Sanyo Kmhs2472 User Manual

For Indoor Unit  
INSTALLATION INSTRUCTIONS  
COOL/DRY/HEAT Model  
– Inverter Split System Air Conditioner –  
This air conditioner uses the new refrigerant R410A.  
Contents  
Model Combinations  
Page  
Combine indoor and outdoor units only as listed  
below.  
IMPORTANT!  
Please Read Before Starting .................................. 2  
Indoor Unit  
KMHS0772  
KMHS0972  
KMHS1272  
KMHS1872  
KMHS2472  
Outdoor Unit  
CMH1972  
CMH2472  
CMH3172  
1. GENERAL .......................................................... 3  
1-1. Tools Required for Installation (not supplied)  
1-2. Accessories Supplied with Unit  
1-3. Optional Copper Tubing Kit  
1-4. Type of Copper Tube and Insulation Material  
1-5. Additional Materials Required for Installation  
2. INSTALLATION SITE SELECTION ................... 4  
2-1. Indoor Unit  
Power Source:  
60 Hz, single-phase, 230 / 208 VAC  
2-2. Embedding the Tubing and Wiring  
3. HOW TO INSTALL THE INDOOR UNIT .............. 6  
3-1. Remove the Rear Panel from the Unit  
3-2. Make a Hole  
Combinations of indoor and outdoor units  
Connect indoor and outdoor units only in the combi-  
nations listed in the catalog or installation manual.  
3-3. Install the Rear Panel on the Wall  
3-4. Remove the Grille to Install the Indoor Unit  
3-5. Shape the Indoor Side Tubing  
3-6. Wiring Instructions  
CAUTION  
3-7. Wiring Instructions for Inter-unit Connections  
3-8. Mounting  
3-9. Drain Hose  
Connecting any other model may result in  
operation failure and system damage.  
4. HOWTOTEST RUNTHE AIR CONDITIONER .... 16  
Be sure to read the yellow instruction sheet  
attached to the outdoor unit for models using the  
new refrigerant R410A.  
5. REMOTE CONTROL UNIT INSTALLATION  
POSITION ......................................................... 17  
5-1. Mounting on a Wall  
6. ADDRESS SWITCH.......................................... 18  
6-1. Address Setting of the Remote  
Control Unit  
7. CONNECTING A HOME AUTOMATION  
DEVICE.............................................................. 19  
NOTE  
The illustrations are based on the typical appearance of  
a standard model. Consequently, the shape may differ  
from that of the air conditioner that you are installing.  
8. INSTALLATION CHECK SHEET ...................... 19  
In Canada  
SANYO FISHER COMPANY  
SANYO Canada Inc.  
A DIVISION OF SANYO NORTH AMERICA CORPORATION  
21605 Plummer Street  
300 Applewood Crescent, Concord  
Ontario, L4K 5C7, Canada  
Chatsworth, CA 91311 U.S.A.  
85264189998000 © SANYO 2006  
1. General  
6. Sabre saw or key hole saw  
7. Hacksaw  
8. Core bits  
9. Hammer  
10. Drill  
This booklet briefly outlines where and how to install the  
air conditioning system. Please read over the entire set  
of instructions for the indoor and outdoor units and make  
sure all accessory parts listed are with the system before  
beginning.  
11. Tube cutter  
1-1. Tools Required for Installation (not supplied)  
1. Standard screwdriver  
12. Tube flaring tool  
13. Torque wrench  
14. Adjustable wrench  
15. Reamer (for deburring)  
2. Phillips head screwdriver  
3. Knife or wire stripper  
4. Tape measure  
5. Carpenter’s level  
1-2. Accessories Supplied with Unit  
Table 1  
Parts  
Figure  
Qʼty  
Parts  
Figure  
Qʼty  
Parts  
Clamp  
Figure  
Qʼty  
Truss-head  
Remote  
Tapping screw  
Phillips  
1
10  
1
control unit  
5/32  
/8" (4 16 mm)  
5
Remote control  
unit holder  
1
2
8
1
2
Rawl plug  
Air clean filter  
Packed in the indoor unit.  
Drain hose  
adapter  
AAA alkaline  
battery  
1-3. Optional Copper Tubing Kit  
Copper tubing for connecting the outdoor unit to the  
indoor unit is available in kits which contain the narrow  
and wide tubing, fittings and insulation. Consult your  
nearest sales outlet or A/C workshop.  
2. Foamed polyethylene insulation for the specified  
copper tubes as required to precise length of tubing.  
