Toshiba Air Conditioner Rav Sm1404bt E User Manual

FILE NO. A10-031  
SERVICE MANUAL  
SPLIT TYPE  
INDOOR UNIT <DIGITAL INVERTER>  
Compact 4-way CassetteType  
RAV-SM404MUT-E RAV-SM404MUT-TR  
RAV-SM454MUT-E RAV-SM454MUT-TR  
RAV-SM564MUT-E RAV-SM564MUT-TR  
Concealed DuctType  
RAV-SM564BT-E  
RAV-SM804BT-E  
RAV-SM1104BT-E  
RAV-SM1404BT-E  
RAV-SM564BT-TR  
RAV-SM804BT-TR  
RAV-SM1104BT-TR  
RAV-SM1404BT-TR  
CeilingType  
RAV-SM564CT-E  
RAV-SM804CT-E  
RAV-SM1104CT-E  
RAV-SM1404CT-E  
RAV-SM564CT-TR  
RAV-SM804CT-TR  
RAV-SM1104CT-TR  
RAV-SM1404CT-TR  
R410A  
PRINTED IN JAPAN, Apr., 2011 ToMo  
6. TROUBLESHOOTING .............................................................................. 42  
6-1. Summary ofTroubleshooting........................................................................... 42  
6-2. Check Code List (Indoor) ................................................................................. 47  
6-3. Diagnostic Procedure for Each Check Code (Indoor Unit)............................ 52  
7. REPLACEMENT OF SERVICE P.C. BOARD ........................................... 64  
7-1. Indoort Unit ....................................................................................................... 64  
8. SETUP AT LOCAL SITE AND OTHERS .................................................. 68  
8-1. Indoor Unit......................................................................................................... 68  
8-2. Setup at Local Site / Others ............................................................................. 78  
8-3. How to Set up Central Control Address Number ........................................... 80  
9. ADDRESS SETUP.................................................................................... 82  
9-1. Address Setup .................................................................................................. 82  
9-2. Address Setup & Group Control...................................................................... 83  
9-3. Address Setup (Manual Setting from Remote Controller)............................. 86  
9-4. Confirmation of Indoor Unit No. Position ....................................................... 87  
10. DETACHMENTS ....................................................................................... 88  
10-1. Compact 4-Way CassetteType ........................................................................ 88  
10-2. Concealed DuctType ........................................................................................ 97  
10-3. CeilingType ..................................................................................................... 100  
11. EXPLODED VIEWS AND PARTS LIST .................................................. 104  
11-1. Compact 4-way CassetteType ....................................................................... 104  
11-2. Concealed DuctType ...................................................................................... 108  
11-3. CeilingType ..................................................................................................... 115  
– 3 –  
Original instruction  
Please read carefully through these instructions that contain important information which complies with the  
“Machinery” Directive (Directive 2006/42/EC), and ensure that you understand them.  
Generic Denomination: Air Conditioner  
Definition of Qualified Installer or Qualified Service Person  
The air conditioner must be installed, maintained, repaired and removed by a qualified installer or qualified  
service person.  
When any of these jobs is to be done, ask a qualified installer or qualified service person to do them for you.  
A qualified installer or qualified service person is an agent who has the qualifications and knowledge  
described in the table below.  
Agent  
Qualifications and knowledge which the agent must have  
Qualified  
installer (1)  
• The qualified installer is a person who installs, maintains, relocates and removes the air  
conditioners made by Toshiba Carrier Corporation.  
He or she has been trained to install, maintain, relocate and remove the air conditioners made by  
Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such operations by  
an individual or individuals who have been trained and is thus thoroughly acquainted with the  
knowledge related to these operations.  
• The qualified installer who is allowed to do the electrical work involved in installation, relocation  
and removal has the qualifications pertaining to this electrical work as stipulated by the local laws  
and regulations, and he or she is a person who has been trained in matters relating to electrical  
work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she has  
been instructed in such matters by an individual or individuals who have been trained and is thus  
thoroughly acquainted with the knowledge related to this work.  
• The qualified installer who is allowed to do the refrigerant handling and piping work involved in  
installation, relocation and removal has the qualifications pertaining to this refrigerant handling  
and piping work as stipulated by the local laws and regulations, and he or she is a person who  
has been trained in matters relating to refrigerant handling and piping work on the air conditioners  
made by Toshiba Carrier Corporation or, alternatively, he or she has been instructed in such  
matters by an individual or individuals who have been trained and is thus thoroughly acquainted  
with the knowledge related to this work.  
• The qualified installer who is allowed to work at heights has been trained in matters relating to  
working at heights with the air conditioners made by Toshiba Carrier Corporation or, alternatively,  
he or she has been instructed in such matters by an individual or individuals who have been  
trained and is thus thoroughly acquainted with the knowledge related to this work.  
Qualified service • The qualified service person is a person who installs, repairs, maintains, relocates and removes  
the air conditioners made by Toshiba Carrier Corporation. He or she has been trained to install,  
repair, maintain, relocate and remove the air conditioners made by Toshiba Carrier Corporation or,  
alternatively, he or she has been instructed in such operations by an individual or individuals who  
have been trained and is thus thoroughly acquainted with the knowledge related to these operations.  
person (1)  
• The qualified service person who is allowed to do the electrical work involved in installation,  
repair, relocation and removal has the qualifications pertaining to this electrical work as stipulated  
by the local laws and regulations, and he or she is a person who has been trained in matters  
relating to electrical work on the air conditioners made by Toshiba Carrier Corporation or,  
alternatively, he or she has been instructed in such matters by an individual or individuals who  
have been trained and is thus thoroughly acquainted with the knowledge related to this work.  
• The qualified service person who is allowed to do the refrigerant handling and piping work  
involved in installation, repair, relocation and removal has the qualifications pertaining to this  
refrigerant handling and piping work as stipulated by the local laws and regulations, and he or  
she is a person who has been trained in matters relating to refrigerant handling and piping  
work on the air conditioners made by Toshiba Carrier Corporation or, alternatively, he or she  
has been instructed in such matters by an individual or individuals who have been trained  
and is thus thoroughly acquainted with the knowledge related to this work.  
• The qualified service person who is allowed to work at heights has been trained in matters  
relating to working at heights with the air conditioners made by Toshiba Carrier Corporation or,  
alternatively, he or she has been instructed in such matters by an individual or individuals who  
have been trained and is thus thoroughly acquainted with the knowledge related to this work.  
– 4 –  
Definition of Protective Gear  
When the air conditioner is to be transported, installed, maintained, repaired or removed, wear protective  
gloves and ‘safety’ work clothing.  
In addition to such normal protective gear, wear the protective gear described below when undertaking the  
special work detailed in the table below.  
Failure to wear the proper protective gear is dangerous because you will be more susceptible to injury, burns,  
electric shocks and other injuries.  
Work undertaken  
All types of work  
Protective gear worn  
Protective gloves  
“Safety” working clothing  
Gloves to provide protection for electricians and from heat  
Insulating shoes  
Electrical-related work  
Clothing to provide protection from electric shock  
Work done at heights (50 cm or more)  
Transportation of heavy objects  
Repair of outdoor unit  
Helmets for use in industry  
Shoes with additional protective toe cap  
Gloves to provide protection for electricians and from heat  
The important contents concerned to the safety are described on the product itself and on this Service Manual.  
Please read this Service Manual after understanding the described items thoroughly in the following contents  
(Indications/Illustrated marks), and keep them.  
[Explanation of indications]  
Indication  
Explanation  
Indicates contents assumed that an imminent danger causing a death or serious injury of  
the repair engineers and the third parties when an incorrect work has been executed.  
DANGER  
Indicates possibilities assumed that a danger causing a death or serious injury of the  
repair engineers, the third parties, and the users due to troubles of the product after work  
when an incorrect work has been executed.  
WARNING  
CAUTION  
Indicates contents assumed that an injury or property damage () may be caused on the  
repair engineers, the third parties, and the users due to troubles of the product after work  
when an incorrect work has been executed.  
Property damage : Enlarged damage concerned to property, furniture, and domestic animal/pet  
[Explanation of illustrated marks]  
Mark  
Explanation  
Indicates prohibited items (Forbidden items to do)  
The sentences near an illustrated mark describe the concrete prohibited contents.  
Indicates mandatory items (Compulsory items to do)  
The sentences near an illustrated mark describe the concrete mandatory contents.  
Indicates cautions (Including danger/warning)  
The sentences or illustration near or in an illustrated mark describe the concrete cautious contents.  
– 5 –  
Warning Indications on the Air Conditioner Unit  
[Confirmation of warning label on the main unit]  
Confirm that labels are indicated on the specified positions  
If removing the label during parts replace, stick it as the original.  
Warning indication  
Description  
WARNING  
WARNING  
ELECTRICAL SHOCK HAZARD  
Disconnect all remote electric power supplies  
before servicing.  
ELECTRICAL SHOCK HAZARD  
Disconnect all remote electric  
power supplies before servicing.  
WARNING  
WARNING  
Moving parts.  
Do not operate unit with grille removed.  
Stop the unit before the servicing.  
Moving parts.  
Do not operate unit with grille removed.  
Stop the unit before the servicing.  
CAUTION  
CAUTION  
High temperature parts.  
You might get burned when removing this panel.  
High temperature parts.  
You might get burned when removing  
this panel.  
CAUTION  
CAUTION  
Do not touch the aluminum fins of the unit.  
Doing so may result in injury.  
Do not touch the aluminum fins of the unit.  
Doing so may result in injury.  
CAUTION  
CAUTION  
BURST HAZARD  
Open the service valves before the operation,  
otherwise there might be the burst.  
BURST HAZARD  
Open the service valves before the  
operation, otherwise there might be the  
burst.  
– 6 –  
Precaution for Safety  
The manufacturer shall not assume any liability for the damage caused by not observing the description of this  
manual.  
WARNING  
Before starting to repair the air conditioner, read carefully through the Service Manual, and repair  
the air conditioner by following its instructions.  
Only qualified service person (1) is allowed to repair the air conditioner.  
Repair of the air conditioner by unqualified person may give rise to a fire, electric shocks, injury,  
water leaks and/or other problems.  
Only a qualified installer (1) or qualified service person (1) is allowed to carry out the electrical  
work of the air conditioner.  
Under no circumstances must this work be done by an unqualified individual since failure to carry  
out the work properly may result in electric shocks and/or electrical leaks.  
Wear protective gloves and safety work clothing during installation, servicing and removal.  
When connecting the electrical wires, repairing the electrical parts or undertaking other electrical  
jobs, wear gloves to provide protection for electricians and from heat, insulating shoes and  
clothing to provide protection from electric shocks.  
Failure to wear this protective gear may result in electric shocks.  
Use wiring that meets the specifications in the Installation Manual and the stipulations in the local  
regulations and laws. Use of wiring which does not meet the specifications may give rise to  
electric shocks, electrical leakage, smoking and/or a fire.  
Only a qualified installer (1) or qualified service person (1) is allowed to undertake work at heights  
using a stand of 50 cm or more or to remove the intake grille of the indoor unit to undertake work.  
General  
When working at heights, use a ladder which complies with the ISO 14122 standard, and follow  
the procedure in the ladder’s instructions.  
Also wear a helmet for use in industry as protective gear to undertake the work.  
When working at heights, put a sign in place so that no-one will approach the work location,  
before proceeding with the work.  
Parts and other objects may fall from above, possibly injuring a person below.  
Do not touch the aluminum fin of the outdoor unit.  
You may injure yourself if you do so. If the fin must be touched for some reason, first put on  
protective gloves and safety work clothing, and then proceed.  
Do not climb onto or place objects on top of the outdoor unit.  
You may fall or the objects may fall off of the outdoor unit and result in injury.  
When transporting the air conditioner, wear shoes with additional protective toe caps.  
When transporting the air conditioner, do not take hold of the bands around the packing carton.  
You may injure yourself if the bands should break.  
This air conditioner has passed the pressure test as specified in IEC 60335-2-40 Annex EE.  
DENGER  
Before carrying out the installation, maintenance, repair or removal work, be sure to set the circuit  
breaker to the OFF position. Otherwise, electric shocks may result.  
Before opening the intake grille of the indoor unit or service panel of the outdoor unit, set the  
circuit breaker to the OFF position. Failure to set the circuit breaker to the OFF position may result  
in electric shocks through contact with the interior parts.  
Only a qualified installer (1) or qualified service person (1) is allowed to remove the intake grille  
of the indoor unit or service panel of the outdoor unit and do the work required.  
Turn off  
Before starting to repair the outdoor unit fan or fan guard, be absolutely sure to set the circuit  
breaker.  
breaker to the OFF position, and place a “Work in progress” sign on the circuit breaker.  
When cleaning the filter or other parts of the indoor unit, set the circuit breaker to OFF without  
fail, and place a “Work in progress” sign near the circuit breaker before proceeding with the work.  
– 7 –  
Even if the circuit breaker has been set to the OFF position before the service panel is removed  
and the electrical parts are repaired, you will still risk receiving an electric shock.  
For this reason, short-circuit the high-voltage capacitor terminals to discharge the voltage before  
proceeding with the repair work.  
For details on the short-circuiting procedure, refer to the Service Manual.  
You may receive an electric shock if the voltage stored in the capacitors has not been sufficiently  
discharged.  
Execute  
discharge  
between  
terminals.  
Place a “Work in progress” sign near the circuit breaker while the installation, maintenance, repair  
or removal work is being carried out.  
There is a danger of electric shocks if the circuit breaker is set to ON by mistake.  
Prohibition  
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the  
electrical parts with the electrical parts box cover of one or more of the indoor units and the  
service panel of the outdoor unit removed in order to find out exactly where the trouble lies, wear  
insulated heat-resistant gloves, insulated boots and insulated work overalls, and take care to  
avoid touching any live parts.  
You may receive an electric shock if you fail to heed this warning. Only qualified service person  
(1) is allowed to do this kind of work.  
Stay on  
protection  
WARNING  
Before troubleshooting or repair work, check the earth wire is connected to the earth terminals of  
the main unit, otherwise an electric shock is caused when a leak occurs.If the earth wire is not  
correctly connected, contact an electric engineer for rework.  
After completing the repair or relocation work, check that the ground wires are connected properly.  
Check earth  
wires.  
Be sure to connect earth wire. (Grounding work) Incomplete grounding causes an electric shock.  
Do not connect ground wires to gas pipes, water pipes, and lightning rods or ground wires for  
telephone wires.  
Do not modify the products.Do not also disassemble or modify the parts.  
It may cause a fire, electric shock or injury.  
Prohibition of  
modification.  
When any of the electrical parts are to be replaced, ensure that the replacement parts satisfy the  
specifications given in the Service Manual (or use the parts contained on the parts list in the  
Service Manual).  
Use specified Use of any parts which do not satisfy the required specifications may give rise to electric shocks,  
parts.  
smoking and/or a fire.  
If, in the course of carrying out repairs, it becomes absolutely necessary to check out the  
electrical parts with the electrical parts box cover of one or more of the indoor units and the  
service panel of the outdoor unit removed in order to find out exactly where the trouble lies, place  
"Keep out" signs around the work site before proceeding.  
Do not bring  
a child close to  
Third-party individuals may enter the work site and receive electric shocks if this warning is not  
the equipment. heeded.  
Connect the cut-off lead wires with crimp contact, etc, put the closed end side upward and then  
apply a water-cut method, otherwise a leak or production of fire is caused at the users’ side.  
Insulating  
measures  
When performing repairs using a gas burner, replace the refrigerant with nitrogen gas because  
the oil that coats the pipes may otherwise burn.  
When repairing the refrigerating cycle, take the following measures.  
1) Be attentive to fire around the cycle.  
When using a gas stove, etc, be sure to put out fire before work; otherwise the oil mixed with  
refrigerant gas may catch fire.  
2) Do not use a welder in the closed room.  
No fire  
When using it without ventilation, carbon monoxide poisoning may be caused.  
3) Do not bring inflammables close to the refrigerant cycle, otherwise fire of the welder may catch  
the inflammables.  
– 8 –  
The refrigerant used by this air conditioner is the R410A.  
Check the used refrigerant name and use tools and materials of the parts which match with it.  
For the products which use R410A refrigerant, the refrigerant name is indicated at a position on  
the outdoor unit where is easy to see.  
To prevent miss-charging, the route of the service port is changed from one of the former R22.  
Do not use any refrigerant different from the one specified for complement or replacement.  
Otherwise, abnormally high pressure may be generated in the refrigeration cycle, which may  
result in a failure or explosion of the product or an injury to your body.  
For an air conditioner which uses R410A, never use other refrigerant than R410A.  
For an air conditioner which uses other refrigerant (R22, etc.), never use R410A.  
If different types of refrigerant are mixed, abnormal high pressure generates in the refrigerating  
cycle and an injury due to breakage may be caused.  
Do not charge refrigerant additionally.  
If charging refrigerant additionally when refrigerant gas leaks, the refrigerant composition in the  
refrigerating cycle changes resulted in change of air conditioner characteristics or refrigerant over  
the specified standard amount is charged and an abnormal high pressure is applied to the inside  
of the refrigerating cycle resulted in cause of breakage or injury.  
Therefore if the refrigerant gas leaks, recover the refrigerant in the air conditioner, execute  
vacuuming, and then newly recharge the specified amount of liquid refrigerant.  
In this time, never charge the refrigerant over the specified amount.  
Refrigerant  
When recharging the refrigerant in the refrigerating cycle, do not mix the refrigerant or air other  
than R410A into the specified refrigerant.  
If air or others is mixed with the refrigerant, abnormal high pressure generates in the refrigerating  
cycle resulted in cause of injury due to breakage.  
After installation work, check the refrigerant gas does not leak.  
If the refrigerant gas leaks in the room, poisonous gas generates when gas touches to fire such  
as fan heater, stove or cocking stove though the refrigerant gas itself is innocuous.  
Never recover the refrigerant into the outdoor unit.  
When the equipment is moved or repaired, be sure to recover the refrigerant with recovering device.  
The refrigerant cannot be recovered in the outdoor unit; otherwise a serious accident such as  
breakage or injury is caused.  
After repair work, surely assemble the disassembled parts, and connect and lead the removed  
wires as before.  
Perform the work so that the cabinet or panel does not catch the inner wires.  
If incorrect assembly or incorrect wire connection was done, a disaster such as a leak or fire is  
caused at user’s side.  
Assembly/  
Cabling  
After the work has finished, be sure to use an insulation tester set (500V Megger) to check the  
resistance is 1MΩ or more between the charge section and the non-charge metal section  
(Earth position).  
Insulator  
check  
If the resistance value is low, a disaster such as a leak or electric shock is caused at user’s side.  
When the refrigerant gas leaks during work, execute ventilation.  
If the refrigerant gas touches to a fire, poisonous gas generates.  
A case of leakage of the refrigerant and the closed room full with gas is dangerous because a  
shortage of oxygen occurs. Be sure to execute ventilation.  
Ventilation  
When the refrigerant gas leaks, find up the leaked position and repair it surely.  
If the leaked position cannot be found up and the repair work is interrupted, pump-down and  
tighten the service valve, otherwise the refrigerant gas may leak into the room.  
The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove  
though the refrigerant gas itself is innocuous.  
When installing equipment which includes a large amount of charged refrigerant such as a multi  
air conditioner in a sub-room, it is necessary that the density does not the limit even if the  
refrigerant leaks.  
If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.  
Tighten the flare nut with a torque wrench in the specified manner.  
Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may  
result in refrigerant leakage.  
Compulsion  
Nitrogen gas must be used for the airtight test.  
The charge hose must be connected in such a way that it is not slack.  
For the installation/moving/reinstallation work, follow to the Installation Manual.  
If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or  
fire is caused.  
– 9 –  
Once the repair work has been completed, check for refrigerant leaks, and check the insulation  
resistance and water drainage.  
Then perform a trial run to check that the air conditioner is running properly.  
After repair work has finished, check there is no trouble. If check is not executed, a fire, electric  
shock or injury may be caused. For a check, turn off the power breaker.  
Check after  
repair  
After repair work (installation of front panel and cabinet) has finished, execute a test run to check  
there is no generation of smoke or abnormal sound.  
If check is not executed, a fire or an electric shock is caused. Before test run, install the front  
panel and cabinet.  
Check the following matters before a test run after repairing piping.  
• Connect the pipes surely and there is no leak of refrigerant.  
• The valve is opened.  
Running the compressor under condition that the valve closes causes an abnormal high  
pressure resulted in damage of the parts of the compressor and etc. and moreover if there is  
leak of refrigerant at connecting section of pipes, the air is suctioned and causes further  
abnormal high pressure resulted in burst or injury.  
Do not  
operate the  
unit with the  
valve closed.  
Only a qualified installer (1) or qualified service person (1) is allowed to relocate the air  
conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual  
since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.  
Check the following items after reinstallation.  
1) The earth wire is correctly connected.  
2) The power cord is not caught in the product.  
3) There is no inclination or unsteadiness and the installation is stable.  
If check is not executed, a fire, an electric shock or an injury is caused.  
Check after  
reinstallation  
When carrying out the pump-down work shut down the compressor before disconnecting the  
refrigerant pipe.  
Disconnecting the refrigerant pipe with the service valve left open and the compressor still  
operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to  
an abnormally high level, and possibly resulting in reputing, injury, etc.  
When the service panel of the outdoor unit is to be opened in order for the compressor or the  
area around this part to be repaired immediately after the air conditioner has been shut down, set  
the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the  
service panel.  
If you fail to heed this warning, you will run the risk of burning yourself because the compressor  
pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair  
work, wear the kind of insulated heat-resistant gloves designed to protect electricians.  
When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor,  
Cooling check inverter or the areas around these parts to be repaired immediately after the air conditioner has  
been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes  
before opening the service panel.  
If you fail to heed this warning, you will run the risk of burning yourself because the fan motor,  
reactor, inverter heat sink and other parts will be very hot to the touch.  
In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant  
gloves designed to protect electricians.  
Only a qualified installer (1) or qualified service person (1) is allowed to install the air  
conditioner. If the air conditioner is installed by an unqualified individual, a fire, electric shocks,  
injury, water leakage, noise and/or vibration may result.  
Before starting to install the air conditioner, read carefully through the Installation Manual, and  
follow its instructions to install the air conditioner.  
Do not install the air conditioner in a location that may be subject to a risk of expire to a  
combustible gas.  
If a combustible gas leaks and becomes concentrated around the unit, a fire may occur.  
Install the indoor unit at least 2.5 m above the floor level since otherwise the users may injure  
themselves or receive electric shocks if they poke their fingers or other objects into the indoor unit  
while the air conditioner is running.  
Installation  
Install a circuit breaker that meets the specifications in the installation manual and the stipulations  
in the local regulations and laws.  
Install the circuit breaker where it can be easily accessed by the qualified service person (1).  
Do not place any combustion appliance in a place where it is directly exposed to the wind of air  
conditioner, otherwise it may cause imperfect combustion.  
– 10 –  
Explanations given to user  
• If you have discovered that the fan grille is damaged, do not approach the outdoor unit but set the circuit  
breaker to the OFF position, and contact a qualified service person to have the repairs done. Do not set the  
circuit breaker to the ON position until the repairs are completed.  
Relocation  
• Only a qualified installer (1) or qualified service person (1) is allowed to relocate the air conditioner.  
It is dangerous for the air conditioner to be relocated by an unqualified individual since a fire, electric shocks,  
injury, water leakage, noise and/or vibration may result.  
• When carrying out the pump-down work shut down the compressor before disconnecting the refrigerant pipe.  
Disconnecting the refrigerant pipe with the service valve left open and the compressor still operating will  
cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to an abnormally high level,  
and possibly resulting in reputing, injury, etc.  
(1) Refer to the “Definition of Qualified Installer or Qualified Service Person.”  
Declaration of Conformity  
Manufacturer:  
Toshiba Carrier Corporation  
336 Tadehara, Fuji-shi, Shizuoka-ken 416-8521 JAPAN  
Authorized  
Nick Ball  
Representative/TCF holder:  
Toshiba EMEA Engineering Director  
Toshiba Carrier UK Ltd.  
Porsham Close, Belliver Industrial Estate,  
PLYMOUTH, Devon, PL6 7DB.  
United Kingdom  
Hereby declares that the machinery described below:  
Generic Denomination:  
Model/type:  
Air Conditioner  
RAV-SM404MUT-E  
RAV-SM454MUT-E  
RAV-SM564MUT-E  
RAV-SM404MUT-TR  
RAV-SM454MUT-TR  
RAV-SM564MUT-TR  
RAV-SM564BT-E  
RAV-SM804BT-E  
RAV-SM1104BT-E  
RAV-SM1404BT-E  
RAV-SM564BT-TR  
RAV-SM804BT-TR  
RAV-SM1104BT-TR  
RAV-SM1404BT-TR  
RAV-SM564CT-E  
RAV-SM804CT-E  
RAV-SM1104CT-E  
RAV-SM1404CT-E  
RAV-SM564CT-TR  
RAV-SM804CT-TR  
RAV-SM1104CT-TR  
RAV-SM1404CT-TR  
Commercial name:  
Digital Inverter Series / Super Digital Inverter Series Air Conditioner  
Complies with the provisions of the “Machinery” Directive (Directive 2006/42/EC) and the regulations  
transposing into national law.  
Complies with the provisions of the following harmonized standard:  
EN 378-2: 2008 / A1: 2009  
Note: This declaration becomes invalid if technical or operational modifications are introduced without the  
manufacturer’s consent.  
– 11 –  
Specifications  
Sound power level (dBA)  
Weight (kg)  
Model  
Main unit (Ceiling panel)  
Cooling  
Heating  
RAV-SM404MUT-E  
RAV-SM454MUT-E  
RAV-SM564MUT-E  
RAV-SM404MUT-TR  
RAV-SM454MUT-TR  
RAV-SM564MUT-TR  
RAV-SM564BT-E  
16 (3)  
16 (3)  
16 (3)  
16 (3)  
16 (3)  
16 (3)  
30  
RAV-SM804BT-E  
39  
RAV-SM1104BT-E  
RAV-SM1404BT-E  
RAV-SM564BT-TR  
RAV-SM804BT-TR  
RAV-SM1104BT-TR  
RAV-SM1404BT-TR  
RAV-SM564CT-E  
54  
54  
30  
39  
54  
54  
21  
RAV-SM804CT-E  
25  
RAV-SM1104CT-E  
RAV-SM1404CT-E  
RAV-SM564CT-TR  
RAV-SM804CT-TR  
RAV-SM1104CT-TR  
RAV-SM1404CT-TR  
33  
33  
21  
25  
33  
33  
: Under 70 dBA  
• Other specifications than abovementioned models are equal to current models (2 series).  
– 12 –  
New Refrigerant (R410A)  
This air conditioner adopts a new HFC type refrigerant (R410A) which does not deplete the ozone layer.  
1. Safety Caution Concerned to New Refrigerant  
The pressure of R410A is high 1.6 times of that of the former refrigerant (R22).  
Accompanied with change of refrigerant, the refrigerating oil has been also changed.  
Therefore, be sure that water, dust, the former refrigerant or the former refrigerating oil is not mixed into the  
refrigerating cycle of the air conditioner with new refrigerant during installation work or service work.  
