Sanyo Ch1872 User Manual

TECHNICAL & SERVICE MANUAL  
KHS1872 + CH1872  
KHS2472 + CH2472  
FILE NO.  
Destination: North America  
DC INVERTER SPLIT SYSTEM AIR CONDITIONER  
Indoor Model No. Product Code No.  
Outdoor Model No. Product Code No.  
KHS1872  
KHS2472  
1 852 099 85  
1 852 099 86  
CH1872  
CH2472  
1 852 330 38  
1 852 330 39  
Indoor Unit  
Outdoor Unit  
KHS1872  
KHS2472  
CH1872  
IMPORTANT  
These air conditioners employ new  
refrigerant R410A.  
Pay special attention when  
servicing the unit.  
CH2472  
REFERENCE NO. SM700656-05  
Table of Contents  
Page  
5
1. OPERATING RANGE ...................................................................................................................  
2. SPECIFICATIONS  
2-1. Unit Specifications .............................................................................................................  
6
2-2. Major Component Specifications ....................................................................................... 10  
2-3. Other Component Specifications ....................................................................................... 14  
3. DIMENSIONAL DATA ..................................................................................................................... 15  
4. REFRIGERANT FLOW DIAGRAM  
4-1. Refrigerant Flow Diagram ................................................................................................... 18  
5. PERFORMANCE DATA  
5-1. Temperature Charts ............................................................................................................ 19  
5-2. Cooling Capacity ................................................................................................................ 23  
5-3. Cooling Capacity (Low Ambient) ......................................................................................... 25  
5-4. Heating Capacity ................................................................................................................ 27  
5-5. Air Throw Distance Charts ................................................................................................. 29  
6. ELECTRICAL DATA  
6-1. Electrical Characteristics .................................................................................................... 31  
6-2. Electric Wiring Diagrams .................................................................................................... 33  
7. MAINTENANCE  
7-1. Address Setting of the Remote Control Unit ....................................................................... 36  
7-2. Disconnecting and Connecting Positive Connector for Outdoor Unit .................................. 37  
8. FUNCTIONS  
8-1. Operation Functions ........................................................................................................... 38  
8-2. Protective Functions ........................................................................................................... 40  
9. TROUBLESHOOTING  
9-1. Precautions before Performing Inspection or Repair ........................................................... 42  
9-2. Method of Self-Diagnostics ................................................................................................. 42  
9-3. Checking the Indoor and Outdoor Units .............................................................................. 45  
9-4. Trouble Diagnosis of Fan Motor ........................................................................................... 49  
9-5. Noise Malfunction and Electromagnetic Interference .......................................................... 51  
3
Page  
10. CHECKING ELECTRICAL COMPONENTS  
10-1. Measurement of Insulation Resistance ............................................................................... 52  
10-2. Checking Continuity of Fuse on PCB Ass'y ......................................................................... 53  
11. REFRIGERANT R410A:  
SPECIAL PRECAUTIONS WHEN SERVICING UNIT  
11-1. Characteristics of New Refrigerant R410A ......................................................................... 54  
11-2. Checklist before Servicing ................................................................................................... 55  
11-3. Tools Specifically for R410A ................................................................................................ 56  
11-4. Tubing Installation Procedures ............................................................................................ 56  
11-5. In Case of Compressor Malfunction .................................................................................... 57  
11-6. In Case Refrigerant is Leaking ............................................................................................ 59  
11-7. Charging Additional Refrigerant .......................................................................................... 60  
11-8. Retro-Fitting Existing Systems ............................................................................................ 60  
APPENDIX A INSTRUCTION MANUAL .......................................................................................... A-1  
APPENDIX B INSTALLAION INSTRUCTIONS ............................................................................... A-2  
4
1. OPERATING RANGE  
Temperature  
Indoor Air Intake Temp.  
95 °F D.B. / 71 °F W.B.  
67 °F D.B. / 57 °F W.B.  
80 °F D.B. / 67 °F W.B.  
Outdoor Air Intake Temp.  
115 °F D.B.  
Maximum  
Cooling  
Minimum  
0 °F D.B.  
Maximum  
Heating  
Minimum  
75 °F D.B. / 65 °F W.B.  
0 °F D.B.  
_
_
D.B. / W.B.  
5
2. SPECIFICATIONS  
2-1. Unit Specifications  
Indoor Unit  
KHS1872  
Outdoor Unit CH1872  
< 230V >  
Voltage Rating  
230V Single-Phase 60Hz  
Cooling Heating  
BTU/h 17,500 ( 4,000 to 17,500 )  
Total Capacity  
20,400 ( 4,400 to 20,400 )  
kW  
5.15 ( 1.2 to 5.15 )  
13,100  
6.0 ( 1.3 to 6.0 )  
Sensible Capacity  
Latent Capacity  
Air Circulation (High)  
Moisture Removal (High)  
Available Voltage Range  
Running Amperes  
Power Input  
-
BTU/h  
BTU/h  
4,400  
-
ft3/min (m3/h)  
524 (890)  
4.89  
541 (920)  
-
Pints/h  
V
187 to 253  
A
W
7.0  
( 1.2 to 7.0 )  
7.4 ( 1.3 to 7.4 )  
1,500 ( 250 to 1,500 )  
1,575 ( 270 to 1,575 )  
Power Factor  
%
93  
11.7  
-
93  
-
EER  
BTU/h/W  
W/W  
BTU/Wh  
BTU/Wh  
A
COP  
3.81  
-
SEER  
20  
-
HSPF  
10  
Compressor Locked Rotor Amperes  
Fuse or Circuit Breaker Capacity  
Controls / Temperature Control  
Control Unit  
17.5  
20  
A
Microprocessor / I.C. Thermister  
Wireless Remote Control Unit  
24-Hour ON or OFF Timer, 1-Hour OFF Timer  
Auto and 3 steps / Auto (Hi, Me, Lo)  
Manual  
Timer  
Fan Speeds  
Indoor / Outdoor  
Horizontal  
Airflow Direction (Indoor)  
Vertical  
Auto  
Air Filter  
Washable, Anti-Mold  
Compressor  
DC Twin Rotary (Inverter)  
R410A / 2.87 (1,300)  
Refrigerant / Amount charged at shipment  
Refrigerant Control  
Ibs (g)  
Electric Expansion Valve  
Operation Sound  
Indoor : Hi/Me/Lo/Qt*  
Outdoor : Hi  
dB-A  
dB-A  
42 / 38 / 30 / 28  
51  
41 / 38 / 30 / 28  
52  
(*Qt = Quiet mode)  
Refrigerant Tubing Connections  
Flare Type  
25 (7.5)  
Max. allowable tubing length at shipment  
ft (m)  
inch (mm)  
inch (mm)  
Refrigerant  
Narrow tube  
Wide tube  
1/4 (6.35)  
1/2 (12.7)  
Tube Diameter  
Refrigerant Tube Kit / Accessories  
Optional / Air Clean Filter  
Indoor Unit Outdoor Unit  
inch 11-23/32 × 41-15/16 × 8-19/32 26-3/8 × 34-21/32 × 11-7/32  
Unit Dimensions  
Height × Width × Depth  
Package Dimensions  
Height × Width × Depth  
(mm)  
inch  
(298 × 1,065 × 218)  
11-3/8 × 44-7/8 × 14-29/32  
(289 × 1,140 × 379)  
26.5 (12.0)  
(670 × 880 × 285)  
29-1/8 × 39-27/32 × 14-31/32  
(740 × 1,012 × 380)  
97.0 (44.0)  
(mm)  
Weight  
Net  
Ibs (kg)  
Ibs (kg)  
cu.ft (m3)  
Shipping  
33.1 (15.0)  
105.8 (48.0)  
Shipping Volume  
4.23 (0.12)  
9.88 (0.28)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
Remarks: Rating conditions are:  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Outdoor air temperature 95°F D.B. / 75°F W.B.  
Heating: Indoor air temperature 70°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
6
Indoor Unit  
KHS1872  
Outdoor Unit CH1872  
< 208V >  
Voltage Rating  
208V Single-Phase 60Hz  
Cooling Heating  
BTU/h 17,500 ( 4,000 to 17,500 )  
Total Capacity  
20,400 ( 4,400 to 20,400 )  
kW  
5.15 ( 1.2 to 5.15 )  
13,100  
6.0 ( 1.3 to 6.0 )  
Sensible Capacity  
Latent Capacity  
Air Circulation (High)  
Moisture Removal (High)  
Available Voltage Range  
Running Amperes  
Power Input  
-
BTU/h  
BTU/h  
4,400  
-
ft3/min (m3/h)  
524 (890)  
4.89  
541 (920)  
-
Pints/h  
V
187 to 253  
A
W
7.7  
( 1.2 to 7.7 )  
8.1 ( 1.3 to 8.1 )  
1,500 ( 250 to 1,500 )  
1,575 ( 270 to 1,575 )  
Power Factor  
%
94  
11.7  
-
93  
-
EER  
BTU/h/W  
W/W  
BTU/Wh  
BTU/Wh  
A
COP  
3.81  
-
SEER  
20  
-
HSPF  
10  
Compressor Locked Rotor Amperes  
Fuse or Circuit Breaker Capacity  
Controls / Temperature Control  
Control Unit  
17.5  
20  
A
Microprocessor / I.C. Thermister  
Wireless Remote Control Unit  
24-Hour ON or OFF Timer, 1-Hour OFF Timer  
Auto and 3 steps / Auto (Hi, Me, Lo)  
Manual  
Timer  
Fan Speeds  
Indoor / Outdoor  
Horizontal  
Airflow Direction (Indoor)  
Vertical  
Auto  
Air Filter  
Washable, Anti-Mold  
Compressor  
DC Twin Rotary (Inverter)  
R410A / 2.87 (1,300)  
Refrigerant / Amount charged at shipment  
Refrigerant Control  
Ibs (g)  
Electric Expansion Valve  
Operation Sound  
Indoor : Hi/Me/Lo/Qt*  
Outdoor : Hi  
dB-A  
dB-A  
42 / 38 / 30 / 28  
51  
41 / 38 / 30 / 28  
52  
(*Qt = Quiet mode)  
Refrigerant Tubing Connections  
Flare Type  
25 (7.5)  
Max. allowable tubing length at shipment  
ft (m)  
inch (mm)  
inch (mm)  
Refrigerant  
Narrow tube  
Wide tube  
1/4 (6.35)  
1/2 (12.7)  
Tube Diameter  
Refrigerant Tube Kit / Accessories  
Optional / Air Clean Filter  
Indoor Unit Outdoor Unit  
inch 11-23/32 × 41-15/16 × 8-19/32 26-3/8 × 34-21/32 × 11-7/32  
Unit Dimensions  
Height × Width × Depth  
Package Dimensions  
Height × Width × Depth  
(mm)  
inch  
(298 × 1,065 × 218)  
11-3/8 × 44-7/8 × 14-29/32  
(289 × 1,140 × 379)  
26.5 (12.0)  
(670 × 880 × 285)  
29-1/8 × 39-27/32 × 14-31/32  
(740 × 1,012 × 380)  
97.0 (44.0)  
(mm)  
Weight  
Net  
Ibs (kg)  
Ibs (kg)  
cu.ft (m3)  
Shipping  
33.1 (15.0)  
105.8 (48.0)  
Shipping Volume  
4.23 (0.12)  
9.88 (0.28)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
Remarks: Rating conditions are:  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Outdoor air temperature 95°F D.B. / 75°F W.B.  
Heating: Indoor air temperature 70°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
7
Indoor Unit  
KHS2472  
Outdoor Unit CH2472  
< 230V >  
Voltage Rating  
230V Single-Phase 60Hz  
Cooling Heating  
BTU/h 24,200 ( 4,000 to 24,200 )  
Total Capacity  
29,000 ( 4,400 to 29,000 )  
kW  
7.1  
( 1.2 to 7.1 )  
14,800  
8.5 ( 1.3 to 8.5 )  
Sensible Capacity  
Latent Capacity  
Air Circulation (High)  
Moisture Removal (High)  
Available Voltage Range  
Running Amperes  
Power Input  
-
BTU/h  
BTU/h  
9,400  
-
ft3/min (m3/h)  
600 (1,020)  
4.89  
653 (1,110)  
-
Pints/h  
V
187 to 253  
A
W
10.8 ( 1.3 to 10.8 )  
12.0 ( 1.3 to 12.0 )  
2,355 ( 280 to 2,355 )  
2,490 ( 290 to 2,490 )  
Power Factor  
%
95  
10.3  
-
90  
-
EER  
BTU/h/W  
W/W  
BTU/Wh  
BTU/Wh  
A
COP  
3.41  
-
SEER  
17  
-
HSPF  
8.5  
Compressor Locked Rotor Amperes  
Fuse or Circuit Breaker Capacity  
Controls / Temperature Control  
Control Unit  
17.5  
20  
A
Microprocessor / I.C. Thermister  
Wireless Remote Control Unit  
24-Hour ON or OFF Timer, 1-Hour OFF Timer  
Auto and 3 steps / Auto (Hi, Me, Lo)  
Manual  
Timer  
Fan Speeds  
Indoor / Outdoor  
Horizontal  
Airflow Direction (Indoor)  
Vertical  
Auto  
Air Filter  
Washable, Anti-Mold  
Compressor  
DC Twin Rotary (Inverter)  
R410A / 4.30 (1,950)  
Refrigerant / Amount charged at shipment  
Refrigerant Control  
Ibs (g)  
Electric Expansion Valve  
Operation Sound  
Indoor : Hi/Me/Lo/Qt*  
Outdoor : Hi  
dB-A  
dB-A  
47 / 44 / 41 / 30  
55  
46 / 43 / 40 / 30  
56  
(*Qt = Quiet mode)  
Refrigerant Tubing Connections  
Flare Type  
33 (10)  
Max. allowable tubing length at shipment  
ft (m)  
inch (mm)  
inch (mm)  
Refrigerant  
Narrow tube  
Wide tube  
1/4 (6.35)  
5/8 (15.88)  
Tube Diameter  
Refrigerant Tube Kit / Accessories  
Optional / Air Clean Filter  
Indoor Unit Outdoor Unit  
inch 11-23/32 × 41-15/16 × 8-19/32 29-1/8 × 35-7/16 × 12-19/32  
Unit Dimensions  
Height × Width × Depth  
Package Dimensions  
Height × Width × Depth  
(mm)  
inch  
(298 × 1,065 × 218)  
11-3/8 × 44-7/8 × 14-29/32  
(289 × 1,140 × 379)  
26.5 (12.0)  
(740 × 900 × 320)  
33-27/32 × 40-5/8 × 16-1/4  
(860 × 1,032 × 413)  
130.1 (59.0)  
(mm)  
Weight  
Net  
Ibs (kg)  
Ibs (kg)  
cu.ft (m3)  
Shipping  
33.1 (15.0)  
138.9 (63.0)  
Shipping Volume  
4.23 (0.12)  
12.71 (0.36)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
Remarks: Rating conditions are:  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Outdoor air temperature 95°F D.B. / 75°F W.B.  
Heating: Indoor air temperature 70°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
8
Indoor Unit  
KHS2472  
Outdoor Unit CH2472  
< 208V >  
Voltage Rating  
208V Single-Phase 60Hz  
Cooling Heating  
BTU/h 24,200 ( 4,000 to 24,200 )  
Total Capacity  
29,000 ( 4,400 to 29,000 )  
kW  
7.1  
( 1.2 to 7.1 )  
14,800  
8.5 ( 1.3 to 8.5 )  
Sensible Capacity  
Latent Capacity  
Air Circulation (High)  
Moisture Removal (High)  
Available Voltage Range  
Running Amperes  
Power Input  
-
BTU/h  
BTU/h  
9,400  
-
ft3/min (m3/h)  
600 (1,020)  
4.89  
653 (1,110)  
-
Pints/h  
V
187 to 253  
A
W
12.1 ( 1.3 to 12.1 )  
13.5 ( 1.3 to 13.5 )  
2,355 ( 280 to 2,355 )  
2,490 ( 290 to 2,490 )  
Power Factor  
%
94  
10.3  
-
89  
-
EER  
BTU/h/W  
W/W  
BTU/Wh  
BTU/Wh  
A
COP  
3.41  
-
SEER  
17  
-
HSPF  
8.5  
Compressor Locked Rotor Amperes  
Fuse or Circuit Breaker Capacity  
Controls / Temperature Control  
Control Unit  
17.5  
20  
A
Microprocessor / I.C. Thermister  
Wireless Remote Control Unit  
24-Hour ON or OFF Timer, 1-Hour OFF Timer  
Auto and 3 steps / Auto (Hi, Me, Lo)  
Manual  
Timer  
Fan Speeds  
Indoor / Outdoor  
Horizontal  
Airflow Direction (Indoor)  
Vertical  
Auto  
Air Filter  
Washable, Anti-Mold  
Compressor  
DC Twin Rotary (Inverter)  
R410A / 4.30 (1,950)  
Refrigerant / Amount charged at shipment  
Refrigerant Control  
Ibs (g)  
Electric Expansion Valve  
Operation Sound  
Indoor : Hi/Me/Lo/Qt*  
Outdoor : Hi  
dB-A  
dB-A  
47 / 44 / 41 / 30  
55  
46 / 43 / 40 / 30  
56  
(*Qt = Quiet mode)  
Refrigerant Tubing Connections  
Flare Type  
33 (10)  
Max. allowable tubing length at shipment  
ft (m)  
inch (mm)  
inch (mm)  
Refrigerant  
Narrow tube  
Wide tube  
1/4 (6.35)  
5/8 (15.88)  
Tube Diameter  
Refrigerant Tube Kit / Accessories  
Optional / Air Clean Filter  
Indoor Unit Outdoor Unit  
inch 11-23/32 × 41-15/16 × 8-19/32 29-1/8 × 35-7/16 × 12-19/32  
Unit Dimensions  
Height × Width × Depth  
Package Dimensions  
Height × Width × Depth  
(mm)  
inch  
(298 × 1,065 × 218)  
11-3/8 × 44-7/8 × 14-29/32  
(289 × 1,140 × 379)  
26.5 (12.0)  
(740 × 900 × 320)  
33-27/32 × 40-5/8 × 16-1/4  
(860 × 1,032 × 413)  
130.1 (59.0)  
(mm)  
Weight  
Net  
Ibs (kg)  
Ibs (kg)  
cu.ft (m3)  
Shipping  
33.1 (15.0)  
138.9 (63.0)  
Shipping Volume  
4.23 (0.12)  
12.71 (0.36)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
Remarks: Rating conditions are:  
Cooling: Indoor air temperature 80°F D.B. / 67°F W.B.  
Outdoor air temperature 95°F D.B. / 75°F W.B.  
Heating: Indoor air temperature 70°F D.B.  
Outdoor air temperature 47°F D.B. / 43°F W.B.  
9
2-2. Major Component Specifications  
2-2-1. Indoor Unit  
Indoor Unit  
KHS1872  
Control PCB  
Part No.  
Controls  
CB-KHS1872  
Microprocessor  
250V 3A  
Control Circuit Fuse  
Remote Control Unit  
RCS-4HVPIS4U  
Fan  
Type  
Cross-Flow  
Q'ty ... Dia. and Length  
inch (mm)  
1 ... D3-11/16 / L33-9/32 (D94/L845)  
Fan Motor  
Type  
DC Motor  
Model ... Q'ty  
SIC-39CVL-D847-2-A ... 1  
No. of Poles  
8
Rough Measure RPM (Cool / Heat)  
Nominal Output  
Coil Resistance  
1,250 / 1,300  
W
30  
-
Ohm  
(Ambient Temp. 68 °F (20 °C))  
Safety Device  
Type  
Internal Controller  
Over-Current Protection  
Over-Heat Protection  
Run Capacitor  
Yes  
Yes  
Micro F  
VAC  
-
-
Flap Motor  
Type  
Stepping Motor  
MP24Z3-12V  
Model  
Rating  
DC 12V  
Coil Resistance  
Ohm  
Each Pair of Terminal : 400 +/- 7%  
(Ambient Temp. 77 °F (25 °C))  
Heat Exchanger Coil  
Coil  
Aluminum Plate Fin / Copper Tube  
Rows  
2
Fins Per inch  
Face Area  
19.5  
ft2 (m2)  
3.07 (0.285)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
10  
Indoor Unit  
KHS2472  
Control PCB  
Part No.  
Controls  
CB-KHS2472  
Microprocessor  
250V 3A  
Control Circuit Fuse  
Remote Control Unit  
RCS-4HVPIS4U  
Fan  
Type  
Cross-Flow  
Q'ty ... Dia. and Length  
inch (mm)  
1 ... D3-11/16 / L33-9/32 (D94/L845)  
Fan Motor  
Type  
DC Motor  
Model ... Q'ty  
SIC-39CVL-D847-2-A ... 1  
No. of Poles  
8
Rough Measure RPM (Cool / Heat)  
Nominal Output  
Coil Resistance  
1,500 / 1,550  
W
30  
-
Ohm  
(Ambient Temp. 68 °F (20 °C))  
Safety Device  
Type  
Internal Controller  
Over-Current Protection  
Over-Heat Protection  
Run Capacitor  
Yes  
Yes  
Micro F  
VAC  
-
-
Flap Motor  
Type  
Stepping Motor  
MP24Z3-12V  
Model  
Rating  
DC 12V  
Coil Resistance  
Ohm  
Each Pair of Terminal : 400 +/- 7%  
(Ambient Temp. 77 °F (25 °C))  
Heat Exchanger Coil  
Coil  
Aluminum Plate Fin / Copper Tube  
Rows  
2
Fins Per inch  
Face Area  
19.5  
ft2 (m2)  
3.07 (0.285)  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
11  
2-2-2. Outdoor Unit  
Outdoor Unit CH1872  
Control PCB  
Part No.  
CB-CH1872  
Microprocessor  
250V 25A  
Controls  
Control Circuit Fuse  
Compressor  
Type  
DC Twin Rotary (Hermetic)  
C-6RVN93H0M / 1,050W  
FV50S ... 0.74 (350)  
R - S : 0.482  
Compressor Model / Nominal Output  
Compressor Oil ... Amount  
Pints (cc)  
Coil Resistance (Ambient Temp. 68 °F (20 °C)) Ohm  
S - T : 0.482  
T - R : 0.482  
Safety Device  
CT (Peak current cut-off control)  
Compressor Discharge Temp. Control  
Operation cut-off control in abnormal ambient Temp.  
Yes  
Yes  
Yes  
Overload Relay  
Model  
Operation Temp.  
Micro F  
CS-7L115  
Open : 239 °F (115 °C), Close : 203 °F (95 °C)  
Run Capacitor  
-
-
-
VAC  
Crankcase Heater  
Fan  
Type  
Propeller  
Q'ty ... Dia.  
inch (mm)  
1 ... D16-17/32 (D420)  
Fan Motor  
Type  
DC Motor  
Model ... Q'ty  
DAJ12-55J71A-CU ... 1  
No. of Poles  
8
820 / 850  
50  
Rough Measure RPM (Cool / Heat)  
Nominal Output  
W
Coil Resistance  
Ohm  
RED - WHT : 77.5  
WHT - BLU : 77.5  
BLU - RED : 77.5  
(Ambient Temp. 68 °F (20 °C))  
Safety Device  
Type  
Internal Controller  
Over- Current Protection  
Run Capacitor  
Yes  
Micro F  
VAC  
-
-
Heat Exchanger Coil  
Coil  
Aluminum Plate Fin / Copper Tube  
Rows  
2
Fins per inch  
Face Area  
21.2  
ft2 (m2)  
5.49 (0.510)  
External Finish  
Acrylic baked-on enamel finish  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
12  
Outdoor Unit CH2472  
Control PCB  
Part No.  
CB-CH2472  
Microprocessor  
250V 25A  
Controls  
Control Circuit Fuse  
Compressor  
Type  
DC Twin Rotary (Hermetic)  
G8T265FU1JW / 2,410W  
FV50S ... 1.49 (700)  
U - V : 0.36  
Compressor Model / Nominal Output  
Compressor Oil ... Amount  
Pints (cc)  
Coil Resistance (Ambient Temp. 68 °F (20 °C)) Ohm  
V - W : 0.36  
W - U : 0.36  
Safety Device  
CT (Peak current cut-off control)  
Compressor Discharge Temp. Control  
Operation cut-off control in abnormal ambient Temp.  
Yes  
Yes  
Yes  
Overload Relay  
Model  
Operation Temp.  
Micro F  
CS-7L115  
Open : 239 °F (115 °C), Close : 203 °F (95 °C)  
Run Capacitor  
-
VAC  
-
Crankcase Heater  
230V 30W  
Fan  
Type  
Propeller  
Q'ty ... Dia.  
inch (mm)  
1 ... D18-1/8 (D460)  
Fan Motor  
Type  
DC Motor  
Model ... Q'ty  
SIC-71FW-D490-1 ... 1  
No. of Poles  
8
850 / 850  
90  
Rough Measure RPM (Cool / Heat)  
Nominal Output  
W
Coil Resistance  
Ohm  
-
(Ambient Temp. 68 °F (20 °C))  
Safety Device  
Type  
Internal Controller  
Over- Current Protection  
Over- Heat Protection  
Run Capacitor  
Yes  
Yes  
Micro F  
VAC  
-
-
Heat Exchanger Coil  
Coil  
Aluminum Plate Fin / Copper Tube  
Rows  
2
Fins per inch  
Face Area  
18.1  
ft2 (m2)  
6.40 (0.595)  
External Finish  
Acrylic baked-on enamel finish  
DATA SUBJECT TO CHANGE WITHOUT NOTICE.  
