Sanyo Mini Eco I 85464359981002 User Manual

INSTALLATION INSTRUCTIONS  
– Mini ECO-i System Air Conditioner –  
X
A
U
D
T
for Refrigerant R410A  
I R410A Models  
Indoor Units  
Class  
7
9
12  
18  
24  
36  
48  
X
A
U
D
T
4-Way Air Discharge Semi-Concealed Type  
1-Way Air Discharge Semi-Concealed Type  
Concealed Duct Type  
XHX1252 XHX1852 XHX2452 XHX3652  
AHX0752  
UHX0752  
AHX0952 AHX1252  
UHX1252 UHX1852 UHX2452 UHX3652  
Concealed Duct  
High-Static Pressure Type  
DHX3652 DHX4852  
Ceiling-Mounted Type  
Wall-Mounted Type  
THX1252 THX1852  
THX2452  
K
KHX0752  
KHX0952 KHX1252 KHX1852 KHX2452  
Outdoor Units  
K
Class  
36  
60  
C
Mini ECO-i  
CHX03652 CHX06052  
* Refrigerant R410A is used in the outdoor units.  
Optional Controllers  
Timer Wired Remote Controller  
Wireless Remote Controller (For U, D Type)  
Wireless Remote Controller (For X Type)  
Wireless Remote Controller (For A, T Type)  
RC Wireless Remote Controller (For K Type)  
Simplified Remote Controller  
System Controller  
RCS-TM80BG  
RCS-BH80AAB.WL  
RCS-SH80AAB.WL  
RCS-TRP80AAB.WL  
RCS-SH1AAB  
RCS-KR1AGB  
SHA-KC64UG  
Intelligent Controller  
SHA-KT256BA  
SHA-KA128AAB  
ART-K45AGB  
Communication Adaptor  
Remote Sensor  
LonWorks Interface  
SHA-LN16UAB  
85464359981002 ©SANYO 2006  
SANYO Electric Co., Ltd.  
Gunma, Japan  
2. The standards for minimum room volume are as fol-  
lows.  
Check of Density Limit  
The room in which the air conditioner is to be installed  
requires a design that in the event of refrigerant gas  
leaking out, its density will not exceed a set limit.  
The refrigerant (R410A), which is used in the air conditioner,  
is safe, without the toxicity or combustibility of ammonia,  
and is not restricted by laws imposed to protect the ozone  
layer. However, since it contains more than air, it poses the  
risk of suffocation if its density should rise excessively.  
Suffocation from leakage of refrigerant is almost non-exis-  
tent. With the recent increase in the number of high density  
buildings, however, the installation of multi air conditioner  
systems is on the increase because of the need for effective  
use of floor space, individual control, energy conservation  
by curtailing heat and carrying power, etc.  
(1) No partition (shaded portion)  
(2) When there is an effective opening with the adjacent  
room for ventilation of leaking refrigerant gas (opening  
without a door, or an opening 0.15% or larger than the  
respective floor spaces at the top or bottom of the  
door).  
Outdoor unit  
Refrigerant tubing  
Most importantly, the multi air conditioner system is able to  
replenish a large amount of refrigerant compared to  
conventional individual air conditioners. If a single unit of  
the multi air conditioner system is to be installed in a small  
room, select a suitable model and installation procedure  
so that if the refrigerant accidentally leaks out, its density  
does not reach the limit (and in the event of an emergency,  
measures can be made before injury can occur).  
In a room where the density may exceed the limit, create  
an opening with adjacent rooms, or install mechanical  
ventilation combined with a gas leak detection device.  
The density is as given below.  
Indoor unit  
(3) If an indoor unit is installed in each partitioned room  
and the refrigerant tubing is interconnected, the  
smallest room of course becomes the object. But when  
mechanical ventilation is installed interlocked with a  
gas leakage detector in the smallest room where the  
density limit is exceeded, the volume of the next  
smallest room becomes the object.  
Refrigerant tubing  
Total amount of refrigerant (oz)  
Min. volume of the indoor unit installed room (ft.3)  
Outdoor unit  
3
<
Density limit (oz/ft. )  
Very  
small  
The density limit of refrigerant which is used in multi air condi-  
tioners is 0.3 oz/ft.3 (ISO 5149).  
Indoor unit  
room  
Small  
room  
Medium  
room  
Large room  
NOTE  
1. If there are 2 or more refrigerating systems in a single  
refrigerating device, the amount of refrigerant should be  
as charged in each independent device.  
Mechanical ventilation device – Gas leak detector  
3. The minimum indoor floor space compared with the  
amount of refrigerant is roughly as follows (when the  
ceiling is 8.8 ft. high):  
For the amount of charge in this example:  
Outdoor unit  
ft.3  
ft.2  
e.g., charged  
amount (353 oz)  
e.g., charged  
amount (529 oz)  
4000  
454  
Range below  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
not needed)  
3500  
3000  
2500  
2000  
1500  
1000  
500  
398  
341  
284  
227  
170  
114  
57  
Indoor unit  
Room A Room B Room C Room D Room E Room F  
Range above  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
needed)  
The possible amount of leaked refrigerant gas in rooms A, B  
and C is 353 oz.  
The possible amount of leaked refrigerant gas in rooms D, E  
and F is 529 oz.  
0
0
0
200 400 600 800 1000 1200  
oz  
Total amount of refrigerant  
3
Precautions for Installation Using New Refrigerant  
1. Care regarding tubing  
1-1. Process tubing  
G Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless  
Pipes and Tubes.”  
G Tubing size: Be sure to use the sizes indicated in the table below.  
G Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints  
(optional).  
G When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.  
Use sufficient care in handling the tubing. Seal the tubing ends with  
CAUTION  
caps or tape to prevent dirt, moisture, or other foreign substances  
from entering. These substances can result in system malfunction.  
Unit: in. (mm)  
Material  
O
Outer diameter  
Wall thickness  
1/4 (6.35)  
1/32 (0.8)  
3/8 (9.52)  
1/32 (0.8)  
1/2 (12.7)  
1/32 (0.8)  
5/8 (15.88)  
5/128 (1.0)  
3/4 (19.05)  
5/128 (1.0)  
Copper tube  
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A  
refrigerant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating  
machine oil, the prevention of water and other impurities becomes more important than ever.  
2. Be sure to recharge the refrigerant only in liquid form.  
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause  
defects of the unit.  
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining  
refrigerant and recharge the required total amount of new refrigerant after fixing the leak.  
3. Different tools required  
3-1. Tool specifications have been changed due to the characteristics of R410A.  
Some tools for R22- and R407C-type refrigerant systems cannot be used.  
Manifold gauge  
R407C tools  
compatible  
with R410A?  
New  
tool?  
Item  
Remarks  
Manifold gauge Yes  
No  
Types of refrigerant, refrigerating machine oil, and  
pressure gauge are different.  
Charge hose  
Yes  
No  
To resist higher pressure, material must be changed.  
Vacuum pump Yes  
Yes  
Use a conventional vacuum pump if it is equipped  
with a check valve. If it has no check valve,  
purchase and attach a vacuum pump adapter.  
Leak detector  
Flaring oil  
Yes  
Yes  
No  
No  
Leak detectors for CFC and HCFC that  
react to chlorine do not function because  
R410A contains no chlorine. Leak detector  
for HFC134a can be used for R410A.  
Vacuum pump  
Outlet  
Inlet  
For systems that use R22, apply mineral oil (Suniso oil)  
to the flare nuts on the tubing to prevent refrigerant  
leakage. For machines that use R407C or R410A, apply  
synthetic oil (ether oil) to the flare nuts.  
* Using tools for R22 and R407C and new tools for R410A together can cause defects.  
4
3-2. Use R410A exclusive cylinder only.  
Valve  
Single-outlet valve  
(with siphon tube)  
Liquid refrigerant should be recharged  
with the cylinder standing on end as  
shown.  
Liquid  
New refrigerant R410A cannot be used for  
earlier models  
1. Compressor specifications are different.  
If recharging a R22 or R407C compressor with  
R410A, durability will significantly decrease since  
some of the materials used for compressor parts are  
different.  
2. Existing tubing cannot be used (especially R22).  
Completely cleaning out residual refrigerating  
machine oil is impossible, even by flushing.  
R410A  
3. Refrigerating machine oil differs (R22).  
Since R22 refrigerating machine oil is mineral oil, it  
does not dissolve in R410A. Therefore, refrigerating  
machine oil discharged from the compressor can  
cause compressor damage.  
R22 refrigerating machine oil  
Mineral oil (Suniso oil)  
R407C refrigerating machine oil Synthetic fluid (ether oil)  
R410A refrigerating machine oil Synthetic fluid (ether oil)  
5
CONTENTS  
Page  
Page  
3-11. Checking the Drainage  
3-12. Electrical Power Wiring  
3-13. How to Install the Ceiling Panel  
IMPORTANT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Please Read Before Starting  
Check of Density Limit  
I Concealed Duct Type (U Type)  
Precautions for Installation Using New Refrigerant  
3-14. Required Minimum Space for Installation and  
Service  
3-15. Suspending the Indoor Unit  
3-16. Installing the Drain Piping  
3-17. Checking the Drainage  
3-18. Increasing the Fan Speed  
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
1-1. Tools Required for Installation (not supplied)  
1-2. Accessories Supplied  
1-3. Type of Copper Tube and Insulation Material  
1-4. Additional Materials Required for Installation  
1-5. Tubing Size  
1-6. Straight Equivalent Length of Joints  
1-7. Additional Refrigerant Charge  
1-8. System Limitations  
1-9. Tubing Length  
1-10. Check of Limit Density  
1-11. Installing Distribution Joint  
I Concealed Duct High-Static Pressure Type  
(D Type)  
3-19. Required Minimum Space for Installation and  
Service  
3-20. Suspending the Indoor Unit  
3-21. Installing the Drain Piping  
3-22. Caution for Ducting Work  
3-23. Indoor Fan Performance  
1-12. Optional Distribution Joint Kit  
1-13. Example of Tubing Size Selection and  
Refrigerant Charge Amount  
I Ceiling-Mounted Type (T Type)  
3-24. Required Minimum Space for Installation and  
Service  
2. SELECTING THE INSTALLATION SITE . . . . . 17  
2-1. Indoor Unit  
3-25. Suspending the Indoor Unit  
3-26. Duct for Fresh Air  
2-2. Outdoor Unit  
2-3. Air-Discharge Chamber for Top Discharge  
2-4. Installing the Unit in Heavy Snow Areas  
2-5. Precautions for Installation in Heavy Snow  
Areas  
2-6. Dimensions of Air-Discharge Chamber  
2-7. Dimensions of Outdoor Unit with  
Air-Discharge Chamber (field supply)  
2-8. Dimensions of Snow Ducting  
2-9. Dimensions of Outdoor Unit with Snow-Proof  
Ducting (field supply)  
3-27. Shaping the Tubing  
3-28. Installing the Drain Piping  
I Wall-Mounted Type (K Type)  
3-29. Removing the Rear Panel from the Unit  
3-30. Selecting and Making a Hole  
3-31. Installing the Rear Panel onto the Wall  
3-32. Removing the Grille to Install the Indoor Unit  
3-33. Preparing the Tubing  
3-34. Shaping the Tubing  
3-35. Installing the Drain Hose  
3-36. When Using Wireless Remote Controller  
Instead of Wired Remote Controller  
3. HOW TO INSTALL THE INDOOR UNIT . . . . . 25  
I 4-Way Air Discharge Semi-Concealed Type  
(X Type)  
4. HOW TO INSTALL THE OUTDOOR UNIT . . . 56  
4-1. Installing the Outdoor Unit  
3-1. Preparation for Suspending  
3-2. Suspending the Indoor Unit  
3-3. Placing the Unit Inside the Ceiling  
3-4. Installing the Drain Piping  
3-5. Checking the Drainage  
3-6. How to Install the Ceiling Panel  
3-7. Special Remarks  
4-2. Drainage Work  
4-3. Routing the Tubing and Wiring  
5. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . 57  
5-1. General Precautions on Wiring  
5-2. Recommended Wire Length and Wire  
Diameter for Power Supply System  
I 1-Way Air Discharge Semi-Concealed Type  
(A Type)  
5-3. Wiring System Diagram  
3-8. Suspending the Indoor Unit  
3-9. Placing the Unit Inside the Ceiling  
3-10. Installing the Drain Piping  
6
Page  
6. HOW TO PROCESS TUBING . . . . . . . . . . . . 61  
6-1. Connecting the Refrigerant Tubing  
6-2. Connecting Tubing Between Indoor and  
Outdoor Units  
6-3. Insulating the Refrigerant Tubing  
6-4. Taping the Tubes  
6-5. Finishing the Installation  
7. AIR PURGING . . . . . . . . . . . . . . . . . . . . . . . . . 65  
I Air Purging with a Vacuum Pump (for Test Run)  
Preparation  
8. TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68  
8-1. Preparing for Test Run  
8-2. Test Run Procedure  
8-3. Outdoor Unit PCB Setting  
8-4. Auto Address Setting  
8-5. Caution for Pump Down  
8-6. Meaning of Alarm Messages  
9. APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . 81  
9-1. 4-Way Air Discharge Semi-Concealed Type  
(X Type)  
9-2. 1-Way Air Discharge Semi-Concealed Type  
(A Type)  
9-3. Concealed Duct (High-Static Pressure) Type  
(U, D Type)  
9-4. Ceiling-Mounted Type (T Type)  
9-5. Wall-Mounted Type (K Type)  
7
1-3. Type of Copper Tube and Insulation Material  
1. GENERAL  
If you wish to purchase these materials separately from  
a local source, you will need:  
This booklet briefly outlines where and how to install  
the air conditioning system. Please read over the entire  
set of instructions for the outdoor unit and make sure all  
accessory parts listed are with the system before  
beginning.  
1. Deoxidized annealed copper tube for refrigerant tub-  
ing.  
2. Foamed polyethylene insulation for copper tubes as  
required to precise length of tubing. Wall thickness of  
the insulation should be not less than 5/16 in.  
1-1. Tools Required for Installation (not supplied)  
1. Standard screwdriver  
2. Phillips head screwdriver  
3. Knife or wire stripper  
4. Tape measure  
3. Use insulated copper wire for field wiring. Wire size  
varies with the total length of wiring.  
Refer to 5. ELECTRICAL WIRING for details.  
5. Carpenter’s level  
6. Sabre saw or key hole saw  
7. Hacksaw  
8. Core bits  
9. Hammer  
Check local electrical codes  
CAUTION  
and regulations before  
obtaining wire. Also, check  
any specified instructions or  
limitations.  
10. Drill  
11. Tube cutter  
12. Tube flaring tool  
13. Torque wrench  
1-4. Additional Materials Required for Installation  
1. Refrigeration (armored) tape  
14. Adjustable wrench  
15. Reamer (for deburring)  
2. Insulated staples or clamps for connecting wire (See  
your local codes.)  
1-2. Accessories Supplied  
3. Putty  
See Tables 1-1 – 1-7.  
4. Refrigeration tubing lubricant  
5. Clamps or saddles to secure refrigerant tubing  
6. Scale for weighing  
Table 1-1 (Outdoor Unit)  
Q’ty  
Part name  
Figure  
03652  
Model  
(4 hp)  
06052  
Model  
(6 hp)  
Tube Discharge  
Assy  
0
1
Instruction manual  
paper  
1
1
hp = horsepower  
8
Table 1-2 (4-Way Air Discharge Semi-Concealed)  
Part Name  
Figure  
Q’ty  
Remarks  
Full-scale installation diagram  
1
Printed on container box  
For securing drain hose  
For securing drain hose  
For drain joint  
Drain hose  
1
1
1
1
1
2
1
1
4
8
1
Hose band  
Drain insulator  
For liquid tube  
Flare insulator  
For gas tube  
White  
Insulating tape  
Packing  
For gas tube joint  
For drain joint  
(heat-resisting)  
Wiring cover  
Screw  
For covering erectrical wiring  
For full-scale installation diagram  
For suspending indoor unit from ceiling  
For fixing the wiring cover  
Washer  
Screw  
Table 1-3 (1-Way Air Discharge Semi-Concealed)  
Part Name  
Figure  
Q’ty  
Remarks  
Full-scale installation diagram  
1
Printed on container box  
Drain hose  
1
1
1
1
1
2
1
8
4
1
For securing drain hose  
For securing drain hose  
For drain joint  
Hose band  
Drain insulator  
For liquid tube  
Flare insulator  
For gas tube  
White  
Insulating tape  
Packing  
For gas tube joint  
(heat-resisting)  
For drain joint  
Washer  
For suspending indoor unit from ceiling  
For full-scale installation diagram  
For electrical junction box  
Screw  
Bushing  
Table 1-4 (Concealed Duct)  
Part Name  
Figure  
Q’ty  
Remarks  
Drain hose  
1
For securing drain hose  
Hose band  
1
1
1
1
2
1
8
1
8
For securing drain hose  
For drain joint  
Packing  
Drain insulator  
Flare insulator  
Insulating tape  
Flare insulator  
Washer  
For drain joint  
For liquid tube  
White  
For gas and liquid tubes flare nuts  
For gas tube  
(heat-resisting)  
For suspending indoor unit from ceiling  
For sealing recessed portion of power supply  
For flare and drain insulators  
Sealing putty  
Vinyl clamp  
G Use 3/8" for suspending bolts.  
G Field supply for suspending bolts and nuts.  
9
Table 1-5 (Concealed Duct High-Static Pressure)  
Part Name  
Figure  
Q’ty  
Remarks  
Washer  
8
For suspending indoor unit from ceiling  
Nut  
8
1
1
1
For suspending indoor unit from ceiling  
For gas tube  
Flare insulator  
For liquid tube  
Drain socket  
For drain pipe connection  
Table 1-6 (Ceiling-Mounted)  
Part Name  
Figure  
Q’ty  
Remarks  
Full-scale installation diagram  
1
Printed on container box  
Washer  
4
2
2
2
8
1
2
1
1
For temporarily suspending indoor unit from ceiling  
T1/8"  
Flare insulator  
For gas and liquid tube joints  
T3/16"  
White  
Insulating tape  
Vinyl clamp  
Drain hose  
For gas and liquid tubes flare nuts  
For flare and drain insulators  
For main unit and PVC pipe joints  
For drain hose connection  
For drain hose joint  
(heat-resisting)  
L5-1/2"  
Hose band  
Drain insulator  
Gum eyelet  
For power supply inlet  
Table 1-7 (Wall-Mounted)  
Part Name  
Figure  
Q’ty  
Remarks  
5/32" × 1"  
Tapping screw  
10  
For fixing the rear panel  
Plastic cover  
1
1
For improved tubing appearance  
Insulator  
For insulating flare nut (2452 type only)  
1-5. Tubing Size  
Table 1-8 Main Tubing Size (LA)  
BTU/h (kW)  
System horsepower  
Gas tubing  
38,200 (11.2)  
4
52,900 (15.5)  
6
ø5/8" (ø15.88)  
ø3/4" (ø19.05)  
Liquid tubing  
ø3/8" (ø9.52)  
Unit: in. (mm)  
Table 1-9 Main Tubing Size After Distribution (LB, LC...)  
Below BTU/h 24,200 (2.5 hp) 38,200 (4 hp) 47,800 (5 hp) 52,900 (6 hp)  
Total capacity  
after distribution  
Over BTU/h  
Gas tubing  
Liquid tubing  
24,200 (2.5 hp)  
ø5/8" (ø15.88)  
ø3/8" (ø9.52)  
ø1/2" (ø12.7)  
ø3/8" (ø9.52)  
ø3/4" (ø19.05)  
Tubing size  
Unit: in. (mm)  
hp = horsepower  
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main  
tubing size for the total capacity of the outdoor units.  
Table 1-10 Indoor Unit Tubing Connection (  
,
2...  
)
n–1  
1
Indoor unit type  
Gas tubing  
7
9
12  
18  
24  
36  
48  
ø1/2" (ø12.7)  
ø5/8" (ø15.88)  
Liquid tubing  
ø1/4" (ø6.35)  
ø3/8" (ø9.52)  
Unit: in. (mm)  
10  
1-6. Straight Equivalent Length of Joints  
Design the tubing system by referring to the following table for the straight equivalent length of joints.  
Table 1-11 Straight Equivalent Length of Joints  
Unit: ft.  
Gas tubing size (in. (mm))  
90° elbow  
1/2" (12.7) 5/8" (15.88) 3/4" (19.05)  
1
1.1  
0.9  
3.4  
9.2  
1.4  
1
0.8  
3
45° elbow  
4.1  
10.5  
U-shape tube bend (R2-3/8" – 4" (60 – 100))  
Trap bend  
7.5  
Y-branch distribution joint  
Ball valve for service  
Equivalent length conversion not needed.  
Equivalent length conversion not needed.  
Table 1-12 Required Copper Tubing Dimensions  
Material  
Unit: in. (mm)  
O
Outer diameter  
Wall thickness  
1/4 (6.35)  
1/32 (0.8)  
3/8 (9.52)  
1/32 (0.8)  
1/2 (12.7)  
1/32 (0.8)  
5/8 (15.88)  
5/128 (1.0)  
3/4 (19.05)  
Copper tube  
over 5/128 (1.0)  
1-7. Additional Refrigerant Charge  
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.  