If an incorrect work or incorrect service is performed, there is a possibility to cause a serious accident.  
Use the tools and materials exclusive to R410A to purpose a safe work.  
2. Cautions on Installation/Service  
1) Do not mix the other refrigerant or refrigerating oil.  
For the tools exclusive to R410A, shapes of all the joints including the service port differ from those of  
the former refrigerant in order to prevent mixture of them.  
2) As the use pressure of the new refrigerant is high, use material thickness of the pipe and tools which are  
specified for R410A.  
3) In the installation time, use clean pipe materials and work with great attention so that water and others  
do not mix in because pipes are affected by impurities such as water, oxide scales, oil, etc.  
Use the clean pipes.  
Be sure to brazing with flowing nitrogen gas. (Never use gas other than nitrogen gas.)  
4) For the earth protection, use a vacuum pump for air purge.  
5) R410A refrigerant is azeotropic mixture type refrigerant.  
Therefore use liquid type to charge the refrigerant. (If using gas for charging, composition of the  
refrigerant changes and then characteristics of the air conditioner change.)  
3. Pipe Materials  
For the refrigerant pipes, copper pipe and joints are mainly used.  
It is necessary to select the most appropriate pipes to conform to the standard.  
Use clean material in which impurities adhere inside of pipe or joint to a minimum.  
1) Copper pipe  
<Piping>  
The pipe thickness, flare finishing size, flare nut and others differ according to a refrigerant type.  
When using a long copper pipe for R410A, it is recommended to select “Copper or copper-base pipe  
without seam” and one with bonded oil amount 40mg/10m or less.  
Also do not use crushed, deformed, discolored (especially inside) pipes.  
(Impurities cause clogging of expansion valves and capillary tubes.)  
<Flare nut>  
Use the flare nuts which are attached to the air conditioner unit.  
2) Joint  
The flare joint and socket joint are used for joints of the copper pipe.  
The joints are rarely used for installation of the air conditioner.  
However clear impurities when using them.  
– 13 –  
4. Tools  
1. Required Tools for R410A  
Mixing of different types of oil may cause a trouble such as generation of sludge, clogging of capillary,  
etc. Accordingly, the tools to be used are classified into the following three types.  
1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))  
2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)  
3) Tools commonly used for R410A and for conventional refrigerant (R22)  
The table below shows the tools exclusive for R410A and their interchangeability.  
Tools exclusive for R410A (The following tools for R410A are required.)  
Tools whose specifications are changed for R410A and their interchangeability  
R410A  
air conditioner installation  
Conventional air  
conditioner installation  
No.  
Used tool  
Usage  
Existence of  
new equipment  
for R410A  
Whether  
conventional equipment  
can be used  
Whether conventional  
equipment can be used  
Flare tool  
Pipe flaring  
Ye s  
Ye s  
Ye s  
Ye s  
(Note)  
(Note)  
N o  
Ye s  
(Note)  
No  

Copper pipe gauge  
for adjusting  
projection margin  
Flaring by  
conventional flare tool  
Torque wrench  
Gauge manifold  
Charge hose  
Tightening of flare nut  
ƒ
Evacuating, refrigerant  
charge, run check, etc.  
N o  
No  
Vacuum pump adapter Vacuum evacuating  
Ye s  
Ye s  
N o  
Ye s  
Ye s  
Electronic balance for  
Refrigerant charge  
refrigerant charging  
Ye s  
Refrigerant cylinder  
Leakage detector  
Refrigerant charge  
Gas leakage check  
Ye s  
Ye s  
N o  
N o  
No  
ˆ
Ye s  
(Note) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection  
margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.  
General tools (Conventional tools can be used.)  
In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary  
as the general tools.  
1) Vacuum pump. Use vacuum pump by  
attaching vacuum pump adapter.  
2) Torque wrench  
3) Pipe cutter  
7) Screwdriver (+, –)  
8) Spanner or Monkey wrench  
9) Hole core drill  
4) Reamer  
10) Hexagon wrench (Opposite side 4mm)  
11) Tape measure  
5) Pipe bender  
6) Level vial  
12) Metal saw  
Also prepare the following equipments for other installation method and run check.  
1) Clamp meter  
2) Thermometer  
3) Insulation resistance tester (Megger)  
4) Electroscope  
– 14 –  
1. AIR DUCTING WORK  
1-1. Static Pressure Characteristics  
Concealed Duct type  
RAV-SN564BT , RAV-SN804BT , RAV-SN1104BT , RAV-SN1404BT ∗  
Fig. 1 SM56 type (Round duct)  
Fig. 3 SM80 type (Round duct)  
Standard air volume 780m³/h  
Standard air volume 1140m³/h  
140  
120  
100  
80  
140  
120  
100  
80  
60  
60  
40  
40  
20  
20  
0
0
500  
700  
Air volume m³/h  
780  
900  
800  
1000  
1140 1200  
1300  
Air volume m³/h  
Fig. 2 SM56 type (Square duct)  
Fig. 4 SM80 type (Square duct)  
Standard air volume 780m³/h  
Standard air volume 1140m³/h  
140  
120  
140  
120  
100  
80  
108  
100  
80  
60  
40  
20  
0
60  
40  
20  
0
500  
700  
780  
900  
800  
1000  
1140 1200  
1300  
Air volume m³/h  
Air volume m³/h  
– 15 –  
Fig. 5 SM110 type (Round duct)  
Fig. 7 SM140 type (Round duct)  
Standard air volume 1620m³/h  
Standard air volume 1980m³/h  
140  
120  
100  
80  
140  
120  
100  
80  
60  
60  
40  
40  
20  
0
20  
0
1200  
1620  
1980  
2000  
1200  
1800  
2200  
2400  
Air volume m³/h  
Air volume m³/h  
Fig. 6 SM110 type (Square duct)  
Fig. 8 SM140 type (Square duct)  
Standard air volume 1620m³/h  
Standard air volume 1980m³/h  
140  
120  
100  
80  
140  
120  
100  
80  
60  
60  
40  
40  
20  
0
20  
0
1200  
1620  
1980  
2000  
1200  
1800  
2200  
2400  
Air volume m³/h  
Air volume hm³/h  
– 16 –  
2. CONSTRUCTION VIEWS (EXTERNAL VIEWS)  
2-1. Compact 4-way CassetteType  
RAV-SM404MUT , RAV-SM454MUT , RAV-SM564MUT  
595 to 660 Ceiling open dimension  
1000 or more  
Obustacle  
1000 or more  
Space required for  
installation and servicing  
142  
64  
368.5  
Knockout for flesh  
air intake Ø100  
268  
27  
Bottom face  
of ceiling  
220.5  
145.5  
93  
700 Panel external dimension  
Drain discharge port  
145.5  
134  
63  
595 to 660 Ceiling open dimension  
525 Hanging bolt pitch  
Hanging bolt  
M10 or W3/8  
local arrange  
Bottom face  
of ceiling  
105 70  
Ceiling panel  
Ø162  
Wiring  
connection  
port  
Ø162  
Refrigerant pipe  
(Liquid) Ø6.4  
320.5  
575 Unit external dimension  
Electric parts box  
55  
For branch duct knockout  
square hole Ø150  
70 105 93  
139.5  
For branch ductt  
knockout square  
hole Ø150  
190.5  
Refrigerant pipe  
(Gas) Ø12.7  
Bottom face of ceiling  
– 17 –  
2-2. Concealed DuctType  
RAV-SM564BT , RAV-SM804BT , RAV-SM1104BT , RAV-SM1404BT  
Refrigerant pipe connecting port  
(Gas side ØF)  
Drain pipe connecting port  
for vinyl chloride pipe  
(Inner dia. 32, VP. 25)  
Hanging bolt  
4-M10 screw  
Discharge port flange  
N-Ø200  
(Arranged locally)  
75  
Main unit dimension 800  
Hanging bolt pitch B  
41  
59  
Hanging bolt pitch 700  
Main unit dimension A  
J = M x K  
50  
638  
498  
393  
H
129  
Knock-out hole Ø125  
(Air take-in port)  
44  
49  
196  
Suction port  
flange  
(Separate sold)  
Refrigerant pipe  
connecting port  
(Liquid side ØG)  
6-Ø4 Tapping screw  
undersized hole Ø160  
Panel C.L  
410  
Ø26 Power supply,  
remote controller  
cable take-out port  
C
Suction port  
panel  
(Separate sold)  
Suction port canvas  
(Separate sold)  
Ceiling open size  
470  
Ceiling open size D  
Panel external  
dimension 500  
Panel external dimension E  
• Dimension  
A
B
C
D
E
F
G
H
J
K
M
1
N
2
3
O
SM56 type  
SM80 type  
700  
766  
690  
750  
780 12.7  
6.4  
9.5  
252  
252  
280  
580  
280  
290  
410  
410  
1000 1066  
990 1050 1080 15.9  
2
SM110 type  
SM140 type  
1350 1416 1340 1400 1430 15.9  
9.5  
252  
930  
310  
3
4
410  
Check port A  
450  
Plane view of main unit  
(Pipe side)  
NOTE 1 :  
For maintenance of the equipment, be sure to install  
a check port A at the position as shown below.  
100  
NOTE 2 :  
Using the drain up kit sold separately, drain-up by 300 (mm)  
from drain pipe draw-out port of the main unit is necessary.  
The drain-up over 300mm or more is impossible.  
Discharge side  
– 18 –  
2-3. CeilingType  
RAV-SM564CT , RAV-SM804CT , RAV-SM1104CT , RAV-SM1404CT  
Upper pipe draw-out port (Knockout hole)  
210  
167  
105  
Power supply cable take-in port (Knockout)  
Pipe draw-out port (Knockout hole)  
128  
216  
Remote controller cable take- in port  
Drain port VP20  
(Inner dia. Ø26, hose attached)  
84 (Knockout hole)  
110 76  
Refrigerant pipe  
(Liquid side ØC)  
Left drain size  
B (Hanging position)  
Refrigerant pipe (Gas side ØD)  
Drain pipe connecting port  
97  
75  
146  
Remote controller cable take- in port  
Hanging bolt  
Power supply cable take-in port (Knockout hole)  
347  
262  
135  
Ceiling surface  
Unit  
Remote controller cable take- in port  
(Knockout hole)  
84  
A
Outside air take-in port  
(Duct sold separately)(Knockout hole Ø92)  
Drain left pipe draw-out port (Knockout hole)  
Pipe hole on wall (Ø100 hole)  
Model name  
A
B
C
D
Wireless sensor  
mounting section  
SM56 type  
910  
855 Ø6.4 Ø12.7  
SM80 type  
1180 1125  
1595 1540  
Ø9.5 Ø15.9  
SM110, 140 type  
250 or more  
250 or more  
– 19 –  
3. WIRING DIAGRAM  
3-1. Indoor Unit  
3-1-1. Compact 4-way CassetteType  
RAV-SM404MUT , RAV-SM454MUT , RAV-SM564MUT  
– 20 –  
3-1-2. Concealed DuctType  
RAV-SM564BT , RAV-SM804BT , RAV-SM1104BT , RAV-SM1404BT  
– 21 –  
3-1-3. CeilingType  
RAV-SM564CT , RAV-SM804CT , RAV-SM1104CT , RAV-SM1404CT  
– 22 –  
4. SPECIFICATIONS OF ELECTRICAL PARTS  
4-1. Compact 4-way CassetteType  
No.  
1
Parts name  
Fan motor (for indoor)  
Type  
Specifications  
Output (Rated) 60 W, 220–240 V  
10 kΩ at 25°C  
SWF-230-60-1R  
155 mm  
2
Thermo. sensor (TA-sensor)  
Heat exchanger sensor (TCJ-sensor)  
Heat exchanger sensor (TC-sensor)  
Float switch  
3
Ø6 mm, 1200 mm  
Ø6 mm, 1200 mm  
FS-0218-102  
ADP-1409  
10 kΩ at 25°C  
4
10 kΩ at 25°C  
5
6
Drain pump motor  
4-2. Concealed DuctType  
No.  
Parts name  
Fan motor (SM804BT)  
Type  
Specifications  
1
ICF-280-120-1C  
Output (Rated) 120 W, 220–240 V  
Fan motor  
(SM564BT/SM1104BT/SM1404BT)  
2
ICF-280-120-2C  
Output (Rated) 120 W, 220–240 V  
3
4
5
6
7
8
Thermo. sensor (TA-sensor)  
Heat exchanger sensor (TCJ-sensor)  
Heat exchanger sensor (TC-sensor)  
Float switch  
618 mm  
Ø6 mm, 1200 mm  
Ø6 mm, 1200 mm  
FS-0218-102  
ADP-1409  
10 kΩ at 25°C  
10 kΩ at 25°C  
10 kΩ at 25°C  
Drain pump motor  
Reactor  
CH-43-2Z-T  
10 mH, 1 A  
4-3. CeilingType  
No.  
Parts name  
Fan motor (SM564CT)  
Fan motor (SM804CT)  
Type  
Specifications  
Output (Rated) 60 W, 220–240 V  
Output (Rated) 60 W, 220–240 V  
Output (Rated) 120 W, 220–240 V  
10 kΩ at 25°C  
1
2
3
4
5
6
7
8
SWF-280-60-1R  
SWF-280-60-2R  
SWF-280-120-2R  
155 mm  
Fan motor (SM1104CT/SM1404CT)  
Thermo. sensor (TA-sensor)  
Heat exchanger sensor (TCJ-sensor)  
Heat exchanger sensor (TC-sensor)  
Louver motor  
Ø6 mm, 1200 mm  
Ø6 mm, 1200 mm  
MP24Z2N  
10 kΩ at 25°C  
10 kΩ at 25°C  
DC 15V  
Reactor  
CH-43-2Z-T  
10 mH, 1 A  
– 23 –  
5. CONTROL BLOCK DIAGRAM  
5-1. Indoor Controller Block Diagram  
5-1-1. In Case of Connection of Wired (Simple) Remote Controller  
Wired (Simple) heder remote controller (Max. 2 units)  
Central remote controller  
Display LCD  
Display LED  
Function setup  
Key switch  
Display LCD  
LCD driver  
CPU  
Function setup  
Key switch  
CN2  
CN1  
CPU  
DC5V  
DC5V  
Power  
circuit  
Remote controller  
communication circuit  
Power circuit  
3  
Secondary  
battery  
Indoor unit  
#1 (Heder)  
#2  
(Follower)  
A
#3  
A
B
(Follower)  
B
A
B
Indoor control P.C. board (MCC-1402)  
DC20V  
Remote controller  
communication circuit  
EEPROM  
DC5V  
TA sensor  
TC sensor  
*
None for  
DC12V  
Duct type  
Louver  
motor  
Same as left  
Same as left  
2  
2  
Driver  
TCJ sensor  
Float input  
HA  
CPU  
H8/3039  
Drain  
pump  
*
Option for  
Ceiling type  
External  
output  
CPU  
TMP88CH47FG  
(TMP88PH47FG)  
Indoor  
fan motor  
Serial send/  
receive circuit  
Run  
Alarm  
1
2
3
1
2
3
Defrost  
Thermo. ON  
COOL  
AC  
Fan motor  
synchronous  
signal input circuit  
HEAT  
control circuit  
Power circuit  
FAN  
DC280V  
1
1
2
2
3
3
Outdoor unit  
Up to 8 units are connectable. 1  
1 However, if “1:1 model connection interface” is  
connected when 2 wired (simple) remote controllers  
are connected, Max. 7 units are connectable.  
Outdoor unit  
“1:1 model” connection interface (Option)  
P.C. board  
(MCC-1440)  
2 Connect “1:1 model connection interface” to only  
1 unit and connect 1 “1:1 model connection  
interface” to the header unit.  
U3  
Central remote  
controller(Option)  
TCC-LINK  
communication circuit  
U4  
3 It is unavailable to connect the Central remote  
controller to the simple wired remote controller.  
Outdoor unit  
– 24 –  
5-1-2. In Case of Connection of Wireless Remote Controller  
Indoor unit  
#1 (Heder)  
Wireless remote controller  
Receiver P.C. board (MCC-1504)  
Display LED  
Receive circuit  
Function setup SW  
Buzzer  
CPU  
Temporary  
operation SW  
DC5V  
Power  
circuit  
Remote controller  
communication circuit  
#2  
(Follower)  
A
#3  
(Follower)  
A
A
B
B
B
Indoor control P.C. board (MCC-1402)  
DC20V  
Remote controller  
communication circuit  
EEPROM  
TA sensor  
DC5V  
*
None for  
Duct type  
DC12V  
Louver  
motor  
TC sensor  
Same as left  
Same as left  
2  
2  
Driver  
CPU  
H8/3039  
TCJ sensor  
Drain  
pump  
Float input  
HA  
*
Option for  
Ceiling type  
External  
output  
CPU  
Indoor  
TMP88CH47FG  
(TVP88PH47FG)  
fan motor  
Serial send/  
receive circuit  
Run  
Alarm  
1
2
3
1
2
3
Defrost  
Thermo. ON  
COOL  
AC  
Fan motor  
control circuit  
synchronous  
signal input circuit  
HEAT  
FAN  
Power circuit  
DC280V  
1
1
2
2
3
3
Outdoor unit  
Up to 8 units are connectable. 1  
1 However, if “1:1 model connection interface” is  
connected when 2 wireless remote controllers are  
connected, Max. 7 units are connectable.  
Outdoor unit  
“1:1 model” connection interface (Option)  
P.C. board  
(MCC-1440)  
2 Connect “1:1 model connection interface” to only  
1 unit and connect 1 “1:1 model connection  
interface” to the header unit.  
U3  
U4  
Central remote  
controller (Option)  
TCC-LINK  
communication circuit  
Outdoor unit  
– 25 –  
5-1-3. Connection of Both Wired (Simple) Remote Controller and Wireless Remote Controller  
Indoor unit  
#1 (Heder)  
Wired (Simple) heder remote controller  
Wireless remote controller  
(Max. 2 units)  
Central remote controller  
Receiver P.C. board  
(MCC-1504)  
Display LED  
Display  
LCD  
Function  
setup  
Display  
LCD  
LCD  
driver  
Receive  
circuit  
Function setup SW  
Display  
LED  
Key  
CPU  
switch  
Function  
setup  
CPU  
CN2  
CN1  
Buzzer  
CPU  
Temporary  
operation SW  
Key  
switch  
DC5V  
Remote controller  
communication circuit  
Power  
circuit  
DC5V  
DC5V  
3  
Power  
circuit  
Remote controller  
communication circuit  
Power  
circuit  
Secondary  
battery  
A
B
A
B
#2  
(Follower)  
A
#3  
(Follower)  
A
A
B
B
B
Indoor control P.C. board (MCC-1402)  
DC20V  
Remote controller  
communication circuit  
EEPROM  
TA sensor  
DC5V  
*
None for  
Duct type  
DC12V  
Louver  
motor  
TC sensor  
Same as left  
Same as left  
2  
2  
Driver  
CPU  
H8/3039  
TCJ sensor  
Float input  
HA  
Drain  
pump  
*
Option for  
Ceiling type  
External  
output  
CPU  
Indoor  
fan motor  
TVP88CH47FG  
Serial send/  
receive circuit  
(TMP88PH47FG)  
Run  
Alarm  
1
2
3
1
2
3
Defrost  
Thermo. ON  
COOL  
AC  
Fan motor  
synchronous  
signal input circuit  
HEAT  
control circuit  
Power circuit  
FAN  
DC280V  
1
1
2
2
3
3
Outdoor unit  
Up to 8 units are connectable. 1  
Outdoor unit  
“1:1 model” connection interface (Option)  
1 However, if “1:1 model connection interface” is  
connected, Max. 7 units are connectable.  
P.C. board  
(MCC-1440)  
2 Connect “1:1 model connection interface” to only  
1 unit and connect 1 “1:1 model connection  
interface” to the header unit.  
U3  
Central remote  
controller (Option)  
TCC-LINK  
communication circuit  
U4  
3 It is unavailable to connect the Central remote  
controller to the simple wired remote controller.  
Outdoor unit  
– 26 –  
5-2. Control Specifications  
No.  
Item  
Outline of specifications  
Remarks  
1
When power  
supply is reset  
1) Distinction of outdoor unit  
When the power supply is reset, the outdoors are distin-  
guished and the control is selected according to the  
distinguished result.  
2) Setting of indoor fan speed and existence of air direction  
adjustment  
Based on EEPROM data, select setting of the indoor fan  
speed and the existence of air direction adjustment.  
Fan speed (rpm)/  
Air direction adjustment  
2
Operation  
mode selection  
1) Based on the operation mode selecting command from the  
remote controller, the operation mode is selected.  
Remote controller  
Control outline  
command  
STOP  
FAN  
Air conditioner stops.  
Fan operation  
COOL  
DRY  
Cooling operation  
Dry operation  
HEAT  
AUTO  
Heating operation  
Ta: Room temp.  
Ts: Setup temp.  
To: Outside temp.  
• COOL/HEAT operation mode is  
automatically selected by Ta, Ts  
and To for operation.  
• The operation is performed as  
shown in the following figure  
according to Ta value at the first  
time only. (In the range of Ts +  
α –1 < Ta < Ts + α + 1, Cooling  
thermo. OFF (Fan)/Setup air  
volume operation continues.)  
Cooling  
operation  
1.0  
Ta˚C Ts +  
–1.0  
Cooling thermo. OFF (Fan)  
• Setup air volume  
α
Heating  
operation  
α is corrected according to the outside temperature.  
Outside temp.  
No To  
Correction value (α)  
0K  
–1K  
0K  
K = deg  
To 24°C  
24°C > To 18°C  
To < 18°C  
+1K  
0K  
To error  
3
Room temp.  
control  
1) Adjustment range: Remote controller setup temperature ( °C )  
COOL/DRY  
18°C to 29°C  
18°C to 30°C  
HEAT  
AUTO  
Wired type  
18°C to 29°C  
16°C to 30°C  
18°C to 29°C  
17°C to 27°C  
Wireless type  
– 27 –  
No.  
Item  
Outline of specifications  
Remarks  
Shift of suction  
temperature in heating  
operation  
3
Room temp.  
control  
(Continued)  
2) Using the CODE No. 06, the setup temperature in heating  
operation can be corrected.  
SET DATA  
0
2
4
6
Setup temp.  
correction  
+0°C  
+2°C  
+4°C  
+6°C  
Setting at shipment  
SET DATA  
2
4
Automatic  
capacity control  
1) Based on the difference between Ta and Ts, the operation  
frequency is instructed to the outdoor unit.  
2) Cooling operation  
(GA control)  
Every 90 seconds, the room temperature difference  
between temperature detected by Ta and Ts and the  
varied room temperature value are calculated to obtain  
the correction value of the frequency command and then  
the present frequency command is corrected.  
Ta (n) – Ts (n) : Room temp. difference  
n
: Counts of detection  
Ta (n-1) – Ts (n) : Varied room temp. value  
n – 1 Counts of detection of 90 seconds before  
3) Heating operation  
:
Every 1 minute (60 sec.), the room temperature differ-  
ence between temperature detected by Ta and Ts and the  
varied room temperature value are calculated to obtain  
the correction value of the frequency command and then  
the present frequency command is corrected.  
Ts (n) – Ta (n)  
n
: Room temp. difference  
: Counts of detection  
Ta (n) – Ta (n – 1): Varied room temp. value  
n – 1  
: Counts of detection of 1 minute before  
4) Dry operation  
The frequency correction control is same as those of the  
cooling operation.  
However the maximum frequency is limited to approxi-  
mately “S6”.  
Note) When LOW is set up, the maximum frequency is  
limited to approximately “SB”.  
5
Automatic  
cooling/heating  
control  
1) The judgment of selecting COOL/HEAT is carried out as  
shown below. When +1.5°C exceeds against Tsh 10  
minutes and after thermo. OFF, heating operation  
(Thermo. OFF) exchanges to cooling operation.  
Description in the parentheses shows an example of  
cooling ON/OFF.  
Tsc: Setup temp. in  
cooling operation  
Tsh: Setup temp. in  
heating operation  
+ temp. correction of  
room temp. control  
Ta ˚C  
+1.5  
Cooling  
(Cooling ON)  
Tsc or Tsh  
–1.5  
(Cooling OFF)  
Heating  
When –1.5°C lowers against Tsc 10 minutes and after thermo. OFF, cooling operation  
(Thermo. OFF) exchanges to heating operation.  
2) For the automatic capacity control after judgment of cooling/heating, see Item 4.  
3) For temperature correction of room temp. control in automatic heating, see Item 3.  
– 28 –  
No.  
Item  
Outline of specifications  
Remarks  
6
Fan speed control  
1) Operation with (HH), (H), (L) or [AUTO] mode is carried  
out by the command from the remote controller.  
HH > H+ > H > L+ >  
L > UL  
2) When the fan speed mode [AUTO] is selected, the fan  
speed varies by the difference between Ta and Ts.  
<COOL>  
Ta ˚C  
A
+3.0  
HH  
B
C
+2.5  
+2.0  
+1.5  
+1.0  
+0.5  
Tsc  
(HH)  
H+ (HH)  
H (HH)  
L+ (H+)  
L (H)  
D
E
L (H)  
F
–0.5  
L (L+)  
G
• Controlling operation in case when thermostat of remote  
controller works is same as a case when thermostat of the  
body works.  
• If the fan speed has been changed once, it is not changed  
for 3 minutes. However when the air volume is exchanged,  
the fan speed changes.  
• When cooling operation has started, select a downward  
slope for the fan speed, that is, the high position.  
• If the temperature is just on the difference boundary, the  
fan speed does not change.  
• Mode in the parentheses indicates one in automatic  
cooling operation.  
<HEAT>  
Ta ˚C  
(–0.5) –1.0  
L (L+)  
E
L+ (H)  
(0) Tsh  
H (H+)  
(+0.5) +1.0  
D
H+  
(HH)  
(+1.0) +2.0  
C
HH  
(HH)  
(+1.5) +3.0  
B
A
(+2.0) +4.0  
Value in the parentheses indicates one when thermostat of  
the remote controller works.  
Value without parentheses indicates one when thermostat of  
the body works.  
• If the fan speed has been changed once, it is not changed  
for 1 minute. However when the fan speed exchanged, the  
fan speed changes.  
• When heating operation has started, select an upward  
slope for the fan speed, that is, the high position.  
• If the temperature is just on the difference boundary, the  
fan speed does not change.  
• Mode in the parentheses indicates one in automatic  
heating operation.  
• In Tc 60°C, the fan speed increases by 1 step.  
Tc: Indoor heat  
exchanger sensor  
temperature  
– 29 –  
No.  
Item  
Outline of specifications  
Remarks  
6
Fan speed control  
(Continued)  
(Ceiling type)  
Selection of high  
ceiling type  
CODE No.  
[5d]  
Standard  
Type 1  
0001  
Type 3  
Type 6  
0003  
0000  
0002  
CODE No.: 5d  
SW501 (1)/(2)  
OFF/OFF  
ON/OFF  
OFF/ON  
ON/ON  
Tap  
F1  
HEAT COOL HEAT COOL HEAT COOL HEAT COOL  
HH HH HH HH  
F2  
HH  
HH  
H+, H H+, H  
L+, L L+, L  
F3  
H+  
H+, H H+, H  
F4  
F5  
F6  
F7  
F8  
F9  
FA  
FB  
FC  
FD  
H+  
H
HH  
H
HH  
H+  
L+  
L
L+  
L
H+  
H
L+  
L
H
L+  
L
L+  
L
L+  
L
UL  
UL  
UL  
UL  
3) In heating operation, the mode changes to [UL] if thermostat  
is turned off.  