Wall thickness of the insulation should be not less  
than 5/16" (8 mm).  
3. Use insulated copper wire for field wiring. Wire size  
varies with the total length of wiring. Refer to 3-6.  
Wiring Instructions for details.  
1-4. Type of Copper Tube and Insulation Material  
If you wish to purchase these materials separately from  
a local source, you will need:  
1. Deoxidized annealed copper tube for refrigerant tub-  
ing as detailed in Table 2.  
Check local electrical codes  
and regulations before  
obtaining wire. Also, check  
any specified instructions or  
limitations.  
CAUTION  
Cut each tube to the appropriate lengths 1' to 1'4"  
(30 cm to 40 cm) to dampen vibration between units.  
Table 2  
Narrow Tube  
Model  
Wide Tube  
Outer Dia.  
Thickness  
Outer Dia.  
Thickness  
KMHS0772  
KMHS0972  
KMHS1272  
KMHS1872  
KMHS2472  
1/4" (6.35 mm)  
1/4" (6.35 mm)  
1/4" (6.35 mm)  
1/4" (6.35 mm)  
1/4" (6.35 mm)  
0.0314" (0.8 mm)  
0.0314" (0.8 mm)  
0.0314" (0.8 mm)  
3/8" (9.52 mm)  
3/8" (9.52 mm)  
3/8" (9.52 mm)  
0.0314" (0.8 mm)  
0.0314" (0.8 mm)  
0.0314" (0.8 mm)  
0.0314" (0.8 mm) 1/2" (12.70 mm) 0.0314" (0.8 mm)  
0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)  
3
1-5. Additional Materials Required for Installation  
1. Refrigeration (armored) tape  
2. Insulated staples or clamps for connecting wire  
(See local codes)  
3. Putty  
4. Refrigeration lubricant  
5. Clamps or saddles to secure refrigerant tubing  
Indoor unit  
2. Installation Site Selection  
2-1. Indoor Unit  
To prevent abnormal heat generation  
WARNING  
and the possibility of fire, do not  
place obstacles, enclosures and  
grilles in front of or surrounding the  
air conditioner in a way that may  
block air flow.  
Drain hose  
Outside drainage  
AVOID:  
G direct sunlight.  
Fig. 1  
G nearby heat sources that may affect performance of the  
unit.  
6" (15 cm)  
min.  
2" (5 cm)  
min.  
2" (5 cm)  
min.  
G areas where leakage of flammable gas may be expected.  
G placing or allowing any obstructions near the A/C inlet or  
outlet.  
Front View  
G installing in rooms that contain instant-on (rapid-start)  
fluorescent lamps. (These may prevent the A/C from  
receiving signals.)  
Fig. 2  
Tubing length (L1)  
INDOOR  
UNIT (1)  
G places where large amounts of oil mist exist.  
INDOOR  
G installing in locations where there are devices that  
UNIT (2)  
generate high-frequency emissions.  
Elevation  
L2  
L3  
difference (H1) OUTDOOR  
UNIT  
H2  
H3  
DO:  
G select an appropriate position from which every corner of  
INDOOR  
UNIT (3)  
H4  
INDOOR  
L4  
UNIT (4)  
the room can be uniformly cooled. (High on a wall is best.)  
Fig. 3a  
G select a location that will hold the weight of the unit.  
G select a location where tubing and drain hose have the  
shortest run to the outside. (Fig. 1)  
CAUTION  
G allow room for operation and maintenance as well as  
Indoor unit  
Wall  
unrestricted air flow around the unit. (Fig. 2)  
For stable operation of the  
air conditioner, do not  
install wall-mounted type  
indoor units less than 5'  
(1.5 m) from floor level.  
G install the unit within the maximum elevation difference  
(H1, H2, H3, H4) above or below the outdoor unit and  
within a total tubing length (L1+L2+L3, L1+L2+L3+L4)  
from the outdoor unit as detailed in Table 3 and Fig. 3a.  
Minimum height  
from floor level  
5' (1.5 m)  
Floor level  
Fig. 3b  
4
G Install the indoor unit more than 3.3' (1 m) away from any  
antenna or power lines or connecting wires used for tele-  
vision, radio, telephone, security system, or intercom.  
Electrical noise from any of these sources may affect  
operation.  
G install in a sturdy manner to avoid increased operating  
noise.  
Table 3  
Max.  
Allowable  
Tubing Length  
per unit  
Max. Allowable Total  
Tubing Length  
at shipment  
Limit of  
Total Tubing Length  
(L1+L2+L3) or  
(L1+L2+L3+L4)  
(ft.)  
