  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.26  
0.29  
0.10  
0.11  
0.13  
0.14  
0.16  
0.18  
0.20  
0.22  
0.24  
0.26  
0.28  
0.31  
0.34  
1
2
3
Deduct these resistance values to the available static resistance in the respective Blower Performance Tables.  
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.  
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return  
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.  
Unitary Products Group  
33  
246646-YTG-C-0606  
TABLE 33: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM  
UNIT MODEL SIZE (NOMINAL TONS)  
HEATER  
078 (6.5)  
090 (7.5)  
102 (8.5)  
120 (10)  
150 (12.5)  
VOLTAGE  
kW  
MINIMUM SUPPLY AIR CFM  
1950  
1950  
1950  
1950  
-
2250  
2250  
2250  
2250  
-
2550  
2550  
2550  
2550  
-
-
-
9
3000  
3000  
3000  
3500  
-
3750  
3750  
3750  
4000  
-
18  
24  
36  
54  
9
208/230  
1950  
1950  
1950  
1950  
-
2250  
2250  
2250  
2250  
-
2550  
2550  
2550  
2550  
-
3000  
3000  
3000  
3000  
-
3750  
3750  
3750  
3750  
-
18  
24  
36  
54  
9
480  
600  
1950  
1950  
1950  
1950  
-
2250  
2250  
2250  
2250  
-
2550  
2550  
2550  
2550  
-
3000  
3000  
3000  
3500  
3750  
3750  
3750  
3750  
18  
24  
36  
54  
TABLE 34: INDOOR BLOWER SPECIFICATIONS  
MOTOR  
RPM Eff.  
1-1/2 1725 80% 1.15  
MOTOR SHEAVE  
BLOWER SHEAVE  
MODEL  
DH078  
DH090  
DH102  
DH120  
DH150  
BELT  
HP  
SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model  
56  
56  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
3.4 - 4.4  
4.3 - 5.3  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
7/8  
1 1/8  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VM50  
1VP56  
7.0  
6.2  
6.5  
6.0  
6.0  
5.7  
8.5  
7.0  
7.0  
6.7  
1
1
1
1
1
1
1
1
1
1
AK74  
AK66  
AK69  
AK64  
AK64  
AK61  
AK89  
AK74  
AK74  
BK77  
A49  
A49  
A49  
A49  
A49  
A49  
A56  
A54  
A54  
BX55  
2
2
3
3
3
2
3
3
5
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 80% 1.15  
1725 87% 1.15  
56  
56  
56  
56  
56  
56  
56  
184T  
TABLE 35: POWER EXHAUST SPECIFICATIONS  
MOTOR  
RPM1  
ELECTRICAL  
POWER EXHAUST  
FUSE  
SIZE  
CFM@  
0.1 ESP  
VOLT  
PHASE  
MODEL  
HP  
QTY  
LRA  
FLA  
5.0  
MCA  
2PE0473225  
2PE0473246  
2PE0473258  
208/230  
460  
1
1
1
24.9  
6.3  
2.8  
1.9  
10  
5
1075  
1050  
0.75  
1
2.2  
3,800  
-
575  
1.5  
4
1
Motors are multi-tapped and factory wired for high speed.  
34  
Unitary Products Group  
246646-YTG-C-0606  
FRONT  
FRONT  
LEFT  
LEFT  
B
C
D
C
B
A
A
E
D
F
FIGURE 4 - UNIT 6 POINT LOAD  
TABLE 37: 6 POINT LOAD WEIGHT  
FIGURE 2 - UNIT 4 POINT LOAD  
TABLE 36: 4 POINT LOAD WEIGHT  
Locations (lbs.)  
Location (lbs.)  
Model  
Model  
A
B
C
D
E
F
A
B
C
D
DH078  
DH090  
DH102  
DH120  
DH150  
138  
139  
141  
181  
180  
113  
113  
115  
163  
161  
93  
94  
146  
147  
149  
214  
213  
176  
178  
180  
237  
235  
216  
218  
221  
264  
262  
DH078  
DH090  
DH102  
DH120  
DH150  
197  
199  
201  
265  
263  
147  
148  
150  
226  
224  
230  
232  
234  
330  
327  
309  
311  
315  
386  
383  
95  
147  
146  
TABLE 38: UNIT WEIGHT  
Shipping  
Weight (lbs.)  
Operating  
Weight (lbs.)  
Model  
DH078  
DH090  
DH102  
DH120  
DH150  
W/ECON.  