4) If Ta 25°C when heating operation has started and when  
defrost operation has been cleared, the air conditioner  
operates with (H) mode or higher mode for  
1 minute after Tc entered in E zone of cool air discharge  
preventive control (No. 7).  
5) In automatic cooling/heating operation, the revolution  
frequency of (HH) is set larger than that in the standard  
cooling/heating operation.  
However only when  
the high ceiling  
selection is set to  
[Standard]  
F5 F4  
Ta ˚C  
47  
However the revolution frequency  
is restricted in the automatic  
heating operation as shown in  
the following figure.  
42  
F5  
6) Self-clean operation  
[Self-clean ] is  
displayed.  
When performing self-clean operation after stopping the  
cooling operation, the mode becomes 210 rpm.  
7
Cool air discharge  
preventive control  
1) In heating operation, the indoor fan is controlled based on  
the detected temperature of Tc sensor or Tcj sensor. As  
shown below, the upper limit of the revolution frequency is  
restricted.  
In D and E zones,  
the priority is given  
to air volume  
selection setup of  
remote controller.  
However B zone is assumed as C zone for  
6 minutes and after when the compressor activated.  
In defrost operation, the control value of Tc is shifted by 6°C.  
In A zone while  
thermo is ON,  
[PRE-HEAT  
(Heating ready)] is  
displayed.  
Tc, Tcj  
˚C  
32  
HH  
H
30  
L
E zone  
28  
UL  
D zone  
26  
OFF  
C zone  
B zone  
A zone  
20  
16  
– 30 –  
No.  
Item  
Outline of specifications  
Remarks  
8
Freeze preventive control 1) The cooling operation (including Dry operation) is  
Tcj:  
(Low temperature release)  
performed as follows based on the detected  
temperature of Tc sensor or Tcj sensor.  
Indoor heat exchanger  
sensor temperature  
When [J] zone is detected for 6 minutes  
(Following figure), the commanded frequency is  
decreased from the real operation frequency.  
After then the commanded frequency changes  
every 30 seconds while operation is performed in  
[J] zone.  
In [K] zone, time counting is interrupted and the  
operation is held.  
When [ I ] zone is detected, the timer is cleared  
and the operation returns to the normal operation.  
If the commanded frequency becomes S0  
because the operation continues in [J] zone, the  
return temperature A is raised from 5°C to 12°C  
until [ I ] zone is detected and the indoor fan  
operates with [L] mode.  
˚C  
A
5
I
K
2
J
Tcn:  
In heating operation, the freeze-preventive control  
works if 4-way valve is not exchanged and the  
following conditions are satisfied.  
(However the temperature for J zone dashing control  
is changed from 2°C to –5°C.)  
Tc temperature when 5  
minutes elapsed after  
activation  
Tc (n – 1):  
Tc temperature at start  
time  
<Conditions>  
• When  
or  
is established 5 minutes after  

activation.  
Tcn Tc (n – 1) – 5  
Tcn < Tc (n – 1) – 1 and Tcn Ta < 5°C  

– 31 –  
No.  
Item  
Outline of specifications  
Remarks  
9
High-temp.  
release control  
1) The heating operation is performed as follows based on the  
detected temperature of Tc sensor or Tcj sensor.  
• When [M] zone is detected, the commanded frequency is  
decreased from the real operation frequency. After then  
the commanded frequency changes every 30 seconds  
while operation is performed in [M] zone.  
However this control is  
ignored in case of the  
follower unit of the twin.  
• In [N] zone, the commanded frequency is held.  
• When [L] zone is detected, the commanded frequency is  
returned to the original value by approx. 6Hz every  
60 seconds.  
Setup at shipment  
Tc, Tcj  
˚C  
Control temp. °C  
M
N
A
A
B
56 (54)  
52 (52)  
B
L
NOTE:  
Same status as that  
when “thermostat-OFF”  
(status that the air  
When the operation has started or when Tc or Tcj < 30°C at start  
of the operation or after operation start, temperature is con-  
trolled between values in parentheses of A and B.  
conditioner enters in the  
room temp. monitor  
mode when the  
temperature reached the  
setup temperature on  
the remote controller)  
10 Drain pump  
control  
1) In cooling operation (including Dry operation), the drain  
pump is usually operated.  
(The ceiling  
type is optional)  
2) If the float switch works while drain pump drives, the  
compressor stops, the drain pump continues the operation,  
and a check code is output.  
Check code [P10]  
3) If the float switch works while drain pump stops, the  
compressor stops and the drain pump operates. If the float  
switch keeps operating for approx. 4 minutes, a check code  
is output.  
11 After-heat  
elimination  
When heating operation stops, in some cases, the indoor fan  
operates with (L) for approx. 30 seconds.  
– 32 –  
No.  
Item  
Outline of specifications  
1) Louver position setup  
Remarks  
12 Louver control:  
Compact 4-way  
type only  
• When the louver position is changed, the position moves  
necessarily to downward discharge position once to return to  
the set position.  
The louver position can be set up in the following operation range.  
In cooling/dry operation In heating/fan operation  
• In group twin/triple operation, the louver positions can be set  
up collectively or individually.  
2) Swing setup  
The swinging  
louver moves  
• [SWING] is displayed and the following display is repeated.  
usually up to the  
ceiling side from  
the louver position  
of the set time.  
In all operations  
(Repeats)  
• In group twin operation, the louver positions can be set up  
collectively or individually.  
3) When the unit stopped or the warning was output, the louver is  
automatically set to full closed position.  
4) When PRE-HEAT  
(Heating ready) is displayed  
(Heating operation started or defrost operation is performed),  
heating thermo is off or self-cleaning is performed, the louver is  
automatically set to horizontal discharge position.  
The louver which air direction is individually set or the locked  
louver closes fully when the unit stops and the louver is  
automatically set to horizontal discharge position when  
PRE-HEAT  
(Heating ready) is displayed, heating thermo is  
off or self-cleaning is performed.  
– 33 –  
No.  
Item  
Outline of specifications  
1) Louver position setup  
Remarks  
13 (Continued)  
For ceiling type only  
• When the louver position is changed, the position  
moves necessarily to downward discharge position  
once to return to the set position.  
• The louver position can be set up in the following  
operation range.  
In cooling/dry operation  
In heating/fan operation  
• In group operation, the louver positions can be set up  
collectively or individually.  
2) Swing setup  
• The swinging position can be moved in the following  
operation range.  
All modes  
• In group operation, the swinging positions can be set  
up collectively or individually.  
Alarm :  
A check code is  
displayed on the  
remote controller, and  
the indoor unit stops.  
(Excluding [F08] and  
[L31])  
3) When the unit stops or when a warning is output, the  
louver automatically moves downward.  
4) While the heating operation is ready or self cleaning,  
the louver automatically moves upward.  
– 34 –  
No.  
Item  
Outline of specifications  
<In case of wired remote controller>  
1) When pushing [CHK] button for 4 seconds or more, [TEST] is  
displayed on the display screen and the mode enters in Test  
run mode.  
Remarks  
13 Frequency  
Command frequency is  
approximately [S7]  
fixed operation  
(Test run)  
2) Push [ON/OFF] button.  
3) Using [MODE] button, set the mode to [COOL] or [HEAT].  
• Do not use other mode than [COOL]/[HEAT] mode.  
• During test run operation, the temperature cannot be ad-  
justed.  
• An error is detected as usual.  
• A frequency fixed operation is performed.  
4) After the test run, push [ON/OFF] button to stop the operation.  
(Display in the display part is same as the procedure in Item 1.)  
5) Push [CHK] button to clear the test run mode.  
([TEST] display in the display part disappears and the status  
returns to the normal stop status.)  
<In case of wireless remote controller>  
(Compact 4-way, Concealed Duct type)  
1) Turn off power of the set.  
Remove the nameplate of the receiver unit and then turn the  
Dip switch to [Test operation / ON].  
2) The test operation starts by [START/STOP] button.  
• [START], [TIMER] and [READY] LEDs flash during test  
operation  
• Under condition of [Test operation / ON], the temperature  
adjustment is invalid even if using the wireless remote  
controller. Do not use it at other cases than a test operation  
because it applies excessive force.  
3) Carry out a test operation under anyone mode of HEAT,  
COOL or FAN operation mode.  
• The outdoor unit does not operate for approx. 3 minutes  
after the power supply was turned on and after operation  
stop.  
4) After the test operation, stop the unit by the wireless remote  
controller and then return Dip switch of the receiver unit to  
the original position.  
(In order to prevent sequential test operation, this receiving  
unit is attached with 60-minutes timer release function.)  
Receiver unit  
Spacer  
M4 × 25 screw  
(2 pieces)  
Nameplate  
Notch  
Small screw  
– 35 –  
No.  
Item  
Outline of specifications  
Remarks  
13 Frequency fixed  
operation  
(Ceiling type)  
Procedure  
Description  
(Test run)  
(Continued)  
Turn on power of the air conditioner.  
The operation is not accepted for 5 minutes when power has been turned on at first time after  
installation, and 1 minute when power has been turned on at the next time and after. After the  
specified time has passed, perform a test operation.  
4
Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button.  
Then change the fan speed to [High] using [Fan] button.  
2
3
Test cooling operation  
Test heating operation  
Set temperature to [18°C] using  
[Temperature set] button.  
Set temperature to [30°C] using  
[Temperature set] button.  
After checking the receiving sound  
“Pi”, immediately push [Temperature set]  
button to set to [19°C]  
After checking the receiving sound  
“Pi”, immediately push [Temperature set]  
button to set to [29°C].  
4
5
After checking the receiving sound “Pi”,  
immediately push [Temperature set] button  
to set to [18°C].  
After checking the receiving sound “Pi”,  
immediately push [Temperature set] button  
to set to [30°C].  
Then repeat the procedure  
.
4 5 4 5  
After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller,  
[Operation] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation.  
6
7
If the lamps do not flash, repeat the procedure 2 and after.  
After the test operation, push [Start/Stop] button to stop the operation.  
<Outline of test operation from the wireless remote controller>  
Test cooling operation:  
Start 18°C 19°C 18°C 19°C 18°C 19°C 18°C (Test operation) Stop  
Test heating operation:  
Start 30°C 29°C 30°C 29°C 30°C 29°C 30°C (Test operation) Stop  
Be sure to set the  
air speed to [High]  
2
3, 4, 5, 6  
2, 7  
14 Filter sign display  
(Except wireless  
type)  
1) The operation time of the indoor fan is calculated, the filter  
reset signal is sent to the remote controller when the  
specified time (2500H) has passed, and it is displayed on  
LCD.  
2) When the filter reset signal has been received from the  
remote controller, time of the calculation timer is cleared.  
[FILTER  
] goes on.  
It is provided  
on the sepa-  
rately sold type  
TCB-AX21E2.  
In this case, the measurement time is reset if the specified  
time has passed, and display on LCD disappears.  
– 36 –  
No.  
Item  
Outline of specifications  
Remarks  
15 Central control  
mode selection  
1) Setting at the central controller side enables to select  
the contents which can be operated on the wired  
remote controller.  
2) Setup contents  
• In case of TCC-LINK Central remote controller  
(TCB-SC642TLE2)  
[Individual]:  
Operated by wired remote controller  
([After-push precedence])  
Display at wired remote  
controller side (No display)  
[Central 1]:  
[
] goes on.  
START / STOP operation by wired remote controller  
is unavailable.  
[Central 2]:  
[
] goes on.  
START / STOP, MODE change and TEMP. setting by  
wired remote controller are unavailable.  
[Central 3]:  
[
[
] goes on.  
] goes on.  
MODE change and TEMP. setting by wired remote  
controller are unavailable.  
[Central 4]:  
MODE change by wired remote controller is  
unavailable.  
• In case of the wireless remote controller, the con-  
tents to be operated are same though the display  
lamp does not change.  
If an item prohibited by the central control mode is  
operated from the remote controller, it is notified with  
receiving sound Pi, Pi, Pi, Pi, Pi (5 times)  
16 Energy-saving  
control  
1) Selecting [AUTO] mode enables an energy-saving to  
be operated.  
2) The setup temperature is shifted (corrected) in the  
range not to lose the comfort ability according to input  
values of various sensors.  
3) Data (Input value room temp. Ta, Outside temp. To, Air  
volume, Indoor heat exchanger sensor temp. Tc) for  
20 minutes are taken the average to calculate correc-  
tion value of the setup temperature.  
4) The setup temperature is shifted every 20 minutes,  
and the shifted range is as follows.  
In cooling time: +1.5 to – 1.0K  
In heating time: –1.5 to +1.0K.  
17 Max. frequency 1) This control is operated by selecting [AUTO] operation mode.  
cut control  
2) COOL operation mode:  
It is controlled according to the following  
figure if To < 28°C.  
3) HEAT operation mode:  
It is controlled according to the following  
figure if To > 15°C.  
Max. frequency is  
restricted to approximately  
Ta ˚C  
Ta ˚C  
the rated heating frequency  
Normal control  
+4  
Tsh  
+3  
–3  
–4  
Tsc  
Normal control  
Max. frequency is  
restricted to approximately  
the rated cooling frequency  
– 37 –  
No.  
Item  
Outline of specifications  
Remarks  
18 DC motor  
1) When the fan operation has started, positioning of  
the stator and the rotor are performed.  
(Moves slightly with tap sound)  
2) The motor operates according to the command from  
the indoor controller.  
Notes)  
• When the fan rotates while the air conditioner stops  
due to entering of outside air, etc, the air conditioner  
may operate while the fan motor stops.  
• When a fan lock is found, the air conditioner stops, and  
an error is displayed.  
Check code [P12]  
19 Self-clean  
operation  
1) When cooling operation mode (AUTO COOL, COOL, DRY) stopped, the following  
three self-clean operations are performed.  
(Dry operation)  
Compressor  
ON period  
Self-clean  
operation period  
FAN  
Drain pump  
Louver  
0 to 10 min.  
10 to 60 min.  
60 min. to  
None  
1 hour  
2 hours  
Horizontal discharge  
position  
Concealed duct is none.  
Fan (UL)  
STOP  
2) During operation of self-clean,  
lights on the wired  
And it is not also on the  
wireless remote controller.  
It is recognized as [STOP]  
from the remote monitor  
side.  
remote controller screen. However the operation  
lamp (Green LED) goes off.  
3) To stop the self-clean operation, push twice the  
[ON/OFF] button on the remote controller  
continuously. (Stop the operation as compressor ON  
time in the table above: 10 minutes or below.)  
4) When the follower unit executes self-clean operation  
in the group connection, the segment of  
is  
displayed on the wired remote controller screen via  
master unit.  
If self-clean operation is not used, set invalidity  
(does not use) of the self-clean operation by  
changing [0001 (At shipment) of CODE No. (DN)  
[D3] to [0000].  
To erase the  
display during operation of  
self-clean, change CODE No. [D4] from [0000:  
Display (At shipment)] to [0001: Non-display].  
SAVE  
20 Save operation  
1) Turn on  
2) During operation of save operation,  
wired remote controller.  
3) During save operation, the current release control is  
performed with the restriction ratio set in EEPROM  
on the outdoor unit.  
button on the remote controller.  
Carry out setting  
operation during stop of  
the unit; otherwise the  
unit stops operation.  
For the setup operation,  
refer to  
“How to set contents of  
save operation” in Sction  
8. SETUP AT LOCAL  
SITE AND OTHERS”.  
lights on the  
SAVE  
4) The restriction ratio can be set by keeping  
button pushed for 4 seconds or more on the remote  
controller.  
5) When validating the save operation, the next opera-  
tion starts with save operation valid because contents  
are held even when operation stops, operation mode  
changes or power supply is reset.  
6) The restriction ratio can be set by changing the setup  
data of CODE No. (DN) [C2] in the range of 50 to  
100% (every 1%, Setting at shipment: 75%).  
– 38 –  
No.  
Item  
Outline of specifications  
Remarks  
21 8°C heating/Frost  
protective operation  
1) This functional is intended for the cold latitudes and  
performs objective heating operation  
(8°C heating operation).  
In a group connection,  
if there is even one  
combination with other  
unit, “This function is not  
provided.is displayed.  
2) This function is valid only for combination with the  
outdoor units.  
3) Using the indoor CODE No. [D1] (1 bit), Valid/Invalid of  
this function is set up at the customer’s side.  
The setup by CODE No. is Invalid [0]/Valid [1] and  
Invalid [0] has been set at the shipment.  
4) This operation is the heating operation which sets 8°C  
as the setup temperature of the target.  
5) This function starts operation by pushing temperature  
The setup temperature  
jumps from [18] to [8].  
button  
pushing  
during heating operation; besides by  
button for 4 seconds or more after  
temperature reached the minimum set temperature.  
6) To stop/release this operation, select and execute one  
from the following operations.  
Push  
button:  

Heating operation 18°C setting) continues.  
Push [START/STOP] button:  
Air conditioner stops.  
(Heating 18°C operation at the next start)  
MODE  
Push  
:
ƒ
Other operation mode is selected and the operation  
continues.  
7) As the setup temperature is 8°C and the human heating is  
not targeted, the cold air discharge preventive control  
(Item 7) is made invalid to suppress the intermittent  
operation.  
8) The settings of the air direction and air volume are  
changeable during this operation.  
9) The indoor fan stops to protect the compressor for  
2 minutes after start of heating operation  
(Thermo-ON) by this function.  
– 39 –  
5-3. Indoor Print Circuit Board  
5-3-1. Compact 4-way CassetteType / Concealed DuctType / CeilingType  
<MCC-1402>  
– 40 –  
Indoor P.C. Board Optional Connector Specifications (MCC-1402)  
Connector  
No.  
Pin  
No.  
Function  
Specifications  
DC12V (COM)  
Remarks  
Option output  
CN60  
1
2
3
4
Defrost output  
ON during defrost operation of outdoor unit  
ON during Real thermo-ON (Comp ON)  
Thermo. ON output  
Cooling output  
ON when operation mode is in cooling system  
(COOL, DRY, COOL in AUTO cooling/heating)  
5
6
Heating output  
Fan output  
ON when operation mode is in heating system  
(HEAT, HEAT in AUTO cooling/heating)  
ON during indoor fan ON  
(Air purifier is used/Interlock cable)  
Outside error input  
CN80  
1
2
3
1
2
1
2
1
2
DC12V (COM)  
DC12V (COM)  
Outside error input  
Check mode input  
0V  
(When continued for 1 minute)  
Check code “L30” is output and forced operation stops.  
CHK  
Operation check  
CN71  
CN72  
CN73  
Used for operation check of indoor unit.  
(Communication with outdoor unit or remote controller  
is not performed, but the specified operation such as  
indoor fan “H” or drain pump ON is output.)  
DISP display mode  
EXCT demand  
Display mode input  
0V  
Display mode enables indoor unit and remote controller  
to communicate. (When power is turned on)  
Demand input  
0V  
Forced thermo-OFF operation in indoor unit  
– 41 –  
6. TROUBLESHOOTING  
6-1. Summary ofTroubleshooting  
<Wired remote controller type>  
1. Before troubleshooting  
1) Required tools/instruments  
+
and  
screwdrivers, spanners, radio cutting pliers, nippers, push pins for reset switch  
Tester, thermometer, pressure gauge, etc.  
2) Confirmation points before check  
a) The following operations are normal.  
1. Compressor does not operate.  
• Is not 3-minutes delay (3 minutes after compressor OFF)?  
• Is not the outdoor unit in standby status though the remote controller reached the setup  
temperature?  
• Does not timer operate during fan operation?  
• Is not an overflow error detected on the indoor unit?  
• Is not outside high-temperature operation controlled in heating operation?  
2. Indoor fan does not rotate.  
• Does not cool air discharge preventive control work in heating operation?  
3. Outdoor fan does not rotate or air volume changes.  
• Does not high-temperature release operation control work in heating operation?  
• Does not outside low-temperature operation control work in cooling operation?  
• Is not defrost operation performed?  
4. ON/OFF operation cannot be performed from remote controller.  
• Is not automatic address being set up?  
(When the power is turned on at the first time or when indoor unit address setting is changed,  
the operation cannot be performed for maximum approx. 5 minutes after power-ON.)  
• Is not being carried out a test run by operation of the outdoor P.C. board?  
b) Did you return the cabling to the initial positions?  
c) Are connecting cables of indoor unit and remote controller correct?  
2. Troubleshooting procedure  
When a trouble occurred, check the parts along with the following procedure.  
Trouble  
Confirmation of check code display  
Check defective parts.  
NOTE :  
For cause of a trouble, power conditions or malfunction/erroneous diagnosis of microcomputer due to outer  
noise is considered except the items to be checked. If there is any noise source, change the cables of the  
remote controller to shield cables.  
– 42 –  
<Wireless remote controller type>  
1. Before troubleshooting  
1) Required tools/instruments  
+
and  
screwdrivers, spanners, radio cutting pliers, nippers, etc.  
Tester, thermometer, pressure gauge, etc.  
2) Confirmation points before check  
a) The following operations are normal.  
1. Compressor does not operate.  
• Is not 3-minutes delay (3 minutes after compressor OFF)?  
• Is not the outdoor unit in standby status though the remote controller reached the setup  
temperature?  
• Does not timer operate during fan operation?  
• Is not an overflow error detected on the indoor unit?  
• Is not outside high-temperature operation controlled in heating operation?  
2. Indoor fan does not rotate.  
• Does not cool air discharge preventive control work in heating operation?  
3. Outdoor fan does not rotate or air volume changes.  
• Does not high-temperature release operation control work in heating operation?  
• Does not outside low-temperature operation control work in cooling operation?  
• Is not defrost operation performed?  
4. ON/OFF operation cannot be performed from remote controller.  
• Is not forced operation performed?  
• Is not the control operation performed from outside/remote side?  
• Is not automatic address being set up?  
• Is not being carried out a test run by operation of the outdoor controller?  
b) Did you return the cabling to the initial positions?  
c) Are connecting cables between indoor unit and receiving unit correct?  
2. Troubleshooting procedure  
(When the power is turned on at the first time or when indoor unit address setting is changed, the operation  
cannot be performed for maximum approx. 5 minutes after power-ON.)  
When a trouble occurred, check the parts along with the following procedure.  
Confirmation of lamp display  
(When wireless remote controller is connected)  
Check defective  
position and parts.  
Trouble  
– 43 –  
Outline of judgment  
The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with  
the following method.  
Method to judge the erroneous position by display panel of the indoor unit  
(lamp display of the wireless receiving part)  
The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis  
are displayed restricted to the following cases if a protective circuit works.  
: Go off,  
: Go on,  
: Flash (0.5 sec.)  
Lamp indication  
Operation Timer Ready  
Check code  
Cause of trouble occurrence  
Power supply OFF or miswiring between lamp indication unit and indoor unit  
No indication at all  
E01  
E02  
E03  
E08  
E09  
E10  
Receiving error ⎫  
Receiving unit  
Miswiring or wire connection error  
Sending error  
between receiving unit and indoor unit  
Communication stop  
Operation Timer  
Ready  
Duplicated indoor unit No.  
Setup error  
Duplicated master units of remote controller  
Flash  
Communication error between CPUs on indoor unit P.C. board  
Wire connection error between indoor units, Indoor power OFF  
(Communication stop between indoor header and follower)  
E18  
Operation Timer  
Operation Timer  
Ready  
Miswiring between indoor unit and outdoor unit or connection erorr  
(Communication stop between indoor and outdoor units)  
E04  
Flash  
Ready  
P10  
P12  
Overflow was detected.  
Protective device of indoor unit worked.  
Indoor DC fan error  
Alternate flash  
P03  
P04  
P05  
P07  
P15  
P19  
P20  
P22  
P26  
P29  
Outdoor unit discharge temp. error  
Outdoor high pressure system error  
Protective device of  
outdoor unit worked.  
1  
Negative phase detection error  
Heat sink overheat error  
Gas leak detection error  
Outdoor unit error  
Operation Timer  
Ready  
4-way valve system error (Indoor or outdoor unit judged.)  
Outdoor unit high pressure protection  
Alternate flash  
Outdoor unit: Outdoor unit error  
Outdoor unit: Inverter Idc operation  
Outdoor unit: Position detection error  
Protective device of  
outdoor unit worked.  
1  
Stopped because of error of other indoor unit in a group  
(Check codes of E03/L03/L07/L08)  
P31  
1: These are representative examples and the check code differs according to the outdoor unit to be combined.  
– 44 –  
Lamp indication  
Operation Timer  
Check code  
F01  
Cause of trouble occurrence  
Ready  
Heat exchanger sensor (TCJ) error  
F02  
Heat exchanger sensor (TC) error  
Heat exchanger sensor (TA) error  
Discharge temp. sensor (TD) error  
Temp. sensor (TE) error  
Indoor unit sensor error  
Alternate flash  
F10  
F04  
F06  
Operation Timer  
Alternate flash  
Ready  
F07  
Temp. sensor (TL) error  
F08  
Temp. sensor (TO) error  
Sensor error of outdoor unit 1  
F12  
Temp. sensor (TS) error  
F13  
Temp. sensor (TH) error  
F15  
Temp. Sensor miswiring (TE, TS)  
Operation Timer  
Ready  
Ready  
F29  
F31  
Indoor EEPROM error  
Outdoor EEPROM error  
Simultaneous flash  
Operation Timer  
Simultaneous flash  
Operation Timer  
Flash  
H01  
H02  
H03  
H04  
H06  
L03  
Compressor break down  
Compressor lock  
Ready  
Outdoor compressor system error 1  
Current detection circuit error  
Case thermostat worked.  
Outdoor unit low pressure system error  
Duplicated header indoor units  
There is indoor unit of group connection AUTO address  
in individual indoor unit.  
L07  
L08  
Operation Timer  
Ready  
If group construction and  
address are not normal  
when power supply turned on,  
automatically goes to address  
setup mode.  
Unsetting of group address  
Simultaneous flash  
Missed setting  
(Unset indoor capacity)  
L09  
L10  
L20  
L29  
L30  
L31  
Unset model type (Service board)  
Duplicated indoor central addresses  
Outdoor unit and other error  
Outside interlock error  
Operation Timer  
Ready  
Others  
Simultaneous flash  
Negative phase error  
1: These are representative examples and the check code differs according to the outdoor unit to be combined.  
– 45 –  
Others (Other than Check Code)  
Lamp indication  
Operation Timer Ready  
Check code  
Cause of trouble occurrence  
During test run  
Simultaneous flash  
Operation Timer Ready  
Disagreement cool/heat  
(Automatic cool/heat setting to automatic cool/heat prohibited mode)  
Alternate flash  
– 46 –  
– 47 –  
Check Code List  
Error mode detected by indoor unit  
Operation of diagnostic function  
Judgment and measures  
Check  
code  
Status of  
air conditioner  
Cause of operation  
Condition  
1. Check cables of remote controller and communication adapters.  
• Remote controller LCD display OFF (Disconnection)  
• Central remote controller [97] check code  
No communication from remote  
controller (including wireless) and  
communication adapter  
Stop  
Displayed when  
E03  
(Automatic reset) error is detected  
1. Outdoor unit does not completely operate.  
• Inter-unit wire check, correction of miswiring  
• Check outdoor P.C. board. Correct wiring of P.C. board.  
