246646-YTG-C-0606
TECHNICAL
GUIDE
®
DESCRIPTION
ASHRAE 90.1 COMPLIANT
®
®
YORK Predator units are convertible single packages with a
common footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors with
independent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications and
can be easily installed on a roof curb, slab, or frame.
HIGH EFFICIENCY
SINGLE PACKAGE AIR CONDITIONERS AND
SINGLE PACKAGE GAS/ELECTRIC UNITS
®
All Predator units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
DH 078, 090, 102, 120 and 150
6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 NOMINAL TONS
10.0-11.5 EER
All units are convertible between side and down airflow. Inde-
pendent economizer designs are used on side and down dis-
charge applications, as well as all tonnage sizes.
®
Predator units are available in the following configurations:
cooling only, cooling with electric heat, and cooling with gas
heat. Electric heaters are available as factory-installed options
or field-installed accessories.
Tested in accordance with:
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246646-YTG-C-0606
6LPSOLFLW\ꢈ&RQWURO
'LVFRQQHFW ORFDW LRQ
ꢁRSWLRQDO GLVFRQQHFW VZLWFKꢂ
%RDUGꢈZꢇVFUHZ
FRQQHFWRUꢈIRUꢈ7ꢀVWDW
ZLULQJꢈDQGꢈQHWZRUN
FRQQHFWLRQV
)LOWHUꢈDFFHVV
ꢁꢄꢋꢈWKURZꢀDZD\ꢂ
)LOWHUꢈGULHUꢈ
ꢁVROLGꢈFRUHꢂ
7HUPLQDO EORFN I RU
KLꢀYROWDJH FRQQHFWLRQ
&RQGHQVHU VHFWLRQ
6HFRQG PRGHO
QDPHSODWH
LQVLGH KLQJHG
DFFHVV SDQHO
6OLGHꢀRXW PRWRU DQG
EORZHU DVVHPEO\ IRU
HDV\ DGMXVWPHQW DQG
VHUYLFH
%HOWꢀGULYH
EORZHUꢈPRWRU
'XDOꢈVWDJHꢈFRROLQJ
IRUꢈPD[LPXPꢈ
FRPIRUW
3RZHU YHQWRU PRWRU
&RPSUHVVRU ꢆꢄ
ꢄꢅꢀJDXJH DOXPLQL]HG
VWHHO WXEXODU KHDW
H[FKDQJHU IRU ORQJ OLIH
ꢁVWDLQOHVV VWHHO RSWLRQꢂ
DFFHVV ꢁKLJKꢀHIILꢀ
FLHQF\ FRPSUHVVRU
ZꢇFUDQNFDVH KHDWHUꢂ
%DVHꢈUDLOVꢈZꢇIRUNOLIW
7ZRꢀVWDJH JDV
KHDWLQJ WR PDLQWDLQ
ZDUPꢃ FRPIRUWDEOH
WHPSHUDWXUH
6OLGHꢀRXWꢈGUDLQꢈSDQ
ZLWKꢈVWHHOꢈꢉꢇꢊꢋꢈ137ꢃ
)HPDOHꢈFRQQHFWLRQ
VORWVꢈꢁꢉꢈVLGHVꢂꢈDQG
OLIWLQJꢈKROHV
5RRIꢈFXUEVꢈLQꢈHLJKWꢈDQG
&RPSUHVVRUꢈꢆꢌꢈDFFHVV
ꢁKLJKꢀHIILFLHQF\ꢈFRPSUHVVRU
ZꢇFUDQNFDVHꢈKHDWHUꢂ
IRXUWHHQꢈLQFKꢈKHLJKWVꢍꢈ
5RRIꢈFXUEVꢈIRUꢈ
,QWHOOLJHQW
FRQWUROꢈERDUG
IRUꢈVDIHꢈDQG
HIILFLHQW
6LGHꢈHQWU\ꢈSRZHU
7RROꢀOHVVꢈ
GRRUꢈODWFK
DQGꢈFRQWUROꢈZLULQJ
NQRFNRXWV
WUDQVLWLRQLQJꢈIURPꢈ
<RUNꢈ6XQOLQHꢈIRRWSULQW
WRꢈWKHꢈ')ꢈ6HULHVꢈIRRWSULQWV
DUHꢈDOVRꢈDYDLODEOH
RSHUDWLRQ
ꢁILHOGꢀLQVWDOOHGꢈDFFHVVRU\ꢂ
®
FIGURE 1 - PREDATOR COMPONENT LOCATION (DH120 SHOWN)
FEATURES
•
High Efficiency – High efficiency units reach as high as
11.5 EER. Gas/electric units have electronic spark igni-
tion and power vented combustion with steady state effi-
ciencies of 80%. These efficiencies exceed all legislated
minimum levels and provide low operating costs.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access
to the condenser coils for cleaning or inspection.
Both the unit control board and ignition control board uti-
lize flash codes to aid in diagnosis of unit malfunctions.
Unique alarm codes quickly identify the source of the
unit alarm.
®
•
Service Friendly – The Predator incorporates a num-
ber of enhancements which improve serviceability.
All units use the same standard filter size. This standard-
ization removes any confusion on which filter sizes are
needed for replacement.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
The non-corrosive drain pan slides out of the unit to per-
mit easy cleaning. The drain pan is accessed by remov-
ing the drain pan cover plate on the rear of the unit. Once
the plate is removed, the drain pan slides out through the
rear of the unit.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to
frequently inspected components and areas, including
the control box, compressors, filters, indoor motor &
blower, and the heating section. The panels are screwed
in place at the factory to prevent access by children or
other unauthorized persons. It is recommended that the
panels be secured with screws once service is complete.
®
All Predator units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
Unitary Products Group
3
246646-YTG-C-0606
•
•
Environmentally Aware – For improved Indoor Air
Quality, foil faced insulation is used exclusively through-
out the units.
low-pressure switches and the freezestats must trip
three times within two hours before the unit control
board will lock out the associated compressor.
®
Balanced Heating – The Predator offers “Ultimate Heat-
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained
through the loss of power.
st
nd
ing Comfort” with a balance between 1 and 2 stage
®
gas heating. The first stage of a gas heat Predator unit
provides 60% of the heating capacity. Balanced heating
allows the unit to better maintain desired temperatures.
•
•
Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two
side duct covers from the outside of the unit and installs
them over the down shot openings. No panel cutting is
required. Convertible airflow design allows maximum
field flexibility and minimum inventory.
•
•
Reliable – From the beginning – All units undergo com-
puter automated testing before they leave the factory.
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term –
System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frost-
ing when the economizer operates at low outdoor air tem-
peratures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and low-
pressure switches. Internal compressor protection is stan-
dard on all compressors. Crankcase heaters are standard
on reciprocating compressors. Scroll compressors do not
require crankcase heaters. Phase Monitors are standard
on units with scroll compressors. This accessory monitors
the incoming power to the unit and protects the unit from
phase loss and reversed phase rotation.
®
All Predator units are painted with a long lasting, pow-
der paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
®
To further simplify planning and installation, Predator
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
•
Advanced Controls - S implicity™ control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
The drain pan can be rotated to drain to either the front
or the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down
to 0°F outdoor ambient without additional assistance.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air tem-
perature is low or when free cooling is available.
•
•
Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
•
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the
standard controls. Compressor reliability is further
ensured by programmable minimum run times. For
testing, the anti-short cycle delay can be temporarily
overridden with the push of a button.
Easy Installation – Gas and electric utility knockouts are
supplied in the unit underside as well as the side of the unit.
A clearly identified location is provided to mount a field sup-
plied electrical disconnect switch. Utility connections can be
made quickly and with a minimum amount of field labor.
•
•
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling
fan delay times are independent of one another. All
units are programmed with default values based
upon their configuration of cooling and heat.
All units are shipped with 2” throw-away filters installed.
•
•
Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to han-
dle most airflow requirements. For high static applica-
tions, factory installed alternate indoor fan motors are
available. With the optional indoor fan motor, all units can
supply nominal airflow at a minimum of 1.5” ESP.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit con-
trol board will alarm on ignition failures, compressor
lockouts and repeated limit switch trips.
Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty. Aluminized steel
and stainless steel tubular heat exchangers carry a 10-
year warranty.
•
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a
“three times, you’re out” philosophy. The high and
4
Unitary Products Group
246646-YTG-C-0606
input, the economizer control monitors outdoor air. The
dual enthalpy kit provides a second input used to mon-
itor the return air. With a dual input kit installed, the
economizer control compares the values of the two
enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
FACTORY INSTALLED OPTIONS
®
YORK offers several equipment options factory installed, for
®
the Predator line.
•
Optional Factory Installed Economizers - Predator units
offer a variety of optional factory installed economizers with
low leak dampers. The outdoor air enthalpy sensor enables
economizer operation if the outdoor enthalpy is less than
the setpoint of the economizer logic module. See Table 41
to determine the correct economizer for your application.
•
•
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
•
Downflow Economizer - (With barometric relief) -
The economizer is provided with a single enthalpy
input. The economizer is 2% low leakage type, and is
shipped installed and wired. The installer needs only
to assemble and mount the outdoor air hood (Pro-
vided). The economizer has spring return, fully modu-
lating damper actuators and is capable of introducing
up to 100% outdoor air. As the outdoor air intake
dampers open, the return air dampers close. The
changeover from mechanical refrigeration to econo-
mizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry
bulb available. To meet regulated air standards, the
•
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
•
•
Aluminized Steel Gas Heat Exchanger - For applica-
tions in non-corrosive environments.
Stainless Steel Gas Heat Exchanger - For applications
in corrosive environments, this option provides a full
stainless steel heat exchanger assembly.
economizer control accepts an optional CO input for
2
demand ventilation. With single enthalpy input, the
economizer control monitors outdoor air. The dual
enthalpy kit provides a second input used to monitor
the return air. With a dual input kit installed, the econ-
omizer control compares the values of the two
enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
•
Stainless Steel Drain Pan - An optional rust-proof stain-
less steel drain pan is available to provide years of trou-
ble-free operation in corrosive environments.
•
Electric Heaters - The electric heaters range from 9kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
•
•
Horizontal Economizer - (Without barometric
relief) - All features of the downflow economizer
exist except you must order the duct mount baro-
metric relief separately. You must order a 1EH0408
if you are installing a power exhaust. You can
order a 1RD0411 Barometric Relief for horizontal
flow economizers only.
•
•
Disconnect Switch - For gas heat units and cooling
units with electric heat, a HACR breaker sized to the unit
is provided. For cooling only units, a switch sized to the
largest electric heat available for the particular unit is
provided. Factory installed option only.
Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with
cover, on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source
and wiring. The “Powered” option is powered by a step-
down transformer in the unit. Factory installed option only.
BAS Ready Economizer -(With barometric relief) -
The economizer is provided with a Belimo actuator
that requires a 0-10V DC input from an external
source (i.e., field installed building automation system
controller). Power exhaust options are available. The
economizer is 2% low leakage type with spring return
and fully modulating dampers capable of introducing
up to 100% outside air. Also include 2” pleated filters.
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
•
Slab Economizer for Energy Recovery Ventilators-
(With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input.
The economizer is 2% low leakage type, and is
shipped installed and wired. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air damp-
ers close. The changeover from mechanical refrigera-
tion to economizer operation is regulated by the
standard single enthalpy input. There is an optional
input dual dry bulb available. To meet regulated air
standards, the economizer control accepts an optional
Factory installed smoke detectors in the return air,
may be subjected to freezing temperatures during
"off" times due to out side air infiltration. These
smoke detectors have an operational limit of 32 °F
to 131°F. Smoke detectors installed in areas that
could be out side those limitations will have to be
moved to prevent having false alarms.
CO input for demand ventilation.With single enthalpy
2
Unitary Products Group
5
246646-YTG-C-0606
•
•
Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
supply air sensor, return air sensor, dirty filter indicator
switch, and air proving switch.
•
•
Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally,
this kit stops animals and foreign objects from entering
the space between the inner condenser coil and the
main cabinet. This is not a hail guard kit.
CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building auto-
mation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
•
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option
or field installed accessory.
•
Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
•
•
•
Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
FIELD INSTALLED ACCESSORIES
Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against cor-
rosion due to harsh environments.
®
YORK offers several equipment accessories for field instal-
®
lation, for the Predator line.
•
Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the econo-
BAS - Building Automation System Controls S implic-
ity™ INTELLI-Comfort™ Control - The York® S implic-
ity™ INTELLI-Comfort™ control is factory installed. It
includes a supply air sensor, a return air sensor, and an
outside air sensor. There are provisions for a field
installed dirty filter indicator switch, an air-proving switch,
an Outside Air Humidity sensor, a Return Air Humidity
sensor, an Inside IAQ sensor, and an Outside Air IAQ
sensor. Construction mode operation, 365-day real time
clock with 7 day programming plus holiday scheduling is
built-in. Two different modes of demand ventilation are
mizer control accepts an optional CO input for demand
2
achieved through the INTELLI-Comfort™ using CO
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit pro-
vides a second input used to monitor the return air. With
a dual input kit installed, the economizer control com-
pares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maxi-
mum efficiency possible
2
sensors. It uses an inside CO sensor to perform
2
Demand Ventilation. It can also use an Outside CO sen-
2
sor to perform Differential Demand Ventilation. It uses a
Patented Comfort Ventilation algorithm to provide com-
fortable ventilation air temperature. The patented econo-
mizer-loading algorithm will protect the equipment when
harsh operating conditions exist. Humidity in the occu-
pied space or return duct can be monitored and con-
trolled via humidity sensors and the on-board connection
for hot gas re-heat system. It uses the INTELLI-Start™
algorithm to maximize energy savings by recovering the
building from the Unoccupied Setpoints to the Occupied
Setpoints just in time for the Occupied Time Period to
begin. The S implicity™ INTELLI-Comfort™ balances
•
•
Horizontal Economizer - (Without barometric relief) -
All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizer.
Slab Economizer for Energy Recovery Ventilator-
(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the econo-
space temperature, ventilation air temperature, CO and
2
humidity for ultimate comfort.
•
•
S implicity™ INTELLI-Comfort™ with ModLINC
Control - The York® S implicity™ INTELLI-Comfort™
with ModLINC control is factory installed. It includes all
the features of the INTELLI-Comfort™ control with an
additional control to translate communications from
MODBUS to the BACnet MSTP protocol.
Novar® BAS Control - The Novar® ETC-3 building
automation system controller is factory installed. Incudes
mizer control accepts an optional CO input for demand
2
6
Unitary Products Group
246646-YTG-C-0606
ventilation.With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit pro-
vides a second input used to monitor the return air. With
a dual input kit installed, the economizer control com-
pares the values of the two enthalpy or temperature
inputs and positions the dampers to provide the maxi-
mum efficiency possible.
•
-60°F Gas Heat Kit - For installations which require gas
heat units to perform in low ambient temperatures, a gas
section heating kit is available. This kit provides electric
heat in the gas heat controls section to ensure the gas
valve and controls will continue to function properly at
extremely low temperatures.