13  
2-3. Other Component Specifications  
Indoor Unit  
KHS1872  
KHS2472  
Outdoor Unit CH1872  
CH2472  
• Indoor heat exchanger sensor  
(Model:PTM-D51H-S3-2 TH1)  
• Compressor temp sensor  
(Model:TKS293B)  
• Indoor air temp sensor  
(Model:PTM-D51H-S3-2 TH2)  
10  
9
8
7
6
5
4
3
2
1
0
200  
180  
160  
140  
120  
100  
80  
60  
40  
20  
0
50 59 68 77 86 95 104  
(10) (15) (20) (25) (30) (35) (40)  
32 50 68 86 104 122 140 158 176 194  
(0) (10)(20) (30) (40)(50) (60) (70)(80) (90)  
Temperature °F (°C)  
Temperature °F (°C)  
• Outdoor air temp sensor  
(Model:TKS295B)  
• Outdoor heat exchanger sensor  
(Model:TKS292B)  
40  
35  
30  
25  
20  
15  
10  
5
0
-
-
4
20)(  
5
14 23 32 41 50 59 68  
10) ( 5) (0) (5) (10) (15) (20)  
Temperature °F (°C)  
(
-
15)(  
-
-
14  
3. DIMENSIONAL DATA  
Indoor Unit  
KHS1872  
KHS2472  
Unit: inch(mm)  
15  
Outdoor Unit CH1872  
23-15/16  
5-11/32  
15/32  
11-17/32  
Wide tube service valve  
dia.1/2" (12.70)  
34-21/32(880)  
2-17/32  
Narrow tube service valve  
dia.1/4" (6.35)  
3/32  
5-23/32  
1-13/16  
2-13/32  
Unit: inch(mm)  
16  
Outdoor Unit CH2472  
23-15/16  
5-11/32  
15/32  
11-17/32  
Narrow tube service valve  
dia.1/4" (6.35)  
35-7/16(900)  
2-15/16  
Wide tube service valve  
dia.5/8" (15.88)  
2-1/32  
4-1/2  
1-21/32  
2-7/8  
Unit: inch(mm)  
17  
4. REFRIGERANT FLOW DIAGRAM  
4-1. Refrigerant Flow Diagram  
Indoor Unit  
KHS1872  
KHS2472  
Outdoor Unit CH1872  
CH2472  
Indoor unit  
Outdoor unit  
Accumulator  
Wide tube  
service  
valve  
Wide tube  
*1  
High pressure  
switch  
Muffler  
H.P.  
4-way  
valve  
Capillary  
tube for  
split flow  
Electric  
expansion  
valve  
Narrow  
tube  
service  
valve  
M
Narrow tube  
Cooling cycle  
(Defrosting cycle)  
Strainer  
O.D.  
1/4"  
(6.35 mm)  
Heating cycle  
*1 O.D.1/2"(12.7 mm) ......... 1872 class  
O.D.5/8"(15.88 mm) ......... 2472 class  
Insulation of Refrigerant Tubing  
IMPORTANT  
Because capillary tubing is used in the outdoor unit, both the  
wide and narrow tubes of this air conditioner become cold. To  
prevent heat loss and wet floors due to dripping of  
condensation, both tubes must be well insulated with a  
proper insulation material. The thickness of the insulation  
should be a min. 5/16"(8 mm).  
Insulation  
Thickness:  
Min. 5/16"(8 mm)  
Thickness:  
Min. 5/16"(8 mm)  
Narrow tube  
After a tube has been insulated,  
Wide tube  
never try to bend it into a narrow  
CAUTION  
curve because it can cause the tube  
to break or crack.  
18  
5. PERFORMANCE DATA  
5-1. Temperature Charts  
Indoor Unit  
KHS1872  
Outdoor Unit CH1872  
Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)  
(1) Low pressure performance chart  
174  
(1.2)  
Lo fan  
Hi Fan  
159  
(1.1)  
145  
(1.0)  
131  
(0.9)  
117  
(0.8)  
104  
(0.7)  
90  
(0.6)  
76  
(0.5)  
-4  
(-20)  
5
(-15)  
14  
(-10)  
23  
(-5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
86  
(30)  
95  
(35)  
104  
(40)  
Outdoor inlet air D.B. temp.°F(°C)  
(2) Operating current performance chart  
8
Lo fan  
Hi Fan  
7
6
5
4
3
2
-4  
(-20)  
5
(-15)  
14  
(-10)  
23  
(-5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
86  
(30)  
95  
(35)  
104  
(40)  
Outdoor inlet air D.B. temp.°F(°C)  
(3) Indoor discharge air performance chart  
64.4 (18)  
Lo fan  
Hi Fan  
60.8 (16)  
57.2 (14)  
53.6 (12)  
50.0 (10)  
46.4 (8)  
-4  
(-20)  
5
(-15)  
14  
(-10)  
23  
(-5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
86  
(30)  
95  
(35)  
104  
(40)  
Outdoor inlet air D.B. temp.°F(°C)  
NOTE  
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.  
19  
Indoor Unit  
KHS1872  
Outdoor Unit CH1872  
Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)  
(1) High pressure performance chart  
494  
(3.4)  
421  
(2.9)  
348  
(2.4)  
275  
(1.9)  
23  
(–5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
Outdoor inlet air D.B. temp. °F(°C)  
(2) Operating current performance chart  
11  
10  
9
8
7
6
5
23  
(–5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
Outdoor inlet air D.B. temp. °F(°C)  
(3) Indoor discharge air performance chart  
131(55)  
122(50)  
113(45)  
104(40)  
95(35)  
86(30)  
23  
(–5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
Outdoor inlet air D.B. temp. °F(°C)  
NOTE  
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.  
Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in  
heating mode. (Refer to "8-2. Overload prevention during heating.")  
20  
Indoor Unit  
KHS2472  
Outdoor Unit CH2472  
Cooling Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)  
(1) Low pressure performance chart  
174  
(1.2)  
Lo fan  
Hi Fan  
159  
(1.1)  
145  
(1.0)  
131  
(0.9)  
117  
(0.8)  
104  
(0.7)  
90  
(0.6)  
76  
(0.5)  
-4  
(-20)  
5
(-15)  
14  
(-10)  
23  
(-5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
86  
(30)  
95  
(35)  
104  
(40)  
Outdoor inlet air D.B. temp.°F(°C)  
(2) Operating current performance chart  
14  
Lo fan  
Hi Fan  
13  
12  
11  
10  
9
8
7
6
5
4
-4  
(-20)  
5
(-15)  
14  
(-10)  
23  
(-5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
86  
(30)  
95  
(35)  
104  
(40)  
Outdoor inlet air D.B. temp.°F(°C)  
(3) Indoor discharge air performance chart  
68.0 (20)  
Lo fan  
Hi Fan  
64.4 (18)  
60.8 (16)  
57.2 (14)  
53.6 (12)  
50.0 (10)  
46.4 (8)  
42.8 (6)  
-4  
5
(-15)  
14  
(-10)  
23  
(-5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
86  
(30)  
95  
(35)  
104  
(40)  
(-20)  
Outdoor inlet air D.B. temp.°F(°C)  
NOTE  
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.  
21  
Indoor Unit  
KHS2472  
Outdoor Unit CH2472  
Heating Characteristics (RH : 46%, Indoor fan speed : High fan) (60Hz, 230V)  
(1) High pressure performance chart  
494  
(3.4)  
421  
(2.9)  
348  
(2.4)  
275  
(1.9)  
23  
(–5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
Outdoor inlet air D.B. temp. °F(°C)  
(2) Operating current performance chart  
16  
15  
14  
13  
12  
11  
10  
23  
(–5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
Outdoor inlet air D.B. temp. °F(°C)  
(3) Indoor discharge air performance chart  
131(55)  
122(50)  
113(45)  
104(40)  
95(35)  
86(30)  
23  
(–5)  
32  
(0)  
41  
(5)  
50  
(10)  
59  
(15)  
68  
(20)  
77  
(25)  
Outdoor inlet air D.B. temp. °F(°C)  
NOTE  
• Check each performance value in test-run mode. Electrical performance values represent a combined indoor/outdoor value.  
Overload prevention operates to protect the air conditioner when outdoor ambient temperature becomes extremely high in  
heating mode. (Refer to "8-2. Overload prevention during heating.")  
22  
5-2. Cooling Capacity  
Indoor Unit  
: KHS1872  
Outdoor Unit : CH1872  
Power Supply : 230V Single Phase 60Hz  
< Cooling Capacity >  
RATING CAPACITY:  
17,500 BTU/h  
AIR FLOW RATE:  
OUTDOOR  
AMBIENT TEMP. oF (oC)  
524 CFM  
INDOOR  
ENT. TEMP. oF (oC)  
W.B.  
D.B.  
65  
75  
85  
95  
105  
115  
(18.3)  
(23.9)  
(29.4)  
(35.0)  
(40.6)  
(46.1)  
TC  
17,710  
17,180  
16,600  
16,040  
15,320  
10,530  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
13,110  
14,840  
16,670  
17,710  
17,710  
12,910  
14,640  
16,370  
17,180  
17,180  
12,610  
14,340  
16,060  
16,600  
16,600  
12,300  
14,030  
15,860  
16,040  
16,040  
12,000  
13,720  
15,320  
15,320  
15,320  
9,760  
10,530  
10,530  
10,530  
10,530  
59  
(15.0)  
TC  
18,460  
17,920  
17,330  
16,770  
16,040  
10,770  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
11,080  
12,810  
14,640  
16,370  
18,100  
10,880  
12,610  
14,340  
16,060  
17,790  
10,570  
12,300  
14,130  
15,860  
17,330  
10,370  
12,000  
13,830  
15,560  
16,770  
9,960  
11,690  
13,520  
15,250  
16,040  
7,720  
9,450  
63  
(17.2)  
10,770  
10,770  
10,770  
TC  
19,190  
18,650  
18,060  
# 17,500  
16,750  
10,980  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
9,050  
10,780  
12,500  
14,230  
15,960  
8,740  
10,470  
12,300  
14,030  
15,760  
8,540  
10,270  
12,100  
13,830  
15,450  
8,330  
8,030  
9,760  
5,790  
7,520  
67  
10,060  
11,790  
13,520  
15,250  
(19.4)  
11,490  
13,220  
14,950  
9,250  
10,980  
10,980  
TC  
19,880  
19,350  
18,760  
18,220  
17,460  
11,160  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
6,810  
8,540  
6,600  
8,330  
6,400  
8,130  
6,200  
7,930  
9,660  
11,390  
13,110  
5,890  
7,620  
3,650  
5,380  
7,210  
8,940  
10,670  
71  
(21.7)  
10,270  
12,000  
13,720  
10,060  
11,790  
13,520  
9,860  
9,350  
11,590  
13,320  
11,080  
12,810  
TC  
20,470  
19,940  
19,350  
18,830  
18,070  
11,270  
75  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
6,300  
8,130  
9,860  
11,590  
6,200  
7,930  
9,660  
11,390  
5,990  
7,720  
9,450  
11,180  
5,790  
7,620  
9,350  
10,980  
5,490  
7,320  
9,050  
10,780  
3,350  
5,180  
6,910  
8,640  
(23.9)  
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)  
NOTE  
1.  
Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.  
: Outdoor Ambient Temp. 95 °F (35 °C) D.B.  
2.  
Above data does not take Freeze Prevention Protection during cooling operation into account.  
For this reason, the value may vary from the actual cooling characteristics.  
3. Above data represents the value when the operation frequency of a compressor is fixed.  
23  
Indoor Unit  
: KHS2472  
Outdoor Unit : CH2472  
Power Supply : 230V Single Phase 60Hz  
< Cooling Capacity >  
RATING CAPACITY:  
24,200 BTU/h  
AIR FLOW RATE:  
OUTDOOR  
AMBIENT TEMP. oF (oC)  
600 CFM  
INDOOR  
ENT. TEMP. oF (oC)  
W.B.  
D.B.  
65  
75  
85  
95  
105  
115  
(18.3)  
(23.9)  
(29.4)  
(35.0)  
(40.6)  
(46.1)  
TC  
24,430  
23,750  
23,010  
22,310  
18,420  
11,170  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
17,180  
19,050  
21,030  
23,010  
24,430  
16,720  
18,700  
20,680  
22,660  
23,750  
16,370  
18,230  
20,330  
22,200  
23,010  
16,020  
17,880  
19,860  
21,850  
22,310  
13,920  
15,900  
17,880  
18,420  
18,420  
10,540  
11,170  
11,170  
11,170  
11,170  
59  
(15.0)  
TC  
25,360  
24,690  
23,940  
23,260  
18,810  
11,390  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
14,730  
16,600  
18,580  
20,560  
22,430  
14,380  
16,250  
18,230  
20,210  
22,080  
13,920  
15,900  
17,880  
19,860  
21,730  
13,690  
15,550  
17,530  
19,510  
21,380  
11,590  
13,450  
15,430  
17,420  
18,810  
8,320  
10,300  
11,390  
11,390  
11,390  
63  
(17.2)  
TC  
26,250  
25,590  
24,850  
# 24,200  
19,150  
11,590  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
12,170  
14,150  
16,130  
18,000  
19,980  
11,820  
13,800  
15,780  
17,770  
19,630  
11,590  
13,450  
15,430  
17,420  
19,280  
11,240  
13,220  
15,200  
17,070  
19,050  
9,020  
11,000  
12,990  
14,970  
16,830  
6,110  
8,090  
67  
(19.4)  
10,070  
11,590  
11,590  
TC  
27,080  
26,430  
25,700  
25,100  
19,420  
11,740  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
9,490  
11,470  
13,450  
15,320  
17,300  
9,260  
11,120  
13,220  
15,080  
17,070  
8,910  
10,890  
12,870  
14,730  
16,720  
8,670  
6,460  
8,440  
3,780  
5,760  
7,740  
9,720  
11,590  
71  
10,650  
12,640  
14,500  
16,480  
(21.7)  
10,420  
12,290  
14,270  
TC  
27,740  
27,120  
26,410  
25,850  
19,570  
11,830  
75  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
8,790  
10,770  
12,750  
14,620  
8,560  
10,540  
12,520  
14,380  
8,320  
10,300  
12,290  
14,150  
8,090  
5,870  
7,970  
9,840  
11,820  
3,540  
5,520  
7,390  
9,370  
(23.9)  
10,070  
12,050  
13,920  
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)  
NOTE  
1.  
Rating conditions (#) : Indoor Unit Entering Air Temp. 80 °F (26.7 °C) D.B. / 67 °F (19.4 °C) W.B.  
: Outdoor Ambient Temp. 95 °F (35 °C) D.B.  
2.  
Above data does not take Freeze Prevention Protection during cooling operation into account.  
For this reason, the value may vary from the actual cooling characteristics.  
3. Above data represents the value when the operation frequency of a compressor is fixed.  
24  
5-3. Cooling Capacity (Low Ambient)  
Indoor Unit  
: KHS1872  
Outdoor Unit : CH1872  
Power Supply : 230V Single Phase 60Hz  
< Cooling Capacity (Low Ambient) >  
RATING CAPACITY:  
17,500 BTU/h  
AIR FLOW RATE:  
524 CFM  
INDOOR  
ENT. TEMP. oF (oC)  
OUTDOOR  
AMBIENT TEMP. oF (oC)  
W.B.  
D.B.  
0
(-17.8)  
15,050  
5
15  
25  
35  
45  
55  
(-15.0)  
(-9.4)  
(-3.9)  
(1.7)  
(7.2)  
(12.8)  
TC  
15,040  
15,010  
15,140  
15,200  
15,260  
15,230  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
11,790  
13,520  
15,050  
15,050  
15,050  
11,790  
13,520  
15,040  
15,040  
15,040  
11,790  
13,520  
15,010  
15,010  
15,010  
11,890  
13,620  
15,140  
15,140  
15,140  
11,890  
13,620  
15,200  
15,200  
15,200  
11,890  
13,620  
15,260  
15,260  
15,260  
11,890  
13,620  
15,230  
15,230  
15,230  
59  
(15.0)  
TC  
15,050  
15,050  
15,090  
15,350  
15,480  
15,620  
15,640  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
9,550  
11,280  
13,110  
14,740  
15,050  
9,550  
11,280  
13,110  
14,740  
15,050  
9,550  
11,280  
13,110  
14,840  
15,090  
9,660  
11,390  
13,220  
14,950  
15,350  
9,760  
11,490  
13,220  
14,950  
15,480  
9,860  
11,490  
13,320  
15,050  
15,620  
9,860  
11,590  
13,320  
15,050  
15,640  
63  
(17.2)  
TC  
14,890  
14,920  
15,040  
15,460  
15,680  
15,910  
16,000  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
7,210  
8,940  
7,210  
8,940  
7,320  
9,050  
7,520  
9,150  
7,520  
9,250  
7,620  
9,350  
7,720  
9,450  
67  
(19.4)  
10,780  
12,500  
14,230  
10,780  
12,500  
14,230  
10,880  
12,500  
14,230  
10,980  
12,710  
14,440  
11,080  
12,810  
14,540  
11,180  
12,910  
14,640  
11,180  
12,910  
14,640  
TC  
14,550  
14,610  
14,820  
15,440  
15,780  
16,120  
16,290  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
4,880  
6,500  
4,880  
6,600  
4,880  
6,600  
5,180  
6,910  
5,280  
7,010  
5,380  
7,110  
5,490  
7,210  
71  
(21.7)  
8,330  
8,330  
8,440  
8,640  
8,740  
8,940  
8,940  
10,060  
11,790  
10,060  
11,790  
10,160  
11,890  
10,370  
12,100  
10,470  
12,200  
10,670  
12,300  
10,670  
12,400  
TC  
14,050  
14,130  
14,450  
15,300  
15,760  
16,210  
16,470  
75  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
4,260  
5,990  
7,720  
9,450  
4,260  
6,100  
7,830  
9,450  
4,370  
6,200  
7,930  
9,550  
4,670  
6,400  
8,130  
9,860  
4,770  
6,600  
8,330  
10,060  
4,880  
6,710  
8,440  
10,160  
4,980  
6,810  
8,540  
10,270  
(23.9)  
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)  
NOTE  
1.  
Above data does not take Freeze Prevention Protection during cooling operation into account.  
For this reason, the value may vary from the actual cooling characteristics.  
2. Above data represents the value when the operation frequency of a compressor is fixed.  
25  
Indoor Unit  
: KHS2472  
Outdoor Unit : CH2472  
Power Supply : 230V Single Phase 60Hz  
< Cooling Capacity (Low Ambient) >  
RATING CAPACITY:  
24,200 BTU/h  
AIR FLOW RATE:  
600 CFM  
INDOOR  
ENT. TEMP. oF (oC)  
OUTDOOR  
AMBIENT TEMP. oF (oC)  
W.B.  
D.B.  
0
(-17.8)  
20,890  
5
15  
25  
35  
45  
55  
(-15.0)  
(-9.4)  
(-3.9)  
(1.7)  
(7.2)  
(12.8)  
TC  
20,930  
20,770  
20,940  
20,890  
20,850  
20,890  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
15,200  
17,180  
19,160  
20,890  
20,890  
15,200  
17,180  
19,160  
20,930  
20,930  
15,200  
17,070  
19,050  
20,770  
20,770  
15,320  
17,180  
19,160  
20,940  
20,940  
15,200  
17,180  
19,160  
20,890  
20,890  
15,200  
17,180  
19,160  
20,850  
20,850  
15,200  
17,180  
19,160  
20,890  
20,890  
59  
(15.0)  
TC  
20,710  
20,780  
20,760  
21,120  
21,130  
21,160  
21,310  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
12,400  
14,380  
16,370  
18,230  
20,210  
12,400  
14,380  
16,370  
18,350  
20,210  
12,400  
14,380  
16,370  
18,230  
20,210  
12,640  
14,500  
16,480  
18,470  
20,330  
12,640  
14,500  
16,600  
18,470  
20,330  
12,640  
14,500  
16,600  
18,470  
20,450  
12,750  
14,620  
16,600  
18,580  
20,450  
63  
(17.2)  
TC  
20,300  
20,400  
20,560  
21,150  
21,250  
21,360  
21,620  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
9,610  
11,470  
13,450  
15,430  
17,300  
9,610  
11,470  
13,570  
15,430  
17,420  
9,610  
11,590  
13,570  
15,550  
17,420  
9,950  
11,820  
13,800  
15,780  
17,650  
9,950  
11,820  
13,920  
15,780  
17,770  
9,950  
11,940  
13,920  
15,900  
17,770  
10,070  
12,050  
14,040  
16,020  
17,880  
67  
(19.4)  
TC  
19,590  
19,740  
20,120  
21,010  
21,200  
21,410  
21,820  
72 (22.2) SHC  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
6,570  
8,440  
6,570  
8,560  
6,810  
8,670  
7,040  
9,020  
7,160  
9,020  
7,270  
9,140  
7,390  
9,370  
71  
(21.7)  
10,540  
12,400  
14,380  
10,540  
12,520  
14,380  
10,650  
12,640  
14,500  
11,000  
12,990  
14,850  
11,120  
12,990  
14,970  
11,120  
13,100  
14,970  
11,350  
13,220  
15,200  
TC  
18,650  
18,840  
19,490  
20,700  
20,980  
21,310  
21,860  
75  
76 (24.4) SHC  
80 (26.7) SHC  
84 (28.9) SHC  
88 (31.1) SHC  
5,640  
7,620  
9,610  
11,470  
5,640  
7,740  
9,610  
11,590  
5,870  
7,860  
9,840  
11,700  
6,340  
8,320  
6,460  
8,440  
6,460  
8,560  
6,690  
8,670  
(23.9)  
10,190  
12,170  
10,300  
12,290  
10,420  
12,400  
10,650  
12,520  
TC : Total Cooling Capacity (BTU/h) SHC : Sensible Heat Capacity (BTU/h)  
NOTE  
1.  
Above data does not take Freeze Prevention Protection during cooling operation into account.  
For this reason, the value may vary from the actual cooling characteristics.  
2. Above data represents the value when the operation frequency of a compressor is fixed.  
26  
5-4. Heating Capacity  
Indoor Unit  
: KHS1872  
Outdoor Unit : CH1872  
Power Supply : 230V Single Phase 60Hz  
< Heating Capacity >  
RATING CAPACITY:  
20,400 BTU/h  
AIR FLOW RATE:  
541 CFM  
OUTDOOR  
ENT. TEMP. oF (oC)  
INDOOR  
AMBIENT TEMP. oF (oC)  
W.B.  
60  
65  
70  
75  
80  
(15.6)  
(18.3)  
(21.1)  
(23.9)  
(26.7)  
0 (-17.8)  
3 (-16.1)  
8 (-13.3)  
13 (-10.6)  
18 (-7.8)  
23 (-5.0)  
28 (-2.2)  
33 (0.6)  
38 (3.3)  
43 (6.1)  
48 (8.9)  
53 (11.7)  
58 (14.4)  
63 (17.2)  
65 (18.3)  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
11,320  
11,700  
12,620  
13,570  
14,610  
15,710  
16,850  
18,030  
19,200  
20,440  
21,700  
22,970  
24,190  
25,450  
25,930  
11,320  
11,700  
12,610  
13,560  
14,610  
15,700  
16,840  
18,020  
19,190  
20,430  
21,680  
22,940  
24,160  
25,410  
25,900  
11,310  
11,690  
12,600  
13,550  
14,590  
15,690  
16,830  
18,000  
19,170  
20,400  
21,650  
22,910  
24,120  
25,360  
25,850  
11,290  
11,680  
12,590  
13,530  
14,570  
15,660  
16,800  
17,970  
19,130  
20,360  
21,600  
22,860  
24,060  
25,300  
25,780  
11,270  
11,650  
12,560  
13,510  
14,540  
15,630  
16,760  
17,930  
19,090  
20,310  
21,550  
22,790  
23,990  
25,220  
25,700  
#
TH : Total Heating Capacity (BTU/h)  
NOTE  
1.  
Rating conditions (#) : Indoor Unit Entering Air Temp. 70 °F (21.1 °C) D.B.  
: Outdoor Ambient Temp. 47 °F (8.3 °C) D.B. / 43 °F (6.1 °C) W.B.  
2.  
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air  
Prevention Protection during heating operation into account. For this reason, the value may vary  
from the actual heating characteristics.  