The serial signal is not output from  
outdoor unit to indoor unit.  
• Miswiring of inter-unit wire  
Stop  
Displayed when  
E04  
• Defective serial sending circuit on  
outdoor P.C. board  
(Automatic reset) error is detected  
2. When outdoor unit normally operates  
Check P.C. board (Indoor receiving / Outdoor sending).  
• Defective serial receiving circuit on  
indoor P.C. board  
E08  
L03  
Duplicated indoor unit address  
Duplicated indoor header unit  
1. Check whether remote controller connection (Group/Individual)  
was changed or not after power supply turned on  
(Finish of group construction/Address check).  
Displayed when  
error is detected  
* If group construction and address are not normal when the  
power has been turned on, the mode automatically shifts to  
address setup mode. (Resetting of address)  
Stop  
There is group wire in individual indoor  
unit.  
L07  
L08  
L09  
Unset indoor group address  
Unset indoor capacity  
Displayed when 1. Set indoor capacity (DN=11)  
error is detected  
Stop  
Stop  
Displayed when 1. Check outside devices.  
L30  
P10  
Abnormal input of outside interlock  
error is detected  
2. Check indoor P.C. board.  
1. Trouble of drain pump  
Float switch operation  
Displayed when  
error is detected  
2. Clogging of drain pump  
3. Check float switch.  
Stop  
• Float circuit, Disconnection,  
Coming-off, Float switch contact error  
4. Check indoor P.C. board.  
1. Position detection error  
Displayed when 2. Indoor fan driving part over-current protective circuit operation  
P12  
P19  
Indoor DC fan error  
Stop  
Stop  
error is detected  
3. Indoor fan lock  
4. Indoor P.C. board check  
1. Check 4-way valve.  
4-way valve system error  
Displayed when 2. Check 2-way valve and check valve.  
• After heating operation has started,  
indoor heat exchangers temp. is  
down.  
(Automatic reset) error is detected  
3. Check indoor heat exchanger (TC/TCJ).  
4. Check indoor P.C. board.  
Stop  
1. Judge follower unit while master unit is [E03], [L03], [L07] or [L08].  
2. Check indoor P.C. board.  
Own unit stops while warning is output  
to other indoor units.  
Displayed when  
(Follower unit)  
error is detected  
(Automatic reset)  
P31  
F01  
F02  
Coming-off, disconnection or short of  
indoor heat exchanger temp. sensor  
(TCJ)  
1. Check indoor heat exchanger temp. sensor (TCJ).  
2. Check indoor P.C. board.  
Stop  
Displayed when  
(Automatic reset) error is detected  
Coming-off, disconnection or short of  
indoor heat exchanger temp. sensor  
(TC)  
1. Check indoor heat exchanger temp. sensor (TC).  
2. Check indoor P.C. board.  
Stop  
Displayed when  
(Automatic reset) error is detected  
Coming-off, disconnection or short of  
indoor heat exchanger temp. sensor  
(TA)  
1. Check indoor heat exchanger temp. sensor (TA).  
2. Check indoor P.C. board.  
Stop  
Displayed when  
F10  
F29  
(Automatic reset) error is detected  
Indoor EEPROM error  
Stop  
Displayed when 1. Check indoor EEPROM. (including socket insertion)  
(Automatic reset) error is detected  
• EEPROM access error  
2. Check indoor P.C. board.  
Communication error between indoor  
MCU  
1. Check indoor P.C. board.  
Stop  
Displayed when  
E10  
E18  
(Automatic reset) error is detected  
• Communication error between fan  
driving MCU and main MCU  
1. Check remote controller wiring.  
2. Check indoor power supply wiring.  
3. Check indoor P.C. board.  
Regular communication error between  
indoor header and follower units  
Stop  
Displayed when  
(Automatic reset) error is detected  
– 48 –  
Error mode detected by outdoor unit  
The check code has been ramified from 4 series and after  
The ramified check code is displayed only when both the indoor unit and the outdoor unit are 4 series and after.  
(Ex. Combination of RAV-SM1404BT-E with RAV-SP1404AT-E)  
When the outdoor unit is 3 series and before, the conventional check code is displayed.  
(Ex. Combination of RAV-SM1404BT-E and RAV-SM1403AT-E: Indoor unit only is 4 series.)  
Operation of diagnostic function  
Check  
code  
Judgment and measures  
Status of  
air conditioner  
Cause of operation  
Condition  
Indoor  
unit  
Disconnection, short of discharge temp. sensor  
(TD)  
1. Check discharge temp. sensor (TD).  
2. Check outdoor P.C. board.  
Displayed when  
error is detected  
F04  
F06  
F07  
F12  
F15  
F08  
Stop  
Stop  
Stop  
Disconnection, short of outdoor temp. sensor  
(TE)  
1. Check temp. sensor (TE).  
2. Check outdoor P.C. board.  
Displayed when  
error is detected  
Disconnection, short of outdoor temp. sensor  
(TL)  
1. Check temp. sensor (TL).  
2. Check outdoor P.C. board.  
Displayed when  
error is detected  
Disconnection, short of suction temp. sensor  
(TS)  
1. Check suction temp. sensor (TS).  
2. Check outdoor P.C. board.  
Displayed when  
error is detected  
Stop  
Stop  
Displayed when 1. Check temp. sensor (TE, TS).  
Miss-mounting of outdoor temp. sensor (TE, TS)  
error is detected  
2. Check outdoor P.C. board.  
Disconnection, short of outside temp. sensor  
(TO)  
1. Check outside temp. sensor (TO).  
2. Check outdoor P.C. board.  
Displayed when  
error is detected  
Continue  
Disconnection, short of heat sink temp. sensor  
(TH)  
Displayed when 1. Check outdoor P.C. board.  
F13  
F31  
L10  
L29  
Stop  
Stop  
Stop  
Stop  
error is detected  
(Q201 is incorporated in TH sensor.)  
Displayed when 1. Check outdoor P.C. board.  
error is detected  
Outdoor P.C. EEPROM error  
Displayed when 1. Outdoor service P.C. board  
Unset jumper of service P.C. board  
error is detected  
Check model type setting jumper wire.  
Communication error between outdoor P.C.  
board MCU  
Displayed when 1. Check outdoor P.C. board  
error is detected  
2. Connection check for each P.C. board.  
Heat sink overheat error  
1. Check screw tightening between PC. Board and heat  
sink and check radiator grease.  
Displayed when  
error is detected  
P07  
Stop  
Stop  
Heat sink temp. sensor detected over specified  
temperature.  
2. Check heat sink blast path.  
1. Check gas leak, recharge  
2. Check full open of service valve.  
3. Check PMV (Pulse Motor Valve).  
4. Check broken pipe.  
Detection of gas leak  
Discharge temp. sensor (TD), Suction temp.  
sensor (TS) detected temperature over  
specified temp.  
Displayed when  
error is detected  
P15  
5. Check discharge temp. sensor (TD), suction temp.  
sensor (TS).  
4-way valve inverse error  
1. Check operation of 4-way valve.  
After heating operation has started, indoor  
heat exchanger temp. lowers under the  
specified temp.  
2. Check outdoor heat exchanger (TE), suction temp.  
sensor (TS).  
Displayed when  
P19  
Stop  
error is detected 3. Check indoor heat exchanger sensor (TC).  
4. Check 4-way valve coil.  
After heating operation has started, outdoor  
heat exchanger / suction temp. rises over the  
specified temp.  
5. Check PMV (Pulse Motor Valve).  
Compressor break down  
1. Check power supply voltage.  
Displayed when  
H01  
H02  
Stop  
Stop  
Although operation has started, operation  
frequency decreases and operation stops.  
2. Overload operation of refrigerating cycle  
error is detected  
Compressor lock  
1. Trouble of compressor (Lock, etc.): Replace compressor.  
Displayed when  
* Over-current detection after compressor  
start-up  
2. Wiring error of compressor (Open phase)  
error is detected  
– 49 –  
Operation of diagnostic function  
Check  
code  
Status of  
air conditioner  
Cause of operation  
Condition  
Judgment and measures  
Indoor  
unit  
Displayed when 1. Check outdoor P.C. board (MCC-1596).  
H03  
P05  
Current detection circuit error  
Stop  
Stop  
error is detected  
(AC current detection circuit)  
1. Check open phase of 3-phase power supply.  
Displayed when  
error is detected  
Open phase of 3-phase power supply  
2. Black lead wire to be connected to CN03 of MCC-1596  
does not pass through T611.  
1. Check connection of Ps sensor connector.  
2. Check failure of Ps sensor.  
Displayed when  
error is detected  
F23  
Ps sensor error  
Stop  
3. Check compressing power error of compressor.  
4. Check 4-way valve error.  
5. Check outdoor P.C. board error.  
1. Check service valves are fully opened.  
(Gas side, Liquid side)  
2. Check clogging of outdoor PMV. (PMV1, 2)  
3. Check SV2 circuit.  
Displayed when  
error is detected  
Low pressure protective operation  
4. Check Ps sensor error.  
H06  
Stop  
5. Check clogging of indoor filter.  
6. Check clogging of refrigerant pipe.  
7. Check of outdoor fan operation. (In heating mode)  
8. Check short of refrigerant.  
Discharge temp. error  
1. Check refrigerating cycle (Gas leak)  
2. Trouble of electronic expansion valve  
3. Check discharge temp. sensor (TD).  
Displayed when  
error is detected  
P03  
H04  
Discharge temp. (TD) over specified value  
was detected.(1.6)  
Stop  
Stop  
1. Check case thermostat and connector.  
2. Check gas leak, recharge  
Case thermostat operation  
Displayed when  
error is detected  
3. Check full open of service valve.  
4. Check PMV (Pulse Motor Valve).  
5. Check broken pipe.  
Abnormal overheat of compressor  
1. Check service valves are fully opened.  
(Gas side, Liquid side)  
2. Check of outdoor fan operation.  
3. Check motor error of outdoor fan.  
4. Check clogging of outdoor PMV. (PMV1, 2)  
5. Check clogging of heat exchanger in indoor/outdoor units.  
6. Short-circuit status of suction/discharge air in outdoor unit.  
7. Check outdoor P.C. board error.  
Displayed when  
error is detected  
P04  
High pressure SW system error  
Stop  
8. Check fan system error (Cause of air volume drop) at  
indoor side.  
9. Check PMV opening status in indoor unit.  
Displayed when 1. Check power supply voltage.  
error is detected  
P05  
P20  
Power supply voltage error  
Stop  
Stop  
1. Check outdoor heat exchanger sensor (TL).  
High pressure protective operation  
2. Check indoor heat exchanger sensor (TC, TCJ).  
3. Check full open of service valve.  
• During cooling operation, outdoor temp.  
sensor (TL) detected temperature over  
specified temp.  
Displayed when 4. Check indoor/outdoor fan.  
error is detected  
5. Check PMV (Pulse Motor Valve).  
• During heating operation, indoor temp.  
sensor (TC, TCJ) detected temperature over  
specified temp.  
6. Check clogging and short circuit of indoor/outdoor heat  
exchanger.  
7. Overcharge of refrigerant. Recharge  
1. Check lock of fan motor.  
Displayed when  
error is detected  
P22  
Outdoor fan system error  
Stop  
2. Check power supply voltage between L2 and N.  
3. Check outdoor P.C. board.  
1. When performing operation while taking-off compressor  
wire, P26 error occurs. Check control P.C. board.  
Short-circuit error of compressor driving  
element  
Displayed when  
P26  
P29  
Stop  
Stop  
error is detected 2. When performing operation while taking-off compressor  
wire, an error does not occur. (Compressor rare short)  
Displayed when 1. Check control P.C. board.  
error is detected  
Position detection circuit error  
– 50 –  
Error mode detected by remote controller or central controller (TCC-LINK)  
Operation of diagnostic function  
Judgment and measures  
Status of  
air conditioner  
Check code  
Cause of operation  
Condition  
Power supply error of remote controller, Indoor  
EEPROM error  
1. Check remote controller inter-unit wiring.  
2. Check remote controller.  
No communication with master indoor unit  
• Remote controller wiring is not correct.  
• Power of indoor unit is not turned on.  
• Automatic address cannot be completed.  
Not displayed at all  
(Operation on  
remote controller  
is impossible.)  
3. Check indoor power wiring.  
4. Check indoor P.C. board.  
Stop  
5. Check indoor EEPROM.  
(including socket insertion)  
Automatic address repeating phenom-  
enon generates.  
Receiving error from remote controller  
1. Check remote controller inter-unit wiring.  
2. Check remote controller.  
No communication with master indoor unit  
Stop  
(Automatic reset)  
E01  
• Disconnection of inter-unit wire between  
remote controller and master indoor unit  
(Detected by remote controller side)  
Displayed when  
error is detected  
If center exists,  
operation continues.  
2  
3. Check indoor power wiring.  
4. Check indoor P.C. board.  
Stop  
Sending error of remote controller  
(Automatic reset)  
Signal send error to indoor unit  
(Detected by remote controller side)  
Displayed when 1. Check sending circuit inside of remote  
E02  
If center exists,  
operation continues.  
error is detected  
controller.  
Replace remote controller.  
1. In 2-remote controllers (including wireless),  
there are multiple main units.  
Stop  
There are multiple main remote controllers.  
(Detected by remote controller side)  
Displayed when  
error is detected  
E09  
L20  
(Sub unit  
Check that there are 1 main remote  
controller and other sub remote controllers.  
continues operation.)  
Duplicated indoor central addresses on  
communication of central control system  
(Detected by indoor/central controller side)  
1. Check setting of central control system  
network address. (Network adapter SW01)  
Stop  
(Automatic reset)  
Displayed when  
error is detected  
Central controller  
L20  
2. Check network adapter P.C. board.  
1. Check communication wire / miswiring  
2. Check communication (U3, U4 terminals)  
3. Check network adapter P.C. board.  
3  
Communication circuit error of central  
control system  
(Detected by central controller side)  
Continues  
Displayed when  
Central controller  
(Send)  
4. Check central controller (such as central  
control remote controller, etc.)  
(By remote controller) error is detected  
C05  
(Receive)  
C06  
5. Check terminal resistance. (TCC-LINK)  
Continuation/Stop  
Indoor Gr sub unit error  
(Detected by central controller side)  
Displayed when Check the check code of the corresponding  
error is detected unit from remote controller.  
(According  
Central controller  
P30  
to each case)  
2 The check code cannot be displayed by the wired remote controller.  
(Usual operation of air conditioner becomes unavailable.)  
For the wireless models, an error is notified with indication lamp.  
3 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4),  
and [E01], [E02], [E03], [E09] or [E18] is displayed or no check display on the remote controller according  
to the contents.  
– 51 –  
6-3. Diagnostic Procedure for Each Check Code (Indoor Unit)  
Check code  
[E01 error]  
NO  
Correct inter-unit cable  
of remote controller  
Is inter-unit cable of A and B normal?  
YES  
Is there no disconnection or  
contact error of connector on harness  
from terminal block of indoor unit?  
YES  
Correct connection of connector.  
Check circuit wiring.  
NO  
NO  
Is group control operation?  
YES  
NO  
Check power connection of indoor unit.  
(Turn on power again.)  
Is power of all indoor units turned on?  
YES  
NO  
Check indoor P.C. board (MCC-1402).  
Is power supplied to remote controller?  
AB terminal: Approx. DC18V  
Defect Replace  
YES  
YES  
Are 2 remote controllers set  
without header unit?  
Correct a header unit/a follower unit.  
(Remote controller address connector)  
NO  
Check remote controller P.C. board.  
Defect Replace  
[E09 error]  
YES  
Are 2 header units set in  
2 remote controllers?  
Correct as a header unit  
and a follower unit.  
NO  
Check remote controller P.C. board.  
Defect Replace  
– 52 –  
[E04 error]  
NO  
NO  
NO  
NO  
Is group address setup of  
remote controller correct?  
Does outdoor operate?  
Check CODE No. [14].  
YES  
YES  
Are wiring in indoor unit and  
1, 2, 3 inter-unit cables correct?  
Correct wiring and  
inter-unit cables.  
YES  
Correct wiring of connector  
and terminal blocks.  
Are wirings of terminal blocks  
(1, 2, 3) wired to CN67 normal?  
YES  
Does the voltage  
between 2 and 3 of the indoor unit  
inter-unit terminal blocks  
(1, 2, 3) vary?  
NO  
Check indoor P.C. board  
(MCC-1402).  
Defect Replace  
As shown in the following figure,  
carry out measurement within 20 seconds  
after the power was turned on.  
S5277G  
Black  
White  
3
2
1
Terminal block  
Check outdoor P.C. board.  
Check indoor P.C. board.  
Defect Replace  
Defect Replace  
[E10 error]  
YES  
Check power supply voltage.  
Is there no disorder of power supply?  
NO  
Correct lines.  
Check and eliminate noise, etc.  
Check indoor control P.C. board  
(MCC-1402).  
Defect Replace  
– 53 –  
[E18 error]  
NO  
Correct inter-unit cable  
of remote controller.  
Is inter-unit cable  
of A and B normal?  
YES  
Is there no disconnection  
or contact error of connector  
on harness from terminal block  
of indoor unit?  
YES  
Correct connection of connector.  
Check circuit wiring.  
NO  
NO  
Is group control operation?  
YES  
Check power  
connection status of indoor unit  
(Connect again).  
NO  
Is power of all indoor units turned on?  
YES  
NO  
Is connection twin-triple connection?  
YES  
Is there no contact error  
of indoor/outdoor inter-unit wire  
YES  
Correct indoor/outdoor inter-unit wire  
(Serial signal line).  
NO  
Check indoor P.C. board  
(MCC-1402).  
Defect Replace  
[E08, L03, L07, L08 error]  
E08: Duplicated indoor unit No.  
L03: There are 2 or more header units in a group control.  
L07: There is 1 or more group address [Individual] in a group control.  
L08: The indoor group address is unset. (99)  
If the above error is detected when power supply turned on, the mode enters automatically in the automatic  
address set mode. (Check code is not output.)  
However, if the above error is detected during the automatic address set mode, a check code may be output.  
[L09 error]  
YES  
Set capacity data of indoor unit.  
(Setup CODE No. (DN)=11)  
Is not yet capacity setting  
of indoor unit set up?  
NO  
Check indoor P.C. board (MCC-1402).  
Defect Replace  
– 54 –  
[L20 error]  
Are wiring connections  
to communication lines  
U3 and U4 normal?  
NO  
Correct wiring connection.  
YES  
YES  
Is not the multiple same central  
control system addresses connected?  
Correct central control system address.  
NO  
Check central controller  
(including 1:1 model connection interface)  
and indoor P.C. board (MCC-1402).  
Defect Replace  
[L30 error]  
NO  
NO  
Are outside devices of  
Check indoor P.C. board (MCC-1402).  
connector CN80 connected?  
Defect Replace  
YES  
Check outside devices.  
Defect Replace  
Do outside devices normally work?  
YES  
Check cause of operation.  
[P30 error] (Central controller)  
NO  
NO  
Is group operation carried out?  
YES  
Is there check code  
on remote controller in the  
follower remote controller?  
YES  
Check indoor P.C. board (MCC-1402).  
Check corresponding  
indoor unit/outdoor unit.  
Defect Replace  
– 55 –  
[P10 error]  
Is connection of  
NO  
float switch connector  
(Indoor control board CN34)  
normal?  
Correct connection  
of connector.  
YES  
NO  
YES  
Does float switch work?  
YES  
Is circuit wiring normal?  
NO  
Check and correct wiring  
and wire circuit.  
NO  
Does drain pump work?  
YES  
Are connector pins 1 and 3  
at drain pump unit side shorted  
(Resistance value 0)?  
NO  
NO  
Is power of  
drain pump turned on? ∗  
YES  
YES  
Replace drain pump  
and indoor P.C. board  
(MCC-1402).  
Check the drain pipe, etc.  
Check indoor P.C. board  
(MCC-1402).  
Replace drain pump.  
Check wiring.  
Defect Replace  
Check that voltage of 1 – 3 pin of CN068 on the indoor P.C. board is 220–240V.  
[F10 error]  
NO  
Is connection of TAsensor connector  
(indoor P.C. board CN104) nornal?  
Connect connector  
of connector.  
YES  
NO  
Are characteristics of TA sensor resistance value normal?  
Replace TA sensor.  
YES  
Refer to Characteristics-1.  
Check indoor P.C. board (MCC-1402).  
Defective Replace  
– 56 –  
[P12 error]  
Turn off the power.  
Are not there connections errors or  
disconnection on connectors CN333 and CN334  
of indoor unit P.C. board (MCC-1402)?  
YES  
Correct connection of connector.  
NO  
Remove connectors CN333 and  
CN334 of indoor unit P.C. board  
(MCC-1402).  
NO  
Does the fan rotate without trouble  
when handling the fan with hands?  
Replace indoor fan motor.  
Replace indoor fan motor.  
YES  
Are resistance values between phases  
at fan motor connector CN333 motor side of  
indoor P.C. board (MCC-1402) correct? *1  
NO  
1
YES  
*
1
3
• Are not coil windings between  
(Red lead) and  
(White lead),  
3
5
between  
5
(White lead) and  
(Black lead), between  
(Red lead) opened or shorted?  
1
(Black lead) and  
For resistance, see the following values.  
Approx. 70 to 100Ω  
SM56, SM80  
SM110, SM140  
35 to 50Ω  
Is resistance value of fan motor connector  
CN333 at motor side of indoor P.C. board  
(MCC-1402) correct? *2  
NO  
2
Replace indoor fan motor.  
YES  
*
Check resistance of fan motor position detection circuit.  
Is not coil winding between  
1
4
(Yellow lead) and  
(Pink lead)  
opened or shorted? Resistance: Approx. 5 to 20kΩ  
NO  
Is signal output of indoor fan motor  
position detection correct? *3  
Replace indoor fan motor.  
YES  
3
*
Check fan motor position detection signal.  
• Using a tester, measure the voltage between CN334  
1
5
and  
of  
indoor P.C. board (MCC-1402) under condition that CN333 and  
CN334 are mounted and the power is turned on.  
Rotate the fan slowly with hands, and check the pin voltage  
swings between 0 to 5V voltage.  
4
5
• Between  
and  
: 5V  
Check indoor P.C. board  
(MCC-1402).  
CN333  
Defect Replace  
CN334  
– 57 –  
[P19 error]  
Is operation of 4-way valve normal?  
(Check the pipe temp., etc.  
during cooling/heating operation.  
NO  
NO  
Are 1.3 to 1.6kΩ applied to  
resistance value of 4-way valve coil ?  
Replace 4-way valve coil.  
YES  
YES  
Defective  
Check outdoor P.C. board.  
Check outdoor P.C. board operation.  
Defective Replace  
(See the following description.)  
OK  
Check temperature sensors.  
TE sensor  
TS sensor  
Indoor TC sensor  
Defective Correct, replace  
Check 4-way valve.  
Defective Replace  
Operation check direction of the outdoor P.C. board (In case of self-preservation valve)  
1) Set the Dip switch SW804 as same as the following table and push SW801 for approx. 1 second. It enables  
you to check the exchange operation to cooling cycle or heating cycle.  
• Only for approx. 10 seconds, the power is turned on.  
• As the heat value of part (coil: resistance R700) is large, when checking the operation continuously, wait 1  
minute or more until the next check. (There is no problem if a coil is not connected.)  
2) After check, turn off all the Dip switches SW804.  
Exchange to cooling cycle  
Exchange to heating cycle  
SW804 SW801 CN701  
SW804 SW801 CN701  
1
1
Push  
Push  
4
4
DC180V or more  
DC180V or more  
Check by tester  
Analog tester: Good article if over DC180V  
Digital tester: Although in some cases, the value varied and indicated. If the maximum value is DC180V or  
more, it is good article.  
– 58 –  
[F02 error]  
NO  
NO  
Is connection of TC sensor connector  
Correct connection of connector.  
Replace TC sensor.  
(CN101 on Indoor P.C. board) correct?  
YES  
Are characteristics of  
TC sensor resistance value normal?  
YES  
Refer to Charqacteristics-2.  
Check indoor P.C. board (MCC-1402).  
Defect Replace  
[F01 error]  
NO  
NO  
Is connection of TCJ sensor connector  
(CN102 on Indoor P.C. board) correct?  
Correct connection of connector.  
Replace TCJ sensor.  
YES  
Are characteristics of  
TCJ sensor resistance value normal?  
YES  
Refer to Charqacteristics-2.  
Check indoor P.C. board (MCC-1402).  
Defect Replace  
– 59 –  
[C06 error] (1:1 model connection interface)  
NO  
NO  
Are U3 and U4 communication lines normal?  
YES  
Correct communication line.  
1  
Correct connection of connector.  
Is connection of connector normal?  
YES  
1  
In case of 1:1 model connection interface  
1:1 model connection interface (MCC-1440) CN51 and indoor P.C. board CN050.  
NO  
Check connection of A and B terminal blocks.  
Correct communication line of remote controller.  
Are A and B communication lines normal?  
YES  
YES  
NO  
Is there no connection error of power supply cable?  
NO  
Correct power wiring.  
Is not the source power supply turned on?  
YES  
Turn on the source power supply.  
YES  
Did a power failure occur?  
NO  
YES  
YES  
Is the network address changed  
from the wired remote controller?  
Clear the check code.  
Eliminate noise, etc.  
NO  
Is there no noise source?  
NO  
Uncontrolled  
(Same to others)  
Can the other indoor units  
be normally controlled from the central controller?  
Or is the operation status of indoor unit reflected?  
Check central controller.  
Defect Replace  
YES  
Uncontrolled  
Can the indoor unit be normally controlled  
from the wired remote controller?  
Check indoor P.C. board (MCC-1402).  
Defect Replace  
YES  
Check the power supply transformer of  
1:1 model connection interface (MCC-1440).  
Defective Replace  
– 60 –  
[E03 error] (Master indoor unit)  
[E03 error] is detected when the indoor unit cannot receive a signal from the wired remote controller  
(also central controller).  
Check A and B remote controllers and communication lines of the central control system U3 and U4.  
As communication is impossible, this check code [E03] is not displayed on the wired remote controller and the  
central controller.  
[E01] is displayed on the wired remote controller and [C06 error] is displayed on the central controller.  
If these check codes generate during operation, the air conditioner stops.  
[F29 error]  
This check code indicates a detection error of IC10 non-volatile memory (EEPROM) on the indoor unit P.C.  
board, which generated during operation of the air conditioner. Replace the service P.C. board.  
When EEPROM was not inserted when power supply turned on or when the EEPROM data read/write  
operation is impossible at all, the automatic address mode is repeated. In this time, [97 error] is displayed on  
the central controller.  
(Approx.  
3 minutes)  
(Approx.  
1 minute)  
LED (D002) on indoor unit  
P.C. board flashes with  
1Hz for approx. 10 seconds.  
[SET] is displayed on  
wired remote controller.  
