Trane Air Cleaner Cah Svx01a En User Manual

Installation  
Operation  
Maintenance  
Custom  
Climate Changer™  
Air Handlers  
Part No. X39640745010  
July 2005  
CAH-SVX01A-EN  
Introduction  
Use this manual to install, startup,  
operate, and maintain the Custom  
Climate Changer™ air handler.  
Carefully review the procedures  
discussed in this manual to minimize  
installation and startup difficulties.  
Custom Climate Changer™ air  
handlers ship as complete  
assemblies or in sections. Some  
jobsite assembly is required when  
the units ship in sections.  
Refrigerant used in any type of air-  
conditioning or refrigerating  
equipment should be recovered for  
reuse, recovered and/or recycled for  
reuse, reprocessed (reclaimed), or  
properly destroyed, whenever it is  
removed from equipment. Never  
release it to the atmosphere!  
Protecting the  
Environment  
World environmental scientists have  
concluded, based on the best  
currently available evidence, that  
ozone in our upper atmosphere is  
being reduced due to the release of  
CFC (chlorofluorocarbon) fully  
halogenated compounds.  
Unit Description  
Custom Climate Changer™ air  
handlers are designed for a variety  
of controlled-air applications. The  
basic unit consists of a fan, heating  
and/or cooling coils, filters, and  
dampers. See the unit submittal  
drawings for detailed descriptions.  
Each unit is provided with a  
nameplate. This nameplate includes  
unit model number, serial number  
and electrical data.  
Trane urges that all HVAC servicers  
working on Trane equipment, or any  
manufacturers products, make  
every effort to eliminate, if possible,  
or vigorously reduce the emission of  
CFC, HCFC (halocarbon that contains  
fluorine, chlorine, carbon, and  
hydrogen), and HFC (halocarbon  
that contains only fluorine, carbon,  
and hydrogen) refrigerants to the  
atmosphere resulting from  
installation, operation, routine  
maintenance, or major service on  
this equipment. Always act in a  
responsible manner to conserve  
refrigerants for continued use even  
when acceptable alternatives are  
available.  
The fans are internally isolated. To  
insure fan stability, the unit ships  
with a minimum of four lock-down  
devices that prevent the fan from  
shifting during shipment and  
installation. These spacers must be  
removed prior to fan operation to  
assure proper vibration isolation.  
Retain these spacers for use in  
adjusting fan isolators if required.  
The units are available with factory  
mounted controls for climate and  
humidity control. These can be use as  
stand-alone devices or operate with a  
complete controls system. End devices  
include factory-mounted starters and  
variable speed drives.  
CAH-SVX01A-EN  
3
Contents  
Introduction .........................................................................3  
Unit Description .................................................................................. 3  
Protecting the Environment ................................................................ 3  
Contents ...............................................................................4  
General Information ............................................................5  
Operating Environment ....................................................................... 5  
Controls ............................................................................................... 5  
Ultraviolet (UV) Germicidal Irradiation Lights (optional) ....................... 6  
Pre-Installation Requirements ...........................................7  
Receiving Checklist ............................................................................. 7  
Resolving Shipping Damage ............................................................... 7  
Job Site Storage Recommendations ................................................... 7  
Preparing the Unit Site ........................................................................ 8  
Roof Curb Installation .......................................................................... 9  
Installation ......................................................................... 10  
Lifting and Rigging .............................................................................10  
Unit Assembly ....................................................................................11  
TCP Model Assembly Instructions .................................................... 12  
TCC Model Assembly Instructions .....................................................17  
Duct Connections ............................................................................. 24  
Component Installation Requirements ............................................. 24  
Coil Piping and Connections ............................................................. 28  
Wiring ................................................................................................ 41  
External Insulating Requirements ..................................................... 42  
Startup ...............................................................................43  
Pre-Startup Checklist ......................................................................... 43  
Unit Operation................................................................................... 44  
Determine Fan Speed ....................................................................... 47  
Sheave Alignment ............................................................................. 47  
Multibelt Check ................................................................................. 47  
Routine Maintenance ........................................................48  
Air Filters ........................................................................................... 49  
Drain Pans ......................................................................................... 50  
Fans ................................................................................................... 50  
Coils .................................................................................................. 52  
Moisture Purge Cycle ........................................................................ 53  
Internal Insulation .............................................................................. 54  
Ultraviolet (UV) Germicidal Irradiation Lights ..................................... 55  
Troubleshooting ................................................................56  
4
CAH-SVX01A-EN  
General  
Information  
Factory-mounted control systems  
ordered with factory-mounted  
starters or VFDs are supplied with  
line to 24 Vac control transformers.  
No additional power wiring is  
required.  
Operating  
Controls  
Environment  
Wiring Sizes and  
Connections  
When considering the placement of  
the Custom Climate Changer air  
handler, it is important to consider  
the operating environment. The  
acceptable ambient temperature  
range for unit operation is -40ºF to  
140ºF (-40ºC to 60ºC).  
As a standard, there are no  
For a more in-depth understanding  
of controls, refer to the following  
manuals:  
penetrations into the Custom air  
handler for any field-provided wiring  
or device. Before installation,  
consider overall unit serviceability  
and accessibility before mounting,  
running wires (power), making  
cabinet penetrations, or mounting  
any components to the module  
cabinet.  
For factory-configured AH540/  
AH541 controllers,  
For heating applications, a special  
motor may be required to withstand  
the higher temperatures. Motors  
with Class B insulation are  
CNT-SVX05B-EN  
For programmable MP580  
controllers, CNT-SVP01A-EN  
acceptable for ambient  
For hardware installation,  
CNT-SVN01A-EN  
temperatures up to 104º F, while  
motors with Class F insulation can  
withstand ambient temperatures to  
+140º F (60º C).  
Wiring to the unit must be provided  
by the installer and must comply  
with all national and local electrical  
codes. The fan motor nameplate  
includes a wiring diagram. If there  
are any questions concerning the  
wiring of the motor, be sure to write  
down the information from the  
motor nameplate and contact your  
local fan motor manufacturer  
For Danfoss VFD,  
TR1-SVX10A-EN  
For universal programmable  
control modules (UPCMs):  
For the units furnished with gas  
furnaces, the heating demands  
require a special motor to withstand  
the higher temperatures. These  
motors are furnished with Class “H”  
insulation to withstand this rigorous  
duty.  
EMTX-PG-5  
EMTX-IN-22A  
Custom air handlers and/or field-  
installed accessories that must be  
stored for a period of time prior to being  
installed must be protected from the  
elements. All controllers and electrical/  
electronic components should be  
stored in conditions of -20 to 120°F and  
5- to 95-percent relative humidity non-  
condensing. Electrical components are  
not moisture-tolerant.  
representative for assistance.  
Note: The customer should provide  
adequate freeze protection for the  
coils.  
Factory-Mounted Controls  
Small items that cannot be factory  
mounted will ship inside the control  
enclosures. Larger items may ship  
inside the fan module.  
Note: All control valves ship directly  
to the “ship-to address” from the  
vendor unless another address is  
given on the Trane sales order.  
Note: The warranty will not cover  
damage to the unit or controls due  
to negligence during storage. A  
controlled indoor environment is  
recommended for proper storage.  
For further storage considerations,  
refer to “Job Site Storage  
Depending on job requirements, the  
customer may need to provide  
120 Vac control power. A dedicated  
15-amp circuit is recommended.  
Recommendations” on page 7.  
CAH-SVX01A-EN  
5
General Information  
ƽ WARNING  
Ultraviolet (UV)  
Germicidal  
Irradiation Lights  
(optional)  
Equipment Damage From  
Ultraviolet (UV) Lights!  
Trane does not recommend field  
installation of ultraviolet lights in its  
air handling equipment for the  
intended purpose of improving  
indoor air quality. High intensity C-  
band ultraviolet light is known to  
severely damage polymer (plastic)  
materials and poses a personal  
safety risk to anyone exposed to the  
light without proper personal  
protective equipment (can cause  
damage to eyes and skin). Polymer  
materials commonly found in HVAC  
equipment that may be susceptible  
include insulation on electrical  
wiring, fan belts, thermal insulation,  
various fasteners and bushings.  
Degradation of these materials can  
result in serious damage to the  
equipment.  
The United States Environmental  
Protection Agency (EPA) believes  
that molds and bacteria inside  
buildings have the potential to cause  
health problems in sensitive  
(1)  
individuals . If specified, Trane  
provides ultraviolet lights (UV-C) as  
a factory-engineered and installed  
option in select commercial air  
handling products.  
When UV lights are factory provided,  
polymer materials that are  
susceptible to deterioration by the  
UV-C light will be substituted or  
shielded from direct exposure to the  
light.  
In addition, UV-C radiation can  
damage human tissue, namely eyes  
and skin. To reduce the potential for  
inadvertent exposure to the lights by  
operating and maintenance  
personnel, electrical interlocks that  
automatically disconnect power to  
the lights are provided at all unit  
entry points to equipment where  
lights are located.  
Trane accepts no responsibility for  
the performance or operation of our  
air handling equipment in which  
ultraviolet devices were installed  
outside of the Trane factory.  
1.United Sates Environmental Protection Agency; A  
Brief Guide to Mold, Moisture and your Home;  
Brochure EPA 402-K-02-003.  
6
CAH-SVX01A-EN  
Pre-Installation  
Requirements  
7
Manually rotate the fan wheel to  
ensure free movement of the  
shaft, bearings, and drive.  
Inspect the fan housing for any  
foreign objects.  
Note: Do not attempt to repair the  
unit without consulting the  
delivering carrier.  
Receiving Checklist  
Based on customer requirements,  
Custom Climate Changer air  
handlers can ship as complete units  
or as individual sections to be field  
assembled.  
3
Notify your Trane sales  
representative of the damage  
and arrange for repair.  
8
9
Locate assembly hardware.  
Note: Do not attempt to repair the  
unit without consulting the Trane  
sales representative.  
Upon receipt of the unit(s) and prior  
to unloading, remove any shipping  
material and inspect the unit for  
damage and verify that the shipment  
is complete.  
Inspect and test all piping for  
possible shipping damage.  
Nipples may be installed on coils  
at the factory but should always  
be tightened and tested before  
any connections are made.  
Rough handling during shipping,  
in addition to other factors can  
cause pipe connections to  
become loose.  
4
Keep the damaged material in  
the same location as it was  
received.  
Note: Delivery cannot be refused.  
Trane is not responsible for shipping  
damage.  
Note: It is the receiver's  
responsibility to provide reasonable  
evidence that concealed damage  
was not incurred after delivery.  
1
2
3
Visually inspect components for  
any damage that may have  
occurred during shipment.  
Note: Trane will not be responsible  
for any leak at the field connections.  
Coils have been factory pressure  
tested before shipping.  
Check all access doors to confirm  
that the latches and hinges are  
not damaged.  
Job Site Storage  
Recommendations  
Custom units and/or field-installed  
accessories that must be stored for a  
period of time before installation  
must be protected from the  
elements. A controlled indoor  
environment is recommended for  
proper storage.  
Inspect the interior of each  
Resolving Shipping  
Damage  
Trane air handlers ship free on board  
(FOB), meaning that the unit belongs  
to the customer the moment the  
delivery truck leaves the factory. If  
damage has occurred to the unit  
during shipment, follow these  
instructions:  
section for any internal damage.  
Note: Concealed damage must be  
reported within 15 days of receipt.  
4
Inspect the coils for damage to  
the fin surface and/or coil  
connections.  
Note: The warranty does not cover  
damage to the unit or controls due  
to negligence during storage.  
5
If the unit was ordered with  
factory-mounted controls, locate  
all sensors.  
Note: Trane is not responsible for  
shipping damage.  
CAUTION  
Use Canvas Only!  
Use only canvas tarps to cover air  
handlers. Plastic tarps cause  
condensation to form in and on the  
equipment, which can result in  
corrosion damage or wet storage  
stains.  
Note: Items that cannot be factory-  
mounted should ship inside the  
control enclosures or should be  
packaged inside the fan module or  
mixing box module.  
1
Make specific notation,  
describing the damage, on the  
freight bill. Take photos of the  
damaged material, if possible.  
6
Check all devices attached to the  
unit exterior and confirm that  
they are not damaged.  
2
Report all claims of shipping  
damage to the delivering carrier  
immediately and coordinate  
carrier inspection, if necessary.  
CAH-SVX01A-EN  
7
Pre-Installation Requirements  
4
Cover the unit securely with a  
canvas tarp.  
5
Confirm the foundation of the  
mounting platform is level and  
large enough to include the unit  
dimensions (refer to the unit  
submittals for specific  
General Storage  
The unit controller and all other  
electrical/electronic components  
should be stored in conditions of  
-20ºF to 120°F and 5 to 95 percent  
relative humidity, non-condensing.  
Electrical components are not  
moisture-tolerant. Factory protective  
coverings should be removed prior  
to storage.  
5
6
Do not stack units.  
Do not pile other material on the  
unit.  
dimensions).  
6
7
Provide adequate lighting for  
maintenance personnel to  
perform maintenance duties.  
Preparing the Unit  
Site  
Provide permanent power  
outlets in close proximity to the  
unit for installation and  
maintenance.  
1
Ensure the installation site can  
support the total weight of the  
unit. The building roof must be  
able to support the entire weight  
of the unit, roof curb and  
Long-Term Storage  
For longer periods of storage, allow  
proper clearance around the unit to  
perform periodic inspection and  
maintenance of the equipment.  
8
9
Depending upon job  
requirements, the customer may  
need to provide 120 Vac power to  
the unit controller. Refer to  
submittals for more information.  
A dedicated 15-amp circuit is  
recommended.  
accessories. Refer to the unit  
submittals for weights.  
While the unit is in storage:  
Every two weeks, rotate the fan  
and motor shaft 30 revolutions  
by hand.  
2
Allow sufficient space to allow  
adequate free air and necessary  
service access. Refer to  
submittals for specific  
minimums.  
Every six months, check fan shaft  
bearings and grease lines. Add  
grease using a manual grease  
gun following the lubrications  
recommendations in “Fan  
Wiring for Custom units must be  
provided by the installer and  
must comply with all national  
and local electrical codes.  
3
4
Allow room for supply and  
return piping, ductwork,  
electrical connections, and coil  
removal.  
Bearing Lubrication” on page 51.  
10 Rooftop curb mounted units  
must be sealed tightly to the  
curb. Use proper sealants and  
roof to curb sealing techniques  
to prevent water and air leakage.  
Outdoor Storage  
Considerations  
Ensure there is adequate height  
for condensate drain  
requirements. See “Drain Pan  
Trapping” on page 29.  
Outdoor storage is not  
recommended; however, when  
outdoor storage is necessary,  
several things must be done to  
prevent damage:  
Note: Preparation of the roof curb or  
pier mount and roof openings  
should be completed prior to lifting  
the unit to the roof.  
Note: Inadequate height may  
necessitate core-drilling the floor to  
attain proper trap height. Insufficient  
height could inhibit condensate  
drainage and result in flooding the  
unit and/or equipment room.  
Note: Keep the equipment in the  
original shipping container for  
protection and ease of handling.  
1
Select a well-drained area,  
preferably a concrete pad or  
blacktop surface.  
ƽ WARNING  
Level Foundation!  