W/PE  
888  
895  
905  
1212  
1202  
85  
883  
890  
900  
1207  
1197  
84  
Y
X
FRONT  
LEFT  
X
Y
23  
Unit Model Number  
DH078  
150  
49  
148  
49  
1
W/ELECT. HEAT  
38  
38  
38  
2
110  
110  
W/GAS HEAT  
23  
DH090  
1
2
54 KW Heater  
8 Tube Heat Exchanger  
23  
DH102  
47 1/2  
47 1/2  
25 1/2  
25 1/2  
DH120  
DH150  
FIGURE 3 - UNIT CENTER OF GRAVITY  
Unitary Products Group  
35  
246646-YTG-C-0606  
30-11/32  
See Detail  
A
X
Control  
Entry  
Ø 7/8  
Power  
Entry  
Ø 2-1/2  
Power  
Entry  
4-1/4  
Ø 2-1/2  
11-1/2  
Convenience  
Power  
Outlet  
Entry  
For Baserail  
Dimensions  
See Detail B  
Ø 7/8  
FRONT  
17-3/16  
For Drain  
Dimensions  
See Detail C  
30-3/16  
24-3/16  
6-3/16  
59  
LEFT  
89  
27  
FIGURE 5 - UNIT DIMENSIONS  
TABLE 39: UNIT HEIGHT  
DETAIL B  
2
-
3
/
8
X
42  
Unit Model Number  
DH078  
42  
DH090  
42  
DH102  
50 3/4  
50 3/4  
DH120  
3
-
3
/
4
DH150  
G
a
s
P
i
p
e
I
n
l
e
t
DETAIL A  
3
-
9
/
1
6
5
-
1
/
4
B
P
a
a
s
n
e
DETAIL C  
1
7
-
1
3
/
1
6
V
i
e
w
o
f
W
a
l
l
A
c
r
o
s
s
f
r
o
m
C
o
i
l
5
-
3
/
8
TABLE 40: UNIT CLEARANCES  
Top1  
72”  
36”  
36”  
Right  
12”  
36”  
0”  
Front  
Left  
Rear2  
Bottom3  
1
2
Units must be installed outdoors. Overhanging structure or  
shrubs should not obstruct condenser air discharge outlet.  
To remove the slide-out drain pan, a rear clearance of 60” is  
required. If space is unavailable, the drain pan can be  
removed through the front by separating the corner wall.  
Units may be installed on combustible floors made from  
wood or class A, B or C roof covering materials.  
3
36  
Unitary Products Group  
246646-YTG-C-0606  
R
I
G
H
T
8
0
-
5
/
8
I
N
S
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
C
O
N
D
E
N
S
E
R
S
E
C
T
I
O
N
2
0
S
U
P
P
L
Y
2
0
6
R
E
T
U
R
N
2
T
Y
P
.
3
0
I
N
S
O
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
5
0
-
1
/
2
C
M
P
R
E
S
S
O
R
S
E
C
T
I
O
N
F
R
O
N
T
8
o
r
1
4
FIGURE 6 - PREDATOR® ROOF CURB DIMENSIONS  
2
T
Y
P
2
3
4
3
0
-
1
/
2
5
0
-
1
/
2
8
0
-
5
/
8
2
6
R
E
T
U
R
N
S
U
P
P
L
Y
1
0
7
6
-
5
/
8
5
9
-
1
/
4
9
4
F
R
O
N
T
R
I
G
H
T
6
4
-
1
/
4
FIGURE 7 - SUNLINE™ TO PREDATOR® TRANSITION ROOF CURBS  
Unitary Products Group  
37  
246646-YTG-C-0606  
32-11/16  
6-13/16  
6-13/16  
SUPPLY  
AIR  
RETURN  
AIR  
6-13/16  
24  
27-1/2  
21  
LEFT  
18  
19-3/16  
21-3/16  
17-3/16  
12-5/16  
Bottom Power,  
14-23/32  
FRONT  
Bottom gas  
supply entry  
Control and  
Convenience  
Outlet Wiring  
Entry  
16-3/8  
18-1/16  
63-1/2  
FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)  
REAR DUCT DIMENSIONS  
DIMENSION  
CABINET SIZE  
“A”  
“B”  
“C”  
FIGURE 9 - REAR DUCT DIMENSIONS  
50 3/4”  
42”  
28 1/4  
27 3/4  
18 1/16  
12 1/16  
28 1/4  
27 1/2  
38  
Unitary Products Group  
246646-YTG-C-0606  
58 1/4  
88 1/4  
39 1/2  
or  
47 1/2  
Outside Air  
Intake Hood  
35 3/4  
Relief Hood for  
Power Exhaust or  
Barometric Relief  
26  
25 3/4  
26  
30 1/4  
FIGURE 10 -DOWNFLOW ECONOMIZER HOOD DETAIL  
TABLE 41: ECONOMIZER USAGE  
Application  
Cabinet Height  
Description  
Model  
Bottom Return  
Side Return  
All  
All  
Downflow economizer with barometric relief  
Horizontal economizer without barometric relief  
Slab Economizer, 42” tall cabinet  
2EE04705424  
2EE047055241  
2EE047056242  
2EE047052242  
42"  
50"  
ERV or End Return  
Slab Economizer, 50” tall cabinet  
1
2
Barometric relief must be ordered seperately and installed in duct work.  