[SETTING]  
goes off.  
Reboot  
(Reset)  
(Power ON)  
(Repetition)  
[P31 error] (Follower indoor unit)  
When the master unit of a group operation detected [E03], [L03], [L07] or [L08] error, the follower unit of the  
group operation detects [P31 error] and then the unit stops.  
There is no display of the check code or alarm history of the wired remote controller. (In this model, the mode  
enters in automatic address set mode when the header unit detected [L03], [L07] or [L08] error.)  
– 61 –  
Temperature – Resistance value characteristic table  
TA,TC,TCJ,TE,TS,TO sensor  
TD,TL sensor  
Representative value  
Representative value  
Resistance value (k  
                                                                                      
Ω
                                                                                       
)
Resistance value (kΩ)  
Temperature  
Temperature  
(°C)  
(Minimum (Standard (Maximum  
(Minimum (Standard (Maximum  
(°C)  
value)  
32.33  
19.63  
12.23  
9.75  
value)  
33.80  
20.35  
12.59  
10.00  
7.990  
5.192  
3.451  
2.343  
1.623  
1.146  
0.8237  
0.6023  
value)  
35.30  
21.09  
12.95  
10.25  
8.218  
5.375  
3.594  
2.454  
1.709  
1.213  
0.8761  
0.6434  
value)  
value)  
value)  
0
10  
20  
25  
30  
40  
50  
60  
70  
80  
90  
100  
0
10  
20  
25  
30  
40  
50  
60  
70  
80  
90  
100  
150.5  
161.3  
172.7  
92.76  
58.61  
47.01  
37.93  
25.12  
17.00  
11.74  
8.269  
5.925  
4.321  
3.205  
99.05  
62.36  
49.93  
40.22  
26.55  
17.92  
12.34  
8.668  
6.195  
4.507  
3.336  
105.6  
66.26  
52.97  
42.59  
28.03  
18.86  
12.95  
9.074  
6.470  
4.696  
3.468  
7.764  
5.013  
3.312  
2.236  
1.540  
1.082  
0.7740  
0.5634  
TA,TC,TCJ,TE,TS,TO sensor  
40  
30  
20  
10  
0
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
Temperature (˚C)  
TD,TL sensor  
200  
150  
100  
50  
20  
15  
10  
5
0
0
0
10  
20  
30  
40  
50  
60  
70  
80  
90  
100  
Temperature (˚C)  
– 62 –  
Winding Resistance of Fan Motor  
Part name  
Checking procedure  
Compact 4-way  
Cassette type  
Measure the resistance value of each winding by using the tester.  
Fan motor  
STF-230-60-1R  
Fan motor inside wiring diagram  
Position  
Resistance value  
87 ± 8.7  
Black – Red  
Red  
1
Black – White  
87 ± 8.7  
2
3
4
5
White  
Black  
Red – White  
87 ± 8.7  
Under 20°C  
Concealed Duct type  
Fan motor  
ICF-280-120-1C  
Measure the resistance value of each winding by using the tester.  
Fan motor inside wiring diagram  
(RAV-SM804BT  
ICF-280-120-2C  
(RAV-SM564BT  
RAV-SM1104BT  
RAV-SM1404BT  
)
Position  
Resistance value  
23.4 ± 2.4  
,
,
)
Black – Red  
Red  
Black – White  
Red – White  
23.4 ± 2.4  
1
2
3
4
5
White  
Black  
23.4 ± 2.4  
Under 20°C  
Ceiling type  
Fan motor  
SWF-280-60-1R  
(RAV-SM564CT  
SWF-280-60-2R  
(RAV-SM804CT  
Measure the resistance value of each winding by using the tester.  
Fan motor inside wiring diagram  
)
Position  
Resistance value  
53 ± 5.3  
)
Black – Red  
Red  
Black – White  
Red – White  
53 ± 5.3  
1
2
3
4
5
White  
Black  
53 ± 5.3  
Under 20°C  
Ceiling type  
Fan motor  
SWF-280-120-1R  
Measure the resistance value of each winding by using the tester.  
Fan motor inside wiring diagram  
(RAV-SM1104CT  
RAV-SM1404CT  
,
)
Position  
Resistance value  
37 ± 3.7  
Black – Red  
Red  
Black – White  
Red – White  
37 ± 3.7  
1
2
3
4
5
White  
Black  
37 ± 3.7  
Under 20°C  
– 63 –  
7. REPLACEMENT OF SERVICE P.C. BOARD  
7-1. Indoort Unit  
<Note: when replacing the P.C. board for indoor unit servicing>  
The nonvolatile memory (hereafter called EEPROM, IC10) on the indoor unit P.C. board before replacement includes  
the model specific type information and capacity codes as the factory-set value and the important setting data which  
have been automatically or manually set when the indoor unit is installed, such as system/indoor/group addresses,  
high ceiling select setting, etc.  
When replacing the P.C. board for indoor unit servicing, follow the procedures below.  
After replacement completes, confirm whether the settings are correct by checking the indoor unit No., Group  
master unit / sub unit settings and perform the cooling cycle confirmation through the trial operation.  
<Replacement procedures>  
CASE 1  
Before replacement, the indoor unit can be turned on and the setting data can be read out by wired  
remote control operation.  
EEPROM data read out [1]  
ò
Replacement of P.C. board for Indoor unit servicing and power on [2]  
ò
Writing the read out EEPROM data [3]  
ò
Power reset  
(for all indoor units connected to the remote control when the group operation control is performed.)  
CASE 2  
Before replacement, the indoor unit cannot be turned on or the wired remote controller operation is  
impossible due to trouble of the power supply circuit to the remote controller. (Defective P.C. board)  
Replacement of EEPROM  
Remove EEPROM installed on the P.C. board before replacement  
and then replace it with EEPROM of the service P.C. board.  
ò
Replacement & power ON for service P.C. board [2]  
ò
Read-out of EEPROM data [1]  
If reading-out is impossible, proceed to CASE 3.  
ò
Replacement of EEPROM  
Replace EEPROM again. (Set the original EEPROM to the service P.C. board.)  
ò
Replacement & power ON for service P.C. board [2]  
ò
Writing-in of the read-out EEPROM data [3]  
Power reset  
(for all indoor units connected to the remote controller when the group operation control is performed.)  
CASE 3  
The EEPROM before replacement is defective and the setting data cannot be read out.  
Replacement & power ON for service P.C. board [2]  
ò
Writing the setting data to EEPROM, such as high ceiling installation setting  
and optional connection setting, etc., based on the customer information. [3]  
ò
Power reset  
(for all indoor units connected to the remote control when the group operation control is performed.)  
– 64 –  
[1] Setting data read out from EEPROM  
The setting data modified on the site, other than factory-set value, stored in the EEPROM shall be read out.  
SET  
CL  
TEST  
Step 1 Push  
,
and  
button on the remote controller simultaneously for more than 4 seconds.  
When the group operation control is performed, the unit No. displayed for the first time is the header unit No.  
At this time, the CODE No. (DN) shows “10 ”. Also, the fan of the indoor unit selected starts its operation  
and the swing operation also starts if it has the louvers.  
UNIT LOUVER  
Step 2 Every time when the  
order. Specify the indoor unit No. to be replaced.  
1. Change the CODE No. (DN) to 10 01 by pushing  
button is pushed, the indoor unit No. under the group control is displayed in  
/
buttons for the temperature  
setting. (this is the setting for the filter sign lighting time.)  
At this time, be sure to write down the setting data displayed.  
2. Change the CODE No. (DN) by pushing  
/
buttons for the temperature setting.  
Similarly, be sure to write down the setting data displayed.  
3. Repeat the step 2-2 to set the other settings in the same way and write down the setting data as shown  
in the table 1 (example).  
The CODE No. (DN) are ranged from “01 ” to “FF ”. The CODE No. (DN) may skip.  
TEST  
Step 3 After writing down all setting data, push  
button to return to the normal stop status.  
(It takes approx. 1 min until the remote controller operation is available again.)  
CODE No. required at least  
1. The CODE No. for the Indoor unit type and Indoor unit capacity are  
DN  
10  
11  
12  
13  
14  
Contents  
Type  
required to set the rotation number setting of the fan.  
2. If the system/indoor/group addresses are different from those before  
replacement, the auto-address setting mode starts and the manual  
resetting may be required again.  
Indoor unit capacity  
System address  
Indoor unit address  
Group address  
(when the multiple units group operation including twin, triple system.)  
[2] P.C. Board for indoor unit servicing replacement procedures  
Step 1 Replace the P.C. board to the P.C. board for indoor unit servicing.  
On the new P.C. board, set the same setting of the jumper wire and setting of shortcut connection  
connector as those of the P.C. board before replacement.  
Step 2 According to the system configuration, turn on the indoor unit following to the either methods shown below.  
a) Single operation (Indoor unit is used as standalone.)  
Turn on the indoor unit.  
1. After completion of the auto-address setting mode (required time: approx. 5 min.), proceed to [3].  
(System address = 1, Indoor unit address = 1, Group address = 0 (standalone) are automatically set.)  
SET  
CL  
TEST  
2. Push  
,
and  
buttons simultaneously for more than 4 seconds to interrupt the auto-address  
setting mode, and proceed to [3]. (The unit No. “  
” is displayed.)  
b) Group operation (including twin system)  
Turn on the indoor unit(s) with its P.C. board replaced to the P.C. board for indoor unit servicing,  
according to either methods 1 or 2 shown below.  
1. Turn on only the indoor unit with its P.C. board replaced. (Be sure to confirm the remote controller is  
surely connected. If not, the operation [3] cannot be performed.)  
Perform either methods 1 or 2 described in item a) above.  
2. Turn on the multiple indoor units including the indoor unit with its P.C. board replaced.  
Twin, triple, double twin, 1 system only  
• All group connections  
After completion of the auto-address setting mode (required time: approx. 5 min.), proceed to [3].  
The header unit of the group may be changed by performing the auto-address setting.  
Also, the system address/Indoor unit address of the indoor unit with its P.C. board replaced may be  
assigned to the addresses (not used) other than those of the indoor units without its P.C. board replaced.  
It is recommended to keep the information in advance, which cooling system the indoor unit belongs to  
or whether the indoor unit works as the header unit or the follower unit in the group control operation.  
– 65 –  
[3] Writing the setting data to EEPROM  
The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.  
SET  
CL  
TEST  
Step 1 Push  
,
and  
buttons on the remote controller simultaneously for more than 4 seconds.  
In the group control operation, the unit No. displayed for the first time is the header unit No.  
At this time, the CODE No. (DN) shows “10 ”. Also, the fan of the indoor unit selected starts its operation  
and the swing operation starts if it has the louvers.  
(The unit No. “  
” is displayed if the auto-address setting mode is interrupted in [2] step 2 a))  
UNIT LOUVER  
Step 2 Every time when  
button is pushed, the indoor unit No. in the group control operation are displayed  
in order.  
(The settings stored in the EEPROM of the P.C. board for indoor unit servicing are the factory-set values.)  
Specify the indoor unit No. with its P.C. board replaced to the P.C. board for indoor unit servicing.  
(You cannot perform this operation if “  
” is displayed.)  
Step 3 Select the CODE No. (DN) can be selected by pushing the  
/
button for the temperature setting.  
Step 4 Set the indoor unit type and capacity.  
The factory-set values shall be written to the EEPROM by changing the type and capacity.  
1. Set the CODE No. (DN) to “10 ”. (without change)  
2. Select the type by pushing  
/
buttons for the timer setting.  
(For example, 4-way Air Discharge Cassette Type is set to “0001”. Refer to table 2)  
SET  
3. Push  
button.  
(The operation completes if the setting data is displayed.)  
4. Change the CODE No. (DN) to “11 ” by pushing  
5. Select the capacity by pushing buttons for the timer setting.  
(For example, 80 Type is set to “0012”. Refer to table 3)  
/
buttons for the temperature setting.  
/
SET  
6. Push  
button.  
(The setting completes if the setting data are displayed.)  
TEST  
7. Return to the normal stop status by pushing  
button.  
(Approx. 1 minute is needed to start operation of the remote controller.)  
Step 5 Write the on-site setting data to the EEPROM, such as address setting, etc. Perform the steps 1 and 2  
above again.  
Step 6 Change the CODE No. (DN) to “01 ” by pushing  
/
buttons for the temperature setting.  
(this is the setting for the filter sign lighting time.)  
Step 7 Check the setting data displayed at this time with the setting data put down in [1].  
1. If the setting data is different, modify the setting data by pushing  
the data put down in [1].  
/
buttons for the timer setting to  
<Fig. 1 RBC-AMT32E>  
The operation completes if the setting data is displayed.  
2. If the data is the same, proceed to next step.  
Step 8 Change the CODE No. (DN) by pushing  
/
buttons for the  
temperature setting. As described above, check the setting data  
and modify to the data put down in [1].  
Step 9 Repeat the steps 6 and 7.  
TEST  
Step 10 After the setting completes, push  
button to return to the normal  
stop status. (It takes approx. 1 min until the remote control opera-  
tion is available again.)  
The CODE No. (DN) are ranged from “01 ” to “FF ”.  
The CODE No. (DN) is not limited to be serial No.  
SET  
Even after modifying the data wrongly and pushing  
button, it  
is possible to return to the data before modification by pushing  
CL  
button if the CODE No. (DN) is not changed.  
3 6 5 1 4 2  
<Fig. 2 EEPROM layout diagram>  
The EEPROM (IC10) is attached to the IC socket. When detaching the EEPROM, use a tweezers, etc. Be sure to  
attach the EEPROM by fitting its direction as shown in the figure.  
Do not bend  
the IC lead  
Match the notched parts of IC socket and  
EEPROM and then put in.  
when replacing.  
Notch  
EEPROM(IC10)  
MCC-1402  
EEPROM  
IC socket  
Notch  
– 66 –  
Table 1  
DN  
01  
02  
03  
06  
0F  
10  
11  
12  
13  
14  
Item  
Filter sign lighting time  
Filter pollution level  
Central control address  
Heating suction temperature shift  
Cooling only  
Setting data  
Factory-set value  
Depending on Type  
0000: standard  
0099: Not determined  
0002: +2°C  
0000: Heat pump  
Type  
Depending on model type  
Depending on capacity type  
0099: Not determined  
0099: Not determined  
0099: Not determined  
Indoor unit capacity  
System address  
Indoor unit address  
Group address  
Temperature range of cooling/heating  
automatic SW control point  
1E  
0003: 3 deg (Ts ± 1.5)  
28  
2b  
31  
32  
40  
60  
C2  
d0  
d1  
d3  
Auto restart after power failure  
0000: None  
Thermo output SW (T10  
)
0000: Thermo ON  
0000: Not available  
0000: Body sensor  
0003: Drain pump OFF  
0000: Available  
0075: 75%  
ƒ
Ventilation fan (standalone)  
Sensor select (Selection of static pressure)  
Drain pump control  
Timer setting (wired remote controller)  
DEMAND setup  
Remote controller save function  
Frost protection function  
0001: Valid  
0000: Not available  
0001: 210rpm  
Revolutions per minute of dry operation  
Table 2. Type: CODE No. 10  
Table 3. Indoor unit capacity:  
CODE No. 11  
Setting data  
0004  
Type  
Type name abb.  
RAV-SM∗∗∗BT-E (TR)  
RAV-SM∗∗∗CT-E (TR)  
RAV-SM∗∗∗MUT-E (TR)  
Setting data  
0000∗  
0006  
Type  
Disable  
40  
Concealed Duct Type  
Ceiling Type  
0007  
0014  
Compact 4-way Cassette Type  
0007  
45  
0009  
56  
0012  
80  
0015  
110  
140  
0017  
EEPROM initial value on the P.C. board for indoor unit servicing.  
– 67 –  
8. SETUP AT LOCAL SITE AND OTHERS  
8-1. Indoor Unit  
8-1-1. Test Run Setup on Remote Controller  
<Wired remote controller>  
1. When pushing TEST button on the remote controller for 4 seconds or more, “TEST” is displayed on LC display.  
ON / OFF  
Then push  
button.  
• “TEST” is displayed on LC display during operation of Test Run.  
• During Test Run, temperature cannot be adjusted but air volume can be selected.  
• In heating and cooling operation, a command to fix the Test Run frequency is output.  
• Detection of error is performed as usual. However, do not use this function except case of Test Run  
because it applies load on the unit.  
2. Use either heating or cooling operation mode for [TEST].  
NOTE : The outdoor unit does not operate after power has been turned on or for approx. 3 minutes after  
operation has stopped.  
3. After a Test Run has finished, push TEST button again and check that [TEST] on LC display has gone off.  
(To prevent a continuous test run operation, 60-minutes timer release function is provided to this remote  
controller.)  
(Compact 4-way Cassette Type and Concealed Duct Type)  
1
Remove a screw which fixes the serial olate of the receiver part on the wireless remote controller.  
Remove the nameplate of the reciver section by inserting a minus screwdriver, etc. into the notch at the  
bottom of the plate, and set the Dip switch to [TEST RUN ON].  
2
Execute a test operation with  
button on the wireless remote controller.  
,
and LED flash during test operation.  
• Under status of [TEST RUN ON], the temperature adjustment from the wireless remote controller is  
invalid.  
Do not use this method in the operation other than test operation because the equipment is damaged.  
3
4
Use either [COOL] or [HEAT] operation mode for test operation.  
• The outdoor unit does not operate approx. 3 minutes after power-ON and operation stop.  
After the test operation finished, stop the air conditioner from the wireless remote controller,  
and return Dip switch of the sensor section as before.  
(A 60 minutes timer clearing function is attached to the sensor section in order to prevent a continuous test  
operation.)  
Receiver unit  
Spacer  
M4 × 25 screw  
(2 pieces)  
Nameplate  
Notch  
Small screw  
– 68 –  
<Ceiling Type>  
Procedure  
Description  
Turn on power of the air conditioner.  
The operation is not accepted for 5 minutes when power has been turned on at first time after installation,  
and 1 minute when power has been turned on at the next time and after. After the specified time has  
passed, perform a test operation.  
1
Push [Start/Stop] button and change the operation mode to [COOL] or [HEAT] with [Mode] button.  
2
3
Then change the fan speed to [High] using [Fan] button.  
Test cooling operation  
Test heating operation  
Set temperature to [18°C] using [Temperature set]  
button.  
Set temperature to [30°C] using [Temperature set]  
button.  
After checking the receiving sound “Pi”, immediately After checking the receiving sound “Pi”, immediately  
push [Temperature set] button to set to [19°C] push [Temperature set] button to set to [29°C].  
4
5
After checking the receiving sound “Pi”, immediately After checking the receiving sound “Pi”, immediately  
push [Temperature set] button to set to [18°C]. push [Temperature set] button to set to [30°C].  
Then repeat the procedure  
.
4 5 4 5  
After approx. 10 seconds, all the display lamps on the sensor part of wireless remote controller,  
[Operation] (Green), [Timer] (Green), and [Ready] (Yellow) flash and the air conditioner starts operation.  
6
7
If the lamps do not flash, repeat the procedure  
and after.  
2
After the test operation, push [Start/Stop] button to stop the operation.  
<Outline of test operation from the wireless remote controller>  
Test cooling operation:  
Start 18°C 19°C 18°C 19°C 18°C 19°C 18°C (Test operation) Stop  
Test heating operation:  
Start 30°C 29°C 30°C 29°C 30°C 29°C 30°C (Test operation) Stop  
Be sure to set the  
air speed to [High]  
2
3, 4, 5, 6  
2, 7  
– 69 –  
8-1-2. Forced Defrost Setup of Remote Controller (For wired remote controller only)  
(Preparation in advance)  
TEST  
SET  
CL  
1
Push  
+
+
buttons simultaneously for 4 seconds or more on the remote controller.  
(Push buttons while the air conditioner stops.)  
The first displayed unit No. is the master indoor unit address in the group control.  
UNIT  
2
Every pushing  
other.  
button, the indoor unit No. in the group control is displayed one after the  
Select a main indoor unit (outdoor unit is connected) which is to be defrosted.  
In this time, fan and louver of the selected indoor unit operate.  
TEMP.  
3
4
5
6
Using the set temperature  
buttons, specify the CODE No. (DN) 8C.  
TIME  
Using the timer time  
buttons, set time to data 0001. (0000 at shipment)  
SET  
Push  
button. (OK if indication lights)  
TEST  
Pushing  
button returns the status to the normal stop status.  
(Practical operation)  
ON / OFF  
• Push ON/OFF  
Key.  
• Select the HEAT mode.  
• After while, the forced defrost signal is sent to the outdoor unit and then the outdoor unit starts defrost  
operation. (The forced defrost operation is performed for Max. 12 minutes.)  
• After defrost operation finished, the operation returns to the heating operation.  
To execute the defrost operation again, start procedure from above item 1 .  
(If the forced defrost operation was executed once, setting of the above forced defrost operation is cleared.)  
8-1-3. LED Display on Indoor P.C. Board  
1. D002 (Red)  
• Goes on at the same time when power was turned on (Main microcomputer operates and goes on.)  
• Flashes with 1-second interval (every 500ms): When EEPROM is not provided or writing was an error.  
• Flashes with 10-seconds interval (every 5S): When the mode is DISP  
2. D203 (Red)  
• Goes on when power is supplied to remote controller (Lights on the hardware)  
– 70 –  
8-1-4. Function Selection Setup  
<Procedure> Perform setting while the air conditioner stops.  
TEST  
SET  
CL  
1
Push  
+
+
buttons simultaneously for 4 seconds or more.  
The first displayed unit No. is the master indoor unit address in the group control.  
In this time, fan and louver of the selected indoor unit operate.  
ò
UNIT LOUVER  
2
Every pushing  
button (button at left side), the indoor unit No. in the group control is  
displayed one after the other. In this time, fan and louver of the selected indoor unit only  
operate.  
ò
TEMP.  
3
4
5
Using the set temperature  
buttons, specify the CODE No. (DN).  
ò
TIME  
Using the timer time  
buttons, select the set data.  
ò
SET  
Push  
button. (OK if indication lights)  
To change the selected indoor unit, proceed to Procedure  
2
.
To change item to be set up, proceed to Procedure  
3
.
ò
TEST  
6
Pushing  
button returns the status to the normal stop status.  
TEMP  
ON / OFF  
TIMER SET  
TIME  
FAN  
SAVE  
MODE  
VENT  
3
6
4
5
FILTER  
RESET TEST  
SET  
CL  
SWING/FIX  
UNIT LOUVER  
1
2
<Operation procedure>  
1 2 3 4 5 6 END  
– 71 –  
Item No. (DN) table (Selection of function)  
DN  
Item  
Description  
At shipment  
0002 :2500H  
01 Filter sign lighting time}  
02 Dirty state of filter  
0000 :None  
0002 :2500H (4-Way/Duct/Ceiling Type)  
0000 :Standard  
0001 : High degree of dirt  
(Half of standard time)  
0000 : Standard  
0099 : Unfixed  
0002 : +2°C  
03 Central control address  
0001 :No.1 unit  
0099 :Unfixed  
to  
to  
0064 : No.64 unit  
06 Heating suction temp shift 0000 :No shift  
0002 :+2°C  
0001 : +1°C  
0010 : –10°C  
(Up to recommendation + 6)  
0F Cooling only  
10 Type  
0000 :Heat pump  
0001 : Cooling only  
0000 : Heat pump  
(No display of [AUTO] [HEAT])  
0004 :Concealed duct type 0007 : Ceiling type  
0014 :Compact 4-way cassette type  
According to model type  
According to capacity type  
11 Indoor unit capacity  
0000 :Unfixed  
0007 :45 type  
0012 : 80 type  
0017 : 140 type  
0006 : 40 type  
0009 : 56 type  
0015 : 110 type  
12 Line address  
0001 :No.1 unit  
0001 :No.1 unit  
0000 :Individual  
to  
to  
0030 : No.30 unit  
0099 :Unfixed  
0099 :Unfixed  
0099 :Unfixed  
13 Indoor unit address  
14 Group address  
0064 : No.64 unit  
0001 : Master of group  
0002 :Follower of group  
19 Louver type  
0000 :No louver  
0002 :1-way  
0001 : Swing only  
0003 : 2-way  
According to model type  
0003 :3 deg (Ts±1.5)  
(Air direction adjustment)  
None for concealed duct 0004 :4-way  
1E Temp difference of  
automatic cooling/heating  
mode selection COOL →  
HEAT, HEAT COOL  
0000 :0 deg to  
0010 : 10 deg  
(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)  
28 Auto restart after power  
failure  
0000 :None  
0001 : Auto restart  
0000 :None  
2A Option  
0002 :Default  
2b Thermo output selection  
0000 :Indoor thermo ON  
0001 :Output of outdoor comp-ON receiving  
0000: Thermo. ON  
(T10  
)
ƒ
2E Option  
30 Option  
31 Option  
0000 :Default  
0000 :Default  
0000 :Default  
0000 :Body sensor  
0000 :°C  
32 Sensor selection  
33 Temperature indication  
40 Option  
0000 :Body TA sensor  
0000 :°C (celsius)  
0001 : Remote controller sensor  
0001 : °F (Fahrenheit)  
0003 :Default  
0000 :Standard  
5d High ceiling selection  
(External static pressure  
selection)  
0000 :Standard  
0002 :High ceiling 2  
0001 : High ceiling 1  
0003 : High ceiling 3  
<Concealed Duct type>  
Set data  
0000  
40 Pa  
0001  
0003  
0006  
70 Pa*1  
100 Pa*2  
20 Pa  
External static  
pressure  
Standard  
High static  
High static Low static  
pressure  
(At shipment) pressure 1 pressure 2  
1: SM140 become to 65Pa.  
2: SM140 become to 90Pa.  
– 72 –  
DN  
Item  
Description  
At shipment  
60 Timer set  
0000 :Available (Operable)  
0001 :Unavailable (Operation prohibited)  
0000 :Available  
(Wired remote controller)  
8b Correction of high heat feeling  
42 Self clean time  
0000 :None  
0001 : Correction  
0000 :None  
0002: 1 hour  
0000: None  
0001: 0.5h to 0.012: 6.0h  
The case that compressor-ON time is 10 to 60 minutes is  
set up. When ON time is over 60 minutes, the operating  
time becomes two times of it.  
C2 Power saving  
0050: 50%  
0000: None  
to  
0100: 100%  
0001: Set  
0075: 75%  
(Current demand × % to outdoor unit)  
CC Forced stop setting for self clean  
0000: None  
0000: Valid  
CD Self clean stop function when [START/  
STOP] operation was prohibited  
When stopping the air conditioner (including “Fire alarm”  
of the control system, etc.) while [START/STOP] operation  
is prohibited (Central 1, 2) from the central controller side,  
0000: Valid (No self cleaning)  
0001: Invalid (Self cleaning)  
D0 Existence of Power save operation  
0000: Invalid (Unavailable)  
0001: Valid (Available)  
0001: Valid (Available)  
D1 Existence of 8°C heating operation  
function  
0000: Invalid (Unavailable)}  
0001: Valid (Available)  
0000: Invalid  
(Unavailable)  
D3 Revolution count of self clean  
0000: Invalid (Self cleaning is not performed.)  
0001: Valid (Self cleaning is performed at 210 rpm.)  