Limit of Elevation  
Difference  
(H1, H2, H3, H4)  
(ft.)  
Required Amount  
of Additional  
Refrigerant  
Model  
(L1+L2+L3) or  
(L1+L2+L3+L4)  
(ft.)  
(oz./ft.)*  
(ft.)  
CMH1972  
CMH2472  
CMH3172  
82  
82  
150 (L1+L2+L3)  
150 (L1+L2+L3)  
50  
50  
50  
150 (L1+L2+L3+L4)  
150 (L1+L2+L3+L4)  
200 (L1+L2+L3+L4)  
230 (L1+L2+L3+L4)  
0.22  
0.22  
100  
* If total tubing length becomes 150 to 200 ft. (Max.) or 150 to 230 ft. (Max.), charge additional refrigerant (R410A) by 0.22 oz./ft.  
No additional charge of compressor oil is necessary.  
2-2. Embedding the Tubing and Wiring  
G Before beginning embedding installation work, consult  
fully with agencies or offices related to the building’s  
foundation, construction, electricity, and water.  
G Wait to make connections to the embedded portion.  
Each connection step is described later in this  
manual.  
G Securely cover the end of the embedded tubing to  
prevent intrusion of dirt or moisture.  
G If an embedded tube is to be left for a long time, fill  
the tube with nitrogen and seal both ends securely.  
If a tube is left open for an extended time, moisture in  
the air inside the tubing may condense into water  
droplets, and lead to water contamination of the refrig-  
erant circuit.  
G In order to prevent insulation breakdown and ground  
faults, do not allow wiring ends to come in contact with  
rainwater, or be subjected to condensation or dew.  
G Apply sufficient thermal insulation to the refrigerant  
tubing and drain pipes.  
5
3. How to Install the Indoor Unit  
3-1. Remove the Rear Panel from the Unit  
(1) Remove and discard the set screw on the rear  
panel. (Fig. 6)  
(2) Press the 2 L marks on the frame cover and disen-  
gage the stationary tabs from the frame. (Fig. 7)  
Set screw only for transportation  
(3) Remove the rear panel.  
Fig. 6  
NOTE  
Tubing can be extended in 5 directions as shown in Fig.  
8. Select the direction you need providing the shortest  
run to the outside unit.  
Rear panel  
G When left tubing is to be done, switch the drain hose  
and drain cap. (For details, refer to “Switching drain  
hose and drain cap” on page 14.)  
3-2. Make a Hole  
(1) Place the rear panel from the indoor unit on the wall  
at the location selected. Make sure the panel is hori-  
zontal, using a carpenter’s level or tape measure to  
measure down from the ceiling. Wait until after cut-  
ting the hole before attaching the rear panel to the  
wall.  
marks  
Fig. 7  
Right-rear  
tubing  
Left  
(recommended)  
tubing  
(2) Determine which side of the unit you should make  
the hole for tubing and wiring. (Fig. 9a or 9b)  
Left-rear  
tubing  
Right tubing  
NOTE  
Downward tubing  
In the case of left-rear tubing, use the measurement  
points from the edge of the rear panel for precise place-  
ment of the hose outlet. (Fig. 9a or 9b)  
Fig. 8  
(KMHS0772, KMHS0972, KMHS1272)  
(3) Before making the hole, check carefully that no  
studs or pipes are directly run behind the spot to be  
cut.  
2-3/4" (70 mm)  
Also avoid areas where elec-  
trical wiring or conduits are  
located.  
CAUTION  
The above precautions are also applicable if tubing  
goes through the wall in any other location.  
Fig. 9a  
(KMHS1872, KMHS2472)  
2-3/8" (60 mm)  
Fig. 9b  
6
(4) Using a sabre saw, key hole saw or hole-cutting drill  
attachment, cut a hole in the wall. See Table 4 and  
Fig. 10.  
NOTE  
Hole should be made at a slight downward slant to the  
outdoor side.  
Table 4  
Indoor  
side  
Outdoor  
side  
Hole Dia.  
KMHS0772/0972/1272  
KMHS1872/2472  
2-9/16" (65 mm)  
3-5/32" (80 mm)  
(5) Measure the thickness of the wall from the inside  
edge to the outside edge and cut PVC pipe at a  
slight angle 1/4" (6 mm) shorter than the thickness of  
the wall. (Fig. 11)  
Fig. 10  
PVC pipe (Locally purchased)  
(6) Place the plastic cover over the end of the pipe (for  
indoor side only) and insert the pipe in the wall.  