Barometric relief or fresh air hood not included. Must be ordered seperately.  
Unitary Products Group  
39  
246646-YTG-C-0606  
2EE04705424  
Fresh Air Hood Fresh Air Damper Return Air Damper  
Barometric Relief Damper  
2EE04705424  
2EE04705424  
2EE04705424  
2EE04705424  
Barometric Relief Hood  
FIGURE 11 - FACTORY INSTALLED DOWNFLOW ECONOMIZER  
2EE04705424  
Fresh Air Hood  
2EE04705424 2EE04705424  
Fresh Air Damper Return Air Damper  
2PE047032XX  
Power Exhaust  
2EE04705424  
Barometric Relief Damper  
2EE04705424  
Barometric Relief Hood  
FIGURE 12 - FIELD INSTALLED DOWNFLOW ECONOMIZER W/POWER EXHAUST  
40  
Unitary Products Group  
246646-YTG-C-0606  
2EE04705524  
Return Air Damper  
Field Installed  
Duct Work  
2EE04705524  
Fresh Air Damper  
2PE047032XX  
Power Exhaust  
1EH0408  
Barometric  
Relief Damper  
1EH0408  
Barometric  
Relief Hood  
2EE04705524  
Fresh Air Hood  
FIGURE 13 - FIELD INSTALLED HORIZONTAL ECONOMIZER W/POWER EXHAUST  
1EH0409  
Fresh Air Hood  
2EE04705X24  
Slab Economizer  
2PE047032XX  
Power Exhaust  
1EH0409 Barometric  
Relief Damper  
1EH0409 Barometric  
Relief Hood  
FIGURE 14 - SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST  
Unitary Products Group  
41  
246646-YTG-C-0606  
1EH0409  
Fresh Air Hood  
Field Installed  
Duct Work  
2EE04705X24  
Slab Economizer  
1EH0409  
Barometric Relief Hood  
2PE047032XX  
Power Exhaust  
1EH0409  
Barometric Relief Damper  
FIGURE 15 - SLAB ECONOMIZER END RETURN W/POWER EXHAUST  
42  
Unitary Products Group  
246646-YTG-C-0606  
FIGURE 16 - COOLING UNIT WITH GAS HEAT WIRING 230 VOLT DIAGRAM  
Unitary Products Group  
43  
246646-YTG-C-0606  
FIGURE 17 - COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM  
44  
Unitary Products Group  
246646-YTG-C-0606  
FIGURE 18 - COOLING UNIT WITH GAS HEAT WIRING 460, 575 VOLT 50 HZ DIAGRAM  
Unitary Products Group  
45  
246646-YTG-C-0606  
GUIDE SPECIFICATIONS  
PREDATOR®  
DH 078, 090, 102, 120 & 150, 11.5 EER  
GENERAL  
of the coils. Condensate pan shall be slide out design, con-  
structed of a non corrosive material, internally sloped and  
conforming to ASHRAE 62-B9 standards. Condensate con-  
nection shall be a minimum of ¾” I.D. female and be rigid  
mount connection.  