2
Place the unit on a dry surface or  
raised off the ground to assure  
adequate air circulation beneath  
the unit and to assure no portion  
of the unit will contact standing  
water at any time.  
The floor or foundation must be  
level and the condensate drain at  
the proper height for proper coil  
drainage and condensate flow.  
Standing water and wet surfaces  
inside air-handling units could result  
in microbial growth, which may  
cause unpleasant odors, serious  
health problems, or death.  
3
Loosen the belt tension on the  
drive belts.  
8
CAH-SVX01A-EN  
Pre-Installation Requirements  
Typical Curb Installation  
Checklist  
Roof Curb  
Installation  
Verify that the roof structure can  
adequately support the  
combined weight of the unit and  
curb assembly.  
It is recommended that the curb be  
installed directly on the support  
members and fastened to the  
supports using tack welds or other  
equivalent methods. Properly  
supported decking should be  
installed inside the air handler  
section of the curb when this  
method is used. (See Figure 1)  
Ensure that the selected  
installation location provides  
sufficient service and operational  
clearances.  
Remove any twist within the curb  
due to roof supports and square  
the curb.  
Level the curb.  
Secure the curb to the roof  
support members.  
Install 2-inch thick boards or rigid  
insulation around the curb.  
Figure 1. Cross section of typical curb installation on new construction  
Install cant strips around the  
curb.  
Bring field supplied roofing felt  
up to the top of the curb nailing  
strips. ail felt into place.  
Install field supplied flashing  
under the lip of the curb flanges  
and over the felt.  
Apply sealant to the four  
corners. Caulk all joints  
between the curb and the  
roof. Attach the gasket  
material to the curbs top  
flanges (entire perimeter) and  
to the supply and return air  
duct opening panel flanges.  
CAH-SVX01A-EN  
9
Installation  
Lifting and Rigging  
Figure 3. Use proper lifting and rigging methods  
ƽ WARNING  
Lifting and Rigging!  
Do not lift, rig, or ceiling-suspend  
from the top of the unit. Lift from  
lifting lugs only, located at the  
bottom of the unit. Use all lifting  
lugs provided.  
Do not use cables (chains or slings)  
except as shown. Each of the cables  
(chains or slings) used to lift the unit  
must be capable of supporting the  
entire weight of the unit. Lifting  
cables (chains or slings) may not be  
of the same length. Adjust as  
necessary for even unit lift.  
Do not use a fork lift for handling  
units. This may result in equipment  
damage. Trane is not responsible for  
equipment damage resulting from  
improper forklifting practices.  
Test lift unit approximately 24 inches  
to verify proper center of gravity lift  
point. To avoid dropping of unit,  
reposition lifting point if unit is not  
level.  
General Lifting  
Considerations  
Per job requirements, air handlers  
will ship as a complete assembly or  
in sections.  
Always rig subassemblies or  
sections as they ship from the  
factory. See the unit submittal  
drawings for correct placement  
of sections.  
Always place, assemble, and  
suspend sections one at a time.  
Trane recommends that the  
contractor use spreader bars and  
slings to rig units and  
Failure to follow instructions could  
result in death or serious injury or  
equipment damage.  
subassemblies.  
Always assemble unit at the  
installation site. Never bolt  
sections together before rigging.  
Before preparing the unit for lifting,  
estimate the approximate center of  
gravity for lifting safety. Because of  
the placement of internal  
components, the unit weight may be  
unevenly distributed, with more  
weight in the coil and fan areas.  
Refer to the unit submittals for  
section weights. Test the unit for  
proper balance and rigging before  
lifting.  
Figure 2. Recommended attachment to  
lifting lugs.  
Make the loop of the sling  
parallel to the direction of  
airflow, if possible.  
Each of the cables used to lift the  
unit must be capable of  
supporting the entire weight of  
the unit.  
When hoisting the unit into  
position, use the proper rigging  
method, such as straps, slings,  
spreader bars, or lifting lugs for  
protection and safety.  
Note: Never lift units in windy  
conditions.  
10  
CAH-SVX01A-EN  
Installation  
Personnel should be positioned  
overhead and on the ground to  
guide the crane or helicopter  
operator in positioning the  
sections.  
The building roof must be able to  
support the entire weight of the unit,  
roof curb and accessories. See  
submittals for approximate unit  
weights.  
Unit Assembly  
Note: If the unit is shipped as a  
complete assembly, go to “Coil  
Piping and Connections” on  
page 28.  
The air handler is not designed  
to be lifted, rigged or ceiling  
suspended from the top of the  
unit.  
Preparation of the roof curb or  
pier mount and roof openings  
should be completed prior to  
lifting the unit to the roof.  
Prior to unit assembly, refer to the  
unit submittal drawings and unit  
tagging for correct placement of  
sections. Failure to review the  
submittal drawings could result in  
performance or assembly problems.  
If there are any discrepancies,  
contact your local Trane sales  
representative before proceeding.  
Never stack the pipe cabinet and  
inlet hoods on the unit as the  
unit is being lifted.  
Check that the gasketing or  
sealant on the roof curb is intact  
and provides an airtight seal with  
the unit base.  
Do not attach the intake/exhaust  
hoods to the unit prior to lifting  
the unit. Doing so may damage  
the equipment. Attach the hoods  
to the unit only after all sections  
are in place.  
Complete all ductwork, piping  
and electrical connections only  
after mounting the unit.  
All shipping supports and crating on  
the face of the sections must be  
removed and discarded to permit  
proper fit-up and sealing of the  
surfaces.  
Assembly Hardware  
Air handlers ship with all necessary  
assembly hardware and gasket  
material. This hardware is packaged  
in either a clear plastic envelope or  
cardboard box and can be found  
inside one of the sections. If space  
inside a section is not adequate, a  
crate or pallet will be loaded onto  
the bed of the truck. Check the Parts  
List on the Field Assembly drawing  
against the contents of the crate. Do  
not proceed with unit assembly until  
verification that all materials are  
present. The number of sections to  
be assembled often makes it  
Units may be mounted on the roof  
with a roof curb or pier mount. Units  
may be mounted indoors on  
housekeeping pads. Refer to  
submittals for unit dimensions and  
openings.  
Note: For proper operation, the unit  
must be supported around the entire  
unit base perimeter. If the unit is  
shipped in sections, the entire  
section perimeter must be  
supported, as well as at the base  
channels of the unit splits.  
necessary to use more than one  
section to ship the material. Please  
check all sections thoroughly before  
contacting your local Trane sales  
engineer to report missing  
Provide clearance around the unit to  
allow adequate free air and  
necessary service access. Also,  
allow room for supply and return  
piping, ductwork, electrical  
hardware.  
connections, and coil removal.  
CAH-SVX01A-EN  
11  
Installation  
two sections should be within 12  
inches to reduce the amount of  
dragging required.  
Note: Failure to compress the  
gasketing may result in air leakage.  
TCP Model  
Assembly  
8
Secure the unit sections at the  
base using the field provided  
bolts, nuts and washers at the  
connecting plates.  
Instructions  
6
7
Remove lifting lugs on mating  
section as required.  
If your nameplate model number  
begins with TCP, use the assembly  
instructions below.  
Insert threaded rods through  
each hole of each mating  
connecting plate (see Figure 4).  
Bring each connecting surface  
together uniformly until  
9
Once the sections are pulled  
together, install the assembly  
hardware as applicable for the  
walls, roof, and the base as  
demonstrated in the following  
assembly sections.  
Joining Sections Edge-to-  
Edge  
gasketing is contacted.  
Units must be installed level for  
proper drainage of condensate from  
the drain pan. In addition, each  
section in a multi-section unit must  
be properly supported.  
Note: Use field provided threaded  
rods inserted in all holes of each  
connecting plate to prevent damage  
and distortion of the sections as they  
are joined. Tighten all rods in  
Note: Leveling each section,  
beginning with the first, is critical.  
Failure to level and align the  
sections immediately creates greater  
misalignment or even structural  
damage afterward.  
sequence. Do not try to join sections  
by tightening only some of the rods.  
Figure 4. Insert threaded rods through each hole of mating connecting plate.  
1
Remove all crating and wrapping  
from the surfaces to be joined.  
2
Place one section of the air  
handler into the desired position.  
Verify each section is level and  
properly supported prior to  
proceeding with assembly. Each  
unit must be level side-to-side  
and front to back. Check  
squareness measuring the  
critical dimensions given.  
3
4
When the unit is positioned and  
squareness is assured within 1/8-  
inch, remove all lifting lugs  
located along the split plane.  
Install 4-inch x 1/4-inch neoprene  
gasket to all mating surfaces of  
the section, including the internal  
walls. This gasket must be  
applied to the full perimeter of  
the section split of both sections  
to be joined.  
5
Move the next mating section  
into alignment with the  
positioned section. Alignment of  
sections must be completed  
before gasket surfaces meet. The  
12  
CAH-SVX01A-EN  
Installation  
3
4
Apply the 3-inch X 1/8-inch  
gasket evenly across the two  
joined edges of the splits.  
TCP Base Section  
Assembly (Typical)  
Note: Failure to completely  
compress the gasketing may result  
in air leakage.  
Before installing the pre-cut 4-  
inch 18 gauge joining strip over  
the gasket, pre-drill holes in the  
floor using the 4-inch strip as a  
guide with a 7/32-inch drill bit at  
12 inch centers.  
1
Join the two units and secure  
with field provided 5/8-inch flat  
washers and 5/8-inch X 2-1/2-inch  
grade 9 bolts though each of the  
six holes.  
5
Apply the 4-inch joining strip  
over the gasket and uniformly  
straddle the splits. Secure with  
number 14 sheet-metal screws at  
12-inch centers.  
2
Caulk the overlapping flange  
along the length of each split to  
maintain a seal.  
Note: Use a polyurethane or  
equivalent caulk.  
Figure 5. TCP base assembly  
PREDRILL HOLES  
18 GAUGE JOINING STRIP  
SECURE W/#14 S.M. SCREWS  
@ 12" CTR'S.  
WITH 7/32"  
DRILL BIT.  
4"  
3" X 1/8" GASKET  
ADD CAULKING BEFORE  
ADDING JOINING STRIPS.  
JOIN WITH  
5/8" FLAT WASHER  
SPLIT  
4" X 1/4" GASKET.  
SPLIT  
5/8" X 2 1/2" GRADE 9 BOLTS  
A
A
BASE ASSEMBLY.  
CAH-SVX01A-EN  
13  
Installation  
4
5
Apply the joining strip over the  
gasket and uniformly straddling  
the splits. Secure with number 10  
sheet metal screws.  
2
Add a bead of caulk along the  
length of the roof seams. Install  
the pre-cut J-cap over the seam  
and secure with number 14 sheet  
metal screws on 12-inch centers.  
TCP Wall Section Assembly  
(Typical)  
1
Apply the walls and join at the  
inside angles with number 14  
sheet-metal screws on 12-inch  
centers along the length of the  
angles.  
Fit the pre-cut hub cap over the  
joining strip the vertical height of  
the wall flush with the roof and  
secure it to the wall with number  
8 sheet metal screws. Fill the top  
and bottom openings with caulk  
as moisture seal. Pre drill holes  
with a number 29 bit.  
Note: Use a polyurethane or  
equivalent caulk. It may be  
necessary to clamp the joint  
together or predrill to prevent  
separation when drilling with  
screws.  
2
3
Apply the 1/8-inch gasket evenly  
to the exterior of the walls across  
the two joined edges of the  
splits.  
3
Apply caulk to the end cap  
interior surface. Secure the end  
cap on the J-cap with one  
number 10 screw.  
Before installing the pre-cut  
joining strip over the gasket, pre- TCP Outdoor Roof Section  
drill holes in the wall using the  
strip as a guide with a number 29  
drill bit at 12-inch centers.  
Assembly (Typical)  
1
Align the roof splits and join the  
interior section trim with number  
14 sheet metal screws on 12 inch  
centers.  
Figure 6. TCP outdoor roof assembly  
INSTALLING J-CAP  
SPLIT  
SPLIT  
SECTION TRIM ACTS AS  
AS JOINING ANGLE  
SECURE w/#14 S.M.  
@ 12" CENTERS.  
4" X 1/4" GASKET  
APPLY CAULKING TO END CAPS  
THEN SECURE END CAPS  
TO THE ENDS OF J CAP.  
J-CAP  
SECURE J-CAP  
W/#14 S.M. SCREWS.  
END CAP  
14  
CAH-SVX01A-EN  
Installation  
4
Before installing the pre-cut  
joining strip over the gasket, pre-  
drill holes in the roof using the  
strip as a guide with a number 29  
drill bit at 12-inch centers.  
TCP Indoor Roof Section  
Assembly (Typical)  
1
Align the walls and join the  
inside angles with number 14  
sheet metal screws on 12-inch  
centers along the length of the  
angles.  
5
6
Apply the joining strip over the  
gasket and uniformly straddling  
the splits. Secure with #10 sheet  
metal screws.  
2
3
Apply a bead of caulk along the  
length of the roof seam joint.  
Fit the pre-cut hub cap and  
secure it to the roof with #8 sheet  
metal screws. Fill the end  
openings with caulk as moisture  
seal. Note: Pre drill the screw  
holes with a number 29 bit.  
Apply the 1/8-inch gasket on the  
exterior of the roof evenly across  
the roof split.  
Figure 7. TCP indoor roof assembly  
JOINING STRIP  
PREDRILL HOLES  
WITH #29  
DRILL BIT.  
SECURE WITH #10 S.M. SCREWS.  
SECURE HUB CAP W/#8  
S.M. SCREWS.  
1/8" THICK GASKET  
(2) 1 1/4" X 6" GALVANIZED ANGLE  
SECURED W/ #14 S.M. SCREWS  
@ 12" CENTERS  
1/4" GASKET  
INDOOR  
ROOF ASSEMBLY COMPLETE  
SPLIT  
CAH-SVX01A-EN  
15  
Installation  
2
3
Apply caulk the length of the  
base between the 2-inch X 2-inch  
angle on the one base section  
and the wall on the adjoining  
section. See Illustration below.  
Note: Use a polyurethane or  
equivalent caulk.  
TCP Base to Interior Wall  
Section Assembly (Typical)  
Note: Failure to completely  
compress the gasketing may result  
in air leakage.  
1
Join the two units and secure  
with field provided 5/8-inch flat  
washers and 5/8-inch X 2-1/2-inch  
grade 9 bolts though each of the  
six holes.  
Secure the 2-inch X 2-inch angle  
to the adjoining wall with  
number 14 sheet-metal crews on  
12-inch centers along the length  
of the angle and wall.  
Figure 8. TCP base to interior wall sections  
4" X 1/4" GASKET  
INTERIOR  
WALL  
SECURE 2" X 2" ANGLE TO WALL  
W/#14 S.M. SCREWS @ 12" CTR'S  
CAULK  
SPLIT  
SPLIT  
INTERIOR  
WALL  
CAULK  
CAULK  
SPLIT  
SPLIT  
BASE TO WALL ASSEMBLY COMPLETE  
16  
CAH-SVX01A-EN  
Installation  
TCC Model  
Assembly  
Instructions  
Figure 9. Remove shipping blocks  
If your nameplate model number  
begins with TCC, use the assembly  
instructions below.  
Joining sections - Edge to  
Edge  
Units must be installed level for  
proper drainage of condensate from  
the drain pan and for squareness of  
the sections during installation. In  
addition, each section in a multi-  
section unit must be properly  
supported.  