Table 1-13 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size  
Liquid tubing size  
(in. (mm))  
Amount of refrigerant  
charge (oz/ft.)  
Required amount of charge = (Amount of refrigerant  
charge per meter of each size of liquid tube × its tube  
length) + (...) + (...)  
ø1/4" (ø6.35)  
ø3/8" (ø9.52)  
0.279  
0.602  
*Always charge accurately using a scale for weighing.  
Table 1-14 Refrigerant Charge Amount at Shipment (for outdoor unit)  
Heat pump unit  
(Single-phase)  
(oz)  
CHX03652  
CHX06052  
123  
123  
1-8. System Limitations  
Table 1-15 System Limitations  
CHX03652 CHX06052  
Outdoor units (Type)  
6
9
Number of max. connectable indoor units  
Max. allowable indoor/outdoor capacity ratio  
50 – 130%  
11  
1-9. Tubing Length  
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown  
in the figure below.  
L1  
L2  
LA  
LB  
LC  
LD  
n
Main tube of unit  
H1  
1st branch  
Unit distribution tube  
2
3
1
n-1  
L3  
H2  
Note: Do not use commercially available T-joints for the liquid tubing.  
R410A distribution joint  
APR-P160BA (for indoor unit)  
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor  
unit connections and tubing branches.  
Table 1-16 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights  
Items  
Marks  
Contents  
Length (ft.)  
>
Actual length  
492  
L1  
Max. tubing length  
>
574  
Equivalent length  
Difference between max. length and min.  
length from the No.1 distribution joint  
Allowable tubing  
length  
>
131  
L (L2 – L3)  
>
98  
,
2...  
Max. length of each distribution tube  
1
n
Total max. tubing length including length of  
>
656  
+ +...  
2
n1+L1  
1
each distribution tube (only narrow tubing)  
>
164  
When outdoor unit is installed higher than indoor unit  
H1  
H2  
Allowable elevation  
difference  
>
When outdoor unit is installed lower than indoor unit  
131  
>
49  
Max. difference between indoor units  
L = Length, H = Height  
12  
Always check the gas density  
limit for the room in which the  
unit is installed.  
Minimum indoor volume & floor area as against the  
amount of refrigerant is roughly as given in the following  
table.  
WARNING  
ft.3  
10000  
ft.2  
1136  
1079  
1022  
966  
909  
852  
795  
738  
682  
625  
568  
511  
454  
398  
341  
284  
227  
170  
114  
57  
1-10. Check of Limit Density  
9500  
9000  
8500  
8000  
7500  
7000  
6500  
6000  
5500  
5000  
4500  
4000  
3500  
3000  
2500  
2000  
1500  
1000  
500  
When installing an air conditioner in a room, it is neces-  
sary to ensure that even if the refrigerant gas accidentally  
leaks out, its density does not exceed the limit level for  
that room.  
Range below  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
not needed)  
If the density could exceed the limit level, it is necessary to  
provide an opening between the unit and the adjacent  
room, or to install mechanical ventilation which is inter-  
locked with the leak detector.  
Range above  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
needed)  
(Total refrigerant charged amount: oz)  
(Min. indoor volume where the indoor unit is installed: ft.3)  
3
<
Limit density 0.3 (oz/ft. )  
0
0
0
500 1000 1500 2000 2500 3000  
oz  
The limit density of refrigerant which is used in this unit is  
0.3 oz/ft. (ISO 5149).  
Total amount of refrigerant  
3
The shipped outdoor unit comes charged with the amount  
of refrigerant fixed for each type, so add it to the amount  
that is charged in the field. (For the refrigerant charge  
amount at shipment, refer to the unit’s nameplate.)  
Tube branching methods (horizontal use)  
B
Pay special attention to any  
CAUTION  
Horizontal  
line  
A
location, such as a basement,  
etc., where leaking refrigerant  
can accumulate, since refrig-  
erant gas is heavier than air.  
A
B
View as seen  
from arrow  
Arrow view  
1-11. Installing Distribution Joint  
Types of vertical trap specifications  
(When using ball valve)  
Main tubing  
(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT”  
enclosed with the optional distribution joint kit  
(APR-P160BA).  
(2) In order to prevent accumulation of refrigerant oil in  
stopped units, if the main tubing is horizontal then each  
branch tubing length should be at an angle that is  
greater than horizontal. If the main tubing is vertical,  
provide a raised starting portion for each branch.  
Indoor unit (more than 2 units)  
(If only 1 unit is connected,  
a ball valve is also needed on this side.)  
Ball valve  
(BV: purchased  
separately)  
Indoor unit (1)  
(When not using ball valve)  
(3) If there are height differences between indoor units or if  
branch tubing that follows a distribution joint is connect-  
ed to only 1 unit, a trap or ball valve must be added to  
that distribution joint. (When adding the ball valve,  
locate it within 1.3 ft. of the distribution joint.)  
(Consult with SANYO separately concerning the ball  
valve.)  
Main tubing  
Horizontal  
Indoor unit  
(Each unit is connected to  
tubing that is either level  
or is directed downward.)  
Branch tubing is  
directed upward.  
More than  
8 in.  
Indoor unit is directed downward  
If a trap or ball valve is not added, do not operate  
the system before repairs to a malfunctioning unit  
are completed. (The refrigerant oil sent through the  
tubing to the malfunctioning unit will accumulate  
and may damage the compressor.)  
13  
1-12. Optional Distribution Joint Kit  
See the installation instructions packaged with the distribution joint kit for the installation procedure.  
Table 1-17  
Model name  
Cooling capacity after distribution  
Remarks  
APR-P160BA  
76,400 BTU/h (22.4 kW) or less  
For indoor unit  
APR-P160BA  
Use: For indoor unit (Capacity after distribution joint is 76,400 BTU/h (22.4 kW) or less.)  
Example  
Gas tube  
4-21/64  
Liquid tube  
4-21/64  
3-13/16  
3-13/16  
B
B
C
DE  
C
D
B
A
A
C
B
Distribution  
Distribution  
Joint  
Joint  
D
C
E
Unit: in.  
Insulation  
Insulation  
Table 1-18 Size of connection point on each part (Shown are inside diameters of tubing)  
Size  
Part A  
Part B  
Part C  
Part D  
Part E  
ø3/4"  
(ø19.05) (ø15.88)  
ø5/8"  
ø1/2"  
(ø12.7)  
ø3/8"  
(ø9.52)  
ø1/4"  
(ø6.35)  
in. (mm)  
14  
1-13. Example of Tubing Size Selection and Refrigerant Charge Amount  
Additional refrigerant charging  
Based on the values in Tables 1-2, 1-3, 1-4 and 1-7, use the liquid tubing size and length, and calculate the amount  
of additional refrigerant charge using the formula below.  
Required additional  
refrigerant charge (oz)  
= 0.602 × (a) + 0.279 × (b)  
(a): Liquid tubing  
Total length of ø3/8" (ft.)  
(b): Liquid tubing  
Total length of ø1/4" (ft.)  
G Charging procedure  
Be sure to charge with R410A refrigerant in liquid form.  
1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be  
in the “fully closed” position.  
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging  
with refrigerant from the gas tubing side. (This is performed at the time of the test run. For this, all valves  
must be in the “fully open” position.)  
Charge with R410A refrigerant in liquid form.  
With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent  
liquid refrigerant from backing up.  
G After charging is completed, turn all valves to the “fully open” position.  
G Replace the tubing covers as they were before.  
1
4
Tightening torque: 590 – 710 lbs·in.  
Tightening torque for valve stem cap: 160 – 180 lbs·in.  
3
Tightening torque: 300 – 360 lbs·in.  
2
Tightening torque for valve stem cap: 240 – 280 lbs·in.  
1. R410A additional charging absolutely must be done through liquid charging.  
2. The R410A refrigerant cylinder has a gray base color, and the top part is pink.  
CAUTION  
3. The R410A refrigerant cylinder includes a siphon tube. Check that the siphon  
tube is present. (This is indicated on the label at the top of the cylinder.)  
4. Due to differences in the refrigerant, pressure, and refrigerant oil involved in  
installation, it is not possible in some cases to use the same tools for R22 and  
for R410A.  
15  
Example:  
L1  
L2  
LA  
LB  
LC  
LN  
n
Main tube of unit  
1st branch  
Unit distribution tube  
model 1852  
2
3
1
n–1  
model 0752 model 0952 model 1252 model 1852  
G Example of each tubing length  
Main tubing  
LA = 131 ft.  
LB = 16 ft.  
LC = 16 ft.  
LD = 49 ft.  
Distribution joint tubing  
Indoor side  
1 = 16 ft.  
2 = 16 ft.  
3 = 7 ft.  
4 = 20 ft.  
5 = 16 ft.  
G Obtain charge amount for each tubing size  
Note that the charge amounts per 3.3 ft. are different for each liquid tubing size.  
ø3/8" (ø9.52) LA + LB + LC + LD  
ø1/4" (ø6.35) 1 + 2 + 3 + 4 + 5 : 75 ft. × 0.279 oz/ft.  
: 212 ft. × 0.602 oz/ft. = 127 oz  
20 oz  
=
Total 147 oz  
Additional refrigerant charge amount is 147 oz.  
Be sure to check the limit  
density for the room in which  
the indoor unit is installed.  
CAUTION  
Checking of limit density  
Density limit is determined on the basis of the size of a  
room using an indoor unit of minimum capacity. For  
instance, when an indoor unit is used in a room (floor area  
80 ft2 × ceiling height 8.8 ft. = room volume 704 ft.3), the  
graph at right shows that the minimum room volume  
should be 497 ft.3 (floor area 56 ft.2) for refrigerant of 147  
oz. Accordingly, openings such as louvers are required for  
this room.  
ft.3  
4000  
ft.2  
454  
Range below  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
not needed)  
3500  
3000  
2500  
2000  
1500  
1000  
500  
398  
341  
284  
227  
170  
114  
57  
Range above  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
needed)  
<Determination by calculation>  
Overall refrigerant charge amount for the air conditioner: oz  
(Minimum room volume for indoor unit: ft.3)  
147 (oz) + 123 (oz)  
0
0
0
200 400 600 800 1000 1200  
oz  
Total amount of refrigerant  
=
= 0.38 (oz/ft.3) > 0.3 (oz/ft.3)  
704 (ft.3)  
Therefore, openings such as louvers are required for this  
room.  
16  
2. SELECTING THE INSTALLATION SITE  
Ceiling-Mounted Type  
Ceiling  
2-1. Indoor Unit  
AVOID:  
Wall  
G areas where leakage of flammable gas may be  
expected.  
min. 10 in.  
min. 10 in.  
G places where large amounts of oil mist exist.  
Front view  
G direct sunlight.  
NOTE  
G locations near heat sources which may affect the  
The rear of the indoor unit can be installed flush  
against the wall.  
performance of the unit.  
Air  
discharge  
G locations where external air may enter the room  
directly. This may cause “sweating” on the air dis-  
charge ports, causing them to spray or drip.  
Air intake  
min. 2 ft.  
G locations where the remote controller will be splashed  
with water or affected by dampness or humidity.  
G installing the remote controller behind curtains or  
Side view  
Max. 10 in.  
Obstacle  
furniture.  
G locations where high-frequency emissions are  
Fig. 2-1  
generated.  
ConcealedDuct(High-StaticPressure)Type  
4-Way Air Discharge Semi-Concealed Type  
DO:  
G select an appropriate position from which every  
corner of the room can be uniformly cooled.  
G select a location where the ceiling is strong enough  
to support the weight of the unit.  
G select a location where tubing and drain pipe have  
the shortest run to the outdoor unit.  
G allow room for operation and maintenance as well as  
unrestricted air flow around the unit.  
Fig. 2-2  
G install the unit within the maximum elevation  
difference above or below the outdoor unit and within  
a total tubing length (L) from the outdoor unit as  
detailed in Table 1-16.  
1-Way Air Discharge Semi-Concealed Type  
Ceiling  
Air  
G allow room for mounting the remote controller about  
3 ft. off the floor, in an area that is not in direct  
sunlight nor in the flow of cool air from the indoor  
unit.  
discharge  
Air  
intake  
min. 2 in.  
Wall  
Wall  
min. 2 in.  
Obstacle  
Side view  
Fig. 2-3  
NOTE  
Wall-Mounted Type  
Air delivery will be degraded if the distance from the  
floor to the ceiling is greater than 10 ft.  
min. 6 in.  
min.  
6 in.  
min.  
6 in.  
Front View  
Fig. 2-4  
17  
2-2. Outdoor Unit  
Exhaust fan  
AVOID:  
Hot air  
G heat sources, exhaust fans, etc. (Fig. 2-5)  
G damp, humid or uneven locations  
Heat source  
Out-  
door  
unit  
DO:  
G choose a place as cool as possible.  
G choose a place that is well ventilated and outside  
air temperature does not exceed maximum 113°F  
constantly.  
Fig. 2-5  
G allow enough room around the unit for air intake/  
exhaust and possible maintenance. (Fig. 2-6)  
G use lug bolts or equal to bolt down unit, reducing  
vibration and noise.  
Installation space  
Distance between obstructions and the unit air inlet  
and outlet must be as shown below.  
(Obstruction above unit)  
Air direction chamber  
(field supply)  
*3  
Inlet side C  
B
More than 25/64"  
*2  
More than 25/64"  
*4  
A
Outlet side  
More than  
3.3 ft.  
Inlet side  
More than 8 in.  
*1  
(Obstruction on  
inlet side)  
*1  
Fig. 2-6  
(Ground)  
Fig. 2-7  
G Concerning inlet-side distance “C” (Fig. 2-6)  
CAUTION  
The minimum for distance “C” is 6 in. if there are no obstructions on the outlet side  
(wall *1 side) and *2 or *4 is not present. In all other cases, the minimum for distance  
“C” is 8 in.  
G If the unit is installed with the outlet side facing wall *1, then there must be no obstruc-  
tions on 2 of the remaining 3 sides: *2, *3, *4.  
G If wall *1 is on the outlet side (Fig. 2-6), or if obstructions are present on all 3 sides *2,  
*3, and *4 (Fig. 2-6), then the minimum distance for “A” and “B” is 6.6 ft. (Fig. 2-8).  
Even if there is no wall on the outlet side, a minimum of 3.3 ft. is required.  
In case of multiple installations  
G provide a solid base (concrete block, 4 × 16 in.  
beams or equal), a minimum of 6 in. above ground  
level to reduce humidity and protect the unit against  
possible water damage and decreased service life.  
(Fig. 2-8)  
Anchor bolts  
(4 pieces)  
G use lug bolts or equal to bolt down unit, reducing  
vibration and noise.  
Fig. 2-8  
18  
2-3. Air Discharge Chamber for Top Discharge  
Be sure to install an air discharge chamber (field sup-  
ply) in the field when:  
Air discharge  
G it is difficult to keep a space of min. 20 in. between  
the air discharge outlet and an obstacle.  
G the air discharge outlet is facing a sidewalk and  
discharged hot air may annoy passers-by.  
Refer to Fig. 2-10.  
2-4. Installing the Unit in Heavy Snow Areas  
In locations with strong wind, snow-proof ducting  
(field supply) should be fitted and direct exposure to  
the wind should be avoided as much as possible.  
Fig. 2-10  
I Countermeasures against snow and wind  
In regions with snow and strong wind, the following  
problems may occur when the outdoor unit is not pro-  
vided with a platform and snow-proof ducting:  
In regions with significant snowfall, the outdoor unit should  
be provided with a platform and snow-proof ducting.  
a) The outdoor fan may not run and damage to the  
unit may occur.  
b) There may be no air flow.  
c) The tubing may freeze and burst.  
d) The condenser pressure may drop because of  
strong wind, and the indoor unit may freeze.  
2-5. Precautions for Installation in Heavy Snow  
Areas  
(1) The platform should be higher than the max. snow  
depth. (Fig. 2-11)  
Without snow-  
proof ducting  
(Low platform)  
With snow-  
proof ducting  
(High platform)  
(2) The 2 anchoring feet of the outdoor unit should be  
used for the platform, and the platform should be  
installed beneath the air intake side of outdoor  
unit.  
Fig. 2-11  
(3) The platform foundation must be firm and the unit  
must be secured with anchor bolts.  
Outdoor  
Unit  
(4) In case of installation on a roof subject to strong  
wind, countermeasures must be taken to prevent  
the unit from being blown over.  
Duct  
Air  
Intake  
Fig. 2-12  
19  
2-6. Dimensions of Air-Discharge Chamber  
Reference diagram for air-discharge chamber (field supply)  
CHX03652/06052  
1
Unit front, air discharge chamber  
2
Unit left side, air discharge chamber  
2
3
4
Unit light side, air discharge chamber  
Reinforcement brackets, 4 locations  
9-7/16  
1-1/8  
3
1-1/8  
9-7/16  
4
1
Rectangular  
hole  
Rectangular  
hole  
Rectangular  
hole  
Rectangular  
hole  
22-13/32  
1
21-13/32  
1
Unit: in.  
2-7. Dimensions of Outdoor Unit with Air-Discharge Chamber (field supply)  
CHX03652/06052  
6-11/16  
25-31/32  
4-5/16  
Wind direction  
1/2  
1/2  
1/2  
2-11/36  
21-13/32  
37  
11-13/16  
Wind direction  
Wind  
direction  
Wind  
direction  
Wind direction  
Wind  
direction  
Wind  
direction  
Unit: in.  
20  
Reference for air-discharge chamber (field supply)  
Required space around outdoor unit  
CHX03652/06052  
If an air discharge chamber is used, the space shown below must be secured around the outdoor unit.  
If the unit is used without the required space, a protective device may activate, preventing the unit from operating.  
(1) Single-unit installation  
Unit: in.  
The top and both sides must remain open.  
If there are obstacles to the front and rear of the outdoor unit,  
the obstacle at either the front or rear must be no taller than the  
CAUTION  
height of the outdoor unit.  
(2) Multiple-unit installation  
Installation in lateral rows  
G
More than 11-13/16  
More than 11-13/16  
Unit: in.  
More than 7-7/8  
The front and top must remain open.  
The obstacles must be no taller than the height of the outdoor unit.  
CAUTION  
Installation in front-rear rows  
G
Installation with intakes facing  
Installation with intakes facing outlets  
intakes or outlets facing outlets  
More than 15-3/4  
More than 78-3/4  
More than 59-1/16  
Unit: in.  
The front and both sides must remain open.  
CAUTION  
21  
2-8. Dimensions of Snow Ducting  
Reference diagram for snow-proof ducting (field supply)  
CHX03652/06052  
Fastened by screws at 13 locations  
30-3/32  
1
2
3
4
Unit top, snow-proof vent  
Unit left side  
Unit right side  
4
1
Unit reverse side  
Unit: in.  
25-13/32  
17-15/32  
3
11-7/8  
2
3-3/4  
19-11/16  
3-31/32  
Fastened by screws at  
3 locations (also on reverse side)  
5/8  
1-3/16  
1-5/8  
28-3/4  
Fastened by screw at  
1 location (also on reverse side)  
15-9/32  
30-5/8  
2-9. Dimensions of Outdoor Unit with Snow-Proof Ducting (field supply)  
CHX03652/06052  
30-3/32  
7-1/16  
Wind direction  
Wind direction  
Unit: in.  
Wind direction  
Wind direction  
37  
24-7/8  
11-29/32  
Wind direction  
Wind direction  
22  
Reference diagram for snow-proof ducting – 1  
Space requirements for setting – (1)  
CHX03652/06052  
[Obstacle to the front of unit]  
[Obstacle to the rear of unit]  
G
G
Top is open:  
Top is open:  
(1) Single-unit installation (2) Obstacles on both sides  
(1) Single-unit installation  
Min. B  
(2) Multiple-unit installation (2 or more units)  
Min. C  
(3) Multiple-unit installation (2 or more units)  
Min. I  
Min. I  
H
I
J
Outdoor unit  
CHX03652/06052  
19-11/16 11-13/16 39-3/8  
Min. E  
Min. E  
Min. E  
Min. F  
A
B
C
D
E
F
G
Outdoor unit  
CHX03652/06052  
5-29/32 5-29/32 11-13/16 7-7/8 11-13/16 5-29/32 7-7/8  
G
Note: In cases 2 and 3 the height of the obstacle  
must be no taller than the height of the outdoor  
unit.  
Top is blocked by an obstacle:  
G
Top is blocked by an obstacle:  
Min. M  
Min. L  
M
N
Outdoor unit  
CHX03652/06052  
39-3/8 39-3/8  
K
L
Outdoor unit  
CHX03652/06052  
19-11/16 5-29/32  
Unit: in.  
23  
Reference diagram for snow-proof ducting – 2  
Space requirements for setting – (2)  
CHX03652/06052  
[Obstacles to the front and rear of unit]  
G
The top and both sides must remain open. Either the obstacle to the front or  
the obstacle to the rear must be no taller than the height of the outdoor unit.  
(1) Single-unit installation  
Dimension Q  
If a snow protection duct is attached after the unit is  
installed, verify that dimension Q is 19-11/16 in. or more.  