3. Above data represents the value when the operation frequency of a compressor is fixed.  
27  
Indoor Unit  
: KHS2472  
Outdoor Unit : CH2472  
Power Supply : 230V Single Phase 60Hz  
< Heating Capacity >  
RATING CAPACITY:  
29,000 BTU/h  
AIR FLOW RATE:  
653 CFM  
OUTDOOR  
ENT. TEMP. oF (oC)  
INDOOR  
AMBIENT TEMP. oF (oC)  
W.B.  
60  
65  
70  
75  
80  
(15.6)  
(18.3)  
(21.1)  
(23.9)  
(26.7)  
0 (-17.8)  
3 (-16.1)  
8 (-13.3)  
13 (-10.6)  
18 (-7.8)  
23 (-5.0)  
28 (-2.2)  
33 (0.6)  
38 (3.3)  
43 (6.1)  
48 (8.9)  
53 (11.7)  
58 (14.4)  
63 (17.2)  
65 (18.3)  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
TH  
16,210  
16,750  
18,050  
19,390  
20,870  
22,420  
24,030  
25,690  
27,330  
29,070  
30,820  
32,580  
34,260  
35,980  
36,640  
16,210  
16,750  
18,050  
19,390  
20,860  
22,410  
24,020  
25,680  
27,320  
29,040  
30,790  
32,540  
34,210  
35,920  
36,580  
16,200  
16,740  
18,040  
19,380  
20,850  
22,390  
24,000  
25,650  
27,280  
29,000  
30,740  
32,470  
34,140  
35,840  
35,780  
16,180  
16,720  
18,010  
19,350  
20,820  
22,360  
23,960  
25,610  
27,230  
28,940  
30,670  
32,390  
34,050  
33,980  
33,880  
16,150  
16,690  
17,980  
19,320  
20,780  
22,320  
23,910  
25,550  
27,160  
28,860  
30,580  
32,300  
32,390  
32,250  
32,150  
#
TH : Total Heating Capacity (BTU/h)  
NOTE  
1.  
Rating conditions (#) : Indoor Unit Entering Air Temp. 70 °F (21.1 °C) D.B.  
: Outdoor Ambient Temp. 47 °F (8.3 °C) D.B. / 43 °F (6.1 °C) W.B.  
2.  
Above data does not take Defrost Operation, Overload Prevention Protection, and/or Cold Air  
Prevention Protection during heating operation into account. For this reason, the value may vary  
from the actual heating characteristics.  
3. Above data represents the value when the operation frequency of a compressor is fixed.  
28  
5-5. Air Throw Distance Charts  
Indoor Unit  
KHS1872  
Room air temp. : 80°F (26.7°C)  
Cooling  
Fan speed  
:
High  
Horizontal distance (ft.)  
10 15 20  
0
0
5
25  
30  
5
10  
15  
: Flap angle 0 ,  
: Flap angle 30 ,  
: Axis air velocity 0  
: Axis air velocity 30  
Room air temp. : 70°F (21.1°C)  
Heating  
Fan speed  
:
High  
Horizontal distance (ft.)  
10 15 20  
0
0
5
25  
30  
5
10  
15  
: Flap angle 45 ,  
: Flap angle 60 ,  
: Axis air velocity 45  
: Axis air velocity 60  
29  
Indoor Unit  
KHS2472  
Room air temp. : 80°F (26.7°C)  
Cooling  
Fan speed  
:
High  
Horizontal distance (ft.)  
10 15 20  
0
0
5
25  
30  
5
10  
15  
: Flap angle 0 ,  
: Flap angle 30 ,  
: Axis air velocity 0  
: Axis air velocity 30  
Room air temp. : 70°F (21.1°C)  
Heating  
Fan speed  
:
High  
Horizontal distance (ft.)  
10 15 20  
0
0
5
25  
30  
5
10  
15  
: Flap angle 45 ,  
: Flap angle 60 ,  
: Axis air velocity 45  
: Axis air velocity 60  
30  
6. ELECTRICAL DATA  
6-1. Electrical Characteristics  
Indoor Unit  
KHS1872  
Outdoor Unit CH1872  
(1) Voltage:230V  
Cooling  
<
230V >  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Fan Motor + Compressor  
230V Single-phase 60Hz  
6.7  
Complete Unit  
Performance at  
Rating conditions  
Running amp.  
Power input  
A
0.3  
32  
7.0  
W
1,468  
1,500  
Rating conditions:  
Indoor air temperature:  
Outdoor air temperature:  
80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.  
95°F (35°C) D.B.  
Heating  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Complete Unit  
Fan Motor + Compressor  
Performance at  
230V Single-phase 60Hz  
Rating conditions  
Running amp.  
Power input  
0.3  
34  
7.1  
7.4  
A
1,541  
1,575  
W
Rating conditions:  
Indoor air temperature  
Outdoor air temperature  
70°F (21.1°C) D.B.  
47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.  
(2) Voltage:208V  
Cooling  
<
208V >  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Complete Unit  
Fan Motor + Compressor  
Performance at  
208V Single-phase 60Hz  
Rating conditions  
Running amp.  
Power input  
0.3  
32  
7.4  
7.7  
A
1,468  
1,500  
W
Rating conditions:  
Indoor air temperature:  
Outdoor air temperature:  
80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.  
95°F (35°C) D.B.  
Heating  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Complete Unit  
Fan Motor + Compressor  
Performance at  
208V Single-phase 60Hz  
Rating conditions  
Running amp.  
Power input  
0.3  
34  
7.8  
8.1  
A
1,541  
1,575  
W
Rating conditions:  
Indoor air temperature  
Outdoor air temperature  
70°F (21.1°C) D.B.  
47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.  
31  
Indoor Unit  
KHS2472  
Outdoor Unit CH2472  
(1) Voltage:230V  
Cooling  
<
230V >  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Fan Motor + Compressor  
230V Single-phase 60Hz  
10.3  
Complete Unit  
Performance at  
Rating conditions  
Running amp.  
Power input  
A
0.5  
55  
10.8  
W
2,300  
2,355  
Rating conditions:  
Indoor air temperature:  
Outdoor air temperature:  
80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.  
95°F (35°C) D.B.  
Heating  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Complete Unit  
Fan Motor + Compressor  
Performance at  
230V Single-phase 60Hz  
Rating conditions  
Running amp.  
Power input  
0.5  
58  
11.5  
12.0  
A
2,432  
2,490  
W
Rating conditions:  
Indoor air temperature  
Outdoor air temperature  
70°F (21.1°C) D.B.  
47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.  
(2) Voltage:208V  
Cooling  
<
208V >  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Complete Unit  
Fan Motor + Compressor  
Performance at  
208V Single-phase 60Hz  
Rating conditions  
Running amp.  
Power input  
0.5  
55  
11.6  
12.1  
A
2,300  
2,355  
W
Rating conditions:  
Indoor air temperature:  
Outdoor air temperature:  
80°F (26.7°C) D.B. / 67°F (19.4°C) W.B.  
95°F (35°C) D.B.  
Heating  
Indoor Unit  
Fan Motor  
Outdoor Unit  
Complete Unit  
Fan Motor + Compressor  
Performance at  
208V Single-phase 60Hz  
Rating conditions  
Running amp.  
Power input  
0.5  
58  
13.0  
13.5  
A
2,432  
2,490  
W
Rating conditions:  
Indoor air temperature  
Outdoor air temperature  
70°F (21.1°C) D.B.  
47°F (8.3°C) D.B. / 43°F (6.1°C) W.B.  
32  
6-2. Electric Wiring Diagrams  
Indoor Unit  
KHS1872 KHS2472  
To avoid electrical shock hazard, be sure to  
disconnect power before checking, servicing  
and/or cleaning any electrical parts.  
WARNING  
TERMINAL BASE  
EVAPORATOR  
1
2
3
BLK  
WHT  
RED  
AC1 AC2 SI  
1 1  
2 2  
3 3  
4 4  
5 5  
6 6  
7 7  
8 8  
9 9  
10 10  
1 1  
2 2  
3 3  
4 4  
5 5  
6 6  
7 7  
8 8  
9 9  
10 10  
RED  
WHT  
WHT  
WHT  
WHT  
WHT  
WHT  
WHT  
WHT  
WHT  
CONNECTOR  
1 1  
2 2  
3 3  
4 4  
5 5  
RED  
1 1  
2 2  
3 3  
4 4  
5 5  
PNK  
BLU  
BRN  
YEL  
FLAP  
5P (WHT)  
10P(  
FLAP  
LAMP  
WHT  
)
FLAP MOTOR  
CONTROLLER  
ROOM THERMISTOR  
1 1  
2 2  
3 3  
4 4  
BLK  
BLK  
BLK  
BLK  
RED 1 1  
2 2  
BLK 3 3  
WHT 4 4  
YEL 5 5  
BLU 6 6  
ROOM/COIL  
4P(  
)
WHT  
DCM  
6P(BLU)  
FM  
COIL THERMISTOR  
FAN MOTOR  
1 1  
2 2  
3 3  
ION  
3P (  
)
WHT  
HA  
JEM-A  
4P (WHT)  
1 2 3 4  
1 2 3 4  
1 2 3 4  
ION  
TERMINAL  
ION ASSY  
8FA2-5257-70500-0  
33  
Outdoor Unit CH1872  
To avoid electrical shock hazard, be sure to  
disconnect power before checking, servicing  
and/or cleaning any electrical parts.  
WARNING  
REACTANCE  
BLK  
POWER RELAY  
1
1
2
2
6
1
4
5
BLK  
W
W
W
W
W
W
W
W
W
W
W
W
W
W
+
+
-
-
-
-
L1  
L2 HIC HIC  
BD BD  
HIC HIC  
AC2 AC2  
A1 A2  
FERRITE  
CORE  
TERMINAL  
PLATE  
E1  
E
25A  
1
2
3
4
5
6
W
W
W
ACIN1  
ACIN2  
SI-A  
BLK  
WHT  
RED  
W
U
CONTROLLER  
GND  
W
V
W
W
BLK  
WHT  
DCFM  
COMP  
A-TH  
COIL/OUTDOOR  
MV0  
RV0 RV1  
1
2
3
4
5
6
7
W
W
1
1
2
2
1
1
2
2
3
3
4
4
1
1
2
2
3
3
4
4
1
1
2
2
3
3
4
4
5
5
N
L
1
1
2
2
3
3
POWER  
SUPPLY  
1
1
2
2
3
3
4
4
5
5
6
6
7
7
HIGH PRESSURE  
SWITCH  
1
1
2
2
1
1
2
2
3
3
4
4
5
5
1
2
1
2
BLK  
BLK  
MVO  
MAGNETIC COIL  
2P-CONNECTOR (BLK)  
S
R
T
RV  
CM  
FM  
GRN/YEL  
4WAY VALVE  
COIL  
OVERLOAD RELAY  
(OLR)  
COMPRESSOR  
MOTOR  
FAN MOTOR  
1
2
1
2
WHT  
WHT  
WHT  
WHT  
2P-CONNECTOR (RED)  
8FA2-5257-64000-2  
34  
Outdoor Unit CH2472  
To avoid electrical shock hazard, be sure to  
disconnect power before checking, servicing  
and/or cleaning any electrical parts.  
WARNING  
REACTANCE  
BLK  
(
)
)
1P-CONNECTOR WHT  
POWER RELAY  
1
1
2
2
1
1
6
1
4
(
1P-CONNECTOR WHT  
1
1
5
BLK  
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
W
+
+
-
BD  
-
BD  
-
-
HEATER1 HEATER0 L1  
L2 HIC HIC  
HIC HIC  
AC2 AC2 A1 A2  
25A  
FERRITE  
CORE  
TERMINAL  
PLATE  
E1  
E
CRANKCASE  
HEATER  
1
2
3
4
5
6
W
ACIN1  
ACIN2  
SI-A  
BLK  
WHT  
RED  
W
U
W
W
CONTROLLER  
GND  
W
V
W
W
BLK  
WHT  
DCFM  
COMP  
A-TH  
COIL/OUTDOOR  
MV0  
RV0 RV1  
1
2
3
4
5
6
7
W
W
1
1
2
2
1
1
2
2
3
3
4
4
1
1
2
2
3
3
4
4
1
1
2
3
3
4
4
5
5
N
L
2
1
1
2
2
3
3
POWER  
SUPPLY  
1
1
2
2
3
3
4
4
5
5
6
6
7
7
HIGH PRESSURE  
SWITCH  
1
1
2
2
1
1
2
2
3
3
4
4
5
5
1
2
1
2
BLK  
BLK  
MVO  
MAGNETIC COIL  
2P-CONNECTOR (BLK)  
V
U
W
RV  
CM  
FM  
4WAY VALVE  
COIL  
OVERLOAD RELAY  
(OLR)  
COMPRESSOR  
MOTOR  
FAN MOTOR  
1
2
1
2
WHT  
WHT  
WHT  
WHT  
2P-CONNECTOR (RED)  
8FA2-5257-69200-3  
35  
Tab  
7. MAINTENANCE  
7-1. Address Setting of the Remote  
Control Unit  
The address can be set in order to prevent  
interference between remote controllers when two  
indoor units are installed near each other. The  
address is normally set to "A." To set a different  
address, it is necessary to change the address on the  
second remote controller.  
Fig. 13  
NOTE  
Once changed, you cannot restore the original  
address setting of the air conditioner.  
(1) Switch on the power source.  
(2) Break the address-setting tab marked "A" on the  
second remote controller to change the address  
(Fig. 13). When the tab is removed, the adress is  
automatically set to B (Fig. 14).  
ACL button  
Fig. 14  
(3) Press and hold the remote controller ION button  
and 1 HR TIMER button. Then, press and hold  
the ACL (reset) button with a pointed object such  
as the tip of a pen. After 5 seconds, release ACL  
button first, then release ION and 1 HR TIMER  
buttons, "oP-1" (test run) appears, blinking in the  
remote controller clock display area.  
(4) Each time the 1 HR TIMER button is pressed, the  
display changes as shown below. Press this  
button 2 times to change the display to "oP-7"  
(address setting). (Fig. 15)  
Test run mode  
ON/OFF  
operation  
button  
ION  
button  
Self-diagnostic mode  
Address setting mode  
1 HR.TIMER  
button  
(5) "oP-7" has now been selected for address setting.  
(6) Press the ON/OFF operation button on the remote  
controller. (Fig. 15) Check that the "beep"  
signalreceived sound is heard from the second  
indoor unit (approximately 5 times). The sound  
you hear is the signal that the remote controller  
address has been changed.  
(7) Finally press the remote controller ACL (reset)  
button to cancel the blinking "oP-7" display. (Fig.  
15)  
ACL (Reset)  
button  
Changing of the second remote controller address is  
now completed.  
Fig. 15  
36  
7-2. Disconnecting and Connecting Positive Connector for Outdoor Unit  
One of the two types of connectors illustrated at left is used. Their  
basic structure is the same for each.  
How to Disconnect  
Hold the resin connector cover, and pull the connector off.  
You cannot disconnect the connector by pulling the wire since  
it is locked inside. Always hold the cover to disconnect. (See  
illustration at left.) For the connector without the resin cover,  
push the lock in the direction of "2" while pulling it off.  
Pull the cover upward  
How to Connect  
In order to connect, hold the resin cover of the connector and  
push it in. Confirm the click sound for the inside lock.  
When the cover is pulled upward, the lock is  
released with the sequence of 1 and 2.  
37  
8. FUNCTIONS  
8-1. Operation Functions  
Emergency operation  
SENSOR DRY  
Emergency operation is available when the remote  
controller malfunctions, has been lost, or otherwise  
cannot be used.  
During DRY operation, the system adjusts the room  
temperature and fan speed according to the conditions in the  
room, in order to maintain a comfortable room environment.  
SENSOR DRY operation  
To operate the system, press the OPERATION button,  
which is also used as the receiver, below the unit display.  
Each time this button is pressed, the OPERATION lamp  
changes color to indicate the type of operation. Select the  
desired type of operation.  
DRY operation is as shown in the figure below.  
Load  
COOL zone  
A zone  
COOL  
(GREEN)  
HEAT  
(RED)  
STOP  
(Lamp Off)  
B zone  
The set temperature is 4°F(2°C) below the detected room  
temperature in the case of cooling operation, and 4°F(2°C)  
above the room temperature in the case of heating  
operation. The flap and fan speed settings are AUTO.  
Conditions are monitored at all  
times when the room temperature  
is below 59°F(15°C).  
DRY A  
The compressor operation frequency varies.  
The indoor fan operates with 1/f fluctuation.  
AUTO cooling/heating operation  
Selecting the operation mode  
DRY B  
When AUTO mode is selected, the microprocessor calculates  
the difference between the set temperature and the room  
temperature, and automatically switches to Cooling or  
Heating mode.  
The compressor operates at a low operating frequency.  
The indoor fan operates with 1/f fluctuation.  
Monitor  
Room temp. Set temp.  
Room temp. Set temp.  
COOL  
HEAT  
Monitoring operation takes place when the room temperature  
is below 59°F  
temperature.  
(15°C), or more than 5°F(3°C) below the set  
As shown by the example in the figure below, with AUTO  
cooling/heating operation, the mode changes between  
Heating and Cooling mode according to changes in the  
relationship between the current room temperature and the  
set temperature.  
When the monitoring range is entered, the compressor stops,  
and the indoor fan operates with 1/f fluctuation.  
NOTE  
Example  
PAM- control  
Example of operation in AUTO mode with the set room temperature  
at 74°F(23°C).  
In order to further improve inverter performance, control is  
switched between PWM control at low operation speeds, and  
PAM control at high operation speeds, making the most  
effective use of power.  
Room temp.  
Zone A  
Zone B  
Zone C  
74  
Set temp.  
Zone C  
Zone B  
More than  
1 hour  
Within  
1 hour  
Zone A  
Compressor  
ON  
ON  
ON  
OFF  
OFF  
Operation mode  
Cooling  
Heating  
Cooling  
38  
HIGH POWER  
NIGHT SETBACK  
This function acts to raise the power but keeps the AC system in  
the same operating mode.  
This function is set with the HIGH POWER button on the remote  
controller.  
(It can be set regardless of the temperature and fan speed  
settings.)  
When NIGHT SETBACK operation is set, the temperature and  
fan speed settings will be adjusted automatically to allow  
comfortable sleep.  
When NIGHT SETBACK operation is set, " mark" appears on  
the remote controller. The main unit display lamp also becomes  
dimmer.  
HIGH POWER operation from remote controller  
COOL and DRY modes  
The unit operates at maximum output for 30 minutes,  
regardless of the desired temperature.  
The fan speed is 1 step above "High."  
When the night setback mode is selected, the air conditioner  
automatically raises the temperature setting 2°F(1°C) when 30  
minutes have passed after the selection was made, and then  
another 2°F(1°C) after another 30 minutes have passed,  
regardless of the indoor temperature when night setback was  
selected. This enables you to save energy without sacrificing  
comfort. This function is convenient when gentle cooling is  
needed.  
Frequency  
MAX  
2°F(1°C)  
Setting  
Time  
0
temperature  
2°F(1°C)  
30 min.  
5 min.  
Press the NIGHT  
SETBACK button  
30 min.  
30 min.  
Start  
End  
Time  
NOTE  
When HIGH POWER operation ends, the unit operates at low  
Hz for 5 minutes, regardless of the thermostat OFF conditions.  
HEAT mode  
When in DRY mode, operation is in the cooling zone.  
When the night setback mode is selected, the air conditioner  
automatically lowers the temperature setting 4°F(2°C) when 30  
minutes have passed after the selection was made, and then  
another 4°F(2°C) after another 30 minutes have passed,  
regardless of the indoor temperature when night setback was  
selected. This enables you to save energy without sacrificing  
comfort. This function is convenient when gentle heating is  
needed.  
Lamp colors  
OPERATION lamp  
HEAT operation  
DRY operation  
COOL operation  
FAN operation  
Red  
Setting  
temperature  
4°F(2°C)  
Orange  
4°F(2°C)  
Time  
Green  
Green  
DEFROSTING operation  
Red and Orange  
alternately  
Press the NIGHT  
SETBACK button  
30 min.  
30 min.  
TIMER lamp  
QUIET lamp  
ION lamp  
Green  
Green  
Green  
Timer backup  
Operation stops if there are no operator controls for 25 hours or  
longer after unit operation switched from OFF to ON by use of  
ON timer operation.  
39  
8-2. Protective Functions  
Overload prevention during heating  
Cold-air prevention during heating  
During HEAT operation, the temperature of the indoor heat  
exchanger is used to control the frequency and lessen the load  
on the compressor before the protective device is activated.  
During heating, the fan speed is set to "LL" (very low) or stopped.  
As the temperature of the indoor heat exchanger rises, the fan  
speed is changed to the set speed.  
Indoor heat exchanger  
A. Control start  
B. Control end  
Set fan speed  
Approx.  
A
High  
127  
(53)  
At stability of operation  
Approx.  
117  
B
(47)  
a
b
c
d
At start of operation  
a. Area: Automatic capacity control  
b. When Point A has been exceeded, the operation frequency is  
reduced by a certain proportion.  
LL  
Stopped  
77  
(25) (30)  
86  
Approx. 104  
(40)  
c. Area: Frequency increase is prohibited.  
d. At Point B and below, overload prevention is ended and  
control is the same as in the  
a
area.  
Indoor heat exchanger  
temperature °F(°C)  
NOTE  
The fan speed is forcibly changed to "LL" beginning 30 seconds  
after the thermostat turns OFF.  
Freeze prevention  
At stability of operation refers to operation when the room  
temperature has approached the set temperature.  
During COOL or DRY operation, freezing is detected and  
operation is stopped when the temperature of the indoor heat  
exchanger matches the conditions below.  
When HEAT operation starts, the indoor fan is stopped until the  
temperature of the indoor heat exchanger reaches 68°F(20°C)  
or higher, or until the room temperature reaches 59°F(15°C) or  
higher.  
1. Freeze-prevention operation is engaged when the  
temperature of the indoor heat exchanger is below 43°F(6°C).  
2. Restart after freeze-prevention operation occurs when the  
temperature of the indoor heat exchanger reaches 46°F(8°C)  
or above.  
Compressor discharge temperature control  
C
46  
(8)  
This function controls the operation frequency to prevent the  
compressor discharge temperature from rising more than a  
specified temperature.  
A
B
43  
(6)  
Compressor discharge temperature °F(°C)  
36  
(2)  
Approx.  
A
*
214  
(101)  
a
b
c
d
Approx.  
B
a. Area: Automatic capacity control  
201  
(94)  
b. When the temperature drops below Point A, the operation  
frequency is reduced by a certain proportion.  
a
b
c
d
c. Area: Frequency increase is prohibited.  
d. When the temperature reaches Point C or above, freezing  
a. Area: Automatic capacity control.  
prevention is ended and control is the same as in the  
a
area.  
b. When the temperature rises above Point A, the operation  
frequency is reduced at a specified rate.  
* When the temperature drops to below 36°F(2°C)  
(continuously for 2 minutes or longer), the compressor stops.  
Once the freeze condition is detected, the air conditioner will  
work less than the maximum frequency until it is turned off.  
c. Area: Further frequency increase is prohibited.  
d. When the temperature falls below Point B, prevention of a rise  
in frequency is released and the air conditioner operates as in  
a
area.  
* The compressor will stop if the temperature of the compressor  
discharge exceeds 248°F(120°C) due to shortage of gas or  
other reason.  
40  
Defrost detection and release  
CT (Peak current cut-off control)  
This function prevents the circuit breaker or fuse from operating  
to open the circuit. This function works when electrical current  
has increased due to an increase in the cooling / heating load,  
or to a decrease in the power supply voltage. In these cases,  
operation frequency is reduced or operation is interrupted auto-  
matically to control the electrical current for operation.  
Reverse-Cycle Defrosting  
Defrosting Sequence  
When the cause of the increase in electrical current is rectified,  
the system will resume operation in the original mode.  
Heating operation  
(A)  
Heating  
<
KHS1872  
>
Outdoor fan ON  
4-way valve ON  
Cooling Dry  
22.5  
Peak current cut-off trips  
Hz down  
14.0  
15.0  
Frost sensing  
(A)  
<
KHS2472>  
Cooling Dry  
Heating  
Defrost detection occurs in either of the following cases:  
Peak current cut-off trips  
Hz down  
22.5  
The temperature of the heat exchanger remains at  
or below the L1 line for 3 minutes after the start of  
HEAT operation.  
14.0  
17.5  
The temperature of the heat exchanger remains at  
or below the L2 line for 120 minutes after the start  
of HEAT operation.  
Electrical current setting for COOL operation is  
used during DEFROST operation.  
NOTE  
Outdoor heat  
exchanger temp.  
0
Ambient temp.  
L2  
L1  
Frosting area  
Reverse-cycle defrosting operation  
Compressor 1 minute after it is stopped,  
compressor is ON.  
Outdoor fan OFF  
Indoor fan OFF  
4-way valve OFF  
Operation lamp  
Repeatedly switches between red  
and orange illumination.  
Releasing of defrosting  
Outdoor heating exchanger temp. is over 57.2°F (14°C).  
Defrosting operation lasts 12 minutes (maximum).  