Note: Leveling each section,  
beginning with the first section, is  
critical. Failure to level and align the  
sections immediately creates greater  
misalignment or even structural  
damage afterward.  
Remove all wooden blocks under  
the unit and shipping protection  
from adjoining surfaces (see  
Figure 9).  
Figure 10. Remove lifting lug bolts  
Place the first section of the air  
handler on the end of the roof  
curb or the housekeeping pad.  
The section must be level from  
side-to-side and front to back.  
Section squareness should be  
within 1/8-inch. Remove the  
bottom bolts from lifting lugs  
located at the shipping split (see  
Figure 10).  
CAH-SVX01A-EN  
17  
Installation  
Move the next unit section as  
close as possible from the  
previous section. The two  
sections should be close enough  
to reduce the amount of  
dragging required. This is  
particularly important when  
mounting on a roof curb to  
minimize damage to the sealant  
on the roof curb. Alignment of  
sections must be completed  
before drawing sections  
together.  
Apply 1.25-inch x 0.33-inch  
ribbed butyl tape to the shipping  
split channel and shipping split  
plates (see Figure 11).  
Figure 12. Remove bottom bolts from  
lifting lugs  
Verify the section is level prior to  
proceeding with the next section  
of the unit.  
Remove the bottom bolts from  
the shipping split lifting lugs (see  
Figure 12).  
Figure 11. Apply butyl tape to shipping splits  
18  
CAH-SVX01A-EN  
Installation  
Insert field provided threaded  
rods through the bottom lifting  
lug and shipping split plates on  
each sides of the unit. Draw both  
sides of the section together  
equally to prevent damage and  
distortion of the sections as they  
joined. Do not try to join sections  
by tightening only one side of  
the rods (see Figure 13).  
Figure 14. Add caulk along the seam  
Note: Field-provided threaded  
hardware should consist of 5/8-11x12  
inch threaded rods 5/8-inch lock  
washers and 5/8-inch nuts.  
Note: Failure to compress the butyl  
tape may result in air and water  
leakage.  
Once the sections are pulled  
together, add a bead of caulk  
(sikaflex) along the seam  
between the two perimeter caps  
(see Figure 14).  
Install the assembly hardware as  
applicable for the shipping split  
frame inside of unit, the walls,  
and the roof as demonstrated in  
the following assembly sections.  
Figure 13. Insert field provided threaded rods  
CAH-SVX01A-EN  
19  
Installation  
TCC internal shipping split  
frame assembly (typical)  
Join the two sections and secure  
with field provided ½-13x8.5 inch  
threaded rods, ½-inch flat  
washers and ½-inch lock washers  
through each of the holes  
provided in the internal shipping  
split frame (see Figure 15) This  
frame runs around the entire  
perimeter of the unit (see  
Figure 11).  
Figure 15. Join internal shipping split frame  
20  
CAH-SVX01A-EN  
Installation  
TCC wall sections  
assembly (typical)  
TCC indoor roof sections  
assembly (typical)  
Verify external unit squareness.  
Verify external unit squareness.  
Apply the 1.25-inch x 0.33-inch  
ribbed butyl tape to the exterior  
of the walls covering the seam of  
the two adjoining sections (see  
method sheet).  
Apply the 1.25-inch x 0.33-inch  
ribbed butyl tape to the exterior  
of the roofs covering the seam of  
the two adjoining sections (see  
method sheet).  
Install seam cap over the butyl,  
uniformly straddling the splits.  
Secure with the provided  
number 10 sheet metal screws  
(see Figure 16).  
Install seam cap over the butyl,  
uniformly straddling the splits.  
Secure with the provided  
number 10 sheet metal screws.  
Figure 16. Install seam cap over the butyl tape  
CAH-SVX01A-EN  
21  
Installation  
TCC outdoor roof sections  
assembly (typical)  
Join two outdoor roof panels  
together at the seams at the  
direction of airflow and secure  
them in place with 5/16-inch x  
3/4-inch bolts and 5/16 lock nuts.  
Cut the proper length of roof  
joint strip to cover the seam  
between two outdoor roof panels  
at the direction of airflow.  
(exclude single outdoor roof  
panel) (see Figure 17).  
Figure 17. Join outdoor roof panels at the seams  
22  
CAH-SVX01A-EN  
Installation  
Join outdoor roof panels  
together at the seams in the  
direction perpendicular to  
two outdoor roof panels overhang at  
the side the unit. Bend joint strip  
over roof panel and use two number  
10 sheet metal screws (one in each  
roof panel) to secure joint strip. Trim  
the roof joint strip to insure that it  
does not protrude more than  
airflow and secure them in place  
with 5/16-inch x 3/4-inch bolts  
and 5/16 lock nuts. Install the roof  
joint strip to cover the seam  
between two outdoor roof panels  
in the perpendicular to airflow  
direction of. Use 3/8-inch butyl  
tape to cover the seam between  
1/16-inch beyond outdoor roof  
overhang (see Figure 18).  
Figure 18. Trim roof joint strip  
CAH-SVX01A-EN  
23  
Installation  
ƽ WARNING  
To activate the isolation, remove the  
shipping tie-down blocks. Retain  
these blocks for use in adjusting  
isolators if necessary.  
Duct Connections  
Hazardous Voltage with  
Capacitors!  
All duct connections to the units  
should be installed in accordance  
with the standards of the National  
Fire Protection Association (NFPA)  
for selecting and installing of air  
conditioning and ventilating  
Disconnect all electric power,  
including remote disconnects and  
discharge all motor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing components provided by  
Trane or others, refer to the  
Isolator Adjustment  
Note: Isolators are pre-adjusted and  
set at the factory. Follow this  
systems other than residence type  
(NFPA 90A), and residence type  
warm air heating and air  
procedure only if necessary and as it  
applies to the isolators used in this  
unit. This procedure, for isolators  
can, and should be, performed by  
one person to ensure that the proper  
sequence is followed.  
conditioning systems (NFPA 90B).  
To ensure the highest fan efficiency,  
duct turns and transitions must be  
made carefully, minimizing air  
friction losses and turbulence.  
Proper duct work installation by such  
organizations as SMACNA (Sheet  
Metal and Air Conditioning  
appropriate manufacturer’s  
literature for allowable waiting  
periods for discharge of capacitors.  
Verify with an appropriate voltmeter  
that all capacitors have discharged.  
Failure to disconnect power and  
discharge capacitors before  
Isolators are selected for distribution  
of equipment weight, but may not all  
compress the same. This procedure  
assumes the base surface is level.  
Isolators are not intended to be  
leveling devices.  
Contractors National Association,  
Inc.) should be adhered to.  
servicing could result in death or  
serious injury.  
1
Verify that the shipping bolts that  
hold the fan base in a fixed  
position have been removed.  
Note: For additional information  
regarding the safe discharge of  
capacitors, see PROD-SVB06A-EN.  
Component  
Installation  
Requirements  
Each component in the Custom air  
handler may have installation  
requirements that could affect the  
units performance.  
2
Remove the jam nut on top of the  
isolator adjusting stud at the first  
isolator to be adjusted. Check  
that the shipping block is in  
place.  
Turn the adjusting nut 2 or 3 turns  
only, counterclockwise on each  
isolator in a sequenced manner. The  
equipment weight will compress the  
spring inside the housing  
approximately 1/4 inch.  
Note: For components included in  
the unit but not included in this  
manual, reference the component  
manufacturers specific Installation,  
Maintenance, and Operation  
manual. Copies of these manuals  
are either included in the package  
with this unit IOM or are attached to  
the components mounted in the  
unit.  
Figure 19. Isolator  
JAM NUT  
SHIPPING  
BOLT  
FAN BASE  
SHIPPING TIE-  
DOWN BLOCK  
(SHIM)  
Fans  
The fan and motor assembly are  
internally isolated. The fan and  
motor bases are bolted to a  
minimum of four spring isolators.  
The isolators are secured to the fan  
section support base. Shipping tie-  
down blocks are bolted to the  
isolators between the fan base and  
the isolator support frame.  
ADJUSTING  
NUT  
24  
CAH-SVX01A-EN  
Installation  
3
4
Check that the bushing on the  
isolator stud is centered in the  
isolator. Adjust to center by  
moving the stud in the fan base  
hole.  
The actuators, factory-mounted or  
field-supplied, are separately wired  
and controlled by a direct-digital  
controller or other building logic.  
Control Dampers  
If the damper actuators are not  
factory mounted install damper  
actuators and connecting linkage.  
Check damper operation and linkage  
alignment.  
VCM (Transducer) Calibration. The  
VCM has an auto-zero function that  
recalibrates the transducer once  
every minute.  
This procedure will raise the  
equipment load until the  
Damper blades should be non-  
binding. Adjust damper frame as  
necessary to ensure free blade  
movement.  
isolators are all off the shims  
(shipping tie-down blocks)  
approximately 1/32-inch (the  
thickness of a credit card), and  
the internal gap is approximately  
equal to the external gap.  
Input Power Signal. The only input  
signal the VCM needs is the 24 Vac  
power connected to terminals 1TB1-  
5 and 1TB1-6.  
Magnahelic Air Filter Gage  
Output Velocity Signal. The  
Check zero adjustment of the gage.  
Turn both vent valves to the “Vent”  
position and adjust the gage pointer  
to zero by means of the external  
adjustment screw in the face of the  
gage. After zeroing, turn the vent  
valves to the “Line” position.  
2 to 10 VDC linear output signal from  
the VCM represents air velocity. This  
voltage can be converted to  
represent airflow (cfm or L/s) using  
the formula below, Table 1 and data  
in your submittal package.  
Note: Do not adjust isolators once  
the fan base is off of the shipping tie  
down blocks.  
5
Continue adjusting other  
isolators in sequence and repeat  
the same adjustment. Continue  
until all isolators are adjusted.  
(volts 2)  
------------------------------  
Airflow = k (cfm @ 10V)  
8
6
Replace the jam nut on each  
isolator adjusting bolt, tighten  
the nut, and remove the shipping  
tie down block.  
OR  
(volts 2)  
------------------------------  
Airflow = k (L/s @ 10V)  
8
Altitude can be adjusted for by using  
the following factors:  
Traq™ Dampers  
Traq dampers are low-leak dampers  
that modulate and measure airflow.  
Each Traq damper module is  
supplied with a factory-mounted  
ventilation control module (VCM) on  
the interior of the mixing box  
module. The VCM has an input  
terminal for power and an output  
terminal for air velocity (see  
Figure 20).  
Table 1. Altitude adjustment factors  
Sea level = 1.0  
Elevation (feet)  
1000  
k
0.982  
0.964  
0.949  
0.930  
0.914  
0.897  
0.876  
0.860  
0.846  
0.825  
2000  
3000  
4000  
5000  
6000  
7000  
8000  
9000  
10,000  
Figure 20. Traq damper terminal connections  
Ventilation Control  
Module  
Velocity (2–10 Vdc)  
GND  
1TB1–3  
1TB1–4  
1TB1–5  
1TB1–6  
24 Vac  
GND  
CAH-SVX01A-EN  
25  
Installation  
Side Load Filters  
Air Filters  
Figure 21. C-70 fastener holds 2-inch  
filter  
Most filters in custom units are  
installed in unitary sheet metal  
frames. If unit is provided with side  
access rack, do the following for  
installation:  
Front Load Filters  
Most filters in custom units are  
installed in unitary sheet metal  
frames. Filters are secured with a  
metal clip. There are several  
different styles.  
2-inch or 4-inch flat filters.  
1
2
Disconnect the power to the unit.  
To install filters:  
Open the filter section access  
door and remove the filters and  
block-offs from their installed  
position.  
1
2
3
4
Disconnect power to the unit.  
Open or remove the filter clip.  
Remove the filter from the rack.  
Figure 22. C-86 fastener (shown) or C-  
77 fastener holds 4-inch pleated filters  
3
4
Slide the filter into the rack.  
Install new filters with the  
directional arrows pointing in the  
direction of airflow.  
Some side load racks will be  
provided with block-off plates.  
Install them into the rack last  
before closing the door.  
5
Secure the filter using the  
appropriate clip for each filter.  
5
Close and secure the door,  
making certain the door closes  
snug against the block-off (see  
Figure 25).  
Review Figure 21 through Figure 24  
for an explanation of the methods  
for securing the different types of  
filters.  
Figure 23. Bag filter show with C-70  
fastener  
The filters are often installed in a  
pre/post filter configuration. Be sure  
to note the order of installation.  
Note: Filters must have an airtight  
seal to prevent air bypass.  
ƽ WARNING  
Hazardous Voltage with  
Capacitors!  
Figure 24. C-80 spring fastener  
secures cartridge  
Disconnect all electric power,  
including remote disconnects and  
discharge all motor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing components provided by  
Trane or others, refer to the  
appropriate manufacturer’s  
literature for allowable waiting  
periods for discharge of capacitors.  
Verify with an appropriate voltmeter  
that all capacitors have discharged.  
Failure to disconnect power and  
discharge capacitors before  
servicing could result in death or  
serious injury.  
26  
CAH-SVX01A-EN  
Installation  
Bag or Cartridge Filters.  
Outdoor Unit Weather  
Hood(s)  
1
2
Disconnect power to the unit.  
1
Per the unit drawing determine  
mounting location of the unit  
weather hoods.  
Keeping the bag filters folded,  
slide each filter into the filter  
rack, pushing them tightly  
against the unit. Pleats should be  
in the vertical position.  
2
All weather hoods have been  
pre-fit on the unit and removed  
for separate shipping at the  
factory. Remove any factory  
mounted screws located in the  
weather hood mounting  
location.  
3
4
5
If using optional pre-filters, slide  
them into the appropriate filter  
rack.  
If block-offs are provided with the  
unit, slide the block-offs into the  
filter track.  
3
Using the factory provided  
screws mount the weather hoods  
to the unit.  
Close and secure the access  
door, making certain the door  
closes snug against the rack.  
Note: Note it is required that the  
hoods be sealed to the unit using  
field provided caulk or gasket.  
Note: The block-off is intended to  
make a seal when the access door is  
closed. It may require a few  
adjustments to ensure a proper seal.  
Figure 25. Filter block-off placement  
CAH-SVX01A-EN  
27  
Installation  
Note: The contractor is responsible  
for supplying the installation  
hardware.  
CAUTION  
Prevent Coil Damage!  
Coil Piping and  
Connections  
To prevent coil damage, do not use  
teflon-based products for any field  
connections because their high  
lubricity may allow connections to  
be over-tightened. Failure to use  
proper materials may cause coil  
header damage.  
For best results, use a short pipe  
nipple on the coil headers prior  
to making any welded flange or  
welded elbow type connections.  
General Recommendations  
Proper installation, piping, and  
trapping is necessary to ensure  
satisfactory coil operation and to  
prevent operational damage:  
Extended drain and vent  
connections are provided as  
standard on DD and D coils only.  
If extended drains and vents are  
required on other water coils,  
they must be field-installed or  
ordered as specials from the  
factory.  
Seal the piping penetration into the  
unit casing before insulating. Seal  
from inner panel to outer panel to  
prevent unconditioned air from  
entering the module. Failure to  
properly seal penetrations may  
cause water leakage.  
Support all piping independently  
of the coils.  
