Sanyo 85464359982001 User Manual

07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page a  
INSTALLATION INSTRUCTIONS  
– W-2WAY System Air Conditioner –  
X
A
U
D
T
for Refrigerant R410A  
I R410A Models  
Indoor Units  
Class  
7
9
12  
18  
24  
36  
48  
X
A
U
D
T
4-Way Air Discharge Semi-Concealed Type  
1-Way Air Discharge Semi-Concealed Type  
Concealed Duct Type  
XHX1252 XHX1852 XHX2452 XHX3652  
AHX0752  
UHX0752  
AHX0952 AHX1252  
UHX1252 UHX1852 UHX2452 UHX3652  
Concealed Duct  
High-Static Pressure Type  
DHX3652 DHX4852  
Ceiling-Mounted Type  
Wall-Mounted Type  
THX1252 THX1852  
THX2452  
K
KHX0752  
KHX0952 KHX1252 KHX1852 KHX2452  
K
Outdoor Units  
Class  
90  
140  
C
ECO-i W-2WAY  
CHDX09053 CHDX14053  
* Refrigerant R410A is used in the outdoor units.  
Optional Controllers  
Timer Wired Remote Controller  
Wireless Remote Controller (For U, D Type)  
Wireless Remote Controller (For X Type)  
Wireless Remote Controller (For A, T Type)  
RC Wireless Remote Controller (For K Type)  
Simplified Remote Controller  
System Controller  
RCS-TM80BG  
RCS-BH80AAB.WL  
RCS-SH80AAB.WL  
RCS-TRP80AAB.WL  
RCS-SH1AAB  
RCS-KR1AGB  
SHA-KC64UG  
Intelligent Controller  
SHA-KT256BA  
SHA-KA128AAB  
ART-K45AGB  
Communication Adaptor  
Remote Sensor  
LonWorks Interface  
SHA-LN16UAB  
85464359982001 ©SANYO 2006  
SANYO Electric Co., Ltd.  
Gunma, Japan  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 3  
2. The standards for minimum room volume are as fol-  
lows.  
Check of Density Limit  
The room in which the air conditioner is to be  
installed requires a design that in the event of refrig-  
erant gas leaking out, its density will not exceed a set  
limit.  
(1) No partition (shaded portion)  
The refrigerant (R410A), which is used in the air condition-  
er, is safe, without the toxicity or combustibility of ammonia,  
and is not restricted by laws imposed to protect the ozone  
layer. However, since it contains more than air, it poses the  
risk of suffocation if its density should rise excessively. Suf-  
focation from leakage of refrigerant is almost non-existent.  
With the recent increase in the number of high density  
buildings, however, the installation of multi air conditioner  
systems is on the increase because of the need for effec-  
tive use of floor space, individual control, energy conserva-  
tion by curtailing heat and carrying power, etc.  
(2) When there is an effective opening with the adjacent  
room for ventilation of leaking refrigerant gas (opening  
without a door, or an opening 0.15% or larger than the  
respective floor spaces at the top or bottom of the  
door).  
Outdoor unit  
Refrigerant tubing  
Most importantly, the multi air conditioner system is able  
to replenish a large amount of refrigerant compared to  
conventional individual air conditioners. If a single unit of  
the multi air conditioner system is to be installed in a  
small room, select a suitable model and installation pro-  
cedure so that if the refrigerant accidentally leaks out, its  
density does not reach the limit (and in the event of an  
emergency, measures can be made before injury can  
occur).  
In a room where the density may exceed the limit, create  
an opening with adjacent rooms, or install mechanical  
ventilation combined with a gas leak detection device.  
The density is as given below.  
Indoor unit  
(3) If an indoor unit is installed in each partitioned room  
and the refrigerant tubing is interconnected, the small-  
est room of course becomes the object. But when  
mechanical ventilation is installed interlocked with a  
gas leakage detector in the smallest room where the  
density limit is exceeded, the volume of the next small-  
est room becomes the object.  
Refrigerant tubing  
Total amount of refrigerant (lbs)  
Min. volume of the indoor unit installed room (ft.3)  
Outdoor unit  
3
<
Density limit (oz/ft. )  
Very  
small  
The density limit of refrigerant which is used in multi air condi-  
tioners is 0.3 oz/ft.3 (ISO 5149).  
Indoor unit  
room  
Small  
room  
Medium  
room  
Large room  
NOTE  
Mechanical ventilation device – Gas leak detector  
1. If there are 2 or more refrigerating systems in a single  
refrigerating device, the amount of refrigerant should be  
as charged in each independent device.  
3. The minimum indoor floor space compared with the  
amount of refrigerant is roughly as follows: (When the  
ceiling is 8.8 ft. high)  
For the amount of charge in this example:  
ft.3  
4000  
ft.2  
454  
Outdoor unit  
e.g., charged  
amount (353 oz)  
e.g., charged  
amount (529 oz)  
Range below  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
not needed)  
3500  
3000  
2500  
2000  
1500  
1000  
500  
398  
341  
284  
227  
170  
114  
57  
Indoor unit  
Range above  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
needed)  
Room A Room B Room C Room D Room E Room F  
The possible amount of leaked refrigerant gas in rooms A, B  
and C is 353 oz.  
The possible amount of leaked refrigerant gas in rooms D, E  
and F is 529 oz.  
0
0
0
200 400 600 800 1000 1200  
oz  
Total amount of refrigerant  
3
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 4  
Precautions for Installation Using New Refrigerant  
1. Care regarding tubing  
1-1. Process tubing  
G Material: Use C1220 phosphorous deoxidized copper specified in JIS H3300 “Copper and Copper Alloy Seamless  
Pipes and Tubes.”  
For tubes of ø7/8" (ø22.22 mm) or larger, use C1220 T-1/2H material or H material, and do not bend the tubes.  
G Tubing size: Be sure to use the sizes indicated in the table below.  
G Use a tube cutter when cutting the tubing, and be sure to remove any flash. This also applies to distribution joints  
(optional).  
G When bending tubing, use a bending radius that is 4 times the outer diameter of the tubing or larger.  
Use sufficient care in handling the tubing. Seal the tubing ends with caps or tape to  
prevent dirt, moisture, or other foreign substances from entering. These substances  
CAUTION  
can result in system malfunction.  
Unit: in. (mm)  
Material  
Outer diameter  
Wall thickness  
Material  
O
1/4 (6.35)  
1/32 (0.8)  
3/8 (9.52)  
1/32 (0.8)  
1/2 (12.7)  
1/32 (0.8)  
5/8 (15.88)  
5/128 (1.0)  
3/4 (19.05)  
Copper tube  
Copper tube  
over 5/128 (1.0)  
Unit: in. (mm)  
1/2 H, H  
1-1/8 (28.58) 1-1/4 (31.75) 1-1/2 (38.1) 1-5/8 (41.28)  
5/128 (1.0) 3/64 (1.1)  
Outer diameter  
Wall thickness  
7/8 (22.22)  
5/128 (1.0)  
1 (25.4)  
5/128 (1.0)  
over 3/64 (1.15) over 3/64 (1.20)  
1-2. Prevent impurities including water, dust and oxide from entering the tubing. Impurities can cause R410A refriger-  
ant deterioration and compressor defects. Due to the features of the refrigerant and refrigerating machine oil, the  
prevention of water and other impurities becomes more important than ever.  
2. Be sure to recharge the refrigerant only in liquid form.  
2-1. Since R410A is a non-azeotrope, recharging the refrigerant in gas form can lower performance and cause defects  
in the unit.  
2-2. Since refrigerant composition changes and performance decreases when gas leaks, collect the remaining refriger-  
ant and recharge the required total amount of new refrigerant after fixing the leak.  
3. Different tools required  
3-1. Tool specifications have been changed due to the characteristics of R410A.  
Some tools for R22- and R407C-type refrigerant systems cannot be used.  
R407C tools  
Manifold gauge  
New  
Item  
compatible  
Remarks  
tool?  
with R410A?  
Manifold gauge Yes  
No  
Types of refrigerant, refrigerating machine  
oil, and pressure gauge are different.  
Charge hose  
Yes  
No  
To resist higher pressure, material must be changed.  
Vacuum pump Yes  
Yes  
Use a conventional vacuum pump if it is equipped  
with a check valve. If it has no check valve,  
purchase and attach a vacuum pump adapter.  
Leak detector  
Flaring oil  
Yes  
Yes  
No  
No  
Leak detectors for CFC and HCFC that  
react to chlorine do not function because  
R410A contains no chlorine. Leak detector  
for HFC134a can be used for R410A.  
Vacuum pump  
Outlet  
Inlet  
For systems that use R22, apply mineral oil (Suniso oil)  
to the flare nuts on the tubing to prevent refrigerant  
leakage. For machines that use R407C or R410A, apply  
synthetic oil (ether oil) to the flare nuts.  
* Using tools for R22 and R407C and new tools for R410A together can cause defects.  
4
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 5  
3-2.Use R410A exclusive cylinder only.  
Valve  
Single-outlet valve  
(with siphon tube)  
Liquid refrigerant should be recharged  
with the cylinder standing on end as  
shown.  
Liquid  
New refrigerant R410A cannot be used for  
earlier models  
1. Compressor specifications are different.  
If recharging a R22 or R407C compressor with  
R410A, durability will significantly decrease since  
some of the materials used for compressor parts are  
different.  
2. Existing tubing cannot be used (especially R22).  
Completely cleaning out residual refrigerating  
machine oil is impossible, even by flushing.  
R410A  
3. Refrigerating machine oil differs (R22).  
Since R22 refrigerating machine oil is mineral oil, it  
does not dissolve in R410A. Therefore, refrigerating  
machine oil discharged from the compressor can  
cause compressor damage.  
R22 refrigerating machine oil  
Mineral oil (Suniso oil)  
R407C refrigerating machine oil Synthetic fluid (ether oil)  
R410A refrigerating machine oil Synthetic fluid (ether oil)  
5
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 6  
CONTENTS  
Page  
Page  
IMPORTANT! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2  
Please Read Before Starting  
Check of Density Limit  
I Concealed Duct Type (U Type)  
3-14. Required Minimum Space for Installation and  
Service  
Precautions for Installation Using New Refrigerant  
New refrigerant R410A cannot be used for earlier models  
3-15. Suspending the Indoor Unit  
3-16. Installing the Drain Piping  
3-17. Checking the Drainage  
3-18. Increasing the Fan Speed  
1. GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8  
1-1. Tools Required for Installation (not supplied)  
1-2. Accessories Supplied  
I Concealed Duct High-Static Pressure Type  
(D Type)  
1-3. Type of Copper Tube and Insulation Material  
1-4. Additional Materials Required for Installation  
1-5. Tubing Length  
3-19. Required Minimum Space for Installation and  
Service  
3-20. Suspending the Indoor Unit  
3-21. Installing the Drain Piping  
3-22. Caution for Ducting Work  
3-23. Indoor Fan Performance  
1-6. Tubing Size  
1-7. Straight Equivalent Length of Joints  
1-8. Additional Refrigerant Charge  
1-9. System Limitations  
I Ceiling-Mounted Type (T Type)  
3-24. Required Minimum Space for Installation and  
Service  
1-10. Check of Limit Density  
1-11. Installing Distribution Joint  
1-12. Optional Distribution Joint Kits  
1-13. Example of Tubing Size Selection and  
Refrigerant Charge Amount  
3-25. Suspending the Indoor Unit  
3-26. Duct for Fresh Air  
3-27. Shaping the Tubing  
2. SELECTING THE INSTALLATION SITE . . . . . 19  
2-1. Indoor Unit  
3-28. Installing the Drain Piping  
I Wall-Mounted Type (K Type)  
2-2. Outdoor Unit  
3-29. Removing the Rear Panel from the Unit  
3-30. Selecting and Making a Hole  
3-31. Installing the Rear Panel onto the Wall  
3-32. Removing the Grille to Install the Indoor Unit  
3-33. Preparing the Tubing  
2-3. Shield for Horizontal Exhaust Discharge  
2-4. Installing the Outdoor Unit in Heavy Snow Areas  
2-5. Precautions When Installing in Heavy Snow  
Areas  
2-6. Dimensions of Wind Ducting  
2-7. Dimensions of Snow Ducting  
3-34. Shaping the Tubing  
3-35. Installing the Drain Hose  
3-36. When Using Wireless Remote Controller  
Instead of Wired Remote Controller  
3. HOW TO INSTALL THE INDOOR UNIT . . . . . 24  
I 4-Way Air Discharge Semi-Concealed Type  
(X Type)  
4. HOW TO INSTALL THE OUTDOOR UNIT . . . 55  
4-1. Transporting  
3-1. Preparation for Suspending  
3-2. Suspending the Indoor Unit  
3-3. Placing the Unit Inside the Ceiling  
3-4. Installing the Drain Piping  
3-5. Checking the Drainage  
3-6. How to Install the Ceiling Panel  
3-7. Special Remarks  
4-2. Installing the Outdoor Unit  
4-3. Routing the Tubing  
4-4. Prepare the Tubing  
4-5. Connect the Tubing  
5. ELECTRICAL WIRING . . . . . . . . . . . . . . . . . . 59  
5-1. General Precautions on Wiring  
5-2. Recommended Wire Length and Wire  
Diameter for Power Supply System  
I 1-Way Air Discharge Semi-Concealed Type  
(A Type)  
3-8. Suspending the Indoor Unit  
3-9. Placing the Unit Inside the Ceiling  
3-10. Installing the Drain Piping  
3-11. Checking the Drainage  
5-3. Wiring System Diagram  
3-12. Electrical Power Wiring  
3-13. How to Install the Ceiling Panel  
6
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 7  
Page  
6. HOW TO PROCESS TUBING . . . . . . . . . . . . 63  
6-1. Connecting the Refrigerant Tubing  
6-2. Connecting Tubing Between Indoor and  
Outdoor Units  
6-3. Insulating the Refrigerant Tubing  
6-4. Taping the Tubes  
6-5. Finishing the Installation  
7. AIR PURGING . . . . . . . . . . . . . . . . . . . . . . . . . 67  
I Air Purging with a Vacuum Pump (for Test Run)  
Preparation  
8. TEST RUN . . . . . . . . . . . . . . . . . . . . . . . . . . . . 70  
8-1. Preparing for Test Run  
8-2. Test Run Procedure  
8-3. Main Outdoor Unit PCB Setting  
8-4. Auto Address Setting  
8-5. Remote Controller Test Run Settings  
8-6. Caution for Pump Down  
8-7. Meaning of Alarm Messages  
9. APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . 85  
9-1. 4-Way Air Discharge Semi-Concealed Type  
(X Type)  
9-2. 1-Way Air Discharge Semi-Concealed Type  
(A Type)  
9-3. Concealed Duct (High-Static Pressure) Type  
(U, D Type)  
9-4. Ceiling-Mounted Type (T Type)  
9-5. Wall-Mounted Type (K Type)  
7
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 8  
1. GENERAL  
This booklet briefly outlines where and how to install the air conditioning system. Please read over the entire set of instructions for  
the outdoor unit and make sure all accessory parts listed are with the system before beginning.  
1-1. Tools Required for Installation (not supplied)  
1-3. Type of Copper Tube and Insulation Material  
1. Standard screwdriver  
2. Phillips head screwdriver  
3. Knife or wire stripper  
4. Tape measure  
If you wish to purchase these materials separately from a  
local source, you will need:  
1. Deoxidized annealed copper tube for refrigerant tubing.  
2. Foamed polyethylene insulation for copper tubes as  
required to precise length of tubing. Wall thickness of the  
insulation should be not less than 5/16 in.  
5. Carpenter’s level  
6. Sabre saw or key hole saw  
7. Hacksaw  
3. Use insulated copper wire for field wiring. Wire size varies  
with the total length of wiring.  
8. Core bits  
9. Hammer  
Refer to 5. ELECTRICAL WIRING” for details.  
10. Drill  
11. Tube cutter  
Check local electrical codes and  
regulations before obtaining  
wire. Also, check any specified  
instructions or limitations.  
12. Tube flaring tool  
13. Torque wrench  
14. Adjustable wrench  
15. Reamer (for deburring)  
CAUTION  
1-4. Additional Materials Required for Installation  
1-2. Accessories Supplied  
1. Refrigeration (armored) tape  
See Tables 1-1 – 1-7.  
2. Insulated staples or clamps for connecting wire  
(See your local codes.)  
3. Putty  
4. Refrigeration tubing lubricant  
5. Clamps or saddles to secure refrigerant tubing  
6. Scale for weighing  
Table 1-1 Outdoor Unit  
Q’ty  
Part name  
Connection tubing  
Instruction manual  
Figure  
09053 Model  
14053 Model  
(10 hp)  
(16 hp)  
Outer  
diameter  
ø1-1/8"  
Inner  
diameter  
ø1"  
0
1
0
1
Outer  
diameter  
ø7/8"  
Inner  
diameter  
ø3/4"  
1
1
paper  
(hp = horse power)  
8
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 9  
Table 1-2 (4-Way Air Discharge Semi-Concealed)  
Part Name  
Figure  
Q’ty  
Remarks  
Full-scale installation diagram  
1
Printed on container box  
For securing drain hose  
For securing drain hose  
For drain joint  
Drain hose  
1
1
1
1
1
2
1
1
4
8
1
Hose band  
Drain insulator  
For liquid tube  
Flare insulator  
For gas tube  
White  
Insulating tape  
Packing  
For gas tube joint  
For drain joint  
(heat-resisting)  
Wiring cover  
Screw  
For covering erectrical wiring  
For full-scale installation diagram  
For suspending indoor unit from ceiling  
For fixing the wiring cover  
Washer  
Screw  
Table 1-3 (1-Way Air Discharge Semi-Concealed)  
Part Name  
Figure  
Q’ty  
Remarks  
Full-scale installation diagram  
1
Printed on container box  
Drain hose  
1
1
1
1
1
2
1
8
4
1
For securing drain hose  
For securing drain hose  
For drain joint  
Hose band  
Drain insulator  
For liquid tube  
Flare insulator  
For gas tube  
White  
Insulating tape  
Packing  
For gas tube joint  
(heat-resisting)  
For drain joint  
Washer  
For suspending indoor unit from ceiling  
For full-scale installation diagram  
For electrical junction box  
Screw  
Bushing  
Table 1-4 (Concealed Duct)  
Part Name  
Figure  
Q’ty  
Remarks  
Drain hose  
1
For securing drain hose  
Hose band  
1
1
1
1
2
1
8
1
8
For securing drain hose  
For drain joint  
Packing  
Drain insulator  
Flare insulator  
Insulating tape  
Flare insulator  
Washer  
For drain joint  
For liquid tube  
White  
For gas and liquid tubes flare nuts  
For gas tube  
(heat-resisting)  
For suspending indoor unit from ceiling  
For sealing recessed portion of power supply  
For flare and drain insulators  
Sealing putty  
Vinyl clamp  
G Use 3/8" for suspending bolts.  
G Field supply for suspending bolts and nuts.  
9
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 10  
Table 1-5 (Concealed Duct High-Static Pressure)  
Part Name  
Figure  
Q’ty  
Remarks  
Washer  
8
For suspending indoor unit from ceiling  
Nut  
8
1
1
1
For suspending indoor unit from ceiling  
For gas tube  
Flare insulator  
For liquid tube  
Drain socket  
For drain pipe connection  
Table 1-6 (Ceiling-Mounted)  
Part Name  
Figure  
Q’ty  
Remarks  
Full-scale installation diagram  
1
Printed on container box  
Washer  
4
2
2
2
8
1
2
1
1
For temporarily suspending indoor unit from ceiling  
T1/8"  
Flare insulator  
For gas and liquid tube joints  
T3/16"  
White  
Insulating tape  
Vinyl clamp  
Drain hose  
For gas and liquid tubes flare nuts  
For flare and drain insulators  
For main unit and PVC pipe joints  
For drain hose connection  
For drain hose joint  
(heat-resisting)  
L5-1/2"  
Hose band  
Drain insulator  
Gum eyelet  
For power supply inlet  
Table 1-7 (Wall-Mounted)  
Part Name  
Figure  
Q’ty  
Remarks  
5/32" × 1"  
Tapping screw  
10  
For fixing the rear panel  
Plastic cover  
1
1
For improved tubing appearance  
Insulator  
For insulating flare nut (2452 type only)  
10  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 11  
1-5. Tubing Length  
Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.  
1.  
2.  
Main tubing length LM = LA + LB … 262 ft  
Main distribution tubes LC – LG are selected according to the capacity after the distribution joint.  
3. The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.  
4.  
Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing sizes on the indoor units.  
L1  
L2  
H3  
L5  
B
LM  
A
Balance tubing  
LB  
LC  
LD  
L3  
(ø1/4")  
LA  
H1  
40  
Explanation of symbols  
5
39  
4
38  
For  
extension  
LE  
Distribution joint  
(APR: purchased separately)  
Max. 1.3 ft  
R410A distribution joint  
For  
extension  
APR-CHP680BA (for outdoor unit)  
APR-CHP1350BA (for outdoor unit)  
APR-P160BA (for indoor unit)  
APR-P680BA (for indoor unit)  
APR-P1350BA (for indoor unit)  
H2  
Ball valve (field supply)  
LG  
Max. 1.3 ft  
T-joint (field supply)  
3
2
1
LF  
L4  
Solidly welded shut  
(pinch weld)  
Note: Do not use commercially available T-joints for the liquid tubing  
and  
parts.  
* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor unit connections and tubing branches.  
Table 1-8 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights  
Item  
Mark  
Contents  
Length (ft.)  
>
Actual length  
492  
L1  
Max. tubing length  
>
574  
Equivalent length  
Difference between max. length and min.  
length from the No.1 distribution joint  
>
131  
L (L2 – L4)  
Allowable tubing  
length  
*3  
262  
>
LM  
Max. length of main tubing (at max. diameter)  
>
98  
40  
Max. length of each distribution tube  
1, 2...  
L1+ +  
A
39+ Total max. tubing length including length of  
2...  
1
>
984  
each distribution tube (only liquid tubing)  
+LE+LF+LG  
Distance between outdoor units  
>
32  
L5  
>
>
131  
>
49  
When outdoor unit is installed higher than indoor unit  
When outdoor unit is installed lower than indoor unit  
Max. difference between indoor units  
164  
H1  
Allowable elevation  
difference  
H2  
>
13  
H3  
Max. difference between outdoor units  
Allowable length of  
joint tubing  
T-joint tubing (field-supply); Max. tubing length between  
the first T-joint and solidly welded-shut end point  
>
6.6  
L3  
L = Length, H = Height  
NOTE  
1: The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to  
the tube ends.  
2: If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for gas  
tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table 1-9) on the  
following page (LA table), and from the table of refrigerant tubing sizes (Table 1-14) on the second following page.)  
3: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the  
gas tubes. (Use a field supply reducer.)  
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)  
4: If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the size.  
* If the existing tubing is used, and the amount of on-site additional refrigerant charge exceeds the value listed below, then  
change the size of the tubing to reduce the amount of refrigerant.  
Max. additional charge for 1 outdoor unit: 62 lbs  
Max. additional charge for 2 outdoor units: 111lbs  
11  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 12  
1-6. Tubing Size  
Table 1-9 Main Tubing Size (LA)  
Unit: in. (mm)  
153,600 191,100 249,100 307,100  
BTU/h  
(kW)  
95,500  
(28.0)  
(45.0)  
(56.0)  
(73.0)  
(90.0)  
Total system horsepower  
10  
16  
20  
26  
32  
10  
10  
16  
10  
16  
16  
Combined outdoor units  
10  
16  
ø7/8"  
(ø22.22)  
ø1-1/8"  
(ø28.58)  
ø1-1/4"  
31.75)  
Gas tubing  
ø3/8"  
(ø9.52)  
ø1/2"  
(ø12.7)  
ø5/8"  
(ø15.88)  
ø3/4"  
(ø19.05)  
Liquid tubing  
*1: If future extension is planned, select the tubing diameter based on the total horsepower after extension.  
However extension is not possible if the resulting tubing size is two ranks higher.  
*2: The balance tube (outdoor unit tube) diameter is ø1/4".  
*3: Type 1 tubing should be used for the refrigerant tubes.  
*4: If the length of the longest tube (L1) exceeds 295 ft. (equivalent length), increase the main tube (LM) size by 1 rank for the gas  
and liquid tubes. (Use field-supply reducers.) (Select from Table 1-9 and Table 1-14.)  
*5: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the  
gas tubes.  
(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table above.)  
I Size of tubing (LO) between outdoor units  
Select the size of tubing between outdoor units based on the main tubing size (LA) as given in the table above.  
Unit: in. (mm)  
Table 1-10 Main Tubing Size After Distribution (LB, LC...)  
hp = horsepower  
76,800  
(8.1 hp)  
102,400  
(11 hp)  
24,200  
(2.5 hp)  
54,600  
(6 hp)  
143,300  
178,800  
238,900  
334,400  
Below BTU/h  
Over BTU/h  
Gas tubing  
(15 hp)  
(19 hp)  
(25 hp)  
(35 hp)  
Total capacity  
after distribution  
24,200  
(2.5 hp)  
54,600  
(6 hp)  
76,800  
(8.1 hp)  
102,400  
(11 hp)  
143,300  
(15 hp)  
178,800  
(19 hp)  
238,900  
(25 hp)  
334,400  
(35 hp)  
ø1/2"  
(ø12.7)  
ø5/8"  
ø3/4"  
ø7/8"  
ø1"  
(ø25.4)  
ø1-1/8"  
ø1-1/8"  
ø1-1/4"  
ø1-1/2"  
38.1)  
(ø15.88) (ø19.05) (ø22.22)  
(ø28.58) (ø28.58) (ø31.75)  
Tubing size  
ø3/8"  
(ø9.52)  
ø3/8"  
(ø9.52)  
ø3/8"  
(ø9.52)  
ø3/8"  
(ø9.52)  
ø1/2"  
(ø12.7)  
ø1/2"  
(ø12.7)  
ø5/8"  
ø3/4"  
ø3/4"  
Liquid tubing  
(ø15.88) (ø19.05) (ø19.05)  
Note: In case the total capacity of connected indoor units exceeds the total capacity of the outdoor units, select the main tubing  
size for the total capacity of the outdoor units. (Especially the main tubing segments of LA, LB and LF.)  
