Toshiba Ram Sm800krt E User Manual

FILE NO. A02-013  
SERVICE MANUAL  
<OWNER’S MANUAL/INSTALLATION MANUAL>  
SPLIT TYPE  
RAV-SM560AT-E/RAV-SM800AT-E  
RAV-SM560UT-E/RAV-SM800UT-E  
RAV-SM560BT-E/RAV-SM800BT-E  
RAV-SM560KRT-E/RAV-SM800KRT-E  
R410A  
PRINTED IN JAPAN, Apr.,2003 ToMo  
Outdoor Unit ––––––––– RAV-SM800AT-E/RAV-SM800AT-E  
INSTALLATION MANUAL  
PRECAUTIONS FOR SAFETY ................................................ 1  
ACCESSORY AND REFRIGERANT ........................................ 3  
SELECTION OF INSTALLATION ............................................. 3  
REFRIGERANT PIPING ........................................................... 8  
EVACUATING ......................................................................... 10  
ELECTRICAL WORK ............................................................. 12  
FINAL INSTALLATION CHECKS........................................... 13  
RAV-SM560UT-E/RAV-SM800UT-E  
INSTALLATION MANUAL  
Accessory parts and Parts to be procured locally ............ 31  
PRECAUTIONS FOR SAFETY .............................................. 32  
SELECTION OF INSTALLATION PLACE .............................. 34  
DRAIN PIPING WORK ........................................................... 39  
REFRIGERANT PIPING ......................................................... 41  
EVACUATING ......................................................................... 42  
ELECTRICAL WORK ............................................................. 44  
TEST RUN .............................................................................. 47  
TROUBLESHOOTING ............................................................ 48  
RAV-SM560BT-E/RAV-SM800BT-E  
INSTALLATION MANUAL  
Accessory parts and Parts to be procured locally ............ 63  
PRECAUTIONS FOR SAFETY .............................................. 64  
SELECTION OF INSTALLATION PLACE .............................. 66  
INSTALLATION OF INDOOR UNIT........................................ 67  
AIR DUCTING WORK ............................................................ 70  
DRAIN PIPING WORK ........................................................... 74  
REFRIGERANT PIPING ......................................................... 75  
EVACUATING ......................................................................... 76  
ELECTRICAL WORK ............................................................. 77  
INSTALLATION/SERVICINGTOOLS ..................................... 78  
RAV-SM560KRT-E/RAV-SM800KRT-E  
INSTALLATION MANUAL  
Accessory parts and Parts to be procured locally ............ 91  
PRECAUTIONS FOR SAFETY .............................................. 92  
INSTALLATION PROCEDURE .............................................. 94  
SELECTION OF INSTALLATION PLACE .............................. 95  
INSTALLATION OF INDOOR UNIT........................................ 95  
DRAIN PIPING WORK ........................................................... 96  
REFRIGERANT PIPING ......................................................... 98  
EVACUATING ......................................................................... 99  
ELECTRICAL WORK ........................................................... 102  
IMPROVING SYSTEM EFFICIENCY ................................... 104  
FINAL INSTALLATION CHECKS......................................... 104  
ENVIRONMENT.................................................................... 106  
???  
INSTALLATION MANUAL  
1
PRECAUTIONS FOR SAFETY  
• Ensure that all Local, National and International regulations are satisfied.  
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.  
• The precautions described below include the important items regarding safety. Observe them without fail.  
• After the installation work, perform a trial operation to check for any problem.  
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.  
Turn off the main power supply switch (or breaker) before the unit maintenance.  
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.  
CAUTION  
New Refrigerant Air Conditioner Installation  
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT DE-  
STROY OZONE LAYER.  
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure  
is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil  
has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or  
refrigerating oil does not enter the refrigerating cycle.  
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging  
port of the main unit and installation tools are charged from those for the conventional refrigerant.  
Accordingly the exclusive tools are required for the new refrigerant (R410A).  
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust  
does not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance  
force and impurity in it.  
CAUTION  
To Disconnect the Appliance from Main Power Supply.  
This appliance must be connected to the main power supply by means of a switch with a contact separation of  
at least 3 mm.  
The installation fuse (25A D type  
) must be used for the power supply line of this conditioner.  
WARNING  
• Ask an authorized dealer or qualified installation professional to install/maintain the air  
conditioner.  
Inappropriate installation may result in water leakage, electric shock or fire.  
Turn off the main power supply switch or breaker before attempting any electrical work.  
Make sure all power switches are off. Failure to do so may cause electric shock.  
• Connect the connecting cable correctly.  
If the connecting cable is connected in a wrong way, electric parts may be damaged.  
• When moving the air conditioner for the installation into another place, be very careful not  
to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.  
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes abnor-  
mally high and it may resultingly causes pipe burst and injuries on persons.  
• Do not modify this unit by removing any of the safety guards or by by-passing any of the  
safety interlock switches.  
• Exposure of unit to water or other moisture before installation may cause a short-circuit of  
electrical parts.  
Do not store it in a wet basement or expose to rain or water.  
1
• After unpacking the unit, examine it carefully if there are possible damage.  
• Do not install in a place that might increase the vibration of the unit.  
• To avoid personal injury (with sharp edges), be careful when handling parts.  
• Perform installation work properly according to the Installation Manual.  
Inappropriate installation may result in water leakage, electric shock or fire.  
• When the air conditioner is installed in a small room, provide appropriate measures to  
ensure that the concentration of refrigerant leakage occur in the room does not exceed the  
critical level.  
• Install the air conditioner securely in a location where the base can sustain the weight  
adequately.  
• Perform the specified installation work to guard against an earthquake.  
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.  
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.  
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.  
• After the installation work, confirm that refrigerant gas does not leak.  
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas  
might generate.  
• Electrical work must be performed by a qualified electrician in accordance with the Installa-  
tion Manual. Make sure the air conditioner uses an exclusive power supply.  
An insufficient power supply capacity or inappropriate installation may cause fire.  
• Use the specified cables for wiring connect the terminals securely fix. To prevent external  
forces applied to the terminals from affecting the terminals.  
• Be sure to provide grounding.  
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.  
• Conform to the regulations of the local electric company when wiring the power supply.  
Inappropriate grounding may cause electric shock.  
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible  
gas.  
If a combustible gas leaks, and stays around the unit, a fire may occur.  
Required tools for installation work  
R410A (Special requirement)  
1) Philips screw driver  
2) Hole core drill (65 mm)  
3) Spanner  
17) Gauge manifold  
9) Thermometer  
10) Mega-tester  
11) Electro circuit tester  
12) Hexagonal wrench  
13) Flare tool  
(Charge hose : R410A special requirement)  
18) Vacuum pump  
(Charge hose : R410A special requirement)  
4) Pipe cutter  
19) Torque wrench  
5) Knife  
1/4 (17 mm) 16 N•m (1.6 kgf•m)  
3/8 (22 mm) 42 N•m (4.2 kgf•m)  
1/2 (26 mm) 55 N•m (5.5 kgf•m)  
5/8 (15.9 mm) 120 N•m (12.0 kgf•m)  
6) Reamer  
14) Pipe bender  
15) Level vial  
7) Gas leak detector  
8) Tape measure  
16) Metal saw  
20) Copper pipe gauge adjusting projection margin  
21) Vacuum pump adapter  
2
2
ACCESSORY AND REFRIGERANT  
Accessory and Installation Parts  
Refrigerant Piping  
Piping kit used for the conventional refrigerant cannot  
be used.  
Use copper pipe with 0.8 mm or more thickness for  
Ø6.4, Ø9.5, Ø12.7.  
1
3
4
Outdoor unit  
Protective bush  
Installation manual x 1  
(For SM800AT only)  
Use copper pipe with 1.0 mm or more thickness for  
Ø15.9.  
Drain nipple  
Flare nut and flare works are also different from those  
of the conventional refrigerant. Take out the flare nut  
attached to the main unit of the air conditioner, and  
use it.  
2
Guard material for  
passage part  
(For SM800AT only)  
Waterproof rubber cap  
3
SELECTION OF INSTALLATION  
<SM800AT-E>  
Before installation  
Length of refrigerant pipe  
connected to  
Be careful to the following items before installation.  
Item  
indoor/outdoor unit  
Addition of refrigerant is  
unnecessary at the local site.  
Length of refrigerant pipe  
20m or shorter  
<SM560AT-E>  
<Addition of refrigerant>  
Add 40g of refrigerant for every  
1m of pipe which exceeds 20m.  
21m to 50m  
*
Length of refrigerant pipe  
connected to  
Item  
indoor/outdoor unit  
* Caution at addition of refrigerant  
Addition of refrigerant is  
unnecessary at the local site.  
When the total length of refrigerant pipe exceeds  
20m, add 40g/m of refrigerant and the maximum total  
length of pipe is 50m.  
20m or shorter  
<Addition of refrigerant>  
Add 20g of refrigerant for every  
1m of pipe which exceeds 20m.  
21m to 30m  
(Max. amount of additional refrigerant is 1200g.)  
*
Charge the refrigerant accurately. Overcharge may  
cause a serious trouble of compressor.  
* Caution at addition of refrigerant  
When the total length of refrigerant pipe exceeds  
20m, add 20g/m of refrigerant and the maximum total  
length of pipe is 30m.  
Air purge  
For air purge, use a vacuum pump.  
(Max. amount of additional refrigerant is 200g.)  
Do not use refrigerant charged in the outdoor unit for  
air purge. (The refrigerant for air purge is not con-  
tained in the outdoor unit.)  
Charge the refrigerant accurately. Overcharge may  
cause a serious trouble of compressor.  
Electrical cabling  
Be sure to fix the power cables and indoor/outdoor  
connecting cables with clamps so that they do not  
contact with the cabinet, etc.  
3
Installation Place  
Necessary Space for Installation  
Obstacle at rear side  
A place which provides a specified space around the  
outdoor unit.  
A place where the operation noise and discharged air  
are not given to your neighbors.  
<Upper side is free>  
1. Single unit installation  
A place that is not exposed to a strong wind.  
A place that does not block a passage.  
When the outdoor unit is installed in an elevated  
position, be sure to secure its feet.  
There must be sufficient space for carrying in the  
unit.  
2. Obstacles at both right and left sides.  
A place where the drain water does not make any  
The height of the  
obstacle should be  
lower than the height  
of the outdoor unit.  
problem.  
CAUTION  
150  
or more  
300  
or more  
1. Install the outdoor unit at a place where dis-  
charge air is not blocked.  
3. Serial installation of two or more units  
2. When an outdoor unit is installed in a place that  
is always exposed to a strong wind like a coast  
or on a high storey of a building, secure a  
normal fan operation by using a duct or a wind  
shield.  
3. When installing the outdoor unit in a place that is  
constantly exposed to a strong wind such as the  
upper stairs or rooftop of a building, apply the  
windproof measures referring to the following  
examples.  
150  
or more  
300  
or more  
300  
or more  
300  
or more  
The height of the obstacle should be lower  
than the height of the outdoor unit.  
1) Install the unit so that its  
discharge port faces to the  
wall of the building. Keep a  
distance 500 mm or more  
between the unit and the  
wall surface.  
<Obstacle also at the upper side>  
150  
or more  
2) Supposing the wind direction during the  
operation season of the air conditioner, install  
the unit so that the discharge port is set at  
right angle to the wind direction.  
Obstacle at front side  
Strong  
wind  
<Upper side is free>  
Strong  
wind  
1. Single unitIn installation  
4. Installation in the following places may result in  
some troubles. Do not install the unit in such  
places below.  
2. Serial installation of two or more units  
A place full of machine oil.  
A place full of sulphuric gas.  
A place where high-frequency radio waves are  
likely to be generated as from audio quipment,  
welders, and medical equipment.  
4
3
SELECTION OF INSTALLATION  
<Obstacle also at the upper side>  
Installation of Outdoor Unit  
Before installation, check strength and horizontality of  
the base so that abnormal sound does not generate.  
1000  
or more  
According to the following base diagram, fix the base  
firmly with the anchor bolts.  
(Anchor bolt, nut: M10 x 4 pairs)  
<SM560AT-E>  
90  
600  
115  
90  
Obstacles at both front and rear sides  
Open the upper side and both right and left sides.  
The height of obstacle at both front and rear side,  
should be lower than the height of the outdoor unit.  
<Standard installation>  
Ø28 Drain hole  
1. Single unit installation  
<SM800AT-E>  
150  
600  
150  
430  
Drain hole  
Drain nipple mounting hole  
Knockout hole  
2. Serial installation of two or more units  
Set the out margin of the anchor bolt to 15mm or less.  
15 or less  
300  
or more  
300  
or more  
In case of drainning through the drain hose, attach  
the following drain nipple and the waterproof rubber  
cap, and use the drain hose (Inner diam.: 16mm) sold  
on the market. And also seal the screws securely with  
silicone material, etc. so that water does not drop  
down. Some conditions may cause dewing or drip-  
ping of water.  
Serial installation at front and rear sides  
Open the upper side and both right and left sides.  
The height of obstacle at both front and rear sides  
should be lower than the height of the outdoor unit.  
<Standard installation>  
1000  
or more  
300  
or more  
1500  
or more  
2000  
or more  
200  
or more  
Drain nipple  
Waterproof rubber cap  
5
<SM560AT-E>  
Refrigerant Piping Connection  
CAUTION  
TAKE NOTICE THESE IMPORTANT  
Waterproof rubber cap  
4 POINTS BELOW FOR PIPING WORK  
1. Keep dust and moisture away from inside the  
connecting pipes.  
2. Tightly connect the connection between pipes  
and the unit.  
Base plate  
3. Evacuate the air in the connecting pipes using  
VACUUM PUMP.  
Drain nipple  
4. Check gas leak at connected points.  
<SM800AT-E>  
<Piping connection>  
Knockout hole  
Capacity  
rank  
Liquid side  
Gas side  
Outer  
diameter  
Outer  
diameter  
Thickness  
Thickness  
RAV-  
Open  
Waterproof rubber cap  
Drain nipple  
SM560  
SM800  
Ø6.4  
0.8  
0.8  
Ø12.7  
0.8  
1.0  
Ø9.5  
Ø15.9  
When there is a possibility of freezing of drain at the  
cold district or a snowfall area, be careful for drainage  
ability of drain.The drainage ability increases when a  
knockout hole on the base plate is opened. (Open the  
knockout hole to outside using a screwdriver, etc.)  
Optional Installation Parts  
(Local Procure)  
Parts name  
Refrigerant piping  
Q’ty  
A
Liquid side : Ø6.35 mm or Ø9.52 mm  
Each one  
Gas side : Ø12.7 mm or Ø15.9 mm  
Pipe insulating material  
(polyethylene foam, 6 mm thick)  
B
C
1
Putty, PVC tapes  
Each one  
6
3
SELECTION OF INSTALLATION  
How to remove the front panel  
Knockout of Pipe Cover  
1. Remove screws of the front panel.  
2. Pull the front panel downward.  
<SM800AT-E>  
Removing the front panel, the electric parts appear at  
the front side.  
The metal pipes are attachable to the piping holes.  
If the size of the used power pipe does not match  
with the hole, adjust the hole size to match with pipe  
size.  
Rear direction  
Pipe cover  
Be sure to fix the power cable and indoor/outdoor  
connecting cable with bundling band sold on the  
market so that they do not make contact with the  
compressor and discharge pipe.  
(Temperature of the compressor and discharge pipe  
becomes high.)  
Side direction  
Front direction  
Down direction  
In order to avoid the force applied to on the connect-  
ing section, be sure to fix the cables to the cord  
clamps provided on the pipe valve fixing plate and the  
electric parts box.  
Knockout procedure  
The indoor/outdoor connecting pipes can be con-  
nected to 4 directions.  
Electric parts box  
Front panel  
Take off the knockout part of the pipe cover in which  
pipes or wires pass through the base plate.  
As shown in the figure, do not remove the pipe cover  
from the cabinet so that the knockout hole can be  
easily punched.To knock out, it is easily taken off by  
hands by punching a position at the lower side of 3  
connected parts with screwdriver along the guide  
line.  
Pipe valve  
fixing plate  
Piping  
hole  
After marking the knockout hole, remove the burr and  
mount the attached protective bush and guard  
material for pass-through part in order to protect  
pipes and wires.  
Cord clamp  
After connecting the pipes, be sure to mount the pipe  
cover. The pipe cover is easily mounted by cutting off  
the slit at the lower part of the pipe cover.  
7
4
REFRIGERANT PIPING  
• Flaring size : A (Unit : mm)  
Pipe Forming/End Positioning  
+0  
<SM560AT-E>  
A
-
0.4  
Outer dia. of copper pipe  
Forming of pipe  
R410A  
9.1  
R22  
9.0  
Form the pipe along with a marked line of the cabinet.  
End positioning of pipe  
6.35  
9.52  
12.7  
15.9  
13.2  
16.6  
19.7  
13.0  
16.2  
19.4  
Match the ends of both pipes at at a distance of  
85 mm apart from the marked line.  
* In case of flaring for R410A with the conventional  
flare tool, pull it out approx. 0.5 mm more than that of  
R22 to adjust to the specified flare size. The copper  
pipe gauge is useful for adjusting projection margin  
size.  
A
Marked line  
• Projection margin in flaring : B (Unit : mm)  
Rigid (Clutch type)  
Flaring  
1. Cut the pipe with a pipe cutter.  
Outer dia.  
of copper  
pipe  
R410A tool used  
R410A R22  
Conventional tool used  
R410A R22  
6.35  
9.52  
12.7  
15.9  
0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0  
0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0  
0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0  
0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0  
90˚  
Obliquity Roughness  
Warp  
Imperial (Wing nut type)  
2. Insert a flare nut into the pipe, and flare the pipe.  
Outer dia. of copper pipe  
R410A  
R22  
As the flaring sizes of R410A differ from those of  
refrigerant R22, the flare tools newly manufactured  
for R410A are recommended.  
However, the conventional tools can be used by  
adjusting projection margin of the copper  
6.35  
9.52  
12.7  
15.9  
1.5 to 2.0  
1.5 to 2.0  
2.0 to 2.5  
2.0 to 2.5  
1.0 to 1.5  
1.0 to 1.5  
1.5 to 2.0  
1.5 to 2.0  
pipe.  
B
8
4
REFRIGERANT PIPING  
Tightening of Connecting Part  
REQUIREMENT  
(Unit: Nm)  
1. Do not put the spanner on the cap. The valve  
may be broken.  
Outer dia. of copper pipe  
6.35mm (diam.)  
Tightening torque  
2. If applying excessive torque, the nut may be  
broken according to some installation conditions.  
14 to 18 (1.4 to 1.8kgfm)  
33 to 42 (3.3 to 4.2kgfm)  
50 to 62 (5.0 to 6.2kgfm)  
63 to 77 (6.3 to 7.7kgfm)  
9.52mm (diam.)  
12.7mm (diam.)  
After the installation work, be sure to check gas leak  
of connecting part of the pipes with nitrogen.  
15.9mm (diam.)  
Flare at  
indoor unit side  
Cover  
Flare at  
outdoor unit side  
Align the centers of the connecting pipes and tighten  
the flare nut strong as far as possible with your  
fingers.  
Then fix the nut with a spanner and tighten it with  
torque wrench as shown in the figure.  
Half union or packed valve  
Flare nut  
Pressure of R410A is higher than that of R22  
(Approx. 1.6 times).Therefore, using a torque  
wrench, tighten the flare pipe connecting sections  
which connect the indoor/outdoor units at the speci-  
fied tightening torque. Incomplete connections may  
cause not only a gas leak, but also a trouble of the  
refrigeration cycle.  
Externally  
threaded side  
Internally  
threaded side  
Fix with spanner.  
Tighten with torque wrench.  
As shown in the figure, be sure to use a double  
spanner to loosen or tighten the flare nut of the valve  
at gas side. If using a single spanner, the nut cannot  
be tightened with necessary tightening torque.  
Do not apply refrigerating machine oil to  
the flared surface.  
On the contrary, use a single spanner to loosen or  
tighten the flare nut of the valve at liquid side.  
Cover  
Cap  
Piping valve  
Loosened  
Tightened  
Flare nut  
SM800 type valve at gas side  
9
5
EVACUATING  
Air Purge  
This air conditioner can be installed up to the connecting pipe length and height difference in the following table.  
Height difference (m)  
Max. connecting  
pipe length (m)  
Hexagonal  
wrench size  
Capacity rank  
Outdoor unit at upper side Outdoor unit at lower side  
SM560 type  
SM800 type  
30  
50  
30  
30  
15  
15  
4mm  
With respect to the preservation of terrestrial environment, adopt Vacuum pumpfor air purge (Evacuate air in  
the connecting pipes) when installing the unit.  
Do not discharge the refrigerant gas to the atmosphere to preserve the terrestrial environment.  
Use a vacuum pump to discharge the air (nitrogen, etc.) remained in the set. If the air remains, the capacity  
may decrease.  
For the vacuum pump, be sure to use one with backflow preventer so that the oil in the pump does not backflow  
into the pipe of the air conditioner when the pump stops. (If oil in the vacuum pump is put in an air conditioner  
including R410A, it may cause trouble on the refrigeration cycle.)  
Vacuum pump  
As shown in the right figure, connect the charge hose after the manifold valve are closed completely.  
Attach the connecting port of the charge hose with a projection to push the valve core (setting pin) to the charge port of the set.  
Open handle Low fully.  
Turn ON the vacuum pump (*1)  
Loosen the flare nut of the packed valve (Gas side) a little to check the air passes through. (*2)  
Tighten the flare nut again.  
Execute vacuuming until the compound pressure gauge indicates 101kPa (76cmHg). (*1)  
Close handle Low completely.  
Turn OFF the vacuum pump.  
Leave the vacuum pump as it is for 1 or 2 minutes, and check the indicator of the compound pressure gauge does not return.  
Open fully the valve stem or the valve handle. (First, at liquid side, then gas side)  
Disconnect the charge hose from the charge port.  
Tighten valve and caps of the charge port surely.  
10  
5
EVACUATING  
Valve unit  
<SM560AT-E>  
OPEN  
Compound pressure gauge  
Pressure gauge  
101kPa  
(76cmHg)  
Manifold valve  
Handle  
Pull out the handle and  
using cutting pliers, etc.  
turn it counterclockwise  
by 90˚. (Open fully)  
Handle Lo  
Handle Hi  
(Keep fully closed)  
Charge hose  
(For R410A only)  
Charge hose  
(For R410A only)  
Charge port  
Vacuum pump adapter  
for counter-flow prevention  
(For R410A only)  
Flare nut  
Valve unit  
CLOSE  
Vacuum  
pump  
Packed valve (Gas side)  
Push in handle.  
Service port (Valve core (Setting pin))  
Flare nut  
Valve unit  
Charge port  
Stopper  
Charge cap  
Flare nut  
Handle position  
Charge port  
Valve rod  
<SM800AT-E>  
Compound pressure gauge  
Pressure gauge  
Handle  
101kPa  
(76cmHg)  
Manifold valve  
Opened fully  
Closed completely  
Handle Lo  
Handle Hi  
(Keep fully closed)  
Charge hose  
(For R410A only)  
*1. Use the vacuum pump, vacuum pump adapters,  
and gauge manifold referring to the manuals  
attached to each tool before using them. For the  
vacuum pump, check oil is filled up to the specified  
line of the oil gauge.  
Charge hose  
(For R410A only)  
Service port  
(Valve core (Setting pin))  
Vacuum pump adapter  
for counter-flow prevention  
(For R410A only)  
*2. While the air is purged, check again that the  
connecting port of charge hose, which has a  
projection to push the valve core, is firmly con-  
nected to the charge port.  
Vacuum  
pump  
Packed valve at gas side  
Valve handling precautions  
Open the valve stem or the handle until it strikes  
the stopper. It is unnecessary to apply further  
force.  
Ø6.4  
Ø9.5  
14 to 18Nm (1.4 to 1.8kgfm)  
33 to 42Nm (3.3 to 4.2kgfm)  
33 to 42Nm (3.3 to 4.2kgfm)  
20 to 25Nm (2.0 to 2.5kgfm)  
14 to 18Nm (1.4 to 1.8kgfm)  
Valve size  
Ø12.7  
Ø15.9  
Securely tighten the cap with a torque wrench.  
Cap tightening torque  
Charge port  
11  
6
ELECTRICAL WORK  
For the air conditioner that has no power cable, connect  
a power cable as mentioned below.  
How to wire  
1. Connect the connecting cable to the terminal as  
identified with their respective numbers on the  
terminal block of indoor and outdoor unit.  
Model  
RAV-  
SM560AT-E SM800AT-E  
220 240 V  
H07 RN-F or 245 IEC 66 (1.0 mm2 or more)  
Power supply  
Single phase 50 Hz  
2. When connecting the connecting cable to the  
outdoor unit terminal, prevent water coming in the  
outdoor unit.  
Maximum running current  
Installation fuse rating  
12A  
15A  
25 A (D type  
)
3. Insulate the unsheathed cords (conductors) with  
electrical insulation tape. Process them so that they  
do not touch any electrical or metal parts.  
H07 RN-F or 245 IEC 66  
(2.5 mm2 or more)  
Power cable  
4. For inter connecting cable, do not use a wire jointed  
to another on the way.  
CAUTION  
Use wires long enough to cover the entire length.  
Wrong wiring may cause a burn-out to some  
electrical parts.  
Terminal block  
Be sure to use the cord clamps attached to the  
1
2
3
L
N
product.  