0001: Valid  
(210rpm/operation)  
D4 Display/ No display of [SELF CLEANING] 0000: Displayed, 0001: Not displayed  
during self clean operation  
0000: Displayed  
– 73 –  
8-1-5. Cabling and Setting of Remote Controller Control  
2-remote controller control  
<Wired remote controller>  
(Controlled by 2 remote controllers)  
This control is to operate 1 or multiple indoor units  
are controlled by 2 remote controllers.  
How to set wired remote controller  
as sub remote controller  
Change DIP switch inside of the rear side of the  
remote controller switch from remote controller master  
to sub. (In case of RBC-AMT32E)  
(Max. 2 remote controllers are connectable.)  
• When connected 2 remote controllers  
operate an idoor unit  
Remote controller (Inside of the rear side)  
Remote controller  
switch (Master)  
Remote controller  
switch (Sub)  
1 2  
Sub remote  
controller  
Sold  
Sold  
separately  
separately  
Master remote  
controller  
A B  
A B  
1
2
DIP switch  
1
2
Remote controller  
cables (Procured locally)  
Terminal block for  
remote controller cables  
<Wireless remote controller>  
A B  
How to set wireless remote controller to sub  
Indoor unit  
1 2 3  
remote controller  
Standalone receiver  
(TCB-AX21E2)  
1 2 3  
Outdoor unit  
• When connected 2 remote controllers  
operate the twin  
[Remote controller  
Sub/Master]  
DIP SW  
Remote controller  
switch (Master)  
Remote controller  
switch (Sub)  
Remote controller  
inter-unit wire  
(Procured locally)  
Sold  
Sold  
[Operation]  
1. The operation contents can be changed by Last-  
push-priority.  
separately  
separately  
A B  
A B  
2. Use a timer on either Master remote controller or  
Sub remote controller.  
Terminal block for  
remote controller cables  
<Wireless remote controller>  
(Ceiling Type)  
A B  
A B  
Indoor unit 1  
1 2 3  
Indoor unit 2  
1 2 3  
How to set wireless remote controller as sub  
remote controller  
Turn Bit [3: Remote controller Sub/Master] of the  
switch S003 from OFF to ON.  
1 2 3  
Inter-unit wiring  
between indoor units  
(Procured locally)  
Outdoor unit  
Rear cover  
ON  
1
2
3
4
ON  
Receiver P.C. board  
Upper case  
S003  
Bit 3 : OFF ON  
(Setup method)  
ON  
One or multiple indoor units are controlled by two  
remote controllers.  
1
2
3
4
ON  
(Max. 2 remote controllers are connectable.)  
– 74 –  
8-1-6. Monitor Function of Remote Controller  
n Calling of sensor temperature display  
<Contents>  
Each sensor temperature of the remote controller, indoor unit, and outdoor unit can become known by calling  
the service monitor mode from the remote controller.  
<Procedure>  
TEST  
CL  
1
Push  
+
buttons simultaneously for 4 seconds to  
call the service monitor mode.  
The service monitor goes on, the master indoor unit No. is  
displayed, at first and then the temperature of CODE No. 00 is  
displayed.  
TEMP  
ON / OFF  
TIMER SET  
TIME  
FAN  
SAVE  
MODE  
VENT  
TEMP.  
2
Push temperature set  
buttons and then change  
the CODE No. of data to be monitored.  
FILTER  
RESET TEST  
SET  
CL  
SWING/FIX  
UNIT LOUVER  
The item code list is shown below:  
2 4 1  
<Operation procedure>  
3
1 2 3 4  
Returned to usual display  
CODE No.  
Data name  
Unit  
CODE No.  
Data name  
Unit  
01  
Room temperature  
°C  
60  
61  
62  
63  
65  
6A  
6D  
70  
72  
73  
F1  
Outdoor heat exchanger (Coil) temperature (TE)  
Outside temperature (TO)  
°C  
°C  
(Remote controller)  
02  
03  
Indoor suction temperature (TA)  
°C  
°C  
Compressor discharge temperature (TD)  
Compressor suction temperature (TS)  
Heat sink temperature (THS)  
°C  
Indoor heat exchanger (Coil)  
temperature (TCJ)  
°C  
°C  
04  
Indoor heat exchanger (Coil)  
temperature (TC)  
°C  
Operation current (× 1/10)  
A
07  
F2  
F3  
F8  
Indoor fan revolution frequency  
Indoor fan calculated operation time  
Filter sign time  
rpm  
×100h  
×1h  
Outdoor heat exchanger (Coil) temperature (TL)  
Compressor operation frequency  
°C  
rps  
rpm  
rpm  
×100h  
Outdoor fan revolution frequency (Lower)  
Outdoor fan revolution frequency (Upper)  
Compressor calculated operation time  
Indoor discharge temperature  
°C  
ò
UNIT LOUVER  
3
4
Push  
button to select the indoor unit to be monitored.  
Each data of the indoor unit and its outdoor units can be monitored.  
ò
TEST  
Pushing  
button returns the status to the usual display.  
• The data value of each item is not the real time, but value delayed by a few seconds to ten-odd seconds.  
• If the combined outdoor unit is one before 2 or 3 series, the outdoor unit data [6D], [70], [72] and [73] are  
not displayed.  
– 75 –  
n Calling of error history  
<Contents>  
The error contents in the past can be called.  
<Procedure>  
TEST  
CL  
1
Push  
+
buttons simultaneously for 4 seconds or  
more to call the service check mode.  
TEMP  
ON / OFF  
Service Check goes on, the CODE No. 01 is displayed, and  
then the content of the latest alarm is displayed.  
The number and error contents of the indoor unit in which an  
error occurred are displayed.  
TIMER SET  
TIME  
FAN  
SAVE  
MODE  
VENT  
FILTER  
RESET TEST  
SET  
CL  
SWING/FIX  
UNIT LOUVER  
2
3
In order to monitor another error history, push the set  
temperature  
/
buttons to change the error  
history No. (CODE No.)  
CODE No. 01 (Latest) CODE No. 04 (Old)  
NOTE : 4 error histories are stored in memory.  
<Operation procedure>  
1 2 3  
2 3 1  
TEST  
Pushing  
button returns the display to usual display.  
Returned to usual display  
REQUIREMENT  
CL  
Do not push  
button, otherwise all the error histories of the indoor unit are deleted. If the error histories are  
deleted by pushing CL button, turn off the power supply once and then turn on the power supply again.  
When the error which is same as one occurred at the last before deletion continuously occurs again, it may not be  
stored in memory.  
(Group control operation)  
In a group control, operation of maximum 8 indoor units can be controlled by a remote controller.  
Twin, triple or double twin of an outdoor unit is one of the group controls.  
The indoor unit connected with outdoor unit (Individual/Header of twin) controls room temperature according to  
setting on the remote controller.  
<System example>  
OUT  
OUT  
IN  
OUT  
IN  
OUT  
IN  
OUT  
IN  
Header  
2-1  
IN  
1-1  
3-1  
4-1  
7-1  
Max. 8 units  
Remote controller  
1. Display range on remote controller  
The setup range (Operation mode/Air volume select/Setup temp) of the indoor unit which was set to the header  
unit is reflected on the remote controller.  
1) Concealed duct high static pressure type (RAV-SMXXX) is not set up on the header unit.  
• If the Concealed duct high static pressure type is the header unit:  
Operation mode: [Cooling/Heating AUTO] [HEAT] [COOL] [FAN] and no [DRY]  
Air volume select: [HIGH]  
• When the operation mode is [DRY], [FAN] stops in concealed duct high static pressure models.  
2. Address setup  
If there is no serial communication between indoor and outdoor when the power is turned on, it is judged as  
follower unit of the twin. (Every time when the power is turned on)  
• The judgment of header (wired) / follower (simple) of twin is carried out every time. It is not stored in non-  
volatile memory.  
Turn on power of the indoor unit to be controlled in a group within 3 minutes after setting of automatic address.  
If power of the indoor unit is not turned on within 3 minutes (completion of automatic address setting), the system  
is rebooted and the automatic address setting will be judged again.  
1) Connect indoor/outdoor connecting wire surely.  
2) Check line address/indoor address/group address of the unit one by one.  
Especially in case of twin, triple, double twin, check whether they are identical system address or not.  
3) The unit No. (line/indoor gout address) which have been set once keep the present status as a rule if the unit  
No. is not duplicated with one of another unit.  
– 76 –  
n Indoor unit power-ON sequence  
• The unit without power feed waits entirely  
Waiting status is released by system start  
• Reboot when power is fed on the way  
Power ON  
<By indoor unit  
which receives power feed from outdoor unit>  
<Automatic  
address judgment>  
Not normal  
NO  
3 minutes elapse  
Gr construction check  
YES  
Normal  
Gr normal  
1) There is no duplicated indoor unit address.  
2) There is no invalid indoor unit address.  
3) Individual unit and header / follower units  
are not intermingled.  
4) Only a unit for individual.  
5) Header indoor unit and 1 or more  
follower units for Gr.  
System start  
Automatic address starts.  
(Approx. 1 minute up to finish)  
<Initial communication>  
Outdoor model distinction (10 seconds) (Indoor unit)  
Twin header/follower distinction (Indoor unit)  
Gr construction, louver information (Remote controller)  
<Cautions at test run>  
• Power supply/Indoor/Outdoor serial and Gr wiring: OK  
• Powers of all indoor units are turned on within 3 minutes.  
• Reception time for remote controller operation  
(After power supply was turned on)  
1) When address is OK : Approx. 50 seconds  
2) In AUTO address  
: Approx. 4 to 5 minutes  
Remote controller operation is available.  
(Approx. 50 seconds after power-ON)  
<Usual regular  
communication>  
Regular communication between indoor units (Every 30 seconds) (Header / Follower)  
Regular communication of the identical piping system (Every 30 seconds)  
(Twin header / follower) (When the above status changes, immediately communicates.)  
(Repetition)  
• In a group operation, if the indoor unit which was fed power after judgment of automatic address cannot  
receive regular communication from the header unit and regular communication on identical pipe within  
120 seconds after power was turned on, it reboots (system reset).  
The operation starts from judgment of automatic address (Gr construction check) again.  
(If the address of the header unit was determined in the previous time, the power fed to the header unit  
and reboot works, the header unit may change though the indoor unit line address is not changed.)  
– 77 –  
8-2. Setup at Local Site / Others  
Model name:TCB-PCNT30TLE  
8-2-1. 1:1 Model Connection Interface (TCC-LINK adapter)  
1. Function  
This model is an optional P.C. board to connect the indoor unit to 1:1 model connection interface.  
2. Microprocessor block diagram  
Indoor unit  
Central controller  
1:1 model connection interface  
P.C. board  
CN40  
CN050  
Indoor control  
P.C. board  
CN041  
1:1 model  
connection interface  
communication circuit  
CN51  
Terminal  
resistance  
SW01  
MCC-1440  
Terminal block  
(A, B)  
1:1 model  
connection interface  
Communication units  
Communication distance : 2000 m  
: Total 64 units  
Remote controller  
3. 1:1 model connection interface wiring connection  
CAUTION  
1) When controlling DI, SDI series collectively, 1:1 model connection interface (This option) is required.  
2) In case of group operation, twin-triple operation, the 1:1 model connection interface is necessary to be  
connected to the header unit.  
3) Connect the central control devices to the central control system wiring.  
4) When controlling DI, SDI series only, turn on only Bit 1 of SW01 of the least line of the system address No. (OFF  
when shipped from the factory)  
In case of DI, SDI series, the address is necessary to be set up again from the wired remote  
controller after automatic addressing.  
Central control device  
Central control device  
Central control devices: Max. 10 units  
U1 U2  
U3 U4  
U1 U2  
U3 U4  
Refrigerant line 1  
Refrigerant line 2  
Refrigerant line 3  
1 2 3  
Refrigerant line 4  
1 2 3  
Outdoor unit  
1 2 3  
1 2 3  
Indoor/outdoor inter-unit wire (AC230V serial)  
Central control system wiring  
Caution 3  
* Wiring for No.1 and 2 only  
Header  
unit  
Follower  
unit  
Follower  
unit  
Follower  
Header unit  
unit  
Indoor unit  
U3 U4 1 2 3  
A B  
U3 U4 1 2 3  
1 2 3  
1 2 3  
U3 U4 1 2 3  
1 2 3  
A B  
A B  
A B  
A B  
A B  
1:1 model connection  
interface  
This product  
sold separately  
Caution 1  
Caution 2  
(
)
Remote controller  
wiring  
Remote controller  
Remote controller  
Remote controller  
Remote controller  
Twin/Triple operation (Example of triple)  
Group operation (Max. 8 units)  
Indoor units in all refrigerant lines: Max. 64 units  
[If mixed with SMMS (Link wiring), multi indoor units are included.]  
* However group follower units of SDI, DI series are not included in number of the units.  
– 78 –  
4. Wiring Specifications  
• Use 2-core with no polar wire.  
No. of wires  
Size  
• Match the length of wire to wire length of the central control  
system. If mixed in the SMMS system, the wire length is  
lengthened with all indoor/outdoor inter-unit wire length at side.  
Up to 1000m: twisted wire 1.25mm2  
Up to 2000m: twisted wire 2.0mm2  
2
To prevent noise trouble, use 2-core shield wire.  
• Connect the shield wire by closed-end connection and apply open process (insulating process) to the last  
terminal. Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter  
(DI, SDI) unit setup)  
CAUTION  
1) Closed-end connection of shield wire (Connect all the connecting parts of each indoor unit)  
2) Apply open process to the last terminal (insulating process).  
3) Ground earth wire to 1 point at indoor unit side.  
Central control device  
U1 U2  
Caution 2  
Caution 1  
Caution 3  
Central control system wiring  
Outdoor unit  
: 1:1 model connection  
interface  
(TCC-LINK adapter)  
(This option)  
1 2 3  
1 2 3  
1 2 3  
1 2 3  
Follower unit  
Header unit  
U3 U4 1 2 3  
Follower unit  
1 2 3  
Follower unit  
1 2 3  
Header unit  
Indoor unit  
U3 U4 1 2 3  
A B  
1 2 3  
U3 U4 1 2 3  
A B  
A B  
A B  
A B  
A B  
Earth screw  
Remote controller  
Remote controller  
Remote controller  
Remote controller  
(Group operation)  
(Triple operation)  
5. P.C. Board Switch (SW01) Setup  
When performing collective control by customized setup only, the setup of terminator is necessary.  
• Using SW01, set up the terminator.  
• Set up the terminator to only the interface connected to the indoor unit of least line address No.  
Central control device  
Central control device  
Central control devices: Max. 10 units  
U1 U2  
U3 U4  
U1 U2  
U3 U4  
Refrigerant line 1  
Outdoor unit  
Refrigerant line 2  
Refrigerant line 3  
1 2 3  
Refrigerant line 4  
1 2 3  
1 2 3  
1 2 3  
Indoor/outdoor inter-unit wire (AC230V serial)  
Central control system wiring  
* Wiring for No.1 and 2 only  
Follower  
Header  
unit  
U3 U4 1 2 3  
Followerunit  
1 2 3  
Follower unit  
1 2 3  
Header unit  
U3 U4 1 2 3  
unit  
Indoor unit  
U3 U4 1 2 3  
1 2 3  
A B  
A B  
A B  
A B  
A B  
A B  
1:1 model connection interface  
(TCC-LINK adapter)  
This product  
Remote controller wiring  
Remote controller Remote controller  
(
)
sold separately  
Remote controller  
Remote controller  
Remote controller  
Group operation (Max. 8 units)  
Twin/Triple operation (Example of triple)  
Line address  
SW01 Bit 1  
SW01 Bit 2  
Remarks  
1
ON  
OFF  
2
OFF  
OFF  
4
OFF  
OFF  
(OFF at shipment from factory)  
(OFF at shipment from factory)  
Turn SW01 Bit 1 to ON. As status shipped from factory  
As status shipped from factory  
(Reference) Setup contents of switch  
SW01  
Terminator  
Remarks  
Bit 1  
OFF  
ON  
OFF  
ON  
Bit 1  
OFF  
OFF  
ON  
None  
100Ω  
75Ω  
Mixed with SMMS (Link wiring) at shipment from factory  
Central control by digital inverter only  
Spare  
Spare  
ON  
43Ω  
– 79 –  
6. External view of P.C. board assembly  
Terminator (SW01)  
52  
85  
7. Address setup  
In addition to set up the central control address, it is necessary to change the indoor unit number.  
(Line/Indoor/Group address). For details, refer to 1:1 model connection interface Installation Manual.  
8-3. How to Set up Central Control Address Number  
When connecting the indoor unit to the central control remote controller using 1:1 model connection interface, it  
is necessary to set up the central control address number.  
• The central control address number is displayed as the line No. of the central control remote controller.  
How to set up from indoor unit side by remote controller  
<Procedure> Perform setup while the unit stops.  
VENT  
TEST  
1
Push  
When group control is executed, first the unit No.  
control are selected. In this time, fans of all the selected indoor units are turned on. (Fig. 1)  
+
buttons for 4 seconds or more.  
is displayed and all the indoor units in the group  
UNIT LOUVER  
(Keep  
displayed status without pushing  
button.)  
In case of individual remote controller which is not group-controlled, Line address and Indoor unit address  
are displayed.  
TEMP.  
2
3
Using temperature setup  
buttons, specify CODE No. 03.  
TIME  
Using timer time  
buttons, select the SET DATA.  
The setup data is shown in the table below (Table 1).  
SET  
4
5
Push  
button. (OK if display goes on.)  
To change the item to be set up, return to Procedure 2.  
(Fig.1)  
TEST  
Push  
button.  
The status returns to usual stop status.  
CODE No.  
SET DATA SETTING  
UNIT No.  
R.C. No.  
(Table 1)  
TEMP.  
ON / OFF  
SET DATA  
Central control address No.  
TIMER SET  
FAN  
MODE  
VENT  
0001  
0002  
0003  
:
1
2
2
1
3
1
TIME  
SAVE  
3
FILTER  
RESET TEST  
SET  
CL  
SWING/FIX  
UNIT LOUVER  
:
0064  
64  
0099  
Unset (Setup at shipment from factory)  
5
4
– 80 –  
How to confirm the central control address (New function for AMT32E remote controller)  
<Procedure> It can be confirmed even during operation or stopping.  
UNIT LOUVER  
1
2
Push  
button for 4 seconds or more.  
ò
In the frame at left side of the remote controller screen, the lighting set contents are  
displayed.  
During unset time, 0099 (At shipment from factory) is displayed.  
ò
3
After lighting display for 3 seconds, the display automatically disappears.  
If any button is pushed during display, immediately the display disappears and then the pushed button is  
displayed.  
– 81 –  
9. ADDRESS SETUP  
9-1. Address Setup  
<Address setup procedure>  
When an outdoor unit and an indoor unit are connected and they are twin-triple, or when an outdoor unit is  
connected to each indoor unit respectively in the group operation even if multiple refrigerant lines are provided,  
the automatic address setup completes with power-ON of the outdoor unit.The operation of the remote control-  
ler is not accepted while automatic address works. (Approx. 4 to 5 minutes)  
Setup of line address of outdoor unit,  
indoor unit address, and group address  
Completion of wiring work  
NO  
YES  
NO  
Do you arbitrarily set the  
indoor unit address?  
Is refrigerant line 1 line?  
NO  
YES  
(MANUAL)  
Is group control performed?  
YES  
(To AUTO address mode)  
NO  
Are there multiple units  
of twin-triple connections?  
YES  
NO  
Do you change setting after  
automatic setting at the first time?  
YES  
Connect one remote controller with  
one indoor unit (1 : 1) tentatively with  
communication wiring.  
Turn on power of outdoor unit.  
Turn on power of outdoor unit.  
Turn on power of outdoor unit.  
After completion of address  
setup, change is to arbitral  
(
)
Setup of automatic  
address finishes within  
Set to all indoor units one by one.  
address/group manually.  
(
)
4 to 5 minutes.  
END  
• When the following addresses are not stored in the neutral memory (IC10) on the indoor P.C. board, a test run  
operation cannot be performed. (Unfixed data at shipment from factory)  
CODE No. Data at shipment  
SET DATA range  
0001 (No. 1 unit) to 0030 (No. 30 unit)  
Line address  
12  
13  
0099  
0099  
Indoor unit  
address  
0001 (No. 1 unit) to 0064 (No. 64 unit)  
Max. value of indoor units in the identical refrigerant line (Double twin = 4)  
0000 : Individual (Indoor units which are not controlled in a group)  
0001 : Header unit (1 indoor unit in group control)  
0002 : Follower unit (Indoor units other than header unit in group control)  
Group  
address  
14  
0099  
– 82 –  
9-2. Address Setup & Group Control  
<Terminology>  
Indoor unit No.  
Group address  
:N – n = Outdoor unit line address N (Max. 30) – Indoor unit address n (Max. 64)  
:0 = Single (Not group control)  
1 = Header unit in group control  
2 = Follower unit in group control  
Header unit (= 1) :The representative of multiple indoor units in group operation sends/receives signals to/  
from the remote controllers and follower indoor units.  
(*It has no relation with an indoor unit which communicates serially with the outdoor units.)  
The operation mode and setup temperature range are displayed on the remote controller  
LCD. (Except air direction adjustment of louver)  
Follower unit (= 2) :Indoor units other than header unit in group operation  
Basically, follower units do not send/receive signals to/from the remote controllers.  
(Except errors and response to demand of service data)  
Master unit  
:This unit communicates with the indoor unit (sub) which serial-communicates with the  
(Representative unit) outdoor units and sends/receives signal (Command from compressor) to/from the outdoor  
(Header Twin)  
Sub unit  
units as the representative of the cycle control in the indoor units of the identical line  
address within the minimum unit which configures one of the refrigerating cycles of Twin,  
Triple, Double twin.  
:Indoor units excluding the header unit in Twin, Triple, Double twin  
(Subordinate unit) This unit communicates with (Master) indoor unit in the identical line address and performs  
(Follower Twin)  
control synchronized with (Master) indoor unit.  
This unit does not perform the signal send/receive operation with the outdoor units.:  
N judgment for serial signal error.  
9-2-1. System configuration  
1. Single  
2. Single group operation  
Outdoor  
1-1  
Individual  
1-1  
1-2  
Indoor  
(Header/Master)  
Header/Master  
Follower/Sub  
Remote controller  
3. Triple  
1-1  
1-2  
Follower/Sub  
1-3  
Follower/Sub  
Header/Master  
– 83 –  
4. Single group operation  
• Each indoor unit controls the outdoor unit individually.  
2-1  
Header/Sub  
1-1  
Header/Sub  
4-1  
3-1  
Header/Sub  
8-1  
Header/Sub  
Header/Master  
5. Multiple groups operation (Manual address setting)  
2-1  
Header/Sub  
1-1  
Header/Sub  
1-2  
Follower/Sub  
3-1  
3-2  
3-3  
Follower/Sub  
Header/Master  
Follower/Sub  
• Master unit: The master unit receives the indoor unit data (thermo status) of the sub  
(Without identical line address & indoor/outdoor serial) and then finally controls the outdoor  
compressor matching with its own thermo status.  
The master unit sends this command information to the sub unit.  
• Sub unit:  
The sub unit receives the indoor unit data from the master (With identical line address & indoor/  
outdoor serial) and then performs the thermo operation synchronized with the master unit.  
The sub unit sends own thermo ON/OFF demand to the master unit.  
(Example)  
No. 1-1 master unit sends/receives signal to/from No. 1-2 and No. 1-3 sub units.  
(It is not influenced by the line 2 or 3 address indoor unit.)  
– 84 –  
9-2-2. Automatic Address Example from Unset Address (No miswiring)  
1. Standard (One outdoor unit)  
(1-1)  
1-2  
(1-2)  
(1-1)  
1-2  
(1-2)  
(1-3)  
1-1  
Individual  
1-1  
1-3  
1-1  
Header/Master  
Follower/Sub  
Header/Sub  
Follower/Master  
Follower/Sub  
(Header/Master)  
Only turning on source power supply (Automatic completion)  
2. Group operation  
(Multiple outdoor units = Multiple indoor units with serial communication only, without twin)  
2-1  
Header/Sub  
1-1  
Header/Sub  
3-1  
8-1  
Header/Sub  
Header/Master  
(Max. : 8 units)  
Only turning on source power supply (Automatic completion)  
3. Multiple groups operation  
Single  
Twin  
Triple  
2-1  
Header/Sub  
1-1  
Header/Sub  
2-3  
3-1  
Header/Sub  
3-3  
1-2  
Follower/Sub  
Follower/Master  
Follower/Sub  
Change is necessary  
Manually change addresses of the multiple sub units  
simultaneously from the remote controller.  
2-1  
1-1  
1-2  
3-1  
3-2  
3-3  
– 85 –  
9-3. Address Setup (Manual Setting from Remote Controller)  
(Example of 2-lines wiring)  
(Real line: Wiring, Broken line: Refrigerant pipe)  
In case that addresses of the indoor units will be  
determined prior to piping work after wiring work  
• Set an indoor unit per a remote controller.  
Turn on power supply.  
Outdoor  
Outdoor  
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
1
2
3
Indoor  
A B  
Indoor  
A B  
Indoor  
A B  
Indoor  
A B  
Indoor  
A B  
2
1
2
2
2
2
1
2
2
1
3
2
Line address 1  
Indoor unit address 1  
Group address 1  
SET  
CL  
TEST  
1
2
Push  
+
+
buttons  
A B  
simultaneously for 4 seconds or more.  
Remote controller  
(Line address)  
Using the temperature setup  
set 12 to the CODE No.  
For the above example, perform setting by  
connecting singly the wired remote controller  
without remote controller inter-unit wire.  
/
buttons,  
Group address  
Individual  
: 0000  
3
4
5
Using timer time  
/
buttons, set the line address.  
Header unit : 0001  
Follower unit : 0002  
In case of group control  
SET  
Push  
button. (OK when display goes on.)  
(Indoor unit address)  
Using the temperature setup  
/
buttons, set 13 to the CODE No.  
6
7
8
Using timer time  
/
buttons, set 1 to the line address.  
SET  
Push  
button. (OK when display goes on.)  
(Group address)  
Using the temperature setup  
/
buttons, set 14 to the CODE No.  
9
Using timer time  
Folloer unit.  
/
buttons, set 0000 to Individual, 0001 to Header unit, and 0002 to  
SET  
10  
11  
Push  
button. (OK when display goes on.)  
TEST  
Push  
button.  
Setup completes. (The status returns to the usual stop status.)  
TEMP  
ON / OFF  
TIMER SET  
TIME  
FAN  
SAVE  
MODE  
VENT  
2, 5, 8  
3, 6, 9  
END 11  
FILTER  
RESET TEST  
SET  
CL  
SWING/FIX  
UNIT LOUVER  
4, 7, 10  
1
<Operation procedure>  
1 2 3 4 5 6 7 8 9 10 11 END  
– 86 –  
9-4. Confirmation of Indoor Unit No. Position  
1. To know the indoor unit addresses though position of the indoor unit body is recognized  
• In case of individual operation (Wired remote controller : indoor unit = 1 : 1)  
(Follow to the procedure during operation)  
<Procedure>  
ON / OFF  
1
2
Push  
Push  
button if the unit stops.  
button.  
