Siemens Sqk3300 User Manual

506  
4
SQL33.00  
SQL83.00  
SQK33.00  
.
.
.
.
.
.
.
.
.
.
.
SQK33.00  
SQL33.0...  
SQL83...  
Electric actuators for  
butterfly valves  
with 90° angle of rotation  
SQK33.00  
SQL33.0... Operating voltage AC 230 V  
SQL83.00 Operating voltage AC 24 V  
3-position control signal  
Operating voltage AC 230 V  
Auxiliary switch and potentiometer for additional functions  
Nominal angle of rotation 90°  
Reversible electric motor  
For mounting on butterfly valves and slipper valves with ASK… mounting kit  
With manual adjuster and position indicator  
Use  
For use in heating, ventilation and air conditioning systems to operate Siemens butterfly  
valves and three-port and four-port slipper valves (mixing valves), types K1i…,  
VKF41…, VB… and VC... (see "Equipment combinations") and valves from other  
manufacturers.  
.
.
The actuators can be fitted with additional auxiliary switches and potentiometers  
Siemens Building Technologies  
HVAC Products  
CM1N4506en  
07.06.2004  
Equipment combinations  
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
The table below shows which actuators may be used with which slipper valves and  
butterfly valves, and indicates the appropriate mounting kits in each case.  
Actuators  
PN class  
Data  
sheet  
SQK33.00  
SQL33.00  
SQL83.00  
SQL33.03 Mounting  
kits  
Valves  
Nominal size (DN)  
Three-port slipper valves  
VBF21...  
(Mixing)  
(40 ... 50)  
(65 ...150)  
(¾”...1½”)  
(¾”...1½”)  
PN6  
N4241  
N4241  
N4232  
N4233  
---  
40 / 50  
---  
40 / 50  
65 ...150  
¾”...1½”  
¾”...1½”  
¾”... 2"  
40 / 50  
65 ...150  
¾”...1½”  
¾”...1½”  
¾”... 2"  
ASK32  
PN6  
ASK31  
VBI31...  
VBG31...  
Other  
PN10  
PN10  
PN6...  
¾”...1½”  
¾”...1½”  
¾”...1½”  
ASK32  
ASK32  
ASK40 *)  
ASK41 *)  
makes  
Four-port valves  
(Mixing)  
VCI31...  
Other  
(¾”...1½”)  
PN10  
N4252  
---  
¾”...1½”  
¾”...1½”  
¾”...1½”  
¾”...  
¾”...1½”  
¾”... 2"  
ASK32  
PN6...  
ASK40 *)  
ASK41 *)  
makes  
Butterfly valves  
K1i...  
(¾”...1¼”)  
PN6  
N4111  
N4131  
¾”...1¼”  
40  
¾”...1¼”  
---  
ASK33  
ASK33  
VKF41...  
(40 ... 200)  
PN16  
40 ... 200  
40 ... 200  
*) Mounting kits ASK40 and ASK41 for non-Siemens actuators: refer to data sheet N42291  
Mechanical design  
The electric actuators require no maintenance. They have a reversible synchronous  
motor and reduction gears with self-lubricating sinter bearings. The housing base and  
the console are die-cast aluminium, and the cover is plastic.  
"AUTO" and "MANUAL" modes can be selected with a rotary switch on the housing  
base. When the switch is set to "MANUAL", the actuator and valve can be operated  
with a manual lever. For manual operation, the angle of rotation is mechanically limited  
by an end-stop.  
The actuators supplied have a 90° angle of rotation suitable for the Siemens valves.  
During automatic operation, rotation is limited by two built-in end-switches. For non-  
Siemens valves, the angle of rotation in the range 70° to 180° can be selected by  
repositioning the switching cams.  
The direction of operation of the actuator can be reversed (refer to "Commissioning").  
3/8  
Siemens Building Technologies  
HVAC Products  
Electric actuators for butterfly valves  
CM1N4506en  
07.06.2004  
Rotary "AUTO" / "MAN" switch  
Manual lever  
Console (e.g. ASK31 mounting kit)  
Terminal strip  
Dual end-switch (always factory fitted)  
Connector for reversal of direction of rotation  
(only with SQK33.00, SQL33.0…, SQL83.00)  
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Accessory ASC9.5  
Accessory ASC9.4  
1 auxiliary switch  
for SQK33.00,  
SQL33.0...  
SQL83.00  
1 dual auxiliary switch  
for SQL33.0...  