Do not damage or scratch the conductive core  
and inner insulator of power and inter-connecting  
cables when peeling them.  
Screw  
Be sure to comply with local regulations of the  
cable from outdoor unit to indoor unit.  
(wire size and cabling method etc.)  
Power cable  
Connecting  
cable  
Use the power and Inter-connecting cables with  
specified thickness, specified type and protective  
devices required.  
Stripping length power cord and connecting cable  
<SM560AT-E>  
10  
10  
1 2 3  
L
N
10  
10  
How to remove the valve cover  
1. Remove screws of the valve cover.  
40  
40  
30  
30  
2. Pull the valve cover downward to remove it.  
Earth line Earth line  
(mm)  
Connecting  
cable  
Power cable  
Valve cover  
Piping cover  
CAUTION  
The installation fuse (25A D type  
) must  
be used for the power supply line of this air  
conditioner.  
Incorrect/incomplete wiring might cause an  
electrical fire or smoke.  
Cord clamp  
Indoor/outdoor  
connecting cables  
Power cable  
Prepare the exclusive power supply for the air  
conditioner.  
This product can be connected to the mains.  
Connection to the fixed wiring :  
A switch which disconnects all poles and has a  
contact separation of at least 3 mm must be  
incorporated in the fixed wiring.  
12  
7
FINAL INSTALLATION CHECKS  
Check and Test Operation  
For R410A, use the leak detector exclusively manufactured for HFC refrigerant (R410A, R134a, etc.).  
The conventional leak detector for HCFC refrigerant  
(R22, etc.) cannot be used because its sensitivity for  
HFC refrigerant lowers to approx. 1/40.  
*
Valve cover  
Piping  
cover  
Pressure of R410A is approx. 1.6 times higher than  
that of R22.  
If installation work is incompletely finished, a gas  
leakage may occur when pressure rises during  
operation.  
Flare nut  
connections  
(Indoor unit)  
Therefore, be sure to test the piping connections for  
leakage.  
Check gas leakage at the flare nut connections, valve  
stem cap connections and service port cap fittings  
with a leak detector or soap water.  
Check points  
of outdoor unit  
Useful Functions (SM800AT-E only)  
Self-Diagnosis by LED Indication  
In addition to the code checking by remote controller of the indoor unit, troubles of the outdoor unit can be diag-  
nosed by LED indications on the cycle control P.C. board of the outdoor unit. Utilize them for various checks.  
For the check by remote controller of the indoor unit, refer to the Installation Manual of the indoor unit.  
Before a check, confirm each bit of the DIP switch is set to OFF position.  
LED indication and code checking  
Cycle control P.C. board  
DIP switch  
LED indication  
Cause  
SW800  
D800 D801 D802 D803  
Heat exchanger sensor (TE) error  
¡
l
¡
l
l
¡
¡
l
¡
l
¥
l
¥
l
¥
l
l
l
l
¡
¡
¡
¡
l
¡
¡
l
l
¥
¥
l
l
l
¡
l
¡
l
l
l
¡
l
¡
l
¡
l
l
l
¥
¥
l
l
l
l
l
¡
l
l
¡
l
¡
¡
l
l
l
l
l
¥
¡
Suction sensor (TS) error  
Discharge sensor (TD) error  
High-pressure protection error  
Outdoor temperature sensor (TO) error  
DC outside fan error  
LED  
indication  
Communication error between IPDU  
Discharge temp. error  
D800  
: Red  
¡
ON  
EEPROM error  
D801  
:Yellow  
¡
1
2
3
4
Communication error between IPDU  
G-Tr short-circuit protection  
D802  
:Yellow  
¡
Detect circuit error  
D803  
:Yellow  
¡
Current sensor error  
Comp. lock error  
Comp. break down  
: Rapid flash  
¥
Phase missing detection, Detection of coming-off of CT current sensor  
Serial communication error by thermo. operation of Comp. case  
: Go off  
l
: Go on  
¡
13  
Changes in the product and components  
Installation/ServicingTools  
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged acciden-  
tally, service port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads  
per inch)  
In order to increase the pressure resisting strength of the refrigerant piping flare processing diameter and size of  
opposite side of flare nuts has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)  
New tools for R410A  
New tools for R410A  
Applicable to R22 model  
Changes  
As pressure is high, it is impossible to measure by means of conventional  
gauge. In order to prevent any other refrigerant from being charged, each  
port diameter is changed.  
Gauge manifold  
×
In order to increase pressure resisting strength, hose materials and port  
size are changed (to 1/2 UNF 20 threads per inch).  
When purchasing a charge hose, be sure to check the port size.  
Charge hose  
×
Electronic balance  
for refrigerant charging  
As pressure is high and gasification speed is fast, it is difficult to read the  
indicated value by means of charging cylinder, as air bubbles occur.  
¡
Torque wrench  
The size of opposite sides of flare nuts have been increased. Incidentally,  
a common wrench is used for nominal diameters 1/4 and 3/8.  
×
¡
(nominal diam. 1/2, 5/8)  
Flare tool  
(clutch type)  
By increasing the clamp bars receiving hole, strength of spring in the tool  
has been improved.  
Gauge for projection adjustment  
Used when flare is made with using conventional flare tool.  
Connected to the conventional vacuum pump. It is necessary to use an  
adapter to prevent vacuum pump oil from flowing back to the charge hose.  
The charge hose connecting part has two ports-one for conventional  
refrigerant (7/16 UNF 20 threads per inch) and one for R410A.  
If the vacuum pump oil (mineral) mixes with R410A a sludge may occur  
and damage the equipment.  
Vacuum pump adapter  
¡
Gas leakage detector  
X
Exclusive for HFC refrigerant.  
×
Incidentally, the refrigerant cylindercomes with the refrigerant designation (R410A) and protector coating in the  
U,S.s ARI specified rose color (ARI color code: PMS 507).  
Also, the charge port and packing for refrigerant cylinderrequire 1/2 UNF 20 threads per inch corresponding to  
the charge hoses port size.  
14  
ACCESSORIES  
Remote controller  
Screws (two pcs.)  
Standard 4-way cassette  
panel optional parts  
PRECAUTIONS FOR SAFETY  
WARNING  
WARNINGS ABOUT INSTALLATION  
• Make sure to ask the qualified installation professional in electric work to install  
the air conditioner.  
If the air conditioner is inappropriate installed by yourself, it may cause water  
leak, electric shock, fire, and so on.  
• Ground the air conditioner without fail.  
Do not connect the ground wire to gas pipe, water pipe, lightning rod or ground  
wire of telephone. If the air conditioner is imperfectly grounded, it may cause  
electric shock.  
CAUTION  
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY  
This appliance must be connected to the mains by means of a switch with a  
contact separation of at least 3 mm.  
The installation fuse (25A D type  
supply line of this conditioner.  
) must be used for the power  
WARNINGS ABOUR OPERATION  
• Avoid cooling the room too strong or exposing the human body to cool breeze  
for a long time as it is bad for the health.  
• When you notice something abnormal with the air conditioner (smells like  
something scorching, poor cooling, etc.), immediately turn off the main switch,  
the circuit breaker, from the mains to stop the air conditioner, and contact the  
dealer.  
If the air conditioner is continuously operated with something abnormal, it may  
cause machine failure, electric shock, fire, and so on.  
WARNINGS ABOUT MOVEMENT AND REPAIR  
• Do not move or repair any unit by yourself.  
Since there is high voltage inside the unit, you may get electric shock when  
removing the cover and main unit.  
• Whenever the air conditioner needs repair, make sure to ask the dealer to do it.  
If it is repaired imperfectly, it may cause electric shock or fire.  
• When moving the air conditioner for re-installing at another place, ask the  
dealer to do it. If it is imperfectly installed, it may cause electric shock or fire.  
15  
CAUTION  
CAUTIONS ABOUT INSTALLATION  
• Certainly lay the drain hose for perfect draining.  
Bad drainage may cause flooding in the house and getting furniture  
wet.  
• Make sure to connect the air conditioner to an exclusive AC outlet of  
the rated voltage, otherwise the unit may break down or cause a fire.  
• Do not install the unit in a place where inflammable gas may leak.  
If inflammable gas accumulates around the unit, it may cause a fire.  
CAUTIONS ABOUT OPERATION  
• Carefully read this manual before starting the air conditioner.  
There are many important things to keep in mind for daily operation.  
• Do not use this air conditioner for special purpose such as preserv-  
ing food, precision instruments, art objects, breeding animals,  
growing potted plants, etc.  
• Avoid exposing potted plants and animals to the wind of the air  
conditioner, since it badly affects the health and growth of them.  
• When the air conditioner is operated with a combustion appliance in  
the same place, be careful of ventilation to let fresh air enter the  
room.  
Poor ventilation causes oxygen shortage.  
• When the air conditioner is used in a closed room, be careful of  
sufficient ventilation of the room. Poor ventilation causes oxygen  
shortage.  
• Do not touch any switches with wet finger, otherwise you may get an  
electric shock.  
• Do not place any combustion appliance in a place where it is directly  
exposed to the wind of air conditioner, otherwise it may cause  
imperfect combustion.  
• If the air conditioner won’t be used for a considerably long time, turn  
off the main switch or the circuit breaker, for safety. Disconnect from  
the power supply prevents the unit from lightning and power supply  
surge.  
• Check the concrete blocks, etc. of the base of the outdoor unit  
occasionally.  
If the base is left damaged or deteriorated, the unit may topple over  
and inflict an injury to a person as the worst case.  
• When cleaning the unit, make sure to turn off the main switch or the  
circuit breaker beforehand for preventing you from getting injured by  
the electric fan running inside. For details of cleaning method, refer to  
“Maintenance” on page 10.  
• Do not put anything on the outdoor unit nor step onto it. If you do so,  
it may not only topple over the unit but also injure yourself.  
To make the air conditioner operate in its original performance,  
operate it within the range of the operating temperature specified in  
the instructions.  
Otherwise it may cause a malfunction, or water leak from the unit.  
• Prevent any liquid from falling into the remote controller. Do not spill  
juice, water or any kind of liquid.  
16  
PARTS NAME  
Indoor unit  
Button  
Earth screw  
Button to open/close the  
suction port  
Provided in the electric parts  
box  
Discharge flap of  
discharge port  
Air filter  
Removes dust or trash.  
(Provided on the suction port.)  
Change the direction of the air  
to be discharged according to  
cool/heat mode.  
Suction air port  
The air in the room is sucked  
in from this port.  
Projection of air filter  
Remote controller  
Outdoor unit  
REMOTE CONTROLLER  
Air inlet (Side and rear)  
Pipes and electric wires  
Air outlet  
17  
PARTS NAME OF REMOTE CONTROLLER  
Display section  
CODE No.  
In the display example, all indicators are displayed for the explana-  
tion.  
SET DATA  
UNIT No.  
Display  
section  
SETTINGTEST R.C. No.  
In reality only, the selected contents are indicated.  
• When turning on the leak breaker at the first time, [SET  
DATA] flashes on the display part of the remote controller.  
While this display is flashing, the model is being automatically  
confirmed. Accordingly, wait for a while after [SET DATA]  
display has disappeared, and then use the remote controller.  
Operation  
section  
UNIT  
SET CL  
1
8
2
4
9
CODE No.  
SET DATA  
UNIT No.  
R.C. No.  
3
5
10  
12  
SETTING  
TEST  
11  
13  
6
14  
7
1
2
3
SET DATA display  
9
SWING display  
Displayed during setup of the timer.  
Displayed during up/down movement of  
the flap.  
Operation mode select display  
The selected operation mode is displayed.  
10  
Set up temperature display  
The selected set up temp. is displayed.  
CHECK display  
Displayed while the protective device works or a  
trouble occurs.  
11  
12  
Remote controller sensor display  
Displayed while the sensor of the remote  
controller is used.  
4
5
Timer time display  
Time of the timer is displayed.  
(When a trouble occurs, the check code is dis-  
played.)  
PRE-HEAT display  
Displayed when the heating operation  
starts or defrost operation is carried out.  
While this indication is displayed, the  
indoor fan stops or the mode enters in  
LOW.  
Timer SETIN setup display  
When pushing the Timer SETIN button, the  
display of the timer is selected in order of [OFF]  
[OFF] repeat OFF timer [ON]  
13  
14  
No function display  
Displayed if there is no function even if  
the button is pushed.  
No display.  
6
7
8
Filter display  
If “FILTER  
Air volume select display  
” is displayed, clean the air filter.  
The selected air volume mode is dis-  
played.  
TEST run display  
(AUTO)  
(HIGH)  
(MED.)  
(LOW)  
Displayed during a test run.  
Flap position display  
Displays flap position.  
18  
Operation section  
Push each button to select a desired operation.  
• The details of the operation needs to be set up once, afterward, the air conditioner can be used by pushing  
button only.  
1
7
8
2
4
3
5
9
UNIT  
10  
SET  
CL  
6
1
2
Air volume select button  
8
button  
Selects the desired air volume mode.  
When the button is pushed, the operation  
starts, and it stops by pushing the button  
again.  
Timer set button  
TIMER SET button is used when the timer is  
set up.  
When the operation has stopped, the operation  
lamp and all the displays disappear.  
3
4
Check button  
9
Operation select button  
The CHECK button is used for the check  
operation. During normal operation, do not  
use this button.  
Selects desired operation mode.  
10  
Set up temperature button  
Adjusts the room temperature.  
Fan button  
FAN button is used when a fan which is sold on  
the market or etc. is connected.  
Set the desired set temperature by pushing  
or  
.
• If “No function” is displayed on the remote  
controller when pushing the FAN button, a  
fan is not connected.  
5
6
Filter reset button  
Resets (Erases) “FILTER  
” display.  
UNIT and AUTO flap button  
UNIT (No function)  
OPTION :  
Remote controller sensor  
Usually the TEMP. sensor of the indoor unit senses  
the temperature.The temperature on the surround-  
ing of the remote controller can also be sensed.  
For details, contact the dealer from which you have  
purchased the air conditioner.  
7
Operation lamp  
Lamp is lit during the operation. Lamp is off  
when stopped.  
Although it flashes when operating the protec-  
tion device or abnormal time.  
19  
CORRECT USAGE  
When you use the air conditioner for the first time or when you change the SET DATA value, follow the proce-  
dure below. From the next time, the operation displayed on the remote controller will start by pushing the  
button only.  
Preparation  
Turn on the main power switch and/or the leakage breaker.  
• When the power supply is turned on, a partition line is displayed on the display part of the remote controller.  
After the power supply is turned on, the remote controller does not accept an operation for approx. 1 minute,  
but it is not a failure.  
*
REQUIREMENT  
• While using the air conditioner, operate it only with  
power switch and the leak breaker.  
button without turning off the main  
1
2
4
3
UNIT  
SET  
CL  
1
2
Push  
button.  
The operation lamp goes on, and the operation starts.  
Select an operation mode with the “MODE” button.  
AUTO  
HEAT  
DRY  
COOL  
FAN  
One push of the button, and the display  
changes in the order shown on the right.  
• In HEAT  
mode, if the room temperature reaches to the set temperature, the outdoor unit stops and  
the air flow becomes LOW and the air volume decreases.  
• In the defrost mode, the fan stops so that cool air is not discharged and PRE-DEF  
is displayed.  
3
4
Select air volume with “FAN ” button.  
AUTO  
HIGH  
MED.  
LOW  
One push of the button, and the display  
changes in the order shown on the right.  
• When air volume is “AUTO  
• In DRY mode, “AUTO  
”, air volume differs according to the room temperature.  
” is displayed and the air volume is LOW.  
• In heating operation, if the room temperature is not heated sufficiently with VOLUME “LOW ” opera-  
tion, select “MED. ” or “HIGH ” operation.  
Determine the set up temperature by pushing the “TEMP.  
” or “TEMP.  
” button.  
20  
Stop  
Push  
button.  
The operation lamp goes off, and the operation stops.  
AUTOMATIC OPERATION (Auto Changeover)  
When you set the air conditioner in  
mode or switch over from AUTO operation because of some settings  
change, it will automatically select either cooling, heating, or fan only operation depending on the indoor  
temperature.  
Start  
1
2
3
button  
Push this button to start the air conditioner.  
Mode select button (MODE)  
Select Auto.  
Temperature button  
Set the desired temperature.  
• In case of cooling, start the operation after approx. 1 minute.  
• In case of heating, the operation mode is selected in accordance with the room temperature and operation  
starts after approximately 3 to 5 minutes.  
• When you select the Auto mode, it is unnecessary to set the fan speed. The FAN speed display will show  
AUTO and the fan speed will be automatically controlled.  
• After the heating operation has stopped, FAN operation may continue for approx. 30 seconds.  
• When the room temperature reaches the set temperature and the outdoor unit stops, the supper low wind is  
discharged and the air volume decreases excessively. During defrost operation, the fan stops so that cool  
air is not discharged and “HEAT READY” is displayed.  
• If the Auto mode is uncomfortable, you can select the desired conditions manually.  
NOTE  
When restarting the operation after stop  
• When restarting the operation immediately after stop, the air conditioner does not operate for approx. 3  
minutes to protect the machine.  
Stop  
Push  
button.  
Push this button again to stop the air conditioner.  
21  
ADJUSTMENT OF WIND DIRECTIONd  
• When the air conditioner stops, the flap (adjustment plate of up/down wind direction) directs downward  
automatically.  
• When the heating operation is in READY states, the flap (adjustment plate of up/down wind direction) directs  
upward.The swinging starts after HEAT READY status cleared, SWING  
controller even if the heating operation is in READY status.  
is displayed on the remote  
How to set up the wind direction  
1
Push  
during operation.  
The wind direction changes for every push of the button.  
In HEAT operation  
Direct the flap (adjustment plate of up/down wind direction) downward. If directing  
at upward, hot air may not come to the foot.  
Initial setup  
In COOL/DRY operation  
Direct the flap (adjustment plate of up/down wind direction) upward. If directing it  
downward, the dew may from on the surface of the air discharge port and may  
drop down.  
Initial setup  
How to start swinging  
1
Push  
, set the flap (adjustment  
plate of up/down wind direction) direction  
to the lowest position, and then push  
again.  
UNIT  
SWING  
is displayed and the up/down wind  
SET  
CL  
direction is automatically selected.  
How to stop swinging  
1
Push SWING/WIND again while the flap is  
swinging.  
In FAN operation  
In all modes  
• The flap stops at a position when you push.  
After then, if pushing  
, the wind  
direction descends from the highest position.  
Series of  
operation  
• In COOL/DRY operation, the flap does not  
stop as it directs downward. If stopping the  
flap as it directs downward during swing  
operation, it stops after moving to the 3rd  
position from the highest position.  
Initial setup  
Display when stopping the swing  
Fan/Heat  
operation  
Cool/Dry  
operation  
22  
TIMER OPERATION  
A type of timer operation can be selected from the following three types.  
OFF timer  
:The operation stops when the time of timer has reached the set time.  
Repeat OFF timer : Every time, the operation stops after the set time has passed.  
ON timer  
:The operation starts when the time of timer has reached the set time.  
Timer operation  
1
UNIT  
2
SET  
CL  
3
4
1
2
PushTIMER SET button.  
• The timer display (type) changes for every  
push of the button.  
OFF  
OFF  
ON  
• SET DATA and  
display flashes.  
(OFF timer)  
(Repeat OFF timer)  
(ON timer)  
No display  
Push  
to select “SETTIME”.  
For every push of  
button, the set time increases in the unit of 0.5 hr (30 minutes).  
The maximum set time is 72.0 hr.  
For every push of  
button, the set time decreases in the unit of 0.5 hr (30 minutes).  
The minimum set time is 0.5 hr.  
3
Push SET button.  
• SET DATA display disappears and  
display goes on.  
(When ON timer is activated, time is displayed, and after time of the timer has been up, displays other  
than ON disappear.)  
Cancel of timer operation  
4
Push CL button.  
• TIMER display disappears.  
NOTICE  
• When the operation stops after the timer reached the preset time, the Repeat OFF timer resumes the  
operation by pushing  
the set time.  
button and stops the operation after the time of the timer has reached  
23  
HINTS FOR ECONOMICAL OPERATION  
Maintain room temperature at comfortable level  
Clean air filters  
The clogged air filter impairs the performance of the air conditioner.  
Clean them every 2 weeks.  
Never open doors and windows more often than necessary  
To keep cool or warm air in the room, never open doors and windows more often than necessary.  
Window curtains  
In cooling, close the curtains to avoid direct sunlight.  
In heating, close the curtains to keep the heat in.  
Get uniform circulation of room air  
Gee, chilly  
Control  
Adjust the air flow direction for the even  
circulation of room air.  
Clean, please.  
Please close  
Blows upward  
Air flow adjustment  
Cool and  
dry air  
Warm  
air  
Blows downward  
MAINTENANCE  
Cleaning of remote controller  
CAUTION  
• Use a dry cloth to wipe the remote controller.  
• A cloth dampened with cold water may be used on the indoor unit if  
it is very dirty.  
• Never use a damp cloth on the remote controller.  
• Do not use a chemically-treated duster for wiping or leave such  
materials on the unit for long. It may damage or fade the surface of  
the unit.  
• Do not use benzine, thinner, polishing powder, or similar solvents for  
cleaning. These may cause the plastic surface to crack or deform.  
24  
If you do not plan to use the unit for more than 1 month  
(1) Operate the fan for 3 to 4 hours to dry inside the unit  
Operate “FAN ONLY” mode with set temperature 30°C.  
(2) Stop the air conditioner and turn off the main power switch or the  
circuit breaker.  
Checks before operation  
(1) Check that the air filters are installed.  
(2) Check that the air outlet or inlet is not blocked.  
(3) Turn on the main power switch or the circuit breaker for the mains  
AC outlet to turn on the air conditioner.  
FAN ONLY operation or  
thermo.-off operation  
WARNING  
Make sure to ask the qualified maintenance professional for cleaning.  
Turn off the main power supply switch or breaker before the unit maintenance.  
Before maintenance, be sure to turn off the leakage breaker.  
Cleaning of air filter  
• If  
is displayed on the remote controller, maintain the air filter.  
• Clogging of the air filter reduce cooling/heating performance.  
Cleaning of panel and air filter  
Suction grille  
Preparation :  
1. Turn off the air conditioner by the remote controller.  
2. Open the suction air port.  
Button  
• Slide the button of the suction air port inward, and open the suction port  
slowly while holding it.  
Clean the panel and air filter with water:  
• Wipe down the panel and air filter with a sponge or towel moistened with  
a kitchen detergent. (Do not use any metallic brush for cleaning.)  
• Carefully rinse the panel and air filter to wash out the detergent.  
• After rinsing the panel and air filter with water, dry it in the shade.  
Suction grille  
3. Close the suction air port.  
• Close the suction air port, slide the button outward, and fix the  
suction port securely.  
Button  
CAUTION  
• Do not start the air conditioner while leaving the panel and air filter removed.  
• Push the filter reset button. (  
indication will be turn off.)  
Cleaning of Air Filters  
• Recommended cleaning intervals: Every two weeks.  
If the air filters are not cleaned, it not only reduce the cooling a  
performance of air conditioner but causes a failure in the air  
conditioner such as water falling in drops.  
Strap to  
prevent falling  
Preparation :  
1. Stop the operation by remote controller.  
2. Dismount the air filter.  
Push  
Air filter  
25  
Use a vacuum cleaner to remove dust from the filters or wash them with water.  
• After rinsing the air filters with water, dry them in the shade.  
• Set the air filter into the air conditioner.  
Cleaning of discharge flap  
The discharge flap can be removed to clean.  
1. Remove the discharge flap.  
• Holding the both ends of the discharge flap,  
remove the flap sagging the center downward.  
2. Cleaning with water  
2
Insert in the flap sagging  
down the center downward.  
• If the dirt is terrible, clean the flap by tepid  
water with neutral detergent or water.  
1
Insert  
3. Mount the discharge flap.  
• First push in one side of the flap, and  
then insert the other side sagging the  
center downward.  
Be careful to the direction of the flap when mounting.  
Mount the flap so that the side with the mark faces upward and the arrow direction of the mark directs.  
NOTE  
For Air conditioning system which is operated regularly, cleaning and maintenance of the indoor/outdoor  
units are strongly recommended.  
As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to  
be cleaned at least once every 3-MONTH. This cleaning and maintenance shall be carried out by a  
qualified person.  
Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leaking and  
even compressor failure.  
26  
AIR CONDITIONER OPERATIONS AND PERFORMANCE  
3 minutes protection function  
3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main  
power switch/circuit breaker is turned on for re-starting the air conditioner.  
Power failure  
Power failure during operation will stop the unit completely.  
To restart the operation, push the START/STOP button on the remote controller.  
• Lightning or a wireless car telephone operating nearby may cause the unit to malfunction. Turn off the main  
power switch or circuit breaker and then turn them on again. Push the START/STOP button on the remote  
controller to restart.  
Heating characteristics  
Preheating operation  
The air conditioner will not deliver warm air immediately after it is turned on. Warm air will start to flow out  
after approximately 5 minutes when the indoor heat exchanger warmed up.  
Warm air control (In heating operation)  
When the room temperature reaches the set temperature, the fan speed is automatically reduced to prevent  
to blow cold draft. At this time, the outdoor unit will stop.  
Defrosting operation  
If the outdoor unit is frosted during the heating operation, defrosting starts automatically (for approximately  
2 to 10 minutes) to maintain the heating capacity.  
• The fans in both indoor and outdoor units will stop during the defrosting operation.  