O
P
Outdoor unit  
CHX03652/06052  
39-3/8 5-29/32  
(2) Obstacles on both sides  
Min. 11-13/16  
Min. 11-13/16  
[Installation in front-rear rows]  
G The top and both sides must remain open. Either the obstacle to the front or the obstacle  
to the rear must be no taller than the height of the outdoor unit.  
0
Min. 11-13/16  
Min. 39-3/8  
Min. 7-7/8  
Min. 59-1/16  
Min. 78-3/4  
Dimension Q  
If a snow protection duct is  
attached after the unit is  
installed, verify that dimension  
Q is 19-11/16 in. or more.  
Unit: in.  
24  
3. HOW TO INSTALL THE INDOOR UNIT  
I 4-Way Air Discharge Semi-Concealed Type (X Type)  
Note: For DC Fan Tap Change Procedure  
for 4-Way Cassette, see page 31.  
3-1. Preparation for Suspending  
This unit uses a drain pump. Use a carpenter’s level to check that the  
unit is level.  
Hole-in-anchor  
Hole-in-plug  
X
Concrete  
Insert  
3-2. Suspending the Indoor Unit  
(1) Fix the suspension bolts securely in the ceiling using the method  
shown in the diagrams (Figs. 3-1 and 3-2), by attaching them to the  
ceiling support structure, or by any other method that ensures that  
the unit will be securely and safely suspended.  
Suspension bolt (M10 or 3/8")  
(field supply)  
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the ceiling.  
Fig. 3-1  
Table 3-1  
Unit: in. (mm)  
Length  
A
B
C
D
Type  
31-1/32 28-15/32 34-27/32 34-27/32  
(788) (723) (885) (885)  
12, 18, 24, 36  
(3) Determine the pitch of the suspension bolts using the supplied full-  
scale installation diagram. The diagram and table (Fig. 3-3 and  
Table 3-2) show the relationship between the positions of the sus-  
pension fitting, unit, and panel.  
Unit: in. (mm)  
Table 3-2  
A (suspension bolt pitch)  
Length  
A
B
C
D
E
Type  
C (ceiling opening dimension)  
4-29/64  
(113)  
6-13/16  
(173)  
10-5/64  
(256)  
8-17/64  
(210)  
3-15/32  
(88)  
12, 18, 24  
Fig. 3-2  
4-29/64  
(113)  
6-13/16  
(173)  
12-9/16  
(319)  
8-17/64  
(210)  
3-15/32  
(88)  
36  
Drain outlet(other side)  
Refregerant tubing joint(liquid side)  
Refregerant tubing joint(gas side)  
(VP25)  
Suspension lug  
Power supply outlet  
Inter-unit control wiring  
Unit: in. (mm)  
Fig. 3-3  
3-3. Placing the Unit Inside the Ceiling  
(1) When placing the unit inside the ceiling, determine  
the pitch of the suspension bolts using the supplied  
full-scale installation diagram. (Fig. 3-4)  
Tubing and wiring must be laid inside the ceiling  
when suspending the unit. If the ceiling is already  
constructed, lay the tubing and wiring into position  
for connection to the unit before placing the unit  
inside the ceiling.  
Full-scale installation diagram  
(printed on top of container box)  
Supplied bolt  
Unit: in. (mm)  
Fig. 3-4  
25  
(2) The length of suspension bolts must be appropriate  
for a distance between the bottom of the bolt and the  
bottom of the unit of more than 19/32 in. as shown in  
Fig. 3-5.  
Suspension bolt  
Suspension lug  
Nuts and washers  
(use for upper and lower)  
(3) Thread the 3 hexagonal nuts and 2 washers (field  
supply) onto each of the 4 suspension bolts as shown  
in Fig. 3-5. Use 1 nut and 1 washer for the upper side,  
and 2 nuts and 1 washer for the lower side, so that the  
unit will not fall off the suspension lugs.  
X
Notch  
Double nut  
15/32 – 43/64 (12 – 17)  
(4) Adjust so that the distance between the unit and the  
ceiling bottom is 15/32 to 43/64 in. Tighten the nuts on  
the upper side and lower side of the suspension lug.  
Unit: in.  
Fig. 3-5  
(5) Remove the protective polyethylene used to protect  
the fan parts during transport.  
Hard PVC  
socket  
Hard PVC pipe  
VP-25  
(Field supply)  
Hose band  
Connection pipe  
VP-25  
(Field supply)  
3-4. Installing the Drain Piping  
Supplied  
drain hose  
(drain port)  
(1) Prepare a standard hard PVC pipe (O.D. 1-1/4 in.) for  
the drain and use the supplied drain hose and hose  
band to prevent water leaks.  
The PVC pipe must be purchased separately. The  
unit’s transparent drain port allows you to check  
drainage. (Fig. 3-6)  
PVC adhesive  
Packing  
(supplied)  
Align the hose  
band with the end  
of the pipe  
CAUTION  
Bead  
Fig. 3-6  
G Insert the drain pipe until it contacts the socket, as  
shown in Fig. 3-6, then secure it tightly with the  
hose band.  
G Do not use adhesive when connecting the supplied  
hose.  
Drain insulator (supplied)  
Reasons: 1. It may cause water to leak from the  
connection. Since the connection is  
slippery just after the adhesive has been  
applied, the pipe easily slips off.  
2. The pipe cannot be removed when  
maintenance is needed.  
Fig. 3-7  
G Do not bend the supplied drain hose 90° or more.  
The hose may slip off.  
G Align the hose bands with the end of the hose.  
Tighten the hose band firmly. Please make sure  
that the bead is not covered by the hose band.  
(Fig. 3-6)  
Air bleeder prohibited  
Tighten the hose clamps so  
their locking nuts face upward.  
(Fig. 3-6)  
CAUTION  
Fig. 3-8  
(2) After checking the drainage, wrap the supplied packing  
and drain pipe insulator around the pipe. (Fig. 3-7)  
G Do not install an air bleeder  
as this may cause water to  
spray from the drain pipe  
outlet. (Fig. 3-8)  
CAUTION  
NOTE  
Make sure the drain pipe has a downward gradient (1/100  
or more) and that there are no water traps.  
26  
CAUTION  
11-3/16 in. or less (as short as possible)  
33-15/32 in. or less  
G In cases where it is necessary to raise the height  
of the drain piping, the drain piping can be raised  
to a maximum height of 33-15/32" above the  
bottom surface of the ceiling. Under no  
conditions attempt to raise it higher than  
33-15/32" above the bottom surface of the ceiling.  
Doing so will result in water leakage. (Fig. 3-9)  
G Do not install the pipe with an upward gradient  
from the connection port. This will cause the  
drain water to flow backward and leak when the  
unit is not operating. (Fig. 3-10)  
0 – 45°  
X
* Length of supplied drain hose = 9-27/32 in.  
Fig. 3-9  
Upward gradient prohibited  
G Do not apply force to the piping on the unit side  
when connecting the drain pipe. The pipe should  
not be allowed to hang unsupported from its  
connection to the unit. Fasten the pipe to a wall,  
frame, or other support as close to the unit as  
possible. (Fig. 3-11)  
Fig. 3-10  
G Provide insulation for any pipes that are run  
indoors.  
Support  
pieces  
3-5. Checking the Drainage  
Fig. 3-11  
After wiring and drain piping are completed, use the  
following procedure to check that the water will drain  
smoothly. For this, prepare a bucket and wiping cloth to  
catch and wipe up spilled water.  
Drainage check  
(1) Connect power to the power terminal board (R, S  
terminals) inside the electrical component box.  
(2) Slowly pour about 0.3 gal of water into the drain pan  
to check drainage. (Fig. 3-12)  
(3) Short the check pin (CHK) on the indoor control  
board and operate the drain pump. Check the water  
flow through the transparent drain pipe and see if  
there is any leakage.  
Drain pan outlet  
Plastic container  
for water intake  
Water (Approx. 0.3 gal)  
(4) When the check of drainage is complete, open the  
check pin (CHK) and remount the tube cover.  
Fig. 3-12  
Be careful since the fan will  
start when you short the pin  
on the indoor control board.  
CAUTION  
27  
3-6. How to Install the Ceiling Panel  
A
must be within the range of 15/32 – 43/64 in.  
3-6-1. Before Installing the Ceiling Panel  
Checking the unit position  
If not within this range, malfunction or other trouble may result.  
(1) Check that the ceiling hole is within this range:  
X
33-55/64 × 33-55/64 to 35-53/64 × 35-53/64 in.  
Main unit  
(2) Use the full-scale installation diagram (from the  
packaging) that was supplied with the unit to  
determine the positioning of the unit on the ceiling  
surface. If the positions of the ceiling surface and  
unit do not match, air leakage, water leakage, flap  
operation failure, or other problems may result.  
A
Ceiling opening  
dimension  
Ceiling side  
Fig. 3-13  
Flap  
CAUTION  
G Never place the panel face-down. Either hang  
it vertically or place it on top of a projecting  
object. Placing it face-down will damage the  
surface.  
G Do not touch the flap or apply force to it.  
(This may cause flap malfunction.)  
Fig. 3-14  
Remove the air-intake grille and air filter from the  
ceiling panel. (Figs. 3-16, 3-17 and 3-18)  
Screw  
Latch  
a) Remove the 2 screws on the latch of the air-intake  
grille. (Fig. 3-16)  
b) Slide the air-intake grille catches in the direction  
1
shown by the arrows  
(Fig. 3-17)  
to open the grille.  
c) With the air-intake grille opened, remove the grille  
hinge from the ceiling panel by sliding it in the direc-  
tion shown by the arrow 2 . (Fig. 3-18)  
Fig. 3-15  
Air-intake grille  
Ceiling panel  
Removing the corner cover  
1
1
a) Slide the corner cover to the direction shown  
1
by the arrow  
(Fig. 3-18).  
to remove the corner cover.  
2
Air-intake grille hinge  
Fig. 3-16  
Fig. 3-17  
Ceiling panel  
Corner cover  
1
Push  
Strap  
Corner cover  
Fig. 3-18  
28  
Inter-unit control wiring  
3-6-2. Installing the Ceiling Panel  
After completing the wiring process, install the  
supplied wiring cover before installing the panel.  
It is not possible to install the wiring cover after  
installing the panel.  
The power must be turned ON in order to change the  
flap angle. (Do not attempt to move the flap by hand.  
Doing so may damage the flap.)  
X
Screw (supplied)  
Wiring cover (supplied)  
Power supply outlet  
M4-8 or 5/32" – 5/16"  
(1) Insert the temporary fasteners (stainless steel) on  
the inside of the ceiling panel into the square  
holes on the unit to temporarily fasten the ceiling  
panel in place. (Fig. 3-20-1)  
Fig. 3-19-1  
Fig. 3-19-2  
Square hole in unit  
G The ceiling panel must be installed in the correct  
direction relative to the unit. Align the REF. PIPE  
and DRAIN marks on the ceiling panel corner with  
the correct positions on the unit.  
Push when  
Temporary  
fastener  
you remove  
Temporary  
fastener  
G To remove the ceiling panel, support the ceiling  
panel while pressing the temporary fasteners  
toward the outside. (Fig. 3-20-1)  
Fig. 3-20-1  
Drain tubing corner  
(2) Align the panel installation holes and the unit  
screw holes.  
Refrigerant tubing  
corner  
(3) Tighten the supplied washer head screws at the  
4 panel installation locations so that the panel is  
attached tightly to the unit. (Fig. 3-20-2)  
After completing the  
wiring process, install  
the supplied wiring cover  
before installing the panel.  
It is not possible to install  
the wiring cover after  
installing the panel.  
(4) Check that the panel is attached tightly to the  
ceiling.  
Celling panel  
G At this time, make sure that there are no gaps  
between the unit and the ceiling panel, or between  
the ceiling panel and the ceiling surface.  
(Fig. 3-21)  
DRAIN mark  
G If there is a gap between the panel and the ceiling,  
leave the ceiling panel attached and make fine  
adjustments to the installation height of the unit to  
eliminate the gap with the ceiling. (Fig. 3-21)  
Panel installation hole  
(4 locations)  
REF,PIPE  
mark  
Washer head  
screws  
Fig. 3-20-2  
Insert a wrench  
or other tool into  
the corner cover  
installation hole  
and make fine  
adjustments to  
the unit nut.  
Do not allow  
gaps  
Main unit  
Ceiling surface  
Ceiling panel  
CAUTION  
Fig. 3-21  
Fig. 3-22  
The height of the unit can be adjusted from the  
ceiling panel corner hole, with the ceiling panel  
attached, to an extent that does not affect the  
unit levelness, the drain hose, or other elements.  
G If the screws are not sufficiently tight-  
ened, trouble such as that shown in  
the figure below may occur. Be sure  
to tighten the screws securely.  
G If a gap remains between the ceiling  
surface and the ceiling panel even  
after the screws are tightened,  
adjust the height of the unit again.  
Air leakage  
Air leakage from  
ceiling surface  
Staining  
Adjust so that there are no gaps.  
Condensation, water leakage  
Fig. 3-23  
29  
3-6-3. Wiring the Ceiling Panel  
(Direction that the unit faces has been changed to  
facilitate explanation.)  
(1) Open the cover of the electrical component box.  
Electrical component  
box cover  
(2) Connect the 7P wiring connector (red) from the  
ceiling panel to the connector in the unit electrical  
component box.  
X
Ceiling panel  
wiring connector  
G If the connectors are not connected, the Auto flap will  
not operate. Be sure to connect them securely.  
G Check that the wiring connector is not caught  
between the electrical component box and the cover.  
G Check that the wiring connector is not caught  
between the unit and the ceiling panel.  
Screws  
(3 locations)  
Ceiling panel side  
Mains side  
Clamp  
* Pass the wiring connector through the clamp to fasten it in place,  
as shown in the figure.  
3-6-4. How to Attach the Corner & Air-Intake Grille  
Attaching the corner cover and air-intake grille  
Fig. 3-24  
A. Attaching the corner cover  
(1) Check that the safety cord from the corner cover is  
fastened to the ceiling panel pin, as shown in the  
figure.  
Pin  
(2) Use the supplied screws to attach the corner cover  
to the ceiling panel.  
B. Attaching the air-intake grille  
Place the corner cover so that the 3 tabs  
fit into the holes in the ceiling panel.  
Then fasten it in place with the supplied screws.  
G To install the air-intake grille, follow the steps for  
Removing the grille in the reverse order. By rotating  
the air-intake grille, it is possible to attach the grille  
onto the ceiling panel from any of 4 directions.  
Coordinate the directions of the air-intake grilles  
when installing multiple units, and change the  
directions according to customer requests.  
Fig. 3-25  
Hole for ceiling panel hook  
G When attaching the air-intake grille, be careful  
that the flap lead wire does not become caught.  
G Be sure to attach the safety cord that prevents  
the air-intake grille from dropping off to the  
ceiling panel unit as shown in the figure at right.  
G With this ceiling panel, the directions of the air-intake  
grille lattices when installing multiple units, and the  
position of the label showing the company name on  
the corner panel, can be changed according to  
customer requests, as shown in the figure below.  
However, the optional wireless receiver kit can only  
be installed at the refrigerant-tubing corner of the  
ceiling unit.  
Hook that prevents  
the grille from dropping  
Fig. 3-26  
Locations of the air-intake grille catches at  
the time the product is shipped.  
* The grille can be installed with these  
Unit drain hose side  
Unit refrigerant tube side  
catches facing in any of 4 directions.  
Optional wireless receiver kit  
* Can only be installed  
in this position.  
Can be installed rotated 90˚  
Unit electrical component box  
Fig. 3-27  
30  
3-6-5. Checking After Installation  
G Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling  
surface. Gaps may cause water leakage and condensation.  
G Check that the wiring is securely connected.  
If it is not securely connected, the auto flap will not operate. (“P09” is displayed on the remote controller.) In addition,  
water leakage and condensation may occur.  
X
3-6-6. When Removing the Ceiling Panel for Servicing  
When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the wiring connector  
inside the electrical component box, and then remove the 4 mounting screws.  
3-6-7. Adjusting the Auto Flap  
The air-direction louver on the ceiling panel outlet can be adjusted as follows.  
G Adjust the louver to the desired angle using the remote controller. The louver also has an automatic air-sweeping  
mechanism.  
NOTE  
G Never attempt to move the louver by hand.  
G Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or  
heating seems inadequate, try changing the direction of the air flow.  
3-7. Special Remarks  
DC Fan Tap Change Procedure  
<Steps> Be sure to turn OFF the power (at mains) before beginning the work below.  
(1) In the table below, check the field-supply parts that will be used. (If this setting is not made, the airflow may  
decrease and condensation may occur.)  
Setting  
Air shield material (for use with 3-direction discharge)*  
(a)  
Air shield material (for use when a discharge duct is connected)*  
(b)  
Air shield material (for use with 2-direction discharge)*  
* Use field-supply air shield material.  
Setting (a): Go to (2).  
Setting (b): Go to (3).  
Indoor unit control PCB  
(2) Setting (a)  
Open the cover of the electrical component box.  
Short the short-circuit pin TP3 (2P, yellow) on the  
indoor unit control PCB.  
* PCB model No.: CR-SXRP56B-B  
(3) Setting (b)  
Open the cover of the electrical component box.  
Short the short-circuit pin TP6 (2P, white) on the  
indoor unit control PCB.  
Fig. 3-28  
31  
I 1-Way Air Discharge Semi-Concealed Type (A Type)  
29-59/64 (Panel outer dimensions)  
28-47/64 (Ceiling opening dimension)  
25-63/64 (Suspension bolt pitch)  
Unit: in.  
3-8. Suspending the Indoor Unit  
(1-27/64)  
1-27/64  
(1) Follow the diagrams to make the holes in the ceiling.  
(Figs. 3-29 and 3-30)  
(2) Depending on the ceiling type:  
G Insert suspension bolts as shown in Fig. 3-31  
or  
G Use existing ceiling supports or construct a suitable  
support as shown in Fig. 3-32.  
A
G Make sure that the length of suspension bolts from the  
bottom of the unit is 19/32 in. or more. (Fig. 3-33)  
23-5/8  
Fig. 3-29  
Drain pipe connection  
(Be sure to connect the supplied flexible hose.)  
WARNING  
22-3/64  
It is important that you use extreme care in  
supporting the indoor unit from the ceiling. Ensure  
that the ceiling is strong enough to support the  
weight of the unit. Before hanging the unit, test the  
strength of each attached suspension bolt.  
10-1/32  
1-19/64  
5-19/64  
1-49/64  
(3) Calculate the suspension bolt pitch using the full-  
size installation diagram (printed on the package).  
The relationship between the positions of the  
suspension lugs, unit, and ceiling panel is as  
shown in Fig. 3-30.  
Flared refrigerant  
connection outlet  
(liquid tube)  
Flared refrigerant  
connection outlet  
(gas tube)  
Inter-unit  
Control Wiring  
Power supply outlet  
Unit: in.  
(4) Cut the ceiling material, if necessary.  
(Figs. 3-29 and 3-30)  
Fig. 3-30  
If the system requires fresh air to be drawn into the unit,  
cut and remove the insulation (both externally and  
Hole-in-anchor  
Hole-in-plug  
Concrete  
Insert  
A
internally) at the location shown as  
3-35.  
in Figs. 3-34 and  
Suspension bolt  
(M10 or 3/8")  
CAUTION  
Fig. 3-31  
When making the cuts to the insulation, be careful  
not to damage the drain pan.  
32  
Ceiling tiles  
3-9. Placing the Unit Inside the Ceiling  
Be sure to use a level gauge  
Ceiling support  
CAUTION  
and confirm that the unit is  
level. If it is not level, water  
leakage may occur.  
(1) Use the supplied M5 or 3/16" screws (4) to attach  
the full-size installation diagram to the indoor unit  
suspension lugs, in order to obtain the ceiling  
opening dimensions for suspending the unit.  
Fig. 3-32  
A
Full-scale  
installation diagram  
Caution: Piping and wiring work must be performed  
inside the ceiling after the unit is suspended.  
Therefore if the ceiling is already installed, the  
wiring and piping work should be completed  
up to the connection points prior to  
Suspension  
lug  
suspending the unit.  
over 19/32 in.  
25/32 – 1 in.  
(2) Attach the special washers (supplied) and nuts (field  
supply) to the suspension bolts (4 locations).  
Fig. 3-33  
CAUTION  
For fresh air intake  
3-15/16 hole)  
A
3-5/32  
G Use M10 or 3/8" nuts.  
G The length of the suspension bolts must be such that  
there is a space of at least 19/32 in. below the bottom  
of the suspension lugs, as shown in Fig. 3-33. If the  
length of the suspension bolts is too long, the bolts  
may interfere with the ceiling panel and louver motor,  
preventing their installation.  
Unit: in.  
Fig. 3-34  
(3) Thread the 3 hexagonal nuts and 2 washers (field  
supply) onto each of the 4 suspension bolts as  
shown in Fig. 3-36. Use 1 nut and 1 washer for the  
upper side, and 2 nuts and 1 washer for the lower  
side, so that the unit will not fall off the suspension  
lugs.  
For fresh air intake  
3-15/16 hole)  
6-11/16  
A
(4) Lift up the indoor unit and fit the suspension bolts  
into the notches in the suspension lugs.  