(Fig. 12)  
Cut at slight angle  
3-3. Install the Rear Panel on the Wall  
Fig. 11  
Be sure to confirm that the wall is strong enough to sus-  
pend the unit.  
INSIDE  
OUTSIDE  
PVC pipe  
Wall  
See either Item a) or b) below depending on the wall type.  
Plastic cover  
(Locally purchased)  
a) If Wooden Wall  
Slight  
angle  
(1) Attach the rear panel to the wall with the 8 screws  
provided. (Fig. 13a or 13b)  
Fig. 12  
If you are not able to line up the holes in the rear  
panel with the beam locations marked on the wall,  
use rawl plugs or toggle bolts to go through the  
holes on the panel or drill 3/16" (5 mm) dia. holes in  
the panel over the stud locations and then mount the  
rear panel.  
(KMHS0772, KMHS0972, KMHS1272)  
(2) Double check with a carpenter’s level or tape mea-  
sure that the panel is level. This is important to install  
the unit properly. (Fig. 14)  
Fig. 13a  
(3) Make sure the panel is flush against the wall. Any  
space between the wall and unit will cause noise  
and vibration.  
(KMHS1872, KMHS2472)  
b) If Block, Brick, Concrete or Similar Type Wall  
Make 3/16" (4.8 mm) dia. holes in the wall. Insert rawl  
plugs for appropriate mounting screws. (Fig. 15)  
Fig. 13b  
Fig. 14  
3/16"  
(4.8 mm) dia. hole  
Rawl plug  
Fig. 15  
7
Grille  
Air intake grille  
3-4. Remove the Grille to Install the Indoor Unit  
3-4-1. Indoor unit types  
(KMHS0772, KMHS0972, KMHS1272)  
Basically, these models can be installed and wired without  
removing the grille. If access to any internal part is needed,  
follow the steps as given below.  
Fig. 16a  
Be sure to wear work gloves  
CAUTION  
during installation to avoid being  
cut by the sharp aluminum fins  
of the heat exchanger.  
How to remove the grille  
(1) Grasp both ends of the air intake grille, and remove it by  
opening towards the front and pulling towards you. (Fig.  
16a)  
Screw cover  
Fig. 16b  
Cover  
(2) Remove the 2 screws. (Fig. 16b)  
Thermistor  
(3) Remove the screw on the right side cover plate and  
open the cover. (Fig. 17a)  
(4) Take out the thermistor from the grille. (Fig. 17b)  
(5) Pull the lower part of the grille toward you to remove.  
(Fig. 18a)  
Thermistor  
Fig. 17b  
Fig. 17a  
(6) Use a standard screwdriver to push on the tabs to  
remove the grille.  
Tab  
*
Grille  
Frame  
How to replace the grille  
*
(1) Reinstall the grille into the lower part while aligning  
its tabs on the upper part. (Fig. 18b) Insert the tabs  
in the slots and push the lower part of the grille back  
into position.  
Tab  
(2) Make sure that the grille and frame are firmly fitted  
together by engaging the tabs.  
Fig. 18a  
(3) Attach the thermistor on the grille. (Fig. 17a)  
*
(4) Close the cover and replace the screw. (Fig. 17a)  
*
(5) Affix the grille with the 2 previously removed screws.  
(Fig. 16b)  
(6) Install the air intake grille.  
(a) Allow the edge of the air intake grille to slide into  
the top of the indoor unit, and then insert it all  
the way inside. (Fig. 19a)  
Fig. 18b  
(b) Press the bottom right and left corners of the air  
intake grille to attach it to the indoor unit. (Fig. 19b)  
Groove  
NOTE  
Pin  
Attach so that the round pins at the top right and left corners  
of the air intake grille are inserted into the grooves at the top  
right and left of the  
indoor unit.  
Fig. 19b  
Fig. 19a  
8
Grille  
Air intake grille  
3-4-2. Indoor unit types  
(KMHS1872, KMHS2472)  
Basically, these models can be installed and wired with-  
out removing the grille. If access to any internal part is  
needed, follow the steps as given below.  
How to remove the grille  
Fig. 16a-1  
(1) Grasp both ends of the air intake grille, and remove  
it by opening towards the front and pulling towards  
you. (Fig. 16a-1)  
(2) Remove the 3 screws. (Fig. 16b-1)  
(3) Remove the screw on the right side cover plate and  
open the cover. (Fig. 17a-1)  
Fig. 16b-1  
(4) Take out the thermistor from the grille. (Fig. 17b-1)  
Cover  
(5) Press the 3 tabs at the top of the grille and the 3  
tabs on the front face to separate the grille from the  
frame. (Fig. 18a-1)  
Thermistor  
Thermistor  
(6) Pull the grill toward you to remove it.  