2 minutes after it is stopped, compressor is ON.  
4-way valve is ON. Outdoor fan is ON.  
NOTE  
If the air conditioner is turned off during the defrosting  
cycle, it will continue defrosting and turn itself off after  
defrosting is completed.  
41  
9. TROUBLESHOOTING  
9-1. Precautions before Performing Inspection or Repair  
After checking the self-diagnostics monitor, turn the power OFF before starting inspection or repair.  
High-capacity electrolytic capacitors are used inside the outdoor unit controller (inverter). They retain an electrical charge  
(charging voltage DC 310V) even after the power is turned OFF, and some time is required for the charge to dissipate. Be  
careful not to touch any electrified parts before the controller LED (red) turns OFF.  
If the outdoor controller is normal, approximately 30 seconds will be required for the charge to dissipate. However, allow  
at least 5 minutes for the charge to dissipate if there is thought to be any trouble with the outdoor controller.  
9-2. Method of Self-Diagnostics  
< Clock display >  
Follow the procedure below to perform detailed trouble diagnostics.  
Test run mode  
Self-diagnostics mode  
NOTE  
1:If the operation lamp blinks every 0.5 seconds immediately when the  
power is turned ON, there is an external ROM (OTP data) failure on the  
indoor circuit board, or a ROM socket insertion problem, or the ROM  
has not been installed.  
2:The failure mode is stored in memory even when the power is not ON.  
Follow the procedure below to perform diagnostics.  
ON/OFF  
operation  
button  
PROCEDURE  
After turning on power to the air conditioner, use the remote controller and  
follow the steps below to execute self-diagnostics.  
ION  
button  
Step 1: Press and hold the remote controller ION button and 1 HR TIMER  
button. Then, press and hold the ACL (reset) button with a pointed  
object such as the tip of a pen. After 5 seconds, release ACL  
button first, then release ION and 1 HR TIMER buttons, "oP-1"  
(test run) appears, blinking in the remote controller clock display  
area.  
1HR.  
TIMER  
button  
Step 2: Next, press the 1 HR TIMER button once to change the display  
from "oP-1" to "oP-3" (self-diagnostics). (The display continues to  
blink.)  
Step 3: Finally press the ON/OFF button to engage self-diagnostics mode.  
The self-diagnostics function utilizes the 3 indicator lamps on the main  
unit, in combinations of ON lamps, blinking lamps, and OFF lamps, to  
report the existence of sensor trouble or a protective operation. (The  
lamps blink or remain ON for 5 seconds, then turn OFF for 2 seconds.)  
Self-diagnostics is completed when the buzzer sounds 3 short beeps.  
A maximum of 3 self-diagnostics reports are displayed, for 5 seconds  
each, beginning with the most recent report. Following this display the  
lamps turn OFF. In order to view the self-diagnostics results again,  
press the ON/OFF button again.  
ACL  
(Reset)  
button  
The 3 lamps remain OFF if no trouble has occurred.  
<IMPORTANT> After self-diagnostics is completed, be sure to press the  
ACL (reset) button to return to normal mode. The air  
conditioner will not operate if this is not done.  
42  
(1) Self-diagnostics Lamps  
INDOOR UNIT  
(1) OPERATION lamp  
(2) TIMER lamp  
(3) QUIET lamp  
ION lamp  
OPERATION button  
REMOTE CONTROL receiver  
Since the indications cover various units, the corresponding parts listed below may not be present in some models.  
.... .... ....  
Indication on indoor unit  
OFF  
Blinking  
ON (Illuminated)  
Quiet  
(3)  
Timer  
(2)  
Operation  
(1)  
Code  
S01  
S02  
S03  
Diagnostics items  
Room temperature sensor failure  
Indoor heat exchanger sensor failure  
Humidity sensor failure  
Diagnostics contents  
(1) Sensor open circuit or short circuit  
(2) Contact failure at connector or open circuit at terminal crimping location  
(short-circuit detection only for the humidity sensor)  
(3) Indoor/outdoor PCboard failure  
Compressor temperature sensor failure  
S04  
S05  
(1) Sensor open circuit or short circuit  
(2) Contact failure at connector or open circuit at terminal crimping location  
(3) Outdoor PCboard failure  
Outdoor heat exchanger sensor failure  
Outdoor air temperature sensor failure  
S06  
S07  
Outdoor electrical current detection  
failure  
Outdoor PCboard failure  
(1) Mis-wiring (2) AC power failure (3) Blown fuse (4) Power Relay failure  
(5) Indoor or outdoor PCboard failure (6) Outdoor Fan Motor failure (7) Reactor failure  
(8) High-Pressure Switch failure (9) Overload Relay failure (10) Magnetic Coil failure  
* See detailed flowchart in this section.  
Indoor/outdoor communications failure  
(serial communications)  
E01  
E02  
(1) HIC or power Tr failure (2) Outdoor fan does not turn. (3) Instantaneous power outage  
(4) Service valve not opened. (5) Outdoor fan blocked. (6) Continuous overload operation  
(7) Compressor failure (8) Outdoor PCboard failure  
• HIC circuit failure  
• Power Tr (transistor) circuit failure  
Outdoor unit external ROM (OTP data)  
failure  
(1) External ROM data failure (2) Outdoor PCboard failure  
E03  
E04  
E05  
(1) Instantaneous power outage (2) HIC or power transistor failure  
(3) Outdoor PCboard failure  
Peak current cut-off  
PAM circuit failure  
Active circuit failure  
(1) Outdoor PCboard failure (2) Outdoor power supply voltage failure  
Compressor discharge overheat  
prevention activated.  
(1) Electric expansion valve failure (2) Capillaries choked (3) Shortage of refrigerant  
E06  
E07  
(4) Continuous overload operation (5) Outdoor fan does not rotate (6) Outdoor PCboard failure  
Indoor fan operating failure  
(1) Fan motor failure (2) Contact failure at connector (3) Indoor PCboard failure  
4-way valve switching failure  
Indoor zero-cross failure  
(1) 4-way valve failure (heat pump model only)  
(2) Outdoor PCboard failure  
E08  
E09  
E10  
E11  
No-refrigerant protection  
(1) Service valve not opened. (2) Shortage of refrigerant  
(1) Open phase (2) Outdoor PCboard failure  
DC compressor drive circuit failure  
Outdoor fan operating failure  
(1) Fan motor failure (2) Contact failure at connector (3) Outdoor PCboard failure  
Outdoor system communications failure  
OLR operation  
Outdoor power supply open phase  
Outdoor coil freezing  
(1) Mis-wiring (2) Blown fuse (3) Power Relay failure (4) Outdoor PCboard failure  
(5) Compressor failure  
E12  
E13  
* See detailed flowchart in this section.  
Freeze-prevention operation activated.  
(1) Indoor fan system failure (2) Shortage of refrigerant (3) Low-temperature operation  
43  
(2) If the self-diagnostics function fails to operate  
Check the indoor unit.  
No indicators illuminate and the  
indoor fan does not rotate.  
Check the power voltage.  
Blown  
Is the fuse blown?  
Normal  
Replace the circuit  
board or the fuse.  
Replace the controller.  
44  
9-3. Checking the Indoor and Outdoor Units  
(1) Checking the indoor unit  
No.  
Control  
Check items (unit operation)  
The rated voltage must be present between inter-unit wirings 1 and 2.  
1
Use the remote controller to operate the  
unit in "TEST run" mode. To determine  
whether the mode is currently in  
"TEST run" mode, check the 4 indicator  
lamps on the unit. If all 4 are blinking,  
the current mode is "TEST run."  
Connect a 5 k ohm resistor between inter-unit wirings 2 and 3. When the  
voltage at both ends is measured, approximately 12 to 15V DC must  
be output and the multimeter pointer must bounce once every 8  
seconds.  
Or instead of measuring the voltage, you can insert an LED jig and  
check that the LED flickers once every 8 seconds.  
If there are no problems with the above, then check the outdoor unit.  
For the "Test run" procedure, refer to the Appendix B "Installation Instructions".  
(2) Checking the outdoor unit  
No.  
Control  
Check items (unit operation)  
1
Apply the rated voltage between outdoor  
unit terminals L and N.  
The control panel LED (red) must illuminate.  
2
Short-circuit the outdoor unit COM terminal  
to the T-RUN terminal.  
The compressor, fan motor and 4-way valve must all turn on.  
If there are no problems with the above, then check the indoor unit.  
TEST/T-RUN terminals  
Using the TEST/T-RUN terminals  
T-RUN  
: Test run (compressor and fan motor turn ON).  
TEST/MV : Compresses time to 1/60th (accelerates  
operation by 60 times faster than normal).  
(TEST)/MV T-RUN COM  
45  
(3) Serial Communication Error Identification Procedure  
If the lamps on the main body show the following conditions after the completion of self-diagnostics,  
a communication error between the indoor unit and outdoor unit might be considered.  
In such a case, identify the breakdown section by using the following procedure.  
NOTE Refer to "Method of Self-Diagnostics" for the self-diagnostics procedure.  
Lamp  
Condition  
Quiet  
Timer  
(2)  
Operation  
(1)  
: Off  
: Blinking  
: Illuminated  
(3)  
E01  
E12  
< Before the Operation >  
For terminal strip short circuit work or inter-unit wiring removal, turn off the power to  
avoid an electric shock.  
WARNING  
Release the terminal strip short circuit after the completion of self-diagnostics.  
Do not perform the short-circuit work between any other terminals except for  
specified ones on the specified terminal strip. If such work is performed between  
the incorrect terminals, the unit might be broken.  
CAUTION  
< Convenient Tool for Short-Circuit Work ( for example ) >  
Cable  
Alligator Clip  
Alligator Clip  
< Check Items before Troubleshooting Serial Communication Start >  
After confirming that the following errors do not exist, start the "Troubleshooting Serial Communication"  
in "Condition: E01 and E12".  
1. Mis -wiring (inter-unit cable, etc.)  
2. AC power failure  
6. Reactor failure (defective insulation, etc.)  
7. High-Pressure Switch failure  
3. Blown fuse  
8. Overload Relay failure  
4. Power Relay failure  
9. Magnetic Coil failure (defective insulation, short-circuit, etc.)  
10. Compressor failure (defective insulation, etc.)  
5. Outdoor Fan Motor failure (defective insulation, etc.)  
(3-1) Condition: E01  
-
+
Outdoor Unit  
V
1
2
3
3
4
5
6
Outdoor Unit  
Troubleshooting Serial Communication  
1
1
2
3
4
5
6
Power  
1
2
Power  
Indoor Unit  
2
3
V
Indoor Unit  
+
-
Fig. 2  
Fig. 1  
1. Turn OFF the power and wait until the power lamp (LED)  
of the outdoor unit controller is turned OFF.  
2. Disconnect the cable from the terminal 3 on the indoor unit  
Is the voltage of about DC12V  
or more given between the terminals  
2 and 3 on the outdoor unit terminal strip  
(Serial Communication Line) ?  
(Fig. 1)  
No  
terminal strip.  
3. Turn ON the power.  
(Fig. 2)  
Yes  
A
( Continued to the next page A. )  
B
( Continued to the next page B. )  
46  
( Continued from the previous page A. )  
A
( Continued from the previous page B. )  
B
Is the voltage of about DC22V to  
24V given between the terminals  
2 and 3 on the indoor unit terminal strip  
(Serial Communication Line) ?  
(Fig. 2)  
Yes  
No  
Defect in the indoor unit  
P.C. board  
Defect or connection error  
in the inter-unit cable  
Outdoor Unit  
1. Turn OFF the power and wait until the power lamp (LED)  
of the outdoor unit controller is turned OFF.  
2. Short-circuit between the terminals 2 and 3 on the outdoor  
1
1
2
2
3
3
4
5
6
Power  
unit terminal strip.  
(Fig. 3)  
Indoor Unit  
Fig. 3  
1. Turn ON the power and operate the system using the  
remote controller or the operation button on the indoor unit.  
2. Perform the self-diagnosis five seconds after the operation  
start.  
Condition: E12  
Defect in the outdoor unit  
P.C. board.  
What is the latest self-diagnosis result ?  
Condition: E01  
Outdoor Unit  
Outdoor Unit  
1. Turn off the power and wait until the power lamp (LED)  
of the outdoor unit controller is turned OFF.  
2. Remove the short-circuit between the terminals 2 and 3 on  
the outdoor unit terminal strip.  
3. Disconnect the cable from the terminal 3 on the indoor unit  
1
1
2
3
3
4
5
6
1
2
2
3
4
5
6
Power  
Power  
2
terminal strip.  
(Fig. 4)  
1
3
Indoor Unit  
Indoor Unit  
Fig. 5  
Fig. 4  
Short-circuit between the terminals 2 and 3 on the indoor unit  
terminal board. (Fig. 5)  
1. Turn ON the power and operate the system using the  
remote controller or the operation button on the indoor unit.  
2. Perform the self-diagnosis five seconds after the operation  
start.  
Condition: E12  
Defect or connection error  
in the inter-unit cable  
What is the latest self-diagnosis result ?  
Condition: E01  
Defect in the indoor unit  
P.C. board  
47  
(3-2) Condition: E12  
Troubleshooting Serial Communication  
Outdoor Unit  
1
1
2
2
3
3
4
5
6
Power  
1. Turn off the power and wait until the power lamp (LED)  
of the outdoor unit controller is turned OFF.  
2. Disconnect the cable from the terminal 3 on the Outdoor  
Indoor Unit  
unit terminal strip.  
(Fig. 6)  
Fig. 6  
1. Turn ON the power and operate the system using the  
remote controller or the operation button on the indoor unit.  
2. Perform the self-diagnosis five seconds after the operation  
start.  
Condition: E01  
Defect in the outdoor unit  
P.C. board  
What is the latest self-diagnosis result ?  
Condition: E12  
Outdoor Unit  
1
1
2
3
3
4
5
6
1. Turn off the power and wait until the power lamp (LED)  
of the outdoor unit controller is turned OFF.  
2. Disconnect the cable from the terminal 3 on the indoor  
Power  
2
unit terminal strip.  
(Fig. 7)  
Indoor Unit  
Fig. 7  
1. Turn ON the power and operate the system using the  
remote controller or the operation button on the indoor unit.  
2. Perform the self-diagnosis five seconds after the operation  
start.  
Condition: E01  
Defect in the inter-unit  
cable  
What is the latest self-diagnosis result ?  
Condition: E12  
Defect in the indoor unit  
P.C. board  
48  
9-4. Trouble Diagnosis of Fan Motor  
9-4-1. Indoor Fan Motor  
This indoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil  
resistance, and the following procedure should be used to check the motor.  
To perform diagnosis, operate the unit in cooling mode with indoor fan speed "High". Next, make sure that the  
indoor unit receive the signals from the remote controller when the ON/OFF operation button is pressed.  
Important:  
(A) Turn OFF the power before connecting or disconnecting the motor connectors.  
(B) When performing voltage measurement at the indoor controller connector for (3) in the table  
below, the DC motor will trip and voltage output will stop approximately 1 minute after operation  
is started. For this reason, to measure the voltage again, turn OFF the unit once using the  
remote controller, and then start the air conditioner again.  
[Trouble symptom 1] The fan does not stop when the unit stops. Indoor unit controller trouble.  
[Trouble symptom 2] The fan motor does not rotate when the unit is operating.  
(Diagnostic procedure)  
* Disconnect the motor connectors and measure the voltage at the DC motor connectors on the indoor  
unit controller (3 locations).  
Measurement location  
Normal value  
DC 230 V or more  
(1) Vm-Gnd: Between pin 1 and pin 3  
(2) Vcc-Gnd: Between pin 4 and pin 3  
(3) Vs-Gnd: Between pin 5 and pin 3  
DC 14 V or more  
Fluctuation between DC 1.7 to 6.1 V  
(Diagnostic results)  
All of the above measured values are normal. Fan motor trouble (Replace the motor.)  
Any one of the above measured values is not normal. Indoor unit controller trouble (Replace the controller .)  
(Reference)  
DC motor connector pin arrangement  
Pin 1: Vm (red)  
Pin 2: Not used  
Pin 3: Gnd (black)  
Pin 4: Vcc (white)  
Pin 5: Vs (yellow)  
Pin 6: PG (blue)  
[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the indoor  
unit operates.  
(There is trouble in the system that provides feedback of motor rotation speed from the  
motor to the indoor unit controller.)  
[Trouble symptom 4] Fan motor rotation speed does not change during indoor unit operation.  
[Trouble symptom 5] Fan motor rotation speed varies excessively during indoor unit operation.  
(Remedy for symptom 3 to 5)  
It is not possible to identify whether the trouble is indoor unit controller trouble or motor trouble.  
Therefore, first replace the indoor unit controller, then (if necessary) replace the DC motor.  
49  
9-4-2. Outdoor Fan Motor  
This outdoor DC fan motor contains an internal control PCB. Therefore, it is not possible to measure the coil  
resistance, and the following procedure should be used to check the motor.  
Perform the trouble diagnosis by Test Run mode described on Installation Instructions.  
Important:  
(A) Turn OFF the power before connecting or disconnecting the motor connectors.  
(B) When performing voltage measurement at the outdoor controller connector for (3) in the table  
below, the DC motor will trip and voltage output will stop approximately 10 seconds after  
operation is started. For this reason, to measure the voltage again, first turn OFF the outdoor  
unit power, then, measure the voltage in Test Run mode.  
[Trouble symptom 1] The fan does not stop when the outdoor unit stops. Outdoor unit controller trouble  
[Trouble symptom 2] The fan motor does not rotate when the outdoor unit is operating.  
(Diagnostic procedure)  
* Disconnect the motor connectors and measure the voltage at the DC motor connectors on the outdoor  
unit controller (3 locations).  
Measurement location  
(1) Vs-Gnd : Between pin 1 and pin 4  
or  
Normal value  
DC 230V or more  
DC 14V or more  
Vm-Gnd : Between pin 1 and pin 4  
(2) Vcc-Gnd : Between pin 5 and pin 4  
(3) Vsp-Gnd : Between pin 7 and pin 4  
After fluctuating 4 times between DC 1.7 to 6.1V  
(1 sec. ON) and DC 0 V (1 sec. OFF), the DC  
motor trips.  
(Diagnostic results)  
All of the above measured values are normal. Fan motor trouble (Replace the motor.)  
Any one of the above measured values is not normal. Outdoor unit controller trouble  
(Replace the controller .)  
(Reference)  
DC motor connector pin arrangement  
CH1872  
CH2472  
Pin 1: Vs (white)  
Pin 2: Not used  
Pin 3: Not used  
Pin 4: Gnd (black)  
Pin 5: Vcc (red)  
Pin 6: FG (blue)  
Pin 7: Vsp (yellow)  
Pin 1: Vm (red)  
Pin 2: Not used  
Pin 3: Not used  
Pin 4: Gnd (blue)  
Pin 5: Vcc (brown)  
Pin 6: PG (white)  
Pin 7: Vsp (orange)  
[Trouble symptom 3] Motor rotates for some time (several seconds), but then quickly stops, when the outdoor  
unit operates.  
(There is trouble in the system that provides feedback of motor rotation speed from the  
motor to the outdoor unit controller.)  
[Trouble symptom 4] Fan motor rotation speed does not change during outdoor unit operation.  
[Trouble symptom 5] Fan motor rotation speed varies excessively during outdoor unit operation.  
(Remedy for symptom 3 to 5)  
It is not possible to identify whether the trouble is outdoor unit controller trouble or motor trouble.  
Therefore, first replace the outdoor unit controller, then (if necessary) replace the DC motor.  
50  
9-5. Noise Malfunction and Electromagnetic Interference  
An inverter A/C operates using pulse signal control and high frequencies. Therefore, it is susceptible to the effects of external  
noise, and is likely to cause electromagnetic interference with nearby wireless devices.  
A noise filter is installed for ordinary use, preventing these problems. However, depending on the installation conditions, these  
effects may still occur. Please pay attention to the points listed below.  
(1) Noise malfunction  
This refers to the application of high-frequency noise to the signal wires, resulting in abnormal signal pulses and malfunction.  
Locations most susceptible to noise  
Trouble  
Correction  
1. Locations near broadcast stations where  
there are strong electromagnetic waves  
Either of the following trouble may occur.  
(The fundamental concept is to make the  
system less susceptible to noise.)  
1. The unit may stop suddenly during  
operation.  
2. Locations near amateur radio (short wave)  
stations  
- Insulate for noise or  
distance from the noise source. -  
2. Indicator lamps may flicker.  
3. Locations near electronic sewing machines  
and arc-welding machines  
1. Use shielded wires.  
2. Move unit away from the noise source.  
(2) Electromagnetic interference  
This refers to noise generated by high-speed switching of the microcomputer and compressor. This noise radiates through  
space and returns to the electric wiring, affecting any wireless devices (televisions, radios, etc.) located nearby.  
Locations most susceptible to noise  
Trouble  
Correction  
1. A television or radio is located near the  
A/C and A/C wiring.  
1. Noise appears in the television picture, 1. Select a separate power source.  
or the picture is distorted.  
2. Keep the A/C and A/C wiring at least 1 meter  
away from wireless devices and antenna cables.  
2. The antenna cable for a television or  
radio is located close to the A/C and A/C  
wiring.  
2. Static occurs in the radio sound.  
3. Change the wireless device’s antenna to a high-  
sensitivity antenna.  
3. Locations where television and radio  
signals are weak.  
4. Change the antenna cable to a BS coaxial cable.  
5. Use a noise filter (for the wireless device).  
6. Use a signal booster.  
51  
10. CHECKING ELECTRICAL COMPONENTS  
10-1. Measurement of Insulation  
Resistance  
Ground wire  
Clip  
The insulation is in good condition if the resistance  
exceeds 1M ohm.  
Probe  
10-1-1. Power Supply Cord  
Insulation  
tester  
Clamp the grounding wire of power cord with the lead  
Fig. 1  
clip of the insulation resistance tester and measure the  
resistance by placing a probe on either of the two  
power wires. (Fig. 1)  
Terminal plate  
Then also measure the resistance between the  
grounding and other power terminals. (Fig. 1)  
Probe  
10-1-2. Indoor Unit  
Clamp an aluminum plate fin or copper tube with the  
lead clip of the insulation resistance tester and  
measure the resistance by placing a probe on each  
terminal screw on the terminal plate. (Fig. 2)  
Note that the ground line terminal should be skipped  
for the check.  
Clip  
Copper  
tube or  
metallic part  
Insulation  
tester  
10-1-3. Outdoor Unit  
Fig. 2  
Clamp a metallic part of the unit with the lead clip of  
the insulation resistance tester and measure the  
resistance by placing a probe on each terminal screw  
where power supply lines are connected on the  
terminal plate. (Fig. 2)  
Probe  
Clip  
10-1-4. Measurement of Insulation  
Resistance for Electrical Parts  
Copper  
tube or  
metallic part  
Disconnect the lead wires of the desired electric part  
from terminal plate, capacitor, etc. Similarly disconnect  
the connector. Then measure the insulation resistance.  
(Figs. 3 and 4)  
Insulation  
tester  
Fig. 3  
NOTE  
From fan motor,  
compressor and  
other parts  
Refer to Electric Wiring Diagram.  
If the probe cannot enter the poles because the hole is  
too narrow then use a probe with a thinner pin.  
Probe  
Metallic  
part  
Clip  
Insulation  
tester  
Fig. 4  
52  
10-2. Checking Continuity of Fuse  
on PCB Ass'y  
Fuse  
Remove the PCB Ass'y from the electrical  
component box. Then pull out the fuse from the PCB  
Ass'y. (Fig. 5)  
Check for continuity using a multimeter as shown in  
Fig. 6.  
PCB Ass'y  
Fig. 5  
Fuse  
Fig. 6  
53  
11. REFRIGERANT R410A:  
SPECIAL PRECAUTIONS WHEN SERVICING UNIT  
11-1. Characteristics of New Refrigerant R410A  
11-1-1. What is New Refrigerant R410A?  
R410A is a new refrigerant that contains two types of pseudo-non-azeotropic refrigerant mixture. Its  
refrigeration capacity and energy efficiency are about the same level as the conventional refrigerant, R22.  
11-1-2. Components (mixing proportions)  
HFC32 (50%) / HFC125 (50%)  
11-1-3. Characteristics  
Less toxic, more chemically stable refrigerant  
The composition of refrigerant R410A changes whether it is in a gaseous phase or liquid phase. Thus, when  
there is a refrigerant leak the basic performance of the air conditioner may be degraded because of a change in  
composition of the remaining refrigerant. Therefore, do not add new refrigerant. Instead, recover the  
remaining refrigerant with the refrigerant recovery unit. Then, after evacuation, totally recharge the specified  
amount of refrigerant with the new refrigerant at its normal mixed composition state (in liquid phase).  
When refrigerant R410A is used, the composition will differ depending on whether it is in gaseous or liquid  
phase, and the basic performance of the air conditioner will be degraded if it is charged while the refrigerant is in  
gaseous state. Thus, always charge the refrigerant while it is in liquid phase.  