Table 1-11 Outdoor Unit Tubing Connection Size ( A C)  
BTU/h  
(kW)  
95,500  
(28.0)  
153,600  
(45.0)  
ø7/8"  
(ø22.22)  
ø1-1/8"  
(ø28.58)  
Gas tubing  
Brazing connection  
ø3/8" (ø9.52)  
ø1/2" (ø12.7)  
Liquid tubing  
Flare connection  
Balance tube  
Gas tube  
ø1/4" (ø6.35)  
Liquid tube  
Balance tubing  
Flare connection  
Unit: in. (mm)  
Unit: in. (mm)  
Table 1-12 Indoor Unit Tubing Connection Size  
Indoor unit type  
Gas tubing  
7
9
12  
18  
24  
36  
48  
ø1/2" (ø12.7)  
ø5/8" (ø15.88)  
ø3/8" (ø9.52)  
ø1/4" (ø6.35)  
Liquid tubing  
Note: Use C1220T-1/2H material for tubing over ø3/4" (ø22.22).  
12  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 13  
1-7. Straight Equivalent Length of Joints  
Design the tubing system by referring to the following table for the straight equivalent length of joints.  
Table 1-13 Straight Equivalent Length of Joints  
Unit: ft.  
1-1/8" 1-1/4" 1-1/2"  
1/2"  
5/8"  
3/4"  
7/8"  
1"  
Gas tubing size (in. (mm))  
90° elbow  
(12.7) (15.88) (19.05) (22.22) (25.4) (28.58) (31.8)  
(38.1)  
1
1.1  
0.9  
3.4  
9.2  
1.4  
1
1.6  
1.2  
1.7  
1.3  
1.9  
1.4  
2.3  
1.7  
2.6  
45° elbow  
0.8  
3
1.9  
7.8  
U-shape tube bent (R2-3/8" – 4" (60 – 100))  
Trap bend  
4.1  
10.5  
4.7  
5.1  
5.6  
6.9  
7.5  
12.5  
14.1  
15.4  
16.4  
14.0  
Y-branch distribution joint  
Ball valve for service  
Equivalent length conversion not needed.  
Equivalent length conversion not needed.  
Table 1-14 Refrigerant tubing (Existing tubing can be used.)  
Tubing size (in. (mm))  
* When bending the tubes, use a bending  
radius that is at least 4 times the outer  
diameter of the tubes.  
Material O  
ø1/4" (ø6.35)  
Material 1/2H • H  
t1/32" (0.8)  
t1/32" (0.8)  
ø7/8" (ø22.22)  
ø1" (ø25.40)  
t5/128" (1.0)  
t5/128" (1.0)  
In addition, take sufficient care to avoid  
crushing or damaging the tubes when  
bending them.  
ø3/8" (ø9.52)  
ø1/2" (ø12.7)  
ø5/8" (ø15.88)  
ø3/4" (ø19.05)  
t1/32" (0.8)  
ø1-1/8" (ø28.58)  
ø1-1/4" (ø31.75)  
ø1-1/2" (ø38.10)  
ø1-5/8" (ø41.28)  
t5/128" (1.0)  
t5/128" (1.0)  
over t5/128" (1.0)  
t3/64" (1.1)  
over t3/64" (1.15)  
over t3/64" (1.20)  
1-8. Additional Refrigerant Charge  
Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.  
Table 1-15 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size  
Required amount of charge = (Amount of refrigerant charge per  
Liquid tubing size  
(in. (mm))  
Amount of refrigerant  
charge (oz/ft.)  
meter of each size of liquid tube × its tube length) + (...) + (...)  
ø1/4" (ø6.35)  
ø3/8" (ø9.52)  
ø1/2" (ø12.7)  
ø5/8" (ø15.88)  
ø3/4" (ø19.05)  
ø7/8" (ø22.22)  
0.279  
0.602  
1.38  
1.99  
2.78  
3.93  
* Always charge accurately using a scale for weighing.  
* If the existing tubing is used, and the amount of on-site additional  
refrigerant charge exceeds the value listed below, then change the  
size of the tubing to reduce the amount of refrigerant.  
Max. additional charge for 1 outdoor unit :62 lbs  
Max. additional charge for 2 outdoor units :111 lbs  
Max. additional charge for 3 outdoor units :133 lbs  
Table 1-16 Refrigerant Charge Amount at Shipment (for outdoor unit)  
CHDX09053  
423  
CHDX14053  
458  
DC  
(oz)  
1-9. System Limitations  
Table 1-17 System Limitations  
Max. No. allowable connected outdoor units  
Max. capacity allowable connected outdoor units  
Max. connectable indoor units  
2 *1  
307,100 BTU/h (32 hp, 90 kW)  
40  
Max. allowable indoor/outdoor capacity ratio  
50 – 130 %  
*1: Up to 2 units can be connected if the system has been extended.  
13  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 14  
Minimum indoor volume & floor area as against the amount  
of refrigerant is roughly as given in the following table.  
Always check the gas density  
limit for the room in which the  
unit is installed.  
WARNING  
ft.3  
10000  
ft.2  
1136  
1079  
1022  
966  
909  
852  
795  
738  
682  
625  
568  
511  
454  
398  
341  
284  
227  
170  
114  
57  
1-10. Check of Limit Density  
9500  
9000  
8500  
8000  
7500  
7000  
6500  
6000  
5500  
5000  
4500  
4000  
3500  
3000  
2500  
2000  
1500  
1000  
500  
When installing an air conditioner in a room, it is necessary to  
ensure that even if the refrigerant gas accidentally leaks out, its  
density does not exceed the limit level for that room.  
If the density could exceed the limit level, it is necessary to provide  
an opening between the unit and the adjacent room, or to install  
mechanical ventilation which is interlocked with a leak detector.  
Range below  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
not needed)  
(Total refrigerant charged amount: oz)  
3
(Min. indoor volume where the indoor unit is installed: ft. )  
Range above  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
needed)  
3
< Limit density 0.3 (oz/ft. )  
The limit density of refrigerant R410A which is used in this unit is  
3
0.3 oz/ft. (ISO 5149).  
0
0
The shipped outdoor unit comes charged with the amount of refrig-  
erant fixed for each type, so add it to the amount that is charged in  
the field. (For the refrigerant charge amount at shipment, refer to the  
unit’s nameplate.)  
0
500 1000 1500 2000 2500 3000  
oz  
Total amount of refrigerant  
Pay special attention to any location,  
such as a basement, etc., where leak-  
Tube branching methods (horizontal use)  
CAUTION  
ing refrigerant can accumulate, since  
refrigerant gas is heavier than air.  
B
1-11. Installing Distribution Joint  
Horizontal  
line  
A
A
(1) Refer to “HOW TO ATTACH DISTRIBUTION JOINT” enclosed  
with the optional distribution joint kit  
View as seen  
from arrow  
B
Arrow view  
(APR-CHP680BA, APR-CHP1350BA, APR-P160BA,  
APR-P680BA, APR-P1350BA).  
(2) When creating a branch using a commercially available  
T-joint (header joint system), orient the main tubing so that it is  
either horizontal (level) or vertical. In order to prevent accumu-  
lation of refrigerant oil in stopped units, if the main tubing is  
horizontal then each branch tubing length should be at an  
angle that is greater than horizontal. If the main tubing is verti-  
cal, provide a raised starting portion for each branch.  
Types of vertical trap specifications  
(When using ball valve)  
Main tubing  
Indoor unit (more than 2 units)  
Ball valve  
(BV: purchased  
(If only 1 unit is connected, a ball valve  
is also needed on this side.)  
(3) If there are height differences between indoor units or if branch  
tubing that follows a distribution joint is connected to only 1  
unit, a trap or ball valve must be added to that  
separately)  
Indoor unit (1)  
(When not using ball valve)  
distribution joint. (When adding the ball valve, locate it  
within 1.3 ft. of the distribution joint.)  
Main tubing  
Horizontal  
Indoor unit  
(Each unit is connected  
to tubing that is either  
level or is directed  
downward.)  
If a trap or ball valve is not added, do not operate the sys-  
tem before repairs to a malfunctioning unit are  
completed. (The refrigerant oil sent through the tubing to  
the malfunctioning unit will accumulate and may damage  
the compressor.)  
Branch tubing is  
directed upward.  
More than  
8 inch  
Indoor unit is directed downward  
14  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 15  
1-12. Optional Distribution Joint Kits  
See the installation instructions packaged with the distribution joint kit for the installation procedure.  
Table 1-18  
Model name  
Cooling capacity after distribution  
232,000 BTU/h (68.0 kW) or less  
460,700 BTU/h (135.0 kW) or less  
76,400 BTU/h (22.4 kW) or less  
232,000 BTU/h (68.0 kW) or less  
460,700 BTU/h (135.0 kW) or less  
Remarks  
1. APR-CHP680BA  
2. APR-CHP1350BA  
3. APR-P160BA  
4. APR-P680BA  
5. APR-P1350BA  
For outdoor unit  
For outdoor unit  
For indoor unit  
For indoor unit  
For indoor unit  
I Tubing size (with thermal insulation)  
1. APR-CHP680BA  
For outdoor unit (Capacity after distribution joint is 232,000 BTU/h (68.0 kW) or less.)  
Example:  
Gas tubing  
6-59/64  
Liquid tubing  
4-21/64  
B
H I  
F
3-13/16  
5-5/16  
F
C
G
C
D E F  
G
E F  
I H  
D
G
C
Distribution  
Joint  
H
I
Distribution  
Joint  
Reducing  
Joints  
Insulation  
Reducing  
Joints  
Unit: in.  
Insulation  
Table 1-19 Size of connection point on each part (Shown are inside diameters of tubing)  
Size  
Part A  
Part B  
Part C  
Part D  
Part E  
Part F  
Part G  
Part H  
Part I  
ø1-1/2"  
(ø38.1)  
ø1-1/4"  
(ø31.75)  
ø1-1/8"  
(ø28.58)  
ø1"  
(ø25.4)  
ø7/8"  
(ø22.22)  
ø3/4"  
(ø19.05)  
ø5/8"  
(ø15.88)  
ø1/2"  
(ø12.7)  
ø3/8"  
(ø9.52)  
in. (mm)  
2. APR-CHP1350BA  
For outdoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW) and no more than  
460,700 BTU/h (135.0 kW).)  
Gas tubing  
6-57/64  
Liquid tubing  
Example:  
4-21/64  
H I  
F
3-13/16  
5-5/16  
A
F
A
B
G
B
G
E F  
I H  
C
D
G
Distribution  
B
Distribution  
Joint  
Joint  
H
I
Reducing  
Insulation  
C
E
F
Joints  
D
Reducing  
Joints  
Unit: in.  
Insulation  
Table 1-20 Size of connection point on each part (Shown are inside diameters of tubing)  
Size  
Part A  
Part B  
Part C  
Part D  
Part E  
Part F  
Part G  
Part H  
Part I  
ø1-1/2"  
(ø38.1)  
ø1-1/4"  
(ø31.75)  
ø1-1/8"  
(ø28.58)  
ø1"  
(ø25.4)  
ø7/8"  
(ø22.22)  
ø3/4"  
(ø19.05)  
ø5/8"  
(ø15.88)  
ø1/2"  
(ø12.7)  
ø3/8"  
(ø9.52)  
in. (mm)  
15  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 16  
3. APR-P160BA  
Use: For indoor unit (Capacity after distribution joint is 76,400 BTU/h (22.4 kW) or less.)  
Example:  
Gas tubing  
4-21/64  
3-13/16  
Liquid tubing  
4-21/64  
3-13/16  
B
A
C
B
D E  
C
B
D
A
Distribution  
Joint  
Distribution  
Joint  
C
B
Insulation  
Insulation  
D
E
C
Unit: in.  
Table 1-21 Size of connection point on each part (Shown are inside diameters of tubing)  
Size  
Part A  
Part B  
Part C  
Part D  
Part E  
ø3/4"  
(ø19.05)  
ø5/8"  
(ø15.88)  
ø1/2"  
(ø12.7)  
ø3/8"  
(ø9.52)  
ø1/4"  
(ø6.35)  
in. (mm)  
4. APR-P680BA  
Use: For indoor unit (Capacity after distribution joint is greater than 76,400 BTU/h (22.4 kW) and no more than  
232,000 BTU/h (68.0 kW).)  
Example:  
Gas tubing  
Liquid tubing  
4-21/64  
6-57/64  
5-5/16  
3-13/16  
A
B C D  
EF  
E
F GH  
D C B  
E
A
GF  
E
A
Distribution  
Joint  
Distribution  
Joint  
F
G
H
B
C
D
Reducing  
Joints  
Reducing  
Joints  
Insulation  
E
F
Insulation  
Unit: in.  
Table 1-22 Size of connection point on each part (Shown are inside diameters of tubing)  
Size  
Part A  
Part B  
Part C  
Part D  
Part E  
Part F  
Part G  
Part H  
ø1-1/8"  
(ø28.58)  
ø1"  
(ø25.4)  
ø7/8"  
(ø22.22)  
ø3/4"  
(ø19.05)  
ø5/8"  
(ø15.88)  
ø1/2"  
(ø12.7)  
ø3/8"  
(ø9.52)  
ø1/4"  
(ø6.35)  
in. (mm)  
5. APR-P1350BA  
Use: For indoor unit (Capacity after distribution joint is greater than 232,000 BTU/h (68.0 kW) and no more than  
460,700 BTU/h (135.0 kW).)  
Example:  
Gas tubing  
6-57/64  
Liquid tubing  
4-21/64  
3-13/16  
5-5/16  
A
F
F
B
G
G
H
B
C D  
A
G
Distribution  
Joint  
B
Distribution  
Joint  
D C  
H
I
J
C
D
Insulation  
E
F
Reducing  
Joints  
Reducing  
Joints  
Insulation  
G
H
Unit: in.  
Part J  
Table 1-23 Size of connection point on each part (Shown are inside diameters of tubing)  
Size  
Part A  
Part B  
Part C  
Part D  
Part E  
Part F  
Part G  
Part H  
Part I  
ø1-1/2"  
(ø38.1)  
ø1-1/4"  
(ø31.75)  
ø1-1/8"  
(ø28.58)  
ø1"  
(ø25.4)  
ø7/8"  
(ø22.22)  
ø3/4"  
(ø19.05)  
ø5/8"  
(ø15.88)  
ø1/2"  
(ø12.7)  
ø3/8"  
(ø9.52)  
ø1/4"  
(ø6.35)  
in. (mm)  
16  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 17  
1-13. Example of Tubing Size Selection and Refrigerant Charge Amount  
Additional refrigerant charging  
Based on the values in Tables 1-9, 10, 11, 12 and 15, use the liquid tubing size and length, and calculate the amount of additional  
refrigerant charge using the formula below.  
Required additional  
refrigerant charge (oz)  
= 3.93 × (a) + 2.78 × (b) + 1.99 × (c) + 1.38 × (d) + 0.602 × (e) + 0.279 × (f)  
(a) : Liquid tubing  
(b) : Liquid tubing  
(c) : Liquid tubing  
Total length of ø7/8" (ft.)  
Total length of ø3/4" (ft.)  
Total length of ø5/8" (ft.)  
(d) : Liquid tubing  
(e) : Liquid tubing  
(f) : Liquid tubing  
Total length of ø1/2" (ft.)  
Total length of ø3/8" (ft.)  
Total length of ø1/4" (ft.)  
G Charging procedure  
Be sure to charge with R410A refrigerant in liquid form.  
1. After performing a vacuum, charge with refrigerant from the liquid tubing side. At this time, all valves must be in the “fully  
closed” position.  
2. If it was not possible to charge the designated amount, operate the system in Cooling mode while charging with refrigerant  
from the gas tubing side. (This is performed at the time of the test run. For this, all valves must be in the “fully open” position.  
However if only one outdoor unit is installed, a balance tube is not used. Therefore, leave the valves fully closed.)  
Charge with R410A refrigerant in liquid form.  
With R410A refrigerant, charge while adjusting the amount being fed a little at a time in order to prevent liquid refrigerant from  
backing up.  
G After charging is completed, turn all valves to the “fully open” position.  
G Replace the tubing covers as they were before.  
Balance tube  
1. R410A additional charging absolutely must  
be done through liquid charging.  
Use a flathead screwdriver and  
open by turning the part with the  
screw groove to the right,  
from “–” to “|”.  
CAUTION  
2. The R410A refrigerant cylinder has a gray  
base color, and the top part is pink.  
3. The R410A refrigerant cylinder includes a  
siphon tube. Check that the siphon tube is  
present. (This is indicated on the label at the  
top of the cylinder.)  
4. Due to differences in the refrigerant, pres-  
sure, and refrigerant oil involved in installa-  
tion, it is not possible in some cases to use  
the same tools for R22 and for R410A.  
Liquid tube  
Use a hex wrench (width 5/32 inch)  
and turn to the left to open.  
Example:  
Gas tube  
Outdoor unit  
Use a flathead screwdriver and  
open by turning the part with the  
screw groove to the right,  
from “–” to “|”.  
09053  
model  
09053  
model  
B
A
LC  
LB  
LA  
1
2
3
4
48 model  
48 model  
48 model  
36 model  
G Example of each tubing length  
Main tubing  
LA = 131 ft.  
LB = 16 ft.  
LC = 16 ft.  
Distribution joint tubing  
Outdoor side  
A = 7 ft.  
Indoor side  
1 = 98 ft.  
2 = 16 ft.  
3 = 16 ft.  
4 = 65 ft.  
B = 7 ft.  
17  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 18  
G Obtain liquid tubing size from Tables 1-9, 10, 11, 12 and 15.  
Main tubing  
LA = ø5/8 (ft.) (Total capacity of indoor unit is 179,400 BTU/h)  
LB = ø1/2 (ft.) (Total capacity of indoor unit is 131,600 BTU/h)  
LC = ø3/8 (ft.) (Total capacity of indoor unit is 83,800 BTU/h)  
The longest tubing length in this example  
(LA = 131 ft.)  
Distribution joint tubing  
Outdoor side  
Indoor side  
A: ø3/8 (ft.)  
1: ø3/8 (ft.)  
B: ø3/8 (ft.) (from outdoor unit connection tubing)  
2: ø3/8 (ft.) 3: ø3/8 (ft.) 4: ø3/8 (ft.) (from indoor unit connection tubing)  
G Obtain charge amount for each tubing size  
Note that the charge amounts per 1 meter are different for each liquid tubing size.  
ø5/8 (ft.) LA  
: 131 ft. × 1.99 oz/ft. = 261 oz  
: 16 ft. × 1.38 oz/ft. 22 oz  
ø1/2 (ft.) LB  
=
ø3/8 (ft.) LC + A – B + 1 – 4 : 225 ft. × 0.602 oz/ft. = 135 oz  
Total 418 oz  
Additional refrigerant charge amount is 418 oz.  
Be sure to check the limit density for  
CAUTION  
the room in which the indoor unit is  
installed.  
Checking of limit density  
Density limit is determined on the basis of the size of a room  
using an indoor unit of minimum capacity. For instance, when  
an indoor unit is used in a room (floor area 161 ft.2 × ceiling  
height 8.8 ft. = room volume 1417 ft.3), the graph at right  
shows that the minimum room volume should be 2455 ft.3  
(floor area 279 ft.2) for refrigerant of 418 oz.  
ft.3  
4000  
ft.2  
454  
Range below  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
not needed)  
3500  
3000  
2500  
2000  
1500  
1000  
500  
398  
341  
284  
227  
170  
114  
57  
<Determination by calculation>  
Overall refrigerant charge amount for the air conditioner: oz  
(Minimum room volume for indoor unit: ft.3)  
418 (oz)  
Range above  
the density limit of  
0.3 oz/ft.3  
(countermeasures  
needed)  
=
= 0.29 (oz/ft.3) < 0.3 (oz/ft.3)  
1417 (ft.3)  
0
0
0
200 400 600 800 1000 1200  
oz  
Total amount of refrigerant  
Therefore, openings such as louvers are not required for this  
room.  
18  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 19  
Ceiling-Mounted Type  
2. SELECTING THE INSTALLATION SITE  
2-1. Indoor Unit  
Ceiling  
Wall  
AVOID:  
G areas where leakage of flammable gas may be expected.  
G places where large amounts of oil mist exist.  
min. 10 in.  
min. 10 in.  
Front view  
NOTE  
G direct sunlight.  
The rear of the indoor unit can be installed flush  
against the wall.  
G locations near heat sources which may affect the  
Air  
discharge  
performance of the unit.  
G locations where external air may enter the room directly.  
This may cause “sweating” on the air discharge ports,  
causing them to spray or drip.  
Air intake  
min. 2 ft.  
G locations where the remote controller will be splashed with  
water or affected by dampness or humidity.  
Side view  
Max. 10 in.  
Obstacle  
G installing the remote controller behind curtains or furniture.  
G locations where high-frequency emissions are generated.  
Fig. 2-1  
ConcealedDuct(High-StaticPressure)Type  
DO:  
4-Way Air Discharge Semi-Concealed Type  
G select an appropriate position from which every corner of  
the room can be uniformly cooled.  
3 ft.  
3 ft.  
G select a location where the ceiling is strong enough to  
support the weight of the unit.  
G select a location where tubing and drain pipe have the  
3 ft.  
shortest run to the outdoor unit.  
3 ft.  
3 ft.  
G allow room for operation and maintenance as well as  
unrestricted air flow around the unit.  
Fig. 2-2  
G install the unit within the maximum elevation difference  
above or below the outdoor unit and within a total tubing  
length (L) from the outdoor unit as detailed in Table 1-8.  
1-Way Air Discharge Semi-Concealed Type  
Ceiling  
G allow room for mounting the remote controller about 3 ft.  
off the floor, in an area that is not in direct sunlight nor in  
the flow of cool air from the indoor unit.  
min. 2 in.  
Wall  
Obstacle  
NOTE  
Air  
Air delivery will be degraded if the distance from the floor to  
the ceiling is greater than 10 ft.  
discharge  
Air  
Wall  
intake  
min. 2 in.  
Side view  
Fig. 2-3  
Wall-Mounted Type  
min.6 in.  
min.  
6 in.  
min.  
6 in.  
Front View  
Fig. 2-4  
19  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 20  
2-2. Outdoor Unit  
Exhaust fan  
Heat  
AVOID:  
Hot air  
G heat sources, exhaust fans, etc.  
G damp, humid or uneven locations  
G indoors (no-ventilation location)  
source  
Out-  
door  
unit  
DO:  
G choose a place as cool as possible.  
G choose a place that is well ventilated.  
Fig. 2-5  
G allow enough room around the unit for air intake/  
Example of installation of 2 units  
(When wall height is below 6 ft.)  
exhaust and possible maintenance.  
Installation Space  
* More than 4 in.  
Install the outdoor unit where there is enough space for ven-  
tilation. Otherwise the unit may not operate properly. Fig. 2-6  
shows the minimum space requirement around the outdoor  
units when 3 sides are open and only 1 side is shuttered,  
with open space above the unit. The mounting base should  
be concrete or a similar material that allows for adequate  
drainage. Make provisions for anchor bolts, platform height,  
and other site-specific installation requirements.  
* More than 4 in.  
More than  
2 in.  
More than  
1.7 ft.  
* More than 4 in.  
G Leave space open above the  
CAUTION  
unit.  
* However, be sure to ensure a space of 1 ft. or more at  
G Construct louvers or other  
openings in the wall, if nec-  
essary, to ensure adequate  
ventilation.  
either the right side or the rear of the unit.  
Fig. 2-6  
NOTE  
3-15/16  
74-1/64 (Ceiling panel dimensions)  
G Do not do any wiring or tubing within 1 ft. of the front  
panel, because this space is needed as a servicing  
space for the compressor.  
35-3/64 (Ceiling panel dimensions)  
35-3/64 (Ceiling panel dimensions)  
G Ensure a base height of 4 in. or more to ensure that  
drainage water does not accumulate and freeze  
around the bottom of the unit.  
G If installing a drain pan, install the drain pan prior to  
installing the outdoor unit.  
* Make sure there is at least 6 in. between the outdoor  
unit and the ground.  
31-7/64 (Installation hole pitch)  
31-7/64 (Installation hole pitch)  
7-7/8  
Also, the direction of the tubing and electrical wiring  
should be from the front of the outdoor unit.  
70-5/64 (Installation hole pitch)  
Unit: in.  
Top view  
Fig. 2-7  
20  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 21  
2-3. Shield for Horizontal Exhaust Discharge  
It is necessary to install an air-discharge chamber (field  
supply) to direct exhaust from the fan horizontally if it is diffi-  
cult to provide a minimum space of 7 ft. between the air-dis-  
charge outlet and a nearby obstacle. (Fig. 2-8)  
In regions with heavy snowfall,  
the outdoor unit should be  
CAUTION  
provided with a solid, raised plat-  
form and snow-proof ducting  
(field supply). (Fig. 2-9)  
2-4. Installing the Outdoor Unit in Heavy Snow  
Areas  
In locations where wind-blown snow can be a problem,  
snow-proof ducting (field supply) should be fitted to the unit  
and direct exposure to the wind should be avoided as much  
as possible. (Fig. 2-10) The following problems may occur if  
proper countermeasures are not taken:  
Fig. 2-8  
DO  
G The fan in the outdoor unit may stop running, causing the  
unit to be damaged.  