• During the defrosting operation, the defrosted water will be drained from the bottom plate of the outdoor  
unit.  
Heating capacity  
In the heating operation, the heat is absorbed from the outside and brought into the room. This way of heating  
is called heat pump system. When the outside temperature is too low, it is recommended to use another  
heating apparatus in combination with the air conditioner.  
Attention to snowfall and freeze on the outdoor unit  
• In snowy areas, the air inlet and air outlet of the outdoor unit are often covered with snow or frozen up.  
If snow or freeze on the outdoor unit is left as it is, it may cause machine failure or poor warming.  
• In cold areas, pay attention to the drain hose so that it perfectly drains water without water remaining inside  
for freeze prevention. If water freezes in the drain hose or inside the outdoor unit, it may cause machine  
failure or poor warming.  
Air conditioner operating conditions  
For proper performance, operate the air conditioner under the following temperature conditions:  
Cooling  
Outdoor temperature  
Room temperature  
: –5°C to 43°C  
operation  
: 21°C to 32°C (Dry valve temp.), 15°C to 24°C (Wet valve temp.)  
Room relative humidity – less than 80 %. If the air conditioner operates  
in excess of this figure, the surface of the air conditioner may cause dewing.  
CAUTION  
Dry operation Outdoor temperature  
Room temperature  
: 15°C to 43°C (Maximum suction air temp. 46°C)  
: 17°C to 32°C  
Heating  
Outdoor temperature  
Room temperature  
: –15°C to 15°C (Wet valve temp.)  
: 15°C to 28°C (Dry valve temp.)  
operation  
If air conditioner is used outside of the above conditions, safety protection may work.  
27  
RE-INSTALLATION  
DANGER  
Ask the dealer or an installation professional to re-install the air conditioner to a new place or  
move it to another place and to observe the following items.  
If the air conditioner is inappropriate installed by yourself, it may cause electric shock or fire.  
Do not install the air conditioner in the following places  
• Do not install the air conditioner in any place within 1 m from a TV, stereo, or radio set. If the unit is installed  
in such place, noise transmitted from the air conditioner affects the operation of these appliances.  
• Do not install the air conditioner near a high frequency appliance (sewing machine or massager for business  
use, etc.), otherwise the air conditioner may malfunction.  
• Do not install the air conditioner in a humid or oily place, or in a place where steam, soot, or corrosive gas is  
generated.  
• Do not install the air conditioner in a salty place such as seaside area.  
• Do not install the air conditioner in a place where a great deal of machine oil is used.  
• Do not install the air conditioner in a place where it is usually exposed to strong wind such as in seaside  
area or on the roof or upper floor of a building.  
• Do not install the air conditioner in a place where sulfureous gas generated such as in a spa.  
• Do not install the air conditioner in a vessel or mobile crane.  
Be careful with noise or vibrations  
• Do not install the air conditioner in a place where noise by outdoor unit or hot air from its air outlet annoys  
your neighbors.  
• Install the air conditioner on a solid and stable foundation so that it prevents transmission of resonating,  
operation noise and vibration.  
• If one indoor unit is operating, some sound may be audible  
from other indoor units that are not operating.  
TROUBLES AND CAUSES  
CAUTION  
If any of the following conditions occur, turn off the main power supply switch and immediately contact the  
dealer :  
• The operation lamps flash at short intervals (5 Hz) even though you have tried turning off the power  
supply and turning on again after 2 or 3 minutes.  
• Switch operation does not work properly.  
• The main power fuse often blows out, or the circuit breaker is often activated.  
• A foreign matter or water fall inside the air conditioner.  
• Any other unusual conditions are observed.  
28  
Before you ask for servicing or repairs, check the following points.  
Inoperative  
• The main power switch is turned off.  
• The circuit breaker is activated to cut off power supply.  
• The main power fuse has blown out.  
• Stoppage of electric current.  
Does not cool well or heat well  
• The air inlet and/or outlet of the outdoor unit is blocked.  
• Doors or windows are opened.  
• The fan speed is set to low.  
• The air conditioner is set in the DRY mode.  
• The set temperature is too high. (In cooling operation)  
• The set temperature is too low. (In heating operation)  
Indoor unit or outdoor unit makes a strange noise.  
• When the temperature suddenly changes, the indoor or outdoor unit  
occasionally makes a strange noise because of expansion/  
contraction of parts or change of refrigerant flow.  
The room air is smelly or a bad odor comes from the air conditioner.  
• Smells impregnated in the walls‚ carpets, furniture, clothing, or furs, come out.  
Outdoor unit is frosted in heating operation.  
Water drains from outdoor unit.  
• The outdoor unit is sometimes frosted in heating operation.  
In that case, the unit automatically performs defrosting  
(for 2 to 10 minutes) for increasing the heating efficiency.  
Calm  
• In defrosting operation, both the indoor and outdoor units stop air flow.  
• Hiss sound is heard when flow of the refrigerant is changed for defrosting.  
• Resultant water of automatic defrosting in heating operation drains from  
outdoor unit.  
Air flow changes though the FAN button is not set to the AUTO mode.  
• When the temperature of blown air drops in heating operation,  
the air conditioner automatically changes or stops air flow from the  
indoor unit not to make persons in the room feel chilly.  
• Air flow from the indoor unit is occasionally changed in the cooling operation.  
A white mist of chilled air or water is generated from the outdoor unit.  
• The indoor unit in cooling operation or the outdoor unit in defrosting  
operation occasionally steams.  
29  
30  
Accessory parts and Parts to be procured locally  
r Accessory parts  
Part name  
Q’ty Shape  
Usage  
Part name  
Q’ty  
Shape  
Usage  
Installation  
Manual  
This  
1
(Be sure to hand over to customers)  
manual  
Washer  
8
For hanging-down unit  
Heat insulating  
pipe  
For heat insulation of pipe  
connecting section  
2
Hose band  
1
1
1
1
For connecting drain pipe  
Installation  
pattern  
For confirmation of ceiling opening  
and main unit position  
1
——  
For adjusting core-out of drain  
pipe  
Flexible hose  
Heat insulator  
Installation  
gauge  
For positioning of ceiling position  
(united with installation pattern)  
2
4
For sealing of wire connecting port  
(Be sure to hand over to customers)  
Pattern fixing  
screw  
M5 x 16L For attach the installation pattern  
Owner’s  
Manual  
For heat insulation of drain  
connecting section  
Heat insulator  
1
<Separate sold parts>  
Part name  
Q’ty Shape  
Usage  
Standard wired  
remote controller  
1
r Parts to be procured locally  
Connecting pipe (Liquid side)  
Connecting cable  
(6.35mm (diam.), Nominal (diam.) 1/4” thick 0.8mm)  
RAV-SM560UT-E, RAV-SM560AT-E  
H07RN-F or 245IEC66 (1.5mm² or more)  
(9.52mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)  
RAV-SM800UT-E, RAV-SM800AT-E  
Thermal insulation for refrigerant pipe  
(10mm or more, thermal insulating foam polyethylene)  
Connecting pipe (Gas side)  
(12.7mm (diam.), Nominal (diam.) 1/2” thick 0.8mm)  
RAV-SM560UT-E, RAV-SM560AT-E  
Thermal insulation for drain pipe  
(10mm or more, foam polyethylene)  
(15.9mm (diam.), Nominal (diam.) 5/8” thick 1.0mm)  
RAV-SM800UT-E, RAV-SM800AT-E  
Drain pipe (Outer 26mm (diam.))  
Tapes  
Power supply cord  
2.5mm² (H07RN-F or 245IEC66) or 3.5mm² (AWG-12)  
Grounding cable (2.0mm (diam.) or more)  
31  
1
PRECAUTIONS FOR SAFETY  
• Ensure that all Local, National and International regulations are satisfied.  
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.  
• The precautions described below include the important items regarding safety. Observe them without fail.  
• After the installation work, perform a trial operation to check for any problem.  
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.  
• Turn off the main power supply switch (or breaker) before the unit maintenance.  
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.  
CAUTION  
New Refrigerant Air Conditioner Installation  
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT  
DESTROY OZONE LAYER.  
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure  
is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil  
has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or  
refrigerating oil does not enter the refrigerating cycle.  
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging  
port of the main unit and installation tools are charged from those for the conventional refrigerant.  
Accordingly the exclusive tools are required for the new refrigerant (R410A).  
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does  
not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance force  
and impurity in it.  
CAUTION  
To Disconnect the Appliance from Main Power Supply.  
This appliance must be connected to the main power supply by means of a switch with a contact separation of  
at least 3 mm.  
The installation fuse (25A D type  
) must be used for the power supply line of this conditioner.  
WARNINGS  
• Ask an authorized dealer or qualified installation professional to install/maintain the air  
conditioner.  
Inappropriate installation may result in water leakage, electric shock or fire.  
• Turn off the main power supply switch or breaker before attempting any electrical work.  
Make sure all power switches are off. Failure to do so may cause electric shock.  
• Connect the connecting cable correctly.  
If the connecting cable is connected in a wrong way, electric parts may be damaged.  
• When moving the air conditioner for the installation into another place, be very careful not  
to enter any gaseous maller other than the specified refrigerant into the refrigeration cycle.  
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes  
abnormally high and it resultingly causes pipe burst and injuries on persons.  
• Do not modify this unit by removing any of the safety guards or by by-passing any of the  
safety interlock switches.  
• Exposure of unit to water or other moisture before installation may cause a short-circuit of  
electrical parts.  
Do not store it in a wet basement or expose to rain or water.  
32  
1
PRECAUTIONS FOR SAFETY  
• After unpacking the unit, examine it carefully if there are possible damage.  
• Do not install in a place that might increase the vibration of the unit.  
• To avoid personal injury (with sharp edges), be careful when handling parts.  
• Perform installation work properly according to the Installation Manual.  
Inappropriate installation may result in water leakage, electric shock or fire.  
• When the air conditioner is installed in a small room, provide appropriate measures to  
ensure that the concentration of refrigerant leakage occur in the room does not exceed the  
critical level.  
• Install the air conditioner securely in a location where the base can sustain the weight  
adequately.  
• Perform the specified installation work to guard against an earthquake.  
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.  
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.  
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.  
• After the installation work, confirm that refrigerant gas does not leak.  
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might  
generate.  
• Electrical work must be performed by a qualified electrician in accordance with the  
Installation Manual. Make sure the air conditioner uses an exclusive power supply.  
An insufficient power supply capacity or inappropriate installation may cause fire.  
• Use the specified cables for wiring connect the terminals securely fix. To prevent external  
forces applied to the terminals from affecting the terminals.  
• Be sure to provide grounding.  
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.  
• Conform to the regulations of the local electric company when wiring the power supply.  
Inappropriate grounding may cause electric shock.  
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible  
gas.  
If a combustible gas leaks, and stays around the unit, a fire may occur.  
33  
2
SELECTION OF INSTALLATION PLACE  
WARNING  
• Install the air conditioner at enough strong place to withstand the weight of the unit.  
If the strength is not enough, the unit may fall down resulting in injury.  
• Install the air conditioner at a height 2.5m or more from the floor.  
If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous  
because you may contact with revolving fan or active electricity.  
CAUTION  
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible  
gas.  
If a combustible gas leaks and stays around the unit, a fire may occur.  
Upon approval of the customer, install the air conditioner in a place that satisfies the  
following conditions.  
Place where the unit can be installed horizontally.  
Place where a sufficient servicing space can be ensured for safety maintenance and check.  
Place where drained water will not cause any problem.  
Avoid installing in the following places.  
Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas  
(hot spring). (Should the unit be used in these places, special protective measures are needed.)  
Place exposed to oil, vapor, oil smoke or corrosive gas.  
Place where organic solvent is used nearby.  
Place close to a machine generating high frequency.  
Place where the discharged air blows directly into the window of the neighboring house. (For outdoor unit)  
Place where noise of the outdoor unit is easily transmitted.  
(When installing the air conditioner on the boundary with the neighbor, pay due attention to the level of noise.)  
Place with poor ventilation. (Before air ducting work, check whether value of air volume, static pressure and  
duct resistance are correct.)  
Installation space  
Secure the specified space in the figure for installation and servicing.  
1000 or more  
1000 or more  
34  
2
SELECTION OF INSTALLATION PLACE  
Selection of installation place  
Discharge direction  
In case of continued operation of the indoor unit under  
high-humidity conditions as described below, dew may  
condense and water may drop.  
As shown in the following figure, No. of  
discharge directions can be selected according  
to the shape of rooms and installation position.  
Especially, high-humidity atmosphere (dew point  
temperature : 23°C or more) may generate dew inside the  
ceiling.  
RAV-SM560UT-E to RAV-SM800UT-E  
1. Unit is installed inside the ceiling with slated roof.  
2. Unit is installed at a location using inside of the ceiling  
as fresh air take-in path.  
Refrigerant pipe side  
3. Kitchen  
If installing a unit at such place, put insulating material  
(glass wool, etc.) additionally on all the positions of the  
indoor unit which come to contact with high-humidity  
atmosphere.  
As shown in the following figure direction are  
not acceptable.  
RAV-SM560UT-E to RAV-SM800UT-E  
Advice  
Set a check service opening panel at right side of the unit  
(size: 450 x 450mm or more) for piping, maintenance, and  
servicing.  
To change discharge direction, use a shielding  
plate.  
When attaching a shielding plate, remove the  
ceiling panel and insert the shielding plate into  
the discharge port as shown in the figure below.  
Ceiling height  
Model RAV-  
Possible installe ceiling height  
SM560UT-E, SM800UT-E  
Up to 3.8m  
When the height of the ceiling exceeds the distance of the  
item Standard/4-way in Table below, the hot air is difficult to  
reach the floor. Therefore, it is necessary to change the  
setup value of the high ceiling switch or discharge direction.  
Shielding plate  
(Prepared locally)  
REQUIREMENT  
When using the air conditioner with 2-way discharge  
system with the standard setting (at a shipment), it  
may stop abnormally in heating. Therefore, change  
the setting switch according to the number of  
discharge direction and the ceiling height.  
WARNING  
Install the air conditioner certainly to sufficiently  
withstand the weight.  
When using the air conditioner with 2-way/3-way  
discharge system, a strong wind blows directly if  
the ceiling height is lower than the standard.  
Therefore, change the setting switch according to  
height of the ceiling.  
If the strength is insufficient, the unit may fall  
down resulting in human injury.  
Perform a specified installation work to guard  
against an earthquake.  
When using the high ceiling (1) or (2) with 4-way  
discharge system, the draft is apt to be felt due to  
drop of the discharge temperature.  
An incomplete installation can cause accidents  
by the units falling and dropping.  
Height list of ceiling possible to be installed  
(Unit : m)  
Model  
RAV-SM560UT-E  
RAV-SM800UT-E  
High ceiling setup  
Set data  
No. of discharge direction 4-way  
3-way  
3.2  
2-way  
4-way  
3-way  
3.3  
2-way  
Standard (at shipment)  
High ceiling (1)  
2.8  
3.2  
3.5  
3.5  
3.8  
3.0  
3.3  
3.6  
3.6  
3.8  
0000  
3.5  
3.5  
0001  
High ceiling (2)  
3.8  
3.8  
0003  
35  
External view  
REQUIREMENT  
Strictly comply with the following rules to prevent damage of the indoor units and human injury.  
• Do not put a heavy article on the indoor unit. (Even units are packaged)  
• Carry in the indoor unit as it is packaged if possible. If carrying in the indoor unit unpacked by necessity, be  
sure to use buffering cloth, etc. to not damage the unit.  
• To move the indoor unit, hold the hooking metals (4 positions) only.  
Do not apply force to the other parts (refrigerant pipe, drain pan, foamed parts, or resin parts, etc.).  
• Carry the package by two or more persons, and do not bundle it with PP band at positions other than  
specified.  
Ceiling bottom surface  
173  
113  
45  
Ø162  
80  
Ø162  
Knockout square  
hole for divide duct  
For Ø150  
Ceiling bottom surface  
240  
Refrigerant pipe  
connecting port  
105  
840 Unit external dimension  
434.5  
105  
(2 positions)  
97  
120  
A
Take-in port  
of pipes  
Electric parts box  
Refrigerant pipe  
connecting port  
B
105  
Ceiling  
bottom  
surface  
130  
210  
Knockout square hole  
for divide duct  
For Ø150  
381.6  
723 Hanging bolt pitch  
950 Panel external dimension  
860 to 910 Ceiling opening dimension  
Hanging bolt  
480  
227  
M10 or Ø3/8  
(To be procured locally)  
Drain pipe connecting port  
A
B
RAV-SM560UT-E Ø6.4 Ø12.7  
RAV-SM800UT-E Ø9.5 Ø15.9  
Ceiling bottom  
surface  
Ceiling panel (sold separately)  
Considering pipe/wire connecting work inside the ceiling after the indoor unit has been hanged, select an installation  
place and determine piping direction.  
• If the ceiling has already been set before hanging the main unit, prepare refrigerant pipe, drain pipe, indoor  
connecting wire, remote controller cord, etc. up to the place where pipe and wire can be connected.  
• Check the size of the indoor unit, and match the indoor unit size, with ceiling opening size and that position using  
the attached installation pattern.  
(Attach the pattern to the lower side of indoor unit with attached four screws M5 x 16L.)  
36  
2
SELECTION OF INSTALLATION PLACE  
Opening a ceiling and installation of hanging bolts  
<Treatment of ceiling>  
The ceiling differs according to structure of building. For details, consult your constructor or interior finish contractor.  
In the process after the ceiling board has been removed, it is important to reinforce ceiling foundation (frame) and to  
keep horizontal level of installed ceiling correctly in order to prevent vibration of ceiling board.  
(1) Cut and remove the ceiling foundation.  
(2) Reinforce the cut surface of ceiling foundation, and add ceiling foundation for fixing the end of ceiling board.  
<Installation of hanging bolt>  
Use M10 hanging bolts (4 pcs, to be local procure). Matching to the existing structure, set pitch according to size in  
the unit external view as shown below.  
New concrete slab  
Steel flame structure  
Existing concrete slab  
Install the bolts with insert brackets or anchor  
bolts.  
Use existing angles or install new  
support angles.  
Use a hole-in anchors, hole-in  
plugs, or a hole-in bolts.  
Hanging bolt  
Rubber  
Anchor bolt  
(Pipe hanging  
(Blade type  
bracket)  
(Slide type  
bracket)  
anchor bolt)  
Hanging bolt  
Support angle  
(1)  
Installation of ceiling opening and hanging bolt  
Hanging bolt  
(W3/8 or M10)  
M10 flat washer  
(Accessory)  
Adjust nut position (lower side) so that clearance between the  
attached washer (lower side) and ceiling board is 88mm.  
Nut  
(2)  
(W3/8 or M10)  
M10 flat washer  
(Accessory)  
Nut  
(W3/8 or M10)  
Hanging bolt  
Nut (Upper side)  
Hanging bolt  
Washer  
(1) Required those other than M10 flat washer at site.  
(Upper side)  
(2) To prevent falling-off of bolt (safety), be sure to  
set it just under the hanging bracket as shown  
in the figure.  
(Hanging bracket  
main unit)  
Level  
Washer  
(Lower side)  
Nuts (Lower side)  
Level vial (Horizontal: within 5mm)  
Ceiling boards  
Hanging bolt  
Indoor unit  
Hanging bracket  
Hanging  
metal  
2) 12 to 17mm  
1) 20 to 30mm  
Hang up the main unit by hanging the nut of hanging bolt to  
Ceiling board  
T groove of hanging bracket of the main unit.  
Installation  
gauge  
Using the level vial, etc., set the horizontal level of the main  
unit within 5mm.  
Using the installation gauge, check and adjust the positional  
relation between the main unit and ceiling opening hole, and  
hanging-up height of the main unit. (Direction to be used is  
indicated on the installation gauge.)  
1) Check lower side of the indoor unit locates at position (12  
to 17) mm higher than the lower surface of the ceiling  
board. (4 corners)  
+5  
0  
1) 12 mm  
Indoor unit  
Ceiling  
board  
2) Check clearance between side of the indoor unit and the  
ceiling board is 20 to 30mm. (Common to 4 corners)  
Installation  
gauge  
2) 20 to 30mm  
37  
REQUIREMENT  
Installation of ceiling panel  
(Sold separately)  
Before installation of the indoor unit, be sure to  
remove the cushion for transportation between the  
fan and the bell mouth. Running the unit without  
removing the cushion may damage the fan motor.  
Install the ceiling panel according to Installation  
Manual attached with it after piping/wiring work has  
completed.  
Check that installation of indoor unit and ceiling  
opening part is correct, and then install it.  
REQUIREMENT  
Joint the connecting sections of ceiling panel,  
ceiling surface, ceiling panel and indoor unit  
closely.  
Any gap between them will cause air leakage and  
this generate condensation or water leakage.  
Installation of ceiling opening and  
hanging bolt  
Be sure to remove the cushion for transportation  
between the fan and the bell mouth.  
For installation of the wired remote controller, follow  
the Installation Manual attached with the remote  
controller.  
Pull out the remote controller cord together with the  
refrigerant pipe or drain pipe.  
Be sure to pass the remote controller cord through  
upper side of the refrigerant pipe and drain pipe.  
38  
3
DRAIN PIPING WORK  
Piping/Heat insulating material  
CAUTION  
Require the following materials for piping and heat  
insulating at site.  
• Following the Installation Manual,  
perform the drain piping work so that  
water is properly drained, and apply a  
heat insulation so as not to cause a dew.  
Inappropriate piping work may result in  
water leakage in the room and wet of  
furniture.  
Hard vinyl chloride pipe VP25  
(Outer dia. : Ø32mm)  
Piping  
Foam polyethylene :  
Heat insulator  
Thickness 10mm or more  
REQUIREMENT  
1.5m to 2m  
Support  
bracket  
Be sure to perform heat insulation of the drain pipes of the indoor unit.  
Never forget to perform heat insulation of the connecting part with the indoor  
unit. An incomplete heat insulation causes dewing.  
1/100 or more  
downward  
Heat  
insulator  
Set the drain pipe with downward slope (1/100 or more), and do not make  
swelling or trap on the piping. It may cause an abnormal sound.  
Arched  
shape  
For length of the traversing drain pipe, restrict to 20m or less.  
In case of a long pipe, provide support brackets with interval of  
1.5 to 2m in order to prevent waving.  
As long as possible (10cm)  
Trap  
VP25  
VP25  
VP25  
Extended  
ventilating pipe  
Set the collective piping as shown in  
the right figure.  
VP30 or more  
Downward slope  
1/100 or more  
Be sure not to apply force to the  
connecting part of the drain pipe.  
The hard vinyl-chloride pipe cannot be directly connected to the drain pipe connecting port of the indoor unit.  
For connection with the drain pipe connecting port, be sure to use/fix the attached flexible hose with the hose  
band, otherwise a damage or water leak is caused on the drain pipe connecting port.  
VP25 vinyl chloride pipe  
Align the attached hose band to the  
end of hose, set the tightening  
position upward, and then tighten it.  
Attached hose band  
(To be local procure)  
Drain pipe  
connecting port  
(Transparent)  
Drain pipe connecting  
port (Hard socket)  
Attached flexible hose  
Flexible hose VP25 vinyl chloride pipe  
(Accessory)  
(To be local procure)  
Socket for VP25  
(To be local procure)  
Soft socket  
Socket for VP25 vinyl chloride pipe  
(To be local procure)  
Hard socket  
Adhesive inhibited :  
Use the attached flexible hose and hose band for connecting the drain hose to the clear drain socket.  
If applying the adhesive, socket will be damaged and cause water leakage.  
Flexible hose  
Use the attached flexible hose to adjust core discrepancy  
of the hard vinyl chloride pipe or to adjust the angle.  
Do not use the flexible hose as stretched, or do not  
deform it more extent than that in the following figure.  
Riser (Trap)  
max  
45˚  
Be sure to fix the soft end of the flexible hose with the  
attached hose band.  
max  
45˚  
Use the flexible hose on a horizontal level.  
90˚ Bend  
39  
Connection procedure  
Check the draining  
Connect a socket and a hard vinyl chloride pipe.  
In the test run, check that water drain is properly  
performed and water does not leak from the  
connecting part of the pipes.  
Using adhesive agent for vinyl chloride pipe, connect  
the drain pipes certainly so that water does not leak.  
Be sure to check draining also when installed in  
heating period.  
It takes approx. 10 hours to dry and harden the  
adhesive agent. During this period, do not apply  
force to the connecting part with the drain pipe.  
Using a pitcher or hose, pour water (1500 to 2000cc)  
into the discharge port before installation of the ceiling  
panel.  
Perform heat insulating.  
As shown in the figure, cover the flexible hose and  
hose band with the attached heat insulator up to the  
bottom of the indoor unit without gap.  
Pour water gradually so that water does not spread on  
the motor of the drain pump.  
Heat  
exchanger  
Drain pan  
Hose band  
Flexible hose  
Heat insulator to be  
Attached heat insulator  
procured locally  
Hard vinyl chloride pipe  
After the electric work has finished, pour water  
during COOL mode operation.  
If the electric work has not yet finished, pull out the  
float switch connector (CN34 : Red) from the electric  
parts box, and check draining by plugging the single  
phase 220/230/240V power to the terminal blocks 1  
and 2.  
Drain up  
If doing so, the drain pump motor operates.  
When a downward grading cannot be secured on the  
drain pipe, drain-up up to 640mm is possible.  
Test water drain while checking the operation sound  
of the drain pump motor.  