Units shall be manufactured by York International Unitary  
Products Group in an ISO 9001 certified facility. YORK®  
Predator units are convertible single packages with a com-  
®
mon footprint cabinet and common roof curb for all 6-1/2  
through 12-1/2 ton models. All units have two compressors  
with independent refrigeration circuits to provide 2 stages of  
cooling. The units were designed for light commercial appli-  
cations and can be easily installed on a roof curb, slab, or  
INDOOR (EVAPORATOR) FAN ASSEMBLY  
Fan shall be a belt drive assembly and include an adjustable  
pitch motor pulley. Job site selected brake horsepower shall  
not exceed the motors nameplate horsepower rating plus the  
service factor. Units shall be designed to operate within the  
service factor. Fan wheel shall be double inlet type with for-  
ward curve blades, dynamically balanced to operate  
smoothly throughout the entire range of operation. Airflow  
design shall be constant volume. Bearings shall be sealed  
and permanently lubricated for longer life and no mainte-  
nance. Entire blower assembly and motor shall be slide out  
design.  
®
frame. All Predator units are self-contained and assembled  
on rigid full perimeter base rails allowing for 3-way forklift  
access and overhead rigging. Every unit is completely  
charged, wired, piped, and tested at the factory to provide a  
quick and easy field installation. All units are convertible  
between side and down airflow. Independent economizer  
designs are used on side and down discharge applications,  
®
as well as all tonnage sizes. Predator units are available in  
the following configurations: cooling only, cooling with electric  
heat, and cooling with gas heat. Electric heaters are available  
as factory-installed options or field-installed accessories.  
OUTDOOR (CONDENSER) FAN ASSEMBLY  
DESCRIPTION  
The outdoor fans shall be of the direct drive type, discharge  
air vertically, have aluminum blades riveted to corrosion  
resistant steel spider brackets and shall be dynamically bal-  
anced for smooth operation. The outdoor fan motors shall  
have permanently lubricated bearings internally protected  
against overload conditions and staged independently. A  
cleaning window shall be provided on two sides of the units  
for coil cleaning.  
Units shall be factory assembled, single package, (Elec/Elec,  
Gas/Elec), designed for outdoor installation. Units shall have  
a minimum EER of 9.0. They shall have built in field convert-  
ible duct connections for down discharge supply/return or  
horizontal discharge supply/return and be available with fac-  
tory installed options or field installed accessories. The units  
shall be factory wired, piped and charged with R-22 refriger-  
ant and factory tested prior to shipment. All unit wiring shall  
be both numbered and color coded. The cooling performance  
shall be rated in accordance with DOE and ARI test proce-  
dures. Units shall be CSA certified to ANSI Z21.47 and UL  
1995/CAN/CSA No. 236-M90 standards.  
REFRIGERANT COMPONENTS  
Compressors:  
A. Shall be fully hermetic type, direct drive, internally pro-  
tected with internal high-pressure relief and over temper-  
ature protection. The hermetic motor shall be suction gas  
cooled and have a voltage range of + or – 10% of the  
unit nameplate voltage.  
UNIT CABINET  
Unit cabinet shall be constructed of G90 galvanized steel with  
exterior surfaces coated with a non-chalking, powder paint  
finish, certified at 1000 hour salt spray test per ASTM-B117  
standards. Indoor blower sections shall be insulated with up  
to 1” thick insulation coated on the airside. Aluminum foil  
faced insulation shall be used in the unit’s compartments and  
be fastened to prevent insulation from entering the air  
stream. Cabinet doors shall be hinged with toolless access  
for easy servicing and maintenance. Full perimeter base rails  
shall be provided to assure reliable transit of equipment,  
overhead rigging, fork truck access and proper sealing on  
roof curb applications. Disposable 2” filters shall be furnished  
and be accessible through hinged access door. Fan perfor-  
mance measuring ports shall be provided on the outside of  
the cabinet to allow accurate air measurements of evaporator  
fan performance without removing panels or creating bypass  
B. Shall have internal spring isolation and sound muffling to  
minimize vibration and noise, and be externally isolated  
on a dedicated, independent mounting.  
Coils:  
A. Evaporator and condenser coils shall have aluminum  
plate fins mechanically bonded to seamless internally  
enhanced copper tubes with all joints brazed. Special  
Phenolic coating shall be available as a factory option.  
B. Evaporator and condenser coils shall be of the direct  
expansion, draw-thru design.  
46  
Unitary Products Group  
246646-YTG-C-0606  
Refrigerant Circuit and Refrigerant Safety Components shall  
include:  
shot type, constructed of aluminum-coated steel. All gas pip-  
ing shall enter the unit cabinet at a single location, through  
either the side or bottom, without any field modifications. An  
integrated control board shall provide timed control of evapo-  
rator fan functioning and burner ignition. Heating section shall  
be provided with the following minimum protection:  
A. Independent fixed-orifice or thermally operated expan-  
sion devices.  