(5) Adjust so that the distance between the bottom of  
the indoor unit suspension lugs and the bottom of  
the ceiling panel is 25/32 – 1 in. Then tighten the  
nuts above and below each suspension lug. The  
full-size installation diagram can be used to help  
adjust the height of the indoor unit.  
Unit: in.  
Fig. 3-35  
Suspension bolt  
Nuts and washers  
Suspension lug  
(Used above and below.)  
Double nuts  
Notch  
over 19/32 in.  
25/32 – 1 in.  
Fig. 3-36  
33  
2-1/8  
2-1/8  
CAUTION  
G The indoor unit includes a drain pump. Be sure to  
use a level gauge and verify that the unit is level.  
G Before inserting the ceiling material, complete as  
much of the drain piping work and refrigerant  
tubing work as possible.  
Suspension bolts  
Tubing side  
Unit: in.  
(6) The distance between the unit and the opening of  
the ceiling and the distance between the bottom  
surface of the ceiling and the bottom surface of the  
flange of the unit should follow the dimensions given  
in Figs. 3-37 and 3-38.  
Suspension bolts  
A
Fig. 3-37  
Ceiling  
material  
3-10. Installing the Drain Piping  
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for  
the drain and use the supplied drain hose and hose  
band to prevent water leaks.  
Fig. 3-38  
The PVC pipe must be purchased separately. The  
unit’s transparent drain port allows you to check  
drainage. (Fig. 3-39)  
Align the hose band with end of the  
hose, and tighten so that it does not  
contact the bead.  
CAUTION  
Drainage check  
Hard PVC  
section on drain port  
pipe  
Drain hose  
(supplied)  
Hard PVC  
(transparent)  
VP-25  
(not supplied)  
socket VP-25  
G Do not use adhesive at the drain connection port on  
the indoor unit.  
(not supplied)  
G Insert the drain pipe until it contacts the socket, as  
shown in the figure at right, then secure it tightly with  
the hose band.  
PVC adhesive  
Packing (supplied)  
Bead  
G Tighten the hose clamps so their locking nuts face  
upward. (Fig. 3-39)  
Fig. 3-39  
G Do not use the supplied drain hose bent at a 90°  
angle. (The maximum permissible bend is 45°.)  
G Check the drainage at the unit drain port  
(transparent).  
Drain insulator (supplied)  
(2) After checking the drainage, wrap the supplied  
packing and drain pipe insulator around the pipe,  
then secure it with the supplied clamps. (Fig. 3-40)  
Fig. 3-40  
NOTE  
Make sure the drain pipe has a downward gradient  
(1/100 or more) and that there are no water traps.  
34  
CAUTION  
G Do not install an air bleeder as this may cause water  
to spray from the drain pipe outlet. (Fig. 3-41)  
G In cases where it is necessary to raise the height of  
the drain piping, the drain piping can be raised to a  
maximum height of 33-15/32" above the bottom  
surface of the ceiling. Under no conditions attempt to  
raise it higher than 33-15/32" above the bottom  
surface of the ceiling. Doing so will result in water  
leakage. (Fig. 3-42)  
Air bleed valve  
Fig. 3-41  
A
11-13/16 in. or less  
33-15/32 in. or less  
G Do not use natural drainage.  
0 – 45°  
G Do not install the pipe with an upward gradient from  
the connection port. This will cause the drain water  
to flow backward and leak when the unit is not  
operating. (Fig. 3-43)  
* Length of supplied drain hose = 9-27/32 in.  
Fig. 3-42  
G Do not apply force to the piping on the unit side when  
connecting the drain pipe. The pipe should not be  
allowed to hang unsupported from its connection to  
the unit. Fasten the pipe to a wall, frame, or other  
support as close to the unit as possible. (Fig. 3-44)  
G Provide insulation for any pipes that are run indoors.  
Uphill slope  
Fig. 3-43  
3-11. Checking the Drainage  
Support  
bracket  
After wiring and drain piping are completed, use the  
following procedure to check that the water will drain  
smoothly. For this, prepare a bucket and wiping cloth to  
catch and wipe up spilled water.  
(1) Connect power to the power terminal board (R, S  
terminals) inside the electrical component box.  
Fig. 3-44  
(2) Pour about 0.2 gal of water into the drain pan using a  
siphon pump through the air outlet grille. (Fig. 3-45)  
Drainage check  
(3) Short the check pin (CHK) on the indoor control board  
and operate the drain pump. Check the water flow  
through the transparent drain pipe and see if there is any  
leakage.  
Drain tube  
connection  
(transparent)  
Discharge port  
water (0.2 gal)  
Be careful since the fan will start  
when you short the pin on the indoor  
control board.  
CAUTION  
Fig. 3-45  
(4) When the drainage check is complete, open the check  
pin (CHK) and remount the insulator.  
The bottom drain port is for use only  
CAUTION  
during test runs and servicing  
inspections. Do not connect the drain  
pipe to the bottom drain port.  
35  
Refrigerant tubing joint  
(gas tube)  
Drain pipe connection  
(Be sure to connect the  
supplied flexible hose.)  
3-12. Electrical Power Wiring  
(1) Wiring connections  
Refrigerant tubing joint  
(liquid tube)  
The power inlet is on the side of the indoor unit where the  
refrigerant tubing is located. The electrical component box  
is on the lower air intake surface of the indoor unit.  
(Fig. 3-46)  
Inter-unit Control Wiring  
Power supply outlet  
(2) Wiring  
A
WARNING  
Fig. 3-46  
G Route the power wiring into the indoor unit through the power inlet on the side of the unit. At this time, be  
sure that the wiring passes through the power inlet in the unit power section. If the wiring does not pass  
through this inlet, it may become pinched by the ceiling panel, and may result in fire.  
G Pass the wiring through the power inlet on the electrical component box and connect it to the terminal plate.  
Then fasten the wiring in place with the clamp.  
3-13. How to Install the Ceiling Panel  
Component Parts  
Part name  
Quantity  
Appearance  
Part name  
Quantity  
Appearance  
M5 × 40  
Washer-head  
screw  
or  
4
5/16" × 9/16"  
Ceiling panel  
1
4 × 12 or 5/32" × 15/32"  
For fastening  
Screw  
2
side panel  
3-13-1. Before Installing the Ceiling Panel  
Checking the position of the indoor unit  
Be sure that this distance is within the range of 25/32 – 1 in.  
If it is not within this range, malfunction or other problems may result.  
(1) Check that the dimensions of the ceiling opening are  
the following:  
28-47/64" × 23-17/64"  
Indoor unit  
* For details, refer to the installation manual that was  
supplied with the indoor unit.  
Ceiling opening dimension  
Ceiling surface  
(2) Check that the positions of the ceiling surface and  
indoor unit are as shown in Fig. 3-47. If the positions  
of the ceiling surface and indoor unit are not correct,  
problems such as air leakage, water leakage, and flap  
operation trouble may occur.  
Fig. 3-47  
G Do not rest the panel facing downwards, lean up against  
a wall, or leave it sitting on top of a protruding object.  
Doing so may scratch the panel surface.  
G Do not apply excessive force to the flap.  
(Doing so may damage the flap.)  
Flap  
Fig. 3-48  
36  
Removing the intake grille  
Screw  
Slide the intake grille hooks (2 locations)  
in the direction of the arrow to open the  
intake grille. (fig. 3-49a)  
Screw  
Hook  
When the intake grille is open, press a  
flathead screwdriver against the rear  
tabs (2 locations) and pull out the intake  
grille. (Fig. 3-49b)  
Fig. 3-49a  
Intake grille  
A
Removing the side panel  
Grasp the finger grip on the side panel  
and slide the panel in the direction of  
arrow  
to remove the panel.  
1
(There are 2 panels: 1 each on the left  
and right sides.) (Fig. 3-51)  
Hinge  
Fig. 3-49b  
Press on the tabs with a flathead (minus)  
screwdriver while pulling out the intake grille.  
Tab  
Fig. 3-50  
Slide  
1
Side panel  
Fig. 3-51  
3-13-2. Installing the ceiling panel  
Hook receiver Press to remove.  
(1) Fasten the hooks on both sides of the ceiling panel to  
the indoor unit. The hooks on one side (2 locations) are  
stationary, while the hook on the other side is move-  
able. (Fig. 3-52)  
Stationary hook  
(2) Angle the panel somewhat and fasten the stationary  
hook into the fastener on the side of the unit.  
Moveable hook  
Fig. 3-53  
(3) After verifying that the hook is fastened, press the other  
end up until the ceiling panel is level. Then press  
upwards until the moveable hook is fastened into the  
fastener on the unit.  
(4) Verify that the hooks on both sides of the ceiling panel  
are securely fastened to the unit. If the hooks are not  
securely fastened, the panel may fall. At this point, the  
panel is now provisionally fastened to the unit.  
Moveable hook  
Fig. 3-52  
G When removing the panel, press the movable hook  
toward the inside while supporting the panel. (Fig. 3-53)  
37  
(5) Align the installation holes on the panel with the  
bolt holes on the unit.  
Indoor unit  
(6) Insert the supplied washer head bolts into the 4  
panel installation holes, and tighten until the panel  
is securely fastened against the unit. (Fig. 3-54)  
(7) Verify that the panel is securely fastened against  
the unit.  
G At this time, make sure that there is no gap  
between the indoor unit and the ceiling panel, or  
between the ceiling panel and the ceiling surface.  
(Fig. 3-55)  
A
G If there is a gap between the ceiling panel and the  
ceiling, leave the panel attached and adjust the  
installation height of the indoor unit upwards until  
the gap with the ceiling is eliminated. (Fig. 3-56)  
Ceiling panel  
G If the adjustment is small enough that it will not  
affect the levelness of the indoor unit or the drain  
piping, then the unit height can be adjusted from  
the side panel installation holes, with the ceiling  
panel still attached.  
Washer-head screw  
Fig. 3-54  
Must be no gap.  
Insert a wrench or other  
standard tool into the side  
panel installation holes  
and make fine adjustments  
to the indoor unit nuts.  
Indoor unit  
Ceiling surface  
Ceiling panel  
Fig. 3-55  
Fig. 3-56  
CAUTION  
• If the screws are not fully tightened,  
problems such as those shown below  
may occur. Be sure to tighten the  
screws securely.  
• If there is a gap between the ceiling  
surface and the ceiling panel even  
when the screws are fully tightened,  
readjust the height of the indoor unit.  
(Fig. 3-56)  
Air leakage  
Ceiling panel  
air leakage  
Stains  
Adjust so that there is no gap.  
Condensation and water leakage  
38  
3-13-3. Wiring the ceiling panel  
(1) Loosen the 2 screws on the electrical component  
box lid, and remove the lid. (Fig. 3-57)  
(2) Fasten the wiring connector (7P, red) which comes  
out from the ceiling panel using the lead wire clamps  
(2 locations) on the unit. Then connect it to the  
connector (7P, red) inside the indoor unit electrical  
component box. (Fig. 3-58)  
G If the connector is not connected, “P09” is displayed  
on the remote controller, and the automatic flap will  
not operate. Be sure to securely connect the connec-  
tor.  
A
Screw  
Electrical compornent  
box cover  
Fig. 3-57  
G Check that the wiring connector is not pinched  
between the electrical component box and the lid.  
G Check that the wiring connector is not pinched  
between the indoor unit and the ceiling panel.  
3-13-4. Installing the side panel and intake grille  
A. Installing the side panel  
(1) Grasp the side panel finger grip and slide the panel  
in the direction of the arrow to install the side panel.  
(Fig. 3-59)  
Inter-unit control wiring  
Power supply outlet  
(2) Fasten the side panel onto the ceiling panel using  
Electrical compornent box  
the supplied screws (4 × 12 or 5/32" × 15/32").  
Indoor unit connector  
B. Installing the intake grille  
Fig. 3-58  
G To install the intake grille, follow the procedure for  
removing it in the reverse order. (Fig. 3-60)  
G When installing the intake grille, be careful that the  
flap lead wire does not become pinched. (Fig. 3-60)  
Fasten with screws  
(4 × 12 or 5/32" × 15/32")  
Tabs  
Tab  
Slide  
3-13-5. Other  
A. Check after installation  
G Check again that there is no gap between the indoor  
unit and the ceiling panel, or between the ceiling  
panel and the ceiling surface.  
Slide the side panel so that the side panel tabs are fastened to  
the ceiling panel. Then fasten in place with the supplied screws  
(4 × 12 or 5/32" × 15/32").  
* If there is a gap, then water leakage and condensa-  
tion may occur.  
Fig. 3-59  
G Check that the wiring connections are secure.  
* If the wiring is not connected, the automatic flap will  
not operate. (“P09” is displayed on the remote  
controller.) In addition, water leakage,  
Screw  
Screw  
condensation, and other problems may occur.  
B. If a wireless remote controller is used  
G For details concerning the installation procedure,  
refer to the installation manual which was supplied  
with the optional wireless remote controller and  
indoor unit internal receiver.  
Fig. 3-60  
39  
I Concealed Duct Type (U Type)  
3-14. Required Minimum Space for  
A (Suspension bolt pitch)  
Electrical  
component box  
Installation and Service  
G This air conditioner is usually installed above the ceiling so that the  
indoor unit and ducts are not visible. Only the air intake and air outlet  
ports are visible from below.  
Inspection  
access  
17-23/32  
min.  
9-27/32  
Indoor unit  
17-23/32  
G The minimum space for installation and service is shown in  
Fig. 3-61 and Table 3-3.  
Refrigerant  
tubing  
min. 25-19/32  
G It is recommended that space is provided (17-23/32 × 17-23/32 in.)  
for checking and servicing the electrical system.  
G Fig. 3-62 and Table 3-4 show the detailed dimensions of the indoor  
unit.  
Air outlet duct flange  
Unit: in.  
Fig. 3-61  
Table 3-3  
Unit: in. (mm)  
U
Type  
7, 12, 18  
24  
36  
A (Length)  
30-23/32 (780) 42-17/32 (1,080) 61-13/32 (1,560)  
Number of duct flanges  
2
3
4
Table 3-4  
Unit: in.  
Dimension  
No. of holes  
A
B
C
D
E
F
G
H
I
J
K
Type  
L
M
23-5/8  
7, 12, 18  
24  
26-1/16  
37-7/8  
27-9/16 30-23/32 11-13/32 10-5/16 26-25/32 28-5/32 7-3/32  
39-3/8 42-17/32 11-13/32 10-23/32 38-19/32 39-31/32 5-1/8  
58-9/32 61-13/32 13-3/16 12-7/32 57-15/32 58-27/32 5-1/8  
13-3/8  
8
12  
(7-7/8 × 3)  
35-7/16  
(7-3/32 × 5)  
54-11/32  
(9-1/16 × 6)  
9-21/32  
(9-21/32 × 1)  
19-9/32  
(9-21/32 × 2)  
9-27/32  
12  
16  
16  
36  
56-25/32  
9-7/16  
18  
Refrigerant tubing joint (liquid tube)  
Refrigerant tubing joint (gas tube)  
Upper drain port (O.D. 1-1/4 in.)  
Bottom drain port (O.D. 1-1/32 in.)  
Suspension lug  
13/32  
13/32  
L-ø1/4  
(Hole)  
11  
I
J
K
J
I
Power supply outlet (2-ø1-3/16 hole)  
Fresh air intake port (ø5-29/32 hole)  
3/4  
3/4  
A (O.D.)  
Flange for the flexible air outlet duct (ø7-7/8 hole)  
Tube cover  
Electrical component box  
Flange for the air intake duct  
(Option or field supply)  
H (Duct suspension bolt pitch)  
G (Ceiling opening dimension)  
4-ø15/32  
(Hole)  
Inter-unit control wiring  
12-7/32  
31/32  
8-9/32  
31/32  
6-7/8  
1-7/32  
1-7/32  
3-17/32  
B
18-ø1/8  
(Hole)  
10  
9
Inspection access  
(17-23/32  
17-23/32)  
(Field supply)  
1-9/16  
C
D
1-3/8  
(5-29/32)  
(Suspension bolt pitch)  
5-1/8  
11-7/32  
2-3/4  
2-15/16  
2-9/16  
E
E
E
F
Inspection access panel  
Ceiling  
Unit: in.  
Fig. 3-62  
40  
3-15. Suspending the Indoor Unit  
Depending on the ceiling type:  
Hole-in-anchor  
Hole-in-plug  
Concrete  
Insert  
• Insert suspension bolts as shown in Fig. 3-63  
or  
• Use existing ceiling supports or construct a suitable support as  
shown in Fig. 3-64.  
Suspension bolt (M10 or 3/8")  
(field supply)  
It is important that you use extreme care  
WARNING  
Fig. 3-63  
in supporting the indoor unit inside the  
ceiling. Ensure that the ceiling is strong  
enough to support the weight of the unit.  
Before hanging the unit, test the strength  
of each attached suspension bolt.  
Ceiling tiles  
Ceiling support  
U
(1) When placing the unit inside the ceiling, determine the pitch of  
the suspension bolts referring to the dimensional data on the  
previous page. (Fig. 3-61 and Table 3-3)  
Tubing must be laid and connected inside the ceiling when  
suspending the unit. If the ceiling is already constructed, lay the  
tubing into position for connection to the unit before placing the  
unit inside the ceiling.  
Fig. 3-64  
Suspension bolt  
(2) Screw in the suspension bolts allowing them to protrude from  
the ceiling as shown in Fig. 3-63. (Cut the ceiling material, if  
necessary.)  
Suspension lug  
Nuts and washers  
(use for upper and lower)  
(3) Thread the 3 hexagonal nuts and 2 washers (field supply) onto  
each of the 4 suspension bolts as shown in Figs. 3-65 and 3-66.  
Use 1 nut and 1 washer for the upper part, and 2 nuts and 1  
washer for the lower part, so that the unit will not fall off the  
suspension lugs.  
Notch  
Double nuts  
Fig. 3-65  
Suspension bolt  
Hexagonal nut  
Double nuts  
G Fig. 3-67 shows an example of installation.  
Bolt anchor  
Fig. 3-66  
Air outlet duct  
Suspension bolt  
Air-intake duct  
Air-outlet grille  
Ceiling material  
Indoor unit  
Air-intake grille  
Fig. 3-67  
41  
3-16. Installing the Drain Piping  
Align the hose band with end of the  
hose, and tighten so that it does not  
contact the bead.  
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the drain  
and use the supplied hose band to  
Drainage check  
Hard PVC  
pipe  
VP-25  
(not supplied)  
prevent water leaks.  
section on drain port  
(transparent)  
Drain hose  
(supplied)  
Hard PVC  
The PVC pipe must be purchased separately.  
The transparent drain part on the unit allows you to check  
drainage. (Fig. 3-68)  
socket VP-25  
(not supplied)  
CAUTION  
PVC adhesive  
Packing (supplied)  
Bead  
G Do not use adhesive at the drain connection port on the  
indoor unit.  
Fig. 3-68  
G Insert the drain pipe until it contacts the socket, as shown in  
the figure at right, then secure it tightly with the hose band.  
G Do not use the supplied drain hose bent at a 90° angle.  
(The maximum permissible bend is 45°.)  
Drain insulator (supplied)  
U
G Tighten the hose clamps so their locking nuts face upward.  
(FIg. 3-68)  
Vinyl clamps  
(2) After connecting the drain piping securely, wrap the supplied  
packing and drain pipe insulator around the pipe, then secure it  
with the supplied vinyl clamps. (Fig. 3-69)  
Fig. 3-69  
Air bleeder  
NOTE  
Make sure the drain pipe has a downward gradient (1/100 or more)  
and that there are no water traps.  
Prohibited  
Fig. 3-70  
G Do not install an air bleeder as this may  
CAUTION  
cause water to spray from the drain pipe  
outlet. (Fig. 3-70)  
11-13/16" or less  
19-11/16" or less  
Good  
G If it is necessary to increase the height of the drain pipe, the  
section directly after the connection port can be raised a  
maximum of 19-11/16". Do not raise it any higher than  
19-11/16", as this could result in water leaks. (Fig. 3-71)  
G Do not install the pipe with an upward gradient from the connec-  
tion port. This will cause the drain water to flow backward and leak  
when the unit is not operating. (Fig. 3-72)  
Fig. 3-71  
Upward gradient  
G Do not apply force to the piping on the unit side when connecting  
the drain pipe. The pipe should not be allowed to hang unsupport-  
ed from its connection to the unit. Fasten the pipe to a wall, frame,  
or other support as close to the unit as possible. (Fig. 3-73)  
Prohibited  
Fig. 3-72  
3-17. Checking the Drainage  
After wiring and drain piping are completed, use the following proce-  
dure to check that the water will drain smoothly. For this, prepare a  
bucket and wiping cloth to catch and wipe up spilled water.  
Support pieces  
(1) Connect power to the power terminal board (R, S terminals)  
inside the electrical component box.  
(2) Remove the tube cover and through the opening, slowly pour  
about 0.3 gal of water into the drain pan to check drainage.  
Fig. 3-73  
(3) Short the check pin (CHK) on the indoor control board and oper-  
ate the drain pump. Check the water flow through the transparent  
drain port and see if there is any leakage.  
42  
Power supply outlet  
Be careful since the fan will start when you  
short the pin on the indoor control board.  
CAUTION  
Inter-unit control wiring  
(4) When the check of drainage is complete, open the check pin (CHK)  
and remount the insulator and drain cap onto the drain inspection port.  