•
•
Gas Heat High Altitude Kit - This kit converts a gas
heat unit to operate at high altitudes, 2,000 to 6,000 feet.
Conversion kits are available for natural gas and pro-
pane.
You can order 1EH0409 Barometric Relief/FA Hood
for field installations without an ERV.
•
•
•
Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
Gas Heat Propane Conversion Kit - This kit converts a
gas-fired heater from natural gas to propane. It contains
the main burner orifices and gas valve replacement
springs.
Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
•
•
Gas Piping Kit - Contains pipe nipples, fittings and gas
cock required for gas supply connection with external
shut off.
Power Exhaust - This accessory installs in the unit with
a down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a hori-
zontal flow application.
Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. Cooling units
include an adapter panel for easy installation of the elec-
tric heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
•
•
Manual Outdoor Air Damper - Like the motorized out-
door air damper, each manual outdoor air damper
includes a slide-in damper assembly with an outdoor air
hood and filters. Customers have a choice of dampers
with ranges of 0% to 100% or 0% to 35% outdoor air
entry.
•
Low Limit / Compressor Lockout Kit
1. Compressor Lockout (CLO): To prevent mechani-
cal (compressorized) operation of the unit during
cold outdoor conditions where there is a risk of
returning liquid refrigerant back to the compressors.
Motorized Outdoor Air Damper - The motorized out-
door air damper includes a slide-in/plug-in damper
assembly with an outdoor air hood and filters. The out-
door air dampers open to the preset position when the
indoor fan motor is energized. The damper has a range
of 0% to 100% outdoor air entry. Factory installed option
or field installed accessory.
2. Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing
the units first stage heating means when there is a
demand for cooling during cold outside conditions.
•
•
•
Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
•
Metal Frame Filter Kit - Metal frame with polyester filter
medium.
•
•
Permanent Filters - Permanent filters are available.
CO Sensor - Senses CO levels and automatically
2
2
Roof Curbs - The roof curbs have insulated decks and
are shipped disassembled The roof curbs are available
in 8” and 14” heights. For applications with security con-
cerns, burglar bars are available for the duct openings of
the roof curbs.
overrides the economizer when levels rise above the
preset limits.
Dirty Filter Switch - This kit includes a differential pres-
sure switch that energizes the fault light on the unit ther-
mostat, indicating that there is an abnormally high
pressure drop across the filters.
•
Roof Curb Transition - Single Piece Adapter (10” High)
- Roof curbs for transitioning from Sunline™ units to
®
•
•
Coil Guard - Field installed decorative wire coil guard.
Predator units. Fits 7.5 to 12.5 Sunline™ roof curbs
only.
Hail Guard - This kit includes a sloped hood which
installs over the outside condenser coil and prevents
damage to the coil fins from hail strikes. Field installed
accessory only.
•
•
Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24-
volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with two-
stage heat/two-stage cool or two-stage cooling only ther-
mostats, depending upon unit configuration.
•
Flue Exhaust Extension Kit - In locations with wind or
weather conditions which may interfere with proper
exhausting of furnace combustion products, this kit can
be installed to prevent the flue exhaust from entering
nearby fresh air intakes.
Unitary Products Group
7
246646-YTG-C-0606
TABLE 1: ACCESSORIES
Part Number
Description
Weight
1RC0470
Roof Curb, 8" Height
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
1RC0471
Roof Curb, 14" Height
1RC0472
Roof Curb, Transition (7.5 T through 12.5 T)
Burglar Bars, Downflow
1BD0408
2TP04520925
2TP04521825
2TP04522425
2TP04523625
2TP04525425
2TP04520946
2TP04521846
2TP04522446
2TP04523646
2TP04525446
2TP04520958
2TP04521858
2TP04522458
2TP04523658
2TP04525458
2TP04540925
2TP04541825
2TP04542425
2TP04543625
2TP04540946
2TP04541846
2TP04542446
2TP04543646
2TP04540958
2TP04541858
2TP04542458
2TP04543658
1FA0411
Electric Heat 9kW 230V
Electric Heat 18kW 230V
Electric Heat 24kW 230V
Electric Heat 36kW 230V
Electric Heat 54kW 230V
Electric Heat 9kW 460V
Electric Heat 18kW 460V
Electric Heat 24kW 460V
Electric Heat 36kW 460V
Electric Heat 54kW 460V
Electric Heat 9kW 575V
Electric Heat 18kW 575V
Electric Heat 24kW 575V
Electric Heat 36kW 575V
Electric Heat 54kW 575V
Electric Heat 9kW 230V, 42" Tall Cabinet
Electric Heat 18kW 230V, 42" Tall Cabinet
Electric Heat 24kW 230V, 42" Tall Cabinet
Electric Heat 36kW 230V, 42" Tall Cabinet
Electric Heat 9kW 460V, 42" Tall Cabinet
Electric Heat 18kW 460V, 42" Tall Cabinet
Electric Heat 24kW 460V, 42" Tall Cabinet
Electric Heat 36kW 460V, 42" Tall Cabinet
Electric Heat 9kW 575V, 42" Tall Cabinet
Electric Heat 18kW 575V, 42" Tall Cabinet
Electric Heat 24kW 575V, 42" Tall Cabinet
Electric Heat 36kW 575V, 42" Tall Cabinet
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
1FA0412
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
Economizer, Downflow (Incl. Barometric Relief & All Hoods)
-
-
2MD04702724
2MD04703324
2EE04705424
2EE04705524
2EE04705224
2EE04705624
2PE04703225
2PE04703246
2PE04703258
2EC04700924
1EH0407
124 lbs.
97 lbs.
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief)
"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet
Power Exhaust, Downflow, 230V (For Units with Economizer only)
Power Exhaust, Downflow, 460V(For Units with Economizer only)
Power Exhaust, Downflow, 580V (For Units with Economizer only)
Dual Enthalpy Control (Use with Single Enthalpy Economizer)
-
-
-
-
-
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)
CO2 Detector Unit Mount
1RD0411
1EH0408
25 lbs.
1EH0409
-
-
-
-
2AQ04700424
2AQ04700324
2SD04700424
2MK04700624
1CG0419
CO2 Detector Space Mount
Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer)
Low Limit / Compressor Lockout Kit
Coil Guard (Electric / Electric & HP models)
-
8
Unitary Products Group
246646-YTG-C-0606
TABLE 1: ACCESSORIES (CONTINUED)
Part Number
Description
Weight
1CG0420
1CG0427
1CG0428
1HG0411
1HG0415
1GP0405
1NP0442
1HA0442
1HA0443
1FE0412
Coil Guard (Gas / Electric models)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
Coil Guard (Electric / Electric & HP Models), 42" Tall Cabinet
Coil Guard (Gas / Electric Models), 42" Tall Cabinet
Hail Guard Kit
Hail Guard Kit, 42" Tall Cabinet
Gas Piping Kit
Propane Conversion Kit
High Altitude Kit for Natural Gas
High Altitude Kit for Propane
Flue Exhaust Extension Kit
2BC04700106
2BC04700151
2BC04700154
1FL0402
Gas Heat Kit, -60 deg F, 230V
Gas Heat Kit, -60 deg F, 460V
Gas Heat Kit, -60 deg F, 575V
Permanent Filter Kit
1FL0423
Permanent Filter Kit, 42" Tall Cabinet
Dirty Filter Switch
2DF0401
1FF0410
Filter Frame Kit, Metal
1FF0411
Metal Filter Frame Kit, 42" Tall Cabinet
Unitary Products Group
9
246646-YTG-C-0606
NOMENCLATURE
®
6.5-12.5 Ton York Model Number Nomenclature
D H 090 N10 A 2 A AA 3 0 1 2 4 A
Product Category
Product Style
D = A/C, Single Pkg., R-22
A = Style A
B = Style B
C = Style C
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
H = 11.0+ EER A/C
SS Drain Pan
CPC Controller, DFS, APS
Nominal Cooling Capacity
Johnson Controller, DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
078 = 6.5 Ton
090 = 7.5 Ton
102 = 8.5 Ton
120 = 10.0 Ton
150 = 12.5 Ton
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
2" Pleated filters
BAS Ready Unit with Belimo Economizer
Shipping Bag
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No heat installed
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Gas Heat Options
Product Generation
N10 = 100 MBH Output Aluminized Steel
N15 = 150 MBH Output Aluminized Steel
N20 = 200 MBH Output Aluminized Steel
S10 = 100 MBH Output Stainless Steel
S15 = 150 MBH Output Stainless Steel
S20 = 200 MBH Output Stainless Steel
3 = Third Generation
4 = Fourth Generation
5 = Fifth Generation
Additional Options
RC = Coil Guard, Shipping Bag & American Flag
TA = Technicoat Condenser Coil
Electric Heat Options
AA = None
AB = Phase Monitor
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
AC = Coil Guard
AD = Dirty Filter Switch
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
Airflow
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
A = Std. Motor
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
N = Hi Static Mtr.
D = Options 1 & 2
E = Option 3
F = Option 4
P = Hi Static Mtr./Econo./Barometric Relief
(Downflow Only)
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
Q = Hi Static Mtr./Econo./Power Exhaust
(Downflow Only)
R = Hi Static Mtr./Motorized Damper (Downflow Only)
S = Hi Static Mtr./Horizontal Economizer (No Baro.)
T = Hi Static Mtr./Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static Mtr./Slab Econo./Barometric Relief
(Downflow only)
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
10
Unitary Products Group
246646-YTG-C-0606
TABLE 2: DH PHYSICAL DATA
Component
Models
102
078
090
120
150
Blower, Centrifugal
12 x 12
12 x 12
12 X 12
15 x 15
15 x 15
(Dia. X Wd. in.)
Motor, Standard (HP)
Motor, Optional (HP)
Rows
Evaporator
Blower
1-1/2
2
2
3
3
3
2
3
3
5
3
3
3
4
4
Fins per Inch
15
15
15
15
40
13.2
15
40
13.2
Evaporator
Coil
Height (in.)
32
32
32
Face Area (ft.2 each)
10.67
10.67
10.67
Propeller Dia.
(in., each)
24
24
24
24
24
Condenser
Fan
(2 per Unit)
Motor (HP, each)
1/3
1/3
1/3
3/4
3/4
CFM, Nominal (each)
3400
3400
3400
4400
4400
Sys 1: 2 Row
Rows (each)
2
2
2
2
Sys 2: 1 Row
Condenser
Coil
(2 per unit)
Fins per Inch
20
36
20
36
20
36
20
44
20
44
Height (in., each)
Face Area (ft.2 each)
System 1 (lb./oz.)
System 2 (lb./oz.)
Quantity
12
12
12
14.5
12/0
11/0
2
14.5
9/14
9/4
8/0
8/12
9/0
2
9/8
8/2
2
Refrigerant
Charge
4/12
2
2
Compressors
Air Filters
Type
Recip.
Recip
Recip.
Recip
Scroll
Size (Wd. x Ht. x
Thickness in.)
25x16x2
4
25x16x2
4
25x16x2
4
25x20x2
4
25x20x2
4
Number Per Unit
Unitary Products Group
11
246646-YTG-C-0606
TABLE 3: DH CAPACITY RATINGS
Cooling Capacity
Nominal
Electric
Heat
Gas Heat Capacity
Seasonal
1
Gas
Line
ARI Ratings
Sound
Rating
Size
Model
(Tons)
CFM
Temp.
Rise
(°F)
Size
(in. OD)
2
3
Input Output
(MBH) (MBH)
(dB)
Capacity
(kW)
MBH EER IPLV
Efficiency
(%)
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
9, 18, 24,
36
078
(6-1/2)
75
11.5
11.5
11.0
11.0
11.90 2421
84
84
84
90
90
Gas Heat
Gas Heat
-
-
120
180
96
80
80
20-50
35-65
3/4
3/4
144
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
090
(7-1/2)
18, 36
89
12.0
3000
Gas Heat
Gas Heat
-
-
120
180
96
80
80
15-45
30-60
3/4
3/4
144
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
9, 18, 24,
36
102
(8-1/2)
99
11.50 2692
Gas Heat
Gas Heat
-
-
120
180
96
80
80
15-45
30-60
3/4
3/4
144
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
18, 24, 36,
54
120
(10)
115
11.70 3840
Gas Heat
Gas Heat
-
-
180
240
144
192
80
80
20-50
35-65
3/4
3/4
Cooling
Only
-
-
-
-
-
-
-
-
-
-
-
Electric
Heat
18, 24, 36,
54
150
(12-1/2)
146
10.0 10.70 4100
Gas Heat
Gas Heat
-
-
180
240
144
192
80
80
10-40
25-55
3/4
3/4
1
2
3
Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb.
Rated in accordance with ARI 270 standard.
See Table 20.
TABLE 4: UNIT VOLTAGE LIMITATIONS
POWER RATING
208/230-3-60
460-3-60
MIN.
187
432
540
MAX.
252
504
575-3-60
630
12
Unitary Products Group
246646-YTG-C-0606
TABLE 5: COOLING CAPACITY DH078 (6-1/2 TON) UNIT
Air On
Temperature of Air on Condenser Coil 75°F
Evap. Coil
Temperature of Air on Condenser Coil 85°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Sensible Capacity (MBH)*
Tot.
Tot.
Cap.1 Input2
(MBH)
Tot.
Tot.