(If the operation sound changes from continuous  
sound to intermittent sound, water is normally  
drained.)  
Set downward grading immediately after raising up  
vertically.  
After the check, the drain pump motor runs,  
connecting the float switch connector.  
(In case of check by pulling out the float switch  
connector, be sure to return the connector to the  
original position.)  
360mm  
or less  
Single phase 220/230/240V  
1
2
White  
Indoor unit  
CN34  
(RED)  
Red  
Underneath of ceiling  
Black  
Pull out connector CN34 (Red) from P.C. board.  
Black  
40  
4
REFRIGERANT PIPING  
• Flaring dia meter size : A (Unit : mm)  
Refrigerant Piping  
+0  
A
-
0.4  
1. If the outdoor units are to be mounted on a wall,  
make sure that the supporting platform is  
sufficiently strong. The platform should be  
designed and manufactured to maintain its strength  
over a long period of time, and sufficient  
consideration should be given to ensuring that the  
outdoor unit will not fall.  
Outer diam. of copper pipe  
R410A  
9.1  
R22  
9.0  
6.35  
9.52  
12.7  
15.9  
13.2  
16.6  
19.7  
13.0  
16.2  
19.2  
2. Use copper pipe with 0.8 mm or more thickness.  
In case of flaring for R410A with the conventional  
3. Flare nut and flare works are also different from  
those of the conventional refrigerant.  
*
flare tool, pull it out approx.  
A
0.5 mm more than that for R22 to  
adjust to the specified flare size.  
The copper pipe gauge is useful  
for adjusting projection margin size.  
Take out the flare nut attached to the main unit of  
the air conditioner, and use it.  
CAUTION  
IMPORTANT 4 POINTS FOR PIPING WORK  
1. Remove dust and moisture from the inside of  
the connecting pipes.  
Tightening connection  
2. Tight connection (between pipes and unit)  
CAUTION  
3. Evacuate the air in the connecting pipes using  
VACUUM PUMP.  
Do not apply excessive torque. Otherwise, the  
nut may crack depending on the conditions.  
4. Check the gas leakage. (Connected points)  
(Unit : Nm)  
Outer diam. of copper pipe  
Tightening torque  
Permissible Piping Length and Heat  
6.35 mm (diam.)  
9.52 mm (diam.)  
12.7 mm (diam.)  
15.9 mm (diam.)  
14 to 18 (1.4 to 1.8 kgfm)  
33 to 42 (3.3 to 4.2 kgfm)  
50 to 62 (5.0 to 6.2 kgfm)  
63 to 77 (6.3 to 7.7 kgfm)  
The maximum piping length from the outdoor to indoor unit  
30 m (Chargeless 20m)  
(RAV-SM560AT-E)  
50 m (Chargeless 20m)  
(RAV-SM800AT-E)  
The maximum height difference outdoor/indoor unit  
Outdoor unit is above  
Outdoor unit is below  
30m  
15m  
• Tightening torque of flare pipe connections  
Pressure of R410A is higher than that of R22.  
(Approx. 1.6 times) Therefore, using a torque  
wrench, tighten the flare pipe connecting sections  
Flaring  
Insert a flare nut into the pipe, and flare the pipe.  
Flare at  
which connect the indoor  
indoor  
As the flaring sizes of R410A differ from those of  
refrigerant R22, the flare tools newly manufactured for  
R410A are recommended.  
However, the conventional tools  
can be used by adjusting  
projection margin  
and outdoor units of the  
specified tightening torque.  
Incorrect connections may  
cause not only a gas  
unit side  
B
leak, but also a trouble  
of the refrigeration cycle.  
of the copper pipe.  
Flare at  
outdoor  
unit side  
• Projection margin in flaring : B (Unit : mm)  
Rigid (Clutch type)  
Align the centers of the connecting pipes and tighten  
the flare nut as far as possible with your fingers. Then  
tighten the nut with a spanner and torque wrench as  
shown in the figure.  
R410A tool used  
R410A R22  
Conventional tool used  
R410A R22  
Outer diam. of  
copper pipe  
6.35 to 9.52 0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0  
Half union  
Flare nut  
Imperial (Wing nut type)  
Externally  
threaded side  
Internally  
threaded side  
Outer diam. of copper pipe  
6.35 or 9.52  
R410A  
R22  
1.5 to 2.0  
2.0 to 2.5  
1.0 to 1.5  
1.5 to 2.0  
12.7 or 15.9  
Use a wrench to secure.  
Use a torque wrench to tighten.  
41  
5
EVACUATING  
REQUIREMENT  
AIR PURGE  
Evacuate the air in the connecting pipes and in the  
indoor unit using vacuum pump.  
Charging an excessive or too little amount of  
refrigerant causes a trouble of the compressor.  
Be sure to charge the refrigerant of specified  
amount.  
Do not use the refrigerant in the outdoor unit.  
For details, see the manual of vacuum pump.  
A personnel who charged the refrigerant should  
write down the pipe length and the added  
refrigerant amount in the nameplate attached to  
the service panel of the outdoor unit. It is  
necessary to troubleshoot the compressor and  
refrigeration cycle malfunction.  
Use a vacuum pump  
Be sure to use a vacuum pump with counter-flow  
prevention function so that inside oil of the pump does  
not flow backward into pipes of the air conditioner  
when the pump stops.  
1. Connect the charge hose from the manifold valve to  
the service port of the gas side packed valve.  
Open the valve fully  
2. Connect the charge hose to the port of vacuum  
pump.  
Open the valve of the outdoor unit fully. A 4mm-  
hexagonal wrench is required for opening the valve.  
3. Open fully the low pressure side handle of the  
gauge manifold valve.  
Gas leak check  
4. Operate the vacuum pump to start evacuating.  
Check with a leak detector or soap water whether gas  
leaks or not, from the pipe connecting section or cap  
of the valve.  
Perform evacuating for about 35 minutes if the  
piping length is 30 meters total for model SM560  
and 50 meters for model SM800  
(assuming a pump capacity of 27 liters per minute.)  
Then confirm that the compound pressure gauge  
reading is 101 kPa ( 76 cmHg).  
REQUIREMENT  
Use a leak detector manufactured exclusively for  
HFC refrigerant (R410A, R134a, etc.).  
5. Close the low pressure side valve handle of gauge  
manifold.  
6. Open fully the valve stem of the packed valves  
(both sides of Gas and Liquid).  
Thermal insulation process  
7. Remove the charging hose from the service port.  
8. Securely tighten the caps on the packed valves.  
Apply thermal insulation for the pipes separately at  
liquid side and gas side.  
For the thermal insulation to the pipes at gas side, be  
sure to use the material with heat-resisting  
temperature 120°C or higher.  
REQUIREMENT  
Using the attached thermal insulation material, apply  
the thermal insulation to the pipe connecting section of  
the indoor unit securely without gap.  
For the tools such as charge hose, etc., use those  
manufactured exclusively for R410A.  
Refrigerant amount to be added  
REQUIREMENT  
For addition of the refrigerant, add refrigerant R410A”  
referring to the attached Installation Manual.  
Apply the thermal insulation to the pipe connecting  
section of the indoor unit securely up to the root  
without exposure of the pipe. (The pipe exposed to  
the outside causes water leak.)  
Be sure to use a scale to charge the refrigerant of  
specified amount.  
42  
5
EVACUATING  
Packed valve handling precautions  
Compound  
Pressure gauge  
pressure gauge  
Open the valve stem all the way out ; do not try to  
open it beyond the stopper.  
101kPa  
(76cmHg)  
Manifold valve  
Securely tighten the valve stem cap at the torque as  
follows:  
Handle Lo  
Handle Hi  
(Keep fully closed)  
Charge hose  
Gas side (15.9 mm (diam.)  
)
63 to 77 Nm (6.3 to 7.7 kgfm)  
Charge hose  
Vacuum pump  
adapter for  
counter-flow  
prevention  
Gas side (12.7 mm (diam.)  
)
50 to 62 Nm (5.0 to 6.2 kgfm)  
Packed valve  
at liquid side  
Gas side (9.52 mm (diam.)) 33 to 42 Nm (3.3 to 4.2 kgfm)  
Liquid side (6.35 mm (diam.)) 14 to 18 Nm (1.4 to 1.8 kgfm)  
Service port  
14 to 18 Nm (1.4 to 1.8 kgfm)  
Vacuum  
pump  
Hexagonal wrench is required.  
Service port  
(Valve core (Setting pin))  
Packed valve at gas side  
<For RAV-SM800AT-E model>  
As shown in the figure, be sure to use a double  
spanner to loosen or tighten the flare nut of the valve  
at gas side. If using a single spanner, the nut cannot  
be tightened with necessary tightening torque.  
On the contrary, use a single spanner to loosen or  
tighten the flare nut of the valve at liquid side.  
Cover  
Cap  
Piping valve  
Loosened  
Tightened  
Flare nut  
SM800 type valve at gas side  
Cover  
Never put the spanner or  
torque wrench, etc. on  
the cover.  
The valve may be broken.  
43  
6
ELECTRICAL WORK  
WARNING  
1. Using the specified cables, ensure to connect the wires, and fix wires securely so that the  
external tension to the cables do not affect the connecting part of the terminals.  
Incomplete connection or fixation may cause a fire, etc.  
2. Be sure to connect earth wire. (Grounding work)  
Do not connect the earth wire to gas pipe, city water pipe, lightning rod, or the earth wire of telephone.  
Incomplete grounding causes an electric shock.  
3. For electric work, strictly follow the Local Regulation in each country and the Installation  
Manual, and use an exclusive circuit.  
Capacity shortage of power circuit or incomplete installation may cause an electric shock or a fire.  
CAUTIONS  
This indoor unit has no power cord.  
If incorrect/incomplete wiring is carried out, it will cause an electrical fire or smoke.  
Be sure to install an earth leakage breaker that is not tripped by shock waves.  
If an earth leakage breaker is not installed, an electric shock may be caused.  
Be sure to use the cord clamps attached to the product.  
Do not damage or scratch the conductive core and inner insulator of power and inter-connecting cables when  
peeling them.  
Be sure to comply with local regulations on running the wire from outdoor unit to indoor unit (size of wire and  
wiring method etc.)  
Use the power cord and Inter-connecting cable of specified thickness, type, and protective devices required.  
REQUIREMENT  
For power supply wiring, strictly conform to the Local Regulation in each country.  
For wiring of power supply of the outdoor units, follow the Installation Manual of each outdoor unit.  
Never connect 220/230/240V power to the terminal blocks (A, B, etc.) for control wiring.  
(Otherwise, the system will fail.)  
Perform the electric wiring so that it does not come to contact with the high-temperature part of the pipe.  
The coating may melt resulting in an accident.  
After connecting cables to the terminal blocks, provide a trap and fix cables with the cable clamp.  
Run the refrigerant piping line and control wiring line in the same line.  
Do not turn on the power of the indoor unit until vacuuming of the refrigerant pipes completes.  
Remote controller wiring  
2-core non polarity cable is used for the remote controller wiring.  
How to wire  
1. Connect the connecting cable to the terminal as identified with their respective numbers on the terminal block of  
indoor and outdoor unit. H07 RN-F or 245 IEC 66 (1.5 mm2 or more)  
2. Insulate the unsheathed redundant cords (conductors) with electrical insulation tape.  
Process them so that they do not touch any electrical or metal parts.  
3. For inter-unit wiring, do not use a wire jointed to another on the way.  
44  
6
ELECTRICAL WORK  
Cable connection  
REQUIREMENT  
Be sure to connect the cables matching the terminal numbers. Incorrect connection causes a trouble.  
Be sure to pass the cables through the bushing of cabling connection port of the indoor unit.  
Keep a margin (Approx. 100mm) on a cable to hang down the electric parts box at servicing, etc.  
The low-voltage circuit is provided for the remote controller. (Do not connect the high-voltage circuit)  
Remove the cover of the electric parts box by taking off the mounting screws (3 positions) and pushing the  
hooking section. (The cover of the electric parts box remains hanged to the hinge.)  
Connect the indoor/outdoor connection cables and REMOCON cable to the terminal block of the electric parts  
box. (Do not apply tension to the connecting section of the terminal block.)  
Tighten the screws of the terminal block, and fix the cables with cord clamp attached to the electric parts box.  
(Do not apply tension to the connecting section of the terminal block.)  
Using the attached thermal insulation material, seal the pipe connecting port. Otherwise, dewing may be caused.  
Mount the cover of the electric parts box without pinching cables.  
(Mount the cover after cabling on the ceiling panel.)  
Cabling  
connecting  
port  
P.C. board  
Hooking section  
Electric parts box  
Louver connector (CN33: White)  
Hinge  
Cover of electric parts box  
Screws at 3 positions  
Power supply Remote controller  
terminal block  
terminal block  
1 2 3  
A B  
<Thermal insulation to cabling connecting port>  
A B C  
Adhered surface  
Notched section  
Cord clamp  
Cord clamp  
Cabling on the ceiling panel  
According to the Installation Manual of the ceiling panel, connect the connector (5P: White) of the ceiling panel to the  
connector (CN33: White) on P.C. board of the electric parts box.  
45  
Cabling  
Cabling diagram  
1. Remove a screw and then remove cover of the  
electric parts box.  
Terminal block  
for remote controller  
cabling of indoor unit  
Approx. 200mm  
2. Strip wire ends (10 mm).  
W : White  
B : Black  
3. Match wire colors with terminal numbers on indoor  
and outdoor unitsterminal blocks and firmly screw  
wires to the corresponding terminals.  
A
B
W
B
Remote  
controller unit  
or sensor part  
4. Connect the ground wires to the corresponding  
terminals.  
Remote controller cable  
(Local procure)  
Remote controller unit or  
cable from sensor part  
Connecting  
part  
5. Fix the cable with cord clamp.  
6. Fix cover of the parts box and the terminal block  
surely with the fixing screws.  
Remote controller cabling  
Make a loop on the cable for margin of the length  
so that the electric parts box can be taken out  
during servicing.  
Cable from remote  
controller unit  
Wire joint  
Remote controller  
Remote controller  
cable  
10  
1
2
3
10  
A
B
2
Indoor side  
1
3
3
40  
30  
Indoor/Outdoor  
connecting cable  
1
L
2
Earth line  
Outdoor side  
N
Connecting  
cable  
(Single phase 220/230/240V)  
For details of cabling/installation of the remote  
controller, refer to the Installation Manual attached to  
in the remote controller.  
Remote Controller Cabling  
Strip off approx. 14mm the cable to be connected.  
Non polarity, 2 core cable is used for cabling of the  
remote controller.  
Twist cable of the remote controller to be connected  
with cable of the remote controller unit (or sensor),  
and press-fit them with a wire joint.  
Wire joints (White: 2 pieces) are included in the  
attachments to the remote controller (sold  
separately) or the wireless remote controller kit (sold  
separately).  
46  
7
TEST RUN  
Before test run  
Before turning on the power supply, carry out the following procedure.  
1) Using 500V-megger, check 1Mor more exists between the terminal block 1 to 3 and the earth.  
If 1Mor less is detected, do not run the unit. Do not apply to the remote controller circuit.  
2) Check the valve of the outdoor unit being opened fully.  
To protect the compressor at activation time, leave power-ON for 12 hours or more be for operating.  
How to execute a test run  
Using the remote controller, operate the unit as usual.  
For the procedure of the operation, refer to the attached Owners Manual.  
A forced test run can be executed in the following procedure if the operation stops by thermo.-OFF.  
In order to prevent a serial operation, the forced test run is released after 60 minutes have passed and returns to the  
usual operation.  
NOTE  
Do not use the forced test run for cases other  
than the test run because it applies an  
excessive load to the devices.  
2, 4  
3
UNIT  
1, 5  
In case of wired remote controller  
SET CL  
Procedure  
Description  
Keep  
button pushed for 4 seconds or more. [TEST] is  
displayed on the display part and the selection of mode in the test  
mode is permitted.  
1
TEST  
Push  
button.  
2
3
4
5
Using  
button, select the operation mode, [COOL] or [HEAT].  
Do not run the air conditioner in a mode other than [COOL] or  
[HEAT].  
The temperature controlling function does not work during test run.  
The detection of error is performed as usual.  
After the test run, push  
button to stop a test run.  
(Display part is same as procedure 1.  
Push  
check button to cancel (release from) the test run mode.  
([TEST] disappears on the display and the status returns to a  
normal.)  
47  
8
TROUBLESHOOTING  
Confirmation and check  
CODE No.  
When a trouble occurred in the air conditioner, the  
check code and the indoor unit No. appear on the  
display part of the remote controller.  
UNIT No.  
R.C. No.  
The check code is only displayed during the operation.  
If the display disappears, operate the air conditioner  
according to the following Confirmation of error  
historyfor confirmation.  
Check code  
Indoor unit No. in which  
an error occurred  
Confirmation of error history  
When a trouble occurred on the air conditioner, the  
trouble history can be confirmed with the following  
procedure. (The trouble history is stored in memory up  
to 4 troubles.)  
The history can be confirmed from both operating  
status and stop status.  
UNIT  
3
2
SET CL  
1
Procedure  
Description  
When pushing [SET] and  
buttons at the same time for 4  
seconds or more, the following display appears.  
CODE No.  
If [Service check] is displayed, the mode enters in the trouble history  
mode.  
UNIT No.  
1
R.C. No.  
[01 : Order of trouble history] is displayed in CODE No. window.  
[Check code] is displayed in CHECK window.  
[Indoor unit address in which an error occurred] is displayed in  
UNIT No.  
Every pushing of [  
displayed in order.  
,
] button used to set temperature, the trouble history stored in memory is  
The numbers in CODE No. indicate CODE No. [01] (latest) [04] (oldest).  
2
3
REQUIREMENT  
Do not push  
button because all the trouble history of the indoor unit will be deleted.  
CL  
After confirmation, push  
button to return to the usual display.  
1. Check the troubles according to the above procedure.  
2. Ask an authorized dealer or qualified service (maintenance) professional to repair or maintain the air conditioner.  
3. More details of the service code are explained in Service Manual.  
48  
ACCESSORIES  
Remote controller  
Screws (two pcs.)  
PRECAUTIONS FOR SAFETY  
WARNING  
WARNINGS ABOUT INSTALLATION  
• Make sure to ask the qualified installation professional in electric work to install  
the air conditioner.  
If the air conditioner is inappropriate installed by yourself, it may cause water  
leak, electric shock, fire, and so on.  
• Ground the air conditioner without fail.  
Do not connect the ground wire to gas pipe, water pipe, lightning rod or ground  
wire of telephone. If the air conditioner is imperfectly grounded, it may cause  
electric shock.  
CAUTION  
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY  
This appliance must be connected to the mains by means of a switch with a  
contact separation of at least 3 mm.  
The installation fuse (25A D type  
supply line of this conditioner.  
) must be used for the power  
WARNINGS ABOUT OPERATION  
• Avoid cooling the room too strong or exposing the human body to cool breeze  
for a long time as it is bad for the health.  
• When you notice something abnormal with the air conditioner (smells like  
something scorching, poor cooling, etc.), immediately turn off the main switch,  
the circuit breaker, from the mains to stop the air conditioner, and contact the  
dealer.  
If the air conditioner is continuously operated with something abnormal, it may  
cause machine failure, electric shock, fire, and so on.  
WARNINGS ABOUT MOVEMENT AND REPAIR  
• Do not move or repair any unit by yourself.  
Since there is high voltage inside the unit, you may get electric shock when  
removing the cover and main unit.  
• Whenever the air conditioner needs repair, make sure to ask the dealer to do it.  
If it is repaired imperfectly, it may cause electric shock or fire.  
• When moving the air conditioner for re-installing at another place, ask the  
dealer to do it. If it is imperfectly installed, it may cause electric shock or fire.  
49  
CAUTION  
CAUTIONS ABOUT INSTALLATION  
• Certainly lay the drain hose for perfect draining.  
Bad drainage may cause flooding in the house and getting furniture  
wet.  
• Make sure to connect the air conditioner to an exclusive AC outlet of  
the rated voltage, otherwise the unit may break down or cause a fire.  
• Do not install the unit in a place where inflammable gas may leak.  
If inflammable gas accumulates around the unit, it may cause a fire.  
CAUTIONS ABOUT OPERATION  
• Carefully read this manual before starting the air conditioner. There  
are many important things to keep in mind for daily operation.  
• Do not use this air conditioner for special purposes such as preserv-  
ing food, precision instruments, art objects, breeding animals,  
growing potted plants, etc.  
• Avoid exposing potted plants and animals to the wind of the air  
conditioner, since it badly affects the health and growth of them.  
• When the air conditioner is operated with a combustion appliance in  
the same place, be careful of ventilation to let fresh air enter the  
room.  
Poor ventilation causes oxygen shortage.  
• When the air conditioner is used in a closed room, be careful of  
sufficient ventilation of the room. Poor ventilation causes oxygen  
shortage.  
• Do not touch any switches with wet finger, otherwise you may get an  
electric shock.  
• Do not place any combustion appliance in a place where it is directly  
exposed to the wind of air conditioner, otherwise it may cause  
imperfect combustion.  
• If the air conditioner won’t be used for a considerably long time, turn  
off the main switch or the circuit breaker, for safety. Disconnect from  
the power supply prevents the unit from lightning and power supply  
surge.  
• Check the concrete blocks, etc. of the base of the outdoor unit  
occasionally.  
If the base is left damaged or deteriorated, the unit may topple over  
and inflict an injury to a person as the worst case.  
• When cleaning the unit, make sure to turn off the main switch or the  
circuit breaker beforehand for preventing you from getting injured by  
the electric fan running inside. For details of cleaning method, refer to  
“Maintenance” on page 9.  
• Do not put anything on the outdoor unit nor step onto it. If you do so,  
it may not only topple over the unit but also injure yourself.  
To make the air conditioner operate in its original performance,  
operate it within the range of the operating temperature specified in  
the instructions.  
Otherwise it may cause a malfunction, or water leak from the unit.  
• Prevent any liquid from falling into the remote controller. Do not spill  
juice, water or any kind of liquid.  
50  
PARTS NAME  
Indoor unit  
NOTE :  
Parts marked with  
XXX  
indicate  
the locally procured parts.  
Connecting duct  
Supply air grille  
Indoor unit  
Duct flange  
Air filter  
Canvas  
Return air grille  
Supply air chamber  
REMOTE CONTROLLER  
Remote controller  
Outdoor unit  
Air inlet (Side and rear)  
Pipes and electric wires  
Air outlet  
51  
PARTS NAME OF REMOTE CONTROLLER  
Display section  
CODE No.  
All display items are shown in right figure for the explanation.  
Only selected contents are displayed in actual operation.  
SET DATA  
UNIT No.  
Display  
section  
SETTING TEST  
R.C. No.  
• When turning on the leakage breaker at the first time, [SET DATA]  
flashes on the display part of the remote controller. While this  
display is flashing, the model is being automatically confirmed.  
Accordingly, wait for a while after [SET DATA] display has disap-  
peared, and then use the remote controller.  
Operation  
section  
UNIT  
SET CL  
1
9
2
10  
CODE No.  
SET DATA  
UNIT No.  
R.C. No.  
3
5
11  
4
6
SETTING  
TEST  
12  
14  
16  
13  
15  
7
8
1
2
3
SET DATA display  
10  
SWING display  
Displayed during setup a timer.  
Displayed during up/down movement of the  
flap.  
Operation mode display  
The selected operation mode is displayed.  
11  
12  
Set up temperature display  
The selected set up temp. is displayed.  
CHECK display  
Displayed while the protective device works  
or a trouble occurs.  
Remote controller sensor display  
Displayed while the sensor of the remote  
controller is working.  
4
5
Timer time display  
Set time by the timer is displayed.  
(When a trouble occurs, the check code is  
displayed.)  
13  
PRE-HEAT display  
Displayed when the heating operation starts or  
defrost operation is carried out.  
While this indication is displayed, the indoor  
fan stops or the mode changes in LOW.  
Timer SETIN setup display  
When pushing the Timer SET button, the  
display of the timer is selected in order of  
14  
15  
No function display  
[OFF]  
[OFF] repeat OFF timer  
Displayed if there is no function even if the  
button is pushed.  
[ON]  
No display.  
Fan mode display  
The selected fan mode is displayed.  
6
Filter display  
(AUTO)  
(HIGH)  
(MED.)  
(LOW)  
If “FILTER  
filter.  
” is displayed, clean the air  
7
8
9
UP/DOWN grille display  
Ventilator operation display  
Flap position display  
16  
TEST run display  
Displayed during a test run.  
52  
Operation section  
Push each button to select a desired operation.  
• The details of the operation needs to be set up once, the same states are used by pushing  
button.  
1
7
8
2
4
3
5
9
UNIT  
10  
SET  
CL  
6
1
2
Fan mode button  
8
button  
Selects a fan mode.  
When the button is pushed, operation starts,  
and it stops by pushing the button again.  
Timer set button  
When the operation stops, the operation lamp  
and all displays disappear.  
TIMER SET button is used when the timer is  
set up.  
9
Operation select button  
3
4
Check button  
Selects operation mode.  
CHECK button is used for check operation.  
During normal operation, do not use this  
button.  
10  
Set up temperature button  
Adjusts required room temperature.  
Set required set temperature by pushing  
Fan button  
FAN button is used when a fan which is sold on  
the market or etc. is connected.  
or  
.
• If “No function” is displayed on the remote  
controller when pushing the FAN button, a  
fan is not connected.  