3-18. Increasing the Fan Speed  
If external static pressure is too great (due to long extension of ducts, for  
example), the air flow volume may drop too low at each air outlet. This problem  
may be solved by increasing the fan speed using the following procedure:  
(1) Remove 4 screws on the electrical component box and  
remove the cover plate.  
(2) Disconnect the fan motor sockets in the box.  
U
Fig. 3-74  
(3) Take out the booster cable (sockets at both ends)  
clamped in the box.  
Indoor Fan Performance  
(4) Securely connect the booster cable sockets between the  
disconnected fan motor sockets in step 2 as shown in  
Fig. 3-75.  
7, 12 Type  
18 Type  
(in.WG)  
0.60  
(in.WG)  
0.60  
(5) Place the cable neatly in the box and reinstall the cover  
plate.  
0.40  
0.20  
0
0.40  
0.20  
0
Electrical component box  
Booster cable  
HT  
Fan  
Booster cable  
motor  
HT  
H
H
M
M
Fan motor socket  
L
L
(At shipment)  
(Booster cable installed)  
Fig. 3-75  
353  
530  
177  
353  
Air Flow (CFM)  
Air Flow (CFM)  
How to read the diagram  
36 Type  
The vertical axis is the external static pressure (in.WG)  
while the horizontal axis represents the air flow (CFM).  
The characteristic curves for “HT,” H,M” and “Lfan  
speed control are shown. The nameplate values are  
shown based on the “H” air flow. For the 24 type, the air  
flow is 635 CFM, while the external static pressure is  
0.20 in.WG at “H” position. If external static pressure is  
too great (due to long extension of ducts, for example),  
the air flow volume may drop too low at each air outlet.  
This problem may be solved by increasing the fan  
speed as explained above.  
(in.WG)  
24 Type  
(in.WG)  
0.60  
0.60  
HT  
0.40  
0.40  
HT  
H
H
0.20  
0
0.20  
0
M
M
L
L
353  
706  
706  
1059  
Air Flow (CFM)  
Air Flow (CFM)  
HT: Using the booster cable  
NOTE  
H: At shipment  
Fig. 3-76  
43  
I Concealed Duct High-Static Pressure Type (D Type)  
Min. 23-5/8  
(Space for service)  
3-19. Required Minimum Space  
19-11/16  
11-27/64  
5-1/8  
for Installation and Service  
G This air conditioner is usually installed above the ceiling  
so that the indoor unit and ducts are not visible. Only the  
air intake and air outlet ports are visible from below.  
G The minimum space for installation and service is shown  
in Fig. 3-77.  
37  
Suspension  
bolt pitch  
38-37/64  
Suspension  
Air suction side  
bolt pitch  
G It is recommended that space be provided (23-5/8" ×  
23-5/8") for checking and servicing the electrical system.  
G Fig. 3-78 and Table 3-5 show the detailed dimensions of  
the indoor unit.  
Refrigerant tubing  
Electrical  
component  
box  
Inspection access  
(23-5/8" × 23-5/8")  
Min. 23-5/8  
Space for  
service  
D
Min. 22-53/64  
Drain pan  
Ceiling face  
Min. 5-1/8  
Unit: in.  
Fig. 3-77  
37  
31-7/32  
7 × 3-15/16 = 27-9/16  
22 - ø1/8  
25/32  
3-35/64  
2-5/32  
1-37/64  
(Hole for full  
circumference)  
2-23/64  
1-57/64  
Unit: in.  
Table 3-5  
Length  
A
B
C
Type  
Electrical component box  
36  
16-17/32 15-35/64 2-43/64  
48  
17-23/32 16-47/64 3-55/64  
4-ø25/32 hole for  
suspension bolt  
1-13/16  
4 × 3-15/16  
= 15-3/4  
Refrigerant liquid line (ø3/8 or ø1/4)  
Refrigerant gas line (ø3/4 or ø5/8)  
Power supply outlet  
16 - ø1/8  
(Hole for full  
19-11/16  
circumference)  
Drain connection (25A, O.D. 1-1/4")  
Duct connection for suction  
Duct connection for discharge  
Inter-unit control wiring  
19/32 38-37/64 (Suspension bolt pitch) 19/32  
24-13/32  
19-11/16  
39-49/64  
2-3/4  
1-3/8  
37  
1-3/8  
25/64  
25/64  
Drain pan  
Unit: in.  
Fig. 3-78  
44  
3-20. Suspending the Indoor Unit  
Depending on the ceiling type:  
Hole-in-anchor  
Hole-in-plug  
Concrete  
Insert  
G Insert suspension bolts as shown in Fig. 3-79  
or  
G Use existing ceiling supports or construct a suitable support as  
shown in Fig. 3-80.  
Suspension bolt (M10 or 3/8")  
(field supply)  
It is important that you use extreme care  
WARNING  
Fig. 3-79  
in supporting the indoor unit inside the  
ceiling. Ensure that the ceiling is strong  
enough to suport the weight of the unit.  
Before hanging the unit, test the strength  
of each attached suspension bolt.  
Ceiling tiles  
Ceiling support  
(1) When placing the unit inside the ceiling, determine the pitch  
of the suspension bolts referring to the dimensional data given  
previously. (Figs. 3-77 and 3-78)  
D
Tubing must be laid and connected inside the ceiling when  
suspending the unit. If the ceiling is already constructed, lay  
the tubing into position for connection to the unit before placing  
the unit inside the ceiling.  
Fig. 3-80  
Suspension bolt  
Hexagonal nuts  
(2) Screw in the suspension bolts allowing them to protrude from  
the ceiling as shown in Fig. 3-79. (Cut the ceiling material, if  
necessary.)  
and washers  
(2 sets)  
(3) Suspend and fix the indoor unit using the 2 hexagonal nuts  
(field supply) and special washers (supplied with the unit) as  
shown in Fig. 3-81.  
Fig. 3-81  
Air-outlet grille  
Air-intake grille  
Fig. 3-82  
45  
3-21. Installing the Drain Piping  
Sealing tape  
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the  
drain and use the supplied drain socket to prevent water  
leaks. The PVC pipe must be purchased separately.  
When doing this, apply adhesive for the PVC pipe at the  
connection point.  
Drain pan  
Drain joint  
(supplied)  
(2) If connecting a drain joint (supplied) to the threaded  
drain port, first wrap the drain port threads with sealing  
tape, then connect the joint. (Fig. 3-83)  
Drain opening  
(25A or 1-11/32" male screw)  
Fig. 3-83  
(3) After connecting the drain pipe securely, wrap insulator  
(field supply) around the pipe.  
Downward gradient  
(4) Ensure the drain pipe has a downward gradient (1/100  
or more) and prepare traps as indicated in Fig. 3-84.  
Min. 1/100  
(5) Also, in another part of the pipe arrangement, prepare  
traps with an inspection plug to clean dust or debris that  
may cause leaking of water. (Fig. 3-85)  
Good  
(6) After connecting the drain piping, slowly pour water into  
the drain pan to check that the water drains smoothly.  
D
3-22. Caution for Ducting Work  
Not good  
G This unit has high static pressure (applicable external static  
pressure Max. 0.68 – 0.88 in.WG. In the case of small  
pressure resistance (for instance, a short duct), install a  
damper for adjusting air flow volume as air flow volume /  
air flow noise increases.  
Fig. 3-84  
G If the air conditioner is to be installed in a room such as  
an office or meeting room which needs a low sound  
level, provide a supply and return noise absorption  
chamber with an acoustic liner.  
Min. 1-31/32 in.  
G Include an air filter (field supply) at the return duct.  
Inspection plug  
3-23. Indoor Fan Performance  
How to Read the Diagram  
Fig. 3-85  
36 Type  
48 Type  
(in.WG)  
1.00  
(in.WG)  
1.00  
The vertical axis is the External Static Pressure  
(in.WG) while the horizontal axis represents the  
Air Flow (CFM). The characteristic curve for the  
0.80  
0.80  
“H,Med,and “Lo” fan speed control.  
The nameplate values are shown based on the  
“H” air flow. Therefore in the case of 36 Type,  
the flow is 1059 CFM, while the External Static  
Pressure is 0.72 in.WG at “H” position. If the  
external static pressure is too great (due to long  
extension of duct, for example), the air flow  
volume may drop too low at each air outlet.  
0.60  
0.60  
0.40  
0.20  
0
0.40  
0.20  
0
883  
1059  
1236  
1059  
1236  
1412  
Air Flow (CFM)  
Air Flow (CFM)  
NOTE  
H: At shipment  
Fig. 3-86  
46  
I Ceiling-Mounted Type (T Type)  
3-24. Required Minimum Space for Installation and Service  
(1) Dimensions of suspension bolt pitch and unit  
B
C
Unit: in.  
Table 3-6  
Dimension  
A
B
C
Type  
Air intake  
12, 18  
24  
33-21/32 35-53/64 8-17/64  
44-19/64 46-29/64 8-17/64  
Ceiling side  
A
1-5/64  
1-5/64  
Air outlet  
Unit: in.  
(Suspension bolt pitch)  
Fig. 3-87  
(2) Refrigerant tubing • drain hose position  
2-21/64  
2-61/64  
3-61/64  
3-13/16  
Rear (figure shows view from front)  
Left side  
Right side  
8-1/2  
(Liquid tubing •  
Gas tubing)  
9/64  
Liquid  
tubing  
2-23/64  
T
Gas tubing  
3-5/16  
6-11/32  
9-7/8  
9-7/8  
5-3/4  
Left drain position  
Closed with rubber stopper at time of shipment.  
Right drain position  
Unit: in.  
Fig. 3-88  
(3) Unit opening position (Refrigerant tubing • drain hose • power inlet port • remote controller wiring inlet port)  
Rear outlet port  
Inter-unit control wiring  
(ø1-3/16", knock-out, use rubber grommet)  
10-5/16  
4-59/64  
2-53/64  
Right-side drain  
hose outlet port  
Left-side drain hose  
outlet port  
Outside air intake duct connection port  
*1  
3-15/16", knock-out)  
Power supply outlet  
(ø1-3/16", knock-out)  
Rear tubing hole  
Left-side drain  
hose outlet port  
3-5/16  
Side panel  
Position of plate  
inside side panel  
13-21/32  
*1  
Unit: in.  
Side panel  
*1 Use a compass saw, jig saw or similar tool and cut along the indented portion of the side panel.  
Fig. 3-89  
47  
(4) Wall and ceiling side opening position  
Figure shows view from front  
Figure shows view from top  
Wall  
Ceiling  
ø3-15/16 ceiling opening  
ø3-15/16 wall side opening  
3-35/64  
5-5/16  
ø3-15/16 wall side opening  
(for left-side drain hose)  
ø3-15/16 ceiling opening  
4-59/64  
Unit: in.  
* If the optional drain up kit is installed, create a ø3-15/16" hole along the dotted line (part marked with * in figure).  
Fig. 3-90  
3-25. Suspending the Indoor Unit  
Ceiling  
(1) Place the full-scale diagram (supplied) on the ceiling  
at the spot where you want to install the indoor unit.  
Wall  
Full-scale  
installation diagram  
Use a pencil to mark the drill holes. (Fig. 3-91).  
NOTE  
Fig. 3-91  
Since the diagram is made of paper, it may shrink or  
stretch slightly because of high temperature or humidity.  
For this reason, before drilling the holes maintain the  
correct dimensions between the markings.  
Hole-in-anchor  
Hole-in-plug  
Concrete  
Insert  
T
(2) Drill holes at the 4 points indicated on the full-scale  
diagram.  
(3) Depending on the ceiling type:  
Suspension bolt (M10 or 3/8")  
(field supply)  
a) Insert suspension bolts as shown in Fig. 3-92.  
or  
Fig. 3-92  
b) Use existing ceiling supports or construct a  
suitable support as shown in Fig. 3-93.  
Ceiling tiles  
Ceiling support  
It is important that you use  
WARNING  
extreme care in supporting the  
indoor unit from the ceiling.  
Ensure that the ceiling is  
strong enough to support the  
weight of the unit. Before  
hanging the ceiling unit, test  
the strength of each attached  
suspension bolt.  
A
A
Fig. 3-93  
Pull out the  
air-intake grille  
pushing claws  
of the hinges  
(4) Screw in the suspension bolts, allowing them to  
protrude from the ceiling as shown in Figs. 3-92  
and 3-93. The distance of each exposed bolt must  
be of equal length within 1-15/16". (Fig. 3-94)  
Hinge  
Screw  
Latch  
unit  
Ceiling  
surface  
Air-intake grille  
Fixture  
Fig. 3-94  
Fig. 3-95  
48  
(5) Before suspending the indoor unit, remove the 2 or 3 screws on the  
latch of the air-intake grilles, open the grilles, and remove them by  
pushing the claws of the hinges as shown in Fig. 3-95. Then remove  
both side panels sliding them along the unit toward the front after  
removing the 2 attachment screws. (Fig. 3-96)  
Slide toward  
front side  
(6) Carry out the preparation for suspending the indoor unit. The  
suspension method varies depending on whether there is a suspended  
ceiling or not. (Figs. 3-97 and 3-98)  
Side panel  
(7) Suspend the indoor unit as follows:  
Fig. 3-96  
a) Mount 1 washer and 2 hexagonal nuts on each suspension bolt as  
shown in Fig. 3-99.  
b) Lift the indoor unit, and place it on the washers through the notches,  
in order to fix it in place. (Fig. 3-100)  
c) Tighten the 2 hexagonal nuts on each suspension bolt to suspend  
the indoor unit as shown in Fig. 3-101.  
Suspension bolt  
(field supply)  
Unit  
Ceiling surface  
Washer (supplied)  
Double nut  
(field supply)  
Fixture  
NOTE  
Fig. 3-97  
The ceiling surface is not always level. Please confirm that the indoor unit  
is evenly suspended. For the installation to be correct, leave a clearance of  
about 3/8" between the ceiling panel and the ceiling surface and fill the gap  
with an appropriate insulation or filler material.  
Suspension bolt  
(field supply)  
Washer (field supply)  
Unit  
(8) If the tubing and wiring are to go towards the rear of the unit, make  
holes in the wall. (Fig. 3-102)  
T
Washer (supplied)  
Double nut  
(field supply)  
(9) Measure the thickness of the wall from the inside to the outside and cut  
PVC pipe at a slight angle to fit. Insert the PVC pipe in the wall.  
(Fig. 3-103)  
Fig. 3-98  
Ceiling  
surface  
Washer  
(supplied)  
Nut  
(field supply)  
Suspension bolt  
Fig. 3-99  
Fig. 3-100  
NOTE  
Fig. 3-101  
The hole should be made at a slight downward slant to  
the outside.  
PVC pipe (locally purchased)  
INSIDE  
OUTSIDE  
Wall  
Indoor  
side  
Outdoor  
side  
PVC pipe  
Slight  
angle  
Cut at slight angle  
Fig. 3-102  
Fig. 3-103  
49  
3-26. Duct for Fresh Air  
Rear outlet port  
There is a duct connection port (knock-out hole) at the right-  
rear of the top panel of the indoor unit for drawing in fresh air.  
If it is necessary to draw in fresh air, remove the cover by  
opening the hole and connecting the duct to the indoor unit  
through the connection port. (Fig. 3-104)  
Inter-unit control wiring  
(ø1-3/16", knock-out, use rubber grommet)  
Outside air intake duct connection port  
3-15/16", knock-out)  
Power supply outlet  
(ø1-3/16", knock-out)  
3-27. Shaping the Tubing  
Rear tubing hole  
G The positions of the refrigerant tubing connections are  
shown in the figure below. (The tubing can be routed in  
3 directions.)  
Left-side drain hose outlet port  
Fig. 3-104  
* When routing the tubing out through the top or right sides,  
knock out the appropriate parts in the top panel and cut  
notches in the side panel as shown in Fig. 3-89.  
* When routing the tubing out through the top, the optional  
L-shape tubing kit is required.  
If the tubing is to be routed out  
together, use a box cutter or simi-  
lar tool to cut out the part of the  
rear cover indicated by the marked  
area in the figure below, to match  
the positions of the tubes. Then  
draw out the tubing.  
T
Rear cover  
Fig. 3-106  
Fig. 3-105  
3-28. Installing the Drain Piping  
G Prepare standard PVC pipe for the drain and connect it to the  
indoor unit drain pipe with the supplied hose clamps to prevent  
water leaks.  
Donward gradient  
Min. 1/100  
(1) Drain hose connection  
G The drain hose is connected below the refrigerant tubing.  
Good  
(2) Installing the drain hose  
G To install the drain hose, first place 1 of the 2 hose bands over the  
unit drain port and the other hose band over the hard PVC pipe  
(not supplied). Then connect both ends of the supplied drain hose.  
G On the unit drain side, grasp the hose band with pliers and insert  
the drain hose all the way to the base.  
Not good  
G If other commercially available hose bands are used, the drain  
hose may become pinched or wrinkled and there is danger of  
water leakage. Therefore be sure to use the supplied hose bands.  
When sliding the hose bands, be careful to avoid scratching the  
drain hose.  
Fig. 3-107  
CAUTION  
G Do not use adhesive when connecting the supplied drain hose to  
the drain port (either on the main unit or the PVC pipe).  
G Wrap the hose with the supplied drain hose insulation and use the  
4 twist ties so that the hose is insulated with no gaps.  
G Connect the drain piping so that it slopes downward from the unit  
to the outside. (Fig. 3-107)  
G Attach so that the hose band fastener is  
on the side of the drain port. (Fig. 3-108)  
G Attach the hose bands so that each is  
approximately 13/64 – 63/64 in. from the  
end of the supplied drain hose.  
50  
Twist tie  
(4 ties, supplied)  
G Never allow traps to occur in the course of the piping.  
G Insulate any piping inside the room to prevent drip-  
ping.  
Hard PVC pipe  
(equivalent to  
VP-20)  
Drain hose  
insulation  
(supplied)  
Position to  
fasten hose  
bands  
Unit drain port  
(Field supply)  
G After the drain piping, pour water into the drain pan to  
check that the water drains smoothly.  
G If the drain hose is to be raised, use the optional drain  
up kit.  
The drain hose can be raised 23-5/8" above the top of  
the main unit. (For details, refer to the manual of the  
Drain hose  
(supplied)  
13/64  
63/64  
13/64  
63/64  
optional part.)  
Drain port  
5-33/64  
Hose band  
(2 bands, supplied)  
Screwdriver  
* If the drain hose is  
routed through the  
left side, refer to Fig.  
3-105, and follow the  
procedure above to  
Unit drain pan  
Unit: in.  
Fig. 3-108  
Rubber stopper  
Check local electrical codes  
and regulations before wiring.  
Also, check any specified  
instruction or limitations.  
CAUTION  
install the hose. Re-attach the rubber stopper that  
was earlier removed onto the right side.  
The rubber stopper can be inserted easily by using a  
screwdriver or similar tool to press the stopper into  
the drain port on the main unit. Press the stopper into  
the main unit drain port as far as it will go.  
T
How to carry out power supply wiring  
(1) Wiring connection ports  
(2) How to carry out wiring  
The power inlet ports are located at the rear and top.  
The remote controller wiring inlet ports are located at  
the rear and top (for use with the wired remote  
controller).  
For details, refer to Fig. 3-104. For the method used to  
insert the wiring, refer to the figure below. (Fig. 3-109)  
G Open the knock-out hole on the rear or top of the  
main unit. Attach the supplied rubber grommet and  
pull the power wiring into the main unit.  
G Feed the wiring into the wiring inlet port on the  
electrical component box. Connect the wiring to  
the terminal plate and fasten in place with the  
supplied clamp.  
G Perform electrical and grounding work in  
accordance with the package A/C power  
specifications, and following local electrical  
codes and regulations.  
When removing the fastening  
CAUTION  
bracket from the cover of the  
electrical component box, use  
caution to avoid dropping the  
bracket.  
Inter-unit control wiring  
ø1-9/32 knock-out  
Eyelet (supplied)  
Powe supply outlet  
Fig. 3-109  
51  
I Wall-Mounted Type (K Type)  
3-29. Removing the Rear Panel from the Unit  
(1) Remove the set screws used to fasten the rear panel to the  
indoor unit during transportation.  
Screws used during  
transportation  
(2) Press up on the frame at the 2 locations shown by the arrows  
in the figure at right, and remove the rear panel.  
Press  
NOTE  
Remove the rear panel  
Tubing can be extended in 4 directions as shown in Fig. 3-111.  
Select the direction which will provide the shortest run to the  
outdoor unit.  
Fig. 3-110  
Left-rear tubing  
3-30. Selecting and Making a Hole  
Right-rear  
tubing  
(recommended)  
Left tubing  
(1) Remove the rear panel from the indoor unit and place it on  
the wall at the location selected. Fix the rear panel and hook  
the unit onto it temporarily. Make sure the unit is horizontal  
using a carpenter’s level or tape measure to measure down  
from the ceiling.  
Right tubing  
(2) Determine which notch of the rear panel should be used.  
(Fig. 3-112)  
Fig. 3-111  
(3) Before drilling a hole, check that there are no studs or pipes  
behind the determined location. The above precautions are  
also applicable if tubing goes through the wall in any other  
location.  