Cap.1
(MBH)
WB
(°F)
Input2
Return Dry Bulb (°F)
CFM
1950
2275
2600
2925
3250
(kW)
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
88.9
85.5
80.0
78.2
91.3
87.9
82.2
80.4
93.8
90.2
84.4
82.6
94.5
90.9
85.0
83.1
95.1
91.5
85.6
83.7
4.8
4.8
4.7
4.7
4.8
4.8
4.7
4.7
4.8
4.8
4.8
4.7
4.8
4.8
4.8
4.7
4.9
4.8
4.8
4.7
51.3 45.8 40.2 34.6 29.1
-
-
84.6
79.8
74.2
73.1
87.1
82.2
76.4
75.2
89.6
84.5
78.6
77.4
90.5
85.4
79.4
78.2
91.4
86.3
80.2
79.0
5.3
5.2
5.1
5.1
5.3
5.3
5.2
5.2
5.4
5.3
5.2
5.2
5.4
5.3
5.2
5.2
5.4
5.3
5.2
5.2
49.4 43.9 38.3 32.7 27.2
-
-
65.4 59.9 54.3 48.7 43.2 37.6 32.1
80.0 73.8 68.2 62.7 57.1 51.5 46.0
78.2 76.8 71.3 65.7 60.2 54.6 49.0
62.9 57.4 51.8 46.2 40.7 35.1 29.6
74.2 69.8 64.3 58.7 53.1 47.6 42.0
73.1 71.6 66.0 60.5 54.9 49.4 43.8
56.3 49.7 43.2 36.6 30.0
-
-
54.5 47.9 41.4 34.8 28.2
-
-
71.4 64.9 58.3 51.7 45.1 38.6 32.0
82.2 79.1 73.3 66.7 60.1 53.5 47.0
80.4 79.7 76.5 70.0 63.4 56.8 50.3
69.1 62.5 56.0 49.4 42.8 36.2 29.7
76.4 74.2 69.4 62.8 56.3 49.7 43.1
75.2 74.5 71.3 64.8 58.2 51.6 45.0
61.3 53.7 46.1 38.5 30.9
-
-
59.6 52.0 44.4 36.9 29.3
-
-
77.4 69.9 62.3 54.7 47.1 39.5 31.9
84.4 84.4 78.3 70.7 63.1 55.5 47.9
82.6 82.6 81.8 74.2 66.6 59.1 51.5
75.3 67.7 60.1 52.5 44.9 37.4 29.8
78.6 78.6 74.6 67.0 59.4 51.8 44.2
77.4 77.4 76.6 69.0 61.5 53.9 46.3
65.3 56.6 48.0 39.4 30.7
-
-
63.7 55.1 46.5 37.8 29.2
-
-
83.2 73.5 64.8 56.2 47.6 38.9 30.3
85.0 85.0 82.0 73.3 64.7 56.0 47.4
83.1 83.1 82.8 74.1 65.5 56.9 48.2
80.1 71.5 62.8 54.2 45.6 36.9 28.3
79.4 79.4 77.4 68.8 60.1 51.5 42.9
78.2 78.2 77.8 69.2 60.5 51.9 43.3
69.3 59.6 49.9 40.2 30.5
-
-
67.8 58.2 48.5 38.8 29.1
-
-
88.9 77.1 67.4 57.7 48.0 38.3 28.6
85.6 85.6 85.6 75.9 66.3 56.6 46.9
83.7 83.7 83.7 74.0 64.4 54.7 45.0
84.9 75.2 65.6 55.9 46.2 36.5 26.8
80.2 80.2 80.2 70.6 60.9 51.2 41.5
79.0 79.0 79.0 69.3 59.6 49.9 40.2
Temperature of Air on Condenser Coil 95°F
Temperature of Air on Condenser Coil 105°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
80.3
74.1
68.5
68.0
82.8
76.5
70.7
70.1
85.4
78.8
72.9
72.2
86.5
79.9
73.9
73.2
87.7
81.0
74.9
74.2
5.8
5.7
5.6
5.6
5.8
5.7
5.6
5.6
5.9
5.8
5.7
5.7
5.9
5.8
5.7
5.7
5.9
5.8
5.7
5.7
47.5 42.0 36.4 30.8 25.3
-
-
74.6
67.4
63.3
63.0
76.8
69.4
65.2
64.8
78.9
71.3
67.0
66.6
80.0
72.3
67.9
67.5
81.0
73.2
68.8
68.4
6.3
6.1
6.0
6.1
6.3
6.2
6.1
6.1
6.4
6.2
6.1
6.2
6.4
6.3
6.2
6.2
6.4
6.3
6.2
6.2
45.1 39.6 34.0 28.5 22.9
-
-
60.4 54.9 49.3 43.7 38.2 32.6 27.1
68.5 65.8 60.3 54.7 49.2 43.6 38.0
68.0 66.4 60.8 55.2 49.7 44.1 38.6
57.6 52.1 46.5 40.9 35.4 29.8 24.3
63.3 60.8 55.2 49.7 44.1 38.6 33.0
63.0 61.2 55.6 50.1 44.5 39.0 33.4
1950
2275
2600
2925
3250
52.7 46.2 39.6 33.0 26.4
-
-
50.2 43.7 37.1 30.5 23.9
-
-
66.8 60.2 53.6 47.0 40.5 33.9 27.3
70.7 69.4 65.6 59.0 52.4 45.8 39.3
70.1 69.3 66.1 59.6 53.0 46.4 39.8
63.0 57.3 50.7 44.1 37.6 31.0 24.4
65.2 63.9 60.2 53.7 47.1 40.5 33.9
64.8 63.9 60.7 54.1 47.5 40.9 34.4
57.9 50.4 42.8 35.2 27.6
-
-
55.3 47.7 40.2 32.6 25.0
-
-
73.1 65.5 57.9 50.4 42.8 35.2 27.6
72.9 72.9 70.8 63.2 55.7 48.1 40.5
72.2 72.2 71.5 63.9 56.3 48.7 41.1
68.5 62.5 54.9 47.3 39.7 32.2 24.6
67.0 67.0 65.2 57.6 50.1 42.5 34.9
66.6 66.6 65.7 58.1 50.5 42.9 35.3
62.2 53.6 44.9 36.3 27.6
-
-
59.6 50.9 42.3 33.7 25.0
-
-
77.0 69.5 60.8 52.2 43.6 34.9 26.3
73.9 73.9 72.8 64.2 55.6 46.9 38.3
73.2 73.2 72.8 64.2 55.6 46.9 38.3
70.8 66.0 57.8 49.2 40.6 31.9 23.3
67.9 67.9 67.0 58.4 49.7 41.1 32.5
67.5 67.5 67.0 58.4 49.7 41.1 32.5
66.4 56.7 47.1 37.4 27.7
-
-
63.8 54.1 44.4 34.8 25.1
-
-
81.0 73.4 63.7 54.0 44.4 34.7 25.0
74.9 74.9 74.9 65.2 55.5 45.8 36.1
74.2 74.2 74.2 64.5 54.9 45.2 35.5
73.2 69.4 60.8 51.1 41.4 31.7 22.0
68.8 68.8 68.8 59.1 49.4 39.7 30.0
68.4 68.4 68.4 58.7 49.0 39.3 29.6
Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
69.0
60.7
58.2
58.0
70.7
62.3
59.6
59.4
72.5
63.8
61.1
60.9
73.4
64.6
61.9
61.7
74.3
65.5
62.7
62.5
6.8
6.6
6.5
6.6
6.8
6.7
6.6
6.7
6.9
6.7
6.6
6.7
6.9
6.7
6.7
6.7
7.0
6.8
6.7
6.8
42.8 37.2 31.6 26.1 20.5
-
-
63.3
54.0
53.0
53.0
64.6
55.2
54.1
54.1
66.0
56.3
55.3
55.3
66.8
57.0
55.9
55.9
67.6
57.7
56.6
56.6
7.3
7.1
7.0
7.1
7.4
7.1
7.1
7.2
7.4
7.2
7.1
7.2
7.5
7.2
7.1
7.3
7.5
7.3
7.2
7.3
40.4 34.8 29.2 23.7 18.1
-
-
54.8 49.3 43.7 38.2 32.6 27.0 21.5
58.2 55.8 50.2 44.7 39.1 33.5 28.0
58.0 56.0 50.5 44.9 39.3 33.8 28.2
52.0 46.5 40.9 35.4 29.8 24.2 18.7
53.0 50.7 45.2 39.6 34.1 28.5 23.0
53.0 50.9 45.3 39.7 34.2 28.6 23.1
1950
2275
2600
2925
3250
47.7 41.2 34.6 28.0 21.4
-
-
45.2 38.7 32.1 25.5 18.9
-
-
59.3 54.4 47.8 41.2 34.7 28.1 21.5
59.6 58.5 54.9 48.3 41.8 35.2 28.6
59.4 58.5 55.2 48.6 42.0 35.5 28.9
55.2 51.5 44.9 38.3 31.8 25.2 18.6
54.1 53.0 49.6 43.0 36.4 29.9 23.3
54.1 53.1 49.7 43.1 36.6 30.0 23.4
52.7 45.1 37.5 30.0 22.4
-
-
50.1 42.5 34.9 27.3 19.8
-
-
63.8 59.5 51.9 44.3 36.7 29.1 21.6
61.1 61.1 59.6 52.0 44.4 36.9 29.3
60.9 60.9 59.9 52.3 44.7 37.2 29.6
56.3 56.3 48.9 41.3 33.7 26.1 18.5
55.3 55.3 54.0 46.4 38.8 31.2 23.7
55.3 55.3 54.1 46.5 39.0 31.4 23.8
57.0 48.3 39.7 31.0 22.4
-
-
54.3 45.7 37.1 28.4 19.8
-
-
64.6 62.5 54.8 46.2 37.6 28.9 20.3
61.9 61.9 61.2 52.5 43.9 35.2 26.6
61.7 61.7 61.2 52.6 43.9 35.3 26.7
57.0 57.0 51.8 43.2 34.6 25.9 17.3
55.9 55.9 55.3 46.7 38.0 29.4 20.8
55.9 55.9 55.4 46.7 38.1 29.5 20.8
61.2 51.5 41.8 32.1 22.4
-
-
58.6 48.9 39.2 29.5 19.8
-
-
65.5 65.5 57.8 48.1 38.4 28.7 19.0
62.7 62.7 62.7 53.0 43.3 33.6 23.9
62.5 62.5 62.5 52.8 43.1 33.4 23.7
57.7 57.7 54.8 45.1 35.5 25.8 16.1
56.6 56.6 56.6 46.9 37.2 27.6 17.9
56.6 56.6 56.6 46.9 37.2 27.6 17.9
1
2
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group
13
246646-YTG-C-0606
TABLE 6: COOLING CAPACITY DH090 (7-1/2 TON) UNIT
Air On
Temperature of Air on Condenser Coil 75°F
Evap. Coil
Temperature of Air on Condenser Coil 85°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Cap.1 Input2
(MBH)
Tot.
Tot.
Cap.1 Input2
(MBH)
Tot.
WB
(°F)
CFM
2250
2625
3000
3375
3750
(kW)
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
102.7
98.7
95.0
5.7
5.6
5.6
5.5
5.7
5.6
5.6
5.5
5.7
5.6
5.6
5.5
5.7
5.6
5.6
5.5
5.7
5.6
5.6
5.5
60.1
75.6
95.0
96.7
65.5
82.0
97.2
98.9
70.9
88.3
99.4
53.7
69.2
87.3
90.6
57.9
74.4
93.4
95.9
62.1
79.5
99.4
47.3 40.9 34.5
-
-
98.5
93.0
88.7
88.4
100.9
95.2
90.8
90.5
103.2
97.4
92.9
92.6
104.6
98.7
94.2
93.9
106.0
6.2
6.1
6.1
6.0
6.2
6.1
6.1
6.1
6.3
6.2
6.1
6.1
6.3
6.2
6.1
6.1
6.3
6.2
6.1
6.1
58.2 51.8 45.4 39.0 32.5
-
-
62.8 56.4 50.0 43.5 37.1
80.9 74.5 68.0 61.6 55.2
84.1 77.7 71.3 64.9 58.5
73.4 67.0 60.5 54.1 47.7 41.3 34.9
88.7 82.4 76.0 69.6 63.2 56.8 50.4
88.4 84.3 77.9 71.5 65.0 58.6 52.2
96.7
105.1
101.0
97.2
50.3 42.8 35.2
-
-
63.8 56.2 48.6 41.1 33.5
-
-
66.8 59.2 51.6 44.0 36.5
86.1 78.5 70.9 63.3 55.7
89.6 82.0 74.4 66.8 59.2
53.4 44.6 35.9
70.8 62.0 53.3 44.5 35.8
91.2 82.5 73.8 65.0 56.3
80.1 72.5 64.9 57.3 49.7 42.2 34.6
90.8 87.7 81.5 73.9 66.3 58.8 51.2
90.5 88.5 83.5 75.9 68.3 60.7 53.2
98.9
107.5
103.3
99.4
-
-
69.4 60.7 51.9 43.2 34.4
-
-
86.8 78.0 69.3 60.5 51.8 43.0 34.3
92.9 92.9 87.0 78.2 69.5 60.7 52.0
92.6 92.6 89.1 80.3 71.6 62.8 54.1
101.2
108.5
104.3
100.4
102.2
109.6
105.4
101.4
103.3
101.2 101.2 95.0 86.2 77.5 68.7 60.0
75.3
94.8
100.4 100.4 95.9 85.9 76.0 66.0 56.0
102.2 102.2 99.1 89.2 79.2 69.2 59.3
79.8
101.3 87.3
101.4 101.4 100.5 89.4 78.2 67.0 55.8
103.3 103.3 103.3 92.1 80.9 69.7 58.6
65.4
83.4
55.4 45.4 35.5
73.5 63.5 53.6 43.6 33.6
-
-
74.2 64.3 54.3 44.3 34.4
-
-
92.4 82.4 72.5 62.5 52.5 42.6 32.6
94.2 94.2 91.0 81.0 71.0 61.1 51.1
93.9 93.9 92.1 82.1 72.2 62.2 52.3
68.6
57.4 46.2 35.1
76.2 65.0 53.8 42.6 31.5 100.1
-
-
79.0 67.9 56.7 45.5 34.3
-
-
98.0 86.8 75.6 64.5 53.3 42.1 30.9
95.4 95.4 95.0 83.8 72.6 61.4 50.3
95.1 95.1 95.1 83.9 72.8 61.6 50.4
95.4
95.1
Temperature of Air on Condenser Coil 95°F
Temperature of Air on Condenser Coil 105°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
94.3
87.3
82.4
80.1
96.6
89.4
84.4
82.1
98.9
91.5
86.4
84.0
100.6
93.1
87.9
85.5
102.4
94.7
89.4
87.0
6.7
6.7
6.5
6.5
6.8
6.7
6.6
6.6
6.8
6.7
6.6
6.6
6.9
6.8
6.7
6.6
6.9
6.8
6.7
6.7
56.3
71.1
82.4
80.1
62.1
78.2
84.4
82.1
67.9
85.2
86.4
84.0
73.1
90.0
87.9
85.5
78.3
94.7
89.4
87.0
49.8
64.7
77.6
78.0
54.5
70.6
82.0
81.0
59.2
76.5
86.4
84.0
63.2
81.4
87.9
85.5
67.1
86.3
89.4
87.0
43.4 37.0 30.6
-
-
87.5
79.7
76.0
74.0
89.8
81.8
78.0
75.9
92.1
83.8
80.0
77.8
93.4
85.1
81.2
79.0
94.8
86.4
82.4
80.2
7.3
7.2
7.1
7.1
7.4
7.2
7.1
7.1
7.4
7.3
7.2
7.2
7.4
7.3
7.2
7.2
7.5
7.3
7.2
7.2
53.7 47.2 40.8 34.4 28.0
-
-
58.3 51.9 45.5 39.1 32.7
71.2 64.8 58.4 51.9 45.5
71.6 65.2 58.8 52.4 46.0
67.8 61.4 55.0 48.6 42.2 35.8 29.4
76.0 71.7 65.3 58.9 52.4 46.0 39.6
74.0 72.0 65.6 59.2 52.7 46.3 39.9
2250
2625
3000
3375
3750
46.9 39.4 31.8
-
-
59.6 52.0 44.4 36.8 29.3
-
-
63.0 55.4 47.9 40.3 32.7
76.9 69.4 61.8 54.2 46.6
77.4 69.8 62.2 54.7 47.1
74.3 67.4 59.9 52.3 44.7 37.1 29.5