FILTER UP/DOWN button  
(No function display)  
5
6
7
Filter reset button  
Resets (Erases) “FILTER  
” display.  
OPTION :  
UNIT and AUTO flap button  
Remote controller sensor  
No function  
Usually the TEMP. sensor of the indoor unit mea-  
sures a temperature. A temperature around the  
remote controller can also be measured.  
Operation lamp  
Lamp is lit during the operation. Lamp is off  
when stopped.  
For details, contact the dealer from which you have  
purchased the air conditioner.  
It flashes when operating a protection device  
or abnormal occurred.  
53  
CORRECT USAGE  
When you use the air conditioner for the first time or when you change SET DATA value, follow the procedure  
below. From the next time, the operation will start as set state by pushing the  
button.  
Preparation  
Turn on the main power switch and/or the leakage breaker.  
• When the power supply is turned on, display section is displayed on the remote controller.  
After the power supply is turned on, the remote controller does not accept an operation for approx. 1 minute,  
but it is not a failure.  
*
REQUIREMENT  
• While using the air conditioner, operate it only with  
power switch and the leakage breaker.  
button without turning off the main  
• When starting the operation after stop for a long time, turn on the main power switch for 12 hours or  
more before start. (This is required to turn on the compressor case heater for warming in order to  
prevent overload on the compressor when activating the outdoor unit.)  
1
3
2
UNIT  
4
SET  
CL  
1
2
Push  
button.  
The operation lamp goes on, and the operation starts.  
Select an operation mode with the “MODE” button.  
AUTO  
HEAT  
DRY  
COOL  
FAN  
One push of the button, in each time the display  
changes in the order shown on the right.  
• In HEAT  
mode, if the room temperature reaches to the set temperature, the outdoor unit stops and  
the air flow becomes LOW and the air volume decreases.  
• In the defrost mode, the fan stops so that cool air is not discharged and PRE-DEF  
is displayed.  
3
4
Select air volume with “FAN ” button.  
AUTO  
HIGH  
MED.  
LOW  
One push of the button, in each time the display  
changes in the order shown on the right.  
• When air volume is “AUTO  
• In DRY mode, “AUTO  
”, air volume differs according to the room temperature.  
” is displayed and the air volume is LOW.  
• In heating operation, if the room temperature is not heated sufficiently with fan mode “LOW ” opera-  
tion, select “MED. ” or “HIGH ” operation.  
Determine the set up temperature by pushing the “TEMP.  
” or “TEMP.  
” button.  
54  
Stop  
Push  
button.  
The operation lamp goes off, and the operation stops.  
AUTOMATIC OPERATION (Auto Changeover)  
When you set the air conditioner in  
mode or switch over from AUTO operation, it will automatically select  
either cooling, heating, or fan only operation depending on the indoor room temperature.  
Start  
1
2
3
button  
Push this button to start the air conditioner.  
Mode select button (MODE)  
Select Auto.  
Temperature button  
Set the desired temperature.  
• In case of cooling, start the operation after approx. 1 minute.  
• In case of heating, starts the operation after approximately 3 to 5 minutes.  
• When you select the Auto mode, it is unnecessary to set the fan speed.  
The fan speed display will show  
and fan speed will be automatically controlled.  
• After heating operation stops, FAN operation may continue for approx. 30 seconds.  
• When the room temperature reaches the set temperature and the outdoor unit stops, the LOW wind is  
discharged and the air volume decreases excessively. During defrost operation, the fan stops so that cool  
air is not discharged and  
is displayed.  
• If the Auto mode is uncomfortable, you can select the desired conditions manually.  
NOTE  
When restarting the operation after stop  
• When restarting the operation immediately after stop, the air conditioner does not operate for approx. 3  
minutes to protect a compressor.  
Stop  
Push  
button.  
Push this button again to stop the air conditioner.  
55  
TIMER OPERATION  
A type of timer operation can be selected from the following three types.  
OFF timer  
Repeat OFF timer : Every time, the operation stops after the set time has passed.  
ON timer :The operation starts after the set time has passed.  
:The operation stops after the set time has passed.  
Timer operation  
1
UNIT  
2
SET  
CL  
3
4
1
2
PushTIMER SET button.  
• The timer display (type) changes every  
push of the button.  
OFF  
OFF  
ON  
(OFF timer)  
(Repeat OFF timer)  
(ON timer)  
• SET TIME and  
,
,
,
display flashes.  
No display  
Push  
to select “SETTIME”.  
button, the set time increases in the unit of 0.5 hr (30 minutes).  
For every push of  
The maximum set time is 72.0 hr.  
For every push of  
button, the set time decreases in the unit of 0.5 hr (30 minutes).  
The minimum set time is 0.5 hr.  
3
Push SET button.  
• SET TIME display disappears and timer time display goes on.  
(When ON timer is activated, timer time are displayed, ON timer  
are disappear.)  
and SETTING other displays  
Clear of timer operation  
4
Push CL button.  
• TIMER display disappears.  
NOTICE  
• Once set “Repeat OFF timer” resumes. So start again, stop by same timer.  
For cancel timer, push CL button..  
56  
HINTS FOR ECONOMICAL OPERATION  
Maintain room temperature at comfortable level  
Clean air filters  
Airflow and performance are reduced if the air filters become blocked.  
Clean them every 2 weeks.  
Do not open doors and windows more often than necessary  
To keep cool or warm air in the room, do not open doors and windows more often than necessary.  
Window curtains  
In cooling, close the curtains to avoid direct sunlight.  
In heating, close the curtains to keep the heat in.  
Gee, chilly  
Control  
Get uniform circulation of room air  
Adjust the air flow direction for the even  
circulation of room air.  
Clean, please.  
Please close  
Blows upward  
Cool  
and  
dry  
air  
Air flow adjustment  
Warm  
air  
Blows downward  
MAINTENANCE  
Cleaning of remote controller  
CAUTION  
• Use a dry cloth to wipe the remote controller.  
• A cloth dampened with cold water may be used on the indoor unit if  
it is very dirty.  
• Never use a damp cloth on the remote controller.  
Thinner  
• Do not use a chemically-treated duster for wiping or leave such  
materials on the unit for long. It may damage or fade the surface of  
the unit.  
• Do not use benzine, thinner, polishing powder, or similar solvents for  
cleaning. These may cause the plastic surface to crack or deform.  
57  
If you do not plan to use the unit for more than 1 month  
(1) Operate the fan for 3 to 4 hours to dry inside the unit  
Operate “FAN ONLY” mode with set temperature 30°C.  
(2) Stop the air conditioner and turn off the main power switch or the  
circuit breaker.  
Checks before operation  
(1) Check that the air filters are installed.  
(2) Check that the air outlet or inlet is not blocked.  
(3) Turn on the main power switch or the circuit breaker for the mains AC  
outlet to turn on the air conditioner.  
FAN ONLY operation  
WARNING  
Make sure to ask the qualified maintenance professional for cleaning.  
Turn off the main power supply switch or breaker before the unit maintenance.  
Cleaning of Return grille  
Preparation :  
1. Turn off the air conditioner by the remote controller.  
2. Dismount the Return grille.  
Clean the Return grilles with water:  
• Wipe down the Return grille with a sponge or towel moistened with a kitchen detergent.  
(Do not use any metallic brush for cleaning.)  
• Carefully rinse the Return grille to wash out the detergent.  
• After rinsing the Return grille with water, dry it in the shade.  
CAUTION  
• Do not start the air conditioner while leaving the return grille removed.  
Cleaning of Air Filters  
• Recommended cleaning intervals : Every two weeks.  
If the air filters are not cleared, it not only impairs the  
cooling performance of air conditioner but causes a  
failure in the air conditioner such as water drops.  
Preparation :  
1. Turn off the air conditioner by the remote controller.  
2. Dismount the Return grille.  
Use a vacuum cleaner to remove dust from  
the filters or wash them with water.  
• After rinsing the air filters with water, dry them in the shade.  
• Set the air filter into the air conditioner.  
NOTE  
For Air conditioning system which is operated regularly, cleaning and maintenance of the indoor/outdoor  
units are strongly recommended.  
As a general rule, if an indoor unit is operated for about 8 hours daily, the indoor/outdoor units will need to  
be cleaned at least once every 3-MONTH. This cleaning and maintenance shall be carried out by a  
qualified person.  
Failure to clean the indoor/outdoor units regularly will result in poor performance, icing, water leaking and  
even compressor failure.  
58  
AIR CONDITIONER OPERATIONS AND PERFORMANCE  
3 minutes protection function  
3-minutes protection function prevents the air conditioner from starting for initial 3 minutes after the main  
power switch/circuit breaker is turned on for re-starting the air conditioner.  
Power failure  
Power failure during operation will stop the unit completely.  
To restart the operation, push the START/STOP button on the remote controller.  
• Lightning or a wireless car telephone operating nearby may cause the unit to malfunction. Turn off the main  
power switch or circuit breaker and then turn them on again. Push the START/STOP button on the remote  
controller to restart.  
Heating characteristics  
Preheating operation  
The air conditioner will not deliver warm air immediately after it is turned on. Warm air will start to flow out  
after approximately 5 minutes when the indoor heat exchanger warmed up.  
Warm air control (In heating operation)  
When the room temperature reaches the set temperature, the fan speed is automatically reduced to prevent  
to blow cold draft. At this time, the outdoor unit will stop.  
Defrosting operation  
If the outdoor unit is frosted during the heating operation, defrosting starts automatically (for approximately  
2 to 10 minutes) to maintain the heating capacity.  
• The fans in both indoor and outdoor units will stop during the defrosting operation.  
• During the defrosting operation, the defrosted water will be drained from the bottom plate of the outdoor  
unit.  
Heating capacity  
In the heating operation, the heat is absorbed from the outside and brought into the room. This way of heating  
is called heat pump system. When the outside temperature is too low, it is recommended to use another  
heating apparatus in combination with the air conditioner.  
Attention to snowfall and freeze on the outdoor unit  
• In snowy areas, the air inlet and air outlet of the outdoor unit are often covered with snow or frozen up.  
If snow or freeze on the outdoor unit is left as it is, it may cause machine failure or poor warming.  
• In cold areas, pay attention to the drain hose so that it perfectly drains water without water remaining inside  
for freeze prevention. If water freezes in the drain hose or inside the outdoor unit, it may cause machine  
failure or poor warming.  
Air conditioner operating conditions  
For proper performance, operate the air conditioner under the following temperature conditions:  
Cooling  
Outdoor temperature  
Room temperature  
: –5°C to 43°C  
operation  
: 21°C to 32°C (Dry valve temp.), 15°C to 24°C (Wet valve temp.)  
Room relative humidity – less than 80 %. If the air conditioner operates  
in excess of this figure, the surface of the air conditioner may cause dewing.  
CAUTION  
Dry operation Outdoor temperature  
Room temperature  
: 15°C to 43°C (Maximum suction air temp. 46°C)  
: 17°C to 32°C  
Heating  
Outdoor temperature  
Room temperature  
: –15°C to 15°C (Wet valve temp.)  
: 15°C to 28°C (Dry valve temp.)  
operation  
If air conditioner is used outside of the above conditions, safety protection may work.  
59  
RE-INSTALLATION  
DANGER  
Ask the dealer or an installation professional to re-install the air conditioner to a new place or  
move it to another place and to observe the following items.  
If the air conditioner is inappropriate installed by yourself, it may cause electric shock or fire.  
Do not install the air conditioner in the following places  
• Do not install the air conditioner in any place within 1 m from a TV, stereo, or radio set. If the unit is installed  
in such place, noise transmitted from the air conditioner affects the operation of these appliances.  
• Do not install the air conditioner near a high frequency appliance (sewing machine or massager for business  
use, etc.), otherwise the air conditioner may malfunction.  
• Do not install the air conditioner in a humid or oily place, or in a place where steam, soot, or corrosive gas is  
generated.  
• Do not install the air conditioner in a salty place such as seaside area.  
• Do not install the air conditioner in a place where a great deal of machine oil is used.  
• Do not install the air conditioner in a place where it is usually exposed to strong wind such as in seaside  
area or on the roof or upper floor of a building.  
• Do not install the air conditioner in a place where sulfureous gas generated such as in a spa.  
• Do not install the air conditioner in a vessel or mobile crane.  
Be careful with noise or vibrations  
• Do not install the air conditioner in a place where noise by outdoor unit or hot air from its air outlet annoys  
your neighbors.  
• Install the air conditioner on a solid and stable foundation so that it prevents transmission of resonating,  
operation noise and vibration.  
• If one indoor unit is operating, some sound may be audible from other indoor units that are not operating.  
TROUBLES AND CAUSES  
CAUTION  
If any of the following conditions occur, turn off the main power supply switch and immediately contact the  
dealer :  
• The operation lamps flash at short intervals (5 Hz) even though you have tried turning off the power  
supply and turning on again after 2 or 3 minutes.  
• Switch operation does not work properly.  
• The main power fuse often blows out, or the circuit breaker is often activated.  
• A foreign matter or water fall inside the air conditioner.  
• Any other unusual conditions are observed.  
60  
Before you ask for servicing or repairs, check the following points.  
Inoperative  
• The main power switch is turned off.  
• The circuit breaker is activated to cut off power supply.  
• The main power fuse has blown out.  
• Stoppage of electric current.  
Does not cool well or heat well  
• The air inlet and/or outlet of the outdoor unit is blocked.  
• Doors or windows are opened.  
• The fan speed is set to low.  
• The air conditioner is set in the DRY mode.  
• The set temperature is too high. (In cooling operation)  
• The set temperature is too low. (In heating operation)  
Indoor unit or outdoor unit makes a strange noise.  
• When the temperature suddenly changes, the indoor or outdoor unit  
occasionally makes a strange noise because of changing of refrigerant flow or  
expansion work.  
The room air is smelly or a bad odor comes from the air conditioner.  
• Smells impregnated in the walls‚ carpets, furniture, clothing, or furs, come  
out from the air conditioner.  
Outdoor unit is frosted in heating operation.  
Water drains from outdoor unit.  
• The outdoor unit is sometimes frosted in heating operation.  
In that case, the unit automatically performs defrosting  
(for 2 to 10 minutes) for increasing the heating efficiency.  
Calm  
• In defrosting operation, both the indoor and outdoor units stop air flow.  
• Hiss sound is heard when flow of the refrigerant is changed for defrosting.  
• Resultant water of automatic defrosting in heating operation drains from  
outdoor unit.  
Air flow changes without FAN button set to AUTO mode.  
• When the temperature of blown air drops in heating operation,  
the air conditioner automatically changes or stops air flow from the  
indoor unit not to make persons in the room feel chilly.  
• Air flow of the indoor unit is occasionally changed in the cooling operation.  
A white mist of chilled air or water is generated from the outdoor unit.  
• The indoor unit in cooling operation or the outdoor unit in defrosting  
operation occasionally cause steams.  
61  
TROUBLES AND CAUSES (Concerning Remote Controller)  
Before you ask for servicing or repairs, check the following points:  
Setting Change is Impossible  
Symptoms  
Causes  
Reason and Disposal  
The fan speed can not be  
changed.  
• Check whether the MODE indi-  
cated on the display is “AUTO”.  
When the automatic mode is se-  
lected, the air conditioner automati-  
cally selects the fan speed.  
AUTO  
• Check whether the MODE indi-  
cated on the display is “DRY”.  
When dry operation is selected, the  
air conditioner automatically selects  
the fan speed.  
(DRY)  
62  
Accessory parts and Parts to be procured locally  
r Accessory parts  
Part name  
Q’ty  
Shape  
Part name  
Q’ty  
Shape  
Connecting cable for  
High static pressure tap  
Pipe insulator  
2
1
Installation Manual  
Owner’s Manual  
1
1
Drain hose socket for  
drain pipe connection  
1
<Separate sold parts>  
Part name  
Q’ty  
Shape  
Standard wired remote  
controller  
1
r Parts to be procured locally  
Connecting pipe (Liquid side)  
Connecting cable  
(6.35mm (diam.), Nominal (diam.) 1/4” thick 0.8mm)  
RAV-SM800BT-E, RAV-SM560AT-E  
H07RN-F or 245IEC66 (1.5mm² or more)  
(9.52mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)  
RAV-SM560BT-E, RAV-SM800AT-E  
Thermal insulation for refrigerant pipe  
(10mm or more, thermal insulating foam polyethylene)  
Connecting pipe (Gas side)  
Thermal insulation for drain pipe  
(12.7mm (diam.), Nominal (diam.) 1/2” thick 0.8mm)  
RAV-SM560BT-E, RAV-SM560AT-E  
(10mm or more, foam polyethylene)  
(15.9mm (diam.), Nominal (diam.) 5/8” thick 1.0mm)  
RAV-SM800BT-E, RAV-SM800AT-E  
Drain pipe (Outer 26mm (diam.))  
Tapes  
Power supply cord  
2.5mm² (H07RN-F or 245IEC66) or 3.5mm² (AWG-12)  
Grounding cable (2.0mm (diam.) or more)  
63  
1
PRECAUTIONS FOR SAFETY  
• Ensure that all Local, National and International regulations are satisfied.  
• Read this “PRECAUTIONS FOR SAFETY” carefully before Installation.  
• The precautions described below include the important items regarding safety. Observe them without fail.  
• After the installation work, perform a trial operation to check for any problem.  
Follow the Owner’s Manual to explain how to use and maintain the unit to the customer.  
• Turn off the main power supply switch (or breaker) before the unit maintenance.  
• Ask the customer to keep the Installation Manual together with the Owner’s Manual.  
CAUTION  
New Refrigerant Air Conditioner Installation  
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT  
DESTROY OZONE LAYER.  
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure  
is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil  
has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or  
refrigerating oil does not enter the refrigerating cycle.  
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging  
port of the main unit and installation tools are charged from those for the conventional refrigerant.  
Accordingly the exclusive tools are required for the new refrigerant (R410A).  
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does  
not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance force  
and impurity in it.  
CAUTION  
To Disconnect the Appliance from Main Power Supply.  
This appliance must be connected to the main power supply by means of a switch with a contact separation of  
at least 3 mm.  
The installation fuse (25A D type  
) must be used for the power supply line of this conditioner.  
WARNINGS  
• Ask an authorized dealer or qualified installation professional to install/maintain the air  
conditioner.  
Inappropriate installation may result in water leakage, electric shock or fire.  
• Turn off the main power supply switch or breaker before attempting any electrical work.  
Make sure all power switches are off. Failure to do so may cause electric shock.  
• Connect the connecting cable correctly.  
If the connecting cable is connected in a wrong way, electric parts may be damaged.  
• When moving the air conditioner for the installation into another place, be very careful not  
to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.  
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes  
abnormally high and it may resultingly causes pipe burst and injuries on persons.  
• Do not modify this unit by removing any of the safety guards or by by-passing any of the  
safety interlock switches.  
• Exposure of unit to water or other moisture before installation may cause a short-circuit of  
electrical parts.  
Do not store it in a wet basement or expose to rain or water.  
64  
1
PRECAUTIONS FOR SAFETY  
• After unpacking the unit, examine it carefully if there are possible damage.  
• Do not install in a place that might increase the vibration of the unit.  
• To avoid personal injury (with sharp edges), be careful when handling parts.  
• Perform installation work properly according to the Installation Manual.  
Inappropriate installation may result in water leakage, electric shock or fire.  
• When the air conditioner is installed in a small room, provide appropriate measures to  
ensure that the concentration of refrigerant leakage occur in the room does not exceed the  
critical level.  
• Install the air conditioner securely in a location where the base can sustain the weight  
adequately.  
• Perform the specified installation work to guard against an earthquake.  
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.  
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.  
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.  
• After the installation work, confirm that refrigerant gas does not leak.  
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might  
generate.  
• Electrical work must be performed by a qualified electrician in accordance with the  
Installation Manual. Make sure the air conditioner uses an exclusive power supply.  
An insufficient power supply capacity or inappropriate installation may cause fire.  
• Use the specified cables for wiring connect the terminals securely fix. To prevent external  
forces applied to the terminals from affecting the terminals.  
• Be sure to provide grounding.  
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.  
• Conform to the regulations of the local electric company when wiring the power supply.  
Inappropriate grounding may cause electric shock.  
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible  
gas.  
If a combustible gas leaks, and stays around the unit, a fire may occur.  
65  
2
SELECTION OF INSTALLATION PLACE  
WARNING  
• Install the air conditioner at enough strong place to withstand the weight of the unit.  
If the strength is not enough, the unit may fall down resulting in injury.  
• Install the air conditioner at a height 2.5m or more from the floor.  
If you insert your hands or others directly into the unit while the air conditioner operates, it is dangerous  
because you may contact with revolving fan or active electricity.  
CAUTION  
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible  
gas.  
If a combustible gas leaks and stays around the unit, a fire may occur.  
Upon approval of the customer, install the air conditioner in a place that satisfies the  
following conditions.  
• Place where the unit can be installed horizontally.  
• Place where a sufficient servicing space can be ensured for safety maintenance and check.  
• Place where drained water will not cause any problem.  
Avoid installing in the following places.  
• Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas  
(hot spring). (Should the unit be used in these places, special protective measures are needed.)  
• Place exposed to oil, vapor, oil smoke or corrosive gas.  
• Place where organic solvent is used nearby.  
• Place close to a machine generating high frequency.  
• Place where the discharged air blows directly into the window of the neighboring house. (For outdoor unit)  
• Place where noise of the outdoor unit is easily transmitted.  
(When installing the air conditioner on the boundary with the neighbor, pay due attention to the level of noise.)  
• Place with poor ventilation. (Before air ducting work, check whether value of air volume, static pressure and  
duct resistance are correct.)  
Selection of installation place  
Installation space  
In case of continued operation of the indoor unit under  
high-humidity conditions as described below, dew may  
condense and water may drop.  
Secure the space required to installation  
and servicing.  
Especially, high-humidity atmosphere (dew point temperature  
: 23°C or more) may generate dew inside the ceiling.  
300 to 400  
for service space  
Refrigerant piping  
Drain piping  
1. Unit is installed inside the ceiling with slated roof.  
Maintenance etc.  
100 or more  
2. Unit is installed at a location using inside of the ceiling  
as fresh air take-in path.  
450  
200  
3. Kitchen  
If installing a unit at such place, adhere insulating material  
(glass wool, etc.) additionally over all the positions of the  
indoor unit which come to contact with high-humidity  
atmosphere.  
450  
Check/service  
opening panel  
420  
or more  
Advice  
Set a check service opening panel at right side of the unit  
(size: 450 x 450mm) for piping, maintenance, and servicing.  
66  
3
INSTALLATION OF INDOOR UNIT  
WARNING  
Install the air conditioner certainly at a place to sufficiently withstand the weight.  
If the strength is insufficient, the unit may fall down resulting in human injury.  
Perform a specified installation work to guard against an earthquake.  
An incomplete installation can cause accidents by the units falling and dropping.  
Installation procedure  
1. Lay drain pipes, refrigerant pipes, and connecting cables behind wall  
or ceiling concurrently with supply/drain water work and piping work.  
2. Install the mounting frames of supply/return air panels  
3. Position the refrigerant and drain pipes  
4. Install the indoor unit  
• Preparation for installation  
• Setting/fixing of indoor unit  
5. Connect cables and pipes  
6. Install supply/return air panels  
7. Mount thermal insulation  
8. Mount check port  
67  
External view  
REQUIREMENT  
The hanging bolt pitch on horizontal direction (B) is not halved at center with the ceiling opening size.  
Therefore, check the relational position in the following figure.  
75  
25  
Main unit dimension 800  
Hanging bolt  
Main unit dimension A  
Hanging bolt pitch B  
Hanging bolt pitch 565  
210  
H
4-M10 screw  
(Arranged  
locally)  
720  
630  
Refrigerant pipe  
connecting port  
(Gas side ØF)  
Refrigerant pipe  
connecting port  
(Liquid side ØG)  
J = M x K  
Suction port  
(with air filter)  
Drain pipe connecting port  
For vinyl chloride pipe  
(Inner dia. 32,  
Ø125 knockout hole  
(Rear face)  
450  
Nominal dia. 25)  
Ceiling opening  
dimension  
470  
2-Ø26 power supply,  
pull-out port of remote  
controller cord  
Check panel  
• Dimension  
A
B
F
G
H
J
K
M
1
N
2
3
RAV-SM560BT-E  
RAV-SM800BT-E  
700  
750  
12.7  
6.4  
9.5  
252  
252  
280  
580  
280  
290  
1000 1050 15.9  
2
1. Hanging down of indoor unit  
Hanging bolt  
Refer to installation figures of hanging material  
and hanging bolt.  
Nut with flange  
(or washer and nut)  
• Adjustment of hanging bolt length and nut  
position  
Square washer  
15 to 20  
20 to 30  
Adjust hanging bolt length and nut position as  
shown in the figure before hanging down the  
indoor unit.  
Hexagonal nut  
NOTE :  
Be sure to set the indoor unit horizontally so as not to  
cause malfunction of the float switch or leakage of water.  
Considering pipe/wire connecting work inside the ceiling after the indoor unit has been hanged, select an installation  
place and determine piping direction.  
• If the ceiling has been already set, prepare refrigerant pipe, drain pipe, connecting wire, switch panel cord, etc. at  
the place where pipe and wire are connected before hanging the main unit.  