G There may be no air flow.  
G The tubing may freeze and burst.  
G The condenser pressure may drop because of strong  
AVOID  
wind, and the indoor unit may freeze.  
2-5. Precautions When Installing in Heavy Snow  
Areas  
a) The platform should be higher than the maximum snow  
depth. (Fig. 2-9)  
Fallen snow  
Without snow-  
With snow-  
proof ducting  
proof ducting  
b) The 2 anchoring feet of the outdoor unit should be used  
for the platform, and the platform should be installed  
beneath the air-intake side of the outdoor unit.  
(Without platform)  
(High platform)  
Fig. 2-9  
c) The platform foundation must be solid and the unit must  
be secured with anchor bolts.  
d) When installing on a roof subject to strong wind, coun-  
termeasures must be taken to prevent the unit from  
being overturned.  
Fig. 2-10  
21  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 22  
2-6. Dimensions of Wind Ducting  
Reference diagram for air-discharge chamber (field supply)  
unit: in.  
Ceiling panel  
Ceiling panel  
33-3/16  
Air direction: Front direction  
Air direction: Right direction  
35-3/64  
(Ceiling panel dimensions)  
35-15/64  
(Maximum bracket dimensions)  
35-3/64  
35-3/64  
(Ceiling panel dimensions)  
(Ceiling panel dimensions)  
2-11/64  
15/16  
15/16  
2-11/64  
Front view  
Right side view  
Front view  
Right side view  
Note: Can be installed so that the air direction is to the front, right, left or rear direction.  
2-unit installation  
74-7/32 (2-unit installation: maximum dimensions)  
5-25/32  
33-3/16  
33-3/16  
Top view  
31-7/64  
31-7/64  
(Installation hole pitch)  
unit: in.  
35-3/64  
(Ceiling panel dimensions)  
2-11/64  
15/16  
7-7/8  
Front view  
Right side view  
22  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 23  
2-7. Dimensions of Snow Ducting  
Reference diagram for snow-proof ducting (field supply)  
31-17/32  
Air direction:  
Front direction  
Air direction:  
Right direction  
Ceiling panel  
Ceiling panel  
31-17/32  
53-55/64  
31-17/32 (Air intake duct)  
33-3/16 (Air outlet duct)  
9-13/32  
9-13/32  
9-13/32  
9-13/32  
9-13/32  
35-3/64  
(Ceiling panel dimensions)  
53-55/64  
9-13/32  
unit: in.  
35-3/64  
35-3/64  
(Ceiling panel dimensions)  
(Ceiling panel dimensions)  
32-7/8  
32-7/8  
15/16  
15/16  
1 pc.  
4 pc.  
Front view  
Right side view  
Front view  
Right side view  
Note: Can be installed so that the air direction is to the front, right, left or rear direction.  
74-1/64 (Ceiling panel dimensions)  
2-unit installation  
Ceiling panel dimensions  
35-3/64  
35-3/64  
3-15/16  
Top (Before installation of snowfall protection duct)  
31-7/64  
7-7/8  
31-7/64  
Installation hole pitch  
Installation hole pitch  
70-5/64  
Installation hole pitch  
2
3
2
unit: in.  
35-3/64  
(Ceiling panel dimensions)  
Ceiling panel  
9-29/64  
2-11/64  
9-29/64  
7/8  
2
3
2
1
1
3
1
2
2
2
92-53/64  
Front view  
Right side view  
23  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 24  
3. HOW TO INSTALL THE INDOOR UNIT  
I 4-Way Air Discharge Semi-Concealed Type (X Type)  
3-1. Preparation for Suspending  
Note: For DC Fan Tap Change Procedure  
for 4-Way Cassette, see page 30.  
This unit uses a drain pump. Use a carpenter’s level to check that the  
unit is level.  
e-in-anchor  
e-in-plug  
X
Concrete  
Insert  
3-2. Suspending the Indoor Unit  
(1) Fix the suspension bolts securely in the ceiling using the method  
shown in the diagrams (Figs. 3-1 and 3-2), by attaching them to  
the ceiling support structure, or by any other method that ensures  
that the unit will be securely and safely suspended.  
Suspension bolt (M10 or 3/8")  
(field supply)  
(2) Follow Fig. 3-2 and Table 3-1 to make the holes in the ceiling.  
Fig. 3-1  
Table 3-1  
Unit: in. (mm)  
Length  
A
B
C
D
Type  
31-1/32 28-15/32 34-27/32 34-27/32  
(788) (723) (885) (885)  
12, 18, 24, 36  
(3) Determine the pitch of the suspension bolts using the supplied  
full-scale installation diagram. The diagram and table (Fig. 3-3  
and Table 3-2) show the relationship between the positions of the  
suspension fitting, unit, and panel.  
Unit: in. (mm)  
A (suspension bolt pitch)  
Table 3-2  
Length  
A
B
C
D
E
Type  
C (ceiling opening dimension)  
4-29/64  
(113)  
6-13/16  
(173)  
10-5/64  
(256)  
8-17/64  
(210)  
3-15/32  
(88)  
12, 18, 24  
Fig. 3-2  
4-29/64  
(113)  
6-13/16  
(173)  
12-9/16  
(319)  
8-17/64  
(210)  
3-15/32  
(88)  
36  
Drain outlet(other side)  
Refregerant tubing joint(liquid side)  
Refregerant tubing joint(gas side)  
(VP25)  
Suspension lug  
Power supply outlet  
Unit: in. (mm)  
Inter-unit control wiring  
Fig. 3-3  
3-3. Placing the Unit Inside the Ceiling  
(1) When placing the unit inside the ceiling, determine  
the pitch of the suspension bolts using the supplied  
full-scale installation diagram. (Fig. 3-4)  
Tubing and wiring must be laid inside the ceiling  
when suspending the unit. If the ceiling is already  
constructed, lay the tubing and wiring into position  
for connection to the unit before placing the unit  
inside the ceiling.  
Full-scale installation diagram  
(printed on top of container box)  
Unit: in. (mm)  
Supplied bolt  
Fig. 3-4  
24  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 25  
(2) The length of suspension bolts must be appropriate  
for a distance between the bottom of the bolt and the  
bottom of the unit of more than 19/32 in. as shown in  
Fig. 3-5.  
Suspension bolt  
Suspension lug  
Nuts and washers  
(use for upper and lower)  
(3) Thread the 3 hexagonal nuts and 2 washers (field  
supply) onto each of the 4 suspension bolts as shown  
in Fig. 3-5. Use 1 nut and 1 washer for the upper side,  
and 2 nuts and 1 washer for the lower side, so that the  
unit will not fall off the suspension lugs.  
X
Notch  
Double nut  
15/32 – 43/64 (12 – 17)  
(4) Adjust so that the distance between the unit and the  
ceiling bottom is 15/32 to 43/64 in. Tighten the nuts on  
the upper side and lower side of the suspension lug.  
Unit: in. (mm)  
Fig. 3-5  
(5) Remove the protective polyethylene used to protect  
the fan parts during transport.  
Hard PVC  
socket  
Hard PVC pipe  
VP-25  
(Field supply)  
Hose band  
Connection pipe  
VP-25  
(Field supply)  
3-4. Installing the Drain Piping  
Supplied  
drain hose  
(drain port)  
(1) Prepare a standard hard PVC pipe (O.D. 1-1/4 in.) for  
the drain and use the supplied drain hose and hose  
band to prevent water leaks.  
The PVC pipe must be purchased separately. The  
unit’s transparent drain port allows you to check  
drainage. (Fig. 3-6)  
PVC adhesive  
Packing  
(supplied)  
Align the hose  
band with the end  
of the pipe  
CAUTION  
Bead  
Fig. 3-6  
G Insert the drain pipe until it contacts the socket, as  
shown in Fig. 3-6, then secure it tightly with the  
hose band.  
G Do not use adhesive when connecting the supplied  
hose.  
Drain insulator (supplied)  
Reasons: 1. It may cause water to leak from the  
connection. Since the connection is  
slippery just after the adhesive has been  
applied, the pipe easily slips off.  
2. The pipe cannot be removed when  
maintenance is needed.  
Fig. 3-7  
G Do not bend the supplied drain hose 90° or more.  
The hose may slip off.  
G Align the hose bands with the end of the hose.  
Tighten the hose band firmly. Please make sure  
that the bead is not covered by the hose band.  
(Fig. 3-6)  
Air bleeder prohibited  
Tighten the hose clamps so  
their locking nuts face upward.  
(Fig. 3-6)  
CAUTION  
Fig. 3-8  
(2) After checking the drainage, wrap the supplied packing  
and drain pipe insulator around the pipe. (Fig. 3-7)  
G Do not install an air bleeder  
as this may cause water to  
spray from the drain pipe  
outlet. (Fig. 3-8)  
CAUTION  
NOTE  
Make sure the drain pipe has a downward gradient (1/100  
or more) and that there are no water traps.  
25  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 26  
CAUTION  
11-3/16 in. or less (as short as possible)  
33-15/32 in. or less  
G In cases where it is necessary to raise the height  
0 – 45°  
of the drain piping, the drain piping can be raised  
X
to a maximum height of 33-15/32" above the  
bottom surface of the ceiling. Under no  
conditions attempt to raise it higher than  
33-15/32" above the bottom surface of the ceiling.  
Doing so will result in water leakage. (Fig. 3-9)  
G Do not install the pipe with an upward gradient  
from the connection port. This will cause the  
drain water to flow backward and leak when the  
unit is not operating. (Fig. 3-10)  
* Length of supplied drain hose = 9-27/32 in.  
Fig. 3-9  
Upward gradient prohibited  
G Do not apply force to the piping on the unit side  
when connecting the drain pipe. The pipe should  
not be allowed to hang unsupported from its  
connection to the unit. Fasten the pipe to a wall,  
frame, or other support as close to the unit as  
possible. (Fig. 3-11)  
Fig. 3-10  
G Provide insulation for any pipes that are run  
indoors.  
Support  
pieces  
3-5. Checking the Drainage  
Fig. 3-11  
After wiring and drain piping are completed, use the  
following procedure to check that the water will drain  
smoothly. For this, prepare a bucket and wiping cloth to  
catch and wipe up spilled water.  
Drainage check  
(1) Connect power to the power terminal board (R, S  
terminals) inside the electrical component box.  
(2) Slowly pour about 0.3 gal of water into the drain pan  
to check drainage. (Fig. 3-12)  
(3) Short the check pin (CHK) on the indoor control  
board and operate the drain pump. Check the water  
flow through the transparent drain pipe and see if  
there is any leakage.  
Drain pan outlet  
Water (Approx. 0.3 gal)  
Plastic container  
for water intake  
(4) When the check of drainage is complete, open the  
check pin (CHK) and remount the tube cover.  
Fig. 3-12  
Be careful since the fan will  
start when you short the pin  
on the indoor control board.  
CAUTION  
26  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 27  
3-6. How to Install the Ceiling Panel  
A
must be within the range of 15/32 – 43/64 in.  
3-6-1. Before Installing the Ceiling Panel  
Checking the unit position  
If not within this range, malfunction or other trouble may result.  
(1) Check that the ceiling hole is within this range:  
33-55/64 × 33-55/64 to 35-53/64 × 35-53/64 in.  
Main unit  
X
(2) Use the full-scale installation diagram (from the  
packaging) that was supplied with the unit to  
determine the positioning of the unit on the ceiling  
surface. If the positions of the ceiling surface and  
unit do not match, air leakage, water leakage, flap  
operation failure, or other problems may result.  
A
Ceiling opening  
dimension  
Ceiling side  
Fig. 3-13  
Flap  
CAUTION  
G Never place the panel face-down. Either hang  
it vertically or place it on top of a projecting  
object. Placing it face-down will damage the  
surface.  
G Do not touch the flap or apply force to it.  
(This may cause flap malfunction.)  
Fig. 3-14  
Remove the air-intake grille and air filter from the  
ceiling panel. (Figs. 3-16, 3-17 and 3-18)  
Screw  
Latch  
a) Remove the 2 screws on the latch of the air-intake  
grille. (Fig. 3-16)  
b) Slide the air-intake grille catches in the direction  
1
shown by the arrows  
(Fig. 3-17)  
to open the grille.  
c) With the air-intake grille opened, remove the grille  
hinge from the ceiling panel by sliding it in the direc-  
tion shown by the arrow 2 . (Fig. 3-18)  
Fig. 3-15  
Air-intake grille  
Ceiling panel  
Removing the corner cover  
1
1
a) Slide the corner cover to the direction shown  
1
by the arrow  
(Fig. 3-18).  
to remove the corner cover.  
2
Air-intake grille hinge  
Fig. 3-16  
Fig. 3-17  
Ceiling panel  
Corner cover  
1
Push  
Strap  
Corner cover  
Fig. 3-18  
27  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 28  
Inter-unit control wiring  
3-6-2. Installing the Ceiling Panel  
After completing the wiring process, install the  
supplied wiring cover before installing the panel.  
It is not possible to install the wiring cover after  
installing the panel.  
X
The power must be turned ON in order to change the  
flap angle. (Do not attempt to move the flap by hand.  
Doing so may damage the flap.)  
Screw (supplied)  
Wiring cover (supplied)  
Power supply outlet  
M4-8 or 5/32" – 5/16"  
(1) Insert the temporary fasteners (stainless steel) on  
the inside of the ceiling panel into the square holes  
on the unit to temporarily fasten the ceiling panel in  
place. (Fig. 3-20-1)  
Fig. 3-19-1  
Fig. 3-19-2  
Square hole in unit  
G The ceiling panel must be installed in the correct  
direction relative to the unit. Align the REF. PIPE  
and DRAIN marks on the ceiling panel corner with  
the correct positions on the unit.  
Push when  
Temporary  
fastener  
you remove  
Temporary  
fastener  
G To remove the ceiling panel, support the ceiling  
panel while pressing the temporary fasteners toward  
the outside. (Fig. 3-20-1)  
Fig. 3-20-1  
Drain tubing corner  
Refrigerant tubing  
corner  
(2) Align the panel installation holes and the unit screw  
holes.  
(3) Tighten the supplied washer head screws at the  
4 panel installation locations so that the panel is  
attached tightly to the unit. (Fig. 3-20-2)  
After completing the  
wiring process, install  
the supplied wiring cover  
before installing the panel.  
It is not possible to install  
the wiring cover after  
installing the panel.  
(4) Check that the panel is attached tightly to the  
ceiling.  
Celling panel  
G At this time, make sure that there are no gaps  
between the unit and the ceiling panel, or between  
the ceiling panel and the ceiling surface. (Fig. 3-21)  
G If there is a gap between the panel and the ceiling,  
leave the ceiling panel attached and make fine  
adjustments to the installation height of the unit to  
eliminate the gap with the ceiling. (Fig. 3-21)  
DRAIN mark  
Panel installation hole  
(4 locations)  
REF,PIPE  
mark  
Washer head  
screws  
Fig. 3-20-2  
Insert a wrench  
or other tool into  
the corner cover  
installation hole  
and make fine  
adjustments to  
the unit nut.  
Do not allow  
gaps  
Main unit  
Ceiling panel  
Ceiling surface  
CAUTION  
Fig. 3-21  
Fig. 3-22  
The height of the unit can be adjusted from the  
ceiling panel corner hole, with the ceiling panel  
attached, to an extent that does not affect the  
unit levelness, the drain hose, or other elements.  
G If the screws are not sufficiently tight-  
ened, trouble such as that shown in  
the figure below may occur. Be sure  
to tighten the screws securely.  
G If a gap remains between the ceiling  
surface and the ceiling panel even  
after the screws are tightened,  
adjust the height of the unit again.  
Air leakage  
Air leakage from  
ceiling surface  
Staining  
Adjust so that there are no gaps.  
Condensation, water leakage  
Fig. 3-23  
28  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 29  
3-6-3. Wiring the Ceiling Panel  
(Direction that the unit faces has been changed to  
facilitate explanation.)  
(1) Open the cover of the electrical component box.  
Electrical component  
box cover  
(2) Connect the 7P wiring connector (red) from the  
ceiling panel to the connector in the unit electrical  
component box.  
X
Ceiling panel  
wiring connector  
G If the connectors are not connected, the Auto flap will  
not operate. Be sure to connect them securely.  
G Check that the wiring connector is not caught  
between the electrical component box and the cover.  
G Check that the wiring connector is not caught  
between the unit and the ceiling panel.  
Screws  
(3 locations)  
Ceiling panel side  
Mains side  
Clamp  
* Pass the wiring connector through the clamp to fasten it in place,  
as shown in the figure.  
3-6-4. How to Attach the Corner & Air-Intake Grille  
Attaching the corner cover and air-intake grille  
Fig. 3-24  
A. Attaching the corner cover  
(1) Check that the safety cord from the corner cover is  
fastened to the ceiling panel pin, as shown in the  
figure.  
Pin  
(2) Use the supplied screws to attach the corner cover  
to the ceiling panel.  
B. Attaching the air-intake grille  
Place the corner cover so that the 3 tabs  
fit into the holes in the ceiling panel.  
Then fasten it in place with the supplied screws.  
G To install the air-intake grille, follow the steps for  
Removing the grille in the reverse order. By rotating  
the air-intake grille, it is possible to attach the grille  
onto the ceiling panel from any of 4 directions.  
Coordinate the directions of the air-intake grilles  
when installing multiple units, and change the  
directions according to customer requests.  
Fig. 3-25  
Hole for ceiling panel hook  
G When attaching the air-intake grille, be careful  
that the flap lead wire does not become caught.  
G Be sure to attach the safety cord that prevents  
the air-intake grille from dropping off to the  
ceiling panel unit as shown in the figure at right.  
G With this ceiling panel, the directions of the air-intake  
grille lattices when installing multiple units, and the  
position of the label showing the company name on  
the corner panel, can be changed according to  
customer requests, as shown in the figure below.  
However, the optional wireless receiver kit can only  
be installed at the refrigerant-tubing corner of the  
ceiling unit.  
Hook that prevents  
the grille from dropping  
Fig. 3-26  
Locations of the air-intake grille catches at  
the time the product is shipped.  
* The grille can be installed with these  
Unit drain hose side  
Unit refrigerant tube side  
catches facing in any of 4 directions.  
Optional wireless receiver kit  
* Can only be installed  
in this position.  
Can be installed rotated 90˚  
Unit electrical component box  
Fig. 3-27  
29  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 30  
3-6-5. Checking After Installation  
G Check that there are no gaps between the unit and the ceiling panel, or between the ceiling panel and the ceiling  
surface. Gaps may cause water leakage and condensation.  
G Check that the wiring is securely connected.  
If it is not securely connected, the auto flap will not operate. (“P09” is displayed on the remote controller.) In addition,  
water leakage and condensation may occur.  
X
3-6-6. When Removing the Ceiling Panel for Servicing  
When removing the ceiling panel for servicing, remove the air-intake grille and air filter, disconnect the wiring connector  
inside the electrical component box, and then remove the 4 mounting screws.  
3-6-7. Adjusting the Auto Flap  
The air-direction louver on the ceiling panel outlet can be adjusted as follows.  
G Adjust the louver to the desired angle using the remote controller. The louver also has an automatic air-sweeping  
mechanism.  
NOTE  
G Never attempt to move the louver by hand.  
G Proper air flow depends on the location of the air conditioner, the layout of the room and furniture, etc. If cooling or  
heating seems inadequate, try changing the direction of the air flow.  
3-7. Special Remarks  
DC Fan Tap Change Procedure  
<Steps> Be sure to turn OFF the power (at mains) before beginning the work below.  
(1) In the table below, check the field-supply parts that will be used. (If this setting is not made, the airflow may  
decrease and condensation may occur.)  
Setting  
Air shield material (for use with 3-direction discharge)*  
(a)  
Air shield material (for use when a discharge duct is connected)*  
(b)  
Air shield material (for use with 2-direction discharge)*  
* Use field-supply air shield material.  
Setting (a): Go to (2).  
Setting (b): Go to (3).  
Indoor unit control PCB  
(2) Setting (a)  
Open the cover of the electrical component box.  
Short the short-circuit pin TP3 (2P, yellow) on the  
indoor unit control PCB.  
* PCB model No.: CR-SXRP56B-B  
(3) Setting (b)  
Open the cover of the electrical component box.  
Short the short-circuit pin TP6 (2P, white) on the  
indoor unit control PCB.  
Fig. 3-28  
30  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 31  
I 1-Way Air Discharge Semi-Concealed Type (A Type)  
29-59/64 (Panel outer dimensions)  
28-47/64 (Ceiling opening dimension)  
25-63/64 (Suspension bolt pitch)  
Unit: in.  
3-8. Suspending the Indoor Unit  
(1-27/64)  
1-27/64  
(1) Follow the diagrams to make the holes in the ceiling.  
(Figs. 3-29 and 3-30)  
(2) Depending on the ceiling type:  
G Insert suspension bolts as shown in Fig. 3-31  
or  
G Use existing ceiling supports or construct a suitable  
support as shown in Fig. 3-32.  
A
G Make sure that the length of suspension bolts from the  
bottom of the unit is 19/32 in. or more. (Fig. 3-33)  
23-5/8  
Fig. 3-29  
Drain pipe connection  
(Be sure to connect the supplied flexible hose.)  
WARNING  
22-3/64  
It is important that you use extreme care in  
supporting the indoor unit from the ceiling. Ensure  
that the ceiling is strong enough to support the  
weight of the unit. Before hanging the unit, test the  
strength of each attached suspension bolt.  
10-1/32  
1-19/64  
5-19/64  
1-49/64  
(3) Calculate the suspension bolt pitch using the full-  
size installation diagram (printed on the package).  
The relationship between the positions of the  
suspension lugs, unit, and ceiling panel is as  
shown in Fig. 3-30.  
Flared refrigerant  
connection outlet  
(liquid tube)  
Flared refrigerant  
connection outlet  
(gas tube)  
Inter-unit  
Control Wiring  
Power supply outlet  
Unit: in.  
Fig. 3-30  
(4) Cut the ceiling material, if necessary.  
(Figs. 3-29 and 3-30)  
Hole-in-anchor  
Hole-in-plug  
If the system requires fresh air to be drawn into the unit,  
cut and remove the insulation (both externally and  
Concrete  
Insert  
A
internally) at the location shown as  
3-35.  
in Figs. 3-34 and  
Suspension bolt  
(M10 or 3/8")  
CAUTION  
Fig. 3-31  
When making the cuts to the insulation, be careful  
not to damage the drain pan.  
31  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 32  
Ceiling tiles  
3-9. Placing the Unit Inside the Ceiling  
Ceiling support  
Be sure to use a level gauge  
CAUTION  
and confirm that the unit is  
level. If it is not level, water  
leakage may occur.  
(1) Use the supplied M5 or 3/16" screws (4) to attach  
the full-size installation diagram to the indoor unit  
suspension lugs, in order to obtain the ceiling  
opening dimensions for suspending the unit.  
Fig. 3-32  
A
Full-scale  
installation diagram  
Caution: Piping and wiring work must be performed  
inside the ceiling after the unit is suspended.  
Therefore if the ceiling is already installed, the  
wiring and piping work should be completed  
up to the connection points prior to  
Suspension  
lug  
suspending the unit.  
over 19/32 in.  
25/32 – 1 in.  
(2) Attach the special washers (supplied) and nuts (field  
supply) to the suspension bolts (4 locations).  
Fig. 3-33  
CAUTION  
For fresh air intake  
3-15/16 hole)  
A
3-5/32  
G Use M10 or 3/8" nuts.  
G The length of the suspension bolts must be such that  
there is a space of at least 19/32 in. below the bottom  
of the suspension lugs, as shown in Fig. 3-33. If the  
length of the suspension bolts is too long, the bolts  
may interfere with the ceiling panel and louver motor,  
preventing their installation.  
Unit: in.  
Fig. 3-34  
(3) Thread the 3 hexagonal nuts and 2 washers (field  
supply) onto each of the 4 suspension bolts as  
shown in Fig. 3-36. Use 1 nut and 1 washer for the  
upper side, and 2 nuts and 1 washer for the lower  
side, so that the unit will not fall off the suspension  
lugs.  
For fresh air intake  
3-15/16 hole)  
6-11/16  
A
(4) Lift up the indoor unit and fit the suspension bolts  
into the notches in the suspension lugs.  
(5) Adjust so that the distance between the bottom of  
the indoor unit suspension lugs and the bottom of  
the ceiling panel is 25/32 – 1 in. Then tighten the  
nuts above and below each suspension lug. The  
full-size installation diagram can be used to help  
adjust the height of the indoor unit.  
Unit: in.  
Fig. 3-35  
Suspension bolt  
Nuts and washers  
Suspension lug  
(Used above and below.)  
Double nuts  
Notch  
over 19/32 in.  
25/32 – 1 in.  
Fig. 3-36  
32  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 33  
2-1/8  
2-1/8  
CAUTION  
G The indoor unit includes a drain pump. Be sure to  
use a level gauge and verify that the unit is level.  
G Before inserting the ceiling material, complete as  
much of the drain piping work and refrigerant  
tubing work as possible.  
Suspension bolts  
Tubing side  
(6) The distance between the unit and the opening of  
the ceiling and the distance between the bottom  
surface of the ceiling and the bottom surface of the  
flange of the unit should follow the dimensions given  
in Figs. 3-37 and 3-38.  