Center of left rear  
tubing hole  
Center of right rear  
tubing hole  
(4) Using a sabre saw, key hole saw or hole-cutting drill attach-  
ment, make a hole (dia. 3-5/32") in the wall. (Fig. 3-113)  
K
Tubing hole diameter ø3-5/32  
(5) Measure the thickness of the wall from the inside edge to the  
outside edge and cut the PVC pipe at a slight angle  
Fig. 3-112  
15/64" shorter than the thickness of the wall. (Fig. 3-114)  
Indoor  
side  
Outdoor  
side  
(6) Place the plastic cover over the end of the pipe (for indoor  
side only) and insert in the wall. (Fig. 3-115)  
NOTE  
The hole should be made at a slight downward gradient to the  
outside.  
Fig. 3-113  
PVC pipe (locally purchased)  
Avoid areas where electrical wiring or  
conduits are located.  
CAUTION  
3-31. Installing the Rear Panel onto the Wall  
Confirm that the wall is strong enough to support the unit.  
See either Item a) or b) below depending on the wall type.  
Cut at slight angle  
a) If the Wall is Wooden  
Fig. 3-114  
(1) Attach the rear panel to the wall with the 10 screws provided. (Fig. 3-116)  
If you are not able to line up the holes in  
INSIDE  
OUTSIDE  
Wall  
the rear panel with the beam locations  
marked on the wall, use Rawl plugs or  
toggle bolts to go through the holes on  
the panel or drill 3/16" dia. holes in the  
panel over the stud locations and then  
mount the rear panel.  
Plastic  
cover  
PVC pipe  
Slight  
angle  
Fig. 3-116  
Fig. 3-115  
52  
(2) Check with a tape measure or carpenter’s level. This is  
important so that the unit is correctly installed. (Fig. 3-117)  
(3) Make sure the panel is flush against the wall. Any space  
between the wall and unit will cause noise and vibration.  
Fig. 3-117  
b) If the Wall is Brick, Concrete or Similar  
Drill 3/16" dia. holes in the wall. Insert Rawl plugs for  
appropriate mounting screws. (Fig. 3-118)  
3/16"  
dia. hole  
3-32. Removing the Grille to Install the Indoor Unit  
In principle, with this model wiring can be completed without  
removing the grille.  
Rawl plug  
However, if it is necessary to change the settings on the PCB,  
follow the procedure below.  
Fig. 3-118  
Removing the grille  
(1) Lift up on both sides of the air-intake grille to open it.  
(Fig. 3-119)  
Intake grille  
(2) Remove the filter. (Fig. 3-119)  
(3) Adjust the flap so that it is horizontal. (Fig. 3-120)  
(4) Open the installation screw covers below the grille  
(3 locations). (Fig. 3-120)  
Filter  
Flap  
(5) Remove the screws. (Fig. 3-120)  
(6) Remove the grille. (Fig. 3-121)  
Attaching the grille  
Open the grille  
Fig. 3-119  
K
(1) Close the flap.  
(2) Keep the grille installation tabs aligned with the top portion of  
the grille, and reinstall the lower portion of the grille.  
Fit the installation tabs into the grooves and press the lower  
portion of the grille back into its original position to install it.  
Installation screw cover  
(3) Press on the installation tabs to completely close the grille.  
Check that the grille and frame are fitted tightly together.  
Fig. 3-120  
3-33. Preparing the Tubing  
(1) Arrangement of tubing by directions  
a) Right or left tubing  
The corner of the right or left frame should be cut with a  
hack saw or similar. (Fig. 3-122)  
Remove the grille  
b) Right-rear or left-rear tubing  
Fig. 3-121  
In this case, the corners of the frame do not need to be  
cut.  
Installation tabs  
(2) Be sure to insulate the part of the drain hose that is  
run indoors, and the refrigerant tubing.  
Frame  
If these are not insulated, condensation may result in  
dripping and damage to walls and furniture.  
The flare nuts on the 24-type (only) are large;  
therefore, use the supplied insulation material.  
Right tubing  
outlet  
Installation tabs  
When left and right side tubing  
Fig. 3-122  
Fig. 3-123  
53  
(3) To mount the indoor unit on the rear panel.  
1. When installing the indoor unit, position the indoor unit onto the  
installation tabs on the upper part of the rear panel. (Fig. 3-123)  
2. Press on the air outlet to hold it in place, and press the lower  
part of the indoor unit until a “click” sound is heard and the  
indoor unit is securely fastened to the installation tabs on the  
lower side of the rear panel. (Fig. 3-124)  
Press  
Raising the clamp to lift up the indoor unit will facilitate this work.  
(Fig. 3-125)  
Fig. 3-124  
Clamp  
To remove the indoor unit, press up on the 2 locations  
(L marks) on the lower part of the unit frame to disconnect the  
installation tabs. Refer to Section 3-1. “Removing the Rear Panel  
from the Unit” (Fig. 3-110).  
Then lift up the indoor unit to remove it.  
3-34. Shaping the Tubing  
Right-rear tubing  
Fig. 3-125  
Rear panel tab  
(1) Shape the refrigerant tubing so that it can easily go into the hole.  
(Fig. 3-126)  
Insulating  
tape  
Refrigerant  
tubing  
(2) After performing a leak test, wrap both the refrigerant tubing and  
drain hose together with insulating tape.  
The drain hose should be positioned below the refrigerant tubes,  
and should be given sufficient space so that no strong tension is  
applied to it.  
Indoor and  
outdoor unit  
connection wiring  
Plastic cover  
(3) Push the wiring, refrigerant tubing and drain hose through the hole  
in the wall. Adjust the indoor unit so it is securely seated on the  
rear panel.  
K
Fig. 3-126  
Fig. 3-127  
Left or left-rear tubing  
(1) Pass the tubing and drain hose into the rear of the indoor unit.  
Provide sufficient length for the connections to be made.  
Next, bend the tubing with a pipe bender, and connect them.  
Insulation  
(2) After performing a leak test, wrap the refrigerant tubing and drain  
hose together with insulating tape, as shown in the figure at right.  
(Fig. 3-128)  
Refrigerant tubing  
Then fit the tubing into the tubing storage space in the rear of the  
indoor unit and clamp in place.  
Rear panel  
Insulating tape  
(3) Adjust the indoor unit so that it is securely installed onto the rear  
panel.  
Inter-unit wiring  
Drain hose  
3-35. Installing the Drain Hose  
Fig. 3-128  
a) The drain hose should be slanted downward to the  
outside. (Fig. 3-129)  
Indoor unit  
b) Never form a trap in the course of the hose.  
c) If the drain hose will run in the room, insulate the hose* so that  
chilled condensation will not damage furniture or floors.  
* Foamed polyethylene or its equivalent is recommended.  
Slant  
Do not supply power to the unit or operate  
it until all tubing and wiring to the outdoor  
unit are completed.  
WARNING  
Refrigerant  
tubing  
Fig. 3-129  
54  
3-36. When Using Wireless Remote Controller Instead Of Wired Remote Controller  
When the wireless remote controller is to be used, slide the switch on the indoor unit control PCB.  
• If this setting is not made, an alarm will occur. (The operation lamp on the display blinks.)  
• This setting is not necessary if both the wired remote controller and wireless remote controller are used.  
• The location of the switch varies depending on the type of PCB used. Check the model name before making the  
setting.  
KHX0752 / 0952 / 1252 / 1852  
CR-KR74GXH56A-0  
Slide No. 3 on SW101  
Setting at time of  
from ON OFF.  
factory shipment  
K
KHX2452  
CR-KR254GXH56A-0  
Slide No. 3 on SW101  
Setting at time of  
from ON OFF.  
factory shipment  
55  
4. HOW TO INSTALL THE OUTDOOR UNIT  
4-1. Installing the Outdoor Unit  
G Use concrete or a similar material to create the base, and  
ensure good drainage.  
G Ordinarily, ensure a base height of 2 in. or more. If a drain  
pipe is used, or for use in cold-weather regions, ensure a  
height of 6 in. or more at the feet on both sides of the unit.  
(In this case, leave clearance below the unit for the drain  
pipe, and to prevent freezing of drainage water in  
cold-weather regions.)  
Drain port (2 locations)  
6-47/64 25-63/64  
4-3/8  
G Refer to the Fig. 4-1 for the anchor bolt dimensions.  
8-5/8  
5-29/32  
G Be sure to anchor the feet with the anchor bolts (M10 or  
3/8"). In addition, use anchoring washers on the top side.  
(Use large square 1-1/4" × 1-1/4" SUS washers with  
diameters of 3/8".) (Field supply)  
33/64  
33/64  
33/64  
33/64  
4-2. Drainage Work  
37  
Follow the procedure below to ensure adequate draining for  
the outdoor unit.  
G For the drain port dimensions, refer to the figure at right.  
G Ensure a base height of 6 in. or more at the feet on both  
sides of the unit.  
4-3. Routing the Tubing and Wiring  
G The tubing and wiring can be extended out in 4 directions:  
front, rear, right, and down.  
G The service valves are housed inside the unit. To access  
them, remove the inspection panel. (To remove the  
inspection panel, remove the 3 screws, then slide the  
panel downward and pull it toward you.)  
Anchor bolt (M10 or 3/8")  
Unit: in.  
Drain port  
Fig. 4-1  
(1) If the routing direction is through the front, rear, or right,  
use a nipper or similar tool to cut out the knockout holes for  
the inter-unit control wiring outlet, power wiring outlet, and  
tubing outlet from the appropriate covers A and B.  
Inter-unit control wiring  
(2) If the routing direction is down, use a nipper or similar tool to  
cut out the lower flange from cover A.  
Inspection panel  
Rear  
G Route the tubing so that it does  
CAUTION  
Cover B  
Cover A  
not contact the compressor,  
panel, or other parts inside the  
unit. Increased noise will result if  
the tubing contacts these parts.  
Front  
Right  
Power supply  
Down  
G When routing the tubing, use a  
Tubing outlet  
tube bender to bend the tubes.  
Fig. 4-2  
56  
5. ELECTRICAL WIRING  
5-1. General Precautions on Wiring  
(1) Before wiring, confirm the rated voltage of the unit  
as shown on its nameplate, then carry out the  
wiring closely following the wiring diagram.  
(7) Regulations on wire diameters differ from locality  
to locality. For field wiring rules, please refer to  
your LOCAL ELECTRICAL CODES before begin-  
ning.  
(2) Provide a power outlet to be used exclusively for  
each unit, and a power supply disconnect and  
circuit breaker for overcurrent protection should be  
provided in the exclusive line.  
You must ensure that installation complies with all  
relevant rules and regulations.  
(8) To prevent malfunction of the air conditioner  
caused by electrical noise, care must be taken  
when wiring as follows:  
(3) To prevent possible hazards from insulation  
failure, the unit must be grounded.  
(4) Each wiring connection must be done in accor-  
dance with the wiring system diagram. Wrong  
wiring may cause the unit to misoperate or  
become damaged.  
G The remote control wiring and the inter-unit control  
wiring should be wired apart from the inter-unit  
power wiring.  
G Use shielded wires for inter-unit control wiring  
(5) Do not allow wiring to touch the refrigerant tubing,  
compressor, or any moving parts of the fan.  
between units and ground the shield on both sides.  
(9) If the power supply cord of this appliance is dam-  
aged, it must be replaced by a repair shop  
appointed by the manufacturer, because special  
purpose tools are required.  
(6) Unauthorized changes in the internal wiring can be  
very dangerous. The manufacturer will accept no  
responsibility for any damage or misoperation that  
occurs as a result of such unauthorized changes.  
5-2. Recommended Wire Length and Wire Diameter for Power Supply System  
Outdoor unit  
Time delay fuse or  
circuit capacity  
Type  
(A) Power supply wiring  
CHX03652  
30 A  
For field wiring rules, please refer  
to your LOCAL ELECTRICAL CODES  
CHX06052  
50 A  
Indoor unit  
Time delay fuse or  
circuit capacity  
Type  
(B) Power supply wiring  
K
A, X, T, U  
D
15 A  
15 A  
15 A  
For field wiring rules, please refer  
to your LOCAL ELECTRICAL CODES  
Control wiring  
(C) Inter-unit (between outdoor and  
(D) Remote control wiring  
(E) Control wiring for group control  
indoor units) control wiring  
AWG #18 (0.75 mm2)  
AWG #18 (0.75 mm2)  
AWG #18 (0.75 mm2)  
Use shielded wiring*  
Use shielded wiring  
Use shielded wiring  
Max. 3,280 ft.  
Max. 1,640 ft.  
Max. 1,640 ft. (Total)  
NOTE  
* With ring-type wire terminal.  
57  
5-3. Wiring System Diagram  
Indoor  
Outdoor unit  
unit (No. 1)  
INV unit  
L1  
L2  
Power supply  
208 / 230 V, 1ø, ~60Hz  
A
L1  
L2  
L1  
L2  
L1  
L2  
Power supply  
208 / 230 V, 1ø, ~60Hz  
C
Ground  
B
Ground  
U1  
U2  
U1  
U2  
Remote  
controller  
WHT  
BLK  
D
Ground  
R1  
R2  
1
1
2
2
Ground  
C
Indoor  
unit (No. 2)  
L1  
L2  
Power supply  
208 / 230 V, 1ø, ~60Hz  
L1  
L2  
Ground  
B
U1  
U2  
Remote  
controller  
D
R1  
R2  
1
1
2
WHT  
BLK  
2
Ground  
C
Indoor  
unit (No. 3)  
Group control:  
L1  
L2  
Power supply  
208 / 230 V, 1ø, ~60Hz  
L1  
L2  
Ground  
B
U1  
U2  
E
R1  
R2  
Ground  
C
Indoor  
unit (No. n)  
L1  
L2  
Power supply  
208 / 230 V, 1ø, ~60Hz  
L1  
L2  
Ground  
B
U1  
U2  
Remote  
controller  
D
R1  
R2  
1
1
2
WHT  
BLK  
2
7P terminal board  
Ground  
NOTE  
(1) Refer to Section 5-2. “Recommended Wire Length  
and Wire Diameter for Power Supply System” for  
the explanation of “A,B,” “C,” “D,” and “E,” in the  
above diagram.  
1(L1) 2(L2)  
U1 U2 R1 R2  
Remote  
(2) The basic connection diagram of the indoor unit  
shows the 7P terminal board, so the terminal  
boards in your equipment may differ from the  
diagram.  
Power  
Inter-unit  
control wiring controller  
supply  
X, A, U, D, T Type  
(3) Refrigerant Circuit (R.C.) address should be set  
before turning the power on.  
5P terminal board  
(4) Regarding the R.C. address setting, refer to page  
72. Auto. address setting can be executed by  
remote controller automatically.  
1
2
3
4
5
1(L1)2(L2)  
Power  
supply control wiring  
U1 U2  
Inter-unit  
Refer to page 72 – 76.  
K Type  
58  
CAUTION  
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the  
short plug (CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor  
units except any one of the outdoor units.  
(When shipping: In shorted condition.)  
Otherwise the communication of S-net link system is not performed. For a system without link (no  
connection wiring between outdoor units), do not remove the short plug.  
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-1)  
Outdoor unit  
Outdoor unit  
Outdoor unit  
Prohibited  
Prohibited  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
Fig. 5-1  
(3) Do not install inter-unit control wiring such as star  
branch wiring. Star branch wiring causes mis-address  
setting.  
Outdoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
NO  
Outdoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
NO  
Branch point  
Fig. 5-2  
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.  
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 5-3)  
Outdoor unit  
Outdoor unit  
Outdoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
more than 3.3 ft.  
Branch  
point  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
16 or fewer  
more than 3.3 ft.  
Indoor unit  
more than 3.3 ft.  
Indoor unit  
Fig. 5-3  
59  
(5) Use shielded wires for inter-unit control wiring (c)  
and ground the shield on both sides, otherwise  
misoperation from noise may occur. (Fig. 5-4)  
Connect wiring as shown in Section “5-3. Wiring  
System Diagram.”  
Shielded wire  
Loose wiring may cause  
Ground  
Ground  
WARNING  
the terminal to overheat or  
result in unit malfunction.  
A fire hazard may also  
exist. Therefore, ensure  
that all wiring is tightly  
connected.  
Fig. 5-4  
When connecting each power wire to the terminal, follow  
the instructions on “How to connect wiring to the terminal”  
and fasten the wire securely with the fixing screw of the  
terminal plate.  
How to connect wiring to the terminal  
Stranded wire  
I For stranded wiring  
(1) Cut the wire end with cutting pliers, then strip the  
insulation to expose the stranded wiring about 3/8 in.  
and tightly twist the wire ends. (Fig. 5-5)  
Ring  
pressure  
terminal  
(2) Using a Phillips head screwdriver, remove the terminal  
screw(s) on the terminal plate.  
(3) Using a ring connector fastener or pliers, securely  
clamp each stripped wire end with a ring pressure  
terminal.  
Fig. 5-5  
(4) Place the ring pressure terminal, and replace and  
tighten the removed terminal screw using a  
screwdriver. (Fig. 5-6)  
Special  
washer  
Screw  
Ring pressure  
terminal  
Screw and  
Special washer  
Terminal plate  
Wire  
Ring  
pressure  
terminal  
Wire  
Fig. 5-6  
60  
6. HOW TO PROCESS TUBING  
Deburring  
After  
Before  
6-1. Connecting the Refrigerant Tubing  
Use of the Flaring Method  
Many of conventional split system air conditioners  
employ the flaring method to connect refrigerant tubes  
which run between indoor and outdoor units. In this  
method, the copper tubes are flared at each end and  
connected with flare nuts.  
Flaring Procedure with a Flare Tool  
(1) Cut the copper tube to the required length with a  
tube cutter. It is recommended to cut approx. 1 –  
2 ft. longer than the tubing length you estimate.  
Fig. 6-1  
(2) Remove burrs at the end of the copper tube with a  
tube reamer or file. This process is important and  
should be done carefully to make a good flare.  
(Fig. 6-1)  
Copper  
tubing  
Reamer  
NOTE  
When reaming, hold the tube end downward and be  
sure that no copper scraps fall into the tube. (Fig. 6-2)  
Fig. 6-2  
(3) Remove the flare nut from the unit and be sure to  
mount it on the copper tube.  
(4) Make a flare at the end of copper tube with a flare  
tool.* (Fig. 6-3)  
(*Use “RIGID®” or equivalent.)  
Flare nut  
Copper  
tubing  
NOTE  
A good flare should have the following characteristics:  
G inside surface is glossy and smooth  
G edge is smooth  
Flare tool  
Fig. 6-3  
G tapered sides are of uniform length  
61  
Caution Before Connecting Tubes Tightly  
(1) Apply a sealing cap or water-proof tape to prevent dust or  
water from entering the tubes before they are used.  
Apply refrigerant  
(2) Be sure to apply refrigerant lubricant to the matching  
surfaces of the flare and union before connecting them  
together. This is effective for reducing gas leaks. (Fig. 6-4)  
lubricant here and here  
Fig. 6-4  
(3) For proper connection, align the union tube and flare tube  
straight with each other, then screw in the flare nut lightly  
at first to obtain a smooth match. (Fig. 6-5)  
G Adjust the shape of the liquid tube using a tube bender at  
the installation site and connect it to the liquid tubing side  
valve using a flare.  
Flare nut  
Union  
Cautions During Brazing  
Fig. 6-5  
G Replace air inside the tube with nitrogen gas to  
prevent copper oxide film from forming during the  
brazing process. (Oxygen, carbon dioxide and Freon  
are not acceptable.)  
Torque wrench  
Spanner  
G Do not allow the tubing to get too hot during brazing.  
The nitrogen gas inside the tubing may overheat,  
causing refrigerant system valves to become dam-  
aged. Therefore allow the tubing to cool when brazing.  
Indoor unit  
Outdoor unit  
G Use a reducing valve for the nitrogen cylinder.  
Fig. 6-6  
G Do not use agents intended to prevent the formation  
of oxide film. These agents adversely affect the  
refrigerant and refrigerant oil, and may cause damage  
or malfunctions.  
Tightening torque,  
approximate  
Tube thickness  
Tube diameter  
ø1/4"  
(ø6.35 mm)  
120 – 160 lbs in.  
1/32"  
(0.8 mm)  
·
·
(140 – 180 kgf cm)  
6-2. Connecting Tubing Between Indoor and Outdoor  
Units  
ø3/8"  
(ø9.52 mm)  
1/32"  
(0.8 mm)  
300 – 360 lbs in.  
·
(340 – 420 kgf cm)  
·
ø1/2"  
(ø12.7 mm)  
1/32"  
(0.8 mm)  
430 – 530 lbs in.  
·
(1) Tightly connect the indoor-side refrigerant tubing extended  
from the wall with the outdoor-side tubing.  
(490 – 610 kgf cm)  
·
ø5/8"  
(ø15.88 mm)  
5/128"  
(1.0 mm)  
590 – 710 lbs in.  
·
·
(2) To fasten the flare nuts, apply specified torque as at right:  
(680 – 820 kgf cm)  
ø3/4"  
(ø19.05 mm)  
over 5/128"  
(1.0 mm)  
870 – 1040 lbs in.  
·
G When removing the flare nuts from the tubing connections,  
or when tightening them after connecting the tubing, be  
sure to use 2 monkey wrenches or spanners as shown.  