68  
3
INSTALLATION OF INDOOR UNIT  
Supply chamber  
Concealed duct type  
Channel  
Supply grille  
Supplying  
200mm (diam.)  
round duct  
Supplying  
Indoor unit  
Returning  
Return air grille  
NOTE:  
• Recommended supplying grille size 400 cm² each or more  
Ledge ceiling concealed duct type  
Supplying  
Supply grille  
Supply  
Indoor unit  
chamber  
Supplying  
200mm (diam.)  
round duct  
Return air grille  
Returning  
Quality of supplying grilles  
SM560BT-E  
SM800BT-E  
2
3
NOTE:  
• Opening area of the return grille should be larger than  
the one for suction port (Air filter) of the indoor unit.  
Restriction to installation  
1. Installation clearance  
• As shown in the figure, keep clearance around the indoor unit.  
Inner ceiling  
100mm or more  
300mm  
or more  
100mm  
or more  
300mm  
or more  
69  
4
AIR DUCTING WORK  
Static pressure characteristics of each model  
Fig. 1 RAV-SM560BT-E  
70% (570m³/h)  
110% (925m³/h)  
Standard air volume : 840m³/h  
Extra HHigh tap  
12  
11  
10  
9
8
High tap  
7
6
Middloeletatpap  
5
4
3
Low tap  
2
1
0
500  
570 600  
700  
800  
900 925  
1000  
Air volume (m³/hr.)  
Fig. 2 RAV-SM800BT-E  
70% (800m³/h)  
110% (1255m³/h)  
Standard air volume : 1140m³/h  
12  
11  
10  
9
Extra HHigh tap  
8
High tap  
7
6
Middoleletatapp  
5
4
3
Low tap  
2
1
0
700  
800  
900  
1000  
1100  
1200 1255  
1300  
Air volume (m³/hr.)  
70  
4
AIR DUCTING WORK  
Installation Reference  
(exp. for RAV-SM800BT-E model)  
The air supply ducting work is classified in two ways, one is branched by the round ducts, and the other is branched  
by the square ducts. (Be sure to divide the air supply duct into three or more branches.)  
<Round duct>  
<Square duct> (Reference for square duct)  
When using the square duct, change the type of the air  
supply flange from round type to square flange at the  
local site.  
In case of the round duct, use the thermal insulator of  
thickness 25mm or more and inner diameter 150mm  
or more to the duct board.  
(If the inner diameter is not enough, resistance  
increase, as the result, air does not flow smoothly and  
loss of the static pressure increases.) For the thermal  
insulator, use high-density glass wool of 24kg/m3 or  
equivalent.  
In case of the square duct, apply the thermal insulator  
of thickness 25mm or more to the duct board. For the  
thermal insulator, use high-density glass wool of  
weight 64kg/m3.  
Density of thermal  
insulator (glass wool) is  
24 kg/m³ or equivalent.  
25mm or more  
Duct board  
Density of thermal  
insulator (glass wool) is  
64 kg/m³ or equivalent.  
Ø150mm or more  
25mm or more  
Connecting method of the duct  
1. Supply air side  
<Round duct>  
<Square duct>  
Thermal insulator with  
Thermal insulator  
Thermal insulator  
Thermal insulator  
at indoor unit side  
Stuck already at  
sticking material  
with sticking material  
at indoor unit side  
(50mm-width, 6mm (t))  
(50mm-width, 6mm-thickness)  
Stuck already at  
(
)
Aluminum tape  
(
)
shipment from the factory  
shipment from the factory  
Aluminum tape  
(Seal : 50mm-width)  
(Seal : 50mm-width)  
Screws  
Screws  
(6 pieces)  
Fit to the arrow  
direction by pushing.  
Fit to the arrow  
direction by pushing.  
(6 pieces)  
Indoor unit side  
Flange  
Attach by pushing to  
(procured locally)  
Round duct  
the arrow direction.  
Seal/thermal insulator  
with sticking material  
(25mm-width, 6mm (t))  
Flange  
Thermal insulator  
Seal/thermal insulator  
with sticking material  
(25mm-width, 6mm (t))  
(Outside corner direction)  
25mm-thickness,  
Square duct board  
(
)
24kg/m³ or equivalent  
25mm-thickness,  
64kg/m³ or equivalent  
(
)
Fit the seal/thermal insulator (25mm-width, 6mm-thickness)  
by pushing to the arrow direction so that no gap can be  
found between the flange and the round duct.  
Fig. 2 (b)  
Fig. 2 (a)  
CAUTION  
Incomplete thermal insulation of the supply air flange and sealing may cause dew drops.  
71  
<Square duct>  
Connecting method of the duct  
1. Using 6 screws, mount the flange to the supply air  
port of the indoor unit. (Fig. 2)  
1. Supply air side  
<Round duct>  
2. Make the square duct according to inner dimension  
of the flange A x B .  
1. Make the round duct according to inner dimension  
of the flange  
Use a glass wool board with inside/outside finishing  
25mm-thickness and 24kg/m³-density.  
Use a glass wool board with inside/outside finishing  
25mm-thickness and 24kg/m³-density.  
3. Connect the flange and each type of duct. (Fig. 3)  
2. Connect the flange and each type of duct. (Fig. 1)  
Thermal insulator (50mm (w), 6mm (t))  
Aluminum tape  
(50mm-width)  
Seal  
Thermal insulator :  
B
(
)
25mm (w), 6mm (t)  
25mm  
Fig. 2  
Thermal insulator (50mm (w), 6mm (t))  
Seal  
Indoor unit  
Aluminum tape  
(50mm-width)  
Thermal insulator :  
(
)
25mm (w), 6mm (t)  
25mm  
End  
End  
Indoor unit  
Round duct board  
Thermal insulator  
(25mm thickness, 24kg/m³ or equivalent)  
Square  
duct board  
(25mm)  
Fig. 1  
Fig. 3  
Points at installation work  
n General cautions  
1. Considering installation places of indoor unit supply chamber, structure of the building and determine the duct  
path.  
2. In order to utilize the static pressure characteristics of the air supply in the indoor unit, design the duct branching  
having the large size of the air supply chamber or setting distance to the first branch as long as possible  
(Min. : 200mm or longer) so that an even air volume can be obtained.  
Especially, when branching just after air supply of the indoor unit, air concentrates at the center part and is  
difficult to flow to the ducts at both sides.  
3. Connect each connecting section surely, and apply sufficient thermal insulation.  
In this model of which the duct is branched in the ceiling, compared with the model for ordinary houses, the high  
temperature generates on the periphery in the cooling time (Especially, at attic and etc.), temperature difference  
increases between the supply air and outside of the duct, and dewing may occur.  
Dewing on the surface of the thermal insulator covering the metal connecting section or leaking portion of the  
cooled air may cause a trouble such as water drops.  
4. Thermal insulation of screwing sections is necessary.  
Prevent dewing by applying thermal insulation to 6 screws those fix the duct flange of the air supply chamber.  
• For duct parts, the flexible branch duct (thermal insulation, 25mm or more thickness) is recommended.  
• Adjust the duct length to 6m or less even for straight pipe, and avoid sharp bending (Air flow resistance is  
large.) if bending.  
72  
4
AIR DUCTING WORK  
Hanging of indoor unit  
Nut  
Lift up the unit with a lifter, etc., and set the hanging metal in the  
hanging bolt.  
• Hook nut of the hanging bolt to the groove of the hanging metal on  
the main unit.  
Washer  
Hanging bolt  
Hanging bracket  
• Using the level, etc., install the main unit horizontally.  
Failure to do this will cause water leakage  
Mounting of filter and canvas for suction port  
1. Mount a long-life filter or a high-performance filter according to each Installation Manual.  
2. Mount the canvases for suction port to the lower side of the above filter.  
Mounting of remote controller  
For the mounting of the wired remote controller, refer to the Installation Manual attached to the remote controller.  
• Take out the remote controller cord together with the refrigerant pipe or drain pipe. Be sure to set the remote  
controller cord so that it passes through the upper side of the refrigerant pipe and drain pipe.  
For reference  
<Square duct>  
(Procured locally)  
Return Air side  
Supply Air side  
For supply  
air side  
G-Ø5 mm holes  
G-Ø5 mm holes  
For return  
air side  
C
B
D
A
A
18  
18  
25  
18  
18  
25  
25  
25  
25  
25  
18  
J
J
J
J
18  
18  
18  
H
H
A
A
A
B
C
D
E
F
G
H
I
J
K
Model  
700  
1000  
400  
430  
65  
439  
439  
265  
265  
409  
409  
245  
245  
4
350 226  
500 226  
RAV-SM560BT-E  
RAV-SM800BT-E  
RAV-SM560BT-E  
RAV-SM800BT-E  
Return Air side  
(Return filter side)  
700  
8
22  
30  
350  
550 455 (65 x 7)  
850 715 (65 x 11)  
530  
830  
275 132.5 227.5 130  
425 132.5 307.5 130  
Supply Air side  
65  
73  
5
DRAIN PIPING WORK  
Piping material  
1.5m to 2m  
Support  
bracket  
• For laying pipes underground, use hard vinyl  
chloride pipe. (Inner diam. 20 or 25mm)  
Indoor  
unit  
1/100 or more  
downward slope  
Thermal  
insulator  
Arched shape  
Trap  
Piping and cautions  
• Set drain side of pipe at downward slope.  
(1/100 or more)  
• Be sure to apply thermal insulation (foaming  
polyethylene, 10mm-thickness or more) for pipes  
passing through the room.  
• As shown in the figure, set the collective piping such  
as the ceiling duct so that waste water does not back  
up from the main pipe.  
• Adhere the connecting sections with vinyl chloride  
agent surely so that no water leakage is caused.  
• Support the piping with hanging bracket so that the  
force is not applied to connection sections of pipe  
and pipe is not waved.  
NOTES :  
• Do not make slack or trap at halfway across piping.  
• Set pipes so that the end of drain pipe is not dipped in  
water, and also keep space 50mm or more to the  
ground.  
50 mm  
or more  
Do not put the drain hose  
end into water or drainage.  
• After piping work, check if water drains smoothly.  
• Hole should be made at a slight downward slant to  
the outdoor side.  
Shield pipe (local parts)  
• When connecting extension drain hose, insulate the  
connecting part of extension drain hose with shield  
pipe.  
Drain hose Inside the room  
Extension drain hose  
Connection of the drain hose  
• Insert the drain hose completely into the connecting port of the drain pan.  
• Apply thermal insulation surely to the drain hose with socket thermal insulation seal.  
As long as possible (Approx. 100mm)  
VP 30  
VP 30  
VP 30  
Extended  
ventilating pipe  
VP 30 or more  
Downward grading  
1/100 or more  
74  
6
REFRIGERANT PIPING  
• Flaring dia meter size : A (Unit : mm)  
Refrigerant Piping  
+0  
A
-
0.4  
1. If the outdoor units are to be mounted on a wall,  
make sure that the supporting platform is  
sufficiently strong. The platform should be  
designed and manufactured to maintain its strength  
over a long period of time, and sufficient  
consideration should be given to ensuring that the  
outdoor unit will not fall.  
Outer diam. of copper pipe  
R410A  
9.1  
R22  
9.0  
6.35  
9.52  
12.7  
15.9  
13.2  
16.6  
19.7  
13.0  
16.2  
19.4  
2. Use copper pipe with 0.8 mm or more  
thickness.  
In the case of flaring for R410A with the conventional  
flare tool, pull out it approx.  
*
3. Flare nut and flare works are also different from  
those of the conventional refrigerant.  
A
0.5 mm more than that for R22 to  
Take out the flare nut attached to the main unit of  
the air conditioner, and use it.  
adjust to the specified flare size.  
The copper pipe gauge is useful  
for adjusting projection margin size.  
CAUTION  
IMPORTANT 4 POINTS FOR PIPING WORK  
Tightening connection  
1. Remove dust and moisture from the inside of  
the connecting pipes.  
CAUTION  
2. Tight connection (between pipes and unit)  
• Do not apply excessive torque. Otherwise, the  
nut may crack depending on the conditions.  
3. Evacuate the air in the connecting pipes using  
VACUUM PUMP.  
4. Check the gas leakage. (connected points)  
(Unit : N•m)  
Outer diam. of copper pipe  
Tightening torque  
Permissible Piping Length and Heat  
6.35 mm (diam.)  
9.52 mm (diam.)  
12.7 mm (diam.)  
15.9 mm (diam.)  
14 to 18 (1.4 to 1.8 kgf•m)  
33 to 42 (3.3 to 4.2 kgf•m)  
50 to 62 (5.0 to 6.2 kgf•m)  
63 to 77 (6.3 to 7.7 kgf•m)  
The maximum piping length from the outdoor to indoor unit  
30 m (Chargeless 20m)  
(RAV-SM560AT-E)  
50 m (Chargeless 20m)  
(RAV-SM800AT-E)  
The maximum height difference outdoor/indoor unit  
Outdoor unit is above  
Outdoor unit is below  
• Tightening torque of flare pipe connections  
30m  
15m  
Pressure of R410A becomes higher than that of R22.  
(Approx. 1.6 times) Therefore, using a torque  
wrench, tighten firmly the flare pipe connecting  
Flaring  
Insert a flare nut into the pipe, and flare the pipe.  
sections which connect the  
indoor and outdoor units up to  
the specified tightening torque.  
Flare at  
indoor  
As the flaring sizes of R410A differ from those of  
refrigerant R22, the flare tools newly manufactured for  
R410A are recommended.  
unit side  
B
Incorrect connections may  
cause not only a gas leakage,  
but also a trouble of the  
refrigeration cycle or  
However, the conventional  
tools can be used by  
adjusting projection margin  
of the copper pipe.  
compressor damage.  
Flare at  
outdoor  
• Projection margin in flaring : B (Unit : mm)  
unit side  
Rigid (Clutch type)  
Align the centers of the connecting pipes and tighten  
the flare nut as far as possible with your fingers. Then  
tighten the nut with a spanner and torque wrench as  
shown in the figure.  
R410A tool used  
R410A R22  
Conventional tool used  
R410A R22  
Outer diam. of  
copper pipe  
6.35 to 9.52 0 to 0.5 (Same as left) 1.0 to 1.5 0.5 to 1.0  
Half union  
Flare nut  
Imperial (Wing nut type)  
Externally  
threaded side  
Internally  
threaded side  
Outer diam. of copper pipe  
6.35 or 9.52  
R410A  
R22  
1.5 to 2.0  
2.0 to 2.5  
1.0 to 1.5  
1.5 to 2.0  
12.7 or 15.9  
Use a wrench to secure.  
Use a torque wrench to tighten.  
75  
7
EVACUATING  
<For RAV-SM800AT-E model>  
AIR PURGE  
• As shown in the figure, be sure to use a double  
spanner to loosen or tighten the flare nut of the valve  
at gas side. If using a single spanner, the nut cannot  
be tightened with necessary tightening torque.  
Evacuate the air in the connecting pipes and in the  
indoor unit using vacuum pump.  
Do not use the refrigerant in the outdoor unit.  
For details, see the manual of vacuum pump.  
On the contrary, use a single spanner to loosen or  
tighten the flare nut of the valve at liquid side.  
Use a vacuum pump  
Cover  
Be sure to use a vacuum pump with counter-flow  
prevention function so that inside oil of the pump does  
not flow backward into pipes of the air conditioner  
when the pump stops.  
Cap  
Piping valve  
1. Connect the charge hose from the manifold valve  
to the service port of the gas side packed valve.  
Loosened  
Tightened  
2. Connect the charge hose to the port of vacuum  
pump.  
3. Open fully the low pressure side handle of the  
gauge manifold valve.  
Flare nut  
4. Operate the vacuum pump to start evacuating.  
SM800 type valve at gas side  
Perform evacuating for about 35 minutes if the  
piping length is 30 meters total for model SM560  
and 50 meters for model SM800  
(assuming a pump capacity of 27 liters per minute.)  
Then confirm that the compound pressure gauge  
reading is –101 kPa ( –76 cmHg).  
Cover  
5. Close the low pressure side valve handle of gauge  
manifold.  
6. Open fully the valve stem of the packed valves  
(both sides of Gas and Liquid).  
Do not put the spanner or  
torque wrench, etc. on  
the cover.  
7. Remove the charging hose from the service port.  
8. Securely tighten the caps on the packed valves.  
The valve may be broken.  
Packed valve handling precautions  
• Open the valve stem all the way out ; do not try to  
open it beyond the stopper.  
Compound  
Pressure gauge  
Manifold valve  
pressure gauge  
• Securely tighten the valve stem cap at the torque as  
follows:  
–101kPa  
(–76cmHg)  
Handle Lo  
15.9 mm (diam.)  
12.7 mm (diam.)  
9.52 mm (diam.)  
6.35 mm (diam.)  
63 to 77 N•m (6.3 to 7.7 kgf•m)  
50 to 62 N•m (5.0 to 6.2 kgf•m)  
33 to 42 N•m (3.3 to 4.2 kgf•m)  
14 to 18 N•m (1.4 to 1.8 kgf•m)  
Handle Hi  
(Keep fully closed)  
Charge hose  
Charge hose  
Vacuum pump  
adapter for  
counter-flow  
prevention  
Packed valve  
at liquid side  
Hexagonal wrench is required.  
Vacuum  
pump  
Service port  
(Valve core (Setting pin))  
Packed valve at gas side  
76  
8
ELECTRICAL WORK  
For the air conditioner that has no power cord.  
Cabling  
NOTE:  
1. As shown in the figure, remove a screw  
then remove cover of the electric part.  
and  

For selection and connection method of the power  
supply cords, refer to the details in the Installation  
Manual of the outdoor unit.  
2. Strip wire ends (10 mm).  
3. Match wire colors with terminal numbers on indoor  
and outdoor units’ terminal blocks and firmly screw  
wires to the corresponding terminals.  
CAUTIONS  
4. Connect the ground wires to the corresponding  
terminals.  
• If incorrect/incomplete wiring is carried out, it  
may cause an electrical fire or smoke.  
5. Fix the cable with cord clamp.  
• Prepare the power supply for exclusive use with  
the air conditioner.  
6. Fix cover of the parts box and the terminal block  
surely with the fixing screws.  
• Be sure to use the cord clamps with attached to  
the product.  
• Do not damage or scratch the conductive core  
and inner insulator of power and inter-connecting  
cables when peeling them.  
• Be sure to comply with local regulations on  
running the wire from outdoor unit to indoor unit  
(wire size of wire and wiring method etc.)  
• Use the power cord and Inter-connecting cable  
of specified thickness, specified type, and  
protective devices required.  
How to wire  
Cord clamp  
1. Connect the connecting cable to the terminal as  
identified with their respective numbers on the  
terminal block of indoor and outdoor unit.  
H07 RN-F or 245 IEC 66 (1.5 mm2 or more)  
2. Insulate the unsheathed redundant cords  
(conductors) with tape.  
Make a loop for the margin of the cable length so that  
the electric parts box can be taken out during servicing.  
3. For inter-unit wiring, do not use a wire jointed to  
another on the way.  
Power supply cord  
Remote controller  
cord  
4. Fix the cable with cord clamp.  
77  
Remote Controller Cabling  
Remote controller cabling  
Cable from remote  
• Strip approx. 14mm the cable to be connected.  
• Non polarity, 2 core cable is used for cabling of the remote controller.  
• Twist cable of the remote controller to be connected with cable of the remote  
controller unit (or sensor), and press-fit them with a wire joint.  
(Wire joints (White: 2 pieces) are included in the attachments to the remote  
controller (sold separately) or the wireless remote controller kit (sold  
separately).  
Wire joint  
controller unit  
Remote controller  
Remote controller  
cable  
A
1
B
2
Approx. 200mm  
W : White  
B : Black  
Indoor side  
3
3
Terminal block  
for remote controller  
cabling of indoor unit  
A
B
W
B
Remote controller  
unit or sensor part  
Indoor/Outdoor  
connecting cable  
1
L
2
Remote controller cable  
(Procured locally)  
Remote controller unit or  
cable from sensor part  
Connecting  
part  
Outdoor side  
N
(Single phase 220/230/240V)  
Cabling diagram  
• For details of cabling/installation of the remote controller, refer to the  
Installation Manual attached to the remote controller.  
Check and Test Operation  
Be sure to test the pipe connections for gas leak.  
• Check the flare nut connections, valve stem cap connections and service port cap connections for gas leak with a  
leak detector or some soap water.  
9
INSTALLATION/SERVICING TOOLS  
Tools  
Tools  
Applicable to R22 model  
Tools  
Applicable to R22 model  
Gauge manifold  
Charge hose  
Flare tool (clutch type)  
¡
o
Gauge for projection  
adjustment  
__  
____  
o
¡
o
Vacuum pump adapter  
Gas leak detector  
¡
Electronic balance for  
refrigerant charging  
Torque wrench  
(nominal diam.  
1/4, 3/8, 1/2, 5/8)  
o
: Newly prepared (They are special requirements for R407C, separate from those for R22.)  
¡
o : Existing tools are available.  
For the details of the tools, refer to the Installation manual of the outdoor unit.  
78  
ACCESSORIES  
Remote controller  
Screws (two pcs.)  
for Remote controller  
Installation plate  
Screws for  
installation plate  
Ø4mm x 25mm  
STANDBY  
FILTER  
F
A
N
CHECK  
COOL  
PRE-HEA  
T
D
R
Y
DEFROST  
LOUVER  
MANUAL  
HEAT AUTO  
AUTO  
CENTRAL  
F
I
X
TEMP.  
FAN SPEED  
LOUVER  
(sold separately)  
PRECAUTIONS FOR SAFETY  
WARNING  
WARNINGS ABOUT INSTALLATION  
• Make sure to ask the qualified installation professional in electric work to install  
the air conditioner.  
If the air conditioner is inappropriate installed by yourself, it may cause water  
leak, electric shock, fire, and so on.  
• Ground the air conditioner without fail.  
Do not connect the ground wire to gas pipe, water pipe, lightning rod or ground  
wire of telephone. If the air conditioner is imperfectly grounded, it may cause  
electric shock.  
CAUTION  
TO DISCONNECT THE APPLIANCE FROM THE MAINS SUPPLY  
This appliance must be connected to the mains by means of a switch with a  
contact separation of at least 3 mm.  
The installation fuse (25A D type  
supply line of this conditioner.  
) must be used for the power  
WARNINGS ABOUT OPERATION  
• Avoid cooling the room too strong or exposing the human body to cool breeze  
for a long time as it is bad for the health.  
• When you notice something abnormal with the air conditioner (smells like  
something scorching, poor cooling, etc.), immediately turn off the main switch,  
the circuit breaker, from the mains to stop the air conditioner, and contact the  
dealer.  
If the air conditioner is continuously operated with something abnormal, it may  
cause machine failure, electric shock, fire, and so on.  
WARNINGS ABOUT MOVEMENT AND REPAIR  
• Do not move or repair any unit by yourself.  
Since there is high voltage inside the unit, you may get electric shock when  
removing the cover and main unit.  
• Whenever the air conditioner needs repair, make sure to ask the dealer to do it.  
If it is repaired imperfectly, it may cause electric shock or fire.  
• When moving the air conditioner for re-installing at another place, ask the  
dealer to do it. If it is imperfectly installed, it may cause electric shock or fire.  
79  
CAUTION  
CAUTIONS ABOUT INSTALLATION  
• Certainly lay the drain hose for perfect draining.  
Bad drainage may cause flooding in the house and getting furniture  
wet.  
• Make sure to connect the air conditioner to an exclusive AC outlet of  
the rated voltage, otherwise the unit may break down or cause a fire.  
• Do not install the unit in a place where inflammable gas may leak.  
If inflammable gas accumulates around the unit, it may cause a fire.  
CAUTIONS ABOUT OPERATION  
• Carefully read this manual before starting the air conditioner.  
There are many important things to keep in mind for daily operation.  
• Do not use this air conditioner for special purpose such as preserv-  
ing food, precision instruments, art objects, breeding animals,  
growing potted plants, etc.  
• Avoid exposing potted plants and animals to the wind of the air  
conditioner, since it badly affects the health and growth of them.  
• When the air conditioner is operated with a combustion appliance in  
the same place, be careful of ventilation to let fresh air enter the  
room.  
Poor ventilation causes oxygen shortage.  
• When the air conditioner is used in a closed room, be careful of  
sufficient ventilation of the room. Poor ventilation causes oxygen  
shortage.  
• Do not touch any switches with wet finger, otherwise you may get an  
electric shock.  
• Do not place any combustion appliance in a place where it is directly  
exposed to the wind of air conditioner, otherwise it may cause  
imperfect combustion.  
• If the air conditioner won’t be used for a considerably long time, turn  
off the main switch or the circuit breaker, for safety. Disconnect from  
the power supply prevents the unit from lightning and power supply  
surge.  
• Check the concrete blocks, etc. of the base of the outdoor unit  
occasionally.  
If the base is left damaged or deteriorated, the unit may topple over  
and inflict an injury to a person as the worst case.  
• When cleaning the unit, make sure to turn off the main switch or the  
circuit breaker beforehand for preventing you from getting injured by  
the electric fan running inside. For details of cleaning method, refer to  
“Maintenance” on page 9.  
• Do not put anything on the outdoor unit nor step onto it. If you do so,  
it may not only topple over the unit but also injure yourself.  
To make the air conditioner operate in its original performance,  
operate it within the range of the operating temperature specified in  
the instructions.  
Otherwise it may cause a malfunction, or water leak from the unit.  
• Prevent any liquid from falling into the remote controller. Do not spill  
juice, water or any kind of liquid.  