How to replace the grille  
Fig. 17b-1  
Fig. 17a-1  
(1) When installing the grille, place the bottom of the  
grille into the frame first. (Fig. 18b-1)  
Tab  
Then insert the tabs on the top of the grille and on  
the front face into the frame.  
(2) Make sure that the grille and frame are firmly fitted  
together by engaging the tabs.  
(3) Attach the thermistor on the grille. (Fig. 17a-1)  
(4) Close the cover and replace the screw. (Fig. 17a-1)  
Tab  
(5) Affix the grille with the 3 previously removed screws.  
(Fig. 16b-1)  
Fig. 18a-1  
(6) Install the air intake grille.  
(a) Allow the edge of the air intake grille to slide into  
the top of the indoor unit, and then insert it all the  
way inside. (Fig. 19a-1)  
(b) Press the bottom right and left corners and center  
of the air intake grille to attach it to the indoor  
unit. (Fig. 19b-1)  
Fig. 18b-1  
NOTE  
Groove  
Attach so that the round pins at the top right and left cor-  
ners of the air intake grille are inserted into the grooves  
at the top right and left of the indoor unit.  
Pin  
Fig. 19a-1  
Fig. 19b-1  
9
3-5. Shape the Indoor Side Tubing  
(1) Arrangement of tubing by directions  
a) Right or left tubing  
Frame  
Cut out the corner of the right/left frame with a  
hacksaw or the like. (Figs. 20 and 21)  
Left tubing  
outlet  
b) Right-rear or left-rear tubing  
In this case, the corner of the frame need not be  
cut.  
(2) To mount the indoor unit on the rear panel:  
Fig. 20  
Hang the 2 mounting slots of the unit on the  
upper tabs of the rear panel. (Fig. 22)  
Frame  
3-6. Wiring Instructions  
General precautions on wiring  
Right tubing  
outlet  
(1) Before wiring, confirm the rated voltage of the unit as  
shown on its nameplate, then carry out the wiring  
closely following the wiring diagram.  
(2) Provide a power outlet to be used exclusively for  
each unit, with a power supply disconnect and cir-  
cuit breaker for overcurrent protection provided in  
the exclusive line.  
Fig. 21  
(3) To prevent possible hazard due to insulation failure,  
the unit must be grounded.  
(4) Each wiring connection must be done tightly and in  
accordance with the wiring system diagram. Wrong  
wiring may cause the unit to misoperate or become  
damaged.  
Fig. 22  
(5) Do not allow wiring to touch the refrigerant tubing,  
compressor, or any moving parts of the fan.  
(6) Unauthorized changes in the internal wiring can be  
very dangerous. The manufacturer will accept no  
responsibility for any damage or misoperation that  
occurs as a result of such unauthorized changes.  
10  
3-7. Wiring Instructions for Inter-unit Connections  
Rear  
panel  
Wall  
(1) Insert the inter-unit wiring (according to local codes)  
into the through-the-wall PVC pipe. Run the wiring  
toward the indoor side allowing approx. 10" (25 cm)  
to extend from the wall face. (Fig. 24)  
Plastic  
cover  
(2) Grasp both ends of the air intake grille, and remove  
it by opening towards the front and pulling towards  
you.  
Wiring  
10"  
(25 cm)  
(3) Remove the screw on the right side cover plate and  
open the cover. (Fig. 25)  
Fig. 24  
Fig. 25  
Fig. 26a  
(4) Route the inter-unit wiring from the back of the  
indoor unit and pull it toward the front for connec-  
tion. (Figs. 26a and 26b)  
Cover  
(5) Connect the inter-unit wiring to the corresponding  
terminals on the terminal plate (Figs. 26a and 26b)  
while referring to the wiring diagram.  
(6) Be sure to secure the wiring with the provided  
clamp.  
NOTE  
When closing the air intake grille, press the bottom right  
and left corners and center. (Fig. 27)  
Please refer to “How to replace the grille” on page 8 or 9  
for installing the air intake grille.  
Terminal  
plate  
Fig. 27  
Inter-unit  
wiring  
Earth  
plate  
Lock nut  
Top of conduit  
connector  
Fig. 26b  
11  
Loose wiring may cause the  
terminal to overheat or result  
in unit malfunction. A fire  
hazard may also exist.There-  
fore, be sure all wiring is  
tightly connected.  