Ether-type oil is used for compressor oil for R410A-type units, which is different  
CAUTION  
from the mineral oil used for R22. Thus more attention to moisture prevention and  
faster replacement work compared with conventional models are required.  
54  
11-2. Checklist before Servicing  
Use a clutch-type flare tool for R410A or the conventional flare tool. Note that sizes of the resultant flares differ  
between these two tools. Where a conventional flare tool is used, make sure to observe A Specification (amount of  
extrusion) by using the flare spacer.  
Specification A  
Diameter of tube D  
Flare tool for R410A  
Conventional flare tool (for R22)  
Dia.1/4" (6.35 mm)  
Dia.3/8" (9.52 mm)  
Dia.1/2" (12.7 mm)  
Dia.5/8" (15.88 mm)  
0 to 0.0196"  
0.0472"  
(0 to 0.5 mm)  
(1.2 mm)  
Size of flare  
Spacer  
D
D
A
A
Flare tool for R410A  
Conventional flare tool (R22)  
Tubing precautions  
Refrigerant R410A is more easily affected by dust or moisture compared with R22, thus be sure to temporarily  
cover the ends of the tubing with caps or tape prior to installation.  
Never use 0.0276" (0.7 mm)-thick copper tubing or tubing which is less than 0.0315" (0.8 mm) in thickness, since  
air conditioners with R410A are subject to higher pressure than those using R22 and R407C.  
No addition of compressor oil for R410A  
No additional charge of compressor oil is permitted.  
No use of refrigerant other than R410A  
Never use a refrigerant other than R410A.  
If refrigerant R410A is exposed to fire  
Through welding, etc., toxic gas may be released when R410A refrigerant is exposed to fire. Therefore, be sure  
to provide ample ventilation during installation work.  
Caution in case of R410A leak  
Check for possible leak points with the special leak detector for R410A. If a leak occurs inside the room,  
immediately provide thorough ventilation.  
55  
11-3. Tools Specifically for R410A  
For servicing, use the following tools for R410A  
Tool Distinction  
Gauge manifold  
Tool Name  
Charging hose  
Gas leak detector  
Refrigerant cylinder  
Charging cylinder  
Refrigerant recovery unit  
Vacuum pump with anti-reverse flow (*1)  
(Solenoid valve-installed type, which prevents oil from flowing back into the  
unit when the power is off, is recommended.)  
Vacuum pump (*2)...can be used if the following adapter is attached.  
Vacuum pump adapter (reverse-flow prevention adapter) (*3).  
(Solenoid valve-installed adapter attached to a conventional vacuum pump.)  
Electronic scale for charging refrigerant  
Flare tool  
Tools specifically for R410A  
Bender  
Tools which can be com-  
monly used for R22,  
R407C, and R410A  
Torque wrench  
Cutter, reamer  
Welding tool, nitrogen gas cylinder  
The above tools specifically for R410A must not be used for R22 and R407C.  
Doing so will cause malfunction of the unit.  
CAUTION  
For the above vacuum pump (*1, *2) and vacuum pump adapter (*3), those for  
R22-type units can be used for R410A-type. However, they must be used  
exclusively for R410A and never alternately with R22 and R407C.  
To prevent other refrigerants (R22, R407C) from being mistakenly charged to this unit, shape and external  
diameter of the service port screw has been altered.  
<External diameter of service port> R410A : 5/16"  
R22, R407C : 1/4"  
11-4. Tubing Installation Procedures  
When the tubes are connected, always apply HAB oil on the flare portions to improve the sealing of tubing.  
The following is the HAB oil generally used:  
Esso: ZERICE S32  
NOTE  
For details on tubing installation procedures, refer to the installation manuals attached to the indoor  
unit and outdoor unit.  
56  
11-5. In Case of Compressor Malfunction  
Should the compressor malfunction, be sure to make the switch to a replacement  
CAUTION  
compressor as quickly as possible.  
Use only the tools indicated exclusively for R410A. See "11-3. Tools  
Specifically for R410A."  
11-5-1. Procedure for Replacing Compressor  
(1) Recovering refrigerant  
Any remaining refrigerant inside the unit should not be  
released to the atmosphere, but recovered using the  
refrigerant recovery unit for R410A.  
(1) Recover refrigerant  
OK  
Do not reuse the recovered refrigerant, since it will contain  
impurities.  
(2) Replacing Compressor  
(2) Replace compressor  
OK  
Soon after removing seals of both discharge and suction  
tubes of the new compressor, replace it quickly.  
(3) Checking for sealing  
Use nitrogen gas for the pressurized gas, and never use a  
refrigerant other than R410A. Also do not use oxygen or  
any flammable gas.  
(3) Check for sealing  
OK  
(4) Evacuation  
Use a solenoid valve-installed vacuum pump so that  
even if power is cut off in the middle of evacuation of air  
due to a power interruption, the valve will prevent the  
pump oil from flowing back.  
(4) Evacuation  
OK  
The equipment may be damaged if moisture remains in  
the tubing, thus carry out the evacuation thoroughly.  
When using a vacuum pump with exhaust air volume more  
than 0.883 cu.ft./min. and ultimate vacuum pressure rate  
of 50 micron Hg.  
(5) Recharge  
Standard time for evacuation  
Length of tubing  
Less than 33 ft. (10 m)  
More than 33 ft. (10 m)  
Evacuation time  
More than 10 minutes  
More than 15 minutes  
57  
(5) Recharging  
Be sure to charge the specified amount of  
Configuration and characteristics of cylinders  
Valve  
refrigerant in liquid state using the service port  
of the wide tube service valve. The proper  
amount is listed on the unit's nameplate.  
When the entire amount cannot be charged all at  
once, charge gradually while operating the unit in  
Cooling Operation.  
Liquid  
Never charge a large amount  
CAUTION  
of liquid refrigerant at once to  
the unit. This may cause  
damage to the compressor.  
Single valve  
Charge liquid refrigerant with  
cylinder in up-side-down position.  
When charging with a refrigerant cylinder, use an  
electronic scale for charging refrigerant. In this  
case, if the volume of refrigerant in the cylinder  
becomes less than 20% of the fully-charged  
amount, the composition of the refrigerant starts  
to change. Thus, do not use the refrigerant if  
the amount in the charging cylinder is less  
than 20%.  
Fig. 1  
Valve  
Also, charge the minimum necessary amount to  
the charging cylinder before using it to charge  
the air conditioning unit.  
Example:  
Liquid  
In case of charging refrigerant to a unit requiring  
1.68 lb. (0.76 Kg) using a capacity of a 22 lb. (10  
Kg) cylinder, the minimum necessary amount for  
the cylinder is:  
Single valve (with siphon tube)  
Charge with cylinder in normal position.  
1.68 + 22 0.20 = 6.08 lb.  
(0.76 + 10 0.20 = 2.76 Kg)  
Fig. 2  
For the remaining refrigerant, refer to the  
instructions of the refrigerant manufacturer.  
NO!  
If using a charging cylinder, transfer the specified  
amount of liquid refrigerant from the refrigerant  
cylinder to the charging cylinder.  
Charging  
cylinder  
Prepare an evacuated charging cylinder  
beforehand.  
To prevent the composition  
CAUTION  
of R410A from changing,  
never bleed the refrigerant  
gas into the atmosphere  
while transferring the  
refrigerant. (Fig. 3)  
Liquid  
Open  
Refrigerant  
cylinder  
Do not use the refrigerant if the amount in the  
charging cylinder is less than 20%.  
Fig. 3  
58  
11-6. In Case Refrigerant is Leaking  
Never attempt to charge additional refrigerant when refrigerant has been leaking  
CAUTION  
from the unit. Follow the procedure described below to locate points of leaks and  
carry out repairs, then recharge the refrigerant.  
(1) Detecting Leaks  
Use the detector for R410A to locate refrigerant leak  
points.  
(1) Detect leaks  
(2) Recovering refrigerant  
Never release the gas to the atmosphere; recover  
OK  
residual refrigerant using the refrigerant recovery unit for  
R410A, instead.  
(2) Recover refrigerant  
Do not reuse the recovered refrigerant because its  
composition will have been altered.  
OK  
(3) Welding leaking points  
Confirm again that no residual refrigerant exists in the unit  
before starting welding.  
(3) Weld leaking points  
OK  
Weld securely using flux and wax for R410A.  
Prevent oxide film from forming inside the tubes utilizing  
substitution with nitrogen (N2) in the refrigerant circuit of  
the unit. Leave ends of tubes open during welding.  
(4) Checking for sealing  
(4) Check for sealing  
OK  
Use nitrogen gas for the pressurized gas, and never use  
a refrigerant other than R410A. Also do not use oxygen or  
any flammable gas.  
(5) Evacuation  
(5) Evacuation  
OK  
Use a solenoid valve-installed vacuum pump so that  
even if power is cut off in the middle of evacuation of air  
due to a power interruption, the valve will prevent the  
pump oil from flowing back.  
The equipment may be damaged if moisture remains in  
the tubing, thus carry out the evacuation thoroughly.  
(6) Recharge  
When using a vacuum pump with exhaust air volume  
more than 0.883 cu.ft./min. and ultimate vacuum pressure  
rate of 50 micron Hg.  
Standard time for evacuation  
Length of tubing  
Less than 33 ft. (10 m)  
More than 33 ft. (10 m)  
Evacuation time  
More than 10 minutes  
More than 15 minutes  
(6) Recharging  
Recharge unit in the same manner explained on the  
previous page "(5) Recharging."  
59  
11-7. Charging Additional Refrigerant  
11-7-1. When Tubes are Extended  
Observe the proper amount of refrigerant as stated in this service manual or the installation manual that came  
with the indoor unit. Charge additional refrigerant in liquid state only.  
Never charge additional refrigerant if refrigerant is leaking from the unit. Follow  
CAUTION  
instructions given in "11-6. In Case Refrigerant is Leaking" and completely carry  
out repairs. Only then should you recharge the refrigerant.  
11-8. Retro-Fitting Existing Systems  
11-8-1. Use of Existing Units  
Never use new refrigerant R410A for existing units which use R22. This will cause the air conditioner to  
operate improperly and may result in a hazardous condition.  
11-8-2. Use of Existing Tubing  
If replacing an older unit that used refrigerant R22 with a R410A unit, do not use its existing tubing. Instead,  
completely new tubing must be used.  
60  
APPENDIX A INSTRUCTION MANUAL  
KHS1872 + CH1872  
KHS2472 + CH2472  
(OI-852-6-4180-801-00-2)  
A-1  
Features  
This air conditioner is an inverter type unit that automatically adjusts capacity as appropriate. Details on these functions  
are provided below; refer to these descriptions when using the air conditioner.  
Microprocessor Controlled Operation  
Automatic Switching between Cooling and  
Heating  
This unit automatically switches between cooling  
operation and heating operation according to the  
difference between the room temperature and the  
temperature setting.  
The interior compartment of the remote control unit  
contains several features to facilitate automatic  
operation, easy logically displayed for easy use.  
Simple One-touch Wireless Remote Control  
The remote control unit has several features to  
facilitate automatic operation.  
Hot Start Heating System  
Right from the start, the air is warm and  
comfortable. This system prevents any cold blasts  
at the beginning while the heat pump is warming  
up, or even defrosting.  
24-Hour ON or OFF Timer  
This timer can be set to automatically turn the unit  
on or off at any time within a 24 hour period.  
1-Hour OFF Timer  
This timer can be set to automatically turn off the  
unit at any time after one hour.  
Automatic Restart Function for Power Failure  
Even when power failure occurs, preset  
programmed operation can be reactivated once  
power resumes.  
Night Setback  
Pressing this button changes the setting of the  
room temperature thermostat, allowing you to set  
the temperature at whatever level that you find  
comfortable.  
High Power Operation  
If not in Auto Operation, the unit operates at  
maximum output for 30 minutes, regardless of the  
desired temperature.  
The fan speed is 1 step above “High”.  
Automatic and 3-step Fan Speed  
Auto/High/Medium/Low  
Quiet Operation  
The fan rotates slower than the fan speed setting to  
provide a quieter operating sound.  
Air Sweep Control  
This function moves a flap up and down in the air  
outlet, directing air in a sweeping motion around the  
room and providing comfort in every corner.  
ION Operation  
While it is operating, the unit generates negative  
ions that freshen up the air in the room.  
Auto. Flap Control  
This automatically sets the flap to the optimum  
position during heating, cooling, and drying  
operation.  
Anti-Mold Filter  
This unit is equipped with an anti-mold filter that  
inhibits the growth of mold and bacteria.  
Air Clean Filter  
An air filter that eliminates unpleasant odors and  
cleans the air is available.  
Purchase a replacement filter at your local dealer.  
(model STK-FDXB)  
OI-801-2-EG  
2
Contents  
Page  
Features...................................................................................................................2  
Product Information..................................................................................................3  
Alert Symbols...........................................................................................................3  
Installation Location .................................................................................................4  
Electrical Requirements...........................................................................................4  
Safety Instructions....................................................................................................4  
Names of Parts ........................................................................................................5  
Using the Remote Control Unit ..............................................................................10  
Operation with the Remote Control Unit ................................................................12  
1. Automatic Operation .....................................................................................12  
2. Manual Operation .........................................................................................13  
3. Adjusting the Fan Speed...............................................................................14  
4. Fan Only........................................................................................................14  
5. Night Setback Mode......................................................................................15  
6. QUIET Mode.................................................................................................16  
7. HIGH POWER Mode ....................................................................................16  
8. ION Mode......................................................................................................16  
Special Remarks....................................................................................................17  
Setting the Timer....................................................................................................18  
Using the 1-Hour OFF Timer .................................................................................20  
Tips for Energy Saving...........................................................................................20  
Adjusting the Airflow Direction ...............................................................................21  
Operation without the Remote Control Unit ...........................................................22  
Care and Cleaning.................................................................................................22  
Troubleshooting......................................................................................................25  
Operating Range....................................................................................................25  
Product Information  
If you have problems or questions concerning your Air Conditioner, you will need  
the following information. Model and serial numbers are on the nameplate on the  
bottom of the cabinet.  
Model No. ______________________ Serial No. _______________________  
Date of purchase ___________________________________________________  
Dealer’s address ___________________________________________________  
Phone number ___________________  
Alert Symbols  
The following symbols used in this manual, alert you to potentially  
dangerous conditions to users, service personnel or the appliance:  
This symbol refers to a hazard or unsafe  
practice which can result in severe  
personal injury or death.  
This symbol refers to a hazard or unsafe  
CAUTION  
practice which can result in personal injury  
or product or property damage.  
OI-801-3EG  
3
Installation Location  
We recommend that this air conditioner be installed properly by qualified  
installation technicians in accordance with the Installation Instructions  
provided with the unit.  
Before installation, check that the voltage of the electric supply in your home or  
office is the same as the voltage shown on the nameplate.  
Do not install this air conditioner where there are fumes or flammable  
gases, or in an extremely humid space such as a greenhouse.  
Do not install the air conditioner where excessively high heat-  
generating objects are placed.  
Avoid: To protect the air conditioner from heavy corrosion, avoid installing the outdoor  
unit where salty sea water can splash directly onto it or in sulphurous air near a  
spa.  
Electrical Requirements  
1. All wiring must conform to the local electrical codes. Consult your dealer or a  
qualified electrician for details.  
2. Each unit must be properly grounded with a ground (or earth) wire or through  
the supply wiring.  
3. Wiring must be done by a qualified electrician.  
Safety Instructions  
Read this Instruction Manual carefully before using this air conditioner. If  
you still have any difficulties or problems, consult your dealer for help.  
This air conditioner is designed to give you comfortable room conditions.  
Use this only for its intended purpose as described in this Instruction  
Manual.  
Never use or store gasoline or other flammable vapor or liquid near the  
air conditioner — it is very dangerous.  
This air conditioner has no ventilator for intaking fresh air from  
outdoors. You must open doors or windows frequently when you use  
gas or oil heating appliances in the same room, which consume a lot of  
oxygen from the air. Otherwise there is a risk of suffocation in an  
extreme case.  
Do not turn the air conditioner on and off from the power mains switch.  
Use the ON/OFF operation button.  
Do not stick anything into the air outlet of the outdoor unit. This is  
dangerous because the fan is rotating at high speed.  
Do not let children play with the air conditioner.  
CAUTION  
Do not cool or heat the room too much if babies or invalids are present.  
OI-801-4-EG  
4
Names of Parts  
Air intakes  
INDOOR UNIT  
Air outlet  
Remote control unit  
Drain hose  
Refrigerant tubes  
OUTDOOR UNIT  
Air outlet  
This illustration is based on the external view of a standard model.  
Consequently, the shape may differ from that of the air conditioner which you  
have selected.  
NOTE  
This air conditioner consists of an indoor unit and an outdoor unit. You can  
control the air conditioner with the remote control unit.  
Air Intake Air from the room is drawn into this section and passes through air filters which  
remove dust.  
Air Outlet Conditioned air is blown out of the air conditioner through the air outlet.  
Remote Control Unit The wireless remote control unit controls power ON/OFF, operation mode  
selection, temperature, fan speed, timer setting, and air sweeping.  
Refrigerant Tubes The indoor and outdoor units are connected by copper tubes through which  
refrigerant gas flows.  
Drain Hose Moisture in the room condenses and drains off through this hose.  
Outdoor (Condensing) Unit The outdoor unit contains the compressor, fan motor, heat exchanger coil, and  
other electrical components.  
OI-801-5EG  
5
Unit Display and Operation Button  
INDOOR UNIT  
IMPORTANT  
OPERATION lamp  
TIMER lamp  
QUIET lamp  
ION lamp  
Avoid using radio equipment  
such as mobile phone near  
(within 4 ft.) the remote  
control receiver. Some radio  
equipment may cause  
QUIET  
OPERATION button  
malfunction of the unit.  
If the trouble happens,  
disconnect power and restart  
the air conditioner after a few  
minutes.  
REMOTE CONTROL receiver  
REMOTE CONTROL receiver This section picks up infrared signals from the remote control unit (transmitter).  
OPERATION button When the remote control cannot be used, pressing this button enables heating  
and cooling operation.  
Each time this button is pressed, the type of operation conducted is indicated by  
the changing color of the OPERATION lamp. Press the button and select the  
lamp color that suits your preference for operation.  
Cooling operation  
(green)  
Heating operation  
(red)  
Stop  
(lamp off)  
OPERATION lamp This lamp lights when the system is in the continuous AUTO (red or green),  
HEAT (red), DRY (orange), COOL (green) and FAN (green) mode.  
The OPERATION lamp lights up red and orange alternately when the system is  
defrosting.  
TIMER lamp This lamp lights when the system is being controlled by the timer.  
QUIET lamp This lamp lights during operation in the QUIET mode.  
ION lamp This lamp lights during operation in the ION mode while the indoor unit is  
operating.  
The unit’s display lamps are dimmed during operation in the NIGHT SETBACK  
mode.  
NOTE  
OI-801-6-EG  
6
Remote Control Unit (Display)  
Displayed when transmitting data  
Displayed when indoor unit  
sensor is in use  
Displayed when setting  
temperature  
Displayed when temperature is  
shown  
Displayed when setting timer  
Displayed when the  
time display is set to  
12-hour time.  
Symbols  
(4) Timer  
(1) Operation mode  
24-hour clock with ON/OFF  
program Timer............................  
AUTO .........................................  
HEAT..........................................  
MILD DRY ..................................  
COOL.........................................  
ON Timer....................................  
OFF Timer..................................  
1-hour OFF Timer.......................  
FAN ............................................  
(2) Fan speed  
(5) NIGHT SETBACK ......................  
(6) Confirmation of transmission .....  
Automatic operation ...................  
(7) Auto. flap indication....................  
Flap angle indication ..................  
Sweep indication........................  
HIGH .........................................  
MEDIUM.....................................  
LOW...........................................  
(8) High power operation.................  
(9) Quiet operation...........................  
(10)ION operation ...........................  
(3) Temperature setting  
60 – 86 °F  
When set to 80 °F  
temperature indication................  
OI-801-7EG  
7
Remote Control Unit  
Sensor  
Transmitter  
(Cover closed)  
Display  
ON/OFF operation button  
1 HR. TIMER button  
ION button  
Temperature setting buttons (TEMP.)  
QUIET button  
MODE selector button  
NIGHT SETBACK button  
HIGH POWER button  
FAN SPEED selector button  
FLAP button  
ON TIME  
setting  
buttons  
Advance button  
Return button  
OFF TIME  
setting  
buttons  
Advance button  
Return button  
CLOCK button  
CANCEL button  
SENSOR button  
Time display selector button  
ACL button  
ADDRESS switch  
NOTE  
Temperature display  
selector button  
The illustration above pictures the remote control unit after the cover has been  
opened.  
Transmitter When you press the buttons on the remote control unit, the  
mark appears in  
the display to transmit the setting changes to the receiver in the air conditioner.  
Sensor A temperature sensor inside the remote control unit senses the room  
temperature.  
Display Information on the operating conditions is displayed while the remote control unit  
is switched on. If the unit is turned off, FLAP setting and FAN SPEED setting are  
not displayed.  
ION button  
: This button is for turning the negative ions generated during operation on  
and off.  
ON/OFF operation button This button is for turning the air conditioner on and off.  
1 HR. TIMER button  
(1-HOUR OFF TIMER)  
: When you press this button, regardless of whether the unit is operating or  
stopping, the unit operates for one hour and then shuts down.  
OI-801-8-EG  
8
Remote Control Unit (continued)  
Temperature setting buttons Press the  
(TEMP.) Press the  
button to increase the set temperature.  
button to reduce the set temperature.  
The temperature setting changes by 1 °C or 2 °F each time one of the TEMP.  
buttons is pressed.  
QUIET button  
: When you press this button, the fan rotates slower than the fan speed  
setting to provide a quieter operating sound.  
MODE selector button Use this button to select AUTO, HEAT, DRY, COOL or FAN mode.  
(AUTO)  
: When this setting is selected, the air conditioner calculates the difference  
between the thermostat setting and the room temperature and  
automatically switches to the ‘‘COOL’ or ‘‘HEAT’’ mode as appropriate.  
(HEAT)  
(DRY)  
: The air conditioner makes the room warmer.  
: The air conditioner reduces the humidity in the room.  
: The air conditioner makes the room cooler.  
(COOL)  
(FAN)  
: The air conditioner works only as a circulation fan.  
FAN SPEED selector button  
: The air conditioner automatically decides the fan speeds.  
: High fan speed  
: Medium fan speed  
: Low fan speed  
NIGHT SETBACK button For details, see “5. Night Setback Mode”. When you press this button in the  
HEAT, DRY or COOL mode, the mark appears in the display, and the remote  
control unit will automatically adjust the set temperature to save energy.  
FLAP button Press this button either to select the setting of the airflow direction to the auto.  
flap in each mode or one of the six possible positions manually or to select the  
sweep function which moves the flap up and down automatically.  
: Auto flap setting: If selected in a heating operation, the flap is set to  
position (3) in the following chart. If selected in a cooling or dry operation,  
the flap is set at position (7) in the following chart.  
: The airflow direction can be set manually. (six positions)  
: The flap moves up and down automatically.  
When you press the FLAP button, the air flow direction will be changed one by  
one as follows.  
NOTE  
SWEEP  
HIGH POWER button  
: If this button is pressed during HEAT, DRY, COOL or FAN operation, the  
unit operates at maximum output for 30 minutes, regardless of the desired  
temperature.  
The fan speed is 1 step above “High”.  
ON TIME/OFF TIME setting No display: The timer does not operate.  
buttons  
: The air conditioner starts at the set time.  
: The air conditioner stops at the set time.  
: The air conditioner stops and starts, or starts and stops, at the  
set times every day. For details, see “Setting the Timer”.  
The indoor fan runs continuously when the system is in normal operation. It does not turn off when the  
desired room temperature is reached. If Night Set Back mode is selected, the fan will turn off  
intermittently during cooling operation in order to control air flow.  
NOTE  
OI-801-9EG  
9
Remote Control Unit (continued)  
SENSOR button When you press this button (use a small-tipped object such as a ballpoint pen),  
the  
mark will appear at the display. And the room temperature is detected by  
the sensor which is built into the indoor unit and the air conditioner is controlled  
accordingly.  
If the remote control is located near a heat source, such as a space heater or in  
NOTE  
direct sunlight, press the SENSOR button to switch to the sensor on the indoor  
unit.  
Temperature Display Selector This switches the temperature display between °C and °F.  
button  
Time Display Selector button This switches the time display between 24-hour time and 12-hour time.  
ACL button (ALL CLEAR) Puts the remote control unit into pre-operation status. Always press this button  
after replacing the batteries.  
ADDRESS switch  
The address switch changes to prevent mixing of signals from remote control  
units when two air conditioners are installed next to each other. Normally, the  
address switch is set to A. For more information, please contact the dealer  
where you made the purchase.  
Normally, the tabs on the remote control unit should not be bent.  