SQL83.00  
Accessory ASZ7.4  
1 auxiliary switch and  
1 1000-ohm potentiometer  
for SQL33.0...  
SQL83.00  
Engineering  
Butterfly valves: see data sheets N4100 … N4199.  
Three-port and four-port slipper valves: see data sheets N4200 … N4299.  
Admissible ambient temperatures, see "Technical data".  
.
Electrical installation  
The actuators must be electrically connected in accordance with local regulations and  
with the connection diagrams.  
Regulations and requirements to ensure the safety of people and property must  
be observed at all times.  
!
If additional functions are to be controlled by the actuator, the ASC9.. (auxiliary switch)  
or ASZ7.5 (auxiliary switch / potentiometer) must be fitted. The relevant switching  
point(s) and zero-ohm position must be noted in the plant documentation.  
4/8  
Siemens Building Technologies  
HVAC Products  
Electric actuators for butterfly valves  
CM1N4506en  
07.06.2004  
Mounting  
Mounting instructions are enclosed with the mounting kit.  
The valve, actuator and mounting kit are packed separately. The valve and actuator  
can be assembled easily on site. There is no need for special tools or calibration.  
Take care to install the valve the right way up. Refer to the mounting instructions for the  
valve concerned (butterfly or slipper valves).  
.
.
.
.
.
.
.
.
.
.
.
Orientation  
90°  
90°  
Commissioning  
When commissioning the complete motorised valve, consisting of actuator, mounting kit  
and (butterfly or slipper) valve, check the wiring and test the functions. This also  
applies to any additional components fitted (e.g. auxiliary switch or potentiometer).  
Siemens slipper valves up to DN50 can be commissioned without an actuator being  
fitted. In this case, the flow rate must be adjusted manually with the standard manual  
adjuster fitted to the valve.  
Note  
For automatic operation, the rotary switch must be set to "AUTO".  
Mode of operation  
Rotary switch for  
mode selection  
"AUTO" = Automatic operation  
"MAN" = Manual operation  
Reversing the  
The actuators are factory-set to rotate in a clockwise direction (as seen from the front).  
The direction of rotation can be reversed by repositioning a connector located under the  
cover (see "Mechanical design").  
direction of rotation  
The wiring for the OPEN and CLOSE control signal is not affected.  
As supplied  
Direction of rotation reversed  
5/8  
Siemens Building Technologies  
HVAC Products  
Electric actuators for butterfly valves  
CM1N4506en  
07.06.2004  
Setting the angle of  
rotation  
The angle of rotation is factory-set to 90°. However, the angle can be changed to  
between 70° and 180°. This may be necessary when using non-Siemens valves.  
Special notes on this subject will be found in the mounting instructions for the ASK40  
and ASK41 (mounting kits for non-Siemens valves).  
Maintenance  
.
The actuators require no maintenance.  
When servicing the valve and/or actuator: switch OFF the pump and power  
supply, close the main shut-off valve in the pipework, release pressure in the  
pipes and allow them to cool down completely.  
Warning !  
If necessary, disconnect electrical connections from terminals.  
Disposal  
The device may not be disposed of together with domestic waste. This applies in  
particular to the PCB.  
Legislation may demand special handling of certain components, or it may be sensible  
from an ecological point of view.  
Current local legislation must be observed.  
Warranty  
The technical data given for these applications is valid only in conjunction with the  
Siemens valves (butterfly and slipper valves) and third-party valves for use with the  
ASK40 / ASK41, as described under "Compatibility". The use of third-party valves  
other than those recommended by Siemens invalidates the warranty.  
Technical data  
.
.
.
.
.
.
.
.
.
.
Power supply  
Rated voltage  
SQK33.00, SQL33.00, SQL33.03  
SQL83.00  
AC 230 V ± 15 %  
AC 24 V ± 20 %  
50 / 60 Hz  
Rated frequency  
Control signal  
3-position  
Power consumption *)  
SQK33.00  
3 VA  
SQL33.00, SQL83.00  
SQL33.0...  
4 VA  
6.5 VA  
Operating data  
Run-time for rotation through 90°  
SQK33.00, SQL33.00  
SQL83.00  
at 50 Hz  
125 s  
125 s  
30 s  
at 60 Hz  
105 s  
105 s  
SQL33.03  
25 s  
Angle of rotation  
Factory setting  
90° ± 2°  
Adjustment range  
70° ...180°  
6/8  
Siemens Building Technologies  
HVAC Products  
Electric actuators for butterfly valves  
CM1N4506en  
07.06.2004  
.