WARNING  
When connecting each power wire to the corresponding  
terminal, follow the instructions “How to connect wiring  
to the terminal” and fasten the wire securely tight with  
the fixing screw of the terminal plate.  
9/32"  
(7 mm)  
(ACTUAL  
STRIP  
SIZE  
SIZE)  
How to connect wiring to the terminal  
a) For Indoor Unit  
Fig. 28  
(1) Cut the wire end with a cutting pliers, then strip the  
insulation to expose the wire about 9/32" (7 mm).  
See the label (Fig. 28) near the terminal plate.  
Solid wire  
Loop  
(2) Using a screwdriver, loosen the terminal screw on  
the terminal plate.  
(3) Insert the wire and tighten the terminal screw com-  
pletely using a screwdriver.  
Insulation  
b) For Outdoor Unit  
Fig. 29  
I For solid core wiring (or F-cable)  
Stranded wire  
(1) Cut the wire end with a cutting pliers, then strip the  
insulation to expose the solid wire about 15/16" (25  
mm). (Fig. 29)  
Ring  
connector  
(2) Using a screwdriver, remove the terminal screw(s)  
on the terminal plate.  
(3) Using the pliers, bend the solid wire to form a loop  
suitable for the terminal screw.  
Fig. 30  
(4) Shape the loop wire properly, place it on the termi-  
nal plate and fix it securely with the removed termi-  
nal screw using a screwdriver.  
Twist wire ends  
I For stranded wiring  
(1) Cut the wire end with a cutting pliers, then strip the  
insulation to expose the stranded wiring about 3/8"  
(10 mm) and tightly twist the wire ends. (Figs. 30  
and 31)  
Fig. 31  
(2) Using a screwdriver, remove the terminal screw(s)  
on the terminal plate.  
Special  
washer  
Screw  
(3) Using a ring connector fastener or pliers, securely  
clamp each stripped wire end with a ring connector.  
(Fig. 30)  
Screw and  
Ring connector  
Terminal plate  
special washer  
Wire  
Ring  
connector  
(4) Place the ring connector wire, and replace and  
tighten the removed terminal screw using a screw-  
driver. (Fig. 32)  
Wire  
Fig. 32  
12  
3-8. Mounting  
(1) To install the indoor unit, mount the indoor unit onto  
the 2 tabs on the upper part of the rear plate.  
(2) Hold down the air discharge outlet and press the  
lower part of the indoor unit until it clicks to securely  
fasten to the 2 tabs on the lower part of the rear  
plate. (Fig. 33)  
Push  
NOTE  
For tubing, choose either the right or left tubing direction  
and follow the steps below. This work can be made easi-  
er by placing padding material (such as styrofoam) at the  
rear right side of the indoor unit. (Fig. 34)  
Fig. 33  
I Right-side tubing  
(1) Shape the refrigerant tubing so that it can easily go  
into the wall hole. (Fig. 35)  
(2) Push the wiring, refrigerant tubing, and drain hose  
through the hole in the wall. Adjust the indoor unit so  
it is securely seated on the rear panel. (Fig. 36)  
Padding material  
(3) Carefully bend the tubing (if necessary) to run along  
the wall in the direction of the outdoor unit and then  
tape as far as the fittings. (See Caution on page 15  
in the outdoor unit installation manual.) The drain  
hose should come straight down the wall to a point  
where water runoff won’t stain the wall.  
Fig. 34  
Rear panel  
Cover  
Refrigerant  
tubing  
(4) Connect the refrigerant tubing to the outdoor unit.  
(After performing a leak test on the connecting part,  
insulate it with the tubing insulation. (Fig. 37a))  
Also, refer to Section 3-6. Tubing connections in the  
outdoor unit installation manual.  
Inter-unit  
wiring  
Drain hose  
(5) Assemble the refrigerant tubing, drain hose, and  
conduit (including inter-unit wiring) as shown in  
Fig. 37b.  
Fig. 35  
Refrigerant tubing  
Insulation  
Fig. 37a  
Conduit  
Drain hose  
Fig. 36  
Inter-unit wiring  
Fig. 37b  
13  
I Left-side tubing  
Rear panel  
(1) Lead the tubing and drain hose through the wall,  
allowing sufficient length for connection. Then bend  
the tubing using a tube bender to make the attach-  
ment. (Fig. 38)  
Hole in wall  
Wide tube  
Narrow tube  
Bent part  
(2) Switch the drain hose and drain cap.  