UNIT LOUVER  
Unit No. 1-1 is displayed on LCD.  
TEMP  
ON / OFF  
(It disappears after several seconds.)  
1
The displayed unit No. indicate line address and indoor unit  
address. (When other indoor units are connected to the  
TIMER SET  
TIME  
FAN  
SAVE  
MODE  
VENT  
Operation  
identical remote controller (Group control unit), other unit  
FILTER  
RESET TEST  
UNIT LOUVER  
SET  
CL  
SWING/FIX  
UNIT LOUVER  
numbers are also displayed every pushing  
button.  
2
<Operation procedure>  
END  
1 2  
2. To know the position of indoor unit body by address  
To confirm the unit No. in the group control  
(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)  
<Procedure>  
The indoor unit numbers in the group control are  
successively displayed, and fan, louver, and drain pump  
of the corresponding indoor unit are turned on.  
(Follow to the procedure during operation)  
VENT  
TEST  
1
Push  
for 4 seconds or more.  
• Unit No. is displayed.  
and  
buttons simultaneously  
TEMP  
ON / OFF  
TIMER SET  
TIME  
FAN  
SAVE  
MODE  
VENT  
• Fans and louvers of all the indoor units in the  
group control operate.  
1
3
FILTER  
RESET TEST  
SET  
CL  
SWING/FIX  
UNIT LOUVER  
UNIT LOUVER  
2
Every pushing  
button, the unit  
numbers in the group control are  
successively displayed.  
• The unit No. displayed at the first time indicates  
the header unit address.  
2
<Operation procedure>  
END  
• Fan and louver of the selected indoor unit only  
operate.  
1 2 3  
TEST  
3
Push  
button to finish the procedure.  
All the indoor units in the group control stop.  
– 87 –  
10. DETACHMENTS  
10-1. Compact 4-Way CassetteType  
RAV-SM  
MUT  
∗∗∗  
Ceiling panel: RBC-UM11PG(W)E  
Preparing work:  
1. Before work, be sure to stop the power supply of the air conditioner and turn off switch of the power supply  
breaker. (Otherwise an electric shock may be caused.)  
2. Be sure to put on the gloves when working; otherwise an injury may be caused with parts sharp edges etc.  
No.  
Part name  
Procedure  
Remarks  
1
Suction grille  
1. Detachment  
1)  
1) Loosen the fixing screw.  
2) Slide the fixing bracket toward the outside.  
3) Slide the air intake grille buttons to detach  
the air intake grille from the ceiling panel.  
Lower the grille slowly whilst holding  
4) Slide hooks (2 positions) of the suction grille  
to inner side, and then hang down the  
suction grille.  
2)  
5) Take off the strap that connects the panel  
and the suction grille, and then lift up shaft of  
the suction grille to remove the suction grille.  
3)  
Suction grille  
Ceiling panel  
Hook hole of ceiling panel  
Hook of  
fall-preventive strap  
Hook of suction grille  
2. Attachment  
1) Hook shaft of the suction grille to the panel.  
2) Hook strap of the suction grille to the original position of the panel.  
3) Close the suction grille and slide the hooks outward to fix it.  
4) Slide the fixing bracket toward the inner side.  
5) Tighten the fixing screw.  
– 88 –  
No. Part name  
Procedure  
Remarks  
2
Electric  
parts cover  
1. Detachment  
Screws  
Temporary hanging hook  
1) Perform work of procedure 1 -1.  
2) Take off screws (Ø4 × 10, 3 pcs.) fixing the  
electric parts cover.  
3) Remove the electric parts cover from the  
temporary hanging hook of the electric  
parts cover, and then open the cover.  
2. Attachment  
1) Close the electric parts cover and hook the  
cover hole to the temporary hanging hook.  
2) Tighten the fixing screws. (Ø4 × 10, 3 pcs.)  
Screw  
Unnecessary to remove this hook.  
3
Adjust  
corner cover  
1. Detachment  
1
1) Perform work of procedure of  
-1.  
2) Turn clockwise screws (4 positions) at the  
suction port corner until adjust corner  
cover rises up.  
NOTE)  
1
2
When you work, keep the torque at below 12N•m.  
Do not use an electric screwdriver; otherwise the  
mechanism of adjust corner cover may be  
damaged and not be removed.  
Torque~12N·m  
3) Pull downward the risen-up part of adjust  
corner cover and remove it.  
4) Remove the strap of adjust corner cover.  
1
2
2. Attachment  
1) Attach the strap of adjust corner cover to  
the panel, hook claws of adjust corner  
cover to the panel corner, and then push  
the opposite side into the panel.  
2) Turn screws (4 positions) of the suction  
port corner counterclockwise until bump  
between adjust corner cover and panel  
disappears.  
NOTE)  
When you work, keep the torque at below 12N•m.  
Do not use an electric screwdriver;  
otherwise the mechanism of adjust corner cover  
may be damaged and not be removed.  
Torque~12N·m  
3
– 89 –  
No.  
Part name  
Procedure  
Remarks  
4
Ceiling panel  
1. Detachment  
1) Perform works of procedure  
1
2
-1-,  
-1,  
3
and  
-1.  
2) Remove the flap connector (CN33, White, 5P)  
connected to the control P.C. board and then  
take off the lead wire from the clamp.  
Hanging  
section of tentative  
hook of ceiling panel  
Temporary  
bracket  
Push to remove  
NOTE)  
Remove the connectors after unlocking the lock of  
the housing.  
Drain piping  
corner  
3) Take off screws (M5, 4 pcs.) fixing the ceiling  
panel.  
4) Push the temporary bracket to inner side to  
remove the ceiling panel.  
2. Attachment  
1) Hook the panel to the temporary bracket of  
the drain pan of the main body.  
Ceiling panel  
Temporary  
bracket  
NOTE)  
The panel has directionality.  
Therefore mount the panel according to the temporary  
bracket and the bracket mounting position.  
2) Tighten the fixing screws. (M5, 4 pcs.)  
Washer  
based screw  
Hanging section  
3) Connect flap connector of the  
ceiling panel to the connector  
(CN33, White, 5P) of the  
control P.C. board.  
of temporary bracket  
CN33  
Cable clamp  
– 90 –  
No. Part name  
Procedure  
Remarks  
5
1. Detachment  
1) Perform works of procedure  
Control P.C.  
board  
1
2
-1- and  
-1.  
2) Remove the connectors connected from the control P.C. board to other parts.  
CN33 : Louver motor (5P, White)  
CN34 : Float switch (3P, Red)  
CN41 : Terminal block of remote controller (3P, Blue)  
CN40 : Terminal block of crossover between inside and outside (5P, Black)  
CN68 : Drain pump (3P, Blue)  
CN67 : Terminal block of power supply (3P, Black)  
CN101: TC sensor (2P, Black)  
CN102: TCJ sensor (2P, Red)  
CN104: Room temp sensor (2P, Yellow)  
CN333: Fan motor power supply (5P, White)  
CN334: Fan motor position detection (5P, White)  
NOTE)  
Remove the connectors after  
unlocking the lock of the housing.  
Ferrite core for sensor lead  
3) Unlock the lock of the card  
edge spacer (6 positions)  
and then remove the  
control P.C. board.  
Card edge spacer  
Drawing-out port of lead wire Ferrite core for fan motor  
2. Attachment  
1) Fix the control P.C. board to the card edge spacer. (6 positions)  
2) Connect the connectors as original before being removed in item 1.  
NOTE)  
For drawing of each wire and position of ferrite core, perform wiring same as those before removing.  
If there is incomplete drawing of wire, short or water leakage of the parts may be caused.  
Fix the sensor lead wires with cord clamps (2 positions) so that  
it does not slacken at P.C. board side and draw wires as shown in the figure.  
Cord clamp  
Tighten together the shield wires of the  
sensor lead wires and the remote controller.  
Be careful that other sensor does not fall out.  
Cord clamp  
Arrow view E  
Please note the  
float SW lead wires are  
set at inner side of the  
fan motor lead wires.  
Turn up the sensor lead wires  
and fix surely with the cord clamp.  
Adhere on the  
transformer.  
<Details of sensor lead wire drawing>  
E
Cord clamp  
As shown in the figure,  
hook the sensor lead wires  
to claw of the piping cover  
and then pass them so that  
they are stored in the groove.  
Turn up the fan motor lead wires  
and fix surely with the cord clamp.  
(There should be no catching of  
lead wire by P.C. board.)  
After mounting the piping  
cover, check each lead wire  
does not hit the liquid pipe.  
Clamp (yellow, gray, black) lead wires  
of the fan motor and arrange them  
as shown in the figure.  
<Details of piping cover assembly and mounting>  
<Details of fan motor lead wire drawing>  
– 91 –  
No. Part name  
Procedure  
Remarks  
1. Detachment  
1) Perform works of procedure  
6
Electric  
parts box  
1
2
-1-and  
-1.  
2) Remove connectors of the lead wire connected to the following connectors of the control P.C.  
board.  
CN33 : Louver motor (5P, White)  
CN34 : Float switch (3P, Red)  
CN68 : Drain pump (3P, Blue)  
CN101: TC2 sensor (2P, Black)  
CN102: TCJ sensor (2P, Red)  
CN333: Fan motor power supply (5P, White)  
CN334: Fan motor position detection (5P, White)  
NOTE)  
Remove the connectors after unlocking the lock of the housing.  
3) Remove each lead wire  
from cord clamps in the  
electric parts box.  
Ferrite core for sensor lead  
4) Remove the power supply  
wiring, remote controller  
wiring, and crossover wiring.  
5) Take off screws  
(Ø4 × 10, 2 pcs.)  
Card edge spacer  
Drawing-out port of lead wire Ferrite core for fan motor  
2. Attachment  
1) Tighten screws (Ø4 × 10, 2 pcs.) fixing the electric parts box.  
2) Connect the connectors as original before being removed in item 1.  
3) Perform power supply wiring, remote controller wiring, and crossover wiring between inside  
and outside.  
NOTE)  
For drawing of each wire and position of ferrite core, perform wiring same as those before removing.  
If there is incomplete drawing of wire, short or water leakage of the parts may be caused.  
Fix the sensor lead wires with cord clamps (2 positions) so that  
it does not slacken at P.C. board side and draw wires as shown in the figure.  
Cord clamp  
Tighten together the shield wires of the  
sensor lead wires and the remote controller.  
Be careful that other sensor does not fall out.  
Cord clamp  
Arrow view E  
Please note the  
float SW lead wires are  
set at inner side of the  
fan motor lead wires.  
Turn up the sensor lead wires  
and fix surely with the cord clamp.  
Adhere on the  
transformer.  
<Details of sensor lead wire drawing>  
E
Cord clamp  
As shown in the figure,  
hook the sensor lead wires  
to claw of the piping cover  
and then pass them so that  
they are stored in the groove.  
Turn up the fan motor lead wires  
and fix surely with the cord clamp.  
(There should be no catching of  
lead wire by P.C. board.)  
After mounting the piping  
cover, check each lead wire  
does not hit the liquid pipe.  
Clamp (yellow, gray, black) lead wires  
of the fan motor and arrange them  
as shown in the figure.  
<Details of piping cover assembly and mounting>  
<Details of fan motor lead wire drawing>  
– 92 –  
No. Part name  
7
Procedure  
Remarks  
Bell mouth  
1. Detachment  
1) Perform work of procedure  
1
-1.  
Fixing claws  
for lead wires  
2) Take off the lead wires of the drain pump, float  
switch, and fan motor from the bell mouth.  
Bell mouth  
3) Take off fixing screws of the bell mouth.  
(Ø4 × 10, 4 pcs.)  
2. Attachment  
1) Mount the bell mouth with screws.  
(Ø4 × 10, 4 pcs.)  
2) Perform wiring as original before being  
removed.  
NOTE)  
Pinch lead wire of the drain pump and float switch  
with lead wire fixing claws of the bell mouth and  
perform wiring along the guide.  
4 screws  
Fixing claws  
for lead wires  
8
Turbo fan  
1. Detachment  
7
1) Perform work of procedure  
-1.  
Fan motor fixing  
M6 nut  
Drawing-out port of  
fan motor lead wire  
2) Take off the nut (M6 nut 1 pc.) of the turbo fan.  
NOTE)  
Use a box wrench for attachment and detachment of  
the turbo fan. If using a monkey wrench etc, the other  
parts may be damaged in work.  
2. Attachment  
1) Insert the turbo fan into the fan motor so that  
boss of the turbo fan matches with cut surface  
of the fan motor, and then tighten it with nut.  
NOTE)  
Tightening torque of turbo fan: 5.9 ± 0.6N.m  
Apply looseness-preventing agent to the nut after  
tightening.  
Turbo fan  
– 93 –  
No. Part name  
Procedure  
Remarks  
9
Fan motor  
1. Detachment  
1) Perform work of procedure  
Fixing nut for fan motor  
8
.
2) Take off screws fixed with lead holding bracket  
of the fan motor. (Ø4 × 10, 2 pcs.)  
3) Open wiring holding part of the fan motor lead  
holding bracket and then take off the fan motor  
lead wire from the bracket.  
4) Take off fixing nuts for the fan motor to remove  
the fan motor.(M 3 pcs.)  
Fan motor  
NOTE)  
Use a box wrench for attachment and detachment of  
the fan motor fixing nuts; otherwise contact or  
damage for other parts may be caused.  
Fan motor  
earthh wire  
Fixing screw  
Holding metal fitting  
for fan motor lead wire  
2. Attachment  
1) Mount the fan motor with the fixing nuts.  
NOTE)  
Tightening torque of turbo fan: 5.9 ± 0.6N.m  
Apply looseness-preventing agent (as paints) to the  
nut after tightening.  
2) Attach the fan motor lead wire holder.  
NOTE)  
• For the fan motor lead wire, fix the lead wire holding  
bracket along concave part of the ceiling panel.  
(There is no catch-in of lead wire and ceiling panel.)  
• When fixing the lead wire bracket, tighten fan motor  
earth together with the lead wire.  
• For this work, do not use an electric screwdriver.  
Take note the damage of earth terminal.  
3) Bend the lead wire holding part and fix the fan  
motor lead wire.  
Wiring holding bracket  
NOTE)  
Be sure that the lead wire does not come to contact  
with the heat exchanger.  
Fan motor lead wire  
Concave part  
of ceiling panel  
– 94 –  
No.  
Part name  
Drain pan  
Procedure  
Remarks  
10  
1. Detachment  
1) Perform works of procedure  
2 screws  
4
7
-1 and  
-1.  
2) Remove the drain cap and extract drain water  
accumulated in the drain pan.  
NOTE)  
Socket of drain pan  
When removing the drain cap, be sure to receive  
drain water with a bucket, etc.  
3) Take off screws fixing the drain pan to remove  
the drain pan. (Ø4×10, 4 pcs.)  
Drain pan  
2. Attachment  
1) Insert the drain cap into the drain pan.  
NOTE)  
Put a stick or others into hole at center of the drain  
cap, and then insert the drain cap until it strikes on  
the socket of the drain pan.  
2 screws  
2) Draw each lead wire to the correct positions,  
and then insert the drain pan into the main  
unit.  
NOTE)  
Piping holder rib  
Draw lead wires of the drain pump and the float  
switch along the guide of the cabinet. Insert the drain  
pan along the guides of sensors (TC1, TC2, TCJ)  
and PMV lead wire.  
The drain pan and each lead wire are not caught in;  
otherwise water leakage may be caused.  
3) Fix the drain pan with screws. (Ø4 × 10, 4 pcs.)  
Piping holder  
Lead wire  
Drain pump  
assembly  
1. Detachment  
11  
Drain pummp assembly  
1) Perform work of procedure 10 -1.  
2) Pick up the hose band and slide it from the  
pump connecting part to remove the drain  
hose.  
Hose band  
3) Take off screws (Ø4 × 10, 3 pcs.) fixing the  
drain pump assembly, and then move hooking  
claw (1 position) of the main body from the  
drain pump assembly to remove the drain  
pump assembly.  
2. Attachment  
White marked position  
1) Fix the drain pump assembly as original.  
Drainn hose  
NOTE)  
For fixing, use a hooking claw (1 position) and  
screws (3 positions).  
When screwing, be sure not to run on the hooking  
claw at main body side.  
2) Mount the drain hose and the hose band as  
original.  
NOTE)  
Insert the drain hose up to the end of pump connect-  
ing part, and then put the band at white marked  
position of the hose.  
Fixingg screw  
for draain pump  
Hooking claw  
for drain pump  
– 95 –  
No. Part name  
Procedure  
Remarks  
12  
Heat  
exchanger  
1. Detachment  
1) Recover refrigerant gas.  
2) Remove the refrigerant pipe at indoor unit  
side.  
Pipingg cover  
3) Perform work of procedure 10 -1.  
4) Take off screws (Ø4 × 10, 3 pcs.) fixing the  
piping cover to remove the piping cover.  
5) While holding the heat exchanger, remove  
fixing band and fixing screws (Ø4 × 10, 3 pcs.)  
and then remove the heat exchanger.  
2. Attachment  
1) Mount parts in order, heat exchanger  
fixing band piping cover drain pan  
bell mouth electric parts box as original.  
3 screws  
NOTE)  
Arrange wires as original.  
2) Attach the removed connectors and wires as  
original.  
3) Connect the refrigerant pipe as original, and  
then perform vacuuming.  
Fixing band  
Fixing band for  
heat exchanger  
<Details of sensor lead wire drawing>  
TCJ sensor  
(Black)  
TC sensor  
(Red)  
Wind pipe cover over the header,  
attach a sensor on it.  
(Do not set the head of tie wrap upward.)  
2 fixing screws for heat exchanger  
– 96 –  
10-2. Concealed DuctType  
RAV-SM  
BT  
∗∗∗ ∗  
Be sure to turn off the power supply or circuit breaker before disassembling work  
No. Part name Procedure  
Remarks  
 Electrical parts 1. Remove the air filter.  
Screws  
(Fixing electrical parts cover and box)  
box  
2. Remove the set screws (2 positions) of the  
Electrical parts cover  
electrical parts cover.  
3. Remove the electrical parts cover.  
4. Remove the set screws (2 positions) of the  
electrical parts box.  
5. Remove the electrical parts box.  
The electrical parts box is fixed to the main  
unit with claws at the right side.  
1 -2  
1 -3  
Lift up it once and pull toward you.  
Then claws come off.  
Screws  
(Fixing electrical parts box and main unit)  
Electrical parts box  
In this time, remove connectors of TA sensor,  
TC sensor and TCJ sensor if necessary.  
1 -4  
1 -5  
Claw (Reverse side)  
Multi blade fan 1. Remove the air filter.  
Hexagon head screws  
(Fixing fan assembly and main unit)  
2. Remove the connector of the fan motor P.C.  
board.  
3. Remove the hexagon head screw  
(562: 2, 802, 1102, 1402 : 3 positions) of  
fixing fan assembly and main unit.  
4. Remove the fan assembly from main unit.  
The fan assembly is fixed to the main unit  
with claws (3 positions) at the upper side.  
2 -3  
Lift up it once and pull toward rear side.  
Then claws come off.  
5. Remove the set screws (4 positions) of  
fixing fan case and fan cover.  
6. Remove the fan cover.  
7. Loosen the sets crew of the Multi blade fan  
using hexagon wrench.  
2 -4  
8. Pull the Multi blade fan towered fan case  
side.  
Fixing claw (Main unit)  
Fixing hole (Fan assembly)  
Then fans come off.  
Multi blade fan  
Fan case  
Fan case cover  
Set screw  
2 -5  
2 -6  
Screws (Fixing fan case cover)  
– 97 –  
No.  
Part name  
Procedure  
Remarks  
ƒ Fan motor  
1. Remove the Multi blade fan.  
2. Remove the hexagon head screw of fixing  
fan motor holder.  
Fan motor  
Fan motor holder  
3. Remove the fan motor holder  
(2 positions).  
3 -2  
3 -3  
Screws  
(Fixing fan motor holder)  
Drain pan  
1. Take down the main unit and then treat the  
drain pan on the floor.  
Screws (Fixing lower plate)  
2. Remove the set screws (562 : 7, 802, 1102,  
1402 : 9 positions) of fixing lower plate.  
4 -2  
4 -3  
3. Remove the lower plate from main unit.  
4. Remove the set screws (562 : Nothing, 802 :  
2 positions, 1102, 1402 : 4 positions) of  
fixing drain pan holder and main unit.  
5. Remove the drain pan holder (562 : Nothing,  
802 : 1 position, 1102, 1402 : 2 positions)  
from main unit.  
Lower plate  
Screws  
(Fixing drain pan holder)  
6. Remove the drain pan.  
Pull it lower side.  
Screws (Fixing drain pan holder)  
4 -4  
4 -5  
Drain pan holder Drain pan  
Float switch  
1. Remove the drain pan.  
2. Remove the set screw (1 position) of fixing  
float switch holder.  
Float switch holder  
Float switch  
3. Remove the plastics nut of foxing float  
switch.  
4. Remove the float switch.  
5 -2  
Screw  
(Fixing float switch holder)  
Float switch (View from reverse side)  
5 -3  
Float switch holder  
Plastic nut  
– 98 –  
No.  
Part name  
Procedure  
Remarks  
Drain pump  
1. Remove the drain pan and float switch.  
2. Remove the set screws (3 positions) of  
fixing drain pump plate and main unit.  
Drain pump  
Drain pump holder  
3. Remove the set screws (3 positions) of  
fixing drain pump plate and drain pump.  
6 -2  
Screws (Fixing drain pump holder)  
Screws (Fixing plate and drain pump)  
6 -3  
Drain pump holder  
(6) -3. View from reverse side of drain pump  
Checking port cover (Right side)  
TC, TCJ sensor 1. Remove the set screws (5 positions) and  
check port cover (right side).  
2. Pull out the sensor is inserted into pipe of  
the heat exchanger.  
7 -1  
Screws (Fixing check port cover (Right side))  
Check port cover (Left side)  
ˆ Heat  
exchanger  
1. Take down the main unit and then treat the  
heat exchanger on the floor.  
2. Remove the drain pan.  
3. Remove the check port cover (right side).  
4. Remove the set screws (6 positions) and  
check port cover (left side).  
5. Remove the set screws (2 positions) of  
fixing heat exchanger and main unit  
(left side).  
6. Remove the set screws (7 positions) of  
fixing heat exchanger and main unit  
(front right side).  
8 -4  
Screws (Fixing check port cover (Left side))  
Screws (Fixing heat exchanger)  
8 -5  
Main unit (Left side)  
Main unit (Front side)  
8 -6  
Screws  
– 99 –  
10-3. CeilingType  
RAV-SM  
CT  
∗∗∗ ∗  
Be sure to turn off the power supply or circuit breaker before disassembling work  
No. Part name Procedure  
Remarks  
 Suction grille 1. Remove the screws of air intake  
Pull out suction grille  
while pushing hook.  
grille fixing knob on a side of each  
filter.  
Hinge  
2. Slide the suction grille fixing knobs  
(2 positions) toward the arrow  
direction of left figure, and open  
the suction grille.  
3. Under the condition of the suction  
grille opened, push the hook  
section of hinges (2 positions) at  
the rear side, and then pull out the  
suction grille.  
Suction grille  
fixing knob  
Suction grille  
Protector  
Side panel  
1. Open the suction grille.  
2. After removing the side panel  
screws (2 positions), slide the side  
panel forward and then remove it.  
Side panel  
Level flap  
Slide forward.  
ƒ Electrical  
1. Remove the suction grille.  
Electrical parts cover  
parts box  
2. Loosen the set screws  
(2 positions) of the electrical parts  
cover.  
3. Remove the electrical parts cover.  
4. Remove the set screws  
(2 positions) of the electrical parts  
box.  
3 -2  
3 -3  
5. Remove the electrical parts box.  
Screws  
(Fixing electrical parts cover and box)  
In this time, remove connectors of TA  
sensor, TC sensor and TCJ sensor if  
necessary.  
3 -4  
3 -5  
Electrical parts box  
Screws  
(Fixing electrical parts box and main unit)  
– 100 –  
No.  
Part name  
Procedure  
Remarks  
Multi blade fan 1. Remove the suction grille.  
Screws  
(Fixing reinforcing bar and main unit)  
motor  
2. Remove the connector of the fan  
motor from P.C. board.  
3. (SM802, SM1102, SM1402CT-E only)  
Remove the set screw (1 position) to  
fixing and reinforcing bar.  
(Slide the reinforcing bar toward  
arrow side on the left figure.)  
4. Push the fan cover fixing hooks  
(2 positions) forward fan cover side  
and remove the fan cover.  
4 -3  
4 -4  
4 -5  
5. (SM1102, SM1402CT-E only)  
Reinforcing bar  
Remove the hexagon head screws (2  
positions) to fix bearing and the  
bearing.  
6. Remove the hexagon head screw of  
fixing fan motor and fan motor holder  
then the assembly removed from the  
main unit.  
7. Loosen the sets crew of the multi  
blade fan using hexagon wrench.  
8. Pull the multi blade fan towered fan  
case side. Then fans come off.  
Fan cover fixing hook  
Fan cover (Lower side)  
Bearing  
Hexagon head screws  
(Fixing bearing and main unit)  
Fan motor holder  
Fan motor  
4 -6  
Hexagon screws  
(Fixing fan motor and main unit)  
4 -7  
Multi blade fan  
Set screw of multi blade fan  
– 101 –  
No.  
Part name  
Procedure  
Remarks  
Drain pan  
1. Take down the main unit and then treat  
the drain pan on the floor.  
Screws  
(Fixing lower plate and main unit)  
2. Remove the both side panels and suction  
grilles.  
3. (SM802, SM1102, SM1402CT-E only)  
Remove the set screw (1 position) to  
fixing and reinforcing bar.  
(Slide the reinforcing bar toward arrow  
side on the right figure.)  
5 -4  
4. Remove the set screws (9 positions) of  
fixing lower plate.  
Heat insulation  
The screw that fixed drain pan and  
main unit is under this insulation.  
5. Remove the heat insulation on the drain  
pan.  
(SM562, SM802 : 1 position, SM1102,  
SM1402 : 2 positions)  
6. Remove the set screws  
(SM562, SM802 : 1 position, SM1102,  
SM1402 : 2 positions) of fixing drain pan  
and main unit.  
7. Remove the drain pan.  
Pull it lower side.  
5 -5  
5 -6  
Vertical grille  
1. Remove the drain pan.  
2. Remove the set screws (2 positions) of  
fixing vertical grille.  
Vertical grille  
3. Remove the vertical grille.  
Screws  
6 -2  
(Fixing drain pan and vertical grille)  
Louver motor,  
Lover drive  
1. Remove the side cover (right side only).  
2. Remove the set screws (2 positions) and  
louver motor.  
Screws  
(Fixing louver drive member and main unit)  
member  
3. Remove the set screws (2 positions) and  
louver drive member.  
Louver drive  
member  
Louver  
motor  
7 -3  
Screws  
(Fixing louver motor and louver drive member)  
– 102 –  
No.  
Part name  
Procedure  
Remarks  
ˆ Horizontal  
1. Push the louver holder toward arrow  
direction of right figure, and pull out  
the center shaft (SM562, SM802 :  
1 position, SM1102, SM1402 :  
louver  
2 positions) from louver holder.  