78.0 75.8 71.0 63.4 55.8 48.3 40.7
75.9 74.9 71.3 63.8 56.2 48.6 41.0
50.5 41.7 33.0
-
-
65.5 56.8 48.0 39.3 30.5
-
-
67.7 59.0 50.2 41.5 32.8
82.7 73.9 65.2 56.4 47.7
83.2 74.4 65.7 57.0 48.2
80.7 73.5 64.7 56.0 47.2 38.5 29.7
80.0 80.0 76.7 68.0 59.2 50.5 41.7
77.8 77.8 77.1 68.3 59.6 50.8 42.1
53.2 43.2 33.3
-
-
70.8 60.8 50.8 40.9 30.9
-
-
71.4 61.5 51.5 41.5 31.6
86.1 76.1 66.1 56.2 46.2
85.1 75.1 65.2 55.2 45.2
83.5 77.8 68.5 58.6 48.6 38.6 28.7
81.2 81.2 79.6 69.6 59.6 49.7 39.7
79.0 79.0 78.6 68.7 58.7 48.7 38.8
55.9 44.8 33.6
-
-
76.0 64.9 53.7 42.5 31.3
-
-
75.1 63.9 52.8 41.6 30.4
89.4 78.2 67.1 55.9 44.7
87.0 75.8 64.6 53.4 42.2
86.4 82.2 72.4 61.2 50.0 38.8 27.6
82.4 82.4 82.4 71.2 60.0 48.9 37.7
80.2 80.2 80.2 69.0 57.8 46.6 35.5
Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
80.6
72.0
69.6
67.8
82.9
74.1
71.6
69.7
85.2
76.1
73.6
71.6
86.2
77.1
74.5
72.5
87.3
78.0
75.4
73.4
7.9
7.7
7.6
7.6
7.9
7.7
7.7
7.7
8.0
7.8
7.7
7.7
8.0
7.8
7.7
7.8
8.1
7.9
7.8
7.8
51.1
64.6
69.6
67.8
57.1
70.3
71.6
69.7
63.1
76.1
73.6
71.6
68.4
77.1
74.5
72.5
73.8
78.0
75.4
73.4
44.6
58.1
65.8
66.0
49.5
64.3
69.7
68.8
54.3
70.4
73.6
71.6
58.5
74.2
74.5
72.5
62.6
78.0
75.4
73.4
38.2 31.8 25.4
-
-
73.7
64.4
63.2
61.6
76.0
66.4
65.2
63.5
78.3
68.4
67.2
65.4
79.0
69.0
67.8
66.0
79.7
69.7
68.4
66.6
8.4
8.2
8.1
8.2
8.5
8.2
8.2
8.2
8.5
8.3
8.2
8.3
8.6
8.4
8.3
8.3
8.7
8.4
8.3
8.4
48.4 42.0 35.6 29.2 22.8
-
-
51.7 45.3 38.9 32.5 26.1
59.4 52.9 46.5 40.1 33.7
59.5 53.1 46.7 40.3 33.9
61.3 54.8 48.4 42.0 35.6 29.2 22.8
63.2 59.9 53.5 47.0 40.6 34.2 27.8
61.6 59.9 53.5 47.1 40.7 34.3 27.8
2250
2625
3000
3375
3750
41.9 34.3 26.7
-
-
54.5 47.0 39.4 31.8 24.2
-
-
56.7 49.1 41.5 34.0 26.4
65.1 57.5 49.9 42.3 34.7
65.3 57.7 50.1 42.5 34.9
66.4 61.1 53.5 46.0 38.4 30.8 23.2
65.2 63.5 59.1 51.6 44.0 36.4 28.8
63.5 62.7 59.2 51.6 44.0 36.4 28.9
45.6 36.8 28.1
-
-
60.6 51.9 43.1 34.4 25.6
-
-
61.7 52.9 44.2 35.4 26.7
70.8 62.0 53.3 44.5 35.8
71.0 62.2 53.5 44.7 36.0
68.4 67.4 58.6 49.9 41.1 32.4 23.6
67.2 67.2 64.8 56.1 47.3 38.6 29.8
65.4 65.4 64.9 56.1 47.4 38.6 29.9
48.5 38.5 28.6
-
-
66.1 56.1 46.1 36.2 26.2
-
-
65.6 55.7 45.7 35.7 25.8
73.1 63.1 53.2 43.2 33.2
72.2 62.2 52.3 42.3 32.3
69.0 69.0 62.7 52.8 42.8 32.8 22.9
67.8 67.8 66.6 56.6 46.7 36.7 26.8
66.0 66.0 65.8 55.8 45.8 35.9 25.9
51.4 40.2 29.1
-
-
71.5 60.3 49.2 38.0 26.8
-
-
69.6 58.4 47.2 36.1 24.9
75.4 64.2 53.0 41.9 30.7
73.4 62.2 51.0 39.9 28.7
69.7 69.7 66.8 55.6 44.5 33.3 22.1
68.4 68.4 68.4 57.2 46.0 34.8 23.7
66.6 66.6 66.6 55.4 44.3 33.1 21.9
1
2
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
14
Unitary Products Group
246646-YTG-C-0606
TABLE 7: COOLING CAPACITY DH102 (8-1/2 TON) UNIT
Air On
Temperature of Air on Condenser Coil 75°F
Evap. Coil
Temperature of Air on Condenser Coil 85°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Sensible Capacity (MBH)*
Tot.
Tot.
Cap.1 Input2
(MBH)
Tot.
Tot.
Cap.1
(MBH)
WB
(°F)
Input2
Return Dry Bulb (°F)
CFM
2550
2975
3400
3825
4250
(kW)
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
117.0
112.1
104.1
104.5
120.7
115.7
107.5
107.8
124.5
119.3
110.8
111.2
125.4
120.2
111.6
112.0
126.3
121.0
112.4
112.8
1.8
1.9
2.0
1.9
4.3
4.3
4.4
4.4
6.8
6.8
6.9
6.8
6.9
6.9
6.9
6.9
6.9
6.9
7.0
6.9
66.8 59.5 52.2 44.9 37.7
-
-
112.5
106.1
98.1
7.6
7.5
7.4
7.4
7.6
7.5
7.4
7.4
7.6
7.5
7.4
7.4
7.7
7.6
7.5
7.5
7.7
7.6
7.5
7.5
64.3 57.0 49.8 42.5 35.2
-
-
85.1 77.8 70.5 63.2 56.0 48.7 41.4
104. 99.2 92.0 84.7 77.4 70.2 62.9
104. 103. 96.0 88.7 81.5 74.2 66.9
82.2 74.9 67.7 60.4 53.1 45.8 38.6
98.1 93.4 86.1 78.8 71.6 64.3 57.0
97.5 96.7 89.4 82.2 74.9 67.6 60.4
97.5
72.7 64.1 55.5 46.9 38.3
-
-
116.0
109.4
101.1
100.6
119.6
112.7
104.2
103.7
120.8
113.9
105.3
104.7
122.1
115.1
106.4
105.8
70.5 61.9 53.3 44.7 36.1
-
-
92.1 83.5 75.0 66.4 57.8 49.2 40.6
107. 105. 97.8 89.2 80.6 72.0 63.4
107. 107. 102. 93.5 84.9 76.3 67.7
89.6 81.0 72.4 63.9 55.3 46.7 38.1
101. 98.8 92.2 83.6 75.0 66.4 57.8
100. 100. 95.8 87.2 78.6 70.0 61.4
78.6 68.7 58.8 48.9 39.0
-
-
76.6 66.7 56.8 46.9 37.0
-
-
99.2 89.3 79.4 69.5 59.6 49.6 39.7
110. 110. 103. 93.7 83.8 73.9 63.9
111. 111. 108. 98.3 88.3 78.4 68.5
97.1 87.1 77.2 67.3 57.4 47.5 37.6
104. 104. 98.3 88.4 78.5 68.6 58.6
103. 103. 102. 92.2 82.3 72.4 62.4
83.4 72.2 60.9 49.6 38.3
-
-
81.8 70.5 59.2 47.9 36.6
-
-
104. 93.5 82.2 70.9 59.6 48.3 37.0
111. 111. 108. 96.7 85.4 74.1 62.8
112. 112. 110. 99.2 87.9 76.6 65.3
103. 91.8 80.5 69.2 57.9 46.6 35.4
105. 105. 102. 91.1 79.8 68.5 57.2
104. 104. 104. 92.7 81.4 70.1 58.8
88.3 75.6 62.9 50.3 37.6
-
-
87.0 74.3 61.6 49.0 36.3
-
-
110. 97.6 85.0 72.3 59.6 46.9 34.3
112. 112. 112. 99.8 87.1 74.4 61.8
112. 112. 112. 100. 87.5 74.8 62.2
109. 96.5 83.8 71.1 58.5 45.8 33.1
106. 106. 106. 93.8 81.1 68.4 55.8
105. 105. 105. 93.2 80.5 67.8 55.2
Temperature of Air on Condenser Coil 95°F
Temperature of Air on Condenser Coil 105°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
108.0
100.0
92.0
13.4
13.1
12.8
12.9
10.9
10.7
10.4
10.5
8.4
8.2
8.0
8.1
8.4
8.3
8.1
8.1
8.4
8.3
8.1
8.1
61.8 54.6 47.3 40.0 32.8
-
-
99.4
90.8
82.0
83.3
102.8
93.9
84.8
86.2
106.2
97.0
87.6
89.1
107.6
98.2
88.8
90.2
108.9
99.5
89.9
91.3
11.5
11.2
11.0
11.1
10.3
10.0
9.8
9.9
9.1
8.9
8.7
8.7
9.1
8.9
8.7
8.8
9.2
8.9
8.8
59.2 52.0 44.7 37.4 30.2
-
-
79.3 72.1 64.8 57.5 50.3 43.0 35.7
92.0 87.5 80.3 73.0 65.7 58.5 51.2
90.5 90.2 82.9 75.6 68.3 61.1 53.8
75.4 68.1 60.8 53.6 46.3 39.0 31.7
82.0 79.8 72.7 65.4 58.2 50.9 43.6
83.3 82.3 75.1 67.8 60.5 53.2 46.0
2550
2975
3400
3825
4250
90.5
111.3
103.1
94.8
68.2 59.7 51.1 42.5 33.9
-
-
65.7 57.2 48.6 40.0 31.4
-
-
87.1 78.5 69.9 61.4 52.8 44.2 35.6
94.8 92.6 86.6 78.0 69.4 60.9 52.3
93.3 93.1 89.5 80.9 72.3 63.7 55.1
83.3 74.7 66.1 57.5 48.9 40.3 31.7
84.8 83.7 79.0 70.4 61.8 53.2 44.6
86.2 85.7 81.5 72.9 64.3 55.7 47.1
93.3
114.7
106.2
97.7
74.6 64.7 54.8 44.9 35.0
-
-
72.3 62.3 52.4 42.5 32.6
-
-
94.9 85.0 75.1 65.2 55.3 45.3 35.4
97.7 97.7 93.0 83.1 73.2 63.3 53.3
96.1 96.1 96.0 86.1 76.2 66.3 56.4
91.2 81.2 71.3 61.4 51.5 41.6 31.7
87.6 87.6 85.2 75.3 65.4 55.5 45.6
89.1 89.1 88.0 78.1 68.1 58.2 48.3
96.1
116.3
107.7
99.1
80.2 68.9 57.6 46.3 35.0
-
-
78.0 66.7 55.4 44.1 32.9
-
-
101. 90.2 78.9 67.6 56.3 45.0 33.7
99.1 99.1 96.7 85.4 74.1 62.8 51.6
97.5 97.5 97.4 86.2 74.9 63.6 52.3
95.0 86.7 75.4 64.1 52.8 41.6 30.3
88.8 88.8 87.6 76.3 65.0 53.7 42.4
90.2 90.2 89.7 78.4 67.1 55.8 44.5
97.5
117.9
109.2
100.5
98.9
85.7 73.0 60.3 47.7 35.0
-
-
83.8 71.1 58.5 45.8 33.1
-
-
108. 95.3 82.7 70.0 57.3 44.7 32.0
100. 100. 100. 87.8 75.1 62.4 49.8
98.9 98.9 98.9 86.2 73.5 60.8 48.2
98.9 92.2 79.5 66.9 54.2 41.5 28.9
89.9 89.9 89.9 77.2 64.6 51.9 39.2
91.3 91.3 91.3 78.7 66.0 53.3 40.7
8.8
Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
90.8
81.6
72.1
76.2
94.3
84.7
74.8
79.1
97.7
87.8
77.6
82.0
98.8
88.8
78.5
82.9
100.0
89.8
79.3
83.8
9.6
9.4
9.2
9.3
9.7
9.4
9.2
9.3
9.8
9.5
9.3
9.4
9.8
9.5
9.4
9.5
9.9
9.6
9.4
9.5
56.6 49.4 42.1 34.8 27.5
-
-
82.2
72.3
62.1
69.0
85.8
75.4
64.8
71.9
89.3
78.6
67.5
74.9
90.1
79.3
68.2
75.6
91.0
80.0
68.8
76.3
7.8
7.5
7.3
7.5
9.1
8.8
8.6
8.8
54.0 46.8 39.5 32.2 24.9
-
-
71.4 64.1 56.8 49.6 42.3 35.0 27.8
72.1 72.1 65.1 57.9 50.6 43.3 36.0
76.2 74.5 67.2 59.9 52.7 45.4 38.1
67.4 60.1 52.9 45.6 38.3 31.0 23.8
62.1 62.1 57.6 50.3 43.0 35.7 28.5
69.0 66.7 59.4 52.1 44.8 37.6 30.3
2550
2975
3400
3825
4250
63.3 54.7 46.1 37.5 28.9
-
-
60.8 52.2 43.6 35.0 26.4
-
-
79.4 70.8 62.2 53.6 45.0 36.4 27.8
74.8 74.8 71.3 62.7 54.1 45.5 36.9
79.1 78.2 73.6 65.0 56.4 47.8 39.2
75.4 66.9 58.3 49.8 41.2 32.6 24.0
64.8 64.8 63.6 55.0 46.4 37.8 29.2
71.9 70.8 65.6 57.0 48.4 39.8 31.3
69.9 60.0 50.0 40.1 30.2
-
-
10.5
10.1
9.9
67.5 57.6 47.7 37.7 27.8
-
-
87.4 77.5 67.6 57.7 47.8 37.8 27.9
77.6 77.6 77.4 67.5 57.6 47.7 37.8
82.0 82.0 79.9 70.0 60.1 50.2 40.3
78.6 73.7 63.8 53.9 44.0 34.1 24.2
67.5 67.5 67.5 59.7 49.8 39.9 30.0
74.9 74.9 71.9 62.0 52.0 42.1 32.2
10.1
10.6
10.2
10.0
10.1
10.6
10.3
10.1
10.2
75.9 64.6 53.3 42.0 30.7
-
-
73.7 62.5 51.2 39.9 28.6
-
-
88.6 83.3 72.0 60.7 49.4 38.1 26.8
78.5 78.5 78.4 67.1 55.8 44.5 33.2
82.9 82.9 81.9 70.6 59.3 48.0 36.7
79.3 79.3 68.5 57.2 46.0 34.7 23.4
68.2 68.2 68.2 57.9 46.6 35.3 24.1
75.6 75.6 74.1 62.8 51.5 40.2 28.9
81.9 69.2 56.6 43.9 31.2
-
-
80.0 67.3 54.7 42.0 29.3
-
-
89.8 89.1 76.4 63.7 51.0 38.4 25.7
79.3 79.3 79.3 66.7 54.0 41.3 28.7
83.8 83.8 83.8 71.2 58.5 45.8 33.2
80.0 80.0 73.2 60.6 47.9 35.2 22.6
68.8 68.8 68.8 56.1 43.5 30.8 18.1
76.3 76.3 76.3 63.7 51.0 38.3 25.6
1
2
These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Unitary Products Group
15
246646-YTG-C-0606
TABLE 8: COOLING CAPACITY DH120 (10 TON) UNIT
Air On
Temperature of Air on Condenser Coil 85°F
Evap. Coil
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Tot.