Provide swing joints or flexible  
fittings on all connections that  
are adjacent to heating coils to  
absorb thermal expansion and  
contraction strains.  
Pipe coils counterflow to airflow.  
When attaching the piping to the  
coil header, make the connection  
only tight enough to prevent  
leaks. Maximum recommended  
torque is 200 foot-pounds.  
If the coil was ordered with  
factory-mounted controls, install  
the control valves. The valves  
ship separately.  
CAUTION  
Use Approved Glycol!  
If glycol is used in chilled water or  
hot water systems, use a glycol  
approved for use with commercial  
cooling and heating systems and  
copper tube coils. Failure to do so  
may result in equipment damage.  
Use pipe sealer on all thread  
connections.  
After completing the piping  
connections, seal around pipe  
from inner panel to outer panel.  
CAUTION  
Use a Backup Wrench!  
Use a backup wrench when  
attaching piping to coils with copper  
headers to prevent damage to the  
coil header. Do not use brass  
connectors because they distort  
easily and may cause connection  
leaks.  
28  
CAH-SVX01A-EN  
Installation  
Drain Pan Trapping  
Threaded condensate drain  
Figure 26. Drain pan trapping for module under negative pressure  
connections are provided on only  
one side of the coil module. Pitch the  
connection lines horizontal or  
downward toward an open drain.  
Trane recommends installing a plug  
to facilitate cleaning of the trap.  
Figure 26 illustrates the proper  
trapping, piping, and operation of  
the trap for negative pressure  
modules. Use the formula under the  
figure to determine the correct  
minimum depth for the condensate  
trap.  
Figure 27 illustrates the proper  
trapping, piping, and operation of  
the trap for positive pressure  
modules.  
L = H + J + pipe diameter  
where:  
H = 1 inch for each inch of negative pressure* plus 1 inch  
J = 1/2 H  
CAUTION  
Water Damage!  
When more than one module has a  
drain pan, trap each module  
*Negative pressure=total unit static pressure at worst case (loaded filters)  
minus external pressure  
individually. Connecting all drains to  
a common line with only one trap  
may result in condensate retention  
and possible water damage to the  
air handler or adjoining space.  
Figure 27. Drain pan trapping for module under positive pressure  
K = 1/2 inch (minimum)  
H = 1/2 inch plus the total unit static pressure at worst case (loaded filters)  
CAH-SVX01A-EN  
29  
Installation  
Install a 1/2-inch NPT, 15 degree  
swing check valve vacuum  
breaker with cracking pressure of  
0.25 inches Hg (3.5 inches water)  
or lower at the top of the coil.  
This vacuum breaker should be  
installed as close to the coil as  
possible.  
Steam Coil Piping  
CAUTION  
Coil Damage!  
M-Series air handlers fitted with  
steam coils have labeled holes for  
piping penetrations. Figure 28 and  
Figure 29 illustrate typical steam coil  
piping configurations. See Table 2  
for the codes of system components  
in these figures.  
In all steam coil installations, the  
condensate return connections must  
be at the low point of the coil.  
Failure to properly install the  
condensate return connection may  
result in coil damage from water  
hammer, unequal thermal stress,  
freeze-up and/or corrosion.  
For coil types A, AA, N, NS, and  
NN, install the vacuum breaker in  
the unused condensate return  
tapping at the top of the coil.  
Table 2. Code of system components  
for piping figures  
Code System component  
Note: The 1/2-inch NPT, 15 degree  
swing check valve vacuum breaker is  
recommended because other  
vacuum breakers, such as spring-  
loaded ball-check breakers, have  
cracking pressures as high as 1.25  
inches Hg (17 inches of water).  
Vacuum breakers with fitting sizes  
smaller than 1/2 inch NPT are too  
small to relieve vacuum quick  
enough to ensure complete  
condensate drainage. Other types of  
swing check valve vacuum breakers  
are acceptable if the fittings size is  
not smaller than 1/2-inch NPT and  
the cracking pressure is not larger  
than 0.25 inches HG (3.5 inches of  
water).  
Types T and ST coils require that  
the vacuum breaker be located  
as near as possible to the supply  
connection.  
FT  
GV  
OV  
Float and thermostatic steam trap  
Gate valve  
Automatic two-position (ON-OFF)  
control valve  
VB  
ST  
AV  
MV  
Vacuum breaker  
Strainer  
Automatic or manual air vent  
Modulating control valve  
Vent the vacuum breaker line to  
atmosphere or connect it into the  
return main at the discharge side  
of the steam trap  
The coil condensate return line must  
be piped full size of the condensate  
trap connection, except for a short  
nipple screwed directly into the coil  
headers condensate return tapping.  
Do not bush or reduce the coil return  
tapping size.  
Note: Vacuum breaker relief is  
mandatory when the coil is  
controlled by a modulating steam  
supply or automatic two position  
(ON-OFF) steam supply valve.  
Vacuum breaker relief is also  
recommended when face-and-  
bypass control is used.  
30  
CAH-SVX01A-EN  
Installation  
Proper steam trap installation is  
necessary for satisfactory coil  
performance and service life. For  
steam trap installation:  
Figure 28. Typical piping for Type N steam coils and horizontal tubes for horizontal  
airflow  
1
Install the steam trap discharge  
12 inches below the condensate  
return connection. Twelve inches  
provides sufficient hydrostatic  
head pressure to overcome trap  
losses and ensures complete  
condensate removal.  
a
Use float and thermostatic  
traps with atmospheric  
pressure gravity condensate  
return, with automatic  
controls, or where the  
possibility of low-pressure  
supply steam exists. (Float  
and thermostatic traps are  
recommended because of  
gravity drain and continuous  
discharge operation.)  
b
Use bucket traps only when  
the supply steam is not  
modulated and is 25 psig or  
higher.  
Figure 29. Typical piping for Type NS steam coils and horizontal tubes for  
horizontal airflow  
Note: Trane steam coils require a  
minimum of 2 psi of pressure to  
assure even heat distribution.  
2
3
4
Trap each coil separately to  
prevent holding up condensate  
in one or more of the coils.  
Install strainers as close as  
possible to the inlet side of the  
trap.  
If installing coils in series airflow,  
control each coil bank  
independently with an automatic  
steam-control valve. Size the  
traps for each coil using the  
capacity of the first coil in  
direction of airflow.  
5
Use a modulating valve that has  
linear flow characteristics to  
obtain gradual modulation of the  
coil steam supply.  
Note: Do not modulate systems with  
overhead or pressurized returns  
CAH-SVX01A-EN  
31  
Installation  
unless the condensate is drained by  
gravity into a receiver, vented to  
atmosphere, and returned to the  
condensate pump.  
Figure 30. Typical piping for type 5W one-row water coil  
6
Pitch all supply and return steam  
piping down 1 inch for every  
10 feet in the direction of the  
steam or condensate flow.  
Note: Do not drain the steam mains  
or take-offs through the coils. Drain  
the mains ahead of the coils through  
a steam trap to the return line.  
7
Ensure overhead returns have  
1 psig of pressure at the steam  
trap discharge for every 2 feet of  
elevation for continuous  
condensate removal.  
Figure 31. Typical piping for type 5A, 5W two-row, K, W 3- to 12-row, WD, D, and  
DD water coils  
Water Coil Piping  
Figure 30 through Figure 32  
illustrate typical water coil piping  
configurations.  
Type WA, 5A, 5W, D, K, W, UW, TT,  
P,2, P4, and P8 water coils are self-  
venting only if the water velocity  
exceeds 1.5 feet per second (fps) in  
the coil tubes. Type UU, WD, and 5D  
water coils are self-venting only if  
the water velocity exceeds 2.5 fps in  
the coil tubes. See the unit  
submittals for coil water velocity. If  
the water velocity is below these  
minimums, vent the coil by one of  
the following methods:  
Install an air vent in the top pipe  
plug tapping of the return  
header.  
Figure 32. Typical piping for type W or WA 1-row water coil  
When the return line rises above  
the top of the coil, vent from the  
top of the return header  
horizontally to the return piping.  
Note: T, ST, and TT coils are  
designed with larger than normal  
end tube sheet holes to allow for  
maximum expansion. Air leakage  
around tubes should be expected  
and handled by capping over coil  
ends or by sealing around tubes  
with a pliable sealant such as  
silicone.  
32  
CAH-SVX01A-EN  
Installation  
proper sequence for positioning  
them in the liquid line. Position the  
components as close to the  
evaporator as possible.  
Routing. Install the liquid line with a  
slight slope in the direction of flow  
so that it can be routed with the  
suction line. Minimize tube bends  
and reducers because these items  
tend to increase pressure drop and  
to reduce subcooling at the  
expansion valve. Liquid line  
receivers, other than those that are  
factory-installed, are not  
Refrigerant Coil Piping  
Note: Refer to the “Protecting the  
Environment” section on page 3 for  
information on handling  
refrigerants.  
Filter drier. There is no substitute  
for cleanliness.during system  
installation. The filter drier  
Use Figure 33 to determine the  
proper, relative sequence of the  
components in the refrigerant lines  
that connect the condensing unit to  
an evaporator coil. Refer to the  
“Examples of Field-Installed  
Evaporator Piping” section on  
page 35 for more detailed  
schematics of evaporator piping.  
prevents residual contaminants,  
introduced during installation,  
from entering the expansion  
valve and solenoid valve.  
recommended.  
Access port. The access port  
allows the unit to be charged  
with liquid refrigerant and is  
used to determine subcooling.  
This port is usually a Schraeder  
valve with a core.  
Insulation. The liquid line is  
generally warmer than the  
surrounding air, so it does not  
require insulation. In fact, heat loss  
from the liquid line improves system  
capacity because it provides  
additional subcooling.  
Liquid Lines  
Solenoid valve. In split systems,  
solenoid valves isolate the  
refrigerant from the evaporator  
during off cycles; under certain  
conditions, they may also trim  
the amount of active evaporator  
as compressors unload.  
Line Sizing. Properly sizing the liquid  
line is critical to a successful split-  
system application. The selected  
tube diameter must provide at least  
5°F [2.7°C] of subcooling at the  
expansion valve throughout the  
operating envelope. Increasing the  
size of the liquid line will not  
Components. Liquid-line refrigerant  
components necessary for a  
successful job include a filter drier,  
access port, solenoid valve,  
moisture-indicating sight glass,  
expansion valve(s), and ball shutoff  
valves. Figure 33 illustrates the  
Generally, the “trim” solenoid  
valve is unnecessary for variable-  
air-volume comfort-cooling  
applications, and is only required  
for constant-volume applications  
when dehumidification is a  
concern.  
increase the available subcooling.  
Figure 33. Example of placement for split-system components  
Moisture-indicating sight glass.  
Be sure to install one moisture-  
indicating sight glass in the main  
liquid line. The only value of the  
sight glass is its moisture  
indication ability. Use actual  
measurements of temperature  
and pressure—not the sight  
glass—to determine subcooling  
and whether the system is  
properly charged. The moisture  
indicator/sight glass must be  
sized to match the size of the  
liquid line at the thermal  
expansion valve.  
Kit with Kit Kit  
Kit with sensor 13790452010 SEN-01212  
Kit with switch - X13100429010 THT 02442  
CAH-SVX01A-EN  
33  
Installation  
Routing. To prevent residual or  
Thermal expansion valve. The  
expansion valve is the throttling  
device that meters the  
refrigerant into the evaporator  
coil. Metering too much  
Cut the process tube and cap  
assembly from the liquid connection  
as shown in Figure 34 and install the  
expansion valve directly to the liquid  
connections.  
condensed refrigerant from “free-  
flowing” toward the compressor,  
install the suction line so it slopes  
slightly—that is, by 1/4-inch to 1-inch  
per 10 feet of run [1 cm per 3 m]—  
toward the evaporator. When the  
application includes a suction riser,  
oil must be forced to travel the  
height of the riser. Riser traps and  
double risers are unnecessary in the  
suction line when the refrigerant coil  
is used with Trane condensing units.  
refrigerant floods the  
compressor; metering too little  
elevates the compressor  
temperature. Choosing the  
correct size and type of  
expansion valve is critical to  
assure it will correctly meter  
refrigerant into the evaporator  
coil throughout the entire  
operating envelope of the  
system. Correct refrigerant  
distribution into the coil requires  
an expansion valve for each  
distributor.  
CAUTION  
Valve Damage!  
Disassemble the thermal expansion  
valve before completing the brazing  
connections. If necessary, wrap the  
valve in a cool, wet cloth while  
brazing. Failure to protect the valve  
from high temperatures may result  
in damage to internal components.  
Avoid putting refrigerant lines  
underground. Refrigerant  
condensation or installation debris  
inside the line, service access, and  
abrasion/corrosion can quickly  
impair reliability.  
Suction Lines  
Line sizing. Proper suction-line  
sizing is required to guarantee the  
oil returns to the compressor  
The thermal expansion valve must  
be selected for proper size and  
capacity. The size of the expansion  
valve should cover the full range of  
loadings. Check that the valve will  
successfully operate at the lightest  
load condition. For improved  
modulation, choose expansion  
valves with balanced port  
Insulation. Any heat that transfers  
from the surrounding air to the  
cooler suction lines increases the  
load on the condenser (reducing the  
systems air-conditioning capacity)  
and promotes condensate formation  
(adversely affecting indoor air  
quality). After operating the system  
and testing all fittings and joints to  
verify the system is leak-free,  
throughout the systems operating  
envelope. At the same time, the line  
must be sized so that the pressure  
drop does not excessively affect  
capacity or efficiency. To accomplish  
both objectives, it may be necessary  
to use two different line diameters:  
one for the horizontal run and for  
vertical drops, and another for the  
vertical lifts.  
construction and external  
equalization.  
insulate the suction lines all the way  
to inner side panel to prevent heat  
gain and unwanted condensation.  
Components. Installing the suction  
line requires field installation of  
these components: a filter, access  
port, and a Frostat™ control when  
the refrigerant coil is used with  
Trane condensing units. Position  
them as close to the compressor as  
possible.  
Figure 34. Type F refrigerant coil with packed elbow  
Perforated plate  
Cut here for  
piping  
Panel  
(packed elbow)  
Note: Placement of the Frostat  
control is illustrated in Figure 33.  
Filter. The suction filter prevents  
contaminants, introduced during  
installation, from entering the  
compressor. For this reason, the  
suction filter should be the  
Venturi type  
distributor  
replaceable-core type, and a  
clean core should be installed  
after the system is cleaned up.  
Coil  
Access port. The access port is  
used to determine suction  
pressure. This port is usually a  
Schraeder valve with a core.  
34  
CAH-SVX01A-EN  
Installation  
4
5
For the vertical riser, use the tube  
diameter recommended by the  
condensing unit manufacturer.  
Assure the top of the riser is  
higher than the evaporator coil.  
Examples of Field-Installed  
Evaporator Piping  
Frostat™ coil frost protection.  
The Frostat control is the  
preferred method for protecting  
evaporator coils from freezing  
when the refrigerant coil is used  
with Trane condensing units. It  
senses the suction-line  
temperature and temporarily  
disables mechanical cooling if it  
detects frost conditions. The  
control is mechanically attached  
to the outside of the refrigerant  
line, near the evaporator, and  
wired to the unit control panel.  