2. Pull off the left and right chaft of  
horizontal louver.  
8 -1  
Louver holder  
Screws  
Shaft of  
horizontal louver  
TC, TCJ sensor 1. Remove the drain pan.  
2. Remove the set screws (4 positions)  
(Fixing heat exchanger support)  
and heat exchanger support.  
3. Pull out the sensor is inserted into  
pipe of the heat exchanger.  
9 -3  
Heat exchanger support  
Heat exchanger  
Š Heat  
exchanger  
1. Take down the main unit and then  
treat the heat exchanger on the floor.  
2. Remove the drain pan.  
3. Remove the set screws (6 positions)  
of fixing heat exchanger and main  
unit.  
10 -3  
Screws  
(Fixing heat exchanger and main unit)  
– 103 –  
11. EXPLODED VIEWS AND PARTS LIST  
11-1. Compact 4-way CassetteType  
RAV-SM404MUT , RAV-SM454MUT , RAV-SM564MUT  
234  
223  
202  
221  
203  
231  
228  
201  
209  
236  
235  
241  
205  
247  
233  
237  
222  
224  
242  
226  
241  
225  
227  
230  
238,  
239  
211  
219 216 217  
– 104 –  
Model name RAV-SM  
Location  
No.  
Part No.  
Description  
404MUT-E 454MUT-E 564MUT-E  
201  
202  
203  
205  
209  
211  
213  
215  
216  
217  
219  
220  
221  
222  
223  
224  
225  
226  
227  
228  
230  
231  
233  
234  
235  
236  
237  
238  
239  
240  
241  
242  
247  
43120225 FAN, ASSY TURBO  
43122094 BELLMOUTH  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
3
1
1
1
3
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
3
1
1
1
3
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
3
1
1
1
3
1
1
1
1
1
3
43172185 PAN ASSY, DRAIN  
43121738 MOTOR, FAN  
4314J329 REFRIGERATION CYCLE ASSY  
4314Q034 DISTRIBUTOR ASSY  
43047685 NUT, FLARE, 1/4 IN  
43149351 SOCKET  
43047688 NUT, FLARE, 1/2, IN  
43149353 SOCKET  
43147195 BONNET, 1/2 IN  
43049697 BONNET  
43170244 HOSE, DRAIN  
43079249 BAND, HOSE  
43060029 FILTER,N0ISE  
43163052 HOLDER, LEAD, FAN MOTOR  
43119482 COVER, ASSY BODY  
43170248 HOSE, DRAIN  
43119483 COVER, PIPE  
43097212 NUT  
43019904 HOLDER, SENSOR (TS)  
43179135 BAND, HOSE  
43139137 RUBBER, CUSHION  
43162056 COVER, E-BOX  
43177001 PUMP, DRAIN  
43151289 SWITCH, FLOAT  
43179126 RUBBER, PUMP DRAIN  
43166011 REMOTE CONTROLLER, SX-A4EE  
43166012 REMOTE CONTROLLER, SX-A5EE  
43166004 REMOTE CONTROLLER, SX-A11JE2  
43166006 REMOTE CONTROLLER, WH-H1JE2  
431S8221 OWNER'S MANUAL  
43197155 WASHER  
– 105 –  
Model name RAV-SM  
Location  
No.  
Part No.  
Description  
404MUT-TR 454MUT-TR 564MUT-TR  
201  
202  
203  
205  
209  
211  
213  
215  
216  
217  
219  
220  
221  
222  
223  
224  
225  
226  
227  
228  
230  
231  
233  
234  
235  
236  
237  
238  
239  
240  
241  
242  
247  
43120225 FAN, ASSY TURBO  
43122094 BELLMOUTH  
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
3
1
1
1
3
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
3
1
1
1
3
1
1
1
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
3
1
1
1
3
1
1
1
1
1
3
43172185 PAN ASSY, DRAIN  
43121738 MOTOR, FAN  
4314J329 REFRIGERATION CYCLE ASSY  
4314Q034 DISTRIBUTOR ASSY  
43047685 NUT, FLARE, 1/4 IN  
43149351 SOCKET  
43047688 NUT, FLARE, 1/2, IN  
43149353 SOCKET  
43147195 BONNET, 1/2 IN  
43049697 BONNET  
43170244 HOSE, DRAIN  
43079249 BAND, HOSE  
43060029 FILTER,N0ISE  
43163052 HOLDER, LEAD, FAN MOTOR  
43119482 COVER, ASSY BODY  
43170248 HOSE, DRAIN  
43119483 COVER, PIPE  
43097212 NUT  
43019904 HOLDER, SENSOR (TS)  
43179135 BAND, HOSE  
43139137 RUBBER, CUSHION  
43162056 COVER, E-BOX  
43177001 PUMP, DRAIN  
43151289 SWITCH, FLOAT  
43179126 RUBBER, PUMP DRAIN  
43166011 REMOTE CONTROLLER, SX-A4EE  
43166012 REMOTE CONTROLLER, SX-A5EE  
43166004 REMOTE CONTROLLER, SX-A11JE2  
43166006 REMOTE CONTROLLER, WH-H1JE2  
431S8222 OWNER'S MANUAL  
43197155 WASHER  
– 106 –  
Electric parts  
401  
405  
403  
404  
402  
Model name RAV-SM  
Location  
No.  
Part No.  
Description  
404MUT-E 454MUT-E 564MUT-E  
(TR)  
(TR)  
(TR)  
401  
402  
403  
404  
405  
43050425 SENSOR ASSY, SERVICE, TC  
43050426 SENS0R, SERVICE, TA  
4316V461 PC BOARD ASSY, MCC-1402  
43160568 TERMINAL, 2P  
2
1
1
1
1
2
1
1
1
1
2
1
1
1
1
43160565 TERMINAL BLOCK, 3P, 20A  
– 107 –  
11-2. Concealed DuctType  
RAV-SM564BT-E, RAV-SM564BT-TR  
240,  
241  
242  
229  
207  
216  
227  
239  
202  
203, 902, 905  
204, 206, 906  
226  
223  
231  
217  
232  
228  
215  
238  
236,  
237  
234  
– 108 –  
Model name  
Location  
No.  
Part No.  
Description  
RAV-SM564BT-E RAV-SM564BT-TR  
202  
203  
204  
206  
207  
215  
216  
217  
223  
226  
227  
228  
229  
231  
232  
234  
236  
237  
238  
239  
240  
241  
242  
902  
905  
906  
43019904 HOLDER, SENSOR (TS)  
43047692 BONNET  
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
43047685 NUT, FLARE, 1/4 IN  
43049697 BONNET  
43079249 BAND, HOSE  
43120239 FAN, MULTI BLADE  
43121747 PUMP ASSY, WIRING  
4312C021 MOTOR, FAN  
4314Q015 DISTRIBUTOR ASSY  
4314J268 REFRIGERATION CYCLE ASSY  
43151294 SWITCH, FLOAT  
43160553 LEAD, MOTOR, FAN  
43170233 HOSE, DRAIN  
43172168 PAN ASSY, DRAIN  
43179110 PLUG  
43180311 AIR FILTER  
43166011 REMOTE CONTROLLER, SX-A4EE  
43166012 REMOTE CONTROLLER, SX-A5EE  
43166004 REMOTE CONTROLLER, SX-A11JE2  
43166006 REMOTE CONTROLLER, WH-H1JE2  
431S8224 OWNER'S MANUAL  
431S8223 OWNER'S MANUAL  
43196012 BUSHING  
1
2
2
1
1
2
2
1
1
43149351 SOCKET  
43047688 NUT, FLARE, 1/2, IN  
43149353 SOCKET  
– 109 –  
RAV-SM804BT-E, RAV-SM804BT-TR  
230  
221  
204  
228,  
229  
211  
219  
202  
203, 904, 905  
901, 902, 903  
222  
218  
235  
216  
212  
223  
220  
210  
232,  
233  
234  
224  
– 110 –  
Model name  
Location  
No.  
Part No.  
Description  
RAV-SM804BT-E RAV-SM804BT-TR  
202  
203  
204  
210  
211  
212  
216  
218  
219  
220  
221  
222  
223  
224  
228  
229  
230  
232  
233  
234  
235  
901  
902  
903  
904  
905  
43019904 HOLDER, SENSOR (TS)  
43047609 BONNET  
2
1
1
2
1
1
1
1
1
1
1
1
1
2
2
1
1
2
1
1
1
1
1
1
1
1
1
2
1
43079249 BAND, HOSE  
43120239 FAN, MULTI BLADE  
43121747 PUMP ASSY, WIRING  
4312C020 MOTOR, FAN  
4314Q016 DISTRIBUTOR ASSY  
4314J269 REFRIGERATION CYCLE ASSY  
43151294 SWITCH, FLOAT  
43160553 LEAD, MOTOR, FAN  
43170233 HOSE, DRAIN  
43172167 PAN ASSY, DRAIN  
43179110 PLUG  
43180312 AIR FILTER  
431S8224 OWNER'S MANUAL  
431S8223 OWNER'S MANUAL  
43196012 BUSHING  
1
2
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
1
43166011 REMOTE CONTROLLER, SX-A4EE  
43166012 REMOTE CONTROLLER, SX-A5EE  
43166004 REMOTE CONTROLLER, SX-A11JE2  
43166006 REMOTE CONTROLLER, WH-H1JE2  
43049776 SOCKET  
43194029 BONNET  
43149355 NUT, FLARE, 3/8, IN  
43149352 NUT, FLARE, 5/8, IN  
43149354 SOCKE  
– 111 –  
RAV-SM1104BT-E, RAV-SM1404BT-E,  
RAV-SM1104BT-TR, RAV-SM1404BT-TR  
230, 231  
232  
204  
223  
211  
220  
221  
237  
215  
202  
214  
203, 904  
213  
901, 902, 903  
219  
224  
236  
212  
225  
222  
210  
234, 235  
226  
– 112 –  
Model name RAV-SM  
Location  
No.  
Part No.  
Description  
1104BT-E 1404BT-E 1104BT-TR 1404BT-TR  
202  
203  
204  
210  
211  
212  
213  
214  
215  
219  
220  
221  
222  
223  
224  
225  
226  
230  
231  
232  
234  
235  
236  
237  
901  
902  
903  
904  
43019904 HOLDER, SENSOR (TS)  
43047609 BONNET  
2
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
2
2
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
2
1
2
1
1
3
1
1
1
1
1
1
1
1
1
1
1
1
2
1
43079249 BAND, HOSE  
43120239 FAN, MULTI BLADE  
43121747 PUMP ASSY, WIRING  
4312C021 MOTOR, FAN  
43125131 BEARING, SHAFT  
43125162 COUPLING  
43125163 SHAFT  
4314Q017 DISTRIBUTOR ASSY  
4314J270 REFRIGERATION CYCLE ASSY  
43151294 SWITCH, FLOAT  
43160553 LEAD, MOTOR, FAN  
43170233 HOSE, DRAIN  
43172166 PAN ASSY, DRAIN  
43179110 PLUG  
43180311 AIR FILTER  
431S8224 OWNER'S MANUAL  
431S8223 OWNER'S MANUAL  
43196012 BUSHING  
1
2
1
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
1
1
43166011 REMOTE CONTROLLER, SX-A4EE  
43166012 REMOTE CONTROLLER, SX-A5EE  
43166004 REMOTE CONTROLLER, SX-A11JE2  
43166006 REMOTE CONTROLLER, WH-H1JE2  
43049776 SOCKET  
43194029 BONNET  
43149355 NUT, FLARE, 3/8, IN  
43149352 NUT, FLARE, 5/8, IN  
– 113 –  
Electric parts  
405  
407  
404  
406  
Model name RAV-SM  
Location  
Part No.  
Description  
564BT-E 804BT-E 1104BT-E 1404BT-E  
No.  
(TR)  
(TR)  
(TR)  
(TR)  
401  
402  
403  
404  
405  
406  
407  
43050425 SENSOR ASSY, SERVICE, TC6  
43050426 SENSOR, SERVICE, TA  
43158193 REACTOR, CH-43-2Z-T  
43160565 TERMINAL BLOCK, 3P, 20A  
4316V462 PC BOARD ASSY, MCC-1402  
43155203 CAPACITOR KIT, SERVICE  
43160568 TERMINAL, 2P  
2
2
2
2
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
– 114 –  
11-3. CeilingType  
RAV-SM564CT , RAV-SM804CT , RAV-SM1104CT , RAV-SM1404CT  
248  
247  
266  
201, 202, 203  
244, 245, 246  
260  
211  
261  
258  
222, 223, 224  
263  
264  
236, 237, 238,  
239, 254, 255  
242  
233, 234, 235,  
253, 256, 257  
240  
226  
267  
210  
214  
217  
225  
231  
232  
249  
259,  
268  
252  
207, 208, 209  
204, 205, 206  
265  
227, 228  
227  
229  
251  
250  
230  
212  
226  
262  
212, 213  
226  
232  
216  
215  
217  
41  
43  
2172  
225  
225  
SM56(Fan assembly)  
SM80(Fan assembly)  
221  
218, 219  
220  
– 115 –  
Model name RAV-SM  
Location  
No.  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
226  
227  
228  
229  
230  
231  
232  
233  
234  
235  
236  
237  
238  
239  
240  
241  
242  
243  
244  
245  
246  
247  
248  
249  
250  
251  
252  
253  
254  
255  
256  
257  
258  
259  
260  
261  
262  
263  
264  
265  
266  
267  
269  
270  
271  
Part No.  
Description  
564CT-E  
804CT-E  
1104CT-E  
1404CT-E  
4314J271 REFRIGERATION CYCLE A'SSY  
4314J272 REFRIGERATION CYCLE A'SSY  
4314J367 REFRIGERATION CYCLE ASSY  
43172188 PAN DRAIN, ASS'Y  
43172189 PAN DRAIN, ASS'Y  
43172190 PAN DRAIN, ASS'Y  
43100356 PANEL, UNDER  
1
1
1
1
1
1
1
1
1
1
43100357 PANEL, UNDER  
43100358 PANEL, UNDER  
1
1
1
1
2
1
1
1
1
1
2
1
43102647 COVER, SIDE (RIGHT)  
43102648 COVER, SIDE (LEFT)  
43109407 GRILLE, INLET  
1
1
2
1
1
43109408 GRILLE, INLET  
2
43121741 MOTOR, FAN  
43121742 MOTOR, FAN  
1
43121743 MOTOR, FAN  
1
3
1
1
1
1
43120227 FAN, MULTI BLADE  
43166011 REMOTE CONTROLLER, SX-A4EE  
43166012 REMOTE CONTROLLER, SX-A5EE  
43166004 REMOTE CONTROLLER, SX-A11JE2  
43166006 REMOTE CONTROLLER, WH-H1JE2  
4314Q090 DISTRIBUTOR ASSY  
43147701 DISTRIBUTOR A'SSY  
43147702 DISTRIBUTOR A'SSY  
43122084 CASE, FAN, LOWER  
43122085 CASE, FAN, UPPER  
43180314 AIR FILTER  
2
1
1
1
1
1
4
1
1
1
1
4
1
1
1
1
1
1
4
4
1
2
1
2
1
1
1
4
4
1
2
1
2
1
1
2
2
2
3
3
43180315 AIR FILTER  
2
1
2
43108014 BASE, RECEIVER  
43179136 BAND, HOSE  
1
2
43125131 BEARING, SHAFT  
43125162 COUPLING  
1
1
43047685 NUT, FLARE, 1/4 IN  
43049776 SOCKET  
1
1
1
43149351 SOCKET  
1
1
43047688 NUT, FLARE, 1/2, IN  
43149352 NUT, FLARE, 5/8, IN  
43149353 SOCKET  
1
1
1
1
1
43149354 SOCKET\  
1
1
1
1
1
1
1
43149326 COVER, BACK BASE  
43125164 SHAFT  
43125165 SHAFT  
43125159 BEARING  
1
1
1
1
43109409 GRILLE A'SSY, HORIZONTAL  
43109410 GRILLE A'SSY, HORIZONTAL  
43109411 GRILLE A'SSY, HORIZONTAL  
43107260 SUPPORT, GRILLE HORIZONTAL  
43122086 GRILLE A'SSY, VERTICAL  
43179129 CAP DRAIN  
1
1
2
3
1
6
3
1
1
1
2
3
1
6
3
1
1
1
2
1
4
2
1
1
2
1
4
2
1
1
43107254 HINGE, GRILLE INLET  
43107255 HOOK, GRILLE INLET  
43170234 HOSE, DRAIN  
43047609 BONNET  
43047692 BONNET  
1
43194029 BONNET  
1
1
1
1
1
1
43149355 NUT, FLARE, 3/8, IN  
43049697 BONNET  
1
2
1
1
1
1
1
1
1
1
43019904 HOLDER, SENSOR (TS)  
431S8225 OWNER'S MANUAL  
43121746 DRIVER A'SSY HORIZONTAL LOUVER  
43160556 LEAD, LOUVER HORIZONTAL  
43108016 MARK TOSHIBA  
2
1
1
1
1
1
1
1
1
2
1
1
1
1
1
1
2
1
2
3
3
3
2
1
1
1
1
1
1
2
1
2
3
3
3
43162049 BUSHING 50DIA  
43162050 BUSHING 56DIA  
43197189 SCREW, FIX DRAIN PAN  
43107252 SHAFT, HOLIZONTAL LOUVER  
43139153 SPACER, BEARING  
43107285 HOOK, GRILLE INLET  
43197202 NUT, FLANGE  
2
2
2
2
2
2
43197203 SCREW, PAINT, M3  
– 116 –  
Model name RAV-SM  
Location  
No.  
201  
202  
203  
204  
205  
206  
207  
208  
209  
210  
211  
212  
213  
214  
215  
216  
217  
218  
219  
220  
221  
222  
223  
224  
225  
226  
227  
228  
229  
230  
231  
232  
233  
234  
235  
236  
237  
238  
239  
240  
241  
242  
243  
244  
245  
246  
247  
248  
249  
250  
251  
252  
253  
254  
255  
256  
257  
258  
260  
261  
262  
263  
264  
265  
266  
267  
268  
269  
270  
271  
Part No.  
Description  
564CT-TR 804CT-TR 1104CT-TR 1404CT-TR  
4314J271 REFRIGERATION CYCLE A'SSY  
4314J272 REFRIGERATION CYCLE A'SSY  
4314J367 REFRIGERATION CYCLE ASSY  
43172188 PAN DRAIN, ASS'Y  
43172189 PAN DRAIN, ASS'Y  
43172190 PAN DRAIN, ASS'Y  
43100356 PANEL, UNDER  
1
1
1
1
1
1
1
1
1
1
43100357 PANEL, UNDER  
43100358 PANEL, UNDER  
1
1
1
1
2
1
1
1
1
1
2
1
43102647 COVER, SIDE (RIGHT)  
43102648 COVER, SIDE (LEFT)  
43109407 GRILLE, INLET  
1
1
2
1
1
43109408 GRILLE, INLET  
2
43121741 MOTOR, FAN  
43121742 MOTOR, FAN  
1
43121743 MOTOR, FAN  
1
3
1
1
1
1
43120227 FAN, MULTI BLADE  
43166011 REMOTE CONTROLLER, SX-A4EE  
43166012 REMOTE CONTROLLER, SX-A5EE  
43166004 REMOTE CONTROLLER, SX-A11JE2  
43166006 REMOTE CONTROLLER, WH-H1JE2  
4314Q090 DISTRIBUTOR ASSY  
43147701 DISTRIBUTOR A'SSY  
43147702 DISTRIBUTOR A'SSY  
43122084 CASE, FAN, LOWER  
43122085 CASE, FAN, UPPER  
43180314 AIR FILTER  
2
1
1
1
1
1
4
1
1
1
1
4
1
1
1
1
1
1
4
4
1
2
1
2
1
1
1
4
4
1
2
1
2
1
1
2
2
2
3
3
43180315 AIR FILTER  
2
1
2
43108014 BASE, RECEIVER  
43179136 BAND, HOSE  
1
2
43125131 BEARING, SHAFT  
43125162 COUPLING  
1
1
43047685 NUT, FLARE, 1/4 IN  
43049776 SOCKET  
1
1
1
43149351 SOCKET  
1
1
43047688 NUT, FLARE, 1/2, IN  
43149352 NUT, FLARE, 5/8, IN  
43149353 SOCKET  
1
1
1
1
1
43149354 SOCKET\  
1
1
1
1
1
1
1
43149326 COVER, BACK BASE  
43125164 SHAFT  
43125165 SHAFT  
43125159 BEARING  
1
1
1
1
43109409 GRILLE A'SSY, HORIZONTAL  
43109410 GRILLE A'SSY, HORIZONTAL  
43109411 GRILLE A'SSY, HORIZONTAL  
43107260 SUPPORT, GRILLE HORIZONTAL  
43122086 GRILLE A'SSY, VERTICAL  
43179129 CAP DRAIN  
1
1
2
3
1
6
3
1
1
1
2
3
1
6
3
1
1
1
2
1
4
2
1
1
2
1
4
2
1
1
43107254 HINGE, GRILLE INLET  
43107255 HOOK, GRILLE INLET  
43170234 HOSE, DRAIN  
43047609 BONNET  
43047692 BONNET  
1
43194029 BONNET  
1
1
1
1
1
1
43149355 NUT, FLARE, 3/8, IN  
43049697 BONNET  
1
2
1
1
1
1
1
1
1
43019904 HOLDER, SENSOR (TS)  
43121746 DRIVER A'SSY HORIZONTAL LOUVER  
43160556 LEAD, LOUVER HORIZONTAL  
43108016 MARK TOSHIBA  
2
1
1
1
1
1
1
1
2
1
1
1
1
1
2
1
2
1
3
3
3
2
1
1
1
1
1
2
1
2
1
3
3
3
43162049 BUSHING 50DIA  
43162050 BUSHING 56DIA  
43197189 SCREW, FIX DRAIN PAN  
43107252 SHAFT, HOLIZONTAL LOUVER  
43139153 SPACER, BEARING  
431S8225 OWNER'S MANUAL  
43107285 HOOK, GRILLE INLET  
43197202 NUT, FLANGE  
1
2
2
2
1
2
2
2
43197203 SCREW, PAINT, M3  
– 117 –  
Electric parts  
403  
401  
406  
402  
405  
404  
407  
Model name RAV-SM  
Location  
Part No.  
Description  
564CT-E 804CT-E 1104CT-E 1404CT-E  
No.  
(TR)  
(TR)  
(TR)  
(TR)  
401  
402  
403  
404  
405  
406  
407  
43050425 SENSOR ASSY, SERVICE, TC  
43050426 SENSOR, SERVICE, TA  
43158193 REACTOR, CH-43-2Z-T  
43160565 TERMINAL BLOCK, 3P, 20A  
4316V461 PC BOARD ASSY, MCC-1402  
43155203 CAPACITOR KIT, SERVICE  
43160568 TERMINAL, 2P  
2
1
1
1
1
1
1
2
1
1
1
1
1
1
2
1
1
1
1
1
1
2
1
1
1
1
1
1
– 118 –  
WARNINGS ON REFRIGERANT LEAKAGE  
Check of Concentration Limit  
Important  
The room in which the air conditioner is to be  
installed requires a design that in the event of  
refrigerant gas leaking out, its concentration will  
not exceed a set limit.  
The refrigerant R410A which is used in the air  
conditioner is safe, without the toxicity or combustibility  
of ammonia, and is not restricted by laws to be imposed  
which protect the ozone layer.  
NOTE 2 :  
The standards for minimum room volume are as follows.  
(1) No partition (shaded portion)  
However, since it contains more than air, it poses the  
risk of suffocation if its concentration should rise  
excessively. Suffocation from leakage of R410A is  
almost non-existent.  
With the recent increase in the number of high  
concentration buildings, however, the installation of  
multi air conditioner systems is on the increase because  
of the need for effective use of floor space, individual  
control, energy conservation by curtailing heat and  
carrying power etc.  
(2) When there is an effective opening with the adjacent  
room for ventilation of leaking refrigerant gas  
(opening without a door, or an opening 0.15% or  
larger than the respective floor spaces at the top or  
bottom of the door).  
Outdoor unit  
Most importantly, the multi air conditioner system is able  
to replenish a large amount of refrigerant compared with  
conventional individual air conditioners.  
Refrigerant piping  
Indoor unit  
If a single unit of the multi conditioner system is to be  
installed in a small room, select a suitable model and  
installation procedure so that if the refrigerant  
accidentally leaks out, its concentration does not reach  
the limit (and in the event of an emergency, measures  
can be made before injury can occur).  
In a room where the concentration may exceed the limit,  
create an opening with adjacent rooms, or install  
mechanical ventilation combined with a gas leak  
detection device.  
(3) If an indoor unit is installed in each partitioned room  
and the refrigerant piping is interconnected, the  
smallest room of course becomes the object.  
But when a mechanical ventilation is installed  
interlocked with a gas leakage detector in the smallest  
room where the density limit is exceeded, the volume  
of the next smallest room becomes the object.  
The concentration is as given below.  
Refrigerant piping  
Total amount of refrigerant (kg)  
Min. volume of the indoor unit installed room (m³)  
Concentration limit (kg/m³)  
Outdoor unit  
Very  
small  
Indoor unit  
room  
The concentration limit of R410A which is used in multi  
air conditioners is 0.3kg/m³.  
Small  
room  
Medium  
room  
Large room  
NOTE 1 :  
Mechanical ventilation device - Gas leak detector  
If there are 2 or more refrigerating systems in a single  
refrigerating device, the amounts of refrigerant should  
be as charged in each independent device.  
NOTE 3 :  
The minimum indoor floor area compared with the  
amount of refrigerant is roughly as follows:  
(When the ceiling is 2.7m high)  
Outdoor unit  
e.g., charged  
e.g.,  
amount (10kg)  
charged amount (15kg)  
40  
Range below the  
35  
m²  
density limit  
of 0.3 kg/m³  
30  
25  
20  
15  
10  
5
(countermeasures  
not needed)  
Room A Room B Room C Room D Room E Room F  
Indoor unit  
Range above  
the density limit  
of 0.3 kg/m³  
For the amount of charge in this example:  
The possible amount of leaked refrigerant gas in rooms  
A, B and C is 10kg.  
The possible amount of leaked refrigerant gas in rooms  
D, E and F is 15kg.  
(countermeasures  
needed)  
0
10  
20  
30  
Total amount of refrigerant  
kg  
TOSHIBA CARRIER CORPORATION  
23-17, TAKANAWA 3 CHOME, MINATOKU, TOKYO, 108-8580, JAPAN  
Copyright © 1999 to 2010 TOSHIBA CARRIER CORPORATION, ALL Rights Reserved.  

Lexmark All In One Printer X560 User Manual
Panasonic Dp 6010 User Manual
Sanyo 09khs71 User Manual
Sanyo N 1200scl User Manual
Sharp Air Cleaner Fp A28u User Manual
Sharp Al 1340 User Manual
Sharp Ar M236 User Manual
Sterling Power Products Abrc User Manual
Toshiba Rav Sm1101at E User Manual
Vector Iveco Motos V08 Ent M12 User Manual