(Fig. 6-6)  
(1000 – 1200 kgf cm)  
·
Because the pressure is approximately 1.6 times  
higher than conventional refrigerant pressure, the  
use of ordinary flare nuts (type 1) or thin-walled  
tubes may result in tube rupture, injury, or  
If the flare nuts are over-tightened, the flare may be dam-  
aged, which could result refrigerant leakage and cause in  
injury or asphyxiation to room occupants.  
G For the flare nuts at tubing connections, be sure to use the  
flare nuts that were supplied with the unit, or else flare nuts  
for R410A (type 2). The refrigerant tubing that is used must  
be of the correct wall thickness as shown in the table at  
right.  
asphyxiation caused by refrigerant leakage.  
G In order to prevent damage to the flare caused by  
over-tightening of the flare nuts, use the table  
above as a guide when tightening.  
G When tightening the flare nut on the liquid tube,  
use a monkey wrench with a nominal handle length  
of 7-7/8 in.  
62  
6-3. Insulating the Refrigerant Tubing  
Tubing Insulation  
Two tubes arranged together  
Liquid tubing  
Gas tubing  
G Thermal insulation must be applied to all unit tubing,  
including distribution joint (purchased separately).  
* For gas tubing, the insulation material must be heat  
resistant to 248°F or above. For other tubing, it must  
be heat resistant to 176°F or above.  
Insulation  
Fig. 6-7  
Insulation material thickness must be 25/64" or greater.  
If the conditions inside the ceiling exceed DB 86°F and  
RH 70%, increase the thickness of the gas tubing  
insulation material by 1 step.  
Taping the flare nuts  
If the exterior of the outdoor  
CAUTION  
unit valves has been finished  
with a square duct covering,  
make sure you allow sufficient  
space to use the valves and to  
allow the panels to be  
attached and removed.  
Sealer (supplied)  
Insulation tape (white)  
(supplied)  
Wind the white insulation tape around the flare nuts at the  
gas tube connections. Then cover up the tubing  
connections with the flare insulator, and fill the gap at the  
union with the supplied black insulation tape. Finally,  
fasten the insulator at both ends with the supplied vinyl  
clamps. (Fig. 6-8)  
Flare insulator (supplied)  
Tube insulator  
(not supplied)  
Heat resistant  
248°F or above  
Unit side  
insulator  
Flare nut  
Vinyl clamps (supplied)  
Insulation material  
Fig. 6-8  
The material used for insulation must have good insulation  
characteristics, be easy to use, be age resistant, and must  
not easily absorb moisture.  
Refrigerant tubing and insulator  
(not supplied)  
Drain insulator  
and clamp.  
Large  
Drain pipe and insulator  
(not supplied)  
After a tube has been  
(supplied)  
CAUTION  
insulated, never try to bend it  
into a narrow curve because it  
can cause the tube to break or  
crack.  
Packing  
clamp.  
Small  
hose band  
(supplied)  
Insulation  
tape  
Vinyl  
Flare  
clamp  
insulator  
Seal  
The procedure used for  
installing the insulator for  
both gas and liquid  
tubes is the same.  
Fig. 6-9  
Never grasp the drain or refrigerant connecting  
outlets when moving the unit.  
63  
6-4. Taping the Tubes  
(1) At this time, the refrigerant tubes (and electrical  
wiring if local codes permit) should be taped  
together with armoring tape in 1 bundle. To prevent  
the condensation from overflowing the drain pan,  
keep the drain hose separate from the refrigerant  
tubing.  
Clamp  
(2) Wrap the armoring tape from the bottom of the  
outdoor unit to the top of the tubing where it enters  
the wall. As you wrap the tubing, overlap half of  
each previous tape turn.  
Drain hose  
Insulated tubes  
(3) Clamp the tubing bundle to the wall, using 1 clamp  
approx. each ft. (Fig. 6-10)  
NOTE  
Fig. 6-10  
Do not wind the armoring tape too tightly since this will  
decrease the heat insulation effect. Also ensure that  
the condensation drain hose splits away from the  
bundle and drips clear of the unit and the tubing.  
Apply putty here  
6-5. Finishing the Installation  
After finishing insulating and taping over the tubing, use  
sealing putty to seal off the hole in the wall to prevent  
rain and draft from entering. (Fig. 6-11)  
Tubing  
Fig. 6-11  
64  
7. AIR PURGING  
Manifold gauge  
Air and moisture in the refrigerant system may have  
undesirable effects as indicated below.  
G pressure in the system rises  
G operating current rises  
G cooling (or heating) efficiency drops  
G moisture in the refrigerant circuit may freeze and block  
capillary tubing  
G water may lead to corrosion of parts in the refrigerant  
system  
Fig. 7-1  
Therefore, the indoor unit and tubing between the indoor  
and outdoor unit must be leak tested and evacuated to  
remove any noncondensables and moisture from the  
system.  
Vacuum pump  
Outlet  
Inlet  
I Air Purging with a Vacuum Pump (for Test Run)  
Preparation  
Check that each tube (both liquid and gas tubes) between  
the indoor and outdoor units has been properly connected  
and all wiring for the test run has been completed. Remove  
the valve caps from both the gas tube and liquid tube  
service valves on the outdoor unit. Note that both liquid and  
gas tube service valves on the outdoor unit are kept closed  
at this stage.  
Fig. 7-2  
Manifold valve  
Pressure  
gauge  
Lo  
Hi  
Leak test  
Charge hose  
(1) Attach a manifold valve (with pressure gauges) and dry  
nitrogen gas cylinder to this service port with charge  
hoses.  
Cylinder  
valve  
Nitrogen gas cylinder  
(In vertical standing  
position)  
Use a manifold valve for air  
CAUTION  
purging. If it is not available, use  
a stop valve for this purpose. The  
“Hi” knob of the manifold valve  
must always be kept closed.  
Service port ø5/16"  
(2) Pressurize the system to no more than  
512 psig (36 kgf/cm2G) with dry nitrogen gas and close  
the cylinder valve when the gauge reading reaches  
512 psig (36 kgf/cm2G). Then, test for leaks with liquid  
soap.  
Open  
Gas  
tube  
Close  
Outdoor unit  
To avoid nitrogen entering the  
Open  
CAUTION  
refrigerant system in a liquid state,  
the top of the cylinder must be  
higher than the bottom when you  
pressurize the system. Usually,  
the cylinder is used in a vertical  
standing position. (Refer to the  
previous page.)  
Liquid  
tube  
Close  
Fig. 7-3  
65  
(3) Do a leak test of all joints of the tubing (both indoor and  
outdoor) and both gas tube and liquid tube service  
valves. Bubbles indicate a leak. Wipe off the soap with a  
clean cloth after the leak test.  
Manifold valve  
(4) After the system is found to be free of leaks, relieve the  
nitrogen pressure by loosening the charge hose  
connector at the nitrogen cylinder. When the system  
pressure is reduced to normal, disconnect the hose from  
the cylinder.  
Pressure  
gauge  
Lo  
Hi  
Evacuation  
(1) Attach the charge hose end described in the preceding  
steps to the vacuum pump to evacuate the tubing and  
indoor unit. Confirm that the “Lo” knob of the manifold  
valve is open. Then, run the vacuum pump. The  
operation time for evacuation varies with the tubing  
length and capacity of the pump. The following table  
shows the amount of time for evacuation:  
Vacuum pump  
Service port ø5/16"  
Open  
Required time for evacuation  
Gas  
tube  
when 30 gal/h vacuum pump is used  
If tubing length is  
less than 49 ft.  
If tubing length is  
longer than 49 ft.  
90 min. or more  
Close  
Outdoor unit  
45 min. or more  
Open  
NOTE  
Liquid  
tube  
The required time in the above table is calculated based on  
the assumption that the ideal (or target) vacuum condition is  
less than –14.7 psig (–755 mmHg, 5 Torr).  
Close  
Fig. 7-4  
(2) When the desired vacuum is reached, close the “Lo”  
knob of the manifold valve and turn off the vacuum pump.  
Confirm that the gauge pressure is under –14.7 psig  
(–755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum  
pump operation.  
66  
Use a cylinder designed for  
use with R410A respectively.  
CAUTION  
Manifold valve  
Pressure  
gauge  
Lo  
Hi  
Charging additional refrigerant  
G Charging additional refrigerant (calculated from the  
liquid tube length as shown in Section 1-7  
“Additional Refrigerant Charge”) using the liquid  
tube service valve. (Fig. 7-5)  
Valve  
G Use a balance to measure the refrigerant accurately.  
G If the additional refrigerant charge amount cannot  
be charged at once, charge the remaining  
refrigerant in liquid form by using the gas tube  
service valve with the system in cooling operation  
mode at the time of test run. (Fig. 7-6)  
Liquid  
Finishing the job  
R410A  
(1) With a hex wrench, turn the liquid tube service  
valve stem counter-clockwise to fully open the  
valve.  
Close  
Open  
Gas  
(2) Turn the gas tube service valve stem  
counter-clockwise to fully open the valve.  
tube  
Close  
Close  
Outdoor unit  
To avoid gas from leaking when  
CAUTION  
removing the charge hose,  
make sure the stem of the gas  
tube is turned all the way out  
(“BACK SEAT” position).  
Liquid  
tube  
(3) Loosen the charge hose connected to the gas  
tube service port (for ø5/16" tube) slightly to  
release the pressure, then remove the hose.  
Fig. 7-5  
(4) Replace the service port cap on the gas tube  
service port and fasten the cap securely with an  
monkey spanner or box wrench. This process is  
very important to prevent gas from leaking from  
the system.  
Open  
Close  
(5) Replace the valve caps at both gas tube and liquid  
tube service valves and fasten them securely.  
Gas  
tube  
Open  
Open  
This completes air purging with a vacuum pump. The  
air conditioner is now ready for a test run.  
Outdoor unit  
Liquid  
tube  
Fig. 7-6  
67  
8. TEST RUN  
8-1. Preparing for Test Run  
G Before attempting to start the air conditioner,  
check the following.  
ON  
(1) All loose matter is removed from the cabinet,  
especially steel filings, bits of wire, and clips.  
(Power must be turned ON  
at least 5 hours before  
attempting test run)  
(2) The control wiring is correctly connected and all  
electrical connections are tight.  
(3) The transportation pads for the indoor fan have  
been removed. If not, remove them now.  
Power mains switch  
(4) The power has been connected to the unit for at  
least 5 hours before starting the compressor. The  
bottom of the compressor should be warm to the  
touch and the crankcase heater around the feet of  
the compressor should be hot to the touch.  
(Fig. 8-1)  
Fig. 8-1  
(5) Both the gas and liquid tube service valves are  
open. If not, open them now. (Fig. 8-2)  
(6) Request that the customer be present for the trial  
run.  
Explain the contents of the instruction manual, then  
have the customer actually operate the system.  
(7) Be sure to give the instruction manual and  
warranty certificate to the customer.  
(8) When replacing the control PCB, be sure to make  
all the same settings on the new PCB as were in  
use before replacement.  
The existing EEP ROM is not changed, and is  
connected to the new control PCB.  
Gas tube service cap  
Liquid tube service cap  
Fig. 8-2  
68  
8-2. Test Run Procedure  
Items to Check Before the Test Run  
1. Turn the remote power switch on at  
least 5 hours before the test, in order to  
energize the crank case heater.  
2. Turn the outdoor service valves (2  
locations) to the full-open positions.  
G Use caution when making the settings. If  
there are duplicated system addresses,  
or if the settings for the Nos. of the  
Recheck the items to check before the test run.  
indoor units are not consistent, an alarm  
will occur and the system will not start.  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S004)  
Set the No. of indoor units.  
G These settings are not made on the  
indoor unit PCB.  
CASE 1  
Are the inter-unit control wires  
connected to more than 1 refrigerant  
system?  
NO  
(Check the link wiring.)  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S002 and S003)  
YES  
Set the system address.  
When multiple outdoor units exist, disconnect the terminals  
extended from the shorted plugs (CN33) at all outdoor main unit  
PCBs except for 1.  
Refer to Fig. 8-4  
Alternatively, move the sockets to the OPEN side.  
CASE 2  
Is it possible to turn ON the power only  
for the 1 refrigerant system where the  
YES  
test run will be performed?  
Turn ON the indoor and  
outdoor unit power for that  
refrigerant system only.  
NO  
Will automatic address setting be  
performed in Heating mode?  
Make necessary corrections.  
Short-circuit the automatic address pin (CN51)  
on the outdoor unit PCB for 1 second or longer,  
then release it.  
NO  
CASE 3B  
Turn OFF the indoor and  
outdoor unit power  
YES  
CASE 3A  
LED 1 and 2 blink alternately  
(about 2 or 3 minutes).  
Is it OK to start the compressors?  
Is it OK to start the compressors?  
Check the alarm contents.  
Turn ON the indoor and  
outdoor unit power.  
Turn ON the indoor and  
outdoor unit power.  
NO  
Are LEDs 1 and 2 on the  
outdoor unit PCB OFF?  
Make necessary  
corrections  
*2  
*2  
Refer to “Table of  
Short-circuit the mode change pin  
(CN50) on the outdoor main unit PCB.  
At the same time, short-circuit the  
automatic address pin (CN51) for 1  
second or longer, then pull it out.  
Short-circuit the automatic address  
pin (CN51) on the outdoor unit PCB  
for 1 second or longer,  
Self-Diagnostic Functions and  
Description of Alarm Displays.”  
YES  
Turn OFF the indoor  
and outdoor unit  
then release it.  
*3  
*3  
Start indoor and outdoor unit  
cooling operation.  
Start indoor and outdoor unit  
heating operation.  
Check the alarm  
contents.  
LED 1 and 2 blink alternately.  
LED 1 and 2 blink alternately.  
*2 A minimum of 5 hours must have passed after the  
power was turned ON to the outdoor unit.  
*3 All indoor units operate in all refrigerant systems  
where the power is ON.  
NO  
Are LEDs 1 and 2 on the  
outdoor unit PCB OFF?  
YES  
Check that test run preparation is OK.  
(Do not allow the short-circuited pins to remain short-circuited.)  
Set the wired remote controller for test run.  
Refer to the remote  
controller test-run  
settings.  
NO  
Check and make corrections according to  
Table of Self-Diagnostic Functions.”  
Does system operate?  
YES  
Return remote control to normal mode  
End test run.  
Fig. 8-3  
69  
8-3. Outdoor Unit PCB Setting  
CN33  
CN51  
CN50  
S003  
S002  
S004  
D043  
(LED2)  
D042  
(LED1)  
Fig. 8-4  
70  
Examples of the No. of indoor units settings  
Indoor unit setting (S004)  
No. of indoor units  
(Rotary switch, red)  
1 unit (factory setting)  
2 units  
Set to 1  
Set to 2  
9 units  
Set to 9  
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used)  
System address (S003)  
System address (S002)  
System address No.  
(2P DIP switch, blue)  
10 20  
(Rotary switch, black)  
ON  
ON  
Set to 1  
Both OFF  
System 1 (factory setting)  
System 11  
2
2
2
2
1
OFF  
ON  
ON  
1 ON  
Set to 1  
Set to 1  
Set to 0  
1
OFF  
ON  
ON  
System 21  
2 ON  
1
OFF  
ON  
ON  
System 30  
1 & 2 ON  
1
OFF  
71  
8-4. Auto Address Setting  
Basic wiring diagram: Example (1)  
• If link wiring is not used  
(The inter-unit control wires are not connected to multiple refrigerant systems.)  
Indoor unit addresses can be set without operating the compressors.  
No. 1 unit settings  
System address  
(system 1 setting)  
No. of indoor units  
(8 units setting)  
(S004)  
(S003)  
ON  
(S002)  
ON  
8
1
2
OFF  
Unit  
No. 1  
Outdoor Unit  
Inter-unit control wiring  
Indoor Unit  
1-1  
1-2  
1-3  
1-8  
Remote controller  
cross-over wiring  
Remote controller  
Fig. 8-5  
(1) Automatic Address Setting from the Outdoor Unit  
1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the  
ON  
ON  
DIP switch (S003) is set to “0.”  
(These are the settings at the time of factory shipment.)  
1
2
OFF  
2. To set the number of indoor units that are connected to the outdoor unit to 8, on the outdoor unit control PCB set  
the No. of indoor units rotary switch (S004) to “8.”  
3. Turn ON the power to the indoor and outdoor units.  
4. On the outdoor unit control PCB, short-circuit the automatic address pin (CN51) for 1 second or longer, then  
release it.  
(Communication for automatic address setting begins.)  
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.  
The LED that indicates that automatic address setting is in progress turns OFF and the process is  
stopped.  
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)  
5. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 to 3, then use the remote controller and  
complete automatic address setting.  
Refer to “Automatic Address Setting from the Remote Controller.”  
72  
Basic wiring diagram: Example (2)  
If link wiring is used  
*When multiple outdoor units exist, remove the socket that  
is used to short-circuit the terminal plug (CN33) from all  
outdoor unit PCBs except for 1.  
Alternatively, move the sockets to the “OPEN” side.  
No. 1 unit settings  
System address  
(system 1 setting)  
No. of indoor units  
(6 units setting)  
(S004)  
(S003)  
(S002)  
ON  
ON  
1
2
OFF  
Leave the socket  
that is used to  
short-circuit the  
terminal plug.  
(CN33)  
Outdoor unit  
system 1  
Unit  
No. 1  
Inter-unit control wiring  
1-1  
1-2  
1-3  
1-6  
Indoor unit  
Remote controller  
communication wiring  
Remote  
controller  
No. 2 unit settings  
System address  
(system 2 setting)  
No. of indoor units  
(7 units setting)  
(S002) (S003)  
(S004)  
ON  
OFF  
ON  
1
2
Leave the socket  
that is used to open  
circuit the terminal  
plug (CN33).  
Unit  
No. 1  
Outdoor unit  
system 2  
Inter-unit control wiring  
Indoor unit  
2-1  
2-2  
2-7  
To other system  
link wiring  
Remote controller  
cross-over wiring  
Remote  
controller  
Make settings as appropriate for the cases listed below.  
(Refer to the instructions on the following pages.)  
Indoor and outdoor unit power can be turned ON for each system separately.  
Case 1  
Indoor and outdoor unit power cannot be turned ON for each system separately.  
Case 2  
Case 3  
Automatic address setting in Heating mode  
Automatic address setting in Cooling mode  
Fig. 8-6  
73  
Case 1  
Automatic Address Setting (no compressor operation)  
G Indoor and outdoor unit power can be turned ON for each system separately.  
Indoor unit addresses can be set without operating the compressors.  
Automatic Address Setting from Outdoor Unit  
1. On the outdoor unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP  
ON  
ON  
switch (S003) is set to “0.”  
(These are the settings at the time of factory shipment.)  
1
2
OFF  
2. To set the number of indoor units that are connected to the outdoor unit to 6, on the outdoor unit control PCB set the  
No. of indoor units rotary switch (S004) to “6.”  
3. At the outdoor unit where all indoor and outdoor unit power has been turned ON, short-circuit the automatic  
address pin (CN51) for 1 second or longer, then pull it out.  
(Communication for automatic address setting begins.)  
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.  
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.  
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor unit control PCB turn OFF.)  
4. Next turn the power ON only for the indoor and outdoor units of the next (different) system. Repeat steps 1 – 3 in  
the same way to complete automatic address settings for all systems.  
5. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 and 2, then use the remote controller  
complete automatic address setting.  
Refer to “Automatic Address Setting from the Remote Controller.”  
74  
Case 2  
Automatic Address Setting in Heating Mode  
G Indoor and outdoor unit power cannot be turned ON for each system separately.  
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.  
Therefore perform this process only after completing all refrigerant tubing work.  
Automatic Address Setting from Outdoor Unit  
Case 1  
1. Perform steps 1 and 2 in the same way as for  
.
2. Turn the indoor and outdoor unit power ON at all systems.  
Heating mode  
3. To perform automatic address setting in  
, on the outdoor unit control PCB in the refrigerant  
system where you wish to set the addresses, short-circuit the automatic address pin (CN51) for 1 second or  
longer, then pull it out.  
(Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for  
more than one system at the same time.)  
(Communication for automatic address setting begins, the compressors turn ON, and automatic address  
setting in heating mode begins.)  
(All indoor units operate.)  
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.  
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.  
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor unit  
control PCB turn OFF.)  
4. At the outdoor unit in the next (different) system, short-circuit the automatic address pin (CN51) for 1 second or  
longer, then pull it out.  
(Repeat the same steps to complete automatic address setting for all units.)  
5. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 and 2, then use the remote controller  
complete automatic address setting.  
Refer to “Automatic Address Setting from the Remote Controller.”  
75  
Case 3  
Automatic Address Setting in Cooling Mode  
G Indoor and outdoor unit power cannot be turned ON for each system separately.  
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.  
Therefore perform this process only after completing all refrigerant tubing work.  
Automatic address setting can be performed during Cooling operation.  
Automatic Address Setting from Outdoor Unit  
Case 1  
1. Perform steps 1 and 2 in the same way as for  
.