Fig. 38  
Switching drain hose and drain cap  
(a) Locate the drain hose and the drain cap. (Fig.  
39)  
(b) Remove the screws fastening the drain hose on  
the right side, and pull out the drain hose to  
remove it. (Fig. 39)  
Drain cap  
(c) Apply moderate force to pull off the drain cap  
on the left side. (If you cannot pull it off by hand,  
use a long-nose pliers.)  
Drain hose  
Fig. 39  
(d) Reattach the drain hose to the left side and the  
drain cap to the right side. (Fig. 40a)  
Drain hose  
Drain hose  
Slide the drain hose fully onto the drain pan outlet  
until the drain hose edge is pushed into the insula-  
tion. Check that the screw holes in the drain bracket  
and the drain pan outlet are aligned and securely in  
contact, then fasten them with the screw. (After  
attaching the drain hose, check that it is attached  
securely.) (Fig. 40c)  
Clamp  
Drain cap  
Drain cap  
Use a Phillips screwdriver to push the drain cap in  
firmly. (If it is difficult to push in, wet the cap with  
water first.)  
Fig. 40a  
Screw hole  
(3) Install the indoor unit on the rear panel.  
(4) Connect the tubing and wiring led inside from out-  
doors.  
Drain pan outlet  
(5) After completing a leak test, bundle the tubing  
together with armoring tape and store it inside the  
tubing storage area at the back of the indoor unit  
and hold it with clamps. (Figs. 40a and 41)  
Insulation  
Drain bracket  
Drain bracket  
Screw  
Drain hose  
Drain hose  
Fig. 40c  
Fig. 40b  
Refrigerant tubing  
Inter-unit wiring  
Conduit  
Fig. 41  
14  
To unmount indoor unit  
Press the 2 L marks on the lower part of the indoor unit  
and unlatch the tabs. Then lift the indoor unit and  
unmount. (Fig. 42)  
3-9. Drain Hose  
a) The drain hose should be slanted downward to the  
outdoors. (Fig. 43)  
b) Never form a trap in the course of the hose.  
c) If the drain hose will run in the room, insulate the  
hose with insulation* so that chilled condensation  
will not damage furniture or floors. (Fig. 44)  
Push  
* Foamed polyethylene or its equivalent is recom-  
Fig. 42  
mended.  
Do not supply power to the  
WARNING  
unit or operate it until all  
tubing and wiring to the out-  
side unit are completed.  
Slant  
Indoor  
unit  
Drain  
hose  
Risk of Electric Shock  
Fig. 43  
Condensation  
Insulation material  
(Locally purchased)  
must be used.  
Fig. 44  
15  
4. How to Test Run the Air Conditioner  
After turning on power to the air conditioner, use the remote  
controller and follow the steps below to conduct the test run.  
(1) Set the remote controller in Test Run mode.  
(Fig. 59a)  
a) Press and hold the ION button.  
b) Then press and hold the 1HR TIMER button.  
c) At the same time, press the ACL (reset) button once.  
Use a pointed object such as the tip of a pen to press  
the ACL button.  
ON/OFF  
operation  
button  
ION  
button  
• After a few seconds, “ ” appears and “oP-1” blinks in  
the remote controller display area.  
(Fig. 59b)  
1HR.  
TIMER  
button  
d) Release the 1HR TIMER button.  
e) Release the ION button.  
(2) Start Cooling mode test run by pressing the ON/OFF  
operation button of the remote controller. (Fig. 59a)  
• This starts the fan producing uncooled forced air with  
the 4 indicator lamps (OPERATION lamp, TIMER  
lamp, QUIET lamp, and ION lamp) on the main unit  
blinking. (Fig. 59c)  
• After 3 minutes, the system shifts into cooling opera-  
tion, and cool air will start to be felt. Cool mode test  
run is unaffected by the room temperature.  
ACL  
A
(Reset)  
button  
Fig. 59a  
(3) Press the ON/OFF operation button of the remote con-  
troller again to stop the test run. (Fig. 59a)  
(4) Finally press the ACL (reset) button of the remote con-  
troller to release it from Test Run mode to return to nor-  
mal mode. (Fig. 59a)  
• “ ” and “oP-1” will disappear from the remote con-  
troller display area.  
IMPORTANT  
After the test run is completed, be sure to press the ACL  
(reset) button to return to normal mode. The air conditioner  
will not operate correctly if this is not done.  