B. Solid core filter drier/strainer to eliminate any moisture or  
foreign matter.  
A. Primary and auxiliary high-temperature limit switches.  
B. Induced draft pressure sensor.  
C. Accessible service gage connections on both suction  
and discharge lines to charge, evacuate, and measure  
refrigerant pressure during any necessary servicing or  
troubleshooting, without losing charge.  
C. Flame roll out switch (manual reset).  
D. Flame proving controls. Unit shall have two independent  
st  
nd  
D. The unit shall have two independent refrigerant circuits,  
equally split in 50% capacity increments.  
stages of capacity (60% 1 stage, 100% 2 stage).  
ELECTRIC HEATING SECTION (IF EQUIPPED)  
Unit Controls:  
An electric heating section, with nickel chromium elements,  
shall be provided in a range of 9 thru 54 KW, offering two  
states of capacity all sizes. The heating section shall have a  
primary limit control(s) (automatic reset) to prevent the heat-  
ing element system from operating at an excessive tempera-  
ture. The Heating Section assembly shall slide out of the unit  
for easy maintenance and service. Units with Electric Heating  
Sections shall be wired for a single point power supply with  
branch circuit fusing (where required).  
A. Unit shall be complete with self-contained low-voltage  
control circuit protected by a resettable circuit breaker on  
the 24-volt transformer side.  
B. Unit shall incorporate a lockout circuit which provides  
reset capability at the space thermostat or base unit  
should any of the following standard safety devices trip  
and shut off compressor:  
C. Loss-of-charge/Low-pressure switch.  
(1) High-pressure switch.  
UNIT OPERATING CHARACTERISTICS  
Unit shall be capable of starting and running at 125 ºF out-  
door temperature, exceeding maximum load criteria of ARI  
Standard 340/360. The compressor, with standard controls,  
shall be capable of operation down to 0 ºF outdoor tempera-  
ture. Unit shall be provided with fan time delay to prevent cold  
air delivery before heat exchanger warms up. (Gas heat only)  
(2) Freeze-protection thermostat, evaporator coil. If any  
of the above safety devices trip, an LED (light-emitting  
diode) indicator shall flash a diagnostic code that indi-  
cates which safety switch has tripped.  
D. Unit shall incorporate “AUTO RESET” compressor over  
temperature, over current protection.  
ELECTRICAL REQUIREMENTS - All unit power wiring shall  
enter unit cabinet at a single factory provided location and be  
capable of side or bottom entry to minimize roof penetrations  
and avoid unit field modifications. Separate side and bottom  
openings shall be provided for the control wiring.  
E. Unit shall operate with conventional thermostat designs  
and have a low voltage terminal strip for easy hook-up.  
F. Unit control board shall have on-board diagnostics and  
fault code display.  
STANDARD LIMITED WARRANTIES - Compressor – 5  
Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5  
Years, Parts – 1 Year  
G. Standard controls shall include anti-short cycle and low  
voltage protection, and permit cooling operation down to  
0 ºF.  
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall  
be made available by either/or):  
H. Control board shall monitor each refrigerant safety  
switch independently.  
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-  
MIZER – Outdoor and return air dampers that are inter-  
locked and positioned by a fully-modulating, spring-  
return damper actuator. The maximum leakage rate for  
the outdoor air intake dampers shall not exceed 2%  
when dampers are fully closed and operating against a  
pressure differential of 0.5 IWG. A unit-mounted potenti-  
ometer shall be provided to adjust the outdoor and return  
air damper assembly to take in outdoor air to meet the  
minimum ventilation requirement of the conditioned  
space during normal operation. During economizer oper-  
ation, a mixed-air temperature control shall modulate the  
I. Control board shall retain last 5 fault codes in non-vola-  
tile memory, which will not be lost in the event of a power  
loss.  
GAS HEATING SECTION (IF EQUIPPED)  
Heat exchanger and exhaust system shall be constructed of  
aluminized steel and shall be designed with induced draft  
combustion with post purge logic, energy saving direct spark  
ignition, and redundant main gas valve. The heat exchanger  
shall be of the tubular type, constructed of T1-40 aluminized  
steel for corrosion resistance and allowing minimum mixed  
air entering temperature of 40 ºF. Burners shall be of the in-  
Unitary Products Group  
47  
outdoor and return air damper assembly to prevent the  
supply air temperature from dropping below 55 ºF.  