Single-Circuit Condensing Units:  
Evaporator Coil with One Distributor  
(see Figure 35)  
Arrange the suction line so the  
refrigerant gas leaving the coil  
flows downward, past the lowest  
suction-header outlet, before  
turning upward.  
1
Pitch the liquid line slightly—  
1 inch/10 feet [1 cm/3 m]—so that  
the refrigerant drains toward the  
evaporator.  
2
3
Provide one expansion valve per  
distributor.  
6
7
Pitch the suction line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
Slightly pitch the outlet line from  
the suction header toward the  
suction riser—that is, 1 inch/  
10 feet [1 cm/3 m] in the direction  
of flow. Use the tube diameter  
that matches the suction-header  
connection.  
Ball shutoff valve. Adding  
manual, ball-type shutoff valves  
upstream and downstream of the  
filter simplifies replacement of  
the filter core.  
Insulate the suction line.  
Figure 35. Single-circuit evaporator coil with one distributor  
CAH-SVX01A-EN  
35  
Installation  
Figure 36. Single-circuit evaporator coil with two distributors  
7
Pitch the suction line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
4
Arrange the suction line so the  
Single-Circuit Condensing Units:  
Evaporator Coil with Two  
Distributors (see Figure 36)  
refrigerant gas leaving the coil  
flows downward, past the lowest  
suction-header outlet, before  
turning upward. Use a double-  
elbow configuration to isolate  
the thermal expansion valve bulb  
from other suction headers.  
1
Pitch the liquid line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
8
9
Insulate the suction line.  
Only use a “trim” solenoid valve  
for constant-volume, humidity-  
sensitive applications. For all  
other applications, install a  
single solenoid valve (the  
“pumpdown” solenoid valve)  
between the liquid-line filter drier  
and the sight glass.  
2
3
Provide one expansion valve per  
distributor.  
5
6
For horizontal tubing, use the  
tube diameter recommended by  
the condensing unit  
Slightly pitch the outlet line from  
the suction header toward the  
suction riser—that is, 1 inch/  
10 feet [1 cm/3 m] in the direction  
of flow. Use the tube diameter  
that matches the suction-header  
connection.  
manufacturer.  
For the vertical riser, use the tube  
diameter recommended by the  
condensing unit manufacturer.  
Assure the top of the riser is  
higher than the evaporator coil.  
36  
CAH-SVX01A-EN  
Installation  
Assure the top of the riser is  
Figure 37. Single-circuit evaporator coil with four distributors  
higher than the evaporator coil.  
7
Pitch the suction line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
8
9
Insulate the suction line.  
Only use a “trim” solenoid valve  
for constant-volume, humidity-  
sensitive applications. For all  
other applications, install a  
single solenoid valve (the  
“pumpdown” solenoid valve)  
between the liquid-line filter drier  
and the sight glass.  
4
Arrange the suction line so the  
Single-Circuit Condensing Units:  
Evaporator Coil with Four  
Distributors (see Figure 37)  
refrigerant gas leaving the coil  
flows downward, past the lowest  
suction-header outlet, before  
turning upward. Use a double-  
elbow configuration to isolate  
the thermal expansion valve bulb  
from other suction headers.  
1
Pitch the liquid line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
2
3
Provide one expansion valve per  
distributor.  
5
6
For horizontal tubing, use the  
tube diameter recommended by  
the condensing unit  
Slightly pitch the outlet line from  
the suction header toward the  
suction riser—that is, 1 inch/  
10 feet [1 cm/3 m] in the direction  
of flow. Use the tube diameter  
that matches the suction-header  
connection.  
manufacturer.  
For the vertical riser, use the tube  
diameter recommended by the  
condensing unit manufacturer.  
CAH-SVX01A-EN  
37  
Installation  
6
The top of the Circuit 2 suction  
riser must be higher than the top  
evaporator coil. Use the tube  
diameter recommended by the  
condensing unit manufacturer  
for the riser.  
Dual-Circuit Condensing Units:  
Evaporator Coil with Two  
Distributors (see Figure 38)  
4
5
The top of the Circuit 1 suction  
riser must be higher than the  
bottom evaporator coil. Use the  
tube diameter recommended by  
the condensing unit  
1
Pitch the liquid lines slightly—1  
inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
manufacturer for the riser.  
7
8
Pitch the suction lines slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
Arrange the suction line so the  
refrigerant gas leaving the coil  
flows downward, past the lowest  
suction-header outlet, before  
turning upward.  
2
3
Provide one expansion valve per  
distributor.  
Slightly pitch the outlet line from  
the suction header toward the  
suction riser—that is, 1 inch/  
10 feet [1 cm/3 m] in the direction  
of flow. Use the tube diameter  
that matches the suction-header  
connection.  
Insulate the suction lines.  
Figure 38. Dual-circuit evaporator coil with two distributors  
38  
CAH-SVX01A-EN  
Installation  
Dual-Circuit Condensing Units:  
Evaporator Coil with Four  
Distributors (see Figure 39)  
Figure 39. Dual-circuit evaporator coil with four distributors  
1
Pitch the liquid line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
2
3
Provide one expansion valve per  
distributor.  
Slightly pitch the outlet line from  
the suction header toward the  
suction riser—that is, 1 inch/  
10 feet [1 cm/3 m] in the direction  
of flow. Use the tube diameter  
that matches the suction-header  
connection.  
4
Arrange the suction line so the  
refrigerant gas leaving the coil  
flows downward, past the lowest  
suction-header outlet, before  
turning upward. Use a double-  
elbow configuration to isolate  
the thermal expansion valve bulb  
from other suction headers.  
5
6
For horizontal tubing, use the  
tube diameter recommended by  
the condensing unit  
manufacturer.  
For the vertical riser, use the tube  
diameter recommended by the  
condensing unit manufacturer.  
Assure the top of the riser is  
higher than the evaporator coil.  
7
8
Pitch the suction line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
9
The top of the Circuit 1 suction  
riser must be higher than the  
bottom evaporator coil. Use the  
tube diameter recommended by  
the condensing unit  
10 The top of the Circuit 2 suction  
riser must be higher than the top  
evaporator coil. Use the tube  
diameter recommended by the  
condensing unit manufacturer  
for the riser.  
Insulate the suction line.  
manufacturer for the riser.  
CAH-SVX01A-EN  
39  
Installation  
Dual-Circuit Condensing Units:  
Evaporator Coil with Eight  
Distributors (see Figure 40)  
Figure 40. Dual-circuit evaporator coil with eight distributors  
1
Pitch the liquid line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
2
3
Provide one expansion valve per  
distributor.  
Slightly pitch the outlet line from  
the suction header toward the  
suction riser—that is, 1 inch/  
10 feet [1 cm/3 m] in the direction  
of flow. Use the tube diameter  
that matches the suction-header  
connection.  
4
Arrange the suction line so the  
refrigerant gas leaving the coil  
flows downward, past the lowest  
suction-header outlet, before  
turning upward. Use a double-  
elbow configuration to isolate  
the TXV bulb from other suction  
headers.  
5
6
For horizontal tubing, use the  
tube diameter recommended by  
the condensing unit  
manufacturer.  
For the vertical riser, use the tube  
diameter recommended by the  
condensing unit manufacturer.  
Assure the top of the riser is  
higher than the evaporator coil.  
7
Pitch the suction line slightly—  
1 inch/10 feet [1 cm/3 m]—so the  
refrigerant drains toward the  
evaporator.  
8
9
Insulate the suction line.  
The top of the Circuit 1 suction  
riser must be higher than the  
bottom evaporator coil. Use the  
tube diameter recommended by  
the condensing unit  
11 Only use a “trim” solenoid valve  
10 The top of the Circuit 2 suction  
riser must be higher than the top  
evaporator coil. Use the tube  
diameter recommended by the  
condensing unit manufacturer  
for the riser.  
for constant-volume, humidity-  
sensitive applications. For all  
other applications, install a  
single solenoid valve (the  
“pumpdown” solenoid valve)  
between the liquid-line filter drier  
and the sight glass.  
manufacturer for the riser.  
40  
CAH-SVX01A-EN  
Installation  
All direct-digital controllers (DDCs)  
are provided with line voltage to  
24 Vac control transformers  
mounted and wired in the starter or  
variable-frequency drive (VFD)  
power box transformer plate (see  
Figure 41) or 120 to 24 Vac control  
transformers mounted and wired in  
the auxiliary control panel (see  
Figure 42).  
Figure 43 shows a typical VFD power  
box.  
Wiring  
Wiring to the unit fan motor must be  
provided by the installer and must  
comply with all national and local  
electrical codes. The installer must  
also furnish a fused disconnect  
switch in compliance with national  
and local electrical codes.  
Note: The valve jack/junction box is  
typically located at the air-leaving  
side of the coil connection inside  
panel. For coils with headers on both  
sides of the module, the valve jack is  
located at the return connection for  
water coils and the supply  
Fan motors also require motor  
overload protective devices that are  
rated or selected in compliance with  
the National Electric Code or  
Canadian Electric Code. Specific unit  
and motor connection diagrams are  
provided on the starter/VFD, if Trane-  
provided, or refer to the motor  
nameplate.  
connection for steam coils.  
Figure 42. Controller with power box  
attached  
ƽ WARNING  
Hazardous Voltage with  
Capacitors!  
Line supply  
24 Vac  
120 Vac  
Disconnect all electric power,  
including remote disconnects and  
discharge all motor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing components provided by  
Trane or others, refer to the  
CAUTION  
Use Copper Conductors  
Only!  
Unit terminals are not designed to  
accept other types of conductors.  
Failure to use copper conductors  
may result in equipment damage.  
appropriate manufacturer’s  
literature for allowable waiting  
periods for discharge of capacitors.  
Verify with an appropriate voltmeter  
that all capacitors have discharged.  
Failure to disconnect power and  
discharge capacitors before  
Figure 41. Transformer plate  
servicing could result in death or  
serious injury.  
Figure 43. Variable-frequency drive  
(VFD)  
To provide field-wiring to units with  
DDC controls:  
Provide 120 Vac power to a  
transformer in the junction box  
provided when a separate circuit  
is recommended (see Figure 42).  
Install outside-air sensor and  
space sensor, if ordered.  
For valve jack junction box  
mounting and wiring detail (see  
Figure 43).  
CAUTION  
Seal the Penetrations!  
Line supply to  
transformers  
24 Vac to end  
devices and  
controllers  
Seal all penetrations into the unit to  
prevent air infiltration during  
operation. Failure to do so may  
result in equipment damage.  
CAH-SVX01A-EN  
41  
Installation  
External Insulating  
Requirements  
Figure 44. Junction box mounting and wiring details  
The following areas should be  
specifically addressed, as applicable:  
Supply and return water piping  
connections  
Supply and return refrigerant  
piping connections  
Condensate drain lines and  
connections  
Outdoor-air-intake duct  
connections  
Discharge duct connections  
Special requirements for low-  
temperature-air systems  
Valve jack wiring:  
.Black connector is for 24 Vac power supply (black wire for GND and red  
wire for 24 Vac)  
.White connector is for 0 to 10 Vac analog signal (black wire for GND and  
red wire for 0 to 10 Vac.  
Figure 45. Typical quick connects with wiring identification  
Power 24 Vac  
Sig. 0–10 Vdc  
Wire from  
ribbon cable  
Signal to Slave  
Actuator  
Actuator  
42  
CAH-SVX01A-EN  
Startup  
Once the Custom Climate Changer  
air handler has been assembled and  
installed, attention must be directed  
to individual components for proper  
operation. Before operating the unit,  
complete the pre-startup checklist.  
Check fan shaft bearings, fan  
wheel, and drive sheave set  
screws for proper torque  
settings.  
Coil-Related Checks  
CAUTION  
Proper Water Treatment!  
Fan sheaves should be tight  
and aligned.  
The use of untreated or improperly  
treated water in coils may result in  
scaling, erosion, corrosion, algae, or  
slime. Engage the services of a  
qualified water treatment specialist  
to determine what water treatment,  
if any, is required. Trane assumes no  
responsibility for equipment failures  
that result from untreated or  
Bearing set screws should be  
torqued.  
ƽ WARNING  
Hazardous Voltage with  
Capacitors!  
Inspect the inlet vane assembly  
for freedom of movement. If  
resistance is above the  
recommended torques, check the  
assembly for any binding or  
misalignment. Do not force the  
vanes.  
Disconnect all electric power,  
including remote disconnects and  
discharge all motor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing components provided by  
Trane or others, refer to the  
improperly treated water.  
Ensure coil and condensate drain  
piping connections are complete.  
Check fan drive belt tension.  
Inspect fan motor and bearings  
for proper lubrication, if  
necessary.  
Check the piping and valves for  
leaks.  
Open or close the valves to  
check operation.  
Check the motor lubrication, if  
necessary.  
appropriate manufacturer’s  
literature for allowable waiting  
periods for discharge of capacitors.  
Verify with an appropriate voltmeter  
that all capacitors have discharged.  
Failure to disconnect power and  
discharge capacitors before  
The drain lines should be  
open.  
Remove and clean grease  
plugs.  
If unit has a refrigerant coil,  
ensure that it has been charged  
and leak-tested according to the  
instructions provided with the  
condenser equipment. Adjust the  
superheat setting.  
Check for moisture in the  
grease. If moisture is present,  
remove the motor and send it  
to an authorized repair shop  
for bearing inspection/  
servicing could result in death or  
serious injury.  
replacement. If no moisture is  
present, refer to the motor  
manufacturers lubrication  
recommendations for proper  
lubrication.  
Note: For additional information  
regarding the safe discharge of  
capacitors, see PROD-SVB06A-EN.  
Remove all foreign material from  
the drain pan and check the pan  
opening and condensate line for  
obstructions.  
For steam coils, slowly turn the  
steam on full for at least  
10 minutes before opening the  
fresh air intake on units with  
fresh air dampers.  
Check the motor lubrication, if  
necessary.  
Pre-Startup  
Checklist  
Remove and clean grease  
plugs.  
Check for moisture in the  
grease. If moisture is present,  
remove the motor and send it  
to an authorized repair shop  
for bearing inspection/  
Fan-Related Checks  
If the unit is internally isolated,  
ensure that the fan isolator tie-  
down bolts have been removed.  
Motor-Related Checks  
Check motor winding. An  
acceptable winding resistance  
reading is from 6 meg-ohms to  
infinity. If reading is less than  
5 mega-ohms, the winding  
should be dried out in an oven or  
by a blower.  
Rotate all fan wheels manually to  
confirm they turn freely in the  
proper direction.  
replacement. If no moisture is  
present, refer to the motor  
manufacturers lubrication  
recommendations for proper  
lubrication.  
Inspect the entire motor for rust  
and corrosion.  
CAH-SVX01A-EN  
43  
Startup  
General Checks  
ƽ WARNING  
Live Electrical  
Components!  
Unit Operation  
Ensure the unit has been  
installed level.  
Before complete startup, bump-start  
the unit and confirm the fan wheel  
rotates properly, as indicated by the  
rotation arrow located on the fan  
housing.  
Ensure supply-air and return-air  
ducts have been connected.  
During installation, testing,  
servicing and troubleshooting of  
this product, it may be necessary to  
work with live electrical  
components. Have a qualified  
licensed electrician or other  
individual who has been properly  
trained in handling live electrical  
components perform these tasks.  