Fig. 59b  
OPERATION lamp  
TIMER lamp  
QUIET lamp  
ION lamp  
Fig. 59c  
16  
5. Remote Control Unit Installation Position  
The remote control unit can be operated from either a  
non-fixed position or a wall-mounted position.  
To ensure that the air conditioner operates correctly, do  
not install the remote control unit in the following places:  
G In direct sunlight  
G Behind a curtain or other place where it is covered  
G More than 26' (8 m) away from the air conditioner  
G In the path of the air conditioner’s airstream  
G Where it may become extremely hot or cold  
G Where it may be subject to electrical or magnetic  
interference  
G Where there is an obstacle between the remote con-  
trol unit and the air conditioner (since a check signal  
is sent from the remote control unit every 5 minutes)  
5-1. Mounting on a Wall  
Before mounting the remote control unit, press the  
ON/OFF operation button at the mounting location to  
make sure that the air conditioner operates from that  
location. The indoor unit should make a beeping sound  
to indicate that it has received the signal.  
Rear side  
Remote control unit mount  
Press  
Mounting screws  
5/32 × 5/8" (4 × 16 mm)  
(Included)  
Hole  
Set in  
place  
To prevent loss of the remote control  
unit, you can connect the remote  
control unit to the mount by passing  
a string through the remote control  
unit and attachment hole.  
To take out the remote control unit, pull it forward.  
Fig. 61  
17  
6. Address Switch  
Tab  
6-1. Address Setting of the Remote Control Unit  
The address can be set in order to prevent interference  
between remote controllers when two Sanyo indoor units  
are installed near each other. The address is normally  
set to “A.” To set a different address, it is necessary to  
change the address on the second remote controller.  
Fig. 62  
NOTE  
Once changed, you cannot restore the original address  
setting of the air conditioner.  
(1) Switch on the power source.  
(2) Break the address-setting tab marked “A” on the  
second remote controller to change the address  
(Fig. 62). When the tab is removed, the address is  
automatically set to B (Fig. 63).  
ACL button  
(3) Press and hold the remote controller ION button and  
1 HR TIMER button. At the same time, press the  
ACL(reset) button. Use a thin object such as the tip  
of a pen to press the ACL button. When this has  
been done, “oP-1” (test run) appears, blinking, in the  
remote controller clock display area.  
Fig. 63  
(4) Each time the 1 HR TIMER button is pressed, the  
display changes as shown below. Press this button  
2 times to change the display to “oP-7” (address  
setting). (Fig. 64)  
Test run mode  
Selfdiagnostic mode  
Adress setting mode  
ON/OFF  
operation  
button  
ION  
button  
(5) “oP-7” has now been selected for address setting.  
1HR.  
(6) Press the ON/OFF operation button on the remote  
controller. (Fig. 64) Check that the “beep”signal-  
received sound is heard from the second indoor unit  
(approximately 5 times). The sound you hear is the  
signal that the remote controller address has been  
changed.  
TIMER  
button  
(7) Finally press the remote controller ACL (reset) but-  
ton to cancel the blinking “oP-7” display.  
(Fig. 64)  
Changing of the second remote controller address is  
now completed.  
ACL  
A
(Reset)  
button  
Fig. 64  
18  
7. Connecting a Home Automation device  
The HA (white) 4P terminal is located on the indoor unit PCB. If a HA device will  
be used, connect it to this terminal.  
8. Installation Check Sheet  
The strength of the installation location is sufficient to support the A/C weight.  
The indoor and outdoor units are installed level and vertically.  
The power and voltage are as specified.  
Inter-unit cables are securely inserted into the  
terminal block.  
Inter-unit cables are securely fixed.  
The power cord and inter-unit cables are not connected anywhere along their  
paths.  
The ground wire is securely connected.  
Thermal insulation has been applied to the tubing connections.  
Drain connections are secure and water drains properly.  
Putty has been used to close the hole in the wall.  
Remote controller signals are being positively received.  
19  

Lexmark X463de User Manual
Mitsubishi Electronics Mitsubishi Digital Electronics Air Conditioner Msz Ana User Manual
Newair Ac 14100e User Manual
Nextel Comm Brr L User Manual
Ricoh Aficio Is 2425 User Manual
Sharp Mx Fr18u User Manual
Toshiba Air Conditioner Rav Sm1606bt Tr User Manual
Trion M1100 User Manual
Webasto Automobile Parts Blue Bird Scholastic Series School Bus Heater User Manual
Xantrex Technology Rs3000 User Manual