.
.
.
.
Torque *)  
Nominal torque  
5 Nm  
Starting torque  
10 Nm  
SQK33.00  
SQL33.03  
10 Nm  
12 Nm  
SQL33.00, SQL83.00  
End switch  
12.5 Nm  
25 Nm  
Switching capacity  
Switching differential  
AC 250 V, 6 (2) A  
Approx. 1°  
Materials  
Housing base and console  
Cover  
Die-cast aluminium  
Plastic  
Dimensions / Weight  
Dimensions  
See “Dimensions”  
.
Cable glands  
20,5 (M20) (4x)  
Weight  
SQK33.00  
1.25 kg  
1.35 kg  
1.40 kg  
SQL33.00, SQL83.00  
SQL33.03, SQL35.00, SQL85.00  
Ambient conditions  
Max. admissible temperature of medium in  
assembled valve  
Operation  
> 120 °C  
To IEC 721-3-3  
Class 3K5  
– Environmental conditions  
– Temperature  
–15 ... +55 °C  
5 ... 95 % rh  
To IEC 721-2-3  
Class 3K2  
– Humidity  
Transport  
– Environmental conditions  
– Temperature  
– 30 ... +65 °C  
< 95 % rh  
– Humidity  
Storage  
To IEC 721-1-3  
Class 3K1  
– Environmental conditions  
– Temperature  
–15 ... +55 °C  
0 ... 95 % rh  
– Humidity  
Industry standards  
Accessories  
Meets the requirements for CE marking in  
EMC Directive  
89/336/EEC  
73/23/EEC  
Low Voltage Directive  
Housing protection standard  
IP44 to IEC529 / DIN40050  
ASC9.5  
Auxiliary switch  
.
.
.
.
.
.
.
.
ASC9.4  
Dual auxiliary switch  
AC 250 V,  
Switching capacity  
10 A resistive / 3 A inductive  
Approx. 1°  
Switching differential  
ASZ7.4  
Auxiliary switch with potentiometer  
AC 250 V,  
Switching capacity  
10 A resistive / 3 A inductive  
Approx. 1°  
Switching differential  
Change in resistance  
0 ... 90° corresponding to  
0 ...1000 ohm  
*) These values apply at nominal voltage, at an ambient temperature of 20°C and at the  
specified nominal running time  
7/8  
Siemens Building Technologies  
HVAC Products  
Electric actuators for butterfly valves  
CM1N4506en  
07.06.2004  
Connection diagrams  
.
.
SQK33.00  
SQL33.00, SQL33.03  
Cm1  
Cm2  
c1  
End switch  
SQL83.00  
End switch  
1 auxiliary switch ASC9.5 or  
1 dual auxiliary switch ASC9.4  
or  
c1, c2  
c1, 10001 installable module ASZ7.4  
(1 auxiliary switch and  
1 potentiometer)  
Dimensions  
SQK33.00  
All dimensions in mm  
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
.
Installation height H*  
for actuator with mounting kit  
ASK31  
ASK32  
ASK33  
162 mm  
132 mm  
162 mm  
SQL33.0... / SQL83.00  
Installation height H*  
for actuator with mounting kit  
ASK31  
ASK32  
ASK33  
188 mm  
158 mm  
188 mm  
Overall height of valve  
and actuator  
= Installation height of slipper or butterfly valve from the middle of the pipe  
+ Installation height H* of the actuator with mounting kit  
+ Minimum clearance from ceiling or wall for mounting, connection,  
operation, service etc.  
>100 mm  
∆ ∆ >200 mm  
2004 Siemens Building Technologies Ltd.  
Subject to technical alteration  
8/8  
Siemens Building Technologies  
HVAC Products  
Electric actuators for butterfly valves  
CM1N4506en  
07.06.2004  

Mikasa Automobile Parts Mtx 70 User Manual
Oce North America Op1050 User Manual
Panasonic Kx Fg2451 User Manual
Sanyo Eco G Spw Gu105xh User Manual
Sharp Ar M257 User Manual
Sharp Mx M1100 User Manual
Sharp Ux A255 User Manual
Subaru Robin Power Products Senseo Hd7832 User Manual
Toshiba Ras 10jkvp E User Manual
York Sunline 2000 48 User Manual