Cap.*
(MBH)
Tot.
Input†
(kW)
Tot.
Cap.* Input†
(MBH)
Tot.
WB
(°F)
CFM
3000
3500
4000
4500
5000
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
136
122
110
109
140
126
114
112
144
129
117
115
151
135
122
121
157
141
128
126
8.8
8.6
8.3
8.7
8.9
8.7
8.4
8.7
9.0
8.8
8.5
8.8
9.1
8.9
8.6
8.9
9.2
9.0
8.7
9.1
79
99
71
90
62
82
98
97
68
89
53
73
89
88
58
79
97
96
62
86
45
64
81
80
48
69
87
86
51
74
93
92
53
78
96
94
55
82
98
96
-
-
126
114
108
103
130
118
112
106
134
122
115
110
139
126
120
114
144
131
124
118
9.4
9.1
9.0
9.1
9.5
9.1
9.0
9.1
9.5
9.2
9.1
9.2
9.6
9.3
9.2
9.3
9.7
9.4
9.3
9.4
79
96
70
88
61
79
97
93
67
86
53
70
89
84
57
76
96
91
61
81
44
62
80
76
47
66
86
81
49
70
91
86
52
74
93
87
54
78
94
88
-
-
56
72
71
-
59
77
76
-
62
82
80
-
65
82
81
-
47
64
63
-
49
67
66
-
51
70
69
-
52
69
67
-
53
72
67
-
56
76
71
-
58
80
75
-
61
79
74
-
45
63
59
-
46
65
61
-
46
68
63
-
48
66
61
-
110 107
109 105
88
110 100
114 112 107
112 110 106
108 106
103 102
87
78
77
96
106
112 111 106
106 106 101
96
116 105
115 115 115 103
110 110 110
105 92 78
124 114 101
120 120 119 106
114 114 114 100
97
86
74
97
84
72
93
121 109
117 117 117 105
115 115 115 104
98
65
87
106
93
80
66
91
131 118 105
122 122 122 109
121 121 121 107
115 100
141 127 112
85
70
97
114
99
84
69
93
67
83
81
53
68
66
131 123 108
124 124 124 109
118 118 118 103
63
79
73
49
64
58
128 128 128 113
126 126 126 111
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
116
106
98
9.9
9.6
9.4
9.5
10.0
9.7
9.4
9.6
10.1
9.7
9.5
9.7
10.1
9.8
9.6
9.8
10.2
9.9
9.7
9.8
74
92
98
96
82
66
84
97
95
72
92
57
75
88
87
62
82
96
94
67
89
49
67
80
78
52
72
86
84
56
77
93
90
60
83
93
91
64
89
94
91
40
58
71
69
42
62
76
74
44
65
81
79
46
70
80
78
49
74
79
77
-
-
106
97
88
10.4
10.1
9.7
10.0
10.5
10.2
9.8
10.1
10.6
10.3
9.9
10.2
10.6
10.3
10.0
10.3
10.7
10.4
10.0
10.3
70
89
88
88
78
96
91
91
86
104
94
94
94
61
80
88
88
68
88
91
91
74
96
94
94
81
53
72
80
80
58
78
87
87
62
84
94
94
68
92
94
95
73
99
94
95
44
63
71
72
47
68
77
77
51
73
82
83
54
78
81
81
58
84
80
80
36
55
63
63
37
58
67
67
39
61
71
71
41
65
68
68
43
69
65
65
-
-
50
63
61
-
52
66
64
-
54
69
67
-
56
67
64
-
41
54
52
-
42
56
54
-
42
58
55
-
43
54
51
-
46
54
54
-
48
57
57
-
49
59
59
-
52
54
55
-
37
46
46
-
38
47
47
-
38
47
48
-
39
41
42
-
3000
3500
4000
4500
5000
96
88
120
109
101
99
110
100
91
101
101 101
99
91
110 100
105 105 104
102 102 102
99
79
91
124
113
105
102
126
115
107
104
129
117
109
106
114
104
94
94
99
86
73
96
114
104
94
114 107
107 107 107
104 104 104
104 100
94
95
103
104 104
94
95
88
95
108
93
79
114
104
94
117 114 104
109 109 109
106 106 106
59
64
62
44
50
47
54
50
50
39
35
35
94
95
94
95
95
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
97
88
78
81
100
92
81
84
104
95
83
87
101
93
82
85
99
91
80
83
10.8
10.5
10.1
10.4
11.0
10.7
10.2
10.6
11.1
10.8
10.3
10.7
11.1
10.9
10.4
10.8
11.2
10.9
10.4
10.8
66
85
78
81
73
91
81
84
80
95
83
87
89
93
82
85
97
91
80
83
57
77
78
81
63
84
81
84
69
92
83
87
76
93
82
85
82
91
80
83
48
68
71
74
53
74
77
80
57
80
83
87
62
87
82
85
67
91
80
83
40
59
63
65
43
64
67
70
46
68
72
75
49
74
69
72
52
79
65
68
31
51
54
57
33
54
57
60
34
57
61
63
36
61
55
59
38
65
50
54
-
-
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
42
45
48
-
44
47
50
-
45
49
52
-
47
42
45
-
34
37
39
-
34
37
40
-
33
37
40
-
34
29
32
-
3000
3500
4000
4500
5000
†
50
35
39
35
20
24
16
Unitary Products Group
246646-YTG-C-0606
TABLE 9: COOLING CAPACITY DH150 (12-1/2 TON) UNIT
Air On
Temperature of Air on Condenser Coil 85°F
Evap. Coil
Temperature of Air on Condenser Coil 95°F
Sensible Capacity (MBH)*
Return Dry Bulb (°F)
Sensible Capacity (MBH)*
Tot.
Tot.
Cap.*
(MBH)
Tot.
Input†
(kW)
Tot.
Cap.* Input†
(MBH)
WB
(°F)
Return Dry Bulb (°F)
CFM
3750
4375
5000
5625
6250
(kW)
86
83
80
77
74
71
68
86
83
80
77
74
71
68
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
165
158
148
138
169
161
151
141
172
165
155
144
172
164
154
143
171
164
154
143
11.9
11.8
11.6
11.5
11.9
11.8
11.7
11.5
12.0
11.9
11.7
11.6
11.9
11.8
11.7
11.5
11.9
11.8
11.6
11.5
95
85
74
63
92
52
82
-
-
159
151
141
132
163
155
144
135
167
159
148
139
166
158
147
138
165
157
146
137
13.1
13.0
12.8
12.8
13.2
13.1
12.9
12.8
13.2
13.1
12.9
12.9
13.2
13.1
12.9
12.8
13.2
13.1
12.9
12.8
94
83
72
62
89
51
79
-
-
124 114 103
147 137 126 115 105
138 135 124 113 103
71
94
92
-
73
98
96
-
60
83
81
-
61
85
83
-
61
88
86
-
56
83
77
-
121 111 100
141 135 124 113 103
132 130 120 109
103
133 121 108
144 141 134 121 109
135 134 129 116 104
68
92
87
-
70
96
91
-
57
81
77
-
57
83
78
-
58
85
80
-
54
78
71
-
98
53
83
105
92
80
67
98
54
86
91
78
65
95
136 124 111
151 146 136 123 111
141 139 134 121 109
115 100
148 134 119 105
155 155 146 132 117 102
144 144 144 129 115 100
121 105
156 139 122 106
154 154 150 133 117 100
143 143 143 127 110
127 109
163 144 126 107
154 154 154 135 116
143 143 143 124 106
86
71
56
90
113
98
84
69
55
87
76
145 131 116 101
148 148 144 129 115 100
139 139 139 124 109
120 104
151 137 120 104
147 147 145 128 112
138 138 138 121 104
127 109
157 143 125 106
72
95
-
71
95
88
-
69
90
81
88
71
55
89
-
73
87
70
54
87
94
-
70
98
87
90
72
53
88
90
71
53
88
51
79
68
50
71
62
146 146 146 127 108
137 137 137 118 99
Temperature of Air on Condenser Coil 105°F
Temperature of Air on Condenser Coil 115°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
152
143
133
124
156
147
137
127
160
150
140
130
159
149
139
129
158
148
138
128
14.6
14.5
14.3
14.2
14.7
14.5
14.3
14.3
14.7
14.5
14.4
14.3
14.7
14.5
14.4
14.3
14.7
14.5
14.3
14.3
91
80
70
97
59
86
48
75
96
90
50
80
-
-
145
135
125
116
149
138
129
119
153
142
132
122
152
141
131
121
151
140
130
120
16.2
15.9
15.8
15.7
16.2
15.9
15.8
15.7
16.2
15.9
15.8
15.8
16.2
15.9
15.8
15.8
16.2
15.9
15.8
15.8
88
78
67
93
56
82
46
72
90
81
48
77
96
87
50
81
-
-
118 107
133 128 118 107
124 122 111 100
64
86
79
-
67
90
83
-
70
94
87
-
68
88
80
-
54
75
68
-
54
77
70
-
55
80
72
-
51
72
63
-
114 104
125 122 111 101
61
79
71
-
64
84
75
-
67
88
78
-
66
81
71
-
50
68
60
-
51
71
62
-
52
74
64
-
49
65
55
-
3750
4375
5000
5625
6250
116 113 103
99 86 73
127 114 102
129 127 122 109
119 118 112 100
92
61
89
101
88
76
63
92
130 118 105
137 134 128 115 103
127 126 121 108
111
142 128 113
140 140 138 123 109
130 130 130 116 101
118 102
145 134 118 101
95
53
84
96
82
67
99
109
94
80
65
96
140 125 111
132 132 132 118 103
122 122 122 108
116 100
140 132 115
131 131 131 115
121 121 121 105
93
50
82
98
88
49
83
93
83
85
68
52
85
83
66
99
139 139 138 121 105
129 129 129 113
126 107 88 70
148 141 122 104
138 138 138 119 101
128 128 128 110 91
96
51
85
124 105
87
68
67
82
72
48
63
54
140 139 120 102
130 130 130 112
120 120 120 102
64
74
64
46
56
46
Temperature of Air on Condenser Coil 125°F
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
72
67
62
57
138
126
118
108
142
130
121
111
146
133
124
114
145
132
123
113
144
131
122
112
17.7
17.3
17.2
17.2
17.7
17.3
17.2
17.2
17.7
17.4
17.2
17.2
17.7
17.4
17.3
17.2
17.7
17.4
17.3
17.2
86
75
64
90
54
79
94
84
58
86
43
68
83
73
46
73
90
79
48
79
97
85
48
80
91
80
47
81
85
75
-
-
*
These capacities are gross ratings. For net
capacity, deduct air blower motor, MBH = 3.415
x kW. Refer to the appropriate Blower Perfor-
mance Table for the kW of the supply air
blower motor.
These ratings include condenser fan motors
and the compressor motors but not the supply
air blower motor.
111 100
118 116 105
108 105
96 84
124 111
58
73
62
-
61
78
66
-
64
83
70
-
63
75
63
-
47
62
52
-
48
65
54
-
50
68
56
-
46
58
47
-
3750
4375
5000
5625
6250
94
71
99
121 120 116 103
†
111 109 104
107 92 78
133 122 108
91
63
93
124 124 124 112
114 114 114
114 98 81
132 130 113
99
65
96
123 123 123 108
113 113 113
122 103 85
131 131 118
122 122 122 104
112 112 112 93
96
66
99
62
67
56
43
48
38
Unitary Products Group
17
246646-YTG-C-0606
TABLE 10: ELECTRICAL DATA DH078 (6-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Max Fuse Size
w/Power
Supply
Blower
Motor FLA Motor Outlet
Pwr
Exh
Pwr
Conv
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Max Fuse*
Size (Amps)
Compressors
RLA LRA
Electric Heater Actual Heater
Exhaust
(Amps)
Voltage
Model No.
KW
Amps
FLA
ea.
1.5
HP
2
HP
1.5
HP
2
HP
1.5
HP
2
HP
1.5
HP
35
35
60
80
2
1.5
HP
40
40
70
80
2
HP
45
45
70
80
110
45
45
80
90
125
25
25
35
45
60
20
20
30
40
50
FLA
FLA
ea.
ea.
HP
40
40
60
80
None
--
6.8
13.5
18
25.5
--
--
29.5
31.3
54.6
70.2
96.2
29.5
34.8
61.9
79.9
31.5 35.0 37.0
33.8 38.2 40.7
57.1 61.5 64.0
72.7 77.1 79.6
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
18.9
37.5
50.0
70.8
--
208
230
460
575
9.0
72.0
1.5
1.5
0.8
0.6
6.2
6.2
3.1
2.4
8.2
8.2
4.1
3.6
5.5
0.0
98.7 103.1 105.6 100 100 110
31.5 35.0 37.0
37.3 41.7 44.2
64.4 68.8 71.3
82.4 86.8 89.3
35
35
70
80
40
40
70
90
40
45
70
90
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
9
21.7
43.3
57.7
81.8
--
9.0
5.8
4.5
72.0
45.0
36.0
5.5
2.2
1.8
0.0
0.0
0.0
18
24
34
--
110.0 112.5 116.9 119.4 110 125 125
17.8
17.8
30.9
40
18.8
20
21
20
20
35
40
60
15
15
25
35
45
20
20
35
45
60
15
20
30
35
50
25
25
35
45
60
20
20
30
35
50
2TP04540946
2TP04541846
2TP04542446
2TP04543646
None
9
11.3
22.6
30.1
42.7
--
18.8 20.2 21.4
32.2 33.7 34.9
18
24
34
--
41.2 42.7
56.2 57.7
44
59
55
13.7
13.8
24.7
31.9
43.9
14.9 15.5 16.7
15.3 16.1 17.6
26.2 26.9 28.4
33.4 34.1 35.6
45.4 46.1 47.6
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9
9.0
18
24
34
18.1
24.1
34.1
TABLE 11: ELECTRICAL DATA DH078 (6-1/2 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET
MCA
Max Fuse Size
w/Power
Supply
Blower
Motor FLA Motor Outlet
Pwr
Exh
Pwr
Conv
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Max Fuse*
Size (Amps)
Compressors
RLA LRA
Electric Heater Actual Heater
Exhaust
(Amps)
Voltage
Model No.