The remote control unit sends the temperature signal to the air conditioner regularly at five minute  
intervals. If the signal from the remote control unit stops for more than 15 minutes due to the loss of the  
remote control unit or other trouble, the air conditioner will switch to the temperature sensor which is built  
into the indoor unit and control the room temperature. In these cases, the temperature around the remote  
control unit may differ from the temperature detected at the air conditioner’s position.  
NOTE  
Using the Remote Control Unit  
How to Install Batteries  
1. Slide the cover in the direction  
indicated by the arrow and remove it.  
2. Install two AAA alkaline batteries.  
Make sure the batteries point in the  
direction marked in the battery  
compartment.  
3. Use a thin object such as the tip of a  
pen to press the ACL button.  
ACL button  
The batteries last about six months, depending on how much you use  
the remote control unit. Replace the batteries when the remote control  
unit’s display fails to light, or when the remote control cannot be used to  
change the air conditioner’s settings.  
NOTE  
Use two fresh leak-proof type-AAA alkaline batteries.  
In replacing batteries, follow the instructions as mentioned in the sub-  
section “How to Install Batteries”.  
If you do not use the remote control unit more than 1 month, take out the  
batteries.  
OI-801-10-EG  
10  
Using the Remote Control Unit (continued)  
How to Use the Remote When using the remote control unit, always point the unit’s transmitter head  
Control Unit directly at the air conditioner’s receiver.  
Air conditioner  
(Indoor unit)  
Receiver  
Remote control  
unit  
(Transmitter head)  
Remote Control Unit The remote control unit may be operated either from a non-fixed position or from  
Installation Position a wall-mounted position. To ensure that the air conditioner operates correctly, DO  
NOT install the remote control unit in the following places:  
DO NOT  
In direct sunlight  
Behind a curtain or other places where it is covered  
More than 26 feet (8 m) away from the air conditioner  
In the path of the air conditioner’s airstream  
Where it may become extremely hot or cold  
Where it may be subject to electrical or magnetic noise  
Where there is an obstacle between the remote control unit and air  
conditioner (since a check signal is sent from the remote control unit every 5  
minutes)  
Mounting the Remote Control Before mounting the remote control unit, press the ON/OFF operation button at  
Unit the mounting location to make sure that the air conditioner operates from that  
location. The indoor unit should make a beeping sound to indicate that it has  
received the signal.  
Rear side  
Remote control  
unit mount  
Press  
Mounting screws  
5/32 x 5/8" (4 x 16 mm)  
(included)  
Hole  
Set in  
place  
To prevent loss of the remote control unit,  
you can connect the remote control unit to  
the mount by passing a string through the  
remote control unit and attachment hole.  
To take out the remote control unit, pull it forward.  
When Holding the Remote  
Control Unit  
When using the remote control unit and during air conditioner operation, the  
transmitter on the remote control unit should be pointed toward the receiver  
on the indoor unit.  
Make sure that there are no objects between the remote control unit and  
receiver which could block the signal.  
OI-801-11EG  
11  
Operation with the Remote Control  
Unit  
This unit automatically switches between cooling operation and heating operation  
according to the difference between the room temperature and the temperature  
setting.  
1. Automatic Operation  
STEP 2  
STEP 1  
Check that the circuit breaker on the power panel is turned on.  
NOTE  
Once  
mode is selected and the unit is preset by following the steps below, you  
can have the air conditioner automatically bring the room to the desired  
temperature simply by pressing the ON/OFF operation button.  
STEP 1  
STEP 2  
Press the MODE selector button to  
Press the ON/OFF operation button.  
.
To stop the air conditioner, press the ON/OFF operation button again.  
To change the temperature setting; press the temperature setting buttons and  
change the setting to the desired temperature.  
NOTE  
OI-801-12-EG  
12  
Operation with the Remote Control Unit (continued)  
2. Manual Operation  
STEP 2  
STEP 3  
STEP 1  
STEP 4  
STEP 5  
Check that the circuit breaker on the power panel is turned on.  
NOTE  
If the automatic operation settings of the unit do not meet your needs, press the  
setting buttons as described below and change the settings as desired.  
STEP 1  
Press the MODE selector button and select the desired mode.  
For heating operation  
For dehumidifying operation  
For cooling operation  
For fan only operation  
STEP 2  
STEP 3  
To start the air conditioner, press the ON/OFF operation button.  
Press the TEMP. setting buttons to change the temperature  
setting to the desired temperature.  
Adjustable temperature range:  
30 °C max.  
16 °C min.  
or  
86 °F max.  
60 °F min.  
STEP 4  
STEP 5  
Set the FAN SPEED selector button to the setting you want.  
Press the FLAP button and set the airflow direction as desired.  
(Refer to “Adjusting the Airflow Direction” on page 21.)  
To stop the air conditioner, press the ON/OFF operation button again.  
OI-801-13EG  
13  
Operation with the Remote Control Unit (continued)  
Choose the best position in the room for the remote control unit, which also  
acts as the sensor for room comfort and transmits the operating instructions.  
Once you’ve found this best position, always keep the remote control unit  
there.  
NOTE  
This appliance has a built-in 5-minute time delay circuit to ensure reliable  
operation. When the operation button is pressed, the compressor will start  
running within three minutes. In the event of power failure, the unit will stop.  
3. Adjusting the Fan Speed  
A. Automatic fan speed  
Simply set the FAN SPEED selector button to the  
position.  
This automatically sets the best fan speed for the room temperature.  
B. Manual fan speed  
4. Fan Only  
If you want to adjust fan speed manually during operation, just set the FAN  
SPEED selector button as desired. [  
,
, or  
]
STEP 2  
STEP 1  
STEP 3  
If you want to circulate air without any temperature control, follow these steps:  
STEP 1  
STEP 2  
STEP 3  
Press the MODE selector button to switch to the fan mode  
Press the ON/OFF operation button.  
.
Press the FAN SPEED selector button to select the fan speed of  
your choice ( or ).  
,
OI-801-14-EG  
14  
Operation with the Remote Control Unit (continued)  
5. Night Setback Mode  
Night Setback Mode is used for saving energy.  
Press the NIGHT SETBACK button while operation.  
The  
mark appears in the display.  
To release the night setback function, press the NIGHT SETBACK button again.  
A. In Cooling and DRY  
Mode: ( and  
When the night setback mode is selected, the air conditioner automatically  
raises the temperature setting 2 °F when 30 minutes have passed after the  
selection was made, and then another 2 °F after another 30 minutes have  
passed, regardless of the indoor temperature when night setback was  
selected. This enables you to save energy without sacrificing comfort. This  
function is convenient when gentle cooling is needed.  
)
2 °F  
Setting  
temperature  
2 °F  
30 min.  
30 min.  
Press the NIGHT  
SETBACK button  
Time  
B. In Heating Mode: (  
)
When the night setback mode is selected, the air conditioner automatically  
lowers the temperature setting 4 °F when 30 minutes have passed after the  
selection was made, and then another 4 °F after another 30 minutes have  
passed, regardless of the indoor temperature when night setback was  
selected. This enables you to save energy without sacrificing comfort. This  
function is convenient when gentle heating is needed.  
Setting  
temperature  
4 °F  
4 °F  
30 min.  
30 min.  
Press the NIGHT  
SETBACK button  
Time  
OI-801-15EG  
15  
Operation with the Remote Control Unit (continued)  
6. QUIET Mode  
QUIET Mode is used to reduce the fan sound of the indoor unit.  
Press the QUIET button.  
The  
mark appears in the display.  
To cancel, press QUIET button again.  
In QUIET Mode, the fan rotates at a slower speed than the fan speed setting.  
If the unit is already operating with a very low airflow, the fan sound may not  
change even if the QUIET button is pressed.  
7. HIGH POWER Mode  
HIGH POWER mode can be used to increase the output of the indoor unit for all  
operation modes except automatic operation.  
Press the HIGH POWER button.  
The  
mark appears in the display.  
To cancel, press HIGH POWER button again.  
When the HIGH POWER button is pressed, the unit operates at maximum  
output for 30 minutes, regardless of the desired temperature. The fan speed is  
1 step above “High”.  
HIGH POWER Mode cannot be used when the operation mode is Automatic  
Operation.  
QUIET Mode and HIGH POWER Mode cannot be used at the same time.  
• When set to High fan speed during heating operation, the fan  
runs at High fan speed even though the mark is displayed.  
NOTE  
• Depending on the operating conditions, the fan speed may be  
increased by a small amount only.  
8. ION Mode  
The ION mode is used during operation to generate negative ions that freshen up  
the air in the room.  
Press the ION button.  
The  
mark appears in the display.  
To cancel, press ION button again.  
The indoor unit’s ION lamp lights up while negative ions are being generated.  
ION “on” is the remote control unit’s initial setting.  
The negative ions are generated from the negative ion generator.  
OI-801-16-EG  
16  
Special Remarks  
‘‘DRY’’ ( ) Operation  
How it works?  
Once the room temperature reaches the level that was set, the unit’s operation  
frequency is changed automatically.  
During DRY operation, the fan speed automatically runs at lower speed for  
providing a comfortable breeze.  
‘‘DRY’’ operation is not possible if the indoor temperature is 59 °F or less.  
Heating ( ) Operation  
Heating performance  
Because this air conditioner heats a room by drawing in the heat of the  
outside air (heat pump system), the heating efficiency will fall off when the  
outdoor temperature is very low. If sufficient heat cannot be obtained with this  
air conditioner, use another heating appliance together with it.  
Defrosting  
When the outdoor temperature is low, frost or ice may form on the heat  
exchanger coil, reducing heating performance. When this happens, a  
microcomputer defrosting system operates. At the same time, the fan on the  
indoor unit stops and the OPERATION lamp lights up red and orange  
alternately until defrosting is completed. Heating operation restarts after  
several minutes. (This interval will vary slightly depending upon the outdoor  
temperature and the way in which frost forms.)  
Cold draft prevention  
For several minutes after the start of heating operation, the indoor fan runs at  
lower speed until the indoor heat exchanger coil has warmed up sufficiently.  
However, the fan may remain stopped when the room temperature is low. This  
is because the COLD DRAFT PREVENTION SYSTEM is operating.  
Sometimes the indoor unit may not get to the set fan speed such as LOW and  
QUIET under cool operation at very low outdoor temperatures due to the  
indoor unit being protected from ice or frost.  
Cooling ( ) Operation  
In the event of power failure, the unit will stop. When the power is resumed,  
the unit will restart automatically within five minutes by the remote control unit.  
Power failure during  
operation  
Clicking Sound  
Clicking sound is heard from  
the air conditioner  
In heating or cooling operation, any plastic parts may expand or shrink due to  
a sudden temperature change. In this event, a clicking sound may occur. This  
is normal, and the sound will soon disappear.  
The remote control unit sends the setting condition to the air conditioner  
regularly at five minute intervals.  
Remote Control Unit  
OI-801-17EG  
17  
Setting the Timer  
In the descriptions below, the following settings are used for the temperature and  
time indicator selector button on the bottom front section of the remote control.  
NOTE  
Temperature: °F  
Time: AM, PM  
(Example) To set to 10:30 pm.  
1. How to set the present  
time  
Operation  
Indication  
1. Press the CLOCK button once if  
The time indication alone flashes.  
the time indicator is not flashing.  
2. Press the Advance, Return ( ,  
) button until PM 10:30 is  
displayed.  
The time can be set in 1-minute  
increments. Holding down the button  
advances the time rapidly in 10-minute  
increments.  
3. Press the CLOCK button again.  
This completes the setting of the  
current time.  
(Example) To stop the air conditioner at 11:00 am.  
2. How to set the OFF time  
1. Press the OFF TIME setting  
The timer  
indication is displayed,  
button once.  
and the present OFF time is shown.  
2. Press the Advance, Return ( ,  
) button until AM 11:00 is  
displayed.  
The timer indication blinks.  
The time can be set in 10-minute  
increments. Holding down the button  
advances the time rapidly in 10-minute  
increments.  
3. Wait a few seconds, and then the The timer  
indication stops  
setting is complete.  
blinking and the present time is  
displayed.  
OI-801-18-EG  
18  
Setting the Timer (continued)  
(Example) To start operation at 7:10 am.  
3. How to set the ON time  
Operation  
Indication  
indication is  
1. Press the ON TIME setting  
The timer  
button once.  
displayed, and the present ON time  
is shown.  
2. Press the Advance, Return ( ,  
) button until AM 7:10 is  
displayed.  
The timer  
indication blinks.  
The time can be set in 10-minute  
increments. Holding down the  
button advances the time rapidly in  
10-minute increments.  
3. Wait a few seconds, and then  
The timer  
indication stops  
the setting is complete.  
blinking and the present time is  
displayed.  
(Example) To start operation at 7:10 am. and stop the air conditioner at 11:00 am.  
4. How to set DAILY ON/OFF  
REPEAT timer  
10:30 pm.  
Present time  
7:10 am.  
ON  
11:00 am.  
OFF  
1. Set the timer ON/OFF times as  
The present time 10:30 pm. and  
are displayed.  
shown in 2-1, 2, 3 and 3-1, 2, 3.  
The ON/OFF combination timer uses the current time as  
the reference, and it is activated starting from whichever  
set time comes first.  
NOTE  
With the ON/OFF combination timer, the settings are  
repeated every day.  
You can check the timer ON/OFF times after you have set  
them by pressing the ON TIME and OFF TIME setting  
buttons.  
To cancel a timer program  
Press the CANCEL button.  
When either an ON or OFF timer is to be canceled, press the button  
corresponding to the timer whose program is to be canceled, and then press  
the CANCEL button.  
The airflow direction, fan speed and temperature setting can be changed after  
a timer program has been set even when the unit is stopped. Even when  
operation is stopped during an ON timer program, the unit will start operating  
when the set time is reached provided that the program is not canceled.  
When the ON timer and OFF timer are set to the same time, the timer  
operates as if it is turned off.  
NOTE  
OI-801-19EG  
19  
Using the 1-Hour OFF Timer  
1. 1-Hour OFF Timer This function causes the unit to operate for one hour and then stop,  
regardless of whether the unit is on or off when this button is pressed.  
The  
indicator in the display indicates that this function is operating.  
Setting procedure:  
Regardless of whether the unit is operating or stopped, press the 1 HR. TIMER  
button.  
appears in the display.  
Cancellation procedure:  
Press the ON/OFF operation button to turn the unit off, wait for the unit to stop  
operating, and then press the ON/OFF operation button again.  
The 1-Hour Timer function is now cancelled and the unit operates normally.  
If, while the 1-Hour Timer function is operating, the 1HR. TIMER button is  
pressed once to cancel the function and then again, the unit continues to  
operate for one hour from that point in time and then stops.  
NOTE  
It is not possible to use the OFF Timer and 1-Hour OFF Timer together.  
Whichever function is set last takes precedence. If the 1 HR. TIMER button is  
pressed while the TIMER OFF function operates, the OFF Timer is cancelled  
and the unit will stop operating one hour later.  
2. Operation together with the The 1-Hour OFF Timer setting is given priority over the DAILY ON/OFF REPEAT  
DAILY ON/OFF REPEAT Timer setting.  
Tips for Energy Saving  
Do not  
Block the air intake and outlet of the unit. If they are obstructed, the unit  
will not work well, and may be damaged.  
Let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the  
room.  
Do  
Always try to keep the air filter clean. (Refer to “Care and Cleaning”.) A  
clogged filter will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other  
openings closed.  
OI-801-20-EG  
20  
Adjusting the Airflow Direction  
1. Horizontal The horizontal airflow can be adjusted by moving the vertical vanes with your  
hands to the left or right.  
When the humidity is high, the vertical vanes should be in the front  
CAUTION  
position during the cooling or dehumidifying operation. If the vertical  
vanes are positioned all of the way to the right or left, condensation may  
begin to form around the air vent and drip down.  
2. Vertical The vertical airflow can be adjusted by moving the flap with the remote control  
unit. Do not move the flap with your hands. Confirm that the remote control unit  
has been turned on. Use the FLAP button to set either the sweep function or one  
of the six airflow direction settings.  
COOL  
SWEEP  
DRY  
FAN  
SWEEP  
HEAT  
A. Sweep function  
B. Setting the airflow manually  
Referring to the above illustration, use the  
The flap starts moving up and down to  
deliver air over the sweep range.  
FLAP button to set the airflow direction  
within the range used during the heating,  
cooling, or dehumidifying operation.  
C. Auto flap function  
The flap is set to the recommended  
position.  
The flap automatically closes when the unit is off.  
NOTE  
During the heating operation, the fan speed will be very low and the flap will  
be in the horizontal position (position ) until the air being blown out of the  
unit begins to warm. Once the air warms up, the flap position and fan speed  
change to the settings specified with the remote control.  
Use the FLAP button on the remote control to adjust the position of the  
flap. If you move the flap by hand, the flap position according to the  
remote control and the actual flap position may no longer match. If this  
should happen, shut off the unit, wait for the flap to close, and then turn  
on the unit again; the flap position will now be normal again.  
CAUTION  
Do not have the flap pointed down during cooling operation.  
Condensation may begin to form around the air vent and drip down.  
OI-801-21EG  
21  
Operation without the Remote  
Control Unit  
INDOOR UNIT  
If you have lost the remote control unit or it has trouble, follow the steps below.  
When the air conditioner is not running  
Each time the OPERATION button is pressed, the type of operation conducted is  
indicated by the changing color of the OPERATION lamp. Press the button and  
select the lamp color that suits your preference for operation.  
Cooling operation  
(green)  
Heating operation  
(red)  
Stop  
(lamp off)  
OPERATION button  
The temperature is set to the room temperature minus 4 °F during the cooling  
operation and to the room temperature plus 4 °F during the heating operation,  
and the fan speed and flap are set to Auto.  
NOTE  
Care and Cleaning  
1. For safety, be sure to turn the air conditioner off and also to disconnect  
the power before cleaning.  
2. Do not pour water on the indoor unit to clean it. This will damage the  
internal components and cause an electric shock hazard.  
Casing and Grille (Indoor Unit) Clean the casing and grille of the indoor unit with a vacuum cleaner brush, or  
wipe them with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid  
detergent. When cleaning the grille, be careful not to force the vanes out of place.  
1. Never use solvents, or harsh chemicals when cleaning the indoor unit.  
CAUTION  
Do not wipe the plastic casing using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if  
handled improperly; be especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be  
cleaned every year. Consult your dealer or service center.  
OI-801-22-EG  
22  
Care and Cleaning (continued)  
Anti-Mold Filter The anti-mold filter behind the air intake grille should be checked and cleaned at  
least once every two weeks.  
How to remove the anti-mold 1. Grasp both ends of the air  
Air intake grille  
filter  
intake grille, and remove it by  
opening towards the front and  
pulling towards you.  
2. Remove the anti-mold filter  
attached to the rear of the air  
intake grille.  
Anti-mold filter  
Cleaning Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter,  
wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.  
How to replace the anti-mold 1. With the FRONT mark of the  
Anti-mold filter  
filter  
anti-mold filter at the front,  
align the two indentions near  
the mark with the hooks at the  
rear of the air intake grille, and  
then mount the anti-mold filter.  
FRONT mark  
Hook  
2. Allow the edge of the air intake  
grille to slide into the top of the  
indoor unit, and then insert it  
all the way inside.  
Groove  
Pin  
Air intake grille  
3. To attach the air intake grille to  
the indoor unit, press its  
bottom right and left corners as  
well as its bottom center into  
place.  
Air intake grille  
Attach so that the round pins at the top right and left corners of the air intake grille  
are inserted into the grooves at the top right and left of the indoor unit.  
NOTE  
OI-801-23EG  
23  
Care and Cleaning (continued)  
Air Clean Filter The air clean filter removes dust and dirt from the air, and reduces odors and smoke from  
tobacco.  
This air clean filter cannot remove harmful gases or vapors nor ventilate air in the  
room. You must open doors or windows frequently when you use gas or oil heating  
appliances. Otherwise there is a risk of suffocation in extreme cases.  
How to install the air The air clean filter needs to be installed behind the air intake grille.  
clean filter 1. Remove the air intake grille.  
2. Install the air clean filter in the position  
shown in the figure.  
3. Remount the air intake grille.  
Air clean filter  
How to clean the air  
clean filter  
In general, the filter should be sucked to remove dust in low fan speed of a vacuum  
cleaner once every three months.  
If there is heavily grime on the filter, soak the filter in lukewarm water with neutral  
detergent diluted 1:500 for 1 to 2 minutes then wash it.  
Rinse the filter in clean water, then let it dry on the towel in room temperature.  
Do not bend nor give excessive force onto the air clean filter.  
If the filter surface is heavily blocked with dirt or damaged, replace it with new one.  
Purchase a replacement filter at your local dealer. (model STK-FDXB)  
NOTE  
Cleaning the main unit  
and remote control  
unit  
Wipe clean using a soft, dry cloth.  
To remove stubborn dirt, moisten a cloth in warm water no hotter than 104 °F, wring  
thoroughly, and then wipe.  
The air intake grille can be removed in order to wash it with water.  
Removing and Refer to “How to remove the anti-mold filter” and “How to replace the anti-mold filter” on  
remounting the air page 23.  
intake grille  
When using a footstool or the like, be careful not to let it tip over.  
CAUTION  
Washing the grille  
with water  
Clean the grille gently using a soft sponge, or the like. Then wipe away any remaining  
moisture.  
Neutral detergent may be used to remove stubborn dirt. Then rinse thoroughly with  
water and wipe away any remaining moisture.  
Cleaning the negative Follow the steps below when the generator has  
ion generator become dirty.  
For safety, be sure to turn the air conditioner  
off and also to disconnect the power before  
cleaning.  
Remove the dust on the negative ion generator.  
Use a toothbrush, etc. to dust off the end.  
Use a cotton swab, etc., to clean around the  
generator inside the plastic case, taking care  
not to touch the electrodes.  
Negative ion generator  
(metal electrodes inside  
plastic case)  
During use, the negative ion generator and other metal parts may become discolored:  
this is normal and not indicative of malfunctioning.  
If the dirt on and around the negative ion generator is left to build up, a puffing or  
sputtering sound will eventually be heard. In this case, clean the generator immediately.  
Do not apply excessive force while performing maintenance.  
NOTE  
OI-801-24-EG  
24  
Troubleshooting  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not  
work properly, contact your dealer or service center.  
Trouble  
Possible Cause  
1. Power failure.  
Remedy  
1. Restore power.  
Air conditioner does not run at all.  
2. Leakage circuit breaker tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Replace batteries.  
4. Batteries in remote control unit have  
run down.  
OPERATION lamp blinks and air  
conditioner does not operate.  
Trouble in system.  
Contact service center.  
Compressor runs but soon stops.  
Obstruction in front of condenser coil.  
1. Dirty or clogged air filter.  
Remove obstruction.  
Poor cooling (or heating) performance.  
1. Clean air filter to improve airflow.  
2. Eliminate heat source if possible.  
2. Heat source or many people in  
room.  
3. Doors and/or windows are open.  
3. Shut them to keep the heat (or cold)  
out.  
4. Obstacle near air intake or air  
discharge port.  
4. Remove it to ensure good airflow.  
5. Thermostat is set too high for  
cooling (or too low for heating).  
5. Set the temperature lower (or  
higher).  
6. (Outdoor temperature is too low for  
heating.)  
6. (Consult your dealer or try to use  
another heat appliance.)  
Clicking sound is heard from the air  
conditioner.  
In heating or cooling operation, any  
plastic parts may expand or shrink due  
to a sudden temperature change. In  
this event, a clicking sound may occur.  
This is normal, and the sound will soon  
disappear.  
OPERATION lamp lights but outdoor  
unit will not run.  
1. The use of cellular phones near the  
air conditioner may cause  
1. Turn off the power then restart the  
air conditioner after a while.  
disturbance to its normal operation.  
2. Consult your dealer.  
Operating Range  
The air conditioner is operable within the temperature ranges as listed below:  
Temperature  
Indoor air temperature  
Outdoor air temperature  
COOLING  
HEATING  
Max.  
Min.  
Max.  
Min.  
95 °F DB / 71 °F WB  
67 °F DB / 57 °F WB  
80 °F DB / 67 °F WB  
– DB / – WB  
115 °F DB  
0 °F DB  
75 °F DB / 65 °F WB  
0 °F DB  
OI-801-25EG  
25  
APPENDIX B INSTALLATION INSTRUCTIONS  
KHS1872 + CH1872  
KHS2472 + CH2472  
(II-852-6-4189-989-00-3)  
A-2  
INSTALLATION INSTRUCTIONS  
COOL/DRY/HEAT Model  
– Inverter Split System Air Conditioner –  
This air conditioner uses the new refrigerant R410A.  
NOTE  
Refrigerant service valve size = 5/16"  
Contents  
Model Combinations  
Page  
Combine indoor and outdoor units only as listed  
below.  
IMPORTANT!  