Suspension bolts  
A
Unit: in.  
Fig. 3-37  
Ceiling  
material  
3-10. Installing the Drain Piping  
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for  
the drain and use the supplied drain hose and hose  
band to prevent water leaks.  
Fig. 3-38  
The PVC pipe must be purchased separately. The  
unit’s transparent drain port allows you to check  
drainage. (Fig. 3-39)  
Align the hose band with end of the  
hose, and tighten so that it does not  
contact the bead.  
CAUTION  
Drainage check  
Hard PVC  
section on drain port  
pipe  
Drain hose  
(supplied)  
Hard PVC  
(transparent)  
VP-25  
(not supplied)  
socket VP-25  
G Do not use adhesive at the drain connection port on  
the indoor unit.  
(not supplied)  
G Insert the drain pipe until it contacts the socket, as  
shown in the figure at right, then secure it tightly with  
the hose band.  
PVC adhesive  
Packing (supplied)  
Bead  
G Tighten the hose clamps so their locking nuts face  
upward. (Fig. 3-39)  
Fig. 3-39  
G Do not use the supplied drain hose bent at a 90°  
angle. (The maximum permissible bend is 45°.)  
G Check the drainage at the unit drain port  
(transparent).  
Drain insulator (supplied)  
(2) After checking the drainage, wrap the supplied  
packing and drain pipe insulator around the pipe,  
then secure it with the supplied clamps. (Fig. 3-40)  
Fig. 3-40  
NOTE  
Make sure the drain pipe has a downward gradient  
(1/100 or more) and that there are no water traps.  
33  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 34  
CAUTION  
G Do not install an air bleeder as this may cause water  
to spray from the drain pipe outlet. (Fig. 3-41)  
Air bleed valve  
G In cases where it is necessary to raise the height of  
the drain piping, the drain piping can be raised to a  
maximum height of 33-15/32" above the bottom  
surface of the ceiling. Under no conditions attempt to  
Fig. 3-41  
A
raise it higher than 33-15/32" above the bottom  
surface of the ceiling. Doing so will result in water  
leakage. (Fig. 3-42)  
11-13/16 in. or less  
33-15/32 in. or less  
G Do not use natural drainage.  
0 – 45°  
G Do not install the pipe with an upward gradient from  
the connection port. This will cause the drain water  
to flow backward and leak when the unit is not  
operating. (Fig. 3-43)  
* Length of supplied drain hose = 9-27/32 in.  
Fig. 3-42  
G Do not apply force to the piping on the unit side when  
connecting the drain pipe. The pipe should not be  
allowed to hang unsupported from its connection to  
the unit. Fasten the pipe to a wall, frame, or other  
support as close to the unit as possible. (Fig. 3-44)  
G Provide insulation for any pipes that are run indoors.  
Uphill slope  
Fig. 3-43  
3-11. Checking the Drainage  
Support  
bracket  
After wiring and drain piping are completed, use the  
following procedure to check that the water will drain  
smoothly. For this, prepare a bucket and wiping cloth to  
catch and wipe up spilled water.  
(1) Connect power to the power terminal board (R, S  
terminals) inside the electrical component box.  
Fig. 3-44  
(2) Pour about 0.2 gal of water into the drain pan using a  
siphon pump through the air outlet grille. (Fig. 3-45)  
Drainage check  
(3) Short the check pin (CHK) on the indoor control board  
and operate the drain pump. Check the water flow  
through the transparent drain pipe and see if there is any  
leakage.  
Drain tube  
connection  
(transparent)  
Discharge port  
water (0.2 gal)  
Be careful since the fan will start  
when you short the pin on the indoor  
control board.  
CAUTION  
Fig. 3-45  
(4) When the drainage check is complete, open the check  
pin (CHK) and remount the insulator.  
The bottom drain port is for use only  
CAUTION  
during test runs and servicing  
inspections. Do not connect the drain  
pipe to the bottom drain port.  
34  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 35  
Refrigerant tubing joint  
(gas tube)  
Drain pipe connection  
(Be sure to connect the  
supplied flexible hose.)  
3-12. Electrical Power Wiring  
(1) Wiring connections  
Refrigerant tubing joint  
(liquid tube)  
The power inlet is on the side of the indoor unit where the  
refrigerant tubing is located. The electrical component box  
is on the lower air intake surface of the indoor unit.  
(Fig. 3-46)  
Inter-unit Control Wiring  
Power supply outlet  
(2) Wiring  
A
WARNING  
Fig. 3-46  
G Route the power wiring into the indoor unit through the power inlet on the side of the unit. At this time, be  
sure that the wiring passes through the power inlet in the unit power section. If the wiring does not pass  
through this inlet, it may become pinched by the ceiling panel, and may result in fire.  
G Pass the wiring through the power inlet on the electrical component box and connect it to the terminal plate.  
Then fasten the wiring in place with the clamp.  
3-13. How to Install the Ceiling Panel  
Component Parts  
Part name  
Quantity  
Appearance  
Part name  
Quantity  
Appearance  
M5 × 40  
Washer-head  
screw  
or  
4
5/16" × 9/16"  
Ceiling panel  
1
4 × 12 or 5/32" × 15/32"  
For fastening  
Screw  
2
side panel  
3-13-1. Before Installing the Ceiling Panel  
Checking the position of the indoor unit  
Be sure that this distance is within the range of 25/32 – 1 in.  
If it is not within this range, malfunction or other problems may result.  
(1) Check that the dimensions of the ceiling opening are  
the following:  
28-47/64" × 23-17/64"  
Indoor unit  
* For details, refer to the installation manual that was  
supplied with the indoor unit.  
Ceiling opening dimension  
Ceiling surface  
(2) Check that the positions of the ceiling surface and  
indoor unit are as shown in Fig. 3-47. If the positions  
of the ceiling surface and indoor unit are not correct,  
problems such as air leakage, water leakage, and flap  
operation trouble may occur.  
Fig. 3-47  
G Do not rest the panel facing downwards, lean up against  
a wall, or leave it sitting on top of a protruding object.  
Doing so may scratch the panel surface.  
G Do not apply excessive force to the flap.  
(Doing so may damage the flap.)  
Flap  
Fig. 3-48  
35  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 36  
Removing the intake grille  
Screw  
Slide the intake grille hooks (2  
locations) in the direction of the  
arrow to open the intake grille.  
(fig. 3-49a)  
Screw  
Hook  
When the intake grille is open,  
press a flathead screwdriver against  
the rear tabs (2 locations) and pull  
out the intake grille. (Fig. 3-49b)  
A
Fig. 3-49a  
Intake grille  
Removing the side panel  
Grasp the finger grip on the side  
panel and slide the panel in the  
direction of arrow  
panel.  
to remove the  
1
(There are 2 panels: 1 each on the  
left and right sides.) (Fig. 3-51)  
Hinge  
Fig. 3-49b  
Press on the tabs with a flathead (minus)  
screwdriver while pulling out the intake grille.  
Tab  
Fig. 3-50  
Slide  
1
Side panel  
Fig. 3-51  
3-13-2. Installing the ceiling panel  
Hook receiver Press to remove.  
(1) Fasten the hooks on both sides of the ceiling panel  
to the indoor unit. The hooks on one side (2  
locations) are stationary, while the hook on the other  
side is moveable. (Fig. 3-52)  
Stationary hook  
(2) Angle the panel somewhat and fasten the stationary  
hook into the fastener on the side of the unit.  
Moveable hook  
Fig. 3-53  
(3) After verifying that the hook is fastened, press the  
other end up until the ceiling panel is level. Then  
press upwards until the moveable hook is fastened  
into the fastener on the unit.  
(4) Verify that the hooks on both sides of the ceiling  
panel are securely fastened to the unit. If the hooks  
are not securely fastened, the panel may fall. At this  
point, the panel is now provisionally fastened to the  
unit.  
Moveable hook  
Fig. 3-52  
G When removing the panel, press the movable hook  
toward the inside while supporting the panel.  
(Fig. 3-53)  
36  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 37  
(5) Align the installation holes on the panel with the  
bolt holes on the unit.  
Indoor unit  
(6) Insert the supplied washer head bolts into the 4  
panel installation holes, and tighten until the panel  
is securely fastened against the unit. (Fig. 3-54)  
(7) Verify that the panel is securely fastened against  
the unit.  
G At this time, make sure that there is no gap  
between the indoor unit and the ceiling panel, or  
between the ceiling panel and the ceiling surface.  
(Fig. 3-55)  
A
G If there is a gap between the ceiling panel and the  
ceiling, leave the panel attached and adjust the  
installation height of the indoor unit upwards until  
the gap with the ceiling is eliminated. (Fig. 3-56)  
Ceiling panel  
G If the adjustment is small enough that it will not  
affect the levelness of the indoor unit or the drain  
piping, then the unit height can be adjusted from  
the side panel installation holes, with the ceiling  
panel still attached.  
Washer-head screw  
Fig. 3-54  
Must be no gap.  
Insert a wrench or other  
standard tool into the side  
panel installation holes  
and make fine adjustments  
to the indoor unit nuts.  
Indoor unit  
Ceiling surface  
Ceiling panel  
Fig. 3-55  
Fig. 3-56  
CAUTION  
• If the screws are not fully tightened,  
problems such as those shown below  
may occur. Be sure to tighten the  
screws securely.  
• If there is a gap between the ceiling  
surface and the ceiling panel even  
when the screws are fully tightened,  
readjust the height of the indoor unit.  
(Fig. 3-56)  
Air leakage  
Ceiling panel  
air leakage  
Stains  
Adjust so that there is no gap.  
Condensation and water leakage  
37  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 38  
3-13-3. Wiring the ceiling panel  
(1) Loosen the 2 screws on the electrical component  
box lid, and remove the lid. (Fig. 3-57)  
(2) Fasten the wiring connector (7P, red) which comes  
out from the ceiling panel using the lead wire clamps  
(2 locations) on the unit. Then connect it to the  
connector (7P, red) inside the indoor unit electrical  
component box. (Fig. 3-58)  
G If the connector is not connected, “P09” is displayed  
A
Screw  
on the remote controller, and the automatic flap will  
Electrical compornent  
box cover  
not operate. Be sure to securely connect the connec-  
tor.  
Fig. 3-57  
G Check that the wiring connector is not pinched  
between the electrical component box and the lid.  
G Check that the wiring connector is not pinched  
between the indoor unit and the ceiling panel.  
3-13-4. Installing the side panel and intake grille  
A. Installing the side panel  
(1) Grasp the side panel finger grip and slide the panel  
in the direction of the arrow to install the side panel.  
(Fig. 3-59)  
Inter-unit control wiring  
Power supply outlet  
(2) Fasten the side panel onto the ceiling panel using  
Electrical compornent box  
the supplied screws (4 × 12 or 5/32" × 15/32").  
Indoor unit connector  
B. Installing the intake grille  
Fig. 3-58  
G To install the intake grille, follow the procedure for  
removing it in the reverse order. (Fig. 3-60)  
G When installing the intake grille, be careful that the  
flap lead wire does not become pinched. (Fig. 3-60)  
Fasten with screws  
(4 × 12 or 5/32" × 15/32")  
Tabs  
Tab  
Slide  
3-13-5. Other  
A. Check after installation  
G Check again that there is no gap between the indoor  
unit and the ceiling panel, or between the ceiling  
panel and the ceiling surface.  
Slide the side panel so that the side panel tabs are fastened to  
the ceiling panel. Then fasten in place with the supplied screws  
(4 × 12 or 5/32" × 15/32").  
* If there is a gap, then water leakage and condensa-  
tion may occur.  
Fig. 3-59  
G Check that the wiring connections are secure.  
* If the wiring is not connected, the automatic flap will  
not operate. (“P09” is displayed on the remote  
controller.) In addition, water leakage,  
Screw  
Screw  
condensation, and other problems may occur.  
B. If a wireless remote controller is used  
G For details concerning the installation procedure,  
refer to the installation manual which was supplied  
with the optional wireless remote controller and  
indoor unit internal receiver.  
Fig. 3-60  
38  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 39  
I Concealed Duct Type (U Type)  
3-14. Required Minimum Space for  
A (Suspension bolt pitch)  
Electrical  
component box  
Installation and Service  
G This air conditioner is usually installed above the ceiling so that the  
indoor unit and ducts are not visible. Only the air intake and air outlet  
ports are visible from below.  
Inspection  
access  
17-23/32  
min.  
9-27/32  
Indoor unit  
17-23/32  
G The minimum space for installation and service is shown in  
Fig. 3-61 and Table 3-3.  
Refrigerant  
tubing  
min. 25-19/32  
G It is recommended that space is provided (17-23/32 × 17-23/32 in.)  
for checking and servicing the electrical system.  
G Fig. 3-62 and Table 3-4 show the detailed dimensions of the indoor  
unit.  
Air outlet duct flange  
Unit: in.  
Fig. 3-61  
Table 3-3  
Unit: in. (mm)  
U
Type  
7, 12, 18  
24  
36  
A (Length)  
30-23/32 (780) 42-17/32 (1,080) 61-13/32 (1,560)  
Number of duct flanges  
2
3
4
Table 3-4  
Unit: in.  
Dimension  
No. of holes  
A
B
C
D
E
F
G
H
I
J
K
Type  
L
M
23-5/8  
7, 12, 18  
24  
26-1/16  
37-7/8  
27-9/16 30-23/32 11-13/32 10-5/16 26-25/32 28-5/32 7-3/32  
39-3/8 42-17/32 11-13/32 10-23/32 38-19/32 39-31/32 5-1/8  
58-9/32 61-13/32 13-3/16 12-7/32 57-15/32 58-27/32 5-1/8  
13-3/8  
8
12  
(7-7/8 × 3)  
35-7/16  
(7-3/32 × 5)  
54-11/32  
(9-1/16 × 6)  
9-21/32  
(9-21/32 × 1)  
19-9/32  
(9-21/32 × 2)  
9-27/32  
12  
16  
16  
36  
56-25/32  
9-7/16  
18  
Refrigerant tubing joint (liquid tube)  
Refrigerant tubing joint (gas tube)  
Upper drain port (O.D. 1-1/4 in.)  
Bottom drain port (O.D. 1-1/32 in.)  
Suspension lug  
13/32  
13/32  
I
L-ø1/4  
(Hole)  
11  
J
K
J
I
Power supply outlet (2-ø1-3/16 hole)  
Fresh air intake port (ø5-29/32 hole)  
3/4  
3/4  
A (O.D.)  
Flange for the flexible air outlet duct (ø7-7/8 hole)  
Tube cover  
H (Duct suspension bolt pitch)  
G (Ceiling opening dimension)  
4-ø15/32  
(Hole)  
Electrical component box  
Flange for the air intake duct  
(Option or field supply)  
Inter-unit control wiring  
12-7/32  
31/32  
8-9/32  
31/32  
6-7/8  
1-7/32  
1-7/32  
3-17/32  
B
18-ø1/8  
(Hole)  
10  
9
Inspection access  
(17-23/32  
17-23/32)  
(Field supply)  
1-9/16  
C
1-3/8  
(5-29/32)  
D
(Suspension bolt pitch)  
5-1/8  
11-7/32  
2-3/4  
2-15/16  
2-9/16  
E
E
E
F
Inspection access panel  
Ceiling  
Unit: in.  
Fig. 3-62  
39  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 40  
3-15. Suspending the Indoor Unit  
Depending on the ceiling type:  
Hole-in-anchor  
Hole-in-plug  
Concrete  
Insert  
• Insert suspension bolts as shown in Fig. 3-63  
or  
• Use existing ceiling supports or construct a suitable support as  
shown in Fig. 3-64.  
Suspension bolt (M10 or 3/8")  
(field supply)  
It is important that you use extreme care  
WARNING  
Fig. 3-63  
in supporting the indoor unit inside the  
ceiling. Ensure that the ceiling is strong  
enough to support the weight of the unit.  
Before hanging the unit, test the strength  
Ceiling tiles  
Ceiling support  
of each attached suspension bolt.  
U
(1) When placing the unit inside the ceiling, determine the pitch of  
the suspension bolts referring to the dimensional data on the  
previous page. (Fig. 3-61 and Table 3-3)  
Tubing must be laid and connected inside the ceiling when  
suspending the unit. If the ceiling is already constructed, lay the  
tubing into position for connection to the unit before placing the  
unit inside the ceiling.  
Fig. 3-64  
Suspension bolt  
(2) Screw in the suspension bolts allowing them to protrude from  
the ceiling as shown in Fig. 3-63. (Cut the ceiling material, if  
necessary.)  
Suspension lug  
Nuts and washers  
(use for upper and lower)  
(3) Thread the 3 hexagonal nuts and 2 washers (field supply) onto  
each of the 4 suspension bolts as shown in Figs. 3-65 and 3-66.  
Use 1 nut and 1 washer for the upper part, and 2 nuts and 1  
washer for the lower part, so that the unit will not fall off the  
suspension lugs.  
Notch  
Double nuts  
Fig. 3-65  
Suspension bolt  
Hexagonal nut  
Double nuts  
G Fig. 3-67 shows an example of installation.  
Bolt anchor  
Fig. 3-66  
Air outlet duct  
Suspension bolt  
Air-intake duct  
Air-outlet grille  
Ceiling material  
Indoor unit  
Air-intake grille  
Fig. 3-67  
40  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 41  
3-16. Installing the Drain Piping  
Align the hose band with end of the  
hose, and tighten so that it does not  
contact the bead.  
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the drain  
and use the supplied hose band to  
Drainage check  
Hard PVC  
pipe  
VP-25  
(not supplied)  
prevent water leaks.  
section on drain port  
(transparent)  
Drain hose  
(supplied)  
Hard PVC  
The PVC pipe must be purchased separately.  
The transparent drain part on the unit allows you to check  
drainage. (Fig. 3-68)  
socket VP-25  
(not supplied)  
CAUTION  
PVC adhesive  
Packing (supplied)  
Bead  
G Do not use adhesive at the drain connection port on the  
indoor unit.  
Fig. 3-68  
G Insert the drain pipe until it contacts the socket, as shown in  
the figure at right, then secure it tightly with the hose band.  
G Do not use the supplied drain hose bent at a 90° angle.  
(The maximum permissible bend is 45°.)  
Drain insulator (supplied)  
U
G Tighten the hose clamps so their locking nuts face upward.  
(FIg. 3-68)  
Vinyl clamps  
(2) After connecting the drain piping securely, wrap the supplied  
packing and drain pipe insulator around the pipe, then secure it  
with the supplied vinyl clamps. (Fig. 3-69)  
Fig. 3-69  
Air bleeder  
NOTE  
Make sure the drain pipe has a downward gradient (1/100 or more)  
and that there are no water traps.  
Prohibited  
Fig. 3-70  
G Do not install an air bleeder as this may  
CAUTION  
cause water to spray from the drain pipe  
outlet. (Fig. 3-70)  
11-13/16" or less  
19-11/16" or less  
Good  
G If it is necessary to increase the height of the drain pipe, the  
section directly after the connection port can be raised a  
maximum of 19-11/16". Do not raise it any higher than  
19-11/16", as this could result in water leaks. (Fig. 3-71)  
G Do not install the pipe with an upward gradient from the connec-  
tion port. This will cause the drain water to flow backward and leak  
when the unit is not operating. (Fig. 3-72)  
Fig. 3-71  
Upward gradient  
G Do not apply force to the piping on the unit side when connecting  
the drain pipe. The pipe should not be allowed to hang unsupport-  
ed from its connection to the unit. Fasten the pipe to a wall, frame,  
or other support as close to the unit as possible. (Fig. 3-73)  
Prohibited  
Fig. 3-72  
3-17. Checking the Drainage  
After wiring and drain piping are completed, use the following proce-  
dure to check that the water will drain smoothly. For this, prepare a  
bucket and wiping cloth to catch and wipe up spilled water.  
Support pieces  
(1) Connect power to the power terminal board (R, S terminals)  
inside the electrical component box.  
(2) Remove the tube cover and through the opening, slowly pour  
about 0.3 gal of water into the drain pan to check drainage.  
Fig. 3-73  
(3) Short the check pin (CHK) on the indoor control board and oper-  
ate the drain pump. Check the water flow through the transparent  
drain port and see if there is any leakage.  
41  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 42  
Power supply outlet  
Be careful since the fan will start when you  
short the pin on the indoor control board.  
CAUTION  
Inter-unit control wiring  
(4) When the check of drainage is complete, open the check pin (CHK)  
and remount the insulator and drain cap onto the drain inspection port.  
3-18. Increasing the Fan Speed  
If external static pressure is too great (due to long extension of ducts, for  
example), the air flow volume may drop too low at each air outlet. This problem  
may be solved by increasing the fan speed using the following procedure:  
(1) Remove 4 screws on the electrical component box and  
remove the cover plate.  
(2) Disconnect the fan motor sockets in the box.  
U
Fig. 3-74  
(3) Take out the booster cable (sockets at both ends)  
clamped in the box.  
Indoor Fan Performance  
(4) Securely connect the booster cable sockets between the  
disconnected fan motor sockets in step 2 as shown in  
Fig. 3-75.  
7, 12 Type  
18 Type  
(
10-3 psi)  
21.8  
(
10-3 psi)  
21.8  
(in.Aq)  
0.6  
(in.Aq)  
0.6  
(5) Place the cable neatly in the box and reinstall the cover  
plate.  
0.4  
0.2  
0
0.4  
14.5  
7.3  
0
14.5  
7.3  
0
Electrical component box  
Booster cable  
HT  
Fan  
Booster cable  
motor  
0.2  
0
HT  
H
H
Fan motor socket  
M
M
L
L
(At shipment)  
(Booster cable installed)  
Fig. 3-75  
353  
530  
177  
353  
3
3
Air Flow (ft. /minute)  
Air Flow (ft. /minute)  
How to read the diagram  
The vertical axis is the external static pressure (psi,  
in.Aq) while the horizontal axis represents the air flow  
(ft. /minute). The characteristic curves for “HT,” H,M”  
36 Type  
(in.Aq)  
(
10-3 psi)  
24 Type  
(
10-3 psi)  
21.8  
(in.Aq)  
3
0.6  
0.6  
21.8  
and “Lfan speed control are shown. The nameplate  
values are shown based on the “H” air flow. For the 24  
3
type, the air flow is 635 ft. /minute, while the external  
HT  
0.4  
0.2  
0
0.4  
0.2  
0
14.5  
7.3  
0
14.5  
7.3  
0
-3  
static pressure is 7.1 × 10 psi at “H” position. If exter-  
HT  
nal static pressure is too great (due to long extension of  
ducts, for example), the air flow volume may drop too  
low at each air outlet. This problem may be solved by  
increasing the fan speed as explained above.  
H
H
M
M
L
L
353  
706  
706  
1059  
3
3
Air Flow (ft. /minute)  
Air Flow (ft. /minute)  
HT : Using the booster cable  
NOTE  
H : At shipment  
Fig. 3-76  
42  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 43  
I Concealed Duct High-Static Pressure Type (D Type)  
Min. 23-5/8  
(Space for service)  
3-19. Required Minimum Space  
19-11/16  
11-27/64  
5-1/8  
for Installation and Service  
G This air conditioner is usually installed above the ceiling  
so that the indoor unit and ducts are not visible. Only the  
air intake and air outlet ports are visible from below.  
G The minimum space for installation and service is shown  
in Fig. 3-77.  
37  
Suspension  
bolt pitch  
38-37/64  
Suspension  
Air suction side  
bolt pitch  
G It is recommended that space be provided (23-5/8" ×  
23-5/8") for checking and servicing the electrical system.  
G Fig. 3-78 and Table 3-3 show the detailed dimensions of  
the indoor unit.  
Refrigerant tubing  
Electrical  
component  
box  
Inspection access  
(23-5/8" × 23-5/8")  
Min. 23-5/8  
Space for  
service  
D
Min. 22-53/64  
Drain pan  
Ceiling face  
Min. 5-1/8  
Unit: in.  
Fig. 3-77  
37  
31-7/32  
7 × 3-15/16 = 27-9/16  
22 - ø1/8  
25/32  
3-35/64  
2-5/32  
1-37/64  
(Hole for full  
circumference)  
2-23/64  
1-57/64  
Table 3-5  
Unit: in.  
Length  
A
B
C
Type  
Electrical component box  
36  
16-17/32 15-35/64 2-43/64  
48  
17-23/32 16-47/64 3-55/64  
4-ø20 hole for  
suspension bolt  
1-13/16  
4 × 3-15/16  
= 15-3/4  
Refrigerant liquid line (ø3/8 or ø1/4)  
Refrigerant gas line (ø3/4 or ø5/8)  
Power supply outlet  
16 - ø1/8  
(Hole for full  
19-11/16  
circumference)  
Drain connection (25A, O.D. 1-1/4")  
Duct connection for suction  
Duct connection for discharge  
Inter-unit control wiring  
19/32 38-37/64 (Suspension bolt pitch) 19/32  
24-13/32  
19-11/16  
39-49/64  
2-3/4  
1-3/8  
37  
1-3/8  
25/64  
25/64  
Drain pan  
Unit: in.  
Fig. 3-78  
43  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 44  
3-20. Suspending the Indoor Unit  
Depending on the ceiling type:  
Hole-in-anchor  
Hole-in-plug  
Concrete  
Insert  
G Insert suspension bolts as shown in Fig. 3-79  
or  
G Use existing ceiling supports or construct a suitable support as  
shown in Fig. 3-80.  