KW
Amps
FLA
ea.
1.5
HP
2
HP
1.5
HP
39.7
43.8
67.1
82.7
2
HP
1.5
HP
2
HP
1.5
HP
45
45
70
90
2
1.5
HP
50
60
80
90
2
HP
50
FLA
FLA
ea.
ea.
HP
50
50
70
90
None
--
6.8
13.5
18
25.5
--
--
41.7 45.2 47.2
46.3 50.7 53.2
69.6 74.0 76.5
85.2 89.6 92.1
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
18.9
37.5
50.0
70.8
--
60
208
230
460
575
9.0
72.0
1.5
1.5
0.8
0.6
6.2
6.2
3.1
2.4
8.2
8.2
4.1
3.6
5.5
10.0
80
100
125
50
108.7 111.2 115.6 118.1 110 125 125
39.7
47.3
74.4
92.4
41.7 45.2 47.2
49.8 54.2 56.7
76.9 81.3 83.8
45
50
80
50
50
80
50
60
90
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
9
21.7
43.3
57.7
81.8
--
60
9.0
5.8
4.5
72.0
45.0
36.0
5.5
2.2
1.8
10.0
5.0
18
24
34
--
90
94.9 99.3 101.8 100 100 100
110
150
30
122.5 125.0 129.4 131.9 125 125 150
22.8
23.7
37.2
46.2
61.2
17.7
18.8
29.7
36.9
48.9
23.8
25
26
25
25
40
50
70
20
20
30
40
50
25
25
40
50
70
20
25
35
40
60
30
30
40
50
70
20
25
35
40
60
2TP04540946
2TP04541846
2TP04542446
2TP04543646
None
9
11.3
22.6
30.1
42.7
--
24.9 26.4 27.7
38.4 39.9 41.2
30
18
24
34
--
45
47.5
62.5
49
64
50.2
65.2
60
70
18.9 19.5 20.7
20.3 21.1 22.6
31.2 31.9 33.4
38.4 39.1 40.6
50.4 51.1 52.6
25
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9
9.0
25
4.0
18
24
34
18.1
24.1
34.1
35
45
60
18
Unitary Products Group
246646-YTG-C-0606
TABLE 12: ELECTRICAL DATA DH090 (7-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET
Supply
Blower Motor
FLA
Pwr
Conv
Outlet
Max Fuse Size
w/Power Exhaust
(Amps)
OD Fan
Motors
Pwr Exh
Motor
Min. Circuit
MCA w/Power
Max Fuse*
Compressors
Electric Heater
Model No.
Actual
KW
Heater
Amps
Ampacity (Amps) Exhaust (Amps) Size (Amps)
Voltage
RLA
ea.
LRA
ea.
FLA
ea.
2 HP 3 HP
FLA
FLA
2 HP
3 HP
2 HP
3 HP
2 HP 3 HP 2 HP
3 HP
None
--
--
42.9
42.9
57.1
72.7
98.7
42.9
42.9
64.4
82.4
112.5
21.7
21.7
32.2
41.2
56.2
17.9
17.9
26.2
33.4
45.4
45.6
45.6
60.5
76.1
102.1
45.6
45.6
67.8
85.8
115.9
22.9
22.9
33.7
42.7
57.7
18.4
18.4
26.8
34.0
46.0
48.4
48.4
64.0
79.6
105.6
48.4
48.4
71.3
89.3
119.4
23.9
23.9
34.9
44.0
59.0
19.7
19.7
28.4
35.6
47.6
51.1
51.1
67.3
83.0
109.0
51.1
51.1
74.6
92.7
122.7
25.1
25.1
36.4
45.5
60.5
20.2
20.2
29.0
36.2
48.3
50
50
60
80
50
50
70
80
60
60
70
80
110
60
60
80
90
125
30
30
35
45
60
25
25
30
40
50
60
60
70
90
110
60
60
80
100
125
30
30
40
50
70
25
25
30
40
50
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
6.8
13.5
18.0
25.5
--
18.9
37.5
50.0
70.8
--
208
230
460
575
14.1
14.1
7.1
110.0
110.0
54.0
1.5
1.5
0.8
0.6
8.2
8.2
4.1
3.6
10.9
10.9
5.3
5.5
0.0
100 110
50
50
70
90
50
50
70
90
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
9
21.7
43.3
57.7
81.8
--
5.5
2.2
1.8
0.0
0.0
0.0
18
24
34
125 125
--
25
25
35
45
60
20
20
30
35
50
25
25
35
45
60
20
20
30
35
50
2TP04540946
2TP04541846
2TP04542446
2TP04543646
None
9.0
18.0
24.0
34.0
--
11.3
22.6
30.1
42.7
--
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9.0
18.0
24.0
34.0
9.0
5.8
44.0
4.1
18.1
24.1
34.1
TABLE 13: ELECTRICAL DATA DH090 (7-1/2 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET
Supply
Blower Motor
FLA
Pwr
Conv
Outlet
Max Fuse Size
w/Power Exhaust
(Amps)
OD Fan
Motors
Pwr Exh
Motor
Min. Circuit
MCA w/Power
Max Fuse*
Compressors
Electric Heater
Model No.
Actual
KW
Heater
Amps
Ampacity (Amps) Exhaust (Amps) Size (Amps)
Voltage
ea.
ea.
ea.
2 HP 3 HP
FLA
FLA
2 HP
3 HP
2 HP
3 HP
2 HP 3 HP 2 HP
3 HP
None
--
--
52.9
52.9
69.6
85.2
111.2
52.9
52.9
76.9
94.9
125.0
26.7
26.7
38.4
47.5
62.5
21.9
21.9
31.2
38.4
50.4
55.6
55.6
73.0
88.6
114.6
55.6
55.6
80.3
98.3
128.4
27.9
27.9
39.9
49.0
64.0
22.4
22.4
31.8
39.0
51.0
58.4
58.4
76.5
92.1
118.1
58.4
58.4
83.8
101.8
131.9
28.9
28.9
41.2
50.2
65.2
23.7
23.7
33.4
40.6
52.6
61.1
61.1
79.8
95.5
121.5
61.1
61.1
87.1
105.2
135.2
30.1
30.1
42.7
51.7
66.7
24.2
24.2
34.0
41.2
53.3
60
60
70
90
60
60
80
90
70
70
70
70
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
6.8
13.5
18.0
25.5
--
18.9
37.5
50.0
70.8
--
208
230
460
575
14.1
14.1
7.1
110.0
110.0
54.0
1.5
1.5
0.8
0.6
8.2
8.2
4.1
3.6
10.9
10.9
5.3
5.5
10.0
80
80
100
125
70
100
125
70
125 125
60
60
80
60
60
90
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
9
21.7
43.3
57.7
81.8
--
70
70
5.5
2.2
1.8
10.0
5.0
18
90
90
24
100 100
125 150
110
150
35
110
150
35
34
--
30
30
40
50
70
25
25
35
40
60
30
30
40
50
70
25
25
35
40
60
2TP04540946
2TP04541846
2TP04542446
2TP04543646
None
9.0
18.0
24.0
34.0
--
11.3
22.6
30.1
42.7
--
35
35
45
45
60
60
70
70
25
25
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9.0
18.0
24.0
34.0
9.0
25
25
5.8
44.0
4.1
4.0
18.1
24.1
34.1
35
35
45
45
60
60
Unitary Products Group
19
246646-YTG-C-0606
TABLE 14: ELECTRICAL DATA DH102 (8-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET
Max Fuse Size
Pwr
Conv
Outlet
Min. Circuit MCA w/Power
OD Fan Supply Blower Pwr Exh
Max Fuse*
Size (Amps)
w/Power
Exhaust
(Amps)
Compressors
Ampacity
(Amps)
Exhaust
(Amps)
Motors
Motor FLA
Motor
Electric Heater Actual Heater
Voltage
Model No.
KW
Amps
RLA
ea.
LRA
ea.
FLA
ea.
3 HP
3 HP
FLA
FLA
3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP
None
--
6.8
13.5
18
25.5
--
--
44.2
44.2
60.5
76.1
44.2
44.2
60.5
76.1
49.7
49.7
67.3
83.0
49.7
49.7
67.3
83.0
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
50
50
70
80
110
50
50
70
90
125
25
25
35
45
60
20
20
30
35
50
60
60
70
90
110
60
60
80
100
125
30
30
40
50
70
25
25
30
40
50
60
60
70
90
110
60
60
80
100
125
30
30
40
50
70
25
25
30
40
50
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
18.9
37.5
50.0
70.8
--
208
230
460
575
11.7
11.7
6.4
88.0
88.0
42.0
36.0
3.5
3.5
1.6
1.3
10.9
10.9
5.3
10.9
5.5
5.5
2.2
1.8
0.0
102.1 102.1 109.0 109.0
44.2
44.2
67.8
85.8
44.2
44.2
67.8
85.8
50.4
50.4
74.6
92.7
50.4
50.4
74.6
92.7
2TP04540925
2TP04541825
2TP04542425
2TP04543625
None
9
21.7
43.3
57.7
81.8
--
10.9
0.0
0.0
0.0
18
24
34
--
115.9 115.9 122.7 122.7
22.9
22.9
33.7
42.7
57.7
18.2
18.2
26.8
34
22.9
22.9
33.7
42.7
57.7
18.2
18.2
26.8
34
25.1
25.1
36.4
45.5
60.5
20
25.1
25.1
36.4
45.5
60.5
20
2TP04540946
2TP04541846
2TP04542446
2TP04543646
None
9
11.3
22.6
30.1
42.7
--
5.3
18
24
34
--
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9
9.0
20
20
5.1
4.1
4.1
18
24
34
18.1
24.1
34.1
29
29
36.2
48.3
36.2
48.3
46
46
TABLE 15: ELECTRICAL DATA DH102 (8-1/2 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET
Max Fuse Size
Pwr
Conv
Outlet
Min. Circuit MCA w/Power
OD Fan Supply Blower Pwr Exh
Max Fuse*
Size (Amps)
w/Power
Exhaust
(Amps)
Compressors
Ampacity
(Amps)
Exhaust
(Amps)
Motors
Motor FLA
Motor
Electric Heater Actual Heater
Voltage
Model No.
KW
Amps
RLA
ea.
LRA
ea.
FLA
ea.
3 HP
3 HP
FLA
FLA
3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP 3 HP
None
--
--
54.2
54.2
73.0
88.6
54.2
54.2
73.0
88.6
59.7
59.7
79.8
95.5
59.7
59.7
79.8
95.5
60
60
60
60
70
70
70
70
2TP04540925
2TP04541825
2TP04542425
2TP04543625
6.8
18.9
37.5
50.0
70.8
208
230
460
575
11.7
11.7
6.4
88.0
88.0
42.0
36.0
3.5
3.5
1.6
1.3
10.9
10.9
5.3
10.9
5.5
5.5
2.2
1.8
10.0
13.5
18
80
80
80
80
90
90
100
125
100
125
25.5
114.6 114.6 121.5 121.5
125
125
None
--
9
--
54.2
54.2
80.3
98.3
54.2
54.2
80.3
59.7
59.7
87.1
59.7
59.7
87.1
60
60
60
60
70
70
70
70
2TP04540925
2TP04541825
2TP04542425
2TP04543625
21.7
43.3
57.7
81.8
10.9
10.0
10.0
10.0
18
24
34
90
90
90
90
98.3 105.2 105.2
100
150
100
150
110
150
110
150
128.4 128.4 135.2 135.2
None
--
--
27.9
27.9
39.9
49
27.9
27.9
39.9
49
30.1
30.1
42.7
51.7
66.7
30.1
30.1
42.7
51.7
66.7
30
30
40
50
70
30
30
40
50
70
35
35
45
60
70
35
35
45
60
70
2TP04540946
2TP04541846
2TP04542446
2TP04543646
9
11.3
22.6
30.1
42.7
5.3
18
24
34
64
64
None
--
--
22.2
22.2
31.8
39
22.2
22.2
31.8
39
24
24
24
24
25
25
35
40
60
25
25
35
40
60
25
25
35
45
60
25
25
35
45
60
2TP04540958
2TP04541858
2TP04542458
2TP04543658
9
9.0
5.1
4.1
4.1
18
24
34
18.1
24.1
34.1
34
34
41.2
53.3
41.2
53.3
51
51
20
Unitary Products Group
246646-YTG-C-0606
TABLE 16: ELECTRICAL DATA DH120 (10 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
2
3
2
3
2
3
2
3
2
HP
70
3
FLA
FLA
HP
HP
HP
HP
HP
HP
HP HP
HP
70
None
--
13.5
18
25.5
40.6
--
--
51.2
57.1
72.7
53.9 56.7 59.4 60 60
60.5 64.0 67.3 60 70
76.1 79.6 83.0 80 80
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
37.5
50.0
70.8
70
70
208
230
460
16.0 137.0
3.5
3.5
1.6
1.3
8.2 10.9
5.5
0.0
80
90
98.7 102.1 105.6 109.0 100 110
110
175
70
110
175
70
112.7 151.1 154.5 158.0 161.4 175 175
--
51.2
64.4
82.4
53.9 56.7 59.4 60 60
67.8 71.3 74.6 70 70
85.8 89.3 92.7 90 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
18
24
34
54
--
43.3
57.7
80
80
16.0 137.0
8.2 10.9
5.5
2.2
1.8
0.0
0.0
0.0
90
100
125
175
35
81.8 112.5 115.9 119.4 122.7 125 125
129.9 140.2 143.5 147.0 150.4 150 175
125
175
35
--
26
27.2 28.2 29.4 30 35
33.7 34.9 36.4 35 35
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
18
24
34
54
--
22.6
30.1
42.7
67.8
--
32.2
41.2
56.2
70.1
20.6
26.2
33.4
45.4
56.5
35
40
8.3
6.4
69.0
58.0
4.1
3.6
5.3
4.1
42.7
57.7
44
59
45.5 45 45
60.5 60 60
45
50
60
70
71.6 72.8 74.3 80 80
21.1 22.4 22.9 25 25
80
80
25
25
2TP04521858
2TP04522458
2TP04523658
2TP04525458
18
24
34
54
18.1
24.1
34.1
54.2
26.8 28.4
29
30 30
30
30
575
34
46
35.6 36.2 35 35
47.6 48.3 50 50
40
40
50
70
50
70
57.1 58.7 59.3 70 70
*
Maximum HACR breaker of the same AMP size is applicable.