Please Read Before Starting .................................. 2  
Indoor Unit  
KHS1872  
KHS2472  
Outdoor Unit  
CH1872  
1. GENERAL .......................................................... 3  
1-1. Tools Required for Installation (not supplied)  
1-2. Accessories Supplied with Unit  
CH2472  
1-3. Optional Copper Tubing Kit  
1-4. Type of Copper Tube and Insulation Material  
1-5. Additional Materials Required for Installation  
Power Source:  
60 Hz, single-phase, 230/208 V  
2. INSTALLATION SITE SELECTION ................... 4  
2-1. Indoor Unit  
Be sure to read the yellow instruction sheet  
attached to the outdoor unit for models using the  
new refrigerant R410A.  
2-2. Outdoor Unit  
3. HOW TO INSTALL THE INDOOR UNIT ............. 6  
3-1. Remove the Rear Panel from the Unit  
3-2. Make a Hole  
3-3. Install the Rear Panel on the Wall  
3-4. Remove the Grille to Install the Indoor Unit  
3-5. Shape the Indoor Side Tubing  
3-6. Wiring Instructions  
7. REMOTE CONTROL UNIT INSTALLATION  
POSITION ......................................................... 23  
7-1. Mounting on a Wall  
3-7. Recommended Wire Length and Diameter  
3-8. Wiring Instructions for Inter-unit Connections  
3-9. Mounting  
8. ADDRESS SWITCH.......................................... 24  
8-1. Address Setting of the Remote  
Control Unit  
3-10. Drain Hose  
4. HOW TO INSTALL THE OUTDOOR UNIT ....... 16  
4-1. Wiring Instructions for the Outdoor Unit  
5. REFRIGERANT TUBING.................................. 17  
5-1. Use of the Flaring Method  
5-2. Flaring Procedure with a Flare Tool  
5-3. Caution before Connecting Tubes Tightly  
5-4. Connecting Tubing between Indoor and  
Outdoor Units  
5-5. Insulation of Refrigerant Tubing  
5-6. Taping the Tubes  
5-7. Finishing the Installation  
NOTE  
The illustrations are based on the typical appearance of  
a standard model. Consequently, the shape may differ  
from that of the air conditioner that you are installing.  
6. AIR PURGING................................................... 19  
I Air Purging with a Vacuum Pump (for Test Run)  
I Basic Functions of the Service Valves  
I Pump Down  
SANYO Commercial Solutions  
A Division of SANYO North America Corporation  
In Canada  
SANYO Canada Inc.  
Cornerstone Business Park,  
1062 Thorndale Avenue,  
1-300 Applewood Crescent, Concord  
Ontario, L4K 5C7, Canada  
Bensenville, IL 60106, U.S.A.  
85264189989003 © SANYO 2007  
W
IMPORTANT!  
Please Read Before Starting  
This air conditioning system meets strict safety and operating  
standards. As the installer or service person, it is an important  
part of your job to install or service the system so it operates  
safely and efficiently.  
When Installing…  
…In a Ceiling or Wall  
Make sure the ceiling/wall is strong enough to hold the  
unit’s weight. It may be necessary to construct a strong  
wood or metal frame to provide added support.  
For safe installation and trouble-free operation, you  
must:  
…In a Room  
G
Carefully read this instruction booklet before beginning.  
Properly insulate any tubing run inside a room to prevent  
“sweating” that can cause dripping and water damage to  
walls and floors.  
G
Follow each installation or repair step exactly as shown.  
G
Observe all local, state, and national electrical codes.  
G
Pay close attention to all warning and caution notices  
given in this manual.  
…In Moist or Uneven Locations  
Use a raised concrete pad or concrete blocks to provide a  
solid, level foundation for the outdoor unit. This prevents  
water damage and abnormal vibration.  
This symbol refers to a hazard  
or unsafe practice which can  
result in severe personal injury  
WARNING  
or death.  
…In an Area with High Winds  
This symbol refers to a hazard  
or unsafe practice which can  
result in personal injury or prod-  
uct or property damage.  
Securely anchor the outdoor unit down with bolts and a  
metal frame. Provide a suitable air baffle.  
CAUTION  
…In a Snowy Area (for Heat Pump-type Systems)  
Install the outdoor unit on a raised platform that is higher  
than drifting snow. Provide snow vents.  
If Necessary, Get Help  
These instructions are all you need for most installation  
sites and maintenance conditions. If you require help for a  
special problem, contact our sales/service outlet or your  
certified dealer for additional instructions.  
When Connecting Refrigerant Tubing  
• Use the flare method for connecting tubing.  
• Apply refrigerant lubricant to the matching surfaces of  
the flare and union tubes before connecting them, then  
tighten the nut with a torque wrench for a leak-free  
connection.  
In Case of Improper Installation  
The manufacturer shall in no way be responsible for improp-  
er installation or maintenance service, including failure to  
follow the instructions in this document.  
• Check carefully for leaks before starting the test run.  
When Servicing  
SPECIAL PRECAUTIONS  
Turn the power OFF at the main power box (mains) before  
opening the unit to check or repair electrical parts and  
wiring.  
WARNING  
When Wiring  
ELECTRICAL SHOCK CAN CAUSE SEVERE  
PERSONAL INJURY OR DEATH. ONLY A  
• Keep your fingers and clothing away from any moving  
parts.  
QUALIFIED, EXPERIENCED ELECTRICIAN  
SHOULD ATTEMPT TO WIRE THIS SYSTEM.  
• Do not supply power to the unit until all wiring and tubing  
are completed or reconnected and checked.  
• Highly dangerous electrical voltages are used in this  
system. Carefully refer to the wiring diagram and these  
instructions when wiring. Improper connections and  
inadequate grounding can cause accidental injury or  
death.  
• Clean up the site after you finish, remembering to check  
that no metal scraps or bits of wiring have been left inside  
the unit being serviced.  
Others  
CAUTION  
• Ground the unit following local electrical codes.  
• Connect all wiring tightly. Loose wiring may cause over-  
heating at connection points and a possible fire hazard.  
• Ventilate any enclosed areas when installing or testing  
the refrigeration system. Escaped refrigerant gas, on  
contact with fire or heat, can produce dangerously  
toxic gas.  
When Transporting  
Be careful when picking up and moving the indoor and out-  
door units. Get a partner to help, and bend your knees when  
lifting to reduce strain on your back. Sharp edges or thin alu-  
minum fins on the air conditioner can cut your fingers.  
• Confirm upon completing installation that no refrigerant  
gas is leaking. If escaped gas comes in contact with a  
stove, gas water heater, electric room heater or other heat  
source, it can produce dangerously toxic gas.  
2
1. General  
6. Sabre saw or key hole saw  
7. Hacksaw  
8. Core bits  
9. Hammer  
10. Drill  
This booklet briefly outlines where and how to install the  
air conditioning system. Please read over the entire set  
of instructions for the indoor and outdoor units and make  
sure all accessory parts listed are with the system before  
beginning.  
11. Tube cutter  
1-1. Tools Required for Installation (not supplied)  
1. Standard screwdriver  
12. Tube flaring tool  
13. Torque wrench  
14. Adjustable wrench  
15. Reamer (for deburring)  
2. Phillips head screwdriver  
3. Knife or wire stripper  
4. Tape measure  
5. Carpenter’s level  
1-2. Accessories Supplied with Unit  
Table 1  
Parts  
Figure  
Q’ty  
Parts  
Figure  
Q’ty  
Parts  
Figure  
Q’ty  
Truss-head  
Remote  
control unit  
Tapping screw  
Phillips  
Hex wrench*  
1
10  
1
5/32 ¥ 5/8" (4¥16 mm)  
Remote control  
unit holder  
1
8
Clamp  
1
Rawl plug  
*Packed in the outdoor unit.  
Drain hose  
adapter  
AAA alkaline  
battery  
2
2
1
4
Cushion  
rubber*  
Air clean filter  
1-3. Optional Copper Tubing Kit  
2. Foamed polyethylene insulation for the specified  
copper tubes as required to precise length of tubing.  
Wall thickness of the insulation should be not less  
than 5/16" (8 mm).  
Copper tubing for connecting the outdoor unit to the  
indoor unit is available in kits which contain the narrow  
and wide tubing, fittings and insulation. Consult your  
nearest sales outlet or A/C workshop.  
3. Use insulated copper wire for field wiring. Wire size  
varies with the total length of wiring. Refer to 3-6.  
Wiring Instructions for details.  
1-4. Type of Copper Tube and Insulation Material  
If you wish to purchase these materials separately from  
a local source, you will need:  
Check local electrical codes  
and regulations before  
obtaining wire. Also, check  
any specified instructions or  
limitations.  
CAUTION  
1. Deoxidized annealed copper tube for refrigerant tub-  
ing as detailed in Table 2.  
Cut each tube to the appropriate lengths 1' to 1'4"  
(30 cm to 40 cm) to dampen vibration between units.  
Table 2  
Narrow Tube  
Model  
Wide Tube  
Outer Dia. Thickness  
Outer Dia.  
Thickness  
KHS1872  
KHS2472  
1/4" (6.35 mm)  
1/4" (6.35 mm)  
0.0314" (0.8 mm) 1/2" (12.70 mm) 0.0314" (0.8 mm)  
0.0314" (0.8 mm) 5/8" (15.88 mm) 0.0393" (1.0 mm)  
3
1-5. Additional Materials Required for Installation  
Indoor unit  
1. Refrigeration (armored) tape  
2. Insulated staples or clamps for connecting wire  
(See local codes)  
3. Putty  
4. Refrigeration lubricant  
5. Clamps or saddles to secure refrigerant tubing  
Drain hose  
2. Installation Site Selection  
Outside drainage  
2-1. Indoor Unit  
Fig. 1  
To prevent abnormal heat genera-  
tion and the possibility of fire, do  
not place obstacles, enclosures  
and grilles in front of or surround-  
ing the air conditioner in a way  
that may block air flow.  
WARNING  
6" (15 cm)  
min.  
2" (5 cm)  
min.  
2" (5 cm)  
min.  
AVOID:  
G direct sunlight.  
Front View  
G nearby heat sources that may affect performance of the unit.  
G areas where leakage of flammable gas may be expected.  
G places where large amounts of oil mist exist.  
Fig. 2  
Tubing length (L)  
INDOOR  
UNIT  
DO:  
G select an appropriate position from which every corner of  
Elevation  
difference (H)  
OUTDOOR  
UNIT  
the room can be uniformly cooled. (High on a wall is best.)  
G select a location that will hold the weight of the unit.  
G select a location where tubing and drain hose have the  
Fig. 3a  
shortest run to the outside. (Fig. 1)  
G allow room for operation and maintenance as well as unre-  
CAUTION  
stricted air flow around the unit. (Fig. 2)  
Indoor unit  
Wall  
G install the unit within the maximum elevation difference (H)  
above or below the outdoor unit and within a total tubing length  
(L) from the outdoor unit as detailed in Table 3 and Fig. 3a.  
For stable operation of the  
air conditioner, do not  
install wall-mounted type  
indoor units less than 5'  
(1.5 m) from floor level.  
Minimum height  
from floor level  
5' (1.5 m)  
G Install the indoor unit more than 3.3' (1 m) away from any  
antenna or power lines or connecting wires used for television,  
radio, telephone, security system, or intercom. Electrical noise  
from any of these sources may affect operation.  
Floor level  
Fig. 3b  
Table 3  
Max. Allowable Tubing  
Length at Shipment  
(ft.)  
Limit of Tubing  
Length (L)  
(ft.)  
Limit of Elevation  
Difference (H)  
(ft.)  
Required Amount of  
Additional Refrigerant  
(oz./ft.)*  
Model  
KHS1872  
KHS2472  
25  
33  
98  
98  
49  
49  
0.27  
0.27  
* If total tubing length becomes 25 to 98 ft. (Max.) or 33 to 98 ft. (Max.), charge additional refrigerant (R410A) by 0.27 oz./ft.  
No additional charge of compressor oil is necessary. For more detailed charging information, refer to the Technical & Service Manual.  
4
2-2. Outdoor Unit  
AVOID:  
Exhaust fan  
NO  
Hot air  
G heat sources, exhaust fans, etc. (Fig. 4)  
G damp, humid or uneven locations.  
Heat source  
DO:  
Outdoor unit  
G choose a place as cool as possible.  
G choose a place that is well ventilated.  
G allow enough room around the unit for air intake/  
exhaust and possible maintenance. (Fig. 5a or 5b)  
G provide a solid base (level concrete pad, concrete block,  
4" × 1'4" (10 × 40 cm) or 6" × 1'4" (15 × 40 cm) beams  
or equal), a minimum of 4" (10 cm) or 6" (15 cm) above  
ground level to reduce humidity and protect the unit  
against possible water damage and decreased service  
life. (Figs. 5c and 5d or 5e)  
Fig. 4  
Obstacle above  
(CH1872)  
Min.  
7' (2 m)  
Min.  
7' (2 m)  
Air intake  
Min. 4" (10 cm) Valve  
side  
Min. 10"  
(25 cm)  
A solid base must not cover  
CAUTION  
Min.  
2" (5 cm)  
the hole of the bottom plate.  
Air discharge  
Min.  
1'4" (40 cm)  
G Install cushion rubber under unit’s feet to reduce  
vibration and noise. (Fig. 5f)  
G use lug bolts or equal to bolt down unit, reducing  
vibration and noise.  
Ground  
Min. 4" (10 cm)  
Air intake  
Fig. 5a  
G Install in a location where no antenna of a television  
or radio exists within 10' (3 m).  
Obstacle above  
(CH2472)  
Anchor bolts  
(4 pcs.)  
Min.  
7' (2 m)  
Min.  
7' (2 m)  
(CH1872)  
Air intake  
Min. 6" (15 cm) Valve  
side  
Min. 10"  
(25 cm)  
Min. 4" (10 cm)  
Air intake  
Min.  
4" (10 cm)  
Air discharge  
Min.  
1'8" (50 cm)  
Concrete  
or equal  
Ground  
Min. 6" (15 cm)  
Air intake  
Fig. 5b  
Drain holes  
Fig. 5d  
Anchor bolts  
(4 pcs.)  
(CH2472)  
Fig. 5c  
Min. 6" (15 cm)  
Air intake  
Concrete  
or equal  
Cushion rubber  
Fig. 5e  
Fig. 5f  
5
3. How to Install the Indoor Unit  
3-1. Remove the Rear Panel from the Unit  
(1) Remove and discard the set screw on the rear  
panel. (Fig. 6)  
(2) Press the 2 L marks on the frame cover and disen-  
gage the stationary tabs from the frame. (Fig. 7)  
Set screw only for transportation  
(3) Remove the rear panel.  
Fig. 6  
NOTE  
Tubing can be extended in 5 directions as shown in Fig.  
8. Select the direction you need providing the shortest  
run to the outside unit.  
Rear panel  
G When left tubing is to be done, switch the drain hose  
and drain cap. (For details, refer to “Switching drain  
hose and drain cap” on page 14.)  
3-2. Make a Hole  
(1) Place the rear panel from the indoor unit on the wall  
at the location selected. Make sure the panel is hori-  
zontal, using a carpenter’s level or tape measure to  
measure down from the ceiling. Wait until after cut-  
ting the hole before attaching the rear panel to the  
wall.  
marks  
Fig. 7  
Right-rear  
tubing  
Left  
(recommended)  
tubing  
(2) Determine which side of the unit you should make  
the hole for tubing and wiring. (Fig. 9)  
Left-rear  
tubing  
Right tubing  
NOTE  
In the case of left-rear tubing, use the measurement  
points 2-3/8" (60 mm) from the edge of the rear panel for  
precise placement of the hose outlet. (Fig. 9)  
Downward tubing  
Fig. 8  
(3) Before making the hole, check carefully that no  
studs or pipes are directly run behind the spot to be  
cut.  
2-3/8" (60 mm)  
Also avoid areas where elec-  
CAUTION  
trical wiring or conduits are  
located.  
Fig. 9  
The above precautions are also applicable if tubing  
goes through the wall in any other location.  
6
(4) Using a sabre saw, key hole saw or hole-cutting drill  
attachment, cut a hole in the wall. See Table 4 and  
Fig. 10.  
NOTE  
Hole should be made at a slight downward slant to the  
outdoor side.  
Table 4  
Indoor  
Outdoor  
side  
side  
Hole Dia.  
3-5/32" (80 mm)  
(5) Measure the thickness of the wall from the inside  
edge to the outside edge and cut PVC pipe at a  
slight angle 1/4" (6 mm) shorter than the thickness of  
the wall. (Fig. 11)  
Fig. 10  
PVC pipe (Locally purchased)  
(6) Place the plastic cover over the end of the pipe (for  
indoor side only) and insert the pipe in the wall. (Fig.  
12)  
3-3. Install the Rear Panel on the Wall  
Cut at slight angle  
Be sure to confirm that the wall is strong enough to sus-  
pend the unit.  
Fig. 11  
INSIDE  
OUTSIDE  
PVC pipe  
See either Item a) or b) below depending on the wall type.  
Wall  
a) If Wooden Wall  
Plastic cover  
(Locally purchased)  
Slight  
angle  
(1) Attach the rear panel to the wall with the 8 screws  
provided. (Fig. 13)  
If you are not able to line up the holes in the rear  
panel with the beam locations marked on the wall,  
use rawl plugs or toggle bolts to go through the  
holes on the panel or drill 3/16" (5 mm) dia. holes in  
the panel over the stud locations and then mount the  
rear panel.  
Fig. 12  
(2) Double check with a carpenter’s level or tape mea-  
sure that the panel is level. This is important to  
install the unit properly. (Fig. 14)  
Fig. 13  
(3) Make sure the panel is flush against the wall. Any  
space between the wall and unit will cause noise  
and vibration.  
b) If Block, Brick, Concrete or Similar Type Wall  
Make 3/16" (4.8 mm) dia. holes in the wall. Insert rawl  
plugs for appropriate mounting screws. (Fig. 15)  
Fig. 14  
3/16"  
(4.8 mm) dia. hole  
Rawl plug  
Fig. 15  
7
Grille  
Air intake grille  
3-4. Remove the Grille to Install the Indoor Unit  
Basically, these models can be installed and wired with-  
out removing the grille. If access to any internal part is  
needed, follow the steps as given below.  
How to remove the grille  
(1) Grasp both ends of the air intake grille, and remove  
it by opening towards the front and pulling towards  
you. (Fig. 16a)  
Fig. 16a  
(2) Remove the 3 screws. (Fig. 16b)  
(3) Remove the screw on the right side cover plate and  
open the cover. (Fig. 17a)  
(4) Take out the thermistor from the grille. (Fig. 17b)  
Fig. 16b  
(5) Press the 3 tabs at the top of the grille and the 3  
tabs on the front face to separate the grille from the  
frame. (Fig. 18a)  
Cover  
Thermistor  
Thermistor  
(6) Pull the grill toward you to remove it.  
How to replace the grille  
(1) When installing the grille, place the bottom of the  
grille into the frame first. (Fig. 18b)  
Fig. 17b  
Fig. 17a  
Tab  
Then insert the tabs on the top of the grille and on  
the front face into the frame.  
(2) Make sure that the grille and frame are firmly fitted  
together by engaging the tabs.  
(3) Attach the thermistor on the grille. (Fig. 17a)  
(4) Close the cover and replace the screw. (Fig. 17a)  
Tab  
(5) Affix the grille with the 3 previously removed screws.  
(Fig. 16b)  
Fig. 18a  
(6) Install the air intake grille.  
(a) Allow the edge of the air intake grille to slide into the  
top of the indoor unit, and then insert it all the way  
inside. (Fig. 19a)  
(b) Press the bottom right and left corners and center of  
the air intake grille to attach it to the indoor unit.  
(Fig. 19b)  
NOTE  
Fig. 18b  
Groove  
Attach so that the round pins at the top right and left cor-  
ners of the air intake grille are inserted into the grooves  
at the top right and left of the indoor unit.  
Pin  
Fig. 19b  
Fig. 19a  
8
3-5. Shape the Indoor Side Tubing  
(1) Arrangement of tubing by direction  
a) Right or left tubing  
Frame  
Cut out the corner of the right/left frame with a  
hacksaw or the like. (Figs. 20 and 21)  
Left tubing  
outlet  
b) Right-rear or left-rear tubing  
In this case, the corner of the frame need not be  
cut.  
(2) To mount the indoor unit on the rear panel:  
Fig. 20  
Hang the 2 mounting slots of the unit on the  
upper tabs of the rear panel. (Fig. 22)  
Frame  
3-6. Wiring Instructions  
General precautions on wiring  
Right tubing  
outlet  
(1) Before wiring, confirm the rated voltage of the unit as  
shown on its nameplate, then carry out the wiring  
closely following the wiring diagram.  
(2) Provide a power outlet to be used exclusively for  
each unit, with a power supply disconnect and cir-  
cuit breaker for overcurrent protection provided in  
the exclusive line.  
Fig. 21  
(3) To prevent possible hazards due to insulation failure,  
the unit must be grounded.  
(4) Each wiring connection must be done tightly and in  
accordance with the wiring system diagram. Wrong  
wiring may cause the unit to misoperate or become  
damaged.  
Fig. 22  
(5) Do not allow wiring to touch the refrigerant tubing,  
compressor, or any moving parts of the fan.  
(6) Unauthorized changes in the internal wiring can be  
very dangerous. The manufacturer will accept no  
responsibility for any damage or misoperation that  
occurs as a result of such unauthorized changes.  
9
3-7. Recommended Wire Length and Diameter  
Regulations on wiring diameter differ from locality to locality. For field wiring  
requirements, please refer to your local electrical codes. Carefully observe these  
regulations when carrying out the installation.  
Table 5 lists recommended wire lengths and diameters for power supply systems.  
NOTE  
Refer to the wiring system diagram (Fig. 23) for the meaning of (A), (B), and (C) in  
Table 5.  
Refer to your local codes or in the absence of local codes see the National Elec-  
tric Code: ANSI/NFPA70.  
Table 5  
(A)+(B)  
(A) Power Supply Wiring Length (ft)  
(B) Power Line Length (ft)  
(C) Control  
Line Length (ft)  
AWG  
Fuse or Circuit  
Breaker Capacity  
Model  
(#14)  
131 (Max.)  
(#12)  
(#14)  
CH1872, CH2472  
230 (Max.)  
98 (Max.)  
20A  
# ... AWG (American Wire Gauge)  
WARNING  
WIRING SYSTEM DIAGRAM  
G Be sure to comply with local codes on running the wire  
from the indoor unit to the outdoor unit (size of wire and  
wiring method, etc.).  
G Each wire must be firmly connected.  
G No wire should be allowed to touch refrigerant tubing, the  
compressor, or any moving part.  
INDOOR  
OUTDOOR  
UNIT  
Disconnect  
switch  
*
UNIT  
Field supply  
Terminal  
Terminal  
(B)  
230/208V  
1
2
3
1
2
3
4
5
6
230/208V  
230/208V  
(C)  
(A)  
L1  
L2  
Grounding line  
WARNING  
(B)  
Grounding  
line  
G To avoid the risk of electric shock, each air conditioner  
unit must be grounded.  
G For the installation of a grounding device, please  
observe local electrical codes.  
G Grounding is necessary, especially for units using  
inverter circuits, in order to release charged electricity  
and electrical noise caused by high tension.  
Otherwise, electrical shock may occur.  
G Place a dedicated ground more than 7' (2 m) away from  
other grounds and do not have it shared with other elec-  
tric appliances.  
Fig. 23  
NOTE  
*
Disconnect switch may be required by  
national or local codes.  
CAUTION  
Always comply with national and local code  
requirements.  
CAUTION  
G Be sure to connect the power supply line to the outdoor unit as shown in the wiring diagram.  
The indoor unit draws its power from the outdoor unit.  
G Do not run wiring for antenna, signal, or power lines of television, radio, stereo, telephone,  
security system, or intercom any closer than 3'4" (1 m) from the power cable and wires  
between the indoor and outdoor units. Electrical noise may affect the operation.  
10  
3-8. Wiring Instructions for Inter-unit Connections  
Rear  
panel  
Wall  
(1) Insert the inter-unit wiring (according to local codes)  
into the through-the-wall PVC pipe. Run the wiring  
toward the indoor side allowing approx. 10" (25 cm)  
to extend from the wall face. (Fig. 24)  
Plastic  
cover  
(2) Grasp both ends of the air intake grille, and remove  
it by opening towards the front and pulling towards  
you.  
Wiring  
10"  
(25 cm)  
(3) Remove the screw on the right side cover plate and  
open the cover. (Fig. 25)  
Fig. 24  
Fig. 25  
Fig. 26a  
(4) Route the inter-unit wiring from the back of the  
indoor unit and pull it toward the front for connec-  
tion. (Fig. 26a, 26b)  
Cover  
(5) Connect the inter-unit wiring to the corresponding  
terminals on the terminal plate (Fig. 26a, 26b) while  
referring to the wiring diagram.  
(6) Be sure to secure the wiring with the provided  
clamp.  
NOTE  
When closing the air intake grille, press the bottom right  
and left corners and center. (Fig. 27)  
Please refer to “How to replace the grille” on page 8 for  
installing the air intake grille.  