80  
PARTS NAME  
Outdoor unit  
1
Air outlet - blows off hot air during cooling  
or cool air during heating  
2,3  
4
1
2
3
4
Power supply box - contains electrical parts  
Earth screw - in the electrical parts box  
Refrigerant line connections  
Indoor unit  
1
2
3
4
5
6
7
8
9
10  
Room temperature sensor  
10 2 4 3 1  
Front panel  
Air inlet grille  
Air filter  
MODE FAN TEMP.  
F
C
A N  
UNIT STANDBY  
FILTER  
C
HECK  
A
D
D
R
E
S
S
2
O O L 1  
PREHEAT  
DEFROST  
Air outlet  
H
E AT  
A
U
T
O
L
O
U
V
E
R
L
FIX CENTRAL  
M
A
N
UA  
MODE  
Horizontal air flow louver  
Vertical air flow louver  
Display panel  
FILTER CHECK  
ON/OFF  
5 9  
6 8 7  
Infrared signal receiver  
Remote controller  
NAME AND FUNCTIONS OF INDICATORS AND CONTROLS  
Display panel  
The operating conditions are indicated below.  
1
2
3
4
5
AUTO (green)  
AUTO  
PRE.DEF.  
FILTER  
TIMER OPERATION  
PRE. DEF. lamp (orange)  
FILTER lamp (orange)  
TIMER lamp (yellow)  
1 2 3 4 5  
OPERATION lamp (green/*orange)  
The operation lamp flash rapidly (five times per second),  
when safety protection feature come into operation.  
When the auto restart function is in operation, the  
OPERATION lamp is orange.  
*
TEMPORARY button  
If you misplace or lose the remote controller or its batteries are  
exhausted, push the TEMPORARY button.  
1
2
Open the air inlet grille to push theTEMPORARY button.  
Push theTEMPORARY button to start the air conditioner.  
Push this button once again to stop it.  
TEMPORARY button  
3
Continue to push the button for 10 seconds to start cooling  
operation.  
81  
NAME AND OPERATIONS OF INDICATORS AND CONTROLS  
Display section  
All display items are shown in the figure below for purpose  
of explanation.  
Only selected items are displayed in actual operation.  
(All indicators are displayed for the explanation.)  
The displayed contents differ according to shape or type.  
1 2 3  
4
5
8
6 7  
1
2
3
CHECK  
7
8
CENTRAL control display  
Displayed during check mode.  
Displayed when used with the central remote  
controller, etc.  
Set up temperature display  
STANDBY display  
The selected set up temp. is displayed.  
It is displayed when the operation cannot be  
performed though it is not an error.  
Unit display  
Unit No. in which error/fault is displayed in the  
set up temp. display section.  
FILTER display  
If “FILTER” is displayed, clean the air filter.  
4
5
Operation mode display  
PREHEAT/DEFROST display  
The selected operation mode is displayed.  
Displayed when heating operation or defrost  
operation starts.  
Fan mode display  
The selected fan mode is displayed.  
LOUVER display  
It is displayed while the discharge louver  
operates in AUTO mode.  
(LOW)  
(MED.)  
(HIGH)  
LOUVER/MANUAL display  
It is not displayed on this model.  
6
Air volume fix display  
This is not displayed on this model.  
82  
Operation section  
Push each button to select a desired operation.  
1
2
3
Operation select button  
6
Operation lamp  
Selects desired operation mode.  
Lamp is lit during the operation.  
Lamp is off when stopped.  
Air volume select button  
Although it flashes when power switch is turned  
on or when turned on again after power failure, it  
goes on if the operation has started.  
Selects the desired air volume mode  
Set up temp. button  
Adjusts the required room temperature.  
Match to the desired set temperature by  
7
8
Louver operation button  
With auto louver function, the discharge louver  
operates or stops during operation of air condi-  
tioner.  
pushing  
.
4
5
Filter reset button  
ON/OFF button  
Resets (Erases) “FILTER” display.  
When the button is pushed, the operation starts,  
and it stops by pushing the button again.  
CHECK button  
When an error/fault occurs on the air  
conditioner, this button is used to check the  
check code indicating fault status.  
When the operation has stopped, the operation  
lamp and louver display disappear though other  
displays remain as they are.  
“Central indication”  
When using a remote controller connected to a central remote controller, etc., contents which can be operated by  
the standard remote controller and “CENTRALdisplay change by setting at the central remote controller.  
Setup on central  
remote controller  
“CENTRALdisplay on  
standard remote controller  
Contents operated by standard remote controller  
Last-push priority  
(No display)  
Operated from both standard remote controller and central  
remote controller, and operated with contents specified later.  
Goes off  
Center  
Goes on  
Flashes  
ON / OFF only can be operated.  
Cannot be operated.  
Operation inhibit  
For application control using other “Weekly timer” or “Central remote controller” other than this standard  
remote controller, refer to the Manual attached to each remote controller.  
83  
CORRECT USAGE  
When you use the air conditioner at the first time or when you change the setup value, follow the procedure  
below. From the next time, the operation displayed on the remote controller will start only by pushing ON /  
OFF button.  
Preparation  
Turn on the power switch.  
• The operation lamp (Red) flashes.  
REQUIREMENT  
• While using the air conditioner, operate it only with ON/OFF button without turning off the power switch.  
• When starting the operation after stop for a long time, turn on the power switch for 12 hours or more  
before start. (This is required because it is necessary to turn on the compressor case heater for heating  
in order to prevent overload on the compressor when activating the outdoor unit.)  
1
2
Select an operation mode withMODE” button.  
FAN  
COOL  
HEAT  
For every push of the button, the display changes as  
right figure :  
Select air volume with theFAN” button.  
The display changes as follows :  
MODE FAN TEMP.  
LOW  
MED.  
HIGH  
AUTO  
F A N  
CHECK A D D R E S S UNIT STANDBY  
C O O L 1 2  
FILTER  
PREHEAT  
DEFROST  
H E AT AU TO  
LOUVER  
CENTRAL MANUAL  
FIX  
• When air volume is “AUTO”, air volume changes according to  
the room temperature.  
MODE  
3
4
Determine the set up temperature by pushing theTEMP.”  
button.  
CK  
FILTE1 2 3  
PushON/OFF” button.  
The operation lamp goes on, and the operation starts .  
ON/OFF  
STOP  
Push “ON/OFF” button.  
4
The operation lamp goes off, and the operation stops.  
NOTE  
In cooling  
• When the operation button is pushed, the operation starts approx. 1minute after.  
In heating  
• When pushing “ON/OFF” button, the indoor fan starts pre-heating operation for 3 to 5 minutes before it  
starts blowing out hot air.  
• When the room temperature reaches the set up temperature and the outdoor unit stops, the mode  
becomes LOW and air volume decreases accordingly. During defrost operation, the fan stops so that  
cool air is not out, and “PREHEAT” and “DEFROST” are displayed.  
When restarting the operation after stop  
• In heating operation, the fan operation may continue for approx. 30 second.  
• When restarting the operation immediately after stop, the air conditioner does not operate for approx. 3  
minutes to protect the machine.  
84  
DRY OPERATION  
Start  
1
2
3
START/STOP button  
Push this button to start the air conditioner.  
Mode select button (MODE)  
MODE FAN TEMP.  
Select DRY.  
F A N  
CHECK A D D R E S S UNIT STANDBY  
FILTER  
C O O L 1 2  
PREHEAT  
DEFROST  
LOUVER  
H E AT AU TO  
Temperature button  
FIX  
CENTRAL MANUAL  
Set the desired temperature.  
MODE  
2
3
• The FAN speed display indicates AUTO  
FILTER CHECK  
• The OPERATION lamp (green) on the switch panel of the remote  
controller lights, and operation starts after approximately 3 minutes.  
ON/OFF  
Stop  
1
START/STOP button  
Push this button again to stop the air conditioner.  
AUTOMATIC OPERATION (Auto Changeover)  
When you set the air conditioner in A mode or switch over from AUTO operation  
because of some settings change, it will automatically select either cooling,  
heating, or fan only operation depending on the outdoor temperature.  
MODE FAN TEMP.  
F A N  
CHECK A D D R E S S UNIT STANDBY  
FILTER  
Start  
C O O L 1 2  
PREHEAT  
DEFROST  
H E AT AU TO  
LOUVER  
1
2
3
START/STOP button  
FIX  
CENTRAL MANUAL  
Push this button to start the air conditioner.  
MODE  
2
3
Mode select button (MODE)  
FILTER CHECK  
Select Auto.  
Temperature button  
ON/OFF  
Set the desired temperature.  
1
• In case of cooling, it starts the operation after approx. 1 minute.  
• In case of heating, the operation mode is selected in accordance with the  
room temperature and operation starts after approximately 3 to 5 minutes.  
• When you select the Auto mode, it is unnecessary to set the fan speed.  
The FAN speed display will show AUTO and the fan speed will be automatically controlled.  
• If the Auto mode is uncomfortable, you can select the desired conditions manually.  
Stop  
START/STOP button  
Push this button again to stop the air conditioner.  
85  
ADJUSTING AIR FLOW DIRECTION  
• Adjust the air flow direction properly. Otherwise, it might cause  
discomfort and make the room temperature uneven.  
• Adjust the vertical air flow using the remote controller.  
• Adjust the horizontal air flow manually.  
Adjust the vertical air flow  
The air conditioner automatically adjusts the vertical air flow direction  
in accordance with the operating conditions.  
To set the air flow direction by yourself  
Perform this adjustment when the air conditioner is in operation.  
Push the LOUVER button once on the remote controller.  
The louver starts to swing. When the desired louver position is  
reached in the swing, push the LOUVER button again and  
louver will stop at desired position.  
To automatically swing the air flow direction  
Perform this function when the air conditioner is in operation.  
Push the LOUVER button on the remote controller.  
To stop the function, push the LOUVER button again.  
CAUTION  
• Do not operate the air conditioner for prolonged periods of time with the air flow direction set downward  
during cooling operation.  
• Do not move the vertical air flow louver manually. Always use the LOUVER button.  
If you move the louver manually, it may malfuction during operation.  
If the louver malfunctions, stop the air conditioner once, and restart.  
Adjust the horizontal air flow  
Preparation :  
Take hold of the lever on the horizontal air flow louver and move them to adjust the air flow direction as you  
desire.  
You can adjust the air flow at the left, center, and right locations of the grilles.  
HOWTHE AIR CONDITIONER WORKS  
Automatic operation  
• The air conditioner selects and operates a mode from the cooling, the heating, or the fan only operations,  
depending on the outdoor temperature.  
• If the AUTO mode is uncomfortable, you can select the desired conditions manually.  
Outdoor temperature in operation  
Operating condition  
Outdoor temperature 22°C or more  
(in case the outdoor is hot)  
Cooling  
operation  
Performs the cooling operation at a temperature 1°C  
higher than the setting.  
Performs the fan only operation (low speed) while  
monitoring the outdoor temperature. When the room  
temperature changes, the air conditioner will select  
the cooling or heating mode.  
Fan only  
operation  
Outdoor temperature 20°C to 22°C  
The set temperature less than 20°C  
(in case the outdoor is cold)  
Heating  
operation  
Performs the heating operation at a temperature 1°C  
lower than the setting.  
86  
HINTS FOR ECONOMICAL OPERATION  
1. Clean air filters  
Air flow and performance are reduced if the air filters become blocked.  
Clean them every 2 weeks..  
2. Never open doors and windows more often than necessary  
To keep cool or warm air in the room, never open doors and windows more often than necessary.  
3. Use the timer effectively  
Set the timer for the desired operating time.  
4. Allow uniform circulation of room air  
Adjust the air flow direction for the even circulation of room air.  
TEMPORARY OPERATION  
TEMPORARY operation  
This function is used to operate the unit temporally in case you  
misplace the remote controller or its batteries are exhausted.  
• Push the TEMPORARY button to start the air conditioner.  
• While the substitute operation is set, the remote controller  
operation is disabled.  
• Continue to push the button for 10 seconds to start cooling  
operation.  
Air filter reset  
TEMPORARY button  
When the FILTER lamp on the air conditioner is indicated, it is time  
for cleaning. (The lamp will start to indicate, after every 1000 hours  
of operation.)  
• The FILTER lamp will be out when the TEMPORARY button is pushed.  
• The FILTER lamp will also be out when the FILTER button on the remote controller is pushed.  
MAINTENANCE  
WARNING  
Before you clean the air conditioner be sure to turn off the circuit breaker or main power switch.  
Cleaning of indoor unit and remote controller  
CAUTION  
• Use a dry cloth to wipe the indoor unit and remote controller.  
• A cloth dampened with cold water may be used on the indoor unit if it is very dirty.  
• Never use a damp cloth on the remote controller.  
• Do not use a chemically-treated duster for wiping or leave such materials on the unit for long. It may  
damage or fade the surface of the unit.  
• Do not use benzine, thinner, polishing powder, or similar solvents for cleaning. These may cause the  
plastic surface to crack or deform.  
If the air conditioner is not to be used for more than one month  
1. Operate the air conditioner in FAN ONLY mode for approximately 6 hours to dry inside the unit  
2. Stop the air conditioner and turn off the circuit breaker.  
3. Remove the batteries from the remote controller.  
87  
Check before operation  
CAUTION  
FAN ONLY Operation  
• Check that the air filters are installed.  
• Check that the air outlet or inlet of the outdoor unit is not blocked.  
Cleaning the air filter  
Air filter  
Clean the air filters every 2 weeks.  
If the air filters are covered with dust, the performance of the air  
conditioner will deteriorate.  
Clean the air filters as often as possible.  
1
2
Open the air inlet grille.  
Lift the air inlet grille up to the horizontal position.  
Take hold of the left and right handles of the air filter and lift  
it up slightly, then pull it downward to take it out from the  
filter holder.  
3
4
Remove the filters.  
Filter holder  
Use a vacuum cleaner to remove the dust from the filters or  
wash them with water. If you wash the air filters, dry them in  
the shade.  
5
6
Insert the upper portion of the air filter aligning right and left  
edges on the indoor unit until correctly positioned.  
Close the air inlet grille.  
* If the filter lamp on the indoor unit is indicated, push the FILTER  
button on the remote controller or the TEMPORARY button on  
the indoor unit to turn off the lamp.  
Filter holder  
88  
Cleaning the air inlet grille  
1. Remove the air inlet grille.  
Hold the both sides of the air inlet grille and open  
upward.  
Move the center arm to the left and remove the grille.  
2. Wash it with water using a soft sponge or towel.  
(Do not use metallic scrubbing brush or other hard  
brushes.)  
• Use of such hard objects will cause scratches on the  
surface of the air inlet grille, and the coating to peel  
off.  
• If very dirty, clean the air inlet grille with a neutral  
detergent, and rinse it off with water after removing it  
from the unit.  
3. Wipe out water from the air inlet grille and dry.  
4. Fit the left and right arms of the air inlet grille to the  
shafts on the two sides of the air conditioner and push in  
completely, and then push in the center arm.  
5. Check that the center arm has been completely inserted  
and close the air inlet grille.  
• Push the arrow locations (four) at the bottom of the air  
inlet grille to check whether the grille is completely  
closed.  
AIR CONDITIONER OPERATIONS AND PERFORMANCE  
3 minute protection function  
A protection feature prevents the air conditioner from being activated for approximately 3 minutes when it is  
restarted immediately after operation or when the power supply switch is turned on. This will protect the  
machine.  
Heating operation characteristics  
Preheating operation  
The air conditioner will not deliver warm air immediately after it is started.  
Warm air flows out after approximately 5-minutes when the indoor heat exchanger warms up.  
(The PRE.-DEF. lamp is on during the preheating operation.)  
Warm air control  
When the room temperature reaches the set temperature, the indoor fan speed is automatically reduced to  
prevent cold draft.  
The outdoor unit will stop.  
Defrosting  
If the outdoor unit is frosted during heating operation, defrosting is started automatically (for approximately 5  
to 10 minutes). To maintain the heating effect, the PRE.-DEF. lamp is on.  
• The fans on the indoor and outdoor units stop during the defrost operation.  
• During defrost operation, defrosted water drains from the bottom plate of the outdoor unit.  
89  
Heating capacity  
If the outdoor temperature is too low, it is recommended that additional heating appliances be used in con-  
junction with the air conditioner.  
Power failure  
Power failure during operation will stop the unit completely.  
• The OPERATION lamp (green) on the indoor unit will start flashing when power is restored.  
To restart operation, push the START/STOP button on the remote controller.  
Air conditioner operating conditions  
For proper performance, operate the air conditioner in the following temperature conditions:  
Cooling  
Outdoor temperature  
Room temperature  
: –5°C to 43°C  
: 18°C to 32°C  
operation  
CAUTION Room relative humidity – less than 80 %. If the air conditioner operates  
in excess of this figure, the surface of the air conditioner may cause dewing.  
Heating  
Outdoor temperature  
Room temperature  
: –15°C to 21°C  
: Less than 30°C  
operation  
If air conditioner is used outside of the above conditions, safety protection may work.  
PROBLEMS AND CAUSES  
CAUTION  
If any of the following conditions occur, turn off the main power supply switch and immediately contact the  
dealer :  
• The indicator lamps flash at short intervals (5 Hz) even though you have tried turning off the power  
supply and turning on again after 2 to 3 minutes.  
• Switch operation is erratic.  
• The main power fuse often blows out, or the circuit breaker is often activated.  
• A foreign matter or water has fallen into the inside of the air conditioner.  
• Any other unusual condition is observed.  
Before you ask for servicing or repairs, check the following points.  
Recheck  
Inoperative  
• The main power switch is turned off.  
• The circuit breaker is activated to cut off power supply.  
• The main power fuse is blown.  
• ON timer is set.  
Does not cool well or heat well  
• The air inlet or outlet of the outdoor unit is blocked.  
• Doors or windows are opened.  
• The air filter is blocked with dust.  
• The louver is not at the correct position.  
• The fan speed is set too low.  
• The set temperature is too high. (In cooling operation)  
• The set temperature is too low. (In heating operation)  
90  
Accessory parts and Parts to be procured locally  
r Accessory parts  
Part name  
Q’ty  
Shape  
Part name  
Q’ty  
Shape  
Mounting screw  
Ø4mm x 25mm  
Installation plate  
1
8
Installation Manual  
Owner’s Manual  
1
1
Pattern paper  
1
1
Service contact  
address label  
<Separate sold parts>  
Part name  
Q’ty  
Shape  
STANDBY  
FILTER  
F
A
N
CHECK  
COOL  
Y
PRE-HEA  
T
D
R
DEFROST  
LOUVER  
MANUAL  
HEAT AUTO  
AUTO  
CENTRAL  
Wired remote  
controller  
F
I
X
TEMP.  
1
FAN SPEED  
LOUVER  
r Parts to be procured locally  
Connecting pipe (Liquid side)  
Connecting cable  
(6.35mm (diam.), Nominal (diam.) 1/4” thick 0.8mm)  
RAV-SM560KRT-E, RAV-SM560AT-E  
H07RN-F or 245IEC66 (1.0mm² or more)  
(9.52mm (diam.), Nominal (diam.) 3/8” thick 0.8mm)  
RAV-SM800KRT-E, RAV-SM800AT-E  
Thermal insulation for refrigerant pipe  
(10mm or more, thermal insulating foam polyethylene)  
Connecting pipe (Gas side)  
(12.7mm (diam.), Nominal (diam.) 1/2” thick 0.8mm)  
RAV-SM560KRT-E, RAV-SM560AT-E  
Thermal insulation for drain pipe  
(10mm or more, foam polyethylene)  
(15.9mm (diam.), Nominal (diam.) 5/8” thick 1.0mm)  
RAV-SM800KRT-E, RAV-SM800AT-E  
Drain pipe (Outer 26mm (diam.))  
Tapes  
Power supply cord  
2.5mm² (H07RN-F or 245IEC66) or 3.5mm² (AWG-12)  
Grounding cable (2.0mm (diam.) or more)  
91  
1
PRECAUTIONS FOR SAFETY  
Ensure that all Local, National and International regulations are satisfied.  
Read this PRECAUTIONS FOR SAFETYcarefully before Installation.  
The precautions described below include the important items regarding safety. Observe them without fail.  
After the installation work, perform a trial operation to check for any problem.  
Follow the Owners Manual to explain how to use and maintain the unit to the customer.  
Turn off the main power supply switch (or breaker) before the unit maintenance.  
Ask the customer to keep the Installation Manual together with the Owners Manual.  
CAUTION  
New Refrigerant Air Conditioner Installation  
• THIS AIR CONDITIONER ADOPTS THE NEW HFC REFRIGERANT (R410A) WHICH DOES NOT  
DESTROY OZONE LAYER.  
The characteristics of R410A refrigerant are ; easy to absorb water, oxidizing membrane or oil, and its pressure  
is approx. 1.6 times higher than that of refrigerant R22. Accompanied with the new refrigerant, refrigerating oil  
has also been changed. Therefore, during installation work, be sure that water, dust, former refrigerant, or  
refrigerating oil does not enter the refrigerating cycle.  
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging  
port of the main unit and installation tools are charged from those for the conventional refrigerant.  
Accordingly the exclusive tools are required for the new refrigerant (R410A).  
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does  
not enter. Moreover, do not use the existing piping because there are problems with pressure-resistance force  
and impurity in it.  
CAUTION  
To Disconnect the Appliance from Main Power Supply.  
This appliance must be connected to the main power supply by means of a switch with a contact separation of  
at least 3 mm.  
The installation fuse (25A D type  
) must be used for the power supply line of this conditioner.  
WARNING  
• Ask an authorized dealer or qualified installation professional to install/maintain the air  
conditioner.  
Inappropriate installation may result in water leakage, electric shock or fire.  
• Turn off the main power supply switch or breaker before attempting any electrical work.  
Make sure all power switches are off. Failure to do so may cause electric shock.  
• Connect the connecting cable correctly.  
If the connecting cable is connected in a wrong way, electric parts may be damaged.  
• When moving the air conditioner for the installation into another place, be very careful not  
to enter any gaseous matter other than the specified refrigerant into the refrigeration cycle.  
If air or any other gas is mixed in the refrigerant, the gas pressure in the refrigeration cycle becomes  
abnormally high and it may resultingly causes pipe burst and injuries on persons.  
• Do not modify this unit by removing any of the safety guards or by by-passing any of the  
safety interlock switches.  
• Exposure of unit to water or other moisture before installation may cause a short-circuit of  
electrical parts.  
Do not store it in a wet basement or expose to rain or water.  
92  
1
PRECAUTIONS FOR SAFETY  
• After unpacking the unit, examine it carefully if there are possible damage.  
• Do not install in a place that might increase the vibration of the unit.  
• To avoid personal injury (with sharp edges), be careful when handling parts.  
• Perform installation work properly according to the Installation Manual.  
Inappropriate installation may result in water leakage, electric shock or fire.  
• When the air conditioner is installed in a small room, provide appropriate measures to  
ensure that the concentration of refrigerant leakage occur in the room does not exceed the  
critical level.  
• Install the air conditioner securely in a location where the base can sustain the weight  
adequately.  
• Perform the specified installation work to guard against an earthquake.  
If the air conditioner is not installed appropriately, accidents may occur due to the falling unit.  
• If refrigerant gas has leaked during the installation work, ventilate the room immediately.  
If the leaked refrigerant gas comes in contact with fire, noxious gas may generate.  
• After the installation work, confirm that refrigerant gas does not leak.  
If refrigerant gas leaks into the room and flows near a fire source, such as a cooking range, noxious gas might  
generate.  
• Electrical work must be performed by a qualified electrician in accordance with the  
Installation Manual. Make sure the air conditioner uses an exclusive power supply.  
An insufficient power supply capacity or inappropriate installation may cause fire.  
• Use the specified cables for wiring connect the terminals securely fix. To prevent external  
forces applied to the terminals from affecting the terminals.  
• Be sure to provide grounding.  
Do not connect ground wires to gas pipes, water pipes, lightning rods or ground wires for telephone cables.  
• Conform to the regulations of the local electric company when wiring the power supply.  
Inappropriate grounding may cause electric shock.  
• Do not install the air conditioner in a location subject to a risk of exposure to a combustible  
gas.  
If a combustible gas leaks, and stays around the unit, a fire may occur.  
93  
2
INSTALLATION PROCEDURE  
Installation Diagram of Indoor Unit  
Insulate the refrigerant pipes  
For rear left and side pipe exit  
separately with insulation, not together.  
Hook  
Wall  
1
Installation  
plate  
Hook  
Insert the cushion between the  
indoor unit and wall, and lift indoor  
unit to make work easier.  
Min. 6 mm thick heat resisting polyethylene foam  
The auxiliary piping can be connected  
the left, rear left, rear, right or bottom.  
Do not allow the drain hose to sag.  
Cut the piping hole  
sloped slightly  
Right  
Rear  
Pipe  
insulation  
Left  
Make sure to run the drain hose  
sloped downward.  
Bottom  
Rear left  
Mounting screw  
Hook  
Mounting the Installation Plate  
55  
65  
For installation of the indoor unit,  
use the paper template included.  
Installation  
plate  
170  
120  
80  
1
0 100  
8
0
m
m
00  
1
m
m
00  
1
Indoor unit  
Weight  
Hook  
Mounting screw Pipe hole  
Hook  
Indoor unit Thread  
Pipe hole  
When the installation plate is directly mounted on the wall  
1. Securely fix the installation plate to the wall by screwing it through the upper and lower fixing holes.  
2. To mount the installation plate on a concrete wall with anchor bolts, utilize the anchor bolt holes as illustrated in  
the above figure.  