Changeover from compressor to economizer operation  
shall be provided by an integral electronic enthalpy con-  
trol that feeds input into the basic module. The outdoor  
intake opening shall be covered with a rain hood that  
matches the exterior of the unit. Water eliminator/filters  
shall be provided. Simultaneous economizer/compressor  
operation is also possible. Dampers shall fully close on  
power loss. Available with barometric relief or power  
exhaust.  
COIL GUARD - Designed to prevent condenser coil  
damage.  
BAS CONTROLS - Include supply air sensor, return air  
sensor, dirty filter indicator and air proving switch.  
DIRTY FILTER SWITCH – This kit includes a differential  
pressure switch that energizes the fault light on the unit  
thermostat, indicating that there is an abnormally high-  
pressure drop across the filters.  
BREAKER – An HACR breaker can be factory installed  
on gas heat units or cooling units with electric heat.  
2. MOTORIZED OUTDOOR AIR DAMPERS – Outdoor  
and return air dampers that are interlocked and posi-  
tioned by a 2-position, spring-return damper actuator.  
The maximum leakage rate for the outdoor air intake  
dampers shall not exceed 2% when dampers are fully  
closed and operating against a pressure differential of  
0.5 IWG. A unit-mounted potentiometer shall be provided  
to adjust the outdoor and return air damper assembly to  
take in the design CFM of outdoor air to meet the ventila-  
tion requirements of the conditioned space during normal  
operation. Whenever the indoor fan motor is energized,  
the dampers open up to one of two pre-selected posi-  
tions – regardless of the outdoor air enthalpy. Dampers  
return to the fully closed position when the indoor fan  
motor is de-energized. Dampers shall fully close on  
power loss.  
DISCONNECT SWITCH - A disconnect can be factory  
installed on a cooling only units sized for the largest elec-  
tric heat available.  
STAINLESS STEEL HEAT EXCHANGER – For applica-  
tions in a corrosive environment, this option provides a  
full stainless steel heat exchanger assembly.  
SMOKE DETECTOR – A smoke detector can be factory  
mounted and wired in the supply and/or return air com-  
partments.  
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE  
ROOF CURB - 14” and 8” high, full perimeter knockdown  
curb, with hinged design for quick assembly.  
BAROMETRIC RELIEF DAMPER – (Unit mounted –  
Downflow, Duct Mounted – Horizontal) – Contains a rain  
hood, air inlet screen, exhaust damper and mounting  
hardware. Used to relieve internal air pressure through  
the unit during economizer operation.  
ADDITIONAL FACTORY INSTALLED OPTIONS  
ALTERNATE INDOOR BLOWER MOTOR – For appli-  
cations with high restrictions, units are available with  
optional indoor blower motors that provide higher static  
output and/or higher airflow.  
PROPANE CONVERSION KIT – Contains new orifices  
and gas valve springs to convert from natural to L.P. gas.  
CONVENIENCE OUTLET (POWERED/NON-POWERED)–  
Unit can be provided with an optional 120VAC GFCI outlet  
with cover on the corner of the unit housing the compressors.  
60ºF GAS HEAT KIT – Provides an electric heat kit for  
the gas compartment for use in extreme low ambient  
conditions.  
ELECTRIC HEAT - Electric Heaters range from 9 kW to  
54 kW and are available in all the voltage options of the  
base unit.  
ECONOMIZER (Downflow and Horizontal flow)  
POWER EXHAUST – (Unit mount – Downflow, Duct  
mount – Horizontal flow)  
PHASE MONITOR - Designed to prevent damage in out-  
of-phase condition.  
DUAL ENTHALPY KIT - Provides a second input to  
economizer to monitor return air.  
Subject to change without notice. Printed in U.S.A.  
246646-YTG-C-0606  
Copyright © 2006 by Unitary Products. All rights reserved.  
Supersedes: 246646-YTG-B-1005/036-21059-007-B-1005  
Unitary  
Products  
Group  
5005  
York  
Drive  
Norman  
OK  
73069  

Panasonic Cu E12jkk User Manual
Panasonic Cw C202kr User Manual
Ryobi P103 User Manual
Samsung Mh19vp2 12 User Manual
Sharp Af 06erl User Manual
Toshiba Lf546 User Manual
Toshiba Multifunctional Digital Systems 282 User Manual
Tripp Lite Apsx2012 User Manual
York 12 Seer H Rc018 Thru 060 User Manual
York Affinity Series R 410a User Manual