Terminal  
plate  
Fig. 27  
Inter-unit  
wiring  
Earth  
plate  
Lock nut  
Top of conduit  
connector  
Fig. 26b  
11  
Loose wiring may cause the  
terminal to overheat or result  
in unit malfunction. A fire  
hazard may also exist. There-  
fore, be sure all wiring is  
tightly connected.  
WARNING  
When connecting each power wire to the corresponding  
terminal, follow the instructions “How to connect wiring  
to the terminal” and fasten the wire securely tight with  
the fixing screw of the terminal plate.  
9/32"  
(7 mm)  
(ACTUAL  
STRIP  
SIZE  
SIZE)  
How to connect wiring to the terminal  
a) For Indoor Unit  
Fig. 28  
(1) Cut the wire end with a cutting pliers, then strip the  
insulation to expose the wire about 9/32" (7 mm).  
See the label (Fig. 28) near the terminal plate.  
Solid wire  
Loop  
(2) Using a screwdriver, loosen the terminal screw on  
the terminal plate.  
(3) Insert the wire and tighten the terminal screw com-  
pletely using a screwdriver.  
Insulation  
b) For Outdoor Unit  
Fig. 29  
I For solid core wiring (or F-cable)  
Stranded wire  
(1) Cut the wire end with a cutting pliers, then strip the  
insulation to expose the solid wire about 15/16" (25  
mm). (Fig. 29)  
Ring  
connector  
(2) Using a screwdriver, remove the terminal screw(s)  
on the terminal plate.  
(3) Using the pliers, bend the solid wire to form a loop  
suitable for the terminal screw.  
Fig. 30  
(4) Shape the loop wire properly, place it on the termi-  
nal plate and fix it securely with the removed termi-  
nal screw using a screwdriver.  
Twist wire ends  
I For stranded wiring  
(1) Cut the wire end with a cutting pliers, then strip the  
insulation to expose the stranded wiring about 3/8"  
(10 mm) and tightly twist the wire ends. (Figs. 30  
and 31)  
Fig. 31  
(2) Using a screwdriver, remove the terminal screw(s)  
on the terminal plate.  
Special  
washer  
Screw  
(3) Using a ring connector fastener or pliers, securely  
clamp each stripped wire end with a ring connector.  
(Fig. 30)  
Screw and  
special washer  
Ring connector  
Terminal plate  
Ring  
connector  
Wire  
(4) Place the ring connector wire, and replace and  
tighten the removed terminal screw using a screw-  
driver. (Fig. 32)  
Wire  
Fig. 32  
12  
3-9. Mounting  
(1) To install the indoor unit, mount the indoor unit onto  
the 2 tabs on the upper part of the rear plate.  
(2) Hold down the air discharge outlet and press the  
lower part of the indoor unit until it clicks to securely  
fasten to the 2 tabs on the lower part of the rear  
plate. (Fig. 33)  
Push  
NOTE  
For tubing, choose either the right or left tubing direction  
and follow the steps below. This work can be made easi-  
er by placing padding material (such as styrofoam) at the  
rear right side of the indoor unit. (Fig. 34)  
Fig. 33  
I Right-side tubing  
(1) Shape the refrigerant tubing so that it can easily go  
into the wall hole. (Fig. 35)  
(2) Push the wiring, refrigerant tubing, and drain hose  
through the hole in the wall. Adjust the indoor unit so  
it is securely seated on the rear panel. (Fig. 36)  
Padding material  
(3) Carefully bend the tubing (if necessary) to run along  
the wall in the direction of the outdoor unit and then  
tape as far as the fittings. (See Caution on page  
18.) The drain hose should come straight down the  
wall to a point where water runoff won’t stain the  
wall.  
Fig. 34  
Rear panel  
Cover  
Refrigerant  
tubing  
(4) Connect the refrigerant tubing to the outdoor unit.  
(After performing a leak test on the connecting part,  
insulate it with the tubing insulation. (Fig. 37a)) Also,  
refer to Section 5-4. Connecting Tubing between  
Indoor and Outdoor Units.  
Inter-unit  
wiring  
Drain hose  
(5) Assemble the refrigerant tubing, drain hose, and  
conduit (including inter-unit wiring) as shown in  
Fig. 37b.  
Fig. 35  
Refrigerant tubing  
Insulation  
Fig. 37a  
Conduit  
Drain hose  
Fig. 36  
Inter-unit wiring  
Fig. 37b  
13  
I Left-side tubing  
Rear panel  
(1) Lead the tubing and drain hose through the wall,  
allowing sufficient length for connection. Then bend  
the tubing using a tube bender to make the attach-  
ment. (Fig. 38)  
Hole in wall  
Wide tube  
Narrow tube  
Bent part  
(2) Switch the drain hose and drain cap.  
Fig. 38  
Switching drain hose and drain cap  
(a) Locate the drain hose and the drain cap. (Fig.  
39)  
(b) Remove the screws fastening the drain hose on  
the right side, and pull out the drain hose to  
remove it. (Fig. 39)  
Drain cap  
(c) Apply moderate force to pull off the drain cap  
on the left side. (If you cannot pull it off by  
hand, use a long-nose pliers.)  
Drain hose  
Fig. 39  
(d) Reattach the drain hose to the left side and the  
drain cap to the right side. (Fig. 40a)  
Drain hose  
Drain hose  
Slide the drain hose fully onto the drain pan outlet  
until the drain hose edge is pushed into the insula-  
tion. Check that the screw holes in the drain bracket  
and the drain pan outlet are aligned and securely in  
contact, then fasten them with the screw. (After  
attaching the drain hose, check that it is attached  
securely.) (Fig. 40c)  
Clamp  
Drain cap  
Drain cap  
Use a Phillips screwdriver to push the drain cap in  
firmly. (If it is difficult to push in, wet the cap with  
water first.)  
Fig. 40a  
Screw hole  
(3) Install the indoor unit on the rear panel.  
(4) Connect the tubing and wiring led inside from out-  
doors.  
Drain pan outlet  
(5) After completing a leak test, bundle the tubing  
together with armoring tape and store it inside the  
tubing storage area at the back of the indoor unit  
and hold it with clamps. (Figs. 40a and 41)  
Insulation  
Drain bracket  
Drain bracket  
Screw  
Drain hose  
Drain hose  
Fig. 40c  
Fig. 40b  
Refrigerant tubing  
Inter-unit wiring  
Conduit  
Fig. 41  
14  
To unmount indoor unit  
Press the 2 L marks on the lower part of the indoor unit  
and unlatch the tabs. Then lift the indoor unit and  
unmount. (Fig. 42)  
3-10. Drain Hose  
a) The drain hose should be slanted downward to the  
outdoors. (Fig. 43)  
b) Never form a trap in the course of the hose.  
c) If the drain hose will run in the room, insulate the  
hose with insulation* so that chilled condensation  
will not damage furniture or floors. (Fig. 44)  
Push  
* Foamed polyethylene or its equivalent is recom-  
Fig. 42  
mended.  
Do not supply power to the  
unit or operate it until all  
tubing and wiring to the out-  
side unit are completed.  
WARNING  
Slant  
Indoor  
unit  
Drain  
hose  
Risk of Electric Shock  
Fig. 43  
Condensation  
Insulation material  
(Locally purchased)  
must be used.  
Fig. 44  
15  
4. How to Install the Outdoor Unit  
First refer to Section 2. Installation Site Selection.  
4-1. Wiring Instructions for the Outdoor Unit  
Lock nut  
Regulations on wire size differ from locality to locality. For  
field wiring requirements, please refer to your local elec-  
trical codes. Make sure that the installation fully complies  
with all local and national regulations.  
Cabinet  
(1) Remove access panel “C”. (Fig. 46)  
Terminal  
(2) Connect the inter-unit and power supply line accord-  
ing to the drawing on the panel side.  
block  
(3) Be sure to size each wire allowing approx. 4"  
(10 cm) longer than the required length for wiring.  
Store excess wiring inside the cabinet.  
Conduit  
plate  
(4) When connections are completed, check that all  
connections are correct as shown in the wiring sys-  
tem diagram on panel side.  
Access panel C  
(5) Be sure to ground the unit according to your local  
codes.  
Inter unit  
(Conduit)  
Power supply  
(Conduit)  
Plug  
Fig. 46  
16  
Deburring  
5. Refrigerant Tubing  
After  
Before  
5-1. Use of the Flaring Method  
Many of the conventional split system air conditioners  
employ the flaring method to connect refrigerant tubes  
which run between indoor and outdoor units. In this  
method, the copper tubes are flared at each end and  
connected with flare nuts.  
5-2. Flaring Procedure with a Flare Tool  
(1) Cut the copper tube to the required length with a  
tube cutter. It is recommended to cut approx. 12" to  
20" (30 to 50 cm) longer than the tubing length you  
estimate.  
Fig. 47  
Copper  
tubing  
(2) Remove burrs at the end of the copper tube with a  
tube reamer or file. This process is important and  
should be done carefully to make a good flare.  
(Fig. 47)  
Reamer  
NOTE  
When reaming, hold the tube end downward and be  
sure that no copper scraps fall into the tube. (Fig. 48)  
Fig. 48  
If the previous flare tool  
(clutch-type) is used:  
If the special R410A  
flare tool is used:  
(3) Remove the flare nut from the unit and be sure to  
mount it on the copper tube.  
0.0472" (1.2 mm)  
(4) Make a flare at the end of copper tube with a flare  
0 to 0.0196"  
(0 to 0.5 mm)  
tool.* (Figs. 49a and 49b)  
Adjust so that the amount of tube  
protrusion is as shown in the figure.  
(*Use “RIGID” or equivalent.)  
Fig. 49a  
NOTE  
A good flare should have the following characteristics:  
G inside surface is glossy and smooth.  
G edge is smooth.  
Flare nut  
Copper  
tubing  
G tapered sides are of uniform length.  
5-3. Caution before Connecting Tubes Tightly  
Flare tool  
a) Be sure to apply a sealing cap or water-proof tape  
to prevent dust or water from getting into the tubes  
before they are used.  
Fig. 49b  
b) Be sure to apply refrigerant lubricant to the match-  
ing surfaces of the flare and union before connect-  
ing them together. This is effective for reducing gas  
leaks. (Fig. 50)  
Apply refrigerant  
lubricant here and here  
Fig. 50  
c) For proper connection, align the union tube and  
flare tube straight with each other, then screw in the  
flare nut lightly at first to obtain a smooth match.  
(Fig. 51)  
Flare nut  
Union  
Fig. 51  
17  
5-4. Connecting Tubing between Indoor and  
Outdoor Units  
Torque wrench  
a) Tightly connect the indoor side refrigerant tubing exten-  
ded from the wall with the outdoor side tubing. (Fig. 52)  
Spanner  
Indoor unit  
b) To fasten the flare nuts, apply specified torque as:  
Table 6  
Outdoor unit  
Tube Dia.  
Tightening Torque  
Fig. 52  
1/4" (6.35 mm)  
3/8" (9.52 mm)  
1/2" (12.70 mm)  
5/8" (15.88 mm)  
Approx. 120 – 160 lbs·in (140 – 180 kgf·cm)  
Approx. 300 – 360 lbs·in (340 – 420 kgf·cm)  
Approx. 430 – 540 lbs·in (490 – 610 kgf·cm)  
Approx. 590 – 710 lbs·in (680 – 820 kgf·cm)  
Insulation  
5-5. Insulation of Refrigerant Tubing  
IMPORTANT  
Fig. 53  
To prevent heat loss and wet floors due to dripping of con-  
densation, both tubes must be well insulated with a  
proper insulation material. (Fig. 53)  
The thickness of the insulation should be a minimum 5/16"  
(8 mm). (Fig. 54)  
Insulation  
Thickness:  
min. 5/16"  
(8 mm)  
Min.  
5/16"  
(8 mm)  
5-6. Taping the Tubes  
Fig. 54  
After a tube has been insulat-  
ed, never try to bend it into a  
narrow curve, as this may  
cause the tube to break or  
crack.  
CAUTION  
(1) At this time, the 2 refrigerant tubes (and electrical wire  
if local codes permit) should be taped together with  
armoring tape. The drain hose may also be included  
and taped together as 1 bundle with the tubing.  
Clamp  
Insulated tubes  
(2) Wrap the armoring tape from the bottom of the outdoor  
unit to the top of the tubing where it enters the wall. As  
you wrap the tubing, overlap half of each previous tape  
turn. (Fig. 55)  
Fig. 55  
(3) Clamp the tubing bundle to wall, using 1 clamp approx.  
every 47" (120 cm).  
Apply putty here  
NOTE  
Do not wind the armoring tape too tightly, since this will  
decrease the heat insulation effect. Also, be sure the con-  
densation drain hose splits away from the bundle and drips  
clear of the unit and the tubing.  
Tubing  
5-7. Finishing the Installation  
Fig. 56  
After finishing insulating and taping over the tubing, use  
sealing putty to seal off the hole in the wall to prevent rain  
and draft from entering. (Fig. 56)  
18  
6. Air Purging  
Indoor unit  
Air and moisture remaining in the refrigerant system  
have undesirable effects as indicated below. Therefore,  
they must be purged completely.  
G pressure in the system rises  
G operating current rises  
G cooling (or heating) efficiency drops  
G moisture in the air may freeze and block capillary tubing  
Outdoor unit  
G water may lead to corrosion of parts in the refrigerant  
system  
I Air Purging with a Vacuum Pump (for Test Run)  
(1) Check that each tube (both narrow and wide tubes)  
between the indoor and outdoor units have been  
properly connected and all wiring for the test run  
has been completed. Note that both narrow and  
wide tube service valves on the outdoor unit are  
kept closed at this stage.  
(2) Using an adjustable wrench or box wrench, remove  
the valve caps from the service valve on both nar-  
row and wide tubes.  
Manifold valve  
(Exclusively for R410A)  
(3) Connect a vacuum pump and a manifold valve (with  
pressure gauges) to the service port on the wide  
tube service valve. (Fig. 57)  
Lo  
Hi  
Pressure  
gauge  
The service port on the wide tube  
service valve uses a Schrader core  
valve to access the refrigerant sys-  
tem. The valve core is similar to  
those used in automobile tires.  
Therefore, be sure to use a vacuum  
hose connector which has a push-  
pin inside.  
CAUTION  
Charging hose  
(Exclusively for R410A)  
Vacuum pump adapter  
(Exclusively for R410A)  
(with reverse flow prevention)  
Vacuum pump  
Be sure to use a manifold valve  
for air purging. If it is not avail-  
able, use a stop valve (field sup-  
ply) for this purpose. The “Hi”  
knob of the manifold valve must  
always be kept closed.  
CAUTION  
Fig. 57  
NOTE  
To prevent other refrigerants from being mistakenly  
charged to units which use R410A, the size of the  
charge port on the service valve is different from the  
one for other refrigerant types. For servicing such as  
recharging, the specified charging hose, manifold and  
vacuum pump adapter (with reverse flow prevention)  
for R410A must be used.  
(4) With the “Lo” knob of the manifold valve open, run  
the vacuum pump. The operation time for the vacu-  
um pump varies with tubing length and the capacity  
of the pump. The following table shows the amount  
of time for evacuation:  
Table 7  
Required time for evacuation when  
100 liter/h vacuum pump is used  
NOTE  
If tubing length is  
less than 33 ft. (10 m)  
If tubing length is  
more than 33 ft. (10 m)  
The required time in Table 7 is calculated based on the  
assumption that the ideal (or target) vacuum condition  
is around 10 mmHg abs.  
10 min. or more  
15 min. or more  
19  
(5) With the vacuum pump still running, close the “Lo”  
knob of the manifold valve. Then stop the vacuum  
pump.  
90° (1/4 turn)  
Narrow tube  
(6) With the accessory hex wrench, turn the valve stem  
on the narrow tube service valve counter-clockwise  
by 90 degrees (1/4 turn) for 10 seconds, and then  
turn the stem clockwise to close it again. (Fig. 58)  
Hex wrench  
Wide tube  
Be sure to completely insert  
CAUTION  
the hex wrench before  
attempting to turn the valve.  
Valve cap  
Vacuum hose to manifold valve  
(7) Leak test all joints at the tubing (both indoor and out-  
doors) with soapy water. Bubbles indicate a leak. Tight-  
en the joint more when leaks, then check if there is no  
leak. Be sure to wipe off the soap with a clean cloth.  
Fig. 58  
(8) With the hex wrench, turn the wide tube service  
valve stem counter-clockwise to fully open the valve.  
(9) Turn the narrow tube service valve stem counter-  
clockwise to fully open the valve.  
(10) Loosen the vacuum hose connected to the wide  
tube service port slightly to release the pressure.  
Then, remove the hose.  
This may cause the refriger-  
ant gas to leak. In order to  
avoid this, take off the hose  
quickly.  
CAUTION  
(11) Fasten the valve cap on the wide tube service port  
securely with an adjustable wrench or box wrench.  
Next, mount the valve cap on the service valve and  
tighten it to 170 lbs·in (200 kgf·cm) with a torque  
wrench. This process is very important to prevent  
gas from leaking from the system.  
(12) Test run the air conditioner. (See next page.)  
(13) While the air conditioner is running, apply liquid  
soap to check for any gas leaks around the service  
valves or caps.  
(14) If there is no leakage, stop the air conditioner.  
(15) Wipe off the soap on the tubing.  
This completes air purging with a vacuum pump and the  
air conditioner is ready for actual operation.  
20  
How to Test Run the Air Conditioner  
After turning on power to the air conditioner, use the remote  
controller and follow the steps below to conduct the test run.  
(1) Set the remote controller in Test Run mode.  
(Fig. 59a)  
a) Press and hold the ION button.  
b) Then press and hold the 1HR TIMER button.  
c) At the same time, press the ACL (reset) button once.  
Use a pointed object such as the tip of a pen to press  
the ACL button.  
ON/OFF  
operation  
button  
ION  
button  
• After a few seconds, “ ” appears and “oP-1” blinks in  
the remote controller display area.  
(Fig. 59b)  
1HR.  
TIMER  
button  
d) Release the 1HR TIMER button.  
e) Release the ION button.  
(2) Start Cooling mode test run by pressing the ON/OFF  
operation button of the remote controller. (Fig. 59a)  
• This starts the fan producing uncooled forced air with  
the 4 indicator lamps (OPERATION lamp, TIMER  
lamp, QUIET lamp, and ION lamp) on the main unit  
blinking. (Fig. 59c)  
• After 3 minutes, the system shifts into cooling opera-  
tion, and cool air will start to be felt. Cool mode test  
run is unaffected by the room temperature.  
ACL  
(Reset)  
button  
A
(3) Press the ON/OFF operation button of the remote con-  
troller again to stop the test run. (Fig. 59a)  
Fig. 59a  
(4) Finally press the ACL (reset) button of the remote con-  
troller to release it from Test Run mode to return to nor-  
mal mode. (Fig. 59a)  
• “ ” and “oP-1” will disappear from the remote con-  
troller display area.  
NOTE  
Troubleshooting:  
In the event that the green “Operation Light” is blinking upon  
powering up the system, an error condition exists. In this  
case, refer to the self-diagnostics procedure on the  
inside of the front cover.  
Fig. 59b  
IMPORTANT  
OPERATION lamp  
TIMER lamp  
QUIET lamp  
ION lamp  
After the test run is completed, be sure to press the  
ACL (reset) button to return to normal mode. The  
air conditioner will not operate correctly if this is not  
done.  
Fig. 59c  
21  
I Basic Functions of the Service Valves  
The basic functions of the service valves are given in Table 8 below.  
Table 8  
Narrow Tube Service  
Wide Tube Service  
Valve (3-Way)  
Action  
Valve (2-Way)  
O-ring  
Valve cap  
CLOSED  
Stem  
Shipping  
Fully OPEN  
Fully OPEN  
CLOSED  
Operating and  
test running  
the air conditioner  
Measuring pressure  
*
and gas charging  
* The service port on the wide tube ser-  
vice valve uses a Schrader core valve  
to access the refrigerant system.  
Therefore, be sure to use a hose con-  
nector which has a push-pin inside.  
(Fig. 60a)  
Air purging with  
*
a vacuum pump  
Service valve  
Hose with push-pin  
CAUTION  
Close  
When opening or clos-  
ing the service valve  
PUSH  
Open  
stem, use the accessory  
hex wrench. Be sure to  
fully seat the wrench  
Hex  
wrench  
NOTE  
External diameter of service port  
R410A: 5/16"  
Fig. 60b  
before turning the valve.  
Fig. 60a  
I Pump Down  
(2) Using a hex wrench, turn the narrow tube service  
valve clockwise all the way to close the service  
valve. (Be sure to confirm that the wide tube service  
valve is fully open.)  
Pump down means collecting all refrigerant gas in the  
system back into the outdoor unit without losing any of  
the gas. Pump down is used when the unit is to be  
moved or before servicing the refrigerant circuit.  
(3) Press the operation button and start cooling oper-  
ation.  
Pump Down Procedure  
Be sure to carry out pump down with the unit in  
cooling mode.  
(4) When the low pressure gauge reading falls to 14.2 to  
7.1 psi (1 to 0.5 kg/cm2), fully close the wide tube  
valve stem. Then quickly stop the unit.  
(1) Connect the Lo side charging hose of the manifold  
valve to the service port on the wide tube service  
valve.  
(5) Disconnect all gauges and hoses, and replace the  
valve caps as they were before.  
22  
7. Remote Control Unit Installation Position  
The remote control unit can be operated from either a  
non-fixed position or a wall-mounted position.  
To ensure that the air conditioner operates correctly, do  
not install the remote control unit in the following places:  
G In direct sunlight  
G Behind a curtain or other place where it is covered  
G More than 26' (8 m) away from the air conditioner  
G In the path of the air conditioner’s airstream  
G Where it may become extremely hot or cold  
G Where it may be subject to electrical or magnetic  
interference  
G Where there is an obstacle between the remote con-  
trol unit and the air conditioner (since a check signal  
is sent from the remote control unit every 5 minutes)  
7-1. Mounting on a Wall  
Before mounting the remote control unit, press the  
ON/OFF operation button at the mounting location to  
make sure that the air conditioner operates from that  
location. The indoor unit should make a beeping sound  
to indicate that it has received the signal.  
Rear side  
Remote control unit mount  
Press  
Mounting screws  
5/32 × 5/8" (4 × 16 mm)  
(Included)  
Hole  
Set in  
place  
To prevent loss of the remote control  
unit, you can connect the remote  
control unit to the mount by passing  
a string through the remote control  
unit and attachment hole.  
To take out the remote control unit, pull it forward.  
Fig. 61  
23  
8. Address Switch  
Tab  
8-1. Address Setting of the Remote Control Unit  
The address can be set in order to prevent interference  
between remote controllers when two Sanyo indoor units  
are installed near each other. The address is normally  
set to “A.” To set a different address, it is necessary to  
change the address on the second remote controller.  
Fig. 62  
NOTE  
Once changed, you cannot restore the original address  
setting of the air conditioner.  
(1) Switch on the power source.  
(2) Break the address-setting tab marked “A” on the  
second remote controller to change the address  
(Fig. 62). When the tab is removed, the address is  
automatically set to B (Fig. 63).  
ACL button  
(3) Press and hold the remote controller ION button and  
1 HR TIMER button. At the same time, press the  
ACL(reset) button. Use a thin object such as the tip  
of a pen to press the ACL button. When this has  
been done, “oP-1” (test run) appears, blinking, in the  
remote controller clock display area.  
Fig. 63  
(4) Each time the 1 HR TIMER button is pressed, the  
display changes as shown below. Press this button  
2 times to change the display to “oP-7” (address  
setting). (Fig. 64)  
Test run mode  
Selfdiagnostic mode  
Address setting mode  
ON/OFF  
operation  
button  
ION  
button  
(5) “oP-7” has now been selected for address setting.  
1HR.  
(6) Press the ON/OFF operation button on the remote  
controller. (Fig. 64) Check that the “beep”signal-  
received sound is heard from the second indoor unit  
(approximately 5 times). The sound you hear is the  
signal that the remote controller address has been  
changed.  
TIMER  
button  
(7) Finally press the remote controller ACL (reset) but-  
ton to cancel the blinking “oP-7” display.  
(Fig. 64)  
Changing of the second remote controller address is  
now completed.  
ACL  
(Reset)  
button  
A
Fig. 64  
24  
SANYO Commercial Solutions  
A Division of SANYO North America Corporation  
1300 Michael Drive, Suite A  
Wood Dale, IL 60191, U.S.A.  
Sanyo Canada Inc.  
1-300 Applewood Crescent, Concord, Ontario L4K 5C7, CANADA  
Jan. / 2009 (T)  

Mitsubishi Electronics Lossnay Lgh 15rx4 E User Manual
Netgear Printer Ps101 User Manual
Riccar Summer Breeze Rsbh O User Manual
Ricoh Aficio Isc 615g User Manual
Samsung Mh026fpea User Manual
Sanyo W 3way Eco I 85464369098000 User Manual
Schumacher Nin 12v Obd User Manual
Schumacher Sf 125a User Manual
Sony Bc Vm50 User Manual
Sterling Power Products 1250ced User Manual