Suspension bolt (M10 or 3/8")  
(field supply)  
It is important that you use extreme care  
WARNING  
Fig. 3-79  
in supporting the indoor unit inside the  
ceiling. Ensure that the ceiling is strong  
enough to suport the weight of the unit.  
Before hanging the unit, test the strength  
of each attached suspension bolt.  
Ceiling tiles  
Ceiling support  
(1) When placing the unit inside the ceiling, determine the pitch  
of the suspension bolts referring to the dimensional data given  
previously. (Figs. 3-77 and 3-78)  
D
Tubing must be laid and connected inside the ceiling when  
suspending the unit. If the ceiling is already constructed, lay  
the tubing into position for connection to the unit before placing  
the unit inside the ceiling.  
Fig. 3-80  
Suspension bolt  
Hexagonal nuts  
(2) Screw in the suspension bolts allowing them to protrude from  
the ceiling as shown in Fig. 3-79. (Cut the ceiling material, if  
necessary.)  
and washers  
(2 sets)  
(3) Suspend and fix the indoor unit using the 2 hexagonal nuts  
(field supply) and special washers (supplied with the unit) as  
shown in Fig. 3-81.  
Fig. 3-81  
Air-outlet grille  
Air-intake grille  
Fig. 3-82  
44  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 45  
3-21. Installing the Drain Piping  
Sealing tape  
(1) Prepare standard hard PVC pipe (O.D. 1-1/4") for the  
drain and use the supplied drain socket to prevent water  
leaks. The PVC pipe must be purchased separately.  
When doing this, apply adhesive for the PVC pipe at the  
connection point.  
Drain pan  
Drain joint  
(supplied)  
(2) If connecting a drain joint (supplied) to the threaded  
drain port, first wrap the drain port threads with sealing  
tape, then connect the joint. (Fig. 3-83)  
Drain opening  
(25A or 1-11/32" male screw)  
Fig. 3-83  
(3) After connecting the drain pipe securely, wrap insulator  
(field supply) around the pipe.  
Downward gradient  
(4) Ensure the drain pipe has a downward gradient (1/100  
or more) and prepare traps as indicated in Fig. 3-84.  
Min. 1/100  
(5) Also, in another part of the pipe arrangement, prepare  
traps with an inspection plug to clean dust or debris that  
may cause leaking of water. (Fig. 3-85)  
Good  
(6) After connecting the drain piping, slowly pour water into  
the drain pan to check that the water drains smoothly.  
D
3-22. Caution for Ducting Work  
Not good  
G This unit has high static pressure (applicable external static  
-3  
-3  
×
×
pressure Max. 24.2 10 to 31.3 10 psi (0.68 – 0.88  
in.Aq). In the case of small pressure resistance (for  
instance, a short duct), install a damper for adjusting air  
flow volume as air flow volume / air flow noise increases.  
G If the air conditioner is to be installed in a room such as  
an office or meeting room which needs a low sound  
level, provide a supply and return noise absorption  
chamber with an acoustic liner.  
Fig. 3-84  
Min. 1-31/32 in.  
G Include an air filter (field supply) at the return duct.  
Inspection plug  
3-23. Indoor Fan Performance  
How to Read the Diagram  
Fig. 3-85  
36 Type  
48 Type  
(
10-3 psi)  
(in.Aq)  
(
10-3 psi)  
36.3  
(in.Aq)  
The vertical axis is the External Static Pressure  
(psi, in.Aq) while the horizontal axis represents  
36.3  
29.0  
21.8  
1.0  
1.0  
3
the Air Flow (ft. /minute). The characteristic  
29.0  
curve for the “H,Med,and “Lo” fan speed  
control.  
0.8  
0.6  
0.4  
0.8  
0.6  
0.4  
The nameplate values are shown based on the  
“H” air flow. Therefore in the case of 36 Type,  
21.8  
3
the flow is 1059 ft. /minute, while the External  
Static Pressure is 0.72 in.Aq at “H” position. If  
the external static pressure is too great (due to  
long extension of duct, for example), the air flow  
volume may drop too low at each air outlet.  
14.5  
7.3  
0
14.5  
7.3  
0
0.2  
0
0.2  
0
883  
1059  
1236  
1059  
1236  
1412  
3
3
Air Flow (ft. /minute)  
Air Flow (ft. /minute)  
NOTE  
H : At shipment  
Fig. 3-86  
45  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 46  
I Ceiling-Mounted Type (T Type)  
3-24. Required Minimum Space for Installation and Service  
(1) Dimensions of suspension bolt pitch and unit  
B
C
Unit: in.  
Table 3-6  
Dimension  
A
B
C
Type  
Air intake  
12, 18  
24  
33-21/32 35-53/64 8-17/64  
44-19/64 46-29/64 8-17/64  
Ceiling side  
A
1-5/64  
1-5/64  
Air outlet  
Unit: in.  
(Suspension bolt pitch)  
Fig. 3-87  
(2) Refrigerant tubing • drain hose position  
2-21/64  
2-61/64  
3-61/64  
3-13/16  
Rear (figure shows view from front)  
Left side  
Right side  
8-1/2  
(Liquid tubing •  
Gas tubing)  
9/64  
Liquid  
tubing  
2-23/64  
T
Gas tubing  
3-5/16  
6-11/32  
9-7/8  
9-7/8  
5-3/4  
Left drain position  
Closed with rubber stopper at time of shipment.  
Right drain position  
Unit: in.  
Fig. 3-88  
(3) Unit opening position (Refrigerant tubing • drain hose • power inlet port • remote controller wiring inlet port)  
Rear outlet port  
Inter-unit control wiring  
10-5/16  
4-59/64  
(ø1-3/16", knock-out, use rubber grommet)  
2-53/64  
Right-side drain  
hose outlet port  
Left-side drain hose  
outlet port  
Outside air intake duct connection port  
*1  
(ø3-15/16", knock-out)  
Power supply outlet  
(ø1-3/16", knock-out)  
Rear tubing hole  
Left-side drain  
hose outlet port  
3-5/16  
Side panel  
Position of plate  
inside side panel  
*1  
13-21/32  
Unit: in.  
Side panel  
*1 Use a compass saw, jig saw or similar tool and cut along the indented portion of the side panel.  
Fig. 3-89  
46  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 47  
(4) Wall and ceiling side opening position  
Figure shows view from front  
Figure shows view from top  
Wall  
Ceiling  
ø3-15/16 ceiling opening  
ø3-15/16 wall side opening  
3-35/64  
5-5/16  
ø3-15/16 wall side opening  
ø3-15/16 ceiling opening  
4-59/64  
(for left-side drain hose)  
* If the optional drain up kit is installed, create a ø3-15/16" hole along the dotted line (part marked with * in figure).  
Fig. 3-90  
3-25. Suspending the Indoor Unit  
Ceiling  
(1) Place the full-scale diagram (supplied) on the ceiling  
at the spot where you want to install the indoor unit.  
Wall  
Full-scale  
installation diagram  
Use a pencil to mark the drill holes. (Fig. 3-91).  
NOTE  
Fig. 3-91  
Since the diagram is made of paper, it may shrink or  
stretch slightly because of high temperature or humidity.  
For this reason, before drilling the holes maintain the  
correct dimensions between the markings.  
Hole-in-anchor  
Hole-in-plug  
Concrete  
Insert  
T
(2) Drill holes at the 4 points indicated on the full-scale  
diagram.  
(3) Depending on the ceiling type:  
Suspension bolt (M10 or 3/8")  
(field supply)  
a) Insert suspension bolts as shown in Fig. 3-92.  
or  
Fig. 3-92  
b) Use existing ceiling supports or construct a  
suitable support as shown in Fig. 3-93.  
Ceiling tiles  
Ceiling support  
It is important that you use  
WARNING  
extreme care in supporting the  
indoor unit from the ceiling.  
Ensure that the ceiling is  
strong enough to support the  
weight of the unit. Before  
hanging the ceiling unit, test  
the strength of each attached  
suspension bolt.  
A
A
Fig. 3-93  
Pull out the  
air-intake grille  
pushing claws  
of the hinges  
(4) Screw in the suspension bolts, allowing them to  
protrude from the ceiling as shown in Figs. 3-92  
and 3-93. The distance of each exposed bolt must  
be of equal length within 1-15/16". (Fig. 3-94)  
Hinge  
Screw  
Latch  
unit  
Ceiling  
surface  
Air-intake grille  
Fixture  
Fig. 3-94  
Fig. 3-95  
47  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 48  
(5) Before suspending the indoor unit, remove the 2 or 3 screws on the  
latch of the air-intake grilles, open the grilles, and remove them by  
pushing the claws of the hinges as shown in Fig. 3-95. Then remove  
both side panels sliding them along the unit toward the front after  
removing the 2 attachment screws. (Fig. 3-96)  
Slide toward  
front side  
(6) Carry out the preparation for suspending the indoor unit. The  
suspension method varies depending on whether there is a suspended  
ceiling or not. (Figs. 3-97 and 3-98)  
Side panel  
(7) Suspend the indoor unit as follows:  
Fig. 3-96  
a) Mount 1 washer and 2 hexagonal nuts on each suspension bolt as  
shown in Fig. 3-99.  
b) Lift the indoor unit, and place it on the washers through the notches,  
in order to fix it in place. (Fig. 3-100)  
c) Tighten the 2 hexagonal nuts on each suspension bolt to suspend  
the indoor unit as shown in Fig. 3-101.  
Suspension bolt  
(field supply)  
Unit  
Ceiling surface  
Washer (supplied)  
Double nut  
(field supply)  
Fixture  
NOTE  
Fig. 3-97  
The ceiling surface is not always level. Please confirm that the indoor unit  
is evenly suspended. For the installation to be correct, leave a clearance of  
about 3/8" between the ceiling panel and the ceiling surface and fill the gap  
with an appropriate insulation or filler material.  
Suspension bolt  
(field supply)  
Washer (field supply)  
Unit  
(8) If the tubing and wiring are to go towards the rear of the unit, make  
T
holes in the wall. (Fig. 3-102)  
Washer (supplied)  
Double nut  
(field supply)  
(9) Measure the thickness of the wall from the inside to the outside and cut  
PVC pipe at a slight angle to fit. Insert the PVC pipe in the wall.  
(Fig. 3-103)  
Fig. 3-98  
Ceiling  
surface  
Washer  
(supplied)  
Nut  
(field supply)  
Suspension bolt  
Fig. 3-99  
Fig. 3-100  
NOTE  
Fig. 3-101  
The hole should be made at a slight downward slant to  
the outside.  
PVC pipe (locally purchased)  
INSIDE  
OUTSIDE  
Wall  
Indoor  
side  
Outdoor  
side  
PVC pipe  
Slight  
angle  
Cut at slight angle  
Fig. 3-102  
Fig. 3-103  
48  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 49  
3-26. Duct for Fresh Air  
Rear outlet port  
There is a duct connection port (knock-out hole) at the right-  
rear of the top panel of the indoor unit for drawing in fresh air.  
If it is necessary to draw in fresh air, remove the cover by  
opening the hole and connecting the duct to the indoor unit  
through the connection port. (Fig. 3-104)  
Inter-unit control wiring  
(ø1-3/16", knock-out, use rubber grommet)  
Outside air intake duct connection port  
3-15/16", knock-out)  
Power supply outlet  
(ø1-3/16", knock-out)  
3-27. Shaping the Tubing  
Rear tubing hole  
G The positions of the refrigerant tubing connections are  
shown in the figure below. (The tubing can be routed in  
3 directions.)  
Left-side drain hose outlet port  
Fig. 3-104  
* When routing the tubing out through the top or right sides,  
knock out the appropriate parts in the top panel and cut  
notches in the side panel as shown in Fig. 3-89.  
* When routing the tubing out through the top, the optional  
L-shape tubing kit is required.  
If the tubing is to be routed out  
together, use a box cutter or simi-  
lar tool to cut out the part of the  
rear cover indicated by the marked  
area in the figure below, to match  
the positions of the tubes. Then  
draw out the tubing.  
T
Rear cover  
Fig. 3-106  
Fig. 3-105  
3-28. Installing the Drain Piping  
G Prepare standard PVC pipe for the drain and connect it to the  
indoor unit drain pipe with the supplied hose clamps to prevent  
water leaks.  
Donward gradient  
Min. 1/100  
(1) Drain hose connection  
G The drain hose is connected below the refrigerant tubing.  
Good  
(2) Installing the drain hose  
G To install the drain hose, first place 1 of the 2 hose bands over the  
unit drain port and the other hose band over the hard PVC pipe  
(not supplied). Then connect both ends of the supplied drain hose.  
G On the unit drain side, grasp the hose band with pliers and insert  
the drain hose all the way to the base.  
Not good  
G If other commercially available hose bands are used, the drain  
hose may become pinched or wrinkled and there is danger of  
water leakage. Therefore be sure to use the supplied hose bands.  
When sliding the hose bands, be careful to avoid scratching the  
drain hose.  
Fig. 3-107  
CAUTION  
G Do not use adhesive when connecting the supplied drain hose to  
the drain port (either on the main unit or the PVC pipe).  
G Wrap the hose with the supplied drain hose insulation and use the  
4 twist ties so that the hose is insulated with no gaps.  
G Connect the drain piping so that it slopes downward from the unit  
to the outside. (Fig. 3-107)  
G Attach so that the hose band fastener is  
on the side of the drain port. (Fig. 3-108)  
G Attach the hose bands so that each is  
approximately 13/64 – 63/64 in. from the  
end of the supplied drain hose.  
49  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 50  
Twist tie  
(4 ties, supplied)  
G Never allow traps to occur in the course of the piping.  
G Insulate any piping inside the room to prevent drip-  
ping.  
Hard PVC pipe  
(equivalent to  
VP-20)  
Drain hose  
insulation  
(supplied)  
Position to  
fasten hose  
bands  
Unit drain port  
(Field supply)  
G After the drain piping, pour water into the drain pan to  
check that the water drains smoothly.  
G If the drain hose is to be raised, use the optional drain  
up kit.  
The drain hose can be raised 23-5/8" above the top of  
the main unit. (For details, refer to the manual of the  
Drain hose  
(supplied)  
13/64  
63/64  
13/64  
63/64  
optional part.)  
Drain port  
5-33/64  
Hose band  
(2 bands, supplied)  
Screwdriver  
* If the drain hose is  
routed through the  
left side, refer to Fig.  
3-105, and follow the  
procedure above to  
Unit drain pan  
Unit: in.  
Fig. 3-108  
Rubber stopper  
Check local electrical codes  
and regulations before wiring.  
Also, check any specified  
instruction or limitations.  
CAUTION  
install the hose. Re-attach the rubber stopper that  
was earlier removed onto the right side.  
The rubber stopper can be inserted easily by using a  
screwdriver or similar tool to press the stopper into  
the drain port on the main unit. Press the stopper into  
the main unit drain port as far as it will go.  
T
How to carry out power supply wiring  
(1) Wiring connection ports  
(2) How to carry out wiring  
The power inlet ports are located at the rear and top.  
The remote controller wiring inlet ports are located at  
the rear and top (for use with the wired remote  
controller).  
For details, refer to Fig. 3-104. For the method used to  
insert the wiring, refer to the figure below. (Fig. 3-109)  
G Open the knock-out hole on the rear or top of the  
main unit. Attach the supplied rubber grommet and  
pull the power wiring into the main unit.  
G Feed the wiring into the wiring inlet port on the  
electrical component box. Connect the wiring to  
the terminal plate and fasten in place with the  
supplied clamp.  
G Perform electrical and grounding work in  
accordance with the package A/C power  
specifications, and following local electrical  
codes and regulations.  
When removing the fastening  
CAUTION  
bracket from the cover of the  
electrical component box, use  
caution to avoid dropping the  
bracket.  
Inter-unit control wiring  
ø1-9/32 knock-out  
Eyelet (supplied)  
Powe supply outlet  
Fig. 3-109  
50  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 51  
I Wall-Mounted Type (K Type)  
3-29. Removing the Rear Panel from the Unit  
(1) Remove the set screws used to fasten the rear panel to the  
indoor unit during transportation.  
Screws used during  
transportation  
(2) Press up on the frame at the 2 locations shown by the arrows  
in the figure at right, and remove the rear panel.  
Press  
NOTE  
Remove the rear panel  
Tubing can be extended in 4 directions as shown in Fig. 3-111.  
Select the direction which will provide the shortest run to the  
outdoor unit.  
Fig. 3-110  
Left-rear tubing  
3-30. Selecting and Making a Hole  
Right-rear  
tubing  
(recommended)  
Left tubing  
(1) Remove the rear panel from the indoor unit and place it on  
the wall at the location selected. Fix the rear panel and hook  
the unit onto it temporarily. Make sure the unit is horizontal  
using a carpenter’s level or tape measure to measure down  
from the ceiling.  
Right tubing  
(2) Determine which notch of the rear panel should be used.  
(Fig. 3-112)  
Fig. 3-111  
(3) Before drilling a hole, check that there are no studs or pipes  
behind the determined location. The above precautions are  
also applicable if tubing goes through the wall in any other  
location.  
Center of left rear  
tubing hole  
Center of right rear  
tubing hole  
(4) Using a sabre saw, key hole saw or hole-cutting drill attach-  
ment, make a hole (dia. 3-5/32") in the wall. (Fig. 3-113)  
K
Tubing hole diameter ø3-5/32  
(5) Measure the thickness of the wall from the inside edge to the  
outside edge and cut the PVC pipe at a slight angle  
Fig. 3-112  
15/64" shorter than the thickness of the wall. (Fig. 3-114)  
Indoor  
side  
Outdoor  
side  
(6) Place the plastic cover over the end of the pipe (for indoor  
side only) and insert in the wall. (Fig. 3-115)  
NOTE  
The hole should be made at a slight downward gradient to the  
outside.  
Fig. 3-113  
PVC pipe (locally purchased)  
Avoid areas where electrical wiring or  
conduits are located.  
CAUTION  
3-31. Installing the Rear Panel onto the Wall  
Confirm that the wall is strong enough to support the unit.  
See either Item a) or b) below depending on the wall type.  
Cut at slight angle  
a) If the Wall is Wooden  
Fig. 3-114  
(1) Attach the rear panel to the wall with the 10 screws provided. (Fig. 3-116)  
If you are not able to line up the holes in  
INSIDE  
OUTSIDE  
Wall  
the rear panel with the beam locations  
marked on the wall, use Rawl plugs or  
toggle bolts to go through the holes on  
the panel or drill 3/16" dia. holes in the  
panel over the stud locations and then  
mount the rear panel.  
Plastic  
cover  
PVC pipe  
Slight  
angle  
Fig. 3-116  
Fig. 3-115  
51  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 52  
(2) Check with a tape measure or carpenter’s level. This is  
important so that the unit is correctly installed. (Fig. 3-117)  
(3) Make sure the panel is flush against the wall. Any space  
between the wall and unit will cause noise and vibration.  
Fig. 3-117  
b) If the Wall is Brick, Concrete or Similar  
Drill 3/16" dia. holes in the wall. Insert Rawl plugs for  
appropriate mounting screws. (Fig. 3-118)  
3/16"  
dia. hole  
3-32. Removing the Grille to Install the Indoor Unit  
In principle, with this model wiring can be completed without  
removing the grille.  
Rawl plug  
However, if it is necessary to change the settings on the PCB,  
follow the procedure below.  
Fig. 3-118  
Removing the grille  
(1) Lift up on both sides of the air-intake grille to open it.  
(Fig. 3-119)  
Intake grille  
(2) Remove the filter. (Fig. 3-119)  
(3) Adjust the flap so that it is horizontal. (Fig. 3-120)  
(4) Open the installation screw covers below the grille  
(3 locations). (Fig. 3-120)  
Filter  
Flap  
(5) Remove the screws. (Fig. 3-120)  
(6) Remove the grille. (Fig. 3-121)  
Attaching the grille  
Open the grille  
Fig. 3-119  
K
(1) Close the flap.  
(2) Keep the grille installation tabs aligned with the top portion of  
the grille, and reinstall the lower portion of the grille.  
Fit the installation tabs into the grooves and press the lower  
portion of the grille back into its original position to install it.  
Installation screw cover  
(3) Press on the installation tabs to completely close the grille.  
Check that the grille and frame are fitted tightly together.  
Fig. 3-120  
3-33. Preparing the Tubing  
(1) Arrangement of tubing by directions  
a) Right or left tubing  
The corner of the right or left frame should be cut with a  
hack saw or similar. (Fig. 3-122)  
Remove the grille  
b) Right-rear or left-rear tubing  
Fig. 3-121  
In this case, the corners of the frame do not need to be  
cut.  
Installation tabs  
(2) Be sure to insulate the part of the drain hose that is  
run indoors, and the refrigerant tubing.  
Frame  
If these are not insulated, condensation may result in  
dripping and damage to walls and furniture.  
The flare nuts on the 24-type (only) are large;  
therefore, use the supplied insulation material.  
Right tubing  
outlet  
Installation tabs  
When left and right side tubing  
Fig. 3-122  
Fig. 3-123  
52  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 53  
(3) To mount the indoor unit on the rear panel.  
1. When installing the indoor unit, position the indoor unit onto the  
installation tabs on the upper part of the rear panel. (Fig. 3-123)  
2. Press on the air outlet to hold it in place, and press the lower  
part of the indoor unit until a “click” sound is heard and the  
indoor unit is securely fastened to the installation tabs on the  
lower side of the rear panel. (Fig. 3-124)  
Press  
Raising the clamp to lift up the indoor unit will facilitate this work.  
(Fig. 3-125)  
Fig. 3-124  
Clamp  
To remove the indoor unit, press up on the 2 locations  
(L marks) on the lower part of the unit frame to disconnect the  
installation tabs. Refer to Section 3-1. “Removing the Rear Panel  
from the Unit” (Fig. 3-110).  
Then lift up the indoor unit to remove it.  
3-34. Shaping the Tubing  
Right-rear tubing  
Fig. 3-125  
Rear panel tab  
(1) Shape the refrigerant tubing so that it can easily go into the hole.  
(Fig. 3-126)  
Insulating  
tape  
Refrigerant  
tubing  
(2) After performing a leak test, wrap both the refrigerant tubing and  
drain hose together with insulating tape.  
The drain hose should be positioned below the refrigerant tubes,  
and should be given sufficient space so that no strong tension is  
applied to it.  
Indoor and  
outdoor unit  
connection wiring  
Plastic cover  
(3) Push the wiring, refrigerant tubing and drain hose through the hole  
in the wall. Adjust the indoor unit so it is securely seated on the  
rear panel.  
K
Fig. 3-126  
Fig. 3-127  
Left or left-rear tubing  
(1) Pass the tubing and drain hose into the rear of the indoor unit.  
Provide sufficient length for the connections to be made.  
Next, bend the tubing with a pipe bender, and connect them.  
Insulation  
(2) After performing a leak test, wrap the refrigerant tubing and drain  
hose together with insulating tape, as shown in the figure at right.  
(Fig. 3-128)  
Refrigerant tubing  
Then fit the tubing into the tubing storage space in the rear of the  
indoor unit and clamp in place.  
Rear panel  
Insulating tape  
(3) Adjust the indoor unit so that it is securely installed onto the rear  
panel.  
Inter-unit wiring  
Drain hose  
3-35. Installing the Drain Hose  
Fig. 3-128  
a) The drain hose should be slanted downward to the  
outside. (Fig. 3-129)  
Indoor unit  
b) Never form a trap in the course of the hose.  
c) If the drain hose will run in the room, insulate the hose* so that  
chilled condensation will not damage furniture or floors.  
* Foamed polyethylene or its equivalent is recommended.  
Slant  
Do not supply power to the unit or operate  
it until all tubing and wiring to the outdoor  
unit are completed.  
WARNING  
Refrigerant  
tubing  
Fig. 3-129  
53  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 54  
3-36. When Using Wireless Remote Controller Instead Of Wired Remote Controller  
When the wireless remote controller is to be used, slide the switch on the indoor unit control PCB.  
• If this setting is not made, an alarm will occur. (The operation lamp on the display blinks.)  
• This setting is not necessary if both the wired remote controller and wireless remote controller are used.  
• The location of the switch varies depending on the type of PCB used. Check the model name before making the  
setting.  
KHX0752 / 0952 / 1252 / 1852  
CR-KR74GXH56A-0  
Slide No. 3 on SW101  
Setting at time of  
from ON OFF.  
factory shipment  
K
KHX2452  
CR-KR254GXH56A-0  
Slide No. 3 on SW101  
Setting at time of  
from ON OFF.  
factory shipment  
54  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 55  
4. HOW TO INSTALL THE OUTDOOR UNIT  
4-1. Transporting  
When transporting the unit, have it delivered as close to the installation site as  
possible without unpacking. Use a hook for suspending the unit. (Fig. 4-1)  
CAUTION  
G When hoisting the outdoor unit, pass ropes or straps under the bottom plate  
as shown in the figure at right. When hoisting, the angle between the rope  
and top panel must be 70° or greater so that the rope does not come into  
contact with the fan guard.  
(Use 2 lengths of rope 25 ft. long or longer.)  
G When passing the ropes through the square holes of the bottom plate:  
Place the rope in the outer edge of the square holes.  
Fig. 4-1  
G Use protective panels or padding at all locations where the rope contacts the  
outer casing or other parts to prevent scratching. In particular, use protective  
material (such as cloth or cardboard) to prevent the edges of the top panel  
from being scratched.  
Plate leg  
Anchor bolts  
Washer  
G Be careful of the fan.  
There is danger of injury if the fan starts to turn during inspection. Be sure to  
turn OFF the remote power switch before beginning inspection.  