Failure to follow all electrical safety  
precautions when exposed to live  
electrical components could result  
in death or serious injury.  
Ensure damper operator motors  
and connecting linkage have  
been installed.  
After initial startup:  
Calculate the motor voltage  
imbalance, notifying the power  
company to correct unacceptable  
imbalances.  
Verify damper operation and  
linkage alignment.  
Check that air filters are in place  
and positioned properly.  
Periodically check the fan belt  
tension.  
Remove any debris from the unit  
interior.  
Close and secure all unit access  
doors.  
Calculate Motor  
Voltage Imbalance  
After startup, measure the motor  
voltage and amperage on all phases  
to ensure proper operation. The  
readings should fall within the range  
given on the motor nameplate. The  
maximum allowable voltage  
Note: UL-listed units require a  
removable latch on access doors.  
The door clip shipped with the unit  
meets this requirement.  
Inspect electrical connections to  
the unit and unit controllers.  
Connections should be clean  
and secure.  
imbalance is 2 percent.  
Voltage imbalance is defined as 100  
times the sum of the deviation of the  
three voltages from the average,  
divided by twice the average  
voltage. For example, if the three  
measured voltages are 221, 230 and  
227, the average voltage would be  
226 volts. The percent of voltage  
imbalance is then calculated:  
Compare the actual wiring  
with the unit diagrams.  
Reference the appropriate  
controller manual for more  
details about starting units  
with factory-mounted  
controls.  
Leave this manual with the unit.  
100A  
Voltage imbalance = -------------------------------------------------  
2 × AvgVoltage  
where:  
A = (226-221) + (230-226) + (227-226)  
Voltage imbalance = 2.2% (not acceptable)  
In the example, 2.2 percent  
imbalance is not acceptable and the  
power company should be notified  
to correct it.  
44  
CAH-SVX01A-EN  
Startup  
Proper belt tension is required to  
ensure maximum bearing and drive  
component life and is based on  
motor horsepower requirement. A  
label located on the bearing support  
on the drive side of the unit lists all  
drive parts, the proper belt tension,  
and deflection for that tension for  
the specific drive.  
Tension the Fan Belt  
Figure 47. Belt tensioner  
Check the fan belt tension at least  
three times during the first days of  
operation because there is a rapid  
decrease in tension until the belt  
settles in (see Figure 46 and  
Figure 47).  
ƽ WARNING  
If the drive is changed from the  
original, proper belt tension can be  
estimated using Table 3.  
Hazardous Voltage with  
Capacitors!  
Disconnect all electric power,  
including remote disconnects and  
discharge all motor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing components provided by  
Trane or others, refer to the  
The correct operation tension for a  
V-belt drive is the lowest tension at  
which the belts will not slip under  
the peak load conditions. It may be  
necessary, however, to increase the  
tension of some drives to reduce  
excessive belt flopping or to reduce  
excessive startup squealing.  
appropriate manufacturer’s  
literature for allowable waiting  
periods for discharge of capacitors.  
Verify with an appropriate voltmeter  
that all capacitors have discharged.  
Failure to disconnect power and  
discharge capacitors before  
Figure 46. Belt tension measurement  
servicing could result in death or  
serious injury.  
CAUTION  
Tension Belts Correctly!  
Over-tensioning belts can cause  
damage to bearings, shafts, and  
drive components. Under tensioning  
belts is the primary cause of  
premature belt failure. Belts should  
not squeal at startup. Recheck belt  
tension after 8 hours, 24 hours, and  
100 hours of operation and monthly  
thereafter.  
CAH-SVX01A-EN  
45  
Startup  
Table 3. Typical sheave diameter and deflection force1  
Smallest Sheave  
Belt Deflection Force (lbs)  
Super Gripbelts and  
Unnotched Gripbands  
Used Belt New Belt  
5.5  
Gripnotch Belts and  
Notched Gripbands  
Used Belt  
Cross  
Section  
Diameter Range  
(in.)  
Speed (rpm)  
Range  
New Belt  
6.4  
3.0–3.6  
1,000–2,500  
2,501–4,000  
1,000–2,500  
2,501–4,000  
1,000–2,500  
2,501–4,000  
860–2,500  
2,501–4,000  
860–2,500  
2,501–4,000  
860–2,500  
2,501–4,000  
500–1,740  
1,741–3,000  
500–1,740  
1,741–3,000  
200–850  
3.7  
2.8  
4.5  
3.8  
5.4  
4.7  
n/a  
n/a  
5.3  
4.5  
6.3  
6.0  
11.5  
9.4  
14.1  
12.5  
24.9  
21.2  
30.4  
25.6  
n/a  
n/a  
3.6  
3.0  
4.9  
4.4  
n/a  
n/a  
n/a  
12.7  
11.2  
15.5  
14.6  
33.0  
26.8  
39.6  
35.3  
4.1  
3.4  
5.0  
4.2  
6.8  
5.0  
7.4  
6.4  
9.4  
7.6  
7.2  
6.2  
10.5  
9.1  
12.6  
10.9  
21.8  
17.5  
23.5  
21.6  
n/a  
n/a  
n/a  
n/a  
4.9  
3.8–4.8  
5.0–7.0  
A, AX  
B, BX  
5.7  
4.3  
8.0  
5.7  
7.0  
5.1  
3.4–4.2  
n/a  
4.9  
n/a  
4.2  
4.4–5.6  
7.9  
7.1  
6.7  
7.1  
5.8–8.6  
9.4  
8.5  
8.9  
7.3  
7.0–9.0  
17.0  
13.8  
21.0  
18.5  
37.0  
31.3  
45.2  
38.0  
n/a  
14.7  
11.9  
15.9  
14.6  
n/a  
n/a  
n/a  
n/a  
3.3  
C, CX  
9.5–16.0  
12.0–16.0  
18.0–20.0  
2.2–2.4  
851–1,500  
200–850  
D
851–1,500  
1,000–2,500  
2,501–4,000  
1,000–2,500  
2,501–4,000  
1,000–2,500  
2,501–4,000  
500–1,749  
1,750–3,000  
3,001–4,000  
500–1,749  
1,750–3,000  
500–1,749  
1,750–3,000  
200–850  
n/a  
2.9  
4.3  
6.2  
5.6  
7.9  
2.65–3.65  
4.12–6.90  
4.4–6.7  
5.1  
4.2  
3V, 3VX  
4.4  
3.8  
7.3  
5.3  
6.6  
4.9  
7.3  
n/a  
n/a  
10.2  
8.8  
15.2  
13.2  
8.5  
22.1  
20.1  
25.5  
25.0  
n/a  
n/a  
5.6  
5V, 5VX  
7.1–10.9  
11.8–16.0  
12.5–17.0  
18.0–22.4  
18.9  
16.7  
23.4  
21.8  
49.3  
39.9  
59.2  
52.7  
14.8  
13.7  
17.1  
16.8  
n/a  
n/a  
n/a  
n/a  
851–1,500  
200–850  
n/a  
n/a  
n/a  
8V  
851–1,500  
1. Source for table: Browning® catalog DC-98, page B-30.  
46  
CAH-SVX01A-EN  
Startup  
Determine Fan  
Speed  
Figure 48. Proper drive alignment  
ƽ WARNING  
Rotating Components!  
During installation, testing,  
servicing and troubleshooting of  
this product it may be necessary to  
measure the speed of rotating  
components. Have a qualified or  
licensed service individual who has  
been properly trained in handling  
exposed rotating components,  
perform these tasks. Failure to  
follow all safety precautions when  
exposed to rotating components  
could result in death or serious  
injury.  
Fan speed can be determined using  
a strobe-type tachometer, or  
revolution counter.  
Check unit vibration if the fan speed  
is changed more than 5 percent from  
the original designed speed, or if  
parts such as shafts, fan wheels,  
bearings, or other drive components  
are replaced. Do not exceed the  
maximum fan speed.  
Pay particular attention to any  
vibration, noise, or overheating of  
the motor and fan bearings;  
however, note that bearings may run  
warm during break in.  
Table 4. Fan and drive compound torque settings (inches)  
Screw Size Hex Key Square Head Hex Head Torque (in.-lb.) Torque (ft.-lb.)  
Sheave Alignment  
1/4  
5/16  
3/8  
1/8  
5/32  
3/16  
7/32  
1/4  
3/8  
1/2  
9/16  
5/8  
7/16  
1/2  
9/16  
5/8  
66-90  
126-164  
228-300  
348-450  
504-650  
1290-1390  
5.5-7.5  
10.5-13.7  
19.0-25.0  
29.0-37.5  
42.0-54.2  
107.0-116.0  
Align the fan and motor sheaves  
using a straightedge. The  
7/15  
1/2  
straightedge must be long enough  
to span the distance between the  
outside edges of the sheaves. When  
the sheaves are aligned, the  
3/4  
3/4  
5/8  
5/16  
15/16  
15/16  
same for each belt, the motor and  
fan shaft are not parallel. Realign as  
required. After realignment, tighten  
the belts again to the standard belt  
tensioning specifications. If the force  
is still not the same for all belts, the  
belts or sheaves are worn and must  
be replaced.  
straightedge will touch both sheaves  
at points A through D (see  
Multibelt Check  
Tighten the belts slightly and rotate  
the drive several times.  
Figure 48) to confirm the shaft is  
parallel. For uneven width sheaves,  
place a string in the center groove of  
both sheaves and pull tight. Adjust  
the sheaves and tighten the sheave  
set screws to the proper torque  
given in Table 4.  
On multiple belt drives, ensure the  
force of deflection is approximately  
the same on each belt by pushing  
each belt in an equal distance at a  
point halfway from each sheave (see  
Figure 48). If this force is not the  
CAH-SVX01A-EN  
47  
Routine  
Maintenance  
The following checklist is provided  
as an abbreviated guide to periodic  
maintenance. Detailed procedural  
information is given after this  
checklist.  
For variable frequency drives or  
other energy storing components  
provided by Trane or others, refer to  
the appropriate manufacturer’s  
literature for allowable waiting  
periods for discharge of capacitors.  
Verify with an appropriate voltmeter  
that all capacitors have discharged.  
ƽ WARNING  
Hazardous Service  
Procedures!  
The maintenance and  
troubleshooting procedures  
recommended in this section of the  
manual could result in exposure to  
electrical, mechanical or other  
potential safety hazards. Always  
refer to the safety warnings provided  
throughout this manual concerning  
these procedures. When possible,  
disconnect all electrical power  
including remote disconnects before  
servicing. Follow proper lockout/  
tagout procedures to ensure the  
power can not be inadvertently  
energized.  
When servicing fans or ductwork,  
secure the impeller to physically  
restrict rotational movement. When  
necessary to work with live  
electrical components, have a  
qualified licensed electrician or  
other individual who has been  
trained in handling live electrical  
components perform these tasks.  
Failure to follow all of the  
recommended safety warnings  
provided, could result in death or  
serious injury.  
Table 5. Routine maintenance checklist  
Frequency  
After 48 hours  
of operation  
Every week  
Every month  
Maintenance  
Belts have acquired their permanent set. Readjust but do not overtighten. See the “Tension the Fan Belt” section on  
page 45 for more information.  
Observe unit weekly for any change in running condition and unusual noise.  
• Clean or replace air filters if clogged or dirty; coat permanent filters with oil after cleaning. See the “Air Filters” section  
on page 49 for more information.  
• Relubricate fan bearings if necessary. See the “Fan Bearing Lubrication” section on page 51 for more information.  
• Check and adjust fan belt tension.  
Every three to  
six months  
• Check fan bearing grease line connections. Lines should be tight to the bearings.  
• Check bearing and motor bracket bolt torque and bearing setscrew torque.  
• Align fan and motor sheaves. Tighten sheave set screws to the proper torque. See the “Sheave Alignment” section on  
page 47 for more information.  
• Inspect and clean drain pans. See the “Drain Pans” section on page 50 for more information.  
• Tighten electrical connections.  
• Inspect coils for dirt build-up. See the “Coils” section on page 52 for more information.  
• Inspect the unit casing for corrosion. If damage is found, clean and repaint the surface with a rust-resistant primer  
and vinyl chlorinated lacquer.  
Every year  
• Clean the fan wheels and fan shaft. See the “Fans” section on page 50 for more information.  
• Inspect and clean drain pans.  
• Check damper linkages, set screws, and blade adjustment. Clean, but do not lubricate, the nylon damper rod  
bushings.  
• Clean damper operators.  
• Inspect electrical components and insulation.  
• Inspect wiring for damage.  
• Rotate the fan wheel and check for obstructions in the fan housing. The wheel should not rub on the fan housing.  
Adjust the center if necessary and tighten wheel set screws to the proper torque.  
• Lubricate motor bearings in accordance with motor manufacturer’s recommendations (see the “Fan Bearing  
Lubrication” section on page 51 for more information).  
• Check condition of gasketing and insulation around unit, door and dampers.  
• Examine flex connections for cracks or leaks. Repair or replace damaged material.  
48  
CAH-SVX01A-EN  
Routine Maintenance  
Permanent Filters  
To clean permanent filters:  
Side Load Filters  
Air Filters  
Most filters in custom units are  
installed in unitary sheet metal  
frames. If unit is provided with side  
access rack, do the following for  
installation:  
Refer to product catalog  
CLCH-PRC003-EN for filter sizes,  
types, and quantities.  
1
2
3
4
5
Disconnect all electrical power to  
the unit.  
Wash the filter under a stream of  
water to remove dirt and lint.  
ƽ WARNING  
2-inch or 4-inch flat filters  
Hazardous Voltage with  
Capacitors!  
Remove oil from the filter with a  
wash of mild alkali solution.  
1
2
Disconnect the power to the unit.  
Disconnect all electric power,  
including remote disconnects and  
discharge all motor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing components provided by  
Trane or others, refer to the  
Open the filter section access  
door and remove the filters and  
block-offs from their installed  
position.  
Rinse the filter in clean, hot water  
and allow to dry.  
Coat both sides of the filter by  
immersing or spraying it with Air  
Maze Filter Lote W or an  
equivalent.  
3
4
Slide the filter into the rack.  
Some side load racks will be  
provided with block-off plates.  
Install them into the rack last  
before closing the door.  
6
7
Allow to drain and dry for about  
12 hours.  
appropriate manufacturer’s  
literature for allowable waiting  
periods for discharge of capacitors.  
Verify with an appropriate voltmeter  
that all capacitors have discharged.  
Failure to disconnect power and  
discharge capacitors before  
Reinstall the filter.  
5
Close and secure the door,  
making certain the door closes  
snug against the block-off.  
Note: It may be preferable to keep  
extra, clean filters to replace the  
dirty filters to minimize unit  
Bag or Cartridge Filters  
downtime for filter maintenance.  
servicing could result in death or  
serious injury.  
1
2
Disconnect power to the unit.  
Front Load Filters  
Keeping the bag filters folded,  
slide each filter into the filter  
rack, pushing them tightly  
against the unit. Pleats should be  
in the vertical position.  
Note: For additional information  
regarding the safe discharge of  
capacitors, see PROD-SVB06A-EN.  
Most filters in custom units are  
installed in unitary sheet metal  
frames. Filters are secured with a  
metal clip. There are several  
different styles.  
Throwaway Filters  
3
4
5
If using optional pre-filters, slide  
them into the appropriate filter  
rack.  