TABLE 17: ELECTRICAL DATA DH120 (10 TON) HIGH EFFICIENCY WITH PWRD CONVENIENCE OUTLET
MCA
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
w/Power
Exhaust
(Amps)
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
2
3
2
3
2
3
2
3
2
3
FLA
FLA
HP
HP
HP
HP
HP
HP
HP HP
HP
80
HP
80
None
--
13.5
18
25.5
40.6
--
--
61.2
69.6
85.2
63.9 66.7 69.4 70 70
73.0 76.5 79.8 70 80
88.6 92.1 95.5 90 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
37.5
50.0
80
80
208
230
460
16.0 137.0
3.5
3.5
1.6
1.3
8.2 10.9
5.5
10.0
100
125
175
80
100
125
175
80
70.8 111.2 114.6 118.1 121.5 125 125
112.7 163.6 167.0 170.5 173.9 175 175
--
61.2
76.9
94.9
63.9 66.7 69.4 70 70
80.3 83.8 87.1 80 90
98.3 101.8 105.2 100 100
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
18
24
34
54
--
43.3
57.7
90
90
16.0 137.0
8.2 10.9
5.5
2.2
1.8
10.0
5.0
110
150
175
40
110
150
175
40
81.8 125.0 128.4 131.9 135.2 125 150
129.9 152.7 156.0 159.5 162.9 175 175
--
31
32.2 33.2 34.4 35 40
39.9 41.2 42.7 40 40
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
18
24
34
54
--
22.6
30.1
42.7
67.8
--
38.4
47.5
62.5
76.3
24.6
31.2
38.4
50.4
61.5
45
45
8.3
6.4
69.0
58.0
4.1
3.6
5.3
4.1
49
64
50.2 51.7 50 50
65.2 66.7 70 70
60
60
70
70
77.8 79.1 80.6 90 90
25.1 26.4 26.9 30 30
90
90
30
30
2TP04521858
2TP04522458
2TP04523658
2TP04525458
18
24
34
54
18.1
24.1
34.1
54.2
31.8 33.4
34
35 35
35
35
575
4.0
39
51
40.6 41.2 40 40
52.6 53.3 60 60
45
45
60
60
62.1 63.7 64.3 70 70
70
70
*
Maximum HACR breaker of the same AMP size is applicable.
Unitary Products Group
21
246646-YTG-C-0606
TABLE 18: ELECTRICAL DATA DH150 (12-1/2 TON) HIGH EFFICIENCY W/O PWRD CONVENIENCE OUTLET
MCA
w/Power
Exhaust
(Amps)
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
3
5
3
5
3
5
3
5
3
5
FLA
FLA
HP
HP
HP
HP
HP
HP
HP HP
HP
80
HP
90
None
--
13.5
18
25.5
40.6
--
--
60.4
60.5
76.1
65.6 65.9 71.1 70 80
67.0 67.3 73.8 70 80
82.6 83.0 89.5 80 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
37.5
50.0
80
90
208
230
460
18.9 146.0
3.5
3.5
1.6
1.3
10.9 16.1
10.9 16.1
5.5
0.0
90
90
70.8 102.1 108.6 109.0 115.5 110 110
112.7 154.5 161.0 161.4 167.9 175 175
110
175
80
125
175
90
--
60.4
67.8
85.8
65.6 65.9 71.1 70 80
74.3 74.6 81.1 70 80
92.3 92.7 99.2 90 100
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
18
24
34
54
--
43.3
57.7
80
90
18.9 146.0
5.5
2.2
1.8
0.0
0.0
0.0
100
125
175
40
100
150
175
40
81.8 115.9 122.4 122.7 129.2 125 125
129.9 143.5 150.0 150.4 156.9 175 175
--
29.9
33.7
42.7
57.7
71.6
23.8
26.8
34
32.7 32.1 34.9 35 40
37.2 36.4 39.9 35 40
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
18
24
34
54
--
22.6
30.1
42.7
67.8
--
40
40
9.5
7.6
73.0
58.4
5.3
4.1
8.1
6.0
46.2 45.5
61.2 60.5
49
64
45 50
60 70
50
50
70
70
75.1 74.3 77.8 80 90
25.7 25.6 27.5 30 30
80
90
30
35
2TP04521858
2TP04522458
2TP04523658
2TP04525458
18
24
34
54
18.1
24.1
34.1
54.2
29.2
29
31.4 30 30
30
35
575
*
36.4 36.2 38.6 35 40
48.4 48.3 50.6 50 50
59.5 59.3 61.7 70 70
40
40
46
57.1
50
70
60
70
Maximum HACR breaker of the same AMP size is applicable.
TABLE 19: ELECTRICAL DATA DH150 (12-1/2 TON) HIGH EFFICIENCY W/PWRD CONVENIENCE OUTLET
MCA
w/Power
Exhaust
(Amps)
Max
Fuse*
Size
Max Fuse* Size
w/Power
Supply
Blower
Pwr
Pwr
Min. Circuit
Ampacity
(Amps)
OD Fan
Motors
Compressors
Exh Conv
Electric Heater Actual Heater
Exhaust
Voltage
Motor FLA Motor Outlet
Model No.
KW
Amps
(Amps)
(Amps)
RLA
ea.
LRA
ea.
FLA
ea.
3
5
3
5
3
5
3
5
3
5
FLA
FLA
HP
HP
HP
HP
HP
HP
HP HP
HP
90
HP
100
100
110
150
200
100
100
125
150
175
45
None
--
13.5
18
25.5
40.6
--
--
70.4
73.0
88.6
75.6 75.9 81.1 80 90
79.5 79.8 86.3 80 90
95.1 95.5 102.0 90 100
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
37.5
50.0
90
208
230
460
18.9 146.0
3.5
3.5
1.6
1.3
10.9 16.1
10.9 16.1
5.5
10.0
100
125
175
90
70.8 114.6 121.1 121.5 128.0 125 125
112.7 167.0 173.5 173.9 180.4 175 175
--
70.4
80.3
75.6 75.9 81.1 80 90
86.8 87.1 93.6 90 90
2TP04521825
2TP04522425
2TP04523625
2TP04525425
None
18
24
34
54
--
43.3
57.7
90
18.9 146.0
5.5
2.2
1.8
10.0
5.0
98.3 104.8 105.2 111.7 100 110
110
150
175
45
81.8 128.4 134.9 135.2 141.7 150 150
129.9 156.0 162.5 162.9 169.4 175 175
--
34.9
39.9
49
37.7 37.1 39.9 40 45
43.4 42.7 46.2 40 45
52.5 51.7 55.2 50 60
67.5 66.7 70.2 70 70
81.3 80.6 84.1 90 90
29.7 29.6 31.5 35 35
2TP04521846
2TP04522446
2TP04523646
2TP04525446
None
18
24
34
54
--
22.6
30.1
42.7
67.8
--
45
50
9.5
7.6
73.0
58.4
5.3
4.1
8.1
6.0
60
60
64
70
80
77.8
27.8
31.8
39
90
90
35
35
2TP04521858
2TP04522458
2TP04523658
2TP04525458
18
24
34
54
18.1
24.1
34.1
54.2
34.2
34
36.4 35 35
35
40
575
*
4.0
41.4 41.2 43.6 40 45
53.4 53.3 55.6 60 60
64.5 64.3 66.7 70 70
45
45
51
62.1
60
70
60
70
Maximum HACR breaker of the same AMP size is applicable.
TABLE 20: ELECTRIC HEAT MULTIPLIERS
NOTES FOR TABLES 21 THROUGH TABLE 30:
VOLTAGE
•
Blower performance includes dry coil and 2” throwaway
filters.
kW Cap. Multiplier
NOMINAL
RATING
208
0.75
0.92
0.92
0.92
•
Blower performance for gas heat includes the maximum
number of heat tubes available for each tonnage.
240
230
480
600
460
ESP (External Static Pressure) given is that available for the
supply and return air duct system. All internal resistances
have been deducted from the total static pressure of the
blower.
575
NOTE: Electric heaters are rated at nominal voltage. Use
this table to determine the electric heat capacity for
heaters supplied at lower voltages.
22
Unitary Products Group
246646-YTG-C-0606
Unitary Products Group
23
246646-YTG-C-0606
24
Unitary Products Group
246646-YTG-C-0606
Unitary Products Group
25
246646-YTG-C-0606
26
Unitary Products Group
246646-YTG-C-0606
Unitary Products Group
27
246646-YTG-C-0606
28
Unitary Products Group
246646-YTG-C-0606
Unitary Products Group
29
246646-YTG-C-0606
30
Unitary Products Group
246646-YTG-C-0606
Unitary Products Group
31
246646-YTG-C-0606
32
Unitary Products Group
246646-YTG-C-0606
TABLE 31: ADDITIONAL STATIC RESISTANCE DH120 AND 150
Electric Heat KW2
24
1
2 3
CFM
Cooling Only
Economizer
9
18
36
54
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.06
0.07
0.08
0.09
0.11
0.12
0.14
0.16
0.18
0.20
0.23
0.25
0.28
0.30
0.33
0.36
0.39
0.42
0.45
0.48
0.52
0.56
0.60
0.02
0.02
0.02
0.02
0.03
0.03
0.03
0.03
0.04
0.04
0.04
0.04
0.05
0.05
0.05
0.05
0.06
0.06
0.06
0.06
0.07
0.07
0.07
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
0.53
0.56
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
1
2
3
Add these resistance values to the available static resistance in the respective Blower Performance Tables.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
TABLE 32: ADDITIONAL STATIC RESISTANCE DH078, 090, 102
Electric Heat KW2
24
1
2 3
CFM
Cooling Only
Economizer
9
18
36
54
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
-0.004
0.01
0.01
0.02
0.03
0.04
0.05
0.06
0.07
0.08
0.09
0.09
0.10
0.07
0.09
0.11
0.13
0.16
0.18
0.20
0.22
0.24
0.27
0.29
0.31
0.33
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.06
0.07
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.08
0.09
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.29
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
1
2
3
Deduct these resistance values to the available static resistance in the respective Blower Performance Tables.
Deduct these resistance values from the available external static pressure shown in the respective Blower Performance Table.
The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return
air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
Unitary Products Group
33
246646-YTG-C-0606
TABLE 33: ELECTRIC HEAT MINIMUM SUPPLY AIR CFM
UNIT MODEL SIZE (NOMINAL TONS)
HEATER
078 (6.5)
090 (7.5)
102 (8.5)
120 (10)
150 (12.5)
VOLTAGE
kW
MINIMUM SUPPLY AIR CFM
1950
1950
1950
1950
-
2250
2250
2250
2250
-
2550
2550
2550
2550
-
-
-
9
3000
3000
3000
3500
-
3750
3750
3750
4000
-
18
24
36
54
9
208/230
1950
1950
1950
1950
-
2250
2250
2250
2250
-
2550
2550
2550
2550
-
3000
3000
3000
3000
-
3750
3750
3750
3750
-
18
24
36
54
9
480
600
1950
1950
1950
1950
-
2250
2250
2250
2250
-
2550
2550
2550
2550
-
3000
3000
3000
3500
3750
3750
3750
3750
18
24
36
54
TABLE 34: INDOOR BLOWER SPECIFICATIONS
MOTOR
RPM Eff.
1-1/2 1725 80% 1.15
MOTOR SHEAVE
BLOWER SHEAVE
MODEL
DH078
DH090
DH102
DH120
DH150
BELT
HP
SF Frame Datum Dia. (in.) Bore (in.) Model Datum Dia. (in.) Bore (in.) Model
56
56
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
3.4 - 4.4
4.3 - 5.3
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
7/8
1 1/8
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
7.0
6.2
6.5
6.0
6.0
5.7
8.5
7.0
7.0
6.7
1
1
1
1
1
1
1
1
1
1
AK74
AK66
AK69
AK64
AK64
AK61
AK89
AK74
AK74
BK77
A49
A49
A49
A49
A49
A49
A56
A54
A54
BX55
2
2
3
3
3
2
3
3
5
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 80% 1.15
1725 87% 1.15
56
56
56
56
56
56
56
184T
TABLE 35: POWER EXHAUST SPECIFICATIONS
MOTOR
RPM1
ELECTRICAL
POWER EXHAUST
FUSE
SIZE
CFM@
0.1 ESP
VOLT
PHASE
MODEL
HP
QTY
LRA
FLA
5.0
MCA
2PE0473225
2PE0473246
2PE0473258
208/230
460
1
1
1
24.9
6.3
2.8
1.9
10
5
1075
1050
0.75
1
2.2
3,800
-
575
1.5
4
1
Motors are multi-tapped and factory wired for high speed.
34
Unitary Products Group
246646-YTG-C-0606
FRONT
FRONT
LEFT
LEFT
B
C
D
C
B
A
A
E
D
F
FIGURE 4 - UNIT 6 POINT LOAD
TABLE 37: 6 POINT LOAD WEIGHT
FIGURE 2 - UNIT 4 POINT LOAD
TABLE 36: 4 POINT LOAD WEIGHT
Locations (lbs.)
Location (lbs.)
Model
Model
A
B
C
D
E
F
A
B
C
D
DH078
DH090
DH102
DH120
DH150
138
139
141
181
180
113
113
115
163
161
93
94
146
147
149
214
213
176
178
180
237
235
216
218
221
264
262
DH078
DH090
DH102
DH120
DH150
197
199
201
265
263
147
148
150
226
224
230
232
234
330
327
309
311
315
386
383
95
147
146
TABLE 38: UNIT WEIGHT
Shipping
Weight (lbs.)
Operating
Weight (lbs.)
Model
DH078
DH090
DH102
DH120
DH150
W/ECON.
W/PE
888
895
905
1212
1202
85
883
890
900
1207
1197
84
Y
X
FRONT
LEFT
X
Y
23
Unit Model Number
DH078
150
49
148
49
1
W/ELECT. HEAT
38
38
38
2
110
110
W/GAS HEAT
23
DH090
1
2
54 KW Heater
8 Tube Heat Exchanger
23
DH102
47 1/2
47 1/2
25 1/2
25 1/2
DH120
DH150
FIGURE 3 - UNIT CENTER OF GRAVITY
Unitary Products Group
35
246646-YTG-C-0606
30-11/32
See Detail
A
X
Control
Entry
Ø 7/8
Power
Entry
Ø 2-1/2
Power
Entry
4-1/4
Ø 2-1/2
11-1/2
Convenience
Power
Outlet
Entry
For Baserail
Dimensions
See Detail B
Ø 7/8
FRONT
17-3/16
For Drain
Dimensions
See Detail C
30-3/16
24-3/16
6-3/16
59
LEFT
89
27
FIGURE 5 - UNIT DIMENSIONS
TABLE 39: UNIT HEIGHT
DETAIL B
2
-
3
/
8
X
42
Unit Model Number
DH078
42
DH090
42
DH102
50 3/4
50 3/4
DH120
3
-
3
/
4
DH150
G
a
s
P
i
p
e
I
n
l
e
t
DETAIL A
3
-
9
/
1
6
5
-
1
/
4
B
P
a
a
s
n
e
DETAIL C
1
7
-
1
3
/
1
6
V
i
e
w
o
f
W
a
l
l
A
c
r
o
s
s
f
r
o
m
C
o
i
l
5
-
3
/
8
TABLE 40: UNIT CLEARANCES
Top1
72”
36”
36”
Right
12”
36”
0”
Front
Left
Rear2
Bottom3
1
2
Units must be installed outdoors. Overhanging structure or
shrubs should not obstruct condenser air discharge outlet.