Vibration insulator  
1-31/32  
4-2. Installing the Outdoor Unit  
Base  
(3-15/16)  
(1) Use anchor bolts (M12 or 15/32") or similar to securely anchor the unit in  
place. (Fig. 4-2)  
Unit: in.  
The vibration insulator, base, or platform must  
be large enough to bear the full surface of the  
base plate legs.  
(2) Be sure the rubber vibration insulator and platform extend to the inside of the  
legs. In addition, the washers used to anchor the unit from the top must be  
larger than the installation anchor holes. (Figs. 4-2 and 4-3)  
Fig. 4-2  
(Positions where anchor bolts are fastened)  
Installation anchor hole (4 – 19/32 × 25/32 oval holes)  
(Detailed view of legs)  
Unit: in.  
4 – 19/32 25/32 hole  
1-33/64  
31-7/64 (Installation hole pitch)  
Fig. 4-3  
35-3/64 (Ceiling panel dimensions)  
74-1/64 (Ceiling panel dimensions)  
35-3/64 (Ceiling panel dimensions)  
35-3/64 (Ceiling panel dimensions)  
31-7/64 (Installation hole pitch)  
31-7/64 (Installation hole pitch)  
70-5/64 (Installation hole pitch)  
Unit: in.  
Top view  
Fig. 4-4  
55  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 56  
4-3. Routing the Tubing  
G The tubing can be routed out either from the front or from the bottom. (Fig. 4-6)  
G The connecting valve is contained inside the unit. Therefore, remove the front panel. (Fig. 4-6)  
(1) If the tubing is routed out from the front, use cutting pliers or a similar tool to cut out the tubing outlet slit (part indicated  
by  
) from the tubing cover. (Figs. 4-5 and 4-6)  
Front  
Bottom  
Remove 11 panel  
screws from front  
panel  
Tubing cover  
Remove 2 screws  
Use cutting pliers or similar  
tool to cut cover out  
Fig. 4-5  
(2) If the tubing is routed out from the bottom, remove the  
slit part ( ).  
G Use a drill bit approximately 13/64 dia. to create holes at  
the 4 slit hole indentations (openings).  
G Punch out the slit part (  
).  
G Be careful not to damage the base plate.  
Indentation  
(4 locations)  
Slit hole  
Fig. 4-6  
56  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 57  
4-4. Prepare the Tubing  
G Material: Use C1220 phosphorous deoxidized copper as described in JIS H3300, “Copper and Copper Alloy Seamless Pipes  
and Tubes.(For tubes that are ø7/8" (ø22.22 mm) or larger, use 1/2H material or H material. For all others use O material.)  
G Tubing size  
Use the tubing size indicated in the table below.  
G When cutting the tubing, use a tube cutter, and be sure to remove any burrs.  
(The same applies to distribution tubing (optional).)  
G When bending the tubes, bend each tube using a radius that is at least 4 times the outer diameter of the tube.  
When bending, use sufficient care to avoid crushing or damaging the tube  
G For flaring, use a flare tool, and be sure that flaring is performed correctly.  
Use sufficient caution during preparation of the tubing. Seal the tube ends by means of caps  
or taping to prevent dust, moisture, or other foreign substances from entering the tubes.  
CAUTION  
Refrigerant tubing (Existing tubing can be used.)  
Tubing size (in. (mm))  
Material O  
ø1/4" (ø6.35)  
Material 1/2H • H  
t1/32" (0.8)  
t1/32" (0.8)  
ø7/8" (ø22.22)  
t5/128" (1.0)  
t5/128" (1.0)  
ø3/8" (ø9.52)  
ø1/2" (ø12.7)  
ø5/8" (ø15.88)  
ø3/4" (ø19.05)  
ø1" (ø25.4)  
t1/32" (0.8)  
ø1-1/8" (ø28.58)  
ø1-1/4" (ø31.75)  
ø1-1/2" (ø38.1)  
ø1-5/8" (ø41.28)  
t5/128" (1.0)  
t5/128" (1.0)  
over t5/128" (1.0)  
t3/64" (1.1)  
over t3/64" (1.15)  
over t3/64" (1.20)  
4-5. Connect the Tubing  
G Use the supplied connector tubing. (See figure below.)  
09053 type (10 hp)  
1
2
3
Refrigerant tubing Connection method Supplied parts used?  
1
2
3
Gas tubing  
Liquid tubing  
Balance tube  
Brazing  
Yes 3/4" ø7/8")  
Flare connection  
Flare connection  
No  
No  
14053 type (16 hp)  
1
3
2
Refrigerant tubing Connection method Supplied parts used?  
1
2
3
Gas tubing  
Liquid tubing  
Balance tube  
Brazing  
Yes (ø1  
"
ø1-1/8")  
Flare connection  
Flare connection  
No  
No  
57  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 58  
Refrigerant tube port  
G Use caulking, putty, or a similar material to fill any gaps at the  
Bottom  
plate  
refrigerant tube port (  
) in order to prevent rainwater, dust or  
Tubing  
cover  
foreign substances from entering the unit.  
* Perform this work even if the tubing is routed out in a downward  
direction.  
G Tighten each cap as specified below.  
Tubing routed out  
through the front side  
Tubing routed out  
through the bottom  
Tightening torque for each cap  
Cap tightening torque  
* Be careful of the cap sizes. The sizes of the service port cap and valve cap  
on the 14053 type liquid tube valves are different from other valve caps.  
Service port cap  
(width 19/32", 43/64")  
60 – 100 lbs in. (70 – 120 kgf cm)  
·
·
Valve cap  
(width 55/64", 15/16")  
170 – 220 lbs in. (200 – 250 kgf cm)  
·
·
(0905 Type)  
(1405 Type)  
Service port cap  
(width 19/32)  
Service port cap  
(width 43/64)  
Valve cap  
(width 55/64)  
Valve cap  
(width 15/16)  
Valve cap  
(width 55/64)  
Valve cap  
(width 55/64)  
Service port cap  
(width 19/32)  
Service port cap  
(width 19/32)  
Valve cap  
(width 55/64)  
Flare nut  
(ø1/4)  
Valve cap  
(width 55/64)  
Flare nut  
(ø1/4)  
Flare nut  
3/8)  
Service port cap  
(width 19/32)  
Flare nut  
3/8)  
Service port cap  
(width 19/32)  
Unit: in.  
Do not apply a monkey wrench  
Use two monkey wrenches, as shown in the figure,  
to the hexagonal part.  
when removing the liquid tube valve flare nut.  
Do not use two monkey wrenches when  
removing or installing the balance tube  
flare nut. In particular, do not apply a  
monkey wrench to the hexagonal part at  
the top of the valve.  
1. Do not apply a wrench to the valve cap when removing or  
installing the flare nuts. Doing so may damage the valve.  
2. If the valve cap is left off for a long period of time, refrigerant  
leakage will occur. Therefore, do not leave the valve cap off.  
3. Applying refrigerant oil to the flare surface can be effective in  
preventing gas leakage, however be sure to use a refrigerant  
oil which is suitable for the refrigerant that is used in the system.  
(This unit utilizes R410A refrigerant, and the refrigerant oil is  
ether oil (synthetic oil). However, hub oil (synthetic oil) can also  
be used.)  
(If force is applied to this part,  
gas leakage will occur.)  
G Precautions for brazing  
Be sure to replace the air inside the tube with nitrogen to prevent oxide film from forming during the brazing process.  
Be sure to use a damp cloth or other means to cool the valve unit during brazing.  
Pressure-reducing valve (regulator)  
Work method  
Remote valve  
Field-supply tube  
Brazing locations  
Taping  
2
1. Be sure to use nitrogen. (Oxygen, CO , and CFC must not be used.)  
2. Use a pressure-reducing valve on the nitrogen tank.  
CAUTION  
3. Do not use agents intended to prevent the formation of oxide film. They will adversely affect the refrig-  
eration oil, and may cause equipment failure.  
4. The balance tube is not used if only 1 outdoor unit is installed.  
Use the unit in the same conditions as when it was shipped from the factory.  
58  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 59  
5. ELECTRICAL WIRING  
5-1. General Precautions on Wiring  
(7) Regulations on wire diameters differ from locality to  
locality. For field wiring rules, please refer to your  
LOCAL ELECTRICAL CODES before beginning.  
(1) Before wiring, confirm the rated voltage of the unit as  
shown on its nameplate, then carry out the wiring  
closely following the wiring diagram.  
You must ensure that installation complies with all  
relevant rules and regulations.  
(2) Provide a power outlet to be used exclusively for each  
unit, and a power supply disconnect and circuit breaker  
for overcurrent protection should be provided in the  
exclusive line.  
(8) To prevent malfunction of the air conditioner caused by  
electrical noise, care must be taken when wiring as  
follows:  
(3) To prevent possible hazards from insulation failure, the  
unit must be grounded.  
G The remote control wiring and the inter-unit control wiring  
(4) Each wiring connection must be done in accordance  
with the wiring system diagram. Wrong wiring may  
cause the unit to misoperate or become damaged.  
should be wired apart from the inter-unit power wiring.  
G Use shielded wires for inter-unit control wiring between  
units and ground the shield on both sides.  
(5) Do not allow wiring to touch the refrigerant tubing,  
compressor, or any moving parts of the fan.  
(9) If the power supply cord of this appliance is damaged, it  
must be replaced by a repair shop appointed by the  
manufacturer, because special purpose tools are  
required.  
(6) Unauthorized changes in the internal wiring can be very  
dangerous. The manufacturer will accept no  
responsibility for any damage or misoperation that  
occurs as a result of such unauthorized changes.  
5-2. Recommended Wire Length and Wire Diameter for Power Supply System  
Outdoor unit  
(A) Power supply  
Time delay fuse or  
circuit capacity  
Type  
Wire size Max. length  
CHDX09053  
CHDX14053  
AWG #8  
AWG #4  
64 ft.  
100 ft.  
60 A  
80 A  
Indoor unit  
(B) Power supply  
AWG #14  
Time delay fuse or  
circuit capacity  
Type  
K
A, X, T, U  
D
Max. 492 ft.  
Max. 426 ft.  
Max. 196 ft.  
15 A  
15 A  
15 A  
Control wiring  
(C) Inter-unit (between outdoor and  
(D) Remote control wiring  
(E) Control wiring for group control  
indoor units) control wiring  
AWG #18 (0.75 mm2)  
AWG #18 (0.75 mm2)  
AWG #18 (0.75 mm2)  
Use shielded wiring*  
Use shielded wiring  
Use shielded wiring  
Max. 3,280 ft.  
Max. 1,640 ft.  
Max. 1,640 ft. (Total)  
(F) Inter-outdoor unit control wiring  
AWG #18 (0.75 mm2)  
Use shielded wiring  
NOTE  
* With ring-type wire terminal.  
Max. 1,640 ft.  
59  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 60  
5-3. Wiring System Diagram  
Indoor  
unit (No. 1)  
L1  
L2  
Power supply  
L1  
L2  
Outdoor unit  
INV unit  
208 / 230V, 1ø, ~60Hz  
A
C
L1  
L2  
L3  
Power supply  
Ground  
1
B
U1  
2
U1  
U2  
208 / 230V, 3ø, ~60Hz  
Remote  
U2  
3
4
5
D
D
controller  
Ground  
3
4
R1  
R2  
1
2
1
2
WHT  
BLK  
Ground  
Ground  
C
Ground  
Indoor  
Ground  
unit (No. 2)  
F
Inter-outdoor-unit control wiring  
Outdoor unit  
L1  
L2  
Power supply  
Ground  
Ground  
L1  
L2  
208 / 230V, 1ø, ~60Hz  
Ground  
B
U1  
U2  
INV unit  
Remote  
A
L1  
L2  
L3  
Power supply  
controller  
1
2
208 / 230V, 3ø, ~60Hz  
R1  
R2  
1
2
1
2
WHT  
3
4
3
4
5
BLK  
C
Ground  
Ground  
Indoor  
Group control:  
L1  
unit (No. 3)  
Power supply  
L1  
L2  
L2  
208 / 230V, 1ø, ~60Hz  
Ground  
Ground  
Ground  
B
E
U1  
U2  
R1  
R2  
C
Indoor  
unit (No. n)  
L1  
L2  
Power supply  
L1  
L2  
208 / 230V, 1ø, ~60Hz  
Ground  
Ground  
B
U1  
U2  
Remote  
D
controller  
1
2
1
2
R1  
R2  
WHT  
BLK  
Ground  
7P terminal board  
NOTE  
(1) Refer to Section 5-2. “Recommended Wire Length and  
Wire Diameter for Power Supply System” for the  
explanation of “A,B,” “C,” “D,” and “E,” in the above  
diagram.  
(2) The basic connection diagram of the indoor unit shows  
the 7P terminal board, so the terminal boards in your  
equipment may differ from the diagram.  
1(L1) 2(L2)  
U1 U2 R1 R2  
Inter-unit  
Remote  
Power  
supply  
control wiring controller  
X, A, U, D, T Type  
(3) Refrigerant Circuit (R.C.) address should be set before  
turning the power on.  
5P terminal board  
(4) Regarding the R.C. address setting, refer to page 74.  
Address setting can be executed by remote controller  
automatically. Refer to page 74 – 78.  
1
2
3
4
5
1(L1)2(L2)  
Power  
U1 U2  
Inter-unit  
control wiring  
supply  
K Type  
60  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 61  
CAUTION  
(1) When linking outdoor units in a network (S-net link system), disconnect the terminal extended from the short plug  
(CN003, 2P Black, location: right bottom on the outdoor main control PCB) from all outdoor units except any one  
of the outdoor units. (When shipping: In shorted condition.)  
Otherwise the communication of S-net link system is not performed. For a system without link (no connection  
wiring between outdoor units), do not remove the short plug.  
(2) Do not install the inter-unit control wiring in a way that forms a loop. (Fig. 5-1)  
Outdoor unit  
Outdoor unit  
Outdoor unit  
Prohibited  
Prohibited  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
Fig. 5-1  
(3) Do not install inter-unit control wiring such as star branch  
wiring. Star branch wiring causes mis-address setting.  
Outdoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
NO  
Outdoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
NO  
Branch point  
Fig. 5-2  
(4) If branching the inter-unit control wiring, the number of branch points should be 16 or fewer.  
(Branches less than 3.3 ft. are not included in the total branch number.) (Fig. 5-3)  
Outdoor unit  
Outdoor unit  
Outdoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
more than 3.3 ft.  
Branch  
point  
Indoor unit  
Indoor unit  
Indoor unit  
Indoor unit  
16 or fewer  
more than 3.3 ft.  
Indoor unit  
less than 3.3 ft.  
Indoor unit  
Fig. 5-3  
61  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 62  
(5) Use shielded wires for inter-unit control wiring (c)  
and ground the shield on both sides, otherwise  
misoperation from noise may occur. (Fig. 5-4)  
Connect wiring as shown in Section “5-3. Wiring  
System Diagram.”  
Shielded wire  
Ground  
Ground  
Loose wiring may cause the  
Fig. 5-4  
terminal to overheat or result  
WARNING  
in unit malfunction. A fire  
hazard may also exist.  
Therefore, ensure that all  
wiring is tightly connected.  
When connecting each power wire to the terminal, follow  
the instructions on “How to connect wiring to the terminal”  
and fasten the wire securely with the fixing screw of the  
terminal plate.  
How to connect wiring to the terminal  
I For stranded wiring  
Stranded wire  
(1) Cut the wire end with cutting pliers, then strip the  
insulation to expose the stranded wiring about 3/8 in.  
and tightly twist the wire ends. (Fig. 5-5)  
Ring  
pressure  
terminal  
(2) Using a Phillips head screwdriver, remove the terminal  
screw(s) on the terminal plate.  
(3) Using a ring connector fastener or pliers, securely  
clamp each stripped wire end with a ring pressure  
terminal.  
Fig. 5-5  
(4) Place the ring pressure terminal, and replace and  
tighten the removed terminal screw using a screwdriver.  
(Fig. 5-6)  
Special  
washer  
Screw  
Ring pressure  
terminal  
Screw and  
Special washer  
Terminal plate  
Wire  
Ring  
pressure  
terminal  
Wire  
Fig. 5-6  
62  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 63  
6. HOW TO PROCESS TUBING  
Deburring  
The liquid tubing side is connected by a flare nut, and the  
gas tubing side is connected by brazing.  
After  
Before  
6-1. Connecting the Refrigerant Tubing  
Use of the Flaring Method  
Many of conventional split system air conditioners employ the  
flaring method to connect refrigerant tubes which run between  
indoor and outdoor units. In this method, the copper tubes are  
flared at each end and connected with flare nuts.  
Flaring Procedure with a Flare Tool  
Fig. 6-1  
(1) Cut the copper tube to the required length with a tube  
cutter. It is recommended to cut approx. 1 – 2 ft. longer  
than the tubing length you estimate.  
Copper  
tubing  
(2) Remove burrs at the end of the copper tube with a tube  
reamer or file. This process is important and should be  
done carefully to make a good flare. (Fig. 6-1)  
Reamer  
NOTE  
When reaming, hold the tube end downward and be sure  
that no copper scraps fall into the tube. (Fig. 6-2)  
Fig. 6-2  
(3) Remove the flare nut from the unit and be sure to  
mount it on the copper tube.  
(4) Make a flare at the end of copper tube with a flare  
tool.* (Fig. 6-3)  
®
Flare nut  
(*Use “RIGID ” or equivalent.)  
Copper  
tubing  
NOTE  
A good flare should have the following characteristics:  
G inside surface is glossy and smooth  
G edge is smooth  
Flare tool  
Fig. 6-3  
G tapered sides are of uniform length  
63  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 64  
Caution Before Connecting Tubes Tightly  
(1) Apply a sealing cap or water-proof tape to prevent dust  
or water from entering the tubes before they are used.  
Apply refrigerant  
lubricant here and here  
(2) Be sure to apply refrigerant lubricant to the matching  
surfaces of the flare and union before connecting them  
together. This is effective for reducing gas leaks.  
(Fig. 6-4)  
Fig. 6-4  
(3) For proper connection, align the union tube and flare  
tube straight with each other, then screw in the flare nut  
lightly at first to obtain a smooth match. (Fig. 6-5)  
G Adjust the shape of the liquid tube using a tube bender  
at the installation site and connect it to the liquid tubing  
side valve using a flare.  
Flare nut  
Union  
Fig. 6-5  
Cautions During Brazing  
G Replace air inside the tube with nitrogen gas to  
prevent copper oxide film from forming during the  
brazing process. (Oxygen, carbon dioxide and Freon  
are not acceptable.)  
Torque wrench  
Spanner  
G Do not allow the tubing to get too hot during  
brazing. The nitrogen gas inside the tubing may  
overheat, causing refrigerant system valves to  
become damaged. Therefore allow the tubing to  
cool when brazing.  
Indoor unit  
Outdoor unit  
Fig. 6-6  
G Use a reducing valve for the nitrogen cylinder.  
G Do not use agents intended to prevent the formation  
of oxide film. These agents adversely affect the  
refrigerant and refrigerant oil, and may cause  
damage or malfunctions.  
Tightening torque,  
approximate  
Tube thickness  
Tube diameter  
120 – 160 lbs inch  
1/32"  
(0.8 mm)  
·
·
ø1/4" (ø6.35 mm)  
(140 – 180 kgf cm)  
1/32"  
(0.8 mm)  
300 – 360 lbs inch  
·
6-2. Connecting Tubing Between Indoor and  
Outdoor Units  
ø3/8" (ø9.52 mm)  
ø1/2" (ø12.7 mm)  
ø5/8" (ø15.88 mm)  
ø3/4" (ø19.05 mm)  
(340 – 420 kgf cm)  
·
1/32"  
(0.8 mm)  
430 – 530 lbs inch  
·
·
(1) Tightly connect the indoor-side refrigerant tubing  
extended from the wall with the outdoor-side tubing.  
(490 – 610 kgf cm)  
5/128"  
(1.0 mm)  
590 – 710 lbs inch  
·
·
(680 – 820 kgf cm)  
(2) To fasten the flare nuts, apply specified torque as at  
right:  
over 5/128"  
(1.0 mm)  
870 – 1040 lbs inch  
·
(1000 – 1200 kgf cm)  
·
G When removing the flare nuts from the tubing  
connections, or when tightening them after connecting  
the tubing, be sure to use 2 monkey wrenches or  
spanners as shown. (Fig. 6-6)  
Because the pressure is approximately 1.6 times higher  
than conventional refrigerant pressure, the use of ordinary  
flare nuts (type 1) or thin-walled tubes may result in tube  
rupture, injury, or asphyxiation caused by refrigerant  
leakage.  
If the flare nuts are over-tightened, the flare may be  
damaged, which could result refrigerant leakage and  
cause in injury or asphyxiation to room occupants.  
G In order to prevent damage to the flare caused by over-  
tightening of the flare nuts, use the table above as a guide  
when tightening.  
G For the flare nuts at tubing connections, be sure to use  
the flare nuts that were supplied with the unit, or else  
flare nuts for R410A (type 2). The refrigerant tubing that  
is used must be of the correct wall thickness as shown in  
the table at right.  
G When tightening the flare nut on the liquid tube, use a  
monkey wrench with a nominal handle length of 7-7/8 in.  
64  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 65  
Two tubes arranged together  
6-3. Insulating the Refrigerant Tubing  
Tubing Insulation  
Liquid tubing  
Gas tubing  
G Thermal insulation must be applied to all unit tubing,  
including the distribution joint (purchased separately).  
* For gas tubing, the insulation material must be heat  
resistant to 248°F or above. For other tubing, it must be  
heat resistant to 176°F or above.  
Insulation  
Insulation material thickness must be 25/64 in. or greater.  
Three tubes arranged together  
If the conditions inside the ceiling exceed DB 86°F and RH  
70%, increase the thickness of the gas tubing insulation  
material by 1 step.  
Cosmetic  
(finishing) tape  
Gas tubing  
Liquid tubing  
If the exterior of the outdoor unit  
valves has been finished with a  
CAUTION  
square duct covering, make sure  
you allow sufficient space to use  
the valves and to allow the panels  
to be attached and removed.  
Insulation  
Balance tubing  
Fig. 6-7  
Taping the flare nuts  
Wind the white insulation tape around the flare nuts at the gas  
tube connections. Then cover up the tubing connections with  
the flare insulator, and fill the gap at the union with the sup-  
plied black insulation tape. Finally, fasten the insulator at both  
ends with the supplied vinyl clamps. (Fig. 6-8)  
Sealer (supplied)  
Insulation tape (white)  
(supplied)  
Flare insulator (supplied)  
Tube insulator  
(not supplied)  
Heat resistant  
248°F or above  
Unit side  
insulator  
Insulation material  
Flare nut  
The material used for insulation must have good insulation  
characteristics, be easy to use, be age resistant, and must not  
easily absorb moisture.  
Vinyl clamps (supplied)  
Fig. 6-8  
Refrigerant tubing and insulator  
(not supplied)  
After a tube has been insulated,  
CAUTION  
Drain insulator  
and clamp.  
Large  
never try to bend it into a narrow  
Drain pipe and insulator  
(not supplied)  
curve because it can cause the  
tube to break or crack.  
(supplied)  
Packing  
clamp.  
Small  
Insulation  
tape  
hose band  
(supplied)  
Vinyl  
clamp  
Flare  
insulator  
Seal  
The procedure used for  
installing the insulator for  
both gas and liquid  
tubes is the same.  
Fig. 6-9  
Never grasp the drain or refrigerant connecting outlets  
when moving the unit.  
65  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 66  
6-4. Taping the Tubes  
(1) At this time, the refrigerant tubes (and electrical wiring  
if local codes permit) should be taped together with  
armoring tape in 1 bundle. To prevent the condensation  
from overflowing the drain pan, keep the drain hose  
separate from the refrigerant tubing.  
(2) Wrap the armoring tape from the bottom of the outdoor  
unit to the top of the tubing where it enters the wall. As  
you wrap the tubing, overlap half of each previous tape  
turn.  
Clamp  
Drain hose  
Insulated tubes  
(3) Clamp the tubing bundle to the wall, using 1 clamp  
approx. each ft. (Fig. 6-10)  
NOTE  
Do not wind the armoring tape too tightly since this will  
decrease the heat insulation effect. Also ensure that the  
condensation drain hose splits away from the bundle and  
drips clear of the unit and the tubing.  
Fig. 6-10  
6-5. Finishing the Installation  
Apply putty here  
After finishing insulating and taping over the tubing, use  
sealing putty to seal off the hole in the wall to prevent rain  
and draft from entering. (Fig. 6-11)  
Tubing  
Fig. 6-11  
66  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 67  
Manifold gauge  
7. AIR PURGING  
Air and moisture in the refrigerant system may have  
undesirable effects as indicated below.  
G pressure in the system rises  
G operating current rises  
G cooling (or heating) efficiency drops  
G moisture in the refrigerant circuit may freeze and block capillary  
tubing  
G water may lead to corrosion of parts in the refrigerant system  
Fig. 7-1  
Therefore, the indoor unit and tubing between the indoor and  
outdoor unit must be leak tested and evacuated to remove any  
noncondensables and moisture from the system.  
Vacuum pump  
Outlet  
Inlet  
I Air Purging with a Vacuum Pump (for Test Run) Preparation  
Check that each tube (both liquid and gas tubes) between the  
indoor and outdoor units have been properly connected and all  
wiring for the test run has been completed. Remove the valve caps  
from both the gas and liquid service valves on the outdoor unit.  
Note that both liquid and gas tube service valves on the outdoor  
unit are kept closed at this stage.  
Fig. 7-2  
Manifold valve  
Leak test  
Pressure  
gauge  
(1) With the service valves on the outdoor unit closed, remove the  
5/16" flare nut and its bonnet on the gas tube service valve.  