2. Turn the indoor and outdoor unit power ON at all systems.  
Cooling mode  
3. To perform automatic address setting in  
, on the outdoor unit control PCB in the refrigerant system  
where you wish to set the addresses, short-circuit the mode change 2P pin (CN50). At the same time, short-circuit  
the automatic address pin (CN51) for 1 second or longer, then pull it out. (Be sure to perform this process for one  
system at a time. Automatic address settings cannot be performed for more than one system at the same time.)  
(Communication for automatic address setting begins, the compressors turn ON, and automatic address  
setting in Cooling mode begins.)  
(All indoor units operate.)  
* To cancel, again short-circuit the automatic address pin (CN51) for 1 second or longer, then pull it out.  
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.  
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor unit control  
PCB turn OFF.)  
4. At the outdoor unit in the next (different) system, short-circuit the automatic address pin (CN51) for 1 second or  
longer, then pull it out.  
(Repeat the same steps to complete automatic address setting for all units.)  
5. Operation from the remote controllers is now possible.  
* Automatic address setting in Cooling mode cannot be done from the remote controller.  
Automatic Address Setting from the Remote Controller  
Selecting each refrigerant system individually for automatic address setting  
---Automatic address setting for each system: Item code “A1”  
G Press the remote controller timer time  
button and  
button at the same  
time. (Press and hold for 4 seconds or longer.)  
G Next, press either the temperature setting  
or  
button.  
(Check that the item code is “A1.)  
G Use either the  
automatic address setting.  
G Then press the button.  
or  
button to set the system No. to perform  
(Automatic address setting for one refrigerant system begins.)  
(When automatic address setting for one system is completed, the system  
returns to normal stopped status.) <Approximately 4 – 5 minutes is required.>  
(During automatic address setting, “SETTING” is displayed on the remote  
controller. This message disappears when automatic address setting is  
completed.)  
G Repeat the same steps to perform automatic address setting for each successive system.  
76  
Display during automatic address setting  
G On outdoor unit PCB  
1
2
LED  
* Do not short-circuit the automatic address setting pin (CN51) again while automatic  
address setting is in progress. Doing so will cancel the setting operation and will cause  
LEDs 1 and 2 to turn OFF.  
Blink alternately  
* When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF.  
* LED 1 is D042. LED 2 is D043.  
* If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then  
perform automatic address setting again.  
G Display details of LEDs 1 and 2 on the outdoor unit control PCB  
:
(
: ON  
: Blinking  
: OFF)  
Display meaning  
LED 1  
LED 2  
After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor  
units in that system is possible.  
After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are  
confirmed in that system; however, the number of indoor units does not match the number that was set.  
Automatic address setting is in progress.  
Automatic address setting completed.  
Alternating  
At time of automatic address setting, the number of indoor units did not match the number that was set.  
(when indoor units are operating) indication appears on the display.  
Simultaneous  
Alternating  
Refer to Table of Self-Diagnostic Functions and Description of Alarm Displays.  
Note:  
indicates that the solenoid is fused or that there is a CT (current detection circuit) failure (current is detected when  
the compressor is OFF).  
G Remote controller display during automatic setting  
is blinking  
Request concerning recording the indoor/outdoor unit combination Nos.  
After automatic address setting has been completed, be sure to record them for future reference.  
List the outdoor unit system address and the addresses of the indoor units in that system in an easily visible loca-  
tion (next to the nameplate), using a permanent marking pen or similar means that cannot be erased easily.  
Example: (Outdoor) 1 – (Indoor) 1-1, 1-2, 1-3…  
(Outdoor) 2 – (Indoor) 2-1, 2-2, 2-3…  
These numbers are necessary for later maintenance. Please be sure to indicate them.  
77  
Checking the indoor unit addresses  
Use the remote controller to check the indoor unit address.  
<If 1 indoor unit is connected to 1 remote controller>  
1. Press and hold the  
button and  
button for 4 seconds or longer (simple settings mode).  
2. The address is displayed for the indoor unit that is connected to the remote controller.  
(Only the address of the indoor unit that is connected to the remote controller can be checked.)  
3. Press the  
button again to return to normal remote controller mode.  
<If multiple indoor units are connected to 1 remote controller (group control)>  
1. Press and hold the button and button for 4 seconds or longer (simple settings mode).  
2. “ALL is displayed on the remote controller.  
3. Next, press the button.  
4. The address is displayed for 1 of the indoor units which is connected to the remote controller. Check that the fan  
of that indoor unit starts and that air is discharged.  
5. Press the  
6. Press the  
button again and check the address of each indoor unit in sequence.  
button again to return to normal remote controller mode.  
Number changes to indicate which indoor unit is currently selected.  
Remote Controller Test Run Settings  
1. Press the remote controller  
button for 4 seconds or longer. Then press the  
button.  
G “TEST” appears on the LCD display while the test run is in progress.  
G The temperature cannot be adjusted when in Test Run mode.  
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)  
2. The test run can be performed using the HEAT, COOL, or FAN operation modes.  
Note: The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after  
operation is stopped.  
3. If correct operation is not possible, a code is displayed on the remote controller display.  
(Refer to “7-6. Meaning of Alarm Messages” and correct the problem.)  
4. After the test run is completed, press the  
troller display.  
button again. Check that “TEST” disappears from the remote con-  
(To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after  
60 minutes.)  
* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type ceil-  
ing panel has not been installed. (“P09” display does not occur.)  
78  
8-5. Caution for Pump Down  
Pump down means refrigerant gas in the system is  
returned to the outdoor unit. Pump down is used  
when the unit is to be moved, or before servicing the  
refrigerant circuit.  
G This outdoor unit cannot collect more than the rated refrigerant amount as shown  
CAUTION  
by the nameplate on the back.  
G If the amount of refrigerant is more than that recommended, do not conduct pump  
down. In this case use another refrigerant collecting system.  
8-6. Meaning of Alarm Messages  
Table of Self-Diagnostics Functions and Description of Alarm Displays  
Alarm messages are indicated by the blinking of LED 1 and 2 (D72, D75) on the outdoor unit PCB. They are also displayed on  
the wired remote controller.  
G Viewing the LED 1 and 2 (D72 and D75) alarm displays  
LED 2  
Alarm contents  
LED 1  
Alarm display  
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.  
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm  
N = Alarm No.  
Alternating  
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.  
Alarm is “P17.”  
(
: Blinking)  
Alarm  
Possible cause of malfunction  
message  
Error in receiving serial communication signal.  
(Signal from main indoor unit in case of group control)  
Ex: Auto address is not completed.  
Remote controller is detecting  
error signal from indoor unit.  
Serial  
<E01>  
commu-nication  
errors  
Mis-setting  
<E02>  
Error in transmitting serial communication signal.  
Indoor unit is detecting error signal from remote controller (and system controller).  
<<E03>>  
Error in receiving serial communication signal.  
When turning on the power supply, the number of connected  
indoor units does not correspond to the number set. (Except R.C.  
address is “0.”)  
Indoor unit is detecting error  
signal from outdoor unit.  
E04  
Error of the outdoor unit in receiving serial communication signal  
from the indoor unit.  
<E06>  
Improper setting of indoor unit or  
remote controller.  
Indoor unit address setting is duplicated.  
E08  
Remote controller address connector (RCU. ADR) is duplicated.  
<<E09>>  
(Duplication of main remote controller)  
Starting auto. address setting is prohibited.  
During auto. address setting,  
number of connected units does  
not correspond to number set.  
E12  
This alarm message shows that the auto address connector CN100  
is shorted while other RC line is executing auto address operation.  
Error in auto. address setting. (Number of connected indoor units  
is less than the number set)  
E15  
E16  
When turning on the power  
supply, number of connected  
units does not correspond to  
number set.  
Error in auto. address setting. (Number of connected indoor units  
is more than the number set)  
No indoor unit is connected during auto. address setting.  
Error of outdoor unit address setting.  
E20  
E25  
(Except R.C. address is “0.”)  
Indoor unit communication error  
Error of main indoor unit in receiving serial communication signal  
E18  
of group control wiring.  
from sub indoor units.  
Continued  
79  
Alarm  
message  
Possible cause of malfunction  
This alarm message shows when the indoor unit for multiple-use  
is not connected to the outdoor unit.  
Serial  
commu-nication  
errors  
Improper setting.  
L02  
Duplication of main indoor unit address setting in group control.  
<L03>  
L04  
Mis-setting  
Duplication of outdoor R.C. address setting.  
There are 2 or more indoor units  
controllers which have operation  
mode priority in 1 refrigerant circuit.  
Priority set remote controller  
L05  
Non-priority set remote controller  
L06  
Group control wiring is connected to individual control indoor unit.  
L07  
Indoor unit address is not set.  
L08  
Capacity code of indoor unit is not set.  
<<L09>>  
L10  
Capacity code of outdoor unit is not set.  
Mis-matched connection of outdoor units which have different kinds  
of refrigerant.  
L17  
4-way valve operation failure  
L18  
<<P01>>  
<<P09>>  
<<P10>>  
P12  
Thermal protector in indoor unit fan motor is activated.  
Improper wiring connections of ceiling panel.  
Float switch is activated.  
Activation of  
protective  
device  
Protective device in indoor unit  
is activated.  
Operation of protective function of fan inverter.  
O2 sensor (detects low oxygen level) activated.  
P14  
Compressor thermal protector is activated.  
Power supply voltage is unusual. (The voltage is more than 260 V  
or less than 160 V between L1 and L2 phase.)  
Protective device in outdoor unit  
is activated.  
P02  
Incorrect discharge temperature.  
P03  
P04  
P05  
High pressure switch is activated.  
Detective phase (3-phase outdoor unit only)  
Compressor running failure resulting from missing phase in the  
compressor wiring, etc. (Start failure not caused by IPM or no gas.)  
P16  
P22  
Outdoor unit fan motor is unusual.  
Overcurrent at time of compressor runs more than 80Hz (DCCT  
secondary current or ACCT primary current is detected at a time  
other than when IPM has tripped.)  
P26  
IPM trip (IPM current or temperature)  
H31  
Inverter for compressor is unusual. (DC compressor does not  
operate.)  
P29  
Indoor coil temp. sensor (E1)  
<<F01>>  
<<F02>>  
<<F03>>  
<<F10>>  
<<F11>>  
F04  
Thermistor  
fault  
Indoor thermistor is either open  
or damaged.  
Indoor coil temp. sensor (E2)  
Indoor coil temp. sensor (E3)  
Indoor suction air (room) temp. sensor (TA)  
Indoor discharge air temp. sensor (BL)  
Compressor discharge sensor (TD)  
Outdoor No. 1 coil liquid temp. sensor (C1)  
Outdoor air temp. sensor (TO)  
Outdoor thermistor is either  
open or damaged.  
F07  
F08  
Compressor suction port temperature sensor (TS)  
High pressure sensor  
F12  
F16  
EEPROM on indoor unit PCB failure  
F29  
Protective  
device for  
Protective device for compressor  
No. 1 is activated.  
EEPROM on the outdoor unit PCB is a failure.  
F31  
compressor is  
activated  
Current is not detected when comp. is ON.  
H03  
80  
9. APPENDIX  
9-1. 4-Way Air Discharge Semi-Concealed Type (X Type)  
I NAME OF PARTS  
Water drain  
X type (4-WAY)  
X
Ceiling panel  
(optional)  
Air outlet  
(4 locations)  
Air intake grille  
(air intake)  
I CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before  
cleaning.  
WARNING  
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-  
nents and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When clean-  
ing the air outlet side, be careful not to force the vanes out of place.  
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic  
CAUTION  
parts using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be  
especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
The air filter collects dust and other particles from the air and should be cleaned at regular intervals  
as indicated in the table below or when the filter indication ( ) on the display of the remote control  
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air  
conditioner drops greatly.  
Air filter  
Type  
Period  
6 months  
NOTE  
X
The frequency with which the filter should be cleaned depends on the environment in which the  
unit is used.  
<How to clean the filter>  
<How to remove the filter>  
1. Remove the air filter from the air intake grille.  
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the fil-  
ter in lukewarm, soapy water, rinse it in clean water, and dry it.  
1. Use a screwdriver to remove the bolt screw on each side for the two latches. (Be sure to  
reattach the two bolt screws after cleaning.)  
2. Press on the two latches of the air intake grille with your thumbs in the direction of the  
arrow to open the grille.  
3. Open the air intake grille downward.  
G When cleaning the air filter, never remove the safety chain. If it is necessary to remove it  
for servicing and maintenance inside, be sure to reinstall the safety chain securely (hook  
on the grille side) after the work.  
CAUTION  
G When the filter has been removed, rotating parts (such as the fan), electrically charged  
areas, etc. will be exposed in the unit’s opening. Bear in mind the dangers that these parts  
and areas pose, and proceed with the work carefully.  
81  
4. Remove the air filter attached to the air intake grille.  
Latch  
X
Safety chain  
Air intake  
grille  
Bolt screws  
Air filter  
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled  
improperly; special care should be taken when you clean these parts.  
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt  
or soot.  
CAUTION  
3. The internal coil and other components of the outdoor unit must also be cleaned periodi-  
cally. Consult your dealer or service center.  
Care: After a prolonged idle period  
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a  
blockage, remove it.  
Operate the fan for half a day to dry out the inside.  
Care: Before a prolonged idle period  
Disconnect the power supply and also turn off the circuit breaker.  
Clean the air filter and replace it in its original position.  
Outdoor unit internal components must be checked and cleaned periodically. Con-  
tact your local dealer for this service.  
I TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
I Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit  
will not work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Do  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
82  
9-2. 1-Way Air Discharge Semi-Concealed Type (A Type)  
I NAME OF PARTS  
SEMI-CONCEALED  
A type (1-WAY)  
Water drain  
Air outlet  
Air intake  
A
Ceiling panel  
(optional)  
I CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power  
WARNING  
before cleaning.  
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-  
nents and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When cleaning  
the air outlet side, be careful not to force the vanes out of place.  
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe  
CAUTION  
plastic parts using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if handled improperly;  
be especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
The air filter collects dust and other particles from the air and should be cleaned at regular intervals  
as indicated in the table below or when the filter indication ( ) on the display of the remote control  
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air  
conditioner drops greatly.  
Air filter  
Type  
A
Period  
2 weeks  
The frequency with which the filter should be cleaned depends on the environment in which the unit is used.  
NOTE  
<How to clean the filter>  
Air filter finger-hold  
Air intake grill  
1. Remove the air filter from the air intake grille.  
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter,  
wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.  
Air filter  
<How to remove the filter>  
1-way air discharge semi-concealed type (A):  
1. Take hold of the finger-hold on the air intake grille and press it to  
the rear, and the grille will open downward.  
Hook  
Screw  
2. Take hold of the finger-hold on the air filter, pull it toward you.  
Latch  
Screw  
Air filter finger-hold  
*Take hold of the finger-hold on the air filter, pull it toward you.  
83  
Outdoor unit  
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled  
improperly; special care should be taken when you clean these parts.  
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt  
or soot.  
CAUTION  
3. The internal coil and other components of the outdoor unit must also be cleaned  
periodically. Consult your dealer or service center.  
Care: After a prolonged idle period  
Care: Before a prolonged idle period  
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a  
blockage, remove it.  
A
Operate the fan for half a day to dry out the inside.  
Disconnect the power supply and also turn off the circuit breaker.  
Clean the air filter and replace it in its original position.  
Outdoor unit internal components must be checked and cleaned periodically.  
Contact your local dealer for this service.  
I TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
I Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit  
will not work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Do  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
84  
9-3. Concealed Duct (High-Static Pressure) Type (U, D Type)  
I NAME OF PARTS  
CONCEALED DUCT  
CONCEALED DUCT  
U type (standard static pressure)  
D type (high static pressure)  
Air intake  
sideduct flange  
(rear)  
Flexible duct  
(optional)  
Water drain  
Water drain  
Canvas duct  
(optional)  
Electrical box  
U
D
Air intake grille  
(air intake)  
(optional)  
Air outlet side  
duct flange  
Air outlet grille  
(optional)  
I CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before  
cleaning.  
WARNING  
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-  
nents and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When clean-  
ing the air outlet side, be careful not to force the vanes out of place.  
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic  
CAUTION  
parts using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be  
especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
*Concealed duct type (U, D):  
Type  
Period  
An air filter is not provided with this air conditioner at the time of shipment. To get clean air  
U, D*  
(Depends on filter  
specifications)  
and to extend the service life of the air conditioner, an air filter must be installed in the air  
intake. For installation and cleaning the air filter, consult your dealer or service center.  
NOTE  
The frequency with which the filter should be cleaned depends on the environment in which the unit is used.  
<How to clean the filter>  
1. Remove the air filter from the air intake grille.  
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the filter in lukewarm, soapy water,  
rinse it in clean water, and dry it.  
85  
I TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
U
D
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
I Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit  
will not work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Do  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
86  
9-4. Ceiling-Mounted Type (T Type)  
I NAME OF PARTS  
CEILING-MOUNTED  
T type  
Air outlet  
Water drain  
(Drain pipe can be  
connected to either  
the left or right side.)  
Air intake  
grille (air  
intake)  
I CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before  
cleaning.  
WARNING  
2. Do not pour water on the indoor unit to clean it. This will damage the internal  
components and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When clean-  
ing the air outlet side, be careful not to force the vanes out of place.  
T
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic  
CAUTION  
parts using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be  
especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
The air filter collects dust and other particles from the air and should be cleaned at regular intervals  
as indicated in the table below or when the filter indication ( ) on the display of the remote control  
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air  
conditioner drops greatly.  
Air filter  
Type  
Period  
NOTE  
T
2 weeks  
The frequency with which the filter should be cleaned depends on the environment in which the  
unit is used.  
<How to clean the filter>  
1. Remove the air filter from the air  
intake grille.  
2. Use a vacuum cleaner to remove  
light dust. If there is sticky dust on  
the filter, wash the filter in lukewarm,  
soapy water, rinse it in clean water,  
and dry it.  
Air filter finger-hold  
Air intake grill  
Air intake grill  
finger-hold  
<How to remove the filter>  
Screw  
Air filter  
1. Take hold of the finger-hold  
on the air intake grille and  
press it to the rear, and the  
grille will open downward.  
2. Take hold of the finger-hold  
on the air filter, pull it toward  
you.  
Hook  
Screw  
Latch  
Air filter finger-hold  
* Take hold of the finger-hold on the air filter, pull it toward you.  
87  
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled  
improperly; special care should be taken when you clean these parts.  
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt  
or soot.  
CAUTION  
3. The internal coil and other components of the outdoor unit must also be cleaned periodi-  
cally. Consult your dealer or service center.  
Care: After a prolonged idle period  
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a  
blockage, remove it.  
Operate the fan for half a day to dry out the inside.  
Care: Before a prolonged idle period  
Disconnect the power supply and also turn off the circuit breaker.  
Clean the air filter and replace it in its original position.  
Outdoor unit internal components must be checked and cleaned periodically. Con-  
tact your local dealer for this service.  
I TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
T
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
I Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit will not  
work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Do  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
88  
9-5. Wall-Mounted Type (K Type)  
I NAME OF PARTS  
K Type (Wall-Mounted)  
Air intake  
Air outlet  
I CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before  
cleaning.  
WARNING  
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-  
nents and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When clean-  
ing the air outlet side, be careful not to force the vanes out of place.  
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic  
parts using very hot water.  
CAUTION  
2. Some meta l edges and the fins are sharp and may cause injury if handled improperly; be  
especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
K
The air filter collects dust and other particles from the air and should be cleaned at regular intervals  
as indicated in the table below or when the filter indication ( ) on the display of the remote control  
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air  
conditioner drops greatly.  
Air filter  
NOTE  
Type  
Period  
K
2 weeks  
The frequency with which the filter should be cleaned depends on the environment in which the  
unit is used.  
<How to clean the filter>  
1. Remove the air filter from the air intake grille.  
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the filter in  
lukewarm, soapy water, rinse it in clean water, and dry it.  
<How to remove the filter>  
1. Move the flap on the air outlet grille to its lowest position with the remote control unit.  
2. The filter is disengaged by pushing the tab up gently. Hold the air filter by the tab at the bottom,  
and pull downward.  
Air intake grille  
Air filter  
When replacing the filter, make sure that the FRONT mark is facing you.  
Push it up until you hear it click back into position.  
89  
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled  
improperly; special care should be taken when you clean these parts.  
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt  
or soot.  
CAUTION  
3. The internal coil and other components of the outdoor unit must also be cleaned periodi-  
cally. Consult your dealer or service center.  
Care: After a prolonged idle period  
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a  
blockage, remove it.  
Operate the fan for half a day to dry out the inside.  
Care: Before a prolonged idle period  
Disconnect the power supply and also turn off the circuit breaker.  
Clean the air filter and replace it in its original position.  
Outdoor unit internal components must be checked and cleaned periodically. Con-  
tact your local dealer for this service.  
I TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
K
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
I Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit will not  
work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Do  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
90  

Lexmark X 750e Mfp User Manual
Mitsubishi Mr Slim Pch42ek User Manual
Oricom Secure 100 User Manual
Samsung As12hpbn User Manual
Samsung Avmbc026ea B 0 User Manual
Teac Automobile Parts 111600 User Manual
Trion Air Boss Dc 4m User Manual
Xerox Workcentre 5745 User Manual
Xerox Workcentre 7655 User Manual
York Champion D2eb User Manual