To remove the slide-out drain pan, a rear clearance of 60” is
required. If space is unavailable, the drain pan can be
removed through the front by separating the corner wall.
Units may be installed on combustible floors made from
wood or class A, B or C roof covering materials.
3
36
Unitary Products Group
246646-YTG-C-0606
R
I
G
H
T
8
0
-
5
/
8
I
N
S
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
C
O
N
D
E
N
S
E
R
S
E
C
T
I
O
N
2
0
S
U
P
P
L
Y
2
0
6
R
E
T
U
R
N
2
T
Y
P
.
3
0
I
N
S
O
U
L
A
T
E
D
D
E
C
K
U
N
D
E
R
5
0
-
1
/
2
C
M
P
R
E
S
S
O
R
S
E
C
T
I
O
N
F
R
O
N
T
8
o
r
1
4
FIGURE 6 - PREDATOR® ROOF CURB DIMENSIONS
2
T
Y
P
2
3
4
3
0
-
1
/
2
5
0
-
1
/
2
8
0
-
5
/
8
2
6
R
E
T
U
R
N
S
U
P
P
L
Y
1
0
7
6
-
5
/
8
5
9
-
1
/
4
9
4
F
R
O
N
T
R
I
G
H
T
6
4
-
1
/
4
FIGURE 7 - SUNLINE™ TO PREDATOR® TRANSITION ROOF CURBS
Unitary Products Group
37
246646-YTG-C-0606
32-11/16
6-13/16
6-13/16
SUPPLY
AIR
RETURN
AIR
6-13/16
24
27-1/2
21
LEFT
18
19-3/16
21-3/16
17-3/16
12-5/16
Bottom Power,
14-23/32
FRONT
Bottom gas
supply entry
Control and
Convenience
Outlet Wiring
Entry
16-3/8
18-1/16
63-1/2
FIGURE 8 - BOTTOM DUCT OPENINGS (FROM ABOVE)
REAR DUCT DIMENSIONS
DIMENSION
CABINET SIZE
“A”
“B”
“C”
FIGURE 9 - REAR DUCT DIMENSIONS
50 3/4”
42”
28 1/4
27 3/4
18 1/16
12 1/16
28 1/4
27 1/2
38
Unitary Products Group
246646-YTG-C-0606
58 1/4
88 1/4
39 1/2
or
47 1/2
Outside Air
Intake Hood
35 3/4
Relief Hood for
Power Exhaust or
Barometric Relief
26
25 3/4
26
30 1/4
FIGURE 10 -DOWNFLOW ECONOMIZER HOOD DETAIL
TABLE 41: ECONOMIZER USAGE
Application
Cabinet Height
Description
Model
Bottom Return
Side Return
All
All
Downflow economizer with barometric relief
Horizontal economizer without barometric relief
Slab Economizer, 42” tall cabinet
2EE04705424
2EE047055241
2EE047056242
2EE047052242
42"
50"
ERV or End Return
Slab Economizer, 50” tall cabinet
1
2
Barometric relief must be ordered seperately and installed in duct work.
Barometric relief or fresh air hood not included. Must be ordered seperately.
Unitary Products Group
39
246646-YTG-C-0606
2EE04705424
Fresh Air Hood Fresh Air Damper Return Air Damper
Barometric Relief Damper
2EE04705424
2EE04705424
2EE04705424
2EE04705424
Barometric Relief Hood
FIGURE 11 - FACTORY INSTALLED DOWNFLOW ECONOMIZER
2EE04705424
Fresh Air Hood
2EE04705424 2EE04705424
Fresh Air Damper Return Air Damper
2PE047032XX
Power Exhaust
2EE04705424
Barometric Relief Damper
2EE04705424
Barometric Relief Hood
FIGURE 12 - FIELD INSTALLED DOWNFLOW ECONOMIZER W/POWER EXHAUST
40
Unitary Products Group
246646-YTG-C-0606
2EE04705524
Return Air Damper
Field Installed
Duct Work
2EE04705524
Fresh Air Damper
2PE047032XX
Power Exhaust
1EH0408
Barometric
Relief Damper
1EH0408
Barometric
Relief Hood
2EE04705524
Fresh Air Hood
FIGURE 13 - FIELD INSTALLED HORIZONTAL ECONOMIZER W/POWER EXHAUST
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer
2PE047032XX
Power Exhaust
1EH0409 Barometric
Relief Damper
1EH0409 Barometric
Relief Hood
FIGURE 14 - SLAB ECONOMIZER DOWNFLOW W/POWER EXHAUST
Unitary Products Group
41
246646-YTG-C-0606
1EH0409
Fresh Air Hood
Field Installed
Duct Work
2EE04705X24
Slab Economizer
1EH0409
Barometric Relief Hood
2PE047032XX
Power Exhaust
1EH0409
Barometric Relief Damper
FIGURE 15 - SLAB ECONOMIZER END RETURN W/POWER EXHAUST
42
Unitary Products Group
246646-YTG-C-0606
FIGURE 16 - COOLING UNIT WITH GAS HEAT WIRING 230 VOLT DIAGRAM
Unitary Products Group
43
246646-YTG-C-0606
FIGURE 17 - COOLING UNIT WITH/WITHOUT ELECTRIC HEAT WIRING DIAGRAM
44
Unitary Products Group
246646-YTG-C-0606
FIGURE 18 - COOLING UNIT WITH GAS HEAT WIRING 460, 575 VOLT 50 HZ DIAGRAM
Unitary Products Group
45
246646-YTG-C-0606
GUIDE SPECIFICATIONS
PREDATOR®
DH 078, 090, 102, 120 & 150, 11.5 EER
GENERAL
of the coils. Condensate pan shall be slide out design, con-
structed of a non corrosive material, internally sloped and
conforming to ASHRAE 62-B9 standards. Condensate con-
nection shall be a minimum of ¾” I.D. female and be rigid
mount connection.
Units shall be manufactured by York International Unitary
Products Group in an ISO 9001 certified facility. YORK®
Predator units are convertible single packages with a com-
®
mon footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors
with independent refrigeration circuits to provide 2 stages of
cooling. The units were designed for light commercial appli-
cations and can be easily installed on a roof curb, slab, or
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall
not exceed the motors nameplate horsepower rating plus the
service factor. Units shall be designed to operate within the
service factor. Fan wheel shall be double inlet type with for-
ward curve blades, dynamically balanced to operate
smoothly throughout the entire range of operation. Airflow
design shall be constant volume. Bearings shall be sealed
and permanently lubricated for longer life and no mainte-
nance. Entire blower assembly and motor shall be slide out
design.
®
frame. All Predator units are self-contained and assembled
on rigid full perimeter base rails allowing for 3-way forklift
access and overhead rigging. Every unit is completely
charged, wired, piped, and tested at the factory to provide a
quick and easy field installation. All units are convertible
between side and down airflow. Independent economizer
designs are used on side and down discharge applications,
®
as well as all tonnage sizes. Predator units are available in
the following configurations: cooling only, cooling with electric
heat, and cooling with gas heat. Electric heaters are available
as factory-installed options or field-installed accessories.
OUTDOOR (CONDENSER) FAN ASSEMBLY
DESCRIPTION
The outdoor fans shall be of the direct drive type, discharge
air vertically, have aluminum blades riveted to corrosion
resistant steel spider brackets and shall be dynamically bal-
anced for smooth operation. The outdoor fan motors shall
have permanently lubricated bearings internally protected
against overload conditions and staged independently. A
cleaning window shall be provided on two sides of the units
for coil cleaning.
Units shall be factory assembled, single package, (Elec/Elec,
Gas/Elec), designed for outdoor installation. Units shall have
a minimum EER of 9.0. They shall have built in field convert-
ible duct connections for down discharge supply/return or
horizontal discharge supply/return and be available with fac-
tory installed options or field installed accessories. The units
shall be factory wired, piped and charged with R-22 refriger-
ant and factory tested prior to shipment. All unit wiring shall
be both numbered and color coded. The cooling performance
shall be rated in accordance with DOE and ARI test proce-
dures. Units shall be CSA certified to ANSI Z21.47 and UL
1995/CAN/CSA No. 236-M90 standards.
REFRIGERANT COMPONENTS
Compressors:
A. Shall be fully hermetic type, direct drive, internally pro-
tected with internal high-pressure relief and over temper-
ature protection. The hermetic motor shall be suction gas
cooled and have a voltage range of + or – 10% of the
unit nameplate voltage.
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up
to 1” thick insulation coated on the airside. Aluminum foil
faced insulation shall be used in the unit’s compartments and
be fastened to prevent insulation from entering the air
stream. Cabinet doors shall be hinged with toolless access
for easy servicing and maintenance. Full perimeter base rails
shall be provided to assure reliable transit of equipment,
overhead rigging, fork truck access and proper sealing on
roof curb applications. Disposable 2” filters shall be furnished
and be accessible through hinged access door. Fan perfor-
mance measuring ports shall be provided on the outside of
the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating bypass
B. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
A. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
B. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
46
Unitary Products Group
246646-YTG-C-0606
Refrigerant Circuit and Refrigerant Safety Components shall
include:
shot type, constructed of aluminum-coated steel. All gas pip-
ing shall enter the unit cabinet at a single location, through
either the side or bottom, without any field modifications. An
integrated control board shall provide timed control of evapo-
rator fan functioning and burner ignition. Heating section shall
be provided with the following minimum protection:
A. Independent fixed-orifice or thermally operated expan-
sion devices.
B. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
A. Primary and auxiliary high-temperature limit switches.
B. Induced draft pressure sensor.
C. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
C. Flame roll out switch (manual reset).
D. Flame proving controls. Unit shall have two independent
st
nd
D. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
stages of capacity (60% 1 stage, 100% 2 stage).
ELECTRIC HEATING SECTION (IF EQUIPPED)
Unit Controls:
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two
states of capacity all sizes. The heating section shall have a
primary limit control(s) (automatic reset) to prevent the heat-
ing element system from operating at an excessive tempera-
ture. The Heating Section assembly shall slide out of the unit
for easy maintenance and service. Units with Electric Heating
Sections shall be wired for a single point power supply with
branch circuit fusing (where required).
A. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
B. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
should any of the following standard safety devices trip
and shut off compressor:
C. Loss-of-charge/Low-pressure switch.
(1) High-pressure switch.
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF out-
door temperature, exceeding maximum load criteria of ARI
Standard 340/360. The compressor, with standard controls,
shall be capable of operation down to 0 ºF outdoor tempera-
ture. Unit shall be provided with fan time delay to prevent cold
air delivery before heat exchanger warms up. (Gas heat only)
(2) Freeze-protection thermostat, evaporator coil. If any
of the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that indi-
cates which safety switch has tripped.
D. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
E. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
F. Unit control board shall have on-board diagnostics and
fault code display.
STANDARD LIMITED WARRANTIES - Compressor – 5
Years, Heat Exchanger – 10 Years, Elect. Heat Elem. – 5
Years, Parts – 1 Year
G. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall
be made available by either/or):
H. Control board shall monitor each refrigerant safety
switch independently.
1. ELECTRONIC ENTHALPY AUTOMATIC ECONO-
MIZER – Outdoor and return air dampers that are inter-
locked and positioned by a fully-modulating, spring-
return damper actuator. The maximum leakage rate for
the outdoor air intake dampers shall not exceed 2%
when dampers are fully closed and operating against a
pressure differential of 0.5 IWG. A unit-mounted potenti-
ometer shall be provided to adjust the outdoor and return
air damper assembly to take in outdoor air to meet the
minimum ventilation requirement of the conditioned
space during normal operation. During economizer oper-
ation, a mixed-air temperature control shall modulate the
I. Control board shall retain last 5 fault codes in non-vola-
tile memory, which will not be lost in the event of a power
loss.
GAS HEATING SECTION (IF EQUIPPED)
Heat exchanger and exhaust system shall be constructed of
aluminized steel and shall be designed with induced draft
combustion with post purge logic, energy saving direct spark
ignition, and redundant main gas valve. The heat exchanger
shall be of the tubular type, constructed of T1-40 aluminized
steel for corrosion resistance and allowing minimum mixed
air entering temperature of 40 ºF. Burners shall be of the in-
Unitary Products Group
47
outdoor and return air damper assembly to prevent the
supply air temperature from dropping below 55 ºF.
Changeover from compressor to economizer operation
shall be provided by an integral electronic enthalpy con-
trol that feeds input into the basic module. The outdoor
intake opening shall be covered with a rain hood that
matches the exterior of the unit. Water eliminator/filters
shall be provided. Simultaneous economizer/compressor
operation is also possible. Dampers shall fully close on
power loss. Available with barometric relief or power
exhaust.
•
•
•
COIL GUARD - Designed to prevent condenser coil
damage.
BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high-
pressure drop across the filters.
•
•
BREAKER – An HACR breaker can be factory installed
on gas heat units or cooling units with electric heat.
2. MOTORIZED OUTDOOR AIR DAMPERS – Outdoor
and return air dampers that are interlocked and posi-
tioned by a 2-position, spring-return damper actuator.
The maximum leakage rate for the outdoor air intake
dampers shall not exceed 2% when dampers are fully
closed and operating against a pressure differential of
0.5 IWG. A unit-mounted potentiometer shall be provided
to adjust the outdoor and return air damper assembly to
take in the design CFM of outdoor air to meet the ventila-
tion requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected posi-
tions – regardless of the outdoor air enthalpy. Dampers
return to the fully closed position when the indoor fan
motor is de-energized. Dampers shall fully close on
power loss.
DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest elec-
tric heat available.
•
•
STAINLESS STEEL HEAT EXCHANGER – For applica-
tions in a corrosive environment, this option provides a
full stainless steel heat exchanger assembly.
SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air com-
partments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
•
ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
•
BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
ADDITIONAL FACTORY INSTALLED OPTIONS
•
ALTERNATE INDOOR BLOWER MOTOR – For appli-
cations with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
•
•
PROPANE CONVERSION KIT – Contains new orifices
and gas valve springs to convert from natural to L.P. gas.
•
•
•
CONVENIENCE OUTLET (POWERED/NON-POWERED)–
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
60ºF GAS HEAT KIT – Provides an electric heat kit for
the gas compartment for use in extreme low ambient
conditions.
ELECTRIC HEAT - Electric Heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
•
•
ECONOMIZER (Downflow and Horizontal flow)
POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
PHASE MONITOR - Designed to prevent damage in out-
of-phase condition.
•
DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Subject to change without notice. Printed in U.S.A.