(Save for reuse.)  
Lo  
Hi  
Charge hose  
(2) Attach a manifold valve (with pressure gauges) and dry  
nitrogen gas cylinder to this service port with charge hoses.  
Cylinder  
valve  
Use a manifold valve for air purging.  
CAUTION  
Nitrogen gas cylinder  
(In vertical standing  
position)  
If it is not available, use a stop valve  
for this purpose. The “Hi” knob of  
the manifold valve must always be  
kept closed.  
2
(3) Pressurize the system to no more than 469 psig (33 kgf/cm G)  
with dry nitrogen gas and close the cylinder valve when the  
Open  
Open  
Open  
2
gauge reading reaches 469 psig (33 kgf/cm G). Then, test for  
Gas  
tube  
leaks with liquid soap.  
Close  
Close  
Close  
To avoid nitrogen entering the  
CAUTION  
refrigerant system in a liquid state, the  
top of the cylinder must be higher than  
the bottom when you pressurize the  
system. Usually, the cylinder is used in  
a vertical standing position.  
Outdoor unit  
Liquid  
tube  
Balance  
tube  
Fig. 7-3  
67  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 68  
(4) Do a leak test of all joints of the tubing (both indoor and  
outdoor) and both gas and liquid service valves. Bub-  
bles indicate a leak. Wipe off the soap with a clean cloth  
after a leak test.  
Manifold valve  
Pressure  
gauge  
Lo  
Hi  
(5) After the system is found to be free of leaks, relieve the  
nitrogen pressure by loosening the charge hose con-  
nector at the nitrogen cylinder. When the system pres-  
sure is reduced to normal, disconnect the hose from the  
cylinder.  
Evacuation  
(1) Attach the charge hose end described in the preceding  
steps to the vacuum pump to evacuate the tubing and  
indoor unit. Confirm that the “Lo” knob of the manifold  
valve is open. Then, run the vacuum pump. The opera-  
tion time for evacuation varies with the tubing length and  
capacity of the pump. The following table shows the  
amount of time for evacuation:  
Vacuum pump  
Open  
Open  
Open  
Gas  
tube  
Required time for evacuation  
Close  
Close  
Close  
when 30 gal/h vacuum pump is used  
If tubing length is  
less than 49 ft.  
If tubing length is  
longer than 49 ft.  
90 min. or more  
Outdoor unit  
45 min. or more  
Liquid  
tube  
Balance  
tube  
Fig. 7-4  
68  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 69  
Manifold valve  
NOTE  
Pressure  
gauge  
Lo  
Hi  
The required time in the above table is calculated based on the  
assumption that the ideal (or target) vacuum condition is less  
than –14.7 psig (–755 mmHg, 5 Torr).  
Valve  
(2) When the desired vacuum is reached, close the “Lo” knob of  
the manifold valve and turn off the vacuum pump. Please  
confirm that the gauge pressure is under –14.7 psig  
(–755 mmHg, 5 Torr) after 4 to 5 minutes of vacuum pump  
operation.  
Liquid  
Use a cylinder designed for use  
CAUTION  
with R410A respectively.  
R410A  
Charging additional refrigerant  
Close  
Open  
Close  
G Charging additional refrigerant (calculated from the liquid  
tube length as shown in Section “1-8. Additional Refrigerant  
Charge”) using the liquid tube service valve. (Fig. 7-5)  
Gas  
tube  
Close  
Close  
Close  
G Use a balance to measure the refrigerant accurately.  
G If the additional refrigerant charge amount cannot be charged  
at once, charge the remaining refrigerant in liquid form by  
using the gas tube service valve with the system in cooling  
operation mode at the time of test run. (Fig. 7-6)  
Outdoor unit  
Liquid  
tube  
Finishing the job  
(1) With a hex wrench, turn the liquid tube service valve stem  
counter-clockwise to fully open the valve.  
Balance  
tube  
Fig. 7-5  
To avoid gas from leaking when  
CAUTION  
removing the charge hose, make  
sure the stem of the gas tube is  
turned all the way out (“BACK  
SEAT” position).  
(2) Turn the gas tube service valve stem counter-clockwise to  
fully open the valve.  
Open  
Close  
Close  
(3) Loosen the charge hose connected to the gas tube service  
port (5/16") slightly to release the pressure, then remove the  
hose.  
Gas  
tube  
Open  
Open  
Open  
(4) Replace the 1/4 in. flare nut and its bonnet on the gas tube  
service port and fasten the flare nut securely with an  
adjustable wrench or box wrench. This process is very  
important to prevent gas from leaking from the system.  
Outdoor unit  
Liquid  
tube  
(5) Replace the valve caps at both gas and liquid service valves  
and fasten them securely.  
This completes air purging with a vacuum pump. The air condi-  
tioner is now ready for a test run.  
Balance  
tube  
Fig. 7-6  
69  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 70  
8. TEST RUN  
8-1. Preparing for Test Run  
G Before attempting to start the air conditioner, check  
the following.  
(1) All loose matter is removed from the cabinet especially  
steel filings, bits of wire, and clips.  
ON  
(Power must be turned ON  
at least 5 hours before  
attempting test run)  
(2) The control wiring is correctly connected and all  
electrical connections are tight.  
(3) The protective spacers for the compressor used for  
transportation have been removed. If not, remove them  
now.  
Power mains switch  
(4) The transportation pads for the indoor fan have been  
removed. If not, remove them now.  
Fig. 8-1  
(5) The power has been connected to the unit for at least 5  
hours before starting the compressor. The bottom of the  
compressor should be warm to the touch and the  
crankcase heater around the feet of the compressor  
should be hot to the touch.  
(Fig. 8-1)  
(6) Both the gas and liquid tube service valves are open. If  
not, open them now. (Fig. 8-2)  
(7) Request that the customer be present for the trial run.  
Explain the contents of the instruction manual, then have  
the customer actually operate the system.  
Balance tube  
Liquid tube  
Gas tube  
(8) Be sure to give the instruction manual and warranty  
certificate to the customer.  
Fig. 8-2  
(9) When replacing the control PCB, be sure to make all the  
same settings on the new PCB as were in use before  
replacement.  
The existing EEP ROM is not changed, and is  
connected to the new control PCB.  
70  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 71  
Items to Check Before the Test Run  
1. Turn the remote power switch on at least 5 hours  
before the test, in order to energize the crank  
case heater.  
8-2. Test Run Procedure  
Recheck the items to check before the test run.  
2. After performing the leak inspection, applying  
vacuum, and performing refrigerant charge for  
the tubing which is connected on-site, fully open  
the outdoor unit service valve. However if only  
one outdoor unit is installed, a balance tube is  
not used. Therefore, leave the valve fully closed.  
NO  
Have the outdoor sub units been connected?  
YES  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S007)  
*1  
*1 The unit with the unit  
No. set to 1 is the  
Set the unit address.  
main unit. All other  
units are sub units.  
3. When replacing the control PCB, be sure that  
the settings on the new PCB match those on the  
old PCB.  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S006)  
Set the No. of outdoor units.  
4. Use caution when making the settings. If there  
are duplicated system addresses, or if the  
settings for the Nos. of the indoor units are not  
consistent, an alarm will occur and the system  
will not start.  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S004 and S005)  
Set the No. of indoor units.  
5. These settings are not made on the indoor unit  
PCB.  
CASE 1  
Are the inter-unit control wires  
connected to more than 1 refrigerant  
system?  
NO  
(Check the link wiring.)  
<Outdoor unit control PCB>  
Unit No. setting switch  
(S002 and S003)  
YES  
Set the system address.  
When multiple outdoor main units exist, disconnect the terminals  
extended from the shorted plugs (CN003) at all outdoor main unit  
PCBs except for 1.  
Note: It is not necessary to remove the socket  
that is used to short-circuit the terminal  
plugs from the outdoor sub unit PCBs.  
Refer to Fig. 8-4  
Alternatively, move the sockets to the OPEN side.  
CASE 2  
Is it possible to turn ON the power only  
for the 1 refrigerant system where the  
YES  
test run will be performed?  
Turn ON the indoor and  
outdoor unit power for that  
refrigerant system only.  
NO  
Will automatic address setting be  
performed in Heating mode?  
Make necessary corrections.  
Short-circuit the automatic address pin (CN100)  
on the outdoor main unit PCB for 1 second or  
longer, then release it.  
NO  
CASE 3B  
Turn OFF the indoor and  
outdoor unit power.  
YES  
CASE 3A  
LED 1 and 2 blink alternately  
(about 2 or 3 minutes).  
Is it OK to start the compressors?  
Is it OK to start the compressors?  
Check the alarm contents.  
Turn ON the indoor and  
outdoor unit power.  
Turn ON the indoor and  
outdoor unit power.  
NO  
Are LEDs 1 and 2 on the  
outdoor unit PCB OFF?  
Make necessary  
corrections  
*2  
*2  
Refer to “Table of  
Short-circuit the mode change pin  
Short-circuit the automatic address  
pin (CN100) on the outdoor main  
unit PCB for 1 second or longer,  
then release it.  
Self-Diagnostic Functions and  
Description of Alarm Displays.”  
(CN101) on the outdoor main unit PCB.  
At the same time, short-circuit the  
automatic address pin (CN100) for 1  
second or longer, then release it.  
YES  
Turn OFF the indoor and  
outdoor unit power.  
*3  
*3  
Start indoor and outdoor unit  
cooling operation.  
Start indoor and outdoor unit  
heating operation.  
Check the alarm  
contents.  
LED 1 and 2 blink alternately.  
LED 1 and 2 blink alternately.  
*2 A minimum of 5 hours must have passed after the  
power was turned ON to the outdoor unit.  
*3 All indoor units operate in all refrigerant systems  
where the power is ON.  
NO  
Are LEDs 1 and 2 on the  
outdoor unit PCB OFF?  
YES  
Check that test run preparation is OK.  
(Do not allow the short-circuited pins to remain short-circuited.)  
Set the wired remote controller for test run.  
Refer to the remote  
controller test-run  
settings.  
NO  
Check and make corrections according to  
Table of Self-Diagnostic Functions.”  
Does system operate?  
YES  
Return remote control to normal mode  
End test run.  
Fig. 8-3  
71  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 72  
8-3. Main Outdoor Unit PCB Setting  
S003 S002 S004 S005 S006 S007  
CN100  
CN101  
CN003  
Fig. 8-4  
72  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 73  
Examples of the No. of indoor units settings (S005, S004)  
Indoor unit setting (S005)  
Indoor unit setting (S004)  
No. of indoor units  
(3P DIP switch, blue)  
(Rotary switch, red)  
10 20 30  
ON  
ON  
1 unit (factory setting)  
11 units  
All OFF  
1 ON  
Set to 1  
Set to 1  
Set to 1  
Set to 1  
2
2
2
2
2
3
3
3
3
3
1
OFF  
ON  
ON  
1
OFF  
ON  
ON  
21 units  
2 ON  
1
OFF  
ON  
ON  
31 units  
3 ON  
1
OFF  
ON  
ON  
0
40 units  
1 & 3 ON  
Set to 0  
1
OFF  
Examples of refrigerant circuit (R.C.) address settings (required when link wiring is used) (S003, S002)  
System address (S003)  
(2P DIP switch, blue)  
System address (S002)  
(Rotary switch, black)  
System address No.  
10 20  
ON  
ON  
Set to 1  
Both OFF  
1 ON  
System 1 (factory setting)  
System 11  
2
2
2
2
1
OFF  
ON  
ON  
Set to 1  
1
OFF  
ON  
ON  
System 21  
2 ON  
Set to 1  
1
OFF  
ON  
ON  
0
System 30  
Set to 0  
1 & 2 ON  
1
OFF  
Examples of the No. of outdoor units settings (S006)  
Outdoor unit setting (S006)  
No. of outdoor units  
(3P DIP switch, blue)  
ON  
ON  
1 unit (factory setting)  
1 ON  
2 ON  
1
2
2
2
2
3
3
3
3
OFF  
ON  
ON  
2 units  
3 units  
4 units  
1
OFF  
ON  
ON  
1 & 2 ON  
1
OFF  
ON  
ON  
3 ON  
1
OFF  
Address setting of main outdoor unit (S007)  
Address setting of outdoor unit (S007)  
Unit No. setting  
(3P DIP switch, blue)  
ON  
ON  
Unit No. 1 (main unit)  
(factory setting)  
1
2
3
OFF  
Address setting of sub outdoor unit  
Address setting of outdoor unit (S007)  
Unit No. setting  
(3P DIP switch, blue)  
ON  
ON  
Unit No. 2 (sub unit)  
(factory setting)  
2 ON  
1 & 2 ON  
3 ON  
1
2
2
2
3
3
3
OFF  
ON  
ON  
Unit No. 3 (sub unit)  
1
OFF  
ON  
ON  
Unit No. 4 (sub unit)  
1
OFF  
The sub unit control PCB contains the same switches as the main unit control PCB for No. of indoor units, No. of outdoor units,  
and system address. However it is not necessary to set these switches.  
73  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 74  
8-4. Auto Address Setting  
Basic wiring diagram: Example (1)  
• If link wiring is not used  
(The inter-unit control wires are not connected to multiple refrigerant systems.)  
Indoor unit addresses can be set without operating the compressors.  
No. 1 (main outdoor unit)  
settings  
No. of indoor units  
(10 units setting)  
System address  
(S004)  
(system 1 setting)  
0
(S002) (S003)  
ON  
ON  
(S005)  
No. 3 (sub unit)  
No. 2 (sub unit)  
ON  
ON  
1
2
OFF  
settings  
settings  
1
2
3
OFF  
Unit  
number  
setting  
(S007)  
Unit  
number  
setting  
(S007)  
No. of  
outdoor  
(S006)  
(S007)  
ON  
ON  
ON  
OFF  
ON  
Unit number  
setting  
(Unit No. 1)  
ON  
ON  
ON  
ON  
units (3 units  
OFF  
1
2
3
1
2
3
(Unit No. 3)  
1
2
3
OFF  
(Unit No. 2)  
1
2
3
setting)  
OFF  
Leave the socket that  
is used to short-circuit  
the terminal plug.  
(CN003)  
Unit  
No. 1  
(Main)  
Unit  
No. 2  
(Sub)  
Unit  
No. 3  
(Sub)  
Outdoor Unit  
Outdoor main/sub  
control wiring  
Outdoor main/sub  
control wiring  
Inter-unit control wiring  
Indoor Unit  
1-1  
1-2  
1-3  
1-10  
Remote controller  
cross-over wiring  
Remote controller  
Fig. 8-5  
Case 1  
(1) Automatic Address Setting from the Outdoor Unit  
1. To set the number of outdoor units, on the outdoor main unit control PCB set the No. of outdoor units DIP switch (S006) to  
ON  
ON  
ON  
(3 units), and set the unit No. DIP switch (S007) to  
(unit No. 1 – main outdoor unit).  
1
2
3
1
2
3
OFF  
ON  
2. On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to  
On the No. 3 (sub) unit control PCB, set the unit No. switch (S007) to  
(unit No. 2).  
(unit No. 3).  
1
2
3
3
ON  
1
2
3. On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP switch  
ON  
ON  
(S003) is set to  
“0.(These are the settings at the time of factory shipment.)  
1
2
OFF  
4. To set the number of indoor units that are connected to the outdoor unit to 10, on the outdoor main unit control PCB set the No. of  
ON  
ON  
indoor units DIP switch (S005) to  
“1,and set the rotary switch (S004) to “0.”  
1
2
3
OFF  
5. Turn ON the power to the indoor and outdoor units.  
6. On the outdoor main unit control PCB, short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
(Communication for automatic address setting begins.)  
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
The LED that indicates that automatic address setting is in progress turns OFF and the process is  
stopped. Be sure to perform automatic address setting again.  
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)  
7. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 to 5, then use the remote controller and com-  
plete automatic address setting.  
G Refer to “Automatic Address Setting from the Remote Controller.”  
74  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 75  
Basic wiring diagram: Example (2)  
• If link wiring is used  
*When multiple outdoor main units exist, remove the socket that  
is used to short-circuit the terminal plug (CN003) from all  
outdoor main unit PCBs except for one unit.  
No. 1 Refrigerant circuit  
No. 1 (main outdoor unit) settings  
Alternatively, move the sockets to the “OPEN” side.  
No. of indoor units  
(13 units setting)  
(S004)  
System address  
(system 1 setting)  
(S002) (S003)  
ON  
OFF  
ON  
1
2
(S005)  
ON  
ON  
No. 2 (sub unit)  
No. 3 (sub unit)  
1
2
3
OFF  
settings  
settings  
No. of  
(S006)  
ON  
Unit  
(S007)  
Unit  
Unit  
(S007)  
(S007)  
ON  
outdoor units  
(3 units  
ON  
ON  
number  
ON  
ON  
number  
setting  
(unit No. 3)  
ON  
number  
setting  
(unit No. 2)  
ON  
setting  
setting)  
1
2
3
1
2
3
(unit No. 1)  
OFF  
OFF  
2
3
1
OFF  
1
2
3
OFF  
Leave the socket that  
is used to short-circuit  
the terminal plug.  
(CN003)  
Unit  
No. 1  
(Main)  
Unit  
No. 2  
(Sub)  
Unit  
No. 3  
(Sub)  
Outdoor unit  
system 1  
Outdoor main/sub  
control wiring  
Inter-unit control wiring  
1-1  
1-2  
1-3  
1-13  
Indoor unit  
Remote controller  
communication wiring  
Remote  
controller  
No. 1 (main unit) settings  
No. 2  
System address  
(system 2 setting)  
Refrigerant  
circuit  
No. of indoor units (9  
units setting)  
(S004)  
(S002) (S003)  
ON  
OFF  
ON  
1
2
(S005)  
ON  
ON  
No. 2 (sub unit) settings  
1
2
3
OFF  
Unit  
(S007)  
ON  
No. of  
(S006)  
ON  
Unit  
(S007)  
ON  
ON  
number  
setting  
(unit No. 2)  
ON  
ON  
outdoor  
number  
units (2 units  
setting)  
setting  
1
2
3
OFF  
2
3
1
2
3
1
(unit No. 1)  
OFF  
OFF  
Unit  
No. 1  
(Main)  
Unit  
No. 2  
(Sub)  
Move the socket to  
the “OPEN” side  
(CN003).  
Outdoor unit  
system 2  
Outdoor main/sub control wiring  
Inter-unit control wiring  
Indoor unit  
2-1  
2-2  
2-9  
To other system  
link wiring  
Remote controller  
cross-over wiring  
Remote  
controller  
Make settings as appropriate for the cases listed below.  
(Refer to the instructions on the following pages.)  
• Indoor and outdoor unit power can be turned ON for each system separately.  
Case 2  
• Indoor and outdoor unit power cannot be turned ON for each system separately.  
Automatic address setting in Heating mode  
Case 3A  
Automatic address setting in Cooling mode  
Case 3B  
Fig. 8-6  
75  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 76  
Case 2  
Automatic Address Setting (no compressor operation)  
G Indoor and outdoor unit power can be turned ON for each system separately.  
Indoor unit addresses can be set without operating the compressors.  
ON  
Automatic Address Setting from Outdoor Unit  
1
2
3
1. On the No. 1 (main) unit control PCB, set the unit No. switch (S007) to  
(unit No. 1).  
(unit No. 2).  
ON  
On the No. 2 (sub) unit control PCB, set the unit No. switch (S007) to  
1
2
2
3
3
ON  
On the No. 3 (sub) unit control PCB, set the unit No. switch (S007) to  
(unit No. 3).  
1
2. To set the number of outdoor units on the outdoor main unit control PCB, set the No. of outdoor units DIP switch (S006) to  
ON  
ON  
(3 units).  
1
2
3
OFF  
3. On the outdoor main unit control PCB, check that the system address rotary switch (S002) is set to “1” and that the DIP  
ON  
ON  
switch (S003) is set to “0”  
. (These are the settings at the time of factory shipment.)  
1
2
OFF  
4. To set the number of indoor units that are connected to the outdoor unit to 13, on the outdoor main unit control PCB set the  
ON  
ON  
No. of indoor units DIP switch (S005) to “1”  
, and set the rotary switch (S004) to “3.”  
1
2
3
OFF  
5. Turn on power to all indoor and outdoor units in the system.  
6. Short-circuit the automatic address pin at the outdoor main unit (CN100) for 1 second or longer, then release it.  
(Communication for automatic address setting begins.)  
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.  
Be sure to perform automatic address setting again.  
(Automatic address setting is completed when LEDs 1 and 2 on the outdoor main unit control PCB turn OFF.)  
7. Next turn the power ON only for the indoor and outdoor units of the next (different) system. Repeat steps 1 – 5 in the same  
way to complete automatic address settings for all systems.  
8. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 – 5, then use the remote controller and  
complete automatic address setting.  
G Refer to “Automatic Address Setting from Remote Controller.”  
76  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 77  
Case 3A  
Automatic Address Setting in Heating Mode  
G Indoor and outdoor unit power cannot be turned ON for each system separately.  
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.  
Therefore perform this process only after completing all refrigerant tubing work.  
Automatic Address Setting from Outdoor Unit  
Case 2  
1. Perform steps 1 – 4 in the same way as for  
.
5. Turn the indoor and outdoor unit power ON at all systems.  
Heating mode  
6. To perform automatic address setting in  
, on the outdoor main unit control PCB in the refrigerant system  
where you wish to set the addresses, short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
(Be sure to perform this process for one system at a time. Automatic address settings cannot be performed for more than  
one system at the same time.)  
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in  
Heating mode begins.)  
(All indoor units operate.)  
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped.  
Be sure to perform automatic address setting again.  
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the main unit control PCB turn  
OFF.)  
7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN100) for 1 second or  
longer, then release it.  
(Repeat the same steps to complete automatic address setting for all units.)  
8. Operation from the remote controllers is now possible.  
* To perform automatic address setting from the remote controller, perform steps 1 – 5, then use the remote controller and  
complete automatic address setting.  
G Refer to “Automatic Address Setting from Remote Controller.”  
77  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 78  
Case 3B  
Automatic Address Setting in Cooling Mode  
G Indoor and outdoor unit power cannot be turned ON for each system separately.  
In the following, automatic setting of indoor unit addresses is not possible if the compressors are not operating.  
Therefore perform this process only after completing all refrigerant tubing work.  
Automatic address setting can be performed during Cooling operation.  
Automatic Address Setting from Outdoor Unit  
Case 2  
1. Perform steps 1 – 4 in the same way as for  
.
5. Turn the indoor and outdoor unit power ON at all systems.  
Cooling mode  
6. To perform automatic address setting in  
, on the outdoor main unit control PCB in the refrigerant system where  
you wish to set the addresses, short-circuit the mode change 2P pin (CN101). At the same time, short-circuit the automatic  
address pin (CN100) for 1 second or longer, then release it. (Be sure to perform this process for one system at a time. Automatic  
address settings cannot be performed for more than one system at the same time.)  
(Communication for automatic address setting begins, the compressors turn ON, and automatic address setting in Cooling  
mode begins.)  
(All indoor units operate.)  
* To cancel, again short-circuit the automatic address pin (CN100) for 1 second or longer, then release it.  
The LED that indicates automatic address setting is in progress turns OFF and the process is stopped. Be  
sure to perform automatic address setting again.  
(Automatic address setting is completed when the compressors stop and LEDs 1 and 2 on the outdoor main unit control PCB  
turn OFF.)  
7. At the outdoor main unit in the next (different) system, short-circuit the automatic address pin (CN100) for 1 second or longer,  
then release it.  
(Repeat the same steps to complete automatic address setting for all units.)  
8. Operation from the remote controllers is now possible.  
* Automatic address setting in Cooling mode cannot be done from the remote controller.  
Automatic Address Setting* from the Remote Controller  
Selecting each refrigerant system individually for automatic address setting  
---Automatic address setting for each system: Item code “A1”  
1. Press the remote controller timer time  
(Press and hold for 4 seconds or longer.)  
button and  
button at the same time.  
2. Next, press either the temperature setting  
(Check that the item code is “A1.)  
or  
button.  
3. Use either the  
address setting.  
or  
button to set the system No. to perform automatic  
4. Then press the  
button.  
(Automatic address setting for one refrigerant system begins.)  
(When automatic address setting for one system is completed, the system returns to  
normal stopped status.) <Approximately 4 – 5 minutes is required.>  
(During automatic address setting, “NOW SETTING” is displayed on the remote con-  
troller. This message disappears when automatic address setting is completed.)  
5. Repeat the same steps to perform automatic address setting for each successive system.  
78  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 79  
Display during automatic address setting  
G On outdoor main unit PCB  
1
2
LED  
* Do not short-circuit the automatic address setting pin (CN100) again while automatic address set-  
ting is in progress. Doing so will cancel the setting operation and will cause LEDs 1 and 2 to turn  
OFF.  
Blink alternately  
* When automatic address setting has been successfully completed, both LEDs 1 and 2 turn OFF.  
* LED 1 is D72. LED 2 is D75.  
* If automatic address setting is not completed successfully, refer to the table below and correct the problem. Then perform  
automatic address setting again.  
G Display details of LEDs 1 and 2 on the outdoor unit control PCB  
(
: ON  
: Blinking  
LED 2  
: OFF)  
Display meaning  
LED 1  
After the power is turned ON (and automatic address setting is not in progress), no communication with the indoor  
units in that system is possible.  
After the power is turned ON (and automatic address setting is not in progress), 1 or more indoor units are  
confirmed in that system; however, the number of indoor units does not match the number that was set.  
Automatic address setting is in progress.  