To replace throwaway filters, install  
new filters with the directional  
arrows pointing in the direction of  
airflow.  
To install filters:  
1
2
3
4
Disconnect power to the unit.  
Open or remove the filter clip.  
Remove the filter from the rack.  
If block-offs are provided with the  
unit, slide the block-offs into the  
filter track.  
Note: Bag and cartridge filters must  
have an airtight seal to prevent air  
bypass. If using other than Trane-  
supplied filters, apply foam  
gasketing to the vertical edges of the  
filter.  
Install new filters with the  
directional arrows pointing in the  
direction of airflow.  
Close and secure the access  
door, making certain the door  
closes snug against the rack.  
5
Secure the filter using the  
Note: The block-off is intended to  
make a seal when the access door is  
closed. It may require a few  
appropriate clip for each filter.  
The filters are often installed in a  
pre/post filter configuration. Be sure  
to note the order of installation.  
adjustments to ensure a proper seal.  
Note: Filters must have an airtight  
seal to prevent air bypass.  
CAH-SVX01A-EN  
49  
Routine Maintenance  
See “ƽ WARNING Hazardous  
Voltage with Capacitors!” on  
page 49 regarding  
areas of the unit or building.  
Properly dispose of all  
contaminated materials and  
cleaning solution.  
4
5
Thoroughly clean all areas with a  
mild bleach and water solution or  
an EPA-approved sanitizer  
specifically designed for HVAC  
use.  
disconnection of power.  
Immediately rinse the affected  
surfaces thoroughly with fresh  
water and a fresh sponge to  
prevent potential corrosion of  
metal surfaces.  
Drain Pans  
Fans  
The condensate drain pan and drain  
line must be checked to assure the  
condensate drains as designed. This  
inspection should occur a minimum  
of every six months or more often as  
dictated by operating experience.  
Inspecting and Cleaning  
Fans  
Fan sections of air handlers should  
be inspected every six months at a  
minimum or more frequently if  
operating experience dictates. If  
evidence of microbial growth (mold)  
is found, identify and remedy the  
cause immediately. Refer to the  
Troubleshooting” section on  
6
7
Allow the unit to dry completely  
before putting it back into  
service.  
If evidence of standing water or  
condensate overflow exists, identify  
and remedy the cause immediately.  
Refer to the “Troubleshooting”  
section on page 56 for possible  
causes and solutions.  
Be careful that any contaminated  
material does not contact other  
areas of the unit or building.  
Properly dispose of all  
contaminated materials and  
cleaning solution.  
page 56 for possible causes and  
solutions. To clean the fan section:  
To clean drain pans:  
1
Disconnect all electrical power to  
the unit.  
1
Disconnect all electrical power to  
the unit.  
Bearing Set Screw  
Alignment  
Align bearing set screws as  
illustrated in Figure 49. Table 4 on  
page 47 provides bearing set screw  
torque measurements.  
2
Wearing the appropriate  
personal protective equipment,  
remove any contamination.  
2
Wearing the appropriate  
personal protective equipment,  
remove any standing water.  
3
Vacuum the section with a  
vacuum device that uses high-  
efficiency particulate arrestance  
(HEPA) filters with a minimum  
efficiency of 99.97 percent at  
0.3 micron particle size.  
3
4
Scrape solid matter off of the  
drain pan.  
Vacuum the drain pan with a  
vacuum device that uses high-  
efficiency particulate arrestance  
(HEPA) filters with a minimum  
efficiency of 99.97 percent at  
0.3 micron particle size.  
Figure 49. Bearing set screw alignment  
5
6
Thoroughly clean all areas with a  
mild bleach and water solution or  
an EPA-approved sanitizer  
specifically designed for HVAC  
use.  
Immediately rinse the affected  
surfaces thoroughly with fresh  
water and a fresh sponge to  
prevent potential corrosion of  
metal surfaces.  
7
8
Allow the unit to dry completely  
before putting it back into  
service.  
Be careful that any contaminated  
material does not contact other  
50  
CAH-SVX01A-EN  
Routine Maintenance  
See “ƽ WARNING Hazardous  
Voltage with Capacitors!” on  
page 49 regarding  
Motor bearings are factory-  
lubricated for normal life. In the case  
of a double-shielded bearing, the  
grease provided is that which is in  
the bearing. To regrease motors  
without grease fittings:  
Table 6. Minimum hex head bolt  
torque in lb.-ft. (Grade 5 bolts)  
disconnection of power.  
Size  
(inches)  
1/4-20  
1/4-28  
65/16-18  
5/16-24  
3/8-16  
3/8-24  
7/16-14  
7/16-20  
1/2-13  
1/2-20  
9/16-12  
9/16-18  
5/8-11  
5/8-18  
3/4-10  
3/4-16  
7/8-9  
Thread  
Designation  
UNC  
Minimum  
Torque  
6
Fan Bearing Lubrication  
UNF  
UNC  
UNF  
UNC  
UNF  
UNC  
UNF  
UNC  
UNF  
UNC  
UNF  
UNC  
UNF  
UNC  
UNF  
UNC  
7
14  
16  
24  
28  
42  
45  
69  
1
2
Remove the bearing brackets.  
CAUTION  
Bearing Failure!  
Do not mix greases with different  
bases within the bearing. Mixing  
grease within the bearing may result  
in premature bearing failure.  
If the original bearing is to be  
relubricated, remove the shield  
opposite the rotor.  
a
b
Do not replace.  
83  
99  
Flush old grease from  
118  
150  
176  
254  
301  
358  
422  
500  
602  
bearing with suitable solvent.  
The grease used in electric motor  
bearings is usually not compatible  
with the grease used in fan bearings.  
Never mix the two grease types!  
3
Lubricate the bearing and add  
grease to the bearing chamber.  
The chamber should be three-  
quarters full of grease. (An  
alternate method is to replace  
the old bearing with a new  
double-shield pre lubricated  
bearing.) See Table 7 for  
Note: Lubricate the bearing  
according to the motor  
manufacturers recommendations  
and use the manufacturer-  
recommended grease.  
7/8-14  
1-8  
1-14  
UNF  
UNC  
UNF  
Soft metric conversions are not acceptable for  
screw and hex sizes.  
maximum grease capacity.  
Refer to Table 6 for minimum torque  
of motor mounting and bearings  
bolts.  
Fan bearings without lubrication  
lines are sealed bearings. Re-  
lubrication is not required.  
Note: Lubricate the bearing  
according to the motor  
manufacturers recommendations  
and use the manufacturer-  
recommended grease.  
Fan bearings equipped with  
lubrication lines should be  
lubricated with a lithium-based  
grease that conforms to NLGI  
No. 2 for consistency.  
4
Reassemble the motor.  
Compatible greases include:  
Fan Motor Inspection  
Inspect fan motors periodically for  
excessive vibration or temperature.  
Texaco Multi Fak 2  
Shell Alvania 2  
Mobil 532  
Chevron Dura-Lith 2  
Exxon Beacon  
Keystone 84H  
Table 7. Fan bearing maximum grease  
capacity  
Shaft size  
(inches)  
Capacity  
(fluid ounce)  
1/2 - 3/4  
1/7  
3/8  
5/8  
7/8  
1 1/4  
2
7/8 - 1 3/16  
1 1/4 - 1 1/2  
1 11/16 - 1 15/16  
2 - 2 7/16  
2 1/2 - 2 15/16  
CAH-SVX01A-EN  
51  
Routine Maintenance  
Type K Cooling Coils  
To clean refrigerant coils:  
See “ƽ WARNING Hazardous  
Voltage with Capacitors!” on  
page 49 regarding  
1
Disconnect all electrical power to  
the unit.  
Type K cooling coils have removable  
headers for cleaning:  
disconnection of power.  
2
Wearing the appropriate  
personal protective equipment,  
use a soft brush to remove loose  
debris from both sides of the  
coil.  
1
2
Remove the headers.  
Use a small nylon or fiber brush  
to clean the tubes.  
Coils  
All coils should be kept clean to  
maintain maximum performance.  
3
4
Flush the tubes with water.  
3
4
Install a block-off to prevent  
spray from going through the  
coil and into a dry section of the  
unit and/or system ductwork.  
Install a new rubber sealing  
gasket and be sure it seats  
properly when the header is  
replaced.  
Steam and Water Coils  
To clean steam and water coils:  
1
2
Disconnect all electrical power to  
the unit.  
Mix a high-quality coil cleaning  
detergent with water according  
to the manufacturers  
Note: Apply washers under the bolt  
heads. Bolts should be evenly  
tightened to 50 foot-pounds of  
torque, beginning in the center and  
working toward the outside.  
Wearing the appropriate  
personal protective equipment,  
use a soft brush to remove loose  
debris from both sides of the  
coil.  
instructions.  
Note: If the detergent is strongly  
alkaline after mixing (PH 8.5 or  
higher), it must contain an inhibitor.  
Follow the cleaning solution  
manufacturers instructions  
regarding the use of the product.  
Refrigerant Coils  
3
4
Insert a block-off to prevent  
steam from blowing through the  
coil and into a dry section of the  
unit.  
ƽ WARNING  
Hazardous Chemicals!  
5
Place the mixed solution in a  
garden pump-up sprayer or high-  
pressure sprayer. If a high  
Coil cleaning agents can be either  
acidic or highly alkaline. Handle  
chemical carefully. Proper handling  
should include goggles or face  
shield, chemical resistant gloves,  
boots, apron or suit as required. For  
personal safety refer to the cleaning  
agent manufacturer’s Materials  
Safety Data Sheet and follow all  
recommended safe handling  
Use a steam cleaning machine to  
clean the coil, cleaning the  
leaving air side of the coil first,  
then the entering air side. Repeat  
as necessary.  
pressure sprayer is to be used:  
Maintain minimum nozzle  
spray angle of 15 degrees.  
Spray perpendicular to the  
coil face.  
Note: Start from the top of the coil  
and work downward.  
Keep the nozzle at least  
6 inches from the coil.  
5
Straighten any coil fins that may  
have been damaged during the  
cleaning process.  
practices. Failure to follow all safety  
instructions could result in death or  
serious injury.  
Do not exceed 600 psi.  
6
7
Spray the leaving air side of the  
coil first, then the entering air  
side.  
6
7
Confirm the drain line is open  
following the cleaning process.  
ƽ WARNING  
Hazardous Pressures!  
Allow the unit to dry thoroughly  
before putting it back into  
service.  
Thoroughly rinse both sides of  
the coil and the drain pan with  
cool, clean water.  
Coils contain refrigerant under  
pressure. When cleaning coils,  
maintain coil cleaning solution  
temperature under 150°F to avoid  
excessive pressure in the coil.  
Failure to follow these safety  
precautions could result in coil  
bursting, which could result in death  
or serious injury.  
8
9
Replace all panels and parts and  
restore electrical power to the  
unit.  
8
9
Repeat steps 6 and 7 as  
necessary.  
Straighten any coil fins damaged  
during the cleaning process.  
Be careful any contaminated  
material does not contact other  
areas of the unit or building.  
Properly dispose of all  
10 Confirm the drain line is open  
following the cleaning process.  
contaminated materials.  
52  
CAH-SVX01A-EN  
Routine Maintenance  
11 Allow the unit to dry thoroughly  
before putting it back into  
service.  
Type W, P2, P4, P8, WD, 5D,  
and 5W Coils  
Moisture Purge  
Cycle  
By its very nature, any HVAC unit  
with a cooling coil serves as a  
dehumidifier, reducing the  
surrounding airs ability to hold  
water vapor as its temperature falls.  
This normally doesn’t present a  
problem when the unit is running.  
However, when the fan stops, water  
vapor condenses on the cold metal  
surfaces inside the air handler and  
remains there until the air warms  
sufficiently to re-evaporate it.  
1
2
3
Remove the vent and drain  
plugs.  
12 Replace all panels and parts and  
restore electrical power to the  
unit.  
Blow the coil out as completely  
as possible with compressed air.  
13 Be careful any contaminated  
material does not contact other  
areas of the unit or building.  
Properly dispose of all  
Fill and drain the coil several  
times with full strength glycol so  
that it mixes thoroughly with the  
water retained in the coil.  
contaminated materials and  
cleaning solution.  
4
5
Drain the coil out as completely  
as possible.  
Coil Winterization  
To ensure no water remains in  
the coil, do not replace the vent  
and drain plugs until the coils are  
put back into service.  
Providing a moisture purge cycle  
15 to 30 minutes after shutdown  
disperses the cold, humid air inside  
the air-handling system more evenly  
throughout the building. This four-  
step cycle:  
Water coil winterization procedures  
consist primarily of draining water  
from the coil before the heating  
season. Trane recommends flushing  
the coil with glycol if coils will be  
exposed to temperatures below 35  
degrees.  
CAUTION  
Twisted Tubes!  
Use care in removing header plugs  
from type P2, P4, and P8 coils.  
Overtorquing may result in twisted  
tubes.  
Closes the outdoor air dampers.  
Turns off the cooling coil.  
Install field-fitted drains and vents to  
permit winterization of coils not in  
use and to assist in evacuating air  
from the water system during  
Opens any variable-air-volume  
terminals connected to the air  
handler.  
Operates the supply fan for  
10 to 15 minutes.  
startup. If draining is questionable  
because of dirt or scale deposits  
inside the coil, fill the coil with glycol  
before the heating season begins.  
Type K Coils  
Rotates inlet guide vanes full  
open to full close.  
1
Remove all vent and drain plugs.  
2
Allow the water to drain from the  
coil.  
Note: On many unit sizes, there are  
multiple coils in the coil module. Be  
sure to winterize all coils in a given  
coil module.  
Air movement discourages water  
condensation and hastens re-  
evaporation of any condensate that  
does happen to form. This simple  
preventative measure effectively  
combats microbial growth and curbs  
moisture-related deterioration of air-  
handling components.  
3
4
Remove the header covers.  
If tubes are fouled, clean the  
tubes with a nylon or wire brush.  
CAUTION  
Use Approved Glycol!  
Use a glycol approved for use with  
commercial cooling and heating  
systems and copper tube coils.  
Failure to do so may result in  
equipment damage.  
5
To ensure no water remains in  
the coil, do not replace the  
header covers until the coils are  
put back into service.  
Note: When the coils are put back  
into service, use new gaskets. Trane  
recommends washers be used  
under the bolt heads and bolts be  
evenly tightened to 50 ft.-lbs torque.  
CAUTION  
Avoid Coil Freezeup!  
Properly drain and vent the coils  
when they are not in use. Trane  
recommends glycol protection in all  
possible freezing applications.  
Failure to properly protect coils may  
result in equipment damage.  
CAH-SVX01A-EN  
53  
Routine Maintenance  
See “ƽ WARNING Hazardous  
Voltage with Capacitors!” on  
page 49 regarding  
Accumulated dirt and other organic  
matter exposed to water or extended  
periods of high relative humidity  
(60 percent or higher) can support  
microbial growth, which must be  
removed to prevent the unit from  
becoming a contaminant source.  
6
7
8
Repeat steps 4 and 5 as  
necessary.  
Confirm the drain line is open  
following the cleaning process.  
disconnection of power.  
ƽ WARNING  
Allow the unit to dry thoroughly  
before putting it back into  
service.  
Hazardous Chemicals!  