3. Attach the installation plate horizontally to the wall.  
CAUTION  
When installing the installation plate with mounting screw, do not use the anchor bolt hole.  
Otherwise the unit may fall down and result in personal injury and property damage.  
Ø5mm hole  
Anchor bolt  
Mounting screw  
Ø4 x 25mm  
Projection  
15mm or less  
Clip anchor  
(local parts)  
94  
3
SELECTION OF INSTALLATION PLACE  
WARNING  
• Install the air conditioner where there is sufficient strength to withstand the weight of the unit.  
If the strength is not sufficient, the unit may fall down resulting in injury.  
CAUTION  
Upon approval of the customer, install the air conditioner in a place that satisfies the  
following conditions.  
Place where the unit can be installed horizontally.  
Place where a sufficient servicing space can be ensured for safe maintenance and check.  
Place where drained water will not cause any problem.  
Avoid installing in the following places.  
Place exposed to air with high salt content (seaside area), or place exposed to large quantities of sulfide gas  
(hot spring). (Should the unit be used in these places, special protective measures are needed.)  
Place exposed to oil, vapor, oil smoke or corrosive gas.  
Place where organic solvent is used nearby.  
Place close to a machine generating high frequency.  
Place where the discharged air blows directly into the window of the neighboring house. (For outdoor unit)  
Place where noise of the outdoor unit is easy to transmit.  
(When installing the air conditioner on the boundary with the neighbor, pay due attention to the level of noise.)  
Place with poor ventilation.  
Where the ceiling height is more than 3m.  
Where the floor/wall/ceiling structure is unable to support the weight of the unit.  
4
INSTALLATION OF INDOOR UNIT  
WARNING  
• Install the air conditioner certainly at a place to sufficiently withstand the weight.  
If the strength is insufficient, the unit may fall down resulting in human injury.  
• Perform a specified installation work to guard against an earthquake.  
An incomplete installation can cause accidents by the units falling and dropping.  
Locate the unit so as to provide uniform circulation of chilled air.  
Avoid locating the unit as shown in the bad-marked figures below :  
Good location  
Bad location  
Bad location  
Evenly hot or cooled  
Shaded area well hot or cooled  
Shaded area well hot or cooled  
If a good location is not possible, use a fan to circulate the air evenly throughout the room.  
95  
5
DRAIN PIPING WORK  
Piping and Drain Hose Installation  
In case of right-side exit  
Cut out the knockout portion by the slits with a knife  
or pair of wire cutters as necessary.  
Slit  
(Body right)  
In case of downward pipe exit  
• Cut out the knockout portion by the slits with a knife  
or pair of wire cutters as necessary.  
Slit  
(Body right)  
Piping via left-hand connection  
Bend the connecting pipe so that it is laid within 43mm above the wall surface. If the connecting pipe is laid  
exceeding 43mm above the wall surface, the indoor unit could be unstable when set on the wall. When bending the  
connecting pipes, always use a suitable bending tool to avoid damaging the pipes.  
Bend the connection pipe within a radius of 30mm.  
To connect the pipe after installation of unit (figure)  
(To the front of the flare)  
465mm  
Liquid side  
365mm  
Gas side  
Outward form  
of indoor unit  
R 30mm  
Use the handle of a screwdriver, etc.  
NOTE :  
If the pipe is bent incorrectly, the indoor unit could be unstable on the wall.  
After passing the connecting pipe through the pipe hole, connect the connecting pipe to the auxiliary pipes and  
insulate as necessary.  
96  
5
DRAIN PIPING WORK  
CAUTION  
• Bind the auxiliary pipes (two) and connecting cable with tape tightly. In case of left-side pipe exit and rear-left  
exit, bind the auxiliary pipes (two) only with facing tape.  
Indoor unit  
Auxiliary pipes  
Connecting cable  
Drain hose  
Installation plate  
Carefully arrange pipes so that any pipe does not stick out of the rear plate of the indoor unit.  
Carefully connect the auxiliary pipes and connecting pipes to each other and cut off the insulating tape wound  
on the connecting pipe to avoid double-taping at the joint, then seal the joint with vinyl tape, etc.  
In order to reduce the possibility of condensed water being produced within the indoor unit, make sure to  
insulate both the connecting pipes.  
(Use a suitable form of insulation material specifically design designed for refrigeration pipe work.)  
When bending a pipe, ensure care is taken to prevent pipe damage.  
Drainage  
1. Run the drain hose sloped downwards.  
Do not rise the drain hose.  
Do not form the drain hose  
into the waved shape.  
50 mm  
or more  
Do not put the  
drain hose end  
into water.  
Do not put the drain  
hose end into the  
drainage ditch.  
2. It is not possible to add water to the drain pan to  
confirm correct drainage. To do this, the unit must be  
operated in the COOL mode.  
Pipe insulation  
3. When connecting extension drain hose, insulate the  
connecting part of extension drain hose with pipe  
insulation.  
Drain hose Inside the room  
Extension drain hose  
CAUTION  
Arrange the drain pipe to allow proper drainage from the unit. Incorrect drainage can result in condensation  
problems.  
This structure of this air conditioner is designed  
condensed water, which may form on the back of the  
indoor unit, into the drain pan.  
Wall  
Drain  
guide  
Therefore, do not store the power cables and other parts  
within the drain guide.  
Space for  
pipes  
97  
6
REFRIGERANT PIPING  
Refrigerant Piping  
1. If the outdoor units are to be mounted on a wall, make sure that the platform supporting is sufficiently strong.  
The platform should be designed and manufactured to maintain its strength over a long period of time, and  
sufficient consideration should be given to ensuring that the outdoor unit will not fall.  
2. Use copper pipe with 0.8 mm or more thickness.  
3. Flare nut and flare works are also different from those of the conventional refrigerant.  
Take out the flare nut attached to the main unit of the air conditioner, and use it.  
CAUTION  
IMPORTANT 4 POINTS FOR PIPING WORK  
1. Take away dust and moisture from the inside of the connecting pipes.  
2. Tight connection (between pipes and unit)  
3. Evacuate the air in the connecting pipes using VACUUM PUMP.  
4. Check the gas leakage. (Connected points)  
Permissible Piping Length and Head  
The maximum piping length from the outdoor to indoor unit  
The maximum height difference outdoor/indoor unit  
Outdoor unit is above  
Outdoor unit is below  
30 m (Without charge 20m)  
(RAV-SM560AT-E)  
50 m (Without charge 20m)  
(RAV-SM800AT-E)  
30m  
15m  
Flaring  
B
Insert a flare nut into the pipe, and flare the pipe.  
As the flaring sizes of R410A differ from those of refrigerant R22, the flare  
tools newly manufactured for R410A are recommended.  
However, the conventional tools can be used by adjusting projection margin  
of the copper pipe.  
• Projection margin in flaring : B (Unit : mm)  
Imperial (Wing nut type)  
Rigid (Clutch type)  
R410A tool used  
R410A R22  
Conventional tool used  
Outer diam. of copper pipe  
R410A  
R22  
Outer diam. of  
copper pipe  
R410A  
R22  
6.35  
9.52  
12.7  
1.5 to 2.0  
1.5 to 2.0  
2.0 to 2.5  
1.0 to 1.5  
1.0 to 1.5  
1.5 to 2.0  
6.35  
9.52  
12.7  
0 to 0.5 (Same as left) 1.0 to 1.5  
0 to 0.5 (Same as left) 1.0 to 1.5  
0 to 0.5 (Same as left) 1.0 to 1.5  
0.5 to 1.0  
0.5 to 1.0  
0.5 to 1.0  
In the case of flaring for R410A with the conventional  
flare tool, pull out it approx. 0.5 mm more than that for  
R22 to adjust to the specified flare size.  
• Flaring dia meter size : A (Unit : mm)  
*
A +0  
-
0.4  
Outer diam. of copper pipe  
The copper pipe gauge is useful  
R410A  
9.1  
R22  
9.0  
A
for adjusting projection margin size.  
6.35  
9.52  
12.7  
13.2  
16.6  
13.0  
16.2  
98  
6
REFRIGERANT PIPING  
• Tightening torque of flare pipe connections  
Tightening connection  
Pressure of R410A becomes higher than that of R22.  
(Approx. 1.6 times) Therefore, using a torque  
wrench, tighten firmly the flare pipe connecting  
sections which connect the indoor and outdoor units  
up to the specified tightening torque.  
Align the centers of the connecting pipes and tighten  
the flare nut as far as possible with your fingers. Then  
tighten the nut with a spanner and torque wrench as  
shown in the figure.  
Incorrect connections may cause not only a gas  
leakage, but also a trouble of the refrigeration cycle  
or compressor damage.  
CAUTION  
Do not apply excess torque. Otherwise, the nut  
may crack depending on the conditions.  
Flare at  
indoor unit side  
(Unit : Nm)  
Outer diam. of copper pipe  
6.35 mm (diam.)  
Tightening torque  
14 to 18 (1.4 to 1.8 kgfm)  
33 to 42 (3.3 to 4.2 kgfm)  
50 to 62 (5.0 to 6.2 kgfm)  
63 to 77 (6.3 to 7.7 kgfm)  
9.52 mm (diam.)  
Flare at  
outdoor unit side  
12.7 mm (diam.)  
15.9 mm (diam.)  
Half union  
Flare nut  
Internally  
Externally  
threaded side  
threaded side  
Use a wrench to secure.  
Use a torque wrench to tighten.  
7
EVACUATING  
3. Open fully the low pressure side handle of the  
gauge manifold valve.  
AIR PURGE  
Evacuate the air in the connecting pipes and in the  
4. Operate the vacuum pump to start for evacuating.  
indoor unit using vacuum pump.  
Do not use the refrigerant in the outdoor unit.  
For details, see the manual of vacuum pump.  
Perform evacuating for about 35 minutes if the  
piping length is total 30 meters for model SM560  
and 50 meters for model SM800.  
(assuming a pump capacity of 27 liters per minute.)  
Then confirm that the compound pressure gauge  
reading is 101 kPa ( 76 cmHg).  
Use a vacuum pump  
5. Close the low pressure side valve handle of gauge  
manifold.  
Be sure to use a vacuum pump with counter-flow  
prevention function so that inside oil of the pump does  
not flow backward into pipes of the air conditioner  
when the pump stops.  
6. Open fully the valve stem of the packed valves  
(both sides of Gas and Liquid).  
1. Connect the charge hose from the manifold valve to  
the service port of the gas side packed valve.  
7. Remove the charging hose from the service port.  
8. Securely tighten the caps on the packed valves.  
2. Connect the charge hose to the port of vacuum  
pump.  
99  
<For RAV-SM560AT-E model>  
Packed valve handling precautions  
Open the valve stem all the way out ; do not try to  
open it beyond the stopper.  
Compound pressure gauge  
Pressure gauge  
Securely tighten the valve stem cap in torque as  
follows:  
101kPa  
(76cmHg)  
Manifold valve  
Gas side (12.7 mm (diam.))  
Gas side (9.52 mm (diam.))  
50 to 62 Nm (5.0 to 6.2 kgfm)  
Handle Lo  
Handle Hi  
(Keep fully closed)  
33 to 42 Nm (3.3 to 4.2 kgfm)  
Charge hose  
(For R410A only)  
Charge hose  
(For R410A only)  
Liquid side (6.35 mm (diam.)) 14 to 18 Nm (1.4 to 1.8 kgfm)  
Service port  
14 to 18 Nm (1.4 to 1.8 kgfm)  
Vacuum pump adapter  
for counter-flow prevention  
(For R410A only)  
Hexagonal wrench is required.  
Vacuum  
pump  
Packed valve (Gas side)  
Service port (Valve core (Setting pin))  
Flare nut  
Valve unit  
<For RAV-SM800AT-E model>  
Stopper  
Charge cap  
As shown in the figure, be sure to use a double  
spanner to loosen or tighten the flare nut of the valve  
at gas side. If using a single spanner, the nut cannot  
be tightened with necessary tightening torque.  
Charge port  
Valve rod  
On the contrary, use a single spanner to loosen or  
tighten the flare nut of the valve at liquid side.  
Cover  
<For RAV-SM800AT-E model>  
Cap  
Compound pressure gauge  
Pressure gauge  
Piping valve  
101kPa  
(76cmHg)  
Manifold valve  
Loosened  
Tightened  
Handle Lo  
Handle Hi  
(Keep fully closed)  
Charge hose  
(For R410A only)  
Flare nut  
Charge hose  
(For R410A only)  
Service port  
(Valve core (Setting pin))  
Vacuum pump adapter  
for counter-flow prevention  
(For R410A only)  
SM800 type valve at gas side  
Vacuum  
pump  
Cover  
Packed valve at gas side  
Do not put the spanner or  
torque wrench, etc. on  
the cover.  
The valve may be broken.  
100  
7
EVACUATING  
Valve unit  
Valve handling precautions  
Open the valve stem or the handle until it strikes  
the stopper. It is unnecessary to apply further  
force.  
Handle  
Securely tighten the cap with a torque wrench.  
Pull out the handle and  
using cutting pliers, etc.  
turn it counterclockwise  
by 90˚. (Open fully)  
Cap tightening torque  
Ø6.4  
Ø9.5  
14 to 18Nm (1.4 to 1.8kgfm)  
33 to 42Nm (3.3 to 4.2kgfm)  
33 to 42Nm (3.3 to 4.2kgfm)  
20 to 25Nm (2.0 to 2.5kgfm)  
14 to 18Nm (1.4 to 1.8kgfm)  
Charge port  
Flare nut  
Valve unit  
Valve  
size  
Ø12.7  
Ø15.9  
Charge port  
Push in handle.  
Additional refrigerant  
1. The amount of refrigerant put into the outdoor unit  
at the factory is sufficient to fill up to 20m of  
refrigerant piping work.  
Charge port  
Flare nut  
2. If the length of the refrigerant piping work is 20m or  
less, addition of refrigerant at the installation site is  
unnecessary.  
Handle position  
3. If the length of the piping work exceeds 20m, extra  
refrigerant must be added. Refer to the outdoor  
installation manual for details of the extra amounts.  
4. Overcharge or undercharge of refrigerant in the  
outdoor unit may cause malfunction of the  
compressor.  
Add Only R410A Refrigerant to These Units  
Handle  
Opened fully  
Closed completely  
Heat insulation  
1. Provide heat insulation on the refrigerant piping on  
both the liquid side and gas side separately, and  
ensure that all joints in the insulation are compleatly  
sealed (without gap).  
1. Use the vacuum pump, vacuum pump adapters,  
and gauge manifold referring to the manuals  
attached to each tool before using them. For the  
vacuum pump, check oil is filled up to the specified  
line of the oil gauge.  
*
2. Since the temperature of the piping on the gas side  
increases during heating operations, the heat  
insulating material used must be able to withstand  
temperatures of more than 120°C.  
2. While the air is purged, check again that the  
connecting port of charge hose, which has a  
projection to push the valve core, is firmly con-  
nected to the charge port.  
*
3. Use the pipe insulation supplied in the accessory  
pack to insulate the piping connecting section on  
the indoor unit side.  
101  
8
ELECTRICAL WORK  
For the air conditioner that has no power cord.  
Wiring between units  
NOTE:  
1. Connect the wires between the units correctly.  
Errors made in the connections can result in the  
unit malfunctioning.  
For selection and connection method of the power  
supply cords, refer to the details in the Installation  
Manual of the outdoor unit.  
2. Connect the control wires between the outdoor unit  
and indoor unit as shown in the figure below :  
CAUTIONS  
Wiring connections  
If incorrect/incomplete wiring is carried out, it  
may cause an electrical fire or smoke.  
Prepare the power supply for exclusive use with  
the air conditioner.  
Air inter  
grille  
Be sure to use the cord clamps specified  
positions with attached to the product.  
Front panel  
Do not damage or scratch the conductive core  
and inner insulator of power and inter-connecting  
cables when peeling them.  
2
1
Be sure to comply with local cords on running  
the wire from outdoor unit to indoor unit (size of  
wire and wiring method etc.)  
Cord clamp  
Terminal cover  
Earth line  
Use the power cord and Inter-connecting cable  
with specified thickness, specified type, and  
protective devices specified.  
Screw  
Connecting  
cable  
Screw  
How to wire  
1. Connect the connecting cable to the terminal as  
identified with their respective matched numbers on  
the terminal block of indoor and outdoor unit.  
H07 RN-F or 245 IEC 66 (1.0 mm2 or more)  
2. Insulate the unsheathed redundant cords  
(conductors) with electrical insulation tape.  
Process them so that they do not touch any  
electrical or metal parts.  
3. For inter-unit wiring, do not use a cut wire jointed to  
another on the way.  
10  
1
2
3
10  
3
2
1
60  
50  
Earth line  
Connecting  
cable  
102  
8
ELECTRICAL WORK  
Installation of Remote Controllers  
Remote Controller Cabling  
Cabling diagram  
Precautions  
1. Low-voltage circuit provision is used for remote  
controller communication, and as such, the remote  
controller cable is subject to the low-power circuit  
provision of internal wiring regulations and therefore  
it cannot be brought into direct contact with a high-  
voltage AC power line, or housed in the same  
conduit tube as a power line.  
Terminal block  
for remote controller  
cabling of indoor unit  
Remote  
controller unit  
or sensor part  
A
B
C
A
B
C
Remote controller cable  
(Local procure)  
Flush wall mounting  
Feed the 3-core cable (obtained locally) though the  
back of the remote controller and then connect to the  
ABC terminals.  
For details of cabling/installation of the remote  
controller, refer to the Installation Manual packaged  
in the remote controller.  
Attach the remote controller to the wall using two  
suitable mounting screws (obtained locally).  
3-core cable,  
obtained locally  
Mounting screws (x 2)  
obtained locally  
Wall surface mounting  
Attach the remote controller to the wall using two  
suitable mounting screws (obtained locally).  
Connect the 3-core cable (obtained locally) to the  
ABC terminals.  
Make a U-shaped cut-out in the center of the top  
edge of the decorative cover and pass the 3-core  
cable though the cut-out.  
3-core cable,  
obtained locally  
Mounting screws (x 2)  
obtained locally  
103  
9
IMPROVING SYSTEM EFFICIENCY  
Air flow direction adjustment  
1. To improve the effects of cooling and heating, use the outlet louver appropriately for cooling and heating  
operations. When in cooling operation the most efficient louver position will be horizontal and when in heating  
operation the optimum louver position is downwards.  
Increasing heating effect  
1. One method increase the warming effect is to fit an additional means of re-circulating the warmed air from the  
upper part of the room :  
2. However if the warming effect of the air conditioner is not good owing to the installation position or the structure of  
the room, then reset the room temperature regulator as follows to raise the temperature of the room. Adjust  
position 1 and 2 on DIP switch SW03 located on the indoor P.C. board, according to the table below :  
Position 1 : ON Position 1 : OFF Position 1 : OFF  
Dip switch SW03  
position 1 & 2  
Position 2 : OFF Position 2 : ON Position 2 : OFF  
Temperature increased Factory pre-set +2°C  
+4°C  
Options  
Test operation  
To switch the TEST RUN (COOL) mode, push TEMPORARY button for 10  
seconds. (The beeper will make a short beep.)  
TEMPORARY button  
10  
FINAL INSTALLATION CHECKS  
Precautions  
Check and Test Operation  
1. Ensure that the electrical cable used for  
power supply and control of the system is  
unable to come into contact with either  
service valves or piping work which are not  
insulated.  
Pressure of R410A is approx. 1.6 times of that of R22.  
If installation work is incompletely finished, a gas leakage  
may occur at the cases such as pressure rise during  
operation.  
Therefore, be sure to test the piping connections for leakage.  
Check the flare nut connections, valve stem cap  
connections and service port cap fittings  
for gas leak with a leak detector or soap water.  
Electrical wiring  
1. When installation is complete, check that all  
power supply and interconnecting wiring has  
been appropriately protected.  
Piping cover  
Refrigerant piping  
Cord clamp  
Flare nut  
Indoor/outdoor  
connections  
1. When refrigerant and drain piping have been  
completed. Ensure that all pipework is fully  
insulated and apply finishing tape to seal the  
insulation.  
connecting cables  
(Indoor unit)  
Power cable  
Valve  
cover  
104  
10  
FINAL INSTALLATION CHECKS  
Self-Diagnosis by LED Indication  
Useful Functions (SM800AT-E only)  
In addition to the code checking by remote controller of the indoor unit, troubles of the outdoor unit can be diagnosed by LED  
indications on the cycle control P.C. board of the outdoor unit. Utilize them for various checks.  
For the check by remote controller of the indoor unit, refer to the Installation Manual of the indoor unit.  
Before a check, confirm each bit of the DIP switch is set to OFF position.  
LED indication and code checking  
Cycle control P.C. board  
DIP switch  
LED indication  
Cause  
Heat exchanger sensor (TE) error  
SW800  
D800 D801 D802 D803  
¡
l
¡
l
l
¡
¡
l
¡
l
¥
l
¥
l
¥
l
l
l
l
¡
¡
¡
¡
l
¡
¡
l
l
¥
¥
l
l
l
¡
l
¡
l
l
l
¡
l
¡
l
¡
l
l
l
¥
¥
l
l
l
l
l
¡
l
l
¡
l
¡
¡
l
l
l
l
l
¥
¡
Suction sensor (TS) error  
Discharge sensor (TD) error  
High-pressure protection error  
Outdoor temperature sensor (TO) error  
DC outside fan error  
LED  
indication  
D800  
: Red  
¡
Communication error between IPDU  
Discharge temp. error  
D801  
: Yellow  
¡
ON  
EEPROM error  
D802  
: Yellow  
¡
Communication error between IPDU  
G-Tr short-circuit protection  
1
2
3
4
D803  
: Yellow  
¡
Detect circuit error  
Current sensor error  
Comp. lock error  
: Rapid flash  
: Go off  
Comp. break down  
¥
l
¡
Phase missing detection, Detection of coming-off of CT current sensor  
Serial communication error by thermo. operation of Comp. case  
: Go on  
Changes in the product and components  
Installation/ServicingTools  
In the case of an air conditioner using R410A, in order to prevent any other refrigerant from being charged accidentally, service  
port diameter of the outdoor unit control valve (3 way valve) has been changed. (1/2 UNF 20 threads per inch)  
In order to increase the pressure resisting strength of the refrigerant piping flare processing diameter and size of opposite  
side of flare nuts has been changed. (for copper pipes with nominal dimensions 1/2 and 5/8)  
New tools for R410A  
New tools for R410A  
Applicable to R22 model  
Changes  
As pressure is high, it is impossible to measure by means of conventional  
gauge. In order to prevent any other refrigerant from being charged, each  
port diameter is changed.  
Gauge manifold  
×
In order to increase pressure resisting strength, hose materials and port  
size are changed (to 1/2 UNF 20 threads per inch).  
When purchasing a charge hose, be sure to check the port size.  
Charge hose  
×
Electronic balance  
for refrigerant charging  
As pressure is high and gasification speed is fast, it is difficult to read the  
indicated value by means of charging cylinder, as air bubbles occur.  
¡
Torque wrench  
The size of opposite sides of flare nuts have been increased. Incidentally,  
a common wrench is used for nominal diameters 1/4 and 3/8.  
×
¡
(nominal diam. 1/2, 5/8)  
Flare tool  
(clutch type)  
By increasing the clamp bars receiving hole, strength of spring in the tool  
has been improved.  
Gauge for projection adjustment  
Used when flare is made with using conventional flare tool.  
Connected to the conventional vacuum pump. It is necessary to use an  
adapter to prevent vacuum pump oil from flowing back to the charge hose.  
The charge hose connecting part has two ports-one for conventional  
refrigerant (7/16 UNF 20 threads per inch) and one for R410A.  
If the vacuum pump oil (mineral) mixes with R410A a sludge may occur  
and damage the equipment.  
Vacuum pump adapter  
¡
Gas leakage detector  
Exclusive for HFC refrigerant.  
×
Incidentally, the refrigerant cylindercomes with the refrigerant designation (R410A) and protector coating in the U,S.s ARI  
specified rose color (ARI color code: PMS 507).  
Also, the charge port and packing for refrigerant cylinderrequire 1/2 UNF 20 threads per inch corresponding to the charge  
hoses port size.  
105  
11  
ENVIRONMENT  
Environmental Issues  
Product maintenance  
1. To minimize the chances of environmental damage and to ensure the efficient operation of the unit, it is  
recommended to have the air conditioner periodically checked and serviced by a qualified engineer.  
Product disposal  
1. Please dispose of the air conditioner unit in an environmentally responsible manner.  
Recycling is the preferred disposal method.  
2. When disposing of an air conditioner system, contact either the manufacture, your local environmental control  
authority or a local waste disposal company for advice.  
3. Ensure all packing material is either recycled or disposed of in accordance with local regulations.  
4. The refrigerant gas within the unit should only be removed by an authorized company.  
WARNING  
Discharge of refrigerant to atmosphere is illegal and may lead to prosecution.  
106  

Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Muz D30na User Manual
Panasonic Kx Tg9150e User Manual
Ricoh Aficio Dsm627 User Manual
Samsung Aq24a1 2 Rc User Manual
Samsung Mh Fm User Manual
Samsung Us07a5 A6 Ma User Manual
Toshiba Multifunctional Digital Systems 225 User Manual
Toshiba Printer 351c User Manual
Trane Air Conditioner Series R Air Cooled Helical Rotary Liquid Chillers User Manual
Trion Air Boss Dc 88 User Manual