Alternating  
Automatic address setting completed.  
At time of automatic address setting, the number of indoor units did not match the number that was set.  
” (when indoor units are operating) indication appears on the display.  
Simultaneous  
Alternating  
Refer to “Table of Self-Diagnostic Functions and Description of Alarm Displays.”  
Note: “ ” indicates that the solenoid is fused or that there is a CT detection current failure (current is detected when the  
compressor is OFF).  
G Remote controller display  
is blinking  
79  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 80  
Request concerning recording the indoor/outdoor unit combination Nos.  
After automatic address setting has been completed, be sure to record them for future reference.  
List the outdoor main unit system address and the addresses of the indoor units in that system in an easily visible location (next to  
the nameplate), using a permanent marking pen or similar means that cannot be abraded easily.  
Example: (Outdoor) 1 – (Indoor) 1-1, 1-2, 1-3…  
(Outdoor) 2 – (Indoor) 2-1, 2-2, 2-3…  
These numbers are necessary for later maintenance. Please be sure to indicate them.  
Checking the indoor unit addresses  
Use the remote controller to check the indoor unit address.  
<If 1 indoor unit is connected to 1 remote controller>  
1. Press and hold the  
button and  
button for 4 seconds or longer (simple settings mode).  
2. The address is displayed for the indoor unit that is connected to the remote controller.  
(Only the address of the indoor unit that is connected to the remote controller can be checked.)  
3. Press the  
button again to return to normal remote controller mode.  
<If multiple indoor units are connected to 1 remote controller (group control)>  
1. Press and hold the button and button for 4 seconds or longer (simple settings mode).  
2. “ALL is displayed on the remote controller.  
3. Next, press the button.  
4. The address is displayed for 1 of the indoor units which is connected to the remote controller. Check that the fan of that indoor  
unit starts and that air is discharged.  
5. Press the  
6. Press the  
button again and check the address of each indoor unit in sequence.  
button again to return to normal remote controller mode.  
Number changes to indicate which indoor unit is currently selected.  
8-5. Remote Controller Test Run Settings  
1. Press the remote controller  
button for 4 seconds or longer. Then press the  
button.  
G “TEST RUN” appears on the LCD display while the test run is in progress.  
G The temperature cannot be adjusted when in Test Run mode.  
(This mode places a heavy load on the machines. Therefore use it only when performing the test run.)  
2. The test run can be performed using the HEAT, COOL, or FAN operation modes.  
Note: The outdoor units will not operate for approximately 3 minutes after the power is turned ON and after operation is  
stopped.  
3. If correct operation is not possible, a code is displayed on the remote controller LCD display.  
(Refer to “Table of Self-Diagnostic Functions” and correct the problem.)  
4. After the test run is completed, press the  
button again. Check that “TEST RUN” disappears from the LCD display.  
(To prevent continuous test runs, this remote controller includes a timer function that cancels the test run after 60 minutes.)  
* If the test run is performed using the wired remote controller, operation is possible even if the cassette-type ceiling panel has not  
been installed. (“P09” display does not occur.)  
80  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 81  
8-6. Caution for Pump Down  
Pump down means refrigerant gas in the system is returned  
to the outdoor unit. Pump down is used when the unit is to  
be moved, or before servicing the refrigerant circuit.  
(Refer to the Service Manual)  
G This outdoor unit cannot  
CAUTION  
collect more than the rated  
refrigerant amount as shown  
by the nameplate on the back.  
G If the amount of refrigerant is  
more than that recommended,  
do not conduct pump down. In  
this case use another  
refrigerant collecting system.  
81  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 82  
8-7. Meaning of Alarm Messages  
Table of Self-Diagnostics Functions and Description of Alarm Displays  
Alarm messages are indicated by the blinking of LED 1 and 2 (D72, D75) on the outdoor unit PCB. They are also displayed on  
the wired remote controller.  
G Viewing the LED 1 and 2 (D72 and D75) alarm displays  
LED 2  
Alarm contents  
LED 1  
Alarm display  
LED 1 blinks M times, then LED 2 blinks N times. The cycle then repeats.  
M = 2: P alarm 3: H alarm 4: E alarm 5: F alarm 6: L alarm  
N = Alarm No.  
Alternating  
Example: LED 1 blinks 2 times, then LED 2 blinks 17 times. The cycle then repeats.  
Alarm is "P17."  
(
: Blinking) Connect the outdoor maintenance remote controller to the RC socket on the outdoor main unit control PCB (3P, bl ue),  
and check the Alarm Messages on the remote controller display.  
Alarm  
message  
Possible cause of malfunction  
Error in receiving serial communication signal.  
(Signal from main indoor unit in case of group control)  
Ex: Auto address is not completed.  
Remote controller is detecting  
error signal from indoor unit.  
Serial  
communication  
errors  
<E01>  
Mis-setting  
<E02>  
Error in transmitting serial communication signal.  
Indoor unit is detecting error signal from remote controller (and system controller).  
<<E03>>  
Error in receiving serial communication signal.  
When turning on the power supply, the number of connected  
indoor units does not correspond to the number set. (Except R.C.  
address is “0.)  
Indoor unit is detecting error  
signal from main outdoor unit.  
E04  
Error of the main outdoor unit in receiving serial communication  
signal from the indoor unit.  
<E06>  
Improper setting of indoor unit or  
remote controller.  
Indoor unit address setting is duplicated.  
E08  
Remote controller address connector (RCU. ADR) is duplicated.  
(Duplication of main remote controller)  
<<E09>>  
Starting auto address setting is prohibited.  
This alarm message shows that the auto address connector CN100  
is shorted while other RC line is executing auto address operation.  
During auto address setting,  
number of connected units does  
not correspond to number set.  
E12  
Error in auto address setting. (Number of connected indoor units  
E15  
E16  
is less than the number set.)  
When turning on the power  
supply, number of connected  
units does not correspond to  
number set.  
Error in auto address setting. (Number of connected indoor units  
is more than the number set.)  
No indoor unit is connected during auto address setting.  
Main outdoor unit is detecting error signal from sub outdoor unit.  
Error of outdoor unit address setting.  
E20  
E24  
E25  
(Except R.C. address is “0.)  
The number of connected main and sub outdoor units do not  
E26  
E29  
E18  
L02  
correspond to the number set at main outdoor unit PCB.  
Error of sub outdoor unit in receiving serial communication signal  
from main outdoor unit.  
Error of main indoor unit in receiving serial communication signal  
from sub indoor units.  
This alarm message shows when an indoor unit for multiple-use  
is not connected to the outdoor unit.  
Indoor unit communication error  
of group control wiring.  
Improper setting.  
Duplication of main indoor unit address setting in group control.  
<L03>  
L04  
Duplication of outdoor R.C. address setting.  
There are 2 or more indoor unit  
controllers that have operation  
mode priority in refrigerant circuit.  
Priority set remote  
controller  
controller  
L05  
Non-priority set remote  
L06  
Group control wiring is connected to individual control indoor unit.  
Indoor unit address is not set.  
L07  
L08  
<<L09>>  
Capacity code of indoor unit is not set.  
L10  
L17  
Capacity code of outdoor unit is not set.  
Mis-matched connection of outdoor units that have different kinds  
of refrigerant.  
L18  
4-way valve operation failure  
Continued  
82  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 83  
Alarm  
message  
Possible cause of malfunction  
Protective device in indoor unit  
is activated.  
Activation of  
protective  
device  
Thermal protector in indoor unit fan motor is activated.  
<<P01>>  
Improper wiring connections of ceiling panel.  
Float switch is activated.  
<<P09>>  
<<P10>>  
P12  
Operation of protective function of fan inverter.  
Compressor thermal protector is activated.  
Protective device in outdoor unit  
Power supply voltage is unusual. (The voltage is more than 260 V  
or less than 160 V between L1 and L2 phase.)  
is activated.  
P02  
Incorrect discharge temperature. (Comp. No. 1)  
High pressure switch is activated.  
P03  
P04  
Negative (defective) phase.  
O2 sensor (detects low oxygen level) activated  
P05  
P14  
Compressor running failure resulting from missing phase in the  
compressor wiring, etc. (Start failure not caused by IPM or no gas.)  
P16  
Incorrect discharge temperature. (Comp. No. 2)  
P17  
P18  
P22  
Compressor 3 discharge temp. failure  
Outdoor unit fan motor is unusual.  
Overcurrent at time of compressor runs more than 80Hz (DCCT  
secondary current or ACCT primary current is detected at a time  
other than when IPM has tripped.)  
P26  
H31  
IPM trip (IPM current or temperature)  
Inverter for compressor is unusual. (DC compressor does not  
operate.)  
P29  
<<F01>>  
<<F02>>  
<<F03>>  
<<F10>>  
Indoor coil temp. sensor (E1)  
Indoor thermistor is either open  
or damaged.  
Thermistor  
fault  
Indoor coil temp. sensor (E2)  
Indoor coil temp. sensor (E3)  
Indoor suction air (room) temp. sensor (TA)  
Indoor discharge air temp. sensor (BL)  
<<F11>>  
F04  
Comp. No. 1 discharge gas temp. sensor (DISCH1)  
Comp. No. 2 discharge gas temp. sensor (DISCH2)  
Outdoor thermistor is either  
open or damaged.  
F05  
(EXG1)  
F06  
Outdoor No. 1 coil gas temp. sensor  
F07  
Outdoor No. 1 coil liquid temp. sensor  
(EXL1)  
F08  
Outdoor air temp. sensor (AIR TEMP)  
Compressor intake port temperature sensor (RDT)  
High pressure sensor. Negative (defective) N phase.  
Low-pressure sensor failure  
F12  
F16  
F17  
Compressor 3 discharge temp. sensor failure (DISCH3)  
F22  
Outdoor No. 2 coil gas temp. sensor (EXG2)  
F23  
F24  
Outdoor No. 2 coil liquid temp. sensor (EXL2)  
EEP ROM on indoor unit PCB failure  
F29  
Protective device for compressor  
No. 1 is activated.  
EEP ROM on the main or sub outdoor unit PCB has failed.  
F31  
Protective  
device for  
Current is not detected when comp. No. 1 is ON.  
H03  
compressor is  
activated  
Discharge gas temperature of the comp. No. 1 is not detected.  
Temp. sensor is not seated at the sensor holder.  
H05  
Overload current is detected.  
Lock current is detected.  
Current is not detected when comp. No. 2 is ON.  
Discharge gas temperature of comp. No. 2 is not detected.  
H11  
H12  
H13  
H15  
H21  
H22  
Protective device for compressor  
No. 2 is activated.  
Protective device for compressor Compressor No. 3 current trouble (overcurrent)  
No. 3 is activated.  
Compressor No. 3 current trouble (locked)  
Compressor No. 3 CT sensor disconnected or short circuit  
Compressor No. 3 discharge temp. sensor disconnected  
Low pressure switch is activated.  
H23  
H25  
H06  
Low oil level.  
H07  
H08  
H27  
H28  
Comp. No. 1 oil sensor  
Comp. No. 2 oil sensor  
Oil sensor (connection) failure  
Oil sensor fault.  
(Disconnection, etc.)  
Continued  
83  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 84  
Alarm messages displayed on system controller  
Indoor or main outdoor unit is not operating correctly.  
Mis-wiring of control wiring between indoor unit, main outdoor unit  
and system controller.  
Error in transmitting serial  
communication signal  
Serial  
communication  
errors  
C05  
C06  
Mis-setting  
Indoor or main outdoor unit is not operating correctly.  
Mis-wiring of control wiring between indoor unit, main outdoor unit  
and system controller.  
Error in receiving serial  
communication signal  
CN1 is not connected properly.  
When using wireless remote controller or system controller, in  
order to check the alarm message in detail, connect wired  
remote controller to indoor unit temporarily.  
Protective device of sub indoor  
unit in group control is activated.  
Activation of  
protective  
device  
P30  
NOTE  
1. Alarm messages in << >> do not affect other indoor unit operations.  
2. Alarm messages in < > sometimes affect other indoor unit operations depending on the fault.  
84  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 85  
9. APPENDIX  
9-1. 4-Way Air Discharge Semi-Concealed Type (X Type)  
NAME OF PARTS  
Water drain  
X type (4-WAY)  
X
Ceiling panel  
(optional)  
Air outlet  
(4 locations)  
Air intake grille  
(air intake)  
CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before  
cleaning.  
WARNING  
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-  
nents and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When clean-  
ing the air outlet side, be careful not to force the vanes out of place.  
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic  
CAUTION  
parts using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be  
especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
The air filter collects dust and other particles from the air and should be cleaned at regular intervals  
as indicated in the table below or when the filter indication ( ) on the display of the remote control  
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air  
conditioner drops greatly.  
Air filter  
Type  
Period  
6 months  
NOTE  
X
The frequency with which the filter should be cleaned depends on the environment in which the  
unit is used.  
<How to clean the filter>  
<How to remove the filter>  
1. Remove the air filter from the air intake grille.  
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the fil-  
ter in lukewarm, soapy water, rinse it in clean water, and dry it.  
1. Use a screwdriver to remove the bolt screw on each side for the two latches. (Be sure to  
reattach the two bolt screws after cleaning.)  
2. Press on the two latches of the air intake grille with your thumbs in the direction of the  
arrow to open the grille.  
3. Open the air intake grille downward.  
G When cleaning the air filter, never remove the safety chain. If it is necessary to remove it  
for servicing and maintenance inside, be sure to reinstall the safety chain securely (hook  
on the grille side) after the work.  
CAUTION  
G When the filter has been removed, rotating parts (such as the fan), electrically charged  
areas, etc. will be exposed in the unit’s opening. Bear in mind the dangers that these parts  
and areas pose, and proceed with the work carefully.  
85  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 86  
4. Remove the air filter attached to the air intake grille.  
Latch  
X
Safety chain  
Air filter  
Air intake  
grille  
Bolt screws  
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled  
improperly; special care should be taken when you clean these parts.  
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt  
or soot.  
CAUTION  
3. The internal coil and other components of the outdoor unit must also be cleaned periodi-  
cally. Consult your dealer or service center.  
Care: After a prolonged idle period  
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a  
blockage, remove it.  
Operate the fan for half a day to dry out the inside.  
Care: Before a prolonged idle period  
Disconnect the power supply and also turn off the circuit breaker.  
Clean the air filter and replace it in its original position.  
Outdoor unit internal components must be checked and cleaned periodically. Con-  
tact your local dealer for this service.  
TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit  
will not work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Do  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
86  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 87  
9-2. 1-Way Air Discharge Semi-Concealed Type (A Type)  
NAME OF PARTS  
SEMI-CONCEALED  
A type (1-WAY)  
Water drain  
Air outlet  
Air intake  
A
Ceiling panel  
(optional)  
CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power  
WARNING  
before cleaning.  
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-  
nents and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When cleaning  
the air outlet side, be careful not to force the vanes out of place.  
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe  
CAUTION  
plastic parts using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if handled improperly;  
be especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
The air filter collects dust and other particles from the air and should be cleaned at regular intervals  
as indicated in the table below or when the filter indication ( ) on the display of the remote control  
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air  
conditioner drops greatly.  
Air filter  
Type  
A
Period  
2 weeks  
The frequency with which the filter should be cleaned depends on the environment in which the unit is used.  
NOTE  
<How to clean the filter>  
Air filter finger-hold  
Air intake grill  
1. Remove the air filter from the air intake grille.  
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter,  
wash the filter in lukewarm, soapy water, rinse it in clean water, and dry it.  
Air filter  
<How to remove the filter>  
1-way air discharge semi-concealed type (A):  
1. Take hold of the finger-hold on the air intake grille and press it to  
the rear, and the grille will open downward.  
Hook  
Screw  
Latch  
2. Take hold of the finger-hold on the air filter, pull it toward you.  
Screw  
Air filter finger-hold  
*Take hold of the finger-hold on the air filter, pull it toward you.  
87  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 88  
Outdoor unit  
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled  
improperly; special care should be taken when you clean these parts.  
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt  
or soot.  
CAUTION  
3. The internal coil and other components of the outdoor unit must also be cleaned  
periodically. Consult your dealer or service center.  
Care: After a prolonged idle period  
Care: Before a prolonged idle period  
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a  
blockage, remove it.  
A
Operate the fan for half a day to dry out the inside.  
Disconnect the power supply and also turn off the circuit breaker.  
Clean the air filter and replace it in its original position.  
Outdoor unit internal components must be checked and cleaned periodically.  
Contact your local dealer for this service.  
TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit  
will not work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Do  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
88  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 89  
9-3. Concealed Duct (High-Static Pressure) Type (U, D Type)  
NAME OF PARTS  
CONCEALED DUCT  
CONCEALED DUCT  
U type (standard static pressure)  
D type (high static pressure)  
Air intake  
sideduct flange  
(rear)  
Flexible duct  
(optional)  
Water drain  
Water drain  
Canvas duct  
(optional)  
Electrical box  
U
D
Air intake grille  
(air intake)  
(optional)  
Air outlet side  
duct flange  
Air outlet grille  
(optional)  
CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before  
cleaning.  
WARNING  
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-  
nents and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When clean-  
ing the air outlet side, be careful not to force the vanes out of place.  
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic  
CAUTION  
parts using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be  
especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
*Concealed duct type (U, D):  
Type  
Period  
An air filter is not provided with this air conditioner at the time of shipment. To get clean air  
U, D*  
(Depends on filter  
specifications)  
and to extend the service life of the air conditioner, an air filter must be installed in the air  
intake. For installation and cleaning the air filter, consult your dealer or service center.  
NOTE  
The frequency with which the filter should be cleaned depends on the environment in which the unit is used.  
<How to clean the filter>  
1. Remove the air filter from the air intake grille.  
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the filter in lukewarm, soapy water,  
rinse it in clean water, and dry it.  
89  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 90  
TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
U
D
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit  
will not work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Do  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
90  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 91  
9-4. Ceiling-Mounted Type (T Type)  
NAME OF PARTS  
CEILING-MOUNTED  
T type  
Air outlet  
Water drain  
(Drain pipe can be  
connected to either  
the left or right side.)  
Air intake  
grille (air  
intake)  
CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before  
cleaning.  
WARNING  
2. Do not pour water on the indoor unit to clean it. This will damage the internal  
components and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When clean-  
ing the air outlet side, be careful not to force the vanes out of place.  
T
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic  
CAUTION  
parts using very hot water.  
2. Some metal edges and the fins are sharp and may cause injury if handled improperly; be  
especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
The air filter collects dust and other particles from the air and should be cleaned at regular intervals  
as indicated in the table below or when the filter indication ( ) on the display of the remote control  
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air  
conditioner drops greatly.  
Air filter  
Type  
Period  
NOTE  
T
2 weeks  
The frequency with which the filter should be cleaned depends on the environment in which the  
unit is used.  
<How to clean the filter>  
1. Remove the air filter from the air intake  
grille.  
2. Use a vacuum cleaner to remove light  
dust. If there is sticky dust on the filter,  
wash the filter in lukewarm, soapy water,  
Air filter finger-hold  
Air intake grill  
rinse it in clean water, and dry it.  
<How to remove the filter>  
1. Take hold of the finger-hold on  
the air intake grille and press it  
to the rear, and the grille will  
open downward.  
Air intake grill  
finger-hold  
Screw  
Air filter  
Hook  
Screw  
2. Take hold of the finger-hold on  
the air filter, pull it toward you.  
Latch  
Air filter finger-hold  
* Take hold of the finger-hold on the air filter, pull it toward you.  
91  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 92  
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled  
CAUTION  
improperly; special care should be taken when you clean these parts.  
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt  
or soot.  
3. The internal coil and other components of the outdoor unit must also be cleaned periodi-  
cally. Consult your dealer or service center.  
Care: After a prolonged idle period  
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a  
blockage, remove it.  
Operate the fan for half a day to dry out the inside.  
Care: Before a prolonged idle period  
Disconnect the power supply and also turn off the circuit breaker.  
Clean the air filter and replace it in its original position.  
Outdoor unit internal components must be checked and cleaned periodically. Con-  
tact your local dealer for this service.  
TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
T
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit will not  
work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Do  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
92  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 93  
9-5. Wall-Mounted Type (K Type)  
NAME OF PARTS  
K Type (Wall-Mounted)  
Air intake  
Air outlet  
CARE AND CLEANING  
1. For safety, be sure to turn the air conditioner off and also to disconnect the power before  
cleaning.  
WARNING  
2. Do not pour water on the indoor unit to clean it. This will damage the internal compo-  
nents and cause an electric shock hazard.  
Air intake and outlet side Clean the air intake and outlet side of the indoor unit with a vacuum cleaner brush, or wipe them  
(Indoor unit) with a clean, soft cloth.  
If these parts are stained, use a clean cloth moistened with a mild liquid detergent. When clean-  
ing the air outlet side, be careful not to force the vanes out of place.  
1. Never use solvents or harsh chemicals when cleaning the indoor unit. Do not wipe plastic  
parts using very hot water.  
CAUTION  
2. Some meta l edges and the fins are sharp and may cause injury if handled improperly; be  
especially careful when you clean these parts.  
3. The internal coil and other components of the outdoor unit must be cleaned every year.  
Consult your dealer or service center.  
The air filter collects dust and other particles from the air and should be cleaned at regular intervals  
K
Air filter  
as indicated in the table below or when the filter indication ( ) on the display of the remote control  
unit (wired type) shows that the filter needs cleaning. If the filter gets blocked, the efficiency of the air  
conditioner drops greatly.  
NOTE  
Type  
Period  
K
2 weeks  
The frequency with which the filter should be cleaned depends on the environment in which the  
unit is used.  
<How to clean the filter>  
1. Remove the air filter from the air intake grille.  
2. Use a vacuum cleaner to remove light dust. If there is sticky dust on the filter, wash the filter in  
lukewarm, soapy water, rinse it in clean water, and dry it.  
<How to remove the filter>  
1. Move the flap on the air outlet grille to its lowest position with the remote control unit.  
2. The filter is disengaged by pushing the tab up gently. Hold the air filter by the tab at the bottom,  
and pull downward.  
Air intake grille  
Air filter  
When replacing the filter, make sure that the FRONT mark is facing you.  
Push it up until you hear it click back into position.  
93  
07-007 W-2WAY_II_NA 1/23/07 6:09 PM Page 94  
1. Certain metal edges and the condenser fins are sharp and may cause injury if handled  
CAUTION  
improperly; special care should be taken when you clean these parts.  
2. Periodically check the outdoor unit to see if the air outlet or air intake is clogged with dirt  
or soot.  
3. The internal coil and other components of the outdoor unit must also be cleaned periodi-  
cally. Consult your dealer or service center.  
Care: After a prolonged idle period  
Check the indoor and outdoor unit air intakes and outlets for blockage; if there is a  
blockage, remove it.  
Operate the fan for half a day to dry out the inside.  
Care: Before a prolonged idle period  
Disconnect the power supply and also turn off the circuit breaker.  
Clean the air filter and replace it in its original position.  
Outdoor unit internal components must be checked and cleaned periodically. Con-  
tact your local dealer for this service.  
TROUBLESHOOTING  
If your air conditioner does not work properly, first check the following points before requesting service. If it still does not work  
properly, contact your dealer or a service center.  
Possible Cause  
Trouble  
Remedy  
Air conditioner does not run at all  
1. Power failure.  
1. After a power outage, press ON/OFF operation button  
on the wired remote control unit.  
2. Leakage circuit breaker has tripped.  
3. Line voltage is too low.  
2. Contact service center.  
3. Consult your electrician or dealer.  
4. Press the button again.  
4. Operation button is turned off.  
heat pump is  
5. The wired remote control unit or  
5. Consult your dealer.  
malfunctioning.  
(The inspection mark  
and the letters E, F,  
combination with numbers appear  
H, L, P in  
K
remote control unit.)  
on the LCD of the wired  
Compressor runs but soon stops  
1. Obstruction in front of condenser coil  
1. Remove obstruction  
Poor cooling (or heating) performance 1. Dirty or clogged air filter.  
1. Clean air filter to improve the airflow.  
2. Eliminate heat source if possible.  
3. Shut them to keep the heat (or cold) out.  
4. Remove it to ensure good airflow.  
room.  
2. Heat source or many people in  
3. Doors and/or windows are open.  
4. Obstacle near air intake or air discharge port.  
5. Thermostat is set too high for cooling  
5. Set the temperature lower (or higher).  
(or too low for heating).  
6. (Defrosting system does not work.)  
6. (Consult your dealer.)  
Tips for Energy Saving  
Do not block the air intake and outlet of the unit. If either is obstructed, the unit will not  
work well, and may be damaged.  
Do not let direct sunlight into the room. Use sunshades, blinds or curtains. If the walls  
and ceiling of the room are warmed by the sun, it will take longer to cool the room.  
Avoid  
Do  
Always try to keep the air filter clean. (Refer to “Care and Cleaning.) A clogged filter  
will impair the performance of the unit.  
To prevent conditioned air from escaping, keep windows, doors and any other openings  
closed.  
Should the power fail while the unit is running  
If the power supply for this unit is temporarily cut off, the unit will automatically resume operation once power is  
restored using the same settings before the power was interrupted.  
NOTE  
94  

Minolta All In One Printer Cf2002 User Manual
Mitsubishi Electronics Peh 15mya User Manual
Panasonic Kx Pw601dl User Manual
Polycom Answering Machine Cx7000 User Manual
Sharp 66129902992 User Manual
Sharp Cv P10lc User Manual
Sharp Mx C401 User Manual
Toshiba Lf600 User Manual
Trion Air Boss 60 User Manual
Xerox Synergix 8850 User Manual