If evidence of contamination exists  
in either the wet or dry sections:  
Coil cleaning agents can be either  
acidic or highly alkaline. Handle  
chemical carefully. Proper handling  
should include goggles or face  
shield, chemical resistant gloves,  
boots, apron or suit as required. For  
personal safety refer to the cleaning  
agent manufacturer’s Materials  
Safety Data Sheet and follow all  
recommended safe handling  
9
Replace all panels and parts and  
restore electrical power to the  
unit.  
Determine and eliminate the  
cause.  
Remove the contamination.  
Sanitize the affected area.  
10 Be careful that any contaminated  
material does not contact other  
areas of the unit or building.  
Properly dispose of all  
See the “Troubleshooting” section  
on page 56 for assistance in  
identifying the cause.  
contaminated materials and  
cleaning solution.  
practices. Failure to follow all safety  
instructions could result in death or  
serious injury.  
If microbial growth on a non-porous  
insulating surface (closed cell  
insulation or sheet metal surface) is  
observed:  
To clean a porous insulating surface  
(fiberglass insulation):  
1
Disconnect all electrical power to  
the unit.  
Internal Insulation  
The process of cooling and  
dehumidification produces  
condensate that must be  
continuously removed from the air-  
handling unit. The section of the unit  
from the entering air side of the  
cooling coil to the leaving edge of  
the drain pan is considered to be the  
“wet” section of the unit. Other  
potentially “wet” sections are  
immediately downstream of a  
humidifier and/or an outside air  
intake section.  
1
Disconnect all electrical power to  
the unit.  
2
Wearing the appropriate  
2
Wearing the appropriate  
personal protective equipment,  
use a vacuum device with a  
HEPA filter (99.97 percent  
efficient at 0.3 micron particles)  
to remove the accumulated dirt  
and organic matter.  
personal protective equipment,  
use a brush for sheet metal  
surfaces or a soft sponge on a  
foil face or closed cell foam  
surface to mechanically remove  
the microbial growth.  
Note: Be careful not to tear the  
insulation surface or edges.  
Note: Be careful not to damage the  
non-porous surface of the insulation.  
3
Confirm the drain line is open  
following the cleaning process.  
3
4
5
Install a block-off to prevent  
spray from going into a dry  
section of the unit and/or system  
ductwork.  
Internal insulation in areas of the  
unit that are normally considered to  
be “dry” must also be periodically  
inspected to assure the insulation is  
clean and dry. Wet insulation in an  
area that is normally considered to  
be “dry” can indicate an operational  
problem (refer to the  
Troubleshooting” section on  
page 56 for further information). The  
equipment should be inspected a  
minimum of every six months or  
more frequently as operating  
experience dictates.  
4
Allow the unit to dry thoroughly  
before putting it back into  
service.  
Thoroughly clean all areas with  
an EPA-approved sanitizer  
specifically designed for HVAC  
use.  
5
6
Replace all panels and parts and  
restore electrical power to the  
unit.  
Rinse the affected surfaces  
thoroughly with fresh water and  
a fresh sponge to prevent  
potential corrosion of the drain  
pan and drain line.  
Be careful that any contaminated  
material does not contact other  
areas of the unit or building.  
Properly dispose of all  
contaminated materials and  
cleaning solution.  
54  
CAH-SVX01A-EN  
Routine Maintenance  
4
Wipe down each bulb with a  
clean cloth and alcohol. Avoid  
touching the bulb with bare  
hands as skin oils can accelerate  
future glass soiling and degrade  
the bulb performance.  
ƽ WARNING  
Ultraviolet (UV)  
Germicidal  
Hazardous Vapors!  
If large numbers of UV bulbs are  
broken, an appropriate respirator  
should be considered to prevent  
inhalation of mercury vapors. Failure  
to use a respirator could result in  
death or serious injury.  
Irradiation Lights  
The intensity of the ultraviolet  
energy emitted from the ultraviolet  
bulbs provided in this unit is  
5
6
Carefully return the bulb to the  
fixture and rotate it 90 degrees in  
either direction until it is firmly  
secured.  
dependent on the cleanliness and  
age of the bulb. The surface of the  
bulb should be kept as clean as  
possible for optimum intensity.  
Depending on the filtration level of  
the HVAC system and the general  
hygiene of the building, periodic  
cleaning may be necessary. Before  
attempting any maintenance  
ƽ CAUTION  
Broken Glass!  
Close and latch all unit panels  
and reenergize power to the  
lights.  
Bulbs are fragile and can be easily  
broken. Always use gloves and eye  
protection when handling these  
bulbs. Failure to handle bulbs  
properly may result in minor to  
moderate injury. Refer to the MSDS  
sheet from the bulb manufacturer  
for additional safety information.  
Replacement of ultraviolet bulbs  
procedures, always follow all  
warnings and cautions as detailed in  
this maintenance section.  
The ultraviolet bulb should be  
replaced annually if operated  
continuously or after 9,000 hours of  
use if operated intermittently.  
Replacement bulbs must be the  
specific size and wattage as  
Always use cloth gloves and  
suitable eye protection when  
cleaning or replacing these bulbs.  
Bulbs may break if dropped or  
handled improperly.  
ƽ WARNING  
Hazardous Voltage and  
Exposure to Ultraviolet  
Radiation!  
originally supplied from the factory.  
Note: Although the lights may  
continue to generate a characteristic  
blue glow beyond 9,000 operating  
hours, the ultraviolet radiation  
emitted by the bulbs degrades over  
time and will no longer provide the  
intended benefit.  
Disposal of Bulbs: UV bulbs, like  
fluorescent bulbs, contain mercury,  
which is a regulated hazardous  
waste. The disposal requirements  
for hazardous wastes are  
determined by local, state and  
federal guidelines. Check all  
regulations before disposing of  
bulbs to assure you have met all  
requirements.  
This product contains components  
that emit high-intensity ultraviolet  
(UV-C) radiation which can be  
harmful to unprotected eyes and  
skin.  
Disconnect all electric power,  
including remote disconnects and  
discharge all motor start/run  
capacitors before servicing. Follow  
proper lockout/tagout procedures to  
ensure the power cannot be  
inadvertently energized. For variable  
frequency drives or other energy  
storing components provided by  
Trane or others, refer to the  
1
Disconnect power to the HVAC  
unit and the ultraviolet bulbs.  
2
Wearing soft cloth gloves and  
safety glasses, use two hands to  
firmly grasp bulb at each end.  
Refer to the MSDS sheet from the  
bulb manufacturer for additional  
disposal, handling and safety  
information.  
3
4
Rotate bulb 90 degrees in either  
direction and move bulb away  
from the fixture and out of unit.  
To clean the bulbs:  
appropriate manufacturer’s  
Carefully install a new  
literature for allowable waiting  
periods for discharge of capacitors.  
Verify with an appropriate voltmeter  
that all capacitors have discharged.  
Failure to disconnect power and  
discharge capacitors before  
1
Disconnect all electrical power to  
the unit and the ultraviolet bulbs.  
replacement bulb in the fixture  
and rotate it 90 degrees in either  
direction until firmly secured.  
2
Wearing soft cloth gloves and  
safety glasses, use two hands  
and firmly grasp the bulb at each  
end.  
5
6
If broken bulbs are found or if  
you are required to dispose of  
used bulbs, the proper warning  
and cautions must be followed.  
servicing could result in death or  
serious injury.  
3
Rotate the bulb 90 degrees in  
either direction and move bulb  
away from the fixture and out of  
unit.  
After replacing bulbs, close and  
latch all unit panels and  
reenergize power to the lights.  
CAH-SVX01A-EN  
55  
Troubleshooting  
This section is intended to be used  
as a diagnostic aid only. For detailed  
repair procedures, contact your local  
Trane service representative.  
including remote disconnects before  
servicing. Follow proper lockout/  
tagout procedures to ensure the  
power can not be inadvertently  
energized. When necessary to work  
with live electrical components,  
have a qualified licensed electrician  
or other individual who has been  
trained in handling live electrical  
components perform these tasks.  
Failure to follow all of the  
ƽ WARNING  
Hazardous Service  
Procedures!  
The maintenance and  
troubleshooting procedures  
recommended in this section of the  
manual could result in exposure to  
electrical, mechanical or other  
potential safety hazards. Always  
refer to the safety warnings provided  
throughout this manual concerning  
these procedures. When possible,  
disconnect all electrical power  
recommended safety warnings  
provided, could result in death or  
serious injury.  
Table 8. Air handler troubleshooting recommendations  
Symptom  
Probable Cause  
Recommended Action  
Bearing is  
First start after relubrication (grease distribution) Allow machine to cool down and restart.  
excessively hot  
Over-lubrication  
Clean surface of grease and purge.  
Over tensioned belts  
No lubricant  
Misaligned bearing  
Blown fuse or open circuit breaker  
Overload trip  
Adjust belt tension.  
Apply lubricant. Check bearings for damage.  
Correct alignment. Check shaft level.  
Replace fuse or reset circuit breaker.  
Check and reset overload.  
Motor fails to start  
Improper wiring or connections  
Improper current supply  
Check wiring with diagram supplied on unit.  
Compare actual supply power with motor nameplate  
recommendations. Contact power company for adjustments.  
Check that motor and drive rotate freely. Check bearing lubricant.  
Check line for an open phase.  
Mechanical failure  
Open phase  
Motor stalls  
Overloaded motor  
Low line voltage  
Poor alignment  
Reduce load or replace with larger motor.  
Check across AC line. Correct voltage if possible.  
Align bearing set screws (see Figure 49). Loosen and retighten  
bearing set screws.  
Excessive vibration  
Bolts not removed.  
Over tensioned belts  
Misaligned drive  
Remove bolts (see the “Isolator Adjustment” section on page 24).  
Adjust belt tension.  
Align drive.  
Motor runs and then Partial loss of line voltage  
dies down  
Check for loose connections. Determine adequacy of main power  
supply.  
Starter shorts when motor warms up  
Motor does not come Low voltage at motor terminals  
Replace starter.  
Check across AC line and correct voltage loss if possible.  
Replace with larger sized wiring.  
up to speed  
Line wiring to motor too small  
Overloaded motor  
Motor overheats  
Reduce load or replace with a larger motor.  
Motor fan is clogged with dirt preventing proper Remove fan cover, clean fan and replace cover.  
ventilation  
Excessive motor  
noise  
Motor mounting bolts loose  
Rigid coupling connections  
Worn motor bearings  
Tighten motor mounting bolts.  
Replace with flexible connections.  
Replace bearings and seals.  
Fan rubbing on fan cover  
Rapid motor bearing Excessive overhung load due to overtensioned  
Remove interference in motor fan housing.  
Check belt tension and overhung load.  
wear  
drive  
Excessive overhung load due to a small diameter Replace sheave with larger one.  
motor sheave  
Loose fan belt  
Motor is poorly positioned  
Worn or damaged belt  
Worn sheaves  
Adjust belt tension.  
Replace belt or belt set. Check sheave alignment.  
Replace sheaves.  
56  
CAH-SVX01A-EN  
Troubleshooting  
Table 5. Air handler troubleshooting recommendations  
Symptom  
Short belt life  
Probable Cause  
Worn sheaves  
Recommended Action  
Replace sheaves.  
Misaligned belt  
Grease or oil on belts  
Belt slipping  
Belts rubbing  
Poor alignment  
Realign drive with MVP sheave set at mean pitch diameter.  
Check for leaky bearings. Clean belts and sheaves.  
Improper belt tension. Adjust tension.  
Remove obstruction or realign drive for clearance.  
Loosen bearing set screws and realign (see the “Bearing Set Screw  
Alignment” section on page 50).  
Bearing noise  
Failed bearing  
Replace bearing.  
Inadequate lubrication  
Incorrect airflow  
Incorrect water flow  
Replace bearing.  
Check fan operating condition.  
Inspect the water pumps and valves for proper operation and check  
the lines for obstructions.  
Low water coil  
capacity  
Incorrect water temperature  
Coil is piped incorrectly  
Adjust the chiller or boiler to provide the proper water  
temperature.  
Verify coil piping (see the “Coil Piping and Connections” section on  
page 28.  
Dirty fin surface  
Incorrect glycol mixture  
Low refrigerant coil Incorrect airflow  
Clean the fin surface (see the “Coils” section on page 52).  
Verify glycol mixture and adjust if necessary.  
Check fan operating condition.  
capacity  
Expansion valve is not operating properly or is  
sized incorrectly  
Check sensing bulb temperature.  
Verify valve operation.  
Verify proper valve size.  
Incorrect refrigerant charge  
Condensing unit failure  
Coil is piped incorrectly  
Verify refrigerant charge and adjust if necessary.  
Verify condensing unit operation.  
Verify coil piping (see the “Coil Piping and Connections” section on  
page 28).  
Clogged refrigerant line filter  
Failure of suction/liquid line components  
Dirty fin surface  
Change filter core.  
Verify component operation  
Clean the fin surface (see the “Coils” section on page 52).  
Note: Do not use steam to clean refrigerant coils.  
Verify defrost cycle operation.  
Fin frosting  
Verify frostat operation.  
Verify refrigerant charge.  
Low steam coil  
capacity  
Incorrect airflow  
Coil is piped incorrectly  
Check fan operating condition.  
Verify coil piping (see the “Coil Piping and Connections” section on  
page 28).  
Incorrect steam pressure  
Excessive steam superheat  
Verify steam pressure and adjust if necessary.  
Check steam superheat.  
Steam superheat should not exceed 50ºF.  
Verify component operation  
Failure of steam line/condensate return  
components  
Boiler failure  
Verify boiler operation  
Dirty fin surface  
Plugged Drain Line  
Unit not level  
Clean the fin surface (see the “Coils” section on page 52).  
Clean drain line  
Level unit  
Drain pan is  
overflowing  
Improper trap design  
Improper trap design  
Unit not level  
Design trap per unit installation instructions  
Design trap per unit installation instructions  
Level unit  
Standing water in  
drain pan  
Plugged Drain Line  
Coil face velocity too high  
Improper trap design  
Drain pan leaks/overflows  
Condensation on surfaces  
Missing filters  
Clean drain line  
Reduce fan speed  
Design trap per unit installation instructions  
Repair leaks  
Insulate surfaces  
Wet interior  
insulation  
Excess dirt in unit  
Replace filters  
Filter bypass  
Standing water in drain pan  
Reduce filter bypass by ensuring all blockoffs are in place.  
See “Standing water in drain pan”  
Microbial growth  
(mold) inside air  
handler  
CAH-SVX01A-EN  
57  
Notes  
58  
CAH-SVX01A-EN  
Notes  
CAH-SVX01A-EN  
59  
Literature Order Number  
Date  
CAH-SVX01A-EN  
July 2005  
New  
Supersedes  
Trane  
A business of American Standard Companies  
Stocking Location  
Inland  
For more information, contact your local Trane  
office or e-mail us at [email protected]  
Trane has a policy of continuous product and product data improvement and reserves the right to  
change design and specifications without notice.  

Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Muy Ana User Manual
Mitsubishi Motors Automobile Parts V5m3 User Manual
Motorola Symbol Ds3578 User Manual
Oki Lan 510w User Manual
Samsung Aw078aa User Manual
Samsung Aw0805b User Manual
Samsung Clp 315nk User Manual
Sanyo Cadnica Cp 1300scr User Manual
Xerox 240 St User Manual
York Sunline Deg 036 User Manual